HomeMy WebLinkAboutPermit EL16-0823 - AT&T - FLOOR BOXESAT&T
1010 SOUTHCENTER MALL
EL16-0823
City of Tukwila
• Department of Community Development
+ 6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670
Inspection Request Line: 206-438-9350
Web site: http://www.TukwilaWA.Rov
ELECTRICAL PERMIT
Parcel No: 9202470010
Permit Number: EL16-0823
Address: 1010 SOUTHCENTER MALL
Issue Date: 10/19/2016
International Residential Code Edition:
Permit Expires On: 4/17/2017
Project Name: AT & T
2014
Owner:
2015
Name: WESTFIELD PROPERTY TAX DEPT
2014
Address: PO BOX i30940, CARLSBAD, CA,
2015
92013
2015
Contact Person:
2015
Name: MARSIAL SEDA
Phone: (562) 216-5244
Address: 111 W OCEAN BLVD, #1750, LONG
BEACH, CA, 90802
Contractor:
Name: OLSEN ELECTRIC INC
Phone: (253) 872-1905
Address: 325 WASHINGTON AVE S #91, KENT,
WA, 98032
License No: OLSENE1931PE
Expiration Date: 10/5/2017
Lender:
Name:
Address:
DESCRIPTION OF WORK:
CORE -DRILL CONCRETE FOR NEW FLOOR BOXES. DEMOLISH ONE EXISTING ELECTRICAL PANEL, AND EXISTING
LIGHTING, POWER/DATA AND SALES FLOOR. INSTSALL NEW POWER/DATA ANDLIGHTING AT SALES FLOOR.
Valuation of single family: $0.00
Fees Collected: $353.34
Valuation of mf/comm: $10,000.00
Type of Work: TENANT IMP
Electrical Service Provided by: PUGEST SOUND ENERGY
Water District: TUKWILA
Sewer District: TUKWILA
Current Codes adopted by the City of Tukwila:
International Building Code Edition:
2015
National Electrical Code:
2014
International Residential Code Edition:
2015
WA Cities Electrical Code:
2014
International Mechanical Code Edition:
2015
WAC 296-46B:
2014
Uniform Plumbing Code Edition:
2015
WA State Energy Code:
2015
International Fuel Gas Code:
2015
Permit Center Authorized Signature:wV MW)c Date:
I hearby certify that I have read and examined this permit and know the same to be true and correct. All
provisions of law and ordinances governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other
state or local laws regulating construction or the performance of work. I am authorized to sign and obtain this
development permi;-rand agree to the conditions attached to this permit.
Signature
Print Nam
Date: to - /q— I4
This permit shall become null and void if the work is not commenced within 180 days for the date of issuance, or if
the work is suspended or abandoned for a period of 180 days from the last inspection.
PERMIT CONDITIONS:
<NONE>
PERMIT INSPECTIONS REQUIRED
Permit Inspection Line: (206) 438-9350
2100
ELECTRICAL FINAL
7003
ROUGH -IN ELECTRICAL
7002
SERVICE
7001
UNDERGROUND/SLAB
CITY OF TUKWILA
Community Development Department
• Permit Center
• 6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
" http://www.TukwilaWA.gov
Electrical Permit No..
Project No.
Date Application Accepted:
Date Application Expires: 22 -% f ��
T
use
ELECTRICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
"Please Print"
SITE LOCATION I
n King Co Assessor's Tax No.: R2 O2 Ll -7 - 001 O
Site Address: - 1 V 10 • 1.u -K c E nie, Nva l l Suite Number: 316 Floor: �
Tenant Name: tl'rx-T New Tenant: .Yes ❑..No
PROPERTY OWNER
Name:
r
Address:
C409 S• 24e 20
City: State: -r b Zip:8 3616
V
CONTACT PERSON - person receiving all project
communication
Name:
SG
Address: t1 VJOce„ 81vd 417S0
City: State: GA Zip: 908
Phone: S62 S Fax:
Qu
Email:
W1.SQ t M
ELECTRICAL CONTRACTOR INFORMATION
Company Name: --Ub
Address:
City: State: Zip:
Phone: Fax:
Contr Reg No.: Exp Date:
Tukwila Business License No.;
Valuation of Project (contractor's bid price): $ 10.� 000
Scope of Work (please provide detailed information): inA -c r-a^r-1ti4Q -Q r- w 66) 2000r U4, Qr
e
K.
0
Will service be altered? ❑ Yes m No Adding more than 50 amps? ❑ Yes m No
Type of Use: Mercantile- cell phone store
Type of work:
❑ New ❑ Addition ❑ Service Change ❑ Remodel m Tenant Improvement
❑ Low Voltage ❑ Generator ❑ Fire Alarm ❑ Telecommunication ❑ Temporary Service
Property Served by:
❑ Puget Sound Energy ❑ Seattle City Light
H:\Applications\Formt-Applications On Line\2014 ApplicationsTlectrical Permit Application Revised 1-1-14.docx
Revised: January 2014
bh
Page I of 2
RESIDENTIAL
NEW RESIDENTIAL SERVICE
❑ New single family dwellings ................................... $152.85
(including an attached garage)
❑ Garages, pools, spas and outbuildings ........................ $81.90 ea
❑ Low voltage systems
(alarm, furnace thermostat) ................................ $59.85 ea
RESIDENTIAL REMODEL AND SERVICE CHANGES
❑ Service change or alteration ......................................
$81.90
(no added/altered circuits)
$80.90
❑ Service change with added/altered circuits .................
$81.90
number of added circuits .......................$11.55
ea
❑ Circuits added/altered without service change ...........
$54.60
(up to 5 circuits)
$10.80 ea
❑ Circuits added/altered without service change ...........
$54.60
(6 or more circuits) ...............................................
$7.65 ea
❑ Meter/mast repair .......................................................
$68.25
❑ Low voltage systems .................................................
$59.85
(alarm, furnace thermostat)
PERMIT APPLICATION NOTES -
MULTI -FAMILY AND COMMERCIAL
Fees are based on the valuation of the electrical contract.
MISCELLANEOUS FEES
❑ Temporary service (residential) .................................
$65.00
❑ Temporary service (generator) ...................................
$80.90
❑ Manufactured/mobile home service ...........................
$86.25
(excluding garage or outbuilding)
❑ Carnivals....................................................................
$80.60
Number of concessions .........................
$10.80 ea
Each ride and generator truck ...............
$10.80 ea
***EFFECTIVE JANUARY 1, 2014 EACH
PERMIT WILL BE ASSESSED A 5%
TECHNOLOGY FEE***
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review — Applications for which no permit is issued within 180 days following the date of application shall expire by limitation
The Building Official may grant one extension of time for an additional period not to exceed 90 days. The extension shall be requested in writing
and justifiable cause demonstrated.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
OR El61;G9PR4GAl6 GONTRA Q
Print
Mailing
Date: O 1 - D'• Za 16
Day Telephone: ZZ 2 • 2-16. S'-'2 Ll 4
) 1*17SD 1--o,
H:Wpplications\Forrns-Applications On Line12014 ApplicationsTlectrical Permit Application Revised 1-1-14.do"
Revised: January 2014
bh
G4 `I c'184 Z
State Zip
Page 2 of 2
DESCRIPTIONS
ACCOUNT QUANTITY
PAID
PermitTRAK
$285.39
EL16-0823 Address: 1010 SOUTHCENTER MALL
Apn: 9202470010
$285.39
ELECTRICAL
$271.80
PERMIT FEE MULTI-FAM/COMM
R000.322.101.00.00 0.00
$271.80
TECHNOLOGY FEE
$13.59
TECHNOLOGY FEE
TOTAL FEES PAID.. . 1
R000.322.900.04.00 0.00
$13.59
Date Paid: Wednesday, September 21, 2016
Paid By: CORNELIA DOREKAMP
Pay Method: CREDIT CARD 01000D
Printed: Wednesday, September 21, 2016 9:10 1 of 1 (r/7"IfV
SYSTElv15
AM
DESCRIPTIONS
PAID
PermitTRAK -
$929.11
D16-0249 Address: 344 SOUTHCENTER MALL
Apn: 9202470010
$811.36
DEVELOPMENT
$811.36
PLAN CHECK FEE
R000.345.830.00.00 0.00
$811.36
EL16-0823 Address: Apn:
$67.95
ELECTRICAL
$67.95
PLAN CHECK FEE
R000.345.832.00.00 0.00
$67.95
M16-0139 Address: 344 SOUTHCENTER MALL
Apn: 9202470010
$49.80
MECHANICAL
$49.80
PLAN CHECK FEE
TOTAL FEES PAID BY RECEIPT: .. 363
R000.322.102.00.00 0.00
$49.80
$929.11
Date Paid: Thursday, September 08, 2016
Paid By: DP INC GENERAL CONTRACTORS
Pay Method: CHECK 4053
Printed: Thursday, September 08, 2016 1:25 PM 1 of 1
p"fSYS7EM5
INSPECTION RECORD
Retain a copy with permit ✓��
INSPECTION NO. PERMIT N0.
4
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd- #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 438-9350
Project: -A�d— 7—
Type of Inspection:
eJ'
Address: (t)
Date Called:
Special Instructions: I
a.
Date Wanted: tC J30.m.
Requester:
Phone No:
C9Approved per applicable codes. 1-1 Corrections required prior to approval.
Inspector: Date.
I 11 {��/ Iit ho h,
El REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
INSPECTION RECORD y�j
Retain a copy with permit 0
INSPEC ION N0. ERMIT N0.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd.., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 438-9350
Project: -Ae�qType
of Inspection:
Al/
Address: Olt�
IQ/Special
Date Called:
Instructions: t
Date Wanted:
a.m.
I Z, p.m.
Requester:
hh&�
Phone No:
MApproved per applicable codes. Corrections required prior to approval.
COMMENTS:
Inspector: Date: lI 't
�� b
El REINSPECTIOIN FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Calt to schedule reinspection.
INSPECTION RECORD
Retain a copy with permit
INSPECTION N0. IIERMIT N0.
CITY OF TUKWILA BUILDING DIVISION
Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-367f-
6300
Permit Inspection Request Line (206) 438-9350
L� Corrections required prior to approval.
REINSPECTIO14 FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection.
INSPECTION RECORD �j
Retain a copy with permit
-OM
INSPECTION NO. PERMIT N0.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 438-9350
Project:
Type of Inspe Iroal-I j
Address: /0(0
Date Called:
Special Instructions:
Date Wanted: ` a.m.
m.
Requester:
Phone No:
FlApproved per applicable codes. t__..J Corrections required prior to approval.
`J paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
INSPECTION RECORD EL'&08�.3
Retain a copy with permit
INSPECTION NO. PERMIT NO. i
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 438-9350
Project:I d T
Type of Inspection'_S
Address`:
U10 �04k
Date Called:
Special Instruction�s:�,
b'�yt�J
Date Wanted: a.m.
Requester:
Phone No:
11 Approved per applicable codes. 11 Corrections required prior to approval.
4
REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
PLAN REVIEW/ROUTING SLIP
PERMIT NUMBER: EL16-0823 DATE: 09/08/16
PROJECT NAME: AT & T
SITE ADDRESS: 1010 SOUTHCENTER MALL
X Original Plan Submittal Revision # before Pbrmit Issued
Response to Correction Letter # Revision # after Permit Issued
DEPARTMENTS:
oi�, Aw �- q,G- t P
Building Division & Fire Prevention ❑ Planning Division ❑
Public Works ❑ Structural ❑ Permit Coordinator ❑
PRELEME NARY REVIEW: DATE: 09/13/16
Not Applicable ❑ Structural Review Required ❑
(no approval/review required)
REVIEWER'S INITIALS:
APPROVALS OR CORRECTIONS:
Approved
C
Corrections Required ❑
(corrections entered in Reviews)
N
REVIEWER'S INITIALS:
DATE:
DUE DATE:
Approved with Conditions X
Denied ❑
(ie: Zoning Issues)
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
12/18/2013
10/11/16
OLSEN ELECTRIC INC
Washington State Deparhnent of
Labor & Industries
OLSEN ELECTRIC INC
Owner or tradesperson
Principals
OLSEN, ERIC S, PRESIDENT
OLSEN, ERIC S, AGENT
Doing business as
OLSEN ELECTRIC INC
I -Ionic. Espanol Contact
Safety & Health
Page 1 of 5
A -Z Index Ifelp MyL&I
Claims & Insurance Workplace Rights Trades & Licensing
325 WASHINGTON AVE S #91
KENT, WA 98032
253-872-1905
KING County
WA UBI No. Business type
602 696 333 Corporation
License
Verify the contractor's active registration / license / certification (depending on trade) and any past violations.
Electrical Contractor Active.
Meets current requirements.
License specialties
GENERAL
License no.
OLSENEI931 PE
Effective — expiration
10/05/2007-10/05/2017
Designated administrator
Active.
OL$EN, ERIC S
Meets current requirements.
License type
License no.
Electrical Administrator
OLSENES9610H
Bond
.._...........
Violation amount
CBIC
$4,000.00
Bond account no.
SI4815
Received by L&I
Effective date
12/28/2009
01/24/2010
Expiration date
Until Canceled
Savings
No savings accounts during the previous 6 year period.
License Violations
Infraction no.
EJACH00948
Satisfied
.................._...
Issue date
RCW/WAC
08/02/2016
19.28.161 RCW
Violation city
Violation amount
KENT
$500.00
Type of violation
https://secure.Ini.wa. gov/verify/Detail.aspx?UBI=602696333 &LIC=OLSENEI931 PE&SAW=
Help us improve
10/19/2016
J
T
N
O
O
1.0
NAMEPLATES
1.0
GROUNDING AND BONDING
BLACK
BROWN
1.1GENERAL:
FURNISH AND MOUNT ON EACH PANEL BOARD/SWITCHBOARD (INCLUDING BRANCH
1_1
GROUND ALL EQUIPMENT PER N.E.C.
BLUE
SWITCHES), LARGE JUNCTION BOX, SAFETY SWITCH, STARTER, REMOTE CONTROL, PUSHBUTTON
NEUTRAL
WHITE
GREY
STATION, AND ALL SIMILAR CONTROLS A NAMEPLATE DESCRIPTIVE OF THE EQUIPMENT OR
1_2
GROUND ALL DRY TYPE TRANSFORMERS AS PER DRAWINGS AND N.E.C.
EQUIPMENT CONTROLLED.
STOP IN ALL OPENINGS CREATED THROUGH FIRE -RATED WALLS, FLOORS, OR CEILINGS.
J
SHALL BE THE EQUAL OF 3M PRODUCTS SCOTCH #35.
1_3
ALL CONDUITS SHALL CONTAIN A CODE -SIZED GROUND WIRE SIZE PER N.E.C. IN ADDITION TO
1.2
PROVIDE BLACK AND WHITE NAMEPLATES CONSTRUCTED FROM LAMINATED PHENOLIC WITH A
THE CONDUCTORS SHOWN ON THE PLANS. WHERE CIRCUIT CONDUCTORS ARE INCREASED IN SIZE
WHITE CENTER CORE. LETTERS SHALL BE ENGRAVED IN THE PHENOLIC TO FORM WHITE
rC
FOR VOLTAGE DROP, THE GROUND WIRE SIZE SHALL BE INCREASE PROPORTIONATELY.
co
LETTERS 3/8" HIGH. FASTEN THE NAMEPLATES WITH SCREWS AND ADHESIVE FASTENER.
4.0
MATERIALS AND WORKMANSHIP
C
1.4
WHERE AN ISOLATED, INSULATED GROUND IS REQUIRED A SEPARATE GREEN GROUND SHALL BE
2.0
MOUNTING ACCESSORIES
4.1ALL
RUN FROM THE PANEL GROUND BUS TO THE ISOLATED GROUND CONNECTION OF THE DEVICE
W
FOR #10AWG AND SMALLER. THHN SHALL NOT BE USED IN WET OR DAMP LOCATIONS.
W
SERVED. IN NO CASE SHALL THE SYSTEM GROUND (WIRE AND ASSOCIATED OUTLET BOXES,
2.1
THIS CONTRACTOR SHALL FURNISH AND INSTALL ALL ANGLE IRON, CHANNEL IRON, RODS,
CONDUIT AND BUILDING STEEL) BE ALLOWED TO CONTACT THE ISOLATED GROUND (GREEN WIRE
1_3
SUPPORTS, HANGERS, CONCRETE OR PLYWOOD REQUIRED TO INSTALL, MOUNT AND SUPPORT
4.2
AND DEVICE GROUND).
7w
ANY ELECTRICAL EQUIPMENT OR DEVICE CALLED FOR ON THE PLANS.
SEVERAL KINDS UNLESS SPECIFIED OR INDICATED ON THE DRAWINGS TO THE CONTRARY.
2 2SUPPORTING
TERIAL SHALL BE COMPLETE WITH HANGERS, CONNECTORS, BOLTS, CLAMPS,
PHALLND
DIVISION 16120 WIRE AND CABLE
DURING EACH PHASE AND AT THE COMPLETION OF THE CONSTRUCTION, THIS CONTRACTOR SHALL
NECESSARY ACCESSOR ES TO MAKE A COMPLETE INSTALLATION. SUPPORTING MATERIA
BIDDING.
REMOVE ALL DEBRIS AND EXCESS MATERIALS CAUSED BY HIS WORK. HE SHALL LEAVE THE AREA
BE GALVANIZED, PAINTED OR OTHERWISE SUITABLY FINISHED. PRODUCTS BY BINKLEY, STEEL CITY
PROVIDE MINIMUM #12 CONDUCTORS, UNLESS OTHERWISE INDICATED.
OF OPERATION BROOM CLEAN.
OR RACO WILL BE ACCEPTABLE.
1.0
WIRE AND CABLE
2_3
ALL SURFACE -MOUNTED EQUIPMENT ON BLOCK WALLS SHALL BE MOUNTED ON 3/4" PLYWOOD
1-1
COLOR CODE CONDUCTORS (EXCEPT CONTROL AND INSTRUMENTATION CONDUCTORS) AS
BACKBOARD. ALL FLOOR -MOUNTED EQUIPMENT SHALL BE INSTALLED ON A 4" HIGH CONCRETE PAD.
CLASS 2.
FOLLOWS.
3.0 EXECUTION
3_1 THE ELECTRICAL WORK FOR CONSTRUCTION PURPOSES SHALL CONFORM TO ALL FEDERAL (OSHA),
STATE, ALL SPECIFIC SAFETY REQUIREMENTS AND THE CURRENT EDITION OF THE NEC.
3_2 CHECK THE HVAC AND PLUMBING SPECIFICATIONS FOR ELECTRICAL REQUIREMENTS AND INCLUDE
THE SAME IN THE CONTRACT COST.
3.3 EQUIPMENT CONNECTIONS, STARTERS, DISCONNECT SWITCHES, CONTROL TRANSFORMERS AND
PUSH-BUTTON STATIONS FOR THE EQUIPMENT FURNISHED BY THE OWNER OR UNDER A SEPARATE
CONTRACT SHALL BE INSTALLED AND CONNECTED UNDER THIS DIVISION, AS INDICATED ON THE
CONTRACT DRAWINGS.
