Loading...
HomeMy WebLinkAboutPermit M16-0188 - BUILD A BEAR - DIFFUSERSI le -114" lei V43 110 656SOLJTHCENTF.R MALL M16-0188 Parcel No Address: Citv of Tukwila Department of Community Development 6300 Southcenter Boulevard, Suite #100 Tukwila, Washington 98188 Phone: 206-431-3670 Inspection Request Line: 206-438-9350 Web site: http://www.TukwilaWA.gov MECHANICAL PERMIT 9202470010 Permit Number: M16-0188 656 SOUTHCENTER MALL Issue Date: 2/16/2017 Permit Expires On: 8/15/2017 Project Name: BUILD A BEAR Owner: Name: WESTFIELD PROPERTY TAX DEPT Address: PO BOX 130940, CARLSBAD, CA, 92013 Contact Person: Name: JOHN RANOUS Address: 3725 VINTON AVE #8, LOS ANGELES, CA, 90034 Contractor: Name: AIR SYSTEMS ENGINEERING INC Address: 3602 S PINE ST, TACOMA, WA, 98409 License No: AIRSYE*229KN Lender: Name: Address: DESCRIPTION OF WORK: NEW DIFFUSERS Valuation of Work: $12,000.00 Type of Work: Fuel type: Phone: (310) 876-1141 Phone: (206) 628-9484 Expiration Date: 2/1/2018 Fees Collected: $358.91 Electrical Service Provided by: PUGEST SOUND ENERGY Water District: TUKWILA Sewer District: TUKWILA Current Codes adopted by the City of Tukwila: International Building Code Edition: 2015 National Electrical Code: 2014 International Residential Code Edition: 2015 WA Cities Electrical Code: 2014 International Mechanical Code Edition: 2015 WAC 296-46B: 2014 Uniform Plumbing Code Edition: 2015 WA State Energy Code: 2015 International Fuel Gas Code: 2015 Date: I hearby certify that I have read and examined this permit and know the same to be true and correct. All provisions of law and ordinances governing this work will be complied with, whether specified herein or not. The granting of this permit does not presume to give authority to violate or cancel the provisions of any other state or local laws regulating construction or the performance of work. I am authorized to sign and obtain this development permit and agree to the conditions attached to this permit. r In Signature: _ ' Date: Print Name: �_j�`��'fJl This permit shall become null and void if the work is not commenced within 180 days for the date of issuance, or if the work is suspended or abandoned for a period of 180 days from the last inspection. PERMIT CONDITIONS: 1: All construction shall be done in conformance with the Washington State Building Code and the Washington State Energy Code. 2: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, any violation of any of the provisions of the building code or of any other ordinances of the City of Tukwila. Permits presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the Building Official from requiring the correction of errors in the construction documents and other data. 3: `MECHANICAL PERMIT CONDITIONS' 4: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila Permit Center (206/431-3670). 5: All permits, inspection record card and approved construction documents shall be kept at the site of work and shall be open to inspection by the Building Inspector until final inspection approval is granted. PERMIT INSPECTIONS REQUIRED Permit Inspection Line: (206) 438-9350 1800 MECHANICAL FINAL 0701 ROUGH -IN MECHANICAL r r/ CITY OF TUKWILA tu da Community Development Department Permit Center • 6300 Soullicenter Blvd., Suite 100 Tulavila, W4 98188 http:/h%�«v.Tuk,,,,,ilaWA.�ov (For office i MECHANICAL PERMIT APPLICATION Mechanical Permit No. w�,,OIN Project No. Date Application Accepted: Date Application Expires: Applications and plans must be complete in order to be accepted for plan review. Applications will not be accepted through the mail or by fax. **please print** SITE LOCATION y� (v✓ Site Address: �southeenter mall Tenant Name: Build A Bear PROPERTY OWNER Name: Westfield Address: 225 E. Washington street City: Indianapolis State: In Zip: 46204 CONTACT PERSON — person receiving all project communication Name: John Ranous Address: 3725 Vinton Ave #8 City: Los Angeles State: Ca 7-P: 90034 Phone: (31.0) 876-1.1.41 Fax: (310) 876-0149 Email: john@nationwidepermits.com Valuation of project (contractor's bid price): $ 12,000 Describe the scope of work in detail: New Diffusers Use: Residential: New.......... ❑ Commercial: New.......... ❑ King Co Assessor's Tax No.: Suite Number: Floor: New Tenant: m.....yes []..No MECHANICAL CONTRACTOR INFORMATION Company Name: tbd Address: City: State: Zip: Phone: Fax: Contr Reg No.: Exp Date: Tukwila Business License No.: Replacement ........ ❑ Replacement ........ Fuel Type: Electric..... 6fl Gas ....... ❑ Other: H: Wppfimtions\Forma-Applications On Line\2011 AppGcationsWe haniml Permit Application Revised 8-9-11.docx Revised: August 2011 bh Page I of 2 iz Indicate type of mechanical work being installed and the quantity below: Unit Type Qty Furnace <100k btu 0 Furnace >100k btu 0 Floor furnace 0 Suspended/wall/floor 0 mounted heater 0 Appliance vent 0 Repair or addition to 0 heat/refrig/cooling 0 system 0 Air handling unit 0 <10,000 cfln Unit Type Qty Air handling unit 0 >10,000 cfln 12 Evaporator cooler 0 Ventilation fan 0 Emer en cy generator 0 connected to single duct 1 Ventilation system 0 Hood and duct fl Incinerator—domestic 0 Incinerator — 0 comm/industrial PERMIT APPLICATION NOTES - Unit Type Qty Fire damper 0 Diff - user 12 Thermostat 0 Wood/gas stove 0 Emer en cy generator 0 Other mechanical equipment 1 Boiler/Compressor Qty 0-3 hp/100,000 btu 0 3-15 lip/500.000 btu 0 15-30 hp/1,000.000 btu 0 30-50 lip/1,750.000 btu Q 50+h /1,750.000 btu 0 Value of construction — in all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the permit center to comply with current fee schedules. Expiration of plan review — applications for which no permit is issued within 180 days folloA ing the date of application shall expire by limitation. The building official may grant one extension of time for additional periods not to exceed 90 days each. The extension shall be requested in writing and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition). I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT BUILDING OWNER OR AUTHORIZED AGENT: Print Mailing Address: 3725 Vinton ave #8 Date: d �--N-1 Day Telephone: (310) 876-1141 los angeles ca 90034 City State Zip H:\Applications\Forms :4pplications On Une\101 I ApplicationsWechanical Permit Application Revised 8-9-11.dm.x Revised: August 1011 Page 2 of 2 bh DESCRIPTIONS PermitTRAK ACCOUNT QUANTITY PAID $396.46 EL17-0128 Address: 656 SOUTHCENTER MALL Apn: 9202470010 $104.94 Credit Card Fee $3.06 Credit Card Fee R000.369.908.00.00 0.00 $3.06 ELECTRICAL $97.03 PERMIT FEE MULTI-FAM/COMM R000.322.101.00.00 0.00 $97.03 TECHNOLOGY FEE $4.85 TECHNOLOGY FEE R000.322.900.04.00 0.00 $4.85 M16-0188 Address: 656 SOUTHCENTER MALL Apn: 9202470010 $291.52 Credit Card Fee $8.49 Credit Card Fee R000.369.908.00.00 0.00 $8.49 MECHANICAL $269.55 PERMIT ISSUANCE BASE FEE R000.322.100.00.00 0.00 $32.50 PERMIT FEE R000.322.100.00.00 0.00 $237.05 TECHNOLOGY FEE $13.48 TECHNOLOGY FEE TOTALR10841 R000.322.900.04.00 0.00 $13.48 • . . Date Paid: Thursday, February 16, 2017 Paid By: AIR SYSTEMS ENGINEERING INC Pay Method: CREDIT CARD 003761 Printed: Thursday, February 16, 2017 11:27 AM 1 of 1 RSYS7EM5 DESCRIPTIONS PermitTRAK ACCOUNT QUANTITY PAID $1,169.86 D16-0345 Address: 656 SOUTHCENTER MALL Apn: 9202470010 $999.12 DEVELOPMENT $999.12 PLAN CHECK FEE R000.345.830.00.00 0.00 $999.12 EL16-1165 Address: 656 SOUTHCENTER MALL Apn: 9202470010 $103.35 ELECTRICAL $103.35 PLAN CHECK FEE R000.345.832.00.00 0.00 $103.35 M16-0188 Address: 656 SOUTHCENTER MALL Apn: 9202470010 $67.39 MECHANICAL $67.39 PLAN CHECK FEE TOTAL FEES PAID BY RECEIPT: R10067 R000.322.102.00.00 0.00 $67.39 $1,169.86 Date Paid: Monday, December 19, 2016 Paid By: MARY ANN PERRY Pay Method: CHECK 4225 Printed: Monday, December 19, 2016 3:41 PM 1 of 1 CRSY57EM5 INSPECTION RECORD C 2 Retain a copy with permiti� INS ION N0. PERMIT NO. CITY OF TUKWILA BUILDING DIVISION 6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670 Permit Inspection Request Line (206) 438-9350 Progjec:v �i) d id %� .f.- Type of Inspection: l�dr - A dress: L[. Date Called: Special Instructions: Date Wanted: a.m Z/ )0-/) 7 _ p.m. Requester: Phone No: REINSPECTION FEE REQUIRED. Prior to next inspection. fee must be paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection. INSPECTION RECORD 9 Retain a copy with permit A PECTION NO. PERMIT NO. CITY OF TUKWILA BUILDING DIVISION 6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670 Permit Inspection Request Line (206) 438-9350 Project, DQ (d Q gc-T-r Type of Inspection: AdcLq�- Address: ail Aa.1 t Date C I d: S ecia Instructions: Date Wanted: —7-'�!- > f p.m. R 1-7 Pha e , IInspector: IDate: 3-7-:2-- ,7.Z_ r7 F] REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be paid at 6300 Southcenter Blvd., Suite 100. Call. to schedule reinspection. ..' R y 1 4.; COPY PLAN REVIEW/ROUTING SLIP PERMIT NUMBER: M16-0188 DATE: 12/20/16 PROJECT NAME: BUILD A BEAR SITE ADDRESS: 656 SOUTHCENTER MALL X Original Plan Submittal Revision # before Permit Issued Response to Correction Letter # Revision # after Permit Issued DEPARTMENTS: AtA MIS' i)4> -i � Building Division IN Fire Prevention In Planning Division ❑ Public Works ❑ Structural ❑ Permit Coordinator ❑ PRELIMINARY REVIEW: DATE: 12/20/16 Not Applicable ❑ Structural Review Required ❑ (no approval/review required) REVIEWER'S INITIALS: APPROVALS OR CORRECTIONS: Approved ❑ Corrections Required ❑ (corrections entered in Reviews) Notation: DATE: DUE DATE: Approved with Conditions Denied ❑ (ie: Zoning Issues) REVIEWER'S INITIALS: DATE: Permit Center Use Only CORRECTION LETTER MAILED: Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials: 01/17/17 12/19/2013 AIR SYSTEMS ENGINEERING INC Page I of 3 Holne Espanol Contract Search L&I `, § A -"L Index Help my LCI Safety & Health Claims & Insurance Workplace Rights Trades & Licensing Washington State Department of Labor & Industries AIR SYSTEMS ENGINEERING INC Owner or tradesperson CRAWFORD, KANDI K Principals CRAWFORD, KANDI K, PRESIDENT CRAWFORD, DOUGLAS D, VICE PRESIDENT GEORGE, WILLIAM, VICE PRESIDENT COLYER, SANDRA K, SECRETARY ANDERSON, CURTIS M (End: 01/07/2010) ANDERSON, LORINE (End: 01/07/2010) 3602 S PINE ST TACOMA, WA 98409-8197 253-572-9484 PIERCE County WA UBI No. Business type 600 099 211 Corporation License Verify the contractor's active registration / license / certification (depending on trade) and any past violations. Construction Contractor Active. .......................................................... Meets current requirements. License specialties $12,000.00 GENERAL License no. AIRSYE*229KN Effective date Effective — expiration 02/01/2008 05/15/1978— 02/01/2018 Expiration date Bond ............ Until Canceled FIDELITY & DEPOSIT CO OF MD $12,000.00 Bond account no. 08358752 Received by L&I Effective date 01/27/2010 02/01/2010 Expiration date Until Canceled VIGILANT INS CO $12,000.00 Bond account no. 82138376 Received by L&I Effective date 02/04/2008 02/01/2008 Expiration date Until Canceled Help us improve https://secure.Ini.wa.gov/verify/Detail.aspx?UBI=600099211&LIC=AIRSYE*229KN&SAW= 2/16/2017 AIR SYSTEMS ENGINEERING INC Page 2 of 3 I.ns.u...ra....nce. ............. Travelers Property Cas Co of A $2,000,000.00 Policy no. VTC 2J C 0828 K6148TI L16 Received by L&I Effective date 11/03/2016 11/01/2016 Expiration date 11/01/2017 Insurance history Savings ................. No sa..vings accounts during the previous 6 year period. Lawsuits against the bond or savings No lawsuits against the bond or savings accounts during the previous 6 year period. L&I Tax debts No L&I tax debts are recorded for this contractor license during the previous 6 year period, but some debts may be recorded by other agencies. License Violations ........................................... No license violations during the previous 6 year period. I Workers' comp Do you know if the business has employees? If so, verify the business is up-to-date on workers' comp premiums. L&I Account ID Account is current. 336.380-00 Doing business as AIR SYSTEMS ENGINEERING Estimated workers reported Quarter 4 of Year 2016 "Greater than 100 Workers" L&I account representative T5 / STEPHANIE HENDERSON (360)902-6266 - Email: HSTE235@lni.wa.gov Workplace safety and health Check for any past safety and health violations found on jobsites this business was responsible for. Inspection results date 09/15/2016 Under appeal. The results of the inspection are Inspection no. being challenged. 317941491 Date of appeal Location 12/01/2016 1000 6th Ave. Bremerton, WA 98337 ... ..... Inspection results date 02/27/2015 Violations Inspection no. 317935015 Location 754 Pacific Ave Tacoma, WA 98402 Inspection results date 01/28/2014 Violations Inspection no. 316961143 Location 1144 Market ST. Tacoma, WA 98402 Inspection results date 08/15/2011 Violations Help us improve https:Hsecure.Ini.wa.gov/verify/Detail.aspx?UBI=600099211&LIC=AIRSYE*229KN&SAW= 2/16/2017 S2 9 50 O EF ;o ■ ■ EF 2 iS1 10 9 W50S2 m 9 . •. (TYP) ?1 87 OO VAV !2 1 i 0 MECHANICAL PLAN SCALE: 1 /4 if= 1 -0 ff ALL DUCTWORK MUST BE RIGID SHEET METAL OR GALVANIZED STEEL OR ALUMINUM - FIBERGLASS DUCT BOARDS OR OTHER NONMETALLIC MATERIAL IS NOT ALLOWED. ALL SPRINKLERS TO BE RECESSED WITH COVER PLATES FACTORY FINISHED TO SAME COLOR AS SURROUNDING. NOTE: BEFORE ANY MALL TENANT SPACE IMPROVEMENTS OR ALTERATIONS ARE TO BEGIN, WHERE PLENUM CEILINGS ARE REMOVED, ALTERED OR RETURN AIR CEILING GRILLES ARE OPEN/EXPOSED TO CONSTRUCTION DUST CONTAMINATION, A"PLENUM PROTECTION PLAN" SHALL BE REQUIRED TO SHOW PROCEDURES AND METHODS FOR PROTECTING AND SEALING THE RETURN AIR PLENUMS OF ANY CONTAMINATION FROM CONSTRUCTION DUST AND COMBUSTIBLES PRIOR TO AND DURING CONSTRUCTION WORK. NO INSPECTIONS SHALL BE PERFORMED UNTIL MITIGATION PROCEDURES ARE MADE TO PROTECT ANY SHARED CEILING PLENUMS. NOTE: EXISTING CONDITIONS WERE TAKEN FROM SITE VISITS AND MAY NOT REFLECT EXACT "AS -BUILT" CONDITIONS. FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO SUBMITTING FINAL BIDS. CONTRACTOR SHALL CAREFULLY COORDINATE NEW WORK AND DEMOLITION WITH ALL OTHER DISCIPLINES AND EXISTING CONDITIONS. ALL HVAC EQUIPMENT AND CONTROLS MUST BE LOCATED FOR PROPER ACCESS FOR MAINTENANCE AND REPAIR, WHETHER INSTALLATION IS EXISTING OR NEW. EXISTING EQUIPMENT AND CONTROLS SHALL BE RELOCATED BY THIS CONTRACTOR IF REQUIRED 7,,`17 2 t. tIY : 11iI 3rD FOR; Q NlectlanicW M*_Tectracal t Ging Gas Piping City of Tukwila BUILDING DIVISION i KEYNOTE SYMBOLS: (OX -DO) 1. RELOCATE EXISTING THERMOSTAT TO LOCATION SPECIFIED ON PLANS. REPLACE THERMOSTAT IF REQUIRED BY MALL 2. EXISTING VAV TO REMAIN. FIELD VERIFY EXACT LOCATION. CLEAN AND REFURBISH TO LIKE NEW CONDITION. BALANCE SUPPLY AIR TO 2100 CFM. REPLACE CONTROLS IF REQUIRED BY MALL 3. FURNISH AND INSTALL GALVANIZED STEEL DUCTWORK, SIZES AS NOTED ON DRAWINGS. DUCTWORK SIZES ARE CLEAR INSIDE DIMENSIONS. REFER TO SPECIFICATIONS FOR INSULATION REQUIREMENTS. 4. SPRINKLER SYSTEM SHALL BE MODIFIED AS REQUIRED TO SERVE THE NEW LAYOUT SHOWN ON THE DRAWING. NOTIFY THE MALL MANAGER 72 HOURS BEFORE SPRINKLER SHUTDOWN IS REQUIRED AND PAY ALL MALL CHARGES FOR SPRINKLER SHUTDOWN. 5. CONNECT TO LANDLORD'S EXISTING SPRINKLER LINE AND TO CONNECTIONS THAT EXIST IN THE SPACE TO ACCOMMODATE THE NEW SPRINKLER LOCATIONS. REUSE SPRINKLER HEAD LOCATIONS WHERE POSSIBLE. 6. CONNECT DIFFUSERS TO NEAREST EXISTING BRANCH DUCT OR TRUNK DUCT OF ADEQUATE SIZE. REUSE EXISTING OPENINGS IN TRUNK DUCT WHERE POSSIBLE. 7. EXISTING DUCTWORK TO REMAIN. CLEAN AND REFURBISH TO LIKE NEW CONDITION. FIELD VERIFY EXACT LOCATION. 8. DUCTWORK AND PIPING SHALL NOT BE ROUTED OVER ELECTRICAL PANELS, DISCONNECTS, TRANSFORMERS, OR OTHER ELECTRICAL EQUIPMENT. VERIFY LOCATION OF ALL ELECTRICAL EQUIPMENT BEFORE INSTALLATION OF HVAC DUCTWORK AND PIPING. 9. REPLACE EXHAUST FANS IN EXISTING LOCATION. CONNECT TO EXISTING EXHAUST DUCT IN SPACE. 20 MECHANICAL KEYNOTES SCALE: N/A FRE COPY Permit No,� Flare is subject to errors and tH proval Of .onsiruciion documents doss; mc1 t3 violation of any adopted code or ordinance. deo-:,:Yi of approved Field Copy and conditions is acknov1,Jla�jx� ,: Data: City of Tukwila BUILDING DIVISION REVISIONS - No charges shat► be made to the ;Cnno of 11 r� kArithout prior approval -)f 1, ')a Bt Wding Division. re ,. url0 mL:y {i1e,ude additional e a neer plan . UF-� _., clonal plan reviev, fe KEYNOTE SYMBOLS: (D'o,o) 1. EXISTING PLUMBING FIXTURES TO REMAIN. CLEAN AND REFURBISH TO LIKE NEW CONDITION. A. ALL PIPING AND HEADS SHALL BE INSTALLED PER LATEST EDITION OF NFPA 13. HEAD SPACING SHALL BE BASED UPON THE ORDINARY HAZARD SCHEDULE. ALL SPRINKLER PIPING SHALL BE SCHEDULE 40 BLACK IRON. SCHEDULE 10 PIPING IS PERMISSIBLE IF ACCEPTABLE TO THE LANDLORD. HYDRAULICALLY PLUMBING KEYNOTES CALCULATE SYSTEM AND SUBMIT COPIES OF THE CALCULATIONS TO THE AUTHORITY HAVING 13 JURISDICTION AND THE LANDLORD. SCALE: N/A B. PREPARE SHOP DRAWINGS FOR SUBMITTAL TO THE AUTHORITY HAVING JURISDICTION AND THE -� VOLUME DAMPER FD : LANDLORD BEFORE FABRICATION. ® CEILING SUPPLY AIR DIFFUSER C. TWO COPIES OF THE APPROVED SHOP DRAWINGS SHALL BE SUBMITTED TO THE OWNER AND THE SIDEWALL AIR DIFFUSER OR GRILLE NEW DUCTWORK REVIEW=GGA LANDLORD PRIOR TO ISSUANCE OF A CERTIFICATE OF OCCUPANCY. EXISTING DUCTWORK API�� - CD - D. PROVIDE FOR INSPECTION TESTING AND APPROVAL BY THE AUTHORITY HAVING JURISDICTION AND THE SD EXISTING SMOKE DETECTOR D STATE INSPECTION BUREAU AS REQUIRED. O PIPE TURNING UP E. PROVIDE SIGNED CERTIFICATE OF COMPLETION COPIES TO BE GIVEN TO OWNER'S REPRESENTATIVE, BALL VALVE e CONNECTION OF NEW TO EXISTING INSURANCE REPRESENTATIVE, AND PROJECT OFFICE. ter- GAS COCK - F. HOLD ALL SPRINKLER LINES AS HIGH AS POSSIBLE TO MAINTAIN 18" CLEARANCE ABOVE STOCK SHELVING. ABOVE FINISHED FLOOR ETR J I� G. SPRINKLER HEADS IN SALES AREA SHALL BE CONCEALED TYPE WITH WHITE COVER PLATES. UPRIGHT AIR DEVICE # S - SUPPLY R - RETURN CFM E - EXHAUST FIRE PROTECTION SYMBOLS LEGEND OE EXISTING SPRINKLER HEAD PENDANT HEADS SHALL BE USED IN ALL AREAS WITHOUT A CEILING. PENDANT HEADS WITH ESCUTCHEON CHROME PENDANT SPRINKLER HEAD O UPRIGHT SPRINKLER HEAD 00 PLATES SHALL BE USED IN ALL STOCKROOM AREAS/RESTROOMS WITH LAY -IN OR GYPSUM BOARD ®I SIDEWALL SPRINKLER HEAD PLUMBING SYMBOLS LEGEND - - - CEILINGS. SPRINKLER HEAD TEMPERATURE RATINGS SHALL BE 165°F IN SALES AND STOCK AREAS AND - - - - HOT WATER i SANITARY DRAIN 212°F IN DISPLAY WINDOWS AND LIGHTING FIXTURE CANOPIES OR AS REQUIRED BY LANDLORD'S SANITARY VENT VTR ! j EO PLUMBING TRAP INSURANCE AGENCY AND LOCAL AUTHORITIES. SPRINKLER HEADS SHALL BE QUICK RESPONSE TYPE. ALL CLEAN OUT / ^' SEMI -RECESSED AND CONCEALED HEADS SHALL BE WHITE H. VISIT THE SITE AND VERIFY ALL EXISTING CONDITIONS WHICH WILL AFFECT THE WORK. PROVIDE ALL 1 REQUIRED PIPING AND OR REVISIONS TO PIPING AS NEEDED FOR A COMPLETE SPRINKLER SYSTEM WHICH IS APPROVED AND ACCEPTED BY LOCAL AUTHORITIES. 