HomeMy WebLinkAboutPermit M16-0127 - SEATTLE CHOCOLATES - CHILLER REPLACEMENTSEATTLE CHOCOLATES
M16-0127
olCity of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670
Inspection Request Line: 206-438-9350
Web site: http://www.TukwilaWA.Rov
Parcel No: 3523049085
Address: 1180 ANDOVER PARK W
Project Name: SEATTLE CHOCOLATES
MECHANICAL PERMIT
Permit Number: M16-0127
Issue Date: 8/16/2016
Permit Expires On: 2/12/2017
Owner:
2015
National Electrical Code:
Name:
DANELLIE LLC
2015
Address:
1180 ANDOVER PARK WEST,
International Mechanical Code Edition:
2015
TUKWILA, WA, 98188
2014
Contact Person:
2015
WA State Energy Code:
Name:
MARK RIEGEL
Phone: (206) 793-0491
Address:
3215 S 116TH ST, TUKWILA, WA,
98168
Contractor:
Name:
CARRIER CORP
Phone:
Address:
3215 S 116TH ST, STE 133, TUKWILA,
WA, 98168
License No:
CARRI**342PP
Expiration Date: 4/27/2017
Lender:
Name:
Address:
, , ,
DESCRIPTION OF WORK:
REPLACE EXISTING CHILLER WITH NEW CHILLER OF LIKE KIND. CHILLED WATER PUMPS TO BE REPLACED AS WELL
TO ACCOMMODATE LARGER CAPACITY
Valuation of Work: $52,841.00 Fees Collected: $905.98
Type of Work: REPLACEMENT Electrical Service Provided by: PUGEST SOUND ENERGY
Fuel type: ELECT Water District: TUKWILA
Sewer District: TUKWILA
Current Codes adopted by the City of Tukwila:
International Building Code Edition:
2015
National Electrical Code:
2014
International Residential Code Edition:
2015
WA Cities Electrical Code:
2014
International Mechanical Code Edition:
2015
WAC 296-466:
2014
Uniform Plumbing Code Edition:
2015
WA State Energy Code:
2015
International Fuel Gas Code:
2015
Permit Center Authorized Signature:
I hearby certify that I have read and examined this permit and know the same to be true and correct. All
provisions of law and ordinances governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other
state or local laws regulating construction or the performance of work. I am authorized to sign and obtain this
development permit anjd agree to the conditions attached to this permit. �Y
Signature: y Date:
Print Name: �f G t'� �t S Alf
This permit shall become null and void if the work is not commenced within 180 days for the date of issuance, or if
the work is suspended or abandoned for a period of 180 days from the last inspection.
PERMIT CONDITIONS:
***MECHANICAL PERMIT CONDITIONS***
All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila
Permit Center (206/431-3670).
All permits, inspection record card and approved construction documents shall be kept at the site of work
and shall be open to inspection by the Building Inspector until final inspection approval is granted.
PERMIT INSPECTIONS REQUIRED
Permit Inspection Line: (206) 438-9350
1800 MECHANICAL FINAL
0701 ROUGH -IN MECHANICAL
CITY OF TUKWILA
Community Development Department
Permit Center
• 6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http://www.Tukwi]aWA.gov
Mechanical Permit No. �A N, "1 *1
Project No.
Date Application Accepted:
Date Application Expires: _
use
MECHANICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
**please print**
SITE LOCATION
King Co Assessor's Tax No.: 3523049085
Site Address: 1180 Andover Park W, Tukwila, WA 98188 Suite Number: Floor:
Tenant Name: Seattle Chocolates New Tenant: ❑ .....Yes ®..No
PROPERTY OWNER
Name: Danellie LLC
Address: 1180 Andover Park W
City: Tukwila State: WA Zip: 98188
CONTACT PERSON — person receiving all project
communication
Name: Mark Riegel
Address: 3215 S 116th St
City: Tukwila State: WA Zip: 98168
Phone: (206) 793-0491 Fax:
Email: mark.riegel@carrier.utc.com
Valuation of project (contractor's bid price): $ 52,841
Describe the scope of work in detail:
MECHANICAL CONTRACTOR INFORMATION
Company Name: Carrier Corporation
Address: 3215 S 116th St
City: Tukwila State: WA Zip: 98168
Phone: (206) 439-0097 Fax:
Contr Reg No.: CC CARRI**342VJ Exp Date: 12/31/2016
Tukwila Business License No.: BUS -0100063
Replacing existing chiller with new chiller of like kind. Chilled water pumps to be replaced as well to accommodate larger
capacity.
Use: Residential: New .......... ❑ Replacement ........ ❑
Commercial: New .......... ❑ Replacement ........ m
Fuel Type: Electric..... LZ Gas ....... ❑ Other:
H:Wpplications\Forms-Applications On Line\2016 ApplicationsWechanical Permit Application Revised 14-16.docx
Revised: January 2016 Page 1 of 2
bh
Indicate type of mechanical work being installed and the quantity below:
Unit Type
Qty
Furnace <100k btu
Residential, Nighttime
Furnace >100k btu
Industrial
Floor furnace
55 dB(A)
Suspended/wall/floor
mounted heater
57 dB(A)
Appliance vent
Commercial
Repair or addition to
heat/refrig/cooling
system
1
Air handling unit
<I0,000 cfm
65 dB(A)
Unit Type
Qty
Air handling unit
>I0,000 cfm
Residential, Nighttime
Evaporator cooler
Industrial
Ventilation fan
connected to single duct
55 dB(A)
Ventilation system
57 dB(A)
Hood and duct
Commercial
Incinerator — domestic
1
Incinerator —
comm/industrial
65 dB(A)
Unit Type
Qty
Fire damper
Residential, Nighttime
Diffuser
Industrial
Thermostat
55 dB(A)
Wood/gas stove
57 dB(A)
Emergency enerator
Commercial
Other mechanical
equipment
1
60 dB(A)
65 dB(A)
Boiler/Compressor Qty
0-3 hp/100,000 btu
3-15 h /500,000 btu
15-30 hp/1,000,000 btu
30-50 hp/1,750,000 btu
50+ h /1,750,000 btu
Noise:
Mechanical units need to be in compliance with the Tukwila Noise Code. Maximum permissible sound levels are based on from where the sound is
created and where the sound is heard. Additionally, if sound can be heard from within a house at night in a residential zone it may not be allowed.
For more details, see TMC 8.22
District of Sound
Producing Source
District of Receiving Property
Residential, Daytime*
Residential, Nighttime
Commercial
Industrial
Residential
55 dB(A)
45 dB(A)
57 dB(A)
60 dB(A)
Commercial
57 dB(A)
47 dB(A)
60 dB(A)
65 dB(A)
Industrial
j 60 dB(A)
50 dB(A)
65 dB(A)
70 dB(A)
*Daytime means 7AM-IOPM, Monday through Friday and 8AM-IOPM, Saturday, Sunday and State -recognized holidays.
A few sounds are exempt from the noise code, including:
Waming devices;
Construction and property maintenance during the daytime hours (7am-1 Opm);
Testing of backup generators during the day.
PERMIT APPLICATION NOTES -
Value of construction — in all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the permit center to comply with current fee schedules.
Expiration of plan review — applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The building official may grant one extension of time for additional periods not to exceed 90 days each. The extension shall be requested in writing
and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDINGOWNEROR AUTHORIZED AGENT:
Print Name: Geoff Vestman
Mailing Address: 3215 S 116th St
H:\Applications\Forms-Applications On Une\2016 Applications\Mechanical Permit Application Revised 14-16.docx
Revised: January 2016
bh
08/09/2016
Day Telephone: (206) 450-1387
Tukwila WA 98168
City State Zip
Page 2 of 2
DESCRIPTIONS
PermitTRAK
1
$731.75
M16-0127 Address: 1180 ANDOVER PARK W
Apn: 3523049085
$731.75
MECHANICAL
$696.90
PERMIT ISSUANCE BASE FEE
R000.322.100.00.00 0.00
$32.50
PERMIT FEE
11000.322.100.00.00 0.00
$664.40
TECHNOLOGY FEE
$34.85
TECHNOLOGY FEE
TOTAL FEES PAID BY RECEIPT: .. 196
11000.322.900.04.00 0.00
$34.85
$731.75
Date Paid: Tuesday, August 16, 2016
Paid By: SEATTLE CHOCOLATES.
Pay Method: CREDIT CARD 005291
Printed: Tuesday, August 16, 2016 10:11 AM 1 of 1
tWSYSTEMS
Date Paid: Tuesday, August 09, 2016
Paid By: GEOFFREY VESTMAN
Pay Method: CREDIT CARD 031324
Printed: Tuesday, August 09, 2016 2:02 PM 1 of 1 CI?
SYSTEMS
INSPECTION RECORD
Retain a copy with permit 17KI 0 _�
INSPECTION NO. PERMIT NO
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 981 (206) 31-3670
Permit Inspection Request Line (206) 438-9350V/1'17-41 . i, $�
Proiect: _ ITvve of In§pection:
ress:
IAIAL
Call
ate � � t�d:
Z1
A e- K
-7qg -Oqq
%Approved per applicable codes. Corrections required prior to approval.
I paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
M0.
0
COVER
PAGE
M 1.0
SITE
PLAN
M 2. 0
M 3. 0
M 4. 0
CARRIER
ur A Unfted recLnoloafem Comp
CARRIER COMMERCIAL SERVICE
3215 SOUTH 116TH STREET
TUKWILA. WA 98168
PHONE: 206-439-0097
EQUIPMENT SCHEDULE
FLOOR
SYSTEM
Job Name: SEATTLE CHOCOLATE
Job Number: 675500248
Job LocaUon:TUKWILA WASHINGTON
Drawing Number: M-0.0
Date. 1 AUG 2016
Supercedes:
Rev. REV 0 PERMIT
Drawn By; MARK RIEGEL
PIAN (EQUIPMENT
LAYOUT
Description: DESCRIPTION
Comments:
DRAWING NOT TO SCALE. RELATIVE SIZES AND
LOCATIONS OF EQUIPMENT ARE APPROXIMATE.
