Loading...
HomeMy WebLinkAboutPP - 3455 S 148TH ST - CHURCH BY THE SIDE OF THE ROAD - PERMITS AND PLANS3455 S 148TH ST ASSOCIATED PERMITS D11-022 D02-079 03-F-108 11-S-055 11-S-008 03-S-167 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: The Church By The Side Of The Road 3455 S X4544' St /Alen Permit No.: 11-S-055 Date: March 15, 2011 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed oonstruction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 20 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2010 Edition. INSPECTION NUMBER INSPECTION RECORD //-S c}' Retain a copy with permit ,b/ / - U a� PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East, Tukwila, Wa. 98188 206-575-4407 Project/Type /I Sprinklers: of Insp ion: cA ix, Monitor: Address: ? v5 -3— Suite #: S / m 71-- Contact Pe son: Special Instructions: Phone No.: [pproved per applicable codes. Corrections required prior to approval. COMMENTS: 5 - - Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: //--\5-yiis-,„2____ Date: //yh Hrs.: $100.00 RIEINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. Call to schedule a reinspection. Billing Address Attn: Company Name: Address: City: State: Zip: Word/Inspection Record Form.Doc 6/11/10 T.F.D. Form F.P. 113 INSPECTION NUMBER INSPECTION RECORD //-g-- Retain /'S- Retain a copy with p - • • 't v // - o> )— PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East, Tukwila, Wa. 98188 206-575-4407 Project: GkIA-c,L, 8/ .5id, o* --ac /206 4 Type of Inspection: SPr1tila, (ove✓ Address: 3 Li 5_5._ S -pip.. St Suite #: Monitor: Contact Person: Col Coic��iv Special Instructions: Occupancy Type: Phone No.: Approved per applicable codes. Corrections required prior to approval. COMMENTS: — L. reJ-Ltst.,4-S ihS- ,!Lad buev-u hook) rAD Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: 4-)'-7 / Date: c./ j,1, / j Hrs.: / $100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. Call to schedule a reinspection. Billing Address Attn: Company Name: Address: City: State: Zip: Word/Inspection Record Form.Doc 6/11/10 T.F.D. Form F.P. 113 INSPECTION NUMBER INSPECTION RECORD Retain a copy with pe , "t -s-oss.. PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East, Tukwila, Wa. 98188 206-575-4407 Project: ella tAe St`d e_. 0 C _. v2* Type of Inspection: SP Address: 2 ijc-S c /f i) 4,.... Suite #: Contact Person: Special Instructions: Phone No.: Approved per applicable codes. RCorrections required prior to approval. COMMENTS: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: 1- A- 6 o L_ s—le-.-2Aitsc i 44/ b, -4N 4 /, N-ee 2- Druc f._.. Cew 4r'v nl .tet) C e *it c)(l0 f -Plow Ta.14' a -q ti- r-1-4-4---- s ciwlsL /3oa I3)S y/ psz ( ?S' • t • ; p' (le 1-e s-1' OM TTO 'NZ (, r Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: ieft ,.-t c --a_. Date: 447// i Hrs.: 1 $80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from e City of Tukwila Finance Department. Call to schedule a reinspection. Word/Inspection Record Form.Doc 1/13/06 T.F.D. Form F.P. 113 INSPECTION NUMBER INSPECTION RECORD Retain a copy with permit £oL- oic 63-r-- 10(Z) 03—S — `\ol PERMIT NUMBERS CITY OF TUKWILA FIR ' EPARTMENT 444 Andover Park East, Tukwila, Wa. 9818 206-575-4407 Project:\\ ,0'`a Type of Inspection: L'` 1 G�'lv r �j--�A' St cL 2 �; vvte-sA,( �, "`5 Address:Contact 41,-,P, Person: _3 Suite #: .3.6.S5 S 1* Special Instructions: Phone No.: Zola — z 7-1 - 14'12 Approved per applicable codes. Corrections required prior to approval. COMMENTS: AA Z L. \ sV<\- v v Y:` s "tt> 1/4)'f 3N6N cgs �c.k\w� j dvut b -j SF-A.r$ i4o4'\4.erA. )- Oyu C4.a c ►\\ , ok *D "et. r,(.._ Needs Shift Inspection: 01144 Sprinklers: Fire Alarm: .0vakLHood & Duct: Monitor: (eek {J� 1i:A.