HomeMy WebLinkAboutPermit M15-0120 - GARAGISTE - GRDS AND DUCTWORKGARAGISTE
17616 W VALLEY HWY
M15-0120
Parcel No:
Address:
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670
Inspection Request Line: 206-438-9350
Web site: http://www.TukwilaWA.gov
2523049017
17616 W VALLEY HWY
Project Name: GARAGISTE
MECHANICAL PERMIT
Permit Number:
Issue Date:
Permit Expires On:
M15-0120
10/5/2015
4/2/2016
Owner:
Name:
Address:
Contact Person:
Name:
Address:
Contractor:
Name:
Address:
License No:
Lender:
Name:
Address:
TERRENO 17600 WVH LLC
101 MONTGOMERY ST #200 , SAN
FRANCISCO, WA, 94104
JOELSCHUPPERT Phone: (253) 255-3884
MECHANICAL & CONTROL SERVICES Phone: (253) 926-9777
INC
6426 18TH ST E , FIFE, WA, 98424
MECHACS962BT Expiration Date: 2/26/2016
6426 18TH ST E , FIFE, WA, 98424
Ill
DESCRIPTION OF WORK:
REMOVE/REINSTALL EXISTING GRD'S AND DUCTWORK AS REQUIRED FOR NEW TENANT IMPROVEMENT PLAN.
Valuation of Work: $9,870.00
Type of Work: REPLACEMENT
Fuel type:
Fees Collected: $324.28
Electrical Service Provided by: PUGET SOUND ENERGY
Water District: RENTON
Sewer District: RENTON SEWER SERVICE
Current Codes adopted by the City of Tukwila:
International Building Code Edition:
International Residential Code Edition:
International Mechanical Code Edition:
Uniform Plumbing Code Edition:
International Fuel Gas Code:
2012
2012
2012
2012
2012
National Electrical Code:
WA Cities Electrical Code:
WAC 296-46B:
WA State Energy Code:
2014
2014
2014
2012
Permit Center Authorized Signature:Fatmel
V- Pplt9 Date:'a 7
I hearby certify that I have read and examined this permit and know the same to be true and correct. All
provisions of law and ordinances governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other
state or local aws r :ulating construction or the performance of work. I am authorized to sign and obtain this
development • - it and agree to the conditions attached to this permit.
Signatur
Print Name:
Date: iQ J —i
This permit shall become null and void if the work is not commenced within 180 days for the date of issuance, or if
the work is suspended or abandoned for a period of 180 days from the last inspection.
PERMIT CONDITIONS:
1: Work shall be installed in accordance with the approved construction documents, and any changes made
during construction that are not in accordance with the approved construction documents shall be
resubmitted for approval.
2: All permits, inspection record card and approved construction documents shall be kept at the site of work
and shall be open to inspection by the Building Inspector until final inspection approval is granted.
3: All construction shall be done in conformance with the Washington State Building Code and the
Washington State Energy Code.
4: Remove all demolition rubble and loose miscellaneous material from lot or parcel of ground, properly cap
the sanitary sewer connections, and properly fill or otherwise protect all basements, cellars, septic tanks,
wells, and other excavations. Final inspection approval will be determined by the building inspector based
on satisfactory completion of this requirement.
5: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila
Permit Center.
6: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an
approval of, any violation of any of the provisions of the building code or of any other ordinances of the City
of Tukwila. Permits presuming to give authority to violate or cancel the provisions of the code or other
ordinances of the City of Tukwila shall not be valid. The issuance of a permit based on construction
documents and other data shall not prevent the Building Official from requiring the correction of errors in
the construction documents and other data.
7: ***MECHANICAL PERMIT CONDITIONS***
8: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila
Permit Center (206/431-3670).
9: Manufacturers installation instructions shall be available on the job site at the time of inspection.
PERMIT INSPECTIONS REQUIRED
Permit Inspection Line: (206) 438-9350
1800 MECHANICAL FINAL
0701 ROUGH -IN MECHANICAL
CITY OF TUKWILA
Community Development Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http://www.TukwilaWA.gov
Mechanical Permit No. IY l 1 5 4 0t2fj
Project No.