REVISIONS
FI-1--10-
changes shall be mar'^ to the scope
of, went without prior r=,^ -^,vpl of
Tukwila Sui!ding D', -
,v;3ion3 will rt' wire a 1 1 �:!abmittai
ads"_;on, l r.„,—_,
E Con
Permit moo.
Plon raAew approval is subject to errors and om*13slons.
Approval of construction documents does, riot authorize
tie violation of any adopted coda or ordinance. Receipt
of approved Field ndn� :`�; r, is acknowledged:
®y:
Date:
City of j u- .
BUILDING
LOCATION
���o, ricai
�P►��::tii;�g
, Gas Pip!ng
City of Tu!,av la
SEATTLE CHOCOLATE
CHILLER REPLACEMENT
COVER PAGE
DRAWING M-0.0
SHEET 1 OF 5
—REV15WED FOR
CODE COMPLIANCE
APPROVED
AUG 16 2016
0—
City
ogTukwila
BUILDING DIVISIQ",I
RECEIVED
CITY OF TUKWILA
AUG 0 9 2016
PERMIT CENTER
-111'2'1
NOTES
1 PROJECT DESCRIPTION:
Chiller replacement
2 PROJECT ADDRESS:
1180 Andover Park W
Tukwila WA
3 PARCEL NUMBER: 1180
(1174 is same owner)
4 EQUIPMENT LOCATION:
outdoors, ground level
to the west of building
5 New pumps and chiller
installed at existing
equipment location.
6 Project includes no
rooftop equipment.
7 Equipment area is
fenced.
CARRIER
A United recbnologlee Compacy
CARRIER COMMERCIAL SERVICE
3215 SOUTH 116TH STREET
TUKWIIA, WA 98168
PHONE: 206-439-0097
lG, i
N H.
J4�
1' 1
• gad r�. iia=' Rmr aL`�ft agE' ? X71 i ij5[ ev i IL
4
4 J
3 a
i
R .
300 FEET -I
Job Name: S 611L.L GriOGVLAIL Description: SITE PLAN
Job Number: 675500248
Job Location:TUKWILA WASHINGTON
Drawing Number-• M-1.0 Comments:
Date: 1 AUG 2016 SCALE — AS INDICATED
Supercedes:
Rev: REV 0 PERMIT
Drawn By: MARK RIEGEL
J - AUG 16 2016
NORTH
SEATTLE CHOCOLATE `f' PEI
CHILLER REPLACEMENT
City of Tukwila
SITE PLAN
DRAWING M-1.0 BUILDING DIVISION
SHEET 2 OF 5
EIVED
TUKWILA
09 2016
CENTER
CHILLER EXISTING NEW
Model Carrier 30GTN015—D-601 Carrier 30RAP0306D—OG100
Capacity 14.3 Ton 28.3 Ton
Operating Wt 1640 Ib 1283 Ib
PUMPS EXISTING NEW
Model Paco 12-12705 Taco KV -1509
Capacity 40gpm/30'/1 hp 60gpm/75'/5hp
NOTES
1 EXISTING EQUIPMENT MODELS ARE NAMEPLATE INFORMATION
2 EXISTING EQUIPMENT CAPACITIES AND SIZES ARE FROM NAMEPLATE AND PRODUCT DATA
3 NEW EQUIPMENT IS BASIS OF DESIGN. CAPACITIES FROM MANUFACTURER SUBMITTALS.
CARRIER
A United Technologies company
CARRIER COMMERCIAL SERVICE
3215 SOUTH 116TH STREET
TUKWILA. WA 98168
PHONE: 206-439-0097
Job Name: SEATTLE CHOCOLATE
Job Number: 675500248
Job Location: TUKWILA WASHINGTON
Drawing Number: M-2.0
Date: 1 AUG 2016
Supercedes:
Rev: REV 0
Drawn By: MARK RIEGEL
Description: DESCRIPTION
Comments:
DRAWING NOT TO SCALE. RELATIVE SIZES AND
LOCATIONS OF EQUIPMENT ARE APPROXIMATE.
SEATTLE CHOCOLATE
CHILLER REPLACEMENT
EQUIPMENT SCHEDULE
DRAWING M-2.0
SHEET 3 OF 5
REVIEWED FOR
CODE COMPLIANCE
AAViROVED
AUG 16 2016
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
AUG 0 9 2016
PERMIT CENTER
NOTES
EXISTING CHILLER (DEMO) / / 1 CWHP = CHILLED WATER PUMP
2 ALL EQUIPMENT AT GRADE LEVEL OUTDOORS
/ 3 EXISTING CHILLER AND EXISTING
I I
PRIMARY CHWP ARE REPLACED
PRIMARY CHWP
/ I I CONDENSING , / / SEE SCHEDULE M2.0
UNIT / , / 4 SUPPLY TANK, RETURN TANK,
RETURN I I
TANK / SECONDARY CHWP, AND
/ / CONDENSING UNITS ARE ALL EXISTING
171 / / , I I / EQUIPMENT AND REMAIN IN PLACE
gg / / / 5 LOCATION OF EXISTING CHILLER SHOWN
SECONDARY CHWP I I / / AS DOTTED LINE
SUPPLYI I CONDENSING
TANK UNIT
/ ZFD / / , " REVIEWED FOR
CODE COMPLIANCE
NEW CHILLER / / / APPROVED
297 CHAINLINK FENCE / / / / AUG 16 2016
(APPROXIMATE) , �
City of Tukwila
/
BUILDING IDIVISION
RECEIVED
CITY OF TUKWILA
AUG 0 9 20%
PERMIT CENTER
NORTH
//� SCALE(INCHES):
120
Job Name: SEATTLE CHOCOLATE Description: DESCRIPTION
CARRIER SEATTLE CHOCOLATE
Job Number: 675SO0248 p CHILLER REPLACEMENT
A United Technologies Company Job Location: TUKWILA WASHINGTON Comments:
Drawing Number: M-3.0
CARRIER COMMERCIAL SERVICE Date: 1 AUG 2016 SCALE AS SHOWN
3215 SOUTH 116TH STREET Sup""es: REv LOCATIONS OF EQUIPMENT ARE APPROXIMATE. FLOORPLAN (EQUIPMENT LOCATION)
TUKWILA, WA 98168°' °� DRAWING M-3.0
PHONE: 206-439-0097 Drawn By: MARK RIEGEL SHEET 4 OF 5
CHILLED WATER
CHILLED WATER
SUPPLY RETURN
SUPPLY RETURN
TAN K TAN K
F
L I
SECONDARY
PRI MARY I
CHWP
j CHWP
I I
I I
I I
CARRIER
A United SecLnolWea Company
CARRIER COMMERCIAL SERVICE
3215 SOUTH 116TH STREET
TUKWILA, WA 98168
PHONE: 206-439-0097
Job Name: SEATTLE CHOCOLATE
Job Number: 675SO0248
Job Location: TUKWILA WASHINGTON
Drawing Number. M-4.0
Date: 1 AUG 2016
Supercedes:
Rev: REV 0 PERMIT,
Drawn By. MARK RIEGEL
Description: SYSTEM LAYOUT
Comments:
DRAWING NOT TO SCALE. RELATIVE SIZES AND
LOCATIONS OF EQUIPMENT ARE APPROXIMATE
NOTES
1 CWHP = CHILLED WATER PUMP
2 EXISTING CHILLER AND EXISTING
PRIMARY CHWP ARE REPLACED
PIPING SHOWN IN DOTTED LINES
IS REPLACED TO THE EXTENT
REQUIRED BY EQUIPMENT INSTALL
3 SUPPLY TANK, RETURN TANK
SECONDARY CHWP AND PIPING
SHOWN IN SOLID LINES IS
EXISTING AND REMAINS IN PLACE
4 PIPE SIZES TO MATCH EXISTING
1-1/2" COPPER
(TYPICAL)
6. Z - o t s
REVIEWED PQM
RECEIVED
CfTY OF TUKWILA
CODE COMPLIAMC
APPROVED
AUG 0 9 2016
AUG 16 2016
PERMIT CENTER
City of Tukwifa
CHILLER REPLACEMENT
SYSTEM LAYOUT (CHILLED WATER PIPING)
DRAWING M-4.0
SHEET 5 OF 5
Carrier
:A
SUBMITTAL
Project
Seattle Chocolates
Date
Thursday, July 21, 2016
Mechanical Contractor
Carrier Service
Kendal Martin
Norby Company
3805 108th Ave. NE
Bellevue WA 98004
RE IEWED FOR
CODAEPP�OVEDNCE
AUG 16 2016
City of Tukwila
BUILDING DTVI_ II N
1=ECE,IVED
CITY OF TUKWILA
AUG 0 9 2016
PERMIT CENTER
VtU-o[i-1
Table Of Contents
Project: Seattle Chocolates 07/21/2016
Prepared By: Kendal Martin 12:14AM
30RAP30 __.......
UnitReport........... ...................... ...... _------- _._ ..__ .__ - _.. ..... ........
. - ..... ......... .... - ...... _... ......... ......... 4
Certified Drawing __
.5
FieldWiring Diagram - - ...... ......... ........
. ........... ... ._._...... -..... ...... __.. ........_ _ _6
Acoustic Summary_._ - .. .-.- __. - .... ....................................
10
Guide Specifications... ....... ... ..... .__.............
-........................... ..... _ .. . I ........ . ....... 11
Detailed Performance Report ......... _... _ ....____. __. . _ .. _... _._..-. -._- ..................
_ _ __. _ ........_... __.. - _ --_ 15
Packaged Chiller Builder NACO 3.49r Page 2 of 17
30RAP30
Project: Seattle Chocolates 07/21/2016
Prepared By: Kendal Martin 12:14AM
30RAP30
Tag Cover Sheet
Unit Report
Certified Drawing
Wiring Diagram
Performance Report
Acoustic Summary
Guide Specification
Detailed Performance Report
Packaged Chiller Builder NACO 3.49r Page 3 of 17
Unit Report For 30RAP30
Project: Seattle Chocolates 07/21/2016
Prepared By: Kendal Martin 12:14AM
Unit Information
Tag Name:. --
30RAP30
Model Number: .......... ...........
30RAP030
Condenser Type:....-..-. ._ ......
Air Cooled
Compressor Type: _ __- _.._.__ .-..__-....___..-_.._.Scroll
Nameplate Voltage:__ ___._... ..... ______....
