HomeMy WebLinkAboutPP - 575 ANDOVER PARK WEST BLDG #3 - S.C. CORPORATE SQUARE BLDG - PERMITS AND PLANS575 ANDOVER PARK WEST BLDG #3
ASSOCIATED PERMITS
89-414
89-023
89-025
89-423
89-422
89-029
5885
5 5 5 _; 75--
/ _
CONTRACTOR'S MATERIAL & TEST CERTIFICATE
SPRINKLER SYSTEMS . WATER SPRAY SYSTEMS
1 PART "A" GENERAL
PROCEDURE
UPON COMPLETION OF WORK, INSPECTION AND TESTS SHOULD BE MADE BY CONTRACTOR'S REPRESENTATIVE AND WITNESSED BY AN OWNER'S REPRESENTATIVE
ALL DEFECTS SHOULD BE CORRECTED AND SYSTEM LEFT IN SERVICE BEFORE CONTRACTOR'S MEN FINALLY LEAVE THE JOB.
A CERTIFICATE SHOULD BE FILLED OUT AND SIGNED BY BOTH REPRESENTATIVES. COPIES SHOULD BE PREPARED FOR INSPECTING AUTHORITIES, OWNER AND
CONTRACTOR. IT IS UNDERSTOOD THE OWNER'S REPRESENTATIVE'S SIGNATURE IN NO WAY PREJUDICES ANY CLAIM AGAINST CONTRACTOR FOR FAULTY
MATERIAL, POOR WORKMANSHIP OR FAILURE TO COMPLY WITH INSPECTING AUTHORITY'S REQUIREMENTS OR LOCAL ORDINANCES.
PROPERTY NAME
Southcenter Corporate Square Ph II
PROPERTY ADDRESS
FILE
527 Andover Park West, Tukwila, WA
ACCEPTED BY INSPECTION AUTHORITY ('S) NAMES
PLANS
INSTRUC•
TIONS
TEST
DESCRIP-
TION
ADDRESS
1 DATE
INSTALLATION CONFORMS TO ACCEPTED PLANS
EQUIPMENT USED 18 APPROVED
IF NO, STATE DEVIATIONS
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION OF CONTROL
VALVES AND CARE OF THIS NEW EQUIPMENT
IF NO, EXPLAIN
HAS A COPY OF INSTRUCTION AND MAINTENANCE CHART BEEN LEFT
AT PLANT
1F NO, EXPLAIN
YE$ 0
YES ❑
NO 0
NO 0
YE8 0
NO 0
YES ❑
NO ❑
FLUSHING: Flow the required rate until ma1Sa are clear as Indicated by no ccUectton of foreign material in burlap bap at outlets inch as hydrants and
Flush at Bows not leas than 750 GPM for 6 -loch pipe and smaller, 1000 GPM for 8 -loch, 1500 GPM for 10 -loch. 2000 CPM for 12 -Inch. Where supply
imp ooved subsequent toproduce tloatallattm rate.ed flow obtain maximum available by using properly sized discharge deviate Piping to be refluahed when water supply la
HYDROSTATIC: Hydrostatic teat should be made at not less than 200 PSI for two hours or 50 PSI above static pressure In excess of 150 PSI. DlferentW
dry -pipe valve clappers should be left open during test to prevent damage. All above ground piping leakage should be stopped.
LEAKAGE. New pipe lad with rubber psketed Joints should, if the workmsn.hlp Is stisfactory, have no leakage at the pints. Unsatisfactory amounts
of leakage usually result from twisted, pinched or cut pskets. However, some leakage might result from mall anoints of grit or small Imperfection..
The amount of leakage at the John. should not exceed 2 quarts per hour per 100 pints Irrespectively of pipe diameter. The leakage should be distributed
over all Joint., It such leakage occurs at a few Joints the installation should be considered unsatisfactory and necessary repairs made. New pipe laid
with caulked lead or lead-.ubstltute Joints should, U the workmanship is satisfactory, hove little or no leakage at the Joints. Any Joint having leakage or
morethana•allght drip' or' weeping' should be repaired, Leakage should not exceed 1 oz. (liquid measure) per hour per Inch of pipe Mammas per Joint.
The leakage should be distrtbutedoverallInstallationus. If such leakage occurs almost entirely ata few Joints, the Installationshould be considered unsatisfactory
and necessary repairs made.
PNEUMATIC: Establish 40 PSI air pressure and measure pressure drop which should not exceed 11/2 PSI In 24 hours. Test pressure make at normal
water level and air pressure, and measure air pressure drop which should not exceed 1 1/2 PSI in 24 hours.
blow -offs.
LOCATION
UNDER-
GROUND
PIPES
AND
JOINTS
TESTS
REQUIRED
FEEDS BLDGS.
PART "B" - UNDERGROUND PIPING
Southcenter Corporate Square Ph II, Andover Park West, Bldgs. 1,2,3,4
PIPE TYPE AND CLASS
TYPE JOINT
Ductile Iron
CONFORMS TO
IF NO, EXPLAIN
STANDARD
JOINTS NEEDING ANCHORAGE CLAMPED, STRAPPED OR BACKED IN ACCORDANCE
WITH STANDARD
IF NO, EXPLAIN
YES 0
YE8 ❑
FLUSHING
TESTS
FLUSHING
HYDROSTATIC LEAKAGE
NEW UNDERGROUND PIPING FLUSHED ACCORDING TO
BY (COMPANY) BY YES ❑
HOW WAS FLUSHING, FLOW OBTAINED
PUBLIC WATER 0
THROUGH WHAT TYPE OPENING
LEAD-INS FLUSHED ACCORDING TO STANDARD
BY (COMPANY) YES ❑
TANK OR RESERVOIR 0 FIRE PUMP 0
HYD. BUTT. ❑ OPEN PIPE 0
HOW WAS FLUSHING FLOW OBTAINED
PUBLIC WATER 0
THROUGH WHAT TYPE OPENING
TANK OR RESERVOIR 0 FIRE PUMP 0
Y CONN. TO FLANGE & SPIGOT 0 OPEN PIPE 0
•
HYDROSTATIC
TEST
•
i� NEW UNDERGROUND PIPING HYDROSTATICALLY TESTED AT
P. S.1. FOR HOURS
LEAKAGE
TEST
TOTAL MOUNT OF LEAKAGE MEASURED
O'er' HOURS
ALLOWABLE LEAKAGE
GALS. HOURS
HYDRANTS
NUMBER INSTALLED
TYPE AND MAKE
ALL OPERATE SATISFACTORILY
YES ❑ NO ❑
CONROL
VALVES
WATER CONTROL VALVA LEFT WIDE OPEN • YE8 ❑ NO 0
IF NO, STATE REASON
REMARKS
DATE LEFT IN SERVICE
PARTS A & 1
NAME OF SPRINKLER CONTRACTOR
TIT.R OF i 1 i t i ac
FOR PROPERTY OWNER (SIGNED) TITLE
SIGNATURES
FOR SPRINKLER CONTRACTOR (SIGNED)
Tim Collins ppippelayyer
DATE
PART "C" — SPRINKLER & WATER SPRAY ABOVE GROI3ND PI NG (FILL OUT SEPARATE PART "C" FOR EACH RISER)
LOCATION
SERVES BLDG.
