HomeMy WebLinkAboutPermit M15-0052 - LEGO - DUCTWORK REPLACEMENTLEGO
837 SOUTHCENTER MALL
M15-0052
Parcel No:
Address:
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670
Inspection Request Line: 206-438-9350
Web site: http://www.TukwilaWA.gov
9202470010
837 SOUTHCENTER MALL
Project Name: LEGO
MECHANICAL PERMIT
Permit Number: M15-0052
Issue Date: 5/20/2015
Permit Expires On: 11/16/2015
Owner:
Name:
Address:
Contact Person:
Name:
Address:
WESTFIELD PROPERTY TAX DEPT
PO BOX 130940 , CARLSBAD, WA,
92013
STEVE STECKLER
22129 NE 114TH ST, REDMOND, WA,
98053
Contractor:
Name: ALTERNATIVE MECHANCL SLTNS INC
Address: PO BOX 7114 , BELLEVUE, WA, 98008
License No: ALTERMS884K3
Lender:
Name:
Address:
Phone: (425) 221-1163
Phone: (425) 221-1163
Expiration Date: 5/30/2016
DESCRIPTION OF WORK:
REPLACE EXISTING DUCT WORK WITH NEW, INSTALLING 1 NEW VAV
Valuation of Work: $14,000.00
Type of Work: REPLACEMENT
Fuel type: GAS
Fees Collected: $376.54
Electrical Service Provided by: PUGET SOUND ENERGY
Water District: TUKWILA
Sewer District: TUKWILA SEWER SERVICE
Current Codes adopted by the City of Tukwila:
International Building Code Edition:
International Residential Code Edition:
International Mechanical Code Edition:
Uniform Plumbing Code Edition:
International Fuel Gas Code:
Permit Center Authorized Signature:
2012
2012
2012
2012
2012
National Electrical Code:
WA Cities Electrical Code:
WAC 296-46B:
WA State Energy Code:
Date:
2014
2014
2014
2012
I hearby certify thaf I have reag'and examined this permit and know the same to be true and correct. All
provisions of law nd o/rdinan es governing this work will be complied with, whether specified herein or not.
The granting of his p'ermi es not presume to give authority to violate or cancel the provisions of any other
state or local la s r /gulab' n construction or the performance of work. I am authorized to sign and obtain this
development rm t an a ee to the conditions attached to this permit.
Signature:
Print Name: //2ae-/'S
Date:
This permit shall become null and void if the work is not commenced within 180 days for the date of issuance, or if
the work is suspended or abandoned for a period of 180 days from the last inspection.
PERMIT CONDITIONS:
1: Work shall be installed in accordance with the approved construction documents, and any changes made
during construction that are not in accordance with the approved construction documents shall be
resubmitted for approval.
2: All permits, inspection record card and approved construction documents shall be kept at the site of work
and shall be open to inspection by the Building Inspector until final inspection approval is granted.
3: All construction shall be done in conformance with the Washington State Building Code and the
Washington State Energy Code.
4: Remove all demolition rubble and loose miscellaneous material from lot or parcel of ground, properly cap
the sanitary sewer connections, and properly fill or otherwise protect all basements, cellars, septic tanks,
wells, and other excavations. Final inspection approval will be determined by the building inspector based
on satisfactory completion of this requirement.
5: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila
Permit Center.
6: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an
approval of, any violation of any of the provisions of the building code or of any other ordinances of the City
of Tukwila. Permits presuming to give authority to violate or cancel the provisions of the code or other
ordinances of the City of Tukwila shall not be valid. The issuance of a permit based on construction
documents and other data shall not prevent the Building Official from requiring the correction of errors in
the construction documents and other data.
7: ***MECHANICAL PERMIT CONDITIONS***
8: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila
Permit Center (206/431-3670).
9: Manufacturers installation instructions shall be available on the job site at the time of inspection.
PERMIT INSPECTIONS REQUIRED
Permit Inspection Line: (206) 438-9350
1800 MECHANICAL FINAL
0701 ROUGH -IN MECHANICAL
CITY OF TUKJ _ A
Community Development Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
littp://www.TukwilaWA.gov
Mechanical Permit No. e - 009a-
Project No.
Date Application Accepted: 1� t/f
Date Application Expires: 11 ' 1 I 1 5f
(For office use only)
MECHANICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
**please print**
SITE LOCATION
Site Address:
Tenant Name:
y J;11 g1i- /�// / //
King Co Assessor's Tax No.:
Suite Number: /Vit ,Floor:
PROPERTY OWNER
Name:
Address:
City:
State:
Zip:
CONTACT PERSON — person receiving all project
communication
Name: 1 j4,w--
Address: z&'z9 /N r /-
City: 11/-� Stater7,x. Zip: gk
Phone: ,z.j.,.-2
7/ //'3 Fax: 72//
Email: c rk� Q77/li Zim,.t�$ / 62,g7.