_460-3.60
Quantity:._... - _.............__._................ .............................
1
Manufacturing Source: .............. Charlotte, NC USA
Refrigerant:.. . _
....... R410A
Independent Refrigerant Circuits:..
_ __ .._.__.__ ....1
Capacity Control Steps:.._.._ _. __--._._.
_._.__-.._._._.22
Minimum Capacity:.. --- _ _ -
_..___. --17.0
Shipping Weight: ... .....
.................1369
Operating Weight: .................... ........_........_._1283
Unit Length:__ _ ...
.89
Unit Width:. ..__ ..._
41
Unit Height:. __........ .... . - -.- ----- .__ ......
..... ..._._ -....79
Accessories and Installed Options
Cooler Heater
Micro Channel
Low Sound
Digital Compressor
V -Ph -Hz Single Point
High Efficiency Variable Condenser Fan
Ib
Ib
in
in
in
Chiller Warranty Information (Note: for US & Canada only)
First Year - Parts Only (Standard)
Start -Up with 1 st Year Carrier CCS Labor - 1st Unit
Ordering Information
Part Number Description Quantity
30RAP0306D-OG100 Packaged Chiller 1
Base Unit
Cooler Heater
Micro Channel
Low Sound
Digital Compressor
Single Point
High Efficiency Variable Condenser Fan
Packaged Chiller Builder NACO 3.49r Page 4 of 17
Certified Drawing for 30RAP30
6epared
oject: Seattle Chocolates 07/21/2016
By: Kendal Martin 12:14AM
.ER ENIR1
P 11 NIOUi
;��A
-LIN
9 16PI I 2'
9 19161 1'
9 19161
36 f9, xl HI x. l
--
I
ea II'19] NIY J DO
pp`I�nl�
II 1 A2 110611 MIV.
v0IE0
11
I
I�
co—ESSOP
ACf E36
.
I p0 - UP OA O,NE 3116[ DISIAUCI "1
110- LINE 1IMPERA,u AE DIME
1. 0 I 111.x1 '1- .1 PAOv 10[D LOA IDIAIM HELD 1O1E1 11� D.
SE [x XOi[ Oe
I
i
AI
I �90A D[A xf[
(I- NO(C RI -11D DL?EROS OX 1 EID 11.91 5111X4.
,D SCAI[I
J. 01 131 Ill IED NOLI USED LOA MINTING UA11.
I
A, 1x11 Is, -1 fU-NCES AS IoEOVS
p? END .Y01 IRIC1.
1
0 C
IIS
�I lIP. ftOW
P�N[l SS ]DDE 'Aid11SZi3] P�A SILO SUALAC[.
X -:
- S Si[ iA91[ I.E. N; GIME XSIOY 101 S-DAAD 'Ax OA -DE
sEDID Ax m la'
6 CAIII[ X lLA 1IT
DBE SNAxpI ur",
j
� ° 1
TOP VIEW
1 DXI, [Ax [pC Os1 IrE ;'L', LI Ff PIXxF,6
HAIR COxx'[DgllOxs R(f FSS EJ 2 IxC xES INS IeE Ux
ul r. A A xD v[xn xc xoLls AAE I NPI
I
I 1
1
I
1
I
OIxE xSI OxS IN I I APE IN HI 11-t AS
SOEL VOIF L Ix
I
O O
II
I
BB to Ii�a1
JI
I II
u
1
�I�
AI UL :OU.D LAX 09110.
IPI C10R1 AL1` 0x1 x1
IB I,O10 11—
AIR FtOv
J6 151x1 vix
6[[ X0,1 A5
WATER III-
-111 11—\
9 sz ita el
e
6EAv1Cf
XLCE SS
e
\
i a
xINGE DOi.(AB'[6S
co—ESSOP
ACf E36
.
Dc'
IIoDSEE I,,` a
21 06 [51A P91 —J.. 13
FRONT VIEW
�I152. x1
1X 1106.91
ii59:61
R 9
Dp 1ua sp ua II
~ i6V N0,[ 1 6(F x011Y 3
10[[LxO�E 1lj lE viA1.
1X 01/1 122.21 XO
llf lD is IRIX 11x1 NG EN13v
VLD AL<f 6S G91I1
�6(F ......
EIAIt A
(,19.61
RIGHT VIEW �;IA
`. ppxurz Il FOR GREENSPEED OPTION
Packaged Chiller Builder NACO 3.49r Page 5 of 17
Field Wiring Diagram for 30RAP30
Project: Seattle Chocolates 07/21/20161
Prepared By: Kendal Martin 12:14AM1
1. FACTORY WIRING IS IN ACCUAAMCC WITH UL 1995 STANDARDS FIELD IGDIFICATIONS '{"S0
OR MOTIONS MUST DC IN CUVLIANCE VRH ILL APPLICARE CORS AtmHAA[
2, &1 UNITS ON COUPLES MAWE SINGLE PRINT PRIMARY POWER UNKC71 M. MAIN POWER
UST RE SUPPLIED FROM A FIELD OR FACTORY STIPPLED DISCONNECT.
3 WIRING FOR MAIN FIELD SUPPLY MIST BE RATED 75G USE COPPER COMDUCTERS CHAT.
a INCOMING WERE SIZE RANGE FOR TERMINAL RLUCA WIN MCA UPTD 1h AMPS TERMINAL BLOCK POWER ENTRY
IS 14 AVG TO 210 FOA I0-61 TO! CHILLERS .
h INCDXING W(E SIZE RANGE FOR TEAMINAL &GEN WIN ICA FROM IMI AMPS 3B0 VRi
TO 335 AMPS IS 6 MG r0 409 XCMIL FDR ID -60 TON CHILLERS O.I
c INCOMING WINE SIZE RANGE FOR 7EAMINAL KGON WIN NU LIPID - NPS RVDRAL
IS 2 AVG TO 60KACNTL FLA A -I% TOM GRILLER.
d INCOMING WITS SIZE RANGE FOR TERMINAL BLOCK WITH MCA FROM 420.1 NPS roHP
TO 760 AMPS IS 6 AVG TO 500 XpIL(TWO OPENINGS PER PRE) FOR 70-150 TON CHILLERS, e0
e. INCOMING VIRE SIZE RANGE FOR MUNI FUSE! DIS@TfCT WIIN MU LETO 100 NPS IS I— TO 370
f ME -11G VINE SIZE RANGE FCR NUN -FUSE DISCINNI3:C WITH MA FROM IMI AMS
TO 250 AMPS IS 6AVG TO 350 MCXIL,
C IRS MING vG TO E RAN E FORD OM FIGS PER POLE) WITH MICA FROM 2501 TO 6W AMS
1 I
1 1
4. IEFFR TO DECEIT® DIMENSIONAL ENT DRAWINGS FOR EXACT LOCATIONS IR MIN
POWER AND [CNTR0. POWER ENTRANCE LOCATIONS
1 I
3 TERNI 21 AND 21 OF THE LVE ARE [OR DONOR 6 GRILLED VATS RMI I[VPI! )STATOR. S 1
TERMINALS 21 AND 24 OF THE R ARE FOR D WATT OF WILLED WATER A SEA ED. IS STARTER
EM MAXIMUM ISMO ALL
FOR THE CHILLED WATER POP RELAY IS 5 VA $EPEE➢, 10 V4 INRUSH 41 24 V. 1 1
FIELD POWER SUPPLY IS XDT REOIIIED
1 I
6. i^RMIHALS A AND 21 OF LVr , 1 FOR AN RWM RELAY,IHC MAXIMUM LOAD ALLOWED FDR THE I
VIM RELAY IS 5 VA $G1E0, 10 VA INRUSH AT 24v. FIELD PCICR StPRY IS NOi REDOREO.
7, MAKE APP9PRCONNECTIONS TO LVT AS SHOWN FOR ENERGY MONAGENENT BOARD OP TONS. THE 9 FIELD POVER SUPPLY
COI TS FOR DEMAND LIMIT AND 1U ROME OPTIONS MUST RE RATED FOR DAY CIRCUIT APPLICATIGH 1
L
CMARIM M
E O HANDLING A 24VAC LOAD UP TO 50 STA ION O' �TIDMAL ENERGY MANAGEMENT BOARD RECAJ REO. —I— - _ _I- - _ -
O REMOVE AVFfR IETVEEN TERNNA-S 11 AND 17 WHEN FIELD CWPI IS INSTALLED LVT�J iCONTROL � DISCOONN¢TE CI'i�RANCH 1
9. TERNINALS 13 L 14 OF T85 ARE FOR FIELD EXTERNAL CONNECTIONS FW REMOTE On -OT. $fe APiE _ -MITE XDCE IT _ J
i1E CONTACTS MUST BE RATED FOA MY CIRCUIT 4PPLIATION CAPABLE OF HANDLING A
2NAC LOAD UP TO SOMA - LVT TERMINAL
LEGEND: II IL1�I �I+ I r�II I I TI+S� 4QQTEL
VARNIGV' "'K STRIP
GMEICAVREUGE K
1 I 1 1 1
CVP - CHILLED WATER POP o b b l T - H { - L , 41J I , I I yN d l HIM -FUSED DISCONNECT POWER EMERY
CVP - CULLED WATER PUMP MTEALOCN 1 I W-OrONT 1 1 1 TEAT "'
EMM - ENERGY NAMAFEMENT !®OLE I �y
LVr - LDV VRIAGE TERMINAL STRIP _ I N /LRA'1
BPr - LOW TEMPERATURE �J
I IBI O W I I I I I I I � \ b I I I I I I 3aR WELT
I DULY
COM d, 41 $I i 4-m :a
- - - FIELD -.TR WIRD. -I 1 =1 1 -'I 1 iqi< 1 1 J _ _ 1 Tan
- - FEED CONTRpL ViRMG NG tEMERATURE _ �� _ _ LES �_ _ _ 7NO E
FACTODAYINSTALLED WIRING C� L J XL J XL J SEC EIET IUTE 7 CVPI SR !UO 6 SEE NOTE 5 ® C
O FADY INSTALLED OFOON Sx1 �J SEE NOTE 7
7_77
L J I .NO
1 I 1
OR ILMND CTPDN6 I 1 1
m+ ww I1pH LINK SEE
SEE TMST 7 SEE NOTE > I
Network _ I —I
LI
Eo R
1 ID I ULT
Inn UPC _ J _ _I_ _L _ L _ _ _ _ _ —
Open - - - _ DISCONNECT'
RRANDH I
LyIR0. 1T
I � �tkt nOONR �R IRC- _ _ _ _ �
LL_1_J
NON-FUSED
TTI9 C
R vF e:vxFe SONN EIG T
Packaged Chiller Builder NACO 3.49r Page 6 of 17
Summary Performance Report For 3ORAP3O
Project: Seattle Chocolates 07/21/2016
Prepared By: Kendal Martin 12:14AM
r"WMA5NAP
Carrier,
_J
30RAP with Greenspeed®Intelligence
Unit Information
_ 28.3
Tons
Tag Name: _ _ . . _ _ ...... __.30RAP30
Fresh Water
kW
Model Number: __.. __.
