HomeMy WebLinkAboutPermit PG17-0123 - TEMPURPEDIC - LAVATORY, MOP SINK, WATER COOLERTEMPURPEDIC
17195 SOUTHCENTER PKWY
PGI7-0123
Parcel No:
Address:
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670
Inspection Request Line: 206-438-9350
Web site: http://www.TukwilaWA.gov
PLUMBING/GAS PIPING PERMIT
2623049071
17195 SOUTHCENTER PKWY
Project Name: TEMPURPEDIC
Permit Number: PG17-0123
Issue Date: 10/26/2017
Permit Expires On: 4/24/2018
Owner:
Name:
Address:
Contact Person:
Name:
Address:
Contractor:
Name:
Address:
License No:
Lender:
Name:
Address:
KTM GROUP LLC
2810 EASTLAKE AVE E , SEATTLE, CA,
98102
ROBBIE FRAZIER
515 S FLOWER ST, LOS ANGELES, CA,
980071'
PRECISION PLUMBING & HEATING
155 SW 142 ST, BURIEN, WA, 98166
PRECI PH894CW
1!/
Phone: (619) 609-9359
Phone: (206) 393-0681
Expiration Date: 2/16/2019
DESCRIPTION OF WORK:
DEMO OLD BATHROOM LOCATIONS. INSTALL NEW TOI;ET, LAVATORY FOR NEW LOCATION OF BATHROOM.
INSTALL NEW MOP SINK AND WATER COOLER
Valuation of Work: $11,800.00
Water District: TUKWILA
Sewer District: TUKWILA
Fees Collected: $246.50
Current Codes adopted by the City of Tukwila:
International Building Code Edition:
International Residential Code Edition:
International Mechanical Code Edition:
Uniform Plumbing Code Edition:
International Fuel Gas Code:
Permit Center Authorized Signature:
2015
2015
2015
2015
2015
National Electrical Code:
WA Cities Electrical Code:
WAC 296-46B:
WA State Energy Code:
2014
2014
2014
2015
Date: 1. / - 11,91
I hearby certify that I have read and examined this permit and know the same to be true and correct. All
provisions of law and ordinances governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other
state or local laws regulating construction or the performance of work. I am authorized to sign and obtain this
development permit and agree to the conditions attached to this permit.
Signature:
Print Name:
&V/ A-6
Date:
This permit shall become null and void if the work is not commenced within 180 days for the date of issuance, or if
the work is suspended or abandoned for a period of 180 days from the last inspection.
PERMIT CONDITIONS:
1: ***PLUMBING/GAS PIPING PERMIT CONDITIONS***
2: No changes shall be made to applicable plans and specifications unless prior approval is obtained from the
Tukwila Building Division.
3: All permits, inspection records and applicable plans shall be maintained at the job and available to the
plumbing inspector.
4: All plumbing and gas piping systems shall be installed in compliance with the Uniform Plumbing Code and
the Fuel Gas Code.
5: No portion of any plumbing system or gas piping shall be concealed until inspected and approved.
6: All plumbing and gas piping systems shall be tested and approved as required by the Plumbing Code and
Fuel Gas Code. Tests shall be conducted in the presence of the Plumbing Inspector. It shall be the duty of
the holder of the permit to make sure that the work will stand the test prescribed before giving notification
that the work is ready for inspection.
7: No water, soil, or waste pipe shall be installed or permitted outside of a building or in an exterior wall
unless, adequate provision is made to protect such pipe from freezing. All hot and cold water pipes
installed outside the conditioned space shall be insulated to minimum R-3.
8: Plastic and copper piping running through framing members to within one (1) inch of the exposed framing
shall be protected by steel nail plates not less than 18 gauge.
9: Piping through concrete or masonry walls shall not be subject to any load from building construction. No
plumbing piping shall be directly embedded in concrete or masonry.
10: All pipes penetrating floor/ceiling assemblies and fire -resistance rated walls or partitions shall be protected
in accordance with the requirements of the building code.
11: Piping in the ground shall be laid on a firm bed for its entire length. Trenches shall be backfilled in thin
layers to twelve inches above the top of the piping with clean earth, which shall not contain stones,
boulders, cinderfill, frozen earth, or construction debris.
12: The issuance of a permit or approval of plans and specifications shall not be construed to be a permit for, or
an approval of, any violation of any of the provisions of the Plumbing Code or Fuel Gas Code or any other
ordinance of the jurisdiction.
13: The applicant agrees that he or she will hire a licensed plumber to perform the work outlined in this permit.
14: All new plumbing fixtures installed in new construction and all remodeling involving replacement of
plumbing fixtures in all residential, hotel, motel, school, industrial, commercial use or other occupancies
that use significant quantities of water shall comply with Washington States Water Efficiency ad
Conservation Standards in accordance with RCW 19.27.170 and the 2006 Uniform Plumbing Code Section
402 of Washington State Amendments
PERMIT INSPECTIONS REQUIRED
Permit Inspection Line: (206) 438-9350
8004 GROUNDWORK
1900 PLUMBING FINAL
8005 ROUGH -IN PLUMBING
CITY OF TUKWILA
Community Development Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http://www.TukwilaWA.gov
Plumbing/Gas Permit No. 174'1-1- 01z3
Project No.
Date Application Accepted:
Date Application Expires: (.4 (,i- (e
(For office use only)
10.x-(1
PLUMBING / GAS PIPING PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
`14 n ( Applications will not be accepted through the mail or by fax.
/" V ( � �% - O'- **Please Print**
SITE LOCATION
Site Address:
17195 South Center Pgrkway
Tenant Name:
Tempur Pedic
PROPERTY OWNER
Name: KTM Group, LLC, Kevin McNulty
Address: 2810 Eastlake Avenue East
City: Seattle State: WA Zip: 98102
CONTACT PERSON — person receiving all project
communication
Name: Robbie Frazier
Address: 155 SW 142nd Street
Address: 515 S. Flower Street
Phone: L 0 (0.. 51 3. 068i Fax: iv,
City: Los Angeles State: CA
Zip: 90071
Phone: (619) 609-9359 Fax:
Email: robbie.frazier@am.jll.com
King Co Assessor's Tax No.:262304-9069; 262304-907€
Suite Number. Floor:
New Tenant: Yes ❑ ..No
PLUMBING CONTRACTOR INFORMATION
Company Name: Precision Plumbing & Heating
Address: 155 SW 142nd Street
City: Burien State: WA Zip: 98166
Phone: L 0 (0.. 51 3. 068i Fax: iv,
Contr Reg No.: PRECIPH894CW Exp Date: Z f f 4% f 9
/
Tukwila Business License No.: o i ` ('v .2
Valuation of Project (contractor's bid price): $ L 8
Scope of Work (please provide detailed information): 1).j y,U 5 (
WA) *LIRA/ iti-ii4d0 "f0 *Pla2AA)
MCI s t i CUA-Ct c'ScLk ' cam, U -V"
Building Use (per Int'I Building Code):
Occupancy (per Int'I Building Code):
Utility Purveyor: Water:
I4: Applicatiars\FomwApp&<scions On Line12011 Applicatio s\PIumlang Permit Application Revised 8.4-11_doc.