New Tenant: ❑ Yes ❑.. No
MECHANICAL CONTRACTOR INFORMATION
Company Name:
/1/ 7 s7 L ' gi-t h7,�/jozxan _
Address: /'�� 7// /
City: ,Gfr/�dile State: Zip: ��,zei
Phone:6,L1) zz /e3 Fax:
Contr Reg No.: igGr_�o5.g8R Date: UJ� /6
J
Tukwila Business License No.:
Valuation of project (contractor's bid price): $
Describe the scope of work in detail: /s'�/-,�n�i�t PXi y�U �i�cl�i��/` uhfli/7,, in.F74/)%' f /n"4/
Use: Residential: New
Commercial: New
Fuel Type: Electric ❑
Replacement ❑ '
Replacement U�(
Gas ❑
Other:
H:\Applications\Forms-Applications On Line \2011 Applications\Mechanical Permit Application Revised 8-9-11.docx
Revised: August 2011
bh
Page 1 of 2
Indicate type of mechanical work being installed and the quantity below:
•
Unit Type i '
Qty
Furnace <1 OOk btu
Furnace >100k btu
Floor furnace
Suspended/wall/floor
mounted heater
Appliance vent
Repair or addition to
heat/refrig/cool ing
system
Air handling unit
<10,000 cfm
Unit Type
Qty
Air handling unit
>10,000 cfm
Evaporator cooler
Ventilation fan
connected to single duct
Ventilation system'
/
Hood and duct
Incinerator — domestic
Incinerator —
comm/industrial
Unit Type
Qty
Fire damper
Diffuser J5
rk
Thermostat I.
Wood/gas stove
Emergency generator
Other mechanical
equipment v1QQ}
Boiler/Compressor
Qty
0-3 hp/100,000 btu
3-15 hp/500,000 btu
-.15-30 hp/1,000,000 btu
30-50 hp/1,750,000 btu
50+ hp/1,750,000 btu
PERMIT APPLICATION NOTES -
Value of construction — in all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the permit center to comply with current fee schedules.
Expiration of plan review — applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The building official may grant one extension of time for additional periods not to exceed 90 days each. The extension shall be requested in writing
and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWNER OR AUTH RIZED AGENT:
Signature:
Print Name:
Mailing Address: ��A/t". 7//7
Date: Sj 7/cS
Day Telephone: //2 ) ZZ /%/�z3
City State Zip
H:\Applications\Forms-Applications On Line\2011 ApplicationsVvlechanical Permit Application Revised 8-9-11.docx
Revised: August 2011
bh
Page 2 of 2
z
4
et 0
J1
Cash Register Receipt
Receipt Number
R5238
DESCRIPTIONS ACCOUNT QUANTITY
PermitTRAK
PAID
$376.54
M15-0052 Address: 837 SOUTHCENTER MALL Apn: 9202470010
$376.54
MECHANICAL
$362.06
PERMIT ISSUANCE BASE FEE
R000.322.100.00.00
0.00
$32.50
PERMIT FEE
R000.322.100.00.00
0.00
$257.15
PLAN CHECK FEE
R000.322.102.00.00
0.00
$72.41
TECHNOLOGY FEE
$14.48
TECHNOLOGY FEE
TOTAL FEES PAID BY RECEIPT: R5238
R000.322.900.04.00
0.00
$14.48
$376.54
Date Paid: Thursday, May 07, 2015
Paid By: ALTERNATIVE MECHANICAL
Pay Method: CHECK 1075
Printed: Thursday, May 07, 2015 12:13 PM 1 of 1
CPSYSTEMS
RINSPECTION RECORD
Retain a copy with permit
INSP '"SN NO.
A(3 =ddf -Z
PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila: WA 98188 (206) 431-367
Permit Inspection Request Line (206) 438-9350
Project:
Type of Inspection:
Ad ess: ✓
3`75i(-
clef- -
(l
Date Called:
Special Instructions:
AA
Date Wanted:
6 �— l/
r 3-
1
a.m.
p.m.
Requester:
k
Phone No:
Approved per applicable codes. Corrections required prior to approval.
•
MENTS:
b
_ Fcfru;(
Inspector:
Date: rr
REINSPECTION FEE REQUIRED. Prior to next inspection. fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection.
