HomeMy WebLinkAboutPermit M16-0085 - SANFORD BROWN COLLEGE - DIFFUSERS AND EXHAUST FAN IN BREAKROOMSANFORD BROWN COLLEG �-j EXPIRED 12/07/16 M16-0085 City of Tukwila Department of Community Development • 6300 Southcenter Boulevard, Suite #100 Tukwila, Washington 98188 Phone: 206-431-3670 Inspection Request Line: 206-438-9350 Web site: http://www.TukwilaWA.gov MECHANICAL PERMIT Parcel No: 2623049143 Permit Number: M16-0085 Address: 645 ANDOVER PARK W Issue Date: 6/6/2016 WA Cities Electrical Code: 2014 Permit Expires On: 12/3/2016 Project Name: SANFORD BROWN COLLEGE 2014 Owner: 2012 WA State Energy Code: Name: SOUTHCENTER CORPORATE SQUAR 2012 Address: 150 CALIFORNIA ST, SAN FRANCISCO, WA, 94111 Contact Person: Name: CONNIE HARDIN Phone: (206) 250-4530 Address: 4600 S 134 PL, SEATTLE, WA, 98168 Contractor: Name: HOLADAY PARKS INC Phone: (206) 248-9700 Address: 4600 S 134 PL, SEATTLE, WA, 98168 License No: HOLADPI379NO Expiration Date: 9/3/2017 Lender: Name: Address: DESCRIPTION OF WORK: RELOCATING (3) DIFFUSERS. INSTALL (1) INLINE EXHAUST FAN IN BREAK -ROOM Valuation of Work: $2,500.00 Fees Collected: $233.88 Type of Work: NEW Electrical Service Provided by: PUGEST SOUND ENERGY Fuel type: ELECT Water District: TUKWILA Sewer District: TUKWILA Current Codes adopted by the City of Tukwila: International Building Code Edition: 2012 National Electrical Code: 2014 International Residential Code Edition: 2012 WA Cities Electrical Code: 2014 International Mechanical Code Edition: 2012 WAC 296-466: 2014 Uniform Plumbing Code Edition: 2012 WA State Energy Code: 2012 International Fuel Gas Code: 2012 Permit Center Authorized Signature: Date: I hearby certify that I have read and examined this permit and know the same to be true and correct. All provisions of law and ordinances governing this work will be complied with, whether specified herein or not. The granting of this permit does not presume to give authority to violate or cancel the provisions of any other state or local/laws regul ting construction or the performance of work. I am authorized to sign and obtain this development pe', An agre A ithe condi 'ons attached to this permit. (0— L(e5::' Signature: Date: nr Print Name: D This permit shall become null and void if the work is not commenced within 180 days for the date of issuance, or if the work is suspended or abandoned for a period of 180 days from the last inspection. PERMIT CONDITIONS: 1: ***BUILDING PERMIT CONDITIONS*** 2: Work shall be installed in accordance with the approved construction documents, and any changes made during construction that are not in accordance with the approved construction documents shall be resubmitted for approval. 3: All permits, inspection record card and approved construction documents shall be kept at the site of work and shall be open to inspection by the Building Inspector until final inspection approval is granted. 4: Readily accessible access to roof mounted equipment is required. 5: All construction shall be done in conformance with the Washington State Building Code and the Washington State Energy Code. 6: All plumbing and gas piping work shall be inspected and approved under a separate permit issued by the City of Tukwila Building Department (206-431-3670). 7: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila Permit Center. 8: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, any violation of any of the provisions of the building code or of any other ordinances of the City of Tukwila. Permits presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the Building Official from requiring the correction of errors in the construction documents and other data. 9: ***MECHANICAL PERMIT CONDITIONS*** 10: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila Permit Center (206/431-3670). 11: Manufacturers installation instructions shall be available on the job site at the time of inspection. PERMIT INSPECTIONS REQUIRED Permit Inspection Line: (206) 438-9350 1800 MECHANICAL FINAL 0701 ROUGH -IN MECHANICAL V7 01 b c(;.v ke%-oP 4m4x).-, Com, CITY OF TUKWILA Community Development Department Mechanical Permit No. Permit Center • 6300 Southcenter Blvd., Suite 100 Project No. Tukwila, WA 98188 Date Application Accepted: http://www.TukwilaWA.eov MECHANICAL PERMIT APPLICATION Ab—COK- 40 Date Application Expires: For oece use only) Applications and plans must be complete in order to be accepted for plan review. Applications will not be accepted through the mail or by fax. **please print** SITE LOCATION ?,a King Co Assessor's Tax No.:Site Address: tiSu umber: Floor: Tenant Name: New Tenant: ❑ .....Yes �No PROPERTY OWNER c i7F L - p� State Zip:. MECHANICAL CONTRACTOR INFORMATION Company Name: Addre City' State Zip Phone;*_ _ "D Fax:.... 1 Valuation of project (contractor's bid price): $ Describe the scope of work in detail: 3 Indicate type of mechanical work being installed and the quantity below: Unit Type Qty Furnace <100k btu Residential, Nighttime Furnace >100k btu Residential Floor furnace 45 dB(A) Suspended/wall/floor mounted heater Commercial Appliance vent 47 dB(A) Repair or addition to heat/refrig/cooling system Industrial Air handling unit <10,000 cfm 50 dB(A) Unit Type Qty Air handling unit >10,000 cfin Residential, Nighttime Evaporator cooler Residential Ventilation fan connected to single duct 45 dB(A) Ventilation system Commercial Hood and duct 47 dB(A) Incinerator — domestic Industrial Incinerator — comm/industrial 50 dB(A) Unit Type Qty Fire damper Diffuser Thermostat Wood/gas stove Emergency enerator Other mechanical equipment 1 Boiler/Compressor Qty 0-3 hp/100,000 btu 3-15 hp/500,000 btu 15-30 hp/1,000,000 btu 30-50 hp/1,750,000 btu 50+ hp/1,750,000 btu Noise: Mechanical units need to be in compliance with the Tukwila Noise Code. Maximum permissible sound levels are based on from where the sound is created and where the sound is heard. Additionally, if sound can be heard from within a house at night in a residential zone it may not be allowed. For more details, see TMC 8.22 District of Sound Producing Source District of Receiving Property Residential, Daytime* Residential, Nighttime Commercial Industrial Residential 55 dB(A) 45 dB(A) 57 dB(A) 60 dB(A) Commercial 57 dB(A) 47 dB(A) 60 dB(A) 65 dB(A) Industrial 60 dB(A) 50 dB(A) 65 dB(A) 70 dB(A) *Daytime means 7AM-1 OPM, Monday through Friday and 8AM-I OPM, Saturday, Sunday and State -recognized holidays. A few sounds are exempt from the noise code, including: Warning devices; Construction and property maintenance during the daytime hours (lam -I Opm); Testing of backup generators during the day. PERMIT APPLICATION NOTES - Value of construction — in