HomeMy WebLinkAboutPermit EL15-0525 - EDDIE BAUER - TENANT IMPROVEMENTEDDIE BAUER
660 SOUTHCENTER MALL
EL15-0525
City of Tukwila
• Department of Community Development
• 6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone:206-431-3670
Inspection Request Line: 206-438-9350
Web site: http://www.TukwilaWA.gov
ELECTRICAL PERMIT
Parcel No:
9202470010
Permit Number: EL15-0525
Address:
660 SOUTHCENTER MALL
Issue Date: 2/19/2016
Permit Expires On: 8/17/2016
Project Name:
EDDIE BAUER
Owner:
Name:
WESTFIELD PROPERTY TAX DEPT
Address:
PO BOX 130940, CARLSBAD, MI,
92013
Contact Person:
Name:
AMY DIEKEVERS
Phone: (616) 493-9334
Address:
75 - 60TH ST SW, WYOMING, MI,
49548
Contractor:
Name:
CORRIDOR ELECTRIC INC
Phone: (360) 862-8062
Address:
408 MAPLE AVE, SNOHOMISH, WA,
98290
License No:
CORRIEI993117
Expiration Date: 12/27/2017
Lender:
Name:
Address:
DESCRIPTION OF WORK:
TENANT IMPROVEMENT
Valuation of single family: $0.00
Fees Collected: $892.62
Valuation of mf/comm: $31,121.00
Type of Work:
Electrical Service Provided by: PUGET SOUND ENERGY
Water District: TUKWILA
Sewer District: TUKWILA SEWER SERVICE
Current Codes adopted by the City of Tukwila:
International Building Code Edition:
2012
National Electrical Code:
2014
International Residential Code Edition:
2012
WA Cities Electrical Code:
2014
International Mechanical Code Edition:
2012
WAC 296-4613:
2014
Uniform Plumbing Code Edition:
2012
WA State Energy Code:
2012
International Fuel Gas Code:
2012
Permit Center Authorized Signature: v Arm( Date:
I hearby certify that I have read and examined this permit and know the same to be true and correct. All
provisions of law and ordinances governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other
state or local laws regulating construction or the performance of work. I am authorized to sign and obtain this
development per 'i4-agree to the conditions attached to this permit.
Signature. Date: -lam
Print Name: ---,'L 1-i-C
This permit shall become null and void if the work is not commenced within 180 days for the date of issuance, or if
the work is suspended or abandoned for a period of 180 days from the last inspection.
PERMIT CONDITIONS:
1: 'ELECTRICAL PERMIT CONDITIONS'
2: A copy of the electrical work permit shall be posted or otherwise made readily accessible to the Electrical
Inspector at each work site.
3: Approved plans shall be maintained at the construction site and shall be readily available to the Electrical
Inspector.
4: All electrical work shall be in accordance with NFPA 70 - NEC, and requirements for electrical installations,
Chapter 296-46B WAC.
5: When any portion of the electrical installation is to be hidden from view by permanent placement of parts
of the building, such equipment shall not be concealed until it has been inspected and approved by the
Electrical Inspector.
6: The issuance of an electrical work permit shall not be construed to be a permit for, or an approval of, any
violation of the provisions of the electrical code or other ordinances of the jurisdiction. Permits or related
documentation that presumes to grant this authority are therefore not valid.
7: Any change in the scope of work described by the electrical work permit shall require additional work
permits. Where approved plans have been issued, revisions to the plans and additional review may be
required.
PERMIT INSPECTIONS REQUIRED
Permit Inspection Line: (206) 438-9350
2100
ELECTRICAL FINAL
7003
ROUGH -IN ELECTRICAL
7002
SERVICE
7001
UNDERGROUND/SLAB
iLA, why CITY OF TUKWILA
o� Community Development Department
Permit Center
6300 Southcenter Blvd., Suite 100
1908 f Tukwila, WA 98188
htto://www. ci. tukwila. wa. us
Electrical Permit No. v M
Project No.
(For office use only) Wr�l
ELECTRICAL PERMIT APPLICATIONXP V 5
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
"Please Print"
SITE LOCATION I
�O King Co Assessor's Tax No.:
Site Address: M Suite Number: Z Floor:
Tenant Name: eta New Tenant: ❑ .....Yes ❑ .. No
Property Owners Name:
Mailing Address:
City State Zip
CONTACT PERSON - Who do we contact when your permit is ready to be issued
Name:
Mailin
E-Mail Address: Q=" r " 1 a 9 U& i �'NU �. (0YV%_ Fax Number: to I La —V 9& '9_�24
ELECTRICAL CONTRACTOR INFORMATION
--� Company Name:
Mailing Address:
�t7
J'
City
State Zip
Contact Person:
Day Telephone:
E-Mail Address:
Fax Number:
Contractor Registration Number:
Expiration Date:
Valuation of Project (contractor's bid price): $ —?-,\ 4
Scope of Work (please provide detailed information):.S(�ck1.�
M�Ci bi
Will service be altered? ❑ Yes No Adding more than 50 amps?
❑ Yes No
ellm
""
Type of Use:(Qr C 1�11�T1
Type of work:
❑ New ❑ Addition ❑ Service Change
Remodel
W Tenant Improvement
❑ Low Voltage ❑ Generator ❑ Fire Alarm
❑ Telecommunication
l
❑ Temporary Service
Property Served by:
❑ Puget Sound Energy
❑ Seattle City Light
H9Applicalions\F-'otms-Applications On llneU-2009 - Electrical Permit Application.dec Page l of 2
bh
RESIDENTIAL
NEW RESIDENTIAL SERVICE
❑ New single family dwellings ................................... $145.60
(including an attached garage)
❑ Garages, pools, spas and outbuildings ........................ $78.00 ea
❑ Low voltage systems
(alarm, furnace thermostat) ................................ $57.00 ea
RESIDENTIAL REMODEL AND SERVICE CHANGES
❑
Service change or alteration ......................................
$78.00
(no added/altered circuits)
❑
Service change with added/altered circuits.................$78.00
number of added circuits .......................$11.00
ea
❑
Circuits added/altered without service change ...........
$52.00
(up to 5 circuits)
❑
Circuits added/altered without service change ...........
$52.00
(6 or more circuits) ...............................................
$7.30 ea
❑
Meter/mast repair .......................................................
$65.00
❑
Low voltage systems .................................................
$57.00
(alarm, furnace thermostat)
PERMIT APPLICATION NOTES -
MULTI -FAMILY AND COMMERCIAL
Fees are based on the valuation of the electrical contract.
MISCELLANEOUS FEES
❑ Temporary service (residential) .................................
$60.00
❑ Temporary service (generator) ...................................
$75.00
❑ Manufactured/mobile home service ...........................
$80.00
(excluding garage or outbuilding)
❑ Carnivals....................................................................$75.00
Number of concessions .........................
$10.00 ea
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review — Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The Building Official may grant one extension of time for an additional period not to exceed 90 days. The extension shall be requested in writing
and justifiable cause demonstrated.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWNER R ELECTRICAL CONTRACTOR:
Date: 6, -LA -
— City State Zip
Date Application Accepted: Date Application Expires: Staff Initials:
H:\Applications\Fortes-Applications On Line\I-2009 - Electrical Permit Application.doc Page 2 of 2
bh
DESCRIPTIONS
PermitTRAK
ACCOUNTQUANTITY
PAID
$727.32
EL15-0525 Address: 660 SOUTHCENTER MALL
Apn: 9202470010
$727.32
ELECTRICAL
$661.20
PERMIT FEE MULTI-FAM/COMM
R000.322.101.00.00
0.00
$661.20
TECHNOLOGY FEE
$66.12
TECHNOLOGY FEE
R000.322.900.04.00 0.00
$33.06
TECHNOLOGY FEE
TOTAL6..
R000.322.900.04.00 0.00
$33.06
Date Paid: Tuesday, February 16, 2016
Paid By: CASSNIK CONTRACTING LLC
Pay Method: CHECK 003131
Printed: Tuesday, February 16, 2016 10:55 AM 1 of 1
p"fSYSTEMS
DESCRIPTIONS
PermitTRAK
ACCOUNT QUANTITY
PAID
$1,948.77
D15-0132 Address: 660 SOUTHCENTER MALL
Apn: 9202470010
$1,678.69
DEVELOPMENT
$1,678.69
PLAN CHECK FEE
11000.345.830.00.00
0.00
$1,678.69
EL15-0525 Address: 660 SOUTHCENTER MALL
Apn: 9202470010
$165.30
ELECTRICAL
$165.30
PLAN CHECK FEE
R000.345.832.00.00
0.00
$165.30
M15-0071 Address: 660 SOUTHCENTER MALL
Apn: 9202470010
$69.90
MECHANICAL
$69.90
PLAN CHECK FEE
R000.322.102.00.00
0.00
$69.90
PG15-0069 Address: 660 SOUTHCENTER MALL
Apn: 9202470010
$34.88
PLUMBING
$34.88
PLAN CHECK FEE
TOTAL
R000.322.103.00.00 0.00
$34.88
Date Paid: Tuesday, June 09, 2015
Paid By: PRECISION PERMIT
Pay Method: CHECK 13465
Printed: Tuesday, June 09, 2015 1:03 PM 1 of 1 07W SY57EMS
INSPECTION RECORD
Retain a copy with permit ���
INSPECTION N0. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd.., #100, Tukwila. WA 98188 (206) 431-367
Permit Inspection Request Line (206) 438-9350
Project: !!
�%b &A tG
Type of Inspection:
Address: 67, NZ
Date Called:
Special Instructions: t
Date Wanted: a.
.m.
Requester:
L
Phone No:
Z 7o �Z
N./ Approved per applicable codes. E Corrections required prior to approval.
Ur-qS I Aj�
nspector:
ate:
El REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
INSPECTION RECORD
3 Retain a copy with permiejit )
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd.., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 438-9350
Project:
Type of Inspection:,
Address:
Date Called:
Special Instructions:
Date Wanted:
p•
Requester:
Phone No:
Approved per applicable codes. 1-1 Corrections required prior to approval.
COMMENTS:
I �� (>
2-0
IInspector: � lj1-1 P Kb /f-V IDate: oio(o / j&
REINSPECTION FEE REQUIRVD. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
INSPECTION RECORD / ,
Retain a copy with permits
INSPECTION NO. PERMIT NO. ,
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 438-9350
Project: Ab1C � &�
Type of Inspection:
Address:
6 70
Date Called:
Special Instructions
Date Wanted:
p.m
Requester:
Approved per applicable codes. E Corrections required prior, to approval.
U paid at 6300 Southcenter Blvd.. Suite 100. Catt to schedule reinspection.
INSPECTION RECORD
Retain a copy with permit��
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 438-9350
Project: ,
1 (WK
Type of Inspectio
.a
Address: 6(0 q4v
Date Called:
Special Instructions: I
Date Wanted:
Requester:
Phone No: r o u
EDApproved per applicable codes. E Corrections required prior to approval.
I Kn Ad- (r� �flflci�
03
REINSPECTION FEE REQUIRED. Prior to next inspection; fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
INSPECTION RECORD,--t
Retain a copy with permit
INSPEC11ON NO. PERMIT N0.
CITY O TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line(206) 438-935
ProjectType
L�'If" .I� ft�r.w
a In on:
Address,
Date Called: `
Special Instructions.
Date ante : a.m.
p.m.
quester:
PhoneA;
If
NA w
roved per applicable codes.Carrectians required prior to approval.
r5aiRENTS.
WHSPC t N FEIr �€�IRM. Prior to next inspection, fee must be
perld # tout#icont+er Blvd. Suite 100. Cali, to schedule reinsrpection
►FA-
RE
%OV
2012 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised Jan 2014
Project Info
Project Address EDDIE BAUER
Date 5/5/2015
Compliance
forms do not
SOUTHCENTER MALL
For Building Department Use
SEATLE, WA.
require a
password to
use.
