Loading...
HomeMy WebLinkAboutPP - 2897 SOUTHCENTER MALL - OKI DOKI - PERMITS AND PLANS2897 SOUTHCENTER MALL ASSOCIATED PERMITS 09-F-120 08-F-270 08-S-313 08-S-310 0 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Permit No.: Date: Reviewer: Vanilla Shell 2897 Southcenter Mall 08-S310 June 11, 2008 Steve Kohler Fire Inspector/Plan Review (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods Tess than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1 "-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ` of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. ilHydraulic I + Summary Job Number: KS0407 Report Description: Ordinary Group II Job Job Number Design Engineer KS0407 Adam Kanter Job Name . State Certification/License Number Vanilla Shells 2897 ! WESTESF136QF Address 1 , AHJ Southcenter Mall City of Tukwila Address 2 Job Site 1 Southcenter Mall City State Zip Code Drawing Name Tukwila Wa 98188 j FP-1-2897.cad System i Remote Area(s) Most Demanding Sprinkler Data : Occupancy 5.6 K -Factor 26.00 at 21.556 : Ordinary Group II Hose Allowance At Source Density Area of Application 250.00 0.20gpm/ft2 , 945.00ft2 (Actual 948.10ft2) Additional Hose Supplies Number Of Sprinklers Calculated Coverage Per Sprinkler Node Flow(gpm) 10 130.00ft2 AutoPeak Results: Pressure For Remote Area(s) Adjacent To Most Remote Area Total Hose Streams 250.00 ( ( �� ` ,�� System Flow Demand Total Water Required (Including Hose Allowance) ;�, r e 292.10 542.10„ ;1 Maximum Pressure Unbalance In Loops �� `V br fi-I� = `� 0.000 Maximum Velocity Above Ground,111r 26.35 between nodes 123 and 49 Maximum Velocity Under Ground ,�tO 1.10 between nodes 1 and 324 Volume capacity of Wet Pipes Volume capacity of Dry Pipes 2750.71 gal 1.35ft' Supplies 1 Hose Flow Static 1 Residual @ Flow j Available @ Total Demand Required Safety Margin Node (gpm) (psi) (psi) (gpm) (psi) (gpm) (psi) i (psi) 1 250.00 140.000 20.000 10900.00 1 139.534 542.10 98.969 40.566 Contractor Contractor Number Contact Name 1 Contact Title KS0407 ' Adam Kantner 1 Project Manager Contractor Name Phone Extension Western States Fire Protection ; 425.881.0100 1 Address 1 FAX 7102 180th Ave Ne, Suite A-105 485.736.9032 Address 2 ' E-mail 1 City State i Zip Code Web -Site Redmond WA 1 98052 kA, ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 06/05/2008 8:31:06AM Page 1 .1 Summary Of Outflowing Devices `Job Number: KS0407 Report Description: Ordinary Group II Device Actual Flow (gpm) Minimum Flow (gpm) K -Factor (K) Pressure (psi) b Sprinkler 101 26.00 26.00 5.6 21.556 Sprinkler 102 26.26 26.00 5.6 21.997 Sprinkler 107 30.78 26.00 5.6 30.211 Sprinkler 103 26.80 26.00 5.6 22.908 Sprinkler 106 30.70 26.00 5.6 30.047 Sprinkler 104 27.68 26.00 5.6 24.436 Skier 108 31.19 26.00 5.6 31.015 Sprinkler 105 29.15 26.00 5.6 27.101 Sprinkler 110 32.21 26.00 5.6 33.084 Sprinkler 109 ; 31.32 26.00 5.6 31.278 c Most Demanding Sprinkler Data (� ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 06/05/2008 8:31:14AM Page 2 Node Analysis Job Number: KS0407 Report Description: Ordinary Group II Node Elevation(Foot) Fittings Pressure(psi) Discharge(gpm) 22 17-6 E(2-0) 28.439 24 17-6 PO(5-0) 28.529 26 17-6 E(2-0) 38.277 31 17-6 PO(5-0) 29.102 33 17-6 ; PO(5-0) 38.492 37 17-6 PO(5-0) 31.156 39 17-6 PO(5-0) 39.782) 43 17-6 ; PO(5-0) 34.736 45 17-6 PO(5-0) 42.537: 49 17-6 PO(5-0). 40.332 123 17-6 2P0(8-0) 61.428 ; 149 17-6 2P0(8-0)61.321 II ' 236 -16-1 . P0(26-4) 91.796 324 -14-1% • BFP(-4.500) 95.518 358 -16-1 . LtE(16-0) 91.832 ' 101 15-01,4 Spr(-21.556) 21.556 26.00 102 15-0% , Spr(-21.997) 21.997 26.26 107 15-0 , Spr(-30.211) 30.211 , 30.78 103 12-0% , Spr(-22.908) 22.908 26.80 106 1 12-0 Spr(-30.047)30.047 30.70 . 104 12-0% ! Spr(-24.436) 24.436 , 27.68 , 108 12-0 Spr(-31.015) 31.015 31.19 105 12-0% j Spr(-27.101) 27.101 29.15 110 12-0 ; Spr(-33.084) 33.084 ' 32.21 109 12-0% Sp (-31.278) 31.278 31.32 1 . -22-0 S 98.969 292.10 , • �t ©M.E.P.CAD, Inc. ,fi AutoSPRINK®VR5 v5.2.6 06/05/2008 8:31:16AM Page 3 i Hydraulic AnalysisIIJob Number: KSO407 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K -Factor Pt Pn Fittings Eq. Length Summary Upstream Total Length ew Route 1 DR 1.049 Q=26.00 9.65 C=120 0.211435 29-7% Pf 7.958 101 15-0' q=26.00 K=5.6 21.556 Spr(-21.556) 8-0 Pe -1.075 22 17-6 28.439 4E(2-0) 37-7% Pv BL 1.610 Q=26.00 4.1.0 C=120 0.026249 3-5, Pf 0.090 22 17-6 28.439 ; Pe 24 17-6 28.529 3-5 Pv BL 1.610 Q=52.26 8.24 0=120 0.095519 6-0 Pf 0.573 24 17-6 28.529 Pe 0.000 31 17-6 29.102 6-0 Pv BL 1.610 Q=79.07 12.46 C=120 0.205450 10-0 Pf 2.054 31 17-6 29.102 1 Pe 37 17-6 31.156 10-0 Pv BL 1.610 Q=106.75 16.82 C=120 0.358004 10-0 Pf 3.580 37 17-6 31.156 ' Pe 43 17-6 34.736 10-0' Pv BL 1.610 Q=135.90 21.42 C=120 0.559605 10-0, Pf 5.596 43 17-6 34.736 Pe 49 17-6 40.332 10-0• Pv BL 1.610 Q=167.22 26.35 0=120 0.821300 17-8 Pf 21.096 49 17-6 40.332 8-0 Pe 123 17-6 61.428 PO(8-0) 25-8', Pv CM 4.260 Q=292.10 6.57 C=120 0_.020.1.67 457-7 Pf 15.808 123 17-6 61.428 177-6 Pe 14.559 236 -16-1 91.796 2cplg(-1.500), 2P0(26-4), E(13-2), 635-1' Pv 6fE(8-11%), BV(15-91A), 2Ee2(5-3), CV(28-11'%), GV(2-7%) FM 8.329 Q=292.10 1.72 C=120 0.000770 14-5% Pf 0.036 236 -16-1 91.796 32-0 Pe 0.000 358 -16-1 91.832 fE(16-0), LtE(16-0) 46-5% Pv FM 10.420 Q=292.10 1.10 0=120 0.000259 28-2'% Pf 4.529 _ _ 358 -16-1 91.832 83-0 Pe -0.842 324 -14-1% 95.518 4LtE(16-0), BV(19-0), BFP(-4.500) 111-2'/z Pv UG 10.400 Q=292.10 1.10 C=140 0.000196 110-2j Pf 0.044 324 -14-1% 95.518 111-7 Pe 3.407 1 -22-0 98.969 E(35-1), 3LtE(25-6), S 221-9% Pv lap Route 2 DR 1.049 0=26.26 9.75 0=120 0.215429 26-3'% Pf 7.607 102 15-0% q=26.26 K=5.6 21.997 Spr(-21.997) 9-0' Pe -1.075 24 17-6 28.529 2E(2-0), P0(5-0) ! 35-3% Pv a. Route 3 DR 1.049 Q=26.80 9.95 C=120 0.223675 29-3'% Pf 8.569 103 12-0'/2 q=26.80 K=5.6 22.908 Spr(-22.908) 9-0 Pe -2.375 31 17-6 29.102 2E(2-0), P0(5-0) 38-3Y Pv Route 4 DR 1.049 Q=27.68 10.28 C=120 0.237435 29-3'/z' Pf 9.096 104 12-0'/2 q=27.68 K=5.6 24.436 Spr(-24.436) 9-0 Pe -2.375 37 17-6 31.156 2E(2-0), PO(5-0) 38-3'/z Pv v Route 5 DR 1.049 Q=29.15 10.82 0=120 0.261301 29-3% Pf 10.010 105 12-0'/ q=29.15 K=5.6 27.101 Spr(-27.101) 9-0 Pe -2.375 43 17-6 34.736 2E(2-0), PO(5-0) 38-3% Pv Q Route 6 DR 1.049 0=30.70 11.40 C=120 0.287472 28-8 Pf 10.829 106 12-0 q=30.70 K=5.6 30.047 Spr(-30.047) 9-0, Pe -2.384 33 17-6 38.492 2E(2-0), P0(5-0) 37-8 Pv BL 1.610 0=61.48 9.69 C=120 0.128981 10-0 Pf 1.290 33 17-6 38.492 , Pe 39 17-6 39.782 10-0 Pv BL 1.610 0=92.66 14.60 C=120 0.275546 10-0 Pf 2.755 39 17-6 39.782 I Pe 45 17-6 42.537 10-0' Pv BL 1.610 Q=124.87 19.68 C=120 0.478504 31-3 Pf 18.783 45 17-6 42.537 8-0 Pe 149 17-6 61.321 P0(8-0) 39-3 Pv CM 4.260 0=124.87 2.81 0=120 0.004187 12-1'h Pf 0.108 149 17-6 61.32113-7 Pe 123 17-6 61.428 2fE(6-9%) 25-9, Pv Route 7 DR 1.049 0=30.78 11.43 0=120 0.288917 25-8 Pf 9.150 107 15-0 q=30.78 K=5.6 30.211 Spr(-30.211) 6-0 Pe -1.084 26 17-6 38.277 3E(2-0) 31-8 Pv ©M.E.P.CAD, Inc. AutoSPRINK®VR5 v5.2.6 06/05/2008 8:31:18AM Page 4 11 Hydraulic Analysis 1 Job Number: KS0407 Report Description: Ordinary Group II • Pipe Type Diameter Flow Velocy HWC Friction Loss Length Pressure Downstream Elevation Discharge K -Factor Pt Pn Fittings Eq. Length Summary Upstream Total Length BL 1.610 Q=30.78 4.85 C=120 0.035868 6-0 Pf 0.215 26 17-6 38.277 Pe 33 17-6 38.492 6-0 Pv Route 8 DR 1.049 Q=31.19 11.58 C=120 0.296025 28-8 Pf 11.151 108 12-0 q=31.19 K=5.6 31.015 Spr(-31.015) 9-0 Pe -2.384 39 17-6 39.782 2E(2-0), PO(5-0) 37-8; Pv o Route 9 DR 1.049 Q=31.32 11.63 C=120 0.298347 29-3'% Pf 11.430 109 12-0% q=31.32 K=5.6 31.278 Spr(-31.278) 9-0 Pe -2.375 49 17-6 40.332 2E(2-0), PO(5-0) 38-3% Pv ob Route 10 DR 1.049 Q=32.21 11.96 C=120 0.314247 28-8 Pf 11.838 110 12-0 q=32.21 K=5.6 33.084 Spr(-33.084) 9-Q Pe -2.384 45 17-6 42.537 2E(2-0), PO(5-0) 37-8' Pv Equivalent Pipe Lengths of Valves and Fittings (C=120 only) ` C Value Multiplier / Actual Inside Diameter 1487 = Factor Value Of C 100 130 140 150 Schedule 40 Steel Pipe Inside Diameter I Multiplying Factor 0.713 1.16 1.33 1.51 Pipe Type Legend Units Legend Fittings Legend AO Arm -Over BL Branch Line CM Cross Main DN Drain DR Drop DY Dynamic FM Feed Main FR Feed Riser MS Miscellaneous OR Outrigger RN Riser Nipple SP Sprig ST Stand Pipe UG UndergroundPv - Diameter Inch Elevation Foot Flow gpm Discharge gpm Velocity fps Pressure psi Length Foot Friction Loss psi/Foot HWC Hazen -Williams Constant Pt Total pressure at a point in a pipe Pn Normal pressure at a point in a pipe Pf Pressure loss due to friction between points Pe Pressure due to elevation difference between indicated points Velocity pressure at a point in a pipe ALV Alarm Valve AngV Angle Valve b Bushing BaIV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Turn 90° cplg Coupling Cr Cross Run CV Check Valve DeiV Deluge Valve DPV Dry Pipe Valve E 90° Elbow EE 45° Elbow -, Eel 11'W Elbow Ee2 22W Elbow f Flow Device FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow flg Flange FN Floating Node fT FireLock(TM) Tee g Gauge GIoV Globe Valve GV Gate Valve Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PrV Pressure Relief Valve PRV Pressure Reducing Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap ©M.E.P.CAD, Inc. tAutoSPRINK® VR5 v5.2.6 06/05/2008 8:31:18AM Page 5 Hydraulic Graph 1 Job Number: KS0407 Report Description: Ordinary Group II Supply at Node 1 150 Static Pressure 140.000 135 120 105 _,542.10 292.10 with hose @ 98.969 streams 90 .N - a _ ai- 75 _ N— co _ 2 _ o_ - 60 -System demand curve 45 30 -9 10900.00 @ 20.000. 