HomeMy WebLinkAboutPermit M17-0192 - JARED'S JEWELERS - ROOFTOP UNITSJARED'S JEWELERS
16840 SOUTHCENTER PKWY
EXPIRED 07/23/18
M17-0192
Parcel No:
Address:
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670
Inspection Request Line: 206-438-9350
Web site: htto://www.TukwilaWA.eov
MECHANICAL PERMIT
2623049129
16840 SOUTHCENTER PKWY
Project Name: JARED'S JEWELERS
Permit Number:
Issue Date:
Permit Expires On:
M 17-0192
1/24/2018
7/23/2018
Owner:
Name:
Address:
Contact Person:
Name:
Address:
Contractor:
Name:
Address:
License No:
Lender:
Name:
Address:
PARKWAY SQUARE L L C
P 0 BOX 5003 , BELLEVUE, WA, 98009
JESSE SIMENSON
PO BOX 29116 , BELLINGHAM, WA,
98228
NORTHSOUND REFRIGERATION INC
PO BOX 29116 , BELLINGHAM, WA,
98228
NORTHRI898CG
Phone: (360) 380-1381
Phone: (360) 380-1381
Expiration Date: 2/7/2019
DESCRIPTION OF WORK:
REMOVAL OF 3 GAS/ELECT ROOFTOP UNITS AND REPJLACE W/NEW UNITS OF SAME SIZE (CAPACITY) W/CURB
ADPT.
Valuation of Work: $10,100.00
Type of Work:
Fuel type:
Fees Collected: $344.08
Electrical Service Provided by: PUGET SOUND ENERGY
Water District: TUKWILA
Sewer District: TUKWILA
Current Codes adopted by the City of Tukwila:
International Building Code Edition:
International Residential Code Edition:
International Mechanical Code Edition:
Uniform Plumbing Code Edition:
International Fuel Gas Code:
2015
2015
2015
2015
2015
National Electrical Code:
WA Cities Electrical Code:
WAC 296-466:
WA State Energy Code:
2017
2017
2017
2015
Permit Center Authorized Signature:
Date:
117q,
I hearby certify that I have read and examined this permit and know the same to be true and correct. All
provisions of law and ordinances governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other
state or local laws regulating construction or the performance of work. I am authorized to sign and obtain this
development perm nd agree to the conditions attached to this permit.
Signature:
Print Name:
ease 1-t
Date: /- 2L1C/
4
This permit shall become null and void if the work is not commenced within 180 days for the date of issuance, or if
the work is suspended or abandoned for a period of 180 days from the last inspection.
PERMIT CONDITIONS:
1: The attached set of mechanical plans have been reviewed by The Tukwila Fire Marshals Office and are
acceptable with the following concerns:
2: H.V.A.C. units rated at greater than 2,000 cfm require auto -shutdown devices. These devices shall be
separately zoned in the alarm panel and local U.L. central station supervision is required. (City Ordinance
#2437)
3: H.V.A.C. systems supplying air in excess of 2,000 cubic feet per minute to enclosed spaces within buildings
shall be equipped with an automatic shutoff. Automatic shutoff shall be accomplished by interrupting the
power source of the air -moving equipment upon detection of smoke in the main return -air duct served by
such equipment. Smoke detectors shall be labeled by an approved agency for air -duct installation and shall
be installed in accordance with the manufacturer's installation instructions. (IMC 606.1, 606.2.1)
4: Remote indicator lights are required on all above ceiling smoke detectors. (City.Ordinance #2437)
5: Duct detectors shall send a supervisory signal only upon activation. (City Ordinance #2437)
6: All new fire alarm systems or modifications to existing systems shall have the written approval of The
Tukwila Fire Prevention Bureau. No work shall commence until a fire department permit has been
obtained. (City Ordinance #2437) (IFC 901.2)
7: An electrical permit from the City of Tukwila Building Department Permit Center (206-431-3670) is required
for this project.
8: Contact The Tukwila Fire Prevention Bureau to witness all required inspections and tests. (City Ordinances
#2436 and #2437)
9: Any overlooked hazardous condition and/or violation of the adopted Fire or Building Codes does not imply
approval of such condition or violation.
10: These plans were reviewed by Inspector 511. If you have any questions, please call Tukwila Fire Prevention
Bureau at (206)575-4407.
11: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila
Permit Center (206/431-3670).
12: Work shall be installed in accordance with the approved construction documents, and any changes made
during construction that are not in accordance with the approved construction documents shall be
resubmitted for approval.
13: RTU curb installation must be inspected before RTU is set on it.
PERMIT INSPECTIONS REQUIRED
Permit Inspection Line: (206) 438-9350
1400 FIRE FINAL
1800 MECHANICAL FINAL
0701 ROUGH -IN MECHANICAL
CITY OF TUKWILA
Community Development Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http://www.TukwilaWA.gov
Mechanical Permit No. M_ 1-1 -0 %Y 2
Project No.
Date Application Accepted: 1 . (g 1/
Date Application Expires: U (HI
(For office use only)
MECHANICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
**please print**
SITE .LOCATION
Site Address: 'bete 5:itt r/CC J7tZ PKWY
Tenant Name: ^,..,I14e. MENU Ls( "2.S
King Co Assessor's Tax No.: Z.230g9 ZR
Floor:
Suite Number:
PROPERTY OWNER
Name: �Agg..wQ-f Sri) UAg.JG L.L.C.
Address:
City: State: Zip:
CONTACT PERSON — person receiving all project
communication
Company Name gef.iziCa,6. n ■,�
Wv
Address: Po. (.li! y 2q 116
Name:. t��se. si t''IEtl
Phone: 2 ,� .300' 150) Fax: _ `�`"`''II
86
C(
oi,
Tukwila Business License No.: sus _63-7L
Address: P 0. sox 2 1 L6
State:
City: Uelf_ m 1+41,1
�
Zip:902 h�
Phone: J13.. J Fax:360
it
3_
Ib
Email.10erni.i
ri1
New Tenant: ❑ Yes No
MECHANICAL CONTRACTOR .INFORMATION
Company Name gef.iziCa,6. n ■,�
Wv
Address: Po. (.li! y 2q 116
City: Damm6 NRM State: IA IA. zip$32
Phone: 2 ,� .300' 150) Fax: _ `�`"`''II
86
Contr Reg No.:NQQni Q= $18cticp Date: 211,• it,
Tukwila Business License No.: sus _63-7L
•wM
Valuation of project (contractor's bid price): $
Describe the scope of work in detail:
gEtAov 4u. or 3 Cr A s / eLL-cc-•'r" RDOF TDP L11414-5 A -.t p - a -i LACE
th M}5 op sprmsS I2E.`(4 p4Sr-171) w 1 Gum
SOD
Use:
Fuel Type:
Residential:
Commercial:
New
New
Electric ,f
Gas
Replacement
Replacement
Other:
H:1Applications\Forms-Applications On Line\2016 Applications\ Mechanical Permit Application Revised 1-4-16.docx
Revised: January 2016
bh
Page 1 of 2
Indicate type of mechanical work being installed and the quantity below:
Unit Type
Qty
Furnace <100k btu
Residential, Nighttime
Furnace >100k btu
Industrial
Floor furnace
55 dB(A)
Suspended/wall/floor
mounted heater
57 dB(A)
Appliance vent
Commercial
Repair or addition to
heat/refrig/cooling
system
47 dB(A)
Air handling unit
<10,000 cfm
65 dB(A)
Unit Type
Qty
Air handling unit
Residential, Nighttime
>10,000 cfm
Industrial
Evaporator cooler
55 dB(A)
Ventilation fan
connected to single duct
57 dB(A)
Ventilation system
Commercial
Hood and duct
47 dB(A)
Incinerator — domestic
65 dB(A)
Incinerator —
comm/industrial
-60 dB(A)
Unit Type
Qty
Fire damper
Residential, Nighttime
Diffuser
Industrial
Thermostat
55 dB(A)
Wood/gas stove
57 dB(A)
Emergency generator
Commercial
Other mechanical
equipment
47 dB(A)
60 dB(A)
65 dB(A)
Boiler/Compressor
Qty
0-3 hp/100,000 btu
3-15 hp/500,000 btu
15-30 hp/1,000,000 btu
30-50 hp/1,750,000 btu
50+ hp/1,750,000 btu
Noise:
Mechanical units need to be in compliance with the Tukwila Noise Code. Maximum permissible sound levels are based on from where the sound is
created and where the sound is heard. Additionally, if sound can be heard from within a house at night in a residential zone it may not be allowed.
