HomeMy WebLinkAboutPermit M16-0194 - CITY TRANSFER - RTUCITY TRANSFER
11222 E MARGINAL WAY S
EXPIRED 07/17/17
Ml 6=01 94
City of Tukwila
• Department of Community Development
• 6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670
Inspection Request Line: 206-438-9350
Web site: http://www.TukwilaWA.gov
MECHANICAL PERMIT
Parcel No: 1023049001 Permit Number: M16-0194
Address: 11222 E MARGINAL WAYS Issue Date: 1/18/2017
Permit Expires On: 7/17/2017
Project Name: CITY TRANSFER
Owner:
Name: SEBCO INC
2015
Address: 4020 E MADISON #320, SEATTLE, WA,
2014
98112
2015
Contact Person:
2014
Name: MARK SMELTZER
Phone: (425) 251-0356
Address: 1012 CENTRAL AVE S, KENT, WA,
2014
98032
2015
Contractor:
2015
Name: PERFORMANCE HEATING & A/C INC
Phone: (425) 251-0356
Address: 1012 CENTRAL AVE S, KENT, WA,
98032
c
License No: PERFOHA15ORT
Expiration Date: 4/30/2017
Lender:
Name:
Address:
DESCRIPTION OF WORK:
RTU -1023049001
Valuation of Work: $8,900.00
Fees Collected: $311.22
Type of Work: NEW
Electrical Service Provided by: SEATTLE CITY LIGHT
Fuel type: GAS
Water District: TUKWILA
Sewer District: VALLEY VIEW
Current Codes adopted by the City of Tukwila:
International Building Code Edition:
2015
National Electrical Code:
2014
International Residential Code Edition:
2015
WA Cities Electrical Code:
2014
International Mechanical Code Edition:
2015
WAC 296-46B:
2014
Uniform Plumbing Code Edition:
2015
WA State Energy Code:
2015
International Fuel Gas Code:
2015
Permit Center Authorized Signature:
c
—
Date: `1 v
I hearby certify that I have read and examined this permit and know the same to be true and correct. All
provisions of law and ordinances governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other
state or local laws regulating construction or the performance of work. I am authorized to sign and obtain this
development permit and agree to the coditions attached to this permit. // G
Signature:
;�2� Date: I / (O ��
Print Name:
This permit shall become null and void if the work is not commenced within 180 days for the date of issuance, or if
the work is suspended or abandoned for a period of 180 days from the last inspection.
PERMIT CONDITIONS:
1: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an
approval of, any violation of any of the provisions of the building code or of any other ordinances of the City
of Tukwila. Permits presuming to give authority to violate or cancel the provisions of the code or other
ordinances of the City of Tukwila shall not be valid. The issuance of a permit based on construction
documents and other data shall not prevent the Building Official from requiring the correction of errors in
the construction documents and other data.
2: ***MECHANICAL PERMIT CONDITIONS***
3: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila
Permit Center (206/431-3670).
4: All permits, inspection record card and approved construction documents shall be kept at the site of work
and shall be open to inspection by the Building Inspector until final inspection approval is granted.
PERMIT INSPECTIONS REQUIRED
Permit Inspection Line: (206) 438-9350
1800 MECHANICAL FINAL
0701 ROUGH -IN MECHANICAL
CITY OF TUKW1- .
Community Development Department
Permit Center
• 6300 Southeenter Blvd., Suite 100
Tukwila, WA 98188
�' http://www.TukwilaWA.gov
Mechanical Permit No.
Project No.
Date Application Accepted:
Date Application Expires: 1
MECHANICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
**please print**
SITE LOCATION
King Co Assessor's Tax No.. 102304-9001
Site Address: 11222 East Marginal Way South Suite Number: NA Floor: Roof
Tenant Name: City Transfer New Tenant: ❑ .....Yes ®..No
PROPERTY OWNER
Name: SEBCO INC
Address: PO Box 130940
City: 4020 E MADISOb State: wa Zip: 98112
Sr -A -KILT;
CONTACT PERSON — person receiving all project
communication
Name: Mark Smeltzer
Address: 1012 Central Ave. S.
City: Kent State: WA Zip: 98032
Phone: (425) 251-0356 Fax: (253) 867-5775
Email: mark@pmghvac.com
Valuation of project (contractor's bid price): $
Describe the scope of work in detail:
1023049001
Use: Residential: New .......... ❑
Commercial: New .......... 1z
MECHANICAL CONTRACTOR INFORMATION
Company Name: Performance Mechanical Group
Address: 1012 Central Ave. S.