15 X011 111111111 1'mull 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 I I I _1_I 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 I.1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 01002200 3300 44005500 6600 7700 8800 9900 11000 Water flow, gpm Hydraulic Graph Supply at Node 1 Static Pressure 140.000 Residual Pressure 10900.00 @ 20.000 Available PressureTime of Test 139.534 @ 542.10 System Demand 292.10 @ 98.969 System Demand (Including Hose Allowance) 542.10 @ 98.969 (b� ©M.E.P.CAD, Inc. 11 AutoSPRINK® VR5 v5.2.6 06/05/2008 8:31:22AM Page 6 €99 Flow Diagram (Top View) Job Number: KS0407 Report Description: Ordinary Group 11 �t ©M.E.P.CAD, Inc. tl AutoSPRINK® VR5 v5.2.6 06/05/2008 8:31:25AM Page 7 EARLY MORNING FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET NUMBER SHEET TITLE FA -01 SYSTEM INFORMATION FA -02 TYPICAL DETAILS - WIRING AND MOUNTING FA -03 FIRE ALARM SYSTEM FLOOR PLAN FA -04 SYSTEM CALCULATIONS (GENERAL), RISER, SITE PLAN T © Without Comments EX As Noted in Red a Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards. Acceptance is subject to errors and Omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings after this date will vold this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and Inspe4ion by The Tukwila Fire Prevention Bureau. oaate:_._By: ( �•4 GO de+ecA- r 40�e i115441t{ci (rear kto-At A ares. 4%1%4 645r•. is cpui(i L'i+�es tLtlW1 A FtitE GPEPART Please cal I : 575.4407 and give this job No. 09 -I �o and exact address for shut. town or rust ,ration so roi L NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection System§. Failure of test will result in a Re -inspection Fee artd termination of the testing. WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATION SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIAT❑R TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATI❑N LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE TWO 600V #12 AWG THHN/THWN TWO 600V #14 AWG THHN/THWN TWISTED TWO CONDUCTOR 300V #18 AWG FPL TW CABLE CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF CONDUIT SIZE MAXIMUM F 1/2" .12 SQUARE 3/4" .21 SQUARE 1" .34 SQUARE 1-1/4" .60 SQUARE 1-1/2"82 SQUARE 2' 1.34 SQUARE FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM DIMENSIONS AREA .244 O.D. .0467 .210 O.D. .0346 .156 O.D. .0191 FROM THE TABLE FILL DIMENSION FROM THE WIRE. LL NCH NCH NCH NCH NCH INCH N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48' A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY SYMBOL DESCRIPTION 2 MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S DEEP VERIFY IN FIELD a DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD 1 0 1 3 1 1 EX CONVENTIONAL CARBON MONOXIDE DETECTOR CODET 12-24 SIEMENS 4S DEEP BOX ® SMOKE DETECTOR (ADDRESSABLE -PHOTO) HFP-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING 12" A.F.F. INSTALLED BY OTHERS CEILING DDUCT DETECTOR SMOKE AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING sc FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 4S DEEP BOX W/ 1-1 /2" EXT. CEILING 80" A.F.F. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1 /2" EXT. CEILING C FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING FIRE ALARM © STROBE (WALL MOUNT) FIRE ALARM SPEAKER (CEILING MOUNT) 4 c ZR -MC --W SIEMENS 4S BOX W/ 1G RING SET -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM CEILING U.O.N. WP FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) MR MULTI -VOLTAGE CONTROL RELAY SET -W SET -S17 -WP MR -201 /C SIEMENS SIEMENS AIR PRODUCTS 4S DEEP BOX W/ 1-1 /2" EXT. 80" A.F.F. TO BOTTOM MT -SUR -BOX 1 /2" PIPE VERIFY IN FIELD 4S BOX VERIFY IN FIELD 0 MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD O JUNCTION BOX F.B.D. F.B.O. N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A U.O.N. UNLESS OTHERWISE NOTED N/A N/A N/A N/A WP WEATHERPROOF DEVICE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A Copyright PAID AUG -7 2009 Tukwila Fire 0726,-747 vi/o 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-651+5 RELEASE/REVISIONS REV. BY: a a DESCRIPTION SHOP DRAWINGS CO ADDITON PER TUKWILA FIRE DATE to (L) tn 03 Z <<<<< CO CO C5 J 00 <rn Z 111 t�zz J w O CC aC Q W N= H 'CALE: 1/8" = ' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: .0B NUMBER: 1 SHEET FA -01 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT �.. DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR SE PREVI❑US ADDRESSABLE DEVIL 0 DUCT DETECTOR L❑CATION END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH 1 0 GROUND -0 r() HTRI—R OSTATUS LED Co CO 0 0 0 N.O. COM N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL O LABEL SCALE NOTE 11 VOLTAGE MAX. - CURRENT MAX. - CONT. RES. MAX. - MAX. CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN. LINE SIZE- (BACKGOUND MUSIC SHUTDOWN) 27 VDC 3.5 rrA DURING POLLING 10 OHMS 200 FT. (18 AVG) 0.02uF 0.04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST 25 SEC. TO GUARANTEE DETECTI❑N. PREVI❑US ADDRESSABLE[+ DEVICE TO NEXT ADDRESSABLE C+ DEVICE _ L 0 TB1 0 0 0 0 123456 HCP TB2 00 65 4321 MUSIC OUTLET SAMPLING, TUBE INLET SAMPLING - TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE I -AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE f STOP IF LAST DEVICE 1(-) FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVICE (-) END OF LINE DEVICE (3.6K 1/4W) SUPERVISED... SWITCH RELAY CONTACTS (4.0A @ 125VAC) GROUND (4.0A @ 30VDC) 0 OND N AC r on 00 El 0 PAD -3 0 oo� INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - Li Li 24K TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE NOTE: 0 7 0 m rr) LO HTRI—D STATUS LED 00 0 NOT USED 0 O FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) DATA OUT TO PANEL L+ DATA IN END OF LINE DEVICE 3.6K 1/4W) 1SUPERVISED SWITCH OVEN FAN CONTACTS NCNO C O 0����—Q VVV 32) END OF LINE DEVIC NAC-4 SUPERVISED SWITCH--- 2 NAC -3 NAC -2 2 NAC -1 1,0 0 0 GROUND NOT SHIELD FAN SHUTDOWN SCALE=NONE N J 0 0 HTRI—R STATUS LED N.O. COY 0 N.G FRONT VIEW 1 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE + DEVICE LOOP NOT USED REMOTE DEVICE LOOP • 0 0 0 0 0— FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY ('S' CABLE) 470 OHMS EOL TS M-1 • 0 O 0 • 0 0 0 e TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE: NONE FROM FACP (V❑ICE CIRCUIT) ('V' CABLE) (S (-) STROBE SPEAKER 0 O EARTH GROUND -0.(+)TO NEXT DEVICE OR >(-) STOP IF LAST DEVICE ( STROBE( -) STROBE SPEAKER (+) ( ) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY 80" A.F.F. R 1.4 O O 4S DEEP BOX W/ 1-1/2" i EXTENSION RING 1(SPEAKER STROBE) 4S BOX ((STROBE ONLY) SPEAKER/STROBE TO NEXT DEVICE OR END OF LINE TO NEXT DEVICE OR END OF LINE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER TIN TEMPERATU E: +32' F (0' c) TO 100' F (338' C) HUMIDITY: NON -CONDENSING HUMIDITY, SIVG HFP-11 SMOKE DETECTOR —> FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (-) > DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR �............ DB -11 I STANDARD SMOKE DETECTOR BASE REAR VIEW NFP -11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT DEVICE > (-) DATA OUT > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID - HARD LID CEILING SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP B❑X.._._....-_ WITH 1-1/2' EXTENSI❑N �\ CEILING MOUNTED SPEAKER/STROBE N CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTION BOX MOUNTED ON CEILING. FLEX 0 0 H TO NEXT DEVICE / / / / / / / JUNCTION BOX ---- MOUNTED - MOUNTED AGAINST \ / CEILING SUPPORT \ / 0 0 -CADDY BAR SMOKE DETECTOR.—" SMOKE ETECT❑R -- SMOKE DETECTOR MOUNTING SCALE:NONE -- SUSPENDED ILLUMINATED CEILING DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. rC) co 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z Q z d DESCRIPTION SHOP DRAWINGS CO ADDITION PER TUKWILLA FIRE Lu I— Q o 5/15/08 rn 10 O 0o CIO OD Q 0) 2 2z z1WF- f�'zz C) w _ cc L OD LU C 1-- z �CALE: 1 /8"= 1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/12/08 BACKROUND PLAN PROVIDED BY: `JOB NUMBER: SHEET Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved FA -02 J EOL EOL—S1 191'i.84V 2S,2V 2S,2V 75 2S,2V 75 2897 WESTFIELD SOUTHCENTER MALL A SCALE II8•=1' FLAG NOTES: 4› - FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS.(SEE SIEMENS INSTALLATI❑N SUBMITTAL FOR L❑CATI❑N GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR. SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. ALARM SIGNAL TO ALARM SYSTEM WILL BE SUPERVIZ❑RY. SUPERVIZED CARBON M❑N❑XIDE SENSOR AND SHUTDOWN THE OVEN TO OVEN FAN CONTROL TERMINALS DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z d NYI DESCRIPTION SHOP DRAWINGS CO ADDITION PER TUKWILLA FIRE DATE 5/15/08 a) 0 co 0 ao 2CCCCC co co 7.1 Z Lij wFZ WZ 0 �_ cc JQ �'S wO CC eC W N= 1-- ` -CALE: 1 /8"=1 DRAWN BY: LAN DERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: .JOB NUMBER: 1 FA -03, Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved i /11111 • 1 :::::::.: _- I NORTH i. O O 0 0 EARLY MORNING WESTFIELD SOUTHCENTER MALL itt Lik-01AORNING SCALE 1132":V �2s,2V Id 75 C 75 L 2s,2Vn, 2s,2V 2s,2Vn 2S,2V L 15 15 C 75 EOL -S1 FA -BOX EX FACP 2I SYSTEM CALCULATIONS BATTERY SIZING CALCULAT ON PROJECT: Notification Appliance Circuit Detail WESTFIELD SOUTHCENTER MALL I Wire Resistance 1.62 CURRENT TOTAL= 653 Panel: EARLY MORNING Date: August 6, 2009 CIRCUIT: S1 Device Type Alarm Current Alarm Total 1 1 SET -MC @15CD SET -MC @30CD 3 !SET -MC @75CD SET -MC @110CD 0 SET-HMC-C@115CD 641 981 233; 318; SET-HMC-C@177CD 4451 SET -HMC @135CD 318' SET -HMC @185CD 445! 641 1..__ .____... Z-MC@15CD 0 Z-MC@30CD 0 SET-MC-CW@110CD DEVICES= 5 PROJECT: Panel: EARLY MORNING Date: August 6, 2009 CIRCUIT:,SPEAKER CIRCUIT 64 Wire Size Wire Length Voltage at EOL Circuit Total 0 525 0 Total Wire Resistance ( R ( WL * 2 )* (R/ft) Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E) (E= I * R) EOL Voltage_ (20.4 - E) 64 981 0 2331 0 TOTAL mA=1 653 12 265 19.8393342 Notification Appliance Circuit Detail WESTFIELD SOUTHCENTER MALL QTY Device Type 4 70.7V 1/8 Wire Resistance 2.58 CURRENT TOTAL= 7.2 !Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL 7.2 Circuit Total ' 0 Total Wire Resistance R 0 0 DEVICES= 4 (Total Cct Load) Voltage Drop ( E) M^ -^- (E= 1 * R) EOL Voltage (20.4 - E)_____ 2.92 0.01 0.02 20.38 0 14 565 20.379009121 7.2 1,0 co 0' 0 z 11.1 LU (1)0 w C) FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS (REV. BY: I EARLY MORNING EARLY MORNING DESCRIPTION FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations DATE oo co on co '-o Current Load: in Standby: Alarm: Current Load: o CCCCC Standby: Alarm: Device Type Qty Amps Total Amps Total Device Type Qty Amps Total Amps Total HFP-11 0.0022 0.0022 0.0023 AD2-P 1 0.0635 0.0635 0.064 0.064 Main System Board 1 0.03 0.03 0.030 • .030 HTR -R CO -DET 2 0.009600 0.0096 0.021 0.042 SET -MC @15CD 1 0.064 0.064 1 0.006000 0.006 0.03 0.030 SET -MC @30CD 0.098 SET -MC @75CD 3 0.175 0.525 SET -MC @110CD 0.233 SET HMC-C@115CD 0.318 SET HMC-C@135CD 0.318 0.0791 Amps 0.136 Amps SET HMC-C@185CD 0.445 ZR -MC @15CD ZR -MC @30CD 1 0.064 0.064 Standby Current Load: 0.0791 Amps For 24 Hours = 1.898 Amp -hours 0.098 HCP 0.0015 Alarm Current Load: 0.136 Amps For 5 Minutes= 0.011 Amp -hours 0.03 Amps 0.683 Amps 25% Derating= 2.387 Amp -hours Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours Alarm Current Load: 0.683 Amps For 5 Minutes= 0.057 Amp -hours Total System Current Load: 2.387 Amp -hours 25% Derating= 0.972 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.972 Amp -hours I Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULAT ON PROJECT: Notification Appliance Circuit Detail WESTFIELD SOUTHCENTER MALL I Wire Resistance 1.62 CURRENT TOTAL= 653 Panel: EARLY MORNING Date: August 6, 2009 CIRCUIT: S1 Device Type Alarm Current Alarm Total 1 1 SET -MC @15CD SET -MC @30CD 3 !SET -MC @75CD SET -MC @110CD 0 SET-HMC-C@115CD 641 981 233; 318; SET-HMC-C@177CD 4451 SET -HMC @135CD 318' SET -HMC @185CD 445! 