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 438-9350
Protct:
0
Type Knspectr:
6
A-f-rJi
Add/rt./
46-57 9l4-1/trtk Mgt(
Date Called
Special Instructions:
q7--C) CICY° 0 LiA
Date wand:
0
a.m.
P.m.
Requester:
e.it-VI
Pho No:
FApproved per applicable codes. 0 Corrections required prior to approval.
OMMENTS:
Inspector:
-Date: 67 (6
REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection.
INSPECTION NOE
INSPECTION RECORD
Retain a copy with permit
44 ty-cdrz,
PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 438-9350
Projec :
Typ of Inspecti9sk . i
frt-) IA (
Aldress: /
537 ro 1/44. f-K-fr ./a-Rt (
Date Called:
Special Instructions: *I
Date 18anted:
5— — 2-2-- (i—
a.m.
P"'
Requester:
7-ertiy 0Gt O"(1
Phone No:
70 -Z-3-
2,&
ii-g-
Approved per applicable codes.
OMMENTS:
LJCorrections required prior to approval.
nspector:
Date:
—75—
T
REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection
INSPECTION RECORD
Retain a copy with permit
CTION NO. PERMIT NO,
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 438-9350
AU: 00 5-1
Pr ,
Type of inspection:
At -
..9i( --Trok _QC-4
Address:
1837 So 6Cf-eLC-fr A4cift
Date Ca11 0:
Specia Instructions:
kii4
Date Wanted:
j- ."-"i•-) — Cr
a.m.
P.m,
Re uester: ,
bil AO re (i @) 'Idte--6L
Phone No:
.-
Approved per applicable codes.
ElCorrections required prior to approval,
C ENTS:
I ector:
Date:
-
REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd.. Suite 100, Call to schedule reinspection.
M (5- 9O52
T STIIIGAVOC
EERVII S
LEGO STORE
SPACE #1450
SOUTHCENTER MALL
SEATTLE, WA
FINAL TAB REPORT
ARCHITECT:
HARTHORNE HAGEN ARCHITECTS
1725 8TH AVENUE NORTH - SEATTLE, WA 98109
MECHANICAL ENGINEER:
CONSULTING ENGINEERING SERVICE
811 MIDDLE STREET - MIDDLETOWN, CT 06457
MECHANICAL CONTRACTOR:
ALTERNATIVE MECHANICAL SOLUTIONS
PROJECT NO: 15-156
DATE: 6/17/2015
TECHNICIAN: JESSE FIFIELD
22129 NE 114TH STREET - REDMOND, WA 98008
Page 1 of 10
06/17/2015
NMI
AA BC
TAC SERVICES, LLC
4811 DESMOND STREET
BELLINGHAM, WA 98229
PH: (360) 255-5306
FAX: (360) 464-9973
ADMIN@TESTANDCX.COM
ammack
IJUN►18MI5
PERMIT CORER
AABC National
Performance Guaranty
Pursuant to the agreement between
TAC Services, LLC
AABC Certified Testing & Balancing Agency
Alternative Mechanical Solutions, Inc.
All systems shall be tested and balanced in accordance with the project plans and specifications
and to the optimum performance capabilities of the equipment. Testing and balancing shall be done
in accordance with the standards published by the Associated Air Balance Council.
If the Agency listed above fails to comply with the specifications for any reason other than
termination of business by the AABC agency or equipment malfunction or inadequacy which
prevents proper balancing of the systems, AABC will investigate and, if warranted, will provide
supervisory personnel to assist the member Agency to perform work in accordance with AABC
Standards. This supervision will be provided at no additional cost to the building owner.
This Guaranty is valid for one year from the date of submission of a test and balance report,
provided the Agency is a current member of AABC, and may only be invoked in writing by the building
owner, architect, or engineer of record. The Guaranty is limited to the terms and conditions as stated
herein.
Project Name LEGO Southcenter Mall
Address 837 Southcenter Mall
Name of Engineer R.J.
Fnn;noor;nn Farm Consulting Engineering Service
w
AABC
Associated Air
Balance Council
1518 K Street, N.W.
Washington, D.C. 20005
202-737-0202 • Fax 202-638-4833
info@aabc.com • www.aabc.com
Page 2 of 10
06/17/2015
1t flNG, AND Chi
SERVICES
TABLE OF CONTENTS
DESCRIPTION
COVER PAGE
AABC NATIONAL PERFORMANCE GUARANTY
TABLE OF CONTENTS
TEST INSTRUMENT CALIBRATION DATES
PROJECT SUMMARY
LEGEND SHEET
EXISTING VAV-1
VAV-2
SCHEMATIC DIAGRAM
AABC
PAGE
1
2
3
4
5
6-8
9
9
10
Page 3 of 10
06/17/2015
1 ESTINri: NO cog
SERVICES
TEST INSTRUMENT
CALIBRATION DATES
AABC
INSTRUMENT
MANUFACTURER
MODEL NO.
