HomeMy WebLinkAboutPermit D16-0047 - PACIFIC CARPET DISTRIBUTORS - STORAGE RACKSPACIFIC CARPET
DISTRIBUTORS
1139 ANDOVER PARK W
D16-0047
Parcel No:
Address:
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670
Inspection Request Line: 206-438-9350
Web site: http://www.TukwilaWA.gov
DEVELOPMENT PERMIT
3523049102 Permit Number:
1139 ANDOVER PARK W
Project Name: PACIFIC CARPET DISTRIBUTORS
Issue Date:
Permit Expires On:
D16-0047
4/27/2016
10/24/2016
Owner:
Name: AMB PROPERTY CORP
Address: 60 STATE ST STE 1200 C/O RE TA ,
BOSTON, WA, 02109
Contact Person:
Name:
DAVID VAN ZANDT
Address: 500 SW 16 ST, RENTON, WA, 98057
Contractor:
Name: MR RACKS LLC
Address:
License No:
Lender:
Name:
Address:
500 SW 16TH ST, RENTON, WA,
98055
MRRACRL924BN
PACIFIC CARPET DISTRIBUTORS
1139 ANDOVER PARK W , TUKWILA,
WA, 98188
Phone: (425) 207-0058
Phone: (425) 207-0058
Expiration Date: 1/17/2018
DESCRIPTION OF WORK:
THE INSTALLATION OF STEEL PALLET RACKING BOLTED TO THE GROUND TO HOUSE CARPET AND ACCESSORIES
Project Valuation: $16,067.00
Type of Fire Protection: Sprinklers: YES
Fire Alarm: YES
Type of Construction: VB
Electrical Service Provided by: TUKWILA FIRE SERVICE
Fees Collected: $724.46
Occupancy per IBC: U
Water District: TUKWILA
Sewer District: TUKWILA SEWER SERVICE
Current Codes adopted by the City of Tukwila:
International Building Code Edition:
International Residential Code Edition:
International Mechanical Code Edition:
Uniform Plumbing Code Edition:
International Fuel Gas Code:
2012
2012
2012
2012
2012
National Electrical Code:
WA Cities Electrical Code:
WAC 296-46B:
WA State Energy Code:
2014
2014
2014
2012
Public Works Activities:
Channelization/Striping:
Curb Cut/Access/Sidewalk:
Fire Loop Hydrant:
Flood Control Zone:
Hauling/Oversize Load:
Land Altering:
Landscape Irrigation:
Sanitary Side Sewer:
Sewer Main Extension:
Storm Drainage:
Street Use:
Water Main Extension:
Water Meter:
Volumes: Cut: 0 Fill: 0
Number: 0
No
Permit Center Authorized Signature:
Date: D Y/.%-,
I hearby certify that I have read and examined this permit and know the same to be true and correct. All
provisions of law and ordinances governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other
state or local laws regulating construction or the performance of work. I am authorized to sign and obtain this
development permit and agree to the condftions attached to this permit.
Signature:
Print Name:
DAV) b VAN 7 dNIPT
Date: y/`' 6
This permit shall become null and void if the work is not commenced within 180 days for the date of issuance, or if
the work is suspended or abandoned for a period of 180 days from the last inspection.
PERMIT CONDITIONS:
1: ***BUILDING PERMIT CONDITIONS***
2: Work shall be installed in accordance with the approved construction documents, and any changes made
during construction that are not in accordance with the approved construction documents shall be
resubmitted for approval.
3: All permits, inspection record card and approved construction documents shall be kept at the site of work
and shall be open to inspection by the Building Inspector until final inspection approval is granted.
4: All construction shall be done in conformance with the Washington State Building Code and the
Washington State Energy Code.
5: All rack storage requires a separate permit issued through the City of Tukwila Permit Center. Rack storage
over 8 -feet in height shall be anchored or braced to prevent overturning or displacement during seismic
events. The design and calculations for the anchorage or bracing shall be prepared by a registered
professional engineer licensed in the State of Washington. Periodic special inspection is required during
anchorage of storage racks 8 feet or greater in height.
6: There shall be no occupancy of a building until final inspection has been completed and approved by
Tukwila building inspector. No exception.
7: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an
approval of, any violation of any of the provisions of the building code or of any other ordinances of the City
of Tukwila. Permits presuming to give authority to violate or cancel the provisions of the code or other
ordinances of the City of Tukwila shall not be valid. The issuance of a permit based on construction
documents and other data shall not prevent the Building Official from requiring the correction of errors in
the construction documents and other data.
8: When special inspection is required, either the owner or the registered design professional in responsible
charge, shall employ a special inspection agency and notify the Building Official of the appointment prior to
the first building inspection. The special inspector shall furnish inspection reports to the Building Official in
a timely manner.
9: A final report documenting required special inspections and correction of any discrepancies noted in the
inspections shall be submitted to the Building Official. The final inspection report shall be prepared by the
approved special inspection agency and shall be submitted to the Building Official prior to and as a
condition of final inspection approval.
12: The total number of fire extinguishers required for an ordinary hazard occupancy with Class A fire hazards is
calculated at one extinguisher for each 1,500 sq. ft. of area. The extinguisher(s) should be of the "All
Purpose" (3A, 40B:C) dry chemical type. Travel distance to any fire extinguisher must be 75' or less. (IFC
906.3) (NFPA 10, 5.4)
10: Portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied.
Hangers or brackets shall be securely anchored to the mounting surface in accordance with the
manufacturer's installation instructions. Portable fire extinguishers having a gross weight not exceeding 40
pounds (18 kg) shall be installed so that its top is not more than 5 feet (1524 mm) above the floor. Hand-
held portable fire extinguishers having a gross weight exceeding 40 pounds (18 kg) shall be installed so that
its top is not more than 3.5 feet (1067 mm) above the floor. The clearance between the floor and the
bottom of the installed hand-held extinguishers shall not be less than 4 inches (102 mm). (IFC 906.7 and IFC
906.9)
11: Extinguishers shall be located in conspicuous locations where they will be readily accessible and
immediately available for use. These locations shall be along normal paths of travel, unless the fire code
official determines that the hazard posed indicates the need for placement away from normal paths of
travel. (IFC 906.5)
13: Maintain fire extinguisher coverage throughout.
15: Sprinklers shall be installed under fixed obstructions over 4 feet (1.2 m) wide. (NFPA 13-8.6.5.3.3)
14: All new sprinkler systems and all modifications to existing sprinkler systems shall have fire department
review and approval of drawings prior to installation or modification. New sprinkler systems and all
modifications to sprinkler systems involving more than 50 heads shall have the written approval of Factory
Mutual or any fire protection engineer licensed by the State of Washington and approved by the Fire
Marshal prior to submittal to the Tukwila Fire Prevention Bureau. No sprinkler work shall commence
without approved drawings. (City Ordinance No. 2436).
17: All new fire alarm systems or modifications to existing systems shall have the written approval of The
Tukwila Fire Prevention Bureau. No work shall commence until a fire department permit has been
obtained. (City Ordinance #2437) (IFC 901.2)
18: Maintain fire alarm system audible/visual notification. Addition/relocation of walls or partitions may
require relocation and/or addition of audible/visual notification devices. (City Ordinance #2437)
19: Clearance between ignition sources, such as light fixtures, heaters and flame -producing devices, and
combustible materials shall be maintained in an approved manner. (IFC 305.1)
20: Where storage height exceeds 15 feet and ceiling sprinklers only are installed, fire protection by one of the
following methods is required for steel building columns located within racks: (a) one-hour fire proofing,
(b) sidewall sprinkler at the 15 foot elevation of the column, (c) ceiling sprinkler density minimums as
determined by the Tukwila Fire Prevention Bureau. (NFPA 13-16.1.4)
21: Storage shall be maintained 2 feet or more below the ceiling in nonsprinklered areas of buildings or a
minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings. (IFC 315.3.1)
22: Flue spaces shall be provided in accordance with International Fire Code Table 3208.3. Required flue
spaces shall be maintained.