3_4
120/208
277/480
PHASE A
BLACK
BROWN
PHASE B
RED
ORANGE
PHASE C
BLUE
YELLOW
NEUTRAL
WHITE
GREY
GROUND
GREEN
GREEN
3_4
ALL CUTTING, PATCHING, EXCAVATING, BACK FILLING AND CONCRETE WORK RELATED TO THIS
1.1a #12 AND #10 CONDUCTORS SHALL HAVE CONTINUOUS INSULATION COLOR, AS LISTED ABOVE.
CONTRACT WILL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR. THIS CONTRACTOR
r
M
SHALL ASSUME THE RESPONSIBILITY OF PROVIDING THE SLEEVES, CHASES AND OPENINGS
1,1b CONDUCTORS LARGER THAN ABOVE, WHICH DO NOT HAVE CONTINUOUS INSULATION COLOR
NECESSARY FOR THE ELECTRICAL INSTALLATION AND FOR THEIR REPAIR IN AN ACCEPTABLE
SHALL BE COLOR CODED BY APPLICATION OF AT LEAST TWO LAPS OF COLORED TAPE ON
MANNER, AS DETERMINED BY THE ARCHITECT. ALL HOLES SHALL BE CORE -DRILLED. PROVIDE FIRE
EACH CONDUCTOR AT ALL POINTS OF ACCESS INCLUDING JUNCTION BOXES. COLOR TAPE
STOP IN ALL OPENINGS CREATED THROUGH FIRE -RATED WALLS, FLOORS, OR CEILINGS.
J
SHALL BE THE EQUAL OF 3M PRODUCTS SCOTCH #35.
3_5
THIS CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL REQUIRED ACCESS PANELS
0<c�T-
1.1c CONDUCTORS SHALL BE SOFT ANNEALED COPPER INSULATED FOR 600 VOLTS UNLESS
NECESSARY FOR HIS WORK, COORDINATE WITH ARCHITECT PRIOR TO INSTALLATION.
SPECIFICALLY INDICATED OTHERWISE. ALUMINUM CONDUCTORS ARE NOT ALLOWED ON THIS
rC
<
co
PROJECT.
4.0
MATERIALS AND WORKMANSHIP
C
ry
1_2
INSULATION TYPE SHALL BE TYPE THW FOR WIRE SIZES #8 AWG AND LARGER AND THHN OR THWN
4.1ALL
WORK SHALL BE INSTALLED IN A PRACTICAL WORKMANLIKE MANNER BY MECHANICS SKILLED IN
W
FOR #10AWG AND SMALLER. THHN SHALL NOT BE USED IN WET OR DAMP LOCATIONS.
W
THE SEVERAL TRADES NECESSARY
<UJ
1_3
PROVIDE WIRE AND RACEWAY SYSTEM AS DESCRIBED HEREIN AND AS INDICATED ON THE
4.2
ALL MATERIALS SHALL BE NEW AND FREE FROM DEFECTS AND SHALL BE THE BEST OF THEIR
7w
DRAWINGS. METAL -CLAD (MC.) ARMORED CABLE (AC) AND NON-METALLIC SHEATHED CABLE (NMC)
SEVERAL KINDS UNLESS SPECIFIED OR INDICATED ON THE DRAWINGS TO THE CONTRARY.
=U~
SHALL NOT BE PERMITTED UNLESS NOTED SPECIFICALLY OTHERWISE AND APPROVED PRIOR TO
4.3
DURING EACH PHASE AND AT THE COMPLETION OF THE CONSTRUCTION, THIS CONTRACTOR SHALL
06W
BIDDING.
REMOVE ALL DEBRIS AND EXCESS MATERIALS CAUSED BY HIS WORK. HE SHALL LEAVE THE AREA
1_4
PROVIDE MINIMUM #12 CONDUCTORS, UNLESS OTHERWISE INDICATED.
OF OPERATION BROOM CLEAN.
4.4
ALL ELECTRICAL EQUIPMENT SHALL BEAR THE UNDERWRITERS LABORATORIES LABEL OR ETL
1.4a CONTROL CONDUCTORS SHALL BE #14 MINIMUM FOR N.E.C. CLASS 1 AND #16 FOR N.E.C.
CLASS 2.
LABEL.
4_5
THIS CONTRACTOR SHALL GUARANTEE HIS WORKMANSHIP AND MATERIAL (LAMPS EXCEPTED) FOR
1_5
CONDUCTORS #8 AWG AND LARGER SHALL BE STRANDED.
A PERIOD OF ONE YEAR FROM THE DATE OF BUILDING OPENING AND LEAVE HIS WORK IN PERFECT
1.6
CONDUCTORS #10 AWG AND SMALLER SHALL BE SOLD
ORDER AT THE COMPLETION. SHOULD DEFECTS DEVELOP WITHIN THE GUARANTEE PERIOD, THE
-
CONTRACTOR SHALL, UPON NOTICE OF THE SAME, REMEDY THE DEFECTS AND HAVE ALL
1_7
INSTALL ALL WIRING IN CONDUIT.
DAMAGES TO OTHER WORK OR FURNISHINGS CAUSED BY THE REPAIRS CORRECTED AT HIS
EXPENSE TO THE CONDITION BEFORE SUCH DAMAGE.
1.8
CONNECT #10 AND SMALLER WIRES WITH CONSTANT PRESSURE EXPANDABLE SPRING TYPE
CONNECTORS, "SCOTCHLOK" BY 3M OR B -CAP BY BUCHANAN.
5.0
SCOPE OF WORK
1_9
CONNECT #8 AND LARGER WIRES WITH COMPRESSION CONNECTORS OR SPLICES AS
5.1
THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIAL, STORAGE, UNPACKING AND
MANUFACTURED BY BURNDY OR T&B.
PLACEMENT; TO INCLUDE BUT NOT BE LIMITED TO, THE FOLLOWING ITEM:
1.10
INSULATE SPLICING CONNECTORS TO AT LEAST 200% OF THE WIRE INSULATION. USE
5.1a EMERGENCY LIGHTING AND POWER
-
PRE -STRETCHED TUBING CONNECTOR INSULATORS. 3M PST FOR #2 AND LARGER CONDUCTORS.
5.1b COMPLETE POWER AND LIGHTING DISTRIBUTION SYSTEM INCLUDING ALL TRANSFORMERS
1.11
PULL CONDUCTORS USING RECOGNIZED METHODS AND EQUIPMENT LEAVING AS LEAST 6" WIRE AT
AND FEEDERS
ALL JUNCTION BOXES FOR CONNECTIONS.
5.1c COMPLETE BRANCH CIRCUIT WIRING SYSTEM.
1.1 la CLEAN OUT EACH CONDUIT SYSTEM BEFORE PULLING WIRE.
5.1d COMPLETE POWER WIRING FOR ALL AIR CONDITIONING EQUIPMENT, PLUMBING
1,12
FORM AND TIE ALL WIRING IN PANEL BOARDS.
SYSTEM, HEATING EQUIPMENT, VENTILATING AND EXHAUST EQUIPMENT.
1.13
THERE SHALL BE NO WIRE NUT JOINTS OR SPLICES MADE INSIDE SWITCHBOARDS/ PANEL BOARDS.
5.1e COMPLETE LIGHTING FIXTURE INSTALLATION, INCLUDING ALL INCANDESCENT, FLUORESCENT
AND HID LAMPS.
1.14
BRANCH CIRCUIT WIRE SIZES (AND CONDUITS) SHALL BE INCREASED FROM THOSE INDICATED ON
THE PLANS TO PREVENT EXCESSIVE VOLTAGE DROP. BRANCH CIRCUITS SHALL BE INSTALLED WITH
5.1f COMPLETE COMMUNICATIONS CONDUIT AND WIRING SYSTEM INCLUDING BOXES, PLATES,
WIRES OF SUFFICIENT SIZE SO THAT VOLTAGE DROP BETWEEN THE PANEL AND THE LOADS DOES
JACKS, ETC., AS SPECIFIED, SHOWN ON THE DRAWINGS AND REQUIRED BY THE TENANT.
NOT EXCEED LIMIT OF 35.
5_1g TEMPORARY ELECTRICAL POWER AND LIGHTING AS REQUIRED FOR CONSTRUCTION.
1.15
WIRE SIZES SHALL BE BASED ON THE 60°C. AMPACITIES FOR WIRE SIZES NO. 14-1 A.W.G., AND 75°C.
AMPACITIES FOR WIRE SIZES #1/0 A.W.G. AND LARGER.
5.1 h TESTING OF ALL CABLES AND CIRCUIT WIRING AFTER INSTALLATION.
1.16
CIRCUITS MAY BE MULTI-PLEXED IN CONDUIT PROVIDED WIRE IS PROPERLY DERATED AND
5_1 ii EXIT LIGHT SYSTEM.
CONDUIT SIZED PER CODE. UNDER NO CIRCUMSTANCES SHALL MORE THAN (9) CURRENT
CARRYING CONDUCTORS BE RUN 1N A SINGLE CONDUIT.
5.11 WIRING DEVICES AND FLOOR BOXES.
1.17
PROVIDE WIRE AND RACEWAY SYSTEMS AS DESCRIBED HEREIN AND INDICATED ON DRAWINGS.
5.1k LIGHTING CONTROLS.
METAL -CLAD (MC), ARMORED CABLE (AC), AND NON-METALLIC SHEATED CABLE (NMC) SHALL NOT
BE PERMITTED, UNLESS NOTED SPECIFICALLY OTHERWISE AND APPROVED PRIOR TO
5.11GROUNDING OF THE ELECTRICAL SYSTEM.
-
BIDDING.
5.1m FIRE SUPERVISORY ALARM SYSTEM.
5.1 n TELEPHONE AND ELECTRIC SERVICES
5.10 SOUND SYSTEM COMPONENTS, CONDUIT SYSTEM & WIRING
DIVISION 16130 - RACEWAYS AND BOXES
1.0 RACEWAYS
1.1 ALL WIRE SHALL BE RUN IN ACCORDANCE WITH CODE IN CORROSION RESISTANT, RIGID,
THREADED, METAL CONDUIT OR ELECTRICAL METALLIC TUBING (E.M.T.) UNLESS OTHERWISE
SPECIFICALLY STATED HEREIN.
1.2 CONDUIT SIZE SHALL BE 3/4" MINIMUM.
1.3 CONDUIT SHALL BE SECURELY FASTENED IN PLACE.
1.4 ALL CONDUIT SHALL BE CONCEALED IN WALLS, FLOOR AND CEILINGS WHEREVER POSSIBLE.
EXPOSED CONDUIT IN FINISHED AREAS WILL NOT BE PERMITTED. EXPOSED CONDUIT WILL BE
PERMITTED IN UNFINISHED AREAS WITH THE SPECIFIC APPROVAL OF THE ARCHITECT.
1.5USE FLEXIBLE CONDUIT FOR THE CONNECTION TO RECESSED OR SEMI -RECESSED LIGHTING
FIXTURES (6' LENGTH MAXIMUM). USE LIQUID TIGHT METAL CONDUIT FOR ALL CONNECTIONS TO
MOTORS AND OTHER EQUIPMENT SUBJECT TO VIBRATION AND IN AREAS SUBJECT TO MOISTURE.
1_6 USE WATERTIGHT JOINTS WITH BURIED AND CONCRETE ENCASED CONDUIT. ALL BURIED CONDUIT
OUTSIDE OF BUILDINGS SHALL HAVE A MINIMUM OF 24" OF COVER. METAL CONDUITS BURIED IN
EARTH SHALL BE PAINTED (TWO COATS) WITH HEAVY ASPHALTUM PAINT.
1.7 SUPPORT RUNS OF CONDUIT AS DETAILED IN THE APPROPRIATE TABLE OF THE NATIONAL
ELECTRICAL CODE (NEC).
1_8 INSTALL EXPOSED RUNS OF CONDUIT AND CONDUIT ABOVE LAY -IN CEILING PARALLEL OR
PERPENDICULAR TO THE WALLS, STRUCTURAL MEMBERS OF INTERSECTIONS OF VERTICAL PLANES
AND CEILINGS. PROVIDE RIGHT ANGLE TURNS USING FITnINGS OR SYMMETRICAL BENDS. SUPPORT
CONDUITS WITHIN 1" OF ALL CHANGES IN DIRECTION.
1_9 IF A CONDUIT IS SUSPENDED, IT SHALL BE SUPPORTED ON TRAPEZE HANGERS WHICH USE
"ALL -THREAD" RODS FROM THE STRUCTURAL STEEL. THE USE OF CEILING SUPPORT WIRE OR
SIMILAR MATERIAL WILL NOT BE ACCEPTED.
1.10 INSTALL EMPTY CONDUIT FOR FUTURE USE AS INDICATED ON THE DRAWINGS. CONDUIT SHALL BE
COMPLETE WITH JETLINE OR PULL ROPE, JUNCTION/OUTLET BOXES, TILE RINGS AND APPROPRIATE
COVER PLATES.
1.11 PROVIDE PITCH POCKETS WHERE CONDUITS PENETRATE THE ROOF.
1.12 THREAD LUBRICATION/SEALANT IS REQUIRED ON OUTDOOR AND UNDERGROUND THREADED
METAL JOINTS.
1.13 INSTALL FIRE SEAL FITTINGS WHERE CONDUITS PENETRATE CONCRETE FLOOR SLABS OR
MASONRY WALLS REQUIRED TO BE FIRE RATED.
1.14 HORIZONTAL PORTION OF CONDUIT EXPOSED ON THE ROOF AND FEEDING EQUIPMENT SHALL NOT
BE MORE THAN 5'-0" UNLESS THE WRITTEN APPROVAL FROM ARCHITECT OR ENGINEER IS
OBTAINED.
2.0 PULL AND JUNCTION BOXES
2_1 INSTALL PULL AND JUNCTION BOXES WHERE SHOWN ON THE DRAWINGS, AND WHERE REQUIRED
FOR CHANGES IN DIRECTION, AT JUNCTION POINTS, AND TO FACILITATE WIRE PULLING. FURNISH
BOX SIZES IN ACCORDANCE WITH NEC UNLESS LARGERBOXES ARE INDICATED.
2_2 PROVIDE STEEL BOXES AND REMOVABLE COVERS OF CODE GAGE, HOT ROLLED SHEET STEEL, HOT
DIPPED GALVANIZED INSIDE AND OUTSIDE, FOR ABOVE GROUND WORK. FURNISH WEATHERPROOF
BOXES WHEN INSTALLED ABOVE GROUND OUTSIDE.
2_3 PROVIDE CAST IRON BOXES, HOT DIPPED GALVANIZED NSIDE AND OUTSIDE WHERE SHOWN ON
THE DRAWINGS. FURNISH REMOVABLE COVERS WITH GASKETS AND STAINLESS STEEL, BRASS OR
BRONZE SCREWS.
2.4 PROVIDE CONCRETE BOXES FOR UNDERGROUND WORK UNLESS OTHERWISE INDICATED ON THE
DRAWINGS. FURNISH STEEL FRAMES AND COVERS WITH THE COVER ATTACHED TO THE FRAME
WITH HEXAGON HEAD, BRASS OR BRONZE CAP SCREWS, 3/8" IN DIAMETER. PROVIDE A RUBBER
GASKET FOR SEALING BETWEEN THE COVER AND THE FRAME. PAINT THE COVER WITH TWO COATS
OF HEAVY ASPHALTUM.
3.0 OUTLET BOXES
3_1 USE SHEET STEEL BOXES, ZINC COATED OR CADMIUM PLATED, FOR CONCEALED INTERIOR WORK.
3_2 USE CAST BOXES, ZINC -CADMIUM FINISH MALLEABLE IRON, FOR EXPOSED INTERIOR WORK, AND
FOR EXPOSED OR CONCEALED WORK IN WET, DAMP OR EXTERIOR LOCATIONS. CAST BOXES SHALL
BE SERIES FD BY CROUSE HINDS OR APPLETON.
3_3 WALL BOX SIZES (MINIMUM) SHALL BE 4" SQUARE X 2-1/2"DEEP WHERE WALL CONSTRUCTION
PERMITS. WHERE WALL CONSTRUCTION DICTATES, THE WIDTH MAY BE REDUCED TO 2-1/8" OR
1-1/2" UNDER SPECIAL CONDITIONS.
3.4 FIXTURE OUTLETS IN CEILINGS (MINIMUM) SHALL BE 4" OC AGONAL X 1-1/2" DEEP (4-11/16"
OCTAGONAL X 2-1/2" DEEP WHERE REQUIRED TO ACCOMNDDATE LARGER CONDUIT OR LARGER
NUMBER OF WIRES).
3.5 GANG BOXES SHALL BE ONE PIECE (MINIMUM), 2-1/8" DEEP.
3.6 PROVIDE FLUSH FLOOR BOX SERIES 880 BY WIRE MOLD WTH DUPLEX RECEPTACLE FOR WOOD
PLATFORM AT DISPLAY SHOW WINDOWS, BOX WITH COVER PLATE FLANGE: CAT. #880W1-817TCAL
AND BRUSHED ALUMINUM COVER PLATE: CAT. #828R-TCAL WITH FLIP LID TO PROTECT RECEPTACLE
WHEN NOT IN USE. BOTH FLANGE AND COVER PLATE SHALL HAVE BRUSHED ALUMINUM FINISH. UL
SCRUB LISTED.
3_7 FLUSH MOUNT BOXES IN ALL FINISHED WALLS, INSTALL THE PLASTER RINGS IN DRY WALLED
PLASTERED WALLS AND RAISED COVERS AS REQUIRED IN WALLS WITH OTHER FINISHES SO THAT
THE COVER PLATES FIT TIGHTLY AGAINST BOXES OR RINGS. 3/16" MAXIMUM GAPS ARE ALLOWED
FOR NONCOMBUSTIBLE WALLS.
3_8 SUPPORT ALL BOXES TO MAINTAIN PROPER ALIGNMENT AND RIGIDITY.
DIVISION 16140 - WIRING DEVICES
1.0 WIRING DEVICES
1_1 WIRING DEVICE COLOR SHALL BE WHITE, UNLESS OTHERWISE NOTED.
1.2 PROVIDE TOTALLY ENCLOSED, 20 AMPERE, 120/277 VOLT, QUIET A/C GENERAL USE SNAP
SWITCHES.
1.3 SWITCHES SHALL BE SPECIFICATION GRADE AS MANUFACTURED BY HUBBELL, P&S, OR LEMON.
1.4 PROVIDE NEMA CONFIGURATION 5-20R DUPLEX 125 VOLT GROUNDING TYPE RECEPTACLES RATED
FOR 20 AMPERES UNLESS OTHERWISE INDICATED ON THE DRAWINGS.
1.5 RECEPTACLES SHALL BE SPECIFICATION GRADE AS MANUFACTURED BY HUBBELL, P&S OR
LEVITON.
1_6 RECEPTACLES REQUIRING AMPERAGES, VOLTAGES OR CONFIGURATIONS DIFFERENT FROM THE
DUPLEX CONVENIENCE RECEPTACLES ABOVE SHALL BE AS INDICATED ON THE DRAWINGS.