SERIAL NO.
CALIBRATION DATE
DIGITAL FLOW CAPTURE HOOD
ALNOR
EBT-721
90647007
4/7/2015
DIGITAL VELOMETER
ALNOR
RVA-801
A03110
8/7/2014
DIGITAL THERMOMETER (AIR)
ALNOR
RVA-801
A03110
8/7/2014
DIGITAL THERMOMETER (AIR)
ALNOR
EBT-721
90647007
4/7/2015
DIGITAL VEL GRID
ALNOR
EBT-721
90647007
4/7/2015
DIGITAL MANOMETER (AIR)
ALNOR
EBT-721
90647007
4/7/2015
HYDRONIC MANOMETER
ALNOR
HM-670
70633302
4/9/2015
SUBMERSIBLE THERMOMETER
ALNOR
HM-670
70633302
4/9/2015
AMMETER
FLUKE
323
29600018WS
3/27/2015
AC VOLT METER
FLUKE
323
29600018WS
3/27/2015
DC VOLT METER
FLUKE
323
29600018WS
3/27/2015
OHM METER
FLUKE
323
29600018WS
3/27/2015
PHOTO TACHOMETER
EXTECH
461895
461895
7/25/2014
CONTACT TACHOMETER
EXTECH
461895
461895
7/25/2014
DIGITAL LOGGING THERMOMETER
UEI
DT304
140104278
3/27/2015
7/21/2014
DUCT AIR LEAKAGE TEST MACHINE
ORIFLO
1" ORIFICE
020662
DUCT AIR LEAKAGE TEST MACHINE
ORIFLO
2" ORIFICE
020663
7/21/2014
DUCT AIR LEAKAGE TEST MACHINE
ORIFLO
3" ORIFICE
020664
7/21/2014
DUCT AIR LEAKAGE TEST MACHINE
ORIFLO
4" ORIFICE
020665
7/21/2014
SOUND LEVEL CALIBRATOR
REED
SC-05
131211221
3/27/2015
PIPE CLAMP THERMOMETER
UEI
ATTPC2
801 / 802
3/27/2015
Page 4 of 10
06/17/2015
rc nac M AU c$
SERVICES
PROJECT SUMMARY
1111/
AABC
1.0 THE AIR & HYDRONIC SYSTEMS WERE TESTED AND THE RESULTS ARE AS TABULATED ON THE ATTACHED DATA
SHEETS
2.0 COMMENTS ON SPECIFIC EQUIPMENT IS INCLUDED UNDER REMARKS SECTION ON INDIVIDUAL DATA FORMS
CONTAINED HEREIN.
Page 5 of 10
06/17/2015
TESTING AHfQ ICst
SERVICES
LEGEND SHEET
AHU AIR HANDLING UNIT
AC OR ACU AIR CONDITIONER UNIT
ACCU AIR COOLED CONDENSING UNIT
AD) P.D. ADJUSTED PITCH DIAMETER
AMP AMPERE
AVG AVERAGE
B.H.P. BRAKE HORSEPOWER
C.D. CEILING DIFFUSER
CFM CUBIC FEET PER MINUTE
C.E. CEILING EXHAUST
CH CHILLER
CHWR CHILLED WATER RETURN
CHW OR CHWS CHILLED WATER SUPPLY
C.R. CEILING RETURN
CT COOLING TOWER
CWR CONDENSER WATER RETURN
CW OR CWS CONDENSER WATER SUPPLY
DB DRY BULB
D.D. DIRECT DRIVE
D.P. DIFFERENCE, NET DECREASE OR INCREASE
DIA DIAMETER
DISP DISPLACEMENT
D.N.A. DATA NOT AVAILABLE
D.N.L DATA NOT LISTED
EAT ENTERING AIR TEMPERATURE
EDC ELECTRIC DUCT COIL
EDH ELECTRIC DUCT HEALER
EF EXHAUST FAN
EMCS ENERGY MANAGEMENT CONTROL SYSTEM (S)
EWT ENTERING WATER TEMPERATURE
FCU FAN COIL UNIT
FH FUME HOOD
FG FLOOR GRILLE
Page 6 of 10
06/17/2015
TESTING.. AIVO C*
SERVICES
F.E. FLOOR EXHAUST OR RETURN
F.L.A FULL LOAD AMPERAGE