Applicant Name: CALVIN.T CHHUOR
Instructional and
calculating cells
Applicant Address: 1750 COMMERCE COURT WHITE BEAR LAKE MN.55110
are write-
�
Applicant Phone: 661-748-1100
Project Description
ElNew Building ElAddition Alteration El Plans Included
Lighting Compliance Path
O Lighting Power Density Calculations Q Total Building Performance
(if Total Building Performance then only LGT-CHK is required.)
Lighting Power Allowance
Method Selection required to
Q Building Area Method QQ Space -By -Space Method
enable LPA forms
Interior Lighting System R EC E i'; E D
Description CITY OF TUKWILA
Briefly describe lighting
012015
,JUN
system type and features.
PERMIT CENTER
Additions and Change of Space Use•(C101.4.3 & C101.4.4)
121 Addition area or Change of Space Use area complies with all applicable provisions as stand alone project
❑ Addition area is combined with existing building lighting systems to demonstrate compliance with all applicable
provisions per C101.4.3
Provide Building Area Method (LTG-INT-BLD) or Space -By -Space Method (LTG-INT-SPACE) Compliance Form. Document maximum
allowed and proposed (including existing if applicable) lighting wattage of Addition or Change of Use space. Provide applicable lighting
controls per C405.2 and commissioning of lighting controls per C405.13,,
Alterations, Renovations and Repairs (C101.4.3.1)
❑✓ 60% or more of luminaires in space replaced
Provide Building Area Method (LTG-INT-BLD) or Space -By -Space Method (L TG- INT-SPACE) CompQance Form. Document maximum
allowed wattage within the lighting retrofit space in Maximum Allowed Wattage table and proposed (including existing) lighting wattage in
Proposed Wattage table. Retrofit and non -retrofit spaces shall be documented separatdly using multiple forms.
❑ Less than 60% of luminaires in space replaced
Provide a separate Space -By -Space Method (LTG-INT-SPACE) Compliance Form for this retrofit area. Document existing total wattage
within the lighting retrofit space in cell provided in the Maximum Allowed Wattage table. Document proposed (including existing) lighting
wattage in the Proposed Wattage table.
:. ❑ Lamp and/or ballast replacement within existing luminaires only — existing total interior building wattage not increased
New wiring installed to serve added fixtures and/or fixtures relocated to new circuit
w . Provide applicable manual lighting controls (C405.2.1), occupancy sensors (C405.2.2.2), daylight zone controls (C405.2.2.3), specific
application controls (C405.2,3), and commissioning of lighting controls per C405.13
❑ New or moved lighting panel
Provide all applicable lighting controls as noted for New Wiring, automatic time switch controls (C405.2.2.1), and commissioning of lighting
1"MSP%9405.13.
S e- luminaires unchanged or moved only
PLCM§ft 00Hb/
lighting controls as noted for New Wiring and commissioning of lighting controls per C405.13.
A -96
o chVjFraire bein
made to the interior lighting and space use not changed.
JUN 2 4 2015
City of Tukwila
BUILDING DIVISION_'
t"l 0 W)C/
!1,
2012 Washington State Energy Code Compliance Forms for Commercial Buildinas inch,dinn R9 x Rs nvar a ttAriac —i �u o1
Project Address EDDIE BAUER
Date 5/5/2015
Lighting Alterations, Renovations & Building Additions
For Building Department Use
O Less than 60% 60% or more O Stand alone O Addition
ote .
L-- hti g fix' re s i a wilding a diti0n may comply as a stand alone project, or they maybe
combs ad h tip oerall ezis ng b/dg lighting to demonstrate compliance. Refer to C101.4.3.
b. or re fits aat) sliding addit%One, provide Space Types and gross interior areas in the
aximum (lowed Lighting table. if a builidng addition will comply as combined with the overall
existing builidng, include all applicable existing Space Types and gross interior areas
c. Document new fixtures and all existing to remain fixtures in the Proposed Lighting table.
d. If less than 60% of existing fixtures will be replaced, provide total existing lighting wattage
(prior to retrofit) in the space provided in the Maximum Allowed Lighting table.
Specify Compliance .Method on LGT-SUM
Location (plan #,
owe
rose Interior
WAs owe
room #)
Space Type*
Watts per ft2
Area in ft2
(watts/ft2 x area)
SALES AREA
Retail: Sales area
1.68
3205
5384
STOCKROOM,
Storage , —
0.63
588
370
TOILET ROOM
Restioom
0.98
62
61
Atrium" Enter Height:
Existing Lighting Enter Exist Watts:
DISPLAY
Retail Display Allowance from LTG-iNT-DISPLAY
552
" Select Table C405.5.2(2) category from drop down menu.
** For atriums, indicate height. Allowed wattage for first 40 feet is 0.03 W/Yt. ht ,
above 40 feet is 0.02 W/ft. ht.
Specify Compliance Method on LGT-SUM
Area Allowed Watts
Total 3855 6368
Location (plan #,
room #)
Fixture Description``*
Number of
Fixtures
Watts/
Fixture
Watts
Proposed
SALES AREA
TYPE F2 TRACK WITH 2A CURRENT LIMITING
192
SALES AREA
TYPE F2 TRACK WITH 4A CURRENT LIMITING
1
384
384
SALES AREA
TYPE F2 TRACK WITH 10A CURRENT LIMITING
3
960
2880
SALES AREA
TYPE F2 TRACK WITH 12A CURRENT LIMITING
1
1152
1152
SALES AREA
TYPE E
90
STOCKROOM
TYPEDIDD
14
58
812
TOILET ROOM
TYPE J
1
120
120
Retail Display Lighting from LTG-INT-DISPLAY
552
Total Proposed Watts may not exceed Total Allowed Watts for Interior Lighting Total Proposed Wattl 5 900
*" Include existing to remain lighting fixtures and exempt lighting equipment per notes below.
Notes:
1, Include ALL proposed lighting fixtures,
2. For proposed Fixture Description, indicate fixture type, lamp type (e.g. T-8), number of lamps in the fixture, and ballast type 0f included). For
track lighting, list the length of the track (in feet) in addition to the fixture, lamp, and ballast information.
3. For proposed Watts✓Fixture, use manufacturer's listed maximum input wattage of the fixture (not simply the lamp wattage) and other criteria
as specified in Section C405.5.1. For line voltage track lighting, list the greater of actual luminaire wattage or length of track multiplied by 50,
or as applicable, the wattage of current limiting devices of the transformer. For low voltage track lighting list the transformer rated wattage.
4. For lighting equipment eligible for exemption per C405.5.1, note exception number and leave Watts/Fixture blank.
5. Document existing to remain fixtures in Proposed Lighting table in the same manner as new fixtures. Identify as existing in fixture description
6, If #NA appears in Retail Display cells, information on L TG-INT-DISPLA Y is incomplete.
(Interior Lighting Power Allowance Building Area Method Selected. Use LTG-INT-BLD,
t
2012 Washington State Energy Code Compliance Forms for Commercial Buildlnns includinn R9 R Rs nvAr q c,nric nn l "u rs, o
Project ITlfO
�
.Project Address EDDIE BAUER
Date 5/5/2015
SOUTHCENTER MALL
For Building Department Use
SEATLE, WA.
Applicant Name: CALVIN.T CHHUOR
Specify Compliance Method on LGT-SUM
Location (plan #,
room #)
Retail Display Area Type*
owe _
Watts per ftz **
Gross n enor
Area in ft2
Wat s owe
(watts/ft2 x area)
DISPLAY
Retail 3: Furniture, clothing, cosmetics, artwork
1.40
500
700
* Only retail sales areas that meet the requirements defined in Table C405.5.2(2) Area Area Watts
footnote A may be entered here. Select retail sales areas form drop down menu. Total 500 700
Wattages per Table C405,5,2(2) footnote A.
++ Display light allowance per footnote A calculation. Display Lighting Base Allowance 500
++ Total Display Allowance 1200
Specify Compliance Method on l...GT-SUM
Oi)lir SEpafatelit controlled disnlav fixtures indr npnrfnnt of nnnraral anon rtni,ti,,,, „— T.M. rangy n . ..... _._
Display Area*
Location (plan #,
room #)
Fixture Description
Number of
Fixtures
Watts/
Fixture
Watts
Proposed
Retail 3
SALES AREA
TRACK 2A CURRENT LIMITING
1
192
192
Retail 3
SALES AREA
TYPE "E"
4
90
360
. —u- icier sates urspiay area from drop down menu.
Total Proposed WattsL 552
r--
Proposed Display Retail t Retail Retail 3 Retail
Lighting Totals 552
Notes:
1. Forproposed Display Fixture Description, indicate fixture type, lamp type (e.g. T-B), number of lamps in the fixture, and ballast type (if
included). For track lighting, list the length of the track (in feet) in addition to the fixture, lamp, and ballast information.
2. For proposed Watts/Fixture, use manufacturer's listed maximum input wattage of the fixture (not simply the lamp wattage) and other
criteria as specified in Section C405.5,1. For line voltage track lighting, list the greater of actual luminaire wattage or length of track
multiplied by 50, or as applicable, the wattage of current limiting devices or of the transformer. For low voltage track lighting list the
transformer rated wattage.
3. List all display fixtures.
•
City of Tukwila Jim Haggerton, Mayor
• Department of Community Development Jack Pace, Director
December 1, 2015
Amy Diekevers
Precision Permit Services
75 60`h St SW
Wyoming, MI 49548
RE: Request for Application Extension
Eddie Bauer— 660 Southcenter Mall
Dear Ms. Diekevers,
This letter is in response to your written request for an extension to Application Number EL15-0525. The
Building Official has reviewed your letter and considered your request to extend the above referenced
application. It has been determined that the City of Tukwila Building Division will be extending your
permit application an additional 180 days, through June 9, 2016.
If you should have any questions, please contact our office at (206) 431-3670 extension 1.
Sincerely,
Bill Rambo
Permit Technician
File: Permit EL15-0525
WAPertnit CenteAExtension Letters\Applications\2015\EL15-0525App Extension Letter. docx
6300 Southcenter Boulevard, Suite #100 0 Tukwila, Washington 98188 • Phone 206-431-3670 • Fax 206-431-3665
Bill Rambo
From: Amy Diekevers <amyd@precisionpermits.com>
Sent: Friday, November 20, 2015 11:05 AM
To: Bill Rambo
Subject: Request for Plan Review Extensions EDDIE BAUER SOUTHCENTER
Attachments: EL15-0525.pdf; PG15-0069.pdf; M15-0071.pdf; D15-0132.pdf
Importance: High
Per the attached notices, I am requesting plan review approval extensions on all of them.
We are scheduled to start construction on 2/ 1/ 16.
Let me know if this is enough to extend the approvals or if there is something additional I need to do.
Thant? you,
Precision Permit Services
75 60th St SW
V✓yoniing MI 49548
616-493-9334 ph
616-493-9351 fax
Request for Extension #
Current Expiration bate:
Extension Request:
Approved for ORO days
Y
❑ Denied (provide explanation)
Signature/Initials
f
1
City of Tukwila
� Jim Haggerton, Mayor
Department of Community Development Jack Pace, Director
November 4, 2015
AMY DIEKEVERS
75 60TH ST SW
WYOMING, MI 49548
RE: Application No. EL15-0525
EDDIE BAUER
660 SOUTHCENTER MALL
Dear AMY DIEKEVERS:
Permit application EL15-0525 for the work proposed at EDDIE BAUER (660 SOUTHCENTER MALL) has not been issued by the
City of Tukwila Permit Center. Per the International Building, Residential, and Mechanical Codes as well as the Uniform Plumbing
Code and/or the National Electric Code, every permit application not issued within 180 days from the date of application shall expire
and become null and void. Currently your application has a status of APPROVED and is due to expire 12/09/2015.
If you still plan to pursue your project, you are hereby advised to do one of the following:
1) If the plan review is completed for the project and your application is approved, you may pick up the application before
the date of expiration. At the time of permit issuance the expiration date will automatically be extended 180 days.
-or-
2) If the plan review is not completed submit a written request for application extension (7) seven days in advance of the
expiration date. Address your extension request to the Building Official and state your reason(s) for the need to extend your
application.