For more details, see TMC 8.22
District of Sound
Producing Source
District of Receiving Property
Residential, Daytime*
Residential, Nighttime
Commercial
Industrial
Residential
55 dB(A)
45 dB(A)
57 dB(A)
60 dB(A)
Commercial
57 dB(A)
47 dB(A)
60 dB(A)
65 dB(A)
Industrial
-60 dB(A)
50 dB(A)
65 dB(A)
70 dB(A)
*Daytim
A few sounds are exempt from the noise code, including:
Waming devices;
• Construction and property maintenance during the daytime hours (lam -1 Opm);
• Testing of backup generators during the day.
PERMIT APPLICATION NOTES -
Value of construction — in all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the pemit center to comply with current fee schedules.
Expiration of plan review — applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The building official may grant one extension of time for additional periods not to exceed 90 days each. The extension shall be requested in writing
and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OW ER OR
Signature:
HORIZED AGENT:
Print Name:
Mailing Address: P- 0 •43D.X. 1 Ib
Date: 12 - d7' Z617
nI) Day Telephone �7� —
tEw k1
City
H:\Applications\Forms-Applications On Line\2016 Applications\Mechanical Permit Application Revised I-4-16.docx
Revised: January 2016
bh
u, 9Zz
State Zip
Page 2 of 2
Cash Register Receipt
City of Tukwila
DESCRIPTIONS ACCOUNT QUANTITY
PermitTRAK
PAID
$344.08
M17-0192 Address: 16840 SOUTHCENTER PKWY •Apn: 2623049129
$344.08
MECHANICAL
$330.85
PERMIT ISSUANCE BASE FEE
R000.322.100.00.00
0.00
$33.15
PERMIT FEE
R000.322.100.00.00
0.00
$231.53
PLAN CHECK FEE
R000.322.102.00.00
0.00
$66.17
TECHNOLOGY FEE
$13.23
TECHNOLOGY FEE
TOTAL FEES PAID BY RECEIPT: R12981
R000.322.900.04.00 0.00
,
•
$13.23
$344.08
Date Paid: Friday, December 08, 2017
Paid By: NORTHSOUND REFRIGERATION INC
Pay Method: CHECK 19671
Printed: Friday, December 08, 2017 9:07 AM 1 of 1
CR(SYSTEMS
i ---REVISIONS
No changes shall he made to the scope
of work r ritho ii prior approval of
I Tukwila Building Division.
NOTE: Revisions will require a new plan submittal
and may include additional plan review fees.
FILE COPY
PermIt No. M (1-- 0 (9X
Plan rev e.w t °cal is subject to errors and omissions.
Approval of ccnsfruction documents does not authorize
the violation of any adopted code or ordinance. Receipt
of approved Field Co, d conditions is acknowledged:
B
Date:
City of Tukwila
BUILDING DIVISION
'SEPARATE PERMIT
1::::CILJIF D FOR:
1Mechanical
I tectrical
L lI mbing
IIW&s Piping
ICity of Tukwila
SI-.D(NG DIVISION
REVIEWED FOR
CODE COMPLIANCE
APPROVED
JAN 17 2010
WO
I city of Tukwila
BUILDING DIVISION
VL1i 92
WIINF
General Data
Table 10. General da
— 6 to 7.5 to — high efficiency
C01RECTION
LTR#�
M1.7%- 0192,
CWILA
018
Putu°' IVTER
Single Compressor
T/YHC072E/F3,4,W
6 Tons
Dual Compressor
T/YHC074F3,4
7.5 Tons
T/YHC092F3,4,
.Cooling Performance(!)
Gross Cooling Capacity
72,000
73,000
EER(b)
12.6
13.1
Nominal cfm/AHRI Rated cin
2,400/2,100
2,400/2,100
.. ,
AHRI Net Cooling Capacity
68,000
71,000
89,000
IEER(c)
14.5
15.5(d)
14,5(e)
System Power (kW)
5.37
5.42
7.06
Compressor 4 - s * r.,,
', w"
,
Number/Type
1/Scroll
2/Scroll
2/Scroll
Sound r , 1
_ " • •
_
Outdoor Sound Rating (dB)\11
89
89
88
Type
Microchannel
Microchannel
Microchannel
Configuration
Full Face
Face -Split
Face -Split
Tube Size (in.)
0.71
1
1
Face Area (sq. ft.)
20.77
20.77
20.77
Rows/FPI (Fins per inch)
1/23
1/20
1/20
Indoor Coif .. 49
...
Type
Lanced
Lanced
Lanced
Configuration
Full Face
Intertwined
Intertwined
Tube Size (in.)
0.3125
0.3125
0.3125
Face Area (sq. ft.)
12.36
12.36
12.36
Rows/FPI(Fins per inch)
4/16
4/16
4/16
Refrigerant Control
Thermal Expansion Valve
Thermal Expansion Valve
Thermal Expansion Valve
Drain Connection No./Size in.)
13 NPT
13A NPT
13/4 NPT
Outdoor Pari : —
;.
i -
=
4...:•:.%''''
°
Type
Propeller
Propeller
Propeller
No. Used/Diameter (in.)
1/26
1/26
1/26
Drive Type/No. Speeds
Direct/1
Direct/1
Direct/1
CFM
5900
5750
6800
Motor HP
0.7
0.7
0.75
Motor RPM
1100
1100
1100
1
Type
FC Centrifugal
BC Plenum
BC Plenum
No. Used/Diameter(in.)/W dth (In.)
1/15x15
1/21.0315x6.14
1/21.0315x6.14
Drive Type/No. Speeds(g)/R?M
Belt/Variable/1,750
DirectNariable
Direct/VaHable
Motor HP (Standard/Oversi ,ed)
1.0/2.0
-
2.75/—
-
2.75/—
Motor Frame Size
(Standard/Oversized)
(Standard/Oversized)
56/56
—/—
®�`/f`p�r� �/�a
E FOR
h '["',; •v: _{•
() 4
A z a , . -
« ,
� ,F i � is ii+ .i f•I:
44
4,
e�::•
J 5
*
Type Furnished
Throwaway
Pp,,
kiVUlarl LU'1IV�fr:.
a _
Throwaway
Throwaway
Number Size Recommended
(4) 20x25x2
�f
1 tl E b
(4) 20x25x2
Option f'�Iot Gas ReheateCail r
, ,
-
t'
• :
i
y
Tube Size (in.) OD
-
�-'-s--it, 7 i
JAN -1 Gui8 rl
_• 3.
0.3125
Face Area (sq. ft.)
—
—
8.652
Rows/FPI(Fins per inch)
—•
—
1/16
RefrigeraitChar P).'r r
,•
p t ,
--w
_
7.7
vir g 1 avv c.
ECMStandard
Optional Hot Gas Reheat Cd
—
.l
�V i LD1i G DI:ViS
,tC.4
i d . OF TU
Heating Pestonnance"jGss/
EfeCtric OnCy}14,
S ♦
.a r.j, . ,
Heating input _t
t -,;a =
C01RECTION
LTR#�
M1.7%- 0192,
CWILA
018
Putu°' IVTER
t -a1,ct2_
"RANF
General Data
Table 11. General d
— 8.5 to 10 tons — high efficiency
CORRE TION
LTR#
FOR
IANCE
ED
018
�CEIVED
)F TUKWILA
N 12 2018
IIT CENTER
RT-PRCO23AN-EN
8.5 Tons
10 Tons
T/YMC102F3,4,W
T/YHC120F3,4,W
COolino Periotrhance(a) :
•
Gross Cooling Capacity
104,000
. e i •
EER(b)
i = 12.5
Y=12.4
•
Nominal cfm/AHRI Rated cPn
3,400/2,720
.: ,: e 0
AHRI Net Cooling Capacity
99,000
113,000
IEER(c)
T= 14.7(4)
YHC102FW=14.5
AER = 14.1
SZVAV, JEER = 15.2
System Power (kW)
7.92
9.11
Compressor °
:} ''; ,.
Number/Type
2/Scroll
2/Scroll
Sound .
7 f.
Outdoor Sound Rating (dB) el
89
87
Outdoor Coil
Type
Microchannel
Microchannel
Configuration
Face Split
Face Split
Tube Size (in.)
1
1
Face Area (sq. ft.)
20.77
26.77
Rows/FPI (Fins per inch)
1/20
1/23
iiidoar-Coit, -�
'
.
_
a-'
Type
• Lanced
Lanced
Configuration
Intertwined
Intertwined
Tube Size (in.)
0.3125
0.3125
Face Area (sq. ft.)
12.36
16.65
Rows/FPI (Fins per inch)
5/16
4/16
Refrigerant Control
Thermal Expansion Valve
Thermal Expansion Valve
Drain Connection No./Size in.)
13,4 NPT
13,4 NPT
Os•tdoorFan, R
-e -
7 - .,. .
Type
Propeller
Propeller
No. Used/Diameter (in.)
