HomeMy WebLinkAboutPP - 2877 SOUTHCENTER MALL - UNKNOWN TENANT - PERMITS AND PLANS2877 SOUTHCENTER MALL
ASSOCIATED PERMITS
08-F-271
SHEET INDEX
SHEET \UM3ER SHEET TITLE
2877
FIRE ALARM SYSTEM
TUKWILA, WASHINGTON
FA -01
SYSTEM I\FORMATIO \
FA -02
TYPICAL DETAILS - WIRI\G A\D
\IOU\TI\G
FA -03
FRE ALARM SYSTEM FLOOR PLA\
FA -04
SYSTEM CALC U LATI O \
S (cE\EAL),
RISER, SITE PLA
WIRE DESIGNATION SCHEDULE
WIRE SCHEDULE AND CONDUIT FILL CHAT
WIRE DESIGNATI❑N
SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE. COLOR CODE
D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET)
H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET)
P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET)
S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET)
A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET)
V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET)
I REMOTE INDICATI❑N LIGHT TWO #18 FPL/FPLR RED (JACKET)
X LOW LEVEL AUDIO TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET)
UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET)
UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET)
M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET)
B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET)
CONDUIT FILL CHART
NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA
TWO 600V #12 AWG THHN/THWN .244 0.0. .0467
• TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346
TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191
CONDUIT FILL
CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE
ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM
THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE.
CONDUIT SIZE MAXIMUM FILL
1/2" .12 SQUARE INCH
3/4" .21 SQUARE INCH
1" .34 SQUARE INCH
1-1/4" .60 SQUARE INCH
1-1/2" .82 SQUARE INCH
2" 1.34 SQUARE INCH
FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4.
SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END
GENERAL NOTES
FOR SIEMENS SYSTEM:
DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH
DEVICES ADDRESS.
1.. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS
DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1.
2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED.
3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL
BRANCHING IS PERMISSIBLE
4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL
ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION.
5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS,
STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT)
ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION.
6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT
AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1
7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY,
TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY,
AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION.
8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED
DRAWINGS FOR "AS BUILT" PURPOSES.
9, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT
SHEETS AND/OR INSTALLATION INSTRUCTIONS.
10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM ,SYSTEM PANELS
MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72,
SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER
SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT
DIRECT. SUPERVISION OF FIRE ALARM TECHNICIAN.
11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT
OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS.
12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE
ACTIVATION DEVICE.
13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET.
14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY
GENERATOR.
15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER
THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL.
EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION
FOR PROTECTION DURING CONSTRUCTION.
DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL
TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72
CHAPTER 7.
16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT
AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR
OTHER BACK BOXES OF DIFFERENT CIRCUITS.
17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND
AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO
FINAL EQUIPMENT TRIM.
18. ALL CABLES SHALL BE MARKED AS INDICATED .ON FIRE ALARM RISER WITH A
PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP.
19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE
OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES
AFTER COMPLETION OF THEIR INSTALLATION.
20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH
IT IS LOCATED.
21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT.
22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING
PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE
INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING
FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE
ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT
CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (LE.,
MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY.
23.
NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE
ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES.
THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF. THE
CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM
SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE
THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE
CABLE IS INSTALLED
QUANTITY
2
1
3
1
1
EX
SYMBOL DESCRIPTION
SYMBOLS LEGEND
MODEL
MANUFACTURER BACKBOX
MOUNTING HEIGHT
FACP
FIRE ALARM
EX CONTROL PANEL
XLS-V
SIEMENS PROVIDED
66" A.F.F.
TO TOP
FARA
FIRE ALARM
REMOTE ANNUNCIATOR
SDD-C
SIEMENS PROVIDED
66" A.F.F.
TO TOP
BPS
REMOTE BOOSTER
EX POWER SUPPLY
PAD -3
SIEMENS PROVIDED
66" A.F.F.
