Loading...
HomeMy WebLinkAboutPP - 575 ANDOVER PARK WEST BLDG #3 - S.C. CORPORATE SQUARE BLDG - PERMITS AND PLANS575 ANDOVER PARK WEST BLDG #3 ASSOCIATED PERMITS 89-414 89-023 89-025 89-423 89-422 89-029 5885 5 5 5 _; 75-- / _ CONTRACTOR'S MATERIAL & TEST CERTIFICATE SPRINKLER SYSTEMS . WATER SPRAY SYSTEMS 1 PART "A" GENERAL PROCEDURE UPON COMPLETION OF WORK, INSPECTION AND TESTS SHOULD BE MADE BY CONTRACTOR'S REPRESENTATIVE AND WITNESSED BY AN OWNER'S REPRESENTATIVE ALL DEFECTS SHOULD BE CORRECTED AND SYSTEM LEFT IN SERVICE BEFORE CONTRACTOR'S MEN FINALLY LEAVE THE JOB. A CERTIFICATE SHOULD BE FILLED OUT AND SIGNED BY BOTH REPRESENTATIVES. COPIES SHOULD BE PREPARED FOR INSPECTING AUTHORITIES, OWNER AND CONTRACTOR. IT IS UNDERSTOOD THE OWNER'S REPRESENTATIVE'S SIGNATURE IN NO WAY PREJUDICES ANY CLAIM AGAINST CONTRACTOR FOR FAULTY MATERIAL, POOR WORKMANSHIP OR FAILURE TO COMPLY WITH INSPECTING AUTHORITY'S REQUIREMENTS OR LOCAL ORDINANCES. PROPERTY NAME Southcenter Corporate Square Ph II PROPERTY ADDRESS FILE 527 Andover Park West, Tukwila, WA ACCEPTED BY INSPECTION AUTHORITY ('S) NAMES PLANS INSTRUC• TIONS TEST DESCRIP- TION ADDRESS 1 DATE INSTALLATION CONFORMS TO ACCEPTED PLANS EQUIPMENT USED 18 APPROVED IF NO, STATE DEVIATIONS HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION OF CONTROL VALVES AND CARE OF THIS NEW EQUIPMENT IF NO, EXPLAIN HAS A COPY OF INSTRUCTION AND MAINTENANCE CHART BEEN LEFT AT PLANT 1F NO, EXPLAIN YE$ 0 YES ❑ NO 0 NO 0 YE8 0 NO 0 YES ❑ NO ❑ FLUSHING: Flow the required rate until ma1Sa are clear as Indicated by no ccUectton of foreign material in burlap bap at outlets inch as hydrants and Flush at Bows not leas than 750 GPM for 6 -loch pipe and smaller, 1000 GPM for 8 -loch, 1500 GPM for 10 -loch. 2000 CPM for 12 -Inch. Where supply imp ooved subsequent toproduce tloatallattm rate.ed flow obtain maximum available by using properly sized discharge deviate Piping to be refluahed when water supply la HYDROSTATIC: Hydrostatic teat should be made at not less than 200 PSI for two hours or 50 PSI above static pressure In excess of 150 PSI. DlferentW dry -pipe valve clappers should be left open during test to prevent damage. All above ground piping leakage should be stopped. LEAKAGE. New pipe lad with rubber psketed Joints should, if the workmsn.hlp Is stisfactory, have no leakage at the pints. Unsatisfactory amounts of leakage usually result from twisted, pinched or cut pskets. However, some leakage might result from mall anoints of grit or small Imperfection.. The amount of leakage at the John. should not exceed 2 quarts per hour per 100 pints Irrespectively of pipe diameter. The leakage should be distributed over all Joint., It such leakage occurs at a few Joints the installation should be considered unsatisfactory and necessary repairs made. New pipe laid with caulked lead or lead-.ubstltute Joints should, U the workmanship is satisfactory, hove little or no leakage at the Joints. Any Joint having leakage or morethana•allght drip' or' weeping' should be repaired, Leakage should not exceed 1 oz. (liquid measure) per hour per Inch of pipe Mammas per Joint. The leakage should be distrtbutedoverallInstallationus. If such leakage occurs almost entirely ata few Joints, the Installationshould be considered unsatisfactory and necessary repairs made. PNEUMATIC: Establish 40 PSI air pressure and measure pressure drop which should not exceed 11/2 PSI In 24 hours. Test pressure make at normal water level and air pressure, and measure air pressure drop which should not exceed 1 1/2 PSI in 24 hours. blow -offs. LOCATION UNDER- GROUND PIPES AND JOINTS TESTS REQUIRED FEEDS BLDGS. PART "B" - UNDERGROUND PIPING Southcenter Corporate Square Ph II, Andover Park West, Bldgs. 1,2,3,4 PIPE TYPE AND CLASS TYPE JOINT Ductile Iron CONFORMS TO IF NO, EXPLAIN STANDARD JOINTS NEEDING ANCHORAGE CLAMPED, STRAPPED OR BACKED IN ACCORDANCE WITH STANDARD IF NO, EXPLAIN YES 0 YE8 ❑ FLUSHING TESTS FLUSHING HYDROSTATIC LEAKAGE NEW UNDERGROUND PIPING FLUSHED ACCORDING TO BY (COMPANY) BY YES ❑ HOW WAS FLUSHING, FLOW OBTAINED PUBLIC WATER 0 THROUGH WHAT TYPE OPENING LEAD-INS FLUSHED ACCORDING TO STANDARD BY (COMPANY) YES ❑ TANK OR RESERVOIR 0 FIRE PUMP 0 HYD. BUTT. ❑ OPEN PIPE 0 HOW WAS FLUSHING FLOW OBTAINED PUBLIC WATER 0 THROUGH WHAT TYPE OPENING TANK OR RESERVOIR 0 FIRE PUMP 0 Y CONN. TO FLANGE & SPIGOT 0 OPEN PIPE 0 • HYDROSTATIC TEST • i� NEW UNDERGROUND PIPING HYDROSTATICALLY TESTED AT P. S.1. FOR HOURS LEAKAGE TEST TOTAL MOUNT OF LEAKAGE MEASURED O'er' HOURS ALLOWABLE LEAKAGE GALS. HOURS HYDRANTS NUMBER INSTALLED TYPE AND MAKE ALL OPERATE SATISFACTORILY YES ❑ NO ❑ CONROL VALVES WATER CONTROL VALVA LEFT WIDE OPEN • YE8 ❑ NO 0 IF NO, STATE REASON REMARKS DATE LEFT IN SERVICE PARTS A & 1 NAME OF SPRINKLER CONTRACTOR TIT.R OF i 1 i t i ac FOR PROPERTY OWNER (SIGNED) TITLE SIGNATURES FOR SPRINKLER CONTRACTOR (SIGNED) Tim Collins ppippelayyer DATE PART "C" — SPRINKLER & WATER SPRAY ABOVE GROI3ND PI NG (FILL OUT SEPARATE PART "C" FOR EACH RISER) LOCATION SERVES BLDG. TESTS REQUIRED 1 HYDROSTATIC TEST OF ALL PIPING 2 PNEUMATIC TEST OF ALL DRY PIPING 3 EQUIPMENT OPERATION TESTS OF ALL EQUIPMENT SPRINKLERS OR SPRAY NOZZLES MAKE MODEL SIZE QUANTITY TEMPERATURE RATING PIPE AND FITTINGS MATERIAL AND MOND CONFORMS TO STANDARD 1 IF NONE, EXPLAIN