Loading...
HomeMy WebLinkAboutPP - 2600 SOUTHCENTER MALL FC-10 - PANDA EXPRESS - PERMITS AND PLANS2600 SOUTHCENTER MALL FC -10 ASSOCIATED PERMITS 08-F-170 08-F-153 08-S-186 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Panda Express 2600 Southcenter Mall FC-( Permit No.: 08-S-186 Date: May 13, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'/ inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. ItiVithout Comment As Noted In Red Per The Attached Letter I UttwiLA FIRE DEPARTMENT, Please call: 575-4407 and give this job No. 0? "— I(o 1 exact address for shute resp ration aDDrolsal; i hese plans have.` en revi ,;,;ped by The Ti; ;ria Fire Prevention Bureau ;, ccr; ��r.,..<,. e ti current city standards. Accapt::.'L ' to errors and omissions which do r ii_., auth c:r ize violations of adopted standards and o;•:1idhc..: ;. for the adequacy of de. - n r.... _o:*�i• With the designer. Additions, deie ;ons or t't:visiofis Ifo these drawings atter this date will void ti . ;cpti7i ce, 7,nd will require a resubmittal of revised ciruwtngs for subsequent approval. Final acceptance if', subject to field test and inspection by The Tukwila Fire, Prevention Bureau, [Date:.5i0 D By: Weld stamps must be inspected before pipe is hung. Do not paint piping prior to hydrostatic test • al.r'prov,:;!. (E) MALL EXIT/ SERVICE CORR (a STORAGE (NM.) MAL! S AIRS VOID FACE ENIC.) WALK IN COOLER HEX COU?. MIN pr. zero < !'ldwea2 V memi1911.1/Y1Jrordas .1,tri er.s7/I.tMm%,wJ'l.GYJ5taroll11�Y71.G 3 �:s -:l 4 ka.►— MANAGERS STATION GENERAL NOTES 1. Western States Fire Protection to add new pendant sprinklers due to new walls and ceilings being added for the tenant improvement. 2. Sprinklers shall be spaced in accordance with NFPA #13 Ordinary Hazard Occupancy with a 15'-0" maximum distance between sprinklers and a maximum coverage area of 130 sq. ft. per sprinkler. 3. All hangers' assemblies shall be spaced and installed in accordance with NFPA-13 & manufacture's specifications. 4. All new bracbline and arm -over pipe is black schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. FlexHead fire sprinkler assemblies to be used to attach fire sprinklers at ceilings. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work shown. All other areas are not in contract and WSFP is not responsible for existing conditions. REGISTER/ PICK UP SYMBOL LEGEND — — Existing piping New piping -R- — Mech. Tee cut into existing pipe \ Hanger notation see detail O Existing Reliable Upright sprinlder 4t New Concealed pendant sprinkler New Semi -Recessed pendant sprinkler New Dry pendant sprinkler 1 (E) MALL COMMON AREA 4121/4' NORDSTROM *sem Fire Sprinkler Plan Level 2 Scale: 1/4" =1'-0" PANDA EXPRESS SPACE FC -1 - UPPER LEVEL_ AREA :$46SaFr. WESTFIELD SOUTHCENTER GENERAL NOTES 1. Aii design and installation in accordance with NFPA Standards. 2. All materials to be Underwriters Labora- tories Listed and/ or FM approved. a Overhead piping to be black steel confor- ming to specifications of ASTM A795, ANSI / ASTM A53, ANSI B3 .10M, ASTM A135. HYDRAULIC DESIGN INFORMATION SYSTEM DESIGN REVISIONS SPRINKLER LEGEND PANDA EXPRESS NORTH DESCRIPTION SYMBOL DESCRIPTION APPROVAL G i 4 o-Fm1L ,ik FINISH NQ.REQ. SYMBOL DESCRIPTION STATIC FINISH NO. REQ. DENSITY MAX.ARENHEAD K -FACTOR RESIDUAL GPM FLOWING DATE & TIME ge.1 fable FIFg ay./ 6rA s Re..1►abt.e F3QZ cow. NO KS O377 DRAWN BY k..).21-1 SPICK. ON SHEET I Z SPRK. ON JOB 7102 - 180th AVE NE, SUITE A-105 • REDMOND, WA • 98052 WESTERN STATES FIRE PROTECTION COMPANY—OFFICES LOCATED DENVER / RAPID CITY / MINNEAPOLIS / DULUTH / DALLAS / HOUSTON ALBUQUERQUE f AUSTIN / SEATTLE / PORTLAND f PHOENIX / KANSAS CITY / ST_ LOUIS Phone 206-881-0100 WA. Reg. # WESTESF136QF Westfield Southcenter 2600 Southcenter Mali FC - Tukwila, WA 98188 SHEET Tukwila Fire 00 i$1 -- Job- Napier Pur. r-F-xe ews -rovve System Steel A LL -30/15 Total - FP rea r•tat 16 Hood * 1 7' 00' Long x 48' Vide x 24' fIQI Hood 8 Riser * 1 Sleet 10' x20' 18mn * 1 Job *1 691170 7' 600' Long x 48' Vide x 24' High Sizeu 10' x 20' "\1—�� r --i r--,17-'- ID 0 1 L___T---rr 1' a 41 r T I 1 J J J L 30/,_io" l'ftoftCPRS Mkttithv‘cAL Gifts ‘1141-4 i iN q_2(u) FC -f v -104)J1LA 1.A ') 126 O O %s R e c_eLime- A p r 22. 3: 33 PM L `' ,--mss Y PD'DVG -- — FgLD PIPING n S I-4 I I K i-ce e,A a t4- ".;s1 key- • Lis44I se iv c, 5',4G1 Sc .ee' Deep yew phot Wok j Pe�;�• '-- A6-+%v4o-coh coq °`PP)' i v.e... UM 11 4-w.. o.. Vt.1}',11q.1-tco, 1.7 ,, - 2008 Tukwila Fire 5141304 crl Zti Prie-e WAY S. Sr•�-,-n.c, v 9 i 34 vai (;,ani sc�J 20(2-340-43O° _ b -----1----7+-41-3 4 g ci+o ruvl S11i'ia,a N MLJX+@ J L 30/,_io" l'ftoftCPRS Mkttithv‘cAL Gifts ‘1141-4 i iN q_2(u) FC -f v -104)J1LA 1.A ') 126 O O %s R e c_eLime- A p r 22. 3: 33 PM L `' ,--mss Y PD'DVG -- — FgLD PIPING n S I-4 I I K i-ce e,A a t4- ".;s1 key- • Lis44I se iv c, 5',4G1 Sc .ee' Deep yew phot Wok j Pe�;�• '-- A6-+%v4o-coh coq °`PP)' i v.e... UM 11 4-w.. o.. Vt.1}',11q.1-tco, 1.7 ,, - 2008 Tukwila Fire 5141304 crl Zti Prie-e WAY S. Sr•�-,-n.c, v 9 i 34 vai (;,ani sc�J 20(2-340-43O° /22/2008 06:38 PM Page: 3 Nola - Fire Systems - Parts List Report 4/22/08 2:26 PM Job # 691120 - Panda Express - Tukwila WA (M 1-08-1189) Location: Tukwila, WA Fire System # 1 Ansul R102 ANSUL-3.0/1.5 Tag: Hoods Covered: Hood # 1Hood # 2 Gas Valve(s): QtY Item CAS # Vendor # Description 6 0 METALCAP-CB METALCAP-CB BLOWOFF CAP - Metal Supplied by Ship Dist CAS Inst Loose 0 6 1 1 AT - 1.5 AT - 1.5 TANK(#1A) -1.5 Gallon SS Tank (for use with 1 0 Automan Release, Actuator, or SS Enclosure (UL)) 1 1 AT - 3.0 AT - 3.0 TANK(#1B) - 3.0 Gallon SS Tank (for use with 1 0 Automan Release, Actuator, or SS Enclosure (UL)) 1 2 AP - AR AP - AR AUTOMAN RELEASE - Ansul Automan Mechanical Release (UL) Tank sold separately 1 0 1 3 AP - AE AP - AE ENCLOSURE - Stainless Steel Enclosure 1 0 Assembly (UL) 1 5 LIQ -3.0 79372 AGENT -Ansulex Low PH Wet Chemical Agent, 3 Gallon (UL) 1 0 1 6 LIQ -1.5 79694 AGENT -Ansulex Low PH Wet Chemical 1 0 Agent, 1.5 Gallon (UL) 1 9 101-30 101-30 CARTRIDGE - Carbon Dioxide, 101-30, Double Tank Cartridge (R-102) 1 0 1 10 TLINK TLINK LINK - Test Link Package 1 0 1 11 MICRO -SD MICRO -SD MICROSWITCH - Single Dual Electric Switch 1 0 1 12 HOSEGROMMET 418511 HOSE - Hose/Grommet Package 1 0 2 13 419337 419337 NOZZLE - 2W Nozzle, Duct 0 2 6 16 419335 419335 NOZZLE - 1N Nozzle, Plenum/Appliance 0 6 2 19 419338 419338 NOZZLE - 3N Nozzle, Appliance 0 2 4 25 418569 418569 NOZZLE ADAPTOR - Swivel Nozzle Adaptor 0 4 10 26 QSA-3/8 QSA-3/8 QUIK SEAL - 3/8" (UL) 0 10 1 27 QPSA-1/2 QPSA-1/2 PULLEY SEAL -112" Hood Seal (UL) 0 1 7 28 S -DET S -DET DETECTOR - Series (Scissor Linkage) 0 7 7 30 ANS-500FL ANS-500FL FUSIBLE LINK - 500deg F, R-102 and 0 7 PIRANHA 1 34 RPS -A RPS -A REMOTE PULL STATION - Aluminum (without 1 0 wire rope) 10 35 PE -LT PE -LT PULLEY ELBOW - Low Temp. Pulley Elbow, 10 0 Set Screw Type http://appl.captiveaire.com/Order/FireSystems/PartsListReport.aspx?JobFireSystemld=141393 Page 1 of 2 Received Time Apr.22. 3:33PM /22/2008 06:38 PM Page: 4 Nola - Fire Systems - Parts List Report 4/22/08 2:26 PM 1 36 PE -HT PE -HT PULLEY ELBOW - High Temp Pulley Elbow, 0 1 Compression Type 6 41 SN -CHAR SN -CHAR SINGLE NOZZLE EXTENDED DROP ASSY 0 6 http://appl.captiveaire.com/Order/FireSystems/PartsListReport.aspx?JobFireSystemld=141393 Page 2 of 2 Received Time Apr.22. 