HomeMy WebLinkAboutPermit D16-0107 - PACIFIC PRIDE STATION - TANKSPACIFIC PRIDE STATION
13435 INTERURBAN AVE S
D16-0107
Parcel No:
Address:
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670
Inspection Request Line: 206-438-9350
Web site: http://www.TukwilaWA.gov
DEVELOPMENT PERMIT
0003000028 Permit Number:
13435 INTERURBAN AVE S
Project Name: PACIFIC PRIDE STATION
Issue Date:
Permit Expires On:
D16-0107
5/9/2016
11/5/2016
Owner:
Name:
Address:
Contact Person:
Name:
Address:
Contractor:
Name:
Address:
License No:
Lender:
Name:
Address:
THORP PROPERTIES INC
4023 WILLIAMS AVE N , RENTON, WA,
98056
BRET HAGDAHL Phone: (360) 423-2245
1121 COLUMBIA BLVD , LONGVIEW,
WA, 98632
PACIFIC NORTHERN ENVIRO CORP Phone: (360) 423-2245
1081 COLUMBIA BLVD , LONGVIEW,
WA, 98632-1024
PACIFNE022MH Expiration Date: 7/1/2016
PETROCARD INC
730 CENTRAL AVE S , KENT, WA, 98032
DESCRIPTION OF
WORK:
INSTALL DIESEL EXHAUST FLUID (DEF) ABOVE GROUND TANK. EXTEND EXISTING ISLAND TO ACCOMODATE NEW
DEF TANK. TANK WITH DISPENSER WILL BE PRE -ASSEMBLED. DEF ISA NONPHAZARDOUS NON-REGULATED, NON-
FLAMMABLE SUBSTANCE.
Project Valuation: $60,168.00
Type of Fire Protection: Sprinklers:
Fire Alarm:
Type of Construction: VB
Fees Collected: $1,874.24
Occupancy per IBC: M
Electrical Service Provided by: TUKWILA FIRE SERVICE Water District: TUKWILA
Sewer District: TUKWILA SEWER SERVICE
Current Codes adopted by the City of Tukwila:
International Building Code Edition:
International Residential Code Edition:
International Mechanical Code Edition:
Uniform Plumbing Code Edition:
International Fuel Gas Code:
2012
2012
2012
2012
2012
National Electrical Code:
WA Cities Electrical Code:
WAC 296-46B:
WA State Energy Code:
2014
2014
2014
2012
Public Works Activities:
Channelization/Striping:
Curb Cut/Access/Sidewalk:
Fire Loop Hydrant:
Flood Control Zone:
Hauling/Oversize Load:
Land Altering:
Landscape Irrigation:
Sanitary Side Sewer:
Sewer Main Extension:
Storm Drainage:
Street Use:
Water Main Extension:
Water Meter:
Volumes: Cut: 0 Fill: 0
Number: 0
No
Permit Center Authorized Signature:
b_ Date: c--9-10
I hearby certify that I have read and examined this permit and know the same to be true and correct. All
provisions of law and ordinances governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other
state or local laws regulating construction or the performance of work. I am authorized to sign and obtain this
development permit and agree to the conditions attach to this permit.
Signature:
Print Name:
DaoliP7,,
Date: 45— 9'"-14=.
f '
This permit shall become null and void if the work is not commenced within 180 days for the date of issuance, or if
the work is suspended or abandoned for a period of 180 days from the last inspection.
PERMIT CONDITIONS:
1: ***BUILDING PERMIT CONDITIONS***
2: Work shall be installed in accordance with the approved construction documents, and any changes made
during construction that are not in accordance with the approved construction documents shall be
resubmitted for approval.
3: All permits, inspection record card and approved construction documents shall be kept at the site of work
and shall be open to inspection by the Building Inspector until final inspection approval is granted.
4: All construction shall be done in conformance with the Washington State Building Code and the
Washington State Energy Code.
5: Notify the City of Tukwila Building Division prior to placing any concrete. This procedure is in addition to
any requirements for special inspection.
6: Remove all demolition rubble and loose miscellaneous material from lot or parcel of ground, properly cap
the sanitary sewer connections, and properly fill or otherwise protect all basements, cellars, septic tanks,
wells, and other excavations. Final inspection approval will be determined by the building inspector based
on satisfactory completion of this requirement.
7: All plumbing and gas piping work shall be inspected and approved under a separate permit issued by the
City of Tukwila Building Department (206-431-3670).
8: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila
Permit Center.
9: Preparation before concrete placement: Water shall be removed from place of deposit before concrete is
placed unless a tremie is to be used or unless otherwise permitted by the building official. All debris and ice
shall be removed from spaces to be occupied by concrete.
10: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an
approval of, any violation of any of the provisions of the building code or of any other ordinances of the City
of Tukwila. Permits presuming to give authority to violate or cancel the provisions of the code or other
ordinances of the City of Tukwila shall not be valid. The issuance of a permit based on construction
documents and other data shall not prevent the Building Official from requiring the correction of errors in
the construction documents and other data.
PERMIT INSPECTIONS REQUIRED
Permit Inspection Line: (206) 438-9350
1700 BUILDING FINAL**
0201 FOOTING
CITY OF TUKWILA
Community Development Department
Public Works Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http://www.TulcwilaWA.gov
Building Permit No. � �p' 0(07
Project No.
Date Application Accepted:
Date Application Expires:
(For office use only)
CONSTRUCTION PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
**Please Print**
SITE LOCATION
King Co Assessor's Tax No.: 003000028
Site Address: 13435 INTERURBAN AVE SOUTH
Tenant Name: PETROCARD SERVICES PACIFIC PRIDE
Suite Number:
New Tenant:
PROPERTY OWNER
Name: BRET HAGDAHL
Name: PETROCARD SERVICES
City: LONGVIEW State: WA Zip: 98632
Address: 730 CENTRAL AVE SOUTH
Email: breth@pnecorp.com
City: KENT State: WA
Zip: 98032
CONTACT PERSON — person receiving all project
communication
Name: BRET HAGDAHL
Address: 1121 COLUMBIA BLVD
City: LONGVIEW State: WA Zip: 98632
Phone: (360) 423-2245 Fax: (360) 423-2272
Email: breth@pnecorp.com
GENERAL CONTRACTOR INFORMATION
Company Name: PNE CONSTRUCTION
Address: 1121 COLUMBIA BLVD
City: LONGVIEW State: WA Zip: 98632
Phone: (360) 423-2245 Fax: (360) 423-2272
Contr Reg No.: PACIFNE022MH Exp Date: 07/01/2016
Tukwila Business License No.: BUS -0995205
H: Applications Worms -Applications On LineVA11 Applications\Pennit Application Revised - 8-9-11.docx
Revised: August 2011
bh
Floor:
❑ Yes ®..No
ARCHITECT OF RECORD
Company Name: Peterson Structural Engineers
Engineer Name: Bill Sandbo
Company Name: NONE
Address: 708 SW Westgate Dr. Suite 100A
Architect Name:
Zip: 98402
Phone: 253-830-2140 Fax:
Address:
Email: bill.sandbo@psengineers.com
City:
State:
Zip:
Phone:
Fax:
Email:
ENGINEER OF RECORD
Company Name: Peterson Structural Engineers
Engineer Name: Bill Sandbo
City: r EivriState: (,\/A Zip: gyri z
Address: 708 SW Westgate Dr. Suite 100A
City: Tacoma State: WA
Zip: 98402
Phone: 253-830-2140 Fax:
Email: bill.sandbo@psengineers.com
LENDER/BOND ISSUED (required for projects $5,000 or
greater per RCW 19.27.095)
Name: NONE eE) etD C /c_ R n It) C.
Address: 730 CE-NrGtAL Ave, S.
City: r EivriState: (,\/A Zip: gyri z
Page 1 of 4
•
BUILDING PERMIT INFORMATION — 206-431-3670
Valuation of Project (contractor's bid price): $ $60,168.00
Existing Building Valuation: $
Describe the scope of work (please provide detailed information):
INSTALL DIESEL EXHAUST FLUID (DEF) ABOVEGROUND TANK. EXTEND EXITING ISLAND TO ACCOMDATE
NEW DEF TANK. TANK WITH DISPENSER WILL BE PRE -ASSEMBLED. DEF IS A NON -HAZARDOUS,
NON-REGULATED, NON-FLAMABLE SUBSTANCE
Will there be new rack storage? ❑ Yes
E.. No If yes, a separate permit and plan submittal will be required.
Provide All Building Areas in Square Footage Below
PLANNING DIVISION:
Single family building footprint (area of the foundation of all structures, plus any decks over 18 inches and overhangs greater than 18 inches)
*For an Accessory dwelling, provide the following:
Lot Area (sq ft): Floor area of principal dwelling: Floor area of accessory dwelling:
*Provide documentation that shows that the principal owner lives in one of the dwellings as his or her primary residence.
Number of Parking Stalls Provided: Standard: Compact: Handicap:
Will there be a change in use? ❑ Yes ❑ No If "yes", explain:
FIRE PROTECTION/HAZARDOUS MATERIALS:
0 Sprinklers 0 Automatic Fire Alarm ❑ None ❑ Other (specify)
Will there be storage or use of flammable, combustible or hazardous materials in the building? 0 Yes ❑ No
If `yes', attach list of materials and storage locations on a separate 8-1/2" x 11" paper including quantities and Material Safety Data Sheets.
SEPTIC SYSTEM
0 On-site Septic System — For on-site septic system, provide 2 copies of a current septic design approved by King County Health
Department.
H:\Applications\Forms-Applications On Line \2011 AppGeatioas Permit Application Revised - 8-9-11.docx
Revised: August 2011
bh
Page 2 of 4
Existing
Interior Remodel
Addition to
Existing
Structure
New
Type of
Construction per
IBC
Type of
Occupancy per
IBC
1st Floor
2nd Floor
3rd Floor
Floors thru
Basement
Accessory Structure*
Attached Garage
Detached Garage
Attached Carport
Detached Carport
Covered Deck
Uncovered Deck
PLANNING DIVISION:
Single family building footprint (area of the foundation of all structures, plus any decks over 18 inches and overhangs greater than 18 inches)
*For an Accessory dwelling, provide the following:
Lot Area (sq ft): Floor area of principal dwelling: Floor area of accessory dwelling:
*Provide documentation that shows that the principal owner lives in one of the dwellings as his or her primary residence.
Number of Parking Stalls Provided: Standard: Compact: Handicap:
Will there be a change in use? ❑ Yes ❑ No If "yes", explain:
FIRE PROTECTION/HAZARDOUS MATERIALS:
0 Sprinklers 0 Automatic Fire Alarm ❑ None ❑ Other (specify)
Will there be storage or use of flammable, combustible or hazardous materials in the building? 0 Yes ❑ No
If `yes', attach list of materials and storage locations on a separate 8-1/2" x 11" paper including quantities and Material Safety Data Sheets.
SEPTIC SYSTEM
0 On-site Septic System — For on-site septic system, provide 2 copies of a current septic design approved by King County Health
Department.
H:\Applications\Forms-Applications On Line \2011 AppGeatioas Permit Application Revised - 8-9-11.docx
Revised: August 2011
bh
Page 2 of 4
•
PUBLIC WORKS PERMIT INFORMATION — 206-433-0179
Scope of Work (please provide detailed information):
NONE
Call before you Dig: 811
Please refer to Public Works Bulletin #1 for fees and estimate sheet.
Water District
❑ ...Tukwila ❑ ...Water District #125
❑ ...Water Availability Provided
Sewer District
❑ ...Tukwila
❑ ...Sewer Use Certificate
❑ .. Highline
❑...Valley View ❑ .. Renton
❑ ... Sewer Availability Provided
❑ .. Renton
❑ .. Seattle
Septic System:
❑ On-site Septic System — For on-site septic system, provide 2 copies of a current septic design approved by King County Health Department.
