HomeMy WebLinkAboutPermit D17-0144 - THOMPSON TILE & STONE - STORAGE RACKSTHOMPSON TILE & STONE
575 STRANDER BLVD
D17-0144
Parcel No:
Address:
0
City of Tukwila
0
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670
Inspection Request Line: 206-438-9350
Web site: http://www.TukwilaWA.gov
DEVELOPMENT PERMIT
0223300010 Permit Number:
575 STRANDER BLVD
Project Name: THOMPSON TILE & STONE
Issue Date:
Permit Expires On:
D17-0144
11/14/2017
5/13/2018
Owner:
Name:
Address:
Contact Person:
Name:
Address:
Contractor:
Name:
Address:
WESTERN B NORTHWEST WA LLC
PO BOX 460169 C/O RYAN, HOUSTON,
WA, 77056
DOUG WILLIAM
3500 W VALLEY HWY N - SUITE 101,
AUBURN, WA, 98001
RAYMOND HANDLING CONCEPTS
CORP
4140 BOYCE RD , FREMONT, CA, 94538
License No: RAYMOHC034KB
Lender:
Name: THOMPSON TILE & STONE
Address: 575 STRANDER BLVD , TUKWILA, WA,
98188
Phone: (253) 335-2410
Phone: (253) 333-2109
Expiration Date: 10/1/2018
DESCRIPTION OF WORK:
PROVIDE AND INSTALL PALLET RACK IN WAREHOUSE
Project Valuation: $20,000.00
Type of Fire Protection: Sprinklers: YES
Fire Alarm:
Type of Construction: VB
Electrical Service Provided by: TUKWILA
Fees Collected: $1,332.66
Occupancy per IBC: S-2
Water District: TUKWILA
Sewer District: TUKWILA
Current Codes adopted by the City of Tukwila:
International Building Code Edition:
International Residential Code Edition:
International Mechanical Code Edition:
Uniform Plumbing Code Edition:
International Fuel Gas Code:
2015
2015
2015
2015
2015
National Electrical Code:
WA Cities Electrical Code:
WAC 296-46B:
WA State Energy Code:
2014
2014
2014
2015
Public Works Activities:
Channelization/Striping:
Curb Cut/Access/Sidewalk:
Fire Loop Hydrant:
Flood Control Zone:
Hauling/Oversize Load:
Land Altering:
Landscape Irrigation:
Sanitary Side Sewer:
Sewer Main Extension:
Storm Drainage:
Street Use:
Water Main Extension:
Water Meter:
Volumes: Cut: 0 Fill: 0
Number: 0
No
Permit Center Authorized Signature:gild
Date:
I hearby certify that I have read and examined this permit and know the same to be true and correct. All
provisions of law and ordinances governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other
state or local laws regulating construction or the performance of work. I am authorized to sign and obtain this
development permit and a ree to the conditions attached to this permit.
Signature: cy� �C e� Date: 1 IMT/ I
Print Name: C2, (Gtr Pear
This permit shall become null and void if the work is not commenced within 180 days for the date of issuance, or if
the work is suspended or abandoned for a period of 180 days from the last inspection.
PERMIT CONDITIONS:
1: ***BUILDING PERMIT CONDITIONS***
2: Work shall be installed in accordance with the approved construction documents, and any changes made
during construction that are not in accordance with the approved construction documents shall be
resubmitted for approval.
3: All permits, inspection record card and approved construction documents shall be kept at the site of work
and shall be open to inspection by the Building Inspector until final inspection approval is granted.
4: The special inspections and verifications for concrete construction shall be as required by IBC Chapter 17,
Table 1705.3.
5: When special inspection is required, either the owner or the registered design professional in responsible
charge, shall employ a special inspection agency and notify the Building Official of the appointment prior to
the first building inspection. The special inspector shall furnish inspection reports to the Building Official in
a timely manner.
6: A final report documenting required special inspections and correction of any discrepancies noted in the
inspections shall be submitted to the Building Official. The final inspection report shall be prepared by the
approved special inspection agency and shall be submitted to the Building Official prior to and as a
condition of final inspection approval.
7: All construction shall be done in conformance with the Washington State Building Code and the
Washington State Energy Code.
8: All rack storage requires a separate permit issued through the City of Tukwila Permit Center. Rack storage
over 8 -feet in height shall be anchored or braced to prevent overturning or displacement during seismic
events. The design and calculations for the anchorage or bracing shall be prepared by a registered
professional engineer licensed in the State of Washington. Periodic special inspection is required during
anchorage of storage racks 8 feet or greater in height.
9: There shall be no occupancy of a building until final inspection has been completed and approved by
Tukwila building inspector. No exception.
10: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an
approval of, any violation of any of the provisions of the building code or of any other ordinances of the City
of Tukwila. Permits presuming to give authority to violate or cancel the provisions of the code or other
ordinances of the City of Tukwila shall not be valid. The issuance of a permit based on construction
documents and other data shall not prevent the Building Official from requiring the correction of errors in
the construction documents and other data.
11: All permits, inspection record card and approved construction documents shall be kept at the site of work
and shall be open to inspection by the Building Inspector until final inspection approval is granted.
12: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila
Permit Center.
23: Rack storage must be maintained at 12 ft. or lower and must not be fully encapsulated or existing sprinkler
density will have to be increased.
16: The total number of fire extinguishers required for an ordinary hazard occupancy with Class A fire hazards is
calculated at one extinguisher for each 1,500 sq. ft. of area. The extinguisher(s) should be of the "All
Purpose" (3A, 40B:C) dry chemical type. Travel distance to any fire extinguisher must be 75' or less. (IFC
906.3) (NFPA 10, 5.4)
13: Portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied.
Hangers or brackets shall be securely anchored to the mounting surface in accordance with the
manufacturer's installation instructions. Portable fire extinguishers having a gross weight not exceeding 40
pounds (18 kg) shall be installed so that its top is not more than 5 feet (1524 mm) above the floor. Hand-
held portable fire extinguishers having a gross weight exceeding 40 pounds (18 kg) shall be installed so that
its top is not more than 3.5 feet (1067 mm) above the floor. The clearance between the floor and the
bottom of the installed hand-held extinguishers shall not be less than 4 inches (102 mm). (IFC 906.7 and IFC
906.9)
14: Extinguishers shall be located in conspicuous locations where they will be readily accessible and
immediately available for use. These locations shall be along normal paths of travel, unless the fire code
official determines that the hazard posed indicates the need for placement away from normal paths of
travel. (IFC 906.5)
15: Fire extinguishers require monthly and yearly inspections. They must have a tag or label securely attached
that indicates the month and year that the inspection was performed and shall identify the company or
person performing the service. Every six years stored pressure extinguishers shall be emptied and
subjected to the applicable recharge procedures. If the required monthly and yearly inspections of the fire
extinguisher(s) are not accomplished or the inspection tag is not completed, a reputable fire extinguisher
service company will be required to conduct these required surveys. (NFPA 10, 7.2, 7.3)
17: Maintain fire extinguisher coverage throughout.
18: Clearance between ignition sources, such as light fixtures, heaters and flame -producing devices, and
combustible materials shall be maintained in an approved manner. (IFC 305.1)
19: Nominal 6" transverse flue spaces between loads and at rack uprights shall be maintained in single row,
double row, and multiple row racks. Random variations in the width of flue spaces or in their vertical
alignment shall be permitted. (NFPA 13-16.11.1) (IFC Table 3208.3)
20: Flue spaces shall be provided in accordance with International Fire Code Table 3208.3. Required flue
spaces shall be maintained.
21: Any overlooked hazardous condition and/or violation of the adopted Fire or Building Codes does not imply
approval of such condition or violation.
22: These plans were reviewed by Inspector 511. If you have any questions, please call Tukwila Fire Prevention
Bureau at (206)575-4407.
PERMIT INSPECTIONS REQUIRED
Permit Inspection Line: (206) 438-9350
1700 BUILDING FINAL**
0611 EMERGENCY LIGHTING
1400 FIRE FINAL
0409 FRAMING
4046 SI-EPDXY/EXP CONC
CITY OF TUKWILA
Community Development Deparhnent
Public Works Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http://www.TukwilaWA.gov
Building Permit No.
Project No.
Date Application Accepted: S ---)S-1.
,
Date Application Expires: �- S( 7
(For office use only)
CONSTRUCTION PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
**Please Print**
SITE LOCATION
Site Address: 575 STRANDER BLVD
Tenant Name: THOMPSON TILE & STONE
King Co Assessor's Tax No.: 0223300010
Suite Number: Floor:
PROPERTY OWNER
Name: DOUG WILLIAM
Name: THOMPSON TILE & STONE
Cit': AUBURN State: WA Zip: 98001
Address: 575 STRANDER BLVD
Email: dwilliam@raymondhandling.com
City: TUKWILA State: WA
Zip: 98188
CONTACT PERSON — person receiving all project
communication
Name: DOUG WILLIAM
Address: 3500 W VALLEY HWY N. SUITE 101
Cit': AUBURN State: WA Zip: 98001
Phone: (253) 335-2410 Fax:
Email: dwilliam@raymondhandling.com
GENERAL CONTRACTOR INFORMATION
Company Name: RAYMOND HANDLING CONCEPT
Address: 3500 W VALLEY HWY N. SUITE 101
City: AUBURN State: WA Zip: 98001
Phone: (253) 335-2410 Fax:
Contr Reg No.: RAYMOHCO34KB Exp Date:
Tukwila Business License No.:
H:\ApplicationsWorms-Applications On Line \2011 Applications\Permit Application Revised - 8-9-11.docx
Revised: August 2011
bh
New Tenant: ❑ Yes ❑..No
ARCHITECT OF RECORD
Company Name: STRUCTURAL CONCEPTS ENG
Engineer Name:
Company Name:
City: LA VERNE State: CA Zip: 91750
Phone: (909) 596-1351 Fax:
Architect Name:
-7 4
S4?e (LA
Address:
City: -17
La.
City:
State:
Zip:
Phone:
Fax:
Email:
ENGINEER OF RECORD
Company Name: STRUCTURAL CONCEPTS ENG
Engineer Name:
Address: 1615 YEAGER AVE
City: LA VERNE State: CA Zip: 91750
Phone: (909) 596-1351 Fax:
Email:
LENDERBOND ISSUED (required for projects $5,000 or
greater per RCW 19.27.095)
Name:•
Address:
-7 4
S4?e (LA
City: -17
La.
State:
Zip:
� ,, s
Page 1 of 4
BUILDING PERMIT INFORMATION— 206-431-3670
Valuation of Project (contractor's bid price): $ 20,000
Describe the scope of work (please provide detailed information):
PROVIDE AND INSTALL PALLET RACK IN WAREHOUSE
Will there be new rack storage? ❑ Yes
Existing Building Valuation: $
❑.. No If yes, a separate permit and plan submittal will be required.
Provide All Building Areas in Square Footage Below
PLANNING DIVISION:
Single family building footprint (area of the foundation of all structures, plus any decks over 18 inches and overhangs greater than 18 inches)
*For an Accessory dwelling, provide the following:
Lot Area (sq ft): Floor area of principal dwelling: Floor area of accessory dwelling:
*Provide documentation that shows that the principal owner lives in one of the dwellings as his or her primary residence.
Number of Parking Stalls Provided: Standard: Compact: Handicap:
Will there be a change in use? ❑ Yes 0 No If "yes", explain:
FIRE PROTECTION/IIAZARDOUS MATERIALS:
0 Sprinklers ❑ Automatic Fire Alarm 0 None ❑ Other (specify)
Will there be storage or use of flammable, combustible or hazardous materials in the building? ❑ Yes ❑ No
If `yes', attach list of materials and storage locations on a separate 8-1/2"x 11" paper including quantities and Material Safety Data Sheets.
SEPTIC SYSTEM
0 On-site Septic System — For on-site septic system, provide 2 copies of a current septic design approved by King County Health
Department.
HAApplications\Fonns-Applications On Lind201 I Applications\Pennit Application Revised - 8-9.11.docx
Revised: August 2011
bh
Page 2 of 4
Existing
Interior Remodel
Addition to
Existing
Structure
New
Type of
Construction per
IBC
Type of
Occupancy per
IBC
In Floor
19,229
VB
2nd Floor
3`d Floor
Floors thru
Basement
Accessory Structure*
Attached Garage
Detached Garage
Attached Carport
Detached Carport
Covered Deck
Uncovered Deck
PLANNING DIVISION:
Single family building footprint (area of the foundation of all structures, plus any decks over 18 inches and overhangs greater than 18 inches)
*For an Accessory dwelling, provide the following:
Lot Area (sq ft): Floor area of principal dwelling: Floor area of accessory dwelling:
*Provide documentation that shows that the principal owner lives in one of the dwellings as his or her primary residence.
Number of Parking Stalls Provided: Standard: Compact: Handicap:
Will there be a change in use? ❑ Yes 0 No If "yes", explain:
FIRE PROTECTION/IIAZARDOUS MATERIALS:
0 Sprinklers ❑ Automatic Fire Alarm 0 None ❑ Other (specify)
Will there be storage or use of flammable, combustible or hazardous materials in the building? ❑ Yes ❑ No
If `yes', attach list of materials and storage locations on a separate 8-1/2"x 11" paper including quantities and Material Safety Data Sheets.
SEPTIC SYSTEM
0 On-site Septic System — For on-site septic system, provide 2 copies of a current septic design approved by King County Health
Department.
HAApplications\Fonns-Applications On Lind201 I Applications\Pennit Application Revised - 8-9.11.docx
Revised: August 2011
bh
Page 2 of 4
PERMIT APPLICATION NOTES —
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review — Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The Building Official may grant one or more extensions of time for additional periods not exceeding 90 days each. The extension shall be
requested in writing and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY B�f LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWNER OR, f� . l� Z i D A
Signature: Date: 05 .2f//7
/ /
Print Name: 7k,( O/'i Day Telephone: 201' rho - 7331
Mailing Address:711 J. gOAA4o J t. 17177Lec 11/ 98 i
City
H:Vtpplications\Forms-Applications On Line \2011 Applications\Pertnit Application Revised - 8-9-1 l.docx
Revised: August 2011
bh
Page 4 of 4
Cash Register Receipt
City of Tukwila
DESCRIPTIONS
ACCOUNT
QUANTITY
PAID
$491.91
$491.91
$491.91
$491.91
$491.91
PermitTRAK
D17-0144 Address: 575 STRANDER BLVD Apn: 0223300010
DEVELOPMENT
PERMIT FEE
TOTAL FEES PAID BY RECEIPT: R12790
R000.322.100.00.00
0.00
Date Paid: Tuesday, November 14, 2017
Paid By: RAYMOND HANDLING
Pay Method: CHECK 258455
Printed: Tuesday, November 14, 2017 9:05 AM 1 of 1
SYSTEMS
Cash Register Receipt
City of Tukwila
DESCRIPTIONS ACCOUNT QUANTITY
PermitTRAK
PAID
$840.75
D17-0144 Address: 575 STRANDER BLVD Apn: 0223300010
$840.75
DEVELOPMENT
$816.15
PERMIT FEE
R000.322.100.00.00
0.00
$491.91
PLAN CHECK FEE
R000.345.830.00.00
0.00
$319.74
WASHINGTON STATE SURCHARGE
B640.237.114
0.00
$4.50
TECHNOLOGY FEE
$24.60
TECHNOLOGY FEE
TOTAL FEES PAID BY RECEIPT: R11575
R000.322.900.04.00
0.00
$24.60
$840.75
Date Paid: Thursday, May 25, 2017
Paid By: RAYMOND HANDLING
Pay Method: CHECK 252677
Printed: Thursday, May 25, 2017 1:33 PM 1 of 1
criliWSYSTEMS
INSPECTION NO.
