Project Name: SPEEA
MECHANICAL PERMIT
Permit Number: M14-0176
Issue Date: 9/29/2014
Permit Expires On: 3/28/2015
Owner:
Name:
Address:
Contact Person:
Name:
Address:
Contractor:
Name:
Address:
License No:
Lender:
Name:
Address:
SPEEA PROPERTIES
15205 52ND AVE S , SEATTLE, WA,
98188
KEITH RICE
7717 DETROIT AVE SW , SEATTLE, WA,
98106
MACDONALD MILLER FACIL SOLUTIO
PO BOX 47983 , SEATTLE, WA, 98146-
7983
Phone: (206) 407-2676
Phone: (206) 768-4180
MACDOFS980RU Expiration Date:
DESCRIPTION OF WORK:
INSTALL (1) SPLIT SYSTEM, INSTALL (1) EXHAUST FAN WITH ASSOCIATED LOUVER AND BACKDRAFT DAMPER.
INSTALL (2) RETURN GRILLES AND MISC DUCT WORK PER PLANS.
Valuation of Work: $6,500.00
Type of Work: REPLACEMENT
Fuel type: ELECT
Fees Collected: $285.10
Electrical Service Provided by: SEATTLE CITY LIGHT
Water District: 125
Sewer District: TUKWILA SEWER SERVICE
Current Codes adopted by the City of Tukwila:
International Building Code Edition:
International Residential Code Edition:
International Mechanical Code Edition:
Uniform Plumbing Code Edition:
2012
2012
2012
2012
International Fuel Gas Code:
WA Cities Electrical Code:
WA State Energy Code:
2012
2014
2012
Permit Center Authorized Signature:
Date: Q i (VIM
I hearby certify that I have read and examined this permit and know the same to be true and correct. All
provisions of law and ordinances governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other
state or local laws regulating construction or the performance of work. I am authorized to sign and obtain this
development permit and agree to the conditions attached to this permit.
Signature: /�-� y \ ��-L ti Date: 9'/2 I/Li
Print Name: ak ` cCS -e
This permit shall become null and void if the work is not commenced within 180 days for the date of issuance, or if
the work is suspended or abandoned for a period of 180 days from the last inspection.
PERMIT CONDITIONS:
1: Work shall be installed in accordance with the approved construction documents, and any changes made
during construction that are not in accordance with the approved construction documents shall be
resubmitted for approval.
2: All permits, inspection record card and approved construction documents shall be kept at the site of work
and shall be open to inspection by the Building Inspector until final inspection approval is granted.
3: Readily accessible access to roof mounted equipment is required.
4: All construction shall be done in conformance with the Washington State Building Code and the
Washington State Energy Code.
5: Remove all demolition rubble and loose miscellaneous material from lot or parcel of ground, properly cap
the sanitary sewer connections, and properly fill or otherwise protect all basements, cellars, septic tanks,
wells, and other excavations. Final inspection approval will be determined by the building inspector based
on satisfactory completion of this requirement.
6: All plumbing and gas piping work shall be inspected and approved under a separate permit issued by the
City of Tukwila Building Department (206-431-3670).
7: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila
Permit Center.
8: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an
approval of, any violation of any of the provisions of the building code or of any other ordinances of the City
of Tukwila. Permits presuming to give authority to violate or cancel the provisions of the code or other
ordinances of the City of Tukwila shall not be valid. The issuance of a permit based on construction
documents and other data shall not prevent the Building Official from requiring the correction of errors in
the construction documents and other data.
9: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila
Permit Center (206/431-3670).
PERMIT INSPECTIONS REQUIRED
Permit Inspection Line: (206) 438-9350
0703 MECH EQUIP EFF
1800 MECHANICAL FINAL
0705 REFRIGERATION EQUIP
0701 ROUGH -IN MECHANICAL
CITY OF TUKWW..A
Comm unity Development Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http://www.TukwilaWA.gov
MECHANICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
**please print**
King Co Assessor's Tax No.: 1157200016
Site Address: 15205 52ND AVE S TUKWILA, WA 98188 Suite Number: Floor: 1 & 2
Tenant Name: SPEEA New Tenant: ❑ Yes O..No
PROPERTY OWNER
Name: SPEEA
Address: 15205 52ND AVE S
City: TUKWILA
State: WA
Zip: 98188
CONTACT PERSON — person receiving all project
communication
Name: KEITH RICE
Address: 7717 DETROIT AVE SW
City: SEATTLE State: WA Zip: 98106
Phone: (206) 407-2676 Fax: (206) 407-2677
Email: keith.rice@macmiller.com
MECHANICAL; CONTRACTORINFORMATION t,.'
Company Name: MACDONALD MILLER
Address: 7717 DETROIT AVE SW
City: SEATTLE State: WA Zip: 98106
Phone: (206) 768-4278 Fax: (206) 768-4279
Contr Reg No.: MACDOFS980RU Exp Date: 01/03/2015
Tukwila Business License No.: BUS-0100868
1L/69.1,
9/0,1g (10.tCY2)
4Q-10
Valuation of project (contractor's bid price): $ 6,500
Describe the scope of work in detail:
INSTALL (1) SPLIT SYSTEM, INSTALL (1) EXHAUST FAN WITH ASSOICATED LOUVER & BACKDRAFT DAMPER.
