HomeMy WebLinkAboutPP - 18000 ANDOVER PARK WEST - CONTINENTAL MILLS INC. - PERMITS AND PLANS18000 ANDOVER PARK WEST ASSOCIATED PERMITS 90-009 88-186 86-102 11-F-156 14-S-105 11-S-098 11-H-224 SITE LOCATION CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East Tukwila, WA 98188 206-575-4407 Date application accepted: FIRE PROTECTION SYSTEMS PERMIT APPLICATION Applications and plans must be complete in order to be accepted for plan review. **PLEASE PRINT** King Co. Assessor's Tax No.: -65 Z 304+ ' I Z Site Address: t O At4'40ovezQ €66.(2*- J t$ S -r Suite Number: Floor: t `► Z Tenant Name: GO14T t i-4 ES 14 "TO L h 1 LA x9 New Tenant? ❑ - Yes (X- No Property Owner's Name: s e C L it. PRO PIS (t.'' 16$ LLC. Mailing Address: CJS t1 Sit &A L. it PP ?.t D2 G ( ve4.4.7 tLA wa ,8 % 88 City State Zip CONTACT PERSON -if there are questions about the submittal. Name: 3 CZ`1 -4 . S4(A 11 .t..0 Company Name: FtRfL S''rSTeg--tS (-%-“S 5-T Day Telephone: 2 534 $33 • . 248 Mailing Address: Z ofv F(-14.)1-4%0cCaaig- (ZO•LC t -k so c-t(L G (7Pac %FIL top. ,8047 City State Zip E-mail Address: 04-tJ evC S`tS•tcsrt wgZ<ST•cati Fax Number: 2S3- 735'. O tt3 Valuation of Project (contractor's bid price): $ % 3, 940 «' Scope of Work (please provide detailed information): 0'*00 .V'`t E ' e.tSFri1,---Ko S•P(ZA.-6.1L L. trot, S -r S-Tt tri t=o(L d' 4r.. w -T. . T... PERMIT APPLICATION NOTES Value of Construction - In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules. Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILDING OWNER OR AUTHORIZED AGENT: ea -c7,., s Print Name: 0, V (Pa -4 5.. 3-p..Q.+6.c'"tt k.s.-Z) Signature: Plan Permit App.doc Date: 4 /z. 1"/(,k. Day Telephone: 25--- • 23-'3- t ZQ$ 5/14/10 TFD FP Form 8 SITE LOCATION CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East Tukwila, WA 98188 206-575-4407 Date application accepted: FIRE PROTECTION SYSTEMS PERMIT APPLICATION Applications and plans must be complete in order to be accepted for plan review. Site Address: 18000 Andover Park West **PLEASE PRINT** ( APR 302014 T-LIYKV ntAW1 E1- King Co. Assessor's TaxNo.: 3523049055 Tenant Name: Continental Mills - Innovation Center Suite Number: 140 Floor: 1 Property Owner's Name: Continental Mills New Tenant? ❑ - Yes x❑ - No Mailing Address: PO Box 88176, Seattle WA 98138-2176 CONTACT PERSON -if there are questions about the submittal. Permit contact- Janet Stebbins Name: Project work- Alan Mahaffie Company Name: SimplexGrinnell City State Zip Permit/Janet: 206-291-1468 Day Telephone: Work/Alan: 206-291-1481 Mailing Address: 9520 10th Ave S, Suite 100 Seattle WA 98108 City State Zip E-mail Address: iastebbins@simplexgrinnell.com Fax Number: 206-291-1500 Total number of new/relocated devices or sprinkler heads: 2 Valuation of Project (contractor's bid price): $ 1946.00 Scope of Work (please provide detailed information): Relocate (2) pendent sprinklers. PERMIT APPLICATION NOTES Value of Construction - In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules. Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILDING OWNER OR AUTHORIZED AGENT: Print Name: Janet Stebbins/SimplexGrinnell Plan Permit App.doc Date: 4/30/14 Day Telephone: 206-291-1468 I/2/13 TFD FP Form 8 410,1 4tt SITE LOCATION CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East Tukwila, WA 98188 206-575-4407 Date application accepted: FIRE PROTECTION SYSTEMS PERMIT APPLICATION Applications and plans must be complete in order to be accepted for plan review. **PLEASE PRINT** King Co. Assessor's Tax No.: 3523049055 Site Address: 18000 Andover Park West Suite Number: Floor: Tenant Name: Continental Mills- North Annex New Tenant? ❑ - Yes ❑x - No Property Owner's Name: Continental Mills, Inc. Mailing Address: PO Box 88176, Seattle WA 98138-2176 CONTACT PERSON -if there are questions about the submittal. Name: Janet Stebbins Day Telephone: 206-291-1468 Company Name: SimplexGrinnell Mailing Address: 9520 10th Ave S, Suite 100 E-mail Address: lastebbins@simplexgrinnell.com City State Zip City State Zip Fax Number: 206-291-1500 Valuation of Project (contractor's bid price): $ 3655.00 Scope of Work (please provide detailed information): Re—pipe existing kitchen hood system. (25) nozzles. PERMIT APPLICATION NOTES Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules. Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILDING OWNER OR AUTHORIZED AGENT: Signature: Print Name: 1").."94‘-r- M.1e// Date: 9/28/11 Janet Stebbins/SimplexGrinnell Plan Permit App.doc Day Telephone: 206-291-1468 5/14/10 TFD FP Form 8 1 FIRE DEPARTMENT HOOD SUPPRESSION PLAN REVIEW COMMENTS Project Name: Continental Mills 18000 Andover Park West 11-H-224 October 3, 2011 Permit No.: Date: Reviewer: Al Metzler Fire Protection Project Coordinator (206) 575-4407 option # 2 (Inspection Requests) (206) 971-8718 (Plan Review Questions) • Nozzle heights above appliances to be per manufacturers installation guidelines. • Fryers shall be installed with at least a 16 inch space between the fryer and surface flames from adjacent cooking equipment or a minimum 8 inch high steel or tempered glass baffle plate shall be installed between the appViances. • Upon activation of the suppression system, the make-up air supply will shut off and the exhaust will keep running. • Type 1 hood systems shall be designed and installed to automatically activate the exhaust system whenever cooking operations occur. The activation of the exhaust system shall occur through an interlock with the cooking appliances, by means of heat sensors or by means of other approved methods. • Activation of the suppression system shall shunt all electrical power under the hood as well as the gas supply. • Install a "K" rated portable fire extinguisher within 30 ft. of the cooking equipment. • The hood suppression system shall be monitored by a U.L. Central Monitoring Station. • The suppression system manual pull station shall be located no closer than 10 ft. and no farther than 20 ft. from the cooking equipment and be placed at a height of 42 to 48 inches above the floor. • The inside lower edge of the hood shall overhang or extend a horizontal distance of not less than 6 inches beyond the edge of the top horizontal surface of the appliance on all open sides. The vertical distance between the front lower lip of the hood and such surface shall not exceed 4 feet. • If cooking appliances are wheeled, the appliance wheels shall be set in tracks permanently mounted to the floor to ensure appliance is returned to original location if moved for cleaning or maintenance. FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Continental Mills 18000 Andover Pk W Permit No.: 11-S-098 Date: May 9, 2011 Reviewer: Al Metzler Fire Protection Project Coordinator (206)971-8718 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ` of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 20 or more sprinkler heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to any sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2010 Edition. ItIOTU:1.LA Central Permit Sysn ntroi No. Permit .No: ; FINAL APPROVAL FORM C TO: 0 Building 0 Planning ❑ Public Works l Fire Dept. ❑ Police ❑ Parks / Recreation Project Name fe A /P c'i e gri--- /�N �G✓moi / t f , Address Type of Permit(s) rT This project is nearing completion. Please investigate your area of responsibility and indicate below either your final approval or necessary corrections. If no response is received within one week, it will be assumed that the project is of no con to your department and a certificate of occupancy may be issued. This project is NOT approved by this department; the following corrections are necessary:; ( ) ( ) h1fry EAG '4v-) e ) ) /Ap« //w,) 0.00.1e -I/19 ) ) ) ) ) ) Authorized Signature Date This project is approved by this department: Authorized Signature C n ITY OF TUJILA Central Permit System (SCofltroi No. 9: Permit No. 5- 3z FINAL APPROVAL FORM °CT TO: 0 Building 0 Planning ❑ Public Works Fire Dept. ❑ Police ❑ Parks / Recreation C Project Name Sc /' ��/ t' y ( 6'G ) Address /k--4 A•..�G��'/�'� U!e S t 1 Type of Permit(s) T/ This project is nearing completion. Please investigate your area of responsibility and indicate below either your final approval or necessary corrections. If no response is received within one week, it will be assumed that the project is of no concern to your department and a certificates ioccupancy ay be issued. This project is NOT approZi by this department; the following correctio re necessary: () () () () () () () () () () fivirkW / n c -/PJ ' ek.-t ��✓% g' �1� Authorized Sign'ature Date This project is approved by this department: Author ze Signature Date CPS Form 3 0 City of Tukwila Fire Department Hubert H. Crawley Fire Chief. FILE +++++++++++*++++++++++++ CORRECTION NOTICE +++++++++++++++++++++++++ FIRM: TYPE OF INSPECTION ,'I -'L/ ADDRESS: i kG u ^ 11~CCUPANCY CLASS z WG /!/' CONTRACTOR: DATE: / /144'-/c TIME: 00i r� . / /<-c' Discrepancy and Action Required 1‘5'e 5- /4 ,G/) c/t 14F' .St%ate 5 ✓Gi WARNING . If the above listed item() are not corrected b the below listed date a citation for Fire Code violation will be issued. Correction of tle above items is required by: a 94 Any overlooked hazardous condition and/or violation of the Fire Prevent- ion Codes of the City of Tukwila does not imply approval of such condit- efor violation. Page r 7.:c---s--z----"' -1-7(..„.?of � Inspecting Officer: /'' . r TFD Form FP 11 Title: City of Tukwila Fire Department, 444 Andover Park East, Tukwila, Washington 98188 (206) 575-4404 10'6" Single Bank Hood 1 36"x24" 12"x18" Oven Oven Oven Oven Broiler(1N) Griddle (1N) (1) A single 2W nozzle protects 100" perimeter or 23" diameter duct. (2) A single 1N nozzle protects 10 linear ft of single bank plenum. (3) A single 1N nozzle can protect a griddle: maximum cooking area of 1080 square inches with a max longest side of 36". Located on perimeter 35"-40" above surface aimed at center. (4) A single 1N nozzle can protect a broiler: maximum length of 36" and total cooking are not to exceed 864 square inches. Located 15"-40" above hazard aimed at center. Hood size 10'6" single bank style with 12"x17" duct opening. Customer currently has 6 gallon Ansul R102 system with fire alarm and electrical tie ins for electric gas valve and shunts. ACCEPTED El Without Comments ❑ As Noted in Red Per The Attached Letter These plans have been reviewed by The Tukwila Fire prevention Bi ireau fo ,itorrnance with current City standards. Accep._» is sub ect to errors and omissions which do not = 1 1�('6" single bank hood -♦ ingle bank hood C a) 0 C a) 0 a) 0 N X 00 N w r 10'6" single bank hood —1110. 10'6" single bank hood —1110 00 r-1 X 00 e-1 16%x13''A PAID SEP 3 0 2011 TUKW.ILA FIRE -A` zo, s 00 m C 0 N 13 a) a) E 0 C 0 03) -i-_.lD -0 a) ,M a) N C O E ao a) -- CO 0 o -.2.s.7 •` 0) N 4., 0 CU _0 a) E a) co to •L -0 C a) C O O iZ fa LI? X C C 0 o Ea) t -0 (0 03 N 0) .I- •1moi 40 O 3 0 N o in v > c 0 a) N 0 c0 (0 O 0 32 f70 M 0 7 cu H a N a) 0) 0 -0 i, -0 C 0 '- X 00 O '-I (0 0 Q 0 O iN-I N 1 co To CO 00 o a) la CIO sX tr. CC -0 O_ O C 00 a) C Y Y N O c 2 0 0 •N N c9 R 0 a, -0 dD a) u E u _O C E ` .~ 7 W. C h012 7 a) ` C. C o E C Zr.) ai vii - ' U X 0 co N O E.v z E E Ycc E hi 7 C aJ co •X -0 O E co _D H O .0 '0 _ COXO C E C ca Q O ti4 E ao O� ° c0 0 c0 ' n O CO i U la CO O vi N Q 4-. 0 O O O O� H Q _ Q > 0_ N O — (o N 3.3 co m c a) O a) O i, 1.4 N O VCN0 ^ HN N vN ` 00C 0L C c C I(c 3 z z mz 0- 0 N I-1 N r -I v a a, a) v aa)) •y E C C C C C E C -0 O N N •N O N N 0 7 < < < '0 < O. < 2 0 -1 N m. II) WASHINGTON SURVEYING AND RATING BUREAU 300 MARKET PLACE ONE 2001 WESTERN AVENUE SEATTLE, WASHINGTON 98121-2190 November 23, 1988 PLAN SHEET 1 OF 1 SUBJEC1 Key Bank Segale Bus Park, Bldg #862 18010 Southcenter Parkway Tukwila, WA. The attached plans have been approved as meeting requirements for classification as a sprinklered risk. The following revisions or additions to the design as shown would qualify the protection for improved rates based upon information shown on these plans: Wet pipe sprinkler equipment is acceptable subject to provision of a thermostatically controlled heating system capable of maintaining temperatures at not less than 40 degrees F in all spaces containing wet pipe sprinkler equipment. 1. Piping and sprinklers do not seem to correspond with Wormald plans, dated 10-20-86. 2. Revise pipe sizes as noted in red pencil on plans. 3. Extend sprinkler protection to vault. 4. Clamp hangers should be provided with retaining straps as specified by article 3-10.3.5.10 of N.F.P.A. #13, 1987. 5. Provide details of fabrication of pipe. All threads in Allied tube should be gauged. 6. All piping, valves and fittings should be listed and labeled by UL for fire service, installed, tested and flushed in accordance with NFPA Standards. APPROVED BY VIKANSIONATugswASH. IO BUREAU :: C, ?:: 19 g nnKlered on the attached laps as ps meeting applies to plans or additions as ccept Acceptance recommended PP requirements of this Bureau for classification .uctem changes ...uad rates. ►,own thereon. 0 0 } cr 1- z u LL 0 z 0 u) N a 1- 0 gia 2 0 } z --a ;z W W 1-- 0 z > a 1— . W 1-- z O z 0 Q O 0 W W N W ac N 1- -s cs J J Q k 4 roWo.., ano u�, � Lance. sheet(s) W�a�reforLconstruction submitted 7ect to inspection for final acceptance. to [elffiiP� sta'lation sub, Acte s:.^.�s,Yz}f �e not ti r gMar•.or'irs retst �,t: l kher ds „„ r Ari r ;;,v,r r l;, itra! lr- +:•.z•�; tor p 'e P Which m 4, ditec �, , •Lye iv ` yti v- i.4 t rsont be const13 2 to :ac ;. it ra. injury or s,;it ease. testa in loss 62, S` 4 GENERAL NOTES DESIGN Design is based on ordinary Hazard Pipe schedule per NFPA 13. Maximum head spaceing is 130 square feet per head. APPROVALS City of Tukwila Fire Department Washington Surveying and Rating Bureau PIPING A11 new piping is Allied "XL" pipe with threaded ends and cast iron screwed fittings. +'= . HANGERS 3/8" top beam clamps, 3/8 all thread rod, proved swivel ring hangers. :1 MEADS U.L. and F.M. ap- Existing pendent heads are 165 Central Model "H" recessed with chrome eschutcheons. STRUCTURE Existing structure is noncombustible with steel trusses. LEGEND — — —Existing piping. New piping. R ® New location of pendent head. Existing upright and pendent ort the same fitting. (� Existing upright. ® Existing pendent. New pendent. KEY 8APJt4 / • /o -D /0-0 /"d 0 t t / I4• / ,I 4 1U -o t,i / /010 ' 6_0 MEN FE:7,TRa0; \ REMJJUE11 EXIST`�� PL V CJ J, E L- V. MA 'H. WOME.UT R TRI i/TELE VAULT TO I,U FP.A CDRR J DJ REMGVE EXIST- l"PLUG -' //`h'-1110....-;_rtwAimrimmigr...;;;74 - .\ KEY BANK 0 HAFT IST FLOOR PLAN `SCALE 1/8 1-0 NORTH 11 1 v =�x • PAQK - Q EVAN BLACK ' DR BAKER-eLVP — pt z ..- ‹ 164T11ST }' S 16STH "-1ST I cn STRANDER 26 BLVD L z� 0 z w -81C c 1 '..x. TRECK DR z INDUS or• > < ,,pl-Py 1 0 Q 1 6 FS CORP RATE DR N CORPORATE •—---- OR S -- -- CDMLIUNLZY_.ttPLAfdD bR HEALTH • EMERGENCY CENTER 4 -- MIDLAND Qin, -r I r SAXON' ,DR TR1LAND DR JOBSITE 180TH D DR 1 Y 0 SITE PLAN ISSUED FOR CONSTRUCTION RivERS!pE DRQ - 4 11a Iffy /. „ is -17.27 /1-71-88 Z�5 REVISIONS: 0 W O cca N CO 00 z J co SOUTHCENTER PARKWAY O 1 co 1 TUKWILA , WA. 98138 H.V.A.C., PIPING, PLUMBIN ENERGY MANAGEMENT & FIRE PROTECTION I1cCtI-STRV MECHANICAL ENGINEERS AND CONTRACTORS 855 S. BARTON ST. P.O. BOX 24567 SEATTLE, WA. 98124 223-01 #MC -KI -N -372ND (206) 762-3311 DRAWN BY: L.B. ; S "71-7, CHECKED BY: B.T. o(, 9 3 /' DATE: /1-11-28 PROJECT: PROJECT NUMBER: 0 7S TITLE: °{ E SHEET: FP -1 oF1 • • 1 1 • KEY BANK ANALOG R v 0 0 y co Lu _ F - O t - _ F- - 3 2 it 0 z 4 z 0_ t F -! - - —t EkV. MACH. __1_, 2 - !t_ T / 4 k0 L _ }6} 1,0Es8Y r • GENERAL NOTES DESIGN r f � TO i FPA /3 jr ELECT TEE E CO RiOOP r —, F I r CORR I FSO -' REMOVE EXl $T_ L"PLU�r_, r = t ._ i -1E • 4 i Y- i _ f' 1 4v, + - -1_ cl_‘1_:r: - -- - i - 4 f -- _ _ -v.-- 4 i 1 ' V j 1 4- Design is based on ordinary Hazard Pipe schedule per NFPA 13. Maximum head spaceing is 130 square feet per head. APPROVALS City of Tukwila Fire Department Washington Su.veying and Rating Bureau PIPING All new piping is Allied ''XL" cast iron screwed fittings. HANGERS pipe with threaded ends and 3/8" top beam clamps, 3/8 all thread rod, U.L. and F.M. ap- proved swivel ring hangers. HEADS Existing pendent heads are with chrome eschutcheons. 165 Central! Model STRUCTURE Existing structure is noncombustible LEGEND — -- — Existing piping. New piping. R® 0 4 New location of pendent head. Existing upright and pendent Existing upright. Existing pendent, New pendent. "H" recessed With steel trusses. on ;the same fitting. KEY BANK 0 r —E rZ t T Yt t t r IST FLOOR PLAN - SCALE 1/8 1-0 / r Z 0 m /go/ NORTH ACCEPTED WITHOUT COM MENTS. AS NOTED IN RED ID PER THE ATTACHED LETTER The drawings affixed hereto have been reviewed and accepted by the City of Tukwila Fire Dept Additions. deletions or revisions to these drawings after this date will void this acceptance and will require a resubmittal of revised drawings - Final acceptance is subject to field - inspection by a representative of this department At- SA- P16 -4-i EvAN BLACK CC CITY OF TUKWILA 575-4407 TUKWILA FIRE DEPARTMENT Please call: 575.4407 and give this job - Lnd address for shut4 down or restoration approval. FILE ILO/ 3 kzkL FS 1 MINKLER BLVD: cc sAxow 10R -4 • 1 • 0 DR 1 NC CC 1 CC 0 art SITE PLAN ISSUED FOR CONSTRUCTION ST RIVERSIOE SEGALE BUSINESS PARK ILI cc a. CV CO 0 CO Nr— H.V.A.C., PIPING, PLUMBING, ENERGY MANAGEMENT & FIRE PROTECTION MECHANICAL ENGINEERS AND CONTRACTORS 855 S. BARTON ST. P 0. BOX 24567 SEATTLE, WA. 98124 223-01 #MC-KI-N-372NO (206) 762-3311 CHECKED BY: DATE. 11-11-88 PROJECT. PROJECT NUMBER. TITLE: KEY mi SHEET: FP -1 OF - MEALS RESTROOM E - WOMLNS RESTR©DAN CO RiOOP r —, F I r CORR I FSO -' REMOVE EXl $T_ L"PLU�r_, r = t ._ i -1E • 4 i Y- i _ f' 1 4v, + - -1_ cl_‘1_:r: - -- - i - 4 f -- _ _ -v.-- 4 i 1 ' V j 1 4- Design is based on ordinary Hazard Pipe schedule per NFPA 13. Maximum head spaceing is 130 square feet per head. APPROVALS City of Tukwila Fire Department Washington Su.veying and Rating Bureau PIPING All new piping is Allied ''XL" cast iron screwed fittings. HANGERS pipe with threaded ends and 3/8" top beam clamps, 3/8 all thread rod, U.L. and F.M. ap- proved swivel ring hangers. HEADS Existing pendent heads are with chrome eschutcheons. 165 Central! Model STRUCTURE Existing structure is noncombustible LEGEND — -- — Existing piping. New piping. R® 0 4 New location of pendent head. Existing upright and pendent Existing upright. Existing pendent, New pendent. "H" recessed With steel trusses. on ;the same fitting. KEY BANK 0 r —E rZ t T Yt t t r IST FLOOR PLAN - SCALE 1/8 1-0 / r Z 0 m /go/ NORTH ACCEPTED WITHOUT COM MENTS. AS NOTED IN RED ID PER THE ATTACHED LETTER The drawings affixed hereto have been reviewed and accepted by the City of Tukwila Fire Dept Additions. deletions or revisions to these drawings after this date will void this acceptance and will require a resubmittal of revised drawings - Final acceptance is subject to field - inspection by a representative of this department At- SA- P16 -4-i EvAN BLACK CC CITY OF TUKWILA 575-4407 TUKWILA FIRE DEPARTMENT Please call: 575.4407 and give this job - Lnd address for shut4 down or restoration approval. FILE ILO/ 3 kzkL FS 1 MINKLER BLVD: cc sAxow 10R -4 • 1 • 0 DR 1 NC CC 1 CC 0 art SITE PLAN ISSUED FOR CONSTRUCTION ST RIVERSIOE SEGALE BUSINESS PARK ILI cc a. CV CO 0 CO Nr— H.V.A.C., PIPING, PLUMBING, ENERGY MANAGEMENT & FIRE PROTECTION MECHANICAL ENGINEERS AND CONTRACTORS 855 S. BARTON ST. P 0. BOX 24567 SEATTLE, WA. 98124 223-01 #MC-KI-N-372NO (206) 762-3311 CHECKED BY: DATE. 11-11-88 PROJECT. PROJECT NUMBER. TITLE: KEY mi SHEET: FP -1 OF t s - 1 r - 1 • I Ems« - t Icitm 4-- ,. 