Revised: August 2011
Mt
bOAretill
[46-641"1 a - biS-1C,ge
eel Of 154,1 114,66141, ,66141, t 14. he Fr)
Sewer:
Page 1 of 2
Indicate type of plumbing fixtures and/or gas piping outlets being installed and the quantity below:
Fixture Type
Qty
Bathtub or combination
bath/shower
Dishwasher, domestic with
independent drain
1
Shower, single head trap
1
Sinks
Rain water system — per
drain (inside building)
1
Grease interceptor for
commercial kitchen (>750
gallon capacity)
i
Each additional medical
gas inlets/outlets greater
than 5
Atmospheric -type vacuum
breakers not included m
lawn sprinkler backflow
protections (1-5)
Medical gas piping
system serving 1-5
inlets/oudets for a specific
gas
Fixture Type
Qty
Bidet
Drinking fountain or water
cooler (per head)
1
Lavatory
1
Urinal
Water heater and/or vent
1
Repair or alteration of
water piping and/or water
treatment equipment
i
Back flow protective device
other than atmospheric -
type vacuum breakers 2
inch (51 mm) diameter or
smaller
Atmospheric -type vacuum
breakers not included in
lawn sprinkler backflow
protections over 5
Medical gas piping
system serving 1-5
inlets/oudets for a specific
gas
Fixture Type
Qty
Clothes washer,
domestic
Food -waste grinder,
commercial
Floor drain
Wash fountain
Water closet
Industrial waste
treatment interceptor,
including trap and vent,
except for kitchen type
grease interceptors
Building sewer and each
trailer park sewer
Repair or alteration of
drainage or vent piping
1
Backflow protective
device other than
atmospheric -type
vacuum breakers over 2
inch (51 mm) diameter
Gas piping outlets
Medical gas piping
system serving 1-5
inlets/oudets for a specific
gas
Future Type
Qty
Dental unit, cuspidor
Floor drain
v
Receptor, indirect waste
Building sewer and each
trailer park sewer
Each grease trap
(connected to not more
than 4 fixtures - <750
gallon capacity
Medical gas piping
system serving 1-5
inlets/oudets for a specific
gas
•
Each lawn sprinkler
system on any one meter
including backflow
protection devices
PA aO St vL ((
1
PERMIT APPLICATION NOTES -
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review —Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The Building Official may grant one extension of time for an additional period not to exceed 180 days. The extension shall be requested in writing
and justiciable cause demonstrated. Section 103.4.3 International Plumbing Code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWNER OR AUIHORIZED AGENT:
f/
Signature: "" I
Print Name:
111nyo
c�, �Z c
Mailing Address: 155 S VJ 14 eJ .
tLApplicetiuns\Forms-Applications Onr ine12011 ApplicuansPPiumbing Permit Application Revised 8-9.11:docx
Revised: August 2011
bh
Day Telephone:
ILLVI to
City
Date: 10/ Z
1,
2r%1c/. ala 42p 8///
98iddla
State Zap
Page 2 of 2
Cash Register Receipt
City of Tukwila
DESCRIPTIONS
ACCOUNT
I QUANTITY
I PAID
$200.22
PermitTRAK
PG17-0123 Address: 17195 SOUTHCENTER PKWY Apn: 2623049071
$200.22
Credit Card Fee
$5.83
Credit Card Fee
I R000.369.908.00.00
0.00
$5.83
PLUMBING
$185.13
PERMIT FEE
R000.322.100.00.00
0.00
$151.98
PERMIT ISSUANCE BASE FEE
R000.322.100.00.00
0.00
$33.15
TECHNOLOGY FEE
$9.26
TECHNOLOGY FEE
TOTAL FEES PAID BY RECEIPT: R12657
R000.322.900.04.00
0.00
$9.26
$200.22
Date Paid: Thursday, October 26, 2017
Paid By: TALIA MARINO
Pay Method: CREDIT CARD 094516
Printed: Thursday, October 26, 2017 1:45 PM 1 of 1
CSYSTEMS
Cash Register Receipt
City of Tukwila
DESCRIPTIONS
ACCOUNT
QUANTITY
PAID
PermitTRAK
$46.28
PG17-0123 Address: 17195 SOUTHCENTER PKWY Apn: 2623049071
$46.28
PLUMBING
$46.28
PLAN CHECK FEE
TOTAL FEES PAID BY RECEIPT: R12508
R000.322.103.00.00
0.00
$46.28
$46.28
Date Paid: Friday, October 06, 2017
Paid By: UNITED STATES PERMIT
Pay Method: CHECK 15340
Printed: Friday, October 06, 2017 11:16 AM 1 of 1
CirliWSYSTEMS
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 438-9350
PERMIT NO.
Project:
' .rv4Pt1RRRVIC
Type of Inspection:
PL. l)tvt5'N6- FINAL
Address:
I7195- SooniCEifiM 444JY
Date Called:
Special Instructions:
Date Wanted:
I
—62-/7
a m.
p.m.
Requester:
Phone No:
Approved per applicable codes.
Corrections required prior to approval.
COMMENTS:
- PLA) .,BIN.G-
Inspector:
Date:
Ia<49-17
REINSPECTION FEE REQUIRED. Prior to next inspection. fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection.
INSPECTION NO.
INSPECTION RECORD
Retain a copy with permit
% .47 8}23
PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 438-9350
Project:
IMPI)R 1'AC9C
Type of Inspection:
RoU64+-6'1 FL-vi/'4 146-
46Add7
ress:
Address:
17145 Sesv i-tCovirzA PRICI
Date Called:
Special Instructions:
Date Wanted:
. l6s3i-17
(m.
P.m
Requester: 50
dd''
Phone No:
'26 6a q/' Li 11
Approved per applicable codes. 1J Corrections required prior to approval.
COMMENTS:
ok- RQi/ /1L/ Y ?Lif /I/re —.
Inspector:
Date:
/6 3/ —I 7
REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
INSPECTION NO.