►,cw‘Ccpre-Fire: Permits: c)14:4 , Occupancy Type: {A Z 1 E 1 R Inspector: m_5 1 Date: 1 Z `I 6-1 Hrs.: ( $80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. Call to schedule a reinspection. Word/Inspection Record Form.Doc 1/13/06 T.F.D. Form F.P. 113 NORCO Fire Protection. Inc. January 6, 2011 Tukwila Fire Department 444 Andover Park East Tukwila, WA 98188 RE: Church By the Side of The Road Porte Cochere 3455 S 148th Tukwila, Washington l+irKWaILA FIRE DEPARTIR, Please call: 575.4407 and give this jolt No. l I— 8 -oog and exact address for shut. `Yun or restoration approval Norco Fire Protection, Inc. has been hired to install a new dry fire sprinkler system for the new porte cochere. However, in order for the contractor to build the new porte cochere they need to demo and cap the existing dry system. Norco is preparing drawings for the new parte cochere and will be submitting for permit Monday, January 10, 2011. We are requesting permission to shut down existing system and remove system from the porte cochere so they may rebuild its replacement. Sincerer' L/ Edwin P Cdgar NORCO FIRE PROTECTION, INC. PO Box 363 Ravensdale, WA 98051 425-432-7250 Fax 425-413-2230 PO BOX 363, RAVENSDALE, WA 98051 425-432-7250 EMAIL: NORCOFIREINC®AOL.COM NORCO FIRE PROTECTION, INC. 24024 SE 261ST PLACE MAPLE VALLEY, WA 98038 HYDRAULIC CALCULATIONS FOR CHRUCH BY THE SIDE OF THE ROAD TUKWILLA, WASHINGTON FILE NUMBER: N10069 DATE: 3/2/1 -DESIGN DATA - OCCUPANCY CLASSIFICATION: ORDINARY HAZAARD OCCUPANCYL DENSITY: RESIDENTIAL .15 gpm/sq. ft. AREA OF APPLICATION: ENTIRE AREA sq. ft. COVERAGE PER SPRINKLER: 130 sq. ft. NUMBER OF SPRINKLERS CALCULATED: 10 sprinklers TOTAL SPRINKLER WATER FLOW REQUIRED: 214.5 gpm TOTAL WATER REQUIRED (including hose): 464.5 gpm FLOW AND PRESSURE (@ BOR): 214.4 gpm @ 41.2 psi SPRINKLER ORIFICE SIZE: 1/2 inch NAME OF CONTRACTOR: NORCO FIRE PROTECTION, INC. DESIGN/LAYOUT BY: EDWIN P COGAR AUTHORITY HAVING JURISDICTION: TUKWILLA FIRE DEPARTMENT CONTRACTOR CERTIFICATION NUMBER: NORCOFP015JO CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 50110271 ) HRS SYSTEMS, INC. TUCKER, GA 30084 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 3/8/2011 C:\HASS\DATA\2010 CALCS\N10069C.SDF JOB TITLE: CHURCH BY THE SIDE OF THE ROAD WATER SUPPLY ANALYSIS N • O m O U) co A Q' �A H W I-4 -H ro co KC O %// •O 80.00 psi Resid: N N U U LO N in �r v r�i 'C o u,I aro U)v aE N 0 N N U) CO A o) 'C) Ute) U aa) ai N -H lD 0 CO CO N P4 V 4 N B. System O 0 N 0 KC 0 w a a w cn m a4 w -- a U) -d -- O O 0 O O N O O CO 0 0 r -i O 0 — O C a 0 a SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 3/8/2011 C:\HASS\DATA\2010 CALCS\N10069C.SDF JOB TITLE: CHURCH BY THE SIDE OF THE ROAD NFPA WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) A 80.0 68.0 1800.0 79.0 464.5 41.9 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 464.5 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 250.0 GPM OTHER HOSE STREAM ALLOWANCES 0.0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 214.5 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES (FT) (PSI) (GPM) 101 10.5 K= 5.24 16.2 21.1 102 10.5 K= 5.24 16.1 21.0 103 10.5 K= 5.24 16.3 21.2 104 10.5 K= 5.24 16.1 21.0 105 10.5 K= 5.24 16.6 21.3 106 10.5 K= 5.24 16.4 21.2 107 10.5 K= 5.24 17.1 21.7 108 10.5 K= 5.24 17.2 21.7 109 10.5 K= 5.24 17.9 22.2 110 10.5 K= 5.24 17.7 22.0 201 12.0 17.6 202 0.0 22.9 203 0.0 23.2 204 0.0 23.8 205 0.0 24.7 8 0.0 30.0 W 4.0 34.5 B 0.0 41.8 C 0.0 41.6 D 0.0 41.2 E 0.0 37.2 A 0.0 SOURCE 41.9 214.5 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 3/8/2011 C:\HASS\DATA\2010 CALCS\N10069C.SDF JOB TITLE: CHURCH BY THE