FPB FAN POWERED BOX
FPM FEET PER MINUTE
F.S. FLOOR SUPPLY
F.S.R FLOOR SUPPLY REGISTER
FT. HD FEET OF HEAD
FTU FAN TERMINAL UNIT
GPM GALLONS PER MINUTE
GFH GAS FIRED HEATER
HC HEATING COIL
HEATER O.L. THERMAL OVERLOAD PROTECTION FOR MOTORS
LOCATED AT THE MOTOR STARTER
HEPA HIGH EFFICIENCY PARTICULATE AIR
H.F. HEPA FILTER
HOA HAND/OFF/AUTO SWITCH
H.P. HORSEPOWER
HPS HIGH PRESSURE STEAM
HRC HEAT RECOVERY COIL OR HEAT RECLAIM COIL
HVAC HEATING , VENTILATION AND AIR CONDITIONING
HWR HOT WATER RETURN OR HEATING WATER RETURN
HWS HOT WATER SUPPLY OR HEATING WATER SUPPLY
HX HEAT EXCHANGER
I.D. INSIDE DIAMETER
LAT LEAVING AIR TEMPERATURE
L.D. LINEAR SUPPLY DIFFUSER
LPS LOW PRESSURE STEAM
L.T. LIGHT TROFFER
LWG LOW WALL GRILLE
LWR LOW WALL RETURN
LWT LEAVING WATER TEMPERATURE
MAU/MUA
MBH
MAKE UP AIR UNIT
1,000 BTU'S PER HOUR
N.A. NOT ACCESSIBLE
N.I. NOT INSTALLED
N.T. NOT TAKEN
N.V.L NO VALID LOCATION
N.Z. NOZZLE
O.D. OUTSIDE DIAMETER
OPEN NO TERMINAL DEVICE INSTALLED
O.S.A. MIN OUTSIDE AIR MINIMUM
OAT OUTSIDE AIR TEMPERATURE
Page 7 of 10
06/17/2015
TESTING ANO Csr
SERVICES
PF POWER FACTOR
PHC PREHEAT COIL
PHC PHASE (S)
PMP CIRCULATING PUMP
P.P PERFORATED PLATE
PSI POUNDS PER SQUARE INCH
P.T. PITOT TRAVERSE
RA RETURN AIR
RF RETURN AIR FAN
R.G. RETURN GRILLE
RHC REHEAT COIL
RPM REVOLUTIONS PER MINUTE
SA SUPPLY AIR
SAT SUPPLY AIR TEMPERATURE
S.D. SUPPLY DIFFUSER
SEF SMOKE EXHAUST FAN
SF (AIR) SUPPLY FAN
S.F. (ELECT) SERVICE FACTORS
SHC STEAM HEATING COIL
S.P. "W.C." STATIC PRESSURE RESISTANCE, MEASURED IN
INCHES OF WATER COLUMN
S.W.E. SIDEWALL EXHAUST
S.W.R. SIDEWALL RETURN
S.W.S. SIDEWALL SUPPLY
TAB TESTING, ADJUSTING, AND BALANCING
TSP TOTAL STATIC PRESSURE
UH UNIT HEATER
V VOLTS
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER
VFD VARIABLE FREQUENCY DRIVE
VP VELOCITY PRESSURE
W WATTS
WB WET BULB
W.G. WATER GAUGE
°F DEGREES FAHRENHEIT
DP DIFFERENTIAL (DELTA) PRESSURE OR PRESSURE
DROP
DT DIFFERENTIAL (DELTA) TEMPERATURE, NET
TEMPERATURE DECREASE OR INCREASE
PSI POUNDS PER SQUARE INCH
Page 8 of 10
06/17/2015
AABC
PROJECT:
LEGO SOUTHCENTER
LOCATION:
TUKWILA, WA
PROJECT NO:
15-156
CONTACT:
JESSE FIFIELD
TERMINAL UNIT ID:
TERMINAL UNIT DATA
EX VAV-1 AREA SERVED: SALES FLOOR
MANUFACTURER:
TITUS MODEL NUMBER: SQT-06-14
SIZE:
14 CORRECTION FACTOR: N/A (NO DDC)
MAXIMUM CFM DESIGN:
2170 MAXIMUM CFM ACTUAL: 2154
MINIMUM CFM DESIGN:
AREA SERVED
SALES FLOOR
NO.