1_7 PROVIDE OTHER RECEPTACLES OF A QUALITY, MATERIAL AND WORKMANSHIP EQUAL TO THAT
SPECIFIED FOR DUPLEX CONVENIENCE RECEPTACLES.
1.8 PROVIDE COVER OR DEVICE PLATES FOR OUTLET BOXES AS FOLLOWS UNLESS OTHERWISE
NOTED:
1.8a FINISHED AREAS: THERMOPLASTIC -COLOR TO MATCH DEVICE.
1.8b UNFINISHED AREAS: ZINC COATED SHEET METAL, ALUMINUM, OR CAST METAL AS
APPROPRIATE FOR THE TYPE OF BOX.
1.8c EXTERIOR AREAS: COPPER FREE ALUMINUM WITH GRAY, POWDER EPDXY FINISH, GASKET,
WEATHERPROOF, CROUSE -HINDS "WLRD" FOR DUPLEX RECEPTACLES AND WLRS FOR SINGLE
RECEPTACLES OR EQUAL.
1.8d TELEPHONE COMMUNICATIONS, AND SIGNAL OUTLET PLATES, SHALL MATCH THOSE USED
FOR RECEPTACLES AND SWITCHES. ALL OUTLET AND/OR JUNCTION BOXES SHALL BE
COMPLETE WITH A COVER PLATE BY THIS CONTRACTOR.
1.8e WHERE DEVICES ARE GANGED, THEY SHALL BE INSTALLED UNDER A COMMON COVER PLATE.
1_9 LOCATE THE SWITCHES APPROXIMATELY 4'-0" ABOVE THE FINISHED FLOOR ELEVATION OR
NEAREST BLOCK COURSE (WITHIN A.D.A. REQUIREMENTS), UNLESS OTHERWISE INDICATED. THE
LONG DIMENSION OF THE SWITCHES SHALL BE VERTICAL.
1.10 LOCATE RECEPTACLES APPROXIMATELY 1'-6" ABOVE THE FINISHED FLOOR ELEVATION OR
NEAREST BLOCK COURSE (WITHIN A.D.A. REQUIREMENTS), UNLESS NOTED OTHERWISE THE LONG
DIMENSION OF RECEPTACLES SHALL BE VERTICAL.
DIVISION 16410 - SAFETY SWITCHES
1.0 SAFETY SWITCHES
1_1 SAFETY SWITCHES SHALL BE THE ENCLOSED HEAVY-DUTY TYPE (TYPE HD) WITH QUICK -MAKE,
QUICK -BREAK MECHANISM AND EXTERNAL PAD LOCKABLE OPERATING HANDLE.
1_2 SAFETY SWITCHES SHALL BE RATED FOR 240 OR 600 VOLTS AS APPLICABLE. THEY SHALL BE
HORSEPOWER RATED WHEN USED IN MOTOR CIRCUITS.
1_3 SAFETY SWITCHES SHALL BE FUSIBLE OR NON -FUSIBLE 2, 3 OR 4 POLE AS INDICATED ON THE
DRAWINGS.
1_4 SAFETY SWITCHES SHALL BE SINGLE THROW UNLESS OTHERWISE INDICATED ON THE DRAWINGS.
1_5 ENCLOSURES SHALL BE NEMA 1 INDOORS AND NEMA 3R OUTDOORS UNLESS OTHERWISE
INDICATED ON THE DRAWINGS.
1_6 MANUFACTURER SHALL BE SQUARE D, SEIMENS OR CULTER-HAMMER.
1_7 MOUNT THE SAFETY SWITCHES SECURELY BETWEEN TX 6' LEVELS ABOVE THE FLOOR UNLESS
OTHERWISE INDICATED ON THE DRAWINGS.
1_8 MOUNT THE SAFETY SWITCHES SECURELY BETWEEN TX T LEVELS ABOVE THE FLOOR UNLESS
OTHERWISE INDICATED ON THE DRAWINGS.
1_9 SWITCHES ON BLOCK WALLS SHALL BE MOUNTED ON A 3/4" PLYWOOD BACKBOARD, WHERE
LOCATED INDOORS.
DIVISION 16420 -MOTOR STARTERS
1.0 MOTOR STARTERS
1_1 PROVIDE MOTOR STARTERS (MAGNETIC OR FUSED COMBINATION) AND CONTROL EQUIPMENT
WHERE SHOWN. STARTERS SHALL BE PROVIDED WITH 120 VOLT COILS, 3 OVERLOADS, CONTROL
TRANSFORMER WITH FUSED 120 VOLT SECONDARY CONTROL CIRCUIT, (2) N.O. AND (2) N.C.
AUXILIARY CONTACTS, HAND -OFF -AUTO SELECTOR SWITCH AND RUNNING PILOT LIGHT, UNLESS
OTHERWISE NOTED. WIRE THRU CONTROL DEVICES FURNISHED BY OTHER TRADES. SINCE MOTOR
DRIVEN EQUIPMENT IS FURNISHED BY OTHER TRADES, THE CONTROL INDICATED ON THE
DRAWINGS SHALL BE CONSIDERED AS FOR BIDDING PURPOSES ONLY. WIRE TO CONFORM TO THE
ACTUAL EQUIPMENT SUPPLIED AND INSTALLED BY THE OTHER TRADES. ALL FUSES SHALL BE DUAL
ELEMENT TYPE. PROVIDE "BLOWN FUSE" INDICATOR LAMPS IN COVER.
1_2 STARTERS SHALL BE SQUARE D, SEIMENS OR CUTLER -HAMMER.
1_3 THE EXACT NUMBER OF NORMALLY OPEN AND NORMALLY CLOSED AUXILIARY CONTACTS IN EACH
STARTER SHALL BE DETERMINED BY THE TEMPERATURE CONTROL AND/OR FIRE ALARM
CONTRACTOR.
i
1.0 LIGHTING CONTROL SYSTEM
1_1 GENERAL INTRODUCTION: THE WORK COVERED IN THIS SECTION IS SUBJECT TO ALL THE
REQUIREMENTS IN THE GENERAL CONDITIONS OF THE SPECIFICATIONS. THE CONTRACTOR SHALL
COORDINATE ALL OF THE WORK IN THIS SECTION WITH ALL OF THE TRADES COVERED IN OTHER
SECTIONS OF THE SPECIFICATION TO PROVIDE A COMPLETE AND OPERABLE SYSTEM.
1.2 DESCRIPTION OF THE WORK:
1.2a THE EXTENT OF THE LIGHTING CONTROL SYSTEM WORK IS INDICATED BY THE DRAWINGS AND
BY THE REQUIREMENTS OF THIS SECTION. IT IS DEFINED TO INCLUDE, BUT NOT BY WAY OF
LIMITATION:
1.2a1 PANELBOARDS CONTAINING INTEGRAL CONTACTORS.
1.2a2 CONTROL ELECTRONICS FOR CONTACTORS AND TIMECLOCKS AND MONITORING THE
STATUS OF THE SYSTEM.
1.20 ASSOCIATED LOW AND LINE VOLTAGE OVERRIDE SWITCHES AND LIGHT SENSORS.
1.2a4 TIMECLOCKS, CONTACTORS.
1.2a5 ANY WORK STATIONS, SOFTWARE AND COMMUNICATIONS HARDWARE.
1.2b SYSTEM INSTALLATION INCLUDES THE FOLLOWING:
1.2b1 WIRING OF BRANCH CIRCUIT CONDUCTORS AND CONTACTORS
1.2b2 INSTALLATION OF EXTERNAL CONTROL DEVICES AND WIRING TO THE CONTROLLER.
1.2b3 INSTALLATION OF COMMUNICATIONS CONDUCTORS AND ASSOCIATED HARDWARE.
1_3 WARRANTY: MANUFACTURER SHALL WARRANT SPECIFIED EQUIPMENT TO BE FREE FROM DEFECTS
IN MATERIALS AND WORKMANSHIP FOR AT LEAST ONE YEAR FROM THE DATE OF INSTALLATION OR
EIGHTEEN MONTHS FROM DATE OF PURCHASE.
2.0 PANELBOARDS
2_1 ACCEPTABLE MANUFACTURERS: SQUARED CUTLER HAMMER SEIMENS G.E. FOR PRICING AND
ORDERING INFORMATION PROVIDE EQUIPMENT AS SPECIFIED HEREIN NO SUBSTITUTIONS
PERMITTED. CONTRACTOR SHALL CONTACT NO LATER THAN 5 DAYS AFTER JOB IS AWARDED TO
ENSURE LEAD TIMES DO NOT AFFECT PROJECT SCHEDULE. PANELBOARDS SHALL BE ENCLOSED
DEAD FRONT SAFETY TYPE WITH FEATURES AND RATINGS AS SCHEDULED ON THE DRAWINGS.
2_2 PANELS KNOWN AS "LOAD CENTERS" ARE UNACCEPTABLE.
2_3 MOLDED CASE CIRCUIT BREAKERS SHALL BE AS SCHEDULED ON THE DRAWINGS AND SPECIFIED IN
THIS DIVISION.
2.4 ALL BUS BARS SHALL BE RECTANGULAR, SOLID COPPER.
2_5 SPACE, WHERE SHOWN IN PANEL SCHEDULES, DESIGNATES SPACE FOR FUTURE PROTECTIVE
DEVICES AND SHALL INCLUDE BUS AND SUPPORT.
2.6 INSTALL CABINETS SO THAT CENTER OF THE TOP BREAKER DOES NOT EXCEED 6'-6" ABOVE THE
FINISHED FLOOR.
2_7 ENTRIES ON DIRECTORY CARDS SHALL BE TYPED, COMPLETE AND ACCURATE.
2_8 ALL BOLTED CONNECTIONS SHALL BE TORQUED IN ACCORDANCE WITH MANUFACTURER'S
STANDARDS.
2_9 ELECTRICAL CONTRACTOR SHALL ARRANGE CIRCUITS AS NEAR AS POSSIBLE TO CIRCUIT NUMBERS
ON THE DRAWINGS. AT COMPLETION OF JOB, ELECTRICAL CONTRACTOR SHALL TAKE CURRENT
READING CHECKS OF RESPECTIVE PHASES. A MINIMUM OF CIRCUIT CONNECTIONS SHALL BE
REARRANGED TO BALANCE AS CLOSELY AS POSSIBLE, THE LOAD IN THE PANEL.
2.10 ALL BREAKERS SHALL BE BOLT -ON TYPE.
2.11 PROVIDE (3) SPARE 1" CONDUITS INTO ACCESSIBLE CEILING SPACE WHERE PANELS ARE
FLUSH -MOUNTED.
3.0 DISTRIBUTION PANELS
3.1 ACCEPTABLE MANUFACTURERS: SQUARE D. CUTLER HAMMER, SEIMENS. G.E.. FOR PRICING AND
ORDERING INFORMATION, PROVIDE EQUIPMENT AS SPECIFIED HEREIN, NO SUBSTITUTIONS
PERMITTED. CONTRACTOR SHALL CONTACT NO LATER THAN 5 DAYS AFTER JOB IS AWARDED TO
ENSURE LEAD TIMES DO NOT AFFECT PROJECT SCHEDULE. DISTRIBUTION PANELS SHALL BE DEAD
FRONT TYPE WITH FEATURES AND RATING AS SCHEDULED ON THE DRAWINGS.
3_2 MOLDED CASE CIRCUIT BREAKERS SHALL BE AS SCHEDULED, OF SIZE AND NUMBER INDICATED ON
THE DRAWINGS. ALL BREAKERS SHALL BE BOLT -ON TYPE.
3_3 ALL LUGS SHALL BE UL APPROVED CU/AL TYPE.
3_4 PANELS SHALL BE MANUFACTURED AS A COMPLETE UNIT AND NOT AN ASSEMBLY OF PARTS
SECURED FROM A SUPPLY HOUSE.
3_5 ALL PANELS SHALL BE CAPABLE OF ACCEPTING CIRCUIT BREAKERS SIZED UP TO AND INCLUDING
400 AMPS.
3_6 VERTICAL BUSSING SHALL BE EXTENDED THE FULL LENGTH OF THE PANEL.
3_7 ALL BUS BARS SHALL BE RECTANGULAR SOLID COPPER.
3_8 DISTRIBUTION PANELS SHALL BE SQUARE D.
3_9 INSTALL PANELS SUCH THAT HANDLE FOR THE TOP BREAKER DOES NOT EXCEED 6'-6" ABOVE
FINISHED FLOOR.
3.10 PROVIDE PHENOLIC LABELS FOR EACH PANEL.
3.11 ALL BOLTED CONNECTIONS SHALL BE TORQUED IN ACCORDANCE WITH MANUFACTURER'S
STANDARDS.
3.12 SURFACE -MOUNTED PANELS SHALL BE MOUNTED ON A 3/4" PLYWOOD BACKBOARD.
FLOOR -MOUNTED PANELS SHALL BE MOUNTED ON A 4" HIGH CONCRETE PAD.
DIVISION 16461 - DRY TYPE TRANSFORMERS
1.0 TRANSFORMERS
1_1 TRANSFORMERS SHALL BE CONTINUOUSLY RATED ISOLATING TYPE FOR 60 HERTZ SERVICE
UNLESS OTHERWISE INDICATED.
1_2 INSULATION SYSTEMS SHALL BE 220 DEGREES C (150 DEGREES RISE).
1_3 ENCLOSURES FOR TRANSFORMERS SHALL BE METALLIC, SUITABLE FOR INDOOR AND OUTDOOR
INSTALLATION AS APPLICABLE AND RODENT PROOF.
1_4 MANUFACTURERS SHALL BE SQUARE D. FRACTIONAL KVA TRANSFORMERS SHALL BE
MANUFACTURED BY EDWARDS OR THE SPECIAL EQUIPMENT MANUFACTURER IN WHICH THE
TRANSFORMERS ARE USED.
1_5 FOUR APPROVED VIBRATION DAMPENERS PER TRANSFORMER SHALL BE EMPLOYED AS
NECESSARY TO AVOID TRANSMITTING ANY VIBRATION TO THE BUILDING STRUCTURE. SIZES OF THE
MOUNTINGS SHALL BE SELECTED ON THE BASIS OF THE WEIGHT OF THE TRANSFORMER, USING:
1.5a A MINIMUM 1" THICK RUBBER -CORK -RUBBER SANDWICH TYPE FOR FLOOR MOUNTING.
1.5b A SPRING TYPE FOR SUSPENSION MOUNTING.
1.5c TWO(2) SPRING TYPE AT THE TOP (WITH TWO (2) STEEL BRACKETS) AND TWO (2) RUBBER -IN
COMPRESSION TYPE AT THE BOTTOM (STAND-OFF) FOR WALL MOUNTING.
COMP I i
NFPA '70 o NE(
SEP 14 2016
ISSUE DATE
LO
co 'SU)
rU)r
y N
(L XON
o ~ixn
t`
�o EGO
m
r>>
�
CO
LO m aC
(0 V) (9 n -
two
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
SEP 08 2016
PERMIT CENTER
P7.
S
x
y
P )7
These drawings/spectfications are the
property of Kamus + Keller. They are
fumished as contract documents only.
The seal(s) and signature(s) appy
only to the documents to which they
affixed, and expressly displaim any
responsibility for all other plans,
specifications, estimates, reports or
other documents or instruments
relating to or intended to be used for
any part or parts of the architectural or
engineering project. Additionally these
drawings and seal(s) shall in no way
convey or imply any time of warranty
or certification retating to the
performance of products and materials
beyond those provided by their
respective manufacturer.
III
PROJECT NO.
16.0430.01
DRAWN/REVIEWED
GFIBB
VIII II III III II I
DATEIISSUE
8.31.2016
SHEET TITLE
ELECTRICAL
SPECIFICATIONS
II I II III IIII
SHEET NO.
E1.1
r
M
W
W
J
0<c�T-
00
00J
1-
rC
<
co
ry
C
ry
UJ
Q
W
I-
W
S'
<UJ
7w
=U~
06W
1-oZ)v
<w0
C)
00
N
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
SEP 08 2016
PERMIT CENTER
P7.
S
x
y
P )7
These drawings/spectfications are the
property of Kamus + Keller. They are
fumished as contract documents only.
The seal(s) and signature(s) appy
only to the documents to which they
affixed, and expressly displaim any
responsibility for all other plans,
specifications, estimates, reports or
other documents or instruments
relating to or intended to be used for
any part or parts of the architectural or
engineering project. Additionally these
drawings and seal(s) shall in no way
convey or imply any time of warranty
or certification retating to the
performance of products and materials
beyond those provided by their
respective manufacturer.
III
PROJECT NO.
16.0430.01
DRAWN/REVIEWED
GFIBB
VIII II III III II I
DATEIISSUE
8.31.2016
SHEET TITLE
ELECTRICAL
SPECIFICATIONS
II I II III IIII
SHEET NO.
E1.1
GENERAL NOTES
1. ELECTRICAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO BASE BID.
IN CASE OF ANY DISCREPANCIES WITH EXISTING FIELD CONDITIONS, ELECTRICAL CONTRACTOR
SHALL VERIFY THE EXACT DIFFERENCE FOR POSSIBLE REVISIONS TO THIS DOCUMENT.
2. INSTALL RECESSED LUMINAIRES USING ACCESSORIES AND FIRE STOPPING MATERIALS TO MEET
REGULATORY REQUIREMENTS FOR FIRE RATING.
3. LIGHT SWITCHES ARE TO BE MOUNTED AT 42" AFF (UNLESS OTHERWISE NOTED).
4. LIGHT FIXTURES ARE TO BE CENTERED ON CEILING TILES (UNLESS OTHERWISE NOTED).
5. CONTACT ARCHITECT TO COORDINATE LIGHT FIXTURE LOCATIONS IF EXISTING CEILING GRID IS
TO BE REUSED.
6. PROVIDE MINIMUM 90 MIN BATTERY PACKS IN EMERGENCY FIXTURES, WHERE INDICATED ON
THE DRAWINGS.
7. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH GENERAL CONTRACTOR AND TENANT
REPRESENTATIVE FOR ORDERING LUMINAIRES FROM TENANTS NATIONAL ACCOUNT WITH
"GRAINGER".
8. PROVIDE BLACK ADHESIVE LABEL ADHERED TO ALL SWITCHED RECEPTACLES WITH 1/4"
LETTERING INDICATING "SWITCHED FOR LIGHTING".
9. COORDINATE TIMING OF TIMECLOCK WITH STORE MANAGER.
10. ON ALL MULTI -WIRED HOMERUN CIRCUIT BREAKERS (REFER TO PLANS) CONTRACTOR SHALL
FIELD INSTALL ON MULTI -USE CIRCUIT BREAKERS AN APPROVED HANDLE TIE PER NEC.
11. ALL EQUIPMENT SHALL BE LISTED BY A NATIONALLY RECOGNIZED TESTING LABORATORY.
12. IT IS ACCEPTABLE TO USE MIC CABLE FOR BRANCH CIRCUITS OR HOMERUNS PROVIDED IT
COMPLIES WITH AUTHORITY HAVING JURISDICTION, LOCAL RECOGNIZED CODE AND LANDLORD.
