HomeMy WebLinkAboutPermit M16-0017 - SABEY - DUCT WORK AND THERMOSTAT RELOCATION12201 TUKWIIA
INTERNATIONAL BLVD
M16-0017
City of Tukwila
• Department of Community Development
+ 6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670
Inspection Request Line: 206-438-9350
Web site: http://www.TukwilaWA.gov
MECHANICAL PERMIT
Parcel No: 0923049120 Permit Number: M16-0017
Address: 12201 TUKWILA INTERNATIONAL Issue Date: 2/25/2016
BLVD BLDG B Permit Expires On: 8/23/2016
Project Name: SABEY
Owner:
Name: INTERNATIONAL GATEWAY WEST
Address: 12201TUKWILA INTERNATIONAL BL,
SEATTLE, WA, 98168
Contact Person:
Name: TERESE ANDERSON Phone: (253) 796-5825
Address: 1221 SECOND AVE N, KENT, WA,
98032
Contractor:
Name: HERMANSON COMPANY LLP Phone: (206) 575-9700
Address: 1221 2ND AVE N, KENT, WA, 98032-
2945
License No: HERMACLO05BJ Expiration Date: 8/25/2016
Lender:
Name:
Address:
DESCRIPTION OF WORK:
RELOCATE EXISTING DUCT WORK AND RELOCATE ONE THERMOSTAT
Valuation of Work: $5,500.00 Fees Collected: $272.02
Type of Work: REPLACEMENT Electrical Service Provided by: SEATTLE CITY LIGHT
Fuel type: ELECT Water District: 20
Sewer District: VALLEY VIEW SEWER SERVICE
Current Codes adopted by the City of Tukwila:
International Building Code Edition:
2012
National Electrical Code:
2014
International Residential Code Edition:
2012
WA Cities Electrical Code:
2014
International Mechanical Code Edition:
2012
WAC 296-466:
2014
Uniform Plumbing Code Edition:
2012
WA State Energy Code:
2012
International Fuel Gas Code:
2012
Permit Center Authorized Signature:
I hearby certify that I have read and examined this permit and know the same to be true and correct. All
provisions of law and ordinances governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other
state or local laws regulating construction or the performance of work. I am authorized to sign and obtain this
development permit and agree to the conditions attached to this permit.
Signa
Print
tures:! L? � 7 Date: Z
Name:
This permit shall become null and void if the work is not commenced within 180 days for the date of issuance, or if
the work is suspended or abandoned for a period of 180 days from the last inspection.
PERMIT CONDITIONS:
1: Work shall be installed in accordance with the approved construction documents, and any changes made
during construction that are not in accordance with the approved construction documents shall be
resubmitted for approval.
2: All permits, inspection record card and approved construction documents shall be kept at the site of work
and shall be open to inspection by the Building Inspector until final inspection approval is granted.
3: All construction shall be done in conformance with the Washington State Building Code and the
Washington State Energy Code.
4: Remove all demolition rubble and loose miscellaneous material from lot or parcel of ground, properly cap
the sanitary sewer connections, and properly fill or otherwise protect all basements, cellars, septic tanks,
wells, and other excavations. Final inspection approval will be determined by the building inspector based
on satisfactory completion of this requirement.
5: All plumbing and gas piping work shall be inspected and approved under a separate permit issued by the
City of Tukwila Building Department (206-431-3670).
6: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila
Permit Center.
7: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an
approval of, any violation of any of the provisions of the building code or of any other ordinances of the City
of Tukwila. Permits presuming to give authority to violate or cancel the provisions of the code or other
ordinances of the City of Tukwila shall not be valid. The issuance of a permit based on construction
documents and other data shall not prevent the Building Official from requiring the correction of errors in
the construction documents and other data.
8: ***MECHANICAL PERMIT CONDITIONS***
9: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila
Permit Center (206/431-3670).
10: Manufacturers installation instructions shall be available on the job site at the time of inspection.
PERMIT INSPECTIONS REQUIRED
Permit Inspection Line: (206) 438-9350
1800 MECHANICAL FINAL
0609 PIPE/DUCT INSULATION
0701 ROUGH -IN MECHANICAL
CITY OF TUKW1
•
Community Development Department
Permit Center
• 6300 Southcenter Blvd., Suite 100
Tuk►vila, WA 98188
hiip://www.TukwilaWA.Pov
Mechanical Permit No. /6-10l7
Project No.
Date Application Accepted: o/%&M,
Date Application Expires: 0-74a &.0
or office use only)
MECHANICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
**please print**
SITE LOCATION
King Co Assessor's Tax No... 0923049120
Site Address: 12201 Tukwila International Blvd Bldg B Suite Number: Floor:
Tenant Name: Sabey New Tenant: ❑ .....Yes 0 ..No
PROPERTY OWNER
Name: Sabey Construction
Address: 12201 Tukwila International Blvd
City: Tukwila State: WA Zip: 98168
CONTACT PERSON — person receiving all project
communication
Name: Terese Anderson
Address: 1221 2nd Ave N
City: Kent State: WA Zip: 98032
Phone: (206) 200-7804 Fax:
Email: tnderson@hermanson.com
MECHANICAL CONTRACTOR INFORMATION
Company Name: Hermanson Company
Address: 1221 2nd Ave N
City: Kent State: wA Zip: 98032
Phone: (206) 575-9700 Fax:
Contr Reg No.: 1qEq04ACL9qc
jDy, Exp Date: 03/12/2017
Tukwila Business License No.: BUS -0994464
Valuation of project (contractor's bid price): $ 5,500
Describe the scope of work in detail:
Relocate existing duct work and Relocate one thermostat
Use: Residential: New .......... ❑ Replacement ........ ❑
Commercial: New .......... ❑ Replacement ........ 0
Fuel Type: Electric..... ❑ Gas ....... ❑ Other:
H:\Applications\Forms-Applications On Line\201 I Applications\Mechanical Permit Application Revised 8-9-1 I.docx
Revised: August 2011 Page I of 2
bh
Indicate type of mechanical work being installed and the quantity below:
Unit Type
Qty
Furnace <100k btu
Furnace >100k btu
Floor furnace
1.
Suspended/wall/floor
mounted heater
Appliance vent
Repair or addition to
heat/refrig/cooling
system
Air handling unit
<10,000 cfm
Unit Type
Qty
Air handling unit
>I0,000 cfin
Evaporator cooler
Ventilation fan
connected to single duct
1.
Ventilation system
Hood and duct
Incinerator — domestic
Incinerator —
comm/industrial
PERMIT APPLICATION NOTES -
Unit Type
Qty
Fire damper
Diffuser
Thermostat
1.
Wood/gas stove
Emergency enerator
Other mechanical
equipment
Boiler/Compressor Qty
0-3 hp/100,000 btu
3-15 bp/500,000 btu
15-30 hp/1,000,000 btu
30-50 hp/1,750,000 btu
50+ hp/1,750,000 btu
Value of construction — in all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the permit center to comply with current fee schedules.