1
CODE
B
651
SIZE
6"
AK
F.H.
MINIMUM
DESIGN
FPM
-
CFM ACTUAL:
CFM
150
INITIAL
FPM
-
CFM
99
646
FINAL
FPM
-
CFM
142
SALES FLOOR
2
A
8"
F.H.
-
200
-
206
-
202
SALES FLOOR
3
B
6"
F.H.
-
150
-
106
-
140
SALES FLOOR
4
A
8"
F.H.
-
200
-
179
-
213
SALES FLOOR
5
A
8"
F.H.
-
200
-
259
-
208
SALES FLOOR
6
A
8"
F.H.
-
200
-
251
-
194
SALES FLOOR
7
A
8"
F.H.
-
150
-
105
-
139
SALES FLOOR
8
B
6"
F.H.
-
200
-
247
-
202
SALES FLOOR
9
B
6"
F.H.
-
150
-
98
-
137
SALES FLOOR
10
A
8"
F.H.
-
200
-
223
-
204
SALES FLOOR
11
A
8"
F.H.
-
170
-
183
-
177
SALES FLOOR
12
A
8"
F.H.
-
200
-
236
-
196
EX VAV-1
--_-
2170
2192
2154
TERMINAL UNIT ID:
----------
VAV-2
TERMINAL UNIT
AREA SERVED:
DATA
STOCKROOM
MANUFACTURER:
PRICE MODEL NUMBER:
SDV8-8
SIZE:
8 CORRECTION FACTOR:
0.71
MAXIMUM CFM DESIGN:
500 MAXIMUM CFM ACTUAL:
508
MINIMUM CFM DESIGN:
AREA SERVED NO.
STOCKROOM 1
150 MINIMUM CFM ACTUAL:
CODE SIZE AK DESIGN INITIAL
FPM CFM FPM
A 6" F.H. - 125 -
152
FINAL
CFM FPM CFM
152 - 126
STOCKROOM 2
A 6" F.H. - 125 - 146 - 121
STOCKROOM 3
A 6" F.H. - 125 - 154 - 128
STOCKROOM 4
A 6" F.H. - 125 - 160 - 133
VAV-2 ---_-
500 612 508
REMARKS
FORM ID: VAV TERMINAL UNIT TEST SHEET
Page 9 of 10
06/17/2015
015 3ns0
a re3a40.5 1
srizt
sogro
SNV'Id >I?IOM M3N
Noue1E0530
SNOISI/s J
r
�8 NOLLPIOIAIRQ 'IVDINVHOH 4I
Vle
VM'3111.V3S
TIV151I31lLiDH1110S
0501M 30VdS
3110.1S 00(31
150-1k1 INVNHI
1435 5,21331.191.3
tOg
€
6
9
MECHANICAL LEGEND
DUCT BLOCKS
MECHANICAL NO
SHEET NO.
Page 10 of 10
06/17/
lltus Submittal
DESV
Single Duct Terminal Unit
Direct Digital Control, Pressure Independent
VILE COPY
Control Enclosure
(Optional on Cooling -Only units) -
12 1/4"
T I
F — 61 /2" ---.-1
Right hand unit shown. All dimensions are in inches.
M G —
Lego Store, Southcenter Mall
Unit No. VAV-2
REVWED FOR
CODE COMPLIANCE
APPPOvED
MAY;
E
L. _
8 2015
City of Tukwila
BUILDING DIVISION
L_________ 18"
Slip & Drive
Cleat Connection
Inlet Size
CFM Range
D
F
G
H
L
M
W
4
0-225
3 7/8
2 1/8
7 3/8
8
15 1/2
5 3/8
12
5
0-350
4 7/8
2 1/8
7 3I8
8
151/2
5 3/8
12
—0.6
0-500
5 7/8
2 1/8
7 3/8
8
15 1/2
3 3/8
12
7
0-650
6 7/8
1 1/8
7 3/8
10
15 1/2
3 3/8
12
8
0-900
7 7/8
1 1/8
7 3/8
10
151/2
3 3/8
12
9
0-1050
8 7/8
-
5 3/8
12 1/2
15 1/2
3 3/8
14
10
0-1400
9 7/8
-
5 3/8
121/2
151/2
3 3/8
14
12
0-2000
11 7/8
-
5 3/8
15
151/2
3 3/8
16
14
0-3000
13 7/8
-
3 3/8
171/2
151/2
3 3/8
20
16
0-4000
15 7/8
-
3 3/8
18
15 1/2
3 3/8
24
24 x 16
0-8000
23 7/8 x 15
7/8
1 1/8
5 3/8
18
15
3 3/8
38
Accessories (Optional)
Check Er if provided.