ALARM VALVE OR FLOW INDICATOR ALARM DEVICE MAKIMUM TIME TO OPERATE THROUGH TEST PIM TYPE MAKE MODEL MIN. BEC. DRY PIPE VALVES OPERATING TENT RESULTS WATER AIR TRIP TIME MAKE MODEL SER. TIME TO TRIP THROUGH TEST PIPE PRESS. PRESS. POINT WATER REACHED ALARM OPERATED NO. WITHOUT Q. O. D. WITH Q. O. D. AIS PRESS. TEST OUTLET PROPERLY MIN. SEC. MIN. SEC. P.8.1. P.S.L P.8.1, MIN.' SEC. YES 1 NO 1F NO, EXPLAIN DELUGE & PREACTION VALVES OPERATION PNEUMATIC 0 ELECTRIC 0 HYDRAULIC 0 PIPING SUPERVISED YES 0 NO 0 DETECTING MEDIA SUPERVISED YES 0 NO 0 DOES VALVE OPERATE FROM THE MANUAL TRIP AND/OR REMOTE CONTROL STATIONS YE8 0 NO 0 1S THERE AN ACCESSIBLE FACILITY IN EACH CMCUIT FOR TESTING IF NO, EXPLAIN YES 0 NO 0 MAKE MODEL DOES EACH CIRCUIT OPERATE SUPERVISION LOBS ALARM DOES EACH CIRCUIT OPERATE VALVE RELEASE MAXIMUM TIME TO OPERATE RELEASE YE8 NO YEN NO MIN. SEC. TESTS ALL PIPING HYDROSTATICALLY TESTED AT PSI FOR 11013118 DRY PIPING PNEUMAT CALLY TESTED YES D NO0 EQUIPMENT OPERATE PROPERLY YES ❑ NOD IF NO STATE REASON 41 RAIPJ TEST: READING OF GAGE LOCATED NEAR WATER SUPPLY TEST PIPE: RESIDUAL PRESSURE V'FTH VALVE IN TEST PIPE OPEN WIDE: ' STATIC PRESSURE PSI PBI BLANK TESTING GASKETS NUMBER USED LOCATIONS NUMBER REMOVED REMARKS DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN. PART "C" SIGNATURES NAME OF SPRINKLER CONTRACTOR FOR P OPERTY R BIG D) TITLE 'i('11,l V / (-006') N.. FOR SPRINKLER CONTRACTOR (SIGNED) CONTRACTOR'S MATERIAL & TEST CERTIFICATE SPRINKLER SYSTEMS - WATER SPRAY SYSTEMS PART "A" GENERAL PROCEDURE UPON COMPLETION OF WORK, INSPECTION AND TESTS SHOULD BE MADE BY CONTRACTOR'S REPRESENTATIVE AND WITNESSED BY AN OWNER'S REPRESENTATIVE. ALL DEFECTS SHOULD BE CORRECTED AND SYSTEM LEFT IN SERVICE BEFORE CONTRACTOR'S MEN FINALLY LEAVE THE JOB. A CERTIFICATE SHOULD BE FILLED OUT AND SIGNED BY BOTH REPRESENTATIVES. COPIES SHOULD BE PREPARED FOR INSPECTING AUTHORITIES, OWNER AND CONTRACTOR. IT IS UNDERSTOOD THE OWNER'S REPRESENTATIVE'S SIGNATURE IN NO WAY PREJUDICES ANY CLAIM AGAINST CONTRACTOR FOR FAULTY MATERIAL, POOR WORKMANSHIP OR FAILURE TO COMPLY WITH INSPECTING AUTHORITY'S REQUIREMENTS OR LOCAL ORDINANCES. PROPERTY NAME �/ (` mo//. c ----/9`g � •i %J/.,42_n,,�l" -2rtr. 77 DATE 5;.:1.9 , PROPERTY ADDRESS —7 A' !a K?/(57 ACCEPTED BY INSPECTION AUTHORITY ('5) NAMES / ir` ,:v 1 T ' f- '4' PLANS ADDRESS �- �!/� U , li -l/c';' INSTALLATION CONFORMS TO ACCEPTED PLANS YES 5 NO 0 EQUIPMENT USED IS APPROVED YES.' NO 0 IF NO, STATE DEVIATIONS INSTRUC- HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION OF CONTROL VALVES AND CARE OF THIS NEW EQUIPMENT YES 5- NO 0 IF NO, EXPLAIN TIONS HAS A COPY OF INSTRUCTION AND MAINTENANCE CHART BEEN LEFT YES ,, NO 0 AT PLANT IF NO, EXPLAIN FLUSHING: Flow the required rate untU mains are clear as indicated by no collection of foreign material in burlap bags at outlets such as bydrums and TEST blow -offs. . Flush at flows not less than 750 GPM for 6 -inch pipe and smaller, 1000 GPM for 11 -inch. 1500 GPM for 10 -inch. 2030 GPM for 12 -inch. Where supply canna produce stipulated flow rate, obtain maximum avallable by using properly sized discharge devices. Piping to be reflushed when water supply Is improved subsequent to installation. HYDROSTATIC: Hydrostatic test should be made at not less than 200 PSI for two hours or 50 PSI above static pressure to excess of 150 PSL Differential DES... 1 - dry -pipe valve clappers should be left open during test to prevent damage. Alt above ground piping leakage should be stopped. LEAKAGE: New pipe laid with rubber gasketed joints should, if the workmanship is satisfactory, have an leakage at the pinta. Unsatisfactory amounts TION of leakage usually result from twisted, pitched or cut gaskets. However, some leakage might result from small amounts of grit or small imperfections. The imam/ of leakage at the Joints should not exceed 2 quarts per hour per 100 joints irrespectively of pipe diameter. The leakage should be dlstrtbu ted over aU Joints. If such leakage occurs at a few joints the installation should be considered unsatisfactory and necessary repairs made. New pipe laid with caulked lead or lead -substitute Joints should, if the workmanship is satisfactory, have little or no leakage at the Joints. Any joint having leakage or more thana'slight drip' or' weeping' should be repaired. Leakage should not exceed 1 ox. (liquid measure) per hour per inch of pipe diameter per joint. The leakage should be distributed over all )Dints. If such leakage occur. almost entirely at a few )Dints, the installation should be considered unaattatactory and necessary repairs made. PNEUMATIC: Establish 40 PSI air pressure std measure pressure drop which should not exceed 11/2 PSI in 24 hours. Test pressure tanks at normal water level and air pressure, and measure air pressure drop which should not exceed 1 1/2 PSI in 24 hours. PART "B" — UNDERGROUND PIPING LOCATION FEEDS BLDGS. / — -.3 -4- PIPE TYPE AND CLASS TYPE JOINT7- UNDER- ; 7 /_.e % .,-....-77/-e...„,. X-.1-1-- 7 /�..1/ CONFORMS TO /I".-%.27:4: STANDARD YES Ela, NO 0 GROUND PIPES IF NO, EXPLAIN AND JOINTS NEED, 91IQAAGE CLAMPED, STRAPPED OR BACKED IN ACCORDANCE yES �' NO 0 WITH /--" STANDARD JOINTS IF NO, EXPLAIN TESTS REQUIRED FLUSHING .- HYDROSTATIC LEAKAGE NEW UNDERGROUND PIPING FLUSHED ACCORDING TO ,„./2774.