PP - 16038 WEST VALLEY HWY - SEATTLE SEATAC COURTYARD - PERMITS AND PLANS
16038 WEST VALLEY HWY ASSOCIATED PERMITS 19-S-080 D18-0298 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Courtyard by Marriott 16038 W Valley Highway Permit No.: 19-S-080 Date: April 30, 2019 Reviewer: Al Metzler Fire Protection Project Coordinator (206) 575-4407 option # 2 (Inspection Requests) (206) 971-8718 (Plan Review Questions) • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 'A inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • All valves controlling the water supply for automatic sprinkler systems and waterflow switches on all sprinkler systems shall be electrically supervised. • All interior control valves shall be readily accessible, labeled and located not more than 6 ft. above the floor. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 20 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2019 Edition. CITY OF TUKWILA FIRE MARSHAL'S OFFICE 206-575-4407 FIRE PROTECTION SYSTEMS PERMIT APPLICATION Applications and plans must be complete in order to be accepted for plan review. **PLEASE PRINT** SITE LOCATION Site Address: 16038 W Valley Hwy, Tukwila, WA 98188 Tenant Name: courtyard Marriott King Co. Assessor's Tax No.: 214,314,414 Suite Number: Floor: 2'3'4 Property Owner's Name: csM corporation New Tenant? ❑ - Yes j - No Mailing Address: 500 Washington Ave S, Ste 3000, Minneapolis, MN 55415 CONTACT PERSON -if there are questions about the submittal. Name: Justin Stivers Company Name: Red Hawk Fire Protection, LLC City State Zip Day Telephone: 253 -84o -990o Mailing Address: 801 Valley Ave NW, Ste D, Puyallup, WA 98371 E-mail Address: justins@redhawkfp.com Contractor's City of Tukwila Business License number: sus -0997549 City State Zip Fax Number: Total number of new/relocated devices or sprinkler heads: 9 Valuation of Project (contractor's bid price): $ 4,500 Scope of Work (please provide detailed information): Adding and/or relocation sprinklers to accommodate new walls and/or ceilings for the tenant improvement. PERMIT APPLICATION NOTES Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules. Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILDING 0 : ' OR AUTHO'. ZED AGENT: Signatur Print Name: Just Plan Permit App.doc PAID SPR 20 2019 TUKWILA FIRE Date: 4-26-2019 Day Telephone: 253-840-9900 8/22/14 TFD FP Form 8 INSPECTION NUMBER INSPECTION RECORD Retain a copy with permit JQ'S -O 9 C - 02--438 PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 206-575-4407 Project: ated"--.0( Type of Inspectio : f/Qtr//`-e Address: / Suite #: 603? lj'JV ity Contact Person: Special In ructions: Phone No.: Approved per applicable codes. Corrections required prior to approval. COMMENTS: plC fU '' a) 3, ?Ptss Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: c /..%-/// �'�3 Date: 672_41 Hrs.: (- o $100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. Call to schedule a reinspection. Billing Address Attn: Company Name: Address: City: State: Zip: Word/Inspection Record Form.Doc 3/14/14 T.F.D. Form F.P. 113 CORRECTION NOTICE/REINSPECTION FEE Inspector: P'71 Permit number: TUKWILA FIRE MARSHAL'S OFFICE Office: 206-575-4407 Fax: 206-575-4439 Email: Fire Marshal(cr�,tukwilawa.ov Business Name: , /� ZIT Type of Inspection �L .L �J - Location Location Address Date (9/ 2.- V/ / 7 Contact Person: i1lle, J t)11n Phone No. ,5 I oseo • ACTION REQUIRED : /ve-D ridd 604ea-40,-€ ecra-1-1--Ai LCL goo CORRECTION OF E E ITEMS ARE REQUIRED BY : � 77( FAILURE TO C 1 Y SULT IN THE ISSUANCE OF A ' M AL CITATION/TICKET. hWEIRO,16 Signature Billin Attn: gim Company Name: Address: City: State: Zip: ❑ A $100.00 Reinspection Fee is required. You will receive an invoice from the City of Tukwila Finance Department. ❑ Ticket Issued. Citation # Correction Notice Reinsp Fee2.doc Revised 6/17/14 T.F.D. Form F.P. 100 King County 0 CONTACT NAME/SIGNATU 14038 w ✓u/lv lty KING COUNTY ZONE 3 FIRE WATCH FORM V FIRE WATCH INSTRUCTIONS 1. Do not reset the alarm if alarm cause is likely a system malfunction. 2. Silence alarm if needed and direct the responsible party to request a service call. 3. Fill out all portions of the Agency Copy. 4. On the Site Copy; a. Fill out the incident number and b. Identify the fire watch frequency c. Circle the appropriate follow-up agency d. Identify which system is out -of -service. Leave the Site copy with the responsible party. Identify the person this form was left with. 5. 6. 7. If the Fire Watch was declined, identify the name of the individual who declined the fire watch. 8. Was the building secure when you left? ❑ Yes ❑ No If not, please explain what actions were taken. 9. 10. 11. Post placard if unable to contact a responsible party and/or when notification to building occupants is important. Fire watch placard posted? Y / N Scan and Email the Agency Copy to the appropriate Fire Marshal's Office. Include Agency Copy with your fire incident report. INCIDENT #: g ' o co 6-q (-/- REASON f REASON FOR FIRE WATCH: ' €.e4 ct-t wI( CP SYSTEM OUT OF SERVICE: Sprinkler ❑ Fire Alarm ❑ Monitoring ❑ Other Suppression ❑ Other e RESPONDING UNIT/COMPANY OFFICER: T5 t V Jk h BUSINESS NAME: C 4 /etit L1 i MQra/ ✓L Olt BUSINESS ADDRESS: 1(o 03g (A) V, �1 f 4W BUSINESS PHONE: 4-2-5 255 O3 OD BUSINESS CONTACT AND PHONE NUMBER: . Mj.t(' ZiAlt 415 (Al cy Copy — White Site Copy - Yellow Z3FM004A 01/2019 Burien/Normandy Park/KCFD#2 FMO u,BurienFire.org, Phone: 206-209-4119 Enumclaw Fire Department/KCFD#28 F ireM ars hal @ Enumc l awf i re. org King County Fire Marshal's Office FireMarshal@KingCounty.gov Mountain View Fire & Rescue/KCFD#44 Pkramlich(KCFD44.org, Phone: 253-735-0284, 253-569-4211 Port of Seattle Fire@PortSeattle.org Puget Sound Regional Fire Authority FirePrevention@PugetSoundFire.org, Phone: 253-856-4444 Renton Regional Fire Authority FireMarshal@RentonRFA.org South King Fire & Rescue Prevention. Division@SouthKingFire.org, Phone: 253-946-7348 Skyway/KCFD#20 Admin u,KCFD20.org, Phone: 206-772-1430 Tukwila Fire Department FireMarshal@TukwilaWA.gov Valley Regional Fire Authority FireMarshal cr,VRFA.org, Phone: 253-261-3616 Vashon Island Fire & Rescue Administration(vifr.org, Phone: 206-463-2405 Z3FM002 01/18 City of Tukwila Fire Department - p 'To 5c. `®_`..k_a-0`g @ -PO FIRE WATCH REQUIRED Due to the