1. SPRINKLER SHOP DRAWINGS UNDER SEPARATE COVER. SUPPLY SPRINKLER SHOP DRAWINGS AND APPLY TO BUILDING DEPARTMENT (REQUIRED). J. LANDLORD DESIGNATED CONTRACTOR TO PERFORM ALL SPRINKLER MODIFICATIONS. SYSTEM MODIFICATIONS SHALL BE SCHEDULED IN ADVANCE WITH THE LANDLORD'S FIELD REPRESENTATIVE. THE SPRINKLER SYSTEM SHALL BE FULLY CHARGED AND OPERATIONAL K. ALL FIRE PROTECTION AND SPRINKLER SYSTEM WORK SHALL BE IN ACCORDANCE WITH MALL'S INSURANCE \' AGENCY REQUIREMENTS, NFPA, STATE, COUNTY AND LOCAL FIRE MARSHALL FIRE PROTECTION SPECIFICATIONS I 18 PLUMBING PLAN I 9 SCALE: N/A SCALE: 1/4" = V-0" 1. ALL OF THE MECHANICAL WORK IS NOT NECESSARILY SHOWN OR NOTED ON THESE DRAWINGS. THE CONTRACTORS SHALL VISIT THE JOB SITE AND VERIFY ALL EXISTING CONDITIONS RELATED TO THEIR WORK BEFORE BIDDING. NOTIFY THE OWNER OF ANY DISCREPANCIES. THOSE ITEMS NOT SHOWN OR NOTED BUT WHICH ARE DEEMED NECESSARY FOR REMOVAL OR RELOCATION BY OWNER'S REPRESENTATIVE SHALL BE PART OF THIS CONTRACT. 2. THE SUBMISSION OF PROPOSALS SHALL BE CONSIDERED EVIDENCE THAT THE CONTRACTORS HAVE VISITED THE SITE. NO EXTRA PAYMENTS WILL BE ALLOWED THESE CONTRACTORS CLAIMS FOR EXTRA WORK MADE NECESSARY BY THEIR FAILURE TO VISIT THE SITE. 3. GUARANTEE ALL EQUIPMENT AND MATERIAL INSTALLED UNDER THIS CONTRACT TO BE FREE FROM DEFECTS FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE AND REPAIR OR REPLACE WITHOUT COST TO THE OWNER ANY EQUIPMENT WHICH IS DEFECTIVE, OR IMPROPERLY INSTALLED. IN ADDITION, ASSUME FULL RESPONSIBILITY FOR ANY DAMAGE TO THE BUILDING AND ITS CONTENTS OR OTHER EQUIPMENT CAUSED BY DEFECTS OR IMPROPER INSTALLATION OF EQUIPMENT OR MATERIALS INSTALLED UNDER THIS PORTION OF THE WORK. 4. ALL WORK SHALL BE COMPLETED AND INSTALLED ACCORDING TO STATE AND OR LOCAL CODES, AND ALL LANDLORD CRITERIA. 5. PAY FOR ALL REQUIRED PERMITS AND INSPECTIONS AND PROVIDE A CERTIFICATE OF INSPECTION. 6. REVIEW ALL LANDLORD REQUIREMENTS AND INSTALL ALL MATERIALS AND EQUIPMENT AS DIRECTED BY THE LANDLORD'S REPRESENTATIVE AND AS REQUIRED BY THE LEASE DOCUMENTS. VERIFY THE REQUIREMENTS BEFORE SUBMITTING A BID. 7. VERIFY THE SIZE, LOCATION AND CONDITION OF THE EXISTING DUCTWORK, EQUIPMENT AND CONTROLS THAT ARE TO REMAIN. NOTIFY THE OWNER OF ANY DISCREPANCIES. REPLACE EXISTING COMPONENTS IF INADEQUATE FOR THE NEW REQUIREMENTS OR INOPERABLE COORDINATE REPLACEMENT COMPONENT SPECIFICATIONS WITH THE LANDLORD'S FIELD REPRESENTATIVE. 8. FIVE (5) COPIES OF ALL SHOP OR EQUIPMENT DRAWINGS SHALL BE SUBMITTED TO THE OWNER. THESE DRAWINGS SHALL BE CLEARLY MARKED INDICATING WHICH ITEMS ARE TO BE SUPPLIED AND SHALL STATE CAPACITIES, SIZES, REQUIRED INSPECTION LABELS AND GENERAL DESCRIPTION OF ALL EQUIPMENT AND FIXTURES. 9. ALL AIR INTAKES AND EXHAUSTS NEED TO BE SEPARATED BY A MINIMUM OF I V-0". 10. NO COMPONENTS MAY BE ABANDONED IN PLACE WITHOUT PERMISSION FROM THE OWNER. ALL COMPONENTS THAT ARE NOT REUSED MUST BE REMOVED. 11. VERIFY ALL CLEARANCES AROUND NEW AND EXISTING EQUIPMENT. 12. CAP ALL UNUSED PLUMBING LINES ASSOCIATED WITH LEASED SPACE AS REQUIRED BY LANDLORD AND LOCAL AUTHORITY HAVING JURISDICTION. 13. FURNISH AND INSTALL BACKFLOW PREVENTER IF REQUIRED BY AUTHORITY HAVING JURISDICTION OR LANDLORD. 14. FURNISH AND INSTALL ALL MECHANICAL EQUIPMENT AND OR AIR DEVICES AS SCHEDULED ON THE DRAWINGS. BIDS SHALL BE BASED ON THE EQUIPMENT SPECIFIED AND NO SUBSTITUTIONS WILL BE ACCEPTED. 15. FURNISH AND INSTALL ALL SYSTEMS OF HVAC CONTROL (TO INCLUDE CONTROL WIRING) TO PROVIDE A COMPLETE SYSTEM. 16. FLEX DUCTWORK SHALL NOT EXCEED 3'-0" IN LENGTH. 17. A CERTIFIED AIR BALANCE REPORT IS TO BE PROVIDED TO THE LANDLORD PRIOR TO STORE OPENING. 18. REMOVE ALL EXISTING MECHANICAL EQUIPMENT, DUCTWORK, PLUMBING FIXTURES, PIPING, SYSTEMS, ETC., NOT BEING REUSED. DO NOT ABANDON. 19. THE G.C. SHALL HAVE EXISTING SANITARY WASTE LINE INSPECTED BY CAMERA, TO LEASE LINE, PRIOR TO COMMENCING NEW WORK. RECORDING OF INSPECTION SHALL BE FURNISHED TO OWNER ALONG WITH ANY FINDINGS ADVISING REPAIR OR CLEARANCE OF ANY OBSERVED OBSTRUCTIONS OF THE EXISTING PIPE P-RIIORI TO ROUGH -IN INSPECTION. e v\ = 20(Y 1 /Lt C- 4'"d 6" f rt(, Sti( C �ti ai 5 MECHANICAL SYMBOLS LEGEND O/O THERMOSTAT / HUMIDISTAT -� VOLUME DAMPER FD : FIRE DAMPER ® CEILING SUPPLY AIR DIFFUSER CEILING RETURN AIR GRILLE SIDEWALL AIR DIFFUSER OR GRILLE NEW DUCTWORK REVIEW=GGA EXISTING DUCTWORK API�� - CD - CONDENSATE DRAIN SD EXISTING SMOKE DETECTOR D PIPE TURNING DOWN O PIPE TURNING UP ef Ell III Uhl BALL VALVE e CONNECTION OF NEW TO EXISTING CHECK VALVE ter- GAS COCK - STRAINER AFF ABOVE FINISHED FLOOR ETR EXISTING TO REMAIN AIR DEVICE # S - SUPPLY R - RETURN CFM E - EXHAUST FIRE PROTECTION SYMBOLS LEGEND OE EXISTING SPRINKLER HEAD CHROME PENDANT SPRINKLER HEAD O UPRIGHT SPRINKLER HEAD 00 CONCEALED SPRINKLER HEAD CI ®I SIDEWALL SPRINKLER HEAD PLUMBING SYMBOLS LEGEND - - - COLD WATER - - - - HOT WATER SANITARY DRAIN ----- SANITARY VENT VTR VENT THROUGH ROOF EO PLUMBING TRAP CO CLEAN OUT 171 GENERAL NOTES 116 LEGEND SCALE: N/A I SCALE: N/A &Vm*k 011 W M M r- O f\ C\ Z L0 U Ou CL W W LQ H • x U Q tY 04 M Q W M > '° ix v0 Vw V,)w N vi Lij >O 0 �Ln a 1 M. E. P. Engineer: ACERTUV CONSULTING GROUP, LLC 14817 West 95th Street ♦ Lenexa. Kansas 66215 IF 913 3715150 ♦ F 913 322 5155 www.AcertusGroup.corn .D FOR IPLIANCE )VIED 20161 LA ukwila DIVISION COPYRIGHT DISCLAIMER: THIS DOCUMENT IS THE PROPERTY OF EPOCH DESIGN GROUP, COPYRIGHTED AS DATED, ALL RIGHTS RESERVED. AUTHORIZATION FROM EPOCH DESIGN GROUP FOR USE OF THIS DOCUMENT Is NOT TRANSFERABLE THE REUPIENT OF THIS DOCUMENT IS HEREBY ADVISED THAT IT IS RELEASED FOR USE UNDER THE FOLLOWING TERMS AND CONDITIONS THE DOCUMENT IS TO BE USED ONLY IN CONJUNCTION WITH THIS PROJECT. REUSE OF ANY PORTION OF THE DOCUMENT IN ANY OTHER CIRCUMSTANCE CONSIT UTES COPYRIGHT INFRINGEMENT. THE DOCUMENT IS FOR DESIGN INTENT AND INFORMATION ONLY, AND DOES NOT CONSTITUTE AS-BLnT CONDITIONS THE RECIPIENT RETAINS THE OBLIGATION TO VERIFY THE CONDITIONS OF THE SUBJECT PROPERTY AND TO COMPLETELY COORDINATE ALL DUIENSIONS, FABRICATION METHODS, RELATED AND INTEGRATED SYSTEMS, ETC. WITH RESPECT TO ALL ASPECTS OF THE WORK. EPOCH DESIGN GROUP MAKES NO WARRANTY AS TO THE SUITABILITY OF THE DOCUMENT FOR THE RECIPIENT'S INTENDED USE THE RECIPIENT SPECIFICALLY AGREES TO WAIVE AND TO INDEMNIFY AND DEFEND ANY AND ALL CLAIMS AGAINST EPOCH DESIGN GROUP, ITS CONSULTANTS, ANY OF ITS RELATED ENTRIES, VENDORS, OR CONTRACTORS, FOR ANY LOSS INCURRED AS A RESULT OF PROPER OR IMPROPER USE OF THIS DOCUMENT. THE RECIPIENT AGREES TO RETURN OR DESTROY THIS DOCUMENT UPON COMPLETION OR TERMINATION OF WORK PERFORMED IN CONJUNCTION WITH THIS PROJECT. PROFESSIONAL SEAL: t PtitiA N� OV WA f - - 12/14/16 EXPIRES: 09/21/17 PROJECT TITLE: SEATTLE, WA SOUTHCENTER MALL SPACE NO.: 1130 11, oft�ffl - , " � ffl " A/ RECEIVED V OF 1 Ul(\ ILA DEC 19 2011 No.,L Revision Description Dote i iUi I'." i, t: i� T R SHEET TITLE: MECHANICAL FLOOR PLAN PROJECT NO.: SHEET NUMBER: 16283 DRAWN BY: JWK ISSUE DATE: 1*0 12/14/16 COPYRIGHT DISCLAIMER: THIS DOCUMENT IS THE PROPERTY OF EPOCH DESIGN GROUP, COPYRIGHTED AS DATED, ALL RIGHTS RESERVED. AUTHORIZATION FROM EPOCH DESIGN GROUP FOR USE OF THIS DOCUMENT IS NOT TRANSFERABM THE RECIPIENT OF THIS DOCUMENT IS HEREBY ADVISED THAT IT IS RELEASED FOR USE UNDER THE FOLLOWING TERMS AND CONDITIONS THE DOCUMENT IS TO BE USED ONLY IN CONJUNCTION WITH 71,1IS PROJECT. REUSE OF ANY PORTION OF THE DOCUMENT IN ANY OTHER CIRCUMSTANCE CONSTITUTES COPYRIGHT INFRINGEMENT. THE DOCUMENT IS FOR DESIGN INTENT AND INFORMATION ONLY, AND DOES NOT CONSTITUTE AS -BUILT CONDITIONS THE RECIPIENT RETAINS THE OBLIGATION TO VERIFY THE CONDITIONS OF THE SUBJECT PROPERTY AND TO COMPLETELY COORDINATE ALL DIMENSIONS, FABRICATION METHODS, RELATED AND INTEGRATED SYSTEMS, ETC, WITH RESPECT TO ALL ASPECTS OF THE WORK. EPOCH DESIGN GROUP MAKES NO WARRANTY AS TO THE SUITABILITY OF THE DOCUMENT FOR THE REOPIENVS INTENDED USE THE RECIPIENT SPECIFICALLY AGREES TO WAIVE AND TO INDEMNIFY AND DEPEND ANY AND ALL CLAIMS AGAINST EPOCH DESIGN GROUP, ITS CONSULTANTS, ANY OF ITS RELATED ENTITIES, VENDORS, OR CONTRACTORS, FOR ANY LOSS INCURRED AS A RESULT OF PROPER OR IMPROPER USE OF THIS DOCUMENT. THE RECIPIENT AGREES TO RETURN OR DESTROY THIS DOCUMENT UPON COMPLETION OR TERMINATION OF WORK PERFORMED IN CONJUNCTION WITH THIS PROJECT. PROFESSIONAL SEAL- 12/14/16 EXPIRES: 09/21/1 7 PROJECT TITLE: SEATTLE, QUA SOUTHICENTER MALL SPACE NO.: 1130 ME L L o.A Revision Description Date SHEET TITLE: R MECHANCIAL DETAILS AND SCHEDULES PROJECT NO.: SHEET NUMBER: 16283 DRAWN BY- JWK ISSUE DATE 0 12/14/16 W M Cl) a O M M (~ w Lu J ON W nZ. V w LL f- E-' Q Y N M WM 9 �O V0 \ w N Lu — Lu ® W N >0 O to z COPYRIGHT DISCLAIMER: THIS DOCUMENT IS THE PROPERTY OF EPOCH DESIGN GROUP, COPYRIGHTED AS DATED, ALL RIGHTS RESERVED. AUTHORIZATION FROM EPOCH DESIGN GROUP FOR USE OF THIS DOCUMENT IS NOT TRANSFERABM THE RECIPIENT OF THIS DOCUMENT IS HEREBY ADVISED THAT IT IS RELEASED FOR USE UNDER THE FOLLOWING TERMS AND CONDITIONS THE DOCUMENT IS TO BE USED ONLY IN CONJUNCTION WITH 71,1IS PROJECT. REUSE OF ANY PORTION OF THE DOCUMENT IN ANY OTHER CIRCUMSTANCE CONSTITUTES COPYRIGHT INFRINGEMENT. THE DOCUMENT IS FOR DESIGN INTENT AND INFORMATION ONLY, AND DOES NOT CONSTITUTE AS -BUILT CONDITIONS THE RECIPIENT RETAINS THE OBLIGATION TO VERIFY THE CONDITIONS OF THE SUBJECT PROPERTY AND TO COMPLETELY COORDINATE ALL DIMENSIONS, FABRICATION METHODS, RELATED AND INTEGRATED SYSTEMS, ETC, WITH RESPECT TO ALL ASPECTS OF THE WORK. EPOCH DESIGN GROUP MAKES NO WARRANTY AS TO THE SUITABILITY OF THE DOCUMENT FOR THE REOPIENVS INTENDED USE THE RECIPIENT SPECIFICALLY AGREES TO WAIVE AND TO INDEMNIFY AND DEPEND ANY AND ALL CLAIMS AGAINST EPOCH DESIGN GROUP, ITS CONSULTANTS, ANY OF ITS RELATED ENTITIES, VENDORS, OR CONTRACTORS, FOR ANY LOSS INCURRED AS A RESULT OF PROPER OR IMPROPER USE OF THIS DOCUMENT. THE RECIPIENT AGREES TO RETURN OR DESTROY THIS DOCUMENT UPON COMPLETION OR TERMINATION OF WORK PERFORMED IN CONJUNCTION WITH THIS PROJECT. PROFESSIONAL SEAL- 12/14/16 EXPIRES: 09/21/1 7 PROJECT TITLE: SEATTLE, QUA SOUTHICENTER MALL SPACE NO.: 1130 ME L L o.A Revision Description Date SHEET TITLE: R MECHANCIAL DETAILS AND SCHEDULES PROJECT NO.: SHEET NUMBER: 16283 DRAWN BY- JWK ISSUE DATE 0 12/14/16 A. GENERAL CONDITIONS 1. DRAWINGS AND GENERAL PROVISIONS OF CONTRACT, INCLUDING GENERAL AND SUPPLEMENTARY CONDITIONS AND ALL OTHER SPECIFICATION SECTIONS (IF PROVIDED AS PART OF THE CONTRACT) ARE A PART OF THIS CONTRACT. 2. THE TERM "CONTRACTOR" SHALL MEAN THE "MECHANICAL CONTRACTOR HIRED TO COMPLETE THE WORK OUTLINED IN THESE PLANS AND SPECIFICATIONS" UNLESS OTHERWISE SPECIFIED. 3. THE CONTRACTOR FOR THIS WORK IS REQUIRED TO REVIEW ALL DRAWINGS FOR ALL OTHER TRADES. 4, THE GENERAL CONTRACTOR 15 RESPONSIBLE FOR PROVIDING ITS SUBCONTRACTORS WITH A FULL SET OF BID DOCUMENTS INCLUDING SPECIFICATIONS AND MUST COORDINATE ITS WORK AND INSPECTIONS AND THE WORK AND INSPECTION OF THEIR SUBCONTRACTORS WITH ALL OTHER TRADES ON SITE TO CONFORM NTH THE GENERAL CONTRACTOR'S TIME SCHEDULE 5. BY SUBMITTING A QUOTATION OR PROPOSAL THE MECHANICAL CONTRACTOR EXPRESSLY STATES AND WARRANTS THAT: ALL DRAWINGS AND SPECIFICATIONS HAVE BEEN THOROUGHLY REVIEWED, CONTRACTOR HAS BECOME FAMILIARIZED WITH JOB SITE CONDITIONS AND IS TOTALLY QUALIFIED TO PERFORM ALL OF THE WORK REQUIRED. 6. BEFORE SUBMITTING A FINAL PROPOSAL THE CONTRACTOR SHALL EXAMINE THE SITE OF THE PROPOSED WORK TO DETERMINE THE EXISTING CONDITIONS THAT MAY AFFECT THE PROPOSAL IF DISCREPANCIES ARE NOTED BETWEEN THE DOCUMENTS AND THE EXISTING CONDITIONS THE ARCHITECT SHALL BE NOTIFIED AND THE CONTRACTOR SHALL RECEIVE CLARIFICATION BEFORE SUBMITTING A BID. THE SUBMISSION OF A PROPOSAL SHALL INDICATE THAT ALL CHARGES AND COSTS MADE NECESSARY BY EXISTING CONDITIONS ARE INCLUDED AND THAT THE COMPLETE SYSTEM AS DESCRIBED HEREIN WILL BE FURNISHED AT THE PROPOSED COST. 7. WHEN USED, THE TERM "PROVIDED BY CONTRACTOR" SHALL BE INTERPRETED AS MEANING "FURNISHED AND INSTALLED BY CONTRACTOR" WITH THE EXCEPTION WHERE ITEMS ARE "PROVIDED BY TENANT" SHALL BE INTERPRETED AS MEANING "FURNISHED BY TENANT (INSTALLED BY CONTRACTOR)", EXCEPT WHERE NOTED OTHERWISE B. GENERAL REQUIREMENTS 1. THE CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS, EQUIPMENT, SERVICES, TOOLS, TRANSPORTATION, INCIDENTALS AND DETAILS NECESSARY TO PROVIDE COMPLETE AND FULLY FUNCTIONAL MECHANICAL SYSTEMS AS SHOWN ON THE DRAWINGS, CALLED FOR IN THE SPECIFICATIONS (IF SUPPLIED) AND AS REQUIRED BY JOB CONDITIONS. ALL WORK NOT SPECIFICALLY NOTED AS BEING BY THE LANDLORD SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR. CLOSELY COORDINATE THE ENTIRE INSTALLATION WITH LANDLORD AS REQUIRED. FIELD VERIFY THE EXACT TYPE, SIZE, LOCATION, REQUIREMENTS, ETC OF EXISTING EQUIPMENT, PIPE AND DUCTS SERVING THE TENANT SPACE PRIOR TO SUBMISSION OF BID. 2. THE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO SUPPLEMENT EACH OTHER AND ANY MATERIAL OR LABOR CALLED FOR IN ONE SHALL BE PROVIDED EVEN THOUGH NOT SPECIFICALLY MENTIONED IN BOTH. ANY MATERIAL OR LABOR WHICH IS NEITHER SHOWN ON THE DRAWINGS NOR CALLED FOR IN THE SPECIFICATIONS, BUT WHICH IS NECESSARY TO COMPLETE THE WORK OR WHICH IS USUALLY INCLUDED IN WORK OF SiMILAR CHARACTER, SHALL BE PROVIDED AS PART OF THE CONTRACT. 3. WHERE THE DRAWINGS AND / OR SPECIFICATIONS CALL FOR ITEMS WHICH EXCEED CODES OR THE LANDLORD'S TENANT CRITERIA, THE CONTRACTOR IS STILL RESPONSIBLE FOR PROVIDING THE SYSTEM AS DESIGNED AND DESCRIBED ON THE DRAWINGS, UNLESS SPECIFICALLY NOTED OTHERWISE 4. THE CONTRACTOR SHALL OBTAIN AND COMPLY WITH DETAILED REQUIREMENTS OF LEASE EXTRACTS FROM THE LANDLORD AND TENANT. 5. COORDINATE LOCATIONS OF ALL AIR OUTLETS WITH ALL WALLS, LIGHTS, SPRINKLER HEADS, CEILING TILES AND DECORATIVE CEILING FIXTURES PRIOR TO INSTALLATION. 6. ALL MECHANICAL WORK SHALL BE INSTALLED SO AS TO BE READILY ACCESSIBLE FOR OPERATION, SERVICE, MAINTENANCE AND REPAIR. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING SUFFICIENT ACCESS TO ALL EQUIPMENT FOR SERVICE. 7. THE CONTRACTOR SHALL DO ALL CUTTING, CORE DRILLING, CHASING, OR CHANNELING AND PATCHING REQUIRED FOR ANY WORK UNDER THIS CONTRACT. CUTTING SHALL HAVE PRiOR APPROVAL BY THE TENANT'S CONSTRUCTION MANAGER AND THE LANDLORD OR LANDLORD'S REPRESENTATIVE PATCHING SHALL MATCH FINISH OF SURROUNDING AREA. C CODES 1. ALL WORK SHALL BE PERFORMED IN A NEAT AND PROFESSIONAL MANNER USING GOOD CONSTRUCTION PRACTICES. ALL WORK SHALL CONFORM TO THE LATEST ADOPTED EDITION OF THE LANDLORD'S CRITERIA; PROVINCE, COUNTY AND LOCAL CODES AND ORDINANCES; THE LATEST EDITIONS OF ASHRAE STANDARDS, THE LIFE SAFETY CODE, THE APPLICABLE BUILDING CODE, UNDERWRITERS LABORATORIES, THE NATIONAL ELECTRICAL CODE, NFPA 70, 90A AND 96 AND ALL OTHER APPLICABLE CODES ENFORCED BY AUTHORITIES HAVING JURISDICTION. THE CHANGES REQUIRED BY ANY APPLICABLE CODES SHALL BE INCLUDED IN THE BID. AFTER THE CONTRACT IS ISSUED, NO ADDITIONAL COST DUE TO CODEISSUES SHALL BE REIMBURSED BY THE TENANT TO THE CONTRACTOR. D. LICENSES, PERMITS, INSPECTIONS AND FEES 1. THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL LICENSES, PERMITS, INSPECTIONS AND FEES REQUIRED OR RELATED TO THIS WORK. 2. FURNISH TO THE TENANT'S CONSTRUCTION MANAGER ALL CERTIFICATES OF INSPECTION AND FINAL INSPECTION APPROVAL AT COMPLETION OF PROJECT. E DRAWINGS 1. DRAWINGS (PLANS AND SPECIFICATIONS) ARE DIAGRAMMATIC AND INDICATE THE GENERAL LOCATION AND INTENT OF THE MECHANICAL SYSTEMS. BECAUSE OF THE SCALE OF THE DRAWINGS, IT IS NOT POSSIBLE TO INDICATE ALL DUCT AND PIPE OFFSETS, FITTINGS AND ACCESSORIES THAT MAY BE REQUIRED. THE MECHANICAL CONTRACTOR MUST OBTAIN APPROVED CONSTRUCTION DRAWINGS FROM THE GENERAL CONTRACTOR BEFORE BEGINNING ANY WORK. 2. THE LAYOUT SHOWN ON THE DRAWINGS IS BASED ON A PARTICULAR MAKE OF EQUIPMENT. IF ANOTHER MAKE OF EQUIPMENT IS USED WHICH REQUIRES MODIFICATION OR CHANGE OF ANY DESCRIPTION FROM THE DRAWINGS OR SPECIFICATIONS, THE CONTRACTOR SHALL BE RESPONSIBLE AS PART OF THIS WORK, FOR MAKING ALL SUCH MODIFICATIONS AND CHANGES, INCLUDING THOSE INVOLVING OTHER TRADES WITH THE COST THEREOF INCLUDED IN THE BID. IN SUCH CASE, CONTRACTOR SHALL SUBMIT DRAWINGS AND SPECIFICATIONS PRIOR TO STARTING WORK SHOWING ALL SUCH MODIFICATIONS AND CHANGES. THE PROPOSAL SHALL BE SUBJECT TO THE APPROVAL OF THE TENANTS CONSTRUCTION MANAGER. F. EXISTING LEASE SPACE CONDITIONS 1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF THE DEMOLITION OF EXISTING MECHANICAL WORK IN THE SPACE NOT SHOWN TO BE REUSED IN THE NEW TENANT SPACE 2. THE CONTRACTOR SHALL INCLUDE AND WILL BE HELD RESPONSIBLE FOR, THE REMOVAL OF ALL EXISTING FIRE PROTECTION, PLUMBING FIXTURES, PIPING, HVAC UNITS, REFRIGERANT RECAPTURE, EXHAUST FANS, DUCTWORK, ETC AND ASSOCIATED ROOF CURBS NOT TO BE REUSED ON THIS PROJECT, UNLESS SPECIFICALLY NOTED OTHERWISE CONTRACTOR MUST VERIFY WITH THE LANDLORD ALL PRESUMED ABANDONED EQUIPMENT, PIPES, DUCTWORK AND EQUIPMENT PRIOR TO REMOVAL ROOF CURBS SHALL BE REMOVED AND THE ROOF PATCHED UNLESS NOTED FOR REUSE OR RECONFIGURATION ON PLANS. ROOF PATCHING SHALL BE PERFORMED AT THE CONTRACTOR'S EXPENSE BY A ROOFING CONTRACTOR APPROVED BY THE LANDLORD. ALL EXTRANEOUS ITEMS IN THE SPACE OR ON THE ROOF (ABOVE THIS SPACE) NOT APPLICABLE TO THE NEW WORK OR PART OF THE LANDLORD'S OR ANOTHER TENANT'S ACTIVE SYSTEM MUST BE REMOVED AND ROOF/WALL/FLOOR PATCHED/REPAIRED TO MATCH THE EXISTING STRUCTURE EXISTING ABANDONED PIPES, DUCTS OR EQUIPMENT IN THE FLOOR, EMBEDDED IN CONCRETE OR OTHERWISE INACCESSIBLE ARE TO BE CUT OFF AND SEALED BELOW OR WITHIN FLOOR OR WALL LEVEL WHEN THEY ARE NOT REUSED IN THIS PROJECT. IF REQUIRED BY THE LANDLORD OR CODES, ABANDONED PIPING AND/OR DUCTWORK MUST BE REMOVED TO POINT OF ORIGIN. CONFIRM THE EXTENT OF DEMOLITION PRIOR TO BID AND INCLUDE IN BID PROPOSAL 3. ACTIVE LANDLORD OR OTHER TENANT SERVICES ENCOUNTERED IN WORK SHALL BE PROTECTED AND SUPPORTED. IF EXISTING SERVICES NOT ANTICIPATED REQUIRE RELOCATION, CONTACT THE TENANT'S CONSTRUCTION MANAGER IMMEDIATELY. ALL COSTS FOR REPAIR OF DAMAGES TO ACTIVE LANDLORD OR OTHER TENANT SERVICES DURING CONSTRUCTION SHALL BE PAID FOR BY THE CONTRACTOR CAUSING THE DAMAGE 4. TIE-INS AND MODIFICATIONS TO EXISTING LANDLORD SERVICES MUST BE DONE WITH MINIMUM INTERRUPTION OF LANDLORD OPERATION AND DURING HOURS SPECIFIED BY THE LANDLORD. THE CONTRACTOR IS RESPONSIBLE FOR CONFIRMING EXACT WORKING HOURS OF THIS WORK WITH THE LANDLORD PRIOR TO SUBMITTING THEIR BID. THE CONTRACTOR SHALL INCLUDE IN THEIR BID, ALL PREMIUM TIME REQUIRED TO PERFORM MODIFICATIONS DURING OTHER THAN NORMAL WORKING HOURS. ALL SUCH WORK MUST BE COORDINATED WITH THE LANDLORD. 