INSPECTION RECORD
Retain a copy with permit
PERMIT N0.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 438-9350
Project: 1
-rti �T�t
Type of Inspection: �,
3�I���>n5 ,NAL
Address:�� ��� f
575 r er a
Date Called:
Special Instructions:
akeit�(► l 1 n@5-
Date Wanted:
24
••
-2_06( p.m:
Requester:
1hone 00206-Io-5z5s-
259653 -52 5"-
NIApproved per applicable codes. LJ Corrections required prior to approval.
COMMENTS:
-
Inspector:'W
Date -z / De/
REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection.
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 438-9350
D17 -c:).114.4
Project:
7/40N -P56/4 '!ice it's78NI
Type of Inspection:
Address:
575 STRAADER DLO
Date Called:
Special Instructions:
pOLD)}4 s 'I fit-
Date Wanted:
Requester:
V1 L Alsi paA,U
Phone No:
503- ` 2tie- 7(e )
0 Approved per applicable codes. Corrections required prior to approval.
COMMENTS:
GL54D .' nee -155
Inspector:
mss
Date:
REINSPECTION FEE REQUIRED. Prior to next inspection. fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection.
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 438-9350
D) 7-r) t 1f-'
Project:
P`6J0 77u et* S—ZIAJE
Type of Inspection:
Address:
57,5' 67NAAJDXR
SL✓D,
Date Called:
Special Instructions:
13 OIL PING IA -L.
PfiLLCT Mcg)1,46
Date Wanted:
tZ-7-iv'
a.m.
(p.m
Requester:
pit'ji-,A%
Phone No:
7 - 444,-67Co)
Approved per applicable codes.
Corrections required prior to approval.
COMMENTS:
biz- �'lr
Inspector:
Date:
REINSPECTION FEE REQUIRED. Prior to next inspection. fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection.
3
INSPECTION NUMBER
INSPECTION RECORD
Retain a copy with permit
PERMIT NUMBERS
CITY OF TUKWILA FIRE DEPARTMENT
206-575-4407
Project:,.......-i,Type
Sprinklers:
Fire Alarm:
of II,nspection: / r
iNct_V-- fe5,..,..e c'itn
Address:
Suite #: S) c
cT
if-
Contact Person: 1 D
Q.,1
Special Instructions:
Phone No.:
/
pA proved per applicable codes.
Corrections required prior to approval.
COMMENTS:
Sprinklers:
Fire Alarm:
Hood & Duct:
Monitor:
'‘*e_
----vey- Li-fikAn '
\--.?Mt5 C'
(--f cort__
V
— - e_,Ac
,,is_6‘,t.,,0
e fSs 0)
_
/,4172t
t-kow (I�� -
--. CR..�-�ci.,V
Needs Shift Inspection:
Sprinklers:
Fire Alarm:
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
Inspector: ,Z
P. S-3
Date:
6---h7 h 8
Hrs.: 1
()
un.'
$100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. Call to schedule a reinspection.
Billing Address
Attn:
Company Name:
Address:
City:
State:
Zip:
Word/Inspection Record Form.Doc
3/14/14
T.F.D. Form F.P. 113
INSPECTION RECORD
Retain a copy with permit
1-7 (1/4.-4-
INSPECTION NUMBER PERMIT NUMBERS
CITY OF TUKWILA FIRE DEPARTMENT
206-575-4407
Project:
//-7444
Type of Inspection:
1-7-://Q 4- L
cK,(U �1 ((-
Address: /
pp))
%) JlJe�2 !�/
Contact Person:
O
Suite #: ��
Special Instructions:
Phone No.:
Approved per applicable codes.
Corrections required prior to approval.
COMMENTS:
Sprinklers:
Fire Alarm:
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
P7744
L)
L ()`- -
C ( 6.7 i--17—; AJ(
,A)0 /
!' /W
/ " i. f :' /
WI qi2- -- ' 1 lir—
.I u! vl-,7! tie V Y r-----
01)Si
f19 -i4- /f-- o"
75 / d
n4 /912
r ( Do A/67—
S,7?,4-give- '
/q4.--6—
/7'" (1' eVi ti -/S
7`-
is iz /,, T /lac vE
,2
Needs Shift Inspection:
Sprinklers:
Fire Alarm:
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
Inspector:
s----4--
Date: /-7./-
Hrs.:
f
$100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. CaII to schedule a reinspection.
Billing Address
•
Attn:
Company Name:
Address:
City:
State:
Zip:
Word/Inspection Record Form.Doc
3/14/14
T.F.D. Form F.P. 113
i
INSPECTION NUMBER
INSPECTION RECORD
Retain a copy with permit
PERMIT NUMBERS
CITY OF TUKWILA FIRE DEPARTMENT
206-575-4407
Project:Type
TH(1)44 05.0
^
of Inspection:
Address: " I
Suite #:
Gi �d,.eV all)
Contact Person:
Special Instructions:
Occupancy Type:
Phone No.:
Approved per applicable codes.
Corrections required prior to approval.
COMMENTS:
Sprinklers:
r
Hood & Duct:
fI/
fr. NI- RIC, Ft lig"'" -1 ' 6Z v c 5 i -)/2-S
Permits:
Occupancy Type:
iti) f) 3I C rf --" 7^D P o I2d -tes —
r
t(>)
X07-- S ?a c /- frithAfr 77-6 S Lr, --F
C4-1 L
r7.61e, 5 4-11-0-- / rt 5,. /r
Needs Shift Inspection:
Sprinklers:
Fire Alarm:
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
Inspector:
Date: 12 /r3/,-
Hrs.:
$100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. CaII to schedule a reinspection.
Billing Address
Attn:
Company Name:
Address:
City:
State:
Zip:
Word/Inspection Record Form.Doc
3/14/14
T.F.D. Form F.P. 113
structural I Cm
Concepts
Engineering
1815 Wright Ave
La Verne, Ga. 91750
Tel: 909-596-1351 Fax: 909-596-7186
Project Name : THOMPSON TILE AND STONE
Project Number : R-042717-5LV
Dote : 05/01/17
Street Address: 575 STRADER BLVD
City/State : TUKWILA, WA 98188
Scope of Work : STORAGE RACK
REVIEWED FOR
'-DE COMPLIANCE
APPROVED
NOV 07 2017
11 AY 0 2 2017
RECEIVED
CITY OF TUKWILA
MAY 25 2017
PERMIT CENTER
Str tural
oncepts
Engineering
1815 Wright Ave La Verne. CA 91750 Tel: 909.596.1351 Fax: 909.596.7186
By: BOB
Project: THOMPSON TILE & STONE Project #: R-042717-5LV
TABLE OF CONTENTS
Title Page 1
Table of Contents 2
Design Data and Definition of Components 3
Critical Configuration 4
Seismic Loads 5 to 6
Column 7
Beam and Connector 8 to 9
Bracing 10
Anchors 11
Base Plate 12
Slab on Grade 13
TYPE I SELECT-THOMPSON TILE
Page 2 of / 3 4/27/2017
Sttural
rIoncepts
�� ngineer6ng
1815 Wright Ave La Verne. CA 91750 Tel: 909.596.1351 Fax: 909.596.7186
By: BOB
Project: THOMPSON TILE & STONE Project #: R-042717-5LV
Design Data
1) The analyses herein conforms to the requirements of the:
2015 IBC Section 2209
2016 CBC Section 2209A
ANSI MH 16.1-2012 Specifications for the Design of Industria/ Steel Storage Racks 2012 RMI Rack Design Manual"
ASCE 7-10, section 15.5.3
2) Transverse braced frame steel conforms to ASTM A570, Gr.50, with minimum strength, Fy=50 ksi
Longitudinal frame beam and connector steel conforms to ASTM A570, Gr.50, with minimum yield, Fy=50 ksi
All other steel conforms to ASTM A36, Gr. 36 with minimum yield, Fy= 36 ksi
3) Anchor bolts shall be provided by installer per ICC reference on plans and calculations herein.
4) All welds shall conform to AWS procedures, utilizing E70xx electrodes or similar. All such welds shall be performed
in shop, with no field welding allowed other than those supervised by a licensed deputy inspector.
5) The existing slab on grade is 6" thick with minimum 2500 psi compressive strength. Allowable Soil bearing capacity is 1000 psf.
The design of the existing slab is by others.
6) Load combinations for rack components correspond to 2012 RMI Section 2.1 for ASD level load criteria
Definition of Components
Frame
Height
A
Beam
Product
Beam
Spacing
Beam
Length
Front View: Down Aisle
(Longitudinal) Frame
Column
Beam to Column
Connector
Base Plate and
Anchors
Panel
Height
Frame
Depth
Section A: Cross Aisle
(Transverse) Frame
Horizontal
Brace
Diagonal
Brace
TYPE I SELECT-THOMPSON TILE
Page 3 of i 3 4/27/2017
' Strturai
oncepts
- Engineering
By: BOB
1815 Wright Ave La Verne. CA 91750 Tel: 909.596.1351 Fax: 909.596.7186
Project: THOMPSON TILE & STONE Project #: R-042717-5LV
Configuration & Summary: TYPE 1 SELECTIVE RACK
48"
48"
192"
48"
1`
48"
96"
192"
48"
48"
36"
36"
L
36"
**RACK COLUMN REACTIONS
ASD LOADS
AXIAL DL= 140 1b
AXIAL LL= 3,800 /b
SEISMIC AXIAL Ps=+/- 5,593 /b
BASE MOMENT= 8,000 in -/b
Seismic Criteria
# Bm Lvls
Frame Depth
Frame Height
# Diagonals
Beam Length
Frame Type
Ss=1.447, Fa=1
4
36 in
192.0 in
4
96 in
Single Row
Component
Description
STRESS
Column
Fy=50 ksi
Struc C4x4.5
P=3940 Ib, M=13230 in -Ib
0.31-0K
Column & Backer
None
None
None
N/A
Beam
Fy=50 ksi
Struc C4x4.5
Unbraced Length=48"
Capacity: 8022 Ib/pr
0.27 -OK
Beam Connector
Fy=50 ksi
Lvl 1: 2 bolt OK
Mconn=9754 in -Ib
Mcap=27480 in -Ib
0.35-0K
Brace -Horizontal
Fy=36 ksi
Struc L2 x L2 x 1/8
0.13 -OK
Brace -Diagonal
Fy=36 ksi
Struc L2 x L2 x 1/8
0.39-0K
Base Plate
Fy=36 ksi
8x5x3/8 Fixity= 8000 in -Ib
0.49-0K
Anchor
2 per Base
0.5" x 3.25" Embed HILTI KWIKBOLT TZ ESR 1917 Inspection Regd (Net Seismic Uplift=3694 Ib)
0.892 -OK
Slab & Soil
6" thk x 2500 psi slab on grade. 1000 psf Soil Bearing Pressure
0.38-0K
Level
Load**
Per Level
Beam Spcg
Brace
Story Force
Transv
Story Force
Longit.
Column
Axial
Column
Moment
Conn.
Moment
Beam
Connector
1 2,200 Ib 48.0 in 36.0 in 164 Ib
122 Ib 3,940 Ib 13,230 "# 9,754 "# 2 bolt OK
2
3
4
2,200 Ib
2,200 Ib
1,000 Ib
48.0 in
48.0 in
48.0 in
36.0 in
48.0 in
48.0 in
327 Ib
491 Ib
314 Ib
244 Ib
366 Ib
234 Ib
2,805 Ib
1,670 Ib
535 Ib
10,117 "# 7,640 "# 2 bolt OK
7,192 "# 5,080 "# 2 bolt OK
2,803 "# 1,700 "# 2 bolt OK
** Load defined as product weight per pair of beams
Notes
Total: 1,296 lb 965 Ib
TYPE 1 SELECT-ThOMPSON TILE
Page Cif of ( 4/27/2017
Str tural
concepts
r•�
ngineering
By: BOB
1815 Wright Ave La Verne. CA 91750 Tel: 909.596.1351 Fax: 909.596.7186
Project: THOMPSON TILE & STONE
Project #: R-042717-5LV
Seismic Forces
Configuration: TYPE 1 SELECTIVE RACK
Lateral analysis is performed with regard to the requirements of the 2012 RMI ANSI MH 16.1-2012 Sec 2.6 & ASCE 7-10 sec 15.5.3
Transverse (Cross Aisle) Seismic Load
V= Cs*Ip*Ws=Cs*Ip*(0.67*P*Prf+D)
Csl= Sds/R
= 0.2412
Cs2= 0.044*Sds
= 0.0424
Cs3= 0.5*S1/R
= 0.0674
Cs -max= 0.2412
Base Shear Coeff=Cs= 0.2412
Level
1
2
3
4
PRODUCT LOAD P
2,200 Ib
2,200 Ib
2,200 Ib
1,000 Ib
Cs -max * Ip= 0.2412
Vmin= 0.015
Eff Base Shear=Cs= 0.2412 Transverse Elevation
Ws= (0.67*PLRFI * PL)+DL (RMI 2.6.2)
= 5,372 Ib
vt
Vtransv=Vt= 0.2412 * (280 Ib + 5092 Ib)
Etransverse= 1,296 Ib
Limit States Level Transverse seismic shear per upright
P*0.67*PRFI DL
1,474 Ib 70 Ib
1,474 Ib 70 Ib
1,474 Ib 70 Ib
6701b 70 Ib
hi
48 in
96 in
144 in
192 in
wi*hi
74,112
148,224
222,336
142,080
Ss= 1.447
S1= 0.539
Fa= 1.000
Fv= 1.500
Sds=2/3*Ss*Fa= 0.965
Sd1=2/3*Sl*Fv= 0.539
Ca=0.4*2/3*Ss*Fa= 0.3859
(Transverse, Braced Frame Dir.) R= 4.0
Ip= 1.0
PRFs= 1.0
Pallet Height=hp= 48.0 in
DL per Beam Lvl= 70 Ib
Fi Fi*(hi+hp/2)
163.7 Ib 11,786-#
327.4 Ib 39,288-#
491.1 Ib 82,505-#
313.8 Ib 67,781-#
sum: P=7600 Ib 5,092 Ib
Longitudinal (Downaisle) Seismic Load
280 Ib W=5372 Ib
586,752
1,296 Ib
Z=201,360
Similarly for longitudinal seismic loads, using R=6.0
Cs1=Sd1/(T*R)= 0.1797
Cs2= 0.0424
Cs3= 0.0449
Cs -max= 0.1797
Level PRODUC LOAD P
1 2,200 Ib
2 2,200 Ib
3 2,200 Ib
4 1,000 Ib
Ws= (0.67 * PLRF2
= 5,372 Ib
Cs=Cs-max*Ip= 0.1797
P) + DL
PRF2= 1.0
(Longitudinal, Unbraced Dir.) R= 6.0
r= 0.50 sec
Vlong= 0.1797 * (280 Ib + 5092 Ib)
Elongitudinal= 965 Ib Limit States Leve/Lungit seismic shear per upright
P*0.67*PRF2
1,474 Ib
1,474 Ib
1,474 Ib
670 Ib
DL
70 Ib
70 Ib
70 Ib
70 Ib
hi
48 in
96 in
144 in
192 in
wi*hi
74,112
148,224
222,336
142,080
l\1
i,"\\.1
Fi
121.9 Ib
243.8 Ib
365.7 Ib
233.7 Ib
Front View
sum: 5,092 Ib
280 Ib W=5372 Ib
586,752
965 Ib
TYPE 1 SELECT-THOMPSON TILE
Page 7 of 1 3 4/27/2017
Str tura)
oncepts
Engineenng
1815 WrightAve La Verne. CA 91750 Tel; 909.596.1351 Fax: 909.596.7186
By: BOB
Project: THOMPSON TILE & STONE Project #: R-042717-5LV
Downaisle Seismic Loads Configuration: TYPE 1 SELECTIVE RACK
Determine the story moments by applying portal analysis. The base plate is assumed to provide partial fixity.