TESTS
REQUIRED
1 HYDROSTATIC TEST OF ALL PIPING
2 PNEUMATIC TEST OF ALL DRY PIPING
3 EQUIPMENT OPERATION TESTS OF ALL EQUIPMENT
SPRINKLERS
OR
SPRAY
NOZZLES
MAKE
MODEL
SIZE
QUANTITY
TEMPERATURE
RATING
PIPE AND
FITTINGS
MATERIAL AND MOND CONFORMS TO STANDARD 1
IF NONE, EXPLAIN
ALARM VALVE
OR FLOW
INDICATOR
ALARM DEVICE
MAKIMUM TIME TO OPERATE THROUGH TEST PIM
TYPE
MAKE
MODEL
MIN.
BEC.
DRY
PIPE
VALVES
OPERATING TENT RESULTS
WATER
AIR
TRIP
TIME
MAKE
MODEL
SER.
TIME TO TRIP
THROUGH TEST PIPE
PRESS.
PRESS.
POINT
WATER
REACHED
ALARM
OPERATED
NO.
WITHOUT
Q. O. D.
WITH
Q. O. D.
AIS
PRESS.
TEST
OUTLET
PROPERLY
MIN.
SEC.
MIN.
SEC.
P.8.1.
P.S.L
P.8.1,
MIN.' SEC.
YES 1 NO
1F NO, EXPLAIN
DELUGE
&
PREACTION
VALVES
OPERATION PNEUMATIC 0 ELECTRIC 0 HYDRAULIC 0
PIPING SUPERVISED YES 0 NO 0 DETECTING MEDIA SUPERVISED YES 0 NO 0
DOES VALVE OPERATE FROM THE MANUAL TRIP AND/OR REMOTE CONTROL STATIONS YE8 0 NO 0
1S THERE AN ACCESSIBLE FACILITY IN EACH CMCUIT FOR TESTING
IF NO, EXPLAIN YES 0 NO 0
MAKE
MODEL
DOES EACH CIRCUIT OPERATE
SUPERVISION LOBS ALARM
DOES EACH CIRCUIT OPERATE
VALVE RELEASE
MAXIMUM TIME TO
OPERATE RELEASE
YE8
NO
YEN
NO
MIN.
SEC.
TESTS
ALL PIPING HYDROSTATICALLY TESTED AT PSI FOR 11013118
DRY PIPING PNEUMAT CALLY TESTED YES D NO0
EQUIPMENT OPERATE PROPERLY YES ❑ NOD
IF NO STATE REASON
41 RAIPJ TEST: READING OF GAGE LOCATED NEAR WATER SUPPLY TEST PIPE: RESIDUAL PRESSURE V'FTH VALVE IN TEST PIPE OPEN WIDE: '
STATIC PRESSURE PSI PBI
BLANK
TESTING
GASKETS
NUMBER USED
LOCATIONS
NUMBER REMOVED
REMARKS
DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN.
PART "C"
SIGNATURES
NAME OF SPRINKLER CONTRACTOR
FOR P OPERTY R BIG D) TITLE
'i('11,l V / (-006') N..
FOR SPRINKLER CONTRACTOR (SIGNED)
CONTRACTOR'S MATERIAL & TEST CERTIFICATE
SPRINKLER SYSTEMS - WATER SPRAY SYSTEMS
PART "A" GENERAL
PROCEDURE
UPON COMPLETION OF WORK, INSPECTION AND TESTS SHOULD BE MADE BY CONTRACTOR'S REPRESENTATIVE AND WITNESSED BY AN OWNER'S REPRESENTATIVE.
ALL DEFECTS SHOULD BE CORRECTED AND SYSTEM LEFT IN SERVICE BEFORE CONTRACTOR'S MEN FINALLY LEAVE THE JOB.
A CERTIFICATE SHOULD BE FILLED OUT AND SIGNED BY BOTH REPRESENTATIVES. COPIES SHOULD BE PREPARED FOR INSPECTING AUTHORITIES, OWNER AND
CONTRACTOR. IT IS UNDERSTOOD THE OWNER'S REPRESENTATIVE'S SIGNATURE IN NO WAY PREJUDICES ANY CLAIM AGAINST CONTRACTOR FOR FAULTY
MATERIAL, POOR WORKMANSHIP OR FAILURE TO COMPLY WITH INSPECTING AUTHORITY'S REQUIREMENTS OR LOCAL ORDINANCES.
PROPERTY NAME �/
(` mo//.
c ----/9`g
� •i %J/.,42_n,,�l" -2rtr. 77
DATE
5;.:1.9 ,
PROPERTY ADDRESS
—7 A' !a K?/(57
ACCEPTED BY INSPECTION AUTHORITY ('5) NAMES
/
ir` ,:v 1
T ' f- '4'
PLANS
ADDRESS �-
�!/� U , li -l/c';'
INSTALLATION CONFORMS TO ACCEPTED PLANS YES 5 NO 0
EQUIPMENT USED IS APPROVED YES.' NO 0
IF NO, STATE DEVIATIONS
INSTRUC-
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION OF CONTROL
VALVES AND CARE OF THIS NEW EQUIPMENT YES 5- NO 0
IF NO, EXPLAIN
TIONS
HAS A COPY OF INSTRUCTION AND MAINTENANCE CHART BEEN LEFT YES ,, NO 0
AT PLANT
IF NO, EXPLAIN
FLUSHING: Flow the required rate untU mains are clear as indicated by no collection of foreign material in burlap bags at outlets such as bydrums and
TEST
blow -offs. .
Flush at flows not less than 750 GPM for 6 -inch pipe and smaller, 1000 GPM for 11 -inch. 1500 GPM for 10 -inch. 2030 GPM for 12 -inch. Where supply
canna produce stipulated flow rate, obtain maximum avallable by using properly sized discharge devices. Piping to be reflushed when water supply Is
improved subsequent to installation.
HYDROSTATIC: Hydrostatic test should be made at not less than 200 PSI for two hours or 50 PSI above static pressure to excess of 150 PSL Differential
DES... 1 -
dry -pipe valve clappers should be left open during test to prevent damage. Alt above ground piping leakage should be stopped.
LEAKAGE: New pipe laid with rubber gasketed joints should, if the workmanship is satisfactory, have an leakage at the pinta. Unsatisfactory amounts
TION
of leakage usually result from twisted, pitched or cut gaskets. However, some leakage might result from small amounts of grit or small imperfections.
The imam/ of leakage at the Joints should not exceed 2 quarts per hour per 100 joints irrespectively of pipe diameter. The leakage should be dlstrtbu ted
over aU Joints. If such leakage occurs at a few joints the installation should be considered unsatisfactory and necessary repairs made. New pipe laid
with caulked lead or lead -substitute Joints should, if the workmanship is satisfactory, have little or no leakage at the Joints. Any joint having leakage or
more thana'slight drip' or' weeping' should be repaired. Leakage should not exceed 1 ox. (liquid measure) per hour per inch of pipe diameter per joint.