Expiration of plan review — applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The building official may grant one extension of time for additional periods not to exceed 90 days each. The extension shall be requested in writing
and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT
BUILDING OWNER OR AUTHORIZED AGENT:
Date: 01/25/2016
Print Name: Terese Anderson Day Telephone: (206) 200-7804
Mailing Address: 1221 2nd Ave N Kent
City
H:\Applications\Forms-Applications On Line\201 I Applications\Mechanical Permit Application Revised 8-9-1 l.doex
Revised: August 2011
bh
WA 98032
State Zip
Page 2 of 2
DESCRIPTIONS
•
QUANTITY
PAID
PermitTRAK
$272.02
M16-0017 Address: 12201 TUKWILA INTERNATIONAL BLVD BLDG B
0923049120
Apn:
$272.02
MECHANICAL
$261.56
PERMIT ISSUANCE BASE FEE
R000.322.100.00.00
0.00
$32.50
PERMIT FEE
R000.322.100.00.00
0.00
$176.75
PLAN CHECK FEE
R000.322.102.00.00
0.00
$52.31
TECHNOLOGY FEE
$10.46
TECHNOLOGY FEE
TOTAL. ..
R000.322.900.04.00
0.00
$10.46
$272.02
Date Paid: Tuesday, January 26, 2016
Paid By: HERMANSON COMPANY
Pay Method: CREDIT CARD 893677
Printed: Tuesday, January 26, 2016 2:28 PM 1 of 1
rPWSYS7fM5
K
INSPECTION RECORD
Retain a copy with permit (6-00f7
INS PtL ON N0. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. `JVA 98188 (206) 431-3670
Permit Inspection Request Line (206) 438-9350
PLC
be y
Type of Inspe tion: _ r
/"
-, �/, /
Address: -r4-
�i� / 4- l ✓
Dat,�JCal d:
9 96,
Special Instructions:
�f
S (' �� l f 1
'. n� p��
Date 1N ted: a.m.
, �� �'[ p.m.
Renester :
e ® Q r�
Phone No:
F] REINSPECTION FEE REQUIRED. Prior to next inspection, tee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
(16
INSPECTION RECORD �tr6-c)o 7t7
Retain a copy with permit
INKCI ION NO, PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd- #100, Tukwila. WA 98188 (206) 43.1-3670
Permit. Inspection Request Line (206) 438-9350
Project:
Ty
j, of Inspection: A p�
�C
Address:
Date C ed: 10
Speciallnstructions:
Date anted: a.m.
-3-1-1,6 p.m.
Requester:
S �.r S-
Phone No:
IInspector :j� IDate:��l `�
❑ REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
PY
PLANEWRRO
Pl��`VTUTING SLIP
PERMIT NUMBER: M16-0017 DATE: 01/26/16
PROJECT NAME: SABEY
SITE ADDRESS: 12201 TUKWILA INTERNATIONAL BLVD
X Original Plan Submittal Revision # before Permit Issued
Response to Correction Letter #,
DEPARTMENTS:
"0 N
Building Division IN
Public Works ❑
PRELIMINARY REVIEW:
Not Applicable ❑
(no approval/review required)
REVIEWER'S INITIALS:
APPROVALS OR CORRECTIONS:
Approved ❑
Corrections Required ❑
(corrections entered in Reviews)
Notation:
REVIEWER'S INITIALS:
Revision # after Permit Issued
AA NIA- 177)%%*
Fire Prevention 6 Planning Division ❑
Structural ❑ Permit Coordinator a
DATE: 01/28/16
Structural Review Required ❑
DATE:
DUE DATE: 02/25/16
Approved with Conditions ❑
Denied ❑
(ie: Zoning Issues)
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
12/18/2013
HERMANSON COMPANY LLP
Home Espanol Contact
Safety & Health
Washington State Department of
Labor & Industries
HERMANSON COMPANY LLP
Owner or tradesperson
Principals
NICOLAISEN, KNUT H, PARTNER/MEMBER
BROCK, DANIEL L, PARTNER/MEMBER
FOX, DEAN M, PARTNER/MEMBER
HENGEL, STEPHEN A, PARTNER/MEMBER
DYCKMAN,KENNETH
A, PARTNER/MEMBER
ROBINETT, PAUL J, PARTNER/MEMBER
HERMANSON, RICHARD
L, PARTNER/MEMBER
ALMON, KEVIN, PARTNER/MEMBER
(End: 08/05/2010)
MACDONALD, JAMES, PARTNER/MEMBER
(End: 08/05/2010)
Doing business as
HERMANSON COMPANY LLP
Page 1 of 3
(Search L&I
A -Z., Index. Help Mc Secure I.,&I
Claims & Insurance Workplace Rights Trades & Licensing
1221 2ND AVE N
KENT, WA98032-2945
206-575-9700
KING County
WA UBI No. Business type
602 004 844 Limited Liability Partnership
Governing persons
CORP
HERMANSON
LLC HERMANSON GROUP;
FTicense
Verify the contractor's active registration / license / certification (depending on trade) and any past violations.
Construction Contractor Active.
Meets current requirements.
License specialties
GENERAL
License no.
HERMACL005BJ
Effective — expiration
01/11/2000— 08/25/2016
Bond
._.............
WESTERN SURETY CO
$12,000.00
Bond account no.