24 V Control Transformer
❑ Dust Tight Enclosure Seal
❑ Fibre Free Liner
❑ W EcoShield Liner
General Description
RECEIVED
CITY OF TUKWILA
MAY 0 7 2015
PERMIT CENTER
❑ 'A" Fibre Free Liner
❑ 1" Fiberglass Liner
❑ 1" EcoShield Liner
❑ 1" Fibre Free Liner
❑ Low Leakage Seal/Test/Certify
❑ SteriLoc Liner
❑ UltraLoc Liner
❑ 'A" EcoShield Liner (Foil Face)
❑ 1" EcoShield Liner (Foil Face)
Disconnect Switch
Hanger Brackets
Removable Air Flow Sensor
Bottom Access Door
• Heavy gauge steel housing.
Mechanically sealed and
gasketed, leak resistant
construction. Less than 2% of
nominal cfm at 1.5" sp wg.
• Dual density intemal insulation,
treated to resist air erosion.
Meets requirements of NFPA 90A
and UL 181.
• Rectangular discharge opening is
designed for slip and drive cleat
duct connection.
• Multipoint center averaging inlet
velocity sensor.
• Digital control packages can be
factory mounted by Titus.
• Choice of right hand or left hand
control location.
Model DESV can be installed
horizontally, vertically, or at any
angle. Operation is not affected
by position.
Gauge tees for cfm
measurement.
MI5.0051-
DESV-2.0 11-7-14
Accessories (Optional)
❑ Hot Water Coil Section
• 1/2" or 7/8" copper tubes
• Aluminum ripple fins, 10 per inch
• Connections: Single circuit, 1/2" or 7/8"
O.D. male solder. Multi -circuit, 7/8"
O.D., male solder.
• Coil is installed at discharge of unit.
• On units with attenuators, coil are
installed at the discharge of
attenuator.
❑1Row
❑ 2 Row
0 3 Row
❑4Row
0
0
W
Electric Coil Section
Standard Features
• Single side access to low voltage,
high voltage, and electric heater
controls.
• Automatic reset thermal cutouts, one
per element
• Manual reset secondary protection.
• Positive pressure flow switch
• Magnetic contactor for each step.
• Slip and drive cleat discharge duct
connection.
0 Optional SCR Controlled Electric Heater
Options
❑ Fuse Block
"AEI Disconnect switch, door
interlock type
O Dust tight construction
0 Mercury contactors
❑ Optional Lynergy Controlled Electric Heater
Supply Voltage
"----09 208V, 1 ph, 60Hz
❑ 240V, 1 ph, 60Hz
❑ 277V, 1 ph, 60Hz
❑ 208V, 3 ph, 60Hz
❑ 480V, 3 ph, 60Hz (4 wire wye
standard)
Inlet Size
H
W
Water Coil
L (1-2 Row)
L (3-4 Row)
4
8
12
5
7 1/4
5
8
12
5
7 1/4
6
8
12
5
71/4
7
10
12
5
7 1/4
8
10
12
5
7 1/4
9
121/2
14
5
71/4
10
121/2
14
5
71/4
12
15
16
5
7 '/4
14
171/2
20
7 1/2
9 3/4
16
18
24
7 1/2
9 3/4
24x16
18
38
5
71/4
The total length of the DESV
unit is the summation of the
unit length (with or without
attenuator) and the length of
the optional water coil.
This submittal is meant to demonstrate general dimensions of this product. The drawings are not meant to detail every aspect of the product. Drawings are not to scale. Titus
reserves the right to make changes without written notice.
AI rights reserved. No pert ethicvArk may Pe reproduced or transmitted in any tom or M any means.®ecVaac or mechanical. Including photocopying and recording, or by any information storage reinaval system without permission Nwilling *Ism Air Distribution Technologies. Inc.
Titus TEAMS
Single Duct Terminal Unit Selection
Project: LEGO STORE, SOUTHCENTER
Tag: VAV-02
i
Project Location:
Altitude: 1 Feet
User:
File:
Room:
Selection
Quantity
Model
Size
CFM
Static
Max NC Levels
Electrical
Unit
Outlet
Max.
Min.
Heating
Inlet
Down
Min.