VERIFY PRIOR TO BID.
13. ALL LOW VOLTAGE WIRING TO BE IN CONDUIT UNLESS OTHERWISE APPROVED BY AUTHORITY
HAVING JURISDICTION
NOTES BY SYMBOL
ONUMBER INDICATES CIRCUIT COORDINATION, LETTER INDICATES SWITCH COORDINATION.
REFER TO LIGHTING CONTROL DETAIL ON SHEET E1.0.
OALL EMERGENCY/EXIT FIXTURES ARE TO BE PROVIDED WITH MINIMUM 90 MIN EMERGENCY
BATTERY BACK-UP AND CONNECTED TO UNSWITCHED LEG OF LOCAL CIRCUIT. BY=PASS
ENERGY MANAGEMENT SYSTEM WHERE REQUIRED).
OALL LIGHTING CIRCUITS INDICATED ON PLANS SHALL BE ROUTED THROUGH THE LIGHTING
CONTROL SYSTEM. REFER TO LIGHTING LIGHTING CONTROL DIAGRAM ON SHEET E1.0
FOR ADDITIONAL INFORMATION.
4OSWITCHBANK LOCATION. REFER TO SWITCHBANK DETAIL ON THIS SHEET AND LIGHTING
CONTROL DIAGRAM ON SHEET E1.0 FOR ADDITIONAL INFORMATION.
OELECTRICAL DISTRIBUTION EQUIPMENT. REFER TO SHEET E3.0 FOR FURTHER COORDINAT
OEXISTING BOH LIGHTING AND SWITCHING TO REMAIN. RE -LAMP, REPAIR, RE -BALLAST AS
NEEDED TO PROVIDE FULLY FUNCTIONING FIXTURES
7O CONNECT TO EXISTING BOH CIRCUIT AND SWITCHING. V.I.F.
SWITCHBANK DETAIL
'a' �b� �'d'
>- Y
Q Q U
Wz
N 0
t7 O
NOTE:
SWITCH CONTROL LOCATION. REFER TO SHEET E1.0 LIGHTING CONTROL DETAIL FOR NUMBER OF
POLES REQUIRED. SWITCHES SHALL BE INSTALLED BETWEEN STUDS. MAKE (MORE) ROWS IF
NECESSARY. DO NOT CUT STUDS TO ACCOMMODATE A SINGLE ROW OF SWITCHES.
ALL CONTROL DEVICES FOR LIGHT, POWER, HEAT, ALARMS, ETC. SHALL BE MOUNTED NO HIGHER
THAN 42" FROM THE FLOOR.
IMPORTANT:
T.G.C. SHALL CONNECT EMERGENCY/NIGHT LIGHTING TO LOCAL CIRCUIT ON UNSWITCHED LEG.
SCALE: 1/4"=l' -O"
REVIEWED RUH'
COMPLIANCE , .J e A,H
NFPA70 - NEC
SEP 14 2016
City of TuWla
BUILDING DIVISION
A)1rrff11 A
w• • • w• • w•��
SEP 08 2016
PERMIT CENTER
ISSUE DATE
C- �
r-nOD
co N r
�
0 ~r
aO m N
C)
m Q.
� �� 9
mfnc0(LLL
These dreviings/specifications are the
property of Kamus + Keller. They are
fumished as contract documents only.
The seal(s) and signature(s) apply
only to the documents to which they
affixed, and expressly displaim any
responsibility for all other plans,
specifications, estimates, reports or
other documents or instruments
relating to or Intended to be used for
any part or parts of the architectural or
engineering project. Additionally these
drawings and seal(s) shaft in no way
convey or imply any time of warranty
or certification relating to the
performance of products and materials
beyond those provided by their
respective manufacturer.
PROJECT NO.
16.0430.01
DRAWN/REVIEWED
GFIBB
DATE/ISSUE
8.31.2016
SHEET TITLE
ELECTRICAL
LIGHTING PLAN
SHEET NO.
E2.0
r
M
W
F_
UJ
(!
U)
_jry
0
Q
QD
0)
Q
wW
<
w
UJ
_J
Q
06
own
<U)0
U)
0
00
N
These dreviings/specifications are the
property of Kamus + Keller. They are
fumished as contract documents only.
The seal(s) and signature(s) apply
only to the documents to which they
affixed, and expressly displaim any
responsibility for all other plans,
specifications, estimates, reports or
other documents or instruments
relating to or Intended to be used for
any part or parts of the architectural or
engineering project. Additionally these
drawings and seal(s) shaft in no way
convey or imply any time of warranty
or certification relating to the
performance of products and materials
beyond those provided by their
respective manufacturer.
PROJECT NO.
16.0430.01
DRAWN/REVIEWED
GFIBB
DATE/ISSUE
8.31.2016
SHEET TITLE
ELECTRICAL
LIGHTING PLAN
SHEET NO.
E2.0
GENERAL NOTES
1. ELECTRICAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO BASE BID.
IN CASE OF ANY DISCREPANCIES WITH EXISTING FIELD CONDITIONS, ELECTRICAL CONTRACTOR
SHALL VERIFY THE EXACT DIFFERENCE FOR POSSIBLE REVISIONS TO THIS DOCUMENT.
2. INSTALL RECESSED LUMINAIRES USING ACCESSORIES AND FIRE STOPPING MATERIALS TO MEET
REGULATORY REQUIREMENTS FOR FIRE RATING.
3. LIGHT SWITCHES ARE TO BE MOUNTED AT 42" AFF (UNLESS OTHERWISE NOTED).
4. LIGHT FIXTURES ARE TO BE CENTERED ON CEILING TILES (UNLESS OTHERWISE NOTED).
5. CONTACT ARCHITECT TO COORDINATE LIGHT FIXTURE LOCATIONS IF EXISTING CEILING GRID IS
TO BE REUSED.
6. PROVIDE MINIMUM 90 MIN BATTERY PACKS IN EMERGENCY FIXTURES, WHERE INDICATED ON
THE DRAWINGS.
7. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH GENERAL CONTRACTOR AND TENANT
REPRESENTATIVE FOR ORDERING LUMINAIRES FROM TENANTS NATIONAL ACCOUNT WITH
"GRAINGER".
8. PROVIDE BLACK ADHESIVE LABEL ADHERED TO ALL SWITCHED RECEPTACLES WITH 1/4"
LETTERING INDICATING "SWITCHED FOR LIGHTING".
9. COORDINATE TIMING OF TIMECLOCK WITH STORE MANAGER.
10. ON ALL MULTI -WIRED HOMERUN CIRCUIT BREAKERS (REFER TO PLANS) CONTRACTOR SHALL
FIELD INSTALL ON MULTI -USE CIRCUIT BREAKERS AN APPROVED HANDLE TIE PER NEC.
11. ALL EQUIPMENT SHALL BE LISTED BY A NATIONALLY RECOGNIZED TESTING LABORATORY.
12. IT IS ACCEPTABLE TO USE M/C CABLE FOR BRANCH CIRCUITS OR HOMERUNS PROVIDED IT
COMPLIES WITH AUTHORITY HAVING JURISDICTION, LOCAL RECOGNIZED CODE AND LANDLORD.
VERIFY PRIOR TO BID.
13. ALL LOW VOLTAGE WIRING TO BE IN CONDUIT UNLESS OTHERWISE APPROVED BY AUTHORITY
HAVING JURISDICTION
NOTES BY SYMBOL
ONUMBER INDICATES CIRCUIT COORDINATION, LETTER INDICATES SWITCH COORDINATION. ALL
MVU LIGHTING CIRCUITS SHALL BE ROUTED THROUGH ENERGY MANAGEMENT SYSTEM. REFEF
TO LIGHTING CONTROL DETAIL ON SHEET E1.0
OELECTRICAL CONTRACTOR TO COORDINATE WITH TELEPHONE/DATA SYSTEM INSTALLER
CONDUIT SIZE, REQUIREMENTS AND ROUTING OF TEUDATA CONDUIT IN FIELD PRIOR TO
ROUGH -IN.
OELECTRICAL CONTRACTOR SHALL COORDINATE WITH ARCHITECTURAL MILLWORK DETAILS
FOR FINAL LOCATION OF ALL DEVICES AND TEUDATA CONDUIT AT MILLWORK. INCLUDE ALL
J -BOXES, TWO CHANNEL WIREMOLDS AND REQUIRED CONDUITS FOR LINE AND LOW
VOLTAGE AS PART OF BASE BID IN ORDER TO OBTAIN A COMPLETE AND OPERATING SYSTEM.
OPROVIDE FLUSH FLOOR MOUNTED POWER AND TEUDATA DEVICE AT LOCATION INDICATED
ON THE PLANS. PROVIDE FLOOR BOX AND CORRESPONDING ACCESSORIES REQUIRED PER
FIELD CONDITIONS (BLACK COVER FOR CARPET FLOORING AND BRASS COVER FOR ALL
OTHER FINISHES.
O5 CORE FLOOR FOR INSTALLATION OF NEW CONDUITS. PROVIDE CONDUIT AS SHOWN WITH
PULL STRING FOR DATA CABLING AND 3/4" CONDUIT WITH POWER WIRING TO FLOOR BOX
RECEPTACLES. FIELD VERIFY ROUTING OF CONDUIT PRIOR TO CUTTING FLOOR. PATCH TO
MATCH EXISTING. COORDINATE WITH FURNITURE SUPPLIER AND ARCHITECTURAL DIMENSION
PLAN PRIOR TO SAW -CUTTING FLOOR. ALL FLOOR MOUNTED DEVICES MUST MEET "SCRUB
WATER TEST'.
OAT THIS LOCATION, STUB CONDUITS UP THROUGH WALL. ALL TEUDATA CONDUITS SHALL BE
STUBBED INTO ACCESSIBLE CEILING SPACE ABOVE. FINAL PLACEMENT OF CONDUITS
STUB -UP AT FLOOR SHALL BE COORDINATED WITH TENANT REPRESENTATIVE PRIOR TO
INSTALLATION
OELECTRICAL CONTRACTOR SHALL PROVIDE DUAL BRANCH CIRCUIT QUAD RECEPTACLES
BEHIND MVU. HALF OF QUAD FOR GENERAL POWER AND HALF FOR SWITCHING. REFER TO
GENERAL NOTES 8 AND 10 ABOVE.
OELECTRICAL DISTRIBUTION EQUIPMENT. REFER TO SHEET E3.0 FOR FURTHER
COORDINATION.
OELECTRICAL CONTRACTOR TO MAKE FINAL CONNECTION TO TENANT SIGN. IF NOT EXISTING,
PROVIDE MEANS OF DISCONNECT AND SEPARATE GROUND PER NEC (CONDUIT GROUND NOT
PERMITTED). CIRCUIT SIGN VIA TIMECLOCK, REFER TO LIGHTING CONTROL DIAGRAM ON
SHEET E1.0.
10 PROVIDE 24"w x 36"h x 6"d TELEPHONE CABINET, 3/4" THICK FIRE RETARDANT PLYWOOD. PAINT
EXPOSED SIDE WITH ADJACENT WALL COLOR. PROVIDE GROUND BUS, 3/4" CONDUIT WITH (1)
#6 GROUND TO LIFER GROUND. PROVIDE QUAD RECEPTACLE AND CIRCUIT AS INDICATED.
11 EXISTING MEANS OF DISCONNECT AND ALL ASSOCIATED ELECTRICAL FOR WATER HEATER
TO REMAIN
12 EXISTING NON-FUSED DISCONNECT, WP/GF) RECEPTACLE, AND DUCT MOUNTED SMOKE
DETECTOR TO REMAIN. REFER TO PANEL SCHEDULE AND RISER DIAGRAM ON SHEET E3.0
ADDITIONAL INFORMATION. V.I.F.
13 EXISTING RECEPTACLE TO REMAIN
14 PROVIDE POWER AND KEYED SWITCHES FOR ROLLING GRILLE. COORDINATE SPEC AND FINAL'
SWITCH LOCATIONS WITH ARCHITECT
15 EXISTING T -STATS TO REMAIN
WIN
(E)
I L
SH I 42
L
26
X60" Lit
10 24
I L �
34
I
i(TYPICAL)
QMI
L
L 23 20,22
IC3 31,33
mC �mL�3� 1 I _ ,
EAR fA!LUE-T 18 MI
MWU MWU FSLS '
c�
.J�
5
(TYPICAL)
AHU-1
12
2L
7/29
(TYPICAL)
AATV-BENCH
AHU-2
L 12
19,21 L
CU -2 CU -1
12 12
L L
36/38/40 28/30
MWU
i, ,
Ems:_
:..
LT -S
2
M — — —
20 LT -D
CLG
LT -S
(TYPICAL)
MWU
L
31,3.
a
m
'-SLT-C
T -D 22 LT -ADA
--S LT -C
(TYPICAL) (TYPICAL)
MWU MWU
SPT1-
4
19 c _ 1
3 i■' 1 fir' ,.A4,4U, 11
i � ■!_ ■ �
SCALE: 1/4"=I'-0"
MWU
BP
L
12
D
12
MPOS
L
� i17
NOTE:
A FIRE ALARM SYSTEM IS REQUIRED
FOR THIS LOCATION. T.G.C. TO HIRE A
LANDLORD APPROVED FIRE
PROTECTION CONTRACTOR TO PROVIDE
FIRE PROTECTION PLANS UNDER A
SEPERATE SUBMITTAL.
RS
MWU
MWU
Ell- �
i�-alp
(2)D V
CLG
JE®
AWILA
2016
:ENTER
ISSUE DATE
mco
I- m
a ; 00
: F-7 j
CL mrN
m oco
m M N m
�j C Lr
� � P='�
(o U) a tL
L
N
O
C
C
Q)
C
U)
C
O
U
■
C
C
N
O-
C
O
a
These drawings/specifications are the
property of Kamus + Keller. They are
furnished as contract documents only.
The seal(s) and signature(s) appy
only to the documents to which they
affixed, and expressly displatm any
responsibility for all other plans,
spectfications, estimates, reports or
other documents or instruments
relating to or intended to be used for
any part or parts of the architectural or
engineering project. Additionally these
drawings and seal(s) shall in no way
convey or Imply any time of warranty
or certification relating to the
performance of products and materials
beyond those provided by their
respective manufacturer.
PROJECT NO.
16.0430.01
DRAWN/REVIEWED
GF1BB
DATEIISSUE
8.31.2016
SHEET TITLE
ELECTRICAL
POWER PLAN
SHEET NO.
E2.1
Cfl
M
W
UJ
U)
Octc
G
Jarmo
0
Q
WI—
W
S�
�CWzW
W
=W06
�
D
<C
0
to
(n
0
W
0
00N
These drawings/specifications are the
property of Kamus + Keller. They are
furnished as contract documents only.
The seal(s) and signature(s) appy
only to the documents to which they
affixed, and expressly displatm any
responsibility for all other plans,
spectfications, estimates, reports or
other documents or instruments
relating to or intended to be used for
any part or parts of the architectural or
engineering project. Additionally these
drawings and seal(s) shall in no way
convey or Imply any time of warranty
or certification relating to the
performance of products and materials
beyond those provided by their
respective manufacturer.
PROJECT NO.
16.0430.01
DRAWN/REVIEWED
GF1BB
DATEIISSUE
8.31.2016
SHEET TITLE
ELECTRICAL
POWER PLAN
SHEET NO.
E2.1
U)
0
Z
v
ii
W
W
MOTES BY SYMBOL
LI+7-2LBCW--4'—' (3)D (1)T — — —
t" CONDUIT FOR
POWER PER TABLE.
1" CONDUIT FOR DATA
PER TABLE.
2" CONDUIT FOR (1) HDMI„
(2) USB, PER TABLE
0 EXISTING METER BASE AND METER SOCKET TO REMAIN.
0 EXISTING 200 AMP BREAKER TO REMAIN.
OEXISTING (4) #3/0 THWN CU, (1) #4 GROUND IN EXISTING CONDUIT TO REMAIN.
4O EXISTING CONDUIT COMPLETE WITH PULL STRING FOR TELEPHONE SERVICE FROM
LANDLORD DMARC STUBBED INTO TENANT SPACE. INTERCEPT AND ROUTE CONDUIT TO
TENANT PHONE BOARD LOCATION.
OEXISTING 60 AMP NON-FUSED DISCONNECT TO REMAIN
OEXISTING 30 AMP NON-FUSED DISCONNECT TO REMAIN
OEXISTING (2) #8 THWN CU (1) #10 GROUND IN EXISTING CONDUIT
OEXISTING (3) #10 THWN CU (1) #10 GROUND IN EXISTING CONDUIT
OEXISTING (2) #12 THWN CU (1) #10 GROUND IN EXISTING CONDUIT
W
REF.
WIREMOLD
I -1 wLIJ
2" CONDUIT STUB -UP BEHIND
FIXTURE (OUTSIDE OF WALL),
FLUSH WITH CONCRETE
I ` =
t
.EGIRAND RFB4E
2,CONDUIT STgB-UP NEXT TO
LOOR BOX, PE TABLE
GENERAL NOTES
1. 120/208 VOLT 4 WIRE EXISTING ELECTRICAL SERVICE
NOTE: RECEPTACLES @ BACKWRAP AND
LEARNING TABLE TO BE ON A SINGLE 20
AMP DEDICATED CIRCUIT. DO NOT ADD
OTHER RECEPTACLES TO CIRC.
NOTE: IF LEARNING TABLES ARE TO BE
TEMPORARILY USED AS POS STATIONS,
THE 2" CONDUIT SHOWN IN ENLARGED
PLAN IS REQUIRED IN ORDER TO PROVIDE
HDMI AND USB CORDS AND AMPLIFIER
FROM THE BACKWRAP TO THE LEARNING
TABLE.
THE HDMI, USB, AND AMPLIFIER SHOUDL BE
ORDERED THROUGH GRAINGER AS
REQUIRED.
POWER/ DATA ENLARGED PLAN @ BCW & LT
CU -1—M5
I
CU-2�
7 8 AHU-1
II I 7 AHU-2
I
II 119
III TC
I EXISTING
PANEL i Cl
I I
L ----J
Ifl JAM!"',
I Imo; 14+4
5r•
i
2. TENANTS GENERAL CONTRACTOR SHALL PROVIDE AND INSTALL ALL COPPER CONDUCTORS
WHEN NEW IS REQUIRED
3. VERIFY ALL EXISTING CONDITIONS IN FIELD. ALL UPGRADES REQUIRED BY CODES, LANDLORD
OR TENANT SHALL BE BY TENANT AT TENANTS EXPENSE.
4. CONTRACTOR TO VERIFY ALL METERING REQUIREMENTS WITH LANDLORD AND LOCAL UTILITY
PRIOR TO BID.
5. CONTRACTOR TO VERIFY EXACT DISTANCE AND ROUTING OF SERVICE FEEDERS FROM
LANDLORD DISTRIBUTION/ SERVICE EQUIPMENT TO TENANT SPACE PRIOR TO BIDDING.