929381801
Received by L&I
Effective date
12/01/2005
01/01/2006
Expiration date
Until Canceled
https:Hsecure.Ini.wa.gov/verify/Detail.aspx?UBI=602004844&LIC=HERMACLO05BJ&SAW= 2/25/2016
MECHANICAL ABBREVIATIONS
A
AMPS
IE
INVERT ELEVATION
AC
AIR CONDITIONING
IEER
INTEGRATED ENERGY EFFICIENCY RATIO
ACH
AIR CHANGES PER HOUR
IMC
INTERNATIONAL MECHANICAL CODE
ACT
ACOUSTICAL CEILING TILE
IN
INCHES
AD
ACCESS DOOR
IN WG
INCHES WATER GAUGE
ADD'L
ADDITIONAL
IPLV
INTEGRATED PART LOAD VALUE
AFF
ABOVE FINISHED FLOOR
KW
KILOWATTS
AFG
ABOVE FINISHED GRADE
LAT
LEAVING AIR TEMPERATURE
AHU
AIR HANDLING UNIT
LB/LBS
POUND/POUNDS
ALUM
ALUMINUM
LF/LIN FT
LINEAL FOOT/FEET
AMP/AMPS
AMPERAGE
LPG
LIQUID PROPANE GAS
AP
ACCESS PANEL
LPS
LOW PRESSURE STEAM
ARCH
ARCHITECT
LVG
LEAVING
BC
BEADED COLLAR
LWA
SOUND POWER RATING LEVEL (IN DB)
BDD
BACKDRAFT DAMPER
LWG
LOW WALL GRILLE
BF
BELOW FLOOR
LWT
LEAVING WATER TEMPERATURE
BHP
BRAKE HORSEPOWER
MAX
MAXIMUM
BLDG
BUILDING
MAU
MAKE UP AIR UNIT
BOD
BOTTOM OF DUCT
MBH
1000 BRITISH THERMAL UNITS/HOUR
BOP
BOTTOM OF PIPE
MCA
MINIMUM CIRCUIT AMPACITY
BOT
BOTTOM
MD
MOTORIZED DAMPER
BS
BIRD SCREEN / BLACK STEEL
MFR
MANUFACTURER
BTU
BRITISH THERMAL UNIT
MISC
MISCELLANEOUS
BTUH
BRITISH THERMAL UNITS PER HOUR
MIN
MINIMUM/MINUTE
CAP
CAPACITY
MPS
MEDIUM PRESSURE STEAM
CC
CONTROLS CONTRACTOR
MT
MOUNT
CD
CEILING DIFFUSER/CONDENSATE DRAIN
MTD
MOUNTED
CDWR
CONDENSER WATER RETURN
MUW
MAKE-UP WATER
CDWS
CONDENSER WATER SUPPLY
NA
NOT APPLICABLE
CFM
CUBIC FEET PER MINUTE
NC
NORMALLY CLOSED/NOISE CRITERIA
CHWR
CHILLED WATER RETURN
NG/NGAS
NATURAL GAS
CHWS
CHILLED WATER SUPPLY
NIC
NOT IN CONTRACT
CLG
CEILING
NO
NORMALLY OPEN/NUMBER
COL
COLUMN
NPW
NON -POTABLE WATER
CONC
CONCRETE
N -R
NON-RESIDENTIAL
COND
CONDENSATE
OA/OSA
OUTSIDE AIR
CONN
CONNECT/CONNECTED/CONNECTION
OBD
OPPOSED BLADE DAMPER
CONT
CONTINUOUS/CONTINUATION
OD
OUTSIDE DIAMETER/DIMENSION
CONTR
CONTRACTOR
PCF
POUNDS PER CUBIC FOOT
COORD
COORDINATE
PD
PRESSURE DROP
COP
COEFFICIENT OF PERFORMANCE
PH
PHASE
CT
COOLING TOWER
POC
POINT OF CONNECTION
CU
CUBIC/CONDENSER UNIT
P/PRESS
PRESSURE
CW
DOMESTIC COLD WATER/CONDENSER WATER
PSI
POUNDS PER SQUARE INCH
DB
DUCTBOARD/DRY BULB/DECIBEL
PSIG
POUNDS PER SQUARE INCH GAUGE
DDC
DIRECT DIGITAL CONTROL
QTY
QUANITY
DEFL
DEFLECTION
R
RETURN GRILLE/RELOCATED/RETURN
DEG
DEGREE/DEGREES
RA
RETURN AIR
DIA
DIAMETER
RD/RND
ROUND
DMPR
DAMPER
REF
REFERENCE
DN
DOWN
REQ
'REQUIRED
DWG
DRAWING
RESID
RESIDENTIAL
EXH
EXHAUST
RF
RELIEF
EA
EACH
RG
REFRIGERANT DISCHARGE GAS
EAT
ENTERING AIR TEMPERATURE
RL
REFRIGERANT LIQUID
EC
EGGCRATE GRILLE/END CAP/ELEC CONTRACTOR
RPM
REVOLUTIONS PER MINUTE
EER
ENERGY EFFICIENT RATING
RS
REFRIGERANT SUCTION
EF
EXHAUST FAN
S
SUPPLY
EFF
EFFICIENCY
SA
SUPPLY AIR
EL
ELEVATION
SAT
SATURATION/SUPPLY AIR TEMPERATURE
ELEC/ELECT ELECTRICAL/ELECTRIC
SD
SMOKE DETECTOR
EMCS
ENERGY MANAGEMENT CONTROL SYSTEM
S/D
SLIP & DRIVE CONNECTION
ENT
ENTERING
S -C
SEATTLE CODE
EQUIP
EQUIPMENT
SEER
SEASONAL ENERGY EFFICIENCY RATING
ESP
EXTERNAL STATIC PRESSURE
SENS
SENSIBLE
EWT
ENTERING WATER TEMPERATURE
SL
SOUND LINED
EXIST
EXISTING
SM
SHEETMETAL
EXH
EXHAUST
SPEC
SPECIFICATION
F
FAHRENHEIT
SO
SCREENED OPENING
FAC
FIRE ALARM CONTRACTOR
SOG
SLAB ON GRADE
FD
FIRE DAMPER
SP
STATIC PRESSURE
FDC
FIRE DEPARTMENT CONNECTION
SF
SQUARE FEET
FF
FINISHED FLOOR
SS
STAINLESS STEEL
FIC
FURNISHED AND INSTALLED BY CONTRACTOR
STRUC
STRUCTURAL
FIO
FURNISHED AND INSTALLED BY OWNER
TA
TRANSFER AIR
FLA
FULL LOAD AMPS
TEMP
TEMPERATURE/TEMPORARY
FLEX
FLEXIBLE
TBD
TO BE DETERMINED
FLR
FLOOR
TOD
TOP OF DUCT
FOB
FLAT ON BOTTOM
TOS
TOP OF STEEL/TOP OF SLAB
FOIC
FURNISHED BY OTHERS,
TOT
TOTAL
INSTALLED BY CONTRACTOR
TSP
TOTAL STATIC -PRESSURE
FOS
FLAT ON SIDE
TSTAT
THERMOSTAT
FOT
FLAT ON TOP
TYP
TYPICAL
FP
FIRE PROTECTION
UH
UNIT HEATER
FPM
FEET PER MINUTE
UNO
UNLESS NOTED OTHERWISE
FSD
FIRE/SMOKE DAMPER
V
VOLT
FT
FOOT/FEET
VD
VOLUME DAMPER
FUT
FUTURE
VEL
VELOCITY
FV
FACE VELOCITY
VERT
VERTICAL
G
GRILLE
VFD
VARIABLE FREQUENCY DRIVE
GA
GAUGE/GALLON
VOL
VOLUME
GALV
GALVANIZED
W
WRAPPED DUCT
GC
GENERAL CONTRACTOR
WB
WET BULB
GPM
GALLONS PER MINUTE
WG
WATER GAUGE
GRD
GRILLE/REGISTER/DIFFUSER
W/
WITH
GWB
GYPSUM WALL BOARD
W/0
WITHOUT
HD
HEAD
W/SF
WATTS PER SQUARE FOOT
HORIZ
HORIZONTAL
WSEC
WASHINGTON STATE ENERGY CODE
HP
HORSEPOWER
HR
HOUR
HSPF
HEATING SEASONAL PERFORMANCE FACTOR
HT
HEIGHT
HWTG
HIGH WALL TRANSFER GRILLE
HWR
HOT WATER RETURN
HWS
HOT WATER SUPPLY
HX
HEAT EXCHANGER
HZ
HERTZ
IBC
INTERNATIONAL BUILDING CODE
ICW
INDUSTRIAL COLD WATER
ID
INSIDE DIAMETER/DIMENSION
MECHANICAL LEGEND
10X10 RECT SUPPLY AIR DUCT
10� UP/TOWARD
10X10 RECT SUPPLY NR DUCT
10X1 `< DN/AWAY
10X10 RECT EXHAUST OR RETURN DUCT
+10X� UP/TOWARD
10X10 ,' RECT EXHAUST OR RETURN DUCT
.].DN/AWAY
100
100 ROUND DUCT - UP/TOWARD
�IQLi
- 110o00 '�� ROUND DUCT - DN/ AWAY
-J
12X100 FLATOVAL DUCT - UP/ TOWARD
12X100; Fl,gTOVAL DUCT - DN/ AWAY
100 � DUCT OVERLAP
100
BOOT TAP
109
100 45' TAP
100 VOLUME DAMPER
100
RISE(R) & DROP(D)
�TRANSITION
TURNING VANES/SPLITTERS
(s) DUCT MOUNTED SMOKE DETECTOR
BACK DRAFT DAMPER
�rw�nn FLEXIBLE DUCT
-Alr> NR ROW (FORCED NR)
COMBINATION FSD
FIRE DAMPER
SMOKE DAMPER
MOTOR OPERATED DAMPER
lll
ACCESS DOORS
SOUND TRAP
FLEX CONNECTION
16X16SL I ACOUSTICALLY LINED DUCT (SL)
s.QQr FABRIC DUCT
CLEARANCE
SUPPLY AIR DIFFUSER
(WITH CORE BLANKOFF)
EXISTING DUCTWORK
DEMO DUCTWORK
I
WALL -MOUNTED GRILLE
CEILING RETURN, TRANSFER OR
PIPE ELBOW UP
18.