all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the permit center to comply with current fee schedules. Expiration of plan review — applications for which no permit is issued within 180 days following the date of application shall expire by limitation. The building official may grant one extension of time for additional periods not to exceed 90 days each. The extension shall be requested in writing and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition). I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILDING Signature:_ Print Name Mailing Add H:1Applicatiora\Forns-Applications On Line\2016 ApplicationsWechanical Permit Application Revised 14-16.docx Revised: January 2016 bh City State zip J Page 2 of 2 DESCRIPTIONS PermitTRAK ACCOUNT QUANTITY PAID $233.88 M16-0085 Address: 645 ANDOVER PARK W Apn: 2623049143 $233.88 MECHANICAL $224.88 PERMIT ISSUANCE BASE FEE R000.322.100.00.00 0.00 $32.50 PERMIT FEE R000.322.100.00.00 0.00 $147.40 PLAN CHECK FEE R000.322.102.00.00 0.00 $44.98 TECHNOLOGY FEE $9.00 TECHNOLOGY FEE TOTAL FEES PAID BY RECEIPT: R8557 R000.322.900.04.00 0.00 $9.00 $233.88 Date Paid: Tuesday, May 24, 2016 Paid By: CONNIE HARDIN Pay Method: CREDIT CARD 00198G Printed: Tuesday, May 24, 2016 2:20 PM 1 of 1 SYSTEMS 2 INSPECTION RECORD Retain a copy with permit AX -W -s- INSPECTION NO. PERMIT NO. CITY OF TUKWILA BUILDING DIVISION 6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670 Permit Inspection Request Line (206) 438-9350 PTj' k Typ f Inspe ion: o A Ad ru— / Date Calle Special Instructions: V' l3'� U' � Date Wanted: a.m. 6 flo p.m. Requq ter: Phone No: 56 o Lf Z Inspector: Datej e i REINSPECTION FEE REQUIRED. Prior to next inspection. fee must be paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection. 11/1/2016 City of Tukwila Allan Ekberg, Mayor Department of Community Development Jack Pace, Director CONNIE HARDIN 4600 S 134 PL SEATTLE, WA 98168 RE: Permit No. M16-0085 SANFORD BROWN COLLEGE 645 ANDOVER PARK W Dear Permit Holder: In reviewing our current records, the above noted permit has not received a final inspection by the City of Tukwila Building Division. Per the International Building Code, International Mechanical Code, Uniform Plumbing Code and/or the National Electric Code, every permit issued by the Building Division under the provisions of these codes shall expire by limitation and become null and void if the building or work authorized by such permit has not begun within 180 days from the issuance date of such permit, or if the building or work authorized by such permit is suspended or abandoned at any time after the work has begun for a period of 180 days. Your permit will expire on 12/7/2016. Based on the above, you are hereby advised to: 1) Call the City of Tukwila Inspection Request Line at 206-438-9350 to schedule for the next or final inspection. Each inspection creates a new 180 day period, provided the inspection shows progress. -or- 2) Submit a written request for permit extension to the Permit Center at least seven(7) days before it is due to expire. Address your extension request to the Building Official and state your reason(s) for the need to extend your permit. The Building Code does allow the Building Official to approve one extension of up to 180 days. If it is determined that your extension request is granted, you will be notified by mail. In the event you do not call for an inspection and/or receive an extension prior to 12/7/2016, your permit will become null and void and any further work on the project will require a new permit and associated fees. Thank you for your cooperation in this matter. Sincerely, Bill Rambo Permit Technician File No: M 16-0085 6300 Southcenter Boulevard Suite #100 • Tukwila, Washington. 98188 • Phone 206-431-3670 • Fax 206-431-3665 PERMIT COORD COPY PLAN REVIEW/ROUTING SLIP PERMIT NUMBER: M16-0085 DATE: 05/24/16 PROJECT NAME: SANFORD BROWN COLLEGE SITE ADDRESS: 645 ANDOVER PARK W X Original Plan Submittal Response to Correction Letter # DEPARTMENTS: Al . iwc., 5-uo'14 Building Division IR Public Works ❑ PRELIMINARY REVIEW: Not Applicable ❑ (no approval/review required) REVIEWER'S INITIALS: APPROVALS OR CORRECTIONS: Approved ❑ Corrections Required ❑ (corrections entered in Reviews) Notation: REVIEWER'S INITIALS: Revision # before Permit Issued Revision # after Permit Issued Fire Prevention Structural ❑ Planning Division ❑ Permit Coordinator K DATE: 05/26/16 Structural Review Required ❑ DATE: DUE DATE: 06/23/16 Approved with Conditions d Denied ❑ (ie: Zoning Issues) DATE: Permit Center Use Only CORRECTION LETTER MAILED: Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials: 12/18/2013 HOLADAY PARKS INC Home Espanol Contact Safety & Health Claims & Insurance 4 'Washington State Department of IlU Labor & Industries HOLADAY PARKS INC Owner or tradesperson 4600 S 134TH PL BECK, DAVID CARL SEATTLE, WA 98168 206-248-9700 Principals KING County BECK, DAVID CARL, PRESIDENT CONNELL, DANIEL A, PRESIDENT GIRI, BIJIT, PRESIDENT PIZZEY, GRACE K, VICE PRESIDENT FREEL, JERRY LEE, VICE PRESIDENT PARKS, GERALD T JR, PRESIDENT (End: 08/12/2015) NAILON, JUNE ANNETTE, VICE PRESIDENT (End: 08/12/2015) O'CONNOR, BONNY K, SECRETARY (End: 08/12/2015) BECK, DAVID CLARENCE, TREASURER (End: 08/12/2015) VAN DER VEEN, ERIC M; VICE PRESIDENT (End: 08/14/2013) PIZZEY, GRACE KATHERINE, VICE PRESIDENT (End: 08/14/2013) VAN DER VEEN, JULIE ELIZABETH, MEMBER (End: 08/14/2013) CONNELL, DANIEL AARON, MEMBER (End: 08/14/2013) GIRI, BUTT, MEMBER (End: 08/14/2013) KIEL, RINALD HOWARD, MEMBER (End: 08/14/2013) WHITMYRE, CHRISTIAN, MEMBER (End: 08/14/2013) NELSON, MICHAEL, SECRETARY (End: 11/04/2010) PARKS, DAVID L, TREASURER (End: 11/04/2010) TALBOT, PAUL, TREASURER (End: 11/04/2010) WA UBI No. Business type 578 004 089 Corporation Page I of 3 Search L&I _____ 1 A -'Z Index Help My LSI Workplace Rights Trades & Licensing https://secure.Ini.wa.gov/verify/Detail.aspx?UBI=578004089&LIC=HOLADPI379NO&SAW= 6/6/2016 HOLADAY PARKS INC I License Verify the contractor's active registration / license / certification (depending on trade) and any past violations. Construt ...................... _.........ction..........Contrac................................or Active. Meets current requirements. License specialties GENERAL $1,000,000.00 License no. HOLADPI379NO Effective — expiration Effective date 01/21/1983— 09/03/2017 11/01/2015 Bond ................. Expiration date LIBERTY MUTUAL INS CO $12,000.00 Bond account no. 23000452 Received by L&I Effective date 08/23/2002 09/01/2002 Expiration date Until Canceled I....n.s....u.ra.nce... ................ Charter Oak Fire Ins Co $1,000,000.00 Policy no. DTC01 F465357PHX15 Received by L&I Effective date 10/30/2015 11/01/2015 Expiration date 11/01/2016 Insurance history Savings No savings accounts during the previous 6 year period. Lawsuits against the bond or savings No lawsuits against the bond or savings accounts during the previous 6 year period. L&I Tax debts No Uf tax'debts are recorded for this contractor license during the previous 6 year period, but some debts may be recorded by other agencies. License Violations ........................................................ No license violations during the previous 6 year period. Workers' comp Do you know if the business has employees? If so, verify the business is up-to-date on workers' comp premiums. L&I Account ID Account is current. 177,231-00 ................................. Doing business as HOLADAY PARKS INC Estimated workers reported Quarter 1 of Year 2016 "Greater than 100 Workers" L&I account representative T4 / CARIE PICKETT (360)902-5592 - Email: PICC235@lni.wa.gov Workplace safety and health Check for any past safety and health violations found on jobsites this business was responsible for. Inspection results date 05/05/2016 Inspection no. 317940156 Location 4600 S 134th PI Tukwila, WA 98168 No violations Page 2 of 3 https:Hsecure.lni.wa.gov/verify/Detail.aspx?UBI=578004089&LIC=HOLADPI379NO&SAW= 6/6/2016 HOLADAY PARKS INC Page 3 of 3 Inspection results date No violations 06/11/2014 Inspection no. 317319382 Location 1011 Dexter Ave Seattle, WA 98102 Inspection results date 05/08/2014 No violations Inspection no. 317278497 Location 2nd and 110th Ave Bellevue, WA 98004 .. ........ Inspection results date Violations iolations Inspection no. 316256841 Location 3003 W Casino Rd Everett, WA 98204 0, Washington State Dept. of Labor & industries. Use of this site is subject to the laws of the state of Washington. https:Hsecure.Ini.wa.gov/verify/Detail.aspx?UBI=578004089&LIC=HOLADPI379NO&SAW= 6/6/2016 GENERAL NOTES 1. THESE DOCUMENTS ARE BASED ON HOLADAY PARKS ENGINEERING AND SHOP FABRICATION STANDARDS, SMACNA DUCT CONSTRUCTION STANDARDS, AND APPLICABLE LOCAL AND STATE CODES WHICH ARE NOT SHOWN/ IN DETAIL ON THESE DRAWINGS. VARIATION FROM THESE PLANS REQUIRES NOTIFICATION OF HDLADAY-PARKS ENGINEERING DEPARTMENT 2. ALL TRADES SHALL LEAVE A MINIMUM OF 36" CLEARANCE IN FRONT OF MECHANICAL EQUIPMENT ACCESS PANELS FOR SERVICING. ACCESS PALLS THAT CONTAIN LINE VOLTAGE POWER (120 VOLT AND GREATER) SHALL HAVE A MINIMUM OF 42' CLEARANCE IN FRONT OF THE ACCESS PANEL AND A MINIMUM OF THE ACCESS PAM. WIDTH CLEAR FROM OBSTRUCTIONS AS REQUIRED BY STATE AND LOCAL ELECTRICAL CODES. 3. CUTTING, FRAMING, PATCHING AND PAINTING OF WALL, CEILING AND FLOOR OPENINGS, AS REQUIRED BY THESE MECHANICAL PLANS, SHALL BE BY THE GENERAL CONTRACTOR. 4. ROOF CURBS, FLASHINGS, SLEEPERS, PITCH POCKETS, CUTTING AND PATCHING OF ROOF OPENINGS, ROOFING, AND ROOF INSULATION SHALL BE BY THE GENERAL CONTRACTOR 5. ROOF CURBS, SLEEPERS, CANT STRIPS, ROOFING, AND ROOF INSULATION SHALL BE PROVIDED AND INSTALLED BY THE GENERAL CONTRACTOR, CURBS ARE TO BE CONSTRUCTED ACCORDING TO THE SIZES PROVIDED BY HOLADAY-PARKS' FIELD FOREMEN AND/OR AS SHOWN ON THE MECHANICAL PLANS. THE ROOF CURBS SHALL BE SHIMMED AS REQUIRED TO MAKE ROOF CURBS AND/OR SLEEPERS LEVEL TOP OF CURBS MUST BE TRUE (FLAT) TO PROVIDE AN ACCEPTABLE SEALING SURFACE THE MAXIMUM ALLOWABLE DEVIATION FROM LEVEL OR FLAT SHALL BE 1/4N IN 10'. ROOF CURBS APIA SLEEPERS MUST BE SECURELY FASTENED TO STRUCTURAL SUPPORT MEMBERS BY THE GENERAL CONTRACTOR. 6. PAINTING OF GRILLES, REGISTERS, AND DFFUSERS, AS MAY BE REQUIRED BY ARCHITECT OR OWNER, SHALL BE DONE BY THE GENERAL CONTRACTOR. 7. CARRY-OVER PERFORMANCE EQUAL TO OR BETTER THAN THE LOUVERS SPECIFIED IN ME MECHANICAL PLANS. 8. EQUIPMENT, DUCTS, AND PIPING WEIGHTS AND LOCATIONS HAVE BEEN COORDINATED WITH ARCHITECT, STRUCTURAL ENGINEER, AND GENERAL CONTRACTOR IN ORDER TO DETERMINE BUILDING STRUCTURAL ADEQUACY. IF IT IS NECESSARY TO RELOCATE EQUIPMENT, DUCTS, OR PIPING, NOTIFY HOLADAY-PARKS' ENGINEERING DEPARTMENT FOR ASSISTANCE IN RE -COORDINATION. 9.- IN NO INSTANCE SHALL OTHER CONTRACTORS HANG OR SUPPORT EQUIPMENT, CEILING WIRES, LIGHT FIXTURE HANGERS, ETC..., FROM HVAC EQUIPMENT, OR DUCTS, OR PIPING. ELECTRICAL COORDINATION NOTES 1. LINE VOLTAGE (120 VOLT AND ABOVE) WIRING FOR MECHANICAL EQUIPMENT SHALL BE PROVIDED AND INSTALLED BY THE ELECTRICAL CONTRACTOR. LOW VOLTAGE (LESS THAN 120 VOLT) WIRING FOR MECHANICAL EQUIPMENT AND DDC SYSTEMS SHALL BE PROVIDED BY THE CONTROLS CONTRACTOR. REFRIGERATION PIPING NOTES 1. INSTALLATION OF REFRIGERANT PIPING SHALL BE IN ACCORDANCE WITH THE 2012 INTERNATIONAL MECHANICAL CODE (IMC) AND LOCAL CODES AND STANDARDS. 2. INSTALLATION OF LISTED AND LABELED FACTORY BUILT EQUIPMENT AND APPLIANCES SHALL BE PER THE MANUFACTURER'S INSTALLATION REQUIREMENTS. INSTALLATION OF REFRIGERANT PIPING SERVING LISTED AND LABELED FACTORY BUILT EQUIPMENT SHALL BE PER THE MANUFACTURER'S INSTALLATION REQUIREMENTS, REFRIGERANT PIPE SIZE SHALL BE NO LESS THAN THAT REQUIRED BY THE MANUFACTURER'S INSTALLATION REQUIREMENTS AND AS REQUIRED FOR THE INSTALLED LENGTH OF PIPE AND THE LOCATION OF THE EQUIPMENT. 3. REFRIGERANT PIPING SHALL BE EITHER SEAMLESS TYPE 'L' DRAWN COPPER TUBING IN ACCORDANCE WITH ASTM B88 OR SEAMLESS COPPER ACR TUBING IN ACCORDANCE WITH ASTM B280. REFRIGERANT PIPE FITTINGS SHALL BE WROUGHT COPPER WITH SILVER -SOLDERED OR BRAZED JOINTS. 4. PENETRATIONS THROUGH FIRE AND/OR SMOKE RATED WALLS, FLOORS, AND CEILINGS SHALL BE PROTECTED IN ACCORDANCE WITH THE 2012 SEATTLE BUILDING CODE (SBC) AND THE 2012 SMC. PROTECTION, AS REQUIRED, SHALL BE PROVIDED AND INSTALLED BY THE PIPING CONTRACTOR. 5. REFRIGERANT PIPING INSULATION THICKNESS SHALL BE BASED ON NOMINAL PIPE DIAMETER AND OPERATING TEMPERATURE RANGE IN ACCORDANCE WITH TABLE C403.2.8. IN THE 2012 SEATTLE ENERGY CODE (SEC). THE PIPE INSULATION MATERIAL SHALL BE PREFORMED ELASTOMERIC INSULATION, "ARMAFLEX', 'RUBATM OR APPROVED EQUAL WITH A CONDUCTIVITY VALUE EQUAL TO OR BETTER THAN THE VAULES LISTED IN TABLE C403.2.8 OF THE 2012 SEC. ALL REFRIGERANT PIPE LOCATED OUTSIDE THE BUILDING SHALL BE INSULATED. ALL REFRIGERANT PIPE INSULATION EXPOSED TO WEATHER SHALL HAVE UV PROTECTION OR SHALL HAVE A PROTECTIVE JACKET TO PREVENT UV DAMAGE IN ACCORDANCE WITH SECTION C403.2.8.1 OF THE SEC. 6. REFRIGERANT PIPING THAT IS PART OF A FIELD ERECTED REFRIGERANT SYSTEM SHALL BE PRESSURE TESTED IN ACCORDANCE WITH THE 2012 SMC. REFRIGERANT PIPING INSTALLED AS PART OF FACTORY BUILT LISTED AND LABELED EQUIPMENT OR APPLIANCES SHALL BE PRESSURE TESTED IN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS. GRILLES, REGISTERS, DIFFERS LEGEND ABBREVIATIONS (MECHANICAL) /W