TO TOP
INTERFACE MODULE HTRI-R
WITH RELAY
SIEMENS 4S DEEP
VERIFY
IN FIELD
E
DUAL INPUT
INTERFACE MODULE
HTRI-D
SIEMENS 4S DEEP
VERIFY
IN FIELD
HCP
CONTROL POINT
MODULE
HCP
SIEMENS 4S DEEP
VERIFY
IN FIELD
HZM
REMOTE CONVENTIONAL HZM
ZONE MODULE
SIEMENS 4S DEEP
VERIFY
IN FIELD
-1Era LINEAR BEAM
SMOKE DETECTOR
PBA -1191 SIEMENS PROVIDED
VERIFY
IN FIELD
® SMOKE DETECTOR HFP-11 W/ SIEMENS
f� (ADDRESSABLE -PHOTO) DB -11 BASE
4S DEEP
W/ 1G RING
CEILING
lel
D
DUCT SMOKE
DETECTOR
AD2-P' W/ SIEMENS DUCT HOUSING VERIFY
TSM MODULE IN FIELD
HEAT DETECTOR
(ADDRESSABLE)
HFPT-11 W/ SIEMENS
DB -11 BASE
4S DEEP
W/ 1G RING
CEILING
FIRE ALARM
SPEAKER STROBE
(CEILING MOUNT)
FIRE ALARM
SPEAKER STROBE
(WALL MOUNT)
SET -MC -CW SIEMENS 45 DEEP BOX CEILING
W/ 1-1/2" EXT.
SET -MC -W SIEMENS
4S DEEP BOX 80" A.F.F.
W/ 1-1/2" EXT. TO BOTTOM
L C
FIRE ALARM
SPEAKER STROBE
(CEILING MOUNT)
SET-HM.0-CW SIEMENS
4S DEEP BOX CEILING
W/ 1-1/2" EXT.
IL]
FIRE ALARM
STROBE
(CEILING MOUNT)
ZR -MC. -CW SIEMENS
4S BOX
W/ 1G RING
CEILING
n
FIRE ALARM
STROBE
(WALL MOUNT)
ZR -MC -W SIEMENS 4S BOX
W/ 1G RING
80" A.F.F.
TO BOTTOM U.O.N.
YC
FIRE ALARM
SPEAKER
(CEILING MOUNT)
FIRE ALARM
SPEAKER
(WALL MOUNT)
SET -CW SIEMENS
4S DEEP BOX CEILING
W/ 1-1/2" EXT.
SET -W
SIEMENS 4S DEEP BOX
W/ 1-1/2" EXT.
80" A.F.F.
TO BOTTOM
B
WP
MR
FIRE ALARM
STROBE
(WEATHERPROOF)
MULTI -VOLTAGE
CONTROL RELAY
SET -S17 -WP SIEMENS
MT -SUR -BOX VERIFY
1/2" PIPE
IN FIELD
MR -201 /C
AIR PRODUCTS 4S BOX
VERIFY
IN FIELD
MAGNETIC
DOOR HOLDER
F.B.O.
F.B.O.
F.B.O.
VERIFY
IN FIELD
FA JB❑X
FIRE ALARM
TERMINAL CABINET
F.B.O.
`F.B.O.
F.B.O.
VERIFT
IN FIELD
JUNCTION BOX
F.B.D.
F
CC!PTED
A.F.F.
ABOVE FINISHED
FLOOR
N/A
N/A
Without Comments
VERI
IN FI LD
N/A ,
BLUE
AS BUILT
NOTES TO CAD
N/A
N/A
N/A
N/A
TUKWILA FIRE DEPARTN1 .i l J
Please call: 575.4402
end give this job
No. OS F2-1(
exact address for shut.
C.. n or restoration approval,
Copyright 2006 by Guardian Security Systems,
VOTICE
ed, signed, Tukwi
)artment Pre-test
FAX (206) 628-4990
TEL. (206) 622-651+5
RELEASE/REVISIONS
REV. BY:
z
As Natal In Rcd
F.B.O.
FURNISHED BY
OTHERS
El
N/A N/A El Per TheAAi��3hed Letter N/A
SHOP DRAWINGS
N/A
APPLICABLE NOTN/A
tpeae plans have been remed by The 1 ukwria FA
Meiention Bureau for con'f�r ance with current ciW/A
standards. Acceptance is subject to errors and
DATE
U.O.N.
UNLESS OTHERWISE
NOTED
N/A
omissions which do not authorize violations of adopted/
s r arcs and orainances. ffte responsibility for OW
adequacy of design rests totally with the designer.
comp
com let
let
Fire Dei
WP
WEATHERPROOF
DEVICE
N/A
A491iitions, deletions or revs to these drawings t,
1 t is ate will void this .accr1r ce and will require d"'
resubmittal of revised drawings for subsequent approval.