PIPE ELBOW DN
SHALL
EXHAUST
AIR GRILLE
DIRECTION OF SLOPE DOWN
o
SLOTTED
DIFFUSER (PLAN VIEW)
PRESS REDUCING ASSEMBLY
Q
REVISION
CLOUD & TRIANGLE
PUMP
##0
ROUND DUCT SYMBOL
i�- RL/RS
##
FLATREES
SYMBOL
t-- LPG -s
##.0
DEG
SYMBOL
2-HWS/HWR-s
®
POINT OF
CONNECTION
z-- FOV
01-100
GRD TAG
IDENTIFIER = TYPE -CFM
2 RDG -i
80
SIZE
T
T'STAT/TEMP SENSOR
®o CARBON DIOXIDE
H
HUMIDITY SENSOR
SENSOR
sD
SMOKE DETECTOR
co CARBON MONOXIDE
sP
STATIC PRESSURE
SENSOR
SENSOR
EXISTING DUCTWORK
MECHANICAL GENERAL NOTES
1. WORK SHALL CONFORM TO APPLICABLE CODES AND REGULATIONS, INCLUDING, BUT NOT LIMITED TO THE 2012 IBC, 2012 WSEC, & 2012 IMC.
2. DIMENSIONS ARE TO FACE OF STUD, CONCRETE, OR MASONRY UNLESS NOTED OTHERWISE.
3. DO NOT SCALE DRAWINGS. DIMENSIONS GOVERN.
4. VERIFY EXISTING CONDITIONS, DIMENSIONS, DETAILS, ETC. NOTIFY ENGINEER OF ANY DISCREPANCIES PRIOR TO PROCEEDING WITH WORK.
5. WHEN CONSTRUCTION DETAILS ARE NOT SHOWN OR NOTED FOR ANY PART OF THE WORK, DETAILS SHALL BE THE SAME
AS FOR OTHER SIMILAR WORK. IF ADDITIONAL QUESTIONS REMAIN, CONTACT THE ENGINEER PRIOR TO PROCEEDING.
6. ALL STRUCTURAL OPENINGS AND PLATFORMS SHALL BE PROVIDED BY THE GENERAL CONTRACTOR UNLESS NOTED OTHERWISE.
7. DUCT SEALING AND CONSTRUCTION TO MEET SMACNA AND ENERGY CODE REQUIREMENTS. UNLESS OTHERWISE NOTED, LOW PRESSURE DUCTWORK
(DOWNSTREAM OF VAV BOXES, CONSTANT VOLUME AC SYSTEMS, TOILET EXHAUSTS, ETC.) TO MEET 2" CONSTRUCTION STANDARDS WITH
SEAL CLASS C. MEDIUM PRESSURE DUCTWORK (UPSTREAM OF VAV BOXES, HIGH VELOCITY EXHAUSTS, ETC.) TO MEET 4" CONSTRUCTION STANDARDS
WITH SEAL CLASS A. DUCT RISERS IN SHAFTS WITH DAMPERED PENETRATIONS TO MEET 6" CONSTRUCTION STANDARDS WITH SEAL CLASS A.
8. ALL CEILING DIFFUSERS ARE 4 -WAY THROW UNLESS NOTED OTHERWISE.
9. ALL DUCT DIMENSIONS ARE CLEAR INSIDE DIMENSIONS AFTER LINING HAS BEEN ACCOUNTED FOR.
10. OUTSIDE AIR INTAKES ON ALL AIR HANDLING UNITS SHALL BE 10 FEET AWAY FROM ANY FUEL BURNING EQUIPMENT OR 3 FEET BELOW
ANY PLUMBING VENT OR EXHAUST OUTLET WITHIN 10 FEET
11. ALL AIR ECONOMIZERS SHALL BE CAPABLE OF THE FOLLOWING:
-0% TO 100% OF THE DESIGN SUPPLY AIR
-CONTROLLED BY A CONTROL SYSTEM DETERMINING IF THE OUTSIDE AIR CAN MEET PART OR ALL OF THE BUILDING COOLING LOADS.
-INTEGRATED TO PROVIDE PARTIAL COOLING EVEN WHEN MECHANICAL COOLING IS REQUIRED.
12. OUTSIDE AIR INTAKE, RELIEF, AND EXHAUST OPENINGS SHALL BE EQUIPPED WITH MOTORIZED (OR GRAVITY DAMPERS PER
EXCEPTIONS IN C403.2.4.4) WHICH CLOSE AUTOMATICALLY WHEN SYSTEM IS OFF OR UPON POWER FAILURE.
13. THE CONTROL SYSTEM SHALL BE 7 -DAY PROGRAMMABLE, CAPABLE OF BEING SET FOR SEVEN (7) DIFFERENT DAY TYPES PER WEEK,
AND CAPABLE OF A DEADBAND SETTING OF AT LEAST 57 (10'F FOR RESIDENTIAL BETWEEN THE HEATING AND COOLING SETPOINTS. AHU CONTROL
SYSTEM SHALL INCLUDE A MICROPROCESSOR AND BE CAPABLE OF RESETTING SU PLY AIR TEMPERATURES BY REPRESENTATIVE BUILDING LOADS.