16: Contact The Tukwila Fire Prevention Bureau to witness all required inspections and tests. (City Ordinances
#2436 and #2437)
23: Any overlooked hazardous condition and/or violation of the adopted Fire or Building Codes does not imply
approval of such condition or violation.
24: These plans were reviewed by Inspector 511. If you have any questions, please call Tukwila Fire Prevention
Bureau at (206)575-4407.
PERMIT INSPECTIONS REQUIRED
Permit Inspection Line: (206) 438-9350
1700 BUILDING FINAL**
1400 FIRE FINAL
4046 SI-EPDXY/EXP CONC
CITY OF TUKWILA
Community Development Department
Public Works Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http://www.TukwilaWA.gov
Building Permit No. IN1461Q 9 7
Project No.
Date Application Accepted:
Date Application Expires:
(For office use only)
CONSTRUCTION PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
**Please Print**
SITE LOCATION
Site Address: f134 MJrJavat RA121C w6s7 -
Tenant Name: RAGIFIG CA1LP r D15T216t/r4Y.s
PROPERTY OWNER
Name: DAVID VAN 2AN
Name:rit RlA0
Address: Soo s(A) 16TM Sr
Address: 1f3q ANOovet. $►PARK
l6ST
City: TV KW 11-A State: %n/A
Zip: more
CONTACT PERSON — person receiving all project
communication
Name: DAVID VAN 2AN
Address: 500 SW 'f(T" Sr
Address: Soo s(A) 16TM Sr
Phone: 42s. 207. U4S$ Fax:
City: RENTO NI State: wA
Zip: Avt:6 7
Phone: L/2.6.207.065*. Fax:
Email: pAvlo®MRRAGicS.coM
GENERAL CONTRACTOR INFORMATION
Company Name:
J'1R•7tAcicS L.1.G.
Address: 500 SW 'f(T" Sr
City: (Zeviron1 State: v4/4 Zip:gvas 7
Phone: 42s. 207. U4S$ Fax:
Contr Reg No.: M Rmu„ g2.4 814 Exp Date: 1.16-17
Tukwila Business License No.: Mam„t-42H
H:\Applications\Fornss-Applications On Line \2011 Applications\Permit Application Revised - 8-9-11.docx
Revised: August 2011
bh
King Co Assessor's Tax No.:
Suite Number: /1,q Floor: 1
New Tenant: 0 Yes /..No
ARCHITECT OF RECORD
Name: to
Company Name:
t PARK wev-
City:T KWIC.,(
Architect Name:
Address:
City:
State:
Zip:
Phone:
Fax:
Email:
ENGINEER OF RECORD
Name: to
Company Name: • Asi Kitcrru A
t PARK wev-
City:T KWIC.,(
Engineer Name: 1Q IL lORiTVLA
Address: 2.1122. 126TM' AVE SE
City: N&t\t. State: t./A
Zip:
,psi
Phone: 2.06 _ .61.7303 Fax:
Email:
LENDER/BOND ISSUED (required for projects $5,000 or
greater per RCW 19.27.095) G
Name: to
Address: mgPAIVa00116
t PARK wev-
City:T KWIC.,(
State: w,h Zip:Crein
Page 1 of 4
BUILDING PERMIT INFORMATION — 206-431-3670
Valuation of Project (contractor's bid price): $ M066.4144
Describe the scope of work (please provide detailed information):
T146 INSrA(.r kriotJ OP S'rec. pp her gAcKIN 6, 6oL-r b To 1146 GRAND.
TO Hov56 GARPEl .AND AGCESSoOLYS,
Existing Building Valuation: $
Will there be new rack storage?
Yes
0.. No If yes, a separate permit and plan submittal will be required.
Provide All Building Areas in Square Footage Below
PLANNING DIVISION:
Single family building footprint (area of the foundation of all structures, plus any decks over 18 inches and overhangs greater than 18 inches)
*For an Accessory dwelling, provide the following:
Lot Area (sq ft): Floor area of principal dwelling: Floor area of accessory dwelling:
*Provide documentation that shows that the principal owner lives in one of the dwellings as his or her primary residence.
Number of Parking Stalls Provided: Standard: Compact: Handicap:
Will there be a change in use? 0 Yes ❑ No If "yes", explain:
FIRE PROTECTION/HAZARDOUS MATERIALS:
JZ Sprinklers 0 Automatic Fire Alarm 0 None 0 Other (specify)
Will there be storage or use of flammable, combustible or hazardous materials in the building? 0 Yes No
If "yes', attach list of materials and storage locations on a separate 8-1/2" x 11" paper including quantities and Material Safety Data Sheets.
SEPTIC SYSTEM
0 On-site Septic System — For on-site septic system, provide 2 copies of a current septic design approved by King County Health
Department.
H:' pplications\Forms-Applications On Line \2011 Applications \Permit Application Revised - 8-9-11.docx
Revised: August 2011
bh
Page 2 of 4
Existing
Interior Remodel
Addition to
Existing
Structure
New
Type of
Construction per
IBC
Type of
Occupancy per
IBC
lv Floor
24475
O
0
O
NGl
N/A
2nd Floor
O
q
0
0
3`d Floor
tf 9
O
Co
9
Floors thru
Basement
Accessory Structure*
Attached Garage
Detached Garage
Attached Carport
Detached Carport
Covered Deck
Uncovered Deck
PLANNING DIVISION:
Single family building footprint (area of the foundation of all structures, plus any decks over 18 inches and overhangs greater than 18 inches)
*For an Accessory dwelling, provide the following:
Lot Area (sq ft): Floor area of principal dwelling: Floor area of accessory dwelling:
*Provide documentation that shows that the principal owner lives in one of the dwellings as his or her primary residence.
Number of Parking Stalls Provided: Standard: Compact: Handicap:
Will there be a change in use? 0 Yes ❑ No If "yes", explain:
FIRE PROTECTION/HAZARDOUS MATERIALS:
JZ Sprinklers 0 Automatic Fire Alarm 0 None 0 Other (specify)
Will there be storage or use of flammable, combustible or hazardous materials in the building? 0 Yes No
If "yes', attach list of materials and storage locations on a separate 8-1/2" x 11" paper including quantities and Material Safety Data Sheets.
SEPTIC SYSTEM
0 On-site Septic System — For on-site septic system, provide 2 copies of a current septic design approved by King County Health
Department.
H:' pplications\Forms-Applications On Line \2011 Applications \Permit Application Revised - 8-9-11.docx
Revised: August 2011
bh
Page 2 of 4
PUBLIC WORKS PERMIT INFORMATION — 206-433-0179
Scope of Work (please provide detailed information):
Call before you Dig: 811
Please refer to Public Works Bulletin #1 for fees and estimate sheet.
Water District
❑ ...Tukwila
0 ...Water Availability Provided
Sewer District
❑ ...Tukwila
❑ ...Sewer Use Certificate
❑ ...Water District #125
❑ .. Highline
❑...Valley View 0 .. Renton
❑...Sewer Availability Provided
0 .. Renton
❑ .. Seattle
Septic System:
❑ On-site Septic System — For on-site septic system, provide 2 copies of a current septic design approved by King County Health Department.
