PP - 12200 EAST MARGINAL WAY SOUTH - KING COUNTY METRO - PERMITS AND PLANS
12200 EAST MARGINAL WAY SOUTH ASSOCIATED PERMITS 16-F-123 16-F-124 16-F-125 12-F-142 98-F-075 669-10 04-S-093 03-S-181 M18-0024 M16-0199 46itt"44 SITE LOCATION CITY OF TUKWILA FIRE MARSHAL'S OFFICE 206-575-4407 FIRE PROTECTION SYSTEMS PERMIT APPLICATION Applications and plans must be complete in order to be accepted for plan review. **PLEASE PRINT** King Co. Assessor's Tax No.: Site Address: 12200 East Marginal Way S. Suite Number: Floor: Tenant Name: Component Supply Center Lube Room New Tenant? ❑ - Yes xQ - No Property Owner's Name: King County Metro Mailing Address: 2255 4th Ave. S. Seattle WA 98134 City State Zip CONTACT PERSON -if there are questions about the submittal. Name: Carissa Thomson Day Telephone: 425-368-4201 Company Name: Performance Systems Integration Mailing Address: 19310 N. Creek Pwky #109 Bothell WA 98011 City State Zip E-mail Address: carissa@psintegrated.com Fax Number: 425-368-4208 Contractor's City of Tukwila Business License number: Total number of new/relocated devices or sprinkler heads: 3 new fire alarm devices Valuation of Project (contractor's bid price): $ 2,552 Scope of Work (please provide detailed information): Addition of (3) devices to existing fire system for isolation of lube/oil system in alarm. PERMIT APPLICATION NOTES Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules. Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILDING OWNER OR UTHORIZED AGENT: Signature: Print Name: Carissa homson Plan Permit App.doc Date: L42-11‘0 Day Telephone: 425-368-4201 8/22/14 IFl) FP Form 8 AWAXIM FILE FIRE PROTECTION SYSTEMS PERMIT APPLICATION CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East Tukwila, WA 98188 206-575-4407 SITE LOCATION Date application accepted: Applications and plans must be complete in order to be accepted for plan review. **PLEASE PRINT** Site Address: ) 7-Z0O E mcw_C,c N AL wP� pAID NN -47 2012 TUKIM FIRE King Co. Assessor's Tax No.: O -733 MO 11 G Suite Number. Floor. Tenant Name; Kt ► '1 M 'TR. G New Tenant? ❑ - Yes El- No Property Owner's Name: K ► NCS C C' Mailing Address: HO I 54 A V c_ CONTACT PERSON -if there are questions about the submittaL Name: RAc-N Aflr: Y Company Name: (,LZN.V6V't..' S Mailing Address: 1-71-' F t c - S4- Ao1'2 ' ?. S,OutiN - Sez.,Ak lie, to zx • c 3 q City State Zip E-mail Address: L7ka2x+sc` S O 9 v a nC) it...0 Sec v r - COMFax Number. *2_0 (4, • 3 (I I - 9S Z C S v_ (z_U , - /I L� City oy State Zip Day Telephone: ?A(- (5Z7-- (G S'4 S >eT Valuation of Project (contractor's bid price): $ Z S CT7 Scope of Work (please provide detailed information): I T P LL �� S fO ► U 62. a ry 5 iti\ 1 -77E- 2. -70 s T Lw Ca ALP (s - PERMIT APPLICATION NOTES Value of Construction - In all cases, a value of construction amount should be entered by the applicant This figure will be reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules. Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILDING ow/s77 ORIZED AGENT: Signature: Print Name: E'R'IN c- AO A or Plan Permit App.doc Date: I -u 1ZC/ l Day Telephone: Z -C) (c - '33 (cZO (o 5/14/10 TFD FP Form 8 City of Tukwila John W. Rants, Mayor Fire Department Thomas P. Keefe, Fire Chief March 31, 1998 Fire Department Review Permit #98-F-75 (511) Re: Vehicle Maintenance Facility - 12200 East Marginal Way South Dear Sir: The attached set of building plans have been reviewed by The Fire Prevention Bureau and are acceptable with the following concerns: 1. Duct smoke detectors shall be separately zoned in the fire alarm panel. 2. Duct smoke detectors shall be capable of being reset from the alarm panel. (City Ordinance #1742) 3. Remote indicator lights are required on all above ceiling smoke detectors. (City Ordinance #1742) 4. A smoke shut -down test is required for final acceptance. Contact The Tukwila Fire Prevention Bureau to witness all required inspections and tests. (UFC 10.503) (City Ordinance #1742) Any overlooked hazardous condition and/or violation of the adopted Fire or Building Codes does not imply approval of such condition or violation. Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: (206) 575-4404 • Fax. (206) 575-4439 City of Tukwila John W. Rants, Mayor Fire Department Thomas P. Keefe, Fire Chief Page number 2 Yours truly, The Tukwila Fire Prevention Bureau cc: TFD file ncd Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: (206) 575-4404 • Fax (206) 575-4439 INSPECTION NUMBER INSPECTION RECORD Retain a copy with permit M' — °d Ly PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 206-575-4407 Project: /te /lock b Type of spection: p Address: Suite #: /2,2100 &iews Contact Person: Special Instructions: Monitor: Phone No.: Approved per applicable codes. Corrections required prior to approval. COMMENTS: eilDicle- Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: _ Occupancy Type: Inspector: Date: Hrs.: /, $100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. Call to schedule a reinspection. Billing Address Attn: Company Name: Address: City: State: Zip: Word/Inspection Record Form.Doc 3/14/14 T.F.D. Form F.P. 113 ( INSPECTION NUMBER INSPECTION RECORD Retain a copy with permit PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 206-575-4407 Project: kt 1,(4 lovu prier -a S,yeht &e'xd2-42- Typens ection /1(46- "-',4Z- Address:Contact Suite #: /2--zcd E/yl 5 Person: 6 g-155 7tJi&2 - Special Instructions: Phone No.: proved per applicable codes. Corrections required prior to approval. COMMENTS: *AT-Dprpot_ Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: 3/ 0 // q ---- 1 b -t) otAi p & /pew -wt. 0-- ivor�d-,5Ir-6--- 4-r-- 7-1 & 61=- / Jj2 Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: r Inspector: / c-4-- Date: 3h / q--Hrs.: $100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. Call to schedule a reinspection. Billing Address Attn: Company Name: Address: City: State: Zip: Word/Inspection Record Form.Doc 3/14/14 T.F.D. Form F.P. 113 t, INSPECTION NUMBER INSPECTION RECORD Retain a copy with permit PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 206-575-4407 Prrect4 r. 0 Ai kg1-71. Type of Inspectig,n. 14--- fw- /)./ 4 -2 -- Fire Alarm: Address: Si --1-7/;"? Aeitect Suite #: /2 gynvurS Person: seiiirti 24---c/4-7-- 0.<--i Special Instructions: Phone No.. Approved per applicable codes. Corrections required prior to approval. COMMENTS: Sprinklers: Fire Alarm: Hood & Duct: Monitor: f /LClPflI z4- C5i79 rte- ('146 — 0.05- Setkr Permits: MI\( -. All Ste- f`i 4* -3 4e) 4 (tceeli 51524 cprr ii t e-✓. f Sp( /Pi 4 j- q( ' O i Se 64"-e) t r� �r f L evs Flf /7/2,— Af e''-�-i Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: F-7,74 521...- Date:& //4.--- Hrs.: i $100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. CaII to schedule a reinspection. Billing Address Attn: Company Name: Address: City: State: Zip: Word/Inspection Record Form.Doc 3/14/14 T.F.D. Form F.P. 113 ( INSPECTION NUMBER INSPECTION RECORD Retain a copy with permit PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 206-575-4407 Project: MC. (r v i 1-09e,244"-- S �-ric ( Gv/i'5f'i Type of Inspection: fkN ��i' �I \//1-7.--- Address: /1 kv Suite #: (7i(Se) f AA,).•.) 