5. EQUIPMENT AND MATERIALS IN TRANSIT SHALL UTILIZE FREIGHT ELEVATOR OR STAIRS. SAID EQUIPMENT OR MATERIALS SHALL BE DISASSEMBLED AS REQUIRED TO MEET THE RESTRICTIONS IMPOSED BY THE BUILDING OR ITS COMPONENT CONSTRAINTS AND THEN REASSEMBLED IN THE NEW WORK AREA. 6. ALL WORK SHALL BE DONE WITH A MINIMUM OF NOISE AND DISTURBANCE TO BUSINESS ROUTINE ALL WORK SCHEDULES SHALL BE COORDINATED WITH AND APPROVED BY, THE TENANTS CONSTRUCTION MANAGER. 7. SINCE THESE ARE SECURE FLOORS, ALL DELIVERIES, WORKERS, WORK OPERATORS, ETC, REQUIRED BY THE CONTRACTOR FOR WORK PERFORMED IN ANY AREA OR SITE BUILDING SHALL BE IN STRICT CONFORMANCE TO THE RULES AND REGULATIONS OF THE OWNER. 8, CONTRACTOR SHALL PROTECT THEIR WORK AND EQUIPMENT FROM DAMAGE, VANDALS, ETC ANY ITEM THAT IS DAMAGED, VANDALIZED OR STOLEN PRIOR TO ACCEPTANCE OF BUILDING BY OWNER AND ARCHITECT SHALL BE REPLACED BY RESPECTIVE CONTRACTOR AT NO CHARGE TO TENANT. 9. IT IS SPECIFICALLY THE INTENTION OF THIS SPECIFICATION TO HOLD THE CONTRACTOR RESPONSIBLE FOR ALL DAMAGE DONE TO ANY EXISTING FACILITIES, EQUIPMENT, PAINTING, OR ARCHITECTURAL AND STRUCTURAL FEATURES OF THE BUILDING, BY EITHER THEIR OWN WORKMEN OR BY ANY OF THEIR SUBCONTRACTORS. THE CONTRACTOR SHALL REPAIR ANY DAMAGE DONE BY THEIR OWN WORKMEN OR SUBCONTRACTORS AND THE OWNER AT THEIR DISCRETION, MAY WITHHOLD PAYMENTS EQUAL TO THE REASONABLE COST OF THE REPAIRS. 10. THIS CONTRACTOR OR THEIR WORKMEN SHALL NOT BE PERMITTED TO USE ANY PART OF THE EXISTING BUILDING AS A SHOP WITHOUT THE APPROVAL OF THE OWNER AND ARCHITECT. 11. WHERE THE WORK MAKES TEMPORARY SHUTDOWN OF SERVICES UNAVOIDABLE, THEY SHALL BE MADE AT NIGHT OR AT SUCH TIMES AS WILL CAUSE THE LEAST INTERFERENCE WITH THE ESTABLISHED OPERATING ROUTINE 12. THIS CONTRACTOR SHALL ARRANGE THE WORK SO AS TO ASSURE THAT SERVICES WILL BE SHUT DOWN ONLY DURING THE TIME ACTUALLY REQUIRED TO MAKE THE NECESSARY CONNECTION TO THE EXISTING WORK. THIS CONTRACTOR SHALL GIVE AMPLE WRITTEN NOTICE IN ADVANCE TO THE OWNER OF ANY REQUIRED SHUT DOWN. 13. ALL MOTORS, FANS, CONTROLS, FIXTURES, HVAC UNIT, DUCTWORK AND OTHER EQUIPMENT FOR USE IN THIS CONTRACT SHALL BE PROTECTED BY TARPAULIN OR BY BOXING AS SOON AS DELIVERED TO THE SITE AND SHALL BE KEPT CLEAN AND DRY. THE MOTORS, UNITS, FIXTURES, FANS, DUCTWORK AND MOVING PARTS SHALL BE KEPT COVERED SO AS TO ELIMINATE DIRT, DUST AND OTHER MATERIALS ENTERING THE PARTS DURING ERECTION AND CONSTRUCTION WORK ON THE BUILDING. SHOULD IT BE FOUND THAT ANY PARTS ARE DAMAGED DUE TO CARELESSNESS ON THE PART OF THE CONTRACTOR IN NOT PROVIDING PROPER PROTECTION, SUCH PART OR PARTS SHALL BE REPLACED BY THE CONTRACTOR AT THEIR OWN COST AND EXPENSE ALL OPENINGS IN DUCTS, PIPING, CONDUITS, ETC, SHALL BE PROPERLY PROTECTED WITH TEMPORARY CAPS OR PLUGS AT ALL TIMES. G. DISCREPANCIES IN DOCUMENTS ARE DIAGRAMMATIC AND INDICATE THE GENERAL LOCATION AND INTENT OF THE MECHANICAL i912011 H. TRADE NAMES AND MANUFACTURERS 1. WHERE TRADE NAMES AND MANUFACTURERS ARE USED ON THE DRAWINGS OR IN THE SPECIFICATIONS, THE EXACT EQUIPMENT SHALL BE USED AS A MINIMUM STANDARD FOR THE BASE BID. MANUFACTURERS CONSIDERED AS AN EQUIVALENT OR BETTER IN ALL ASPECTS TO THAT SPECIFIED WILL BE SUBJECT TO REVIEW IN WRITING BY THE TENANT'S CONSTRUCTION MANAGER PRIOR TO ACCEPTANCE THE USE OF ANY UNAUTHORIZED EQUIPMENT SHALL BE SUBJECT TO REMOVAL AND REPLACEMENT AT THE CONTRACTOR'S EXPENSE 1. SUBMIT THREE COPIES OF MATERIAL LISTS AND SHOP DRAWINGS FOR ALL EQUIPMENT AND DUCT FABRICATION DRAWINGS TO THE TENANT'S CONSTRUCTION MANAGER FOR REVIEW PRIOR TO ORDERING EQUIPMENT. SUBMISSIONS MUST BE EARLY ENOUGH TO ALLOW THE TENANT'S RE .SUBMITTALS CONSTRUCTION MANAGER EiGHT WORKING DAYS FOR REVIEW WITHOUT CAUSING DELAYS OR CONFLICTS TO THE JOB S PROG SS SHALL BE IN ACCORDANCE WITH THE GENERAL CONDITIONS USING THE MANUFACTURER'S LISTED ON THE DRAWINGS. SHOP DRAWINGS SHALL INCLUDE ALL DATA THAT PERTAINS TO THE REQUIREMENTS SET FORTH ON THE DRAWINGS AND IN THE SPECIFICATIONS. THE SUBMITTAL SHALL INCLUDE BUT NOT BE LIMITED TO CUTS OR CATALOGS INCLUDING DESCRIPTIVE LITERATURE AND CHARACTERISTICS OF EQUIPMENT SHALL SHOW MAJOR DIMENSIONS, ROUGHING -IN DATA, CAPACITY, CURVES, PRESSURE DROPS, CODE COMPLIANCE, MOTOR AND DRIVE DATA AND ELECTRICAL DATA. OBSERVE SPECIAL INSTRUCTIONS WHEN REQUIRED. SUBMITTALS SHALL BEAR THE STAMP OF THE GENERAL AND SUBCONTRACTOR SHOWING THAT HE HAS REVIEWED AND CONFIRMED THAT THEY ARE IN CONFORMANCE WITH THE CONTRACT DOCUMENTS OR INDICATE WHERE EXCEPTIONS TAKE PLACE LACK OF SUCH CONTRACTOR'S REVIEW WILL BE CAUSE FOR REJECTION WITHOUT REVIEW BY TENANT'S CONSTRUCTION MANAGER. ALL SHOP DRAWINGS MUST APPEAR IN THE OPERATION AND MAINTENANCE MANUALS LEFT ON SITE AT JOB COMPLETION. 2. TENANT'S CONSTRUCTION MANAGER'S OR ARCHITECT'S REVIEW OF SHOP DRAWINGS OR SCHEDULES SHALL NOT RELIEVE THE CONTRACTOR FROM RESPONSIBILITY FOR ERRORS, OMISSIONS OR OTHER DEFICIENCIES OR DEVIATIONS IN THE SHOP DRAWINGS FROM THE CONSTRUCTION DOCUMENTS. 3. IT IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR AND / OR THEIR SUBCONTRACTORS TO FURNISH SHOP DRAWINGS AND SUBMITTALS ON ANY AND ALL EQUIPMENT, DUCT, DAMPERS, CONTROLS ETC TO THE ARCHITECT FOR THEIR REVIEW PRIOR TO CONSTRUCTION. 1. RECORD DRAWINGS 1. THE CONTRACTOR SHALL MAINTAIN ONE COPY OF DRAWINGS AND SPECIFICATIONS ON THE JOB SITE TO RECORD DEVIATIONS FROM CONTRACT DRAWINGS, SUCH AS LOCATIONS OF CONCEALED PIPING VALVES AND DUCTS, REVISIONS, ADDENDUM'S AND CHANGE ORDERS, SIGNIFICANT DEVIATIONS MADE NECESSARY BY FIELD CONDITIONS, APPROVED EQUIPMENT SUBSTITUTIONS AND CONTRACTOR'S COORDINATION WITH OTHER TRADES AND EXACT ROUTING OF ALL SANITARY AND DOMESTIC WATER PIPING UNDER FLOOR. 2. AT COMPLETION OF THE PROJECT AND BEFORE FINAL APPROVAL, THE CONTRACTOR SHALL MAKE ANY FINAL CORRECTIONS TO DRAWINGS AND CERTIFY THE ACCURACY OF EACH PRINT BY SIGNATURE THEREON. THE DRAWINGS ARE TO BE TURNED OVER TO THE TENANT. K. GUARANTEE, WARRANTY ON ALL UIPMENT AND MATERIAL 1. THE MECHANICAL CONTRACTOR SHALL INCLUDE IN THE PROPOSAL A ONE YEAR GUARANTEE, WARRANTY EQ INSTALLED OR REFURBISHED, ALL MATERIALS AND WORK UNDER THE CONTRACT AND SHALL MAKE GOOD, REPAIR, OR REPLACE AT THEIR OWN EXPENSE, ANY DEFECTIVE WORK, MATERIAL OR EQUIPMENT WHICH MAY BE DISCOVERED WITHIN A PERIOD OF 12 MONTHS FROM THE DATE OF WRITTEN ACCEPTANCE OF THE INSTALLATION BY THE TENANT'S CONSTRUCTION MANAGER. IN CASE OF REPLACEMENT OR REPAIR OF EQUIPMENT DUE TO FAILURE WITHIN THE GUARANTEE PERIOD, THE GUARANTEE ON THAT PORTION OF WORK SHALL BE EXTENDED FOR A PERIOD OF 12 MONTHS FROM THE DATE OF SUCH REPLACEMENT OR REPAIR. THIS GUARANTEE, WARRANTY IS TO INCLUDE ALL LABOR, MATERIAL, PARTS, ETC NECESSARY TO MAINTAIN THE SYSTEM IN SATISFACTORY OPERATION FOR A PERIOD OF ONE YEAR STARTING FROM THE DATE OF ACCEPTANCE OF THE SYSTEM BY THE TENANT. IT SHALL ALSO INCLUDE ONE SUMMER TO WINTER CHANGEOVER AND ONE WINTER TO SUMMER CHANGEOVER, A NEW SET OF FILTERS AT THE TIME OF STARTUP AND TWELVE (12) MONTHLY FILTER CHANGES DURING THE FIRST YEAR. THE NORMAL PREVENTATIVE MAINTENANCE WORK SHALL BE PERFORMED AT THE TIME OF THE FILTER CHANGES. USE ONLY #40 PLEATED TYPE AIR FILTERS. L OPERATIONS MANUALS 1.ONE COPY OF EACH OPERATION AND MAINTENANCE MANUAL FOR ALL EQUIPMENT FURNISHED ON THE JOB SHALL BE PROVIDED TO THE TENANT BOUND TOGETHER IN A 3 INCH, THREE RING BINDER. THE BINDER SHALL INCLUDE BUT NOT BE LIMITED TO INSTALLATION, MAINTENANCE AND OPERATING INSTRUCTIONS, PAMPHLETS OR BROCHURES, REVIEWED SHOP DRAWINGS AND WARRANTIES OBTAINED FROM EACH MANUFACTURER OF PRINCIPAL ITEMS OF EQUIPMENT. i%#t;ff; 1. THE CONTRACTOR SHALL PROVIDE SLEEVES TO PROTECT EQUIPMENT OR FACILITIES IN THE INSTALLATION. EACH SLEEVE SHALL EXTEND THROUGH ITS RESPECTIVE FLOOR, WALL, OR PARTITION AND SHALL BE CUT FLUSH WITH EACH SURFACE EXCEPT SLEEVES THAT PENETRATE THE FLOOR, WHICH SHALL EXTEND 2 INCHES ABOVE THE FLOOR. 2. ALL SLEEVES AND OPENINGS THROUGH FIRE RATED WALLS AND/OR FLOORS SHALL BE RRE SEALED WITH APPROVED SEALANTS RATED FOR THE APPLICATION SO AS TO MAINTAIN THE FIRE RATING OF THE ASSEMBLY. CONFORM TO THE U.L ASSEMBLY RATING OF THE FLOOR OR WALL 3. SLEEVES IN BEARING AND MASONRY WALLS, FLOORS AND PARTITIONS SHALL BE STANDARD WEIGHT STEEL PIPE FINISHED WITH SMOOTH EDGES. FOR OTHER THAN MASONRY PARTITIONS, THROUGH SUSPENDED CEILINGS OR FOR CONCEALED VERTICAL PIPING, SLEEVES SHALL BE 22 GAUGE GALVANIZED STEEL MINIMUM. 4. DUCT SLEEVES SHALL BE MINIMUM 14 GAUGE STEEL N. HANGERS 1. HANGERS SHALL INCLUDE ALL MISCELLANEOUS STEEL SUCH AS ANGLE IRON, BANDS, C -CLAMPS WITH RETAINING CLIPS, CHANNELS, HANGER RODS, ETC NECESSARY FOR THE INSTALLATION OF WORK. 2. HANGERS SHALL BE FASTENED TO BUILDING STEEL, CONCRETE, OR MASONRY, BUT NOT TO PIPING OR DUCTWORK. DUCTWORK SHALL NOT BE SUPPORTED FROM ROOF DECKING AND/OR BRIDGING, BUT SHALL BE SUSPENDED FROM THE TOP CHORD OF BAR JOISTS, STEEL OR OTHER STRUCTURE DUCTWORK SHALL CLEAR ALL SPRINKLERS AND OTHER OBSTACLES AND SHALL BE HUNG AS HIGH AS POSSIBLE IN WORK AND STORAGE AREAS. WHERE INTERFERENCE'S OCCUR, IN ORDER TO SUPPORT DUCTWORK OR PIPING, THE CONTRACTOR MUST INSTALL TRAPEZE TYPE HANGERS OR SUPPORTS WHICH SHALL BE LOCATED WHERE THEY DO NOT INTERFERE WITH ACCESS TO FIRE DAMPERS, VALVES, ACCESS DOORS AND OTHER EQUIPMENT SERVICE REQUIREMENTS AND/OR OTHER TRADES. HANGER TYPES AND INSTALLATION METHODS ARE SUBJECT TO LANDLORD CRITERIA 3. HANGERS FOR ALL INSULATED PIPING SHALL BE SIZED AND INSTALLED FOR THE OUTER DIAMETER OF INSULATION. INSTALL 6 INCH LONG SPLIT CIRCLE GALVANIZED SADDLE BETWEEN THE HANGER AND THE PIPE INSULATION. 4. HANGERS AND PIPING OF DISSIMILAR METALS SHALL BE DI -ELECTRICALLY SEPARATED FROM ONE ANOTHER. 0. ELECTRIC MOTORS 1. FURNISH, INSTALL AND ALIGN ALL MOTORS REQUIRED FOR THIS EQUIPMENT, UNLESS THEY ARE FACTORY INSTALLED ON THE UNIT. ALL STARTERS AND ASSOCIATED WIRING AND SAFETY SWITCHES FOR SUCH MOTORS SHALL BE FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR. STARTERS SHALL MEET ALL REQUIREMENTS AS DEFINED IN THE ELECTRICAL SPECIFICATIONS. 2. DESIGN, CONSTRUCTION AND PERFORMANCE CHARACTERISTICS OF MOTORS SHALL CONFORM TO ALL APPLICABLE PROVISIONS OF LATEST NEMA, ANSI, ISEE STANDARDS FOR ELECTRICAL EQUIPMENT. ALL MOTORS SHALL BE SUITABLE FOR OPERATION ON VOLTAGE VARIATION OF PLUS OR MINUS 10 PERCENT, 40 DEGREES C AMBIENT TEMPERATURE AND HAVE A SERVICE FACTOR OF NOT LESS THAN 1.15. P. LOW VOLTAGE (24 VOLT) WIRING 1. THE CONTRACTOR IS TO INSTALL ALL LOW VOLTAGE WIRING REQUIRED FOR THEIR EQUIPMENT. THIS WORK INCLUDES ALL TRANSFORMERS AND DEVICES TO MAKE THIS A COMPLETE FUNCTIONAL SYSTEM. 2. ALL WORK IS TO CONFORM TO THE ELECTRICAL SPECIFICATIONS AND THE REQUIREMENTS OF THE AUTHORITIES HAVING JURISDICTION. 3. ANY CONDUIT REQUIRED BY CODE OR THE LANDLORD WILL BE INSTALLED BY THE ELECTRICAL SUBCONTRACTOR. 4. SMOKE DETECTORS AND REMOTE TEST STATION A. IONIZING TYPE ARE TO BE USED ON THE RETURN SIDE OF THE HVAC UNIT AND PHOTO -TYPE ARE TO BE USED ON THE SUPPLY SIDE ON ALL OTHER TYPES OF HVAC UNITS WHERE SMOKE DUCT DETECTORS ARE REQUIRED, USE FIELD INSTALLED IONIZING TYPE IN RETURN DUCTWORK AND PHOTO -TYPE ON THE SUPPLY LOCATED BEFORE THE FIRST TAKEOFF. ONCE ACTIVATED, THE SMOKE DETECTOR WILL SHUT DOWN HVAC UNIT. B. SMOKE DETECTORS SHALL HAVE THEIR OWN REMOTE KEY TEST STATION SYSTEM WITH AUDIBLE AND VISUAL ALARM, SIMPLEX MODEL 4098-9842 OR APPROVED EQUIVALENT. ALARM TO HAVE CANDELA SETTING OF 75 AND A HIGH VOLUME HORN TONE SETTING. MECHANICAL SPECIFICATIONS A. HEATING, VENTILATION AND AIR CONDITIONING 1. BEFORE STARTING WORK, THIS CONTRACTOR SHALL EXAMINE THE ARCHITECTURAL, STRUCTURAL, MECHANICAL AND ELECTRICAL PLANS AND SPECIFICATIONS TO SEQUENCE, COORDINATE AND INTEGRATE THE VARIOUS ELEMENTS OF THE HVAC SYSTEM, MATERIALS AND EQUIPMENT WITH OTHER CONTRACTORS TO AVOID INTERFERENCE'S AND CONFLICTS. B. HVAC EQUIPMENT (REFER TO PLANS FOR SCHEDULE OF EQUIPMENT) 1. PRIMARY HVAC UNITS ARE TO BE AS SCHEDULED. EQUIVALENTS MAY BE SUBSTITUTED WITH WRITTEN APPROVAL ONLY. ALL COMPRESSORS ARE TO INCLUDE A 5 YEAR EXTENDED WARRANTY. 2. ALL EQUIPMENT SHALL BE COMPLETE IN EVERY RESPECT WITH ALL DEVICES, APPURTENANCES AND ACCESSORIES PROVIDED TO MEET THE DESIGN INTENT AND OPERATION OF THE SYSTEMS SHOWN ON THE DRAWINGS AND SPECIFIED. 3. EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. ALL AIR CONDITIONING EQUIPMENT MUST HAVE A CONDENSATE DRAIN AND BE TRAPPED IN ACCORDANCE WITH MANUFACTURER'S DATA. SEE DRAWINGS FOR ADDITIONAL DETAILS. 4. SECONDARY DRAIN PANS ARE REQUIRED TO BE INSTALLED BENEATH ALL INDOOR AIR CONDITIONING EQUIPMENT WITH THE EXCEPTION OF AIR TERMINAL BOXES. SECONDARY PANS ARE TO PROTECT ENTIRE UNIT. PROVIDE CONDENSATE PUMPS AS REQUIRED. CONDENSATE SHALL BE DIRECTED TO MOP SINK, LAVATORY TRAP OR OTHER APPROVED DRAIN. C TOILET EXHAUST FANS 1. WHERE SHOWN ON DRAWINGS PROVIDE A TOILET EXHAUST FAN COMPLETE WITH GRAVITY BACKDRAFT DAMPER. ALL DUCTWORK, ROOF OPENINGS AND CAPS NECESSARY TO PROVIDE A COMPLETE EXHAUST SYSTEM SHALL BE PROVIDED BY THE CONTRACTOR. REFER TO PLANS FOR APPLICABILITY. D. VIBRATION ISOLATION DEVICES 1. VIBRATION ISOLATION DEVICES SHALL BE PROVIDED IN ALL SUPPORTS BETWEEN VIBRATING EQUIPMENT (FANS, ROOFTOP UNITS, WATER SOURCE HEAT PUMPS, AIR HANDLERS, FAN POWERED VAV BOXES, ETC) AND STRUCTURE 2. VIBRATING EQUIPMENT HUNG FROM STRUCTURE SHALL BE ISOLATED WITH RUBBER AND SPRING DEVICES. VIBRATING EQUIPMENT SUPPORTED FROM FLOOR OR DECK SHALL BE ISOLATED WITH HOUSED SPRING MOUNT DEVICES. 3. EXAMINE DEAD LOAD AND OPERATING LOAD CONDITIONS WHEN SELECTING DEVICES. ADJUST FOR PROPER ALIGNMENT AND LOADING. AVOID "GROUNDING" THE ISOLATOR. 4. CHECK HANGER ROD SIZE FOR ALLOWABLE LOADS AT THE ISOLATING DEVICE AND THE UPPER AND LOWER ATTACHMENTS TO STRUCTURES, DUCTS, EQUIPMENT, ETC 5. CONSULT MANUFACTURER FOR APPLICATION DATA. G. CURBS AND STEEL FRAMING FOR SUPPORT 1. THIS CONTRACTOR WILL PROVIDE ALL NECESSARY CURBS AND STEEL FRAMING REQUIRED TO INSTALL ALL HVAC EQUIPMENT. CURBS SHALL BE A MINIMUM OF 14 INCHES HIGH AND OF THE SAME MANUFACTURER AS THE EQUIPMENT SUPPORTED. INSULATE UNDER THE COMPRESSOR SECTION TO PREVENT CONDENSATION. ALL CURBS MUST BE INSTALLED SO THAT THE TOP OF CURBS ARE'DEAD" LEVEL ALL PENETRATIONS OF EXISTING STRUCTURE SHALL BE DONE IN ACCORDANCE WITH THE LANDLORD'S GUIDELINES AT THIS CONTRACTOR'S EXPENSE ALL CONNECTIONS TO ROOFTOP EQUIPMENT SHALL BE INSIDE THE CURB (CONDENSATE DRAIN, POWER WIRING, CONTROL WIRING, ETC). H. METAL DUCTWORK - NO FIBERGLASS DUCT ALLOWED 1. NO DUCTWORK SHALL BE FABRICATED PRIOR TO APPROVAL BY THE TENANT'S CONSTRUCTION MANAGER. DEVIATIONS FROM DESIGN MUST BE APPROVED BY TENANT'S CONSTRUCTION MANAGER PRIOR TO FABRICATION OR INSTALLATION. ALL DUCT MAINS ARE TO BE RECTANGULAR. ALL DUCT BRANCHES TO DIFFUSERS ARE TO BE ROUND SPIRAL DUCT. 2. ALL DUCTWORK SHALL BE PROVIDED AND INSTALLED IN ACCORDANCE WITH SMACNA LOW VELOCITY AND "HVAC DUCT CONSTRUCTION STANDARDS MANUAL', LATEST EDITION AND ASHRAE USING PRIME SHEETS OF GALVANIZED STEEL CONFORM TO THE REQUIREMENTS IN THE REFERENCED STANDARD FOR METAL THICKNESS, REINFORCING TYPES AND INTERVALS, TIE ROD APPLICATIONS AND JOINT TYPES AND INTERVALS. ALL SQUARE ELBOWS SHALL BE PROVIDED WITH DOUBLE WALLED VANES ON MAXIMUM 3" CENTERS. PROVIDE SEAL CLASS "CON ALL TRAVERSE JOINTS UNLESS SUPERSEDED BY MORE STRINGENT LOCAL CODES. ALL DUCT CONNECTIONS ARE TO BE RIGID AND LEAK FREE ASSEMBLIES. EALED P F ANY PENINGS EITHER AT ALLED I TO BE COMPLETELY S U 0 0 ANY DUCTWORK (NST S N PHA E OF THE PROJECT , D RING THE CONSTRUCTIO S 3. U , THE BEGINNING OR END OF A DUCT RUN OR AT A BRANCH, COLLAR DIFFUSER OR REGISTER TO AVOID DIRT OR OTHER CONTAMINANTS FROM ENTERING THE SYSTEM. 4. EXCEPT WHERE OTHERWISE INDICATED, CONSTRUCT DUCT SYSTEMS TO 2 INCH WATER GAUGE PRESSURE CLASSIFICATION (VERIFY WHETHER RETURN OR EXHAUST DUCT IS POSITIVE OR NEGATIVE PRESSURE). PRESSURE TEST DUCTS FOR LEAKAGE REMAKE LEAKING JOINTS AND APPLY SEALANTS AS REQUIRED TO FABRICATE A SYSTEM THAT DOES NOT EXCEED 5 PERCENT LEAKAGE OR LESS AS STATED BY PRESSURE CLASS RATINGS IN SMACNA STANDARDS. 5. AS A MINIMUM, CROSSBREAK ALL FLAT SURFACES OR REINFORCE WITH A BEAD APPROXIMATELY 3/8 INCH WIDE BY 3/16 INCH DEEP ON 12 INCH CENTERS TO PREVENT VIBRATIONS. 