Submitted with Application (mark boxes which apply):
❑ ...Civil Plans (Maximum Paper Size — 22" x 34")
❑ ...Technical Information Report (Storm Drainage) 0 .. Geotechnical Report
❑ ...Bond 0 .. Insurance 0 .. Easement(s) 0 .. Maintenance Agreement(s)
Proposed Activities (mark boxes that apply):
❑ ...Right-of-way Use - Nonprofit for less than 72 hours
❑ ...Right-of-way Use - No Disturbance
❑ ...Construction/Excavation/Fill - Right-of-way 0
Non Right-of-way 0
❑ ...Total Cut
❑ ...Total Fill
cubic yards
cubic yards
❑ ...Sanitary Side Sewer
❑ ...Cap or Remove Utilities
0 ...Frontage Improvements
❑ ...Traffic Control
0 ...Backflow Prevention - Fire Protection
Irrigation
Domestic Water
❑ ...Traffic Impact Analysis
❑ ...Hold Harmless — (SAO)
❑ ...Hold Harmless — (ROW)
❑ .. Right-of-way Use - Profit for less than 72 hours
❑ .. Right-of-way Use — Potential Disturbance
❑ .. Work in Flood Zone
❑ .. Storm Drainage
❑ .. Abandon Septic Tank
❑ .. Curb Cut
❑ .. Pavement Cut
❑ .. Looped Fire Line
❑ .. Grease Interceptor
❑ .. Channelization
❑ .. Trench Excavation
❑ .. Utility Undergrounding
❑ ...Permanent Water Meter Size... WO #
❑ ...Temporary Water Meter Size .. WO #
❑ ...Water Only Meter Size WO # ❑...Deduct Water Meter Size
❑ ...Sewer Main Extension Public 0 Private 0
0 ...Water Main Extension Public 0 Private 0
FINANCE INFORMATION
Fire Line Size at Property Line Number of Public Fire Hydrant(s)
0 ...Water 0 ...Sewer 0 ...Sewage Treatment
Monthly Service Billing to:
Name: Day Telephone:
Mailing Address:
City State Zip
Water Meter Refund/Billing:
Name:
Mailing Address:
Day Telephone:
City
State Zip
H:\Applications\Forms-Applications On Linc\2011 Applicationacmnit Application Rcviscd - 8-9-11.docx
Rcviscd: August 2011
bh
Page 3 of 4
PERMIT APPLICATION NOTES —
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review — Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The Building Official may grant one or more extensions of time for additional periods not exceeding 90 days each. The extension shall be
requested in writing and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
I HEREBY CERTIFY THAT 1 HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING 0 ER OR AUTHORI D A NT:
Signature:
Print Name: DAV 1 Q VAIJ ZIlh1D'i
Mailing Address: GOO SW 16T" 5T
Date: Z'2Z ) 6
Day Telephone: (112S) 207-oo5fc-
tZ614TO 4a057
H: Applications\Fonns-Applications On Linc\201 l Applications\Pcrmit Application Rcviscd - 8-9-11.docx
Rcviscd: August 2011
bh
City State Zip
Page 4 of 4
Cash Register Receipt
City of Tukwila
DESCRIPTIONS 1 ACCOUNT 1 QUANTITY 1
PermitTRAK
PAID
$724.46
D16-0047 Address: 1139 ANDOVER PARK W Apn: 3523049102
$724.46
DEVELOPMENT
$703.28
PERMIT FEE
R000.322.100.00.00
0.00
$423.50
PLAN CHECK FEE
R000.345.830.00.00
0.00
$275.28
WASHINGTON STATE SURCHARGE
B640.237.114
0.00
$4.50
TECHNOLOGY FEE
$21.18
TECHNOLOGY FEE
R000.322.900.04.00 0.00
$21.18
$724.46
TOTAL FEES'S D�BRECEIPT: R7738
Date Paid: Monday, February 22, 2016
Paid By: MR. RACKS
Pay Method: CHECK 5673
Printed: Monday, February 22, 2016 11:57 AM 1 of 1
I?SYSTEMS
INSPECTION RECORD
Retain a copy with permit Ditp--00117
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 438-9350
Project: p
► V 1..4-
6 r-.
TYPe of e,>titCik Or C nJo
L ti pn J
Address: It 3 if
4)Date
Called:
Special Instructions.!
.���N
H
Lc..
FLA/wt.-
Date Wanted:
p.m
Requester:
Phone No:
Approved per applicable codes. u Corrections required prior to approval.
COMMENTS:
- eileicctdof ucal-rNi
S/ 4A%a+oR.S
kePoiz2- paodtmF�
F )
�nO�tc, p2A�it�,
AI
6c -os t& Pt-f'11r
Inspector:
Date:
o6(2-1 1
n REINSPECTION FEE REQUIRED. Prior to next inspection. fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection.
INSPECTION RECORD
Retain a copy with permit
SPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 438-9350
P16-0 elf7
Project:
j�gGf-frC C r e f
Ty e of Inspection:G
13(c rrnei. f
Address: ✓
Date Calf d:
Special Instructions:
1141.rf
Am
Date Wanted:
C—
�hs
a.m. a.m.
P.m.
Requester:
PhoneLfj:
20 7- oust
QApproved per applicable codes.
Corrections required prior to approval.
COMMENTS:
Cou6el(ee{ by co*6K-dc-i-DU
( (( 4r ti€ ti pec -11
Inspector:K_E___
Date:5 s 2,7 ,
REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
INSPECTION RECORD
rpIM Retain a copy with permit
�SPECTION NO.
,t)//- Go'7
PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 438-9350
Pr � t: f
,/ C C Carr
Type f ndpecti n:(t `
i(3 f! l
Address: ���
113'f dJ�
,
Date Callen
Special Instructions:
oQ(rrf Ac
rig
Date Wanted:
5-z-7--146
a.m.
p.m.
Requester:
l / in
jj���
/'�C
hP(
Pone -56 /
(74)
0 Approved per applicable codes.
Corrections required prior to approval.
COMMENTS:
v -dr' ' ta(-S a (3-(6
Na lt?„
C:�((
fer vetvispeaid �
Inspector: 1/,
Date ZS (6
REINSPECTION FEE REQUIRED. Prior to next inspection. fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection.
INSPECTION RECORD
Retain a copy with permit
SPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
piL-061-1
6300 Southcenter Blvd., #100, Tukwila. WA 98188
Permit Inspection Request Line (206) 438-9350
(206) 431-3670
t:t
Prfrcfccrp
Type of ns ection: r f
11I i %l ( I
0) R,'At(2 f F( rv►c-(( 1 lirS q(7)10 r,
1J
Address.
I f 3 cf iiiitotekkir Ik" P- Ili
Date Calle •
5) cbt-t P.v Pte- I/ — e... ((t (41( �
1,0 y J R %0'
Special Instructions: ?AiDate
fecfS
Want?j:� C
a.m.
p.m.
Re nester:
lic. vc a i%CGc
f
Phone No:
1 `17.2- 7-oo
)
CApproved per applicable codes.
Corrections required prior to approval.