Date Application Accepted:
Date Application Expires: I� LLL
(For office use only)
MECHANICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
**please print**
SITE LOCATION
Site Address: 11 b I(0 W. V L.L.EY ii(.l) K
Tenant Name: &AAA 6 t ST f
PROPERTY OWNER
Name: CQDize
Address: zo -1 1 S -nob vE SG . SiE 21 Q
City: IC.EN'r State: (A3 A Zip:98o3 2
CONTACT PERSON - person receiving all project
communication
Name: �O EL SCH U PpLia T
Address: G42(A 1 $TH Sr. EA .
City: f- t r E State: A Zipl 874,2q
Phone:'S.3 2ss-388o Fax:
Email: TO ELS & GeoutPrAcs. #.14
King Co Assessor's Tax No.: 2.SZ304-19 OI-7
Suite Number: Floor:
New Tenant: [2' Yes ❑ . No
MECHANICAL CONTRACTOR INFORMATION
Company Name:
I1IE0HANteAC.4 C r.irtot. Cett1!CZ'S.
Address: tOy 210 I $TH sr EAS r
City: Fire
!rE State: WA Zip:9Bg2y
Phone:2s3.926_9177 Fax:
Contr Reg No.:m6 �5%2 g.rExp Date: 2-2(0^I c
Tukwila Business License No.:
Valuation of project (contractor's bid price): $ 9, O 70
Describe the scope of work in detail: REM Otte/ 2E TN STALL. Ex( Sr,,4 Cs 6 R b S ANC b A Crc d 21C
AS 12EGLLA t get Fog- NEW TEn1ArJT ivAPeliti e-NT l�t.Anl .
Use:
Residential:
New ❑ Replacement 0
New ❑ Replacement 0
Fuel Type: Electric El
Gas ❑
Other:
Wpplications\Forns-Applications On Line\2011 Applications\Mechanial Penult Application Revisal 8-9-1 I.docx
Revised: August 2011
bh
Page 1 of 2
Indicate type of mechanical work being installed and the quantity below:
Unit Type
Qty
Fumace <100k btu
Furnace >100k btu
Floor fumace
Suspended/wall/floor
mounted heater
Appliance vent
Repair or addition to
heat/refrig/cooling
system
Air handling unit
<10,000 cfm
Unit Type
Qty
Air handling unit
>10,000 cfm
Evaporator cooler
Ventilation fan
connected to single duct
Ventilation system
Hood and duct
Incinerator— domestic
Incinerator—
comm/industrial
Unit Type
Qty
Fire damper
Diffuser
2. (o
Thermostat
Wood/gas stove
Emergency generator
Other mechanical
equipment
Boiler/Compressor
(NY
0-3 hp/100,000 btu
3-15 hp/500,000 btu
15-30 hp/1,000,000 btu
30-50 hp/1,750,000 btu
50+ hp/1,750,000 btu
PERMIT APPLICATION NOTES -
Value of construction — in all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the permit center to comply with current fee schedules.
Expiration of plan review — applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The building official may grant one extension of time for additional periods not to exceed 90 days each. The extension shall be requested in writing
and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
I HEREBY CERTIFY THAT 1 HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF RJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING NER OR AUTHORIZED AGENT:
Signature. Date: I— 1 S. l C
Print Name: 1-, eL SGU.