-%7/ .-?,04 STANDARD YES etr BY (COMPANY) HOW WAS FLUSHING FLOW OBTAINED PUBLIC WATER g TANK OR RESERVOIR 0 FIRE PUMP 0 FLUSHING THROUGH WHAT TYPE OPENING HYD. BUTT. 0 OPEN PIPE 0 LEAD-INS FLUSHED ACCORDING TO "27,;%P/c STANDARD YES 0 TESTS BY (COMPANY) HOW WAS FLUSHING FLOW OBTAINED PUBLIC WATEP 51 TANK OR RESERVOIR 0 FIRE PUMP 0 THROUGH WHAT TYPE OPENING Y CONN. TO FLANGE & SPIGOT OPEN PIPE .❑ • HYDROSTATIC(') TEST ALL NEW UNDERGROUND PIPING HYDR ATICALLY TESTED AT P. S. I. FOR HOURS LEAKAGE TEST TOTAL MOUNT OF LEAKAGE MEASURED GALS. HOURS ALLOWABLE LEAKAGE GALS. HOURS HYDRANTS NUMBER INSTALLED _R /,A4', --e TYPE AND MAKE ALL OPERATE SATISFACTORILY YES ❑ NO ❑ CONROI VALVES WATER CONTROL VALVES LEFT WIDE OPEN YES, NO 0 IF NO, STATE REASON REMARKS DATE LEFT IN SERVICE ' U 'a 5 ;0 PARTS A & 8 NAME OF SPRINKLER CONTRACTOR FOR PROPERTY OWNER (SIGNED) TITLE SIGNATURES FOR SPRINKLER CONTRACTOR (SIGNED) DATE PART "C" - SPRINKLER & WATER SPRAY ABOVE GROUND PIPING (FILL OUT SEPARATE PART "C^ FOR EACH RISER) LOCATION SERVES BLDGS. TESTS REQUIRED 1 HYDROSTATIC TEST OF ALL PIPING 2 PNEUMATIC TEST OF ALL DRY PIPING 3 EQUIPMENT OPERATION TESTS OF ALL EQUIPMENT SPRINKLERS OR SPRAY NOZZLES MALE MODEL. SIZE QUANTITY TEMPERATURE RATING PIPE AND ' FITTINGS MATERIAL AND KIND CONFORMS TO STANDARD IF NONE, EXPLAIN ALARM VALVE OR FLOW INDICATOR ALARM DEVICE MAXIMUM TIME TO OPERATE THROUGH TEST PIPE TYPE I MAKE MODEL MIN. SEC. DRY PIPE VALVES OPERATING TEST RESULTS WATER PRESS. AIR PRESS. TRIP POINT AIR PRESS, TIME WATER REACHED TEST OUTLET ALARM OPERATED PROPERLY MAKE MODEL SER. TIME TO TRIP THROUGH TEST PIPE NO. WITHOUT Q. O. D. WITH Q. O. D. MIN. SEC. MIN. SEC. P. 3.1. P.B.I. P.S.I. MIN, SEC. YES NO IF NO, EXPLAIN DELUGE 8` PREACTION VALVES OPERATION PNEUMATIC ❑ ELECTRIC❑ HYDRAULIC 0 PIPING SUPERVISED YES 0 NO 0 DETECTING MEDIA SUPERVISED YES 0 NO ❑ DOES VALVE OPERATE FROM THE MANUAL TRIP AND/OR REMOTE CONTROL STATIONS YES 0 NO 0 IS THERE AN ACCESSIBLE FACILITY IN EACH CIRCUIT FOR TESTING YES ❑ NO 0 IF NO, EXPLAIN MAKE MODEL DOES EACH CIRCUIT OPERATE SUPERVISION LOSS ALARM DOES EACH CIRCUIT OPERATE VALVE RELEASE MAXIMUM TIME TO OPERATE RELEASE YES NO YES NO MIN. SEC. TESTS ALL PIPING HYDROSTATICALLY TESTED AT PSI FOR HOURS DRY PIPING PNEUMATICALLY TESTED YES 0 1400 EQUIPMENT OPERATE PROPERLY YES ❑ NO❑ IF NO, STATE REASON DRAIN TEST: READING OF GAGE LOCATED NEAR WATER SUPPLY TEST PIPE: RESIDUAL PRESSURE wITH VALVE IN TEST PIPE OPEN WIDE: STATIC PRESSURE PSI PSI BLANK TESTING GASKETS NUMBER USED LOCATIONS NUMBER REMOVED REMARKS DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN, PART „C,. SIGNATURES NAME OFSPRIN1G.ER CONTRACTOR � R PROP OWNER (SIGNED) TITLE , p, f: (4z -/%r; f., �� ( , - ..----F-Pa sr 3 FOR SPRINKLER CONTRACTOR (SIGNED) Ip Washington State Fire Marshal Insurance Building AQ -21 sime Olympia, Wa. 98504 CONTRACTOR'S MATERIAL & TEST CERTIFICATE FOR ABOVE GROUND PIPING PROCEDURE Upon completion of work, inspection and tests shall be made by the contractor's representative and witnessed by an owner's representative. All defects shall be corrected and system left in service before contractor's personnel finally leave the job. A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners and contractor. It is understood the owner's representative's signature in no way prejudices any claim against contractor for faulty material, poor workmanship. or failure to comply with approving authority's requirements or local ordinances. PROPERTY NAME S'q�•i�1- PROPERTY ADDRESS 1. PLANS DATE ACCEPTED BY APPROVIN,.a AUTHORITY('S) NAMES ADDRESS 7 -tea X9,9 kLL• • /? / i --e • L•AL-Iti.• /? fi67, )-r- ('7; --- INSTALLATION CONFORMS TO ACCEPTED PLANS EQUIPMENT USED IS APPROVED IF NO, STATE DEVIATIONS 9'YYES 0 NO Its YES 0 NO 2. INSTRUCTIONS HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION OF CONTROL VALVES AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT? IF NO, EXPLAIN lit YES ❑ NO HAVE COPIES OF APPROPRIATE INSTRUCTIONS AND CARE AND MAINTENANCE CHARTS AND NFPA 13A BEEN LEFT ON PREMISES? IF NO, EXPLAIN ISYES 0 NO 3• LOCATION OF SYSTEM SUPPLIES BLDGS. 4. SPRINKLERS 5 PIPE AND FITTINGS MAKE MODEL YEAR OF MANUFACTURE ORIFICE SIZE QUANTITY G /1 K/,raf/,P -94`b y%iJ l T -3 /9:4 9 /3Z— TEMPERATURE RATING 2 -z /6_3 - / GS/ PIPE CONFORMS TO FITTINGS CONFORM TO F NO, EXPLAIN STANDARD TANDARD TES YES 0 NO 0 NO 6. ALARM VALVE OR FLOW INDICATOR ALARM DEVICE MAXIMUM TIME TO OPERATE THROUGH TEST PIPE TYPE MAKE MODEL MIN. SEC. >- I NA• 41 /1 ?'s?OJ 7. DRY PIPE OPERATING TEST DRY VALVE O.O.D. MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO. `� e J,, , • TIME TO TRIP THRU TEST PIPE 1 WATER PRESSURE - AIR PRESSURE TRIP POINT AIR PRESSURE TIME WATER REACHED TEST OUTLET ALARM OPERATED PROPERLY MIN. SEC. PSI PSI Psi MIN. SEC. YES NO Without O.O.D. 6 / 4 3 L'9 9 16 With O.O.D. IF NO, EXPLAIN S.F.M. 223A (Rev. 3183) a1SSSA-564 (OVER) 8. DELUGE & PREACTION VALVES OPERATION L/NEUMATIC PIPING SUPERVISED 0 ELECTRIC 0 HYDRAI� DETECTING MEDIA SUPERVISED 0 YES 0 NO y DOES VALVE OPERATE FROM THE MANUAL TRIP AND/OR REMOTE CONTROL •NS ❑ YES ❑ YES ❑ NO ❑ NO IS THERE AN ACCESSIBLE FACILITY IN EACH CIRCUIT FOR TESTIN 0 YES ❑ NO ACH CIRCUIT OPERATE MAKE MODEL SUPERVISION LOSS ALARM NO VES IF NO, EXPLAIN DOES EACH CIRCUIT OPERATE VALVE RELEASE MAXIMUM TIME