HomeMy WebLinkAboutOrd 1134 - Water Main Installation and Extension (Repealed by Ord 1766)ORDINANCE NO 1134
SECTION 6 AMENDED BY 1213
REPEALED BY 1766
AN ORDINANCE OF THE CITY OF TUKWILA, WASHINGTON,
RELATING TO SIZES, DESIGN STANDARDS, CONSTRUCTION,
AND QUALITY OF MATERIALS FOR WATER MAIN INSTALLA-
TION AND EXTENSION; AMENDING SECTION 6 OF ORDINANCE
#264 AND REPEALING ORDINANCE #383.
NOW, THEREFORE, THE CITY COUNCIL OF THE CITY OF TUKWILA,
WASHINGTON, DO ORDAIN AS FOLLOWS:
COUNCIL ACTION
MEETING ONE I AG IT M I ACTION
TYPE
VW 'b/a�, g I R 1
14 I I//5\ gb I P
I
Section 6 of Ordinance #264 is hereby amended to read as follows:
Section 6. The current requirements of The Tukwila Municipal Code,
The Tukwila Public Works Department, The Tukwila Fire Department, The Rules
and Regulations of the Washington State Department of Social and Health
Services, The Seattle /King County Plumbing Code, American Water Works Association
Standards, The American Public Works Association Standards shall be met and
apply to any and all water main installations, extensions, service connection,
irrigation sprinkler connections, hydrant connection, fire sprinkler and fire
main connections, and branches hereinafter installed in the City of Tukwila.
The following minimum sizes, standards of design, construction and quality of
material shall apply:
(a) Residential water service connections shall use standard
galvanized pipe, copper tubing, or plastic pipe or tubing approved by the
current Seattle /King County Plumbing Code for sizes up to and including
3/4 inch in size.
(b) Water service connections to other than single family
residential shall be a minimum of 1" and shall use standard galvanized
iron or steel pipe, copper tubing or pipe, or class 52 ductile iron pipe.
(c) All pipe and fittings shall be rated for a minimum working
pressure of 150 pounds per square inch plus for a surge allowance of 100
pounds per square inch.
(d) All mains, extensions and appurtenances thereto shall be
constructed of a minimum class 52 ductile iron pipe and approved fittings.
(e) In areas zoned for industry or commerce, mains shall be a
minimum of 8 inches in diameter (I.D.) unless a larger size is required by
the Public Works Director.
(f) In areas zoned residential, mains shall be a minimum of 6 inches
in diameter (I.D.) unless a larger size is required by the Public Works Director.
(g) All plans and specifications for water main extensions and
branches must be presented to the City of Tukwila Public Works Department for
review and approval.
(h) Permits to install water mains, extensions, valves, hydrants,
fire sprinkler connections, fire main, irrigation sprinkler connections and
branches shall be secured from the City of Tukwila Public Works Department
before commencing any installations.
(i) A street repair bond to assure restoration may be required by
the Public Works Director prior to issuance of a permit.
(j) Application for water service connections shall be filled with
and approved by the Public Works Director before the installation of a water
service connection is made.
PASSED BY THE CITY COUNCIL OF THE CITY OF TUKWILA, WASHINGTON,
at a regular meeting thereof this S day of j, 1979.
Apfr<oved as to Form:
Ordinance No. 383 is hereby repealed.
3 pa- 44 1VALe_
ty Attc7rrrey, Lawrence E. Hard
Published: Record Chronicle, November 9, 1979
ATTEST:
Mayor
-2-
41 1 awe/
C :17,7
City Clerk