_30RAP030
(hr-sqft-F)/BTU
Quantity: . _...... ... _ _.......
.. _ 1
°F
Manufacturing Source:.... Charlotte, NC USA
__......._54.00
Refrigerant:,_ - _. -
- ..._.R410A
_...__...__..67.8
Independent Refrigerant Circuits:
__._____.1
... _ _....... 11.8
Shipping Weight: _._._.... .... _......
- _1369
Ib
Operating Weight: ................ ................
_........1283
Ib
Unit Length: - _ _ _ --
-.. -.89
in
Unit Width: _ ...__ _ _ _ __...__
_.....-41
in
Unit Height: .......... .......... ..........____..
_ _ ..._ _ _.79
in
Chiller Pressure Drop*:....___.. ....... _
........ ._..17.9
ft wg
*Use Chiller Pressure Drop for sizing pumps.
This value
includes losses due to chiller piping, fittings, 40
mesh factory
supplied strainer and BPHX.
Evaporator Information
_ 28.3
Tons
Fluid Type: _____.___.____ ______...
Fresh Water
kW
Fouling Factor:...... ___..._ .......
_..... .... .00010
(hr-sqft-F)/BTU
Leaving Temperature: .... ... ..._......
_ _.. 44.00
°F
Entering Temperature: ...... __........
__......._54.00
*F
Fluid Flow:_._ _ _ ... _ _.......
_...__...__..67.8
gpm
Evaporator Pressure Drop*:. .......
... _ _....... 11.8
ft wg
*Refer to Chiller Pressure Drop for sizing pumps.
Condenser Information
Altitude:_ ..... _ .._.. - _ _ ___..._ __.___.. _.. __0 ft
Number of Fans: ............................................- __..2
Total Condenser Fan Air Flow: .__ __..19400 CFM
Entering Air Temperature:_ _ .. __... 95.00 °F
Integrated Pump Information
No Pump Selected
Performance Information
Cooling Capacity:._ .................._..... _ _.
_ 28.3
Tons
Total Compressor Power: ......... .... ......_
_ .30.7
kW
Total Fan Motor Power:_____ .__............
........ .67
kW
Total Unit Power (without pump): __
_ ....33.4
kW
Efficiency (without pump): ___ __..__._
10.18
EER
IPLV: _ .._ . _
....16.31
EER
Accessories and Installed Options
Cooler Heater
Micro Channel
Low Sound
Digital Compressor
Single Point
High Efficiency Variable Condenser Fan
Electrical Information
Unit Voltage: ... ... __..... ..............460-3-60 V -Ph -Hz
Connection Type: _ .. _ .Single Point
Amps
Electrical Electrical
Circuit 1 Circuit 2
MCA
66.3 —
MOCP
90.0 —
ICF
211.7 —
Rec Fuse Size
80.0
An uncoated Novation condenser coil was selected for this product. This is based on an installed location with postal code 98074 and
a non -corrosive localized environment.
Sound power measured in accordance with ANSI/AHRI Standard 370-2001.
Packaged Chiller Builder NACO 3.49r Page 7 of 17
Summary Performance Report For 30RAP30
Project: Seattle Chocolates 07/21/2016
Prepared By: Kendal Martin 12:14AM
} 'Certified in accordance with the AHRI Air -Cooled Water -Chilling Packages Certification Program, which is based on AHRI Standard
550/590 (I -P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at www.anddirectory.org.
Packaged Chiller Builder NACO 3.49r Page 8 of 17
Summary Performance Report For 30RAP30
Project: Seattle Chocolates 07/21/2016
Prepared By: Kendal Martin 12:14AM
Unit Parameters
31
Tag Name: -.__ -. - ._ . _ ......
_........30RAP30
Model Number:...._.............._-...._......._.__..-_._.._30RAP030
500
Condenser Type:.........__ ............._...-_........_
.._.__ Air Cooled
Compressor Type:..... _... .................
_... ...... .. . .__ - .. Scroll
Chiller Nameplate Voltage:......_.
.... ..... .__...._......460-3-60
Quantity:... .........
.. - - .1
Manufacturing Source:__.. __.
__...Charlotte, NC USA
Refrigerant:..-._._. - -_ - .._ - _._
...................._..R410A
Shipping Weight: - - .. ..__ - ................
._....... ......_......1369
Operating Weight:__.._ .... .... ................
... 1283
UnitLength:... __ _ -._....................
......... ._..... _....... ...89
UnitWidth:...__...._ _... ....... ... _._..........
..____._- _------- ----- --_41
Unit Height:_.. -- ...... __......... ___...
.. ..... - ...- ....79
Accessories and Installed Options
Cooler Heater
Micro Channel
Low Sound
fiV -Ph -Hz
Ib
Ib
in
in 1 - Chiller Height Above Ground
in 2 - Horizontal Distance From Chiller to Receiver
3 - Receiver Height Above Ground
(See Note 3)
Digital Compressor
Single Point
High Efficiency Variable Condenser Fan
Acoustic Information
Table 1. A -Weighted Sound Power Levels (dB re 1 picowatt). See note #1.
Octave Band Center Frequency, Hz
31
63
125
250
500
Ilk
2k
4k
8k
Overall
100% Load
39
59
72
78
83
84
84
78
70
89
75% Load
36
56
71
76
79
81
81
75
69
86
50% Load
37
55
65
75
76
79
79
73
70
84
25% Load
35
57
59
70
76
77
79
72
67
83
Table 2. A -Weighted Sound Pressure Levels (dB re 20 micropascals) calculated based upon user defined input for
dimensions 1, 2 and 3 as shown in above diagram. See note #2 and #3.
Octave Band Center Frequency, Hz
31
63
125
250
500
Ilk
2k
4k
8k
Overall
100% Load
12
32
45
51
55
56
56
50
42
62
75% Load
9
29
44
49
51
53
53
47
41
59
50% Load
9
28
37
48
49
51
52
45
43
57
25% Load
8
29
32
43
48
49
51
45
39
55
Notes: (1) Measurements performed in accordance with AHRI Standard 370 for air cooled Chillers.
(2) Chiller is assumed to be a point source on a reflecting plane.
(3) Without user defined input, the default dimensions used to construct Table 2 are as follows:
1 - Chiller Height Above Ground = 0.0 ft
2 - Horizontal Distance From Chiller to Receiver = 30.0 ft
3 - Receiver Height Above Ground = 3.0 ft
Packaged Chiller Builder NACO 3.49r Page 9 of 17
Acoustic Summary For 30RAP30
Project: Seattle Chocolates 07/21/2016
Prepared By: Kendal Martin 12:14AM
Please refer to Performance Output Summary or Detailed
Performance Report for Acoustic information
Packaged Chiller Builder NACO 3.49r Page 10 of 17
Guide Specification for 30RAP30
Project: Seattle Chocolates 07/21/2016
Prepared By: Kendal Martin 12:14AM
a
rrier
GUIDE SPECIFICATIONS —30RAP0306D-OG100
HVAC Guide Specifications
Air -Cooled Liquid Chiller
Size: 030
Part 1: General
SYSTEM DESCRIPTION
1.01. Microprocessor controlled, air-cooled liquid chillerfor outdoor installation, utilizing scroll compressors, lowsound fans,
electronic expansion valve, optional hydronic pump system, and fluid storage tank (storage tank on models 010-060 only).
1.02. With Greenspeed intelligence, all fans are controlled with variable speed fan drive motors. Chillersoftware shall be specifically
developed to coordinate optimal fan speed for application conditions and provide refrigerant circuit optimization, resulting in
higher part load efficiency and reduced acoustic levels.
QUALITY ASSURANCE
1.01. Unit shall berated in accordance with AH RI (Air -Conditioning, Heating and Refrigeration Institute) Standard 550/590, latest
edition (U.S.A.) and all units shall beASHRAE (American Society of Heating, Refrigerating and Air -Conditioning Engineers)
90.1 compliant.
1.02. Unit construction shall comply with ASH RAE 15 Safety Code, U L latest edition, and ASM E (American Society of Mechanical
Engineers) applicable codes (U.S.A. codes).
1.03. Unit shall be manufactured in a facility registered to ISO 9001 Manufacturing Quality Standard.
1.04. Unit shall be full load run tested at the factory.
DELIVERY, STORAGE AND HANDLING
1.01. Unit controls shall be capable ofwithstanding 150 F (66 C) storage temperatures in the control compartment.
1.02. Unit shall be stored and handled per unit manufacturer's recommendations.
Part 2: Products
EQUIPMENT
2.01. General:
A. Factory assembled, single -piece chassis, air-cooled liquid chiller. Contained within the unit cabinet shall be all factory
wiring, piping, controls, refrigerant charge (R -410A), and special features required priorto field start-up.
2.02. UnitCabinet:
A. Frame shall beofheavy-gage, galvanized steel.
B. Exteriorpanels shall be galvanized steel with a baked enamel powderor pre -painted finish.
C. Cabinet shall be capable ofwithstanding 500 -hour salt spray test in accordance with the ASTM (American Society for
Testing and Materials, U.S.A.) B-117 standard.
2.03. Fans:
A. Standard condenserfans shall be direct -driven, 9 -blade airfoil cross-section, reinforced polymerconstruction, shrouded -
axial type, and shall be statically and dynamically balanced with inherent corrosion resistance.