CertificatE
to the ]
commcncE
RED
AS
ADDBUILT OR CHANGE
N/A
` AO acceptance is subject ietd test and inspecti�riity
The TukwilaFire Prevention Bureau.
Testing
and De
GREEN
AS BUILT
REMOVE
N/A
Date 6 (ly A� 0700 N/A
Fain i ure
-
- �-Re-ir
terminali
BLUE
AS BUILT
NOTES TO CAD
N/A
N/A
N/A
N/A
TUKWILA FIRE DEPARTN1 .i l J
Please call: 575.4402
end give this job
No. OS F2-1(
exact address for shut.
C.. n or restoration approval,
Copyright 2006 by Guardian Security Systems,
VOTICE
ed, signed, Tukwi
)artment Pre-test
FAX (206) 628-4990
TEL. (206) 622-651+5
RELEASE/REVISIONS
REV. BY:
z
DESCRIPTION
SHOP DRAWINGS
DATE
1
2
aCCaC
CO
T
< C)
Z
w cc
w o
N. zz
N. 2w=
C\J 5 F.<
CC CI)
co Is -
D
H
a
must be presented
Inspector prior to
ment of Acceptant
of any Fire Alarm
tection Systems.
�f test will result
spection Fee and
on of the testing.
PAID
2008
Tukwila Fire
_.-412_676 3�
Inc. All Rights Reserved'
SCALE: 1/8"=1'
DRAWN BY:
I.ANDERSON
DESIGNED BY:
R.VEZZANI
DATE: 5/ 12/08
BACKROUND PLAN PROVIDED BY:
\,LOB NUMBER:
SHEET
FA -01
THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72.
THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX
DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED.
BEND OR OTHER
OBSTRUCTION
ANY DUCK OVER 3' WIDE, SAMPLE TUBE
MUST GO THRU THE DUCT AND BE CAPPED.
6-10 DUCT
EQUIVALENT
DIAMETERS
TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT
LABEL SCALE
COMBINE ALL SHIELDS AND
IS❑LATE FROM GROUNDING
TO NEXT ADDRESSABLE DEVICE
STOP IF LAST DEVICE
0
DUCT DETECTOR
LOCATION
FROM XLS CONTROL PANEL OR i+
PREVI❑US ADDRESSABLE DEVIL
END OF LINE DEVICE(3.6K 1/4W) S
0
GROUND -4)
0
M
SUPERVISED SWITCH
Ln
0
HTRI—R
OSTATUS LED
0
N.O.
t\
0
COM
J-
0
N.0
NOTE:
FOR ADDITIONAL SPECIFICATIONS
SEE PRODUCT DOCUMENTATION.
0
TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL
LABEI. SCALE (BACKGOUND MUSIC SHUTDOWN)
PREVI❑US ADDRESSABLE'.
DEVICE
TO NEXT ADDRESSABLE
DEVICE
+
NOTE 1:
VOLTAGE MAX. -
CURRENT MAX. -
CONT. RES. MAX. -
MAX, CABLE LENGTH -
C (LINE TO LINE) -
C (LINE TO SHIELD) -
MAX. LINE SIZE -
MIN. LINE SIZE -
MUSIC
OUTLET SAMPLING --
TUBE `•
INLET SAMPLIN
TUBE
AT LEAST
SIX DUCT
WIDTHS
FROM BEND
TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR
SCALE=NONE
14 -AC POWER SOURCE
COMBINE ALL SHIELDS AND
ISOLATE FROM GROUNDING
TO NEXT ADDRESSABLE DEVICE l(+)
STOP IF LAST DEVICE 1(+)
FROM XLS CONTROL PANEL OR
PREVIOUS ADDRESSABLE DEVICE (
RELAY CONTACTS
(4.OA @ 125VAC)
(4.0A @ 30VDC)
27 VDC
3.5 PIA DURING POLLING
10 OHMS
200 FT. (18 AWG)
0,02uF
0,04uF
14 AWG
18 AWG
NOTE 2:
ALL SUPERVISED SWITCHES MUST BE HELD CLOSED
AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE
DETECTI❑N.
O
J
1001
TB1
S 0 0 0 0
123456
HCP
TB2
00 01
654321
O
0
0
END OF LINE . 10
DEVICE S 7 J 0
(3.6K 1/4W)
SUPERVISED.___' /
SWITCH /
GROUND
NOTE:
M
HTRI—D
OSTATUS LED
Co
0
0
NOT USED
c0
0
FOR ADDITIONAL SPECIFICATIONS
SEE PRODUCT DOCUMENTATION.
TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL
LABEL sm (FIRE SUPPRESSION SYSTEM INTERFACE)
0
GND N AC
Tot
0
PAD -3
0
0
00
0
INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX
1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + -
0 0 0
0000g.�m�����
a
24K
n
+
TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP)
LABEL SCALE
NAC -4
cNAC-3
NAC -2
NAC -1
END OF
LINE DEVICE
3,6K 1/4W)
UPERVISED
SWITCH
FRONT VIEW
NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION.
NOT USED
REMOTE
DEVICE LOOP
NOT USED
REMOTE
DEVICE LOOP
0
0
0
0
FROM XLS CONTROL PANEL OR (+)>
PREVIOUS ADDRESSABLE DEVICE (—)>
FROM REMOTE
POWER SUPPLY
C'S' CABLE)
FROM, FACP
(V❑ICE CIRCUIT)
('V' CABLE>
470
OHMS
EOL
T
M-1
0
oa oo
'Po��z
'Pr oco
igifkrO`O
SMC
:3
0
CC
TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL
SCAIE NO*
C
(+) (—)
STROBE
SPEAKER
(+) ( )
0
(+)
STR❑BE—,
EARTH
GROUND
—>(+)TO NEXT DEVICE OR }
-- >(—) STOP IF LAST DEVICE
()
STROBE
SPEAKER
(+) (—)
SPEAKERISTROBE AND STROBE WIRING
LABEL SCALE
SPEAKER STROBE
OR STROBE' ONLY
80" A.F.F.
R
0
4S DEEP BOX
W/ 1-1 /2"
EXTENSION RING
(SPEAKER SIKOBE)
4S BOX•
(STROBE ONLY)
SPEAKER/STROBE
WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS
SCALE=NONE
TO NEXT
DEVICE ❑R
END OF LINE
TO NEXT
DEVICE OR
END OF LINE
NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION.
OPERt1IN TEMPERATURE:
+32' F (0' C) TO 100* F 38' C)
HUMIDITY: O-93333337. RELATIVE HUMIDITY,
NON -CONDENSING
HFP-11 SMOKE
DETECTOR
—> FROM PREVIOUS
ADDRESSABLE DEVICE
OR POWER SOURCE
tDATA IN ( )>
DATA IN (+) >
DEVICE IS USTED FOR AIR VOLOCITY
APPUCATIONS OF 300-4000 FT/MIN
WHEN USED IN CONJUNCTION WITH
DUCT HOUSINGS AD -11P OR AD-11XPR
- DB -11
STANDARD
SMOKE
DETECTOR
BASE
REAR VIEW
NFP -11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL
LABEL SCALE
TO NEXT DEVICE F—
> (—) DATA OUT
> (+) DATA OUT
CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID)
HARD LID
CEILING
HARD LID
SPEAKER SUPPORT T _- -------
BRIDGE
4' SQUARE DEEP BOX --
WITH 1-1/2' EXTENSION \
CEILING MOUNTED
SPEAKER/STROBE
CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING)
SCALE=NONE
JUNCTION BOX --
MOUNTED ON \
CEILING FLEX \
JUNCTIIIN BOX
MOUNTED AaAINST
CEILING SUPPORT
i1
/a O O ? 1 TO NEXT DEVICE
0 0
---CADDY BAR
SMOKE DETECTOR
SMOKE DETECTOR MOUNTING
SCALE=NONE
`--- SUSPENDED
ILLUMINATED CEILING
DO \OT INSTALL
ADDRESSABLE IN HATS\G
DEVICES „NAIL
PR-PROGR,4VVED WITH
DEVICES ADDRESS.
Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved
0
Z
cc
D
FAX (206) 628-4990
TEL. (206) 622-6545
RELEASE/REVISIONS
OD
w
z
DESCRIPTION
SHOP DRAWINGS
LU
L --
a
D
co
0
a}
0
0
0
00
00
<co
C)
W tO
1N-2 W =
co cc
S =0
CC t�
LL V J
co
N D
0
CL
�CALE: 1 /8"=1
DRAWN BY:
(.ANDERSON
DESIGNED BY:
R.VEZZANI
DATE: 5/ 12/08
BACKROUND PLAN PROVIDED BY:
\OB NUMBER:
SHEET
FA -02
0
I
1
2877 WESTFIELD SOUTHCENTER MALL
SCALE 1/8"4
FLAG N
OTE S:
FIELD LOCATE RELAY MODULE FOR
BACK GROUND MUSIC INTERFACE.