CITY OF TUKWILA BUILDING
6300 Southcenter Blvd., #100, Tukwila. WA 98188
Permit Inspection Request Line (206) 438-9350
INSPECTION RECORD
Retain a copy with permit
F 476123
PERMIT NO.
DIVISION
(206) 431-3670
Project:
TiZr"tPi)&?i
iC._
Type of Inspection:
g oVAJO i4JcRK
Address:
Date Called:
, j
Special Instructions:
Date Wanted:
i!O--31--17
a.mj
N711.
Requester:
Phone No:
Approved per applicable codes. L_J Corrections required prior to approval.
COMMENTS:
6u — CcONID t' K
Inspector:
Date:
i0 -:3i
REINSPECTION FEE REQUIRED. Prior to next inspection. fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
PERMIT COORD COPY
PLAN REVIEW/ROUTING SLIP
PERMIT NUMBER: PG17-0123 DATE: 10/06/17
PROJECT NAME: TEMPURPEDIC
SITE ADDRESS: 17195 SOUTHCENTER PKWY
X Original Plan Submittal
Response to Correction Letter #
Revision # before Permit Issued
Revision # after Permit. Issued
DEPARTMENTS:
—�7 Buildin Division
g
S A C WH 7
Public Works
Fire Prevention
Structural
PRELIMINARY REVIEW:
Not Applicable n
(no approval/review required)
❑ Planning Division ❑
❑ Permit Coordinator
DATE: 10/10/17
Structural Review Required
REVIEWER'S INITIALS: DATE:
APPROVALS OR CORRECTIONS: DUE DATE: 11/07/17
Approved
❑ Approved with Conditions
Corrections Required ❑ Denied ❑
(corrections entered in Reviews) (ie: Zoning Issues)
Notation:
REVIEWER'S INITIALS:
DATE:
'Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg 0 Fire 0 Ping 0 PW ❑ Staff Initials:
12/18/2013
PRECISION PLUMBING & HEATING
Home Espanol Contact
Safety & Health
Washington State Department of
`% Labor & Industries
Search L&I
Page 1 of 4
A -Z Index Help My 1.,81
Claims & Insurance Workplace Rights
PRECISION PLUMBING & HEATING
Owner or tradesperson
Principals
DIXON, ERIC JOHN, PARTNER
MARINO, TALIA ROSE, PARTNER
Doing business as
PRECISION PLUMBING & HEATING
WA UBI No.
603 068 715
155 SW 142nd St
BURIEN, WA 98166
206-393-0681
KING County
Business type
Partnership
Governing persons
TALIA
ROSE
MARINO
ERIC JOHN DIXON;
License
Verify the contractor's active registration / license / certification (depending on trade) and any past violations.
Construction Contractor Active.
..................._...._........_........................_.......
Meets current requirements.
License specialties
GENERAL
License no.
PRECIPH894CW
Effective — expiration
02/16/2011— 02/16/2019
Bond
Lexon Ins Co
Bond account no.
9808725
Received by L&I
09/13/2011
$12,000.00
Effective date
09/14/2011
Expiration. date
Until Canceled
Bond history
Insurance
Ohio Security Ins Co $1,000,000.00
Policy no. -
BKS56298282
Received by L&I Effective date
07/20/2017 09/14/2014
Expiration date
09/14/2018
Insurance history
Trades & Licensing
Help us improve
https://secure.lni.wa.gov/verify/Detail.aspx?UBI=603068715&LIC=PRECIPH894CW&SAW= 10/26/2017
PRECISION PLUMBING & HEATTNG
Savings
..................
No savings accounts during the previous 6 yea, period.
Lawsuits against the bond or savings
No lawsuits against the bond or savings accounts during the previous 6 year period.
L&I Tax debts
No L&I tax debts are recorded for this contractor license during the previous 6 year period, but some debts
may be recorded by other agencies.
License Violations
Infraction no.
EJONM01549
Issue date .
05/02/2017
Violation city
BURIEN
Type of violation
ELECTRICAL CITATION
Description
Offering to perform, submitting a bid for,
advertising, installing or maintaining cables,
conductors or equipment that convey or
utilize electrical current without having a valid
electrical contractor license.
Infraction no.
EJONM01550
Issue date
05/02/2017
Violation city
BURIEN
Type of violation
ELECTRICAL CITATION
Description
Failing to get an inspection or obtain a valid
electrical/telecommunications work permit or
post a provisional electrical work permit prior
to beginning the electrical/telecommunication
installation or alteration as referenced in WAC
296-46B-901.
Infraction no.
PJONV04114
Issue date
12/02/2016
Violation city
BURIEN
Type of violation
PLUMBER INFRACTION
Description
Contractor employed a person to engage in
the trade of plumbing without a current
journeyman, specialty or trainee certificate,
temporary permit or medical gas endorsement
as required. ERIC DIXON CONDUCTING
PLUMBING INSTALLATION WITHOUT A VALID
PLUMBING CERTIFICATE.
Infraction no.
PJONV04113
Issue date
12/02/2016
Violation city
BURIEN
Type of violation
PLUMBER INFRACTION
Description
Satisfied
..........................
RC W/WAC
19.28.041 RCW
Violation amount
$500.00
Satisfied
RCW/WAC
19.28.101 RCW
Violation amount
$250.00
Satisfied
....................
RCW/WAC
18.106.020
Violation amount
$500.00
Satisfied
.......... _..............
RCW/WAC
18.106.020
Violation amount
$500.00
Page 2 of 4
Help us improve
https://secure.lni.wa.gov/verify/Detail.aspx?UBI=603068715&LIC=PRECIPH894CW&SAW= 10/26/2017
NOTE: PROVIDE TRAP PRIMERS
FOR DRAINS AS REQUIRED BY
LOCAL AUTHORITIES OR CODE.
COLD
WATER
LINE
BALL VALVE
1/2" CW CONNECT TO TOP
OF COLD WATER MAIN.
TRAP PRIMER
CEILING
/2" PRIMING LINE
TRAP PRIMER DETAIL
SCALE: NONE
CHROME WALLCOVER
AND SCREW
1/8 BEND IF
CLEANOUT OCCURS
AT END OF LINE
.a.
