Loading...
HomeMy WebLinkAboutPP - 2866 SOUTHCENTER MALL - PAYLESS SHOE SOURCE - PERMITS AND PLANS2866 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-248 08-S-273 08-S-265 i1 • FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Payless Shoes 2866 Southcenter Mall Permit No.: 08-S-265 Date: June 4, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. • COSCO FIRE PROTECTION, INC. 10910 - 117TH PLACE, N.E. KIRKLAND,WA 98033-5027 HYDRAULIC CALCULATIONS FOR PAYLESS SHOES 2866 SOUTHCENTER MALL TUKWILLA, WA 98188A FILE NUMBER:25KS-7944 DATE: 05/30/08 -DESIGN DATA - OCCUPANCY CLASSIFICATION: ORDINARY HAZARD GROUP -2 DENSITY: 0.20 gpm/sq. ft. AREA OF APPLICATION: 1595 sq. ft. COVERAGE PER SPRINKLER: 120 sq. ft. NUMBER OF SPRINKLERS CALCULATED: 17 sprinklers TOTAL SPRINKLER WATER FLOW REQUIRED: 570.7 gpm TOTAL WATER REQUIRED (including hose): 900.8 gpm FLOW AND PRESSURE (@ BOR): 650.7 gpm @ 97.2 psi SPRINKLER ORIFICE SIZE: 1/2 inch NAME OF CONTRACTOR: COSCO FIRE PROTECTION DESIGN/LAYOUT BY: BRIAN SCHULZE AUTHORITY HAVING JURISDICTION: TUKWILLA FIRE CONTRACTOR CERTIFICATION NUMBER: COSCOFP110NM CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 4903012830) HRS SYSTEMS, INC. TUCKER, GA 30084 TUCKER, GA 30084 DATE: 5/30/2008 JOB TITLE: PAYLESS SHOES SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 C:\HASS78\HASSDATA\PAYLESS SHOES.SDF WATER SUPPLY DATA SOURCE NODE TAG SOURCE STATIC PRESS. (PSI) 140.0 RESID. PRESS. (PSI) 20.0 AGGREGATE FLOW ANALYSIS: FLOW (GPM) 10900.0 TOTAL FLOW AT SOURCE TOTAL HOSE STREAM ALLOWANCE AT SOURCE OTHER HOSE STREAM ALLOWANCES TOTAL DISCHARGE FROM ACTIVE SPRINKLERS NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE (FT) 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 AVAIL. PRESS. (PSI) 138.8 TOTAL @ DEMAND (GPM) 900.8 GPM 250.0 GPM 80.0 GPM 570.8 GPM PRESSURE (PSI) 21.7 21.7 21.6 22.3 22.4 32.5 32.4 47.6 50.1 40.5 40.8 44.4 50.6 42.2 41.0 44.4 49.4 25.0 25.4 25.1 25.5 25.6 27.1 25.3 27.5 32.2 34.6 35.6 37.8 35.5 38.5 53.2 57.6 57.5 REQ'D PRESS. (PSI) 900.8 104.8 DISCHARGE (GPM) 26.1 26.1 26.0 26.5 26.5 31.9 31.9 38.6 39.7 35.7 35.8 37.3 39.8 36.4 35.9 37.3 39.4 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 5/30/2008 C:\HASS78\HASSDATA\PAYLESS SHOES.SDF JOB TITLE: PAYLESS SHOES NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) 17A 31.5 18 28.0 19 28.0 20 28.0 21 28.0 22 28.0 23 31.5 24 31.5 25 31.5 26 28.0 27 28.0 28 31.5 29 31.5 30 28.0 31 28.0 32 28.0 33 31.5 34 31.5 35 31.5 36 28.0 37 31.5 38 31.5 39 31.5 40 31.5 41 31.5 42 31.5 43 33.5 44 33.5 45 33.5 46 14.0 TOR 14.0 BOR 2.0 M10 2.0 BFO 4.0 BFI 4.0 UG1 1.2 SOURCE -4.0 HOSE STREAM SOURCE 57.6 48.8 48.7 48.7 49.1 50.6 50.3 51.8 58.0 46.4 46.8 49.4 56.6 48.4 49.3 51.0 50.8 51.8 58.5 47.0 49.4 55.3 58.2 58.5 59.0 78.1 78.6 78.8 80.3 89.2 90.8 97.2 97.3 96.6 101.1 102.3 104.8 80.0 650.8 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 'DATE: 5/30/2008 C:\HASS78\HASSDATA\PAYLESS SHOES.SDF JOB TITLE: PAYLESS SHOES PIPE DATA PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 1 -26.1 1.049 PL 20.00 PF 4.7 101 25.0 5.6 21.7 26.1 9.7 120 FTG E PE -1.3 1 28.0 0.0 25.0 0.0 0.212 TL 22.00 PV Pipe: 2 -26.1 1.049 PL 20.00 PF 4.7 102 25.0 5.6 21.7 26.1 9.7 120 FTG E PE -1.3 3 28.0 0.0 25.1 0.0 0.213 TL 22.00 PV Pipe: 3 -26.1 1.610 PL 4.00 PF 0.3 1 28.0 0.0 25.0 0.0 4.1 120 FTG T PE 0.0 2 28.0 0.0 25.4 0.0 0.026 TL 12.00 PV Pipe: 4 -26.1 1.610 PL 3.00 PF 0.3 3 28.0 0.0 25.1 0.0 4.1 120 FTG T PE 0.0 2 28.0 0.0 25.4 0.0 0.026 TL 11.00 PV Pipe: 5 -52.1 1.610 PL 2.00 PF 0.2 2 28.0 0.0 25.4 0.0 8.2 120 FTG ---- PE 0.0 4 28.0 0.0 25.5 0.0 0.095 TL 2.00 PV Pipe: 6 -26.0 1.049 PL 18.00 PF 5.3 103 25.0 5.6 21.6 26.0 9.7 120 FTG ET PE -1.3 4 28.0 0.0 25.5 0.0 0.211 TL 25.00 PV Pipe: 7 -78.1 1.610 PL 8.00 PF 1.6 4 28.0 0.0 25.5 0.0 12.3 120 FTG ---- PE 0.0 6 28.0 0.0 27.1 0.0 0.201 TL 8.00 PV Pipe: 8 -26.5 1.049 PL 19.00 PF 4.6 104 25.0 5.6 22.3 26.5 9.8 120 FTG E PE -1.3 5 28.0 0.0 25.6 0.0 0.218 TL 21.00 PV Pipe: 8A -26.5 1.049 PL 2.00 PF 1.5 5 28.0 0.0 25.6 0.0 9.8 120 FTG T PE 0.0 6 28.0 0.0 27.1 0.0 0.218 TL 7.00 PV Pipe: 9 -104.6 1.610 PL 1.00 PF 0.3 6 28.0 0.0 27.1 0.0 16.5 120 FTG ---- PE 0.0 8 28.0 0.0 27.5 0.0 0.345 TL 1.00 PV Pipe: 10 -26.5 1.049 PL 17.00 PF 4.2 105 25.0 5.6 22.4 26.5 9.8 120 FTG E PE -1.3 7 28.0 0.0 25.3 0.0 0.219 TL 19.00 PV Pipe: 11 -26.5 1.049 PL 5.00 PF 2.2 7 28.0 0.0 25.3 0.0 9.8 120 FTG T PE 0.0 8 28.0 0.0 27.5 0.0 0.219 TL 10.00 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: 5/30/2008 C:\HASS78\HASSDATA\PAYLESS SHOES.SDF JOB TITLE: PAYLESS SHOES PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 12 -131.1 1.610 PL 5.00 PF 4.7 8 28.0 0.0 27.5 0.0 20.7 120 FTG E PE 0.0 9 28.0 0.0 32.2 0.0 0.524 TL 9.00 PV Pipe: 13 -131.1 1.610 PL 3.50 PF 3.9 9 28.0 0.0 32.2 0.0 20.7 120 FTG E PE -1.5 10 31.5 0.0 34.6 0.0 0.524 TL 7.50 PV Pipe: 14 -131.1 1.610 PL 6.00 PF 3.1 10 31.5 0.0 34.6 0.0 20.7 120 FTG ---- PE 0.0 12 31.5 0.0 37.8 0.0 0.524 TL 6.00 PV Pipe: 15 -31.9 1.049 PL 17.00 PF 5.9 106 25.0 5.6 32.5 31.9 11.9 120 FTG E PE -2.8 11 31.5 0.0 35.6 0.0 0.309 TL 19.00 PV Pipe: 16 -31.9 1.049 PL 2.00 PF 2.2 11 31.5 0.0 35.6 0.0 11.9 120 FTG T PE 0.0 12 31.5 0.0 37.8 0.0 0.309 TL 7.00 PV Pipe: 17 -163.1 1.610 PL 1.00 PF 0.8 12 31.5 0.0 37.8 0.0 25.7 120 FTG ---- PE 0.0 14 31.5 0.0 38.5 0.0 0.784 TL 1.00 PV Pipe: 18 -31.9 1.049 PL 17.00 PF 5.9 107 25.0 5.6 32.4 31.9 11.8 120 FTG E PE -2.8 13 31.5 0.0 35.5 0.0 0.308 TL 19.00 PV Pipe: 19 -31.9 1.049 PL 5.00 PF 3.1 13 31.5 0.0 35.5 0.0 11.8 120 FTG T PE 0.0 14 31.5 0.0 38.5 0.0 0.308 TL 10.00 PV Pipe: 20 -195.0 1.610 PL 10.00 PF 19.6 14 31.5 0.0 38.5 0.0 30.7 120 FTG T PE 0.0 39 31.5 H.S. 58.2 80.0 1.091 TL 18.00 PV Pipe: 21 -38.6 1.049 PL 17.00 PF 8.4 108 25.0 5.6 47.6 38.6 14.3 120 FTG E PE -2.8 15 31.5 0.0 53.2 0.0 0.440 TL 19.00 PV Pipe: 22 -38.6 1.049 PL 5.00 PF '4.4 15 31.5 0.0 53.2 0.0 14.3 120 FTG T PE 0.0 16 31.5 0.0 57.6 0.0 0.440 TL 10.00 PV Pipe: 23 -38.6 1.610 PL 1.00 PF 0.1 16 31.5 0.0 57.6 0.0 6.1 120 FTG ---- PE 0.0 17A 31.5 0.0 57.6 0.0 0.055 TL 1.00 PV Pipe: 24 -40.8 1.610 PL 1.00 PF 0.5 17A 31.5 0.0 57.6 0.0 6.4 120 FTG T PE 0.0 39 31.5 H.S. 58.2 80.0 0.060 TL 9.00 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 DATE: 5/30/2008 C:\HASS78\HASSDATA\PAYLESS SHOES.SDF JOB TITLE: PAYLESS SHOES PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 25 -43.0 1.049 PL 17.00 PF 10.2 109 25.0 5.6 50.1 39.7 15.9 120 FTG E PE -2.8 17 31.5 0.0 57.5 0.0 0.535 TL 19:00 PV Pipe: 26 -43.0 1.610 PL 2.00 PF 0.1 17 31.5 0.0 57.5 0.0 6.8 120 FTG ---- PE 0.0 17A 31.5 0.0 57.6 0.0 0.066 TL 2.00 PV Pipe: 27 -40.8 1.610 PL 1.00 PF 0.5 17A 31.5 0.0 57.6 0.0 6.4 120 FTG T PE 0.0 39 31.5 H.S. 58.2 80.0 0.060 TL 9.00 PV Pipe: 28 3.3 1.049 PL 17.00 PF 0.1 109 25.0 5.6 50.1 39.7 1.2 120 FTG E PE -1.3 18 28.0 0.0 48.8 0.0 0.005 TL 19.00 PV Pipe: 29 3.3 1.049 PL 4.00 PF 0.0 18 28.0 0.0 48.8 0.0 1.2 120 FTG T PE 0.0 19 28.0 0.0 48.7 0.0 0.005 TL 9.00 PV Pipe: 30 3.3 1.610 PL 3.00 PF 0.0 19 28.0 0.0 48.7 0.0 0.5 120 FTG ---- PE 0.0 20 28.0 0.0 48.7 0.0 0.001 TL 3.00 PV Pipe: 31 -35.7 1.049 PL 17.00 PF 7.2 110 25.0 5.6 40.5 35.7 13.2 120 FTG E PE -1.3 26 28.0 0.0 46.4 0.0 0.379 TL 19.00 PV Pipe: 32 -35.7 1.049 PL 1.00 PF 2.3 26 28.0 0.0 46.4 0.0 13.2 120 FTG T PE 0.0 20 28.0 0.0 48.7 0.0 0.379 TL 6.00 PV Pipe: 33 -32.3 1.610 PL 9.00 PF 0.4 20 28.0 0.0 48.7 0.0 5.1 120 FTG ---- PE 0.0 21 28.0 0.0 49.1 0.0 0.039 TL 9.00 PV Pipe: 34 -35.8 1.049 PL 17.00 PF 7.3 111 25.0 5.6 40.8 35.8 13.3 120 FTG E PE -1.3 27 28.0 0.0 46.8 0.0 0.382 TL 19.00 PV Pipe: 35 -35.8 1.049 PL 1.00 PF 2.3 27 28.0 0.0 46.8 0.0 13.3 120 FTG T PE 0.0 21 28.0 0.0 49.1 0.0 0.382 TL 6.00 PV Pipe: 36 -68.1 1.610 PL 6.00 PF 1.6 21 28.0 0.0 49.1 0.0 10.7 120 FTG E PE 0.0 22 28.0 0.0 50.6 0.0 0.156 TL 10.00 PV Pipe: 37 -68.1 1.610 PL 3.50 PF 1.2 22 28.0 0.0 50.6 0.0 10.7 120 FTG E PE -1.5 23 31.5 0.0 50.3 0.0 0.156 TL 7.50 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7 DATE: 5/30/2008 C:\HASS78\HASSDATA\PAYLESS SHOES.SDF JOB TITLE: PAYLESS SHOES PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 38 -68.1 1.610 PL 6.00 PF 1.6 23 31.5 0.0 50.3 0.0 10.7 120 FTG E PE 0.0 24 31.5 0.0 51.8 0.0 0.156 TL 10.00 PV Pipe: 39 -37.3 1.049 PL 17.00 PF 7.8 112 25.0 5.6 44.4 37.3 13.8 120 FTG E PE -2.8 28 31.5 0.0 49.4 0.0 0.412 TL 19.00 PV Pipe: 40 -37.3 1.049 PL 1.00 PF 2.5 28 31.5 0.0 49.4 0.0 13.8 120 FTG T PE 0.0 24 31.5 0.0 51.8 0.0 0.412 TL 6.00 PV Pipe: 41 -105.4 1.610 PL 11.00 PF 6.6 24 31.5 0.0 51.8 0.0 16.6 120 FTG T PE 0.0 40 31.5 0.0 58.5 0.0 0.350 TL 19.00 PV Pipe: 42 -39.8 1.049 PL 17.00 PF 8.8 113 25.0 5.6 50.6 39.8 14.8 120 FTG E PE -2.8 29 31.5 0.0 56.6 0.0 0.465 TL 19.00 PV Pipe: 43 -39.8 1.049 PL 1.00 PF 1.4 29 31.5 0.0 56.6 0.0 14.8 120 FTG E PE 0.0 25 31.5 0.0 58.0 0.0 0.465 TL 3.00 PV Pipe: 44 -39.8 1.610 PL 1.00 PF 0.5 25 31.5 0.0 58.0 0.0 6.3 120 FTG T PE 0.0 40 31.5 0.0 58.5 0.0 0.058 TL 9.00 PV Pipe: 45 -36.4 1.049 PL 17.00 PF 7.5 114 25.0 5.6 