Submitted with Application (mark boxes which apply):
❑ ...Civil Plans (Maximum Paper Size — 22" x 34")
El ...Technical Information Report (Storm Drainage)
❑ ...Bond ❑ .. Insurance ❑ .. Easement(s)
Proposed Activities (mark boxes that apply):
❑ ...Right-of-way Use - Nonprofit for less than 72 hours
0 ...Right-of-way Use - No Disturbance
El ...Construction/Excavation/Fill - Right-of-way ❑
Non Right-of-way ❑
❑ ...Total Cut cubic yards ❑ .. Work in Flood Zone
❑ ...Total Fill cubic yards 0 .. Storm Drainage
❑ .. Geotechnical Report
❑ .. Maintenance Agreement(s)
❑...Traffic Impact Analysis
El ...Hold Harmless — (SAO)
❑ ...Hold Harmless — (ROW)
❑ .. Right-of-way Use - Profit for less than 72 hours
❑ .. Right-of-way Use — Potential Disturbance
❑ ...Sanitary Side Sewer
❑ ...Cap or Remove Utilities
❑ ...Frontage Improvements
El ...Traffic Control
0 ...Backflow Prevention - Fire Protection
Irrigation
Domestic Water
❑ .. Abandon Septic Tank
❑ .. Curb Cut
❑ .. Pavement Cut
El .. Looped Fire Line
11
❑ .. Grease Interceptor
❑ .. Channelization
❑ .. Trench Excavation
❑ .. Utility Undergrounding
❑ ...Permanent Water Meter Size... " WO #
0 ...Temporary Water Meter Size .. " WO #
❑ ...Water Only Meter Size 3 5WO # ❑ ...Deduct Water Meter Size
❑ ...Sewer Main Extension Public ❑ Private ❑
❑ ...Water Main Extension Public ❑ Private ❑
FINANCE INFORMATION
Fire Line Size at Property Line Number of Public Fire Hydrant(s)
❑ ...Water ❑ ...Sewer ❑ ...Sewage Treatment
Monthly Service Billing to:
Name: Day Telephone:
Mailing Address:
Water Meter Refund/Billing:
Name:
Mailing Address:
City
State Zip
Day Telephone:
City
State Zip
H:\Applicalions\Forms-Applications On Line\2011 Applications\Permit Application Revised - 8-9-11.docx
Revised: August 2011
bb
Page 3 of 4
PERMIT APPLICATION NOTES —
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review — Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The Building Official may grant one or more extensions of time for additional periods not exceeding 90 days each. The extension shall be
requested in writing and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWNER A
Signature:
of /
Date: 01/28/2016
Print Name: BRET HAGDAHLL Day Telephone: (360) 423-2245
Mailing Address: 1121 COLUMBIA BLVD
H:\Applicationsfforms-Applications On Line \2011 Applications'Peunit Application Revised - 8-9-11.docx
Revised: August 2011
bh
LONGVIEW WA 98632
City State Zip
Page 4 of 4
Cash Register Receipt
City of Tukwila
DESCRIPTIONS I ACCOUNT
PermitTRAK
QUANTITY
I PAID
$1,874.24
D16-0107 Address: 13435 INTERURBAN AVE S Apn: 0003000028
$1,874.24
DEVELOPMENT
$1,819.25
PERMIT FEE
R000.322.100.00.00
0.00
$1,099.85
PLAN CHECK FEE
R000.345.830.00.00
0.00
$714.90
WASHINGTON STATE SURCHARGE
B640.237.114
0.00
$4.50
TECHNOLOGY FEE
$54.99
TECHNOLOGY FEE
TOTAL FEES PAID BY RECEIPT: R8285
R000.322.900.04.00
0.00
$54.99
$1,874.24
Date Paid: Friday, April 22, 2016
Paid By: SELIM ABOUNADER
Pay Method: CREDIT CARD 16168D
Printed: Friday, April 22, 2016 2:20 PM 1 of 1
7LJ L� U LJ SYSTEMS
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 438-9350
D{6 -V10
P�at(- �r(
TYp�of IgspectJ(�
Address:
(3 H 3S
urbc't All-�
Date Call
for,
Special Instructions:
A�
Date W nte1.:
(.4a.m.
p.m.
Requester:
Phone No:
I!/11 Approved per applicable codes. El Corrections required prior to approval.
COMMENTS:
Inspector:
Date:/ j
//'
REINSPECTION FEE REQUIRED. Prior to next inspection. fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection.
INSPECTION RECORD
Retain a copy with permit
1)(6-0907
PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 5outhcenter Blvd., #100, Tukwila. WA 98188
Permit Inspection Request Line (206) 438-9350
(206) 431-3670
Pr pct: < +.
rd�- d PG�cIc.i
Type of a tion:
J
� l
Address:
_Mu wr_bakt
Aa Called:
Special Instructions:
Am
�`(�
Date W me
//
a.m.
p.m.
Requester:
Phone No:
Approved per applicable codes. Corrections required prior to approval.
COMMENTS:
Peon
it c A -i c e3S iLocTS Pee AA/ix/Li Aqua:XS
SP6e-S.
Inspector444
Date 2
n REINSPECTION FEE REQUIRED. Prior to next inspection. fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection.
D
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 438-9350
t'i -0/0
P ject:Type
r c (( Z, lir( t
f Inspeftioln:
1-1 it-
Address.�r
35 arta (
�j,i�sd
Date Called:
SpX11
ecial Instructions:
I
,_ r
fuck() (S(Rv
Date Wanted: - /
3 l�
a.m.
p.m.
Requester:
Phone No:
Approved per applicable codes. Corrections required prior to approval.
COMMENTS:
Inspector:
Date: %
n REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection.
SSE
Peterson Structural Engineers, Inc.
rilLt3
Structural Design Calculations
PetroCard Tukwila DEF Tank Anchorage
Tukwila, Washington
Client Information
PNE Construction
1121 Columbia Blvd
Longview, WA 98632
REVIEWED FOR
CODE COMPLIANCE
APPROVED
MAY 0 5 2016
•
City of Tukwila
BUILDING DIVISION
Prepared By:
Peterson Structural Engineers
April 21, 2016
Job No. 16-025
RECEIVED
CITY OF TUKWILA
APR 22 2016
PERMIT CENTER
bL 0107
Consulting Structural Engineers
Portland, Oregon • Tacoma, Washington
www.psengineers.com
Project Site
Tukwila Pacific Pride
13435 Interurban Ave. S
Tukwila, WA 98168
Endorsement
5319 SW Westgate Dr. Suite 215, Portland, OR 97221 • Phone: 503-292-1635
708 Broadway Suite 100A, Tacoma, WA 98402 • Phone: 253-830-2140
SSE
Peterson Structural Engineers, Inc.
Consulting Structural Engineers
Portland, Oregon • Tacoma, Washington
www.psengineers.com
SCOPE
To provide structural calculations for the foundation and anchorage of a DEF storage tank located in
Tukwila, WA. These calculations consider both wind and seismic loading in addition to the weight of
the tank and contents. Worst case loading is considered for the tank for both full and empty
conditions. The foundation pad is also investigated for soil bearing and global stability (sliding and
overturning). Items specifically excluded include the design of the tank itself.
REFERENCES
1. 2013 Washington State Building Code (WSBC)
2. 2012 International Building Code (IBC)
3. ASCE/SE 7-10, Third Edition "Minimum Design Loads for Buildings and Other Structures" (ASCE)
4. 2011 Building Code Requirements for Structural Concrete, ACI 318-11
ASSUMPTIONS
Per ASCE 7-10 section 15.7.6.1, the tank and contents have been assumed to be a "rigid mass
system" and base shear and overturning are calculated per ASCE 7-10 Section 15.4.2.
TABLE OF CONTENTS
Scope 1
References 1
Assumptions 1
Table of Contents 1
Site Plan and Elevation 2
Tank Information 3
Load Generation 5
Wind Loads 6
Seismic Loads 8
Load Combinations 11
Anchor Demand and Design 12
Slab Reinforcing 12
Foundation Check 13
Appendix A — Anchorage Calcs 15
Peterson Structural Engineers, Inc.
www.psengineers. corn
Portland Office
5319 SW Westgate Drive Suite215
Portland, Oregon 97221
Tacoma Office
708 Broadway Suite 110
Tacoma, Washington
Project: 16-025 Date
04/06/16
Calc. by HSN Sheet
1 of 15
nag
Peterson Structural Engineers, Inc.
Consulting Structural Engineers
Portland, Oregon • Tacoma, Washington
www.psengineers.corn
SITE PLAN AND ELEVATION
Area Of Work
Sign -
Pole D
(E) Bollards
To Be Removed
aatenite 1
0 ® ❑
Round Cover
Master/Master 7
(N) DEF 1,000 GAL. TANK
IN) 1,000 GALLON 'DEE" TANK
FILL -
-
(N)BOLLARD -
~Canopy 8 Concrete
Drive Pad Outline
~8" Sch. 40 Steel
Pipe Bollard
f TYP•)
Card
Reader
Figure 1 — Partial Site Plan
J
L
(E)DRAINAGE SWALE -
Figure 2 — Site Elevation
Raised Concrete
island (Typ.)
- (N) "DEF" DISPIENSER
Peterson Structural Engineers, Inc.
www.psengineers.com
Portland Office
5319 SW Westgate Drive Suite215
Portland, Oregon 97221
Tacoma Office
708 Broadway Suite 110
Tacoma, Washington
Project: 16-025 Date
04/06/16
Calc. by HSN Sheet
2 of 15
SSE
Peterson Structural Engineers, Inc..
Consulting Structural Engineers
Portland, Oregon • Tacoma, Washington
www.psengineers.com
TANK INFORMATION
Tank Info
item
value
comments
width
41 inch
at base (per wind calc)
length
120 inch
tank length (filled portion)
height
101 inch
excludes lid height
weight (empty)
1,950 lbs
tank only
weight (empty w/ dispenser)
2,400 lbs
tank and dispenser
weight (full w/ dispenser)
12,137 lbs
full tank and dispenser
base area
34 sf
base area (length x width)
profile area (wind)
85 sf
broad side of tank
0.9D
1,755 lbs
0.9 x tank only weight
1.2D
14,565 lbs
1.2 * tank, dispenser & contents
A
1li
Minium
I
II
-1-f
_
_+Ljl-
—I
-
i`
106
_.
Li
-
,
r ,
Figure 3 – Tank Elevation
Peterson Structural Engineers, Inc.
www.psengineers.corn
Portland Office
5319 SW Westgate Drive Suite215
Portland, Oregon 97221
Tacoma Office
708 Broadway Suite 110
Tacoma, Washington
Project: 16-025 Date
04/06/16
Calc. by HSN Sheet
3 of 15
SSE
Peterson Structural Engineers, Inc.
Consulting Structural Engineers
Portland, Oregon • Tacoma, Washington
www.psengineers.com
Peterson Structural Engineers, Inc.
www.psengineers.com
Portland Office
5319 SW Westgate Drive Suite215
Portland, Oregon 97221
Tacoma Office
708 Broadway Suite 110
Tacoma, Washington
Project: 16-025 Date
04/06/16
Calc. by HSN Sheet
4 of 15
Peterson Structural Engineers, Inc.