Seismic Story Forces
Vlong= 965 Ib
Vco1=Vlong/2= 483 Ib
F1= 122 lb
F2= 244 Ib
F3= 366 Ib
Seismic Story Moments
Typical frame made
Tributary area of two columns
of rack frame \.
14— 96
Front View
Conceptual System
ktitititis
Side View
Typical Frame made
of two columns
E» --'i v \\. -++-tip
N. �titi t titin �titi t titi
7r w
Top View
-r r
Mbase-max= 8,000 in -Ib <=== Default capacity
Mbase-v= (Vcol*hleff)/2
= 10,615 in -Ib <=== Moment going to base
Mbase-eff= Minimum of Mbase-max and Mbase-v
= 8,000 in -Ib
M 1-1= [Vcol * hleff]-Mbase-eff M 2-2= [Vcol-(F1)/2] * h2
= (483 Ib * 44 in) -8000 in -Ib = [483 Ib - 121.9 Ib]*48 in/2
= 13,230 in -Ib = 10,117 in -Ib
hl-eff= hi - beam clip height/2
= 44 in Vool
Mseis= (Mupper+Mlower)/2
Mseis(1-1)= (13230 in -Ib + 10117 in-lb)/2
Mseis(2-2)= (10117 in -Ib + 7192 in-Ib)/2
= 11,674 in -Ib = 8,654 in -Ib
Beam to Column
Elevation
rho= 1.0000
Summary of Forces
LEVEL hi
1 48 in
2 48 in
3 48 in
4 48 in
Axial Load
3,940 Ib
2,805 Ib
1,670 Ib
535 Ib
Column Moment**
13,230 in -Ib
10,117 in -Ib
7,192 in -lb
2,803 in -Ib
Mseismic** Mend -fixity Mconn**
11,674 in -Ib 2,260 in -Ib 9,754 in -Ib
8,654 in -Ib 2,260 in -Ib 7,640 in -Ib
4,997 in -Ib 2,260 in -Ib 5,080 in -Ib
1,402 in -Ib 1,027 in -Ib 1,700 in -Ib
Beam Connector
2 bolt OK
2 bolt OK
2 bolt OK
2 bolt OK
Mconn= (Mseismic + Mend-fixity)*0.70*rho
Mconn-allow(2 Bolt)= 27,480 in -Ib
**all moments based on limit states level loading
TYPE I SELECT-THOMPSON TILE
Page W of 3 4/27/2017
Sttural
rI#oncepts
Engineering
1815 Wright Ave La Verne. CA 91750 Tel: 909.596.1351 Fax: 909.596.7186
By: BOB Project: THOMPSON TILE & STONE
Column (Longitudinal) Configuration: TYPE 1 SELECTIVE RACK
Project #: R-042717-5LV
Section Properties
Column Member= Struc C4x4.5
Aeff = 1.192 in^2
Ix = 3.270 in^4
Sx = 1.635 in^3
rx = 1.656 in
Iy = 0.256 in^4
Sy = 0.237 in^3
Ty = 0.464 in
Loads Considering loads at level 1
Fy= 50,000 psi
Kx= 1.7
Lx= 46.0 in
Ky= 1.0
Ly= 36.0 in
Cm= 0.85
4.00 in -171
COLUMN DL= 140 Ib
COLUMN PL= 3,800 Ib
Mcol= 13,230 in -Ib
Sds= 0.9647
1+0.105*Sds= 1.1013
1.4+0.14Sds= 1.5351
1+0.14Sds= 1.1351
0.85+0.14*Sds= 0.9851
B= 0.7000
rho= 1.0000
Axial Analysis
Critical load cases are: RMI Sec 2.1
Load Case 5: : (1+0.105*Sds)D + 0.75*(1.4+0.14Sds)*B*P + 0.75*(0.7*rho*E)<= 1.0, ASD Method
Load Case 6: : (1+0.104*Sds)D + (0.85+0.14Sds)*B*P + (0.7*rho*E)<= 1.0, ASD Method
By analysis, Load case 6 governs utilizing loads as such
Axial Load=Pa= 1.135058*140 Ib + 0.985058*0.7*3800 Ib
= 2,779 Ib
Moment=Mx= 0.7*rho*Mcol
= 0.7 * 13230 in -Ib
= 9,261 in -Ib
(kl/r)x = (1.7*46 in/1.656 in)
= 47.22
(kl/r)max= 77.59
(kl/r)y = (1*36 in/0.464 in)
= 77.59
Cc = (2n^2E/Fy)^0.5
= 107.0
SINCE (KL/r)max < Cc, USE EQTN E2-1
Fa = fl-((kl/r)^2/2Cc^2)}Fy
5/3 + 3(kl/r)/8Cc - (kl/r)^3/8Cc^3
= 19,491 psi
fa= Pa/AREA
= 2,332 psi fa/Fa= 0.12 < 0.15
Bending Analysis
fbx= Mx/Sx
= 5,664 psi
F'ex= (12*n^2*E)/(23*(KL
= 66,966 psi
(1-fa/F'e)= 1.00
Combined Stresses
Fbx= 0.6*Fy
= 30,000 psi
fb/Fb= 0.19
(H1-3): fa/Fa + fb/Fb=
0.31 <_ 1.0 OK
TYPE I SELECT-TI0MPSON TILE Page 7 of / 3 4/27/2017
S trL.oncepts
tura)
Engineering
1815 Wright Ave La Verne. CA 91750 Tel: 909.596.1351 Fax: 909.596.7186
By: BOB Project: THOMPSON TILE & STONE
Project #: R-042717-5LV
Beam Configuration: TYPE 1 SELECTIVE RACK
The beam to column connection is assumed to provide partial end fixity for the beam frame. The end moment calculated herein is added
to the lateral force force portal moment when analyzing the connection capacity.
The impact load on the beam is addressed by including the Impact Factor "a" in the determination of the beam center bending stress.
Section Properties
Beam Member= Struc C4x4.5
Beam at Level= 1
Beam Type= Structural
Ix= 3.469 in^4
Sx= 1.735 inA3
Beam Length=L= 96.0 in
Unbraced Length, Lu= 48.0 in
Loads
Beam Weight= 4.0 Ib/ft
Thickness= 0.137 in
Beam Shape= Channel
d/Af= 9.4
Impact Factor (a)=[1-(25%/2)]= 0.875
4.000 in
Load Case: D t 0.88P + Impact RMI Section 21, Load case 10
0/0 End Fixity= 25
0 = 0.25
Mcenter= 6*(wL^2/8)
= 0.832*(wL^2/8)
Mends= 0*Mmax(fixed ends)
= (wL^2/12)*0.25
= 0.0208*wLA2
Fb= 0.6 * Fy
= 30,000 psi
Fb-eff= 26,596 psi
Live Load/Pair= 2,200 Ib
Mcenter= 0.104 * wL^2
= 11,302 in -Ib
Bending
Coeff 13= 0.104/0.125
= 0.832
Mcenter= Mcenter(simple ends) - 0*Mcenter(fixed ends)
= wL^2/8 - (0.25 * wL^2/12)
= wL^2/8 - wL^2/48
= 0.104 * wL^2
Fy= 50,000 psi
Fb' = 12,000/(lu*d/Af)
= 12,000/(48*9.4)
= 26,596 psi
Dead Load/Pair= (4 lb/ft) * 2 * 96 in/12
= 64 Ib
Mends= 0.0208*wL^2
= 2,260 in -Ib
Dist Load=w= 11.8 Ib/in
M= 11,302 in -Ib
fb= (M/Sx)/a AI- includes impact factor (a) reduction coeff, conservatively 1.0P is used in lieu of 0.88P
= 7,445 psi
fb/Fb= 7445 psi/26596 psi
0.28 <= 1.0, OK
Bending Capcity= 8,022 Ib/pair <=== Critical
Deflection
Defl-allow=L/ 180
= 0.534 in
Deflection Capacity= 11,341 Ib/Pair
Allowable load per beam pair= 8,022 Ib
Defl= f3 * [5wL^4/(384*E*Ix)]
= [5*11.8 lb/in*(96 in)^4/(384*29.5x10A6 psi * 3.469 in^4)]*0.832
= 0.106 in <= 0.534 in, OK
TYPE I SELECT-THOMPSON TILE Page
of (3 4/27/2017
— Y1el1d ocnn1MPl
1815 Wright Ave La Verne, CA 91750 Tel: 909.596.1351 Fax: 909.596.7186
By: BOB
Project: ThOMPSON TILE $ STONE
R -042717-S
Project #: W
2 Bolt Beam to Column Connection
Configuration: TYPE I SELECTIVE RACK
Mconn max= (Mseismic + Mend-fixity)*0.70*Rho
= 9,754 in -Ib
Connector Type= 2 Bolt
Shear Capacity of Bolt
1"
O
o•
P2
Standard Bolt Pattern
C
P1
bolt Dam= 0.50 in
Fv-bolt= 21,000 psi
Ashear= (0.5 in) ^ 2 * Pi/4
= 0.1963 in ^ 2
Fy= 50,000 psi
Pshear= Ashear * Fv
= 21,000 psi * 0. 1963 in ^ 2
= 4, 122 112
Bearing Capacity of Bolt
tcol= 0.137 in Fu= 65,000 psi
Bolt Diam= 0.5
Pbearing= 1 .2 * bearing Area * Fu
= I .2 * 0.5 in dram * 0. 137 in " 65000 psi
= 5,343 Ib > 41 22 117
Moment Capacity of bracket
Edge Distance=E= I .00 in Bolt Spacing= 4.0 in
C= PI +P2
= PI+P1*(276")
= 1.11 *PI
tclip= 0.18 in
Mcap= Sclip * Fbendmg C*d= Mcap = 1 . 1 I
= 0.14 in^3*0.66"Fy
= 4,620 m-119
Pclip= Mcap/(I . 1 1 * d)
= 4620 in-Ib/(I . 1 1 " I in) Thus, P I = 4,122 Ib
= 4,162 Ib
Mconn-allow= [121 *6"+P 1 *(2"/6")*0 5"]
= 4122 LB*[6"+(276")*2"]
= 27,480 in -112 > Mconn max, OK
•
:u
(2)-°C GR 5
50LT
Fy= 50,000 psi
Sclip= 0. 140 in ^ 3
d= E
= I .00 in
r
$"
i
TYPE I SELECT-ThOMPSON TILE
Page 5 of (_3 4/27/2017
pts
ngineering
1815 Wright Ave La Verne, CA 91750 Tel: 909.596.1351 Fax: 909.596.7186
By:
BOB
Project: THOMPSON TILE & STONE
Transverse Brace
TYPE 1 SELECTIVE RACK
Project #:
R-042717-5LV
Diagonal Member= Struc L2 x L2 x 1/8
Area= 0.48 in^2
r min= 0.398 in
K= 1.0
Fy= 36,000 psi
Frame Dimensions
Horizontal Member= Struc L2 x L2 x 1/8
Area= 0.48 in^2
r min= 0.398 in
K= 1.0
0
Load Case 6:: (1+ + [(0.85-f0.14.5ds)*B*P
Bottom Panel Height=H= 48.0 in
Frame Depth=D= 36.0 in
Column Width=B= 1.6 in
Diagonal Brace
+ [0.7*rho*E]<= 1.0, ASD Method
Clear Depth=D-B*2-4"=d= 28.8 in
Ldiag= [d^2 + H^2]^0.5
= 56.0 in
D
Typical Panel
Configuration
Vtransverse= 1,296 Ib
Vb=Vtransv*0.7*rho= 1296 Ib * 0.7 * 1
= 907 Ib
(kl/r)max= 140.70
(kl/r)x = (1*56 in/0.398 in)
= 140.70
(KL/r)max > Cc, Eqtn E2-2 Applies
Fa = 12n^2E/23(kl/r)^2
23(kl/r)^2
= 7,543 psi
fa/Fa= 0.39 <= 1.0 OK
Horizontal Brace
Vdiag= V*(Ldiag/D)
= 1,4111b
Cc = (2n^2E/Fy)^0.5
= 126.1
fa= P/AREA
= 2,915 psi
Check Weld
Weld Tension= 1,411 Ib
tweld= 0.125 in
Lweld= 4.0 in
Fweld= 70,000 psi
Weld Capacity= tweld*0.7071*Lweld*0.3*Fweld*1.0
= 7,425 Ib 19.0% OK
V=Vtransv= 907 Ib
(kl/r)x = (1*36 in/0.398 in) (kl/r)max= 90.45
= 90.45
(KL/r)max < Cc, Eqtn E2-1 Applies
Fa = [1-((kl/r)^2/2Cc^2)1Fv
5/3 + 3(kl/r)/8Cc - (kl/r)^3/8Cc^3
= 14,151 psi
fa/Fa= 0.13 <= 1.0 OK
Cc = (2n^2E/Fy)^0.5
= 126.1
fa= P/AREA
= 1,874 psi
Strtural
I oncepts
7 Engineering
By: BOB
1815 Wright Ave
La Verne. CA 91750 Tel: 909.596.1351 Fax: 909.596.7186
Project: THOMPSON TILE & STONE
Single Row Frame Overturning
Configuration: TYPE 1 SELECTIVE RACK
Project #: R-042717-5LV
Loads
Critical Load case(s):
1) RMI Sec 2.2, item 7: (0.9-0.2Sds)D + (0.9-0.20Sds)*B*Papp - E*rho
Vtrans=V=E=Qe= 1,296 Ib
DEAD LOAD PER UPRIGHT=D= 280 Ib
PRODUCT LOAD PER UPRIGHT=P= 7,600 Ib
Papp=P*0.67= 5,092 Ib
:1=Wst1=(0.70706*D + 0.70706*Papp*1)= 3,798 Ib
Product Load Top Level, Ptop= 1,000 Ib
DL/LvI= 70 Ib
Seismic Ovt based on E, E(Fi*hi)= 201,360 in -Ib
height/depth ratio= 5.3 in
Sds= 0.9647
(0.9-0.20Sds)= 0.7071
(0.9-0.2Sds)= 0.7071
B= 1.0000
rho= 1.0000
Frame Depth=Df= 36.0 in
Htop-Iv1=H= 192.0 in
# Levels= 4
# Anchors/Base= 2
hp=480in
T
<<<
1
A) Fully Loaded Rack h=H+hp/2= 216.0 in
Load case 1:
Movt= E(Fi*hi)*E*rho Mst= Wst1 * Df/2
= 201,360 in -Ib = 3798 Ib * 36 in/2
= 68,364 in -Ib
T= (Movt-Mst)/Df
= (201360 in -Ib - 68364 in-Ib)/36 in
= 3,694 Ib Net Uplift per Column
Net Seismic Uplift= 3,694 Ib
B) Top Level Loaded Only
Load case 1:
ED V1=Vtop= Cs * Ip * Ptop >= 350 Ib for H/D >6.0
= 0.2412 * 1000 Ib
= 241 Ib
Vleff= 241 Ib Critical Level= 4
V2=VOL= Cs*Ip*D Cs*Ip= 0.2412
= 68 Ib
Mst= (0.70706*D + 0.70706*Ptop*1) * 36 in/2
= 16,291 in -Ib
Movt= [V1*h + V2 * H/2]*0.7*rho
= 41,008 in -Ib
T= (Movt-Mst)/Df
= (41008 in -Ib - 16291 in-Ib)/36 in
= 687 Ib Net Uplift per Column
Net Seismic Uplift= 687 Ib
Check (2) 0.5" x 3.25" Embed HILTI KWIKBOLT TZ anchor(s) per base plate.
