FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS
Project Name: Cowlitz Tribal Health
6450 Southcenter BI
Permit No.: 19-S-046
Date: March 12, 2019
Reviewer: Al Metzler
Fire Protection Project Coordinator
(206) 575-4407 option # 2 (Inspection Requests)
(206) 971-8718 (Plan Review Questions)
• Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross
mains, and branch lines 2.5" and larger. Bracing is provided for the last length of
pipe but within 6' of the end of a feed or cross main. Bracing is required unless
all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for
any size pipe, 9.3.5.3.
• Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4
exceptions, 9.3.4.
• Longitudinal sway bracing is a maximum of 80' for mains and cross mains and
within 40 ' of the end of the line, 9.3.5.4.
• Provide lateral and longitudinal bracing for changes in pipe direction per section
9.3.5.11.2 for pipe size 2 1/2 inches and larger.
• Restrain branch lines at the end sprinkler of each line, restrain against vertical
and lateral movement, 9.3.6.3.
• Restraints for branch lines shall be at intervals per table 9.3.6.4 and section
9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6.
• Comply with ASCE 7-02, section 9.6.2.6.2 (e).
• Ceilings used for flex drop attachments shall comply with ASTM C 635 and
ASTM C 636 per section 9.2.1.3.3.2.
• Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a
suspended ceiling, a hanger(s) attached to the structure shall be required to
ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3).
• Flexible sprinkler hose bends shall not exceed the maximum radius permitted by
the listing.
• Provide sprinkler protection beneath all obstructions greater than 4 ft. in width.
• Extend sprinkler protection to all combustible concealed spaces.
• Comply with NFPA 13 obstruction tables.
• All valves controlling the water supply for automatic sprinkler systems and
waterflow switches on all sprinkler systems shall be electrically supervised.
• All interior control valves shall be readily accessible, labeled and located not
more than 6 ft. above the floor.
• Comply with obstructed/non-obstructed construction rules for sprinkler head
placement.
• Sprinkler heads spaced closer than 6 ft. apart must be baffled.
• Modifications involving 20 or more sprinkler heads require hydrostatic test and
system isolation if necessary.
• For dry pipe and double interlock preaction systems in addition to the standard
hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24
hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the
24 hours shall be corrected. These conditions apply to all sprinkler piping
exposed as necessary to accomplish the permitted scope of work.
• These conditions apply to all sprinkler piping exposed as necessary to
accomplish the permitted scope of work.
All code references are NFPA 13, 2016 Edition.
SITE LOCATION
CITY OF TUKWILA
FIRE MARSHAL'S OFFICE
206-575-4407
FIRE PROTECTION SYSTEMS PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
**PLEASE PRINT**
King Co. Assessor's Tax No.: 000320-0011
Site Address: 6450 Southcenter Blvd Tukwila, WA 98188 Suite Number: Floor: 1
Tenant Name: Cowlits Tribal Health
Property Owner's Name: Andover Management Co.
Mailing Address: 900 SW 16th sSt Suite 100 Renton
City
New Tenant? ®- Yes ❑ - No
WA
State Zip
CONTACT PERSON -if there are questions about the submittal.
Name: Vadim Timoshchuk Day Telephone: (253) 840-9900
Company Name: Red Hawk Fire Protection, LLC
Mailing Address: 901 Valley Ave. NW Suite D Puyallup WA 98371
City State Zip
E-mail Address: VadimT@RedHawkFP.com Fax Number:
3322-0107-C Contractor's City of Tukwila BUS -0997549
NICET III number: Business License number:
Total number of new/relocated devices or sprinkler heads: 4
Valuation of Project (contractor's bid price): $ 3,000
Scope of Work (please provide detailed information): RHFP is adding and relocating sprinkler heads
to accommodate new walls and ceilings.
PERMIT APPLICATION NOTES
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be
reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules.
Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit
is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or
abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in
writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing
and justifiable cause demonstrated.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE
UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY
FOR THIS PERMIT. PAID
BUILDING OWNER OR AUTHORIZED AGENT: PA - 1 2019
Signature: TUKWILA 1KWILA FIRE Date:
Print Name: Vadim Timoshchuk y� Day Telephone: (253) 840-9900
Plan Permit App.doc
8/22/14 TFD FP Form 8
Z
INSPECTION NUMBER
INSPECTION RECORD
Retain a copy with permit
t 8 - 03) '
PERMIT NUMBERS
CITY OF TUKWILA FIRE DEPARTMENT
206-575-4407
Project —+2 1
, L
A t‘ixt
Type of Inspection:
,As/ri
Address: 9
Suite #:
��
BUcP
Contact Person:
Special Instructions:
Phone No.:
pproved per applicable codes.