3:33PM S'ECTION'IV — SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-28 REV.5 4-1-06 Nozzle Application Chart The following chart has been developed to assist in calculating the quantity and type of nozzle required to protect each duct, plenum, or appliance. NOTICE This chart is for general reference only. See complete details for each type of hazard. Minimum Maximum Hazard Nozzle _ Nozzle Hazard Dimensions Quantity Heights 10 Duct or Transition Length — Unlimited 1 (Single Nozzle) Perimeter — 50 in. (127 cm) Diameter —16 in. (40.6 cm) Duct or Transition (Single Nozzle) Duct or Transition (Dual Nozzle) Electrostatic Precipitator (At Base of Duct) Plenum (Horizontal Protection) 0. Plenum (Horizontal Protection) Plenum (Vertical Protection) Fryer (Split or Non -Split Vat) Fryer (Split or Non -Split Vat) Fryer (Split or Non -Split Vat)* Fryer (Non -Split Vat Only) Length — Unlimited Perimeter —100 in. (254 cm) Diameter — 31 7/8 in. (81 cm) Length — Unlimited Perimeter —150 in. (381 cm) Diameter — 48 in. (122 cm) Individual Cell Length — 10 ft. (3.1 m) Length — 6 ft. (1.8 m) Width —4ft. (12m) Length — 4 ft. (12 m) Width — 4 ft. (1.2 m) Maximum Size (without drip board) 14 in. (36 cm) x 15 in. (38 cm) Low Proximity Maximum Size (without drip board) 14 1/2 in. (37 cm) x 14 in. (36 cm) Medium Proximity Maximum Size (without drip board) 15 in. (38 cm) x 14 in. (36 cm) High Proximity Medium Proximity Maximum Size (without drip board) 191 /2 in. (49.5 cm) x 19 in. (48.2 cm) High Proximity Low Proximity Maximum Size (without drip board) 18 in. (45.7 cm) x 18 in. (45.7 cm) High Proximity 1 1 1 1 1 1 1 1 1 1 1 1 1 ' For multiple nozzle protection of single fryers, see detailed information on Pages 4-12 through 4-14. 13-16 in. (33 — 41 cm) 16 — 27 in. (41 — 69 cm) 27 — 47 in. 20 — 27 in. 21 — 34 in. 13-16 in. 25 — 35 in. (64-89 cm) Nozzle Part No. 430912 419337 419337 419334 419335 430192 419336 419336 419342 419342 419339 419340 419338 419342 419338 Nozzle Tip Stamping — Flow No. 1W 2W 2W 1/2N 1N 1W 1W 1W 290 290 230 245 3N 290 3N Nozzle Application Chart (Continued) Hazard Wood Fueled Char -Broiler Upright Broiler Salamander Broiler Wok Maximum Hazard Dimensions Longest Side — 30 in. (76 cm) Area — 720 sq. in. (4645 sq. cm) Length — 32.5 in. (82.5 cm) Width — 30 in. (76 cm) Length — 32.5 in. (82.5 cm) 2 Width — 30 in. (76 cm) 14 in. — 30 in. (36 — 76 cm) Diameter 3.75 — 8.0 in. (9.5 — 20 cm) Deep 11 in. — 24 in. (28 — 61 cm) Diameter 3.0 — 6.0 in. (8 — 15.2 cm) Deep SECTION IV — SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-31 3-1-04 REV.6 Minimum Nozzle Nozzle Quantity Heights 1 14 — 40 in. (36 — 102 cm) 2 — 1 35 — 45 in. (89 —114 cm) 30 — 40 in. (76 —102 cm) Nozzle Part No. 419338 419334 419334 419341 Nozzle Tip Stamping — Flow No. 3N 1 /2N 1 /2N 260 419335/417332 1 N/1 NSS r„�ovL ru t OMAN Regulated -Mechanical Release Assembly (3.0,gallon — Part No. 79290 cr .1.5 gallon — Pan No. 79291) contains the regulated release mechanism, agent tank. expellant gas hose for agent tank hookup. and enclosure knockouts to facilitate installing actuation piping; expellant piping: detection system; and additional equipment. This regu- lated release assembly is used in single, double, and multiple - tank systems and must be mounted to a rigid surface. The release mechanism can be used to interconnect both the actu- ation and expellant gas lines as required per system design. The regulator is designed to allow a constant flow of gas into the tank at 100 psi (690 kPa) when the system is actuated. In single. double, and multiple -tank systems, the provided expel- lant gas hose connects the agent tank to the bottom outlet of the regulator. In double and multiple -tank system configurations. the back outlet of the regulator is used as an expellant gas feed for one additional tank -enclosure or tank -bracket hookup. The enclosure contains the required knockouts to facilitate this con - rection. If a pressure switch is to be attached to the regulator, additional fittings are required. The tank is mounted within the enclosure. The tank contains an adaptor/tube assembly with a burst disc union: The burst disc helps prevent siphoning of the agent up the pipe due to signifi• - cant temperature fluctuations in the area where the -tank is located. The tank is mild steel and, under normal conditions, requires hydrostatic testing every twelve years. - The agent tank is shipped uncharged and must be -filled with 1.53 gallons (5.8 L) or 3.06 gallons (11.6 L) of only ANSULEX Low pH Liquid Fire Suppressant during installation.. The detection and additional equipment required per system design are connected to'the release mechanism. The enclosure contains knockouts to facilitate detection and additional hookups. The system can ba actuated automatically or manually. Auto- matic actuation occurs when a fusible link within the detection system separates in a fire condition. Manual actuation of the system occurs when personnel pull on the remote manual pull station pull rine. E)C lNGU1SHING AGENT ANSULEX Low pH Liquid Fire Suppressant (1.5 gallon — Part No. 79694 or 3.0 gallon — Part No. 79372) is a potassium -based solution designed forfast knock -down and suppression of grease -related fires. The agent is shipped in plastic containers which provide one complete tank charge. Agent storage life expectancy is twelve years. The distributor must record the batch numbers and date of shipment receipt to be filed with each instal- lation record. Total Flow No' 1-5 Tank Quantity 1 ANSUL Type of System : Tvoe of Hardware Single 1.5 Gal. Reg. Release Single 3.0 Gal. Reg. Release ELECTRICAL SWITCHES — LOC,Pap It3 .EA -CA. I U D The electrical switches are intended for use with_ electric gas valves, alarms, contactors, lights, contractor supplied electric power shut-off devices :and other elect;icai devices that are designed to shut off or tum on when the system is actuated. Switches are available in kits: One Switch Kit, PartNo. 423878 Two Switch Kit, Part No. 423879, Three Switch Kit, Part No. 423880, and Four Swfh Kit, Part No. 423881. Each switch has a set of single -pole, double -throw contacts rated at 21 amp, 1 HP, 125, 250, 277 VAC or 2 HP, 250, 277 VAC. Mounting hardware is provided with each kit. R-102 RESTAURANT FIRE SUPPRESSION SYSTEM (Standard UL 300 Listed) Nozzle Identification Chart Nozzle Nozzle Noz Nozzle Type Part No. Stamoin❑ Roy 1W Nozzle 1WSS Nozzle 1N Nozzle 1NSS Nozzle 1/2N Nozzle 3N Nozzle 2W Nozzle 2WH Nozzle 230 No=Ie 245 Nozzle 260 Nozzle 290 Nozzle 2120 Nozzle 1F Nozzle I t oo 1407 -Ur Nitrogen Cartridge Reouired LT -20-R (7032) LT -30-R (5373) 419336 417333 419335 417332 419334 419338 419337 78078 419339 419340 419341 419342 419343 419333 -460,12 1W 1 1W 1 1N 1N 1/2N 3N 2W 2WH 230 2 245 2 260 2 290 2 2120 2 1F 1 1100 1 1 1/2 3 2 2 Carbon Dioxide Ca :co_D Rern�ired 101-10 (15850) 101-20 (17492) WR et\tiflusT 1:=150 51 -Ms ,SuteLy ktk 5W -1-5E. 5 GS 5 -Pel I ?O (T �q-Ts) u10X- NW> Susi c IF Pf1Ag` F -l0, S t -MS . 15 S v i • SECTION IX - APPENDIX UL EX. 3470 ULC CEx747 Page 9-1 7-1-98 REV. 3 SYSTEM SELECTION GUIDE ' NOTE: System options do not cover all conceivable variations. They are listed here as a general guideline to show the most common type arrangement for multiple systems, Based on certain system designs utilizing manifolding, non-manifolding, 3 -tank systems, etc., other tank/cartridge combinations can be designed. The combinations below are based on 11 flow, 3.0 gallon tanks and 5 flow, 1.5 gallon tanks. More competitive designs may be available by utilizing 12 flow and 6 flow systems when appropriate. Total Tank Type of Nitrogen Carbon Dioxide Cartridge Required Cartridge Required Flow No.