B. Standard condenserfans shall be direct -driven (VFD [variable frequency drive] controlled on units with Greenspeed
intelligence), 9 -blade airfoil cross-section, reinforced polymer construction, shrouded -axial type, and shall be statically and
Packaged Chiller Builder NACO 3.49r Page 11 of 17
Guide Specification for 30RAP30
Project: Seattle Chocolates 07/21/2016
Prepared By: Kendal Martin 12:14AM,
dynamically balanced with inherent corrosion resistance.
C. The variable speed drivesforthecondenserfans on 30RAP unitswith Greenspeed intelligence shall include a DC link
reactor.
D. Fan operation shall allowreduced sound levelsduring scheduled unoccupied operating periods. Manufacturerswithout
unoccupied reduced sound capabilityshall submit 1 /3octave band data and sound powerdata asmeasured accordingto
AHRI 370 as confirmation of unitsound characteristics.
E. Air shall be discharged vertically upward.
F. Fans shall be protected by coated steel wire safety guards.
2.04. Compressor/CompressorAssembly:
A. Fully hermetic, direct -drive, scroll type compressors.
B. Compressor motors shall be cooled by refrigerant gas passing through motorwindings and shall have either internal line
breakthermal and currentovedoad protection orextemal current overload moduleswith compressortemperature sensors.
C. Compressors shall be mounted on rubber in shearvibration isolators.
D. Staging of compressors shall provide unloading capability. Digital compressor unloading control shall be available as an
option (sizes 010-090 only).
E. Crankcase heaters are not required on sizes 010-060dueto very low refrigerant charge.
2.05. Cooler:
A. Cooler shall berated fora refrigerantworking-side pressure of 565 psig (3896 kPa) and shall be tested fora maximum
waterside pressure of 300 psig (2068 kPa) or 150 psig (1034 kPa) when optional hydronic package is installed.
B. Shall be single -pass, ANSI (American National Standards Institute) type 316 stainless steel, brazed plate construction.
C. Shellshall be insulated with 3/4 -in. (1 9mm) closed -cell, polyvinyl -chloride foam with amaximum Kfactorof 0.28.
D. Shall have one independent refrigerant circuit.
E. Cooler shall have optional factory -installed heater, to protect coolerfrom ambient temperature freeze down to -20 F (-29
C).
F. Unit shall be provided with a factory -installed flow switch.
G. All connections shall use standard V ctaulic-typefittings.
H. Coolerfluid inlet line shall have a40 mesh strainerjust ahead ofthe cooler.
2.06. Condenser.
A. Coil shall be air-cooled Novation® heat exchangertechnologywith microchannel (MCHX) coils and shall have a series of
flattubes containing a series of multiple, parallel flow microchannels layered between the refrigerant manifolds.
B. Coils shall consist of a two -pass arrangement. Coil construction shall consist of aluminum alloys forfins, tubes, and
manifolds in combination with a corrosion-resistantcoating.
C. Tubes shall be cleaned, dehydrated, and sealed.
D. Assembled condensercoils shall be leaktested and pressure tested at656 psig (4522 kPa).
2.07. Refrigeration Components:
A. Refrigerant circuit components shall include filter drier, moisture indicating sight glass, electronic expansion device, and
complete operating charge of both refrigerant R-410Aand compressoroil.
2.08. Controls, Safeties, and Diagnostics:
A. Unit controls shall include the following minimum components:
1. Microprocessorwith non-volatile memory. Battery backup system shall not be accepted.
2. Separate terminal blockfor powerand controls.
3. Control transformerto serve all controllers, relays, and control components.
4. ON/OFF control switch.
5. Replaceable solid-state controllers.
6. Pressure sensorsshall be installed to measuresuction and discharge pressureforeach circuit. Thermistors shall be
installed to measure coolerentering and leaving fluid temperatures, outdoorambienttemperature, and suction
temperature. Provision forfield installation of accessory sensorto measure compressor return gastemperature.
B. Unit controls shall include the following functions:
Packaged Chiller Builder NACO 3.49r Page 12 of 17
Guide Specification for 30RAP30
Project: Seattle Chocolates 07/21/2016
Prepared By: Kendal Martin 12:14AM
1. Automatic circuit lead/lag for dual circuit chillers.
2. Hermetic scroll compressors are maintenancefree and protected byanauto-adaptive control that minimizes
compressorwear.
3. Capacity control based on leaving chilled fluid temperature and compensated by rate of change ofretum-fluid
temperaturewith temperature set point accuracyto 0.1 VF (0.06'C).
4. Limiting the chilled fluid temperature pulldown rate at start-up to an adjustable range of 0.2° F to 2° F (0.11'C to 1.1'
C) perminuteto prevent excessive demand spikes atstart-up.
5. Seven-daytimeschedule.
6. Leaving chilled fluid temperature resetfrom return fluid and outside airtemperature.
7. Chilled waterpump start/stop control and primary/standby sequencing to ensure equal pump run time.
8. Dual chillercontrol for parallel chiller applications without addition of hardware modules and control panels
(additional thermistors andwells are required).
9. Timed maintenance scheduling to signal maintenance activities forpumps, condensercoil cleanings, strainer
maintenanceand user -defined maintenanceactivities.
10. Boilerenable signal to initiate system heating mode.
11. Low ambient protection to energize coolerand hydronic system heaters.
12. Periodic pump startto ensure pump seals are properly maintained during off-season periods.
13. Single step demand limit control activated by remote contact closure.
14. Nighttime sound modeto reducethe sound ofthe machine by a user -defined schedule.
C. Diagnostics:
1. The control panel shall include, as standard, a scrolling marquee display capable of indicating the safety lockout
condition by displaying a code forwhich an explanation maybe scrolled atthe display.
2. Information included for display shall be:
a Compressorlockout.
b. Lossofcharge.
a Low fluid flow.
d. Coolerfreeze protection.
e Coolersetpoint.
f. Chilled waterresetparameters.
g. Thermistorandtransducermalfunction.
h. Entering and leaving -fluid temperature.
i. Compressorsuctiontemperature.
j. Evaporatorandcondenserpressure.
k. System refrigeranttemperatures.
I. Chiller run hours.
m. Compressorrun hours.
n. Compressor numberof starts.
o. Lowsuperheat.
p. Time of day:
1) Display module, in conjunction with the microprocessor, must also be capable of displaying the output
(results) of a service test. Service test shall verify operation of every switch, thermistor, fan, and compressor
before chiller is started.
II) Diagnostics shall include the ability to review a list of the 20 most recent alarms with clear language
descriptions of the alarm event. Display of alarm codes without the ability for clear language descriptions
shall be prohibited.
111) An alarm history buffershall allowthe userto store no less than 20 alarm eventswith clearlanguage
descriptions, time and date stamp evententry.
IV) The chiller controller shall include multiple connection ports for communicating with the local equipment
Packaged Chiller Builder NACO 3.49r Page 13 of 17
Guide Specification for 30RAP30
Project: Seattle Chocolates 07/21/2016
Prepared By: Kendal Martin 12:14AM
network, the CarrierComfortNetwork®(CCN) system and accesstochillercontrol functions from any point
onthechiller.
V) The control system shall allow software upgrade withoutthe need fornew hardware modules.
D. Safeties:
1. Unit shall be equipped with thermistors and all necessary components in conjunction with the control system to provide
the unit with the following protections:
a Loss of refrigerant charge.
b. Reverse rotation.
a Low chilled fluid temperature.
d. Thermaloverload.
a High pressure.
f. Electrical overload.
2. Factory pump motors shall have external overcurrent protection.
2.09. OperatingCharacteristics:
A. Unit shall be capable of starting and operating down to45 F (7 C) as standard.
B. Unit shall be capable of starting and running at outdoor ambient temperatures up to 120 F (50 C) for all sizes. Unit shall
additionally be able to stay online when running with a 125 F (52 C) ambient temperature.
C. Unit shall be capable of starting up with 95 F (35 C) entering fluid temperature to the cooler.
2.10. Fan Motors:
A. Condenserfansshall bedirect-ddveAero-AcousticTMtype, discharging airvertically upward.
B. All condenserfan motors shall be totally enclosed 3-phase type with permanently lubricated ball bearings, Class F
insulation and internal, automatic reset thermal overload protection or manual reset calibrated circuit breakers.
C. Shafts shall have inherent corrosion resistance.
D. Fan blades shall be statically and dynamically balanced.
E. Condenserfan openings shall be equipped with PVC coated steel wire safetyguards.
2.11. Electrical Requirements:
A. Unit/module primary electrical power supply shall enterthe unit at a single electrical box.
B. Unit shall operate on 3-phase power atthe voltage shown in the equipment schedule.
C. Control points shall be accessed through terminal block.
D. Unit shall be shipped with factory control and powerwiring installed.
2.12. Chilled WaterCircuit:
A. Chilled water circuit shall berated for 300 psig (2068 kPa) working pressure.
B. Solid-state flow monitorwith integral relay shall be factory installed and wired.
C. Brass body strainerwith 40 mesh screen and ball type blow down.
2.13. Special Features:
A. High-EfficiencyVariable Condenser Fans:
1. All fans on the unit shall have variable speed fan motors to provide higher part load efficiency and reduced acoustic
levels. Each fan circuit shall have afactory-installed, independent variable speed drive with display. Variable speed
drives are rated IP -55 enclosures and UL Listed. The use of this option, with the addition of antifreeze in the cooler
circuit and wind baffles, shall allow running with outdoor am bienttemperatures down to —20 F (-28.9 C). This option
is a standard feature on sizes 011 and 016, is not available on sizes 010, 015, and 070-150, and is notavailable in
combination with low ambient head pressure control.
B. Freeze ProtectionCoolerHeaters:
1. Cooler heaters shall provide protection from coolerfreeze-up to -20 F (-29 C) 60 Hz and -15 F (-26 C) 50 Hz.
C. Digital Compressor Option:
Shall provide a factory -installed digital compressorto provide incremental steps fortightertemperature control (not
available on any application with a leaving fluid temperature below 35 F [2 C]).
Packaged Chiller Builder NACO 3,49r Page 14 of 17
Detailed Performance Summary For 3ORAP3O
Project: Seattle Chocolates 07/21/2016
Prepared By: Kendal Martin 12:14AM
Unit Information
66.3 --
MOCP
Tag Name:..... . -.--. ..---
.---30RAP30
Tons
Model Number: . __-_.__30RAP030
- _ .0.00010
kW
Condenser Type:__....__.._ ... ........