The Building Code does allow the Building Official to approve one extension of up to 90 days. If it is determined that your extension
request is granted, you will be notified by mail.
In the event that your permit is not issued, we do not receive your written request for extension, or your request is denied your permit
application will expire and your project will require a new permit application, plans and specifications, and associated fees.
Thank you for your cooperation in this matter.
Sincerely,
� I
Bill Rambo
Permit Technician
File No: ELI5-0525
6300 Southcenter Boulevard Suite #100 • Tukwila, Washington 98188 * Phone 206-431-3670 • Fax 206-431-3665
. s'RMIT COORD COPY
PLAN REVIEW/ROUTING SLIP
PERMIT NUMBER: EL15-0525 DATE: 06/15/15
PROJECT NAME: EDDIE BAUER
SITE ADDRESS: 660 SOUTHCENTER MALL
X Original Plan Submittal Revision # before Permit Issued
Response to Correction Letter # Revision # after Permit Issued
DEPARTMENTS:
�! .W
(- - �-� s-
Building Division Fire Prevention Planning Division
Public Works ❑ Structural ❑ Permit Coordinator ❑
PRELIMINARY REVIEW: DATE: 06/16/15
Not Applicable ❑ Structural Review Required ❑
(no approval review required)
REVIEWER'S INITIALS: DATE:
APPROVALS OR CORRECTIONS: DUE DATE: 07/14/2015
Approved ❑ Approved with Conditions
Corrections Required ❑ Denied ❑
(corrections entered in Reviews) (ie: Zoning Issues)
Notation:
REVIEWER'S INITIALS: DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
12/18/2013
CORRIDOR ELECTRIC INC
Page 1 of 3
Home Espanol Contact.
Safety & Health
(3 Washington State Department of
Labor & Industries
CORRIDOR ELECTRIC INC
Search L&I � ��rr
A-'L IndeA Help My Secure I,&I
Claims & Insurance Workplace Rights Trades & Licensing
Owner or tradesperson
408 MAPLE AVENUE
SNOHOMISH, WA98290
Principals
360-862-8062
BERGMAN, STEVEN P, PRESIDENT
SNOHOMISH County
Bergman, Terri A, VICE PRESIDENT
BERGMAN, STEVEN P, AGENT
BERGMAN, STEVEN P, VICE PRESIDENT
(End: 02/25/2011)
Doing business as
CORRIDOR ELECTRIC INC
WA UBI No. Business type
602 165 975 Corporation
Governing persons
STEVEN
PETER
BERGMAN
TERRI ANN BERGMAN;
License
Verify the contractor's active registration / license / certification (depending on trade) and any past violations.
Electrical Contractor Active.
.......................................................... .
Meets current requirements.
License specialties
GENERAL
License no.
CORRIE1993R7
Effective — expiration
12/27/2001-12/27/2017
Designated administrator
BERGMAN, STEVEN P
License type
Master Electrician
Bond
American Contractors Indem CO
Bond account no.
100170133
Received by L&I
09/21/2011
Bond history
Savings
Savings history
Active.
Meets current requirements.
License no.
BERGMSP965DD
$4,000.00
Effective date
07/18/2011
Expiration date
Until Canceled
'Ms-oR9)- la-1-7
https://secure.lni.wa.gov/verify/Detail.aspx?UBI=602165975&LIC=CORRIE1993R7&SAW= 2/19/2016
U
# O25
24 J
s 27
1�IKP
z1 1z
PANEL LA -
OPANEL
0 P
LA-24 32
® F( ACP� LB-13
El
LA-33
LA-39
LA-35
N
DO NOT PLACE ANYTHING ON THE BACKWRAP
WALL EXCEPT BACKWRAP EQUIPMENT.
83-
1 /4" = 1'-0"
40-1"
72—i"
1 60-1j"
NITS
LA-37
LA-33
40—J'
:, e ;, is gl 1, •
GENERAL NOTES
A. CONTRACTOR SHALL COMPLETELY REMOVE ALL EQUIPMENT, PANELBOARDS,
DEVICES, FIXTURES, WIRING, CONDUIT, ETC. AND ALL ASSOCIATED SUPPORTS,
BRACING, PADS, ETC. NOT BEING REUSED OR SHOWN TO REMAIN WHETHER IN
THE DEMISED SPACE, ON THE ROOF OR OTHERWISE LOCATED OUTSIDE OF THE
DEMISED SPACE. DO NOT ABANDON IN PLACE.
B. ALL 120 VOLT BRANCH CIRCUITS IN EXCESS OF 75' SHALL HAVE CONDUCTOR
SIZE INCREASED A MINIMUM OF 1 CONDUCTOR SIZE. INSTALLING CONTRACTOR
SHALL DETERMINE ACTUAL CONDUCTOR SIZE TO BE INSTALLED TO ADHERE TO
VOLTAGE DROP REQUIREMENTS.
C. REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR ALL DEVICE LOCATIONS
PRIOR TO ROUGH -IN. FIELD COORDINATE WITH OWNERS REPRESENTATIVE.
D. REFER TO SHEET E4 FOR ELECTRICAL SYMBOL LEGEND.
E. PAINT ALL EXPOSED ELECTRICAL CONDUIT, JUNCTION BOXES, CONNECTORS, WIRE,
LIGHT FIXTURE SUPPORT RODS/CHAINS, EQUIPMENT SUPPORT ROD/CHAINS,
PLATFORMS, ETC. COLORS AS INDICATED ON ARCHITECTURAL REFLECTED CEILING
PLAN TO MATCH CEILING.
F. ADD A BLANK COVER PLATE TO ALL OPEN J-BOXES AFTER A/V AND
COMMUNICATION SYSTEMS INSTALLATION IS COMPLETE.
LA-39
.......... _... _.......
_.
................
28 ii --
I
A.F.F.
LA-10-\ LA-10-,
Kf•1
:r-i;vsiT
�a �12ZED FOR:
l F.I b.lia lical
0-Electrical
IfPiumbing
[Zocas PVmg
of Tukwffa
; .3 DfVDS30'Ni
FILE CORI
Permit Me. _h S_ ft. 0 S�Ar
Plan review approval is subject to c. rors and orni:;&71ons.
Appiraval of construction documents does not authorize
the violation of any adopted code or ordinance. Receipt
of approved Field Copy d conditions is acknowledged:
B. .
Date:
City of Tukwila
BUILDING DIVISION
REV►Sl4NS
No changes shall be made to the scope
t71 Wvork f' 11ou€t prior to
of
}"� Division.
�� rila Building stun.
;a;;uire a near
El to may inc'::de d �' plan submittal2,�d?banal plan r2�ri^t}r fuss.
KEY NOTES THIS DRAWING
REVIEWED.FOR
COMPLIANCE WITH
NFPA 70 - NEC
JUN 2 4 2015
City oflulwila
BUILDING DIVISION
O1 ELECTRICAL EQUIPMENT LOCATION. REFER TO ELECTRICAL PANEL SCHEDULES 18 AT PROCESSING COUNTER IN STOCK ROOM PROVIDE:.
AND POWER RISER DIAGRAM ON SHEET E3 FOR FURTHER INFORMATION. 2)DUPLEX RECEPTACLES AT 49" A.F.F., EACH WITH ITS OWN DEDICATED CIRCUIT.
1 FOURPLEX CONVENIENCE RECEPTACLE AT 49" A.F.F.
O2 FOR VIDEO ARRAY AT FOCAL WALL, PROVIDE (2) RECESSED QUAD RECEPTACLES 1PHONE ROUGH —IN FOR MODEM AT 49" A.F.F. — EXTEND 3/4" CONDUIT FROM
AND (1) 4x4x2 BOX WITH SINGLE GANG MUD RING FOR LOW VOLTAGE CABLING. ROUGH —IN TO HIGH ON WALL.
PROVIDE A SEPARATE DEDICATED 120V CIRCUIT FOR EACH QUAD RECEPTACLE (2 (1)ROUGH—IN FOR WALL PHONE AT 60" A.F.F. — EXTEND 3/4" CONDUIT FROM
TOTAL). REFER TO DETAIL 3 THIS SHEET FOR MOUNTING HEIGHTS. ROUGH —IN TO HIGH ON WALL.
O3 PROVIDE 1 1/4" EMPTY CONDUIT WITH PULLSTRING TO BACKBOARD AT 19 PROVIDE ROUGH —IN AND FINAL CONNECTION TO 120V HAND DRYER. COORDINATE
DATA/EQUIPMENT RACK FOR DATA LINE. EXACT LOCATION PRIOR TO ROUGH —IN.
O4 ELECTRICAL CONTRACTOR TO PROVIDE 1" EMPTY CONDUIT AND PULLSTRING TO 20 EXISTING 120V, 1.5 KW WATER HEATER LOCATED ABOVE TOILET ROOM TO REMAIN.
BACKBOARD AT DATA/EQUIPMENT RACK FOR CASH WRAP TELEPHONE AND VERIFY EXACT LOCATION.
DATACOMM.
21 CONTRACTOR SHALL MAKE ARRANGEMENTS WITH LANDLORD FOR INSTALLATION OF
O5 CHANNEL FLOOR FOR NEW CONDUITS, STUB UP BENEATH CASH WRAP DESK. TELEPHONE BOARD. CONTACT LOCAL UTILITY FOR SERVICE. TELEPHONE
ROUTING SHOWN FOR REFERENCE ONLY. ROUTE CONDUITS VIA THE SHORTEST EQUIPMENT SHALL BE INSTALLED BY COMMUNICATIONS SUB —CONTRACTOR. REUSE
PATH POSSIBLE. EXISTING IF APPLICABLE.
O6 AT EACH LOCATION NOTED AT CASH WRAP DESK PROVIDE: 9> PROVIDE NEW TIME CLOCK AND CONTACTORS. REFER TO SHEET E2 FOR
(1)DEDICATED GROUND DUPLEX RECEPTACLE FOR P.O.S. TERMINALS, CIRCUIT AS FURTHER INFORMATION AND DETAIL 5/E3.
INDICATED.
�1�CONVENIENCE DUPLEX RECEPTACLE, CIRCUIT AS INDICATED. INSTALL DOOR BUZZER SIGNALING DEVICE AND LV TRANSFORMER AT 7'-6"
123SINGLE GANG BOX FOR TELEPHONE AND DATACOMM. ABOVE STOCK FLOOR. CONNECT TO STOCK RECEPTACLE CIRCUIT. INSTALL DOOR
CONDUIT FOR POWER AND COMMUNICATION CABLING TO RECEPTACLES AND BUZZER RECESSED IN WALL NEAR REAR DOOR.
TECHNOLOGY DEVICES TO BE ROUTED ON FLOOR BENEATH CASH WRAP DESK.
<24> PROVIDE DOOR BUZZER PUSH BUTTON AT 48" A.F.F.. EXTEND BELL WIRE IN
O7 INSTALL DOOR BUZZER 11'-6" OFF CASH WRAP CABINET FACE AND EXTEND BELL 3/4" CONDUIT TO SIGNALING TRANSFORMER IN STOCKROOM. SEE DETAIL 2 ON
WIRE TO SIGNALING TRANSFORMER CALLED OUT IN KEY NOTE #26. SEE DETAIL SHEET E3.
2 ON SHEET E3.
25 LOCATION OF BATTERY POWERED DETEX. FURNISHED BY OWNER, INSTALLED BY
< PROVIDE ROUGH —IN FOR SECURITY CONTACT AT BASE OF DOOR. EXTEND 3/4" CONTRACTOR.
CONDUIT FROM CONTACTOR LOCATION AND STUB OUT HIGH ON WALL. VERIFY
EXACT ROUGH —IN REQUIREMENTS PRIOR TO COMMENCING ANY WORK. 26 PROVIDE ROUGH —IN FOR SECURITY DOOR SWITCH CONNECTION AT HEAD OF DOOR
ON STRIKE SIDE OF DOOR AND STUB OUT HIGH ON WALL. VERIFY EXACT
O9 FOR SHOPPERTRAK: LOCATE J—BOX 1'—O" FROM ENTRY CENTERED ON DOOR ROUGH —IN REQUIREMENTS PRIOR TO COMMENCING ANY WORK.