FIELD LOCATE SIEMENS DUCT
DETECTOR ON RETURN SIDE OF
ALL VAV UNITS,CSEE SIEMENS
INSTALLATION SUBMITTAL FOR
L❑CATION GUIDELINES AND FA -02)
DEVICES SUPPLIED BY GSS,
INSTALLED BY MECHANICAL
CONTRACTOR.
WIRED BY ELECTRICAL
CONTRACTOR,
SIEMENS HTRI—D ADDRESSABLE
INPUT WITH HU❑D VENILLAT❑R
FIRE SUPPRESI❑N SYSTEM, FIELD
LOCATE WITHIN 3 FEET OF
CONTRL PANEL.
FIELD LOCATE SIEMENS PAD -3
BOOSTER POWER SUPPLY FOR
STROBE POWER. AC POWER BY EC
FROM DEDICATED, LOCKED OUT
20A, 110 VAC BRANCH CIRCUIT.
DO NOT I I\STALL
ADDRESSABLE D \ T AT NG
DEVICES \TIL
DREPRQGRAW✓ ED WOTH
DEVICES ADD ESS.
Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved
rca
v
w
y
cc
D
c7
1743 IST AVE. SO., SEATTLE, WASHINGTON 98134
FAX (206) 628-4990
TEL. (206) 622-6545
RELEASE/REVISIONS
REV. BY: I
NVI
DESCRIPTION
SHOP DRAWINGS
DATE
co
0
L.
tn
)2
<-<«<
SCALE: 1 /8"=1
DRAWN BY:
LAN DERSON
DESIGNED BY:
R.VEZZANI
DATE: 5/ 12/08
BACKROUND PLAN PROVIDED BY:
1._OB NUMBER:
SHEET
\_ FA -03
NORTH
2871 WESTFIELD SOUTHCENTER MALL
SCALE 1132°4
115 C 115 C 75 15
EX
RISER DIAGRAM
SYSTEM CALCULATIONS
BATTERY SIZING CALCULATION
2877
2877
FACP ADD ONS
SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations
DESCRIPTION
PROJECT:
WESTFIELD SOUTHCENTER MALL
DATE
5/15/08
Panel:
2877
Wire Resistance 1.62
aaaaa
Date:
June 3, 2008
CURRENT TOTAL=
Current Load:
Standby:
Alarm:
S1
Current Load:
i
Standby:
Alarm:
QTY
Device Type
Alarm Current
Alarm Total
Wire Size
Wire Length
Voltage at EOL
Circuit Total
1
SET -MC @15CD
64
64
Device Type
Qty
Amps
Total
Amps
Total
0.86
Device Type
SET -MC @30CD
Qty
Amps
Total
Amps
Total
HFP-11
3
0.0022
0.0022
0.0023
Total Device Load, Amps (I)
0.65
0
SET -MC @11OCD
233
0
AD2-P
1
0.0635
0.0635
0.064
0.064
0
Main System Board
318
1
0.03
0.03
0.030
0.030
Voltage Drop (E)
HTR -R
0
2
0.009600
0.0096
0.021
0.042
SET -MC @15CD
1
0
SET -HMC @135CD
0.064
0.064
HTRI-D
0.001600
0.005
EOL Voltage
0.0035
0
SET -HMC @185CD
SET -MC @30CD
SET -MC @75CD
0
3
0.098
0.175
0.525
ICP -B6
Z-MC@15CD
64
64
0
SET -MC @110CD
98
0
0.233
0
SET-MC-CW@110CD
233
0
19.83933421 6531
SET HMC-C@115CD
SET HMC-C@135CD
SET HMC-C@185CD
ZR -MC @ 15C D
1
653
12
265
0.318
0.318
0.445
0.064
0.064
r Notification Appliance Circuit Detail
PROJECT:
WESTFIELD SOUTHCENTER MALL
0.0731
Amps
0.106
Amps
Panel:
2877
Standby Current Load:
0.0731
Amps
For 24 Hours =
1.754
Amp -hours
ZR -MC @30CD
CIRCUIT:
SPEAKER CIRCUIT
0.098
QTY
Device Type
Alarm Current
Alarm Total
HCP
Wire Length
Voltage at EOL
Circuit Total
0.0015
3
70.7V 1/8
Alarm Current Load:
5.4
0.106
Amps
