HomeMy WebLinkAboutPermit M17-0189 - CATALYST WORKPLACE - GRDS AND THERMOSTATSCATALYST WORKPLACE
10848 E MARGINAL WAY S
M17-0189
Parcel No:
Address:
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670
Inspection Request Line: 206-438-9350
Web site: http://www.TukwilaWA.gov
MECHANICAL PERMIT
0323049164
10848 E MARGINAL WAY S
Project Name: CATALYST WORKPLACE
Permit Number: M17-0189
Issue Date: 12/11/2017
Permit Expires On: 6/9/2018
Owner:
Name:
Address:
E MARGINAL WAY PROPS LLC
3006 NORTHUP WAY STE 101,
BELLEVUE, WA, 98004
Contact Person:
Name: TAYLOR LOWERY
Address:
Contractor:
Name:
Address:
License No:
Lender:
Name:
Address:
1221 SECOND AVE N , KENT, WA,
98032
HERMANSON COMPANY LLP
1221 2ND AVE N , KENT, WA, 98032-
2945
HERMACL005B1
Phone: (206) 817-9099
Phone: (206) 575-9700
Expiration Date: 8/25/2018
DESCRIPTION OF WORK:
23 GRD'S, 5 THERMOSTATS RELOCATION, REUSING MOST EXISTING GRD'S
Valuation of Work: $30,000.00
Type of Work: REPLACEMENT
Fuel type: ELECT
Fees Collected: $615.18
Electrical Service Provided by: SEATTLE CITY LIGHT
Water District: TUKWILA
Sewer District: VALLEY VIEW
Current Codes adopted by the City of Tukwila:
International Building Code Edition:
International Residential Code Edition:
International Mechanical Code Edition:
Uniform .Plumbing Code Edition:
International Fuel Gas Code:
2015
2015
2015
2015
2015
National Electrical Code:
WA Cities Electrical Code:
WAC 296-46B:
WA State Energy Code:
2017
2017
2017
2015
Permit Center Authorized Signature:
,/
I hearby certify that I have read and examined this permit and know the same to be true and correct. All
provisions of law and ordinances governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other
state or local laws regulating construction or the performance of work. I am authorized to sign and obtain this
development permit and agree to the conditions attached to this permit.
Signature:
Print Nam l7
oy 1
Date:I L/ 1 I f 11
This permit shall become null and void if the work is not commenced within 180 days for the date of issuance, or if
the work is suspended or abandoned for a period of 180 days from the last inspection.
PERMIT CONDITIONS:
1: Work shall be installed in accordance with the approved construction documents, and any changes made
during construction that are not in accordance with the approved construction documents shall be
resubmitted for approval.
2: All permits, inspection record card and approved construction documents shall be kept at the site of work
and shall be open to inspection by the Building Inspector until final inspection approval is granted.
3: All construction shall be done in conformance with the Washington State Building Code and the
Washington State Energy Code.
4: Remove all demolition rubble and loose miscellaneous material from lot or parcel of ground, properly cap
the sanitary sewer connections, and properly fill or otherwise protect all basements, cellars, septic tanks,
wells, and other excavations. Final inspection approval will be determined by the building inspector based
on satisfactory completion of this requirement.
5: All plumbing and gas piping work shall be inspected and approved under a separate permit issued by the
City of Tukwila Building Department (206-431-3670).
6: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila
Permit Center.
7: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an
approval of, any violation of any of the provisions of the building code or of any other ordinances of the City
of Tukwila. Permits presuming to give authority to violate or cancel the provisions of the code or other
ordinances of the City of Tukwila shall not be valid. The issuance of a permit based on construction
documents and other data shall not prevent the Building Official from requiring the correction of errors in
the construction documents and other data.
8: ***MECHANICAL PERMIT CONDITIONS***
9: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila
Permit Center (206/431-3670).
10: Manufacturers installation instructions shall be available on the job site at the time of inspection.
PERMIT INSPECTIONS REQUIRED
Permit Inspection Line: (206) 438-9350
1800 MECHANICAL FINAL
0701 ROUGH -IN MECHANICAL
11)
CITY OF TUKWILA
Community Development Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http://www.TukwilaWA.gov
Mechanical Permit No. j"( ( ` d ( y
I
Project No.
Date Application Accepted: 19- ` H - 7
Date Application Expires:
(For office use only)
MECHANICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
**please print**
SITE LOCATION
Site Address: U p 4 D f. Yutot,r
King Co Assessor's Tax No.: 0 3 2_3 ( 46) 1124
rod WouJ S Suite Number: Floor:
((\�
Tenant Name: Wl 1 All St W(} V 1G4 -e,; New Tenant: ❑ Yes Y.No
PROPERTY OWNER
Name: —
I A LI/VO Y Lowe v`�-
Name: cotkait1Si' W 1G1ct,
City: V-Ln-fV" State: �,� I # Zip: (lc0r03Z
V
Address:
In 4 . mourckinc4.4Wow
S.
City: -Ici , V , A , Im State: w Zip:
GI It
CONTACT PERSON — person receiving all project
communication
Name: —
I A LI/VO Y Lowe v`�-
Address: 1,Lt 2A l a fIQ
City: V-Ln-fV" State: �,� I # Zip: (lc0r03Z
V
Phone: 4 511 �Kax.
25
Email:
iv i mr. I UWCrw &, h?rmrxnSON
MECHANICAL CONTRACTOR INFORMATION
Company Name:
`krrna, 1S0n, C b.
Address:'Z.LI i nd 14V I M .
City: p State: IAA Zip:01 60 iz
Phone: Lou a,.1 ci oatgFax.
Contr Reg No.: ft x, 00 5xo ate: to it.15/ i g
Tukwila Business License No.: E kA S _ 0 olai 44 ti 4
o rvt
Valuation of project (contractor's bid price): $ i )0 1 000 , d 0
Describe the scope of work in detail:
Use:
Fuel Type:
Residential:
Commercial:
Electric
23 C IZVS 5 t SI-arl-S re) 0coLti a v
\(-cu nT- m 06 t f).iSt r- C, QTY S
New ❑ Replacement ❑
New ❑ Replacement
Gas ❑
Other:
H:\Applications\Forms-Applications On Line \2016 ApplicationsWechanical Permit Application Revised 1-4-16.docx
Revised: January 2016
bh
Page 1 of 2
Indicate type of mechanical work being installed and the quantity below:
Unit Type
Qty
Furnace <100k btu
Residential, Nighttime
Furnace >100k btu
2.3
Floor furnace
5
Suspended/wall/floor
mounted heater
57 dB(A)
Appliance vent
Commercial
Repair or addition to
heat/refrig/cooling
system
47 dB(A)
Air handling unit
65 dB(A)
<10,000 cfm
60 dB(A)
Unit Type
Qty
Air handling unit
Residential, Nighttime
>10,000 cfm
2.3
Evaporator cooler
5
Ventilation fan
connected to single duct
57 dB(A)
Ventilation system
Commercial
Hood and duct
47 dB(A)
Incinerator — domestic
65 dB(A)
Incinerator —
comm/industrial
60 dB(A)
Unit Type
Qty
Fire damper
Residential, Nighttime
Diffuser
2.3
Thermostat
5
Wood/gas stove
57 dB(A)
Emergency generator
Commercial
Other mechanical
equipment
47 dB(A)
60 dB(A)
65 dB(A)
Boiler/Compressor
Qty
0-3 hp/100,000 btu
3-15 hp/500,000 btu
15-30 hp/1,000,000 btu
30-50 hp/1,750,000 btu
50+ hp/1,750,000 btu
Noise:
Mechanical units need to be in compliance with the Tukwila Noise Code. Maximum permissible sound levels are based on from where the sound is
created and where the sound is heard. Additionally, if sound can be heard from within a house at night in a residential zone it may not be allowed.
For more details, see TMC 8.22
District of Sound
Producing Source
District of Receiving Property
Residential, Daytime*
Residential, Nighttime
Commercial
Industrial
Residential
55 dB(A)
45 dB(A)
57 dB(A)
60 dB(A)
Commercial
57 dB(A)
47 dB(A)
60 dB(A)
65 dB(A)
Industrial
60 dB(A)
50 dB(A)
65 dB(A)
70 dB(A)
*Daytime means 7AM-10PM, Monday through Friday and 8AM-1OPM, Saturday, Sunday and State -recognized holidays.
A few sounds are exempt from the noise code, including:
• Warning devices;
• Construction and property maintenance during the daytime hours (7am-lOpm);
• Testing of backup generators during the day.
PERMIT APPLICATION NOTES -
Value of construction — in all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the permit center to comply with current fee schedules.
Expiration of plan review — applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The building official may grant one extension of time for additional periods not to exceed 90 days each. The extension shall be requested in writing
and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDINGWNER 0 AUTHORIZED AGENT:
Signature: • (\./t0\
Print Nam;:f6 0 y/ i 6ti,?JV'
Mailing Address: 1 2.1 Znol kit) N •
H:Wpplications\Forms-Applications On Line \2016 Applications\Mechanical Permit Application Revised 1-4-16.docx
Revised: January 2016
bh
Date: Z/
Day Telephone: 2. % - Qc‘9A
�fXl� W 1cr qlS U�
City State Zip
Page 2 of 2
Cash Register Receipt
City of Tukwila
DESCRIPTIONS
PermitTRAK
1 ACCOUNT
QUANTITY
PAID
$615.18
M17-0189 Address: 10848 E MARGINAL WAY S Apn: 0323049164 '
$615.18
Credit Card Fee
$17.92
Credit Card Fee
R000.369.908.00.00
0.00
$17.92
MECHANICAL
$574.29
PERMIT ISSUANCE BASE FEE
R000.322.100.00.00
0.00
$33.15
PERMIT FEE
R000.322.100.00.00
0.00
$426.28
PLAN CHECK FEE
R000.322.102.00.00
0.00
$114.86
TECHNOLOGY FEE
$22.97
TECHNOLOGY FEE
TOTAL FEES PAID BY RECEIPT: R12937
R000.322.900.04.00 0.00
$22.97
$615.18
Date Paid: Monday, December 04, 2017
Paid By: SYDNEY LOWERY
Pay Method: CREDIT CARD 256983
Printed: Monday, December 04, 2017 10:40 AM 1 of 1
?SYSTEMS
INSPECTION NO.
INSPECTION RECORD
Retain a copy with permit
PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 438-9350
ProjeccFcAl.
We4RAtmedi
Pe ofRiT
Rat
Fn.
M�F
Address:
E.
i
Date Called:
‘oetiK
pecial Instructions
*e-Wated
.
6.201
a.
P.m.
Requester:
Phone No:
Approved per applicable codes. Corrections required prior to approval.
COMMENTS:
ecko,niCAL — DJ
A J`1 ed 1 CAL rimoL kr
Inspect (NW
Date:4/ /(o" 2.0
?l
REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Hermanson
Project:
Hermanson Company LLP
1221 2nd Avenue North
Kent, WA 98032
tel 206-575-9700
fax 206-575-9800
Catalyst Workplace Activation
10848 E. Marginal Way S.
Tukwila, WA 98168
Date: November - 30, 2017
Load Calculations
REVIEWED FOR
CODE COMPLIANCE
APPROVED
DEC 0 8 2017
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
DEC 04 2017
PERMIT CENTER
Mechanical Construction,
Engineering and Service
www.hermanson.com
3) Hermanson
SPACE
INPUT DATA
System Loads
Carrier HAP Version 5.1
TUK_Catalyst Workplace Activation_v5_1
HERMANSON COMPANY LLP
Roof Constructions
11/29/2017
01:53PM
Existing Roof
Roof Details
Outside Surface Color Medium
Absorptivity 0.675
Overall U -Value 0.030 BTU/(hr•ft2•°F)
Roof Lavers Details (Inside to Outside
Layers
Thickness
in
Density
Ib/ft'
Specific Ht.
BTU / (Ib•°F)
R -Value
(heft'•°F)/BTU
Weight
Ib/ft'
Inside surface resistance
0.000
0.0
0.00
0.68500
0.0
R-30 batt insulation
9.000
0.5
0.20
28.84615
0.4
22 gage steel deck
0.034
489.0
0.12
0.00011
1.4
4 -in LW concrete
4.000
40.0
0.20
3.33333
13.3
Built-up roofing
0.375
70.0
0.35
0.33245
2.2
Outside surface resistance
0.000
0.0
0.00
0.17000
0.0
Totals
13.409
-
33.36703
17.3
Hourly Analysis Program v5.10 Page 1 of 1
TUK_Catalyst Workplace Activation_v5_1
HERMANSON COMPANY LLP
Window Constructions
11/29/2017
01:54PM
Existing Glazing 10'
Window Details:
Detailed Input Yes
Height 10.00 ft
Width 1.00 ft
Frame Type Aluminum with thermal breaks
Internal Shade Type None
Overall U -Value 0.612 BTU/(hrft2•°F)
Overall Shade Coefficient 0.545
Glass Details:
Gap Type 1/2" Air Space
Glazing
Glass Type
Transmissivity
Reflectivity
Absorptivity
Outer Glazing
1/4" gray tint
0.479
0.062
0.459
Glazing #2
1/4" clear
0.792
0.079
0.129
Glazing #3
not used
1.000
0.000
0.000
Existing Glazing 3'
Window Details:
Detailed Input Yes
Height 10.00 ft
Width 1.00 ft
Frame Type Aluminum with thermal breaks
Internal Shade Type None
Overall U -Value 0.612 BTU/(hrft2•°F)
Overall Shade Coefficient 0.545
Glass Details:
Gap Type 1/2" Air Space
Glazing
Glass Type
Transmissivity
Reflectivity
Absorptivity
Outer Glazing
1/4" gray tint
0.479
0.062
0.459
Glazing #2
1/4" clear
0.792
0.079
0.129
Glazing #3
not used
1.000
0.000
0.000
Hourly Analysis Program v5.10 Page 1 of 1
TUK_Catalyst Workplace Activation_v5_1
HERMANSON COMPANY LLP
Wall Constructions
11/29/2017
01:52PM
Existing Wall
Wall Details
Outside Surface Color Medium
Absorptivity 0.675
Overall U -Value 0.113 BTU/(hrft2•°F)
Wall Lavers Details (Inside to Outside
Layers
Thickness
in
Density
Ib/ft3
Specific Ht.
BTU / (Ib•°F)
R -Value
(hrft2•°F)/BTU
Weight
, Ib/ft2
Inside surface resistance
0.000
0.0
0.00
0.68500
0.0
Gypsum board
0.625
50.0
0.26
0.56000
2.6
R-11 batt (24" O.C.)
4.000
0.5
0.20
6.60000
0.2
8 -in HW concrete
8.000
140.0
0.20
0.66667
93.3
Outside surface resistance
0.000
0.0
0.00
0.33300
0.0
Totals
12.625
-
8.84467
96.1
Hourly Analysis Program v5.10 Page 1 of 1
TUK_Catalyst Workplace Activation_v5_1
HERMANSON COMPANY LLP
Space Input Data
11/30/2017
01:19PM
01-01 E Conference
1. General Details:
Floor Area 245.0
Avg. Ceiling Height 10.0
Building Weight 70.0
1.1. OA Ventilation Requirements:
Space Usage User -Defined
OA Requirement 1 5.0 CFM/person
OA Requirement 2 0.06 CFM/ft2
Space Usage Defaults .. ASHRAE Standard 62.1-2010
ft2
ft
Ib/ft2
2. Internals:
2.1. Overhead Lighting:
Fixture Type Recessed (Unvented)
Wattage 0.89 W/ft2
Ballast Multiplier 1.08
Schedule 90.1 Office Lights/Elec
2.2. Task Lighting:
Wattage 0.00 W/ft2
Schedule None
2.3. Electrical Equipment:
Wattage 500.0 Watts
Schedule 90.1 Office Lights/Elec
3. Walls, Windows, Doors:
2.4. People:
Occupancy 9.0 People
Activity Level Office Work
Sensible 245.0 BTU/hr/person
Latent 205.0 BTU/hr/person
Schedule 90.1 Office Occupants
2.5. Miscellaneous Loads:
Sensible 0 BTU/hr
Schedule None
Latent 0 BTU/hr
Schedule None
Exp.
Wall Gross Area (ft2)
Window 1 Qty.
Window 2 Qty.
Door 1 Qty.
SE
333.0
0
0
0
3.1. Construction Types for Exposure SE
Wall Type Existing Wall
4. Roofs, Skylights:
Exp.
Roof Gross Area (ft2)
Roof Slope (deg.)
Skylight Qty.
H
245.0
0
0
4.1. Construction Types for Exposure H
Roof Type Existing Roof
5. Infiltration:
Design Cooling 0.00 CFM
Design Heating 0.50 ACH
Energy Analysis 0.00 CFM
Infiltration occurs at all hours.
6. Floors:
Type Slab Floor On Grade
Floor Area 245.0 ft2
Total Floor U -Value 0.420 BTU/(hrft2•°F)
Exposed Perimeter 20.8 ft
Edge Insulation R -Value 10.00 (hrft2•°F)/BTU
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 193.0 ft2
U -Value 0.333 BTU/(hrft2•°F)
Uncondit. Space Max Temp 82.0 °F
Ambient at Space Max Temp 82.0 °F
Uncondit. Space Min Temp 55.0 °F
Ambient at Space Min Temp 24.0 °F
Hourly Analysis Program v5.10 Page 1 of 13
TUK_Catalyst Workplace Activation_v5_1
HERMANSON COMPANY LLP
Space Input Data
11/30/2017
01:19PM
01-02 SE Open Office
1. General Details:
Floor Area 675.0
Avg. Ceiling Height 10.0
Building Weight 70.0
1.1. OA Ventilation Requirements:
Space Usage User -Defined
OA Requirement 1 5.0 CFM/person
OA Requirement 2 0.06 CFM/ft2
Space Usage Defaults .. ASHRAE Standard 62.1-2010
ft2
ft
Ib/ft2
2. Internals:
2.1. Overhead Lighting:
Fixture Type Recessed (Unvented)
Wattage 0.89 W/ft2
Ballast Multiplier 1.08
Schedule 90.1 Office Lights/Elec
2.2. Task Lighting:
Wattage 0.00 W/ft2
Schedule None
2.3. Electrical Equipment:
Wattage 1540.0 Watts
Schedule 90.1 Office Lights/Elec
3. Walls, Windows, Doors:
2.4. People:
Occupancy 14.0 People
Activity Level Office Work
Sensible 245.0 BTU/hr/person
Latent 205.0 BTU/hr/person
Schedule 90.1 Office Occupants
2.5. Miscellaneous Loads:
Sensible 0 BTU/hr
Schedule None
Latent 0 BTU/hr
Schedule None
Exp.