TO OPERATE RELEASE VES NO MIN. SEC TEST DESCRIPTION 9. TESTS HYDROSTATIC: Hydrostatic shall be made at not Tess than 200 psi (13.6 bars) fo two hours or 50 psi (3.4 bars) above static pressure in excess of 150 psi (10.2 bars) for two hours. Differential dry -pipe valve clappers shall be left open during test to prevent damage. All aboveground piping leakage shall be stopped. FLUSHING: Flow the required rate until water is clear as indicated by no collection of foreign material in burlap bags at outlets such as hydrants and blow -offs. Flush at flows not Tess than 400 GPM (1514 L/min) for 4 -inch pipe, 600 GPM (2271 L/min) for 5 -inch pipe, 760 GPM (2839 L/min) for 6 -inch pipe, 1000 GPM (3785 L / min) for 8 -inch pipe, 1500 GPM (5678 L /min) for 10 -inch pipe and 2000 GPM (7570 L /min) for 12 -Inch pipe. When supply cannot produce stipulated flow rates, obtain maximum available. PNEUMATIC: Establish 40 psi (2.7 bars) air pressure and measure drop which shall not exceed 1-15 psi (0.1 bars) in 24 hours. Test pressure tanks at normal water level and air pressure and measure air pressure drop which shall not exceed 1-15 psi (0.1 bars) in 24 hours. IF NO, STATE REASON ALL PIPING HYDROSTATICALLY TESTED AT ar.2�71PSI FOR 2 HRS. B DRY PIPING. PNEUMATICALLY TESTED Y S 0 NO EOUIPMENT OPERATES PROPERLY U'YES 0 NO DRAIN TEST READING OF GAGE LOCATED NEAR WATER SUPPLY TEST PIPE: STATIC PRESSURE. /Yaa' PSI RESIDUAL PREpRE WITH VALVE IN TEST PIPE OPEN WIDE �2 PSI Underground mains and lead In connections to system risers flushed before connection made to sprinkler piping. OT:HER EXPLAIN VERIFIED BY COPY OF THE U FORM NO. 85B. FLUSHED BY INSTALLER OF UNDERGROUND SPRINKLER PIPING 10. BLANK TESTING GASKETS 11. WELDING NUMBER USED WELDING PIPING LOCATIONS Er, ,., YES 0 NO AYES ❑ NO NUMBER REMOVED ❑ YES ❑ NO IF YES... DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT WELDING PROCEDURES COMPLY WITH THE REQUIREMENTS OF AT LEAST AWS D10.9, LEVEL AR -3 DO YOU CERTIFY THAT THE WELDING WAS PERFORMED BY WELDERS QUALIFIED IN COMPLIANCE WITH THE REQUIREMENTS OF AT LEAST AWS D10.9, LEVEL AR -3 DO YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANCE WITH A DOCUMENTED OUALITY CONTROL PROCEDURE TO INSURE THAT ALL DISCS ARE RETRIEVED, THAT OPENINGS IN PIPING ARE SMOOTH, THAT SLAG AND OTHER WELDING RESIDUE ARE REMOVED, AND THAT THE .INTERNAL ' DIAMETERS OF PIPING ARE NOT PENETRATED ❑ YES ❑ NO ❑ YES ❑ NO ❑ YES 0 NO 12. HYDRAUUC DATA NAMEPLATE 13. REMARKS NAMEPLATE PROVIDED 0 YES LJ NO IF NO, EXPLAIN DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN: 14. SIGNATURES NAME OF SPRINKLER CONTRACTOR /,e /1 �.c P1-4! 4/ ,e-1,/‹.); TESTS WITNESSED BY FOR PROPERTY OWNER (SIGNED) TITLE 1 TITLE FORRPRINKLER CONTRACTOR (SIGNED) AN ADDITIONAL EXPLANL /,lrTl, N DATE DATE • 854 Beck -554- 15. CERTIFICATION This is to certify that this automatic sprinkler system has been installed in accordance with the standards adopted by the Washington State Fire Marshal and N.F.P.A. Standard 13. Name of Firm Mailing Address Name Title Date (Signature of Firm Official) WHEN ALL APPLICABLE ITEMS THROUGH 15 HAVE BEEN COMPLETED THIS ORIGINAL FORM SHALL BE RETURNED TO THE STATE FIRE MARSHAL'S OFFICE 16. CONFIRMATION OF SPRINKLER SYSTEM INSTALLATION Name Title Date State Fire Marshal Representative Acceptable: ❑ YES ❑ NO 17. COMMENTS• ADDITIONAL EXPLANATION AND NOTES reftWashington State Fire Marshal 0 ,.,'Insurance Building AQ -21 Olympia, Wa. 98504 CONTRACTOR'S MATERIAL & TEST CERTIFICATE FOR U NDERGROUND PIPING PROCEPURE Upon completion of work. inspection and tests shall be made by the contractor's representative and witnessed by an owner's representative. All defects shall be corrected and system Tett in service before contractor's personnel finally leave the job. A certificate shall be filled out and signed by both representatives. Copies shrill be prepared for approving authorities, owners and contractor. It Is understood the owner's representative's signature in no way prejudices any claim against contractor for faulty material, poor workmanship, or failure to comply with approving authority's requirements or local ordinances. PROPERTY NAME DATE PROPERTY ADDRESS 1. ACCEPTED BY APPROVING AUTHORITY( S) NAMES ADDRESS PLANS INSTALLATION CONFORMS TO ACCEPTED PLANS EQUIPMENT USED IS APPROVED IF NO, STATE DEVIATIONS ■ YES • NO • YES • NO 2. HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION OF CONTROL VALVES AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT IF NO, EXPLAIN • • YES • NO _ INSTRUCTIONS HAVE COPIES OF APPROPRIATE INSTRUCTIONS AND CARE AND MAINTENANCE CHARTS BEEN LEFT ON PREMISES F NO. EXPLAIN • YES • NO S. LOCATION SUPPLIES BLDGS. 