1/26
1/30
Drive Type/No. Speeds
Direct/1
Direct/1
CFM
6,800
7,540 ,
Motor HP
0.75
0.75
Motor RPM
1,100
,i00RFVIF%jvFn
door Fare ; }
Ihtr
_, ,.
(r
s,... C
Type (Standard)
BC Plenum
B 'P n n G~� `"`
No. Used/Diameter (in. )/Wkth (in.)
1/21.0315x6.14
1/21.Ip315x6.1APPRCV
Drive Type/No. Speeds/RPh to
Direct/Variable
Direiariabier a
Motor HP
2.75/—
(q� _
2.75/— JAN 1
Motor Frame Size
—/—
Filters(a) r :1 «
r _
a
.
Type Furnished
Throwaway
Th wawa�3..
Number Size Recommendei
(4) 20x25x2
(4) Ox2Sx10"4r �� i fY
(2) RPM nl nic; nil
conal Hot 6as Reh(eatiCot1-
g
..
� *- .
�
,-��
" -=•"•in
Tube Size (In.) OD
0.3125
0.3125
Face Area (sq. ft.)
8.652
15.23
Rows/FPI (Fins per Inch)
1/16
1/16 TV
Refngerant-Charge(ibs 3rR-. -
410A)(h1• -
r
. , f t ,.. , t
a
q GI rf -Io
; } c- >:.
Standard
6.3/4.9
7.7/5.2
Optional Hot Gas Reheat Ca I
6.6/4.7
8.6/5.2 JA
Heating'Perrormance (G is/
tlectric onti)r), . ..
;. ;
- t'
. t
CORRE TION
LTR#
FOR
IANCE
ED
018
�CEIVED
)F TUKWILA
N 12 2018
IIT CENTER
RT-PRCO23AN-EN
AAar S.Paier
1d.
Jared #415 Replacement
Product Data - 3-10 Ton R410A PKGD Unitary Gas/Electric
All Units
DX cooling, gas heat
—.High efficiency
Convertible configuration
10 Ton
Major design sequence
208-230/60/3
Microprocessor controls 3ph
Medium gas heat 3ph
Economizer Dry Bulb 0-100%
Standard condenser coil w/hail guard
Through the base electrical 3ph
Circuit breaker
Unpowered convenience outlet (3ph units)
tsp.Return air smoke detector 3ph
Power exhaust (Fld)
CO2 wall mounted, field sensor kit (Fld)
Year 6-10 heat exchanger warranty
June 26, 2017
Rooftop
REVIEWED FOR
ODE COMPLIANCE
APPROVED
JAN 17 2018
City of Tukwila
> t Ill nINt � 4 °4h`I
RECEIVED
CITY OF TUKWILA
DEC 0°8 2017
PERMIT CENTER
0161(1
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 4 of 18
Others
Jared #415 Replacement
Mechanical Specifications - 3-10 Ton R410A PKGD Unitary Gas/Electric Rooftop
Item: Al - A3 Qty: 3 Tag(s): R-1, R-2, R-3
June 26, 2017
General
The units shall be convertible airflow. The operating range shall be between 115°F and 0°F in cooling as standard from
the factory for units with microprocessor controls. Operating range for units with electromechanical controls shall be
between 115°F and 40°F. Cooling performance shall be rated in accordance with ARI testing procedures. All units shall
be factory assembled, internally wired, fully charged with R -410A, and 100 percent run tested to check cooling
operation, fan and blower rotation, and control sequence before leaving the factory. Wiring internal to the unit shall be
colored and numbered for simplified identification. Units shall be cULus listed and labeled, classified in accordance for
Central Cooling Air Conditioners.
Casing
Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall be cleaned,
phosphatized, and finished with a weather -resistant baked enamel finish. Units surface shall be tested 672 hours in a
salt spray test in compliance with ASTM 8117. Cabinet construction shall allow for all maintenance on one side of the
unit. Service panels shall have lifting handles and be removed and reinstalled by removing two fasteners while providing
a water and air tight seal. All exposed vertical panels and top covers in the indoor air section shall be insulated with a
cleanable foil -faced, fire -retardant permanent, odorless glass fiber material. The base of the unit shall be insulated with
1/8 inch, foil -faced, closed -cell insulation. All insulation edges shall be either captured or sealed. The unit's base pan
shall have no penetrations within the perimeter of the curb other than the raised 1 1/8 inch high downflow supply/return
openings to provide an added water integrity precaution, if the condensate drain backs up. The base of the unit shall
have provisions for forklift and crane lifting, with forklift capabilities on three sides of the unit.
Unit Top
The top cover shall be one piece construction or, where seams exist, it shall be double -hemmed and gasket -sealed.
The ribbed top adds extra strength and enhances water removal from unit top.
Filters
Throwaway filters shall be standard on all units. Optional 2 -inch MERV 8 and MERV 13 filters shall also be available.
Compressors
All units shall have direct -drive, hermetic, scroll type compressors with centrifugal type oil pumps. Motor shall be suction
gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of unit nameplate voltage. Internal
overloads shall be provided with the scroll compressors.
Dual compressors are outstanding for humidity control, light load cooling conditions and system back-up applications.
Dual compressors are available on 71/2-10 ton models and allow for efficient cooling utilizing 3 -stages of compressor
operation for all high efficiency models.
Notes:
Crankcase heaters are optional on YSC (036, 048, 060, 072, 090, 102, 120); standard on YHC (036, 048, 060, 072, 092,
102, 120).
Indoor Fan
The following units shall be equipped with a direct drive plenum fan design (T/YSC120F,T/YHC074F,
T/YHC092F,T/YHC102F, 120F). Plenum fan design shall include a backward -curved fan wheel along with an external
rotor direct drive variable speed indoor motor. All plenum fan designs will have a variable speed adjustment
potentiometer located in the control box.
3 to 5 ton units (high efficiency 3-phase with optional motor) are belt driven, FC centrifugal fans with adjustable motor
sheaves. 3 to 5 ton units (standard and high efficiency 3-phase) have multispeed, direct drive motors. All 6 to 81/2 ton
units (standard efficiency) shall have belt drive motors with an adjustable idler -arm assembly for quick -adjustment to fan
belts and motor sheaves. All motors shall be thermally protected. All 10 tons, 6 ton (074), 71 to 81 (high efficiency)
units have variable speed direct drive motors. All indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT).
Outdoor Fans
The outdoor fan shall be direct -drive, statically and dynamically balanced, draw -through in the vertical discharge
position. The fan motor shall be permanently lubricated and shall have built-in thermal overload protection.
Evaporator and Condenser Coils
Internally finned, 5/16" copper tubes mechanically bonded to a configured aluminum plate fin shall be standard.
Evaporator coils are standard for all 3 to 10 ton standard efficiency models. Microchannel condenser coils are standard
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 5 of 18
Others
Jared #415 Replacement June 26, 2017
for all 3 to 10 ton standard efficiency models and 4, 5, 6, 7.5, 8.5 ton high efficiency models. The microchannel type
condenser coil is not offered on the 4 and 5 ton dehumidification model. Due to flat streamlined tubes with small ports,
and metallurgical tube -to -fin bond, microchannel coil has better heat transfer performance. Microchannel condenser coil
can reduce system refrigerant charge by up to 50% because of smaller internal volume, which leads to better
compressor reliability. Compact all -aluminum microchannel coils also help to reduce the unit weight. These all
aluminum coils are recyclable. Galvanic corrosion is also minimized due to all aluminum construction. Strong aluminum
brazed structure provides better fin protection. In addition, flat streamlined tubes also make microchannel coils more
dust resistant and easier to clean. Coils shall be leak tested at the factory to ensure the pressure integrity. The
evaporator coil and condenser coil shall be leak tested to 600 psig. The assembled unit shall be leak tested to 465 psig.
The condenser coil shall have a patent pending 1+1+1 hybrid coil designed with slight gaps for ease of cleaning. A
plastic, dual -sloped, removable and reversible condensate drain pan with through -the -base condensate drain is
standard.
Tool -less Hail Guards
Tool -less, hail protection quality coil guards are available for condenser coil protection.
Controls
Unit shall be completely factory -wired with necessary controls and contactor pressure lugs or terminal block for power
wiring. Unit shall provide an external location for mounting a fused disconnect device. A choice of microprocessor or
electromechanical controls shall be available. Microprocessor controls provide for all 24V control functions. The resident
control algorithms shall make all heating, cooling, and/or ventilating decisions in response to electronic signals from
sensors measuring indoor and outdoor temperatures. The control algorithm maintains accurate temperature control,
minimizes drift from set point, and provides better building comfort. A centralized microprocessor shall provide anti -short
cycle timing and time delay between compressors to provide a higher level of machine protection. 24 -volt
electromechanical control circuit shall include control transformer and contactor
High Pressure Control
All units include High Pressure Cutout as standard.