COMMENTS: `-
rf vet, ( ft o - Pn 0 4
0) R,'At(2 f F( rv►c-(( 1 lirS q(7)10 r,
1J
'i) I j -s--k,' b I e -t -f -k-
5) cbt-t P.v Pte- I/ — e... ((t (41( �
1,0 y J R %0'
1-e 00
CA (C EzN-- .e_c-4.-('0 in
Y
Inspector:
Date: 3 ,1 b
REINSPECTION FEE REQUIRED. Prior to next inspection. fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection.
Ki
of
INSPECTION NUMBER
INSPECTION RECORD
Retain a copy with permit
PERMIT NUMBERS
CITY OF TUKWILA FIRE DEPARTMENT
206-575-4407
Project:
Sprinklers:
Type of-In/s�pection:
Address:.Contact
Suite #: 9
/
Pkt1
Person:
Special Instructions:
Occupancy Type:
Phone No.:
Approved per applicable codes.
Corrections required prior to approval.
COMMENTS:
Sprinklers:
Fire Alarm:
Hood & Duct:
Monitor:
-.
Permits:
Occupancy Type:
--=
7,'-/-44e ,rS
,%'-S
-.--
7)k/
/ imi A/(..L - FYI gieva 14lir
l
i if
1.-----">
0 g
% v
/ate C;6116/ g/V i2itr. — w c -4(f il-
Needs Shift Inspection:
Sprinklers:
Fire Alarm:
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
i
Inspector(
,ji f-5
Date: 0 c/h (,
Hrs.:
/, Ca
/
$100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. CaII to schedule a reinspection.
Billing Address
Attn:
Company Name:
Address:
City:
State:
Zip:
Word/Inspection Record Form.Doc
3/14/14
T.F.D. Form F.P. 113
INSPECTION NUMBER
INSPECTION RECORD
Retain a copy with permit
D1° Doy7
PERMIT NUMBERS
,CITY OF TUKWILA FIRE DEPARTMENT.
206-575-4407
Project:—Fil--c4A.c,
(„../117e f
Type of Inspection::`
/C
Address:
Suite #: /3
", J
Contact Person:
Special Instructions:
Occupancy Type:
Phone No.:
Approved per applicable codes.
Corrections required prior to approval.
COMMENTS:
Sprinklers:
Fire Alarm:
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
A/ A'
7:2C.47(4---/ A91
cad /1/
a,- - -
/
A57
y", (lN L?
dvdR-S (0 G4-7 /6(
,4#
,24)//
//v5-1111
S 7 j
/u,4(
Au S e ,
',/1-7),
/tt l- ,----/c- /-G
. —1 404 2
. l u/ ) (L j tOlit /P
O/
‹,4c/! / -~z
/JN- /4z'
Needs Shift Inspection:
Sprinklers:
Fire Alarm:
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
Inspector
s�5C-?
Date: ��/d//6 -
Hrs.:
, d
$100.00 REINSPECTION FEE REQUIRED. Yo ti will receive an invoice from
the City of Tukwila Finance Department. Call to schedule a reinspection.
Billing Address
Attn:
Company Name:
Address:
City:
State:
Zip:-
Word/Inspection Record Form.Doc
3/14/14
T.F.D. Form F.P. 113
CONFIRMATION #:
A.A.R. TESTING LABORATORY, INC.
P.O. BOX 2523 Phone: (425) 881-5812
REDMOND, WA 98073 FAX: (425) 881-5441
CLIENT:''
ATTN:
ADDRESS:
FILE: NO
/32616
PROJECT IrAcrPit GAR5Tizii3vISZ
ADDRESS 1139 4,,J ib/if? PAI
0/ lei A rnit-A
ARCHITECT:<.
CONTRACTOR,;; > r-' R. 7Z,/4 G c
....................
PERMIT NO
1,I% -i6/1
TIME -4 limo' ds 1 : . TEMPI 444
®j Sri F:'Z A 44( For< i s s. FA Li_ sr T'
eget 1c 051.;7 s1 tli 7 . ookia•-• ate T. Z 4. -2f -rt. A,.IIr%25 94) )(Li --4/
Z ?£2 134Sfc Fall. Ar APtfizOv "S £.r' nc-pi-►EJ-r-AGI. / i4e, 5
ISE i� v'R- 343 rc� o,s G,7,6k5 /"*7g# c>Kf-n
A 4A RA1-10 -I'caR41,1C W 2'24.k.;:4-1
f 403 - Ff- LOS oia (t A 7% r I,-1
RA4-44,s rJ -PtAi' t-OcAr,ar 13Z,3 1?-, 6,, 13, 1 13,3 13,6 •, 13,9 •, Iu,1 14,1
•1 )O i ds Fi? / 4.3 41‘117 1 ,6 13. -1 AIM Jrr6
CpkffRAci iva—rgc, *' r ,i rfi '4 . A1' -rig rS Tlr-y�
PLA G i ,-r t^r1 f 1 r`i C it -1 irOr7 r -i. A,JeZ ri-( t-,/,40, (j rr S Pet.4 s Gr�a t->'�C��T' poe i,-t,,A )r5
z6$ 31
/INSPECTOR
ALL REPORTS ARE CONSIDERED CONFIDENTIAL AND ARE THE PROPERTY OF THE CLIENT AND A.A.R. TESTING LABORATORY, INC.
REPRODUCTION EXCEPT IN FULL, WITHOUT THE WRITTEN CONSENT OF A.A.R. TESTING IS STRICTLY FORBIDDEN.
A.A.R. TESTING LABORATORY, INC.
P.O. BOX 2523 Phone: (425) 881-5812
REDMOND, WA 98073 FAX: (425) 881-5441
CLIENT::``
ATTN:
ADDRESS:
Dlb —007
CONFIRMATION #:
FILE NO
PROJECT
ADDRESS:
CITY::>
41 -
DATE:
Gt
ENGINEER:>.:>.<
ARCHITECT:
CONTRACTOR:
c
OWNER:
PERMIT:NO :
TIME:I TEMP:J
ot(1/4^)(40
„Co ( \e‘C 04.
-\C2G-4.S an
see � -Iry �4.0 h S71s
.0t4(,,\,kv‘,401/44kc v S4���,
1 `3
c>\/(v l,1c 2, cagy\ �� t. ► ) ,�' G /,!
t.„41/4 1 ` 4e Q \C .gee. c)
,CV / 11P,.S
.10& \,;\ ca.ci4 \744
Arc-vb‘")
INSPECTOR
ALL REPORTS ARE CONSIDERED CONFIDENTIAL AND ARE THE PROPERTY OF THE CLIENT AND A.A.R. TESTING LABORATORY, INC.
REPRODUCTION EXCEPT IN FULL, WITHOUT THE WRITTEN CONSENT OF A.A.R. TESTING IS STRICTLY FORBIDDEN.
f'L
Field Report Report #: 65081
A.R. Testing Laboratory, Inc. 7126 180th Ave.N.E., Park 180, Suite 0101, Redmond, WA
Phone 425.881.5812 Fax 425.881.5441
8052
Client: Mr. Racks
500 S.W. 16th St.
Renton, WA 98057
Contact: Carey Ferguson
Project Number: 16-346
Permit #: D16-0047
Project Name: Pacific Carpet Distributors
Address: 1139 Andover Park W.
Inspection Performed: Proprietary Anchors
Date: 5/13/2016
Time:
Temperature:
On site for wedge anchor inspection for steel pallet racking.
Contractor used Simpson Strong Bolt 2, wedge anchors, 1/2" diameter x 4 3/4". Two per base plate
at approximately 3" embedment depth, diagonal with 4+ holes. Per ESR 3037 torque was
measured at 60 ft. lbs. or greater using a calibrated torque wrench.