42.2 36.4 13.5 120 FTG E PE -1.3 30 28.0 0.0 48.4 0.0 0.394 TL 19.00 PV Pipe: 46 -36.4 1.610 PL 14.00 PF 0.9 30 28.0 0.0 48.4 0.0 5.7 120 FTG E PE 0.0 31 28.0 0.0 49.3 0.0 0.049 TL 18.00 PV Pipe: 47 -35.9 1.049 PL 17.00 PF 7.3 115 25.0 5.6 41.0 35.9 13.3 120 FTG E PE -1.3 36 28.0 0.0 47.0 0.0 0.383 TL 19.00 PV Pipe: 48 -35.9 1.049 PL 1.00 PF 2.3 36 28.0 0.0 47.0 0.0 13.3 120 FTG T PE 0.0 31 28.0 0.0 49.3 0.0 0.383 TL 6.00 PV Pipe: 49 -72.2 1.610 PL 6.00 PF 1.7 31 28.0 0.0 49.3 0.0 11.4 120 FTG E PE 0.0 32 28.0 0.0 51.0 0.0 0.174 TL 10.00 PV Pipe: 50 -72.2 1.610 PL 3.50 PF 1.3 32 28.0 0.0 51.0 0.0 11.4 120 FTG E PE -1.5 33 31.5 0.0 50.8 0.0 0.174 TL 7.50 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 8 DATE: 5/30/2008 C:\HASS78\HASSDATA\PAYLESS SHOES.SDF JOB TITLE: PAYLESS SHOES PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 51 -72.2 1.610 PL 6.00 PF 1.0 33 31.5 0.0 50.8 0.0 11.4 120 FTG ---- PE 0.0 34 31.5 0.0 51.8 0.0 0.174 TL 6.00 PV Pipe: 52 -37.3 1.049 PL 17.00 PF 7.8 116 25.0 5.6 44.4 37.3 13.8 120 FTG E PE -2.8 37 31.5 0.0 49.4 0.0 0.412 TL 19.00 PV Pipe: 53 -37.3 1.049 PL 1.00 PF 2.5 37 31.5 0.0 49.4 0.0 13.8 120 FTG T PE 0.0 34 31.5 0.0 51.8 0.0 0.412 TL 6.00 PV Pipe: 54 -109.5 1.610 PL 11.00 PF 7.1 34 31.5 0.0 51.8 0.0 17.3 120 FTG T PE 0.0 41 31.5 0.0 59.0 0.0 0.375 TL 19.00 PV Pipe: 55 -39.4 1.049 PL 17.00 PF 8.7 117 25.0 5.6 49.4 39.4 14.6 120 FTG E PE -2.8 38 31.5 0.0 55.3 0.0 0.456 TL 19.00 PV Pipe: 56 -39.4 1.049 PL 2.00 PF 3.2 38 31.5 0.0 55.3 0.0 14.6 120 FTG T PE 0.0 35 31.5 0.0 58.5 0.0 0.456 TL 7.00 PV Pipe: 57 -39.4 1.610 PL 1.00 PF 0.5 35 31.5 0.0 58.5 0.0 6.2 120 FTG T PE 0.0 41 31.5 0.0 59.0 0.0 0.057 TL 9.00 PV Pipe: 58 -356.6 4.260 PL 10.50 PF 0.3 39 31.5 H.S. 58.2 80.0 8.0 120 FTG ---- PE 0.0 40 31.5 0.0 58.5 0.0 0.029 TL 10.50 PV Pipe: 59 -501.8 4.260 PL 9.00 PF 0.5 40 31.5 0.0 58.5 0.0 11.3 120 FTG ---- PE 0.0 41 31.5 0.0 59.0 0.0 0.055 TL 9.00 PV Pipe: 60 -650.7 4.260 PL 163.00 PF 19.2 41 31.5 0.0 59.0 0.0 14.6 120 FTG 4E PE 0.0 42 31.5 0.0 78.1 0.0 0.089 TL 215.80 PV Pipe: 61 -650.7 4.260 PL 2.00 PF 1.3 42 31.5 0.0 78.1 0.0 14.6 120 FTG E PE -0.9 43 33.5 0.0 78.6 0.0 0.089 TL 15.20 PV Pipe: 62 -650.7 4.260 PL 2.00 PF 0.2 43 33.5 0.0 78.6 0.0 14.6 120 FTG ---- PE 0.0 44 33.5 0.0 78.8 0.0 0.089 TL 2.00 PV Pipe: 63 -650.7 6.357 PL 45.00 PF 1.5 44 33.5 0.0 78.8 0.0 6.6 120 FTG 2ET PE 0.0 45 33.5 0.0 80.3 0.0 0.013 TL 117.90 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 9 DATE: 5/30/2008 C:\HASS78\HASSDATA\PAYLESS SHOES.SDF JOB TITLE: PAYLESS SHOES PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 64 -650.7 6.357 PL 19.50 PF 0.5 45 33.5 0.0 80.3 0.0 6.6 120 FTG E PE 8.4 46 14.0 0.0 89.2 0.0 0.013 TL 37.10 PV Pipe: 65 -650.7 6.357 PL 60.00 PF 1.6 46 14.0 0.0 89.2 0.0 6.6 120 FTG 4E PE 0.0 TOR 14.0 0.0 90.8 0.0 0.013 TL 130.40 PV Pipe: 66 -650.7 6.357 PL 12.00 PF 1.1 TOR 14.0 0.0 90.8 0.0 6.6 120 FTG TC PE 5.2 BOR 2.0 0.0 97.2 0.0 0.013 TL 89.90 PV Pipe: 67 -650.7 8.249 PL 3.58 PF 0.1 BOR 2.0 0.0 97.2 0.0 3.9 120 FTG E PE 0.0 M10 2.0 0.0 97.3 0.0 0.004 TL 23.58 PV Pipe: 68 -650.7 10.374 PL 31.42 PF 0.2 M10 2.0 0.0 97.3 0.0 2.5 120 FTG 4EB PE -0.9 BFO 4.0 0.0 96.6 0.0 0.001 TL 151.12 PV Pipe: 69 FIXED PRESSURE LOSS DEVICE BFI 4.0 0.0 101.1 0.0 4.5 psi, 650.7 gpm BFO 4.0 0.0 96.6 0.0 Pipe: 70 -650.7 10.374 PL 2.83 PF 0.0 BFI 4.0 0.0 101.1 0.0 2.5 120 FTG B PE 1.2 UG1 1.2 0.0 102.3 0.0 0.001 TL 24.13 PV Pipe: 71 -650.8 10.275 PL 85.00 PF 0.2 UG1 1.2 0.0 102.3 0.0 2.5 140 FTG 2ETG PE 2.2 SOURCE -4.0 SRCE 104.8 (N/A) 0.001 TL 225.80 PV NOTES (HASS): (1) Calculations were performed by the HASS 7.9 computer program under license no. 4903012830 granted by HRS Systems, Inc. 4792 LaVista Road Tucker, GA 30084 (2) The system has been calculated to provide an average imbalance at each node of 0.002 gpm and a maximum imbalance at any node of 0.166 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 30.7 ft/sec at pipe 20. SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 10 DATE: 5/30/2008 C:\HASS78\HASSDATA\PAYLESS SHOES.SDF JOB TITLE: PAYLESS SHOES (4) PIPE FITTINGS TABLE Pipe Table Name: MOST.PIP PAGE: A MATERIAL: SCH.40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D F Ell Tee LngEll ChkV1v BfyVly GatV1v AlmChk DPV1v 45E11 H Q I S U V W 22/Ell 11gE11 Couplg FM90E1 FM45E1 FMTee FMRunT 1.049 2.00 5.00 2.00 5.00 6.00 1.00 17.00 23.00 1.00 0.50 0.30 1.00 6.00 5.00 9.00 0.00 1.610 4.00 8.00 2.00 9.00 6.00 1.00 17.00 23.00 2.00 1.00 0.50 1.00 8.00 6.00 12.00 0.00 PAGE: B MATERIAL: SCH.10 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D F Ell Tee LngEll ChkVly BfyVly GatVly AlmChk DPV1v 45E11 4.260 6.357 8.249 10.374 H Q I S U V W 22/Ell 11gE11 Couplg FM90E1 FM45E1 FMTee FMRunT 13.20 26.30 7.90 29.00 15.80 2.60 36.90 39.50 6.60 3.30 1.60 1.30 18.40 11.90 31.60 0.00 17.60 37.70 11.30 40.20 12.60 3.80 37.70 41.50 8.80 4.40 2.20 1.30 22.60 13.80 42.70 0.00 20.00 38.90 14.50 50.00 13.30 4.40 45.60 41.50 10.00 5.00 2.50 1.10 24.50 14.50 43.40 0.00 24.60 56.00 17.90 61.60 21.30 5.60 45.60 41.50 12.30 6.20 3.10 1.10 29.10 16.80 56.00 0.00 PAGE: D MATERIAL: DI -52 HWC: 140 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D F Ell Tee LngEll ChkV1v BfyVly GatV1v AlmChk DPV1v 45E11 10.275 H Q 22/Ell 11gEll 31.30 71.10 22.70 78.20 27.00 7.10 61.20 47.20 15.60 7.80 3.90 NOTES (USER): • SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 11 DATE: 5/30/2008 JOB TITLE: PAYLESS SHOES WATER SUPPLY ANALYSIS Flow: 10900.0 gpm 0 0 0 140.00 psi Resid: C:\HASS78\HASSDATA\PAYLESS SHOES.SDF E E v v a a rn rn�+ a) co wUU •v 0 0 Sa 0 x,21 N O O r-1 0 A v u) a E z ° ° Q 0 ••( a .c 11) � °4..' m •- S 0 >, • 0 • m CO CO tr' w rn a) O • ai Ava rl N 0 0 0 N O 0 0 0 0 l0 N 0 H H H H O 0 CO 0 0 C7K4 (DW arx 1cncnrxw --aEn 0 O dr GO 0 0 0 0 0 rn rn c0 O 0 O 0 N N O w SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 12 DATE: 5/30/2008 C:\HASS78\HASSDATA\PAYLESS SHOES.SDF JOB TITLE: PAYLESS SHOES WATER SUPPLY CURVE 132+ \ \ I \ I P 96+ R I E I S S 84+ U 1 R E I 72+ \ ( I \ P I \ S I \ I 60+ \ I \ I \ I \ 48+ \ I \ I \ I \ 36+ \ I \ I \ I \ 24+ LEGEND \ \ \ \ \ \ \ X = Required Water Supply 104.77 psi @ 900.8 gpm 0 = Available Water Supply 138.81 psi @ 900.8 gpm "* <-20.0 psi @ 10900 gpm " Flow Test Point II II II 11 0++-+---+----+ + + + + + + 32004800 6400 8000 9600 11200 12800 14400 16000 FLOW (GPM) FILE CO"Y SHEET INDEX. A„..,: ALAI 'III; YTEM TUKWIL'''F;i f HINOTON NERAL NOTES S =ET \UVI3ESHEET TITLE FA -01 SYSTEV INFOVATIO\ FA --02 TYPICAL DETAILS - WRI\ G A\3 MOUNTI\G FA --03 FRE ALARM SYSTEM FLOO PLA FA -04 YSTEv1 CALCULATIO\S (CE\EAL), �ISE�, SITE PLA\ tEr ❑ Without Comments As Noted In Red Per The Attached Letter I nese pans hove ficarf reviewed 17y The Tukwila iia Fire Prevention i_.}Urea'? for co:'.+..+r r'iu+i';C ;ith current city standards. Ac, .c ;t._. i;;,•:' _ :: ':errors and ornissions ,,,; :-,-.:tr .... r .,t 7_..--''.1i<.tir. n:, Pi adopted I standeras .,1 rc: , . . , • r=: U,--;s6i;,t,,rfior the i cie(quc.'cv ::t •.. ...,i'; ,,; i.;.:.:: {: : i ner. ; dc,fIt:-)rs .. .r � ;; i:iifa +!jf;a ,atter ifliS d`I:,-: . '‘,1,--4 ...r'- ... Ind..iiil requite a resubmittal ct ,.a+ut aegt!ent approval. Final acc:pt;y;!.(.1.... -i tittwv;t!a;r,`d inspection by IThe.Tuk\ivila Fixe Date: 5- 3°-(42, By: TUKWILA FIRE DEPARTMEN1.. Pease call: 575-440Z and give this job t 1o._Q - '))`\ and �.._c: addre3s for shut. approval. NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and c; min tion of the testing. WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATION SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD 4#16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWD *14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO 1#16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD 1#12 FPL/FPLR RED (JACKET) 2S STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) 2V SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWD #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED 4#18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) 'B BEAM DETECTOR POWER TWD #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART :irr 11 I. :: ! ;'i. :�-»+i;,i.,.;• it t�l ' NO. . ! CONDUIT -1 ' i i 1 i'.' : li I I, i!! OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ' ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO . BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END 4.t 1 ;j;i FOR SIEMENS SYSTEM': L!1 ' DO NOT INSTALL ADDRESSABLE DEVICES ADDRESS. !' INITIATING DEVICES UNTIL. PREPROGRAMMED WITH 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE',;; THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIfOUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING I ,SUPERVISED. NO PARALLEL BRANCHING IS PERVIISSIBLE 4. INSTALLATION SHALL BE IN`I-_STRIC1T ;CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NEPA 72, LOCAL ;CbDE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (kE I. CONQUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER Of TICSi'.EABLE, FITTINGS, AND ASSOCIATED EQUIPvIENT) ARE NOT SUPPLIED BY SIEMENS ;CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE0UNTED IN DIRECT AIR STREAM OF AIR SUPPLY' .OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN :WITH : ESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOI:CODEIi:CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED F031( FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SH LL;;RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" I URP'OSES. • t I' 9. FOR ADDITIONAL INSTALLATION: 'If STRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLAT10S, RUCTIONS. 