inoperative fire protection system(s) in your facility, you are required to provide a fire watch per City of Tukwila Ordinance #2437, section 16.40.120-D and Ordinance #2436, section 16.42.100-C (see reverse side). The fire watch shall be maintained until the system(s) are operational as determined by the Tukwila Fire Marshal's Office. FAX paperwork to 206-575-4439 to verify the completion of repair work and/or the restoration of system monitoring, in order to end the fire watch. The fire watch is required 24 hours a day. Designated employees may serve as the fire watch during business hours, while performing their regular job. Fire watch personnel must be aware of, and accept the duties of the fire watch. After hours fire watch personnel must be o location and must patrol the building following the close of business. Every two hours they must call 206-971-873 nd leave a message stating the following: 1. Your name. 2. Street address of firewatch location. 3. Time of day. 4. If everything is OK, state all clear. If you discover an emergency during your patrol , call 9-1-1 immediately to report it. Date: -7 - S Inspectors: Gth( Start time: o ea/6 e`ffP Reason For Fire watch: Dry- 6. y4/ PArttSted - c fie-fIncident #:) &77`i Business Name: ea rtef8A-fes M.9crl on -- Business Address: /6636 Business Phone: 75 9-55 d;00 Person in Charg In W - Fire Marshal's Office Y wner/Manager Rev. 7/29/14 T.F.D. Form F.P. 41 Tukwila Fire Marshal's Office • Phone: 206-575-4407 • Fax: 206-575-4439 • Email: FireMarshal@tukwilawa.gov 7_2_0—/(f. /-Z 5v -a z s 1,-)14Ate /71 PS sr .—,4.fin April 7, 2017 City of Tukwila Fire Department Mr. Kyle Johnson Courtyard Seattle Sea -Tac 16038 West Valley Highway Tukwila, Washington 98188 Dear Mr. Johnson: In reference to your email dated April 7, 2017, requesting an extension for compliance, I have made the following disposition. You are granted additional time to comply with all items listed on the Fire Department Correction Notice dated March 28, 2017. Your new inspection date is April 27, 2017. Any re -inspection fees already issued will not be waived. A re -inspection will be conducted on the above date to confirm correction of violations. Failure to correct the items listed in the original Correction Notice by the indicated date will result in a re- inspection fee. Yours truly, Battalion Chief Don Tomaso Fire Marshal Tukwila Fire Marshal's Office • 6300 Southcenter Blvd., Suite #209 • Tukwila, Washington 98188 • Phone: 206-575-4407 • Fax: 206-575-4439 • Email: FireMarshal@tukwilawa.gov . 11-Soc RED HAWK FIRE PROTECTION, LLC 801 Valley Avenue N.W. Suite D Puyallup, WA 98371 (253) 840-9900 tifret Vligurt FIRE SPRINKLER EQUIPMENT SUBMITTAL FOR Courtyard Marriott Tukwila, WA RHFP JOB NO. 19111088 TABLE OF CONTENTS RED HAWK FIRE PRorEcnoN, LLC Section 1 - Fire Sprinklers Description Viking VK430 QR Residential Pendent K=4.3 Viking VK484 QR Residential Horizontal Sidewall K=4.2 Comments Page 1 of 5 NIKING® TECHNICAL DATA FREEDOM® RESIDENTIAL PENDENT SPRINKLER VK430 (K4.3) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com 1. DESCRIPTION Viking Freedom® Residential Pendent Sprinkler VK430 is a thermosensitive, glass -bulb residential sprinkler available in several different finishes and temperature ratings to meet varying design requirements. The Electroless Nickel PTFE (ENT) coating has been investigated for installation in corrosive atmospheres and is C -UL -US -EU Listed as corrosion resistant as indicated in the Approval Chart. The orifice design, with a K -Factor of 4.3 (62 metric*), allows efficient use of available water supplies for the hydraulically designed fire -protection system. The fast response type glass bulb and special deflector combine speed of operation and area of coverage to meet residential sprinkler standards while being aesthetically pleasing. 2. LISTINGS AND APPROVALS c pt us UL Listed (C -UL -US -EU): Category VKKW --- NYC Approved: MEA 89-92-E, Volume 24 Refer to the Approval Chart on and Design Criteria for C -UL -US -EU Listing require- ments that must be followed. /� WARNING: Cancer and Reproductive Harm- / l www.P65Warnings.ca.gov 3. TECHNICAL DATA Specifications: Minimum Operating Pressure: Refer to the Approval Chart. Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to 500 psi (34.5 bar). Thread size: 1/2" (15 mm) NPT Nominal K -Factor: 4.3 U.S. (62 metric`) * Metric K -factor measurement shown is for when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K -factor shown by 10.0. Glass -bulb fluid temperature rated to -65 °F (-55 °C) Overall Length: 2-1/4" (58 mm) Material Standards: Frame Casting: Brass UNS-C84400 or QM Brass Deflector: Brass UNS-C26000 Bulb: Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape Compression Screw: Brass UNS-C36000 Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 Pip Cap Attachment (for QM Brass sprinklers only): Brass UNS-C36000 For ENT coated sprinklers: Belleville spring - Exposed. Screw and Pipcan - ENT plated. Available Finishes and Temperature Ratings: Finish . Brass "Chrome White.Polyester Black Polyester ' _ ENT ' -, Suffix A F M -IW M -/B JN =Temperature` ,e155 °F (68 °C) 175.°F (79°:C) . ,, _- -- Suffix B D -- -- -- Ordering Information: (Refer to Table 1.) 4. INSTALLATION Refer to appropriate NFPA Installation Standards. 5. OPERATION During fire conditions, the heat -sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. Form No. F_082095 19.02.21 Rev 18.2 .P65 Replaces Form No. F_082095 Rev 18.2 (Removed F-1 Escutcheon.) Page 2 of 5, NIKING® TECHNICAL DATA FREEDOM® RESIDENTIAL PENDENT SPRINKLER VK430 (K4.3) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com 7. AVAILABILITY The Viking Model VK430 Sprinkler is available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking's current list price schedule or contact Viking directly. Sprinkler Base Part • No. Size TABLE 1: ORDERING Instructions: Using the (1) add the suffix (2) add the suffix for 1: Finishes,._;_, _ . INFORMATION sprinkler base part number, for the desired Finish the desired Temperature Rating. 2: Temperature.Ratings .._ __..,..-„.....w.� .a.,,:...,;,4... NPT Inch BSP mm Description 'Suffix' Nominal Rating Bulb Color Max. Ambient Ceiling Temperature- Suffix. 