Special inspection is required per ESR 1917.
Fully Loaded:
Top Level Loaded:
Pullout Capacity=Tcap= 1,961 Ib
Shear Capacity=Vcap= 2,517 Ib
L.A. City Jurisdiction? NO
Phi= 1
(1847 Ib/1961 Ib)^1 + (324 Ib/2517 Ib)^1 =
(343 Ib/1961 Ib)^1 + (60 Ib/2517 Ib)^1 =
Tcap*Phi= 1,961 Ib
Vcap*Phi= 2,517 Ib
1.07 <= 1.2 OK
0.20 <= 1.2 OK
TYPE I SELECT-THOMPSON TILE
Page ► / of (3 4/27/2017
www.hiiti.us
Profis Anchor 2.7.2
Company: SCE
Specifier: S.P.
Address: 1815 Wright
Phone I Fax: 909.596.1351 1 909.596.7186
E -Mail: MAIL@SCEINC.NET
Page: 1
Project: Thompson Tile
Sub -Project I Pos. No.: R -042717-51v
Date: 4/28/2017
Specifiers comments: STORAGE RACKING
1 Input data
Anchor type and diameter: Kwik Bolt TZ - CS 1/2 (3 1/4)
Effective embedment depth: hef,act = 3.250 in., hnom = 3.625 in.
Material: Carbon Steel
Evaluation Service Report: ESR -1917
Issued 1 Valid: 6/1/2016 1 5/1/2017
Proof: Design method ACI 318-11 / Mech.
Stand-off installation: eb = 0.000 in. (no stand-off); t = 0.375 in.
Anchor plate: Ix x ly x t = 5.000 in. x 8.000 in. x 0.375 in.; (Recommended plate thickness: not calculated
Profile: S shape (AISC); (L x W x T x FT) = 3.000 in. x 2.330 in. x 0.170 in. x 0.260 in.
Base material: cracked concrete, 3000, fc' = 3000 psi; h = 6.000 in.
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present
edge reinforcement: none or < No. 4 bar
Seismic loads (cat. C, D, E, or F) Tension load: yes (D.3.3.4.3 (d))
Shear load: yes (D.3.3.5.3 (c))
Geometry [in.] & Loading [Ib, in.lb]
2
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL -9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us
Profis Anchor 2.7.2
Company: SCE
Specifier: S.P.
Address: 1815 Wright
Phone I Fax: 909.596.1351 1 909.596.7186
E -Mail: MAIL@SCEINC.NET
Page: 2
Project: Thompson Tile
Sub -Project I Pos. No.: R -042717-51v
Date: 4/28/2017
2 Load case/Resulting anchor forces
Load case: Design loads
Anchor reactions [Ib]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 1847 324 0 324
2 1847 324 0 324
max. concrete compressive strain: - [%o]
max. concrete compressive stress: - [psi]
resulting tension force in (x/y)=(0.000/0.000): 3694 [Ib]
resulting compression force in (x/y)=(0.000/0.000): 0 [Ib]
3 Tension Toad
AY
Tension
01
Load Nua [Ib] Capacity @ Nn [Ib] Utilization r•N = Nua/+ Nn Status
Steel Strength* 1847 8029 24 OK
Pullout Strength* 1847 2625 71 OK
Concrete Breakout Strength** 3694 4296 86 OK
* anchor having the highest loading **anchor group (anchors in tension)
3.1 Steel Strength
Nsa = ESR value
Nsa > Nua
Variables
Ase.N [in.2]
0.10
Calculations
Nsa [Ib]
10705
Results
Nsa [lb]
10705
refer to ICC -ES ESR -1917
ACI 318-11 Table D.4.1.1
luta [Psi)
106000
3.2 Pullout Strength
fc
Npn,f = N9,2500 2, a 2500
Npn.f > Nua
4) steel
0.750
w nonduotile
1.000
Nsa [lb]
refer to ICC -ES ESR -1917
ACI 318-11 Table D.4.1.1
Variables
fc [psi] h a No,2500 [Ib]
3000 1.000 4915
Calculations
ff
2500
1.095
Results
Npn.r [lb]
5384
concrete
0.650
4 seismic
0.750
8029
nonductile
1.000
Nua [lb]
1847
4) Npn.f. [lb]
2625
Nua [Ib]
1847
Input data and results must be checked for agreement with the existing conditions and for plausibility:
PROFIS Anchor ( c) 2003-2009 Hilti AG, FL -9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us
Profis Anchor 2.7.2
Company: SCE
Specifier: S.P.
Address: 1815 Wright
Phone I Fax: 909.596.1351 1 909.596.7186
E -Mail: MAIL@SCEINC.NET
Page: 3
Project: Thompson Tile
Sub -Project I Pos. No.: R -042717-51v
Date: 4/28/2017.
3.3 Concrete Breakout Strength
ANc `1/
Ncbg (ANIc0 tr ec,N W ed,N rV c.N rV cp,N Nb
Ncbg > Nua
AN, see ACI 318-11, PartD.5.2.1, Fig. RD.5.2.1(b)
ANoo = 9 her
1
111 ec.N2 eN � 1.0
1+3hef
111 ed,N = 0.7 + 0.3 ( cam" )< 1.0
1.5her
= MAXI Ca min 1.5hef1 1.0
Cac Cac f
=kca hef5
11
cp,N
Nb
Variables
hef [in.]
3.250
ec1,N [in.]
ec2N [m.]
ACI 318-11 Eq. (D-4)
ACI 318-11 Table D.4.1.1
ACI 318-11 Eq. (D-5)
ACI 318-11 Eq. (D-8)
ACI 318-11 Eq. (D-10)
ACI 318-11 Eq. (D-12)
ACI 318-11 Eq. (D-6)
Ca,min [in.]
0.000
0.000
8.000
Cac [in.] kc a, a fc [psi]
7.500 17 1.000 3000
11 c.N
1.000
Calculations
ANC [In.z ] ANc0 [In.z ] W ec1,N 111 ec2,N til ed.N 111 cp,N Nb [lb]
153.56 95.06 1.000 1.000 1.000 1.000 5455
Results
Ncb9 [Ib] concrete 4, seismic 4, nonduclile 4. Nth, [Ib] Nua [Ib]
8813 0.650 0.750 1.000 4296 3694
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c) 2003-2009 Hilti AG, FL -9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us
Profis Anchor 2.7.2
Company: SCE
Specifier: S.P.
Address: 1815 Wright
Phone I Fax: 909.596.1351 1909.596.7186
E -Mail: MAIL@SCEINC.NET
Page: 4
Project: Thompson Tile
Sub -Project 1 Pos. No.: R -042717-51v
Date: 4/28/2017
4 Shear Toad
Load Vua [Ib] Capacity Vn [Ib] Utilization [3v = Vua/V,, Status
Steel Strength* 324 3572 10 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 648 12338 6 OK
Concrete edge failure in direction y+" 648 3311 20 OK
anchor having the highest loading **anchor group (relevant anchors)
4.1 Steel Strength
Vsa,eq = ESR value
Vsteel > Vua
refer to ICC -ES ESR -1917
ACI 318-11 Table D.4.1.1
Variables
Ase,v [In 2] luta [psi]
0.10 106000
Calculations
Vsa,eq [Ib]
5495
Results
Vsa,eq [Ib] 4) steel 4) nonductile Vsa [Ib] Vua [Ib]
5495 0.650 1.000 3572 324
4.2 Pryout Strength
VcPg = kcP [ (ANc
AN-) Vr ec.N tV ed,N W c,N 91 cp,N Nb]
Vcpg > Vua
ANc see ACI 318-11, Part D.5.2.1, Fig. RD.5.2.1(b)
ANCO
4f ec,N
tV ed,N
Vr cp,N
Nb
= 9 hef
1
1 2eN <_1.0
+3hef
= 0.7 + 0.3 (Camin) 1.0
1.5het
= MAX(ca—min 1.5he1) 1.0
Cac Cac J
=kc1.aV/Ts her5
Variables
kcp
2
l' c,N
1.000
Calculations
AN. [in.2]
153.56
Results
Vcpg [Ib]
17625
hef [in.]
3.250
Cac [in.]
7.500
ANCO [in•2]
95.06
4) concrete
0.700
ACI 318-11 Eq. (D-41)
ACI 318-11 Table D.4.1.1
ACI 318-11 Eq. (D-5)
ACI 318-11 Eq. (D-8)
ACI 318-11 Eq. (D-10)
ACI 318-11 Eq. (D-12)
ACI 318-11 Eq. (D-6)
ec1,N [In.] ec2,N [In.] Ca,min [in.]
0.000 0.000 8.000
kc a a fc [psi]
17 1.000 3000
Vr ecl ,N 4f ec2,N Vr ed,N 41 cp,N Nb [Ib]
1.000 1.000 1.000 1.000 5455
1) seismic 4) nonductile (I) Vcpg [Ib] Vua [Ib]
1.000 1.000 12338 648
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c) 2003-2009 Hilti AG, FL -9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us
Profis Anchor 2.7.2
Company: SCE
Specifier: S.P.
Address: 1815 Wright
Phone I Fax: 909.596.1351 1 909.596.7186
E -Mail: MAIL@SCEINC.NET
Page: 5
Project: Thompson Tile
Sub -Project I Pos. No.: R -042717-51v
Date: 4/28/2017
4.3 Concrete edge failure in direction y+
Avc
Vcbg — (A\ 0) 1p ec,V 111 ed.V y1 c,V lit h,V W parallel,V Vb
(1? Vcbg > Vua
Ave see ACI 318-11, Part D.6.2.1, Fig. RD.6.2.1(b)
= 4.5 cal
1
Avco
1/ ec,V
41 ed,V
111 h.V
Vb
(
1 + 2ev 55 1.0
3Cai
=0.7+0.3(15ca1)-1.0
—
V1.5c01 > 1.0
ha
02
= 1 / 7 (14 ) VUa) X. a Vic Cai5
a
Variables
ca, [in.]
8.000
le [in.]
cat [in.]
3.250
Calculations
Avc [in.2]
120.00
Results
Vcbg [Ib]
4731
8.000
a
1.000
ecv [in.]
0.000
da [in.]
ACI 318-11 Eq. (D-31)
ACI 318-11 Table D.4.1.1
ACI 318-11 Eq. (D-32)
ACI 318-11 Eq. (D-36)
ACI 318-11 Eq. (D-38)
ACI 318-11 Eq. (D-39)
ACI 318-11 Eq. (D-33)
Avco [in.2]
0.500
11/ c.V ha [in.]
1.000 6.000
fe [psi] 111 para llel,V
3000 1.000
111 ec.V 111 ed,V 11/ h,V Vb [lb]
288.00 1.000 0.900 1.414 8920
concrete
0.700
seismic nonductile m Vcbg [Ib] Vua [Ib]
1.000 1.000 3311 648
5 Combined tension and shear loads
RN (31./ C Utilization pN.v [%] Status
0.8608 0.196 5/3 85 OK
RNV= +RV < 1
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c) 2003-2009 Hilti AG, FL -9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us
Profis Anchor 2.7.2
Company: SCE
Specifier: S.P.
Address: 1815 Wright
Phone I Fax: 909.596.1351 1 909.596.7186
E -Mail: MAIL@SCEINC.NET
Page: 6
Project: Thompson Tile
Sub -Project I Pos. No.: R -042717-51v
Date: 4/28/2017
6 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.). This
means load re -distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is assumed to be
sufficiently stiff, in order not to be deformed when subjected to the design loading.. PROFIS Anchor calculates the minimum required anchor plate
thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the rigid base plate assumption
is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the existing conditions and for
plausibility!
• Condition A applies when supplementary reinforcement is used. The factor is increased for non -steel Design Strengths except Pullout Strength
and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout Strength. Refer to
your local standard.
• Refer to the manufacturer's product literature for cleaning and installation instructions.
• Checking the transfer of loads into the base material and the shear resistance are required in accordance with ACI 318 or the relevant standard!
• An anchor design approach for structures assigned to Seismic Design Category C, D, E or F is given in ACI 318-11 Appendix D, Part D.3.3.4.3
(a) that requires the governing design strength of an anchor or group of anchors be limited by ductile steel failure. If this is NOT the case, the
connection design (tension) shall satisfy the provisions of Part D.3.3.4.3 (b), Part D.3.3.4.3 (c), or Part 0.3.3.4.3 (d). The connection design
(shear) shall satisfy the provisions of Part D.3.3.5.3 (a), Part D.3.3.5.3 (b), or Part D.3.3.5.3 (c).
• Part D.3.3.4.3 (b) / part D.3.3.5.3 (a) require the attachment the anchors are connecting to the structure be designed to undergo ductile yielding
at a load level corresponding to anchor forces no greater than the controlling design strength. Part D.3.3.4.3 (c) / part D.3.3.5.3 (b) waive the
ductility requirements and require the anchors to be designed for the maximum tension / shear that can be transmitted to the anchors by a
non -yielding attachment. Part D.3.3.4.3 (d) / part D.3.3.5.3 (c) waive the ductility requirements and require the design strength of the anchors to
equal or exceed the maximum tension / shear obtained from design load combinations that include E, with E increased by wo.
Hilti post -installed anchors shall be installed in accordance with the Hilti Manufacturers Printed Installation Instructions (MPII). Reference ACI
318-11, Part D.9.1
Fastening meets the design criteria!