Consulting Structural Engineers
Portland, Oregon • Tacoma, Washington
www.psengineers.corn
LOAD GENERATION
Peterson Structural Engineers, Inc.
www.psengineers.com
Portland Office
5319 SW Westgate Drive Suite215
Portland, Oregon 97221
Tacoma Office
708 Broadway Suite 110
Tacoma, Washington
Project: 16-025 Date
04/06/16
Calc. by HSN Sheet
5 of 15
SSE
Peterson Structural Engineers, Inc.
Consulting Structural Engineers
Portland, Oregon • Tacoma, Washington
www.psengineers.corn
WIND LOADS
Wind Loadin: Summa
item
value
comments
Risk Category
II --
Basic Wind Speed, V
120 mph
conservatively use 120 mph
Exposure Category
C --
open terrain, scattered obstructions
Velocity Pressure Exposure Coeff., K,
0.85 --
ASCE 7-10 Table 29.3-1
Topographic Factor, KE
1.00 --
ASCE 7-10 Section 26.8.2
Wind Directionality Factor., Kd
0.90 --
ASCE 7-10 Table 26.6-1
Wind Velocity Pressure, q,
29 psf
ASCE 7-10 Eqn. 29.3-1
Gust Effect Factor, G
0.85 --
ASCE 7-10 Section 26.9.1
Force Coefficient, Cf
1.4 --
ASCE 7-10 Figure 26.5-1
Wind Pressure (calculated)
35 psf
ASCE 7-10 Eqn. 29.5-1
Wind Pressure (minimum)
50 psf
minimum to use per client
Wind Pressure (used)
50 psf
maximum of two values above
Wind Pressure Area
85 sf
broad side of tank
Wind Force (calculated)
4.25 kip
wind force on tank
height to centroid
50.5 inch
one half tank height
overturning moment
215 kip -in
overturning moment
moment arm
41 inch
tank width at base
total shear due to wind, Vw
4.250 kip
horizontal wind force
total uplift due to wind, Tw
5.244 kip
de -coupled overturning moment
I
--"
h/2
/
1ti"iki
h/2
L
°`G
OVERTURNING
i
I
/
OVERTURNING i OVERTURNING
TENSION COMPRESSION
X width X
Figure 5 —Wind Overturning
p
Peterson Structural Engineers, Inc.
www.psengineers.com
Portland Office
5319 SW Westgate Drive Suite215
Portland, Oregon 97221
Tacoma Office
708 Broadway Suite 110
Tacoma, Washington
Project: 16-025 Date
04/06/16
Calc. by HSN Sheet
6 of 15
SSE
Peterson Structural Engineers, Inc.
Consulting Structural Engineers
Portland, Oregon • Tacoma, Washington
www.psengineers.com
Search Results
Query Data: Tun Feb 16 2016
Latitude: 47.4825
Longitude: -12124)92
ASCE 7-10 Windspeede
j3-ssc peak gust in mphi:
Risk Category I: 103
Risk Category IL 11 1)
RISK Category 111-IY: 115
MRI" 10 -Year. 72
MR1•• 25 -Year. 79
MRI" 60 -Year. 665
MRI"' td0-Year: 91
ASCE 7-05 WI Mspeed:
95 (3 -sec peek twat t rnlh)
ASCE 743 Windspeed.
Ta (fastest mie in inch)
'tI*..S t-+ Y,R.
t J Pnnt your rlsldlss,
.I /NDSP ED B t CATION
WINDSPEED WEBSITE DISCLAIMER
Wilde The irrormetron presersed at this weesite is belie -.ed lo be cared ATC and its sporsors and conerib tors
assune ro respor:ubrity re Isabhly far its auxlrar_y Thr, netcrwl prascrted in tiro wirdspraa report stolid not
to ti t.i or IVO sip7r for &sny anpwrtitirn utlh7;11 .nr-np?tQn; €., rniratirn and ,:enlicWoon of =K
ertur9rysufabriltr enc eppolr abilft by or.3rn«ers or other IICr•n5._v1 eroressimal6 ATC aces not :mend lyfy? elle
ude of Mie iniarrna utr replace the sound itdgl•eirl ut esr'h L'.i i etert C.otesobele, hereto euiefience one
krowlet ge in the field oA Ie -hen_ nor lu sJbstilule for Cite slandard of care required of such psofessionela
interpreting and applying tne resells r/ tie wirdspenn report provided ay Nos website. risers of the ir<ortnetor
from this wotisile assume all Icabtity arising (rum :such 144 Lse of tho o.11pl rf this wabsilc dotes nal imply
approval by the g w r-iir. biulr1inlg rr4iis horses ntspInsit a for hl,iIcmg node appro.:al aryl inlerpreidtion for the
Ixitdirg sl19 describe° Iv, Iatittrdarlarftude Ipcetor n the wrrdsDced loan Mp r1
A :: ]:loboor.oef 1.:RD.• hositsaitykaisaramast IlsffAe,.xf :i-,ie/'k 4"A. w,,,' I,lr 7,4n.4K-M'wYA CC, IY:':a11i ,,. 94nr,i"1,i4i: 291.1!44,
Peterson Structural Engineers, Inc.
www.psengineers.com
Portland Office
5319 SW Westgate Drive Suite215
Portland, Oregon 97221
Tacoma Office
708 Broadway Suite 110
Tacoma, Washington
Project: 16-025 Date
04/06/16
Calc. by HSN Sheet
7 of 15
SSE
Peterson Structural Engineers, Inc.
Consulting Structural Engineers
Portland, Oregon • Tacoma, Washington
www.psengineers.corn
SEISMIC LOADS
See below for seismic load generation per ASCE 7-10.
Seismic Loadin: Summa
item
value
comments
Risk Category
II --
ASCE 7-10 Table 1.5-1
Seismic Importance Factor, le
1.00 --
ASCE 7-10 Table 1.5-2
Site Class
D
default site class
short period spectral accel., Ss
1.487 g
USGS Seismic Design Map
1 -sec period spectral accel., Si
0.557 g
USGS Seismic Design Map
short period site coeff., Fa
1 -sec peroid site coeff., F"
site short period accel., Sms
site 1 -second period accel., Sml
short period design accel., Sds
1.00 --
1.50 --
1.487 g
0.835 g
0.991 g
ASCE 7-10 Table 11.4-1
ASCE 7-10 Table 11.4-2
ASCE 7-10 Eqn. 11.4-1
ASCE 7-10 Eqn. 11.4-2
ASCE 7-10 Eqn. 11.4-3
1 -sec period design accel., Shc
0.557 g
ASCE 7-10 Eqn. 11.4-4
Seismic Design Category (SDC)
D --
ASCE 7-10 Table 11.6-1 & 2
period coefficient, Ct
0.02 --
ASCE 7-10 Table 12.8-2
structural height, hn
period parameter, x
8.42 --
0.75 --
per product specs
ASCE 7-10 Table 12.8-2
Approximate Period, Ta
0.099 sec
ASCE 7-10 Eqn. 12.8-7
response modification factor, R
3 --
ASCE 7-10 Table 15.4-2
seismic overstrength, flo
2 --
ASCE 7-10 Table 15.4-2
deflection amplification factor, Cd
2.5 --
ASCE 7-10 Table 15.4-2
seismic response coeff., C,
0.331 g
ASCE 7-10 Eqn. 12.8-2
seismic response coeff., Cs
0.298 g
ASCE 7-10 Eqn. 15.4-5
seismic response coeff., C, max
1.875 g
ASCE 7-10 Eqn. 12.8-3
seismic response coeff., C,,min
0.044 g
ASCE 7-10 Eqn. 12.8-5
USED seismic response coeff., C,
0.331 g
--
weight (empty)
1,950 lbs
tank only
_ Vbase, empty tank
weight (full w/ dispenser)_
0.646 kip
12,137 Ibs
min base shear, ASCE 7-10 Eqn. 12.8-1
full tank and dispenser
Vbase, full tank
4.018 kip
max base shear, ASCE 7-10 Eqn. 12.8-1
height to centroid
50.5 inch
one half tank height
_ Mot, empty tank
Mot, full tank
33 kip -in
203 kip -in
overturning moment
overturning moment
moment arm at base
41 inch
tank width at base
seismic base shear (empty), Vs,e
0.646 kip
seismic horizontal force
seismic base shear (full), Vs,f
4.018 kip
seismic horizontal force
seismic uplift (empty), Ts,e
0.805 kip
decoupled overturning uplift
seismic uplift (full), Ts,f
4.952 kip
_
decoupled overturning uplift
Peterson Structural Engineers, Inc.
www.psengineers.com
Portland Office
5319 SW Westgate Drive Suite215
Portland, Oregon 97221
Tacoma Office
708 Broadway Suite 110
Tacoma, Washington
Project: 16-025 Date
04/06/16
Calc. by HSN Sheet
8 of 15
LP5E
Peterson Structural Engineers, Inc.
Consulting Structural Engineers
Portland, Oregon • Tacoma, Washington
WWW.psengineers.com
Peterson Structural Engineers, Inc.
www.psengineers.com
Portland Office
5319 SW Westgate Drive Suite215
Portland, Oregon 97221
Tacoma Office
708 Broadway Suite 110
Tacoma, Washington
Project: 16-025 Date
04/06/16
Calc. by HSN Sheet
9 of 15
Seismic Loadin; Summa - Vertical Corn onent
item
value
comments
short period design accel., Sds
0.991 g
ASCE 7-10 Eqn. 11.4-3
weight (empty)
1,950 lbs
tank only
weight (full w/ dispenser)
12,137 lbs
full tank and dispenser
Tank Empty - min
dead load factor (EQ)
0.701
0.9-0.2*Sds
factored tank weight
1366 lbs
Tank Empty - max
dead load factor (EQ)
1.398
1.2+0.2*Sds
factored tank weight
2727 lbs
Tank Full - min
dead load factor (EQ)
0.701
0.9-0.2*Sds
factored tank weight
8508 lbs
Tank Full - max
dead load factor (EQ)
1.398
1.2+0.2*Sds
factored tank weight
16967 lbs
h/2
X
IV.11'•dllK(
-
h/2
IJ ill.
1
OVERTURNING
OVERTURNING OVERTURNING
TENSION COMPRESSION
X width X
Figure 6 — Wind Overturning
Peterson Structural Engineers, Inc.
www.psengineers.com
Portland Office
5319 SW Westgate Drive Suite215
Portland, Oregon 97221
Tacoma Office
708 Broadway Suite 110
Tacoma, Washington
Project: 16-025 Date
04/06/16
Calc. by HSN Sheet
9 of 15
SSE
Peterson Structural Engineers, Inc.
Consulting Structural Engineers
Portland, Oregon • Tacoma, Washington
www.psengineers.com
USGS Design Maps Summary Report
User -Specified input
Report Title laksi i ' f 1i.5to'
Building Code Reference Document 231? Ir:ernntiona Bu Ie rc Code
Site Coordinates 47.48252°N, 122 26909°W
Site Soil Classification S to C' ass D - "Stiff So
Risk Category 1/11/11[
Vashoft
Bur ien.
DH, Moine
USGS-Provided Output
Ss= 1 487 g
S1 = 0 557 g
S45= 1.487g
5,,, = 0.835 y
,nett
€a.
(5$aqual'1
Renton
Maple Valley
S5 = 0.991 g
Ss = 0 5 5 7 g
F
•H0
ru- n'aln;dib.0 air'o'n the; S5 ear ti Si Maur., ewv- htv, b._• c4 c_Inl-9' uir, pruLcsrl •.t5..-teroet-7i end
ce'erm•n 5Dc 2ro.n6 m .tr.ns r• the lrrec o^ 0' '-rtm.m r0- conral •Pie '"!c. DICOs- rntu'r t9 v'
It1,1 "2.79 NE -PP' Su, d nU cads: rele•,ai.e. dor...nr• It.