6. INSTALL RIGID ROUND AND RECTANGULAR METAL DUCT WITH SUPPORT SYSTEMS INDICATED IN SMACNA STANDARDS. NO WOOD SHALL BE USED TO SUPPORT OR BRACE DUCTS. PROVIDE SWAY AND SEISMIC BRACING AS REQUIRED BY PROVINCE AND LOCAL CODES OR BY LANDLORD. 7. WHERE DUCTS PASS THROUGH ROOFS, FLOORS AND FIRE RATED PARTITIONS, PROVIDE AS MINIMUM 1-1/2 INCH BY 1-1/2 INCH BY i/8 INCH STEEL ANGLE FRAMES AT EACH SIDE OF OPENING. THE ANNULAR SPACE BETWEEN DUCT AND ANGLE FRAMES SHALL BE CAULKED WITH SILICONE SEALANT OR FIREPROOFED AS REQUIRED BY THE ASSEMBLY FIRE RATING. CONTRACTOR TO PROVIDE FIRE OR COMBINATION FIRE / SMOKE DAMPERS AT EACH PENETRATION WHERE REQUIRED BY CODE 8. ALL TRAVERSE JOINTS AND SEAMS IN SUPPLY AIR DUCT SHALL BE SEALED AIR TIGHT WITH DAP CMC DUCT SEALER. JOINTS ALSO SHALL BE RIVETED OR CONNECTED WITH SHEET METAL SCREWS. 9. SOFT ELASTOMER BUTYL GASKETS WITH ADHESIVE BACKING SHALL BE USED TO SEAL FLANGED JOINTS. 10. DUCT TRANSITIONS SHALL NOT EXCEED 30 DEGREES SLOPE EXCEPT AS SPECIFICALLY NOTED OTHERWISE 11. PROVIDE ACCESS TO ALL MOTORIZED DAMPERS, FIRE DAMPERS, FIRE /SMOKE DAMPERS, CONTROLS AND OTHER ITEMS IN DUCTWORK THAT REQUIRE SERVICE OR INSPECTION. iF THE ACCESS PANEL LOCATION IS EXPOSED TO THE SALES AREA, iT MUST BE APPROVED BY THE TENANT'S CONSTRUCTION MANAGER PRIOR TO INSTALLATION. LAY -IN SUPPLY AND RETURN AIR DIFFUSERS, GRILLES AND REGISTERS WITH PLASTER FRAMES MAY BE USED AS ACCESS LOCATIONS. 12. ALL BRANCHES AND TAKEOFFS SHALL BE EQUIPPED WITH MANUAL VOLUME CONTROWNG DEVICES HAVIHG AN INDICATING AND LOCKING DEVICE I. FLEXIBLE CONNECTIONS 1. FLEXIBLE COLLARS SHALL BE PROVIDED IN All CONNECTIONS BETWEEN VIBRATING EQUIPMENT (FANS, ROCFTOP UNITS, WATER SOURCE HEAT PUMPS, AIR HANDLERS, FAN POWERED VAV BOXES, ETC) AND DUCTS OR CASINGS. ALSO PROVIDE FLEXIBLE CONNECONS WHERE DUCTS CROSS BUILDING EXPANSION JOINTS. 2. FLEXIBLE CONNECTIONS SHALL BE CONSTRUCTED OF NEOPRENE -COATED FLAMEPROOF FABRIC PROVIDE ADEQUATE JOINT FLEXIBILITY TO ALLOW FOR MOVEMENT AND PREVENT THE TRANSMISSION OF VIBRATION. 3. FLEXIBLE CONNECTIONS ARE TO BE RATED FOR THE OPERATING PRESSURE OF THE SYSTEM. 4. FINAL CONNECTIONS TO EXHAUST FANS) SHALL BE WITH A HEAVY AIRTIGHT ACID RESISTANT FIRE RETARDANT FIBERGLASSED NEOPRENE CONNECTOR, A MINIMUM OF SIX (6) INCHES IN LENGTH. THE CONNECTOR SHALL BE FASTENED TO EQUIPMENT AND DUCT WITH TWO FLEXIBLE REMOVABLE BRASS STRAPS OR ALTERNATE APPROVES] METHOD. J. THERMOSTATS A. MOUNT THERMOSTATS X-0" (ADA COMPLYING), THERMOSTAT SENSORS V-0" ABOVE FINISHED FLOORS AHD SET DATE, TIME, TEMPERATURE, ETC TURN OVER OPERATING INSTRUCTIONS TO TENANT REPRESENTATIVE B. THERMOSTATS SHALL BE PROVIDED WITH KEY OPERATED SECURITY COVERS AND DESCRIPTIVE NAMEPLATES. K. FIRE DAMPERS, SMOKE DAMPERS 1. THE MECHANICAL CONTRACTOR SHALL PROVIDE ALL FIRE DAMPERS AS REQUIRED BY LANDLORD AND / OR TENANT CRITERIA AND / OR CODES HAVING JURISDICTION. ALL FIRE DAMPERS SHALL COMPLY WITH THE REQUIREMENTS OF THE BOARD OF FIRE WDERWRITERS, THE LOCAL FIRE MARSHAL AND SHALL BE LABELED AND APPROVED BY UNDERWRITERS LABORATORIES. 2. FIRE DAMPERS SHALL HAVE THE BLADES OUT OF THE AIR STREAM AND A 165 DEGREE F FUSIBLE UNK. 3. PROVIDE ALL NECESSARY FRAMING AND SLEEVES FOR DAMPER MOUNTING PER UL AND CODE REQUIREMETTS. 4. PROVIDE DUCT ACCESS DOORS IN AN ACCESSIBLE LOCATION FOR ALL FIRE DAMPERS. DOOR IS TO BE 20 CAUGE GALVANIZED DOOR WITH QUICK -OPENING LATCH AND PIANO HINGE 5. WHERE REQUIRED BY LOCAL CODES, LANDLORD AND IF INDICATED ON DRAWINGS, PROVIDE UL555S SMOCE DAMPER WITH FIRE/HEAT/SMOKE SENSOR, REVERSIBLE MOTOR AND INTERLOCK WITH FIRE ALARM SYSTEM. 1, FLEXIBLE DUCT FOR CONNECTIONS SHALL BE A FACTORY FABRICATED ASSEMBLY CONSISTING OF AN INNEL SLEEVE, INSULATION AND AN OUTER MOISTURE BARRIER. THE INNER SLEEVE SHALL BE CONSTRUCTED OF A CONTINUOUS VINYL COATED SPRING PEEL WIRE HELIX FUSED TO A CONTINUOUS LAYER OF FIBERGLASS IMPREGNATED AND COATED VINYL A 1 1 /4" THICK LAYER OF INSULATING BLANKET OF FIBERGLASS WOOL SHALL ENCASE THE INNER SLEEVE AND BE SHEATHED WITH AN OUTER MOISTURE BARRIER OF A BIDIRECTIONAL REINFORCED METAJZED VAPOR BARRIER. THE FLEXIBLE DUCT SHALL BE RATED FOR A MAXIMUM WORKING VELOCITY OF 6000 FPM AND SHALL BE LISTED BY THE UNDERWIITERS LABORATORIES UNDER THEIR UL -181 STANDARDS AS A CLASS 1 DUCT AND SHALL COMPLY WITH NFPA STANDARD - 90A. THE FLEXIBLE DUCT SHAII BE THERMAFLEX M -KC OR APPROVED EQUIVALENT. FLEXIBLE DUCT SHALL ROUTE FROM SHEET METAL DUCTWORK TO CEILING DIFFUSERS ONLY. THEIE SHALL BE NO EXPOSED FLEXIBLE DUCT. 2. FLEXIBLE AIR DUCT MAY ONLY BE USED IN VERTICAL APPLICATIONS WiTH PRIOR APPROVAL FROM THE TENANT'S CONSTRUCTION MANAGER. 3. FLEXIBLE DUCT SHALL NOT EXTEND OVER 5 FEET IN LENGTH AT ANY ONE LOCATION. M. SUPPLY AND RETURN AIR TAKEOFF FITTINGS A. RECTANGULAR DUCT 1. PROVIDE 45 DEGREE RECTANGULAR TAKEOFFS FROM MAIN DUCTWORK TO RECTANGULAR BRANCHES. B. SPIRAL DUCT 1. PROVIDE SADDLE OR DIRECT CONNECTION OF A BRANCH DUCT INTO A LARGER DUCT. THE DIAMETER OF THE BRANCH SHALL NOT EXCEED TWO THIRDS OF THE DIAMETER OF THE MAIN. PROTRUSIONS INTO THE MAIN ARE NOT ALLOWED. N. DAMPERS 1. PROVIDE MANUAL LOCKING QUADRANT VOLUME CONTROL DAMPERS WITH HANDLE OPERATORS IN EACH BRANCH DUCT AND AS SHOWN ON PLANS TO FACILITATE AIR BALANCING. 2. WHERE ACCESS TO BALANCING DAMPER IS RESTRICTED OR IN AREAS WITH SHEET ROCK CEILINGS, YOUNG REGULATORS SHALL BE USED. 3. ALL RECTANGULAR DAMPERS IN OUTSIDE AIR AND RELIEF AIR DUCTS ARE TO BE OPPOSED BLADE TYPE ALL (ECTANGULAR DAMPERS IN RETURN AIR DUCTS TO BE PARALLEL BLADE TYPE. ALL OUTSIDE AIR DUCT DAMPERS MUST ALSO BE OF THE LOW LEAKAGE TYPE 4. ALL MOTORIZED DAMPERS NOT FURNISHED WITH EQUIPMENT ARE TO BE HONEYWELL DAMPERS. 0. DIFFUSERS, GRILLES AND REGISTERS 1. PROVIDE DIFFUSERS, GRILLES AND REGISTERS AS SCHEDULED. DEVICES TO BE COMPLETE WITH FRAMES AND ALL ACCESSORIES. ALL DIFFUSERS, GRILLES AND REGISTERS IN SHEET ROCK CEILINGS TO BE PROVIDED WITH PLASTER FRAMES. FINISH TO BE COORDINATED WITH INTERIOR FINISHES. 2. INSTALL ALL AIR DEVICES AS LOCATED ON THE ARCHITECTURAL REFLECTED CEILING PLAN OR THE MECHANICAL PLAN. P. DUCTWORK INSULATION 1. ALL NEW SUPPLY AND RETURN AIR DUCTWORK WITHIN IV OF HVAC UNIT SHALL BE ACOUSTICALLY LINED.DUCT SIZES SHOWN ON THE DRAWING ARE INTERNAL FREE AREA SIZES. INTERNAL LINER SHALL BE 1 1 /2" THICK DUCT LINER EQUIVALENT TO JOHNS MANVILLE'PERMACOTE LINACOUSTIC" ("R VALUE" = 6.3) AND SHALL BE APPLIED TO THE DUCTWORK WITH FIRE RESISTIVE ADHESIVES AND CADMIUM 01 COPPER PLATED MECHANICAL FASTENERS. 2. ALL OUTSIDE AIR AND UNEXPOSED DUCTWORK WITHIN BUILDING, EXCEPT WHERE ACOUSTICALLY LINED, STALL HAVE 2 INCH, FIBERGLASS DUCT WRAP INSULATION WITH FSK FACING EQUIVALENT TO JOHNS MANVILLE'MICROLITE XG TYPE 75' (INSTALLED "R VALUE" = 5.6). 3. LEADING EDGES OF DUCT INSULATION SHALL BE OVERLAPPED BY ADJOINING INSULATION FOR 6" MINIMUM AND THEIN SEALED WITH FOIL VAPOR BARRIER ADHESIVE AND DUCT MASTIC SO THAT NO FIBERGLASS INSULATION IS VISIBLE 4. ALL INSULATION ON EXISTING PIPING OR DUCTS THAT IS WETTED, DAMAGED, DISTURBED OR REMOVED SHALL BE REPLACED. 5. INSTALL INSULATION PRODUCTS IN ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS AND IJ ACCORDANCE WITH RECOGNIZED INDUSTRY PRACTICES. INSULATION MUST COMPLY WITH NFPA 90A. 6. ALL INSULATION SHALL HAVE A FLAME SPREAD RATING OF NOT MORE THAN 25 AND A SMOKE DEVELOPED RATING OF NO HIGHER THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM C 411 OR AS REQUIRED BY LOCAL CODES. 7. EXTERIOR SUPPLY AND RETURN DUCT INSULATION A. SERVICE, RECTANGULAR, SUPPLY -AIR AND RETURN -AIR DUCTS. 1. MATERIAL• INSULATION BOARD, 6 PSF MINIMUM AND PLAIN FACING. 2. THICKNESS: 2 INCHES. 3. NUMBER OF LAYERS: TWO. TOTAL THICKNESS = 4" 4. VAPOR RETARDER REQUIRED: YES. A. INORGANIC GLASS FIBERS PREFORMED AND BONDED BY THERMOSETTING RESIN. MUST COMPLY WITH ASTM C 612, TYPE 1 A AND 1 B, 1. KNAUF INSULATION OR APPROVED EQUIVALENT. A. INSULATION INSTALLED OUTDOORS: FLAME SPREAD RATING OF 25 OR LESS AND SMOKE DEVELOPED RATING OF 50 OR LESS. B. APPLY INSULATION AS FOLLOWS: A. APPLY TWO -LAYER INSULATION WITH JOINTS TIGHTLY BUTTED AND STAGGERED AT LEAST 3 INCHES. SECURE LAYERS WITH ADHESIVE, MECHANICAL FASTENERS OR BANDING. FASTENERS SHALL BE LOCATED A MAXIMUM OF 3" FROM EACH EDGE AND NO GREATER THAN 12' APART. B. ON EXPOSED APPLICATIONS, FINISH INSULATION WITH A SKIM COAT OF MINERAL -FIBER, HYDRAULIC -SETTING CEMENT TO SURFACE OF INSTALLED INSULATION. WHEN DRY, APPLY FLOOD COAT OF LAGGING ADHESIVE AND PRESS ON ONE LAYER OF GLASS CLOTH OR TAPE OVERLAP EDGES AT LEAST 1 INCH (25 MM). APPLY FINISH COAT OF LAGGING ADHESIVE OVER GLASS CLOTH OR TAPE TITIN THE FINISH COAT TO ACHIEVE SMOOTH FINISH. OUTDOOR JACKET. POLYGUARD PRODUCTS, INC'ALUMAGUARD 60' OR MFM BUILDING PRODUCTS CORP.'FLEXCLAD 400". Q. SYSTEM CLEANOUT 1. UPON COMPLETION OF INSTALLATION, CLEAN ENTIRE SYSTEM BEFORE INSTAWNG AIR OUTLETS. CONTRACTOR TO PROVIDE A CERTIFICATION THAT CLEANING WAS ACCOMPLISHED PRIOR TO PROJECT CLOSEOUT. 2. FILTERS MUST BE IN UNITS AT ANY TIME FANS ARE OPERATED. R. SYSTEM TESTING. ADJUSTING AND BALANCING 1. TESTING, ADJUSTING AND BALANCING OF ALL WORK SHALL BE COMPLETED BY AN INDEPENDENT CONTRACTOR WHO IS CURRENTLY LICENSED BY THE ASSOCIATED AIR BALANCING COUNCIL (AABC) OR NATIONAL ENVIRONMENTAL BALANCING BUREAU (NEBB). NO OTHER BALANCE REPORTS WILL BE REVIEWED OR ACCEPTED. ALL BALANCING WORK MUST BE COMPLETE AND DONE IN ACCORDANCE WITH TEE MOST RECENT STANDARDS OF THEIR SOCIETY. PAYMENT OF ALL COSTS FOR TESTING SHALL BE MADE BY THE HVAC CONTRACTOR. 2. THE CONTRACTOR SHALL INSTALL NEW FILTERS IN ALL UNITS PRIOR TO THE AIR BALANCING. THE COMPLETE AIR BALANCE SHALL TAKE PLACE WITH OUTSIDE AIR DAMPERS IN MINIMUM POSITION. M TED N THE DRAWIN S. ANY R UIRED CHANGES IN 3. BALANCE AIR AND WATER QUANTITIES TO WITHIN PLUS OR THUS 5 PERCENT OF THAT INDICA 0 G EQ SHEAVES, BELTS, PULLEYS OR THE ADDITION OF DAMPERS REQUIRED TO ACHIEVE SPECIFIED FLOW RATES SHALL BE PROVIDED BY THE HVAC CONTRACTOR WITH NO ADDITIONAL COST TO THE TENANT. 4. THE BALANCE REPORT SHALL INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION: A) AABC OR NEBB CERTIFICATION NUMBER AND SIGNATURE OF BALANCING CONTRACTOR. B) INSTRUMENTATION UST WITH LAST CALIBRATION DATES. C) MAKE AND MODEL NUMBERS OF ALL HVAC EQUIPMENT TESTED. D) AIR CFM AND STATIC PRESSURE READINGS (DISCHARGE AND SUCTION) AS MEASURED BY PITOT TUBE DUCT TRAVERSE AT THE UNITS. E) MOTOR NAMEPLATE DATA WITH ACTUAL FIELD VOLTAGE AND AMPERAGE READINGS FOR EACH LEG. 0 MOTOR AND FAN RPM, SHEAVE SIZES AND BELT SIZES AND LENGTHS. G) OUTSIDE, RETURN, MIXED AND SUPPLY AIR TEMPERATURES AT FULL COOLING. H) WATER BALANCE DATA INCLUDING GPM WITH INLET AND OUTLET TEMPERATURE AND PRESSURE READINGS. 1) MAKE AND MODEL NUMBERS OF ALL AIR DISTRIBUTION EQUIPMENT. J) FINAL BALANCED AIR VOLUMES AT ALL OUTLETS (INCLUDING RETURNS WHERE DUCTED). K) INDEXED PLAN WITH DIFFUSER AND RETURN LOCATIONS. 5. ALL CONTROL SEQUENCES SHALL BE TESTED AND OPERATING STATUS RECORDED IN THE REPORT. 6. THREE COPIES OF THE BALANCE REPORT SHALL BE SUBMITTED THROUGH THE GENERAL CONTRACTOR TO THE TENANT'S CONSTRUCTION MANAGER FOR REVIEW AND COMMENT. 7. THE BALANCING CONTRACTOR SHALL PERFORM ALL APPLICABLE TESTING AND BALANCING FUNCTIONS REQUIRED FOR THE SYSTEM DESIGNED IN THESE DRAWINGS. THE BALANCING CONTRACTOR SHALL RECHECK ANY ITEMS THAT THE TENANT DEEMS NECESSARY AT NO ADDITIONAL COST TO THE TENANT. 8. FINAL BALANCE REPORT SHALL BE INCLUDED IN THE OPERATION AND MAINTENANCE MANUAL 1. ASIDE FROM NORMAL INTERIM INSPECTIONS OF WORK IN PLACE, THE TENANT SHALL HAVE THE RiGHT TO HAVE AN INDEPENDENT HVAC CONTRACTOR INSPECT THE FINISHED HVAC INSTALLATION UPON COMPLETION FOR COMPLIANCE WITH THE PLANS, SPECIFICATIONS AND CODES. THE INSTALLING CONTRACTOR WILL BE RESPONSIBLE TO BRING ALL ITEMS REPORTED BY THE INDEPENDENT HVAC CONTRACTOR UP TO PLANS AND SPECIFICATIONS REQUIREMENTS AT NO ADDITIONAL COST TO THE TENANT. T. INDOOR AIR QUAUTY 1. NO ANALYSIS HAS BEEN MADE WITH REGARD TO SOURCES OR POTENTIAL SOURCES OF INDOOR OR OUTDOOR AIR CONTAMINANTS OR LEVELS OF CONTAMINATION. 2. IT IS THE RESPONSIBILITY OF THE GENERAL AND MECHANICAL CONTRACTOR TO INFORM THE TENANT'S REPRESENTATIVE, LANDLORD AND TENANT'S ARCHITECT IF ANY SOURCE OR POTENTIAL SOURCE OF INDOOR AIR CONTAMINATION IS IDENTIFIED. 3. PRIOR TO ENCLOSING SPACES SUCH AS PLUMBING CHASES, AIR SHAFTS AND RETURN AIR PLENUMS CLEAN ALL AREAS THOROUGHLY. THE CONTRACTOR SHALL GUARANTEE THAT THE PLENUM CHAMBER USED FOR RECIRCULATING OF AiR WILL BE OF TIGHT CONSTRUCTION AND THAT ALL SOURCES OF CONTAMINATION FROM TRAPS, SOIL STACKS, DOWNSPOUTS, VENTS, EXHAUST DISCHARGES AND OTHER SOURCES WILL BE ENCLOSED SO THAT NO CONTAMINATED AIR WILL BE RECIRCULATED. 4. PRIOR TO COMMENCING CONSTRUCTION ACTIVITIES SHUT OFF THE HVAC SYSTEM, BLOCK OFF ALL AIR GRILLS, DIFFUSERS AND OTHER OPENINGS OUTSIDE THE IMMEDIATE CONSTRUCTION AREA. OPENINGS TO ADJACENT TENANT SPACES SHALL BE COVERED WITH FILTER MEDIA TO PREVENT DUST AND OTHER AIRBORNE CONTAMINANTS FROM PASSING TO ADJOINING SPACES. 5. CONTRACTOR TO INSTALL TEMPORARY EXHAUST SYSTEM TO VENTILATE CONSTRUCTION SITE AND KEEP SITE UNDER SLIGHT NEGATIVE PRESSURE DURING ALL HOURS OF CONSTRUCTION, EVEN IF AFTER NORMAL BUSINESS HOURS. 6. CONTRACTOR TO INSTALL TEMPORARY BARRIERS TO PROTECT ADJACENT SPACES FROM DUST, PARTICULATES, VAPORS AND NOISE WHERE TEMPORARY BARRIERS ARE INSTALLED ALWAYS MAINTAIN FIRE EXITS AND EXITWAYS. I 1-30-06 PLUMBING SPECIFICATIONS 1. IT IS THE INTENT OF THESE SPECIFICATIONS TO PROVIDE A COMPLETE INSTALLATION FOR FINISHED WORK, TESTED AND READY FOR OPERATION. THE WORK THROUGHOUT SHALL BE EXECUTED IN THE BEST AND MOST THOROUGH MANNER UNDER THE DIRECTION OF AND TO THE SATISFACTION OF THE OWNER. 2. ALL MATERIALS REQUIRED FOR THIS WORK SHALL BE NEW, UNUSED, BEST OF ITS RESPECTIVE KINDS, AND FREE FROM DEFECTS AND OF FIRST CLASS QUALITY. BASIS OF QUALITY SHALL BE LATEST STANDARDS OF ASTM, ANSI FEDERAL SPECIFICATIONS OR OTHER ACCEPTABLE STANDARDS. 3. THE PLUMBING CONTRACTOR SHALL BE RESPONSIBLE FOR THEIR WORK UNTIL ITS COMPLETION AND FINAL ACCEPTANCE AND SHALL REPLACE ANY OF THE SAME WHICH MAY BE DAMAGED, LOST OR STOLEN WITHOUT ADDITIONAL COST TO THE OWNER. 4. THE PLUMBING CONTRACTOR SHALL GUARANTEE ALL WORK PERFORMED AND MATERIALS INSTALLED TO BE FREE FROM INHERENT DEFECTS AND SHALL KEEP IN REPAIR AND REPLACE ANY DEFECTIVE MATERIALS OF WORKMANSHIP, FREE OF COST TO THE TENANT (OWNER) FOR A PERIOD OF ONE (1) YEAR AFTER THE OPENING FOR BUSINESS. 5. ALL WORK SHALL BE DONE ACCORDING TO THE REQUIREMENTS OF ALL APPLICABLE CODES AND LEASE CRITERIA (IF APPLICABLE) AND SHALL RECEIVE THE APPROVAL OF ALL AUTHORITIES HAVING JURISDICTION. PREPARE ALL REQUIRED DOCUMENTS, DRAWINGS AND PERFORM ALL REQUIRED TESTS AND PAY ALL REQUIRED CHARGES TO OBTAIN THESE APPROVALS. 6. CONTRACTOR SHALL BE HELD TO HAVE EXAMINED THE SITE FOR THE WORK BEFORE HAVING SUBMITTED A PROPOSAL NO ADDITIONAL COMPENSATION WILL BE ALLOWED FOR CONDITIONS FOUND DURING THE COURSE OF THE CONTRACT. 7. THIS CONTRACTOR MUST PROVIDE LANDLORD'S CONSTRUCTION REPRESENTATIVE WITH COPIES OF REQUIRED INSURANCE AND COPIES TO BE FURNISHED TO THE OWNER BEFORE COMMENCING WORK. 8. SUBMIT THREE (3) SETS OF SHOP DRAWINGS IDENTIFIED WITH PROJECT NAME OF THE FOLLOWING (1) ELECTRIC HOT WATER HEATER (2) PLUMBING FIXTURES AND TRIM. CONTRACTOR SHALL SUBMIT SHOP DRAWING OF PIPING LAYOUT TO THE OWNER FOR THEIR FILE 9. THE PLUMBING CONTRACTOR IS A SUBCONTRACTOR OF THE TENANT'S GENERAL CONTRACTOR. 10. NOTCHING AND BORING OF STRUCTURAL STEEL MEMBERS IS NOT PERMITTED. WHEN HANGING FROM STRUCTURAL STEEL ONLY HANG FROM TOP FLANGE OF BEAMS AND TOP CHORDS ONLY AT PANEL POINTS OF JOISTS / TRUSSES. I. WORK RESPONSIBILITY 1. FURNISH ALL LABOR, MATERIALS, EQUIPMENT AND CONTRACTORS FOR A COMPLETE, SAFE INSTALLATION OF PLUMBING WORK IN FULL CONFORMITY WITH REQUIREMENTS OF ALL AUTHORITIES HAVING JURISDICTION AS INDICATED ON DRAWINGS AND/OR HEREIN SPECIFIED, INCLUDING IN GENERAL THE FOLLOWING: 2. SANITARY DRAINAGE CONNECTIONS TO PLUMBING FIXTURES AND EQUIPMENT REQUIRING SAME WITH FINAL CONNECTIONS TO EXISTING PREINSTALLED OUTLETS PROVIDED BY PRIOR TENANTS) OR LANDLORD. PLUMBER SHALL VERIFY EXACT LOCATION OF WASTE PIPE OUTLET BEFORE SUBMITTING BID AND NOTIFY THE ARCHITECT OF ANY LOCATION DISCREPANCIES. PLUMBING CONTRACTOR SHALL BE RESPONSIBLE FOR ANY CONCRETE SAWCUTTING REQUIRED TO MAKE THE FINAL CONNECTION TO THE EXISTING WASTE PIPING OR CAPPED OUTLET(S). SAWCUTTiNG, EXCAVATING, BACKFIWNG AND NEW CONCRETE MUST MEET WITH THE LANDLORD'S APPROVAL A. SNAKE SANITARY FOR A DISTANCE OF 100 FEET AND REPORT ANY BLOCKAGE B. TEST WATER PRESSURE TO INSURE MINIMUM OF 30 PSI. 3. COMPLETE VENT SYSTEM, ALL FIXTURES INDIVIDUALLY VENTED WITH FINAL CONNECTION THROUGH ROOF OR TO EXISTING LANDLORD SUPPLIED COMMON VENT. ROOF PENETRATION AND FLASHING TO BE PERFORMED BY LANDLORD'S ROOFER (IF APPLICABLE). COST OF ROOF PENETRATION AND FLASHING TO BE PART OF THIS CONTRACT, UNLESS NOTED OTHERWISE IN BID PROPOSAL (IF APPLICABLE). 4. DOMESTIC WATER SUPPLY SYSTEM INCLUDING CONNECTION TO EXISTING CAPPED OUTLET AND FINAL CONNECTIONS TO PLUMBING FIXTURES AND EQUIPMENT REQUIRING SAME VERIFY EXACT LOCATION AND SIZE BEFORE SUBMITTING BID. 5. INSULATION OF ALL HOT AND COLD WATER PIPING, INCLUDING UNDER LAVATORY A.D.A. PIPE WRAPPINGS. 6. FURNISH AND INSTALL WATER METER (IF APPLICABLE) ACCESSIBLE TO UTILITY COMPANY OR LANDLORD'S REPRESENTATIVE FOR MONITORING WATER, BUT METER SHOULD IN NO WAY BE IN THE PATH OF THE A.DA/CABG-ANSI, 5'-0' CIRCULAR PATTERN. 111. MATERIALS 1. DRAINAGE AND VENT PIPING: EXTRA HEAVY HUB AND SPIGOT CAST IRON SOIL WITH RUBBER GASKETS CONFORMING TO ASTM C564. NO -HUB CAST IRON TO HAVE HEAVY DUTY, TYPE 304 STAINLESS STEEL COUPLINGS CONFORMING TO ASTM A 666, TYPE 304 STAINLESS STEEL SHIELD, TYPE 304 STAINLESS STEEL BANDS AND SLEEVE: NPS 1 1/2" TO NPS 4": 3' WIDE SHIELD WITH 4 BANDS; NPS 5" TO NPS 10": 4" WIDE BAND WITH 6 BANDS. 