Loading...
HomeMy WebLinkAboutPP - 6400 SOUTHCENTER BLVD - XEROX CORPORATION - PERMITS AND PLANS6400 SOUTHCENTER BLVD ASSOCIATED PERMITS 12-S-238 13-S-014 92-S-293 92-F-312 93-S-295 99-S-055 99-S-085 99-F-0224 03-S-017 04-F-186 11-F-102 95-F-070 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Xerox (2"d floor) 6400 Southcenter BI Permit No.: 13-S-014 Date: January 22, 2013 Reviewer: Al Metzler Fire Protection Project Coordinator (206) 575-4407 option # 2 (Inspection Requests) (206) 971-8718 (Plan Review Questions) • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ` of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'/z inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • All valves controlling the water supply for automatic sprinkler systems and waterflow switches on all sprinkler systems shall be electrically supervised. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 20 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a Toss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2010 Edition. SITE LOCATION CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East Tukwila, WA 98188 206-575-4407 Date application accepted: FIRE PROTECTION SYSTEMS PERMIT APPLICATION Applications and plans must be complete in order to be accepted for plan review. **PLEASE PRINT** P/ ( King Co. Assessor's Tax No.: MS I 6400 TUKWI LA 0003200003 Site Address: 6400 Southcenter Blvd, Tukwila, WA Suite Number: Floor: 1st Tenant Name: Xerox Property Owner's Name: Xerox Mailing Address: New Tenant? ❑ - Yes ®- No 6400 Southcenter Blvd, Tukwila, WA City State Zip CONTACT PERSON -if there are questions about the submittal. Name: Dave Hova t e r Day Telephone: 425-486-2600 Company Name: Red Hawk Fire & Security Mailing Address: 21312 30th Dr. SE, #103, Bothell, WA 98121 City State Zip E-mail Address: dave . hovat er@redhawkus . com Fax Number: 425-486-2611 Total number of new/relocated devices or sprinkler heads: 1 Valuation of Project (contractor's bid price): $ 1070.00 Scope of Work (please provide detailed information): Install 1 relay module to break power to the door magnet during a fire alarm. PERMIT APPLICATION NOTES Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules. Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILDING OWNER OR AUTHORIZED AGENT: Signature: Dave Hovate3� Print Name: !IDA -- Plan Permit App.doc Date:2-11-13 Day Telephone: 42 5- 4 8 6- 2 6 0 0 1/2/13 TFD FP Form 8 CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East Tukwila, WA 98188 206-575-4407 Date application accepted: FIRE PROTECTION SYSTEMS PERMIT APPLICATION Applications and plans must be complete in order to be accepted for plan review. **PLEASE PRINT** SITE LOCATION Site Address: (91/CO Swthtenkr Alvei King Co. Assessor's Tax No.: Tenant Name: Xe I OX ' Mar -hi? ,(rf7/N7, MG Suite Number: Floor: 7 New Tenant? ❑-Yes ❑-No Property Owner's Name: UUP" 4 -•c -\•P \,a / / 1 anrliE »1J1 ' C, r(7u Mailing Address - City City CONTACT PERSON -if there are questions about the submittal. State Zip Name: j�� • InscmDay Telephone: 17/2.5e1 4/8/.76)66 Company Name: Crown_ re_ ?rotCr+ �.1l 0)1 / l Y1L' Mailing Address: I. (�� u E-mail Address: jes,svicap C_Tow Yl•• (')fl City Fax Number: 4/23---4*. Valuation of Project (contractor's bid price): $ 8, .^ Scope of Work (please provide detailed information): CiACJ 1g a (X.)4 014 heads -inNg. 9e.�c& e. (2 2) hea&s, ‘,),>+ t,1 hods, 1P'101Ci) W j PERMIT APPLICATION NOTES Value of Coustrnction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules. Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in writing, one or more extensions of time,.for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILDING OWNER OR AUTHORIZED AGENT: Signature: / CZ /#'L Date: `•/7 Print Name: CJ/,5J lea flOhJi2�Y7 Day Telephone: 4EZ7 ''// ' 76)4 Plan Permit App.doc 5/14/10 TFD FP Form 8 OFERM CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East Tukwila, WA 98188 206-575-4407 Date application accepted: FIRE PROTECTION SYSTEMS PERMIT APPLICATION Applications and plans must be complete in order to be accepted for plan review. **PLEASE PRINT** SITE LOCATION King C . Assessor's Tax No.: Site Address: (QVA) ce 1=2,1 Suite Number: Floor: Tenant Name: tea \ %Y -V >nel /,)cQX New Tenant? El- Yes ❑ - No Property Owner's Name: Mailing Address: CONTACT PERSON -if there are questions about the submittal. City State Zip Name: QN' ‘st-\-e _ Day Telephone: 1 -12F) -4t 1.7 / wri__Ttce_ ThDier_41or)jn Mailing Address: � L7 J / " U (r4, b()A--- 9s'te2 Fax Number: �,r! ,cif) bl?,c Company Name: E-mail Address: Valuation of Project (contractor's bid price): $ Scope of Work (please provide detailed information): lea PERMIT APPLICATION NOTES Value of Construction - In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules. Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. fad Cz> --c\rP \Y\\€r I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILDING 0 ER OR AUTHO l • GENT: Signature: Alle, �,i/. _ le �_ e i , Print Name: Plan Permit App.doc hlnQ r) 5/14/10 Day Telephone: Date: `1 k.D l 12 42t- L 81.76)1C1 TFD FP Form 8 From:THE SAFETY TEAM INC. 05/13/2011 10:50 #103 P.0021006 THE SAFETY TEAM, INC. ThESAFETY T EAMiNc. 670 South Lucile Street PO Box 81246 Seattle, WA 98108 Phone: (206) 762-1450 Fax: (206) 762-1799 Email: elaine@thesafetyteaminc.com May 13, 2011 City Of Tukwila Fire Department Attn: Al Metzler 444 Andover Park East Tukwila, WA 98188 Phone: (206) 575-4404 Fax: (206) 575-4439 Re: Xerox Building located at 6400 Southcenter Blvd, Tukwila, WA To Whom It May Concern: The above-mentioned building currently is being monitored -via Scan Alert. The existing equipment has been unreliable and has gone down several times. Martin Smith, Inc. (property management) for the Xerox Building has requested that The Safety Team provide and install RF (radio frequency) monitoring today. We will install and program an AES radio frequency monitoring panel (to be located in •. the same location as the existing S.T.U.), set up a new account with Central Station Monitoring, inter -connect to the existing fire alarm panel and central station monitoring and send signals to Central Station and confirm they are received. We will also fax you a copy of all confirmed test signals once the new equipment is on line. Attached is also cut sheets for the AES panel to be installed. If you have any further questions and/or concerns, please feel free to contact me in the office @ (206) 762-1450. Thanks for help on getting this work started and completed. Thank you, /- Efaine Cafxcvag (The Safety Team, Inc. None: (206) 762-14.50 Tax (2061762-1799 SEmail: eAine@thesafetyteaminc.com TUKWILA FIRE DEPARTMENT Please call 206-575-4407 and g1»3 this Fire Permit No. 1/- r -iaa- and exact address for shut- down hutdown or restoration approval. XER SCOPE OF WORK: RELOCATE mama DUCT DETECTORS TO THE RETURN AIR MD PROGRAM TEM AS A SUPERVISORY SIGNAL REPLACE THE EXISTING FACP WTIBANEW ADDRESSABLE FACP. INSTALL (1) PULL STATION AT THE PANEL, (1) SMOKE DETECTOR ABOVE THE FACP AND (1) HORN/STROBE. 