WITH A CAT 5, 4 PAIR PLENUM RATED CABLE FROM J—BOX TO THE EQUIPMENT
RACK WITH 20" OF CABLE COILED AT BOTH ENDS. 27 PROVIDE ROUGH —IN AT 48" A.F.F. FOR SECURITY SYSTEM KEYPAD. EXTEND 3/4"
CONDUIT HIGH ON WALL. KEYPAD SHALL BE INSTALLED BY SECURITY SYSTEM
10 LOCATION OF SECURITY ALARM HORN — FURNISHED AND INSTALLED BY OWNERS SUB —CONTRACTOR. VERIFY EXACT ROUGH —IN REQUIREMENTS PRIOR TO
SUB —CONTRACTOR. INDICATED HERE FOR REFERENCE ONLY. COMMENCING ANY WORK.
11 LOCATION OF DIRECTIONAL INFRARED MOTION DETECTOR FURNISHED AND <0>PROVIDE PHONE JACK AND SINGLE GANG BOX AT 50-1/2" A.F.F..
INSTALLED BY OWNERS SUB —CONTRACTOR. PROVIDE SINGLE GANG BOX WITH
COVERPLATE AND EXTEND 3/4" CONDUIT TO VICINITY OF DATA EQUIPMENT IN 29 EXISTING HVAC UNITS (FCU—EX-1 & HP—EX-1), 480V/30, TO REMAIN. MAINTAIN
OFFICE. VERIFY EXACT ROUGH —IN REQUIREMENTS PRIOR TO COMMENCING ANY EXISTING FEEDERS AND CIRCUITING. VERIFY EXACT LOCATION WITH MECHANICAL
WORK * 12 PROVIDE WALL MOUNTED DUPLEX RECEPTACLE 6" ABOVE SHOW WINDOW. COLOR
CONTRACTOR. RE:;EiVED
TO MATCH ADJACENT SURFACE. ROUTE CIRCUIT VIA CONTACTOR C3. 30 NOT USED. Ci T Y OF TUKW LA
13 EQUIPMENT RACK LOCATION. REFER TO 1/E3 FOR FURTHER INFORMATION. JUN -9-9 201
31 NOT USED.
14 PROVIDE FLUSH MOUNTED SINGLE GANG BOX WITH COVER AT 9'-0" A.F.F. FOR PERMIT CENTER
OWNER SUPPLIED STOCKROOM SPEAKER. PROVIDE SINGLE GANG BOX WITH 32 PROVIDE FIRE ALARM DEVICES AS INDICATED AND CONNECT TO LANDLORDS FIRE
COVER AT 48" A.F.F. FOR OWNER SUPPLIED VOLUME CONTROL FOR STOCKROOM ALARM SYSTEM. COORDINATE EXACT REQUIREMENTS WITH LANDLORD FIRE ALARM
SPEAKER. PROVIDE 3/4" CONDUIT FOR CONTROL WIRE FROM VOLUME CONTROL CONTRACTOR PRIOR TO BID AND INSTALLATION. REUSE/RELOCATE EXISTING
LOCATION TO WALL MOUNTED SPEAKER. DEVICES IF APPLICABLE. FIRE ALARM DEVICE LOCATIONS ARE SHOWN FOR
REFERENCE ONLY. FINAL LOCATIONS NEED TO BE INSTALLED PER CODE AND
15 NOT USED. ARE THE RESPONSIBILITY OF THE CONTRACTOR INSTALLING IT.
16 NOT USED.
17 AT BREAK COUNTER PROVIDE:
(1)DUPLEX RECEPTACLE AT 15" A.F.F. FOR REFRIGERATOR.
1 DUPLEX RECEPTACLE AT 40" A.F.F. FOR MICROWAVE.
REFER TO BREAK COUNTER DETAIL ON SHEET A11 FOR EXACT LOCATION OF
DEVICES. 61
I:II�I�7�
PANEL LB
PANEL LB
I91 1
ic.
W.oIll—
D [
LA-23cI I LA-
LA-13
F2 14)
LA-13
LA-5 /
��j is wLA-1I I " EM " 5
LA-1 O
F LS) 1� F L7)
LA-11 LA-11
w w
u TYP.
LA-5 F2L0,
-
10A 5
F L8)
LA-5 t,-n
F?L6)
LA-11
G 11
LA-15 0 LA-7
FZL7) 10A V FLA 8)
LA-7
-...__.......
(PLEASE DON' T FORGET TO INCLUDE THIS REV70 LAYER WITH NEXT REVISION)
w 11Y
�tf
LA-9
F L8) F L8)
LA-11 LA-11
TYP.
DO NOT PLACE ANYTHING ON THE BACKWRAP
WALL EXCEPT BACKWRAP EQUIPMENT.
NOTE:
FEEDER CONDUCTORS SHALL BE SIZED FOR A MAXIMUM VOLTAGE
DROP OF 2 PERCENT AT DESIGN LOAD. BRANCH CIRCUIT
CONDUCTORS MUST BE SIZED FOR A MAXIMUM VOLTAGE DROP OF
3 PERCENT AT DESIGN LOAD.
CIRCUIT IDENTIFICATION
XX FIXTURE TYPE
R-5c PANEL & CIRCUIT NUMBER
C2f CONTACTOR NUMBER
SWITCH CONTROL
CURRENT LIMITING DEVICE SCHEDULE
TAG
LIGHTOLIER CATALOG #
DESCRIPTION
WATT
RATING
80% MAX
LOAD
2A
PLD240WH
2A CURRENT LIMITING DEVICE
240W
192W
4A
PLD480WH
4A CURRENT LIMITING DEVICE
48OW
384W
10A
I PLD1200WH
10A CURRENT LIMITING DEVICE
120OW
960W
INSTALLED FIXTURE WATTAGE IS NOT TO EXCEED 80% OF CURRENT LIMITER RATING.
CONTACTOR SCHEDULE
MARK
AREA
CONTROL
COIL
LINE
POLE
AMP
CIRCUITS CONTROLLED
C1
PERIMETER
SWITCH a
120
120
8
20
LA-5,7,13,29
TRACK
C2
SALES AREA
SWITCH b
120
120
6
20
LA-9,11
GENERAL
C3
I STOREFRONT
TIME CLOCK
120
120
6
20
LA-3,17,25,27
1 /4„ = 1'-011
F�8)
LA-9
F�8)
LA-9
1
F2L8) F L8)
LA-9 rF�6) LA-9
A-9ir
G 0 <8>
LA-15
I
F L7)
v-7 LA-7
LA-3
Y `'�
I� .2A'
OV EM V
LA-1 F2C10)
I
LA-5
3
l
a
F L8)
3:
•a
LA-9
d
F25)
I
-.. ....
XRLA-1
j
LA-17
, CJ
�.
0 • LA �3
I
...._l
.................
LA-3
LK 1
F�8)
LA-7
I
OEM
LA-1
_...................._._...................-......._........................ __.__......... __ ........
,,
LIGHTFIXTURE SCHEDULE
PLAN MARK
LOCATION'
DESCRIPTION
MANUFACTURER
CATALOG#
VOLTAGE
PHILIPS
LAMP
DATA
MOUNTING.
REMARKS
FURN. BY
TYPE
WATT
NO.
MODEL NO.
LOCATION
TYPE
CHAIN HUNG W FLUOR
WLM 76-4-232-QS-EB2-
CHAIN
D
STOCKROOM
WILLIAMS
12a,
FLUOR
32
2
F32T8/TL830
CEILING
EB
WITH SOLID REFECTORS
AD-BD-UNV
HUNG
--
CHAIN HUNG W FLUOR
WITH SOLID REFECTORS
CHAIN.
DD
STOCKROOM
WILLIAMS
120
FLUOR
32
2
F32T8/TL830
CEILING
EB
AND EMERGENCY
WLM76-4-232-EB2-AD
HUNG
BATTERY BALLAST
BD-UNV-EM1400
--
RETAIL/3WAY
CALCULITE8242HU-
COMPACT
PLT42W/830/
E
RECESSED CAN LIGHT
LIGHTOLIER
120
CEILING
RECESSED
EB
MIRROR
ADV/8038 CLWCCLW
FLUOR
42
2
4P
--
GIMBAL RING TRACK
TRACK HUNG
F2
RETAIL
LIGHTOLIER
9022 BLACK
120
LED
19
1
PAR38
FROM,
TRACK
EB
HEAD
CEILING
--
G
RETAIL
PENDANT CYLI NDER
WILLIAMS
PVC90-142T-BLK-CS-
120
COMPACT
42
1
CEILING
STEM
EB
PM-EB9-UNV
FLUOR
--
TP-U-R-B-EM-EXIT,
X
THRU OUT
EXITSIGN
ASTRALITE
UNIVERSAL
120
LED WITH UNIT
SURFACE
EB
STORE
W/CANOPY, 2
CEILING/
DIFFUSERS
WALL
--
1
OFFICEAND
2X2 SURFACE MOUNTED
LIGHTOLIER
PNB2SRAVA3FT
120
--
40
3
PLL40W/30/R5
CEILING-
SURFACE
EB
TOILET
120X3CU L
--
EM
SALES
THERMOPLASTIC
LITHONIA
ELM2
120
INCAND;
5.4
2
WITH UNIT
CEILING
PENDANT'
EB;
EMERGENCY LIGHT
--
GENERAL NOTES
A. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT LIGHT FIXTURE
LOCATIONS AND HEIGHTS.
B. SEE SHEET E-1 FOR PANELBOARD LOCATIONS.
C. SEE SHEET E-3 FOR PANELBOARD SCHEDULES.
D. REFER TO CONTACTOR SCHEDULE FOR CIRCUITS BEING CONTROLLED.
E. EXPOSED FLUORESCENT LAMPS SHALL HAVE TUBE GUARDS TS81252 4' T8 TUBE
GUARD, FOIC.
F. ALL LINEAR FLUORESCENT LIGHT FIXTURES SHALL BE INSTALLED TO MEET THE
REQUIREMENTS OF NEC SECTION 410-13OG REGARDING LOCAL DISCONNECTING
MEANS.
G. ALL 120 VOLT BRANCH CIRCUITS IN EXCESS OF 75' SHALL HAVE CONDUCTOR
SIZE INCREASED A MINIMUM OF 1 CONDUCTOR SIZE. INSTALLING CONTRACTOR
SHALL DETERMINE ACTUAL CONDUCTOR SIZE TO BE INSTALLED TO ADHERE TO
VOLTAGE DROP REQUIREMENTS.
H. TO MAINTAIN POLARITY, STARTER TRACK IS TO BE DISASSEMBLED AND
COMPONENT END FEED AND/OR DEAD END COVERS ARE TO BE INSTALLED
ELSEWHERE ALONG RUN OF TRACK. UNUSED COMPONENTS ARE TO BE
DISCARDED.
MINIMUM EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A PERIOD OF 1.5
HOURS IN THE EVENT OF FAILURE OF NORMAL LIGHTING, WITHIN THE WORK
AREAS. EMERGENCY LIGHTING FACILITIES SHALL BE ARRANGED TO PROVIDE
INITIAL ILLUMINATION THAT IS AT LEAST AN AVERAGE OF 1 FOOTCANDLE
MEASURED ALONG THE PATH OF EGRESS AT FLOOR LEVEL. FBC2007 1006,
I. T1006 EXISTING FBC2007 705.7.1.
J. ELECTRICAL OUTLETS OR BOXES SHALL NOT REDUCE THE FIRE RESISTANCE
RATING OF FIRE RESISTANCE RATED WALL(S) AND SHALL COMPLY WITH FBC2007
712.3.2..
K. PLANS MUST BE DESIGNED IN ACCORDANCE WITH THE 2011 NATIONAL ELECTRIC
CODE.
L. PROVIDE SEISMIC BRACING AS REQUIRED FOR ALL SUSPENDED/LAY-IN LIGHT
FIXTURES.