2. WATER PIPING BELOW SLAB: TYPE K HARD COPPER TUBING, WITH CAST BRONZE OR WROUGHT COPPER SOLDER JOINT FITTINGS USING 95-5 SOLDER. WATER PIPING ABOVE SLAB: TYPE L COPPER TUBING USING SILVER SOLDER. 3. WATER HAMMER ARRESTORS: PROVIDE ON HOT AND COLD WATER BRANCHES TO FIXTURES, J. R. SMITH HYDROTROL MODEL 5020 FOR UP TO 60 FIXTURE UNITS. 4. VALVES: GATE VALVE WATTS SERIES B-3000, CHECK VALVE WATTS SERIES B-5000, BALL VALVE WATTS SERIES B6080 OR 86081 FULL PORT. ALL VALVES 1 /2' TO 2" BRONZE BODY. 5. PRESSURE AND TEMPERATURE RELIEF VALVE: WATTS REGULATING CO. MODEL l OL 6. PRESSURE REDUCING VALVE WATTS SERIES 25AUB BRONZE BODY WITH INTEGRAL S/S STRAINER, SEALED CAGE FOR 1 /2' TO 2 1 /2' DIA. TO 300 PSI. 7. PRESSURE GAUGE: AMETEK DIV. OF U.S. GAUGE MODEL P5105, 3 1/2' DIAL,1/4" STEM, ALUMINUM CASE, BLACK FINISH. 8. AIR VENT. HOFFMAN #79 WATER MAIN VENT VALVE 9. WATER METER: HERSEY CO. MODEL 400 SERIES IIS. 10. VACUUM RELIEF VALVE WATTS MODEL N36 -Ml BRASS BODY,1/2" NPT LINE SIZE 11. TRAP PRIMER: PPP MODEL P1-500 UP TO FOUR CONNECTIONS. OPTIONAL DISTRIBUTION UNIT REQUIRED FOR 2, 3 AND FOUR DRAIN LINES. 12. MIXING VALVE: WATTS SERIES MMV MIXING VALVE,1/2' LINE SIZE 13. BACKFLOW PREVENTOR. WATTS SERIES 719 DOUBLE CHECK VALVE ASSEMBLY BACKFLOW PREVENTOR. LINE SIZE 1 /2" TO 2" TO MATCH INLET WATER LINE SIZE IV. INSULATION 1. ALL HOT AND COLD WATER PIPING AND FITTINGS SHALL BE INSULATED WITH 1' THICK RIGID FIBERGLASS WITH VAPOR BARRIER UNIVERSAL JACKET PASTED WITH VAPOR BARRIER CEMENT. VAPOR BARRIER NOT REQUIRED ON HOT WATER PIPING. 2. ALL ADA CONFORMING, WHEELCHAIR ACCESSIBLE LAVATORY P -TRAP AND ANGLE VALVE ASSEMBLIES TO BE COVERED WITH THE MOLDED, ANTIMICROBIAL TRUBRO, INC "LAV -GUARD' UNDERSINK PROTECTIVE PIPE COVER MODEL #103. V. SPECIFIC PLUMBING SPECIFICATIONS 1. INSTALL NEW ONLY IF EXISTING DOES NOT MEET CURRENT ADA/CABG-ANSI (AS APPLICABLE) STANDARDS, OR IS DAMAGED, NOT IN WORKING ORDER OR NOT EXISTING AS APPLICABLE 2. IT IS THIS CONTRACTOR'S RESPONSIBILITY TO SUPPLY HANDICAPPED TOILET FIXTURES, IF REQUIRED BY CODE OR NOTED ON THE DRAWINGS, UTILIZING THE SPECIFICATION ABOVE AS A STANDARD AND MEETING CODE REQUIREMENTS. SPACING OF FIXTURES TO BE COORDINATED WITH THE GENERAL CONTRACTOR AS WELL AS THE PLUMBING INSPECTOR'S REQUIREMENTS. 3. PVC PIPING IS NOT PERMITTED ABOVE GRADE 4. INSTALL PLUMBING VENTS MINIMUM 10'-0" FROM BUILDING AIR INTAKES. 5. COSTS FOR WORKING BELOW TENANT'S SLAB IN ANOTHER TENANTS SPACE 6. INSTALLATION OF FLOOR DRAIN, BACKFLOW PREVENTER (IF REQ. BY CODE) AS PER LANDLORD REQUIREMENT AND CLEANOUT PER LOCAL CODE COORDINATE ALL LOCATIONS WITH OPERATIONS MANAGER. 7. COMPLETE NATURAL GAS PIPING SYSTEMS (AS APPLICABLE, REFER TO PLANS) 11. GENERAL ITEMS i. SLEEVES: PROVIDE #22 GAUGE GALVANIZED IRON PIPE SLEEVES FOR PIPING THROUGH WALLS AND FLOOR, PACK WITH NON -ASBESTOS ROPE AND FILL WiTH EXPANDO NON -SHRINKING CEMENT. 2. ESCUTCHEONS: PROVIDE EXPOSED PIPING, BOTH BARE AND COVERED, WITH CP CAST BRASS ESCUTCHEONS WHERE PASSING THROUGH FLOORS, CEILINGS, WALLS OR PARTITIONS. 3. HANGERS AND SUPPORTS: SUPPORT HORIZONTAL DRAINAGE PIPING AT LEAST EVERY 5 FEET OR AT EVERY HUB COPPER BI TU NG EVERY 7 FEET AND STEEL PIPE EVERY 10 FEET WITH "CLEVIS' HANGERS AND INSULATION PROTECTION SHIELDS. PIPING SHALL NOT BE SUPPORTED FROM BRIDGING OR OTHER PIPING. ONLY SUPPORT FROM TOP FLANGES OF BEAMS AND TOP CHORDS AT PANELS OF 101ST AND TRUSSES. PROVIDE SWAY AND SEISMIC BRACING WHERE REQUIRED BY CODES. 4. TEST. TEST PIPING AND PROVE TIGHT FOR AT LEAST TWO HOURS IN ACCORDANCE WITH REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION AND/OR AS SPECIFIED. TEST SHALL BE PERFORMED IN THE PRESENCE OF OWNER'S REPRESENTATIVE AND LOCAL INSPECTOR. TEST SHALL BE REPEATED IF NECESSARY UNTIL FINAL APPROVAL OF SYSTEM IS OBTAINED. A. TEST DRAINAGE AND VENT PIPING BY FILLING WITH WATER TO OVERFLOWING AT ROOF, WATER LEVEL TO REMAIN. B. TEST WATER PIPING WITH WATER 1 1 /2 TIMES THE WORKING PRESSURE 5. STERILIZATION OF DOMESTIC WATER SYSTEM: BEFORE BEING PLACED IN SERVICE, ALL WATER LINES SHALL BE CHLORINATED TO THE SATISFACTION OF THE ARCHITECT OR LANDLORD'S REPRESENTATIVE, IN ACCORDANCE WITH ANNA SPECIFICATION C601 -53T. 6. SLOPE WASTE LINES 2 INCHES AND SMALLER NOT LESS THAN 1/4 INCH PER FOOT. SLOPE LARGER MAINS NOT LESS THAN 1/B INCH PER FOOT. 7. INSTALL A CLEANOUT AT BASE OF EACH SOIL STACK, AT EACH CHANGE IN DIRECTION, AT INTERVALS NOT OVER 50 FEET AND ELSEWHERE AS SHOWN ON DRAWINGS OR REQUIRED BY LOCAL CODE CLEANOUTS SHALL NOT BE INSTALLED IN PUBLIC AREAS WITHOUT SPECIFIC PERMISSION BY TENANT'S CONSTRUCTION MANAGER. RECEIVE Cj_r,y L3 r -r t.l K REVIEWED FOR -CODE COi' PLiANCE QLC 1 9 2 �PPRQ'VE® DEC 2 3 2016 PF -6 -du i i City of Tukwila i BUILDING DIVISION f;. ,;, X _ ov M� 0 N CV N N i -4 M C; w W Z -' =V) J Q w u- >- 3 W Ch Q aM LLJ ,o > - VO LLJ N w N Lu � I -- �vi u - >O OJ Ln ~ �Q N COPYRIGHT DISCLAIMER: THIS DOCUMENT IS THE PROPERTY OF EPOCH DESIGN GROUP, COPYRIGHTED AS DATED, ALL RIGHTS RESERVED. AUTHORIZATION FROM EPOCH DESIGN GROUP FOR USE OF THIS Dmme,rr IS NOT TRANSFERABLE THE RECIPIENT OF THIS DOCUMENT IS HEREBY ADVISED THAT R IS RELEASED FOR USE (UNDER THE FOLLOWING TERMS AND CONDITIONS. THE DOCUMENT IS TO BE USED ONLY IN CONJUNCTION WITH THIS PROJECT. REUSE OF ANY PORTION OF THE DOCUMENT IN ANY OTHER CIRCUMSTANCE CONSTITUTES COPYRIGHT INFRINGEMENT. THE DOCUMENT IS FOR DESIGN INTENT AND INFORMATION ONLY, AND DOES NOT CONSTITUTE AS -BUILT CONDITIONS. THE RECIPIENT RETAINS THE OBLIGATION TO VERIFY THE CONDITIONS OF THE SUBJECT PROPERTY AND TO COMPLETELY COORDINATE ALL DIMENSIONS, FABRICATION METHODS, RELATED AND INTEGRATED SYSTEMS, ETC, WITH RESPECT TO ALL ASPECTS OF THE WORK. EPOCH DESIGN GROUP MAKES NO WARRANTY AS TO THE SUITABILITY OF THE DOCUMENT FOR THE RECIPIENT'S INTENDED USE THE RECIPIENT SPECIFICALLY AGREES TO WAIVE AND TO INDEMNIFY AND DEFEND ANY AND ALL CWMS AGAINST EPOCH DESIGN GROUP, RS CONSULTANTS, ANY OF ITS RELATED ENTRIES, VENDORS, OR CONTRACTORS, FOR ANY LOSS INCURRED AS A RESULT OF PROPER OR IMPROPER USE OF THIS DOCUMENT. THE RECIPIENT AGREES TO RETURN OR DESTROY THIS DOCUMENT UPON COMPLETION OR TERMINATION OF WORK PERFORMED IN CONJUNC ION WITH THIS PROJECT. PROFESSIONAL SEAL - L 12/14/16 EXPIRES: 09/21 �1 % PROJECT TITLE: SEATTLE, WA SOUTHCENTER MALL SPACE NO.: 1130 g •' j " No.O Revision Description Date _qHEET TITLE: MECHANICAL SPECIFICATIONS PROJECT NO.: SHEET NUMBER: 16283 DRAWN BY: JWK ISSUE DATE 12/14/16 S2 9 50 O EF ;o ■ ■ EF 2 iS1 10 9 W50S2 m 9 . •. (TYP) ?1 87 OO VAV !2 1 i 0 MECHANICAL PLAN SCALE: 1 /4 if= 1 -0 ff ALL DUCTWORK MUST BE RIGID SHEET METAL OR GALVANIZED STEEL OR ALUMINUM - FIBERGLASS DUCT BOARDS OR OTHER NONMETALLIC MATERIAL IS NOT ALLOWED. ALL SPRINKLERS TO BE RECESSED WITH COVER PLATES FACTORY FINISHED TO SAME COLOR AS SURROUNDING. NOTE: BEFORE ANY MALL TENANT SPACE IMPROVEMENTS OR ALTERATIONS ARE TO BEGIN, WHERE PLENUM CEILINGS ARE REMOVED, ALTERED OR RETURN AIR CEILING GRILLES ARE OPEN/EXPOSED TO CONSTRUCTION DUST CONTAMINATION, A"PLENUM PROTECTION PLAN" SHALL BE REQUIRED TO SHOW PROCEDURES AND METHODS FOR PROTECTING AND SEALING THE RETURN AIR PLENUMS OF ANY CONTAMINATION FROM CONSTRUCTION DUST AND COMBUSTIBLES PRIOR TO AND DURING CONSTRUCTION WORK. NO INSPECTIONS SHALL BE PERFORMED UNTIL MITIGATION PROCEDURES ARE MADE TO PROTECT ANY SHARED CEILING PLENUMS. NOTE: EXISTING CONDITIONS WERE TAKEN FROM SITE VISITS AND MAY NOT REFLECT EXACT "AS -BUILT" CONDITIONS. FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO SUBMITTING FINAL BIDS. CONTRACTOR SHALL CAREFULLY COORDINATE NEW WORK AND DEMOLITION WITH ALL OTHER DISCIPLINES AND EXISTING CONDITIONS. ALL HVAC EQUIPMENT AND CONTROLS MUST BE LOCATED FOR PROPER ACCESS FOR MAINTENANCE AND REPAIR, WHETHER INSTALLATION IS EXISTING OR NEW. EXISTING EQUIPMENT AND CONTROLS SHALL BE RELOCATED BY THIS CONTRACTOR IF REQUIRED 7,,`17 2 t. tIY : 11iI 3rD FOR; Q NlectlanicW M*_Tectracal t Ging Gas Piping City of Tukwila BUILDING DIVISION i KEYNOTE SYMBOLS: (OX -DO) 1. RELOCATE EXISTING THERMOSTAT TO LOCATION SPECIFIED ON PLANS. REPLACE THERMOSTAT IF REQUIRED BY MALL 2. EXISTING VAV TO REMAIN. FIELD VERIFY EXACT LOCATION. CLEAN AND REFURBISH TO LIKE NEW CONDITION. BALANCE SUPPLY AIR TO 2100 CFM. REPLACE CONTROLS IF REQUIRED BY MALL 3. FURNISH AND INSTALL GALVANIZED STEEL DUCTWORK, SIZES AS NOTED ON DRAWINGS. DUCTWORK SIZES ARE CLEAR INSIDE DIMENSIONS. REFER TO SPECIFICATIONS FOR INSULATION REQUIREMENTS. 4. SPRINKLER SYSTEM SHALL BE MODIFIED AS REQUIRED TO SERVE THE NEW LAYOUT SHOWN ON THE DRAWING. NOTIFY THE MALL MANAGER 72 HOURS BEFORE SPRINKLER SHUTDOWN IS REQUIRED AND PAY ALL MALL CHARGES FOR SPRINKLER SHUTDOWN. 5. CONNECT TO LANDLORD'S EXISTING SPRINKLER LINE AND TO CONNECTIONS THAT EXIST IN THE SPACE TO ACCOMMODATE THE NEW SPRINKLER LOCATIONS. REUSE SPRINKLER HEAD LOCATIONS WHERE POSSIBLE. 6. CONNECT DIFFUSERS TO NEAREST EXISTING BRANCH DUCT OR TRUNK DUCT OF ADEQUATE SIZE. REUSE EXISTING OPENINGS IN TRUNK DUCT WHERE POSSIBLE. 7. EXISTING DUCTWORK TO REMAIN. CLEAN AND REFURBISH TO LIKE NEW CONDITION. FIELD VERIFY EXACT LOCATION. 8. DUCTWORK AND PIPING SHALL NOT BE ROUTED OVER ELECTRICAL PANELS, DISCONNECTS, TRANSFORMERS, OR OTHER ELECTRICAL EQUIPMENT. VERIFY LOCATION OF ALL ELECTRICAL EQUIPMENT BEFORE INSTALLATION OF HVAC DUCTWORK AND PIPING. 9. REPLACE EXHAUST FANS IN EXISTING LOCATION. CONNECT TO EXISTING EXHAUST DUCT IN SPACE. 20 MECHANICAL KEYNOTES SCALE: N/A FRE COPY Permit No,� Flare is subject to errors and tH proval Of .onsiruciion documents doss; mc1 t3 violation of any adopted code or ordinance. deo-:,:Yi of approved Field Copy and conditions is acknov1,Jla�jx� ,: Data: City of Tukwila BUILDING DIVISION REVISIONS - No charges shat► be made to the ;Cnno of 11 r� kArithout prior approval -)f 1, ')a Bt Wding Division. re ,. url0 mL:y {i1e,ude additional e a neer plan . UF-� _., clonal plan reviev, fe KEYNOTE SYMBOLS: (D'o,o) 1. EXISTING PLUMBING FIXTURES TO REMAIN. CLEAN AND REFURBISH TO LIKE NEW CONDITION. A. ALL PIPING AND HEADS SHALL BE INSTALLED PER LATEST EDITION OF NFPA 13. HEAD SPACING SHALL BE BASED UPON THE ORDINARY HAZARD SCHEDULE. ALL SPRINKLER PIPING SHALL BE SCHEDULE 40 BLACK IRON. SCHEDULE 10 PIPING IS PERMISSIBLE IF ACCEPTABLE TO THE LANDLORD. HYDRAULICALLY PLUMBING KEYNOTES CALCULATE SYSTEM AND SUBMIT COPIES OF THE CALCULATIONS TO THE AUTHORITY HAVING 13 JURISDICTION AND THE LANDLORD. SCALE: N/A B. PREPARE SHOP DRAWINGS FOR SUBMITTAL TO THE AUTHORITY HAVING JURISDICTION AND THE -� VOLUME DAMPER FD : LANDLORD BEFORE FABRICATION. ® CEILING SUPPLY AIR DIFFUSER C. TWO COPIES OF THE APPROVED SHOP DRAWINGS SHALL BE SUBMITTED TO THE OWNER AND THE SIDEWALL AIR DIFFUSER OR GRILLE NEW DUCTWORK REVIEW=GGA LANDLORD PRIOR TO ISSUANCE OF A CERTIFICATE OF OCCUPANCY. EXISTING DUCTWORK API�� - CD - D. PROVIDE FOR INSPECTION TESTING AND APPROVAL BY THE AUTHORITY HAVING JURISDICTION AND THE SD EXISTING SMOKE DETECTOR D STATE INSPECTION BUREAU AS REQUIRED. O PIPE TURNING UP E. PROVIDE SIGNED CERTIFICATE OF COMPLETION COPIES TO BE GIVEN TO OWNER'S REPRESENTATIVE, BALL VALVE e CONNECTION OF NEW TO EXISTING INSURANCE REPRESENTATIVE, AND PROJECT OFFICE. ter- GAS COCK - F. HOLD ALL SPRINKLER LINES AS HIGH AS POSSIBLE TO MAINTAIN 18" CLEARANCE ABOVE STOCK SHELVING. ABOVE FINISHED FLOOR ETR J I� G. SPRINKLER HEADS IN SALES AREA SHALL BE CONCEALED TYPE WITH WHITE COVER PLATES. UPRIGHT AIR DEVICE # S - SUPPLY R - RETURN CFM E - EXHAUST FIRE PROTECTION SYMBOLS LEGEND OE EXISTING SPRINKLER HEAD PENDANT HEADS SHALL BE USED IN ALL AREAS WITHOUT A CEILING. PENDANT HEADS WITH ESCUTCHEON CHROME PENDANT SPRINKLER HEAD O UPRIGHT SPRINKLER HEAD 00 PLATES SHALL BE USED IN ALL STOCKROOM AREAS/RESTROOMS WITH LAY -IN OR GYPSUM BOARD ®I SIDEWALL SPRINKLER HEAD PLUMBING SYMBOLS LEGEND - - - CEILINGS. SPRINKLER HEAD TEMPERATURE RATINGS SHALL BE 165°F IN SALES AND STOCK AREAS AND - - - - HOT WATER i SANITARY DRAIN 212°F IN DISPLAY WINDOWS AND LIGHTING FIXTURE CANOPIES OR AS REQUIRED BY LANDLORD'S SANITARY VENT VTR ! j EO PLUMBING TRAP INSURANCE AGENCY AND LOCAL AUTHORITIES. SPRINKLER HEADS SHALL BE QUICK RESPONSE TYPE. ALL CLEAN OUT / ^' SEMI -RECESSED AND CONCEALED HEADS SHALL BE WHITE H. VISIT THE SITE AND VERIFY ALL EXISTING CONDITIONS WHICH WILL AFFECT THE WORK. PROVIDE ALL 1 REQUIRED PIPING AND OR REVISIONS TO PIPING AS NEEDED FOR A COMPLETE SPRINKLER SYSTEM WHICH IS APPROVED AND ACCEPTED BY LOCAL AUTHORITIES. 1. SPRINKLER SHOP DRAWINGS UNDER SEPARATE COVER. SUPPLY SPRINKLER SHOP DRAWINGS AND APPLY TO BUILDING DEPARTMENT (REQUIRED). J. LANDLORD DESIGNATED CONTRACTOR TO PERFORM ALL SPRINKLER MODIFICATIONS. SYSTEM MODIFICATIONS SHALL BE SCHEDULED IN ADVANCE WITH THE LANDLORD'S FIELD REPRESENTATIVE. THE SPRINKLER SYSTEM SHALL BE FULLY CHARGED AND OPERATIONAL K. ALL FIRE PROTECTION AND SPRINKLER SYSTEM WORK SHALL BE IN ACCORDANCE WITH MALL'S INSURANCE \' AGENCY REQUIREMENTS, NFPA, STATE, COUNTY AND LOCAL FIRE MARSHALL FIRE PROTECTION SPECIFICATIONS I 18 PLUMBING PLAN I 9 SCALE: N/A SCALE: 1/4" = V-0" 1. ALL OF THE MECHANICAL WORK IS NOT NECESSARILY SHOWN OR NOTED ON THESE DRAWINGS. THE CONTRACTORS SHALL VISIT THE JOB SITE AND VERIFY ALL EXISTING CONDITIONS RELATED TO THEIR WORK BEFORE BIDDING. NOTIFY THE OWNER OF ANY DISCREPANCIES. THOSE ITEMS NOT SHOWN OR NOTED BUT WHICH ARE DEEMED NECESSARY FOR REMOVAL OR RELOCATION BY OWNER'S REPRESENTATIVE SHALL BE PART OF THIS CONTRACT. 2. THE SUBMISSION OF PROPOSALS SHALL BE CONSIDERED EVIDENCE THAT THE CONTRACTORS HAVE VISITED THE SITE. NO EXTRA PAYMENTS WILL BE ALLOWED THESE CONTRACTORS CLAIMS FOR EXTRA WORK MADE NECESSARY BY THEIR FAILURE TO VISIT THE SITE. 3. GUARANTEE ALL EQUIPMENT AND MATERIAL INSTALLED UNDER THIS CONTRACT TO BE FREE FROM DEFECTS FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE AND REPAIR OR REPLACE WITHOUT COST TO THE OWNER ANY EQUIPMENT WHICH IS DEFECTIVE, OR IMPROPERLY INSTALLED. IN ADDITION, ASSUME FULL RESPONSIBILITY FOR ANY DAMAGE TO THE BUILDING AND ITS CONTENTS OR OTHER EQUIPMENT CAUSED BY DEFECTS OR IMPROPER INSTALLATION OF EQUIPMENT OR MATERIALS INSTALLED UNDER THIS PORTION OF THE WORK. 4. ALL WORK SHALL BE COMPLETED AND INSTALLED ACCORDING TO STATE AND OR LOCAL CODES, AND ALL LANDLORD CRITERIA. 5. PAY FOR ALL REQUIRED PERMITS AND INSPECTIONS AND PROVIDE A CERTIFICATE OF INSPECTION. 6. REVIEW ALL LANDLORD REQUIREMENTS AND INSTALL ALL MATERIALS AND EQUIPMENT AS DIRECTED BY THE LANDLORD'S REPRESENTATIVE AND AS REQUIRED BY THE LEASE DOCUMENTS. VERIFY THE REQUIREMENTS BEFORE SUBMITTING A BID. 7. VERIFY THE SIZE, LOCATION AND CONDITION OF THE EXISTING DUCTWORK, EQUIPMENT AND CONTROLS THAT ARE TO REMAIN. NOTIFY THE OWNER OF ANY DISCREPANCIES. REPLACE EXISTING COMPONENTS IF INADEQUATE FOR THE NEW REQUIREMENTS OR INOPERABLE COORDINATE REPLACEMENT COMPONENT SPECIFICATIONS WITH THE LANDLORD'S FIELD REPRESENTATIVE. 8. FIVE (5) COPIES OF ALL SHOP OR EQUIPMENT DRAWINGS SHALL BE SUBMITTED TO THE OWNER. THESE DRAWINGS SHALL BE CLEARLY MARKED INDICATING WHICH ITEMS ARE TO BE SUPPLIED AND SHALL STATE CAPACITIES, SIZES, REQUIRED INSPECTION LABELS AND GENERAL DESCRIPTION OF ALL EQUIPMENT AND FIXTURES. 9. ALL AIR INTAKES AND EXHAUSTS NEED TO BE SEPARATED BY A MINIMUM OF I V-0". 10. NO COMPONENTS MAY BE ABANDONED IN PLACE WITHOUT PERMISSION FROM THE OWNER. ALL COMPONENTS THAT ARE NOT REUSED MUST BE REMOVED. 11. VERIFY ALL CLEARANCES AROUND NEW AND EXISTING EQUIPMENT. 12. CAP ALL UNUSED PLUMBING LINES ASSOCIATED WITH LEASED SPACE AS REQUIRED BY LANDLORD AND LOCAL AUTHORITY HAVING JURISDICTION. 13. FURNISH AND INSTALL BACKFLOW PREVENTER IF REQUIRED BY AUTHORITY HAVING JURISDICTION OR LANDLORD. 14. FURNISH AND INSTALL ALL MECHANICAL EQUIPMENT AND OR AIR DEVICES AS SCHEDULED ON THE DRAWINGS. BIDS SHALL BE BASED ON THE EQUIPMENT SPECIFIED AND NO SUBSTITUTIONS WILL BE ACCEPTED. 15. FURNISH AND INSTALL ALL SYSTEMS OF HVAC CONTROL (TO INCLUDE CONTROL WIRING) TO PROVIDE A COMPLETE SYSTEM. 16. FLEX DUCTWORK SHALL NOT EXCEED 3'-0" IN LENGTH. 17. A CERTIFIED AIR BALANCE REPORT IS TO BE PROVIDED TO THE LANDLORD PRIOR TO STORE OPENING. 18. REMOVE ALL EXISTING MECHANICAL EQUIPMENT, DUCTWORK, PLUMBING FIXTURES, PIPING, SYSTEMS, ETC., NOT BEING REUSED. DO NOT ABANDON. 