Wall Gross Area (ft2)
Window 1 Qty.
Window 2 Qty.
Door 1 Qty.
SE
745.0
12
0
1
3.1. Construction Types for Exposure SE
Wall Type Existing Wall
1st Window Type Existing Glazing 3'
Door Type SEA -NR Swinging
4. Roofs, Skylights:
Exp.
Roof Gross Area (ft2)
Roof Slope (deg.)
Skylight Qty.
H
675.0
0
0
4.1. Construction Types for Exposure H
Roof Type Existing Roof
5. Infiltration:
Design Cooling 0.00 CFM
Design Heating 0.50 ACH
Energy Analysis 0.00 CFM
Infiltration occurs at all hours.
6. Floors:
Type Slab Floor On Grade
Floor Area 675.0 ft2
Total Floor U -Value 0.420 BTU/(hr•ft2-°F)
Exposed Perimeter 43.0 ft
Edge Insulation R -Value 10.00 (hr•ft2•°F)/BTU
7. Partitions:
(No partition data).
Hourly Analysis Program v5.10 Page 2 of 13
TUK_Catalyst Workplace Activation_v5_1
HERMANSON COMPANY LLP
Space Input Data
11/30/2017
01:19PM
01-03 SW Open Office
1. General Details:
Floor Area 715.0
Avg. Ceiling Height 10.0
Building Weight 70.0
1.1. OA Ventilation Requirements:
Space Usage User -Defined
OA Requirement 1 5.0 CFM/person
OA Requirement 2 0.06 CFM/ft2
Space Usage Defaults .. ASHRAE Standard 62.1-2010
ft2
ft
Ib/ft2
2. Internals:
2.1. Overhead Lighting:
Fixture Type Recessed (Unvented)
Wattage 0.89 W/ft2
Ballast Multiplier 1.08
Schedule 90.1 Office Lights/Elec
2.2. Task Lighting:
Wattage 0.00 W/ft2
Schedule None
2.3. Electrical Equipment:
Wattage 400.0 Watts
Schedule 90.1 Office Lights/Elec
3. Walls, Windows, Doors:
2.4. People:
Occupancy 16.0 People
Activity Level Office Work
Sensible 245.0 BTU/hr/person
Latent 205.0 BTU/hr/person
Schedule 90.1 Office Occupants
2.5. Miscellaneous Loads:
Sensible 0 BTU/hr
Schedule None
Latent 0 BTU/hr
Schedule None
Exp.
Wall Gross Area (ft2)
Window 1 Qty.
Window 2 Qty.
Door 1 Qty.
SE
123.0
0
0
1
SW
1692.0
50
0
1
3.1. Construction Types for Exposure SE
Wall Type Existing Wall
Door Type SEA -NR Swinging
3.2. Construction Types for Exposure SW
Wall Type Existing Wall
1st Window Type Existing Glazing 10'
Door Type SEA -NR Swinging
4. Roofs, Skylights:
Exp.
Roof Gross Area (ft2)
Roof Slope (deg.)
Skylight Qty.
H
715.0
0
0
4.1. Construction Types for Exposure H
Roof Type Existing Roof
5. Infiltration:
Design Cooling 0.00 CFM
Design Heating 0.50 ACH
Energy Analysis 0.00 CFM
Infiltration occurs at all hours.
6. Floors:
Type Slab Floor On Grade
Floor Area 715.0 ft2
Total Floor U -Value 0.420 BTU/(hr•ft2•°F)
Exposed Perimeter 129.0 ft
Edge Insulation R -Value 10.00 (hr•ft2•°F)/BTU
7. Partitions:
(No partition data).
Hourly Analysis Program v5.10 Page 3 of 13
TUK_Catalyst Workplace Activation_v5_1
HERMANSON COMPANY LLP
Space Input Data
11/30/2017
01:19PM
01-04 Conference
1. General Details:
Floor Area 395.0 ft2
Avg. Ceiling Height 10.0 ft
Building Weight 70.0 Ib/ft2
1.1. OA Ventilation Requirements:
Space Usage User -Defined
OA Requirement 1 5.0 CFM/person
OA Requirement 2 0.06 CFM/ft2
Space Usage Defaults .. ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting:
Fixture Type Recessed (Unvented)
Wattage 0.89 W/ft2
Ballast Multiplier 1.08
Schedule 90.1 Office Lights/Elec
2.2. Task Lighting:
Wattage 0.00 W/ft2
Schedule None
2.3. Electrical Equipment:
Wattage 650.0 Watts
Schedule 90.1 Office Lights/Elec
3. Walls, Windows, Doors:
(No Wall, Window, Door data).
4. Roofs, Skylights:
2.4. People:
Occupancy 14.0 People
Activity Level Office Work
Sensible 245.0 BTU/hr/person
Latent 205.0 BTU/hr/person
Schedule 90.1 Office Occupants -
2.5. Miscellaneous Loads:
Sensible 0 BTU/hr
Schedule None
Latent 0 BTU/hr
Schedule None
Exp.
Roof Gross Area (ft2)
Roof Slope (deg.)
Skylight Qty.
H
395.0
0
0
4.1. Construction Types for Exposure H
Roof Type Existing Roof
5. Infiltration:
Design Cooling 0.00 CFM
Design Heating 0.00 ACH
Energy Analysis 0.00 CFM
Infiltration occurs at all hours.
6. Floors:
Type Slab Floor On Grade
Floor Area 395.0 ft2
Total Floor U -Value 0420 BTU/(hrft2•°F)
Exposed Perimeter 0.0 ft
Edge Insulation R -Value 10.00 (hrft2•°F)/BTU
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 647.0 ft2
U -Value 0.330 BTU/(hrft2•°F)
Uncondit. Space Max Temp 82.0 °F
Ambient at Space Max Temp 82.0 °F
Uncondit. Space Min Temp 55.0 °F
Ambient at Space Min Temp 24.0 °F
Hourly Analysis Program v5.10 Page 4 of 13
TUK_Catalyst Workplace Activation_v5_1
HERMANSON COMPANY LLP
Space Input Data
11/30/2017
01:19PM
01-05 Open Office
1. General Details:
Floor Area 1835.0 ft2
Avg. Ceiling Height 10.0 ft
Building Weight 70.0 Ib/ft2
1.1. OA Ventilation Requirements:
Space Usage User -Defined
OA Requirement 1 5.0 CFM/person
OA Requirement 2 0.06 CFM/ft2
Space Usage Defaults _ ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting:
Fixture Type Recessed (Unvented).
Wattage 0.89 W/ft2
Ballast Multiplier 1.08
Schedule 90.1 Office Lights/Elec
2.2. Task Lighting:
Wattage 0.00 W/ft2
Schedule None
2.3. Electrical Equipment:
Wattage 2860.0 Watts
Schedule 90.1 Office Lights/Elec
3. Walls, Windows, Doors:
(No Wall, Window, Door data).
4. Roofs, Skylights:
2.4. People:
Occupancy 26.0 People
Activity Level Office Work
Sensible 245.0 BTU/hr/person
Latent 205.0 BTU/hr/person
Schedule 90.1 Office Occupants
2.5. Miscellaneous Loads:
Sensible 0 BTU/hr
Schedule None
Latent 0 BTU/hr
Schedule None
Exp.
Roof Gross Area (ft2)
Roof Slope (deg.)
Skylight Qty.
H
1835.0
0
0
4.1. Construction Types for Exposure H
Roof Type Existing Roof
5. Infiltration:
Design Cooling 0.00 CFM
Design Heating 0.00 ACH
Energy Analysis 0.00 CFM
Infiltration occurs at all hours.
6. Floors:
Type Slab Floor On Grade
Floor Area 1835.0 ft2
Total Floor U -Value 0.420 BTU/(hr•ft2•°F)
Exposed Perimeter 0.0 ft
Edge Insulation R -Value 10.00 (hr•ft2•°F)/BTU
7. Partitions:
7.1. 1st Partition Details:
Partition Type Wall Partition
Area 1223.0
ft2
U -Value 0.330 BTU/(hr•ft2•°F)
Uncondit. Space Max Temp 82.0 °F
Ambient at Space Max Temp 82.0 °F
Uncondit. Space Min Temp 55.0 °F
Ambient at Space Min Temp 24.0 °F
7.2. 2nd Partition Details:
(No partition data).
Hourly Analysis Program v5.10 Page 5 of 13
TUK_Catalyst Workplace Activation_v5_1
HERMANSON COMPANY LLP
Space Input Data
11/30/2017
01:19PM
01-06 Enclosed Office
1. General Details:
Floor Area 90.0 ft2
Avg. Ceiling Height 10.0 ft
Building Weight 70.0 Ib/ft2
1.1. OA Ventilation Requirements:
Space Usage User -Defined
OA Requirement 1 5.0 CFM/person
OA Requirement 2 0.06 CFM/ft2
Space Usage Defaults .. ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting:
Fixture Type Recessed (Unvented)
Wattage 0.89 W/ft2
Ballast Multiplier 1.08
Schedule 90.1 Office Lights/Elec
2.2. Task Lighting:
Wattage 0.00 W/ft2
Schedule None
2.3. Electrical Equipment:
Wattage 135.0 Watts
Schedule 90.1 Office Lights/Elec
3. Walls, Windows, Doors:
(No Wall, Window, Door data).
4. Roofs, Skylights:
2.4. People:
Occupancy 1.0 Person
Activity Level Office Work
Sensible 245.0 BTU/hr/person
Latent 205.0 BTU/hr/person
Schedule 90.1 Office Occupants
2.5. Miscellaneous Loads:
Sensible 0 BTU/hr
Schedule None
Latent 0 BTU/hr
Schedule None
Exp.
Roof Gross Area (ft2)
Roof Slope (deg.)
Skylight Qty.
H
90.0
0
0
4.1. Construction Types for Exposure H
Roof Type Existing Roof
5. Infiltration:
Design Cooling 0.00 CFM
Design Heating 0.00 ACH
Energy Analysis 0.00 CFM
Infiltration occurs at all hours.
6. Floors:
Type Slab Floor On Grade
Floor Area 90.0 ft2
Total Floor U -Value 0420 BTU/(hr•ft2•°F)
Exposed Perimeter 0.0 ft
Edge Insulation R -Value 8.00 (hr•ft2•°F)/BTU
7. Partitions:
7.1. 1st Partition Details:
Partition Type Wall Partition
Area 163.0 ft2
U -Value 0.330 BTU/(hr•ft2•°F)
Uncondit. Space Max Temp 82.0 °F
Ambient at Space Max Temp 82.0 °F
Uncondit. Space Min Temp 55.0 °F
Ambient at Space Min Temp 24.0 °F
7.2. 2nd Partition Details:
(No partition data).
Hourly Analysis Program v5.10 Page 6 of 13
TUK_Catalyst Workplace Activation_v5_1
HERMANSON COMPANY LLP
Space Input Data
11/30/2017
01:19PM
01-07 Meeting
1. General Details:
Floor Area 115.0 ft2
Avg. Ceiling Height 10.0 ft
Building Weight 70.0 Ib/ft2
1.1. OA Ventilation Requirements:
Space Usage User -Defined
OA Requirement 1 5.0 CFM/person
OA Requirement 2 0.06 CFM/ft2
Space Usage Defaults.. ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting:
Fixture Type Recessed (Unvented)
Wattage 0.89 W/ft2
Ballast Multiplier 1.08
Schedule 90.1 Office Lights/Elec
2.2. Task Lighting:
Wattage 0.00 W/ft2
Schedule None
2.3. Electrical Equipment:
Wattage 300.0 Watts
Schedule 90.1 Office Lights/Elec
3. Walls, Windows, Doors:
(No Wall, Window, Door data).
4. Roofs, Skylights:
2.4. People:
Occupancy 3.0 People
Activity Level Office Work
Sensible 245.0 BTU/hr/person
Latent 205.0 BTU/hr/person
Schedule 90.1 Office Occupants
2.5. Miscellaneous Loads:
Sensible 0 BTU/hr
Schedule None
Latent 0 BTU/hr
Schedule None
Exp.
Roof Gross Area (ft2)
Roof Slope (deg.)
Skylight Qty.
H
115.0
0
0
4.1. Construction Types for Exposure H
Roof Type Existing Roof
5. Infiltration:
Design Cooling 0.00 CFM
Design Heating 0.00 ACH
Energy Analysis 0.00 CFM
Infiltration occurs at all hours.
6. Floors:
Type Slab Floor On Grade
Floor Area 115.0 ft2
Total Floor U -Value 0.420 BTU/(hrft2•°F)
Exposed Perimeter 0.0 ft
Edge Insulation R -Value 8.00 (hrft2•°F)/BTU
7. Partitions:
(No partition data).
Hourly Analysis Program v5.10 Page 7 of 13
TUK_Catalyst Workplace Activation_v5_1
HERMANSON COMPANY LLP
Space Input Data
11/30/2017
01:19PM
01-08 Open Office
1. General Details:
Floor Area 3450.0 ft2
Avg. Ceiling Height 10.0 ft
Building Weight 70.0 Ib/ft2
1.1. OA Ventilation Requirements:
Space Usage User -Defined
OA Requirement 1 5.0 CFM/person
OA Requirement 2 0.06 CFM/ft2
Space Usage Defaults .. ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting:
Fixture Type Recessed (Unvented)
Wattage 0.89 W/ft2
Ballast Multiplier 1.08
Schedule 90.1 Office Lights/Elec
2.2. Task Lighting:
Wattage 0.00 W/ft2
Schedule None
2.3. Electrical Equipment:
Wattage 2420.0 Watts
Schedule 90.1 Office Lights/Elec
3. Walls, Windows, Doors:
2.4. People:
Occupancy 30.0 People
Activity Level Office Work
Sensible 245.0 BTU/hr/person
Latent 205.0 BTU/hr/person
Schedule 90.1 Office Occupants
2.5. Miscellaneous Loads:
Sensible 0 BTU/hr
Schedule None
Latent 0 BTU/hr
Schedule None
Exp.
Wall Gross Area (ft2)
Window 1 Qty.
Window 2 Qty.
Door 1 Qty.
SW
185.0
10
0
0
3.1. Construction Types for Exposure SW
Wall Type Existing Wall
1st Window Type Existing Glazing 10'
4. Roofs, Skylights:
Exp.
Roof Gross Area (ft2)
Roof Slope (deg.)
Skylight Qty.
H
3450.0
0
0
4.1. Construction Types for Exposure H
Roof Type Existing Roof
5. Infiltration:
Design Cooling 0.00 CFM
Design Heating 0.00 ACH
Energy Analysis 0.00 CFM
Infiltration occurs at all hours.
6. Floors:
Type Slab Floor On Grade
Floor Area 3450.0 ft2
Total Floor U -Value 0420 BTU/(hrft2•°F)
Exposed Perimeter 0.0 ft
Edge Insulation R -Value 8.00 (hrft2•°F)/BTU
7. Partitions:
(No partition data).
Hourly Analysis Program v5.10 Page 8 of 13
TUK_Catalyst Workplace Activation_v5_1
HERMANSON COMPANY LLP
Space Input Data
11/30/2017
01:19PM
01-09 Conference
1. General Details:
Floor Area 95.0 ft2
Avg. Ceiling Height 10.0 ft
Building Weight 70.0 Ib/ft2
1.1. OA Ventilation Requirements:
Space Usage User -Defined
OA Requirement 1 5.0 CFM/person
OA Requirement 2 0.06 CFM/ft2
Space Usage Defaults .. ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting:
Fixture Type Recessed (Unvented)
Wattage 0.89 W/ft2
Ballast Multiplier 1.08
Schedule 90.1 Office Lights/Elec
2.2. Task Lighting:
Wattage 0.00 W/ft2
Schedule None
2.3. Electrical Equipment:
Wattage 300.0 Watts
Schedule 90.1 Office Lights/Elec
3. Walls, Windows, Doors:
(No Wall, Window, Door data).
4. Roofs, Skylights:
2.4. People:
Occupancy 4.0 People
Activity Level Office Work
Sensible 245.0 BTU/hr/person
Latent 205.0 BTU/hr/person
Schedule 90.1 Office Occupants
2.5. Miscellaneous Loads:
Sensible 0 BTU/hr
Schedule None
Latent 0 BTU/hr
Schedule None
Exp.
Roof Gross Area (ft2)
Roof Slope (deg.)
Skylight Qty.
H
95.0
0
0
4.1. Construction Types for Exposure H
Roof Type Existing Roof
5. Infiltration:
Design Cooling 0.00 CFM
Design Heating 0.00 ACH
Energy Analysis 0.00 CFM
Infiltration occurs at all hours.
6. Floors:
Type Slab Floor On Grade
Floor Area 95.0 ft2
Total Floor U -Value 0.420 BTU/(hr•ft2•°F)
Exposed Perimeter 0.0 ft
Edge Insulation R -Value 8.00 (hr•ft2•°F)/BTU
7. Partitions:
(No partition data).
Hourly Analysis Program v5.10 Page 9 of 13
TUK_Catalyst Workplace Activation_v5_1
HERMANSON COMPANY LLP
Space Input Data
11/30/2017
01:19PM
01-10 Telephone Room
1. General Details:
Floor Area 35.0 ft2
Avg. Ceiling Height 10.0 ft
Building Weight 70.0 lb/ft2
1.1. OA Ventilation Requirements:
Space Usage User -Defined
OA Requirement 1 5.0 CFM/person
OA Requirement 2 0.06 CFM/ft2
Space Usage Defaults .. ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting:
Fixture Type Recessed (Unvented)
Wattage 0.89 W/ft2
Ballast Multiplier 1.08
Schedule 90.1 Office Lights/Elec
2.2. Task Lighting:
Wattage 0.00 W/ft2
Schedule None
2.3. Electrical Equipment:
Wattage 50.0 Watts
Schedule 90.1 Office Lights/Elec
3. Walls, Windows, Doors:
(No Wall, Window, Door data).
4. Roofs, Skylights:
2.4. People:
Occupancy 1.0 Person
Activity Level Office Work
Sensible 245.0 BTU/hr/person
Latent 205.0 BTU/hr/person
Schedule 90.1 Office Occupants
2.5. Miscellaneous Loads:
Sensible 0 BTU/hr
Schedule None
Latent 0 BTU/hr
Schedule None
Exp.
Roof Gross Area (ft2)
Roof Slope (deg.)
Skylight Qty.