INSTALL (2) RETURN GRILLES AND MISC DUCT WORK PER PLANS.
Use: Residential: New ❑ Replacement ❑
Commercial: New ❑ Replacement
Fuel Type: Electric 0 Gas ❑
?s-(ti-{
Other:
H:\Applications\Forms-Applications On Line\2011 Applications\Mechanical Permit Application Revised 8-9-11.docx
Revised: August 2011
bh
Page 1 of 2
Indicate type of mechanical work being installed and the quantity below:
Unit Type
Qty
Furnace <100k btu
Furnace > l 00k btu
Floor furnace
Suspended/wall/floor
mounted heater
Appliance vent
Repair or addition to
heat/refrig/cooling
system
Air handling unit
<10,000 cfm
Unit Type
Qty
Air handling unit
>10,000 cfm
Evaporator cooler
Ventilation fan
connected to single duct
Ventilation system
Hood and duct
Incinerator — domestic
Incinerator —
comm/industrial
Unit Type
Qty
Fire damper
Diffuser
3
Thermostat
Wood/gas stove
Emergency generator
Other mechanical
equipment
2
Boiler/Compressor
Qty
0-3 hp/100,000 btu
3-15 hp/500,000 btu
15-30 hp/1,000,000 btu
30-50 hp/1,750,000 btu
50+ hp/1,750,000 btu
PERMIT APPLICATIONNOTE
Value of construction — in all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the permit center to comply with current fee schedules.
Expiration of plan review — applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The building official may grant one extension of time for additional periods not to exceed 90 days each. The extension shall be requested in writing
and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWNER OR AUTHORIZED AGENT:
Signatur �— _�' Date: 09/09/2014
Print Name: DARLA DOLL Day Telephone: (206) 768-4278
Mailing Address: 7717 DETROIT AVE SW SEATTLE WA 98106
City State Zip
H:\Applications\Forms-Applications On Line \2011 Applications\Mechanical Permit Application Revised 8-9-11.docx
Revised: August 2011
bh
Page 2 of 2
Cash Register Receipt
City of Tukwila
DESCRIPTIONS
h, � ,:,,,,, ^„
PermitTRAK
ACCOUNT I QUANTITY
� a
4 � }ram G ?i" k �H, .. _. r
PAID
J�'n
N $242.84
g
0
�`t M14 0176 Address 1520$52ND AVE 5
d�fb't'+�
Apn: 1157200016Y
r ^ $242.84
MECHANICAL
$233.50
PERMIT FEE
R000.322.100.00.00
0.00
$186.80
PLAN CHECK FEE
R000.322.102.00.00
0.00
$46.70
TECHNOLOGY FEE
$9.34
TECHNOLOGY FEE
TOTAL FEES PAID BY RECEIPT: R3095
R000.322.900.04.00
0.00
$9.34
$242.84
Date Paid: Wednesday, September 10, 2014
Paid By: MACDONALD-MILLER
Pay Method: CHECK 4032
Printed: Thursday, September 18, 2014 8:40 AM 1 of 1
CSYSTEMS
DESCRIPTIONS
ermltTRAK
Cash Register Receipt
City of Tukwila
ACCOUNT QUANTITY
PAID
2.26
14-0176 Address: 15205 52ND AVE
n: 1157200016
2
MECHANICAL
$40.63
PERMIT ISSUANCE BASE FEE
R000.322.100.00.00
0.00
$32.50
PLAN CHECK FEE
R000.322.102.00.00
0.00
$8.13
TECHNOLOGY FEE
$1.63 !;
TECHNOLOGY FEE
TOTAL FEES PAID BY RECEIPT: R3175
R000.322.900.04.00
0.00
$1.63
$42.26
Date Paid: Monday, September 29, 2014
Paid By: MACDONALD-MILLER FACILITY SOLU
Pay Method: CHECK 4045
Printed: Monday, September 29, 2014 12:10 PM 1 of 1
I?SYSTEMS
CITY FORM NO 1 1912 ADOPTED BY DIVISION OF MUNICIPAL CORPORATIONS.
W1Lq
(Ste
2
CITY OF TUKWILA
TREASURER'S RECEIPT NE 47843
0 i
Date �� 1. 20 4
/
1908d '
Receiveof 104LVi Oh\. 1 A ' ,AA \A V , 2,
� V }` 1�ry f ('DollarsFc)K 7 14 (;P
Krk,
eiYrMI _
0 00 , ° I--.
l iP
I�1-1
w.
LiUt
-G b00 . 9-2- , W 2-
o
.
r (Lk T L 600 , )7"2- -. q00
• ( . O .
lij-
TOTAL
2L10.—
q9
BY AiettAIC %
(
DEPT: Ol.%jam
WHITE - Finance Dept. CANARY - Customer PINK - File
,J$
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 431-2451
Project:.
c)P,e_e
Type of inspe Lion:
i t(tAA
,
, t✓
1'
AdIrs fl y
2.4�
5 2,
f(e
Date Called:
Jco 06ft
1 A/
Special Instructions:
/
k.�' \X
Date Wanted:
(a.m.-
p.m.