5 Contact Person. Monitor: % -- Special Instructions: Phone No.: Approved per applicable codes. Corrections required prior to approval. COMMENTS: Fe41 /41Pp11— r"" 5 r - r Fif PrVED kvotve&tser s1(vr € Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: . , Date: j i l____ Hrs.: $100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. Call to schedule a reinspection. Billing Address Attn : Company Name: Address: City: State: Zip: Word/Inspection Record Form.Doc 3/14/14 T.F.D. Form F.P. 113 i INSPECTION NUMBER INSPECTION RECORD , Retain a copy with permit PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East, Tukwila, Wa. 98188 206-575-4407 Proje Co Vv)-'l'U Sprinklers: Typpf Inspection: -- - 1l4- Address�y,,, 1P- a-00 Suite #: ma'/) 5 Contact Person: Special Instr ctior(s: Phone No.: eA pproved per applicable codes. Corrections required prior to approval. COMMENTS: Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: `✓ 9_-- Date: / 7 / ?he__Hrs.: j $100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. Call to schedule a reinspection. Billing Address Attn: Company Name: Address: City: State: Zip: Word/Inspection Record Form.Doc 6/11/10 T.F.D. Form F.P. 113 I INSPECTION NUMBER .NSPECTION RECORD -b 7- /0 Retain a copy with_permit •n u a PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East, Tukwila, Wa. 98188 206-575-4407 Project: `,x, /" ` 0 Fire Alarm: Type�j Inspecti n: Op .u'si. 1C 1 oo4 Address:raaov Suite #: Cw f' Contact Person: Otr-e.. C,-,0 vl/ Special Instructions: Phone No.: 24' SNI— sc81 roved per applicable codes. Corrections required prior to approval. COMMENTS: Rr g. tZer rar,se.,A (to) Pre se, " (cJw2) Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occpancy Type: Inspector: it... .5-?___ Date: /2 12- (10 Hrs.: $80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. Call to schedule a reinspection. Word/Inspection Record Form.Doc 1/13/06 T.F.D. Form F.P. 113 TU� `VILA FIRE MARSHAL'S OF,'E Phone: 206-575-4407 • Fax: 206-575-4439 • Email: FireMarshal@tukwilawa.gov ostip CONTRACTORS MATERIAL AND TEST CERTIFICATE FIRE ALARM AND FIRE DETECTION SYSTEMS X41 Fire alarm System is ready for Fire Department acceptance testing. Failure of test will result in termination of the testing and additional fees will be assessed. Contractor is responsible for supplying manpower for Final Acceptance Test with two-way communications. Date 3 / /v// 7 Permit # - - 1 2-5 Property Address / 2 2,co E . /Mei)) Suite # City TUKWILA Zip Code `lg r6 Name of Facility ie,✓ri4 Mf r' , s-4 Occupied as 1-v� Owner or Representative Phone # Installing Company P601(LN«rs-CC- `J y44- 5 Installing Contractor's Address 16/ ?/6. N- cx c-64- Pk c„,-( 5. 5L, "tc fag City (L (1 Phone # '1V 369' Installer's Name (PRINT) M6-11 l fr l> e 2_ License and/or Certificate N`h / r General Contractor Electrical Contractor PP,/ �+ i C C4-12ti FACP Equipment Manufacturer C S+ Model # 3 This system has been installed, pre -tested and operates in accordance with the standards listed below and was inspected by NE ( L On (date) 3W I-7 and includes the devices listed on back. Circle all that apply: V NFPA 72, Chapter 1 2 4 5 6 7 and/or IFC SEC 907 V NFPA 70, National Electrical Code, Article 760 Manufacturer's Instructions 1 Manufacturer's Instructions Other (specify) / Tukwila City Ordinance Numbers 2050. 2051 UL Central Station Monitor ASA 12746(. 0 System is monitored by 6,, R -AJ SIGNED ,1 i _ Date 3// o(/7 System Firmware: / Installed version S. 3 i Checksum Date 307 Initial program Installation Date 3/ir//7 Revisions and Reasons Programmed by NF , 1 % EQUIPMENT INSTALLED AND TESTED: Control Panel j of L Make/Model o F S }0 71 P 6 Manual Station of Make/Model Smoke Detectors of Make/Model Heat Detectors of Make/Model Duct Detectors _ of _ Make/Model •2-. Z /2...t o( I S /474 G �'(' c.>")14- ( k F (/f `i 5 A/V Devices of Make/Model Audio Devices of Make/Model Visual Devices of Make/Model Auto Door Release of _ Make/Model Trouble Indictors of Make/Model Pa& - Yr -f Batteries �-�y�= t (-1(6 3 C o . 2t iAy Readings Battery Full Load Charge Generator of Make/Model HVAC Controls of Make/Model Fire Alarm Dialer of Make/Model Monitored by Annunciator of Make/Model Sprinkler System. (Fire Alarm connections only) Water Flow Sw. of Make/Model Valve Tamper Sw. _ of _ Make/Model PIV of Make/Model Elec. Alarm Bell of Make/Model Automatic time Delay of Water Flow Alarm seconds. None Installed Do you meet audible/visible requirements of WAC 51-20, IFC SEC 907., and/or NFPA 72 Chapter 6? Yes No Test of alarm System on emergency power, satisfactory? Yes 7 No Test Witnessed by W--,1 Title --1-6-{Z, Date 3/l6//7 Comments: Fire Alarm Certificate.doc Revised: 6/17/14 TFD FP Form #110 Lo 55 TU; 'VILA FIRE MARSHAL'S OFT •�E Phone: 206-575-4407 • Fax: 206-575-4439 • Email: FireMarshal@tukwilawa.gov 4; CONTRACTORS MATERIAL AND TEST CERTIFICATE FIRE ALARM AND FIRE DETECTION SYSTEMS Fire alarm System is ready for Fire Department acceptance testing. Failure of test will result in termination of the testing and additional fees will be assessed. Contractor is responsible for supplying manpower for Final Acceptance Test with two-way communications. Date 3l(e// 7 Permit # ((e- F - / Z Property Address 12- lisp e - �t-t �p ( ,A.•-• , Suite # City TUKWILA Zip Code / 9/g Name of Facility ki'a1 L7./v,v 1'f / ¢,P -v �� ,,.� `p,,,,,c �( �- Z,�f Occupied as Owner or Representative Phone # Installing Company Pe"..--/ Installing Contractor's Address l' City (-)- 4 (1 Phone # X2,5 Installer's Name (PRINT) tiE, / j %c',&- License and/or Certificate FAle« NA e,6 t K t3 General Contractor Electrical Contractor 6 . / ( 1l21'c FACP Equipment Manufacturer 5 Model # 3 This system has been installed, pre -tested and operates in accordance with the standards listed below and was inspected by lam. ( Llz On (date) 3/ta and includes the devices listed on hack. Circle all that apply: NFPA 72, Chapter 1 2 4 5 6 7 and/or IFC SEC 907 `r NFPA 70, National Electrical Code, Article 760 Manufacturer's Instructions Manufacturer's Instructions Other (specify) Tukwila City Ordinance Numbers 2050. 2051 UL Central Station Monitor System is monitored by G- �.�zc ��✓ SIGNED Date System Firmware: Installed version S, 3 1 Checksum Date 3/"% 7 Initial program Installation Date Revisions and Reasons Programmed by / , / EQUIPMENT INSTALLED AND TESTED: Control Panel 1 of Make/Model R¢'SG, A J c, - f Manual Station of Make/Model Smoke Detectors of Make/Model Heat Detectors of _ Make/Model Duct Detectors _ of Make/Model 3d 3 NsR—/a r/ 5.'