City: Kent State: WA Zip: 98032
Phone: (425) 251-0356 Fax: (253) 867-5775
Contr Reg No.: PERFOHA15ORT Exp Date: 04/30/2017
Tukwila Business License No.: BUS -0994165
•11
Replacement ........ ❑
Replacement ........ ❑
Fuel Type: Electric..... ❑ Gas ....... ® Other:
H:Upplications,Fort -Applications On Line\2016 ApplicationsWechanical Permit Application Revised 1-4-16.docx
Revised: January 2016
bh
Page] of 2
Indicate type of mechanical work being installed and the quantity below:
Unit Type
Qty
Furnace <100k btu
Residential, Nighttime
Furnace >1 OOk btu
Industrial
Floor furnace
55 dB(A)
Suspended/wall/floor
mounted heater
57 dB(A)
Appliance vent
Commercial
Repair or addition to
heat/refrig/cooling
system
47 dB(A)
Air handling unit
<I0,000 cfm
1
Unit Type
Qty
Air handling unit
210,000 cfm
Residential, Nighttime
Evaporator cooler
Industrial
Ventilation fan
connected to single duct
55 dB(A)
Ventilation system
57 dB(A)
Hood and duct
Commercial
Incinerator — domestic
47 dB(A)
Incinerator —
comm/industrial
65 dB(A)
Unit Type
Qty
Fire damper
Residential, Nighttime
Diffuser
Industrial
Thermostat
55 dB(A)
Wood/gas stove
57 dB(A)
Emergency enerator
Commercial
Other mechanical
equipment
47 dB(A)
60 dB(A)
65 dB(A)
Boiler/Compressor Qty
0-3 hp/100,000 btu
3-15 h /500,000 btu
15-30 hp/1,000,000 btu
30-50 hp/1,750,000 btu
50+hp/1,750,000 btu
Noise:
Mechanical units need to be in compliance with the Tukwila Noise Code. Maximum permissible sound levels are based on from where the sound is
created and where the sound is heard. Additionally, if sound can be heard from within a house at night in a residential zone it may not be allowed.
For more details, see TMC 8.22
District of Sound
Producing Source
District of Receiving Property
Residential, Daytime*
Residential, Nighttime
Commercial
Industrial
Residential
55 dB(A)
45 dB(A)
57 dB(A)
60 dB(A)
Commercial
57 dB(A)
47 dB(A)
60 dB(A)
65 dB(A)
Industrial
60 dB(A)
50 dB(A)
65 dB(A)
70 dB(A)
*Daytime means 7AM-1 OPM, Monday through Friday and 8AM-1 OPM, Saturday, Sunday and State -recognized holidays.
A few sounds are exempt from the noise code, including:
Warning devices;
Construction and property maintenance during the daytime hours (lam-IOpm);
Testing of backup generators during the day.
PERMIT APPLICATION NOTES -
Value of construction — in all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the permit center to comply with current fee schedules.
Expiration of plan review — applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The building official may grant one extension of time for additional periods not to exceed 90 days each. The extension shall be requested in writing
and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWNER OR AUTHORIZED AGENT
Signature:
Print Name: Mark Smeltzer
Mailing Address: 1012 Central Ave. S.
Date: 12/21/2016
Day Telephone: (425) 251-0356
Kent WA 98032
City State Zip
H:tApplications%Fonns-Applications On Line\2016 ApplicationsWechanical Permit Application Revised 1-4-16.docx
Revised: January 2016 Page 2 of 2
bh
DESCRIPTIONS
PAID
PermitTRAK
$311.22
M16-0194 Address: 11222 E MARGINAL WAY S
Apn: 1023049001
$311.22
MECHANICAL
$299.25
PERMIT ISSUANCE BASE FEE
R000.322.100.00.00
0.00
$32.50
PERMIT FEE
R000.322.100.00.00
0.00
$206.90
PLAN CHECK FEE
R000.322.102.00.00
0.00
$59.85
TECHNOLOGY FEE
$11.97
TECHNOLOGY FEE
TOTAL FEES PAID BY RECEIPT: R10110
R000.322.900.04.00
0.00
$11.97
Date Paid: Thursday, December 22, 2016
Paid By: BARRETT ROBERTS
Pay Method: CREDIT CARD 867522
Printed: Thursday, December 22, 2016 11:50 AM 1 of 1
SYSTEMS
STRUCTURAL CALCULATIONS
16-025-26
PMG - City Transfer RTU
11222 East Marginal Way South
Tukwila, WA 98168
for
PMG
November 28, 2016
R� D FOR
CODE PRRMPI
OVED LIANCE
JAN 0 6 2011
City of Tukwila
BUIL ION
_.__ a
CITY OF TUKWILA
DEC 2 2 20%
PERMIT CENTER
IL
Ate I
1 i
1201 First Avenue South, Suite 310 Seattle, Washington 98134 206-402-5156 www.lundopsahl.com
Project Address:
Design Code:
Project Description:
Project PMG - City Transfer RTU Sheet ;
Subject Overturning
Client
Performance Mechanical Group Page No. 1 ;
Designer DCD Date 11/28/16
www.lundopsahlxc m Tel: 206.402.5156
11222 East Marginal Way South
Tukwila, WA 98168
2012 IBC
ASCE 7-10
Review existing structure to support new mechanical unit
Provide seismic anchorage for the new unit
Mechanical Unit Information (provided by Client)
Unit Tag
(e)
Wei ht
(n) Weight
% Change
Note
RTU
403 lbs
405 lbs
0.5%
Doesn't increase by more than 5%, no further review required.