Requester:
hone No: 3 t —
& r}
V
ElApproved per applicable codes.
Corrections required prior to approval.
COMMENTS:
CTM 1 AA (} c) P
f
Date:o ZZ_t
REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
4*-(
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO, PERMIT NO,
CITY OF TUKWILA BUILDING DIVISION C/
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 431-2451
Project:
25PP. A-
Type of Inspection:
i c_.frr,4P ► A71—:0h/
Address: AI
Date Called:
Special Instructions: �� �,�/��
jp(A4l, r r, s ST? Al`14
pA.
2. r9J'' t :lies
Li..5
Date Wanted:
"_ (O — CO '' 4 4
! ,a.m
p.m.
Requester:
Phone No:
Approved per applicable codes.
QCorrections required prior to approval.
COMMENTS:
Inspector:
1
Date:
It/ l
n REINSPECTION FEE REQUIRED. Prior to next inspection. fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
PERMIT COORD COPY
PLAN REVIEW/ROUTING SLIP
PERMIT NUMBER: M14-0176
PROJECT NAME: SPEEA
DATE: 09/10/2014
SITE ADDRESS: 15205 52 AVE S
X Original Plan Submittal
Response to Correction Letter #
Revision # before Permit Issued
Revision # after Permit Issued
DEPARTMENTS:
ft-T oO L& t1
Building Division
Public Works
AW' IA- D '\1 I i
Fire Prevention
Structural
n
Planning Division
Permit Coordinator
PRELIMINARY REVIEW:
Not Applicable n
(no approval/review required)
DATE: 09/16/14
Structural Review Required
REVIEWER'S INITIALS: DATE:
n
APPROVALS OR CORRECTIONS: DUE DATE: 10/14/14
Approved
Corrections Required
El
(corrections entered in Reviews)
Approved with Conditions
Denied
(ie: Zoning Issues)
Notation:
REVIEWER'S INITIALS:
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
12/18/2013
MACDONALD/MILLER FAC SOI TNC
Page 1 of 3
Washington State Department of
Labor & Industries
MACDONALD/MILLER FAC SOL INC
Owner or tradesperson
SIMONDS, DERRICK R
Principals
SIMONDS, DERRICK R, PRESIDENT
WEBSTER, MARK E, VICE PRESIDENT
NOEL, STEPHANIE W, MEMBER
SIGMUND, FREDRIC, PRESIDENT
(End: 01/04/2011)
LOVELY, STEVE C, VICE PRESIDENT
(End: 01/04/2011)
HACK, RICHARD, SECRETARY
(End: 01/04/2011)
KOPET, TYLER, TREASURER
(End: 01/04/2011)
TURLEY, DOUGLAS, CHIEF EXECUTIVE
OFFICER
(End: 01/04/2011)
TURLEY, DOUGLAS, CHIEF OPERATING
OFFICER
(End: 01/04/2011)
GOUGH, DAVID ANTHONY, DIRECTOR
(End: 08/29/2014)
Doing business as
MACDONALD/MILLER FAC SOL INC
WA UBI No.
602 254 260
PO BOX 47983
SEATTLE, WA98106
206-768-4180
KING County
Business type
Corporation
License
Verify the contractor's active registration / license / certification (depending on trade) and any past violations.
Construction Contractor
License specialties
GENERAL
License no.
MACDOFS980RU
Effective — expiration
12/31 /2002— 01 /03/2015
Active.
Meets current requirements.
https://secure.lni.wa.gov/verify/Detail.aspx?UBI=602254260&LIC=MACDOFS980RU&SAW= 09/29/2014
J:\7314\6795 SPEEA — TAB
04, 2014 4:00:41 PM
Thursday, September
ABBV
A
AC
AD
AFF
AL
BDD
BOB
BOD
BOTT
BTU
BTUH
BWG
BWR
C
CAP
CC
CFM
CHWR
CHWS
COMB
CONN
CWR
CWS
DB
DIFF
DMPR
DN
EC
EGG
EER
ELEV
EMS
FULL NAME
COMPRESSED AIR LINE
AIR CONDITIONING UNIT