Corrections required prior to approval.
COMMENTS:
Na ine.M..��----
tis f 4-4.) IZ-R-ceAwi"¢.�
-- 5P �
Fit-, At 1 — "A -ss
6-1- 0 6i-64 r d . << 4N t L4MM"---)
Needs Shift Inspection:
Sprinklers:
Fire Alarm:
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
Inspector:
A
_____ ?
61
Date: On 21/9
Hrs.:
t.. C)
$100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. Call to schedule a reinspection.
Billing Address
Attn:
Company Name:
Address:
City:
State:
Zip:
Word/Inspection Record Form.Doc
3/14/14
T.F.D. Form F.P. 113
z
i
INSPECTION NUMBER
INSPECTION RECORD
Retain a copy with permit
PERMIT NUMBERS
CITY OF TUKWILA FIRE DEPARTMENT
206-575-4407
Projeew ( CEZ— 1)^djAit
ffType
of Inspection: a 4%1(/'
Address: /L
Suite #: lP
C ��
Contact Person:
Special Instructions:
,/01;---
Phone No.:
Approved per applicable codes.
Corrections required prior to approval.
COMMENTS:
Qi r
Sp-( ivtlL-e.vs Gte_
Needs Shift Inspection:
Sprinklers: (..(
Fire Alarm:
i
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
Inspector:
��-
Date: 4/4A 9
IHrs.:
(
$100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. Call to schedule a reinspection.
Billing Address
Attn:
Company Name:
Address:
City:
State:
Zip:
Word/Inspection Record Form.Doc
3/14/14
T.F.D. Form F.P. 113
J
FIRE SPRINKLER PLAN
0 2 4 8
16
SCALE 1 /8"=1'-0"
l Without Comments
O As Noted in Red
Per The Attecrle3d getter
t Ese plans have been reviewed t\ Tukwila Fire
..,ention Bureau for co?forrnance current City
rdards. Accent -n e k subject tc. e- ors and
-. sslons which rj.) rii`-1 T 0r ze tfrO'atIni,S =%f adopted
: darns and cr _ -c Thc2 rsborsit,irscy for the
;;luacy of desm-- JeSiver.
itior r diet} :s 'Y,sio ,5 to i"s'', ese Drawings after
` .1.5 data will 1,z3- 6 ... _ : _ o n and ,itl redulre a
Sab tilt? n v/ i''3` f su seduer.t approval.
Final acceQta. �su ;yam: _ field test and inspection by
Tne Tukwila Fire Pi eaert,c ; Bur eau.
Date: 3-/ a -"I q By: s I
��ia� SLA IrIRE 1;/'Er'Ti\ i
Plea:�a.:53i�2C6-575-4407 1r��c.nd
gtve. its Mie Perymit No.
1g .- -O`t(0
and exact address for shut-
down or restoration approv°al.
EXISTING
BRANCH LINE
OR CROSS MAIN;
IGS MECH. TEE
AB2 BRACKET
/ FLEX. DROP
CEILING -1
i-- SPRINKLER HEAD
IGS MECH. TEE TO FLEX.
EXISTING—\
OUTLET
r—M THREADED x IGS
ADAPTER
EXISTING -1
BRANCH LINE
OR CROSS MAIN
AB2 BRACKET
rnrr ,r r—AH2-CC
/ FLEX. DROP
CEILING--'
--SPRINKLER HEAD
IGS MECH. TEE TO FLEX.
PRE -DRILL HOLE --- -
LID WOOD JOIST
3/8" ALL—
THREAD ROD
RING HANGER
SAMMY SCREW
PIPE
(2" MAX.)
HANGER NO. 14W
SAMMY SCREW
Sprinkler Legend
Symbol
0
Manufacturer
Reliable
Type Response
Pendent Standard
SIN
R1015
K -Factor
5.6
Size
Temperature
155°F
Finish ' Escutcheon
Chrome
Quantity
Recessed
4
Total = 4
SCOPE OF WORK
THIS PROJECT IS ATENANT IMPROVEMENT. RED HAWK FIRE PROTECTION IS
ADDING AND RELOCATING SPRINKLER TO ACCOM MODATE NEW WALLS AND
CEILINGS.
EXCLUSIONS
PAINTING OR LABELING OF PIPE AND/OR EQUIPMENT
ELECTRICAL WIRING OF ANY KIND INCLUDING BUT NOT LIMITED TO WATERFLOW
SWITCH, ELECTRIC BELL, AND TAMPER SWITCHES
CENTRAL STATION MONITORING EQUIPMENT, WIRING AND SERVICES
ALL UNDERGROUND WORK INCLUDING BUT NOT LIMITED TO: BACKFILL, SELECT
FILL, BREAKING PATCHING, SAW CUTTING, LAWN REPAIR, LANDSCAPING, TREE
REMOVAL, STERILIZATION, DEVELOPMENT FEES AND CITY CONNECTION.
RELOCATING EXISTING PIPING FOR OTHER TRADES.
GENERAL NOTES
1. SPRINKLER SYSTEM DESIGN PER NFPA#13.
2. ALL MATERIALS SHALL BE NEW AND UL AND/OR FM APPROVED.
3. FIRE SPRINKLER SYSTEM TO BE INSTALLED, BRACED AND TESTED IN
ACCORDANCE WITH NFPA#13.
4. IN LOCALITIES SUBJECT TO FREEZING CONDITIONS IT IS THE OWNERS
RESPONSIBILITY TO PROVIDE HEAT THROUGH OUT THE WET PIPE SPRINKLER
SYSTEM AREAS AND IN ENCLOSURES FOR DRY PIPE, DELUGE AND OTHER TYPES
OF VALVES CONTROLLING WATER SUPPLIES TO SPRINKLER SYSTEMS.
5. FIRE PROTECTION CONTRACTOR SHALL NOT BE RESPONSIBLE FOR THE
ABILITY OF THE STRUCTURE TO ADEQUATELY SUPPORT THE FIRE SPRINKLER
SYSTEM OR ANYAPPURTENANCES THEREOF.
6. ALL ELECTRICAL, PAINTING OF PIPE, FURRING, CUTTING OR PATCHING TO BE
BY OTHERS.
7. 1" PIPING TO BE SCHED 40 WITH THREADED OR INNOVATIVE GROOVE SYSTEM
(IGS) FITTINGS.
8. ALL PENDENT HEADS TO BE LOCATED IN CENTER LINE OF CEILING TILES.
TENANT IMPROVEMENT
THIS PROJECT IS ATENANT IMPROVEMENT. THIS FACILITY HAS ALREADY BEEN
PROTECTED BYA FIRE SPRINKLER SYSTEM. RED HAWK FP IS ADDING AND/OR
RiZOi ATING SPRINKLER -HEADS TOACCOPv1MODA E THE NEW i ENANT JVALL,
CEILING, LIGHTING AND HVAC LAYOUT. ALL WORK WILL BE DONE WITHOUT
AFFECTING THE CAPABILITY OF THE EXISTING SYSTEM.
RED HAWK
FIRE PROTECTION, LLC
801 VALLEY AVE NW, SUITE D
PUYALLUP, WA 98371
PHONE: (253) 840-9900 Fax (800) 591-4382
WA CL# REDHAHF901 QP
N ICET Stamp
WASHINGTON STATE
CERTIFICATE OF COMPETENCY
FIRE PROTECTION SPRINKLER SYSTEMS
Scott Seibert
3322-0107-C Level 3
Red Hawk Fire Protection, LLC
REDHAWHF901 QP
SIgnatura
Approvals Required
CITY OF TUKWILA
OWNER /ARCHITECT
Revisions
Contract With:
SUPERIOR BUILDERS
6313 20TH ST E
FIFE, WA 98424
Contact BRANDON ELMER
Phone: (253) 878-2779
Fax: _
SYMBOL LEGEND
OR
•A
0
MT
- DENOTES A SPRINKLER HEAD TO BE
RELOCATED.
- DENOTES A SPRINKLER HEAD TO BE ADDED.
- DENOTES AN EXISTING PENDENT SPRINKLER OR OUTLET.
- DENOTES AN EXISTING UPRIGHT SPRINKLER OR OUTLET.
- MECHANICAL TEE
- REPRESENTS EXISTING SPRINKLER PIPE.
- REPRESENTS NEW SPRINKLER PIPE.
- NEW WALL.
VICINITY MAP
Macad :m
Wmter G rden
tIT
Fort Ih•nt Park
Start-1re Sports
Watefwo,k
-Gerrie,*
0019 ,
1 rn.r.'r,YRS
ulactu•ers Mineral
Contract Name:
COWLITS TRIBAL
HEALTH
6450 SOUTHCENTER BLVD
TUKWILA, WA 98188
Drawing Title
FIRE SPRINKLER P
AN
Key Plan
AREA OF WORK
(E) SPRINKLER
ROOM
Date:
Job Number:
Designer:
Building Permit:
February 27, 2019
40148
VADIM TIMOSI ICHUK
PAID
Drawing No.
FA?, - 1-2319
TUKWILA FIRE
Frv.v1'->z'_tA
r1
FB 2319
TUKWILA FIRE
Oc4-Bruning 82013 Form 12419
SOUTH CEnITE2 BLVD
ACCEPTED
WITHOUT COMMENTS.
10 AS NOTED IN RED
0 PER THE ATTACHED LETTER
The drawings affixed hereto have been
reviewed and accepted by the City of
Tukwila Fire Dedt. Aiditions, deletions
or revisions to these drawings after this
date will void thi_ , :�;atance and will
require a resubmittal of revised drawings.
Final acceptance is subject to field -
inspection by a representative of this
department
DATE: 57?/9f- BY: S'/1
CITY OF TUKWILA
575-4407
TUKWILA FIRE DEPARTMENT
Please call: 575-4407
and give this job
o.
and exact address for shut.
down or restoration approval.
4
SCOPE OF WORK=
I. RELoGP.TE (i) , 111.5' , 'Z CHZ.. RELESSED
PE,/Oe-,U-r TO A MIN /MUM Co" OFF
WALL .
rgTfigrim
MAY 6 1996
SMITH FIRE SYSTEMS, INC.
4519 South Orchard
Tacoma, Washington 98466
CONTR. REG. NO SMITHFSI360T
Bus: •(206) 473-6967 Fax: (206) 475-1205
PROJECT
AMER' CAM Sp,—ES LEADS
Co 4 50 S O U TN C EN TE IZ _ 81_v D,
To Kt.J ILA
DESIGNER
DATE
SHEET
JOB NO.
D.X. HUGHE`c
5-3-9to
1 OF I
5-17_89
Oce-Bruning 82013 Form 12419
ACCEPTED
c'WITHOUT COMMENTS.
❑ AS NJTED IN Rt=)
❑ PER THE ATTAC ,ED LETTER
The drawings affixed hereto have been
reviewed and accepted by the City of
Tukwila Fire Dept. A.i .iiticns, deL tions
or revisions to the 'r 'wings after this
date will void thi : .A..1nOe and will
require a resubmittal of revised drawings.
Final acceptance is subject to field -
inspection by a representative of this
department
CITY OF TUKWILA
575-4407
REI✓IoVE
TUKWILA FIRE DEPARTMENT
Please call: 575-4407
and give this job /
/�o
No. 96,— "Si' 0
and exact address for shut-
down or restoration approval.
fp -
Ex (STING ARMovER
REPLACE WITH 1(0-(0)
RI I P P L E.
CUT INTO EXISTING
a" RRANCHLINE WITH
2"1( IIS MEd -i. T E E
SPRINKLERS:
ES RELIABLE "G'
R• RELIABLE V
AS RELIABLE"G1
SSP- REC
SSP -REC
SSP- REC
2
BILE
r
I
I
I
I
2
EXTEND EXISTING
ARMOVER, Q Y
AND ICI -O)
SCOPE OF WORK
SMITH FIRE SYSTEMS WILL RELOCATE (2) SPRINKLERS
AND ADD (1) SPRINKLER TO ACCOMMODATE FOR THE
TENANT IMPROVEMENTS.
DESIGN CRITERIA
PER NFPA #13:
OFFICE LIGHT HAZARD
CLARIFICATION
ALL AREAS PROTECTED BY WET PIPE SPRINKLER EQUIPMENT
MUST BE PROTECTED BY OTHERS TO A MINIMUM OF 40° F
EXCLUSIONS
*
PAINTING AND/OR LABELING OF SPRINKLER PIPE AND
ECU(PMENT
ELECTRICAL WIRING OF ANY KIND
STRUCTURAL REVIEW AND ENGINEERING FEES TO
DETERMINE IF THE STRUCTURE IS ADEQUATE TO SUPPORT
THE SPRINKLER SYSTEM
CENTRAL STATION MONITORING EQUIPMENT, SERVICE,
AND WIRING
NOTES
ALL MATERIAL TO BE UL LISTED AND/OR FM APPROVED
ALL HANGERS TO BE IN ACCORDANCE WITH NFPA #13
ALL ARMOVERS IN EXCESS OF 2' - 0" TO BE SUPPORTED
WITH A HANGER
*
*
r-
CHR/c HR
CHR/CHR
CH R/C HR
12"
12"
SPRINKLER PLAN
SCALE: 14"-4,
I6go 3
165° a
1(05°
TQTA L Co
.14t410,
SMITH FIRE SYSTEMS, INC.
1106 54th Ave. E.
Tacoma, WA 98424
CONTR. REG. NO SMITHFS1360T
Ph: (206) 926-1880 Fax: (206) 926-2350
PROJECT
ROYAL COACHMAN
6450 SOUTHCENTER BLVD #102
TUKWILA, WAHINGTON
DESIGNER
DATE
SHEET
JOB NO.
M. BRANDEWIE
I - - I OF
5- 1117