14. RECORD DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDED TO THE BUILDING OWNER WITHIN 90 DAYS OF THE DATE
OF SYSTEM ACCEPTANCE PER THE WASHINGTON STATE ENERGY CODE. AN OPERATING MANUAL AND MAINTENANCE MANUAL
SHALL BE PROVIDED TO THE BUILDING OWNER. ALL HVAC SYSTEMS SHALL BE BALANCED AND A WRITTEN BALANCING REPORT
SHALL BE PROVIDED TO THE OWNER. HVAC CONTROL SYSTEMS SHALL BE TESTED TO ENSURE THAT THEY OPERATE IN ACCORDANCE
WITH APPROVED PLANS. A PRELIMINARY COMMISSIONING REPORT OF TEST PROCEDURES AND RESULTS SHALL
BE PREPARED PRIOR TO ISSUANCE OF A FINAL CERTIFICATE OF OCCUPANCY. A COMPLETE FINAL COMMISSIONING REPORT OF
TEST PROCEDURES AND RESULTS SHALL BE PROVIDED TO THE OWNER. COMMISSIONING, SYSTEM BALANCING, RECORD DRAWINGS
AS REQUIRED PER THE WASHINGTON STATE ENERGY CODE C408.
15. MECHANICAL SYSTEMS SHALL COMPLY WITH SEISMIC RESTRAINT REQUIREMENTS OF THE BUILDING CODE SMACNA AND ASCE 7. ALL LIFE
SAFETY OR HAZARDOUS MATERIAL RELATED SYSTEMS SHALL BE DEEMED AN Ip
-1.5 FOR RESTRAINT METHODS OR AS NOTED ON THE DRAWINGS.
REFER TO CODES FOR INSTALLATION REQUIREMENTS AND EXCEPTIONS BASED ON SIZING, WEIGHTS AND MOUNTING HEIGHTS.
16. PROVIDE EARTHQUAKE RESTRAINTS FOR HVAC EQUIPMENT AS REQUIRED BY SMACNA SEISMIC RESTRAINT MANUAL, SEISMIC HAZARD B.
WIRES FOR CEILING SYSTEM ETC. SHALL NOT BE HUNG OFF HVAC EQUIPMENT OR HVAC EQUIPMENT SUPPORTS.
17.
DEMO DUCTWORK
I
WALL -MOUNTED GRILLE
PLANS AND
PIPE ELBOW UP
18.
PIPE ELBOW DN
SHALL
DIRECTION OF FLOW
WITH AN UL
DIRECTION OF SLOPE DOWN
AND INTERLOCK
PLUG OR CAP
ELECTRICAL CONTRACTOR AS APPLICABLE.
PRESS REDUCING ASSEMBLY
AND INSTALLED BY GENERAL
SOLENOID VALVE
--�
PUMP
2-CHWS/CHWR-S
CHILLED WATER SUPPLY/RETURN
i�- RL/RS
REFRIGERANT LIQUID/SUCTION
t-- NG --s
NATURAL GAS
t-- LPG -s
LIQUID PROPANE GAS
2-CDWS /CDWR-s
CONDENSER WATER SUPPLY/RETURN
2-HWS/HWR-s
HEATING WATER SUPPLY/RETURN
Z-- COND ---s
CONDENSATE
z-- FOV
FUEL OIL VENT
2--- FOS /FOR -s
FUEL OIL SUPPLY/RETURN
2 RDG -i
REFRIGERANT DISCHARGE GAS
MECHANICAL GENERAL NOTES
1. WORK SHALL CONFORM TO APPLICABLE CODES AND REGULATIONS, INCLUDING, BUT NOT LIMITED TO THE 2012 IBC, 2012 WSEC, & 2012 IMC.
2. DIMENSIONS ARE TO FACE OF STUD, CONCRETE, OR MASONRY UNLESS NOTED OTHERWISE.
3. DO NOT SCALE DRAWINGS. DIMENSIONS GOVERN.
4. VERIFY EXISTING CONDITIONS, DIMENSIONS, DETAILS, ETC. NOTIFY ENGINEER OF ANY DISCREPANCIES PRIOR TO PROCEEDING WITH WORK.
5. WHEN CONSTRUCTION DETAILS ARE NOT SHOWN OR NOTED FOR ANY PART OF THE WORK, DETAILS SHALL BE THE SAME
AS FOR OTHER SIMILAR WORK. IF ADDITIONAL QUESTIONS REMAIN, CONTACT THE ENGINEER PRIOR TO PROCEEDING.
6. ALL STRUCTURAL OPENINGS AND PLATFORMS SHALL BE PROVIDED BY THE GENERAL CONTRACTOR UNLESS NOTED OTHERWISE.
7. DUCT SEALING AND CONSTRUCTION TO MEET SMACNA AND ENERGY CODE REQUIREMENTS. UNLESS OTHERWISE NOTED, LOW PRESSURE DUCTWORK
(DOWNSTREAM OF VAV BOXES, CONSTANT VOLUME AC SYSTEMS, TOILET EXHAUSTS, ETC.) TO MEET 2" CONSTRUCTION STANDARDS WITH
SEAL CLASS C. MEDIUM PRESSURE DUCTWORK (UPSTREAM OF VAV BOXES, HIGH VELOCITY EXHAUSTS, ETC.) TO MEET 4" CONSTRUCTION STANDARDS
WITH SEAL CLASS A. DUCT RISERS IN SHAFTS WITH DAMPERED PENETRATIONS TO MEET 6" CONSTRUCTION STANDARDS WITH SEAL CLASS A.
8. ALL CEILING DIFFUSERS ARE 4 -WAY THROW UNLESS NOTED OTHERWISE.
9. ALL DUCT DIMENSIONS ARE CLEAR INSIDE DIMENSIONS AFTER LINING HAS BEEN ACCOUNTED FOR.
10. OUTSIDE AIR INTAKES ON ALL AIR HANDLING UNITS SHALL BE 10 FEET AWAY FROM ANY FUEL BURNING EQUIPMENT OR 3 FEET BELOW
ANY PLUMBING VENT OR EXHAUST OUTLET WITHIN 10 FEET
11. ALL AIR ECONOMIZERS SHALL BE CAPABLE OF THE FOLLOWING:
-0% TO 100% OF THE DESIGN SUPPLY AIR
-CONTROLLED BY A CONTROL SYSTEM DETERMINING IF THE OUTSIDE AIR CAN MEET PART OR ALL OF THE BUILDING COOLING LOADS.
-INTEGRATED TO PROVIDE PARTIAL COOLING EVEN WHEN MECHANICAL COOLING IS REQUIRED.
12. OUTSIDE AIR INTAKE, RELIEF, AND EXHAUST OPENINGS SHALL BE EQUIPPED WITH MOTORIZED (OR GRAVITY DAMPERS PER
EXCEPTIONS IN C403.2.4.4) WHICH CLOSE AUTOMATICALLY WHEN SYSTEM IS OFF OR UPON POWER FAILURE.