ACCESS DOOR (WALUROOFIDUCT - SEE DRAWING)
ABOVE FINISHED FLOOR
ALUMINUM
BACKDRAFT DAMPER
BOTTOM OF BEAM
BOTTOM OF DUCT
BOTTOM
BRITISH THERMAL UNITS
BRITISH THERMAL UNITS PER HOUR
BOTTOM WALL GRILLE
BOTTOM WALL REGISTER
CONDENSATE
CAPACITY
CONTROLS CONTRACTOR
CUBIC FEET PER MINUTE
CHILLED WATER RETURN
CHILLED WATER SUPPLY
COMBUSTION
CONNECT
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
DUCT BOARD
DIFFUSER
DAMPER
DOWN
ELECTRICAL CONTRACTOR
EGGCRATE
ENERGY EFFICIENCY RATIO
ELEVATION
ENERGY MANAGEMENT SYSTEM
ABBV
ESP
EXH
EXTR
FAC
FD
FLA
FOB
FOT
FRD
FSD
G
GALV
GC
GPM
GR
GWB
HG
HP
HWR
HWS
ID
INT
LIQ
M-M
MBH
MC
MCA
MD
MIN
MT
MUA
NOM
FULL NAME
EXTERNAL STATIC PRESSURE
EXHAUST
EXTRACTOR
FIRE ALARM CONTRACTOR
FIRE DAMPER
FULL LOAD AMPS
FLAT ON BOTTOM
FLAT ON TOP
FRICTION DAMPER
FIRE SMOKE DAMPER
GAS LINE
GALVANIZED
GENERAL CONTRACTOR
GALLONS PER MINUTE
GRILLE
GYPSUM WALL BOARD
HOT GAS LINE
HORSE POWER
HOT WATER RETURN
HOT WATER SUPPLY
INSIDE DIMENSION
INTERLOCK
LIQUID LINE
MACDONALD-MILLER
ONE THOUSAND BTUH
MECHANICAL CONTRACTOR
MINIMUM CIRCUITAMPACITY
MOTORIZED DAMPER
MINIMUM
MOUNT
MAKE-UP AIR
NOMINAL
ABBV
OSA
OBD
OD
RA
REG
REQ'D
RIO
SA
SCD
SD
SL
SM
SP
SS
SSSC
STL
SUC
SUSP
T'STAT
TC
TOD
TOS
TV
TWG
TWR
TYP
UNO
VD
VFD
0
FULL NAME
OUTSIDE AIR
OPPOSED BLADE DAMPER
OUTSIDE DIMENSION
RETURN AIR
REGISTER (GRILLE WITH DAMPER)
REQUIRED
ROUGH IN ONLY
SUPPLY AIR
SMOKE CONTROL DAMPER
SMOKE DAMPER
SOUND LINING
SHEET METAL
STATIC PRESSURE
START/STOP
SOLID STATE SPEED CONTROLLER
STEEL
SUCTION LINE
SUSPENDED
THERMOSTAT
TEMPERATURE CONTROL
TOP OF DUCT
TOP OF STEEL
TURN VANES
TOP WALL GRILLE
TOP WALL REGISTER
TYPICAL
UNLESS NOTED OTHERWISE
VOLUME DAMPER
VARIABLE FREQUENCY DRIVE
VOLTAGE PHASE & DUCT DIAMETER
DESCRIPTION
SYMBOL
DESCRIPTION
SYMBOL
BARE SHEETMETAL
14x12
ROUND SHEETMETAL WRAPPED W/ INSULATION (2")
120W
SOUNDLINE SHEETMETAL (1" LINING)
14x12SL
CLEANROOM QUALITY DUCTWORK
14x12C
SHEETMETAL WRAPPED W/ INSULATION (2")
14x12W
BARE FLAT OVAL SHEETMETAL
14x120
BARE ROUND SHEETMETAL
120
FLAT OVAL FLAT SHEETMETAL W/ INSULATION (2")
14x120W
EXPOSED QUALITY SHEETMETAL
14x12Q
DUCTBOARD (1" FIBERGLASS)
14x12DB
EXAMPLE OF NEW
1 4x1 2
EXAMPLE OF NOT IN CONTRACT (NIC)
14x12
EXAMPLE OF DEMO
EXAMPLE OF EXISTING
xxxXXXX
1 4X 12
FLEX DUCT
FLEX CONNECTOR
-%nnnnr-
SYMBOL
MANUFACTURER & MODEL NUMBER
SIZE
TYPE
NOTES
SIZE
\JCFM
SHOEMAKER 701-MA
AS NOTED
T-BAR LAY -IN DIFFUSER
M-M METAL EGGCRATE
12/24
RETURN/EXH
M-M METAL EGGCRATE
24/24
RETURN/EXH
UNIT
NO.
EF-1
AREA SERVED
AN CLOSET
MFG & MODEL NO.
BROAN L150
TYPE
IN -LINE
CFM
157
ESP
0.125
RPM
710
FLA
1.3
HP
VOLT/PH
11511
BDD
YES
WT
LBS
23.1
NOTES
NEW, 1-6
n
NOTES:
1. POWER WIRING AND DISCONNECT SWITCH BY ELECTRICAL CONTRACTOR.
2. MOTOR STARTER BY ELECTRICAL CONTRACTOR.
3. SPRING ISOLATORS.
4. LOW NOISE CONSTRUCTION
5. CONNECT TO LINE VOLTAGE THERMOSTAT, HIGH TEMP - MOUNT AT 48" AFF, SET AT 80° F
6. CONNECT TO NEW EXTERIOR WALL EXHAUST TERMINATION, WITH BACKDRAFT DAMPER
UNIT
NO.
MANUFACTURER
INDOOR UNIT
OUTDOOR UNIT
MODEL
NOM.