H
35.0
0
0
4.1. Construction Types for Exposure H
Roof Type Existing Roof
5. Infiltration:
Design Cooling 0.00 CFM
Design Heating 0.00 ACH
Energy Analysis 0.00 CFM
Infiltration occurs at all hours.
6. Floors:
Type Slab Floor On Grade
Floor Area 35.0 ft2
Total Floor U -Value 0.420 BTU/(hr•ft2•°F)
Exposed Perimeter 0.0 ft
Edge Insulation R -Value 8.00 (hr•ft2•°F)/BTU
7. Partitions:
(No partition data).
Hourly Analysis Program v5.10 Page 10 of 13
TUK_Catalyst Workplace Activation_v5_1
HERMANSON COMPANY LLP
Space Input Data
11/30/2017
01:19PM
01-11 Telephone Room
1. General Details:
Floor Area 35.0 ft2
Avg. Ceiling Height 10.0 ft
Building Weight 70.0 Ib/ft2
1.1. OA Ventilation Requirements:
Space Usage User -Defined
OA Requirement 1 5.0 CFM/person
OA Requirement 2 0.06 CFM/ft2
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting:
Fixture Type Recessed (Unvented)
Wattage 0.89 W/ft2
Ballast Multiplier 1.08
Schedule 90.1 Office Lights/Elec
2.2. Task Lighting:
Wattage 0.00 W/ft2
Schedule None
2.3. Electrical Equipment:
Wattage 50.0 Watts
Schedule 90.1 Office Lights/Elec
3. Walls, Windows, Doors:
(No Wall, Window, Door data).
4. Roofs, Skylights:
2.4. People:
Occupancy 1.0 Person
Activity Level Office Work
Sensible 245.0 BTU/hr/person
Latent 205.0 BTU/hr/person
Schedule 90.1 Office Occupants
2.5. Miscellaneous Loads:
Sensible 0 BTU/hr
Schedule None
Latent 0 BTU/hr
Schedule None
Exp.
Roof Gross Area (ft2)
Roof Slope (deg.)
Skylight Qty.
H
35.0
0
0
4.1. Construction Types for Exposure H
Roof Type Existing Roof
5. Infiltration:
Design Cooling 0.00 CFM
Design Heating 0.00 ACH
Energy Analysis 0.00 CFM
Infiltration occurs at all hours.
6. Floors:
Type Slab Floor On Grade
Floor Area 35.0 ft2
Total Floor U -Value 0.420 BTU/(hr•ft2•°F)
Exposed Perimeter 0.0 ft
Edge Insulation R -Value 8.00 (hr•ft2•°F)/BTU
7. Partitions:
(No partition data).
Hourly Analysis Program v5.10 Page 11 of 13
TUK_Catalyst Workplace Activation_v5_1
HERMANSON COMPANY LLP
Space Input Data
11/30/2017
01:19PM
01-12 Conference
1. General Details:
Floor Area 125.0 ft2
Avg. Ceiling Height 10.0 ft
Building Weight 70.0 Ib/ft2
1.1. OA Ventilation Requirements:
Space Usage User -Defined
OA Requirement 1 5.0 CFM/person
OA Requirement 2 0.06 CFM/ft2
Space Usage Defaults .. ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting:
Fixture Type Recessed (Unvented)
Wattage 0.89 W/ft2
Ballast Multiplier 1.08
Schedule 90.1 Office Lights/Elec
2.2. Task Lighting:
Wattage 0.00 W/ft2
Schedule None
2.3. Electrical Equipment:
Wattage 300.0 Watts
Schedule 90.1 Office Lights/Elec
3. Walls, Windows, Doors:
(No Wall, Window, Door data).
4. Roofs, Skylights:
2.4. People:
Occupancy 4.0 People
Activity Level Office Work
Sensible 245.0 BTU/hr/person
Latent 205.0 BTU/hr/person
Schedule 90.1 Office Occupants
2.5. Miscellaneous Loads:
Sensible 0 BTU/hr
Schedule None
Latent 0 BTU/hr
Schedule None
Exp.
Roof Gross Area (ft2)
Roof Slope (deg.)
Skylight Qty.
H
125.0
0
0
4.1. Construction Types for Exposure H
Roof Type Existing Roof
5. Infiltration:
Design Cooling 0.00 CFM
Design Heating 0.00 ACH
Energy Analysis 0.00 CFM
Infiltration occurs at all hours.
6. Floors:
Type Slab Floor On Grade
Floor Area 125.0 ft2
Total Floor U -Value 0.420 BTU/(hrft2•°F)
Exposed Perimeter 0.0 ft
Edge Insulation R -Value 8.00 (hrft2•°F)/BTU
7. Partitions:
(No partition data).
Hourly Analysis Program v5.10 Page 12 of 13
TUK_Catalyst Workplace Activation_v5_1
HERMANSON COMPANY LLP
Space Input Data
11/30/2017
01:19PM
01-13 Copy/Mail Room
1. General Details:
Floor Area 125.0
Avg. Ceiling Height 10.0
Building Weight 70.0
1.1. OA Ventilation Requirements:
Space Usage User -Defined
OA Requirement 1 5.0 CFM/person
OA Requirement 2 0.06 CFM/ft2
Space Usage Defaults .. ASHRAE Standard 62.1-2010
ft2
ft
Ib/ft2
2. Internals:
2.1. Overhead Lighting:
Fixture Type Recessed (Unvented)
Wattage 0.89 W/ft2
Ballast Multiplier 1.08
Schedule 90.1 Office LightslElec
2.2. Task Lighting:
Wattage
Schedule
0.00 W/ft2
None
2.3. Electrical Equipment:
Wattage
Schedule 90.1 Office LightslElec
500.0 Watts
3. Walls, Windows, Doors:
(No Wall, Window, Door data).
4. Roofs, Skylights:
2.4. People:
Occupancy 0.0 Person
Activity Level Office Work
Sensible 245.0 BTU/hr/person
Latent 205.0 BTU/hr/person
Schedule None
2.5. Miscellaneous Loads:
Sensible 0 BTU/hr
Schedule None
Latent 0 BTU/hr
Schedule None
Exp.
Roof Gross Area (ft2)
Roof Slope (deg.)
Skylight Qty.
H
125.0
0
0
4.1. Construction Types for Exposure H
Roof Type Existing Roof
5. Infiltration:
Design Cooling 0.00 CFM
Design Heating 0.00 ACH
Energy Analysis 0.00 CFM
Infiltration occurs at all hours.
6. Floors:
Type Slab Floor On Grade
Floor Area 125.0 ft2
Total Floor U -Value 0.420 BTU/(hr•ft2•°F)
Exposed Perimeter 0.0 ft
Edge Insulation R -Value . 8.00 (hr•ft2•°F)/BTU
7. Partitions:
(No partition data).
Hourly Analysis Program v5.10 Page 13 of 13
Hermanson
SYSTEM
INPUT DATA
System Loads
Carrier HAP Version 5.1
Project Name: TUK_Catalyst Workplace Activation_v5_1
Prepared by: HERMANSON COMPANY LLP
RTU -R01 Input Data
11/30/2017
01:19PM
1. General Details:
Air System Name RTU -R01
Equipment Type Packaged Rooftop Units
Air System Type Single Zone CAV
Number of zones 1
2. Ventilation System Components:
Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method ASHRAE Std 62.1-2010
Unocc. Damper Position Closed
Damper Leak Rate 5 %
Outdoor Air CO2 Level 400 ppm
Economizer Data:
Control Integrated enthalpy control
Upper Cutoff 75.0 °F
Lower Cutoff 35.0 °F
Central Cooling Data:
Supply Air Temperature 55.0 °F
Coil Bypass Factor 0.100
Cooling Source Air -Cooled DX
Schedule JFMAMJJASOND
Capacity Control Cycled or Staged Capacity - Fan On
Central Heating Data:
Supply Temperature 86.9 °F
Heating Source Combustion - Natural Gas
Schedule JFMAMJJASOND
Capacity Control Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 1.75
Overall Efficiency 54
Fan Control 2 -speed fan cooling, 1 -speed fan heating
Low Speed Fan Airflow 67
in wg
ok
Ok
Duct System Data:
Supply Duct Data:
Duct Heat Gain 3 %
Duct Leakage 2 %
Return Duct or Plenum Data:
Return Air Via Ducted Return
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
Cooling T-Stat
Occ.
(°F)
01-05 Open Office
x1
01-06 Enclosed Office
x1
01-07 Meeting
x1
Thermostats and Zone Data:
Zone
Cooling T-Stat
Occ.
(°F)
Cooling T-Stat
Unocc.
(°F)
Heating T-Stat
Occ.
(°F)
Heating T-Stat
Unocc.
(°F)
T-Stat
Throttling
Range
(°F)
Diversity
Factor
(%)
Direct
Exhaust
Airflow
(CFM)
Direct
Exhaust Fan
(kW)
1
75.0
80.0
72.0
55.0
1.50
100
0.0
0.0
Thermostat Schedule 90.1 Office HVAC
Unoccupied Cooling is Available
Supply Terminals Data:
Hourly Analysis Program 5.10
Page 1 of 10
Project Name: TUK_Catalyst Workplace Activation_v5_1
Prepared by: HERMANSON COMPANY LLP
RTU -R01 Input Data
11/30/2017
01:19PM
Zone
Terminal Type
Air
Distribution
Air
Distribution
Effectiveness
Specification
Air
Distribution
Effectiveness
Minimum Airflow
Fan Performance
Fan
Efficiency
Design
Supply
Temp.
1
Diffuser (no
reheat)
Ceiling supply /
ceiling return
ASHRAE 62.1
1
0.30 CFM/ft2
-
-
-
Zone Heating Units:
Zone Unit Heat Source Electric Resistance
Zone Heating Unit Schedule JFMAMJJASOND
4. Sizing Data (Computer -Generated):
System Sizing Data:
Sizing Data:
Cooling Supply Temperature 55.0 °F
Supply Fan Airflow 1327.5 CFM
Ventilation Airflow 276.8 CFM
Heating Supply Temperature 86.9 °F
Hydronic Sizing Specifications:
Chilled Water Delta -T 10.0 °F
Hot Water Delta -T 20.0 °F
Safety Factors:
Cooling Sensible 0 %
Cooling Latent 0 %
Heating 0 %
Zone Sizing Data:
Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads
Zone
Supply Airflow
(CFM)
Zone Htg Unit
(MBH)
Reheat Coil
(MBH)
-
(CFM)
1
1300.9
-
-
5. Equipment Data
Central Cooling Unit - Air -Cooled DX
Estimated Maximum Load 42.5 MBH
Design OAT 95.0 °F
Equipment Sizing User -Defined
Gross Cooling Capacity 1.0 MBH
Compressor & OD Fan Power 1.000 kW
DX System Configuration 1 -stage compression, 1 circuit
Conventional Cutoff OAT 55.0 °F
Low Temperature Operation Not used
Central Heating Unit - Combustion
Estimated Maximum Load 23.3 MBH
Equipment Sizing User -Defined
Gross Heating Capacity 1.0 MBH
Average Efficiency 85.0 %
Misc. Electric 0.000 kW
Hourly Analysis Program 5.10 Page 2 of 10
Project Name: TUK_Catalyst Workplace Activation_v5_1
Prepared by: HERMANSON COMPANY LLP
RTU -R02 Input Data
11/30/2017
01:19PM
1. General Details:
Air System Name RTU -R02
Equipment Type
Air System Type
Number of zones
Packaged Rooftop Units
Single Zone CAV
1
2. Ventilation System Components:
Ventilation Air Data:
Airflow Control
Ventilation Sizing Method
Unocc. Damper Position
Damper Leak Rate 5 %
Outdoor Air CO2 Level 400 ppm
Constant Ventilation Airflow
ASHRAE Std 62.1-2010
Closed
Economizer Data:
Control Integrated enthalpy control
Upper Cutoff 75.0 °F
Lower Cutoff 35.0 °F
Central Cooling Data:
Supply Air Temperature 55.0 °F
Coil Bypass Factor 0.100
Cooling Source Air -Cooled DX
Schedule JFMAMJJASOND
Capacity Control Cycled or Staged Capacity - Fan On
Central Heating Data:
Supply Temperature 86.9 °F
Heating Source Combustion - Natural Gas
Schedule JFMAMJJASOND
Capacity Control Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 1.75 in wg
Overall Efficiency 54 %
Fan Control 2 -speed fan cooling, 1 -speed fan heating
Low Speed Fan Airflow 67 %
Duct System Data:
Supply Duct Data:
Duct Heat Gain
3 %
Duct Leakage 2 %
Return Duct or Plenum Data:
Return Air Via Ducted Return
3. Zone Components:
Space Assignments:
Zone 1: Zone 2
01-04 Conference
x1
01-13 Copy/Mail Room
x1
Thermostats and Zone Data:
Zone
Cooling T-Stat
Occ.
(°F)
Cooling T-Stat
Unocc.
(°F)
Heating T-Stat
Occ.
(°F)
Heating T-Stat
Unocc.
(°F)
T-Stat
Throttling
Range
(°F)
Diversity
Factor
(%)
Direct
Exhaust
Airflow
(CFM)
Direct
Exhaust Fan
(kW)
1
75.0
80.0
72.0
55.0
1.50
100
0.0
0.0
Thermostat Schedule 90.1 Office HVAC
Unoccupied Cooling is Available
Supply Terminals Data:
Hourly Analysis Program 5.10
Page 3 of 10
Project Name: TUK_Catalyst Workplace Activation_v5_1
Prepared by: HERMANSON COMPANY LLP
RTU -R02 Input Data
11/30/2017
01:19PM
Zone
Terminal Type
Air
Distribution
Air
Distribution
Effectiveness
Specification
Air
Distribution
Effectiveness
Minimum Airflow
Fan Performance
Fan
Efficiency
Design
Supply
Temp.
1
Diffuser (no
reheat)
Ceiling supply /
ceiling return
ASHRAE 62.1
1
0.30 CFM/ft2
-
-
-
Zone Heating Units:
Zone Unit Heat Source Electric Resistance
Zone Heating Unit Schedule JFMAMJJASOND
4. Sizing Data (Computer -Generated):
System Sizing Data:
Sizing Data:
Cooling Supply Temperature 55.0 °F
Supply Fan Airflow 480.3 CFM
Ventilation Airflow 105.1 CFM
Heating Supply Temperature 86.9 °F
Hydronic Sizing Specifications:
Chilled Water Delta -T 10.0 °F
Hot Water Delta -T 20.0 °F
Safety Factors:
Cooling Sensible 0
Cooling Latent 0 %
Heating 0
Zone Sizing Data:
Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads
Zone
Supply Airflow
(CFM)
Zone Htg Unit
(MBH)
Reheat Coil
(MBH)
-
(CFM)
1
470.7
-
-
5. Equipment Data
Central Cooling Unit - Air -Cooled DX
Estimated Maximum Load 15.7 MBH
Design OAT 95.0 °F
Equipment Sizing User -Defined
Gross Cooling Capacity 1.0 MBH
Compressor & OD Fan Power 1.000 kW
DX System Configuration 1 -stage compression, 1 circuit
Conventional Cutoff OAT 55.0 °F
Low Temperature Operation Not used
Central Heating Unit - Combustion
Estimated Maximum Load 8.9 MBH
Equipment Sizing User -Defined
Gross Heating Capacity 1.0 MBH
Average Efficiency 85.0 %
Misc. Electric 0.000 kW
Hourly Analysis Program 5.10 Page 4 of 10
Project Name: TUK_Catalyst Workplace Activation_v5_1
Prepared by: HERMANSON COMPANY LLP
RTU -R03 Input Data
11/30/2017
01:19PM
1. General Details:
Air System Name RTU -R03
Equipment Type
Air System Type
Number of zones
Packaged Rooftop Units
Single Zone CAV
1
2. Ventilation System Components:
Ventilation Air Data:
Airflow Control
Ventilation Sizing Method
Unocc. Damper Position
Damper Leak Rate 5 %
Outdoor Air CO2 Level 400 ppm
Constant Ventilation Airflow
ASHRAE Std 62.1-2010
Closed
Economizer Data:
Control Integrated enthalpy control
Upper Cutoff 75.0 °F
Lower Cutoff 35.0 °F
Central Cooling Data:
Supply Air Temperature 55.0 °F
Coil Bypass Factor 0.100
Cooling Source Air -Cooled DX
Schedule JFMAMJJASOND
Capacity Control Cycled or Staged Capacity - Fan On
Central Heating Data:
Supply Temperature 86.9 °F
Heating Source Combustion - Natural Gas
Schedule JFMAMJJASOND
Capacity Control Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 1.75 in wg
Overall Efficiency 54 %
Fan Control 2 -speed fan cooling, 1 -speed fan heating
Low Speed Fan Airflow 67 %
Duct System Data:
Supply Duct Data:
Duct Heat Gain
3 %
Duct Leakage 2 %
Return Duct or Plenum Data:
Retum Air Via Ducted Return
3. Zone Components:
Space Assignments:
Zone 1: Zone 3
01-01 E Conference
x1
01-02 SE Open Office
x1
Thermostats and Zone Data:
Zone
Cooling T-Stat
Occ.
(°F)
Cooling T-Stat
Unocc.
(°F)
Heating T-Stat
Occ.
(°F)
Heating T-Stat
Unocc.
(°F)
T-Stat
Throttling
Range
(°F)
Diversity
Factor
(%)
Direct
Exhaust
Airflow
(CFM)
Direct
Exhaust Fan
(kW)
1
75.0
80.0
72.0
55.0
1.50
100
0.0
0.0
Thermostat Schedule 90.1 Office HVAC
Unoccupied Cooling is Available
Supply Terminals Data:
Hourly Analysis Program 5.10
Page 5 of 10
Project Name: TUK_Catalyst Workplace Activation_v5_1
Prepared by: HERMANSON COMPANY LLP
RTU -R03 Input Data
11/30/2017
01:19PM
Zone
Terminal Type
Air
Distribution
Air
Distribution
Effectiveness
Specification
Air
Distribution
Effectiveness
Minimum Airflow
Fan Performance
Fan
Efficiency
Design
Supply
Temp.