MCER Response Spectrum
Design Response Spectrum
I I- ,.1
♦.
a /A, 'S IV' 1`" 1? 111 1t" IT, I -
Period, t (sad
del r) • /' ' CS 1 r- Ill 1 4 114 1 t 2 ""
Period, T {mei
Peterson Structural Engineers, Inc.
www.psengineers.com
Portland Office
5319 SW Westgate Drive Suite215
Portland, Oregon 97221
Tacoma Office
708 Broadway Suite 110
Tacoma, Washington
Project: 16-025 Date
04/06/16
Calc. by HSN Sheet
10 of 15
SSE
Peterson Structural Engineers, Inc.
Consulting Structural Engineers
Portland, Oregon • Tacoma, Washington
www.psengineers.com
LOAD COMBINATIONS
2.3.2. Consider wind and seismic loading for
of tank, uplift will control. Note that bearing
Identify controlling load combinations per ASCE 7-10 Section
both an empty and a full tank. Evaluate demand per side
pressures are less than 1,000psf.
Load Combination Ana sis
item
value
comments
Load Combo A - empty + wind (0.9D + 1.0W)
0.9 D (total)
1.755 kip
factored vertical load
0.9 D (half)
0.877 kip
1/2 factored vertical load
1.0 W (shear)
4.250 kip
factored wind load shear
1.0 W (uplift)
5.244 kip
factored wind load uplift
net uplift/side
4.367 kip
factored net uplift
net shear/side
2.125 kip
1/2 shear demand
Load Combo B - full + wind (1.2D + 1.0W)
1.2 D (total)
14.565 kip
factored vertical load
1.2 D (half)
7.282 kip
1/2 factored vertical load
1.0 W (shear)
4.250 kip
factored wind load shear
1.0 W (uplift)
5.244 kip
factored wind load uplift
net uplift/side
NO UPLIFT kip
factored net uplift
net shear/side
2.125 kip
1/2 shear demand
Load Combo C - empty + EQ (0.9-0.2*Sds) + 2.0EQ)
(0.9-0.2*Sds)D (total)
1.366 kip
factored vertical load
(0.9-0.2*Sds)D (half)
0.683 kip
1/2 factored vertical load
seismic overstrength, C2o
2 --
ASCE 7-10 Table 15.4-2
2.0 EQ (shear)
1.292 kip
EQ shear w/ overstrength
2.0 W (uplift)
1.610 kip
EQ uplift w/ overstrength
net uplift/side
0.927 kip
factored net uplift
net shear/side
0.646 kip
1/2 shear demand
Load Combo D - full + EQ (1.2+0.2*Sds) + 2.0EQ)
(1.2+0.2*Sds)D (total)
16.967 kip
factored vertical load
(1.2+0.2*Sds)D (half)
8.483 kip
1/2 factored vertical load
seismic overstrength, Qo
2 --
ASCE 7-10 Table 15.4-2
2.0 EQ (shear)
8.036 kip
EQ shear w/ overstrength
2.0 W (uplift)
9.904 kip
EQ uplift w/ overstrength
net uplift/side
1.421 kip
factored net uplift
net shear/side
4.018 kip
1/2 shear demand
Peterson Structural Engineers, Inc.
www.psengineers.com
Portland Office
5319 SW Westgate Drive Suite215
Portland, Oregon 97221
Tacoma Office
708 Broadway Suite 110
Tacoma, Washington
Project: 16-025 Date
04/06/16
Calc. by HSN Sheet
11 of 15
SSE
Peterson Structural Engineers, Inc.
Consulting Structural Engineers
Portland, Oregon • Tacoma, Washington
www.psengineers.com
ANCHOR DEMAND AND DESIGN
Anchor Demand
Calculate anchor demand and identify worst case loading.
The above table demonstrates that load combination A and D control design. These combos correspond to
• Combo A - empty tank under wind loads for max uplift
• Combo D — full tank under EQ loads for max shear
For design demand use 550 lbs. shear in both directions and 550 lbs. uplift. Include edge distance checks.
Anchor Design
See appendix A for anchorage design.
Use 3/8" diameter Stainless Steel Hilti Kwik Bolk TZ w/ 2" embedment and 4" edge distance in all
directions.minimum f c=2,500psi.
SLAB REINFORCING
Existing slab is assumed to meet the minimum requirements for anchorage.
Peterson Structural Engineers, Inc.
www.psengineers.com
Portland Office
5319 SW Westgate Drive Suite2l5
Portland, Oregon 97221
Tacoma Office
708 Broadway Suite 110
Tacoma, Washington
Project: 16-025 Date
04/06/16
Calc. by HSN Sheet
12 of 15
A c o a• e Deman s
item
value
comments
# anchors/side
8 --
anchors per side
Load Combo A- tension/anchor
546 lb
tension load per anchor
Load Combo A - shear/anchor
266 lb
shear load per anchor
Load Combo B - tension/anchor
0 lb
tension load per anchor
Load Combo B - shear/anchor
266 lb
shear load per anchor
Load Combo C - tension/anchor
116 lb
tension load per anchor
Load Combo C - shear/anchor
81 lb
shear load per anchor
Load Combo D - tension/anchor
178 lb
tension load per anchor
Load Combo D- shear/anchor
503 lb
shear load per anchor
The above table demonstrates that load combination A and D control design. These combos correspond to
• Combo A - empty tank under wind loads for max uplift
• Combo D — full tank under EQ loads for max shear
For design demand use 550 lbs. shear in both directions and 550 lbs. uplift. Include edge distance checks.
Anchor Design
See appendix A for anchorage design.
Use 3/8" diameter Stainless Steel Hilti Kwik Bolk TZ w/ 2" embedment and 4" edge distance in all
directions.minimum f c=2,500psi.
SLAB REINFORCING
Existing slab is assumed to meet the minimum requirements for anchorage.
Peterson Structural Engineers, Inc.
www.psengineers.com
Portland Office
5319 SW Westgate Drive Suite2l5
Portland, Oregon 97221
Tacoma Office
708 Broadway Suite 110
Tacoma, Washington
Project: 16-025 Date
04/06/16
Calc. by HSN Sheet
12 of 15
SSE
Peterson Structural Engineers, Inc.
Consulting Structural Engineers
Portland, Oregon • Tacoma, Washington
WWW.psengineers.cotn
FOUNDATION CHECK
item value
comments
Concrete Pad Info
foundation width 7
ft
min concrete width
foundation length 20
ft
conservative, actual is longer
foundation area 140
sf
conservative foundation area
slab thickness 8
inc
h
concrete slab thickness
concrete unit weight 150
pcf
reinforced concrete
concrete area load 100
psf
wt. concrete/sf
total weight of concrete pad 14000
lbs
weight of concrete pad
Static Bearing
max wt of unit 12,137
lbs
full tank + control
bearing pressure from unit 87
psf
tank weight/slab area
concrete slab 100
psf
slab area load
total bearing stress 187
psf
static bearing pressure
allowable bearing stress 1500
psf
code prescribed minimum allowable bearing
static bearing okay? okay
Sliding Check - empty tank + wind (combo A)
empty tank weight + dispenser 2400
lbs
min tank weight (service)
pad weight 14000
lbs
concrete pad weight (service)
total weight of pad + empty tank 16400
lbs
total weight
coefficient of friction 0.35
assumed coefficient of friction
sliding resistance 5740
lbs
resistance to sliding (friction only)
sliding demand 2975
lbs
driving demand (wind)
sliding okay? okay
resistance > demand?
Overturning Check - empty tank + wind (combo A)
empty tank weight + dispenser 2400
lbs
min tank weight (service)
pad weight 14000
lbs
concrete pad weight (service)
total weight of pad + empty tank, P 16400
lbs
total weight
overturning moment, M 12584
Ib -
ft
overturning moment due to wind
eccentricity, e 0.768
ft
moment eccentricity, M/P
foundation length, L 20
ft
length of foundation
foundation width, W 7
ft
width of foundation (direction of loading)
pad area 140
sf
pad area (L*W)
kern dimension, W/6 1.167
ft
eccentricity w/in kern = no net uplift
Peterson Structural Engineers, Inc.
www.psengineers.com
Portland Office
5319 SW Westgate Drive Suite2l5
Portland, Oregon 97221
Tacoma Office
708 Broadway Suite 110
Tacoma, Washington
Project: 16-025 Date
04/06/16
Calc. by HSN Sheet
13 of 15
SSE
Peterson Structural Engineers, Inc.
Consulting Structural Engineers
Portland, Oregon • Tacoma, Washington
www.psengineers.com
resultant w/in kern?
YES
eccentricity w/in kern?
max bearing pressure
195
psf
max pressure at footing edge
min bearing pressure
41
psf
min pressure at footing edge
bearing pressure okay? okay
bearing less than allowable?
Sliding Check- full tank + wind (combo D)
full tank + dispenser
12137
lbs
max tank weight (service)
pad weight
14000
lbs
concrete pad weight (service)
total weight of pad + empty tank
26137
lbs
total weight
coefficient of friction
0.35
assumed coefficient of friction
sliding resistance
9148
lbs
resistance to sliding (friction only)
sliding demand
4018
lbs
driving demand (EQ)
sliding okay? okay
resistance > demand?
Overturning Check - empty tank + wind (combo A)
full tank weight + dispenser
12137
lbs
max tank weight (service)
pad weight
14000
lbs
concrete pad weight (service)
total weight of pad + empty tank, P
26137
lbs
total weight
overturning moment, M
16917
Ib -
ft
overturning moment due to EQ
eccentricity, e
0.648
ft
moment eccentricity, M/P
foundation length, L
20
ft
length of foundation
foundation width, W
7
ft
width of foundation (direction of loading)
pad area
140
sf
pad area (L*W)
kern dimension, W/6
1.167
ft
eccentricity w/in kern = no net uplift
resultant w/in kern?
YES
eccentricity w/in kern?
max bearing pressure
291
psf
max pressure at footing edge
min bearing pressure
83
psf
min pressure at footing edge
bearing pressure okay? okay
bearing less than allowable?
Peterson Structural Engineers, Inc.
www.psengineers.com
Portland Office
5319 SW Westgate Drive Suite215
Portland, Oregon 97221
Tacoma Office
708 Broadway Suite 110
Tacoma, Washington
Project: 16-025 Date
04/06/16
Calc. by HSN Sheet
14 of 15
SSE
Peterson Structural Engineers, Inc.
Consulting Structural Engineers
Portland, Oregon • Tacoma, Washington
www.psengineers.com
APPENDIX A — ANCHORAGE CALCS
Peterson Structural Engineers, Inc.
www.psengineers.com
Portland Office
5319 SW Westgate Drive Suite215
Portland, Oregon 97221
Tacoma Office
708 Broadway Suite 110
Tacoma, Washington
Project: 16-025 Date
04/06/16
Calc. by HSN Sheet
15 of 15
www.hilti.us
Profis Anchor 2.6.3
Company:
Specifier:
Address:
Phone I Fax:
E -Mail:
Page:
Project:
Sub -Project I Pos. No.:
Date:
1
2/24/16
Specifier's comments:
1 Input data
01
Anchor type and diameter: Kwik Bolt TZ - SS 316 3/8 (2)„_�
Effective embedment depth: hef,act = 2.000 in., hno = 2.313 in.
Material: AISI 316
Evaluation Service Report: ESR -1917
Issued I Valid: 10/1/151 5/1/17
Proof: Design method ACI 318-11 / Mech.
Stand-off installation: - (Recommended plate thickness: not calculated)
Profile: no profile
Base material: cracked concrete, 2500, f: = 2500 psi; h = 8.000 in.