SIDE OF THE ROAD NFPA PIPE DATA Pipe Tag K-fac Add Fl Add Fl To Fit: L C (F Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (F To Node El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (F Pipe: 1 5.24 21.1' Disch 6.50 100 201 12.0 17.6 0.0 1.000 T: 3.6 3.57 101 10.5 16.2 21.1 1.049 10.07 0.202 Pipe: 2 201 102 5.24 12.0 17.6 10.5 16.1 21.0 Disch 0.0 21.0 Pipe: 3 5.24 21.2 Disch 202 0.0 22.9 0.0 103 10.5 16.3 21.2 Pipe: 4 202 104 5.24 21.0 Disch 0.0 22.9 0.0 10.5 16.1 21.0 1.000 T: 3.6 1.049 1.000 T: 3.6 1.049 1.000 T: 3.6 1.049 7.50 100 3.57 11.07 0.200 6.50 100 3.57 10.07 0.202 7.50 100 3.57 11.07 0.200 Pipe: 5 5.24 21.3 Disch 6.50 100 203 0.0 23.2 0.0 1.000 T: 3.6 3.57 105 10.5 16.6 21.3 1.049 10.07 0.205 Pipe: 6 5.24 21.2 Disch 7.50 100 203 0.0 23.2 0.0 1.000 T: 3.6 3.57 106 10.5 16.4 21.2 1.049 11.07 0.203 Pipe: 7 5.24 21.7 Disch 204 0.0 23.8 0.0 107 10.5 17.1 21.7 Pipe: 8 204 108 5.24 21.7 Disch 0.0 23.8 0.0 10.5 17.2 21.7 Pipe: 9 5.24 22.2 Disch 205 0.0 24.7 0.0 109 10.5 17.9 22.2 Pipe: 10 205 110 5.24 0.0 24.7 10.5 17.7 22.0 Disch 0.0 22.0 Pipe: 11 0.0 0.0 202 0.0 22.9 42.1 201 12.0 17.6 42.1 1.000 T: 3.6 1.049 1.000 T: 3.6 1.049 1.000 T: 3.6 1.049 1.000 T: 3.6 1.049 2.500 2.635 6.50 100 3.57 10.07 0.212 6.26 100 3.57 9.83 0.212 6.50 100 3.57 10.07 0.220 7.50 100 3.57 11.07 0.218 9.67 100 0.00 9.67 0.008 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: 3/8/2011 C:\HASS\DATA\2010 CALCS\N10069C.SDF JOB TITLE: CHURCH BY THE SIDE OF THE ROAD Pipe Tag K-fac Add Fl Add Fl To Fit: L C (F Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (F To Node El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (F Pipe: 12 0.0 42.1 201 9.67 100 203 0.0 23.2 42.2 103 2.500 0.00 202 0.0 22.9 84.3 2.635 9.67 0.029 Pipe: 13 204 203 Pipe: 14 205 204 0.0 0.0 0.0 0.0 0.0 23.8 23.2 0.0 24.7 23.8 84.3 202 42.5 105 126.9 126.9 203 43.4 107 170.2 2.500 2.635 2.500 2.635 9.67 100 0.00 9.67 0.063 8.00 100 0.00 8.00 0.108 Pipe: 15 0.0 170.2 204 14.83 100 8 0.0 30.0 44.2 109 2.500 3E:17.6 17.64 205 0.0 24.7 214.4 2.635 32.47 0.165 Pipe: 16 0.0 0.0 240.00 100 w 4.0 34.5 214.4 205 4.000 8E:75.2 150.36 8 0.0 30.0 214.4 4.260 4T:75.2 390.36 0.016 Pipe: 17 E W 0.0 4.0 0.0 37.2 34.5 0.0 214.4 8 214.4 4.000 4.260 ETC2G 5.00 100 52.63 57.63 0.016 Pipe: 18 0.0 Fixed Pressure Loss Device D 0.0 41.2 214.4 W 4.0 psi, 214.4 gpm E 0.0 37.2 214.4 Pipe: 19 0.0 0.0 C 0.0 41.6 214.4 E D 0.0 41.2 214.4 4.000 2E:18.8 4.260 6.00 100 18.79 24.79 0.016 Pipe: 20 0.0 0.0 200.00 140 B 0.0 41.8 214.4 D D6.000 0.00 C 0.0 41.6 214.4 6.280 200.00 0.001 Pipe: 21 Source 0.0 25.00 140 A 0.0 41.9 214.4 C D6.000 0.00 B 0.0 41.8 214.5 6.280 25.00 0.001 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 DATE: 3/8/2011 C:\HASS\DATA\2010 CALCS\N10069C.SDF JOB TITLE: CHURCH BY THE SIDE OF THE ROAD NOTES (HASS): (1) Calculations were performed by the HASS 8.1 computer program under license no. 50110271 granted by HRS Systems, Inc. 208 South Public Square Petersburg, TN 37144 (931) 659-9760 (2) The system has been calculated to provide an average imbalance at each node of 0.007 gpm and a maximum imbalance at any node of 0.144 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 12.6 ft/sec at pipe 15. NECTION TO EXISTING 21 ' SUPPLY PIPE 0 18" BEAM 18" BEAM 1 t 1 ►a" 9'-8" 91.011 REFLECTED CEILING PLAN SCALE = 1/8" =1'-O' 4'-8" PORTE COCHERE PI DING PLAN SCALE =1/8' =1'-0" PIPING,U o ALLALPIPE I TOBE" TO BE SCHEDULE 40 INSPECTORS TEST AND DRUM DRIP HANGERMATE FIG. 100 ALL THREAD ROD FlG. 200 ADJUSTABLE RING HANGER HANGERMATE, ROD & RING WOOD CONSTRUCTION HANGER 91 DETAIL FIG. 910 SWIVEL SWAY BRACE FITTING NUT 1/2' X 4�MINIMUM BEAM BRACE PIPE \) FIG. 1000 ��"FAST CLAMP"& SWAY