10. THE 120vac POWER ELECTRRK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICL° j72 !A{ ND 760 OF NEPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5 ..5.2 .' 1'N REFERENCE TO DEDICATED . BRANCH POWER SOURCES. 120vac POWER S ;ALL';N!OT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRL: AL , M TECHNICIAN. 11. ALL HORN STROBE AND STI.QB ;'EVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOWLDROP ,ED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATION' SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. I' 13. ALL PANEL NUMBERS AND ,CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE 'ROM 'DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. :I 15. PER NFPA 72 SECTION 5-3;.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN- UP 0F! ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY; THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED. OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED,' :VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. Ii1 18. ALL CABLES SHALL BE MARKED AS. INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALLIDEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR .SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RAID) !FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS 'SHALL BE LOCATED IN CONDUIT. •1 22. NEPA 72 2007 6.4.2.2.2 ALk' 1 STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G;„ METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE SUTG0I.NG AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE, ,C,ONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT B!fU�N' ISN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), E{N I'DSURE, OR RACEWAY. illy NFPA 72 2007 A.6.4.2.2.2 : A GOAL' OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETYVEEN.; J 1E OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUI,.ED..T0j MELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DA ElHE RECOMMENDED MINIMUM SEPARATION TO PREVENT PVYSICAL, DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VO,TICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED 23. IH: QUANTITY 3 2 2 2 2 EX OL DESCRIPTION EX EX IRE ALARM ONTROL PANEL IRE ALARM ;EMOTE ANNUNCIATOR DEMOTE BOOSTER DOWER SUPPLY 1TERFACE MODULE ITH RELAY UAL INPUT 1TERFACE MODULE 'ONTROL POINT ODULE SYMBOLS LEGEND MODEL XLS-V SDD-C PAD -3 HTRI-R HTRI-D HCP EMOTE CONVENTIONAL HZM ,ONE MODULE INEAR BEAM MOKE DETECTOR MANUFACTURER BACKBOX SIEMENS SIEMENS SIEMENS SIEMENS SIEMENS SIEMENS SIEMENS PBA -1191 SIEMENS SMOKE DETECTOR HFP-11 W/ SIEMENS ADDRESSABLE -PHOTO) DB -11 BASE 1 1 UCT SMOKE ETECTOR EAT DETECTOR ADDRESSABLE) LIRE ALARM RPEAKER STROBE :CEILING MOUNT) IRE ALARM PEAKER STROBE WALL MOUNT) ;;IRE ALARM SPEAKER STROBE ,WALL MOUNT) FIRE ALARM STROBE ;,CEILING MOUNT) FIRE ALARM STROBE HALL MOUNT) SIRE ALARM SPEAKER ;'CEILING MOUNT) =IRE ALARM SPEAKER WALL MOUNT) AD2-P W/ SIEMENS TSM MODULE HFPT-11 W/ SIEMENS DB -11 BASE SET -MC -CW SIEMENS SET -MC -W SIEMENS SET -HMC -CW SIEMENS ZR -MC -CW SIEMENS ZR -MC -W SIEMENS SET -CW SIEMENS SET -W SIEMENS PROVIDED PROVIDED PROVIDED 4S DEEP 45 DEEP 4S DEEP 4S DEEP PROVIDED 4S DEEP W/ 1G RING DUCT HOUSING 4S DEEP W/ 1G RING MOUNTING HEIGHT 66" A.F.F. TO TOP 66" A.F.F. TO TOP 66" A.F.F. TO TOP VERIFY IN FIELD VERIFY IN FIELD VERIFY IN FIELD VERIFY IN FIELD VERIFY IN FIELD CEILING VERIFY IN FIELD CEILING 4S DEEP BOX CEILING W/ 1-1/2" EXT. 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM 4S DEEP BOX CEILING W/ 1-1/2" EXT. 4S BOX W/ 1G RING 4S BOX IN/ 1G RING CEILING 80" A.F.F. TO BOTTOM U.O.N. 4S DEEP BOX CEILING W/ 1-1/2" EXT. 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM P SIRE ALARM fiTROBE WEATHERPROOF) SET -S17 -WP SIEMENS MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD MRI ULTI-VOLTAGE ONTROL RELAY MR -201 /C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA :WB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD JUNCTI❑N BOX F.B.O. F.B.❑. N/A VERIFY IN FIELD 'B❑VE FINISHED FLOOR FURNISHED BY OTHERS ,Y NOT APPLICABLE UNLESS OTHERWISE NOTED WEATHERPR❑❑F DEVICE AS BUILT FDD OR CHANGE !i{S BUILT REMOVE H. AS BUILT NOTES TO CAD N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A • Copyright 2006 by Guardian Security Systems, Inc. All Rights R,eserv,`d RELEASE/REVISIONS rn :0' .0' co z•c O `o - L7 \O'. C/) Q REV. BY: I z a DESCRIPTION SHOP DRAWINGS DATE 5/15/08 o <1<<<< co co J T- < 0) 2 Z U) FE 2- W 1_1_1 0 Z -I c O (Z < � <C Q � 0 o� LL SCALE: 1 /8"=1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: \:.OB NUMBER:54534 1 FA -01 i'• I:! • 1:!„:': • ' THE DUCT ,SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED1LINSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS,FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. ;; • • • !!! BEND OR OTHER 1 OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS „•• TYPICAL.SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE ; " „I • I! : „., !I! ' COMBINE ALL SHIELDS AND; ISOLATE FROM GROUNDING • ;TO NEXT,,ADDRESSABLE DEVICE' STOP IFLAST DEVICE 14 FROM XLS .CONTROL PANEL OR fl !RREVIOUS-„ADDRESSABLE DEVIC •:: ,„ DUCT DETECTOR LOCATION 0 t 1 ildi•72) END CIF, LINE DEVICE(3.6K 1/4‘./ _L :i • : SUPERVISED SWITCH NOTE: ;I. 1 I 1•LID GROUND.'„ • 10 HTRI—R STATUS LED oo 0 N.O. 0 COM CO 0 N.C. FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. • 1,{' ; ,„;•A„ PliEVIOUS DEVICE itiNEXT DEVICE ,• 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) ADDRESSABLE - t 1.; ADDRESSABLE Li + NOTE 1: VOLTAGE MAX. - CURRENT MAX, - CONT. RES. MAX, - MAX. CABLE LENGTH - C (LINE TO LIND- C (LINE TO SHIELD) - MAX,LINE SIZE - MIN, LINE SIZE - MUSIC 1; • :I I ! !I • •.:. , H, • : ' , , TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR DUTLETHSAMPLING TUBE INLET SAMPLING TUBE , 1 1 , • AT LEAST', SIX DUCT'. WIDTHS FROM BEND.. I , ,!.., SCALE=NONE :}-Ac POWER 'SDURC .H.J • COMBINE ; ALL SHIELDS:I.,ANDi ISOLATE FROM GROUNDING ; „ ; ,.;„ .; 1„.„.• , L4:,•/; ; TO NEXT: ADDRESSABLE DEXICEft!"(1.) STOP IF LAST;DEVICE FROM XLS CONTROL PANEL 1 OR 4(+) PREVIOUS ADDRESSABLE DEVICE (-) RELAY CONTACTS (4.0A @,125VAC) (4.0A @ 30VDC) 27 VDC:! 3.5 mAl DURING POLLING 10 OHMS ; A 200 FT„q8 AWG) 0.02uF ; ! 0,04UF: !' 14 AWG 18 AWG END:i.OF LINE DEVICE (3.61. 1/4W) • ; SSWUIPTECRHV, ISD • GROUND 10 @ HTRI—D C1) STATUS LED CO 0 CO 0 0 NOTE: ' FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL kfRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL Lig3a SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) NOTE 2: ' ALL SUPERVISED 'SWITCHES MUST' BE HELD! CLOSED ; AND/OR OPEN FOR AT LEAST .25 SEC, TO GUARANTEE DETECTION. • • • • GNO!..AC • , • 0 0 0 t 1• 1 _ • • . „ , 0 PAD -3 INPUT TROUBLE.' NAC1 NAC2 • • •:.1+ 1-' 1 2+2- 2 -NC C NO +- + - • .2. 0 ,NAC3NAC4, + - 1112 0 0 G 24K ' 0 TYPICAL WIRINGFOR HCP MODULE (PAD -3 TRIP) LABEL SCALE • • n ; NAC -4 NAC -3 NAC -2 NAC -1 END F „.LINE! `,DEVICE „..• ,.. 3.6K 14'14W) .. l• ,i UPE VISED '‘../I.i. I :1 :. i: • .ri : . . • :, :. FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED 0 REMOTE E DEVICE LOOP A- 0 NOT USED 0 REMOTE DEVICE LOOP FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> 470 OHMS 110/ EOL IC INPU LEQ TEM -1 Ls_ N. EAR GRO .-)r..(+) TO >(-) S c) TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE: NONE FROM REMOTE POWER SUPPLY ('S' CABLE) FROM FACP (VOICE CIRCUIT) ('V' CABLE) C C (-1-) H STROBE SPEAKER (1) STROBE STROBE SPEAKER H SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY, , 80" A.F.F. 4S DEEP BOX • W/ 1-1 /2" • EXTENSION RING (SPEAKER II -OBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALENONE, t XT DEA OR IF LAST DEVICE ;., TO DE. EN TL EXT ICE OR OF LINE EXT CE OR OF LINE NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERTINTEMPERATUE: +320*F C TO 100' F (38' C) HUMDITY: O-93% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR FROM PREVIDUS ADDRESSABLE DEVICE; OR POWER SOURCE: DATA IN DATA IN (+) DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WN DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE • TO NEXT DEVICE - REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL UTBEL SCALE - >( ) DATA OUT (+) DATA OUT CEILING MOUNT S PEAKER/STROBE MOUNTING (HARD LID) HARD LID CEILING HARD LID SPEAKER SUPPORT TILE BRIDGE • • 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTION BOX MOUNTED ON CEILING FLEX • JUNCTION BOX ' MOUNTED AGAINST CEILING SUPPORT 00 0 0 ITD NEXT SMOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE:NONE P ` .,' .,.. 