Phase monitor
Phase monitor shall provide 100% protection for motors and compressors against problems caused by phase loss,
phase imbalance, and phase reversal. Phase monitor is equipped with an LED that provides an ON or FAULT indicator.
There are no field adjustments. The module will automatically reset from a fault condition.
Refrigerant Circuits
Each refrigerant circuit offer thermal expansion valve as standard. Service pressure ports, and refrigerant line filter
driers are factory -installed as standard. An area shall be provided for replacement suction line driers.
Gas Heating Section
The heating section shall have a progressive tubular heat exchanger design using stainless steel burners
and corrosion resistant steel throughout. An induced draft combustion blower shall be used to pull the combustion
products through the firing tubes. The heater shall use a direct spark ignition (DSI) system. On initial call for heat, the
combustion blower shall purge the heat exchanger for 20 seconds before ignition After three unsuccessful ignition
attempts, the entire heating system shall be locked out until manually reset at the thermostat/zone sensor. Units shall be
suitable for use with natural gas or propane (field -installed kit) and also comply with the California requirement for low
NOx emissions (Gas/Electric Only).
Powered or Unpowered Convenience Outlet
This is a GFCI, 120v/15amp, 2 plug, convenience outlet, either powered or unpowered. When the convenience outlet is
powered, a service receptacle disconnect will be available. The convenience outlet is powered from the line side of the
disconnect or circuit breaker, and therefore will not be affected by the position of the disconnect or circuit breaker. This
option can only be ordered when the Through the Base Electrical with either the Disconnect Switch or Circuit Breaker
option is ordered.
Plenum Fan
The following unit shall be equipped with a direct drive plenum fan design (all 10 tons and 7.5-8.5 ton high efficiency
units). Plenum fan design shall include a backward -curved fan wheel along with an external rotor direct drive variable
speed indoor motor. All plenum fan designs will have a variable speed adjustment potentiometer located in the control
box.
Economizer
This accessory shall be available with or without barometric relief. The assembly includes fully modulating 0-100
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 6 of 18
Others
Jared #415 Replacement June 26, 2017
percent motor and dampers, minimum position setting, preset linkage, wiring harness with plug, spring return actuator
and fixed dry bulb control. The barometric relief shall provide a pressure operated damper that shall be gravity closing
and shall prohibit entrance of outside air during the equipment off cycle. Optional solid state or differential enthalpy
control shall be available for either factory or field installation. The economizer arrives in the shipping position and shall
be moved to the operating position by the installing contractor.
Through the Base Electrical Access
An electrical service entrance shall be provided allowing electrical access for both control and main power connections
inside the curb and through the base of the unit. Option will allow for field installation of liquid -tight conduit and an
external field -installed disconnect switch.
Through the Base Electrical with Circuit Breaker
This option is a thermal magnetic, molded case, HACR Circuit Breaker with provisions for through the base electrical
connections. The circuit breaker will be installed in a water tight enclosure in the unit with access through a swinging
door. Wiring will be provided from the switch to the unit high voltage terminal block. The circuit breaker will provide
overcurrent protection, be sized per NEC and UL guidelines, and be agency recognized by UL/CSA.
Supply and/or Return Air Smoke Detector
Smoke detector shall be factory installed photoelectric smoke detector mounted in the return air section (with or without
the economizer or motorized damper option), AND/OR in the supply air fan compartment. The detector will be wired for
continuous power whenever the unit is energized. Upon detection of smoke, the detector will shut down all unit
operations. Local codes may dictate the location of detectors. Note: Due to the shipping position of the economizer or
motorized damper, the return air smoke detector will not be completely factory installed. The wiring harness for the
detector will be routed and tied off in the fan compartment for shipping. The smoke detector and barometric damper
hood will also be installed in a shipping position in the fan compartment.
Accessory - Powered Exhaust
The powered exhaust shall provide exhaust of return air, when using an economizer, to maintain better building
pressurization.
Accessory - CO2 Sensing
The CO2 sensor shall have the ability to monitor space occupancy levels within the building by measuring the parts per
million of CO2 (Carbon Dioxide) in the air. As the CO2 levels increase, the outside air damper modulates to meet the
CO2 space ventilation requirements.
Supply, Return, and Plenum Air Smoke Detector
With this option installed, if smoke is detected, all unit operation will be shut down. Reset will be manual at the unit. In
order for the supply air smoke detector or return air smoke detector to properly sense smoke in the supply air stream or
the return air stream, the air velocity entering the smoke detector unit must be between 500 - 4000 feet per minute.
Equipment covered in this manual will develop an airflow velocity that falls within these limits over the entire airflow
range specified in the evaporator fan performance table. Supply and/or Return Smoke Detectors may not be used with
the Plenum Smoke Detector.
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 7 of 18
Others
Jared #415 Replacement
Unit Dimensions - 3-10 Ton R410A PKGD Unitary Gas/Electric Rooftop
Item: Al - A3 Qty: 3 Tag(s): R-1, R-2, R-3
June 26, 2017
3/4"-14 DIA HOLE
CONDENSATE DRAIN
27 5/8"
4 3/4"
ISOMETRIC -PACKAGED COOLING
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 8 of 18
Others
Jared #415 Replacement
Unit Dimensions - 3-10 Ton R410A PKGD Unitary Gas/Electric Rooftop
Item: Al - A3 Qty: 3 Tag(s): R-1, R-2, R-3
ELECTRICAL / GENERAL DATA
June 26, 2017
'GENERAL (2)(4")
Model:
YHC120F
Oversized Motor
HEATING PERFORMANCE
HEATING - GENERAL DATA
Unit Operating Voitage:
187-253
MCA: N/A
Heating Model: 'Medium
Unit Primary Voltage:
Unit Secondary Voltage
208
MFS: N/A
Heating Input (BTU): 200,000/140,000
230
MCB: N/A
Heating Output (BTU): 160,000/112,000
Unit Hertz:60
Unit Phase:
se:
3
No. Burners: 4
No. Stages 2
EER
Standard Motor
Field Installed Oversized Motor
'Gas Inlet Pressure
MCA:
'46.1
MCA: N/A
Natural Gas (Min/Max): '4.5/14
MFS:
60.0
MFS: N/A
LP (Min/Max) 10.0/14.0
MCB:
60.0
MCB: N/A
Gas Pipe Connection Size: 3/4"
INDOOR MOTOR
Standard Motor
Oversized Motor Field Installed Oversized Motor
Number:
'1
Number: N/A Number: N/A
Horsepower:
3.8
Horsepower: N/A Horsepower: N/A
Motor Speed (RPM):
--
Motor Speed (RPM): N/A Motor Speed (RPM): N/A
Phase '
3
Phase N/A Phase N/A
Full Load Amps:
8.5 - 8.5
Full Load Amps: N/A Full Load Amps: N/A
Locked Rotor Amps:
__
Locked Rotor Amps: N/A Locked Rotor Amps: N/A
COMPRESSOR
Circuit 1 /2
OUTDOOR MOTOR
Number:
'2
Number: '1
Horsepower:
5.1/3.0
Horsepower: 0.75
Phase:
3
Motor Speed (RPM): 1100
Rated Load Amps:
19.6/10.4
Phase: 3
Locked Rotor Amps:
136.0/73.0
Full Load Amps: 2.7
Locked Rotor Amps: 9.8
POWER EXHAUST ACCESSORY 131
FILTERS
REFRIGERANT (2)
(Field Installed Power Exhaust)
Type R-410
Phase:
1
Type: Throwaway
Horsepower:
0.87
Furnished: Yes
Factory Charge
Motor Speed (RPM):
1075
Number 3 / 2
Circuit 81 7.1 Ib
Full Load Amps:
5.7
Recommended 20"x25"x2"
Circuit 82 5.0 Ib
Locked Rotor Amps:
13.6
20"x30"x2"
NOTES:
1. Maximum (HACK) Circuit Breaker sizing is for installations in the United States only.
2. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
3. Value does not include Power Exhaust Accessory.
4. Value includes oversized motor.
5. Value does not include Power Exhaust Accessory.
6. EER is rated at AHRI conditions and in accordance with DOE test procedures.
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 10 of 18
Others
Jared #415 Replacement
Accessory - 3-10 Ton R410A PKGD Unitary Gas/Electric Rooftop
Item: Al - A3 Qty: 3 Tag(s): R-1, R-2, R-3
June 26, 2017
ECONOMIZER HOOD
ECONOMIZER HOOD
16 3/4"
ECONOMIZER HOOD
ACCESSORY
6 7/8"
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 13 of 18
Others
Jared #415 Replacement
Accessory - 3-10 Ton R410A PKGD Unitary Gas/Electric Rooftop
Item: Al - A3 Qty: 3 Tag(s): R-1, R-2, R-3
June 26, 2017
POWER EXHAUST
POWER EXHAUST
ECONOMIZER HOOD
4
5 5/8"
21 5/8"
POWER EXHAUST AND HOOD
ACCESSORY
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 14 of 18
Others
Jared #415 Replacement
Accessory - 3-10 Ton R410A PKGD Unitary Gas/Electric Rooftop
Item: Al - A3 Qty: 3 Tag(s): R-1, R-2, R-3
F2 7/8"
4 11/16"
June 26, 2017
NOTES:
1. SEE ENGINEERING SPECIFICATION FOR DETAILS.
2. VERIFY ALL DIMENSION WITH INSTALLER DOCUMENTS
BEFORE INSTALLATION.