BRACE ATTACHMENT LATERAL EARTHQUAKE BRACE BRACE PIPE THREADED ONE END NUT & BOLT THUR BEAM 1/2' X 4 MINIMUM rowc° no. 1000 "rAS cLAAIP"W' 3. MAX 4 WAY EARTHQUAKE BRACE 0100 no. 907 LATERAL/LONGITUDINAL EARTHQUAKE BRACE 5,4" 13'4" 5'4" PORTE COCHERE SECTION SCALE =1/8" =1'-0" DRY PIPING TO BE SLOPED PER NFPA #13 LINES TO BE PITCHED AT 1/2' IN 10'-0' MINIMUM MAINS TO BE PITCHED AT 1/4" IN 10'-0" MINIMUM GENERAL NOTES 1. SYSTEM DESIGNED TO NFPA #13 EDITION. ORDINARY HAZARD OCCUPANCY TYPICAL UNLESS NOTED OTHERWISE 2. SYSTEM HYDRAULICALLY CALCULATED TO NFPA #13 STANDARDS AND LOCAL FIRE DEPARTMENT REQUIREMENTS 3. UNDERGROUND IS EXISTING AND NOT PART OF THIS SUBMITTAL 4. SPRINKLER MADS SPACED PER NFPA #13 AND MANUFACTURERS REQUIREMENTS FOR THEIR APPUCATION 5. SYSTEM TO BE HMG AND SWAY BRACED TO NFPA#13 STANDARDS AND MANUFACTURERS REQUIREMENTS 6. ALL CLEANING AND PAINTING OF PIPE IF REQUIRED TO BE BY OTHERS 7. ALL ELECTRICAL WIRING CONDUIT MATERIALS AND INSTALLATION TO BE BY OTHERS, NORCO WILL PROVIDE SWITCHES 8. ALL TESTING OF SYSTEMS TO BE PER NFPA #13 AND LOCAL FIRE DEPARTMENT REQUIREMENTS 9. ALL MATERIAL AND EQUIPMENT TO BE NEW AND UL AND OR FM APPROVED 10. PIPE HANGERS AND METHOD OF ATTACHMENT TO BE PER NFPA #13 AVM MANUFACTURERS REQUIREMENTS 11. STRUCTURE ADEQUACY OF THE BUILDING TO SUPPORT THE SPRINKLER SYSTEM PIPING IS THE RESPONSIBITY OF THE OWNER AND OR STRUCTUAL REPRESENTATIVE Er( Without Comments As Noted in Red Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau fnr conformance with current City ai:andards. Acceptance is subject to errors and cI► fissions which do not authorize violations of adopted :::artdards and ordinances. The responsibility for the adequacy of design totally with the designer. Additions, deletions of revisions to these drawings after this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by rhe Tukwila Fire Prevention Bureau. 1 UKVVILA FIRE DEPARTMEIY, Pease call: 575-4407 and give this job S-oss and exact address for shut' iown or restoration aourovl N iA W ?o S 8 10' 12' 14' 16' 18' NOTES SYMBOLS ® SYSTEMS RISER o RISE UP • DROP DN L--7 2 WAY EARTHQUAKE BRACE 4 WAY EARTHQUAKE BRACE GROOVED COUPLING \#01 HANGER TYPE AND LOCATION' Al > WELD TAG NUMBER 0 UPRIGHT HEAD ® PENDENT HEAD D SIDE WALL HEAD REVISIONS LEGEND pA UPRIGHT OVER PENDENT 25 PIPE SIZING 1 HYDRAULIC CALC NODE REVISION NUMBER 1❑ BRANCH LINE NUMBER DATE DESCRIPTION 2/28/2011 REVISED ATTIC AREA TO STANDARD UPRIGHTS BY ("' SPRINKLER SYMBOLS SYM •CNT • M NAME METAL TEMP K NPT ORIF MFG. MODEL# CONN. Q® 10 DRY PEND CHROME 160 5.6 1/2" 1/2 RELIABLE F3QR Defaul 0 10 UPRIGHT BRASS 200' 5.6 1/2" 1/2 RELIABLE F1FR Defaul 20 TOTAL HEADS ON PROJECT ORCO Fire Protection, Inc. PO Box 363 Ravensdale, WA 98051 425-432-7250 OWNER INFORMATION NAME CHURCH SIDE OF THE RD ADDRESS 4314 SOUTH 131ST PL TUKWILLA, WA PHONE 208-227-1472 FIRE DEPT INFORMATION NAME TUKWILA FIRE DEPT ADDRESS444 ANDOVER PAARK EAST TUKWILA, WA 98188 PHONE (208) 575.4404 WATER DEPT. INFORMATION NAME ADDRESS PHONE WATER INFORMATON STATIC 90 RESIDUAL 20 GPM 4850 BACKFLOW 8" SOURCE AS BUILT DRAWING TUKWILLA WATER DEPT BUILDING INFORMATION SQ. FT. 838 SOFT. TYPE Wood FTmIn3 OCCUPANCY .L1GNTI' HAZARD otz u LEGAL DESCRIPTION TAX PARCEL # -FE a4 s � � ,U 8 SeaTac A ,erton Heigfif 1\uT S 15Dt u— 1 « 3955 5198th 5t, Seattle, WA.. 3455 5 148th St Seattle, WA 98168 99) 48th -St C(na.4 'n38-2Y5I' ro.o CC7JId:1Yl a'40!!BC eR All 15=1 th 5rT fl VICINITY MAP NO SCALE N A r E CHURCH BY THE SIDE OF THE ROAD 3455 S 145TH ST TUKWILA, WASHINGTON CONTRACTOINORCO FIRE PROTETION, INC. PORTE COCHERE PIPING PLAN PERMIT NO. CONTRACT NO. N10069 APPROVAL TUKWILA FD DRAWN BY ED COGAR SCALE 1/8" = 