The leakage should be distributed over all )Dints. If such leakage occur. almost entirely at a few )Dints, the installation should be considered unaattatactory
and necessary repairs made.
PNEUMATIC: Establish 40 PSI air pressure std measure pressure drop which should not exceed 11/2 PSI in 24 hours. Test pressure tanks at normal
water level and air pressure, and measure air pressure drop which should not exceed 1 1/2 PSI in 24 hours.
PART "B" — UNDERGROUND PIPING
LOCATION
FEEDS BLDGS.
/ — -.3 -4-
PIPE TYPE AND CLASS
TYPE JOINT7-
UNDER-
; 7 /_.e
% .,-....-77/-e...„,.
X-.1-1-- 7 /�..1/
CONFORMS TO /I".-%.27:4: STANDARD YES Ela, NO 0
GROUND
PIPES
IF NO, EXPLAIN
AND
JOINTS NEED, 91IQAAGE CLAMPED, STRAPPED OR BACKED IN ACCORDANCE yES �' NO 0
WITH /--" STANDARD
JOINTS
IF NO, EXPLAIN
TESTS
REQUIRED
FLUSHING .- HYDROSTATIC LEAKAGE
NEW UNDERGROUND PIPING FLUSHED ACCORDING TO ,„./2774.-%7/ .-?,04 STANDARD YES etr
BY (COMPANY)
HOW WAS FLUSHING FLOW OBTAINED
PUBLIC WATER g TANK OR RESERVOIR 0 FIRE PUMP 0
FLUSHING
THROUGH WHAT TYPE OPENING
HYD. BUTT. 0 OPEN PIPE 0
LEAD-INS FLUSHED ACCORDING TO "27,;%P/c STANDARD YES 0
TESTS
BY (COMPANY)
HOW WAS FLUSHING FLOW OBTAINED
PUBLIC WATEP 51 TANK OR RESERVOIR 0 FIRE PUMP 0
THROUGH WHAT TYPE OPENING
Y CONN. TO FLANGE & SPIGOT OPEN PIPE .❑
•
HYDROSTATIC(')
TEST
ALL NEW UNDERGROUND PIPING HYDR ATICALLY TESTED AT
P. S. I. FOR HOURS
LEAKAGE
TEST
TOTAL MOUNT OF LEAKAGE MEASURED
GALS. HOURS
ALLOWABLE LEAKAGE
GALS. HOURS
HYDRANTS
NUMBER INSTALLED
_R /,A4', --e
TYPE AND MAKE
ALL OPERATE SATISFACTORILY
YES ❑ NO ❑
CONROI
VALVES
WATER CONTROL VALVES LEFT WIDE OPEN YES, NO 0
IF NO, STATE REASON
REMARKS
DATE LEFT IN SERVICE '
U 'a 5 ;0
PARTS A & 8
NAME OF SPRINKLER CONTRACTOR
FOR PROPERTY OWNER (SIGNED) TITLE
SIGNATURES
FOR SPRINKLER CONTRACTOR (SIGNED)
DATE
PART "C" - SPRINKLER & WATER SPRAY ABOVE GROUND PIPING (FILL OUT SEPARATE PART "C^ FOR EACH RISER)
LOCATION
SERVES BLDGS.
TESTS
REQUIRED
1 HYDROSTATIC TEST OF ALL PIPING
2 PNEUMATIC TEST OF ALL DRY PIPING
3 EQUIPMENT OPERATION TESTS OF ALL EQUIPMENT
SPRINKLERS
OR
SPRAY
NOZZLES
MALE
MODEL.
SIZE
QUANTITY
TEMPERATURE
RATING
PIPE AND '
FITTINGS
MATERIAL AND KIND CONFORMS TO STANDARD
IF NONE, EXPLAIN
ALARM VALVE
OR FLOW
INDICATOR
ALARM DEVICE
MAXIMUM TIME TO OPERATE THROUGH TEST PIPE
TYPE I
MAKE
MODEL
MIN.
SEC.
DRY
PIPE
VALVES
OPERATING TEST RESULTS
WATER
PRESS.
AIR
PRESS.
TRIP
POINT
AIR
PRESS,
TIME
WATER
REACHED
TEST
OUTLET
ALARM
OPERATED
PROPERLY
MAKE
MODEL
SER.
TIME TO TRIP
THROUGH TEST PIPE
NO.
WITHOUT
Q. O. D.
WITH
Q. O. D.
MIN.
SEC.
MIN.
SEC.
P. 3.1.
P.B.I.
P.S.I.
MIN, SEC.
YES NO
IF NO, EXPLAIN
DELUGE
8`
PREACTION
VALVES
OPERATION PNEUMATIC ❑ ELECTRIC❑ HYDRAULIC 0
PIPING SUPERVISED YES 0 NO 0 DETECTING MEDIA SUPERVISED YES 0 NO ❑
DOES VALVE OPERATE FROM THE MANUAL TRIP AND/OR REMOTE CONTROL STATIONS YES 0 NO 0
IS THERE AN ACCESSIBLE FACILITY IN EACH CIRCUIT FOR TESTING YES ❑ NO 0
IF NO, EXPLAIN
MAKE
MODEL
DOES EACH CIRCUIT OPERATE
SUPERVISION LOSS ALARM
DOES EACH CIRCUIT OPERATE
VALVE RELEASE
MAXIMUM TIME TO
OPERATE RELEASE
YES
NO
YES
NO
MIN.
SEC.
TESTS
ALL PIPING HYDROSTATICALLY TESTED AT PSI FOR HOURS
DRY PIPING PNEUMATICALLY TESTED YES 0 1400
EQUIPMENT OPERATE PROPERLY YES ❑ NO❑
IF NO, STATE REASON
DRAIN TEST: READING OF GAGE LOCATED NEAR WATER SUPPLY TEST PIPE: RESIDUAL PRESSURE wITH VALVE IN TEST PIPE OPEN WIDE:
STATIC PRESSURE PSI PSI
BLANK
TESTING
GASKETS
NUMBER USED
LOCATIONS
NUMBER REMOVED
REMARKS
DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN,
PART „C,.
SIGNATURES
NAME OFSPRIN1G.ER CONTRACTOR �
R PROP OWNER (SIGNED) TITLE
, p, f: (4z -/%r; f., �� ( ,
- ..----F-Pa sr 3
FOR SPRINKLER CONTRACTOR (SIGNED)
Ip
Washington State Fire Marshal
Insurance Building AQ -21
sime
Olympia, Wa. 98504
CONTRACTOR'S MATERIAL & TEST CERTIFICATE FOR ABOVE GROUND PIPING
PROCEDURE
Upon completion of work, inspection and tests shall be made by the contractor's representative and witnessed by an owner's representative. All defects shall be corrected
and system left in service before contractor's personnel finally leave the job.
A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners and contractor. It is understood the owner's
representative's signature in no way prejudices any claim against contractor for faulty material, poor workmanship. or failure to comply with approving authority's requirements
or local ordinances.
PROPERTY NAME
S'q�•i�1-
PROPERTY ADDRESS
1.