1 i . r. ' ,..4.-. ' ...z- CADDY BAR' -.1„ \ ---- SUSPENDED „.rilill'I„: : ..,1„ ..„1” .„.„.: „. ILLUMINATEDlitICEIL:.., .,„:.i,,11:::.,L :,- :,•,„ . ; ii!„:,.,i,,,,. ...i!i!!„., .;:, .... ••1 '11‘ DC) NOT: I AQRESSABLE DEVICES „NTIL D.REPOQRAMMED W DEVICFS DD S. ri ht 006 Gudrdian:Securit .„:; S stems, Inc. All Rights Rsery *1- • LL 0 0 ( Qin CALE: 1 8 -1' DRAWN I.ANDERSON. • DESIGNED BY:: R.VEZZANI, DATE:5/12/08 BACKROUND PLAN PROVIDED BY: \OB NUMBER:4534 SHEET 4 , jA. t• . to cu • • 43 1 x-1 • c). cv • • , 1- ,, Q .1. -I < 41..) "0 1 • .03 Tr' (r; r) c0 c:t c) cNi c0 ' rq • c). . I 1:1 • (j) LLI i• :!! < ! ; (1) Cn !!! 0 ! t E 1. 4(0 - • ; LLJ i '< ! Z •:2 L.L.1 '0 1 Dte 1 ! .< • ! L1J I ! t !.0 Lf). jl • CL • • • !'! ']!! ! 't ..! 1 t • • • 1:1 •1!! !!: ! I! .1! '11 : 'ffir LU !In mervynirs Li L. 1 (---S .>DS• LOCKER :ROOM CLEC oNIC'S BOUTIQUE PRETZEI:f. TUE 11 I SPORTS S LE • 'PlC) F: K WEIi N lONG coLJN-ry LekAr-z\ir M E CC. _L.1 F- CL ti I 17 PAYLESS WESTFIELD SOUTHCENTER MALL SCALE 113264 2S,2V 2S,2V 2S,2V 2S,2V 2S,2V 2S,2V (1 75 C 75 C 15 30 15 15 EOL -S1 FA -430X 1 FACP EX RISER DIAGRAM D,I 21, rrent Load: Ovice TYpe -11 2- 137- FkIrD :11 Qty - SYSTEM CA FACP ADD ONS Standby: Amps 0.0022 0.0635 0.009600 0.001600 0.005 Total 0.0022 .0.0635 0.0096 Amps 0.0023 0.064 0.021 0.0035 0.128 0.063 ent Load: 6 ice Type TIONS n System Board MC @15CD @30CD @75CD 'SftMC @1 1 0 C D PAYLESS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations Qty Amps 0.03 Standby: Total 0.03 Amps 0.030 0.064 0.098 0.175 0.233 Alarm: Total 0.030 0.064 0.098 0.350 '-"I I 0.0731 Amps HMC-C@115CD S PHMC-C@135CD andby Current Load: 0.0731 Amps For, 24 Hours = 1.754 Amp -hours -HMC-C@185CD Z C @15CD C @30CD 0.318 0.318 0.445 0.064 0.098 0.128 0.0015 ern Current Load: 0.191 Amps For 5 Minutes= 0.016 Amp -hours 0.03 Amps 0.67 Amfis 25% Derating= 2.213 Amp -hours t bdby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours AI i-rn Current Load: 0.67 Amps For 5 Minutes= 0.056 Amp -hours Total System Current Load: 2.213 Amp -hours B ttery Pair to be Used: 12VDC I Amp -hours 7AH 25% Derating= 0.970 Amp -hours PROJECT: Panel: Date: CIRCUIT: Total System Current Load: 0.970 Amp -hours eery Pair to be Used: 12VDC Amp -hours 7AH ALCULATION Notification Appliance WESTFIELD SOUTHCENTER MALL PAYLESS May 22, 2008 S1 Wire Resistance 1.62 RENT TOTAL= 640 .4 !!!-• 1! , 4 QTY 2. 0 0 0 0 Device Type SET -MC @15CD SET -MC @30CD SET -MC @75CD SET -MC @110CD SET-HMC-C@115CD SET-HMC-C@177CD SET -HMC @135CD SET -HMC @185CD Alarm Current Alarm Total 64 98 175 445 318 445 64 98 350 Wire Size VVirO,Lengt Voltage at EOL Circuit Total Total Wire Resistance ( R ) (WL*2 )*(R/ft) Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E ) (E= I * R) EOL Voltage (20.4 - E) 0.86 0.64 0.55 19.85 2 Z-MC@15CD 64 128 Z-MC@30CD 98 SET-MC-CW@110CD 233 DEVICES= 6 TOTAL rnAT:- 640 12 19.850496 6401 Notification Appliance tfrcut Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: PAYLESS Wire Resistance 2.58 Date: May. 22, 2008 R ENT TOTAL 7.2 CIRCUIT: SPEAKER CIRCUIT I I QTY Device Type 4 70.7V 1/8 Alarm Current Alarm Total Wire Size 1.81 0 7.2 Wire Voltage at EOL Circuit Total Total Wire Resistance ( R ( WL * 2 )* (R/ft) 2.92 Total Device Load, Amps (I) 0.01 (Total Cct Load) Voltage Drop ( E) 0.02 (E= I * R) EOL Voltage 20.38 0 DEVICES= 4 TOTAL m A= 7.2 VOLTAGE DRO 20.37900912 (20.4 - E) 7.2 t; Copyright 2006 by Guardian Security Systems, Inc. All Rights Reser 1743- IST AVE. SEATTLE, LO 10 0. (NJ CD LLI 5:- m _ . ..... LLI fY a . , , . .. DESCRIPTION SHOP DRAWINGS - DATE 0 ! : ''',. !;• <, ul ..- •••.., If) : C) ‹<<<< 0 DRAWN BY:" .AN DESIGNED BY: R.VEZZANI DATE: 5/1 2/08 BACKROUND • PLAN PROVIDED BY: FA -04 O 101.00 A MALL EGRESS PASSAGEWAY _COVE 105 I /I C E I L •42.-4. ADJACENT-7EN ADJACENT TENANT d' �,--,(t..31''G AFF 1 21'-5 3/8" =G E I L 12-D/ a" -P, FILE COPY THICKNESS of CONCRETE vaRiea • A y .. S/YX2•Y4'KIIK139.t • • ' j pA � A 3/V ROD CPKs CUT NS' ATR (PER FLAW Fla HANGER TOIL 110 1/2.At6,- Il2Xl O FORT' TO4'PIPE ALL LOCATIONS (UN,O) 3As' x 2-S/4' I1111 OLE ECU 3M' ATR x(OEE PU1U 31B'.RCD CPU PIPE HANGER Rt1G I. A L secoweviip EY PM #13 HANGER DETAIL FIG. 65 BEAM CLAMP milli �s11Efi�tiil�lL•1J FIG. 69 — RETAINING / STRAP JA LOCK < NUT IREQ' VIEW A -A �-- PIG. 100 ALL THREAD RDD �-- FIG. 200 L4AA14 ERA15LE RING FF10E 102 tV2ALi 112)(Zl-0 BOTTOM BEAM CLAMP, ROD, AND RING CE I L L2 D \ ( 1 �EIL.iI/-L I TOLCO FIG. 25 SURGE RESTRAINER TYPE 1 — FOR 1" AND 1-1/4" PIPE AND HANGER TYPE 2 — FOR 1-1/2" AND 2" PIPE AND HANGER TOLCO FIG. 25 IS DESIGNED TO BE USED ONLY WITH TOLCO BAND HANGERS FIG. 200 AND 2NFPA TO RESTRAIN THE UPWARD. MOVEMENT OF PIPE AS IT OCCURS DURING SPRINKLER HEAD ACTIVATION 'OR SEISMIC ACTIVITY FIGURE 25 SURGE RESTRAINER FOR STEEL OR CPVC. PLASTIC PIPE LINEMIE L ?4 THH E3(c EEDS 2'-4" Anrcr.0 CMSET E000KET IDRXT. ALL TI AD .ROD 1 1•10.5 REMOTE. A SPACE #2866 EA 15-95 SCS. .FT A System -- N.T.S. 3/3" XWIK BOLT Part COWt to It 2'-4" MAX. PER DINGLE OT144' M13E A.,OEML.T. ParAID BOTH SIDES I4 it MlioG (UP TO 2" PIE) LINE RESTRAINT DETAIL 5F4Ci WITH IN 6" OF A HNG R'EVY43'ON4LINE.. I 0" Victaulic #750 /Butterfly Valve n WILKINS I 0" 350 DAG n Vertical Backflow Preventer \I 0" Victaulic #750 Butterfly Valve I 0" Flange G1 @ 4. I '-2" AFF \FF@O'-0" 10" D.I. T8 Riser Assembly Detail t ADJACENT TENANT j---131 -6) A,F F CEI L. I I ORA.1-:F 3-0 CELL IZ C AFF 3-3 13-0 5-3 &14 -DAF GENER NOTES* RiCraCE Weld stamps must be aspected before pie is hung. ag not paint piping . prior to hydrostatic test approval. Wthout Commertte As Noted in Red. Per The Attached Letter 1 nese plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted stanaard s and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings after this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: `� ..„(11)By; / V w`" -- TAIL 1UKWILA FIRE DEPARTMENT Please call: 575-4407 and give this job No. and exact address for shut" ,.own or restoration approval, 1. RETAIL AREAS ARE DESIGNED IN ACCORDANCE WITH THE REQUIREMENTS OF N.F.P.A. 13 ORDINARY HAZARD GROUP 2 MAX SPACING 130 SQ. FT. 2. COSCO POINT OF CONNECTION IS AT EXIST BUILDING SHELL SYSTEM 4" MAIN AS SHOWN ON THESE PLANS. 3. ALL PAINTING OF FIRE SPRINKLER PIPING (IF REQ) TO BE DONE BY OTHERS . 4. ALL WIRING BY OTHER. 5. ALL MATERIAL IS NEW U.L. LISTED AND MEETS THE REQUIREMENTS OF THE TUKWILA FIRE FIRE DEPT. 6. OWNER IS RESPONSIBLE TO ASSURE THAT STRUCTURE AS IT IS SHOWN ON CONTRACT DRAWINGS CAN ADEQUATELY SUPPORT ALL FIRE SPRINKLER PIPING LOADS. NO AUXILLIARY DEVICES OR ATTACHMENTS SHALL BE PROVIDED BY COSCO TO SUPPLIMENT THE STRUCTURE TO ACCOMODATE FIRE SPRINKLER PIPING LOADS. 7. OWNER I5 RESPONSIBLE TO PROVIDE ADEQUATE HEAT TO MAINTAIN 40 DEG. F. MINIMUM AT ALL TIMES YEAR ROUND. 8: SPRINKLER HEAD LOCATIONS INDICATED ON THESE DRAWINGS ARE NOT INTENDED TO BE "CENTER OF TILE" HEAD PLACEMENT. 9. COSCO ASSUMES NO RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, FOR THE CONDITION, PERFORMANCE OR CURRENT CODE COMPLIANCE. OF THE EXISTING SYSTEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY COSCO. 10. OWNER IS RESPONSIBLE TO ARRANGE FOR THE PERIODIC INSPECTION, TESTING AND MAINTENANCE OF THESE FIRE SPRINKLER SYSTEMS IN ACCORDANCE WITH THE MINIMUM REQUIREMENTS OF N.F.P.A. 25-2002 BY QUALIFIED PERSONNEL COMMENCING AFTER WARRANTY PERIOD HAS EXPIRED. THE FIRM THAT DESIGNED AND INSTALLED THIS SYSTEM IS BEST QUALIFIED TO PROVIDE THE ONGOING. LONG TERM TESTING, MAINTENANCE AND SERVICING OF THIS SYSTEM(S). FIELD NOTES ****** I) THREADED PIPE FROM 1" THRU 2" SIZE TO BE SCH. 40 STD. WALL PIPE (IMPORT). 2) GROOVED END PIPE FROM 2 1/2" THRU 8" TO BE SC11.1 O (IMPORT). 3) ALL GROOVED COUPLING ARE TO BE "RIGID" TYPE U.N.O. (IMPORT). 4) ALL THREADED FITTINGS ARE 300# CLASS D.I. (IMPORT). FIELD/NOTES 1" s EXISTING PIPE NEW PIPE EXISTING HEAD NEW HEAD REG NEW HEAD CCDN PAU) - 2008 gi' w !!a Fire DUB REVISIONS NO. DESCRIPTION DATE BY SPRINKLER HEAD LEGEND : SYMBOL S/N ORIFICE NPT K -FACT. HEAD FINISH FINISH TEMP. QUAN. RELIABLE MOD G4A CONCEALED SSP 1/2' 1/2'. 5.6 BRASS WHT 165 1(0 REUABLE MOD G4A CONCEALED SSP co 1/2' 1/2'' 5.6 BRASS BLACK . 165 REUABLE MOD F1 FR REC SSP 1/2' 1/2' 5.6 WHT WHT 155 20 APPROVALS BY: TOTAL SPRINKLERS THIS SHEET GV . • 0 . 