1`4i1 _ Z - S iz i-7 3-11 l I 114 tr � 'It1. 114 ?—!1 I 4* r4� * tock. ?t 7—'i coL c p'r -t Z-8 1-47i `i -Q 4-7�t- f { N4vtf WAa_ =...: ,r i__ > - - ---_ w- 1_ :3\TT G,T,1..; HOE �1N1 j - 1.-- — - _ _ 5 - TO NEW LOCA1101,1 Q 4 14 -16 I 1`Qt, 7-$L A VED a.. rataati lg or ati L,J.aau of Fire P.evention. Aid,tiacs or to these drawings after this date shall not be construed as being approved or review d. - CITY OF TU ILA BUREAU OF FIRE PREVENTION REVILE) Oh -Z5-60 UtiT FM HEW OlklEALIC115 FIRE PREVENTION SYSTEMS, INC. 6E32-6316 SEATTLE * WASH., 9E1109 Offices: Seattle -Anchorage - Fairbanks HOS THIS SHT JOB NO DWG NO DRAWN - — DATE SCALE iCk a K� f £ Y r- 3- z k t # 2 COACH SCREW, ROD & RING # 3 CEILING PLATE_ ROD & RING # 4 EYE ROD WOOD SCREW & RING # 7 POWDER DRIVEN STUD ROD & RING • $ 1- 7 11. i i # 10 TOP BEAM C CLAMP ROD & RING -# 12 SIDE BEAM BKT ROD & RING -# 13 SHORTCLIP SPRINKLER HEAD SYMBOLS UPRIGHT ON LINE PENDENT ON LINE - UPRIGHT ON STUB UP 0 DRY PENDENT SIDEWALL - 9 UPR &PEND ON DROP • 41 OW 'UV NEW Oitti..tr 4 --;ZZA\1\ SPRINKLER DESCRIPTIONS TYPE SYM TEMP QTY TAL APPROVALS& INSPECTION 2 4t-Wit4; far) 3 4 _ WATER DEPT ADDRESS PHON COPIES CONTRACT WITH - ADDRESS CITY PHONE ARCHITECT ADDRESS 13 FIRE PREVENTION - SYSTEMS, INC - — APPROVED The drawings affixed hereto have been reviewed and accepted as meeting or exceeding MIMMUM requirements of the City of Tukwila Fire Dept , Btareau of fire Prevention Additions -or revisions to tnese drawings after this date shaft not be construed as being approved or iew d CITY OF TU W1LA BUREAU OF FIRE PREVENTION PHONE PHONE - Ipia0114 --VJA 15tat) APPROVED BY SEATTLE WASH -11123 2 As meeting requirements of this Buread tor classification ac sprint—red however system changes Or additions as recommendPd on the e taotel sheet(s) will result in Improved ra es Acceptance appiteb tc. 1, t ds submitted and for construction and occupancy showi Mewl. t n srw.I All comments approvals and acceotances relate exclusivPly to relative effect of var a con,' rtr-tc u3on ft e Insurance rates ThPy are not to Injury or dam ige to -13 operty is recognized that hazards which mag result in loss sti exist K HOS THIS SHT e ji DRAWN DATE 6111,04 SCALE Nan cr 3-3 North Annex).cad DATE:04/15/11 TIMIE:15:38:09 -- SITE PLAN 0 10 20 30 40 50 L.1.. -1..1 1111 -J_1J SCALE 1' = 40' CONT.INENTAL'MILLS:TI INNOVATION'tENTER CONSTRUCtIQN T1fPg(I-B `' OCCUPAN CY'TyRE:"B': OFFICE' PPRQXIMATFLY'28,6OO SQ./FT: • 8" DCDA BACKFLOW IN VAULT (EXISTING) FIRE DEPARTIIIEN CONNECTION (EXISTING)I 0 .aFr��iale•' BUILDING CROSS SECTION SCALE: NO SCALE SITE SYMBOLS i:J111111111121111trr'trrrtrtr 00 PIPING BY FSW EXISTING PIPING PIPING BY OTHERS FIRE DEPARTMENT CONNECTION POST INDICATOR VALVE EXISTING FIRE HYDRANT GATE VALVE IN ROADWAY BOX -6- NEW FIRE HYDRANT FLOW TEST INFORMATION FLOW DATA PROVIDE BY: HIGHLINE WATER DEPT. STATIC PRESSURE 140 PSI RESIDUAL PRESSURE 133.6 PSI FLOWING: MIN 1500 GPM NOTE: PER HIGHLINE WATER DEPT, DESIGN PRESSURE REDUCED TO 80 PSI SCOPE OF WORK FIRE SYSTEMS WEST (FSW) WILL RELOCATE SPRINKLER ON ARM -OVERS ON AN EXISTING WET SPRINKLER SYSTEM FOR TENANT IMPROVEMENT IN A EXISTING BUILDING. CLARIFICATIONS -ALL AREAS PROTECTED BY A WET SYSTEM MUST BE MAINTAINED BY OTHERS AT A MINIMUM 40°F TO PREVENT FREEZING. EXCLUSIONS - PAINTING OR LABELING OF PIPE AND/OR EQUIPMENT - ELECTRICAL WIRING OF ANY KIND INCLUDING BUT NOT LIMITED TO WATERFLOW SWITCH, ELECTRIC BELL, AND TAMPER SWITCHES - CENTRAL STATION MONITORING EQUIPMENT, WIRING AND SERVICES -ALL UNDERGROUND BEYOND 5 FOOT OUT INCLUDING BUT NOT LIMITED TO:BACKFILL, SELECT FILL, BREAKING PATCHING, SAW CUTTING, LAWN REPAIR, LANDSCAPING, TREE REMOVAL, STERILIZATION, DEVELOPMENT FEES AND CITY CONNECTION. DESIGN CRITERIA PER NFPA 13 AND CITY OF TUKWILA OFFICE WET SYSTEM ORDINARY GROUP I HAZARD UNDERGROUND NOTES a' 1. ALL UNDERGROUND PIPING IS EXISTING AND BEYOND THE SCOPE OF THIS CONTRACT. FLOW TEST INFORMATION FLOW DATA PROVIDE BY: HIGHLINE WATER DEPT. STATIC PRESSURE 140 PSI RESIDUAL PRESSURE 133.6 PSI FLOWING: MIN 1500 GPM NOTE: PER HIGHLINE WATER Q 1N. ith,ot Comments 13 As Noted in Red i2' Per he Attached Letter These pians have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards. Acceptance is subject to errors and omissions which do riot authorize violations of adopted ;andards and ordinances. The responsibility for the adequacy of design rest totally with the designer. F':ddltions, deletion' or revisions to these drawings after tills date will void this accelptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwfia Fire Prevention Bureau. Date: 5- 9-1( By:�,. 511 o 4-. Ct.GcrS5 c",d, reify;. ". PaAeway r ' 8 — S& `-er ,Eur Lesr' y rr I�'.. FAmons; Gavlds raQ191-11>nrlw,a8 S 17th .St • Regal Parkway It , 1 Plaza 12 Nem -est t3 +S 18CIth St ' - til r — '--- Clr,ikoti J;III iI`nr .•• •'691 SQAa)a' .,.. nat:a`e,t�' Trlland Dr ' Cr,ollnaerstol DEPT, DESIGN PRESSURE REDUCED TO 80 PSI TUKWILA FIRE DEPARTMENT Please call 206-575-4407 and give i this si e - q $ac.ttiNo. and exact address for shut- down or restoration approval. NOTICE Weld stamps must be inspected before pipe is hung. Do not paint piping prior to hydrostatic test approval. ... -� Corporcr7fdn r-Sorltlltteittrr it 1• 1_x' C?&i �+i Home ti' S ,1$Oth Sf :office / JOB SIT Sugaie Park dr.15- 11) Les So1i4inb, Tire Center,: ' s' , 180th St t31dge ,_.,til.. = i 'r I;Hnv+al....GreA 11 'riviri;•plaoe' Si,KteS r1/.MHrr101t .c.>BN1ll& ',SOi.10,1 nitri 16 iti'zt+Ii 1 43rd St VICINITY MAP N.T.S. • b I� I� PAID ;Jw` MAY -5 2011 , .a�> TUKWILA FIRE t-(' Z 7-0 �S SITE PLAN 155 HANGER LEGEND TOTAL COUNT OF SPRINKLER HEADS FOR PROJECT REVISIONS GENERAL NOTES DESIGN CRITERIA AND NOTES SYM TYPE MFG MODEL ORIFICE THREAD TEMP FINISH CANOPY QTY MK DATE BY DESCRIPTION -- FILE:2-10-5712 Revision00 SSP TYCO TY -FRB 1/2" / 5.6K 1/2" 155" CHROME CHROME 243 HSW TYCO TY -FRB 1/2" / 5.6K 1/2" 155" CHROME CHROME 2 0 A A APPROVALS REQUIRED: DISTRIBUTION: AUTHORITY TUKWILA OWNER / ARCHITECT OWNER / ARCHITECT 1 FIRE SYSTEMS WEST 1 1. ALL MATERIAL AND EQUIPMENT TO BE NEW AND UNDERWRITERS APPROVED. 2. PIPING DIMENSIONS ARE CENTER TO CENTER EXCEPT RISER & DIMENSIONS SHOWN THUSLY (1'-6") WHICH ARE END TO END. 3.EARTHQUAKE BRACING SHALL BE PROVIDED IN ACCORDANCE WITH NFPA #13. 4 PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH NFPA #13. 5.PIPING SHALL BE IN ACCORDANCE WITH NFPA #13. 6. JOINING OF PIPE AND FITTINGS, THREADED AND WELDED SHALL BE IN ACCORDANCE WITH NFPA #13. 7. OWNER TO PROVIDE ADEQUATE HEAT TO PREVENT WATER IN PIPES FROM FREEZING IN AREAS PROTECTED BY WET PIPE SPRINKLER SYSTEM. 8. STRUCTURAL ADEQUACY OF THE BUILDING TO SUPPORT THE SPRINKLER PIPING IS THE RESPONSIBILITY OF THE OWNER OR HIS STRUCTURAL REPRESENTATIVE. 1. ALL NEW BRANCHLINE PIPING TO BE SCHEDULE 40 JOINED W/ BLACK CAST IRON FITTINGS (UNO). 2. ALL HANGERS AT CONCRETE SLABS TO BE HILTI KWIK BOLT II (UNO). 3. ALL PENDENT HEADS TO BE LOCATED IN CENTER OF TILES - CEILING TILE IS 2' X 2'. BUILDING PERMIT # CONTRACT NAME: CMI INNOVATION CENTER 18000 ANDOVER PARK WEST TUKWILLA WA 98188 CONTRACT WITH: GLY CONSTRUCTION 15 LAKE BELLEVUE DRIVE, SUITE 200 BELLEVUE WA 98008 CONTACT: BRYAN HAAKENSON Phone: (425) 451-8877 Fax: (425) 453-5680 F.ire Systems West 206 Frontage Road North, Suite C Pacific, WA. 98047 (253) 833-1248 Fax: (253) 735-0113 WA CL# FIRESWI 140B1 Q.C. FAB BY: Q.C. INSTALL BY: DESIGNER DATE JOB NUMBER SHEET B. JARAMILLO 04/15/11 2-10-5712 1 of 3 OFFICE OPEN \ OFFICE WALL " ;' , ' 'S �' "' ji , ` /. /// ! �/ DO s-2x4ACT CEILING OPEN O OFFICE OFFICE 1255) 2ss GLASS OFFICE 282 '' ICr F.F. 6" CONCRETE DYER 1.5' PAN DECK / ' / ' / ' %' / / T 'T TIIT' / M --r— MAIL/ • ,� '�i , �• \-2x4ACT CEILING LUNCHROOM r OFFICE HALL COPY 7// / , " ���i/ /' ,-` '; 144 187 185 184 /' /%/�� '; '% , i': /:! 1. //' , ,, ,/, // / /' BUILDING CROSS SECTION SCALE: NO SCALE SITE SYMBOLS i:J111111111121111trr'trrrtrtr 00 PIPING BY FSW EXISTING PIPING PIPING BY OTHERS FIRE DEPARTMENT CONNECTION POST INDICATOR VALVE EXISTING FIRE HYDRANT GATE VALVE IN ROADWAY BOX -6- NEW FIRE HYDRANT FLOW TEST INFORMATION FLOW DATA PROVIDE BY: HIGHLINE WATER DEPT. STATIC PRESSURE 140 PSI RESIDUAL PRESSURE 133.6 PSI FLOWING: MIN 1500 GPM NOTE: PER HIGHLINE WATER DEPT, DESIGN PRESSURE REDUCED TO 80 PSI SCOPE OF WORK FIRE SYSTEMS WEST (FSW) WILL RELOCATE SPRINKLER ON ARM -OVERS ON AN EXISTING WET SPRINKLER SYSTEM FOR TENANT IMPROVEMENT IN A EXISTING BUILDING. CLARIFICATIONS -ALL AREAS PROTECTED BY A WET SYSTEM MUST BE MAINTAINED BY OTHERS AT A MINIMUM 40°F TO PREVENT FREEZING. EXCLUSIONS - PAINTING OR LABELING OF PIPE AND/OR EQUIPMENT - ELECTRICAL WIRING OF ANY KIND INCLUDING BUT NOT LIMITED TO WATERFLOW SWITCH, ELECTRIC BELL, AND TAMPER SWITCHES - CENTRAL STATION MONITORING EQUIPMENT, WIRING AND SERVICES -ALL UNDERGROUND BEYOND 5 FOOT OUT INCLUDING BUT NOT LIMITED TO:BACKFILL, SELECT FILL, BREAKING PATCHING, SAW CUTTING, LAWN REPAIR, LANDSCAPING, TREE REMOVAL, STERILIZATION, DEVELOPMENT FEES AND CITY CONNECTION. DESIGN CRITERIA PER NFPA 13 AND CITY OF TUKWILA OFFICE WET SYSTEM ORDINARY GROUP I HAZARD UNDERGROUND NOTES a' 1. ALL UNDERGROUND PIPING IS EXISTING AND BEYOND THE SCOPE OF THIS CONTRACT. FLOW TEST INFORMATION FLOW DATA PROVIDE BY: HIGHLINE WATER DEPT. STATIC PRESSURE 140 PSI RESIDUAL PRESSURE 133.6 PSI FLOWING: MIN 1500 GPM NOTE: PER HIGHLINE WATER Q 1N. ith,ot Comments 13 As Noted in Red i2' Per he Attached Letter These pians have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards. Acceptance is subject to errors and omissions which do riot authorize violations of adopted ;andards and ordinances. The responsibility for the adequacy of design rest totally with the designer. F':ddltions, deletion' or revisions to these drawings after tills date will void this accelptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwfia Fire Prevention Bureau. Date: 5- 9-1( By:�,. 511 o 4-. Ct.GcrS5 c",d, reify;. ". PaAeway r ' 8 — S& `-er ,Eur Lesr' y rr I�'.. FAmons; Gavlds raQ191-11>nrlw,a8 S 17th .St • Regal Parkway It , 1 Plaza 12 Nem -est t3 +S 18CIth St ' - til r — '--- Clr,ikoti J;III iI`nr .•• •'691 SQAa)a' .,.. nat:a`e,t�' Trlland Dr ' Cr,ollnaerstol DEPT, DESIGN PRESSURE REDUCED TO 80 PSI TUKWILA FIRE DEPARTMENT Please call 206-575-4407 and give i this si e - q $ac.ttiNo. and exact address for shut- down or restoration approval. NOTICE Weld stamps must be inspected before pipe is hung. Do not paint piping prior to hydrostatic test approval. ... -� Corporcr7fdn r-Sorltlltteittrr it 1• 1_x' C?&i �+i Home ti' S ,1$Oth Sf :office / JOB SIT Sugaie Park dr.15- 11) Les So1i4inb, Tire Center,: ' s' , 180th St t31dge ,_.,til.. = i 'r I;Hnv+al....GreA 11 'riviri;•plaoe' Si,KteS r1/.MHrr101t .c.>BN1ll& ',SOi.10,1 nitri 16 iti'zt+Ii 1 43rd St VICINITY MAP N.T.S. • b I� I� PAID ;Jw` MAY -5 2011 , .a�> TUKWILA FIRE t-(' Z 7-0 �S SITE PLAN 155 HANGER LEGEND TOTAL COUNT OF SPRINKLER HEADS FOR PROJECT REVISIONS GENERAL NOTES DESIGN CRITERIA AND NOTES SYM TYPE MFG MODEL ORIFICE THREAD TEMP FINISH CANOPY QTY MK DATE BY DESCRIPTION -- FILE:2-10-5712 Revision00 SSP TYCO TY -FRB 1/2" / 5.6K 1/2" 155" CHROME CHROME 243 HSW TYCO TY -FRB 1/2" / 5.6K 1/2" 155" CHROME CHROME 2 0 A A APPROVALS REQUIRED: DISTRIBUTION: AUTHORITY TUKWILA OWNER / ARCHITECT OWNER / ARCHITECT 1 FIRE SYSTEMS WEST 1 1. ALL MATERIAL AND EQUIPMENT TO BE NEW AND UNDERWRITERS APPROVED. 2. PIPING DIMENSIONS ARE CENTER TO CENTER EXCEPT RISER & DIMENSIONS SHOWN THUSLY (1'-6") WHICH ARE END TO END. 3.EARTHQUAKE BRACING SHALL BE PROVIDED IN ACCORDANCE WITH NFPA #13. 4 PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH NFPA #13. 5.PIPING SHALL BE IN ACCORDANCE WITH NFPA #13. 6. JOINING OF PIPE AND FITTINGS, THREADED AND WELDED SHALL BE IN ACCORDANCE WITH NFPA #13. 7. OWNER TO PROVIDE ADEQUATE HEAT TO PREVENT WATER IN PIPES FROM FREEZING IN AREAS PROTECTED BY WET PIPE SPRINKLER SYSTEM. 8. STRUCTURAL ADEQUACY OF THE BUILDING TO SUPPORT THE SPRINKLER PIPING IS THE RESPONSIBILITY OF THE OWNER OR HIS STRUCTURAL REPRESENTATIVE. 1. ALL NEW BRANCHLINE PIPING TO BE SCHEDULE 40 JOINED W/ BLACK CAST IRON FITTINGS (UNO). 2. ALL HANGERS AT CONCRETE SLABS TO BE HILTI KWIK BOLT II (UNO). 3. ALL PENDENT HEADS TO BE LOCATED IN CENTER OF TILES - CEILING TILE IS 2' X 2'. BUILDING PERMIT # CONTRACT NAME: CMI INNOVATION CENTER 18000 ANDOVER PARK WEST TUKWILLA WA 98188 CONTRACT WITH: GLY CONSTRUCTION 15 LAKE BELLEVUE DRIVE, SUITE 200 BELLEVUE WA 98008 CONTACT: BRYAN HAAKENSON Phone: (425) 451-8877 Fax: (425) 453-5680 F.ire Systems West 206 Frontage Road North, Suite C Pacific, WA. 98047 (253) 833-1248 Fax: (253) 735-0113 WA CL# FIRESWI 140B1 Q.C. FAB BY: Q.C. INSTALL BY: DESIGNER DATE JOB NUMBER SHEET B. JARAMILLO 04/15/11 2-10-5712 1 of 3 First Floor North Annex).cad DATE:04/15/11 TIME:15:39:48 -- 0 0 c .0 0-5712 Revi 5 0 r--1 - 1 -1 97 "+: OQ r 2 112 41z7"1• 14 10'.1 -.211':" Q�ALIrY pb �IUAL(TY M DiUM OFFICI .;-''+ SMALL OFFICE 114 i 111 .ti SPECIAL SERVICESa 4 %. _ WORKROOM P•+ F;, O� PEN OFFII 2j mom= 11 CR .ATI ('VICES 0 OPEtI OFFICE WAITINGICAFE 1IEDIUri R&P MEDIUM 'OFFICE - 1001 1002 CROSSHATCHED AREA NOT IN CONTRACT FITTER PLEASE NOTE: 1. ALL NEW CEILINGS ARE AT 9'.O" AFF 2. ALL HANGERS MUST BE NO MORE THEN 12" FROM END OF PIPE. � J 2 0-4Y2 2 I= 0.2'hl N l+tib ti • 2 1-4'/: 2" AGF TEST & DRAIN VA. 8" WATERFLOW INDICATOR 8" BFY. VA. wl BUILT-IN TAMPER SWITCH PIPE DRAIN TO EXISTING CONNECTION REVISED SYSTEM RISER DETAIL SCALE: 1/2"=1-0" FIRST FLOOR REMOTE AREA LEVEL 1 SPRINKLER PLAN -INNOVATION CENTER SCALE: 118" = 1'-0" Design Basis Occupancy: Total Sprinklers: Number Of Sprinklers Calculated: K -Factor: Orifice Size: Design Density: Average Density: Area of Application: Demand at Base Of Riser or Point Of Connection Total Demand Flow(gpm): Pressure(psi): Water Supply Information At Time Of Design Static Pressure(ps1): Residual Pressure(psi): Supply Flow(gpm): Total Demand Flow(gpm): Total Demand Pressure(psi): First Floor - Ordinary Group I 161 19 5.6 0.5 0.15gpmift2 0.26gpmfft2 1500,001t2 (Actual 1591.51ft') 408.04 31.66 80.00 73.60 1500.00 658.04 42.06 TYPICAL DROP DETAIL NO SCALE 1ST FLOOR HANGER LEGEND SPRINKLER HEADS REVISIONS GENERAL NOTES DESIGN CRITERIA AND NOTES SYM TYPE MFG MODEL ORIFICE THREAD TEMP SSP TYCO TY -FRB 1/2"/5.6K 1/2" 155* FINISH CHROME CANOPY CHROME QTY 142 MK DATE BY DESCRIPTION 0 SSU EXIST 0 A A APPROVALS REQUIRED: OWNER / ARCHITECT DISTRIBUTION: TUKWILA OWNER / ARCHITECT FIRE SYSTEMS WEST 1. ALL MATERIAL AND EQUIPMENT TO BE NEW AND UNDERWRITERS APPROVED. 2. PIPING DIMENSIONS ARE CENTER TO CENTER EXCEPT RISER & CIMENSIONS SHOWN THUSLY (1'-6") WHICH ARE END TO END. 3.EARTHQUAKE BRACING SHALL BE PROVIDED IN ACCORDANCE WITH NFPA #13. 4. PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH NFPA #13. 5.PIPING SHALL BE IN ACCORDANCE WITH NFPA #13. 6. JOINING OF PIPE AND FITTINGS, THREADED AND WELDED SHALL BE IN ACCORDANCE WITH NFPA #13. 7. OWNER TO PROVIDE ADEQUATE HEAT TO PREVENT WATER IN PIPES FROM FREEZING IN AREAS PROTECTED BY WET PIPE SPRINKLER SYSTEM. 8. STRUCTURAL ADEQUACY OF THE BUILDING TO SUPPORT THE SPRINKLER PIPING IS THE RESPONSIBILITY OF THE OWNER OR HIS STRUCTURAL REPRESENTATIVE. 1. ALL NEW BRANCHLINE PIPING TO BE SCHEDULE 40 JOINED Wl BLACK CAST IRON FITTINGS (UNO). 2. ALL HANGERS AT CONCRETE SLABS TO BE HILTI KWIK BOLT II (UNO). 3. ALL PENDENT HEADS TO BE LOCATED IN CENTER OF TILES - CEILING TILE IS 2' X 2'. BUILDING PERMIT # CONTRACT NAME: CMI INNOVATION CENTER 18000 ANDOVER PK W TUKWILA WA 98188 CONTRACT WITH: GLY CONSTRUCTION 15 LAKE BELLEVUE DRIVE, SUITE 200 BELLEVUE WA 98005 PROJECT MGR BRYAN HAAKENSON Phone: (425) 451-8877 Fax: (425) 453-5680 Fire Systems West 206 Frontage Road North, Suite C Pacific, WA. 98047 (253) 833-1248 Fax: (253) 735-0113 WA CL# FIRESWI 140B1 Q.C. FAB BY: Q.C. INSTALL BY: DESIGNER DATE JOB NUMBER B. JARAMILLO 04/15/11 2-10-5712 SHEET 2 of 3 112" KWIK BOLT • a . 71' v a • • 4 ° '. .b • Al 112' KWWIK BOLT //////////// ////// // ,/ /i TOLCO FIG. 980 SWAY BRACE END /), ii CONC DECK f FLAT OR CORK _ TOLCO FIG. 980 SWAY BRACE END ta _;y WEDGE ANCHOR W/ ROD COUPLING /1.1 1" BRACE PIPE @ 7'-0" 45 TO 69 DEG. /' 0/ TOLCO FIG. 980 1" BRACE PIPE © 7'-0" ,/o59DEG. TOLCO FIG. 1000 FAST CLAMP LATERAL SWAY CONCRETE CONNECTION *-- BRACE TYPE -CA ALL THREAD ROD JI1II RING HANGER 4u) • 4 -■ • SWAY BRACE END 00 O HANGER R WEDGE ANCHOR LONGITUDINAL CONCRETE -._- TOLCO FIG. 4A PIPE CLAMP SWAY BRACE CONNECTION TYPE -CA 2 0-4Y2 2 I= 0.2'hl N l+tib ti • 2 1-4'/: 2" AGF TEST & DRAIN VA. 8" WATERFLOW INDICATOR 8" BFY. VA. wl BUILT-IN TAMPER SWITCH PIPE DRAIN TO EXISTING CONNECTION REVISED SYSTEM RISER DETAIL SCALE: 1/2"=1-0" FIRST FLOOR REMOTE AREA LEVEL 1 SPRINKLER PLAN -INNOVATION CENTER SCALE: 118" = 1'-0" Design Basis Occupancy: Total Sprinklers: Number Of Sprinklers Calculated: K -Factor: Orifice Size: Design Density: Average Density: Area of Application: Demand at Base Of Riser or Point Of Connection Total Demand Flow(gpm): Pressure(psi): Water Supply Information At Time Of Design Static Pressure(ps1): Residual Pressure(psi): Supply Flow(gpm): Total Demand Flow(gpm): Total Demand Pressure(psi): First Floor - Ordinary Group I 161 19 5.6 0.5 0.15gpmift2 0.26gpmfft2 1500,001t2 (Actual 1591.51ft') 408.04 31.66 80.00 73.60 1500.00 658.04 42.06 TYPICAL DROP DETAIL NO SCALE 1ST FLOOR HANGER LEGEND SPRINKLER HEADS REVISIONS GENERAL NOTES DESIGN CRITERIA AND NOTES SYM TYPE MFG MODEL ORIFICE THREAD TEMP SSP TYCO TY -FRB 1/2"/5.6K 1/2" 155* FINISH CHROME CANOPY CHROME QTY 142 MK DATE BY DESCRIPTION 0 SSU EXIST 0 A A APPROVALS REQUIRED: OWNER / ARCHITECT DISTRIBUTION: TUKWILA OWNER / ARCHITECT FIRE SYSTEMS WEST 1. ALL MATERIAL AND EQUIPMENT TO BE NEW AND UNDERWRITERS APPROVED. 2. PIPING DIMENSIONS ARE CENTER TO CENTER EXCEPT RISER & CIMENSIONS SHOWN THUSLY (1'-6") WHICH ARE END TO END. 3.EARTHQUAKE BRACING SHALL BE PROVIDED IN ACCORDANCE WITH NFPA #13. 4. PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH NFPA #13. 5.PIPING SHALL BE IN ACCORDANCE WITH NFPA #13. 6. JOINING OF PIPE AND FITTINGS, THREADED AND WELDED SHALL BE IN ACCORDANCE WITH NFPA #13. 7. OWNER TO PROVIDE ADEQUATE HEAT TO PREVENT WATER IN PIPES FROM FREEZING IN AREAS PROTECTED BY WET PIPE SPRINKLER SYSTEM. 8. STRUCTURAL ADEQUACY OF THE BUILDING TO SUPPORT THE SPRINKLER PIPING IS THE RESPONSIBILITY OF THE OWNER OR HIS STRUCTURAL REPRESENTATIVE. 