4. UNDERGROUND PIPES AND JOINTS PIPE TYPES AND CLASS TYPE JOINT PIPE CONFORMS TO STANDARD • YES • NO FITTINGS CONFORM TO STANDARD 0 YES ■ NO F NO, EXPLAIN JOINTS NEEDING ANCHORAGE CLAMPED, STRAPPED. OR BLOCKED P1 ACCORDANCE WITH STANDARD 0 YES n NO F NO. EXPLAIN 5. TEST DESCRIPTION FLUSHING. Flow the required rate until water is dear as indicated by and blow -offs. Flush at flows not less than 400 GPM (1514 L/min) for tor 8 -inch pipe, 1000 GPM (3786 L/min) for 8 -inch pipe, 1600 GPM (5678 When supply cannot produce stipulated flow rates, obtain maximum available. HYDROSTATIC. Hydrostatic tests shall be made at not fps than 200 excess of 160 pal (10.3 bars) for two hours. LEAKAGE. New pipe laid with rubber pasketed joints shall, N the workmanship leakage at the joints ahaN not exceed 2 qts. per M. (1.89 Lt') per 100 joints.I leakageagkae occurs at • be increasedw joints the by 1 knst.Nation shaN be considered II in. diameter no collection of foreign 4 -inch pipe, 000 L/min) for 10inch psi (13.8 bars) for is satisfactory, joints Irrespective material in burlap bags at outlets such as hydrants GPM (2271 L/min) for 6 -Inch pipe. 760 GPM (2839 L/min) pipe and 2000 GPM (7670 L/min) for 12 -inch pipe. two hours 60 (3.4 bare) 1 or psi above static pressure have little or no leakage et the joints. The amount d of pipe diamneter. The leakage shall be distributed over al and aecessary repairs made. The amount of allowable for isolating the unsatisfactory per hour (30 so the hydrants such per valve test section. 11 dry barrel hydrants are tested with the main vaive open. mL/min) leakage Is permitted for each hydrant. aL/25 awn/h) each .metal seated valve are under pressure, en additional 6 as per minute (15C 5. FLUSHING TESTS NEW UNDERGROUND PIPING FLUSHED ACCORDING TO RTANDARD • YES • NO BY (COMPANY) F NO, EXPLAIN HOW FLUSHING FLOW WAS OBTAINED FIRE PUMP THROUGH WHAT TYPE OPENING 0 HYDRANT BUTT. ❑ OPEN PIPE • PUBLIC WATER • TANK 011 RESERVOIR • LEAD-INSACCORDING FLUSD ACCORDING TO RTANDARD • YES • NO BY (COMPANY) F NO, EXPLAIN HOW FLUSHING FLOW WAS OBTAINED FIRE PUMP THROUGH WHAT TYPE OPENING • PUBLIC WATER • TANK OR RESERVOIR • • Y CONN TO FLANGE & SPIGOT • OPEN PIPE 7. HYDROSTATIC TEST ALL NEW UNDERGROUND PIPING HY iTATICALLY TESTED AT PSI FOR HOURS 8. LEAKAGE TEST TOTAL AMOUNT OF LEAKAGE MEASURED GALS HOURS ALLOWABLE LEAKAGE GALS HOURS NUMBER INSTALLED 9' HYDRANTS TYPE AND MAKE ALL OPERATE SATISFAC aILY DYE Cl NO 10. CONTROL VALVES WATER CONTROL VALVES LEFT WIDE OPEN IF NO, STATE REASON ❑ YE:. ❑ NO HOSE THREADS OF FIRE DEPARTMENT CONNECTIONS AND HYDRANTS INTERCHANGEABLE 0 YE: 0 NO WITH THOSE OF FIRE DEPARTMENT ANSWERING ALARM 11. DATE LEFT IN SERVICE REMARKS 12. SIGNATURES NAME OF INSTALLING CONTRACTOR TESTS WITNESSED BY FOR PROPERTY OWNER (SIGNED) TITLE DATE FOR INSTALLING CONTRACTOR (SIGNED) TITLE DATE 13. CERTIFICATION This is to cei:ify that this automatic sprinkler system has been installed in accordance with the standards adopted by the Washington State Fire Marshal and N.F.P.A. Standard 13. Name of Firm Mailing Address Name Title Date (Signature of Firm Official) WHEN ALL APPLICABLE ITEMS THROUGH 13 HAVE BEEN COMPLETED THIS ORIGINAL FORM SHALL BE RETURNED TO THE STATE FIRE MARSHAL'S OFFICE 14. CONFIRMATION OF SPRINKLER SYSTEM INSTALLATION Name Title Date State Fire Marshal Representative Acceptable: . 0 YES 0 NO 15. COMMENTS. ADDITIONAL EXPLANATION AND NOTES (55 Back -655- City of Tukwila FIRE DEPARTMENT 444 Andover Park East Tukwila, Washington 98188-7661 (206) 575-4404 Fire Department Review (513) Control #89-414 Gary L. VanDusen, Mayor December 28, 1989 Re: Southcenter Corporate Square, Building #3, 575 Andover Park West, Tukwila, Wa. Dear Sir: The attached set of building plans have been reviewed by The Fire Prevention Bureau and are acceptable with the following concerns: 1. The total number of fire extinguishers required for your establishment is calculated at one extinguisher for each 3000 sq. ft. of area. The extinguisher(s) should be of the "All Purpose" (2A, 10 B:C) dry chemical type. Travel distance to any fire extinguisher must be 75' or less. (NFPA 10, 3-1.1) (UFC 10.301b) Extinguishers shall be installed on the hangers or in the brackets supplied, mounted in cabinents, or set on shelves (NFPA 10, 1-6.6), and shall be installed so that the top of the extinguisher is not more than 5 ft. above the floor. (NFPA 10, 1-6.6) (UFC 10.301) Extinguishers shall be located so as to be in plain view (if at all possible), or if not in plain view, they shall be identified with a sign stating, "Fire Extinguisher," with an arrow pointing to the unit. (NFPA 10, 1-6.3) (UFC 10.301) 2. Exit hardware and marking must meet the requirements of Uniform Fire Code Sections 12.104 & 12.114. Exit doors shall be openable from the inside without the use of a key or any special knowledge or effort. (UFC 12.104b) The exits from office #113 shall be separated by no less than one-half the diagonal of that office. City of Tukwila FIRE DEPARTMENT 444 Andover Park East Tukwila, Washington 98188-7661 (206) 575-4404 Page number 2 Gary L. VanDusen, Mayor Exit doors shall swing in the direction of exit travel when serving an occupant load of 50 or more. (UBC 3303) (UFC 12.101) Exits serving more than 50 occupants shall be served by illuminated exit signs. Exits shall be illuminated at any time the building is occupied. An emergency system shall automatically provide exit illumination upon failure of the main power supply. (UFC 12.113a) 3. Maintain sprinkler protection for all enclosed areas. (NFPA 13, 4-1.1.1) (UFC 10.302) All sprinkler drawings shall be prepared by companies licensed to perform this type of work. Drawings shall first be approved by the Washington Surveying & Rating Bureau, Factory Mutual Engineering or Industrial Risk Insurers, then by. the Tukwila Fire Department. No sprinkler work shall commence without approved drawings. (City Ordinance #1141 & NFPA 