1 cosco •••••... ••0••••• Fire Protection FIRE PROTECTION AND LIFE SAFETY SPECIALISTS www.coscofire.com WASHINGTON OFFICE 15000 Woodinville -Redmond Rd NE License No: Woodinville, Washington 98072 COSCOFP110NM call (425) 686-8300 • fax (425) 827-4784 SAN DIEGO • LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEATILE • ANCHORAGE PROJECT :PAYLESS SHOES 2866 SOUTHCENTER MALL SPACE # 2165 TUKWILA, WA 98188. WELDON 913-226-8468 SCALE: 1/4=1'-0 CONTRACT BRUNDIGE FLOOR COVERINGS 10203 W 125TH TERRACE OVERLAND PARK, KS 66213 DRAINING ME FIRE SPRINKLER TENANT IMPROVEMENT a1E : 05/27/08 SCALE : 1 /4= 1'- 0" DRAWN BY : BRIAN SCHULZE I'5KS-7944 SHEET NO. D 2866 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-248 08-S-273 08-S-265 i1 • FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Payless Shoes 2866 Southcenter Mall Permit No.: 08-S-265 Date: June 4, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. • COSCO FIRE PROTECTION, INC. 10910 - 117TH PLACE, N.E. KIRKLAND,WA 98033-5027 HYDRAULIC CALCULATIONS FOR PAYLESS SHOES 2866 SOUTHCENTER MALL TUKWILLA, WA 98188A FILE NUMBER:25KS-7944 DATE: 05/30/08 -DESIGN DATA - OCCUPANCY CLASSIFICATION: ORDINARY HAZARD GROUP -2 DENSITY: 0.20 gpm/sq. ft. AREA OF APPLICATION: 1595 sq. ft. COVERAGE PER SPRINKLER: 120 sq. ft. NUMBER OF SPRINKLERS CALCULATED: 17 sprinklers TOTAL SPRINKLER WATER FLOW REQUIRED: 570.7 gpm TOTAL WATER REQUIRED (including hose): 900.8 gpm FLOW AND PRESSURE (@ BOR): 650.7 gpm @ 97.2 psi SPRINKLER ORIFICE SIZE: 1/2 inch NAME OF CONTRACTOR: COSCO FIRE PROTECTION DESIGN/LAYOUT BY: BRIAN SCHULZE AUTHORITY HAVING JURISDICTION: TUKWILLA FIRE CONTRACTOR CERTIFICATION NUMBER: COSCOFP110NM CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 4903012830) HRS SYSTEMS, INC. TUCKER, GA 30084 TUCKER, GA 30084 DATE: 5/30/2008 JOB TITLE: PAYLESS SHOES SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 C:\HASS78\HASSDATA\PAYLESS SHOES.SDF WATER SUPPLY DATA SOURCE NODE TAG SOURCE STATIC PRESS. (PSI) 140.0 RESID. PRESS. (PSI) 20.0 AGGREGATE FLOW ANALYSIS: FLOW (GPM) 10900.0 TOTAL FLOW AT SOURCE TOTAL HOSE STREAM ALLOWANCE AT SOURCE OTHER HOSE STREAM ALLOWANCES TOTAL DISCHARGE FROM ACTIVE SPRINKLERS NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE (FT) 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 AVAIL. PRESS. (PSI) 138.8 TOTAL @ DEMAND (GPM) 900.8 GPM 250.0 GPM 80.0 GPM 570.8 GPM PRESSURE (PSI) 21.7 21.7 21.6 22.3 22.4 32.5 32.4 47.6 50.1 40.5 40.8 44.4 50.6 42.2 41.0 44.4 49.4 25.0 25.4 25.1 25.5 25.6 27.1 25.3 27.5 32.2 34.6 35.6 37.8 35.5 38.5 53.2 57.6 57.5 REQ'D PRESS. (PSI) 900.8 104.8 DISCHARGE (GPM) 26.1 26.1 26.0 26.5 26.5 31.9 31.9 38.6 39.7 35.7 35.8 37.3 39.8 36.4 35.9 37.3 39.4 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 5/30/2008 C:\HASS78\HASSDATA\PAYLESS SHOES.SDF JOB TITLE: PAYLESS SHOES NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) 17A 31.5 18 28.0 19 28.0 20 28.0 21 28.0 22 28.0 23 31.5 24 31.5 25 31.5 26 28.0 27 28.0 28 31.5 29 31.5 30 28.0 31 28.0 32 28.0 33 31.5 34 31.5 35 31.5 36 28.0 37 31.5 38 31.5 39 31.5 40 31.5 41 31.5 42 31.5 43 33.5 44 33.5 45 33.5 46 14.0 TOR 14.0 BOR 2.0 M10 2.0 BFO 4.0 BFI 4.0 UG1 1.2 SOURCE -4.0 HOSE STREAM SOURCE 57.6 48.8 48.7 48.7 49.1 50.6 50.3 51.8 58.0 46.4 46.8 49.4 56.6 48.4 49.3 51.0 50.8 51.8 58.5 47.0 49.4 55.3 58.2 58.5 59.0 78.1 78.6 78.8 80.3 89.2 90.8 97.2 97.3 96.6 101.1 102.3 104.8 80.0 650.8 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 'DATE: 5/30/2008 C:\HASS78\HASSDATA\PAYLESS SHOES.SDF JOB TITLE: PAYLESS SHOES PIPE DATA PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 1 -26.1 1.049 PL 20.00 PF 4.7 101 25.0 5.6 21.7 26.1 9.7 120 FTG E PE -1.3 1 28.0 0.0 25.0 0.0 0.212 TL 22.00 PV Pipe: 2 -26.1 1.049 PL 20.00 PF 4.7 102 25.0 5.6 21.7 26.1 9.7 120 FTG E PE -1.3 3 28.0 0.0 25.1 0.0 0.213 TL 22.00 PV Pipe: 3 -26.1 1.610 PL 4.00 PF 0.3 1 28.0 0.0 25.0 0.0 4.1 120 FTG T PE 0.0 2 28.0 0.0 25.4 0.0 0.026 TL 12.00 PV Pipe: 4 -26.1 1.610 PL 3.00 PF 0.3 3 28.0 0.0 25.1 0.0 4.1 120 FTG T PE 0.0 2 28.0 0.0 25.4 0.0 0.026 TL 11.00 PV Pipe: 5 -52.1 1.610 PL 2.00 PF 0.2 2 28.0 0.0 25.4 0.0 8.2 120 FTG ---- PE 0.0 4 28.0 0.0 25.5 0.0 0.095 TL 2.00 PV Pipe: 6 -26.0 1.049 PL 18.00 PF 5.3 103 25.0 5.6 21.6 26.0 9.7 120 FTG ET PE -1.3 4 28.0 0.0 25.5 0.0 0.211 TL 25.00 PV Pipe: 7 -78.1 1.610 PL 8.00 PF 1.6 4 28.0 0.0 25.5 0.0 12.3 120 FTG ---- PE 0.0 6 28.0 0.0 27.1 0.0 0.201 TL 8.00 PV Pipe: 8 -26.5 1.049 PL 19.00 PF 4.6 104 25.0 5.6 22.3 26.5 9.8 120 FTG E PE -1.3 5 28.0 0.0 25.6 0.0 0.218 TL 21.00 PV Pipe: 8A -26.5 1.049 PL 2.00 PF 1.5 5 28.0 0.0 25.6 0.0 9.8 120 FTG T PE 0.0 6 28.0 0.0 27.1 0.0 0.218 TL 7.00 PV Pipe: 9 -104.6 1.610 PL 1.00 PF 0.3 6 28.0 0.0 27.1 0.0 16.5 120 FTG ---- PE 0.0 8 28.0 0.0 27.5 0.0 0.345 TL 1.00 PV Pipe: 10 -26.5 1.049 PL 17.00 PF 4.2 105 25.0 5.6 22.4 26.5 9.8 120 FTG E PE -1.3 7 28.0 0.0 25.3 0.0 0.219 TL 19.00 PV Pipe: 11 -26.5 1.049 PL 5.00 PF 2.2 7 28.0 0.0 25.3 0.0 9.8 120 FTG T PE 0.0 8 28.0 0.0 27.5 0.0 0.219 TL 10.00 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: 5/30/2008 C:\HASS78\HASSDATA\PAYLESS SHOES.SDF JOB TITLE: PAYLESS SHOES PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 12 -131.1 1.610 PL 5.00 PF 4.7 8 28.0 0.0 27.5 0.0 20.7 120 FTG E PE 0.0 9 28.0 0.0 32.2 0.0 0.524 TL 9.00 PV Pipe: 13 -131.1 1.610 PL 3.50 PF 3.9 9 28.0 0.0 32.2 0.0 20.7 120 FTG E PE -1.5 10 31.5 0.0 34.6 0.0 0.524 TL 7.50 PV Pipe: 14 -131.1 1.610 PL 6.00 PF 3.1 10 31.5 0.0 34.6 0.0 20.7 120 FTG ---- PE 0.0 12 31.5 0.0 37.8 0.0 0.524 TL 6.00 PV Pipe: 15 -31.9 1.049 PL 17.00 PF 5.9 106 25.0 5.6 32.5 31.9 11.9 120 FTG E PE -2.8 11 31.5 0.0 35.6 0.0 0.309 TL 19.00 PV Pipe: 16 -31.9 1.049 PL 2.00 PF 2.2 11 31.5 0.0 35.6 0.0 11.9 120 FTG T PE 0.0 12 31.5 0.0 37.8 0.0 0.309 TL 7.00 PV Pipe: 17 -163.1 1.610 PL 1.00 PF 0.8 12 31.5 0.0 37.8 0.0 25.7 120 FTG ---- PE 0.0 14 31.5 0.0 38.5 0.0 0.784 TL 1.00 PV Pipe: 18 -31.9 1.049 PL 17.00 PF 5.9 107 25.0 5.6 32.4 31.9 11.8 120 FTG E PE -2.8 13 31.5 0.0 35.5 0.0 0.308 TL 19.00 PV Pipe: 19 -31.9 1.049 PL 5.00 PF 3.1 13 31.5 0.0 35.5 0.0 11.8 120 FTG T PE 0.0 14 31.5 0.0 38.5 0.0 0.308 TL 10.00 PV Pipe: 20 -195.0 1.610 PL 10.00 PF 19.6 14 31.5 0.0 38.5 0.0 30.7 120 FTG T PE 0.0 39 31.5 H.S. 58.2 80.0 1.091 TL 18.00 PV Pipe: 21 -38.6 1.049 PL 17.00 PF 8.4 108 25.0 5.6 47.6 38.6 14.3 120 FTG E PE -2.8 15 31.5 0.0 53.2 0.0 0.440 TL 19.00 PV Pipe: 22 -38.6 1.049 PL 5.00 PF '4.4 15 31.5 0.0 53.2 0.0 14.3 120 FTG T PE 0.0 16 31.5 0.0 57.6 0.0 0.440 TL 10.00 PV Pipe: 23 -38.6 1.610 PL 1.00 PF 0.1 16 31.5 0.0 57.6 0.0 6.1 120 FTG ---- PE 0.0 17A 31.5 0.0 57.6 0.0 0.055 TL 1.00 PV Pipe: 24 -40.8 1.610 PL 1.00 PF 0.5 17A 31.5 0.0 57.6 0.0 6.4 120 FTG T PE 0.0 39 31.5 H.S. 58.2 80.0 0.060 TL 9.00 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 DATE: 5/30/2008 C:\HASS78\HASSDATA\PAYLESS SHOES.SDF JOB TITLE: PAYLESS SHOES PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 25 -43.0 1.049 PL 17.00 PF 10.2 109 25.0 5.6 50.1 39.7 15.9 120 FTG E PE -2.8 17 31.5 0.0 57.5 0.0 0.535 TL 19:00 PV Pipe: 26 -43.0 1.610 PL 2.00 PF 0.1 17 31.5 0.0 57.5 0.0 6.8 120 FTG ---- PE 0.0 17A 31.5 0.0 57.6 0.0 0.066 TL 2.00 PV Pipe: 27 -40.8 1.610 PL 1.00 PF 0.5 17A 31.5 0.0 57.6 0.0 6.4 120 FTG T PE 0.0 39 31.5 H.S. 58.2 80.0 0.060 TL 9.00 PV Pipe: 28 3.3 1.049 PL 17.00 PF 0.1 109 25.0 5.6 50.1 39.7 1.2 120 FTG E PE -1.3 18 28.0 0.0 48.8 0.0 0.005 TL 19.00 PV Pipe: 29 3.3 1.049 PL 4.00 PF 0.0 18 28.0 0.0 48.8 0.0 1.2 120 FTG T PE 0.0 19 28.0 0.0 48.7 0.0 0.005 TL 9.00 PV Pipe: 30 3.3 1.610 PL 3.00 PF 0.0 19 28.0 0.0 48.7 0.0 0.5 120 FTG ---- PE 0.0 20 28.0 0.0 48.7 0.0 0.001 TL 3.00 PV Pipe: 31 -35.7 1.049 PL 17.00 PF 7.2 110 25.0 5.6 40.5 35.7 13.2 120 FTG E PE -1.3 26 28.0 0.0 46.4 0.0 0.379 TL 19.00 PV Pipe: 32 -35.7 1.049 PL 1.00 PF 2.3 26 28.0 0.0 46.4 0.0 13.2 120 FTG T PE 0.0 20 28.0 0.0 48.7 0.0 0.379 TL 6.00 PV Pipe: 33 -32.3 1.610 PL 9.00 PF 0.4 20 28.0 0.0 48.7 0.0 5.1 120 FTG ---- PE 0.0 21 28.0 0.0 49.1 0.0 0.039 TL 9.00 PV Pipe: 34 -35.8 1.049 PL 17.00 PF 7.3 111 25.0 5.6 40.8 35.8 13.3 120 FTG E PE -1.3 27 28.0 0.0 46.8 0.0 0.382 TL 19.00 PV Pipe: 35 -35.8 1.049 PL 1.00 PF 2.3 27 28.0 0.0 46.8 0.0 13.3 120 FTG T PE 0.0 21 28.0 0.0 49.1 0.0 0.382 TL 6.00 PV Pipe: 36 -68.1 1.610 PL 6.00 PF 1.6 21 28.0 0.0 49.1 0.0 10.7 120 FTG E PE 0.0 22 28.0 0.0 50.6 0.0 0.156 TL 10.00 PV Pipe: 37 -68.1 1.610 PL 3.50 PF 1.2 22 28.0 0.0 50.6 0.0 10.7 120 FTG E PE -1.5 23 31.5 0.0 50.3 0.0 0.156 TL 7.50 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7 DATE: 5/30/2008 C:\HASS78\HASSDATA\PAYLESS SHOES.SDF JOB TITLE: PAYLESS SHOES PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 38 -68.1 1.610 PL 6.00 PF 1.6 23 31.5 0.0 50.3 0.0 10.7 120 FTG E PE 0.0 24 31.5 0.0 51.8 0.0 0.156 TL 10.00 PV Pipe: 39 -37.3 1.049 PL 17.00 PF 7.8 112 25.0 5.6 44.4 37.3 13.8 120 FTG E PE -2.8 28 31.5 0.0 49.4 0.0 0.412 TL 19.00 PV Pipe: 40 -37.3 1.049 PL 1.00 PF 2.5 28 31.5 0.0 49.4 0.0 13.8 120 FTG T PE 0.0 24 31.5 0.0 51.8 0.0 0.412 TL 6.00 PV Pipe: 41 -105.4 1.610 PL 11.00 PF 6.6 24 31.5 0.0 51.8 0.0 16.6 120 FTG T PE 0.0 40 31.5 0.0 58.5 0.0 0.350 TL 19.00 PV Pipe: 42 -39.8 1.049 PL 17.00 PF 8.8 113 25.0 5.6 50.6 39.8 14.8 120 FTG E PE -2.8 29 31.5 0.0 56.6 0.0 0.465 TL 19.00 PV Pipe: 43 -39.8 1.049 PL 1.00 PF 1.4 29 31.5 0.0 56.6 0.0 14.8 120 FTG E PE 0.0 25 31.5 0.0 58.0 0.0 0.465 TL 3.00 PV Pipe: 44 -39.8 1.610 PL 1.00 PF 0.5 25 31.5 0.0 58.0 0.0 6.3 120 FTG T PE 0.0 40 31.5 0.0 58.5 0.0 0.058 TL 9.00 PV Pipe: 45 -36.4 1.049 