1. ALL NEW BRANCHLINE PIPING TO BE SCHEDULE 40 JOINED Wl BLACK CAST IRON FITTINGS (UNO). 2. ALL HANGERS AT CONCRETE SLABS TO BE HILTI KWIK BOLT II (UNO). 3. ALL PENDENT HEADS TO BE LOCATED IN CENTER OF TILES - CEILING TILE IS 2' X 2'. BUILDING PERMIT # CONTRACT NAME: CMI INNOVATION CENTER 18000 ANDOVER PK W TUKWILA WA 98188 CONTRACT WITH: GLY CONSTRUCTION 15 LAKE BELLEVUE DRIVE, SUITE 200 BELLEVUE WA 98005 PROJECT MGR BRYAN HAAKENSON Phone: (425) 451-8877 Fax: (425) 453-5680 Fire Systems West 206 Frontage Road North, Suite C Pacific, WA. 98047 (253) 833-1248 Fax: (253) 735-0113 WA CL# FIRESWI 140B1 Q.C. FAB BY: Q.C. INSTALL BY: DESIGNER DATE JOB NUMBER B. JARAMILLO 04/15/11 2-10-5712 SHEET 2 of 3 (6) NOT I CONTRACT AREA OF WORK iro '' .. - r ' ••••1 • n .•L.. 0,..........-r • •7 A ,_ A .11.1175:4 sa.--, mo(list -1,,, `. -- sca so t slim ass sa =ST s --- l'4 rb c:r szt 4.____ -------------- 1% ----,,-. - (Zig- No , C:ig.. •;i- SMALL OFFICE ITTER PLEASE NOTE: REPLACE ALL EXISTING PENDENT STANDARD RESPONSE SPRINKLERS WITH NEW QUICK RESPONSE PENDANT SPRINKLERS IN N.I.C. AREA. ...II I. 11111 SIM !kid - OFFICE 1 SAIIPLE LAB STORAGE OPEN 0 FIC Annir AIIIMIA11111.1111121111111M1111111/ LEVEL 2 SPRINKLER PLAN - INNOVATION CENTER SCALE: 1/8" = 1'-0" NOT IN CONTRACT AREA OF WORK CROSSHATCHED AREA NOT IN CONTRACT FITTER PLEASE NOTE: 1. ALL NEW CEILINGS ARE AT 9'-0" AFF 2. ALL HANGERS MUST BE NO MORE THEN 12" FROM END OF PIPE. SECOND FLOOR REMOTE AREA Design Basis Occupancy: Total Sprinklers: Number Of Sprinklers Calculated: K -Factor: Orifice Size: Design Density: Average Density: Area of Application: Demand at Base Of Riser or Point Of Connection Total Demand Flow(gpm): Pressure(psi): Water Supply Information At Time Of Design Static Pressure(psi): Residual Pressure(psi): Supply Flow(gpm): Total Demand Flow(gpm): Total Demand Pressure(psi): Second Floor - Ordinary Group I 202 23 5.6 0.5 0.15gpmlft2 0.35gpmfftz 1500.00ft2 (Actual 1501A1ft) 519.38 41.80 80.00 73.60 1500.00 769.38 52.44 TYPICAL DROP DETAIL NO SCALE 18 GA. METAL PAN DECK 318" X 4" ALL THREAD ROD ea 2 il 11116mmaiffionalit, 1.... 3/8" NUT1 AND WASHERS TYPICAL 2" AF ON FIG.552 TAPPED SIDE BEAM BRACKET OR LISTED EQUAL 318" ALL THREAD ROD 1" MAXIMUM ALLOWED PIPE SIZE PER NFPA 9.2.1.4 HANGER RING 1" MAXIMUM ALLOWED PIPE SIZE HANGER X SIDE BEAM BRACKET TO PAN DECK 2ND FLOOR HANGER LEGEND SPRINKLER HEADS REVISIONS GENERAL NOTES DESIGN CRITERIA AND NOTES SYM TYPE MFG MODEL ORIFICE THREAD TEMP FINISH CANOPY QTY MK DATE BY DESCRIPTION 0 SSP HSN TYCO TYCO TY -FRB 1Y -FRB 1/2" / 5.6K 1/2" / 5.6K 1/2" 155* 1/2" 155* CHROME CHROME CHROME 101 CHROME 2 A A SSP EXIST A A APPROVALS REQUIRED: DISTRIBUTION: AUTHORITY OWNER / ARCHITECT TUKWILA OWNER / ARCHITECT TOTAL 103 FIRE SYSTEMS WEST 1. ALL MATERIAL AND EQUIPMENT TO BE NEWAND UNDERWRITERS APPROVED. 2. PIPING DIMENSIONS ARE CENTER TO CENTER EXCEPT RISER & DIMENSIONS SHOWN THUSLY (1-6") WHICH ARE END TO END. 3. EARTHQUAKE BRACING SHALL BE PROVIDED IN ACCORDANCE WITH NFPA #13. 4. PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH NFPA #13. 5. PIPING SHALL BE IN ACCORDANCE WITH NFPA #13. 6. JOINING OF PIPE AND FITTINGS, THREADED AND WELDED SHALL BE IN ACCORDANCE WITH NFPA #13. 7. OWNER TO PROVIDE ADEQUATE HEAT TO PREVENT WATER IN PIPES FROM FREEZING IN AREAS PROTECTED BY WET PIPE SPRINKLER SYSTEM. 8. STRUCTURAL ADEQUACY OF THE BUILDING TO SUPPORT THE SPRINKLER PIPING IS THE RESPONSIBILITY OF THE OWNER OR HIS STRUCTURAL REPRESENTATIVE. 1. ALL NEW BRANCHLINE PIPING TO BE SCHEDULE 40 JOINED W/ BLACK CAST IRON FITTINGS (UNO). 2. ALL HANGERS AT CONCRETE SLABS TO BE HILTI KWIK BOLT II (UNO). 3. ALL PENDENT HEADS TO BE LOCATED IN CENTER OF TILES - CEILING TILE IS 2 X 2'. BUILDING PERMIT # CONTRACT NAME: CMI INNOVATION CENTER 18000 ANDOVER PK W TUKWILA WA 98188 CONTRACT WITH: GLY CONSTRUCTION 15 LAKE BELLEVUE DRIVE, SUITE 200 BELLEVUE WA 98005 PROJECT MGR BRYAN HAAKENSON Phone: (425) 451-8877 Fax: (425) 453-5680 Fire Systems West 206 Frontage Road North, Suite C Pacific, WA. 98047 (253) 833-1248 Fax: (253) 735-0113 WA CL# FIRESWI 140B1 DESIGNER B. JARAMILLO DATE 04/15/11 JOB NUMBER 2-10-5712 SHEET 3 of 3 o WithoutComments Fir As Noted in Red 0 Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards.' Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the iidequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings after this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to fleld test and inspection by The Tukwila Fire Prevention Bt eau. Date» ` V < ( By: / /VI TUKWILA FIRE DEPARTMENT Please call 206-575-4407 and give this Fire Permit No, and exact address for shut- down or restoration approval. -)( / 1f atevtce4 -lti &.‹ 1,0•,y,i add1...)j4Sit • Dis4e.1( 6rr4- L die ci4&.r o+, otedIcklecl FA c.(' c,id L 5 L�✓w�-i' ta-curers _ % 1.4' ho+ glvYa•li do+,.e , GAaKy.e o✓t' kt1Sw‘ h k ha ISche. NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. 1/1 111llillmilllo tp, ii,fi/ll I lie /i/illllllllllllllllihhllhI Fir tar an "If 1luuuu���� a equipment Supplled By Sins xGrinnei A Tyco International Company Project Contact Information Generic Project Information: Drawing/Engineering Information: Technician Scheduling: Blake Erickson Zack Olson Yvonne Thompson berickson@simpkkxgrirreIL.com zolson@simplexgrinnell.com ythompson@simplexgrinnell.com (206) 291-1415 (206) 291-1430 (206) 291-1450 PAID 1 UKVVILH FORE Simplexerinnell BE SAFE. ATyco International Company SimplexGrinnell 9520 10th Avenue South, Suite 100 Seattle, Wa. 98108 SALES: 206-291-1400 SERVICE: 206-291-1400 © 2002 3D PLEXGRINNELL IR FAX: 206-291-1500 ALL RIGHTS RESERVED DRAWING LIST CO 2 to 0 03 957065203 SHEET NAME DRAWING NAME ELECTRONIC DRAWING NAME INCLUDED IN THIS PROJECT FA—COV-01 TITLE SHEET FA—COVER X FA—COV-02 COVER SHEET FA—COVER X FA—RIS-01 RISER SHEET FA—COVER X FA—DET-01 DETAIL SHEET FA—COVER X FA—F-01 1ST FLOOR PLAN FA—FLOOR X FA—F-02 2ND FLOOR PLAN FA—FLOOR X Simplexerinnell BE SAFE. ATyco International Company SimplexGrinnell 9520 10th Avenue South, Suite 100 Seattle, Wa. 98108 SALES: 206-291-1400 SERVICE: 206-291-1400 © 2002 3D PLEXGRINNELL IR FAX: 206-291-1500 ALL RIGHTS RESERVED Q a CO 2 to 0 03 957065203 664 ez 5 0 1 A i 1a 0 REVIEW COMMENTS p02 mr- ..4> at FIRE ALARM SYSTEM TITLE SHEET CONTINENTAL MILLS CORP ANNEX 18000 ANDOVER PARK WEST TUKWILA, WA 98188 DATE: 10-29-2004 SITE/PROJECT NUMBER: 458-4058194/904390901 SHEET NUMBER: FA—COV-01 GENERAL FIRE ALARM SYSTEM NOTES 1) FIRE ALARM SYSTEM IS POWER LIMITED. METALLIC RACEWAY SHALL BE USED IF REQUIRED BY CODE, SPECIFICATIONS AND CONTRACT DOCUMENTS OR AHJ. 2) ALL RACEWAYS MUST BE FREE OF MOISTURE 3) REFER TO SIMPLEXGRINNELL FIRE ALARM DATA SHEETS FOR PROPER TYPE AND SIZES OF REQUIRED DEVICE MOUNTING ELECTRICAL BOXES. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR PROPER INSTALLATION OF ALL DEVICES. 4) AC VOLTAGE IS NOT PERMITTED IN THE SAME RACEWAY AS FIRE ALARM WIRING. 5) UNRELATED (NON -FIRE ALARM) WIRING SHALL NOT BE IN THE SAME RACEWAY AS FIRE ALARM WIRING. 6) ALL CONTRACTOR FIELD WIRING MUST ENTER ALARM CONTROL PANEL BACKBOX FOLLOWING POWER -LIMITED AND NON POWER -LIMITED WIRING REQUIREMENTS. REFER TO INSTALLATION INSTRUCTIONS FOR MORE INFORMATION. 7) ZONE CIRCUITS AND SIGNAL CIRCUITS ARE ELECTRICALLY SUPERVISED. BRANCH CIRCUITS SHALL BE LOOPED TO MAINTAIN INTEGRITY OF SUPERVISED CIRCUITS--T-TAPPING OF ZONE CIRCUITS AND SIGNAL CIRCUITS IS NOT PERMITTED. 8) REFER TO FACP MODULE DIAGRAMS, INCLUDED WITH FACP, FOR SPECIFICATIONS AND INFORMATION ON INDIVIDUAL PANEL MODULES. VERIFY ALL CONNECTIONS WITH A SIMPLEXGRINNELL FIELD TECHNICAL REPRESENTATIVE PRIOR TO TERMINATION. 9) ALL FIRE ALARM WIRING SHALL TEST FREE OF OPENS, SHORTS AND GROUNDS. 10) ALL WIRING SHALL BE LABELED AND TAGGED 11) ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR INSTALLATION AND MAKING ALL FINAL CONNECTIONS PRIOR TO JOB CHECKOUT AND FINAL TESTING BY A SIMPLEXGRINNELL FIELD TECHNICAL REPRESENTATIVE. CALL A MINIMUM OF 5 DAYS IN ADVANCE TO SCHEDULE A SIMPLEXGRINNELL TECHNICIAN AT (206) 291-1400 12) ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR MAKING ALL ARRANGEMENTS FOR INSPECTION, TEST AND CERTIFICATION OF THE FIRE ALARM SYSTEM BY ALL APPROPRIATE AUTHORITIES. • 13) UPON WRITTEN REQUEST, SIMPLEXGRINNELL WILL PROVIDE WRITTEN INSTRUCTIONS REGARDING THE APPROPRIATE WIRE/CABLE FOR INSTALLATION OF THE EQUIPMENT/SYSTEM(S) IDENTIFIED IN THESE DRAWINGS. SIMPLEXGRINNELL SHALL NOT BE RESPONSIBLE FOR PROBLEMS OR DAMAGES RESULTING FROM THE USE OF WIRE/CABLE OTHER THAN THAT WHICH HAS BEEN IDENTIFIED IN WRITING BY SIMPLEXGRINNELL FOR A SPECIFIC APPLICATION. 14) ALL WIRING SHALL MEET ALL APPLICABLE NATIONAL ELECTRIC CODE ARTICLES FOR FIRE ALARM AND LOW VOLTAGE WIRING. ARCHITECT: T.I. FIRE ALARM SYSTEM DESIGNED BY: SIMPLEXGRINNELL SEATTLE, WA T.I. FIRE ALARM SYSTEM INSTALLED BY: EQUIPMENT FOR FIRE ALARM SYSTEM SUPPUED BY: JOHNSON ELECTRIC KIRKLAND, WA SIMPLEXGRINNELL SEATTLE, WA WASHINGTON STATE ELECTRICAL CONTRACTORS NUMBER: #SIMPLL*981 SG TI -ESE DRAWINGS DO NOT SUPERSEDE THE CONTRACT DRAWINGS AID SPECRCAITOM, Tl -EY ARE WENDED AS A SUPPLEMENT ONLY ANO MUST BE USED IN CONJUNMION WITH TIS CONTRACT DOMENTS.11EY DO NOT 'TM CONTRACTORS OSUGATIONS TO TO TIE PROJECTS ELECTRICAL CONTRACTOR ASBUILTS - ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING SIMPLEXGRINNELL WITH ACCURATE REDLINED DRAWINGS. DRAWINGS SHALL BE REDLINED AS NECESSARY TO SHOW THE FOLLOWING: * DEVICE LOCATIONS - ADDS/DELETES. * CIRCUIT NUMBERS - ADDRESSABLE/SIGNAL/AUXILIARY/ZONE. * WIRE/CONDUIT - ACCURATE ROUTING. * WIRE FILL - USING WIRE CODE. * EOL RESISTOR LOCATIONS. SIMPLEXGRINNELL WILL PROVIDE (UPON REQUEST) A BLANK SET OF FLOOR PLANS TO BE REDLINED. SIMPLEXGRINNELL WILL INCORPORATE ALL REDLINED CHANGES INTO THE RECORD AUTOCAD SET OF DRAWINGS. ELECTRICAL CONTRACTOR - ELECTRICAL CONTRACTOR IS TO SCHEDULE A PRELIMINARY SITE MEETING WITH A SIMPLEXGRINNELL TECHNICAL REPRESENTATIVE. THESE MEETINGS ARE FOR REVIEWING EQUIPMENT LISTS, INSTALLATION PROCEDURES, AND PROVIDING ANSWERS TO QUESTIONS RELATIVE TO SYSTEM INSTALLATION. - PLEASE ALLOW A MINIMUM OF FIVE WORKING DAYS ADVANCE NOTICE TO SCHEDULE A TECHNICAL REPRESENTATIVE. - TO SCHEDULE A MEETING PLEASE CONTACT OUR SERVICE DEPARTMENT AT (206) 291-1400. - DO NOT USE FIRE ALARM CABINET AS TERMINAL CABINET NOTES: - FIRE ALARM DRAWINGS ARE SCHEMATIC ONLY. - ALL CABLE SUBSTITUTIONS MUST BE APPROVED BY SIMPLEX ENGINEERING IN WRITING. - NOTE: MOUNT HORN/STROBES, SPEAKER/STROBES AND STROBES AT 80" TO BOTTOM OF DEVICE. - NOTE: MOUNT PULL STATIONS AT 48" TO TOP OF DEVICE. Fire Alarm Control Panel Auxiliary Circuits AUX1 Not Available AUX2 - Not Available AUX3 - Spare AUX4 - Aux Power AUX5 - Not Available AUX6 - Aux Power AUX7 - Spare AUX8 Spare AUX9 Spare AUX10 - Spare AUX11 - Spare AUX12 - Spare AUX13 - Spare AUX14 - Spare IDNET Channel #M1 First Floor: M1-1 to M1-18 Second Floor: M1-30 to M1-38 I/O Points 101 102 103 104 105 106 107 108 109 1010 1011 1012 1013 1014 1015 1016 1017 1018 1019 1020 1021 1022 1023 1024 Input from Security Panel: Input from Security Panel: Input from Security Panel: Input from Security Panel: Input from Security Panel: Input from Security Panel: Input from Security Panel: Input from Security Panel: Input from Security Panel: Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Reception Panic Button North Door "Forced Open" East Door "Forced Open" South Door "Forced Open" West Door "Forced Open" North Door "Left Open" East Door "Left Open" South Door "Left Open" West Door "Left Open" Sequence of Operation Manual Station Smoke Detection 1st Fir Elevator Lobbies Smoke Detection Elev Lobbies Except 1st Fir Smoke Detection Elevator Mach Room Smoke Detection Elevator Shaft Smoke Detection Elevator Power Monitor Duct Smoke Detection Flow Switch Tamper Switch System Trouble Door Alarm From Access Control Activation of Local Alarm at FACP (LCD Display & Audible Indication)X X X X X X /X. Z CV Activation of Local Alarm at Annunciator x x x x x x DATE: 10-29-2004 SITE/PROJECT NUMBER: 458-4058194/904390901 x SHEET NUMBER: FA -COV -02 Activate AudibleNisible Devices v " ,x Fan Shutdown x x x x x X x Initiate Primary Elevator Recall x x Initiate Alternate Elevator Recall x v Activate Elevator Hat Ugh'. x V /� Priority 2 indication at FACP x Priority 2 Alarm To Central Station Monitor v X! Priority 2 Alarm Display at LCD Annunciator x Transmit Alarm Signal To Central Station Monitor v /� x y /X v /X y !X v X x Trouble Indication at FACP v Trouble Indication at Annunciator x Transmit Trouble Signal To Central Station Monitor x Supv Indication at FACP x x x Supv Indication at Annunciator x x i 'i Transmit Supv Signal To Central Station Monitor x x x BATTERY CALCULATIONS - FACP Does the system have an Emergency Generator that meets NEC 700.01? _yes X no How many hours of battery standby are required? 4 X 24 -_48 CO (4 hours minimum vv/ Emergency Generators) ty Part # Description Standby Total Alarm Current (A) Standby (A) Current (A) Total Alarm (A) 1 4100-9111 1 4603-9101 2 4098-9756 2 4098-9843 3 2088-9008 Fire Alarm Control Panel AudibleNisible Device Load LCD Annunciator TrueAlarm Duct Smoke Sensor Duct Detector Relay Remote Relay Total Standby Current Required= Total Alarm Current Required= Total= 20% Depletion Factor= Total Amp/Hour Required= Total Amp/Hour Batteries Provided= 0.4680 0.0000 0.0300 0.0024 0.0000 0.0000 Total Standby= 0.5028 6.7680 0.4680 0.0000 0.0300 0.0048 0.0000 0.0000 0.5028 X X 0.7500 5.7430 0.1700 0.0150 0.0150 0.0150 0.7500 5.7430 0.1700 0.0300 0.0300 0.0450 Total Alarm= 6.7680 Time (Hrs) 24.0000 12.0672 0.0833 0.5638 12.6310 2.5262 15.1572 (1) set 33.0000 -u -a '0 u) o 10 r CO Is .0 SD.D 0 0 0 in to - c `c c c 1 1 0 i ADDRESSABLE DEVICES ADDRESSABLE DEVICES PX PX PX PX PX PX ,i-- TO FAN SHUTDOWN ,t. PX PX PX PX PX C ( C 2C NAL' I}i i�iCtllEi; EAR E l GrW JND 120VA�'' 3C n1 1 PX PX PX PX CPX !' t: 2CPX C C EOL EOL C C Eli sp l 1- 3CPX C 4CPX C C iF- EOL C C C 141 VI?75cd C CC C C I I 1/F75cd EOL d-- 5CPX R R '1� TO ELEVATOR POWER MONITOR A \4C TO PRIMARY RECALL EOL TO ALTERNATE RECALL 'is— TO FIREMAN'S HAT LIGHT EOL ()COL 120VAC -- c7-5CPX 4100ES FACP i' 'lCAL 1R/OER 21/A6 A11/4/ 66A..lf: NONE EOL EOL HORN/STROBE CIRCUIT N2-3 HORN/STROBE CIRCUIT N2-2 HORN/STROBE CIRCUIT N2-1 BELL/S1POBE CIRCUIT SIG10 HORN/STROBE CIRCUIT SIG9 HORN/STROBE CIRCUIT SIG5 HORN/STROBE CIRCUIT SIG4 HORN/STROBE CIRCUIT SIG3 R 2ND FLR 1ST FLR A .21191. FACP - CABINET #1 a 0 iJ (i 0 PJ CO 0 IV 4.0 o IV w 0 N CO 4100-1279 c N CO 0 N CO 4100ES FRONT PANEL Symbol Description Legend Part # Backbox EK 15cd N1-1 15cd N1-1 15cd N1-1 15d N1-1 VV?75d 1-2 Multi—Candela Horn/Strobe *Subscript Indicates Circuit # & Candela Setting Multi—Candela Horn/Strobe, Celina Mount *Subscript indicates Circuit # & Candela Setting Multi—Candela Strobe *Subscript Indicates Circuit # & Candela Setting Multi—Candela Strobe Ceiling. Mount *Subscript Indicates Circuit # & Candela Setting Weatherproof Strobe *Subscript Indicates Circuit # Weatherproof Strobe *Subscript Indicates Circuit # Subscript Indiicates Circuit # Addressable Manual Station TrueAlarm Smoke Sensor 00 TrueAlarm Duct Detector Duct Detector Relay Supervised !AM Flow Switch Tamper Switch Post Indicator Valve Relay IAM Remote Relay Dual Circuit Heat Detector LC0 LCD Annunciator NAC Panel 4100ES Fire Alarm Control Panel LIAM e RI EMI FACE 4906-9127 4906-9130 4906-9101 4906-9104 4" sq by EC 4" sq by EC 4" sq by EC Sg by EC RSSWP-2475W—FR WPSBB—R 4906-9105 MB—G10-24—R 4099-9001 4098-9714 w/ 4098-9792 Base 4098-9756 w/ 2098-9798 Tube 4098-9843 4090-9001 By Others By Others By Others 4090-9002 2088-9008 5623 4603-9101 4009-9201 4100-9111 4905-9828 WBB—R 4" sq. w/sg ring by EC 4" oct by EC Self—Contained 4" sq. w/ cover by EC 4" sq. w/ cover by EC By Others By Others By Others 4" sq. w/cover by EC Self—Contained 4" Oct. by EC 6—Gang 3-1/2" deep by EC 16.25" x 13.5" x 4.25" 56"H X 24"W X 11.6875"D Letter Qty Color/Type Wire Code Size Function A 2 Black/Orange TFN C 2 Red/Blue THHN D 4 (2) Red/(2) Blue THHN H 1 WestPenn D975 2 Red/Black THHN P 2 Red/Black THHN X 1 WestPenn D975 16 Zone 14 Horn/Strobe 14 Horn/Strobe Loop 18 Serial Communication 14 14 24VDC Power 18 Addressable Data Line c c 957085203 957065203 4100-5111 IDNET CHANNEL #1 SIG3-5 ^) 'le, 1 o AUX3-.4. 4100-3206 AUX7-14 4100-5101 4100-5115 SIG9-14 AUX6 BACK PANEL 4/CCE-3 PANEL L. L IY UT' l+O 1 0 Simplexerinnell BE SAFE. A Tyco International Company SimplexGrinnell 9520 10th Avenue South, Suite 100 Seattle, Wa. 98108 SALES: 206-291-1400 SERVICE: 206-291-1400 © 2002 SIMPLEXGRINNELL LP FAX: 206-291-1500 ALL RIGHTS RESERVED PROJECT # 957085203 957065203 _ A 5 REVISION DESCRIPTION 0 a M 1 REVIEW COMMENTS c:4 V m rsi i R: -_c" I FIRE ALARM SYSTEM RISER SHEET CONTINENTAL MILLS CORP ANNEX 18000 ANDOVER PARK WEST TUKW LA, WA 98188 APPROVED BY: J.C.P. DRAWN BY: J.C.P. DATE: 10-29-2004 SITE/PROJECT NUMBER: 458-4058194/904390901 SHEET NUMBER: FA -RIS -01 TYPICAL STROBE !MIRING DIAGRAM TYPICAL HORN/STROBE KR/NG DIAGRAM TYPICAL CEILING 5TROBE HIRING DIAGRAM TYPICAL INEATHERPROOP SI I,OBE HIRING DIAGRAM TYPICAL CEILING HORN/5TROBE MIRING DIAGRAM 1(11 omior 111.• .......... c C= (2) #14 AWG (-) (+) KC 2 WC 3 IHC 4 0 -NN 0 +NY 0 -Illi 00010 NY +NM -NM a a a a a o 12 a 0 a a a O 0 0 a 0 0 n n 121._.02 000 HARDWARE ADDRESS 1ST BAND C= (2) #14 AWG (-) (+) KC 2 WC 3 IHC 4 0 -NN 0 +NY 0 -Illi 00010 NY +NM -NM a a a a a o 12 a 0 a a a O 0 0 a 0 0 n n 121._.02 000 HARDWARE ADDRESS NlC5 TB6 0 O O O O 0 0 O 0 N + OUT + N - OUT - TB5 NC WC 7 NC e 4009-9201 IDNet NAC PANEL b1 CONFIG SOFTWARE 00000 TB4 ADDRESSABLE NAC SYSTEM 0 o ASSY 0565-771 A B C D O X= (1) WEST PENN D975 #18 AWG LCD ANNUNCIATOR 4603-9101 SHLD -CONN +COMM TO FACP 24VDC POWER SUPPLY TYPICAL PULL STATION /MIRING DIAGRAM - X= (1) WEST PENN D975 #18 AWG TYPICAL SMOKE DETECTOR ,/MIRING DIAGRAM *BASE (\\40Q0_9792 \ 1.32 !!'/I k___H= (1) WEST PENN D975 #18 AWG (2) #14 AWG eeeee rB3' 1 2 3 4 5 T8 BS= m k§ tioym CPU MOTHERBOARD -r 0 04 0 D a re tionEK vJi; 3 1162.31 22 0 P4 8 7 8 5 4 3 2 1 eeeeeeee TB1 TB1 2 3 4 5 CO <a ZDNet SHIELD II Y 0000 0000 0000 182 1 2 3 4 5 6 7 8 9 10 11 12 coma<mm<<m®a< NAC3 NAC4 NAC5 4100-9111 SYSTEM POWER SUPPLY 120VAC 60Hz (566-070) AUX3 CITY P6 (1) WEST PENN D975 #18 AWG 0 00 0❑ 00 P3 B RY (+) P4 BTRY (-) P5 C= (2) #14 AWG ( BASE / 4098-9792 4 SHLD A , 1-- 11 ii II II V V ISHLD Letter Qty ColoNType Wire Code Size Function A C H P X 2 Black/Orange TFN 2 Red//Blue THHN 4 (2) Red/(2) Blue THHN 1 WestPenn D975 2 Red/Black THHN 2 Red/Black THHN 1 VVestPenn D975 16 14 14 18 14 14 18 Zone Horn/Strobe Horn/Strobe Loop Serial Communication 24VDC Power Addressable Data Line TO NEXT DEVICE OR 10K OHM EOL RESISTOR TYPICAL DUCT DETECTOR JNIRING DIAGRAM 4098-9756 4-W1RE DUCT SENSOR 1ST BAND SW2 16M:=3 9 2® 3® 4=1.1 51® 6I7 7[6111= J 0=51/ 0 NS 00000 -NM +NN -Mr 0000 AM -Nr +N11 0 -Nil 7 8 MAP - 9 10 11 12 +24V NlC5 TB6 0 O O O O 0 0 O 0 N + OUT + N - OUT - TB5 NC WC 7 NC e 4009-9201 IDNet NAC PANEL b1 CONFIG SOFTWARE 00000 TB4 ADDRESSABLE NAC SYSTEM 0 o ASSY 0565-771 A B C D O X= (1) WEST PENN D975 #18 AWG LCD ANNUNCIATOR 4603-9101 SHLD -CONN +COMM TO FACP 24VDC POWER SUPPLY TYPICAL PULL STATION /MIRING DIAGRAM - X= (1) WEST PENN D975 #18 AWG TYPICAL SMOKE DETECTOR ,/MIRING DIAGRAM *BASE (\\40Q0_9792 \ 1.32 !!'