Rad
Dis
MCA
MOP
1
DESV
06
12x8
500
150
150
1
0.25
0.2 i
28
22
6.0
15
Notes:
1 See below for PWL calculations used to obtain Max NC rating.
2 Outlet size is approximate and does not include coil dimensions. See submittal drawings for exact dimensions.
3. Inlet static pressure includes downstream pressure drop.
Electric Heating Coil Performance
KW
Max KW
CFM
EAT
LAT
Volts / Phase
Steps
1
7.5
150
50
71.1
20811
1
Other Information
Maximum CFM : 500
Design CFM : 500
Safety Factor: 0%
UnitLxWxH: 39.5X 12X8in.
Controls: DDC
Acoustic Summary
Accessories
Outlet: Attenuator
Lining: 1/2 in. Fiberglass
Heating Coil: Electric
Attenuator: Yes
Sound Description
Radiated Sound PWL
NC
Discharge Sound PWL
NC
2
3
4
5
6
7
2
3
4
5
6
7
Primary Sound
Total Attenuation per
62
18
59
19
49
20
44
26
40
31
35
36
66
27
64
29
58
40
47
51
36
53
36
39
*
Room Sound Level
44
40
29
18
-
-
28
39
35
18
-
-
-
22
Notes: 1. Selections are based on Titus as Manufacturer.
2. All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2008.
3. All NC levels determined using AHRI 885-2008 Appendix E.
4. All airflow, pressure losses and heating performance values have been corrected for altitude.
5. Units of measure: dimensions (in), airflow (cfm), water flow (gpm), air pressure (in wg), water head losses (ft) and temperatures (degF).
6. In the "Steps" column, code "S" denotes a modulating SCR heater.
7. The minimum supply circuit ampacity (MCA) and maximum overcurrent protection (MOP) ratings were calculated in accordance with UL
standards based on motor and electric coil full Toad current ratings.
The results of this program are only an aid to the designer, and are not a substitute for professional design services.
Titus accepts no liability for the adequacy of any resulting design or installation.
All data subject to change without notice.
Printed: 4/29/2015 : 3:42 PM
Page:1
PERMIT COORD COPY
PLAN REVIEW/ROUTING SLIP
PERMIT NUMBER: M15-0052
PROJECT NAME: LEGO
DATE: 05/07/15
SITE ADDRESS: 837 SOUTHCENTER MALL PKWY
X Original Plan Submittal
Response to Correction Letter #
Revision #
Revision #
before Permit Issued
after Permit Issued
DEPARTMENTS:
P's\ PC*�
Building Division
Public Works
titIc
Fire Prevention
Structural
Planning Division
Permit Coordinator
PRELIMINARY REVIEW:
Not Applicable ❑
(no approval/review required)
DATE: 5/12/2015
Structural Review Required
REVIEWER'S INITIALS: DATE:
APPROVALS OR CORRECTIONS: DUE DATE: 6/9/2015
Approved
Corrections Required
Approved with Conditions
Denied
(corrections entered in Reviews) (ie: Zoning Issues)
Notation:
REVIEWER'S INITIALS:
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
12/18/2013
ALTERNATIVE MECHANCL SL"T''`TS INC
Page 1 of 4
Hone Inicio en .Espanol Contact
Search L&I
A-% .index Help My Secure 1.,&I
Safety Claims & Insurance Workplace Rights Trades & Licensing
Washington State Department of
Labor & Industries
ALTERNATIVE MECHANCL SLTNS INC
Owner or tradesperson
Principals
STECKLER, STEPHEN FRANCES, VICE
PRESIDENT
WHEELER, JULIEANN D, PRESIDENT
(End: 08/30/2013)
GORDON, ROBERT, DIRECTOR
(End: 10/11/2012)
Doing business as
ALTERNATIVE MECHANCL SLTNS INC
WA UBI No.
603 187 603
PO BOX 7114
BELLEVUE, WA98008
425-221-1163
KING County
Business type
Corporation
License
Verify the contractor's active registration / license / certification (depending on trade) and any past violations.
Construction Contractor Active.
.......................................................................
Meets current requirements.
License specialties
GENERAL
License no.
ALTERMS884K3
Effective — expiration
05/23/2012— 05/30/2016
Bond
..............
American Contractors Indem CO
Bond account no.
100219964
$12,000.00
Received by L&I Effective date
05/08/2013 04/08/2013
Expiration date
Until Canceled
Bond history
Insurance
........... ..................
Ohio Security Ins Co $1,000,000.00
Policy no.
BKS56113589
Received by L&I Effective date
04/30/2015 05/08/2015
Expiration date
05/08/2016
Insurance history
Savings
....................
No savings accounts during the previous 6 year period.
https://secure.lni.wa.gov/verify/Detail.aspx?UBI=603187603&LIC=ALTERMS884K3&SAW= 5/20/2015