Racks in placed at locations, B/12.3. 12.6, 13.1, 13.6, 13.9, 14.1 and 14.3. Two bays from B14.1,
14.3 and 8/13.6, 13.9 are not present. Contractor elected to not install at this time.
Placement in conformance with manufacturer's specification and contract documents.
RECEIVED
CITY OF TUKWILA
MAY 2 6 2016
PERMIT CENTER
Distribution:
i%: Distribute Client Distribute Contractor
Inspector: Gabrys, Jorden
Distribute Engineer Distribute Owner
;v! Distribute Municipality Distribute Other Reviewed by: Michele Guerrini
Distribute Architect Distribute Other
All reports are considered confidential and are the property of the client and A.A.R. Testing Laboratory, Inc.
Reproduction except in full without the written consent of A.A.R. Testing is strictly forbidden
i
riLr
Job Ittie PACIFIC CSAtt r 1Sie,6. Tu i y erg, Date .2-20* Job No. moor 3
AM
Subject 4a - FDtM eO S&et rtu e 1Z4 / tJ4 J'Checkeci sheet 1 of 3
(fatiactisis 4 2 es' -i 01x ItAczs Coopn/t i 7p wit Wiz DR'
gEc zw , -nie Wet gm.r C St -C. is 5.3 Asa' 7-/o
L/s,,s We As Ase ew V ;: p.14 Cr Zp k1 r
Lode -A6 rp = !.o p4cru7y J,r avrop',u 7, lxe pu,uc .��� ‘I
,` itis
�'s • t 2A) FA.Ass)ii
s : 1.442 rte. The P4C1iy ,4OO1Z&!r, ,
tic a ho ppot sire' Ct44s D .
g = 4-r0 772-445v 1.444 cep, ,,11, Vrtwo. MIs2tds,
It = 6. v 1,001J44r. C ADA) 40'L !I; x 0.04: WAS ,
Pts - ti • 10714PL,tp ' n. + Di. t- . 25 GC Wye 11.= -GL
mAx. tiricz Liao /tev. / pA4 Pr 4fotimJ :Meg- 66
(t) g,ac s type, 04 ; 3,000 Las . ale tool //cvo. Fog, Z.
lb) se,Ack4 Trpb 6,t 2,006 Cj3 . pm Ate eu& 1.0 /!d Aare ,1),ItercsboiJs
711A4334. 1.(. % Moe A At.44v Co,vriezic IT A) s . 47s 3000 4-JOo : a/ielteVeL
V,-. 0,1404,43v 0Lu3v 2.1to • 1.4tlkr a 140.1? a`
S&#& ,u : tt+Z .gz k1 Q le 4v. 3 3q " 60)0J)
yes 1 : 4. rti t
M • a Com. t) JZ . 3,14s- t` r = 719 41 V • 31O /CoLm4
WO 9,3 Top Usve t *Aug V f 0.44ite t4 *' r s 7 lei b''er i EL d% CAA..
r 2 D.-r(*.r714-4.SD) + 0.,s ., 4.t..b" ._
2- yi'cby 4.3/4' 5iinpaoJ Sb-Zestwa JJc (Be)etmpte.- tAiffi6 pOrs
cis On : 210 t.) p r --El �t -3037 c)' specie � , spEcrtc
c n 4 SS Z$' 4) �j� s .5..# , : � l iia j 1,7Q w I ,,i S .� coU / .,Ca w'�. i 5' '
,
12660
`\: Ff .
O1,AL
24
l(4.
REVTEwED FOR
CODE ..IAN' , 1-0 r 7u = 1176 #
APPROVED rut), 1),, 4. Vu//, Vn 0.53 4- .6), ,s. o , G7
AP10/5010 44 Ace Vr 7 1.014- A6 (T►eA .4 AAcAr )
c►#Thkwi. f�eti, - L'')2-- (4) J . sa Go"City
BUILDING DIVISION =
1. bpi -i7 40, - 12 1, Z1
bL
= 74,0
o% < /. 24)
RECEIVED
CITY OF TUKWILA.
FEB 22 2116
PERMIT CENTER
i
Job Title
Subject
Date Z 2.0
Checked
Job No. 300 / 3
Sheet -2 of
TALL Auc6s ,KG1l2 sc11.4:x a4 C-5Ec ieMs : Ae A28v °".i„d
.40
Pc a A* Fit. a It 3 �'-� *4 '? O.7: f
tOse pGk ', 6 Vox G = 4,44f
pL4ry Axe 5:2%3/81' 4' 4 _ 40.00a„ a+
z 0447 104 - Plc t .4.1zpo .gyp . o .7 x '' .. 1.750 kat
late ptiere +M = O.4(4 Ca.11 /z = o. 522 14."/-
=
.c.,I r: 27 k 49Lp = 0.?41' — tsk E A uAc ..3!$
5° -Mick CCeaC. $14 E44'7Y f - 2, WO psi
1418 *u = 5Gil Oa . (14 jam; 04= 04 id r14)
LJ
Riots SNA Q 0,044v 50/12 I, c, 312. k.'1.
�•
312. Z p("LIZ , tisiii& / ps C.s k a
$124G �b w (24 t 5.0 1-6.0) 6242-1- 5.0 4. 8,4 %A 5.7441-
= AbK h p 41.4s4 - '7- Pc
L.oict‘e,, bg1L. I. TM A fiAC441 CoA M (..
V c. Wok 3 2. /2 7 8.331'/Co i4
Fi'r-r • ovik &_ 434 1 x asg
}?.o' spAtx kite A►A3r. We/CAC
-rte PPM t4 i /WC*. iie s h)
k 1 ) co' i3RrAC1ttr-rT .1 57D W
M L*; CaS1Z. w.` Q = tz,c;"'
Sx, O.410IA . 28,43 k
SIMS 1Ai : 22,07 */$E,AM
Deft /0 r coom-040
rthAta
i
4. o-44sS$w
.sew
0)
lea= ce-
d $ L", Lyz
1
41,g8 &Jo ok ACt4c k * ISS0 */1361,1
LisiA4 At kr - Mk* ',7 4* 4.73S
tWm Gam47y 6o 440Th k tli2G 2. k"
CvPe 1,1) = ,IS --(0S00) -4- So r P I $ */ =Gm
Job Title By Date 2- 240" Job No. 14, D 13
Subject Checked Sheet 3 of 3
6ht. I t *4 Tarot- &•o 4Wt g . s (1'•:/ 4. ZIA? z
< C/ er 444 r /2.45 .
01(
OS,
COL 0/414 S kite 3 x 3 A 14. CA C—Secy/bN J i7t 34- ACPril/241
044 Of 5j e = o, 1►;." • to (r). >gy a. r .x t.260"
4 1,115 `+
r 2./ #i �`�,aor/ i;-4 0.2615 sr 3.197"
;UAL - r -412 s leo ° 4 : 1./ (k yr s, ga 9r' . 44,4
.14 s2.4
I, 4 c)ci 4,t pit = az„40
.b l .�
5Zw kr a, .g = 284'3 ► eadrAgAr
.ems ---
4=,E= to? -1
0.1(4,4 +0.16- : 3,s3 k -{ a 6.0 kepi
r 7, 3 S ko . %"gic,To 12,4 t5; 60► . Mi i " 30 kg,;
e gk o. cI4 4 o. c 7 ,. 4,c13 — 9k 1.0
J
March 09, 2016
f
City of Tukwila
Department of Community Development
DAVID VAN ZANDT
500 SW 16 ST
RENTON, WA 98057
RE: Correction Letter # 1
DEVELOPMENT Permit Application Number D16-0047
PACIFIC CARPET DISTRIBUTORS - 1139 ANDOVER PARK W
Dear DAVID VAN ZANDT,
Allan Ekberg, Mayor
Jack Pace, Director
This letter is to inform you of corrections that must be addressed before your development permit can be approved. All
correction requests from each department must be addressed at the same time and reflected on your drawings. I have
enclosed comments from the following departments:
FIRE DEPARTMENT: Al Metzler at 206-971-8718 if you have questions regarding these comments.