WITH WRAP (DUCT INSULATION) HRWS HEAT RECOVERY WATER SUPPLY AAV AUTOMATIC AIR VENT HVAC HEATING VENTILATION AIR CONDITIONING ABV ABOVE HWC HOT WATER COI. AC AIR CONDITIONER HWR HOT WATER RETURN ACC AIR COOLED CONDENSER HWS HOT WATER SUPPLY AD ACCESS DOOR HX HEAT EXCHANGER AFF ABOVE FINISHED FLOOR ID INSIDE DIAMETER/DIMENSION AHU AIR HANDLING UNIT IE INVERT ELEVATION AL ALUMINUM INS INSULATION AP ACCESS PANEL KE KITCHEN EXHAUST AR ARGON KH KITCHEN HOOD B BDHI.ER LAT LEAVING AIR TEMPERATURE BAS BUILDING AUTOMATION SYSTEM LBS POUNDS BDD BACK DRAFT DAMPER LN LIQUID NITROGEN BEL BELOW LIPS LOW PRESSURE STEAM BFV BUTTERFLY VALVE LWT LEAVING WATER TEMPERATURE BIP BRAKE HORSE POWER M METER BOD BOTTOM OF DUCT M.C. MECHANICAL CONTRACTOR BOI BOTTOM OF INSULATION MAV MANUAL AIR VENT BOP BOTTOM OF PIP MAX MAXIMUM BOS BOTTOM OF STEEL MBH THOUSANDS BTU/HR BOU BOTTOM OF UNIT MCA MINIMUM CIRCUIT AMPACITY BP BOOSTER PUMP MD MOTORIZED DAMPER BTU BRITISH THERMAL UNITS MER MECHANICAL EQUIPMENT ROOM BTUH BRITISH THERMAL KNITS PER HOUR MIN MINIMUM BV BALANCE VALVE, BALL VALVE MPG MEDIUM PRESSURE GAS C.C. CONTROLS CONTRACTOR MUA MAKE UP AIR CA COMPRESSED AIR MV MOTORIZED VALVE CB BDD COUNTER BALANCED BACK DRAFT DAMPER MVD MANUAL VOLUME DAMPER CC COOLING COIL N2 NITROGEN CFF CAPPED FOR FUTURE NC NORMALLY CLOSED CFM CUBIC FEET PER MINUTE NIC NOT IN CONTRACT CHWR CHILLED WATER RETURN NO NORMALLY OPEN CHWS CHILLED WATER SUPPLY NOS NITROUS OXIDE Cl CAST IRON NTS NOT TO SCALE CO CLEANOUT 02 OXYGEN CO2 CARBON DIOXIDE OA OUTSIDE AIR COND CONDENSATE OBD OPPOSED BLADE DAMPER CONN CONNECTION OCWR OPEN CONDENSER WATER RETURN CP CIRCULATING PUMP OCWS OPEN CONDENSER WATER SUPPLY CS CLEAN STEAM, CURRENT SWITCH OD OUTSIDE DIAMETER/DIMENSION CT COOLING TOWER P PUMP CU CONDENSING UNIT P.C. PLUMBING CONTRACTOR CV CHECK VALVE PC PUMPED CONDENSATE CWR CONDENSER WATER RETURN PCU POLLUTION CONTROL UNIT CWS CONDENSER WATER APPLY PCWR PROCESS COOLING WATER RETURN D DROP (DOWN IN ELEVATION) PCWS PROCESS COOLJNG WATER SUPPLY DB DRY BULB, DUCTBOARD PHWR PROCESS HEATING WATER RETURN DBP DOUBLE BOOSTER PUMP PHWS PROCESS HEATING WATER SUPPLY DCVA DOUBLE CHECK VALVE ASSEMBLY PI PRESSURE INDICATOR DC DUST COLLECTION POC POINT OF CONNECTION DE DRYER EXHAUST PRIM PRIMARY DEMO DEMOLITION PRV PRESSURE REDUCING VALVE DH DUCT HEATER PS PRESSURE SENSOR DN DOWN (THROUGH FLOOR BELOW) PSI POUNDS PER SQUARE INCH DPT DIFFERENTIAL PRESSURE TRANSMITTER PT PRESSURE TEMPERATURE TRAP (FETE'S PLUG) DWG DRAWING RV RELIEF VENT DXFC DIRECT EXPANSION FAN COIL R RISE (UP IN ELEVATION) E EXISTING RA RETURN AIR E.C. ELECTRICAL CONTRACTOR RELF RELIEF AIR EA EACH RF RELIEF FAN EAT ENTERING AIR TEMPERATURE RL REFRIGERANT LIQUID ECH ELECTRIC CABINET HEATER RODI REVERSE OSMOSIS DEIONIZED WATER EF EXHAUST FAN RFBA REDUCED PRESSURE BACK FLOW ASSEMBLY EFF EFFICIENCY RS REFRIGERANT SUCTION ELEV ELEVATION RTU ROOF TOP UNIT EMR ELEVATOR MACHINE ROOM S SENSOR EPF ELEVATOR PRESSURIZATION FAN SA SUPPLY AIR EQZR EQUALIZING LINES SCLP STEAM CONDENSATE LOW PRESSURE ESP EXTERNAL STATIC PRESSURE SCHP STEAM CONDENSATE EUH ELECTRIC UNIT HEATER SCMP STEAM CONDENSATE EWT ENTERING WATER TEMPERATURE SCPU STEAM CONDENSATE PUMPED EXH EXHAUST SCVT STEAM CONDENSATE VENT EXHP EXHAUST PIPING SD SMOKE DAMPER, SMOKE DETECTOR FC FLEXIBLE CONNECTION, FLUID COOLER SEF SMOKE EXHAUST FAN FCU FAN COIL UNIT SF SUPPLY FAN FD FIRE DAMPER, FLOOR DRAIN SL SOUND LINING FE FUME EXHAUST SM SHEETMETAL FFD FUNNEL FLOOR DRAIN SP STATIC PRESSURE FFL FINISHED FLOOR LEVEL SPF STAIR PRESSURIZATION FAN FLA FULL LOAD AMPS SS STAINLESS STEEL FM FLOW METER ST SOLVENT TRANSFER, SOUND TRAP FOB FLAT ON BOTTOM T THERMOSTAT FOR FUEL OIL RETURN TA TRANSFER AIR FOS FUEL OIL SUPPLY, FLAT ON SIDE TBD TO BE DETERMINED FOT FLAT ON TOP TE TOILET EXHAUST FSD FIRE SMOKE DAMPER TI TEMPERATURE INDICATOR, TENANT IMPROVEMENT FLIT FUTURE TOD TOP OF DUCT FV FLOAT VALVE TOP TOP OF PIPE G LOW PRESSURE GAS TOS TOP OF STEEL G.C. GENERAL CONTRACTOR TOU TOP OF UNIT GPM GALLONS PER MINUTE TS TEMPERATURE SENSOR GRV GAS REGULATOR VENT TVs TURNING VANES GV GATE VALVE TYP TYPICAL HC HEATING COIL UP UP (THROUGH FLOOR ABOVE) HE HELIUM VAC VACUUM HHP HYD RONIC HEAT PUMP VAV VARIABLE AIR VOLUME HP HEAT PUMP, HORSE POWER VD VOLUME DAMPER HPG HIGH PRESSURE GAS VFD VARIABLE FREQUENCY DRIVE HPS HIGH PRESSURE STEAM W/ WITH HPWR HEAT PUMP WATER RETURN WF WATER FILTER GRILLES, REGISTERS, DIFFERS LEGEND LEVEL NOTE: THE "/FD' CALLOUT INDICATES A GRILLE WITH U.L CLASSIFIED INDOOR UNIT OUTDOOR RADIATION DAMPER TO BE INSTALLED IN RATED FLOOR/CEILING REMARKS TAG OR ROOF/CEILING ASSEMBLIES. USE RUSKIN MODEL CFD. INCLUDE MODEL NOMINAL THERMAL INSULATION BLANKET FOR LAY -IN T -BAR CEILINGS. COOLING (MBH) NOTE: ALL SUPPLY DIFFUSERS ARE TO BE INSTALLED WITH A DIFFUSER CAN EERTON SEER W/ PERF DIVIDER, GENSCO REGISTER BOX W/ FLEX COLLAR & DIFF, ECON (Y/N) MIN. OSA MODEL COLDC21 OR EQUIV. TAG NOTE: FOR EXPOSED DUCTWORK WITH SUPPLY EXHAUST GRILLES TAKEOFFS ELECTRICAL DATA SOUND PRESSURE dB(A) TO BE GRILLE SIZE PLUS 2' TO MATCH GRILLE FRAME. I VOLTS/PH MCA CEILING DIFFUSER (LAY -IN T -BAR CEILING) 1 X'xX" CD 4 CORE ADJUSTABLE, WITH FILLER FOR 24' x 24" LAY -IN MODULE -Q- CFM TITUS MODEL, MCD, BORDER TYPE 3 - KRUEGER SERIES 1244, FRAME 23 I 80/67 (USE X"0 RUNOUT) 21.6 203-208/1 0.3 CEILING DIFFUSER WITH FIRE DAMPER (LAY -IN T -BAR CEILING) - X"xX" CD FD 4 CORE ADJUSTABLE, ALL STEEL CONSTRUCTION, RADIATION - CFM DAMPER SHALL BE RUSKIN MODEL CFD W/ THERMAL INSULATING I AOU18RLXFW BLANKET (USE X'0 RUNOUT) I _ " " X xX CDP CEILING DIFFUSER (PLASTER CEILING) 'V" -� CFM 4 CORE ADJUSTABLE, FRAME TITUS MODEL. MCD, BORDER TYPE 6 - KRUEGER SERIES 1244, FRAME 21 X xX" CD P FD CEILING DIFFUSER (PLASTER CEILING) WITH FIRE DAMPER SAME AS C.D./P WITH RADIATION DAMPER AS NOTED ABOVE CFM (USE X'O RUNOUT) i CEILING DIFFUSER WITH PERFORATED FACE (LAY -IN T -BAR CEILING) X"xX" CD PF 4 CORE ADJUSTABLE, WITH FILLER FOR 24' x 24" LAY -IN MODULE -D- CFM KRUEGER SERIES 1244P, FRAME 23 (USE X" RUNOUT) 1 (USE X" RUNOUT) CEILING LAMINAR FLOW DIFFUSER WITH PERFORATED FACE CFM TITUS TL.F-SS © SLOT-INLETO SLOT DIFFUSER FOR LAY -IN CEILING I CFM KEES-100 /SLOT-INLErO/FD SLOT DIFFUSER FOR RATED LAY -IN CEILING WITH FIRE DAMPER I CFM TEMPMASTER FRD 1 #SLOT-INLETO/P SLOT DIFFUSER (PLASTER CEILING) CFM KEES K-100, FRAME OPTION 12 1 -�j JSLOT-IN.O FD/P SLOT DIFFUSER NTH FIRE DAMPER (PLASTER CEILING) CFM TEMPMASTER MODEL TFD-F OR FRD-F FOR SURFACE MOUNTING StDEWALL SUPPLY REGISTER S.S.R. DOUBLE DEFLECTION, HORIZONTAL FRONT BLADES, WITH O.B.D. ` TITUS MODEL 272RL O.B.D. - KRUEGER MODEL 880H O.B.D. SDEWALL SUPPLY GRILLE S.S.G. DOUBLE DEFLECTION, HORIZONTAL FRONT BLADES, WITH O.B.D. TITUS MODEL 272RL - KRUEGER MODEL 88OH O.B.D. LINEAR WALL SUPPLY GRILLE LN.W.S.G. FIXED 15 DEGREE DEFLECTION BLADES KRUEGER MODEL 1515, FRAME 415, ALUMINUM CONSTRUCTION RETURN AIR GRILLE ® R.A.G. ALUMINUM EGGCRATE WITH y2" x '/2' x '/2' CORE TITUS MODEL 50F - KRUEGER EG -5 RETURN AIR GRILLE PIASTER CEILING R.A.G./ACCESS INSTALLED IN TITUS RAPID MOUNT FRAME (MODEL TRM) TO ALLOW CEILING ACCESS. FIXED 35 DEGREE REFLECTION BLADES. KRUEGER MODEL SBO - TITUS MODEL 350RL RETURN AIR GRILLE (PLASTER CEILING) la R.A.G./P. FIXED 35 DEGREE D M EC11ON BLADES KRUEGER MODEL S8OH - TITUS MODEL 35ORL S.R.G. SIDEWALL RETURN GRILLE FIXED 35 DEGREE DEFLECTION BLADES, WITHOUT O.B.D. TITUS MODEL. 