19. THE G.C. SHALL HAVE EXISTING SANITARY WASTE LINE INSPECTED BY CAMERA, TO LEASE LINE, PRIOR TO COMMENCING NEW WORK. RECORDING OF INSPECTION SHALL BE FURNISHED TO OWNER ALONG WITH ANY FINDINGS ADVISING REPAIR OR CLEARANCE OF ANY OBSERVED OBSTRUCTIONS OF THE EXISTING PIPE P-RIIORI TO ROUGH -IN INSPECTION. e v\ = 20(Y 1 /Lt C- 4'"d 6" f rt(, Sti( C �ti ai 5 MECHANICAL SYMBOLS LEGEND O/O THERMOSTAT / HUMIDISTAT -� VOLUME DAMPER FD : FIRE DAMPER ® CEILING SUPPLY AIR DIFFUSER CEILING RETURN AIR GRILLE SIDEWALL AIR DIFFUSER OR GRILLE NEW DUCTWORK REVIEW=GGA EXISTING DUCTWORK API�� - CD - CONDENSATE DRAIN SD EXISTING SMOKE DETECTOR D PIPE TURNING DOWN O PIPE TURNING UP ef Ell III Uhl BALL VALVE e CONNECTION OF NEW TO EXISTING CHECK VALVE ter- GAS COCK - STRAINER AFF ABOVE FINISHED FLOOR ETR EXISTING TO REMAIN AIR DEVICE # S - SUPPLY R - RETURN CFM E - EXHAUST FIRE PROTECTION SYMBOLS LEGEND OE EXISTING SPRINKLER HEAD CHROME PENDANT SPRINKLER HEAD O UPRIGHT SPRINKLER HEAD 00 CONCEALED SPRINKLER HEAD CI ®I SIDEWALL SPRINKLER HEAD PLUMBING SYMBOLS LEGEND - - - COLD WATER - - - - HOT WATER SANITARY DRAIN ----- SANITARY VENT VTR VENT THROUGH ROOF EO PLUMBING TRAP CO CLEAN OUT 171 GENERAL NOTES 116 LEGEND SCALE: N/A I SCALE: N/A &Vm*k 011 W M M r- O f\ C\ Z L0 U Ou CL W W LQ H • x U Q tY 04 M Q W M > '° ix v0 Vw V,)w N vi Lij >O 0 �Ln a 1 M. E. P. Engineer: ACERTUV CONSULTING GROUP, LLC 14817 West 95th Street ♦ Lenexa. Kansas 66215 IF 913 3715150 ♦ F 913 322 5155 www.AcertusGroup.corn .D FOR IPLIANCE )VIED 20161 LA ukwila DIVISION COPYRIGHT DISCLAIMER: THIS DOCUMENT IS THE PROPERTY OF EPOCH DESIGN GROUP, COPYRIGHTED AS DATED, ALL RIGHTS RESERVED. AUTHORIZATION FROM EPOCH DESIGN GROUP FOR USE OF THIS DOCUMENT Is NOT TRANSFERABLE THE REUPIENT OF THIS DOCUMENT IS HEREBY ADVISED THAT IT IS RELEASED FOR USE UNDER THE FOLLOWING TERMS AND CONDITIONS THE DOCUMENT IS TO BE USED ONLY IN CONJUNCTION WITH THIS PROJECT. REUSE OF ANY PORTION OF THE DOCUMENT IN ANY OTHER CIRCUMSTANCE CONSIT UTES COPYRIGHT INFRINGEMENT. THE DOCUMENT IS FOR DESIGN INTENT AND INFORMATION ONLY, AND DOES NOT CONSTITUTE AS-BLnT CONDITIONS THE RECIPIENT RETAINS THE OBLIGATION TO VERIFY THE CONDITIONS OF THE SUBJECT PROPERTY AND TO COMPLETELY COORDINATE ALL DUIENSIONS, FABRICATION METHODS, RELATED AND INTEGRATED SYSTEMS, ETC. WITH RESPECT TO ALL ASPECTS OF THE WORK. EPOCH DESIGN GROUP MAKES NO WARRANTY AS TO THE SUITABILITY OF THE DOCUMENT FOR THE RECIPIENT'S INTENDED USE THE RECIPIENT SPECIFICALLY AGREES TO WAIVE AND TO INDEMNIFY AND DEFEND ANY AND ALL CLAIMS AGAINST EPOCH DESIGN GROUP, ITS CONSULTANTS, ANY OF ITS RELATED ENTRIES, VENDORS, OR CONTRACTORS, FOR ANY LOSS INCURRED AS A RESULT OF PROPER OR IMPROPER USE OF THIS DOCUMENT. THE RECIPIENT AGREES TO RETURN OR DESTROY THIS DOCUMENT UPON COMPLETION OR TERMINATION OF WORK PERFORMED IN CONJUNCTION WITH THIS PROJECT. PROFESSIONAL SEAL: t PtitiA N� OV WA f - - 12/14/16 EXPIRES: 09/21/17 PROJECT TITLE: SEATTLE, WA SOUTHCENTER MALL SPACE NO.: 1130 11, oft�ffl - , " � ffl " A/ RECEIVED V OF 1 Ul(\ ILA DEC 19 2011 No.,L Revision Description Dote i iUi I'." i, t: i� T R SHEET TITLE: MECHANICAL FLOOR PLAN PROJECT NO.: SHEET NUMBER: 16283 DRAWN BY: JWK ISSUE DATE: 1*0 12/14/16 COPYRIGHT DISCLAIMER: THIS DOCUMENT IS THE PROPERTY OF EPOCH DESIGN GROUP, COPYRIGHTED AS DATED, ALL RIGHTS RESERVED. AUTHORIZATION FROM EPOCH DESIGN GROUP FOR USE OF THIS DOCUMENT IS NOT TRANSFERABM THE RECIPIENT OF THIS DOCUMENT IS HEREBY ADVISED THAT IT IS RELEASED FOR USE UNDER THE FOLLOWING TERMS AND CONDITIONS THE DOCUMENT IS TO BE USED ONLY IN CONJUNCTION WITH 71,1IS PROJECT. REUSE OF ANY PORTION OF THE DOCUMENT IN ANY OTHER CIRCUMSTANCE CONSTITUTES COPYRIGHT INFRINGEMENT. THE DOCUMENT IS FOR DESIGN INTENT AND INFORMATION ONLY, AND DOES NOT CONSTITUTE AS -BUILT CONDITIONS THE RECIPIENT RETAINS THE OBLIGATION TO VERIFY THE CONDITIONS OF THE SUBJECT PROPERTY AND TO COMPLETELY COORDINATE ALL DIMENSIONS, FABRICATION METHODS, RELATED AND INTEGRATED SYSTEMS, ETC, WITH RESPECT TO ALL ASPECTS OF THE WORK. EPOCH DESIGN GROUP MAKES NO WARRANTY AS TO THE SUITABILITY OF THE DOCUMENT FOR THE REOPIENVS INTENDED USE THE RECIPIENT SPECIFICALLY AGREES TO WAIVE AND TO INDEMNIFY AND DEPEND ANY AND ALL CLAIMS AGAINST EPOCH DESIGN GROUP, ITS CONSULTANTS, ANY OF ITS RELATED ENTITIES, VENDORS, OR CONTRACTORS, FOR ANY LOSS INCURRED AS A RESULT OF PROPER OR IMPROPER USE OF THIS DOCUMENT. THE RECIPIENT AGREES TO RETURN OR DESTROY THIS DOCUMENT UPON COMPLETION OR TERMINATION OF WORK PERFORMED IN CONJUNCTION WITH THIS PROJECT. PROFESSIONAL SEAL- 12/14/16 EXPIRES: 09/21/1 7 PROJECT TITLE: SEATTLE, QUA SOUTHICENTER MALL SPACE NO.: 1130 ME L L o.A Revision Description Date SHEET TITLE: R MECHANCIAL DETAILS AND SCHEDULES PROJECT NO.: SHEET NUMBER: 16283 DRAWN BY- JWK ISSUE DATE 0 12/14/16 W M Cl) a O M M (~ w Lu J ON W nZ. V w LL f- E-' Q Y N M WM 9 �O V0 \ w N Lu — Lu ® W N >0 O to z COPYRIGHT DISCLAIMER: THIS DOCUMENT IS THE PROPERTY OF EPOCH DESIGN GROUP, COPYRIGHTED AS DATED, ALL RIGHTS RESERVED. AUTHORIZATION FROM EPOCH DESIGN GROUP FOR USE OF THIS DOCUMENT IS NOT TRANSFERABM THE RECIPIENT OF THIS DOCUMENT IS HEREBY ADVISED THAT IT IS RELEASED FOR USE UNDER THE FOLLOWING TERMS AND CONDITIONS THE DOCUMENT IS TO BE USED ONLY IN CONJUNCTION WITH 71,1IS PROJECT. REUSE OF ANY PORTION OF THE DOCUMENT IN ANY OTHER CIRCUMSTANCE CONSTITUTES COPYRIGHT INFRINGEMENT. THE DOCUMENT IS FOR DESIGN INTENT AND INFORMATION ONLY, AND DOES NOT CONSTITUTE AS -BUILT CONDITIONS THE RECIPIENT RETAINS THE OBLIGATION TO VERIFY THE CONDITIONS OF THE SUBJECT PROPERTY AND TO COMPLETELY COORDINATE ALL DIMENSIONS, FABRICATION METHODS, RELATED AND INTEGRATED SYSTEMS, ETC, WITH RESPECT TO ALL ASPECTS OF THE WORK. EPOCH DESIGN GROUP MAKES NO WARRANTY AS TO THE SUITABILITY OF THE DOCUMENT FOR THE REOPIENVS INTENDED USE THE RECIPIENT SPECIFICALLY AGREES TO WAIVE AND TO INDEMNIFY AND DEPEND ANY AND ALL CLAIMS AGAINST EPOCH DESIGN GROUP, ITS CONSULTANTS, ANY OF ITS RELATED ENTITIES, VENDORS, OR CONTRACTORS, FOR ANY LOSS INCURRED AS A RESULT OF PROPER OR IMPROPER USE OF THIS DOCUMENT. THE RECIPIENT AGREES TO RETURN OR DESTROY THIS DOCUMENT UPON COMPLETION OR TERMINATION OF WORK PERFORMED IN CONJUNCTION WITH THIS PROJECT. PROFESSIONAL SEAL- 12/14/16 EXPIRES: 09/21/1 7 PROJECT TITLE: SEATTLE, QUA SOUTHICENTER MALL SPACE NO.: 1130 ME L L o.A Revision Description Date SHEET TITLE: R MECHANCIAL DETAILS AND SCHEDULES PROJECT NO.: SHEET NUMBER: 16283 DRAWN BY- JWK ISSUE DATE 0 12/14/16 A. GENERAL CONDITIONS 1. DRAWINGS AND GENERAL PROVISIONS OF CONTRACT, INCLUDING GENERAL AND SUPPLEMENTARY CONDITIONS AND ALL OTHER SPECIFICATION SECTIONS (IF PROVIDED AS PART OF THE CONTRACT) ARE A PART OF THIS CONTRACT. 2. THE TERM "CONTRACTOR" SHALL MEAN THE "MECHANICAL CONTRACTOR HIRED TO COMPLETE THE WORK OUTLINED IN THESE PLANS AND SPECIFICATIONS" UNLESS OTHERWISE SPECIFIED. 3. THE CONTRACTOR FOR THIS WORK IS REQUIRED TO REVIEW ALL DRAWINGS FOR ALL OTHER TRADES. 4, THE GENERAL CONTRACTOR 15 RESPONSIBLE FOR PROVIDING ITS SUBCONTRACTORS WITH A FULL SET OF BID DOCUMENTS INCLUDING SPECIFICATIONS AND MUST COORDINATE ITS WORK AND INSPECTIONS AND THE WORK AND INSPECTION OF THEIR SUBCONTRACTORS WITH ALL OTHER TRADES ON SITE TO CONFORM NTH THE GENERAL CONTRACTOR'S TIME SCHEDULE 5. BY SUBMITTING A QUOTATION OR PROPOSAL THE MECHANICAL CONTRACTOR EXPRESSLY STATES AND WARRANTS THAT: ALL DRAWINGS AND SPECIFICATIONS HAVE BEEN THOROUGHLY REVIEWED, CONTRACTOR HAS BECOME FAMILIARIZED WITH JOB SITE CONDITIONS AND IS TOTALLY QUALIFIED TO PERFORM ALL OF THE WORK REQUIRED. 6. BEFORE SUBMITTING A FINAL PROPOSAL THE CONTRACTOR SHALL EXAMINE THE SITE OF THE PROPOSED WORK TO DETERMINE THE EXISTING CONDITIONS THAT MAY AFFECT THE PROPOSAL IF DISCREPANCIES ARE NOTED BETWEEN THE DOCUMENTS AND THE EXISTING CONDITIONS THE ARCHITECT SHALL BE NOTIFIED AND THE CONTRACTOR SHALL RECEIVE CLARIFICATION BEFORE SUBMITTING A BID. THE SUBMISSION OF A PROPOSAL SHALL INDICATE THAT ALL CHARGES AND COSTS MADE NECESSARY BY EXISTING CONDITIONS ARE INCLUDED AND THAT THE COMPLETE SYSTEM AS DESCRIBED HEREIN WILL BE FURNISHED AT THE PROPOSED COST. 7. WHEN USED, THE TERM "PROVIDED BY CONTRACTOR" SHALL BE INTERPRETED AS MEANING "FURNISHED AND INSTALLED BY CONTRACTOR" WITH THE EXCEPTION WHERE ITEMS ARE "PROVIDED BY TENANT" SHALL BE INTERPRETED AS MEANING "FURNISHED BY TENANT (INSTALLED BY CONTRACTOR)", EXCEPT WHERE NOTED OTHERWISE B. GENERAL REQUIREMENTS 1. THE CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS, EQUIPMENT, SERVICES, TOOLS, TRANSPORTATION, INCIDENTALS AND DETAILS NECESSARY TO PROVIDE COMPLETE AND FULLY FUNCTIONAL MECHANICAL SYSTEMS AS SHOWN ON THE DRAWINGS, CALLED FOR IN THE SPECIFICATIONS (IF SUPPLIED) AND AS REQUIRED BY JOB CONDITIONS. ALL WORK NOT SPECIFICALLY NOTED AS BEING BY THE LANDLORD SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR. CLOSELY COORDINATE THE ENTIRE INSTALLATION WITH LANDLORD AS REQUIRED. FIELD VERIFY THE EXACT TYPE, SIZE, LOCATION, REQUIREMENTS, ETC OF EXISTING EQUIPMENT, PIPE AND DUCTS SERVING THE TENANT SPACE PRIOR TO SUBMISSION OF BID. 2. THE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO SUPPLEMENT EACH OTHER AND ANY MATERIAL OR LABOR CALLED FOR IN ONE SHALL BE PROVIDED EVEN THOUGH NOT SPECIFICALLY MENTIONED IN BOTH. ANY MATERIAL OR LABOR WHICH IS NEITHER SHOWN ON THE DRAWINGS NOR CALLED FOR IN THE SPECIFICATIONS, BUT WHICH IS NECESSARY TO COMPLETE THE WORK OR WHICH IS USUALLY INCLUDED IN WORK OF SiMILAR CHARACTER, SHALL BE PROVIDED AS PART OF THE CONTRACT. 3. WHERE THE DRAWINGS AND / OR SPECIFICATIONS CALL FOR ITEMS WHICH EXCEED CODES OR THE LANDLORD'S TENANT CRITERIA, THE CONTRACTOR IS STILL RESPONSIBLE FOR PROVIDING THE SYSTEM AS DESIGNED AND DESCRIBED ON THE DRAWINGS, UNLESS SPECIFICALLY NOTED OTHERWISE 4. THE CONTRACTOR SHALL OBTAIN AND COMPLY WITH DETAILED REQUIREMENTS OF LEASE EXTRACTS FROM THE LANDLORD AND TENANT. 5. COORDINATE LOCATIONS OF ALL AIR OUTLETS WITH ALL WALLS, LIGHTS, SPRINKLER HEADS, CEILING TILES AND DECORATIVE CEILING FIXTURES PRIOR TO INSTALLATION. 6. ALL MECHANICAL WORK SHALL BE INSTALLED SO AS TO BE READILY ACCESSIBLE FOR OPERATION, SERVICE, MAINTENANCE AND REPAIR. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING SUFFICIENT ACCESS TO ALL EQUIPMENT FOR SERVICE. 7. THE CONTRACTOR SHALL DO ALL CUTTING, CORE DRILLING, CHASING, OR CHANNELING AND PATCHING REQUIRED FOR ANY WORK UNDER THIS CONTRACT. CUTTING SHALL HAVE PRiOR APPROVAL BY THE TENANT'S CONSTRUCTION MANAGER AND THE LANDLORD OR LANDLORD'S REPRESENTATIVE PATCHING SHALL MATCH FINISH OF SURROUNDING AREA. C CODES 1. ALL WORK SHALL BE PERFORMED IN A NEAT AND PROFESSIONAL MANNER USING GOOD CONSTRUCTION PRACTICES. ALL WORK SHALL CONFORM TO THE LATEST ADOPTED EDITION OF THE LANDLORD'S CRITERIA; PROVINCE, COUNTY AND LOCAL CODES AND ORDINANCES; THE LATEST EDITIONS OF ASHRAE STANDARDS, THE LIFE SAFETY CODE, THE APPLICABLE BUILDING CODE, UNDERWRITERS LABORATORIES, THE NATIONAL ELECTRICAL CODE, NFPA 70, 90A AND 96 AND ALL OTHER APPLICABLE CODES ENFORCED BY AUTHORITIES HAVING JURISDICTION. THE CHANGES REQUIRED BY ANY APPLICABLE CODES SHALL BE INCLUDED IN THE BID. AFTER THE CONTRACT IS ISSUED, NO ADDITIONAL COST DUE TO CODEISSUES SHALL BE REIMBURSED BY THE TENANT TO THE CONTRACTOR. D. LICENSES, PERMITS, INSPECTIONS AND FEES 1. THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL LICENSES, PERMITS, INSPECTIONS AND FEES REQUIRED OR RELATED TO THIS WORK. 2. FURNISH TO THE TENANT'S CONSTRUCTION MANAGER ALL CERTIFICATES OF INSPECTION AND FINAL INSPECTION APPROVAL AT COMPLETION OF PROJECT. E DRAWINGS 1. DRAWINGS (PLANS AND SPECIFICATIONS) ARE DIAGRAMMATIC AND INDICATE THE GENERAL LOCATION AND INTENT OF THE MECHANICAL SYSTEMS. BECAUSE OF THE SCALE OF THE DRAWINGS, IT IS NOT POSSIBLE TO INDICATE ALL DUCT AND PIPE OFFSETS, FITTINGS AND ACCESSORIES THAT MAY BE REQUIRED. THE MECHANICAL CONTRACTOR MUST OBTAIN APPROVED CONSTRUCTION DRAWINGS FROM THE GENERAL CONTRACTOR BEFORE BEGINNING ANY WORK. 2. THE LAYOUT SHOWN ON THE DRAWINGS IS BASED ON A PARTICULAR MAKE OF EQUIPMENT. IF ANOTHER MAKE OF EQUIPMENT IS USED WHICH REQUIRES MODIFICATION OR CHANGE OF ANY DESCRIPTION FROM THE DRAWINGS OR SPECIFICATIONS, THE CONTRACTOR SHALL BE RESPONSIBLE AS PART OF THIS WORK, FOR MAKING ALL SUCH MODIFICATIONS AND CHANGES, INCLUDING THOSE INVOLVING OTHER TRADES WITH THE COST THEREOF INCLUDED IN THE BID. IN SUCH CASE, CONTRACTOR SHALL SUBMIT DRAWINGS AND SPECIFICATIONS PRIOR TO STARTING WORK SHOWING ALL SUCH MODIFICATIONS AND CHANGES. THE PROPOSAL SHALL BE SUBJECT TO THE APPROVAL OF THE TENANTS CONSTRUCTION MANAGER. F. EXISTING LEASE SPACE CONDITIONS 1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF THE DEMOLITION OF EXISTING MECHANICAL WORK IN THE SPACE NOT SHOWN TO BE REUSED IN THE NEW TENANT SPACE 2. THE CONTRACTOR SHALL INCLUDE AND WILL BE HELD RESPONSIBLE FOR, THE REMOVAL OF ALL EXISTING FIRE PROTECTION, PLUMBING FIXTURES, PIPING, HVAC UNITS, REFRIGERANT RECAPTURE, EXHAUST FANS, DUCTWORK, ETC AND ASSOCIATED ROOF CURBS NOT TO BE REUSED ON THIS PROJECT, UNLESS SPECIFICALLY NOTED OTHERWISE CONTRACTOR MUST VERIFY WITH THE LANDLORD ALL PRESUMED ABANDONED EQUIPMENT, PIPES, DUCTWORK AND EQUIPMENT PRIOR TO REMOVAL ROOF CURBS SHALL BE REMOVED AND THE ROOF PATCHED UNLESS NOTED FOR REUSE OR RECONFIGURATION ON PLANS. ROOF PATCHING SHALL BE PERFORMED AT THE CONTRACTOR'S EXPENSE BY A ROOFING CONTRACTOR APPROVED BY THE LANDLORD. ALL EXTRANEOUS ITEMS IN THE SPACE OR ON THE ROOF (ABOVE THIS SPACE) NOT APPLICABLE TO THE NEW WORK OR PART OF THE LANDLORD'S OR ANOTHER TENANT'S ACTIVE SYSTEM MUST BE REMOVED AND ROOF/WALL/FLOOR PATCHED/REPAIRED TO MATCH THE EXISTING STRUCTURE EXISTING ABANDONED PIPES, DUCTS OR EQUIPMENT IN THE FLOOR, EMBEDDED IN CONCRETE OR OTHERWISE INACCESSIBLE ARE TO BE CUT OFF AND SEALED BELOW OR WITHIN FLOOR OR WALL LEVEL WHEN THEY ARE NOT REUSED IN THIS PROJECT. IF REQUIRED BY THE LANDLORD OR CODES, ABANDONED PIPING AND/OR DUCTWORK MUST BE REMOVED TO POINT OF ORIGIN. CONFIRM THE EXTENT OF DEMOLITION PRIOR TO BID AND INCLUDE IN BID PROPOSAL 3. ACTIVE LANDLORD OR OTHER TENANT SERVICES ENCOUNTERED IN WORK SHALL BE PROTECTED AND SUPPORTED. IF EXISTING SERVICES NOT ANTICIPATED REQUIRE RELOCATION, CONTACT THE TENANT'S CONSTRUCTION MANAGER IMMEDIATELY. ALL COSTS FOR REPAIR OF DAMAGES TO ACTIVE LANDLORD OR OTHER TENANT SERVICES DURING CONSTRUCTION SHALL BE PAID FOR BY THE CONTRACTOR CAUSING THE DAMAGE 4. TIE-INS AND MODIFICATIONS TO EXISTING LANDLORD SERVICES MUST BE DONE WITH MINIMUM INTERRUPTION OF LANDLORD OPERATION AND DURING HOURS SPECIFIED BY THE LANDLORD. THE CONTRACTOR IS RESPONSIBLE FOR CONFIRMING EXACT WORKING HOURS OF THIS WORK WITH THE LANDLORD PRIOR TO SUBMITTING THEIR BID. THE CONTRACTOR SHALL INCLUDE IN THEIR BID, ALL PREMIUM TIME REQUIRED TO PERFORM MODIFICATIONS DURING OTHER THAN NORMAL WORKING HOURS. ALL SUCH WORK MUST BE COORDINATED WITH THE LANDLORD. 5. EQUIPMENT AND MATERIALS IN TRANSIT SHALL UTILIZE FREIGHT ELEVATOR OR STAIRS. SAID EQUIPMENT OR MATERIALS SHALL BE DISASSEMBLED AS REQUIRED TO MEET THE RESTRICTIONS IMPOSED BY THE BUILDING OR ITS COMPONENT CONSTRAINTS AND THEN REASSEMBLED IN THE NEW WORK AREA. 6. ALL WORK SHALL BE DONE WITH A MINIMUM OF NOISE AND DISTURBANCE TO BUSINESS ROUTINE ALL WORK SCHEDULES SHALL BE COORDINATED WITH AND APPROVED BY, THE TENANTS CONSTRUCTION MANAGER. 7. SINCE THESE ARE SECURE FLOORS, ALL DELIVERIES, WORKERS, WORK OPERATORS, ETC, REQUIRED BY THE CONTRACTOR FOR WORK PERFORMED IN ANY AREA OR SITE BUILDING SHALL BE IN STRICT CONFORMANCE TO THE RULES AND REGULATIONS OF THE OWNER. 8, CONTRACTOR SHALL PROTECT THEIR WORK AND EQUIPMENT FROM DAMAGE, VANDALS, ETC ANY ITEM THAT IS DAMAGED, VANDALIZED OR STOLEN PRIOR TO ACCEPTANCE OF BUILDING BY OWNER AND ARCHITECT SHALL BE REPLACED BY RESPECTIVE CONTRACTOR AT NO CHARGE TO TENANT. 9. IT IS SPECIFICALLY THE INTENTION OF THIS SPECIFICATION TO HOLD THE CONTRACTOR RESPONSIBLE FOR ALL DAMAGE DONE TO ANY EXISTING FACILITIES, EQUIPMENT, PAINTING, OR ARCHITECTURAL AND STRUCTURAL FEATURES OF THE BUILDING, BY EITHER THEIR OWN WORKMEN OR BY ANY OF THEIR SUBCONTRACTORS. THE CONTRACTOR SHALL REPAIR ANY DAMAGE DONE BY THEIR OWN WORKMEN OR SUBCONTRACTORS AND THE OWNER AT THEIR DISCRETION, MAY WITHHOLD PAYMENTS EQUAL TO THE REASONABLE COST OF THE REPAIRS. 10. THIS CONTRACTOR OR THEIR WORKMEN SHALL NOT BE PERMITTED TO USE ANY PART OF THE EXISTING BUILDING AS A SHOP WITHOUT THE APPROVAL OF THE OWNER AND ARCHITECT. 11. WHERE THE WORK MAKES TEMPORARY SHUTDOWN OF SERVICES UNAVOIDABLE, THEY SHALL BE MADE AT NIGHT OR AT SUCH TIMES AS WILL CAUSE THE LEAST INTERFERENCE WITH THE ESTABLISHED OPERATING ROUTINE 12. THIS CONTRACTOR SHALL ARRANGE THE WORK SO AS TO ASSURE THAT SERVICES WILL BE SHUT DOWN ONLY DURING THE TIME ACTUALLY REQUIRED TO MAKE THE NECESSARY CONNECTION TO THE EXISTING WORK. THIS CONTRACTOR SHALL GIVE AMPLE WRITTEN NOTICE IN ADVANCE TO THE OWNER OF ANY REQUIRED SHUT DOWN. 13. ALL MOTORS, FANS, CONTROLS, FIXTURES, HVAC UNIT, DUCTWORK AND OTHER EQUIPMENT FOR USE IN THIS CONTRACT SHALL BE PROTECTED BY TARPAULIN OR BY BOXING AS SOON AS DELIVERED TO THE SITE AND SHALL BE KEPT CLEAN AND DRY. THE MOTORS, UNITS, FIXTURES, FANS, DUCTWORK AND MOVING PARTS SHALL BE KEPT COVERED SO AS TO ELIMINATE DIRT, DUST AND OTHER MATERIALS ENTERING THE PARTS DURING ERECTION AND CONSTRUCTION WORK ON THE BUILDING. SHOULD IT BE FOUND THAT ANY PARTS ARE DAMAGED DUE TO CARELESSNESS ON THE PART OF THE CONTRACTOR IN NOT PROVIDING PROPER PROTECTION, SUCH PART OR PARTS SHALL BE REPLACED BY THE CONTRACTOR AT THEIR OWN COST AND EXPENSE ALL OPENINGS IN DUCTS, PIPING, CONDUITS, ETC, SHALL BE PROPERLY PROTECTED WITH TEMPORARY CAPS OR PLUGS AT ALL TIMES. G. DISCREPANCIES IN DOCUMENTS ARE DIAGRAMMATIC AND INDICATE THE GENERAL LOCATION AND INTENT OF THE MECHANICAL i912011 H. TRADE NAMES AND MANUFACTURERS 1. WHERE TRADE NAMES AND MANUFACTURERS ARE USED ON THE DRAWINGS OR IN THE SPECIFICATIONS, THE EXACT EQUIPMENT SHALL BE USED AS A MINIMUM STANDARD FOR THE BASE BID. MANUFACTURERS CONSIDERED AS AN EQUIVALENT OR BETTER IN ALL ASPECTS TO THAT SPECIFIED WILL BE SUBJECT TO REVIEW IN WRITING BY THE TENANT'S CONSTRUCTION MANAGER PRIOR TO ACCEPTANCE THE USE OF ANY UNAUTHORIZED EQUIPMENT SHALL BE SUBJECT TO REMOVAL AND REPLACEMENT AT THE CONTRACTOR'S EXPENSE 1. SUBMIT THREE COPIES OF MATERIAL LISTS AND SHOP DRAWINGS FOR ALL EQUIPMENT AND DUCT FABRICATION DRAWINGS TO THE TENANT'S CONSTRUCTION MANAGER FOR REVIEW PRIOR TO ORDERING EQUIPMENT. SUBMISSIONS MUST BE EARLY ENOUGH TO ALLOW THE TENANT'S RE .SUBMITTALS CONSTRUCTION MANAGER EiGHT WORKING DAYS FOR REVIEW WITHOUT CAUSING DELAYS OR CONFLICTS TO THE JOB S PROG SS SHALL BE IN ACCORDANCE WITH THE GENERAL CONDITIONS USING THE MANUFACTURER'S LISTED ON THE DRAWINGS. SHOP DRAWINGS SHALL INCLUDE ALL DATA THAT PERTAINS TO THE REQUIREMENTS SET FORTH ON THE DRAWINGS AND IN THE SPECIFICATIONS. THE SUBMITTAL SHALL INCLUDE BUT NOT BE LIMITED TO CUTS OR CATALOGS INCLUDING DESCRIPTIVE LITERATURE AND CHARACTERISTICS OF EQUIPMENT SHALL SHOW MAJOR DIMENSIONS, ROUGHING -IN DATA, CAPACITY, CURVES, PRESSURE DROPS, CODE COMPLIANCE, MOTOR AND DRIVE DATA AND ELECTRICAL DATA. OBSERVE SPECIAL INSTRUCTIONS WHEN REQUIRED. SUBMITTALS SHALL BEAR THE STAMP OF THE GENERAL AND SUBCONTRACTOR SHOWING THAT HE HAS REVIEWED AND CONFIRMED THAT THEY ARE IN CONFORMANCE WITH THE CONTRACT DOCUMENTS OR INDICATE WHERE EXCEPTIONS TAKE PLACE LACK OF SUCH CONTRACTOR'S REVIEW WILL BE CAUSE FOR REJECTION WITHOUT REVIEW BY TENANT'S CONSTRUCTION MANAGER. ALL SHOP DRAWINGS MUST APPEAR IN THE OPERATION AND MAINTENANCE MANUALS LEFT ON SITE AT JOB COMPLETION. 