08-S-355
FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS
Project Name:
Permit No.:
Date:
Reviewer:
American Express Lounge
3648 Southcenter Mall
08-S355
June 24, 2008
Steve Kohler
Fire Inspector/Plan Review
(206)575-4407
• Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross
mains, and branch lines 2.5" and larger. Bracing is provided for the last length of
pipe but within 6' of the end of a feed or cross main. Bracing is required unless
all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for
any size pipe, 9.3.5.3.
• Minimum clearance around pipes: 2 " for 1 "-3.5", 4" for 4" and larger, see 4
exceptions, 9.3.4.
• Longitudinal sway bracing is a maximum of 80' for mains and cross mains and
within 40 ' of the end of the line, 9.3.5.4.
• Provide lateral and longitudinal bracing for changes in pipe direction per section
9.3.5.11.2 for pipe size 2'h inches and larger.
• Restrain branch lines at the end sprinkler of each line, restrain against vertical
and lateral movement, 9.3.6.3.
• Restraints for branch lines shall be at intervals per table 9.3.6.4 and section
9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6.
• Comply with ASCE 7-02, section 9.6.2.6.2 (e).
• Ceilings used for flex drop attachments shall comply with ASTM C 635 and
ASTM C 636 per section 9.2.1.3.3.2.
• Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a
suspended ceiling, a hanger(s) attached to the structure shall be required to
ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3).
• Provide sprinkler protection beneath all obstructions greater than 4 ft. in width.
• Extend sprinkler protection to all combustible concealed spaces.
• Comply with NFPA 13 obstruction tables.
• Sprinkler heads spaced closer than 6 ft. apart must be baffled.
All references are NFPA 13, 2007 Edition.
BTM OF STEEL
RETAINER STRAP WHERE REQUIRED
IN SEISMIC AREAS
TOP BEAM/ C—CLAMP
WITH SET SCREW
EL =
CLNG GRID SYSTEM
EL = 20'-5"
BTM OF CLOUDS
EL =
•••
NOTE: COORDINATE WITH
MALL EXPANSION SOFFIT AND
CEILING
INTERIOR ELEVATION
SCALE: 1/4" = 1'-0"
/
/
. ,
/ • /
/ .// //
•
—,,
•
••••••
/
.••••/
„
HANGER DETAIL — TOP. CHORD
NTS
•
•
•
•
•
•
„
•
\\
/
/
/
BTM OF STEEL
EL. = 16'-7”
BTM OF SOFFIT
EL. = 12'-0"
TOP OF GLASS
EL. = 10'-0"
0
FINISH FLOOR
EL. = 0P-0"
•••••••••••••••••,•••
JaYaloom•
6' MAX,
3/8' HEX NUT Si
FENDER WASHER
ABOVE AND BELOW
BOTTUM CHORD
3/8' ALL THREAD ROD
PIPE SWIVEL RING
•11
BOTTOM C
STEEL JO
FEED OR CROSS M
(3' OR LARGER)
HANGER DETAIL — BOTTOM CHC
NTS
' I
x
, •
r
X
x .
•
;lig ZN, ;ITN.
ULL
:;-e-tcrTee-La-37:11-e-rih9-nical. Brpncq-1 Connector 177.0.M. WARD
.C.BC=a
•• M- P ..-Trrrr WE=
.34fgai.sej1 rat •iartorr-rr •
FlexHead Sprinkler Drop
//--
20 Suage galvanized Sheet Mll
5:18'
Corrugated stainless steel hose with stainless steel braid
available In 2% 3'.4'$*& 6' legnIhs
-lub section 1G guage galvanized sheet. metal
Sprinkler bleed
Mew SwF/
FLEX HEAD
Design per NFA 13 — Ordinary hazard Occupancy 130 sq ft
All materials to be new, U.L. listed, and F.M. approved
All heads to be a minimum of 6' apart and to be unobstructed by any meal
Upright fire sprinkler heads to remain.
6 — Add Reliable G4A 155° Quick Response Concealed Heads 1/2 x 'A
re7r-r
C '4.540 LI ifIr:.;',1
Without Comments
As Noted In Red
Per The Attached Lotter
I ..rxy I }.4'111
!nese plans have been reviewed by Thc Th:w Fie
Prevention Bureau for cenibrtrience with cuircnt city
standards. Acceptance is ubiect to error,: and
omissions which do not euthoria... violations of2idoptE,,d
standaras and ordinances. The rc.•-;-)onsibility for the r•1
adequacy of design rests totally with the designer.
&Additions, deletions or revisions to these drawings atter •I
this date will void thks.acceptance and will require a
resubmittal of revised drawings for subsequent approval.
Final acceptance is subject to field test and inspection by
The Tukwila Fire, Prevention Bure
By:
NOTICE
Weld stamps must be •
inspected before pipe ig
hung. Do not paint piping
prior to hydrostatic test
TUKWILA FIRE DE.PAR I tvtLet4,
Please call: 575-4407
and give this job
No.
and exact address for shut.
lown or restoration aporov01,
0 \A/ N
FIRE PROTECTION
1N CORP ORA TED
P.O. BOX 12113
MILL CREEK, WASHINGTON 98082-0113
PH. (425) 481-7669
SOUTHCENTER
GLASS BOX
Ai
JUN 2 4 2(01-
(572;61-1/ &)(/ - 55 Tukwila Fire
et L.-, ri 70-.246d-, je(5-6
DATE:. Li 6._,z31)1__iM:,1)4.. I SCALE: " 1
3648 SOUTHCENTER MALL
ASSOCIATED PERMITS
08-S-355
FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS
Project Name:
Permit No.:
Date:
Reviewer:
American Express Lounge
3648 Southcenter Mall
08-S355
June 24, 2008
Steve Kohler
Fire Inspector/Plan Review
(206)575-4407
• Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross
mains, and branch lines 2.5" and larger. Bracing is provided for the last length of
pipe but within 6' of the end of a feed or cross main. Bracing is required unless
all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for
any size pipe, 9.3.5.3.