1'-0" DATE 2/16/2011 REVISED PLOTTED FP1of1 �� N/ s��5/ 3455 S 148TH ST ASSOCIATED PERMITS D11-022 D02-079 03-F-108 11-S-055 11-S-008 03-S-167 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: The Church By The Side Of The Road 3455 S X4544' St /Alen Permit No.: 11-S-055 Date: March 15, 2011 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed oonstruction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 20 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2010 Edition. INSPECTION NUMBER INSPECTION RECORD //-S c}' Retain a copy with permit ,b/ / - U a� PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East, Tukwila, Wa. 98188 206-575-4407 Project/Type /I Sprinklers: of Insp ion: cA ix, Monitor: Address: ? v5 -3— Suite #: S / m 71-- Contact Pe son: Special Instructions: Phone No.: [pproved per applicable codes. Corrections required prior to approval. COMMENTS: 5 - - Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: //--\5-yiis-,„2____ Date: //yh Hrs.: $100.00 RIEINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. Call to schedule a reinspection. Billing Address Attn: Company Name: Address: City: State: Zip: Word/Inspection Record Form.Doc 6/11/10 T.F.D. Form F.P. 113 INSPECTION NUMBER INSPECTION RECORD //-g-- Retain /'S- Retain a copy with p - • • 't v // - o> )— PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East, Tukwila, Wa. 98188 206-575-4407 Project: GkIA-c,L, 8/ .5id, o* --ac /206 4 Type of Inspection: SPr1tila, (ove✓ Address: 3 Li 5_5._ S -pip.. St Suite #: Monitor: Contact Person: Col Coic��iv Special Instructions: Occupancy Type: Phone No.: Approved per applicable codes. Corrections required prior to approval. COMMENTS: — L. reJ-Ltst.,4-S ihS- ,!Lad buev-u hook) rAD Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: 4-)'-7 / Date: c./ j,1, / j Hrs.: / $100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. Call to schedule a reinspection. Billing Address Attn: Company Name: Address: City: State: Zip: Word/Inspection Record Form.Doc 6/11/10 T.F.D. Form F.P. 113 INSPECTION NUMBER INSPECTION RECORD Retain a copy with pe , "t -s-oss.. PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East, Tukwila, Wa. 98188 206-575-4407 Project: ella tAe St`d e_. 0 C _. v2* Type of Inspection: SP Address: 2 ijc-S c /f i) 4,.... Suite #: Contact Person: Special Instructions: Phone No.: Approved per applicable codes. RCorrections required prior to approval. COMMENTS: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: 1- A- 6 o L_ s—le-.-2Aitsc i 44/ b, -4N 4 /, N-ee 2- Druc f._.. Cew 4r'v nl .tet) C e *it c)(l0 f -Plow Ta.14' a -q ti- r-1-4-4---- s ciwlsL /3oa I3)S y/ psz ( ?S' • t • ; p' (le 1-e s-1' OM TTO 'NZ (, r Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: ieft ,.-t c --a_. Date: 447// i Hrs.: 1 $80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from e City of Tukwila Finance Department. Call to schedule a reinspection. Word/Inspection Record Form.Doc 1/13/06 T.F.D. Form F.P. 113 INSPECTION NUMBER INSPECTION RECORD Retain a copy with permit £oL- oic 63-r-- 10(Z) 03—S — `\ol PERMIT NUMBERS CITY OF TUKWILA FIR ' EPARTMENT 444 Andover Park East, Tukwila, Wa. 9818 206-575-4407 Project:\\ ,0'`a Type of Inspection: L'` 1 G�'lv r �j--�A' St cL 2 �; vvte-sA,( �, "`5 Address:Contact 41,-,P, Person: _3 Suite #: .3.6.S5 S 1* Special Instructions: Phone No.: Zola — z 7-1 - 14'12 Approved per applicable codes. Corrections required prior to approval. COMMENTS: AA Z L. \ sV<\- v v Y:` s "tt> 1/4)'f 3N6N cgs �c.k\w� j dvut b -j SF-A.r$ i4o4'\4.erA. )- Oyu C4.a c ►\\ , ok *D "et. r,(.._ Needs Shift Inspection: 01144 Sprinklers: Fire Alarm: .0vakLHood & Duct: Monitor: (eek {J� 1i:A.