1
Diffuser (no
reheat)
Ceiling supply /
ceiling return
ASHRAE 62.1
1
0.30 CFM/ft2
-
-
-
Zone Heating Units:
Zone Unit Heat Source Electric Resistance
Zone Heating Unit Schedule JFMAMJJASOND
4. Sizing Data (Computer -Generated):
System Sizing Data:
Sizing Data:
Cooling Supply Temperature 55.0 °F
Supply Fan Airflow 948.0 CFM
Ventilation Airflow 173.6 CFM
Heating Supply Temperature 86.9 °F
Hydronic Sizing Specifications:
Chilled Water Delta -T 10.0 °F
Hot Water Delta -T 20.0 °F
Safety Factors:
Cooling Sensible 0 %
Cooling Latent 0 %
Heating 0 %
Zone Sizing Data:
Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads
Zone
Supply Airflow
(CFM)
Zone Htg Unit
(MBH)
Reheat Coil
(MBH)
-
(CFM)
1
929.0
-
-
5. Equipment Data
Central Cooling Unit - Air -Cooled DX
Estimated Maximum Load 29.3 MBH
Design OAT 95.0 °F
Equipment Sizing User -Defined
Gross Cooling Capacity 1.0 MBH
Compressor & OD Fan Power ,____ 1.000 kW
DX System Configuration 1 -stage compression, 1 circuit
Conventional Cutoff OAT 55.0 °F
Low Temperature Operation Not used
Central Heating Unit - Combustion
Estimated Maximum Load 22.5 MBH
Equipment Sizing User -Defined
Gross Heating Capacity 1.0 MBH
Average Efficiency 85.0 %
Misc. Electric 0.000 kW
Hourly Analysis Program 5.10 Page 6 of 10
Project Name: TUK_Catalyst Workplace Activation_v5_1
Prepared by: HERMANSON COMPANY LLP
RTU -R04 Input Data
11/30/2017
01:19PM
1. General Details:
Air System Name RTU -R04
Equipment Type
Air System Type
Number of zones 1
Packaged Rooftop Units
Single Zone CAV
2. Ventilation System Components:
Ventilation Air Data:
Airflow Control
Ventilation Sizing Method
Unocc. Damper Position
Damper Leak Rate 5 %
Outdoor Air CO2 Level 400 ppm
Constant Ventilation Airflow
ASHRAE Std 62.1-2010
Closed
Economizer Data:
Control Integrated enthalpy control
Upper Cutoff 75.0 °F
Lower Cutoff 35.0 °F
Central Cooling Data:
Supply Air Temperature 55.0 °F
Coil Bypass Factor 0.100
Cooling Source Air -Cooled DX
Schedule JFMAMJJASOND
Capacity Control Cycled or Staged Capacity - Fan On
Central Heating Data:
Supply Temperature 86.9 °F
Heating Source Combustion - Natural Gas
Schedule JFMAMJJASOND
Capacity Control Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 1.75 in wg
Overall Efficiency 54 %
Fan Control 2 -speed fan cooling, 1 -speed fan heating
Low Speed Fan Airflow 67 %
Duct System Data:
Supply Duct Data:
Duct Heat Gain
3 %
Duct Leakage 2 %
Return Duct or Plenum Data:
Return Air Via Ducted Return
3. Zone Components:
Space Assignments:
Zone 1: Zone 4
Cooling T-Stat
Occ.
(°F)
01-08 Open Office
x1
01-09 Conference
x1
01-10 Telephone Room
x1
01-11 Telephone Room
x1
01-12 Conference
x1
Thermostats and Zone Data:
Zone
Cooling T-Stat
Occ.
(°F)
Cooling T-Stat
Unocc.
(°F)
Heating T-Stat
Occ.
(°F)
Heating T-Stat
Unocc.
(°F)
T-Stat
Throttling
Range
(°F)
Diversity
Factor
(%)
Direct
Exhaust
Airflow
(CFM)
Direct
Exhaust Fan
(kW)
1
75.0
80.0
72.0
55.0
1.50
100
0.0
0.0
Thermostat Schedule 90.1 Office HVAC
Unoccupied Cooling is Available
Supply Terminals Data:
Hourly Analysis Program 5.10
Page 7 of 10
Project Name: TUK_Catalyst Workplace Activation_v5_1
Prepared by: HERMANSON COMPANY LLP
RTU -R04 Input Data
11/30/2017
01:19PM
Zone
Terminal Type
Air
Distribution
Air
Distribution
Effectiveness
Specification
Air
Distribution
Effectiveness
Minimum Airflow
Fan Performance
Fan
Efficiency
Design
Supply
Temp.
1
Diffuser (no
reheat)
Ceiling supply /
ceiling retum
ASHRAE 62.1
1
0.30 CFM/ft2
-
-
-
Zone Heating Units:
Zone Unit Heat Source Electric Resistance,
Zone Heating Unit Schedule JFMAMJJASOND
4. Sizing Data (Computer -Generated):
System Sizing Data:
Sizing Data:
Cooling Supply Temperature 55.0 °F
Supply Fan Airflow 1814.3 CFM
Ventilation Airflow 449.9 CFM
Heating Supply Temperature 86.9 °F
Hydronic Sizing Specifications:
Chilled Water Delta -T 10.0 °F
Hot Water Delta -T 20.0 °F
Safety Factors:
Cooling Sensible 0 %
Cooling Latent 0 %
Heating 0 %
Zone Sizing Data:
Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads
Zone
Supply Airflow
(CFM)
Zone Htg Unit
(MBH)
Reheat Coil
(MBH)
-
(CFM)
1
1778.0
-
-
5. Equipment Data
Central Cooling Unit - Air -Cooled DX
Estimated Maximum Load 59.6 MBH
Design OAT 95.0 °F
Equipment Sizing User -Defined
Gross Cooling Capacity 1.0 MBH
Compressor & OD Fan Power 1.000 kW
DX System Configuration 1 -stage compression, 1 circuit
Conventional Cutoff OAT 55.0 °F
Low Temperature Operation Not used
Central Heating Unit - Combustion
Estimated Maximum Load 29.4 MBH
Equipment Sizing User -Defined
Gross Heating Capacity 1.0 MBH
Average Efficiency 85.0 %
Misc. Electric 0.000 kW
Hourly Analysis Program 5.10 Page 8 of 10
Project Name: TUK_Catalyst Workplace Activation_v5_1
Prepared by: HERMANSON COMPANY LLP
RTU -R05 Input Data
11/30/2017
01:19PM
1. General Details:
Air System Name RTU -R05
Equipment Type Packaged Rooftop Units
Air System Type Single Zone CAV
Number of zones 1
2. Ventilation System Components:
Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method ASHRAE Std 62.1-2010
Unocc. Damper Position Closed
Damper Leak Rate 5 %
Outdoor Air CO2 Level 400 ppm
Economizer Data:
Control Integrated enthalpy control
Upper Cutoff 75.0 °F
Lower Cutoff 35.0 °F
Central Cooling Data:
Supply Air Temperature 55.0 °F
Coil Bypass Factor 0.100
Cooling Source Air -Cooled DX
Schedule JFMAMJJASOND
Capacity Control Cycled or Staged Capacity - Fan On
Central Heating Data:
Supply Temperature 86.9 °F
Heating Source Combustion - Natural Gas
Schedule JFMAMJJASOND
Capacity Control Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 1.75 in wg
Overall Efficiency 54 %
Fan Control 2 -speed fan cooling, 1 -speed fan heating
Low Speed Fan Airflow 67 %
Duct System Data:
Supply Duct Data:
Duct Heat Gain
3 %
Duct Leakage 2 %
Return Duct or Plenum Data:
Retum Air Via Ducted Return
3. Zone Components:
Space Assignments:
Zone 1: Zone 5
01-03 SW Open Office
x1
Thermostats and Zone Data:
Zone
Cooling T-Stat
Occ.
(°F)
Cooling T-Stat
Unocc.
(°F)
Heating T-Stat
Occ.
(°F)
Heating T-Stat
Unocc.
(°F)
T-Stat
Throttling
Range
(°F)
Diversity
Factor
(%)
Direct
Exhaust
Airflow
(CFM)
Direct
Exhaust Fan
(kW)
1
75.0
80.0
72.0
55.0
1.50
100
0.0
0.0
Thermos at Schedule 90.1 Office HVAC
Unoccupied Cooling is Available
Supply Terminals Data:
Hourly Analysis Program 5.10
Page 9 of 10
Air
Distribution
Air
Design
Air
Effectiveness
Distribution
Fan
Supply
Zone
Terminal Type
Distribution
Specification
Effectiveness
Minimum Airflow
Fan Performance
Efficiency
Temp.
Hourly Analysis Program 5.10
Page 9 of 10
Project Name: TUK_Catalyst Workplace Activation_v5_1
Prepared by: HERMANSON COMPANY LLP
RTU -R05 Input Data
11/30/2017
01:19PM
1
Diffuser (no
reheat)
Ceiling supply /
ceiling retum
ASHRAE 62.1
1
0.30 CFM/ft2
Zone Heating Units:
Zone Unit Heat Source Electric Resistance
Zone Heating Unit Schedule JFMAMJJASOND
4. Sizing Data (Computer -Generated):
System Sizing Data:
Sizing Data:
Cooling Supply Temperature 55.0 °F
Supply Fan Airflow 1888.3 CFM
Ventilation Airflow 122.9 CFM
Heating Supply Temperature 86.9 °F
Hydronic Sizing Specifications:
Chilled Water Delta -T 10.0 °F
Hot Water Delta -T 20.0 °F
Safety Factors:
Cooling Sensible 0 %
Cooling Latent 0 %
Heating 0 %
Zone Sizing Data:
Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space Toads
Zone
Supply Airflow
(CFM)
Zone Htg Unit
(MBH)
Reheat Coil
(MBH)
-
(CFM)
1
1850.5
-
-
5. Equipment Data
Central Cooling Unit - Air -Cooled DX
Estimated Maximum Load 47.6 MBH
Design OAT 95.0 °F
Equipment Sizing User -Defined
Gross Cooling Capacity 1.0 MBH
Compressor & OD Fan Power 1.000 kW
DX System Configuration 1 -stage compression, 1 circuit
Conventional Cutoff OAT 55.0 °F
Low Temperature Operation Not used
Central Heating Unit - Combustion
Estimated Maximum Load 31.6 MBH
Equipment Sizing User -Defined
Gross Heating Capacity 1.0 MBH
Average Efficiency 85.0
Misc. Electric 0.000 kW
Hourly Analysis Program 5.10 Page 10 of 10
Hermanson
SYSTEM
OUTPUT DATA
System Loads
Carrier HAP Version 5.1
Air System Sizing Summary for RTU -R01
Project Name: TUK_Catalyst Workplace Activation_v5_1
Prepared by: HERMANSON COMPANY LLP
11/30/2017
01:20PM
Air System Information
Air System Name RTU -R01
Equipment Class PKG ROOF
Air System Type SZCAV
Number of zones 1
Floor Area 2040.0 ft2
Location Seattle IAP, Washington
Sizing Calculation Information
Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 3.5 Tons Load occurs at Jul 1500
Total coil load 42.5 MBH OA DB / WB 86.0 / 67.0 °F
Sensible coil load 35.0 MBH Entering DB / WB 78.0 / 63.3 °F
Coil CFM at Jul 1500 1327 CFM Leaving DB / WB 53.2 / 51.9 °F
Max block CFM 1327 CFM Coil ADP 50.4 °F
Sum of peak zone CFM 1327 CFM Bypass Factor 0.100
Sensible heat ratio 0.825 Resulting RH 46 %
CFM/Ton 375.0 Design supply temp. 55.0 °F
ft2/Ton 576.2 Zone T -stat Check 1 of 1 OK
BTU/(hr•ft2) 20.8 Max zone temperature deviation 0.0 °F
Water flow @ 10.0 °F rise N/A
Central Heating Coil Sizing Data
Max coil load 23.3 MBH Load occurs at Des Htg
Coil CFM at Des Htg 1327 CFM BTU/(hrft2) 11.4
Max coil CFM 1327 CFM Ent. DB / Lvg DB 61.7 / 78.2 °F
Water flow @ 20.0 °F drop N/A
Supply Fan Sizing Data
Actual max CFM 1327 CFM Fan motor BHP 0.64 BHP
Standard CFM 1306 CFM Fan motor kW 0.50 kW
Actual max CFM/ft2 0.65 CFM/ft2 Fan static 1.75 in wg
Outdoor Ventilation Air Data
Design airflow CFM 277 CFM CFM/person 9.23 CFM/person
CFM/ft2 0.14 CFM/ft2
Hourly Analysis Program 5.10 Page 1 of 20
Zone Sizing Summary for RTU -R01
Project Name: TUK_Catalyst Workplace Activation_v5_1
Prepared by: HERMANSON COMPANY LLP
11/30/2017
01:20PM
Air System Information
Air System Name RTU -R01
Equipment Class PKG ROOF
Air System Type SZCAV
Sizing Calculation Information
Calculation Months Jan to Dec
Sizing Data Calculated
Zone Terminal Sizing Data
Number of zones 1
Floor Area 2040.0 ft2
Location Seattle IAP, Washington
Zone CFM Sizing Sum of space airflow rates
Space CFM Sizing Individual peak space loads
Zone Name
Design
Supply
Airflow
(CFM)
Minimum
Supply
Airflow
(CFM)
Zone
CFM/ft2
Reheat
Coil
Load
(MBH)
Reheat
Coil
Water
gpm
@ 20.0 °F
Zone
Htg Unit
Coil
Load
(MBH)
Zone
Htg Unit
Water
gpm
@ 20.0 °F
Mixing
Box Fan
Airflow
(CFM)
Zone 1
1301
1301
0.64
0.0
-
0.0
-
0
Zone Peak Sensible Loads
Zone Name
Zone
Cooling
Sensible
(MBH)
Time of
Peak Sensible
Cooling Load
Zone
Heating
Load
(MBH)
Zone
Floor
Area
(ft2)
Zone 1
27.5
Jul 1800
10.7
2040.0
Space Loads and Airflows
Zone Name /
Space Name
Mult.
Cooling
Sensible
(MBH)
Time of
Peak
Sensible
Load
Air
Flow
(CFM)
Heating
Load
(MBH)
Floor
Area
(ft2)
Space
CFM/ft2
Zone 1
01-05 Open Office
1
24.2
Jul 1800
1138
9.5
. 1835.0
0.62
01-06 Enclosed Office
1
1.3
Jul 1800
66
1.0
90.0
0.73
01-07 Meeting
1
2.1
Jul 2100
97
0.2
115.0
0.85
Hourly Analysis Program 5.10 Page 2 of 20
Ventilation Sizing Summary for RTU -R01
K_Catalyst Workplace Activation_v5_1
MANSON COMPANY LLP
3 Method ASHRAE Std 62.1-2010
Cooling operation
ity (D) 1000
door Air Intake (Vou) 272 CFM
)n Efficiency (Ev) 0.984
(Vot) 277 CFM
tion Analysis
)gram 5.10
Supply Air
(CFM)
Space Floor
Area
(ft2)
Area Outdoor
Air Rate
(CFM/ft2)
Time
Averaged
Occupancy
(Occupants)
People
Outdoor Air
Rate
(CFM/person)
Air
Distribution
Effectiveness
Space
Outdoor Air
(CFM)
Breathing
Zone
Outdoor Air
(CFM)
Spa(
Ventilatic
Efficieni
:e Name
Mult.
(Vpz)
(Az)
(Ra)
(Pz)
(Rp)
(Ez)
(Voz)
(Vbz)
(Ev
ce
1
1138
1835.0
0.06
26.0
5.00
1.0
240
240
0.9E
Office
1
66
90.0
0.06
1.0
5.00
1.0
10
10
1.0!
1
97
115.0
0.06
3.0
5.00
1.0
22
22
0.9E
e Multipliers)
1301
272
0.91
)gram 5.10
Air System Design Load Summary for RTU -R01
Project Name: TUK_Catalyst Workplace Activation_v5_1
Prepared by: HERMANSON COMPANY LLP
11/30/2017
01:20PM
Hourly Analysis Program 5.10
Page 4 of 20
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1500
COOLING OA DB / WB 86.0 °F / 67.0 °F
HEATING DATA AT DES HTG
HEATING OA DB / WB 24.0 °F / 19.2 °F
ZONE LOADS
Details
Sensible
(BTU/hr)
Latent
(BTU/hr)
Details
Sensible
(BTU/hr)
Latent
(BTU/hr)
Window & Skylight Solar Loads
0 ft2
0
-
0 ft2
-
-
Wall Transmission
0 ft2
0
-
0 ft2
0
-
Roof Transmission
2040 ft2
1002
-
2040 ft2
2935
-
Window Transmission
0 ft2
0
-
0 ft2
0
-
Skylight Transmission
0 ft2
0
-
0 ft2
0
-
Door Loads
0 ft2
0
-
0 ft2
0
-
Floor Transmission
2040 ft2
0
-
2040 ft2
0
-
Partitions
1386 ft2
2734
-
1386 ft2
7775
-
Ceiling
0 ft2
0
-
0 ft2
0
-
Overhead Lighting
1961 W
6087
-
0
0
-
Task Lighting
0 W
0
-
0
0
-
Electric Equipment
3295 W
10790
-
0
0
-
People
30
6181
6150
0
0
0
Infiltration
-
0
0-
0
0
Miscellaneous
-
0
0
-
0
0
Safety Factor
0% / 0%
0
0
0%
0
0
» Total Zone Loads
-
26794
6150
-
10710
0
Zone Conditioning
-
29541
6150
-
10691
0
Plenum Wall Load
0%
0
-
0
0
-
Plenum Roof Load
0%
0
-
0
0
-
Plenum Lighting Load
0%
0
-
0
0
-
Retum Fan Load
1327 CFM
0
-
1327 CFM
0
-
Ventilation Load
277 CFM
2962
1304
277 CFM
13993
0
Supply Fan Load
1327 CFM
1722
-
1327 CFM
-1722
-
Space Fan Coil Fans
-
0
--
0
-
Duct Heat Gain / Loss
3%
804
-
3%
321
-
» Total System Loads
-
35028
7454
-
23283
0
Central Cooling Coil
-
35028
7455
-
0
0
Central Heating Coil-
0
-
-
23283
-
» Total Conditioning
-
35028
7455
-
23283
0
Key:
Positive values are clg loads
Negative values are htg loads
Positive values are htg loads
Negative values are clg loads
Hourly Analysis Program 5.10
Page 4 of 20
Air System Sizing Summary for RTU -R02
Project Name: TUK_Catalyst Workplace Activation_v5_1
Prepared by: HERMANSON COMPANY LLP.