M. PAINT ALL EXPOSED ELECTRICAL CONDUIT, JUNCTION BOXES, CONNECTORS, WIRE,
LIGHT FIXTURE SUPPORT RODS/CHAINS, EQUIPMENT SUPPORT ROD/CHAINS,
PLATFORMS, ETC. COLORS AS INDICATED ON ARCHITECTURAL REFLECTED CEILING
PLAN TO MATCH CEILING.
N. ADD A BLANK COVER PLATE TO ALL OPEN J-BOXES AFTER A/V AND
COMMUNICATION SYSTEMS INSTALLATION IS COMPLETE.
KEY NOTES THIS DRAWING
O1 ELECTRICAL EQUIPMENT LOCATION. REFER TO ELECTRICAL PANEL SCHEDULES
AND POWER RISER DIAGRAM ON SHEET E3 FOR FURTHER INFORMATION.
O2 PROVIDE J-BOX. AND DISCONNECTING MEANS FOR STOREFRONT SIGNAGE. ROUTE
SIGN CIRCUIT VIA THE TIME CLOCK. COORDINATE SCHEDULING WITH LANDLORD.
COORDINATE EXACT LOCATION AND REQUIREMENTS WITH ARCHITECTURAL SHEETS.
3O CIRCUIT SHOW WINDOW DOWNLIGHTS VIA TIME CLOCK LOCATED ADJACENT TO
PANELS IN STOCK ROOM. COORDINATE SCHEDULING WITH LANDLORD. REVIEWED FOR
OCURRENT LIMITING END FEED. NUMBER REPRESENTS AMP RATING OF DEVICE. COMPLIANCE WITH
REFER TO CURRENT LIMITING DEVICE SCHEDULE FOR MORE INFORMATION. N PA 70 ® NEC
O MOUNT THE BOTTOM OF THIS FIXTURE 4" ABOVE ADJACENT LIGHT FIXTURES.
JUN 24 2015
OPROVIDE MULTIPOLE LIGHTING CONTACTORS (C1, C2 AND C3) FOR SALES AREA
LIGHTING AND STOREFRONT LIGHTING AND RECEPTACLES. CONTACTORS C1 AND
C2 SHALL BE CONTROLLED BY WALL SWITCHES (a & b) LOCATED ADJACENT TO City ®f llukWfl�
SALES/STOCK DOOR. SWITCHES SHALL BE APPROPRIATELY LABELED "PERIMETER
TRACK" AND "SALES TRACK", AND BE GANGED UNDER ONE COVERPLATE. BUILDING DIVISION
CONTACTOR C3 SHALL BE CONTROLLED BY THE TIME CLOCK. REFER TO
CONTACTOR SCHEDULE THIS SHEET AND LIGHTING CONTROL DIAGRAM ON SHEET
E3 FOR FURTHER INFORMATION.
O7 PROVIDE TIMECLOCK FOR MASTER CONTROL OF CONTACTORS C1, C2 AND C3. RECEIVED
COORDINATE SETTINGS WITH STORE OPERATIONS. CITY OF TUKWILA
8O PROVIDE MANUAL OVERRIDE SWITCH (OR) FOR MASTER CONTROL OF TIME CLOCK SUN (g 2015
AND CONTACTORS. SWITCH SHALL BE A TIMED OVERRIDE TYPE. MAXIMUM TIME
SETTING OF FOUR (4) HOURS.
PERMIT CENTER
O9 PROVIDE CEILING MOUNTED OCCUPANCY SENSOR APPROPRIATE FOR CIRCUITING
AND SPACE USE. PROVIDE REQUIRED POWER SUPPLIES, RELAYS, ETC. FOR A
COMPLETE INSTALLATION. IN TOILET ROOMS, SENSOR SHALL CONTROL LIGHTING
AND EXHAUST FANS.
10 CONNECT EXIT ;AND EMERGENCY FIXTURES IN STOCK AREA TO SAME CIRCUIT AS
GENERAL LIGHTING AHEAD OF LOCAL SWITCHING.IN ACCORDANCE WITH $THE N.E.C.
11 MOUNT THE BOTTOM OF THIS FIXTURE 13'-0" ABO 917SHED OOR
Af
\Gw
77
HEI Project No:
R 1 5-2 1 24.01 3
(ARCHITECT'.................
f�
Z
N
L Q
m Y
M
�J Of
W O
m
p, dl n
0 0 t
0
n,,z-�L2
W ry
CO
6. coj
W
Z W O1
J
J �v E 00
C C.. U
LO
2W
FET T t,
0- NVAS�l�
a4Q50
f�'o�, �clsT>✓fi�� �w�
(0, A11,,
1
EXPIRES
LL Review Set Issued:
05/OG/201 5
Permit Set Issued:
05/2G/201 5
Bid Set Issued:
05/2G/201 5
Construction Set Issued:
Revisions
No.: Date:
A
0
drawn by: CTC
Sheet Title
LIGHTING
PLAN
Sheet No.
ELECTRICAL SPECIFICATIONS
NOTE:
MANUFACTURER'S NAMES ON WHICH THIS SPECIFICATION IS BASED
INDICATE THE MINIMUM QUALITY OF PRODUCT REQUIRED.
SUBSTITUTION MAY BE MADE TO THOSE SPECIFIED IF DEEMED
EQUIVALENT BY THE OWNER'S REPRESENTATIVE. ALL WORK AND
PRODUCTS SHALL MEET THE REQUIREMENTS OF THE LANDLORD.
1. THE GENERAL CONDITIONS AND SUPPLEMENTARY GENERAL
CONDITIONS SHALL BE CONSIDERED AS PART OF THIS
SPECIFICATION.
2. ALL WORK TO BE IN ACCORDANCE WITH THE RULES AND
REGULATION OF THE LOCAL AUTHORITIES HAVING JURISDICTION
AND THE MOST RECENT EDITION OF NATIONAL ELECTRIC CODE.
3. CONTRACTOR SHALL FILE PLANS WITH AND OBTAIN APPROVALS
FROM MUNICIPAL AGENCIES. ALL PERMITS AND CERTIFICATES OF
INSPECTION SHALL BE OBTAINED AND PAID FOR BY THE
CONTRACTOR. PERTINENT CERTIFICATES. SHALL BE DELIVERED TO
THE OWNER'S REPRESENTATIVE, PRIOR TO FINAL BILLING.
4. CONTRACTOR SHALL VISIT SITE PRIOR TO BIDDING. BIDS SHALL
SERVE AS EVIDENCE OF KNOWLEDGE OF EXISTING CONDITIONS.
HE SHALL CAREFULLY EXAMINE THE EXISTING CONDITIONS AND
LIMITATIONS THEREOF. HE SHALL ASCERTAIN CONDITIONS UNDER
WHICH THE WORK `, MUST BE PERFORMED, INCLUDING THE HANDLING
OF MATERIALS, SECURITY AND LIMITING FIELD DIMENSIONS.
FURTHER, THIS CONTRACTOR SHALL PROVIDE FIELD VERIFICATION
OF LOCATION OF THE POINTS OF CONNECTION TO LANDLORD'S
ELECTRICAL AND TELEPHONE EQUIPMENT AND DISTANCE FROM
LEASED SPACE.
ANY DISCREPANCIES WITH THE CONSTRUCTION DOCUMENTS
DISCOVERED AS A RESULT OF THE AFOREMENTIONED FIELD
SURVEY, SHALL BE BROUGHT TO THE ATTENTION OF THE OWNER'S
REPRESENTATIVE, PRIOR TO COMMENCING ANY WORK. ANY
ADDITIONAL COSTS RESULTING FROM CONTRACTOR'S FAILURE TO
DO SO SHALL BE THIS RESPONSIBILITY AND SHALL BE BORNE BY
HIM.
5. ELECTRICAL CONTRACTOR SHALL RECORD ALL FIELD CHANGES IN
HIS WORK AS THE JOB PROGRESSES; AN ACCURATE RECORD OF
ALL WORK AS ACTUALLY INSTALLED.
UPON COMPLETION OF THE WORK AND BEFORE FINAL PAYMENT IS
AUTHORIZED, SHALL TURN OVER TO THE OWNER'S
REPRESENTATIVE A RECORD SET OF PRINTS SHOWING THESE
CHANGES.
6. SUBMIT MATERIAL LISTS AND SHOP DRAWINGS FOR MAJOR
EQUIPMENT TO THE OWNER'S REPRESENTATIVE FOR REVIEW.
SUBMITTALS SHALL BE IN ACCORDANCE WITH GENERAL
CONDITIONS AND SHALL BEAR THE STAMP OF THE ELECTRICAL
CONTRACTOR SHOWING THAT HE HAS REVIEWED AND APPROVED
THEM. LACK OF SUCH CONTRACTOR'S APPROVAL WILL BE CAUSE
FOR REJECTION WITHOUT REVIEW BY THE OWNER.
7. THIS CONTRACTOR SHALL DO ALL CUTTING, CHASING, OR
CHANNELING PATCHING REQUIRED FOR ANY WORK HEREIN
SPECIFIED. ANY CUTTING SHALL HAVE PRIOR APPROVAL BY THE
LANDLORD.
ALL OPENINGS THROUGH STRUCTURALLY SUPPORTED SLABS MUST
BE CORE BORED, SLEEVED, GROUTED, SEALED AND MADE
WATERPROOF. SLEEVES MUST EXTEND AT LEAST 2" AFF. WATER
PROOFING MUST BE INSPECTED AND APPROVED BY THE LANDLORD
BEFORE ANY FLOORING MATERIAL IS INSTALLED.
CONTRACTOR IS RESPONSIBLE TO TAKE WHATEVER MEASURES ARE
NECESSARY, INCLUDING BUT NOT LIMITED TO THOSE MEASURES
PRESCRIBED BY THE LANDLORD IN THE EXERCISE OF ITS
REASONABLE JUDGMENT TO ASSURE THAT CORE BORING WILL NOT
DAMAGE LANDLORD'S STRUCTURE, CONDUITS, ETC. OR THE WORK
OF OTHER TENANTS BELOW. THE COST OF SUCH TESTS OR
REPAIR OF ANY DAMAGE WILL BE BORNE BY THIS CONTRACTOR.
ALL SLEEVES, OPENINGS, ETC, THROUGH FIRE RATED WALLS AND
FLOORS SHALL BE. SEALED AFTER CONDUIT INSTALLATION TO
RETAIN FIRE RATING.
8. ALL ELECTRICAL WORK SHALL BE INSTALLED SO AS TO BE
READILY ACCESSIBLE FOR OPERATING, SERVICING, MAINTAINING
AND REPAIR.
HANGERS SHALL INCLUDE ALL MISCELLANEOUS STEEL, SUCH AS
CHANNEL, RODS, ETC., NECESSARY FOR THE INSTALLATION OF
WORK AND SHALL BE SECURED TO THE BUILDING STRUCTURE,
NOT TO PIPING OR DUCTWORK.
ALL CONDUIT SHALL BE CONCEALED WHERE POSSIBLE. EXPOSED
CONDUIT SHALL BE RUN IN STRAIGHT LINES PARALLEL WITH OR
AT RIGHT ANGLES TO COLUMN LINES AND SEPARATED AT LEAST
3" FROM WATER LINES WHEREVER THEY RUN ALONG SIDE OR
ACROSS SUCH LINES.
9. EVERY PART OF THE INSTALLATION SHALL BE TESTED, OPERATED
AND LEFT IN PERFECT WORKING ORDER.
TEST ALL WIRES AND CABLES INSTALLED UNDER THIS CONTRACT
WITH A 1,000 VOLT MEGOHM METER. IF ANY READINGS ARE
FOUND LOWER THAN REQUIRED BY GOOD PRACTICE OR
APPLICABLE CODES, THE EQUIPMENT OR MATERIALS INVOLVED
SHALL BE PROMPTLY REPLACED.
SHOULD TESTING REVEAL ANY OTHER DEFECTS, PROMPTLY
CORRECT ANY SUCH DEFECTS AND RERUN TESTS UN11L THE
ENTIRE INSTALLATION IS SATISFACTORY IN ALL RESPECTS.