►,cw‘Ccpre-Fire: Permits: c)14:4 , Occupancy Type: {A Z 1 E 1 R Inspector: m_5 1 Date: 1 Z `I 6-1 Hrs.: ( $80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. Call to schedule a reinspection. Word/Inspection Record Form.Doc 1/13/06 T.F.D. Form F.P. 113 NORCO Fire Protection. Inc. January 6, 2011 Tukwila Fire Department 444 Andover Park East Tukwila, WA 98188 RE: Church By the Side of The Road Porte Cochere 3455 S 148th Tukwila, Washington l+irKWaILA FIRE DEPARTIR, Please call: 575.4407 and give this jolt No. l I— 8 -oog and exact address for shut. `Yun or restoration approval Norco Fire Protection, Inc. has been hired to install a new dry fire sprinkler system for the new porte cochere. However, in order for the contractor to build the new porte cochere they need to demo and cap the existing dry system. Norco is preparing drawings for the new parte cochere and will be submitting for permit Monday, January 10, 2011. We are requesting permission to shut down existing system and remove system from the porte cochere so they may rebuild its replacement. Sincerer' L/ Edwin P Cdgar NORCO FIRE PROTECTION, INC. PO Box 363 Ravensdale, WA 98051 425-432-7250 Fax 425-413-2230 PO BOX 363, RAVENSDALE, WA 98051 425-432-7250 EMAIL: NORCOFIREINC®AOL.COM NORCO FIRE PROTECTION, INC. 24024 SE 261ST PLACE MAPLE VALLEY, WA 98038 HYDRAULIC CALCULATIONS FOR CHRUCH BY THE SIDE OF THE ROAD TUKWILLA, WASHINGTON FILE NUMBER: N10069 DATE: 3/2/1 -DESIGN DATA - OCCUPANCY CLASSIFICATION: ORDINARY HAZAARD OCCUPANCYL DENSITY: RESIDENTIAL .15 gpm/sq. ft. AREA OF APPLICATION: ENTIRE AREA sq. ft. COVERAGE PER SPRINKLER: 130 sq. ft. NUMBER OF SPRINKLERS CALCULATED: 10 sprinklers TOTAL SPRINKLER WATER FLOW REQUIRED: 214.5 gpm TOTAL WATER REQUIRED (including hose): 464.5 gpm FLOW AND PRESSURE (@ BOR): 214.4 gpm @ 41.2 psi SPRINKLER ORIFICE SIZE: 1/2 inch NAME OF CONTRACTOR: NORCO FIRE PROTECTION, INC. DESIGN/LAYOUT BY: EDWIN P COGAR AUTHORITY HAVING JURISDICTION: TUKWILLA FIRE DEPARTMENT CONTRACTOR CERTIFICATION NUMBER: NORCOFP015JO CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 50110271 ) HRS SYSTEMS, INC. TUCKER, GA 30084 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 3/8/2011 C:\HASS\DATA\2010 CALCS\N10069C.SDF JOB TITLE: CHURCH BY THE SIDE OF THE ROAD WATER SUPPLY ANALYSIS N • O m O U) co A Q' �A H W I-4 -H ro co KC O %// •O 80.00 psi Resid: N N U U LO N in �r v r�i 'C o u,I aro U)v aE N 0 N N U) CO A o) 'C) Ute) U aa) ai N -H lD 0 CO CO N P4 V 4 N B. System O 0 N 0 KC 0 w a a w cn m a4 w -- a U) -d -- O O 0 O O N O O CO 0 0 r -i O 0 — O C a 0 a SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 3/8/2011 C:\HASS\DATA\2010 CALCS\N10069C.SDF JOB TITLE: CHURCH BY THE SIDE OF THE ROAD NFPA WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) A 80.0 68.0 1800.0 79.0 464.5 41.9 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 464.5 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 250.0 GPM OTHER HOSE STREAM ALLOWANCES 0.0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 214.5 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES (FT) (PSI) (GPM) 101 10.5 K= 5.24 16.2 21.1 102 10.5 K= 5.24 16.1 21.0 103 10.5 K= 5.24 16.3 21.2 104 10.5 K= 5.24 16.1 21.0 105 10.5 K= 5.24 16.6 21.3 106 10.5 K= 5.24 16.4 21.2 107 10.5 K= 5.24 17.1 21.7 108 10.5 K= 5.24 17.2 21.7 109 10.5 K= 5.24 17.9 22.2 110 10.5 K= 5.24 17.7 22.0 201 12.0 17.6 202 0.0 22.9 203 0.0 23.2 204 0.0 23.8 205 0.0 24.7 8 0.0 30.0 W 4.0 34.5 B 0.0 41.8 C 0.0 41.6 D 0.0 41.2 E 0.0 37.2 A 0.0 SOURCE 41.9 214.5 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 3/8/2011 C:\HASS\DATA\2010 CALCS\N10069C.SDF JOB TITLE: CHURCH BY THE SIDE OF THE ROAD NFPA PIPE DATA Pipe Tag K-fac Add