Air Cooled
kW
Compressor Type:... _....__ ......_.........._._...Scroll
...33.4
kW
Nameplate Voltage:._ ...... ..... ._
............. 460-3-60
V -Ph -Hz
Quantity:. ....__ ..... ...................................................1
_- ___ 11.8
ft wg
Manufacturing Source:...Charlotte, NC USA
Refrigerant: ............................ ....................
...... R41 OA
Capacity Control Steps: ----- .............
.. ............... . 22
Minimum Capacity: . .........................
...... . ..... 17.00
%
Shipping Weight: ___ ....... .....
..... .. _1 369
Ib
Operating Weight:_. _.............._.....
.....__...1283
Ib
Unit Length: _ .. _ .___.._ ...__
_ _.. - ......_89
in
Unit Width: __ ._ ._ _ __ -...
_._ _41
in
Unit Height:......_..... ... _. _
_ -__ _ ...__.79
in
Minimum Outdoor Operating
Temp:... -20.00
°F
Chiller Pressure Drop*: .. _ ....
. ....... 17.9
ft wg
"Use Chiller Pressure Drop for sizing pumps.
This value
includes losses due to chiller piping, fittings, 40
mesh factory
supplied strainer and BPHX.
Performance Information
66.3 --
MOCP
Cooling Capacity: __...__....__...__............
......... 8.3
Tons
Total Compressor Power: ..... ........ __..__...._30.7
- _ .0.00010
kW
Total Fan Motor Power:...-. ......
_2.67
kW
Total Unit Power (without pump):_____
...33.4
kW
Efficiency (without pump): .......... . ...............
10.18
EER
Evaporator Information
66.3 --
MOCP
Fluid Type:_ _... __-
.Fresh Water
211.7 --
Fouling Factor:._ _.... _..._.-.----
- _ .0.00010
(hr-sqft-F)/BTU
Leaving Temperature:. .... _.......
...... _..._44.00
°F
Entering Temperature:..__ ...
_ .. .... .64.00
°F
Fluid Flow: _.-,..
...........67.8
gpm
Evaporator Pressure Drop*:..
_- ___ 11.8
ft wg
"Refer to Chiller Pressure Drop for sizing pumps.
Condenser Information
Altitude:....._ ..............__...._ ..... _ . _ .. _ .0 ft
Number of Fans:..-- - _............... ............................2
Total Condenser Fan Air Flow:... _19400 CFM
Entering Air Temperature:-....._... _ ----- _. 95.00 °F
Integrated Pump Information
No Pump Selected
Accessories and Installed Options
Cooler Heater
Micro Channel
Low Sound
Digital Compressor
Single Point
High Efficiency Variable Condenser Fan
Electrical Information
Unit Voltage:..... . _. . .460-3-60 V -Ph -Hz
Connection Type: . __ .._ .. Single Point
Electrical Electrical
Amps Circuit 1 Circuit 2
MCA
66.3 --
MOCP
90.0
ICF
211.7 --
Rec Fuse Size
80.0
Packaged Chiller Builder NACO 3.49r Page 15 of 17
Detailed Performance Summary For 30RAP30
Project: Seattle Chocolates 07/21/2016
Prepared By: Kendal Martin 12:14AM
Integrated Part Load Value (AHRI)
IPLV:........... ..... _ ...... .... ..... ...._... .. _ 16.31 EER
Unit Performance
Percent of Full Load Capacity, %
100.00
75.00
50.00
25.00
Percent of Full Load Power, %
100.00
53.45
28.71
13.73
Unloading Sequence
A
A
A
A
Cooling Capacity, Tons
28.3
21.3
14.2
7.1
Total Unit Power, kW
33.4
17.9
9.6
4.6
Efficiency, EER
10.18
14.29
17.74
18.54
Evaporator Data
Fluid Entering Temperature, °F
53.96
51.46
48.97
46.49
Fluid Leaving Temperature, °F
44.00
44.00
44.00
44.00
Fluid Flow Rate, gpm
68.0
68.0
68.0
68.0
Fouling Factor, hr -s ft -F /BTU
0.0001
0.0001
0.0001
0.0001
Condenser Data
Entering Air Temperature, °F
95.00
80.00
65.00
55.00
For some 75% operating points, the efficiency may be calculated at a condenser inlet air operating temperature as much as 0.8
degrees higher.
An uncoated Novation condenser coil was selected for this product. This is based on an installed location with postal code 98074 and
a non -corrosive localized environment.
Sound power measured in accordance with ANSI/AHRI 370-2001.
Certified in accordance with the AHRI Air -Cooled Water -Chilling Packages Certification Program, which is based on AHRI
Standard 550/590 (I -P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org.
Packaged Chiller Builder NACO 3.49r Page 16 of 17
Detailed Performance Summary For 30RAP30
Project: Seattle Chocolates 07/21/2016
Prepared By: Kendal Martin 12:14AM
Unit Parameters
31
63
125
Tag Name: _....... ....... _.... -
..... ..... -- - 30RAP30
1k
�
Model Number: -__--- - - - - --
------ -- --- -- - 30RAP030
Overall
100% Load
Condenser Type:__._..__ _.....____--
---- Air Cooled
72
'
Compressor Type:..- - ..-
__ _.._ Scroll
84
-
Chiller Nameplate Voltage
_.._ _ __ _.460-3-60
V -Ph -Hz
36
Quantity:_ ........--- ....................... -__-----
- ........ - - ...... - _ _ 1
76
79
Manufacturing Source: ._.-
.___Charlotte, NC USA
75
3 �
Refrigerant:......_ ................. ---......
- ..... .. ...... R410A
37
55
Shipping Weight:- ........ ...................
.... - ......._.....------------ -1369
Ib
r �i
Operating Weight:._......_...................................................1283
73
Ib
84
UnitLength: ......... ........ .__........... ..............
..... ........................... 89
in
59
Unit Width:_. ...... .__........ _
.......... ....-.._ ._._ ...._ ....41
in
1 - Chiller Height Above Ground
Unit Height:..... __....._ _ ._...._ ___....
____... ___ ...... .79
in
2 - Horizontal Distance From Chiller to Receiver
51
45
39
3 - Receiver Height Above Ground
(See Note 3)
Accessories and Installed Options
Cooler Heater
Digital Compressor
Micro Channel
Single Point
Low Sound
High Efficiency Variable Condenser Fan
Acoustic Information
Table 1. A -Weighted Sound Power Levels (dB re 1 picowatt). See note #1.
Octave Band Center Frequency, Hz
31
63
125
250
500
1k
2k
4k
8k
Overall
100% Load
39
59
72
78
83
84
84
78
70
89
75% Load
36
56
71
76
79
81
81
75
69
86
50% Load
37
55
65
75
76
79
79
73
70
84
25% Load
35
57
59
70
76
77
79
72
67
83
Table 2. A -Weighted Sound Pressure Levels (dB re 20 micropascals) calculated based upon user defined input for
dimensions 1, 2 and 3 as shown in above diagram. See note #2 and #3.
Octave Band Center Frequency,
Hz
31
63
125
250
500
1 k
2k
4k
8k
Overall
100%
Load
12
32
45
51
55
56
56
50
42
62
75%
Load
9
29
44
49
51
53
53
47
41
59
50%
Load
9
28
37
48
49
51
52
45
43
57
25%
Load
8
29
32
43
48
49
51
45
39
55
Notes: (1) Measurements performed in accordance with AHRI Standard 370 for air cooled Chillers.
(2) Chiller is assumed to be a point source on a reflecting plane.
(3) Without user defined input, the default dimensions used to construct Table 2 are as follows:
1 - Chiller Height Above Ground = 0.0 ft
2 - Horizontal Distance From Chiller to Receiver = 30.0 ft
3 - Receiver Height Above Ground = 3.0 ft
Packaged Chiller Builder NACO 3.49r Page 17 of 17
Carrier
4
Product 30GTN
Data Packaged Air -Cooled
Reciprocating Chillers
50/60 Hz
60 Hz — 15 to 35 Nominal Tons (53 to 123 Nominal kW)
50 Hz — 15 to 30 Nominal Tons (53 to 106 Nominal kW)
CITY OF TUKWiLA
AUG 0 9 2016
PERMIT CENTER
Copyright 1999 Carrier Corporation
Features/Benefits
• Simple and easy to use
ComfortLinkTm communicating
controls
• Wide operating envelope from —28
to 52 C (-20 to 125 F).
• Accurate temperature control with
return fluid compensation.
• Value added features built-in; dual
chiller control, reset from return.
• Precise multiple -step capacity.
ComfortLink control
Your link to a world of simple and easy
to use air-cooled chillers that offer out-
standing performance and value. The
30GTN liquid chillers employ more
than the latest advanced microproces-
sor controls, they utilize an expandable
platform that grows as your needs
change. From stand-alone operation to
remotely monitored and operated
multi -chiller plants, ComfortLink con-
trols can keep you plugged in.
ComfortLink controls are fully
communicating, and are cable ready
for connection to a Carrier Comfort
Network (CCN). Occupancy schedul-
ing, temperature and pressure
read-outs, and the ComfortLink scroll-
ing marquee clear language display
complement the standard features,
linking you to a world of carefree com-
fort. The 30GTN chillers are built on
the legendary performance of the
Carrier model 30G FlotronicTM chiller
and share many of the same time -prov-
en features and technologies providing
easy operation, quick installation, and
start-ups that save you money!