2. TENANT'S CONSTRUCTION MANAGER'S OR ARCHITECT'S REVIEW OF SHOP DRAWINGS OR SCHEDULES SHALL NOT RELIEVE THE CONTRACTOR FROM RESPONSIBILITY FOR ERRORS, OMISSIONS OR OTHER DEFICIENCIES OR DEVIATIONS IN THE SHOP DRAWINGS FROM THE CONSTRUCTION DOCUMENTS. 3. IT IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR AND / OR THEIR SUBCONTRACTORS TO FURNISH SHOP DRAWINGS AND SUBMITTALS ON ANY AND ALL EQUIPMENT, DUCT, DAMPERS, CONTROLS ETC TO THE ARCHITECT FOR THEIR REVIEW PRIOR TO CONSTRUCTION. 1. RECORD DRAWINGS 1. THE CONTRACTOR SHALL MAINTAIN ONE COPY OF DRAWINGS AND SPECIFICATIONS ON THE JOB SITE TO RECORD DEVIATIONS FROM CONTRACT DRAWINGS, SUCH AS LOCATIONS OF CONCEALED PIPING VALVES AND DUCTS, REVISIONS, ADDENDUM'S AND CHANGE ORDERS, SIGNIFICANT DEVIATIONS MADE NECESSARY BY FIELD CONDITIONS, APPROVED EQUIPMENT SUBSTITUTIONS AND CONTRACTOR'S COORDINATION WITH OTHER TRADES AND EXACT ROUTING OF ALL SANITARY AND DOMESTIC WATER PIPING UNDER FLOOR. 2. AT COMPLETION OF THE PROJECT AND BEFORE FINAL APPROVAL, THE CONTRACTOR SHALL MAKE ANY FINAL CORRECTIONS TO DRAWINGS AND CERTIFY THE ACCURACY OF EACH PRINT BY SIGNATURE THEREON. THE DRAWINGS ARE TO BE TURNED OVER TO THE TENANT. K. GUARANTEE, WARRANTY ON ALL UIPMENT AND MATERIAL 1. THE MECHANICAL CONTRACTOR SHALL INCLUDE IN THE PROPOSAL A ONE YEAR GUARANTEE, WARRANTY EQ INSTALLED OR REFURBISHED, ALL MATERIALS AND WORK UNDER THE CONTRACT AND SHALL MAKE GOOD, REPAIR, OR REPLACE AT THEIR OWN EXPENSE, ANY DEFECTIVE WORK, MATERIAL OR EQUIPMENT WHICH MAY BE DISCOVERED WITHIN A PERIOD OF 12 MONTHS FROM THE DATE OF WRITTEN ACCEPTANCE OF THE INSTALLATION BY THE TENANT'S CONSTRUCTION MANAGER. IN CASE OF REPLACEMENT OR REPAIR OF EQUIPMENT DUE TO FAILURE WITHIN THE GUARANTEE PERIOD, THE GUARANTEE ON THAT PORTION OF WORK SHALL BE EXTENDED FOR A PERIOD OF 12 MONTHS FROM THE DATE OF SUCH REPLACEMENT OR REPAIR. THIS GUARANTEE, WARRANTY IS TO INCLUDE ALL LABOR, MATERIAL, PARTS, ETC NECESSARY TO MAINTAIN THE SYSTEM IN SATISFACTORY OPERATION FOR A PERIOD OF ONE YEAR STARTING FROM THE DATE OF ACCEPTANCE OF THE SYSTEM BY THE TENANT. IT SHALL ALSO INCLUDE ONE SUMMER TO WINTER CHANGEOVER AND ONE WINTER TO SUMMER CHANGEOVER, A NEW SET OF FILTERS AT THE TIME OF STARTUP AND TWELVE (12) MONTHLY FILTER CHANGES DURING THE FIRST YEAR. THE NORMAL PREVENTATIVE MAINTENANCE WORK SHALL BE PERFORMED AT THE TIME OF THE FILTER CHANGES. USE ONLY #40 PLEATED TYPE AIR FILTERS. L OPERATIONS MANUALS 1.ONE COPY OF EACH OPERATION AND MAINTENANCE MANUAL FOR ALL EQUIPMENT FURNISHED ON THE JOB SHALL BE PROVIDED TO THE TENANT BOUND TOGETHER IN A 3 INCH, THREE RING BINDER. THE BINDER SHALL INCLUDE BUT NOT BE LIMITED TO INSTALLATION, MAINTENANCE AND OPERATING INSTRUCTIONS, PAMPHLETS OR BROCHURES, REVIEWED SHOP DRAWINGS AND WARRANTIES OBTAINED FROM EACH MANUFACTURER OF PRINCIPAL ITEMS OF EQUIPMENT. i%#t;ff; 1. THE CONTRACTOR SHALL PROVIDE SLEEVES TO PROTECT EQUIPMENT OR FACILITIES IN THE INSTALLATION. EACH SLEEVE SHALL EXTEND THROUGH ITS RESPECTIVE FLOOR, WALL, OR PARTITION AND SHALL BE CUT FLUSH WITH EACH SURFACE EXCEPT SLEEVES THAT PENETRATE THE FLOOR, WHICH SHALL EXTEND 2 INCHES ABOVE THE FLOOR. 2. ALL SLEEVES AND OPENINGS THROUGH FIRE RATED WALLS AND/OR FLOORS SHALL BE RRE SEALED WITH APPROVED SEALANTS RATED FOR THE APPLICATION SO AS TO MAINTAIN THE FIRE RATING OF THE ASSEMBLY. CONFORM TO THE U.L ASSEMBLY RATING OF THE FLOOR OR WALL 3. SLEEVES IN BEARING AND MASONRY WALLS, FLOORS AND PARTITIONS SHALL BE STANDARD WEIGHT STEEL PIPE FINISHED WITH SMOOTH EDGES. FOR OTHER THAN MASONRY PARTITIONS, THROUGH SUSPENDED CEILINGS OR FOR CONCEALED VERTICAL PIPING, SLEEVES SHALL BE 22 GAUGE GALVANIZED STEEL MINIMUM. 4. DUCT SLEEVES SHALL BE MINIMUM 14 GAUGE STEEL N. HANGERS 1. HANGERS SHALL INCLUDE ALL MISCELLANEOUS STEEL SUCH AS ANGLE IRON, BANDS, C -CLAMPS WITH RETAINING CLIPS, CHANNELS, HANGER RODS, ETC NECESSARY FOR THE INSTALLATION OF WORK. 2. HANGERS SHALL BE FASTENED TO BUILDING STEEL, CONCRETE, OR MASONRY, BUT NOT TO PIPING OR DUCTWORK. DUCTWORK SHALL NOT BE SUPPORTED FROM ROOF DECKING AND/OR BRIDGING, BUT SHALL BE SUSPENDED FROM THE TOP CHORD OF BAR JOISTS, STEEL OR OTHER STRUCTURE DUCTWORK SHALL CLEAR ALL SPRINKLERS AND OTHER OBSTACLES AND SHALL BE HUNG AS HIGH AS POSSIBLE IN WORK AND STORAGE AREAS. WHERE INTERFERENCE'S OCCUR, IN ORDER TO SUPPORT DUCTWORK OR PIPING, THE CONTRACTOR MUST INSTALL TRAPEZE TYPE HANGERS OR SUPPORTS WHICH SHALL BE LOCATED WHERE THEY DO NOT INTERFERE WITH ACCESS TO FIRE DAMPERS, VALVES, ACCESS DOORS AND OTHER EQUIPMENT SERVICE REQUIREMENTS AND/OR OTHER TRADES. HANGER TYPES AND INSTALLATION METHODS ARE SUBJECT TO LANDLORD CRITERIA 3. HANGERS FOR ALL INSULATED PIPING SHALL BE SIZED AND INSTALLED FOR THE OUTER DIAMETER OF INSULATION. INSTALL 6 INCH LONG SPLIT CIRCLE GALVANIZED SADDLE BETWEEN THE HANGER AND THE PIPE INSULATION. 4. HANGERS AND PIPING OF DISSIMILAR METALS SHALL BE DI -ELECTRICALLY SEPARATED FROM ONE ANOTHER. 0. ELECTRIC MOTORS 1. FURNISH, INSTALL AND ALIGN ALL MOTORS REQUIRED FOR THIS EQUIPMENT, UNLESS THEY ARE FACTORY INSTALLED ON THE UNIT. ALL STARTERS AND ASSOCIATED WIRING AND SAFETY SWITCHES FOR SUCH MOTORS SHALL BE FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR. STARTERS SHALL MEET ALL REQUIREMENTS AS DEFINED IN THE ELECTRICAL SPECIFICATIONS. 2. DESIGN, CONSTRUCTION AND PERFORMANCE CHARACTERISTICS OF MOTORS SHALL CONFORM TO ALL APPLICABLE PROVISIONS OF LATEST NEMA, ANSI, ISEE STANDARDS FOR ELECTRICAL EQUIPMENT. ALL MOTORS SHALL BE SUITABLE FOR OPERATION ON VOLTAGE VARIATION OF PLUS OR MINUS 10 PERCENT, 40 DEGREES C AMBIENT TEMPERATURE AND HAVE A SERVICE FACTOR OF NOT LESS THAN 1.15. P. LOW VOLTAGE (24 VOLT) WIRING 1. THE CONTRACTOR IS TO INSTALL ALL LOW VOLTAGE WIRING REQUIRED FOR THEIR EQUIPMENT. THIS WORK INCLUDES ALL TRANSFORMERS AND DEVICES TO MAKE THIS A COMPLETE FUNCTIONAL SYSTEM. 2. ALL WORK IS TO CONFORM TO THE ELECTRICAL SPECIFICATIONS AND THE REQUIREMENTS OF THE AUTHORITIES HAVING JURISDICTION. 3. ANY CONDUIT REQUIRED BY CODE OR THE LANDLORD WILL BE INSTALLED BY THE ELECTRICAL SUBCONTRACTOR. 4. SMOKE DETECTORS AND REMOTE TEST STATION A. IONIZING TYPE ARE TO BE USED ON THE RETURN SIDE OF THE HVAC UNIT AND PHOTO -TYPE ARE TO BE USED ON THE SUPPLY SIDE ON ALL OTHER TYPES OF HVAC UNITS WHERE SMOKE DUCT DETECTORS ARE REQUIRED, USE FIELD INSTALLED IONIZING TYPE IN RETURN DUCTWORK AND PHOTO -TYPE ON THE SUPPLY LOCATED BEFORE THE FIRST TAKEOFF. ONCE ACTIVATED, THE SMOKE DETECTOR WILL SHUT DOWN HVAC UNIT. B. SMOKE DETECTORS SHALL HAVE THEIR OWN REMOTE KEY TEST STATION SYSTEM WITH AUDIBLE AND VISUAL ALARM, SIMPLEX MODEL 4098-9842 OR APPROVED EQUIVALENT. ALARM TO HAVE CANDELA SETTING OF 75 AND A HIGH VOLUME HORN TONE SETTING. MECHANICAL SPECIFICATIONS A. HEATING, VENTILATION AND AIR CONDITIONING 1. BEFORE STARTING WORK, THIS CONTRACTOR SHALL EXAMINE THE ARCHITECTURAL, STRUCTURAL, MECHANICAL AND ELECTRICAL PLANS AND SPECIFICATIONS TO SEQUENCE, COORDINATE AND INTEGRATE THE VARIOUS ELEMENTS OF THE HVAC SYSTEM, MATERIALS AND EQUIPMENT WITH OTHER CONTRACTORS TO AVOID INTERFERENCE'S AND CONFLICTS. B. HVAC EQUIPMENT (REFER TO PLANS FOR SCHEDULE OF EQUIPMENT) 1. PRIMARY HVAC UNITS ARE TO BE AS SCHEDULED. EQUIVALENTS MAY BE SUBSTITUTED WITH WRITTEN APPROVAL ONLY. ALL COMPRESSORS ARE TO INCLUDE A 5 YEAR EXTENDED WARRANTY. 2. ALL EQUIPMENT SHALL BE COMPLETE IN EVERY RESPECT WITH ALL DEVICES, APPURTENANCES AND ACCESSORIES PROVIDED TO MEET THE DESIGN INTENT AND OPERATION OF THE SYSTEMS SHOWN ON THE DRAWINGS AND SPECIFIED. 3. EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. ALL AIR CONDITIONING EQUIPMENT MUST HAVE A CONDENSATE DRAIN AND BE TRAPPED IN ACCORDANCE WITH MANUFACTURER'S DATA. SEE DRAWINGS FOR ADDITIONAL DETAILS. 4. SECONDARY DRAIN PANS ARE REQUIRED TO BE INSTALLED BENEATH ALL INDOOR AIR CONDITIONING EQUIPMENT WITH THE EXCEPTION OF AIR TERMINAL BOXES. SECONDARY PANS ARE TO PROTECT ENTIRE UNIT. PROVIDE CONDENSATE PUMPS AS REQUIRED. CONDENSATE SHALL BE DIRECTED TO MOP SINK, LAVATORY TRAP OR OTHER APPROVED DRAIN. C TOILET EXHAUST FANS 1. WHERE SHOWN ON DRAWINGS PROVIDE A TOILET EXHAUST FAN COMPLETE WITH GRAVITY BACKDRAFT DAMPER. ALL DUCTWORK, ROOF OPENINGS AND CAPS NECESSARY TO PROVIDE A COMPLETE EXHAUST SYSTEM SHALL BE PROVIDED BY THE CONTRACTOR. REFER TO PLANS FOR APPLICABILITY. D. VIBRATION ISOLATION DEVICES 1. VIBRATION ISOLATION DEVICES SHALL BE PROVIDED IN ALL SUPPORTS BETWEEN VIBRATING EQUIPMENT (FANS, ROOFTOP UNITS, WATER SOURCE HEAT PUMPS, AIR HANDLERS, FAN POWERED VAV BOXES, ETC) AND STRUCTURE 2. VIBRATING EQUIPMENT HUNG FROM STRUCTURE SHALL BE ISOLATED WITH RUBBER AND SPRING DEVICES. VIBRATING EQUIPMENT SUPPORTED FROM FLOOR OR DECK SHALL BE ISOLATED WITH HOUSED SPRING MOUNT DEVICES. 3. EXAMINE DEAD LOAD AND OPERATING LOAD CONDITIONS WHEN SELECTING DEVICES. ADJUST FOR PROPER ALIGNMENT AND LOADING. AVOID "GROUNDING" THE ISOLATOR. 4. CHECK HANGER ROD SIZE FOR ALLOWABLE LOADS AT THE ISOLATING DEVICE AND THE UPPER AND LOWER ATTACHMENTS TO STRUCTURES, DUCTS, EQUIPMENT, ETC 5. CONSULT MANUFACTURER FOR APPLICATION DATA. G. CURBS AND STEEL FRAMING FOR SUPPORT 1. THIS CONTRACTOR WILL PROVIDE ALL NECESSARY CURBS AND STEEL FRAMING REQUIRED TO INSTALL ALL HVAC EQUIPMENT. CURBS SHALL BE A MINIMUM OF 14 INCHES HIGH AND OF THE SAME MANUFACTURER AS THE EQUIPMENT SUPPORTED. INSULATE UNDER THE COMPRESSOR SECTION TO PREVENT CONDENSATION. ALL CURBS MUST BE INSTALLED SO THAT THE TOP OF CURBS ARE'DEAD" LEVEL ALL PENETRATIONS OF EXISTING STRUCTURE SHALL BE DONE IN ACCORDANCE WITH THE LANDLORD'S GUIDELINES AT THIS CONTRACTOR'S EXPENSE ALL CONNECTIONS TO ROOFTOP EQUIPMENT SHALL BE INSIDE THE CURB (CONDENSATE DRAIN, POWER WIRING, CONTROL WIRING, ETC). H. METAL DUCTWORK - NO FIBERGLASS DUCT ALLOWED 1. NO DUCTWORK SHALL BE FABRICATED PRIOR TO APPROVAL BY THE TENANT'S CONSTRUCTION MANAGER. DEVIATIONS FROM DESIGN MUST BE APPROVED BY TENANT'S CONSTRUCTION MANAGER PRIOR TO FABRICATION OR INSTALLATION. ALL DUCT MAINS ARE TO BE RECTANGULAR. ALL DUCT BRANCHES TO DIFFUSERS ARE TO BE ROUND SPIRAL DUCT. 2. ALL DUCTWORK SHALL BE PROVIDED AND INSTALLED IN ACCORDANCE WITH SMACNA LOW VELOCITY AND "HVAC DUCT CONSTRUCTION STANDARDS MANUAL', LATEST EDITION AND ASHRAE USING PRIME SHEETS OF GALVANIZED STEEL CONFORM TO THE REQUIREMENTS IN THE REFERENCED STANDARD FOR METAL THICKNESS, REINFORCING TYPES AND INTERVALS, TIE ROD APPLICATIONS AND JOINT TYPES AND INTERVALS. ALL SQUARE ELBOWS SHALL BE PROVIDED WITH DOUBLE WALLED VANES ON MAXIMUM 3" CENTERS. PROVIDE SEAL CLASS "CON ALL TRAVERSE JOINTS UNLESS SUPERSEDED BY MORE STRINGENT LOCAL CODES. ALL DUCT CONNECTIONS ARE TO BE RIGID AND LEAK FREE ASSEMBLIES. EALED P F ANY PENINGS EITHER AT ALLED I TO BE COMPLETELY S U 0 0 ANY DUCTWORK (NST S N PHA E OF THE PROJECT , D RING THE CONSTRUCTIO S 3. U , THE BEGINNING OR END OF A DUCT RUN OR AT A BRANCH, COLLAR DIFFUSER OR REGISTER TO AVOID DIRT OR OTHER CONTAMINANTS FROM ENTERING THE SYSTEM. 4. EXCEPT WHERE OTHERWISE INDICATED, CONSTRUCT DUCT SYSTEMS TO 2 INCH WATER GAUGE PRESSURE CLASSIFICATION (VERIFY WHETHER RETURN OR EXHAUST DUCT IS POSITIVE OR NEGATIVE PRESSURE). PRESSURE TEST DUCTS FOR LEAKAGE REMAKE LEAKING JOINTS AND APPLY SEALANTS AS REQUIRED TO FABRICATE A SYSTEM THAT DOES NOT EXCEED 5 PERCENT LEAKAGE OR LESS AS STATED BY PRESSURE CLASS RATINGS IN SMACNA STANDARDS. 5. AS A MINIMUM, CROSSBREAK ALL FLAT SURFACES OR REINFORCE WITH A BEAD APPROXIMATELY 3/8 INCH WIDE BY 3/16 INCH DEEP ON 12 INCH CENTERS TO PREVENT VIBRATIONS. 6. INSTALL RIGID ROUND AND RECTANGULAR METAL DUCT WITH SUPPORT SYSTEMS INDICATED IN SMACNA STANDARDS. NO WOOD SHALL BE USED TO SUPPORT OR BRACE DUCTS. PROVIDE SWAY AND SEISMIC BRACING AS REQUIRED BY PROVINCE AND LOCAL CODES OR BY LANDLORD. 7. WHERE DUCTS PASS THROUGH ROOFS, FLOORS AND FIRE RATED PARTITIONS, PROVIDE AS MINIMUM 1-1/2 INCH BY 1-1/2 INCH BY i/8 INCH STEEL ANGLE FRAMES AT EACH SIDE OF OPENING. THE ANNULAR SPACE BETWEEN DUCT AND ANGLE FRAMES SHALL BE CAULKED WITH SILICONE SEALANT OR FIREPROOFED AS REQUIRED BY THE ASSEMBLY FIRE RATING. CONTRACTOR TO PROVIDE FIRE OR COMBINATION FIRE / SMOKE DAMPERS AT EACH PENETRATION WHERE REQUIRED BY CODE 8. ALL TRAVERSE JOINTS AND SEAMS IN SUPPLY AIR DUCT SHALL BE SEALED AIR TIGHT WITH DAP CMC DUCT SEALER. JOINTS ALSO SHALL BE RIVETED OR CONNECTED WITH SHEET METAL SCREWS. 9. SOFT ELASTOMER BUTYL GASKETS WITH ADHESIVE BACKING SHALL BE USED TO SEAL FLANGED JOINTS. 10. DUCT TRANSITIONS SHALL NOT EXCEED 30 DEGREES SLOPE EXCEPT AS SPECIFICALLY NOTED OTHERWISE 11. PROVIDE ACCESS TO ALL MOTORIZED DAMPERS, FIRE DAMPERS, FIRE /SMOKE DAMPERS, CONTROLS AND OTHER ITEMS IN DUCTWORK THAT REQUIRE SERVICE OR INSPECTION. iF THE ACCESS PANEL LOCATION IS EXPOSED TO THE SALES AREA, iT MUST BE APPROVED BY THE TENANT'S CONSTRUCTION MANAGER PRIOR TO INSTALLATION. LAY -IN SUPPLY AND RETURN AIR DIFFUSERS, GRILLES AND REGISTERS WITH PLASTER FRAMES MAY BE USED AS ACCESS LOCATIONS. 12. ALL BRANCHES AND TAKEOFFS SHALL BE EQUIPPED WITH MANUAL VOLUME CONTROWNG DEVICES HAVIHG AN INDICATING AND LOCKING DEVICE I. FLEXIBLE CONNECTIONS 1. FLEXIBLE COLLARS SHALL BE PROVIDED IN All CONNECTIONS BETWEEN VIBRATING EQUIPMENT (FANS, ROCFTOP UNITS, WATER SOURCE HEAT PUMPS, AIR HANDLERS, FAN POWERED VAV BOXES, ETC) AND DUCTS OR CASINGS. ALSO PROVIDE FLEXIBLE CONNECONS WHERE DUCTS CROSS BUILDING EXPANSION JOINTS. 2. FLEXIBLE CONNECTIONS SHALL BE CONSTRUCTED OF NEOPRENE -COATED FLAMEPROOF FABRIC PROVIDE ADEQUATE JOINT FLEXIBILITY TO ALLOW FOR MOVEMENT AND PREVENT THE TRANSMISSION OF VIBRATION. 3. FLEXIBLE CONNECTIONS ARE TO BE RATED FOR THE OPERATING PRESSURE OF THE SYSTEM. 4. FINAL CONNECTIONS TO EXHAUST FANS) SHALL BE WITH A HEAVY AIRTIGHT ACID RESISTANT FIRE RETARDANT FIBERGLASSED NEOPRENE CONNECTOR, A MINIMUM OF SIX (6) INCHES IN LENGTH. THE CONNECTOR SHALL BE FASTENED TO EQUIPMENT AND DUCT WITH TWO FLEXIBLE REMOVABLE BRASS STRAPS OR ALTERNATE APPROVES] METHOD. J. THERMOSTATS A. MOUNT THERMOSTATS X-0" (ADA COMPLYING), THERMOSTAT SENSORS V-0" ABOVE FINISHED FLOORS AHD SET DATE, TIME, TEMPERATURE, ETC TURN OVER OPERATING INSTRUCTIONS TO TENANT REPRESENTATIVE B. THERMOSTATS SHALL BE PROVIDED WITH KEY OPERATED SECURITY COVERS AND DESCRIPTIVE NAMEPLATES. K. FIRE DAMPERS, SMOKE DAMPERS 1. THE MECHANICAL CONTRACTOR SHALL PROVIDE ALL FIRE DAMPERS AS REQUIRED BY LANDLORD AND / OR TENANT CRITERIA AND / OR CODES HAVING JURISDICTION. ALL FIRE DAMPERS SHALL COMPLY WITH THE REQUIREMENTS OF THE BOARD OF FIRE WDERWRITERS, THE LOCAL FIRE MARSHAL AND SHALL BE LABELED AND APPROVED BY UNDERWRITERS LABORATORIES. 2. FIRE DAMPERS SHALL HAVE THE BLADES OUT OF THE AIR STREAM AND A 165 DEGREE F FUSIBLE UNK. 3. PROVIDE ALL NECESSARY FRAMING AND SLEEVES FOR DAMPER MOUNTING PER UL AND CODE REQUIREMETTS. 4. PROVIDE DUCT ACCESS DOORS IN AN ACCESSIBLE LOCATION FOR ALL FIRE DAMPERS. DOOR IS TO BE 20 CAUGE GALVANIZED DOOR WITH QUICK -OPENING LATCH AND PIANO HINGE 5. WHERE REQUIRED BY LOCAL CODES, LANDLORD AND IF INDICATED ON DRAWINGS, PROVIDE UL555S SMOCE DAMPER WITH FIRE/HEAT/SMOKE SENSOR, REVERSIBLE MOTOR AND INTERLOCK WITH FIRE ALARM SYSTEM. 1, FLEXIBLE DUCT FOR CONNECTIONS SHALL BE A FACTORY FABRICATED ASSEMBLY CONSISTING OF AN INNEL SLEEVE, INSULATION AND AN OUTER MOISTURE BARRIER. THE INNER SLEEVE SHALL BE CONSTRUCTED OF A CONTINUOUS VINYL COATED SPRING PEEL WIRE HELIX FUSED TO A CONTINUOUS LAYER OF FIBERGLASS IMPREGNATED AND COATED VINYL A 1 1 /4" THICK LAYER OF INSULATING BLANKET OF FIBERGLASS WOOL SHALL ENCASE THE INNER SLEEVE AND BE SHEATHED WITH AN OUTER MOISTURE BARRIER OF A BIDIRECTIONAL REINFORCED METAJZED VAPOR BARRIER. THE FLEXIBLE DUCT SHALL BE RATED FOR A MAXIMUM WORKING VELOCITY OF 6000 FPM AND SHALL BE LISTED BY THE UNDERWIITERS LABORATORIES UNDER THEIR UL -181 STANDARDS AS A CLASS 1 DUCT AND SHALL COMPLY WITH NFPA STANDARD - 90A. THE FLEXIBLE DUCT SHAII BE THERMAFLEX M -KC OR APPROVED EQUIVALENT. FLEXIBLE DUCT SHALL ROUTE FROM SHEET METAL DUCTWORK TO CEILING DIFFUSERS ONLY. THEIE SHALL BE NO EXPOSED FLEXIBLE DUCT. 2. FLEXIBLE AIR DUCT MAY ONLY BE USED IN VERTICAL APPLICATIONS WiTH PRIOR APPROVAL FROM THE TENANT'S CONSTRUCTION MANAGER. 3. FLEXIBLE DUCT SHALL NOT EXTEND OVER 5 FEET IN LENGTH AT ANY ONE LOCATION. M. SUPPLY AND RETURN AIR TAKEOFF FITTINGS A. RECTANGULAR DUCT 1. PROVIDE 45 DEGREE RECTANGULAR TAKEOFFS FROM MAIN DUCTWORK TO RECTANGULAR BRANCHES. B. SPIRAL DUCT 1. PROVIDE SADDLE OR DIRECT CONNECTION OF A BRANCH DUCT INTO A LARGER DUCT. THE DIAMETER OF THE BRANCH SHALL NOT EXCEED TWO THIRDS OF THE DIAMETER OF THE MAIN. PROTRUSIONS INTO THE MAIN ARE NOT ALLOWED. N. DAMPERS 1. PROVIDE MANUAL LOCKING QUADRANT VOLUME CONTROL DAMPERS WITH HANDLE OPERATORS IN EACH BRANCH DUCT AND AS SHOWN ON PLANS TO FACILITATE AIR BALANCING. 2. WHERE ACCESS TO BALANCING DAMPER IS RESTRICTED OR IN AREAS WITH SHEET ROCK CEILINGS, YOUNG REGULATORS SHALL BE USED. 3. ALL RECTANGULAR DAMPERS IN OUTSIDE AIR AND RELIEF AIR DUCTS ARE TO BE OPPOSED BLADE TYPE ALL (ECTANGULAR DAMPERS IN RETURN AIR DUCTS TO BE PARALLEL BLADE TYPE. ALL OUTSIDE AIR DUCT DAMPERS MUST ALSO BE OF THE LOW LEAKAGE TYPE 4. ALL MOTORIZED DAMPERS NOT FURNISHED WITH EQUIPMENT ARE TO BE HONEYWELL DAMPERS. 0. DIFFUSERS, GRILLES AND REGISTERS 1. PROVIDE DIFFUSERS, GRILLES AND REGISTERS AS SCHEDULED. DEVICES TO BE COMPLETE WITH FRAMES AND ALL ACCESSORIES. ALL DIFFUSERS, GRILLES AND REGISTERS IN SHEET ROCK CEILINGS TO BE PROVIDED WITH PLASTER FRAMES. FINISH TO BE COORDINATED WITH INTERIOR FINISHES. 2. INSTALL ALL AIR DEVICES AS LOCATED ON THE ARCHITECTURAL REFLECTED CEILING PLAN OR THE MECHANICAL PLAN. P. DUCTWORK INSULATION 1. ALL NEW SUPPLY AND RETURN AIR DUCTWORK WITHIN IV OF HVAC UNIT SHALL BE ACOUSTICALLY LINED.DUCT SIZES SHOWN ON THE DRAWING ARE INTERNAL FREE AREA SIZES. INTERNAL LINER SHALL BE 1 1 /2" THICK DUCT LINER EQUIVALENT TO JOHNS MANVILLE'PERMACOTE LINACOUSTIC" ("R VALUE" = 6.3) AND SHALL BE APPLIED TO THE DUCTWORK WITH FIRE RESISTIVE ADHESIVES AND CADMIUM 01 COPPER PLATED MECHANICAL FASTENERS. 