13, 1-9.1) (UFC 10.307) Hose stations are required. (Plans must be submitted to the Fire Marshal for approval prior to installation.) (City Ordinance #1141) (Removal of the hose stations requires, among other considerations, the written approval of the Fire Chief) 4. Your street address must be conspicuously posted on the building and shall be plainly visible and legible from the street. Numbers shall contrast with their background. (UFC 10.208) All required occupancy separations, area separation walls, and draft -stop partitions shall be maintained and shall be properly repaired, restored or replaced when damaged, altered, breached, penetrated, removed or improperly installed. (UFC 10.401) 0 City of Tukwila FIRE DEPARTMENT 444 Andover Park East Tukwila, Washington 98188-7661 (206) 575-4404 Page number 3 Gary L. VanDusen, Mayor All interior wall covering materials shall be fire -resistive or shall be treated to be fire -resistive, so as to result in a flame -spread rating as required by UFC Appendix VI -C tables 42A and 42B. A certificate of the flame spread rating is required to be delivered to the Tukwila Fire Department. (UBC 4204) (UFC 10.401) This review limited to speculative tenant space only special fire permits may be necessary depending on detailed description of intended use. Yours truly, The Tukwila Fire Prevention Bureau cc: T.F.D. File slj City Tukwila FIRE DEPARTMENT 444 Andover Park East Tukwila, Washington 98188-7661 (206) 575-4404 Fire Department Review Control Number 89-422 (513) Gary L. VanDusen, Mayor December 22, 1989 Re: Southcenter Corporate Square, Bldg. #3 - 575 Andover Park West, Tukwila, Wa. Dear Sir: The attached set of building plans have been reviewed by The Fire Prevention Bureau and are acceptable with the following concerns: 1. Maintain fire extinguisher coverage throughout. 2. Maintain sprinkler protection for all enclosed areas. (NFPA 13, 4-1.1.1) (UFC 10.302) 3. All required occupancy separations, area separation walls, and draft -stop partitions shall be maintained and shall be properly repaired, restored or replaced when damaged, altered, breached, penetrated, removed or improperly installed. (UFC 10.401) Obtain a welding permit from the Fire Department for the welding to be done on this job and the job with the control number of 89-423. Yours truly, The Tukwila Fire Prevention Bureau cc: T.F.D. file ncd City Tukwila FIRE DEPARTMENT 444 Andover Park East Tukwila, Washington 98188-7661 (206) 575-4404 Fire Department Review Control Number 89-025 (513) Gary L. VanDusen, Mayor March 8, 1989 Re: Southcenter Corporate Square - 575 Andover Park West, Tukwila, Wa. Dear Sir: The attached set of building plans have been reviewed by The Fire Prevention Bureau and are acceptable with the following concerns: 1. The total number of fire extinguishers required for your establishment is calculated at one extinguisher for each 3000 sq. ft. of area. The extinguisher(s) should be of the "All Purpose" (2A, 10 B:C) dry chemical type. Travel distance to any fire extinguisher must be 75' or less. (NFPA 10, 3-1.1) (UFC 10.301b) Extinguishers shall be installed on the hangers or in the brackets supplied, mounted in cabinents, or set on shelves (NFPA 10, 1-6.6), and shall be installed so that the top of the extinguisher is not more than 5 ft. above the floor. (NFPA 10, 1-6.6) (UFC 10.301) Extinguishers shall be located so as to be in plain view (if at all possible), or if not in plain view, they shall be identified with a sign stating, "Fire Extinguisher," with an arrow pointing to the unit. (NFPA 10, 1-6.3) (UFC 10.301) 2. No point in a sprinklered building may be more than 200 feet from an exit, measured along the path of travel. (UBC 3302) (UFC 12.101) Exit hardware and marking must meet the requirements of Uniform Fire Code Sections 12.104 & 12.114. Exit doors shall be openable from the inside without Cit?of Tukwila FIRE DEPARTMENT 444 Andover Park East Tukwila, Washington 98188-7661 (206) 575-4404 Page number 2 Gary L. VanDusen, Mayor the use of a key or any special knowledge or effort. (UFC 12.104b) Exits serving more than 50 occupants are required to have illuminated exit signs. (UFC 12.114) Exits shall be illuminated at any time the building is occupied. An emergency system shall automatically provide exit illumination upon failure of the main power supply. (UFC 12.113a) Second floor exits which enter the skybridge must be provided with exit doors and locks which (A) swing in the directions of travel and (B) may be opened in the directions of travel without a key or special knowledge. 