Z4-
11
-I
:111
„i 1 iii 1 lil H III=
WALL CLEANOUT DETAIL
SCALE: NONE
MAY EXTEND AS
WASTE OR VENT
PLUGGED TEE
w/ CLEANOUT
FLOOR LINE
1/8 BEND
WASTE LINE
LENGTH TO SUIT
WASTE LINE
STONE BASE
SLB. LEAD FLASHING SHALL BE FORMED TO CHIPPED CONCRETE WITH A POSITIVE
/ SLOPE TO CLAMP DEVICE. PROVIDE NONSHRINK GROUT UNDER LEAD FLASHING
AS REQUIRED TO FACILITATE POSITIVE SLOPE (ANY FLASHING MATERIALS OTHER
THAN LEAD IS UNACCEPTABLE. MINIMUM WIDTH OF FLASHING SHALL BE 24").
1/2" C
TO T
PRIMER
ADJUSTABLE
STRAINER
FINISH FLOOR
SLOPE TO DRAIN
CAST IRON
FLOOR DRAIN
CORE DRILL 10"0
AND 413 HOLES
THREADED OR C
OUTLET
lTh\— OUTLET
NOTE: THE GENERAL CONTRACTOR SHALL PROVIDE A ONE PIECE WATER PROOF
MEMBRANE FLOOR AND BASE IN THE TOILET ROOM(S).
FLOOR DRAIN W/TRAP PRIMER
SCALE: NONE
C5
PIPE INSULATION
INSULATION SHALL BE RUN
CONTINUOUS THRU HANGERS
INSULATION PROTECTION SHIELD.
USE 16 GAUGE SHEET STEEL,
2 PIPE DIAMETERS LONG,
120 DEGREES SUPPORT, OR
GRINNEL FIGURE 167.
PIPE HANGER DETAIL
SCALE: NONE
6
MOP HANGER
SERVICE FAUCET WITH
VACUUM BREAKER
30"HOSE
HOSE BRACKET
24"
0_
APPLY SILICONE
SEALANT BETWEEN
MOP SINK AND
ADJACENT
SURFACES
MOP SINK DETAIL /-
SCALE:
NONE
VACUUM BREAKER
07- HEAT TRAP
4_
5
GATE VALVE (TYP.)
ELECTRIC UNION (TYP.)
WATER
11/HEATER
T & P RELIEF VALVE.
DISCHARGE TO MOP SINK.
2" WIDE, 20 GA. SHEET METAL BAND,
f SECURE TO WALL IN THE FOR
•
•
1$
MOO
SEISMIC BRACING WHERE
REQUIRED BY CODE. BRACING
SHALL BE LOCATED IN THE UPPER
ONE-THIRD OF THE UNIT AND THE
LOWER ONE-THIRD OF THE UNIT.
THE LOWER BRACING MUST BE A
MIN. 4" ABOVE WATER HEATER
CONTROL UNIT AS APPLICABLE.
2 -GAL. THERMAL
EXPANSION TANK
24"x24"x9" GALV.
SHEET METAL
(16 GA) DRAIN
PAN
3/4" DRAIN LINE FROM SAFE 'N'NMOUNTING SHELF,
--N-- rt.) ry PAN. ROUTE TO MOP SINK REFER TO
PER CODE. ARCHITECTURAL
WATER HEATER DETAIL SHEET A400.
SCALE: NONE
PLUMBING SPECIFICATIONS
HANDICAP SPECIFICATIONS: ARCHITECTURAL BARRIERS ACT 42/USC. 4151-4157
GENERAL
THE WORK COVERED BY THESE SPECIFICATIONS INCLUDES BUT IS NOT LIMITED TO PROVIDING ALL LABOR,
MATERIAL, AND EQUIPMENT NECESSARY TO COMPLY WITH REQUIREMENTS OF THIS FACILITY.
REFER TO ARCHITECTURAL SHEET A400 FOR ADA REQUIREMENTS AND CLEARANCES OF PLUMBING FIXTURES.
PLUMBING FIXTURES
A. WATER CLOSET (STANDARD) - AS IDENTIFIED ON PLANS - 1/2" C.W. SUPPLY AND 4" VENTED WASTE.
FORCE REQUIRED TO ACTIVATE FLUSH VALVE LEVER TO BE 5 LBS. MAXIMUM (4.16.5)
B. LAVATORY - AS IDENTIFIED ON PLANS WITH FAUCET, 1/2" C.W. AND H.W. SUPPLY AND 1-1/2" VENTED WASTE.
EXPOSED WATER AND DRAIN PIPING BELOW LAVATORY SHALL BE INSULATED WITH "PLUMBEREX" (OR EQUAL)
PIPE COVERS.
FAUCET CONTROLS SHALL BE OF THE TYPE NOT REQUIRING TIGHT GRASPING, PINCHING, OR TWISTING OF
WRIST AND AN OPERATING FORCE NOT EXCEEDING 5 LBS.
SELF-CLOSING VALVES SHALL BE OF THE TYPE REMAINING OPEN FOR AT LEAST 10 SECONDS.
C. CLEAN -OUTS - SHALL BE AS MANUFACTURED BY JOSAM, ZURN, OR EQUAL, AND SHALL BE INSTALLED AT
ALL BENDS, ANGLES, AND ENDS OF ALL WASTE AND SEWER LINES, AS CALLED FOR ON THE DRAWINGS AND
AS REQUIRED BY LOCAL CODES. ALL CLEAN -OUTS SHALL BE FLUSH WITH FINISHED FLOOR TO GRADE, AND
IN ALL CASES, SHALL BE PROVIDED WITH SUFFICIENT SPACE FOR RODDING.
D. FLOOR DRAIN - AS IDENTIFIED ON PLANS. CAST IRON DRAIN WITH NICKEL -BRONZE STRAINER; INSIDE CAULK
OUTLET AND COMBINATION INVERTIBLE MEMBRANE CLAMP AND ADJUSTABLE COLLAR. PROVIDE WITH TRAP
PRIMER TAP AND TRAP PRIMER WHERE INDICATED.
E. WATER HEATER - MANUFACTURER AS IDENTIFIED ON PLANS. REFER TO PLUMBING DRAWING TO
DETERMINE IF NEW WATER HEATER IS A TANK TYPE OR IS OF THE INSTANTANEOUS VARIETY.
F. WATER HAMMER ARRESTOR - EQUAL TO PRECISION PLUMBING PRODUCT SC SERIES, INSTALLED PER
MANUFACTURER'S RECOMMENDATIONS.
NOTE: NOTE: OWNER'S GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER INSTALLATION OF ALL
TOILET ACCESSORIES INCLUDING SUPPORT BLOCKING INSIDE WALL.
MATERIALS
A. SANITARY SEWER - ALL SANITARY PIPING SHALL BE CAST IRON. VENTS TWO INCHES (2") IN SIZE AND
SMALLER MAY BE EITHER SCHEDULE 40 GALVANIZED STEEL OR COPPER PIPING. PVC CAN BE USED IF
ALLOWED BY LANDLORD AND CODE.
