HomeMy WebLinkAboutPP - 2877 SOUTHCENTER MALL - UNKNOWN TENANT - PERMITS AND PLANS2877 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-271 SHEET INDEX SHEET \UM3ER SHEET TITLE 2877 FIRE ALARM SYSTEM TUKWILA, WASHINGTON FA -01 SYSTEM I\FORMATIO \ FA -02 TYPICAL DETAILS - WIRI\G A\D \IOU\TI\G FA -03 FRE ALARM SYSTEM FLOOR PLA\ FA -04 SYSTEM CALC U LATI O \ S (cE\EAL), RISER, SITE PLA WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHAT WIRE DESIGNATI❑N SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE. COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATI❑N LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDIO TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.0. .0467 • TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END GENERAL NOTES FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1.. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM ,SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT. SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED .ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (LE., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF. THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 1 3 1 1 EX SYMBOL DESCRIPTION SYMBOLS LEGEND MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD E DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD -1Era LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD ® SMOKE DETECTOR HFP-11 W/ SIEMENS f� (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING lel D DUCT SMOKE DETECTOR AD2-P' W/ SIEMENS DUCT HOUSING VERIFY TSM MODULE IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -CW SIEMENS 45 DEEP BOX CEILING W/ 1-1/2" EXT. SET -MC -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM L C FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET-HM.0-CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. IL] FIRE ALARM STROBE (CEILING MOUNT) ZR -MC. -CW SIEMENS 4S BOX W/ 1G RING CEILING n FIRE ALARM STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. YC FIRE ALARM SPEAKER (CEILING MOUNT) FIRE ALARM SPEAKER (WALL MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM B WP MR FIRE ALARM STROBE (WEATHERPROOF) MULTI -VOLTAGE CONTROL RELAY SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR -201 /C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. `F.B.O. F.B.O. VERIFT IN FIELD JUNCTION BOX F.B.D. F CC!PTED A.F.F. ABOVE FINISHED FLOOR N/A N/A Without Comments VERI IN FI LD N/A , BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A TUKWILA FIRE DEPARTN1 .i l J Please call: 575.4402 end give this job No. OS F2-1( exact address for shut. C.. n or restoration approval, Copyright 2006 by Guardian Security Systems, VOTICE ed, signed, Tukwi )artment Pre-test FAX (206) 628-4990 TEL. (206) 622-651+5 RELEASE/REVISIONS REV. BY: z As Natal In Rcd F.B.O. FURNISHED BY OTHERS El N/A N/A El Per TheAAi��3hed Letter N/A SHOP DRAWINGS N/A APPLICABLE NOTN/A tpeae plans have been remed by The 1 ukwria FA Meiention Bureau for con'f�r ance with current ciW/A standards. Acceptance is subject to errors and DATE U.O.N. UNLESS OTHERWISE NOTED N/A omissions which do not authorize violations of adopted/ s r arcs and orainances. ffte responsibility for OW adequacy of design rests totally with the designer. comp com let let Fire Dei WP WEATHERPROOF DEVICE N/A A491iitions, deletions or revs to these drawings t, 1 t is ate will void this .accr1r ce and will require d"' resubmittal of revised drawings for subsequent approval. CertificatE to the ] commcncE RED AS ADDBUILT OR CHANGE N/A ` AO acceptance is subject ietd test and inspecti�riity The TukwilaFire Prevention Bureau. Testing and De GREEN AS BUILT REMOVE N/A Date 6 (ly A� 0700 N/A Fain i ure - - �-Re-ir terminali BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A TUKWILA FIRE DEPARTN1 .i l J Please call: 575.4402 end give this job No. OS F2-1( exact address for shut. C.. n or restoration approval, Copyright 2006 by Guardian Security Systems, VOTICE ed, signed, Tukwi )artment Pre-test FAX (206) 628-4990 TEL. (206) 622-651+5 RELEASE/REVISIONS REV. BY: z DESCRIPTION SHOP DRAWINGS DATE 1 2 aCCaC CO T < C) Z w cc w o N. zz N. 2w= C\J 5 F.