"Note: Mechanical Unit Weights were provided by Client. Lund Opsahl takes no responsibility if incorrect unit weights were
provided
ummary
he framing supporting the above mentioned units were checked for the additional weight added
the roof structure to verify demand on the existing framing does not exceed 5% per IBC
hapter 34. For members that had their demand increase by more that 5% additional strength
3Iculations were performed to verify the member has adequate capacity to support the unit.
he above mentioned mechanical units were reviewed for overturning forces from wind and
ismic loading. Calculations verifying PMG's proposed anchorage are included.
e proposed anchorage of the units is acceptable.
Project PMG - City Transfer RTU Sheet
Subject Overturning
Performance Mechanical Group p Page No. 2 �
_Designer DCD Date 11/28/16
www.lundopsahlxc m Tel: 206.402.5156
Seismic Design Criteria [ASCE 7-10 Chapter 13]
Risk Category = II
Site Class = D
ap = 2.5
RP = 6
1p = 1
Ss = 1.5g
Fa = 1
SMS = Fax Ss = 1.5g
Sds = 2/3 x Sms = 1.0g
z/h = 1.0g
Lateral Seismic Force.
Fp _ 0.4RpPlp i (1+2 h) _ .500Wp
P
FPmax = 1.6SpslpWp = 1.600Wp
Fpmt.a = 0.3SDsIpWp = .300Wp
Vertical Seismic Force.
Fp(-rt)=+/-0.2SDSWP = .200Wp
Wind Design Criteria [ASCE 7-10 Chapter 29]
[Table 1.5-1]
[Assumed]
[Table 13.6-1]
[Table 13.6-1]
[Section 13.1.3]
[Figure 22-1; Worst Case for Washington]
[Table 11.4-1]
[Eq 11.4-1]
[Eq 11.4-3]
[Assumed]
[Eq 13.3-1] <---Controls
[Eq 13.3-2]
[Eq 13.3-3]
[Section 13.3.1]
Avg Structure Roof Ht = 30 ft [Assumed]
Risk Category = II
Exposure = B [Section 26.7.3]
Basic Wind Speed, Vuit = 110 mph [Figure 26.5-1]
Kn = 1 [Section 26.8.2]
Kd = 0.85 [Section 26.6]
KZ = 0.7 [Table 29.3-1]
qZ = 0.00256KZKnKdV2
qZ = 18.43 psf
ASCE 7-10 Section 29.5 has two separate equations for buildings less than 60ft and more than 60ft
the equation for buildings less than 60ft produces higher loads and will be used for all cases
Horizontal Pressure Vertical Pressure
Fh=gh(GCr)Af [Eq 29.5-2] F,,=gh(GCr)Af [Eq 29.5-3]
GCr = 1.9 [Section 29.5.1] GCr = 1.5 [Section 29.5.1]
Fh = 35.02 psf Fh = 27.65 psf
SAHL
Unit Information
Tag: RTU -1
Weight: 405 Ibs
Height: 3.13 ft
Length: 3.79 ft
Width: 13.46 ft
Project PMG - City Transfer RTU Sheet
Subject Overturning
Performance Mechanical Group 3
Client P Page No. i
Desiqner DCD Date 11/28/16
www.lundopsahl.c�m Tel: 206.402.5156
Seismic Loading \I/
Fp= 20�EFp(ve
405 Ibs
+/- 81 Ibs =
Width
N
Worst Cast Uplift
ASD: 0.6D+0.7E = 29 lbs
LRFD: 0.9D+E = 50 Ibs
"Note negative values indicate uplift
Wind Loading
Fh= 415 Ibs D= 405 Ibs
FV _ +/- 363 Ibs =
Width
N
CY (Y
Worst Cast Uplift 4�
ASD: 0.6D+0.6W-1001bs I
"Note negative values indicate uplift
"Note our calculation checks overturning moment of
the mechanical unit in the short direction(width).