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present
edge reinforcement: none or < No. 4 bar
Seismic loads (cat. C, D, E, or F) Tension load: yes (D.3.3.4.3 (d))
Shear load: yes (D.3.3.5.3 (c))
Geometry [in.] & Loading [Ib, in.lb]
vi
ult0
sso
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL -9494 Schaan Hilti Is a registered Trademark of Hilti AG, Schaan
www.hilti.us
1■■III�TI
Profis Anchor 2.6.3
Company:
Specifier:
Address:
Phone I Fax:
E -Mail:
Page:
Project:
Sub -Project I Pos. No.:
Date:
2
2/24/16
2 Load case/Resulting anchor forces
Load case: Design loads
Anchor reactions [lb]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 550 778 550 550
max. concrete compressive strain: - [%e]
max. concrete compressive stress: - [psi]
resulting tension force in (x/y)=(0.000/0.000): 0 [Ib]
resulting compression force in (x/y)=(0.000/0.000): 0 [Ib]
3 Tension load
Load Nua [Ib] Capacity 4Na [Ib] Utilization ON = Nua/4N. Status
Steel Strength* 550 4476 13 OK
Pullout Strength* 550 1141 49 OK
Concrete Breakout Strength** 550 1172 47 OK
* anchor having the highest loading **anchor group (anchors in tension)
3.1 Steel Strength
Nsa = ESR value
Nsa aka
Variables
Aso' [In 2]
refer to ICC -ES ESR -1917
ACI 318-11 Table D.4.1.1
futa [psi]
0.05
Calculations
Nsa [Ib]
5968
Results
Nsa [lb]
5968
115000
3.2 Pullout Strength
Npn,f = Np,2500 %a
Npn.(< — Nua
Variables
( [psi]
fe
2500
4steel
0.750
xa
4nonductile
1.000
refer to ICC -ES ESR -1917
ACI 318-11 Table D.4.1.1
2500
Calculations
2500
1.000
Results
Nan.f, [Ib]
2340
1.000
4>concrete
0.650
Np2500 [lb]
2340
4seismic
0.750
(0 Nsa [Ib] Nua [Ib]
4476 550
4nonductile
1.000
4, Non.G [Ib] Nua [lb]
1141 550
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL -9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us
1�■11`T1
Profis Anchor 2.6.3
Company:
Specifier:
Address:
Phone I Fax:
E -Mail:
Page:
Project:
Sub -Project I Pos. No.:
Date:
3
2/24/16
3.3 Concrete Breakout Strength
ANc
Ncb —
(ANco) Wed,N 4fc.N'1cp.N Nb
4, Nth Z Nua
AN, see ACI 318-11, Part D.5.2.1, Fig. RD.5.2.1(b)
ANco = 9 her
i 1 �
111ec,N = 1 + 2 eN <_ 1.0
3 het
Wed,N=0.7+O.3(Ca,min)c1.0
`1.5hef
tVcp.N = MAX(Ca=min 1.5hatl < 1.0
Cac Cane
an /
Nb=kcXoJhei5
ACI 318-11 Eq. (D-3)
ACI 318-11 Table D.4.1.1
ACI 318-11 Eq. (D-5)
ACI 318-11 Eq. (D-8)
ACI 318-11 Eq. (D-10)
ACI 318-11 Eq. (D-12)
ACI 318-11 Eq. (D-6)
Variables
het [in.] ec1,N [in -1 ec2,N [in.] Ca,min [in.]
2.000 0.000 0.000 4.000
Cac [in.] kc a.a fc [psi]
3.875 17 1.000 2500
Calculations
ANc
[in.2]
36.00
Results
Nth [Ib]
2404
Awn [in.2]
36.00
4)concrete
0.650
Wc,N
1.000
Wecl,N Wec2.N Wed,N Wcp,N
1.000 1.000 1.000 1.000
Nb [Ib]
seismic 4nonduclile 4, Ncb [Ib] Nua [Ib]
0.750 1.000 1172 550
2404
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL -9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us
i�111�T1
Profis Anchor 2.6.3
Company:
Specifier:
Address:
Phone I Fax:
E -Mail:
Page:
Project:
Sub -Project I Pos. No.:
Date:
4
2/24/16
4 Shear load
Load Vua [Ib] Capacity +Vn [Ib] Utilization Dv = Vua/4Vn Status
Steel Strength* 778 1836 43 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 778 1683 47 OK
Concrete edge failure in direction x+** 778 1258 62 OK
* anchor having the highest loading **anchor group (relevant anchors)
4.1 Steel Strength
Vsa,eq = ESR value
4 Vsteel Z Vua
Variables
Ase,v [in.2]
0.05
Calculations
Vsa,eq [lb]
2825
Results
Vsa.eq [Ib]
2825
refer to ICC -ES ESR -1917
ACI 318-11 Table D.4.1.1
fut. [psi]
115000
+steel
0.650
4tnonductile
1.000
4.2 Pryout Strength
Ir P`Nc 11
vep – kg, L�ANcO� Wed.N 'lIc,N 4lcp,N Nb]
4 Vcp � Vua J
ANC see ACI 318-11, Part D.5.2.1, Fig. RD.5.2.1(b)
ANco = 9 hef
1
tiec,N = 1 + 2 eN <_ 1.0
3 her
WedN =0.7+0.3 (Ca,min) 5 1.0
`1.5hef
Wcp,N = MAX Ca—min 1.5hef a 1.0
� �Cec Cac
Nb = kc %a VTc hei5
Variables
kcp
1
hef [in.]
ec1,N [in.]
(I) Vsa [Ib] Vua [Ib]
1836 778
ACI 318-11 Eq. (D-40)
ACI 318-11 Table D.4.1.1
ACI 318-11 Eq. (D-5)
ACI 318-11 Eq. (D-8)
ACI 318-11 Eq. (D-10)
ACI 318-11 Eq. (D-12)
ACI 318-11 Eq. (D-6)
ec2.N [in.]
Ca,min [in.]
2.000
0.000
Wc,N Cac [in.] kC
1.000 3.875 17
Calculations
ANc [in.2l
36.00
Results
VCp [Ib]
2404
0.000
1.000
ANc0 [In?] t]ecl,N Wec2,N
36.00 1.000 1.000
4.000
fC [psi]
2500
+concrete +seismic 4nonductile
0.700 1.000 1.000
WedN Wcp,N
1.000 1.000
Nb [Ib]
Vcr, [Ib] yea [Ib]
1683 778
2404
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL -9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us
1■�11`TI
Profis Anchor 2.6.3
Company:
Specifier:
Address:
Phone I Fax:
E -Mail:
Page:
Project:
Sub -Project I Pos. No.:
Date:
5
2/24/16
4.3 Concrete edge failure in direction x+
Vcb — (ZA / lJed,V wc,V yJh,V yJparallel,V Vb
4)Vc,ZVua
Avc see ACI 318-11, Part D.6.2.1, Fig. RD.6.2.1(b)
Avco = 4.5 Ca,
i 1 �
'Vec,V = 1 + 2e„ 5. 1.0
3;1 l
y<ed,V = 0.7 + 0.3
(1 5ca1) < 1.0
= 1.5Ca1Z1.0
ha
/ 0.2
_ (7 1 Ic) Yc7a� a.a yTc cai
a
wh,V
Vb
ACI 318-11 Eq. (D-30)
ACI 318-11 Table D.4.1.1
ACI 318-11 Eq. (D-32)
ACI 318-11 Eq. (D-36)
ACI 318-11 Eq. (D-38)
ACI 318-11 Eq. (D-39)
ACI 318-11 Eq. (D-33)
Variables
ca, [in.] ca2 [in.] ecv [in.] wc,V
4.000 4.000 0.000 1.000
ha [in.]
le [in.] Xa da [in.] fc [psi]
2.000 1.000 0.375 2500
Calculations
Avc [in 2]
60.00
Results
Vo [lb]
1797
8.000
yfparallel,V
1.000
Avco [in•21 yrec,V Wed,V yrh,V Vb [lb]
72.00 1.000 0.900 1.000 2396
4)concrete 4lseismic 4Inonductile 4) Vcb [lb] Vua [lb]
0.700 1.000 1.000 1258 778
5 Combined tension and shear loads
13N (3v K Utilization (3N,v [%] Status
0.482 0.618 5/3 75 OK
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL -9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us
14Hair I
Profis Anchor 2.6.3
Company:
Specifier:
Address:
Phone I Fax:
E -Mail:
Page:
Project:
Sub -Project I Pos. No.:
Date:
6
2/24/16
6 Warnings
• Load re -distributions on the anchors due to elastic deformations of the anchor plate are not considered. The anchor plate is assumed to be
sufficiently stiff, in order not to be deformed when subjected to the loading! Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• Condition A applies when supplementary reinforcement is used. Them factor is increased for non -steel Design Strengths except Pullout Strength
and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout Strength. Refer to
your local standard.
• Refer to the manufacturer's product literature for cleaning and installation instructions.
• Checking the transfer of loads into the base material and the shear resistance are required in accordance with ACI 318 or the relevant standard!
• An anchor design approach for structures assigned to Seismic Design Category C, D, E or F is given in ACI 318-11 Appendix D, Part D.3.3.4.3
(a) that requires the governing design strength of an anchor or group of anchors be limited by ductile steel failure. If this is NOT the case, the
connection design (tension) shall satisfy the provisions of Part D.3.3.4.3 (b), Part D.3.3.4.3 (c), or Part D.3.3.4.3 (d). The connection design
(shear) shall satisfy the provisions of Part D.3.3.5.3 (a), Part D.3.3.5.3 (b), or Part D.3.3.5.3 (c).
• Part D.3.3.4.3 (b) / part D.3.3.5.3 (a) require the attachment the anchors are connecting to the structure be designed to undergo ductile yielding
at a load level corresponding to anchor forces no greater than the controlling design strength. Part D.3.3.4.3 (c) / part D.3.3.5.3 (b) waive the
ductility requirements and require the anchors to be designed for the maximum tension / shear that can be transmitted to the anchors by a
non -yielding attachment. Part D.3.3.4.3 (d) / part D.3.3.5.3 (c) waive the ductility requirements and require the design strength of the anchors to
equal or exceed the maximum tension / shear obtained from design load combinations that include E, with E increased by no.
Hilti post -installed anchors shall be installed in accordance with the Hilti Manufacturer's Printed Installation Instructions (MPII). Reference ACI
318-11, Part D.9.1
Fastening meets the design criteria!
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL -9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us
Profis Anchor 2.6.3
Company:
Specifier:
Address:
Phone I Fax:
E -Mail:
Page:
Project:
Sub -Project 1 Pos. No.:
Date:
7
2/24/16
7 Installation data
Anchor plate, steel: -
Profile: -
Hole diameter in the fixture: -
Plate thickness (input): -
Recommended plate thickness: -
Drilling method: Hammer drilled
Cleaning: Manual cleaning of the
7.1 Recommended accessories
Anchor type and diameter: Kwik Bolt TZ - SS 316 3/8 (2)
Installation torque: 300.000 in.lb
Hole diameter in the base material: 0.375 in.
Hole depth in the base material: 2.625 in.
Minimum thickness of the base material: 5.000 in.
drilled hole according to instructions for use is required,
Drilling Cleaning
Setting
• Suitable Rotary Hammer • Manual blow-out pump • Torque wrench
• Properly sized drill bit • Hammer
Coordinates Anchor in.
Anchor x
y
c.x
1 0.000 0.000
C+x
4.000
c -y
C*y
4.000
8 Remarks; Your Cooperation Duties
Any and all information and data contained in the Software concem solely the use of Hilti products and are based on the principles, formulas and
security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly
complied with by the user. All figures contained therein are average figures, and therefore use -specific tests are to be conducted prior to using
the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in.
Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you.
Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to
compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms
and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific
application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the
regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use
the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each case
by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or
programs, arising from a culpable breach of duty by you.
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL -9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
1 r
I QQ QQ ai ,n, -n ;}Uen , 5,}rpi_,.r;,A 7r r QQ -:orp-1.9mt.o:ou p!)
Interurban Ave. S.
i..---
Driveway \ Driveway
Sidewalk
Sidewalk
—
—Landscape
Sidewalk
I--
1
\------ -----
\ � 1
\\
PetroCard "Tukwila" Pacific Pride
13435 Interburan Ave S.
Tukwila, Washington 98168
ILandscape
1
Reader
Card
Landscape
• '
•
•
(] l] ® D 0 0
Building
I
—•
1
•
Ins
REVIEWED AS NOTED
GALLON
Satellite
P.I.„o, 50.0.1 .an.«e 0c Apr 06 2016 HSN
NEW 1,000
Pole ~a
Peterson Structural Engineers
1
DEF STORAGE TANK
Round Cover
708 Broadway, Suite 100A
Tacoma, WA 98402 (253) 830-2 0
ON EXISTING
CONCRETE SLAB (E) Bollardse
4'."
41:412".• CT' / f!c Se 1
To Removed
Master/Master
--Canopy 8 Concrete
Drive Pad Outline I//e I / t b I �/'� IA/C0 FOR
;c V Y VC
Area Of Work
7
/ 1 + Ai
?C' t. MP A.
4:-'
. E
{- w
A
�8" Sch. 40 Steel � MED
1
(N) DEE 1,000 GAL. TANK
EDCovered
-
Sump Pipe Bollard
(TYP) l ,1 AY ', �;' '
Satellite Pacific Pride b
Satellite Tukwila
1
is Jll• 13435 Interurban Ave. S.
0Ci
•
`Raised Concrete 1
'" I of la
1
Card Island (Typ.) f ¶ U
Reader BUIL'-.,.ING ri A C.�
1 � ''
1
1
Master/Master '
•
1
® 1
•
•
Master '
(Single Sided)
\CIT YO
ILA' Landscape4101
Sa ellite
Landscape '
, APR 2 2 ,
Drawn by. W.D.J. 8
Approved: M.
Issued Date 03/30/16
z,
Q
1
e `- 1
Landscape
ERMI CE
ER
Revisions
Drawing Tale:
Site Plan
13445
PARK
Interurban
I
8 RIDE
Tukwila
I
Ave.
S.
,—.t4
\ /
SCAB _ 10.-0-
DSL
1.0
I
I
I
I
a1-
1 1x17 SETS ARE 50% REDUCTION
Project No:
•
NEW 1,000
DEF
REVIEWED AS NOTED
4rnizi'
Amami
��
ns
(N) 1,000 GALLON "DEF' TANK
!
-
STORAGE TANK
11
(N) "DEF' DISPENSER
1i
�� (E) CANOPY COLUMN
Paterson Structure;�, Apr 06 2016 HSN
Peterson Structural Engineers
708 Broadway, Suite 100A
Tacoma, WA 98402 (2 53) 830-2140
6a•
1(
(E) DISPENSER V
FILL
(N) BOLLARD ���
gig.
I
111111
—
! l
'`�
/(_\.--..
'Iti ito
bb
�� (E) BOLLARD
1d`'
_
T
,u
`v
,
L
L
q
A
ii
0
Ls
u
2.
P
f
::4
.II!
..
■
.
■
II
I I
II
I
I I
LL J�
I)
II
I
I I
(E) DRAINAGE
. _
SWALE
I I
I IV
I I EXISTING ISLAND
L --J L-
(E) UDC
-- J
(E)
I
I
I
I
LL
UDC
I
I
I
J J
PetroCard Tukwila "Pacific Pride"
13435 Interburan Ave S.
Tukwila, Washington 98168
I
SOUTH ELEVATION ( W) SCALE: 1/2" I-0"
DEF TANK
ANCHORS
(16) anchors
total, (8) per side equally space as best possible --V—
Kwik
Bolt TZ - Stainless Steel 316, 3/8" diameter with 2" embedment
�� (E) CANOPY COLUMN
NOTE:
Minimum
Install
edge distance in any direction = 4"
in strict conformance with manufacturer's recommendationsy.
—
SAWCUTAND REMOVE
11" OF EXISTING ISLAND
—(E)DISPENSER
Existing slab is assumed to meet the
minimum requirements for anchorage.
• ,. • • °
REMOVED
(E) COVER PLATES
�.___---- (E) BOLLARD
RECEIVED
iIl r
II
Ill1
17
I
I I
I T 7
I I 0 (1 I (E) ISLAND (l (l
I fi I CITY OF TUKWILA
rl
I I Ic.
'APR
BOLLARDS
BY
(E) DRAINAGE SWALE I
I
OTHERS LL J
I L — — J (E)DRIVE PAD L-- — — J I I
() I
J (E) UDC (E) UDC LL J J
REVIEWED FOR
CODE COMPLIANCE
221016
APPROVED
PERMIT CENTER
2
SO 1 ELEVATION (EXISTING)
mu n 5 7l 1
SCALE: 1/2" = 1'-0"
(N) 8" SCH .40 STEEL PIPE BOLLARD
p (E) CANOPY COLUMN
TYP. OF 2 —-1--1--
TYP.
-J
•
. `kw a
City of 1 MRWiiIQ
Tukwila
v
` • • • 'TANK ,
'-- ^I (E) COVER PLATES
.--IApproved
15, 6"
BUILDING DIVISIO�
T, �"
Drawer by'. W.D.J.
B H.
Issued Data. 03/30/16
CLS
13.
— —
e
, --
•
,...k
--
, -- _ .-. . --�'
• •
=
�i
—
(N) 8" SCH .40 STEEL PIPE BOLLARD
(E) CANOPY COLUMN
Rerlslons
f
Ila
36 MIN. ABOVE GRADE
36 MIN. BELOW GRADE
•� ^
\__11
I II
I
IDraw;ay
EXISTING
Tale:
ank8,Dispen erE" Stand e
Details
I
(E) DRAINAGE SWALE J (E) ISLAND
I I I (E) DRAINAGE SWALE
^�� ISLAND
FIG.
2.0
L J I CUT LINE J
L—J
(E) UDC
3
I ISLAND EXTENSION PLAN VIEW SCALE: 1/2" = 1'-0"
4 (SOUTH SECTION (NEW) SCALE: 1/2" = 1-0"
P,ele,Ne.
1
Recomme.ndezi Pmericesfor flg•i$Nr.4(e •11,1,d1:14spqii.Mwof 1 inie1 .1.-Wattst Add (DEF)
•
2,13 generic:ter-pi for all liquid -
containing components from. the: cutlet fitting of the
,e,ti:$geo0,r'1:42: to and jt lading the dispensing nozzle,
Typical hauging4lardWa-re COMponentS inelude dispens-
ing.hOSes, swivels, hrealtaways, and notzles,
244 11'01004o Oulft:cor4ilner(pc), A eont:ainer,
typically 275 to 3:30 tallOna,:naed fur transport and star
age of fluid andbulk materials. iSame; us'
g.143- iiiR.OtPatlitlii#IFitp coo :(1Ft.), A model fire code;
developed by tholittpplagoaat -000
Z-1.6 International Organst1od for fatEtti€14f.dfrAloit
(I$Q). A:ritni--,:geyennnental standar&settinghody estab-
lished. to. promote- the: develOpitent.of! .tfitidas412:a.#.11
and.related.activities,
247 Lipted..A, doignatiou kr products certified and
°published in a database by 4:11tiotiOly, recognized test
.ingjaboratoiy.(NkTL).,
2413 1140ter Creep. An. event where the dispense
meter register indicates n therease-.41 V011,10Ad when ti
pptqls: on, even though no.productis1Jeih4di51ienSe
249 11/14.0.1101 SPfotli: Data Sheet (IVISDS), A do
mentreontaining information and histrnetiona on mat
els- present in the workplace. •
220 11,110-6.414 $ystottl, A Wilkey storage, and
pensing system that afriVes at:a site fully assoiibled
.i-Llohidos::41:1 required vents; valves, anCLapPtirtenatie
taay be pie wred insulated, and/or provide tcon
poMainment..
2.44r. Af.ational Elootrical Oodo..(INIEC), .8TO
2.22 'llatioriel :Pipe Thr.Ood (MK), The
for• tapered threads used to join pipes -and
If
Tt
as
ard
2,23 Nozzle, 4 device: ty_pically.consisting ,of a spout,
handle, and operating:10pr, attached to the-endofA
pensing'1ose and:lised-fOr controlling. the flOW MT;
2,24 SOlectiVe Catalytic leductwri (9CR) An emhp-
siolKeduction technology that uses DEP With a catalytic
Op -vertex to: rechi-Of-,INO-jtiln cliesetenghtee3banst,
REVIEVVEOTORf
CODE COM *,.
APPR • hos_
MAY 0 52mi
e, The period of time, starting with the
oclection, in which Di -,113, .stared -Under
jons,. remains within the specifidatiOns
212.41-10(E), Table 1.
at*, A vessel having a liquid capacity
2.21 Tote, A container, typieally ii6tworl. 275 and 330
gallonS, used f,Or trospoit and storage of fluids and
bullmaterials. Satfire as an interntediate built container
(IBC,Y
'2.23 TOITIQV.61 'dim- required, to use the, voltune of
DEF salted hi a tank.
22 Urea, An o,rganio; compound :With: 'the ellem10:1
.fi:lCOitoIkneWri .aS catb amide,
ipOp(4.001:golvics::
GeirerJ. BBP i a nleOr3 C4iiorleSS non40ntle,
nop4larnM6le, Tt is #1406-1.-19 .
of -32.5 pouont urea with:the
- izeil at Urea.atid Watef7are:cettiPletely miscible an&
do riot separate in siorage„DEEhasia 40.ifig:/.-goviv:; of
1.09 atP andweighS!approximatell,(l19.0$10,110.
DEF is NOTt.:
• a motor fuel
-P. a. t.a01 additive
.4 4 flammable ot-ePrnIMStible liquid
• a volatile organic:compound
• a 1.1Y4:9.P4:459n liquid
• a liquid thatrequireS Stagy I ot Stage II vapor
recovery
currently regulated by Me federal gov-
,
lire
UP federal storage :diSpenSint " or disosal
fetlylretneras'for DgF.
City of Tukwila
BUILDING DIVISION
'equivement,s, . he -quality requirements:
for DEE are specified in ISO 222414. and DIN 70970.