Fl Add Fl To Fit: L C (F Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (F To Node El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (F Pipe: 1 5.24 21.1' Disch 6.50 100 201 12.0 17.6 0.0 1.000 T: 3.6 3.57 101 10.5 16.2 21.1 1.049 10.07 0.202 Pipe: 2 201 102 5.24 12.0 17.6 10.5 16.1 21.0 Disch 0.0 21.0 Pipe: 3 5.24 21.2 Disch 202 0.0 22.9 0.0 103 10.5 16.3 21.2 Pipe: 4 202 104 5.24 21.0 Disch 0.0 22.9 0.0 10.5 16.1 21.0 1.000 T: 3.6 1.049 1.000 T: 3.6 1.049 1.000 T: 3.6 1.049 7.50 100 3.57 11.07 0.200 6.50 100 3.57 10.07 0.202 7.50 100 3.57 11.07 0.200 Pipe: 5 5.24 21.3 Disch 6.50 100 203 0.0 23.2 0.0 1.000 T: 3.6 3.57 105 10.5 16.6 21.3 1.049 10.07 0.205 Pipe: 6 5.24 21.2 Disch 7.50 100 203 0.0 23.2 0.0 1.000 T: 3.6 3.57 106 10.5 16.4 21.2 1.049 11.07 0.203 Pipe: 7 5.24 21.7 Disch 204 0.0 23.8 0.0 107 10.5 17.1 21.7 Pipe: 8 204 108 5.24 21.7 Disch 0.0 23.8 0.0 10.5 17.2 21.7 Pipe: 9 5.24 22.2 Disch 205 0.0 24.7 0.0 109 10.5 17.9 22.2 Pipe: 10 205 110 5.24 0.0 24.7 10.5 17.7 22.0 Disch 0.0 22.0 Pipe: 11 0.0 0.0 202 0.0 22.9 42.1 201 12.0 17.6 42.1 1.000 T: 3.6 1.049 1.000 T: 3.6 1.049 1.000 T: 3.6 1.049 1.000 T: 3.6 1.049 2.500 2.635 6.50 100 3.57 10.07 0.212 6.26 100 3.57 9.83 0.212 6.50 100 3.57 10.07 0.220 7.50 100 3.57 11.07 0.218 9.67 100 0.00 9.67 0.008 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: 3/8/2011 C:\HASS\DATA\2010 CALCS\N10069C.SDF JOB TITLE: CHURCH BY THE SIDE OF THE ROAD Pipe Tag K-fac Add Fl Add Fl To Fit: L C (F Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (F To Node El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (F Pipe: 12 0.0 42.1 201 9.67 100 203 0.0 23.2 42.2 103 2.500 0.00 202 0.0 22.9 84.3 2.635 9.67 0.029 Pipe: 13 204 203 Pipe: 14 205 204 0.0 0.0 0.0 0.0 0.0 23.8 23.2 0.0 24.7 23.8 84.3 202 42.5 105 126.9 126.9 203 43.4 107 170.2 2.500 2.635 2.500 2.635 9.67 100 0.00 9.67 0.063 8.00 100 0.00 8.00 0.108 Pipe: 15 0.0 170.2 204 14.83 100 8 0.0 30.0 44.2 109 2.500 3E:17.6 17.64 205 0.0 24.7 214.4 2.635 32.47 0.165 Pipe: 16 0.0 0.0 240.00 100 w 4.0 34.5 214.4 205 4.000 8E:75.2 150.36 8 0.0 30.0 214.4 4.260 4T:75.2 390.36 0.016 Pipe: 17 E W 0.0 4.0 0.0 37.2 34.5 0.0 214.4 8 214.4 4.000 4.260 ETC2G 5.00 100 52.63 57.63 0.016 Pipe: 18 0.0 Fixed Pressure Loss Device D 0.0 41.2 214.4 W 4.0 psi, 214.4 gpm E 0.0 37.2 214.4 Pipe: 19 0.0 0.0 C 0.0 41.6 214.4 E D 0.0 41.2 214.4 4.000 2E:18.8 4.260 6.00 100 18.79 24.79 0.016 Pipe: 20 0.0 0.0 200.00 140 B 0.0 41.8 214.4 D D6.000 0.00 C 0.0 41.6 214.4 6.280 200.00 0.001 Pipe: 21 Source 0.0 25.00 140 A 0.0 41.9 214.4 C D6.000 0.00 B 0.0 41.8 214.5 6.280 25.00 0.001 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 DATE: 3/8/2011 C:\HASS\DATA\2010 CALCS\N10069C.SDF JOB TITLE: CHURCH BY THE SIDE OF THE ROAD NOTES (HASS): (1) Calculations were performed by the HASS 8.1 computer program under license no. 50110271 granted by HRS Systems, Inc. 208 South Public Square Petersburg, TN 37144 (931) 659-9760 (2) The system has been calculated to provide an average imbalance at each node of 0.007 gpm and a maximum imbalance at any node of 0.144 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 12.6 ft/sec at pipe 15. NECTION TO EXISTING 21 ' SUPPLY PIPE 0 18" BEAM 18" BEAM 1 t 1 ►a" 9'-8" 91.011 REFLECTED CEILING PLAN SCALE = 1/8" =1'-O' 4'-8" PORTE COCHERE PI DING PLAN SCALE =1/8' =1'-0" PIPING,U o ALLALPIPE I TOBE" TO BE SCHEDULE 40 INSPECTORS TEST AND DRUM DRIP HANGERMATE FIG. 100 ALL THREAD ROD FlG. 200 ADJUSTABLE RING HANGER HANGERMATE, ROD & RING WOOD CONSTRUCTION HANGER 91 DETAIL FIG. 910 SWIVEL SWAY BRACE FITTING NUT 1/2' X 4�MINIMUM BEAM BRACE PIPE \) FIG. 1000 ��"FAST CLAMP"& SWAY BRACE ATTACHMENT LATERAL EARTHQUAKE BRACE