09530 1/2 -- Brass A 155 °F (68 °C) Red 100 °F (38 °C) B Chrome F 175 °F (79 °C) Yellow 150 °F (65 °C) D White Polyester 4.5 M -/W Black Polyester 4.5 M -/B ENT 4.5 JN Example: 09530AB = VK430 with Brass Finish and 155 °F (68 area with a maximum ambient temperature of 100 °F (38 °C) ambient rating, you shall use a higher temperature -rated sprinkler. °C) Nominal temperature rating. This sprinkler is to be installed into an meaning if the area will experience temperatures above the maximum Accessories Sprinkler Wrenches (see Figure 1): A. Standard Wrench: Part No. 21475M/B. B. Recessed Socket Wrench: Part No. 13655W/B2. C. Protective Sprinkler Cap/Escutcheon installation tool' 15915. Sprinkler Cabinet: A. Up to 6 sprinklers: Part number 01724A. B. 6-12 Sprinklers: Part number 01725A. Footnotes 1. Where a dash (-) is shown in the Finish suffix designation, insert the desired Temperature Rating suffix. See example above. 2. Requires a 1/2” ratchet which is not available from Viking. 3. Based on NFPA 13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 4. UL Listed as corrosion resistant. 5. The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Chart. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway. 6. Allows installation from the floor by attaching a length of 1" diameter CPVC tubing to the tool. Ideal for sprinkler cabinets. Refer to Bulletin F_051808. Form No. F_082095 19.02.21 Rev 18.2 .P65 Page 3 of 5 NIKING® TECHNICAL DATA FREEDOM° RESIDENTIAL PENDENT SPRINKLER VK430 (K4.3) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com Approval Chart Viking VK430, 4.3 K -Factor Residential Pendent Sprinkler For systems designed to NFPA 13D or NFPA 13R. For systems designed to NFPA 13, refer to the design criteria on page 5. For Ceiling types refer to current Editions of NFPA 13, 13R or 130 Sprinkler Base Part Number' SIN NPT Thread Size Nominal K -Factor Maximum Water Working Pressure Overall Length Inches mm U.S. metric 2 Inches mm 09530 VK430 1/2 15 4.3 62 175 psi (12 bar) 2-1/4 58 Max. Cover- age Area° Ft.X Ft. (m X m) Ordinary Temp Rating (155 °F/68 °C) Intermediate Temp Rat- ing (175 °F/79 °C) Deflector to Ceiling Installation Type Listings and Approv- als 3 Minimum Spacing Ft. m ( ) Flow° GPM (Umin) Pressure° PSI (bar) Flow° GPM (L/min) Pressure° PSI (bar) 5 C 4L us SU NYC' NSF8 12 X 12 (3.7 X 3.7) 12 (45.4) 7.8 (0.54) 12 (45.4) 7.8 (0.54) 1-1/8 to 2 inch Standard surface - mounted escutch- eons or recessed with the Mi- cromatic® Model E-1, E-2, or E-3 Recessed Escutcheon See Foot- note 6 and 10 See Foot - note 6 See Foot- note 6 8 (2.4) 14 X 14 (4.3 X 4.3) 13 (49.2) 9.1 (0.63) 13 (49.2) 9.1 (0.63) 16 X 16 (4.9 X 4.9) 13 (49.2) 9.1 (0.63) 13 (49.2) 9.1 (0.63) 18 X 18 5.5 X ( 5.5 ) 17 ( 64.4 ) 15.6 ( 1.08 ) 17 (64.4) 15.6 (1.08) 20 X 20 (6.1 X 6.1) 21 (79.5) 23.9 (1.64) 21 (79.5) 23.9 (1.64) Footnotes 1. Part number shown is the base part number. For complete part number, refer to Viking's current price schedule. 2. Metric K -factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K -factor shown by 10.0. 3. This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional ap- provals. Refer also to Design Criteria on page 5. 4. For areas of coverage smaller than shown, use the "Flow" and "Pressure" for the next larger area listed. Flows and pressures listed are per sprinkler. 5. Listed by Underwriter's Laboratories, Inc. for use in the U.S., Canada, and European Union. 6. Approved Finishes are: Brass, Chrome, White Polyester, and Black Polyester 9. 7. Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E, Vol. 24. 5. UL Classified to: NSF/ANSI Standard 61, Drinking Water System Components (MH48034). 9. Other paint colors are available on request with the same C -UL -US -EU listings as the standard finish colors. 10. Approved finish is Electroless Nickel PTFE (ENT). ENT is C -UL -US -EU Listed as corrosion resistant. ENT is available with standard surface -mounted escutcheons or the Micromatic Model E-1 Recessed Escutcheon. Form No. F_082095 19.02.21 Rev 18.2 .P65 Page 4 of 5, NUKING® TECHNICAL DATA FREEDOM° RESIDENTIAL PENDENT SPRINKLER VK430 (K4.3) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com DESIGN CRITERIA` (Also refer to the Approval Chart on page 3.) UL Listing Requirements (C -UL -US -EU): When using Viking Residential Pendent Sprinkler VK430 for systems designed to NFPA 13D or NFPA 13R, apply the listed areas of coverage and minimum water supply requirements shown in the Approval Chart on page 3. For systems designed to NFPA 13: The number of design sprinklers is to be the four contiguous most hydraulically demanding sprinklers. The mini- mum required discharge from each of the four sprinklers is to be the greater of the following: • The flow rates given in the Approval Chart on data page 3 for NFPA 13D and NFPA13R applications for each listed area of coverage, 2E • Calculated based on a minimum discharge of 0.1 gpm/sq. ft. over the "design area" in accordance with sections 8.5.2.1 or 8.6.2.1.2 of NFPA 13. • Minimum distance between residential sprinklers: 8 ft. (2.4 m). IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080190, F_080814, and F_080415 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA and any other similar Authorities Having Jurisdiction, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Final approval and acceptance of all residential sprinkler installations must be obtained from the Authorities Having Jurisdiction. Sprinkler Wrench 13655W/B** for installing recessed pendent sprinklers (A 1/2" ratchet is required. Not available from Viking.) Carefully slide the wrench sideways around the protective cap, ensuring engagement with the sprinkler wrench flats. Figure 2: Wrench 13655W/B for Recessed Pendent Sprinklers Form No. F_082095 19.02.21 Rev 18.2 .P65 Page 5 of 5 NIKINGi® TECHNICAL DATA FREEDOM® RESIDENTIAL PENDENT SPRINKLER VK430 (K4.3) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com Ceiling Opening Size: 2-5/16" (59 mm) minimum 2-1/2" (64 mm) maximum Installed with a standard 1/8" surface -mounted escutcheon Figure 3: Sprinkler Dimensions with a Standard Surface Mount Escutcheon ilk 2-1/8" Ceiling Opening Size: 2-5/16" (59 mm) minimum 2-1/2" (64 mm) maximum (54 mm) 7 1-3/4" (45 mm) Max. i Installed with a Model E-1 Recessed Escutcheon 1-1/8" (29 mm) 2" Min. (51 mm) Max. i0111.111.111" Installed with a Model E-2 Thread -on Recessed Escutcheon 1-1/8" (29 mm) Min. Figure 4: Sprinkler Dimensions with the Model E-1 and E-2 Recessed Escutcheons Form No. F_082095 19.02.21 Rev 18.2 .P65 Replaces Form No. F_082095 Rev 18.2.P65 (Removed F-1 Escutcheon.) Page 1 of 5, VIKING® TECHNICAL DATA FREEDOM® RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK484 (K4.2) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com 1. DESCRIPTION Viking Freedom® Residential Horizontal Sidewall Sprinkler VK484 is a small, thermosensitive, glass -bulb residential sprinkler available in several different finishes and temperature ratings to meet varying design requirements. The Electroless Nickel PTFE (ENT) coating has been investigated for installation in corrosive atmospheres and is cULus Listed as corrosion resistant as indicated in the Approval Chart. The sprinkler orifice design, with a K -factor of 4.2, allows efficient use of available water supplies for the hydraulically designed fire -protection system. The glass bulb operating element and special deflector characteristics meet the challenges of residential sprinkler standards. 2. LISTINGS AND APPROVALS c®ea cULus Listed: Category VKKW Refer to the Approval Chart and Design Criteria for cULus Listing requirements that must be followed. 3. TECHNICAL DATA Specifications: Available since 2011. Minimum Operating Pressure: Refer to the Approval Chart. Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to 500 psi (34.5 bar). Thread size: 1/2" (15 mm) NPT Nominal K -Factor: 4.2 U.S. (57 metrict) t Metric K -factor measurement shown is in Bar. When pressure is measured in kPa, divide the metric K -factor shown by 10.0. Glass -bulb fluid temperature rated to -65 °F (-55 °C) Overall Length: 3" (76 mm) Material Standards: Frame Casting: QM Brass Deflector: Brass UNS-C23000 Bulb: Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Polytetrafluoroethylene (PTFE) Compression Screw: Brass UNS-C36000 Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 Pip Cap Attachment: Brass UNS-C36000 For ENT coated sprinklers: Belleville spring - Exposed. Screw and PiocaD - ENT plated. Ordering Information: (Also refer to the current Viking price list.) Sprinkler: Base Part No. 16240 Order Sprinkler VK484 by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the tempera- ture rating to the sprinkler base part number. Finish Suffix: Brass = A, Chrome = F, White Polyester = M -W, Black Polyester = M -B, and ENT = JN Temperature Suffix: 155 °F (68 °C) = B, 175 °F (79 °C) = D For example, sprinkler VK484 with a Brass finish and a 155 °F (68 °C) temperature rating = Part No. 16240AB. Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the Viking website.) Sprinkler Wrenches: A. Standard Wrench: Part No. 21475MB (available since 2017) B. Wrench for recessed sprinklers: Part No. 13655WBtt (available since 2006) ttA Y.' ratchet is required (not available from Viking). Sprinkler Cabinets: A. Six -head capacity: Part No. 01724A (available since 1971) B. Twelve -head capacity: Part No. 01725A (available since 1971) it WARNING: Cancer and Reproductive Harm- www. P65Wamings.ca.gov Form No. F_050310 19.02.21 Rev 19.1 Replaces Form No. F_050310 Rev 18.1.P65 (Removed F-1 Escutcheon.) Page 2 of 5 NUKING® TECHNICAL DATA FREEDOM° RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK484 (K4.2) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com 4. INSTALLATION Refer to appropriate NFPA Installation Standards. 5. OPERATION During fire conditions, the heat -sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY The Viking Model VK484 Sprinkler is available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking's current list price schedule or contact Viking directly. TABLE 1: Sprinkler Temperature Classification AVAILABLE SPRINKLER TEMPERATURE Sprinkler Nominal Temperature Rating' RATINGS AND FINISHES Maximum Ambient Bulb Color Ceiling Temperature2 Ordinary 155 °F (68 °C) 100 °F (38 °C) Red Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester, and ENT Corrosion Resistant Coatings': ENT Footnotes ' The sprinkler temperature rating is stamped on the deflector. 2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Chart. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compat- ible with or suitable for the proposed environment. For ENT coated sprinklers, the waterway is coated. Note that the spring is exposed on sprinklers with ENT coating. Wrench Flat 1111140112(1,1 • • Protective Sprinkler Shield 21475 Figure 1: Standard Sprinkler Wrench 21475MB Form No. F_050310 19.02.21 Rev 19.1 Page 3 of 5, NIKING8 TECHNICAL DATA FREEDOM® RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK484 (K4.2) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com Approval Chart Viking VK484, 4.2 K -Factor Residential Horizontal Sidewall Sprinkler For systems designed to NFPA 13D or NFPA 13R, For systems designed to NFPA 13, refer to the design criteria. For Ceiling types refer to NFPA 13, 13R or 13D current editions NPT Thread Size Nominal K -Factor Overall Length Sprinkler Base Part SIN Maximum Water Working Number' Pressure Inches mm U.S. metric 2 Inches mm 16240 VK484 1/2 15 4.2 57 175 psi (12 bar) 3 76 Max. Coverage Ordinary Temp Rating (155 °F/68 °C) Intermediate Temp Rating (175 °F/79 °C) Listings and Approvals 3 Area 4 Max. To of Minimum Width X Length Spacing p Deflector Installation Spacing Ft. X Ft. Ft. Flow 4 Pressure 4 Flow 4 Pressure' to Ceiling Type Ft. (m X m) (m) GPM PSI GPM PSI cULus5 NYC (m) (L/min) (bar) (L/min) (bar) 12 X 12 (3.7 X 3.7) 12 (3.7) 13 (49.2) 9.6 (0.66) 13 (49.2) 9.6 (0.66) 14 X 14 (4.3 X 4.3) 14 (4.3) 14 (53.0) 11.1 (0.77) 15 (56.8) 12.8 (0.88) 16 X 16 (4.9 X 4.9) 16 (4.9) 16 (60.6) 14.5 (1.00) 17 (64.4) 16.4 (1.13)4 to 6 inches Standard surface - 16 X 18 (4.9 X 5.5) 16(4.9) 19(71.9) 20.5 (1.41) 19(71.9) 20.5 (1.41) mounted escutcheons 16 X 20 (4.9 X 6.1) 16 (4.9) 22 (83.3) 27.4 (1.89) 22 (83.3) 27.4 (1.89) or recessed with the Micromatic® See Footnotes 7 and 9. See Footnote 6 8 (2.4) 12 X 12 (3.7 X 3.7) 12 (3.7) 14 (53.0) 11.1 (0.77) 14 (53.0) 11.1 (0.77) 14 X 14 (4.3 X 4.3) 14 (4.3) 16 (60.6) 14.5 (1.00) 16 (60.6) 14.5 (1.00) Model E-1, E-2, E-3, or 16 X 16 (4.9 X 4.9) 16 (4.9) 18 (68.1) 18.4 (1.27) 18 (68.1) 18.4 (1.27) 6 to 12 inches G-1 Recessed Escutcheon 16 X 18 (4.9 X 5.5) 16 (4.9) 20 (75.7) 22.7 (1.56) 20 (75.7) 22.7 (1.56) 16 X 20 (4.9 X 6.1) 16 (4.9) 25 (94.6) 35.4 (2.44) 25 (94.6) 35.4 (2.44) Footnotes 'Part number shown is the base part number. For complete part number, refer to Viking's current price schedule. 2 Metric K -factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K -factor shown by 10.0. 3 This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals. Refer also to Design Criteria. 4 For areas of coverage smaller than shown, use the "Flow" and "Pressure" for the next larger area listed. Flows and pressures listed are per sprinkler. 'Listed by Underwriter's Laboratories, Inc. for use in the U.S. and Canada. 6 Meets New York City requirements, effective July 1, 2008. 'Approved Finishes are: Brass, Chrome, White Polyester, and Black Polyester 8 8 Other paint colors are available on request with the same cULus listings as the standard finish colors. 9 Approved finish is Electroless Nickel PTFE (ENT). ENT is cULus Listed as corrosion resistant. ENT is available with standard surface -mounted escutcheons or the Micromatic Model E-1 Recessed Escutcheon. Form No. F_050310 19.02.21 Rev 19.1 f Page 4 of 5 \IIKJNG® TECHNICAL DATA FREEDOM® RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK484 (K4.2) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com DESIGN CRITERIA (Also refer to the Approval Chart.) cULus Listing Requirements: When using Viking Residential Sprinkler VK484 for systems designed to NFPA 13D or NFPA 13R, apply the listed areas of coverage and minimum water supply requirements shown in the Approval Chart. For systems designed to NFPA 13: The number of design sprinklers is to be the four contiguous most hydraulically demanding sprinklers. The minimum required discharge from each of the four sprinklers is to be the greater of the following: • The flow rates given in the Approval Chart for NFPA 13D and NFPA13R applications for each listed area of coverage, 21- • • Calculated based on a minimum discharge of 0.1 gpm/sq. ft. over the "design area" in accordance with sections 8.5.2.1 or 8.6.2.1.2 of NFPA 13. • Minimum distance between residential sprinklers: 8 ft. (2.4 m). • The VK484 horizontal sidewall sprinkler deflector shall be located a minimum of 1-3/4" (44.5 mm) and a maximum of 6" (152 mm) from the wall on which it is installed. DEFLECTOR POSITION: Install Viking Residential Horizontal Sidewall Sprinkler VK484 with the leading edge of the deflector oriented parallel with the ceiling and the sprinkler frame arms oriented perpendicular to the ceiling. Refer to the Approval Chart for the required distance between the top of the deflector and the ceiling. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA and any other similar Authorities Having Jurisdiction, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Final approval and acceptance of all residential sprinkler installations must be obtained from the Authorities Having Jurisdiction. Protective Sprinkler Shield Sprinkler Wrench Part No. 13655W/B** for Recessed Horizontal Sidewall Sprinklers Fit the wrench over the sprinkler and protective shield as shown. \ \ \ 1? ii I ii I \,\ ',ii // **Note: A 1/2" ratchet is required (not available from Viking). Figure 2: Wrench 13655W/B for Recessed Sprinkler VK484 Form No. F_050310 19.02.21 Rev 19.1 • Page 5 of 5. VIKING® TECHNICAL DATA FREEDOM® RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK484 (K4.2) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs©vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com 1/2' (15 mm) NPT 3' (76 mm) 1-11/32' (34,5 mm) _a! HSW Sprinkler 16240 (VK484) Installed with a standard 1/8' (3.1 mm) surface -mounted escutcheon Figure 3: Sprinkler VK484 Dimensions with a Standard Escutcheon Wall Opening SIze: 2-5/16' (58.7 mm) minimum 2-1/2' (63.5 mm) maximum Wall Opening Size 2-5/16' (58.7 mm) minimum 2-1/2' (63.5 mm) maximum 1-15/16' (37.3 mm) Minimum 2-1/8' (54 mm) 2-9/16' (65 mm) Maximum Installed with a Micromatic Model E-1 Recessed Escutcheon 2-1/8' (54 mm) 1 For use with sloped ceilings. Wall Opening Sizer 2-5/8' (66 mm) minimum 2' 3-3/4' (95 mm) maximum (50.8 mm) Minimum 2-3/4' (70 mm) Maximum Installed with a Model E-2 Thread -on Recessed Escutcheon T- 71==== 66 nn 2-5/8' Maximum Recess: 1/2' (12.7 mm) Installed with a Model G-1 Recessed Escutcheon Figure 4: Sprinkler VK484 Dimensions with Model E-1, E-2, and G-1 Recessed Escutcheons Form No. F_050310 19.02.21 Rev 19.1 Replaces Form No. F_050310 Rev 18.1.P65 (Removed F-1 Escutcheon.) PRE -DRILL HOLE — -- 3/8" ALL THREAD ROD RING HANGER, SAMMY SCREW PIPE (2" MAX.) HANGER - 14W SAMMY SCREW SOLID WOOD JOIST E -* • FASTENER WOOD STRUCTURAL ATTACHMENT 3/8" ALL THREAD ROD BRANCH LINE RESTRAINT DEVICE (CSBBRP) HANGER - WG BRANCH LINE RESTRAINT 1 7-6 1 0-10 A� 01 "F-10 .11 DOOM 214 6-3Y2 to t0 11 ROOM 214 FIRE SPRINKLER TI PLAN 0 1 2 4 8 SCALE 1/4"=l'-0" SAMMY SCREW 318" ALL THREAD ROD ----- — PIPE (2" MAX.) ---- RING HANGER --------- HANGER - 14W SAMMY SCREW ❑ Without Comments ❑ As Noted in Red Per The Attached `etter These plans have bems- 'revent on Bureau- :•-andards. Accep!-: --.-- 5, nissions which CC. ) �. candaras and or t1,; i ri adequacy of design r-== ;additions, deletions this date will void resubmittal o` r,.;ri viewed by The Tukwila Fire .=orrnance •;tin current City _._t ct to errors aid _ adopted ,IY ..7i%ul�e .by for the witn the designer. these drawings after re,--uire a i Lr�t approval. Final acceotar c= _ . {- ._ :. t and inspection b The Tukwila Fire ?reventoo '`urea u. Br, Dote: L _ 1.. 0-10\ A N 1'/4 1 0 0-10 110 7-4% ... i:OOM 314 U -O ) 6-5 M 1 Pik•(rtv:= gli V.-.-...V,:. + and jC rf t of I•bws.��'S`tN'�Y3f i Zs t EdS .. ly ROOM 314 FIRE SPRINKLER TI PLAN 0 1 2 4 8 SCALE 1/4"=l'-0" 1 Manufacturer 7-0 Viking Viking Viking Type Response I SIN Sidewalll Quick iVK484 Pendent; Quick I VK430 Pendent] Quick 1VK430 Sprinkler Legend K -Factor 1 :;t A 0 4S O� ! 1'J4 +O�`• 0 0-10'r 110 `- o 7-0 7-41/2 kOOM 414 8'0 6-5 (0 r I I 5.6 4.9 4.9 Size ROOM 414 FIRE SPRINKLER TI PLAN 0 1 2 4 SCALE 1 /4"=1'-0" Temperature 155°F 175°F 155°F Finish White White White Spacing 16 x 18 16 x 16 16 x 16 Discharge Quantity 20 gpm @ 22.7 psi 13 gpm @ 9.1 psi 13 gpm @ 9.1 psi 3 3- 3 Total = 9: - SCOPE OF WORK THIS PROJECT ISATENANT IMPROVEMENT. RED HAWK FIRE PROTECTION IS ADDING AND / OR RELOCATING SPRINKLER TO ACCOMMODATE NEW WALLS AND rrii !Kir EXCLUSIONS PAINTING OR LABELING OF PIPE AND/OR EQUIPMENT ELECTRICAL WIRING OF ANY KIND INCLUDING BUT NOT LIMITED TO WATERFLOW SWITCH, ELECTRIC BELL, AND TAMPER SWITCHES CENTRAL STATION MONITORING EQUIPMENT, WIRING AND SERVICES ALL UNDERGROUND WORK INCLUDING BUT NOT LIMITED TO: BACKFILL, SELECT FILL, BREAKING PATCHING, SAW CUTTING, LAWN REPAIR, LANDSCAPING, TREE REMOVAL, STERILIZATION, DEVELOPMENT FEES AND CITY CONNECTION. GENERAL NOTES 1. SPRINKLER SYSTEM DESIGN PER NFPA #13. 2. ALL MATERIALS SHALL BE NEW AND UL AND/OR FM APPROVED. 3. FIRE SPRINKLER SYSTEM TO BE INSTALLED, BRACED AND TESTED IN ACCORDANCE WITH NFPA #13. 4. IN LOCALITIES SUBJECT TO FREEZING CONDITIONS IT IS THE OWNERS RESPONSIBILITY TO PROVIDE HEAT THROUGH OUT THE WET PIPE SPRINKLER SYSTEM AREAS AND IN ENCLOSURES FOR DRY PIPE, DELUGE AND OTHER TYPES OF VALVES CONTROLLING WATER SUPPLIES TO SPRINKLER SYSTEMS. 5. FIRE PROTECTION CONTRACTOR SHALL NOT BE RESPONSIBLE FOR THE ABILITY OF THE STRUCTURE TO ADEQUATELY SUPPORT THE FIRE SPRINKLER SYSTEM OR ANY APPURTENANCES THEREOF. 6. ALL ELECTRICAL, PAINTING OF PIPE, FURRING, CUTTING OR PATCHING TO BE BY OTHERS. 7. 1" - 1 %" PIPING TO BE SCHED 40 WITH THREADED FITTINGS. 8. ALL PENDENT HEADS TO BE LOCATED IN CENTER LINE OF CEILING TILES. TENANT IMPROVEMENT T HIS PROJECT ISA TENANT IMPROVEMENT. THIS FACILITY HAS ALREADY BEEN i ROTECTED BYA FIRE SPRINKLEP SYSTEM. RED HAWK FP IS ADD:NG AND/OR RELOCATING SPRINKLER HEADS TO ACCOMMODATE THE NEW TENANT WALL, CEILING, LIGHTING AND HVAC LAYOUT. ALL WORK WILL BE DONE WITHOUT EFFECTING THE CAPABILITY OF THE EXISTING SYSTEM. SYMBOL LEGEND 0 R - DENOTES A SPRINKLER HEAD TO BE RELOCATED. OA - DENOTES A SPRINKLER HEAD TO BE ADDED. 0E - DENOTES A SPRINKLER TO REMAIN. MT - MECHANICAL TEE - REPRESENTS EXISTING SPRINKLER PIPE. REPRESENTS NEW SPRINKLER PIPE. VICINITY MAP ukwila Palk: I ewe 5 I'r the in,prniement >ADrCllr.:±Print ('l ,;c>uet Ti,kW 1a A ' 1 Vail 8 west y Highway SITE LOCATION Se:altit> F=ri,angtt iG! Sr�taltu:tnter _. Fed E"rdl Reser RED HAWK FIRE PROTECTION, LLC fifrce *Art 801 VALLEY AVE NW, SUITE D PUYALLUP, WA 98371 PHONE: (253) 840-9900 FAx (800) 591-4382 WA CL# REDHAHF901 QP NICET Stamp WASHINGTON STATE CERTIFICATE OF COMPETENCY FIRE PROTECTION SPRINKLER SYSTEMS David Fox 0121-0409-C Level 3 Red Hawk Fire Protection, LLC REDHAWHF901QP Signature N v 0 s 0 iExpires 12/31/19 Approvals Required CITY OF TUKWILA OWNER /ARCHITECT Revisions Contract With: COURTYARD MARRIOTT 16038 W VALLEY HWY TUKWILA, WA 98188 PM: FELIX HERRAWA Phone: 503-572-5458 Contract Name: COURTYARD MARRIOTT 16038 W VALLEY HWY TUKWILA, WA 98188 Drawing Title FIRE SPRINKLER TI PLAN Key Plan Date: Job Number: Designer: Building Permit: April 26, 2019 19111088 JUSTIN STIVERS Drawing No. FP 1.00 PAID /°R 2s 2319 TUKWILA FI R E cc ,1_30-v — 7-77�� (%/ 16038 WEST VALLEY HWY ASSOCIATED PERMITS 12-F-181 06-5-210 12-S-195 (2) %"x2J" LAG BOLT STRUT PIPE CLAMP STRUT STRUT SUPPORT ON FRAMED WALL NOTE: THE OVER HEAD SPRiNKL"ER SYSTEM iS EXISTING. FOR iNSTAL"L-ATiON OF TENANT IMPROVEMENT WORK ONLY. E 11-612 1 1 tOFFIT HEIGHT 6'-1' II E - 1 0 1 111 1 1' 4' GRAPHIC SCALE 1 14-612 8 2 A CEiLING +-1EiG 4T 81-011 TYP- A 1 FIRE SPRINKLER PIPING PLAN SCALE 1/4' • 1-0 FLAG NOTES 11E INTO EXISTING SYSTEM FIELD / LISTING NOTES 1 THREADED PIPE FROM 1" THRU 2" SIZE TO BE DYNA-THREAD THREAD PIPE (IMPORT). 2 ALL THREADED FITTINGS ARE TO BE 175# CLASS CAST IRON (IMPORT) 3 ALL PIPE LENGTHS SHOWN ARE CUT LENGTH DIMENSIONS. 4 EXISTING PIPE SIZE UNKNOWN, FIELD SPOT REQUIRED. 5 USE WALL STUDS FOR HANG POINTS WITH DESIGNATED HANGERS. SIRE SF1INKLEf LEGEND EXISTING PIPE: NEW FIFE: x x ADDED SPRINKLER: X -X EXISTING SPRINKLER E 10 11 12 T Without CornmGnis �] As Nord In fad • Per The Attached fetter These plans have been reviewed by The Tukwifia Fire Prevention Bureau for conformance with current city standards. Acceptance is eubjt> t to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the _adequacy of design rests totally with the designer. Additions, deletions or; visions to these drawings after ':res date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: `O -/rP - 0 S- By: / y ° -' 31/ TUKWILA FiRE DEPARTMENT, Please call: 575-440Z and give this job No. 0 and exact address for shut. ;own or restoration approver 3 1441fi outticentsr... ' St:ander Blvd q}Fait i53 vOtdt4` t117 -St" -L---- -- L _ y ji #z I Kent w 1 VAC INiTY MAP MOT TO eCALE T.I. LOCATION 2ND FLOOR KEYPLAN NOT TO SCALE PROJECT DATA: BUILDING CODE: 2003 IBC OCCUPANCY GROUP: M CONSTRUCTION TYPE: III -A SPRINKLER LOCATION: ROOM 214 SECOND FLOOR PROJECT ADDRESS: COURTYARD BY MARRIOTT 16035 NEST VALLEY HIGHWAY SEATTLE, NA 98188 AREA OF SALES OFFICE: 345 SQ. FT. SCOPE OF WORK 1 ADD (2) NEW SIDEWALL SPRINKLERS IN REMODELED TENANT IMPROVEMENT AREA FROM EXISTING WET SYSTEM. GENERAL NOTES 1 THE OVER -HEAD SPRINKLER SYSTEM iS EXISTING. 2 ALL NEW PIPE SHALL BE DMA -THREAD WITH 115 lb. BLACK CAST IRON FITTINGS OR GROOVED WITH GROOVED FITTINGS 4 COUPLINGS, AS SHOUi1. 3 ALL HANGERS TO BE INSTALLED IN ACCORDANCE NFA *13. 4 ALL DESIGN AND INSTALLATION SHALL BE IN ACCORDANCE WITH NFPA x'13 AND THE CITY OF TUKWiLLA. OCT 16 2006 Tukwila Fire 4fr2q763 WiTH, 7‘,0 IMPORTANT In localities subject to freezing conditions, it la the owner's responsibility to provide heat throughout wet pipe sprinkler systema areas and in enclosures for dry pipe deluge and other types of valves f1r controlling water supplies to sprinkler systems. This drawing and the information and design application herein contained is the property of TYCO FIRE & SECURITY / SlmplexGrinnell and/or its subsidiaries and is loaned upon express conditions that the same be returned to SimplexGrinnell upon request; all Information herein contained shall be treated as secret, and confidential; no reproduction of this drawing or any part thereof shall be made without written consent of SlmplexGrrnnell. Created by the SimplexGrinnell , "All rights reserved". `Copyright by SlmplexGrinnell 2001 1 CONTRACT RESPONSIBILITIES ITEM SimplexGrinnell/BY OTHERS STREET WATER CONNECTION UNDERGROUND WATER MAINS EXCAVATIONS BY OTHERS BY OTHERS BY OTHERS BACKFILL WIRING BY OTHERS BY OTHERS I 1 Hydrmdb Reference Point PAINTING BY OTHERS Lkis DeNgswtbn A T Main D.Ngnatlan - SYMBOLS Jt- Row Sitt I (FS) 8 Narita Switch Earthquake Bracing -id- Hanger -111— Union Screwed cap e13" t or Phe Below Bottom of Deck —) Grooved Cap — 4 Screwed Plug - 0- Grooved Coupling (OC) Devotion Cheap h Pipe -111-- Flanged ConnectionU (not u Roar) ® %stem Miser t of P. Above Ret. Pkne °k moo 2 3 1 IX Gat. Voles L N.N.S. (GV) SIC} GS&Y Gate Vain (0S&t) -f-4- Butterfly Vohs n Alarm V_ (ALV) .Q." a.atrio Ba water Motor Gong (NMG) -DI wafer Check Valve -IV- Swing Check Valve SFr. DeptConn Stma.rd)(FDc) .4e= Fks DeptConn(Ru h) (FDC) 4 --s -3- -4' Fin D.pt:lkesr.(FDC) Part Indicator Valve (PN) Fire Hydrant (3 way) Thrust Block Key Gate Sectional Valve with Roadway Bmf FTs Hass Assembly Inspectors Test Globe Valve Mae Valve Dry RP, Valve SPRINKLERS MAKE TYPE TYCO SIDEWALL MODEL TY—FRB SIN NPT / K—FACTOR TEMP. FINISH ESCUTCHEON NOTES SYMBOL TY3331 1/2" K=5.6 155 CHROME WRENCH 56-000-6-387 QTY. 4 REM. AREA NAMI/NO. 2 HAZARD CLASSIFICATION HYDRAULIC DESIGN DATA DENSITY GPM/SQ.FT. AREA OF APPUC. HOSE ALLOW. SQ. FT. /HD. J TOTAL SYSTEM REQUIREMENTS GPM PSI AT 3 4 WATER SUPPLY INFORMATION. STATIC PRESSURE I RESIDUAL PRESSURE PSI PSI. WITH GPM FLOWING 5 6 TEST LOCATION: -TOTAL THIS SHEET- 4 BY: 8 9 TEST DATE: 10 ABBREVIATIONS AC - Above Finished Cahg AFF Above Finished Par BC - Below Finished Ce1bg BOB - Bottom of Beam BOD - Bottom of Deck BOJ - Bottom of Joist BOP - Bottom of Pwih HV - Hoes Vohs MC Not In Contract NTS - Not to Sale OBJ - Open Bar Joist S' - Standpipe TOB - Tap of Beam TCP - Tap of Purlh 10S - Tap of Steel LION - Unless Otherwise Noted SYSTEM TYPE ‘tEr ®Daum _❑ DRY ❑ PREACTION _❑ D ORY ❑ CNTY I-lni APPROVALS OUT gl OUT IN SPECIAL REQUIREMENTS( ❑ DOMESTIC PIPE ❑ SCHEDULE 40 ❑ SCHEDULE Bo ❑ GALVANIZED PIPE ❑ GALVANIZED FITTINGS ❑ GALVANIZED MATERIALS ❑ SPECIAL FITTINGS 16038 W VALLEY HWY 06-S-210 REVISIONS - SEE FLAGGED AREA ON PLAN gg IN 0 0 to 000 = r r r- r r COco N Ci Ci =r? 000 �N CVNN s � Gl o� tea.. c‘i as 0 d z FOR INSTALLATION: 0 8 c D W co co J ccFfco ciW J H- a ><= io E F SCALE: AS (VOTED DRAWN BY: MAT 11 -EW G CHECKED BY: L_ ALAN MAHAFRE DATE: 0-06-036 CONTRACT NUMBER: 923013701 SHEET NUMBER: FP -1 ` SHEET 1 OF 1 12 H FE RESTAURANT L 1274 SF RECEPTION LOUNGE Ll 229 OF Without Comments As Noted in Red Per The Attached Letter BUSINESS CENTER Li10 1418 SF AREA OF '!WORK -, LOBBY 100 808 SF These plans have been reviewed by The Tukwila Fire Prevention Bureau coy .:.mfrrrlarrce ✓'kh current City standards. io errors and -..ornlssi0ns-whit i. t t .: = i latf'3r'1ra-0i -adopted...- :andards and (3r ^r 1 r ons.oility for the adequacy of dIr+o. ,vi l ,ieFigner. Additions, ciele'd .•; to 11 drawings after • this date will void ti r quire a resubrnittal ot .,VIS ,L31 .dil r • uo.,.4:gqu,:ni approval. Final acceptance is r1 fz+ < :c and inspection by The Tukwila lFire Pr. ven1r, on Bureau. By: TU ILA FIRE F S 3; - g'(11,di 'NT plea 206-575:107 glv_this Fire regY iy n • � r address for 516- v 1 1 or rest `^lion app' ro FEC MAR KET .M, MI J L Sr" i L"." - UM PIPPIR PO 1(12 F— Ji 1= r L I,8,i FITTER 1 LISTER 1. ALL CEILING HEIGHTS TO BE VERIFIED BY FITTER PRIOR TO CUTTING DROPS 2. ALL HANGERS TO BE TYPED' U.N,O. 3. SPRINKLER HEADS ARE NOT NECESSARILY CENTERED IN THE CEILING TILES. 4, DROPS TO BE PER TYP DROP DETAIL THIS SHEET MARRIOTT SEATAC LOBBY SCALE: 1/8" = 1'_O' DETAINER STRAP NUT - BEAM CLAMP STEEL_._._. STRUCTURE w HANGER D TOP BEAM CLAMP A.T.R. SIZE PER N.F.P.A. RING HANGER OPTIONAL 46'1 FLEX DROP 1 STINt LINE NEW NIPPLE AND ELBOW NEW QUICK RESPONSE RECESSED SPRINKLER TYP.E DROP DETAIL M4'an,Fkn -. to- VICINITY MAP SCALE: NONE SCOPE OF WORK - THIS PROJECT IS A TENANT IMPROVEMENT. FIRE SYSTEMS WEST IS ADDING AND/OR RELOCATING SPRINKLERS TO ACCOMMODATE NEW WALLS AND CEILINGS, CLARIFICATIONS - ALL AREAS PROTECTED BY A WET SYSTEM MUST BE MAINTAINED BY OTHERS AT A MINIMUM 40''F TO PREVENT FREEZING, EXCLUSIONS - ALL PAINTING DESIRED OR REQUIRED, INCLUDING CLEANING OF PIPING, AND PROTECTION OF THE INSTALLED SPRINKLER HEADS FROM PAINT. - PIPE IDENTIFICATION EXCEPT THAT REQUIRED BY CODE, - ALL ELECTRICAL WIRING OF ANY KIND. - CENTRAL STATION MONITORING EQUIPMENT, WIRING AND SERVICES. DESIGN CRITERIA PER NEPA 13(2007) AND CITY OF TUKWILA ALL NEW WORK SHALL BE DONE WITHOUT AFFECTING THE CAPABILITY OF THE EXISTING SYSTEM. LEGEND A. R. i EXISTING SPRINKLER PIPE NEW SPRINKLER PIPE NEW SPRINKLER TO BE ADDED OR RELOCATED EXISTING SPRINKLER AREA OF WORK._ __ L 1 FIRE SPRINKLER BUILDING PERMIT # CONTRACT NAME Marriot Sea -Tac Lobby 16038 West Valley Highway Tukwila, WA 98188 CONTRACT WITH: Cornerstone Construction Services 12901 Pioneer Trail Eden Prairie, MN 55347 PM John Keil Phone: 612-599-4600 Fax: 952-944-0604 -a P 4 U Hc.1._ar'< SUPER SCREW U.1 HANGER LEGEND L L -ROD t �"t A..,. H ER PLATE ,TE I 1 THR05 .:OI'NICREaEINSERT 1 N TOP BEAM CLAMP F HDP' POWDER DRI +EN STUD R WEDGE ANCHOR T TRAPEZE I CEILING FLANGE U H ; SIDE BEAM DiRACKET...yd4P. SIDEWrNO'ER. SHORT CLIP 11" 3/4" 1/2" 111 SPRIN<LER LEGEND SPRINKLER TEE ORIFICE SIZES UPRIGH- PENDENT ,SIZE AND TYPE 7/16" 1/2" SPRAY 17/32" SPRAY 3/3" 7/16" 1/2' SIDEWALL 1/2" DRY TYP tai 1/2" 111 3/4" SPRINKLERS -UP & DN SYM TYPE MFG OPEN'G ..... OPEN'G •�.d..w.. ,� SSP TYCO UP SYM DOWN 1/2" 1" 1/2" V2" 11" j TEMP RATING 111.. es + 1” 1/2" 156 200' 286. SPRINKLER HEADS MODEL ORIFICE THREAD TEMP TY -FRB FINISH CANOPY QTY MK DATE BY 5_6K 112" 155° 1 CHROME CHROME TOTAL 4 APPROVALS REQUIRED: City of Tukwila REVISIONS DISTRIBUTION: City of Tukwlia. OWNER / ARCHITECT OWNER 1 ARCHITECT FIRE SYSTEMS WEST 3 GENERAL NOTES 1. ALL MATERIAL AND EQUIPMv ENT TO BE NEW AND UNDERWRITERS APPROVED, 2, PIPING DIMENSIONS ARE CENTER TO CENTER EXCEPT RISER & DIMENSIONS SHOWN THUSLY (1°-6") WHICH ARE END TO END. 3,EARTHQUAKE BRACING SHALL BE PROVIDED IN ACCORDANCE VVITH NFPA#13, 4, PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH NFPA #13. S,PIPING SHALL BE IN ACCORDANCE WITH NFPA #13. 6. JOINING OF PIPE AND FITTINGS, THREADED AND WELDED SHALL BE IN ACCORDANCE VVITH NFPA #13, 7. OWNER TO PROVIDE ADEQUATE HEAT TO PREVENT WATER IN PIPES FROM FREEZING IN AREAS PROTECTED BY WET PIPE SPRINKLER SYSTEM. 8, STRUCTURAL ADEQUACY OF THE BUILDING TO SUPPORT THE SPRINKLER PIPING 15 THE RESPONSIBILITY OF THE f VVNER OR HIS STRUCTURAL REPRESENTATIVE, DESIGN CRITERIA AND NOTES 1. ALL MAIN AND WELDED BRANCHLINE PIPING TO BE IMPORT SCHEDULE 10 JOINED W/ GROOVED COUPLINGS AND FITTINGS(UNO). 