13. THE CONTROL SYSTEM SHALL BE 7 -DAY PROGRAMMABLE, CAPABLE OF BEING SET FOR SEVEN (7) DIFFERENT DAY TYPES PER WEEK,
AND CAPABLE OF A DEADBAND SETTING OF AT LEAST 57 (10'F FOR RESIDENTIAL BETWEEN THE HEATING AND COOLING SETPOINTS. AHU CONTROL
SYSTEM SHALL INCLUDE A MICROPROCESSOR AND BE CAPABLE OF RESETTING SU PLY AIR TEMPERATURES BY REPRESENTATIVE BUILDING LOADS.
14. RECORD DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDED TO THE BUILDING OWNER WITHIN 90 DAYS OF THE DATE
OF SYSTEM ACCEPTANCE PER THE WASHINGTON STATE ENERGY CODE. AN OPERATING MANUAL AND MAINTENANCE MANUAL
SHALL BE PROVIDED TO THE BUILDING OWNER. ALL HVAC SYSTEMS SHALL BE BALANCED AND A WRITTEN BALANCING REPORT
SHALL BE PROVIDED TO THE OWNER. HVAC CONTROL SYSTEMS SHALL BE TESTED TO ENSURE THAT THEY OPERATE IN ACCORDANCE
WITH APPROVED PLANS. A PRELIMINARY COMMISSIONING REPORT OF TEST PROCEDURES AND RESULTS SHALL
BE PREPARED PRIOR TO ISSUANCE OF A FINAL CERTIFICATE OF OCCUPANCY. A COMPLETE FINAL COMMISSIONING REPORT OF
TEST PROCEDURES AND RESULTS SHALL BE PROVIDED TO THE OWNER. COMMISSIONING, SYSTEM BALANCING, RECORD DRAWINGS
AS REQUIRED PER THE WASHINGTON STATE ENERGY CODE C408.
15. MECHANICAL SYSTEMS SHALL COMPLY WITH SEISMIC RESTRAINT REQUIREMENTS OF THE BUILDING CODE SMACNA AND ASCE 7. ALL LIFE
SAFETY OR HAZARDOUS MATERIAL RELATED SYSTEMS SHALL BE DEEMED AN Ip
-1.5 FOR RESTRAINT METHODS OR AS NOTED ON THE DRAWINGS.
REFER TO CODES FOR INSTALLATION REQUIREMENTS AND EXCEPTIONS BASED ON SIZING, WEIGHTS AND MOUNTING HEIGHTS.
16. PROVIDE EARTHQUAKE RESTRAINTS FOR HVAC EQUIPMENT AS REQUIRED BY SMACNA SEISMIC RESTRAINT MANUAL, SEISMIC HAZARD B.
WIRES FOR CEILING SYSTEM ETC. SHALL NOT BE HUNG OFF HVAC EQUIPMENT OR HVAC EQUIPMENT SUPPORTS.
17.
PROVIDE FIRE AND COMBINATION FIRE/SMOKE DAMPERS
WHERE
SHOWN ON
PLANS AND
WHERE REQUIRED PER CODE.
18.
ALL PIPING PENETRATIONS THROUGH RATED ASSEMBLIES
SHALL
BE SEALED
WITH AN UL
APPROVED FIRE CAULKING.
19. SMOKE DETECTORS PROVIDING AUTOMATIC SHUTDOWN SHALL BE
PROVIDED FOR HVAC EQUIPMENT DELIVERING
IN EXCESS OF
2000 CFM [INCLUDING MULTIPLE UNITS DUCTED INTO COMMON
DISTRIBUTION OR
RETURN, WITH AN AGGREGATE SUPPLY GREATER
THAN 2000 CFM]
OR EACH STORY OF RETURN SYSTEMS OVER
15,000 CFM IN A
MULTI -STORY INSTALLATION,
PER CODE.
SMOKE DETECTORS SHALL BE FIC (ELEC) UNO. POWER -WIRING
AND INTERLOCK
TO FIRE ALARM SYSTEM BY
ELECTRICAL CONTRACTOR AS APPLICABLE.
20. MECHANICAL ACCESS PANELS SHALL BE PROVIDED BY MECHANICAL CONTRACTOR
AND INSTALLED BY GENERAL
CONTRACTOR.
21. ALL MOTOR STARTERS NOT SHOWN IN EQUIPMENT SCHEDULES SHALL BE FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR.
MOTOR EFFICIENCIES TO MEET OR EXCEED CODE MINIMUM.
22. FOR ALL "SEALED AIR TIGHT" SHAFTS OR ROOMS, THE FOLLOWING SHALL OCCUR:
-ALL VERTICAL JOINTS & CORNERS INSIDE THE SHAFT SHALL BE PROVIDED WITH A CONTINUOUS SEAL FOR THE LENGTH OF THE JOINT, (BY GC).
-TOP AND BOTTOM WALL TRACKS SHOULD BE CAULKED ALONG THEIR ENTIRE LENGTH (BY GC).
-ANY FLOOR DECKING PERPENDICULAR TO THE SHAFT SHALL BE CAULKED (BY GC). )FILLING WITH ROCK WOOL IS NOT ACCEPTABLE
-USE SECTIONPENETRATIONS
T909.50OFTTHE52012 IBC FOR CMAX ALDLOWABOLEKLEAKAGE CONDUIT,
PIPING, LLOWINGATHEBGUIDEELLINESOFOROTIGHTDSTAIR SHAFT CONSTRUCTION.
-ALL DOORS SHALL BE PROVIDED WITH TIGHT FITTING GASKETS, AND OPEN AGAINST THE DIRECTION OF ROOM/SHAFT PRESSURE.
23. MAXIMUM LENGTH OF FLEXIBLE DUCT SHALL BE 12 FEET. REFER TO INSTALLATION DETAILS FOR SUPPORT REQUIREMENTS.
FLEXIBLE DUCT FLAME SPREAD RATING SHALL BE < 25 AND SMOKE DEVELOPED RATING SHALL BE < 50. USE FLEXIDUCT
MODEL G -KM FOR LOW AND MEDIUM PRESSURE APPLICATIONS OR APPROVED EQUAL.
24. LOCATION AND DETAILS OF EQUIPMENT DUCT ROUTING, AND CONNECTIONS ARE APPROXIMATE. COORDINATE FINAL LOCATIONS WITH
OTHER TRADES. INSTALL IN ACCORDANOE WITH APPROVED SUBMITTALS AND DETAIL DRAWINGS WHEN APPLICABLE.