TONS
CFM
HSPF/
SEER
ELECTRIC
VOLT/PH
AL WT
MCA LBS
MODEL
ELECTRIC
CFM VOLT/PH
AL WT
MCA LBS
NOTES
AHU-1, CU-1
FUJITSU
ASU12RL2
400 16.00
115
1.0 16
AOU12RL2
1013
115
15.0
69
1,2,3,4,5
NOTES:
1. PROVIDE WITH T'STAT (MT. ON WALL), WHITE FINISH, CONDENSATE PUMP
2. INSTALL IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS AND DETAILS ON DRAWINGS.
3. PROVIDE 3/4" TYPE L COPPER CONDENSATE DRAIN TO BUILDING EXTERIOR
4. INDOOR UNITS FACTORY WIRED AND CIRCUIT PROTECTED FOR SINGLE POINT ELECTRICAL CONNECTION.
5. CONFIRM EQUIPMENT VOLTAGES ON SITE, CONFIRM SINGLE PHASE PRIOR TO EQUIPMENT ORDER.
UNIT
NO. MFG & MODEL NO.
HP-1 TRANE 4WCC3048A3000A
HP-2 TRANE 4WCC3030B1000A
HP-3 TRANE 4WCC3024B1000A
NOM
TONS
4.0
2.5
2.0
HEAT
MBH
47.0
28.0
22.0
CFM
1600
1000
800
ESP
0.5
0.5
0.5
FAN
HP
3/4
1/2
1/2
OA
CFM
240
150
HP-4
HP-5
TRANE 4WCC3024B1000A
TRANS 4WCC303061000A
/ i \ HP-6 TRANE 4WCC3030B1000A
HP-7 TRANE 4WCC3030B1000A
2.0
2.5
2.5
2.5
22.0
28.0
28.0
28.0
800
1000
1000
1000
0.5
0.5
0.5
0.5
1/2
1/2
1/2
1/2
120
120
150
150
150
HSPF/
COP
7.7/
7.7/
8.0/
8.0/
7.7/
7.7/
7.7/
EER/
SEER
/13.0
/13.0
/13.0
ELECTRICAL
VOLT/PH AUX HTR KW
208/3
208/1
208/1
7.5
6.0
3.8
MCA
54.0
61.0
39.0
WT
LBS
425
321
357
NOTES
EXIST
EXIST
EXIST
/13.0
/13.0
/13.0
208/1
208/1
208/1
208/1
3.8
6.0
6.0
39.0
45.0
61.0
61.0
357
321
321
321
EXIST
EXIST
EXIST
EXIST
NOTES:
. THESE PLANS ARE SCHEMATIC AND DO NOT SHOW EXACT ROUTING OR EVERY OFFSET WHICH MAY BE REQUIRED. THE HVAC CONTRACTOR IS TO COORDINATE WITH ALL OTHER
TRADES AND IS TO VERIFY ALL CLEARANCES BEFORE COMMENCING WORK.
2. MATERIALS, METHODS, AND INSTALLATION SHALL COMPLY WITH THE PROVISIONS OF THE 2012 EDITIONS OF THE INTERNATIONAL MECHANICAL CODE, INTERNATIONAL BUILDING
CODE, INTERNATIONAL FIRE CODE AND STATE AND LOCAL CODES AND ORDINANCES.
3. DUCT CONSTRUCTION AND HANGING SHALL COMPLY WITH CHAPTER 6 OF THE 2012 IMC AND WITH CURRENT SMACNA STANDARDS. EARTHQUAKE BRACE ALL DUCTS 28" DIA
AND LARGER WHICH ARE SUSPENDED MORE THAN 12" BELOW STRUCTURAL SYSTEM.
4. JOINTS OF MEDIUM AND HIGH VELOCITY DUCT SYSTEMS SHALL BE SEALED WITH GASKETS OR LISTED MASTIC TYPE DUCT SEALANT.
5. DUCTS SHALL BE INSULATED AS INDICATED ON PLANS, PER 2012 WSEC.
- DUCT WRAP, WHERE INDICATED, SHALL BE 1 1/2" 0.75 LB/CU FT FIBERGLASS DUCT INSULATION WITH A FACTORY APPLIED REINFORCED ALUM. FOIL VAPOR BARRIER (R-4.2 MIN.).
- SOUND LINING, WHERE INDICATED, SHALL BE 1" 1.5 LB/CU FT FIBERGLASS DUCT LINING COATED TO PREVENT FIBER EROSION AT VELOCITIES UP TO 6000 FPM (R-4.2 MIN.).
- DUCT BOARD, WHERE INDICATED, SHALL BE 1" RIGID FRK FACED El 475 FIBERGLASS DUCT BOARD SYSTEM, UL 181 LISTED AS A CLASS 1 AIR DUCT (R-4.3 MIN.). AIR DUCT (R-4.3 MIN.).
6. FLEX DUCTS SHALL CONSIST OF A REINFORCED VAPOR BARRIER, 1 1/2" FIBERGLASS INSULATION, AND NON -PERFORATED INTERIOR LINER WITH WIRE HELIX. DUCT SHALL BE A
UL 181 LISTED CLASS 1 AIR DUCT. FLEX DUCTS SHALL ONLY BE USED WHERE SHOWN AND SHALL NOT EXCEED 12' IN LENGTH UNLESS NOTED OTHERWISE.