HPPeg S Day Telephone: 2S3' 2S-3$'q
Mailing Address: Co 4 Uo (' p
Sr- E� . �t F� (�� , _l NZg
City State Zip
H:\Applicatiota\Fomts-Applications On Line\2011 Applications\Mechanical Permit Application Revised 8-9-11.docx
Revised: August 2011
bh
Page 2 of 2
Cash Register Receipt
City of Tukwila
DESCRIPTIONS ACCOUNT QUANTITY
PermitTRAK
PAID
$324.28
M15-0120 Address: 17616 W VALLEY HWY Apn: 2523049017
$324.28
MECHANICAL
$311.81
PERMIT ISSUANCE BASE FEE
R000.322.100.00.00
0.00
$32.50
PERMIT FEE
R000.322.100.00.00
0.00
$216.95
PLAN CHECK FEE
R000.322.102.00.00
0.00
$62.36
TECHNOLOGY FEE
$12.47
TECHNOLOGY FEE
TOTAL FEES PAID BY RECEIPT: R6199
R000.322.900.04.00
0.00
$12.47
$324.28
Date Paid: Friday, September 18, 2015
Paid By: MECHANICAL & CONTROL SERVICES
Pay Method: CHECK 27755
Printed: Friday, September 18, 2015 12:27 PM 1 of 1
CSYSTEMS
INSPECTION RECORD
Retain a copy permit
ermit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd.., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 438-9350
Project: J
Type ofIection
,�
#0,41-1167-/Q--
/�le/��Addres
Date
Special Instructions: r
Dat Panted:
ff
/�
/�
� j
a.m.
p.m.
Requester:
Phone No:
Approved per applicable codes. Corrections required prior to approval.
COMMENTS:
1—ov-e4).
v
Inspector:
r;;,ev-49/A--
Date: //
REINSPECTION FEE REQUIRED. Prior to next inspection. fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection.
Retain a copy with permit44
INSCTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188
Permit Inspection Request Line (206) 438-9350
(206) 431-3670
Project r,4 1 e
Type o,1€ spectit n. ^ Gc I
Address:
1`'. 11w..
w Ver14Y
Date Called:
�
Special Instructions:
Date Wanted:
100
-psis-
Requeste��
PhoneNo , x65 075
EiApproved per applicable codes. Corrections required prior to approval.
COMMENTS:
,'�& i'`�
Inspector:
Date:
REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection.
HVAC EQUIPMENT SCHEDULE
EQUIP ID
TYPE
NEW
EXISTING
MFG
MODEL
CFM
BTU
VOLTS
PH
MCA
MOCP
WEIGHT
NOTES
RTU-3 I GAS I EXISTING I TRANE I YCD102C4L ( 3400
109,350 I 460
3 I 29 I 35 I NA
1,2,3,4
RTU-7
GAS I EXISTING I TRANE I YCCO24F1L
800 I 32,000 I 230 11 I 15.7 I 25
NA
1,2,3
NOTES:
1
VERIFY EXISTING UNIT FUNCTIONS SAFELY AND PROPERLY PRIOR TO TENANT OCCUPANCY
2
EXISTING BUILDING CONTROLS SYSTEM MODIFICATIONS IF REQUIRED ARE NOT COVERED IN THESE PLANS AND/OR PERMIT
3
REUSE EXISTING VISION PRO THERMOSTAT
4
VERIFY AND/OR INSTALL DUCT SMOKE DETECTOR INSTALLED PER 2012 IMC 606.2.1
GRILLS, REGISTERS AND DIFFUSERS
THERMOSTATS/SENSORS
TYPE
MFG
LABEL
SIZE
MODEL
TYPE I OBD
UNIT ID
MANUFACTURER
MODEL
SUPPLY
TITUS
S-1
8X8
MCD
TBAR
NO
RTU-3
HONEYWELL
VISION PRO
VI
S-2
It
GYP
YES
S-3
10X10
TBAR
NO
RTU-7 I HONEYWELL
VISION PRO
RETURN
VI
R-1
10X22
50F
R-2
22X22
NOTES:
RELOCATE AND/OR INSTALL EXISTING GRD'S AS REQUIRED
2
REBALANCE PER NEW VALUE
3
INSTALL PER ALL CODES
VICINITY MAP
NTS
PE[1,174, COPY
Ko.IW�� .1 "v
HVAC GENERAL NOTES
1) THESE PLANS ARE SCHEMATIC AND DO NOT SHOW EXACT ROUTING OR EVERY
OFFSET, WHICH MAY BE REQUIRED. HVAC CONTRACTOR TO COORDINATE WITH ALL
OTHER TRADES
2) ALL WORK SHALL CONFORM TO THE REQUIRMENTS OF WASHINGTON STATE CODES,
REGULATIONS, ORDINANCES AND THE AUTHORITY HAVING JURISDICTION INCLUDING
BUT NOT LIMITED TO ANY OF THE FOLLOWING: IBC 2012, IMC 2012, UPC 2012 AND THE
WSEC 2012
3) AIR ECONOMIZERS SHALL BE PROVIDED ON ALL NEW SYSTEMS IF APPLICABLE.