Superior temperature control
equals potential for greater
productivity
Whether in the classroom, on the pro-
duction floor, or in the office,
ComfortLink controls can help you to
adapt to changing weather and
Form 30GTN-2PD
Z
Physical data 60 Hz
Carrier
f:+
UNIT 30GTN
015
020 025
030
035
COMPRESSOR
Reciprocating, Semi -Hermetic
Reciprocating, Semi -Hermetic
Weight, Ib (kg)
Weight, Ib (kg)
1640 (744)
1821 (826) 2170 (984)
2268 (1029)
2965 (1345)
No. ...Type
1...06DG537
1...06E2250 1...06E7265
1...06E7275
1...06E7299
No. Cyl (ea) ... Speed, Rpm (r/s)
6...1750 (29)
4...1750 (29) 6...1750 (29)
6...1750 (29)
6...1750 (29)
Capacity Steps
3
2 3
3
3
Minimum Capacity Step %
33
50" 33
33
33
REFRIGERANT CHARGE R-22
49.0 (22.2)
CONDENSER FANS, Type
Propeller, D' riven
Total Ib (kg)
25.0 (11.3)
31.0 (14.1) 40.0 (18.1)
47.0 (21.3)
57.0 (25.9)
CONDENSER FANS, Type
Propeller, Direct Driven
No. Fans...Total kW
Fan Speed, Rpm (r/s)
2..3.0
1140 (19)
Total Airflow, Cfm (Us)
10,600 (5000)
No. Blades... Diameter, in. (mm)
15,700 (7400)
3...30 (762)
Horizontal Plate Fin
No. Fans... Total kW
2..1.7
2..1.7 2...3.0
2...3.0
3...4.5
Total Airflow, Cfm (Us)
10,600 (5000)
10,600 (5000) 15,700 (7400)
15,700 (7400)
23,700 (11,200)
CONDENSER COIL, Type
I 23.5(2. 39.2 (3.64)
I
Horizontal Plate Fin
Max. Working Pressure Refrigerant,
Tubes, Copper, in. (mm)
% (9.5) O.D.
Rows ... Fins/in. (Fin Spacing mm)
2...19 (1.34)
3...17 (1.49) 2...19 (1.34)
3...17 (1.49)
3...17 (1.49)
Total Face Area, sq ft (m2)
23.5 (2.18)
23.5 (2.18) 39.2 (3.64)
I I I
39.2 (3.64)
I 58.4 (5.43)
Max. Working Pressure Refrigerant,
Refrigerant Side - 235 (1620)
450 (3103)
psig (kPa
psig (kPa)
WATE NNECTIONS, in.
COOLER
,et and Outlet
Shell -and -Tube, Direct Expansion
2 FPT
Net Water Volume, gal. (L)
6.8 (25.7)
I 6.8 (25.7) I 9.9 (37.5) I
9.9 (37.5)
I 12.8 (48.4)
Max. Design Working Pressure,
Refrigerant Side - 235 (1620)
psig (kPa)
Water Side -150 (1034)
WATER CONNECTIONS, in.
Inlet and Outlet
2 FPT
21/2 FPT
Drain
3/4 MPT
3/4 MPT
' Uses hot gas bypass at capacities less than 50%.
Rb,ysical data 50 Hz nol vylplic k0t
UNIT 30GTN
015
020 025
030
COMPRESSOR
Reciprocating, Semi -Hermetic
Weight, Ib (kg)
1741 (790)
1864 (846) 2193 (995)
233 rY
No. ...Type
1...06E2250
1...06E7265 1...06E7275
6E7299
No. Cyl (ea) ... Speed, Rpm
4...1450 (24.2)
6...1450 (24.2) 6...1450 (24.2)
...1450 (24.2)
Capacity Steps
2
3 3
3
Minimum Capacity Step %
50'
33 33
33
REFRIGERANT CHARGE R-22
Total Ib (kg)
26.0 (11.8)
35.0 (15.9) 4 . (19.0)
49.0 (22.2)
CONDENSER FANS, Type
Propeller, D' riven
Fan Speed, Rpm (r/s)
15.8)
No. Blades... Diameter, in. (mm)
...30 (762)
No. Fans...Total kW
2..3.0
Total Airflow, Cfm (Us)
10,600 (5000)
0,600 (5000) 15,700 (7400)
15,700 (7400)
CONDENSER COIL, Type
Horizontal Plate Fin
Tubes, Copper, in. (mm)
3/B (9.5) O.D.
Rows ... Fins/in. (Fin Spacing mm)
(1.34)
3...1 .49) 2...19 (1.34)
3...17 (1.49)
Total Face Area, sq ft (m2)
23.5 (2.18)
I 23.5(2. 39.2 (3.64)
I
I 39.2 (3.64)
Max. Working Pressure Refrigerant,
45 03)
psig (kPa)
COOLER
Shell -and -Tube, Direct nsion
Net Water Volume, ga
6.8 (25.7)
I 6.8 (25.7) I 9.9 (3 .
I 9.9 (37.5)
Max. Design W ng Pressure,
Refrigerant Side - 235 (1620)
psig (kPa
Water Side -150 (1 034)
WATE NNECTIONS, in.
,et and Outlet
2 FPT
Ptain
3/4 MPT
' Uses hot gas bypass at capacities less than 50%.
1201
Base unit dimensions — 30GTNO155020
NOTES:
1. There must be a minimum 8 ft (2440 mm) clear air space above unit.
2. Dimensions in [ ] are in millimeters.
HNSED ACCESS DOOR
12491
9 13/16'
-3
-3 3/4"
DOOR
�I
3. The approximate operating weight of the unit is:
UNIT 60 Hz 50 Hz
30GTN Ib kg
Ib kg
015 1640 744
1741 790
015C 1732 786
1833 831
020 1821 826
1864 846
020C 1 1945 882
1988 902
LEGEND
UNIT 30GTN
A
C — Copper Coils
[1219]
COMPR— Compressor
015
4'-0"
MTG — Mounting
2 1/8'
NEC — National Electrical
020
[1207]
Code (U.S.A.)
3'-111/2"
VAV — Variable -Air Volume
F
CLEARANCE TO ( WALL 1219] OR4'REX-0'T UNIT
I—� I Ia•�o"
N 9
WONNING
CLEARANCE 1
PER NEC
110-16
163.5-92.17 2 1/2-3 5/8' DIA.
FIELD MAIN POWER SUPPLY
CONTROL BOX t:0A1� TIM
122.21 7/8" DIA.
FIELD CONTROL CIRCUIT WIRING
[12197 4'-0'
CLEARANCE TO WALL OR NEXT UNIT
181 I^— 17661_
3 3/161 1 ;,,,�-,.6
ACCESS PANEL CENTER OF GRAVITY
9
'I
1583]
CENTER
Of
i.PAV1 TY
LE
ersn:: Tania
3
3' '
ACCESS
HNSED ACCESS DOOR
12491
9 13/16'
-3
-3 3/4"
DOOR
�I
FORK TRUCN
Qa �auA
�KI2351
nE ,
..
LIFT POCNETS
9 ua
ersn:: Tania
FAN No. 1 FAN No. 2
TOP VIEW
AIRFLOW ER
CONDENSER
ACCESS PANELof sc,TRECT
MOUNTING
LOCATION
L —'—I
WATER INLET
111381 2' FPT
ACCESS (PANEL
(63.FI5-92.11 13461IFI^
2 1/2ELD "-3 PO5/8
WER'DIA 1'-1 5/8'
1
ENTRY d LIFTING 1 140]9/16' 12 ,
2' I8 21
-7 IS/ —
16'
11001
3 IS/I6' L
7/8' DIA. 222.21 HOLES
FIELD CONTROL
LJ
FORK TRUCK
LIF/ POCKETS
SOTH SIDES
1692I -
3
I/4'
ER Dfl AIN
" MPT
_r
11860] MTG. HOLES \
Q 6'.2. It` 163.51
f 13871 2/2' DIA.
LIFTING
d'-6 5/8"
205
9.
6'-
32411
122.21 7/8' DIA. 10•.7 13/16' SIDE VIEW
V.A.V. POWER ENTRY
116261 —�-�
5'-4'
MIN CLEARANCE FOR
COOLER REMOVAL
W
�Q OF COOLER NOZZLES
.1130;N ll8'
I Q OF COOLER DRAIN
I i691
6 5/8'
FORK TRUCN
Qa �auA
�KI2351
LIFT POCNETS
9 ua
1611
[1007]
2 7116"
3'-3 II/16"
1541
111151
2 1/8'
3'-7 15/16"
319.11
3/4" DIA.
MOUNTING HOLES
ITYP 1 PLACES(
END VIEW
FAN No. 1 FAN No. 2
TOP VIEW
AIRFLOW ER
CONDENSER
ACCESS PANELof sc,TRECT
MOUNTING
LOCATION
L —'—I
WATER INLET
111381 2' FPT
ACCESS (PANEL
(63.FI5-92.11 13461IFI^
2 1/2ELD "-3 PO5/8
WER'DIA 1'-1 5/8'
1
ENTRY d LIFTING 1 140]9/16' 12 ,
2' I8 21
-7 IS/ —
16'
11001
3 IS/I6' L
7/8' DIA. 222.21 HOLES
FIELD CONTROL
LJ
FORK TRUCK
LIF/ POCKETS
SOTH SIDES
1692I -
3
I/4'
ER Dfl AIN
" MPT
_r
11860] MTG. HOLES \
Q 6'.2. It` 163.51
f 13871 2/2' DIA.
LIFTING
d'-6 5/8"
205
9.
6'-
32411
122.21 7/8' DIA. 10•.7 13/16' SIDE VIEW
V.A.V. POWER ENTRY
116261 —�-�
5'-4'
MIN CLEARANCE FOR
COOLER REMOVAL
W
�Q OF COOLER NOZZLES
.1130;N ll8'
I Q OF COOLER DRAIN
I i691
6 5/8'
Application data (cont)
Maximum cooler flow (> 5 gpm/ton or < 5 F range
[> 0.09 L/s • kW or < 2.7 C range]) results in practical
maximum pressure drop through cooler.
1. Return water may bypass the cooler to keep pressure
drop through cooler within acceptable limits. This
permits a higher AT with lower water flow through
cooler and mixing after the cooler.
2. Special cooler baffling is available by special order to
permit a cooler flow rate increase of 10%.
NOTE: Bypass flow is shown below.
BYPASS FLOW
CHILLER COOLER
BYPASS
i--
SUPPLY RETURN 1
MINIMUM/MAXUVIUM COOLER FLOW
RATES AND RECOMMENDED
MINIMUM LOOP VOLUME
LEGEND
ARI - Air Conditioning and Refrigeration
Institute (U.S.A.)
N - Liters per kW
V - Gallons per Ton
NOTES:
1. Operation below recommended minimum loop volumes will reduce
accuracy of loop temperature control.
2. Minimum flow based on 1.5 fps (0.46 m/s) velocity in cooler without
special cooler baffling.