120 VAC 20 AMP DEDICATED JOB LOCATION XEROX 6400 SOI THCENTER TUKWILA, WA, 98188 001 1104 1102 1101 STOP €Ivy 1llera 1....) 1..2.31.KS,L..) 1107 1106 1105 P FACP AxiaQ MME TELMAMSUS DAT AV. TUKWILA FIRE DEPARTtvirall. Please call: 575.4407, and give this job No, re eft address for Sdhit• LEGEND CONTROL PANEL ONE-LLNE Tlims'Isms have bee....,,.:,,..,,) L, k Mic SCALE: NCevention Bureau for conformance with current city standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings after this date will void this,acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and Inspection by The Tukwila Fire Prevention Burea V 48k. 4CCEPTED Without Comments ❑ As Noted In Red ❑ Per The Attached Letter ❑ MANUAL PULL STATLoN MONITOR MODULE PDW DUAL MONITOR MODULE PHOTO SMOKE BLVD. Date: vl-ye i By: CONTRACT WITH: MARTIN SMITH INC. 1109 FIRST AVE. 1500 SEATIYE, WL 98101 rIL . 219 FRONTAGE ROAD N SUITE B, PACIFIC, WA 98047 { Phone: (253) 833-1248 Fes (253) 735-0113 DEMON= SUCK PAGED DATE: 9/9/04 le> _A. lc ID) SEP 1 3 2004 2 7 v9 ,his -0' MUM FA40. 1 LIST OF MATERIALS SUPPLIED TO: XEROX CORPORATION 6400 SOUTH CENTER BLVD TUKWILA WA 98188 FOR SPRINKLER MONITORING BY: ADT SECURITY SYSTEMS ACC Without Comments ❑ As Noted In Red �rity Services, The Qf�A aeiol Renton, WA 98055 These plans have been r oarg a ioukwilit Fire Prevention Bureau for confc, mance with current city standards. Acceptance is subject to errors and omissions which do not authorizs vicletns of adopted standards and ordinances. The ro por sibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions in these drawings after this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The TukwilalFire Prevention Bureau. Date: —1( ( 3c\F\ By: M CONTACT: DWAYNE JOHNSON 206-389-8071 STATE REGISTRATION NUMBER: ADTSESI032O5 DATE: 7-12-99 QUANTITY MODEL DESCRIPTION IUKVVILA i IRc vEPARrMENI Please call: 575-4407 and give this job and exact address for shut- down or restoration approval. NOTE: ADT IS MAKING A CONNECTION FROM AN EXISTING FOCUS 45(MONITORING PANEL) TO A NEW SPRINKLER TAMPER SWITCH INSTALLED BY OTHERS. WIRE IS SUPPLIED AND RAN BY OTHERS. ADT IS ONLY SUPPLYING LABOR TO COMPLETE WIRE CONNECTIONS TO EXISTING PANEL. TAMPER IS LOCATED IN PIT. FILE hi JUL 12, 1,99g PciED A two INTERNATIONAL LTD. COMPANY CU FOCUS 45 XEROX CORP. 1 640.8 SOUTHCENTER BLVD. ADT SECURITY SYSTEMS WEST Y A on m V .•. JEFF L. GILL ACCEPTED WITHOUT COMMENTS. ❑ AS NOTED IN RED o PER THE ATTACHED LETTER The drawings affixed hereto have been reviewed and accepted by the City of Tukwila Fire Dept. Additions, deletions or revisions to these drawings after this date will void this acceptance and will require a resubmittal of revised drawings. Final acceptance is subject to field - inspection oy a representative of this dep .r'n-:ent DATE:/ 442 BY: -, s. jCITY OF TUKWILA 575-4407 cc TUKWILA FIRE DEPARTMENT Please call: 575-4407 and give this job No. 92- /'`5/2 - and exact address tor shut- down er restoration ap,00val. n. EL EL • —, EL of EL EL •o EL of of of EL EL /; ;<',, ,". • ,", ,, ;<' EL EL EL oN EL D ! � L — El EL EL EL EL EI_ cL [;] N /; y' \. N `�' `Y/ `441 O8 O ,: ,' ,. .' , 1 .•�,,' y •F: 0 • , . 44010111111111 Itilliiiiiiiiiiiiiiiiii "««�'E HifliHhiii1III o�,1room IVIIIINI INIIIIIIIIMI 11111110 III� I 1 . : ineimoni Liu\ nirmouninummin 1 in mu mon 11111111111101 Milli 11111111111111 IIIIII �I IIi1Ui`o;IIulu,I IL. E rvG �, �I :cE,FPY• i 1111 111111111R11 1111, H ,, II LIR I 1 11111 i 11111 ill 11111111 I i_iiniiCI 1 IV ow il illii •1I1mI 5 N E_"NUL\ 1 II MI 1 I 111111111 !I ION EL II I Pall IIL C 1 ill 1111111 I El tall i ii tom I 1 imil El MI di a i 1 1111 MEM II 1111r d ii i 1 ' i it 1 1 II l' fa I de , , EL III 1111 Mil 1111 I1E01111 IIIEll EIIIIILIE.E‘ . - ,e 1 111111111111i 1111 III Fig 1 III ... .. . 'lltiliiiiiiiimu min nomII 11111111111110 0 1 • • • NS ■ 111111.11:111i IllmlliiIr\ " . . •• • . • • • • • • • • I!IIIII E� s II 1 113111 1111101 1111111 1 EL .1 . ELEL i I Io -1I �I I D I11111EL11111!.II!IFEL EL EL EL F-1 I I 1 I 1 L�J 0 EL r LD 5 Clip Hangers ■ Hanger Rings: UL Listed & FM Approved ■ Hanger Rods / Fasteners: Comply with NFPA 13 O All Thread Rods 0 Machine Thread Rods 1 Finishes: O Standard Components 0 All Galvanized Components 1"= 25.4 mm Components 1. Clip (Ceiling Flange) 2. Hex Nut 3. Wood Screw 4. Hanger Rod 5. Adjustable Hanger Ring Application / Description No. 5 Hangers are designed to support small piping from smooth level wood planking that has a thickness sufficient to receive the required fasteners. The hanger is secured to the planking by means of a clip (ceiling flange or hanger flange) that is provided with a standard thread r the rod and holes for 2 wood screws. To prevent possibl loosening of the rod due to vibration, the hanger is further secured by a hex nut tightened against the clip. There are 6 components in a basic No. 5 Hanger: The clip, 2 wood screws, a hanger rod and locking hex nut, and an adjustable hanger ring. The rod may be either all thread rod (ATR) or machine thread rod (MTR). All thread rod is considered to be standard, however. As a rule, machine thread rod is provided only when it is a specific require- ment of the job specifications. No. 5 Hangers may also be used with other types of construction of adequate strength when provided with suitable fasteners — subject to the approval of the authority having jurisdiction (AHJ). Deviations from standard fas- teners are to be clearly indicated on the plan by detail or in a hanger note (see Hanger Codes / Plan Designations). NFPA Requirements / Limitations NFPA 13 permits the use of 2 screw ceiling flanges only for pipe sizes up to 2" and it calls for the use of screws having dimensions not Tess than those of No. 18 x 1'/2" wood screws. Drive screws and nails are not acceptable fasteners and wood screws are not to be driven. TUKWILA FIRE DEPARTMENT Please call 205-575-2.407 and give ` 1.3 Fre Permit No. I3 -S-01'-) end exact 2d±,2ss for shut cicv n or reLtor ton approval. pi 77.773 P.,FX 4 l -tot t Comments As r,k_ited in Re.d P . !t -_A .,r;.Aieter • rl-iese p!ans have neOewed by The Tu:owi!a Fire wit.. Eur+refit City stz- cia 's. A t je;•ror and ii ii 17..,,,sCns bt ill ,. . _ _ .