* Quantity System Type of Hardware 1-5 1 Single 1.5 Gal. Reg. Release LT -20-R (7032) 101-10 (15850) 7032 6-11 1 Single 3.0 Gal. Reg. Release LT -30-R (5373) 101-20 (17492) 5373 12-16 2 Double 1.5 Gal. Reg.Release Double (73022) 101-30 (15851) 3.0 Gal: Additional Tank 17-22 2 Double 3.0 Gal. Reg. Release Double73022 3.0 Gal. Additional Tank Double(73022) 101-30 (15851)`• 23-27 3 Multiple 1.5 Gal. Reg. Release LT -20-R (7032) 101-10 (15850) 3.0 Gal. Reg. Actuator LT -A-101-30 (29187) 101-30 (15851y- 3.0 Gal. Additional Tank 28-33 28-33 (Optional) 34-38 3 4 39-44 4 45-49 5 50-55 5 56-60 6 Multiple 3.0 Gal. Reg. Release LT -30-R5373 3.0 Gal. Reg. Actuator ( ) 101-20 (1749) 3.0 Gal. Additional Tank Multiple 3.0 Gal. Reg. Release (2) 3.0 Gal. Additional Tanks Multiple 1.5 Gal. Reg. Release 3.0 Gal. A.dditional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank Multiple 3.0 Gal. Reg. Release 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank Multiple 1.5 Gal. Reg. Release 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank Multiple 3.0 Gal. Reg. Release 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank Multiple 1.5 Gal. Reg. Release 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator' 3.0 Gal. Additional Tank 61-66 6 Multiple 3.0 Gal. Reg. Release 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank - Based on 5 flow numbers for a 1.5 gal. system and 11 flow numbers for a 3.0 gal. system. See Pages 4-39 - 4-42 for exceptions. If tanks are man,folded. only a "double tank" nitrogen cartridge (Part No. 73022) can be used. If tanks are manifotded, either an LT -A-101-30 nitrogen cartridge (Part No. 29187) or a double tank cartridge (Part No. 73022) can be used. LT -A-101-30 (29187) 101-30 (15851Y - Double 15851Y- Double (73022) N/A Double (73022) LT -A-101-30 (29187) 101-30 (15851) 101-30 (15851)"' Double (73022) 101-30 (15851)" LT -A-101-30 (29187) 101-30 (15851y - LT -20-R (7032) LT -A-101-30 (29187) LT -A-101-30 (29187) LT -30-R (5373) LT -A-101-30 (29187) LT -A-101-30 (29187) Double (73022) LT -A-101-30 (29187) LT -A-101-30 (29187) Double (73022) LT -A-101-30 (29187) LT -A-101-30 (29187) 101-10 (15850) 101-30 (15851)- 101-30 (15851)- 101-20 (17492) 101-30 (15851)- 101-30 (15851y- 101-30 (15851) 101-30 (15851)' 101-30 (15851)- 101-30 (15851)" 101-30 (15851)"' 101-30 (15851)"' V • • • ACCEPTED O Without Comments As Noted In Red 0 Per The Attached Letter nese plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is :..ubiect to errors and omissions which dc ) -Juhcirize violations of adopted standards and orrrs-; h•-; re wont);Itty for the adequacy of Ne. -1-1 the designer. Additions, ds ri;vi,n100`' thee drawings atter this date will void th:-,5 a.:cizi)tan e'_rd will require a resubmittal of revised dr aA ing li for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. IBy: 11 Date: -0 2 utcwILA FIRE DEPARTMENT, Please call: 575-440Z Ind give this job 0 -1 C3 xact address for shut% or restoration aPorovell FIRE L t---1 SYSTEM TUKWI i .A. WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET NUMBER SHEET TITLE FA -01 SYSTEM INFORMATION FA -02 TYPICAL DETAILS - WIRING AND MOUNTING FA -03 FIRE ALARM SYSTEM FLOOR PLAN FA -04 SYSTEM CALCULATIONS (GENERAL), RISER, SITE PLAN' T- !nese plans have h ;n revib,.: fed by The Tukwila Fire Prevention Buret i It. _.t:, ... s . , ..:: with current city standards. A..ccb pi.? (1C.0',::.:i::'..:.:-.q ,. c=ircrs and Omissions wh;c13 o. i !., Y:" t OfS o1` adopted il Stand sras and -i n,:: .3risib t for the adequacy o , .._ ;i, Me designer. 1 Additions, :""_ :'i; ..).,..._. k;. tht=:;;ti drawings atter , this date wiil void u -.:r-: 9n l vt%i1 require a "f.i.e.subraittaI of rov!;:o 1 r�,' "i, ;Of 2ubsequent approval. Final acc ct"r.i.: ..`'.... ?)....,,-•-...-. ."r F:r.4r. 1.(:.:7.-,t a•nd inspection by The Tukwila ;_ ,.. r C‘.'' .,,; n S'Ji ttLU. Date: 3--- 4 -v0 By: /iJ ACC PTED Wthout Comments As Noted In Red Per The Attached Letter i TUKWILA FIRE DEPARTMt11'1, Please call:. 575.440Z and give this job No. 0,S?-F�l 7 0; and exact address for shut% down or restoration approval; NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) 2S STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #I6 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) 2V SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATI❑N LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATI❑N TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M BOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR: SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT. TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS.. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 9. 10. THE. 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD. DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER 'CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION ,TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 1 1 3 1 SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP. E FIRE ALARM CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD D DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP: CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING DUCT SMOKE ®D, DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM 4S DEEP BOX CEILING W/ 1-1/2" EXT. C; FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING L FIRE ALARM STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. c. FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. FIRE ALARM SPEAKER (WALL MOUNT) SET -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM B WP FIRE ALARM STROBE (WEATHERPROOF) SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR 1 MULTI -VOLTAGE CONTROL RELAY MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD O JUNCTI❑N BOX F.B.D. F.B.O. N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A U.❑.N. UNLESS OTHERWISE NOTED N/A N/A N/A N/A WP WEATHERPROOF DEVICE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A PAI - 2008 Tukwila Fire Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 75 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 RELEASE/REVISIONS REV. BY: Z a DESCRIPTION SHOP DRAWINGS co L1.1 oo z CCCCC 0 z ‘CALE: 1/8"=1' DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE: 5/05/08 BACKROUND PLAN PROVIDED BY: �OB NUMBER:54532 SHEET FA -01 ',, THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT MYTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS DUCT DETECTOR LOCATION p TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT v LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVIC y END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH GROUND 0 r 0 © © HTRI-R OSTATUS LED CO C.0 0 0 0 N.O. COM N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 Am TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL NIP LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE DEVICE TO NEXT ADDRESSABLE r DEVICE L NOTE 1: VOLTAGE MAX. - CURRENT MAX. - CONT. RES. MAX. - MAX. CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN. LINE SIZE - MUSIC OUTLET SAMPLING TUBE INLET SAMPLING TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE 14 -AC POWER SOURCE COMBINE ALL SHIELDS ANDS ISOLATE FROM GROUNDING'.;;'.: TO NEXT ADDRESSABLE DEVICI STOP IF LAST DEVICE FROM XLS CONTROL.. PANEL OR',' PREVIOUS ADDRESSABLE DEVICE (—) (+) (-) (+) RELAY CONTACTS (4.0A @ 125VAC) (4.0A @ 30VDC) 27 VDC 3.5 mA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0.02uF 0.04uF 14 AWG 18 AWG NOTE 2: ALL SUPERVISED• SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTI❑N. IeQI TB1 0 0 0 0 0 123456 HCP TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE END OF; LINE DEVICE'i;;l (3.6K 1'/, 4VJ) 0 SUPERVISED % SWITCH ;; L; NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. -TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL 0 0 0 © HTRI-D STATUS LED 00 0 0 LABEL SCALE (FIRE:SUPPRESSION SYSTEM INTERFACE) - 0 0 GND N AC 0.101E 00 0 00 0 INPUT INPUT TROUBLE NAC1 NAC2. NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - MAIM 11 24K NOT USED END OF LINE DEVICE' 3.6K 1/4W) UPERVXSED 'WITCH it 2 NAC -4 NAC -3 NAC -2 NAC=1. • FRONT MEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE DEVICE LOOP I 0 FROM XLS CONTROL PANEL OR (+), PREVIOUS ADDRESSABLE DEVICE (—)' 470 OHMS AW EOL TS M-1 0 o1 ac ' V (DocO '5 moo C ae000 o 5. CQCO m TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL - SCALE: NONE FROM REMOTE POWER SUPPLY ('S' CABLE) FROM FACP (VOICE CIRCUIT) ('V' CABLE) n r (+) (—) STROBE SPEAKER EARTH GROUND --)r(+)TO NEXT DEVICE OR >(—) STOP IF. LAST DEVICE +) ( ) STROBE (-0 ' () STROBE SPEAKER (+) (—) SPEAKERISTROBE AND STROBE \AIRING LABEL SCALE SPEAKER STROBE F OR STROBE ONLY E 80" A.F.F. 0 0 0 4S DEEP BOX W/ 1-1/2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE=NONE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERAIIN TEMPERA ' +32' F I C) TO 1017 F 3K C) HUMIDITY: % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR —� FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DEVICE IS LISTED FOR AIR VOLOCITY APPUCATIONS OF 300-400D FT IN IIIEIEN USED IN CONJJNCTION %1TH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE DATA IN (—) >— DATA IN (+) > REAR VIEW TO NEXT DEVICE > ( ) DATA OUT } (+) DATA OUT HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE CEILING MOUNT ' SPEAKER/STROBE MOUNTING (HARD LID) 1 TO NEXT DEVICE OR —! END OF LINE, TO NEXT DEVICE OR . END OF LINE HARD LID -- CEILING SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION N CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE=NONE JUNCTION BOX MOUNTED ON - . CEILINGI FLEX \.\ - JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPP❑RT / / / / / / TO NEXT DEVICE' O O CADDY BAR SMOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE=NONE --- SUSPENDED ILLUMINATED CEILING(; Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved.; fa -4 00 0' 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 ( RELEASE/REVISIONS CO LU DESCRIPTION SHOP DRAWINGS w Q 03 0 .Ln 0 z C 1 J 00 (/) CO CI) W W E- z a zo W � �=z W CC = _ Q QOM owryco Z 7 LL am CD (NI ~ CC CO V 4 -74.F - J 0 tSCALE: 1 8"=1' DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE: 5/05/08 BACKROUND PLAN PROVIDED BY: `0B NUMBER:54532 SHEET FA -O2 • , --------------------------------------------------- r ,i r `4-,4=4-7_47-;:::: I/ il 1,1 .1/.. / , 4 ----- / r A ,,,,..4,_ i 1 / , / ; / .,., ; STORAGE / i----1---4 --------, t / EXITi SERVICE KC.) - - I I I / i 1 i I.ssi0-,-zM!g':l:E!- r Ebt,----51• --'1-.-t -rivic:,:ri20.20V I ___------, -- .__ I • r 1 . , I------ ' • MALL STARS 1 N4 I Vi!!!',1 WALK 41 FREEZER I 144 S 75: WAS INa ----- VODSPACE / 31 AFF ---- -------------- CO9UNG 1 Lie . ‘,3 .• , • /' Ei C , . , E2' r•In1r!.-r-.• p- 1 :4 -,--_ ui cm v. a) 10' —0" AFF WALK IN COOLER MANAGERS STATION 12 —10" AFF REGISTER/ PM LIP PANDA EXPRESS WESTFIELD SOUTHCENTER MALL SCALE 118%T • FLAG i\ OTS: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATION SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR, Copyright 2006 by Guardian Security Systems, Inc. All Rights I; • • •:: Reserved !!! 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 RELE.ASE/REVISIONS REV. BY: z <t DESCRIPTION SHOP DRAWINGS DATE 5/5/08 2 ‹<<<< —J —J cC8 co &`;-E; cca) u J2 wz 12P 16(.1 X I UJ 15 en ter 0 < W 0 Z an. D CO I— N LT. 'ALE: 1/8"=1' DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE: 5/05/08 BACKROUND PLAN PROVIDED BY: ...JOB NUMBER:54532 SHEET FA -03 0 NORTH A k, - A 1\ ----- N PANDA EXPRESS WESTFIELDSOUTHCENTER MALL. W,--F-r:------7--\\ 0 \ \\ \ ..--------- 3.1 V\ '1, \ \ k\ , \ ..... A \ ---- - \ 1 1 'I / i SCALE 11374 S,2V Op S,2Ve 113:11:1111 75 C C 75 C EOL -S1 20.20V 2S,2V EX D,I 21 RISER DIAGRAM SYSTEM CALCULATIONS BATTERY SIZING CALCULATION ELD SOUTHC• ENAppliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: PANDA EXPRESS Wire Resistance 1.62 Date: May 5, 2008 CIRCUIT: S1 QTY 1 Device Type 1 SET -MC @15CD ISET-MC,@30CD 2 1SET-MC,@75CD O iSET-MC @110CD 0 SET-HMC-C@115CD CURRENT TOTAL=1414 ' t I i i . . ... .. . . 1 . -,i i Alarm Current i AlarrivTotal i Wire Size Wire Length ', Voltage at EOL Circuit Total ...- O SET-HMC-C@177CD - 0 1SET-HMC @135CD 0 !SET -HMC @185CD 641 •1- 64! Total Wire Resistance ( R ) 0.49 981- ' ol , , . ( WL* 2 )* (R/ft) , ; , 0.41! 175! 350, , , ; Total Device Load, Amps (I) 2331 01 0 , (Total Cct Load) 0.20 I , 318 i 4451 ; Voltage Drop ( E ) 0 0! (E= I * R) : 318! : EOL Voltage 20.201 445 0 i , (20.4 - E) 1Z-MC@15CDillol 0 IZ-MC@30CD 2001 oi 0 isEnMC-cw@i loci) 1 264i 0 ; TOTAL- m A= DEVICES=3 4141 12 151 20.19745464 414 Notification Appliance Circuit Detail PROJECT: ,WESTFIELD SOUTHCENTER MALL Panel: ;PANDA EXPRESS ,Wire Resistance 2.58 Date: May 5, 2008 5 5 CURRENT TOTAL=1'5.4 CIRCUIT: SPEAKER CIRCUIT QTY Device Type - Alarm Current Alarm Total Wire Size i Wire Length 1 Voltage at EOL Circuit Total 3 70.7V 1/8 1.8! 5.41 !Total Wire Resistance ( R ) 0.78' 01 01 , ( WL * 2 )* (R/ft) 0 , . 01 0 1 . . . 1Total Device Load, Amps (I) 0.01 00i 0 , ', . , J , (Total Cct Load) O 0 i 0 Voltage Drop ( E ) ; i 0. 00 0 0 0 i i . If (E= I * R) 1 ; . 0 01 0 , ""- ) EOL Voltage 20.40 (20.4 - E) O 0 0' 0 , 0 0; 0 DEVCES=i3 1 TOTAL mA=1 5.4i 14 ; ,` 151 20.39579254 5.4, 0 0 VOLTAGE DROP CALCULATION 1743 ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 U) z 0 uJ CC LLI U) LLJ LU CC REV. BY: PANDA EXPRESS .':, PANDA EXPRESS FACP ADD ONS ' \t!SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations SHOP DRAWINGS DATE 5/5/08 2 < <<<< Current Load: Standby: Alarm: , Current Load: , Standby: Alarm: 1; Device Type Qty Amps Total Amps Total ., i,, Device Type Qty Amps Total Amps Total , HFP-11 0.0022 0.0022 0.0023 AD2-P 1 0.0635 0.0635 0.064 0.064 :1 Main System Board 1 0.03 0.03 0.030 0.030 I, HTR -R.1 FiT141:15 ----- , ICP -B60.005 ..., _ • . _ .. .... - ---- - - - _ ,. , _.., .. . ...._, ,_, . _. o.009600 0.0096 0.021 0.021 ' ' SET -MC @15CD SET -MC @30CD_ SLT-MC@7666 SET -Via @i1066 - SET-i-iik:odifeD SET-HMC-C@135CD SET:HMC:C@185CD ZR -MC @15CD _ „_. , ZR -MC @30CD.,,, HCP 1 0.064 0.064 1 0.001600 0.0016 0.0035 0.004 ' 0.098 , 2 0.175 0.350 ., 0.233 0.318 0.318 0.0747 Amps 0.0885 Amps 0.445 .,, 0.064 , Standby Current Load: 0.0747 Amps For 24 Hours = 1.793 Amp -hours •, !. 0.098 , . -,, 0.0015 , Alarm Current Load: 0.0885 Amps For 5 Minutes= 0.007 Amp -hours , 0.03 Amps 0.444 AmpS• 25% Derating= 2.250 Amp -hours : Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours .i . Alarm Current Load: 0.444 Amps For 5 Minutes= 0.037 Amp -hours Total System Current Load: 2.250 Amp -hours ' 25% Derating= 0.947 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.947 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULATION ELD SOUTHC• ENAppliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: PANDA EXPRESS Wire Resistance 1.62 Date: May 5, 2008 CIRCUIT: S1 QTY 1 Device Type 1 SET -MC @15CD ISET-MC,@30CD 2 1SET-MC,@75CD O iSET-MC @110CD 0 SET-HMC-C@115CD CURRENT TOTAL=1414 ' t I i i . . ... .. . . 1 . -,i i Alarm Current i AlarrivTotal i Wire Size Wire Length ', Voltage at EOL Circuit Total ...- O SET-HMC-C@177CD - 0 1SET-HMC @135CD 0 !SET -HMC @185CD 641 •1- 64! Total Wire Resistance ( R ) 0.49 981- ' ol , , . ( WL* 2 )* (R/ft) , ; , 0.41! 175! 350, , , ; Total Device Load, Amps (I) 2331 01 0 , (Total Cct Load) 0.20 I , 318 i 4451 ; Voltage Drop ( E ) 0 0! (E= I * R) : 318! : EOL Voltage 20.201 445 0 i , (20.4 - E) 1Z-MC@15CDillol 0 IZ-MC@30CD 2001 oi 0 isEnMC-cw@i loci) 1 264i 0 ; TOTAL- m A= DEVICES=3 4141 12 151 20.19745464 414 Notification Appliance Circuit Detail PROJECT: ,WESTFIELD SOUTHCENTER MALL Panel: ;PANDA EXPRESS ,Wire Resistance 2.58 Date: May 5, 2008 5 5 CURRENT TOTAL=1'5.4 CIRCUIT: SPEAKER CIRCUIT QTY Device Type - Alarm Current Alarm Total Wire Size i Wire Length 1 Voltage at EOL Circuit Total 3 70.7V 1/8 1.8! 5.41 !Total Wire Resistance ( R ) 0.78' 01 01 , ( WL * 2 )* (R/ft) 0 , . 01 0 1 . . . 1Total Device Load, Amps (I) 0.01 00i 0 , ', . , J , (Total Cct Load) O 0 i 0 Voltage Drop ( E ) ; i 0. 00 0 0 0 i i . If (E= I * R) 1 ; . 0 01 0 , ""- ) EOL Voltage 20.40 (20.4 - E) O 0 0' 0 , 0 0; 0 DEVCES=i3 1 TOTAL mA=1 5.4i 14 ; ,` 151 20.39579254 5.4, 0 0 VOLTAGE DROP CALCULATION 1743 ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 U) z 0 uJ CC LLI U) LLJ LU CC REV. BY: z 4 DESCRIPTION SHOP DRAWINGS DATE 5/5/08 2 < <<<< -J -J C° < C° CO CO. U) cc a) w 2 w Z WF -0 CC CL Xi W cc 15cn < o< L.1 Lu CD ,,;" CL 80 (DI- N zrr- co z 0 (1) z0 DRAWN BY: !ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/05/08 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved BACKROUND PLAN PROVIDED 13Y: ..10B NUMBER:54532 SHEET FA -04 j 2600 SOUTHCENTER MALL FC -10 ASSOCIATED PERMITS 08-F-170 08-F-153 08-S-186 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Panda Express 2600 Southcenter Mall FC-( Permit No.: 08-S-186 Date: May 13, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'/ inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. ItiVithout Comment As Noted In Red Per The Attached Letter I UttwiLA FIRE DEPARTMENT, Please call: 575-4407 and give this job No. 0? "— I(o 1 exact address for shute resp ration aDDrolsal; i hese plans have.` en revi ,;,;ped by The Ti; ;ria Fire Prevention Bureau ;, ccr; ��r.,..<,. e ti current city standards. Accapt::.'L ' to errors and omissions which do r ii_., auth c:r ize violations of adopted standards and o;•:1idhc..: ;. for the adequacy of de. - n r.... _o:*�i• With the designer. Additions, deie ;ons or t't:visiofis Ifo these drawings atter this date will void ti . ;cpti7i ce, 7,nd will require a resubmittal of revised ciruwtngs for subsequent approval. Final acceptance if', subject to field test and inspection by The Tukwila Fire, Prevention Bureau, [Date:.5i0 D By: Weld stamps must be inspected before pipe is hung. Do not paint piping prior to hydrostatic test • al.r'prov,:;!. (E) MALL EXIT/ SERVICE CORR (a STORAGE (NM.) MAL! S AIRS VOID FACE ENIC.) WALK IN COOLER HEX COU?. MIN pr. zero < !'ldwea2 V memi1911.1/Y1Jrordas .1,tri er.s7/I.tMm%,wJ'l.GYJ5taroll11�Y71.G 3 �:s -:l 4 ka.►— MANAGERS STATION GENERAL NOTES 1. Western States Fire Protection to add new pendant sprinklers due to new walls and ceilings being added for the tenant improvement. 2. Sprinklers shall be spaced in accordance with NFPA #13 Ordinary Hazard Occupancy with a 15'-0" maximum distance between sprinklers and a maximum coverage area of 130 sq. ft. per sprinkler. 3. All hangers' assemblies shall be spaced and installed in accordance with NFPA-13 & manufacture's specifications. 4. All new bracbline and arm -over pipe is black schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. FlexHead fire sprinkler assemblies to be used to attach fire sprinklers at ceilings. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work shown. All other areas are not in contract and WSFP is not responsible for existing conditions. REGISTER/ PICK UP SYMBOL LEGEND — — Existing piping New piping -R- — Mech. Tee cut into existing pipe \ Hanger notation see detail O Existing Reliable Upright sprinlder 4t New Concealed pendant sprinkler New Semi -Recessed pendant sprinkler New Dry pendant sprinkler 1 (E) MALL COMMON AREA 4121/4' NORDSTROM *sem Fire Sprinkler Plan Level 2 Scale: 1/4" =1'-0" PANDA EXPRESS SPACE FC -1 - UPPER LEVEL_ AREA :$46SaFr. WESTFIELD SOUTHCENTER GENERAL NOTES 1. Aii design and installation in accordance with NFPA Standards. 2. All materials to be Underwriters Labora- tories Listed and/ or FM approved. a Overhead piping to be black steel confor- ming to specifications of ASTM A795, ANSI / ASTM A53, ANSI B3 .10M, ASTM A135. HYDRAULIC DESIGN INFORMATION SYSTEM DESIGN REVISIONS SPRINKLER LEGEND PANDA EXPRESS NORTH DESCRIPTION SYMBOL DESCRIPTION APPROVAL G i 4 o-Fm1L ,ik FINISH NQ.REQ. SYMBOL DESCRIPTION STATIC FINISH NO. REQ. DENSITY MAX.ARENHEAD K -FACTOR RESIDUAL GPM FLOWING DATE & TIME ge.1 fable FIFg ay./ 6rA s Re..1►abt.e F3QZ cow. NO KS O377 DRAWN BY k..).21-1 SPICK. ON SHEET I Z SPRK. ON JOB 7102 - 180th AVE NE, SUITE A-105 • REDMOND, WA • 98052 WESTERN STATES FIRE PROTECTION COMPANY—OFFICES LOCATED DENVER / RAPID CITY / MINNEAPOLIS / DULUTH / DALLAS / HOUSTON ALBUQUERQUE f AUSTIN / SEATTLE / PORTLAND f PHOENIX / KANSAS CITY / ST_ LOUIS Phone 206-881-0100 WA. Reg. # WESTESF136QF Westfield Southcenter 2600 Southcenter Mali FC - Tukwila, WA 98188 SHEET Tukwila Fire 00 i$1 -- Job- Napier Pur. r-F-xe ews -rovve System Steel A LL -30/15 Total - FP rea r•tat 16 Hood * 1 7' 00' Long x 48' Vide x 24' fIQI Hood 8 Riser * 1 Sleet 10' x20' 18mn * 1 Job *1 691170 7' 600' Long x 48' Vide x 24' High Sizeu 10' x 20' "\1—�� r --i r--,17-'- ID 0 1 L___T---rr 1' a 41 r T I 1 J J J L 30/,_io" l'ftoftCPRS Mkttithv‘cAL Gifts ‘1141-4 i iN q_2(u) FC -f v -104)J1LA 1.A ') 126 O O %s R e c_eLime- A p r 22. 3: 33 PM L `' ,--mss Y PD'DVG -- — FgLD PIPING n S I-4 I I K i-ce e,A a t4- ".;s1 key- • Lis44I se iv c, 5',4G1 Sc .ee' Deep yew phot Wok j Pe�;�• '-- A6-+%v4o-coh coq °`PP)' i v.e... UM 11 4-w.. o.. Vt.1}',11q.1-tco, 1.7 ,, - 2008 Tukwila Fire 5141304 crl Zti Prie-e WAY S. Sr•�-,-n.c, v 9 i 34 vai (;,ani sc�J 20(2-340-43O° _ b -----1----7+-41-3 4 g ci+o ruvl S11i'ia,a N MLJX+@ J L 30/,_io" l'ftoftCPRS Mkttithv‘cAL Gifts ‘1141-4 i iN q_2(u) FC -f v -104)J1LA 1.A ') 126 O O %s R e c_eLime- A p r 22. 3: 33 PM L `' ,--mss Y PD'DVG -- — FgLD PIPING n S I-4 I I K i-ce e,A a t4- ".;s1 key- • Lis44I se iv c, 5',4G1 Sc .ee' Deep yew phot Wok j Pe�;�• '-- A6-+%v4o-coh coq °`PP)' i v.e... UM 11 4-w.. o.. Vt.1}',11q.1-tco, 1.7 ,, - 2008 Tukwila Fire 5141304 crl Zti Prie-e WAY S. Sr•�-,-n.c, v 9 i 34 vai (;,ani sc�J 20(2-340-43O° /22/2008 06:38 PM Page: 3 Nola - Fire Systems - Parts List Report 4/22/08 2:26 PM Job # 691120 - Panda Express - Tukwila WA (M 1-08-1189) Location: Tukwila, WA Fire System # 1 Ansul R102 ANSUL-3.0/1.5 Tag: Hoods Covered: Hood # 1Hood # 2 Gas Valve(s): QtY Item CAS # Vendor # Description 6 0 METALCAP-CB METALCAP-CB BLOWOFF CAP - Metal Supplied by Ship Dist CAS Inst Loose 0 6 1 1 AT - 1.5 AT - 1.5 TANK(#1A) -1.5 Gallon SS Tank (for use with 1 0 Automan Release, Actuator, or SS Enclosure (UL)) 1 1 AT - 3.0 AT - 3.0 TANK(#1B) - 3.0 Gallon SS Tank (for use with 1 0 Automan Release, Actuator, or SS Enclosure (UL)) 1 2 AP - AR AP - AR AUTOMAN RELEASE - Ansul Automan Mechanical Release (UL) Tank sold separately 1 0 1 3 AP - AE AP - AE ENCLOSURE - Stainless Steel Enclosure 1 0 Assembly (UL) 1 5 LIQ -3.0 79372 AGENT -Ansulex Low PH Wet Chemical Agent, 3 Gallon (UL) 1 0 1 6 LIQ -1.5 79694 AGENT -Ansulex Low PH Wet Chemical 1 0 Agent, 1.5 Gallon (UL) 1 9 101-30 101-30 CARTRIDGE - Carbon Dioxide, 101-30, Double Tank Cartridge (R-102) 1 0 1 10 TLINK TLINK LINK - Test Link Package 1 0 1 11 MICRO -SD MICRO -SD MICROSWITCH - Single Dual Electric Switch 1 0 1 12 HOSEGROMMET 418511 HOSE - Hose/Grommet Package 1 0 2 13 419337 419337 NOZZLE - 2W Nozzle, Duct 0 2 6 16 419335 419335 NOZZLE - 1N Nozzle, Plenum/Appliance 0 6 2 19 419338 419338 NOZZLE - 3N Nozzle, Appliance 0 2 4 25 418569 418569 NOZZLE ADAPTOR - Swivel Nozzle Adaptor 0 4 10 26 QSA-3/8 QSA-3/8 QUIK SEAL - 3/8" (UL) 0 10 1 27 QPSA-1/2 QPSA-1/2 PULLEY SEAL -112" Hood Seal (UL) 0 1 7 28 S -DET S -DET DETECTOR - Series (Scissor Linkage) 0 7 7 30 ANS-500FL ANS-500FL FUSIBLE LINK - 500deg F, R-102 and 0 7 PIRANHA 1 34 RPS -A RPS -A REMOTE PULL STATION - Aluminum (without 1 0 wire rope) 10 35 PE -LT PE -LT PULLEY ELBOW - Low Temp. Pulley Elbow, 10 0 Set Screw Type http://appl.captiveaire.com/Order/FireSystems/PartsListReport.aspx?JobFireSystemld=141393 Page 1 of 2 Received Time Apr.22. 3:33PM /22/2008 06:38 PM Page: 4 Nola - Fire Systems - Parts List Report 4/22/08 2:26 PM 1 36 PE -HT PE -HT PULLEY ELBOW - High Temp Pulley Elbow, 0 1 Compression Type 6 41 SN -CHAR SN -CHAR SINGLE NOZZLE EXTENDED DROP ASSY 0 6 http://appl.captiveaire.com/Order/FireSystems/PartsListReport.aspx?JobFireSystemld=141393 Page 2 of 2 Received Time Apr.22. 