HOMERUNS AND BRANCH WIRING FOR 20 AMP CIRCUITS SHALL
ELECTRICAL LOAD
BE AS FOLLOWS:
LENGTH
CIRCUIT WIRE SIZE HOMERUN WIRE SIZE
1 FT TO 50FT
NO.12 AWG
NO.12 AWG
51 FT TO 75FT
NO.12 AWG
NO.10 AWG
76FT TO 120FT
NO.10 AWG
NO.8 AWG
121 FT TO 190FT
NO.10 AWG
NO.6 AWG
191 FT TO 30OFT
NO.10 AWG
NOA AWG
SCALE: N.T.S.
NOTE REGARDING EXAMINATION OF PREMISES/FIELD CONDITIONS:
PRIOR TO SUBMITTING PROPOSALS FOR THE WORK, EACH BIDDER IS
REQUIRED TO HAVE EXAMINED THE PREMISES AND VERIFY THE EXISTING
FIELD CONDITIONS. THE EXISTING CONDITIONS HAVE BEEN EXAMINED IN THE
FIELD BY TENANT REPRESENTATIVE'S AND ARE BELIEVED TO BE DEPICTED IN
A ACCURATE MANNER AS THEY EXIST.
IF THE BIDDER FINDS THAT THAT THERE ARE DISCREPANCIES BETWEEN THE
EXISTING CONDITIONS AND THE INFORMATION SHOWN ON THESE DRAWINGS,
THEY SHOULD NOTIFY THE TENANTS REPRESENTATIVE OF THOSE
DISCREPANCIES. IF THESE INSTRUCTIONS ARE IGNORED, THE CONTRACTOR
SHALL BE RESPONSIBLE FOR FURNISHING ALL THE EQUIPMENT REQUIRED
FOR A COMPLETE AND FUNCTIONING ELECTRICAL SYSTEM AT NO ADDITIONAL
COST TO TENANT.
NOTE REGARDING ELECTRICAL DISTRIBUTION SYSTEM:
THE ELECTRICAL RISER DIAGRAM INDICATED HAS BEEN PROPERLY DESIGNED
TO ACCOMMODATE TENANTS POWER REQUIREMENTS AND MEETS ALL
APPLICABLE BUILDING CODES. IT IS THE RESPONSIBILITY OF THE G.C. TO
VERIFY ALL EXISTING CONDITIONS AND DETERMINE IF ANY EXISTING
EQUIPMENT AND WIRING IS SUITABLE FOR REUSE IN THE SYSTEM PRIOR TO
BIDDING.
G.C. SHALL PERFORM ALL WORK NECESSARY TO RESULT IN A COMPLETE AND
LEGAL INSTALLATION INCLUDING THE UPGRADING AND/OR MODIFICATION OF
THE EXISTING SERVICE FEEDERS, CONDUITS AND TAP -INS EXTENDED TO
PROPER POINT OF ORIGIN AS COORDINATED WITH THE LANDLORD.
NOTES: I TOTAL AMPS @1201208V 3PH 128.24
1. 100% OF FIRST 10,000 WATTS, PLUS. 50% OF REMAINING LOAD.
2. 100% OF A/C LOAD (COOLING VS HEATING) PLUS 25% OF LARGEST MOTOR.
REVIEWED FOR
COMPLIANCE 1 'ITH
NFPA 7n A NEC
SEP 14: 2016
City of-T'ukWl1a
BUILDING DIVISInN
RECEIVED
CITY OF TUKWILA
SEP 0 8 2016
PERMIT CENTER
ISSUE DATE
T
S
Sr r 00
T
ti C
0 r
rN'
CL
o C 00
m CO m
9 C m
ur):n) > Lo��
L
ai
CZ
c
a�
t»
r_
0
0
c
c
cv
CL
C
0
ELECTRICAL LOAD
S MMA■ iY
1201208V 3PH - 4W
LOAD DESCRIPTION
CONNECTED VA
FACTOR DEMAND VA
VOLTAGE
PHASE
LIGHTING
4,537
1.25
5,671
120
1
RECEPTACLES
9,280
NOTE # 1
9,280
120
1
SHOW WINDOW RECEPTACLE:
0
1.25
0
120
1
MECHANICAL
23,984
NOTE # 2
24,715
208
3
SIGN LIGHTING
1,200
1.25
1,500
120
1
WATER HEATERS
31600
1.25
4,500
120
1
MISCELLANEOUS
500
1.00.
500
120
1
TOTAL
43,101
46,166
208
3
NOTES: I TOTAL AMPS @1201208V 3PH 128.24
1. 100% OF FIRST 10,000 WATTS, PLUS. 50% OF REMAINING LOAD.
2. 100% OF A/C LOAD (COOLING VS HEATING) PLUS 25% OF LARGEST MOTOR.
REVIEWED FOR
COMPLIANCE 1 'ITH
NFPA 7n A NEC
SEP 14: 2016
City of-T'ukWl1a
BUILDING DIVISInN
RECEIVED
CITY OF TUKWILA
SEP 0 8 2016
PERMIT CENTER
ISSUE DATE
T
S
Sr r 00
T
ti C
0 r
rN'
CL
o C 00
m CO m
9 C m
ur):n) > Lo��
L
ai
CZ
c
a�
t»
r_
0
0
c
c
cv
CL
C
0
These drawings/specifications are the
property of Kamus + Keller. They are
furnished as contract documents only.
The seal(s) and signature(s) apply
only to the documents to which they
affixed, and expressly dispiaim any
responsibility for all other plans,
specifications, estimates, reports or
other documents or Instruments
relating to or intended to be used for
any part or parts of the architectural or
engineering project. Additionally these
drawings and seal(s) shall in no way
convey or imply any time of warranty
or certification relating to the
performance of products and materials
beyond those provided by their
respective manufacturer.
III I
PROJECT NO.
16.0430.01
DRAWN/REVIEWED
GFIBB
DATE/ISSUE
8.31.2016
SHEET TITLE
ELEC PANEL
SCHEDULES &
RISER DIAGRAM
I,I�IIII VIII
SHEET NO.
E3.0
(0
Ir—
co M
W
W
U3
OQ_j°r°
_i
OO
0ol
WW�<
J
z
W
WW
UW
Z
J
UI~—
°6
Z)
I—
W
d�o�
U)
O
00
(N
These drawings/specifications are the
property of Kamus + Keller. They are
furnished as contract documents only.
The seal(s) and signature(s) apply
only to the documents to which they
affixed, and expressly dispiaim any
responsibility for all other plans,
specifications, estimates, reports or
other documents or Instruments
relating to or intended to be used for
any part or parts of the architectural or
engineering project. Additionally these
drawings and seal(s) shall in no way
convey or imply any time of warranty
or certification relating to the
performance of products and materials
beyond those provided by their
respective manufacturer.
III I
PROJECT NO.
16.0430.01
DRAWN/REVIEWED
GFIBB
DATE/ISSUE
8.31.2016
SHEET TITLE
ELEC PANEL
SCHEDULES &
RISER DIAGRAM
I,I�IIII VIII
SHEET NO.
E3.0
J
T
N
O
O
1.0
NAMEPLATES
1.0
GROUNDING AND BONDING
BLACK
BROWN
1.1GENERAL:
FURNISH AND MOUNT ON EACH PANEL BOARD/SWITCHBOARD (INCLUDING BRANCH
1_1
GROUND ALL EQUIPMENT PER N.E.C.
BLUE
SWITCHES), LARGE JUNCTION BOX, SAFETY SWITCH, STARTER, REMOTE CONTROL, PUSHBUTTON
NEUTRAL
WHITE
GREY
STATION, AND ALL SIMILAR CONTROLS A NAMEPLATE DESCRIPTIVE OF THE EQUIPMENT OR
1_2
GROUND ALL DRY TYPE TRANSFORMERS AS PER DRAWINGS AND N.E.C.
EQUIPMENT CONTROLLED.
STOP IN ALL OPENINGS CREATED THROUGH FIRE -RATED WALLS, FLOORS, OR CEILINGS.
J
SHALL BE THE EQUAL OF 3M PRODUCTS SCOTCH #35.
1_3
ALL CONDUITS SHALL CONTAIN A CODE -SIZED GROUND WIRE SIZE PER N.E.C. IN ADDITION TO
1.2
PROVIDE BLACK AND WHITE NAMEPLATES CONSTRUCTED FROM LAMINATED PHENOLIC WITH A
THE CONDUCTORS SHOWN ON THE PLANS. WHERE CIRCUIT CONDUCTORS ARE INCREASED IN SIZE
WHITE CENTER CORE. LETTERS SHALL BE ENGRAVED IN THE PHENOLIC TO FORM WHITE
rC
FOR VOLTAGE DROP, THE GROUND WIRE SIZE SHALL BE INCREASE PROPORTIONATELY.
co
LETTERS 3/8" HIGH. FASTEN THE NAMEPLATES WITH SCREWS AND ADHESIVE FASTENER.
4.0
MATERIALS AND WORKMANSHIP
C
1.4
WHERE AN ISOLATED, INSULATED GROUND IS REQUIRED A SEPARATE GREEN GROUND SHALL BE
2.0
MOUNTING ACCESSORIES
4.1ALL
RUN FROM THE PANEL GROUND BUS TO THE ISOLATED GROUND CONNECTION OF THE DEVICE
W
FOR #10AWG AND SMALLER. THHN SHALL NOT BE USED IN WET OR DAMP LOCATIONS.
W
SERVED. IN NO CASE SHALL THE SYSTEM GROUND (WIRE AND ASSOCIATED OUTLET BOXES,
2.1
THIS CONTRACTOR SHALL FURNISH AND INSTALL ALL ANGLE IRON, CHANNEL IRON, RODS,
CONDUIT AND BUILDING STEEL) BE ALLOWED TO CONTACT THE ISOLATED GROUND (GREEN WIRE
1_3
SUPPORTS, HANGERS, CONCRETE OR PLYWOOD REQUIRED TO INSTALL, MOUNT AND SUPPORT
4.2
AND DEVICE GROUND).
7w
ANY ELECTRICAL EQUIPMENT OR DEVICE CALLED FOR ON THE PLANS.
SEVERAL KINDS UNLESS SPECIFIED OR INDICATED ON THE DRAWINGS TO THE CONTRARY.
2 2SUPPORTING
TERIAL SHALL BE COMPLETE WITH HANGERS, CONNECTORS, BOLTS, CLAMPS,
PHALLND
DIVISION 16120 WIRE AND CABLE
DURING EACH PHASE AND AT THE COMPLETION OF THE CONSTRUCTION, THIS CONTRACTOR SHALL
NECESSARY ACCESSOR ES TO MAKE A COMPLETE INSTALLATION. SUPPORTING MATERIA
BIDDING.
REMOVE ALL DEBRIS AND EXCESS MATERIALS CAUSED BY HIS WORK. HE SHALL LEAVE THE AREA
BE GALVANIZED, PAINTED OR OTHERWISE SUITABLY FINISHED. PRODUCTS BY BINKLEY, STEEL CITY
PROVIDE MINIMUM #12 CONDUCTORS, UNLESS OTHERWISE INDICATED.
OF OPERATION BROOM CLEAN.
OR RACO WILL BE ACCEPTABLE.
1.0
WIRE AND CABLE
2_3
ALL SURFACE -MOUNTED EQUIPMENT ON BLOCK WALLS SHALL BE MOUNTED ON 3/4" PLYWOOD
1-1
COLOR CODE CONDUCTORS (EXCEPT CONTROL AND INSTRUMENTATION CONDUCTORS) AS
BACKBOARD. ALL FLOOR -MOUNTED EQUIPMENT SHALL BE INSTALLED ON A 4" HIGH CONCRETE PAD.
CLASS 2.
FOLLOWS.
3.0 EXECUTION
3_1 THE ELECTRICAL WORK FOR CONSTRUCTION PURPOSES SHALL CONFORM TO ALL FEDERAL (OSHA),
STATE, ALL SPECIFIC SAFETY REQUIREMENTS AND THE CURRENT EDITION OF THE NEC.
3_2 CHECK THE HVAC AND PLUMBING SPECIFICATIONS FOR ELECTRICAL REQUIREMENTS AND INCLUDE
THE SAME IN THE CONTRACT COST.
3.3 EQUIPMENT CONNECTIONS, STARTERS, DISCONNECT SWITCHES, CONTROL TRANSFORMERS AND
PUSH-BUTTON STATIONS FOR THE EQUIPMENT FURNISHED BY THE OWNER OR UNDER A SEPARATE
CONTRACT SHALL BE INSTALLED AND CONNECTED UNDER THIS DIVISION, AS INDICATED ON THE
CONTRACT DRAWINGS.
3_4
120/208
277/480
PHASE A
BLACK
BROWN
PHASE B
RED
ORANGE
PHASE C
BLUE
YELLOW
NEUTRAL
WHITE
GREY
GROUND
GREEN
GREEN
3_4
ALL CUTTING, PATCHING, EXCAVATING, BACK FILLING AND CONCRETE WORK RELATED TO THIS
1.1a #12 AND #10 CONDUCTORS SHALL HAVE CONTINUOUS INSULATION COLOR, AS LISTED ABOVE.
CONTRACT WILL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR. THIS CONTRACTOR
r
M
SHALL ASSUME THE RESPONSIBILITY OF PROVIDING THE SLEEVES, CHASES AND OPENINGS
1,1b CONDUCTORS LARGER THAN ABOVE, WHICH DO NOT HAVE CONTINUOUS INSULATION COLOR
NECESSARY FOR THE ELECTRICAL INSTALLATION AND FOR THEIR REPAIR IN AN ACCEPTABLE
SHALL BE COLOR CODED BY APPLICATION OF AT LEAST TWO LAPS OF COLORED TAPE ON
MANNER, AS DETERMINED BY THE ARCHITECT. ALL HOLES SHALL BE CORE -DRILLED. PROVIDE FIRE
EACH CONDUCTOR AT ALL POINTS OF ACCESS INCLUDING JUNCTION BOXES. COLOR TAPE
STOP IN ALL OPENINGS CREATED THROUGH FIRE -RATED WALLS, FLOORS, OR CEILINGS.
J
SHALL BE THE EQUAL OF 3M PRODUCTS SCOTCH #35.
3_5
THIS CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL REQUIRED ACCESS PANELS
0<c�T-
1.1c CONDUCTORS SHALL BE SOFT ANNEALED COPPER INSULATED FOR 600 VOLTS UNLESS
NECESSARY FOR HIS WORK, COORDINATE WITH ARCHITECT PRIOR TO INSTALLATION.
SPECIFICALLY INDICATED OTHERWISE. ALUMINUM CONDUCTORS ARE NOT ALLOWED ON THIS
rC
<
co
PROJECT.
4.0
MATERIALS AND WORKMANSHIP
C
ry
1_2
INSULATION TYPE SHALL BE TYPE THW FOR WIRE SIZES #8 AWG AND LARGER AND THHN OR THWN
4.1ALL
WORK SHALL BE INSTALLED IN A PRACTICAL WORKMANLIKE MANNER BY MECHANICS SKILLED IN
W
FOR #10AWG AND SMALLER. THHN SHALL NOT BE USED IN WET OR DAMP LOCATIONS.
W
THE SEVERAL TRADES NECESSARY
<UJ
1_3
PROVIDE WIRE AND RACEWAY SYSTEM AS DESCRIBED HEREIN AND AS INDICATED ON THE
4.2
ALL MATERIALS SHALL BE NEW AND FREE FROM DEFECTS AND SHALL BE THE BEST OF THEIR
7w
DRAWINGS. METAL -CLAD (MC.) ARMORED CABLE (AC) AND NON-METALLIC SHEATHED CABLE (NMC)
SEVERAL KINDS UNLESS SPECIFIED OR INDICATED ON THE DRAWINGS TO THE CONTRARY.
=U~
SHALL NOT BE PERMITTED UNLESS NOTED SPECIFICALLY OTHERWISE AND APPROVED PRIOR TO
4.3
DURING EACH PHASE AND AT THE COMPLETION OF THE CONSTRUCTION, THIS CONTRACTOR SHALL
06W
BIDDING.
REMOVE ALL DEBRIS AND EXCESS MATERIALS CAUSED BY HIS WORK. HE SHALL LEAVE THE AREA
1_4
PROVIDE MINIMUM #12 CONDUCTORS, UNLESS OTHERWISE INDICATED.
OF OPERATION BROOM CLEAN.
4.4
ALL ELECTRICAL EQUIPMENT SHALL BEAR THE UNDERWRITERS LABORATORIES LABEL OR ETL
1.4a CONTROL CONDUCTORS SHALL BE #14 MINIMUM FOR N.E.C. CLASS 1 AND #16 FOR N.E.C.
CLASS 2.
LABEL.
4_5
THIS CONTRACTOR SHALL GUARANTEE HIS WORKMANSHIP AND MATERIAL (LAMPS EXCEPTED) FOR
1_5
CONDUCTORS #8 AWG AND LARGER SHALL BE STRANDED.
A PERIOD OF ONE YEAR FROM THE DATE OF BUILDING OPENING AND LEAVE HIS WORK IN PERFECT
1.6
CONDUCTORS #10 AWG AND SMALLER SHALL BE SOLD
ORDER AT THE COMPLETION. SHOULD DEFECTS DEVELOP WITHIN THE GUARANTEE PERIOD, THE
-
CONTRACTOR SHALL, UPON NOTICE OF THE SAME, REMEDY THE DEFECTS AND HAVE ALL
1_7
INSTALL ALL WIRING IN CONDUIT.
DAMAGES TO OTHER WORK OR FURNISHINGS CAUSED BY THE REPAIRS CORRECTED AT HIS
EXPENSE TO THE CONDITION BEFORE SUCH DAMAGE.
1.8
CONNECT #10 AND SMALLER WIRES WITH CONSTANT PRESSURE EXPANDABLE SPRING TYPE
CONNECTORS, "SCOTCHLOK" BY 3M OR B -CAP BY BUCHANAN.
5.0
SCOPE OF WORK
1_9
CONNECT #8 AND LARGER WIRES WITH COMPRESSION CONNECTORS OR SPLICES AS
5.1
THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIAL, STORAGE, UNPACKING AND
MANUFACTURED BY BURNDY OR T&B.
PLACEMENT; TO INCLUDE BUT NOT BE LIMITED TO, THE FOLLOWING ITEM:
1.10
INSULATE SPLICING CONNECTORS TO AT LEAST 200% OF THE WIRE INSULATION. USE
5.1a EMERGENCY LIGHTING AND POWER
-
PRE -STRETCHED TUBING CONNECTOR INSULATORS. 3M PST FOR #2 AND LARGER CONDUCTORS.
5.1b COMPLETE POWER AND LIGHTING DISTRIBUTION SYSTEM INCLUDING ALL TRANSFORMERS
1.11
PULL CONDUCTORS USING RECOGNIZED METHODS AND EQUIPMENT LEAVING AS LEAST 6" WIRE AT
AND FEEDERS
ALL JUNCTION BOXES FOR CONNECTIONS.
5.1c COMPLETE BRANCH CIRCUIT WIRING SYSTEM.
1.1 la CLEAN OUT EACH CONDUIT SYSTEM BEFORE PULLING WIRE.
5.1d COMPLETE POWER WIRING FOR ALL AIR CONDITIONING EQUIPMENT, PLUMBING
1,12
FORM AND TIE ALL WIRING IN PANEL BOARDS.