Reactions
D E
R1
R2203 Ibs -91 Ibs +/- 41 Ibs
203 lbs 91 Ibs +/- 41 Ibs
Worst Case Compression
ASD: D+0.7E = 295 Ibs
LRFD: 1.2D+E = 375 Ibs
Reactions
D W
R1 203 Ibs -187 Ibs +/- 181 Ibs
R2 203 lbs 187 Ibs +/- 181 Ibs
COMP. USED ON PAGE 5
Worst Case Compression
ASD: D+0.6W = 4241bs
LRFD: 1.2D+W = 6121bs
UPLIFT USED ON PAGE 4
Project PMG - CITY TRANSFER RTU Sheet
Subject OVERTURNING Page No. 4
UNDClient PERFORMANCE MECHANICL GROUP `—
Project No.
3AHL Designer DCD oat. 11/28/16
www.lundopsahl.com I Tel: 206.402.5156
C RITERI.q
uvilj = 40S L;S [FROM PAGE 71
U,PLI P-1 C K0 = -1CX) 4.35
C4 4A I L= PjWoj 12 GAUGE [FROM PAGE 61
U?L! t''ER IQGl.E= 10()L?,S/-2 ANGLES = '�,Cl LBS/AQUE
L z"x2''x 11/1 1 G Gr,
Si aE F E.Q
# 1U ;C.REvJ To uuzT
-w10 SCREWS iv cliptWEL
Cq Lam, EA
ANGLE] -T-1P.
F--____— P 1 ODD C u AIJ rJ EA-
-T
.
S/8'0 XS" LP6 SCREW @ Pfd
CUR N t9
LKIi J& 1G GA. SnEET METAL(CGU r�tAEV w1 PM&) FGR
` wt- U, n,
SI4EA-R =. 2 SCREWS X 370 Lf3SfiSCREu3 = -4G LAS ? S�jLRS
TFtJs�.o�l = � sc�Ews x ►37 c.as/SCRtt�
LA& ScRr--W To SLEIePER
�sSu rnT�v F%R
PER � DS I W = � 3 Lg5/ iN Of PEOE'1 RATTOQ
I" LAG F:ti- 15/8 10,Ntt t L " E TG 14: = 1.3 O
pvNuT�?J h G N
VJ = ;9 3 L6S/DJ x 1, 3b)' = 335.39 L&S > SCS L&s 011
MTN. CEKnEF TO CEVTSR= 3X D -T -ANA 3 X 0.00'=0.571)
M-1 ,J- EDGE 1)TST. = 1.S xISM, = I.S x0.1 (j-.
z�S,r
G.S'?" } 2(0,2F,5) = 1.t4L 1.S"
L NG SCREW sPRc1N& =
EDGE t7 -LST � 4D = 4 x 318 = 1,S))
4'' SLF-1~PF.R- ---� (1. S") = 1" 0
Project PMG - CITY TRANSFER RTU Sheet
Subject OVERTURNING Page No. 5
PERFORMANCE MECHANICL GROUP
Tient Protect No.
Designer DCD Date 11/28/16
www.lundopsahl.com I Tel: 206.402.5156
C0f,APRESSZe)N UN PIGGCG:
cjpW1= 72!'=s—`
M A X. ALLOW. tANTFOR NA L.CUHQ= SGO L?�,S
A(TUAL< LOAD 0 1A LbS/CHAWWEL_; = a la L8S
ala L9S, GC) L 6S ' • (rj7�)
'W4'95# i
I
X /
v'
o —
0
Z —
jl I
2x6 na 2'-0"O.C., TYP.
'WI'134#
'W2'84#
0
/A5TEN RTq 4 TO NEW CHANNELS WITHL2x2x161GA. TYP. 9 EACH CORNER,
FASTENAN LE TO CHANNEL WITH (2) #10 SCRE S. FASTENANGLE TO RTU -4
BASERAIL M 7TH(2) #10 SCREWS. (16) TOTAL #1 SCREWS.