/,v A/V Devices of Make/Model Audio Devices of Make/Model Visual Devices of Make/Model Auto Door Release of Make/Model Trouble Indictors 3_ of 3 Make/Model /9 rei c T / / S(<-,4 c 7 Z f Batteries Readings Battery Full Load Charge Generator of Make/Model HVAC Controls of Make/Model Fire Alarm Dialer of Make/Model Monitored by Annunciator of Make/Model Sprinkler System. (Fire Alarm connections only) Water Flow Sw. of Make/Model Valve Tamper Sw. of Make/Model PIV of Make/Model Elec. Alarm Bell of Make/Model Automatic time Delay of Water Flow Alarm seconds. None Installed Do you meet audible/visible requirements of WAC 5 1-20, IFC SEC 907., and/or NFPA 72 Chapter 6? Yes No Test of alarm System on emer Test Witnessed by Comments: ncy power, satisfactory? YesNo sp Title !VAYvt tU i /j Tt ev Date 31) b Fire Alarm Certificate.doc Revised: 6/17/14 TFD FP Form #110 TU: 'VILA FIRE MARSHAL'S OFA 'E Phone: 206-575-4407 • Fax: 206-575-4439 • Email: FireMarshal@tukwilawa.gov 4tittitt CONTRACTORS MATERIAL AND TEST CERTIFICATE FIRE ALARM AND FIRE DETECTION SYSTEMS Fire alarm System is ready for Fire Department acceptance testing. Failure of test will result in termination of the testing and additional fees will be assessed. Contractor is responsible for supplying manpower for Final Acceptance Test with two-way communications. Date /o! / 7 Permit # �C — F -- 12 3 Property Address / Z o E . it Pin 1 n-✓ S . Suite # City TUKWILA Zip Code qi3 /6g Name of Facility '< It,* Cern* �/i {L Wye Occupied as L v Del. Owner or Representative Phone # Installing Company Pte; ."- ,,.,cy- Installing Contractor's Address 19 3(e fV • C !c_- "It - $ S - I City A /4E If Phone # /2 S- -2C e--12 O j Installer's Name (PRINT) ►IIE,` f 8,dr-6z- License and/or Certificate }Pkit-,)A• gev ( 10 General Contractor Electrical Contractor P -tC- (c4 --i C. FACP Equipment Manufacturer QST Model # 3 This system has been installed, re -tested and operates in accordance with the standards listed below and was inspected by Nil On (date) 3//6:l / 7 and includes the devices listed on back. Circle all that apply: NFPA 72, Chapter 1 2 4 5 6 7 and/or IFC SEC 907 NFPA 70, National Electrical Code, Article 760 Manufacturer's Instructions 7.--" Manufacturer's Instructions Other (specify) Tukwila City Ordinance Numbers 2050, 2051 UL Central Station Monitor AL---3,zAU1 ✓o System is monitored by (xu d , -,J SIGNED �Ve—t f Date 3/ra f /7 System Firmware: Installed version 5. 3 Checksum Date 3/0i/ 7 Initial program Installation Date 3/0(7 Revisions and Reasons Programmed by Pe--; l ea= r EQUIPMENT INSTALLED AND TESTED: Control Panel / of J Make/Model (`'t 15/95 / D ( Pow, .5-4-,),..21-f G Manual Station of Make/Model Smoke Detectors of Make/Model Heat Detectors of Make/Model Duct Detectors _ of _ Make/Model 1 '�-1 S .Z '2_ AA Jf • 7 0 1 4 5 t G z4 c c.,,,rd 0 ,rd - 1 �'-r'W A/V Devices of Make/Model J Audio Devices of Make/Model Visual Devices of Make/Model Auto Door Release _ of Make/Model Trouble Indictors -of ?j Make/Model P�44.- St.-pp/1)V j�r.a,'', e)4,.J lF- Batteries T ti96_ ^4-415 l6- [3 6:Dt_4 126-1 +a rnaN, pa,,m- LosS Readings Battery Full Load Charge Generator of Make/Model HVAC Controls of Make/Model Fire Alarm Dialer of Make/Model Monitored by Annunciator of Make/Model Sprinkler System. (Fire Alarm connections only) Water Flow Sw. of Make/Model Valve Tamper Sw. of _ Make/Model PIV of Make/Model Elec. Alarm Bell of Make/Model Automatic time Delay of Water Flow Alarm seconds. None Installed Do you meet audible/visible requirements of WAC 51-20, IFC SEC 907., and/or NFPA 72 Chapter 6? Yes No Test of alarm System on emergency power, satisfactory? Yes ✓ No Test Witnessed by NE ► L A4% Title TC—cts_ Comments: Date ?/ia// 7 Fire Alarm Certificate.doc Revised: 6/17/14 TFD FP Form #110 KNEAL ELECTRIC, INC. 2709 SIXTH PL. N.E. ` RENTON, WA. 98056 P. 425-226-8441 * F. 425-228-3910 VEHICLE MAINTENANCE FACILITY 12200 EAST MARGINAL WAY S. TUKWILA, WA. FIRE ALARM SUBMITTAL Arzffr7;7;7,---1-1-7:r7-D ❑ Without Comments D As Noted In Red Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted :standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings after •i,is date will void this acceptance and will require a :submittal of revised drawings for subsequent approval. . ina1 acceptance is subject to field test and inspection by The Tukwila Fire Prevention 0419Bureauu. Date: 3/3 � By: 1411 - TUKWILA FIRE DEPARTMENT Please call: 575.4407 and give this job No. 78- F- 078 and exact address for shutd down or restoration approval. 1A@NIITIE1 Al MAR 2 7 199B ........................... rd(% O J / • KNEAL ELECTRIC, INC. 2709 SIXTH PL. N.E. * RENTON, WA. 98056 * P. 425-226-8441 * F. 425-228-3910 VEHICLE MAINTENANCE FACILITY FOR 709 (DW) TWO WIRE DUCT SMOKE DETECTOR W/ REMOTE RESETABLE POWER. WIRE SCHEDULE SIZE DESCRIPTION 2-14 SOLID THHN WORK SHEET DEVICE QUANITY STAND-BY CURRENT ALARM CURRENT F.A. I .00025 .050 HORNS 16 N/A 1.936 DUCT SMOKE 4 .000070 .060 .00032 2.049 BATTERY CALCULATIONS FORMULA: (A*B+C*D) X 1.2 = AU3 WHERE: A -STANDBY AMPS B-24 HOURS C -ALARM AMPS D-5 MINUTES (.00032*24+2.049*.083) X 1.2 = ASI (.00768+.170) X 1.2 = ASH (.17768) X 1.2 = .2132 A\H MIN. SIZE CELLS PROVIDED ARE 7.0 A\II CONTROLS COMPANY Uni-Line Division The Energy Control Company! The 26,50-430 Series Duct Mounted Stroke Deiectorsare designed for early detection cf smoke and particles of combustion pre nt In the air moving through air concttiCring cr ventilation ducts, , y are self contained, operating from alter 123VAC/244VAC/24VAC/24VDC and provide contacts for both drect fan control and capability for remote annunciation or alarm pane operation. These units consist of either aro ionization or phOtosiecitrorlie type detector assembly enc,oaed in amolded NOFRYLLplaitic hbusing with a transparent cover. The wiring Dox, containing two conduit holes, is an Integral part of the housing with =case for the detector {~reu?try by rltmov*1 of Me cover. Motafting is by means of two sprews and speeanLte. Sampling tt.be'e are available In various lengths fpr ducts uP to 12 feet in width (see Ordering lista). i All units are UL. listed ane mount easily to round or reotanfar ducts. Units are wrathy momentary lila :nrptionofpower orbyuse a remote i reset Station (see Ordering Data) - ORDERING DATA u13.uNE ttRa•LACiS moot MODEL OEECaIaTtol 2l50.450 01000ALOCI 4.W,9E IONIZATION nuCT DETECT R -1 ',B.SWer/ bH40oAC00A 4•WIRE P110TAELEOTRONID WTI OR rDETECTOR SAMPLING TUBES 1 Rseates 9T•r.6 2:491 r r-zsz beacRurnoN M6TA(.8M1PL)NO TIME (r .11 $T4 METAL $,WPuNo TIME (2.4') METAL SAMRLIN4 NBC 41') %T .SAMPUNOTiaate.:21 214793 SY-to ACCESSORIES AND REPLACEMENT PARTS oto.t.II O REPLACES ORDER No. MODEL Eld a Csemo-ot 2t.tso MOG400n 214E2 Ai650-01 rezo SOUN0ER R&°ucaMorr FAXEns (4 EAo+) •.-via 1�a14M Reguc est r14/417ATIONHFAD 2a04.074 2451 AEPLACaPJEM RHOTOELECTRON;C HEAD PRINTED IN U,S.A. $/91, REV. 3/94 DATA SHEET 2650-400 SERIES DUCT MOUNTED IONIZAi10 N/PHOTOELEC7RONlC SMOKE DETECTORS SPECIFICATIONS Operating voltace . 120VAC/240VAC/24vACr24v0C Current-consurnptlon Standby (maximum) 25rM ®24VDC Alarm (meearnum) 95mA 0 24VDC Contact ratings Alarm Initiation contacts (SPST) 2.OA ® 30VAC/D0 (0.6 power tactor) /Van auxiliary contacts (DPDT)10A eC aovDC 10A ® 277VDC (0.75 power factor) 240VA G 240VAC (0.4 power factor) 1/$14? 0 120VAC 1/4 HP 0 240VAC Auxiliary contact current must be more than 500 ilia 6 24VDC. Trouble cornets (SP$T) ....,,.„ 0.3A m 3240 (resist w{ Amblent temperature Hm is ........ 32°F to 120°F tfumidity............ ....109a so 93% rotative humidity, excluding condensation Alr duct velocity .................. ..._......... .,....... .. 300 to 4,000 toot per minute Mechanical caeca Slee (approximate) 14,1/21. x 5'W x4 -D Weight (approximate) 41bs, Resettime ............. ..... ....... ..._...... ..,...... ........ 0.3 seconds (maximum) UL Listed to 269A /914 Robortstaw Controls Company 156-553-C1 K r r' • / n 1 3 TENOUNTLAKE 0 RRACE SNOHOm I STI KING ES COUHIY T'�'-, OOTHELL si = a � 0 REOIA:No 0001 v �L'u Alr mink MA `w MU mufti's N111&. 