TklirOtOdit001,:qf iany- impurities : can degrade .,DEF
qual1ty:. and.affect..: the ;:pertbrolnce.:,:of the SCft ,sysigig
Them must beat duringstopage
aiddipnsbjg Sea Appendix A for details op Imp.scifiii-
The-American:Petrolenm institute (API) has established
the:DieSel Exhaust'. Fluid Certiikation Prgram: it is a,
-voluntary- program that Certifies and monitors the qual-
ity ..of DEV. intended for use: in SCR;e4doped dlesl
hacks and passenger ears. DEF marketers participating
in the program can display the 041 giftECEVE
- CITY
APR 2
ikt(rOtO*7
F!'
a
ILA
PERMIT CENTER
it
FILE
Recommended PracticesJoi'the Storage and Dispensing of Diesel Exhaust XPiuidl.DE.P)
r^
APPENDIX B
EPA LETTER OF CLARIFICATION
;;a','iES' t=i1VItr1tat.1Eht'r1a_ a�CirEC'(i�u ;,r;iii4i
Wt.SHii'!ea Oi ! D.C. 20 1 7
SEP 2 2 2009
DMA
SUBJECT: Regulatory Status of UndergroutdDiese Exhaust Fluid Tanks
FROM: • Carolyn Iloskinson, Director
Office of Underground Stora
OFFb:[ ul-
SCLID
r.ESPci."SI:
TO: EPA UST/LUST Regional Program Managers
State UST Program Managers
This memorandum responds to questions from states on the regulatory status of
underground storage tanks (USTs) containing diesel exhaust fluid (DEF). Specifically, states
have asked whether EPA regulates USTs containing DEF under the federal UST regulations in
40 CFR Part 280. According to these regulations, an 'UST is regulated if it contains petroleum or
hazardous substances; however, a number of UST systems are excluded from the Part 280
requirements. One of the exclusions applies to "ja)ny UST system that contains a de tttiniinis
concentration of regulated substances" (*280.10(6)(5)). The regulations do not specify a de
ininbttis quantity, but do allow the implementing agency to determine do minimis concentrations
on a ease -by -case basis.
DEF is a 32.5 percent aqueous solution of urea used in Selective Catalytic Reduction
(SCR) technology as ono way to reduce nitrogen oxide emissions from heavy-duty diesel
engines, as required by EPA's "2007 heavy -Duty Highway' Rule." Although aqueous urea is
neither petroleum nor a hazardous substance, the DEF solution may contain a small amount of
ammonia, which is .a regulated substance. According to DEF manufacturers. any amount of
ammonia present in DEF is considered to be a contaminant. To address this contamination
concern, the industry has set a very strict limit on the maximum amount of ammonia allowed in
REVIEWE
ODE COM
APPRO
MAY 0E
D FOR .'ll;
PLI;NCE
aVED sht:
2016 t.'..'
City of Tukwila
BUILDING OIVISION
tion. Ilse international standard for DEF allows no more thim 02 percent by weight of
tinily. ntersuted as ammonia. to he present in solution. Although 0.2 percent is the
:imum allowed limit according to the international standard. mauuf-neturers indicatr. thrat•titr,
;al amount of ammonia in solution should be much less than 0.2 percent and ideally there
Id be no ammonia iu solution. Since EPA expects that the presence. of ammonia in a Dbt
will he miinimal, it is EPA's view that tslil' lists ;meet tIe ah= rrrirrimis rsclusiotr .tact tittet
;nt lr•.�utai.'i t.; li.-�_:a'toue: stibsOjue.c 1. S I s under ttt;: lell,:-rsl I sf
•
Y:e_ ; �I�' . .r .' .ri." ".I I.. : d .:. r. {(f`I. I.II
RECEIV
'CITY OF TU
bt OO7
APR 21 201
PERMIT CENTER
ILA
PEI Recontnteuded Practices 1100-10
Ak PENINX E,: t_PA LCEIT O[ C.LARlFIC=ATIOIV continued
In addition, EPA expects USTs storing DEP ;Hill be both compatible and secondarily
contained. international standards for DEEP set strict requirements for compatibility in order to
avoid product contamination caused by materials in the storage tank system degrading into the
DEF and also to prevent releases due to corrosion. Further, manufacturers recommend that
underground DEP' tank systems use secondary containment technologies with interstitial
monitoring. EPA expects that owners and operators of l)EF USTs will generally follow these
industry, manufacturer, and international standards for the storage of DEF in USTs.
If in the future EPA finds that ammonia released from DEF USTs endangers human
health and the environment, EPA may revisit the de mininris exclusion analysis contained in this
memorandum. Itis important to note that some states may choose to be more stringent than
federal regulations and require DEP USTs to fully comply with state UST regulations.
If you have any questions about this interpretation, please contact Andrea Barbet), at
barberti.andrea.(epa.nov or 703/603-7137.
cc: OUST Management
OUST Regional Liaisons
Kathy Nan, OGC
BILE
MATERIAL SAFETY DATA SHEET
SECTION 1. PRODUCT AND COMPANY INFORMATION
Trade Name (as labeled):
Common Name:
Distributed By:
Business Phone:
Emergency Phone:
Date of Preparation:
NOxBLUE Diesel Exhaust Fluid
Diesel Exhaust Fluid, Urea Solution
CoreFluids, LLC
PO Box 1027
Arroyo Grande, CA 93421
(877) 245-5518
INFOTRAC — (800) 535-5053
December, 2009
Revised Nov. 2010
SECTION 2. COMPOSITION AND INFORMATION ON INGREDIENTS
Chemical Name
CAS #
% by weight
Urea
57-13-6
32.5
Water
7732-18-5
67.5
SECTION 3. EMERGENCY/HAZARDS OVERVIEW
Emergency Overview:
Caution
Eye and Skin Irritant
Symptoms Of Over
Routes of exposure:
Eyes:
Skin:
Inhalation:
Ingestion:
Target Organs:
Signs and symptoms:
Exposure:
Eye, Skin contact, Inhalation, Ingestion
May cause irritation
May cause irritation
May cause irritation, May cause respiratory tract irritation
May cause stomach distress, nausea or vomiting
Eyes, skin and respiratory system.
May include redness, edema, drying, cracking of the skin,
Symptoms of exposure may be headache, dizziness, tiredness, nausea and
vomiting.
1
REVIEWED FOR
CODE COMPLIANCE
APPROVED
MAY 0 5 2016
City of Tukwila
BUILDING DIVISION
Hazardous Material Information Rating System:
(0 = least; 1 = slight; 2 = moderate; 3 = high; 4 = extreme)
Health (blue) 1
Flammability (red) 0
Reactivity (yellow) 0
CoreFluids, LLC
blv 00'1
RECEIVED
CITY OF TUKWILA
APR 22 2016
PERMIT CENTER
NOxBLUE Diesel Exhaust Fluid
2
SECTION 4. FIRST-AID MEASURES
If Inhaled:
Remove to fresh air. If breathing becomes difficult, contact a
medical physician. Give artificial respiration if victim is not
breathing and obtain immediate medical attention.
If Ingested:
Call physician or Poison Control Center immediately for most
current information. Dilute with large amounts of water. Do not
induce vomiting unless directed to do so by a medical
professional. Never induce vomiting or give diluents (milk or
water) to someone who is unconscious, having convulsions, or
who cannot swallow. If vomiting occurs, keep head lower than
hips to prevent introduction of fluid into the lungs.
In Case Of Skin Contact:
Wash thoroughly with soap and water. Remove contaminated
clothing and wash before reuse. Seek medical attention if skin
becomes irritated.
In Case Of Eve Contact:
Flush immediately with water for at least 15 minutes, lifting the
upper and lower eyelids occasionally. Call a physician if eye
irritation persists.
Victims of chemical exposure and all rescuers must be taken for medical attention. Take a copy of label
and MSDS to physician or health professional with victim.
SECTION
Flash Point:
Test Method:
LEL Flammable Limits:
UEL Flammable Limits:
Autoignition Temperature:
Extinguishing Media:
Unusual Fire and Explosion Hazards:
Special Firefighting Procedures:
5. FIRE -FIGHTING MEASURES
Not flammable.
Not flammable.
Not flammable.
Not flammable.
Not flammable.
Water spray, Foam, Carbon Dioxide, Dry -Chemical.
Avoid high temperatures that may cause thermal
decomposition..
Wear positive pressure, self-contained breathing
apparatus (SCBA) and goggles.
SECTION 6. ACCIDENTAL RELEASE MEASURES
Spill And Leak Response: For small or incidental spills, the minimum personal protective equipment
should be rubber gloves, rubber apron, and chemical goggles. Uncontrolled releases should be
responded to by trained personnel using pre -planned procedures. Proper protective equipment should be
used. Gas masks with ammonia canister or SCBA gear may be required. For large spills, contain by
diking with soil, sand or other absorbent material such as vermiculite or diatomaceous earth. Keep
material out of sewers, storm drains, and surface waters. Comply with all applicable government
regulations on spill reporting, handling, and waste disposal.
CoreFluids, LLC NOxBLUE Diesel Exhaust Fluid
3
Storage Practices:
Handling Practices:
SECTION 7. STORAGE AND HANDLING
Store in areas away from children, feed and food products and sources
of heat. Immediately clean up spills that occur during handling or
storage. Protect from freezing keep containers closed when not in use.
Optimal Storage Temperature 40 to 80°F.
Keep away from incompatible materials. Do not breathe mists. Wash
thoroughly after handling. Avoid contact with eyes, skin, and clothing.
Wash with soap and water after handling.
SECTION 8. EXPOSURE CONTROLS AND PERSONAL PROTECTION
Ventilation/Engineering Controls: Use with adequate ventilation to keep airborne levels below
recommended exposure limits.
Respiratory Protection: If work conditions generate vapors or mist, wear a NIOSH approved respirator
appropriate for those emission levels. Appropriate respirator may be a full face piece respirator, an SCBA
in the pressure demand mode, or a supplied -air respirator.
Eve Protection: Chemical dust/splash goggles or full -face shield to prevent eye contact. As a general
rule, contact lenses should not be worn when working with chemicals because they contribute to the
severity of an eye injury.
Hand Protection: Rubber gloves with gauntlets.
Body Protection: Use body protection appropriate for task. Chemical -resistant coveralls and rubber
aprons are generally acceptable.
Other Protective Measures: An eyewash and safety shower should be nearby and ready for use.
SECTION
Appearance:
Odor:
Water Solubility:
Density:
Specific Gravity (HgO = 1):
Stability:
Conditions to Avoid:
Incompatibility:
9. PHYSICAL AND CHEMICAL PROPERTIES
Clear, colorless Boiling Point: 104*C
Liquid
Very slight Freezing Point: -12*C
ammonia odor
9.8 to 10.0
100%. Vapor Pressure: NA.
9.1 lbs/gallon. Vapor Density (air = 1): NA.
1.087 — 1.093 @ NA = Not Available.
20�C
SECTION 10. STABILITY AND REACTIVITY
Stable under recommended storage conditions
Do not mix with any other chemicals or products.
Avoid contact with strong oxidizers (chlorine, peroxide,
chromates, nitric acid, perchlorates, concentrated oxygen, and
permanganates) which can generate heat, fire or explosions or
release toxic fumes.
Hazardous Polymerization: Will not occur.
Hazardous Decomposition Products: Oxides of nitrogen, oxides of carbon, and ammonia
SECTION 11. TOXICOLOGICAL INFORMATION
CoreFluids, LLC NOxBLUE Diesel Exhaust Fluid
A
Toxicity Data:
Urea LD50 Oral RAT 8471 mg/kg
Acute Effects:
Eyes: Moderate irritant. May cause redness, burning, inflammation, and/or damage.
Skin: Moderate irritant, especially with prolonged exposure. May cause skin ulceration and/or
burns.
Ingestion: May cause severe gastrointestinal irritation, vomiting, stomach cramps, and diarrhea.
May interfere with circulation and oxygen carrying capacity of blood with prolonged
exposure.
Inhalation: May cause irritation to mucous membranes, coughing, or breathing difficulties. If
exposed to decomposition gases remove from area immediately.
Chronic Effects: Not Available
SECTION 12. ECOLOGICAL INFORMATION
Ecotoxicity- Freshwater Fish Species Data
Urea 5713-6 96 Hr LC50 Barillius barna: >9,100 mg/I
Ecotoxicity- MicroTox Data
Urea 5713-6 24 Hr EC50 Daphnia magna straus: >10,000 mg/I
SECTION 13. DISPOSAL CONSIDERATIONS
Do not contaminate lakes, streams, ponds, estuaries, oceans, or other waters by discharge of waste
effluents or equipment rinsate. Dispose of waste effluents according to federal, state, and local
regulations. Chemical additions or other alterations of this product may invalidate any disposal
information in this MSDS.
