HomeMy WebLinkAboutPP - 15425 53RD AVE S - SMILES AT SOUTHCENTER - PERMITS AND PLANS15425 53RD AVE S ASSOCIATED PERMITS D08-349 D08-067 D08-064 M08-156 PW08-038 08-F-432 08-S-366 08-S-360 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Smiles @ Southcenter 15425 53rd Ave. S.. Permit No.: 08-S366 Date: July 8, 2008 Reviewer: Steve Kohler Fire Prevention Inspector/planreview (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ` of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All references are NFPA 13, 2007 Edition. 5 INSPECTION RECORD Retain a copy with permit <c INSPECTION NUMBER : o') PERMIT NUMBERS Do8- CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East, Tukwila. Wa. 98188 206-575-4407 Project: 5,.,4; le_ g S wtri Type of Inspection: 7�—Fr. J Hrs.: Address: / SL/ ZS Suite #: 5-3 A V, 5 Contact Person: TEr-c Special Instructions: Phone No.: 12S'- 41Y!-- c-pi1y, pproved per applicable codes. nCorrections required prior to approval. COMMENTS: Needs Shift Inspection: S wtri Sprinklers:/ Hrs.: Fire Alarm: / Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: S wtri Date: /aV.2.3ipcp Hrs.: / $80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. Call to schedule a reinspection. Word/Inspection Record Form.Doc 1/13/06 T.F.D. Form F.P. 113 INSPECTION NUMBER INSPECTION RECORD Retain a copy with permit Doi-oG� PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East, Tukwila, Wa. 98188 206-575-4407 Project: �", , j-Jc s Sprinklers: Type of Inspection: sipr,-n iL%A- h' / Address: /Sties Suite #: 53 Av. 5. Contact Person: <YEW Special Instructions: Occupancy Type: Phone No.: y--17y1—eiy/y 1-9/Approved per applicable codes. Corrections required prior to approval. COMMENTS: p / C44 -1p Gam' . Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: sh.,(3--js--- Date: JG/ / r Hrs.: / $80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from he City of Tukwila Finance Department. Call to schedule a reinspection. Word/Inspection Record Form.Doc 1/13/06 T.F.D. Form F.P. 113 3 INSPECTION NUMBER INSPECTION RECORD V• Dog - oG,� Retain a copy with permit PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East, Tukwila, Wa. 98188 206-575-4407 Project: Sola s 6—, �,44.c,,1,,_.1cy 1/sit-,25 ,,-a I Type of Inspection: J j I A ,-72_ Ar/ -C/'Gj 1 1 c,/ b1 z� Address: /5y25 Suite #: 53 ,V • S, , Contact Person:/ 57c: Ffi- Special Instructions: /Needs Pre -Fire: Phone No.: y2.- 141414– lciiy Approved per applicable codes. Corrections required prior to approval. COMMENTS: 6—, �,44.c,,1,,_.1cy 1/sit-,25 ,,-a I Pass -z-___. !/c/6 a- Fire Alarm: Hood & Duct: Monitor: /Needs Pre -Fire: / Permits: Occupancy Type: Shift Inspection: 6—, Sprinklers: Hrs.: Fire Alarm: Hood & Duct: Monitor: /Needs Pre -Fire: / Permits: Occupancy Type: Inspector: 56,✓ 6—, Date: l6/G/G,p Hrs.: / $80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from City of Tukwila Finance Department. Call to schedule a reinspection. Word/Inspection Record Form.Doc 1/13/06 T.F.D. Form F.P. 113 2 INSPECTION NUMBER SEP 2 6 2008 INSPECTION RECORD ),00 8'— OG 7 Retain a copy withrmit o ) rote'— /6 ( PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East, Tukwila, Wa. 98188 206-575-4407 Project: 4,y•; J.Gs Sprinklers: Fire Alarm: Type of Inspection: S4si[€ Sk., I ✓Jvwn Address: /3" 1 Suite #: vii 41/• 5 • Contact Person: Special Instructions: Phone No.: ['Approved per applicable codes. Corrections required prior to approval. COMMENTS: I'Ve 17.e4 c&1 ,rn v /4- $) J PO4,4 ,, Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: Sc,, (Jr Date: g/ZK/Or Hrs.: / $80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from e City of Tukwila Finance Department. Call to schedule a reinspection. Word/Inspection Record Form.Doc 1/13/06 T.F.D. Form F.P. 113 BUSINESS NAME: ADDRESS: TUKWILA FIRE DEPARTMENT FIRE PREVENTION BUREAU (206) 575-4407 CORRECTION NOTICE/REINSPECTION FEE 5*? ; I c s DATE: 9 119 far /s'1 z 5 $3 .4v. S_ BLDG: SUITE: ) "L/ APT: TYPE OF INSPECTION:hir. CONTACT PERSON: &a/atm INSPECTOR: a r BLDG. PERMIT #: 0 PHONE:Y2$7-YYY' rt/50 ACTION REQUIRED: a gpifr {eat 0 Acid Hare) S7a..6, 44- rrsOw/ °Doi.L 4.5 .d re ate' e4 f K opt 4-Ar, ioo ~i 5.�� e.Ac a -1= y 3z illcrtgCo (X 1- 1 1 0 21S�.p1) 1' *7 44-4 VI) ..., i4 j+c/ L Jerks-L. ie.,.,, PI - CORRECTION %) A $80.00 Finance FAILURE TO OF THE ABOVE ITEMS ARE REQUIRED BY: 7 ale/14,s l --za' Reinspection Fee is required. You will receive an invoice from the City of Tukwila Department. COMPLY may result in the issuance of a criminal citation. , Correction Notice Reinspec Fee W -Office Y -File P -Contractor Revised 1/13/06 T.F.D. Form F.P. 100 2 INSPECTION NUMBER INSPECTION RECORD Retain a copy wit, it SEP 2 2 2008 OP.F• °!32 'wog- o 3 , PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East, Tukwila, Wa. 98188 206-575-4407 Project: 5,,„; jos Sprinklers:/ Type of Inspection: ill 'ev'4j4'yy1 gr,..) Address: /SW L5 Suite #: t3 Av. s Contact Person: F1 Special Instructions: 1. Phone No.: 11z6s— liyL - PIA, VI/Approved per applicable codes. Corrections required prior to approval. COMMENTS: Sprinklers:/ Date: Fire Alarm: Hood & Duct: 2. Monitor: 1. Horn /S?a.Jvts cd GvC. Permits: 2 / Proms Ob me 3 . 34a.e ..mss YsN3 2Y., Y. Vqk.j4 J'Miri.a.ril.•S s•. en at DX L, -Ae.- v ZY. 7 C PAsi it.4 Trvvb 1` /3. .,,i 0 astis Ai • c< 7. ?'re.4,1.L i4 I.4.1.06i Xer.07 rJ. • 1 Lfi arc. d. nil el;bLJ )ti .i -m o .�/ .X. 7. isegXG c / fi..- iw ftiC4 we. /o. S,•lx/��rd o?P fk)cot-4•38. &At ms.4 /1. Pit R'rtr L�v.&e%ukC • Needs Shift Inspection: Sprinklers:/ Date: Fire Alarm: Hood & Duct: 2. Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: SW 535 Date: 9//4/•$, Hrs.: 2. 4114r$80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from he City of Tukwila Finance Department. CaII to schedule a reinspection. Word/Inspection Record Form.Doc 1/13/06 T.F.D. Form F.P. 113 3 INSPECTION NUMBER INSPECTION RECORD Retain a copy with permit pas -�y9 d6 -s-344. PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East, Tukwila, Wa. 98188 206-575-4407 Project: ,s,,,,,i,t.e‘s Sprinklers: Fire Alarm: Hood & Duct: Type of Ins ection: kI 0t C' Address: 45 if ZS Suite #: 5 3 AI/ 5. Contact P rson: Special Instructions: Phone No.: riApproved per applicable codes. Corrections required prior to approval. COMMENTS: irisfolco- c 12-oo c Z35 76. CND a / (bV c Z/°° h416eo 61(-- Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: ns I_ • Ir: �. n%u.� S 1 Z- Date: $%Z2 /D� Hrs.: Z_ $50.00 REINSPECTION FEE REQUIRED. You will receive an invoice from City of Tukwila Finance Department. Call to schedule a reinspection. Word/Inspection Record Form.Doc 1/13/06 T.F.D. Form F.P. 113 2 INSPECTION NUMBER INSPECTION RECORD Retain a copy with permit t .DP8' 3Y 9 C28- S 34.G PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East, Tukwila1 Wa. 98188 206-575-4407 Project: 5,moi' lis Sprinklers:/ f)3 Type of Inspection: Pav4,10 C //l. tIas Sez- pf ,,,3 Address: istrz.f' Suite #: 5'3 ori. s. Contact Person: ,Ocn•2; 3 So, ,4-14 Special Instructions: Phone No.: .25.2- 6'33 — )Zcfk proved per applicable codes. Corrections required prior to approval. COMMENTS: D 10 Cb✓Gn/ M4/1‘) 1 [ 3 ! j iii cel a )1294.e4 Needs Shift Inspection: Sprinklers:/ f)3 Fire Alarm: Hood & Duct: Hrs.: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: SW f)3 Date: VZ31vi Hrs.: $80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. Call to schedule a reinspection. Word/Inspection Record Form.Doc 1/13/06 T.F.D. Form F.P. 113 INSPECTION NUMBER INSPECTION RECORD Retain a copy with permit 051- .J- 3 GC PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East, Tukwila, Wa. 98188 206-575-4407 Project: .',,,,%S Sprinklers: Fire Alarm: Type of Inspection: _ Si%NLetrw- ..Ai cit .--d, Address: /51i25' Suite #: 57,3 20, - Contact Person: G„a, )41,74.— Special Instructions: Phone No.: ,2333- k33— /2y9 Approved per applicable codes. corrections required prior to approval. COMMENTS: Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: jt,, ,55--- Date: 7�j34i Hrs.: $80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from h City of Tukwila Finance Department. Call to schedule a reinspection. Word/Inspection Record Form.Doc 1/13/06 T.F.D. Form F.P. 113 444 Andover Park East, Tukwila, WA 98188 - Phone 206-575-4407 - Fax 206-575-4439 E-mail: tukfdpry@ci.tukwila.wa.us. . CONTRACTORS M.A:TERXA.L AND TEST CERTIFICATE • FIRE ALARM AND FIRE DETECTION SYSTEMS Fire alarm System is ready for Fire Department acceptance testing. Failure of test will result in termination of the testing and additional fees will be assessed. Contractor is responsible for supplying manpower for Final Acceptance Test with two-way communications. • • Date ' �"i I !clic, 6 Permit # Property Address.Suite # City Tukwila Zip Code Name of Facility Sv • r_l_pr-L — l G� Occupied as Owner or Representative Phone # .Installing Company .t,r. C,p v� Instilling Contractor's Address City Phone # Installer's Name (PRINT) Ie%"-CkI47-e__ Kf:elr- License and/or Certificate General Contractor t.%) yo„ 1A6.e.e1", Electrical Contractor FACP Equipment Manufacturer , 4 Model # ? 00 This system has beet jzistalled, pre -tested and operates in accordance with the standards listed below and was inspected by 1—, t £_ On (date) . Circle all that apply: NFPA 72, Chapter 1 2 4 5 6 7 and/or IFC SEC 907 }C NFPA 70, National Electrical Code, Article 760 Manufacturer's Instructions Manufacturer's Instructions Other (specify) Tukwila City Ordinance Numbers 2050, 2051 UL Central Sta on onit r '7 572 L 17 / / System is monitored by SIGNED Date and includes the devices listed on back. System Firmware: Installed version • Initial program Checksum Date EQUIPMENT INSTALLED AND TESTED: Control Panel of Manual Station L of r - Smoke Detectors of Heat Detectors — of Duct Detectors. of ATV Devices ± of Audio Devices of Visual Devices of 2, Auto Door Release of Trouble Indictors of Batteries • Readings Battery 27.3 Full Load r b Charge 2`7 t •Make/Model Make/Model Make/Model' Make/Model Make/Model Make/Model • Make/Model Make/Model 6,e Make/Model Make/Model Generator of HVAC Controls of Fire Alarm Dialer of Monitored by A-( w. Annunciator of Make/Model Make/Model 1I _ Make/Model tckee-1 -7c-7Z Make/Model ❑ Sprinkler System. (Fire Alarm connections only) Water Flow Sw. l of ( Make/Model 4,0 11�� Valve Tamper Sw. "2 of Make/Model >d ft r/ PIV of ( Make/Model 1�a`�r Elec. Alarm.B ell of • Make/Model Automatic time Delay of Water Flow Alarm d seconds. None Installed Do you meet audible/visible requirements of WAC51-20; IFC SEC 907., and/or NFPA 72 Chapter 6? Yes X. No Test of alarm System on emergency power, satisfactory? YesiC No _ Test Witnessed by Title Date Comments: WASHINGTON SURVEYING & RATING BUREAU 2101 4th Avenue Suite 300 Seattle, WA 98121 P 206.217.9772 F 206.217.9329 www.wsrb.com Underwriting Information, Filings & Property Loss Costs Jose A. Buitrago Senior Field Representative/ Pian Review jose.buitrago©wsrb.com 206.273.7157 July 2, 2008 PLAN SHEETS 1 of 1 SUBJECT Smiles @ Southcenter 15425 — 53"1 Ave. South Tukwila, Washington The attached plans have been reviewed as follows: The following revisions or additions to the design as shown would qualify the protection for improved rates based upon information shown on these plans. Completed copies of the Contractor's Material and Test Certificates for both the overhead and underground piping should be submitted to this Bureau, including tests of the local alarm and main water supply test pipe (2 -inch). All piping, valves, and fittings should be listed and labeled by UL for fire service and installed, tested, and flushed in accordance with NFPA standards. A minimum temperature of 40°F must be maintained with a thermostatically controlled heating system in all areas containing wet pipe sprinkler equipment. 1. Hangers should be installed according to UL listing and as specified by NFPA 13. 2. Extend sprinkler protection to all areas including exterior eaves, soffits, canopies, combustible blind and roof spaces, and to roof skylights. 3N gpk, n rDa�ual In ue wd l stry Since 1911 ,a4 Serving the P ty q PO Box 3932 Seattle WA 98124-3932 206-234-5700 Tel 253-517-5775 Fax Fire Com NW, Inc. Battery Calculation Work Sheet Project: Smiles @ Southcenter Fire Alarm System Project 15425 — 53`d Avenue South Tukwila WA 98188 This project consists of a tenant improvement to an existing space in the building. The building is fully sprinklered. This worksheet is for the fire alarm control panel and the connected devices. Qty Part # and description Supervised Current mA Alarm Current mA 1 5700 Silent Knight FACP 200 325 1 SD505-APS Add smoke det 0.55 0.55 4 SD500 —PS Add pull stations 2.20 2.20 5 SD500-AIM Add input mod 2.75 2.75 4 GEC3 Horn strobes wall mt 0 548 12 GESS Strobes wall mt 0 660 Subtotal 206 1538 Total battery power hours x24 x.083 Subtotal 4944 128 Safety factor -10% +494 + 13 Total 5438 ma 141 ma Total Current Required 5579 ma or 5.6 amps Battery size used: 2ea- 12volt, 7amp PAID -A•• AUG 2 5 2008 h ukwila Fire 25s X77/ 06/25/2008 09:25 FAX 2537350113 FIRE SYSTEMS WEST Z001 Ore Systems Wesi"Inc. 219 Frontage Road North, Suite B • Pacific, Washington 98047-1023 • Phone (253)833-1248 • Fax (253 735-0113 6/25/08 Tukwila Fire Department 444 Andover Park East Tukwila, WA 98138 Attn: Lt. Don Tumaso Fax # (206) 575-4439 Re: Smiles @ Southcenter — Demo. FSW Job No. 2-11-10077 15 T _ S 5 3 46>. Dear Lt. Tumaso FSW is requesting a Tukwila shutdown number in order to demo some sprinkler drops and an existing fire hose cabinet in the way of wall framing. FSW is preparing drawings for plan review at this time. am Ruark Project ManagenDesigner Fire Systems West, Inc. l I UKWILA FIRE DEF'Arc 1 mast Please call: 575-4407, and give this ,job and exact address for shut. Immo or rest:,ratiion approval A D AA j EXISTING(--=3 AM b Q SPRINKLERA —d A o—A AM A—o 126 curwFE,e A u eE P5 OP 6 116 STAFF ENTRY 3 P7 OP 8 118 A IJ OP 4 114 APE, B B b OP 3 113 LIBRARY 102 OP 2 112 WOMEN'S RR 103 0, hi 1171 HA AY TO FACP A LO B NGE 1123 F B 111 /E LAB 120 0 MEENN'S 121 if " D ELECTP NEL B b PAN CBPH 110 '—B CLOSET 109 B 6 STAFF 122 Orws )FFIC 108 B CLE:MTFIC.F,I L� J STAFF ENTRY 2 (EXISTING) A U B b RECEPTION 101 CHECKOUT los C9NSULT 107 A A RE U SKIN 104 1, w 3 ADD 1 LAYER OF ave TO EKE SURFACE BUSINESS 106 STAFF ENTRY 1 (EXISTING) FIRE ALARM PLAN SCALE: 1/8"s1'-0" 0 1 2 4 8 16 FIRST FLOOR TO 120 VAC UNBIMTCFED DEDICATED CIRCUIT TO TELCO ROOM FIRE ALARM RISER DIAGRAM SCALL: NONE EQUIPMENT LEGEND MBE QUANTITY PART NUM" 001101PT $ 840308 ® 1 5700 FIRE ALARM CONTROL PANEL INCLUDED I© 4 50500 -PS MANUAL PULL STATION SRIO)F GNIG m 1 S050S-APS SMOKE DETECTOR 4 SQUARE X 1-7/r DEEP ®0 4 0E03 HORN STROBE 4 SQUARE P 1-7/s' Da ® 12 0883 STROBE 4 50UAEX1-7/r ® 3 50500-59A ADDRESSABLE INPUT MODULE 4 80U/ OECX 1-7/86 OE 2 -- DUCT DETECTOR (0) PROVIDED BY OTHERS © 2 -- TAMPER SMAICN (A) PROVIDED BY OTHERS ® 1 -- WATER -FLOW PATCH (0) PROVIDED BY owns (0) - PROVIDED AND NSTAU.EO BY OTHERS WIRE LEGEND MBE DISCI P110N A 18 AVO, 2 CONDUCTOR 'PPCF JACKETED CABLE 5 14 AWA 2 CONDUCTOR 'FPLP' JACKETED CABLE c is AWA 4 CONDUCTOR 'FPL, JACKETED CABLE GENERAL NOTES: 1. ALL WORK IS TO CONFORM TO NATIONAL ELECTRIC CODE STANDARDS. 2. WIRING METHOD IS TO BE OPEN CABLING EXCEPT WHERE IT IS EXPOSED AND BELON SEVEN FEET • THEN R 1S TO BE IN CONDUIT. 3. ALL JUNCTION BOXES, CODERS, AND BACK BOXES ARE TO BE PANTED RED. 4. PULL STATIONS ARE TO BE MOUNTED AT 48' TO 53 ABOVE THE FLOOR. 5. ALL WALL MOUNT 84 DOOR HORNS, STROBES, HORN STROBES, AND SPEAKER STROBES ARE TO BE MOUNTED 80' ABODE THE FLOOR OR 8• BELOW THE CEING, NNICHEVER IS LOWER. 8. SMOKE DETECTORS SHALL BE INSTALLED N ACCORDANCE WITH THE FOLLOWING: A) 38' INCHES AWAY FROM ANY AIR HANDLING SYSTEM DIFFUSER 9) NOT N CLOSE PROXIMITY TO ANY FLUORESCENT LIGHT FIXTURES 7. EXTERIOR HORN / STROBE SHALL BE MOUNTED ON THE TOP 2/3 OF THE OUTSIDE WALL OF THE BUILDING, AS HIGH AS POSSIBLE FOR MAXIMUM VISIBILITY FROM THE FIRE DEPARTMENT ACCESS ROADWAY. S. ALL WIRING PENETRATNOANY FIRE RATED BARRIER SHALL BE SEALED WITH MATERIAL WHICH WILL PREVENT PASSAGE Of FLAME AND HOT GASES. FIRE COM NW PO sox 3932 Seatt. WA 981243832 208-2344700 DATE: 8/22/08 DRAWN: CEA CHECKED: JD APPROVED BY: JD SCALD 1/8"=1'-0" N0. DATE REVISION BY PROJECT NAME SMILES E2 SOUTHCENTER 15425 53rd Avenue S. Tuklwile, WA 98188 Mir WILE: FIRE ALARM PLAN JOS NUMBER: 08- FA -1 O( / fog >.. sta ' `.-,,-... Addie::: this date resubmittal of re.;:_:..„ : 441I•Mr,maa Aft i 1 1 Final acceptance is subject 10 b` The Tukwila Fire Prevention Bureau. 1 Date: a, OBy: NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection System-. Failure of test will resu. in a Re -inspection Fee termination of the te' ri. ANT NOTICE Because of fr1.7.1-FaF-t-1 demand our inspectors e,re booked 3-7 days ahhea:i. Ii:�:,-efore, you will need to call 206-575-4407 to schedule your inspections a minimum of 48 hours in advance of the date you want an inspection. —�'4.341 fl re ,„v -j e L. & D. s - o►- 46o ve- Ce, f, hg ANA- die+ vc-IO rS '-' Ihs-1-41( /0 G GC o of t u i Ce b h d edi i Cw 1A.ci f�4 Gi rc, ;`-- %vewkit^. A -a d re -5 s o, s repoC6„r6w t S t-r-v-4?oti 1‘1-04--w 6 l 4 kwo c O o y. rufkwILA FIRE DEPARTMEN Pease call: 575-440Z and give this job No.Of j cxa�t adiress for shut. .;n or rQ_taration aonrrwml: FILE COPY LA e -P., E2`( R-EGei pESI� _ 10`-0' , Weld stamps must be inspected before pipe is hung. D0 not paint piping. prior to hydrostatic test �I .�'�;`i 1. CCEPTE Without Comments AsNoted lnRed Per The Attached Letter I hese plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted stemmas and orcunances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings atter this date will void thie.acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire, Prevention Bure Date, •► 0 By: '2 9 0. ( o -0 0 A 2" WOOD NAILER SIDEWINDER! HANGER MATE - 3/8" ALL THREAD ROD RING HANGER Lc) U ki6a D2. oiIGI✓ 5XNc, UP121&1PITS To �EMAI14 •Ay 'Zoo F THLrr, 12.EL.ocPcTE EX I4-rI NICD 1" E7I2.c)P IAdJ r7 PE1-I D L -h GATT o I4 , P--EPL.A C -e EX I STl til ( PERI 17 04-- P P 1,1 Ie-L-EIz-S w rrkF-- OPEN WEB JOIST (4" AND SMALLER PIPE) I HANGER JW SIDEWINDER (WOOD) _VICINITY -FL TENANT IMPROVEMENT THIS PROJECT ISA TENANT IMPROVEMENT. THIS FACILITY HAS ALREADY BEEN PROTECTED BY A FIRE SPRINKLER SYSTEM. FIRE SYSTEMS WEST IS ADDING AND/OR RELOCATING SPRINKLER HEADS TO ACCOMMODATE THE NEW TENANT WALL, CEILING, LIGHTING AND HVAC LAYOUT. ALL WORK WILL BE DONE WITHOUT AFFECTING THE CAPABILITY OF THE EXISTING SYSTEM. HANGER LEGEND 'U" H00I< COACH SCREW ROD 'C' CLAMP D TOP BEAM CLAMP W/ STRAP EYE ROD FLUSH SHELL CEILING FLANGE SIDE BEAM BRACKET • Ell0 CI 'L" ROD SYMBOL LEGEND IuKWILA FIRE. UENAKIiW hair Please call: 575.4407 and give this job No, S and exact address for shut. lawn or restoration approvaj, CONTRACT NAME: R - DENOTES A SPRINKLER HEAD TO BE . RELOCATED. A = DENOTES A SPRINKLER HEAD TO BE ADDED. '-' — - REPRESENTS EXISTING SPRINKLER PIPE. - REPRESENTS NEW SPRINKLER PIPE. SPRINKLER LEGEND SPRINKLER HEADS MACHINE THREADED ROD TOGGLE NUT POWDER DRIVEN STUD V,'EDGE ANCHOR SPKR THRDS. SPRINKLER ORIFICE SIZES AND TYPE UPRIGHT PEND. TEE SIZE SPRINKLERS UP AND DOWN SYMBOL TYPE REVISIONS 0 5N r7 kI1 MFG TYco MODEL T`r--23 SIZE I/Z" 1/2' 3/4' 1/2' 1' 5/16' 3/6' 7/16' 1/2' SPRAY 17/32' SPRAY 3/8' 7/16' 1/2' SSDEWALL 1/2' DRY TWE O O 1/2' OPEN'G UP SYMBOL OPEN'G DOWN TEMP. 155° ©R. FINISH GHI2OME CANOPY I2EL, CI -1 2 QUANTITY Sg DATE O 1' 1/2' 1' 0 0 3/4' 1' 1/2' El 1' 1' 1' 1/2' d 1' 1' 1/2' TEMP RATING 1/2' -e- 200' 286.' 350' BY ■ ■ DESCRIPTION APPROVALS REQUIRED 6.1TY oF- ru1=-VuILA ow NE--/Al2-cH. VI''R TOTAL THIS SHEET 58 DISTRIBUTION r t,t% TOTAL Ea GENERAL NOTES 1. ALL MATERIAL AND EQUIPMENT TO BE NEW AND UNDERWRITERS APPROVED. 2. PIPING DIMENSIONS ARE CENTER 10 CENTER EXCEPT RISER & DIMENSIONS SHOWN THUSLY (1-6) WHICH ARE END 10 END. 3. EARTHQUAKE BRACING SHALL BE PROVIDED IN ACCORDANCE WITH NFPA PAMPHLET NO. 13. 4. PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13. :5. PIPING SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13. 6. JOINING OF PIPE AND FITTINGS, THREADED AND WELDED SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13. 7. OWNER TO PROVIDE ADEQUATE HEAT TO PREVENT WATER IN PIPES FROM FREEZING IN AREAS PROTECTED BY A WET PIPE SPRINKLER SYSTEM. 8. STRUCTURAL ADEQUACY OF THE BUILDING TO SUPPORT THE SPRINKLER PIPING IS THE RESPONSIBILITY OF THE OWNER AND/OR HIS STRUCTURAL REPRESENTATIVE. DESIGN CRITERIA AND NOTES PIPIT 51ZE1? ANrc Pte- Ni fA I3, oR_DIHArz-%( I-4AZAgc7 PIPE 4G1-I-G12L)L-E HF�r`IC'I ALL.- A2I -off/ 1 ovEiZ.I'-O", CONTRACT WITH: K,kPISI SISITuimilaFire 4- 7(0593,7 (2-510 I30 LANE NE 1 — KI 12 -K -LAR D, c"1 `b03A- (1-z S-) 82-1- 6zocd) 354- - 52.11 Fire S'ste s Wst 219 Frontage Road North, suite B Pacific, WA 98047 (253) 833-1248 fax: (253) 735-0113 WA CL #FIRESW1 140B1 Q.C. FAB BY: / / DESIGNER JAMES 17 -QA DATE Jz5 o' Q.C. INSTALL BY: / / JOB NO. SHEET 2. -At -100-1—t IoF I TE12-IL� 114: Tn —1 i l'i' II 11 R-EGei pESI� _ 10`-0' , Weld stamps must be inspected before pipe is hung. D0 not paint piping. prior to hydrostatic test �I .�'�;`i 1. CCEPTE Without Comments AsNoted lnRed Per The Attached Letter I hese plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted stemmas and orcunances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings atter this date will void thie.acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire, Prevention Bure Date, •► 0 By: '2 9 0. ( o -0 0 A 2" WOOD NAILER SIDEWINDER! HANGER MATE - 3/8" ALL THREAD ROD RING HANGER Lc) U ki6a D2. oiIGI✓ 5XNc, UP121&1PITS To �EMAI14 •Ay 'Zoo F THLrr, 12.EL.ocPcTE EX I4-rI NICD 1" E7I2.c)P IAdJ r7 PE1-I D L -h GATT o I4 , P--EPL.A C -e EX I STl til ( PERI 17 04-- P P 1,1 Ie-L-EIz-S w rrkF-- OPEN WEB JOIST (4" AND SMALLER PIPE) I HANGER JW SIDEWINDER (WOOD) _VICINITY -FL TENANT IMPROVEMENT THIS PROJECT ISA TENANT IMPROVEMENT. THIS FACILITY HAS ALREADY BEEN PROTECTED BY A FIRE SPRINKLER SYSTEM. FIRE SYSTEMS WEST IS ADDING AND/OR RELOCATING SPRINKLER HEADS TO ACCOMMODATE THE NEW TENANT WALL, CEILING, LIGHTING AND HVAC LAYOUT. ALL WORK WILL BE DONE WITHOUT AFFECTING THE CAPABILITY OF THE EXISTING SYSTEM. HANGER LEGEND 'U" H00I< COACH SCREW ROD 'C' CLAMP D TOP BEAM CLAMP W/ STRAP EYE ROD FLUSH SHELL CEILING FLANGE SIDE BEAM BRACKET • Ell0 CI 'L" ROD SYMBOL LEGEND IuKWILA FIRE. UENAKIiW hair Please call: 575.4407 and give this job No, S and exact address for shut. lawn or restoration approvaj, CONTRACT NAME: R - DENOTES A SPRINKLER HEAD TO BE . RELOCATED. A = DENOTES A SPRINKLER HEAD TO BE ADDED. '-' — - REPRESENTS EXISTING SPRINKLER PIPE. - REPRESENTS NEW SPRINKLER PIPE. SPRINKLER LEGEND SPRINKLER HEADS MACHINE THREADED ROD TOGGLE NUT POWDER DRIVEN STUD V,'EDGE ANCHOR SPKR THRDS. SPRINKLER ORIFICE SIZES AND TYPE UPRIGHT PEND. TEE SIZE SPRINKLERS UP AND DOWN SYMBOL TYPE REVISIONS 0 5N r7 kI1 MFG TYco MODEL T`r--23 SIZE I/Z" 1/2' 3/4' 1/2' 1' 5/16' 3/6' 7/16' 1/2' SPRAY 17/32' SPRAY 3/8' 7/16' 1/2' SSDEWALL 1/2' DRY TWE O O 1/2' OPEN'G UP SYMBOL OPEN'G DOWN TEMP. 155° ©R. FINISH GHI2OME CANOPY I2EL, CI -1 2 QUANTITY Sg DATE O 1' 1/2' 1' 0 0 3/4' 1' 1/2' El 1' 1' 1' 1/2' d 1' 1' 1/2' TEMP RATING 1/2' -e- 200' 286.' 350' BY ■ ■ DESCRIPTION APPROVALS REQUIRED 6.1TY oF- ru1=-VuILA ow NE--/Al2-cH. VI''R TOTAL THIS SHEET 58 DISTRIBUTION r t,t% TOTAL Ea GENERAL NOTES 1. ALL MATERIAL AND EQUIPMENT TO BE NEW AND UNDERWRITERS APPROVED. 2. PIPING DIMENSIONS ARE CENTER 10 CENTER EXCEPT RISER & DIMENSIONS SHOWN THUSLY (1-6) WHICH ARE END 10 END. 3. EARTHQUAKE BRACING SHALL BE PROVIDED IN ACCORDANCE WITH NFPA PAMPHLET NO. 13. 4. PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13. :5. PIPING SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13. 6. JOINING OF PIPE AND FITTINGS, THREADED AND WELDED SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13. 7. OWNER TO PROVIDE ADEQUATE HEAT TO PREVENT WATER IN PIPES FROM FREEZING IN AREAS PROTECTED BY A WET PIPE SPRINKLER SYSTEM. 8. STRUCTURAL ADEQUACY OF THE BUILDING TO SUPPORT THE SPRINKLER PIPING IS THE RESPONSIBILITY OF THE OWNER AND/OR HIS STRUCTURAL REPRESENTATIVE. DESIGN CRITERIA AND NOTES PIPIT 51ZE1? ANrc Pte- Ni fA I3, oR_DIHArz-%( I-4AZAgc7 PIPE 4G1-I-G12L)L-E HF�r`IC'I ALL.- A2I -off/ 1 ovEiZ.I'-O", CONTRACT WITH: K,kPISI SISITuimilaFire 4- 7(0593,7 (2-510 I30 LANE NE 1 — KI 12 -K -LAR D, c"1 `b03A- (1-z S-) 82-1- 6zocd) 354- - 52.11 Fire S'ste s Wst 219 Frontage Road North, suite B Pacific, WA 98047 (253) 833-1248 fax: (253) 735-0113 WA CL #FIRESW1 140B1 Q.C. FAB BY: / / DESIGNER JAMES 17 -QA DATE Jz5 o' Q.C. INSTALL BY: / / JOB NO. SHEET 2. -At -100-1—t IoF I 15425 53RD AVE S ASSOCIATED PERMITS D08-349 D08-067 D08-064 M08-156 PW08-038 08-F-432 08-S-366 08-S-360 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Smiles @ Southcenter 15425 53rd Ave. S.. Permit No.: 08-S366 Date: July 8, 2008 Reviewer: Steve Kohler Fire Prevention Inspector/planreview (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ` of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All references are NFPA 13, 2007 Edition. 5 INSPECTION RECORD Retain a copy with permit <c INSPECTION NUMBER : o') PERMIT NUMBERS Do8- CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East, Tukwila. Wa. 98188 206-575-4407 Project: 5,.,4; le_ g S wtri Type of Inspection: 7�—Fr. J Hrs.: Address: / SL/ ZS Suite #: 5-3 A V, 5 Contact Person: TEr-c Special Instructions: Phone No.: 12S'- 41Y!-- c-pi1y, pproved per applicable codes. nCorrections required prior to approval. COMMENTS: Needs Shift Inspection: S wtri Sprinklers:/ Hrs.: Fire Alarm: / Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: S wtri Date: /aV.2.3ipcp Hrs.: / $80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. Call to schedule a reinspection. Word/Inspection Record Form.Doc 1/13/06 T.F.D. Form F.P. 113 INSPECTION NUMBER INSPECTION RECORD Retain a copy with permit Doi-oG� PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East, Tukwila, Wa. 98188 206-575-4407 Project: �", , j-Jc s Sprinklers: Type of Inspection: sipr,-n iL%A- h' / Address: /Sties Suite #: 53 Av. 5. Contact Person: <YEW Special Instructions: Occupancy Type: Phone No.: y--17y1—eiy/y 1-9/Approved per applicable codes. Corrections required prior to approval. COMMENTS: p / C44 -1p Gam' . Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: sh.,(3--js--- Date: JG/ / r Hrs.: / $80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from he City of Tukwila Finance Department. Call to schedule a reinspection. Word/Inspection Record Form.Doc 1/13/06 T.F.D. Form F.P. 113 3 INSPECTION NUMBER INSPECTION RECORD V• Dog - oG,� Retain a copy with permit PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East, Tukwila, Wa. 98188 206-575-4407 Project: Sola s 6—, �,44.c,,1,,_.1cy 1/sit-,25 ,,-a I Type of Inspection: J j I A ,-72_ Ar/ -C/'Gj 1 1 c,/ b1 z� Address: /5y25 Suite #: 53 ,V • S, , Contact Person:/ 57c: Ffi- Special Instructions: /Needs Pre -Fire: Phone No.: y2.- 141414– lciiy Approved per applicable codes. Corrections required prior to approval. COMMENTS: 6—, �,44.c,,1,,_.1cy 1/sit-,25 ,,-a I Pass -z-___. !/c/6 a- Fire Alarm: Hood & Duct: Monitor: /Needs Pre -Fire: / Permits: Occupancy Type: Shift Inspection: 6—, Sprinklers: Hrs.: Fire Alarm: Hood & Duct: Monitor: /Needs Pre -Fire: / Permits: Occupancy Type: Inspector: 56,✓ 6—, Date: l6/G/G,p Hrs.: / $80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from City of Tukwila Finance Department. Call to schedule a reinspection. Word/Inspection Record Form.Doc 1/13/06 T.F.D. Form F.P. 113 2 INSPECTION NUMBER SEP 2 6 2008 INSPECTION RECORD ),00 8'— OG 7 Retain a copy withrmit o ) rote'— /6 ( PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East, Tukwila, Wa. 98188 206-575-4407 Project: 4,y•; J.Gs Sprinklers: Fire Alarm: Type of Inspection: S4si[€ Sk., I ✓Jvwn Address: /3" 1 Suite #: vii 41/• 5 • Contact Person: Special Instructions: Phone No.: ['Approved per applicable codes. Corrections required prior to approval. COMMENTS: I'Ve 17.e4 c&1 ,rn v /4- $) J PO4,4 ,, Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: Sc,, (Jr Date: g/ZK/Or Hrs.: / $80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from e City of Tukwila Finance Department. Call to schedule a reinspection. Word/Inspection Record Form.Doc 1/13/06 T.F.D. Form F.P. 113 BUSINESS NAME: ADDRESS: TUKWILA FIRE DEPARTMENT FIRE PREVENTION BUREAU (206) 575-4407 CORRECTION NOTICE/REINSPECTION FEE 5*? ; I c s DATE: 9 119 far /s'1 z 5 $3 .4v. S_ BLDG: SUITE: ) "L/ APT: TYPE OF INSPECTION:hir. CONTACT PERSON: &a/atm INSPECTOR: a r BLDG. PERMIT #: 0 PHONE:Y2$7-YYY' rt/50 ACTION REQUIRED: a gpifr {eat 0 Acid Hare) S7a..6, 44- rrsOw/ °Doi.L 4.5 .d re ate' e4 f K opt 4-Ar, ioo ~i 5.�� e.Ac a -1= y 3z illcrtgCo (X 1- 1 1 0 21S�.p1) 1' *7 44-4 VI) ..., i4 j+c/ L Jerks-L. ie.,.,, PI - CORRECTION %) A $80.00 Finance FAILURE TO OF THE ABOVE ITEMS ARE REQUIRED BY: 7 ale/14,s l --za' Reinspection Fee is required. You will receive an invoice from the City of Tukwila Department. COMPLY may result in the issuance of a criminal citation. , Correction Notice Reinspec Fee W -Office Y -File P -Contractor Revised 1/13/06 T.F.D. Form F.P. 100 2 INSPECTION NUMBER INSPECTION RECORD Retain a copy wit, it SEP 2 2 2008 OP.F• °!32 'wog- o 3 , PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East, Tukwila, Wa. 98188 206-575-4407 Project: 5,,„; jos Sprinklers:/ Type of Inspection: ill 'ev'4j4'yy1 gr,..) Address: /SW L5 Suite #: t3 Av. s Contact Person: F1 Special Instructions: 1. Phone No.: 11z6s— liyL - PIA, VI/Approved per applicable codes. Corrections required prior to approval. COMMENTS: Sprinklers:/ Date: Fire Alarm: Hood & Duct: 2. Monitor: 1. Horn /S?a.Jvts cd GvC. Permits: 2 / Proms Ob me 3 . 34a.e ..mss YsN3 2Y., Y. Vqk.j4 J'Miri.a.ril.•S s•. en at DX L, -Ae.- v ZY. 7 C PAsi it.4 Trvvb 1` /3. .,,i 0 astis Ai • c< 7. ?'re.4,1.L i4 I.4.1.06i Xer.07 rJ. • 1 Lfi arc. d. nil el;bLJ )ti .i -m o .�/ .X. 7. isegXG c / fi..- iw ftiC4 we. /o. S,•lx/��rd o?P fk)cot-4•38. &At ms.4 /1. Pit R'rtr L�v.&e%ukC • Needs Shift Inspection: Sprinklers:/ Date: Fire Alarm: Hood & Duct: 2. Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: SW 535 Date: 9//4/•$, Hrs.: 2. 4114r$80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from he City of Tukwila Finance Department. CaII to schedule a reinspection. Word/Inspection Record Form.Doc 1/13/06 T.F.D. Form F.P. 113 3 INSPECTION NUMBER INSPECTION RECORD Retain a copy with permit pas -�y9 d6 -s-344. PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East, Tukwila, Wa. 98188 206-575-4407 Project: ,s,,,,,i,t.e‘s Sprinklers: Fire Alarm: Hood & Duct: Type of Ins ection: kI 0t C' Address: 45 if ZS Suite #: 5 3 AI/ 5. Contact P rson: Special Instructions: Phone No.: riApproved per applicable codes. Corrections required prior to approval. COMMENTS: irisfolco- c 12-oo c Z35 76. CND a / (bV c Z/°° h416eo 61(-- Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: ns I_ • Ir: �. n%u.� S 1 Z- Date: $%Z2 /D� Hrs.: Z_ $50.00 REINSPECTION FEE REQUIRED. You will receive an invoice from City of Tukwila Finance Department. Call to schedule a reinspection. Word/Inspection Record Form.Doc 1/13/06 T.F.D. Form F.P. 113 2 INSPECTION NUMBER INSPECTION RECORD Retain a copy with permit t .DP8' 3Y 9 C28- S 34.G PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East, Tukwila1 Wa. 98188 206-575-4407 Project: 5,moi' lis Sprinklers:/ f)3 Type of Inspection: Pav4,10 C //l. tIas Sez- pf ,,,3 Address: istrz.f' Suite #: 5'3 ori. s. Contact Person: ,Ocn•2; 3 So, ,4-14 Special Instructions: Phone No.: .25.2- 6'33 — )Zcfk proved per applicable codes. Corrections required prior to approval. COMMENTS: D 10 Cb✓Gn/ M4/1‘) 1 [ 3 ! j iii cel a )1294.e4 Needs Shift Inspection: Sprinklers:/ f)3 Fire Alarm: Hood & Duct: Hrs.: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: SW f)3 Date: VZ31vi Hrs.: $80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. Call to schedule a reinspection. Word/Inspection Record Form.Doc 1/13/06 T.F.D. Form F.P. 113 INSPECTION NUMBER INSPECTION RECORD Retain a copy with permit 051- .J- 3 GC PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East, Tukwila, Wa. 98188 206-575-4407 Project: .',,,,%S Sprinklers: Fire Alarm: Type of Inspection: _ Si%NLetrw- ..Ai cit .--d, Address: /51i25' Suite #: 57,3 20, - Contact Person: G„a, )41,74.— Special Instructions: Phone No.: ,2333- k33— /2y9 Approved per applicable codes. corrections required prior to approval. COMMENTS: Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: jt,, ,55--- Date: 7�j34i Hrs.: $80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from h City of Tukwila Finance Department. Call to schedule a reinspection. Word/Inspection Record Form.Doc 1/13/06 T.F.D. Form F.P. 113 444 Andover Park East, Tukwila, WA 98188 - Phone 206-575-4407 - Fax 206-575-4439 E-mail: tukfdpry@ci.tukwila.wa.us. . CONTRACTORS M.A:TERXA.L AND TEST CERTIFICATE • FIRE ALARM AND FIRE DETECTION SYSTEMS Fire alarm System is ready for Fire Department acceptance testing. Failure of test will result in termination of the testing and additional fees will be assessed. Contractor is responsible for supplying manpower for Final Acceptance Test with two-way communications. • • Date ' �"i I !clic, 6 Permit # Property Address.Suite # City Tukwila Zip Code Name of Facility Sv • r_l_pr-L — l G� Occupied as Owner or Representative Phone # .Installing Company .t,r. C,p v� Instilling Contractor's Address City Phone # Installer's Name (PRINT) Ie%"-CkI47-e__ Kf:elr- License and/or Certificate General Contractor t.%) yo„ 1A6.e.e1", Electrical Contractor FACP Equipment Manufacturer , 4 Model # ? 00 This system has beet jzistalled, pre -tested and operates in accordance with the standards listed below and was inspected by 1—, t £_ On (date) . Circle all that apply: NFPA 72, Chapter 1 2 4 5 6 7 and/or IFC SEC 907 }C NFPA 70, National Electrical Code, Article 760 Manufacturer's Instructions Manufacturer's Instructions Other (specify) Tukwila City Ordinance Numbers 2050, 2051 UL Central Sta on onit r '7 572 L 17 / / System is monitored by SIGNED Date and includes the devices listed on back. System Firmware: Installed version • Initial program Checksum Date EQUIPMENT INSTALLED AND TESTED: Control Panel of Manual Station L of r - Smoke Detectors of Heat Detectors — of Duct Detectors. of ATV Devices ± of Audio Devices of Visual Devices of 2, Auto Door Release of Trouble Indictors of Batteries • Readings Battery 27.3 Full Load r b Charge 2`7 t •Make/Model Make/Model Make/Model' Make/Model Make/Model Make/Model • Make/Model Make/Model 6,e Make/Model Make/Model Generator of HVAC Controls of Fire Alarm Dialer of Monitored by A-( w. Annunciator of Make/Model Make/Model 1I _ Make/Model tckee-1 -7c-7Z Make/Model ❑ Sprinkler System. (Fire Alarm connections only) Water Flow Sw. l of ( Make/Model 4,0 11�� Valve Tamper Sw. "2 of Make/Model >d ft r/ PIV of ( Make/Model 1�a`�r Elec. Alarm.B ell of • Make/Model Automatic time Delay of Water Flow Alarm d seconds. None Installed Do you meet audible/visible requirements of WAC51-20; IFC SEC 907., and/or NFPA 72 Chapter 6? Yes X. No Test of alarm System on emergency power, satisfactory? YesiC No _ Test Witnessed by Title Date Comments: WASHINGTON SURVEYING & RATING BUREAU 2101 4th Avenue Suite 300 Seattle, WA 98121 P 206.217.9772 F 206.217.9329 www.wsrb.com Underwriting Information, Filings & Property Loss Costs Jose A. Buitrago Senior Field Representative/ Pian Review jose.buitrago©wsrb.com 206.273.7157 July 2, 2008 PLAN SHEETS 1 of 1 SUBJECT Smiles @ Southcenter 15425 — 53"1 Ave. South Tukwila, Washington The attached plans have been reviewed as follows: The following revisions or additions to the design as shown would qualify the protection for improved rates based upon information shown on these plans. Completed copies of the Contractor's Material and Test Certificates for both the overhead and underground piping should be submitted to this Bureau, including tests of the local alarm and main water supply test pipe (2 -inch). All piping, valves, and fittings should be listed and labeled by UL for fire service and installed, tested, and flushed in accordance with NFPA standards. A minimum temperature of 40°F must be maintained with a thermostatically controlled heating system in all areas containing wet pipe sprinkler equipment. 1. Hangers should be installed according to UL listing and as specified by NFPA 13. 2. Extend sprinkler protection to all areas including exterior eaves, soffits, canopies, combustible blind and roof spaces, and to roof skylights. 3N gpk, n rDa�ual In ue wd l stry Since 1911 ,a4 Serving the P ty q PO Box 3932 Seattle WA 98124-3932 206-234-5700 Tel 253-517-5775 Fax Fire Com NW, Inc. Battery Calculation Work Sheet Project: Smiles @ Southcenter Fire Alarm System Project 15425 — 53`d Avenue South Tukwila WA 98188 This project consists of a tenant improvement to an existing space in the building. The building is fully sprinklered. This worksheet is for the fire alarm control panel and the connected devices. Qty Part # and description Supervised Current mA Alarm Current mA 1 5700 Silent Knight FACP 200 325 1 SD505-APS Add smoke det 0.55 0.55 4 SD500 —PS Add pull stations 2.20 2.20 5 SD500-AIM Add input mod 2.75 2.75 4 GEC3 Horn strobes wall mt 0 548 12 GESS Strobes wall mt 0 660 Subtotal 206 1538 Total battery power hours x24 x.083 Subtotal 4944 128 Safety factor -10% +494 + 13 Total 5438 ma 141 ma Total Current Required 5579 ma or 5.6 amps Battery size used: 2ea- 12volt, 7amp PAID -A•• AUG 2 5 2008 h ukwila Fire 25s X77/ 06/25/2008 09:25 FAX 2537350113 FIRE SYSTEMS WEST Z001 Ore Systems Wesi"Inc. 219 Frontage Road North, Suite B • Pacific, Washington 98047-1023 • Phone (253)833-1248 • Fax (253 735-0113 6/25/08 Tukwila Fire Department 444 Andover Park East Tukwila, WA 98138 Attn: Lt. Don Tumaso Fax # (206) 575-4439 Re: Smiles @ Southcenter — Demo. FSW Job No. 2-11-10077 15 T _ S 5 3 46>. Dear Lt. Tumaso FSW is requesting a Tukwila shutdown number in order to demo some sprinkler drops and an existing fire hose cabinet in the way of wall framing. FSW is preparing drawings for plan review at this time. am Ruark Project ManagenDesigner Fire Systems West, Inc. l I UKWILA FIRE DEF'Arc 1 mast Please call: 575-4407, and give this ,job and exact address for shut. Immo or rest:,ratiion approval A D AA j EXISTING(--=3 AM b Q SPRINKLERA —d A o—A AM A—o 126 curwFE,e A u eE P5 OP 6 116 STAFF ENTRY 3 P7 OP 8 118 A IJ OP 4 114 APE, B B b OP 3 113 LIBRARY 102 OP 2 112 WOMEN'S RR 103 0, hi 1171 HA AY TO FACP A LO B NGE 1123 F B 111 /E LAB 120 0 MEENN'S 121 if " D ELECTP NEL B b PAN CBPH 110 '—B CLOSET 109 B 6 STAFF 122 Orws )FFIC 108 B CLE:MTFIC.F,I L� J STAFF ENTRY 2 (EXISTING) A U B b RECEPTION 101 CHECKOUT los C9NSULT 107 A A RE U SKIN 104 1, w 3 ADD 1 LAYER OF ave TO EKE SURFACE BUSINESS 106 STAFF ENTRY 1 (EXISTING) FIRE ALARM PLAN SCALE: 1/8"s1'-0" 0 1 2 4 8 16 FIRST FLOOR TO 120 VAC UNBIMTCFED DEDICATED CIRCUIT TO TELCO ROOM FIRE ALARM RISER DIAGRAM SCALL: NONE EQUIPMENT LEGEND MBE QUANTITY PART NUM" 001101PT $ 840308 ® 1 5700 FIRE ALARM CONTROL PANEL INCLUDED I© 4 50500 -PS MANUAL PULL STATION SRIO)F GNIG m 1 S050S-APS SMOKE DETECTOR 4 SQUARE X 1-7/r DEEP ®0 4 0E03 HORN STROBE 4 SQUARE P 1-7/s' Da ® 12 0883 STROBE 4 50UAEX1-7/r ® 3 50500-59A ADDRESSABLE INPUT MODULE 4 80U/ OECX 1-7/86 OE 2 -- DUCT DETECTOR (0) PROVIDED BY OTHERS © 2 -- TAMPER SMAICN (A) PROVIDED BY OTHERS ® 1 -- WATER -FLOW PATCH (0) PROVIDED BY owns (0) - PROVIDED AND NSTAU.EO BY OTHERS WIRE LEGEND MBE DISCI P110N A 18 AVO, 2 CONDUCTOR 'PPCF JACKETED CABLE 5 14 AWA 2 CONDUCTOR 'FPLP' JACKETED CABLE c is AWA 4 CONDUCTOR 'FPL, JACKETED CABLE GENERAL NOTES: 1. ALL WORK IS TO CONFORM TO NATIONAL ELECTRIC CODE STANDARDS. 2. WIRING METHOD IS TO BE OPEN CABLING EXCEPT WHERE IT IS EXPOSED AND BELON SEVEN FEET • THEN R 1S TO BE IN CONDUIT. 3. ALL JUNCTION BOXES, CODERS, AND BACK BOXES ARE TO BE PANTED RED. 4. PULL STATIONS ARE TO BE MOUNTED AT 48' TO 53 ABOVE THE FLOOR. 5. ALL WALL MOUNT 84 DOOR HORNS, STROBES, HORN STROBES, AND SPEAKER STROBES ARE TO BE MOUNTED 80' ABODE THE FLOOR OR 8• BELOW THE CEING, NNICHEVER IS LOWER. 8. SMOKE DETECTORS SHALL BE INSTALLED N ACCORDANCE WITH THE FOLLOWING: A) 38' INCHES AWAY FROM ANY AIR HANDLING SYSTEM DIFFUSER 9) NOT N CLOSE PROXIMITY TO ANY FLUORESCENT LIGHT FIXTURES 7. EXTERIOR HORN / STROBE SHALL BE MOUNTED ON THE TOP 2/3 OF THE OUTSIDE WALL OF THE BUILDING, AS HIGH AS POSSIBLE FOR MAXIMUM VISIBILITY FROM THE FIRE DEPARTMENT ACCESS ROADWAY. S. ALL WIRING PENETRATNOANY FIRE RATED BARRIER SHALL BE SEALED WITH MATERIAL WHICH WILL PREVENT PASSAGE Of FLAME AND HOT GASES. FIRE COM NW PO sox 3932 Seatt. WA 981243832 208-2344700 DATE: 8/22/08 DRAWN: CEA CHECKED: JD APPROVED BY: JD SCALD 1/8"=1'-0" N0. DATE REVISION BY PROJECT NAME SMILES E2 SOUTHCENTER 15425 53rd Avenue S. Tuklwile, WA 98188 Mir WILE: FIRE ALARM PLAN JOS NUMBER: 08- FA -1 O( / fog >.. sta ' `.-,,-... Addie::: this date resubmittal of re.;:_:..„ : 441I•Mr,maa Aft i 1 1 Final acceptance is subject 10 b` The Tukwila Fire Prevention Bureau. 1 Date: a, OBy: NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection System-. Failure of test will resu. in a Re -inspection Fee termination of the te' ri. ANT NOTICE Because of fr1.7.1-FaF-t-1 demand our inspectors e,re booked 3-7 days ahhea:i. Ii:�:,-efore, you will need to call 206-575-4407 to schedule your inspections a minimum of 48 hours in advance of the date you want an inspection. —�'4.341 fl re ,„v -j e L. & D. s - o►- 46o ve- Ce, f, hg ANA- die+ vc-IO rS '-' Ihs-1-41( /0 G GC o of t u i Ce b h d edi i Cw 1A.ci f�4 Gi rc, ;`-- %vewkit^. A -a d re -5 s o, s repoC6„r6w t S t-r-v-4?oti 1‘1-04--w 6 l 4 kwo c O o y. rufkwILA FIRE DEPARTMEN Pease call: 575-440Z and give this job No.Of j cxa�t adiress for shut. .;n or rQ_taration aonrrwml: FILE COPY LA e -P., E2`( R-EGei pESI� _ 10`-0' , Weld stamps must be inspected before pipe is hung. D0 not paint piping. prior to hydrostatic test �I .�'�;`i 1. CCEPTE Without Comments AsNoted lnRed Per The Attached Letter I hese plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted stemmas and orcunances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings atter this date will void thie.acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire, Prevention Bure Date, •► 0 By: '2 9 0. ( o -0 0 A 2" WOOD NAILER SIDEWINDER! HANGER MATE - 3/8" ALL THREAD ROD RING HANGER Lc) U ki6a D2. oiIGI✓ 5XNc, UP121&1PITS To �EMAI14 •Ay 'Zoo F THLrr, 12.EL.ocPcTE EX I4-rI NICD 1" E7I2.c)P IAdJ r7 PE1-I D L -h GATT o I4 , P--EPL.A C -e EX I STl til ( PERI 17 04-- P P 1,1 Ie-L-EIz-S w rrkF-- OPEN WEB JOIST (4" AND SMALLER PIPE) I HANGER JW SIDEWINDER (WOOD) _VICINITY -FL TENANT IMPROVEMENT THIS PROJECT ISA TENANT IMPROVEMENT. THIS FACILITY HAS ALREADY BEEN PROTECTED BY A FIRE SPRINKLER SYSTEM. FIRE SYSTEMS WEST IS ADDING AND/OR RELOCATING SPRINKLER HEADS TO ACCOMMODATE THE NEW TENANT WALL, CEILING, LIGHTING AND HVAC LAYOUT. ALL WORK WILL BE DONE WITHOUT AFFECTING THE CAPABILITY OF THE EXISTING SYSTEM. HANGER LEGEND 'U" H00I< COACH SCREW ROD 'C' CLAMP D TOP BEAM CLAMP W/ STRAP EYE ROD FLUSH SHELL CEILING FLANGE SIDE BEAM BRACKET • Ell0 CI 'L" ROD SYMBOL LEGEND IuKWILA FIRE. UENAKIiW hair Please call: 575.4407 and give this job No, S and exact address for shut. lawn or restoration approvaj, CONTRACT NAME: R - DENOTES A SPRINKLER HEAD TO BE . RELOCATED. A = DENOTES A SPRINKLER HEAD TO BE ADDED. '-' — - REPRESENTS EXISTING SPRINKLER PIPE. - REPRESENTS NEW SPRINKLER PIPE. SPRINKLER LEGEND SPRINKLER HEADS MACHINE THREADED ROD TOGGLE NUT POWDER DRIVEN STUD V,'EDGE ANCHOR SPKR THRDS. SPRINKLER ORIFICE SIZES AND TYPE UPRIGHT PEND. TEE SIZE SPRINKLERS UP AND DOWN SYMBOL TYPE REVISIONS 0 5N r7 kI1 MFG TYco MODEL T`r--23 SIZE I/Z" 1/2' 3/4' 1/2' 1' 5/16' 3/6' 7/16' 1/2' SPRAY 17/32' SPRAY 3/8' 7/16' 1/2' SSDEWALL 1/2' DRY TWE O O 1/2' OPEN'G UP SYMBOL OPEN'G DOWN TEMP. 155° ©R. FINISH GHI2OME CANOPY I2EL, CI -1 2 QUANTITY Sg DATE O 1' 1/2' 1' 0 0 3/4' 1' 1/2' El 1' 1' 1' 1/2' d 1' 1' 1/2' TEMP RATING 1/2' -e- 200' 286.' 350' BY ■ ■ DESCRIPTION APPROVALS REQUIRED 6.1TY oF- ru1=-VuILA ow NE--/Al2-cH. VI''R TOTAL THIS SHEET 58 DISTRIBUTION r t,t% TOTAL Ea GENERAL NOTES 1. ALL MATERIAL AND EQUIPMENT TO BE NEW AND UNDERWRITERS APPROVED. 2. PIPING DIMENSIONS ARE CENTER 10 CENTER EXCEPT RISER & DIMENSIONS SHOWN THUSLY (1-6) WHICH ARE END 10 END. 3. EARTHQUAKE BRACING SHALL BE PROVIDED IN ACCORDANCE WITH NFPA PAMPHLET NO. 13. 4. PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13. :5. PIPING SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13. 6. JOINING OF PIPE AND FITTINGS, THREADED AND WELDED SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13. 7. OWNER TO PROVIDE ADEQUATE HEAT TO PREVENT WATER IN PIPES FROM FREEZING IN AREAS PROTECTED BY A WET PIPE SPRINKLER SYSTEM. 8. STRUCTURAL ADEQUACY OF THE BUILDING TO SUPPORT THE SPRINKLER PIPING IS THE RESPONSIBILITY OF THE OWNER AND/OR HIS STRUCTURAL REPRESENTATIVE. DESIGN CRITERIA AND NOTES PIPIT 51ZE1? ANrc Pte- Ni fA I3, oR_DIHArz-%( I-4AZAgc7 PIPE 4G1-I-G12L)L-E HF�r`IC'I ALL.- A2I -off/ 1 ovEiZ.I'-O", CONTRACT WITH: K,kPISI SISITuimilaFire 4- 7(0593,7 (2-510 I30 LANE NE 1 — KI 12 -K -LAR D, c"1 `b03A- (1-z S-) 82-1- 6zocd) 354- - 52.11 Fire S'ste s Wst 219 Frontage Road North, suite B Pacific, WA 98047 (253) 833-1248 fax: (253) 735-0113 WA CL #FIRESW1 140B1 Q.C. FAB BY: / / DESIGNER JAMES 17 -QA DATE Jz5 o' Q.C. INSTALL BY: / / JOB NO. SHEET 2. -At -100-1—t IoF I TE12-IL� 114: Tn —1 i l'i' II 11 R-EGei pESI� _ 10`-0' , Weld stamps must be inspected before pipe is hung. D0 not paint piping. prior to hydrostatic test �I .�'�;`i 1. CCEPTE Without Comments AsNoted lnRed Per The Attached Letter I hese plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted stemmas and orcunances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings atter this date will void thie.acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire, Prevention Bure Date, •► 0 By: '2 9 0. ( o -0 0 A 2" WOOD NAILER SIDEWINDER! HANGER MATE - 3/8" ALL THREAD ROD RING HANGER Lc) U ki6a D2. oiIGI✓ 5XNc, UP121&1PITS To �EMAI14 •Ay 'Zoo F THLrr, 12.EL.ocPcTE EX I4-rI NICD 1" E7I2.c)P IAdJ r7 PE1-I D L -h GATT o I4 , P--EPL.A C -e EX I STl til ( PERI 17 04-- P P 1,1 Ie-L-EIz-S w rrkF-- OPEN WEB JOIST (4" AND SMALLER PIPE) I HANGER JW SIDEWINDER (WOOD) _VICINITY -FL TENANT IMPROVEMENT THIS PROJECT ISA TENANT IMPROVEMENT. THIS FACILITY HAS ALREADY BEEN PROTECTED BY A FIRE SPRINKLER SYSTEM. FIRE SYSTEMS WEST IS ADDING AND/OR RELOCATING SPRINKLER HEADS TO ACCOMMODATE THE NEW TENANT WALL, CEILING, LIGHTING AND HVAC LAYOUT. ALL WORK WILL BE DONE WITHOUT AFFECTING THE CAPABILITY OF THE EXISTING SYSTEM. HANGER LEGEND 'U" H00I< COACH SCREW ROD 'C' CLAMP D TOP BEAM CLAMP W/ STRAP EYE ROD FLUSH SHELL CEILING FLANGE SIDE BEAM BRACKET • Ell0 CI 'L" ROD SYMBOL LEGEND IuKWILA FIRE. UENAKIiW hair Please call: 575.4407 and give this job No, S and exact address for shut. lawn or restoration approvaj, CONTRACT NAME: R - DENOTES A SPRINKLER HEAD TO BE . RELOCATED. A = DENOTES A SPRINKLER HEAD TO BE ADDED. '-' — - REPRESENTS EXISTING SPRINKLER PIPE. - REPRESENTS NEW SPRINKLER PIPE. SPRINKLER LEGEND SPRINKLER HEADS MACHINE THREADED ROD TOGGLE NUT POWDER DRIVEN STUD V,'EDGE ANCHOR SPKR THRDS. SPRINKLER ORIFICE SIZES AND TYPE UPRIGHT PEND. TEE SIZE SPRINKLERS UP AND DOWN SYMBOL TYPE REVISIONS 0 5N r7 kI1 MFG TYco MODEL T`r--23 SIZE I/Z" 1/2' 3/4' 1/2' 1' 5/16' 3/6' 7/16' 1/2' SPRAY 17/32' SPRAY 3/8' 7/16' 1/2' SSDEWALL 1/2' DRY TWE O O 1/2' OPEN'G UP SYMBOL OPEN'G DOWN TEMP. 155° ©R. FINISH GHI2OME CANOPY I2EL, CI -1 2 QUANTITY Sg DATE O 1' 1/2' 1' 0 0 3/4' 1' 1/2' El 1' 1' 1' 1/2' d 1' 1' 1/2' TEMP RATING 1/2' -e- 200' 286.' 350' BY ■ ■ DESCRIPTION APPROVALS REQUIRED 6.1TY oF- ru1=-VuILA ow NE--/Al2-cH. VI''R TOTAL THIS SHEET 58 DISTRIBUTION r t,t% TOTAL Ea GENERAL NOTES 1. ALL MATERIAL AND EQUIPMENT TO BE NEW AND UNDERWRITERS APPROVED. 2. PIPING DIMENSIONS ARE CENTER 10 CENTER EXCEPT RISER & DIMENSIONS SHOWN THUSLY (1-6) WHICH ARE END 10 END. 3. EARTHQUAKE BRACING SHALL BE PROVIDED IN ACCORDANCE WITH NFPA PAMPHLET NO. 13. 4. PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13. :5. PIPING SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13. 6. JOINING OF PIPE AND FITTINGS, THREADED AND WELDED SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13. 7. OWNER TO PROVIDE ADEQUATE HEAT TO PREVENT WATER IN PIPES FROM FREEZING IN AREAS PROTECTED BY A WET PIPE SPRINKLER SYSTEM. 8. STRUCTURAL ADEQUACY OF THE BUILDING TO SUPPORT THE SPRINKLER PIPING IS THE RESPONSIBILITY OF THE OWNER AND/OR HIS STRUCTURAL REPRESENTATIVE. DESIGN CRITERIA AND NOTES PIPIT 51ZE1? ANrc Pte- Ni fA I3, oR_DIHArz-%( I-4AZAgc7 PIPE 4G1-I-G12L)L-E HF�r`IC'I ALL.- A2I -off/ 1 ovEiZ.I'-O", CONTRACT WITH: K,kPISI SISITuimilaFire 4- 7(0593,7 (2-510 I30 LANE NE 1 — KI 12 -K -LAR D, c"1 `b03A- (1-z S-) 82-1- 6zocd) 354- - 52.11 Fire S'ste s Wst 219 Frontage Road North, suite B Pacific, WA 98047 (253) 833-1248 fax: (253) 735-0113 WA CL #FIRESW1 140B1 Q.C. FAB BY: / / DESIGNER JAMES 17 -QA DATE Jz5 o' Q.C. INSTALL BY: / / JOB NO. SHEET 2. -At -100-1—t IoF I