35ORL - KRUEGER MODEL S8OH LINEAR WALL RETURN GRILLE LN.W.R.G. FIXED 0 DEGREE DEFLECTION BLADES KRUEGER MODEL 1500, FRAME 415 ALUMINUM CONSTRUCTION EXHAUST GRILLE Q E.G. ALUMINUM EGGCRATE WITH f2" x V2" x '/2' CORE TITUS MODEL 50F - KRUEGER EG -5 RETURN AIR GRILLE (BASTER CEILING) 0 EG./P. FIXED 35 DEGREE DEFLECTION BLADES TITUS MODEL 35ORL - KRUEGER MODEL SSOH EXHAUST REGISTER E.R. FIXED 35 DEGREE DEFLECTION BLADES TITUS MODEL 35ORL O.B.D. - KRUEGER MODEL. S80H O.B.D. TRANSFER GRILLE ® T.G. ALUMINUM EGGCRATE WITH '/2' x '/2" x '/i CORE 11TUS MODEL 50F - KRUEGER EG -5 TRANSFER GRILLE (PLASTER CEILING OR WALL) 0 T.G./P. FIXED 35 DEGREE DEFLECTION BLADES TITUS MODEL 35ORL - KRUEGER MODEL S80H EXHAUST 4' STATIONARY LOUVER LOUVER EL CMODEL -375 RUSH ELF 4" STATIONARY LOUVER WITH DRAINABLE BLADES INTAKE GALVANIZED STEEL CONSTRUCTION LOUVER RUSKIN MODEL ELF -375D FINISH: FACTORY APPLIED PRIME COAT SYMBOLS LEGEND (HVAC) 12"x12"/SL 12'x12' SM /71202�_J_/ 12'x12" SM/W SHEET INDEX DUCT UNDER POSITIVE PRESSURE REV # SHEET # SKEET TITLE 2 * M0.01 LEGENDS AND NOTES DUCT UNDER NEGATIVE PRESSURE 1 * M2.01 LEVEL 1 HVAC PLAN 2 M2.02 LEVEL 2 HVAC PLAN TURNING VANES ELEVATION FROM F.F.L. (INSULATION AND DUCT FLANGES EXTEND 1'h" BELOW BOD CALLOUT) EQUIPMENT IDENTIFICATION THERMOSTAT /13.611M CEILING OR INUNE EXHAUST FAN 24" x 12' RETURN AIR GRILLE W/SOUNDLIPED CAN SUPPLY AIR ARROW RETURN AIR ARROW SPEED? SWITCH: FURNISHED BY HOLADAY-PARKS, INSTALLED BY ELECTR. CONTR. FLEXIBLE CONNECTION DUCT HEATER MANUAL VOLUME DAMPER MOTORIZED DAMPER BACK DRAFT DAMPER VERTICAL FIRE DAMPER (1 %2 HOUR) IN AIRSTREAM RUSKIN MODEL DIB2 STYLE A HORIZONTAL FIRE DAMPER (1 %2 HOUR) IN AIRSTREAM RUSKIN MODEL DIB2 STYLE A VERTICAL FIRE DAMPER (3 HOUR) IN AIRSTREAM RUSKIN MODEL DIB23 STYLE A HORIZONTAL FIRE DAMPER (3 HOUR) IN AIRSTREAM RUSKIN MODEL DIB23 STYLE A BACK DRAFT DAMPER RUSKIN MODEL BD2/A1, LOCAL VELOCITY < 1500 FPM BACK DRAFT DAMPER RUSKIN MODEL BD2/A2, LOCAL VELOCITY < 2500 FPM BACK DRAFT DAMPER RUSKIN MODEL BD6, LOCAL VELOCITY < 3500 FPM HORIZONTAL COMBINATION SMOKE AND FIRE DAMPER VERTICAL COMBINATION SMOKE AND FIRE DAMPER SPIN -IN TAKE -OFF & VOLUME DAMPER INDICATES 14" x 14' O.D. SHEETMETAL WITH 1" SOUNDLINER (U.N.O.), 12" x 12" NET I.D. INDICATES UNLINED 12' x 12' S.M. DUCT INDICATES 12" x 12" I.D. DUCTBOARD INDICATES UNLINED 12" x 12' S.M. DUCT WITH INSULATED WRAP RISE OR DROP IN DIRECTION OF FLOW FLEXIBLE DUCT INDICATES FLAT OVAL DUCT SPIN -IN TAKE -OFF & VOLUME DAMPER WITH RIGID ROUND FIBERGLASS DUCT INDICATES AIRFLOW DIRECTION THROUGH THE PARKING GARAGE TO THE GARAGE EXHAUST FANS. DUCTLESS SPLIT HEAT PUMP SCHEDULE LEVEL ROOM MAKE INDOOR UNIT OUTDOOR UNIT REMARKS TAG LOCATION MODEL NOMINAL ENT. DB/WB COOLING (MBH) HEATING MBH047f ELECTRICAL DATA EERTON SEER HSPF ECON (Y/N) MIN. OSA WEIGHT (LLS) TAG LOCATION MODEL ELECTRICAL DATA SOUND PRESSURE dB(A) WEIGHT (LBS) TOTAL SENS. VOLTS/PH MCA VOLTS/PH MCA 1 110 FUJITSU DXHP-1-1 110 ASU18RLF 1.50 80/67 18.0 - 21.6 203-208/1 0.3 13.3 22.0 10 N 0 31 CU -1-1 ROOF AOU18RLXFW 203-208/1 14.5 49 135 1,2,3,4,5,6,7 1: OUTDOOR UNIT WIRING AND DISCONNECT BY E.C. SINGLE POINT POWER CONNECTION. 2: PLUMBING CONTRACTOR TO ROUTE CONDENSATE TO APPROVED PLUMBING RECEPTICAL 3: NO SPRING OR NEOPRENE ISOLATION REQUIRED. 4: T -STAT PROVIDED WITH UNIT, INSTALLED BY C.C. 5: POWER WIRING FROM OUTDOOR UNIT TO INDOOR BY EC. EC TO DETERMINE IF ADDITIONAL DISCONNECT FOR INDOOR UNIT IS REQUIRED PER CODE. 6: SEER AND HSPF RATINGS PER AHRI STANDARDS. • U ..SERVES ELECTRO C E ENT ROOM. NO AIRSIDE ECO MIZER PRO ED, LIZIN EXC TIO U C 4.1 T AT FAN SCHEDULE FAN NUMBER TENANT AREA SERVED MAKE TYPE MODEL CLASS VFD (Y/N) PERFORMANCE DATA HP VOLTS/ PHASE WGT. LBS. REMARKS CFM S.P. RPM BHP EF -2-1 SANFORD BROWN BREAK ROOM PANASONIC INLINE FV-20NLF1 - N 200 0.4 1154 - 57W 120/1 17 1, 2, 3 1: WIRING AND DISCONNECT BY E.C. 2: MANUAL STARTER W/OVERLOAD PROTECTION SHALL BE PROVIDED AND INSTALLED BY E.C. 3: LINE VOLTAGE (120V) TIME CLOCK SHALL BE PROVIDED BY C.C. AND INSTALLED BY E.C. * INCLUDED IN THIS ISSUE LOT 3 OF CIT, OF TL WILA SHORT PLAT NO L97-0049 RECORDING NO 9711069009 SAID SHORT PLAT DEFINED - PORTION OF E 1/2 OF NW 1/4 OF SE 1/4, BEGIN NE CORNER OF SAID E 1/2 BEING N 88-05-42 W 1339.34 FT FROM NE CORNER OF SE 1/4 TH S 01-47-29 W 1322.34 FT TO SOUTHEAST CORNER TH N 87-55-02 W 659.35 FT TO W UNE OF E 659.34 FT OF SAID E 1/2 TH N 01-47-29 E 1320.30 FT TO N UNE OF SAID E 1/2 TH S 88-05-42 E 659.34 FT TO POB LESS PORTION FOR 59TH AVE SOUTH LESS PORTIONS FOR STREETS AS CONVEYED BY DEED, RECORDING NO 7907120770 LESS PORTION CONVEYED TO CITY OF TUKWILA FOR ROAD BY DEED, RECORDING NO 9408290327 1. RELOCATE THREE (3) DIFFUSERS FOR NEW SPACE LAYOUT. 2. INSTALL ONE (1) INLINE EXHAUST FAN FOR BREAK ROOM. REVIEWED FOR COMPUANCE Via MAY 2 7 2016 ACi `ukwlia Me. yK BUILDING DIVi- SON Ram rOV18W Ss FOYRI is SUbjact to errmrs and oma^sir�y .,. Approval of consiruciion dMilments does not aurhej iza d PL of approvod � i , anad: BY City of I Ok ilaw BUILDING DIVISION SFPPirMTE PEP-;gliT REQUIRED FOR: 13 M Chanicd Icctdcal ;7rplumbbV as Plft CIV of Tukwila REVISIONS No changes shalt be made to the scope of work without prior approval of Tt.skwila Building Division. RCv1.;iens will require a new plan submittal end may include additional plan review fees. 0 RECEIVED CITY OF TUKWILA MAY 2 4 2016 PERMIT CENTER CITY APPROVAL Mechanical Solutions a Energy Services Building Controls 9 Service & Maintenance 4600 S. 134TH PLACE SEATTLE, WA 98168 a (206) 248-9700 HOLADAYPARKS.com WA LICENSE NUMBER: HOLADPI379NO PROJECT DESIGN TEAM Designed bv: RL Drawn by: MLK, MV Approved by: Job Number. 