11/30/2017
01:20PM
Air System Information
Air System Name RTU -R02
Equipment Class PKG ROOF
Air System Type SZCAV
Number of zones 1
Floor Area 520.0 ft2
Location Seattle IAP, Washington
Sizing Calculation Information
Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space Toads
Central Cooling Coil Sizing Data
Total coil load 1.3 Tons Load occurs at Jul 1700
Total coil load 15.7 MBH OA DB / WB 84.2 / 66.4 °F
Sensible coil load 12.4 MBH Entering DB / WB 77.6 / 63.5 °F
Coil CFM at Jul 1700 480 CFM Leaving DB / WB 53.2 / 52.0 °F
Max block CFM 480 CFM Coil ADP 50.5 °F
Sum of peak zone CFM 480 CFM Bypass Factor 0.100
Sensible heat ratio 0.795 Resulting RH 48 %
CFM/Ton 368.2 Design supply temp. 55.0 °F
ft2/Ton 398.7 Zone T -stat Check 1 of 1 OK
BTU/(hrft2) 30.1 Max zone temperature deviation 0.0 °F
Water flow @ 10.0 °F rise ' N/A
Central Heating Coil Sizing Data
Max coil load 8.9 MBH Load occurs at Des Htg
Coil CFM at Des Htg 480 CFM BTU/(hrft2) 17.2
Max coil CFM 480 CFM Ent. DB / Lvg DB 61.0 / 78.5 °F
Water flow @ 20.0 °F drop N/A
Supply Fan Sizing Data
Actual max CFM 480 CFM Fan motor BHP 0.23 BHP
Standard CFM 473 CFM Fan motor kW 0.18 kW
Actual max CFM/ft2 0.92 CFM/ft2 Fan static 1.75 in wg
Outdoor Ventilation Air Data
Design airflow CFM 105 CFM CFM/person 7.51 CFM/person
CFM/ft2 0.20 CFM/ft2
Hourly Analysis Program 5.10 Page 5 of 20
Zone Sizing Summary for RTU -R02
Project Name: TUK_Catalyst Workplace Activation_v5_1
Prepared by: HERMANSON COMPANY LLP
11/30/2017
01:20PM
Air System Information
Air System Name RTU -R02
Equipment Class PKG ROOF
Air System Type SZCAV
Sizing Calculation Information
Calculation Months Jan to Dec
Sizing Data Calculated
Zone Terminal Sizing Data
Number of zones 1
Floor Area 520.0 ft2
Location Seattle IAP, Washington
Zone CFM Sizing Sum of space airflow rates
Space CFM Sizing Individual peak space loads
Zone Name
Design
Supply
Airflow
(CFM)
Minimum
Supply
Airflow
(CFM)
Zone
CFM/ft2
Reheat
Coil
Load
(MBH)
Reheat
Coil
Water
gpm
@ 20.0 °F
Zone
Htg Unit
Coil
Load
(MBH)
Zone
Htg Unit
Water
gpm
@ 20.0 °F
Mixing
Box Fan
Airflow
(CFM)
Zone 2
471
471
0.91
0.0
-
0.0
-
0
Zone Peak Sensible Loads
Zone Name
Zone
Cooling
Sensible
(MBH)
Time of
Peak Sensible
Cooling Load
Zone
Heating
Load
(MBH)
Zone
Floor
Area
(ft2)
Zone 2
10.0
Jul 1800
4.4
520.0
Space Loads and Airflows
Zone Name /
Space Name
Mult.
Cooling
Sensible
(MBH)
Time of
Peak
Sensible
Load
Air
Flow
(CFM)
Heating
Load
(MBH)
Floor
Area
(ft2)
Space
CFM/ft2
Zone 2
01-04 Conference
1
7.9
Jul 1800
371
4.2
395.0
0.94
01-13 Copy/Mail Room
1
2.1
Jul 2000
99
0.2
125.0
0.79
Hourly Analysis Program 5.10 Page 6 of 20
Ventilation Sizing Summary for RTU -R02
K_Catalyst Workplace Activation_v5_1
MANSON COMPANY LLP
1 Method ASHRAE Std 62.1-2010
Cooling operation
ity (D) 1.000
door Air Intake (Vou) 101 CFM
3 Efficiency (Ev) 0.963
(Vot) 105 CFM
tion Analysis
)gram 5.10
Supply Air
(CFM)
Space Floor
Area
(ft2)
Area Outdoor
Air Rate
(CFM/ft2)
Time
Averaged
Occupancy
(Occupants)
People
Outdoor Air
Rate
(CFM/person)
Air
Distribution
Effectiveness
Space
Outdoor Air
(CFM)
Breathing
Zone
Outdoor Air
(CFM)
Spa(
Ventilatic
Efficient
se Name
Mult.
(Vpz)
(Az)
(Ra)
(Pz)
(Rp)
(Ez)
(Voz)
(Vbz)
(Ev
1)e
1
371
395.0
0.06
14.0
5.00
1.0
94
94
0.9(
I Room
1
99
125.0
0.06
0.0
5.00
1.0
8
8
1.1i
e Multipliers)
471
101
0.91
)gram 5.10
Air System Design Load Summary for RTU -R02
Project Name: TUK_Catalyst Workplace Activation_v5_1
Prepared by: HERMANSON COMPANY LLP
11/30/2017
01:20PM
Hourly Analysis Program 5.10
Page 8 of 20
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1700
COOLING OA DB / WB 84.2 °F / 66.4 °F
HEATING DATA AT DES HTG
HEATING OA DB / WB 24.0 °F / 19.2 °F
ZONE LOADS
Details
Sensible
(BTU/hr)
Latent
(BTU/hr)
Details
Sensible
(BTU/hr)
Latent
(BTU/hr)
Window & Skylight Solar Loads
0 ft2
0
-
0 ft2
-
-
Wall Transmission
0 ft2
0
-
0 ft2
0
-
Roof Transmission
520 ft2
313
-
520 ft2
748
-
Window Transmission
0 ft2
0
-
0 ft2
0
-
Skylight Transmission
0 ft2
0
-
0 ft2
0
-
Door Loads
0 ft2
0
-
0 ft2
0
-
Floor Transmission
520 ft2
0
-
520 ft2
0
-
Partitions
647 ft2
1304
-
647 ft2
3630
-
Ceiling
0 ft2
0
-
0 ft2
0
-
Overhead Lighting
500 W
1571
-
0
0
-
Task Lighting
0 W
0
-
0
0
-
Electric Equipment
1150 W
3786
-
0
0
-
People
14
2954
2870
0
0
0
Infiltration
-
0
0
-
0
0
Miscellaneous
-
0
0
-
0
0
Safety Factor
0% / 0%
0
0
0%
0
0
» Total Zone Loads
-
9928
2870
-
4378
0
Zone Conditioning
-
10591
2870
-
4133
0
Plenum Wall Load
0%
0
-
0
0
-
Plenum Roof Load
0%
0
-
0
0
-
Plenum Lighting Load
0%
0
-
0
0
-
Retum Fan Load
480 CFM
0
-
480 CFM
0
-
Ventilation Load
105 CFM
935
333
105 CFM
5292
0
Supply Fan Load
480 CFM
623
-
480 CFM
-623
-
Space Fan Coil Fans-
0
-
-
0
-
Duct Heat Gain / Loss
3%
298
-
3%
131
-
» Total System Loads
-
12447
3203
-
8933
0
Central Cooling Coil
-
12447
3203
-
0
0
Central Heating Coil
-
0
-
-
8933
-
» Total Conditioning
-
12447
3203
-
8933
0
Key:
Positive values are clg loads
Negative values are htg loads
Positive values are htg loads
Negative values are clg loads
Hourly Analysis Program 5.10
Page 8 of 20
Air System Sizing Summary for RTU -R03
Project Name: TUK_Catalyst Workplace Activation_v5_1
Prepared by: HERMANSON COMPANY LLP
11/30/2017
01:20PM
Air System Information
Air System Name RTU -R03
Equipment Class PKG ROOF
Air System Type SZCAV
Number of zones 1
Floor Area 920.0 ft2
Location Seattle IAP, Washington
Sizing Calculation Information
Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 2.4 Tons Load occurs at Aug 1500
Total coil load 29.3 MBH OA DB / WB 86.0 / 67.0 °F
Sensible coil load 24.1 MBH Entering DB / WB 77.7 / 63.5 °F
Coil CFM at Aug 1500 948 CFM Leaving DB / WB 53.9 / 52.6 °F
Max block CFM 948 CFM Coil ADP 51.2 °F
Sum of peak zone CFM 948 CFM Bypass Factor 0.100
Sensible heat ratio 0.820 Resulting RH 48 %
CFM/Ton 387.8 Design supply temp. 55.0 °F
ft2/Ton 376.3 Zone T -stat Check 1 of 1 OK
BTU/(hrft2) 31.9 Max zone temperature deviation 0.0 °F
Water flow @ 10.0 °F rise N/A
Central Heating Coil Sizing Data
Max coil load 22.5 MBH Load occurs at Des Htg
Coil CFM at Des Htg 948 CFM BTU/(hrft2) 24.4
Max coil CFM 948 CFM Ent. DB / Lvg DB 62.5 / 84.8 °F
Water flow @ 20.0 °F drop N/A
Supply Fan Sizing Data
Actual max CFM 948 CFM Fan motor BHP 0.45 BHP
Standard CFM 933 CFM Fan motor kW 0.36 kW
Actual max CFM/ft2 1.03 CFM/ft2 Fan static 1.75 in wg
Outdoor Ventilation Air Data
Design airflow CFM 174 CFM CFM/person 7.55 CFM/person
CFM/ft2 0.19 CFM/ft2
Hourly Analysis Program 5.10 Page 9 of 20
Zone Sizing Summary for RTU -R03
Project Name: TUK_Catalyst Workplace Activation_v5_1
Prepared by: HERMANSON COMPANY LLP
11/30/2017
01:20PM
Air System Information
Air System Name RTU -R03
Equipment Class PKG ROOF
Air System Type SZCAV
Sizing Calculation Information
Calculation Months Jan to Dec
Sizing Data Calculated
Zone Terminal Sizing Data
Number of zones 1
Floor Area 920.0 ft2
Location Seattle IAP, Washington
Zone CFM Sizing Sum of space airflow rates
Space CFM Sizing Individual peak space loads
Zone Name
Design
Supply
Airflow
(CFM)
Minimum
Supply
Airflow
(CFM)
Zone
CFM/ft2
Reheat
Coil
Load
(MBH)
Reheat
Coil
Water
gpm
@ 20.0 °F
Zone
Htg Unit
Coil
Load
(MBH)
Zone
Htg Unit
Water
gpm
@ 20.0 °F
Mixing
Box Fan
Airflow
(CFM)
Zone 3
929
929
1.01
0.0
0.0
-
0
Zone Peak Sensible Loads
Zone Name
Zone
Cooling
Sensible
(MBH)
Time of
Peak Sensible
Cooling Load
Zone
Heating
Load
(MBH)
Zone
Floor
Area
(ft.)
Zone 3
19.1
Aug 1700
14.6
920.0
Space Loads and Airflows
Zone Name /
Space Name
Mult.
Cooling
Sensible
(MBH)
Time of
Peak
Sensible
Load
Air
Flow
(CFM)
Heating
Load
(MBH)
Floor
Area
(ft.)
Space
CFM/ft2
Zone 3
01-01 E Conference
1
5.7
Aug 1800
294
4.7
245.0
1.20
01-02 SE Open Office
1
13.5
Aug 1600
635
9.9
675.0
0.94
Hourly Analysis Program 5.10 Page 10 of 20
Ventilation Sizing Summary for RTU -R03
K_Catalyst Workplace Activation_v5_1
MANSON COMPANY LLP
t Method ASHRAE Std 62.1-2010
Cooling operation
ity (D) 1000
door Air Intake (Vou) 170 CFM
jn Efficiency (Ev) 0.980
(Vot) 174 CFM
tion Analysis
)gram 5.10
Supply Air
(CFM)
Space Floor
Area
(ft2)
Area Outdoor
Air Rate
(CFM/ft2)
Time
Averaged
Occupancy
(Occupants)
People
Outdoor Air
Rate
(CFM/person)
Air
Distribution
Effectiveness
Space
Outdoor Air
(CFM)
Breathing
Zone
Outdoor Air
(CFM)
Spat
Ventilatic
Efficien4
:e Name
Mult.
(Vpz)
(Az)
(Ra)
(Pz)
(Rp)
(Ez)
(Voz)
(Vbz)
(Ev
:rice
1
294
245.0
0.06
9.0
5.00
1.0
60
60
0.9
Office
1
635
675.0
0.06
14.0
5.00
1.0
111
111
1.0(
e Multipliers)
929
170
0.91
)gram 5.10
Air System Design Load Summary for RTU -R03
Project Name: TUK_Catalyst Workplace Activation_v5_1
Prepared by: HERMANSON COMPANY LLP
11/30/2017
01:20PM
Hourly Analysis Program 5.10
Page 12 of 20
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Aug 1500
COOLING OA DB / WB 86.0 °F / 67.0 °F
HEATING DATA AT DES HTG
HEATING OA DB / WB 24.0 °F / 19.2 °F
ZONE LOADS
Details
Sensible
(BTU/hr)
Latent
(BTU/hr)
Details
Sensible
(BTU/hr)
Latent
(BTU/hr)
Window & Skylight Solar Loads
36 ft'
1309
-
36 ft2
-
-
Wall Transmission
1021 ft'
2457
-
1021 ft'
5541
-
Roof Transmission
920 ft'
389
-
920 ft'
1323
-
Window Transmission
36 ft'
171
-
36 ft'
1064
-
Skylight Transmission
0 ft'
0
-
0 ft'
0
-
Door Loads .
21 ft'
60
-
21 ft2
373
-
Floor Transmission
920 ft2
0
-
920 ft2
1249
-
Partitions
193 ft'
384
-
193 ft'
1093
-
Ceiling
0 ft'
0
-
0 ft'
0
-
Overhead Lighting
884 W
2745
-
0
0
-
Task Lighting
0 W
0
-
0
0
-
Electric Equipment
2040 W
6680
-
0
0
-
People
23
4739
4715
0
0
0
Infiltration
-
0
0
-
3910
0
Miscellaneous
-
0
0
-
0
0
Safety Factor
0% / 0%
0
0
0%
0
0
» Total Zone Loads
-
18935
4715
-
14554
0
Zone Conditioning
-
20389
4715
-
14555
0
Plenum Wall Load
0%
0
-
0
0
-
Plenum Roof Load
0%
0
-
0
0
-
Plenum Lighting Load
0%
0
-
0
0
-
Retum Fan Load
948 CFM
0
-
948 CFM
0
-
Ventilation Load
174 CFM
1864
569
174 CFM
8691
0
Supply Fan Load
948 CFM
1230
-
948 CFM
-1230
-
Space Fan Coil Fans
-
0
--
0
-
Duct Heat Gain / Loss
3%
568
-
3%
437
-
» Total System Loads
-
24050
5284
-
22452
0
Central Cooling Coil-
24050
5285
-
0
0
Central Heating Coil-
0
-
-
22452
-
» Total Conditioning
-
24050
5285
-
22452
0
Key:
Positive values are clg loads
Negative values are htg loads
Positive values are htg loads
Negative values are clg loads
Hourly Analysis Program 5.10
Page 12 of 20
Air System Sizing Summary for RTU -R04
Project Name: TUK_Catalyst Workplace Activation_v5_1
Prepared by: HERMANSON COMPANY LLP
11/30/2017
01:20PM
Air System Information
Air System Name RTU -R04
Equipment Class PKG ROOF
Air System Type SZCAV
Number of zones 1
Floor Area 3740.0 ft2
Location Seattle IAP, Washington
Sizing Calculation Information
Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 5.0 Tons Load occurs at Aug 1500
Total coil load 59.6 MBH OA DB / WB 86.0 / 67.0 °F
Sensible coil load 49.2 MBH Entering DB / WB 78.7 / 63.5 °F
Coil CFM at Aug 1500 1814 CFM Leaving DB / WB 53.2 / 51.8 °F
Max block CFM 1814 CFM Coil ADP 50.4 °F
Sum of peak zone CFM 1814 CFM Bypass Factor 0.100
Sensible heat ratio 0.825 Resulting RH 45 %
CFM/Ton 365.2 Design supply temp. 55.0 °F
ft2/Ton 752.8 Zone T -stat Check 0 of 1 OK
BTU/(hr•ft2) 15.9 Max zone temperature deviation 0.3 °F
Water flow @ 10.0 °F rise N/A
Central Heating Coil Sizing Data
Max coil load 29.4 MBH Load occurs at Des Htg
Coil CFM at Des Htg 1814 CFM BTU/(hrft2) 7.9
Max coil CFM 1814 CFM Ent. DB / Lvg DB 59.9 / 75.2 °F
Water flow @ 20.0 °F drop N/A
Supply Fan Sizing Data
Actual max CFM 1814 CFM Fan motor BHP 0.87 BHP
Standard CFM 1785 CFM Fan motor kW 0.69 kW
Actual max CFM/ft2 0.49 CFM/ft2 Fan static 1.75 in wg
Outdoor Ventilation Air Data
Design airflow CFM 450 CFM CFM/person 11.25 CFM/person
CFM/ft2 0.12 CFM/ft2
Hourly Analysis Program 5.10 Page 13 of 20
Zone Sizing Summary for RTU -R04
Project Name: TUK_Catalyst Workplace Activation_v5_1
Prepared by: HERMANSON COMPANY LLP
11/30/2017
01:20PM
Air System Information
Air System Name RTU -R04
Equipment Class PKG ROOF
Air System Type SZCAV
Sizing Calculation Information
Calculation Months Jan to Dec
Sizing Data Calculated
Zone Terminal Sizing Data
Number of zones 1
Floor Area 3740.0 ft2
Location Seattle IAP, Washington
Zone CFM Sizing Sum of space airflow rates
Space CFM Sizing Individual peak space loads
Zone Name
Design
Supply
Airflow
(CFM)
Minimum
Supply
Airflow
(CFM)
Zone
CFM/ft2
Reheat
Coil
Load
(MBH)
Reheat
Coil
Water
gpm
@ 20.0 °F
Zone
Htg Unit
Coil
Load
(MBH)
Zone
Htg Unit
Water
gpm
@ 20.0 °F
Mixing
Box Fan
Airflow
(CFM)
Zone 4
1778
1778
0.48
0.0
-
0.0
-
0
Zone Peak Sensible Loads
Zone Name
Zone
Cooling
Sensible
(MBH)
Time of
Peak Sensible
Cooling Load
Zone
Heating
Load
(MBH)
Zone
Floor
Area
(ft2)
Zone 4
37.6
Aug 1600
8.8
3740.0
Space Loads and Airflows
Zone Name /
Space Name
Mult.