641 1..__ .____... Z-MC@15CD 0 Z-MC@30CD 0 SET-MC-CW@110CD DEVICES= 5 PROJECT: Panel: EARLY MORNING Date: August 6, 2009 CIRCUIT:,SPEAKER CIRCUIT 64 Wire Size Wire Length Voltage at EOL Circuit Total 0 525 0 Total Wire Resistance ( R ( WL * 2 )* (R/ft) Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E) (E= I * R) EOL Voltage_ (20.4 - E) 64 981 0 2331 0 TOTAL mA=1 653 12 265 19.8393342 Notification Appliance Circuit Detail WESTFIELD SOUTHCENTER MALL QTY Device Type 4 70.7V 1/8 Wire Resistance 2.58 CURRENT TOTAL= 7.2 !Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL 7.2 Circuit Total ' 0 Total Wire Resistance R 0 0 DEVICES= 4 (Total Cct Load) Voltage Drop ( E) M^ -^- (E= 1 * R) EOL Voltage (20.4 - E)_____ 2.92 0.01 0.02 20.38 0 14 565 20.379009121 7.2 1,0 co 0' 0 z 11.1 LU (1)0 w C) FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS (REV. BY: I Z DESCRIPTION SHOP DRAWINGS CO ADDITION PER TUKWILLA FIRE DATE oo co on co '-o in CO o CCCCC coo Q 0) Z 1 -CC Wo (1)Z Z O 2 L_ CC J w O� Cn W ND 1- 3 W z w C/) z O -J 0 W F- >- VJ / �CALE: 1/8"=1' DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE: 5/12/08 BACKROUND PLAN PROVIDED BY: RISER DIAGRAM VOLTAGE DROP CALCULATION FA -04 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved �013 NUMBER: SHEET 1 2897 FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET \UM3ESHEET TITLE FA -01 SYSTEM INFO MATT O \ FA -02 TYPICAL DETAILS - WRI\G A\D V 0„\TI\C FA -03 FRE ALA VI SYSTEM FLOG LA \ FA -04 SYSTEM CALCULATIO\S (GE\EAL), �ISE�, SITE PLA\ WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATI❑N TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED • .210 0.0. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT DF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED, NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO 'CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM ;SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 3 1 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP ® INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D` SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD �"1 LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD La SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING DUCT SMOKE p DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-1 i W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE C (CEILING MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE C (CEILING MOUNT) SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING C FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -1 -CW SIEMENS 4S BOX W/ 1G RING CEILING L FIRE ALARM STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. YC FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING B AWP FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -S17 -WP SIEMENS MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD MR MULTI -VOLTAGE CONTROL RELAY MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JB❑X FIRE ALARM TERMINAL CABINET JUNCTI❑N BOX F.B.O. F.B.O. F.B.O. F. B.0: CCETED VERIY IN TLD VERIFY IN FtELD A.F.F. ABOVE FINISHED N/A N / A Without Corints N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A t: OE Cal CO3 C4 CC 114:D 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS m LU z DESCRIPTION SHOP DRAWINGS W F- a 0 0 u� C co J 00 w EEO � F- (3 I``•� Z Z W 1 -E C4I Q cc ND NOTICE d, signed, Tukwila' �artment Pre-test must be presented Inspector prior to ement of Acceptances of any Fire Alarm etection Systems. of test will result spection Fee and termination of the testing. fU$WILA FIRE DEPARTNIElit Please call: 575-4402 and give this job No. and exact address for shut= gown or restoration approval' RECEIVED JUN - 3 2008 T vela Fire abov-d- Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved J SCALE: 1 /8"=1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: JOB NUMBER: SHEET FA -01 LuuiN As -Noted In Red F.B.D. FURNISHED BY OTHERS N/A N/A ❑ Per The Attatiled Letter N/A The Tukwila Fire N/A NOTN/A APPLICABLE i nese plans have beef ieviewed by Pk,Qntion Bureau for confit nce with current citvN/A standards. Acceptance is sublet to errors and A Complete - - U.D.N. UNLESS OTHERWISEomissions NOTED N/A which do not autitut ize violations of adopted sMrrd�rus and orcinances.NVt responsibility for the/A adequacy of design rests totally with the designer. WP WEATHERPROOF DEVICE N/A A�d,�di ions, •e a Ions or reels • . - - • - - t11ti tate will void this.acce�t/aftce and will require aN/A resubmittal of revised drawings for subsequent approval. Certificat to the commenc Testing and D Failure in a Re -ii RED AS BUILT ADD ❑R CHANGE N/A I afacceptance is subjedtf&fiietd test and inspectiglxrby The Tukwila Fire Prevention Bureau. GREEN AS BUILT REMOVE N/A a E/A CX) N/A Date BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A t: OE Cal CO3 C4 CC 114:D 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS m LU z DESCRIPTION SHOP DRAWINGS W F- a 0 0 u� C co J 00 w EEO � F- (3 I``•� Z Z W 1 -E C4I Q cc ND NOTICE d, signed, Tukwila' �artment Pre-test must be presented Inspector prior to ement of Acceptances of any Fire Alarm etection Systems. of test will result spection Fee and termination of the testing. fU$WILA FIRE DEPARTNIElit Please call: 575-4402 and give this job No. and exact address for shut= gown or restoration approval' RECEIVED JUN - 3 2008 T vela Fire abov-d- Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved J SCALE: 1 /8"=1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: JOB NUMBER: SHEET FA -01 ( THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABa SCALE COMBINE ALL SHIELDS AND IS❑LATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE. v � o DUCT DETECTOR LOCATI❑N FROM XLS CONTROL PANEL OR if PREVIOUS ADDRESSABLE DEVIC END OF LINE DEVICE<3.6K 1/4W) SUPERVISED SWITCH eT O m GROUND �r- 0 HTRI—R OSTATUS LED 00 1-. CO 0 O O N.O. COM N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. O TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE DEVICE TO NEXT ADDRESSABLE DEVICE + NOTE 1: VOLTAGE MAX. - CURRENT MAX. - CONT. RES. MAX. - MAX. CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX, LINE SIZE - MIN, LINE SIZE - MUSIC OUTLET SAMPLING- \ TUBE INLET SAMPLING TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE 1} -AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE {(+j FROM XLS CONTROL PANEL OR .[(+) PREVIOUS ADDRESSABLE DEVICE (-)-1 RELAY CONTACTS C4.OA @ 125VAC) (4.0A @ 30VDC) 27 VDC 3,5 mA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0.02uF 0.04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST 25 SEC, TO GUARANTEE DETECTI❑N. 0 TB1 S 0 m 0 0 123456 HCP TB2 0 0 0� -+- 654321 END OF LINE DEVICE (3,6K 1/4W) O -Q SUPERVISED_____�� SWITCH GROUND NOTE: ; i ; O HTRI—D OSTATUS LED 00 m 0 1 NOT USED O FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC 1 T 0 PAD -3 0 00 O INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 24K n TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE NAC -4 NAC -3 2 NAC -2 NAC -1 END OF LINE DEVICE 3.6K 1/4W) UPERVISED SWITCH r FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE + DEVICE LOOP NOT USED REMOTE �I.. DEVICE LOOP 0 0 0 FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY C'S' CABLE) FROM FACP <VOICE CIRCUIT) C'V' CABLE) 470 OHMS �YV EOL TEM -1 0 0 SMC O 0 9C CI c0 TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE NOW () STROBE SPEAKER (+) (-) u � ( STROBE-) EARTH GROUND -->(+)TO NEXT DEVICE OR >(-) STOP IF LAST DEVICE () STROBE SPEAKER SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE F OR STROBE ONLY RI 80" A.F.F. 4S DEEP BOX W/ 1-1 /2" EXTENSION RING (SPEAKER SIHOBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE TO NEXT DEVICE OR END OF LINE TO NEXT DEVICE OR END OF LINE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER 11N TEMPERA1U E: +32' F 0' C) TO 100' F 38' C) HUMIDITY: 933% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR —� FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE fDATA IN ( ) >- DATA IN (+) > DEVICE IS USTED FOR NR VOLOCITY APPUCATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE __ TO NEXT DEVICE E— > ( ) DATA OUT > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID —� CEILING HARD LID ---� ------SPEAKER SUPPORT TILL BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSI❑N \ CEILING MOUNTED SPEAKER/STROBE -N. CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTI❑N BOX— MOUNTED ON CEILING( FLEX \ 45 JUNCTI❑N BOX ---- MOUNTED AGAINST CEILING SUPPORT 0 0 IL TO NEXT DEVICE -----CADDY BAR SMOKE DETECTOR------ SMOKE ETECT❑R— SMOKE DETECTOR MOUNTING SCALE=NONE SUSPENDED ILLUMINATED CEILING DO N O T IN ADDRESSA DEVICES U\ PREDROC: A DVICES AD ST _L LE T TI_ \VIED W DHSS. AT UC TH Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved v 06:5% fA cocat 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: NVI DESCRIPTION SHOP DRAWINGS DATE 0 in to (9 aa«CC ‘CALE: 1 /8"=1 0 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE:5/12/08 BACKROUND PLAN PROVIDED BY: `JOB NUMBER: J SHEET FA -02 \ \ t\.\. \. \\ \ EQL—S1 1 .84V • 2891 WESTFIELD SOUTHCENTER MALL SCALE 118'14 LAG NO ES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATION SUBMITTAL FOR L❑CATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR, SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM, FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NOT INS O A_L ADDRESSABLE N DEVICES ,INTI PREFROGRAVME DEVICES ADDRL (THAT NG D WITH SS. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved Cia z (,)C#3iu z 46 Zit z FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS CO W 0 E- < o Ln CO CO JJ CO Q 2 Z cc WO I` Ci) Z Z 2 N Q -‹ CC CVD 1— SCALE: 1 /8"=1 DRAWN BY: !.