10. GUARANTEE:
CONTRACTOR IS TO GUARANTEE ALL WORK FOR A PERIOD OF ONE
YEAR AFTER THE DATE OF ACCEPTANCE OF THE PROJECT BY THE
OWNER. IT IS UNDERSTOOD BY HIS ACCEPTANCE OF THE
CONTRACT THAT THIS CONTRACTOR WILL MAKE GOOD ANY AND
ALL WORK WHICH IN ANY WAY HAS BECOME DEFECTIVE AS TO
THE QUALITY OF MATERIALS AND WORKMANSHIP FOR ANY CAUSE
OTHER THAN ORDINARY WEAR AND TEAR.
FOR THE SAME PERIOD, ELECTRICAL CONTRACTOR SHALL BE
RESPONSIBLE FOR ANY DAMAGE TO THE PREMISES CAUSED BY
DEFECTS IN WORKMANSHIP OR IN THE WORK OR EQUIPMENT
FURNISHED AND/OR INSTALLED BY HIM.
i
11. THE CONTRACTOR, BEFORE FINAL ACCEPTANCE BY THE OWNER
WILL BE GRANTED, SHALL CLEAN ALL LIGHTING FIXTURES, DEVICE
PLATES, SERVICE FITTINGS AND OTHER ITEMS FURNISHED UNDER
THIS CONTRACT. HE SHALL INSURE THAT ALL DIRECTORIES ARE
IN PLACE WITH COMPLETED OR REVISED SCHEDULES AND ALL
IDENTIFICATIONS AND MARKINGS OF EQUIPMENT, CABLES AND
OTHER ITEMS ARE COMPLETED.
12. THIS CONTRACTOR SHALL COORDINATE SEQUENCE OF WORK WITH
ALL OTHER TRADES. CONTRACTOR SHALL VERIFY VOLTAGE OF
MECHANICAL EQUIPMENT AND FLUORESCENT FIXTURE BALLASTS,
PRIOR TO COMMENCING ANY WORK. NO REMOVALS SHALL BE
MADE WITHOUT OWNER'S APPROVAL. ALL EXISTING EQUIPMENT,
MATERIALS, ETC.. THAT ARE NOT TO BE REUSED SHALL BE
REMOVED COMPLETELY AND DISPOSED OF BY THIS CONTRACTOR.
13. THIS CONTRACTOR SHALL MAKE ARRANGEMENTS FOR TEMPORARY
POWER AND SHALL PAY THE COST FOR THE UTILITY CONNECTION
AND SHALL BE RESPONSIBLE FOR THE PROPER MAINTENANCE OF
THE TEMPORARY WORK AND FOR THE REMOVAL OF SAME.
CONTRACTOR SHALL PAY ALL UTILITY CHARGES IN CONNECTION
WITH THE TEMPORARY POWER.
CONTRACTOR SHALL PROVIDE GROUND FAULT PROTECTION FOR
ALL POWER EQUIPMENT USED ON THE PREMISES DURING
CONSTRUCTION.
14. CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, SUPPLIES,
EQUIPMENT AND FEES REQUIRED TO COMPLETELY INSTALL, TEST
AND PLACE THE HEREIN SPECIFIED EQUIPMENT, COMPONENTS,
CONTROLS, AND SYSTEMS IN SERVICE.
SCOPE OF WORK:
INSTALLATION OF ELECTRICAL SERVICE INCLUDING:
WORK IN THE LANDLORD'S MAIN DISTRIBUTION EQUIPMENT SHALL
BE AS INDICATED AND/OR REQUIRED.
COMPLETE POWER AND LIGHTING DISTRIBUTION SYSTEMS INCLUDING
ALL PANELS AND STEP DOWN TRANSFORMER.
COMPLETE BRANCH CIRCUIT WIRING SYSTEM.
PROVISIONS FOR OWNER SUPPLIED SECURITY SYSTEM.
PROVISIONS FOR OWNER SUPPLIED DATA COMMUNICATIONS
SYSTEM.
PROVISIONS FOR OWNER SUPPLIED SOUND SYSTEM.
PROVISIONS FOR OWNER SUPPLIED CLOSED CIRCUIT SURVEILLANCE
SYSTEM.
PROVISIONS FOR COMPLETE TELEPHONE SYSTEM.
COMPLETE UTILITY MOTOR WIRING SYSTEMS, (EXCEPT AS NOTED)
FOR ALL AIR CONDITIONING AND/OR HEATING EQUIPMENT,
EXHAUST EQUIPMENT AND CONTROLS.
ELECTRIC HEATING EQUIPMENT, CONTROLS AND INSTALLATION OF
SAME.
COMPLETE LIGHTING FIXTURE INSTALLATION FIXTURES ARE
FURNISHED BY THE OWNER.
COMPLETE TELEPHONE CONDUIT SYSTEM, INCLUDING SERVICE
CONDUIT FROM POINT OF CONNECTION TO LANDLORD'S SYSTEM
AND ALL TERMINAL DEVICES, BOXES, CONDUIT, PLATES, ETC.
COMPLETE FIRE ALARM SYSTEM, INCLUDING INTERFACE WITH
LANDLORD'S SYSTEM.
TEMPORARY ELECTRICAL SERVICE AS REQUIRED FOR
CONSTRUCTION.
TESTING OF ALL CABLES AND CIRCUIT WIRING AFTER
INSTALLATION.
TESTING OF ALL ELECTRICAL EQUIPMENT WARRANTY OF ALL WORK
FOR A PERIOD OF ONE YEAR FROM DATE OF PROJECT
CLOSE-OUT.
15. ELECTRICAL SERVICE:
LANDLORD PROVIDES 208/120V, 3-PHASE, 4 WIRE SERVICE FOR
THE LEASED SPACE.
PROVIDE ELECTRICAL AS INDICATED ON THE DRAWING.
ALL WORK NOT SPECIFICALLY NOTED AS BEING BY THE LANDLORD
SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR.
CLOSELY COORDINATE ENTIRE INSTALLATION WITH THE LANDLORD.
CONTRACTOR SHALL MAKE ARRANGEMENTS. WITH THE LANDLORD
FOR INSTALLATION OF CHECK METER AT TENANT'S EXPENSE.
16. CONTRACTOR SHALL MAKE ARRANGEMENTS WITH THE LOCAL
TELEPHONE UTILITY FOR INSTALLATION OF SERVICE TO THE SPACE.
LANDLORD HAS PROVIDED CONDUIT FROM LANDLORD'S TELEPHONE
EQUIPMENT ROOM TO THE LEASED SPACE, FOR USE BY THIS
CONTRACTOR.
COORDINATE INSTALLATION OF TELEPHONE WORK AND INSTALL
ALL CONDUIT FOR TELEPHONE SYSTEM WITHIN LEASED SPACE WITH
OWNER'S TELEPHONE EQUIPMENT SUPPLIER.
OUTLET BOXES SHALL BE 4" SQUARE MINIMUM (UNLESS
OTHERWISE NOTED) WITH SINGLE DEVICE AND COVER AND
TELEPHONE PLATE.
THIS CONTRACTOR PROVIDES ROUGH-IN'S ONLY. TELEPHONE
EQUIPMENT, DEVICES AND ALL CABLING ARE PROVIDED BY
OTHERS:
CONTACT: MICHELLE BRODERICK
PHONE: (206)882-6214
ELECTRICAL CONTRACTOR SHALL VERIFY ALL ROUGH -IN
REQUIREMENTS PRIOR TO COMMENCING ANY WORK.
ALL TELEPHONE ROUGH -INS SHALL BE INSPECTED BY
TELECOMMUNICATIONS SUBCONTRACTOR PRIOR TO CLOSING OF
WALLS AND CEILINGS. IT IS THE RESPONSIBILITY OF THE
ELECTRICAL CONTRACTOR TO MAKE ARRANGEMENTS WITH THIS
SUBCONTRACTOR FOR SUCH AN INSPECTION.
17. SOUND SYSTEM THIS CONTRACTOR SHALL PROVIDE ROUGH-IN'S ONLY
(INCLUDING CONDUIT FOR WIRING AS INDICATED ON THE PLANS) FOR ALL
SOUND SYSTEM COMPONENTS. ALL EQUIPMENT, DEVICES, ACCESSORIES,
AND WIRING SHALL BE PROVIDED BY: PLAY NETWORK, INC.
CONTACT: CORY NAHOOPII
PH:(425) 629-1835
ELECTRICAL CONTRACTOR SHALL VERIFY ALL ROUGH -IN REQUIREMENTS
PRIOR TO COMMENCING ANY WORK. ALL SOUND SYSTEM ROUGH -INS
SHALL BE INSPECTED BY AUDIO SYSTEM SUBCONTRACTOR PRIOR TO
CLOSING OF WALLS AND CEILINGS. IT IS THE RESPONSIBILITY OF THE
ELECTRICAL CONTRACTOR TO MAKE ARRANGEMENTS WITH THIS
SUBCONTRACTOR FOR SUCH AN INSPECTION.
18. DATA COMMUNICATION SYSTEM THIS CONTRACTOR SHALL PROVIDE
ROUGH-IN'S ONLY (INCLUDING CONDUIT FOR CABLE AS INDICATED
ON THE PLANS) FOR ALL DATA COMMUNICATIONS SYSTEM
COMPONENTS. ALL EQUIPMENT, DEVICES, ACCESSORIES, AND
CABLE SHALL BE PROVIDED BY:
CONTACT: CELESTE BUSCONI
PH: (508) 635-2006
ELECTRICAL CONTRACTOR SHALL VERIFY ALL ROUGH -IN
REQUIREMENTS PRIOR TO COMMENCING ANY WORK.
ALL DATA COMMUNICATIONS SYSTEM ROUGH-IN'S SHALL BE
INSPECTED BY BY DATA COMMUNICATIONS SYSTEM
SUBCONTRACTOR PRIOR TO CLOSING OF WALLS AND CEILINGS. IT
IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO
MAKE ARRANGEMENTS WITH THIS SUBCONTRACTOR FOR SUCH AN
INSPECTION.
19. SECURITY SYSTEM AND CLOSED CIRCUIT TELEVISION SYSTEM
THIS CONTRACTOR SHALL PROVIDE ROUGH-IN'S ONLY (INCLUDING
CONDUIT FOR CABLE AS INDICATED ON THE PLANS) FOR ALL
SECURITY COMPONENTS. ALL EQUIPMENT, DEVICES, ACCESSORIES,
CABLE SHALL BE PROVIDED BY:
ADT CONTACT - MIKE LOTTES PH: (206) 391-5428
ELECTRICAL CONTRACTOR SHALL VERIFY ALL ROUGH -IN
REQUIREMENTS PRIOR TO COMMENCING ANY WORK. ALL SECURITY
SYSTEM ROUGH-IN'S SHALL BE INSPECTED BY SECURITY SYSTEM
SUBCONTRACTOR PRIOR TO CLOSING OF WALLS AND CEILINGS. IT
IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO
MAKE ARRANGEMENTS WITH THIS SUBCONTRACTOR FOR SUCH AN
INSPECTION.
20. FURNISH ALL LABOR, MATERIALS, EQUIPMENT AND TOOLS TO
PERFORM ELECTRICAL WORK SHOWN, NOTED OR SCHEDULED FOR
A COMPLETE AND FINISHED INSTALLATION.
20.1. THE WORD "PROVIDE" AS USED HEREIN MEANS TO FURNISH AND
INSTALL COMPLETE.
20.2. MATERIALS, PRODUCTS AND EQUIPMENT, INCLUDING COMPONENTS
THEREOF, SHALL BE NEW AND SUCH AS APPEARS ON THE
UNDERWRITER'S LABORATORY LIST OF APPROVED ITEMS AND
SHALL MEET THE REQUIREMENTS OF RECOGNIZED STANDARDS.
20.3. EQUIPMENT SHALL BE SIZED IN CONFORMITY WITH REQUIREMENTS
OF THE NATIONAL ELECTRICAL CODE AND OTHER APPLICABLE
CODES.