BRACE PIPE THREADED ONE END NUT & BOLT THUR BEAM 1/2' X 4 MINIMUM rowc° no. 1000 "rAS cLAAIP"W' 3. MAX 4 WAY EARTHQUAKE BRACE 0100 no. 907 LATERAL/LONGITUDINAL EARTHQUAKE BRACE 5,4" 13'4" 5'4" PORTE COCHERE SECTION SCALE =1/8" =1'-0" DRY PIPING TO BE SLOPED PER NFPA #13 LINES TO BE PITCHED AT 1/2' IN 10'-0' MINIMUM MAINS TO BE PITCHED AT 1/4" IN 10'-0" MINIMUM GENERAL NOTES 1. SYSTEM DESIGNED TO NFPA #13 EDITION. ORDINARY HAZARD OCCUPANCY TYPICAL UNLESS NOTED OTHERWISE 2. SYSTEM HYDRAULICALLY CALCULATED TO NFPA #13 STANDARDS AND LOCAL FIRE DEPARTMENT REQUIREMENTS 3. UNDERGROUND IS EXISTING AND NOT PART OF THIS SUBMITTAL 4. SPRINKLER MADS SPACED PER NFPA #13 AND MANUFACTURERS REQUIREMENTS FOR THEIR APPUCATION 5. SYSTEM TO BE HMG AND SWAY BRACED TO NFPA#13 STANDARDS AND MANUFACTURERS REQUIREMENTS 6. ALL CLEANING AND PAINTING OF PIPE IF REQUIRED TO BE BY OTHERS 7. ALL ELECTRICAL WIRING CONDUIT MATERIALS AND INSTALLATION TO BE BY OTHERS, NORCO WILL PROVIDE SWITCHES 8. ALL TESTING OF SYSTEMS TO BE PER NFPA #13 AND LOCAL FIRE DEPARTMENT REQUIREMENTS 9. ALL MATERIAL AND EQUIPMENT TO BE NEW AND UL AND OR FM APPROVED 10. PIPE HANGERS AND METHOD OF ATTACHMENT TO BE PER NFPA #13 AVM MANUFACTURERS REQUIREMENTS 11. STRUCTURE ADEQUACY OF THE BUILDING TO SUPPORT THE SPRINKLER SYSTEM PIPING IS THE RESPONSIBITY OF THE OWNER AND OR STRUCTUAL REPRESENTATIVE Er( Without Comments As Noted in Red Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau fnr conformance with current City ai:andards. Acceptance is subject to errors and cI► fissions which do not authorize violations of adopted :::artdards and ordinances. The responsibility for the adequacy of design totally with the designer. Additions, deletions of revisions to these drawings after this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by rhe Tukwila Fire Prevention Bureau. 1 UKVVILA FIRE DEPARTMEIY, Pease call: 575-4407 and give this job S-oss and exact address for shut' iown or restoration aourovl N iA W ?o S 8 10' 12' 14' 16' 18' NOTES SYMBOLS ® SYSTEMS RISER o RISE UP • DROP DN L--7 2 WAY EARTHQUAKE BRACE 4 WAY EARTHQUAKE BRACE GROOVED COUPLING \#01 HANGER TYPE AND LOCATION' Al > WELD TAG NUMBER 0 UPRIGHT HEAD ® PENDENT HEAD D SIDE WALL HEAD REVISIONS LEGEND pA UPRIGHT OVER PENDENT 25 PIPE SIZING 1 HYDRAULIC CALC NODE REVISION NUMBER 1❑ BRANCH LINE NUMBER DATE DESCRIPTION 2/28/2011 REVISED ATTIC AREA TO STANDARD UPRIGHTS BY ("' SPRINKLER SYMBOLS SYM •CNT • M NAME METAL TEMP K NPT ORIF MFG. MODEL# CONN. Q® 10 DRY PEND CHROME 160 5.6 1/2" 1/2 RELIABLE F3QR Defaul 0 10 UPRIGHT BRASS 200' 5.6 1/2" 1/2 RELIABLE F1FR Defaul 20 TOTAL HEADS ON PROJECT ORCO Fire Protection, Inc. PO Box 363 Ravensdale, WA 98051 425-432-7250 OWNER INFORMATION NAME CHURCH SIDE OF THE RD ADDRESS 4314 SOUTH 131ST PL TUKWILLA, WA PHONE 208-227-1472 FIRE DEPT INFORMATION NAME TUKWILA FIRE DEPT ADDRESS444 ANDOVER PAARK EAST TUKWILA, WA 98188 PHONE (208) 575.4404 WATER DEPT. INFORMATION NAME ADDRESS PHONE WATER INFORMATON STATIC 90 RESIDUAL 20 GPM 4850 BACKFLOW 8" SOURCE AS BUILT DRAWING TUKWILLA WATER DEPT BUILDING INFORMATION SQ. FT. 838 SOFT. TYPE Wood FTmIn3 OCCUPANCY .L1GNTI' HAZARD otz u LEGAL DESCRIPTION TAX PARCEL # -FE a4 s � � ,U 8 SeaTac A ,erton Heigfif 1\uT S 15Dt u— 1 « 3955 5198th 5t, Seattle, WA.. 3455 5 148th St Seattle, WA 98168 99) 48th -St C(na.4 'n38-2Y5I' ro.o CC7JId:1Yl a'40!!BC eR All 15=1 th 5rT fl VICINITY MAP NO SCALE N A r E CHURCH BY THE SIDE OF THE ROAD 3455 S 145TH ST TUKWILA, WASHINGTON CONTRACTOINORCO FIRE PROTETION, INC. PORTE COCHERE PIPING PLAN PERMIT NO. CONTRACT NO. N10069 APPROVAL TUKWILA FD DRAWN BY ED COGAR SCALE 1/8" = 1'-0" DATE 2/16/2011 REVISED PLOTTED FP1of1 �� N/ s��5/