PLANS
DATE
ACCEPTED BY APPROVIN,.a AUTHORITY('S) NAMES
ADDRESS
7 -tea X9,9
kLL• • /? / i --e
•
L•AL-Iti.• /? fi67,
)-r- ('7; ---
INSTALLATION CONFORMS TO ACCEPTED PLANS
EQUIPMENT USED IS APPROVED
IF NO, STATE DEVIATIONS
9'YYES 0 NO
Its YES 0 NO
2.
INSTRUCTIONS
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION
OF CONTROL VALVES AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT?
IF NO, EXPLAIN
lit YES ❑ NO
HAVE COPIES OF APPROPRIATE INSTRUCTIONS AND CARE AND MAINTENANCE CHARTS AND NFPA 13A
BEEN LEFT ON PREMISES?
IF NO, EXPLAIN
ISYES 0 NO
3• LOCATION
OF SYSTEM
SUPPLIES BLDGS.
4.
SPRINKLERS
5 PIPE AND
FITTINGS
MAKE
MODEL
YEAR OF
MANUFACTURE
ORIFICE
SIZE
QUANTITY
G /1
K/,raf/,P
-94`b
y%iJ l
T -3
/9:4 9
/3Z—
TEMPERATURE
RATING
2 -z
/6_3 -
/
GS/
PIPE CONFORMS TO
FITTINGS CONFORM TO
F NO, EXPLAIN
STANDARD
TANDARD
TES
YES
0 NO
0 NO
6. ALARM
VALVE
OR FLOW
INDICATOR
ALARM DEVICE
MAXIMUM TIME TO OPERATE THROUGH TEST PIPE
TYPE
MAKE
MODEL
MIN.
SEC.
>- I NA• 41 /1
?'s?OJ
7.
DRY PIPE
OPERATING
TEST
DRY VALVE
O.O.D.
MAKE
MODEL
SERIAL NO.
MAKE
MODEL
SERIAL NO.
`� e
J,, , •
TIME TO TRIP
THRU TEST PIPE
1
WATER
PRESSURE
-
AIR
PRESSURE
TRIP POINT
AIR PRESSURE
TIME WATER
REACHED
TEST OUTLET
ALARM
OPERATED
PROPERLY
MIN.
SEC.
PSI
PSI
Psi
MIN.
SEC.
YES
NO
Without
O.O.D.
6
/ 4
3
L'9
9
16
With
O.O.D.
IF NO, EXPLAIN
S.F.M. 223A (Rev. 3183) a1SSSA-564
(OVER)
8.
DELUGE &
PREACTION
VALVES
OPERATION
L/NEUMATIC
PIPING SUPERVISED
0 ELECTRIC 0 HYDRAI�
DETECTING MEDIA SUPERVISED
0 YES 0 NO
y
DOES VALVE OPERATE FROM THE MANUAL TRIP AND/OR REMOTE CONTROL •NS
❑ YES
❑ YES
❑ NO
❑ NO
IS THERE AN ACCESSIBLE FACILITY IN EACH CIRCUIT FOR TESTIN
0 YES ❑ NO
ACH CIRCUIT OPERATE
MAKE MODEL
SUPERVISION LOSS ALARM
NO
VES
IF NO, EXPLAIN
DOES EACH CIRCUIT
OPERATE VALVE RELEASE
MAXIMUM TIME TO
OPERATE RELEASE
VES
NO
MIN.
SEC
TEST
DESCRIPTION
9.
TESTS
HYDROSTATIC: Hydrostatic shall be made at not Tess than 200 psi (13.6 bars) fo two hours or 50 psi (3.4 bars) above static pressure in excess of 150 psi
(10.2 bars) for two hours. Differential dry -pipe valve clappers shall be left open during test to prevent damage. All aboveground piping leakage shall be stopped.
FLUSHING: Flow the required rate until water is clear as indicated by no collection of foreign material in burlap bags at outlets such as hydrants and blow -offs.
Flush at flows not Tess than 400 GPM (1514 L/min) for 4 -inch pipe, 600 GPM (2271 L/min) for 5 -inch pipe, 760 GPM (2839 L/min) for 6 -inch pipe, 1000 GPM
(3785 L / min) for 8 -inch pipe, 1500 GPM (5678 L /min) for 10 -inch pipe and 2000 GPM (7570 L /min) for 12 -Inch pipe. When supply cannot produce stipulated flow
rates, obtain maximum available.
PNEUMATIC: Establish 40 psi (2.7 bars) air pressure and measure drop which shall not exceed 1-15 psi (0.1 bars) in 24 hours. Test pressure tanks at normal
water level and air pressure and measure air pressure drop which shall not exceed 1-15 psi (0.1 bars) in 24 hours.
IF NO, STATE REASON
ALL PIPING HYDROSTATICALLY TESTED AT ar.2�71PSI FOR 2 HRS.
B
DRY PIPING. PNEUMATICALLY TESTED Y S 0 NO
EOUIPMENT OPERATES PROPERLY U'YES 0 NO
DRAIN
TEST
READING OF GAGE LOCATED NEAR WATER SUPPLY TEST PIPE:
STATIC PRESSURE. /Yaa' PSI
RESIDUAL PREpRE WITH VALVE IN TEST PIPE OPEN WIDE
�2 PSI
Underground mains and lead In connections to system risers flushed before connection made to sprinkler piping.
OT:HER EXPLAIN
VERIFIED BY COPY OF THE U FORM NO. 85B.
FLUSHED BY INSTALLER OF UNDERGROUND
SPRINKLER PIPING
10.
BLANK TESTING
GASKETS
11.
WELDING
NUMBER USED
WELDING PIPING
LOCATIONS
Er,
,., YES 0 NO
AYES ❑ NO
NUMBER REMOVED
❑ YES ❑ NO
IF YES...
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT WELDING PROCEDURES COMPLY WITH THE
REQUIREMENTS OF AT LEAST AWS D10.9, LEVEL AR -3
DO YOU CERTIFY THAT THE WELDING WAS PERFORMED BY WELDERS QUALIFIED IN COMPLIANCE
WITH THE REQUIREMENTS OF AT LEAST AWS D10.9, LEVEL AR -3
DO YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANCE WITH A DOCUMENTED OUALITY
CONTROL PROCEDURE TO INSURE THAT ALL DISCS ARE RETRIEVED, THAT OPENINGS IN PIPING ARE
SMOOTH, THAT SLAG AND OTHER WELDING RESIDUE ARE REMOVED, AND THAT THE .INTERNAL
' DIAMETERS OF PIPING ARE NOT PENETRATED
❑ YES ❑ NO
❑ YES ❑ NO
❑ YES 0 NO
12. HYDRAUUC
DATA
NAMEPLATE
13.
REMARKS
NAMEPLATE PROVIDED
0 YES LJ NO
IF NO, EXPLAIN
DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN:
14.
SIGNATURES
NAME OF SPRINKLER CONTRACTOR
/,e /1 �.c P1-4! 4/ ,e-1,/‹.);
TESTS WITNESSED BY
FOR PROPERTY OWNER (SIGNED) TITLE
1
TITLE
FORRPRINKLER CONTRACTOR (SIGNED)
AN
ADDITIONAL EXPLANL
/,lrTl, N
DATE
DATE •
854 Beck -554-
15. CERTIFICATION
This is to certify that this automatic sprinkler system has been installed in accordance with the standards adopted by the
Washington State Fire Marshal and N.F.P.A. Standard 13.