PL 17.00 PF 7.5 114 25.0 5.6 42.2 36.4 13.5 120 FTG E PE -1.3 30 28.0 0.0 48.4 0.0 0.394 TL 19.00 PV Pipe: 46 -36.4 1.610 PL 14.00 PF 0.9 30 28.0 0.0 48.4 0.0 5.7 120 FTG E PE 0.0 31 28.0 0.0 49.3 0.0 0.049 TL 18.00 PV Pipe: 47 -35.9 1.049 PL 17.00 PF 7.3 115 25.0 5.6 41.0 35.9 13.3 120 FTG E PE -1.3 36 28.0 0.0 47.0 0.0 0.383 TL 19.00 PV Pipe: 48 -35.9 1.049 PL 1.00 PF 2.3 36 28.0 0.0 47.0 0.0 13.3 120 FTG T PE 0.0 31 28.0 0.0 49.3 0.0 0.383 TL 6.00 PV Pipe: 49 -72.2 1.610 PL 6.00 PF 1.7 31 28.0 0.0 49.3 0.0 11.4 120 FTG E PE 0.0 32 28.0 0.0 51.0 0.0 0.174 TL 10.00 PV Pipe: 50 -72.2 1.610 PL 3.50 PF 1.3 32 28.0 0.0 51.0 0.0 11.4 120 FTG E PE -1.5 33 31.5 0.0 50.8 0.0 0.174 TL 7.50 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 8 DATE: 5/30/2008 C:\HASS78\HASSDATA\PAYLESS SHOES.SDF JOB TITLE: PAYLESS SHOES PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 51 -72.2 1.610 PL 6.00 PF 1.0 33 31.5 0.0 50.8 0.0 11.4 120 FTG ---- PE 0.0 34 31.5 0.0 51.8 0.0 0.174 TL 6.00 PV Pipe: 52 -37.3 1.049 PL 17.00 PF 7.8 116 25.0 5.6 44.4 37.3 13.8 120 FTG E PE -2.8 37 31.5 0.0 49.4 0.0 0.412 TL 19.00 PV Pipe: 53 -37.3 1.049 PL 1.00 PF 2.5 37 31.5 0.0 49.4 0.0 13.8 120 FTG T PE 0.0 34 31.5 0.0 51.8 0.0 0.412 TL 6.00 PV Pipe: 54 -109.5 1.610 PL 11.00 PF 7.1 34 31.5 0.0 51.8 0.0 17.3 120 FTG T PE 0.0 41 31.5 0.0 59.0 0.0 0.375 TL 19.00 PV Pipe: 55 -39.4 1.049 PL 17.00 PF 8.7 117 25.0 5.6 49.4 39.4 14.6 120 FTG E PE -2.8 38 31.5 0.0 55.3 0.0 0.456 TL 19.00 PV Pipe: 56 -39.4 1.049 PL 2.00 PF 3.2 38 31.5 0.0 55.3 0.0 14.6 120 FTG T PE 0.0 35 31.5 0.0 58.5 0.0 0.456 TL 7.00 PV Pipe: 57 -39.4 1.610 PL 1.00 PF 0.5 35 31.5 0.0 58.5 0.0 6.2 120 FTG T PE 0.0 41 31.5 0.0 59.0 0.0 0.057 TL 9.00 PV Pipe: 58 -356.6 4.260 PL 10.50 PF 0.3 39 31.5 H.S. 58.2 80.0 8.0 120 FTG ---- PE 0.0 40 31.5 0.0 58.5 0.0 0.029 TL 10.50 PV Pipe: 59 -501.8 4.260 PL 9.00 PF 0.5 40 31.5 0.0 58.5 0.0 11.3 120 FTG ---- PE 0.0 41 31.5 0.0 59.0 0.0 0.055 TL 9.00 PV Pipe: 60 -650.7 4.260 PL 163.00 PF 19.2 41 31.5 0.0 59.0 0.0 14.6 120 FTG 4E PE 0.0 42 31.5 0.0 78.1 0.0 0.089 TL 215.80 PV Pipe: 61 -650.7 4.260 PL 2.00 PF 1.3 42 31.5 0.0 78.1 0.0 14.6 120 FTG E PE -0.9 43 33.5 0.0 78.6 0.0 0.089 TL 15.20 PV Pipe: 62 -650.7 4.260 PL 2.00 PF 0.2 43 33.5 0.0 78.6 0.0 14.6 120 FTG ---- PE 0.0 44 33.5 0.0 78.8 0.0 0.089 TL 2.00 PV Pipe: 63 -650.7 6.357 PL 45.00 PF 1.5 44 33.5 0.0 78.8 0.0 6.6 120 FTG 2ET PE 0.0 45 33.5 0.0 80.3 0.0 0.013 TL 117.90 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 9 DATE: 5/30/2008 C:\HASS78\HASSDATA\PAYLESS SHOES.SDF JOB TITLE: PAYLESS SHOES PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 64 -650.7 6.357 PL 19.50 PF 0.5 45 33.5 0.0 80.3 0.0 6.6 120 FTG E PE 8.4 46 14.0 0.0 89.2 0.0 0.013 TL 37.10 PV Pipe: 65 -650.7 6.357 PL 60.00 PF 1.6 46 14.0 0.0 89.2 0.0 6.6 120 FTG 4E PE 0.0 TOR 14.0 0.0 90.8 0.0 0.013 TL 130.40 PV Pipe: 66 -650.7 6.357 PL 12.00 PF 1.1 TOR 14.0 0.0 90.8 0.0 6.6 120 FTG TC PE 5.2 BOR 2.0 0.0 97.2 0.0 0.013 TL 89.90 PV Pipe: 67 -650.7 8.249 PL 3.58 PF 0.1 BOR 2.0 0.0 97.2 0.0 3.9 120 FTG E PE 0.0 M10 2.0 0.0 97.3 0.0 0.004 TL 23.58 PV Pipe: 68 -650.7 10.374 PL 31.42 PF 0.2 M10 2.0 0.0 97.3 0.0 2.5 120 FTG 4EB PE -0.9 BFO 4.0 0.0 96.6 0.0 0.001 TL 151.12 PV Pipe: 69 FIXED PRESSURE LOSS DEVICE BFI 4.0 0.0 101.1 0.0 4.5 psi, 650.7 gpm BFO 4.0 0.0 96.6 0.0 Pipe: 70 -650.7 10.374 PL 2.83 PF 0.0 BFI 4.0 0.0 101.1 0.0 2.5 120 FTG B PE 1.2 UG1 1.2 0.0 102.3 0.0 0.001 TL 24.13 PV Pipe: 71 -650.8 10.275 PL 85.00 PF 0.2 UG1 1.2 0.0 102.3 0.0 2.5 140 FTG 2ETG PE 2.2 SOURCE -4.0 SRCE 104.8 (N/A) 0.001 TL 225.80 PV NOTES (HASS): (1) Calculations were performed by the HASS 7.9 computer program under license no. 4903012830 granted by HRS Systems, Inc. 4792 LaVista Road Tucker, GA 30084 (2) The system has been calculated to provide an average imbalance at each node of 0.002 gpm and a maximum imbalance at any node of 0.166 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 30.7 ft/sec at pipe 20. SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 10 DATE: 5/30/2008 C:\HASS78\HASSDATA\PAYLESS SHOES.SDF JOB TITLE: PAYLESS SHOES (4) PIPE FITTINGS TABLE Pipe Table Name: MOST.PIP PAGE: A MATERIAL: SCH.40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D F Ell Tee LngEll ChkV1v BfyVly GatV1v AlmChk DPV1v 45E11 H Q I S U V W 22/Ell 11gE11 Couplg FM90E1 FM45E1 FMTee FMRunT 1.049 2.00 5.00 2.00 5.00 6.00 1.00 17.00 23.00 1.00 0.50 0.30 1.00 6.00 5.00 9.00 0.00 1.610 4.00 8.00 2.00 9.00 6.00 1.00 17.00 23.00 2.00 1.00 0.50 1.00 8.00 6.00 12.00 0.00 PAGE: B MATERIAL: SCH.10 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D F Ell Tee LngEll ChkVly BfyVly GatVly AlmChk DPV1v 45E11 4.260 6.357 8.249 10.374 H Q I S U V W 22/Ell 11gE11 Couplg FM90E1 FM45E1 FMTee FMRunT 13.20 26.30 7.90 29.00 15.80 2.60 36.90 39.50 6.60 3.30 1.60 1.30 18.40 11.90 31.60 0.00 17.60 37.70 11.30 40.20 12.60 3.80 37.70 41.50 8.80 4.40 2.20 1.30 22.60 13.80 42.70 0.00 20.00 38.90 14.50 50.00 13.30 4.40 45.60 41.50 10.00 5.00 2.50 1.10 24.50 14.50 43.40 0.00 24.60 56.00 17.90 61.60 21.30 5.60 45.60 41.50 12.30 6.20 3.10 1.10 29.10 16.80 56.00 0.00 PAGE: D MATERIAL: DI -52 HWC: 140 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D F Ell Tee LngEll ChkV1v BfyVly GatVly AlmChk DPV1v 45E11 10.275 H Q 22/Ell 11gEll 31.30 71.10 22.70 78.20 27.00 7.10 61.20 47.20 15.60 7.80 3.90 NOTES (USER): • SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 11 DATE: 5/30/2008 JOB TITLE: PAYLESS SHOES WATER SUPPLY ANALYSIS Flow: 10900.0 gpm 0 0 0 140.00 psi Resid: C:\HASS78\HASSDATA\PAYLESS SHOES.SDF E E a) a) a a rn rn�+ 7 7 a)oo oUU • •v 7 0 Sa 0 x,21 A a) • W • 04 z ° • ° • CO Q C7 • � 0, •r -I aa A r)' w °,-' m• -c S 70 >, • 7 • CO CO co 01 w m o • ai Ava rl N 0 N O 0 0 0 0 l0 N 0 H H H H O 0 CO 0 0 004 (.7w arzwancnAww 04 En 0 O d4 0 0 N GO 0 0 0 O H O O 0 N N SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 12 DATE: 5/30/2008 C:\HASS78\HASSDATA\PAYLESS SHOES.SDF JOB TITLE: PAYLESS SHOES WATER SUPPLY CURVE 132+ \ \ I \ I P 96+ R I E I S 1 S 84+ U 1 R 1 E 72+ \ ( I \ P I \ S I \ I 60+ \ I \ I \ I \ 48+ \ I \ I \ I \ 36+ \ I \ I \ I \ 24+ LEGEND \ \ \ \ \ \ \ X = Required Water Supply 104.77 psi @ 900.8 gpm 0 = Available Water Supply 138.81 psi @ 900.8 gpm "* <-20.0 psi @ 10900 gpm " Flow Test Point II II II II 0++-+---+----+ + + + + + + 32004800 6400 8000 9600 11200 12800 14400 16000 FLOW (GPM) FILE CO"Y SHEET INDEX. IlIt; ',1t E A„..,: ALAI III; YTEM TUKWIL'''F;i f HINOTON NERAL NOTES S =ET \UVI3ESHEET TITLE FA -01 SYSTEV INFOVATIO\ FA --02 TYPICAL DETAILS - WRI\ G A\3 MOUNTI\G FA --03 FRE ALARM SYSTEM FLOO PLA FA -04 YSTEv1 CALCULATIO\S (CE\EAL), �ISE�, SITE PLA\ tEr Without Comments As Noted In Red Per The Attached Letter I nese pans h ve he=n review :d 17y The Tukwila iia Fire Prevention i_.}Urea'? •`or CO:'...+f �'iai;C0 ith current city standards. A,c,:.c ',cE: i; +� _ ':::(errocs and omissions w;.;.'h ....r .,t7_.7--''.1i<.tir.n:, Pi adopted Istantiar os ..,Inc: , . . , • r=: Unsi ii,tyrfor the i cie(qui cv ::t •.. ...,i:; ','II; 1.;.:.:: {:a . i ne. r. ; dc,fIt:-)rs .. .r � ;; i:iifa +!jfa ,atter ifliS dat . '‘,1,--4 ...r'- ... Ind..5+iil requite a resubmittal ct i.a+ut egt!ent approval. Final acc:ptsy _ Lit .... -i tltwvct6r,`d inspection by Date: 5-3o--(42,By: ru kWILA FIRE DEPARTMEN1.. Please call: 575-440Z and give this job t•No._Q - and exact addre3s for shut. approval. NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and c; min tion of the testing. WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATION SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) 2S STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) 2V SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) 'B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART :iri 11 I. :. :: ! ;'i. :�-»+i;,i.,.;• it h.t,�l ' NO. ! CONDUIT -1 ' i i i'.' : li I I, i!! OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ' ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9,, TABLE 4. SHIELDED WIRE TO . BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END 4.t 1 ;j;i FOR SIEMENS SYSTEM': , L!1 ' DO NOT INSTALL ADDRESSABLE DEVICES ADDRESS. !' INITIATING DEVICES UNTIL. PREPROGRAMMED WITH 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE',;; THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIfOUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING I ,SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN`I STRIC1T ;CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL ;CbDE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I +', I. CONQUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER Of TICSII.E ABLE, FITTINGS, AND ASSOCIATED "'EQUIPvIENT) ARE NOT SUPPLIED BY SIEMENS ;CERBERUS DIVISION. 