Cooling
Sensible
(MBH)
Time of
Peak
Sensible
Load
Air
Flow
(CFM)
Heating
Load
(MBH)
Floor
Area
(ft2)
Space
CFM/ft2
Zone 4
01-08 Open Office
1
32.2
Aug 1600
1517
8.4
3450.0
0.44
01-09 Conference
1
2.2
Jul 2100
104
0.1
95.0
1.10
01-10 Telephone Room
1
0.5
Jul 2100
24
0.1
35.0
0.69
01-11 Telephone Room
1
0.5
Jul 2100
24
0.1
35.0
0.69
01-12 Conference
1
2.3
Jul 2100
109
0.2
. 125.0
0.87
Hourly Analysis Program 5.10
Page 14 of 20
Ventilation Sizing Summary for RTU -R04
K_Catalyst Workplace Activation_v5_1
MANSON COMPANY LLP
3 Method ASHRAE Std 62.1-2010
Cooling operation
ity (D) 1.000
door Air Intake (Vou) 424 CFM
3n Efficiency (Ev) 0.943
(Vot) 450 CFM
tion Analysis
)gram 5.10
Supply Air
(CFM)
Space Floor
Area
(ft2)
Area Outdoor
Air Rate
(CFM/ft2)
Time
Averaged
Occupancy
(Occupants)
People
Outdoor Air
Rate
(CFM/person)
Air
Distribution
Effectiveness
Space
Outdoor Air
(CFM)
Breathing
Zone
Outdoor Air
(CFM)
Spa(
Ventilatic
Efficieni
:e Name
Mult.
(Vpz)
(Az)
(Ra)
(Pz)
(Rp)
(Ez)
(Voz)
(Vbz)
(Ev
ce
1
1517
3450.0
0.06
30.0
5.00
1.0
357
357
1.0(
:e
1
104
95.0
0.06
4.0
5.00
1.0
26
26
0.9(
a Room
1
24
35.0
0.06
1.0
5.00
1.0
7
7
0.9,
3 Room
1
24
35.0
0.06
1.0
5.00
1.0
7
7
0.9,
:e
1
109
125.0
0.06
4.0
5.00
1.0
28
28
0.9E
e Multipliers)
1778
424
0.94
)gram 5.10
Air System Design Load Summary for RTU -R04
Project Name: TUK_Catalyst Workplace Activation_v5_1
Prepared by: HERMANSON COMPANY LLP
11/30/2017
01:20PM
Hourly Analysis Program 5.10
Page 16 of 20
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Aug 1500
COOLING OA DB / WB 86.0 °F / 67.0 °F
HEATING DATA AT DES HTG
HEATING OA DB / WB 24.0 °F / 19.2 °F
ZONE LOADS
Details
Sensible
(BTU/hr)
Latent
(BTU/hr)
Details
Sensible
(BTU/hr)
Latent
(BTU/hr)
Window & Skylight Solar Loads
100 ft2
5265
-
100 ft2
-
-
Wall Transmission
85 ft2
130
-
85 ft2
461
-
Roof Transmission
3740 ft2
1582
-
3740 ft2
5380
-
Window Transmission
100 ft2
473
-
100 ft2
2939
-
Skylight Transmission
0 ft2
0
-
0 ft2
0
-
Door Loads
0 ft2
0
-
0 ft2
0
-
Floor Transmission
3740 ft2
0
-
3740 ft2
0
-
Partitions
0 ft2
0
-
0 ft2
0
-
Ceiling
0 ft2
0
-
0 ft2
0
-
Overhead Lighting
3595 W
11159
-
0
0
-
Task Lighting
0 W
0
-
0
0
-
Electric Equipment
3120 W
10217
-
0
0
-
People
40
8242
8200
0
0
0
Infiltration
-
0
0
-
0
0
Miscellaneous-
0
0
-
0
0
Safety Factor
0% / 0%
0
0
0%
0
0
» Total Zone Loads
-
37068
8200
-
8780
0
Zone Conditioning-
41103
8200
-
8664
0
Plenum Wall Load
0%
0
-
0
0
-
Plenum Roof Load
0%
0
-
0
0
-
Plenum Lighting Load
0%
0
-
0
0
-
Retum Fan Load
1814 CFM
0
-
1814 CFM
0
-
Ventilation Load
450 CFM
4633
2217
450 CFM
22854
0
Supply Fan Load
1814 CFM
2354
-
1814 CFM
-2354
-
Space Fan Coil Fans
-
0
-
-
0
-
Duct Heat Gain / Loss
3%
1112
-
3%
263
-
» Total System Loads
-
49202
10417
-
29427
0
Central Cooling Coil
-
49202
10417
-
0
0
Central Heating Coil-
0
-
-
29427
-
» Total Conditioning
-
49202
10417
-
29427
0
Key:
Positive values are clg loads
Negative values are htg loads
Positive values are htg loads
Negative values are clg Toads
Hourly Analysis Program 5.10
Page 16 of 20
Air System Sizing Summary for RTU -R05
Project Name: TUK_Catalyst Workplace Activation_v5_1
Prepared by: HERMANSON COMPANY LLP
11/30/2017
01:20PM
Air System Information
Air System Name RTU -R05
Equipment Class PKG ROOF
Air System Type SZCAV
Number of zones 1
Floor Area 715.0 ft2
Location Seattle IAP, Washington
Sizing Calculation Information
Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space Toads
Central Cooling Coil Sizing Data
Total coil load 4.0 Tons Load occurs at Sep 1500
Total coil load 47.6 MBH OA DB / WB 84.0 / 66.0 °F
Sensible coil load 43.8 MBH Entering DB / WB 76.5 / 62.3 °F
Coil CFM at Sep 1500 1888 CFM Leaving DB / WB 54.7 / 53.3 °F
Max block CFM 1888 CFM Coil ADP 52.2 °F
Sum of peak zone CFM 1888 CFM Bypass Factor 0.100
Sensible heat ratio 0.920 Resulting RH 45 %
CFM/Ton 476.0 Design supply temp. 55.0 °F
ft2/Ton 180.2 Zone T -stat Check 1 of 1 OK
BTU/(hrft2) 66.6 Max zone temperature deviation 0.0 °F
Water flow @ 10.0 °F rise N/A
Central Heating Coil Sizing Data
Max coil load 31.6 MBH Load occurs at Des Htg
Coil CFM at Des Htg 1888 CFM BTU/(hrft2) 44.2
Max coil CFM 1888 CFM Ent. DB / Lvg DB 67.8 / 83.5 °F
Water flow @ 20.0 °F drop N/A
Supply Fan Sizing Data
Actual max CFM 1888 CFM Fan motor BHP 0.90 BHP
Standard CFM 1858 CFM Fan motor kW 0.72 kW
Actual max CFM/ft2 2.64 CFM/ft2 Fan static 1.75 in wg
Outdoor Ventilation Air Data
Design airflow CFM 123 CFM CFM/person 7.68 CFM/person
CFM/ft2 0.17 CFM/ft2
Hourly Analysis Program 5.10 Page 17 of 20
Zone Sizing Summary for RTU -R05
Project Name: TUK_Catalyst Workplace Activation_v5_1
Prepared by: HERMANSON COMPANY LLP
11/30/2017
01:20PM
Air System Information
Air System Name RTU -R05
Equipment Class PKG ROOF
Air System Type SZCAV
Sizing Calculation Information
Calculation Months Jan to Dec
Sizing Data Calculated
Zone Terminal Sizing Data
Number of zones 1
Floor Area 715.0 ft2
Location Seattle IAP, Washington
Zone CFM Sizing Sum of space airflow rates
Space CFM Sizing Individual peak space loads
Zone Name
Design
Supply
Airflow
(CFM)
Minimum
Supply
Airflow
(CFM)
Zone
CFM/ft2
Reheat
Coil
Load
(MBH)
Reheat
Coil
Water
gpm
@ 20.0 °F
Zone
Htg Unit
Coil
Load
(MBH)
Zone
Htg Unit
Water
gpm
@ 20.0 °F
Mixing
Box Fan
Airflow
(CFM)
Zone 5
1851
1851
2.59
0.0
-
0.0
-
0
Zone Peak Sensible Loads
Zone Name
Zone
Cooling
Sensible
(MBH)
Time of
Peak Sensible
Cooling Load
Zone
Heating
Load
(MBH)
Zone
Floor
Area
(ft2)
Zone 5
39.3
Sep 1500
27.9
715.0
Space Loads and Airflows
Zone Name /
Space Name
Mult.
Cooling
Sensible
(MBH)
Time of
Peak
Sensible
Load
Air
Flow
(CFM)
Heating
Load
(MBH)
Floor
Area
(ft2)
Space
CFM/ft2
Zone 5
01-03 SW Open Office
1
39.3
Sep 1500
1851
27.9
715.0
2.59
Hourly Analysis Program 5.10 Page 18 of 20
Ventilation Sizing Summary for RTU -R05
K_Catalyst Workplace Activation_v5_1
MANSON COMPANY LLP
Method ASHRAE Std 62.1-2010
1 Cooling operation
ity (D) 1000
door Air Intake (Vou) 123 CFM
Jn Efficiency (Ev) 1.000
(Vot) 123 CFM
tion Analysis
)gram 5.10
Supply Air
(CFM)
Space Floor
Area
(ft2)
Area Outdoor
Air Rate
(CFM/ft2)
Time
Averaged
Occupancy
(Occupants)
People
Outdoor Air
Rate
(CFM/person)
Air
Distribution
Effectiveness
Space
Outdoor Air
(CFM)
Breathing
Zone
Outdoor Air
(CFM)
Spa
Ventilatic
Efficieni
:e Name
Mult.
(Vpz)
(Az)
(Ra)
(Pz)
(Rp)
(Ez)
(Voz)
(Vbz)
(Ev
Office
1
1851
715.0
0.06
16.0
5.00
1.0
123
123
1.0(
e Multipliers)
1851
123
1.01
)gram 5.10
Air System Design Load Summary for RTU -R05
Project Name: TUK_Catalyst Workplace Activation_v5_1
Prepared by: HERMANSON COMPANY LLP
11/30/2017
01:20PM
Hourly Analysis Program 5.10
Page 20 of 20
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Sep 1500
COOLING OA DB / WB 84.0 °F / 66.0 °F
HEATING DATA AT DES HTG
HEATING OA DB 1 WB 24.0 °F / 19.2 °F
ZONE LOADS
Details
Sensible
(BTU/hr)
Latent
(BTU/hr)
Details
Sensible
(BTU/hr)
Latent
(BTU/hr)
Window & Skylight Solar Loads
500 ft2
28672
-
500 ft2
-
-
Wall Transmission
1273 ft2
1891
-
1273 ft2
6909
-
Roof Transmission
715 ft2
183
-
715 ft2
1029
-
Window Transmission
500 ft2
1752
-
500 ft2
14695
-
Skylight Transmission
0 ft2
0
-
0 ft2
0
-
Door Loads
42 ft2
89
-
42 ft2
746
-
Floor Transmission
715 ft2
0
-
715 ft2
1466
-
Partitions
0 ft2
0
-
0 ft2
0
-
Ceiling
0 ft2
0
-
0 ft2
0
-
Overhead Lighting
687 W
2133
-
0
0
-
Task Lighting
0 W
0
-
0
0
-
Electric Equipment
400 W
1310
-
0
0
-
People
16
3297
3280
0
0
0
Infiltration
-
0
0
-
3039
0
Miscellaneous
-
0
0
-
0
0
Safety Factor
0% / 0%
0
0
0%
0
0
» Total Zone Loads
-
39327
3280
-
27883
0
Zone Conditioning-
39122
3280
-
27076
0
Plenum Wall Load
0%
0
-
0
0
-
Plenum Roof Load
0%
0
-
0
0
-
Plenum Lighting Load
0%
0
-
0
0
-
Retum Fan Load
1888 CFM
0
-
1888 CFM
0
-
Ventilation Load
123 CFM
1048
520
123 CFM
6114
0
Supply Fan Load
1888 CFM
2450
-
1888 CFM
-2450
-
Space Fan Coil Fans
-
0
-
-
0
-
Duct Heat Gain / Loss
3%
1180
-
3%
836
-
» Total System Loads
-
43799
3800
-
31576
0
Central Cooling Coil-
43799
3803
-
0
0
Central Heating Coil-
0
-
-
31576
-
» Total Conditioning
-
43799
3803
-
31576
0
Key:
Positive values are clg Toads
Negative values are htg loads
Positive values are htg loads
Negative values are clg loads
Hourly Analysis Program 5.10
Page 20 of 20
PERMIT COORD COPY
PLAN REVIEW/ROUTING SLIF
PERMIT NUMBER: M17-0189 DATE: 12/04/17
PROJECT NAME: CATALYST WORKPLACE
SITE ADDRESS: 10848 E MARGINAL WAY S
X Original Plan Submittal
Response to Correction Letter #
Revision # before Permit Issued
Revision # after Permit Issued
DEPARTMENTS:
P/J PAN& 141 4�
Building Division Fire Prevention Planning Division
Public Works
Structural
❑ Permit Coordinator
0
PRELIMINARY REVIEW:
Not Applicable ❑
(no approval/review required)
REVIEWER'S INITIALS:
DATE: 12/05/17
Structural Review Required
DATE:
APPROVALS OR CORRECTIONS:
Approved
Corrections Required
(corrections entered in Reviews)
Approved with Conditions
Denied
(ie: Zoning Issues)
DUE DATE: 01/02/18
Notation:
REVIEWER'S INITIALS:
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg 0 Fire 0 Ping 0 PW 0 Staff Initials:
12/18/2013
HERMANSON COMPANY LLP
Home Espanol Contact
Safety & Health
0 Washington State Department of
Labor & Industries
Claims & Insurance
Search L&I
A -Z Index Help
Workplace Rights
HERMANSON COMPANY LLP
Owner or tradesperson
Principals
NICOLPJSEN, KNUT H, PARTNER/MEMBER
BROCK, DANIEL L, PARTNER/MEMBER
FOX, DEAN M, PARTNER/MEMBER
HENGEL, STEPHEN A, PARTNER/MEMBER
DYCKMAN, KENNETH
A, PARTNER/MEMBER
ROBINETT, PAUL J, PARTNER/MEMBER
HERMANSON, RICHARD
L, PARTNER/MEMBER
ALMON, KEVIN, PARTNER/MEMBER
(End: 08/05/2010)
MACDONALD, JAMES, PARTNER/MEMBER
(End: 08/05/2010)
Doing business as
HERMANSON COMPANY LLP
WA UBI No.
602 004 844
1221 2ND AVE N
KENT, WA 98032-2945
206-575-9700
KING County
Business type
Limited Liability Partnership
Governing persons
CORP
HERMANSON
LLC HERMANSON GROUP;
License
Verify the contractor's active registration / license / certification (depending on trade) and any past violations.
Construction Contractor
License specialties
GENERAL
License no.
HERMACLOO5BJ
Effective — expiration
01/11/2000— 08/25/2018
Bond
WESTERN SURETY CO
Bond account no.
929381801
Received by L&I
12/01/2005
Active.
Meets current requirements.