/I k___H= (1) WEST PENN D975 #18 AWG (2) #14 AWG eeeee rB3' 1 2 3 4 5 T8 BS= m k§ tioym CPU MOTHERBOARD -r 0 04 0 D a re tionEK vJi; 3 1162.31 22 0 P4 8 7 8 5 4 3 2 1 eeeeeeee TB1 TB1 2 3 4 5 CO <a ZDNet SHIELD II Y 0000 0000 0000 182 1 2 3 4 5 6 7 8 9 10 11 12 coma<mm<<m®a< NAC3 NAC4 NAC5 4100-9111 SYSTEM POWER SUPPLY 120VAC 60Hz (566-070) AUX3 CITY P6 (1) WEST PENN D975 #18 AWG 0 00 0❑ 00 P3 B RY (+) P4 BTRY (-) P5 C= (2) #14 AWG ( BASE / 4098-9792 4 SHLD A , 1-- 11 ii II II V V ISHLD Letter Qty ColoNType Wire Code Size Function A C H P X 2 Black/Orange TFN 2 Red//Blue THHN 4 (2) Red/(2) Blue THHN 1 WestPenn D975 2 Red/Black THHN 2 Red/Black THHN 1 VVestPenn D975 16 14 14 18 14 14 18 Zone Horn/Strobe Horn/Strobe Loop Serial Communication 24VDC Power Addressable Data Line TO NEXT DEVICE OR 10K OHM EOL RESISTOR TYPICAL DUCT DETECTOR JNIRING DIAGRAM 4098-9756 4-W1RE DUCT SENSOR 1ST BAND SW2 16M:=3 9 2® 3® 4=1.1 51® 6I7 7[6111= J 0=51/ 4TH BAND ADDRESS SWITCH 101 1 2 3 4 5 6 4421°4444°y444444 + - I MAP + I ED I LEST Li 7 8 MAP - 9 10 11 12 +24V 13 14 24C 15 16 + -- ALM BROWN GREEN BROWN GOLD N/A 1K BROWN BLACK RED GOLD N/A 1.8K BROWN GREY RED GOLD N/A X= (1) WEST PENN D975 #18 AWG TYPICAL JNEATHERPROOP 5 / /,OBE !NIR/NG DIAGRAM STROBE ± REAR VIEW IL FIRE FIRE FRONT VIEW C= (2) #14 AWG (1) WEST PENN D975 #18 AWG TO FACP 24VDC POWER SUPPLY TYPICAL INEATHERPROOE BELL lN/R/NG DIAGRAM Temma< comas mmaa NAC9 NAC10 NAC11 4100-5101 XPS POWER SUPPLY 120VAC 60Hz AUX 1200,ER 182Y 0V +2A 1211115(,4 eeee eeee e 000 %ELAYR FUYELAY R 11 3 NCNO C NC 12 C C NCNO C S®SAS®®@S LLAY NC 14© C ® 4100--3206 8 SPDT 3 AMP RELAY BOARD N r) *10 CO P CO 1H) 16 N M 7 If) 10 00000000 4100-1290 24 POINT I/O (562-858) MOTHER BD. MI, MEM Mill NM wo Immo mem P3 J2 22 Z .00000000�u P1 RR�y' N ��R?V �NNN 10000(9000 POWER + POWER - P=(2) #14 AWG TO NEXT DEYOE OR 1OK OHN EDI. RESISTOi TO 24VDC POWER TO ELEVATOR PRIMARY RECALL/ ALTERNATE RECALL/FIREMAN'S HAT UGIT (rte) 0 0 00 N/C C N/O �SPOT CONTACTS 10 AMPS 81 115 VAC [I 24 115 230 0 IkI$01! o 0,10 TYPICAL RELAY /AM /MIRING DIAGRAM TO NEXT ADDRESSABU DENCE TYP/CAL IAM d1(/RING DIAGRAM SHIELD Symbol Description Legend Part # Backbox 15cd N1-1 Mufti -Candela Horn/Strobe 4906-9127 *Subscript Indicates Circuit # & Candela Setting Multi -Candela Hom/Strobe, Ceiling Mount 4906-9130 15cd *Subscript Indicates Circuit # & Candela Setting N1-1 15cd N1-1 15c3 111-1 V6,75cd Q• F 1-2 IAM i$ 6 RI LCD NA FALL' Multi -Candela Strobe 4906-9101 *Subscript Indicates Circuit # & Candela Setting Multi -Candela Strobe. Ceiling Mount *Subscript Indicates Circuit ,' & Candela Setting *Subscript Indicates Circuit # Weatherproof Strobe *Subscript Indicates Circuit # Weatherproof Bell *Subscript Indicates Circuit Addressable Manual Station TrueAlarm Smoke Sensor TrueAlotm Duct Detector Duct Detector Relay Supervised IAM Flow Switch Tamper Switch Post Indicator Valve Relay IAM Remote Relay Dual Circuit Heat Detector LCD Annunciator NAC Panel 4100ES Fire Alarm Control Panel 4906-9104 4" sq by EC 4" sq by EC 4" sq by EC Sg by EC RSSWP-2475W-FR WPSBB-R 4906-9105 MB -G10 -24-R 4099-9001 4098-9714 w/ 4098-9792 Base 4098-9756 w/ 2098-9798 Tube 4098-9843 4090-9001 By Others By Others By Others 4090-9002 2088-9008 5623 4603-9101 4009-9201 4100-9111 4905-9828 WBB-R 4" sq. w/sg ring by EC 4" oct by EC Self -Contained 4" sq. w/ cover by EC 4" sq. w/ cover by EC By Others By Others By Others 4" sq. w/cover by EC Self -Contained 4" Oct. by EC 6 -Gang 3-1/2" deep by EC 16.25" x 13.5" x 4.25" 56"H X 24"W X 11.6875"D 1/2 W 10K EOL RESISTOR 4081-9008 (6.81( 1/2W) -866 TYPICAL IAM /MIRING DIAGRAM (1) WEST PENN D975 #18 AWG IDNET+ TYPICAL SPRINKLER SIA/ITCH J'\/RING DIAGRAM TYPICAL IAM DURING DIAGRAM SHIELD SHIELD X= (1) WEST PENN 0975 #18 AWG 7YP/ f L. t/E\e/ICE PVIRINA,P/A6RAM SCALE: NOM: NOTE: ALL DEVICES ARE TYPICAL (6.5� /_21A) 7 SHIELD 1 IDNET- X= (1) WEST PENN D975 #18 AWG —( TYPICAL 5623 SYSTEM SENSOR HEAT DETECTOR /MIRING DIAGRAM 120VAC SHUNT POWER A=(2) #16 AWG1/2W) (6.873 -886 OMHS 1ST BAND 2ND BAND 3RD BAND 4TH BAND 5TH BAND 120 BROWN RED BROWN GOLD N/A 150 BROWN GREEN BROWN GOLD N/A 1K BROWN BLACK RED GOLD N/A 1.8K BROWN GREY RED GOLD N/A 2.2K RED RED RED GOLD N/A 3.3K ORANGE ORANGE RED GOLD N/A 4.7K YELLOW VIOLET RED GOLD N/A 6.8K BLUE GREY RED GOLD N/A 10K BROWN BLACK ORANGE GOLD N/A SHUNT TRIP BREAKER ®NA c N/0 0 1.7 Yk 24 115 230 X= (1) WEST PENN D975 #18 AWG 0 0 SImplexerinnell ®E SAFE. FE. ATyco International Company SimplexGrinnell 9520 10th Avenue South, Suite 100 Seattle, Wa. 98108 SALES: 206-291-1400 SERVICE: 206-291-1400 © 2002 SIMPLEXGRINNEL L LP FAX: 206-291-1500 ALL RIGHTS RESERVED Ma t g a 957065203 957065203 1 A a 0 0 REVISION DESCRIPTION 1 If_ i i s 1 m t- FIRE ALARM SYSTEM DETAIL SHEET CONTINENTAL MILLS CORP ANNEX 18000 ANDOVER PARK VEST TUKWILA, WA 98188 APPROVED BY: J.C.P. DRAWN BY: J.C.P. DATE: 10-29-2004 SITE/PROJECT NUMBER: 458-4058194/904390901 ) c t SHEET NUMBER: FA—DET-01 J S1c1O EOL Siclo wQ ±11'-3"X14'– pct,, )rt_ j'p HX ONFERENCE tR r`'li ±21'--6". -$ �.. SMAL ±1 15cd gG3 OPEN 0 'E _i49' -6"X29'– 1 1==.:11Ocd i^=3 C EATLV ;% OREA,11'0 II .ySREA-IG/E. IL :v SC_I\JII. C.J 7�It' l'--'' I ! .�� l... J Ips I ka —DISPLAY Cc) COPY/PRT AREA PKG/PR ±217 FUTU E FRY ±29'-9 40'-3" 15cd SIG5 li .,4---- I- ,6. - �.Y/IvIVO(KiI l'JR'AGE R;L.'.ii,; I!-wP75cd---- 1 ((0 t 1 L I1 ,0I SUMER I 1 i ,h �-- F I!i I UI / 1----;--,11i ! iiC( '5' P/IEk l20N �I li',"1-Ril ' 1i ; I IRE' it II! s 1 li C ilk/ I(_ N i t' 1 i'"• -)';'s ! 1/' i 1 1 1 _ I �— =_-i� • I • , Ili 75cd SIG4 CONSUMER i DISPLAY- 1 I F�Mib17 \ FIRST FLOOR 1C1-AAN SCALE 1/8"=1=0" GENERAL NOTES: 1. DEVICES SHOWN LIGHT ARE EXISTING REMOVED DURING DEMOLITION AND ARE TO BE RE—USED IN NEW LOCATIONS. SET CANDELA VALUE AS SHOWN ON FLOOR PLANS AND RE—CIRCUIT AS INDICATED. DEVICES WITH FLAG NOTE 2 ARE EXISTING DEVICES IN AREAS THAT ARE NOT PART OF CONTRACT AND WILL NEED TO BE TIED BACK INTO NEW CIRCUITING, BUT SHOULD REMAIN IN THEIR CURRENT LOCATIONS. 2. MOUNT ALL NEW MAIIUAL PULL STATIONS PER ADA RECOMMENDED HEIGHTS. FLAG NOTES: / EXISTING DEVICE NOT IN SCOPE OF WORK TO REMAIN. RE—CONNECT TO NEW CIRCUITING AS INDICATED. FIELD VERIFY WIRE LOCATION FROM IAM TO EXISTING PIV CONNECTION. r_ FIELD 'an' LOCATION Symbol Description Legend Part # Backbox E 15cd N1-1 15cd N1-1 15cd N1-1 ►01 15x1 N1-1 i1P75cd ENO 1-2 EI IAM E.] LCD Multi—Candela Horn/Strobe *Subscript Indicates Circuit # Multi—Candela Horn/Strobe, C *Subscript Indicates Circuit # Multi—Candela Strobe *Subscript Indicates Circuit # Multi—Candela Strobe Ceiling' *Subscript Indicates Circuit # Weatherproof Strobe *Subscript Indicates Circuit # Subscript Indicates Circuit # Weatherproof Bell *Subscript Indicates Circuit # Addressable Manual Station TrueAlarrn Smoke Sensor TrueAlarm Duct Detector Duct Detector Relay Supervised IAM Flow Switch Tamper Switch Post Indicator Valve Relay IAM Remote Relay Dual Circuit Heat Detector LCD Annunciator NAC Panel & Candela Setting eiling Mount & Candela Setting & Candela Setting 4906-9127 4906-9130 4906-9101 Mount 4906-9104 & Candela Setting FACP 1 4100ES Fire Alarm Control Panel 4" sq by EC 4" sq by EC 4" sq by EC Sg by EC RSSWP-2475W—FR WPSBB—R 4906-9105 MB—G10-24—R 4099-9001 4098-9714 w/ 4098-9792 Base 4098-9756 w/ 2098-9798 Tube 4098-9843 4090-9001 By Others By Others By Others 4090-9002 2086-9008 5623 4603-9101 4009-9201 4100-9111 4905-9828 WBB—R 4" sq. w/sg ring by EC 4" oct by EC Self—Contained 4" sq. w/ cover by EC 4" sq. w/ cover by EC By Others By Others By Others 4" sq. w/cover by EC Self—Contained 4" Oct. by EC 6—Gang 3-1/2" deep by EC 16.25" x 13.5" x 4.25" 56"H X 24"W X 11.6875"D Letter Qty Color/Type Wire Code Size Function A 2 Black/Orange TFN C 2 Red/Blue THHN D 4 (2) Red/(2) Blue THHN H 1 WestPenn D975 2 Red/Black THHN P 2 Red/Black THHN X 1 WestPenn D975 16 Zone 14 Horn/Strobe 14 Horn/Strobe Loop 18 Serial Communication 14 14 24VDC Power 18 Addressable Data Line P?( 111-7 M1-6 M1-5 PX fah -4 \--m.—TO TO FIREMAN'S HAT LIGHT �-r�— TO PRIMARY RECALL \--10— TO ALTERNATE RECALL TO €L EV. POWER MONITOR PX 1 2 BE SAFE. A Tyco International Company SimplexGrinnell 9520 10th Avenue South, Suite 100 Seattle, Wa. 98108 SALES: 206-291-1400 SERVICE: 206-291-1400 © 2002 SINPLEXGRINNELL 12 FAX: 206-291-1500 Ail. RIGHTS RESERVED A n .O ai A z 0 o gi i p 1 A m da r- FIRE ALARM SYSTEM FIRST FLOOR PLAN CONTINENTAL MILLS CORP ANNEX 18000 ANDOVER PARK WEST TUKWILA, WA 98188 APPROVED BY: J.C.P. DRAWN BY: J.C.P. DATE: 10-29-2004 SITE/PROJECT NUMBER: 458-4058194/904390901 C L 1 c L SHEET NUMBER: FA—F-01 _N.I.C. - AREA OF WORK r ill' CA EXI STI Nt E3 E N C I -TCS OPEN OFFICE 40'_ G"X18' -6" —_L I [i - ' 15'-_I1 CB r—r`— — — -- -- — — — — To7E, WATER COC LER I�( ,fit J_iSI�E3i'i J — AR L =J 1 �-• L JD 7 SC \A/CASE' KITCHEN ±J3' -6X2,. j , 1 110cd N2-3 OPEN OFFICE 52'-6"X32'-6" I •I LJ EXISTING BENCHES r 7 —JT 7 71 L_____1L_—J I I L N2 -1I —� 1 �` jlL.LlS! OTT,- II •%Y:_.'\J AREA �- ZONE_ :)0M R',?:;r:! 7.,cd N'2.—• ilocd' N2 -1I ,0 "%./A2C 15cd \ Xi I To E .EV. SHUNT TRW 1-34 1•1 30cd N2-1• 15cd N2-1 EOL 1;1 EXISTING FREEZER X 1 1-37 i IL 11Od N2-3 r_2)7,0. L 1 11 JI :tI *MO MP, =n M "M CIMS n - - 1 1- 1 77; --- 6"X23: rI OPEN OFFICE ±44'-6"X21'--6" NE1. / B'ENCHES "17.i.,',..?* - �. .+1_x.22?J'.17.0t. C 'dl N2-2.._... 1 11 11 I 1 II 1 _— 1 ,j — `' —r-- — I I EXISTING E?ENCHE` ! - -N2-3 I ! I N2-2 15cd N2-2 - --- I-- - - -! i C — II I 11 _ _ I 1 _.____----___ ., I 1, I .__ I I I I 'L , 1 II .,, 71�....� .. ,T�a.m. .....-.1 s„:..�1G� .a.. - T -"Tr ___IL,...,,,a,.�.z-, :���.:a ..-7-- — L -..�.r- .`:,:�` n;.: -:;;'t. --,.-;.... .r., LI -71 II GENERAL NOTES: 1. DEVICES SHOWN LIGHT ARE EXISTING REMOVED DURING DEMOLI11ON AND ARE TO BE RE -USED IN NEW LOCATIONS. SET CANDELA VALUE AS SHOWN ON FLOOR PLANS AND RE -CIRCUIT AS INDICATED. DEVICES WITH FLAG NOTE 2 ARE EXISTING DEVICES IN AREAS THAT ARE NOT PART OF CONTRACT AND ,WILL NEED TO BE TIED BACK INTO NEW CIRCUITING, BUT SHCULD REMAIN IN THEIR CURRENT LOCATIONS. 2. MOUNT ALL NEVI MANUAL PULL STATIONS PER ADA RECOMMENDED HEIGHTS. EAG NOTES: EXISTING DEVICE NOT IN SCOPE OF WORK TO REMAIN. RE -CONNECT TO NEW CIRCUITING AS INDICATED. DUCT DETECTOR TO BE MOUNTED ON RETURN AIR SIDE, FIELD VERIFY EXISTING LOCATION. HEAT DETECTION IS REQUIRED IF SHAFT IS SPRINKLED. � II r_ • 1 J� j J I Symbol Description Legend Part # Backbox ►-t ►©4 15cd N1-1 Multi -Candela Hom/Strobe *Subscript Indicates Circuit # & Candela Setting Multi -Candela Hom/Strobe, Ceiling Mount 15cd *Subscript Indicates Circuit # & Gandela Setting N1-1 15cd N1-1 1�1 15cd N1-1 WP 1W750:1 1-2 IAM Multi -Candela Strobe *Subscript Indicates Circuit # & Candela Setting 4906-9127 4906-9130 4906-9101 Multi -Candela Strobe Ceiling. Mount 4906-9104 *Subscript Indicates Circuit & Cande!,k Setting 4" sq by EC 4" sq by EC 4" sq by EC Sg by EC Weatherproof theptIcates RSSWP-2475W-FR WPSBB-RndiCircuit # Weatherproof Strobe *Subscript Indicates Circuit # Subscript Indiicates Circuit # Addressable Maiiuoi Station TrueAlarm Smoke Sensor T rueAlaim Duct Detector Duct Detector Relay Supervised IAM } Flow Switch �*5 Tamper Switch Post Indicator Valve RI Relay IAM Q Remote Relay HQ Dual Circuit Heat Detector E:3 LCD Annunciator NAC Panel CO4100ES Fire Alarm Control Panel 4906-9105 MB -G10 -24-R 4099-9001 4098-9714 w/ 4098-9792 Base 4098-9756 w/ 2098-9798 Tube 4098-9843 4090-9001 By Others By Others By Others 4090-9002 2088-9008 5623 4603-9101 4009-9201 4100-9111 4905-9828 WBB-R 4" sq. w/sg ring by EC 4" oct by EC Self -Contained 4" sq. w/ cover by EC 4" sq. w/ cover by EC By Others By Others By Others 4" sq. w/cover by EC Self -Contained 4" Oct. by EC 6 -Gang 3-1/2" deep by EC 16.25" x 13.5" x 4.25" 56"H X 24"W X 11.6875"D Letter Qty Color/Type Wire Code Size Function A 2 Black/Orange TFN C 2 Red/Blue THHN D 4 (2) Red/(2) Blue THHN H 1 WestPenn 0975 2 Red/Black THHN P 2 Red/Black THHN X 1 WestPenn D975 16 Zone 14 Horn/Strobe 14 Horn/Strobe Loop 18 Serial Communication 14 14 24VDC Power 18 Addressable Data Line V EC'N17 FL- OR i�1 AN SCALE 1/8"=-1=0" Simplexerl tnell BE SAFE. A i yco International Company SimplexGrinnell 9520 10th Avenue South, Suite 100 Seattle, Wa. 98108 SALES: 206-291-1400 SERVICE: 206-291-1400 © 2002 SIMPLEXG L 12 FAX: 206-291-1500 ALL RIGHTS RESERVED PROJECT # 957065203 957065203 1 1 A ____ O 1 CI Z o 1 1 a 6 i a U N. A m FIRE ALARM SYSTEM SECOND FLOOR PLAN CONTINENTAL MILLS CORP ANNEX 18000 ANDOVER PARK WEST TUKWIL A, WA 98188 I APPROVED BY: J.C.P. DRAWN BY: J.C.P. DATE: 10-29-2004 SITE/PROJECT NUMBER: 458-4058194/904390901 SHEET NUMBER: I I FA—F-02 10 11 CCE ?IT Without Comments CI As Noted in Red CI Per The Attached Letter These plans have heed i reviewed by The Tukwila Fire Prevention Bureau for conformance with Current City standards. Acceptance Is subject to errors and orrlissions which do not authorize violations of adopted st;:ndards and ordinances. The responsibility for the :c;eguacy of design rests totally with the designer. Aki«dltions, deletions or revisions to these drawings after this date will void this acceptance and will require a i esubmittal of revised drawings for subsequent approval. 'final acceptance is subject -to field test and Inspection by The Tukwila Fire Prevention Bureau. pate: - C '1 `( By: TUKWILA FIRE DEPARTMENT Please call 206-5754407 and give this Fire Permit No. and exact address for shut- down hutdown or restoration approval. NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing n L -nvira © 6'-0" 1 R Corrugated stainless steel hose with stainless steel braid available in 2', 3',4',5' & 6' legnths FlexHead Sprinkler Drop CONTINENTAL MILLS - INNOVATION CENTER - ROOM 140 O FREEZER CHEST J 32'-G' 4.1'-0" re 2 E SS TAU 4X Multi—Port Bracket Adjustable Hub Sprinkler TYP. FLEXHEAD SPRINKLER DROP NOT TO SCALE E CONTINENTAL MILLS — INNOVATION CENTER — ROOM 140 FIRE SPRINKLER PIPING PLAN SCALE 1/4" = 1'—O" 0 1' 2' 4' 1 1 1 1 I GRAPHIC SCALE 8' Ir>C:er€ S r. elm L: IVIidl'arid.izr r: .:T16 e,d.i)r S1' S. Hamod Fc.dr 2014. :3`si€c' sws13 vCtii3P.s 3rzrs~ 261r`+193k13 VICINITY MAP NO SCALE FIRE SPRINKLER LEGEND EXISTING PIPE: NEW PIPE: X El MI MI MI El NI III IS III MI X OA E ADDED PENDENT SPRINKLER: EXISTING PENDENT SPRINKLER: RELOCATED PENDENT SPRINKLER: R OWNER / OCCUPANT x x x SITE CONTACT: x CELL: x SCOPE 1 RELOCATE (2) SPRINKLERS AND DEMO AS NEEDED IN REMODELED TENANT IMPROVEMENT AREAS AS SHOWN ON PLAN. GENERAL NOTES 1 THE OVER–HEAD SPRINKLER SYSTEM IS EXISTING. 2 THE DESIGN CRITERIA FOR THE T.I. AREAS OF WORK IS BASED ON EXISTING PIPE SIZING. 3 ALL NEW PIPE TO BE SCH 40 PIPE WITH 125 Ib. BLACK CAST IRON FITTINGS OR GROOVED WITH GROOVED FITTINGS & COUPLINGS, AS SHOWN. 4 ALL NEW ARM–OVERS OVER 2-0 SHALL HAVE A HANGER. 5 ALL HANGERS TO BE HANGER #1, UON. ALL HANGERS TO BE INSTALLED IN ACCORDANCE WITH NFPA #13. 6 ALL DESIGN AND INSTALLATION TO BE IN ACCORDANCE WITH NFPA #13 AND THE CITY OF TUKWILA. FIELD / LISTING NOTES 1 THREADED PIPE FROM 1" THRU 2" SIZE TO BE SCH. 40 PIPE. 2 GROOVED END PIPE FROM 1-1/2" THRU 4" TO BE SCH. 10 PIPE. 3 ALL GROOVED COUPLING ARE TO BE "RIGID" TYPE U.N.O. (IMPORT) 4 ALL THREADED FITTINGS ARE TO BE 175# CLASS CAST IRON (IMPORT) 5 ALL 1" NIPPLES NOT IDENTIFIED ARE 0-2 U.N.O. 6 ALL HANGER RODS TO BE FIELD CUT 7 ALL DIMENSIONS ON PIPING ARE CENTER TO CENTER FOR SUBMITTAL DRAWINGS 8 ALL DIMENSIONS ON PIPING ARE CUT LENGTHS FOR INSTALLATION DRAWINGS MIMI•IN FIR Alar 678. Sim SIM lb Slgnat I HYDRAULIC DESIGN DATA IMPORTANT In localities subject to freezing conditions, it is the owner's responsibility to provide heat throughout wet pipe sprinkler systems areas and In enclosures for d pipe deluge and other types of valves controlling water supplies to sprinkler systems. This drawing and the information and design application herein contained Is the property of TYCO FIRE &SECURITY SimplexGrinnell P oP Y / P and/or its subsidiaries and is loaned upon express conditions that the same be retumed to StmplexGrinnell upon request; all information herein contained shall be treated as secret, and confidential; no reproduction of this drawing or any part thereof shall be made without written consent of SimplexGrinnell. Created bythe Sim IexGrinnell , "All rights reserved". copyright y SimplexGrinnell 2001 g CONTRACT RESPONSIBILITIES ITEM SimplexGrInne&I/BY OTHERS SYMBOLS now %vita 05) C.G Gate Vohs L N.R.S. (GV) ND FF. Deat:Cann.(FDC) .�- Poet Indicator Vdve (FIV) 'go Fire Hy<Ikmt (3 Mby) -I. Thrust ` K•Y tial• S.ottond �� tdtlk Roodrroy Box o® Fare Haw Assembly y Inspectors Teat -5- Gobs Vdv. ) �'Angle Valve 3 Dry � Vdv. SPRINKLERS REM. AREA NAME 0. HAZARD CLASSIFICATION DENSITY GPM/SQ.FT. AREA OF APPUC. HOSE ALLOW. SQ. FT. /HD. TOTAL SYSTEM REQUIREMENTS ABBREVIATIONS AC - Above Finished Coling AFF Above Ribbed Floor ttEr SYSTEM TYPE SPECIAL REQUIREMENTS' GPM PSI AT MAKE TYPE MODEL SIN NPT / K—FACTOR TEMP. FINISH ESCUTCHEON NOTES SYMBOL QTY. ■ DFIUGE ■ DOMESTIC PIPE ■ +SLE a ■ SCHEDULE so cc u. SCALE: AS NOTED DRAWN BY: ALAN MAHAFFI'E CHECKED BY: BC - Balm FinishedColin BOB -Bottom of Beam BCD - Bottom of Delle BOJC- Bottan of Jost BDP -Bottom of Puffin HV - Haw V v. NIC Not h Contrast DRY _■ ■ PREAC11ON ■ I T WATER CONNECTION N/A I I Hydraulic R.finka. POM _AL fl Mader zwltalk -pa- ossY oat. Vd,, (os�') 1 tis. D ation '-"�'' Earthquake Brodng _4 Butterfly Vdve TYCO PENDENT TY—FRB TY3231 1 2" K=5.6 / 155' CHROME CHROME MATCH EXISTING ® (� 2 UNDERGROUND WATER MAINS N/A 'y L3 ■CITY ■aTM ■ FM APPROVALS EXCAVATIONS N/A 4 f Haw Norm Valve (ALV) ■GALVANIZED PIPE ■ GALVANIZED FITTINGS BACKFILL N A / e A 1 Mob Designation -kQ - Union WRING N/A Electric Bel OUT N wale Screwed Cap �. water Motor coo WATER SUPPLY INFORMATION: STATIC PRESSURE f RESIDUAL PRESSURE - aB'I - Jobt I■ aALvANizED MATERIALS • SPECIAL FITTINGS ■ F.M. MATERIAL PAINTING N/A *13" E a Pyo Bib. Bottom of Deck —� Gfwmid CcP —4 Screwed Plug -a wQhr Chalk V°We +12'-4" of Pp. Above Ref. Plan. -N- Swing Check Vdve GrocV.d coupling No C ono El'vat1on Ching. In p� ... Flanged Connection .,Ft. D'p'C0m Stoddard PSI PSI. WITH GPMFLOWING CUT IN TEST DATE:out TDB - Top of Bean TDP - Tap of Pwiik TOS - Top of Steel UaFI - unless othw.iw Noted TEST LOCATION: BY: OUT 14 • ■OTHER (not ti"" floor) ® n Baer - RAD D.ptConn.(Flwh) �C) - TOTAL THIS SHEET - 2 n r J 9 A R 7 Q 10 11 12 1 Fire & Security SimplexGrinnell 9520 10th Avenue South, Suite 100 Seattle, Wa. 98108 SALES: 206-291-1400 SERVICE: 206-291-1400 © 2002 SIMPLE%GRINNEIL LP 91 WASHINGTON STATE CERTIFICATE OF COMPETENCY PROTECTION SPRINKLER SYSTEMS i Mahaffie 3-0105-C Level 3 N plexGrinnell, L.P. N W a 3LL*988BG Expires =-� 12/31/14 UM 8 E f EM CONTINENTAL MI cc u. SCALE: AS NOTED DRAWN BY: ALAN MAHAFFI'E CHECKED BY: DATE: 04/29/2014 CONTRACT NUMBER: 977528207 SHEET NUMBER: �a..,.....,,.,' ......1 SHEET 1 OF 1, , 12 18000 ANDOVER PARK WEST ASSOCIATED PERMITS 90-009 88-186 86-102 11-F-156 14-S-105 11-S-098 11-H-224 SITE LOCATION CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East Tukwila, WA 98188 206-575-4407 Date application accepted: FIRE PROTECTION SYSTEMS PERMIT APPLICATION Applications and plans must be complete in order to be accepted for plan review. **PLEASE PRINT** King Co. Assessor's Tax No.: -65 Z 304+ ' I Z Site Address: t O At4'40ovezQ €66.