3:33PM S'ECTION'IV — SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-28 REV.5 4-1-06 Nozzle Application Chart The following chart has been developed to assist in calculating the quantity and type of nozzle required to protect each duct, plenum, or appliance. NOTICE This chart is for general reference only. See complete details for each type of hazard. Minimum Maximum Hazard Nozzle _ Nozzle Hazard Dimensions Quantity Heights 10 Duct or Transition Length — Unlimited 1 (Single Nozzle) Perimeter — 50 in. (127 cm) Diameter —16 in. (40.6 cm) Duct or Transition (Single Nozzle) Duct or Transition (Dual Nozzle) Electrostatic Precipitator (At Base of Duct) Plenum (Horizontal Protection) 0. Plenum (Horizontal Protection) Plenum (Vertical Protection) Fryer (Split or Non -Split Vat) Fryer (Split or Non -Split Vat) Fryer (Split or Non -Split Vat)* Fryer (Non -Split Vat Only) Length — Unlimited Perimeter —100 in. (254 cm) Diameter — 31 7/8 in. (81 cm) Length — Unlimited Perimeter —150 in. (381 cm) Diameter — 48 in. (122 cm) Individual Cell Length — 10 ft. (3.1 m) Length — 6 ft. (1.8 m) Width —4ft. (12m) Length — 4 ft. (12 m) Width — 4 ft. (1.2 m) Maximum Size (without drip board) 14 in. (36 cm) x 15 in. (38 cm) Low Proximity Maximum Size (without drip board) 14 1/2 in. (37 cm) x 14 in. (36 cm) Medium Proximity Maximum Size (without drip board) 15 in. (38 cm) x 14 in. (36 cm) High Proximity Medium Proximity Maximum Size (without drip board) 191 /2 in. (49.5 cm) x 19 in. (48.2 cm) High Proximity Low Proximity Maximum Size (without drip board) 18 in. (45.7 cm) x 18 in. (45.7 cm) High Proximity 1 1 1 1 1 1 1 1 1 1 1 1 1 ' For multiple nozzle protection of single fryers, see detailed information on Pages 4-12 through 4-14. 13-16 in. (33 — 41 cm) 16 — 27 in. (41 — 69 cm) 27 — 47 in. 20 — 27 in. 21 — 34 in. 13-16 in. 25 — 35 in. (64-89 cm) Nozzle Part No. 430912 419337 419337 419334 419335 430192 419336 419336 419342 419342 419339 419340 419338 419342 419338 Nozzle Tip Stamping — Flow No. 1W 2W 2W 1/2N 1N 1W 1W 1W 290 290 230 245 3N 290 3N Nozzle Application Chart (Continued) Hazard Wood Fueled Char -Broiler Upright Broiler Salamander Broiler Wok Maximum Hazard Dimensions Longest Side — 30 in. (76 cm) Area — 720 sq. in. (4645 sq. cm) Length — 32.5 in. (82.5 cm) Width — 30 in. (76 cm) Length — 32.5 in. (82.5 cm) 2 Width — 30 in. (76 cm) 14 in. — 30 in. (36 — 76 cm) Diameter 3.75 — 8.0 in. (9.5 — 20 cm) Deep 11 in. — 24 in. (28 — 61 cm) Diameter 3.0 — 6.0 in. (8 — 15.2 cm) Deep SECTION IV — SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-31 3-1-04 REV.6 Minimum Nozzle Nozzle Quantity Heights 1 14 — 40 in. (36 — 102 cm) 2 — 1 35 — 45 in. (89 —114 cm) 30 — 40 in. (76 —102 cm) Nozzle Part No. 419338 419334 419334 419341 Nozzle Tip Stamping — Flow No. 3N 1 /2N 1 /2N 260 419335/417332 1 N/1 NSS r„�ovL ru t OMAN Regulated -Mechanical Release Assembly (3.0,gallon — Part No. 79290 cr .1.5 gallon — Pan No. 79291) contains the regulated release mechanism, agent tank. expellant gas hose for agent tank hookup. and enclosure knockouts to facilitate installing actuation piping; expellant piping: detection system; and additional equipment. This regu- lated release assembly is used in single, double, and multiple - tank systems and must be mounted to a rigid surface. The release mechanism can be used to interconnect both the actu- ation and expellant gas lines as required per system design. The regulator is designed to allow a constant flow of gas into the tank at 100 psi (690 kPa) when the system is actuated. In single. double, and multiple -tank systems, the provided expel- lant gas hose connects the agent tank to the bottom outlet of the regulator. In double and multiple -tank system configurations. the back outlet of the regulator is used as an expellant gas feed for one additional tank -enclosure or tank -bracket hookup. The enclosure contains the required knockouts to facilitate this con - rection. If a pressure switch is to be attached to the regulator, additional fittings are required. The tank is mounted within the enclosure. The tank contains an adaptor/tube assembly with a burst disc union: The burst disc helps prevent siphoning of the agent up the pipe due to signifi• - cant temperature fluctuations in the area where the -tank is located. The tank is mild steel and, under normal conditions, requires hydrostatic testing every twelve years. - The agent tank is shipped uncharged and must be -filled with 1.53 gallons (5.8 L) or 3.06 gallons (11.6 L) of only ANSULEX Low pH Liquid Fire Suppressant during installation.. The detection and additional equipment required per system design are connected to'the release mechanism. The enclosure contains knockouts to facilitate detection and additional hookups. The system can ba actuated automatically or manually. Auto- matic actuation occurs when a fusible link within the detection system separates in a fire condition. Manual actuation of the system occurs when personnel pull on the remote manual pull station pull rine. E)C lNGU1SHING AGENT ANSULEX Low pH Liquid Fire Suppressant (1.5 gallon — Part No. 79694 or 3.0 gallon — Part No. 79372) is a potassium -based solution designed forfast knock -down and suppression of grease -related fires. The agent is shipped in plastic containers which provide one complete tank charge. Agent storage life expectancy is twelve years. The distributor must record the batch numbers and date of shipment receipt to be filed with each instal- lation record. Total Flow No' 1-5 Tank Quantity 1 ANSUL Type of System : Tvoe of Hardware Single 1.5 Gal. Reg. Release Single 3.0 Gal. Reg. Release ELECTRICAL SWITCHES — LOC,Pap It3 .EA -CA. I U D The electrical switches are intended for use with_ electric gas valves, alarms, contactors, lights, contractor supplied electric power shut-off devices :and other elect;icai devices that are designed to shut off or tum on when the system is actuated. Switches are available in kits: One Switch Kit, PartNo. 423878 Two Switch Kit, Part No. 423879, Three Switch Kit, Part No. 423880, and Four Swfh Kit, Part No. 423881. Each switch has a set of single -pole, double -throw contacts rated at 21 amp, 1 HP, 125, 250, 277 VAC or 2 HP, 250, 277 VAC. Mounting hardware is provided with each kit. R-102 RESTAURANT FIRE SUPPRESSION SYSTEM (Standard UL 300 Listed) Nozzle Identification Chart Nozzle Nozzle Noz Nozzle Type Part No. Stamoin❑ Roy 1W Nozzle 1WSS Nozzle 1N Nozzle 1NSS Nozzle 1/2N Nozzle 3N Nozzle 2W Nozzle 2WH Nozzle 230 No=Ie 245 Nozzle 260 Nozzle 290 Nozzle 2120 Nozzle 1F Nozzle I t oo 1407 -Ur Nitrogen Cartridge Reouired LT -20-R (7032) LT -30-R (5373) 419336 417333 419335 417332 419334 419338 419337 78078 419339 419340 419341 419342 419343 419333 -460,12 1W 1 1W 1 1N 1N 1/2N 3N 2W 2WH 230 2 245 2 260 2 290 2 2120 2 1F 1 1100 1 1 1/2 3 2 2 Carbon Dioxide Ca :co_D Rern�ired 101-10 (15850) 101-20 (17492) WR et\tiflusT 1:=150 51 -Ms ,SuteLy ktk 5W -1-5E. 5 GS 5 -Pel I ?O (T �q-Ts) u10X- NW> Susi c IF Pf1Ag` F -l0, S t -MS . 15 S v i • SECTION IX - APPENDIX UL EX. 3470 ULC CEx747 Page 9-1 7-1-98 REV. 3 SYSTEM SELECTION GUIDE ' NOTE: System options do not cover all conceivable variations. They are listed here as a general guideline to show the most common type arrangement for multiple systems, Based on certain system designs utilizing manifolding, non-manifolding, 3 -tank systems, etc., other tank/cartridge combinations can be designed. The combinations below are based on 11 flow, 3.0 gallon tanks and 5 flow, 1.5 gallon tanks. More competitive designs may be available by utilizing 12 flow and 6 flow systems when appropriate. Total Tank Type of Nitrogen Carbon Dioxide Cartridge Required Cartridge Required Flow No.