BAYCO2K001 B - WALL MOUNT CO2
ACCESSORY
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 15 of 18
Others
Jared #415 Replacement
Field Wiring - 3-10 Ton R410A PKGD Unitary Gas/Electric Rooftop
Item: Al - A3 Qty: 3 Tag(s): R-1, R-2, R-3
June 26, 2017
/
f -77
0
0
I
I
HTB1
`1t
i -
'
O
V
V
0
O
.
V
ZONE SENSOR WIRE TABLE
WIRE SIZE
MAXIMUM WIRE LENGTH
22 GAUGE
20 GAUGE
18 GAUGE
16 GAUGE
14 GAUGE
NOTE:
1. All wiring and devices shown dashed to be supplied and installed by the customer in accordance with national and local electrical codes.
2. Low voltage control wiring must not be run in conduit with power wiring.
1800"
3000"
4500"
7200"
11700"
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 16 of 18
Others
Jared #415 Replacement
Field Wiring - 3-10 Ton R410A PKGD Unitary Gas/Electric Rooftop
Item: Al - A3 Qty: 3 Tag(s): R-1, R-2, R-3
3.75
June 26, 2017
CO2 SENSOR WIRING
ECA DCV
6P8
2
ALPHA 543012 CABLE
LTB
0
100EE (RED)
24VAC
150A(BLK)
151A (BRN)
F
0 101YY(BLU)
LTB
24VAC
CO2
W44 (BLU)
CO2-
CO2
SENSOR
4V 1._)
OUT
24COM
GND
VENTILATION OVERRIDE WIRING
RTOM
EXHAUST
PURGE
PRESSURIZE
5J6
2
3
195A (BLK)
194A (BLK)
LTB
0
191A (BLK
W42 (RED)
OPTIONAL POWER EXHAUST
ACCY WIRES
W43 (BLU)
WNI
•
1 R (RED)
EXH
PUR
0
PRS
0
24VAC
WN2 2K (BLU)
•
O 1 0
LI T1
F
L2'
I I 01-2
T2
FIRE PANEL
REF
DESCRIPTION
ECA
ECONOMIZER ACTUATOR
F
FAN CONTACTOR
LTB
LOW VOLT TERM BLOCK
RTOM
OPTIONS MODULE
WNI
WIRE NUT
WN2
WIRE NUT
NOTE:
1. DASHED LINES REPRESENT RECOMMENDED FIELD
WIRING.
2. APPLIES TO DUCT MOUNTED SENSOR ONLY.
NOTES:
1. PRINT ON STRIP -TAC PLUS WITH BLACK LETTERS
2. REDUCE TRIMMED LABEL TO SIZE INDICATED.
3 50"
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 17 of 18
Others
Jared #415 Replacement
June 26, 2017
Field Installed Options - Part/Order Number Summary
This is a report to help you locate field installed options that arrive at the jobsite. This report provides part or order
numbers for each field installed option, and references it to a specific product tag. It is NOT intended as a bill of
material for the job.
Product Family - 3-10 Ton R410A PKGD Unitary Gas/Electric Rooftop
Item
Tag(s)
Qty
Description
Model Number
Al
R-1
1
3-10 Ton R410A PKGD Unitary
Gas/Electric
YHC120F3RMA--C
001 A2A000A0000
000000000000
A2
R-2
1
3-10 Ton R410A PKGD Unitary
Gas/Electric
YHC120F3RMA--C
001 A2A000A0000
000000000000
A3
R-3
1
3-10 Ton R410A PKGD Unitary
Gas/Electric
YHC120F3RMA--C
001 A2A000A0000
000000000000
Field Installed Option Description
Part/Ordering Number
CO2 wall mounted, field sensor kit
BAYCO2K001 B
Power exhaust
BAYPWRX026A
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 18 of 18
Others
Kingworks
CONSULTING ENGINEERS
600 Dupont St * Ste B
Bellingham, WA 98225
360-714-8260 www.king-works.com
JOB TITLE NRS - Jared's Southcenter
Structural Cales and Sketches
JOB N0. 17201 SHEET NO. 1 ;
CALCULATED BY BBJ DATE 12/6/17
CHECKED BY JRK DATE 17/07/17
Code:
Loads:
FuLa
STRUCTURAL CALCULATIONS
FOR
Northsound Retridgeration
Jared's Southcenter RTU Replacement
16840 Southcenter Parkway
Tukwila, WA
2015 International Building Code
Existing Roof
Dead
Live
20 psf
25 psf
Applied to PDF
REVIEWED FOR
CODE COMPLIANCE
APPROVED
JAN 172013
_BU
City of Tukwila
Mechanical Units
Tag
Ex Wt
New Wt
Change
Note
RTU 1- 7.5T
RTU 2 - 7,5T
RTU 3 - 10T
956 lbs
956 lbs
1094 lbs
1395.5 lbs
1395.5 lbs
1395.5 lbs
46%
46%
28%
increase is greater than 5%, see attached
increase is greater than 5%, see attached
increase is greater than 5%, see attached
Description:
Reviewing replacement of (3) new rooftop mechanical units. Structural calculations
include check for the increase in demand on the existing structure and seismic/wind
anchorage calculations. Structural Sketches Attached in the Appendix
Page Item
1 Calc Cover Sheet
2 Disclaimer and results summary
3 Existing Beam Check
6 Overturning. Criteria
8 Lateral Anchorage
9 Appendix 1: Structural Sketches
13 Appendix 2: As -Built Info Frorn Client
RECEIVED
CITY OF TUKWILA
DEC 0 8 2017
PERMIT CENTER
�IU1�Olg2
Kingworks
CONSULTING ENGINEERS
600 Dupont St * Ste B
Bellingham, WA 98226
360-714-8280 www.king-works.com
JOB TITLE NRS - Jared's Southcenter
Structural Calculations
JOB No. 17201 SHEET NO. 2
CALCULATED BY BBJ DATE 12/6/17
CHECKED BY JRK DATE 12/7/17
Structural Review Disclaimer:
All weights, geometry, and existing building information has been provided by Northsound Refridgeration.
Kingworks takes no responsibility for any incorrect or inaccurate information provided that would change the
results of our calculations. Notify Kingworks immediately if any variations from what has been provided are
encountered in the field.
Structural Review Findings:
The new units do not increase demand on the existing structure by more than 5%. The attached structural
sketches in the appendix outline required seismic anchorage and strengthening to the existing trusses(as
necessary).
Kingworks
CONSULTING ENGINEERS
800 Dupont St * Ste B
Bellingham, WA 98225
380.714-8260 www.king-works.com
JOB TITLE NRS - Jared's Southcenter
Structural Calm and Sketches
JOB NO. 17201 SHEET NO, 3
CALCULATED BY BBJ DATE 12/8/17
CHECKED BY JRK DATE 17/07/17
Review Existing Member to Verify Increase in Demand is Less than 5%
Member: Joists under RTU 1 Span
Existing Loading
Full Uniform Load Point Loads
Pi=
Partial Uniform Load
w1=_1 From
New Proposed Loading
Full Uniform Load . Point Loads
w 41 t, P1=
Loading. Shear, and Moment Diagrams
Existing Loading
Loading
Shear
Moment
1
Results Summary
Partial Uniform Load
w'=
e i¢ From
4',
% Change
w1=
a From tI to
5248 lbs
5327 Ibs
wi=,ir
FromJ
Moment
93775 ft -lbs
New Loading
Existing
New
% Change
Status
Shear
5248 lbs
5327 Ibs
1.52%
OK
Moment
93775 ft -lbs
96201 ft -lbs
2.59%
OK
Kingworks
CONSULTING ENGINEERS
600 Dupont St ` Ste 8
Bellingham, WA 98226
360-714-8260 www.king•works.com
JOB TITLE NRS - Jared's Southcenter
Structural Caics and Sketches
JOB NO. 17201 SHEET NO. 4
CALCULATED BY BBJ DATE 12/6/17
CHECKED BY JRK DATE 17/07/17
Review Existing Member to Verify Increase in Demand is Less than 5%
Member: Joists under RTU 2 Span
Existing Loading
Full Uniform Load Point Loads
w= P1=
Partial Uniform Load
w�=
New Proposed Loading
Full Uniform Load Point Loads
w= P =
Loading, Shear: and Moment Diagrams
Existing Loading
Loading
1
Shear
Moment
Results Summary
Partial Uniform Load
w1=
>Q
From
a
to
w,=
e a
From
1.60%
to 9
w,=
.