(2*- J t$ S -r Suite Number: Floor: t `► Z Tenant Name: GO14T t i-4 ES 14 "TO L h 1 LA x9 New Tenant? ❑ - Yes (X- No Property Owner's Name: s e C L it. PRO PIS (t.'' 16$ LLC. Mailing Address: CJS t1 Sit &A L. it PP ?.t D2 G ( ve4.4.7 tLA wa ,8 % 88 City State Zip CONTACT PERSON -if there are questions about the submittal. Name: 3 CZ`1 -4 . S4(A 11 .t..0 Company Name: FtRfL S''rSTeg--tS (-%-“S 5-T Day Telephone: 2 534 $33 • . 248 Mailing Address: Z ofv F(-14.)1-4%0cCaaig- (ZO•LC t -k so c-t(L G (7Pac %FIL top. ,8047 City State Zip E-mail Address: 04-tJ evC S`tS•tcsrt wgZ<ST•cati Fax Number: 2S3- 735'. O tt3 Valuation of Project (contractor's bid price): $ % 3, 940 «' Scope of Work (please provide detailed information): 0'*00 .V'`t E ' e.tSFri1,---Ko S•P(ZA.-6.1L L. trot, S -r S-Tt tri t=o(L d' 4r.. w -T. . T... PERMIT APPLICATION NOTES Value of Construction - In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules. Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILDING OWNER OR AUTHORIZED AGENT: ea -c7,., s Print Name: 0, V (Pa -4 5.. 3-p..Q.+6.c'"tt k.s.-Z) Signature: Plan Permit App.doc Date: 4 /z. 1"/(,k. Day Telephone: 25--- • 23-'3- t ZQ$ 5/14/10 TFD FP Form 8 SITE LOCATION CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East Tukwila, WA 98188 206-575-4407 Date application accepted: FIRE PROTECTION SYSTEMS PERMIT APPLICATION Applications and plans must be complete in order to be accepted for plan review. Site Address: 18000 Andover Park West **PLEASE PRINT** ( APR 302014 T-LIYKV ntAW1 E1- King Co. Assessor's TaxNo.: 3523049055 Tenant Name: Continental Mills - Innovation Center Suite Number: 140 Floor: 1 Property Owner's Name: Continental Mills New Tenant? ❑ - Yes x❑ - No Mailing Address: PO Box 88176, Seattle WA 98138-2176 CONTACT PERSON -if there are questions about the submittal. Permit contact- Janet Stebbins Name: Project work- Alan Mahaffie Company Name: SimplexGrinnell City State Zip Permit/Janet: 206-291-1468 Day Telephone: Work/Alan: 206-291-1481 Mailing Address: 9520 10th Ave S, Suite 100 Seattle WA 98108 City State Zip E-mail Address: iastebbins@simplexgrinnell.com Fax Number: 206-291-1500 Total number of new/relocated devices or sprinkler heads: 2 Valuation of Project (contractor's bid price): $ 1946.00 Scope of Work (please provide detailed information): Relocate (2) pendent sprinklers. PERMIT APPLICATION NOTES Value of Construction - In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules. Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILDING OWNER OR AUTHORIZED AGENT: Print Name: Janet Stebbins/SimplexGrinnell Plan Permit App.doc Date: 4/30/14 Day Telephone: 206-291-1468 I/2/13 TFD FP Form 8 410,1 4tt SITE LOCATION CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East Tukwila, WA 98188 206-575-4407 Date application accepted: FIRE PROTECTION SYSTEMS PERMIT APPLICATION Applications and plans must be complete in order to be accepted for plan review. **PLEASE PRINT** King Co. Assessor's Tax No.: 3523049055 Site Address: 18000 Andover Park West Suite Number: Floor: Tenant Name: Continental Mills- North Annex New Tenant? ❑ - Yes ❑x - No Property Owner's Name: Continental Mills, Inc. Mailing Address: PO Box 88176, Seattle WA 98138-2176 CONTACT PERSON -if there are questions about the submittal. Name: Janet Stebbins Day Telephone: 206-291-1468 Company Name: SimplexGrinnell Mailing Address: 9520 10th Ave S, Suite 100 E-mail Address: lastebbins@simplexgrinnell.com City State Zip City State Zip Fax Number: 206-291-1500 Valuation of Project (contractor's bid price): $ 3655.00 Scope of Work (please provide detailed information): Re—pipe existing kitchen hood system. (25) nozzles. PERMIT APPLICATION NOTES Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules. Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILDING OWNER OR AUTHORIZED AGENT: Signature: Print Name: 1").."94‘-r- M.1e// Date: 9/28/11 Janet Stebbins/SimplexGrinnell Plan Permit App.doc Day Telephone: 206-291-1468 5/14/10 TFD FP Form 8 1 FIRE DEPARTMENT HOOD SUPPRESSION PLAN REVIEW COMMENTS Project Name: Continental Mills 18000 Andover Park West 11-H-224 October 3, 2011 Permit No.: Date: Reviewer: Al Metzler Fire Protection Project Coordinator (206) 575-4407 option # 2 (Inspection Requests) (206) 971-8718 (Plan Review Questions) • Nozzle heights above appliances to be per manufacturers installation guidelines. • Fryers shall be installed with at least a 16 inch space between the fryer and surface flames from adjacent cooking equipment or a minimum 8 inch high steel or tempered glass baffle plate shall be installed between the appViances. • Upon activation of the suppression system, the make-up air supply will shut off and the exhaust will keep running. • Type 1 hood systems shall be designed and installed to automatically activate the exhaust system whenever cooking operations occur. The activation of the exhaust system shall occur through an interlock with the cooking appliances, by means of heat sensors or by means of other approved methods. • Activation of the suppression system shall shunt all electrical power under the hood as well as the gas supply. • Install a "K" rated portable fire extinguisher within 30 ft. of the cooking equipment. • The hood suppression system shall be monitored by a U.L. Central Monitoring Station. • The suppression system manual pull station shall be located no closer than 10 ft. and no farther than 20 ft. from the cooking equipment and be placed at a height of 42 to 48 inches above the floor. • The inside lower edge of the hood shall overhang or extend a horizontal distance of not less than 6 inches beyond the edge of the top horizontal surface of the appliance on all open sides. The vertical distance between the front lower lip of the hood and such surface shall not exceed 4 feet. • If cooking appliances are wheeled, the appliance wheels shall be set in tracks permanently mounted to the floor to ensure appliance is returned to original location if moved for cleaning or maintenance. FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Continental Mills 18000 Andover Pk W Permit No.: 11-S-098 Date: May 9, 2011 Reviewer: Al Metzler Fire Protection Project Coordinator (206)971-8718 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ` of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 20 or more sprinkler heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to any sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2010 Edition. ItIOTU:1.LA Central Permit Sysn ntroi No. Permit .No: ; FINAL APPROVAL FORM C TO: 0 Building 0 Planning ❑ Public Works l Fire Dept. ❑ Police ❑ Parks / Recreation Project Name fe A /P c'i e gri--- /�N �G✓moi / t f , Address Type of Permit(s) rT This project is nearing completion. Please investigate your area of responsibility and indicate below either your final approval or necessary corrections. If no response is received within one week, it will be assumed that the project is of no con to your department and a certificate of occupancy may be issued. This project is NOT approved by this department; the following corrections are necessary:; ( ) ( ) h1fry EAG '4v-) e ) ) /Ap« //w,) 0.00.1e -I/19 ) ) ) ) ) ) Authorized Signature Date This project is approved by this department: Authorized Signature C n ITY OF TUJILA Central Permit System (SCofltroi No. 9: Permit No. 5- 3z FINAL APPROVAL FORM °CT TO: 0 Building 0 Planning ❑ Public Works Fire Dept. ❑ Police ❑ Parks / Recreation C Project Name Sc /' ��/ t' y ( 6'G ) Address /k--4 A•..�G��'/�'� U!e S t 1 Type of Permit(s) T/ This project is nearing completion. Please investigate your area of responsibility and indicate below either your final approval or necessary corrections. If no response is received within one week, it will be assumed that the project is of no concern to your department and a certificates ioccupancy ay be issued. This project is NOT approZi by this department; the following correctio re necessary: () () () () () () () () () () fivirkW / n c -/PJ ' ek.-t ��✓% g' �1� Authorized Sign'ature Date This project is approved by this department: Author ze Signature Date CPS Form 3 0 City of Tukwila Fire Department Hubert H. Crawley Fire Chief. FILE +++++++++++*++++++++++++ CORRECTION NOTICE +++++++++++++++++++++++++ FIRM: TYPE OF INSPECTION ,'I -'L/ ADDRESS: i kG u ^ 11~CCUPANCY CLASS z WG /!/' CONTRACTOR: DATE: / /144'-/c TIME: 00i r� . / /<-c' Discrepancy and Action Required 1‘5'e 5- /4 ,G/) c/t 14F' .St%ate 5 ✓Gi WARNING . If the above listed item() are not corrected b the below listed date a citation for Fire Code violation will be issued. Correction of tle above items is required by: a 94 Any overlooked hazardous condition and/or violation of the Fire Prevent- ion Codes of the City of Tukwila does not imply approval of such condit- efor violation. Page r 7.:c---s--z----"' -1-7(..„.?of � Inspecting Officer: /'' . r TFD Form FP 11 Title: City of Tukwila Fire Department, 444 Andover Park East, Tukwila, Washington 98188 (206) 575-4404 10'6" Single Bank Hood 1 36"x24" 12"x18" Oven Oven Oven Oven Broiler(1N) Griddle (1N) (1) A single 2W nozzle protects 100" perimeter or 23" diameter duct. (2) A single 1N nozzle protects 10 linear ft of single bank plenum. (3) A single 1N nozzle can protect a griddle: maximum cooking area of 1080 square inches with a max longest side of 36". Located on perimeter 35"-40" above surface aimed at center. (4) A single 1N nozzle can protect a broiler: maximum length of 36" and total cooking are not to exceed 864 square inches. Located 15"-40" above hazard aimed at center. Hood size 10'6" single bank style with 12"x17" duct opening. Customer currently has 6 gallon Ansul R102 system with fire alarm and electrical tie ins for electric gas valve and shunts. ACCEPTED El Without Comments ❑ As Noted in Red Per The Attached Letter These plans have been reviewed by The Tukwila Fire prevention Bi ireau fo ,itorrnance with current City standards. Accep._» is sub ect to errors and omissions which do not = 1 1�('6" single bank hood -♦ ingle bank hood C a) 0 C a) 0 a) 0 N X 00 N w r 10'6" single bank hood —1110. 10'6" single bank hood —1110 00 r-1 X 00 e-1 16%x13''A PAID SEP 3 0 2011 TUKW.ILA FIRE -A` zo, s 00 m C 0 N 13 a) a) E 0 C 0 03) -i-_.lD -0 a) ,M a) N C O E ao a) -- CO 0 o -.2.s.7 •` 0) N 4., 0 CU _0 a) E a) co to •L -0 C a) C O O iZ fa LI? X C C 0 o Ea) t -0 (0 03 N 0) .I- •1moi 40 O 3 0 N o in v > c 0 a) N 0 c0 (0 O 0 32 f70 M 0 7 cu H a N a) 0) 0 -0 i, -0 C 0 '- X 00 O '-I (0 0 Q 0 O iN-I N 1 co To CO 00 o a) la CIO sX tr. CC -0 O_ O C 00 a) C Y Y N O c 2 0 0 •N N c9 R 0 a, -0 dD a) u E u _O C E ` .~ 7 W. C h012 7 a) ` C. C o E C Zr.) ai vii - ' U X 0 co N O E.v z E E Ycc E hi 7 C aJ co •X -0 O E co _D H O .0 '0 _ COXO C E C ca Q O ti4 E ao O� ° c0 0 c0 ' n O CO i U la CO O vi N Q 4-. 0 O O O O� H Q _ Q > 0_ N O — (o N 3.3 co m c a) O a) O i, 1.4 N O VCN0 ^ HN N vN ` 00C 0L C c C I(c 3 z z mz 0- 0 N I-1 N r -I v a a, a) v aa)) •y E C C C C C E C -0 O N N •N O N N 0 7 < < < '0 < O. < 2 0 -1 N m. II) WASHINGTON SURVEYING AND RATING BUREAU 300 MARKET PLACE ONE 2001 WESTERN AVENUE SEATTLE, WASHINGTON 98121-2190 November 23, 1988 PLAN SHEET 1 OF 1 SUBJEC1 Key Bank Segale Bus Park, Bldg #862 18010 Southcenter Parkway Tukwila, WA. The attached plans have been approved as meeting requirements for classification as a sprinklered risk. The following revisions or additions to the design as shown would qualify the protection for improved rates based upon information shown on these plans: Wet pipe sprinkler equipment is acceptable subject to provision of a thermostatically controlled heating system capable of maintaining temperatures at not less than 40 degrees F in all spaces containing wet pipe sprinkler equipment. 1. Piping and sprinklers do not seem to correspond with Wormald plans, dated 10-20-86. 2. Revise pipe sizes as noted in red pencil on plans. 3. Extend sprinkler protection to vault. 4. Clamp hangers should be provided with retaining straps as specified by article 3-10.3.5.10 of N.F.P.A. #13, 1987. 5. Provide details of fabrication of pipe. All threads in Allied tube should be gauged. 6. All piping, valves and fittings should be listed and labeled by UL for fire service, installed, tested and flushed in accordance with NFPA Standards. APPROVED BY VIKANSIONATugswASH. IO BUREAU :: C, ?:: 19 g nnKlered on the attached laps as ps meeting applies to plans or additions as ccept Acceptance recommended PP requirements of this Bureau for classification .uctem changes ...uad rates. ►,own thereon. 0 0 } cr 1- z u LL 0 z 0 u) N a 1- 0 gia 2 0 } z --a ;z W W 1-- 0 z > a 1— . W 1-- z O z 0 Q O 0 W W N W ac N 1- -s cs J J Q k 4 roWo.., ano u�, � Lance. sheet(s) W�a�reforLconstruction submitted 7ect to inspection for final acceptance. to [elffiiP� sta'lation sub, Acte s:.^.�s,Yz}f �e not ti r gMar•.or'irs retst �,t: l kher ds „„ r Ari r ;;,v,r r l;, itra! lr- +:•.z•�; tor p 'e P Which m 4, ditec �, , •Lye iv ` yti v- i.4 t rsont be const13 2 to :ac ;. it ra. injury or s,;it ease. testa in loss 62, S` 4 GENERAL NOTES DESIGN Design is based on ordinary Hazard Pipe schedule per NFPA 13. Maximum head spaceing is 130 square feet per head. APPROVALS City of Tukwila Fire Department Washington Surveying and Rating Bureau PIPING A11 new piping is Allied "XL" pipe with threaded ends and cast iron screwed fittings. +'= . HANGERS 3/8" top beam clamps, 3/8 all thread rod, proved swivel ring hangers. :1 MEADS U.L. and F.M. ap- Existing pendent heads are 165 Central Model "H" recessed with chrome eschutcheons. STRUCTURE Existing structure is noncombustible with steel trusses. LEGEND — — —Existing piping. New piping. R ® New location of pendent head. Existing upright and pendent ort the same fitting. (� Existing upright. ® Existing pendent. New pendent. KEY 8APJt4 / • /o -D /0-0 /"d 0 t t / I4• / ,I 4 1U -o t,i / /010 ' 6_0 MEN FE:7,TRa0; \ REMJJUE11 EXIST`�� PL V CJ J, E L- V. MA 'H. WOME.UT R TRI i/TELE VAULT TO I,U FP.A CDRR J DJ REMGVE EXIST- l"PLUG -' //`h'-1110....-;_rtwAimrimmigr...;;;74 - .\ KEY BANK 0 HAFT IST FLOOR PLAN `SCALE 1/8 1-0 NORTH 11 1 v =�x • PAQK - Q EVAN BLACK ' DR BAKER-eLVP — pt z ..- ‹ 164T11ST }' S 16STH "-1ST I cn STRANDER 26 BLVD L z� 0 z w -81C c 1 '..x. TRECK DR z INDUS or• > < ,,pl-Py 1 0 Q 1 6 FS CORP RATE DR N CORPORATE •—---- OR S -- -- CDMLIUNLZY_.ttPLAfdD bR HEALTH • EMERGENCY CENTER 4 -- MIDLAND Qin, -r I r SAXON' ,DR TR1LAND DR JOBSITE 180TH D DR 1 Y 0 SITE PLAN ISSUED FOR CONSTRUCTION RivERS!pE DRQ - 4 11a Iffy /. „ is -17.27 /1-71-88 Z�5 REVISIONS: 0 W O cca N CO 00 z J co SOUTHCENTER PARKWAY O 1 co 1 TUKWILA , WA. 98138 H.V.A.C., PIPING, PLUMBIN ENERGY MANAGEMENT & FIRE PROTECTION I1cCtI-STRV MECHANICAL ENGINEERS AND CONTRACTORS 855 S. BARTON ST. P.O. BOX 24567 SEATTLE, WA. 98124 223-01 #MC -KI -N -372ND (206) 762-3311 DRAWN BY: L.B. ; S "71-7, CHECKED BY: B.T. o(, 9 3 /' DATE: /1-11-28 PROJECT: PROJECT NUMBER: 0 7S TITLE: °{ E SHEET: FP -1 oF1 • • 1 1 • KEY BANK ANALOG R v 0 0 y co Lu _ F - O t - _ F- - 3 2 it 0 z 4 z 0_ t F -! - - —t EkV. MACH. __1_, 2 - !t_ T / 4 k0 L _ }6} 1,0Es8Y r • GENERAL NOTES DESIGN r f � TO i FPA /3 jr ELECT TEE E CO RiOOP r —, F I r CORR I FSO -' REMOVE EXl $T_ L"PLU�r_, r = t ._ i -1E • 4 i Y- i _ f' 1 4v, + - -1_ cl_‘1_:r: - -- - i - 4 f -- _ _ -v.-- 4 i 1 ' V j 1 4- Design is based on ordinary Hazard Pipe schedule per NFPA 13. Maximum head spaceing is 130 square feet per head. APPROVALS City of Tukwila Fire Department Washington Su.veying and Rating Bureau PIPING All new piping is Allied ''XL" cast iron screwed fittings. HANGERS pipe with threaded ends and 3/8" top beam clamps, 3/8 all thread rod, U.L. and F.M. ap- proved swivel ring hangers. HEADS Existing pendent heads are with chrome eschutcheons. 165 Central! Model STRUCTURE Existing structure is noncombustible LEGEND — -- — Existing piping. New piping. R® 0 4 New location of pendent head. Existing upright and pendent Existing upright. Existing pendent, New pendent. "H" recessed With steel trusses. on ;the same fitting. KEY BANK 0 r —E rZ t T Yt t t r IST FLOOR PLAN - SCALE 1/8 1-0 / r Z 0 m /go/ NORTH ACCEPTED WITHOUT COM MENTS. AS NOTED IN RED ID PER THE ATTACHED LETTER The drawings affixed hereto have been reviewed and accepted by the City of Tukwila Fire Dept Additions. deletions or revisions to these drawings after this date will void this acceptance and will require a resubmittal of revised drawings - Final acceptance is subject to field - inspection by a representative of this department At- SA- P16 -4-i EvAN BLACK CC CITY OF TUKWILA 575-4407 TUKWILA FIRE DEPARTMENT Please call: 575.4407 and give this job - Lnd address for shut4 down or restoration approval. FILE ILO/ 3 kzkL FS 1 MINKLER BLVD: cc sAxow 10R -4 • 1 • 0 DR 1 NC CC 1 CC 0 art SITE PLAN ISSUED FOR CONSTRUCTION ST RIVERSIOE SEGALE BUSINESS PARK ILI cc a. CV CO 0 CO Nr— H.V.A.C., PIPING, PLUMBING, ENERGY MANAGEMENT & FIRE PROTECTION MECHANICAL ENGINEERS AND CONTRACTORS 855 S. BARTON ST. P 0. BOX 24567 SEATTLE, WA. 98124 223-01 #MC-KI-N-372NO (206) 762-3311 CHECKED BY: DATE. 11-11-88 PROJECT. PROJECT NUMBER. TITLE: KEY mi SHEET: FP -1 OF - MEALS RESTROOM E - WOMLNS RESTR©DAN CO RiOOP r —, F I r CORR I FSO -' REMOVE EXl $T_ L"PLU�r_, r = t ._ i -1E • 4 i Y- i _ f' 1 4v, + - -1_ cl_‘1_:r: - -- - i - 4 f -- _ _ -v.-- 4 i 1 ' V j 1 4- Design is based on ordinary Hazard Pipe schedule per NFPA 13. Maximum head spaceing is 130 square feet per head. APPROVALS City of Tukwila Fire Department Washington Su.veying and Rating Bureau PIPING All new piping is Allied ''XL" cast iron screwed fittings. HANGERS pipe with threaded ends and 3/8" top beam clamps, 3/8 all thread rod, U.L. and F.M. ap- proved swivel ring hangers. HEADS Existing pendent heads are with chrome eschutcheons. 165 Central! Model STRUCTURE Existing structure is noncombustible LEGEND — -- — Existing piping. New piping. R® 0 4 New location of pendent head. Existing upright and pendent Existing upright. Existing pendent, New pendent. "H" recessed With steel trusses. on ;the same fitting. KEY BANK 0 r —E rZ t T Yt t t r IST FLOOR PLAN - SCALE 1/8 1-0 / r Z 0 m /go/ NORTH ACCEPTED WITHOUT COM MENTS. AS NOTED IN RED ID PER THE ATTACHED LETTER The drawings affixed hereto have been reviewed and accepted by the City of Tukwila Fire Dept Additions. deletions or revisions to these drawings after this date will void this acceptance and will require a resubmittal of revised drawings - Final acceptance is subject to field - inspection by a representative of this department At- SA- P16 -4-i EvAN BLACK CC CITY OF TUKWILA 575-4407 TUKWILA FIRE DEPARTMENT Please call: 575.4407 and give this job - Lnd address for shut4 down or restoration approval. FILE ILO/ 3 kzkL FS 1 MINKLER BLVD: cc sAxow 10R -4 • 1 • 0 DR 1 NC CC 1 CC 0 art SITE PLAN ISSUED FOR CONSTRUCTION ST RIVERSIOE SEGALE BUSINESS PARK ILI cc a. CV CO 0 CO Nr— H.V.A.C., PIPING, PLUMBING, ENERGY MANAGEMENT & FIRE PROTECTION MECHANICAL ENGINEERS AND CONTRACTORS 855 S. BARTON ST. P 0. BOX 24567 SEATTLE, WA. 98124 223-01 #MC-KI-N-372NO (206) 762-3311 CHECKED BY: DATE. 11-11-88 PROJECT. PROJECT NUMBER. TITLE: KEY mi SHEET: FP -1 OF t s - 1 r - 1 • I Ems« - t Icitm 4-- ,. 