* Quantity System Type of Hardware 1-5 1 Single 1.5 Gal. Reg. Release LT -20-R (7032) 101-10 (15850) 7032 6-11 1 Single 3.0 Gal. Reg. Release LT -30-R (5373) 101-20 (17492) 5373 12-16 2 Double 1.5 Gal. Reg.Release Double (73022) 101-30 (15851) 3.0 Gal: Additional Tank 17-22 2 Double 3.0 Gal. Reg. Release Double73022 3.0 Gal. Additional Tank Double(73022) 101-30 (15851)`• 23-27 3 Multiple 1.5 Gal. Reg. Release LT -20-R (7032) 101-10 (15850) 3.0 Gal. Reg. Actuator LT -A-101-30 (29187) 101-30 (15851y- 3.0 Gal. Additional Tank 28-33 28-33 (Optional) 34-38 3 4 39-44 4 45-49 5 50-55 5 56-60 6 Multiple 3.0 Gal. Reg. Release LT -30-R5373 3.0 Gal. Reg. Actuator ( ) 101-20 (1749) 3.0 Gal. Additional Tank Multiple 3.0 Gal. Reg. Release (2) 3.0 Gal. Additional Tanks Multiple 1.5 Gal. Reg. Release 3.0 Gal. A.dditional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank Multiple 3.0 Gal. Reg. Release 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank Multiple 1.5 Gal. Reg. Release 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank Multiple 3.0 Gal. Reg. Release 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank Multiple 1.5 Gal. Reg. Release 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator' 3.0 Gal. Additional Tank 61-66 6 Multiple 3.0 Gal. Reg. Release 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank - Based on 5 flow numbers for a 1.5 gal. system and 11 flow numbers for a 3.0 gal. system. See Pages 4-39 - 4-42 for exceptions. If tanks are man,folded. only a "double tank" nitrogen cartridge (Part No. 73022) can be used. If tanks are manifotded, either an LT -A-101-30 nitrogen cartridge (Part No. 29187) or a double tank cartridge (Part No. 73022) can be used. LT -A-101-30 (29187) 101-30 (15851Y - Double 15851Y- Double (73022) N/A Double (73022) LT -A-101-30 (29187) 101-30 (15851) 101-30 (15851)"' Double (73022) 101-30 (15851)" LT -A-101-30 (29187) 101-30 (15851y - LT -20-R (7032) LT -A-101-30 (29187) LT -A-101-30 (29187) LT -30-R (5373) LT -A-101-30 (29187) LT -A-101-30 (29187) Double (73022) LT -A-101-30 (29187) LT -A-101-30 (29187) Double (73022) LT -A-101-30 (29187) LT -A-101-30 (29187) 101-10 (15850) 101-30 (15851)- 101-30 (15851)- 101-20 (17492) 101-30 (15851)- 101-30 (15851y- 101-30 (15851) 101-30 (15851)' 101-30 (15851)- 101-30 (15851)" 101-30 (15851)"' 101-30 (15851)"' V • • • ACCEPTED O Without Comments As Noted In Red 0 Per The Attached Letter nese plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is :..ubiect to errors and omissions which dc ) -Juhcirize violations of adopted standards and orrrs-; h•-; re wont);Itty for the adequacy of Ne. -1-1 the designer. Additions, ds ri;vi,n100`' thee drawings atter this date will void th:-,5 a.:cizi)tan e'_rd will require a resubmittal of revised dr aA ing li for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. IBy: 11 Date: -0 2 utcwILA FIRE DEPARTMENT, Please call: 575-440Z Ind give this job 0 -1 C3 xact address for shut% or restoration aPorovell FIRE L t---1 SYSTEM TUKWI i .A. WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET NUMBER SHEET TITLE FA -01 SYSTEM INFORMATION FA -02 TYPICAL DETAILS - WIRING AND MOUNTING FA -03 FIRE ALARM SYSTEM FLOOR PLAN FA -04 SYSTEM CALCULATIONS (GENERAL), RISER, SITE PLAN' T- !nese plans have h ;n revib,.: fed by The Tukwila Fire Prevention Buret i It. _.t:, ... s . , ..:: with current city standards. A..ccb pi.? (1C.0',::.:i::'..:.:-.q ,. c=ircrs and Omissions wh;c13 o. i !., Y:" t OfS o1` adopted il Stand sras and -i n,:: .3risib t for the adequacy o , .._ ;i, Me designer. 1 Additions, :""_ :'i; ..).,..._. k;. tht=:;;ti drawings atter , this date wiil void u -.:r-: 9n l vt%i1 require a "f.i.e.subraittaI of rov!;:o 1 r�,' "i, ;Of 2ubsequent approval. Final acc ct"r.i.: ..`'.... ?)....,,-•-...-. ."r F:r.4r. 1.(:.:7.-,t a•nd inspection by The Tukwila ;_ ,.. r C‘.'' .,,; n S'Ji ttLU. Date: 3--- 4 -v0 By: /iJ ACC PTED Wthout Comments As Noted In Red Per The Attached Letter i TUKWILA FIRE DEPARTMt11'1, Please call:. 575.440Z and give this job No. 0,S?-F�l 7 0; and exact address for shut% down or restoration approval; NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) 2S STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #I6 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) 2V SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATI❑N LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATI❑N TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M BOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR: SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT. TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS.. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 9. 10. THE. 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD. DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER 'CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION ,TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 1 1 3 1 SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP. E FIRE ALARM CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD D DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP: CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING DUCT SMOKE ®D, DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM 4S DEEP BOX CEILING W/ 1-1/2" EXT. C; FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING L FIRE ALARM STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. c. FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. FIRE ALARM SPEAKER (WALL MOUNT) SET -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM B WP FIRE ALARM STROBE (WEATHERPROOF) SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR 1 MULTI -VOLTAGE CONTROL RELAY MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD O JUNCTI❑N BOX F.B.D. F.B.O. N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A U.❑.N. UNLESS OTHERWISE NOTED N/A N/A N/A N/A WP WEATHERPROOF DEVICE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A PAI - 2008 Tukwila Fire Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 75 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 RELEASE/REVISIONS REV. BY: Z a DESCRIPTION SHOP DRAWINGS co L1.1 oo z CCCCC 0 z ‘CALE: 1/8"=1' DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE: 5/05/08 BACKROUND PLAN PROVIDED BY: �OB NUMBER:54532 SHEET FA -01 ',, THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT MYTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS DUCT DETECTOR LOCATION p TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT v LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVIC y END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH GROUND 0 r 0 © © HTRI-R OSTATUS LED CO C.0 0 0 0 N.O. COM N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 Am TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL NIP LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE DEVICE TO NEXT ADDRESSABLE r DEVICE L NOTE 1: VOLTAGE MAX. - CURRENT MAX. - CONT. RES. MAX. - MAX. CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN. LINE SIZE - MUSIC OUTLET SAMPLING TUBE INLET SAMPLING TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE 14 -AC POWER SOURCE COMBINE ALL SHIELDS ANDS ISOLATE FROM GROUNDING'.;;'.: TO NEXT ADDRESSABLE DEVICI STOP IF LAST DEVICE FROM XLS CONTROL.. PANEL OR',' PREVIOUS ADDRESSABLE DEVICE (—) (+) (-) (+) RELAY CONTACTS (4.0A @ 125VAC) (4.0A @ 30VDC) 27 VDC 3.5 mA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0.02uF 0.04uF 14 AWG 18 AWG NOTE 2: ALL SUPERVISED• SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTI❑N. IeQI TB1 0 0 0 0 0 123456 HCP TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE END OF; LINE DEVICE'i;;l (3.6K 1'/, 4VJ) 0 SUPERVISED % SWITCH ;; L; NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. -TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL 0 0 0 © HTRI-D STATUS LED 00 0 0 LABEL SCALE (FIRE:SUPPRESSION SYSTEM INTERFACE) - 0 0 GND N AC 0.101E 00 0 00 0 INPUT INPUT TROUBLE NAC1 NAC2. NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - MAIM 11 24K NOT USED END OF LINE DEVICE' 3.6K 1/4W) UPERVXSED 'WITCH it 2 NAC -4 NAC -3 NAC -2 NAC=1. • FRONT MEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE DEVICE LOOP I 0 FROM XLS CONTROL PANEL OR (+), PREVIOUS ADDRESSABLE DEVICE (—)' 470 OHMS AW EOL TS M-1 0 o1 ac ' V (DocO '5 moo C ae000 o 5. CQCO m TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL - SCALE: NONE FROM REMOTE POWER SUPPLY ('S' CABLE) FROM FACP (VOICE CIRCUIT) ('V' CABLE) n r (+) (—) STROBE SPEAKER EARTH GROUND --)r(+)TO NEXT DEVICE OR >(—) STOP IF. LAST DEVICE +) ( ) STROBE (-0 ' () STROBE SPEAKER (+) (—) SPEAKERISTROBE AND STROBE \AIRING LABEL SCALE SPEAKER STROBE F OR STROBE ONLY E 80" A.F.F. 0 0 0 4S DEEP BOX W/ 1-1/2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE=NONE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERAIIN TEMPERA ' +32' F I C) TO 1017 F 3K C) HUMIDITY: % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR —� FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DEVICE IS LISTED FOR AIR VOLOCITY APPUCATIONS OF 300-400D FT IN IIIEIEN USED IN CONJJNCTION %1TH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE DATA IN (—) >— DATA IN (+) > REAR VIEW TO NEXT DEVICE > ( ) DATA OUT } (+) DATA OUT HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE CEILING MOUNT ' SPEAKER/STROBE MOUNTING (HARD LID) 1 TO NEXT DEVICE OR —! END OF LINE, TO NEXT DEVICE OR . END OF LINE HARD LID -- CEILING SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION N CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE=NONE JUNCTION BOX MOUNTED ON - . CEILINGI FLEX \.\ - JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPP❑RT / / / / / / TO NEXT DEVICE' O O CADDY BAR SMOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE=NONE --- SUSPENDED ILLUMINATED CEILING(; Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved.; fa -4 00 0' 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 ( RELEASE/REVISIONS CO LU DESCRIPTION SHOP DRAWINGS w Q 03 0 .Ln 0 z C 1 J 00 (/) CO CI) W W E- z a zo W � �=z W CC = _ Q QOM owryco Z 7 LL am CD (NI ~ CC CO V 4 -74.F - J 0 tSCALE: 1 8"=1' DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE: 5/05/08 BACKROUND PLAN PROVIDED BY: `0B NUMBER:54532 SHEET FA -O2 • , --------------------------------------------------- r ,i r `4-,4=4-7_47-;:::: I/ il 1,1 .1/.. / , 4 ----- / r A ,,,,..4,_ i 1 / , / ; / .,., ; STORAGE / i----1---4 --------, t / EXITi SERVICE KC.) - - I I I / i 1 i I.ssi0-,-zM!g':l:E!- r Ebt,----51• --'1-.-t -rivic:,:ri20.20V I ___------, -- .__ I • r 1 . , I------ ' • MALL STARS 1 N4 I Vi!!!',1 WALK 41 FREEZER I 144 S 75: WAS INa ----- VODSPACE / 31 AFF ---- -------------- CO9UNG 1 Lie . ‘,3 .• , • /' Ei C , . , E2' r•In1r!.-r-.• p- 1 :4 -,--_ ui cm v. a) 10' —0" AFF WALK IN COOLER MANAGERS STATION 12 —10" AFF REGISTER/ PM LIP PANDA EXPRESS WESTFIELD SOUTHCENTER MALL SCALE 118%T • FLAG i\ OTS: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATION SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR, Copyright 2006 by Guardian Security Systems, Inc. All Rights I; • • •:: Reserved !!! 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 RELE.ASE/REVISIONS REV. BY: z <t DESCRIPTION SHOP DRAWINGS DATE 5/5/08 2 ‹<<<< —J —J cC8 co &`;-E; cca) u J2 wz 12P 16(.1 X I UJ 15 en ter 0 < W 0 Z an. D CO I— N LT. 'ALE: 1/8"=1' DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE: 5/05/08 BACKROUND PLAN PROVIDED BY: ...JOB NUMBER:54532 SHEET FA -03 0 NORTH A k, - A 1\ ----- N PANDA EXPRESS WESTFIELDSOUTHCENTER MALL. W,--F-r:------7--\\ 0 \ \\ \ ..--------- 3.1 V\ '1, \ \ k\ , \ ..... A \ ---- - \ 1 1 'I / i SCALE 11374 S,2V Op S,2Ve 113:11:1111 75 C C 75 C EOL -S1 20.20V 2S,2V EX D,I 21 RISER DIAGRAM SYSTEM CALCULATIONS BATTERY SIZING CALCULATION ELD SOUTHC• ENAppliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: PANDA EXPRESS Wire Resistance 1.62 Date: May 5, 2008 CIRCUIT: S1 QTY 1 Device Type 1 SET -MC @15CD ISET-MC,@30CD 2 1SET-MC,@75CD O iSET-MC @110CD 0 SET-HMC-C@115CD CURRENT TOTAL=1414 ' t I i i . . ... .. . . 1 . -,i i Alarm Current i AlarrivTotal i Wire Size Wire Length ', Voltage at EOL Circuit Total ...- O SET-HMC-C@177CD - 0 1SET-HMC @135CD 0 !SET -HMC @185CD 641 •1- 64! Total Wire Resistance ( R ) 0.49 981- ' ol , , . ( WL* 2 )* (R/ft) , ; , 0.41! 175! 350, , , ; Total Device Load, Amps (I) 2331 01 0 , (Total Cct Load) 0.20 I , 318 i 4451 ; Voltage Drop ( E ) 0 0! (E= I * R) : 318! : EOL Voltage 20.201 445 0 i , (20.4 - E) 1Z-MC@15CDillol 0 IZ-MC@30CD 2001 oi 0 isEnMC-cw@i loci) 1 264i 0 ; TOTAL- m A= DEVICES=3 4141 12 151 20.19745464 414 Notification Appliance Circuit Detail PROJECT: ,WESTFIELD SOUTHCENTER MALL Panel: ;PANDA EXPRESS ,Wire Resistance 2.58 Date: May 5, 2008 5 5 CURRENT TOTAL=1'5.4 CIRCUIT: SPEAKER CIRCUIT QTY Device Type - Alarm Current Alarm Total Wire Size i Wire Length 1 Voltage at EOL Circuit Total 3 70.7V 1/8 1.8! 5.41 !Total Wire Resistance ( R ) 0.78' 01 01 , ( WL * 2 )* (R/ft) 0 , . 01 0 1 . . . 1Total Device Load, Amps (I) 0.01 00i 0 , ', . , J , (Total Cct Load) O 0 i 0 Voltage Drop ( E ) ; i 0. 00 0 0 0 i i . If (E= I * R) 1 ; . 0 01 0 , ""- ) EOL Voltage 20.40 (20.4 - E) O 0 0' 0 , 0 0; 0 DEVCES=i3 1 TOTAL mA=1 5.4i 14 ; ,` 151 20.39579254 5.4, 0 0 VOLTAGE DROP CALCULATION 1743 ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 U) z 0 uJ CC LLI U) LLJ LU CC REV. BY: PANDA EXPRESS .':, PANDA EXPRESS FACP ADD ONS ' \t!SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations SHOP DRAWINGS DATE 5/5/08 2 < <<<< Current Load: Standby: Alarm: , Current Load: , Standby: Alarm: 1; Device Type Qty Amps Total Amps Total ., i,, Device Type Qty Amps Total Amps Total , HFP-11 0.0022 0.0022 0.0023 AD2-P 1 0.0635 0.0635 0.064 0.064 :1 Main System Board 1 0.03 0.03 0.030 0.030 I, HTR -R.1 FiT141:15 ----- , ICP -B60.005 ..., _ • . _ .. .... - ---- - - - _ ,. , _.., .. . ...._, ,_, . _. o.009600 0.0096 0.021 0.021 ' ' SET -MC @15CD SET -MC @30CD_ SLT-MC@7666 SET -Via @i1066 - SET-i-iik:odifeD SET-HMC-C@135CD SET:HMC:C@185CD ZR -MC @15CD _ „_. , ZR -MC @30CD.,,, HCP 1 0.064 0.064 1 0.001600 0.0016 0.0035 0.004 ' 0.098 , 2 0.175 0.350 ., 0.233 0.318 0.318 0.0747 Amps 0.0885 Amps 0.445 .,, 0.064 , Standby Current Load: 0.0747 Amps For 24 Hours = 1.793 Amp -hours •, !. 0.098 , . -,, 0.0015 , Alarm Current Load: 0.0885 Amps For 5 Minutes= 0.007 Amp -hours , 0.03 Amps 0.444 AmpS• 25% Derating= 2.250 Amp -hours : Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours .i . Alarm Current Load: 0.444 Amps For 5 Minutes= 0.037 Amp -hours Total System Current Load: 2.250 Amp -hours ' 25% Derating= 0.947 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.947 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULATION ELD SOUTHC• ENAppliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: PANDA EXPRESS Wire Resistance 1.62 Date: May 5, 2008 CIRCUIT: S1 QTY 1 Device Type 1 SET -MC @15CD ISET-MC,@30CD 2 1SET-MC,@75CD O iSET-MC @110CD 0 SET-HMC-C@115CD CURRENT TOTAL=1414 ' t I i i . . ... .. . . 1 . -,i i Alarm Current i AlarrivTotal i Wire Size Wire Length ', Voltage at EOL Circuit Total ...- O SET-HMC-C@177CD - 0 1SET-HMC @135CD 0 !SET -HMC @185CD 641 •1- 64! Total Wire Resistance ( R ) 0.49 981- ' ol , , . ( WL* 2 )* (R/ft) , ; , 0.41! 175! 350, , , ; Total Device Load, Amps (I) 2331 01 0 , (Total Cct Load) 0.20 I , 318 i 4451 ; Voltage Drop ( E ) 0 0! (E= I * R) : 318! : EOL Voltage 20.201 445 0 i , (20.4 - E) 1Z-MC@15CDillol 0 IZ-MC@30CD 2001 oi 0 isEnMC-cw@i loci) 1 264i 0 ; TOTAL- m A= DEVICES=3 4141 12 151 20.19745464 414 Notification Appliance Circuit Detail PROJECT: ,WESTFIELD SOUTHCENTER MALL Panel: ;PANDA EXPRESS ,Wire Resistance 2.58 Date: May 5, 2008 5 5 CURRENT TOTAL=1'5.4 CIRCUIT: SPEAKER CIRCUIT QTY Device Type - Alarm Current Alarm Total Wire Size i Wire Length 1 Voltage at EOL Circuit Total 3 70.7V 1/8 1.8! 5.41 !Total Wire Resistance ( R ) 0.78' 01 01 , ( WL * 2 )* (R/ft) 0 , . 01 0 1 . . . 1Total Device Load, Amps (I) 0.01 00i 0 , ', . , J , (Total Cct Load) O 0 i 0 Voltage Drop ( E ) ; i 0. 00 0 0 0 i i . If (E= I * R) 1 ; . 0 01 0 , ""- ) EOL Voltage 20.40 (20.4 - E) O 0 0' 0 , 0 0; 0 DEVCES=i3 1 TOTAL mA=1 5.4i 14 ; ,` 151 20.39579254 5.4, 0 0 VOLTAGE DROP CALCULATION 1743 ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 U) z 0 uJ CC LLI U) LLJ LU CC REV. BY: z 4 DESCRIPTION SHOP DRAWINGS DATE 5/5/08 2 < <<<< -J -J C° < C° CO CO. U) cc a) w 2 w Z WF -0 CC CL Xi W cc 15cn < o< L.1 Lu CD ,,;" CL 80 (DI- N zrr- co z 0 (1) z0 DRAWN BY: !ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/05/08 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved BACKROUND PLAN PROVIDED 13Y: ..10B NUMBER:54532 SHEET FA -04 j