Name of Firm
Mailing Address
Name Title Date
(Signature of Firm Official)
WHEN ALL APPLICABLE ITEMS THROUGH 15 HAVE BEEN COMPLETED
THIS ORIGINAL FORM SHALL BE RETURNED TO THE STATE FIRE MARSHAL'S OFFICE
16. CONFIRMATION OF SPRINKLER SYSTEM INSTALLATION
Name Title Date
State Fire Marshal Representative
Acceptable: ❑ YES ❑ NO
17. COMMENTS•
ADDITIONAL EXPLANATION AND NOTES
reftWashington State Fire Marshal 0
,.,'Insurance Building AQ -21
Olympia, Wa. 98504
CONTRACTOR'S MATERIAL & TEST CERTIFICATE FOR U NDERGROUND PIPING
PROCEPURE
Upon completion of work. inspection and tests shall be made by the contractor's representative and witnessed by an owner's representative. All defects shall be corrected
and system Tett in service before contractor's personnel finally leave the job.
A certificate shall be filled out and signed by both representatives. Copies shrill be prepared for approving authorities, owners and contractor. It Is understood the owner's
representative's signature in no way prejudices any claim against contractor for faulty material, poor workmanship, or failure to comply with approving authority's requirements
or local ordinances.
PROPERTY NAME
DATE
PROPERTY ADDRESS
1.
ACCEPTED BY APPROVING AUTHORITY( S) NAMES
ADDRESS
PLANS
INSTALLATION CONFORMS TO ACCEPTED PLANS
EQUIPMENT USED IS APPROVED
IF NO, STATE DEVIATIONS
■ YES • NO
• YES • NO
2.
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION
OF CONTROL VALVES AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT
IF NO, EXPLAIN
•
• YES • NO
_
INSTRUCTIONS
HAVE COPIES OF APPROPRIATE INSTRUCTIONS AND CARE AND MAINTENANCE CHARTS
BEEN LEFT ON PREMISES
F NO. EXPLAIN
• YES • NO
S.
LOCATION
SUPPLIES BLDGS.
4.
UNDERGROUND
PIPES
AND
JOINTS
PIPE TYPES AND CLASS
TYPE JOINT
PIPE CONFORMS TO STANDARD
• YES • NO
FITTINGS CONFORM TO STANDARD
0 YES ■ NO
F NO, EXPLAIN
JOINTS NEEDING ANCHORAGE CLAMPED, STRAPPED. OR BLOCKED P1
ACCORDANCE WITH STANDARD
0 YES n NO
F NO. EXPLAIN
5.
TEST
DESCRIPTION
FLUSHING. Flow the required rate until water is dear as indicated by
and blow -offs. Flush at flows not less than 400 GPM (1514 L/min) for
tor 8 -inch pipe, 1000 GPM (3786 L/min) for 8 -inch pipe, 1600 GPM (5678
When supply cannot produce stipulated flow rates, obtain maximum available.
HYDROSTATIC. Hydrostatic tests shall be made at not fps than 200
excess of 160 pal (10.3 bars) for two hours.
LEAKAGE. New pipe laid with rubber pasketed joints shall, N the workmanship
leakage at the joints ahaN not exceed 2 qts. per M. (1.89 Lt') per 100
joints.I leakageagkae occurs at • be increasedw joints the
by 1 knst.Nation shaN be considered
II in. diameter
no collection of foreign
4 -inch pipe, 000
L/min) for 10inch
psi (13.8 bars) for
is satisfactory,
joints Irrespective
material in burlap bags at outlets such as hydrants
GPM (2271 L/min) for 6 -Inch pipe. 760 GPM (2839 L/min)
pipe and 2000 GPM (7670 L/min) for 12 -inch pipe.
two hours 60 (3.4 bare) 1
or psi above static pressure
have little or no leakage et the joints. The amount d
of pipe diamneter. The leakage shall be distributed over al
and aecessary repairs made. The amount of allowable
for isolating the
unsatisfactory
per hour (30
so the hydrants
such per valve
test section. 11 dry barrel hydrants are tested with the main vaive open.
mL/min) leakage Is permitted for each hydrant.
aL/25 awn/h) each .metal seated valve
are under pressure, en additional 6 as per minute (15C
5.
FLUSHING
TESTS
NEW UNDERGROUND PIPING FLUSHED ACCORDING TO RTANDARD • YES • NO
BY (COMPANY)
F NO, EXPLAIN
HOW FLUSHING FLOW WAS OBTAINED
FIRE PUMP
THROUGH WHAT TYPE OPENING
0 HYDRANT BUTT. ❑ OPEN PIPE
• PUBLIC WATER • TANK 011 RESERVOIR •
LEAD-INSACCORDING FLUSD ACCORDING TO RTANDARD
• YES • NO
BY (COMPANY)
F NO, EXPLAIN
HOW FLUSHING FLOW WAS OBTAINED
FIRE PUMP
THROUGH WHAT TYPE OPENING
• PUBLIC WATER • TANK OR RESERVOIR •
• Y CONN TO FLANGE & SPIGOT • OPEN PIPE
7. HYDROSTATIC
TEST
ALL NEW UNDERGROUND PIPING HY iTATICALLY TESTED AT
PSI FOR HOURS
8.
LEAKAGE
TEST
TOTAL AMOUNT OF LEAKAGE MEASURED
GALS HOURS
ALLOWABLE LEAKAGE
GALS HOURS
NUMBER INSTALLED
9' HYDRANTS
TYPE AND MAKE
ALL OPERATE SATISFAC aILY
DYE Cl NO
10.
CONTROL
VALVES
WATER CONTROL VALVES LEFT WIDE OPEN
IF NO, STATE REASON
❑ YE:. ❑ NO
HOSE THREADS OF FIRE DEPARTMENT CONNECTIONS AND HYDRANTS INTERCHANGEABLE 0 YE: 0 NO
WITH THOSE OF FIRE DEPARTMENT ANSWERING ALARM
11.
DATE LEFT IN SERVICE
REMARKS
12.
SIGNATURES
NAME OF INSTALLING CONTRACTOR
TESTS WITNESSED BY
FOR PROPERTY OWNER (SIGNED)
TITLE DATE
FOR INSTALLING CONTRACTOR (SIGNED)
TITLE DATE
13. CERTIFICATION
This is to cei:ify that this automatic sprinkler system has been installed in accordance with the standards adopted by the
Washington State Fire Marshal and N.F.P.A. Standard 13.
Name of Firm
Mailing Address
Name
Title Date
(Signature of Firm Official)
WHEN ALL APPLICABLE ITEMS THROUGH 13 HAVE BEEN COMPLETED
THIS ORIGINAL FORM SHALL BE RETURNED TO THE STATE FIRE MARSHAL'S OFFICE
14. CONFIRMATION OF SPRINKLER SYSTEM INSTALLATION
Name Title Date
State Fire Marshal Representative
Acceptable: . 0 YES 0 NO
15. COMMENTS.
ADDITIONAL EXPLANATION AND NOTES
(55 Back -655-
City of Tukwila
FIRE DEPARTMENT
444 Andover Park East
Tukwila, Washington 98188-7661
(206) 575-4404
Fire Department Review (513)
Control #89-414
Gary L. VanDusen, Mayor
December 28, 1989
Re: Southcenter Corporate Square, Building #3, 575 Andover
Park West, Tukwila, Wa.