C
I I
NEW PI000 HANNEL TO SPANEXISTING 4x4 WO D SLEEPERS, TYP.
OF(2) CHA NELS. FA5TENPI000 TO EXISTINGSL EPER WITH3/8x3"
LAGBOL T. ) LAG @ EACHEND OFCHANNEL, (4)L465TOTAL.
I I
EX15TINGR )OFED-IN 4x4x76"LONG WOOD SLEE R FASTENED TO
EXISTINGRQOFSTRUCTURE, TYP. OF(2) I
W
Figure 2. 4YCC4024-4036
-#1
(OUTSIDE)
BACK DUCT OPENINGS
SECT N
TYPICAL (8) SIDES OF SIDEFLON DUCT OPENINGS
Outline Drawings
O LM I
kot VAkt :
t-e0&50At17.,eV-.
145.1121
(SURFACE AREA)
BACK SIDE
313 �1*VP5.
3 Z Lt3 .
405 �bra.
530.60
[20.7/81
Height mm/in Flu Hood w/brkt
mm/InWeight
A D
W1
Approx. Corner Weight - kg / lbs
W2 W3
W4
Shipping
kg/lbs
Total Unit
Weight
kg/lbs
Center of Gravity mm/in
B C
4YCC4024 (060) 898.53 [35-3/8] 157.16 [6-3/16)
58.3 [129)
36.8 [81]
26.1 [58]
41.0 [90)
196.1 [432]
162.4 [358)
479.8 [18.9)
527.8 [20.8]
4YCC4030 (070) 898.53 [35-3/8] 157.16 [6-3/16)
61.3 [135]
38.7 [85]
27.5 [61]
43.1 (95]
204.8 [451]
171.1 [377]
406.5 [16.0]
594.1 [23.4]
4YCC4036 (070) 949.33 [37-3/8] 157.16 [6.3/16)
61.1 [134]
38.3 [84)
27.1 (60]
43.2 [95]
203.4 [438]
169.7 [374]
414.3 (16.3)
697.6 [27.5]
4YCC4036 (090) 949.53 [37-3/8] 157.16 [6.3/16]
61.7 [136]
38.9 (86]
27.7 161)
43.7 (96]
205.7 [453]
172.0 [379]
414.3 [16.3]
697.6 [27.5)
4YCC4036A-SUB-1 F -EN 5
Outline Drawings
M
10•
X41
18.03 18.29
123/321 123/321
14.22
191161
SECTION
TYPICAL (8) SIDES OF DOWNFLOW DUCT OPENINGS
Figure 1. 4YCC4024-4036
110-21/711
Note: The view labeled "Bottom side"
represents the base as viewed looking
up from underneath the unit.
4
OUTLET
Ez
LUE
ODD
4YCC4036A-SUB-1 F -E N
City of Tukwila Allan Ekberg, Mayor
Department of Community Development Jack Pace, Director
6/5/2017
MARK SMELTZER
1012 CENTRAL AVE S
KENT, WA 98032
RE: Permit No. M16-0194
CITY TRANSFER
11222 E MARGINAL WAY S
Dear Permit Holder:
In reviewing our current records, the above noted permit has not received a final inspection by the City of Tukwila Building
Division. Per the International Building Code, International Mechanical Code, Uniform Plumbing Code and/or the National Electric
Code, every permit issued by the Building Division under the provisions of these codes shall expire by limitation and become null
and void if the building or work authorized by such permit has not begun within 180 days from the issuance date of such permit, or if
the building or work authorized by such permit is suspended or abandoned at any time after the work has begun for a period of 180
days. Your permit will expire on 7/17/2017.
Based on the above, you are hereby advised to:
1) Call the City of Tukwila Inspection Request Line at 206-438-9350 to schedule for the next or final inspection. Each
inspection creates a new 180 day period, provided the inspection shows progress.
-or-
2) Submit a written request for permit extension to the Permit Center at least seven(7) days before it is due to expire.
Address your extension request to the Building Official and state your reason(s) for the need to extend your permit.
The Building Code does allow the Building Official to approve one extension of up to 180 days. If it is determined that your
extension request is granted, you will be notified by mail.
In the event you do not call for an inspection and/or receive an extension prior to 7/17/2017, your permit will become null and void
and any further work on the project will require a new permit and associated fees.
Thank you for your cooperation in this matter.