B. DOMESTIC WATER AND HOT WATER PIPING ABOVE GROUND TO BE COPPER TUBING TYPE "L" AND BELOW
GROUND SHALL BE COPPER TUBING TYPE "K." ALL COLD AND HOT WATER PIPING SHALL BE INSULATED
WITH ARMAFLEX OR EQUIVALENT INSULATING TO A THICKNESS OF 1".
PIPING
A. PIPING AND FITTINGS SHALL BE OF THE WEIGHTS AND TYPES SHOWN ON DRAWINGS. SIZES SHOWN ON ON
DRAWINGS ARE NOMINAL PIPE SIZES.
B.
C. ALL PIPING SHALL BE UPENDED AND POUNDED TO REMOVE ANY FOREIGN MATERIAL PRESENT AND SHALL
BE SWABBED IF NECESSARY.
PREPARING PIPE
A. SCREWED PIPE SHALL BE INSTALLED WITH PIPE COMPOUND APPLIED TO THE MALE THREAD WITH NOT
MORE THAN TWO THREADS LEFT EXPOSED. PIPE SHALL BE REAMED AFTER THREADING.
B. COPPER JOINTS SHALL BE MADE UP WITH 95-5 SOLDER.
HANGERS AND SUPPORTS
HORIZONTAL PIPING SHALL BE SUPPORTED AT INTERVALS NOT TO EXCEED 10'-0" WITH SWIVEL SPLIT PIPE
HANGERS EQUAL TO CRANE #199F OR GRINNELL #104. VERTICAL PIPING SHALL BE SUPPORTED BY MEANS OF
WROUGHT IRON CLAMPS SUSPENDED FROM THE UNDERSIDE OF STRUCTURE WITH HANGER RODS.
VALVES
ALL VALVES SHALL BE BRASS AND MANUFACTURED BY CRANE, NIBCO, STOCKHAM, LUNKENHEIMER,
NORDSTROM, GRINNELL OR EQUAL.
TESTING AND ADJUSTING
CONTRACTOR SHALL DEMONSTRATE OPERATION OF PIPING SYSTEM TO FULL SATISFACTION OF TENANT. ALL
PIPING SHALL WITHSTAND AIR PRESSURE TESTING PER GOVERNING CODES.
GUARANTEE
ALL MATERIALS, EQUIPMENT, AND WORKMANSHIP SHALL BE GUARANTEED FOR A PERIOD OF ONE (1) YEAR
AFTER DATE OF ACCEPTANCE. THE COMPLETED PLUMBING SYSTEM SHALL BE FULLY OPERATIONAL AND
ACCEPTANCE BY TENANT SHALL BE A CONDITION OF THIS CONTRACT. ALL WORK FOUND TO BE DEFECTIVE
SHALL BE REPAIRED OR REPLACED BY THIS SUBCONTRACTOR WITHOUT ADDITIONAL COST TO THE TENANT.
PLUMBING FIXTURE SCHEDULE
FIXTURE DATA
CONNECTION DATA
•
REMARKS
FIXTURE
QTY.
MFG.
CATALOG
NO.
SOIL
SIZE
VENT
SIZE
TRAP
WATER
COLD
HOT
5
LAVATORY
1
1
1
1-1/2"
2
2
EMERGENCY FLOOR DRAIN
1
WATER
CLOSET
(WC)
1
*AMERICAN
STANDARD
2467.100
4"
2"
4"
1/2"
---
1.1 GPF, 16-1/2" HIGH,
ELONGATED BOWL, PROVIDE
WITH ELONGATED OPEN FRONT
TOILET SEAT (#5325.024)
LAVATORY
(LAV)
1
*AMERICAN
STANDARD
0124.024
1 1/ z
1 1/ a
1 1/ "
z
1/ ,
'2
1/ „
z
20"x18" VITREOUS CHINA, 4"
CENTERSET, WITH WALL
HANGER. FAUCET: AMERICAN
STANDARD RELIANT 3 MODEL#
7385.000 W/POP -UP DRAIN,
METAL LEVER HANDLE,
PROVIDE 0.5 GPM AERATOR
SPRAY. PROVIDE WITH
THERMOSTATIC MIXING VALVE
PER CODE UNDER LAVATORY.
ADJUST TO A MAXIMUM
SETTING OF 110°F AT TIME OF
INSTALLATION.
MOP SINK
(MS)
1
FIAT
MSB 2424
3"
2"
3"
1/Z
z
I/z „
24"x24"x10"H MOLDED STONE
MOP SINK WITH VINYL
BUMPER GUARDS AND FIAT
#QDC-3 FOR 3" DRAIN
CONNECTION. FAUCET:
AMERICAN STANDARD
8354.112 WITH VACUUM
BREAKER AND INTEGRAL
SUPPLY STOPS.
FLOOR DRAIN
(FD)
1
ZURN
Z415
4"
4"
1"
FLOOR DRAIN
O
3" WITH NICKEL BRONZE
STRAINER. EQUALS BY J.R.
SMITH OR WADE.
TRAP PRIMER
(TP)
1
*PPP
P1-500
--
---
---
/2„
___
WALL CLEAN
OUT (WCO)
2
*ZURN
Z1441
SEE
RISER
___
___
___
---
EQUALS BY J.R. SMITH OR
WADE.
WATERs
HEATER
(WH)
1
*A.O.
SMITH
DEL -10
---
---
- _-
s
/a
„
/4
10 GALLON ELECTRIC WATER
HEATER, 3000W, 120V, 1
PHASE, 8 GPH RECOVERY
RATE AT 90°F RISE. PROVIDE
DRAIN VALVE, T & P RELIEF
VALVE, DRAIN PAN, AND 2
GALLON EXPANSION TANK,
AMTROL, MODEL #ST -5.
HI-LO1
DRINKING
FOUNTAIN
*SUNROC
ADAACB
1�4 .1
��a„
1�a"
3
i a
---BARRIER
FREE BI -LEVEL
W/FRONT PUSH BAR, PROVIDE
WITH APRON.
* OR APPROVED EQUAL
NEW PLUMBING FIXTURE CALCULATIONS
PLUMBING
FIXTURE
SANITARY
FIXTURE
QUANTITY
SANITARY
FIXTURE
UNIT EA.
SANITARY
FIXT. UNIT1
TOTAL 1
VENT
SIZE
EACH
C.W.
F.U.
EACH
C.W.
F.U.