111 I�j•� A LAKE SEATTLE 0 9ELLEVUE LOCATION MA AREA SHOWN AT LEFT 4D TACOMA 4D VICINITY MAP 0 s to ! u u MILES KING COUNTY PIERCE COINTY Ilkitli � UWAMISH 44 LAKE WASHINGTON PROJECT LOCATION 12100 EAST MARGINAL WAY S. f � %IL. ...L,"1"" kigammammial k -' �'� 1\llk 1_ � ° ii►�;iJ1�i � 1■ riEl111 elp \ 1 1 16" 1,11 -111.11114 --ccrol-11844p 41M1 LOCATION MAP 1 2 1 NtAtr • 2 !DIES A 106 .0/06 Dpa- sc./ Fkrrd?1U O,V LEGEND AREA OF WORK CONTRACTORS OFFICE I/!/d AND STAGING AREA NOTE 1. SOUTH BASE IS OPERATIONAL 24 HOURS A DAY. THE CONTRACTOR SHALL WORK WITH ALL. DUE CAUTION TO AVOID INTERFERENCES WITH BUS AND OTHER VEHICLE TRAFFIC DURING THIS WORK. THE CONTRACTOR SHALL BE RESTRICTED TO THE OUTLINED STAGING AREA AS SHOWN ON THIS SITE MAP UNLESS OTHERWISE INDICATED. 1 S. II9th MAINTENANCF OPERA1IONS BUILDING BUS ENTRANCE N Y CONTRACTORS FNTRANCF • SOUTH BASE CGI001 PANNING UNIT REPAIR j FACIUTY z FUEL/WASH BUILDING 70& SITE VmF PARKING SITE MAP o 200 400 600 FEET H ST Z TYPICAL SECTION AND DETAIL REFERENCING SYSTEM rt ( / (1) THE SECTION IS CUT ON DRAWING A101 SECTION NUMBER ELEVATION NUMBER 2/A103 A105 J DRAWING ON WHICH SECTION/ELEVATION APPEARS. - INDICATES THE DRAWING IS ON THE SAME SHEET. (2) ON DRAWING A105 THIS SECTION IS IDENTIFIED SECTION NUMBER SECTION SCALE: 1 1/2"= 1.-0" (3) DRAWING ON WHICH SECTION WAS TAKEN. - INDICATES THE DRAWING IS TAKEN FROM THE SAME SHEET. DETAILS ARE CROSS-REFERENCED IN A SIMILAR MANNER, EXCEPT THAT DETAILS ARE IDENTIFIED BY LETTER RATHER THAN BY NUMBER. SHT. NO. DWG. NO. GENERAL 2 3 DEMOLITION 4 5 6 7 INDEX DRAWING TITLE TO DRAWINGS SHT. NO. DWG. NO. MECHANICAL G101 NC?IITY & LOCATION MAPS. INDEX TO DRAWINGS G102 MECHANICAL ABBREVIATIONS. LE:.END & GENERAL NOTES G103 ELECTRICAL ABBREVIATIONS 4 LEGEND 0101 FIRST FLOOR DEMOLITION PLAN—AREA B 0102 SECOND FLOOR DEMOLITION PLAN—AREA B 0103 ROOF DEMOUTION PLANS—AREA A AND B 0104 CEUNG DEMOUTION PLAN 1S1 & 2ND FLOORS — AREA 9 ARCHITECTURAL 8 A101 9 10 11 12 13 STRUCTURAL 14 A102 A103 A104 A105 A106 5101 TEMPORARY ROOF PROTECTION PANELS PLAN SECOND FLOOR MECHANICAL I::N';LOSURE PLAN—AREA B ROOF PLANS AREAS A & B REFLECTED CEIUNG PLAN 1ST AT _ND FLOORS — AREA 8 DETAILS DETAILS DETAILS 15 16 17 18 19 20 21 22 23 24 14101 14102 M103 M104 M105 M106 M107 M108 44109 M110 DRAWING TITLE UPPER LEVEL PLAN—AREA A FIRST FLOOR PLAN—AREA 8 SECOND FLOOR PLAN—AREA 8 SECOND FLOOR MECHANICAL ENCLOSURE—AREA B ROOF PLANS—AREA AND B BOILER ROOM & BEADBLAST ROOM PARTIAL PLANS SECTIONS SECTIONS DETAILS & DIAGRAMS SCHEDULES ELECTRICAL 25 E101 ROOF PLANS AREA A&B 26 E102 SECOND FLOOR ELECTRICAL ENCLOSURE—AREA B 27 E103 BEADBLAST ROOM PARTIAL PLAN 28 0104 PANEL AND SCHEDULES RACEWAY 29 E105 DETAILS 30 E106 PANEL BOARDS & CONTROL PANEL LOCATIONS 66°1° eip6-01t.sw,L. tvi- ,10 to K 3° UNIT REPAIR FACILITY HVAC REHABILITATION CONTRACT NO. C73091C A REVISION V BY APP 'Ca DATE V C 1 0 E DESIGtED: JPB/JM DRAWN: 8 RECOMMENDED: C. JACKSON C� AMOCO R. ISLER V- CHECKED: CRJ Sfi4L NOTED CONTRACT N0: C73091C F King County DEPARTMENT OF TRANSPORTATION VEHICLE MAINTENANCE FACILITY - UNIT REPAIR 5 UNIT HVAC REHABILITATION VICINITY & LOCATION MAPS AND INDEX TO DRAWINGS V H DATE JULY 1997 FILE N0: D'9 6-1 G1O1 SHEET NO: OF 1 30 M RGI+AN 1 cA L SHoP 3- PAIRS 41. iy TO FAGP 1 N Ex \STI NG Cor DV IT - FIRE ALARM -PANEL Pr F • lkeNOrtA STo RAO E COMPRESS© R LoADIK01 006K `XXt b^ .% ($TEM PARTIAL DRAW' WTI SMOKE_LDucr DETEc1 R `4' Z'M1R %i9 SO -LW Thi- N ALARM► c1(T. =L # 1Q .SOt 714 Nt R ESET"A BLE W R . LV NGN Qo o r" AC 101 RooF -2 PA►R * l I 0-1 0 MENS RO0M% AC. 103 RooF WoMCNS Room 'fill MZU (Oi E,O.I.. Z.PAIR itt ly PARTS sroRA4 2►' RAO R. MA 1 NT oFF►cE VEN tcLE M,4+ NTEomcz F#ci 1. rY 12 2, oo EAS'r MA SiPPr.. WRY SCALE: 1 � 20 DATE :3-20_96 APPROVED BY: DRAWN BY KEt. REVISED ADO y DUCT SMOKE. DETECTGRS o'sir RALT aet C7309lc DRAWING NUMBER GUARDIAN SECURITY Seattle- Tacoma - Poulsbo - Bellingham June 26, 2012 City of Tukwila Fire Depaituient Headquarters — Station 51 444 Andover Park East Tukwila, WA 98188 RE: Installing AES Radio Transmitter 1743 First Avenue South Seattle, WA 98134 Tel: 206.622.6545 Fax: 206.341.9928 TUKWILA FIRE DEPARTMENT Please r-311206-575-4fi07 and give this Fire Permit No. and exact address for shut- down hutdown or restoration approva. Guardian security would like to request a fire permit to install an AES RADIO Transmitter to monitor the existing FACP (EST -3). Northwest Alarm Central Station located at 1743 First Avenue South, Seattle, WA 98134 will be monitoring the following address: KING COUNTY METRO COMPONENT SUPPLY CENTER 12200 E MARGINAL WAY SOUTH TUKWILA, WA 98168 Thank you, Traci Adams Guardian Security 1743 First Ave. South Seattle, WA 98134 Phone: 206-622-6545 Ext: 217 Email: tadams@guardiansecurity.com CI Without Comments pr As Noted in Red /❑ Per The Attached Letter 'hese plans have been reviewed by The Tukwila Fire ,.iention Bureau fCr conformance *cab current City :idards. Accerr, is >ubject to errors and fissions which r.r..;4., auvr,ornze v-oiarions of adopted odards ana cr'":"•r"~:c as. 17:= responsibility for the ,quacy of de.>>, : 1s k��t;?11v wit the designer. dons, deleticr, • ,'E v; :loafs to r6;ese drawings after rnis date will void rr,:. `:ept nct: nd wi require a resubmittal of re: r,e l iyewi a r(,' uosequent approval. aminal acceptance k. C) field test and inspection by The Tukwila Fire P.', ✓girls. �t : 1 4. eau. Date:7— 5-- l i- 6v: WO LU 1— 0 o; Lu CO I (y/ iv) Lu;» Q Z wl V'J Z co °"0-10— DCY co LU OWJ O � i Nr PLANS BY: BILL DRIVER NICET FIRE ALARM SYSTEMS LEVEL III: 129292 DC DRAWN BY EC CHECKED BY 02/22/2016 PLAN SUBMITTAL REVISIONS PLOT DATE 02/22/2016 PROJECT NUMBER 107668PW SHEET TITLE COVER SYSTEM SCALE N/A SHEET N.. FA -0.01 N W W N CABLE TYPE CABLE USE FIRE DETECTION & ALARM - WIRE SCHEDULE ABCDEFHPX SOUND AND DISPLAY AT REMOTE FIRE ALARM ANNUNCIATOR ACTIVATE HORN -STROBE CIRCUITS ALARM SIGNAL TRANSMIT THRU FACP DIALER TROUBLE SIGNAL TRANSMIT THRU FACP DIALER SUPERVISORY SIGNAL TRANSMIT THRU FACP DIALER LUBE OIL SHUT -DOWN PANEL SHUT -DOWN ANTI -FREEZE AND LUBE OIL PUMP 12" x 10" x 6" i 12 AWG PAIR POWER SUPPLY — BY OTHERS ILA o FIRE ALARM SYSTEM OPEN CIRCUIT 0 14 AWG PAIR ® o 0 0 0 INTELLIGENT DUAL INPUT MODULE FIRE ALARM SYSTEM GROUND FAULT 0 0 16 AWG PAIR — 0 o FIRE ALARM CONTROL TERMINAL CABINET FIRE ALARM SYSTEM TROUBLE 0 0 0 E 18 AWG PAIR o BY OTHERS EOIR END OF LINE RELAY -#A77 -716B — • • EXISTING SUPERVISORY NOT SHOWN 0 0 FPLR OR FPLP (AS REQUIRED) 0 • 0 0 0 0 0 0• SHIELDED 0 NEW CIRCUIT POWER STATUS 0 0 0 0 T 0 TWISTED NEW MECHANICAL BYPASS VALVE 0 0 0 0 RATED FOR UNDERGROUND AND WET CONDITIONS (AS REQUIRED: 0 0 0 0 0 0 0 0 0 SIGNAL LINE CIRCUIT (SLC) 0 CONVENTIONAL INITIATING DEVICE CIRCUIT (IDC) o ZONE INPUT o RELAY OUTPUT o NOTIFICATION APPLIANCE CIRCUIT (NAC) o REMOTE ANNUNCIATOR 24VDC PWR o REMOTE ANNUNCIATOR RS485 DATA 0 AUDIO RISER o SPEAKER CIRCUIT 0 DOOR HOLDER CIRCUIT 0 AUX 24VDC PWR 0 RS232 (USE 18 AWG PAIR / SHIELDED, TWISTED) NOT ALL CABLE TYPES MAY BE USED IN PLAN w 0 , tt r. Without Comments As Nosed in Re0, 0 Pe; The Attached Letter These e plans have tic4-1-0 °j;' :vention Burecu. 'r,.- ,i:andards. Accept: omissions whicr, .�tandards ano c:• ;.;ciequacy of desua' • :additions, ceietic� <• I:hls date will vote , r'. resubmittal riewed by The Tukwila Fire - formance with current City ;, alert to errors and :or at ,,,ofation of adopted roe +esuansihffit/ for the with the designer. These drawings after ;epce c.e and will require a :y.7,,rinns .:;,,ibsequent approval. Final acceptance rs si.folecs t.c) neio test and inspection by The Tukwila Fire Prevention Bureau. Date: ( 10-1S.. 7. `WI L A FIRE DEPART HENT .::::!G6 -575-4,i07 �^a give this Fire Permit Flt No - I 'i and exact add ass for shut- down or restoration zIpprov as EXISTING TO REMAIN NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement ©f Acceptance Testing of any 'Fire Alarm and Detection 5yst nis. Failure of test will result in a Re -inspection Fee and termination of the testind FDA - SYSTEM INPUTS FIRE DETECTION & ALARM - SYSTEM OUTPUTS EXISTING FIRE ALARM SYSTEM NEW POWER SUPPLY AND FIELD DEVICES AREA OF WORK FACP 0000 CASP 00 00 A BLOCK DIAGRAM - SYSTEM NOTES (CLASS B SYSTEM) : ODETECTORS: DUCT SMOKE TYPE, SMOKE, HEAT... OMONITOR MODULES: INPUTS FOR CONVENTIONAL TYPE DEVICES, WATERFLOW, SPRINKLER SUPERVISORY, HVAC, ELEVATOR, CRITICAL PROCESSES... (47K OHM EOLR AT LAST DEVICE) ORELAY MODULES: OUTPUTS FOR AUDIBLE TEMPORAL PATTERN GENERATORS, HVAC, ELEVATOR, CRITICAL PROCESSES (THRU MULTI -VOLTAGE CONTROL RELAY AS REQUIRED) 0 MANUAL PULL STATIONS OHORNS, STROBES, HORN -STROBES... (EOLR AT LAST DEVICE) 0120VAC MAIN POWER FOR THE FIRE ALARM SYSTEM (RE -USE EXISTING). THIS SYSTEM REQUIRES A DEDICATED CIRCUIT THAT IS LABELED "FIRE ALARM CIRCUIT' AND IS ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL. OCIRCUIT BREAKER LOCATION(S) SHALL BE PERMANENTLY NOTED AT ALL FIRE ALARM PANELS 11I\L L1L1 SYMBOL DESCRIPTION (SOUND AND DISPLAY AT FIRE ALARM CONTROL PANEL I SOUND AND DISPLAY AT REMOTE FIRE ALARM ANNUNCIATOR ACTIVATE HORN -STROBE CIRCUITS ALARM SIGNAL TRANSMIT THRU FACP DIALER TROUBLE SIGNAL TRANSMIT THRU FACP DIALER SUPERVISORY SIGNAL TRANSMIT THRU FACP DIALER LUBE OIL SHUT -DOWN PANEL SHUT -DOWN ANTI -FREEZE AND LUBE OIL PUMP 12" x 10" x 6" i ENCLOSURE BY OTHERS POWER SUPPLY — BY OTHERS ILA MULTI -VOLTAGE CONTROL RELAY FIRE ALARM SYSTEM OPEN CIRCUIT 0 0 ® INTELLIGENT CONTROL RELAY MODULE 0 PLUG IN UIO MOTHERBOARD © INTELLIGENT DUAL INPUT MODULE FIRE ALARM SYSTEM GROUND FAULT 0 0 FIRE ALARM CONTROL PANEL — 0 liZAE FIRE ALARM CONTROL TERMINAL CABINET FIRE ALARM SYSTEM TROUBLE 0 • 0 E SOLENOID o BY OTHERS EOIR END OF LINE RELAY -#A77 -716B — BY OTHERS EXISTING SUPERVISORY NOT SHOWN 0 0 0 EXISTING ALARM INPUT NOT SHOWN • • o 0 0 0 NEW CIRCUIT POWER STATUS 0 0 0 T 0 NEW MECHANICAL BYPASS VALVE 0 0 0 0 EXISTING FIRE ALARM SYSTEM NEW POWER SUPPLY AND FIELD DEVICES AREA OF WORK FACP 0000 CASP 00 00 A BLOCK DIAGRAM - SYSTEM NOTES (CLASS B SYSTEM) : ODETECTORS: DUCT SMOKE TYPE, SMOKE, HEAT... OMONITOR MODULES: INPUTS FOR CONVENTIONAL TYPE DEVICES, WATERFLOW, SPRINKLER SUPERVISORY, HVAC, ELEVATOR, CRITICAL PROCESSES... (47K OHM EOLR AT LAST DEVICE) ORELAY MODULES: OUTPUTS FOR AUDIBLE TEMPORAL PATTERN GENERATORS, HVAC, ELEVATOR, CRITICAL PROCESSES (THRU MULTI -VOLTAGE CONTROL RELAY AS REQUIRED) 0 MANUAL PULL STATIONS OHORNS, STROBES, HORN -STROBES... (EOLR AT LAST DEVICE) 0120VAC MAIN POWER FOR THE FIRE ALARM SYSTEM (RE -USE EXISTING). THIS SYSTEM REQUIRES A DEDICATED CIRCUIT THAT IS LABELED "FIRE ALARM CIRCUIT' AND IS ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL. OCIRCUIT BREAKER LOCATION(S) SHALL BE PERMANENTLY NOTED AT ALL FIRE ALARM PANELS 11I\L L1L1 SYMBOL DESCRIPTION LV I IlJIN Oc /`1L/"1f\IVI J 1 IVIL)'.JL.)) / UfAL,I\ MOUNTING BOX L)\JA IINI VI\IVIrAI IVIN INSTALLATION NOTES f to,;.. -2 COMPRESSED AIR SHUTDOWN PANEL 12" x 10" x 6" i ENCLOSURE BY OTHERS POWER SUPPLY — BY OTHERS ILA MULTI -VOLTAGE CONTROL RELAY — MOUNT WITHIN 3' OF CONTROLLED DEVICE IR101 ® INTELLIGENT CONTROL RELAY MODULE — PLUG IN UIO MOTHERBOARD © INTELLIGENT DUAL INPUT MODULE — PLUG IN UIO MOTHERBOARD FIRE ALARM CONTROL PANEL — EXISTING DEVICE TO REMAIN UNLESS NOTED liZAE FIRE ALARM CONTROL TERMINAL CABINET — EXISTING DEVICE TO REMAIN UNLESS NOTED lL9E 0 E SOLENOID — BY OTHERS EOIR END OF LINE RELAY -#A77 -716B — BY OTHERS EQUIPMENT LIST QUANTITY MODEL MANUFACTURER DESCRIPTION 1 1 1 MR101/C SIGA-CR SIGA-CT2 EST EST EST RELAY SINGLE SPDT WITH LED IN METAL ENCLOSURE CONTROL RELAY MODULE - UIO MOUNT DUAL INPUT MODULE - UIO MOUNT PROJECT INFORMATION FIRE ALARM WORK (BOTH DESIGN AND INSTALLATION) SHALL COMPLY WITH THE FOLLOWING: • NFPA 72, IFC, IBC AND ADA; EDITIONS AS ADOPTED BY CITY OF SEATTLE FIRE DEPT. • IN ACCORDANCE WITH ALL APPLICABLE CODES AND STANDARDS AND ALL REQUIREMENTS OF THE STATE OF WASHINGTON; KING COUNTY AND CITY OF SEATTLE • NFPA 101 • UFC O NFPA 70 O NFPA 72 • FM GLOBAL DATA SHEET 5-40 • FM GLOBAL DATA SHEET 5-48 LIFE SAFETY CODE UNIFORM FIRE CODE NATIONAL ELECTRICAL CODE NATIONAL FIRE ALARM CODE FIRE ALARM SYSTEM AUTOMATIC FIRE DETECTION SCOPE OF WORK • ADDITION TO EXISTING AUTOMATIC, MICROPROCESSOR BASED, ADDRESSABLE TECHNOLOGY, ZONED, FULLY SUPERVISED, CLASS B FIRE ALARM SYSTEM O FIRE ALARM SYSTEM TO FUNCTION AND BE PROGRAMMED/CONTROLLED FROM THE EXISTING FIRE ALARM CONTROL PANEL (NOT SHOWN IN PLAN) • OUTPUTS AND RELAYS (LOAD RELAYS FOR HVAC SHUTDOWN EXCLUDED) PROVIDED FOR AUTOMATIC ALARM OPERATIONS AS REQUIRED O FIRE ALARM PANEL INTERCONNECTION AND PROGRAMMING - INTERCONNECT THE LUBE OIL ISOLATION CONTROL WITH EXISTING FIRE ALARM PANELS TO CONTROL THE ISOLATION SYSTEMS IN THE EVENT OF A FIRE ALARM. ASBUILT NOTE TO INSTALLING CONTRACTOR INSTALLING ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING A SINGLE ACCURATE AND LEGIBLE RELINED DRAWING SET. DRAWINGS SHALL BE REDLINED AS NECESSARY TO SHOW THE FOLLOWING: • DEVICE AND PANEL LOCATIONS, ADDITIONS, DELETIONS AND ADDRESSES OR BAR CODES • CIRCUIT NUMBERS • WIRE AND CONDUIT ROUTING • WIRE FILL USING WIRE CODE FROM LEGEND ON SHOP DRAWINGS • EOL RESISTOR LOCATIONS AND VALUES PERFORMANCE SYSTEMS INTEGRATION WILL INCORPORATE ALL REDLINDED CHANGES INTO THE RECORD AUTOCAD SET OF DRAWINGS FOLLOWING THE RECEIPT OF THE REDLINED DRAWING SET. PAID JUN •- 6 2016 :OKI/VILA FIRE z Ow — W 0 E- V) <C (/) NONREVENUE VEHICLE MAINTENANCE (1ST FL) ATLAN'fiC BASE BUS PARKING 0 zw J F - (f) < 0) : D 0 ca 0 CENTRAL GARAGE 1 0 .1•1 5 ATLANTIC CENTRAL BASE 1�, BUS PARKING D LL 1. CENTRAL VM 0 CAUHIER'S }`; OFFICE ......................... E-31 BUS WAY BUS PARKING OPSNM BLDG g F ti FA1 YERSO BUS PARKING FOURTI=hWEE=r5OUTH S MASSACHUSETTS S 1/ 1111 I d 11, Np 12 7TH AVE NE EELLEVUE BASE FUEL/WASH BUS PARKING 2 STORAGE ri n BUS PARKING O ASH EMPOYEE PA KING FUEL OPERATIONS AND MAINTENANCE BUILDING 124TH AVE NE EAST PSE EMPLOYEE PARKING 1 ` BUS PARKING GARAGE 1 BUS PARKING FP ....w LL OPERATIONS MAINTENANCE NORTH BASE NORTH BASE SCALE: NONE ATLANTIC, CENTRAL, RYERSON, NRV BASE SCALE: NONE BELLEVUE, EAST BASE SCALE: NONE SOUTH BASE / / / i / / / / / /,./ /' ,// / ////' / /,,,,/ / // / i `\ l' 0rn S-rogPG. [-r Z Fit [ < W� U 5001 vC-�‘o1 GOsi'� SOUTH BASE SCALE: NONE I FIRE DETECTION AND ALARM ADDITION z 0 V) 0 0W OO W >. 1— Q z3 w o� >- < a_ - z w - co Q 0, LLJ zN OWJ O c ►— PLANS BY: BILL DRIVER NICE FIRE ALARM SYSTEMS LEVEL III: 129292 DC DRAWN BY EC CHECKED BY 02/22/2016 PLAN SUBMITTAL REVISIONS PLOT DATE 02/22/2016 PROJECT NUMBER 107668PW SHEET TITLE AREAS OF LOCATON SCALE N/A SHEET FA -0.02 SHEET SIZE: 22X36 IN 1 l,L I;L .111 ii. ,_. r _......r.{� f//7/77/%%77/77777-7/777/777.14.1 7�.... . 1.... t r i 2X J i TOM SLC(SIGNALI TO EXISTING .`•a.: TEM Al* WE' DOOR RI FI T `Prd - UT P-1 E-EZ-E--S-CU 13 E Q'11F If CI CUIT P; WEF ) i_. ANICAL BY ) s E CIRCUIT) MP TUS'< 47K EOLR MINO VALVE < 47K i'( Dkj- AREA OF WORK - ENGINE DYNAMOMETER AREA LARGE UNIT STORAGE ROOM - PARTIAL PLAN SCALE: 3/8" = 1'-0" PLAN NOTES: FIELD VERIFY LOCATION INSTALL MFC -A WITHIN 3 FEET OF THE SHUT OFF PANEL. SOLENOID AND RELAY POWER SUPPLIED FROM SHUT OFF PANEL. AREA OF WORK 1 sr a 11 1 SIGA-CT2 j 0 0 0 0 Typical Wiring Mxiu!es will accept 018 AWG (0.75mm7, 01E (1.0mm ), and Ot14AWG (1.50rnmrj, and 0(2 AWG (2.5C1-nrn7) wire sizes. Note: Sizon 016 AWG (1.OrnmT) and 018 AWG (0:75mn) are preferred for ease of installation. See Signature Loop Controller catalog shoot for detailed wiring requirrzment specifications. loll lating(Sto(e) Oevice Cireuit Wirer Specifications Ma l u rn Anart+r ble Wire Resistance Maximum Allowable Wire Capacitance For Design Reference: INJULC Lirlud 470)1 fol_ 50 ohms (25 ohms per wire) per Circuit . (110' per Circuit Wire Size 018 AWCi (0.75 nsrr") A16 AW(311.00 nsn) 014 AWG (1.50 mret) # 12 AWG (1.50 nunTJ__ Typical NO Initiating Device Input 2 Oats In + Signature Own circuit Daman AAA A 1 Alnxirnunt Dist»ace to EOLR 4,000 tt 0,219 m) ULIULU Listed 47tM1 C01 1.1412 UIOr*7 series rnottierixwrd No connections required for 14012 Other modules me ' require connections. Green (.ED mNormn() Red1E01Actts:el - No connections or Jurncersettinos reyulreJ kut-12T2. SIGA-MCT2 NOTES 1Q Maximum 25 Ohm resistance per wire. Q Maximurn 012 AWG (2.5 rnm2) wire: Minimum #18 AWG (0.75 mm2). QRefer to Signature controller installation sheet for wring specifications. Maximum 10 Vdc Cr 350 pA A The SIGA-U106R and the SIGA-U1021t do not come with Tal 4. 6 All wiring is supervised and power -limited. 7 These modules will not support 2 -wire smoke detectors. MR101 /C Installation Wiring (TYPICAL FOR ONE MODULE POSITION) SPOT Contacts 10AMPS 5) 115 V.A.C. III NC C N6 input 1 • 0 24 ,Is 230 Control Volt ego 2avoO ----.._ 1A vat .....�....« r vee Z4 vq • 0 iEwU NAA. STe CArmEr.TtCEN MR -1o1 Power Requirements' MR -101 Position 15 mA a 24 Vac, 24 Vdc. 115 Vac, 230 Vac PARTS LI F'Jttit"rFiaPLY-=F3Yti- E'01-R-ENdLoiEr4CMCErJBit1oir(ERxi EOLA • en TG-Ci.iFitllEy�yiE�s Cti riii•riifP.1 �:JrLE erIt GA=CO;VtTCFL RE'�,'ICY-ESr-"c'�+4 GF? }x11.FE1-1,'d->=a rARLIVC-,. 1 1)D1?♦ ,vt�LE1)C1F� (t3Y DTH! R i'.-`.GJ;flOTFit C MPRESSXD tER I -FT -DOM SCHEMATIC ugeJ, 14Ept.,a.' E TRF E. (tyPic.OFDI?3 1:4AP,tr-!'L,t T[Fat�s`` .N >F ir*i Th ,,l r ,I Ce roeTIiCWi't IitruTv-041,i}E OFT €sdMiNED i3'>t'Yr1E F111rALMA tr.7t"#U'.X!i'ltirb3 6tfthstrti rLk 1: Fi.11�L4l1aE.•w�i11I r�lrll_I..r1(irt)di;: • Iff?IEM !915U�xirtltk�1+1 • *4OLp L LLEF Iti PrillInixigL FOR MoONtItoi 1111_ t.l t Nt itTI r?FLAY 5: _ le]LC�TtitILLECIQi 'OrEArc "RabAfib ,PRr,FN LEr Itibi'.3 Sit E VIEW )VER COT TI ESSEL, Ala tHuT-covvN pNCLO SLI R,E. LAYQ INSIOE BOX.. ,IiJIPT1 NAMEPLATES NAMEPLl1`E.SS" 1 .L MS I MSR SIILITUOWN: C NtJoL f , ) LIGHT INDICATE k ALARM COMM '8. Ea Al RSR UTCOt . ED L14iTt RecA OrPRSlR of mAtit>L EYP SS TRQUIILE SENT : i1 F1111 Putti SIGA-CR Relay Type and Rating Form C, 2 Amps 0 24 Vdc (pilot duty), 0.5 Amps 0120 Vac and 0.25 Amps 0 220 Vac (220 Vac is non -UL) Not rated for capacitive loads. Typical Wiring Modules vAi accept 418 AWG (0.75mm'i, 016 (1.0mm7, 414 AWG (1.50mmr) and #12 AWG (2,5mm7 wire sizes. Note: Sizes 4016 AWG (1.0mm') and #16 ANG (0.7Emm7) are preferred for 9ase of installation. See Signature Loop Controller catalog shoat for d'talod aririna requirement !recitations. Normally- Normnfly- Open Ccnrnon Closed 0A1A IN (4-)1 DATA IN (-) from Signofure Controller or PreVous Device Rod LED (Alarr nfActve) Ts 101 SIGA-CR Control Relay Green LED (Marmot) DATA 0111 (a) 1 DATA OM (-) )} Te Next Dev:cu Notes zt Refer to Signature Loop Controller instaflation Sheet for wiring specifications. Typical Wiring Modules will accept 4#18 AWG (0,75mm7), #16 (1.Omm'), and #14AWG (1.5Omml, and #12 AWG (2.5Omm') wire sizes. Note: Sizes 416 AWG (1.Omm5) and 418 AWG (0.75rnm55) are preferred for ease of installation. See Signature Loop Controller catalog sheet for detailed wiring requirement specifications. Initiating (Slave) Device Circuit Wire Specifications Maximum Allowable Wire Resistance Maximum Allowable Wire Capacitance For Design Reference: 50 ohms (25 ohms per wire) per Circuit 0,1pF per Circuit Wire Size Maximum t5lstance to EOt R #18 AWG (0.75 n'0117) 416 AWG (1.00 mm2) #14AWG (1.50mm2) #12 AWG (1.50 mm2) 4,000 ft (1, ?16 m) LAU Z <cccD H-= 2".11- ci) Uzi 2 W LAJ C!' C') w� no N r�'x ' °o E O Muj u rn W rsia 13d Cit 0 C ti 1%\ O W 00 w MU N P4 o 0 0 ce co Lu J W ZQ W of �< Z 00 NDe co Q� W i- ZN ow 0a X3 N � PLANS BY: BILL DRIVER NICET FIRE ALARM SYSTEMS LEVEL iII: 129292 ( DC DRAWN BY EC CHECKED BY 02/22/2016 PLAN SUBMITTAL REVISIONS PLOT DATE 02/22/2016 PROJECT NUMBER 107668PW SHEET TITLE PARTIAL FLOOR PLAN SCALE 3/8" = 1'-0" SHEET Prilfful? 411J(7pi.t, .214 PARTS LI F'Jttit"rFiaPLY-=F3Yti- E'01-R-ENdLoiEr4CMCErJBit1oir(ERxi EOLA • en TG-Ci.iFitllEy�yiE�s Cti riii•riifP.1 �:JrLE erIt GA=CO;VtTCFL RE'�,'ICY-ESr-"c'�+4 GF? }x11.FE1-1,'d->=a rARLIVC-,. 1 1)D1?♦ ,vt�LE1)C1F� (t3Y DTH! R i'.-`.GJ;flOTFit C MPRESSXD tER I -FT -DOM SCHEMATIC ugeJ, 14Ept.,a.' E TRF E. (tyPic.OFDI?3 1:4AP,tr-!'L,t T[Fat�s`` .N >F ir*i Th ,,l r ,I Ce roeTIiCWi't IitruTv-041,i}E OFT €sdMiNED i3'>t'Yr1E F111rALMA tr.7t"#U'.X!i'ltirb3 6tfthstrti rLk 1: Fi.11�L4l1aE.•w�i11I r�lrll_I..r1(irt)di;: • Iff?IEM !915U�xirtltk�1+1 • *4OLp L LLEF Iti PrillInixigL FOR MoONtItoi 1111_ t.l t Nt itTI r?FLAY 5: _ le]LC�TtitILLECIQi 'OrEArc "RabAfib ,PRr,FN LEr Itibi'.3 Sit E VIEW )VER COT TI ESSEL, Ala tHuT-covvN pNCLO SLI R,E. LAYQ INSIOE BOX.. ,IiJIPT1 NAMEPLATES NAMEPLl1`E.SS" 1 .L MS I MSR SIILITUOWN: C NtJoL f , ) LIGHT INDICATE k ALARM COMM '8. Ea Al RSR UTCOt . ED L14iTt RecA OrPRSlR of mAtit>L EYP SS TRQUIILE SENT : i1 F1111 Putti SIGA-CR Relay Type and Rating Form C, 2 Amps 0 24 Vdc (pilot duty), 0.5 Amps 0120 Vac and 0.25 Amps 0 220 Vac (220 Vac is non -UL) Not rated for capacitive loads. Typical Wiring Modules vAi accept 418 AWG (0.75mm'i, 016 (1.0mm7, 414 AWG (1.50mmr) and #12 AWG (2,5mm7 wire sizes. Note: Sizes 4016 AWG (1.0mm') and #16 ANG (0.7Emm7) are preferred for 9ase of installation. See Signature Loop Controller catalog shoat for d'talod aririna requirement !recitations. Normally- Normnfly- Open Ccnrnon Closed 0A1A IN (4-)1 DATA IN (-) from Signofure Controller or PreVous Device Rod LED (Alarr nfActve) Ts 101 SIGA-CR Control Relay Green LED (Marmot) DATA 0111 (a) 1 DATA OM (-) )} Te Next Dev:cu Notes zt Refer to Signature Loop Controller instaflation Sheet for wiring specifications. Typical Wiring Modules will accept 4#18 AWG (0,75mm7), #16 (1.Omm'), and #14AWG (1.5Omml, and #12 AWG (2.5Omm') wire sizes. Note: Sizes 416 AWG (1.Omm5) and 418 AWG (0.75rnm55) are preferred for ease of installation. See Signature Loop Controller catalog sheet for detailed wiring requirement specifications. Initiating (Slave) Device Circuit Wire Specifications Maximum Allowable Wire Resistance Maximum Allowable Wire Capacitance For Design Reference: 50 ohms (25 ohms per wire) per Circuit 0,1pF per Circuit Wire Size Maximum t5lstance to EOt R #18 AWG (0.75 n'0117) 416 AWG (1.00 mm2) #14AWG (1.50mm2) #12 AWG (1.50 mm2) 4,000 ft (1, ?16 m) LAU Z <cccD H-= 2".11- ci) Uzi 2 W LAJ C!' C') w� no N r�'x ' °o E O Muj u rn W rsia 13d Cit 0 C ti 1%\ O W 00 w MU N P4 o 0 0 ce co Lu J W ZQ W of �< Z 00 NDe co Q� W i- ZN ow 0a X3 N � PLANS BY: BILL DRIVER NICET FIRE ALARM SYSTEMS LEVEL iII: 129292 ( DC DRAWN BY EC CHECKED BY 02/22/2016 PLAN SUBMITTAL REVISIONS PLOT DATE 02/22/2016 PROJECT NUMBER 107668PW SHEET TITLE PARTIAL FLOOR PLAN SCALE 3/8" = 1'-0" SHEET EXISTING 11¢' MNN 2�t x >lf MECH TEE 22X20(E) UP TO HV -8 W/ TURN VANES L. RADIATOR SHOP 10x16E DN (TYP 2)-\ 16x10E (` 16x9S 171 T 6x9S 16x10E SD -1 160 690 CFM /TYP 2) 1 22X20(S) UP TO HV -8 W/ TURN VANES SD -2 L 18x18 1180 CFM (TYP 4) 9 20X14E DN TO 1' AFF 18x12S 20x14E 18x12S N WELDING HOP N(11 20X14 ON TO 8' AFF N 20x14E 18x12S 35X20(S) UP TO HV -9 W/ TURN VANES 118x12S 38x14E JJ !/moi 35X20(E) UP TO HV -9 W/ TURN VANES 58x14 20x14E EXST 42x28 TRANSFER 18x12E \-12x18E DN (TIP 2) /18x12E SHEET METAL LAYOUT 28x18E \--25x16$ \-24x16E ER -1 122x10 835 CFM (TYP 3) 18x18E-\ 24x12E 14x12E 9 20xi4E DN 1 1 SD -2 18x18 1385 CFM (NP 4) `-20x12S 14-0 48x2 /48x165 SHEET ET SHOP 4LO \-20x 2S 18x12E CHIEF BODY SHOP 12X10E DN 16X1RE 12x11 S DN 10x8S DN\ w® 20x14E DN TO 8'-8"AFF 20x18E 22x14E 14 18x14S SD -2 18x18 1295 CFM (TYP 12) I !� "-18x12E 1 TROLLEY POE SHOP CHIEFELE SHOP 18x12E STAIR NO6 /18x12_ DN MEMTYP =) ® 12x10E, OFFICE 12x105- 11 6x1 0 S 2x105 20x14E \ 116x1OS L10x8E DN ® I�!1 k11 -132x14E 7 1� SD -1 8x8 200 CFM (TYP 2) -8S �Sx8S 12x8S, 20x14E \20x14 ‘ 116x9S 11 iE `1 1J1 • Li 20xl8S-'4 i I 20x18S II 16x95 EG -1 18x10 720 CFM—. 18x14S STORAGE 010 13¢ x 1 MECH TEE 26x14S MACHINE SHOP 30x20E 14x22E DN (TYP 4)—N 22x20E 22x14E 30x22 1 1/2 .L — 1 1/4 1-6\ � ) 26x14S 1Y x 1 WE H 1EE -44x20E _ 1 1/2- -� IXx1 %HZ - — r MECH / 1-6 =" ER -1 36x12 1285 CFM (TYP 6) a .- 1-BOE Ni 122x14E i i 22x20E 11 'c i v • 11/2 . I 1 1/4 Z — / 1Y x 11MECH IEEJ MACHINE 72 22S 26x14S I0 Iz 44x20E 3Cx2OE r22x 14E ( DN 19 14-c6.E 16x14E DN-/ SD -2 15x15 �C I 825 CFM 1 (TYP 3) 16x14E DN 20x20E 20x18SN 16x165 36x20E 38X22E 22x20E �16x14E DN 14x20E TRANSMISSION SHOP 7 20x20S (j t OxRE f 16x14E DN-/ 10x 16x2OS j 16x14S 22x14E ER -1 22x10 690 CFM (TYP 4) 22x14E DN 34X20E UP TO 44J-3 W/ TURN VANES AND 1' SOUND UNER #4205 UP TO HV -3 W/ TURN VANES AND 1' SOUND LINER SD -2 15x15 825 CFM �! (TYP 3) /- 1 11 S TRANS O 14x22E DN -� 10x8S DN EXST PENETRATION ER -1 22x10 690 CFM (TYP 4) 14x22E DN 26x14E 26 20E Ox20E I SD -2 18x18 1230 CFM (TYP 6) /-20x12S FOREM®S OFFICE 22x20E 122x14E1 12x16E 'DN (TYP 4) -tel 16x8S 24x18S SD -i 164 ELECTRICAL SHOP 935 CFM con (TYP 2) 24x1 S SD -1 140 545 CFM (TYP 3) 16x8S 24x8S _'x12S PAS 3E IA METAL RAY PASSAGE 16x'12E -• TAIR NO 5 1'20x14= ON (TYP 2) SD -1 160 700 CFM i'' i,��; i (TYP 3) STORAGE CORRIDOR 50-1 160 700 CFM (TYP 6) 10x -.1"S SR -1 12x8 360 CFM (TIP 2) 18x9S - L UPHOLSTERY SHOP 1 'N\ 14x10E 18x10E DN — SD -1 140 630 CFM (TYP 2) 16x9S 36x9S 36x155 r -- r 1 22X14S--_J21 20x14E-1 .-22x1 20x14E 7-16x14 TORAGE I Jv 20x32 UP W/ �� TURNING VANES TRANS i0 14x38E/./c UP TO HV -1 1 -- �--( 18x20E 42x14E 18x10E 18x18S DN TRANSITION UP TO 20x12S UP TO HV -11 EG -1 18x10 -:G 07M 1 OL -T20x14E 16112E N 10x1 GS MEG NAFLUX �1r_X15S MEN CMG W® FLAIR BOX REPAIR ICED �10x10S ^._-14L10E DI \I ruSD -2 10x10 450 CFM i (TYP 2) CO® R FIRST AID COB U4 x 1 MECH TEE- 1 1/2 1 1/2 68x14E W/ TURNING VANES UP` TO 1fix118S 16xiOS 16x95 15x10E N SD -1 140 p I. 630 r • r; • P v1' 1 CORRIDOR 1 1/2 20X40E UP W/ TURNING VANES. TRANS TO 35X20 Ufa TO HV -13 20x18S I SIGN e 24X165 'W/TURNING VINES UP TO ,Mu - CHIEF SIGN STAIR NO HOOD t SD -2- 18x18 1240 CFM —18x12S 42x185 SD -1 12X18 DN W/ FIRE DAMPER 10x10 335 CFMI;�] 10x8S--/ -i,4.:ti.3 'W/ - --L I TURNING VANES TAN SITION TO X20S UP TO FJ -13 J 18x12S -' 160 NMI MINI 4x8S ---14x20S DOWN W/VANES 0 PAINT L.. `18X12E 8S 111822X4001:3I:S I • J 1-1 12x265 DOWN W/VAN ES —20x12S v20"0E DN & UP TO F-25 0 t4x10E MECHA® SHOP 32x20S 22x: -- 20x12S SD -2 18x18 1230 CFI (TYP 7) r- 44x205 20x112S 58x205—` 26x20E 26414E 22x14E UP TO HV -20 W/ TURN VANES no DN (TYP2 BEAD BLAST 160 700 CFM <11 12x SE 14/ TURN TO TO 6X20 UP V-6 MILLWRIGHT 104 0 CORRIDOR 20x 12S2 CLEANING ROOM NI —12 26x12S 26x18S DISMANTELING Al/EA DM [22x10E 14x38S W/ TURNING VANES UP, TRANS TO 20X26 UP TO HV -6 1802 00 I CFM 15x15 945 CFM (TYP 7) —12 9-3 16x12S 11( 22x20E ER -1 600 CFM (TYP 2) 38x164 -- 10 x2OS 3 x 1Y4 TECH TEE 22x17E —DUSTING 3' WAIN LARGE UNIT STORAGE 16x12S DYNORM 30x30E EG -1 UP TO F-15 -= 6720 DN REPLACE EXISTING PANTED UPRIGHTS WITH NEW UPRIGHTS 32x20E N A f eh I 1 H2.r2T Ruv24 A ,xRX: 4:424 as4I r E4E GT 01. tU:PA NTWEO/s • 16x12S 35x20E 10x22E LIN JANITOR \-42x18E ON AT EXST OPENING W/ FIRE DAMPER DARK ROOM STG firri LEGEND NORTH 3nr“ er Scale: 3/32" = 1'-0" PAINT CLEANUP L 50-1 j 10x10 335 CFM OMPRESSOR BOILER ROOM ) ELECTRICAL Sy bc Lece O Existing Standard Coverage Upright O New Standard Coverage Uprig qt OR Relocate Standard Coverage Jpright 1:1 Mechanical Tee Syrribol — Existing Sprinkler Pipe New Sprinkler Pipe Generc \otds SHIPPING AND RECLEVING DN 22x10E TOL Top Beam Clamp 111, WIDE FLANGE DM BEAM CLAMP W/ RETAINER STRAP AU- THREAD ROD Scale: 0 0 0 er _etc CEP ED Without Comments As Noted In Red Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions b these drawincs afte,r I this date will void this,acceptance and will require a • resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. \ ' ENGINE REBUILD OFF OM TAIR NO5 TESTING TURBO VESaThULE o 10x22E UP 5/8" SUCTION U LEANING CORRIDOR HALL • PARTS STORAGE SR -1 415 CFM SECURE STG SR -1 295 CFM CAP LOBBY EXST EG 275 CFM7 Ox9E 11 Aar - Tiran (TYP 4) ELEVATOR EQUIP !DIETING OVERHEAD SYSTEM RELOCATE AND ADD ANY NECESSARY UPRIGHT SPRINKLERS TO PRIPADE PROPER FEE PROTON DUE TO NEW AND USING WPC EXST GRILLE 140 CFM METING OVERHEAD MEM -- RELOCATE AND ADD ANY NECESSARY 1 UPRGHT SPRINKLERS TO PROVIDE PROPER ERE PROTECTION DUE TO I NEN AND EASRNG HVAC ' 900 CFM 24x8 ID 18x10 560 CPR TUKWILA FIRE UEPAR WENT Please call: 575-4407 and give this job and exact address for shut- down or restoration approval. 1. Western States Fire 4)rotection to add new upright sprinklers and relocate any existing sprinklers due to new and existing HVAC ducts. Sprinklers shall be spaced in accordance to NFPA #13 Ordinary Hazard Group 1 Occupancy with a 15 maximum distance per sprinkler with a maximum coverage area of 130 sq. ft. 2. The building is constructed with combustible materials and qualifies as unobstructed construct,ion. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer s specifications. 4. Branchline and arm—over pipe is black Schedule 40 pipe. 5. All new threaded fittings are ductile iron class 150. 6. The owner is responcsilDle for all appropriate maintenance of sprinkler system in accordance with 7. The owner is responsible for th? freeze protection of all sprinkler system piping and components that are not designOd for freezing conditions. 8. Fitter to fiPld verify evistina con-lit;nrs CFYF 5) PARTS STORAGE - 18x14S 1 x10E DN OFFICE OFFICE OFFICE LIFITBY EFEI 12 14-S Area of Work 750 CFM 1425 CEM OFFICE OFFICE STAIR NO1 REVISIONS SPRINKLER SPECIFICATIONS SPRINKLER SPECIFICATIONS NUMBER DESCRIPTION DATE SYMBOL DESCRIPTION ORIF. TEMP. FINISH SYMBOL DESCRIPTION ORIF. TEMP. FINISH QTY. APPROVAL(S) City of Tukwila 0 Viking Model M Standard Coverage Upright 1/2" 165' Brass 6 LICENSE NUMBER Viking Model M Standard Coverage Upright 1/2" 220' Brass 13 JOB NUMBER 252319 Reliable Model G Pendent Sprinkler 1/2" 165' Chr 2 DESIGNED BY M. AGNER NEW SPRK ON PLAN 21 NEW SPRK ON JOB 21 DATE 4-29-04 Western Stctes Fire Protection 7102 18Cth Avenue \E Suite A-105 edrrionc, Washincton 98:52 Phone: 425-881-0100 FOX: 425-881-3030 Vetro Trusit Divisio <inc: County Department of Transportation 12200 East Varcinal Way South Seattle, Washincton APR 3 0 Z004 SHEET T 01 < L-1:;;;;> WY PAINT BOOTH VESTIBULE PAINT SHOP 013 033 0112 LEGEND NORTH 3nr“ er Scale: 3/32" = 1'-0" PAINT CLEANUP L 50-1 j 10x10 335 CFM OMPRESSOR BOILER ROOM ) ELECTRICAL Sy bc Lece O Existing Standard Coverage Upright O New Standard Coverage Uprig qt OR Relocate Standard Coverage Jpright 1:1 Mechanical Tee Syrribol — Existing Sprinkler Pipe New Sprinkler Pipe Generc \otds SHIPPING AND RECLEVING DN 22x10E TOL Top Beam Clamp 111, WIDE FLANGE DM BEAM CLAMP W/ RETAINER STRAP AU- THREAD ROD Scale: 0 0 0 er _etc CEP ED Without Comments As Noted In Red Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions b these drawincs afte,r I this date will void this,acceptance and will require a • resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. \ ' ENGINE REBUILD OFF OM TAIR NO5 TESTING TURBO VESaThULE o 10x22E UP 5/8" SUCTION U LEANING CORRIDOR HALL • PARTS STORAGE SR -1 415 CFM SECURE STG SR -1 295 CFM CAP LOBBY EXST EG 275 CFM7 Ox9E 11 Aar - Tiran (TYP 4) ELEVATOR EQUIP !DIETING OVERHEAD SYSTEM RELOCATE AND ADD ANY NECESSARY UPRIGHT SPRINKLERS TO PRIPADE PROPER FEE PROTON DUE TO NEW AND USING WPC EXST GRILLE 140 CFM METING OVERHEAD MEM -- RELOCATE AND ADD ANY NECESSARY 1 UPRGHT SPRINKLERS TO PROVIDE PROPER ERE PROTECTION DUE TO I NEN AND EASRNG HVAC ' 900 CFM 24x8 ID 18x10 560 CPR TUKWILA FIRE UEPAR WENT Please call: 575-4407 and give this job and exact address for shut- down or restoration approval. 1. Western States Fire 4)rotection to add new upright sprinklers and relocate any existing sprinklers due to new and existing HVAC ducts. Sprinklers shall be spaced in accordance to NFPA #13 Ordinary Hazard Group 1 Occupancy with a 15 maximum distance per sprinkler with a maximum coverage area of 130 sq. ft. 2. The building is constructed with combustible materials and qualifies as unobstructed construct,ion. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer s specifications. 4. Branchline and arm—over pipe is black Schedule 40 pipe. 5. All new threaded fittings are ductile iron class 150. 6. The owner is responcsilDle for all appropriate maintenance of sprinkler system in accordance with 7. The owner is responsible for th? freeze protection of all sprinkler system piping and components that are not designOd for freezing conditions. 8. Fitter to fiPld verify evistina con-lit;nrs CFYF 5) PARTS STORAGE - 18x14S 1 x10E DN OFFICE OFFICE OFFICE LIFITBY EFEI 12 14-S Area of Work 750 CFM 1425 CEM OFFICE OFFICE STAIR NO1 REVISIONS SPRINKLER SPECIFICATIONS SPRINKLER SPECIFICATIONS NUMBER DESCRIPTION DATE SYMBOL DESCRIPTION ORIF. TEMP. FINISH SYMBOL DESCRIPTION ORIF. TEMP. FINISH QTY. APPROVAL(S) City of Tukwila 0 Viking Model M Standard Coverage Upright 1/2" 165' Brass 6 LICENSE NUMBER Viking Model M Standard Coverage Upright 1/2" 220' Brass 13 JOB NUMBER 252319 Reliable Model G Pendent Sprinkler 1/2" 165' Chr 2 DESIGNED BY M. AGNER NEW SPRK ON PLAN 21 NEW SPRK ON JOB 21 DATE 4-29-04 Western Stctes Fire Protection 7102 18Cth Avenue \E Suite A-105 edrrionc, Washincton 98:52 Phone: 425-881-0100 FOX: 425-881-3030 Vetro Trusit Divisio <inc: County Department of Transportation 12200 East Varcinal Way South Seattle, Washincton APR 3 0 Z004 SHEET T 01 Generc \otes 1.AII materals used on this project shall be UL Listed and/or FM Approved. QII materials shall be installed in accordance with NFPA, state 8c local codes, & manufacturers specifications. For a description of all material used on this project, see the Product Descriptive Data submitted separately. 2. All portions of thesprinkler system shall be able to drain in accordance with NFA. 3.AII ranger assemblies shall be installed in accordance with NFPA & manufacturgr s specifications. All hanger assembliesshall be spaced in accordance with NFPA & manufacturer s specifications. 4. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state 8c local codes. 5.The owner is responsible for the freeze ,protection of all sprinkler system piping and components that are not designed for freezing conditions. 6.The owner is responsible for all monitoring of the sprinkler system in accordance with state & local codes. 7.Add pendent sprinklers due to new ceiling at 14'-0" AFF. Pendent sprinklers shall be spaced based on the existing overhead system. Ordinary Hazard Group 2 with a maximum head spacing of 15' on center with a maximum of 130 square feet per sprinkler. MB PAINT BOOTH 1 142 1 CL EL 19'-0 AFF 01 1 1_.1/9 'CUT IN E 1/4 x 1 MT :417 L.L/' \-•1E1/2 x 1 MT� 0 Hcip L1/2 t_11-21 1I 11%2x1 MT :�►/►41 t►• ►•1►1►t►fit► ♦1O'.PA1T t►•t►••►•••4I►4 PREPARATI ON O►�4►fit►.•.4►4►: NI • � 1 — /4A, n o _J � i 1 =o f at oVA•• � A 1/2 �I. i ik 0c 14�-0° �I � 1 2 1 1/21/2 2 41/2 41 _ _1 r . .i NM r --e- 1. `may v ♦ 7 A '41 ..... 10- 1 1/4 «, 1 1/4 / 1/2 1/2 2 4_4 1 1/2e 1 1 1/2471 --� �lo �lo SrinK er Scale: 1/8' = 1'-0" 3 C ACCEPTED Without Comments ❑ As Noted In Red ❑ Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings after this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: i(D3% /b 3 By: 1 CL EL 20'-4 AFF 1/4 .\ 1 1/4 CL EL 20'-4 AFF 6" iEJ /4 ,\ 1 1/4 `CL EL 20'-4 AFF E TUKWILA FIRE DEPARTMENT. Please call: 575.4402 and give this job No. O3—\c— is)] and exact address for shut, dawn or restoration approval. d Sprinkler Symbol Legend d Existing Upright Sprinkler. o New Pendent Sprinkler Symbol. See individual sheets for sprinkler legend. o Mechanical Tee used for additional outlet. ---- Existing Fire Sprinkler Pipe 2- Sprinkler Pipe with pipe size and pipe length. 3 -8 Riser Nipple. — - Rise or Drop in Piping. 7'-8' AFF Pipe Elevation Tag with Above Finish Floor elevations. TOP BEAM CLAMP Hcncer Dctc Scale: Not to Scale /AREA OF WORK S Key 9Icn Scale: Not to Scale LEGEND NORTH REVISIONS SPRINKLER SPECIFICATIONS SPRINKLER SPECIFICATIONS NUMBER DESCRIPTION DATE SYMBOL DESCRIPTION ORIF. TEMP. FINISH QTY. SYMBOL DESCRIPTION ORIF. TEMP. FINISH QTY. APPROVAL(S) City of Tukwila Submittal Plan 10-22-03 Viking Model M Quick Response Standard Coverage Pendent Sprinkler 1/" 155' Chr 18 LICENSE NUMBER WESTESF136QF JOB NUMBER 252319 DESIGNED BY M. AGNER NEW SPRK ON PLAN 18 NEW SPRK ON JOB 18 Total 28 DATE 10-22-03 Western Stctes Fire protection 7102 180th Avenue \E Suite A-105 ednond, Washington 58052 Phone: 425-98I-0100 Fax: 425-88I-1070 V etro Trcnslt Division Kine County Department of Transportation 12200 East Varginal Way South Seattle, Washincton OCT 3 0 2003 2z7(p d /dr SHEET FP -01 OF 1