2. ALL OUTSIDE AIR AND UNEXPOSED DUCTWORK WITHIN BUILDING, EXCEPT WHERE ACOUSTICALLY LINED, STALL HAVE 2 INCH, FIBERGLASS DUCT WRAP INSULATION WITH FSK FACING EQUIVALENT TO JOHNS MANVILLE'MICROLITE XG TYPE 75' (INSTALLED "R VALUE" = 5.6). 3. LEADING EDGES OF DUCT INSULATION SHALL BE OVERLAPPED BY ADJOINING INSULATION FOR 6" MINIMUM AND THEIN SEALED WITH FOIL VAPOR BARRIER ADHESIVE AND DUCT MASTIC SO THAT NO FIBERGLASS INSULATION IS VISIBLE 4. ALL INSULATION ON EXISTING PIPING OR DUCTS THAT IS WETTED, DAMAGED, DISTURBED OR REMOVED SHALL BE REPLACED. 5. INSTALL INSULATION PRODUCTS IN ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS AND IJ ACCORDANCE WITH RECOGNIZED INDUSTRY PRACTICES. INSULATION MUST COMPLY WITH NFPA 90A. 6. ALL INSULATION SHALL HAVE A FLAME SPREAD RATING OF NOT MORE THAN 25 AND A SMOKE DEVELOPED RATING OF NO HIGHER THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM C 411 OR AS REQUIRED BY LOCAL CODES. 7. EXTERIOR SUPPLY AND RETURN DUCT INSULATION A. SERVICE, RECTANGULAR, SUPPLY -AIR AND RETURN -AIR DUCTS. 1. MATERIAL• INSULATION BOARD, 6 PSF MINIMUM AND PLAIN FACING. 2. THICKNESS: 2 INCHES. 3. NUMBER OF LAYERS: TWO. TOTAL THICKNESS = 4" 4. VAPOR RETARDER REQUIRED: YES. A. INORGANIC GLASS FIBERS PREFORMED AND BONDED BY THERMOSETTING RESIN. MUST COMPLY WITH ASTM C 612, TYPE 1 A AND 1 B, 1. KNAUF INSULATION OR APPROVED EQUIVALENT. A. INSULATION INSTALLED OUTDOORS: FLAME SPREAD RATING OF 25 OR LESS AND SMOKE DEVELOPED RATING OF 50 OR LESS. B. APPLY INSULATION AS FOLLOWS: A. APPLY TWO -LAYER INSULATION WITH JOINTS TIGHTLY BUTTED AND STAGGERED AT LEAST 3 INCHES. SECURE LAYERS WITH ADHESIVE, MECHANICAL FASTENERS OR BANDING. FASTENERS SHALL BE LOCATED A MAXIMUM OF 3" FROM EACH EDGE AND NO GREATER THAN 12' APART. B. ON EXPOSED APPLICATIONS, FINISH INSULATION WITH A SKIM COAT OF MINERAL -FIBER, HYDRAULIC -SETTING CEMENT TO SURFACE OF INSTALLED INSULATION. WHEN DRY, APPLY FLOOD COAT OF LAGGING ADHESIVE AND PRESS ON ONE LAYER OF GLASS CLOTH OR TAPE OVERLAP EDGES AT LEAST 1 INCH (25 MM). APPLY FINISH COAT OF LAGGING ADHESIVE OVER GLASS CLOTH OR TAPE TITIN THE FINISH COAT TO ACHIEVE SMOOTH FINISH. OUTDOOR JACKET. POLYGUARD PRODUCTS, INC'ALUMAGUARD 60' OR MFM BUILDING PRODUCTS CORP.'FLEXCLAD 400". Q. SYSTEM CLEANOUT 1. UPON COMPLETION OF INSTALLATION, CLEAN ENTIRE SYSTEM BEFORE INSTAWNG AIR OUTLETS. CONTRACTOR TO PROVIDE A CERTIFICATION THAT CLEANING WAS ACCOMPLISHED PRIOR TO PROJECT CLOSEOUT. 2. FILTERS MUST BE IN UNITS AT ANY TIME FANS ARE OPERATED. R. SYSTEM TESTING. ADJUSTING AND BALANCING 1. TESTING, ADJUSTING AND BALANCING OF ALL WORK SHALL BE COMPLETED BY AN INDEPENDENT CONTRACTOR WHO IS CURRENTLY LICENSED BY THE ASSOCIATED AIR BALANCING COUNCIL (AABC) OR NATIONAL ENVIRONMENTAL BALANCING BUREAU (NEBB). NO OTHER BALANCE REPORTS WILL BE REVIEWED OR ACCEPTED. ALL BALANCING WORK MUST BE COMPLETE AND DONE IN ACCORDANCE WITH TEE MOST RECENT STANDARDS OF THEIR SOCIETY. PAYMENT OF ALL COSTS FOR TESTING SHALL BE MADE BY THE HVAC CONTRACTOR. 2. THE CONTRACTOR SHALL INSTALL NEW FILTERS IN ALL UNITS PRIOR TO THE AIR BALANCING. THE COMPLETE AIR BALANCE SHALL TAKE PLACE WITH OUTSIDE AIR DAMPERS IN MINIMUM POSITION. M TED N THE DRAWIN S. ANY R UIRED CHANGES IN 3. BALANCE AIR AND WATER QUANTITIES TO WITHIN PLUS OR THUS 5 PERCENT OF THAT INDICA 0 G EQ SHEAVES, BELTS, PULLEYS OR THE ADDITION OF DAMPERS REQUIRED TO ACHIEVE SPECIFIED FLOW RATES SHALL BE PROVIDED BY THE HVAC CONTRACTOR WITH NO ADDITIONAL COST TO THE TENANT. 4. THE BALANCE REPORT SHALL INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION: A) AABC OR NEBB CERTIFICATION NUMBER AND SIGNATURE OF BALANCING CONTRACTOR. B) INSTRUMENTATION UST WITH LAST CALIBRATION DATES. C) MAKE AND MODEL NUMBERS OF ALL HVAC EQUIPMENT TESTED. D) AIR CFM AND STATIC PRESSURE READINGS (DISCHARGE AND SUCTION) AS MEASURED BY PITOT TUBE DUCT TRAVERSE AT THE UNITS. E) MOTOR NAMEPLATE DATA WITH ACTUAL FIELD VOLTAGE AND AMPERAGE READINGS FOR EACH LEG. 0 MOTOR AND FAN RPM, SHEAVE SIZES AND BELT SIZES AND LENGTHS. G) OUTSIDE, RETURN, MIXED AND SUPPLY AIR TEMPERATURES AT FULL COOLING. H) WATER BALANCE DATA INCLUDING GPM WITH INLET AND OUTLET TEMPERATURE AND PRESSURE READINGS. 1) MAKE AND MODEL NUMBERS OF ALL AIR DISTRIBUTION EQUIPMENT. J) FINAL BALANCED AIR VOLUMES AT ALL OUTLETS (INCLUDING RETURNS WHERE DUCTED). K) INDEXED PLAN WITH DIFFUSER AND RETURN LOCATIONS. 5. ALL CONTROL SEQUENCES SHALL BE TESTED AND OPERATING STATUS RECORDED IN THE REPORT. 6. THREE COPIES OF THE BALANCE REPORT SHALL BE SUBMITTED THROUGH THE GENERAL CONTRACTOR TO THE TENANT'S CONSTRUCTION MANAGER FOR REVIEW AND COMMENT. 7. THE BALANCING CONTRACTOR SHALL PERFORM ALL APPLICABLE TESTING AND BALANCING FUNCTIONS REQUIRED FOR THE SYSTEM DESIGNED IN THESE DRAWINGS. THE BALANCING CONTRACTOR SHALL RECHECK ANY ITEMS THAT THE TENANT DEEMS NECESSARY AT NO ADDITIONAL COST TO THE TENANT. 8. FINAL BALANCE REPORT SHALL BE INCLUDED IN THE OPERATION AND MAINTENANCE MANUAL 1. ASIDE FROM NORMAL INTERIM INSPECTIONS OF WORK IN PLACE, THE TENANT SHALL HAVE THE RiGHT TO HAVE AN INDEPENDENT HVAC CONTRACTOR INSPECT THE FINISHED HVAC INSTALLATION UPON COMPLETION FOR COMPLIANCE WITH THE PLANS, SPECIFICATIONS AND CODES. THE INSTALLING CONTRACTOR WILL BE RESPONSIBLE TO BRING ALL ITEMS REPORTED BY THE INDEPENDENT HVAC CONTRACTOR UP TO PLANS AND SPECIFICATIONS REQUIREMENTS AT NO ADDITIONAL COST TO THE TENANT. T. INDOOR AIR QUAUTY 1. NO ANALYSIS HAS BEEN MADE WITH REGARD TO SOURCES OR POTENTIAL SOURCES OF INDOOR OR OUTDOOR AIR CONTAMINANTS OR LEVELS OF CONTAMINATION. 2. IT IS THE RESPONSIBILITY OF THE GENERAL AND MECHANICAL CONTRACTOR TO INFORM THE TENANT'S REPRESENTATIVE, LANDLORD AND TENANT'S ARCHITECT IF ANY SOURCE OR POTENTIAL SOURCE OF INDOOR AIR CONTAMINATION IS IDENTIFIED. 3. PRIOR TO ENCLOSING SPACES SUCH AS PLUMBING CHASES, AIR SHAFTS AND RETURN AIR PLENUMS CLEAN ALL AREAS THOROUGHLY. THE CONTRACTOR SHALL GUARANTEE THAT THE PLENUM CHAMBER USED FOR RECIRCULATING OF AiR WILL BE OF TIGHT CONSTRUCTION AND THAT ALL SOURCES OF CONTAMINATION FROM TRAPS, SOIL STACKS, DOWNSPOUTS, VENTS, EXHAUST DISCHARGES AND OTHER SOURCES WILL BE ENCLOSED SO THAT NO CONTAMINATED AIR WILL BE RECIRCULATED. 4. PRIOR TO COMMENCING CONSTRUCTION ACTIVITIES SHUT OFF THE HVAC SYSTEM, BLOCK OFF ALL AIR GRILLS, DIFFUSERS AND OTHER OPENINGS OUTSIDE THE IMMEDIATE CONSTRUCTION AREA. OPENINGS TO ADJACENT TENANT SPACES SHALL BE COVERED WITH FILTER MEDIA TO PREVENT DUST AND OTHER AIRBORNE CONTAMINANTS FROM PASSING TO ADJOINING SPACES. 5. CONTRACTOR TO INSTALL TEMPORARY EXHAUST SYSTEM TO VENTILATE CONSTRUCTION SITE AND KEEP SITE UNDER SLIGHT NEGATIVE PRESSURE DURING ALL HOURS OF CONSTRUCTION, EVEN IF AFTER NORMAL BUSINESS HOURS. 6. CONTRACTOR TO INSTALL TEMPORARY BARRIERS TO PROTECT ADJACENT SPACES FROM DUST, PARTICULATES, VAPORS AND NOISE WHERE TEMPORARY BARRIERS ARE INSTALLED ALWAYS MAINTAIN FIRE EXITS AND EXITWAYS. I 1-30-06 PLUMBING SPECIFICATIONS 1. IT IS THE INTENT OF THESE SPECIFICATIONS TO PROVIDE A COMPLETE INSTALLATION FOR FINISHED WORK, TESTED AND READY FOR OPERATION. THE WORK THROUGHOUT SHALL BE EXECUTED IN THE BEST AND MOST THOROUGH MANNER UNDER THE DIRECTION OF AND TO THE SATISFACTION OF THE OWNER. 2. ALL MATERIALS REQUIRED FOR THIS WORK SHALL BE NEW, UNUSED, BEST OF ITS RESPECTIVE KINDS, AND FREE FROM DEFECTS AND OF FIRST CLASS QUALITY. BASIS OF QUALITY SHALL BE LATEST STANDARDS OF ASTM, ANSI FEDERAL SPECIFICATIONS OR OTHER ACCEPTABLE STANDARDS. 3. THE PLUMBING CONTRACTOR SHALL BE RESPONSIBLE FOR THEIR WORK UNTIL ITS COMPLETION AND FINAL ACCEPTANCE AND SHALL REPLACE ANY OF THE SAME WHICH MAY BE DAMAGED, LOST OR STOLEN WITHOUT ADDITIONAL COST TO THE OWNER. 4. THE PLUMBING CONTRACTOR SHALL GUARANTEE ALL WORK PERFORMED AND MATERIALS INSTALLED TO BE FREE FROM INHERENT DEFECTS AND SHALL KEEP IN REPAIR AND REPLACE ANY DEFECTIVE MATERIALS OF WORKMANSHIP, FREE OF COST TO THE TENANT (OWNER) FOR A PERIOD OF ONE (1) YEAR AFTER THE OPENING FOR BUSINESS. 5. ALL WORK SHALL BE DONE ACCORDING TO THE REQUIREMENTS OF ALL APPLICABLE CODES AND LEASE CRITERIA (IF APPLICABLE) AND SHALL RECEIVE THE APPROVAL OF ALL AUTHORITIES HAVING JURISDICTION. PREPARE ALL REQUIRED DOCUMENTS, DRAWINGS AND PERFORM ALL REQUIRED TESTS AND PAY ALL REQUIRED CHARGES TO OBTAIN THESE APPROVALS. 6. CONTRACTOR SHALL BE HELD TO HAVE EXAMINED THE SITE FOR THE WORK BEFORE HAVING SUBMITTED A PROPOSAL NO ADDITIONAL COMPENSATION WILL BE ALLOWED FOR CONDITIONS FOUND DURING THE COURSE OF THE CONTRACT. 7. THIS CONTRACTOR MUST PROVIDE LANDLORD'S CONSTRUCTION REPRESENTATIVE WITH COPIES OF REQUIRED INSURANCE AND COPIES TO BE FURNISHED TO THE OWNER BEFORE COMMENCING WORK. 8. SUBMIT THREE (3) SETS OF SHOP DRAWINGS IDENTIFIED WITH PROJECT NAME OF THE FOLLOWING (1) ELECTRIC HOT WATER HEATER (2) PLUMBING FIXTURES AND TRIM. CONTRACTOR SHALL SUBMIT SHOP DRAWING OF PIPING LAYOUT TO THE OWNER FOR THEIR FILE 9. THE PLUMBING CONTRACTOR IS A SUBCONTRACTOR OF THE TENANT'S GENERAL CONTRACTOR. 10. NOTCHING AND BORING OF STRUCTURAL STEEL MEMBERS IS NOT PERMITTED. WHEN HANGING FROM STRUCTURAL STEEL ONLY HANG FROM TOP FLANGE OF BEAMS AND TOP CHORDS ONLY AT PANEL POINTS OF JOISTS / TRUSSES. I. WORK RESPONSIBILITY 1. FURNISH ALL LABOR, MATERIALS, EQUIPMENT AND CONTRACTORS FOR A COMPLETE, SAFE INSTALLATION OF PLUMBING WORK IN FULL CONFORMITY WITH REQUIREMENTS OF ALL AUTHORITIES HAVING JURISDICTION AS INDICATED ON DRAWINGS AND/OR HEREIN SPECIFIED, INCLUDING IN GENERAL THE FOLLOWING: 2. SANITARY DRAINAGE CONNECTIONS TO PLUMBING FIXTURES AND EQUIPMENT REQUIRING SAME WITH FINAL CONNECTIONS TO EXISTING PREINSTALLED OUTLETS PROVIDED BY PRIOR TENANTS) OR LANDLORD. PLUMBER SHALL VERIFY EXACT LOCATION OF WASTE PIPE OUTLET BEFORE SUBMITTING BID AND NOTIFY THE ARCHITECT OF ANY LOCATION DISCREPANCIES. PLUMBING CONTRACTOR SHALL BE RESPONSIBLE FOR ANY CONCRETE SAWCUTTING REQUIRED TO MAKE THE FINAL CONNECTION TO THE EXISTING WASTE PIPING OR CAPPED OUTLET(S). SAWCUTTiNG, EXCAVATING, BACKFIWNG AND NEW CONCRETE MUST MEET WITH THE LANDLORD'S APPROVAL A. SNAKE SANITARY FOR A DISTANCE OF 100 FEET AND REPORT ANY BLOCKAGE B. TEST WATER PRESSURE TO INSURE MINIMUM OF 30 PSI. 3. COMPLETE VENT SYSTEM, ALL FIXTURES INDIVIDUALLY VENTED WITH FINAL CONNECTION THROUGH ROOF OR TO EXISTING LANDLORD SUPPLIED COMMON VENT. ROOF PENETRATION AND FLASHING TO BE PERFORMED BY LANDLORD'S ROOFER (IF APPLICABLE). COST OF ROOF PENETRATION AND FLASHING TO BE PART OF THIS CONTRACT, UNLESS NOTED OTHERWISE IN BID PROPOSAL (IF APPLICABLE). 4. DOMESTIC WATER SUPPLY SYSTEM INCLUDING CONNECTION TO EXISTING CAPPED OUTLET AND FINAL CONNECTIONS TO PLUMBING FIXTURES AND EQUIPMENT REQUIRING SAME VERIFY EXACT LOCATION AND SIZE BEFORE SUBMITTING BID. 5. INSULATION OF ALL HOT AND COLD WATER PIPING, INCLUDING UNDER LAVATORY A.D.A. PIPE WRAPPINGS. 6. FURNISH AND INSTALL WATER METER (IF APPLICABLE) ACCESSIBLE TO UTILITY COMPANY OR LANDLORD'S REPRESENTATIVE FOR MONITORING WATER, BUT METER SHOULD IN NO WAY BE IN THE PATH OF THE A.DA/CABG-ANSI, 5'-0' CIRCULAR PATTERN. 111. MATERIALS 1. DRAINAGE AND VENT PIPING: EXTRA HEAVY HUB AND SPIGOT CAST IRON SOIL WITH RUBBER GASKETS CONFORMING TO ASTM C564. NO -HUB CAST IRON TO HAVE HEAVY DUTY, TYPE 304 STAINLESS STEEL COUPLINGS CONFORMING TO ASTM A 666, TYPE 304 STAINLESS STEEL SHIELD, TYPE 304 STAINLESS STEEL BANDS AND SLEEVE: NPS 1 1/2" TO NPS 4": 3' WIDE SHIELD WITH 4 BANDS; NPS 5" TO NPS 10": 4" WIDE BAND WITH 6 BANDS. 2. WATER PIPING BELOW SLAB: TYPE K HARD COPPER TUBING, WITH CAST BRONZE OR WROUGHT COPPER SOLDER JOINT FITTINGS USING 95-5 SOLDER. WATER PIPING ABOVE SLAB: TYPE L COPPER TUBING USING SILVER SOLDER. 3. WATER HAMMER ARRESTORS: PROVIDE ON HOT AND COLD WATER BRANCHES TO FIXTURES, J. R. SMITH HYDROTROL MODEL 5020 FOR UP TO 60 FIXTURE UNITS. 4. VALVES: GATE VALVE WATTS SERIES B-3000, CHECK VALVE WATTS SERIES B-5000, BALL VALVE WATTS SERIES B6080 OR 86081 FULL PORT. ALL VALVES 1 /2' TO 2" BRONZE BODY. 5. PRESSURE AND TEMPERATURE RELIEF VALVE: WATTS REGULATING CO. MODEL l OL 6. PRESSURE REDUCING VALVE WATTS SERIES 25AUB BRONZE BODY WITH INTEGRAL S/S STRAINER, SEALED CAGE FOR 1 /2' TO 2 1 /2' DIA. TO 300 PSI. 7. PRESSURE GAUGE: AMETEK DIV. OF U.S. GAUGE MODEL P5105, 3 1/2' DIAL,1/4" STEM, ALUMINUM CASE, BLACK FINISH. 8. AIR VENT. HOFFMAN #79 WATER MAIN VENT VALVE 9. WATER METER: HERSEY CO. MODEL 400 SERIES IIS. 10. VACUUM RELIEF VALVE WATTS MODEL N36 -Ml BRASS BODY,1/2" NPT LINE SIZE 11. TRAP PRIMER: PPP MODEL P1-500 UP TO FOUR CONNECTIONS. OPTIONAL DISTRIBUTION UNIT REQUIRED FOR 2, 3 AND FOUR DRAIN LINES. 12. MIXING VALVE: WATTS SERIES MMV MIXING VALVE,1/2' LINE SIZE 13. BACKFLOW PREVENTOR. WATTS SERIES 719 DOUBLE CHECK VALVE ASSEMBLY BACKFLOW PREVENTOR. LINE SIZE 1 /2" TO 2" TO MATCH INLET WATER LINE SIZE IV. INSULATION 1. ALL HOT AND COLD WATER PIPING AND FITTINGS SHALL BE INSULATED WITH 1' THICK RIGID FIBERGLASS WITH VAPOR BARRIER UNIVERSAL JACKET PASTED WITH VAPOR BARRIER CEMENT. VAPOR BARRIER NOT REQUIRED ON HOT WATER PIPING. 2. ALL ADA CONFORMING, WHEELCHAIR ACCESSIBLE LAVATORY P -TRAP AND ANGLE VALVE ASSEMBLIES TO BE COVERED WITH THE MOLDED, ANTIMICROBIAL TRUBRO, INC "LAV -GUARD' UNDERSINK PROTECTIVE PIPE COVER MODEL #103. V. SPECIFIC PLUMBING SPECIFICATIONS 1. INSTALL NEW ONLY IF EXISTING DOES NOT MEET CURRENT ADA/CABG-ANSI (AS APPLICABLE) STANDARDS, OR IS DAMAGED, NOT IN WORKING ORDER OR NOT EXISTING AS APPLICABLE 2. IT IS THIS CONTRACTOR'S RESPONSIBILITY TO SUPPLY HANDICAPPED TOILET FIXTURES, IF REQUIRED BY CODE OR NOTED ON THE DRAWINGS, UTILIZING THE SPECIFICATION ABOVE AS A STANDARD AND MEETING CODE REQUIREMENTS. SPACING OF FIXTURES TO BE COORDINATED WITH THE GENERAL CONTRACTOR AS WELL AS THE PLUMBING INSPECTOR'S REQUIREMENTS. 3. PVC PIPING IS NOT PERMITTED ABOVE GRADE 4. INSTALL PLUMBING VENTS MINIMUM 10'-0" FROM BUILDING AIR INTAKES. 5. COSTS FOR WORKING BELOW TENANT'S SLAB IN ANOTHER TENANTS SPACE 6. INSTALLATION OF FLOOR DRAIN, BACKFLOW PREVENTER (IF REQ. BY CODE) AS PER LANDLORD REQUIREMENT AND CLEANOUT PER LOCAL CODE COORDINATE ALL LOCATIONS WITH OPERATIONS MANAGER. 7. COMPLETE NATURAL GAS PIPING SYSTEMS (AS APPLICABLE, REFER TO PLANS) 11. GENERAL ITEMS i. SLEEVES: PROVIDE #22 GAUGE GALVANIZED IRON PIPE SLEEVES FOR PIPING THROUGH WALLS AND FLOOR, PACK WITH NON -ASBESTOS ROPE AND FILL WiTH EXPANDO NON -SHRINKING CEMENT. 2. ESCUTCHEONS: PROVIDE EXPOSED PIPING, BOTH BARE AND COVERED, WITH CP CAST BRASS ESCUTCHEONS WHERE PASSING THROUGH FLOORS, CEILINGS, WALLS OR PARTITIONS. 3. HANGERS AND SUPPORTS: SUPPORT HORIZONTAL DRAINAGE PIPING AT LEAST EVERY 5 FEET OR AT EVERY HUB COPPER BI TU NG EVERY 7 FEET AND STEEL PIPE EVERY 10 FEET WITH "CLEVIS' HANGERS AND INSULATION PROTECTION SHIELDS. PIPING SHALL NOT BE SUPPORTED FROM BRIDGING OR OTHER PIPING. ONLY SUPPORT FROM TOP FLANGES OF BEAMS AND TOP CHORDS AT PANELS OF 101ST AND TRUSSES. PROVIDE SWAY AND SEISMIC BRACING WHERE REQUIRED BY CODES. 4. TEST. TEST PIPING AND PROVE TIGHT FOR AT LEAST TWO HOURS IN ACCORDANCE WITH REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION AND/OR AS SPECIFIED. TEST SHALL BE PERFORMED IN THE PRESENCE OF OWNER'S REPRESENTATIVE AND LOCAL INSPECTOR. TEST SHALL BE REPEATED IF NECESSARY UNTIL FINAL APPROVAL OF SYSTEM IS OBTAINED. A. TEST DRAINAGE AND VENT PIPING BY FILLING WITH WATER TO OVERFLOWING AT ROOF, WATER LEVEL TO REMAIN. B. TEST WATER PIPING WITH WATER 1 1 /2 TIMES THE WORKING PRESSURE 5. STERILIZATION OF DOMESTIC WATER SYSTEM: BEFORE BEING PLACED IN SERVICE, ALL WATER LINES SHALL BE CHLORINATED TO THE SATISFACTION OF THE ARCHITECT OR LANDLORD'S REPRESENTATIVE, IN ACCORDANCE WITH ANNA SPECIFICATION C601 -53T. 6. SLOPE WASTE LINES 2 INCHES AND SMALLER NOT LESS THAN 1/4 INCH PER FOOT. SLOPE LARGER MAINS NOT LESS THAN 1/B INCH PER FOOT. 7. INSTALL A CLEANOUT AT BASE OF EACH SOIL STACK, AT EACH CHANGE IN DIRECTION, AT INTERVALS NOT OVER 50 FEET AND ELSEWHERE AS SHOWN ON DRAWINGS OR REQUIRED BY LOCAL CODE CLEANOUTS SHALL NOT BE INSTALLED IN PUBLIC AREAS WITHOUT SPECIFIC PERMISSION BY TENANT'S CONSTRUCTION MANAGER. RECEIVE Cj_r,y L3 r -r t.l K REVIEWED FOR -CODE COi' PLiANCE QLC 1 9 2 �PPRQ'VE® DEC 2 3 2016 PF -6 -du i i City of Tukwila i BUILDING DIVISION f;. ,;, X _ ov M� 0 N CV N N i -4 M C; w W Z -' =V) J Q w u- >- 3 W Ch Q aM LLJ ,o > - VO LLJ N w N Lu � I -- �vi u - >O OJ Ln ~ �Q N COPYRIGHT DISCLAIMER: THIS DOCUMENT IS THE PROPERTY OF EPOCH DESIGN GROUP, COPYRIGHTED AS DATED, ALL RIGHTS RESERVED. AUTHORIZATION FROM EPOCH DESIGN GROUP FOR USE OF THIS Dmme,rr IS NOT TRANSFERABLE THE RECIPIENT OF THIS DOCUMENT IS HEREBY ADVISED THAT R IS RELEASED FOR USE (UNDER THE FOLLOWING TERMS AND CONDITIONS. THE DOCUMENT IS TO BE USED ONLY IN CONJUNCTION WITH THIS PROJECT. REUSE OF ANY PORTION OF THE DOCUMENT IN ANY OTHER CIRCUMSTANCE CONSTITUTES COPYRIGHT INFRINGEMENT. THE DOCUMENT IS FOR DESIGN INTENT AND INFORMATION ONLY, AND DOES NOT CONSTITUTE AS -BUILT CONDITIONS. THE RECIPIENT RETAINS THE OBLIGATION TO VERIFY THE CONDITIONS OF THE SUBJECT PROPERTY AND TO COMPLETELY COORDINATE ALL DIMENSIONS, FABRICATION METHODS, RELATED AND INTEGRATED SYSTEMS, ETC, WITH RESPECT TO ALL ASPECTS OF THE WORK. EPOCH DESIGN GROUP MAKES NO WARRANTY AS TO THE SUITABILITY OF THE DOCUMENT FOR THE RECIPIENT'S INTENDED USE THE RECIPIENT SPECIFICALLY AGREES TO WAIVE AND TO INDEMNIFY AND DEFEND ANY AND ALL CWMS AGAINST EPOCH DESIGN GROUP, RS CONSULTANTS, ANY OF ITS RELATED ENTRIES, VENDORS, OR CONTRACTORS, FOR ANY LOSS INCURRED AS A RESULT OF PROPER OR IMPROPER USE OF THIS DOCUMENT. THE RECIPIENT AGREES TO RETURN OR DESTROY THIS DOCUMENT UPON COMPLETION OR TERMINATION OF WORK PERFORMED IN CONJUNC ION WITH THIS PROJECT. PROFESSIONAL SEAL - L 12/14/16 EXPIRES: 09/21 �1 % PROJECT TITLE: SEATTLE, WA SOUTHCENTER MALL SPACE NO.: 1130 g •' j " No.O Revision Description Date _qHEET TITLE: MECHANICAL SPECIFICATIONS PROJECT NO.: SHEET NUMBER: 16283 DRAWN BY: JWK ISSUE DATE 12/14/16