• Smoke vents are required in the warehouse per International Fire Code Table 3206.2. Please submit a drawing
showing the existing/proposed smoke vents.
Please address the comments above in an itemized format with applicable revised plans, specifications, and/or other
documentation. The City requires that two (2) sets of revised plan pages, specifications and/or other documentation be
resubmitted with the appropriate revision block.
In order to better expedite your resubmittal, a 'Revision Submittal Sheet' must accompany every resubmittal. I have
enclosed one for your convenience. Corrections/revisions must be made in person and will not be accepted through the mail
or by a messenger service.
If you have any questions, I can be reached at (206)433-7165.
Sincerely,
114
achelle ' ipley
Permit Technician
File No. D16-0047
6300 Southcenter Boulevard Suite #100 • Tukwila Washington 98188 • Phone 206-431-3670 • Fax 206-431-3665
?ERMIT COORD COPY
PLAN REVIEW/ROUTING SLIP
PERMIT NUMBER: D16-0047 DATE: 03/26/16
PROJECT NAME: PACIFIC CARPET DISTRIBUTORS
SITE ADDRESS: 1139 ANDOVER PARK W
Original Plan Submittal
Revision # before Permit Issued
X Response to Correction Letter # 1 Revision # after Permit Issued
DEPARTMENTS:
Building Division
Public Works
AlAi td 4 -)4 --Cc
Fire Prevention 1�1
Structural
Planning Division
' I Permit Coordinator
PRELIMINARY REVIEW:
Not Applicable n
(no approval/review required)
DATE: 03/29/16
Structural Review Required
REVIEWER'S INITIALS: DATE:
APPROVALS OR CORRECTIONS:
Approved
Corrections Required
❑ Approved with Conditions
❑ Denied
(corrections entered in Reviews) (ie: Zoning Issues)
Notation:
DUE DATE: 04/26/16
REVIEWER'S INITIALS:
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
12/18/2013
PERMIT COORD COPY
PLAN REVIEW/ROUTING SLIP
PERMIT NUMBER: D16-0047 DATE: 02/22/16
PROJECT NAME: PACIFIC CARPET DISTRIBUTORS
SITE ADDRESS: 1139 ANDOVER PARK W
X Original Plan Submittal Revision # before Permit Issued
Response to Correction Letter # Revision # after Permit Issued
DEPARTMENTS:
k! I�W1 2
Building Division
Public Works
1 -fp
re
n
MO G0 h1/19.0
Fire Prevention NIP
Structural
Planning Division
nPermit Coordinator
1
PRELIMINARY REVIEW:
Not Applicable n
(no approval/review required)
DATE: 02/23/16
Structural Review Required
REVIEWER'S INITIALS: DATE:
APPROVALS OR CORRECTIONS: DUE DATE: 03/22/16
Approved
Corrections Required
❑ Approved with Conditions
n Denied n
n
(corrections entered in Reviews) (ie: Zoning Issues)
Notation:
REVIEWER'S INITIALS:
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg Vi Fire 0 Ping ❑ PW 0 Staff Initials: K-
12/18/2013
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670
Web site: http://www.TukwilaWA.gov
REVISION
SUBMITTAL
Revision submittals must be submitted in person at the Permit Center.
Revisions will not be accepted through the mail, fax, etc.
Date: 5/23&
Plan Check/Permit Number: D I6YoUN 7
Response to Incomplete Letter #
Response to Correction Letter #
❑ Revision # after Permit is Issued
❑ Revision requested by a City Building Inspector or Plans Examiner
❑ Deferred Submittal #
Project Name: g6/f' G rot e• ri 'S- r i bu
Project Address: I r363 ANrov . (4 j( 1, j
Contact Person: PAVID t/4N 7.4N DT PhoneNumber:C%1ZS) 207-0o65
Summary of Revision:
AlpfED SMOG VENTS To t,*ov7 t AL✓1N
RECEIVED
CITY ®F TUKWIL/-
MAR '2 3 2016
IT CENTER
Sheet Number(s):
"Cloud" or highlight all areas of revision including dat; of rvisio
Received at the City of Tukwila Permit Center by:
❑ Entered in TRAKiT on
W:\Permit Center\Templates\Forms\Revision Submittal Form.doc
Revised: August 2015
MR RACKS LLC
Washington State Department of
abor & Industries
Homo Es a iol Contact
Safety & Health Claims & Insurance
Page 1 of 2
Search L&I
A -Z, Index Help My Li&I
Workplace Rights Trades & Licensing
MR RACKS LLC
Owner or tradesperson
Principals
Ferguson, Carey Scott, PARTNER/MEMBER
Ferguson, Julie Lynn, PARTNER/MEMBER
Ferguson, Carey Scott, AGENT
GONSER, BRETT, PARTNER/MEMBER
(End: 04/30/2013)
MCLENDON, ROBERT, PARTNER/MEMBER
(End: 04/30/2013)
Doing business as
MR RACKS LLC
WA UBI No.
602 779 014
500 SW 16TH ST
RENTON, WA 98057
425-207-0058
KING County
Business type
Limited Liability Company
Governing persons
CAREY
FERGUSON
JULIE FERGUSON;
License
Verify the contractor's active registration / license / certification (depending on trade) and any past violations.
Construction Contractor
License specialties
GENERAL
License no.
MRRACRL924BN
Effective — expiration
01/03/2008— 01/17/2018
Bond
..............
AMERICAN CONTRACTORS INDEM CO
Bond account no.
100031015
Active.
Meets current requirements.
$12,000.00
Received by L&I Effective date
01/03/2008 12/20/2007
Expiration date
Until Canceled
Insurance
.... ........................
Ohio Security Ins Co $1,000,000.00
Policy no.
BKS1654574031
Received by L&I Effective date
05/27/2015 06/29/2015
Expiration date
https://secure.lni.wa.gov/verify/Detail.aspx?UBI=602779014&LIC=MRRACRL924BN&SAW= 4/27/2016
‘.
246'-0"
NOTES:
1. ALL PALLET RACK POSITIONED TO LEAVE A 6" FLUE SPACE
MINIMUM ON ALL SIDES WHEN LOADED.
2. SHELF SUPPORTS ARE WIRE DECK OR 2 X 6 WOOD SUPPORTS - NO
SOLID SHELVES
3. WAREHOUSE AREA IS APPROXIMATELY 26,975 SQ. FT.
15J
REVISIONS
No changes shall be made to the scope
of work with !:t prior approval of
;t'; -'iiia Luiadirtg Division.
will require a new plan submittal
1 6/N and may include additional plan reviewfeed
49'-0"
es
49'-0"
49'-0"
49'-0"
50'-0"
z
W
z
w
U
12' TYP FOR B RACKS
A
EMST.TRM'SFVNNER j
ro RERAN.