< CC CI) co Is - D H a must be presented Inspector prior to ment of Acceptant of any Fire Alarm tection Systems. �f test will result spection Fee and on of the testing. PAID 2008 Tukwila Fire _.-412_676 3� Inc. All Rights Reserved' SCALE: 1/8"=1' DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: \,LOB NUMBER: SHEET FA -01 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND IS❑LATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE 0 DUCT DETECTOR LOCATION FROM XLS CONTROL PANEL OR i+ PREVI❑US ADDRESSABLE DEVIL END OF LINE DEVICE(3.6K 1/4W) S 0 GROUND -4) 0 M SUPERVISED SWITCH Ln 0 HTRI—R OSTATUS LED 0 N.O. t\ 0 COM J- 0 N.0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEI. SCALE (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE'. DEVICE TO NEXT ADDRESSABLE DEVICE + NOTE 1: VOLTAGE MAX. - CURRENT MAX. - CONT. RES. MAX. - MAX, CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN. LINE SIZE - MUSIC OUTLET SAMPLING -- TUBE `• INLET SAMPLIN TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE=NONE 14 -AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE l(+) STOP IF LAST DEVICE 1(+) FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVICE ( RELAY CONTACTS (4.OA @ 125VAC) (4.0A @ 30VDC) 27 VDC 3.5 PIA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0,02uF 0,04uF 14 AWG 18 AWG NOTE 2: ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTI❑N. O J 1001 TB1 S 0 0 0 0 123456 HCP TB2 00 01 654321 O 0 0 END OF LINE . 10 DEVICE S 7 J 0 (3.6K 1/4W) SUPERVISED.___' / SWITCH / GROUND NOTE: M HTRI—D OSTATUS LED Co 0 0 NOT USED c0 0 FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL sm (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC Tot 0 PAD -3 0 0 00 0 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 0 0 0 0000g.�m����� a 24K n + TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE NAC -4 cNAC-3 NAC -2 NAC -1 END OF LINE DEVICE 3,6K 1/4W) UPERVISED SWITCH FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE DEVICE LOOP 0 0 0 0 FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (—)> FROM REMOTE POWER SUPPLY C'S' CABLE) FROM, FACP (V❑ICE CIRCUIT) ('V' CABLE> 470 OHMS EOL T M-1 0 oa oo 'Po��z 'Pr oco igifkrO`O SMC :3 0 CC TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCAIE NO* C (+) (—) STROBE SPEAKER (+) ( ) 0 (+) STR❑BE—, EARTH GROUND —>(+)TO NEXT DEVICE OR } -- >(—) STOP IF LAST DEVICE () STROBE SPEAKER (+) (—) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE' ONLY 80" A.F.F. R 0 4S DEEP BOX W/ 1-1 /2" EXTENSION RING (SPEAKER SIKOBE) 4S BOX• (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE=NONE TO NEXT DEVICE ❑R END OF LINE TO NEXT DEVICE OR END OF LINE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERt1IN TEMPERATURE: +32' F (0' C) TO 100* F 38' C) HUMIDITY: O-93333337. RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR —> FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE tDATA IN ( )> DATA IN (+) > DEVICE IS USTED FOR AIR VOLOCITY APPUCATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR - DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW NFP -11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT DEVICE F— > (—) DATA OUT > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID CEILING HARD LID SPEAKER SUPPORT T _- ------- BRIDGE 4' SQUARE DEEP BOX -- WITH 1-1/2' EXTENSION \ CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE=NONE JUNCTION BOX -- MOUNTED ON \ CEILING FLEX \ JUNCTIIIN BOX MOUNTED AaAINST CEILING SUPPORT i1 /a O O ? 1 TO NEXT DEVICE 0 0 ---CADDY BAR SMOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE=NONE `--- SUSPENDED ILLUMINATED CEILING DO \OT INSTALL ADDRESSABLE IN HATS\G DEVICES „NAIL PR-PROGR,4VVED WITH DEVICES ADDRESS. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 0 Z cc D FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS OD w z DESCRIPTION SHOP DRAWINGS LU L -- a D co 0 a} 0 0 0 00 00 <co C) W tO 1N-2 W = co cc S =0 CC t� LL V J co N D 0 CL �CALE: 1 /8"=1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: \OB NUMBER: SHEET FA -02 0 I 1 2877 WESTFIELD SOUTHCENTER MALL SCALE 1/8"4 FLAG N OTE S: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,CSEE SIEMENS INSTALLATION SUBMITTAL FOR L❑CATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR, SIEMENS HTRI—D ADDRESSABLE INPUT WITH HU❑D VENILLAT❑R FIRE SUPPRESI❑N SYSTEM, FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NOT I I\STALL ADDRESSABLE D \ T AT NG DEVICES \TIL DREPRQGRAW✓ ED WOTH DEVICES ADD ESS. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved rca v w y cc D c7 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: I NVI DESCRIPTION SHOP DRAWINGS DATE co 0 L. tn )2 <-<«< SCALE: 1 /8"=1 DRAWN BY: LAN DERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: 1._OB NUMBER: SHEET \_ FA -03 NORTH 2871 WESTFIELD SOUTHCENTER MALL SCALE 1132°4 115 C 115 C 75 15 EX RISER DIAGRAM SYSTEM CALCULATIONS BATTERY SIZING CALCULATION 2877 2877 FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL DATE 5/15/08 Panel: 2877 Wire Resistance 1.62 aaaaa Date: June 3, 2008 CURRENT TOTAL= Current Load: Standby: Alarm: S1 Current Load: i Standby: Alarm: QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 1 SET -MC @15CD 64 64 Device Type Qty Amps Total Amps Total 0.86 Device Type SET -MC @30CD Qty Amps Total Amps Total HFP-11 3 0.0022 0.0022 0.0023 Total Device Load, Amps (I) 0.65 0 SET -MC @11OCD 233 0 AD2-P 1 0.0635 0.0635 0.064 0.064 0 Main System Board 318 1 0.03 0.03 0.030 0.030 Voltage Drop (E) HTR -R 0 2 0.009600 0.0096 0.021 0.042 SET -MC @15CD 1 0 SET -HMC @135CD 0.064 0.064 HTRI-D 0.001600 0.005 EOL Voltage 0.0035 0 SET -HMC @185CD SET -MC @30CD SET -MC @75CD 0 3 0.098 0.175 0.525 ICP -B6 Z-MC@15CD 64 64 0 SET -MC @110CD 98 0 0.233 0 SET-MC-CW@110CD 233 0 19.83933421 6531 SET HMC-C@115CD SET HMC-C@135CD SET HMC-C@185CD ZR -MC @ 15C D 1 653 12 265 0.318 0.318 0.445 0.064 0.064 r Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL 0.0731 Amps 0.106 Amps Panel: 2877 Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours ZR -MC @30CD CIRCUIT: SPEAKER CIRCUIT 0.098 QTY Device Type Alarm Current Alarm Total HCP Wire Length Voltage at EOL Circuit Total 0.0015 3 70.7V 1/8 Alarm Current Load: 5.4 0.106 Amps For 5 Minutes= 0.009 Amp -hours Total Wire Resistance (R) 2.92 0 0 0 0.03 Amps 0.683 Amps (WL*2)*(R/ft) 0 0 0 Total Device Load, Amps (I) 0.01 0 0 0 25% Derating 2.204 Amp -hours Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours Voltage Drop ( E) 0.02 0 0 0 (E=I*R) 0 - 0 0 EOL Voltage 20.38 0 Alarm Current Load: 0 0.683 Amps For 5 Minutes= 0.057 Amp -hours (20.4 - E) Total System Current Load: 2.204 Amp -hours 0 0 0 DEVICES= 3 TOTAL mA= 5.4 14 25% Derating= 0.972 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.972 Amp -hours Battery Pair to be Used: 12VDC 1 Amp -hours 7AH BATTERY SIZING CALCULATION VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z Notification Appliance Circuit Detail DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL DATE 5/15/08 Panel: 2877 Wire Resistance 1.62 aaaaa Date: June 3, 2008 CURRENT TOTAL= 653 CIRCUIT: S1 QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 1 SET -MC @15CD 64 64 Total Wire Resistance (R) 0.86 0 SET -MC @30CD 98 0 (WL * 2 ) * (R/ft) 3 SET -MC @75CD 175 525 Total Device Load, Amps (I) 0.65 0 SET -MC @11OCD 233 0 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 Voltage Drop (E) 0.56 0 SET-HMC-C@177CD 445 0 (E= I * R) 0 SET -HMC @135CD 318 0 EOL Voltage 19.84 0 SET -HMC @185CD 445 0 (20.4 - E) 1 Z-MC@15CD 64 64 0 Z-MC@30CD 98 0 0 SET-MC-CW@110CD 233 0 19.83933421 6531 DEVICES= 5 TOTAL mA= 653 12 265 r Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: 2877 Wire Resistance 2.58 Date: May 29, 2008 CURRENT TOTAL= 5.4 CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 3 70.7V 1/8 1.8 5.4 Total Wire Resistance (R) 2.92 0 0 0 (WL*2)*(R/ft) 0 0 0 Total Device Load, Amps (I) 0.01 0 0 0 (Total Cct Load) 0 0 0 Voltage Drop ( E) 0.02 0 0 0 (E=I*R) 0 - 0 0 EOL Voltage 20.38 0 0 0 (20.4 - E) 0 0 0 0 0 0 DEVICES= 3 TOTAL mA= 5.4 14 565 20.384256841 5.41 VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z DESCRIPTION SHOP DRAWINGS DATE 5/15/08 aaaaa co co T <0) 2 2Z pE 0 FW -0 Imo- ZZ CO Ir =Q CCC co N D F- CL LU cr w 0) EE 0 J. w cn >- ` \ () SCALE: 1 /8"=1' DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: \0B NUMBER: SHEET -% FA -04