-.. `-t� %/k-',.:„.,;-;" of adopted s ,. ,z;.c.5 T: f-_=,.' rj: for the adequacy itt n LS'r nor Additions, t�,,ions C';`=3i? (;'ewlnaS after this date Zvi:. > _ _: +.� c 1' "�'- - -.r, will require a resubmiztai of f..; );:egt:ent approval. -Fiinal�a ce�;fif .e sy ct to P 'o test and inspection by. The 1 ukwi a I`ii i •1 ev.:niion Bureau. Design per NFPA 13, Light Hazard, Offices A-1"i All materials to b new, U.L. listed, and F.M. approved Date: / ',I2 / 3 Dy: 1 All fire sprinkler heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart 401 Chrome Style Trim • 146 - Change existing standard response heads to Globe GL5601 Quick Response 155° Pendents 1/2 x 1/2 • 22 - Relocate'Globe GL5601 Quick Response 155° Pendents %2 x 1/2 • 26 - Adjust for new ceiling height Globe GL5601 Quick Response 155° Pendents 1/2 x 1/2 • 1 - Plug existing ` C\ S A -o \ NORTH SECOND FLUOR REFLECTED CEILING DEMO & CONSTRUCTION PLAN vs" CROWN FIRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 (e'l())( e.ot\.k Martin Smith, Inc. 6400 Southcenter Blvd 2nd Floor Tukwila, WA 98188 DATE: 'l 13, 13 DRAWN: r; S SCALE: •I' EL • of EL EL •o EL of of of EL EL EL oN D ! � L — El ELS EL cL 5 Clip Hangers ■ Hanger Rings: UL Listed & FM Approved ■ Hanger Rods / Fasteners: Comply with NFPA 13 O All Thread Rods 0 Machine Thread Rods 1 Finishes: O Standard Components 0 All Galvanized Components 1"= 25.4 mm Components 1. Clip (Ceiling Flange) 2. Hex Nut 3. Wood Screw 4. Hanger Rod 5. Adjustable Hanger Ring Application / Description No. 5 Hangers are designed to support small piping from smooth level wood planking that has a thickness sufficient to receive the required fasteners. The hanger is secured to the planking by means of a clip (ceiling flange or hanger flange) that is provided with a standard thread r the rod and holes for 2 wood screws. To prevent possibl loosening of the rod due to vibration, the hanger is further secured by a hex nut tightened against the clip. There are 6 components in a basic No. 5 Hanger: The clip, 2 wood screws, a hanger rod and locking hex nut, and an adjustable hanger ring. The rod may be either all thread rod (ATR) or machine thread rod (MTR). All thread rod is considered to be standard, however. As a rule, machine thread rod is provided only when it is a specific require- ment of the job specifications. No. 5 Hangers may also be used with other types of construction of adequate strength when provided with suitable fasteners — subject to the approval of the authority having jurisdiction (AHJ). Deviations from standard fas- teners are to be clearly indicated on the plan by detail or in a hanger note (see Hanger Codes / Plan Designations). NFPA Requirements / Limitations NFPA 13 permits the use of 2 screw ceiling flanges only for pipe sizes up to 2" and it calls for the use of screws having dimensions not Tess than those of No. 18 x 1'/2" wood screws. Drive screws and nails are not acceptable fasteners and wood screws are not to be driven. TUKWILA FIRE DEPARTMENT Please call 205-575-2.407 and give ` 1.3 Fre Permit No. I3 -S-01'-) end exact 2d±,2ss for shut cicv n or reLtor ton approval. pi 77.773 P.,FX 4 l -tot t Comments As r,k_ited in Re.d P . !t -_A .,r;.Aieter • rl-iese p!ans have neOewed by The Tu:owi!a Fire wit.. Eur+refit City stz- cia 's. A t je;•ror and ii ii 17..,,,sCns bt ill ,. . _ _ .-.. `-t� %/k-',.:„.,;-;" of adopted s ,. ,z;.c.5 T: f-_=,.' rj: for the adequacy itt n LS'r nor Additions, t�,,ions C';`=3i? (;'ewlnaS after this date Zvi:. > _ _: +.� c 1' "�'- - -.r, will require a resubmiztai of f..; );:egt:ent approval. -Fiinal�a ce�;fif .e sy ct to P 'o test and inspection by. The 1 ukwi a I`ii i •1 ev.:niion Bureau. Design per NFPA 13, Light Hazard, Offices A-1"i All materials to b new, U.L. listed, and F.M. approved Date: / ',I2 / 3 Dy: 1 All fire sprinkler heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart 401 Chrome Style Trim • 146 - Change existing standard response heads to Globe GL5601 Quick Response 155° Pendents 1/2 x 1/2 • 22 - Relocate'Globe GL5601 Quick Response 155° Pendents %2 x 1/2 • 26 - Adjust for new ceiling height Globe GL5601 Quick Response 155° Pendents 1/2 x 1/2 • 1 - Plug existing ` C\ S A -o \ NORTH SECOND FLUOR REFLECTED CEILING DEMO & CONSTRUCTION PLAN vs" CROWN FIRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 (e'l())( e.ot\.k Martin Smith, Inc. 6400 Southcenter Blvd 2nd Floor Tukwila, WA 98188 DATE: 'l 13, 13 DRAWN: r; S SCALE: •I' SVC A -; Vi;4 iL4= Comments iimet ,tom 0 Pe. . ;f C.ec t±C Letter These plans hay.=. _ `•„, _y d Tri Tukwi`a Fre Preve,,n ion purY . , �.z �; t:,t current City standards, Ac; tc errors nd Oflhissio.ns ritA .c;F -- 3 d7pted ry _ _ irlt ':4 e..• `i'. - forthe standards am, -: Sig:..., v,. -a •. _ ,.. -" �`I adequacy i;:e jes! c . Additions, dei2t o;= dr `.I-if,'s after this da .; .viii V` .i _... _ _ti - =v���>r': r-;�:� iii', r "-u]re a . resubmk - -: P r. - _- - - _ l. _ t 3-n oVal FInel acre ,a - The Tuk :: t r Date:/1-7-')-�- Inspection by TUKWILA FIRE DEPARTMENT Please call 206-575-4407 and give this Fire Permit No. /D_ -,S- DZSg and exact address for shut- down or restoration approve • Design per NFPA 13, Ordinary Hazard All materials to be new, U.L. listed, and F.M. approved All fire sprinkler heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart • 1 — Add Reliable Model G Standard Response 165° Pendents '/2 x 1/2 o 1 — Add Reliable Model G Standard Response 165° Upright 1/2 x 1/2 • E — Existing no change Total — 2 . Rce Skoo:‘ r `Piz t" <J. -ft M Clip Hangers ■ Hanger Rings: UL Listed & FM Approved ■ Hanger Rods / Fasteners: Comply with NFPA 13 D All Thread Rods ❑ Machine Thread Rods ▪ Finishes: 0 Standard Components 0 All Galvanized Components 1"=25.4mm Components 1. Clip (Ceiling Flange) 2. Hex Nut 3. Wood Screw 4. Hanger Rod 5. Adjustable Hanger Ring