3. Minimum Loop Volumes
Gallons = V x ARI Cap. (tons)
Liters = N x ARI Cap. (kW)
APPLICATION
MINIMUM
MAXIMUM
RECOMMENDED
UNIT
FLOW
FLOW
MINIMUM
30GTN
Low Ambient Unit Operation
.6 to 10
LOOP VOLUME
1.00
Gpm
I Us
Gpm
Us
G
L
015
25
2
134
9
45
171
020
25
2
163
10
60
228
025
30
2
230
15
75
285
030
30
2
250
16
90
342
035
34
2
326
21
1 105
399
LEGEND
ARI - Air Conditioning and Refrigeration
Institute (U.S.A.)
N - Liters per kW
V - Gallons per Ton
NOTES:
1. Operation below recommended minimum loop volumes will reduce
accuracy of loop temperature control.
2. Minimum flow based on 1.5 fps (0.46 m/s) velocity in cooler without
special cooler baffling.
3. Minimum Loop Volumes
Gallons = V x ARI Cap. (tons)
Liters = N x ARI Cap. (kW)
APPLICATION
V
N
Normal Air Conditioning
3 to 6
3.25 to 6.5
Process Type Cooling
6 to 10
6.5 to 10.8
Low Ambient Unit Operation
.6 to 10
6.5 to 10.8
Water loop volume should range from 3 to 6 gallons per
nominal ton of cooling (3.25 to 6.5 liters per kW) for tem-
perature stability and accuracy in normal air conditioning
applications. (For example, a 30GTNO25 would require
75 gallons (285 liters) in circulation in system loop - see
12 1201
Carrie
Minimum/Maximum Cooler Flow Rates and Minimum -
Loop Volume table above.) For process jobs where accura-
cy is vital, there should be from 6 to 10 gallons per ton
(6.5 to 10.8 liters per W4. To achieve this volume, it is of-
ten necessary to install a tank in the loop. Tank should be
baffled to ensure there is no stratification and that water
(or brine) entering tank is thoroughly mixed with liquid in
tank. Refer to ASHRAE (American Society of Heating,
Refrigeration and Air Conditioning Engineers, U.S.A.)
guides or similar publication for information on storage
tank design.
NOTE: Tank installation is shown below.
TANK INSTALLATION
y
NO! GOOD
NO! GOOD
Cooler fouling factor used to calculate tabulated ratings
was 0.00010 ft2 • hr • ° F/Btu (0.000018 m2 • K/W). As
fouling factor is increased, both unit capacity and compres-
sor power decrease. Standard ratings should be corrected
using following multipliers:
FOULING FACTOR CORRECTION
FOULING FACTOR
CAPACITY
COMPRESSOR
English
S�
(ft2POWER
• hr
m2
( )
MULTIPLIER
MULTIPLIER
•'F/Btu)
0
0
1.00
0.00010
0.000018
1.00
1.00
0.00075
0.000132
0.97
0.98
0.00175
0.000308
0.91
0.91
Condenser altitude correction factors must be applied
to standard ratings of altitudes above 2000 ft (610 m) us-
ing following multipliers.
ALTITUDE CORRECTION FACTORS
ALTITUDE
CAPACITY
MULTIPLIER
COMPRESSOR
POWER
English
SI
(ft)
(m)
MULTIPLIER
0
0
1.00
1.00
2,000
610
0.99
1.01
4,000
1220
0.98
1.02
6,000
1830
0.97
1.03
8,000
2440
0.96
1.04
10,000
1 3050
0.95
1.05
Performance data
•
ARI*
STANDARD
RATINGS - 60 Hz
UNIT CAPACITY COMPRESSOR
POWER INPUT
FAN POWER
COOLER WATER
PRESSURE DROP
EER
COP IPLV
30GTN
Tons kW (kW)
kW )
ft water kPa
015 14.3 50.4 15.7
1.7
2.9 8.6
9.9
2.90 12.9
020 17.4 61.2 19.9
1.7
4.1 12.3
9.7
2.83 11.4
025 24.4 85.7 27.1
3.0
6.7 20.0
9.7
2.85 12.8
030 27.1 95.4 30.6
3.0
8.4 25.0
9.7
2.84 12.4
035 35.2 1 123.8 40.4
4.5
13.2 39.5
9.4
2.76 11.3
ARI*
STANDARD RATINGS - 50 Hz
UNIT CAPACITY COMPRESSOR
FAN POWER
COOLER WATER
30GTN POWER INPUT
(kW)
PRESSURE DROP
EER
COP IPLV
Tons kW (kW)
ft water kPa
015 15.5 54.5 16.7
3.0
3.3 9.9
9.5
2.77 10.1
020 19.9 70.0 22.8
3.0
5.3 15.8
9.2
2.71 11.7
025 23.6 83.0 25.7
3.0
6.3 18.7
9.9
2.89 12.3
030 30.0 105.4 36.6
3.0
10.3 30.7
9.1
2.66 11.4
LEGEND
COP - Coefficient of Performance (Capacity [kW] _ Input Power [kW])
3. IPLV is a single number part -load efficiency value calculated from the system
EER - Energy Efficiency Ratio (Capacity [Btuh] _ Input Power
[W])
full -load efficiency values and corrected for a typical building air-conditioning
IPLV - Integrated Part -Load Value
application.
Air Conditioning and Refrigeration Institute (U.S.A.)
4. All data in this table is rated
in accordance
with ARI Standard 550/590 as
represented in the Packaged
Chiller Selection Program (E -Cat) Version 2.00.
NOTES:
1. Rated in accordance with ARI Standard 550/590-98 at standard
rating
conditions.
2. Standard rating conditions are as follows:
Cooler Conditions
Leaving water temperature: 44 F (6.7 C)
F
Entering water temperature: 54 F (12.2 C)
Fouling Factor: 0.00010 ftz x hr x °F/Btu (0.000018 mz x'K/W)
Condenser Conditions:
Entering Air Temperature: 95 F (35 C)
17
a
DdH Ln o Ln c1 cn
y r� (D d- K) c7
U) r
OL
z
133.E N0U"0ono
Sld3Sdd0l lA NI GU H
0 0 0 0
tl 0 Ln 0 N 0 Q
N tO
S6313W NI OV3H
Lo O Lo 0
N N r r- u7 00
'•
_■MOM■M■■M■■M■■
■■■■■■MEMO■■■■■■ip■■■■M■■
■O■MMMM
IMM■M■MMM■M■■MSPAN .i�M■MMOMM■
MM■M■M■■■N
■M■M■MM■■■ it i mmom■■■■■■
MUMM■M■M■■ = - ILll■illoslJ■■■MMM
•
.UNMMM■MMM
Ml1■MOM■■■ .-.i■■1■l�%omm ■■
O '■■OO■:#■IOM%►M■■OO
■m■■1■ ■■■■
1►MMMMIMM■ANEW
■MM■i■■■M■■MwIllm■oull ■■■■
■MMM' f��/`/®/MEMARM ■■■■
■■■■ Iepowai/1r1■rimum■i'fi■■■■■■■
mmorto l
■ ■■'�■:iirM®f■dri■�rO■■■■M■■
MM■M mm! "MMMmMm■■■■■
■
_
mmmm
mmmm
■■M._ , . ImmmilII111■OMS ramm■■■
ME
M
■O■■ ' 1■ oil • ■ 1 * l■■■■■■ "
■1
NONE • 1■ •• oil ■ 1 •'l■o■■■■
x
Ln C Ifs O Ln
C r— Ln N
133.E NI GV3H
I
Ln
I
Ln c
O
37
PERMIT COORD COPY
PLAN REVIEW/ROUTING SLIP
PERMIT NUMBER: M16-0127 DATE: 08/11/16
PROJECT NAME: SEATTLE CHOCOLATES
SITE ADDRESS: 1180 ANDOVER PARK W
X Original Plan Submittal Revision # before Permit Issued
Response to Correction Letter # Revision # after Permit Issued
DEPARTMENTS:
N K* $
Building Division
Public Works ❑
PRELIMINARY REVIEW:
Not Applicable ❑
(no approval review required)
REVIEWER'S INITIALS:
APPROVALS OR CORRECTIONS:
Approved ❑
Corrections Required ❑
(corrections entered in Reviews)
Notation:
REVIEWER'S INITIALS:
AAA n4, t. 11-1(p
Fire Prevention IN
Structural ❑
Planning Division ❑
Permit Coordinator ❑
DATE: 08/11/16
Structural Review Required ❑
DATE:
DUE DATE: 09/08/16
Approved with Conditions ❑
Denied ❑
(ie: Zoning Issues)
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
12/18/2013
CARRIER CORP
Home fispahol Contact
Safety & Health
Washington State Department of
k,j Labor & Industries
CARRIER CORP
Owner or tradesperson
Principals
KENNA, E DOUGLAS
ALLEN, ROBERT F
WESTLAKE, WILLIAM
HOOVER, EDWARD F
CT, CORPORATION, AGENT
Doing business as
CARRIER CORP
Claims & Insurance
3215 S 116TH ST STE 133
TUKWILA, WA 98168
425-641-4810
KING County
Page I of 2
(Search L&Iii
A-1 .Index Ile][) My L&I
Workplace Rights Trades & Licensing
WA UBI No. Business type
600 340 198 Corporation
License
Verify the contractor's active registration / license / certification (depending on trade) and any past violations.
Construction Contractor. Active.
....................._..._............._.......................
Meets current requirements.
License specialties
GENERAL
$1,000,000.00
License no.
CARRI**342PP
Effective — expiration
Effective date
10/17/1966— 04/27/2017
04/01/2016
Bond
.................
Expiration date
FEDERAL INS CO
$12,000.00
Bond account no.
81892394
Received by L&I
Effective date
01/16/2003
02/05/2003
Expiration date
Until Canceled
Insurance
..........,
Hartford Fire Ins Co
$1,000,000.00
Policy no.
02CSET10004
Received by L&I
Effective date
03/30/2016
04/01/2016
Expiration date
04101/2017
Insurance history
Savings
No savings accounts during the previous 6 year period.
https://secure.Ini.wa.gov/verify/Detail.aspx?UBI=600340198&LIC=CARRI * * 342PP& SAW= 8/16/2016