25. FOR RESIDENTIAL INSULATION ON DUCTWORK AND PIPING SEE ENERGY CODE CHAPTER R403.
26. ELECTRICAL METERING OF SYSTEMS AS REQUIRED BY ENERGY CODE SECTION C409 IS BY ELECTRICAL. THE ELECTRICAL DESIGN & CONTRACTOR TEAM
WILL FURNISH THE NECESSARY ELECTRICAL DISTRIBUTION AND METERING COMPONENTS - SEE ELECTRICAL DRAWINGS. THE MECHANICAL CONTRACTOR
WILL FURNISH A BUILDING MANAGEMENT SYSTEM CAPABLE OF COLLECTING AND STORING THE INFORMATION. A PERMANENT AND VISIBLE DISPLAY IS
TO BE PROVIDED FOR EACH BUILDING, READILY ACCESSIBLE TO OPERATION AND MANAGEMENT PERSONNEL
MINIMUMCT INSULATION LAST UPDATED 01/10/14
DUCT TYPE
DUCT LOCATION IN HEATED AND MECHANICALLY COOLED DUCT SYSTEM
INSULATION
R -VALUE
REMARKS
SUPPLY & RETURN
NOT WITHIN CONDITIONED SPACE, OUTSIDE BUILDING
R-8
1,2,3
OUTSIDE AIR
WITHIN CONDITIONED SPACE, INSIDE BUILDING
SEE NOTES 4 & 5
1,2,3,4,5
SUPPLY & RETURN
NOT WITHIN CONDITIONED SPACE: INSIDE BUILDING
R-6
1,2
SUPPLY AIR
<550 OR >1050
WITHIN CONDITIONED SPACE
R-3.3
1,2
1 KUFtK I U tNtKbY (UUt Stl. 11UN lffU3.L./ 1 -UK I -UK I ntK KtL2U1KtIvICIV 1 J
2 INSULATED COOLED DUCTS REQUIRED A VAPOR RETARDER (PERM < 0.5) AND SEALED JOINTS
3 WEATHERPROOF BARRIER REQUIRED AROUND DUCTWORK TO MAINTAIN WATER TIGHTNESS
4 INSULATE OUTSIDE AIR DUCTS TO BUILDING EXTERIOR WALL LEVEL PER ENERGY CODE SECTION: C403.2.7.1 UNTIL
CONNECTED TO EQUIPMENT SERVED OR TO THE CODE REQUIRED SHUTOFF DAMPER (THEN R-6 FOR REST OF
INSTALLATION) OR HEATING & COOLING EQUIPMENT
5 R-7 CAN BE USED IN LIEU OF BUILDING ENVELOPE INSULATION LEVEL IF:
DEDICATED OUTSIDE AIR SYSTEM AND LESS THAN 2,800 CFM SUPPLY AIR
MINIMUMI E INSULATION LAST UPDATED: 01/10/14
FLUID DESIGN
INSULATION CONDUCTIVITY NOMINAL PIPE DIAMETER (INCH)
OPERATING
TEMP °F
CONDUCTIVITY
RANGE
MEAN TEMP
RATING °F <1
1 TO
<1-1/2
1-1/2TO
<4
4 TO
<8
>8
HEATING SYSTEMS (STEAM, CONDENSATE, HYDRONIC HOT WATER, DOMESTIC HOT WATER)
>350 0.32-0.34 250 4.5 5.0 5.0 5.0 5.0
251-350 0.29-0.32 200 3.0 4.0 4.5 4.5 4.5
201-250 0.27-0.30 150 2.5 2.5 2.5 3.0 3.0
141-200 0.25-0.29 125 1.5 1.5 2.0 2.0 2.0
105-140 0.21-0.28 100 1.0 1.0 1.5 1 1.5 1.5
DOMESTIC COLD WATER AND HORIZONTAL RAIN LEADERS TO FIRST VERTICAL RAIN LEADER
40-60 1 0.21-0.27 1 75 1 0.5 1 0.5 1 1.0 1.0 1.0
COOLING SYSTEMS (CHILLED WATER, BRINE AND REFRIGERANT, WATERSIDE ECONOMIZER SYSTEMS)**
40-60
0.21-0.27
75 0.5
1 0.5 1.0
1 1.0
1.0
<40
0.20-0.26
75 0.5
1 1.0 1.0
1 1.0
1.5
NOT RLQUIRLD FOR 51 KA1NtK5, WN I KUL VALVtb & bALANLANC3 VALvtJ AJ'ULIA I tU vvi 1 n rlriimu 1.. UK Lc.)� IN Ulm.
** TYPICAL CONDENSER WATER PIPE IN NON -ECONOMIZER SYSTEMS DOES NOT REQUIRE INSULATION
o ftft, MW/0011
Plan reviaW -Ap 7) wt.! i_ subject to errors and omsiorm.
A�rovai Cii�r1rP'?;['i)r; d� llft3tn$�t 91�4tiE:`ifc? i_3
the vioisticn of airy adoWiadt codin or Rct "Pt
of approvs , Fold Copy and Condi; id is e' lcklnt;:�vicd,,, r.:. :
mte:
0923049120
LEGAL DESCRIPTION
BEGIN NW CORNER OF NE 1/4 OF SE 1/4 TH S 89-16-35 E 100 FT TH S
24-13-53 E 969.61 FT TO POINT OF BEGINNING TH N 65-46-07 E 58.17
FT TH N 63-32-48 E 62.13 FT TH S 22-47-01 E 21.44 FT TH N
65-30-25 E 199.33 FT TO POINT ON WLY R/W LINE OF PRIMARY STATE
HIGHWAY NO 1 (SR 99) SOUTH 118TH ST TO JCT SSH NO 1-K APPROVED
JULY 23, 1957 TH FOLLOWING SAID WLY R/W LINE ALONG ARC OF 2805 FOOT
RADIUS NON TANGENT CURVE TO RIGHT, CENTER BEARING S 65-44-51 W,
THRU C/A OF 1-16-30 DISTANCE OF 62.42 FT TH FOLLOWING SAID WLY R/W
LINE N 67-01-21 E 10 FT TH FOLLOWING SAID WLY R/W LINE ALONG ARC
OF 2815 FOOET RADIUS NON TANGENT CURVE TO RIGHT CENTER BEARING S
67-01-21 W THRU C/A OF 6-31-21 DISTANCE OF 320.45 FT TH S
73-32-42 W 16.58 FT TH S 71-35-51 W 61.96 FT TH N 78-38-58 W
7.83 FT TH S 75-53-44 W 106.07 FT TH N 05-01-10 W 18.41 FT TH S
82-22-27 W 64.93 FT TH S 63-55-24 W 58.16 FT TH N 24-13-53 W
334.22 FT TO POINT OF BEGINNING - LOT B OF CITY OF TUKWILA BOUNDARY
LINE ADJUSTMENT NO L98-0033 RECORDING NO 9810059013
SITE MAP
NO SCALE
ISSUE FOR PERMIT
Building Today, Defining Tomorrow
Hermanson Company LLP
1221 2nd Avenue North
Kent, Washington 98032
Tel: (206) 575-9700
Fax: (206) 575-9800
www.hermanson.com
Contractor Reg #: HERMACL0056J
IGW BLDG B
SUITE 140 TI
12201 TUKWILA INTERNATIONAL BLVD
TUKWILA, WA 98168
REVVIStotvs
Reo changes shalt I-, rad' to the scope
of work withr : r print arprov2f of
T�-►•'t^�;ra Gz,�}:.lir:;f t�i,,sic�~�
f'�t.� s __..:��•,� +':.:,nisi �:: ;;, � r,..t :;.:a s• � i �,
M
Revisions
01/22/16 MIG ISSUE FOR PERMIT
Date By Description
Design Team
Design MIG
Drawn FVP
Checked DTN
Scale AS NOTED
Drawing Number C-0582-07156
Project Number 11-16-07156
Issue Date 01/22/16
LEGEND, ABBREVIATIONS,
GENERAL NOTES & SHEET
INDEX -HVAC
REVI:EVVED FOR
RECEIVED PODE COMPLIANCE
CITY OF TUINVWILA I APPROVED
PERMIT CENTERCity of Tukwila
BUILDING DIVISION
DRAWING INDEX
SHEET NO.