7. PROVIDE EARTHQUAKE RESTRAINT FOR HVAC EQUIPMENT IN ACCORDANCE WITH SECTION 1613 OF THE 2012 IBC.
8. PROVIDE FIRE DAMPERS, SMOKE DAMPERS AND FIRE/SMOKE DAMPERS WHERE INDICATED ON PLANS AND AS REQUIRED BY SECTION 717.5 OF THE 2012 IBC. PROVIDE CEILING
FIRE DAMPERS WHERE INDICATED ON PLANS AND AS REQUIRED BY SECTION 717,6.2.1 OF THE 2012 IBC. INSTALL FIRE DAMPERS SMOKE DAMPERS AND FIRE/SMOKE
DAMPERS IN ACCORDANCE WITH THE MANUFACTURERS INSTRUCTIONS, THE TERMS OF THEIR LISTING, AND THE REQUIREMENTS OF THE CODE.
9. PIPING PENETRATIONS OF FIRE RATED WALLS OR FLOORS SHALL BE SLEEVED AND FIRE STOPPED WITH LISTED MATERIALS SO AS TO MAINTAIN THE INTEGRITY AND RATING OF
THE FLOOR OR WALL.
10. HVAC EQUIPMENT, VALVES AND DAMPERS SHALL BE LOCATED IN EASILY ACCESSIBLE LOCATIONS. UNLESS SHOWN ON ARCHITECTURAL DRAWINGS, REQUIRED ACCESS PANELS
SHALL BE PROVIDED AND INSTALLED BY THE GENERAL CONTRACTOR. MINIMUM ACCESS DOOR SIZE FOR VALVES AND DAMPERS TO BE 18" X 18".
11. MOTORS STARTERS NOT LISTED AS BEING PROVIDED IN THE HVAC EQUIPMENT SCHEDULES ARE TO BE PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR.
12. WITHIN 90 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD DRAWINGS OF THE ACTUAL INSTALLATION TO BE PROVIDED TO THE BUILDING OWNER. RECORD DRAWINGS
SHALL INCLUDE AS A MINIMUM THE LOCATION AND PERFORMANCE DATA ON EACH PIECE OF EQUIPMENT, GENERAL CONFIGURATION OF DUCT AND PIPE DISTRIBUTION SYSTEM,
INCLUDING SIZES, AND THE TERMINAL AIR AND WATER DESIGN FLOW RATES.
13. OPERATING AND MAINTENANCE MANUALS TO BE PROVIDED TO THE BUILDING OWNER THAT INCLUDE: SUBMITTAL DATA, NAMES AND ADDRESSES OF AT LEAST ONE SERVICE
AGENCY, HVAC CONTROLS SYSTEM MAINTENANCE AND CALIBRATION INFORMATION AND A COMPLETE OPERATIONAL NARRATIVE FOR EACH SYSTEM.
14. COMMISSIONING IS REQUIRED ON THIS PROJECT IN ACCORD WITH WASHINGTON STATE ENERGY CODE (WSEC) SECTION 1416 AND WITH LEED NC-2.1 FUNDAMENTAL BUILDING
SYSTEMS COMMISSIONING AND ADDITIONAL COMMISSIONING.
15. A COMPLETE REPORT OF TEST PROCEDURES AND RESULTS SHALL BE PREPARED AND FILED WITH THE OWNER
REVIEWED FOP,
CODE COMPLIANCE
APPROVED
SEP 2 4 2014
AT
City of u >rifa
BUILDIN D 1/leln
APN# 115720-0016
SITE ADDRESS: 15205 52ND AVE S 98188
LEGAL DESCRIPTION: BROOKVALE GARDEN TRS PARCEL A OF TUKWILA SP NO 79-32-SS REC NO 7912050555 SD PLAT DAF - POR TR 1 BROOKVALE GARDEN TRS LY WLY OF 52ND AVE S LESS N 30 FT OF VAC ST ADJ LESS
W 20 FT THOF FOR CO RD LESS S 51.00 FT THOF
ADD (1) NEW 1 TON SPLIT SYSTEM TO VESTIBULE.
ADD (1) NEW EXHAUST FAN AND DOOR LOUVER TO AN CLOSET
ADD (2) NEW RETURNS TO 2ND FLOOR OFFICES
TITLE
PROJECT ENGINEER
ACCOUNT MANAGER
PRODUCTION MANAGER
SHEET METAL FOREMAN
AIR BALANCE FOREMAN
FACILITIES DIRECTOR
NAME
ERRYN EDRINGTON
MIKE REICHERT
TIM FELTON
RON LANDBERG
MARTIN PASCUAL
COMPANY
MACDONALD MILLER
MACDONALD MILLER
MACDONALD MILLER
MACDONALD MILLER
MACDONALD MILLER
SPEEA
PHONE NUMBER
206-
253-798-5080
206-768-4216
206-407-2692
206-571-2661
204-433-0995 X 126
EMAIL
@MACMILLER.COM
ERRYN.EDRIN GTON @MACMI LLER.COM
MIKE.REICHERT@MACMILLER.COM
TI M.FELTON@MACM I LLER.COM
RON.LANDBERG@MACMILLER.COM
MARTINP@SPEEA.ORG
NAME
TITLE
NAME
TITLE
TM0.01
DM2.01
SCHEDULES -HVAC
1ST FLOOR DEMO PLAN - HVAC
TM2.01 1ST FLOOR PLAN - HVAC
TM2.02 2ND FLOOR PLAN - HVAC
SEPARATE Rp PERMIT
REQ
❑ Mechanical
Electrical
Plumbing
Gas Piping
!A
►�1
City of Tukwila
BUILDING DIVISION
S 152nd St
518
S 151 st Si
51 st Ave S
52nd Ave S
Southcenter Blvd
FILE COPY
Permit No. A 1
n review approval is subject to errors and omissions.
proval of construction documents does not authorize
violation of any adopted code or ordinance. Receipt
f pproved Field Copy and conditions Is acknowledged:
B n
y:
Date: _ 9
REVISIONS
No changes shall be made to the scope
of work without prior approval of
Tukwila Building Division.