TOTAL
WATER CLOSET
1
4
4
2"
5
5
LAVATORY
1
1
1
1-1/2"
2
2
EMERGENCY FLOOR DRAIN
1
0
0
2"
–
–
TRAP PRIMER
1
–
–
–
0.5
0.5
MOP SINK
1
2
2
2"
3
3
HI–LO DRINKING FOUNTAIN
1
0.5
0.5
1-1/2"
0.25
0.25
TOTALS
SERVICE CONNECTION SIZE
7.5
–
FLOOR CLEAN OUT
10.75
SAN.
VENT
C.W.
4"
4"
1"
PLUMBING CONTRACTOR'S NOTES
ALL OF THE PLUMBING/PIPING WORK IS NOT NECESSARILY SHOWN OR NOTED ON THESE
DRAWINGS. THE CONTRACTORS SHALL VISIT THE JOB SITE AND FIELD VERIFY ALL EXISTING
CONDITIONS RELATED TO THE WORK PRIOR TO BIDDING. THOSE ITEMS NOT SHOWN OR NOTED BUT
WHICH ARE DEEMED NECESSARY FOR REMOVAL OR RELOCATION BY OWNER OR HIS
REPRESENTATIVE SHALL BE PART OF HIS CONTRACT. THE SUBMISSION OF THE PROPOSALS SHALL
BE CONSIDERED EVIDENCE THAT THE CONTRACTORS HAVE VISITED THE SITE. NO EXTRA
PAYMENTS WILL BE ALLOWED THESE CONTRACTORS ON ACCOUNT OF EXTRA WORK MADE
NECESSARY BY HIS FAILURE TO VISIT THE JOB SITE.
PLUMBING CONTRACTOR TO PROVIDE BACKFLOW PREVENTER DEVICE IF REQUIRED PER CODE
AND/OR LANDLORD. COORDINATE WITH TEMPUR SEALY'S ARCHITECT/ENGINEER PRIOR TO
LOCATING BACKFLOW PREVENTER DEVICE.
�O
MS
HI -LO
D.F.
WC
WCO•
2"V
3"SS
4"55
1-1/2"V
M.
SANITARY PLAN
SCALE: 1/4' =1'=0'
ROUTE NEW 2" VENT TO EXISTING
MIN 3" VTR. ENSURE VTR IS 10'-0"
AWAY FROM ANY OUTSIDE AIR
INTAKE. COORDINATE WITH
LANDLORD.
2"V
2"V
PLUMBING CONTRACTOR TO CONNECT NEW 4"
SANITARY PIPING TO EXISTING SANITARY
PIPING. FIELD VERIFY EXACT SIZE, LOCATION
AND DIRECTION OF FLOW.
NOTE:
ALL NEW VENT PIPING PASSING
THROUGH CEILING PLENUM
AREA SHALL BE CAST IRON.
eq:
NEW4"
WCO
4"SS
4"SS
1/2"CW FROM TRAP
PRIMER.
PLUMBING KEYED NOTES®
O
NEW ELECTRIC WATER HEATER SUPPLIED AND INSTALLED BY PLUMBING CONTRACTOR. REFER TO SCHEDULE AND
RISER DIAGRAMS FOR ADDITIONAL INFORMATION. COORDINATE WITH ELECTRICAL CONTRACTOR. ROUTE DRAINAGE
LINES TO MOP SINK WITH AIR GAP PER LOCAL CODE.
® REPLACE EXISTING WATER CLOSET WITH NEW HANDICAPPED WATER CLOSET SUPPLIED AND INSTALLED BY
PLUMBING CONTRACTOR. REFER TO SCHEDULE FOR ADDITIONAL INFORMATION.
® REPLACE EXISTING LAVATORY WITH NEW HANDICAPPED LAVATORY SUPPLIED AND INSTALLED BY PLUMBING
CONTRACTOR. REFER TO SCHEDULE FOR ADDITIONAL INFORMATION.
PLUMBING CONTRACTOR TO CONNECT NEW 4" SANITARY PIPING TO EXISTING SANITARY PIPING OF ADEQUATE SIZE.
FIELD VERIFY EXACT SIZE, LOCATION AND DIRECTION OF FLOW.
® PLUMBING CONTRACTOR TO CONNECT NEW 3/4" COLD WATER PIPING TO EXISTING COLD WATER MAIN OF ADEQUATE
SIZE. FIELD VERIFY EXACT SIZE AND LOCATION. FIELD VERIFY LOCATION, SIZE, AND CONDITION OF EXISTING WATER
METER. COORDINATE ANY REPAIRS OF EXISTING MAIN AND METER WITH LANDLORD.
OPLUMBING CONTRACTOR TO ROUTE NEW 2" VENT LINE TO EXISTING VENT THRU ROOF OF ADEQUATE SIZE. VERIFY
EXISTING VTR IS LOCATED A MINIMUM OF 10 FT DISTANCE FROM ANY FRESH AIR INTAKE. FIELD VERIFY EXISTING
CONDITIONS. COORDINATE WITH LANDLORD ON EXACT LOCATION.
, NEW 3" FLOOR DRAIN PROVIDED AND INSTALLED BY PLUMBING CONTRACTOR. SEE SCHEDULE AND DETAIL FOR
ADDITIONAL INFORMATION.
O
NEW TRAP PRIMER SUPPLIED AND INSTALLED BY PLUMBING CONTRACTOR. REFER TO DETAIL AND SCHEDULE FOR
ADDITIONAL INFORMATION.
O NEW MOP SINK SUPPLIED AND INSTALLED BY PLUMBING CONTRACTOR. REFER TO SCHEDULE FOR ADDITIONAL
INFORMATION.
10 PLUMBING CONTRACTOR TO SUPPLY AND INSTALL A MANUAL MIXING VALVE (WATTS #LFUSG-B) AT LAVATORY AND
SET MAX DISCHARGE TEMPERATURE NOT TO EXCEED 110°F FROM REACHING PLUMBING FIXTURES PER CODE.
11 EXISTING PLUMBING FIXTURES NOT BEING REUSED ARE TO BE REMOVED. FIELD VERIFY EXACT LOCATIONS AND
SIZES. CAP WATER, SANITARY, AND VENT LINES BACK TO POINT OF REUSE. PATCH FLOOR/WALL BACK TO "LIKE NEW'
CONDITION.
COPY
Permit No. -lo 10-3
Plan review approval is subject to slurs and omission&
Approval of construction documents not authorize
the violation of any adopted code or ordnance. Receipt
of approved Field Copy and con toms is acknowledged:
BY: 7
Date: C b (2b I
City of Tukwila
BUILDING DIVISION
SEPAg l':; it PERMIT
s OU RE= FOR:
L4}echanical
._ I Electrical
0 Plumbing
as Piping
City of Tukwila
t.,I °;lLD' 1G DIVISION
0
7
HI -LO
D.F..