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL -9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Jttura)
rLioncepts
Engineering
`- - 1815 Wright Ave La Verne. CA 91750 Tel: 909.596.1351 Fax: 909.596.7186
By: BOB Project: THOMPSON TILE & STONE
Project #: R-042717-5LV
Base Plate Configuration: TYPE 1 SELECTIVE RACK
Section
Baseplate= 8x5x3/8
Eff Width=W = 8.00 in a = 3.00 in
Eff Depth=D = 5.00 in Anchor c.c. =2*a=d = 6.00 in
Column Width=b = 4.00 in N=# Anchor/Base= 2
Column Depth=dc = 1.58 in Fy = 36,000 psi
L = 2.00 in
Plate Thickness=t = 0.375 in
Down Aisle Loads Load Case 5:: (1+0.105*Sds)D + 0.75*%(1.4+0.14Sds)*B*P + 0.75*(0.7*rho*E7<= 1.0, ASD Method
Downaisle Elevation
COLUMN DL= 140 Ib Axial=P= 1.1012935 * 140 Ib + 0.75 * (1.535058 * 0.7 * 3800 Ib)
COLUMN PL= 3,800 Ib
Base Moment= 8,000 in -Ib
1+0.105*Sds= 1.1013
1.4+0.14Sds= 1.5351
B= 0.7000
Axial stress=fa = P/A = P/(D*W)
= 80 psi
Moment Stress=fb = M/S = 6*Mb/[(D*B^2]
= 78.8 psi
Moment Stress=fbl = fb-fb2
= 39.4 psi
M3 = (1/2)*fb2*L*(2/3)*L = (1/3)*fb2*LA2
= 53 in -Ib
S -plate = (1)(t^2)/6
= 0.023 in '3/in
fb/Fb = Mtotal/[(S-plate)(Fb)]
= 0.46 OK
Tanchor = (Mb-(PLapp*0.75*0.46)(a))/[(d)*N/2]
= -1,199 Ib No Tension
Cntica/ toad case RMI Sec 21, item 4: (1+0.115dsXOL + (1+0.14505)PL'0.75+EL'0.75 c= 1.0, ASV Method
= 3,217 Ib
Mb= Base Moment*0.75*0.7*rho
= 8000 in -Ib * 0.75*0.7*rho
= 4,200 in -Ib
Axial Load P = 3,217 Ib Mbase=Mb = 4,200 in -Ib
Cross Aisle Loads
M1= wL^2/2= fa*L^2/2
= 161 in -Ib
Moment Stress=fb2 = 2 * fb * L/W
= 39.4 psi
M2= fb1*L^2)/2
= 79 in -Ib
Mtotal = M1+M2+M3
= 292 in-Ib/in
Fb = 0.75*Fy
= 27,000 psi
Pp= 0.7*F'c
= 1,750 psi OK
Tallow= 1,961 Ib
Pstatic= 3,217 Ib
Movt*0.75*0.7*rho= 105,714 in -Ib
Frame Depth= 36.0 in
P=Pstatic+Pseismic= 6,153 Ib
b =Column Depth= 1.58 in
L =Base Plate Depth -Col Depth= 2.00 in
Pseismic= Movt/Frame Depth
= 2,937 Ib
fa = P/A = P/(D*W) M= wL^2/2= fa*L^2/2
= 154 psi = 308 in-Ib/in
Sbase/in = (1)(t^2)/6 Fbase = 0.75*Fy
= 0.023 in^3/in = 27,000 psi
fb/Fb = M/[(S-plate)(Fb)]
0.49 OK
OK
Check uplift Toad on Baseplate
Effec.
Effec.
Check uplift forces on baseplate with 2 or more anchors per RMI 7.2.2.
'When the base plate configuration consists of two anchor bolts located on either side
f the column and a net uplift force exists, the minimum base plate thickness
hall be determined based on a design bending moment in the plate equal
o the uplift force on one anchor times 1/2 the distance from
he centerline of the anchor to the nearest edge of the rack column"
Ta
4- c
Mu
T
b
Elevation
Uplift per Column= 3,694 Ib
Qty Anchor per BP= 2
Net Tension per anchor=Ta= 1,847 Ib
c= 2.00 in
Mu=Moment on Baseplate due to uplift= Ta*c/2
= 1,847 in -Ib
Splate= 0.117 in''3
fb Fb *0.75= 0.438 OK
TYPE I SELECT-THOMPSON TILE Page /a_ oft 3
4/27/20 17
Str tural
I oncepts
Engineering
By: BOB
1815 Wright Ave La Verne. CA 91750 Tel: 909.596.1351 Fax: 909.596.7186
Project: THOMPSON TILE & STONE
Slab on Grade
Configuration: TYPE 1 SELECTIVE RACK
Project #: R-042717-5LV
1111111111111111111111 1 11111111111111111111
SLAB ELEVATION
Base Plate
Effec. Baseplate width=B= 8.00 in
Effec. Baseplate Depth=D= 5.00 in
Column Loads
width=a= 4.00 in
depth=b= 1.58 in
slab
ra
' Cross
Aisle
. • . • Down Aisle
Baseplate Plan View
Concrete
fc= 2,500 psi
tslab=t= 6.0 in
teff= 6.0 in
phi=0= 0.6
Soil
fsoil= 1,000 psf
Movt= 140,952 in -Ib
Frame depth= 36.0 in
Sds= 0.965
0.2*Sds= 0.193
midway dist face of column to edge of plate=c= C.00 in
midway dist face of column to edge of plate=e= 3.29 in
DEAD LOAD=D= 140 Ib per column
unfactored ASD load
PRODUCT LOAD=P= 3,800 Ib per column
unfactored ASO load
Papp= 2,546 Ib per column
P-seismic=E= (Movt/Frame depth)
= 3,915 Ib per column
unfactored Limit State load
B= 0.7000
rho= 1.0000
Sds= 0.9647
1.2 + 0.2*Sds= 1.3929
0. 9 - 0.20Sds= 0.7071
Puncture
Load Case 1) (1.2+0.2Sds)D + (1.2+0.2Sds)*B*P+ rho*E RMI SEC 2.2 EQTN
= 1.39294 * 140 Ib + 1.39294 * 0.7 * 3800 Ib + 1 * 3915 Ib
= 7,815 Ib
Load Case 2) (0.9-0.2Sds)D + (0.9-0.2Sds)*B*Papp + rho*E RMI SEC 2.2 EQTN 7
= 0.70706 * 140 Ib + 0.70706 * 0.7 * 2546 Ib + 1 * 3915 Ib
= 5,274 Ib
Load Case 3) 1.2*D + 1.4*P RMI SEC 2.2 EQTN 1,2
= 1.2*140 Ib + 1.4*3800 Ib
= 5,488 Ib
Effective Column Load=Pu= 7,815 Ib per column
Apunct= [(c+t)+(e+t)]*2*t
= 255.48 in^2
Slab Bending
Fpunct= 2.66*phi*sgrt(fc)
= 79.8 psi
fv/Fv= Pu/(Apunct*Fpunct)
= 0.383 < 1 OK
Pse=DL+PL+E= 7,815 Ib
Asoil= (Pse*144)/(fsoil)
= 1,125 in^2
x= (L -y)/2
= 8.5 in
Fb= 5*(phi)*(fc)^0.5
= 150. psi
L= (Asoil)^0.5
= 33.54 in
M= w*x^2/2
= (fsoil*x^2)/(144*2)
= 253.8 in -Ib
y= (c*e)^0.5 + 2*t
= 16.4 in
S -slab= 1*teff^2/6
= 6.0 in^3
fb/Fb= M/(S-slab*Fb)
= 0.282 <1,OK
TYPE 1 SELECT-THOMPSON TILE
Page /3 of � 4/27/2017
5/1/2018
City of Tukwila
Department of Community Development
DOUG WILLIAM
3500 W VALLEY HWY N - SUITE 101
AUBURN, WA 98001
RE: Permit No. D17-0144
THOMPSON TILE & STONE
575 STRANDER BLVD
Dear Permit Holder:
Allan Ekberg, Mayor
Jack Pace, Director
In reviewing our current records, the above noted permit has not received a final inspection by the City of Tukwila Building
Division. Per the International Building Code, International Mechanical Code, Uniform Plumbing Code and/or the National Electric
Code, every permit issued by the Building Division under the provisions of these codes shall expire by limitation and become null
and void if the building or work authorized by such permit has not begun within 180 days from the issuance date of such permit, or if
the building or work authorized by such permit is suspended or abandoned at any time after the work has begun for a period of 180
days. Your permit will expire on 6/25/2018.
Based on the above, you are hereby advised to:
1) Call the City of Tukwila Inspection Request Line at 206-438-9350 to schedule for the next or fmal inspection. Each
inspection creates a new 180 day period, provided the inspection shows progress.
-or-
2) Submit a written request for permit extension to the Permit Center at least seven(7) days before it is due to expire.
Address your extension request to the Building Official and state your reason(s) for the need to extend your permit.
The Building Code does allow the Building Official to approve one extension of up to 180 days. If it is determined that your
extension request is granted, you will be notified by mail.
In the event you do not call for an inspection and/or receive an extension prior to 6/25/2018, your permit will become null and void
and any further work on the project will require a new permit and associated fees.
Thank you for your cooperation in this matter.
Sincerely,
Bill Rambo
Permit Technician
File No: D17-0144
6300 Southcenter Boulevard Suite #100 • Tukwila, Washington 98188 • Phone 206-431-3670 • Fax 206-431-3665
June 15, 2017
0
City of Tukwila
Department of Community Development
DOUG WILLIAM
3500 W VALLEY HWY N - SUITE 101
AUBURN, WA 98001
RE: Correction Letter # 1
DEVELOPMENT Permit Application Number D17-0144
THOMPSON TILE & STONE - 575 STRANDER BLVD
Dear DOUG WILLIAM,
Allan Ekberg, Mayor
Jack Pace, Director
This letter is to inform you of corrections that must be addressed before your development permit can be approved. All
correction requests from each department must be addressed at the same time and reflected on your drawings. I have
enclosed comments from the following departments:
BUILDING DEPARTMENT: Allen Johannessen at 206-433-7163 if you have questions regarding these comments.
• (GENERAL NOTE)
PLAN SUBMITTALS: (Min. size 11x17 to maximum size of 24x36; all sheets shall be the same size. New revised
plan sheets shall be the same size sheets as those previously submitted.)
(If applicable) "STAMP AND SIGNATURES" "Every page of a plan set must contain the seal/stamp, signature of
the licensee(s) who prepared or who had direct supervision over the preparation of the work, and date of signature.
Specifications that are prepared by or under the direct supervision of a licensee shall contain the seal/stamp,
signature of the licensee and the date of signature. If the "specifications" prepared by a licensee are a portion of a
bound specification document that contains specifications other than that of an engineering or land surveying
nature, the licensee need only seal/stamp that portion or portions of the documents for which the licensee is
responsible." It shall not be required to have each page of "specifications" (calculations) to be stamped and signed;
Front page only will be sufficient. (WAC 196-23-010 & 196-23-020)
(BUILDING REVIEW NOTES)
1. Revise all plan set notes to show compliance with all 2015 International and Washington State Codes.
2. For maximum common path of egress travel distance, an exit access doorway for "S" occupancy and occupant
load exceeds 29, shall not exceed 100 feet from any point of the building. Provide 2nd exit door location (at least
1/3 diagonal apart from existing door #1). (IBC Table 1006.2.1)
3. In addition to the egress plan, emergency illumination shall be provided along the designated common paths of
egress and shall have at least an average 1 foot-candle and a minimum at any point of 0.1 -foot candle measured
along the path of egress at the floor level. Emergency lighting shall also be required at exterior landings or exit
discharge doorways where two or more exits are required. Show exit signs and specify emergency illumination per
code. (IBC 107.2.3 & Section 1008)
4. New base plate welding shall require special inspection and special inspection shall be provided for the
installation of the anchor bolts securing rack base plates to the concrete. Engineer or record shall provide a table
matrix specifying type of required special inspections. Special inspection notes shall be shown on the plan sheets
with the relative details. (2015 IBC CHAPTER 17, 1704.2.5 & 1705.12.7)
Note: In response to these corrections for this permit -plan -review, other corrections may be needed.
6300 Southcenter Boulevard Suite #100 • Tukwila Washington 98188 • Phone 206-431-3670 • Fax 206-431-3665
FIRE DEPARTMENT: Al Metzler at 206-971-8718 if you have questions regarding these comments.
The existing ceiling fire sprinkler density is not adequate for the proposed type/quantity of storage. Provide a
technical report from a Washington State Licensed Fire Protection Engineer (FPE) that determines the required
sprinkler density per NFPA 13.
A separate submittal must be made to the Tukwila Fire Marshal's Office to obtain a fire sprinkler permit for the
necessary modifications.
Please address the comments above in an itemized format with applicable revised plans, specifications, and/or other
documentation. The City requires that two (2) sets of revised plan pages, specifications and/or other documentation be
resubmitted with the appropriate revision block.
In order to better expedite your resubmittal, a 'Revision Submittal Sheet' must accompany every resubmittal. I have
enclosed one for your convenience. Corrections/revisions must be made in person and will not be accepted through the mail
or by a messenger service.
If you have any questions, I can be reached at 206-431-3655.
Sincerely,
Bill Rambo
Permit Technician
File No. D17-0144
6300 Southcenter Boulevard Suite #100 • Tukwila Washington 98188 • Phone 206-431-3670 • Fax 206-431-3665
9ERMIT COORD COPY. o
PLAN REVIEW/ROUTING SLIP
PERMIT NUMBER: D17-0144 DATE: 10/24/17
PROJECT NAME: THOMPSON TILE & STONE
SITE ADDRESS: 575 STRANDER BLVD
Original Plan Submittal
X Response to Correction Letter # 1
Revision #
Revision #
before Permit Issued
after Permit Issued
DEPARTMENTS:
sitto c ID -)-17
Building Division
Public Works
Alk /ilkc 10-31--t7
re
Fire Prevention
Structural
Planning Division
❑ Permit Coordinator
PRELIMINARY REVIEW:
Not Applicable ❑
(no approval/review required)
DATE: 10/26/17
Structural Review Required
REVIEWER'S INITIALS: DATE:
APPROVALS OR CORRECTIONS: DUE DATE: 11/23/17
Approved ❑ Approved with Conditions
Corrections Required ❑ Denied ❑
(corrections entered in Reviews) (ie: Zoning Issues)
Notation: S1$cj, \ cVeirS
REVIEWER'S INITIALS:
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg 0 Fire 0 Ping 0 PW ❑ Staff Initials:
12/18/2013
PERMIT COORD COSY
PLAN REVIEW/ROUTING SLIP
PERMIT NUMBER: D17-0144 DATE: 05/25/17
PROJECT NAME: THOMPSON TILE & STONE
SITE ADDRESS: 575 STRANDER BLVD
X Original Plan Submittal
Response to Correction Letter #
Revision #
Revision #
before Permit Issued
after Permit Issued
DEPARTMENTS:
A -1"C
Building Division
Public Works
s-)47-1
■
Co (0.11'17
Fire Prevention
Structural
Planning Division
❑ Permit Coordinator
PRELIMINARY REVIEW:
Not Applicable ❑
(no approval/review required)
DATE: 05/30/17
Structural Review Required
REVIEWER'S INITIALS: DATE:
APPROVALS OR CORRECTIONS:
Approved
Corrections Required
(corrections entered in Reviews
DUE DATE: 06/27/17
❑ Approved with Conditions ❑
Denied
(ie: Zoning Issues)
Notation:
REVIEWER'S INITIALS:
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections:
Ping PW 0 Staff Initials:
12/18/2013
0
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670
Web site: http://www.TukwilaWA.gov
REVISION
SUBMITTAL
Revision submittals must be submitted in person at the Permit Center.
Revisions will not be accepted through the mail, fax, etc.
Date: I O/ _4 / j 7
Plan Check/Permit Number:
01-7- oi4q
❑ Response to Incomplete Letter #
a Response to Correction Letter # 1
❑ Revision # after Permit is Issued
❑ Revision requested by a City Building Inspector or Plans Examiner
❑ Deferred Submittal #
1
Project Name: -01o .n ()SOY) ie v{ 01)
Project Address: 5 7S S -ka'o1 lvd
Contact Person: P,'1AfI Deo..,n
Summary of Revision:
. Rev'Seol cAmp/'a.i e 1'o( Zo/S Znfl arfot WA c J s.
2. Ex'fSi-i'49 yw' eac,4 Joey .rl p/aee, pevisea{ eyes pfd
3. Addek ex►s4,'1 exR- 111944s -to o(law n9.
RECEIVED
CITY OFTUKWILA
OCT 2 4 2017
PERMIT CENTER
Phone Number: (S03) 6- 076/
L -I-. Spe-cial ;n ped;o,o t✓ornio%-/e
DeraMneni'
S Is CA p(a.c e, cti� (2\ 14'/ k , 1)o s foray6 above 12 . Com, lyes u i -A
CfArr'en+ Spe k 7 S9S ein.