From
2.42%
to
New Loading
_A
Existing
New
% Change
Status
Shear
5257 lbs
5341 IN
1.60%
OK
Moment
93439 ft -lbs
95703 ft-tbs
2.42%
OK
Kingworks
CONSULTING ENGINEERS
600 Dupont St * Ste 8
Bellingham, WA 98225
360-714-8260 www,king-works,com
Jos TITLE NRS - Jared's Southcenter
Structural Calcs and Sketches
JOB NO. 17201 SHEET No. 5
CALCULATED BY BBJ DATE 12/6/17
CHECKED BY JRK DATE 17/07/17
Review Existing Member to Verify Increase in Demand is Less than 5%
Member: Joists under RTU 3 Span
Existing Loading
Full Uniform Load Point Loads
w
Partial Uniform Load
From
New Proposed Loading
Full Uniform Load Point Loads
Pi
Loading, Shear, and Moment Diagrams
Existing Loading
Loading
Shear
Moment
Results Summary
Partial Uniform Load
w1_
Existing
ra r From
:®
Status
Shear
w1=
(a..1
From
OK
to
P
eq, From
e �
to
New Loading
1
Existing
New
% Change
Status
Shear
5205 Ibs
5241 Ibs
0.69%
OK
Moment
93239 ft -lbs
94537 ft -lbs
1.39%
OK
Kingworks
CONSULTING ENGINEERS
600 Dupont St *Ste B
Bellingham, WA 98225
360-714-8260 www.king-works.com
Wind and Seismic Overturning Criteria
Seismic (ASCE 7-10 Chapter 13),
Site Class =
Stn.
Ip =
a =
Rp=
Bldg Ht =
Unit Ht on Bldg =
JOB TrrLE NRS - Jared's Southcenter
Structural Cates and Sketches
JOB NO. 17201 SHEET NO. 6
CALCULATED BY BBJ DATE 12/6/"
CHECKED BY JRK DATE 17/07/11
[Assumed]
[USGS Hazard Calculator]
[ASCE Section 13.1.3]
[ASCE Table 13.6-11
[ASCE Table. 13.6-11
[h]
[z]
Seismic Design Force(ASCE 13.3)
Horizontal
0.4dpFfDSWpl1+2h
Fp
pmax = 1.6SDS1PWP
FPmin = 0`3SDSi;pWP
Fp = .48 x Wp <-----controls
F,3max = 1.55 x Wp
Rpm, .29xWp
Design Fptt = .48 x Wp
Vertical
Fpw,t = +/-0.2SdsWp
Design Fp„rt = .19 x Wp
Wind Loads (ASCE 7-10 Chapter 29 Building Appurtenances)
Wind Speed, V
Exposure Cat
Ka=
Kn =
ze =
Kz =
Horizontal GC, =
Horizontal GCr =
qh =
[ASCE Section 26.7.3]
[ASCE Table 28.8.1 ]
[ASCE Section 26.8]
7 [ASCE Table 26.9-1]
1200 [ASCE Table 26.9-1]
0.70 [ASCE Table 27.3-1 Footnote Equations]
1.9 [ASCE Section 29.5.1 ]
1.5 [ASCE Section 29.5.1]
18.446 psf [ASCE Eq 29.3.1]
Phoriz = 35.048 psf
P„et = 27.669 psf
Kingworks
CONSULTING ENGINEERS
800 Dupont St • Ste 8
Bellingham, WA 98225
360.714-8260 www.king-worka.com
JOB TITLE.
JOB NO.
CALCULATED BY
CHECKED BY
NAS - Jared's Southcenter
Structural Calor and Sketches
17201 SHEET NO. 7
BBJ DATE 12/6117
JRK DATE 17107117.
Calculate Unit Overturning and Shear For Wind & Seismic
Unit: RTU 1
Weight =
Length
Width
Height =
Overturning in Short Direction
.13 0
NCV
II II
w
= 676 Ibs
12901bs
Width = 5.25
Overturning in Long Direction
676 Ibs
= 8131bs
Z
Length = 8.333 ft
Max/Min Reactions (LRFD)
1.2D+E: 1257 Ibs
.9D+E: 208 lbs
1.2D+W: 1985 Ibs
.9D+W:-519 lbs
MaxiMin Reactions (ASD)
D+.7E: 992 Ibs
.6D+.7E: 125 Ibs
D+.6W: 1387 Ibs
.6D+.6W: -270 ibs
Max/Min Reactions (LRFD)
1.2D+E: 1152 Ibs
.9D+E: 314 Ibs
1.2D+W: 1658 Ibs
.90+W:-1921bs
Max/Min Reactions (ASD)
D+.7E: 918 Ibs
.6D+.7E: < 199 lbs
D+.6W: 1190 Ibs
.6D+.6W: -74 Ibs
kingworks
CONSULTING ENGINEERS
PROJECT
DESCRIPTION .. .. .. .-....I 1►•? .
ENGINEER PROJECT NO.
360.714-8260 www.kIng-worksrcom ' 9 z.Z /401
DATE
PAGE
AS PIA Pr
MECHANICAL
UNIT PER PLAN
2"x4"x16 GA PLATE WITH (2)#
12 SCREWS INTO MECH'L
UNIT AND (2) #12 SCREWS
INTO CURB ADAPTOR. (2)
PLATES EACH SIDE OF UNIT
CURB ADAPTOR
(18 GA MIN)
..:
#12 SCREW AT 12* OC FOR
PERIMETER OF CURB.
(E) CURB
VERIFY #12aCREWSAT 12" OC MIN,
ADD SCREWS AS REQUIRED TO
MEET 12" OC CRITERIA.
(E) ROOF SHEATHING
(E) JOIST OR
BLOCKING
•
ti (a).#"rz
..:rota "xe ;s( :•
2
Z.
5cZEL.).
S
18
1,4
Kingworks
CONSULTING ENGINEERS
800 Dupont St • Ste 8
Bellingham, WA 88225
SS0-714.8280 www.ding•woncs.com
JOB TITLE NRS - Jared's Southcenter
Structural Cellos and Sketches
JOB NO. 17201 SHEET NO 9
CALCULATED BY BBJ DATE 12/6/17
CHECKED BY JRK DATE 17/07/17
APPENDIX 1: Structural Sketches
FOR
Northsound Refridgeration
Jared's Southcenter RTU Replacement
18840 Southcenter Parkway
Tukwila, WA
0
a
VERIFY IN FIELD
t
90' - 0"
(E) CMU WALLS AT
PERIMETER, TYP
VERIFY IN FIELD
NEW RTU, MAX WT = 1,400 LBS
(EXISTING WT = 1094 LBS)
NEW RTU, MAX WT = 1,400 LBS:
(EXISTING WT = 956 LBS):
NEW RTU, MAX WT = 1,400 LB
(EXISTING WT = 956 LBS)
INDICATES 46" DEEP WOOD
:TRUSSES AT 4'-0" OC SPANNING
BETWEEN CMU WALLS
III
Digi - Seal
Applied to PDF
L
RTU PER PLAN
(E) WOOD TRUSS
PER PLAN
10
SIM
VERIFY MIN 2x6
BLOCKING BELOW
EXISTING CURB BTWN)
JOISTS
NOTES:
1. NOTIFY KINGWORKS IF ANY DISCREPANCIES FROM
EXISTING FRAMING SHOWN ARE FOUND. EXISTING
STRUCTURE SHOWN IS BASED ON INFORMATION
PROVIDED BY NSR, KINGWORKS TAKES NO
RESPONSIBILITY IF ACTUAL FRAMING VARIES FROM WHAT
IS SHOWN.
2. EACH UNIT IS SUPPORTED BY (3) TRUSSES MINIMUM.
3. IF MECHANICAL CURB DOES NOT ALIGN WITH PANEL
POINT ON JOIST, PROVIDE TRUSS STRENGTHENING PER
SSK-03.
k i n gwo rks
EXISTING ROOF PLAN
NSR -SOUTHCENTER JARED'S
CONSULTING ENGINEERS, PLLC
600 DUPONT STREET, SUITE B
BELLINGHAM, WARMS
960-7148260
Www.king-works.com
,Project number 17201
SSK_O 1 1
Date 12107/17
Dram by BBJ
Checked by JRK
Scale As indicated
mpyngi Kn
12/7/2017911.02M4
Digit. Seal
Applied to PDF
L
MECHANICAL
UNIT PER PLAN
2"x4"x16 GA PLATE WITH (2)#
12 SCREWS INTO MECH'L
UNIT AND (2) #12 SCREWS
INTO CURB ADAPTOR. (2)
PLATES EACH SIDE OF UNIT
CURB ADAPTOR
(18 GA MIN)
#12 SCREW AT 12" OC FOR
PERIMETER OF CURB.