67016 Filename: M001.DWG APPROVED FOR CONSTRUCTION ISSUE NAMEIDATE PENDING CITY APPROVAL 5/24/16 REVISION'S - No. Date By Description 1 5/4/16 RL PHASE I PERMIT / CD 2 5/24/16 RL PHASE II PERMIT/ CD SHEET TITLE LEGENDS & NOTES SHEET NUMBER �u wmrta evm, n� oa�w++m "aaa w un raw ro�.at�to�r.vuws, wc. w aNtr or two ooau�crtr.ar ee �vnaouc5e i" un rowt at"r.wr.tEwm wrt�wur vewaww wwmrn raw �uuwr vuus, we 0 10 _ LEVEL 2 HVAC PLAN r wAm •Vr • f -Or A° t7' '' z Mechanical Solutions o Energy Services Building Controls r Service & Maintenance 4600 S. 134TH PLACE SEATTLE, WA 98168 . (206) 248-9700 HOLADAYPARKS.com WA LICENSE NUMBER: HOLADPI379N0 PROJECT D� io 600 I�� to RECEIVED CITY OF TUKWILA MAY 2 4 2016 PERMIT CENTER LINETYPE LEGEND EXISTING CONSTRUCTION = NEW CONSTRUCTION — — — — — — — = FUTURE CONSTRUCTION — — — — — — — = DEMOLITION TENANT BOUNDARY CITY APPROVAL DESIGN TEAM Designed bv: RL Drawn by: MLK, MV Approved by: Job Number. 67016 Filename: M202.DWG REGISTRATION 5/24/16 APPROVED FOR CONSTRUCTION ISSUE NAMEIDATE PENDING CITY APPROVAL 5/24/16 REVISIONS No. Date By Description 2 5/24/16 RL PHASE 11 PERMIT/ CD ISSUE SHEET TITLE LEVEL 2 HVAC PLAN SHEET NUMBER All.wartsnesERnM THEM DPAYHHOs slaw WAW rain TO Ha AMY -PMNs, NG HOPM OF THs DOOMEM MWOE qEP MCEDMMY FaN asffVMV AMWTH=ftWS5MWWRTWOFWWHQAWYPMH4W- GENERAL NOTES 1. THESE DOCUMENTS ARE BASED ON HOLADAY PARKS ENGINEERING AND SHOP FABRICATION STANDARDS, SMACNA DUCT CONSTRUCTION STANDARDS, AND APPLICABLE LOCAL AND STATE CODES WHICH ARE NOT SHOWN/ IN DETAIL ON THESE DRAWINGS. VARIATION FROM THESE PLANS REQUIRES NOTIFICATION OF HDLADAY-PARKS ENGINEERING DEPARTMENT 2. ALL TRADES SHALL LEAVE A MINIMUM OF 36" CLEARANCE IN FRONT OF MECHANICAL EQUIPMENT ACCESS PANELS FOR SERVICING. ACCESS PALLS THAT CONTAIN LINE VOLTAGE POWER (120 VOLT AND GREATER) SHALL HAVE A MINIMUM OF 42' CLEARANCE IN FRONT OF THE ACCESS PANEL AND A MINIMUM OF THE ACCESS PAM. WIDTH CLEAR FROM OBSTRUCTIONS AS REQUIRED BY STATE AND LOCAL ELECTRICAL CODES. 3. CUTTING, FRAMING, PATCHING AND PAINTING OF WALL, CEILING AND FLOOR OPENINGS, AS REQUIRED BY THESE MECHANICAL PLANS, SHALL BE BY THE GENERAL CONTRACTOR. 4. ROOF CURBS, FLASHINGS, SLEEPERS, PITCH POCKETS, CUTTING AND PATCHING OF ROOF OPENINGS, ROOFING, AND ROOF INSULATION SHALL BE BY THE GENERAL CONTRACTOR 5. ROOF CURBS, SLEEPERS, CANT STRIPS, ROOFING, AND ROOF INSULATION SHALL BE PROVIDED AND INSTALLED BY THE GENERAL CONTRACTOR, CURBS ARE TO BE CONSTRUCTED ACCORDING TO THE SIZES PROVIDED BY HOLADAY-PARKS' FIELD FOREMEN AND/OR AS SHOWN ON THE MECHANICAL PLANS. THE ROOF CURBS SHALL BE SHIMMED AS REQUIRED TO MAKE ROOF CURBS AND/OR SLEEPERS LEVEL TOP OF CURBS MUST BE TRUE (FLAT) TO PROVIDE AN ACCEPTABLE SEALING SURFACE THE MAXIMUM ALLOWABLE DEVIATION FROM LEVEL OR FLAT SHALL BE 1/4N IN 10'. ROOF CURBS APIA SLEEPERS MUST BE SECURELY FASTENED TO STRUCTURAL SUPPORT MEMBERS BY THE GENERAL CONTRACTOR. 6. PAINTING OF GRILLES, REGISTERS, AND DFFUSERS, AS MAY BE REQUIRED BY ARCHITECT OR OWNER, SHALL BE DONE BY THE GENERAL CONTRACTOR. 7. CARRY-OVER PERFORMANCE EQUAL TO OR BETTER THAN THE LOUVERS SPECIFIED IN ME MECHANICAL PLANS. 8. EQUIPMENT, DUCTS, AND PIPING WEIGHTS AND LOCATIONS HAVE BEEN COORDINATED WITH ARCHITECT, STRUCTURAL ENGINEER, AND GENERAL CONTRACTOR IN ORDER TO DETERMINE BUILDING STRUCTURAL ADEQUACY. IF IT IS NECESSARY TO RELOCATE EQUIPMENT, DUCTS, OR PIPING, NOTIFY HOLADAY-PARKS' ENGINEERING DEPARTMENT FOR ASSISTANCE IN RE -COORDINATION. 9.- IN NO INSTANCE SHALL OTHER CONTRACTORS HANG OR SUPPORT EQUIPMENT, CEILING WIRES, LIGHT FIXTURE HANGERS, ETC..., FROM HVAC EQUIPMENT, OR DUCTS, OR PIPING. ELECTRICAL COORDINATION NOTES 1. LINE VOLTAGE (120 VOLT AND ABOVE) WIRING FOR MECHANICAL EQUIPMENT SHALL BE PROVIDED AND INSTALLED BY THE ELECTRICAL CONTRACTOR. LOW VOLTAGE (LESS THAN 120 VOLT) WIRING FOR MECHANICAL EQUIPMENT AND DDC SYSTEMS SHALL BE PROVIDED BY THE CONTROLS CONTRACTOR. REFRIGERATION PIPING NOTES 1. INSTALLATION OF REFRIGERANT PIPING SHALL BE IN ACCORDANCE WITH THE 2012 INTERNATIONAL MECHANICAL CODE (IMC) AND LOCAL CODES AND STANDARDS. 2. INSTALLATION OF LISTED AND LABELED FACTORY BUILT EQUIPMENT AND APPLIANCES SHALL BE PER THE MANUFACTURER'S INSTALLATION REQUIREMENTS. INSTALLATION OF REFRIGERANT PIPING SERVING LISTED AND LABELED FACTORY BUILT EQUIPMENT SHALL BE PER THE MANUFACTURER'S INSTALLATION REQUIREMENTS, REFRIGERANT PIPE SIZE SHALL BE NO LESS THAN THAT REQUIRED BY THE MANUFACTURER'S INSTALLATION REQUIREMENTS AND AS REQUIRED FOR THE INSTALLED LENGTH OF PIPE AND THE LOCATION OF THE EQUIPMENT. 3. REFRIGERANT PIPING SHALL BE EITHER SEAMLESS TYPE 'L' DRAWN COPPER TUBING IN ACCORDANCE WITH ASTM B88 OR SEAMLESS COPPER ACR TUBING IN ACCORDANCE WITH ASTM B280. REFRIGERANT PIPE FITTINGS SHALL BE WROUGHT COPPER WITH SILVER -SOLDERED OR BRAZED JOINTS. 4. PENETRATIONS THROUGH FIRE AND/OR SMOKE RATED WALLS, FLOORS, AND CEILINGS SHALL BE PROTECTED IN ACCORDANCE WITH THE 2012 SEATTLE BUILDING CODE (SBC) AND THE 2012 SMC. PROTECTION, AS REQUIRED, SHALL BE PROVIDED AND INSTALLED BY THE PIPING CONTRACTOR. 5. REFRIGERANT PIPING INSULATION THICKNESS SHALL BE BASED ON NOMINAL PIPE DIAMETER AND OPERATING TEMPERATURE RANGE IN ACCORDANCE WITH TABLE C403.2.8. IN THE 2012 SEATTLE ENERGY CODE (SEC). THE PIPE INSULATION MATERIAL SHALL BE PREFORMED ELASTOMERIC INSULATION, "ARMAFLEX', 'RUBATM OR APPROVED EQUAL WITH A CONDUCTIVITY VALUE EQUAL TO OR BETTER THAN THE VAULES LISTED IN TABLE C403.2.8 OF THE 2012 SEC. ALL REFRIGERANT PIPE LOCATED OUTSIDE THE BUILDING SHALL BE INSULATED. ALL REFRIGERANT PIPE INSULATION EXPOSED TO WEATHER SHALL HAVE UV PROTECTION OR SHALL HAVE A PROTECTIVE JACKET TO PREVENT UV DAMAGE IN ACCORDANCE WITH SECTION C403.2.8.1 OF THE SEC. 6. REFRIGERANT PIPING THAT IS PART OF A FIELD ERECTED REFRIGERANT SYSTEM SHALL BE PRESSURE TESTED IN ACCORDANCE WITH THE 2012 SMC. REFRIGERANT PIPING INSTALLED AS PART OF FACTORY BUILT LISTED AND LABELED EQUIPMENT OR APPLIANCES SHALL BE PRESSURE TESTED IN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS. GRILLES, REGISTERS, DIFFERS LEGEND ABBREVIATIONS (MECHANICAL) /W WITH WRAP (DUCT INSULATION) HRWS HEAT RECOVERY WATER SUPPLY AAV AUTOMATIC AIR VENT HVAC HEATING VENTILATION AIR CONDITIONING ABV ABOVE HWC HOT WATER COI. AC AIR CONDITIONER HWR HOT WATER RETURN ACC AIR COOLED CONDENSER HWS HOT WATER SUPPLY AD ACCESS DOOR HX HEAT EXCHANGER AFF ABOVE FINISHED FLOOR ID INSIDE DIAMETER/DIMENSION AHU AIR HANDLING UNIT IE INVERT ELEVATION AL ALUMINUM INS INSULATION AP ACCESS PANEL KE KITCHEN EXHAUST AR ARGON KH KITCHEN HOOD B BDHI.ER LAT LEAVING AIR TEMPERATURE BAS BUILDING AUTOMATION SYSTEM LBS POUNDS BDD BACK DRAFT DAMPER LN LIQUID NITROGEN BEL BELOW LIPS LOW PRESSURE STEAM BFV BUTTERFLY VALVE LWT LEAVING WATER TEMPERATURE BIP BRAKE HORSE POWER M METER BOD BOTTOM OF DUCT M.C. MECHANICAL CONTRACTOR BOI BOTTOM OF INSULATION MAV MANUAL AIR VENT BOP BOTTOM OF PIP MAX MAXIMUM BOS BOTTOM OF STEEL MBH THOUSANDS BTU/HR BOU BOTTOM OF UNIT MCA MINIMUM CIRCUIT AMPACITY BP BOOSTER PUMP MD MOTORIZED DAMPER BTU BRITISH THERMAL