GAS
,V,ItATE PERMIT
7.QUiTilEDFOR:
170 rl chanical
1-44fle U icai
f 'T9mbing
"t i aS Piping
C '/ of Tukwila
n'^,,1 ENVISION
PILE COM
P r ft No. 'b1(- O'1
Plan review approval is subject to errors and omissions.
Approval of co: �str ciion documents does not authorize
the violation of any€adopicd codo or ordinance. Rccoipt
of approval ► iok! Copy and co i io i ac owlodL,cd:
Ls.
Date: 41/2?/!
City of Tukwila
BUILDING DIVISION
co
N
r -
N
N
CORRE
LTR#
TIQN
VIEWED FOR
CODE COMPLIANCE
i
+..1 APPROVED
Y APR 2 5 2016
City of Tuttvv la
%AMINO DIVISION
RECEIVED
CITY OF TUKWILA
MAR 2 3 2016
PERMIT CENTER
1
rha
A
0
43 WI
0
IFM8gPcg
CJE-
W A
SAaO OwrME
0-569-9765
17110 S.E 2
em
0
.moi
-f—
vi
ES
0
co
00 -•
Er_ CO en
—
D e[
DRAWN BY:
CF
SCALE:
NONE
DATE:
10-2-15
DRAWING NO:
CHECKED BY:
B. Kattula
SHEET NO.
1
OF 2 SHEETS
246-0"
NOTES:
1. ALL PALLET RACK POSITIONED TO LEAVE A 6" FLUE SPACE
MINIMUM ON ALL SIDES WHEN LOADED.
2. SHELF SUPPORTS ARE WIRE DECK OR 2 X 6 WOOD SUPPORTS - NO
SOLID SHELVES
3. WAREHOUSE AREA IS APPROXIMATELY 26,975 SQ. FT.
49'-0"
49'-0"
49'-0"
49'-0"
50'-0"
,' 13'-0",'
42" X 120"
N
A
P 42" X 120 142
A
iC
A
N
A
a a
0.4
A A
T
A A
E
Nml"' • tV'
A A
A A
T
X X
A—A
as
A A
a a
DC DC
A A
13'-0"
('7Yl lA
I13'-0"
13'-0"
12'-9"
I><
_.-
IIS ..•
\
II \1"r
1 :;111,
0 0 0
DIRVAIRIOIR
TOPIIWIL
>,
•rAr4
AMMO
iw..n.aratl
246'-0"
2'-10"
5'r0"
20'-8"
N
1TTY! FMB La3
B
0.4
B
PC
4
B
A
B
is
B
a
4
B
4
B
a
4 I 4
B B
� PC
B_ B
aha
B B
B B
is I
B B
-krI�
B B
a a
04
B
B
ELEC.
GAS
►i�
0
N 4
N
N
N
CB`
`DJ
REVIEWED FOR
CODE COMPLIANCE
APPROVED
APR 2 5 2016
City of Tukwila
BUILDING DIVISION
• RECEIVED
CITY OF TUKWILA
FEB 22 2016
ERMIT CENTER
660 fr
A /1(.'(. I U\Z?';\,44/
•
b1(0 OoLl7
DESCRIPTION
rig
cs
to
co
(.0)
da
C0
0IR 04° 20
.A -+8,
g
U
cri
12
DRAWN BY:
CF
SCALE:
NONE
DATE:
10-2-15
DRAWING NO:
CHECKED BY:
B. Kattula
SHEET NO.
1
OF 2 SHEETS ito
3/8" THK
—®-3'-6" Dal
SIDE
FRONT
RACK TYPE A
3'-6"OR 3'-8"
SIDE
RACK ELEVATIONS
SCALE: 1/2" = 1'
FLOOR ANCHOR DETAIL
SEE NOTES FOR SPECS
BRACING CONNECTION DETAIL
r
10'
FRONT
RACK TYPE B
BASE PLATE DETAIL
.375 R
DQQ��OC30
O D D O D O
2" TYP.
AS NOTED
In
3
1
14GA THK.
7/8"
3"
—'-I La -3/4"
COLUMN DETAIL
RACK DETAILS
SCALE: 3" = 1'
R1/8"
TYP.
STRUCTURAL NOTES:
1. RACKS ARE MANUFACTURED BY LODI METAL TECH OF LODI, CA. OR EQUAL.
2. MINIMUM YIELD (Fy) AND ULTIlVIATE (Fu) STEEL STRENGTHS FOR SELECTIVE RACKS SHALL BE AS
FOLLOWS:
(a) BEAMS AND COLUMN'S Fy=50ksi Fu=65ksi.
(b) BRACING STRUTS Fy=36ksi Fu=58ksi.
(c) BASE PLATES FY=36ksi Fu=58ksi.
3. MAXIMUM RACK LOAD PER LEVEL PER PAIR OF BEAMS SHALL BE AS FOLLOWS:
(a) RACKS TYPE A: 3,000 LBS
(b) RACKS TYPE B: 2,000 LBS
4. CONCRETE SLAB IS GIVEN AS 5" THICK WITH fc'=2,500 psi.
5. ALLOWABLE SOIL BEARING PRESSURE IS GIVEN AS 1,500psf FOR GRAVITY LOADS.
6. TIE -DOWN ANCHORS SHALL BE SIMPSON STRONG BOLT II WEDGE ANCHORS. USE
TWO (2) 1/2" 0 X 4-3/4" ANCHORS WITH A 3" EMBEDMENT PER BASEPLATE. PLACE ANCHORS
DIAGONALLY ON BASEPLATE FOR ANY BASEPLATE WITH FOUR HOLES.
SPECIAL INSPECTION IS REQUIRED.
7. POST LOAD SIGNS NOT LESS THAN 50 SQUARE INCHES IN AREA SPECIFYING THE
DESIGN CAPACITY AT CONSPICUOUS LOCATIONS.
8. IF ANY DISCREPANCY OCCURS, CONTACT THE ENGINEER FOR CLARIFICATION.
9. ANALYSIS AND DESIGN OF RACK CONFORMS TO THE 2012 IBC SEC 2209, THE 2012 RMI
CODE, AND SEC. 15.5.3 OF SEI/ASCE 7-10 USING THE ASD METHOD WHERE:
V = C1 CS Ip W$ AND Ip 1.0 (RESTRICTED AREA - NO PUBLIC ALLOWED)
S$=1.442
C$ = 2.5 Ca /R AND Ca = 0.3845 FOR THE GIVEN ADDRESS AND SITE CLASS D
S1= 0.536
R = 4.0 BRACED DIR. - TRANSVERSE (BRACED) DIR.
Fa=1.0
R = 6.0 UNBRACED DIR. - LONGITUDINAL (MOMENT) DIR.
10. PROJECT HAS NO FIELD WELDING. ALL WELDING IS COMPLETED IN THE SHOP BY
LICENSED WELDERS.
11. THERE ARE NO SHOP DRAWINGS FOR THIS PROJECT. THIS DRAWING SHALL
SERVE AS THE PROJECT SHOP DRAWING.
FIRE PROTECTION NOTES:
1. SPRINKLER SYSTEM DENSITY IS .39 GPM/5,600 SQ. FT WITH HEAD TEMPERATURE SET AT 286°
2. TYPE OF STORED PRODUCT IS AS FOLLOWS:
a) RACKS TYPE A: CLASS I-IV FLOORING AND SUNDRIES STORED ON PALLETS - NO
ENCAPSULATION.
b) RACKS TYPE B: CARPET AND PAD. PAD TO BE STORED ON THE FLOOR LEVEL ONLY.
TOP OF PAD NOT TO EXCEED 5'.