Dear Sir:
The attached set of building plans have been reviewed by
The Fire Prevention Bureau and are acceptable with the
following concerns:
1. The total number of fire extinguishers required for
your establishment is calculated at one extinguisher for
each 3000 sq. ft. of area. The extinguisher(s) should be
of the "All Purpose" (2A, 10 B:C) dry chemical type.
Travel distance to any fire extinguisher must be 75' or
less. (NFPA 10, 3-1.1) (UFC 10.301b)
Extinguishers shall be installed on the hangers or in
the brackets supplied, mounted in cabinents, or set on
shelves (NFPA 10, 1-6.6), and shall be installed so
that the top of the extinguisher is not more than 5
ft. above the floor. (NFPA 10, 1-6.6) (UFC 10.301)
Extinguishers shall be located so as to be in plain
view (if at all possible), or if not in plain view,
they shall be identified with a sign stating, "Fire
Extinguisher," with an arrow pointing to the unit.
(NFPA 10, 1-6.3) (UFC 10.301)
2. Exit hardware and marking must meet the requirements
of Uniform Fire Code Sections 12.104 & 12.114.
Exit doors shall be openable from the inside without
the use of a key or any special knowledge or effort.
(UFC 12.104b)
The exits from office #113 shall be separated by no
less than one-half the diagonal of that office.
City of Tukwila
FIRE DEPARTMENT
444 Andover Park East
Tukwila, Washington 98188-7661
(206) 575-4404
Page number 2
Gary L. VanDusen, Mayor
Exit doors shall swing in the direction of exit travel
when serving an occupant load of 50 or more. (UBC
3303) (UFC 12.101)
Exits serving more than 50 occupants shall be served
by illuminated exit signs.
Exits shall be illuminated at any time the building is
occupied. An emergency system shall automatically
provide exit illumination upon failure of the main
power supply. (UFC 12.113a)
3. Maintain sprinkler protection for all enclosed areas.
(NFPA 13, 4-1.1.1) (UFC 10.302)
All sprinkler drawings shall be prepared by companies
licensed to perform this type of work. Drawings shall
first be approved by the Washington Surveying & Rating
Bureau, Factory Mutual Engineering or Industrial Risk
Insurers, then by. the Tukwila Fire Department. No
sprinkler work shall commence without approved
drawings. (City Ordinance #1141 & NFPA 13, 1-9.1)
(UFC 10.307)
Hose stations are required. (Plans must be submitted
to the Fire Marshal for approval prior to
installation.) (City Ordinance #1141) (Removal of the
hose stations requires, among other considerations, the
written approval of the Fire Chief)
4. Your street address must be conspicuously posted on
the building and shall be plainly visible and legible from
the street. Numbers shall contrast with their background.
(UFC 10.208)
All required occupancy separations, area separation
walls, and draft -stop partitions shall be maintained
and shall be properly repaired, restored or replaced
when damaged, altered, breached, penetrated, removed
or improperly installed. (UFC 10.401)
0
City of Tukwila
FIRE DEPARTMENT
444 Andover Park East
Tukwila, Washington 98188-7661
(206) 575-4404
Page number 3
Gary L. VanDusen, Mayor
All interior wall covering materials shall be
fire -resistive or shall be treated to be
fire -resistive, so as to result in a flame -spread
rating as required by UFC Appendix VI -C tables 42A and
42B. A certificate of the flame spread rating is
required to be delivered to the Tukwila Fire
Department. (UBC 4204) (UFC 10.401)
This review limited to speculative tenant space only
special fire permits may be necessary depending on
detailed description of intended use.
Yours truly,
The Tukwila Fire Prevention Bureau
cc: T.F.D. File
slj
City Tukwila
FIRE DEPARTMENT
444 Andover Park East
Tukwila, Washington 98188-7661
(206) 575-4404
Fire Department Review
Control Number 89-422
(513)
Gary L. VanDusen, Mayor
December 22, 1989
Re: Southcenter Corporate Square, Bldg. #3 - 575 Andover
Park West, Tukwila, Wa.
Dear Sir:
The attached set of building plans have been reviewed by
The Fire Prevention Bureau and are acceptable with the
following concerns:
1. Maintain fire extinguisher coverage throughout.
2. Maintain sprinkler protection for all enclosed areas.
(NFPA 13, 4-1.1.1) (UFC 10.302)
3. All required occupancy separations, area separation
walls, and draft -stop partitions shall be maintained and
shall be properly repaired, restored or replaced when
damaged, altered, breached, penetrated, removed or
improperly installed. (UFC 10.401)
Obtain a welding permit from the Fire Department for
the welding to be done on this job and the job with
the control number of 89-423.
Yours truly,
The Tukwila Fire Prevention Bureau
cc: T.F.D. file
ncd
City Tukwila
FIRE DEPARTMENT
444 Andover Park East
Tukwila, Washington 98188-7661
(206) 575-4404
Fire Department Review
Control Number 89-025
(513)
Gary L. VanDusen, Mayor
March 8, 1989
Re: Southcenter Corporate Square - 575 Andover Park West,
Tukwila, Wa.
Dear Sir:
The attached set of building plans have been reviewed by
The Fire Prevention Bureau and are acceptable with the
following concerns:
1. The total number of fire extinguishers required for
your establishment is calculated at one extinguisher for
each 3000 sq. ft. of area. The extinguisher(s) should be
of the "All Purpose" (2A, 10 B:C) dry chemical type.
Travel distance to any fire extinguisher must be 75' or
less. (NFPA 10, 3-1.1) (UFC 10.301b)
Extinguishers shall be installed on the hangers or in
the brackets supplied, mounted in cabinents, or set on
shelves (NFPA 10, 1-6.6), and shall be installed so
that the top of the extinguisher is not more than 5
ft. above the floor. (NFPA 10, 1-6.6) (UFC 10.301)
Extinguishers shall be located so as to be in plain
view (if at all possible), or if not in plain view,
they shall be identified with a sign stating, "Fire
Extinguisher," with an arrow pointing to the unit.
(NFPA 10, 1-6.3) (UFC 10.301)
2. No point in a sprinklered building may be more than
200 feet from an exit, measured along the path of travel.
(UBC 3302) (UFC 12.101)
Exit hardware and marking must meet the requirements
of Uniform Fire Code Sections 12.104 & 12.114.
Exit doors shall be openable from the inside without
Cit?of Tukwila
FIRE DEPARTMENT
444 Andover Park East
Tukwila, Washington 98188-7661
(206) 575-4404
Page number 2
Gary L. VanDusen, Mayor
the use of a key or any special knowledge or effort.