LAV
1
WATER PLAN
SCALE: 1/4' = 1'-0'
PLUMBING CONTRACTOR TO CONNECT
NEW COLD WATER PIPING TO EXISTING
COLD WATER MAIN. FIELD VERIFY EXACT
SIZE AND LOCATION.
EXISTING
SHUT-OFF
VALVE.
EXISTING
WATER METER.
FIELD VERIFY
LOCATION, SIZE,
AND CONDITION
SANITARY SEWER RISER
SCALE: 1/4' - ro•
T.P.R.V. 3/4"HW OUT
3/4"CW IN 0/ 1/2"CW
NEW 10 -GALLON
ELEC. WATER
HEATER
C
REVISIONS -~
No changes shall be made to the scope
Of work without prior approval of
Tukwila Building Division.
NOTE: Revisions will require a new plan submittal
and may include additional plan review fees.
NOTE:
ALL NEW HOT AND COLD
WATER LINES SHALL BE
INSULATED
SAFE PAN - MIN. 6"
CLEARANCE ALL
AROUND WATER
HEATER. SEE DETAIL.
DRAIN LINE FROM SAFE PAN
UNDER NEW WATER HEATER.
ROUTE TO MOP SINK PER
CODE. ENSURE 1" AIR GAP.
M.S.
HI -LO
D.F.
1/2'HW
p�1/2'CW
REVIEWED FOR
CODE COMPLIANCE
APPROVED
OCT 16 2011
�J(L
City Of Tukwila
BUILDING DIVISION
LAV.
DOMESTIC WATER RI
T.P.
1/2"CW
1/2"CW FROM
TRAP PRIMER.
1/2"HW
1/2"CW
W.C.
RECEIVED
ITV OF TUKWILA
OCT 0 6 2017
SCALE: 1/4' -1'a0'
IT CENTER
448 S. HILL ST.
LOS ANGELES, CA 90013
SUITE 808
310.437.8203 TEL
WWW.SARGARCH.COM
ARCHITECTURAL SEAL
10/3/2017
CONSULTANTS
THE
DIMENSION
GROUP
10755 SANDHILL ROAD
DALLAS, TEXAS 75238
0: 214-343-9400
dimensiongrp.com
DATE ISSUE
DATE
SUBMISSION
08/11/17
CD SET
A
09/21/17
10 03.17
REV1
REV,2
PROJECT NAME / LOCATION
17195 SOUTHCENTER
PARKWAY
TUKWILA,WA 98188
PROJECT INFORMATION
PROJECT NO. 1899-17
JLL PROJECT ID.
B Tukwila, WA_002
AREA: 2,964 S.F.
DRAWN BY: T.G.
CHECKED BY: T.H.
SHEET TITLE
PLUMBING
PLANS AND
RISERS
SHEET NUMBER
P6flolr3 P1.0
PLUMBING SYMBOLS
T.P.R.V.
TEMPERATURE PRESSURE
SAN.
SANITARY SEWER LINE
RELIEF VALVE
ST
STORM SEWER LINE
P.O.C.
POINT OF CONNECTION
V
VENT LINE
D.F.
ELECTRIC DRINKING FOUNTAIN
COLD WATER SUPPLY LINE
M.V.
MIXING VALVE
HOT WATER SUPPLY LINE
M.S.
MOP SINK
DQ
SHUT-OFF VALVE
LAV.
LAVATORY
— i\I
BACKFLOW PREVENTER
V.T.R.
VENT THRU ROOF
W.C.
WATER CLOSET
T.P.
TRAP PRIMER
A.F.F.
ABOVE FINISHED FLOOR
F.C.O.
FLOOR CLEAN OUT
B.F.F.
BELOW FINISHED FLOOR
W.C.O.
WALL CLEAN OUT
M
WATER METER
F.D.
FLOOR DRAIN
O
REMOTE READER FOR WATER
W.H.
WATER HEATER
METER
PLUMBING CONTRACTOR'S NOTES
ALL OF THE PLUMBING/PIPING WORK IS NOT NECESSARILY SHOWN OR NOTED ON THESE
DRAWINGS. THE CONTRACTORS SHALL VISIT THE JOB SITE AND FIELD VERIFY ALL EXISTING
CONDITIONS RELATED TO THE WORK PRIOR TO BIDDING. THOSE ITEMS NOT SHOWN OR NOTED BUT
WHICH ARE DEEMED NECESSARY FOR REMOVAL OR RELOCATION BY OWNER OR HIS
REPRESENTATIVE SHALL BE PART OF HIS CONTRACT. THE SUBMISSION OF THE PROPOSALS SHALL
BE CONSIDERED EVIDENCE THAT THE CONTRACTORS HAVE VISITED THE SITE. NO EXTRA
PAYMENTS WILL BE ALLOWED THESE CONTRACTORS ON ACCOUNT OF EXTRA WORK MADE
NECESSARY BY HIS FAILURE TO VISIT THE JOB SITE.
PLUMBING CONTRACTOR TO PROVIDE BACKFLOW PREVENTER DEVICE IF REQUIRED PER CODE
AND/OR LANDLORD. COORDINATE WITH TEMPUR SEALY'S ARCHITECT/ENGINEER PRIOR TO
LOCATING BACKFLOW PREVENTER DEVICE.
�O
MS
HI -LO
D.F.
WC
WCO•
2"V
3"SS
4"55
1-1/2"V
M.
SANITARY PLAN
SCALE: 1/4' =1'=0'
ROUTE NEW 2" VENT TO EXISTING
MIN 3" VTR. ENSURE VTR IS 10'-0"
AWAY FROM ANY OUTSIDE AIR
INTAKE. COORDINATE WITH
LANDLORD.
2"V
2"V
PLUMBING CONTRACTOR TO CONNECT NEW 4"
SANITARY PIPING TO EXISTING SANITARY
PIPING. FIELD VERIFY EXACT SIZE, LOCATION
AND DIRECTION OF FLOW.
NOTE:
ALL NEW VENT PIPING PASSING
THROUGH CEILING PLENUM
AREA SHALL BE CAST IRON.
eq:
NEW4"
WCO
4"SS
4"SS
1/2"CW FROM TRAP
PRIMER.