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: �OB NUMBER: SHEET FA -03} NORTH 2897 WESTFIELD SOUTHCENTER MAIL SCALE 1132"=1' D D 75 C 75 15 15 C 75 EX SYSTEM CALCULATIONS BATTERY SIZING CALCULATION 2897 2897 FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations z 0 I - a_ CC U CO w 0 PROJECT: WESTFIELD SOUTHCENTER MALL uJ F- <4 0 5/15/08 2897 Wire Resistance 1.62 9 Panel: June 2, 2008 CURRENT TOTAL= 653 Current Load: Standby: Alarm: S1 Current Load: Standby: Alarm: QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Volta_ ge at EOL Circuit Total Total Wire Resistance (R) 0.86 1 SET -MC @15CD 64 Device Type Qty Amps Total Amps Total Device Type Qty Amps (WL*2)*(R/ft) Total Amps Total 175 HFP-11 0.0022 0.0022 0.0023 Total Device Load, Amps (I) 0.65 0 SET -MC @110CD 233 0 AD2-P 1 0.0635 0.0635 0.064 0.064 _ Main System Board 1 0.03 0.56 0.03 0.030 0.030 0 HTR -R 2 0.009600 0.0096 0.021 0.042 0. SET -MC @15CD 318 1 0.064 0.064 EOL Voltage HTRI-D 0 SET -HMC @185CD 0.001600 0 0.0035 SET -MC @30CD (20.4 - E) 1 Z-MC@15CD 0.098 64 ICP -B6 0.005 0 Z-MC@30CD SET -MC @75CD 0 3 0.175 0.525 0 SET-MC-CW@110CD 233 0 19.83933421 653 SET -MC @110CD DEVICES= 5 TOTAL mA= 653 0.233 265 Amps SET-HMC-C@115CD SET HMC-C@135CD SET HMC-C@185CD ZR -MC @15CD ZR -MC @30CD HCP 1 _ PROJECT: 0.318 0.318 0.445 0.064 0.098 0.0015 0.064 2877 Wire Resistance 2.58 Panel: June 2, 2008 0.0731 Amps 0.106 Date: CIRCUIT: SPEAKER CIRCUIT 1.754 Amp -hours Standby Current Load: 0.0731 Amps For 24 Hours = Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total Alarm Current Load: 0.106 Amps For 5 Minutes= 0.009 Amp -hours - Total Wire Resistance (R) 2.92 0.03 Amps 0.683 Amps (WL*2)*(R/ft) 0 0 0 Total Device Load, Amps (I) 0.01 0 0 25% Derating= 2.204 Amp -hours Standby Current Load: 0.03 Amps 0 For 24 Hours = 0.720 Amp -hours Voltage Drop ( E) 0.02 0 0 ; (E= I * R) 0 0 0 - ! Alarm Current Load: EOL Voltage 0.683 Amps For 5 Minutes= 0.057 Amp -hours Total System Current Load: 2.204 Amp -hours 0 0 0 0 0 0 i DEVICES= 25% Derating= 0.972 Amp -hours 14 Battery Pair to be Used: 20.379009121 7.2 12VDC Amp -hours 7AH Total System Current Load: 0.972 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULATION z (#) z cc izzz O 0' 0' co N 0 O N X La Ln 10 N N .0 O N J Lu cn z 0 (1) Lu w CO w J W CC REV. BY: z a Notification Appliance Circuit Detail z 0 I - a_ CC U CO w 0 PROJECT: WESTFIELD SOUTHCENTER MALL uJ F- <4 0 5/15/08 2897 Wire Resistance 1.62 9 Panel: June 2, 2008 CURRENT TOTAL= 653 Date: CIRCUIT: S1 QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Volta_ ge at EOL Circuit Total Total Wire Resistance (R) 0.86 1 SET -MC @15CD 64 64 0 SET-MC@30CD 98 0 (WL*2)*(R/ft) 3 SET -MC @75CD . 175 525 Total Device Load, Amps (I) 0.65 0 SET -MC @110CD 233 0 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 _ Voltage Drop (E) 0.56 0 SET-HMC-C@177CD 445 0 (E= I * R) 0. SET -HMC @135CD 318 0 EOL Voltage 19.84 0 SET -HMC @185CD 445 0 (20.4 - E) 1 Z-MC@15CD 64 64 0 Z-MC@30CD 98 0 0 SET-MC-CW@110CD 233 0 19.83933421 653 DEVICES= 5 TOTAL mA= 653 12 265 Notification Appliance Circuit Detail _ PROJECT: WESTFIELD SOUTHCENTER MALL 2877 Wire Resistance 2.58 Panel: June 2, 2008 CURRENT TOTAL= 7.2 Date: CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 4 70.7V 1/8 1.8 7.2 Total Wire Resistance (R) 2.92 0 0 - 0 (WL*2)*(R/ft) 0 0 0 Total Device Load, Amps (I) 0.01 0 0 0 (Total Cct Load) 0 - 0 0 Voltage Drop ( E) 0.02 0 0 ; (E= I * R) 0 0 0 - ! EOL Voltage 20.38 0 0 0 (20.4-E) 0 0 0 0 0 0 i DEVICES= 4 TOTAL mA= 7.2 14 565 20.379009121 7.2 z (#) z cc izzz O 0' 0' co N 0 O N X La Ln 10 N N .0 O N J Lu cn z 0 (1) Lu w CO w J W CC REV. BY: z a z 0 I - a_ CC U CO w 0 SHOP DRAWINGS uJ F- <4 0 5/15/08 9 CaCCC co co co<0) 2Z WO N. (I)ZZ CO �U� CV Q W� CE co CV D 1 -- 5 0 w F- CD w CC w z w Cl) z 0 -J 0 w CI) (SCALE: 1/8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: JOB NUMBER: RISER DIAGRAM VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc.. All Rights Reserved SHEET FA -04 � VICINITY MAP (Suite#2897 SCAM -NTS General Notes 2897 SHELL SPACE 1. Western States Fire Protection to add new pendent heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to;pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7, The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. EAST RISER DETAIL HYDRAULIC = REFERENCE ONLY NOT TO SCALE SYMBOL LEGEND REVISIONS 30� !Ordinary Group 11'0.20gpm/ft2 for 945.00ft2 j -"::1;7• • PIPE NIPPLE FLEXHEAD SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS MOUNTING BRACKET REDUCING FITTING 5'-0"-A.F.F SUSPENDED T -BAR GRID CEILING TILE Existing Main 0701 e= Existing Main Zone T9 3-i • FIRE SPRINKLERSYSTEM Sprinkler Legend 12'-0"-A.F.F 3 52_9 i 2 -WAY EARTHQUAKE BRACE NO. DESCRIPTION DATE SYM. SIN QTY. K SPRAY ORIF. FIN. TEMP. MFR./MODEL 4 -WAY EARTHQUAKE BRACE R3615 15 5.6 Pendent Chrome 155`F F1FR Semi-Rec APPROVAL: saw FLEXHEAD DETAIL NOT TO SCALE FIG. 90a SWIVEL SWAY BRACE FITTING Cl BRACE PIPE 318' KWIK BOLT (2114' EMBED LENGTH) FIG. 1000 "FAST CLAMP' SWAY BRACE ATTACHMENT LINE PIPE LATERAL LINE RESTRAINTS NON. THREADED BRACE PIPE Remote Area 2897 SHELL SPACE FIG.4A PIPE CLAMP FOR SWAY BRACE 3/E' KWIK BOLT (2114' EMBED LENGTH) FIG. 909 NO.THREAD SWIVEL SWAY BRACE ATTACHMENT ULATERAL BRANCHLINE RESTRAINT chid�.NOt4.THREADED BRACE PIPE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE CALCULATION DESIGN CRITERIA STANDARD NFPA #13-2007 OCCUPANCY CLASS ORD HAZARD 11 MAX. COVERAGE per HEAD 130 Ft' DENSITY .20 GPM 1 Ft' for 945.0 Ft' SPRINKLER Reliable F1FR Semi-Rec ORIFICE 112" K= 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 _ PSI FLOW 10900 GPM AT BASE OF RISER. SYSTEM REQUIRES: 292.10 GPM @ 95.5 PSI At time of Design 12'- 0" CLG. = 37.00% AREA REDUCTION , Ceara ist Or N +d . ?Davies ; l ha:tty 97 City of Tukwila HYDLRAULIC REFERENCE POINT R5415 7 5.6 Pendent White 155`F G4A Concealed CONT. NO.: KS0407 Total = 22 DRAWN BY: Adam Kantner HANGER SYMBOL BRANCHLINE RESTRAINT SPRK ON SHEET: SEE LEGEND SPRK ON JOB: DATE: 06/05/08 Hanger No. 07C HILTI Kwik Bolt III 7-)N/ '_ S HILTI KVR Bok U Orfled Anchor--- / —1 nchor7- "1 \5// / �i Concrete Construction Cut Rod Lgth Rounded to Nearest Inch Rod Coupling All Thread Rod Swivel Ring Pipe Bottom of Concrete to Center Line of Pipe Note on Plan Note on Plan: Hanger Number and 'A' Dimension • HANGER DETAIL NOT TO SCALE t Vanilla Shells 2897 w z 0 PT Without Comments As Noted In Red Per The Attached Letter i nese plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted stanaaras and orainances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings atter this date will void this,acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to fletd test and Inspection by The Tukwila Fire, Prevention Bureau. te•'//2---/e0,413�By: &7cD VICINITY MAP DETAI L Western States Fire Protection Company 7102 180th AVE NE, STE A-105 - REDMOND, WA - 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE/AUSTN/DALLAS/DECATUR / DENVER / DULUTH / HOUSTON /KANSAS CITY LAS VEGAS /MIMIEAPOLIS /PHOENIX I PORTLAND I RAPID CITY/ST. PAUL/ SALT LACE CITY/SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 1'UKWILA FIRE Lth.HAi=i Please call: 575.4407 and give this job and exact address for shut• iLswn or restoration approval. NOTICE Weld stamps must be inspected before pipe is hung. Do not paint piping prior to hydrostatic test approval. Vanilla Shells 2897 Southcenter Mall Tukwila ,Wa 98188 FIRE SPRINKLER SYSTEM -- a SHEET FP -1 OF 1 2303 1 11Tv'tict 2(rD2� Swinerton Builders tY 0 0 1— z 0 U General Notes VICINITY MAP (Suite#2897) SCALE: NTS 2897 SHELL SPACE 1. Western States Fire Protection to add new pendent heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. EAST RISER DETAIL HYDRAULIC REFERENCE : ONLY NOT TO SCALE Existing Main Existing Main Zone T9 !Ordinary Group II'0.20gpm/ft2 for 945.00ft2 a °.<.`:.I Ai 11 I III 0 '\ 44. 1111w''Zill�� oco i Noir' ��Eiii� • - U• iii/ amitomi 11,,,N1111111111tr fN IICP' • 0 -0 0 Em 3-3Y N -1--12,-0"-A.F.F 1 3h t1, tam CIPA81 MI s."4-= 1 1_1- 03. Q I: —0---, [ 18'-0"-A.F.F I ^!V 9` O 0 -3'h o 1 FIRE SPRINKLER SYSTEM 1/8"=V-0" TYPICAL FLEXABLE SPRINKLER CONNECTION:. FLEXHEAD MOUNTING BRACKET PIPE NIPPLE SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS REDUCING FITTING SUSPENDED T -BAR GRID SPRINKLER HEAD CEILING TILE FLEXHEAD DETAIL NOT TO SCALE FIG. 808 SWIVEL SWAY BRACE FITTING 3R' KWIK BOLT „.-- (21/4' EMBED LENGTH) BRAE PIPE FIG. 1000 -'FAST CLAMP" SWAY BRACE ATTACHMENT LINE PIPE LATERAL LINE RESTRAINTS NON -THREADED BRACE PIPE Remote Area 2897 SHELL SPACE CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY CLASS ORD HAZARD II MAX. COVERAGE per HEAD 130 Ft' DENSITY .20 GPM / Ft' for 945.0 Ft' SPRINKLER Reliable F1 FR Semi-Rec ORIFICE 1/2" K= 5.6 WATER FLOW INFORMATION': STATIC 140 RESIDUAL 20 PSI PSI FLOW 10900 GPM AT BASE OF RISER. SYSTEM REQUIRES: 292.10 GPM © 95.5 PSI ' At time of Design 12'- 0" CLG. = 37.00% AREA REDUCTION FIG. 4A PIPE CLAMP FOR SWAY BRACE 3/8' KWIK BOLT (2 114' EMBED LENGTH) FIG. 909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT LATERAL BRANCHLINE RESTRAINT WAN NON -THREADED BRACE PIPE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE Hanger No. 07C HILTI Kwik Bolt III N'/ / HILTI Kwik8°k(1 Drilled Anchor i Cut Rod Lgth Rounded to Nearest Inch Rod Coupling All Thread Rod Swivel Ring Pipe Concrete f Construction Bottom of Concrete to Center Line of Pipe Note on Plan Note on Plan: Hanger Number and 'A' Dimension HANGER DETAIL NOT TO SCALE VICINITY MAP DETAIL NOT TO SCALE 05-53/'3 co N (1) co U) w z 0 Adam Kantner a 0 Swinerton Builders CONTRACTOR SYMBOL LEGEND REVISIONS Sprinkler Legend 2 -WAY EARTHQUAKE BRACE NO. DESCRIPTION DATE SYM. SIN QTY. K SPRAY ORIF. FIN. TEMP. MFR./MODEL 4 -WAY EARTHQUAKE BRACE R3615 15 5.6 Pendent Chrome 155°F F1 FR Semi-Rec APPROVAL: City of Tukwila HYDRAULIC REFERENCE POINT HANGER SYMBOL R5415 7 5.6 Pendent White 155°F G4A Concealed CONT. NO.: KS0407 Total = 22 DRAWN BY: Adam Kantner BRANCHLINE RESTRAINT SPRK ON SHEET: SEE LEGEND SPRK. ON JOB: DATE: 06/19/08 Western States Fire Protection Company 7102 180th AVE NE, STE A-105 - REDMOND, WA - 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUOUEROUE/AUSTIN ! DALLAS/ DECATUR / DEWERI DULUTH I HOUSTON/KANSAS CITY LAS VEGAS /MINNEAPOLIS / PHOENIX! PORTLAND / RAPID CITY/ ST. PAUL / SALT LAKE CITY/SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 Vanilla Shells 2897 Southcenter Mall Tukwila ,Wa 