Sheet Number(s):
"Cloud" or highlight all areas of revision includin
to of revisio,
c
Received at the City of Tukwila ]P/e�rmit Center by: �✓CJLJI'
I Entered in TRAKiT on L V -4)'14%."( 7
W:\Permit Center\Templates\Fomis\Revision Submittal Formdoc
Revised: August 2015
RAYMOND HANDLING CONCF ? S CORP (--1
Horne Espanol Contact
Safety & Health Claims & Insurance
Washington State Department of
Labor & Industries
Search L&I
Page 1 of 2
A -Z Index Help lbtpL&1
Workplace Rights Trades & Licensing
RAYMOND HANDLING CONCEPTS CORP
Owner or tradesperson
HEALY, HEIDI REBEE
Principals
HEALY, HEIDI REBEE, VICE PRESIDENT
JONES, DONALD JESSE, VICE PRESIDENT
RAYMOND, STEPHEN SPENCER, CHIEF
EXECUTIVE OFFICER
KOEL, STEVE
(End: 09/25/2017)
STERNBERG, PAUL
(End: 09/25/2017)
GABORRO, ALEX
(End: 09/25/2017)
WA UBI No.
604 102 532
41400 BOYCE ROAD
FREMONT, CA 94538
253-333-2100
Business type
Corporation
License
Verify the contractor's active registration / license / certification (depending on trade) and any past violations.
Construction Contractor
License specialties
GENERAL
License no.
RAYMOHC034KB
Effective — expiration
05/02/1997-10/23/2019
Bond
FEDERATED MUTUAL INS CO
Bond account no.
1090263
Active.
Meets current requirements.
$12,000.00
Received by L&I Effective date
09/28/2001 07/22/2001
Expiration date
Until Canceled
Insurance
Federated Mutual Ins Co $1,000,000.00
Policy no.
9045549
Received by L&I Effective date
08/07/2017 10/01/2017
Expiration date
10/01/2018
Help us improve
https://secure.lni.wa.gov/verify/Detail.aspx?UBI=604102532&LIC=RAYMOHC034KB&SAW= 11/8/2017
APPLICABLE CODES
SHEET INDEX
2015 INTERNATIONAL BUILDING CODE
2015 INTERNATIONAL FIRE CODE
SCOPE OF WORK
PROVIDE AND INSTALL PALLET RACK
OCCUPANCY CLASSIFICATION
B-1, OFFICE
S-1. STORAGE
APN 0223300010
TYPE OF CONSTRUCTION
FIRE SPRINKLED
NUMBER OF STORIES
BUILDING SQ. FT.
OFFICE SQ. FT.
WAREHOUSE SQ. FT.
SCOPE SQ. FT.
VB
YES
1
81,200 SQ.FT.
274 SQ.FT.
19,229 SQ.FT.
19,229 SQ.FT.
COVER SHEET
SITE PLAN
PLAN VIEW
ELEVATIONS
EGRESS PATH
RH1.0
RH2.0
RH3.0
RH3.1
RH4.0
575 STRANDER BLVD
TUKWILA, WA, 98188
It
COPY
Noe r7— 01 i'fq
Is to •re and omissfo .
of construction dnot authorize
the violation of nny adopted code or ordinance. Receipt
of approved Field Copy d conditi b Is ecimowledged:
By: ,-
Date: / (
14(/7
City of Tukwila
BUILDING DIVISION
U)
z
0
w
0
let
CC
CC
y
LU
Col
2
0
"IT'S NOT JUST BUSINESS, IT'S PERSONAL"
FOR ASSISTANCE CALL: 800.675.2500
DESCRIPTION:
INITIAL RELEASE
4<
FIRE SPRINKLER SYSTEM DATA
COMMODITIES TO BE STORE
D
VICINITY MAP
SPRINKLER HEIGHT: +1- 28'-0"
SYSTEM TYPE: DRY SPRINKLER
BASIS OF DESIGN:
DENSITY: .20/1950 GPM/SQ.FT.
DESIGNED AREA OF DISCHARGE: 1950 SQ.FT.
TEMPERATURE OF HEAD: 286 DEGREES
WATER FLOW RATE: 0.20 GPM
FLOW DEMAND BOR: 690 @ 130 PSI
NOTE: ANY CHANGES TO THE FIRE SPRINKLER SYSTEM
REQUIRES A SEPARATE SUBMITTAL, PERMIT, PLAN REVIEW,
INSPECTIONS AND FEES.
A MODIFICATION TO THE EXISTING FIRE SPRINKLER SYSTEM
WILL BE APPLIED FOR ON A SEPARATE PERMIT SUBMITTAL.
S
CLASS I (PALLETIZED TILE AND STONE) ENCAPSULATED
MAXIMUM STORAGE HEIGHT FOR RACK STORAGE: 18'-0"
HIGH PILED STORAGE SHALL COMPLY WITH THE REQUIREMENTS OF THE
2015 IBC CHAPTER
THIS FACILITY IS NOT ACCESSIBLE TO THE GENERAL PUBLIC.
PATH OF TRAVEL TO AND WITHIN EXITS IN THE BUILDING SHALL BE
IDENTIFIED BY ILLUMINATED EXIT SIGNS CONFORMING TO THE
REQUIREMENTS OF 2015 IBC
FIRE LANES / EMERGENCY VEHICLE ACCESS ARE AVAILABLE ONE THREE
SIDES OF THE BUILDING, RAIL ROAD TRACK RUNS ALONG THE BACK
ALL PORTIONS OF THE BUILDING SHALL BE WITHIN 75 FEET OF A FIRE
EXTINGUISHER. THE MINIMUM SIZE OF THE FIRE EXTINGUISHER SHALL BE
3-A: 40 B:C.
STORAGE RACKS WILL HAVE SIGNS STATING WEIGHT LOAD AND MAXIMUM
HEIGHT LIMITS.
CONTRACTOR INFORMATION
STRUCTURAL ENGINEER
RAYMOND HANDLING CONCEPTS
3500 W VALLEY HWY N. SUITE 101
AUBURN, WA 98001
WA. CONTRACTOR LICENSE# RAYMOHC034KB
DOUG WILLIAM
253-335-2410
dwilliam@raymondhandling.com
STRUCTURAL CONCEPTS ENGINEERING
1615 YEAGER AVE.
LA VERNE, CA. 91750
PH: 909-596-1351
PROJECT SITE
erRvdi
SEPARATE PERMIT
REQUIRED FOR:
Piseetrici
umbing
I'Vtn.3 6�ipfng
City of Tukwila
BUILDING DIVISION
5 Strander Boulevard
REVIEWED FOR
CODE COMPLIANCE
APPROVED
NOV 0 7 2017 r`
REVISIONS
No changes shall be made to the scope
of work withou.t prior approval of
Tukwila Building Division.
NOTE: Revisions will require a new plan submittal
and may include additional plan review fees.
CORRECiTIOM
LTR#..._4
D �7
RECEIVED
CITY OF TUKWILA
OCT 2 4 2017
PERMIT CENTER
Lig
STA\3E�
LO
RAYMOND HANDLING
CONCEPTS CORP.
FREMONT OFFICE:
41400 BOYCE ROAD
FREMONT, CA 94583
The information on the drawing is prepared with the
intern ofcotm.nicat g a concept and design that is
'het intellectual property d Raymond Hahvig
Concepts Corporation. It is not intended kr other
organizations as a means of (poling, assigning /aid
i orergaag alternatives.
PROJECT #: 9750
PROJ. DESC: RACK
PALLET POS. ##
SQ.FT.
NA
DRAWN BY: O.H
5 DATE: 04/26/17
SCALE: NTS
SHEET OF: 1/5
REVISION: 0
SHEET NO.
RHtO
1
HANDLING CONCEPTS CORPORATION
"IT'S NOT JUST BUSINESS, IT'S PERSONAL"
FOR ASSISTANCE CALL: 800.675.2500
I
c
DOTES ANb G(IAkEN T5: CHICAGO TITLE INSURANCE COMPANY DESCRIP11ON•
(.GAL • POSSIBLE ENGRNCROACH ENTS;
t) BY GRAPHIC PLOTTING CNLY. THIS PROPERTY IS IN ZONE X (AREAS OF 500-
YEAR FLOOD; OF 100-YEAR now MTH AVERAGE DEPTHS OF LESS PRELIMINARY TITLE REPORT NO. 1198012 TRACT 1, ANDOVER INDUSTRIAL PARK NO. 4. ACCORDING TO THE PLAT THERE ARE Na ENCROACHMENTS BY IMPROVEMENTS ON THE ADJOINING
AREAS
'EAtt
?-
1 FOOT OR DRAINAGE AREAS LESS 'THAN 1 90UARE ULE; AND SCHEDULE Q - EXCEPTIONS; THEREOF, RECORDED IN VOLUME 79 OF PLATS. PACE(S) 39 AND 40. IN KING PROPERTY ONTO SUBJECT PROPERTY, AND NO ENCROACHMENTS BY
s
m
OR LOCATED ON PLOTTEDEECT PROPERTY OVER ANY ADJOINING
AREAS PROTECTED BY LEVEES FROM 100-YEAR FLOOD). OF THE FLOOD 1) UNDERGROUND ELECTRIC EASEMENT RECORDED JANUARY 12. 1966 AS COUNTY, WASHINGTON. PROPERTY
INSURANCE RATE MAP. COMMUNITY PANEL NO. 53033C 0978F WHICH INSTRUMENT NUMBER 5975876, AFFECTS SUBJECT PROPERTY. PLOTTED.PROPERTY OR OVER ANY OR PLOTTABLE EASEMENTS.
BEARS AN EFFECTIVE DATE OF MAY 16, 1995 AND IS NOT iN A SPECIAL THE PROPERTY DESCRIBED AND SHOWN AN HEREON IS THE SAME PROPERTY AS
FLOOD HAZARD AREA. NO FIELD SURVEYING WAS PERFORMED TO DESCRIBED IN THE CHICAGO TITLE INSURANCE COMPANY TITLE PRELIMINARY •
2) RAILROAD EASEMENT AS DIOYON ON 7HE PLAT OF ANDOVER INDUSTRIAL TITLE REPORT NO. 1198012, DATED JANUARY 26, 2006. SURVEYORS CERTIFICATION; LEGEND:
FLOODDETER
THIS ZONE AND AN ELEVATION CERTIFICATE MAY BE NEEDED PARK NO. 4 RECORDED IN VOLUME 79 OF PLATS, PAGES 39 AND 40, I hereby certfy to The Prudential Insurance Company of America, TA Associates Realty, The Realty
TO VERIFY THIS DETERMINATION CR APPLY FOR A VARIANCE FROM THE AFFECTS SUBJECT PROPERTY, PLOTTED. Associates Fund V% L.P-. and their respective successors and a -EASEMENT UNE
FEDERAL EMERGENCY MANAGEMENT AGENCY. r'e1ee ' assigns, and Chicago Title Insurance
61
Company that this is a true and coned survey of 551-581 5trander Boulevard. TukwTa Washirtgtan, PROPERTY UNE
3) EASEMENTS CONTAINED iN STATUTORY WARRANTY DEED RECORDED and show's tie correct location of the buildings and improvements situated on such fond and all Qs=
- - BUILDING SETBACK UNE
2) PER THE CITY OF TTUKOFLA PLANNING DEPARTMENT. THIS SITE t5 MARCH 31, 1966 AS INSTRUMENT NUMBER 6008247. AFFECTS SUBJECT easements. rights-of-way, setback lines. and similar restrictions of record affecting the property
`i
0
CURRENTLY ZONED TUC (TUI(WL.A URBAN CENTER); THE CURRENT PROPERTY. PLOTTED- surveyed. Tie buf1d'xsgs and Improvements do not overhang or encroach upon any easement or CENTERLINE
ZONING ALLOWS FOR THE CURRENT USE OF THE SITE. rights-of-way of others, and there ore no encroachments either wayacross the property rases. The/
Prof Y ' / / / / / / , / / / 'BUILDING NG LIN£
TUC ZONING REQUIREMENTS FOR THIS SITE:
s
r
z
'ori
Q
REVISIONS
REV. DATE:
4) SEWER EASEMENT RECORDED AUGUST 17, 1967 AS INSTRUMENT NUMBER property surveyed contal ns 8.93 acres of land and 130 parking
SETBACKS: 6220747. AFFECTS SUBJECT PROPERTY. PERMANENT EASEMENT PLOTTED. floodlaiarea. P g spaces, and Is not located within o
-
a
V
to
PUBLIC STREET SIDE: 15 FEET (STRANDER BLVD) UNABLE TO DETERMINE AFFECT OF TEMPORARY CONSTRUCTION
SIDE: 10 FEET EASEMENT, DOCUMENT NOT LEGIBLE
EDGE OF ASPHALT
I hereby certfy that this map or plat and the survey on which it is based were made in accordance 6' CONCRETE CURB
8
o
n
Cha
40
Gn
REAR: 10 FEET
Y with the 'Mirimurn Standard Data Requirements for ALTA/AGSM Land Title Surveys" jointlyU
C.
p
y
HEIGHT: 115 FEET 5) RAILROAD EASEMENT RECORDED APRIL 21. 1975 AS INSTRUMENT NUMBER
M established and adopted by ALTA and NSPS in 2005. and includes Items 2-4, 6, 7(a). 7(b)(1), x x 6' CHAIN LINK FENCE
>
U
Lei
DESCRIPTION:
INITIAL RELEASE
7504210345, AFFECTS SUBJECT PROPERTY, PLOTTED- sr=a :.ti;
PARKING: 1 PER 2,000 SQUARE FEET FOR WAREHOUSE USE. 3 PER
1.000 SQUARE FEET FOR OFFICE USE
7(b)(2), 7(c), 8-10. 11(o). 11(b), 13, 14, 15 and 16-18 of Table A thereof- Pursuant to the Accuracy
= Standards as adopted by ALTA and NSPS and In effect on the date of this certification. the
-.
: , �
CONCRETE SURFACE
X
6) US WEST EASEMENT RECORDED JUNE 24, 1993, AS INSTRUMENT NUMBER
93(36240702, AFFECTS SUBJECT PROPERTY, PLOTTED.
3) TOTAL LAND AREA 389,165 SQUARE FEET OR 8.93 ACRES, MORE OR 1 FSS
4) THE BUILDING AREA SHOWN HEREgi WAS QE7ERWIN£D BY THE FIELD 7) CONVEYANCE EXISTING UTILITY EASEMENT FOR USE AS SIDEWALK
E ERNE
undersigned further certifies that In
. State of Washington the Relative Position
positional tolerance.
sr A .:=R"ra
my professional opinion. as a land surveyor registered in the
Accuracy of thls survey does not exceed the Womble `r7 FIRE HYDRANT
WATER METER
o
_
s
F`-
NATES ONLY ACKNOWLEDGES SIGNED AND STAMPED MAPS AND DRAWINGS. NO RESPONSIBIUTY OR UABIUTY IS EXPRESSED OR IMPLIED FOR ELECTRONIC DATA AND/OR REPRODUCED MAPS AND DRAWINGS.
MEASUREMENTS OF THE EXTERI WALLS AT TVD LEVET EASEMENT RECORDED NOVEMBER 30, 1995 AS INSTRUMENT 9511300506.
AFFECTS SUBJECT PROPERTY, PLATTED.