ECONOMIZERS SHALL COMPLY WITH SECTIONS C403.4.1.1 THROUGH C403.4.1.4 OF THE
WSEC 2012
4) FLEXIBLE DUCT LENGTHS SHALL NOT EXCEED 10' UNLESS PRIOR APPROVAL HAVE
BEEN GIVEN. FLEXIBLE DUCT TO COMPLY WITH 2012 IMC SECTIONS 603.6.1, 603.6.1.1
AND 603.6.4
5) PROVIDE EARTHQUAKE RESTRAINT FOR HVAC EQUIPMENT IN ACCORDANCE WITH
THE CURRENT IBC
6) PIPING AND DUCT PENETRATIONS THRU FLOORS AND WALLS SHALL BE SLEEVED
AND/OR FIRE STOPPED SO AS TO MAINTAIN THE INTEGRITY OF THE SURFACE PER 2012
IMC 603.7
7) MAINTAIN 10' MINIMUM CLEARANCES TO ALL OUTSIDE AIR AND ECONOMIZER
INTAKES FROM ANY EXHAUST VENTS
8) DUCTWORK TO MEET THE R-VALUE REQUIRMENTS OF THE 2012 WSEC C403.2.7.1/2
9) ALL DUCTWORK CONSTRUCTED AND SEALED PER 2012 WSEC C403.2.7.1 & C403.2.7.3
10) EQUIPMENT SCHEDULE PROVIDED PER 2012 WSEC C403.2.3, C403.2.3.2, C403.2.13
AND C403.2.12.1
11) THERMOSTATIC CONTROLS INDICATED ON PLANS PER WSEC C403.2.4.1
12) THERMOSTATS TO PROVIDE 5 DEG DEADBAND MINIMUM PER WSEC C403.2.4.2
13) THERMOSTAT TO PROVIDE AUTOMATIC SETBACK & MANUAL OVERRIDE PER WSEC
C403.2.4.3
14) ALL NEW HVAC PIPING TO BE INSULATED PER 2012 WSEC C403.2.8
15) DUCT SMOKE DETECTORS TO BE INSTALLED IN RETURN AIR SYSTEMS WITH A
DESIGN CAPACITY GREATER THAN 2000 CFM IN THE RETURN AIR DUCT OR PLENUM PER
2012 IMC 606.2.1
SCOPE OF WORK:
REMOVE/REINSTALL EXISTING GRD'S AND DUCTWORK AS REQUIRED FOR NEW
TENANT IMPROVMENT PLAN. EXISTING RTU'S AND THERMOSTATS TO BE REUSED.
REBALNCE ALL GRD'S TO NEW LISTED VALUES. VERIFY EXISTING EQUIPMENT IS
FUNCTIONING SAFELY AND PROPERLY. VERIFY AND/OR CORRECT ANY EXISTING
DUCTWORK ETC. IS INSTALLED PER ANY/ALL APPLICABLE CODES.
Ian reviav approval is ctgact to errors and ornissio71s.
PRE r'f construction documents does not authu ias
a via. do adoglad
.
ap7oved
B
Date:
t 7td Lions achnolvizi£, ad:
City of Val, la
BUILDING DIVE
•
SITE/BUILDING PLAN
NTS
AREA OF _WORK
• caG,1'I i'ii c
Ate.
Nam: Rio
MECHANICAL &
CONTROL SERVICES, INC.
groupmcs.cr*
182PARATEP MIT
1E01 D FOR:
yi av co
GcsP nO
-1 y off>krZ r
REVIEWED FOR
CODE COai DANCE
SEP 3 0 2015
pki
City of Tukwila
OU!LDING DIV6SION
CITY OF TUKWILA
SEP 1 8 2015
PERMIT CENTER
cz11bintlEQ C* scope
v uItYout prl0., c9Fc.rel o
skiing Mcztan
s catill r .auiro Z ram', i!rn
de additional plan 43,/.4 w tea
F.R.O.