$12,000.00
Effective date
01/01/2006
Expiration date
Until Canceled
Page 1 of 3
Mg L&1
Trades & Licensing
Help us improve
https://secure.lni.wa.gov/verify/Detail.aspx?UBI=602004844&LIC=HERMACL005BJ&SAW= 12/8/2017
10"o (d)
A
AC
ACH
ACT
AD
ADD'L
AFF
AEG
AHU
ALUM
AMP/AMPS
AP
ARCH
BC
BDD
BF
BHP
BLDG
BOD
BOP
BOT
BS
BTU
BTUH
CAP
CBD
CC
CD
CDWR
CDWS
CFM
CHWR
CHWS
CLG
COL
CONC
COND
CONN
CONT
CONTR
COORD
COP
CT
CU
CW
DB
DDC
DEFL
DEG
DIA
DMPR
DN
DOAS
DWG
EXH
EA
EAT
EC
EER
EF
EFF
EL
ELEC/ELECT
EMCS
ENT
EQUIP
ESP
EXIST/(E)
EXH
F
FAC
FD
FDC
FF
FIC
FIO
FLA
FLEX
FLR
FOB
FOIC
FOS
FOT
FP
FPM
FSD
FT
FUT
FV
G
GA
GALV
GC
GPM
GRD
GWB
HD
HORIZ
HP
HR
HSPF
HT
HWTG
HWR
HWS
HX
HZ
MECHANICAL ABBREVIATIONS
AMPS
AIR CONDITIONING
AIR CHANGES PER HOUR
ACOUSTICAL CEILING TILE
ACCESS DOOR
ADDITIONAL
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
ALUMINUM
AMPERAGE
ACCESS PANEL
ARCHITECT
BEADED COLLAR
BACKDRAFT DAMPER
BELOW FLOOR
BRAKE HORSEPOWER
BUILDING
BOTTOM OF DUCT
BOTTOM OF PIPE
BOTTOM
BIRD SCREEN / BLACK STEEL
BRITISH THERMAL UNIT
BRITISH THERMAL UNITS PER HOUR
CAPACITY
CALIBRATED BALANCING DAMPER
CONTROLS CONTRACTOR
CEILING DIFFUSER/CONDENSATE DRAIN
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
CUBIC FEET PER MINUTE
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CEILING
COLUMN
CONCRETE
CONDENSATE
CONNECT/CONNECTED/CONNECTION
CONTINUOUS/CONTINUATION
CONTRACTOR
COORDINATE
COEFFICIENT OF PERFORMANCE
COOLING TOWER
CUBIC/CONDENSER UNIT
DOMESTIC COLD WATER/CONDENSER WATER
DUCTBOARD/DRY BULB/DECIBEL
DIRECT DIGITAL CONTROL
DEFLECTION
DEGREE/DEGREES
DIAMETER
DAMPER
DOWN
DEDICATED OUTSIDE AIR SYSTEM
DRAWING
EXHAUST
EACH
ENTERING AIR TEMPERATURE
EGGCRATE GRILLE/END CAP/ELEC CONTRACTOR
ENERGY EFFICIENT RATING
EXHAUST FAN
EFFICIENCY
ELEVATION
ELECTRICAL/ELECTRIC
ENERGY MANAGEMENT CONTROL SYSTEM
ENTERING
EQUIPMENT
EXTERNAL STATIC PRESSURE
ENTERING WATER TEMPERATURE
EXISTING
EXHAUST
FAHRENHEIT
FIRE ALARM CONTRACTOR
FIRE DAMPER
FIRE DEPARTMENT CONNECTION
FINISHED FLOOR
FURNISHED AND INSTALLED BY CONTRACTOR
FURNISHED AND INSTALLED BY OWNER
FULL LOAD AMPS
FLEXIBLE
FLOOR
FLAT ON BOTTOM
FURNISHED BY OTHERS,
INSTALLED BY CONTRACTOR
FLAT ON SIDE
FLAT ON TOP
FIRE PROTECTION
FEET PER MINUTE
FIRE/SMOKE DAMPER
FOOT/FEET
FUTURE
FACE VELOCITY
GRILLE
GAUGE/GALLON
GALVANIZED
GENERAL CONTRACTOR
GALLONS PER MINUTE
GRILLE/REGISTER/DIFFUSER
GYPSUM WALL BOARD
HEAD
HORIZONTAL
HORSEPOWER
HOUR
HEATING SEASONAL PERFORMANCE FACTOR
HEIGHT
HIGH WALL TRANSFER GRILLE
HOT WATER RETURN
HOT WATER SUPPLY
HEAT EXCHANGER
HERTZ
BC
CW
D
E
EER
MC
N
N WG
PLV
KW
LAT
LB/LBS
LF/LIN FT
LPG
LPS
LVG
LWA
LWG
LWT
MAX
MAU
MBH
MCA
MD
MFR
MISC
MIN
MPS
MT
MTD
MUW
NA
NC
NG/NGAS
NIC
NO
NPW
N -R
OA/OSA
OBD
OD
PCF
PD
PH
POC
P/PRESS
PSI
PSIG
QTY
R
RA
RD/RND
REF
REQ
RESID
RF
RG
RL
RPM
RS
S
SA
SAT
SD
S/D
S_C
SEER
SENS
SL
SM
SPEC
SO
SOG
SP
SF
SS
STRUC
TA
TEMP
TBD
TOD
TOS
TOT
TSP
TSTAT
TYP
UH
UNO
V
VD
VEL
VERT
VFD
VOL
W
WB
WG
W/
W/O
W/SF
WSEC
NTERNATIONAL BUILDING CODE
NDUSTRIAL COLD WATER
NSIDE DIAMETER/DIMENSION
NVERT ELEVATION
NTEGRATED ENERGY EFFICIENCY RATIO
NTERNATIONAL MECHANICAL CODE
NCHES
NCHES WATER GAUGE
NTEGRATED PART LOAD VALUE
KILOWATTS
LEAVING AIR TEMPERATURE
POUND/POUNDS
LINEAL FOOT/FEET
LIQUID PROPANE GAS
LOW PRESSURE STEAM
LEAVING
SOUND POWER RATING LEVEL (IN DB)
LOW WALL GRILLE
LEAVING WATER TEMPERATURE
MAXIMUM
MAKE UP AIR UNIT
1000 BRITISH THERMAL UNITS/HOUR
MINIMUM CIRCUIT AMPACITY
MOTORIZED DAMPER
MANUFACTURER
MISCELLANEOUS
MINIMUM/MINUTE
MEDIUM PRESSURE STEAM
MOUNT
MOUNTED
MAKE-UP WATER
NOT APPLICABLE
NORMALLY CLOSED/NOISE CRITERIA
NATURAL GAS
NOT IN CONTRACT
NORMALLY OPEN/NUMBER
NON -POTABLE WATER
NON-RESIDENTIAL
OUTSIDE AIR
OPPOSED BLADE DAMPER
OUTSIDE DIAMETER/DIMENSION
POUNDS PER CUBIC FOOT
PRESSURE DROP
PHASE
POINT OF CONNECTION
PRESSURE
POUNDS PER SQUARE INCH
POUNDS PER SQUARE INCH GAUGE
QUANTITY
RETURN GRILLE/RELOCATED/RETURN
RETURN AIR
ROUND
REFERENCE
REQUIRED
RESIDENTIAL
RELIEF
REFRIGERANT DISCHARGE GAS
REFRIGERANT LIQUID
REVOLUTIONS PER MINUTE
REFRIGERANT SUCTION
SUPPLY
SUPPLY AIR
SATURATION/SUPPLY AIR TEMPERATURE
SMOKE DETECTOR
SLIP & DRIVE CONNECTION
SEATTLE CODE
SEASONAL ENERGY EFFICIENCY RATING
SENSIBLE
SOUND LINED
SHEETMETAL
SPECIFICATION
SCREENED OPENING
SLAB ON GRADE
STATIC PRESSURE
SQUARE FEET
STAINLESS STEEL
STRUCTURAL
TRANSFER AIR
TEMPERATURE/TEMPORARY
TO BE DETERMINED
TOP OF DUCT
TOP OF STEEL/TOP OF SLAB
TOTAL
TOTAL STATIC PRESSURE
THERMOSTAT
TYPICAL
UNIT HEATER
UNLESS NOTED OTHERWISE
VOLT
VOLUME DAMPER
VELOCITY
VERTICAL
VARIABLE FREQUENCY DRIVE
VOLUME
WRAPPED DUCT
WET BULB
WATER GAUGE
WITH
WITHOUT
WATTS PER SQUARE FOOT
WASHINGTON STATE ENERGY CODE
MECHANICAL LEGEND
fio"xio"IXI
•10"X10";)
,10"X 10"
4-10"x1017-1
10"X10"0
1-10"xio";,/
,10"X10"n
1Q"0
10"0
10"0O
)12"X10"oQ)
h 12"X1O"�
10"o 1F
10
10"0J Jj
10"O1
•k
2
11
1>
NrwVV%
-1\r>
RECT SUPPLY AIR DUCT
UP/TOWARD
RECT SUPPLY AIR DUCT
DN/AWAY
RECT EXHAUST OR RETURN DUCT
UP/TOWARD
RECT EXHAUST OR RETURN DUCT
DN/AWAY
ROUND DUCT - UP/TOWARD
ROUND DUCT - DN/ AWAY
FLATOVAL DUCT - UP/ TOWARD
FLATOVAL DUCT - DN/ AWAY
DUCT OVERLAP
BOOT TAP
45' TAP
VOLUME DAMPER
CALIBRATED BALANCING DAMPER
RISE(R) & DROP(D)
TRANSITION
TURNING VANES/SPLITTERS
DUCT MOUNTED SMOKE DETECTOR
BACK DRAFT DAMPER
FLEXIBLE DUCT
AIR FLOW (FORCED AIR)
6_"X16"ODSLi
lo
CD1-100
8"0
T T'STAT/TEMP SENSOR
H HUMIDITY SENSOR
sD SMOKE DETECTOR
sP STATIC PRESSURE SENSOR
oU OCCUPANCY SENSOR
COMBINATION FSD
FIRE DAMPER
SMOKE DAMPER
MOTOR OPERATED DAMPER
ACCESS DOORS
SOUND TRAP
FLEX CONNECTION
ACOUSTICALLY LINED DUCT
OD = OUTSIDE DIMENSIONS
SL = SOUND LINING (THICKNESS)
FABRIC DUCT
CLEARANCE
SUPPLY AIR DIFFUSER
(WITH CORE BLANKOFF/ROTATE)
CEILING RETURN, TRANSFER OR
EXHAUST AIR GRILLE
SLOTTED DIFFUSER (PLAN VIEW)
REVISION CLOUD & TRIANGLE
ROUND DUCT SYMBOL
FLATOVAL DUCT SYMBOL
DEGREES SYMBOL
POINT OF CONNECTION
GRD TAG IDENTIFIER = TYPE -CFM
SIZE
z
CARBON DIOXIDE
SENSOR
co CARBON MONOXIDE
SENSOR
()SENSOR
EXISTING DUCTWORK
• DEMO DUCTWORK
4.
0
D
z z
z z
2-CHWS /CHWR-5
z- RL/RS5
2- NG -5
LPG -s
z-CDWS /CDWR-5
z--HWS/HWR-5
z- COND -5
FOV -5
z-- FOS /FOR -s
RDG-i
® z
da z
WALL -MOUNTED GRILLE
PIPE ELBOW UP
PIPE ELBOW DN
DIRECTION OF FLOW
DIRECTION OF SLOPE DOWN
PLUG OR CAP
PRESS REDUCING ASSEMBLY
SOLENOID VALVE
PUMP
CHILLED WATER SUPPLY/RETURN
REFRIGERANT LIQUID/SUCTION
NATURAL GAS
LIQUID PROPANE GAS
CONDENSER WATER SUPPLY/RETURN
HEATING WATER SUPPLY/RETURN
CONDENSATE
FUEL OIL VENT
FUEL OIL SUPPLY/RETURN
REFRIGERANT DISCHARGE GAS
MECHANICAL GENERAL NOTES
1. WORK SHALL CONFORM TO APPLICABLE CODES AND REGULATIONS, INCLUDING, BUT NOT LIMITED TO THE 2015 IBC, 2015 WSEC, 2015 IMC, &
& SIMILAR YEAR WAC 296-104 BOILER RULES.
2. DO NOT SCALE DRAWINGS, DIMENSIONS GOVERN. DIMENSIONS ARE TO FACE OF STUD, CONCRETE, OR MASONRY UNO.
3. LOCATION AND DETAILS OF EQUIPMENT, DUCT ROUTING, AND CONNECTIONS ARE APPROXIMATE. COORDINATE FINAL LOCATIONS WITH
OTHER TRADES. INSTALL IN ACCORDANCE WITH APPROVED SUBMITTALS AND DETAIL DRAWINGS WHEN APPLICABLE.
4. VERIFY EXISTING CONDITIONS, DIMENSIONS, DETAILS, ETC. NOTIFY ENGINEER OF ANY DISCREPANCIES PRIOR TO PROCEEDING WITH WORK.
5. WHEN CONSTRUCTION DETAILS ARE NOT SHOWN OR NOTED FOR ANY PART OF THE WORK DETAILS SHALL BE THE SAME
AS FOR OTHER SIMILAR WORK. IF ADDITIONAL QUESTIONS REMAIN, CONTACT THE ENGINEER PRIOR TO PROCEEDING.
6. ALL STRUCTURAL OPENINGS AND PLATFORMS SHALL BE PROVIDED BY THE GENERAL CONTRACTOR UNO.
7. DUCT SEALING AND CONSTRUCTION TO MEET SMACNA AND ENERGY CODE REQUIREMENTS. UNLESS OTHERWISE NOTED, LOW PRESSURE DUCTWORK
DOWNSTREAM OF VAV BOXES, CONSTANT VOLUME AC SYSTEMS, TOILET EXHAUSTS, ETC.) TO MEET 2" CONSTRUCTION STANDARDS WITH
SEAL CLASS C. MEDIUM PRESSURE DUCTWORK (UPSTREAM OF VAV BOXES, HIGH VELOCITY EXHAUSTS, ETC.) TO MEET 4" CONSTRUCTION STANDARDS
WITH SEAL CLASS A. DUCT RISERS IN SHAFTS WITH DAMPERED PENETRATIONS TO MEET 6" CONSTRUCTION STANDARDS WITH SEAL CLASS A.
8. ALL CEILING DIFFUSERS ARE 4 -WAY THROW UNLESS NOTED OTHERWISE.
9. ALL DUCT DIMENSIONS ARE OUTSIDE DIMENSIONS BEFORE SOUND LINING HAS BEEN ACCOUNTED FOR (SOUND LINING ® 1", UNO)
10. OUTSIDE AIR INTAKES ON ALL AIR HANDLING UNITS SHALL BE 10 FEET AWAY FROM ANY VENTS, STREETS, LOADING DOCK,
NEIGHBORING LOT LINES & FUEL BURNING EQUIPMENT OR 3 FEET BELOW OR 25' ABOVE ANY CONTAMINANT SOURCE WITHIN 10 FEET.
11. ALL AIR ECONOMIZERS SHALL BE CAPABLE OF THE FOLLOWING PER C403.3.1 & C403.2.4.7:
- 0% TO 100% OF THE DESIGN SUPPLY AIR WITH FAULT DETECTION & DIAGNOSTIC REPORTING.
- CONTROLLED BY A CONTROL SYSTEM DETERMINING IF THE OUTSIDE AIR CAN MEET PART OR ALL OF THE BUILDING COOLING LOADS.
- INTEGRATED TO PROVIDE PARTIAL COOLING EVEN WHEN MECHANICAL COOLING IS REQUIRED.
12. OUTSIDE AIR INTAKE, RELIEF, AND EXHAUST OPENINGS SHALL BE EQUIPPED WITH MOTORIZED CLASS 1 LOW LEAK (<4 CFM/SF ® 1" WG) DAMPERS
(OR GRAVITY PER EXCEPTIONS IN C403.2.4.3) DAMPERS WHICH CLOSE AUTOMATICALLY WHEN SYSTEM IS OFF OR UPON POWER FAILURE, UNO FOR
SMOKE CONTROL SYSTEM OPERATION.
13. THE CONTROL SYSTEM SHALL MEET C403 AND BE PROGRAMMABLE, CAPABLE OF BEING SET FOR DIFFERENT DAY TYPES PER WEEK,
DEADBAND SETTING OF AT LEAST 5'F (10'F FOR RESIDENTIAL), BETWEEN THE HEATING AND COOLING SETPOINTS AND
SETBACK TEMPERATURES WITH OPTIMAL START CONTROL. CONTROL SYSTEM SHALL INCLUDE A MICROPROCESSOR AND BE CAPABLE OF VARYING FLOWS
AND RESETTING SUPPLY AIR & WATER TEMPERATURES BY REPRESENTATIVE BUILDING LOADS WHERE REQUIRED IN C403.4.
14. WHERE REQUIRED BY C408 RECORD DRAWINGS OF THE. ACTUAL INSTALLATION SHALL BE PROVIDED TO THE BUILDING OWNER
WITHIN 90 DAYS OF THE DATE OF SYSTEM ACCEPTANCE PER THE ENERGY CODE. AN OPERATING MANUAL AND MAINTENANCE MANUAL
SHALL BE PROVIDED TO THE BUILDING OWNER. ALL HVAC SYSTEMS SHALL BE BALANCED AND A WRITTEN BALANCING REPORT
SHALL BE PROVIDED TO THE OWNER. HVAC CONTROL SYSTEMS SHALL BE TESTED TO ENSURE THAT THEY OPERATE IN ACCORDANCE
WITH APPROVED PLANS. A PRELIMINARY COMMISSIONING REPORT OF TEST PROCEDURES AND RESULTS SHALL
BE PREPARED PRIOR TO ISSUANCE OF A FINAL CERTIFICATE OF OCCUPANCY. A COMPLETE FINAL COMMISSIONING REPORT OF
TEST PROCEDURES AND RESULTS SHALL BE PROVIDED TO THE OWNER.
15. MECHANICAL SYSTEMS SHALL COMPLY WITH SEISMIC RESTRAINT REQUIREMENTS OF THE BUILDING CODE SMACNA AND ASCE 7. ALL LIFE
SAFETY OR HAZARDOUS MATERIAL RELATED SYSTEMS SHALL BE DEEMED AN Ip=1.5 FOR RESTRAINT METHODS OR AS NOTED ON THE DRAWINGS.
REFER TO CODES FOR INSTALLATION REQUIREMENTS AND EXCEPTIONS BASED ON SIZING, WEIGHTS AND MOUNTING HEIGHTS.
16. PROVIDE EARTHQUAKE RESTRAINTS FOR HVAC EQUIPMENT AS REQUIRED BY SMACNA SEISMIC RESTRAINT MANUAL, SEISMIC HAZARD B.
WIRES FOR CEILING SYSTEM ETC. SHALL NOT BE HUNG OFF HVAC EQUIPMENT OR HVAC EQUIPMENT SUPPORTS.
17. PROVIDE FIRE AND COMBINATION FIRE/SMOKE DAMPERS WHERE SHOWN ON PLANS AND WHERE REQUIRED PER CODE.
18. ALL PIPING PENETRATIONS THROUGH RATED ASSEMBLIES SHALL BE SEALED WITH AN UL APPROVED FIRE CAULKING.
19. SMOKE DETECTORS PROVIDING AUTOMATIC SHUTDOWN SHALL BE PROVIDED IN THE RETURN AIR, PER MECH CODE, SUCH AS HVAC
EQUIPMENT DELIVERING (NOT EXHAUST) >2000 CFM (INCLUDING MULTIPLE UNITS DUCTED INTO COMMON DISTRIBUTION OR RETURN, WITH A TOTAL
SUPPLY >2000 CFM) OR EACH STORY OF RETURN SYSTEMS OVER 15,000 CFM IN A MULTI -STORY INSTALLATION, NOT IN SYSTEMS SERVING SINGLE
ROOMS/SPACES. SMOKE DETECTORS SHALL BE FIC (ELEC) UNO. POWER -WIRING AND INTERLOCK TO FIRE ALARM SYSTEM BY ELECTRICAL CONTRACTOR
AS APPLICABLE. VAV BOX (WITH FAN) SHUTDOWN CAN BE THROUGH CONTROLS SYSTEM.
20. MECHANICAL ACCESS PANELS SHALL BE PROVIDED BY MECHANICAL CONTRACTOR AND INSTALLED BY GENERAL CONTRACTOR.
21. ALL MOTOR STARTERS NOT SHOWN IN EQUIPMENT SCHEDULES SHALL BE FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR.
MOTOR EFFICIENCIES TO MEET OR EXCEED CODE MINIMUM.
22. FOR ALL "SEALED AIR TIGHT" OR PRESSURIZED SHAFTS/ROOMS, THE FOLLOWING SHALL OCCUR:
- ALL VERTICAL JOINTS & CORNERS SHALL BE PROVIDED WITH A CONTINUOUS SEAL FOR THE LENGTH OF THE JOINT (BY GC).
- TOP AND BOTTOM WALL TRACKS SHOULD BE CAULKED ALONG THEIR ENTIRE LENGTH (BY GC).
-ANY FLOOR DECKING PERPENDICULAR TO THE CONSTRUCTION SHALL BE CAULKED (BY GC). FILLING WITH ROCK WOOL IS NOT ACCEPTABLE.
- ANY PENETRATIONS OF THE CONSTRUCTION (DUCTWORK CONDUIT PIPING ...) SHALL BE SEALED ON BOTH SIDES
- ALL DOORS SHALL BE PROVIDED WITH TIGHT FITTING GASKETS AND THRESHOLD SWEEPS, AND OPEN AGAINST THE DIRECTION OF PRESSURE.
- USE SECTION 909.5 OF THE 2012 IBC FOR MAX ALLOWABLE LEAKAGE AREA, FOLLOWING THE GUIDELINES FOR TIGHT STAIR SHAFT CONSTRUCTION.
23. ALL ADHESIVES, SEALANTS, PAINTS AND COATINGS USED DURING THE INSTALLATION/FINISH WORK SHALL MEET THE LEED REQUIREMENTS FOR IEQ.
24. MAXIMUM S(UL-181
ANDARD LENGTH OF FLEXIBLE DUCT SHALL BE 12 FEET; UP TO 25' MAXIMUM LENGTH IS ACCEPTABLE IF;
REFER TOTINST LLATION SDETDAILS NOT "SUPPORTOREQIS
REMENTSDFLEXIBLE DUCTEFFIAMEBSPREADMRNATINGI SHALLBBED< 2520 NOT EXCEED
MOK RDEVELOPEDL.
RATING SHALL BE < 50. USE THERMAFLEX MODEL G -KM FOR LOW AND MEDIUM PRESSURE APPLICATIONS OR APPROVED EQUAL.
25. ELECTRICAL METERING OF SYSTEMS AS REQUIRED BY ENERGY CODE SECTION C409 IS BY ELECTRICAL. THE ELECTRICAL DESIGN & CONTRACTOR TEAM
WILL FURNISH THE NECESSARY ELECTRICAL DISTRIBUTION AND METERING COMPONENTS - SEE ELECTRICAL DRAWINGS. THE MECHANICAL CONTRACTOR
WILL FURNISH A BUILDING MANAGEMENT SYSTEM CAPABLE OF COLLECTING AND STORING THE INFORMATION WITH A VISIBLE DISPLAY/NOTIFICATION
READILY ACCESSIBLE TO OPERATION AND MANAGEMENT PERSONNEL AS REQUIRED.
26. C406 "ADDITIONAL ENERGY PACKAGE OPTIONS" AS APPLICABLE.
DUCTI LAST UPDATED 07/11/16
DUCT TYPE
DUCT LOCATION (IN HEATED AND MECHANICALLY COOLED DUCT SYSTEM)
INSULATION
R -VALUE
REMARKS
SUPPLY & RETURN
NOT WITHIN CONDITIONED SPACE: OUTSIDE BUILDING
R-8
1,2,3
OUTSIDE AIR
WITHIN CONDITIONED SPACE: INSIDE BUILDING
SEE NOTES 4 & 5
1,2,3,4,5
SUPPLY & RETURN
NOT WITHIN CONDITIONED SPACE: INSIDE BUILDING
R-6
1,2
SUPPLY AIR
<55° OR >105°
WITHIN CONDITIONED SPACE
R-3.3
1,2
1 REFER TO C403.2.8 FOR FURTHER REQUIREMENTS & ALSO R403 FOR RESIDENTIAL INSTALLATIONS
2 INSULATED COOLED DUCTS REQUIRED A VAPOR RETARDER (PERM < 0.5) AND SEALED JOINTS
3 WEATHERPROOF BARRIER REQUIRED AROUND DUCTWORK TO MAINTAIN WATER TIGHTNESS
4 INSULATE OUTSIDE AIR DUCTS TO BUILDING EXTERIOR WALL LEVEL PER ENERGY CODE SECTION: C403.2.8.1 UNTIL
CONNECTED TO EQUIPMENT SERVED OR TO THE CODE REQUIRED SHUTOFF DAMPER (AND Z" THICK INSULATION MIN.
TO PREVENT CONDENSATION ON DUCTS IN PLENUM UP TO THE HEATING OR COOLING EQUIPMENT)
5 R-7 CAN BE USED IN LIEU OF BUILDING ENVELOPE INSULATION LEVEL IF: DEDICATED OUTSIDE AIR SYSTEM AND <2,800 CFM SUPPLY AIR
MINIMUM PIPE INSULATION LAST UPDATED: 07/11/16
FLUID DESIGN
OPERATING
TEMP °F
INSULATION CONDUCTIVITY
NOMINAL PIPE DIAMETER (INCH)
CONDUCTIVITY
RANGE
MEAN TEMP
RATING °F
<1
1 TO
<1-1/2
1-1/2 TO
<4
4 TO
<8
>8
HEATING SYSTEMS (STEAM, CONDENSATE, HYDRONIC HOT WATER, DOMESTIC HOT WATER & RECIRC)
>350
0.32-0.34
250
4.5
5.0
5.0
5.0
5.0
251-350
0.29-0.32
200
3.0
4.0
4.5
4.5
4.5
201-250
0.27-0.30
150
2.5
2.5
2.5
3.0
3.0
141-200
0.25-0.29
125
1.5
1.5
2.0
2.0
2.0
105-140
0.21-0.28
100
1.0
1.0
1.5
1.5
1.5
DOMESTIC COLD WATER AND HORIZONTAL RAIN LEADERS TO FIRST VERTICAL RAIN LEADER (TO PREVENT CONDENSATION)
N/A
0.21-0.27
75
0.5
1 0.5
0.5
0.5
0.5
COOLING SYSTEMS (CHILLED WATER, BRINE AND REFRIGERANT, WATERSIDE ECONOMIZER SYSTEMS)**
40-60
0.21-0.27
75
0.5
0.5
1.0
1.0
1.0
<40
0.20-0.26
75
0.5
1.0
1.0
1.0
1.5
NOTE:
* NOT REQUIRED FOR STRAINERS, CONTROL VALVES & BALANCING VALVES ASSOCIATED WITH PIPING 1" OR LESS IN DIA.
TYPICAL CONDENSER WATER PIPE IN NON -ECONOMIZER SYSTEMS IS NOT INSULATED SEE R403 FOR RESIDENTIAL INSTALLATIONS.
**
DRAWING INDEX
SHEET NO.
SHEET TITLE
CURRENT
REVISION
M0.00
LEGEND, ABBREVIATIONS, GENERAL NOTES, & SHEET INDEX - HVAC
M0.01
SCHEDULE SHEET - HVAC
M2.01 D
PARTIAL 1ST FLOOR DEMO PLAN - HVAC
M2.01
PARTIAL 1ST FLOOR PLAN - HVAC
r--.._________________....
REVISIONS
No changes shall i• f -n do to the scope
of work withcu+l prior approve) of
Tukwila Building Division.
NOTE: Revisions will require a new plan submittal
and may include additional plan review fees
tSERARA I'" SIT
1 REQUIT* ? C'= Vii:
❑ Niectzanicai
Iectrical
lumbing
Gas Piping
City of Tukwila
BLiII_I;IING DIVISION
APN NUMBER
0323049164
Hermanson
Building Today, Defining Tomorrow
Hermanson Company LLP
1221 2nd Avenue North
Kent, Washington 98032
Tel: (206) 575-9700
Fax: (206) 575-9800
www.hermanson.com
Contractor Reg #: HERMACLOO5BJ
LEGAL DESCRIPTION
PARCEL 2 OF TUKWILA BLA L08-023 REC #20080612900007 LOCATED IN W
1/2 OF SW 1/4 OF 03-23-04
CATALYST
WORKPLACE
ACTIVATION TI
10848 E. MARGINAL WAY S.
TUKWILA, WA
VICINITY MAP
NO SCALE
FILE COPY
Permit NotV%I'I0`61
Plan review approval i3 subject to errors and omissions.
Approval of constructi pn documents does net a Jtiorize
the violation of any adopted coda or ordinanc o. Receipt
of approved Field Copy and conditions is acknowizdged:
17-j 11 / 11
SITE MAP
NO SCALE
By:
Date:
CtyofTukwila
BUILDING DIVISION
CEIVED
QF TUKWILA
042017
PERMIT CENTER
I7- 0 1 8 9
ISSUE FOR PERMIT
Revisions
12/01/17 TMP ISSUE FOR PERMIT
No. Date By Description
Design
Design Team
TMP
Drawn
FVP
Checked
DTN
Pre -Construction Number 11-17-11513
Construction Number
Issue Date
12/01/17
LEGEND, ABBREVIATION,
GENERAL NOTES & SHEET
INDEX - HVAC
MO
REVIEWED FOR
MPLIANCE
OVED
E`'82017
ft -4 x-12
City of Tukwila
BUILDING DIVISION
PACKAGED AC UNIT SCHEDULE (EXISTNG) LAST UPDATED: 11/22/17
UNIT
TAG
LOCATION
AREA
SERVED
BASIS OF
DESIGN
SUPPLY
CFM
OSA
CFM
ESP
IN WG
OSA °F
MAT °F
UNIT/DUCT
SAT DB °F
COOLING CAPACITY
GAS HEATING CAPACITY
SEER/
EER
ELEC
6
SOUND
dBA
WEIGHT
LBS
REMARKS
STAGES
INPUT
MBH
OUTPUT
MBH
NG
CONN
DB
WB
COND DB
DB
WB
TOTAL MBH
SENS. MBH
MCA
V/PH
RTU -R01
ROOF
CONFERENCE
GCS16-048
1600
280
0.50
82
66
95
78.0
63.0
55.0
47
34
1
75
60
0.50
10.3/9.5
12
460/3
82
500
1,2
RTU -R02
ROOF
OPEN OFFICE
TRANE 4YCC3030
1000
105
0.58
82
66
95
78.0
63.0
55,0
29
23
1
75
60.5
0.50
13/11
19
208/3
70
500
1,2
RTU -R03
ROOF
OPEN OFFICE
TRANE YCC030
1000
170
0.40
82
66
95
78.0
63.0
55.0
30
-
-
40
32
-
-
20
208/3
-
-
1,2
RTU -R04
ROOF
OPEN OFFICE
TRANE YCD060
2000
495
0.50
82
66
95
78:0
63.0
55.0
60
-
-
90
73
-
-
16
460/3-
-
1 2
RTU -R05
ROOF
OPEN OFFICE
GCS16-060
2000
130
0.50
82
66
95
78.0
63.0
55.0
59
43
1
75
60
0.50
10/8.9
16
460/3
82
530
1,2
GENERAL: ALL TRADES TO CONFIRM EQUIPMENT REQUIREMENTS (ELECTRICAL, WEIGHT, SIZE, ETC ..) WITH APPROVED SUBMITTALS PRIOR TO INSTALLATION; FIELD COORDINATE FINAL LOCATION & INSTALL PER MANUFACTURERS REQUIREMENTS
REMARKS:
1 EXISTING UNIT
2 REBALANCE AIRFLOW AS SHOWN ON PLANS
MODULAR DIFFUSER SCHEDULE LAST UPDATED: 11/28/17
UNIT
TAG
BASIS OF
DESIGN
TYPE
NECK SIZE
IN DIA
MAX
CFM
CORE
SIZE
FACE
SIZE
NC
MOUNTING
MATERIAL
REMARKS
DT1
SHOEMAKER 700MA
MODULAR
6
100
6 X 6
24 X 24
20
T -BAR
STEEL
1,2,3,4,5
DT2
SHOEMAKER 700MA
MODULAR
8
210
8 X 8
24 X 24
20
T -BAR
STEEL
1,2,3,4,5
DT3
SHOEMAKER 700MA
MODULAR
10
350
10 X 10
24 X 24
25
T -BAR
STEEL
1,2,3,4,5
DT4
SHOEMAKER 700MA
MODULAR
12
500
12 X 12
24 X 24
25
T -BAR
STEEL
1,2,3,4,5
ALUMINUM
1, 2, 3/4, 5
R7
SHOEMAKER 600T
1,800
20
T -BAR
24 x 24
ALUMINUM
1, 2, 3/4, 5
GENERAL ALL TRADES TO CONFIRM EQUIPMENT REQUIREMENTS (ELECTRICAL, WEIGHT, SIZE, ETC...) WITH APPROVED SUBMITTALS
PRIOR TO INSTALLATION; FIELD COORDINATE FINAL LOCATION &INSTALL PER MANUFACTURERS REQUIREMENTS
1 RUN OUT SIZE SAME SIZE AS DIFFUSER NECK SIZE, U.N.O. ON DWGS.
2 ALL DIFFUSERS TO HAVE SIDE INLET SHEET METAL CAN PLENUM IF < 1.5 DIA STRAIGHT FLEX AVAILABLE FOR TOP INLET
3 ECCO MFG DIFFUSER CAN TO HAVE PERFORATED INTERIOR PLATE (AND 1" SOUNDLINING IF SPACE <_ NC -30 OR SAT < 55°F)
4 STANDARD WHITE POWDER COAT
TRANSFER / RETURN 1 EXHAUST AIR GRILLES
LAST UPDATED: 11/28/2017
UNIT
TAG
BASIS OF
DESIGN
MAX
CFM
NECK SIZE
IN DIA
MOUNTING
FACE
SIZE
MATERIAL
REMARKS
R1
SHOEMAKER 600T
150
8
T -BAR
24 x 12
ALUMINUM
1, 2, 3/4, 5
R2
SHOEMAKER 600T
300
10
T -BAR
24 x 12
ALUMINUM
1, 2, 3/4, 5
R3
SHOEMAKER 600T
500
12
T -BAR
24 x 12
ALUMINUM
1, 2, 3/4, 5
R4
SHOEMAKER 600T
750
14
T -BAR
24 x 24
ALUMINUM
1, 2, 3/4, 5
R5
SHOEMAKER 600T
1,000
16
T -BAR
24 x 24
ALUMINUM
1, 2, 3/4, 5
R6
SHOEMAKER 600T
1,400
18
T -BAR
24 x 24
ALUMINUM
1, 2, 3/4, 5
R7
SHOEMAKER 600T
1,800
20
T -BAR
24 x 24
ALUMINUM
1, 2, 3/4, 5
GENERAL ALL TRADES TO CONFIRM EQUIPMENT REQUIREMENTS (ELECTRICAL, WEIGHT, SIZE, ETC...) WITH APPROVED SUBMITTALS
PRIOR TO INSTALLATION; FIELD COORDINATE FINAL LOCATION &INSTALL PER MANUFACTURERS REQUIREMENTS
1 RUNOUT SAME AS DWG NECK SIZE U.N.O. ON DWG
2 T -BAR LAY -IN
3 PROVIDE DUCTBOARD PLENUM
4 PROVIDE SHEETMETAL PLENUM
5 STANDARD SOFT WHITE FINISH
Mr/ IP
RECEIVED
CITY OF TUKWILA
DEC 04 2017
PERMIT CENTER
ISSUE FOR PERMIT
Hermanson
Building Today, Defining Tomorrow
Hermanson Company LLP
1221 2nd Avenue North
Kent, Washington 98032
Tel: (206) 575-9700
Fax: (206) 575-9800
www.hermanson.com
Contractor Reg #: HERMACL005BJ
CATALYST
WORKPLACE
ACTIVATION TI
10848 E. MARGINAL WAY S.
TUKWILA, WA
Revisions
12/01/17 TMP ISSUE FOR PERMIT
No. Date By Description
Design
Design Team
TMP
Drawn
FVP
Checked DTN
Pre—Construction Number 11-17-11513
Construction Number
Issue Date 12/01/17
SCHEDULE SHEET
- HVAC
REVIEWED FOR
CODE COMPLIANCE
APPROVED
City of Tukwila
BUILDING DIVISION
M0 .01
23"X23"RA UP
19"X21"SA UP
12"0 r':._ 10 0
UP TO
RTU -R01....
Hermanson Company LLP
1221 2nd Avenue North
Kent, Washington 98032
Tel: (206) 575-9700
Fax: (206) 575-9800
www.hermanson.com
Contractor Reg #: HERMACLOO5BJ
CATALYST
WORKPLACE
ACTIVATION TI
10848 E. MARGINAL WAY S.
TUKWILA, WA
Revisions
12/01/17 TMP ISSUE FOR PERMIT
No. Date By Description
Design
Design Team
TMP
Drawn FVP
23"X23"RA UP
19"X21"SA UP
Checked DTN
Pre -Construction Number 11-17-11513
Construction Number
L-19 L-19
Issue Date 12/01/17
1►I►i L►
•
UP TO
RTU -R05
PARTIAL
1ST FLOOR DEMO PLAN
- HVAC
RECEIVED
CITY OF. TUKWILA
DEC 0 4 2017
PERMIT CE
EVIE D FOR
E COIF, PLIANC
APPR VED
PARTIAL 1ST FLOOR DEMO PLAN - HVAC
SCALE: 1/8" = 1'-0"
DEC 0 2011
ISSUE FOR PERMIT
City ofukwila
BUILDINGIVIOIO!'1
FURNITURE STORAGE WAREHOUSE
0
RELOCATED---
EXIST T—STAT
RELOCATED
DIST T -STAT
WALL DISPLAY PANEL
DT1-100
UP TO '
RTU -R01
Hermanson Company LLP
1221 2nd Avenue North
Kent, Washington 98032
Tel: (206) 575-9700
Fax: (206) 575-9800
www.hermanson.com
Contractor Reg #: HERMACLOO5BJ
1600 CFM
RAL. OPEI1 OFFICE
280 CFM
;280 CFM
;280 CFM 280 CFM:
DT2-150
CATALYST
WORKPLACE
ACTIVATION TI
16"X18"
R2-300
10848 E. MARGINAL WAY S.
TUKWILA, WA
UP TO
RTU—R02
•
DT3-235
14"X14".
..........._..._.
EXISTING WATER FOUNTAIN /
BOTTLE FILLING STATION
DT2-155
DT2-155
Revisions
DT2-155
L/COP ` RK/I_
VCT -1
150 CFM!
8"0
700 CFM
GEN FA
1155 CFM
8"0
(E)
DT3-235
OPEN OFFICE/
:MODULAR:. Tta.TEE:E::W.FLt.
1600 CFM
DT1-50
DT1-50
6"0
12/01/17 TMP ISSUE FOR PERMIT
No. Date By Description
R5-1000
16"0
DT2-155
8"0
DT2-155
235 CFM
Design
Design Team
TMP
23"X23"RA UP
19"X21 "SA UP
Drawn FVP
Checked DTN
Pre—Construction Number 11-17-11513
DT2-155'
8"0
DT2-155
8"0
R5-1000
16"0(TYP 2)
Construction Number
20X2 /.: •
22'X22"RA UP
Issue Date 12/01/17
285 CFM
DT3-285
10"0
DT3-285'
10"0
PARTIAL
1ST FLOOR PLAN
- HVAC
285 CFM 285 CFM
(E) CLOSE
H
CONSTRUCTION NOTE:
Q1 MOUNT THERMOSTAT ON INSULATED SUB—BASE.
PARTIAL 1ST FLOOR PLAN - HVAC
SCALE: 1/4" = 1'-0"
RECEIVED
CITY OF KWILA
DEC 0 017
PERMIT iNTER
REVIEWI'D FOR
CODE COW PLIANCE
APPRC VED
• ISSUE FOR PERMIT DEC of 2017
City of Tukwila
BUILDING DIVISION