Sincerely,
kacAeR
ley
Permit Technician
File No: M16-0194
6300 Southcenter Boulevard Suite #100 9 Tukwila, Washington 98188 0 Phone 206-431-3670 • Fax 206-431-3665
�co� i t s o Y li EatORD MPY
PLAN REVIEW/ROUTING SLIP
PERMIT NUMBER: M16-0194 DATE: 12/23/16
PROJECT NAME: CITY TRANSFER
SITE ADDRESS: 11222 E MARGINAL WAY S
X Original Plan Submittal
Response to Correction Letter #,
Revision # before Permit Issued
Revision # after Permit Issued
DEPARTMENTS:
0 KYv& lit A'M Nor I�
Building Division N Fire Prevention Planning Division ❑
Public Works ❑ Structural ❑ Permit Coordinator ❑
PRELIMINARY REVIEW: DATE: 12/27/16
Not Applicable ❑ Structural Review Required ❑
(no approval review required)
REVIEWER'S INITIALS: DATE:
APPROVALS OR CORRECTIONS:
Approved ❑
Corrections Required ❑
(corrections entered in Reviews)
Notation: 1 SNI 1��V I
REVIEWER'S INITIALS:
DUE DATE: 01/24/17
Approved with Conditions ❑
Denied ❑
(ie: Zoning Issues)
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
12/18/2013
PERFORMANCE HEATING & A/C INC Page 1 of 2
Home Espanol Contnet Search L&I
e
A -J index help My L &I
Safety & Health Claims & Insurance Workplace Rights Trades & Licensing
10 Washington State Department of
Labor & Industries
PERFORMANCE HEATING & A/C INC
Owner or tradesperson
1012 Central Ave S
GENERAL
KENT, WA 98032
Principals
p
425-251-0356
MILLER, DANIEL E, PRESIDENT
KING County
ERDAHL, DARRIN, VICE PRESIDENT
Effective date
GOWIN, RICHARD L, VICE PRESIDENT
04/28/2016
(End: 04/26/2011)
Expiration date Help us improve
GOWIN, CONSTANCE F, VICE PRESIDENT
$12,000.00
(End: 11/15/2007)
Doing business as
PERFORMANCE HEATING & A/C INC
WA UBI No. Business type
600 601 386 Corporation
Governing persons
DANIEL
E
MILLER
DARRIN P ERDAHL;
License
Verify the contractor's active registration / license / certification (depending on trade) and any past violations.
Construction Contractor. Active.
..........................................................................
Meets current requirements.
License specialties
GENERAL
$1,000,000.00
License no.
PERFOHA15ORT
Effective — expiration
Effective date
12/30/1985— 04/30/2017
04/28/2016
Bond
......._....
Expiration date Help us improve
DEVELOPERS SURETY & INDEM CO
$12,000.00
Bond account no.
748802C
Received by L&I
Effective date
11127/2007
10/01/2007
Expiration date
Until Canceled
Insurance
..............._....._
AMCO Ins Co
$1,000,000.00
Policy no.
GLA03007606389
Received by L&I
Effective date
04/26/2016
04/28/2016
Expiration date Help us improve
https://secure.Ini.wa.gov/verify/Detail.aspx?UBI=600601386&LIC=PERFOHA15ORT&SAW= 1/18/2017
PERFORMANCE HEATING & A/C INC Page 2 of 2
04/28/2017
Insurance history
Savings
N"O",
.. .......
No savings accounts during the previous 6 year period.
Lawsuits against the bond or_savings
No lawsuits against the bond or savings accounts during the previous 6 year period.
L&I Tax debts
No L&I tax debts are recorded for this contractor license during the previous 6 year period, but some debts
may be recorded by other agencies.
License Violations
................_......................................
No license violations during the previous 6 year period.
Workers' comp
Do you know if the business has employees? If so, verify the business is up-to-date on workers' comp premiums.
L&I Account ID Account Is current.
494,599-00
.................................
Doing business as
PERFORMANCE HEATING & AIR COND
Estimated workers reported
Quarter 3 of Year 2016 "51 to 75 Workers"
L&I account representative
T1 / NICHOLE CAROW (360)902-5634 - Email: CANI235@lni.wa.gov
Workplace safety and health
Check for any past safety and health violations found on jobsites this business was responsible for.
Inspection results date
12/04/2015 No violations
Inspection no.
317938325
Location
3600 15th Ave W
Seattle, WA 98119
J Washington State Dept. of Labor & Industries. Use of this site is subject to the laws of the state of Washington.
Help us improve
https:Hsecure.lni.wa.gov/verifyIDetail.aspx?UBI=600601386&LIC=PERFOHA15ORT&SAW= 1/18/2017