For 5 Minutes=
0.009
Amp -hours
Total Wire Resistance (R)
2.92
0
0
0
0.03
Amps
0.683
Amps
(WL*2)*(R/ft)
0
0
0
Total Device Load, Amps (I)
0.01
0
0
0
25% Derating
2.204
Amp -hours
Standby Current Load:
0.03
Amps
For 24 Hours =
0.720
Amp -hours
Voltage Drop ( E)
0.02
0
0
0
(E=I*R)
0
-
0
0
EOL Voltage
20.38
0
Alarm Current Load:
0
0.683
Amps
For 5 Minutes=
0.057
Amp -hours
(20.4 - E)
Total System Current Load:
2.204
Amp -hours
0
0
0
DEVICES=
3
TOTAL mA=
5.4
14
25% Derating=
0.972
Amp -hours
Battery Pair to be Used:
12VDC
Amp -hours
7AH
Total System Current Load:
0.972
Amp -hours
Battery Pair to be Used:
12VDC
1
Amp -hours
7AH
BATTERY SIZING CALCULATION
VOLTAGE DROP CALCULATION
Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved
1743 IST
FAX (206) 628-4990
TEL. (206) 622-6545
RELEASE/REVISIONS
REV. BY:
z
Notification Appliance Circuit Detail
DESCRIPTION
PROJECT:
WESTFIELD SOUTHCENTER MALL
DATE
5/15/08
Panel:
2877
Wire Resistance 1.62
aaaaa
Date:
June 3, 2008
CURRENT TOTAL=
653
CIRCUIT:
S1
QTY
Device Type
Alarm Current
Alarm Total
Wire Size
Wire Length
Voltage at EOL
Circuit Total
1
SET -MC @15CD
64
64
Total Wire Resistance (R)
0.86
0
SET -MC @30CD
98
0
(WL * 2 ) * (R/ft)
3
SET -MC @75CD
175
525
Total Device Load, Amps (I)
0.65
0
SET -MC @11OCD
233
0
(Total Cct Load)
0
SET-HMC-C@115CD
318
0
Voltage Drop (E)
0.56
0
SET-HMC-C@177CD
445
0
(E= I * R)
0
SET -HMC @135CD
318
0
EOL Voltage
19.84
0
SET -HMC @185CD
445
0
(20.4 - E)
1
Z-MC@15CD
64
64
0
Z-MC@30CD
98
0
0
SET-MC-CW@110CD
233
0
19.83933421 6531
DEVICES=
5
TOTAL mA=
653
12
265
r Notification Appliance Circuit Detail
PROJECT:
WESTFIELD SOUTHCENTER MALL
Panel:
2877
Wire Resistance 2.58
Date:
May 29, 2008
CURRENT TOTAL=
5.4
CIRCUIT:
SPEAKER CIRCUIT
QTY
Device Type
Alarm Current
Alarm Total
Wire Size
Wire Length
Voltage at EOL
Circuit Total
3
70.7V 1/8
1.8
5.4
Total Wire Resistance (R)
2.92
0
0
0
(WL*2)*(R/ft)
0
0
0
Total Device Load, Amps (I)
0.01
0
0
0
(Total Cct Load)
0
0
0
Voltage Drop ( E)
0.02
0
0
0
(E=I*R)
0
-
0
0
EOL Voltage
20.38
0
0
0
(20.4 - E)
0
0
0
0
0
0
DEVICES=
3
TOTAL mA=
5.4
14
565
20.384256841 5.41
VOLTAGE DROP CALCULATION
Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved
1743 IST
FAX (206) 628-4990
TEL. (206) 622-6545
RELEASE/REVISIONS
REV. BY:
z
DESCRIPTION
SHOP DRAWINGS
DATE
5/15/08
aaaaa
co
co
T
<0)
2 2Z
pE 0
FW -0
Imo- ZZ
CO Ir
=Q
CCC
co
N D
F-
CL
LU
cr
w
0)
EE
0
J.
w
cn
>-
` \ ()
SCALE: 1 /8"=1'
DRAWN BY:
I.ANDERSON
DESIGNED BY:
R.VEZZANI
DATE: 5/ 12/08
BACKROUND PLAN PROVIDED BY:
\0B NUMBER:
SHEET
-%