• Minimum clearance around pipes: 2 " for 1 "-3.5", 4" for 4" and larger, see 4
exceptions, 9.3.4.
• Longitudinal sway bracing is a maximum of 80' for mains and cross mains and
within 40 ' of the end of the line, 9.3.5.4.
• Provide lateral and longitudinal bracing for changes in pipe direction per section
9.3.5.11.2 for pipe size 2'h inches and larger.
• Restrain branch lines at the end sprinkler of each line, restrain against vertical
and lateral movement, 9.3.6.3.
• Restraints for branch lines shall be at intervals per table 9.3.6.4 and section
9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6.
• Comply with ASCE 7-02, section 9.6.2.6.2 (e).
• Ceilings used for flex drop attachments shall comply with ASTM C 635 and
ASTM C 636 per section 9.2.1.3.3.2.
• Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a
suspended ceiling, a hanger(s) attached to the structure shall be required to
ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3).
• Provide sprinkler protection beneath all obstructions greater than 4 ft. in width.
• Extend sprinkler protection to all combustible concealed spaces.
• Comply with NFPA 13 obstruction tables.
• Sprinkler heads spaced closer than 6 ft. apart must be baffled.
All references are NFPA 13, 2007 Edition.
BTM OF STEEL
RETAINER STRAP WHERE REQUIRED
IN SEISMIC AREAS
TOP BEAM/ C—CLAMP
WITH SET SCREW
EL =
CLNG GRID SYSTEM
EL = 20'-5"
BTM OF CLOUDS
EL =
•••
NOTE: COORDINATE WITH
MALL EXPANSION SOFFIT AND
CEILING
INTERIOR ELEVATION
SCALE: 1/4" = 1'-0"
/
/
. ,
/ • /
/ .// //
•
—,,
•
••••••
/
.••••/
„
HANGER DETAIL — TOP. CHORD
NTS
•
•
•
•
•
•
„
•
\\
/
/
/
BTM OF STEEL
EL. = 16'-7”
BTM OF SOFFIT
EL. = 12'-0"
TOP OF GLASS
EL. = 10'-0"
0
FINISH FLOOR
EL. = 0P-0"
•••••••••••••••••,•••
JaYaloom•
6' MAX,
3/8' HEX NUT Si
FENDER WASHER
ABOVE AND BELOW
BOTTUM CHORD
3/8' ALL THREAD ROD
PIPE SWIVEL RING
•11
BOTTOM C
STEEL JO
FEED OR CROSS M
(3' OR LARGER)
HANGER DETAIL — BOTTOM CHC
NTS
' I
x
, •
r
X
x .
•
;lig ZN, ;ITN.
ULL
:;-e-tcrTee-La-37:11-e-rih9-nical. Brpncq-1 Connector 177.0.M. WARD
.C.BC=a
•• M- P ..-Trrrr WE=
.34fgai.sej1 rat •iartorr-rr •
FlexHead Sprinkler Drop
//--
20 Suage galvanized Sheet Mll
5:18'
Corrugated stainless steel hose with stainless steel braid
available In 2% 3'.4'$*& 6' legnIhs
-lub section 1G guage galvanized sheet. metal
Sprinkler bleed
Mew SwF/
FLEX HEAD
Design per NFA 13 — Ordinary hazard Occupancy 130 sq ft
All materials to be new, U.L. listed, and F.M. approved
All heads to be a minimum of 6' apart and to be unobstructed by any meal
Upright fire sprinkler heads to remain.
6 — Add Reliable G4A 155° Quick Response Concealed Heads 1/2 x 'A
re7r-r
C '4.540 LI ifIr:.;',1
Without Comments
As Noted In Red
Per The Attached Lotter
I ..rxy I }.4'111
!nese plans have been reviewed by Thc Th:w Fie
Prevention Bureau for cenibrtrience with cuircnt city
standards. Acceptance is ubiect to error,: and
omissions which do not euthoria... violations of2idoptE,,d
standaras and ordinances. The rc.•-;-)onsibility for the r•1
adequacy of design rests totally with the designer.
&Additions, deletions or revisions to these drawings atter •I
this date will void thks.acceptance and will require a
resubmittal of revised drawings for subsequent approval.
Final acceptance is subject to field test and inspection by
The Tukwila Fire, Prevention Bure
By:
NOTICE
Weld stamps must be •
inspected before pipe ig
hung. Do not paint piping
prior to hydrostatic test
TUKWILA FIRE DE.PAR I tvtLet4,
Please call: 575-4407
and give this job
No.
and exact address for shut.
lown or restoration aporov01,
0 \A/ N
FIRE PROTECTION
1N CORP ORA TED
P.O. BOX 12113
MILL CREEK, WASHINGTON 98082-0113
PH. (425) 481-7669
SOUTHCENTER
GLASS BOX
Ai
JUN 2 4 2(01-
(572;61-1/ &)(/ - 55 Tukwila Fire
et L.-, ri 70-.246d-, je(5-6
DATE:. Li 6._,z31)1__iM:,1)4.. I SCALE: " 1