SYSTEM, HEATING EQUIPMENT, VENTILATING AND EXHAUST EQUIPMENT.
1.13
THERE SHALL BE NO WIRE NUT JOINTS OR SPLICES MADE INSIDE SWITCHBOARDS/ PANEL BOARDS.
5.1e COMPLETE LIGHTING FIXTURE INSTALLATION, INCLUDING ALL INCANDESCENT, FLUORESCENT
AND HID LAMPS.
1.14
BRANCH CIRCUIT WIRE SIZES (AND CONDUITS) SHALL BE INCREASED FROM THOSE INDICATED ON
THE PLANS TO PREVENT EXCESSIVE VOLTAGE DROP. BRANCH CIRCUITS SHALL BE INSTALLED WITH
5.1f COMPLETE COMMUNICATIONS CONDUIT AND WIRING SYSTEM INCLUDING BOXES, PLATES,
WIRES OF SUFFICIENT SIZE SO THAT VOLTAGE DROP BETWEEN THE PANEL AND THE LOADS DOES
JACKS, ETC., AS SPECIFIED, SHOWN ON THE DRAWINGS AND REQUIRED BY THE TENANT.
NOT EXCEED LIMIT OF 35.
5_1g TEMPORARY ELECTRICAL POWER AND LIGHTING AS REQUIRED FOR CONSTRUCTION.
1.15
WIRE SIZES SHALL BE BASED ON THE 60°C. AMPACITIES FOR WIRE SIZES NO. 14-1 A.W.G., AND 75°C.
AMPACITIES FOR WIRE SIZES #1/0 A.W.G. AND LARGER.
5.1 h TESTING OF ALL CABLES AND CIRCUIT WIRING AFTER INSTALLATION.
1.16
CIRCUITS MAY BE MULTI-PLEXED IN CONDUIT PROVIDED WIRE IS PROPERLY DERATED AND
5_1 ii EXIT LIGHT SYSTEM.
CONDUIT SIZED PER CODE. UNDER NO CIRCUMSTANCES SHALL MORE THAN (9) CURRENT
CARRYING CONDUCTORS BE RUN 1N A SINGLE CONDUIT.
5.11 WIRING DEVICES AND FLOOR BOXES.
1.17
PROVIDE WIRE AND RACEWAY SYSTEMS AS DESCRIBED HEREIN AND INDICATED ON DRAWINGS.
5.1k LIGHTING CONTROLS.
METAL -CLAD (MC), ARMORED CABLE (AC), AND NON-METALLIC SHEATED CABLE (NMC) SHALL NOT
BE PERMITTED, UNLESS NOTED SPECIFICALLY OTHERWISE AND APPROVED PRIOR TO
5.11GROUNDING OF THE ELECTRICAL SYSTEM.
-
BIDDING.
5.1m FIRE SUPERVISORY ALARM SYSTEM.
5.1 n TELEPHONE AND ELECTRIC SERVICES
5.10 SOUND SYSTEM COMPONENTS, CONDUIT SYSTEM & WIRING
DIVISION 16130 - RACEWAYS AND BOXES
1.0 RACEWAYS
1.1 ALL WIRE SHALL BE RUN IN ACCORDANCE WITH CODE IN CORROSION RESISTANT, RIGID,
THREADED, METAL CONDUIT OR ELECTRICAL METALLIC TUBING (E.M.T.) UNLESS OTHERWISE
SPECIFICALLY STATED HEREIN.
1.2 CONDUIT SIZE SHALL BE 3/4" MINIMUM.
1.3 CONDUIT SHALL BE SECURELY FASTENED IN PLACE.
1.4 ALL CONDUIT SHALL BE CONCEALED IN WALLS, FLOOR AND CEILINGS WHEREVER POSSIBLE.
EXPOSED CONDUIT IN FINISHED AREAS WILL NOT BE PERMITTED. EXPOSED CONDUIT WILL BE
PERMITTED IN UNFINISHED AREAS WITH THE SPECIFIC APPROVAL OF THE ARCHITECT.
1.5USE FLEXIBLE CONDUIT FOR THE CONNECTION TO RECESSED OR SEMI -RECESSED LIGHTING
FIXTURES (6' LENGTH MAXIMUM). USE LIQUID TIGHT METAL CONDUIT FOR ALL CONNECTIONS TO
MOTORS AND OTHER EQUIPMENT SUBJECT TO VIBRATION AND IN AREAS SUBJECT TO MOISTURE.
1_6 USE WATERTIGHT JOINTS WITH BURIED AND CONCRETE ENCASED CONDUIT. ALL BURIED CONDUIT
OUTSIDE OF BUILDINGS SHALL HAVE A MINIMUM OF 24" OF COVER. METAL CONDUITS BURIED IN
EARTH SHALL BE PAINTED (TWO COATS) WITH HEAVY ASPHALTUM PAINT.
1.7 SUPPORT RUNS OF CONDUIT AS DETAILED IN THE APPROPRIATE TABLE OF THE NATIONAL
ELECTRICAL CODE (NEC).
1_8 INSTALL EXPOSED RUNS OF CONDUIT AND CONDUIT ABOVE LAY -IN CEILING PARALLEL OR
PERPENDICULAR TO THE WALLS, STRUCTURAL MEMBERS OF INTERSECTIONS OF VERTICAL PLANES
AND CEILINGS. PROVIDE RIGHT ANGLE TURNS USING FITnINGS OR SYMMETRICAL BENDS. SUPPORT
CONDUITS WITHIN 1" OF ALL CHANGES IN DIRECTION.
1_9 IF A CONDUIT IS SUSPENDED, IT SHALL BE SUPPORTED ON TRAPEZE HANGERS WHICH USE
"ALL -THREAD" RODS FROM THE STRUCTURAL STEEL. THE USE OF CEILING SUPPORT WIRE OR
SIMILAR MATERIAL WILL NOT BE ACCEPTED.
1.10 INSTALL EMPTY CONDUIT FOR FUTURE USE AS INDICATED ON THE DRAWINGS. CONDUIT SHALL BE
COMPLETE WITH JETLINE OR PULL ROPE, JUNCTION/OUTLET BOXES, TILE RINGS AND APPROPRIATE
COVER PLATES.
1.11 PROVIDE PITCH POCKETS WHERE CONDUITS PENETRATE THE ROOF.
1.12 THREAD LUBRICATION/SEALANT IS REQUIRED ON OUTDOOR AND UNDERGROUND THREADED
METAL JOINTS.
1.13 INSTALL FIRE SEAL FITTINGS WHERE CONDUITS PENETRATE CONCRETE FLOOR SLABS OR
MASONRY WALLS REQUIRED TO BE FIRE RATED.
1.14 HORIZONTAL PORTION OF CONDUIT EXPOSED ON THE ROOF AND FEEDING EQUIPMENT SHALL NOT
BE MORE THAN 5'-0" UNLESS THE WRITTEN APPROVAL FROM ARCHITECT OR ENGINEER IS
OBTAINED.
2.0 PULL AND JUNCTION BOXES
2_1 INSTALL PULL AND JUNCTION BOXES WHERE SHOWN ON THE DRAWINGS, AND WHERE REQUIRED
FOR CHANGES IN DIRECTION, AT JUNCTION POINTS, AND TO FACILITATE WIRE PULLING. FURNISH
BOX SIZES IN ACCORDANCE WITH NEC UNLESS LARGERBOXES ARE INDICATED.
2_2 PROVIDE STEEL BOXES AND REMOVABLE COVERS OF CODE GAGE, HOT ROLLED SHEET STEEL, HOT
DIPPED GALVANIZED INSIDE AND OUTSIDE, FOR ABOVE GROUND WORK. FURNISH WEATHERPROOF
BOXES WHEN INSTALLED ABOVE GROUND OUTSIDE.
2_3 PROVIDE CAST IRON BOXES, HOT DIPPED GALVANIZED NSIDE AND OUTSIDE WHERE SHOWN ON
THE DRAWINGS. FURNISH REMOVABLE COVERS WITH GASKETS AND STAINLESS STEEL, BRASS OR
BRONZE SCREWS.
2.4 PROVIDE CONCRETE BOXES FOR UNDERGROUND WORK UNLESS OTHERWISE INDICATED ON THE
DRAWINGS. FURNISH STEEL FRAMES AND COVERS WITH THE COVER ATTACHED TO THE FRAME
WITH HEXAGON HEAD, BRASS OR BRONZE CAP SCREWS, 3/8" IN DIAMETER. PROVIDE A RUBBER
GASKET FOR SEALING BETWEEN THE COVER AND THE FRAME. PAINT THE COVER WITH TWO COATS
OF HEAVY ASPHALTUM.
3.0 OUTLET BOXES
3_1 USE SHEET STEEL BOXES, ZINC COATED OR CADMIUM PLATED, FOR CONCEALED INTERIOR WORK.
3_2 USE CAST BOXES, ZINC -CADMIUM FINISH MALLEABLE IRON, FOR EXPOSED INTERIOR WORK, AND
FOR EXPOSED OR CONCEALED WORK IN WET, DAMP OR EXTERIOR LOCATIONS. CAST BOXES SHALL
BE SERIES FD BY CROUSE HINDS OR APPLETON.
3_3 WALL BOX SIZES (MINIMUM) SHALL BE 4" SQUARE X 2-1/2"DEEP WHERE WALL CONSTRUCTION
PERMITS. WHERE WALL CONSTRUCTION DICTATES, THE WIDTH MAY BE REDUCED TO 2-1/8" OR
1-1/2" UNDER SPECIAL CONDITIONS.
3.4 FIXTURE OUTLETS IN CEILINGS (MINIMUM) SHALL BE 4" OC AGONAL X 1-1/2" DEEP (4-11/16"
OCTAGONAL X 2-1/2" DEEP WHERE REQUIRED TO ACCOMNDDATE LARGER CONDUIT OR LARGER
NUMBER OF WIRES).
3.5 GANG BOXES SHALL BE ONE PIECE (MINIMUM), 2-1/8" DEEP.
3.6 PROVIDE FLUSH FLOOR BOX SERIES 880 BY WIRE MOLD WTH DUPLEX RECEPTACLE FOR WOOD
PLATFORM AT DISPLAY SHOW WINDOWS, BOX WITH COVER PLATE FLANGE: CAT. #880W1-817TCAL
AND BRUSHED ALUMINUM COVER PLATE: CAT. #828R-TCAL WITH FLIP LID TO PROTECT RECEPTACLE
WHEN NOT IN USE. BOTH FLANGE AND COVER PLATE SHALL HAVE BRUSHED ALUMINUM FINISH. UL
SCRUB LISTED.
3_7 FLUSH MOUNT BOXES IN ALL FINISHED WALLS, INSTALL THE PLASTER RINGS IN DRY WALLED
PLASTERED WALLS AND RAISED COVERS AS REQUIRED IN WALLS WITH OTHER FINISHES SO THAT
THE COVER PLATES FIT TIGHTLY AGAINST BOXES OR RINGS. 3/16" MAXIMUM GAPS ARE ALLOWED
FOR NONCOMBUSTIBLE WALLS.
3_8 SUPPORT ALL BOXES TO MAINTAIN PROPER ALIGNMENT AND RIGIDITY.
DIVISION 16140 - WIRING DEVICES
1.0 WIRING DEVICES
1_1 WIRING DEVICE COLOR SHALL BE WHITE, UNLESS OTHERWISE NOTED.
1.2 PROVIDE TOTALLY ENCLOSED, 20 AMPERE, 120/277 VOLT, QUIET A/C GENERAL USE SNAP
SWITCHES.
1.3 SWITCHES SHALL BE SPECIFICATION GRADE AS MANUFACTURED BY HUBBELL, P&S, OR LEMON.
1.4 PROVIDE NEMA CONFIGURATION 5-20R DUPLEX 125 VOLT GROUNDING TYPE RECEPTACLES RATED
FOR 20 AMPERES UNLESS OTHERWISE INDICATED ON THE DRAWINGS.
1.5 RECEPTACLES SHALL BE SPECIFICATION GRADE AS MANUFACTURED BY HUBBELL, P&S OR
LEVITON.
1_6 RECEPTACLES REQUIRING AMPERAGES, VOLTAGES OR CONFIGURATIONS DIFFERENT FROM THE
DUPLEX CONVENIENCE RECEPTACLES ABOVE SHALL BE AS INDICATED ON THE DRAWINGS.
1_7 PROVIDE OTHER RECEPTACLES OF A QUALITY, MATERIAL AND WORKMANSHIP EQUAL TO THAT
SPECIFIED FOR DUPLEX CONVENIENCE RECEPTACLES.
1.8 PROVIDE COVER OR DEVICE PLATES FOR OUTLET BOXES AS FOLLOWS UNLESS OTHERWISE
NOTED:
1.8a FINISHED AREAS: THERMOPLASTIC -COLOR TO MATCH DEVICE.
1.8b UNFINISHED AREAS: ZINC COATED SHEET METAL, ALUMINUM, OR CAST METAL AS
APPROPRIATE FOR THE TYPE OF BOX.
1.8c EXTERIOR AREAS: COPPER FREE ALUMINUM WITH GRAY, POWDER EPDXY FINISH, GASKET,
WEATHERPROOF, CROUSE -HINDS "WLRD" FOR DUPLEX RECEPTACLES AND WLRS FOR SINGLE
RECEPTACLES OR EQUAL.
1.8d TELEPHONE COMMUNICATIONS, AND SIGNAL OUTLET PLATES, SHALL MATCH THOSE USED
FOR RECEPTACLES AND SWITCHES. ALL OUTLET AND/OR JUNCTION BOXES SHALL BE
COMPLETE WITH A COVER PLATE BY THIS CONTRACTOR.
1.8e WHERE DEVICES ARE GANGED, THEY SHALL BE INSTALLED UNDER A COMMON COVER PLATE.
1_9 LOCATE THE SWITCHES APPROXIMATELY 4'-0" ABOVE THE FINISHED FLOOR ELEVATION OR
NEAREST BLOCK COURSE (WITHIN A.D.A. REQUIREMENTS), UNLESS OTHERWISE INDICATED. THE
LONG DIMENSION OF THE SWITCHES SHALL BE VERTICAL.
1.10 LOCATE RECEPTACLES APPROXIMATELY 1'-6" ABOVE THE FINISHED FLOOR ELEVATION OR
NEAREST BLOCK COURSE (WITHIN A.D.A. REQUIREMENTS), UNLESS NOTED OTHERWISE THE LONG
DIMENSION OF RECEPTACLES SHALL BE VERTICAL.
DIVISION 16410 - SAFETY SWITCHES
1.0 SAFETY SWITCHES
1_1 SAFETY SWITCHES SHALL BE THE ENCLOSED HEAVY-DUTY TYPE (TYPE HD) WITH QUICK -MAKE,
QUICK -BREAK MECHANISM AND EXTERNAL PAD LOCKABLE OPERATING HANDLE.
1_2 SAFETY SWITCHES SHALL BE RATED FOR 240 OR 600 VOLTS AS APPLICABLE. THEY SHALL BE
HORSEPOWER RATED WHEN USED IN MOTOR CIRCUITS.
1_3 SAFETY SWITCHES SHALL BE FUSIBLE OR NON -FUSIBLE 2, 3 OR 4 POLE AS INDICATED ON THE
DRAWINGS.
1_4 SAFETY SWITCHES SHALL BE SINGLE THROW UNLESS OTHERWISE INDICATED ON THE DRAWINGS.
1_5 ENCLOSURES SHALL BE NEMA 1 INDOORS AND NEMA 3R OUTDOORS UNLESS OTHERWISE
INDICATED ON THE DRAWINGS.
1_6 MANUFACTURER SHALL BE SQUARE D, SEIMENS OR CULTER-HAMMER.
1_7 MOUNT THE SAFETY SWITCHES SECURELY BETWEEN TX 6' LEVELS ABOVE THE FLOOR UNLESS
OTHERWISE INDICATED ON THE DRAWINGS.
1_8 MOUNT THE SAFETY SWITCHES SECURELY BETWEEN TX T LEVELS ABOVE THE FLOOR UNLESS
OTHERWISE INDICATED ON THE DRAWINGS.
1_9 SWITCHES ON BLOCK WALLS SHALL BE MOUNTED ON A 3/4" PLYWOOD BACKBOARD, WHERE
LOCATED INDOORS.
DIVISION 16420 -MOTOR STARTERS
1.0 MOTOR STARTERS
1_1 PROVIDE MOTOR STARTERS (MAGNETIC OR FUSED COMBINATION) AND CONTROL EQUIPMENT
WHERE SHOWN. STARTERS SHALL BE PROVIDED WITH 120 VOLT COILS, 3 OVERLOADS, CONTROL
TRANSFORMER WITH FUSED 120 VOLT SECONDARY CONTROL CIRCUIT, (2) N.O. AND (2) N.C.
AUXILIARY CONTACTS, HAND -OFF -AUTO SELECTOR SWITCH AND RUNNING PILOT LIGHT, UNLESS
OTHERWISE NOTED. WIRE THRU CONTROL DEVICES FURNISHED BY OTHER TRADES. SINCE MOTOR
DRIVEN EQUIPMENT IS FURNISHED BY OTHER TRADES, THE CONTROL INDICATED ON THE
DRAWINGS SHALL BE CONSIDERED AS FOR BIDDING PURPOSES ONLY. WIRE TO CONFORM TO THE
ACTUAL EQUIPMENT SUPPLIED AND INSTALLED BY THE OTHER TRADES. ALL FUSES SHALL BE DUAL
ELEMENT TYPE. PROVIDE "BLOWN FUSE" INDICATOR LAMPS IN COVER.
1_2 STARTERS SHALL BE SQUARE D, SEIMENS OR CUTLER -HAMMER.
1_3 THE EXACT NUMBER OF NORMALLY OPEN AND NORMALLY CLOSED AUXILIARY CONTACTS IN EACH
STARTER SHALL BE DETERMINED BY THE TEMPERATURE CONTROL AND/OR FIRE ALARM
CONTRACTOR.
i
1.0 LIGHTING CONTROL SYSTEM
1_1 GENERAL INTRODUCTION: THE WORK COVERED IN THIS SECTION IS SUBJECT TO ALL THE
REQUIREMENTS IN THE GENERAL CONDITIONS OF THE SPECIFICATIONS. THE CONTRACTOR SHALL
COORDINATE ALL OF THE WORK IN THIS SECTION WITH ALL OF THE TRADES COVERED IN OTHER
SECTIONS OF THE SPECIFICATION TO PROVIDE A COMPLETE AND OPERABLE SYSTEM.
1.2 DESCRIPTION OF THE WORK:
1.2a THE EXTENT OF THE LIGHTING CONTROL SYSTEM WORK IS INDICATED BY THE DRAWINGS AND
BY THE REQUIREMENTS OF THIS SECTION. IT IS DEFINED TO INCLUDE, BUT NOT BY WAY OF
LIMITATION:
1.2a1 PANELBOARDS CONTAINING INTEGRAL CONTACTORS.