% r f
r/ -
SITE
L 0
0E4 WA UR)-
1 iyFjr
�� tt WATER GAS VALVE
r WATER/GAS
i C SANITARY SEWER MANHOLE
S) TOTAL PARKING SPACES 130 >s 130 REGULAR SPACES
THERE ARE 28 TRUCK PARKING SPACES AT LOADING DOCKS. 8) COVENANTS. CONDITIONS, AND 52564 3, RECORDED FEBRUARY 28.
1961 AS INSTRUMENT NUMBER 5256443, AND AMENDED SEPTEMBER 22, s EE, CR
1961 AS INSTRUMENT NUMBER 5332848, NOVEMBER 1. 1962 AS
ACCESS TO PROPERTY VIA PUBUC RIGHT OF WAYS: INSTRUMENT NUMBER 5500900. FEBRUARY 10. 1967 AS INSTRUMENT�
Y:
z
%)
Ot
,� a
•A ��
r
r
A w <� TELEPHONE MANHOLE
i 1/20/06 STORM SEWER MANHOLE
STANDER BOULEVARD NUMBER 6138154. JUNE 12. 1967 AS INSTRUMENT NUMBER 6188232. MAY 24, ` =s� Mitchell Duryea
THE UNDERGROUND t11DLITIES SHffeYN 1967 AS INSTRUMENT NUMBER 6180358, AND JUNE 6, 1994 AS INSTRUMENT LS 33658
7)HEREON ARE G OMP1l ED FROM THE NUMBER 940$061388, AFFECTS SUBJECT PROPERTY, PLOTTED. Exp. 9/17/07
VISIBLE SURFACE FEATURES OF THESE UTILITIES. AN EXACT LOCATION 1) EASEMENTS:
s
t`Mss ,�_'�_,,�p58 "
/' CtyS °yJg
vygt LAAO
r Date UTILITY MANHOLE
f 0 CATCH BASIN
i
15 FOOT UTILITY EASEMENT ON FRONTAGE STREETS.
OF THESE UTILITIES WAS NOT PERFORMED FOR THIS SURVEY. BEFORE 27 FOOT RAIL AND UTILITY EASEMENT AT REAR OR SIDE VICINITY MAP
DIGGING, CAU. THE APPROPRIATE LOCAL. UTILITY LOCATE SERVICE FOR
D(P1RRS: 9-17-07
UGHT STANDARD
•IV ELECTRIC VAULT
OF PROPERTY.- TO SCALE •••
FIELD) LOCATIONS OF UNDERGROUND UTILITY LINES. 5 FOOT EASEMENT ON EACH SIDE OF THE COMMON
BOUNDARY OF ANY T O TRACKS.
8) PROPERTY ADDRESS: 551-581 STRANDER BLVD.. TUKWILA. WA 2) PARKING REQUIREMENT OF ONE PASSENGER CAR SPACE PER 1.000
UILOINO AREA.
SQUARE FEET OF Bu
9) BASIS OF BEARINGS: THE BEARING OF NORTH 42'36'45" WEST ALONG THE 3) BUILDING SETBACK MINIMUMS OF 60 FEET ON FRONT AND 15 FEET ON
EASTERLY UNE E TRACT C ANDOVERDIllINDUSTRIAL PARK NO. 4, ACCORDING SIDES
TO THE PLAT THEREOF, RECORDED VOLUME IA OF PLATS. PAGE(S) 39
AND 40, IN KING COUNTY. WASHINGTON. WAS TAKEN AS THE BASIS OF BEARINGS 9) BUILDING SETBACK LINES AS SHOWN ON THE PLAT OF ANDOVER
SHOWN UPON THIS SURVEY. INDUSTRIAL PARK N0. 4 RECORDED IN VOLUME 79 OF PLATS, PAGES 39
AND 40, AFFECTS SUBJECT PROPERTY, PLOTTED.
10) TAX MAP PARCEL NO. 0223300010
10) RESTRICTIONS AS SHOitiN ON THE PLAT OF ANDOVER INDUSTRIAL PARK
11) AT THE TiNE OF 114E FIELD SURVEY. THERE WAS NO EVIDENCE OF N0. 4 RECORDED IN VOLUME 79 OF PLATS. PAGES 39 AND 40. AFFECTS
,-- LL JUNCTION BOX
[J UTILITY VAULT
POWER TRANSFORMER
- . ._ . -- - __ EXISTING UNDERGROUND STORM SEVER LINE
: _ _ _ _ ,. ..... _ - - EXISTING UNDERGROUND SANITARY SEWER LINEZ‹.111.<1.1
EXISTING UNDERGROUND WATER UNE
EXISTING UNDERGROUND FIBER OPTIC UNE
FOUND AS NOTED
111
IC
'
�'•'�'r .�.
4
„,..-.1, �
M k� . ,
.
a.,
.tt-�
M
• e r^
_ , '
T^:.,
fir, i
r t
; y U t W
�
2 T., Pr,
°r-
v yam
qas
'1T� r iii'T?t J Y V'R
f
i . s'k' fist
575 STRA\DER BLVD, TJ'<WILA, WA, 98188 S1117. PLAN
CURRENT EARTH MOVING WORK, BUILDING CONSTRUCTION. OR BUILDING SUBJECT PROPERTY. REFERENCES 119,1 NUMBER 8. (SEE ITEM 8).
ADDITIONS.
12) PURSUANT TO THE CITY OF TLUKMALA PLANNING DEPARTMENT, 11) RIGHT OF THE PUBLIC TO MAKE NECESSARY SLOPES FOR CUTS OR FILLS
ARE 110 CURRENT PROPOSALS FOR ANY CHANGESDA STREET THEREE.1T OF UPON SAID PROPERTY IN THE REASONABLE ORIGINAL GRADING OF STREETS,
WAY LINES ADJACENT TO THE SUBJECT PROPERTY SHOWN ON THIS AVENUES, ALLEYS, AND ROADS AS DEDICATED ON THE PLAT OF ANDOVER9
INDUSTRIAL PARK N0. 4 RECORDED IN VOLUME 79 OF PLATS, PAGES 39
SURVEY. AND 40, AFFECTS SUBJECT PROPERTY, NOT PLOTTED. GENERAL IN NATURE.
13) AT THE TIME OF THE FIELD SURVEY THERE WAS NO EVIDENCE OF SITE
USE AS A SCUD WASTE DUMP. SUMP OR SANITARY LANDFILL
14) AT THE TIME OF THE RaDUSE FOR AS AA CEMETERY OR CROWD.RVEY, THERE S NO EVIDENCE OF SITE 4
o
,
, 40\
GRAPHIC SCALE
m 6o exs
f L/S LANDSCAPED AREA
t
15) EASEMENT RIGHTS: PLOTTABLE EASEMENTS ARE SHOWN FROM THE
OWNER SUPPLIED TITLE
w �G ®`s
11.11111.
Gtr r��� I%�I��Si;��
w.;,.G;;�c�4���u�s��i�)�?�
REPORT. NON-PLOTTABLE EASEMENTS ARE
NOTED ON THE SURVEY AS BEING T
SERVICE IS U ITER TO REPORTING C EASEW£tJT LOCATIONS R / (INFEET )
1 WE
ft-
1 tach •• 40 ft-
STRONGLY RECOMMEND LEGAL COUNSEL TO BE RETAINED TO REPORT ,(�,,
�
ON TITLE PAPERS 1N THEIR ENTIRTY! vE
I4
16 THIS IS AN AS-BUILT SURVEY PREPARED IN ACCORDANCE WITH THE
'TITLE SURVEYS. ARD DETAIL RE TS FOR ALTA/AGSM LAND O y /
\,. N 0144'27 E
17) THE ON-SITE STORM DRAINAGE SYSTEif FOR THIS PROPERTY IS DESIGNED LP 61.32'
TO COLLECT ALL. ON-SITE STORM WATER USING THE CATCH BASINS AS %'
COLLECTION POINTS, THEN DEPOSITING THE STORM WATER INTO THE \Y' ` \ �i
PUBUC STORM SEWER SYSTEM + f r,. ,� �\ FOUND t-1/2' - r
) ('1
C, / 3 8, I
f8) THIS SURVEY WAS PREPARED FOR THE PURPOSES OF OBTAINING AN 4i r \ \ IRON PIPE W/TAG cte t-«.) TRACT 39.).
ALTA/AGSM
ANDOVER 1
551-581 STRAP
EXTENDED COVERAGE TITLE INSURANCE POLICY AND DOES NOT 0. / r \ \ \
CONTAIN SUFFICIENT DETAIL FOR DESIGN PURPOSES. ADDITIONAL l P r / / ~�'-
v , . e -
SURVEYING 1U BE REQUIRED FOR DESIGN PURPOSES./ - T )
a°,'- r s.:Ar.Y_._ (79 PW 39 L -
)1 Lti H �Y � e� r,s a;_rMr _ N 61'41'06' W
- r •_ _---_� - _- �-- ASP114:..7 s Krzc _ J U”: tri CArE ri;7 (,;' cs;5.9 60.78' r
:5.�e_<T) { M
_.
-../ -- -..� .� %15 • `_ __ �_ N 42'38'45' W 755.44' (BASIS OF BEARINGS) i I FUND 1-1/2• c
/'`'
19) THE USE OF THE WORD *CERTIFY" OR 'tEUt1IFiCATtOfI' WITHIN THIS s: / • �. �, ""' --
h� "`.,, i l--A:tSAL c;:uAc:_i IRON PIPE W/
SURVEY ONLY CONSTITUTES AN EXPRESSION Of PROFESSIONAL OPINION , y , / ._.« '"•r ` ': -. r -. fs • e
_ WOOD
T5 Df GS SHOWN ON THIS SURVEY, AND ' // / \ :: " --- " -;- _ PLUG
REGARDING THOSE FAC AND FINDINGS _ _ - -"' " • ^--
'' " ' ` •'-� .� �..- ' _'- ,» _.... ., .-,•._ .----. f " - -i-- •••_ I ..•
DOES NOT CONSTITUTE A WARRANTY OR GUARANTEE, EITHER IMPLIED _
OR EXPRESSED. 9 l -- __ _ - ti- ' r-. �� r........---.^...... _ w
/ ! ._ ...- __ ._ __ - -_.. -.. --. I T } 4 7 . _.w.rt. .+� s : •,-•... p,-� Z _ice_ _ .-:.fir �. �. I' /"q
` / / r 3A' S'a:F EASIVEN1 - u -- - '- __ - _.. - .._ - ..- - .._ --- -- _. _.. - - --..__%'3_ _ - - __--_...._ i ..�.. r.._-.._.__ - - y
(52201'47)--,�na rx;tt : _fir 1,-:i� G
• •- - - -- _ •!
.� i / t•- Ah
`moi" % 4;`.‘,^11:.^:1„:',6,1 ,1 /t
-"-'S'Cni -'_ t'- - - C r-�'' 1:4 '•+3
.. - _. _.� _ _._ Y _�3 `�. G
uFFc r3 Sr .. r.t'�bN.� .t' 4 5 _.._ .... ----4S
- - -
/ \ ./ -- ,_ _
'\
,�� 4:.",'E. C''';" Es tVc1iC -` wj 4,. / / / / S q�
•� / /� .
t``;i '
2 VS MtE_1 E E i' / /
r L/�
/ i91= 7J r
! LJ A�,, N
�s YMaIT 1 =ACt� I
_-_« 412
I
'
1 r / / / f �� / / r
i
- ® .:Pttirt .
fisi -4.'a 8
o
r.:II * 9 t7
-
r / ! ..
S/r �'1 X' ` / • / r / /:732' / / . /. r ALP
E.--Tag,
Q\
u'.. t
t
_ - { _moo
r
1213 .1 i
/
GCr int" / N;/ / r
\� /
yY/ / ` r
\ r
LI, / / , ... r / / y f
m
/ j // r LJ / / /
' '
rLE _
14 THOMPSON TI
' &STONE / a � f
f
1 r ONE STORY "BUILDING B' r _ M_^+
r y
�" r \ CONCRETE 1TLT-UP BUILDING h / t<
/ AREAS 81.2(30 SQ. FT (FOOTPRINT) TRACT 1 L
/ r• Lis HEICHT*. 32' (79 PM 39) 8
UILDING A' f i
/ ;; / ONE STORY •• CRETE TILT-UP BUILDING s
u.p?• \ / AREAS 81.2 SQ. FT t (FOOTPRINT) .% I
iy
AN 56.5' ' "' Fi"eRes,t74i 1� i
y / GHT oro' EJ Stu , 1
N-
/
/
I
i %
/
\ N r' L/5 /
N.4
��r A ���.LS"AT79ei �� /
f 4710', / /
O?@;
t Sc cc_ "h
/ 0'9 Fl, '19) { i t4
/ -ter..--�
/ f - `
/Siva/v.-4 LNE
R 2 6 t
11
NP
i.
/ / / / 'B".
1 -
. " ..-
_. ... ry :TRACT
_ tis I ;(79 PM 39)\
'.1,
RAYMOND HANDLING
CORP.
FREMONT OFFICE:
OYCE ROAD
RI MON CA 9�5 63
e3, .� -- --_ - _-- - - _ _ � ' .
- c
-- - _ - _.,J
_ _ _- - _ __ __ _ _ _ - _ - __ ._ __ __ .-- -- _ �� -- - - - - -, r - - - -� I
PA
rCONCEPTS
i ,REVIEWED FOR
t_51.5,:_,
;; '
cooE OI�flPLIAI�!
-- .... ,. _ ..: , _ _ ,.. -.._. ,. _...,. w.._._.-_, .. , , - ._
SHEET
_. -- --- 1...: Y.. _ ._1
,.._.�.,- ..�....�...._ _. .... ....,......_....._..._... ...., .... �. «..,. "�."�.... ,» ."...-...��.»_Ira Oft* a......._...+....+"..._ ,...Imo _..�.
Ce
0
_,r............__."_..........,. _.3,.. ".:_ _
N 45'OI9.27' W 821.51' -"_.
_.., •. ''- _..:. -.. 2S' Ra>i~4osrT £a.SE!.C:vr
(79 Rx 39) I
03:8247)
(7(ot
Ca24_:i°�i
(57'014) '
W A h/
NOVl7 b.D
14UQ
•
drailg is
p�paed.dhi9a
-.�irantaam�emiie:0n
a e«roeptaddevgngoatm
ehe.detfedualpmpalyeiFEry7owd Handing
Wended liar other
Concepb Cotpar�'oMt II is 9uoi18. 9
dganimSans eb /and
co
's
OF 1 SHEETS)
ff Tukwila
t IJIVIL IO
PROJECT #: 9750
EUILOA
308 N0. 06-1002
PROJ. DESC: RACK
UV.0 awrSGf s et usrts 1r.. rvnr«rar twee. n1�...Ir..ys iota yra s� ndt e>. r.fpaa'%.+a f. , or aatda ror, aMe et 4 a+snma w ar cyw ar eIw ++�a s. w,Mw» a 100 M eMgas m the droe/rgp mast r e in .trrtirq end r-wt lie cpprored cry aw pnywr.r el Netu mepa, wrreys ani yloaa.
'�
PALLET POS. ##
SQ.FT. NA
RECEIVED
CITY OF TUKWILA
n
OCT 2 4 2017
PERMIT CENTER
DRAWN BY: O^H
DATE: 04/26/17
scALE: NTS
SHEET OF: 2/5
REVISION: 0
SHEET NO.