21. CONDUIT SHALL BE STANDARD STEEL, RIGID, IMC OR EMT (THIN
WALL) ACCORDING TO CODE REQUIREMENTS. CONDUIT SHALL BE
CONCEALED IN FINISHED AREAS, EXCEPT AS OTHERWISE
APPROVED BY OWNER'S REPRESENTATIVE. EMT CONNECTIONS
SHALL BE COMPRESSION TYPE.
21.1. MINIMUM SIZES OF CONDUIT SHALL BE 3/4", EXCEPT 1 /2" FOR
SWITCH LEGS. EMT SHALL BE GALVANIZED OR
ELECTRO-GALVANIZED. EMT SHALL BE USED FOR FEEDERS AND
BRANCH CIRCUITS RUN ABOVE SUSPENDED CEILINGS OR
CONCEALED IN INTERIOR PARTITIONS. EMT SHALL NOT BE
CONCEALED IN POURED CONCRETE FLOOR OR WALLS.
21.2. USE HEAVY WALL CONDUIT OR IMC FOR UNDER SLAB
INSTALLATIONS. IMC IS PERMITTED WITH SCREW CONNECTIONS.
21.3. FLEXIBLE METALLIC TUBING MAY BE USED IN LIEU OF EMT FOR
CONCEALED BRANCH CIRCUIT WIRING ONLY, WHERE PERMITTED BY
LOCAL AUTHORITIES.
22. ALL CONDUCTORS SHALL BE SOFT DRAWN, ANNEALED COPPER,
WITH 600V INSULATION:
22.1. #10 AND SMALLER - SOLID WITH SINGLE BRAID. #8 AND LARGER
- STRANDED WITH AT LEAST DOUBLE BRAID. MINIMUM WIRE SIZE
SHALL BE #12, EXCEPT #14 MAY BE USED FOR CONTROL
APPLICATIONS.
22.2. ALL WIRE AND CABLE SHALL BE NEW AND SHALL BE BROUGHT TO
THE SITE IN UNBROKEN PACKAGES.
22.3. GENERAL WIRING SHALL HAVE THW, THHN OR THWN INSULATION.
22.4. ALUMINUM CONDUCTORS ARE NOT PERMITTED.
22.5. WIRE CONNECTORS SHALL BE EQUAL TO SCOTCHLOCK FOR #8
AND SMALLER, AND T & B "LOCK-TITE" FOR #6 AND LARGER.
22.6. WIRES SHALL BE COLOR CODED IN KEEPING WITH LANDLORD'S
CONVENTION.
23. OUTLET BOXES AND COVERS SHALL BE ONE PIECE, GALVANIZED
OR SHERARDIZED STEEL; 4" X 4-11 /16", KNOCKOUT TYPE WITH
FIXTURE STUDS AS REQUIRED. JUNCTION BOXES, PULL BOXES AND
COVERS SHALL BE GALVANIZED STEEL, CODE GAUGE AND SIZE.
24. WIRING DEVICES:
WALL SWITCHES, SINGLE POLE, DOUBLE POLE, AND THREE WAY
SHALL BE GENERAL DUTY, FLUSH, TOGGLE SWITCHES;
SPECIFICATION GRADE, 20A 120/277V, WITH SCREW TERMINALS,
MANUFACTURERS SHALL BE HUBBELL, BRYANT, PASS AND
SEYMOUR, OR LEVITON. SEE DEVICES COLOR BELOW FOR
MORE INFORMATION.
GENERAL DUTY DUPLEX RECEPTACLES SHALL BE 2-POLE, 3-WIRE
GROUNDING TYPE, SPECIFICATION GRADE, 20A, 125V, NEMA 5-20R
UNLESS OTHERWISE INDICATED. MANUFACTURERS SHALL BE
HUBBELL, BRYANT, PASS AND SEYMOUR, OR LEVITON. SEE
DEVICES COLOR BELOW FOR MORE INFORMATION.
GROUND FAULT INTERRUPTER RECEPTACLE SHALL BE GENERAL
DUTY, DUPLEX RECEPTACLES, GROUND FAULT CIRCUIT
INTERRUPTER, FEED -THROUGH TYPE, CAPABLE OF PROTECTING
CONNECTED DOWNSTREAM RECEPTACLES ON A SINGLE CIRCUIT,
GROUNDING TYPE UL-RATED CLASS A, GROUP 1, 20A 120V,
60HZ; WITH SOLID-STATE GROUND -FAULT SENSING AND
SIGNALING; WITH 5 MILLIAMPERES GROUND -FAULT TRIP LEVEL; IN
NEMA 5-15R CONFIGURATION. MANUFACTURERS SHALL BE
HUBBELL, BRYANT, PASS AND SEYMOUR, OR LEVITON.
DUPLEX ISOLATED GROUND TYPE RECEPTACLE SHALL BE 2-POLE,
4-WIRE, 15A STRAIGHT BLADE DEVICE WITH SEPARATE ISOLATED
GROUND AND BUILDING GROUND CONNECTIONS, IN NEMA 5-20R
CONFIGURATION, AS MANUFACTURED BY HUBBELL IG-5362.
DEVICES COLOR: DEVICES INSTALLED ON GREY WALLS SHALL BE
GREY. DEVICES INSTALLED ON BLACK WALLS SHALL BE BLACK.
DEVICES INSTALLED ON KHAKI WALLS SHALL BE WHITE. ALL
DEVICES INSTALLED AT THE BACK OF THE HOUSE SHALL BE
WHITE.
WIRING DEVICE ACCESSORIES INCLUDING ALL WALL PLATES SHALL
BE PROVIDED AT EACH DEVICE. WALL PLATES SHALL BE SAME
COLOR AS DEVICE AND MANUFACTURED AS A COMPANION TO
THE DEVICE, EXCEPT IN COVER PLATES FOR DEVICES INSTALLED
IN THE SALES AREA SHALL HAVE WHITE FINISH. MOUNTING
HEIGHTS OF DEVICES SHALL BE TO THE FOLLOWING CENTERLINES
(UNLESS NOTED OTHERWISE):
TOGGLE SWITCHES 48"
RECEPTACLES 15"
WALL TELEPHONE OUTLETS 48"
DISCONNECT SWITCHES 66"
PANELBOARDS 60"
25. THIS CONTRACTOR SHALL PROVIDE, INSTALL AND CONNECT A
COMPLETE SYSTEM OF GROUNDING FOR ALL EQUIPMENT AND
STRUCTURES. A GOOD MECHANICAL AND ELECTRICAL CONNECTION
SHALL BE MADE WITH APPROVED GROUNDING CONNECTORS.
ELECTRICAL SYSTEM AND EQUIPMENT GROUNDS SHALL COMPLY
WITH ALL LOCAL, STATE AND NEC CODES AND REGULATIONS.
PANELS, CONDUIT SYSTEMS, MOTOR FRAMES, LIGHTING FIXTURES
AND OTHER EQUIPMENT THAT ARE A PART OF THIS INSTALLATION
SHALL BE SECURELY GROUNDED BOTH MECHANICALLY AND
ELECTRICALLY IN ACCORDANCE WITH ALL CODES.
MAIN GROUNDING SYSTEM SHALL BE SIZED TO CONFORM WITH
SECTION 250, TABLE 250-94 OF THE NATIONAL ELECTRICAL CODE,
PROVIDE CONDUIT TO PROTECT GROUND WIRE FROM DAMAGE TO
AN AREA 6' ABOVE FLOOR.
MAKE ALL JOINTS AND CONNECTIONS OF THE CONDUIT SYSTEM
TIGHT TO CONTINUITY OF MECHANICAL AND ELECTRICAL GROUND
THROUGHOUT SYSTEM.
GROUND ALL 3 WIRE RECEPTACLES TO THE OUTLET BOXES.
GROUND NEUTRAL FROM THE TRANSFORMER CONNECTED TO WATER
LINE. PROVIDE NEUTRAL TO GROUND BOND AT TRANSFORMER
SECONDARY.
GROUND CONDUCTOR SHALL BE SUPPLIED IN ALL NONMETALLIC
CONDUIT.
A DEDICATED INSULATED GROUND CONDUCTOR SHALL BE
INSTALLED FOR ELECTRONIC CASH REGISTERS, AND OTHER DEVICES
INDICATED ON THE PLANS.
26. EXISTING TO BE RE -USED. REPLACE AS REQUIRED WITH THE
FOLLOWING. LIGHTING PANEL BOARD SHALL BE 3-PHASE, 4-WIRE
DISTRIBUTED PHASE TYPE WITH SOLID NEUTRAL, GROUND LUG,
GROUND BUS AND NUMBER OF CIRCUIT BREAKERS AS SHOWN ON
THE PANEL SCHEDULE. BUSBARS SHALL BE HARD DRAWN
COPPER OR AL. CABINET SHALL BE CONSTRUCTED OF CODE.
GAUGE STEEL WITH HINGED DOOR HAVING DIRECTORY CARD,
NEATLY AND PROPERLY INSCRIBED AND SET IN FRAME WITH
TRANSPARENT COVER.
ELECTRICAL CONTRACTOR SHALL PERMANENTLY LABEL
PANELBOARD BY MEANS OF LAMINATED BLOCK AND WHITE
PHENONIC LABEL.
ALL BREAKERS SHALL BE BOLTED TYPE, THERMAL MAGNETIC WITH
ALL TWO OR THREE POLE BREAKERS HAVING COMMON TRIP.
CIRCUIT BREAKERS SHALL DERATED FOR MINIMUM 10,000 AMP
SYMMETRICAL SHORT CIRCUIT CURRENT AT 120/208V.
CIRCUIT BREAKERS SERVING LIGHTING CIRCUITS SHALL BE RATED
FOR SWITCH SERVICE.
PANELBOARDS AND BREAKERS SHALL BE AS MANUFACTURED BY
SQUARE-D EQUAL. PROVIDE "LOCK -ON" DEVICE AT BREAKERS
SERVING NIGHT -LIGHT / EMERGENCY CIRCUIT, CASH REGISTER,
AND TIME SWITCH CIRCUIT. PANEL SHALL BE CIRCUITED SO THAT
THE LOAD IS DISTRIBUTED EVENLY ACROSS ALL THREE PHASES.;
27. PROVIDE SAFETY AND DISCONNECT SWITCHES, FUSED OR
NON -FUSED, AS CALLED FOR ON DRAWING AND AS REQUIRED BY
CODE. SWITCHES SHALL BE HEAVY DUTY, LOAD AND
HORSEPOWER RATED AS MANUFACTURED BY SQUARE-D, GENERAL
ELECTRIC, OR EQUAL. SWITCH ENCLOSURE TO BE SUITABLE FOR
APPLICATION.
FURNISH AND INSTALL DUAL ELEMENT CURRENT LIMITING FUSES,
OF TYPE AND AMPACITY DESIGNED TO PROTECT SYSTEM AGAINST
AVAILABLE SHORT CIRCUIT FAULT CURRENT.
28. PROVIDE DRY -TYPE TRANSFORMER WHICH SHALL BE ENCLOSED,
VENTILATED TYPE WITH KVA AND VOLTAGE RATINGS AS CALLED,
FOR ON THE DRAWING AS MANUFACTURED BY SQUARE-D.
TRANSFORMER SHALL HAVE A MINIMUM OF 150 DEGREE, CLASS H
INSULATION AND A MINIMUM OF (4) 2-1 /2% TAPS BELOW ANAD
(2)2-1/2% TAPS ABOVE RATED PRIMARY VOLTAGE.
SOUND LEVEL SHALL BE LOW AND INSTALLATION SHALL INCLUDE
VIBRATION DAMPENING MOUNTS AND FLEXIBLE STEEL CONDUIT FOR
PRIMARY AND SECONDARY CONNECTIONS TO MINIMIZE SOUND
TRANSMISSION. MOUNT TRANSFORMER ON VIBRATION ISOLATORS.
29. HEATING AND COOLING MOTORS AND CONTROLS
ALL LINE AND LOW VOLTAGE POWER AND CONTROL WIRING
INCLUDING TEMPERATURE CONTROL WIRING, CONNECTION TO
DAMPERS, INSTALLATION OF THERMOSTATS, INTERLOCKING, ETC.