1.2a2 CONTROL ELECTRONICS FOR CONTACTORS AND TIMECLOCKS AND MONITORING THE
STATUS OF THE SYSTEM.
1.20 ASSOCIATED LOW AND LINE VOLTAGE OVERRIDE SWITCHES AND LIGHT SENSORS.
1.2a4 TIMECLOCKS, CONTACTORS.
1.2a5 ANY WORK STATIONS, SOFTWARE AND COMMUNICATIONS HARDWARE.
1.2b SYSTEM INSTALLATION INCLUDES THE FOLLOWING:
1.2b1 WIRING OF BRANCH CIRCUIT CONDUCTORS AND CONTACTORS
1.2b2 INSTALLATION OF EXTERNAL CONTROL DEVICES AND WIRING TO THE CONTROLLER.
1.2b3 INSTALLATION OF COMMUNICATIONS CONDUCTORS AND ASSOCIATED HARDWARE.
1_3 WARRANTY: MANUFACTURER SHALL WARRANT SPECIFIED EQUIPMENT TO BE FREE FROM DEFECTS
IN MATERIALS AND WORKMANSHIP FOR AT LEAST ONE YEAR FROM THE DATE OF INSTALLATION OR
EIGHTEEN MONTHS FROM DATE OF PURCHASE.
2.0 PANELBOARDS
2_1 ACCEPTABLE MANUFACTURERS: SQUARED CUTLER HAMMER SEIMENS G.E. FOR PRICING AND
ORDERING INFORMATION PROVIDE EQUIPMENT AS SPECIFIED HEREIN NO SUBSTITUTIONS
PERMITTED. CONTRACTOR SHALL CONTACT NO LATER THAN 5 DAYS AFTER JOB IS AWARDED TO
ENSURE LEAD TIMES DO NOT AFFECT PROJECT SCHEDULE. PANELBOARDS SHALL BE ENCLOSED
DEAD FRONT SAFETY TYPE WITH FEATURES AND RATINGS AS SCHEDULED ON THE DRAWINGS.
2_2 PANELS KNOWN AS "LOAD CENTERS" ARE UNACCEPTABLE.
2_3 MOLDED CASE CIRCUIT BREAKERS SHALL BE AS SCHEDULED ON THE DRAWINGS AND SPECIFIED IN
THIS DIVISION.
2.4 ALL BUS BARS SHALL BE RECTANGULAR, SOLID COPPER.
2_5 SPACE, WHERE SHOWN IN PANEL SCHEDULES, DESIGNATES SPACE FOR FUTURE PROTECTIVE
DEVICES AND SHALL INCLUDE BUS AND SUPPORT.
2.6 INSTALL CABINETS SO THAT CENTER OF THE TOP BREAKER DOES NOT EXCEED 6'-6" ABOVE THE
FINISHED FLOOR.
2_7 ENTRIES ON DIRECTORY CARDS SHALL BE TYPED, COMPLETE AND ACCURATE.
2_8 ALL BOLTED CONNECTIONS SHALL BE TORQUED IN ACCORDANCE WITH MANUFACTURER'S
STANDARDS.
2_9 ELECTRICAL CONTRACTOR SHALL ARRANGE CIRCUITS AS NEAR AS POSSIBLE TO CIRCUIT NUMBERS
ON THE DRAWINGS. AT COMPLETION OF JOB, ELECTRICAL CONTRACTOR SHALL TAKE CURRENT
READING CHECKS OF RESPECTIVE PHASES. A MINIMUM OF CIRCUIT CONNECTIONS SHALL BE
REARRANGED TO BALANCE AS CLOSELY AS POSSIBLE, THE LOAD IN THE PANEL.
2.10 ALL BREAKERS SHALL BE BOLT -ON TYPE.
2.11 PROVIDE (3) SPARE 1" CONDUITS INTO ACCESSIBLE CEILING SPACE WHERE PANELS ARE
FLUSH -MOUNTED.
3.0 DISTRIBUTION PANELS
3.1 ACCEPTABLE MANUFACTURERS: SQUARE D. CUTLER HAMMER, SEIMENS. G.E.. FOR PRICING AND
ORDERING INFORMATION, PROVIDE EQUIPMENT AS SPECIFIED HEREIN, NO SUBSTITUTIONS
PERMITTED. CONTRACTOR SHALL CONTACT NO LATER THAN 5 DAYS AFTER JOB IS AWARDED TO
ENSURE LEAD TIMES DO NOT AFFECT PROJECT SCHEDULE. DISTRIBUTION PANELS SHALL BE DEAD
FRONT TYPE WITH FEATURES AND RATING AS SCHEDULED ON THE DRAWINGS.
3_2 MOLDED CASE CIRCUIT BREAKERS SHALL BE AS SCHEDULED, OF SIZE AND NUMBER INDICATED ON
THE DRAWINGS. ALL BREAKERS SHALL BE BOLT -ON TYPE.
3_3 ALL LUGS SHALL BE UL APPROVED CU/AL TYPE.
3_4 PANELS SHALL BE MANUFACTURED AS A COMPLETE UNIT AND NOT AN ASSEMBLY OF PARTS
SECURED FROM A SUPPLY HOUSE.
3_5 ALL PANELS SHALL BE CAPABLE OF ACCEPTING CIRCUIT BREAKERS SIZED UP TO AND INCLUDING
400 AMPS.
3_6 VERTICAL BUSSING SHALL BE EXTENDED THE FULL LENGTH OF THE PANEL.
3_7 ALL BUS BARS SHALL BE RECTANGULAR SOLID COPPER.
3_8 DISTRIBUTION PANELS SHALL BE SQUARE D.
3_9 INSTALL PANELS SUCH THAT HANDLE FOR THE TOP BREAKER DOES NOT EXCEED 6'-6" ABOVE
FINISHED FLOOR.
3.10 PROVIDE PHENOLIC LABELS FOR EACH PANEL.
3.11 ALL BOLTED CONNECTIONS SHALL BE TORQUED IN ACCORDANCE WITH MANUFACTURER'S
STANDARDS.
3.12 SURFACE -MOUNTED PANELS SHALL BE MOUNTED ON A 3/4" PLYWOOD BACKBOARD.
FLOOR -MOUNTED PANELS SHALL BE MOUNTED ON A 4" HIGH CONCRETE PAD.
DIVISION 16461 - DRY TYPE TRANSFORMERS
1.0 TRANSFORMERS
1_1 TRANSFORMERS SHALL BE CONTINUOUSLY RATED ISOLATING TYPE FOR 60 HERTZ SERVICE
UNLESS OTHERWISE INDICATED.
1_2 INSULATION SYSTEMS SHALL BE 220 DEGREES C (150 DEGREES RISE).
1_3 ENCLOSURES FOR TRANSFORMERS SHALL BE METALLIC, SUITABLE FOR INDOOR AND OUTDOOR
INSTALLATION AS APPLICABLE AND RODENT PROOF.
1_4 MANUFACTURERS SHALL BE SQUARE D. FRACTIONAL KVA TRANSFORMERS SHALL BE
MANUFACTURED BY EDWARDS OR THE SPECIAL EQUIPMENT MANUFACTURER IN WHICH THE
TRANSFORMERS ARE USED.
1_5 FOUR APPROVED VIBRATION DAMPENERS PER TRANSFORMER SHALL BE EMPLOYED AS
NECESSARY TO AVOID TRANSMITTING ANY VIBRATION TO THE BUILDING STRUCTURE. SIZES OF THE
MOUNTINGS SHALL BE SELECTED ON THE BASIS OF THE WEIGHT OF THE TRANSFORMER, USING:
1.5a A MINIMUM 1" THICK RUBBER -CORK -RUBBER SANDWICH TYPE FOR FLOOR MOUNTING.
1.5b A SPRING TYPE FOR SUSPENSION MOUNTING.
1.5c TWO(2) SPRING TYPE AT THE TOP (WITH TWO (2) STEEL BRACKETS) AND TWO (2) RUBBER -IN
COMPRESSION TYPE AT THE BOTTOM (STAND-OFF) FOR WALL MOUNTING.
COMP I i
NFPA '70 o NE(
SEP 14 2016
ISSUE DATE
LO
co 'SU)
rU)r
y N
(L XON
o ~ixn
t`
�o EGO
m
r>>
�
CO
LO m aC
(0 V) (9 n -
two
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
SEP 08 2016
PERMIT CENTER
P7.
S
x
y
P )7
These drawings/spectfications are the
property of Kamus + Keller. They are
fumished as contract documents only.
The seal(s) and signature(s) appy
only to the documents to which they
affixed, and expressly displaim any
responsibility for all other plans,
specifications, estimates, reports or
other documents or instruments
relating to or intended to be used for
any part or parts of the architectural or
engineering project. Additionally these
drawings and seal(s) shall in no way
convey or imply any time of warranty
or certification retating to the
performance of products and materials
beyond those provided by their
respective manufacturer.
III
PROJECT NO.
16.0430.01
DRAWN/REVIEWED
GFIBB
VIII II III III II I
DATEIISSUE
8.31.2016
SHEET TITLE
ELECTRICAL
SPECIFICATIONS
II I II III IIII
SHEET NO.
E1.1
r
M
W
W
J
0<c�T-
00
00J
1-
rC
<
co
ry
C
ry
UJ
Q
W
I-
W
S'
<UJ
7w
=U~
06W
1-oZ)v
<w0
C)
00
N
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
SEP 08 2016
PERMIT CENTER
P7.
S
x
y
P )7
These drawings/spectfications are the
property of Kamus + Keller. They are
fumished as contract documents only.
The seal(s) and signature(s) appy
only to the documents to which they
affixed, and expressly displaim any
responsibility for all other plans,
specifications, estimates, reports or
other documents or instruments
relating to or intended to be used for
any part or parts of the architectural or
engineering project. Additionally these
drawings and seal(s) shall in no way
convey or imply any time of warranty
or certification retating to the
performance of products and materials
beyond those provided by their
respective manufacturer.
III
PROJECT NO.
16.0430.01
DRAWN/REVIEWED
GFIBB
VIII II III III II I
DATEIISSUE
8.31.2016
SHEET TITLE
ELECTRICAL
SPECIFICATIONS
II I II III IIII
SHEET NO.
E1.1
GENERAL NOTES
1. ELECTRICAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO BASE BID.
IN CASE OF ANY DISCREPANCIES WITH EXISTING FIELD CONDITIONS, ELECTRICAL CONTRACTOR
SHALL VERIFY THE EXACT DIFFERENCE FOR POSSIBLE REVISIONS TO THIS DOCUMENT.
2. INSTALL RECESSED LUMINAIRES USING ACCESSORIES AND FIRE STOPPING MATERIALS TO MEET
REGULATORY REQUIREMENTS FOR FIRE RATING.
3. LIGHT SWITCHES ARE TO BE MOUNTED AT 42" AFF (UNLESS OTHERWISE NOTED).
4. LIGHT FIXTURES ARE TO BE CENTERED ON CEILING TILES (UNLESS OTHERWISE NOTED).
5. CONTACT ARCHITECT TO COORDINATE LIGHT FIXTURE LOCATIONS IF EXISTING CEILING GRID IS
TO BE REUSED.
6. PROVIDE MINIMUM 90 MIN BATTERY PACKS IN EMERGENCY FIXTURES, WHERE INDICATED ON
THE DRAWINGS.
7. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH GENERAL CONTRACTOR AND TENANT
REPRESENTATIVE FOR ORDERING LUMINAIRES FROM TENANTS NATIONAL ACCOUNT WITH
"GRAINGER".
8. PROVIDE BLACK ADHESIVE LABEL ADHERED TO ALL SWITCHED RECEPTACLES WITH 1/4"
LETTERING INDICATING "SWITCHED FOR LIGHTING".
9. COORDINATE TIMING OF TIMECLOCK WITH STORE MANAGER.
10. ON ALL MULTI -WIRED HOMERUN CIRCUIT BREAKERS (REFER TO PLANS) CONTRACTOR SHALL
FIELD INSTALL ON MULTI -USE CIRCUIT BREAKERS AN APPROVED HANDLE TIE PER NEC.
11. ALL EQUIPMENT SHALL BE LISTED BY A NATIONALLY RECOGNIZED TESTING LABORATORY.
12. IT IS ACCEPTABLE TO USE MIC CABLE FOR BRANCH CIRCUITS OR HOMERUNS PROVIDED IT
COMPLIES WITH AUTHORITY HAVING JURISDICTION, LOCAL RECOGNIZED CODE AND LANDLORD.
VERIFY PRIOR TO BID.
13. ALL LOW VOLTAGE WIRING TO BE IN CONDUIT UNLESS OTHERWISE APPROVED BY AUTHORITY
HAVING JURISDICTION
NOTES BY SYMBOL
ONUMBER INDICATES CIRCUIT COORDINATION, LETTER INDICATES SWITCH COORDINATION.
REFER TO LIGHTING CONTROL DETAIL ON SHEET E1.0.
OALL EMERGENCY/EXIT FIXTURES ARE TO BE PROVIDED WITH MINIMUM 90 MIN EMERGENCY
BATTERY BACK-UP AND CONNECTED TO UNSWITCHED LEG OF LOCAL CIRCUIT. BY=PASS
ENERGY MANAGEMENT SYSTEM WHERE REQUIRED).
OALL LIGHTING CIRCUITS INDICATED ON PLANS SHALL BE ROUTED THROUGH THE LIGHTING
CONTROL SYSTEM. REFER TO LIGHTING LIGHTING CONTROL DIAGRAM ON SHEET E1.0
FOR ADDITIONAL INFORMATION.
4OSWITCHBANK LOCATION. REFER TO SWITCHBANK DETAIL ON THIS SHEET AND LIGHTING
CONTROL DIAGRAM ON SHEET E1.0 FOR ADDITIONAL INFORMATION.
OELECTRICAL DISTRIBUTION EQUIPMENT. REFER TO SHEET E3.0 FOR FURTHER COORDINAT
OEXISTING BOH LIGHTING AND SWITCHING TO REMAIN. RE -LAMP, REPAIR, RE -BALLAST AS
NEEDED TO PROVIDE FULLY FUNCTIONING FIXTURES
7O CONNECT TO EXISTING BOH CIRCUIT AND SWITCHING. V.I.F.
SWITCHBANK DETAIL
'a' �b� �'d'
>- Y
Q Q U
Wz
N 0
t7 O
NOTE:
SWITCH CONTROL LOCATION. REFER TO SHEET E1.0 LIGHTING CONTROL DETAIL FOR NUMBER OF
POLES REQUIRED. SWITCHES SHALL BE INSTALLED BETWEEN STUDS. MAKE (MORE) ROWS IF
NECESSARY. DO NOT CUT STUDS TO ACCOMMODATE A SINGLE ROW OF SWITCHES.
ALL CONTROL DEVICES FOR LIGHT, POWER, HEAT, ALARMS, ETC. SHALL BE MOUNTED NO HIGHER
THAN 42" FROM THE FLOOR.
IMPORTANT:
T.G.C. SHALL CONNECT EMERGENCY/NIGHT LIGHTING TO LOCAL CIRCUIT ON UNSWITCHED LEG.
SCALE: 1/4"=l' -O"
REVIEWED RUH'
COMPLIANCE , .J e A,H
NFPA70 - NEC
SEP 14 2016
City of TuWla
BUILDING DIVISION
A)1rrff11 A
w• • • w• • w•��
SEP 08 2016
PERMIT CENTER
ISSUE DATE
C- �
r-nOD
co N r
�
0 ~r
aO m N
C)
m Q.
� �� 9
mfnc0(LLL
These dreviings/specifications are the
property of Kamus + Keller. They are
fumished as contract documents only.
The seal(s) and signature(s) apply
only to the documents to which they
affixed, and expressly displaim any
responsibility for all other plans,
specifications, estimates, reports or
other documents or instruments
relating to or Intended to be used for
any part or parts of the architectural or
engineering project. Additionally these
drawings and seal(s) shaft in no way
convey or imply any time of warranty
or certification relating to the
performance of products and materials
beyond those provided by their
respective manufacturer.
PROJECT NO.
16.0430.01
DRAWN/REVIEWED
GFIBB
DATE/ISSUE
8.31.2016
SHEET TITLE
ELECTRICAL
LIGHTING PLAN
SHEET NO.
E2.0
r
M
W
F_
UJ
(!
U)
_jry
0
Q
QD
0)
Q
wW
<
w
UJ
_J
Q
06
own
<U)0
U)
0
00
N
These dreviings/specifications are the
property of Kamus + Keller. They are
fumished as contract documents only.
The seal(s) and signature(s) apply
only to the documents to which they
affixed, and expressly displaim any
responsibility for all other plans,
specifications, estimates, reports or
other documents or instruments
relating to or Intended to be used for
any part or parts of the architectural or
engineering project. Additionally these
drawings and seal(s) shaft in no way
convey or imply any time of warranty
or certification relating to the
performance of products and materials
beyond those provided by their
respective manufacturer.
PROJECT NO.
16.0430.01
DRAWN/REVIEWED
GFIBB
DATE/ISSUE
8.31.2016
SHEET TITLE
ELECTRICAL
LIGHTING PLAN
SHEET NO.
E2.0
GENERAL NOTES
1. ELECTRICAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO BASE BID.
IN CASE OF ANY DISCREPANCIES WITH EXISTING FIELD CONDITIONS, ELECTRICAL CONTRACTOR
SHALL VERIFY THE EXACT DIFFERENCE FOR POSSIBLE REVISIONS TO THIS DOCUMENT.
2. INSTALL RECESSED LUMINAIRES USING ACCESSORIES AND FIRE STOPPING MATERIALS TO MEET
REGULATORY REQUIREMENTS FOR FIRE RATING.
3. LIGHT SWITCHES ARE TO BE MOUNTED AT 42" AFF (UNLESS OTHERWISE NOTED).
4. LIGHT FIXTURES ARE TO BE CENTERED ON CEILING TILES (UNLESS OTHERWISE NOTED).
5. CONTACT ARCHITECT TO COORDINATE LIGHT FIXTURE LOCATIONS IF EXISTING CEILING GRID IS
TO BE REUSED.
6. PROVIDE MINIMUM 90 MIN BATTERY PACKS IN EMERGENCY FIXTURES, WHERE INDICATED ON
THE DRAWINGS.
7. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH GENERAL CONTRACTOR AND TENANT
REPRESENTATIVE FOR ORDERING LUMINAIRES FROM TENANTS NATIONAL ACCOUNT WITH
"GRAINGER".
8. PROVIDE BLACK ADHESIVE LABEL ADHERED TO ALL SWITCHED RECEPTACLES WITH 1/4"
LETTERING INDICATING "SWITCHED FOR LIGHTING".
9. COORDINATE TIMING OF TIMECLOCK WITH STORE MANAGER.
10. ON ALL MULTI -WIRED HOMERUN CIRCUIT BREAKERS (REFER TO PLANS) CONTRACTOR SHALL
FIELD INSTALL ON MULTI -USE CIRCUIT BREAKERS AN APPROVED HANDLE TIE PER NEC.