3. An automatic fire extinguishing (sprinkler) system is required and shall be designed, installed and tested. (City Ordinance #1141) All sprinkler drawings shall be prepared by companies licensed to perform this type of work. Drawings shall first be approved by the Washington Surveying & Rating Bureau, Factory Mutual Engineering or Industrial Risk Insurers, then by the Tukwila Fire Department. No sprinkler work shall commence without approved drawings. (City Ordinance #1141 & NFPA 13, 1-9.1) (UFC 10.307) All sprinkler systems with more than 100 heads shall be supervised by an approved central, proprietary or remote station service or a local alarm which will give an audible signal at a constantly attended location. Approved central stations are those listed by Underwriter's Laboratories, Inc. (UFC 10.309) 4. Your street address must be conspicuously posted on the building and shall be plainly visible and legible from the street. Numbers shall contrast with their background. (UFC 10.208) City of Tukwila FIRE DEPARTMENT 444 Andover Park East Tukwila, Washington 98188-7661 (206) 575-4404 Page number 3 Gary L. VanDusen, Mayor All required occupancy separations, area separation walls, and draft -stop partitions shall be maintained and shall be properly repaired, restored or replaced when damaged, altered, breached, penetrated, removed or improperly installed. (UFC 10.401) All interior wall covering materials shall be fire -resistive or shall be treated to be fire -resistive, so as to result in a flame -spread rating as required by UFC Appendix VI -C tables 42A and 42B. A certificate of the flame spread rating is required to be delivered to the Tukwila Fire Department. (UBC 4204) (UFC 10.401) Yours truly, The Tukwila Fire Prevention Bureau cc: T.F.D. file ncd of Tukwila PLANNING DEPARTMENT 6200 Southcenter Boulevard —Tukwila, Washington 98188 (206) 433-1849 TO: FROM: DATE 24 PROJECT: OnC;-rZ. CORP Pak T2 -)14:q. O3 Sheet l0f The following corrections and/or clarifications are required to complete the ptan review. ( i u Alm RcoF � ?t1 c,TLJ 6 4LTzA-rf_o q t&) TIZt,lc,TLJRrscL CAL.cmemot s : CO HAT 1-0413)Bort{ Co E -t A -r ANp u N‘ FORM IS Th tS A TE I T�i�t �� �oR r GLA�ZN t r -c j u) .h c�4 VFobtnONAt_. 1)1a2L NS To ISE U €o . 'F -4 4x tz 4 4 x to cAu,e,n ?K o N-0,41IS Ms* "DeiAt .''. r 2, (JILL C�c.r=- c4t it RooFvC STe (.ovNAisl4 E To vitaec LO, S, G -- Cape IZIATS, i OtcATE_ 114A -c "E.McL IS ta+ rarvc E VALISES �i T P�(,E 4-3 . '� c.h.) 1.4O(A) c.o.( LL Coin Lc � or.. ��1a� T[�� ��CATIht� �t�-Io►�- tT 1=c -si 4 (10/T2.MEMO) +► Date:2-26-89 ORDINANCE COMPLIANCE CHECKLIST UNIFORM BUILDING CODE, 1965Ed. Sheet 190F I Project: ` 'xYT}ACet4T i Ct --p. �--�Xu lr GI , 13 Fi 1 e B9.O2� 5-35- Ai-Ne T- OC,CUPANCY GROUP: -1+3-2/ (js� TYPE OF CONSTRUCTION: \J e--kall-10-0.4-5 1K.1Scl.I.GP OM:e.g.-141S f) LOCATION ON PROPERTY: i�*S1-1( BLDG.HT./ NO of STORIES: 1 /O 2 - S -(Dig, `r • FLOOR AREA: Tp AL L - 5 /4altp et 6. OCCUPANT LOAD: II L. ammo /2p61/461.1.614 C/ n 6, L 20 � = DETAILED REQUIREMENTS: • er/Occupancy Type of Construction Exitingd QD Engineering Regs. & Reqmts. 60i 1}t ) 04,1 F C 6cl-00-e - O. Compliance w/ WSEC Compliance w/ Chapter 51-10 W.A.C. NOTES: C CITY OF TUK 'ILA Central Permit System ‘Atontrol No. $9-'cz> Permit No. FINAL APPROVAL FORM 2 NOV igRg TO: ❑ Building ❑ Planning ❑ Public Works Fire Dept. O Police 0 Parks/Recreation Project Name c.=. -ii -et ?e ---/74--p, 4- 5I��► f Address s-7'5' Type of Permit(s) T / r c /I) This project is nearing completion. Please investigate your area of responsibility and indicate below either your final approval or necessary corrections. If no response is received within one week, it will be assumed that the project is of no concern to your department and a certificate of occupancy may be issued. This project is NOT approved by this department; the following corrections are necessary: ( ) /r9 �C 4J G� f G"/ f7 P ( ) ( ) ( ) ( ) )w ( ) ( ) ( ) ( ) Authorized Signature Date This project is approved by this department: Auth. ed Signature Date CPS Form 3 ol CITY OF TU ILA Central Permit System Oontroi No 5"S 76 Permit No. g% -oz 5 FINAL APPROVAL FORM TO: ❑ Building ❑ Planning ❑ Public Works j- Fire Dept. d 114 le 11nil' -fl.lL- ue JAN 2 2 1990 ❑ Police ❑ Parks/Recreation C Project Name e-, /e �.,,,y�w �� s� �� i e Address ,1,,4/(.,4'4.' 6/ Type of Permit(s) T - This project is nearing completion. Please investigate your area of responsibility and indicate below either your final approval or necessary corrections. If no response is received within one week, it will be assumed that the project is of no concern to your department and a certificate of occupancy may be issued. This project is NOT approved. ;; is department; the fo owing corrections are necessary.: s At pe.,,s .. �;` #1 /rte Ae.1 r / }. / It C. Pix 71,37 ✓i s'i! ) C ./A ;€ //e /J/Jii✓r[1C�7 �-�. ✓J's®Q / r e- /G / 4e- //lCr+r�VA 4/ �� .►�f / r- q «e,c /L7ee 44'' /4 ✓m is ..54/..,%6lr 573 Authorized Signature 7s -g2 Date This project is approved by this department: p s7) / -,'9 - 9z Authorized Signature Date CPS Form 3 CITY OF TUKIALA Central Permit System Qntrol No F9 f) Y Permit No FINAL APPROVAL FORM TO: ❑ Building ❑ Planning ❑ Public Works Fire Dept. 111 Police ❑ Parks / Recreation Project Name 5--ce- sg ,AV -C Address s'7 5;01/11/04-/c-- Type ;01/11/G''c- Type of Permit(s) / This project is nearing completion. Please investigate your area of responsibility and indicate below either your final approval or necessary corrections. If no response is received within one week, it will be assumed that the project is of no concern to your department and a certificate of occupancy may be issued. This project is NOT approved by this department; the following corrections are necessary: () / y () () () () () () () () () () Authorized Signature Date 1 This project is approved by this department: Authorized Signature 7-47 p21 Date CPS Form 3 CITY OF TUILA Central Permit System ontrol No. S Permit No. S 8' FINAL APPROVAL FORM TO: ❑ Building ❑ Planning ❑ Public Works `K7 Fire Dept. APR 24 199* ❑ Police ❑ Parks/Recreation Project Name s�,.