6. DETECTORS SHALL NOT BEOUNTED IN DIRECT AIR STREAM OF AIR SUPPLYI' OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAT ;WITH : ESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOII:CODEIi:CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOCI( TUTU , IDENTIFICATION. I : 8. INSTALLING CONTRACTOR SH LL;;RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" URP'OSES. • t I' 9. FOR ADDITIONAL INSTALLATIN 'If STRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATIP INSTRUCTIONS. 10. THE 120vac POWER ELECTRRK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICL° j72 !A{ ND 760 OF NEPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5 ..5.2 .' 1'N REFERENCE TO DEDICATED . BRANCH POWER SOURCES. 120vac POWER S ;ALL';N!OT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRL: AL , M TECHNICIAN. 11. ALL HORN STROBE AND STI.OB ;'EVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A:F.F. OR 6" BELOW DROPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATION' .SH`ALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. I' 13. ALL PANEL NUMBERS AND ',CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE 'ROM 'DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. :I 15. PER NFPA 72 SECTION 5-3..6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN- UP OF! ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY; THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED. OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP' TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED,' :VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS. INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALLDEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR . SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR ' INSTALLATION. 20. DETECTORS MUST BE RAID) !FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS 'SHALL BE LOCATED IN CONDUIT. •1 22. NFPA 72 2007 6.4.2.2.2 ALk' 1 STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G;„ METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE .:OUTCGOI.NG 'AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE, ',,ONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT ''4 CONDUCTORS SHALL NOT B!fU�N' ISN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), E{N IIDSURE, OR RACEWAY. illy NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETYVEEN.; JHE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUI; D .T0j ELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DA ElHE RECOMMENDED MINIMUM SEPARATION TO PREVENT PVYSICAL, DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VO,TICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED I 23. IH: QUANTITY 3 2 2 2 2 EX OL DESCRIPTION EX EX IRE ALARM ONTROL PANEL IRE ALARM ;EMOTE ANNUNCIATOR REMOTE BOOSTER ROWER SUPPLY 1TERFACE MODULE ITH RELAY UAL INPUT ITERFACE MODULE 'ONTROL POINT ODULE SYMBOLS LEGEND MODEL XLS-V SDD-C PAD -3 HTRI-R HTRI-D HCP EMOTE CONVENTIONAL HZM i.ONE MODULE INEAR BEAM MOKE DETECTOR MANUFACTURER BACKBOX SIEMENS SIEMENS SIEMENS SIEMENS SIEMENS SIEMENS SIEMENS PBA -1191 SIEMENS SMOKE DETECTOR HFP-11 W/ SIEMENS ADDRESSABLE -PHOTO) DB -11 BASE I I UCT SMOKE ETECTOR EAT DETECTOR DDRESSABLE) I,IRE ALARM RPEAKER STROBE :CEILING MOUNT) IRE ALARM PEAKER STROBE WALL MOUNT) ;;IRE ALARM SPEAKER STROBE ,WALL MOUNT) FIRE ALARM STROBE ;,CEILING MOUNT) FIRE ALARM STROBE HALL MOUNT) SIRE ALARM SPEAKER 'CEILING MOUNT) =IRE ALARM SPEAKER WALL MOUNT) AD2-P W/ SIEMENS TSM MODULE HFPT-11 W/ SIEMENS DB -11 BASE SET -MC -CW SIEMENS SET -MC -W SIEMENS SET -HMC -CW SIEMENS ZR -MC -CW SIEMENS ZR -MC -W SIEMENS SET -CW SIEMENS SET -W SIEMENS PROVIDED PROVIDED PROVIDED 4S DEEP 45 DEEP 4S DEEP 4S DEEP PROVIDED 4S DEEP W/ 1G RING DUCT HOUSING 4S DEEP W/ 1G RING MOUNTING HEIGHT 66" A.F.F. TO TOP 66" A.F.F. TO TOP 66" A.F.F. TO TOP VERIFY IN FIELD VERIFY IN FIELD VERIFY IN FIELD VERIFY IN FIELD VERIFY IN FIELD CEILING VERIFY IN FIELD CEILING 4S DEEP BOX CEILING W/ 1-1/2" EXT. 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM 4S DEEP BOX CEILING W/ 1-1/2" EXT. 4S BOX W/ 1G RING 4S BOX IN/ 1G RING CEILING 80" A.F.F. TO BOTTOM U.O.N. 4S DEEP BOX CEILING IN/ 1-1/2" EXT. 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM P RIRE ALARM fiTROBE WEATHERPROOF) SET -S17 -WP SIEMENS MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD MRIi ULTI-VOLTAGE ONTROL RELAY MR -201 /C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA :WB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD JUNCTION BOX F.B.O. F,B,❑, N/A VERIFY IN FIELD 'B❑VE FINISHED FLOOR FURNISHED BY OTHERS ,Y NOT APPLICABLE UNLESS OTHERWISE NOTED 4 , WEATHERPROOF DEVICE AS BUILT ADD OR CHANGE A'S BUILT REMOVE H. AS BUILT NOTES TO CAD N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A • Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserv,`d RELEASE/REVISIONS VD :0' cr co z N o 'o - \0 z C/) Q .:. LL'.. ,w.171 -11j1::; I- LIJ O LC) gyp^ Lu F- REV. BY: I z a DESCRIPTION SHOP DRAWINGS DATE co0 in o <1<<<< 2„f., AR: Y2 4 aa) < 0) 2 Z va FE 2- W I_I_I 0 Z -I c O (Z < � <C Q � 0 o� LL SCALE: 1 /8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: \:.OB NUMBER:54534 FA -01 ':••-• !•• I:! ! • • THE DUCT IMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS, FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. • • • !!! BEND OR OTHER :OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS „•• A !II TYPICAL.SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE „.1 : AI • I" • j?. 1. I !I! ' COMBINE ALL SHIELDS ANDJ; ISOLATE FROM GROUNDING •AA • ,• iTO NEXT,,ADDRESSABLE DEVICE STOP IF:,LAST DEVICE -14 FROM XLS .CONTROL PANEL OR fl 'pREVIOUS.:ADDRESSABLE DEVIC DUCT DETECTOR LOCATION 0 !A' t.. 1 ..• ildi•72) END OF, LINE DEVICE(3.6K 1/4W1) _L :i • : :'-:SUPERVISED SWITCH NOTE: ; 1 I !LID GROUND, • HTRI—R STATUS LED oo 0 N.O. 0 COM CO 0 N.C. FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. • 1,r. - PREVIOUS DEVICE TONE -XT DEVICE :• 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) ADDRESSABLE — • • ; ADDRESSABLE .1 + NOTE 1: VOLTAGE MAX. - CURRENT MAX, - CONT. RES. MAX, - MAX. CABLE LENGTH - C (LINE TO LIND- C (LINE TO SHIELD) - MAX, LINE SIZE - MIN, LINE SIZE - MUSIC OUTLETH SAMPLING TUBE • I, I •• : ' ; I • 'I I. I .:, • " ',I II I ! • ! !I • • , H, • ..,A, ' , , TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR INLET SAMPLING TUBE !: , 1 1 , • • , AT LEAST', SIX DUCT. WIDTHS '.. •"A': FROM BEND.. I , ,!... SCALE=NONE 'SOURC .•:,•J • •:I COMBINE; ALL SHIELDS:1..ANDI.,,•• •ISOLATE FROM GROUNDING I ! .;,.„ .• • TO NEXT, ADDRESSABLE DEVICEftI(+) STOP IF LAST DEVICE FROM XLS CONTROL PANEL I TJR1:i44(+) PREVIOUS ADDRESSABLE Do/IL,(-) RELAY CONTACTS (4.0A @L125VAC) (4.0A @ 30VDC) 27 VDC:! 3,5 rnAl DURING. POLLING 10 OHMS ; A ! 200 FT„(I8 AWG) 0.02uF ; 0,04LAFA 14 AWG 18 AWG END:i.OF LINE DEVICE (3.61 1/4W) • ••• A / SSWUIPTECRHV, I7 • -/ GROUND 10 @ A HTRI—D C1) STATUS LED CO 0 CO 0 • ,!.END F •.LINE! ;DEVICE - A• ,.. :3.6K 14'14W) .I.II., .. l• ,i 'SUPE VISED '‘../I.i.'...Fi y:,, ;. .... r• .ri ; . ; , • ,.•:-,; . • :, ,. 'A \ 0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL kfRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL Lig3a SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) NOTE 2: ALL SUPERVISED 'SWITCHES MUST' BE HELDCLOSED A AND/OR OPEN FOR AT LEAST .25 SEC, TO GUARANTEE DETECTION, • • • •-; 1. • !! r • A- GNDI;I•1:!:'AC • •, • .! • 0 0 0 t • f• A . 1 _ • ; • . ,.-0 PAD -3 INPUT - TROUBLE- NAC1 NAC2 • • •:.1+ 1-' 1 2+2- 2 -NC C NO +- + ,NAC3 NAC4, AUX ' A + - 11,12 0 0 G A 24K ' 0 • n ; TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE '...1!1!•! • • NC -4 NAC -3 NAC -2 NAC -1 • 411 A I:,,r.- FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. • NOT USED 0 REMOTE -T- DEVICE LOOP 0 NOT USED 0 REMOTE DEVICE LOOP FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (—)> 470 OHMS 110/ EOL IC INPU LEO TEM -1 Ls - N. • EAR GRO —)r.-(+) TO >(—) S c) TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE: NONE FROM REMOTE POWER SUPPLY ('S' CABLE) FROM FACP (VOICE CIRCUIT) ('V' CABLE) • C C (.1-) H STROBE SPEAKER (-1-) STROBE (+) (—) STROBE SPEAKER (4-) (--) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY, . 80" A.F.F. 4S DEEP BOX • W/ 1-1 /2" • EXTENSION RING (SPEAKER 11-ZOBE) 45 BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALENONE, •. .. ; t .•.. s • XT DEA OR IF LAST DEVICE TO DE, EN TL EXT ICE OR OF LINE EXT CE OR OF LINE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERTINTEMPERATIIRE: +320*F C TO 100' F (38' C) HUMIDITY: 0-93% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR FROM PREVIOUS .! ADDRESSABLE DEVICE; .. OR POWER SOURCE: • . DATA IN (-7).> DATA IN (+) . • DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WN DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE • TO NEXT DEVICE'— REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LPTBEL SCALE - • >( ) DATA OUT (+) DATA OUT CEILING MOUNT S PEAKER/STROBE MOUNTING (HARD LID) HARD LID— CEILING HARD LID SPEAKER SUPPORT TILE BRIDGE • ••1 ;I '111!:!