98188 FIRE SPRINKLER SYSTEM SHEET FP -1 OF 1 2897 SOUTHCENTER MALL ASSOCIATED PERMITS 09-F-120 08-F-270 08-S-313 08-S-310 0 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Permit No.: Date: Reviewer: Vanilla Shell 2897 Southcenter Mall 08-S310 June 11, 2008 Steve Kohler Fire Inspector/Plan Review (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods Tess than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1 "-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ` of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. ilHydraulic I + Summary Job Number: KS0407 Report Description: Ordinary Group II Job Job Number Design Engineer KS0407 Adam Kanter Job Name . State Certification/License Number Vanilla Shells 2897 ! WESTESF136QF Address 1 , AHJ Southcenter Mall City of Tukwila Address 2 Job Site 1 Southcenter Mall City State Zip Code Drawing Name Tukwila Wa 98188 j FP-1-2897.cad System i Remote Area(s) Most Demanding Sprinkler Data : Occupancy 5.6 K -Factor 26.00 at 21.556 : Ordinary Group II Hose Allowance At Source Density Area of Application 250.00 0.20gpm/ft2 , 945.00ft2 (Actual 948.10ft2) Additional Hose Supplies Number Of Sprinklers Calculated Coverage Per Sprinkler Node Flow(gpm) 10 130.00ft2 AutoPeak Results: Pressure For Remote Area(s) Adjacent To Most Remote Area Total Hose Streams 250.00 ( ( �� ` ,�� System Flow Demand Total Water Required (Including Hose Allowance) ;�, r e 292.10 542.10„ ;1 Maximum Pressure Unbalance In Loops �� `V br fi-I� = `� 0.000 Maximum Velocity Above Ground,111r 26.35 between nodes 123 and 49 Maximum Velocity Under Ground ,�tO 1.10 between nodes 1 and 324 Volume capacity of Wet Pipes Volume capacity of Dry Pipes 2750.71 gal 1.35ft' Supplies 1 Hose Flow Static 1 Residual @ Flow j Available @ Total Demand Required Safety Margin Node (gpm) (psi) (psi) (gpm) (psi) (gpm) (psi) i (psi) 1 250.00 140.000 20.000 10900.00 1 139.534 542.10 98.969 40.566 Contractor Contractor Number Contact Name 1 Contact Title KS0407 ' Adam Kantner 1 Project Manager Contractor Name Phone Extension Western States Fire Protection ; 425.881.0100 1 Address 1 FAX 7102 180th Ave Ne, Suite A-105 485.736.9032 Address 2 ' E-mail 1 City State i Zip Code Web -Site Redmond WA 1 98052 kA, ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 06/05/2008 8:31:06AM Page 1 .1 Summary Of Outflowing Devices `Job Number: KS0407 Report Description: Ordinary Group II Device Actual Flow (gpm) Minimum Flow (gpm) K -Factor (K) Pressure (psi) b Sprinkler 101 26.00 26.00 5.6 21.556 Sprinkler 102 26.26 26.00 5.6 21.997 Sprinkler 107 30.78 26.00 5.6 30.211 Sprinkler 103 26.80 26.00 5.6 22.908 Sprinkler 106 30.70 26.00 5.6 30.047 Sprinkler 104 27.68 26.00 5.6 24.436 Skier 108 31.19 26.00 5.6 31.015 Sprinkler 105 29.15 26.00 5.6 27.101 Sprinkler 110 32.21 26.00 5.6 33.084 Sprinkler 109 ; 31.32 26.00 5.6 31.278 c Most Demanding Sprinkler Data (� ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 06/05/2008 8:31:14AM Page 2 Node Analysis Job Number: KS0407 Report Description: Ordinary Group II Node Elevation(Foot) Fittings Pressure(psi) Discharge(gpm) 22 17-6 E(2-0) 28.439 24 17-6 PO(5-0) 28.529 26 17-6 E(2-0) 38.277 31 17-6 PO(5-0) 29.102 33 17-6 ; PO(5-0) 38.492 37 17-6 PO(5-0) 31.156 39 17-6 PO(5-0) 39.782) 43 17-6 ; PO(5-0) 34.736 45 17-6 PO(5-0) 42.537: 49 17-6 PO(5-0). 40.332 123 17-6 2P0(8-0) 61.428 ; 149 17-6 2P0(8-0)61.321 II ' 236 -16-1 . P0(26-4) 91.796 324 -14-1% • BFP(-4.500) 95.518 358 -16-1 . LtE(16-0) 91.832 ' 101 15-01,4 Spr(-21.556) 21.556 26.00 102 15-0% , Spr(-21.997) 21.997 26.26 107 15-0 , Spr(-30.211) 30.211 , 30.78 103 12-0% , Spr(-22.908) 22.908 26.80 106 1 12-0 Spr(-30.047)30.047 30.70 . 104 12-0% ! Spr(-24.436) 24.436 , 27.68 , 108 12-0 Spr(-31.015) 31.015 31.19 105 12-0% j Spr(-27.101) 27.101 29.15 110 12-0 ; Spr(-33.084) 33.084 ' 32.21 109 12-0% Sp (-31.278) 31.278 31.32 1 . -22-0 S 98.969 292.10 , • �t ©M.E.P.CAD, Inc. ,fi AutoSPRINK®VR5 v5.2.6 06/05/2008 8:31:16AM Page 3 i Hydraulic AnalysisIIJob Number: KSO407 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K -Factor Pt Pn Fittings Eq. Length Summary Upstream Total Length ew Route 1 DR 1.049 Q=26.00 9.65 C=120 0.211435 29-7% Pf 7.958 101 15-0' q=26.00 K=5.6 21.556 Spr(-21.556) 8-0 Pe -1.075 22 17-6 28.439 4E(2-0) 37-7% Pv BL 1.610 Q=26.00 4.1.0 C=120 0.026249 3-5, Pf 0.090 22 17-6 28.439 ; Pe 24 17-6 28.529 3-5 Pv BL 1.610 Q=52.26 8.24 0=120 0.095519 6-0 Pf 0.573 24 17-6 28.529 Pe 0.000 31 17-6 29.102 6-0 Pv BL 1.610 Q=79.07 12.46 C=120 0.205450 10-0 Pf 2.054 31 17-6 29.102 1 Pe 37 17-6 31.156 10-0 Pv BL 1.610 Q=106.75 16.82 C=120 0.358004 10-0 Pf 3.580 37 17-6 31.156 ' Pe 43 17-6 34.736 10-0' Pv BL 1.610 Q=135.90 21.42 C=120 0.559605 10-0, Pf 5.596 43 17-6 34.736 Pe 49 17-6 40.332 10-0• Pv BL 1.610 Q=167.22 26.35 0=120 0.821300 17-8 Pf 21.096 49 17-6 40.332 8-0 Pe 123 17-6 61.428 PO(8-0) 25-8', Pv CM 4.260 Q=292.10 6.57 C=120 0_.020.1.67 457-7 Pf 15.808 123 17-6 61.428 177-6 Pe 14.559 236 -16-1 91.796 2cplg(-1.500), 2P0(26-4), E(13-2), 635-1' Pv 6fE(8-11%), BV(15-91A), 2Ee2(5-3), CV(28-11'%), GV(2-7%) FM 8.329 Q=292.10 1.72 C=120 0.000770 14-5% Pf 0.036 236 -16-1 91.796 32-0 Pe 0.000 358 -16-1 91.832 fE(16-0), LtE(16-0) 46-5% Pv FM 10.420 Q=292.10 1.10 0=120 0.000259 28-2'% Pf 4.529 _ _ 358 -16-1 91.832 83-0 Pe -0.842 324 -14-1% 95.518 4LtE(16-0), BV(19-0), BFP(-4.500) 111-2'/z Pv UG 10.400 Q=292.10 1.10 C=140 0.000196 110-2j Pf 0.044 324 -14-1% 95.518 111-7 Pe 3.407 1 -22-0 98.969 E(35-1), 3LtE(25-6), S 221-9% Pv lap Route 2 DR 1.049 0=26.26 9.75 0=120 0.215429 26-3'% Pf 7.607 102 15-0% q=26.26 K=5.6 21.997 Spr(-21.997) 9-0' Pe -1.075 24 17-6 28.529 2E(2-0), P0(5-0) ! 35-3% Pv a. Route 3 DR 1.049 Q=26.80 9.95 C=120 0.223675 29-3'% Pf 8.569 103 12-0'/2 q=26.80 K=5.6 22.908 Spr(-22.908) 9-0 Pe -2.375 31 17-6 29.102 2E(2-0), P0(5-0) 38-3Y Pv Route 4 DR 1.049 Q=27.68 10.28 C=120 0.237435 29-3'/z' Pf 9.096 104 12-0'/2 q=27.68 K=5.6 24.436 Spr(-24.436) 9-0 Pe -2.375 37 17-6 31.156 2E(2-0), PO(5-0) 38-3'/z Pv v Route 5 DR 1.049 Q=29.15 10.82 0=120 0.261301 29-3% Pf 10.010 105 12-0'/ q=29.15 K=5.6 27.101 Spr(-27.101) 9-0 Pe -2.375 43 17-6 34.736 2E(2-0), PO(5-0) 38-3% Pv Q Route 6 DR 1.049 0=30.70 11.40 C=120 0.287472 28-8 Pf 10.829 106 12-0 q=30.70 K=5.6 30.047 Spr(-30.047) 9-0, Pe -2.384 33 17-6 38.492 2E(2-0), P0(5-0) 37-8 Pv BL 1.610 0=61.48 9.69 C=120 0.128981 10-0 Pf 1.290 33 17-6 38.492 , Pe 39 17-6 39.782 10-0 Pv BL 1.610 0=92.66 14.60 C=120 0.275546 10-0 Pf 2.755 39 17-6 39.782 I Pe 45 17-6 42.537 10-0' Pv BL 1.610 Q=124.87 19.68 C=120 0.478504 31-3 Pf 18.783 45 17-6 42.537 8-0 Pe 149 17-6 61.321 P0(8-0) 39-3 Pv CM 4.260 0=124.87 2.81 0=120 0.004187 12-1'h Pf 0.108 149 17-6 61.32113-7 Pe 123 17-6 61.428 2fE(6-9%) 25-9, Pv Route 7 DR 1.049 0=30.78 11.43 0=120 0.288917 25-8 Pf 9.150 107 15-0 q=30.78 K=5.6 30.211 Spr(-30.211) 6-0 Pe -1.084 26 17-6 38.277 3E(2-0) 31-8 Pv ©M.E.P.CAD, Inc. AutoSPRINK®VR5 v5.2.6 06/05/2008 8:31:18AM Page 4 11 Hydraulic Analysis 1 Job Number: KS0407 Report Description: Ordinary Group II • Pipe Type Diameter Flow Velocy HWC Friction Loss Length Pressure Downstream Elevation Discharge K -Factor Pt Pn Fittings Eq. Length Summary Upstream Total Length BL 1.610 Q=30.78 4.85 C=120 0.035868 6-0 Pf 0.215 26 17-6 38.277 Pe 33 17-6 38.492 6-0 Pv Route 8 DR 1.049 Q=31.19 11.58 C=120 0.296025 28-8 Pf 11.151 108 12-0 q=31.19 K=5.6 31.015 Spr(-31.015) 9-0 Pe -2.384 39 17-6 39.782 2E(2-0), PO(5-0) 37-8; Pv o Route 9 DR 1.049 Q=31.32 11.63 C=120 0.298347 29-3'% Pf 11.430 109 12-0% q=31.32 K=5.6 31.278 Spr(-31.278) 9-0 Pe -2.375 49 17-6 40.332 2E(2-0), PO(5-0) 38-3% Pv ob Route 10 DR 1.049 Q=32.21 11.96 C=120 0.314247 28-8 Pf 11.838 110 12-0 q=32.21 K=5.6 33.084 Spr(-33.084) 9-Q Pe -2.384 45 17-6 42.537 2E(2-0), PO(5-0) 37-8' Pv Equivalent Pipe Lengths of Valves and Fittings (C=120 only) ` C Value Multiplier / Actual Inside Diameter 1487 = Factor Value Of C 100 130 140 150 Schedule 40 Steel Pipe Inside Diameter I Multiplying Factor 0.713 1.16 1.33 1.51 Pipe Type Legend Units Legend Fittings Legend AO Arm -Over BL Branch Line CM Cross Main DN Drain DR Drop DY Dynamic FM Feed Main FR Feed Riser MS Miscellaneous OR Outrigger RN Riser Nipple SP Sprig ST Stand Pipe UG UndergroundPv - Diameter Inch Elevation Foot Flow gpm Discharge gpm Velocity fps Pressure psi Length Foot Friction Loss psi/Foot HWC Hazen -Williams Constant Pt Total pressure at a point in a pipe Pn Normal pressure at a point in a pipe Pf Pressure loss due to friction between points Pe Pressure due to elevation difference between indicated points Velocity pressure at a point in a pipe ALV Alarm Valve AngV Angle Valve b Bushing BaIV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Turn 90° cplg Coupling Cr Cross Run CV Check Valve DeiV Deluge Valve DPV Dry Pipe Valve E 90° Elbow EE 45° Elbow -, Eel 11'W Elbow Ee2 22W Elbow f Flow Device FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow flg Flange FN Floating Node fT FireLock(TM) Tee g Gauge GIoV Globe Valve GV Gate Valve Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PrV Pressure Relief Valve PRV Pressure Reducing Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap ©M.E.P.CAD, Inc. tAutoSPRINK® VR5 v5.2.6 06/05/2008 8:31:18AM Page 5 Hydraulic Graph 1 Job Number: KS0407 Report Description: Ordinary Group II Supply at Node 1 150 Static Pressure 140.000 135 120 105 _,542.10 292.10 with hose @ 98.969 streams 90 .N - a _ ai- 75 _ N— co _ 2 _ o_ - 60 -System demand curve 45 30 -9 10900.00 @ 20.000. 