-7L4��A. • r Address ) 7.S � �,./� � . /� - �• <1. (d/O 3% Type of Permit(s) This project is nearing completion. Please investigate your area of responsibility and indicate below either your final approval or necessary corrections. If no response is received within one week, it will be assumed that the project is of no concern to your department and a certificate of occupancy may be issued. J This project is NOT approved by this department; the following corrections are necessary: O () h P�0f m / —j1., 1, 'y6 t 1 £ :•' () () O () () () () () Authorized Signature Date This project is approved by this department: Authorized Signature I="Z. ri3 Date CPS Form 3 Ilk . METROMARK INVESTMENT MANAGEMENT February 25, 1994 Ms. Norita Deckard Tukwila Fire Dept. 444 Andover Park East Tukwila, WA 98188-7661 RE: Change of Mailing Address Southcenter Corporate Square Southcenter Place Building Sent via Certified Mail Dear Ms. Deckard: Please change your records for the below office buildings. The management of these buildings is located at a new location. Please address all future correspondence for Southcenter Corporate Square to the following: Southcenter Corporate Square c/o Metromark Investment Management 14335 NE 24th St, Suite 202 Bellevue, WA 98007 Southcenter Corporate Square consists of 12 buildings with the following addresses: Building 1 545 Andover Park West Building 3 575 Andover Park West Building 5 625 Andover Park West Building 7 655 Andover Park West Building 9 665 Andover Park West Building 11 375 Andover Park West Building 2 565 Andover Park West Building 4 555 Andover Park West Building 6 645 Andover Park West Building 8 635 Andover Park West Building 10 360 Andover Park West Building 12 370 Andover Park West .ISH Properties, Inc. / 14335 NE 24th, Suite 202 / Bellevue, Washington 98007 206 454-6663 FAX: 206 454-1391 City of Tukwila Fire Department FIRE WATCH REQUIRED Due to the inoperative fire protection system(s) in your facility, you are required to provide a fire watch per City of Tukwila Ordinance #2437, section 16.40.120-D and Ordinance #2436, section 16.42.100-C (see reverse side). The fire watch shall be maintained until the system(s) are operational as determined by the Tukwila Fire Marshal's Office. FAX paperwork to 206-575-4439 to verify the completion of repair work and/or the restoration of system monitoring. in order to end the tire watch. The fire watch is required 24 hours a day. Designated employees may serve as the fire watch during business hours, while performing their regular job. Fire watch personnel must be aware of, and accept the duties of the fire watch. After hours fire watch personnel must be on location and must patrol the building following the close of business. Every two hours they must call 206-971-8737 and leave a message stating the following: Date: I. Your name. 2. Street address of firewatch location. 3. Time of day. 4. If everything is OK, state all clear. If you discover an emergency during your patrol , call 9-1-1 immediately to report it. [/4i -ii 7 Reason For Fire watch: Inspectors: \ Start time: It -130 Business Name: Z---ZeitIACejl....^(- Business Address: Incident #: Business Phone:57 S"--3:1)5?) Person in Charge: (AAA LA) Signature: W Fire Marshal's Office Y Owner Manager Rev. 719.114 T.F.D. Form F.P. 41 Tukwila Fire Marshal'x Office • Phone: 206-575-4407 • Fax: 206-575-4439 • Email: FireMarshantakwilawa.gov c ( 1) C) (3) I " ) () I/) cp,) (') 1) SUITE 101 ,/ ; / //` LEASED MFIRST FLOOR PLAN N -L-/ NOT TO SCALE modwev 30' NUR TH Marvin Stei &sociates, LLC planning design 2221 Fifth Avenue, Seat t le, Washington 98121 1206) 441-1449 COLLIERS INTERN NTiONAL (206) 223-0866 TIRE MARKETING PLAN SOUTHCENTER CORP. SQ. Job BUILDING 3 Job No. 99135-036 Dote 11/16/06 Sheet No. 3.1 (1 (a) (4) (5) (i vaccm SUITE 202 VACANT C9) (B) L% LEASED / MSECOND FLOOR PLAN NOT TO SCALE NORTH 5. 10' 20' 30" Marvin Ste sociates, LLC planning design 2221 Filth Aviiut, Sott le, WaNIIiiigton 98121 206) 4 4 1-1449 (206) 223-0866 TITLE MARKETING PLAN Job No. 99135-036 Date 11/16/06 SOUTHCENTER CORP. SQ. Job BUILDING 3 Sheet No. 3.2 Unit CompuPay, Inc Assured Imaging Women's Wellness Qwest/Equis Corporation v 1-201 VACANT ✓ 1-205 Hak Club for Men 5-5 .6400 33.0 12-101/ V1-209 0-211 ✓1-215 10-101 ✓ Hair Club For Men Resilient Commercial Coatings. Inc. Link Resources Corporation Le Cordon Bleu Home Depot USA, Inc Customer Research 72-102 American Fidelity Assurance Company 2-110 VACANT 2-119 VACANT �2-201x VACANT 3-1011, WA State Nurses Association 3-202 VACANT /3-205 Rainier Umsery Council 3-210 1-5 Direct Contact. LLC v4-101 CompuPay, Inc BSc s SqF 4-110 Level Two, Inc. 1,1 ✓4-201 Systematech Technical Mgmt Services /5-101 Medical Billing Solutions, Inc. s 5-107 VACANT 5-111 AFT Washington ✓5-201 / 6-601 U‘117 7-101 8-100 International Academy of Design & Tech International Academy of Design & Tech International Academy of Design & Tech VACANT. t J(_ =8-101 NUCA of Washington Wl)v 8-107 Building Amenities/Management Office,8-108 Kathy Ross 18.111 VACANT /8-200 SEWHealthcare NW Partnership •1 iTraining 01 V VACANT ((� �F ANTENNA SBA Communications Corporation PARKINGA United Parcel Service, Inc. PARKINGB VACANT Property Totals: