HomeMy WebLinkAboutPP - 6155 SEGALE PARK DR C - CONTINENTAL MILLS - PERMITS AND PLANS6155 SEGALE PARK DR C
ASSOCIATED PERMITS
D19-0261
09-F-124
18-F-049
99-F-276
4 ift-4t
SITE LOCATION
CITY OF TUKWILA
FIRE MARSHAL'S OFFICE
206-575-4407
FIRE PROTECTION SYSTEMS PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
**PLEASE PRINT**
King Co. Assessor's Tax No.: 3523049115
Site Address: 6155 Segale Park Dr C Tukwila, WA 98188 Suite Number: Floor: Main
Tenant Name: Continental Mills New Tenant? ❑ - Yes H- No
Property Owner's Name: Continental MITIS
Mailing Address: PO BOX 88176 Seattle WA 98138
City State Zip
CONTACT PERSON -if there are questions about the submittal.
Name: Manny Ornelas _ Day Telephone: 206-436-5301
Company Name: Washington Alarm
Mailing Address: 2030 Airport Way S
E-mail Address:
permits@washingtonalarm.com
City State Zip
Fax Number: 206-322-7214
Contractor's City of Tukwila Business License number: BUS -0992857
Total number of new/relocated devices or sprinkler heads: 79
Valuation of Project (contractor's bid price): $ 24,000
Scope of Work (please provide detailed information): Multi stage project to relocate rack mounted
Horn/strobes to ceiling due to fork lift damage. Also replacing power supplies for device sync.
PERMIT APPLICATION NOTES
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be
reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules.
Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit
is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or
abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in
writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing
and justifiable cause demonstrated.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE
UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY
FOR THIS PERMIT.
BUILDING OWNER OR A __,� ZE
Signature:
•
3IzI)A1Q
Print Name: Manny Ornelas Day Telephone: 206-436-5301
Plan Permit App.doc
8/22/14 TFD FP Form 8
INSPECTION NUMBER
INSPECTION RECORD
Retain a copy with permit
PERMIT NUMBERS
CITY OF TUKWILA FIRE DEPARTMENT
206-575-4407
Project:
Type of Inspection:
Fire Alarm:
Address: 7'n 55 ,
Suite #: W(55 S4R ��C-
Contact Person:
Ual cal
Pre -Fire:
Permits: A n
Special Instructions:
_
Phone No.:
ZSR
IZ-
16/y
Approved per applicable codes.
nCorrections required prior to approval.
COMMENTS:
-740(.5
Needs Shift Inspection:
Sprinklers:
Fire Alarm:
Hood & Duct:
Monitor:
Pre -Fire:
Permits: A n
Occupancy Type:
i
Inspector,., ��5
Date: /(f7 k ¶
Hrs.:
x"100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. Call to schedule a reinspection.
Billing Address
Attn:
Company Name:
Address:
City:
State:
Zip:
Word/Inspection Record Form.Doc
3/14/14
T.F.D. Form F.P. 113
Configure Circuits
Print Page
/
-swu�pn�e�vume�. . ' , � .
�
��B��y��`
.
Project Name: Continental Mills.
Standby Hours:
24
14 KNlGlIT
Project ID: 15499-1 ` 4 Alarm Mins
5 <
Prepo�dB�MannyOmo�a Derating Factor:
1.2
5495 Power Expander Calculati'. i
Date: 3/5/2�
~ Voltage Drop Waming
' `
VerSion 09
��`
Threshold %•
10
=_=_-
w ^ ^ '-
Pane ID: 5495 5495P�e MaxC��n 3�Amp
r, � . ~ � ' ^ ` ' ` ' ~
L000don1Power Supply 1 ll Volts* 24\��� _ _ __ _ _ - MnxPane Current: (�VAmpm —
Current Draw Wire AWG Ohms Per Length(ft) Actual '���
Nmn%Dmp
C�Circuit o�d-
Standby Alarm & Type 1000 Ft. One -Way Ohms B]L
5495
5495 Pwr Module ‘1
0.075
0205
* 4" m ,' � ^* '' + "` * ;, '
NAC #1
5495 Circuit 1
0.000
0.000
#16 Stranded
4.02
95
0.76
19.73
3.29%
NAC #2
5495Circuit 2
0.000
0.880
#16 Stranded
4:02 ~
190
1.53
- 19.06
6.59%
NAC #3
5495 Circuit 3
0.000
0.880
#16 Stranded
4.02
260
2.09
18.56
9.02%
NAC #4
5495 Circuit 4
0.000
0.880
#16 Stranded
4.02 ''''
280
' 2.25
18.42
9.71%
Aux
5495 Aux Power Out
0.000
0.000
#16 Solid
4.02
0.00
20.40
0.00%
Total Current .ps>
0.075
3.725
Tmo|�|annCunon��(Amps) '
Standby Time In Hours
'. 24 .
0.083
Alarm Time In Minutes /60 (5 Mins)
Total Standbv AH Required
_1.8V0
0.310
Total Alarm AHRequired
TotaI Combined AH Required
,` 2.11 ~
Wire resistances are based upon an ambienttempera ure of 72 degrees F. Because of
the minimal difference between solid and stranded wire no differential was made.
Multiply By The Derating Factor
1.20
Minimum Battery AmpHours Required
� '2.53 �
Configure Circuits
Print Page
/
Circuit Configuration
[Project InromNnon
Project Name: Continental Mills
Prepared By: Manny Ornelas
Project ID: 15499-1
Date: 3/5/2018
Ckt. Number. NAC #1 Panel ID: 5495
Ckt. Name: 5495 Circuit 1 Max Circuit Current: 3 Amps
Qty Device Current Draw Each Current Draw Total
Standby Alarm Standby Alarm
5
System Sensor P2/PC2 Horn/Strobe (75cd)
0.000
0.176
0.000
0.880
Unused
0.000
0.000
0.000
0.000
Unused
0.000
0.000
0.000
0.000
Unused
0.000
-9.000
=--0.000-11
0.000^
0.000
0.000
Totals 0 000 0.880
Ckt. Number: NAC#2 Panel ID: 5495
Ckt. Name: 5495 Circuit 2 Max Circuit Current: 3 Amps
Qty Device Current Draw Each Current Draw Total
Standby Alarm Standby Alarm
5
System Sensor P2/PC2 Horn/Strobe (75cd)
0.000
0.176
0.000 "
0.880
Unused
0.000
0.000
0.000
0.000
Unused
0.000
0.000
0.000
0.000
Unused
0.000
0.000
0.000 '
0.000
0.000
0.000
Totals 0.000 0.880
Ckt. Number: NAC #3 Panel ID: 5495
Ckt. Name: 5495 Circuit 3 Max Circuit Current: 3 Amps
Qty Device Current Draw Each Current Draw Total
Standby Alarm Standby Alarm
5
System Sensor P2/PC2 Horn/Strobe (75cd)
0.000
0.176
0.000
0.880
Unused
0.000
0.000
0.000
0.000
Unused
0.000
0.000
0.000
0.000
Unused
0.000
0.000
0.000'
0.000
0.000
0.000
Totals 0 000 0.880
Ckt. Number: NAC #4 Panel ID: 5495
Ckt. Name: 5495 Circuit 4 ' Max Circuit Current: 3 AmpS
Qty Device Current Draw Each Current Draw Total
Standby Alarm Standby Alarm
5
System Sensor P2/PC2 Horn/Strobe (75cd)
0.000
' 0.176 '
0.000
0.880
Unused
0.000
0.000
0.000
0.000
Unused
0.000
0.000
0 000
0.000
Unused
0.000
0.000 '
0.000
0.000
0.000
0.000
Totals 0.000 0.880
Ckt. Number: Aux Panel ID: 5495
Ckt. Name: 5495 Aux Power Out Max Circuit Current: 3 Amps '
Qty Device Current Draw Each Current Draw Total
. Standby Alam1 Standby Alarm
Unused
0.000
' 0.000 '
0.000
0.000
Unused
' 0.000
0.000
0.000
0.000
Unused
0.000
0.000
0.000
0.000
Unused
0.000
0.000
0.000
0.000
0.000
0.000
Totals 0.000 0.000
Configure Circuits
Print Page
—Global Project Values.
SII,EN"1
Project Name:
Continental Mills Standby Hours: 24 1 <,
TO KNICI IT
Project ID:
15499-1
Alarm Mins: 5 1
` Prepared By
Manny Ornelas
Derating Factor:
1.2
5495 Power Expander Calculations
Date:
3/5/2018
Voltage Drop Waming
Version 02 18.09 Q
Threshold % . 10
Panel ID: 5495 Model: 5495 Power Expander 'Max NAC Current:" 3.0 Amps
Location: [Power Supply 2 I Volts: 24 VDC ..,.. Max,Nanel Current:.6.0 Amps,. —.,„...d.
Current Draw 0 Wire AWG t Ohms Per Length(ft) 4,, Actual ' Volts @ a
Ckt.# Circuit Name'Standby Alarm & Type 1000 Ft. One -Way Ohms EOL °Drop
5495
5495 Pwr Module I 1 .,
0.075
0.205
NAC #1
5495 Circuit 1
0.000
0.880
#16 Stranded
.. 4.02 :
95
.. 0.76 .
19.73,
3.29%
NAC #2
5495 Circuit 2
0.000
0.880
#16 Stranded
4.02
190
1.53
19.06
6.59%
NAC #3
5495 Circuit 3
0.000
0.880
#16 Stranded
4.02 k`
260
' 2.09
18.56
9.02%
NAC #4
5495 Circuit 4
0.000
0.880
#16 Stranded
�� 4.02 ;.,
280
. 2.25
18.42
9.71%
Aux
5495 Aux Power Out
0.000
0.000
#16 Solid
4.02
0.00
20.40
0.00%
Total Standbyturrent (Amps)
0.075
3.725
Total Alarm Current (Amps)
a .. Standby Time In.Hours
;; 24 ..
0.083
Alarm Time In Minutes / 60 (5 Mins)
Total Standby AH Required
1.800
0.310
Total Alarm AH Required
Total Combined AH Required
2.11
Wire resistances are based upon an ambient tempera ure of 72 degrees F. Because of
the minimal difference between solid and stranded wire no differential was made.
Multiply By The Derating Factor
11.20
Minimum Battery AmpHours Required
2.53
Configure Circuits
Print Page
®II :,111
Circuit Configuration
fProject Inforrtwuon
Project Name: Continental Mills
Prepared By: Manny Omelas
Project ID: 15499-1
Date: 3/5/2018
Ckt. Number: NAC #1 Panel ID: 5495
Ckt. Name: 5495 Circuit 1 .. Max Circuit Current: 3 Amps
Qty Device Current Draw Each Current Draw Total
Standby Alarm Standby Alarm
5
System Sensor P2/PC2 Horn/Strobe (75cd)
0.000
0.176 '
0.000
0.880
Unused
0.000
0.000
0.000
0.000
Unused
0.000
, 0.000
0.000
' 0.000,.
Unused
0.000
0,000-
0.000
- 0.000
0.000
0.000
Totals 0.000 0.880
Ckt. Number: NAC #2 ' ' Panel ID: 5495
Ckt. Name: 5495 Circuit 2 Max Circuit Current: 3 Amps
Oty Device "' Current Draw Each Current Draw Total
Standby Alarm Standby Alarm
5
System Sensor P2/PC2 Horn/Strobe (75cd)
0.000
0.176
0.000
0.880
Unused
'0.000
0.000
0.000
' 0.000
Unused
0.000
0.000
0.000
0.000
Unused
0.000
0.000
0.000
, 0.000
0.000
0.000
Totals 0.000 0,880
Ckt. Number: NAC #3 Panel ID: 5495 %.Ckt. Name: 5495 Circuit 3 - Max Circuit Current: 3 Amps
Qty Device Current Draw Each Current Draw Total
Standby . Alarm Standby , Alarm
5
System Sensor P2/PC2 Hom/Strobe (75cd)
0.000
0.178
0.000
0.880
Unused
0.000
0.000
0.000
0.000
Unused
0.000 `
0.000
0.000
'' 0.000
Unused
0.000
0.000
0.000
0.000
0.000
0.000
Totals 0.000 0.880
Ckt. Number: NAC #4 Panel ID: 5495
Ckt. Name: 5495 Circuit 4 Max Circuit Current: 3 Amps
Qty Device Current Draw Each Current Draw Total
Standby Alarm Standby Alarm
5
System Sensor P2/PC2 Hom/Strobe (75cd)
0.000
0.176
0.000
0.880
Unused
0.000
0.000
0.000
0.000
Unused
0.000
0.000
0.000
0.000
Unused
` 0.000 ,
0.000
0.000
0.000
0.000
0.000
Totals 0.000 0.880
Ckt. Number: Aux Panel ID: 5495 , ,
Ckt. Name: 5495 Aux Power Out Max Circuit Current: 3 Amps
Qty Device Current Draw Each Current Draw Total
' Standby Alarm Standby Alarm
Unused
0.000
0.000
0.000
0.000
Unused
0.000
0.000
0.000
0.000
Unused
' 0.000
0.000
0.000
0.000
Unused
0.000
0.000
0.000
0.000
0.000 '
0.000
Totals 0.000 0.000
Configure Circuits
Print Page
`
—Global Project Values:
SILENT
Project Name:IContinental Mills
Standby Hours:
24
14 KNIGHT
Project ID: 15499-1
Alarm Mins:
5
Prepared By:IManny Ornelas
Derating Factor:.
1.2
5495 Power Expander Calculations
Date:
3/5/2018
Voltage Drop Warning
Version 02.18.09
Threshold °I° 10
Panel ID: [5495
Model: 5495 Power Expander Max NAC Current: 3.0 Amps
Location: (Power Supply 3 I Volts: 24VDC ___ _Max Panel Current: 6.0 Amps
,.
Current Draw Wire AWG Ohms Per Length(ft) Actual Volts @ %Dro
Ckt.# Circuit Name Standby Alarm $, & Type G.. 1000 Ft. One -Way Ohms 4 EOL<,< ps
5495
5495 Pwr Module I 1
0.075
0.205
NAC #1
5495 Circuit 1
0.000
0.880
#16 Stranded
' 4.02 •
95
e 0.76
19.73
3.29%
NAC #2
5495 Circuit 2
0.000
0.880
#16 Stranded
4.02
190
1.53
19.06
6.59%
NAC #3
5495 Circuit 3
0.000
0.880
#16 Stranded
" 4.02
260
2.09
18.56
9.02%
NAC #4
5495 Circuit 4
0.000
0.880
#16 Stranded
4.02
280
2.25
18.42
9.71%
Aux
5495 Aux Power Out
0.000
0.000
#16 Solid
4.02
0.00
20.40
0.00%
Total Standby Current (Amps)
0.075
3.725
Total Alarm Current (Amps)
Standby Time In Hours
24
0.083
Alarm Time In Minutes / 60 (5 Mins)
Total Standby AH Required
1.800
0.310
Total Alarm AH Required
Total Combined AH Required
2.11
Wire resistances are based upon an ambient tempera ure of 72 degrees F. Because of
the minimal difference between solid and stranded wire no differential was made.
Multiply By The Derating Factor
1.20•
Minimum Battery AmpHours Required
2.53
Configure Circuits
Print Page
ea
IH
Circuit Configuration
[Project Information
Project Name: Continental Mills
Prepared By: Manny Omelas
Project ID: 15499-1
Date: 3/5/2018
Ckt. Number. NAC #1 Panel ID: 5495
Ckt. Name: 5495 Circuit 1 Max Circuit Current: 3 Amps
Qty Device .. Current Draw Each :Current Draw Total
Standby Alarm Standby Alarm
5
System Sensor P2/PC2 Horn/Strobe (75cd)
0.000
.0.176
0.000
^ 0.880
Unused
0.000
0.000
0.000
0.000
Unused
0.000
' 0.000
' 0.000
0.000
Unused
"9.000 -.
0.000'
'=0.000 "
'"0.000'"'
0.000
'' 0.000
Totals 0.000 0.880
Ckt. Number: NAC#2 Panel ID: 5495
Ckt, Name: 5495 Circuit 2 ... Max Circuit Current: 3 Amps . .,,
Qty Device Current Draw Each Current Draw Total
Standby :Alam Standby r. Alarm
5
System Sensor P2/PC2 Hom/Strobe (75cd)
0.000
0.176
0.000
0.880
Unused
0.000
' 0.000
0.000
'' 0.000
Unused
0.000
0.000
0.000
0.000
Unused
`0.000
''0.000
' 0.000
' 0.000
0.000
0.000
Totals 0.000 0.880
Ckt. Number: NAC #3 Panel ID: 5495 „ .,
Ckt. Name: 5495 Circuit 3 Max Circuit Current: 3 Amps
Qty Device ^� Current Draw Each ,, Current Draw Total
Standby Alarm Standby Alarm
5
System Sensor P2/PC2 Horn/Strobe (75cd)
.- 0,000
' 0.176
i` 0.000
= 0.880
Unused
0.000
0.000
0.000
0.000
Unused
0.000
' 0.000
' 0.000
' 0.000
Unused
0.000
0.000
0.000
0.000
' 0.000
' 0.000
Totals 0.000 0.880
Ckt. Number: NAC #4 ' Panel ID. 5495
Ckt. Name: 5495 Circuit 4 .. .. ... Max Circuit Current: 3 Amps ,.
Qty Device Current Draw Each Current Draw Total
. 4, Standby ' Alarm r Standby k, Alarm
5
System Sensor P2/PC2 Horn/Strobe (75cd)
0.000
0.176
0.000
0.880
Unused
' 0.000
0.000
' 0.000
0.000
Unused
0.000
0.000
0.000
0.000
Unused
' 0.000
0.000
" 0.000
' 0.000
0.000
0.000
Totals 0 000 0.880
Ckt. Number: Aux �, Panel ID: 5495 .,
Ckt. Name: 5495 Aux Power Out Max Circuit Current: 3 Amps
Qty Device Current Draw Each . Current Draw Total
Standby Alarm Standby Alarm
Unused
- 0.000
0.000
' 0.000
0.000
Unused
0.000
0.000
0.000
0.000
Unused
0.000
' 0.000
0.000
0.000
Unused
0.000
0.000
0.000
0.000
0.000.
._ 0.000_
Totals 0.000 0.000
Configure Circuits
Print Page
—Global Project Values.
LENT
Project Name: (Continental Mills I Standby Hours: 24
%SI
/I KNIGHT
Project ID:
15499-1 Alarm Mins:
5
Prepared By:
Manny Ornelas
Derating Factor:
1.2
5495 Power Expander Calculations
Date:
3/5/2018 Voltage Drop Warning
Version 02.18.09
•Threshold % . 10
Panel ID:
5495 Model: 5495 Power Expander Max NAC Current: 3.0 Amps
Location:Power Supply 4 I Volts: 24 VDC ' _ Max Panel Current: 6.0 Amps -
Current Draw Wire AWG Ohms Per Length(ft) Actual Volts @ o
Ckt.# Circuit Name Standby Alarm & Type 1000 Ft. One -Way Ohms EOL 0Drop
5495
5495 Pwr Module
1
0.075
0.205
NAC #1
5495 Circuit 1
0.000
1.760
#16 Stranded
4.02
95
0.76
19.06
6.59%
NAC #2
5495 Circuit 2
0.000
1.232
#16 Stranded
4.02
190
1.53
18.52
9.23%
NAC #3
5495 Circuit 3
0.000
0.880
#16 Stranded
4.02
260
- 2.09
18.56
9.02%
NAC #4
5495 Circuit 4
0.000
0.880
#16 Stranded
4.02
280
2.25
18.42
9.71%
Aux
5495 Aux Power Out
0.000
0.000
#16 Solid
4.02
0.00
20.40
0.00%
Total Standby Current (Amps)
0.075
4.957
Total Alarm Current (Amps)
Standby Time In Hours
24
0.083
Alarm Time In Minutes / 60 (5 Mins)
Total Standby AH Required
1.800
0.413
Total Alarm AH Required
Total Combined AH Required
2.21
Wire resistances are based upon an ambient tempera ure of 72 degrees F. Because of
the minimal difference between solid and stranded wi e no differential was made.
Multiply By The Derating Factor
1.20
Minimum Battery AmpHours Required
2.66
Configure Circuits
Print Page
MI
Circuit Configuration
[Project Information
Project Name: Continental Mills
Prepared By: Manny Omelas
Project ID: 15499-1
Date: 3/5/2018
Ckt. Number: NAC #1 Panel ID: 5495
Ckt. Name: 5495 Circuit 1 Max Circuit Current: 3 Amps
Qty Device Current Draw Each Current Draw Total
Standby Alarm ' Standby Alarm
10
System Sensor P2/PC2 Hom/Strobe (75cd)
0.000
0.176
0.000
1.760
Unused
0.000
0.000
0.000
"0.000+
Unused
0.000
0.000
0.000
0.000
Unused
^.* 0.000°M'
._0.000^
^0.000 +'0.000a
0.000
0.000
0.000
Totals 0.000 1 760
Ckt. Number. NAC #2 r ' Panel ID: 5495
Ckt. Name: 5495 Circuit 2 Max Circuit Current: 3 Amps
Qty Device Current Draw Each ' Current Draw Total
Standby Alarm Standby Alarm
7
System Sensor P2/PC2 Horn/Strobe (75cd)
0.000
0.178
0.000
. 1.232
Unused
0.000
0.000
0.000
0.000
Unused
0.000
0.000
0.000
0.000
Unused
0.000
0.000
0.000
0.000
0.000
0.000
Totals 0.000 1.232
Ckt. Number: NAC #3 Panel ID. 5495
Ckt. Name: 5495 Circuit 3 _ Max Circuit Current:, 3 Amps
Qty Device Current Draw Each Current Draw Total
Standby Alarm Standby Alarm
5
System Sensor P2/PC2 Horn/Strobe (75cd)
0.000
0.178 w
0.000
0.880
Unused
0.000
0.000
0.000
0.000
Unused
:. 0.000
'0.000 HI
0.000
0.000
Unused
0.000
0.000
0.000
0.000
0.000
- 0.000
Totals 0.000 0.880
Ckt. Number: NAC #4 Panel ID: 5495
Ckt. Name: 5495 Circuit 4 ` Max Circuit Current: 3 Amps
Qty Device Current Draw Each Current Draw Total
Standby Alarm Standby Alarm
5
System Sensor P2/PC2 Hom/Strobe (75cd)
0.000
0.176
0.000
0.880
Unused
0.000
0.000
0.000
0.000
Unused
0.000
0.000
0.000
0.000
Unused
0.000
0.000
0.000
0.000
0.000
_.0.000
Totals 0.000 0.880
Ckt. Number. Aux , Panel ID: 5495
Ckt. Name: 5495 Aux Power Out Max Circuit Current: 3 Amps
Qty„Device Current Draw Each Current Draw Total
, ' Standby " Alarm Standby Alarm
Unused
0.000
0,000
0.000
0.000
Unused
0.000
= 0.000
0.000
0.000
Unused
0.000
0.000
0.000
0.000
Unused
0,000
0.000 .
0.000
0.000
_ 0.000
.. 0.000
Totals 0.000 0.000
Configure Circuits
Print Page
— Global Project Values:
44 SILENT
Project Name:
Continental Mills
Standby Hours:1 24
KNICI I"r
Project ID:
15499-1 ., - Alarm Mins:1 5 I
Prepared By:
Manny Ornelas Derating Factor:
1.2
5495 Power Expander Calculations
Date:
3/5/2018 Voltage Drop Waming
Version 02 18.09
Threshold % :
10
Panel ID: 5495 Model: 5495 Power Expander Max NAC Current: 3.0 Amps
Location: 'Power Supply 3 _ ,r1 Volts: 24 VDC Max Panel Current: -6.0 Amps
Current Draw Wire AWG Ohms Per Length(ft) Actual , Volts @
Ckt.# Circuit Name Standby Alarm & Type 1000 Ft. One -Way Ohms EOL �oDrop
5495
5495 Pwr Module I 1 ,
0.075
0.205
NAC #1
5495 Circuit 1
0.000
0.880
#16 Stranded
4.02
95
0.76
19.73
3.29%
NAC #2
5495 Circuit 2
0.000
0.880
#16 Stranded
4.02
190
1.53
19.06
6.59%
NAC #3
5495 Circuit 3
0.000
0.880
#16 Stranded
4.02 °
260
' 2.09
18.56
9.02%
NAC #4
5495 Circuit 4
0.000
0.880
#16 Stranded
.. 4.02
280
2.25
18.42..
9.71%
Aux
5495 Aux Power Out
0.000
0.000
#16 Solid
4.02
0.00
20.40
0.00%
Total Standby Current (Amps)
0.075
3.725
Total Alarm Current (Amps)
Standby Time In Hours
24 .
0.083
Alarm Time In Minutes / 60 (5 Mins) '
Total Standby AH Required
1.800
0.310 ,
Total Alarm AH Required
Total Combined AH Required
2.11
Wire resistances are based upon an ambient tempera ure of 72 degrees F. Because of
the minimal difference between solid and stranded wire no differential was made.
Multiply By The Derating Factor
1.20
Minimum Battery AmpHours Required
2.53
Configure Circuits
Print Page
1
Circuit Configuration
Protect lnrorma0on
Project Name: Continental Mills
Prepared By: Manny Ornelas
Project ID: 15499-1
Date: 3/5/2018
Ckt. Number: NAC #1 Panel ID: 5495 ' ...
Ckt. Name: 5495 Circuit 1 Max Circuit Current: 3 Amps
Qty Device Current Draw Each Current Draw Total
Standby Alarm Standby Alarm
5
System Sensor P2/PC2 Horn/Strobe (75cd)
0.000
0.176
« 0.000
0.880
Unused
0.000
0.000
0.000
0.000
Unused
0.000
0.000
0.000
0.000
Unused
0.000
0.000
- 0.000
""0.000
. 0.000
0.000
Totals 0.000 0.880
Ckt. Number. NAC #2 Panel ID: 5495
Ckt. Name: 5495 Circuit 2 ' Max Circuit Current: 3 Amps
Qty Device Current Draw Each Current Draw Total
. Standby Alarm Standby ''Alarm
5
System Sensor P2/PC2 Hom/Strobe (75cd)
0.000
0.176
0.000
0.880
Unused
0.000
0.000
0.000
0.000
Unused
0.000
0.000
0.000
0.000
Unused
0.000
0.000
0.000
' 0.000
0.000
0.000
Totals 0.000 0.880
Ckt. Number: NAC #3 Panel ID: 5495
Ckt. Name: 5495 Circuit 3 Max Circuit Current: 3 Amps
Qty Device Current Draw Each Current Draw Total
Standby Alarm Standby Alarm
5
System Sensor P2/PC2 Horn/Strobe (75cd)
0.000
0.176
0.000
' 0.880
Unused
0.000
0.000
0.000
0.000
Unused
0.000
0.000
0.000
' 0.000
Unused
0.000
0.000
0.000
0.000
0.000
, 0.000
Totals 0.000 0.880
Ckt. Number NAC #4 Panel ID: 5495
Ckt. Name: 5495 Clrcuit 4 Max Circuit Current: 3 Amps
Qty - Device Current Draw Each Current Draw Total
Standby Alarm Standby Alarm
5
System Sensor P2/PC2 Hom/Strobe (75c0)
0.000
0.176
0.000
0.880
Unused
0.000
0.000
0.000
0,000
Unused
0.000
0.000
0.000
0.000
Unused
0.000
0.000.
0.000
0.000
0.000
0.000
Totals 0.000 0.880
Ckt. Number. Aux Panel ID: 5495
Ckt. Name: 5495 Aux Power Out Max Circuit Current: 3 Amps .
Qty Device Current Draw Each Current Draw Total
Standby Alarm Standby Alarm
Unused
0.000
0.000
0.000
0.000
Unused
0.000
0.000
0.000
0.000
Unused
0.000
0.000 '
0.000
0.000
Unused
' 0.000
0.000
0.000
0.000
0.000
0.000
Totals 0.000 0.000
120
-0"
il�
19'-0"
41'-0"
30'-0"
30'-0"
DRIVE UP
RAMP
OFFICE PLAN
UR/RX
(100)°
OPEN
OFFICE
(E)
ROOM
( E )
WAREHOUSE
(E)
OFFICE
(E)
WOMEN
(E)
COMPUTER
(E)
, SHOWER
(E)
OFFICE
(E)
OFFICE
(E)
LUNCH
ROOM
LT
7
CONFERENCE
(E)
vs
(01 5-5- O K 17 r C
ckg i S 2)
\ \-, Dc ST � ►7j— A—A--
12-SM ‘,./A
-
NOTICE
A completed, signed, Tukwila
Fire Department Pre-test
Certificate must be presented
to the Inspector prior to
commencement of Acceptance
Testing of any Fire Alarm
and Detection Systems.
Failure of test will result
in a Re -inspection Fee and
termination of the testing.
ACCEPTED
Without pt Comments
As Notpd in Red
0 Per The Attached Letter
These plans have been reviewed by The Tukwila Fire
Prevention Bureau for conformance with current City
s . rkdards. Acceptance is subject to errors and
o fissions which co not authorize violations of adopted
s andards and ordinances. The res rs :? ity +u: :'�
adequacy of design rests totVly with the des;oner.
A} ditions, deletions or revisions to these draw rq-s after
his date will void this acceptance and will require a
r•submittal of revised drawings for subsequent approval.
nal acceptance is subject to Feld test and Inspection by
e Tukwila Fire Prevention Bureau.
By: ,,, .�1 r
te: �-(�-o�►
1Yil W1LA FtitE i3EPl1RIAJii11
Please call: 575.4407
end give this Job
No.O���-I�-`S
3 i exact address for shut•
i,wn or restoration approval
O
r
AUG 1
247
north
1
4.1115
ACCEPTED
Without Comments
As Noted in Rea
0 Per The Attached Letter
These plans have been reviewed by The Tukwila Fire
Prevention Bureau for conformance with current City
standards. Acceptance is subject to errors and
omissions which do not authorize violations of adopted
standards and ordinances. The responsibil ty for the
adequacy of design rests totally with the designer.
Additions, deletions or revisions to these drawings after
this date will void this acceptance and will require a
resubmittal of revised drawings for subsequent approval.
Final acceptance is subject to field test and inspection by
The Tukwila Fire Pi:•event on Bureau.
Date: 3.-t 1"/3 By;
For phase, 3 3,,661:4-44 i, pro irk co , i'e-f-+
�i4 �1 �a ►'SSS s �, o�A„ti.5g ! ► d e v; cess sea, C,'
GhA totida.ia ret-1-7-uJS.
TUKWI A FIRE DEPARTMENT
:--cat c ll 20 6-575 D7 and
a6�:.t �. i
givQ FIR"! c Perrli No.
f
= . shut-
-
t -
OTICE
complPteci, signed, Tukwila
Fre ' a -Tr n _ 1ce- �St
Ce `Ices:._-
=
Find _ --
irt a ,
telminzCufl of the Lest_ J
E
T1
LX IT
F XIT
P E
stoZ7-
E
r,LEI
E
E
x
ilk
1
E
STA[
f/ 1
E
E
E
�7 E
iso P
E
E
STAGFA
STAGE
E
E
E E FPS=E
E E
FACP EPS FPS4FPSb
E
E
h
'H
E
E
E
E
E lE
E (_
11�)
it
n
ate;
z�F
E�
iH
E
ti
.1E
E
1i
E
E
EvE
\iE
1›:1r
E
E
E
r
E
Th
E E
�f_P
FIRE ALARM SYN
NOTE: ALL SYMBOLS MAY NOT BE USED
30 L LEGEND
ON THIS PROJECT
_ Y M`OL
,n SCR P €'r_ON
Mc U !'`"
_ i=
F ALARM CON^O PAN-
E [ .1[^
�
± nAr.jf
i t._
Y
FIRE ALARM POWER SUPPLY
EiSTI G
FF`F
.r^
E
MANUAL PULL STATION
LitS..:T rNG -
.),--:--
II H)ir
' r Ar - , 4^i"•F
CEtI !a-" MOUNT
Lr`L+ANG <4 OUN HORN I .. 1-_ —
EXISTING
EXIT NG
{ F
� HOR'l ,` ,,,,_,u0,_ [
EX;S i ING -
rLRRREVATlLd
EiJ! .,. TION
< =I
SPEAKER .r.n - mak:
E ]( ,} _Y,
'rt.xlhrvL t. .! —� CA'tULL4 —
f-
Y1r:1FCI AR
i
i=EN A'.. MOAN:
2_ — OE'.1i ADDRESS -
LI iJ v'v t OR nrt
LA., t _
fL—DENOTES^.J�x
WO?
s � M — �GENOiES DETECTOR :;[t ;+;JGL"I
eti
k S t -t N 1 u 1 i v 1 -
SC it --Yl F- u HASE
F
V-
F 1tF
Via- A1H Y ..,
WI
F M _ CM- [_ .NF 1- s! icCR
Ent i-?
ENFI OE rINF ntIAy
i-4716 9 (S'i'r'i =
4 TWP -
Am;
AM 1-- RICAN WIRE Gy l ICII-
r;.-
Mit, .-1 PAIR
tic �.`-'+A rFl•
.t t_.r
r 1- �I
A=n COUNT
CONDUCTOR yA1,YL:� _v� %Uvwt
SSE
..Y
r Y , 43!
-Y. ii
EMS PAR
r-1 r'
_ 4 . r1 I P
HI* +=.4. ._ . I._. .._ ..-..
1k:RL -
1fl
F L
- PI
I`eL.L ;]'Axe IM( TI -I R- t� -
i rY9�I? ,14. I: !il-ir [S
$ CC CABLES (iF Ok.i Eu
�
ONLY I ;ABLE NEE:EDI
-
-
I„a.;
aiyt,
. I I
No I-3 if :AAP -1 !AWE
t: t.:F 14 .;-., ION H: :!?I`+I. �.i?1.-. III
St C:
SII INAti I Y. I INF- CI:tlCUIi
/ FIRE ALARM PLAN
INVSCALA 16.
r't f, t �i A r f �
GENERAL i� 1 I
1_ SCOPE OF "'OP' T(Rt_E� STAGE
PROJECT Ti R�_LOCAT !`%!sTIN i RACK MO1INTEn
HORNS RCL0[_^ ON TOG'ERHE^�n B EM:_ i- P fJ:AC inW R SUPPLIES FORSYNi
_
2_ il-1ESE D rl iYtlivV�
EXACT 111M
`tP ^'t�AA a;c1, AT - REFER 17 T� ' A 'T ^T al;f [j At;rin!��.-• FOR
JIACRAMMA IC. REFER k L I r'C ARCHITECTURAL F TURA DRA(7IiY S
}A[�TArr AT?; ;(.r li rMl [� iAiIT` NEC A,?f_YiA 7i Ai t1T LM Ar.rc-t A rC `�^:`'
�L ( C f !tom -1 IYt •. A - AND ti Ilii f Cr �t ES
Tl t ^ Ar At
H
t fT�}r-}r. [fl; T,Rk IP` ii ['°Fc't..!'�'.`1`r
F Iii
' � r?_irliti�CJ E AL A!ORIT t4.TVtill'-?
! WIRING 4( D. tC Z O THESE NS lr fir" TIC - ACTLIA ,{:IRE 1 TIONS MAX
`t_ fYF EttVi3 i.,1�Ei'1TE%1 v1� it4�--C e i:�'.IV� i� -�1-M'1 r` LOCATIONS
�- FROM Tr_i ^r PLANS.
_ _r••. \r _ _ _ �,rn^ j- AS ACTUAL r' It .x0.:s•c
GtF ROM ESL SPLA !1 4i 4N[ [' S '{ B RE K }
Lt! 1 irl4 I•r�a J+`lt ii}y_`aL i 1�2J. i la. �`v ...i:yiE"4� [ BF t�E��i LKIYt L..r r I���
t� Y F C t h._ U�.1!L I"_ice?
n i� TRL1CTiON L OND i t:- AI OW A. TO M _M+I1 E IRAs t'11 THROUGH AREA
T 'C1 ! 1 "' � R dt• _ ,f --r- -[--I,. T +iP r� A;�
'L:4 -y. .-�,..r 1..JlV J�.i,.siT_1.t� Lor( AND TO tllik�Y-1',{�� = L lL 1'v E.., . y -
CL^ARATIO(,N 4;11A`SS AN FRIE WALLS_ THF USF CIF RACEWAY IS PERMITTED
`S
iy rr''4. Yr rliLr,� t�� y-ttii.! r14it— 'a.a�s_ .iIL l.!�i� .�_ A -'-1ivL;fYA: IS .,xr:.k!tLf AS
- AS NO s a:l=! -r "`I T = - .,! THE SAME
RACEWAY_ k'� t HIGHER Er t CCE S A, r ;. ,F- ACr 'T
L�.i�d'+.� `i �i i iii �� OR E'tlV r't Clt Yl_i! [.-Vi tit �_ � t'.:-1_ IN �: 1xYel_ t.1 -i4 'Y'�t'!4_
5_ FIRE RATINGS S rl I BE MY1:'N C.NED FOR ALL PENETRATIONS THROUGH F1RE-Re?ED
COtNSTRLIC ICN.
6. POWER FOR AIL FIRE ALARM PANELS AND FIRE Ar r - M PJ WE_-SUPPLIES
MUST RF
�P-ROVI,^}_i-; 4B;( tDEFDICAT �R€ BRANCH C 4Ct tT -_ f5'TIO:-"..1 ,C THE E` ANC
i �:li it iLs Lt BY A L'C Lti\Jflt Els AC CIRCUIT_ `JFF. T�k L. i_!Ji-Pt`v Et �i 1t1= s��:"•�i 41�H
CIRCUIT BRF KER SHALL BE
PERMANENTLY IDE NTI FIED THF CO-N TRnr UNIT AND
SHALL HAIR A RED MARKING IN ACCORDANCE WITH NETA 72_
F1�1 F -1"i4Tr._D AND
iPCWER- L ttTrLi CIRCUIT `'tC M
:.rT SEPriR1 �•D
1i5 CABINET. ArI POWER -LIMITED CIRCUIT WIRING MUST REMAIN AT LFAST 0_25" AWAY
FROM.. ANY rYrn4r R-LrV}IED ^tr�-=UIT WIRING_ - ^ l _^M nn rAlf POWER -LIMITED
AND NONPOWER-LIMITED
rt_OEF LtMlED CIRCUIT 'WIRING UST� ENTER AND EXIT
TF:C CABINET
Ti -ROUGH DIFFERENT KNOCK OUTS AND/OR SEPARATE CONDUITS.
WHEN VTI' !ZING CLASS "r" CI^C.r I_..I.TC CEPARATE OUTGOING AND RETURN CONDUCTORS
Cr CLAS "A" CIRCUITS R° A MINIMUM OF in"WHERE RUN VERTICALLY
uRT[CALLY MD 48"
i' -'ERE RUN Irl: IZO;;!T?;`L
I !r 11-,1,1 4"
tit_I NCTt_F
SHIELDED
H:_[r=i�:A --!�—D r4ApL[ TIE SHIELDS
ELv
TS
A r LiA"r
tir-,=.
J11
T €-',.- : 4 t _ AND !► Ui ATF
;
Li -
Aft FIRE AI ARM CABLING sHAL1 RF AC:CEPTABL F TO
At1 i
± 1 sYL
1 €^ rt FOR THE INI E -- r} PURPOSE_
11. SI4OKF 0!E_ FCkORS SHALL
ri COMPLETED.. ttr4
AlAT
r Ar
t Ar'MA
AL14,! Eu+i i
STALLED U tiTII AFTER
" E CO -NC RUCTlON Cl FAN-UP
12_ OCAT t SMOKE DETECTORS AMY,kIM1M nvr THRFF fFEET FROM MECHANICAL
r- FUSE WAr M - OI IA -1 ED SMOk' DET CT�'1R SF.iA1 B LOCATED MINIMUM OF
t. � 1 t.i .,_�1_ �Yr -iY:L'*-s iY. _ter WOKE V_ir�L. Ji'.J �.: IT1LE BF A -�:I4�i I.Y:L rY, OF
n
AND
+ 19"
^ 4!r
+rr zl
6- ?A M -t � t � r .—T[.
uN� a ! O,• ! t 1t i'f�
.`r r 1 ° t , �`
!� FROM - _ `L IY-4•Vt IEE, .. v C UL{LL__rl
r-4 `I ;r - e' i� - ��
y �}r Y — Mint INTM
(�N CEILINGS ANn 1•`,s -T t , r,= (1TT:"lkt` CF yt_ xti i=- G ISS 5
;�i'L; :L'S= ,..,v�1ae'=L1 4_::`t I'tlti..i 4YL)i �iY C t�-J :Y�� vi }".?:_ tiv .:�.Jt�_
1 Z
FEW r4 r: ;- I``y;^f:,A. 7^A. F ts; r -•t r- NOTIFICATION
!AFrzTCIRCUIT
4.• 1 K NI .I?- (' 1� ?� 1 I ( i
E6 JYI � SYNCHRONIZATION �:i t: c_J. I�Kl:vt�Y L:� ^L � YI.�` � i -YJ 41�IL±'k IL1Y :1 •r_lt':i'iL �-Iii Lr till._._
PROVIDE A' L FEC ,FED SYN. -0 Mn [ EIS_ PROVIDE = tLii-SY C Mn vL Lt - E
CI %Nr-- 4 �I Ari -UN .ALL s INc- MnDULES_
Crr
VERIFY ALL
tr .SFI
.ii7E�TA ��� .�L,_
iL•Tf SETTINGS
ETT GS C- NOTIFICATION'
hP
P!
A
WITH F.RE APV CON RYTOR
..r. UPON COMPLETION
F f[R ALARM cYSTEM INSTALLATION.... AND ROG_
RMJIN.
THF : T LL,IYG CONTRACTOR (MALL PuRFvR FINAL TESTING OF THF� ENTIRE SYSTEM
a
PER
�r A '+A r� �: ^t- AND
/�1 '\ ^('c :`,IATr- R PERFORM
�; / A r'A' !?��
PER ALL : ;PPLIC ABLE Ct)DE_S, AND SHA' i CCORDll A F Al44D PERrO \ A r'4- L FIRE
F14 SYSTEM SPE �.T`ON
PROVIDE OFF -S 1TE MONITORING AS REQUIRED BY THE INTERNATIONAL tJA tf
rL!RE CODE
LE -C ION an7 -]�, D :1;E (OCAI At' jR ;f i-iA is{r. !F r}r.(4iSr11�+ 4/ A:
-J LS.r{4.1 'i .lvi f � L1 TI, �J`�.r:'4L r�t!r t.r lit t FA�Olt; t.: t._ll i..iL EL tt�l t_
17. [NSW IG ^�aNTRA1R SHALL, iYS,..xFC_ALL.r LABEL
ALL
__ IV:TI TrG DEVICES AND
NOTIFICATIONAPPLIANCE
,IRCUt T r_ND OF LINE (WHEN WIRING CLASS "B"). THF
SE
LAPELS JH,"A-1!—t Fir_ IN RAF= PRIOR Tnv START—UP AND TESTING_
shop drawings
created by.
5794 W. 4600 So.
Hooper, UT 84315
Office: 801.985.0410
www.unicod.net
PAID
HAR 201Z
TUKWIIJA FIRE
%ys?`
TUKWILA CONTINENTAL MILLS
GALE PK DR.
1.0
TUKWILA, WA
FIRE ALARM PLAN
DRAWN
CWS
UNICAD JOB ij17792
PRtDY B HAWS
..LECKE --
WCET
,ATE 1/10/ 2018
REVISION
0
cr.v E
FA -1
•
. - -
_ 7_
CN1
LL
0
CN
LLJ
LLJ
(f)
LLJ
LLJ
(J)
LLJ
0- Tamperswitch
0 Row switch
Ti Horn strobe
- Manual pull
- TEO Annudator panel
mr) Control panel
Exterior bell
® Smoke detector
X Strobe
Washington Alarm Inc
1253 S Jackson St
Seattle, WA 98144
(206)328-3288
contact: Neal Rider
Qs)
11•11111111111111M1111113.11.11111•0110MOMINIMININE=111•11•11111,
CD
LFjC)
ji (
E ED.'
n
- -
• ;". ./F,„
• /.
D
De a
0
a
LoL c7A1-ECL
0
•••••••••
7
c act_
fr,
0
0
0
a
0
0
\,\
0
0
a
0
EDL
cE.0 L
---
P
0
a
L
•
0
a
0
a
0
0
0
0
0
0
a
0
L
E 0 I--
0
0
1 t'
JL
1
I /
I /
/
__ •
RgLARM-
-
+Mr
REVISIONS:
SEGALE
BUSINESS PARK
TUKWILA, WASHINGTON
(206) 575-2000
1TTLE:
Continental Mills
6155 Segale Park Drive "C"
DESIGNED BY: PROJECT NUMBER:
DRAWN BY:
SN
CHECKED BY:
SCALE:
1/16= r —0"
CADD ALE:
ALARMEAST.dwg
ISSUE DATE:
DATE:
8/13/99
DRAWING NUMBER:
SHEET: 1
- - .
TUKWILA FIRE DEPARTMENT
Please call: 575-4407
and give this job
No.
and exact address for shut,
down or restoration approval.
ACCEPTED
Without Comments
As I\10ted In Red
Per The Attached Letter
se ans have been reviewed by The Tukwila Fire
t- on Bureau foriconformance with current city
standards. Acceptande is subject to errors and
uniisori whklfdo not authorize violations of adopted
standards and ordinances. The responsibility for the
adequacy of design rests totally with the desgner.
Additions, deletions or revisions to these drawings after
this date will void this acceptance and will require a
resubmittal of revised drawings forsubsequent approval.
Final acceptance is Subject to field test and inspection by
The TukwiLa Fire Prevention Bureau.
Date: cAkz:\ By:
5 (0
•
- - - - T - - _ _ 7_ • - - - , -
FLE
-f
- - - - - - - -
_ -
•
5.
- ()es* cif) 0--
CJasi- tM1E WO -0
Noriilp We. 4shys,5_.(G)
Notit, C.J•174Sdle.0--0—
No rill CJ /*SE-. (.3')
r-iilects+ G...)ifSe. (I) 0-0
IfSft I
7.
ierafP C'S) t -AC E ri for
CJ H-sE r
We) o FrxcE
[1)o*. r•.Ea-S+ (A) ftE-CE ffoye r
12.) F
Deiecit) r
E.Iec ic .00 Pi
Ptloo e Fc.i3
I. (S) C.Jt-t. S E_ tJez-ks
Cd) tiS s
NSE_ s
(3) 0•FFXCS
(3)
1
PC.
TELCO
0- Tamper switch
-<>0 Row switch
Ed Horn strobe
Op Manual pull
ItE3 Annuciator pane
rfo Control panel
2 Exterior bell
® Smoke detector
)( Strobe
@) -c7i— ptoiKe r
Washington Alarm Inc
1253 S Jackson St
Seattle, WA 98144
(206)328-3288
contact: Neal Rider
1
fiE3
a
J
a
a
a
a
13
a
D
Drij1,4E.oL,
DS CI ral
L.JEDL—
CN
LL
Li
LLJ
(f)
LLJ
LLJ
Cf)
LLJ
T
1'
•t
•
•
a
t
FIRE ALARM
- _ r
•._- _ _
. - -
- - .
- - _ -E--- • - • _
_ _ - - - - - •_-- - - - _ - • - _ - _ - -
REVISIONS:
M11•11116
SEGALE
BUSINESS PARK
TUKWILA, WASHINGTON
(206) 575-2000
TrTLE:
Continental Milis
6155 Segale Park Drive "C"
DESIGNED BY: PROJECT NUMBER:
DRAWN BY:
SN
CHECKED BY:
CADD FILE:
ALARMEAST2.dwg
ISSUE DATE:
SCALE: DATE:
1/16=1'-0" 8/13/99
DRAWING NUMBER: _
SHEET:
0F:2
•
gr
- - - • - - . - - - , _ - - -
*77
•
- - . • _7-- , Tr_