2. ALL THREADED BRANCHLINE PIPING TO BE IMPORT SCHEDULE 40 JOINED W/ IMPORT CAST IRON THREADED FITTINGS. 3. ALL DRY MAIN PIPING TO BE SLOPED AT 1/4" PER 10'-O" AND ALL DRY LINE PIPING TO BE SLOPED AT 1/2" PER 10'-0". 4. ALL GROOVED COUPLINGS TO BE RIGID UNLESS NOTED W/'F" FOR FLEXIBLE. 5. ALL HANGERS AT STEEL BAR JOISTS AND WIDE FLANGE BEAMS TO BE TOP BEAM CLAMP, CEILING FLANGE, OR SAMMY SIDEWINDER (UNO). PAID AUG 27 2012 16038 W VALLEY HWY TUKWQ, FIRE 12-S-195 fire Systems West 206 Frontage Road North, Suite C Pacific, WA. 98047 (253) 833-1248 Fax: (253) 735-01'13 WA CL# FIRESWII 140B1 Q.C.:. FAB BY: Craig 01111er Q.C. INSTALL BY: DESIGNER DATE JOB INCUMBER SHEET Phi Le e4/24/201 2 2-11-10850 1OF1 —67/7a ) 7(7j �D CEILING STROBE TO EXISTING 004 TO EXISTING WALL STROBE 100111 Without Comments As Noted in Red d Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for confarmancr with current City standards. Acceptance is subject to errors and omissions which Flo nt_t,. 6ui:horize violations of adopted standards and ordinance Tire responsibility for the adequacy of design its:.., toia!Iy t,vith the designer. Additions, deietioi iia t;ti' r (: visile:)ris tri rbese drawings after this date will void t'rt _. _ eptan:e and will require a resubmittal of revised di vin!,!F fcg sr)h' <l..ient approval. Final acceptance Is subject to tido test. aricl inspection by Tile Tukwila Fire Prevention Bureau. Date: By: J l l -LhSwe 1.,,c(3,uNt 12,A 54-,14-)o'\5 o ctIl-ele-tce,ov- TUKWILA FIRE DEPARTMENT Please call 206-5754407 and give this Fire Permit No. la -r- --Iql and exact address for shut- down or restoration approval, w14';,\, 4- 4 - 5- TO EXISTING TO EXISTING EX <. R>p',R R EX!` RELOCATE RELDCATE EX R LOCATE CLG. LEGEND ,.I ELEVATION REQUIREMENT ## HDRN/STR❑BE N/A ## = CD ## TBE N/A ## = CD i##Vi HORN/STROBE 80'-96' J� ## = CD AFF ("" Fti STROBE ## = CD 80'-96' AFF P PULL STATI❑N 42'-48' ANNUNCIATOR AFF A 14/2 FPLP B 16/2 FPLP EX EXISTING L❑CATI❑N R RELOCATED 4- 4 - 5- TO EXISTING TO EXISTING EX <. R>p',R R EX!` RELOCATE RELDCATE EX R LOCATE CLG. LOWER LEVEL FIRE ALARM PLAN SCALE: 1/8" = 1'-0" 2' 0 4 8' 16' GENERAL NOTES / SCOPE OF WORK 1. FACTORY RECOMMENDED MINIMUM WIRING SIZES, TYPE AND CONSTRUCTION AS NOTED ON THE DRAWINGS MUST BE STRICTLY FOLLOWED. ANYONE SISHING TO MAKE CHANGES WILL DO SO AT THERE OWN RISK!! 2. THE CIRCUIT ROUTING AND WIRING COUNTS ON THE FLOOR PLAN DRAWINGS ARE SHOWN DIAGRAMMATIC BASED ON CONTINUOUS AND SHORTEST POSSIBLE ROUTING FROM THE CONTROL PANEL AND BETWEEN CONNECTED FIELD DEVICES WITH NO PHYSICAL OBSTRUCTIONS. THE WIRING OR CIRCUIT COUNTS (IF SHOWN) ARE PROVIDED AS A CONVENIENCE ONLY AND AS MEANS TO HASTEN INSTALLATION OR TO DETERMINE WIRING ROUTS. 2. WIRE SHOWN IN THIS DRAWING SET IS PERMITTED IN RACEWAYS LEADING TO FIRE PROTECTION EQUIPMENT. OTHER WIRE SHALL NOT BE PERMITTED. 3. FIRE ALARM SYSTEM INSTALLATION SHALL CONFORM WITH THE LATEST U.L., N.E.C., N.F.P.A., W.A.C., AND OTHER STANDARDS AS APPLICABLE TO THE CITY STANDARDS. 4. WHEN NECESSARY, DUE TO CHANGING DESIGN REQUIREMENTS, FACTORY AVAILABILITY, ETC. FIRE SYSTEMS WEST RESERVES THE RIGHT TO SUBSTITUTE EQUIPMENT HEREIN MENTIONED OR SPECIFIED, WITH EQUIPMENT OF EQUAL OR BETTER QUALITY, FUNCION AND DESIGN. 4. PARALLEL BRANCHING OF WIRE TO ALL NOTIFICATION APPLIANCE CIRCUITS SHALL NOT BE PERMITTED. 5. PARALLEL BRANCHING OF WIRE TO ANALOG INITIATING DEVICE CIRBUITS IS PERMISSIBLE. 6. SMOKE DETECTORS SHALL NOT BE LOCATED WITHIN A 3'0" RADIUS OF SUPPLY -AIR DUCTS. 7. BUILDING HAS AN EXISTING FIRE ALARM SYSTEM. 8. BUILDING IS FULY SPRINKLERED. 9. WE ARE ADDING NOTIFICATION TO TI SPACE ONLY TI SPACE ONLY. KEY PLAN VICINITY MAP 16038 W VALLEY HWY 12-F-181 0_ WA ECL# FIRESWI 055LW WA CL# FIRESWI › - 0 0 W a 0 N 00 0 Co REVISIONS ISSUED_FOR_REVIEW O Z RELOCATED DEVICE COUNT 0 z 0 M N to J 0 1- w Horn/Strobe Pull Station 0 m L_ 0 0 U N N Q� 0 > 00 -I—� 00 Cn � C-) 0o Q r 0CD 0 N 00 0 co AS NOTED 1 E 0 Q� LL 0 W 0 0 Li 0 J 0 LLJ w to --/74�rn 4g.29/ 177,:RD - 7. Lfl7/R/R - ?-1 I -F L 1f\-1€-1 1-I�M(11 n• -1H 1 - - ,.I `SMOKE/HEAT DETECTOR HORN / STROBE MODULE ni, i...... .,i! it • & • J RR .vw oMa - rad SURLY 8 . &WO I•TOM M i" ANNUNCIATOR ,":'o N N PULL STATION (PER ADA)111PERR O N O co (ADA) '. LOWER LEVEL FIRE ALARM PLAN SCALE: 1/8" = 1'-0" 2' 0 4 8' 16' GENERAL NOTES / SCOPE OF WORK 1. FACTORY RECOMMENDED MINIMUM WIRING SIZES, TYPE AND CONSTRUCTION AS NOTED ON THE DRAWINGS MUST BE STRICTLY FOLLOWED. ANYONE SISHING TO MAKE CHANGES WILL DO SO AT THERE OWN RISK!! 2. THE CIRCUIT ROUTING AND WIRING COUNTS ON THE FLOOR PLAN DRAWINGS ARE SHOWN DIAGRAMMATIC BASED ON CONTINUOUS AND SHORTEST POSSIBLE ROUTING FROM THE CONTROL PANEL AND BETWEEN CONNECTED FIELD DEVICES WITH NO PHYSICAL OBSTRUCTIONS. THE WIRING OR CIRCUIT COUNTS (IF SHOWN) ARE PROVIDED AS A CONVENIENCE ONLY AND AS MEANS TO HASTEN INSTALLATION OR TO DETERMINE WIRING ROUTS. 2. WIRE SHOWN IN THIS DRAWING SET IS PERMITTED IN RACEWAYS LEADING TO FIRE PROTECTION EQUIPMENT. OTHER WIRE SHALL NOT BE PERMITTED. 3. FIRE ALARM SYSTEM INSTALLATION SHALL CONFORM WITH THE LATEST U.L., N.E.C., N.F.P.A., W.A.C., AND OTHER STANDARDS AS APPLICABLE TO THE CITY STANDARDS. 4. WHEN NECESSARY, DUE TO CHANGING DESIGN REQUIREMENTS, FACTORY AVAILABILITY, ETC. FIRE SYSTEMS WEST RESERVES THE RIGHT TO SUBSTITUTE EQUIPMENT HEREIN MENTIONED OR SPECIFIED, WITH EQUIPMENT OF EQUAL OR BETTER QUALITY, FUNCION AND DESIGN. 4. PARALLEL BRANCHING OF WIRE TO ALL NOTIFICATION APPLIANCE CIRCUITS SHALL NOT BE PERMITTED. 5. PARALLEL BRANCHING OF WIRE TO ANALOG INITIATING DEVICE CIRBUITS IS PERMISSIBLE. 6. SMOKE DETECTORS SHALL NOT BE LOCATED WITHIN A 3'0" RADIUS OF SUPPLY -AIR DUCTS. 7. BUILDING HAS AN EXISTING FIRE ALARM SYSTEM. 8. BUILDING IS FULY SPRINKLERED. 9. WE ARE ADDING NOTIFICATION TO TI SPACE ONLY TI SPACE ONLY. KEY PLAN VICINITY MAP 16038 W VALLEY HWY 12-F-181 0_ WA ECL# FIRESWI 055LW WA CL# FIRESWI › - 0 0 W a 0 N 00 0 Co REVISIONS ISSUED_FOR_REVIEW O Z RELOCATED DEVICE COUNT 0 z 0 M N to J 0 1- w Horn/Strobe Pull Station 0 m L_ 0 0 U N N Q� 0 > 00 -I—� 00 Cn � C-) 0o Q r 0CD 0 N 00 0 co AS NOTED 1 E 0 Q� LL 0 W 0 0 Li 0 J 0 LLJ w to --/74�rn 4g.29/ 177,:RD - 7. Lfl7/R/R - ?-1 I -F L 1f\-1€-1 1-I�M(11 n• -1H 1 - -