NOTE: Revisions will require a new plan v uhmittal
and may include additional plan review fees.
VICINITY MAP
NO SCALE
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
SEP 1 0 2014
PERMIT CENTER
Mt'4 0 vRo•
sa5 o) O IM
COI`
0)
Q °
0
I.-_ N N
� _(LL
CIO 0
GO en
a)o
0
_ 0)> CO
C.) 0o "dio
NCO
N
c �,;;j� di
�G LL
N. D-
ENGINEER:
K RICE
CHECKED BY:
B GEZON
CAD:
J HACKNEY
DRAWING NUMBER:
C-1980-73
SHEET NUMBER:
1 I I
I I I
I
rn
cV
I
tp
0
.macmiller.com
WA Lic No: MACDOFS980RU
REVISIONS:
W
0
REVISIONS:
z
0
0
z
0
0
Ct
0
LL
0
L!J
U)
U)
LAST REVISED:
08-29-14
DATE PLOTTED:
08-29-14
ISSUE DATE:
08-29-14
146795-00
TM0.01
J:\7314\6795 SPEEA — TAB Deficiency List Repairs —
S b7\
D S
212' - 2Y4"
1 §3'-4
)1
S0�
Cf)
1 I
_fp
�R B
VD
MI+
REVIEWED FOR
CODE COMPLIANCE
APPROVED
SEP 24 2014
City of Tukwila
BUILDING DIVISION
170
RECEIVED
CITY OF TUKWILA
SEP 1 0 2014
PERMIT CENTER
W 0)
z
_cs
O
V
O
0ct
0
w
ENGINEER:
K RICE
CHECKED BY:
B GEZON
CAD:
J HACKNEY
DRAWING NUMBER:
C-1980-73146
SHEET NUMBER:
.macmiller.com
co
O
(Y
0
0
H
cc
a.ICJ
WA Lic No: MACDOFS980RU
Lv
a
0
REVISIONS:
IJ J
0
0)
Z
0
z
0
U
U)
z
0
U
0
LL
0
W
LAST REVISED:
08-29-14
DATE PLOTTED:
08-29-14
ISSUE DATE:
08-29-14
795-00
TM0.01 S
B
4/18
12" 0
1" SL SM
365 CFM
FCU-3
20/16
"SLSM-
535 CFM --,-
12/12 MID-S
ONE WAY THROW
450 CFM EA
��O
ANEM. 10/10
S3HD 1201CFM
400.
CFM
3/4"
COND.
LINE
175 FM
MEETING R0O! `j
RFCEPTION
ANEM. 8/8
S3HOD 125 CFM
(7)
ANEM. 10/10
S3HD 170 CFM
—24/12
570 CFM
:ON1 1=tv1
PRINT RM.
285 C M
0
24/12 D.
14/12 D.B.
165 CFM
EF #01
?4/12
200 CFM
19/15 SL SM
8"0
165 CFM
`120 CFM
ANEM-6/6
MRD-S 40 CFM
To
ERVICE
NK
WO tiiL N
ANEM. 10/10
S3HOD 220 CFM
s
nfi
ANEM.
S3HOD i' CFM
ANEM. 10/10
S3HOD 240 CFM
170 CFM
ANEM. 10/10
S3HD 65 CFM
6" 0
10
`-:DR
REFRI
GERANT
LINES UP TO
ROOFTOP UNIT
(3 TYPICAL)
\10
3/4" COND. LINE
I._OUNO
24/12
ANEM. 10/10
MRD-S 275 CF
310 CFM
230 CFM
380 CFM
REVIEWED FOR
CODE COMPLIANCE
APPROVED
SEP 2 4 2014
City of Tukwila
BUILDING DIVISION
VLLw-OI7&
RECEIVED
CITY OF TUKWILA
SEP 1 0 2014
z
I I I I I I I I
I I I I I I I I
rn
N
CO
0
0
0
w
0_
I I I I I 1<-
OOR DEMO PLAN
ENGINEER:
K RICE
REVISIONS:
w
0
REVISIONS:
Z
0
0
F-
Z
0
0
0
u_
0
w
�v J
VJ
LAST REVISED:
08-29-14
CHECKED BY: DATE PLOTTED:
B GEZON 08-29-14
CAD: ISSUE DATE:
J HACKNEY 08-29-14
DRAWING NUMBER:
0-1980-73146795-00
SHEET NUMBER:
DM2.01
PERMIT CENTER
1/8" = 1'-0"
J:\7314\6795 SPEEA - TAB
NEW 10X8 TRANSFER GRILLE
IN EXISTING DOOR
B'
2014 10:59:47 AM
f_.._,
4/18
12" 0
1 " SL SM
365 CFM
20/16
1" SL SM
535 CFM
12/12 MRD—S
ONE WAY THRO'
450 CFM EA
ANEM. 10/10
S3HD 120 CFM
-EF-----1
DROP TO BLLY BPiND OF SIDING
0
0
NEW EXHAUST
9' ABOVE G'
TERMINAT ON
UND L L
ANEM. 10/10
S3HD 170 CFM
\I 24/12
+ % 570 CFM
14" 0
01 SL SM
0
`175 CFM
- T MEETING RO VIS
7)
585
CFM
N 1-. I M
CU-1
EF #01
4/ 1-2
1" SL
200 CFM
19/15 .L SM --
8"0 /
165 CFM
8
JrN20 CFM
ANEM-6/6
MRD—S 40 CFM
0
ERVICE
NK
uP
11/11 S
AC-1
12''0
24/12 D.