SECTION 14. TRANSPORTATION INFORMATION
This material is not regulated by US DOT for highway transportation.
SECTION 15. REGULATORY INFORMATION
CERCLA: A spill or release of this material may trigger the emergency release reporting requirements
under CERCLA (40CFR Part 300) and/or SARA Title III (40 CFR Part 355). State and local reporting
requirements may differ from federal requirements. Consult for further guidance on your responsibilities
under these laws: (urea)
SARA Reporting Requirements: SARA, TITLE III, SECTION 313: This product not does contain toxic
chemicals subject to the reporting requirements of Section 313, Title III of the Superfund Amendments
and Reauthorization Act of 1986.
SECTION 16. OTHER INFORMATION
The information and recommendations herein are taken from data contained in independent industry
recognized references including NIOSH, OSHA, ANSI, and NFPA. This information is, as of date, listed
above, true and accurate to the best of CoreFluids, LLC knowledge. It is intended for use by persons
possessing technical knowledge and at their own discretion and risk. Since actual use is beyond our
control, no guarantee, express or implied, and no liability is assumed by CoreFluids, LLC in conjunction
with the use of this information. Actual conditions of use and handling may require consideration of
information other than, or in addition to, that which is provided herein.
CoreFluids, LLC NOxBLUE Diesel Exhaust Fluid
PERMIT COORD COPY
PLAN REVIEW/ROUTING SLIP
PERMIT NUMBER: D16-0107 DATE: 04/22/16
PROJECT NAME: PACIFIC PRIDE STATION
SITE ADDRESS: 13435 INTERURBAN AVE S
X Original Plan Submittal Revision # before Permit Issued
Response to Correction Letter # Revision # after Permit Issued
DEPARTMENTS:
Building Division op
)`11 Wo s
/v//h
Fire Prevention Planning Division gi
Structural
❑ Permit Coordinator
S
PRELIMINARY REVIEW:
Not Applicable ❑
(no approval/review required)
DATE: 04/26/16
Structural Review Required
REVIEWER'S INITIALS: DATE:
APPROVALS OR CORRECTIONS:
Approved
Corrections Required ❑ Denied
(ie: Zoning Issues)
Approved with Conditions
(corrections entered in Reviews)
DUE DATE: 05/24/16
Notation:
REVIEWER'S INITIALS:
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED.
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
12/18/2013
PACIFIC NORTHERN ENVIRO C )RP
Horne Espaiiol Contact
Safety & Health
CoWashington State Department of
Labor & Industries
Claims & Insurance
A -Z index Help
Page 1 of 3
My L&I
Workplace Rights Trades & Licensing
PACIFIC NORTHERN ENVIRO CORP
Owner or tradesperson
Principals
PARTRIDGE, JOHN WILFRED, PRESIDENT
JABUSCH, STEVE EDWIN, VICE PRESIDENT
PARTRIDGE, VICKIE VERL, SECRETARY
YOUNG, LARRY LEO, MEMBER
ARNOLD, DAVE W
(End: 01/01/1980)
WALDSCHMIDT, DAVE A
(End: 01/01/1980)
PACE, LOREN
(End: 01/01/1980)
QUIRK, JOE, CHIEF FINANCIAL OFFICER
(End: 06/30/2010)
Doing business as
PACIFIC NORTHERN ENVIRO CORP
WA UBI No.
601 217 845
1081 COLUMBIA BLVD
LONGVIEW, WA 98632-1024
360-423-2245
COWLITZ County
Business type
Corporation
Governing persons
DIRK
BARRAM
GARY HEALEA;
JOE QUIRK;
JOHN W PARTRIDGE;
JOHN WILFRED PARTRIDGE;
LARRY PETERSON;
STEVE JABUSCH;
TODD PARTRIDGE;
VICKIE V PARTRIDGE;
WILLIAM WILSON;
License
Verify the contractor's active registration / license / certification (depending on trade) and any past violations.
Construction Contractor Active.
Meets current requirements.
License specialties
GENERAL
License no.
PACIFNE022MH
Effective — expiration
07/08/1998— 07/01/2016
Bond
....._..........
ALLIED WORLD SPECIALTY INSURANCE
COMPANY
Bond account no.
S0011826
$12,000.00
https://secure.lni.wa.gov/verify/Detail.aspx?UBI=601217845&LIC=PACIFNE022MH&SAW= 5/9/2016
Interurban Ave. S.
411?
i
Driveway Driveway
�k�on poa6$�
a
Sidewalk
Sidewalk
Sidewalk
d
°
— —
Landscape
— — — — — —
�i
C E %�� _ ^r_
ATE ERMIT
sg°°��
t'_ '�`�ZS
FaU3 2��4
O
Vd..l�/"Y/ 1
i�Uit.D FOR:
@
ik6echanical
�l
Lectricaf
&Plumbing
Landscape
00
CardReader
l 4as Piping
City of Tukwila
Buy nING DIVISION
°�
O
a
,
Landscape
® Q D 11 ®
Building
A
1
CD
AS NOTED
°o
Satellite
MSREVIEWED
Peterson Structural Engineers, Ino. Apr 06 2016 HSN
11
Sign
NEW 1,000 GALLONa
o e �`o
o ®
Peterson Structural Engineers
708 Suite 100A
d
DEF STORAGE TANK •
Round Cover
Broadway,
Tacoma, WA 98402 (253) 830-2140
ON EXISTING
o
CONCRETE SLAB .� (E) Bollards
To e Removed°�
Master/Master
,.
Canopy &Concrete
Drive Pad Outline
�'
�
Area Of Work
J
1
° 1
.:`;pin
any
j,
$" Sch. 40 Steel
Covered
Sump
Pipe Bollard ►
CO
g
(N) DEF 1,000 GAL. TANK
Satellite
(TYP)
Pacific Pride
.0 • r
c� V)
o
Satellite
Tukwila
'1
0- 4)
— > c
REVISIONS
��o changes shall be made
° ®
13435 Interurban Ave. S.
cti Q O
Zi t
to the sc.,.�.
Qf"`Qrh �'�'ithout prior approval of
Raised Concrete
� �
dk�v la Building
1 �?� =: i=;;vaons will require aDnew plan submittal
Card
Reader
Island (Typ.)
COC
CO • a
j and may include additional plan review fees.
1
1(0-0 `7 1
(n
d
g
Permitae t D
-
L
a)
Master/Master
FIS Fie+,rY
� '1—'
, approval is subject
u ! ct to errors and omissions.
J �k_
!
s.
A
°
R 4
G�
F1 , r
1 i ; i ?1 fat r tion
ra! et construction documents
«.Aid APPROVED �7noemrft... �s
a r.
0
, does t
not kiutho6l�Q
COMPLIANCE
Cti
0
0
the violation of anyt
adopted
1,i changes �° �; t�� t?'. tothese
coda ®rordinanc. Receipt 1
of approved d Field Co andis cr.
l'
APPROVED
.—
O CO
o
O
IaW ti�olr?oWi from the
Planning tg Division of DCS
Master
(Single Sided)
conditions f..«nol�iod od.
l
S ` /
MAY ���
-E—+ �-
°o
` I
'-�
Date: -
Approved 13 :
�,
.�,/' 1
! c.it'tSTC(%ftAly`–
Landscape
/—•-----`�""-'
I
BUILDING ti�ftl0
IDate:
� v
city
Satellite
of Tukwila
BUILDING DIVISION
Drawn by: W.D.J.
g
'
Landscape i
Approved: B.H.
o
3
00
I
Issued Date: 03/30/16
@
} 4
Landscape ,.._.�
it) I
Revisions
E
a
- _ _
.- .r
Drawing Title:
I
I
Q� RECEIVED
CITY OF TUKWILA
site Plan
13445
PARK&RIDE
Interurban
Tukwila
Ave.
S.
APR 222016
CENT:-
SCALE f10' o.
D S L
1.0
0 5 10
11 x17 SETS ARE 50% REDUCTION
Project No:
NEW 1,000
G�
OD
03,
U
t
M
la
g
°
d
o0
g
AA
E
a
L
.
g
(� V
AA
E
O
a
�p
G
e
g
°�
2
r,
3
LI
g
a
2.0
O
Ti°O
b
C�
o
DEF
_...01.=10..._GALLON
REVIEWED AS NOTED
STORAGE TANK
(N) 1,000 GALLON "DEF" TANK -��
Apr 06 2016 HSN
" "DISPENSER
(N) DEF
�� (E) CANOPY COLUMN
Peterson Structural Engineers, Inc,
Peterson Structural Engineers
708 Broadway, Suite 100A
Tacoma, WA 98402 (253) 830-2140
(E) DISPENSER
��
I
I
FILL
,1
-.I
-J
___
------
_
_
'
(N) BOLLARD
�� (E) BOLLARD
,4
;
�
I `
I I
I'
r.M�
d•►•.fi
��x,
.
r
t
.
Fic Pride"
168
II
LL(
I
J
II
1 .I
�
IE)
DRAINAG
E
W LE
S A
I
I
(E)
I
I EXISTING ISLAND
UDC
(E)
1
UDC
I
�L
J�
II
I
I
SCALE: 1 /2" = 1'-0"
SOUTH ELEVATION �aa
W
)
DEF TANK ANCHORS
(16) anchors total, (8) per side equally
Kwik Bolt TZ -Stainless Steel 316, 3/8"
space
diameter
as best possible
with 2" embedment
,� (E) CANOPY COLUMN
NOTE:
Minimum edge distance in any direction
Install in strict conformance with manufacturer'sSAWCUTAND
=
4"
recommendations
�� (E) DISPENSER
Existingslab is assumed to meet the
minimum requirements for anchorage.
11" OF
REMOVE
EXISTING ISLAND
---.....„.....,6._(E)
(E) BOLLARD
REMOVED
COVER PLATES
�-
it
REVIEWED FOR
BOLLARDS
BY OTHERS
(E) DRAINAGE SWALE
I
I
I
�L
L
I
I
1
J�
-
1
I
I
1
I n (\
L_ � � -�
(E)
I
I
I (E) ISLAND
E DRIVE PAD
O
UDC
(� (�
�- � .� J°
(E)
I
I II
UDC
1I
1
I I
�L
J
I
I
11
I
1
CODE COMPLIANCE
APPROVED
<...
`' MAY 2��i
Tukwila
c o_I
BUILDING DIVISION
\t)
1 (0... 0 1 0 7
2
SO
I
ELEVATION (EXISTING)
SCALE: 1/2" = 1 —0
(N) 8" SCH STEEL PIPE BOLLARD
CANOPY COLUMN
.
.40
(E)
TYP. OF 2
-
. 4 I I - " TANK
��
I
COVER PLATES
15'-6"
7'-7"
(E)
,--.—
e
e
e
®
�
�— (N) 8" SCH .40 STEEL PIPE BOLLARD
E CANOPY COLUMN
(E)
e
��
36 MIN. ABOVE GRADE
I
.Q
36 MIN. BELOW GRADE
,d
o o
�� �'
II
I
II
I
I
EXISTING RECEIVED
(E) DRAINAGE SWALE
��
(E) ISLAND
I
I
I
I
(E) DRAINAGE SWALE
I
-.I
I-
- -
ISLAND
ILA
r
II
L J
CUT LINE
APR 22 2016
(E) UDC
PERMIT CENTER
3
ISLAND EXTENSION PLAN VIEW SCALE: 1/2" = 1'-0"
4
SOUTH SECTION (NEW) SCALE: 1/2" = 1'-0"