9-17-15
16289
JFS
M-1
(E)
RTU-3
WAREHOUSE
®(E)
EXHAUST
FAN
(E)
8X8
SUPPLY
125 CFM tjg
r
ZL1S
1
(E)
10x10
10"
4
12"
10"
(E)
10X1
SUPPLY
250 CFM
SUPPLY
250 CFM
1u
\/I(E)
srr
sump(
250 CFM
L
20X20
14"
16"
J
8X
8xa
(E)
SUPPLY �
125 CFM �_T
(E)
ITID(HAUST
FAN
10"
i
16"
(E)
22X22
1225 CFM
(E)
8X8
SUPPLY
150 CFM
(E)
10X10
SUPPLY
250 CFM
16"
(E)
SUPPLY
250 CFM
D
14"
10" .
ZI(E)
10X10
SUPPLY
250 CFM
14"V
10"
12
J
(E)
10X10
SUPPLY
200 CFM
(E)
10X22
RETUR
200 CFM
10"
(E)
10X10
SUPPLY
250 CFM
(E)
10X10
SUPPLY
250 CFM
(E)
22X22
RETURN
650 CFM
U
(E)
8X8
SUPPLY
150 CFM
(E
2;
RE
1;
14�
X22
TURN
25 CFM
8"
10"
X1OX1
(
SUPPLY
250 CAM
12"
(E)
RYA
SUPPLY
150 CF
(E)
10X22
RETURN
150 CFM
0" (E)
10X10
SUPPLY
250 CFM
1ST FLOOR REVISED HVAC PLAN
rilEVIEVVED FOR
DE,COMPLIANCE
APPri-tOIeQ
SEP 3 0 2015
•
MECHANICAL &
CONTROL SERVICES, INC.
groupres.com
1606 no street fait., WA. 9609
City of Tukwila
BUILDING DIVISION
(E)
22X22
RETURN
800 CFM
(E)
8X8
0
►
SUPPLY
,i511
200 CFM
.
.
.
.
(E)
8X8
EXISTING
]\/SUPPLY
RTU-7
200 CFM
_
OPEN
OFFICE
201
(E)
8X8
E>L.
8XX 8
�
X
SUPPLY
200 CFM
SUPPLY
200 CFM
D Q_I II
c.,f 4�.1
2ND FLOOR REVISED HVAC PLt I TV OF TUKWILA
SEP 1 8 2015
PERMIT CENTER
NGTON 98168
NORTH
F.R.O.
9-17-15
16289
J FS
M-2
REUSE AND/OR
ADD TAKEOFFS
AND DUCT AS
REQUIRED FOR
NEW FLOOR PLAN
EXISTING BRANCH
DUCTWORK
TYPICAL
EXISTING RTU
fll
NSULAOED REDDIE DUCT
DEWED venti too? DuC1
STRIMITEO TA IT(UXE UP SULK)
FAD( DUCT 0 T-EAR CEIUAGS (USE
HARD OUQ 0 OM71 CEIINU;S)�
RUU. RACK ACID t MOUTON FROM CORE 0001,
DOLLECI EXCESS INTER DUCT PAST COUAR MAD UUT&
MLY STRETCHED. THEN OAP AT ILTST TWICE AROUND
URN APPROVED DUCT WE. SECIP MTIM APPROVED CWIP.
PUU. =KET & b'SKUJTD! BACK OVER THE CORE SECURE
J8 31 MAR TWO PAWS OF DUCT TAPE AKD A APPR0.WD
CLAMP. TUCK NI EDGE OF JACKET 0R TAPE
3/8' EGLI ON DJCT CC?L8R F'09
A8TT9IACCHF80 FLU. DUCT (TYPICAL)
SCUM TO ROUND ADAPTOR
FASTENUS, ALL SIOES—
LAT-IN CUING 06fUSER
1-68R CtMUNG
0
3/8'ARS PwIDv.) BV� 08 000T
/ DUCT HWCER (TTP)
7-WNIW. 1OLUM DAMPER
C0.YS1Err/18181 IED PER
01NSTRUCITJN STANDARDS
�MWB!UM 1-1/2 CAUSER
CENTERLINE TURNING RADIUS
TYPICAL ALL FLEX DUCT
FSTAUATIO.N
Two DUCT DIAMETERS
OF STRAIGHT' DUCT
NOTE: USE WOE CLEAR HEW LY CENDC
SPACE /ALDMS 2-DUCT DOWERS OF
SIRVGHT VEHik'AL DUCT.