1`4i1 _ Z - S iz i-7 3-11 l I 114 tr � 'It1. 114 ?—!1 I 4* r4� * tock. ?t 7—'i coL c p'r -t Z-8 1-47i `i -Q 4-7�t- f { N4vtf WAa_ =...: ,r i__ > - - ---_ w- 1_ :3\TT G,T,1..; HOE �1N1 j - 1.-- — - _ _ 5 - TO NEW LOCA1101,1 Q 4 14 -16 I 1`Qt, 7-$L A VED a.. rataati lg or ati L,J.aau of Fire P.evention. Aid,tiacs or to these drawings after this date shall not be construed as being approved or review d. - CITY OF TU ILA BUREAU OF FIRE PREVENTION REVILE) Oh -Z5-60 UtiT FM HEW OlklEALIC115 FIRE PREVENTION SYSTEMS, INC. 6E32-6316 SEATTLE * WASH., 9E1109 Offices: Seattle -Anchorage - Fairbanks HOS THIS SHT JOB NO DWG NO DRAWN - — DATE SCALE iCk a K� £ r- 4 - 3- - n" t # 3 CEILING PLATE_ ROD & RING # 4 EYE ROD WOOD SCREW & RING # 7 POWDER DRIVEN STUD ROD & RING • 4 $ 1- 7 11. i i # 10 TOP BEAM C CLAMP ROD & RING -# 12 SIDE BEAM BKT ROD & RING -# 13 SHORTCLIP SPRINKLER HEAD SYMBOLS UPRIGHT ON LINE PENDENT ON LINE - UPRIGHT ON STUB UP 0 DRY PENDENT SIDEWALL - 9 UPR &PEND ON DROP 11, TYPE • 41 IttiM NEW Oitti..tr 4 --;ZZA\1\ SPRINKLER DESCRIPTIONS SYM TEMP QTY TAL APPROVALS& INSPECTION 2 4t-Wit4; 3 4 _ WATER DEPT ADDRESS PHON COPIES CONTRACT WITH - ADDRESS CITY PHONE ARCHITECT ADDRESS FIRE PREVENTION - SYSTEMS, INC - - APPROVED The drawings affixed hereto have been reviewed and accepted as meeting or exceeding MIMMUM requirements of the City of Tukwila Fire Dept , BLreau of fire Prevention Additions -or revisions to tnese drawings after this date shaft not be construed as being approved or iew d CITY OF TU W1LA BUREAU OF FIRE PREVENTION PHONE PHONE - Ipia0114 --VJA 151M) APPROVED BY SEATTLE WASH -11123 2 As meeting requirements of this Buiead tor classification ac sprint—red however system changes Or additions as recommendPd on the e woiel sheet(s) will result in Improved ra es Acceptance appites ic as submitted aid for construction and occupancy showi Mewl. t n siw.1 inStalle+1011SUb eCt to inspection for final accepta,ce All comments approvals and acceotances relate exclusivPly to relative effect of var ot cowl rirtc u3on ft e insurance rates ThPy are not to care h., r LIG 0.01 frcpect. to possible habili4 for personal Injury or dam ige to -13 operty is recognized that hazards which mag result in loss sti exist K HOS THIS SHT e ji DRAWN DATE 61004 SCALE Nan North Annex).cad DATE:04/15/11 TIMIE:15:38:09 -- SITE PLAN 0 10 20 30 40 50 L.1.. -1..1 1111 -J_1J SCALE 1' = 40' CONT.INENTAL'MILLS:TI INNOVATION'tENTER CONSTRUCtIQN T1fPg(I-B `' OCCUPAN CY'TyRE:"B': OFFICE' PPRQXIMATFLY'28,6OO SQ./FT: • 8" DCDA BACKFLOW IN VAULT (EXISTING) FIRE DEPARTIIIEN CONNECTION (EXISTING)I 0 .aFr��iale•' BUILDING CROSS SECTION SCALE: NO SCALE SITE SYMBOLS i:J111111111121111trr'trrrtrtr 00 PIPING BY FSW EXISTING PIPING PIPING BY OTHERS FIRE DEPARTMENT CONNECTION POST INDICATOR VALVE EXISTING FIRE HYDRANT GATE VALVE IN ROADWAY BOX -6- NEW FIRE HYDRANT FLOW TEST INFORMATION FLOW DATA PROVIDE BY: HIGHLINE WATER DEPT. STATIC PRESSURE 140 PSI RESIDUAL PRESSURE 133.6 PSI FLOWING: MIN 1500 GPM NOTE: PER HIGHLINE WATER DEPT, DESIGN PRESSURE REDUCED TO 80 PSI SCOPE OF WORK FIRE SYSTEMS WEST (FSW) WILL RELOCATE SPRINKLER ON ARM -OVERS ON AN EXISTING WET SPRINKLER SYSTEM FOR TENANT IMPROVEMENT IN A EXISTING BUILDING. CLARIFICATIONS -ALL AREAS PROTECTED BY A WET SYSTEM MUST BE MAINTAINED BY OTHERS AT A MINIMUM 40°F TO PREVENT FREEZING. EXCLUSIONS - PAINTING OR LABELING OF PIPE AND/OR EQUIPMENT - ELECTRICAL WIRING OF ANY KIND INCLUDING BUT NOT LIMITED TO WATERFLOW SWITCH, ELECTRIC BELL, AND TAMPER SWITCHES - CENTRAL STATION MONITORING EQUIPMENT, WIRING AND SERVICES -ALL UNDERGROUND BEYOND 5 FOOT OUT INCLUDING BUT NOT LIMITED TO:BACKFILL, SELECT FILL, BREAKING PATCHING, SAW CUTTING, LAWN REPAIR, LANDSCAPING, TREE REMOVAL, STERILIZATION, DEVELOPMENT FEES AND CITY CONNECTION. DESIGN CRITERIA PER NFPA 13 AND CITY OF TUKWILA OFFICE WET SYSTEM ORDINARY GROUP I HAZARD UNDERGROUND NOTES a' 1. ALL UNDERGROUND PIPING IS EXISTING AND BEYOND THE SCOPE OF THIS CONTRACT. FLOW TEST INFORMATION FLOW DATA PROVIDE BY: HIGHLINE WATER DEPT. STATIC PRESSURE 140 PSI RESIDUAL PRESSURE 133.6 PSI FLOWING: MIN 1500 GPM NOTE: PER HIGHLINE WATER Q 1N. ith,ot Comments 13 As Noted in Red i2' Per he Attached Letter These pians have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards. Acceptance is subject to errors and omissions which do riot authorize violations of adopted ;andards and ordinances. The responsibility for the adequacy of design rest totally with the designer. F':ddltions, deletion' or revisions to these drawings after tills date will void this accelptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwfia Fire Prevention Bureau. Date: 5- 9-1( By:�,. 511 o 4-. Ct.GcrS5 c",d, reify;. ". PaAeway r ' 8 — S& `-er ,Eur Lesr' y rr I�'.. FAmons; Gavlds raQ191-11>nrlw,a8 S 17th .St • Regal Parkway It , 1 Plaza 12 Nem -est t3 +S 18CIth St ' - til r — '--- Clr,ikoti J;III iI`nr .•• •'691 SQAa)a' .,.. nat:a`e,t�' Trlland Dr ' Cr,ollnaerstol DEPT, DESIGN PRESSURE REDUCED TO 80 PSI TUKWILA FIRE DEPARTMENT Please call 206-575-4407 and give i this si e - q $ac.ttiNo. and exact address for shut- down or restoration approval. NOTICE Weld stamps must be inspected before pipe is hung. Do not paint piping prior to hydrostatic test approval. ... -� Corporcr7fdn r-Sorltlltteittrr it 1• 1_x' C?&i �+i Home ti' S ,1$Oth Sf :office / JOB SIT Sugaie Park dr.15- 11) Les So1i4inb, Tire Center,: ' s' , 180th St t31dge ,_.,til.. = i 'r I;Hnv+al....GreA 11 'riviri;•plaoe' Si,KteS r1/.MHrr101t .c.>BN1ll& ',SOi.10,1 nitri 16 iti'zt+Ii 1 43rd St VICINITY MAP N.T.S. • b I� I� PAID ;Jw` MAY -5 2011 , .a�> TUKWILA FIRE t-(' Z 7-0 �S SITE PLAN 155 HANGER LEGEND TOTAL COUNT OF SPRINKLER HEADS FOR PROJECT REVISIONS GENERAL NOTES DESIGN CRITERIA AND NOTES SYM TYPE MFG MODEL ORIFICE THREAD TEMP FINISH CANOPY QTY MK DATE BY DESCRIPTION -- FILE:2-10-5712 Revision00 SSP TYCO TY -FRB 1/2" / 5.6K 1/2" 155" CHROME CHROME 243 HSW TYCO TY -FRB 1/2" / 5.6K 1/2" 155" CHROME CHROME 2 0 A A APPROVALS REQUIRED: DISTRIBUTION: AUTHORITY TUKWILA OWNER / ARCHITECT OWNER / ARCHITECT 1 FIRE SYSTEMS WEST 1 1. ALL MATERIAL AND EQUIPMENT TO BE NEW AND UNDERWRITERS APPROVED. 2. PIPING DIMENSIONS ARE CENTER TO CENTER EXCEPT RISER & DIMENSIONS SHOWN THUSLY (1'-6") WHICH ARE END TO END. 3.EARTHQUAKE BRACING SHALL BE PROVIDED IN ACCORDANCE WITH NFPA #13. 4 PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH NFPA #13. 5.PIPING SHALL BE IN ACCORDANCE WITH NFPA #13. 6. JOINING OF PIPE AND FITTINGS, THREADED AND WELDED SHALL BE IN ACCORDANCE WITH NFPA #13. 7. OWNER TO PROVIDE ADEQUATE HEAT TO PREVENT WATER IN PIPES FROM FREEZING IN AREAS PROTECTED BY WET PIPE SPRINKLER SYSTEM. 8. STRUCTURAL ADEQUACY OF THE BUILDING TO SUPPORT THE SPRINKLER PIPING IS THE RESPONSIBILITY OF THE OWNER OR HIS STRUCTURAL REPRESENTATIVE. 1. ALL NEW BRANCHLINE PIPING TO BE SCHEDULE 40 JOINED W/ BLACK CAST IRON FITTINGS (UNO). 2. ALL HANGERS AT CONCRETE SLABS TO BE HILTI KWIK BOLT II (UNO). 3. ALL PENDENT HEADS TO BE LOCATED IN CENTER OF TILES - CEILING TILE IS 2' X 2'. BUILDING PERMIT # CONTRACT NAME: CMI INNOVATION CENTER 18000 ANDOVER PARK WEST TUKWILLA WA 98188 CONTRACT WITH: GLY CONSTRUCTION 15 LAKE BELLEVUE DRIVE, SUITE 200 BELLEVUE WA 98008 CONTACT: BRYAN HAAKENSON Phone: (425) 451-8877 Fax: (425) 453-5680 F.ire Systems West 206 Frontage Road North, Suite C Pacific, WA. 98047 (253) 833-1248 Fax: (253) 735-0113 WA CL# FIRESWI 140B1 Q.C. FAB BY: Q.C. INSTALL BY: DESIGNER DATE JOB NUMBER SHEET B. JARAMILLO 04/15/11 2-10-5712 1 of 3 OFFICE OPEN \ OFFICE WALL " ;' , ' 'S �' "' ji , ` /. /// ! �/ DO s-2x4ACT CEILING OPEN O OFFICE OFFICE 1255) 2ss GLASS OFFICE 282 '' ICr F.F. 6" CONCRETE DYER 1.5' PAN DECK / ' / ' / ' %' / / T 'T TIIT' / M --r— MAIL/ • ,� '�i , �• \-2x4ACT CEILING LUNCHROOM r OFFICE HALL COPY 7// / , " ���i/ /' ,-` '; 144 187 185 184 /' /%/�� '; '% , i': /:! 1. //' , ,, ,/, // / /' BUILDING CROSS SECTION SCALE: NO SCALE SITE SYMBOLS i:J111111111121111trr'trrrtrtr 00 PIPING BY FSW EXISTING PIPING PIPING BY OTHERS FIRE DEPARTMENT CONNECTION POST INDICATOR VALVE EXISTING FIRE HYDRANT GATE VALVE IN ROADWAY BOX -6- NEW FIRE HYDRANT FLOW TEST INFORMATION FLOW DATA PROVIDE BY: HIGHLINE WATER DEPT. STATIC PRESSURE 140 PSI RESIDUAL PRESSURE 133.6 PSI FLOWING: MIN 1500 GPM NOTE: PER HIGHLINE WATER DEPT, DESIGN PRESSURE REDUCED TO 80 PSI SCOPE OF WORK FIRE SYSTEMS WEST (FSW) WILL RELOCATE SPRINKLER ON ARM -OVERS ON AN EXISTING WET SPRINKLER SYSTEM FOR TENANT IMPROVEMENT IN A EXISTING BUILDING. CLARIFICATIONS -ALL AREAS PROTECTED BY A WET SYSTEM MUST BE MAINTAINED BY OTHERS AT A MINIMUM 40°F TO PREVENT FREEZING. EXCLUSIONS - PAINTING OR LABELING OF PIPE AND/OR EQUIPMENT - ELECTRICAL WIRING OF ANY KIND INCLUDING BUT NOT LIMITED TO WATERFLOW SWITCH, ELECTRIC BELL, AND TAMPER SWITCHES - CENTRAL STATION MONITORING EQUIPMENT, WIRING AND SERVICES -ALL UNDERGROUND BEYOND 5 FOOT OUT INCLUDING BUT NOT LIMITED TO:BACKFILL, SELECT FILL, BREAKING PATCHING, SAW CUTTING, LAWN REPAIR, LANDSCAPING, TREE REMOVAL, STERILIZATION, DEVELOPMENT FEES AND CITY CONNECTION. DESIGN CRITERIA PER NFPA 13 AND CITY OF TUKWILA OFFICE WET SYSTEM ORDINARY GROUP I HAZARD UNDERGROUND NOTES a' 1. ALL UNDERGROUND PIPING IS EXISTING AND BEYOND THE SCOPE OF THIS CONTRACT. FLOW TEST INFORMATION FLOW DATA PROVIDE BY: HIGHLINE WATER DEPT. STATIC PRESSURE 140 PSI RESIDUAL PRESSURE 133.6 PSI FLOWING: MIN 1500 GPM NOTE: PER HIGHLINE WATER Q 1N. ith,ot Comments 13 As Noted in Red i2' Per he Attached Letter These pians have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards. Acceptance is subject to errors and omissions which do riot authorize violations of adopted ;andards and ordinances. The responsibility for the adequacy of design rest totally with the designer. F':ddltions, deletion' or revisions to these drawings after tills date will void this accelptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwfia Fire Prevention Bureau. Date: 5- 9-1( By:�,. 511 o 4-. Ct.GcrS5 c",d, reify;. ". PaAeway r ' 8 — S& `-er ,Eur Lesr' y rr I�'.. FAmons; Gavlds raQ191-11>nrlw,a8 S 17th .St • Regal Parkway It , 1 Plaza 12 Nem -est t3 +S 18CIth St ' - til r — '--- Clr,ikoti J;III iI`nr .•• •'691 SQAa)a' .,.. nat:a`e,t�' Trlland Dr ' Cr,ollnaerstol DEPT, DESIGN PRESSURE REDUCED TO 80 PSI TUKWILA FIRE DEPARTMENT Please call 206-575-4407 and give i this si e - q $ac.ttiNo. and exact address for shut- down or restoration approval. NOTICE Weld stamps must be inspected before pipe is hung. Do not paint piping prior to hydrostatic test approval. ... -� Corporcr7fdn r-Sorltlltteittrr it 1• 1_x' C?&i �+i Home ti' S ,1$Oth Sf :office / JOB SIT Sugaie Park dr.15- 11) Les So1i4inb, Tire Center,: ' s' , 180th St t31dge ,_.,til.. = i 'r I;Hnv+al....GreA 11 'riviri;•plaoe' Si,KteS r1/.MHrr101t .c.>BN1ll& ',SOi.10,1 nitri 16 iti'zt+Ii 1 43rd St VICINITY MAP N.T.S. • b I� I� PAID ;Jw` MAY -5 2011 , .a�> TUKWILA FIRE t-(' Z 7-0 �S SITE PLAN 155 HANGER LEGEND TOTAL COUNT OF SPRINKLER HEADS FOR PROJECT REVISIONS GENERAL NOTES DESIGN CRITERIA AND NOTES SYM TYPE MFG MODEL ORIFICE THREAD TEMP FINISH CANOPY QTY MK DATE BY DESCRIPTION -- FILE:2-10-5712 Revision00 SSP TYCO TY -FRB 1/2" / 5.6K 1/2" 155" CHROME CHROME 243 HSW TYCO TY -FRB 1/2" / 5.6K 1/2" 155" CHROME CHROME 2 0 A A APPROVALS REQUIRED: DISTRIBUTION: AUTHORITY TUKWILA OWNER / ARCHITECT OWNER / ARCHITECT 1 FIRE SYSTEMS WEST 1 1. ALL MATERIAL AND EQUIPMENT TO BE NEW AND UNDERWRITERS APPROVED. 2. PIPING DIMENSIONS ARE CENTER TO CENTER EXCEPT RISER & DIMENSIONS SHOWN THUSLY (1'-6") WHICH ARE END TO END. 3.EARTHQUAKE BRACING SHALL BE PROVIDED IN ACCORDANCE WITH NFPA #13. 4 PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH NFPA #13. 5.PIPING SHALL BE IN ACCORDANCE WITH NFPA #13. 6. JOINING OF PIPE AND FITTINGS, THREADED AND WELDED SHALL BE IN ACCORDANCE WITH NFPA #13. 7. OWNER TO PROVIDE ADEQUATE HEAT TO PREVENT WATER IN PIPES FROM FREEZING IN AREAS PROTECTED BY WET PIPE SPRINKLER SYSTEM. 8. STRUCTURAL ADEQUACY OF THE BUILDING TO SUPPORT THE SPRINKLER PIPING IS THE RESPONSIBILITY OF THE OWNER OR HIS STRUCTURAL REPRESENTATIVE. 1. ALL NEW BRANCHLINE PIPING TO BE SCHEDULE 40 JOINED W/ BLACK CAST IRON FITTINGS (UNO). 2. ALL HANGERS AT CONCRETE SLABS TO BE HILTI KWIK BOLT II (UNO). 3. ALL PENDENT HEADS TO BE LOCATED IN CENTER OF TILES - CEILING TILE IS 2' X 2'. BUILDING PERMIT # CONTRACT NAME: CMI INNOVATION CENTER 18000 ANDOVER PARK WEST TUKWILLA WA 98188 CONTRACT WITH: GLY CONSTRUCTION 15 LAKE BELLEVUE DRIVE, SUITE 200 BELLEVUE WA 98008 CONTACT: BRYAN HAAKENSON Phone: (425) 451-8877 Fax: (425) 453-5680 F.ire Systems West 206 Frontage Road North, Suite C Pacific, WA. 98047 (253) 833-1248 Fax: (253) 735-0113 WA CL# FIRESWI 140B1 Q.C. FAB BY: Q.C. INSTALL BY: DESIGNER DATE JOB NUMBER SHEET B. JARAMILLO 04/15/11 2-10-5712 1 of 3 First Floor North Annex).cad DATE:04/15/11 TIME:15:39:48 -- 0 0 c .0 0-5712 Revi 5 0 r--1 - 1 -1 97 "+: OQ r 2 112 41z7"1• 14 10'.1 -.211':" Q�ALIrY pb �IUAL(TY M DiUM OFFICI .;-''+ SMALL OFFICE 114 i 111 .ti SPECIAL SERVICESa 4 %. _ WORKROOM P•+ F;, O� PEN OFFII 2j mom= 11 CR .ATI ('VICES 0 OPEtI OFFICE WAITINGICAFE 1IEDIUri R&P MEDIUM 'OFFICE - 1001 1002 CROSSHATCHED AREA NOT IN CONTRACT FITTER PLEASE NOTE: 1. ALL NEW CEILINGS ARE AT 9'.O" AFF 2. ALL HANGERS MUST BE NO MORE THEN 12" FROM END OF PIPE. � J 2 0-4Y2 2 I= 0.2'hl N l+tib ti • 2 1-4'/: 2" AGF TEST & DRAIN VA. 8" WATERFLOW INDICATOR 8" BFY. VA. wl BUILT-IN TAMPER SWITCH PIPE DRAIN TO EXISTING CONNECTION REVISED SYSTEM RISER DETAIL SCALE: 1/2"=1-0" FIRST FLOOR REMOTE AREA LEVEL 1 SPRINKLER PLAN -INNOVATION CENTER SCALE: 118" = 1'-0" Design Basis Occupancy: Total Sprinklers: Number Of Sprinklers Calculated: K -Factor: Orifice Size: Design Density: Average Density: Area of Application: Demand at Base Of Riser or Point Of Connection Total Demand Flow(gpm): Pressure(psi): Water Supply Information At Time Of Design Static Pressure(ps1): Residual Pressure(psi): Supply Flow(gpm): Total Demand Flow(gpm): Total Demand Pressure(psi): First Floor - Ordinary Group I 161 19 5.6 0.5 0.15gpmift2 0.26gpmfft2 1500,001t2 (Actual 1591.51ft') 408.04 31.66 80.00 73.60 1500.00 658.04 42.06 TYPICAL DROP DETAIL NO SCALE 1ST FLOOR HANGER LEGEND SPRINKLER HEADS REVISIONS GENERAL NOTES DESIGN CRITERIA AND NOTES SYM TYPE MFG MODEL ORIFICE THREAD TEMP SSP TYCO TY -FRB 1/2"/5.6K 1/2" 155* FINISH CHROME CANOPY CHROME QTY 142 MK DATE BY DESCRIPTION 0 SSU EXIST 0 A A APPROVALS REQUIRED: OWNER / ARCHITECT DISTRIBUTION: TUKWILA OWNER / ARCHITECT FIRE SYSTEMS WEST 1. ALL MATERIAL AND EQUIPMENT TO BE NEW AND UNDERWRITERS APPROVED. 2. PIPING DIMENSIONS ARE CENTER TO CENTER EXCEPT RISER & CIMENSIONS SHOWN THUSLY (1'-6") WHICH ARE END TO END. 3.EARTHQUAKE BRACING SHALL BE PROVIDED IN ACCORDANCE WITH NFPA #13. 4. PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH NFPA #13. 5.PIPING SHALL BE IN ACCORDANCE WITH NFPA #13. 6. JOINING OF PIPE AND FITTINGS, THREADED AND WELDED SHALL BE IN ACCORDANCE WITH NFPA #13. 7. OWNER TO PROVIDE ADEQUATE HEAT TO PREVENT WATER IN PIPES FROM FREEZING IN AREAS PROTECTED BY WET PIPE SPRINKLER SYSTEM. 8. STRUCTURAL ADEQUACY OF THE BUILDING TO SUPPORT THE SPRINKLER PIPING IS THE RESPONSIBILITY OF THE OWNER OR HIS STRUCTURAL REPRESENTATIVE. 1. ALL NEW BRANCHLINE PIPING TO BE SCHEDULE 40 JOINED Wl BLACK CAST IRON FITTINGS (UNO). 2. ALL HANGERS AT CONCRETE SLABS TO BE HILTI KWIK BOLT II (UNO). 3. ALL PENDENT HEADS TO BE LOCATED IN CENTER OF TILES - CEILING TILE IS 2' X 2'. BUILDING PERMIT # CONTRACT NAME: CMI INNOVATION CENTER 18000 ANDOVER PK W TUKWILA WA 98188 CONTRACT WITH: GLY CONSTRUCTION 15 LAKE BELLEVUE DRIVE, SUITE 200 BELLEVUE WA 98005 PROJECT MGR BRYAN HAAKENSON Phone: (425) 451-8877 Fax: (425) 453-5680 Fire Systems West 206 Frontage Road North, Suite C Pacific, WA. 98047 (253) 833-1248 Fax: (253) 735-0113 WA CL# FIRESWI 140B1 Q.C. FAB BY: Q.C. INSTALL BY: DESIGNER DATE JOB NUMBER B. JARAMILLO 04/15/11 2-10-5712 SHEET 2 of 3 112" KWIK BOLT • a . 71' v a • • 4 ° '. .b • Al 112' KWWIK BOLT //////////// ////// // ,/ /i TOLCO FIG. 980 SWAY BRACE END /), ii CONC DECK f FLAT OR CORK _ TOLCO FIG. 980 SWAY BRACE END ta _;y WEDGE ANCHOR W/ ROD COUPLING /1.1 1" BRACE PIPE @ 7'-0" 45 TO 69 DEG. /' 0/ TOLCO FIG. 980 1" BRACE PIPE © 7'-0" ,/o59DEG. TOLCO FIG. 1000 FAST CLAMP LATERAL SWAY CONCRETE CONNECTION *-- BRACE TYPE -CA ALL THREAD ROD JI1II RING HANGER 4u) • 4 -■ • SWAY BRACE END 00 O HANGER R WEDGE ANCHOR LONGITUDINAL CONCRETE -._- TOLCO FIG. 4A PIPE CLAMP SWAY BRACE CONNECTION TYPE -CA 2 0-4Y2 2 I= 0.2'hl N l+tib ti • 2 1-4'/: 2" AGF TEST & DRAIN VA. 8" WATERFLOW INDICATOR 8" BFY. VA. wl BUILT-IN TAMPER SWITCH PIPE DRAIN TO EXISTING CONNECTION REVISED SYSTEM RISER DETAIL SCALE: 1/2"=1-0" FIRST FLOOR REMOTE AREA LEVEL 1 SPRINKLER PLAN -INNOVATION CENTER SCALE: 118" = 1'-0" Design Basis Occupancy: Total Sprinklers: Number Of Sprinklers Calculated: K -Factor: Orifice Size: Design Density: Average Density: Area of Application: Demand at Base Of Riser or Point Of Connection Total Demand Flow(gpm): Pressure(psi): Water Supply Information At Time Of Design Static Pressure(ps1): Residual Pressure(psi): Supply Flow(gpm): Total Demand Flow(gpm): Total Demand Pressure(psi): First Floor - Ordinary Group I 161 19 5.6 0.5 0.15gpmift2 0.26gpmfft2 1500,001t2 (Actual 1591.51ft') 408.04 31.66 80.00 73.60 1500.00 658.04 42.06 TYPICAL DROP DETAIL NO SCALE 1ST FLOOR HANGER LEGEND SPRINKLER HEADS REVISIONS GENERAL NOTES DESIGN CRITERIA AND NOTES SYM TYPE MFG MODEL ORIFICE THREAD TEMP SSP TYCO TY -FRB 1/2"/5.6K 1/2" 155* FINISH CHROME CANOPY CHROME QTY 142 MK DATE BY DESCRIPTION 0 SSU EXIST 0 A A APPROVALS REQUIRED: OWNER / ARCHITECT DISTRIBUTION: TUKWILA OWNER / ARCHITECT FIRE SYSTEMS WEST 1. ALL MATERIAL AND EQUIPMENT TO BE NEW AND UNDERWRITERS APPROVED. 2. PIPING DIMENSIONS ARE CENTER TO CENTER EXCEPT RISER & CIMENSIONS SHOWN THUSLY (1'-6") WHICH ARE END TO END. 3.EARTHQUAKE BRACING SHALL BE PROVIDED IN ACCORDANCE WITH NFPA #13. 4. PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH NFPA #13. 5.PIPING SHALL BE IN ACCORDANCE WITH NFPA #13. 6. JOINING OF PIPE AND FITTINGS, THREADED AND WELDED SHALL BE IN ACCORDANCE WITH NFPA #13. 7. OWNER TO PROVIDE ADEQUATE HEAT TO PREVENT WATER IN PIPES FROM FREEZING IN AREAS PROTECTED BY WET PIPE SPRINKLER SYSTEM. 8. STRUCTURAL ADEQUACY OF THE BUILDING TO SUPPORT THE SPRINKLER PIPING IS THE RESPONSIBILITY OF THE OWNER OR HIS STRUCTURAL REPRESENTATIVE. 