•, '.. A • 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION N CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKER/STROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTION BOX MOUNTED ON CEILING FLEX \'‘. • JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT 0 0 jTO NEXT • SMOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE:NONE 00 DC) NOT: I AQRESSABLE DEVICES „NTIL D.REPOQRAMMED W DEVICFS DD S. ri ht 006 Gudrdian:Securit S stems, Inc. All Rights Rsery en I • !.! • • ; ' - • • i LU LL Qin CALE: 1 8 —1' DRAWN I.ANDERSON. • DESIGNED BY:: R.VEZZANI I DATE:5/12/08 BACKROUND PLAN PROVIDED BY: \,OB NUMBP:4534 SHEET 4 , jA. t• . to cu • • 43 1 x-1 • c). cv • • , 1- ,, Q .1. -I < 41..) "0 1 • .03 Tr' (r; r) c0 c:t c) cNi c0 ' rq • c). . I 1:1 • (j) LLI i• :!! < ! ; (1) Cn !!! 0 ! t E 1. 4(0 - • ; LLJ i '< ! Z •:2 L.L.1 '0 1 Dte 1 ! .< • ! L1J I ! t !.0 Lf). jl • CL • • • !'! ']!! ! 't ..! 1 t • • • 1:1 •1!! !!: ! I! .1! '11 : 'ffir LU !In mervynirs Li L. 1 (---S .>DS• LOCKER :ROOM CLEC oNIC'S BOUTIQUE PRETZEI:f. TUE 11 I SPORTS S LE • 'PlC) F: K WEIi N lONG coLJN-ry LekAr-z\ir M E CC. _L.1 F- CL ti I 17 PAYLESS WESTFIELD SOUTHCENTER MALL SCALE 113264 2S,2V 2S,2V 2S,2V 2S,2V 2S,2V 2S,2V (1 75 C 75 C 15 30 15 15 EOL -S1 FA -430X 1 FACP EX RISER DIAGRAM D,I 21, rrent Load: Ovice TYpe -11 2- 137- FkIrD :11 Qty - SYSTEM CA FACP ADD ONS Standby: Amps 0.0022 0.0635 0.009600 0.001600 0.005 Total 0.0022 .0.0635 0.0096 Amps 0.0023 0.064 0.021 0.0035 0.128 0.063 ent Load: 6 ice Type TIONS n System Board MC @15CD @30CD @75CD 'SftMC @1 1 0 C D PAYLESS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations Qty Amps 0.03 Standby: Total 0.03 Amps 0.030 0.064 0.098 0.175 0.233 Alarm: Total 0.030 0.064 0.098 0.350 '-"I I 0.0731 Amps HMC-C@115CD S PHMC-C@135CD andby Current Load: 0.0731 Amps For, 24 Hours = 1.754 Amp -hours -HMC-C@185CD Z C @15CD C @30CD 0.318 0.318 0.445 0.064 0.098 0.128 0.0015 ern Current Load: 0.191 Amps For 5 Minutes= 0.016 Amp -hours 0.03 Amps 0.67 Amfis 25% Derating= 2.213 Amp -hours t bdby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours AI i-rn Current Load: 0.67 Amps For 5 Minutes= 0.056 Amp -hours Total System Current Load: 2.213 Amp -hours B ttery Pair to be Used: 12VDC I Amp -hours 7AH 25% Derating= 0.970 Amp -hours PROJECT: Panel: Date: CIRCUIT: Total System Current Load: 0.970 Amp -hours eery Pair to be Used: 12VDC Amp -hours 7AH ALCULATION Notification Appliance WESTFIELD SOUTHCENTER MALL PAYLESS May 22, 2008 S1 Wire Resistance 1.62 RENT TOTAL= 640 .4 !!!-• 1! , 4 QTY 2. 0 0 0 0 Device Type SET -MC @15CD SET -MC @30CD SET -MC @75CD SET -MC @110CD SET-HMC-C@115CD SET-HMC-C@177CD SET -HMC @135CD SET -HMC @185CD Alarm Current Alarm Total 64 98 175 445 318 445 64 98 350 Wire Size VVirO,Lengt Voltage at EOL Circuit Total Total Wire Resistance ( R ) (WL*2 )*(R/ft) Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E ) (E= I * R) EOL Voltage (20.4 - E) 0.86 0.64 0.55 19.85 2 Z-MC@15CD 64 128 Z-MC@30CD 98 SET-MC-CW@110CD 233 DEVICES= 6 TOTAL rnAT:- 640 12 19.850496 6401 Notification Appliance tfrcut Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: PAYLESS Wire Resistance 2.58 Date: May. 22, 2008 R ENT TOTAL 7.2 CIRCUIT: SPEAKER CIRCUIT I I QTY Device Type 4 70.7V 1/8 Alarm Current Alarm Total Wire Size 1.81 0 7.2 Wire Voltage at EOL Circuit Total Total Wire Resistance ( R ( WL * 2 )* (R/ft) 2.92 Total Device Load, Amps (I) 0.01 (Total Cct Load) Voltage Drop ( E) 0.02 (E= I * R) EOL Voltage 20.38 0 DEVICES= 4 TOTAL m A= 7.2 VOLTAGE DRO 20.37900912 (20.4 - E) 7.2 t; Copyright 2006 by Guardian Security Systems, Inc. All Rights Reser 1743- IST AVE. SEATTLE, LO 10 0. (NJ CD LLI 5:- m _ . ..... LLI fY a . , , . .. DESCRIPTION SHOP DRAWINGS - DATE 0 ! : ''',. !;• <, ul ..- •••.., If) : C) ‹<<<< 0 DRAWN BY:" .AN DESIGNED BY: R.VEZZANI DATE: 5/1 2/08 BACKROUND • PLAN PROVIDED BY: FA -04 O 101.00 A MALL EGRESS PASSAGEWAY _COVE 105 I /I C E I L •42.-4. ADJACENT-7EN ADJACENT TENANT d' �,--,(t..31''G AFF 1 21'-5 3/8" =G E I L 12-D/ a" -P, FILE COPY THICKNESS of CONCRETE vaRiea • A y .. S/YX2•Y4'KIIK139.t • • ' j pA � A 3/V ROD CPKs CUT NS' ATR (PER FLAW Fla HANGER TOIL 110 1/2.At6,- Il2Xl O FORT' TO4'PIPE ALL LOCATIONS (UN,O) 3As' x 2-S/4' I1111 OLE ECU 3M' ATR x(OEE PU1U 31B'.RCD CPU PIPE HANGER Rt1G I. A L secoweviip EY PM #13 HANGER DETAIL FIG. 65 BEAM CLAMP milli �s11Efi�tiil�lL•1J FIG. 69 — RETAINING / STRAP JA LOCK < NUT IREQ' VIEW A -A �-- PIG. 100 ALL THREAD RDD �-- FIG. 200 L4AA14 ERA15LE RING FF10E 102 tV2ALi 112)(Zl-0 BOTTOM BEAM CLAMP, ROD, AND RING CE I L L2 D \ ( 1 �EIL.iI/-L I TOLCO FIG. 25 SURGE RESTRAINER TYPE 1 — FOR 1" AND 1-1/4" PIPE AND HANGER TYPE 2 — FOR 1-1/2" AND 2" PIPE AND HANGER TOLCO FIG. 25 IS DESIGNED TO BE USED ONLY WITH TOLCO BAND HANGERS FIG. 200 AND 2NFPA TO RESTRAIN THE UPWARD. MOVEMENT OF PIPE AS IT OCCURS DURING SPRINKLER HEAD ACTIVATION 'OR SEISMIC ACTIVITY FIGURE 25 SURGE RESTRAINER FOR STEEL OR CPVC. PLASTIC PIPE LINEMIE L ?4 THH E3(c EEDS 2'-4" Anrcr.0 CMSET E000KET IDRXT. ALL TI AD .ROD 1 1•10.5 REMOTE. A SPACE #2866 EA 15-95 SCS. .FT A System -- N.T.S. 3/3" XWIK BOLT Part COWt to It 2'-4" MAX. PER DINGLE OT144' M13E A.,OEML.T. ParAID BOTH SIDES I4 it MlioG (UP TO 2" PIE) LINE RESTRAINT DETAIL 5F4Ci WITH IN 6" OF A HNG R'EVY43'ON4LINE.. I 0" Victaulic #750 /Butterfly Valve n WILKINS I 0" 350 DAG n Vertical Backflow Preventer \I 0" Victaulic #750 Butterfly Valve I 0" Flange G1 @ 4. I '-2" AFF \FF@O'-0" 10" D.I. T8 Riser Assembly Detail t ADJACENT TENANT j---131 -6) A,F F CEI L. I I ORA.1-:F 3-0 CELL IZ C AFF 3-3 13-0 5-3 &14 -DAF GENER NOTES* RiCraCE Weld stamps must be aspected before pie is hung. ag not paint piping . prior to hydrostatic test approval. Wthout Commertte As Noted in Red. Per The Attached Letter 1 nese plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted stanaard s and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings after this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: `� ..„(11)By; / V w`" -- TAIL 1UKWILA FIRE DEPARTMENT Please call: 575-4407 and give this job No. and exact address for shut" ,.own or restoration approval, 1. RETAIL AREAS ARE DESIGNED IN ACCORDANCE WITH THE REQUIREMENTS OF N.F.P.A. 13 ORDINARY HAZARD GROUP 2 MAX SPACING 130 SQ. FT. 2. COSCO POINT OF CONNECTION IS AT EXIST BUILDING SHELL SYSTEM 4" MAIN AS SHOWN ON THESE PLANS. 3. ALL PAINTING OF FIRE SPRINKLER PIPING (IF REQ) TO BE DONE BY OTHERS . 4. ALL WIRING BY OTHER. 5. ALL MATERIAL IS NEW U.L. LISTED AND MEETS THE REQUIREMENTS OF THE TUKWILA FIRE FIRE DEPT. 6. OWNER IS RESPONSIBLE TO ASSURE THAT STRUCTURE AS IT IS SHOWN ON CONTRACT DRAWINGS CAN ADEQUATELY SUPPORT ALL FIRE SPRINKLER PIPING LOADS. NO AUXILLIARY DEVICES OR ATTACHMENTS SHALL BE PROVIDED BY COSCO TO SUPPLIMENT THE STRUCTURE TO ACCOMODATE FIRE SPRINKLER PIPING LOADS. 7. OWNER I5 RESPONSIBLE TO PROVIDE ADEQUATE HEAT TO MAINTAIN 40 DEG. F. MINIMUM AT ALL TIMES YEAR ROUND. 8: SPRINKLER HEAD LOCATIONS INDICATED ON THESE DRAWINGS ARE NOT INTENDED TO BE "CENTER OF TILE" HEAD PLACEMENT. 9. COSCO ASSUMES NO RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, FOR THE CONDITION, PERFORMANCE OR CURRENT CODE COMPLIANCE. OF THE EXISTING SYSTEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY COSCO. 10. OWNER IS RESPONSIBLE TO ARRANGE FOR THE PERIODIC INSPECTION, TESTING AND MAINTENANCE OF THESE FIRE SPRINKLER SYSTEMS IN ACCORDANCE WITH THE MINIMUM REQUIREMENTS OF N.F.P.A. 25-2002 BY QUALIFIED PERSONNEL COMMENCING AFTER WARRANTY PERIOD HAS EXPIRED. THE FIRM THAT DESIGNED AND INSTALLED THIS SYSTEM IS BEST QUALIFIED TO PROVIDE THE ONGOING. LONG TERM TESTING, MAINTENANCE AND SERVICING OF THIS SYSTEM(S). FIELD NOTES ****** I) THREADED PIPE FROM 1" THRU 2" SIZE TO BE SCH. 40 STD. WALL PIPE (IMPORT). 2) GROOVED END PIPE FROM 2 1/2" THRU 8" TO BE SC11.1 O (IMPORT). 3) ALL GROOVED COUPLING ARE TO BE "RIGID" TYPE U.N.O. (IMPORT). 4) ALL THREADED FITTINGS ARE 300# CLASS D.I. (IMPORT). FIELD/NOTES 1" s EXISTING PIPE NEW PIPE EXISTING HEAD NEW HEAD REG NEW HEAD CCDN PAU) - 2008 gi' w !!a Fire DUB REVISIONS NO. DESCRIPTION DATE BY SPRINKLER HEAD LEGEND : SYMBOL S/N ORIFICE NPT K -FACT. HEAD FINISH FINISH TEMP. QUAN. RELIABLE MOD G4A CONCEALED SSP 1/2' 1/2'. 5.6 BRASS WHT 165 1(0 REUABLE MOD G4A CONCEALED SSP co 1/2' 1/2'' 5.6 BRASS BLACK . 165 REUABLE MOD F1 FR REC SSP 1/2' 1/2' 5.6 WHT WHT 155 20 APPROVALS BY: TOTAL SPRINKLERS THIS SHEET GV . • 0 . 1 cosco •••••... ••0••••• Fire Protection FIRE PROTECTION AND LIFE SAFETY SPECIALISTS www.coscofire.com WASHINGTON OFFICE 15000 Woodinville -Redmond Rd NE License No: Woodinville, Washington 98072 COSCOFP110NM call (425) 686-8300 • fax (425) 827-4784 SAN DIEGO • LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEATILE • ANCHORAGE PROJECT :PAYLESS SHOES 2866 SOUTHCENTER MALL SPACE # 2165 TUKWILA, WA 98188. WELDON 913-226-8468 SCALE: 1/4=1'-0 CONTRACT BRUNDIGE FLOOR COVERINGS 10203 W 125TH TERRACE OVERLAND PARK, KS 66213 DRAINING ME FIRE SPRINKLER TENANT IMPROVEMENT a1E : 05/27/08 SCALE : 1 /4= 1'- 0" DRAWN BY : BRIAN SCHULZE I'5KS-7944 SHEET NO. D