11. ALL EQUIPMENT SHALL BE LISTED BY A NATIONALLY RECOGNIZED TESTING LABORATORY.
12. IT IS ACCEPTABLE TO USE M/C CABLE FOR BRANCH CIRCUITS OR HOMERUNS PROVIDED IT
COMPLIES WITH AUTHORITY HAVING JURISDICTION, LOCAL RECOGNIZED CODE AND LANDLORD.
VERIFY PRIOR TO BID.
13. ALL LOW VOLTAGE WIRING TO BE IN CONDUIT UNLESS OTHERWISE APPROVED BY AUTHORITY
HAVING JURISDICTION
NOTES BY SYMBOL
ONUMBER INDICATES CIRCUIT COORDINATION, LETTER INDICATES SWITCH COORDINATION. ALL
MVU LIGHTING CIRCUITS SHALL BE ROUTED THROUGH ENERGY MANAGEMENT SYSTEM. REFEF
TO LIGHTING CONTROL DETAIL ON SHEET E1.0
OELECTRICAL CONTRACTOR TO COORDINATE WITH TELEPHONE/DATA SYSTEM INSTALLER
CONDUIT SIZE, REQUIREMENTS AND ROUTING OF TEUDATA CONDUIT IN FIELD PRIOR TO
ROUGH -IN.
OELECTRICAL CONTRACTOR SHALL COORDINATE WITH ARCHITECTURAL MILLWORK DETAILS
FOR FINAL LOCATION OF ALL DEVICES AND TEUDATA CONDUIT AT MILLWORK. INCLUDE ALL
J -BOXES, TWO CHANNEL WIREMOLDS AND REQUIRED CONDUITS FOR LINE AND LOW
VOLTAGE AS PART OF BASE BID IN ORDER TO OBTAIN A COMPLETE AND OPERATING SYSTEM.
OPROVIDE FLUSH FLOOR MOUNTED POWER AND TEUDATA DEVICE AT LOCATION INDICATED
ON THE PLANS. PROVIDE FLOOR BOX AND CORRESPONDING ACCESSORIES REQUIRED PER
FIELD CONDITIONS (BLACK COVER FOR CARPET FLOORING AND BRASS COVER FOR ALL
OTHER FINISHES.
O5 CORE FLOOR FOR INSTALLATION OF NEW CONDUITS. PROVIDE CONDUIT AS SHOWN WITH
PULL STRING FOR DATA CABLING AND 3/4" CONDUIT WITH POWER WIRING TO FLOOR BOX
RECEPTACLES. FIELD VERIFY ROUTING OF CONDUIT PRIOR TO CUTTING FLOOR. PATCH TO
MATCH EXISTING. COORDINATE WITH FURNITURE SUPPLIER AND ARCHITECTURAL DIMENSION
PLAN PRIOR TO SAW -CUTTING FLOOR. ALL FLOOR MOUNTED DEVICES MUST MEET "SCRUB
WATER TEST'.
OAT THIS LOCATION, STUB CONDUITS UP THROUGH WALL. ALL TEUDATA CONDUITS SHALL BE
STUBBED INTO ACCESSIBLE CEILING SPACE ABOVE. FINAL PLACEMENT OF CONDUITS
STUB -UP AT FLOOR SHALL BE COORDINATED WITH TENANT REPRESENTATIVE PRIOR TO
INSTALLATION
OELECTRICAL CONTRACTOR SHALL PROVIDE DUAL BRANCH CIRCUIT QUAD RECEPTACLES
BEHIND MVU. HALF OF QUAD FOR GENERAL POWER AND HALF FOR SWITCHING. REFER TO
GENERAL NOTES 8 AND 10 ABOVE.
OELECTRICAL DISTRIBUTION EQUIPMENT. REFER TO SHEET E3.0 FOR FURTHER
COORDINATION.
OELECTRICAL CONTRACTOR TO MAKE FINAL CONNECTION TO TENANT SIGN. IF NOT EXISTING,
PROVIDE MEANS OF DISCONNECT AND SEPARATE GROUND PER NEC (CONDUIT GROUND NOT
PERMITTED). CIRCUIT SIGN VIA TIMECLOCK, REFER TO LIGHTING CONTROL DIAGRAM ON
SHEET E1.0.
10 PROVIDE 24"w x 36"h x 6"d TELEPHONE CABINET, 3/4" THICK FIRE RETARDANT PLYWOOD. PAINT
EXPOSED SIDE WITH ADJACENT WALL COLOR. PROVIDE GROUND BUS, 3/4" CONDUIT WITH (1)
#6 GROUND TO LIFER GROUND. PROVIDE QUAD RECEPTACLE AND CIRCUIT AS INDICATED.
11 EXISTING MEANS OF DISCONNECT AND ALL ASSOCIATED ELECTRICAL FOR WATER HEATER
TO REMAIN
12 EXISTING NON-FUSED DISCONNECT, WP/GF) RECEPTACLE, AND DUCT MOUNTED SMOKE
DETECTOR TO REMAIN. REFER TO PANEL SCHEDULE AND RISER DIAGRAM ON SHEET E3.0
ADDITIONAL INFORMATION. V.I.F.
13 EXISTING RECEPTACLE TO REMAIN
14 PROVIDE POWER AND KEYED SWITCHES FOR ROLLING GRILLE. COORDINATE SPEC AND FINAL'
SWITCH LOCATIONS WITH ARCHITECT
15 EXISTING T -STATS TO REMAIN
WIN
(E)
I L
SH I 42
L
26
X60" Lit
10 24
I L �
34
I
i(TYPICAL)
QMI
L
L 23 20,22
IC3 31,33
mC �mL�3� 1 I _ ,
EAR fA!LUE-T 18 MI
MWU MWU FSLS '
c�
.J�
5
(TYPICAL)
AHU-1
12
2L
7/29
(TYPICAL)
AATV-BENCH
AHU-2
L 12
19,21 L
CU -2 CU -1
12 12
L L
36/38/40 28/30
MWU
i, ,
Ems:_
:..
LT -S
2
M — — —
20 LT -D
CLG
LT -S
(TYPICAL)
MWU
L
31,3.
a
m
'-SLT-C
T -D 22 LT -ADA
--S LT -C
(TYPICAL) (TYPICAL)
MWU MWU
SPT1-
4
19 c _ 1
3 i■' 1 fir' ,.A4,4U, 11
i � ■!_ ■ �
SCALE: 1/4"=I'-0"
MWU
BP
L
12
D
12
MPOS
L
� i17
NOTE:
A FIRE ALARM SYSTEM IS REQUIRED
FOR THIS LOCATION. T.G.C. TO HIRE A
LANDLORD APPROVED FIRE
PROTECTION CONTRACTOR TO PROVIDE
FIRE PROTECTION PLANS UNDER A
SEPERATE SUBMITTAL.
RS
MWU
MWU
Ell- �
i�-alp
(2)D V
CLG
JE®
AWILA
2016
:ENTER
ISSUE DATE
mco
I- m
a ; 00
: F-7 j
CL mrN
m oco
m M N m
�j C Lr
� � P='�
(o U) a tL
L
N
O
C
C
Q)
C
U)
C
O
U
■
C
C
N
O-
C
O
a
These drawings/specifications are the
property of Kamus + Keller. They are
furnished as contract documents only.
The seal(s) and signature(s) appy
only to the documents to which they
affixed, and expressly displatm any
responsibility for all other plans,
spectfications, estimates, reports or
other documents or instruments
relating to or intended to be used for
any part or parts of the architectural or
engineering project. Additionally these
drawings and seal(s) shall in no way
convey or Imply any time of warranty
or certification relating to the
performance of products and materials
beyond those provided by their
respective manufacturer.
PROJECT NO.
16.0430.01
DRAWN/REVIEWED
GF1BB
DATEIISSUE
8.31.2016
SHEET TITLE
ELECTRICAL
POWER PLAN
SHEET NO.
E2.1
Cfl
M
W
UJ
U)
Octc
G
Jarmo
0
Q
WI—
W
S�
�CWzW
W
=W06
�
D
<C
0
to
(n
0
W
0
00N
These drawings/specifications are the
property of Kamus + Keller. They are
furnished as contract documents only.
The seal(s) and signature(s) appy
only to the documents to which they
affixed, and expressly displatm any
responsibility for all other plans,
spectfications, estimates, reports or
other documents or instruments
relating to or intended to be used for
any part or parts of the architectural or
engineering project. Additionally these
drawings and seal(s) shall in no way
convey or Imply any time of warranty
or certification relating to the
performance of products and materials
beyond those provided by their
respective manufacturer.
PROJECT NO.
16.0430.01
DRAWN/REVIEWED
GF1BB
DATEIISSUE
8.31.2016
SHEET TITLE
ELECTRICAL
POWER PLAN
SHEET NO.
E2.1
U)
0
Z
v
ii
W
W
MOTES BY SYMBOL
LI+7-2LBCW--4'—' (3)D (1)T — — —
t" CONDUIT FOR
POWER PER TABLE.
1" CONDUIT FOR DATA
PER TABLE.
2" CONDUIT FOR (1) HDMI„
(2) USB, PER TABLE
0 EXISTING METER BASE AND METER SOCKET TO REMAIN.
0 EXISTING 200 AMP BREAKER TO REMAIN.
OEXISTING (4) #3/0 THWN CU, (1) #4 GROUND IN EXISTING CONDUIT TO REMAIN.
4O EXISTING CONDUIT COMPLETE WITH PULL STRING FOR TELEPHONE SERVICE FROM
LANDLORD DMARC STUBBED INTO TENANT SPACE. INTERCEPT AND ROUTE CONDUIT TO
TENANT PHONE BOARD LOCATION.
OEXISTING 60 AMP NON-FUSED DISCONNECT TO REMAIN
OEXISTING 30 AMP NON-FUSED DISCONNECT TO REMAIN
OEXISTING (2) #8 THWN CU (1) #10 GROUND IN EXISTING CONDUIT
OEXISTING (3) #10 THWN CU (1) #10 GROUND IN EXISTING CONDUIT
OEXISTING (2) #12 THWN CU (1) #10 GROUND IN EXISTING CONDUIT
W
REF.
WIREMOLD
I -1 wLIJ
2" CONDUIT STUB -UP BEHIND
FIXTURE (OUTSIDE OF WALL),
FLUSH WITH CONCRETE
I ` =
t
.EGIRAND RFB4E
2,CONDUIT STgB-UP NEXT TO
LOOR BOX, PE TABLE
GENERAL NOTES
1. 120/208 VOLT 4 WIRE EXISTING ELECTRICAL SERVICE
NOTE: RECEPTACLES @ BACKWRAP AND
LEARNING TABLE TO BE ON A SINGLE 20
AMP DEDICATED CIRCUIT. DO NOT ADD
OTHER RECEPTACLES TO CIRC.
NOTE: IF LEARNING TABLES ARE TO BE
TEMPORARILY USED AS POS STATIONS,
THE 2" CONDUIT SHOWN IN ENLARGED
PLAN IS REQUIRED IN ORDER TO PROVIDE
HDMI AND USB CORDS AND AMPLIFIER
FROM THE BACKWRAP TO THE LEARNING
TABLE.
THE HDMI, USB, AND AMPLIFIER SHOUDL BE
ORDERED THROUGH GRAINGER AS
REQUIRED.
POWER/ DATA ENLARGED PLAN @ BCW & LT
CU -1—M5
I
CU-2�
7 8 AHU-1
II I 7 AHU-2
I
II 119
III TC
I EXISTING
PANEL i Cl
I I
L ----J
Ifl JAM!"',
I Imo; 14+4
5r•
i
2. TENANTS GENERAL CONTRACTOR SHALL PROVIDE AND INSTALL ALL COPPER CONDUCTORS
WHEN NEW IS REQUIRED
3. VERIFY ALL EXISTING CONDITIONS IN FIELD. ALL UPGRADES REQUIRED BY CODES, LANDLORD
OR TENANT SHALL BE BY TENANT AT TENANTS EXPENSE.
4. CONTRACTOR TO VERIFY ALL METERING REQUIREMENTS WITH LANDLORD AND LOCAL UTILITY
PRIOR TO BID.
5. CONTRACTOR TO VERIFY EXACT DISTANCE AND ROUTING OF SERVICE FEEDERS FROM
LANDLORD DISTRIBUTION/ SERVICE EQUIPMENT TO TENANT SPACE PRIOR TO BIDDING.
HOMERUNS AND BRANCH WIRING FOR 20 AMP CIRCUITS SHALL
ELECTRICAL LOAD
BE AS FOLLOWS:
LENGTH
CIRCUIT WIRE SIZE HOMERUN WIRE SIZE
1 FT TO 50FT
NO.12 AWG
NO.12 AWG
51 FT TO 75FT
NO.12 AWG
NO.10 AWG
76FT TO 120FT
NO.10 AWG
NO.8 AWG
121 FT TO 190FT
NO.10 AWG
NO.6 AWG
191 FT TO 30OFT
NO.10 AWG
NOA AWG
SCALE: N.T.S.
NOTE REGARDING EXAMINATION OF PREMISES/FIELD CONDITIONS:
PRIOR TO SUBMITTING PROPOSALS FOR THE WORK, EACH BIDDER IS
REQUIRED TO HAVE EXAMINED THE PREMISES AND VERIFY THE EXISTING
FIELD CONDITIONS. THE EXISTING CONDITIONS HAVE BEEN EXAMINED IN THE
FIELD BY TENANT REPRESENTATIVE'S AND ARE BELIEVED TO BE DEPICTED IN
A ACCURATE MANNER AS THEY EXIST.
IF THE BIDDER FINDS THAT THAT THERE ARE DISCREPANCIES BETWEEN THE
EXISTING CONDITIONS AND THE INFORMATION SHOWN ON THESE DRAWINGS,
THEY SHOULD NOTIFY THE TENANTS REPRESENTATIVE OF THOSE
DISCREPANCIES. IF THESE INSTRUCTIONS ARE IGNORED, THE CONTRACTOR
SHALL BE RESPONSIBLE FOR FURNISHING ALL THE EQUIPMENT REQUIRED
FOR A COMPLETE AND FUNCTIONING ELECTRICAL SYSTEM AT NO ADDITIONAL
COST TO TENANT.
NOTE REGARDING ELECTRICAL DISTRIBUTION SYSTEM:
THE ELECTRICAL RISER DIAGRAM INDICATED HAS BEEN PROPERLY DESIGNED
TO ACCOMMODATE TENANTS POWER REQUIREMENTS AND MEETS ALL
APPLICABLE BUILDING CODES. IT IS THE RESPONSIBILITY OF THE G.C. TO
VERIFY ALL EXISTING CONDITIONS AND DETERMINE IF ANY EXISTING
EQUIPMENT AND WIRING IS SUITABLE FOR REUSE IN THE SYSTEM PRIOR TO
BIDDING.
G.C. SHALL PERFORM ALL WORK NECESSARY TO RESULT IN A COMPLETE AND
LEGAL INSTALLATION INCLUDING THE UPGRADING AND/OR MODIFICATION OF
THE EXISTING SERVICE FEEDERS, CONDUITS AND TAP -INS EXTENDED TO
PROPER POINT OF ORIGIN AS COORDINATED WITH THE LANDLORD.
NOTES: I TOTAL AMPS @1201208V 3PH 128.24
1. 100% OF FIRST 10,000 WATTS, PLUS. 50% OF REMAINING LOAD.
2. 100% OF A/C LOAD (COOLING VS HEATING) PLUS 25% OF LARGEST MOTOR.
REVIEWED FOR
COMPLIANCE 1 'ITH
NFPA 7n A NEC
SEP 14: 2016
City of-T'ukWl1a
BUILDING DIVISInN
RECEIVED
CITY OF TUKWILA
SEP 0 8 2016
PERMIT CENTER
ISSUE DATE
T
S
Sr r 00
T
ti C
0 r
rN'
CL
o C 00
m CO m
9 C m
ur):n) > Lo��
L
ai
CZ
c
a�
t»
r_
0
0
c
c
cv
CL
C
0
ELECTRICAL LOAD
S MMA■ iY
1201208V 3PH - 4W
LOAD DESCRIPTION
CONNECTED VA
FACTOR DEMAND VA
VOLTAGE
PHASE
LIGHTING
4,537
1.25
5,671
120
1
RECEPTACLES
9,280
NOTE # 1
9,280
120
1
SHOW WINDOW RECEPTACLE:
0
1.25
0
120
1
MECHANICAL
23,984
NOTE # 2
24,715
208
3
SIGN LIGHTING
1,200
1.25
1,500
120
1
WATER HEATERS
31600
1.25
4,500
120
1
MISCELLANEOUS
500
1.00.
500
120
1
TOTAL
43,101
46,166
208
3
NOTES: I TOTAL AMPS @1201208V 3PH 128.24
1. 100% OF FIRST 10,000 WATTS, PLUS. 50% OF REMAINING LOAD.
2. 100% OF A/C LOAD (COOLING VS HEATING) PLUS 25% OF LARGEST MOTOR.
REVIEWED FOR
COMPLIANCE 1 'ITH
NFPA 7n A NEC
SEP 14: 2016
City of-T'ukWl1a
BUILDING DIVISInN
RECEIVED
CITY OF TUKWILA
SEP 0 8 2016
PERMIT CENTER
ISSUE DATE
T
S
Sr r 00
T
ti C
0 r
rN'
CL
o C 00
m CO m
9 C m
ur):n) > Lo��
L
ai
CZ
c
a�
t»
r_
0
0
c
c
cv
CL
C
0
These drawings/specifications are the
property of Kamus + Keller. They are
furnished as contract documents only.
The seal(s) and signature(s) apply
only to the documents to which they
affixed, and expressly dispiaim any
responsibility for all other plans,
specifications, estimates, reports or
other documents or Instruments
relating to or intended to be used for
any part or parts of the architectural or
engineering project. Additionally these
drawings and seal(s) shall in no way
convey or imply any time of warranty
or certification relating to the
performance of products and materials
beyond those provided by their
respective manufacturer.
III I
PROJECT NO.
16.0430.01
DRAWN/REVIEWED
GFIBB
DATE/ISSUE
8.31.2016
SHEET TITLE
ELEC PANEL
SCHEDULES &
RISER DIAGRAM
I,I�IIII VIII
SHEET NO.
E3.0
(0
Ir—
co M
W
W
U3
OQ_j°r°
_i
OO
0ol
WW�<
J
z
W
WW
UW
Z
J
UI~—
°6
Z)
I—
W
d�o�
U)
O
00
(N
These drawings/specifications are the
property of Kamus + Keller. They are
furnished as contract documents only.
The seal(s) and signature(s) apply
only to the documents to which they
affixed, and expressly dispiaim any
responsibility for all other plans,
specifications, estimates, reports or
other documents or Instruments
relating to or intended to be used for
any part or parts of the architectural or
engineering project. Additionally these
drawings and seal(s) shall in no way
convey or imply any time of warranty
or certification relating to the
performance of products and materials
beyond those provided by their
respective manufacturer.
III I
PROJECT NO.
16.0430.01
DRAWN/REVIEWED
GFIBB
DATE/ISSUE
8.31.2016
SHEET TITLE
ELEC PANEL
SCHEDULES &
RISER DIAGRAM
I,I�IIII VIII
SHEET NO.
E3.0