1. ALL NEW BRANCHLINE PIPING TO BE SCHEDULE 40 JOINED Wl BLACK CAST IRON FITTINGS (UNO). 2. ALL HANGERS AT CONCRETE SLABS TO BE HILTI KWIK BOLT II (UNO). 3. ALL PENDENT HEADS TO BE LOCATED IN CENTER OF TILES - CEILING TILE IS 2' X 2'. BUILDING PERMIT # CONTRACT NAME: CMI INNOVATION CENTER 18000 ANDOVER PK W TUKWILA WA 98188 CONTRACT WITH: GLY CONSTRUCTION 15 LAKE BELLEVUE DRIVE, SUITE 200 BELLEVUE WA 98005 PROJECT MGR BRYAN HAAKENSON Phone: (425) 451-8877 Fax: (425) 453-5680 Fire Systems West 206 Frontage Road North, Suite C Pacific, WA. 98047 (253) 833-1248 Fax: (253) 735-0113 WA CL# FIRESWI 140B1 Q.C. FAB BY: Q.C. INSTALL BY: DESIGNER DATE JOB NUMBER B. JARAMILLO 04/15/11 2-10-5712 SHEET 2 of 3 (6) NOT I CONTRACT AREA OF WORK iro '' .. - r ' ••••1 • n .•L.. 0,..........-r • •7 A ,_ A .11.1175:4 sa.--, mo(list -1,,, `. -- sca so t slim ass sa =ST s --- l'4 rb c:r szt 4.____ -------------- 1% ----,,-. - (Zig- No , C:ig.. •;i- SMALL OFFICE ITTER PLEASE NOTE: REPLACE ALL EXISTING PENDENT STANDARD RESPONSE SPRINKLERS WITH NEW QUICK RESPONSE PENDANT SPRINKLERS IN N.I.C. AREA. ...II I. 11111 SIM !kid - OFFICE 1 SAIIPLE LAB STORAGE OPEN 0 FIC Annir AIIIMIA11111.1111121111111M1111111/ LEVEL 2 SPRINKLER PLAN - INNOVATION CENTER SCALE: 1/8" = 1'-0" NOT IN CONTRACT AREA OF WORK CROSSHATCHED AREA NOT IN CONTRACT FITTER PLEASE NOTE: 1. ALL NEW CEILINGS ARE AT 9'-0" AFF 2. ALL HANGERS MUST BE NO MORE THEN 12" FROM END OF PIPE. SECOND FLOOR REMOTE AREA Design Basis Occupancy: Total Sprinklers: Number Of Sprinklers Calculated: K -Factor: Orifice Size: Design Density: Average Density: Area of Application: Demand at Base Of Riser or Point Of Connection Total Demand Flow(gpm): Pressure(psi): Water Supply Information At Time Of Design Static Pressure(psi): Residual Pressure(psi): Supply Flow(gpm): Total Demand Flow(gpm): Total Demand Pressure(psi): Second Floor - Ordinary Group I 202 23 5.6 0.5 0.15gpmlft2 0.35gpmfftz 1500.00ft2 (Actual 1501A1ft) 519.38 41.80 80.00 73.60 1500.00 769.38 52.44 TYPICAL DROP DETAIL NO SCALE 18 GA. METAL PAN DECK 318" X 4" ALL THREAD ROD ea 2 il 11116mmaiffionalit, 1.... 3/8" NUT1 AND WASHERS TYPICAL 2" AF ON FIG.552 TAPPED SIDE BEAM BRACKET OR LISTED EQUAL 318" ALL THREAD ROD 1" MAXIMUM ALLOWED PIPE SIZE PER NFPA 9.2.1.4 HANGER RING 1" MAXIMUM ALLOWED PIPE SIZE HANGER X SIDE BEAM BRACKET TO PAN DECK 2ND FLOOR HANGER LEGEND SPRINKLER HEADS REVISIONS GENERAL NOTES DESIGN CRITERIA AND NOTES SYM TYPE MFG MODEL ORIFICE THREAD TEMP FINISH CANOPY QTY MK DATE BY DESCRIPTION 0 SSP HSN TYCO TYCO TY -FRB 1Y -FRB 1/2" / 5.6K 1/2" / 5.6K 1/2" 155* 1/2" 155* CHROME CHROME CHROME 101 CHROME 2 A A SSP EXIST A A APPROVALS REQUIRED: DISTRIBUTION: AUTHORITY OWNER / ARCHITECT TUKWILA OWNER / ARCHITECT TOTAL 103 FIRE SYSTEMS WEST 1. ALL MATERIAL AND EQUIPMENT TO BE NEWAND UNDERWRITERS APPROVED. 2. PIPING DIMENSIONS ARE CENTER TO CENTER EXCEPT RISER & DIMENSIONS SHOWN THUSLY (1-6") WHICH ARE END TO END. 3. EARTHQUAKE BRACING SHALL BE PROVIDED IN ACCORDANCE WITH NFPA #13. 4. PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH NFPA #13. 5. PIPING SHALL BE IN ACCORDANCE WITH NFPA #13. 6. JOINING OF PIPE AND FITTINGS, THREADED AND WELDED SHALL BE IN ACCORDANCE WITH NFPA #13. 7. OWNER TO PROVIDE ADEQUATE HEAT TO PREVENT WATER IN PIPES FROM FREEZING IN AREAS PROTECTED BY WET PIPE SPRINKLER SYSTEM. 8. STRUCTURAL ADEQUACY OF THE BUILDING TO SUPPORT THE SPRINKLER PIPING IS THE RESPONSIBILITY OF THE OWNER OR HIS STRUCTURAL REPRESENTATIVE. 1. ALL NEW BRANCHLINE PIPING TO BE SCHEDULE 40 JOINED W/ BLACK CAST IRON FITTINGS (UNO). 2. ALL HANGERS AT CONCRETE SLABS TO BE HILTI KWIK BOLT II (UNO). 3. ALL PENDENT HEADS TO BE LOCATED IN CENTER OF TILES - CEILING TILE IS 2 X 2'. BUILDING PERMIT # CONTRACT NAME: CMI INNOVATION CENTER 18000 ANDOVER PK W TUKWILA WA 98188 CONTRACT WITH: GLY CONSTRUCTION 15 LAKE BELLEVUE DRIVE, SUITE 200 BELLEVUE WA 98005 PROJECT MGR BRYAN HAAKENSON Phone: (425) 451-8877 Fax: (425) 453-5680 Fire Systems West 206 Frontage Road North, Suite C Pacific, WA. 98047 (253) 833-1248 Fax: (253) 735-0113 WA CL# FIRESWI 140B1 DESIGNER B. JARAMILLO DATE 04/15/11 JOB NUMBER 2-10-5712 SHEET 3 of 3 o WithoutComments Fir As Noted in Red 0 Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards.' Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the iidequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings after this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to fleld test and inspection by The Tukwila Fire Prevention Bt eau. Date» ` V < ( By: / /VI TUKWILA FIRE DEPARTMENT Please call 206-575-4407 and give this Fire Permit No, and exact address for shut- down or restoration approval. -)( / 1f atevtce4 -lti &.‹ 1,0•,y,i add1...)j4Sit • Dis4e.1( 6rr4- L die ci4&.r o+, otedIcklecl FA c.(' c,id L 5 L�✓w�-i' ta-curers _ % 1.4' ho+ glvYa•li do+,.e , GAaKy.e o✓t' kt1Sw‘ h k ha ISche. NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. 1/1 111llillmilllo tp, ii,fi/ll I lie /i/illllllllllllllllihhllhI Fir tar an "If 1luuuu���� a equipment Supplled By Sins xGrinnei A Tyco International Company Project Contact Information Generic Project Information: Drawing/Engineering Information: Technician Scheduling: Blake Erickson Zack Olson Yvonne Thompson berickson@simpkkxgrirreIL.com zolson@simplexgrinnell.com ythompson@simplexgrinnell.com (206) 291-1415 (206) 291-1430 (206) 291-1450 PAID 1 UKVVILH FORE Simplexerinnell BE SAFE. ATyco International Company SimplexGrinnell 9520 10th Avenue South, Suite 100 Seattle, Wa. 98108 SALES: 206-291-1400 SERVICE: 206-291-1400 © 2002 3D PLEXGRINNELL IR FAX: 206-291-1500 ALL RIGHTS RESERVED DRAWING LIST CO 2 to 0 03 957065203 SHEET NAME DRAWING NAME ELECTRONIC DRAWING NAME INCLUDED IN THIS PROJECT FA—COV-01 TITLE SHEET FA—COVER X FA—COV-02 COVER SHEET FA—COVER X FA—RIS-01 RISER SHEET FA—COVER X FA—DET-01 DETAIL SHEET FA—COVER X FA—F-01 1ST FLOOR PLAN FA—FLOOR X FA—F-02 2ND FLOOR PLAN FA—FLOOR X Simplexerinnell BE SAFE. ATyco International Company SimplexGrinnell 9520 10th Avenue South, Suite 100 Seattle, Wa. 98108 SALES: 206-291-1400 SERVICE: 206-291-1400 © 2002 3D PLEXGRINNELL IR FAX: 206-291-1500 ALL RIGHTS RESERVED Q a CO 2 to 0 03 957065203 664 ez 5 0 1 A i 1a 0 REVIEW COMMENTS p02 mr- ..4> at FIRE ALARM SYSTEM TITLE SHEET CONTINENTAL MILLS CORP ANNEX 18000 ANDOVER PARK WEST TUKWILA, WA 98188 DATE: 10-29-2004 SITE/PROJECT NUMBER: 458-4058194/904390901 SHEET NUMBER: FA—COV-01 GENERAL FIRE ALARM SYSTEM NOTES 1) FIRE ALARM SYSTEM IS POWER LIMITED. METALLIC RACEWAY SHALL BE USED IF REQUIRED BY CODE, SPECIFICATIONS AND CONTRACT DOCUMENTS OR AHJ. 2) ALL RACEWAYS MUST BE FREE OF MOISTURE 3) REFER TO SIMPLEXGRINNELL FIRE ALARM DATA SHEETS FOR PROPER TYPE AND SIZES OF REQUIRED DEVICE MOUNTING ELECTRICAL BOXES. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR PROPER INSTALLATION OF ALL DEVICES. 4) AC VOLTAGE IS NOT PERMITTED IN THE SAME RACEWAY AS FIRE ALARM WIRING. 5) UNRELATED (NON -FIRE ALARM) WIRING SHALL NOT BE IN THE SAME RACEWAY AS FIRE ALARM WIRING. 6) ALL CONTRACTOR FIELD WIRING MUST ENTER ALARM CONTROL PANEL BACKBOX FOLLOWING POWER -LIMITED AND NON POWER -LIMITED WIRING REQUIREMENTS. REFER TO INSTALLATION INSTRUCTIONS FOR MORE INFORMATION. 7) ZONE CIRCUITS AND SIGNAL CIRCUITS ARE ELECTRICALLY SUPERVISED. BRANCH CIRCUITS SHALL BE LOOPED TO MAINTAIN INTEGRITY OF SUPERVISED CIRCUITS--T-TAPPING OF ZONE CIRCUITS AND SIGNAL CIRCUITS IS NOT PERMITTED. 8) REFER TO FACP MODULE DIAGRAMS, INCLUDED WITH FACP, FOR SPECIFICATIONS AND INFORMATION ON INDIVIDUAL PANEL MODULES. VERIFY ALL CONNECTIONS WITH A SIMPLEXGRINNELL FIELD TECHNICAL REPRESENTATIVE PRIOR TO TERMINATION. 9) ALL FIRE ALARM WIRING SHALL TEST FREE OF OPENS, SHORTS AND GROUNDS. 10) ALL WIRING SHALL BE LABELED AND TAGGED 11) ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR INSTALLATION AND MAKING ALL FINAL CONNECTIONS PRIOR TO JOB CHECKOUT AND FINAL TESTING BY A SIMPLEXGRINNELL FIELD TECHNICAL REPRESENTATIVE. CALL A MINIMUM OF 5 DAYS IN ADVANCE TO SCHEDULE A SIMPLEXGRINNELL TECHNICIAN AT (206) 291-1400 12) ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR MAKING ALL ARRANGEMENTS FOR INSPECTION, TEST AND CERTIFICATION OF THE FIRE ALARM SYSTEM BY ALL APPROPRIATE AUTHORITIES. • 13) UPON WRITTEN REQUEST, SIMPLEXGRINNELL WILL PROVIDE WRITTEN INSTRUCTIONS REGARDING THE APPROPRIATE WIRE/CABLE FOR INSTALLATION OF THE EQUIPMENT/SYSTEM(S) IDENTIFIED IN THESE DRAWINGS. SIMPLEXGRINNELL SHALL NOT BE RESPONSIBLE FOR PROBLEMS OR DAMAGES RESULTING FROM THE USE OF WIRE/CABLE OTHER THAN THAT WHICH HAS BEEN IDENTIFIED IN WRITING BY SIMPLEXGRINNELL FOR A SPECIFIC APPLICATION. 14) ALL WIRING SHALL MEET ALL APPLICABLE NATIONAL ELECTRIC CODE ARTICLES FOR FIRE ALARM AND LOW VOLTAGE WIRING. ARCHITECT: T.I. FIRE ALARM SYSTEM DESIGNED BY: SIMPLEXGRINNELL SEATTLE, WA T.I. FIRE ALARM SYSTEM INSTALLED BY: EQUIPMENT FOR FIRE ALARM SYSTEM SUPPUED BY: JOHNSON ELECTRIC KIRKLAND, WA SIMPLEXGRINNELL SEATTLE, WA WASHINGTON STATE ELECTRICAL CONTRACTORS NUMBER: #SIMPLL*981 SG TI -ESE DRAWINGS DO NOT SUPERSEDE THE CONTRACT DRAWINGS AID SPECRCAITOM, Tl -EY ARE WENDED AS A SUPPLEMENT ONLY ANO MUST BE USED IN CONJUNMION WITH TIS CONTRACT DOMENTS.11EY DO NOT 'TM CONTRACTORS OSUGATIONS TO TO TIE PROJECTS ELECTRICAL CONTRACTOR ASBUILTS - ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING SIMPLEXGRINNELL WITH ACCURATE REDLINED DRAWINGS. DRAWINGS SHALL BE REDLINED AS NECESSARY TO SHOW THE FOLLOWING: * DEVICE LOCATIONS - ADDS/DELETES. * CIRCUIT NUMBERS - ADDRESSABLE/SIGNAL/AUXILIARY/ZONE. * WIRE/CONDUIT - ACCURATE ROUTING. * WIRE FILL - USING WIRE CODE. * EOL RESISTOR LOCATIONS. SIMPLEXGRINNELL WILL PROVIDE (UPON REQUEST) A BLANK SET OF FLOOR PLANS TO BE REDLINED. SIMPLEXGRINNELL WILL INCORPORATE ALL REDLINED CHANGES INTO THE RECORD AUTOCAD SET OF DRAWINGS. ELECTRICAL CONTRACTOR - ELECTRICAL CONTRACTOR IS TO SCHEDULE A PRELIMINARY SITE MEETING WITH A SIMPLEXGRINNELL TECHNICAL REPRESENTATIVE. THESE MEETINGS ARE FOR REVIEWING EQUIPMENT LISTS, INSTALLATION PROCEDURES, AND PROVIDING ANSWERS TO QUESTIONS RELATIVE TO SYSTEM INSTALLATION. - PLEASE ALLOW A MINIMUM OF FIVE WORKING DAYS ADVANCE NOTICE TO SCHEDULE A TECHNICAL REPRESENTATIVE. - TO SCHEDULE A MEETING PLEASE CONTACT OUR SERVICE DEPARTMENT AT (206) 291-1400. - DO NOT USE FIRE ALARM CABINET AS TERMINAL CABINET NOTES: - FIRE ALARM DRAWINGS ARE SCHEMATIC ONLY. - ALL CABLE SUBSTITUTIONS MUST BE APPROVED BY SIMPLEX ENGINEERING IN WRITING. - NOTE: MOUNT HORN/STROBES, SPEAKER/STROBES AND STROBES AT 80" TO BOTTOM OF DEVICE. - NOTE: MOUNT PULL STATIONS AT 48" TO TOP OF DEVICE. Fire Alarm Control Panel Auxiliary Circuits AUX1 Not Available AUX2 - Not Available AUX3 - Spare AUX4 - Aux Power AUX5 - Not Available AUX6 - Aux Power AUX7 - Spare AUX8 Spare AUX9 Spare AUX10 - Spare AUX11 - Spare AUX12 - Spare AUX13 - Spare AUX14 - Spare IDNET Channel #M1 First Floor: M1-1 to M1-18 Second Floor: M1-30 to M1-38 I/O Points 101 102 103 104 105 106 107 108 109 1010 1011 1012 1013 1014 1015 1016 1017 1018 1019 1020 1021 1022 1023 1024 Input from Security Panel: Input from Security Panel: Input from Security Panel: Input from Security Panel: Input from Security Panel: Input from Security Panel: Input from Security Panel: Input from Security Panel: Input from Security Panel: Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Reception Panic Button North Door "Forced Open" East Door "Forced Open" South Door "Forced Open" West Door "Forced Open" North Door "Left Open" East Door "Left Open" South Door "Left Open" West Door "Left Open" Sequence of Operation Manual Station Smoke Detection 1st Fir Elevator Lobbies Smoke Detection Elev Lobbies Except 1st Fir Smoke Detection Elevator Mach Room Smoke Detection Elevator Shaft Smoke Detection Elevator Power Monitor Duct Smoke Detection Flow Switch Tamper Switch System Trouble Door Alarm From Access Control Activation of Local Alarm at FACP (LCD Display & Audible Indication)X X X X X X /X. Z CV Activation of Local Alarm at Annunciator x x x x x x DATE: 10-29-2004 SITE/PROJECT NUMBER: 458-4058194/904390901 x SHEET NUMBER: FA -COV -02 Activate AudibleNisible Devices v " ,x Fan Shutdown x x x x x X x Initiate Primary Elevator Recall x x Initiate Alternate Elevator Recall x v Activate Elevator Hat Ugh'. x V /� Priority 2 indication at FACP x Priority 2 Alarm To Central Station Monitor v X! Priority 2 Alarm Display at LCD Annunciator x Transmit Alarm Signal To Central Station Monitor v /� x y /X v /X y !X v X x Trouble Indication at FACP v Trouble Indication at Annunciator x Transmit Trouble Signal To Central Station Monitor x Supv Indication at FACP x x x Supv Indication at Annunciator x x i 'i Transmit Supv Signal To Central Station Monitor x x x BATTERY CALCULATIONS - FACP Does the system have an Emergency Generator that meets NEC 700.01? _yes X no How many hours of battery standby are required? 4 X 24 -_48 CO (4 hours minimum vv/ Emergency Generators) ty Part # Description Standby Total Alarm Current (A) Standby (A) Current (A) Total Alarm (A) 1 4100-9111 1 4603-9101 2 4098-9756 2 4098-9843 3 2088-9008 Fire Alarm Control Panel AudibleNisible Device Load LCD Annunciator TrueAlarm Duct Smoke Sensor Duct Detector Relay Remote Relay Total Standby Current Required= Total Alarm Current Required= Total= 20% Depletion Factor= Total Amp/Hour Required= Total Amp/Hour Batteries Provided= 0.4680 0.0000 0.0300 0.0024 0.0000 0.0000 Total Standby= 0.5028 6.7680 0.4680 0.0000 0.0300 0.0048 0.0000 0.0000 0.5028 X X 0.7500 5.7430 0.1700 0.0150 0.0150 0.0150 0.7500 5.7430 0.1700 0.0300 0.0300 0.0450 Total Alarm= 6.7680 Time (Hrs) 24.0000 12.0672 0.0833 0.5638 12.6310 2.5262 15.1572 (1) set 33.0000 -u -a '0 u) o 10 r CO Is .0 SD.D 0 0 0 in to - c `c c c 1 1 0 i ADDRESSABLE DEVICES ADDRESSABLE DEVICES PX PX PX PX PX PX ,i-- TO FAN SHUTDOWN ,t. PX PX PX PX PX C ( C 2C NAL' I}i i�iCtllEi; EAR E l GrW JND 120VA�'' 3C n1 1 PX PX PX PX CPX !' t: 2CPX C C EOL EOL C C Eli sp l 1- 3CPX C 4CPX C C iF- EOL C C C 141 VI?75cd C CC C C I I 1/F75cd EOL d-- 5CPX R R '1� TO ELEVATOR POWER MONITOR A \4C TO PRIMARY RECALL EOL TO ALTERNATE RECALL 'is— TO FIREMAN'S HAT LIGHT EOL ()COL 120VAC -- c7-5CPX 4100ES FACP i' 'lCAL 1R/OER 21/A6 A11/4/ 66A..lf: NONE EOL EOL HORN/STROBE CIRCUIT N2-3 HORN/STROBE CIRCUIT N2-2 HORN/STROBE CIRCUIT N2-1 BELL/S1POBE CIRCUIT SIG10 HORN/STROBE CIRCUIT SIG9 HORN/STROBE CIRCUIT SIG5 HORN/STROBE CIRCUIT SIG4 HORN/STROBE CIRCUIT SIG3 R 2ND FLR 1ST FLR A .21191. FACP - CABINET #1 a 0 iJ (i 0 PJ CO 0 IV 4.0 o IV w 0 N CO 4100-1279 c N CO 0 N CO 4100ES FRONT PANEL Symbol Description Legend Part # Backbox EK 15cd N1-1 15cd N1-1 15cd N1-1 15d N1-1 VV?75d 1-2 Multi—Candela Horn/Strobe *Subscript Indicates Circuit # & Candela Setting Multi—Candela Horn/Strobe, Celina Mount *Subscript indicates Circuit # & Candela Setting Multi—Candela Strobe *Subscript Indicates Circuit # & Candela Setting Multi—Candela Strobe Ceiling. Mount *Subscript Indicates Circuit # & Candela Setting Weatherproof Strobe *Subscript Indicates Circuit # Weatherproof Strobe *Subscript Indicates Circuit # Subscript Indiicates Circuit # Addressable Manual Station TrueAlarm Smoke Sensor 00 TrueAlarm Duct Detector Duct Detector Relay Supervised !AM Flow Switch Tamper Switch Post Indicator Valve Relay IAM Remote Relay Dual Circuit Heat Detector LC0 LCD Annunciator NAC Panel 4100ES Fire Alarm Control Panel LIAM e RI EMI FACE 4906-9127 4906-9130 4906-9101 4906-9104 4" sq by EC 4" sq by EC 4" sq by EC Sg by EC RSSWP-2475W—FR WPSBB—R 4906-9105 MB—G10-24—R 4099-9001 4098-9714 w/ 4098-9792 Base 4098-9756 w/ 2098-9798 Tube 4098-9843 4090-9001 By Others By Others By Others 4090-9002 2088-9008 5623 4603-9101 4009-9201 4100-9111 4905-9828 WBB—R 4" sq. w/sg ring by EC 4" oct by EC Self—Contained 4" sq. w/ cover by EC 4" sq. w/ cover by EC By Others By Others By Others 4" sq. w/cover by EC Self—Contained 4" Oct. by EC 6—Gang 3-1/2" deep by EC 16.25" x 13.5" x 4.25" 56"H X 24"W X 11.6875"D Letter Qty Color/Type Wire Code Size Function A 2 Black/Orange TFN C 2 Red/Blue THHN D 4 (2) Red/(2) Blue THHN H 1 WestPenn D975 2 Red/Black THHN P 2 Red/Black THHN X 1 WestPenn D975 16 Zone 14 Horn/Strobe 14 Horn/Strobe Loop 18 Serial Communication 14 14 24VDC Power 18 Addressable Data Line c c 957085203 957065203 4100-5111 IDNET CHANNEL #1 SIG3-5 ^) 'le, 1 o AUX3-.4. 4100-3206 AUX7-14 4100-5101 4100-5115 SIG9-14 AUX6 BACK PANEL 4/CCE-3 PANEL L. L IY UT' l+O 1 0 Simplexerinnell BE SAFE. A Tyco International Company SimplexGrinnell 9520 10th Avenue South, Suite 100 Seattle, Wa. 98108 SALES: 206-291-1400 SERVICE: 206-291-1400 © 2002 SIMPLEXGRINNELL LP FAX: 206-291-1500 ALL RIGHTS RESERVED PROJECT # 957085203 957065203 _ A 5 REVISION DESCRIPTION 0 a M 1 REVIEW COMMENTS c:4 V m rsi i R: -_c" I FIRE ALARM SYSTEM RISER SHEET CONTINENTAL MILLS CORP ANNEX 18000 ANDOVER PARK WEST TUKW LA, WA 98188 APPROVED BY: J.C.P. DRAWN BY: J.C.P. DATE: 10-29-2004 SITE/PROJECT NUMBER: 458-4058194/904390901 SHEET NUMBER: FA -RIS -01 TYPICAL STROBE !MIRING DIAGRAM TYPICAL HORN/STROBE KR/NG DIAGRAM TYPICAL CEILING 5TROBE HIRING DIAGRAM TYPICAL INEATHERPROOP SI I,OBE HIRING DIAGRAM TYPICAL CEILING HORN/5TROBE MIRING DIAGRAM 1(11 omior 111.• .......... c C= (2) #14 AWG (-) (+) KC 2 WC 3 IHC 4 0 -NN 0 +NY 0 -Illi 00010 NY +NM -NM a a a a a o 12 a 0 a a a O 0 0 a 0 0 n n 121._.02 000 HARDWARE ADDRESS 1ST BAND C= (2) #14 AWG (-) (+) KC 2 WC 3 IHC 4 0 -NN 0 +NY 0 -Illi 00010 NY +NM -NM a a a a a o 12 a 0 a a a O 0 0 a 0 0 n n 121._.02 000 HARDWARE ADDRESS NlC5 TB6 0 O O O O 0 0 O 0 N + OUT + N - OUT - TB5 NC WC 7 NC e 4009-9201 IDNet NAC PANEL b1 CONFIG SOFTWARE 00000 TB4 ADDRESSABLE NAC SYSTEM 0 o ASSY 0565-771 A B C D O X= (1) WEST PENN D975 #18 AWG LCD ANNUNCIATOR 4603-9101 SHLD -CONN +COMM TO FACP 24VDC POWER SUPPLY TYPICAL PULL STATION /MIRING DIAGRAM - X= (1) WEST PENN D975 #18 AWG TYPICAL SMOKE DETECTOR ,/MIRING DIAGRAM *BASE (\\40Q0_9792 \ 1.32 !!'/I k___H= (1) WEST PENN D975 #18 AWG (2) #14 AWG eeeee rB3' 1 2 3 4 5 T8 BS= m k§ tioym CPU MOTHERBOARD -r 0 04 0 D a re tionEK vJi; 3 1162.31 22 0 P4 8 7 8 5 4 3 2 1 eeeeeeee TB1 TB1 2 3 4 5 CO <a ZDNet SHIELD II Y 0000 0000 0000 182 1 2 3 4 5 6 7 8 9 10 11 12 coma<mm<<m®a< NAC3 NAC4 NAC5 4100-9111 SYSTEM POWER SUPPLY 120VAC 60Hz (566-070) AUX3 CITY P6 (1) WEST PENN D975 #18 AWG 0 00 0❑ 00 P3 B RY (+) P4 BTRY (-) P5 C= (2) #14 AWG ( BASE / 4098-9792 4 SHLD A , 1-- 11 ii II II V V ISHLD Letter Qty ColoNType Wire Code Size Function A C H P X 2 Black/Orange TFN 2 Red//Blue THHN 4 (2) Red/(2) Blue THHN 1 WestPenn D975 2 Red/Black THHN 2 Red/Black THHN 1 VVestPenn D975 16 14 14 18 14 14 18 Zone Horn/Strobe Horn/Strobe Loop Serial Communication 24VDC Power Addressable Data Line TO NEXT DEVICE OR 10K OHM EOL RESISTOR TYPICAL DUCT DETECTOR JNIRING DIAGRAM 4098-9756 4-W1RE DUCT SENSOR 1ST BAND SW2 16M:=3 9 2® 3® 4=1.1 51® 6I7 7[6111= J 0=51/ 0 NS 00000 -NM +NN -Mr 0000 AM -Nr +N11 0 -Nil 7 8 MAP - 9 10 11 12 +24V NlC5 TB6 0 O O O O 0 0 O 0 N + OUT + N - OUT - TB5 NC WC 7 NC e 4009-9201 IDNet NAC PANEL b1 CONFIG SOFTWARE 00000 TB4 ADDRESSABLE NAC SYSTEM 0 o ASSY 0565-771 A B C D O X= (1) WEST PENN D975 #18 AWG LCD ANNUNCIATOR 4603-9101 SHLD -CONN +COMM TO FACP 24VDC POWER SUPPLY TYPICAL PULL STATION /MIRING DIAGRAM - X= (1) WEST PENN D975 #18 AWG TYPICAL SMOKE DETECTOR ,/MIRING DIAGRAM *BASE (\\40Q0_9792 \ 1.32 !!'