FZI-12.0
'IW„ rarv4�t
1'
1'
10'-102"
I
1'
MOKE
1. -SMOKE VENT
X
SMOKE VENT
EXIT DOOR
85'-7"
1�I
--u
REVIEWED FOR
CODE COMPLIANCE
APPROVED
Nay 01 MT
City Of Tutt
BUILDING GMS
RECEIVED
CITY OF TUKWILA
OCT 242017
PERMIT CENTER
t3r1.o.tL(L,
"IT'S NOT JUST BUSINESS, IT'S PERSONAL"
FOR ASSISTANCE CALL: 800.675.2500
rte
ID
0
RAYMOND HANDLING
CONCEPTS CORP.
FREMONT OFFICE:
41400 ICOYCE ROAD
FREMONT, CA 94583
,he intoner/inn on Mie droning ieprepared %OhM s
inland olconi nunicafng a conceptaid design Malin
Me inkteaid properly of Raymond Ha g
Concepts Coiporak n. pie not Wended for ober
aga�ons
draias a !means of quoting, daeig *g/and
or ig aimaafres.
PROJECT #: 9750
PROJ. DESC: RACK
PALLET POS. ##
SQ.FT. NA
DRAWN BY: O.H
DATE 04/26/17
SCALE:
3/32" =1'- 0"
SHEET OF: 3/5
REVISION: 0
SHEET NO.
RH3.0
192"
96"
NO LOAD ALLOWED
C-3 STRUCTURAL
126"
f
NO LOAD ALLOWED
1
LOAD NOT TO EXCEED 12'
48"
96"
144"
Front View
Back to Back Row
192"
12"
n
3
Sn
3
a
a
a
3 `\
❑
❑
'a
a
3
❑
3
0
a,
0
v
�.S
3
a
a
0
a
0.
0
3
a
a
a
a
�
a
ni
Side View
Back to Back Row
REVIEWED FOR
CODE COMPLIANCE
APPROVED
NUS 07 2017
City of Tuicwiia
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
OCT 242017
PERMIT CENTER
14y
"IT'S NOT JUST BUSINESS, IT'S PERSONAL"
FOR ASSISTANCE CALL: 800.675.2500
00
CO
00
V
J
0
STRA\DER
RAYMOND HANDLING
CONCEPTS CORP.
FREMONT OFFICE:
41400 BOYCE ROAD
FREMONT, CA 94583
The idomralon on lis draeig isprepseedvah
intent otwmnaeiaingaconcept addew' that is
Ile ter a Raymond Ha
Caneeple CIPoralon. tis not !Mended far elm
arga irafons as a weans dQni e.desioig,aid
erengineering allama6sea.
PROJECT #: 9750
PROJ. DESC: RACK
PALLET POS. ##
SQFT. NA
DRAWN BY: O.H
DATE 04/26/17
SCALE 3/4" = 1' — 0"
SHEET OF: 4/5
REVISION: 0
SHEET NO.
RH3.1
‘,F
HANDLING CONCEPTS CORPORATION
"IT'S NOT JUST BUSINESS, IT'S PERSONAL"
FOR ASSISTANCE CALL: 800.675.2500
EXIT SIGN
- c
EXIT SIGN6.-i)
III
I1
'"li
�
A
/\
,
a a
3—
r
t
—
'
e
r
REV. DATE:I
—
—
'==s
s
!—mss
r_e
--
Z
0
( )
w
fY
DESCRIPTION:
INITIAL RELEASE
TOTAL EGRESS DISTANCE = 81'
TOTAL EGRESS DISTANCE = 94'
a- - - - -T____- It.------
Q--
C
TOTAL EGRESS DISTANCE = 111'
TOTAL EGRESS DISTANCE = 128'
!�
TOTAL EGRESS DISTANCE = 144'
TOTAL EGRESS DISTANCE = 157'
=-
a
MOKE
4 i—
SMO
E
—!
T
—
a—
!�
a !__
B
'—'
—
t !—I
t
r
!
f=
i -t
!
B
l
mtv
1 r. a+
7....).
rte.
575 STA\ DEQ 3LVD, TU<WILA, WA, 98188 LIFE SAFETY
j
8 —
188,_81
L EGRESS DISTANCE = 103'
L EGRESS DISTANCE = 101'
18'
L EGRESS DISTANCE = 124'
L EGRESS DISTANCE = 108'
L EGRESS DISTANCE = 95'
.i
a a
--
4
! ---!
t
!
,irvmr,- :�.yggy** HI.f. yg, l.,s.•n w�.. y;.H'..
EMERGENCY ILLUMINATION FOR BUILDINGS AND
1
,—
!—,
—,
,_—
—.
--
—,
_,
DURATION OF ILLUMINATION (1008.3.2--1008.3.5)`
In the event of power supply failure in Rooms and spaces,
emergency electrical system shall automatically illuminateilluminated
all of the following areas: 1. Electrical equipment rooms, 2. Fireillumination
Fire
20151BC SECTION 1008 MEANS OF EGRESS
ILLUMINATION REQUIRED �•°I
entinga roomorspaceshallbean
atall times thtthe roomor spaceisoccupied;
The means of egress ;los
level shall benot less than 1! footcandle
t—__
command centers, 3. pump rooms, 4. Generator rooms,
Public restrooms with an area greater than 300 square feet
emergency power system shall provide power foranormallybeprovidedby
of not Tess than 90 minutes and shall consist bfIntheeventofpowersupplyfailureinroomsandspacesthatstorage batteries, unit equipment or an on-site generator.requiretwoormoremeansfegress,anemergencyelectrical—_a
walking surface.
at the5.
Thepowersupplyfor eans of egressilluminationshallThe
thepremises'electricalsupply.duration
=
a
!—
Illumination level under emergency power, the lightingsystemshallautomatically illuminateallofthefolfacilities shall be arran ed to rovide initial illumination that is lowingareas:9 p 1.Aisles,2. Corridors,3.Exitaccess stairwaysandramps.not less than an average of 1 footcandle and a minimum atIn the event of power supply failure in buildings that requireany point of 0.1 footcandle measured along the path of egresstwoormoremeansof egres, an emergency electrical system
at floor level. .. p shall automatically Illuminate
`�"
—
<
0
__1
0
,—r
o
I•—
,—r
!—,
,
o
I—
--
0
I—
o
all of the following areas: 1.
Illumination levels shall be permitted to decline to 0;6 , m, Interior exit access stairways and ram s. 2. Interior at d
footcandle average and a minimum at an y point of 0.(36 exterior exit stairways &ramps, 3. Exit passageways, 4.
footcandle at the end of the emergency lighting time duration.'
Vestibules at level of discharge, 5. Exterior landings and areas
Amaximum-to-minimum illumination uniformity ratio of 40 to 1 used for exit discharge.
shall not be exceeded. g
_
} _"""" �;,'" „�•"` �+a .✓`��"` ice...,. �, ,r,?'.,..w...;s"°*.„»4 }i
•
meg.,..,.
!
RAYMOND HANDLING
CONCEPTS CORP.
FREMONT OFFICE:
41400 BOYCE ROAD
FREMONT, CA 94583
4
!
MOKE VENT MOKE VENT
B
a
RECEIVED
REVIEWED FOR
,>b o,�/ is ,me
i,�,ea a "rcepenaomzs
'�'"'°ro°�`"a""" '°
concapmCorpaaWn.nienairrnmaaraAsrr
aa designing /and
or engineering alleanatves.
CITY OF TUKWILA
C®®E a ADLIAI CE
APPROVED OCT 2 4 2017
�� 012017 PERMIT CENTER
PROJ��
PROJEDESC: RACK
POS.
EGRESSPATH,
l•PALLET
City ®f TUkwlla
SQ.F1. NA
0 FIRE EXTINGUISHER
— EXIT SIGN 85'-7° EXIT SIGN
BUILDING DIVISION
DRAWN BY: O.H
DATE: 04/26/17
® EIRE HOSE
��"
Yb �
SCALE: 3/32" =1' - 0"
SHEET OF: 5/5
NO SMO'<ING SIGN
„ , ILLUMINATED EXIT SIGN
®b
„...,____,
ti
�,'
11
REVISION: 0
SHEET NO.
RH4.0
0 1
188'-8
M
KE
NT
1
MOKE VENT
II
III
III
�I
II
10, -1
1„
2
I
LONGEST EGRESS PATH DOES NOT EXCEED 2
MO
0
77
XIT 000
85' - 7"
•
6"
C-3 STRUCTURAL
192'
Bac
Row
48
96"
4'
root View
� ,o Baca
Bac
Row
*ALL MATERIAL IS STRUCTURAL STEEL
12"
--I-1362=14w
Side View
� ,o Baca
COMMODITIES: CLASS I (PALLETIZED TILE AND STO
MAXIMUM STORAGE HEIGHT NOT TO EXCEED 18'-6"
P
PRO
SCALE: 1 /4" = 1'-0"
REVIEWED FOR
CODE COMPLIANCE
APPROVED
NOV 07 2011
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
MAY 252017
PERMIT CENTER
l
Strticti_!rEll
G. /
1.2
3ESIG\ BY:
Raymond Handling Concepts Corporation
"IT'S NOT JUST BUSINESS, IT'S
PERSONAL"
FOR ASSISTANCE CALL: 800.675.2500
3
= SIG\ PREDAE3 EOR:
Thompson Tile and
Stone
575 Strander Blvd.
Tukwila, WA 98188
STR.,CT„RAL
Structural Concepts
1615 Yeager Ave.
Laverne, CA 91750
STR„CTURAL E\G
•
1.„1
\E
1,1RY 0 2 2017
PRC�d6CT #: 9750
STAv
DESIGNER: David Norris
REV.#
DESCRIPTION
DATE
SCALE: 3/32" = 1'-0"
ORAG
P
A
TO OR C..STOV-RS:
The information on this drawing is
prepared with the intent of communicating
a concept and design that is the
intellectual property of Raymond Handling
Concepts Corporation. It is not intended
for other organizations as a means of
quoting, designing / and or enineer'ng
alternatives.
PM: David Norris
DATE: 1/13/2016
SCALE: As Noted
SHEET NO.
SHEET NO.
1 5/
C4" X 4.5#
COLUMN
NOTES:
USE @ ALL
COLUMN/BASE
LOCATIONS TYP.
3/8"
TYP
2"
"1/8"
2"
9/16110 HOLE TYP.
1/2"
1 1/2" _
2"
12"MIN.
1/8" V1 1/4" <TYP.
2" x 2" x 1/8" PLATE
1 1/2" x 1 1/2" x 1/8" ANGLE
DESCRIPTION
BASE PLATE: 8" x 5"
DESCRIPTION
COLUMN: 4" STRUCTURAL
DESCRIPTION
BRACING: HORIZ. & DIAG.
MATERIAL
3/8" THICK PLATE
MATERIAL
C4" X 4.5#
MATERIAL
1/8" THK
STEEL YIELD
ASTM A36, Fy = 36, 000 PSI
(2) 2'O GR
BOLT
1 9/16"
0
O
STEEL YIELD
ASTM A572, Fy=50,000 PSI
STEEL YIELD
ASTM A36, Fy=36,000 PSI
NOTES:
USE @ ALL STRUCT.
BRACE LOCATIONS TYP.
DESCRIPTION
STRUCT. ROW SPACER
MATERIAL
1/8" THICK
STEEL YIELD
ASTM A36, Fy = 36,000 PSI
NOTES:
ATTACH WITH (2) 1/2"0 GR. 5
BOLT EACH END
2"
2"
2"
3"
8"
1 5/8"
/
/
/
/
/
C4" 4.5#
BASE PLATE
0.
NOTES:
CONFIRM O.A.L. OF ANCHORS WITH
ENSURE REQUIRED EMBEDMENT IS
1/2"
INSTALLER TO
OBTAINED.
3 1/4"
MIN. EMBED.
DESCRIPTION 2 -BOLT CONNECTOR
MATERIAL
7 GAGE
STEEL YIELD ASTM A572, Fy=50,000 PSI
NOTES:
USE @ ALL BEAM TO CONNECTOR
LOCATIONS TYP.
DESCRIPTION 4" BEAM STRUCTURAL
MATERIAL C4" X 4.5#
STEEL YIELD ASTM A572, Fy=50,000 PSI
NOTES:
USE @ ALL BEAM LOCATIONS TYP.
DESCRIPTION HILTI KWIK BOLT TZ
SIZE 1/2"0 x 3-1/4" MIN. E
ESR # 1917
ANCHOR
MBED.
TYPE 1 SELECTIVE RACK
96"
48"
FRONT VIEW
44"
44"
44"
44"
36"
12" MIN.
n
n
SIDE VIEW
GENERAL PROJECT NOTES
1. DESIGNED PER REQUIREMENTS OF THE 2015 IBC, ASCE 7-10 &
2012 RMI RACK DESIGN MANUAL
2. SEISMIC CRITERIA Ss = 1.447, S1 = 0.539, Fa=1.00, Fv = 1.50
Ip = 1.0 (NO PUBLIC ACCESS), Sds = 0.964, Sd1 = 0.539, OCC. CATAG. II,
SITE CLASS D, SEISMIC DESIGN CLASS D
3. STORAGE CAPACITY:
2200# @ LEVEL 1-3, 1000# @ TOP LEVEL
4. ANCHORS HILTI KWIK BOLT TZ ESR# 1917 OR POWER SD2 ESR#2502,
OR ICC & ENGINEER APPROVED EQUAL.
1/2"O x 3-1/4" MIN. EMBED.
(2) ANCHOR PER BASEPLATE
5. PERIODIC SPECIAL INSPECTION IS REQUIRED DURING ANCHOR INSTALLATION.
6. CONCRETE THICKNESS & COMPRESSIVE STRENGTH, 6" x 2500 PSI.
7. SOIL BEARING PRESSURE 1000 PSF @ GRADE OR BETTER
8. ALL RACK INSTALLATIONS AND RACKS MANUFACTURED IN CONFORMITY
WITH THIS STANDARD SHALL DISPLAY IN ONE OR MORE CONSPICUOUS
LOCATIONS A PERMANENT PLAQUE EACH NOT LESS THAN 50 SQUARE
INCHES IN AREA AND SHOWING THE MAXIMUM PERMISSIBLE UNIT LOAD IN CLEAR, LEGIBLE PRINT.
9. ALL BOLTS GR. 5 OR BETTER. INSTALL TO SNUG TIGHT FIT WITH ALL PLYS IN FLAT CONTACT
10. ALL WELDING PERFORMED IN THE SHOP OF AN APPROVED FABRICATOR BY AWS
CERTIFIED WELDERS USING E70XX ELECTRODE OR BETTER. FIELD WELDS, IF
ANY, SHALL BE PROVIDED UNDER THE SUPERVISION OF A LICENSED DEPUTY INSPECTOR.
11. THE CLEAR SPACE BELOW SPRINKLERS SHALL BE A MIN. OF 18" BETWEEN
TOP OF THE STORAGE AND THE CEILING SPRINKLER DEFLECTOR.
F
REVIEWED FOR
ODE COMPLIANCE
APPROVED
NOV 0 7 2017
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
MAY 25 2017
PERMIT CENTER
z
0
co
cc
z
0
06
L1J
—J
TUKWILA, WA. 98188
�'7yyChrty':F�.f,
EXPIRE
CLIENT RAYMOND HANDUNG
DATE 04/27/2017
DRWN BY V.N.
STRUCTURAL
w
W
2
JOB NO.
Q-042717-5
SHEET NO.
`SCE 1OF1