15 X011 111111111 1'mull 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 I I I _1_I 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 I.1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 01002200 3300 44005500 6600 7700 8800 9900 11000 Water flow, gpm Hydraulic Graph Supply at Node 1 Static Pressure 140.000 Residual Pressure 10900.00 @ 20.000 Available PressureTime of Test 139.534 @ 542.10 System Demand 292.10 @ 98.969 System Demand (Including Hose Allowance) 542.10 @ 98.969 (b� ©M.E.P.CAD, Inc. 11 AutoSPRINK® VR5 v5.2.6 06/05/2008 8:31:22AM Page 6 €99 Flow Diagram (Top View) Job Number: KS0407 Report Description: Ordinary Group 11 �t ©M.E.P.CAD, Inc. tl AutoSPRINK® VR5 v5.2.6 06/05/2008 8:31:25AM Page 7 EARLY MORNING FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET NUMBER SHEET TITLE FA -01 SYSTEM INFORMATION FA -02 TYPICAL DETAILS - WIRING AND MOUNTING FA -03 FIRE ALARM SYSTEM FLOOR PLAN FA -04 SYSTEM CALCULATIONS (GENERAL), RISER, SITE PLAN T © Without Comments EX As Noted in Red a Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards. Acceptance is subject to errors and Omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings after this date will vold this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and Inspe4ion by The Tukwila Fire Prevention Bureau. oaate:_._By: ( �•4 GO de+ecA- r 40�e i115441t{ci (rear kto-At A ares. 4%1%4 645r•. is cpui(i L'i+�es tLtlW1 A FtitE GPEPART Please cal I : 575.4407 and give this job No. 09 -I �o and exact address for shut. town or rust ,ration so roi L NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection System§. Failure of test will result in a Re -inspection Fee artd termination of the testing. WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATION SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIAT❑R TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATI❑N LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE TWO 600V #12 AWG THHN/THWN TWO 600V #14 AWG THHN/THWN TWISTED TWO CONDUCTOR 300V #18 AWG FPL TW CABLE CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF CONDUIT SIZE MAXIMUM F 1/2" .12 SQUARE 3/4" .21 SQUARE 1" .34 SQUARE 1-1/4" .60 SQUARE 1-1/2"82 SQUARE 2' 1.34 SQUARE FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM DIMENSIONS AREA .244 O.D. .0467 .210 O.D. .0346 .156 O.D. .0191 FROM THE TABLE FILL DIMENSION FROM THE WIRE. LL NCH NCH NCH NCH NCH INCH N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48' A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY SYMBOL DESCRIPTION 2 MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S DEEP VERIFY IN FIELD a DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD 1 0 1 3 1 1 EX CONVENTIONAL CARBON MONOXIDE DETECTOR CODET 12-24 SIEMENS 4S DEEP BOX ® SMOKE DETECTOR (ADDRESSABLE -PHOTO) HFP-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING 12" A.F.F. INSTALLED BY OTHERS CEILING DDUCT DETECTOR SMOKE AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING sc FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 4S DEEP BOX W/ 1-1 /2" EXT. CEILING 80" A.F.F. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1 /2" EXT. CEILING C FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING FIRE ALARM © STROBE (WALL MOUNT) FIRE ALARM SPEAKER (CEILING MOUNT) 4 c ZR -MC --W SIEMENS 4S BOX W/ 1G RING SET -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM CEILING U.O.N. WP FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) MR MULTI -VOLTAGE CONTROL RELAY SET -W SET -S17 -WP MR -201 /C SIEMENS SIEMENS AIR PRODUCTS 4S DEEP BOX W/ 1-1 /2" EXT. 80" A.F.F. TO BOTTOM MT -SUR -BOX 1 /2" PIPE VERIFY IN FIELD 4S BOX VERIFY IN FIELD 0 MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD O JUNCTION BOX F.B.D. F.B.O. N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A U.O.N. UNLESS OTHERWISE NOTED N/A N/A N/A N/A WP WEATHERPROOF DEVICE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A Copyright PAID AUG -7 2009 Tukwila Fire 0726,-747 vi/o 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-651+5 RELEASE/REVISIONS REV. BY: a a DESCRIPTION SHOP DRAWINGS CO ADDITON PER TUKWILA FIRE DATE to (L) tn 03 Z <<<<< CO CO C5 J 00 <rn Z 111 t�zz J w O CC aC Q W N= H 'CALE: 1/8" = ' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: .0B NUMBER: 1 SHEET FA -01 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT �.. DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR SE PREVI❑US ADDRESSABLE DEVIL 0 DUCT DETECTOR L❑CATION END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH 1 0 GROUND -0 r() HTRI—R OSTATUS LED Co CO 0 0 0 N.O. COM N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL O LABEL SCALE NOTE 11 VOLTAGE MAX. - CURRENT MAX. - CONT. RES. MAX. - MAX. CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN. LINE SIZE- (BACKGOUND MUSIC SHUTDOWN) 27 VDC 3.5 rrA DURING POLLING 10 OHMS 200 FT. (18 AVG) 0.02uF 0.04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST 25 SEC. TO GUARANTEE DETECTI❑N. PREVI❑US ADDRESSABLE[+ DEVICE TO NEXT ADDRESSABLE C+ DEVICE _ L 0 TB1 0 0 0 0 123456 HCP TB2 00 65 4321 MUSIC OUTLET SAMPLING, TUBE INLET SAMPLING - TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE I -AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE f STOP IF LAST DEVICE 1(-) FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVICE (-) END OF LINE DEVICE (3.6K 1/4W) SUPERVISED... SWITCH RELAY CONTACTS (4.0A @ 125VAC) GROUND (4.0A @ 30VDC) 0 OND N AC r on 00 El 0 PAD -3 0 oo� INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - Li Li 24K TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE NOTE: 0 7 0 m rr) LO HTRI—D STATUS LED 00 0 NOT USED 0 O FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) DATA OUT TO PANEL L+ DATA IN END OF LINE DEVICE 3.6K 1/4W) 1SUPERVISED SWITCH OVEN FAN CONTACTS NCNO C O 0����—Q VVV 32) END OF LINE DEVIC NAC-4 SUPERVISED SWITCH--- 2 NAC -3 NAC -2 2 NAC -1 1,0 0 0 GROUND NOT SHIELD FAN SHUTDOWN SCALE=NONE N J 0 0 HTRI—R STATUS LED N.O. COY 0 N.G FRONT VIEW 1 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE + DEVICE LOOP NOT USED REMOTE DEVICE LOOP • 0 0 0 0 0— FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY ('S' CABLE) 470 OHMS EOL TS M-1 • 0 O 0 • 0 0 0 e TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE: NONE FROM FACP (V❑ICE CIRCUIT) ('V' CABLE) (S (-) STROBE SPEAKER 0 O EARTH GROUND -0.(+)TO NEXT DEVICE OR >(-) STOP IF LAST DEVICE ( STROBE( -) STROBE SPEAKER (+) ( ) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY 80" A.F.F. R 1.4 O O 4S DEEP BOX W/ 1-1/2" i EXTENSION RING 1(SPEAKER STROBE) 4S BOX ((STROBE ONLY) SPEAKER/STROBE TO NEXT DEVICE OR END OF LINE TO NEXT DEVICE OR END OF LINE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER TIN TEMPERATU E: +32' F (0' c) TO 100' F (338' C) HUMIDITY: NON -CONDENSING HUMIDITY, SIVG HFP-11 SMOKE DETECTOR —> FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (-) > DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR �............ DB -11 I STANDARD SMOKE DETECTOR BASE REAR VIEW NFP -11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT DEVICE > (-) DATA OUT > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID - HARD LID CEILING SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP B❑X.._._....-_ WITH 1-1/2' EXTENSI❑N �\ CEILING MOUNTED SPEAKER/STROBE N CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTION BOX MOUNTED ON CEILING. FLEX 0 0 H TO NEXT DEVICE / / / / / / / JUNCTION BOX ---- MOUNTED - MOUNTED AGAINST \ / CEILING SUPPORT \ / 0 0 -CADDY BAR SMOKE DETECTOR.—" SMOKE ETECT❑R -- SMOKE DETECTOR MOUNTING SCALE:NONE -- SUSPENDED ILLUMINATED CEILING DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. rC) co 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z Q z d DESCRIPTION SHOP DRAWINGS CO ADDITION PER TUKWILLA FIRE Lu I— Q o 5/15/08 rn 10 O 0o CIO OD Q 0) 2 2z z1WF- f�'zz C) w _ cc L OD LU C 1-- z �CALE: 1 /8"= 1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/12/08 BACKROUND PLAN PROVIDED BY: `JOB NUMBER: SHEET Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved FA -02 J EOL EOL—S1 191'i.84V 2S,2V 2S,2V 75 2S,2V 75 2897 WESTFIELD SOUTHCENTER MALL A SCALE II8•=1' FLAG NOTES: 4› - FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS.(SEE SIEMENS INSTALLATI❑N SUBMITTAL FOR L❑CATI❑N GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR. SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. ALARM SIGNAL TO ALARM SYSTEM WILL BE SUPERVIZ❑RY. SUPERVIZED CARBON M❑N❑XIDE SENSOR AND SHUTDOWN THE OVEN TO OVEN FAN CONTROL TERMINALS DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z d NYI DESCRIPTION SHOP DRAWINGS CO ADDITION PER TUKWILLA FIRE DATE 5/15/08 a) 0 co 0 ao 2CCCCC co co 7.1 Z Lij wFZ WZ 0 �_ cc JQ �'S wO CC eC W N= 1-- ` -CALE: 1 /8"=1 DRAWN BY: LAN DERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: .JOB NUMBER: 1 FA -03, Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved i /11111 • 1 :::::::.: _- I NORTH i. O O 0 0 EARLY MORNING WESTFIELD SOUTHCENTER MALL itt Lik-01AORNING SCALE 1132":V �2s,2V Id 75 C 75 L 2s,2Vn, 2s,2V 2s,2Vn 2S,2V L 15 15 C 75 EOL -S1 FA -BOX EX FACP 2I SYSTEM CALCULATIONS BATTERY SIZING CALCULAT ON PROJECT: Notification Appliance Circuit Detail WESTFIELD SOUTHCENTER MALL I Wire Resistance 1.62 CURRENT TOTAL= 653 Panel: EARLY MORNING Date: August 6, 2009 CIRCUIT: S1 Device Type Alarm Current Alarm Total 1 1 SET -MC @15CD SET -MC @30CD 3 !SET -MC @75CD SET -MC @110CD 0 SET-HMC-C@115CD 641 981 233; 318; SET-HMC-C@177CD 4451 SET -HMC @135CD 318' SET -HMC @185CD 445! 641 1..__ .____... Z-MC@15CD 0 Z-MC@30CD 0 SET-MC-CW@110CD DEVICES= 5 PROJECT: Panel: EARLY MORNING Date: August 6, 2009 CIRCUIT:,SPEAKER CIRCUIT 64 Wire Size Wire Length Voltage at EOL Circuit Total 0 525 0 Total Wire Resistance ( R ( WL * 2 )* (R/ft) Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E) (E= I * R) EOL Voltage_ (20.4 - E) 64 981 0 2331 0 TOTAL mA=1 653 12 265 19.8393342 Notification Appliance Circuit Detail WESTFIELD SOUTHCENTER MALL QTY Device Type 4 70.7V 1/8 Wire Resistance 2.58 CURRENT TOTAL= 7.2 !Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL 7.2 Circuit Total ' 0 Total Wire Resistance R 0 0 DEVICES= 4 (Total Cct Load) Voltage Drop ( E) M^ -^- (E= 1 * R) EOL Voltage (20.4 - E)_____ 2.92 0.01 0.02 20.38 0 14 565 20.379009121 7.2 1,0 co 0' 0 z 11.1 LU (1)0 w C) FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS (REV. BY: I EARLY MORNING EARLY MORNING DESCRIPTION FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations DATE oo co on co '-o Current Load: in Standby: Alarm: Current Load: o CCCCC Standby: Alarm: Device Type Qty Amps Total Amps Total Device Type Qty Amps Total Amps Total HFP-11 0.0022 0.0022 0.0023 AD2-P 1 0.0635 0.0635 0.064 0.064 Main System Board 1 0.03 0.03 0.030 • .030 HTR -R CO -DET 2 0.009600 0.0096 0.021 0.042 SET -MC @15CD 1 0.064 0.064 1 0.006000 0.006 0.03 0.030 SET -MC @30CD 0.098 SET -MC @75CD 3 0.175 0.525 SET -MC @110CD 0.233 SET HMC-C@115CD 0.318 SET HMC-C@135CD 0.318 0.0791 Amps 0.136 Amps SET HMC-C@185CD 0.445 ZR -MC @15CD ZR -MC @30CD 1 0.064 0.064 Standby Current Load: 0.0791 Amps For 24 Hours = 1.898 Amp -hours 0.098 HCP 0.0015 Alarm Current Load: 0.136 Amps For 5 Minutes= 0.011 Amp -hours 0.03 Amps 0.683 Amps 25% Derating= 2.387 Amp -hours Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours Alarm Current Load: 0.683 Amps For 5 Minutes= 0.057 Amp -hours Total System Current Load: 2.387 Amp -hours 25% Derating= 0.972 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.972 Amp -hours I Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULAT ON PROJECT: Notification Appliance Circuit Detail WESTFIELD SOUTHCENTER MALL I Wire Resistance 1.62 CURRENT TOTAL= 653 Panel: EARLY MORNING Date: August 6, 2009 CIRCUIT: S1 Device Type Alarm Current Alarm Total 1 1 SET -MC @15CD SET -MC @30CD 3 !SET -MC @75CD SET -MC @110CD 0 SET-HMC-C@115CD 641 981 233; 318; SET-HMC-C@177CD 4451 SET -HMC @135CD 318' SET -HMC @185CD 445! 641 1..__ .____... Z-MC@15CD 0 Z-MC@30CD 0 SET-MC-CW@110CD DEVICES= 5 PROJECT: Panel: EARLY MORNING Date: August 6, 2009 CIRCUIT:,SPEAKER CIRCUIT 64 Wire Size Wire Length Voltage at EOL Circuit Total 0 525 0 Total Wire Resistance ( R ( WL * 2 )* (R/ft) Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E) (E= I * R) EOL Voltage_ (20.4 - E) 64 981 0 2331 0 TOTAL mA=1 653 12 265 19.8393342 Notification Appliance Circuit Detail WESTFIELD SOUTHCENTER MALL QTY Device Type 4 70.7V 1/8 Wire Resistance 2.58 CURRENT TOTAL= 7.2 !Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL 7.2 Circuit Total ' 0 Total Wire Resistance R 0 0 DEVICES= 4 (Total Cct Load) Voltage Drop ( E) M^ -^- (E= 1 * R) EOL Voltage (20.4 - E)_____ 2.92 0.01 0.02 20.38 0 14 565 20.379009121 7.2 1,0 co 0' 0 z 11.1 LU (1)0 w C) FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS (REV. BY: I Z DESCRIPTION SHOP DRAWINGS CO ADDITION PER TUKWILLA FIRE DATE oo co on co '-o in CO o CCCCC coo Q 0) Z 1 -CC Wo (1)Z Z O 2 L_ CC J w O� Cn W ND 1- 3 W z w C/) z O -J 0 W F- >- VJ / �CALE: 1/8"=1' DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE: 5/12/08 BACKROUND PLAN PROVIDED BY: RISER DIAGRAM VOLTAGE DROP CALCULATION FA -04 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved �013 NUMBER: SHEET 1 2897 FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET \UM3ESHEET TITLE FA -01 SYSTEM INFO MATT O \ FA -02 TYPICAL DETAILS - WRI\G A\D V 0„\TI\C FA -03 FRE ALA VI SYSTEM FLOG LA \ FA -04 SYSTEM CALCULATIO\S (GE\EAL), �ISE�, SITE PLA\ WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATI❑N TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED • .210 0.0. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT DF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED, NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO 'CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM ;SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 3 1 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP ® INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D` SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD �"1 LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD La SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING DUCT SMOKE p DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-1 i W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE C (CEILING MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE C (CEILING MOUNT) SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING C FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -1 -CW SIEMENS 4S BOX W/ 1G RING CEILING L FIRE ALARM STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. YC FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING B AWP FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -S17 -WP SIEMENS MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD MR MULTI -VOLTAGE CONTROL RELAY MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JB❑X FIRE ALARM TERMINAL CABINET JUNCTI❑N BOX F.B.O. F.B.O. F.B.O. F. B.0: CCETED VERIY IN TLD VERIFY IN FtELD A.F.F. ABOVE FINISHED N/A N / A Without Corints N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A t: OE Cal CO3 C4 CC 114:D 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS m LU z DESCRIPTION SHOP DRAWINGS W F- a 0 0 u� C co J 00 w EEO � F- (3 I``•� Z Z W 1 -E C4I Q cc ND NOTICE d, signed, Tukwila' �artment Pre-test must be presented Inspector prior to ement of Acceptances of any Fire Alarm etection Systems. of test will result spection Fee and termination of the testing. fU$WILA FIRE DEPARTNIElit Please call: 575-4402 and give this job No. and exact address for shut= gown or restoration approval' RECEIVED JUN - 3 2008 T vela Fire abov-d- Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved J SCALE: 1 /8"=1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: JOB NUMBER: SHEET FA -01 LuuiN As -Noted In Red F.B.D. FURNISHED BY OTHERS N/A N/A ❑ Per The Attatiled Letter N/A The Tukwila Fire N/A NOTN/A APPLICABLE i nese plans have beef ieviewed by Pk,Qntion Bureau for confit nce with current citvN/A standards. Acceptance is sublet to errors and A Complete - - U.D.N. UNLESS OTHERWISEomissions NOTED N/A which do not autitut ize violations of adopted sMrrd�rus and orcinances.NVt responsibility for the/A adequacy of design rests totally with the designer. WP WEATHERPROOF DEVICE N/A A�d,�di ions, •e a Ions or reels • . - - • - - t11ti tate will void this.acce�t/aftce and will require aN/A resubmittal of revised drawings for subsequent approval. Certificat to the commenc Testing and D Failure in a Re -ii RED AS BUILT ADD ❑R CHANGE N/A I afacceptance is subjedtf&fiietd test and inspectiglxrby The Tukwila Fire Prevention Bureau. GREEN AS BUILT REMOVE N/A a E/A CX) N/A Date BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A t: OE Cal CO3 C4 CC 114:D 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS m LU z DESCRIPTION SHOP DRAWINGS W F- a 0 0 u� C co J 00 w EEO � F- (3 I``•� Z Z W 1 -E C4I Q cc ND NOTICE d, signed, Tukwila' �artment Pre-test must be presented Inspector prior to ement of Acceptances of any Fire Alarm etection Systems. of test will result spection Fee and termination of the testing. fU$WILA FIRE DEPARTNIElit Please call: 575-4402 and give this job No. and exact address for shut= gown or restoration approval' RECEIVED JUN - 3 2008 T vela Fire abov-d- Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved J SCALE: 1 /8"=1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: JOB NUMBER: SHEET FA -01 ( THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABa SCALE COMBINE ALL SHIELDS AND IS❑LATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE. v � o DUCT DETECTOR LOCATI❑N FROM XLS CONTROL PANEL OR if PREVIOUS ADDRESSABLE DEVIC END OF LINE DEVICE<3.6K 1/4W) SUPERVISED SWITCH eT O m GROUND �r- 0 HTRI—R OSTATUS LED 00 1-. CO 0 O O N.O. COM N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. O TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE DEVICE TO NEXT ADDRESSABLE DEVICE + NOTE 1: VOLTAGE MAX. - CURRENT MAX. - CONT. RES. MAX. - MAX. CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX, LINE SIZE - MIN, LINE SIZE - MUSIC OUTLET SAMPLING- \ TUBE INLET SAMPLING TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE 1} -AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE {(+j FROM XLS CONTROL PANEL OR .[(+) PREVIOUS ADDRESSABLE DEVICE (-)-1 RELAY CONTACTS C4.OA @ 125VAC) (4.0A @ 30VDC) 27 VDC 3,5 mA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0.02uF 0.04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST 25 SEC, TO GUARANTEE DETECTI❑N. 0 TB1 S 0 m 0 0 123456 HCP TB2 0 0 0� -+- 654321 END OF LINE DEVICE (3,6K 1/4W) O -Q SUPERVISED_____�� SWITCH GROUND NOTE: ; i ; O HTRI—D OSTATUS LED 00 m 0 1 NOT USED O FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC 1 T 0 PAD -3 0 00 O INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 24K n TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE NAC -4 NAC -3 2 NAC -2 NAC -1 END OF LINE DEVICE 3.6K 1/4W) UPERVISED SWITCH r FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE + DEVICE LOOP NOT USED REMOTE �I.. DEVICE LOOP 0 0 0 FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY C'S' CABLE) FROM FACP <VOICE CIRCUIT) C'V' CABLE) 470 OHMS �YV EOL TEM -1 0 0 SMC O 0 9C CI c0 TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE NOW () STROBE SPEAKER (+) (-) u � ( STROBE-) EARTH GROUND -->(+)TO NEXT DEVICE OR >(-) STOP IF LAST DEVICE () STROBE SPEAKER SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE F OR STROBE ONLY RI 80" A.F.F. 4S DEEP BOX W/ 1-1 /2" EXTENSION RING (SPEAKER SIHOBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE TO NEXT DEVICE OR END OF LINE TO NEXT DEVICE OR END OF LINE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER 11N TEMPERA1U E: +32' F 0' C) TO 100' F 38' C) HUMIDITY: 933% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR —� FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE fDATA IN ( ) >- DATA IN (+) > DEVICE IS USTED FOR NR VOLOCITY APPUCATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE __ TO NEXT DEVICE E— > ( ) DATA OUT > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID —� CEILING HARD LID ---� ------SPEAKER SUPPORT TILL BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSI❑N \ CEILING MOUNTED SPEAKER/STROBE -N. CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTI❑N BOX— MOUNTED ON CEILING( FLEX \ 45 JUNCTI❑N BOX ---- MOUNTED AGAINST CEILING SUPPORT 0 0 IL TO NEXT DEVICE -----CADDY BAR SMOKE DETECTOR------ SMOKE ETECT❑R— SMOKE DETECTOR MOUNTING SCALE=NONE SUSPENDED ILLUMINATED CEILING DO N O T IN ADDRESSA DEVICES U\ PREDROC: A DVICES AD ST _L LE T TI_ \VIED W DHSS. AT UC TH Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved v 06:5% fA cocat 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: NVI DESCRIPTION SHOP DRAWINGS DATE 0 in to (9 aa«CC ‘CALE: 1 /8"=1 0 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE:5/12/08 BACKROUND PLAN PROVIDED BY: `JOB NUMBER: J SHEET FA -02 \ \ t\.\. \. \\ \ EQL—S1 1 .84V • 2891 WESTFIELD SOUTHCENTER MALL SCALE 118'14 LAG NO ES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATION SUBMITTAL FOR L❑CATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR, SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM, FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NOT INS O A_L ADDRESSABLE N DEVICES ,INTI PREFROGRAVME DEVICES ADDRL (THAT NG D WITH SS. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved Cia z (,)C#3iu z 46 Zit z FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS CO W 0 E- < o Ln CO CO JJ CO Q 2 Z cc WO I` Ci) Z Z 2 N Q -‹ CC CVD 1— SCALE: 1 /8"=1 DRAWN BY: !.