/I k___H= (1) WEST PENN D975 #18 AWG (2) #14 AWG eeeee rB3' 1 2 3 4 5 T8 BS= m k§ tioym CPU MOTHERBOARD -r 0 04 0 D a re tionEK vJi; 3 1162.31 22 0 P4 8 7 8 5 4 3 2 1 eeeeeeee TB1 TB1 2 3 4 5 CO <a ZDNet SHIELD II Y 0000 0000 0000 182 1 2 3 4 5 6 7 8 9 10 11 12 coma<mm<<m®a< NAC3 NAC4 NAC5 4100-9111 SYSTEM POWER SUPPLY 120VAC 60Hz (566-070) AUX3 CITY P6 (1) WEST PENN D975 #18 AWG 0 00 0❑ 00 P3 B RY (+) P4 BTRY (-) P5 C= (2) #14 AWG ( BASE / 4098-9792 4 SHLD A , 1-- 11 ii II II V V ISHLD Letter Qty ColoNType Wire Code Size Function A C H P X 2 Black/Orange TFN 2 Red//Blue THHN 4 (2) Red/(2) Blue THHN 1 WestPenn D975 2 Red/Black THHN 2 Red/Black THHN 1 VVestPenn D975 16 14 14 18 14 14 18 Zone Horn/Strobe Horn/Strobe Loop Serial Communication 24VDC Power Addressable Data Line TO NEXT DEVICE OR 10K OHM EOL RESISTOR TYPICAL DUCT DETECTOR JNIRING DIAGRAM 4098-9756 4-W1RE DUCT SENSOR 1ST BAND SW2 16M:=3 9 2® 3® 4=1.1 51® 6I7 7[6111= J 0=51/ 4TH BAND ADDRESS SWITCH 101 1 2 3 4 5 6 4421°4444°y444444 + - I MAP + I ED I LEST Li 7 8 MAP - 9 10 11 12 +24V 13 14 24C 15 16 + -- ALM BROWN GREEN BROWN GOLD N/A 1K BROWN BLACK RED GOLD N/A 1.8K BROWN GREY RED GOLD N/A X= (1) WEST PENN D975 #18 AWG TYPICAL JNEATHERPROOP 5 / /,OBE !NIR/NG DIAGRAM STROBE ± REAR VIEW IL FIRE FIRE FRONT VIEW C= (2) #14 AWG (1) WEST PENN D975 #18 AWG TO FACP 24VDC POWER SUPPLY TYPICAL INEATHERPROOE BELL lN/R/NG DIAGRAM Temma< comas mmaa NAC9 NAC10 NAC11 4100-5101 XPS POWER SUPPLY 120VAC 60Hz AUX 1200,ER 182Y 0V +2A 1211115(,4 eeee eeee e 000 %ELAYR FUYELAY R 11 3 NCNO C NC 12 C C NCNO C S®SAS®®@S LLAY NC 14© C ® 4100--3206 8 SPDT 3 AMP RELAY BOARD N r) *10 CO P CO 1H) 16 N M 7 If) 10 00000000 4100-1290 24 POINT I/O (562-858) MOTHER BD. MI, MEM Mill NM wo Immo mem P3 J2 22 Z .00000000�u P1 RR�y' N ��R?V �NNN 10000(9000 POWER + POWER - P=(2) #14 AWG TO NEXT DEYOE OR 1OK OHN EDI. RESISTOi TO 24VDC POWER TO ELEVATOR PRIMARY RECALL/ ALTERNATE RECALL/FIREMAN'S HAT UGIT (rte) 0 0 00 N/C C N/O �SPOT CONTACTS 10 AMPS 81 115 VAC [I 24 115 230 0 IkI$01! o 0,10 TYPICAL RELAY /AM /MIRING DIAGRAM TO NEXT ADDRESSABU DENCE TYP/CAL IAM d1(/RING DIAGRAM SHIELD Symbol Description Legend Part # Backbox 15cd N1-1 Mufti -Candela Horn/Strobe 4906-9127 *Subscript Indicates Circuit # & Candela Setting Multi -Candela Hom/Strobe, Ceiling Mount 4906-9130 15cd *Subscript Indicates Circuit # & Candela Setting N1-1 15cd N1-1 15c3 111-1 V6,75cd Q• F 1-2 IAM i$ 6 RI LCD NA FALL' Multi -Candela Strobe 4906-9101 *Subscript Indicates Circuit # & Candela Setting Multi -Candela Strobe. Ceiling Mount *Subscript Indicates Circuit ,' & Candela Setting *Subscript Indicates Circuit # Weatherproof Strobe *Subscript Indicates Circuit # Weatherproof Bell *Subscript Indicates Circuit Addressable Manual Station TrueAlarm Smoke Sensor TrueAlotm Duct Detector Duct Detector Relay Supervised IAM Flow Switch Tamper Switch Post Indicator Valve Relay IAM Remote Relay Dual Circuit Heat Detector LCD Annunciator NAC Panel 4100ES Fire Alarm Control Panel 4906-9104 4" sq by EC 4" sq by EC 4" sq by EC Sg by EC RSSWP-2475W-FR WPSBB-R 4906-9105 MB -G10 -24-R 4099-9001 4098-9714 w/ 4098-9792 Base 4098-9756 w/ 2098-9798 Tube 4098-9843 4090-9001 By Others By Others By Others 4090-9002 2088-9008 5623 4603-9101 4009-9201 4100-9111 4905-9828 WBB-R 4" sq. w/sg ring by EC 4" oct by EC Self -Contained 4" sq. w/ cover by EC 4" sq. w/ cover by EC By Others By Others By Others 4" sq. w/cover by EC Self -Contained 4" Oct. by EC 6 -Gang 3-1/2" deep by EC 16.25" x 13.5" x 4.25" 56"H X 24"W X 11.6875"D 1/2 W 10K EOL RESISTOR 4081-9008 (6.81( 1/2W) -866 TYPICAL IAM /MIRING DIAGRAM (1) WEST PENN D975 #18 AWG IDNET+ TYPICAL SPRINKLER SIA/ITCH J'\/RING DIAGRAM TYPICAL IAM DURING DIAGRAM SHIELD SHIELD X= (1) WEST PENN 0975 #18 AWG 7YP/ f L. t/E\e/ICE PVIRINA,P/A6RAM SCALE: NOM: NOTE: ALL DEVICES ARE TYPICAL (6.5� /_21A) 7 SHIELD 1 IDNET- X= (1) WEST PENN D975 #18 AWG —( TYPICAL 5623 SYSTEM SENSOR HEAT DETECTOR /MIRING DIAGRAM 120VAC SHUNT POWER A=(2) #16 AWG1/2W) (6.873 -886 OMHS 1ST BAND 2ND BAND 3RD BAND 4TH BAND 5TH BAND 120 BROWN RED BROWN GOLD N/A 150 BROWN GREEN BROWN GOLD N/A 1K BROWN BLACK RED GOLD N/A 1.8K BROWN GREY RED GOLD N/A 2.2K RED RED RED GOLD N/A 3.3K ORANGE ORANGE RED GOLD N/A 4.7K YELLOW VIOLET RED GOLD N/A 6.8K BLUE GREY RED GOLD N/A 10K BROWN BLACK ORANGE GOLD N/A SHUNT TRIP BREAKER ®NA c N/0 0 1.7 Yk 24 115 230 X= (1) WEST PENN D975 #18 AWG 0 0 SImplexerinnell ®E SAFE. FE. ATyco International Company SimplexGrinnell 9520 10th Avenue South, Suite 100 Seattle, Wa. 98108 SALES: 206-291-1400 SERVICE: 206-291-1400 © 2002 SIMPLEXGRINNEL L LP FAX: 206-291-1500 ALL RIGHTS RESERVED Ma t g a 957065203 957065203 1 A a 0 0 REVISION DESCRIPTION 1 If_ i i s 1 m t- FIRE ALARM SYSTEM DETAIL SHEET CONTINENTAL MILLS CORP ANNEX 18000 ANDOVER PARK VEST TUKWILA, WA 98188 APPROVED BY: J.C.P. DRAWN BY: J.C.P. DATE: 10-29-2004 SITE/PROJECT NUMBER: 458-4058194/904390901 ) c t SHEET NUMBER: FA—DET-01 J S1c1O EOL Siclo wQ ±11'-3"X14'– pct,, )rt_ j'p HX ONFERENCE tR r`'li ±21'--6". -$ �.. SMAL ±1 15cd gG3 OPEN 0 'E _i49' -6"X29'– 1 1==.:11Ocd i^=3 C EATLV ;% OREA,11'0 II .ySREA-IG/E. IL :v SC_I\JII. C.J 7�It' l'--'' I ! .�� l... J Ips I ka —DISPLAY Cc) COPY/PRT AREA PKG/PR ±217 FUTU E FRY ±29'-9 40'-3" 15cd SIG5 li .,4---- I- ,6. - �.Y/IvIVO(KiI l'JR'AGE R;L.'.ii,; I!-wP75cd---- 1 ((0 t 1 L I1 ,0I SUMER I 1 i ,h �-- F I!i I UI / 1----;--,11i ! iiC( '5' P/IEk l20N �I li',"1-Ril ' 1i ; I IRE' it II! s 1 li C ilk/ I(_ N i t' 1 i'"• -)';'s ! 1/' i 1 1 1 _ I �— =_-i� • I • , Ili 75cd SIG4 CONSUMER i DISPLAY- 1 I F�Mib17 \ FIRST FLOOR 1C1-AAN SCALE 1/8"=1=0" GENERAL NOTES: 1. DEVICES SHOWN LIGHT ARE EXISTING REMOVED DURING DEMOLITION AND ARE TO BE RE—USED IN NEW LOCATIONS. SET CANDELA VALUE AS SHOWN ON FLOOR PLANS AND RE—CIRCUIT AS INDICATED. DEVICES WITH FLAG NOTE 2 ARE EXISTING DEVICES IN AREAS THAT ARE NOT PART OF CONTRACT AND WILL NEED TO BE TIED BACK INTO NEW CIRCUITING, BUT SHOULD REMAIN IN THEIR CURRENT LOCATIONS. 2. MOUNT ALL NEW MAIIUAL PULL STATIONS PER ADA RECOMMENDED HEIGHTS. FLAG NOTES: / EXISTING DEVICE NOT IN SCOPE OF WORK TO REMAIN. RE—CONNECT TO NEW CIRCUITING AS INDICATED. FIELD VERIFY WIRE LOCATION FROM IAM TO EXISTING PIV CONNECTION. r_ FIELD 'an' LOCATION Symbol Description Legend Part # Backbox E 15cd N1-1 15cd N1-1 15cd N1-1 ►01 15x1 N1-1 i1P75cd ENO 1-2 EI IAM E.] LCD Multi—Candela Horn/Strobe *Subscript Indicates Circuit # Multi—Candela Horn/Strobe, C *Subscript Indicates Circuit # Multi—Candela Strobe *Subscript Indicates Circuit # Multi—Candela Strobe Ceiling' *Subscript Indicates Circuit # Weatherproof Strobe *Subscript Indicates Circuit # Subscript Indicates Circuit # Weatherproof Bell *Subscript Indicates Circuit # Addressable Manual Station TrueAlarrn Smoke Sensor TrueAlarm Duct Detector Duct Detector Relay Supervised IAM Flow Switch Tamper Switch Post Indicator Valve Relay IAM Remote Relay Dual Circuit Heat Detector LCD Annunciator NAC Panel & Candela Setting eiling Mount & Candela Setting & Candela Setting 4906-9127 4906-9130 4906-9101 Mount 4906-9104 & Candela Setting FACP 1 4100ES Fire Alarm Control Panel 4" sq by EC 4" sq by EC 4" sq by EC Sg by EC RSSWP-2475W—FR WPSBB—R 4906-9105 MB—G10-24—R 4099-9001 4098-9714 w/ 4098-9792 Base 4098-9756 w/ 2098-9798 Tube 4098-9843 4090-9001 By Others By Others By Others 4090-9002 2086-9008 5623 4603-9101 4009-9201 4100-9111 4905-9828 WBB—R 4" sq. w/sg ring by EC 4" oct by EC Self—Contained 4" sq. w/ cover by EC 4" sq. w/ cover by EC By Others By Others By Others 4" sq. w/cover by EC Self—Contained 4" Oct. by EC 6—Gang 3-1/2" deep by EC 16.25" x 13.5" x 4.25" 56"H X 24"W X 11.6875"D Letter Qty Color/Type Wire Code Size Function A 2 Black/Orange TFN C 2 Red/Blue THHN D 4 (2) Red/(2) Blue THHN H 1 WestPenn D975 2 Red/Black THHN P 2 Red/Black THHN X 1 WestPenn D975 16 Zone 14 Horn/Strobe 14 Horn/Strobe Loop 18 Serial Communication 14 14 24VDC Power 18 Addressable Data Line P?( 111-7 M1-6 M1-5 PX fah -4 \--m.—TO TO FIREMAN'S HAT LIGHT �-r�— TO PRIMARY RECALL \--10— TO ALTERNATE RECALL TO €L EV. POWER MONITOR PX 1 2 BE SAFE. A Tyco International Company SimplexGrinnell 9520 10th Avenue South, Suite 100 Seattle, Wa. 98108 SALES: 206-291-1400 SERVICE: 206-291-1400 © 2002 SINPLEXGRINNELL 12 FAX: 206-291-1500 Ail. RIGHTS RESERVED A n .O ai A z 0 o gi i p 1 A m da r- FIRE ALARM SYSTEM FIRST FLOOR PLAN CONTINENTAL MILLS CORP ANNEX 18000 ANDOVER PARK WEST TUKWILA, WA 98188 APPROVED BY: J.C.P. DRAWN BY: J.C.P. DATE: 10-29-2004 SITE/PROJECT NUMBER: 458-4058194/904390901 C L 1 c L SHEET NUMBER: FA—F-01 _N.I.C. - AREA OF WORK r ill' CA EXI STI Nt E3 E N C I -TCS OPEN OFFICE 40'_ G"X18' -6" —_L I [i - ' 15'-_I1 CB r—r`— — — -- -- — — — — To7E, WATER COC LER I�( ,fit J_iSI�E3i'i J — AR L =J 1 �-• L JD 7 SC \A/CASE' KITCHEN ±J3' -6X2,. j , 1 110cd N2-3 OPEN OFFICE 52'-6"X32'-6" I •I LJ EXISTING BENCHES r 7 —JT 7 71 L_____1L_—J I I L N2 -1I —� 1 �` jlL.LlS! OTT,- II •%Y:_.'\J AREA �- ZONE_ :)0M R',?:;r:! 7.,cd N'2.—• ilocd' N2 -1I ,0 "%./A2C 15cd \ Xi I To E .EV. SHUNT TRW 1-34 1•1 30cd N2-1• 15cd N2-1 EOL 1;1 EXISTING FREEZER X 1 1-37 i IL 11Od N2-3 r_2)7,0. L 1 11 JI :tI *MO MP, =n M "M CIMS n - - 1 1- 1 77; --- 6"X23: rI OPEN OFFICE ±44'-6"X21'--6" NE1. / B'ENCHES "17.i.,',..?* - �. .+1_x.22?J'.17.0t. C 'dl N2-2.._... 1 11 11 I 1 II 1 _— 1 ,j — `' —r-- — I I EXISTING E?ENCHE` ! - -N2-3 I ! I N2-2 15cd N2-2 - --- I-- - - -! i C — II I 11 _ _ I 1 _.____----___ ., I 1, I .__ I I I I 'L , 1 II .,, 71�....� .. ,T�a.m. .....-.1 s„:..�1G� .a.. - T -"Tr ___IL,...,,,a,.�.z-, :���.:a ..-7-- — L -..�.r- .`:,:�` n;.: -:;;'t. --,.-;.... .r., LI -71 II GENERAL NOTES: 1. DEVICES SHOWN LIGHT ARE EXISTING REMOVED DURING DEMOLI11ON AND ARE TO BE RE -USED IN NEW LOCATIONS. SET CANDELA VALUE AS SHOWN ON FLOOR PLANS AND RE -CIRCUIT AS INDICATED. DEVICES WITH FLAG NOTE 2 ARE EXISTING DEVICES IN AREAS THAT ARE NOT PART OF CONTRACT AND ,WILL NEED TO BE TIED BACK INTO NEW CIRCUITING, BUT SHCULD REMAIN IN THEIR CURRENT LOCATIONS. 2. MOUNT ALL NEVI MANUAL PULL STATIONS PER ADA RECOMMENDED HEIGHTS. EAG NOTES: EXISTING DEVICE NOT IN SCOPE OF WORK TO REMAIN. RE -CONNECT TO NEW CIRCUITING AS INDICATED. DUCT DETECTOR TO BE MOUNTED ON RETURN AIR SIDE, FIELD VERIFY EXISTING LOCATION. HEAT DETECTION IS REQUIRED IF SHAFT IS SPRINKLED. � II r_ • 1 J� j J I Symbol Description Legend Part # Backbox ►-t ►©4 15cd N1-1 Multi -Candela Hom/Strobe *Subscript Indicates Circuit # & Candela Setting Multi -Candela Hom/Strobe, Ceiling Mount 15cd *Subscript Indicates Circuit # & Gandela Setting N1-1 15cd N1-1 1�1 15cd N1-1 WP 1W750:1 1-2 IAM Multi -Candela Strobe *Subscript Indicates Circuit # & Candela Setting 4906-9127 4906-9130 4906-9101 Multi -Candela Strobe Ceiling. Mount 4906-9104 *Subscript Indicates Circuit & Cande!,k Setting 4" sq by EC 4" sq by EC 4" sq by EC Sg by EC Weatherproof theptIcates RSSWP-2475W-FR WPSBB-RndiCircuit # Weatherproof Strobe *Subscript Indicates Circuit # Subscript Indiicates Circuit # Addressable Maiiuoi Station TrueAlarm Smoke Sensor T rueAlaim Duct Detector Duct Detector Relay Supervised IAM } Flow Switch �*5 Tamper Switch Post Indicator Valve RI Relay IAM Q Remote Relay HQ Dual Circuit Heat Detector E:3 LCD Annunciator NAC Panel CO4100ES Fire Alarm Control Panel 4906-9105 MB -G10 -24-R 4099-9001 4098-9714 w/ 4098-9792 Base 4098-9756 w/ 2098-9798 Tube 4098-9843 4090-9001 By Others By Others By Others 4090-9002 2088-9008 5623 4603-9101 4009-9201 4100-9111 4905-9828 WBB-R 4" sq. w/sg ring by EC 4" oct by EC Self -Contained 4" sq. w/ cover by EC 4" sq. w/ cover by EC By Others By Others By Others 4" sq. w/cover by EC Self -Contained 4" Oct. by EC 6 -Gang 3-1/2" deep by EC 16.25" x 13.5" x 4.25" 56"H X 24"W X 11.6875"D Letter Qty Color/Type Wire Code Size Function A 2 Black/Orange TFN C 2 Red/Blue THHN D 4 (2) Red/(2) Blue THHN H 1 WestPenn 0975 2 Red/Black THHN P 2 Red/Black THHN X 1 WestPenn D975 16 Zone 14 Horn/Strobe 14 Horn/Strobe Loop 18 Serial Communication 14 14 24VDC Power 18 Addressable Data Line V EC'N17 FL- OR i�1 AN SCALE 1/8"=-1=0" Simplexerl tnell BE SAFE. A i yco International Company SimplexGrinnell 9520 10th Avenue South, Suite 100 Seattle, Wa. 98108 SALES: 206-291-1400 SERVICE: 206-291-1400 © 2002 SIMPLEXG L 12 FAX: 206-291-1500 ALL RIGHTS RESERVED PROJECT # 957065203 957065203 1 1 A ____ O 1 CI Z o 1 1 a 6 i a U N. A m FIRE ALARM SYSTEM SECOND FLOOR PLAN CONTINENTAL MILLS CORP ANNEX 18000 ANDOVER PARK WEST TUKWIL A, WA 98188 I APPROVED BY: J.C.P. DRAWN BY: J.C.P. DATE: 10-29-2004 SITE/PROJECT NUMBER: 458-4058194/904390901 SHEET NUMBER: I I FA—F-02 10 11 CCE ?IT Without Comments CI As Noted in Red CI Per The Attached Letter These plans have heed i reviewed by The Tukwila Fire Prevention Bureau for conformance with Current City standards. Acceptance Is subject to errors and orrlissions which do not authorize violations of adopted st;:ndards and ordinances. The responsibility for the :c;eguacy of design rests totally with the designer. Aki«dltions, deletions or revisions to these drawings after this date will void this acceptance and will require a i esubmittal of revised drawings for subsequent approval. 'final acceptance is subject -to field test and Inspection by The Tukwila Fire Prevention Bureau. pate: - C '1 `( By: TUKWILA FIRE DEPARTMENT Please call 206-5754407 and give this Fire Permit No. and exact address for shut- down hutdown or restoration approval. NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing n L -nvira © 6'-0" 1 R Corrugated stainless steel hose with stainless steel braid available in 2', 3',4',5' & 6' legnths FlexHead Sprinkler Drop CONTINENTAL MILLS - INNOVATION CENTER - ROOM 140 O FREEZER CHEST J 32'-G' 4.1'-0" re 2 E SS TAU 4X Multi—Port Bracket Adjustable Hub Sprinkler TYP. FLEXHEAD SPRINKLER DROP NOT TO SCALE E CONTINENTAL MILLS — INNOVATION CENTER — ROOM 140 FIRE SPRINKLER PIPING PLAN SCALE 1/4" = 1'—O" 0 1' 2' 4' 1 1 1 1 I GRAPHIC SCALE 8' Ir>C:er€ S r. elm L: IVIidl'arid.izr r: .:T16 e,d.i)r S1' S. Hamod Fc.dr 2014. :3`si€c' sws13 vCtii3P.s 3rzrs~ 261r`+193k13 VICINITY MAP NO SCALE FIRE SPRINKLER LEGEND EXISTING PIPE: NEW PIPE: X El MI MI MI El NI III IS III MI X OA E ADDED PENDENT SPRINKLER: EXISTING PENDENT SPRINKLER: RELOCATED PENDENT SPRINKLER: R OWNER / OCCUPANT x x x SITE CONTACT: x CELL: x SCOPE 1 RELOCATE (2) SPRINKLERS AND DEMO AS NEEDED IN REMODELED TENANT IMPROVEMENT AREAS AS SHOWN ON PLAN. GENERAL NOTES 1 THE OVER–HEAD SPRINKLER SYSTEM IS EXISTING. 2 THE DESIGN CRITERIA FOR THE T.I. AREAS OF WORK IS BASED ON EXISTING PIPE SIZING. 3 ALL NEW PIPE TO BE SCH 40 PIPE WITH 125 Ib. BLACK CAST IRON FITTINGS OR GROOVED WITH GROOVED FITTINGS & COUPLINGS, AS SHOWN. 4 ALL NEW ARM–OVERS OVER 2-0 SHALL HAVE A HANGER. 5 ALL HANGERS TO BE HANGER #1, UON. ALL HANGERS TO BE INSTALLED IN ACCORDANCE WITH NFPA #13. 6 ALL DESIGN AND INSTALLATION TO BE IN ACCORDANCE WITH NFPA #13 AND THE CITY OF TUKWILA. FIELD / LISTING NOTES 1 THREADED PIPE FROM 1" THRU 2" SIZE TO BE SCH. 40 PIPE. 2 GROOVED END PIPE FROM 1-1/2" THRU 4" TO BE SCH. 10 PIPE. 3 ALL GROOVED COUPLING ARE TO BE "RIGID" TYPE U.N.O. (IMPORT) 4 ALL THREADED FITTINGS ARE TO BE 175# CLASS CAST IRON (IMPORT) 5 ALL 1" NIPPLES NOT IDENTIFIED ARE 0-2 U.N.O. 6 ALL HANGER RODS TO BE FIELD CUT 7 ALL DIMENSIONS ON PIPING ARE CENTER TO CENTER FOR SUBMITTAL DRAWINGS 8 ALL DIMENSIONS ON PIPING ARE CUT LENGTHS FOR INSTALLATION DRAWINGS MIMI•IN FIR Alar 678. Sim SIM lb Slgnat I HYDRAULIC DESIGN DATA IMPORTANT In localities subject to freezing conditions, it is the owner's responsibility to provide heat throughout wet pipe sprinkler systems areas and In enclosures for d pipe deluge and other types of valves controlling water supplies to sprinkler systems. This drawing and the information and design application herein contained Is the property of TYCO FIRE &SECURITY SimplexGrinnell P oP Y / P and/or its subsidiaries and is loaned upon express conditions that the same be retumed to StmplexGrinnell upon request; all information herein contained shall be treated as secret, and confidential; no reproduction of this drawing or any part thereof shall be made without written consent of SimplexGrinnell. Created bythe Sim IexGrinnell , "All rights reserved". copyright y SimplexGrinnell 2001 g CONTRACT RESPONSIBILITIES ITEM SimplexGrInne&I/BY OTHERS SYMBOLS now %vita 05) C.G Gate Vohs L N.R.S. (GV) ND FF. Deat:Cann.(FDC) .�- Poet Indicator Vdve (FIV) 'go Fire Hy<Ikmt (3 Mby) -I. Thrust ` K•Y tial• S.ottond �� tdtlk Roodrroy Box o® Fare Haw Assembly y Inspectors Teat -5- Gobs Vdv. ) �'Angle Valve 3 Dry � Vdv. SPRINKLERS REM. AREA NAME 0. HAZARD CLASSIFICATION DENSITY GPM/SQ.FT. AREA OF APPUC. HOSE ALLOW. SQ. FT. /HD. TOTAL SYSTEM REQUIREMENTS ABBREVIATIONS AC - Above Finished Coling AFF Above Ribbed Floor ttEr SYSTEM TYPE SPECIAL REQUIREMENTS' GPM PSI AT MAKE TYPE MODEL SIN NPT / K—FACTOR TEMP. FINISH ESCUTCHEON NOTES SYMBOL QTY. ■ DFIUGE ■ DOMESTIC PIPE ■ +SLE a ■ SCHEDULE so cc u. SCALE: AS NOTED DRAWN BY: ALAN MAHAFFI'E CHECKED BY: BC - Balm FinishedColin BOB -Bottom of Beam BCD - Bottom of Delle BOJC- Bottan of Jost BDP -Bottom of Puffin HV - Haw V v. NIC Not h Contrast DRY _■ ■ PREAC11ON ■ I T WATER CONNECTION N/A I I Hydraulic R.finka. POM _AL fl Mader zwltalk -pa- ossY oat. Vd,, (os�') 1 tis. D ation '-"�'' Earthquake Brodng _4 Butterfly Vdve TYCO PENDENT TY—FRB TY3231 1 2" K=5.6 / 155' CHROME CHROME MATCH EXISTING ® (� 2 UNDERGROUND WATER MAINS N/A 'y L3 ■CITY ■aTM ■ FM APPROVALS EXCAVATIONS N/A 4 f Haw Norm Valve (ALV) ■GALVANIZED PIPE ■ GALVANIZED FITTINGS BACKFILL N A / e A 1 Mob Designation -kQ - Union WRING N/A Electric Bel OUT N wale Screwed Cap �. water Motor coo WATER SUPPLY INFORMATION: STATIC PRESSURE f RESIDUAL PRESSURE - aB'I - Jobt I■ aALvANizED MATERIALS • SPECIAL FITTINGS ■ F.M. MATERIAL PAINTING N/A *13" E a Pyo Bib. Bottom of Deck —� Gfwmid CcP —4 Screwed Plug -a wQhr Chalk V°We +12'-4" of Pp. Above Ref. Plan. -N- Swing Check Vdve GrocV.d coupling No C ono El'vat1on Ching. In p� ... Flanged Connection .,Ft. D'p'C0m Stoddard PSI PSI. WITH GPMFLOWING CUT IN TEST DATE:out TDB - Top of Bean TDP - Tap of Pwiik TOS - Top of Steel UaFI - unless othw.iw Noted TEST LOCATION: BY: OUT 14 • ■OTHER (not ti"" floor) ® n Baer - RAD D.ptConn.(Flwh) �C) - TOTAL THIS SHEET - 2 n r J 9 A R 7 Q 10 11 12 1 Fire & Security SimplexGrinnell 9520 10th Avenue South, Suite 100 Seattle, Wa. 98108 SALES: 206-291-1400 SERVICE: 206-291-1400 © 2002 SIMPLE%GRINNEIL LP 91 WASHINGTON STATE CERTIFICATE OF COMPETENCY PROTECTION SPRINKLER SYSTEMS i Mahaffie 3-0105-C Level 3 N plexGrinnell, L.P. N W a 3LL*988BG Expires =-� 12/31/14 UM 8 E f EM CONTINENTAL MI cc u. SCALE: AS NOTED DRAWN BY: ALAN MAHAFFI'E CHECKED BY: DATE: 04/29/2014 CONTRACT NUMBER: 977528207 SHEET NUMBER: �a..,.....,,.,' ......1 SHEET 1 OF 1, , 12