PLUMBING KEYED NOTES®
O
NEW ELECTRIC WATER HEATER SUPPLIED AND INSTALLED BY PLUMBING CONTRACTOR. REFER TO SCHEDULE AND
RISER DIAGRAMS FOR ADDITIONAL INFORMATION. COORDINATE WITH ELECTRICAL CONTRACTOR. ROUTE DRAINAGE
LINES TO MOP SINK WITH AIR GAP PER LOCAL CODE.
® REPLACE EXISTING WATER CLOSET WITH NEW HANDICAPPED WATER CLOSET SUPPLIED AND INSTALLED BY
PLUMBING CONTRACTOR. REFER TO SCHEDULE FOR ADDITIONAL INFORMATION.
® REPLACE EXISTING LAVATORY WITH NEW HANDICAPPED LAVATORY SUPPLIED AND INSTALLED BY PLUMBING
CONTRACTOR. REFER TO SCHEDULE FOR ADDITIONAL INFORMATION.
PLUMBING CONTRACTOR TO CONNECT NEW 4" SANITARY PIPING TO EXISTING SANITARY PIPING OF ADEQUATE SIZE.
FIELD VERIFY EXACT SIZE, LOCATION AND DIRECTION OF FLOW.
® PLUMBING CONTRACTOR TO CONNECT NEW 3/4" COLD WATER PIPING TO EXISTING COLD WATER MAIN OF ADEQUATE
SIZE. FIELD VERIFY EXACT SIZE AND LOCATION. FIELD VERIFY LOCATION, SIZE, AND CONDITION OF EXISTING WATER
METER. COORDINATE ANY REPAIRS OF EXISTING MAIN AND METER WITH LANDLORD.
OPLUMBING CONTRACTOR TO ROUTE NEW 2" VENT LINE TO EXISTING VENT THRU ROOF OF ADEQUATE SIZE. VERIFY
EXISTING VTR IS LOCATED A MINIMUM OF 10 FT DISTANCE FROM ANY FRESH AIR INTAKE. FIELD VERIFY EXISTING
CONDITIONS. COORDINATE WITH LANDLORD ON EXACT LOCATION.
, NEW 3" FLOOR DRAIN PROVIDED AND INSTALLED BY PLUMBING CONTRACTOR. SEE SCHEDULE AND DETAIL FOR
ADDITIONAL INFORMATION.
O
NEW TRAP PRIMER SUPPLIED AND INSTALLED BY PLUMBING CONTRACTOR. REFER TO DETAIL AND SCHEDULE FOR
ADDITIONAL INFORMATION.
O NEW MOP SINK SUPPLIED AND INSTALLED BY PLUMBING CONTRACTOR. REFER TO SCHEDULE FOR ADDITIONAL
INFORMATION.
10 PLUMBING CONTRACTOR TO SUPPLY AND INSTALL A MANUAL MIXING VALVE (WATTS #LFUSG-B) AT LAVATORY AND
SET MAX DISCHARGE TEMPERATURE NOT TO EXCEED 110°F FROM REACHING PLUMBING FIXTURES PER CODE.
11 EXISTING PLUMBING FIXTURES NOT BEING REUSED ARE TO BE REMOVED. FIELD VERIFY EXACT LOCATIONS AND
SIZES. CAP WATER, SANITARY, AND VENT LINES BACK TO POINT OF REUSE. PATCH FLOOR/WALL BACK TO "LIKE NEW'
CONDITION.
COPY
Permit No. -lo 10-3
Plan review approval is subject to slurs and omission&
Approval of construction documents not authorize
the violation of any adopted code or ordnance. Receipt
of approved Field Copy and con toms is acknowledged:
BY: 7
Date: C b (2b I
City of Tukwila
BUILDING DIVISION
SEPAg l':; it PERMIT
s OU RE= FOR:
L4}echanical
._ I Electrical
0 Plumbing
as Piping
City of Tukwila
t.,I °;lLD' 1G DIVISION
0
7
HI -LO
D.F..
LAV
1
WATER PLAN
SCALE: 1/4' = 1'-0'
PLUMBING CONTRACTOR TO CONNECT
NEW COLD WATER PIPING TO EXISTING
COLD WATER MAIN. FIELD VERIFY EXACT
SIZE AND LOCATION.
EXISTING
SHUT-OFF
VALVE.
EXISTING
WATER METER.
FIELD VERIFY
LOCATION, SIZE,
AND CONDITION
SANITARY SEWER RISER
SCALE: 1/4' - ro•
T.P.R.V. 3/4"HW OUT
3/4"CW IN 0/ 1/2"CW
NEW 10 -GALLON
ELEC. WATER
HEATER
C
REVISIONS -~
No changes shall be made to the scope
Of work without prior approval of
Tukwila Building Division.
NOTE: Revisions will require a new plan submittal
and may include additional plan review fees.
NOTE:
ALL NEW HOT AND COLD
WATER LINES SHALL BE
INSULATED
SAFE PAN - MIN. 6"
CLEARANCE ALL
AROUND WATER
HEATER. SEE DETAIL.
DRAIN LINE FROM SAFE PAN
UNDER NEW WATER HEATER.
ROUTE TO MOP SINK PER
CODE. ENSURE 1" AIR GAP.
M.S.
HI -LO
D.F.
1/2'HW
p�1/2'CW
REVIEWED FOR
CODE COMPLIANCE
APPROVED
OCT 16 2011
�J(L
City Of Tukwila
BUILDING DIVISION
LAV.
DOMESTIC WATER RI
T.P.
1/2"CW
1/2"CW FROM
TRAP PRIMER.
1/2"HW
1/2"CW
W.C.
RECEIVED
ITV OF TUKWILA
OCT 0 6 2017
SCALE: 1/4' -1'a0'
IT CENTER
448 S. HILL ST.
LOS ANGELES, CA 90013
SUITE 808
310.437.8203 TEL
WWW.SARGARCH.COM
ARCHITECTURAL SEAL
10/3/2017
CONSULTANTS
THE
DIMENSION
GROUP
10755 SANDHILL ROAD
DALLAS, TEXAS 75238
0: 214-343-9400
dimensiongrp.com
DATE ISSUE
DATE
SUBMISSION
08/11/17
CD SET
A
09/21/17
10 03.17
REV1
REV,2
PROJECT NAME / LOCATION
17195 SOUTHCENTER
PARKWAY
TUKWILA,WA 98188
PROJECT INFORMATION
PROJECT NO. 1899-17
JLL PROJECT ID.
B Tukwila, WA_002
AREA: 2,964 S.F.
DRAWN BY: T.G.
CHECKED BY: T.H.
SHEET TITLE
PLUMBING
PLANS AND
RISERS
SHEET NUMBER
P6flolr3 P1.0