Application / Description No. 5 Hangers are designed to support small piping from smooth level wood planking that has a thickness sufficient to receive the required fasteners. The hanger is secured to the planking by means of a clip (ceiling flange or hanger flange) that is provided with a standard thread r the rod and holes for 2 wood screws. To prevent possibly loosening of the rod due to vibration, the hanger is further secured by a hex nut tightened against the clip. There are 6 components in a basic No. 5 Hanger: The clip, 2 wood screws, a hanger rod and locking hex nut, and an adjustable hanger ring. The rod may be either all thread rod (ATR) or machine thread rod (MTR). All thread rod is considered to be standard, however. As a rule, machine thread rod :s provided only when it is a specific require- ment of the job specifications. No. 5 Hangers may also be' used with other types of construction of adequate strength when provided with suitable fasteners — subject to the approval of the authority having jurisdiction (AHJ). Deviations from standard fas- teners are to be clearly indicated on the plan by detail or in a hanger note (see Hanger Codes / Plan Designations). NFPA Requirements / Limitations NFPA 13 permits the use of 2 screw ceiling flanges only for pipe sizes up to 2" and it calls for the use of screws having dimensions not less than those of No. 18 x 1'/z" wood screws. Drive screws and flails are not acceptable fasteners and wood screws are not to be driven. FILE • CROWN FIRE PROTECTION ,INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 f'\1r1\ SMiSr1n, 6400 Building -Remodel 6400 Southcenter Blvd Tukwila, WA 98188 DATE: 11, (Q , ( 2 DRAWN: SCALE: i I ICI PAID NOV 07 2012 }<M LA FIR -,2/275z3 p C 10 11 12 ;_ _STANDARD HANGERS (Circle hanger(s) to be used/ - . 1w 3C FASTENER U -NOOK \-CEILING PLATE (OPTIONAL! - COACH SCREW ROO ...ME RING \- FASTENER . (PAGER STUO' ;L -R00 COUPLING --ALL THREAD - F100 RIPE RING a.• • 0• O.o • P 4C - 5W 5C 5S 4'•0 !t_ CONCRETE I ANCHOR \\ (ORILLE01 %` ROO COUPLING —ALL THREAD - Roo -- PIPE RING o r- _J FASTENER SIDE BEAM (RACKET iCLIP4 ALL 4HREA0 ROO _ --PIPE RING -- - FASTENER 6W ' � I 8S k•�--• SHORT STRAP SPRING LOADED -TOGGLE `CEILING PLATE ,(OPTIGNALI — ALL -THREAD - RUO --- IPL RIN0 HER NIR - -_�•_� FLAT WASHER . 10S ALL THREAD ROD - -• -+PIPE RING TOP -SEAM C CLAMP -ALL-THREAD - 490 PIPE RING -'To* REAM _ C CLAM? .--Att. _Twit AD - R00 •PIPE MNG - - CEILING FLANGE 1. -FASTENER Alt. THREAD ROO �ryPE Rt4 . 12S 13S FASTENER CAP. OR k_ STOP TRAPEZE BAR-- - - CHANNEL.M►E 0R ANGLE IRON �--� All THREAD" • R00 •--NPf RING TOP BEAM Ct AMP t— THREADED _ UBOLT 14S -' 14W 14C - SB -1 - FASTENER --. BRACE FITTING COMPLETE SWAY MACE PIPE SB -2 11 EYE Roo PIPt RING -BRACE PITTING i ENO WELDED SIDE REAM CLIP FASTENER--. BRACE FITTING COMPLETE NAT BA ACE-• - . !'1.DA- 04.7.R *won - AROWASHERS O Y D 1X; ,- 14,,: L,..0 - -1 ,i `'.. `- ij ! ;tT -It� I4 ,L, 1 \ ; ,• �''`�'.''_, 4') ;,+ ! 4•n i� r• T `� k' -H'• r►,r'ar• ` • ?-Y ^ V {'moi R i—'� —a :�"� _y • �l�f_ 4=-i; -71 ` y7_ ._ 'r. r z.o (' C.S t Fx ^`r`1 A -'1,1.; ,'� w -� 'f _-te.-: - .- -I �7 \7 't_ y z vt; i,� ;-a 1 ►'_ r 34-.7.,,.., :.:',r:. ., a 4 , s V :moi,'. "l9 •• LI Mk ,.�� .,/ 7 .d - `.1 't,XICI rti 11'" V L�1 C ,4j u -7-"':L .•ij"'''_I j-':" 1' IC r i�.P 4" I nt•`_ r_C � r -,1-.1,i -' • r- , =f2 ` 1 ' c:,-1, i-;:---07.) I .v-•--1 "j I- 4.1:'t---- N- f"?‘"- T.4 ----("K„,. tM'�kihL: ;,..E. !':I.Tt. 1t i -civ f'.GF.-E- _ 4 I"-..."=aK 1^Ai -tom ",/,41...N...:S '11- I,... �' I aj' L- 2-1 G l`t r, .4 r- j`�j ' I ti"- Y ' 011,:1', :' -+i • r -) .7( Vti OIO .-E'er � .RIE• �, •I � tT la J^6 Li{' _i - 1) ti a rta. i I . ci !4:4''4 F�4 -7-4.. r. T24"4:;1%, • •,= 1 4-4 `r‘1' -11 "1-'� _ ra 4 f ' 1 1-_4 .4. 7' --.I I IN- _. 1 r'\ \` - V a%' .01„f„.;- 4. t I -- 4t. see - .i' 31 to r . F� i - - - f �r a - 'tib., r 4 trr-� ; _' _ i4 -r =`_' \-, --�-•- I r f r, t y `T'•' . .�-"��r, ' �•s 3 � � r{,,-�` • ! I \:'.,-.-.. �� Gs / - r le Twp,'4 & IST -- rt.,'i i* :':. �-tri:=^ .it : 74- - % i -4. _ +E -4 - "'.1- 1_-_;___+1 l'. �-.- - - _ - IU�tl'-,--IML.C•.r.-•'-''CEt•.,t--�.a:+-•.,+.:.ct 1' all- •- \�\1 �+' -ice . - Lt4.,t 3v •c..,--?---..-„-->-ozo - . ' x ?•'s U i+ 0 e - BRACE FITTING \ FEND t -HPE CLAMP \`�1 J • sZi:;moi • '}'- �JJ \~ • ---t` Lv s f•"-17 . 4 I.rf- tea i i c-3 fp- • 4- .- Ne- L _ -'3 ►-mss. 4.$P 11 E 7 6i ti-'iJ 1`F • tf - 3"�� k+1X- 1 )j -_ _ +� 1' t4 • J fi _ r, -77 UKi .c. • • Q it 644 4.13 • r.‘:•4 /"•:111-?..., -C2 sr; " 4-74 • o ai " 11:- #e °I - 4 7-; 4 Li 14E tcl *45 • • 7 TN t 3. 04. 44 • o t. - BEPARTMENT APPROVED BY WASHINGTON SURVEYING & RATING BUREAU sEATTLE. WASH. AUG 3 1979 As meeting requirements of tills ouieau tor classification as sprinklered; however, system changes or additions as recommended on the attached sheet(s) will result in improved rates. Acceptance applies to plans as submitted and for construCtiOn and occupancy shown thereon. Einished installation subject to inspection for final acceptance,. Tin comments. approvals and acceptances relate exclusively to relative effect a; il=rn tire inAtarice rates. They are not to be 8-.1v 4424-y upon the ovstion of whether "due care" has beep exercised witti respect to possiole liability for personal Injury or damage to property. It is recognized that hazards Willa result in loss still exist. • • E The drawings affixed hereto have been reviewed and accepted as meeting or , exceedin3 minimum requirements of thel City of Tukwila fire Dept., Bureau of Tirrei Prevention. Additions cr. revisions to 4h:8Se drawings after this data shall[ribt.lbe construed a being approved orreviewed.. No. DATE BY REVISIONS - SEE FLAGGED AREA ON PLAN • IMPORTANT - In localities subject to freezing conditions, it is the owner's responsi- bility to provide heat throughout wet pipe sprinkler systems areas and in enclosures for dry pipe deluge and other types of valves controlling water supplies to sprinkler systems. _ _ This" drawing and the information. and design apptication herein contained is the property of Grinnell Fire Protection Systems Com- _ pany; inc_-:and/or its subsidiaries and =is loaned upon the express conditions that the same be returned -to GFPS upon request; all information herein contained shall be treated as secret and confidential; no _reproductiOn-_of this drawing or any part thereof shatl be made without the