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: �OB NUMBER: SHEET FA -03} NORTH 2897 WESTFIELD SOUTHCENTER MAIL SCALE 1132"=1' D D 75 C 75 15 15 C 75 EX SYSTEM CALCULATIONS BATTERY SIZING CALCULATION 2897 2897 FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations z 0 I - a_ CC U CO w 0 PROJECT: WESTFIELD SOUTHCENTER MALL uJ F- <4 0 5/15/08 2897 Wire Resistance 1.62 9 Panel: June 2, 2008 CURRENT TOTAL= 653 Current Load: Standby: Alarm: S1 Current Load: Standby: Alarm: QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Volta_ ge at EOL Circuit Total Total Wire Resistance (R) 0.86 1 SET -MC @15CD 64 Device Type Qty Amps Total Amps Total Device Type Qty Amps (WL*2)*(R/ft) Total Amps Total 175 HFP-11 0.0022 0.0022 0.0023 Total Device Load, Amps (I) 0.65 0 SET -MC @110CD 233 0 AD2-P 1 0.0635 0.0635 0.064 0.064 _ Main System Board 1 0.03 0.56 0.03 0.030 0.030 0 HTR -R 2 0.009600 0.0096 0.021 0.042 0. SET -MC @15CD 318 1 0.064 0.064 EOL Voltage HTRI-D 0 SET -HMC @185CD 0.001600 0 0.0035 SET -MC @30CD (20.4 - E) 1 Z-MC@15CD 0.098 64 ICP -B6 0.005 0 Z-MC@30CD SET -MC @75CD 0 3 0.175 0.525 0 SET-MC-CW@110CD 233 0 19.83933421 653 SET -MC @110CD DEVICES= 5 TOTAL mA= 653 0.233 265 Amps SET-HMC-C@115CD SET HMC-C@135CD SET HMC-C@185CD ZR -MC @15CD ZR -MC @30CD HCP 1 _ PROJECT: 0.318 0.318 0.445 0.064 0.098 0.0015 0.064 2877 Wire Resistance 2.58 Panel: June 2, 2008 0.0731 Amps 0.106 Date: CIRCUIT: SPEAKER CIRCUIT 1.754 Amp -hours Standby Current Load: 0.0731 Amps For 24 Hours = Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total Alarm Current Load: 0.106 Amps For 5 Minutes= 0.009 Amp -hours - Total Wire Resistance (R) 2.92 0.03 Amps 0.683 Amps (WL*2)*(R/ft) 0 0 0 Total Device Load, Amps (I) 0.01 0 0 25% Derating= 2.204 Amp -hours Standby Current Load: 0.03 Amps 0 For 24 Hours = 0.720 Amp -hours Voltage Drop ( E) 0.02 0 0 ; (E= I * R) 0 0 0 - ! Alarm Current Load: EOL Voltage 0.683 Amps For 5 Minutes= 0.057 Amp -hours Total System Current Load: 2.204 Amp -hours 0 0 0 0 0 0 i DEVICES= 25% Derating= 0.972 Amp -hours 14 Battery Pair to be Used: 20.379009121 7.2 12VDC Amp -hours 7AH Total System Current Load: 0.972 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULATION z (#) z cc izzz O 0' 0' co N 0 O N X La Ln 10 N N .0 O N J Lu cn z 0 (1) Lu w CO w J W CC REV. BY: z a Notification Appliance Circuit Detail z 0 I - a_ CC U CO w 0 PROJECT: WESTFIELD SOUTHCENTER MALL uJ F- <4 0 5/15/08 2897 Wire Resistance 1.62 9 Panel: June 2, 2008 CURRENT TOTAL= 653 Date: CIRCUIT: S1 QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Volta_ ge at EOL Circuit Total Total Wire Resistance (R) 0.86 1 SET -MC @15CD 64 64 0 SET-MC@30CD 98 0 (WL*2)*(R/ft) 3 SET -MC @75CD . 175 525 Total Device Load, Amps (I) 0.65 0 SET -MC @110CD 233 0 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 _ Voltage Drop (E) 0.56 0 SET-HMC-C@177CD 445 0 (E= I * R) 0. SET -HMC @135CD 318 0 EOL Voltage 19.84 0 SET -HMC @185CD 445 0 (20.4 - E) 1 Z-MC@15CD 64 64 0 Z-MC@30CD 98 0 0 SET-MC-CW@110CD 233 0 19.83933421 653 DEVICES= 5 TOTAL mA= 653 12 265 Notification Appliance Circuit Detail _ PROJECT: WESTFIELD SOUTHCENTER MALL 2877 Wire Resistance 2.58 Panel: June 2, 2008 CURRENT TOTAL= 7.2 Date: CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 4 70.7V 1/8 1.8 7.2 Total Wire Resistance (R) 2.92 0 0 - 0 (WL*2)*(R/ft) 0 0 0 Total Device Load, Amps (I) 0.01 0 0 0 (Total Cct Load) 0 - 0 0 Voltage Drop ( E) 0.02 0 0 ; (E= I * R) 0 0 0 - ! EOL Voltage 20.38 0 0 0 (20.4-E) 0 0 0 0 0 0 i DEVICES= 4 TOTAL mA= 7.2 14 565 20.379009121 7.2 z (#) z cc izzz O 0' 0' co N 0 O N X La Ln 10 N N .0 O N J Lu cn z 0 (1) Lu w CO w J W CC REV. BY: z a z 0 I - a_ CC U CO w 0 SHOP DRAWINGS uJ F- <4 0 5/15/08 9 CaCCC co co co<0) 2Z WO N. (I)ZZ CO �U� CV Q W� CE co CV D 1 -- 5 0 w F- CD w CC w z w Cl) z 0 -J 0 w CI) (SCALE: 1/8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: JOB NUMBER: RISER DIAGRAM VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc.. All Rights Reserved SHEET FA -04 � VICINITY MAP (Suite#2897 SCAM -NTS General Notes 2897 SHELL SPACE 1. Western States Fire Protection to add new pendent heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to;pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7, The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. EAST RISER DETAIL HYDRAULIC = REFERENCE ONLY NOT TO SCALE SYMBOL LEGEND REVISIONS 30� !Ordinary Group 11'0.20gpm/ft2 for 945.00ft2 j -"::1;7• • PIPE NIPPLE FLEXHEAD SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS MOUNTING BRACKET REDUCING FITTING 5'-0"-A.F.F SUSPENDED T -BAR GRID CEILING TILE Existing Main 0701 e= Existing Main Zone T9 3-i • FIRE SPRINKLERSYSTEM Sprinkler Legend 12'-0"-A.F.F 3 52_9 i 2 -WAY EARTHQUAKE BRACE NO. DESCRIPTION DATE SYM. SIN QTY. K SPRAY ORIF. FIN. TEMP. MFR./MODEL 4 -WAY EARTHQUAKE BRACE R3615 15 5.6 Pendent Chrome 155`F F1FR Semi-Rec APPROVAL: saw FLEXHEAD DETAIL NOT TO SCALE FIG. 90a SWIVEL SWAY BRACE FITTING Cl BRACE PIPE 318' KWIK BOLT (2114' EMBED LENGTH) FIG. 1000 "FAST CLAMP' SWAY BRACE ATTACHMENT LINE PIPE LATERAL LINE RESTRAINTS NON. THREADED BRACE PIPE Remote Area 2897 SHELL SPACE FIG.4A PIPE CLAMP FOR SWAY BRACE 3/E' KWIK BOLT (2114' EMBED LENGTH) FIG. 909 NO.THREAD SWIVEL SWAY BRACE ATTACHMENT ULATERAL BRANCHLINE RESTRAINT chid�.NOt4.THREADED BRACE PIPE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE CALCULATION DESIGN CRITERIA STANDARD NFPA #13-2007 OCCUPANCY CLASS ORD HAZARD 11 MAX. COVERAGE per HEAD 130 Ft' DENSITY .20 GPM 1 Ft' for 945.0 Ft' SPRINKLER Reliable F1FR Semi-Rec ORIFICE 112" K= 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 _ PSI FLOW 10900 GPM AT BASE OF RISER. SYSTEM REQUIRES: 292.10 GPM @ 95.5 PSI At time of Design 12'- 0" CLG. = 37.00% AREA REDUCTION , Ceara ist Or N +d . ?Davies ; l ha:tty 97 City of Tukwila HYDLRAULIC REFERENCE POINT R5415 7 5.6 Pendent White 155`F G4A Concealed CONT. NO.: KS0407 Total = 22 DRAWN BY: Adam Kantner HANGER SYMBOL BRANCHLINE RESTRAINT SPRK ON SHEET: SEE LEGEND SPRK ON JOB: DATE: 06/05/08 Hanger No. 07C HILTI Kwik Bolt III 7-)N/ '_ S HILTI KVR Bok U Orfled Anchor--- / —1 nchor7- "1 \5// / �i Concrete Construction Cut Rod Lgth Rounded to Nearest Inch Rod Coupling All Thread Rod Swivel Ring Pipe Bottom of Concrete to Center Line of Pipe Note on Plan Note on Plan: Hanger Number and 'A' Dimension • HANGER DETAIL NOT TO SCALE t Vanilla Shells 2897 w z 0 PT Without Comments As Noted In Red Per The Attached Letter i nese plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted stanaaras and orainances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings atter this date will void this,acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to fletd test and Inspection by The Tukwila Fire, Prevention Bureau. te•'//2---/e0,413�By: &7cD VICINITY MAP DETAI L Western States Fire Protection Company 7102 180th AVE NE, STE A-105 - REDMOND, WA - 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE/AUSTN/DALLAS/DECATUR / DENVER / DULUTH / HOUSTON /KANSAS CITY LAS VEGAS /MIMIEAPOLIS /PHOENIX I PORTLAND I RAPID CITY/ST. PAUL/ SALT LACE CITY/SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 1'UKWILA FIRE Lth.HAi=i Please call: 575.4407 and give this job and exact address for shut• iLswn or restoration approval. NOTICE Weld stamps must be inspected before pipe is hung. Do not paint piping prior to hydrostatic test approval. Vanilla Shells 2897 Southcenter Mall Tukwila ,Wa 98188 FIRE SPRINKLER SYSTEM -- a SHEET FP -1 OF 1 2303 1 11Tv'tict 2(rD2� Swinerton Builders tY 0 0 1— z 0 U General Notes VICINITY MAP (Suite#2897) SCALE: NTS 2897 SHELL SPACE 1. Western States Fire Protection to add new pendent heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. EAST RISER DETAIL HYDRAULIC REFERENCE : ONLY NOT TO SCALE Existing Main Existing Main Zone T9 !Ordinary Group II'0.20gpm/ft2 for 945.00ft2 a °.<.`:.I Ai 11 I III 0 '\ 44. 1111w''Zill�� oco i Noir' ��Eiii� • - U• iii/ amitomi 11,,,N1111111111tr fN IICP' • 0 -0 0 Em 3-3Y N -1--12,-0"-A.F.F 1 3h t1, tam CIPA81 MI s."4-= 1 1_1- 03. Q I: —0---, [ 18'-0"-A.F.F I ^!V 9` O 0 -3'h o 1 FIRE SPRINKLER SYSTEM 1/8"=V-0" TYPICAL FLEXABLE SPRINKLER CONNECTION:. FLEXHEAD MOUNTING BRACKET PIPE NIPPLE SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS REDUCING FITTING SUSPENDED T -BAR GRID SPRINKLER HEAD CEILING TILE FLEXHEAD DETAIL NOT TO SCALE FIG. 808 SWIVEL SWAY BRACE FITTING 3R' KWIK BOLT „.-- (21/4' EMBED LENGTH) BRAE PIPE FIG. 1000 -'FAST CLAMP" SWAY BRACE ATTACHMENT LINE PIPE LATERAL LINE RESTRAINTS NON -THREADED BRACE PIPE Remote Area 2897 SHELL SPACE CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY CLASS ORD HAZARD II MAX. COVERAGE per HEAD 130 Ft' DENSITY .20 GPM / Ft' for 945.0 Ft' SPRINKLER Reliable F1 FR Semi-Rec ORIFICE 1/2" K= 5.6 WATER FLOW INFORMATION': STATIC 140 RESIDUAL 20 PSI PSI FLOW 10900 GPM AT BASE OF RISER. SYSTEM REQUIRES: 292.10 GPM © 95.5 PSI ' At time of Design 12'- 0" CLG. = 37.00% AREA REDUCTION FIG. 4A PIPE CLAMP FOR SWAY BRACE 3/8' KWIK BOLT (2 114' EMBED LENGTH) FIG. 909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT LATERAL BRANCHLINE RESTRAINT WAN NON -THREADED BRACE PIPE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE Hanger No. 07C HILTI Kwik Bolt III N'/ / HILTI Kwik8°k(1 Drilled Anchor i Cut Rod Lgth Rounded to Nearest Inch Rod Coupling All Thread Rod Swivel Ring Pipe Concrete f Construction Bottom of Concrete to Center Line of Pipe Note on Plan Note on Plan: Hanger Number and 'A' Dimension HANGER DETAIL NOT TO SCALE VICINITY MAP DETAIL NOT TO SCALE 05-53/'3 co N (1) co U) w z 0 Adam Kantner a 0 Swinerton Builders CONTRACTOR SYMBOL LEGEND REVISIONS Sprinkler Legend 2 -WAY EARTHQUAKE BRACE NO. DESCRIPTION DATE SYM. SIN QTY. K SPRAY ORIF. FIN. TEMP. MFR./MODEL 4 -WAY EARTHQUAKE BRACE R3615 15 5.6 Pendent Chrome 155°F F1 FR Semi-Rec APPROVAL: City of Tukwila HYDRAULIC REFERENCE POINT HANGER SYMBOL R5415 7 5.6 Pendent White 155°F G4A Concealed CONT. NO.: KS0407 Total = 22 DRAWN BY: Adam Kantner BRANCHLINE RESTRAINT SPRK ON SHEET: SEE LEGEND SPRK. ON JOB: DATE: 06/19/08 Western States Fire Protection Company 7102 180th AVE NE, STE A-105 - REDMOND, WA - 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUOUEROUE/AUSTIN ! DALLAS/ DECATUR / DEWERI DULUTH I HOUSTON/KANSAS CITY LAS VEGAS /MINNEAPOLIS / PHOENIX! PORTLAND / RAPID CITY/ ST. PAUL / SALT LAKE CITY/SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 Vanilla Shells 2897 Southcenter Mall Tukwila ,Wa 98188 FIRE SPRINKLER SYSTEM SHEET FP -1 OF 1