14/12 D.B.
165 CFM
ANEM. 10/10
S3HOD 220 CFM
MOUNT CON .DENSIN UNITON NEW
CONCRETE PAD
NEW REFRIGERANT PIPING
1 /4" LIQUID, 3/8" GAS
PREINSULATED OUTDOOR LINES
LOCATE UNIT BEHIND
SCREENING BUSHES
CU-1
GROUND LEVEL
ET
ANEM. 10/10
S3HOD 240 CFM
R < I D ( Ik
�170 CFM
CJ
113
ANEM. 10/10
S3HD 65 CFM
(_0 RAC F
REFRIGERANT
LINES UP TO
ROOFTOP UNIT
(3 TYPICAL)
3/4" COND. LINE
_OUNCE
SCREENING BUSHES
ANEM. 10/10`
MRD—S 275 CF14\
310 CFM
230 CFM
380 CFM
NEW 6" EXHAUST GRILLE
REVIEWED FOR
CODE COMPLIANCE
APPROVED
s 2 4 2014
C;tv 'f Tukwila
BUILOIiNi DIVISION
Mly
170
RECEIVED
CITY OF TUKWILA
SEP 1 0 2014
PERMIT CENTER
Z
C9 Cr)
03(0
rnNs
a�
a)0
N
N U
ALL
CI o f0 C.)
C
Q
O CO
N
N
r-- L
D_
0
0
cc
w
a_
I I I I I I<
OOR PLAN
ENGINEER:
K RICE
CHECKED BY:
B GEZON
CAD:
J HACKNEY
DRAWING NUMBER:
0
co
0
(/)
LL
2
Z
U
REVISIONS:
w
0
REVISIONS:
z
0
0
z
0
U
0
0
W
(/ JJ
VJ
LAST REVISED:
08-29-14
DATE PLOTTED:
08-29-14
ISSUE DATE:
08-29-14
0-1980-73146795-00
SHEET NUMBER:
TM2.01
1/8" = 1'-0"
OI
0
•
List Repairs — EE\00\2
c
c
G
J:\7314\6795 SPEEA — TAB
ANEM.
MRD-S
r
12/8 D.B.
6/24 EC.
DIPECTo(
12/24 D.B.
&R DROPS
-27T2
355 CFM
CO C3)
a.
a
N
s
N
0
E
r
L0011080
0,
7
10X10
8/2
2/24 EC
24 EC
10X10
A 240
10X10
0210
-_-----1 �- r - r
--- &R DROPS
O"
1 /24 E ` .
350 CFM_ 18/246„
12i-D--B
:;R DROPS
LLL`+/.
12/24
EC (TYP
71
2 24 D.B
& __DROP?
ANEM. 10/10
S3HOD 255 CFM
E!)
370 CFM EA
1 1 /,p0C.
1..2/6._ D
ANEM. 10/10
S3HOD 270 CFM
10X10
i Esc $Ei fE
10X10
A v—v190
INSTALL PER
M.M. STD SA-
STORACL.
-= TL
8X8
(T5YP 2)
REFRIGERANT
LINES DN. TO
FAN -COIL UNIT
(3-TYPICAL)
B
PS
REVIEWED FOR
CODE COMPLIANCE
APPROVED
SEP 24 2014
City of Tukwila
BUILDING DIVISION
filly-/ ►7
RECEIVED
CITY OF TUKWILA
SEP 1 0 2014
PERMIT CENTER
E9z
1/8" = 1'-0"
L co
o co
0
2 00
' H N
_13 3 Cn li
OM
a Lc
1 1 1 1 1 1 1 1
1 1 I •-1
rn
CV
I
0
2ND FLOOR PLAN
ENGINEER:
K RICE
CHECKED BY:
B GEZON
CAD:
J HACKNEY
0
IiJ
K
REVISIONS:
REVISIONS:
z
0
0
z
0
0
0
0
W
C0
G0
LAST REVISED:
08-29-14
DATE PLOTTED:
08-29-14
ISSUE DATE:
08-29-14
DRAWING NUMBER:
C-1980-73146795-00
SHEET NUMBER:
TM2.02