(UFC 12.104b)
Exits serving more than 50 occupants are required to
have illuminated exit signs. (UFC 12.114)
Exits shall be illuminated at any time the building is
occupied. An emergency system shall automatically
provide exit illumination upon failure of the main
power supply. (UFC 12.113a)
Second floor exits which enter the skybridge must be
provided with exit doors and locks which (A) swing in
the directions of travel and (B) may be opened in the
directions of travel without a key or special
knowledge.
3. An automatic fire extinguishing (sprinkler) system is
required and shall be designed, installed and tested.
(City Ordinance #1141)
All sprinkler drawings shall be prepared by companies
licensed to perform this type of work. Drawings shall
first be approved by the Washington Surveying & Rating
Bureau, Factory Mutual Engineering or Industrial Risk
Insurers, then by the Tukwila Fire Department. No
sprinkler work shall commence without approved
drawings. (City Ordinance #1141 & NFPA 13, 1-9.1)
(UFC 10.307)
All sprinkler systems with more than 100 heads shall
be supervised by an approved central, proprietary or
remote station service or a local alarm which will
give an audible signal at a constantly attended
location. Approved central stations are those listed
by Underwriter's Laboratories, Inc. (UFC 10.309)
4. Your street address must be conspicuously posted on
the building and shall be plainly visible and legible from
the street. Numbers shall contrast with their background.
(UFC 10.208)
City of Tukwila
FIRE DEPARTMENT
444 Andover Park East
Tukwila, Washington 98188-7661
(206) 575-4404
Page number 3
Gary L. VanDusen, Mayor
All required occupancy separations, area separation
walls, and draft -stop partitions shall be maintained
and shall be properly repaired, restored or replaced
when damaged, altered, breached, penetrated, removed
or improperly installed. (UFC 10.401)
All interior wall covering materials shall be
fire -resistive or shall be treated to be
fire -resistive, so as to result in a flame -spread
rating as required by UFC Appendix VI -C tables 42A and
42B. A certificate of the flame spread rating is
required to be delivered to the Tukwila Fire
Department. (UBC 4204) (UFC 10.401)
Yours truly,
The Tukwila Fire Prevention Bureau
cc: T.F.D. file
ncd
of Tukwila
PLANNING DEPARTMENT
6200 Southcenter Boulevard
—Tukwila, Washington 98188
(206) 433-1849
TO:
FROM:
DATE 24
PROJECT: OnC;-rZ. CORP Pak T2 -)14:q. O3
Sheet l0f
The following corrections and/or clarifications are required to complete the ptan review.
( i u Alm RcoF � ?t1 c,TLJ 6 4LTzA-rf_o q t&)
TIZt,lc,TLJRrscL CAL.cmemot s : CO HAT 1-0413)Bort{
Co E -t A -r ANp u N‘ FORM IS Th tS A TE I
T�i�t �� �oR r GLA�ZN
t r -c j u) .h c�4 VFobtnONAt_.
1)1a2L NS To ISE U €o . 'F -4 4x tz 4 4 x to cAu,e,n
?K o N-0,41IS Ms* "DeiAt .''.
r
2, (JILL C�c.r=- c4t it RooFvC
STe
(.ovNAisl4 E To vitaec LO, S, G --
Cape IZIATS, i OtcATE_ 114A -c "E.McL
IS ta+
rarvc E VALISES �i T P�(,E 4-3 . '� c.h.) 1.4O(A)
c.o.( LL Coin
Lc � or.. ��1a�
T[�� ��CATIht� �t�-Io►�- tT 1=c -si 4
(10/T2.MEMO)
+► Date:2-26-89
ORDINANCE COMPLIANCE CHECKLIST UNIFORM BUILDING CODE, 1965Ed. Sheet 190F I
Project: ` 'xYT}ACet4T i Ct --p. �--�Xu lr GI , 13 Fi 1 e B9.O2�
5-35- Ai-Ne T-
OC,CUPANCY GROUP: -1+3-2/ (js�
TYPE OF CONSTRUCTION: \J e--kall-10-0.4-5 1K.1Scl.I.GP OM:e.g.-141S f)
LOCATION ON PROPERTY: i�*S1-1(
BLDG.HT./ NO of STORIES: 1 /O 2 - S -(Dig, `r
•
FLOOR AREA: Tp AL L - 5 /4altp
et 6. OCCUPANT LOAD:
II L. ammo
/2p61/461.1.614 C/ n 6, L
20 � =
DETAILED REQUIREMENTS: •
er/Occupancy
Type of Construction
Exitingd QD
Engineering Regs. & Reqmts. 60i 1}t ) 04,1 F C 6cl-00-e - O.
Compliance w/ WSEC
Compliance w/ Chapter 51-10 W.A.C.
NOTES:
C
CITY OF TUK 'ILA
Central Permit System
‘Atontrol No. $9-'cz>
Permit No.
FINAL APPROVAL FORM 2
NOV igRg
TO: ❑ Building
❑ Planning
❑ Public Works
Fire Dept.
O Police
0 Parks/Recreation
Project Name c.=. -ii -et ?e ---/74--p, 4- 5I��► f
Address s-7'5'
Type of Permit(s) T /
r c /I)
This project is nearing completion. Please investigate your area of responsibility and indicate
below either your final approval or necessary corrections.
If no response is received within one week, it will be assumed that the project is of no concern
to your department and a certificate of occupancy may be issued.
This project is NOT approved by this department; the following corrections are necessary:
( ) /r9 �C 4J G� f G"/ f7 P
( )
( )
( )
( )
)w
( )
( )
( )
( )
Authorized Signature Date
This project is approved by this department:
Auth. ed Signature
Date
CPS Form 3 ol
CITY OF TU ILA
Central Permit System
Oontroi No 5"S 76
Permit No. g% -oz 5
FINAL APPROVAL FORM
TO: ❑ Building
❑ Planning
❑ Public Works
j- Fire Dept.
d 114 le
11nil'
-fl.lL-
ue
JAN 2 2 1990
❑ Police
❑ Parks/Recreation
C
Project Name e-, /e �.,,,y�w �� s� �� i e
Address ,1,,4/(.,4'4.' 6/
Type of Permit(s) T -
This project is nearing completion. Please investigate your area of responsibility and indicate
below either your final approval or necessary corrections.
If no response is received within one week, it will be assumed that the project is of no concern
to your department and a certificate of occupancy may be issued.
This project is NOT approved. ;; is department; the fo owing corrections are necessary.:
s At pe.,,s .. �;` #1 /rte Ae.1 r
/ }. / It
C. Pix 71,37 ✓i s'i!
) C
./A ;€ //e
/J/Jii✓r[1C�7
�-�. ✓J's®Q / r e-
/G / 4e- //lCr+r�VA 4/
�� .►�f / r-
q «e,c
/L7ee 44''
/4 ✓m
is ..54/..,%6lr
573
Authorized Signature
7s -g2
Date
This project is approved by this department:
p s7) / -,'9 - 9z
Authorized Signature
Date
CPS Form 3
CITY OF TUKIALA
Central Permit System
Qntrol No F9 f) Y
Permit No
FINAL APPROVAL FORM
TO: ❑ Building
❑ Planning
❑ Public Works
Fire Dept.