(E) CURB
VERIFY #12x3" SCREWS AT 12" OC
MIN, ADD SCREWS AS REQUIRED
TO MEET 12" OC CRITERIA.
(E) ROOF SHEATHING
(E) TOP CHORD OF WOOD
TRUSS. BLOCKING BTWN
TRUSSES AT SIM
11
k i n g� V V A o r'ks
MECHANICAL UNIT ANCHORAGE DETAIL
NSR - SOUTHCENTER JARED'S
CONSULTING ENGINEERS, PLLC
600 DUPONT STREET, WA SUITE
BELLINGHAM, 26 98225
360-714-8260
www.king-works.com
Project number 17201
SSK-02
SSK-02
Date - 12/07/17
Drawn by Author
Checked by Checker
Scale 1 1/2". 1'-0"
® copyright Kingworks Consulting Engineers PLLD 2017
12/7/2017 940:33 AM
CURB ADAPTOR CURB ADAPTOR
(E) CURB (E) CURB
(3) SIMPSON SDS25300
SCREWS EA END
INDICATES (E)
TRUSS PANEL
POINT, TYP
2x8 HF#2 SPANNING
FROM TOP TO BOTTOM
CHORD AS SHOWN
(E) WOOD TRUSS 8" MAX
OPTION A
Digi Seal
Applied to PDF
L
(8) 10d COMMON NAILS
EACH END, SPACE
EQUALLY (ACCEPTABLE
TO STAGGER)
OPTION B
NOTE: STRENGTHENING SHOWN IN THIS SKETCH IS NOT REQUIRED WHEN DIMENSION 'X' IS
LESS THAN 6"
12
3/4" PLYWOOD
STRUCT-I
PLAYWOOD
SHEATHING
ki n gwo rks
EXISTING TRUSS STRENGTHENING DETAIL
NSR-SOUTHCENTER JARED'S
CONSULTING ENGINEERS, PLLC
600 DUPONT STREET, SUITEB
BELLI3GNAM, WA 98225225Date
360-714-8260
www.king-works.com
Project number 17201
SSK-03
12/07/17
Drawn by Author
Checked by Checker
Scale 3/4" = 1'-0"
e copyright Kingwaks ConsNOng Engineers PLLC: 2017
12R/201784833 AM
Kingworks
CONSULTING ENGINEERS
800 Dupont StSte B
Bellingham, WA 98225
360-714-8280 www.kIng-worb.com
JOB TITLE NRS - Jared's Southcenter
Structural Caics and Sketches
JOB NO. 17201 SHEET NO 13
CALCULATED BY 813.1 DATE 12/6/17
CHECKED BY JRK DATE 17/07/17
APPENDIX 2: As-Builts from NSR
FOR
Northsound Refridgeration
Jared's Southcenter RTU Replacement
16840 Southcenter Parkway
Tukwila, WA
Dated 11415 Re lacement
Unit Dimensions - 3.10 Ton R41OA PKGD Unitary Gas/Electric Rooftop
item: Al - A3 Qty: 3 Tag(s): R-1, 11-2, Rya
June 26, 2017
GAS CONNECTION
(SEE NOTE 2)
4017rDO0ii TOP PANEL
DENSER FAN. '
EVAPORATOR SECT O1
ACCESS PANEL—
CONDENSATE (SEL'thiE:4) —
-CONDENSER COIL
C MPE Ssi3R ACC t SS PANEL
POWER WIRE {SEE NOTGi 3l
PACKAGED GAS f ELECTRICAL
THROLIOH THE F.TASE CO
NOTES
1, ALTERNATE CONOtNSATE DRAIN c N,INECTION
... 314'.:-14 NPT DIA. HOLE .... .
2,12' NR -r GAS CONNECTION (0 mbh.120 mbt }
Ft4' NPT GAS CONNECTION (I5 nb ,, 200m64, 25011b15
3. UNIT POWER WIRE 13/0" DIA. HOLE:
4. TRW -THE .BASE ELECTRICAL AND OAS IS NOT STANDARD ON ALL UN ITS.
5 VERIFY WEIGHT, CONNECTION, ANO AU. DIMENSION :WI .
INSTALLER °OCOMENTS BEFORE INSTALLATION .:
PLAN VIEW Ut+NT
OIMCNS1ON DnAVYINia
?i25IRV . 5b7/8'
16 11116`
COb.
StR CE
CONDENSATE DRAIN
PACKAGED GAS I ELECTRICAL
DIMENSION DRAWING
FLO Furnished by Trane U.S. Inc. l In t> tiled by equipment Sabin! al
Ushers
Page 9 ai 1
Jared 5415 Re = Iacement
Weight, Clearance & Rigging Diagram « 3.10 Ton 1141 PKQA Unitary Gas/Electric Rooftop
item: Al • A3 Qty: 3 . Teg(a):.R-1, R-2, R -
INSTALLED ACCESSORIES NET EIGHT DATA
!MRNOAitXfJ3
MOTs la s OSUTSICfE AIR rii
MANUl11'C?UT$ DE Aiti t tA1
BAROiiFi[G RELtEP
Dvti1T&tzD MOT.ti.
I3ELTO IVE t OT♦
POWER E%HAUS'f
THROUGHT THE BASE ELECTRICAL AS:{Ftr g} : 13.t] tE
UNIT A 3UWTEO CIRCUIT BREAKER k0PSS3 S:tt Ib.
POWEREDCONNVEN117M
RINSED DOCRS,tF1OP I
HAIL I3UARD'
TECTOR, SUPPLY ' netu iN.
NOVAR CONTROL
STAINLESS STEEL I -EAT EXCHANGER
ROC* CDPIR
CORNER WEIGHTS I CEfdTEA O :CnAYrtl
(EtLENfi#17 SFiWtDTH
NOTE
All %ado g epproxt ;
Wabhte to pPttons thn! tas trot rot refer to Onto liti/ ¢rs 0uide-
3. 7hn sow I wBrpIn rue Feted m ata unit namedat8. .
4: Refer to unit nameplate mrd Instal alkn atOde for weight; beim srlreduSna tramponellon andOf fink •
tial
S: Tho weight Moan representsthe weal urpt opalciana Weight for ate cced'igutaUon eeacied. Ee1'dnoted
at +t• 1C %of did nameplate .wool. ,
6. Vealy welpttt, cohne teen. and all denensfon wh initaihr dot -favorite beta) installation::
T., Corner wegnts:aro glen for information Oniy
��. 9. NalSnifpng weight at optiwtal anOaserlae slra4d be added to'untt wetgid Mizen ordering (esttory or held
InsttilWd aac04sottea,
PACKAGED GAS J ELECTRICAL
RIGGING AND CENTER OF GRAVITY
FLO = Furnis►ted b
Others
mite US Inc. It
felled by
Equipri
t'atte i"t a# l8
Jar d 11415 ae • acament ... June 2a 2
Weight, Clearance & Rigging. Diagram 3-10 Ton R410A PKQD.Unitary Gas/Electric Rooftop
Item: Al • A3 Qty: 3 Tag(s): R-1, R•2, R-3 .
EAWANCE'FROM TOP OF MT
CLEARANCE 33
CLEARANCE 413'
r> it ~»` k
r, t yr RANCE 48
DOWNFLOW CLEARANCE 36`
HORIZONTAL CLEARANCE :irk
GLEARMICE .36'
PACKAGED, GAS /ELECTH
c EANGE ' ..
i1NITC& (Anima'
633116•
PACKAGEP GAS/ELECTRIC
L oWNFL OV TYPICAL ito it 00ENING
FLn: Furnish c d by .Trane U.S. Inc./1 I by Equipment Subn
Others
Page 12 of 18
CURD
SVTGTTALUT M
COI RESERVES HERIGHT TO CHANGE
WITHOUT NOTIFICATION> IF CURB 18 NQ£DEO IN A
DIFFERENT CONFIGURATION COI.NUST 88 NOTIFIED
PRIOR TO PLACING AN ORDER.. .:... :
6/1/2018
City of Tukwila
Department of Community Development
JESSE SIMENSON
PO BOX 29116
BELLINGHAM, WA 98228
RE: Permit No. M17-0192
JARED'S JEWELERS
16840 SOUTHCENTER PKWY
Dear Permit Holder:
Allan Ekberg, Mayor
Jack Pace, Director
In reviewing our current records, the above noted permit has not received a final inspection by the City of Tukwila Building
Division. Per the International Building Code, International Mechanical Code, Uniform Plumbing Code and/or the National Electric
Code, every permit issued by the Building Division under the provisions of these codes shall expire by limitation and become null
and void if the building or work authorized by such permit has not begun within 180 days from the issuance date of such permit, or if
the building or work authorized by such permit is suspended or abandoned at any time after the work has begun for a period of 180
days. Your permit will expire on 7/23/2018.