SHEET TITLE CURRENT
REVISION
MO.00
LEGEND ABBREVIATIONS GENERAL NOTES & SHEET INDEX - HVAC
M2.01 D
PARTIAL 1ST FLOOR DEMO PLAN - HVAC
M2.01
PARTIAL 1 ST FLOOR PLAN - HVAC
o ftft, MW/0011
Plan reviaW -Ap 7) wt.! i_ subject to errors and omsiorm.
A�rovai Cii�r1rP'?;['i)r; d� llft3tn$�t 91�4tiE:`ifc? i_3
the vioisticn of airy adoWiadt codin or Rct "Pt
of approvs , Fold Copy and Condi; id is e' lcklnt;:�vicd,,, r.:. :
mte:
0923049120
LEGAL DESCRIPTION
BEGIN NW CORNER OF NE 1/4 OF SE 1/4 TH S 89-16-35 E 100 FT TH S
24-13-53 E 969.61 FT TO POINT OF BEGINNING TH N 65-46-07 E 58.17
FT TH N 63-32-48 E 62.13 FT TH S 22-47-01 E 21.44 FT TH N
65-30-25 E 199.33 FT TO POINT ON WLY R/W LINE OF PRIMARY STATE
HIGHWAY NO 1 (SR 99) SOUTH 118TH ST TO JCT SSH NO 1-K APPROVED
JULY 23, 1957 TH FOLLOWING SAID WLY R/W LINE ALONG ARC OF 2805 FOOT
RADIUS NON TANGENT CURVE TO RIGHT, CENTER BEARING S 65-44-51 W,
THRU C/A OF 1-16-30 DISTANCE OF 62.42 FT TH FOLLOWING SAID WLY R/W
LINE N 67-01-21 E 10 FT TH FOLLOWING SAID WLY R/W LINE ALONG ARC
OF 2815 FOOET RADIUS NON TANGENT CURVE TO RIGHT CENTER BEARING S
67-01-21 W THRU C/A OF 6-31-21 DISTANCE OF 320.45 FT TH S
73-32-42 W 16.58 FT TH S 71-35-51 W 61.96 FT TH N 78-38-58 W
7.83 FT TH S 75-53-44 W 106.07 FT TH N 05-01-10 W 18.41 FT TH S
82-22-27 W 64.93 FT TH S 63-55-24 W 58.16 FT TH N 24-13-53 W
334.22 FT TO POINT OF BEGINNING - LOT B OF CITY OF TUKWILA BOUNDARY
LINE ADJUSTMENT NO L98-0033 RECORDING NO 9810059013
SITE MAP
NO SCALE
ISSUE FOR PERMIT
Building Today, Defining Tomorrow
Hermanson Company LLP
1221 2nd Avenue North
Kent, Washington 98032
Tel: (206) 575-9700
Fax: (206) 575-9800
www.hermanson.com
Contractor Reg #: HERMACL0056J
IGW BLDG B
SUITE 140 TI
12201 TUKWILA INTERNATIONAL BLVD
TUKWILA, WA 98168
REVVIStotvs
Reo changes shalt I-, rad' to the scope
of work withr : r print arprov2f of
T�-►•'t^�;ra Gz,�}:.lir:;f t�i,,sic�~�
f'�t.� s __..:��•,� +':.:,nisi �:: ;;, � r,..t :;.:a s• � i �,
M
Revisions
01/22/16 MIG ISSUE FOR PERMIT
Date By Description
Design Team
Design MIG
Drawn FVP
Checked DTN
Scale AS NOTED
Drawing Number C-0582-07156
Project Number 11-16-07156
Issue Date 01/22/16
LEGEND, ABBREVIATIONS,
GENERAL NOTES & SHEET
INDEX -HVAC
REVI:EVVED FOR
RECEIVED PODE COMPLIANCE
CITY OF TUINVWILA I APPROVED
PERMIT CENTERCity of Tukwila
BUILDING DIVISION
M
M
d�
MAIV
0
ti PARTIAL
o SCALE: 1/8" = 1'-0"
N
da
1ST FLOOR DEMO PLAN - HVAC
AIREA 00 WORK ? S i T i
2 R M A /S
0
y KEY PLAN
SCALE: NONE
d �
A N d
a
R CEIV`:D
CITY OF TUKWILA
JAN 2 6 2016
RERiT CENTER
ISSUE FOR PERMIT
Hermanson Company LLP
1221 2nd Avenue North
Kent, Washington 98032
Tel: (206) 575-9700
Fax: (206) 575-9800
www.hermanson.com
Contractor Reg #: HERMACL0056J
IGW BLDG B
SUITE 140 TI
12201 TUKWILA INTERNATIONAL BLVD
TUKWILA, WA 98168
Revisions
01/22/16 MIG ISSUE FOR PERMIT
No. Date By Description
Design Team
Design MIG
Drawn FVP
Checked DTN
Scale AS NOTED
Drawing Number C-0582-07156
Project Number 11-16-07156
Issue Date 01/22/16
PARTIAL
1ST FLOOR DEMO PLAN
- HVAC
REAWED FOR
¢QDE COMPLIANCE
APPRQY D
City of Tukwila
BUILDING DIVISION
\6/
(e'� --- —
N
AREA OF1, WOW
T
RECI--IV=D
CITY OF TUKA!ILA
JAN 26 216
PERMIT CENTER
ISSUE FOR PERMIT
Building Today, Defining Tomorrow
Hermanson Company LLP
1221 2nd Avenue North
Kent, Washington 98032
Tel: (206) 575-9700
Fax: (206) 575-9800
www.hermanson.com
Contractor Reg J: HERMACL005BJ
Revisions
01/22/16 MIG ISSUE FOR PERMIT
No. Date By Description
Drawing Number C-0582-07156
Project Number 11-16-07156
Issue Date 01/22/16
PARTIAL 1ST FLOOR PLAN
- HVAC
REVfEWED FOR
ODE COMPLIANCE
APPROVED
LCity of Tukwila
BUDIVISION
M2.01