EXCEPT AS SPECIFICALLY NOTED AS BEING BY MECHANICAL
CONTRACTOR, SHALL BE PROVIDED BY THE ELECTRICAL
CONTRACTOR.
CONTROLS, EXCEPT AS NOTED, WILL BE SUPPLIED BY THE
MECHANICAL CONTRACTOR TO THIS CONTRACTOR WHO SHALL DO
ALL INSTALLATION AND AND WIRING. ELECTRICAL CONTRACTOR
SHALL CONNECT ALL MOTORS, SUPPLIED BY THE MECHANICAL
CONTRACTOR, WHICH DO NOT COME FACTORY WIRED IN THE
EQUIPMENT.
ELECTRICAL CONTRACTOR SHALL PERMANENTLY LABEL ALL
DISCONNECT SWITCHES, CONTACTORS, CONTROLS AND BOXES IN
THE SYSTEMS. IDENTIFY EACH AS TO USE, ON THE FACE OF
CABINETS OR COVERS BY MEANS OF A LAMINATED BLACK AND
WHITE PHENOLIC LABEL.
30. LIGHTING FIXTURES:
THE CONTRACTOR SHALL PROVIDE A NEW LIGHTING FIXTURE OF
THE TYPE SPECIFIED FOR EACH LIGHTING OUTLET SHOWN WITH
COMPLETE LAMPS OR TUBES. ALL FIXTURES SHALL BE HUNG
AND MOUNTED IN PLACE, PROPERLY WIRED, TESTED AND LEFT
READY FOR OPERATION.
THE OWNER SELECTS AND PROVIDES THE LIGHTING FIXTURES,
COMPLETE WITH ACCESSORIES AND LAMPS. SEE LIGHTING
FIXTURE SCHEDULE ON PLANS.
THIS CONTRACTOR PROVIDES INSTALLATION ONLY. FIXTURES,
LAMPS AND ACCESSORIES ARE PROVIDED BY:
WESTERN EXTRALITE
CONTACT. KATHY HENRY
PH: (888) 939-4399
FIXTURES PROVIDED BY THE OWNER SHALL BE SHIPPED TO THE
SITE FOR INSTALLATION BY THE CONTRACTOR. THE CONTRACTOR
SHALL SURVEY THE SHIPMENT TO VERIFY FIXTURE QUANTITIES
AND DAMAGES. IN THE EVENT THAT SHIPMENT IS INCOMPLETE OR
DAMAGED, CONTRACTOR SHALL INFORM THE OWNER.
AFTER THE SHIPMENT IS VERIFIED AND ACCEPTED, CONTRACTOR
SHALL MOVE FIXTURE TO AN AREA OF SAFETY FOR STORAGE
UNTIL THEY MAY BE INSTALLED. HE ASSUMES RESPONSIBILITY
FOR THE FIXTURES UNTIL THE PROJECT IS TURNED OVER TO THE
OWNER.
31. LIGHTING CONTROLS (EXISTING TO BE REUSED, MODIFY IN FIELD AS
REQUIRED).
CIRCUITS FOR STORE FRONT LIGHTING SHALL BE CONTROLLED BY A
PROGRAMMABLE TIME SWITCH. SWITCH SHALL BE EQUAL TO TORK
SERIES 1100, SYNCHRONOUS MOTOR -DRIVEN 40-AMPERE, 24 HOUR,
7 DAYS -A HOUR, 7-DAYS-A-WEEK, WITH SKIP -A -DAY FEATURE.
UNIT SHALL BE FURNISHED WITH NEMA 1 ENCLOSURE.
ALL OTHER CIRCUITS OF SALES AREA LIGHTING SHALL BE
CONTROLLED BY MUL11POLE MECHANICALLY HELD LIGHTING
CONTACTORS. PROVIDE SEPARATE CONTACTORS FOR
FLUORESCENT LIGHTING CIRCUITS AND TRACK LIGHTING CIRCUITS.
CONTACTORS ARE, IN TURN, CONTROLLED BY MOMENTARY
CONTACT SWITCHES.
MULTIPOLE LIGHTING CONTACTORS SHALL BE MAGNETIC LIGHTING
CONTACTOR, MECHANICALLY HELD AND ELECTRICALLY OPERATED
WITH ENCAPSULATED COILS. STANDARD COIL CLEARING CONTACTS
ARE TO BE PROVIDED SO THAT THE CONTACTOR COILS SHALL BE
ENERGIZED ONLY DURING THE INSTANCE OF OPERATION. COIL
VOLTAGE: 120V AC NUMBER OF POLES SHALL BE AS SCHEDULED.
CONTACT RATING: 20 AMPERES FOR ALL TYPES OF BALLAST AND
TUNGSTEN LIGHTING, RESISTIVE HEATING, AND MOTOR LOADS.
CONTACT: TOTALLY ENCLOSED, DOUBLE -BREAK
SILVER -CADMIUM -OXIDE POWER CONTACTS. CONTACT INSPECTION
AND REPLACEMENT SHALL BE POSSIBLE WITHOUT DISTURBING LINE
OR LOAD WIRING. ALL CONTACTS SHALL HAVE CLEARLY VISIBLE
N.O. AND N.C. CONTACT STATUS INDICATORS. LIGHTING
CONTACTORS SHALL BE EQUAL TO SQUARE D SERIES 8903 MODEL
LGX 1200-V02-Y1002.
CONTACTOR SHALL BE CONTROLLED BY PASS AND SEYMORE #1251
MOMENTARY CONTACT SWITCH.
32. PAINTING OF ELECTRICAL CONDUITS, ETC.. IF REQUIRED, WILL BE
BY GENERAL CONTRACTOR.
33. DOORBUZZER SYSTEM (EXISTING TO BE REUSED, MODIFY IN FIELD
AS REQUIRED).
THE PUSHBUTTON SHALL BE MOUNTED IN THE WALL NEXT TO THE
DOOR AT 4' -6" A.F.F. THE BUZZER SHALL BE MOUNTED IN THE
STOCK ROOM AT 10'-0" (OR JUST BELOW ANY STOCK ROOM
CEILING) IN A POSITION LOCATED CLOSE TO THE ENTRY TO THE
SALES AREA.
BUZZER: EDWARDS - 725 OR EQUAL
CHIME: EDWARDS - 55 - 6G5 - OR EQUAL
PUSHBUTTON: EDWARDS - 632 - OR EQUAL
TRANSFORMER: 1OV, 5VA SECONDARY EDWARDS - 590 OR
EQUAL WIRE: #20 AWG STRANDED BELL WIRE
34. FINALLY. IT IS THE INTENT THAT THE FOREGOING WORK SHALL
BE COMPLETE IN EVERY RESPECT AND THAT ANY MATERIAL OR
WORK NOT SPECIFICALLY MENTIONED OR SHOWN ON THE
DRAWINGS, BUT NECESSARY TO FULLY COMPLETE THE WORK
SHALL BE FURNISHED.
THE LOCATION OF RECEPTACLES AND FIXTURES SHOWN ON THE
DRAWING IS APPROXIMATE AND THE OWNER SHALL HAVE THE
RIGHT TO RELOCATE ANY RECEPTACLES OR FIXTURES BEFORE,
THEY ARE INSTALLED WITHOUT ANY ADDITIONAL COST.
I
35. CABLE TYPES AC AND NM ARE NOT ALLOWED. IF USED, FLEXIBLE
TYPE MC CABLE SHALL HAVE A BLUE STRIP.
36. PROVIDE FIRE ALARM SHUTDOWN REQUIREMENT FOR
INTERCONNECTION TO TENANT'S AIR HANDLING UNITS.
37. TENANT SHALL CONNECT TO MALL FIRE ALARM SYSTEM FOR
COMPLETE MONITORING.
ELECTRICAL SYMBOL LEGEND
POWER
SYMBOL
DESCRIPTION
qp
DUPLEX RECEPTACLE MOUNTED AT 15"AFF UNLESS
NOTED OTHERWISE
QUAD PLEX RECEPTACLE MOUNTED AT 15"AFF UNLESS
NOTED OTHERWISE
�DG
DUPLEX DEDICATED GROUND TYPE RECEPTACLE
MOUNTED AT 15"AFF UNLESS NOTED OTHERWISE
�,.DG
�`
QUAD PLEX ISOLATED GROUND TYPE RECEPTACLE
MOUNTED AT 15"AFF UNLESS NOTED OTHERWISE
�GFi
DUPLEX GROUND FAULT INTERRUPTING TYPE
RECEPTACLE
JUNCTION BOX
MOTOR CONNECTION
DISCONNECT SWITCH
®
480/277 VOLT, SURFACE MOUNT SINGLE SECTION
PANELBOARD
208/120 VOLT, SURFACE MOUNT SINGLE SECTION
PANELBOARD
COMMUNICATIONS
ROUGH -IN FOR TELEPHONE VOICE LINE MOUNTED AT
15"AFF UNLESS NOTED OTHERWISE
sz
ROUGH -IN FOR TELEPHONE VOICE / DATACOM
MOUNTED AT 15"AFF UNLESS NOTED OTHERWISE
EMPTY CONDUIT FOR TELEPHONE CABLES TO BE
INSTALLED BY COMMUNICATIONS SUB CONTRACTOR
EMPTY CONDUIT FOR DATA CABLES TO BE INSTALLED
BY DATA COM SUB CONTRACTOR
DOOR BUZZER SIGNALING
Q
DOOR BUZZER PUSHBUTTON - LOCATED AT REAR
DOOR
ri
REMOTE DOOR BUZZER
DOOR BUZZER AND SIGNALING TRANSFORMER
SECURITY SYSTEM
❑KP
S
KEY PAD LOCATION - PROVIDE ROUGH -IN ONLY
[EMD
INFRARED MOTION DETECTOR LOCATION - PROVIDE
ROUGH -IN ONLY
sB
SHATTER BOX - PROVIDE ROUGH -IN ONLY
ALARM HORN ON CEILING - PROVIDE ROUGH -IN ONLY
ADC
DOOR CONTACT SWITCH - PROVIDE ROUGH -IN ONLY
SOUND SYSTEM
CEILING SPEAKER LOCATION - PROVIDE ROUGH -IN
ONLY
Q
WALL SPEAKER LOCATION - PROVIDE ROUGH -IN ONLY
Q
VOLUME CONTROL DEVICE (WALL MOUNTED) - PROVIDE
ROUGH -IN ONLY
FIRE ALARM SYSTEM
FA�CP
FIRE ALARM CONTROL PANEL
OH
HEAT DETECTOR
F
FIRE ALARM HORN
ODs
DUCT MOUNTED SMOKE DETECTOR
P
CEILING MOUNTED SMOKE DETECTOR
F
HORN STROBE -NUMBER INDICATES CANDELLA OF
STROBE
F
STROBE - NUMBER INDICATES CANDELLA OF STROBE
Q
PULL STATION
LIGHTING CONTROL
I
WALL MOUNTED TOGGLE SWITCH
3
I
3-WAY WALL MOUNTED TOGGLE SWITCH
PROGRAMMABLE TIME CLOCK (TO CONTROL
STOREFRONT LIGHTING CIRCUITS)
Q
CONTACTOR (MULTI -POLE)
City ®f-TukW a '
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
JUN T9 2015
PERMIT CENTER
HE Project No:
R 1 5- 2 1 24.01 3
ARcH[TEcr
0
ul
z
m
M
W O
m
(D (D ca
c3�
�-�/ =19
W LL v
W
OOW m �O
JZ E i
�Z58 Darn
= CU n
z 2ul�
= W =Eto
to
�.FETTI;,,
o. iWAS
s��!
44050
O' ISTE�� �0'
SIONALG1
EXPIRESJZ�j/ZO��
LL Review Set Issued:
05/OG/201 5
Permit Set Issued:
05/2G/201 5
51d Set Issued:
05/2G/201 5
Construction Set Issued:
Revisions
No.: Date:
drawn by: CTC
reviewed by: KLS/PJF
scale: AS NOTED
Sheet Title
ELECTRICAL
SPECIFICA'nONS
AND SYMBOL
LEGEND
Sheet No.