UNITS MER MECHANICAL EQUIPMENT ROOM BTUH BRITISH THERMAL KNITS PER HOUR MIN MINIMUM BV BALANCE VALVE, BALL VALVE MPG MEDIUM PRESSURE GAS C.C. CONTROLS CONTRACTOR MUA MAKE UP AIR CA COMPRESSED AIR MV MOTORIZED VALVE CB BDD COUNTER BALANCED BACK DRAFT DAMPER MVD MANUAL VOLUME DAMPER CC COOLING COIL N2 NITROGEN CFF CAPPED FOR FUTURE NC NORMALLY CLOSED CFM CUBIC FEET PER MINUTE NIC NOT IN CONTRACT CHWR CHILLED WATER RETURN NO NORMALLY OPEN CHWS CHILLED WATER SUPPLY NOS NITROUS OXIDE Cl CAST IRON NTS NOT TO SCALE CO CLEANOUT 02 OXYGEN CO2 CARBON DIOXIDE OA OUTSIDE AIR COND CONDENSATE OBD OPPOSED BLADE DAMPER CONN CONNECTION OCWR OPEN CONDENSER WATER RETURN CP CIRCULATING PUMP OCWS OPEN CONDENSER WATER SUPPLY CS CLEAN STEAM, CURRENT SWITCH OD OUTSIDE DIAMETER/DIMENSION CT COOLING TOWER P PUMP CU CONDENSING UNIT P.C. PLUMBING CONTRACTOR CV CHECK VALVE PC PUMPED CONDENSATE CWR CONDENSER WATER RETURN PCU POLLUTION CONTROL UNIT CWS CONDENSER WATER APPLY PCWR PROCESS COOLING WATER RETURN D DROP (DOWN IN ELEVATION) PCWS PROCESS COOLJNG WATER SUPPLY DB DRY BULB, DUCTBOARD PHWR PROCESS HEATING WATER RETURN DBP DOUBLE BOOSTER PUMP PHWS PROCESS HEATING WATER SUPPLY DCVA DOUBLE CHECK VALVE ASSEMBLY PI PRESSURE INDICATOR DC DUST COLLECTION POC POINT OF CONNECTION DE DRYER EXHAUST PRIM PRIMARY DEMO DEMOLITION PRV PRESSURE REDUCING VALVE DH DUCT HEATER PS PRESSURE SENSOR DN DOWN (THROUGH FLOOR BELOW) PSI POUNDS PER SQUARE INCH DPT DIFFERENTIAL PRESSURE TRANSMITTER PT PRESSURE TEMPERATURE TRAP (FETE'S PLUG) DWG DRAWING RV RELIEF VENT DXFC DIRECT EXPANSION FAN COIL R RISE (UP IN ELEVATION) E EXISTING RA RETURN AIR E.C. ELECTRICAL CONTRACTOR RELF RELIEF AIR EA EACH RF RELIEF FAN EAT ENTERING AIR TEMPERATURE RL REFRIGERANT LIQUID ECH ELECTRIC CABINET HEATER RODI REVERSE OSMOSIS DEIONIZED WATER EF EXHAUST FAN RFBA REDUCED PRESSURE BACK FLOW ASSEMBLY EFF EFFICIENCY RS REFRIGERANT SUCTION ELEV ELEVATION RTU ROOF TOP UNIT EMR ELEVATOR MACHINE ROOM S SENSOR EPF ELEVATOR PRESSURIZATION FAN SA SUPPLY AIR EQZR EQUALIZING LINES SCLP STEAM CONDENSATE LOW PRESSURE ESP EXTERNAL STATIC PRESSURE SCHP STEAM CONDENSATE EUH ELECTRIC UNIT HEATER SCMP STEAM CONDENSATE EWT ENTERING WATER TEMPERATURE SCPU STEAM CONDENSATE PUMPED EXH EXHAUST SCVT STEAM CONDENSATE VENT EXHP EXHAUST PIPING SD SMOKE DAMPER, SMOKE DETECTOR FC FLEXIBLE CONNECTION, FLUID COOLER SEF SMOKE EXHAUST FAN FCU FAN COIL UNIT SF SUPPLY FAN FD FIRE DAMPER, FLOOR DRAIN SL SOUND LINING FE FUME EXHAUST SM SHEETMETAL FFD FUNNEL FLOOR DRAIN SP STATIC PRESSURE FFL FINISHED FLOOR LEVEL SPF STAIR PRESSURIZATION FAN FLA FULL LOAD AMPS SS STAINLESS STEEL FM FLOW METER ST SOLVENT TRANSFER, SOUND TRAP FOB FLAT ON BOTTOM T THERMOSTAT FOR FUEL OIL RETURN TA TRANSFER AIR FOS FUEL OIL SUPPLY, FLAT ON SIDE TBD TO BE DETERMINED FOT FLAT ON TOP TE TOILET EXHAUST FSD FIRE SMOKE DAMPER TI TEMPERATURE INDICATOR, TENANT IMPROVEMENT FLIT FUTURE TOD TOP OF DUCT FV FLOAT VALVE TOP TOP OF PIPE G LOW PRESSURE GAS TOS TOP OF STEEL G.C. GENERAL CONTRACTOR TOU TOP OF UNIT GPM GALLONS PER MINUTE TS TEMPERATURE SENSOR GRV GAS REGULATOR VENT TVs TURNING VANES GV GATE VALVE TYP TYPICAL HC HEATING COIL UP UP (THROUGH FLOOR ABOVE) HE HELIUM VAC VACUUM HHP HYD RONIC HEAT PUMP VAV VARIABLE AIR VOLUME HP HEAT PUMP, HORSE POWER VD VOLUME DAMPER HPG HIGH PRESSURE GAS VFD VARIABLE FREQUENCY DRIVE HPS HIGH PRESSURE STEAM W/ WITH HPWR HEAT PUMP WATER RETURN WF WATER FILTER GRILLES, REGISTERS, DIFFERS LEGEND LEVEL NOTE: THE "/FD' CALLOUT INDICATES A GRILLE WITH U.L CLASSIFIED INDOOR UNIT OUTDOOR RADIATION DAMPER TO BE INSTALLED IN RATED FLOOR/CEILING REMARKS TAG OR ROOF/CEILING ASSEMBLIES. USE RUSKIN MODEL CFD. INCLUDE MODEL NOMINAL THERMAL INSULATION BLANKET FOR LAY -IN T -BAR CEILINGS. COOLING (MBH) NOTE: ALL SUPPLY DIFFUSERS ARE TO BE INSTALLED WITH A DIFFUSER CAN EERTON SEER W/ PERF DIVIDER, GENSCO REGISTER BOX W/ FLEX COLLAR & DIFF, ECON (Y/N) MIN. OSA MODEL COLDC21 OR EQUIV. TAG NOTE: FOR EXPOSED DUCTWORK WITH SUPPLY EXHAUST GRILLES TAKEOFFS ELECTRICAL DATA SOUND PRESSURE dB(A) TO BE GRILLE SIZE PLUS 2' TO MATCH GRILLE FRAME. I VOLTS/PH MCA CEILING DIFFUSER (LAY -IN T -BAR CEILING) 1 X'xX" CD 4 CORE ADJUSTABLE, WITH FILLER FOR 24' x 24" LAY -IN MODULE -Q- CFM TITUS MODEL, MCD, BORDER TYPE 3 - KRUEGER SERIES 1244, FRAME 23 I 80/67 (USE X"0 RUNOUT) 21.6 203-208/1 0.3 CEILING DIFFUSER WITH FIRE DAMPER (LAY -IN T -BAR CEILING) - X"xX" CD FD 4 CORE ADJUSTABLE, ALL STEEL CONSTRUCTION, RADIATION - CFM DAMPER SHALL BE RUSKIN MODEL CFD W/ THERMAL INSULATING I AOU18RLXFW BLANKET (USE X'0 RUNOUT) I _ " " X xX CDP CEILING DIFFUSER (PLASTER CEILING) 'V" -� CFM 4 CORE ADJUSTABLE, FRAME TITUS MODEL. MCD, BORDER TYPE 6 - KRUEGER SERIES 1244, FRAME 21 X xX" CD P FD CEILING DIFFUSER (PLASTER CEILING) WITH FIRE DAMPER SAME AS C.D./P WITH RADIATION DAMPER AS NOTED ABOVE CFM (USE X'O RUNOUT) i CEILING DIFFUSER WITH PERFORATED FACE (LAY -IN T -BAR CEILING) X"xX" CD PF 4 CORE ADJUSTABLE, WITH FILLER FOR 24' x 24" LAY -IN MODULE -D- CFM KRUEGER SERIES 1244P, FRAME 23 (USE X" RUNOUT) 1 (USE X" RUNOUT) CEILING LAMINAR FLOW DIFFUSER WITH PERFORATED FACE CFM TITUS TL.F-SS © SLOT-INLETO SLOT DIFFUSER FOR LAY -IN CEILING I CFM KEES-100 /SLOT-INLErO/FD SLOT DIFFUSER FOR RATED LAY -IN CEILING WITH FIRE DAMPER I CFM TEMPMASTER FRD 1 #SLOT-INLETO/P SLOT DIFFUSER (PLASTER CEILING) CFM KEES K-100, FRAME OPTION 12 1 -�j JSLOT-IN.O FD/P SLOT DIFFUSER NTH FIRE DAMPER (PLASTER CEILING) CFM TEMPMASTER MODEL TFD-F OR FRD-F FOR SURFACE MOUNTING StDEWALL SUPPLY REGISTER S.S.R. DOUBLE DEFLECTION, HORIZONTAL FRONT BLADES, WITH O.B.D. ` TITUS MODEL 272RL O.B.D. - KRUEGER MODEL 880H O.B.D. SDEWALL SUPPLY GRILLE S.S.G. DOUBLE DEFLECTION, HORIZONTAL FRONT BLADES, WITH O.B.D. TITUS MODEL 272RL - KRUEGER MODEL 88OH O.B.D. LINEAR WALL SUPPLY GRILLE LN.W.S.G. FIXED 15 DEGREE DEFLECTION BLADES KRUEGER MODEL 1515, FRAME 415, ALUMINUM CONSTRUCTION RETURN AIR GRILLE ® R.A.G. ALUMINUM EGGCRATE WITH y2" x '/2' x '/2' CORE TITUS MODEL 50F - KRUEGER EG -5 RETURN AIR GRILLE PIASTER CEILING R.A.G./ACCESS INSTALLED IN TITUS RAPID MOUNT FRAME (MODEL TRM) TO ALLOW CEILING ACCESS. FIXED 35 DEGREE REFLECTION BLADES. KRUEGER MODEL SBO - TITUS MODEL 350RL RETURN AIR GRILLE (PLASTER CEILING) la R.A.G./P. FIXED 35 DEGREE D M EC11ON BLADES KRUEGER MODEL S8OH - TITUS MODEL 35ORL S.R.G. SIDEWALL RETURN GRILLE FIXED 35 DEGREE DEFLECTION BLADES, WITHOUT O.B.D. TITUS MODEL. 