Based on the above, you are hereby advised to:
1) Call the City of Tukwila Inspection Request Line at 206-438-9350 to schedule for the next or final inspection. Each
inspection creates a new 180 day period, provided the inspection shows progress.
-or-
2) Submit a written request for permit extension to the Permit Center at least seven(7) days before it is due to expire.
Address your extension request to the Building Official and state your reason(s) for the need to extend your permit.
The Building Code does allow the Building Official to approve one extension of up to 180 days. If it is determined that your
extension request is granted, you will be notified by mail.
In the event you do not call for an inspection and/or receive an extension prior to 7/23/2018, your permit will become null and void
and any further work on the project will require a new permit and associated fees.
Thank you for your cooperation in this matter.
Sincerely,
h e'�le
Permit Technician
File No: M17-0192
6300 Southcenter Boulevard Suite #100 • Tukwila, Washington 98188 • Phone 206-431-3670 • Fax 206-431-3665
City of Tukwila
Department of Community Development
December 20, 2017
JESSE SIMENSON
PO BOX 29116
BELLINGHAM, WA 98228
RE: Correction Letter # 1
MECHANICAL Permit Application Number M17-0192
JARED'S JEWELERS - 16840 SOUTHCENTER PKWY
Dear JESSE SIMENSON,
Allan Ekberg, Mayor
Jack Pace, Director
This letter is to inform you of corrections that must be addressed before your development permit can be approved. All
correction requests from each department must be addressed at the same time and reflected on your drawings. I have
enclosed comments from the following departments:
BUILDING - M DEPARTMENT: Alien Johannessen at 206-433-7163 if you have questions regarding these
comments.
• (GENERAL INFORMATION NOTE)
PLAN SUBMITTALS: (Min. size 11x17 to maximum size of 24x36; all sheets shall be the same size. New revised
plan sheets shall be the same size sheets as those previously submitted.)
(If applicable) "STAMP AND SIGNATURES" "Every page of a plan set must contain the seal/stamp, signature of
the licensee(s) who prepared or who had direct supervision over the preparation of the work, and date of signature.
Specifications that are prepared by or under the direct supervision of a licensee shall contain the seal/stamp,
signature of the licensee and the date of signature. If the "specifications" prepared by a licensee are a portion of a
bound specification document that contains specifications other than that of an engineering or land surveying
nature, the licensee need only seal/stamp that portion or portions of the documents for which the licensee is
responsible." It shall not be required to have each page of "specifications" (calculations) to be stamped and signed;
Front page only will be sufficient. (WAC 196-23-010 & 196-23-020)
(BUILDING REVIEW NOTES)
1. Provide manufactures specification complete with the EER ratings per WSEC, TABLE's C403.
Note: Contingent on response to these corrections, further plan review may request for additional corrections.
Please address the comments above in an itemized format with applicable revised plans, specifications, and/or other
documentation. The City requires that two (2) sets of revised plan pages, specifications and/or other documentation be
resubmitted with the appropriate revision block.
In order to better expedite your resubmittal, a 'Revision Submittal Sheet' must accompany every resubmittal. I have
enclosed one for your convenience. Corrections/revisions must be made in person and will not be accepted through the mail
or by a messenger service.
6300 Southcenter Boulevard Suite #100 • Tukwila Washington 98188 • Phone 206-431-3670 • Fax 206-431-3665
If you have any questions, I can be reached at (206)433-7165.
Sincerely,
Rachelle Ripley
Permit Technician
File No. M17-0192
6300 Southcenter Boulevard Suite #100 • Tukwila Washington 98188 • Phone 206-431-3670 • Fax 206-431-3665
PERMIT COORD COPY
PLAN REVIEW/ROUTING SLIP
PERMIT NUMBER: M17-0192 DATE: : 01/12/18
PROJECT NAME: JARED'S JEWELERS
SITE ADDRESS: 16840 SOUTHCENTER PKWY
Original Plan Submittal Revision #
X Response to Correction Letter # 1 Revision #
before Permit Issued
after Permit Issued
DEPARTMENTS:
Building Division
Public Works ❑
Fire Prevention
Structural
Planning Division
Permit Coordinator
PRELIMINARY REVIEW:
Not Applicable ❑
(no approval/review required)
DATE:
01/16/18
Structural Review Required
REVIEWER'S INITIALS: DATE:
n
APPROVALS OR CORRECTIONS:
Approved
Corrections Required
❑ Approved with Conditions
❑ Denied ❑
DUE DATE: 02/13/18
(corrections entered in Reviews)
(ie: Zoning Issues)
Notation:
REVIEWER'S INITIALS:
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections:
Bldg 0 Fire 0 Ping 0 PW 0
Staff Initials:
12/18/2013
PERMIT CQCRD COPY
PLAN REVIEW/ROUTING SLIP
PERMIT NUMBER: M17-0192 DATE: 12/12/17
PROJECT NAME: JAREDoS JEWELERS
SITE ADDRESS: 16840 SOUTHCENTER PKWY
X Original Plan Submittal
Response to Correction Letter #
Revision # before Permit Issued
Revision # after Permit Issued
DEPARTMENTS:
COltr. ZN)4
Building Division II
Public Works
Fire Prevention
Structural
it*
Planning Division n
❑ Permit Coordinator ❑
PRELIMINARY REVIEW:
Not Applicable
(no approval/review required)
DATE: 12/12/17
Structural Review Required
REVIEWERc6 INITIALS: DATE:
APPROVALS OR CORRECTIONS:
Approved
DUE DATE: 01/09/18
❑ Approved with Conditions ❑
Corrections Required oim
4.1 Denied
(corrections entered in Reviews (ie: Zoning Issues)
Notation:
REVIEWERc$ INITIALS:
DATE:
[Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections:
Bldg Fire ❑ Ping ❑ PW ❑ Staff Initials: P(1.--
12/18/2013
City of Tukwila
REVISION
SUBMITTAL
Department of Community Development
6 300 Southcenter Boulevard, Suite #100
T ikwila, Washington 98188
Phone: 206-431-3670
Web site: http://wvTukwilaWA.gov7)
Revision submittals must be submitted in person at the Permit Center.
Revisions will not be accepted through the mail, fax, etc.
Date: -1 1 1'0 1 8 Pian Check/Permit Number: M17-0192
❑ Response to Inc( mplete Letter #
® Response to Corection Letter # 1
El Revision # after Permit is Issued
❑ Revision requested by a City Building Inspector or Plans Examiner
Deferred Submittal #
Project Name: JARED'S JEWELERS
Project Address:
Contact Perso
16840 SOUTHCENTER PKWY
Summary of Revision :
Phone Number: DO'
cft-
RECEIVED
CITY OE TUKWILA
JAN 12 2018
PERMIT CENTER
Sheet Number(s):
"Cloud" or highlight all areas of revision including date of nevi:
Received at the City o=
NORTHSOUND REFRIGERATIO'T INC
Home Espanol Contact
Safety & Health Claims & Insurance
Washington State Department of
Labor & industries
Page 1 of 2
Search L&I
A -Z Index Help - My L&1
Workplace Rights Trades & Licensing
NORTHSOUND REFRIGERATION INC
Owner or tradesperson
Principals
MILSTEAD, PAUL STUART, PRESIDENT
Doing business as
NORTHSOUND REFRIGERATION INC
WA UBI No.
602 170 260
PO BOX 29116
BELLINGHAM, WA 98228
360-380-1381
WHATCOM County
Business type
Corporation
License
Verify the contractor's active registration / license / certification (depending on trade) and any past violations.
Construction Contractor
License specialties
GENERAL
License no.
NORTHRI898CG
Effective — expiration
02/07/2011— 02/07/2019
Bond
CBIC
Bond account no.
SI8582
Active.
Meets current requirements.
$12,000.00
Received by L&I Effective date
02/07/2011 02/03/2011
Expiration date
Until Canceled
Insurance
Berkley Insurance Co $2,000,000.00
Policy no.
CPA602833622
Received by L&I Effective date
06/02/2017 06/09/2017
Expiration date
06/09/2018
Insurance history
Savings
No savings accounts during the previous 6 year period.
Lawsuits against the bond or savings
No lawsuits against the bond or savings accounts during the previous 6 year period.
L&I Tax debts
No L&I tax debts are recorded for this contractor license during the previous 6 year period, but some debts
may be recorded by other agencies.
License Violations
No license violations during the previous 6 year period.
Help us improve