3. TOP OF STORED PRODUCT NOT TO EXCEED AS FOLLOWS:
a) RACKS TYPE A: 18'-6"
b) RACKS TYPE B: 16'-0"
4. APPROXIMATE CEILING HEIGHT 25'-0".
EXITING NOTES:
1. EXTERIOR DOORS ARE 3' SWING TYPE WITH LOCKING KNOB WHICH REQUIRES
NO SPECIAL KNOWLEDGE OR EFFORT TO OPEN.
2. EXTERIOR EXIT DOORS TO BE MARKED PER APPLICABLE CODE
11/2"
.075 THK-- - 1 1/4"
COLUMN STRUT
O
BRACKET ASSY.
AS NOTED
(f
O
BEAM SECTION 14 GA THK.
ASTM A570 GR50
AS NOTED
BEAM
FOR 120" SPANS
BRACKET ASSY. 23/4"
BEAM SECTION 14 GA THK.
ASTM A572 GR50
BEAM
FOR 106" SPANS
Dt
REV EVVED FOR
%%DE COMPLIANCE
:'' APPROVED
APR 2 5 2016
City of Tukwila
BUILDING DIVISION
O4 12660 aC; a
i G9
z-z-u-gra6
RECEIVED
CITY OF TUKWILA
FEB 22 2016
PERMIT CENTER
rg
C)
a
iml a
ANit
a�
FAW
as
U
253-569-9765
0
03
Covington, WA
17110 S.E 264th
.4*
col
DRAWN BY:
CF
SCALE:
AS SHOWN
DATE:
9-23-15
DRAWING NO:
CHECKED BY:
B. Kattula
SHEET NO.
2
OF 2 SHEETS 4#
8'-10" OR 10'
g 1
1
CO
1
ir
FRONT
RACK TYPE A
3'-6"OR 3'-8"
SIDE
RACK ELEVATIONS
SCALE: 1/2" = 1'
FLOOR ANCHOR DETAIL
SEE NOTES FOR SPECS
BRACING CONNECTION DETAIL
r
10'
FRONT
RACK TYPE B
BASE PLATE DETAIL
.375 R
DQQ��OC30
O D D O D O
2" TYP.
AS NOTED
In
3
1
14GA THK.
7/8"
3"
—'-I La -3/4"
COLUMN DETAIL
RACK DETAILS
SCALE: 3" = 1'
R1/8"
TYP.
STRUCTURAL NOTES:
1. RACKS ARE MANUFACTURED BY LODI METAL TECH OF LODI, CA. OR EQUAL.
2. MINIMUM YIELD (Fy) AND ULTIlVIATE (Fu) STEEL STRENGTHS FOR SELECTIVE RACKS SHALL BE AS
FOLLOWS:
(a) BEAMS AND COLUMN'S Fy=50ksi Fu=65ksi.
(b) BRACING STRUTS Fy=36ksi Fu=58ksi.
(c) BASE PLATES FY=36ksi Fu=58ksi.
3. MAXIMUM RACK LOAD PER LEVEL PER PAIR OF BEAMS SHALL BE AS FOLLOWS:
(a) RACKS TYPE A: 3,000 LBS
(b) RACKS TYPE B: 2,000 LBS
4. CONCRETE SLAB IS GIVEN AS 5" THICK WITH fc'=2,500 psi.
5. ALLOWABLE SOIL BEARING PRESSURE IS GIVEN AS 1,500psf FOR GRAVITY LOADS.
6. TIE -DOWN ANCHORS SHALL BE SIMPSON STRONG BOLT II WEDGE ANCHORS. USE
TWO (2) 1/2" 0 X 4-3/4" ANCHORS WITH A 3" EMBEDMENT PER BASEPLATE. PLACE ANCHORS
DIAGONALLY ON BASEPLATE FOR ANY BASEPLATE WITH FOUR HOLES.
SPECIAL INSPECTION IS REQUIRED.
7. POST LOAD SIGNS NOT LESS THAN 50 SQUARE INCHES IN AREA SPECIFYING THE
DESIGN CAPACITY AT CONSPICUOUS LOCATIONS.
8. IF ANY DISCREPANCY OCCURS, CONTACT THE ENGINEER FOR CLARIFICATION.
9. ANALYSIS AND DESIGN OF RACK CONFORMS TO THE 2012 IBC SEC 2209, THE 2012 RMI
CODE, AND SEC. 15.5.3 OF SEI/ASCE 7-10 USING THE ASD METHOD WHERE:
V = C1 CS Ip W$ AND Ip 1.0 (RESTRICTED AREA - NO PUBLIC ALLOWED)
S$=1.442
C$ = 2.5 Ca /R AND Ca = 0.3845 FOR THE GIVEN ADDRESS AND SITE CLASS D
S1= 0.536
R = 4.0 BRACED DIR. - TRANSVERSE (BRACED) DIR.
Fa=1.0
R = 6.0 UNBRACED DIR. - LONGITUDINAL (MOMENT) DIR.
10. PROJECT HAS NO FIELD WELDING. ALL WELDING IS COMPLETED IN THE SHOP BY
LICENSED WELDERS.
11. THERE ARE NO SHOP DRAWINGS FOR THIS PROJECT. THIS DRAWING SHALL
SERVE AS THE PROJECT SHOP DRAWING.
FIRE PROTECTION NOTES:
1. SPRINKLER SYSTEM DENSITY IS .39 GPM/5,600 SQ. FT WITH HEAD TEMPERATURE SET AT 286°
2. TYPE OF STORED PRODUCT IS AS FOLLOWS:
a) RACKS TYPE A: CLASS I-IV FLOORING AND SUNDRIES STORED ON PALLETS - NO
ENCAPSULATION.
b) RACKS TYPE B: CARPET AND PAD. PAD TO BE STORED ON THE FLOOR LEVEL ONLY.
TOP OF PAD NOT TO EXCEED 5'.
3. TOP OF STORED PRODUCT NOT TO EXCEED AS FOLLOWS:
a) RACKS TYPE A: 18'-6"
b) RACKS TYPE B: 16'-0"
4. APPROXIMATE CEILING HEIGHT 25'-0".
EXITING NOTES:
1. EXTERIOR DOORS ARE 3' SWING TYPE WITH LOCKING KNOB WHICH REQUIRES
NO SPECIAL KNOWLEDGE OR EFFORT TO OPEN.
2. EXTERIOR EXIT DOORS TO BE MARKED PER APPLICABLE CODE
11/2"
.075 THK-- - 1 1/4"
COLUMN STRUT
O
BRACKET ASSY.
AS NOTED
(f
O
BEAM SECTION 14 GA THK.
ASTM A570 GR50
AS NOTED
BEAM
FOR 120" SPANS
BRACKET ASSY. 23/4"
BEAM SECTION 14 GA THK.
ASTM A572 GR50
BEAM
FOR 106" SPANS
Dt
REV EVVED FOR
%%DE COMPLIANCE
:'' APPROVED
APR 2 5 2016
City of Tukwila
BUILDING DIVISION
O4 12660 aC; a
i G9
z-z-u-gra6
RECEIVED
CITY OF TUKWILA
FEB 22 2016
PERMIT CENTER
rg
C)
a
iml a
ANit
a�
FAW
as
U
253-569-9765
0
03
Covington, WA
17110 S.E 264th
.4*
col
DRAWN BY:
CF
SCALE:
AS SHOWN
DATE:
9-23-15
DRAWING NO:
CHECKED BY:
B. Kattula
SHEET NO.
2
OF 2 SHEETS 4#