35ORL - KRUEGER MODEL S8OH LINEAR WALL RETURN GRILLE LN.W.R.G. FIXED 0 DEGREE DEFLECTION BLADES KRUEGER MODEL 1500, FRAME 415 ALUMINUM CONSTRUCTION EXHAUST GRILLE Q E.G. ALUMINUM EGGCRATE WITH f2" x V2" x '/2' CORE TITUS MODEL 50F - KRUEGER EG -5 RETURN AIR GRILLE (BASTER CEILING) 0 EG./P. FIXED 35 DEGREE DEFLECTION BLADES TITUS MODEL 35ORL - KRUEGER MODEL SSOH EXHAUST REGISTER E.R. FIXED 35 DEGREE DEFLECTION BLADES TITUS MODEL 35ORL O.B.D. - KRUEGER MODEL. S80H O.B.D. TRANSFER GRILLE ® T.G. ALUMINUM EGGCRATE WITH '/2' x '/2" x '/i CORE 11TUS MODEL 50F - KRUEGER EG -5 TRANSFER GRILLE (PLASTER CEILING OR WALL) 0 T.G./P. FIXED 35 DEGREE DEFLECTION BLADES TITUS MODEL 35ORL - KRUEGER MODEL S80H EXHAUST 4' STATIONARY LOUVER LOUVER EL CMODEL -375 RUSH ELF 4" STATIONARY LOUVER WITH DRAINABLE BLADES INTAKE GALVANIZED STEEL CONSTRUCTION LOUVER RUSKIN MODEL ELF -375D FINISH: FACTORY APPLIED PRIME COAT SYMBOLS LEGEND (HVAC) 12"x12"/SL 12'x12' SM /71202�_J_/ 12'x12" SM/W SHEET INDEX DUCT UNDER POSITIVE PRESSURE REV # SHEET # SKEET TITLE 2 * M0.01 LEGENDS AND NOTES DUCT UNDER NEGATIVE PRESSURE 1 * M2.01 LEVEL 1 HVAC PLAN 2 M2.02 LEVEL 2 HVAC PLAN TURNING VANES ELEVATION FROM F.F.L. (INSULATION AND DUCT FLANGES EXTEND 1'h" BELOW BOD CALLOUT) EQUIPMENT IDENTIFICATION THERMOSTAT /13.611M CEILING OR INUNE EXHAUST FAN 24" x 12' RETURN AIR GRILLE W/SOUNDLIPED CAN SUPPLY AIR ARROW RETURN AIR ARROW SPEED? SWITCH: FURNISHED BY HOLADAY-PARKS, INSTALLED BY ELECTR. CONTR. FLEXIBLE CONNECTION DUCT HEATER MANUAL VOLUME DAMPER MOTORIZED DAMPER BACK DRAFT DAMPER VERTICAL FIRE DAMPER (1 %2 HOUR) IN AIRSTREAM RUSKIN MODEL DIB2 STYLE A HORIZONTAL FIRE DAMPER (1 %2 HOUR) IN AIRSTREAM RUSKIN MODEL DIB2 STYLE A VERTICAL FIRE DAMPER (3 HOUR) IN AIRSTREAM RUSKIN MODEL DIB23 STYLE A HORIZONTAL FIRE DAMPER (3 HOUR) IN AIRSTREAM RUSKIN MODEL DIB23 STYLE A BACK DRAFT DAMPER RUSKIN MODEL BD2/A1, LOCAL VELOCITY < 1500 FPM BACK DRAFT DAMPER RUSKIN MODEL BD2/A2, LOCAL VELOCITY < 2500 FPM BACK DRAFT DAMPER RUSKIN MODEL BD6, LOCAL VELOCITY < 3500 FPM HORIZONTAL COMBINATION SMOKE AND FIRE DAMPER VERTICAL COMBINATION SMOKE AND FIRE DAMPER SPIN -IN TAKE -OFF & VOLUME DAMPER INDICATES 14" x 14' O.D. SHEETMETAL WITH 1" SOUNDLINER (U.N.O.), 12" x 12" NET I.D. INDICATES UNLINED 12' x 12' S.M. DUCT INDICATES 12" x 12" I.D. DUCTBOARD INDICATES UNLINED 12" x 12' S.M. DUCT WITH INSULATED WRAP RISE OR DROP IN DIRECTION OF FLOW FLEXIBLE DUCT INDICATES FLAT OVAL DUCT SPIN -IN TAKE -OFF & VOLUME DAMPER WITH RIGID ROUND FIBERGLASS DUCT INDICATES AIRFLOW DIRECTION THROUGH THE PARKING GARAGE TO THE GARAGE EXHAUST FANS. DUCTLESS SPLIT HEAT PUMP SCHEDULE LEVEL ROOM MAKE INDOOR UNIT OUTDOOR UNIT REMARKS TAG LOCATION MODEL NOMINAL ENT. DB/WB COOLING (MBH) HEATING MBH047f ELECTRICAL DATA EERTON SEER HSPF ECON (Y/N) MIN. OSA WEIGHT (LLS) TAG LOCATION MODEL ELECTRICAL DATA SOUND PRESSURE dB(A) WEIGHT (LBS) TOTAL SENS. VOLTS/PH MCA VOLTS/PH MCA 1 110 FUJITSU DXHP-1-1 110 ASU18RLF 1.50 80/67 18.0 - 21.6 203-208/1 0.3 13.3 22.0 10 N 0 31 CU -1-1 ROOF AOU18RLXFW 203-208/1 14.5 49 135 1,2,3,4,5,6,7 1: OUTDOOR UNIT WIRING AND DISCONNECT BY E.C. SINGLE POINT POWER CONNECTION. 2: PLUMBING CONTRACTOR TO ROUTE CONDENSATE TO APPROVED PLUMBING RECEPTICAL 3: NO SPRING OR NEOPRENE ISOLATION REQUIRED. 4: T -STAT PROVIDED WITH UNIT, INSTALLED BY C.C. 5: POWER WIRING FROM OUTDOOR UNIT TO INDOOR BY EC. EC TO DETERMINE IF ADDITIONAL DISCONNECT FOR INDOOR UNIT IS REQUIRED PER CODE. 6: SEER AND HSPF RATINGS PER AHRI STANDARDS. • U ..SERVES ELECTRO C E ENT ROOM. NO AIRSIDE ECO MIZER PRO ED, LIZIN EXC TIO U C 4.1 T AT FAN SCHEDULE FAN NUMBER TENANT AREA SERVED MAKE TYPE MODEL CLASS VFD (Y/N) PERFORMANCE DATA HP VOLTS/ PHASE WGT. LBS. REMARKS CFM S.P. RPM BHP EF -2-1 SANFORD BROWN BREAK ROOM PANASONIC INLINE FV-20NLF1 - N 200 0.4 1154 - 57W 120/1 17 1, 2, 3 1: WIRING AND DISCONNECT BY E.C. 2: MANUAL STARTER W/OVERLOAD PROTECTION SHALL BE PROVIDED AND INSTALLED BY E.C. 3: LINE VOLTAGE (120V) TIME CLOCK SHALL BE PROVIDED BY C.C. AND INSTALLED BY E.C. * INCLUDED IN THIS ISSUE LOT 3 OF CIT, OF TL WILA SHORT PLAT NO L97-0049 RECORDING NO 9711069009 SAID SHORT PLAT DEFINED - PORTION OF E 1/2 OF NW 1/4 OF SE 1/4, BEGIN NE CORNER OF SAID E 1/2 BEING N 88-05-42 W 1339.34 FT FROM NE CORNER OF SE 1/4 TH S 01-47-29 W 1322.34 FT TO SOUTHEAST CORNER TH N 87-55-02 W 659.35 FT TO W UNE OF E 659.34 FT OF SAID E 1/2 TH N 01-47-29 E 1320.30 FT TO N UNE OF SAID E 1/2 TH S 88-05-42 E 659.34 FT TO POB LESS PORTION FOR 59TH AVE SOUTH LESS PORTIONS FOR STREETS AS CONVEYED BY DEED, RECORDING NO 7907120770 LESS PORTION CONVEYED TO CITY OF TUKWILA FOR ROAD BY DEED, RECORDING NO 9408290327 1. RELOCATE THREE (3) DIFFUSERS FOR NEW SPACE LAYOUT. 2. INSTALL ONE (1) INLINE EXHAUST FAN FOR BREAK ROOM. REVIEWED FOR COMPUANCE Via MAY 2 7 2016 ACi `ukwlia Me. yK BUILDING DIVi- SON Ram rOV18W Ss FOYRI is SUbjact to errmrs and oma^sir�y .,. Approval of consiruciion dMilments does not aurhej iza d PL of approvod � i , anad: BY City of I Ok ilaw BUILDING DIVISION SFPPirMTE PEP-;g1iT REQUIRED FOR: 13 M Chanicd Icctdcal ;7rplumbbV as Plft CIV of Tukwila REVISIONS No changes shalt be made to the scope of work without prior approval of Tt.skwila Building Division. RCv1.;iens will require a new plan submittal end may include additional plan review fees. 0 RECEIVED CITY OF TUKWILA MAY 2 4 2016 PERMIT CENTER CITY APPROVAL Mechanical Solutions a Energy Services Building Controls 9 Service & Maintenance 4600 S. 134TH PLACE SEATTLE, WA 98168 a (206) 248-9700 HOLADAYPARKS.com WA LICENSE NUMBER: HOLADPI379NO PROJECT DESIGN TEAM Designed bv: RL Drawn by: MLK, MV Approved by: Job Number. 67016 Filename: M001.DWG APPROVED FOR CONSTRUCTION ISSUE NAMEIDATE PENDING CITY APPROVAL 5/24/16 REVISION'S - No. Date By Description 1 5/4/16 RL PHASE I PERMIT / CD 2 5/24/16 RL PHASE II PERMIT/ CD SHEET TITLE LEGENDS & NOTES SHEET NUMBER �u wmrta evm, n� oa�w++m "aaa w un raw ro�.at�to�r.vuws, wc. w aNtr or two ooau�crtr.ar ee �vnaouc5e i" un rowt at"r.wr.tEwm wrt�wur vewaww wwmrn raw �uuwr vuus, we 0 10 _ LEVEL 2 HVAC PLAN r wAm •Vr • f -Or A° t7' '' z Mechanical Solutions o Energy Services Building Controls r Service & Maintenance 4600 S. 134TH PLACE SEATTLE, WA 98168 . (206) 248-9700 HOLADAYPARKS.com WA LICENSE NUMBER: HOLADPI379N0 PROJECT D� io 600 I�� to RECEIVED CITY OF TUKWILA MAY 2 4 2016 PERMIT CENTER LINETYPE LEGEND EXISTING CONSTRUCTION = NEW CONSTRUCTION — — — — — — — = FUTURE CONSTRUCTION — — — — — — — = DEMOLITION TENANT BOUNDARY CITY APPROVAL DESIGN TEAM Designed bv: RL Drawn by: MLK, MV Approved by: Job Number. 67016 Filename: M202.DWG REGISTRATION 5/24/16 APPROVED FOR CONSTRUCTION ISSUE NAMEIDATE PENDING CITY APPROVAL 5/24/16 REVISIONS No. Date By Description 2 5/24/16 RL PHASE 11 PERMIT/ CD ISSUE SHEET TITLE LEVEL 2 HVAC PLAN SHEET NUMBER All.wartsnesERnM THEM DPAYHHOs slaw WAW rain TO Ha AMY -PMNs, NG HOPM OF THs DOOMEM MWOE qEP MCEDMMY FaN asffVMV AMWTH=ftWS5MWWRTWOFWWHQAWYPMH4W-