111 Police
❑ Parks / Recreation
Project Name 5--ce- sg ,AV -C
Address s'7 5;01/11/04-/c--
Type
;01/11/G''c-
Type of Permit(s) /
This project is nearing completion. Please investigate your area of responsibility and indicate
below either your final approval or necessary corrections.
If no response is received within one week, it will be assumed that the project is of no concern
to your department and a certificate of occupancy may be issued.
This project is NOT approved by this department; the following corrections are necessary:
() / y
()
()
()
()
()
()
()
()
()
()
Authorized Signature Date
1 This project is approved by this department:
Authorized Signature
7-47 p21
Date
CPS Form 3
CITY OF TUILA
Central Permit System
ontrol No.
S
Permit No. S 8'
FINAL APPROVAL FORM
TO: ❑ Building
❑ Planning
❑ Public Works
`K7 Fire Dept.
APR 24 199*
❑ Police
❑ Parks/Recreation
Project Name s�,.-7L4��A. • r
Address ) 7.S � �,./� � . /� - �• <1. (d/O 3%
Type of Permit(s)
This project is nearing completion. Please investigate your area of responsibility and indicate
below either your final approval or necessary corrections.
If no response is received within one week, it will be assumed that the project is of no concern
to your department and a certificate of occupancy may be issued.
J
This project is NOT approved by this department; the following corrections are necessary:
O
() h P�0f m / —j1., 1, 'y6 t 1 £ :•'
()
()
O
()
()
()
()
()
Authorized Signature
Date
This project is approved by this department:
Authorized Signature
I="Z. ri3
Date
CPS Form 3
Ilk .
METROMARK
INVESTMENT MANAGEMENT
February 25, 1994
Ms. Norita Deckard
Tukwila Fire Dept.
444 Andover Park East
Tukwila, WA 98188-7661
RE: Change of Mailing Address
Southcenter Corporate Square
Southcenter Place Building
Sent via Certified Mail
Dear Ms. Deckard:
Please change your records for the below office buildings. The management of
these buildings is located at a new location.
Please address all future correspondence for Southcenter Corporate Square
to the following:
Southcenter Corporate Square
c/o Metromark Investment Management
14335 NE 24th St, Suite 202
Bellevue, WA 98007
Southcenter Corporate Square consists of 12 buildings with the following
addresses:
Building 1 545 Andover Park West
Building 3 575 Andover Park West
Building 5 625 Andover Park West
Building 7 655 Andover Park West
Building 9 665 Andover Park West
Building 11 375 Andover Park West
Building 2 565 Andover Park West
Building 4 555 Andover Park West
Building 6 645 Andover Park West
Building 8 635 Andover Park West
Building 10 360 Andover Park West
Building 12 370 Andover Park West
.ISH Properties, Inc. / 14335 NE 24th, Suite 202 / Bellevue, Washington 98007
206 454-6663 FAX: 206 454-1391
City of Tukwila
Fire Department
FIRE WATCH REQUIRED
Due to the inoperative fire protection system(s) in your facility, you are required to provide a fire watch
per City of Tukwila Ordinance #2437, section 16.40.120-D and Ordinance #2436, section 16.42.100-C
(see reverse side). The fire watch shall be maintained until the system(s) are operational as determined
by the Tukwila Fire Marshal's Office. FAX paperwork to 206-575-4439 to verify the completion of
repair work and/or the restoration of system monitoring. in order to end the tire watch.
The fire watch is required 24 hours a day. Designated employees may serve as the fire watch during
business hours, while performing their regular job. Fire watch personnel must be aware of, and accept
the duties of the fire watch.
After hours fire watch personnel must be on location and must patrol the building following the close of
business. Every two hours they must call 206-971-8737 and leave a message stating the following:
Date:
I. Your name.
2. Street address of firewatch location.
3. Time of day.
4. If everything is OK, state all clear. If you discover an emergency during your patrol , call
9-1-1 immediately to report it.
[/4i -ii 7
Reason For Fire watch:
Inspectors: \
Start time:
It -130
Business Name: Z---ZeitIACejl....^(-
Business Address:
Incident #:
Business Phone:57 S"--3:1)5?)
Person in Charge: (AAA
LA)
Signature:
W Fire Marshal's Office Y Owner Manager
Rev. 719.114
T.F.D. Form F.P. 41
Tukwila Fire Marshal'x Office • Phone: 206-575-4407 • Fax: 206-575-4439 • Email: FireMarshantakwilawa.gov
c
( 1) C) (3)
I "
)
()
I/) cp,)
(')
1)
SUITE 101
,/ ;
/
//`
LEASED
MFIRST FLOOR PLAN
N -L-/ NOT TO SCALE
modwev
30'
NUR TH
Marvin Stei &sociates, LLC
planning design
2221 Fifth Avenue, Seat t le, Washington 98121 1206) 441-1449
COLLIERS
INTERN NTiONAL
(206) 223-0866
TIRE MARKETING PLAN
SOUTHCENTER CORP. SQ.
Job BUILDING 3
Job No. 99135-036
Dote 11/16/06
Sheet No. 3.1
(1
(a)
(4)
(5)
(i
vaccm
SUITE 202
VACANT
C9)
(B)
L% LEASED
/
MSECOND FLOOR PLAN
NOT TO SCALE
NORTH
5. 10' 20' 30"
Marvin Ste sociates, LLC
planning design
2221 Filth Aviiut, Sott le, WaNIIiiigton 98121 206) 4 4 1-1449
(206) 223-0866
TITLE MARKETING PLAN Job No. 99135-036
Date 11/16/06
SOUTHCENTER CORP. SQ.
Job BUILDING 3 Sheet No. 3.2
Unit
CompuPay, Inc
Assured Imaging
Women's Wellness
Qwest/Equis Corporation
v 1-201 VACANT
✓ 1-205 Hak Club for Men
5-5
.6400
33.0 12-101/
V1-209
0-211
✓1-215
10-101 ✓
Hair Club For Men
Resilient Commercial
Coatings. Inc.
Link Resources
Corporation
Le Cordon Bleu
Home Depot USA, Inc
Customer Research
72-102 American Fidelity
Assurance Company
2-110 VACANT
2-119 VACANT
�2-201x VACANT
3-1011, WA State Nurses
Association
3-202 VACANT
/3-205 Rainier Umsery Council
3-210
1-5
Direct Contact. LLC
v4-101 CompuPay, Inc
BSc
s
SqF
4-110 Level Two, Inc. 1,1
✓4-201 Systematech Technical
Mgmt Services
/5-101
Medical Billing Solutions,
Inc.
s 5-107 VACANT
5-111 AFT Washington
✓5-201
/ 6-601
U‘117 7-101
8-100
International Academy of
Design & Tech
International Academy of
Design & Tech
International Academy of
Design & Tech
VACANT.
t
J(_ =8-101 NUCA of Washington
Wl)v 8-107 Building
Amenities/Management
Office,8-108 Kathy Ross
18.111 VACANT
/8-200 SEWHealthcare NW
Partnership
•1
iTraining
01 V VACANT
((� �F ANTENNA SBA Communications
Corporation
PARKINGA United Parcel Service,
Inc.
PARKINGB VACANT
Property Totals: