HomeMy WebLinkAboutPP - 1251 ANDOVER PARK WEST - DANIA - PERMITS AND PLANS1251 ANDOVER PARK WEST
ASSOCIATED PERMITS
18-F-153
18-F-070
443ttliWitt4e
SITE LOCATION
CITY OF TUKWILA
FIRE MARSHAL'S OFFICE
206-575-4407
I2M
FIRE PROTECTION SYSTEMS PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
**PLEASE PRINT**
King Co. Assessor's Tax No.: 3523049103
Site Address: 1251 Andover Pk W Tukwila, WA 98188 Suite Number: Floor:
e
Tenant Name: V01/44/a 0\ G •
New Tenant? ❑ - Yes ENo
Property Owner's Name: Dania Inc.
Mailing Address: 2250 S McDowell Blvd Petaluma CA 94954
CONTACT PERSON -if there are questions about the submittal.
Name: Manny Ornelas Day Telephone: 206-436-5301
Company Name: Washington Alarm
Mailing Address: 2030 Airport Way S
City State Zip
permits@washingtonatarm.com City
E-mail Address:
Contractor's City of Tukwila Business License number: BUS -0992857
State Zip
Fax Number: 206-322-7214
Total number of new/relocated devices or sprinkler heads:
Valuation of Project (contractor's bid price): $ 1 ,000
Scope of Work (please provide detailed information):
Connection of a new HVAC Smoke Duct Detector to existing 1912 FACP
PERMIT APPLICATION NOTES
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be
reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules.
Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit
is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or
abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in
writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing
and justifiable cause demonstrated.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE N
UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY
FOR THIS PERMIT. PAID `R
BUILDING OWNER 0 c.aUir 0 • I AGENT:
Signature: �'? __t 20r Date: 3/29/2018
Print Name:
Manny Ornelas 1IIUK Iky TFelephoIRne:ir- 206-436-5301
Plan Permit App.doc
8/22/14 C C /P Z6b
TFD FP Form 8
4 ittN/
SITE LOCATION
CITY OF TUKWILA
FIRE MARSHAL'S OFFICE
206-575-4407
FIRE PROTECTION SYSTEMS PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
**PLEASE PRINT**
King Co. Assessor's Tax No.: 3523049103
Site Address: 1251 Andover Pk W Tukwila, WA 98188 Suite Number: Floor:
Tenant Name: Dania Inc. New Tenant? ❑ - Yes ENo
Property Owner's Name: Dania Inc.
Mailing Address: 2250 S McDowell Blvd Petaluma CA 94954
City State Zip
CONTACT PERSON -if there are questions about the submittal.
Name: Manny Ornelas Day Telephone: 206-436-5301
Company Name: Washington Alarm
Mailing Address: 2030 Airport Way S
ermits�washin tonalarm.com City State Zip
E-mail Address: P g Fax Number: 206.322-7214
Contractor's City of Tukwila Business License number: BUS -0992857
Total number of new/relocated devices or sprinkler heads: 6
Valuation of Project (contractor's bid price): $ 4,200
Scope of Work (please provide detailed information): Installation of a new Fire Alarm control panel
& AES radio for monitoring of an existing fire alarm system.
PERMIT APPLICATION NOTES
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be
reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules.
Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit
is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or
abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in
writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing
and justifiable cause demonstrated.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE
UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY
FOR THIS PERMIT.
BUILDING OW
JIORIZE
GENT:
Signature: PPP-
anny Ornelas
Print Name:
Plan Permit App doc
PAID
IRI_ 312018
Date:
.71 31 lb
TUKWILOIte: 206-436-5301
8/22/14 TFD FP Form 8
INSPECTION NUMBER
INSPECTION RECORD
Retain a copy with permit
PERMIT NUMBERS
CITY OF TUKWILA FIRE DEPARTMENT
206-575-4407
Project: N
t
Type of Inspection:r
4fr,1,24.0
Address:
Suite #: fl 4.5-7
/
Contact Person:
Special Instructions:
41
Phone No.:
pproved per applicable codes.
Corrections required prior to approval.
COMMENTS:
r'etv,-4 /9-ae--0 Fps' A-Evi-e-e-5
c�., �.ct cw w,ll
lu/'P*'� wl�c.H. ct��fwc- lotiec.-i-s
Needs Shift Ins ction:
Sprinklers: C(••€"5
Fire Alarm: tel"
Hood & Duct:
Monitor: fit/
41
/4-‘
Pre -Fire:
Permits:
Occupancy Type:
S-- I
Inspector: .F1vt,
Date: VG? /1
Hrs.:
$100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. Call to schedule a reinspection.
Billing Address
Attn:
Company Name:
Address:
City:
State:
Word/Inspection Record Form.Doc
3/14/14
Zip:
T.F.D. Form F.P. 113
l
INSPECTION NUMBER
INSPECTION RECORD
Retain a copy with permit
-F-153
PERMIT NUMBERS
CITY OF TUKWILA FIRE DEPARTMENT
206-575-4407
Project:Type
�a A.
`
of Inspection
-
Address:
Suite #: /-7,--/
_ _
Contact Person:
Special Instructions:
Phone No.:
Approved per ap licable codePt/ CiAreZlek*
COMMENTS
Corrections required prior to approval.
/IAD Hai( cdo-
l'tew isqviv-e, g
P(eArA
/10
/-' �"D laoua8
(-(044 /‘ /,(66e., Ahod- -aze---
e 11WrWig-e) 01-10tt" te-eAdvS Slibr-tv owe_
Needs Shift Inspection:
Date: I�/12l(q
Sprinklers: ti
Fire Alarm: y
Hood & Duct:
Monitor: IIA a4#-
v'---
Pre -Fire:
Permits:
Occupancy Type:
5,
Inspector: pleyl 91—
Date: I�/12l(q
Hrs.:
$100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. Call to schedule a reinspection.
Billing Address
Attn:
Company Name:
Address:
City:
State:
Zip:
Word/Inspection Record Form.Doc
3/14/14
T.F.D. Form F.P. 113
4,1404
WASHINGTON AL
Record of Completion
Fire Alarm and
Fire Detection Systems
Proudly Pro\iding
Quality, Service & Integrity
To The Pacific Northwest
Since 1943
Date: 1 ZD e Permit #: /9' / SS
Name of Facility: bog( #..0.- 'F✓r;n; e.._
Property Address /Z57 Je1 v1 J.J . City/State/Zip: 1:ki,tl, rte, iJ4 98/88
Installing Company: sL r,- 4644,41
Address: 20 S. City/State/Zip:
Installer's Name (PRINT): Ori N J v1
License and/or Certificate: /V
Occupied as: BoS #..ems — ori'
Qyner or Representative: 12o7.5 we J- f Phone:ZO6 — 5751- /9 / b
Authority having Jurisdiction: % v ki,,, L /.ev4i r
Address: Phone: do --S7 S— zi9/0
General Contractor:
Electrical Contractor:
nl/A
basks b r / . (4.1 to
FACP Equip. Manf: 5;14#14-14#;51A4— Model No.: 67760
The State or Local Electrical Permit "Final" inspection was completed on
(date). This
system has been installed, pre -tested and operates in accordance withh standards listed
below, was inspected by tat 5 isr1 A(9 444 on f t�1- 74) (6 and
includes the devices listed below.
✓/ NFPA 72
NFPA 70, National Elect. Code, Article 760, Manufacturer's Instructions.
Manufacturer's Instructions.
International Fire Code
Other (specify)
2030 Airport Way S
Seattle WA 98134-1603
UL LISTED CENTRAL STATION
LICENSED & BONDED ELECTRICAL CONTRACTOR
WASH IA1282C3
www.washingtonalarm.com
P: 206-328-3288
F: 206-322-7214
WASH I NGTON ALA
System m
Signed
Remote
Date i(
System Firmware: b Installed Version:
Checksum: Date:
Initial program Installation: le,/l7'fZo l$ Date:
Revisions and Reasons: A amu(. 14-419 In cx, iviCe•
Programmed by: JL1 %�i v (r k- t tillyS(t i ft4.t,)n /Kt uwt jJ ce,4-ff 14 3 1
Equipment Installed and Tested
Control Panel e of / Make/Model 5` L4 6 D0
Manual Station / of / Make/Model 5- k is g jL-iPul (-DA
Smoke Detectors / of / Make/Model ff� lkvr�%4 SIL - C4/
Heat Detectors Q'' of a Make/Model
Duct Detectors 2- of 2— Make/Model S; ,
A/V Device I of t Make/Model Sy vt- - P2 it) 1(�—
Audio Devices a of Make/Model
Visual Devices 3— of 3 Make/Model 5y,' i ,.�,>o� 5C -C)1 ---
Auto Door Release / of / Make/Model SIL—Peri
Trouble Indicators 'L of 2 Make/Model
Proudly Providing
Quality, Service & Integrity
To The Pacific Northwest
Since 1943
entral Station /�
?-z i8
iS;o/L'K�/
by 44.46
Batteries j of 2 Make/Model -VA-(e.-64k 4St_A /D 7
Readings Battery Full Load Charge 26.7c4
Generator of
HVAC controls of
Make/Model
Make/Model
Fire Alarm Dialer ( of / Make/Model 455-7-1.07-Fi
Monitored by 061614;#1) 10),1 j(e044 Phone ZOfr-3ZPy /get)
Annunciator ( of ( Make/Model S ( " kt..30 51960/�
Sprinkler System (Fire Alarm connections only)
2030 Airport Way S UL LISTED CENTRAL STATION
Seattle WA 98134-1603 LICENSED & BONDED ELECTRICAL CONTRACTOR
WASHIA1282C3
www.washingtonalarm.com
P: 206-328-3288
F: 206-322-7214
10,
WASHINGTONAL
Water Flow S 3 of .3
Valve Tamper
w. Sw.' of
3 of3
Eley.PIV Alarm Bell pof
Proudly Providing
Quality, Service & Integrity
To The Pacific Northwest
F , . Since 1943
Make/Model
Make/Model
Make/Model 5:k.•41--4.7/tl; O.°I
Make/Model
Automatic time delay of General Alarm minutes. None Installed X
Do you meet audible/visible requirements of NFPA 72, Section 7? •
No
Was the test of Alarm System on emergency power satisfactory? • Yes • No
Comments ()hes ✓I01' �[,1r/� p er,• �/�iy.S u�1
CERTIFICATIONS AND APPROVALS
Property or Owner Representative:
I accept this system as having been installed and tested to its specifications and all NFPA
standards cited herein.
Signed: Printed:
Organization: Title:
Date:
Phone:
Authority Having Jurisdiction:
I have witnessed a satisfactory acceptance test of this system and find it to be installed and
operating properly
in accordance with its approved plans and specifications, with its approved sequence of
operations, and with all
NFPA standards cited herein.
Signed: Printed:
Organization: Title:
Date:
Phone:
2030 Airport Way S
Seattle WA 98134-1603
UL LISTED CENTRAL STATION
LICENSED & BONDED ELECTRICAL CONTRACTOR
WASH IA1282C3
www.washingtonalarm.com
P: 206-328-3288
F: 206-322-7214
5D/
25' Rfrt
(0 VIA* Nftit,r
xklalitsieA
ACCEPTED
15 Without Comments
o As Noted in Red
O Per The Attached Letter
A NI - TLAILL,,, ► l4-
1\\
W4" E
5
These plans have been reviewed by The Tukwila Fire
Prevention Bureau for conformance with current City
standards. Acceptance is subject to errors and
omissions which do not authorize violations of adopted
c.:tandards and ordinances The responsibility for the
deguacy of design rests totally with the designer.
Additions, deletions o, :-visions to these drawings after
this date will void this acceptance and will regLire a
resubmittal of revised drawings for subsequent approval.
Final acceptance is subject to field test and inspection by
The Tukwila Fire Prevention Bu eau.
Date:
LI- ID By
51I
TUKWILA FIRE DEPARTMENT
Please call 205-573-4407 and
ghee this Fire Permit No.
t_nd exact address for shut -
.;:own or restoration approval.
PAID
IAP, 2O
TUKWILA, FIRE -
cc
120 VAC BELL/1J
(BY OTHERS) V -I
O Without Comments
"' As Noted in Red
Per The Attached Letter
These plans have been reviewed by The Tukwila Fire
Prevention Bureau for conformance with current City
standards. Acceptance is subject to errors and
omissions which do not authorize violations of adopted
standards and ordinances rhe responsibility for the
adequacy of design ;'oasts totally with the designer.
Additions, cf,letions =` revisions to these drawings after
this date wit! void this acceptance and will require a
resubmittal of revised drawings for subsequent approval.
Final acceptance is subject to field test and Inspection by
The Tukwila Fire Prevention Bureau.
Date: $- 9-I By: S I I ._
IM VS VS,IM 5T1 -270-q1
IM VS VS M DOC P
FWFM �T
M5 M-2
THRU THRU
M7 M-4
SLC
FROM
FACP
SHIPPING AND
RECIEVING
1/;;:#16/2 TWP
.5 FROM
FACP
UKWILA FIRS, DEPARTMENT
lease calf 206-575-4407 and
Siwe this Fire Permit No.
exact address for shut-
,..,ovvri
#16/2 TWP
SHOW ROOK
BUILDING FIRE ALARM PLAN
SCALE: 1/16"=1'-o"
0
8'
18'
32'
#14/2 AWG
FROM
FACP-1
MAIN
ENTRANCE
WP
75
N1-1
MD
!tit_ 312018
TUKWILA FIREo
shop drawings
seated by.
5794 W. 4800 So.
Hooper, UT 84315
Office: 801.985.0410
www.unicod.net
NICET III
Fire Alarm Systems
Date:
Signature
7/30/2018
Fire Protection Engineering
Technology
Fire t3ems
Cert.
N No..m 1 1388 751
Exp 5/1/2019
O
N
O
M
2
0
H
a
C.)
U)
w
EW & APPROVAL
0
N
rn
1253 S JACKSON ST. SEATTLE, WA 206-328-3288
TU - x ILA, WA 98188
FIRE ALARM PLAN
CRL
UNICAD JOB #18461
BRADY B. HAWS
NICET III 138751
Point to Point NAC Voltage Drop Calculation 7/30/2018
FACP Battery Calculation 7/30/2018
PROJECT NAME:
TEMPLATE
Required Standby Time:
Required Alarm Time:
24
5
Hours
Minutes
AC Branch Current
AC Branch Current: Amps CO 120V
Regulated Load in Standby
16.0
370
Device Type
Number
of Devices
14
Current
(Amps)
3.00
Total Current
(Amps)
FACP MAINBOARD
SMOKE DETECTOR
MONITOR MODULE
PULL STATION
ANNUNCIATOR
1
1
6
1
1
X
X
X
X
X
0.20000
0.00030
0.00040
0.00038
0.02000
=
=
=
=
=
0.20000
0.00030
0.00240
0.00038
0.02000
TOTAL STANDBY LOAD 0.22308
Regulated Load in ALARM
370
NAC -1
Device Type
Number
of Devices
WATER FLOW SWITCH
Current
(Amps)
Ea
Total Current
(Amps)
FACP MAINBOARD
SMOKE DETECTOR
MONITOR MODULE
PULL STATION
ANNUNCIATOR
FACP-1 (See Voltage Drop Calculations)
1
1
6
1
1
1
X
X
X
X
X
X
0.36500
0.00030
0.00040
0.00500
0.02500
0.17600
=
=
=
=
=
=
0.36500
0.00030
0.00240
0.00500
0.02500
0.17600
TOTAL ALARM LOAD 0.57370
Battery Requirements
Standby Load Required Standby Time in Hours
Current (Amps) 0.22308 X 24.00000 = 5.35380
Alarm Load Required Alarm Time in Hours
Current (Amps) 0.57370 X 0.08333 = 0.04781
Total Ampere Hours (before derating factor) 5.40161
Derating Factor X 1.2
TOTAL AMPERE HOURS REQUIRED = 6.48193
BATTERIES TO BE PROVIDED (2 - 12v) 8 Mi
DESCRIPTION
Point to Point NAC Voltage Drop Calculation 7/30/2018
Project Name
Circuit Number
Nominal System Voltage
Minimum Device Voltage
Distance from source to 1st device
Wire Gauge for balance of circuit
Max Output Current
Total Circuit Current
End of Line Voltage
DESCRIPTION
TEMPLATE
FACP-1
ACTIVATE AUDIBLE SUPERVISORY SIGNAL
volts
volts
feet
amps
amps
volts
Wire
Gauge
Resistance
Per 1000
3.07
3.07
20.4
16.0
370
14
rn
14
Lr `
3.00
0.176
20.00
Circuit is within limits
I
Device
Current
Distance
previous Voltage at Drop from Percent
device Device source Drop
370 20.00 0.400 1.96%
Device 1
0.176
Totals
0.176
370
NAC -1
Notes:
Wire resistance is doubled in the calculations for two wires (Positive and Negative).
The voltage calculated to the last device must not be lower than the manufactures listed
minimum operating voltage (IE: rated operating voltage 16-33 WC (24 VOC nominal)).
MODEL 5860
REMOTE
ANNUNCIATOR
SBUS
#14/4 AWG -'
120 VAC S --
(DEDICATED CKT.)
COM
AES -7788F
WIRELESS
FIRE ALARM
COMMUNICATOR
RJ31X
RJ31�
FACP
SYMBOL
DESCRIPTION
MOUNTING
ACTIVATE SUPERVISORY INDICATOR
ACTIVATE AUDIBLE SUPERVISORY SIGNAL
ACTIVATE TROUBLE INDICATOR
`FRCP
FIRE ALARM CONTROL PANEL
WALL -TOP ® 66"
TRANSMIT TROUBLE SIGNAL
FIRE SYSTEM ANNUNCIATOR
WALL -TOP 0 66"
rn
Lr `
KNIGHT SILENT
COM
O2 T
IntelliKnight
MODEL 5700
CEILING
"C00
LLII
w
a
rn
r
DIAL=R
MANUAL PULL STATION
NAC -1
24V
FROM
POWER
FACP
NAC -2
WATER FLOW SWITCH
BY OTHERS
Ea
•
VALVE SUPERVISORY SWITCH
/
VS
BATTERY f BATTERY
#14/2 AWG
EOL
EOL
FIRE ALARM RISER DIAGRAM
VS
M-3
VS VS VS WF
M-4 M-5 M-6 M-7
FIRE ALARM SYMBOL LEGEND
NM: AU. SYMBOLS MAY NOT BE USED ON THIS PROJECT
SYMBOL
DESCRIPTION
MOUNTING
ACTIVATE SUPERVISORY INDICATOR
ACTIVATE AUDIBLE SUPERVISORY SIGNAL
ACTIVATE TROUBLE INDICATOR
`FRCP
FIRE ALARM CONTROL PANEL
WALL -TOP ® 66"
TRANSMIT TROUBLE SIGNAL
FIRE SYSTEM ANNUNCIATOR
WALL -TOP 0 66"
FSA
WIRELESS FIRE ALARM COMMUNICATOR
WALL -TOP ® 66"
COM
O2 T
THERMAL/PHOTO ELECTRIC SMOKE DETECTOR
CEILING
ADDRESSABLE MONITOR MODULE
FIELD VERIFY
r
MANUAL PULL STATION
WALL ® 48"
P
WATER FLOW SWITCH
BY OTHERS
Ea
VALVE SUPERVISORY SWITCH
BY OTHERS
VS
R.
BELL
BY OTHERS
igKi WP
WEATHER PROOF HORN / STROBE
WALL 80"-96"
ABBREVIATION
DESCRIPTION
VALVE TAMPER SWITCHES
®4
75 $�A 30
E
EXISTING
A �GW)
G
WITH GUARD
P
PENDANT MOUNT
OO ,r DEVICE ADDRESS -\ CI
L1D001 OR DO1
b - oENOTEs LOOP
(D or M - ENOTES DEFECTOR 09 MODULE #)
R
RESIDENTIAL (110V)
S
SOUNDER BASE
WP
WEATHER PROOF
EOL
END OF LINE RESISTOR
EOLR
END OF LINE RELAY
- 16 2 TWP
AWG
AMERICAN WIRE GAUGE
TWP
TWISTED PAIR
WIRE TYPE ABBREVIATED
CONDUCTOR COUNT
TWSP
TWISTED SHIELDED PAIR
FPLP
FIRE POWER LIMITED PLENUM
WIRE SIZE
FPLR
FIRE POWER LIMITED RISER
OPEN CIRCUIT
OF CABLES (IF EDED) D
NLY 1 CABLE NEEDED)
NAC
NOTIFICATION APPLIANCE CIRCUIT
SLC
SIGNALING LINE CIRCUIT
OPERATIONS
MATRIX
FIRE ALARM INPUT
0
0
0
ff
w
rz
ACTIVATE ALARM INDICATOR I
ACTIVATE AUDIBLE ALARM
ACTIVATE SUPERVISORY INDICATOR
ACTIVATE AUDIBLE SUPERVISORY SIGNAL
ACTIVATE TROUBLE INDICATOR
ACTIVATE AUDIBLE TROUBLE INDICATOR
TRANSMIT ALARM SIGNAL
TRANSMIT SUPERVISORY SIGNAL
TRANSMIT TROUBLE SIGNAL
ACTIVATE NOTIFICATION APPLIANCES
SMOKE DETECTORS
PULL STATIONS
0
WATERFLOW SWITCHES
VALVE TAMPER SWITCHES
FIRE ALARM AC POWER FAIL
FIRE ALARM LOW BATTERY
OPEN CIRCUIT
GROUND FAULT
NAC SHORT CIRCUIT
LOSS OF AC TO BUILDING
-4" MIN
A/C SUPPLY OR
RETURN DIFFUSER
4' MIN
12' MAX
EVER
HERE
CEILING -MOUNTED
HEAT DETECTOR AUDIBLE/VISUAL 6" MIN.
AND/OR VISUAL
ONLY APPLIANCE E
WALL -MOUNTED
HEAT DETECTOR
80"-96"
TO LOWEST
PART OF LENS
90" MIN.
WHERE CEILING
HEIGHT ALLOWS
AUDIBLE -ONLY
APPLIANCES
GENERAL NOTES:
1. SCOPE OF WORK: THIS PROJECT SHALL INCLUDE THE INSTALLATION AND
MONITORING OF A NEW FIRE ALARM PANEL AND AES COMMUNICATION, TO AN
EXISTING SYSTEM, WAI CURRENTLY MAINTAINS.
2. THESE DRAWINGS ARE DIAGRAMMATIC. REFER TO THE ARCHITECTURAL DRAWINGS FOR
EXACT DIMENSIONS.
3. INSTALLATION SHALL COMPLY WITH NEC, NFPA 72 AND ALL OTHER APPLICABLE CODES
AS REQUIRED BY THE LOCAL AUTHORITY HAVING JURISDICTION.
4. WIRING DEPICTED ON THESE PLANS IS SCHEMATIC - ACTUAL WIRE LOCATIONS MAY
DIFFER FROM THESE PLANS. WIRING SHALL BE PERFORMED AS ACTUAL BUILDING
CONSTRUCTION CONDITIONS ALLOW AND TO MINIMIZE PENETRATIONS THROUGH AREA
SEPARATION WALLS AND FIRE WALLS. THE USE OF A RACEWAY IS PERMITTED AS
LONG AS NO 110V OR HIGHER VOLTAGE CABLES ARE IN THE SAME RACEWAY.
5. FIRE RATINGS SHALL BE MAINTAINED FOR ALL PENETRATIONS THROUGH FIRE -RATED
CONSTRUCTION.
6. POWER FOR ALL FIRE ALARM PANELS AND FIRE ALARM POWER SUPPLIES MUST BE
PROVIDED BY A DEDICATED AC BRANCH CIRCUIT. THE LOCATION OF THE BRANCH
CIRCUIT BREAKER SHALL BE PERMANENTLY IDENTIFIED AT THE CONTROL UNIT AND
SHALL HAVE A RED MARKING IN ACCORDANCE WITH NFPA 72.
7. POWER -LIMITED AND NONPOWER -LIMITED CIRCUIT WIRING MUST REMAIN SEPARATED
IN CABINET. ALL POWER -LIMITED CIRCUIT WIRING MUST REMAIN AT LEAST 0.25" AWAY
FROM ANY NONPOWER -LIMITED CIRCUIT WIRING. FURTHERMORE, ALL POWER -LIMITED
AND NONPOWER -LIMITED CIRCUIT WIRING MUST ENTER AND EXIT THE CABINET
THROUGH DIFFERENT KNOCK OUTS AND/OR SEPARATE CONDUITS.
8. WHEN UTILIZING CLASS "A" CIRCUITS, SEPARATE OUTGOING AND RETURN CONDUCTORS
OF CLASS "A" CIRCUITS BY A MINIMUM OF 12" WHERE RUN VERTICALLY AND 48"
WHERE RUN HORIZONTALLY.
9. WHEN UTILIZING SHIELDED CABLE TIE SHIELDS THROUGH AND INSULATE AT EACH
JUNCTION BOX. INSULATE AND TAPE BACK AT END.
10. ALL FIRE ALARM CABLING SHALL BE ACCEPTABLE TO THE FIRE ALARM EQUIPMENT
MANUFACTURER FOR THE INTENDED PURPOSE.
11. SMOKE DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER CONSTRUCTION CLEAN-UP
IS COMPLETED AND FINAL.
12. LOCATE SMOKE DETECTORS A MINIMUM OF THREE (3) FEET FROM MECHANICAL
DIFFUSERS. WALL -MOUNTED SMOKE DETECTORS SHALL BE LOCATED A MINIMUM OF
4" AND A MAXIMUM OF 12" FROM CEILING.
13. PROVIDE SYNCHRONIZATION OF ALL VISUAL NOTIFICATION APPLIANCE CIRCUITS.
PROVIDE ALL REQUIRED SYNC MODULES. PROVIDE A MULTI -SYNC MODE SLAVE
CONNECTION BETWEEN ALL SYNC MODULES.
14. VERIFY ALL FIELD SELECTABLE AUDIBILITY SETTINGS OF NOTIFICATION APPLIANCES
WITH FIRE ALARM CONTRACTOR.
15. UPON COMPLETION OF THE FIRE ALARM SYSTEM INSTALLATION AND PROGRAMMING,
THE INSTALLING CONTRACTOR SHALL PERFORM FINAL TESTING OF THE ENTIRE SYSTEM,
PER ALL APPLICABLE CODES, AND SHALL COORDINATE AND PERFORM A FINAL FIRE
ALARM SYSTEM INSPECTION.
16. PROVIDE OFF-SITE MONITORING AS REQUIRED BY THE INTERNATIONAL FIRE CODE,
SECTION 907.6.5 AND THE LOCAL AUTHORITY HAVING JURISDICTION.
17. INSTALLING CONTRACTOR SHALL, PHYSICALLY, LABEL ALL INITIATING DEVICES AND
NOTIFICATION APPLIANCE CIRCUIT END OF LINE (WHEN WIRING CLASS "B"). THESE
LABELS SHALL BE IN PLACE PRIOR TO START-UP AND TESTING.
///// \\\\\� • • JJI /I
-I 36" MIN. I-=
MANUAL
PULL I-5' MAX.
STATION
O
42"-48"
NOTE: MEASUREMENTS
SHOWN ARE TO THE
/y+E LI1J,`I� CLOSEST POINT OF
JJ JJl1�1J/1JJJ111JIJJJJl-l1JJl JJIIJJ_I_ DETECTOR
WALL -MOUNTED
CEILING MOUNTED SMOKE DETECTOR
SMOKE/HEAT
DETECTOR
i
DOOR WIDTH
-LESS 3=I
6"
MAGNETIC o
DOOR
HOLDER
SIDE WALL
FINISHED
/FLOOR tt
(/i>IIIIIIJJJIJ/IIIIII/IIIII/III m.ezII_IIIJII,II,III,,,,
,,,,JI JJJ//
/I//IIIIIIIJIJJIJ/JJJJII/I,,,,,,/JIIII,,,,,IIIIJI/1
FIRE ALARM DEVICE MOUNTING HEIGHTS
SCALE: NOT TO SCALE
FINISHED
WALL
Bra Signature
Date: 7/30/2018
Fire Protection Engineering
Technoly
Fire Alarm S ems
Cert. No. 1 751
Exp 5/1/2019
00
z
0
a
rJ
w
0
FOR REVIEW & APPROVAL
2
0
0
1253 S JACKSON ST. SEATTLE, WA 206-328-3288
shop drawings
created by:
5794 W.4600 So.
Hooper, UT 84315
Office: 801.985.0410
www.unicod.net
NBCA
71tin
Inc.
t
DANIA TU ILA
1251 ANDOVER PARK WEST
TU =` ILA, WA 98188
CALCULATIONS, DIAGRAMS, AND NOTES
DRAWN
CRL
UNICAD JOB #18461
CHECKED
BRADY B. HAWS
NICET III 138751
DATE
7/30/2018
REVISION
0
SCALE
1/16"=1'-0"
FA -2