DETAIL - CEDING SUPPLY DIFFUSER CONNECTION
SCALE: NONE
NEW TBAR CEILING
EXISTING DUCT
DROPS TYPICAL
11
EXISTING DUCTWORK MODIFY AS REQUIRED DRAWING
MECHANICAL &
CONTROL SERVICES, INC.
groupmcs.com
REVEWED FOR
CODE COMPLIANCE
APPROWD
SEP 3 0 2015
City of Tukwila
BUILDING DIVISION
Ri CEl E
CITY OF TLJKWILA
SEP 18 2015
PERMIT CENTER
ROOF
I�\VERIFY EYJSTING DUCTWORK
SUPPORTED PER CODE
RELOCATED
GRD'S TYPICAL
GARAGISTE •
17616 WEST VALLEY HWY
TUKWILA, WA. 98168 1
DETAIL
PAGE
F.R.O.
9-17-15
16289
JFS
M-3
PERMIT COORD COPY
PLAN REVIEW/ROUTING SLIP
PERMIT NUMBER: M15-0120
PROJECT NAME: GARAGISTE
SITE ADDRESS: 17616 W VALLEY HWY
X Original Plan Submittal
Response to Correction Letter #
DATE: 09/21/15
Revision # before Permit Issued
Revision # after Permit Issued
DEPARTMENTS:
Awb �I
Building Division
Public Works
gM n��/`�
Fire Prevention
Structural
El
Planning Division
Permit Coordinator
El
PRELIMINARY REVIEW:
Not Applicable ❑
(no approval/review required)
DATE: 09/22/15
Structural Review Required
REVIEWER'S INITIALS: DATE:
El
APPROVALS OR CORRECTIONS: DUE DATE: 10/20/15
Approved
Corrections Required
Approved with Conditions
Denied
(corrections entered in Reviews) (ie: Zoning Issues)
Notation:
REVIEWER'S INITIALS:
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
12/18/2013
MECHANICAL & CONTROL SRI' �'S INC
Page 1 of 3
Home Inicio en Espanol Contact
Search L&I
A-Z Index Help My Secure L&I
Safety Claims & Insurance Workplace Rights Trades & Licensing
Washington State Department of
Labor & Industries
MECHANICAL & CONTROL SRVCS INC
Owner or tradesperson
Principals
Hull, Travis Edward, PRESIDENT
Hunt, Ted Lamond, VICE PRESIDENT
GROVER, HAROLD, VICE PRESIDENT
(End: 02/26/2010)
DICKSON, PAUL, TREASURER
(End: 02/26/2010)
Doing business as
MECHANICAL & CONTROL SRVCS INC
WA UBI No.
602 338 440
6426 18th St E
FIFE, WA 98424
253-926-9777
PIERCE County
Business type
Corporation
Governing persons
ANGELA
DAWN
HULL
TRAVIS EDWARD HULL;
License
Verify the contractor's active registration / license / certification (depending on trade) and any past violations.
Construction Contractor Active.
.......................................................................
Meets current requirements.
License specialties
GENERAL
License no.
MECHACS962BT
Effective — expiration
01/30/2004— 02/26/2016
Bond
...._...........
American Contractors Indem CO
Bond account no.
100239439
$12,000.00
Received by L&I Effective date
02/10/2014 02/06/2014
Expiration date
Until Canceled
Bond history
Insurance
......................
Ohio Security Ins Co $1,000,000.00
Policy no.
53709396
Received by L&I Effective date
01/22/2015 01/23/2015
Expiration date
https://secure.lni.wa.gov/verify/Detail.aspx?UBI=602338440&LIC=MECHACS962BT&SAW= 10/02/2015