written consent of .G F PS. CONTRACT RESPONSIBILITIES STREET WATER CONNECTION -UNDER-GRO-UND WATER MAINS EXCAVATION BACKFILL WIRING PAINTING OTHERS - COORDINATION RECORD - CONTR. NAME REF_ DWG. REV./DATE NAME TELEPHONE MATERIAL REQUIRED PIPING - INTERIOR DIAMETER FEET PIECES TYPE SPRINKLERS ORIF. , TEMP. FINISH CANOPY SYMB. QTY. UNDERGROUND TOTAL THIS SHEET 440 Line Designation •le 9_ of Pipe Below Bottorn of Deck (12:-.41)q._ of Pipe Above Ref. Plane 44. Earthquake Bracing: 2 & 4 Way Hanger •—• Screwed CaP —I) Grooved CaP —ea Screwed Plug Elevation Change in Pipe • SYMBOLS Flow Switch (FSI CI Monitor Switch Butterfly Valve • Alarm Valve (ALV) Electric Bell Water Motor Gong (WMG1 Wafer Check Valve " -IN- Swing Check Valve - &V.; Fire Dept. Conn. -(Standard) IF= ulig4 Fire Dept_ Conn. (Husk) f.FOCY- 4d` Fire Dept. Conn. (Sidewalk). (FDC) .....t__ Post Indicator Valve (PIV) 124 Fire Hydrant 13 Way) ••••kp Thrust Block .4-- Key Gate Section& Valve with Roadway Box orz2zi Fire Hose Assembly (see notes) Inspectors Test- - Grooved Couptling (GC/ —ifi— Flanged Connection -- - Globe Valve - Angle Valve Dry Pipe Valve _ BOB_ _ Bottom of team BOD_. Bottom of Deck NV-- Hose Valve NIC Not in Conkract " NTS Not to Scale OBS =- Open Bar Joists PRV. _ Pressure Rad, Valve RM Roof Manifold SP - Standpipe TOS __lac of Stec LION_ --- Lktiess Otharwise Noted - SYSTEM TYPE DRY_ PRE ACTION 0 0 PO FM APPROVALS IN GIONEAL FIRE PRUTECTION SYMMS EXECUTIVE OFFICES . PROVIDENCE, R.I. CONTRACT NAME: CONTRACT WITH: SCALE: DRAWN BY: DESCRIPTION: R • CHECKED BY: SYSTEM DESIGN DATA HAZARD CLASSIFICATION - SYSTEM AREA: DENSITY - DESIGN! DATA: AREA OF AFFLICATIoN:,- GPM/SCL FT. HOSE ALLOWANCES: GPM. TOTAL SYSTEM WATER SUPPLY iNFORMATION: STATIC PRESSURE GPM. AT PSi. AT PSt THESE PLANS PREPARED AT: ENGINEER ING DEPARTMENT DRAWING NO. - RESIDUAL PRESSURE PSI. WITH GPM FLOWING TEST - TAKEN AT DATE - CONTRACT NO; 12 AREA 'B' CONSTRUCTION PLAN SCALE: 1/4.. = 1. -0 - FIRE SPRINKLER PLAN SPRINKLER FIRE SPRINKLER PLAN r it SCALE: 1/8" = 1'-0" AREA 'A' CONSTRUCTION PLAN SCALE: 1/4. = GENERAL NOTES 1 SPRINKLER SYSTEM DESIGN PER N.F.P.A. #13 2 ALL MATERIALS SHALL BE NEW AND U.L. LISTED OR F.M. A 3 FIRE SPRINKLER SYSTEM TO BE INSTALLED, BRACED AND T ACCORDANCE WITH N.F.P.A. #13 4 IN LOCALITIES SUBJECT TO FREEZING CONDITIONS IT IS THE RESPONSIBILITY TO PROVIDE HEAT THROUGHOUT THE WET SPRINKLER SYSTEM AREAS AND IN ENCLOSURES FOR DRY AND OTHER TYPES OF VALVES CONTROLLING WATER SUPPL SPRINKLER SYSTEMS 5 FIRE PROTECTION CONTRACTOR SHALL NOT BE RESPONSIBL PROVED STED IN OWNERS IPE IPE, DELUGE S TO FOR THE ABILITY OF THE STRUCTURE TO ADEQUATELY SUPPORT THE FIRE SPRINKLER SYSTEM 6 ALL ELECTRICAL, PAINTING OF PIPE, FURRING, CUTTING OR PATCHING TO BE BY OTHERS 7 SPRINKLER HEADS ARE NOT NECESSARILY LOCATED IN CENTER POINT OR QUARTER POINT OF CEILING TILE 8 EXISTING SPRINKLER SYSTEM HYDRAULICALLY CALCULATED , ND DESIGNED TO PROVIDE .20 PSI / 1500 SQ. FT. 9 RELOCATED HEADS ARE ON 1" SCH.40 ARM OVERS, ADDEC HEADS AND NEW BRANCH LINES ARE TO MATCH EXISTING PIPE SC. 10 AREAS OUTSIDE SCOPE OF WORK NOT SHOWN, AND ARE T REMAIN. 11 SPRINKLER HEADS ADDED AND RELOCATED TO ACCOMMODA TENANT IMPROVEMENTS •r SPRINKLER HEADS SYM KEY PLAN ' NAME METAL TEMP ADDED SPRINKLER HEAD Ct RELOCATED SPRINKLER HEAD • OR 0 EXISTING SPRINKLER HEAD (TO REM/,IN) — — — — EXISTING BRANCHLINE PIPING REC. PEND l NEW BRANCHLINE PIPING 155 5.60 1/2" EXISTING MAIN PIPING GEM F-950 / NEW HANGER LOCATION REC. PEND -X-X X- X- REMOVE EXISTING PIPING 5.60 GENERAL NOTES 1 SPRINKLER SYSTEM DESIGN PER N.F.P.A. #13 2 ALL MATERIALS SHALL BE NEW AND U.L. LISTED OR F.M. A 3 FIRE SPRINKLER SYSTEM TO BE INSTALLED, BRACED AND T ACCORDANCE WITH N.F.P.A. #13 4 IN LOCALITIES SUBJECT TO FREEZING CONDITIONS IT IS THE RESPONSIBILITY TO PROVIDE HEAT THROUGHOUT THE WET SPRINKLER SYSTEM AREAS AND IN ENCLOSURES FOR DRY AND OTHER TYPES OF VALVES CONTROLLING WATER SUPPL SPRINKLER SYSTEMS 5 FIRE PROTECTION CONTRACTOR SHALL NOT BE RESPONSIBL PROVED STED IN OWNERS IPE IPE, DELUGE S TO FOR THE ABILITY OF THE STRUCTURE TO ADEQUATELY SUPPORT THE FIRE SPRINKLER SYSTEM 6 ALL ELECTRICAL, PAINTING OF PIPE, FURRING, CUTTING OR PATCHING TO BE BY OTHERS 7 SPRINKLER HEADS ARE NOT NECESSARILY LOCATED IN CENTER POINT OR QUARTER POINT OF CEILING TILE 8 EXISTING SPRINKLER SYSTEM HYDRAULICALLY CALCULATED , ND DESIGNED TO PROVIDE .20 PSI / 1500 SQ. FT. 9 RELOCATED HEADS ARE ON 1" SCH.40 ARM OVERS, ADDEC HEADS AND NEW BRANCH LINES ARE TO MATCH EXISTING PIPE SC. 10 AREAS OUTSIDE SCOPE OF WORK NOT SHOWN, AND ARE T REMAIN. 11 SPRINKLER HEADS ADDED AND RELOCATED TO ACCOMMODA TENANT IMPROVEMENTS •r SPRINKLER HEADS SYM CNT NAME METAL TEMP K NPT ORIF MFG. MODEL# e 2 REC. PEND CHROME 155 5.60 1/2" 1/2 GEM F-950 e 3 REC. PEND CHROME 155 5.60 1/2" 1/2 GEM F-950 F LE C.- 'r e: "ts [] As; _'s�=.1 i,. Red • Per Th These plans have ;_ =.'t•.:1 f Tr" : Prevention i.vs standards. ffc.-2;:3_ : -.: miesions ^d'',equacy of d�, _;�: -•-_ '" AdniOnS o;'.... 4...._� u ' is date will void c -' resubmittal of'v:, !;; r� Final acceptant o i__ st±:: ' d test ,rv; The Tukwila Fire PRtv-_r! >n Date: l /z/2 '3': TUKWILA FIRE DEPARTLVkI''U Please call: 575-4407 and give this job No.03 —S" 0/7 and exact address for shut. down or restoration approve. FIRST FLOOR KEY PLAN NOT TO SCALE BRANCHLINE KWIK BOLT —\ r—STRUCTURE RING 1" X ARMOVER 111111k(SEE PLAN) " X 1/2" R.C. PENDENT W/ ESCT. SUSPENDED CEILING TYP. RELOCATE ASSEMBLY STRUCTURE 1" X NIPPLE BRANCHLINE 6 V0v 5 C ife Of Your Building SEATTLE: 5005 3RD AVENUE S PO BOX 24567 SEATTLE, WA 98124 1-800-669-6223 PORTLAND: 5400 NE COLUMBIA BLVD PORTLAND, OR 97218 503-331-0234 www.mckinstry.com PROJECT: XEROX TUKWILA CBU c,=sc clic TUKWILA, WA. REGISTRATION: REVISIONS: 1 01/17/03 PERMIT ISSUE NO. DATE DESCRIPTION McKINSTRY DIVISION: FIRE PROTECTION DESIGNED BY: DJ DRAWN BY: • CHECKED BY: Dwayne Johnson RF (206)832-8139 JOB NUMBER: 8111 DATE: 1" X 1/2" R.C. �- PENDANT HEAD SUSPENDED CEILING-' RETURN BEND ASSEMBLY ALE: AS SHOWN FIRE PROTECTION TENANT IMPROVEMENT SHEET NUMBER: FP -1 JAN 1 7 2003 _79 "--7/ AREA 'E' CONSTRUCTION PLAN SCALE: 1". - , I 4. ; AREA 'D' CONSTRUCTION PLAN SCALE: 1/4" 1'-0" 1! x 4 7' • - • CURRENT COVERAGE ACCEpTABL'- ii THIS OFFICE 4RRENT COVER AGE , - IS :ACCEPTABLE THIS OFFICE I II ! 1 CURRENT: COVERAGE IS ACCEPTABLE THIS !OFFICE 1: f a 4. f AREA 'C' CONSTRUCTION PLAN SCALE: 1/e - 1.-0. FIRE SPRINKLER PLAN SCALE: 1/8" = BRANCHLINE KWIK BOLT 0 GENERAL NOTES 1 SPRINKLER SYSTEM DESIGN PER N.F.P.A. #13 2 ALL MATERIALS SHALL BE NEW AND U.L. LISTED OR F.M. APPROVED 3 FIRE SPRINKLER SYSTEM TO BE INSTALLED, BRACED AND TESTED IN ACCORDANCE WITH N.F.P.A. #13 4 IN LOCALITIES SUBJECT TO FREEZING CONDITIONS IT IS THE OWNERS RESPONSIBILITY TO PROVIDE HEAT THROUGHOUT THE WET PIPE SPRINKLER SYSTEM AREAS AND IN ENCLOSURES FOR DRY PIPE, DELUGE AND OTHER TYPES OF VALVES CONTROLLING WATER SUPPLIES TO SPRINKLER SYSTEMS 5 FIR PROTECTION CONTRACTOR SHALL NOT BE RESPONSIBLE FOR THE ABILITY OF THE STRUCTURE TO ADEQUATELY SUPPORT THE FIRE SPRINKLER SYSTEM 6 ALL, ELECTRICAL, PAINTING OF PIPE, FURRING, CUTTING OR PATCHING TO BE BY OTHERS 7 SPRINKLER HEADS ARE NOT NECESSARILY LOCATED IN CENTER POINT OR QUARTER POINT OF CEILING TILE 8 EXISTING SPRINKLER SYSTEM HYDRAULICALLY CALCULATED AND DESIGNED TO PROVIDE .20 PSI / 1500 SQ. FT. 9 RELOCATED HEADS ARE ON 1" SCH.40 ARM OVERS, ADDED HEADS AND NEW BRANCH LINES ARE TO MATCH EXISTING PIPE SCH. 10 AREAS OUTSIDE SCOPE OF WORK NOT SHOWN, AND ARE TO REMAIN. 11 SPRINKLER HEADS ADDED AND RELOCATED TO ACCOMMODATE TENANT IMPROVEMENTS SPRINKLER HEADS SYM KEY PLAN NAME c* ADDED SPRINKLER HEAD e RELOCATED SPRINKLER HEAD • OR 0 ) EXISTING SPRINKLER HEAD (TO REMAIN) _1 — — — EXISTING BRANCHLINE PIPING REC. PEND CHROME NEW BRANCHLINE PIPING 5.60 1/2" 1/2 GEM EXISTING MAIN PIPING eS / NEW HANGER LOCATION —X -X X X - REMOVE EXISTING PIPING GENERAL NOTES 1 SPRINKLER SYSTEM DESIGN PER N.F.P.A. #13 2 ALL MATERIALS SHALL BE NEW AND U.L. LISTED OR F.M. APPROVED 3 FIRE SPRINKLER SYSTEM TO BE INSTALLED, BRACED AND TESTED IN ACCORDANCE WITH N.F.P.A. #13 4 IN LOCALITIES SUBJECT TO FREEZING CONDITIONS IT IS THE OWNERS RESPONSIBILITY TO PROVIDE HEAT THROUGHOUT THE WET PIPE SPRINKLER SYSTEM AREAS AND IN ENCLOSURES FOR DRY PIPE, DELUGE AND OTHER TYPES OF VALVES CONTROLLING WATER SUPPLIES TO SPRINKLER SYSTEMS 5 FIR PROTECTION CONTRACTOR SHALL NOT BE RESPONSIBLE FOR THE ABILITY OF THE STRUCTURE TO ADEQUATELY SUPPORT THE FIRE SPRINKLER SYSTEM 6 ALL, ELECTRICAL, PAINTING OF PIPE, FURRING, CUTTING OR PATCHING TO BE BY OTHERS 7 SPRINKLER HEADS ARE NOT NECESSARILY LOCATED IN CENTER POINT OR QUARTER POINT OF CEILING TILE 8 EXISTING SPRINKLER SYSTEM HYDRAULICALLY CALCULATED AND DESIGNED TO PROVIDE .20 PSI / 1500 SQ. FT. 9 RELOCATED HEADS ARE ON 1" SCH.40 ARM OVERS, ADDED HEADS AND NEW BRANCH LINES ARE TO MATCH EXISTING PIPE SCH. 10 AREAS OUTSIDE SCOPE OF WORK NOT SHOWN, AND ARE TO REMAIN. 11 SPRINKLER HEADS ADDED AND RELOCATED TO ACCOMMODATE TENANT IMPROVEMENTS SPRINKLER HEADS SYM CNT NAME METAL TEMP K NPT ORIF MFG. MODEL# el. 3 REC. PEND CHROME 155 5.60 1/2" 1/2 GEM F-950 eS f REC. PEND CHROME 155 5.60 1/2" 1/2 GEM F-950 FIRST FLOOR KEY PLAN NOT TO SCALE ,e/-- STRUCTURE RING SUSPENDED CEILING 0.9.1 1" X ARMOVER (SEE PLAN) 1" X 1/2" R.C. PENDENT W/ ESCT. TYP. RELOCATE ASSEMBLY STRUCTURE 1" X NIPPLE BRANCHLINE rte„ • 4r • - • -7 •P C_.?"4 741 _1K ,; F:— 0 0 SUSPENDED CEILING—/ ife Of Your Building SEATTLE: 5005 3RD AVENUE S PO BOX 24567 SEATTLE, WA 98124 1-800-669-6223 PORTLAND: 5400 NE COLUMBIA BLVD PORTLAND, OR 97218 503-331-0234 www.mckinstry.com PROJECT: XEROX TUKWILA CBU TUKWILA, WA. REGISTRATION: REVISIONS: 1 01/17/03 PERMIT ISSUE NO. DATE DESCRIPTION 1" X 1/2" R.C. PENDANT HEAD RETURN BEND ASSEMBLY McKINSTRY DIVISION: FIRE PROTECTION DESIGNED BY: DJ DRAWN BY: CHECKED BY: JOB NUMBER: Dwayne Johnson (206)832-8139 RF 8111 ATE: 01-17-03 SCALE: AS SHOWN SHEET TITLE: FIRE PROTECTION TENANT IMPROVEMENT SHEET NUMBER: FP -2 II �_ 1, / = 1 1., , -tOI• —, it 1 > II - �t I I I 'II _` i �I,"—.—moi-�. ; f , r ;,- _ _ I, - fi • "A.� L.L" I II f.24,71 ,. 1 i ti Z�I - C — o▪ f 1 ti l ► • 1 W GAP, [ t f dc Ni. I • - - -- -- 1 - —4— — , \ • I --I 1 I `\ ; , �vN'Gv� aX: V/_>v r) - -1C —I— - H fi\\\IINCI NIU I LE -S- - t%'.)E Cu Fr i Tib JJ OF'— .W i .7 C '1- ( fir `� c� .� i ► ��� ; \'A G <31 eris I— is 1, 11O r.;"1`,.:1-:(--1 XF 1 �/^ 7 . 1- L I.X./ ;aFil: --, - —11.1,1rVt{_d_ •t - •E: to, I' f> 1 Lt- — / / - �2 ,-iov ---`..-,1 t--1(. YAW ?;G,�. � I I +C- i �IGF,J--: Tc 1).0-:',-) - • %ice% \.\ t.�� . — -i— - , ss _.. — — -----:-T — i--- -\--TF------7-----7--t:,--" '71'-i" ',\.,_, / .kt:i • !•:tet.= 1 I �I��1�k!ie! = e Efumusiit- LLS t - �� ■■i■ �_•�� �, 1� �I�liii111�ii1�i :1111111'.,./linumipm urtoailliall 41111111 • �1W ' ■� ��! ���A��„L�u ip, 11 trId:tilifi::ll':'.:;?4$4':L,1:114:llr:llwrt:4[rj:::111!Lmir: 40c11:11:110111:*:?:4.o 1::::;,!:1-7 ::::: 611,111 \11IIIIIW A61111 1111 1111"1111611113111.711611111,41464rtit l1 I IMMInullimime: o EL.1711ii... '-: -4114÷tv-r "144 11111160hf 'psi Ill, 74611 Milt ' ItAlk` . 4** 1511111111 Ralzmiro1 NIMPLL 1..... 3, ,Minn III dill 41 9 -1 Nt -- .&-------mAMP ILI 1111 ik IMPORTANT In localities subject to freezing conditions, it ie -this owner'e responsibfity to provide heat throughout wet pips -sprinkler systems areas and In enclosures for dry pipe deluge and other types of valves controli:ng woter supplies to ear inkier eyat. ms. This drawing and the information and dss1gn oppliccti>on herein contained Is the property of Grinnell Fire Protection systems Company. Inc. and/or tti s.,bsld'or'•es and is loaned uport e,.ptess conditions that the some be returned to GFPS upon request; on Inforrration herein ccntoired shall be treated as_ secret. cnd confidential; no reproduction of this drawing or on,y port thereof shall be mode without written consent of Created by the Grinnell Design Systems . 'Ail rtv---ht-s •resersedr. Copyright by Grinnell Corporation 1990. 11111111111, CONTRACT RESPONSIBILITIES Min. G.F.P. S. OTHERS STREET 11A TER CONNECTION tIt4Y J`1DERGR :.JND WATER i4A''NS SYMBOL ' XCAVATiONS - i BACKFILL 4A1 ' i tt , PAINTING - r . 11 -& i 4 ;., t l . CONTRACT RESPONSIBILITIES ITEM G.F.P. S. OTHERS STREET 11A TER CONNECTION FINISH J`1DERGR :.JND WATER i4A''NS SYMBOL ' XCAVATiONS - i BACKFILL _r_ii +1RING - i tt , PAINTING - 1_ i , TOTAL THIS SHEET - - - - V) L _ I il CONTRACT RESPONSIBILITIES ITEM G.F.P. S. OTHERS STREET 11A TER CONNECTION FINISH J`1DERGR :.JND WATER i4A''NS SYMBOL ' XCAVATiONS - i BACKFILL +1RING - i tt , PAINTING - i = r C; COMt.- ii ' Hydraulic #10 =Line Des 5" -=Con 412" of Pipe £clow Bottom of C-ack _ i2 - of P' -e Alcove Ref. _ - ice; n Demno-tort +-► i - far+sque'+e £ -r_*'rig: 2&4 Wr y - ` _..,1.— Union - 7 Screws -4d Cop- -Grooved op- rooved -Cop —4 _ Strewed Plug Changs gs in Pipe (nit tit f o3* ) Reference Feint - Plane SYMBOLS G -ate Voles — N?S (-ON() Gate V;.*ve (c &Y) S_ Flow Switch (Fs) 8 Monitor Ssi -r1 , r Butterfly Vclve - 0 Alarm, ¥olwe" (AL'). L Electric E3sit - �- Water k! :torr g (W .3) —:a1 Yi- fel Check Voivs -i'V- S+ing Ch r -A - Valve +S System, -P ser - . Fre Cwt-Carrrt.(Storrdarci)(F'C FiFe %i -Conn.( assh) (FDC) Firs Dept.Conn.(Side*olk)(FDC) Post Indicator Valve (PIV) Fire Hydrant (3 lay) Thrust Sock Key Got* Sectional Vo've with Roorfwoy Sox Firs Hose Asaernbiy (see notes) Inspectors Test Grooved Coupi!ng (GC) - Flanged Conrettion Globs Valve Amis Valve - Dry Pips Valve SCALE — -0 0 Iv ACCEPTED Without Comments As Noted In Red Per The Attached Letter Those plans have been reviewed by The Tukwila Fire Frew^tion Bureau for conformance with current city standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions .s these drawings after this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: 11 ��1:'( By: Sc( TUKWILA FIRE DEPARTMEN1. Please call: 575.4407, and give this job No. 99 50'85 and exact address for shut= down or restoration approval. t 1511 503 GRINNELL FIRE" PROTECTION ! SYSTEMS COMPANY co.aRACI NAME XERox 4C0 EL V D ABBREVIATIONS Be gao B3P DO HY N 8c Nl(s NTS oeJ PRY RIA sp TDB _TOP TOS LION - Bottom of 5aarn - Bottom of Delle Sott rn of Pip. - Ditto Host Yo`vs C tPpp{e vtd Cap Not In Controct Not to Soots I nrt ear Joist Pressure Red Vohs - Roof Montfaid - st X,dplp. top of Ee0.m Top of Pips - Top of Steel _- Unless Otherwise Noted WET DRY SYSTEM TYPE ® DELUGE L 0 ❑ PREACTI(jtd 0 APPROVALS= jN ❑ISO OUT ❑IR( - DFM OUT OUT 4N IN i1 N GRINNELL FIRE PROTECTION SYSTEMS i r.ilfiiiptii nk53 s ' ctlY.is Ekarea i for dans'^,c:, i ),13 or ad'Oklarts as rccenvr,c-dei P reties. r coeptar{ce apv;ies to occupancy '{armn viueremn. Plass' ed is _..a . •'����- excAusWy to the rezt.:yo u as d:.:err,'°^cJ r m SCALE: -ROC WILS. WA iala CONTRACT Y{iTft DESCRIPTION: PIPING PLAN DRAWN BY: SYSTEM DESIGN DATA CHECKED BY: SPRINKLERS - KOD EXECUTIVE OFFICES EXETER, N.H. S. FT.JND. ATEA OF APP,_ : 1500 -SQ.-F t =aSE ._LLCnANr-r 100 CPLI DATE: -a THESE PLANS PREP KENT, Nil EN,;.�,EER NG CEP TOTAL SYSTEMA PSI. AT BASE OF RISER WATER SUPPLY INFORMATION - DRAWING NO. FP# !of, STATIC RESYJAL PRESSURE GPA Fie%-kIG TEST TAKEN AT BY CATE CONTRACT N0• 41.1 44 TYPE ORIFICE TE).AP. FINISH CANOPY - - SYMBOL QTY. i i tt , TOTAL THIS SHEET - - - - V) ABBREVIATIONS Be gao B3P DO HY N 8c Nl(s NTS oeJ PRY RIA sp TDB _TOP TOS LION - Bottom of 5aarn - Bottom of Delle Sott rn of Pip. - Ditto Host Yo`vs C tPpp{e vtd Cap Not In Controct Not to Soots I nrt ear Joist Pressure Red Vohs - Roof Montfaid - st X,dplp. top of Ee0.m Top of Pips - Top of Steel _- Unless Otherwise Noted WET DRY SYSTEM TYPE ® DELUGE L 0 ❑ PREACTI(jtd 0 APPROVALS= jN ❑ISO OUT ❑IR( - DFM OUT OUT 4N IN i1 N GRINNELL FIRE PROTECTION SYSTEMS i r.ilfiiiptii nk53 s ' ctlY.is Ekarea i for dans'^,c:, i ),13 or ad'Oklarts as rccenvr,c-dei P reties. r coeptar{ce apv;ies to occupancy '{armn viueremn. Plass' ed is _..a . •'����- excAusWy to the rezt.:yo u as d:.:err,'°^cJ r m SCALE: -ROC WILS. WA iala CONTRACT Y{iTft DESCRIPTION: PIPING PLAN DRAWN BY: SYSTEM DESIGN DATA CHECKED BY: SPRINKLERS - KOD EXECUTIVE OFFICES EXETER, N.H. S. FT.JND. ATEA OF APP,_ : 1500 -SQ.-F t =aSE ._LLCnANr-r 100 CPLI DATE: -a THESE PLANS PREP KENT, Nil EN,;.�,EER NG CEP TOTAL SYSTEMA PSI. AT BASE OF RISER WATER SUPPLY INFORMATION - DRAWING NO. FP# !of, STATIC RESYJAL PRESSURE GPA Fie%-kIG TEST TAKEN AT BY CATE CONTRACT N0• 41.1 44 STANDARD HANGERS (Circle Nangerls) to be used) 1•t 1W r ASTI.E1 j 3C ti t 4C SW SC u 11•271•111 p0.ot11 sru.t 1100 COU•11116 —alt tw.f AO 1100 CO.CRE TE a.Cwoe IC IL110. 1100 COWLI.G eau Tw11EA0 000 ...MP' a,.G O A I r/•511.1• — 10E ■tar 1■.c•1T !CLIP% (ATTI.t■ t 6W I 7W ES T-O•T CT..P S7.,•2 L O.Of O TOCCIF '1/4._CIH.e2 Plc!' , OPT,O..0 ILL 1..111 • C: t P •1 .-.G aye 1 ■f s _ _ . 1.•PI.a.l All T..IAD • 00 11W 11S . Q . Li.mac l_..tTl.f. .LL .-.f Aa .1a it 3 —1 11• •••W1 ..e. 125 1 —BLL T..f.: .Oa W •• Tiro 44—T0•it•.u.r 13S i• ; tiC1 Y SO.. 14S 14W 14C SB -1 _..t,t..• S8-2 ,� Z///// • 1ST. ■l ■ s..a •.TT..0 LCL E T1 sa.• sated wit 11.2 a ata •,•••5R •.0 sISR 4 start .:T.,.d t.. i r'.PI LL i th, A I k 111111111111 ummil CR Opal ZINN 311) <43'_ imummun 11111 NII nIL\ 4011111111 .AA a11111111151 4mis+A 44p 0111111111112111 Ill 41& Ak f 1 `. o o ti � G 01 MIMI mak! • L Emu _ EMI nummunuminninsi-nWrAillaiiisnmuum 1111111111 111 ° isiress1�' D •na. ° 111111111101111•1111 ° I IM °111. 11 EWE= WOMMEMEMINEENNEMEM ESA E NOTE EXISTING- SPRINKLERS TO AUCNODI+TE h'EW MUt.G LAYOUT ANDY/PUS. RELDC.ATIN& Fe, 1-1EADS AND ADDING $ FOS PtZ^.JPER CSD` E ACI -E 0 -WITH A( R1 R LOCATE 0-W1TH A (A) ADD ON - s1 1111111111111111111111111111111111111111111 IMS / iuii i.FIC1111111 : Mr &MON 1116111111111::: i/i I _ I / -II '11 " 1 III II I% ill 11- kilIII F' 11.1../://aP/11.11...11.1111"\,11.11.i; 1111 r i LOWER FLOOR XEROX BUILDING TENANT IMPROVMak\1T EXISTIN 6 SPRINKLER - SCALE 13r- 1-0 r TUKWILA FIRE DEPARTMENT Please call: _ 575.4407 and give this job No. �9— o S -S and exact address for shut- down or restoration approval, r ACCEpT° )[P1 Without Comments - As Noted In Red Per The Attached Lett These plans have been reviewed by 7'' Prevention Bureau for conformancet standards. Acceptance is subject to 1. omissions which do not authorize viol standards and ordinances. The resp: - adequacy of design rests totally with f Additions, deletions or revisions to th( this date will void this acceptance anc resubmittal of revised drawings for sur. Final acceptance is subject to field test The Tukwi : Fire Prevention Burea Date: By. 2 •-: ^%ted 4fter •=° oval. ion by FILE DATE Y REVISIONS — SEE FLAGGED AREA ON PLAN IMPORTANT In localities subject is lreezrrse eondrtevns• it is tNe owner's se.por*i bully to provide heat Throughout wet jot sprrnkler Systems yeas and in enclosures for dry pipe deluge arsd ether types of valves euntreILng water supplies to sprinkler systems. This drawing and the -enformatton and • titsgn eppllcat.on herein contained is the peoperti of Ora -noel Foe Protection Systems Corn pang, Inc- author its su sidtarles and is loaned uucrs the eeptess conditions that the sante be returned to GFPS upon request_ all information hereincvrtained shall b treatel as setter -4=d confidential no reproduct.aw of this tfrawr-eg Cr arty -part t=ie+,f v`tatt be ma-Je without the written cG4.unt..! CF PS CONTRACT RESPONSIBILITIES ITEM GFPS OTHERS STREET WATER CONNECTION UNDE RG ROuNrD WATER MAINS EXCAVATIC"I BACKFILL WIRING PAINTING SPECIAL REQUIREMENTS ❑ 004&51C PPE O 5O£OtlE 40 O SCI-EpULE ED OFM. IATERA_ ❑ GNL4 l• -ZED PIPE ❑ GALI.,QED Fit L O GALLAUI1ED MAI Lf A&. I ❑ x" GV-.. Fit I aa: FOREMAN NOTE ANY DESIGN CHANGES OR ADDITIONAL MATERIAL REQUIRED FOR -THIS PROJECT MUST BE CLEARED AND ORDERED THRU THE ENGINEERING DEPT. CONTACT: PHONE: SPRINKLERS TYPE CRIF TEMP FINISH CANOPY SYMB QTY (i E YY1 12 C- C I-' 0 g;c, THIS SHEET • t0 eta' Cz47 A Hydraulic Reference Pont �TC} Lune Des.gnat.on rt of P.pe Be ow Bolton of Deck Q cL of P.pe Apo..e Ref Pane 0 Ma.n Des.gr+at.ors Earthouake Brac.ng. 2 & 4 Way # Hanger - tin.on - Screv.ed Cap - Grooved Cap Screwed Plug Ele.amon Chanpf in Pape (not ihru floor) SYT.'aOLS Gale Valve -N R S IGVI OSsYGale Va'.eICS&Yl Flo.+S....tch IFS) Mon,tor Sw.ich Butterfly Valre Alarm Valve (ALV) £Iectr.r Bell Water Mtor Gmlg (WMGI Wafer Check Valve Swing Check Va've System R,ser F.re Dept. Conn- (S.de.ea'kl IF DCI Post tnd•cator Valve (Ply) .2" F..e Hydrant (3 way! - Thrust Block - - �... Key Cate Sect.onal Vafre Wath Roadv.ay Boa Fire Hae Ass:mbty (see notes; Insp•clotI Test - - Grooved Covpl.aa (GCI Flanged Connect.on G•obc Valve - Ar•#e Vale, Dry P.pe Vatve Fare Dept. Conn. tStandarc) (FOCI F.re Dept Conn. (Ftushl (FOCI Th ABBREVIATIONS BOB f Botco'n of Bean. BOO ' E.7Tto#T of Deck BOP ' B-tt.r'. of Papa DO = Duo - HV - Hose Va've N 4.0 - N.opte aid Cao NIC ;hot .n Convert NTS - Not to Scale OS! Open Eat joists PRY [ Pressure Fad Varve RPJ' Foot Afan.fold SP Standcpcn TOB p Topof Bean.. TOP _ E Too of P.pe - TOS Too of Steel tdONI r Othe-12.12,2 Noted n— — — -- _ k F SYSTEM TYPE WET 3 DELUGE_O DRY rJ PREACTFON0 3 ISO C 1 R t 0 FM 7s"4I9 APPROVALS OUT Out OUT OUT 1M 'N 1P. 1N GRINNELL FIRE PROTECTION SY r s CONTRACT NAME XER04 64DD SDUT1ACENTEK ISLVD T UIC\NILA WA 95;SE SCALE DRAWN BY: 111•1 Hop:7Es DESCRIPTION CHECKED BY SYSTEM DESIGN DATA - I^tAZA wD CLASSI•.CATION- SYSTEM APEA- DATE riYGRAULtC DENSITY DESIGN CASA GPM.4.•SO. FT. SQ. FT/I-10 AREA OF APPLICATION TOTAL SYSTEM RE OUTPE MENTS -SO-FT. PtOSE ALLOWANCES Cry ENGINEERING DEPARTtiENT THESE PLAN 5 PREPARE) AT 1 ICS 1,I7 F I GPM AT PST AT .NATER SUPPLY INFORMATION STATIC PRESSURE PSI RESIOUALPRESSURE PSI. WITH = GPM TEST TAKEN AT - By DATE -DRAWING ND_ FFL- a 1500 D f�JJ ------ 2" TO UPPER LEVEL } 2 14 -NEW 84:2 CUTIN 1 1 f CENTRAL MOO AF DRY PIPE VALVE 2" OS & Y GATE VALVE W/ TAMPER AIR COMPRESSOR z I I i EXISTING 8" ALARM 'VALVE —1-- ; -- -- 1 &3 I AL_ DRY SYS fE`.1 AIR CAPACITY RISER SECTION 1/4- = t LIT)WH LLVEL 118„ = I' -p„ • t i _t 2 2 2 \It // 12-0 GG 12-0 GG 2 12-0 GG EXISTING SPRINKLERS - TYPICAL r+j • zl .'J :rYEw 2" DRY PIPE VALVE 3I!_ EXISTINC 8- A! ARM VALVE 6- _ 3LAN 2' TO t;PPFR LEVEL t_ ! 2" DRY FROM LOM -IR LEVEL I' HAN ; W/ 2—HOLE CEILING FLG 3: -R LEVEL =LEVEL 118.,_1'�O" LA I t UPRIGHT SrPRINKLER GENERAL LEGEND BOD BOB BOJ .FOS FOW EARTHQUAKE BRACING PIPE HANGER GROOVED CAP RIGID COUPLING ( UNLESS NOTED ) CAP - PLUG - CEN TER1INE HYDRAULIC REFERENCE PUNT CENTERLINE PIPE TO BOTTOM CF DECK CENTERLINE PIPE TO BOTTGM OF BEAM CENTERLINE PIPE TO BOTTOM 0F JOIST FACE OF STUD FACE OF WALL - FOC FACE OF CONCRETE AFF ABOVE FINISHED FLOOR CH CEIUNG HEIGHT R.C. REDUCING COUPLING 6' OUTLET COUPLING WELDED OUTLET S "FIT' FITTING E/C END TO CENTER C/C CENTER TO CENTER C/E CENTER TO ENO GG _ GROOVE/GROOVE TG - THREAD/GROOVE (ALSO "GT-) TGF THREAD/"FIT. (ALSO "Fxr) ATR ALL—THREAD ROD SLOPE UNE FROM 127 TO 147 COLUMN L-1 L—i vrtALri ii -AY SECT t#` SPRINKLERS S"I,4 LTSCRIPTION - - -- - TEMP OTY 1 t I ` RELIABLE moo .G' BRASS LIPRsf;HT 1/21 165' 6 1 <7.. RELIABLE MOD 'G-3' DRY PENDENT - 1/2" - 155' - 4 JOB TOTAL. _- GENERAL NOTES - - E - - - 1 SPRINKLER SYSTEM DESIGN PER N.F_P.A. #13 - 2 ALL MATERIALS SHALL BE NEW AND U.L. LISTED OR F.M. APPROVED - - - - - 3 ARE SPRINKLER SYSTEM TO BE INSTALLED, BRACED AND TESTED IN ACCORDANCE WITH N_F.P.A.- #13 -- 4 k FIR E PROTECTION CONTRACTOR SHALL NOT BE RESPONSIBLE FOR THE ABILITY OF THE STRUCTURE TO ADEOUATELY SUPPORT THE FIRE SPRINKLER SYSTEM. OR ANY APPURTENANCES THEREOF _ 5 -ALL ELECTRICAL, PAINTING OF PIPE, FURRING, CUTTING OR PATCHING TO BE BY OTHERS - F3 PIPE SIZING PERIN.F.P.A. #13 -- ORDINARY HAZARD - - -- - - 7 PIPING 10- BE 'DYNA-THREAD' FOR SCREWED PIPING / 'DYNA-FLOW' FOR GROOVED PIPING - 10 I _- ACCEPTt - fl WITHOUT Cfe►1MEN1 Ef AS NOTED 1. tR :ia - - - 0 PER THE ACTA ; E) The drawings affixed haret-a h ; i en reviewed and accepted by t,t,) Ci;! of_ Tukwila Fire Dept. Additian.3, dot..=i ns or revisions to these dr.:mi 1 ,s aft._: -..is - - date will void this accedt.,,a ;1 c.n. -- 11 - require a resubmittal of reviaeJ I. sings. Final acceptance is subject to fi€l 1- - - inspection by a representative of this = department _ - - - - DATE: //-;v-93 Sl% .- CITY OF TUKWILA -- 575-4407 - - - OCATE U. TUKWILA FIRE DEPARTMENT Please call: 575.4407 and give this job - - - No. 93 -S- a 7-s and exact address for shut• down or restoration approval. 9�pROTECTtO 4 S� - 7TELCO LINE TO MUM. STAT 134 CCM &SDI RISER ROOM TELCO ROOM FLOOR PLAN SCALE' NONE EXISTING FOCUS 45 1 1 ISO vac RISER ACCEPTED ❑ WITHOUT COMMENTS. ❑ AS itikl ED IBJ RED ❑ PER THE ATTACHED LETTER The drawings affixed hereto have been reviewed and accepted by the City of Tukwila Fire Dept. Additions, deletions or revisions to these drawings after this date will void this acceptance and will r::quire a resubmittal of revised drawings. Final acceptance is subject to field - ins lection by a representative of this department DATE: 3//Y/9J_ BY: /4441 J7/ CITY OF TUKWILA 575-4407 LEGEND tai TUKWILA FIRE DEPARTMENT, Please call: 575-440Z and give this job No. /S -F-070 and exact address for shuti i down or restoration approval EXISTING CONTROL UNIT Q WATERFLOW DET. INSTALLED BY OTHERS Q AIR FLOW SWITCH INSTALLED BY OTHERS NOTE' ADT IS MAKING THE CONNECTION BETWEEN THE SWITCHES & THE F45 FOR MONITORING. t;RAM PI D. LEE A� a-> CHEOXD _. PROJECT NAME ZEROX KYISIC S - --— -- _ . , 11 3114 =DI AK. Fx tSIa CRLISON DATE` ' SHEET T I TLE FIRE ALARM MONITORING OSWALT si ma in -MS SCALD NINE j,TY SYSTEX4 IXSCR IPT IQi SHEET ADT -1