HomeMy WebLinkAboutPP - 2600 SOUTHCENTER MALL FC-11 - CHICKEN NOW - PERMITS AND PLANS2600 SOUTHCENTER MALL FC -11 FOOD COURT ASSOCIATED PERMITS 08-F-293 08-S-344 12-H-164 08-H-358 FIRE DEPARTMENT HOOD SUPPRESSION PLAN REVIEW COMMENTS Project Name: Chicken Now 2600 Southcenter Mall FC -11 Permit No.: 08-H-358 Date: June 25, 2008 Reviewer: Steve Kohlerr Fire Prevention Inspector/plan review (206)575-4407 • Nozzle heights above appliances to be per manufacturers installation guidelines. • Install splash guards between fryers and ranges/charbroilers. • Upon activation of the suppression system, the make-up air supply will shut off and the exhaust will keep running. • Type 1 hood systems shall be designed and installed to automatically activate the exhaust fan whenever cooking operations occur. The activation of the exhaust fan shall occur through an interlock with the cooking appliances, by means of heat sensors or by means of other approved methods. • Activation of the suppression system shall shunt all electrical power under the hood as well as the gas supply. • Install a "K" rated portable fire extinguisher within 30 ft. of the cooking equipment. • The hood suppression system shall be monitored by a U.L. Central Monitoring Station. FIRE DEPARTMENT HOOD SUPPRESSION PLAN REVIEW COMMENTS Project Name: Chicken Now A*** 2600 Southcenter Mall FC -11 Permit No.: 12-H-164 Date: July 24, 2012 Reviewer: Al Metzler Fire Protection Project Coordinator (206) 575-4407 option # 2 (Inspection Requests) (206) 971-8718 (Plan Review Questions) F • Nozzle heights above appliances to be per manufacturers installation guidelines. • Fryers shall be installed with at least a 16 inch space between the fryer and surface flames from adjacent cooking equipment or a minimum 8 inch high steel or tempered glass baffle plate shall be installed between the appliances. • Upon activation of the suppression system, the make-up air supply will shut off and the exhaust will keep running. • Type 1 hood systems shall be designed and installed to automatically activate the exhaust system whenever cooking operations occur. The activation of the exhaust system shall occur through an interlock with the cooking appliances, by means of heat sensors or by means of other approved methods. • Activation of the suppression system shall shunt all electrical power under the hood as well as the gas supply. • Install a "K" rated portable fire extinguisher within 30 ft. of the cooking equipment. • The hood suppression system shall be monitored by a U.L. Central Monitoring Station. • A minimum 110 candela horn/strobe shall be installed above the kitchen hood suppression system manual pull station at a height of 80 inches above the floor. • A separate fire alarm permit from the Tukwila Fire Department is required for all fire alarm work. • The suppression system manual pull station shall be located no closer than 10 ft. and no farther than 20 ft. from the cooking equipment and be placed at a height of 42 to 48 inches above the floor. • The inside lower edge of the hood shall overhang or extend a horizontal distance of not less than 6 inches beyond the edge of the top horizontal surface of the appliance on all open sides. The vertical distance between the front lower lip of the hood and such surface shall not exceed 4 feet. • If cooking appliances are wheeled, the appliance wheels shall be set in tracks permanently mounted to the floor to ensure appliance is returned to original location if moved for cleaning or maintenance. } b9SLae ZZ si kck GAadIa Feld Tpaa! Ce 2a'1. X 24'WX26"N Boge .2 burners F� Type G.. Irl K2rWX3erri �ryr-I i V.1Wmo r Fuld Typal Go Irl x wwxarH Fryer Rol Type: Gas MOM 1WL x 1PWx411-14 Fry■.- Full Val lel Mad N r rwx3erw o Ryer - Fuel 7yFFi.I aiaag Dla�■d�, pe* Gac trl x IrwxSrw PL212,75 U J L 14.37 N. N. W N. N. 5 • t 4 ce " N. N. - • ...i z J IV 0 11- 0 0 uI 0 1• OZ Fo G C (^T_` r LA z cp IONE 5 Et Hoof Mil. Hood 1 -SEC' E thatw1 Ccllar. 121 W)C 1 g ° a N V- r N a+if 4,71G ITiligi Part No. ZZ 182756A Drawing No. ZZL ST182756A ANSUL R-102_ FIRE SYSTEM PARTS JOITmrs+ TAINS CDtFIDENT(I4L IIF THE C113KPANY [iF THE CAHP/WNY fIN REDIJE4T. 1J4TION tT WNTAINS CLJIISED TD PERSENS TV CEIsSISTENT WITH 'HE DDCIR'ENT 1, I'V PARR TF i DESCRP1WPl MEDI I1S41ALLONANS0E* T037 13 4 anLLLINIAtrllex 417J'%I ISFAIES DETECTOR FUSEiLE LDJitS ITBIYj 1 1 218:4 IT T LPZ 1GAS V Jt IF13d]DETERIMED 15!50 LD1 -10 CARBON (ROME CART_ 5373 LT 111F1 NTAOGEM CPRTHIUf 13E61 114140 CAFBQ4 U100»JDE CART - G 12 YES 421E53 IREGLIIATfD REIBISE ASSY 430850 IREG:I A -1E IACTWTORASSY 110501 I GE3.1 REGULATED ACTUATOR 42!J1E.2 3p CIAllf111 TANKPSSFIJBLY 42Pa70 13.G GALLON TANK {aTC BIKE dIVR 4 115 CALLON OM AVZLI3LY 4L1S (REMOTE PULL STATION 4271 GB IFULIEY TEF 15621 IWRE ROPE (4D FF_ETl 1 1 42.5578 DP DE ELECTRICAL SWITCH t 1 IAJAR LEN' SUM_ I1JRfl6IRO€E 10 1 415571 THIGH TEI P PLLLEY ELBC. 77164 313 RRQUICK.SF& 77216 131 IM. COMPREBSK)N SEA 701=0 lin Pt OCYJC47WrSEAL ?Ma IFIDOD SEA. 419373 11Ft 72LET1FLOM 418314 I1/2 N IJO2 LE I E0- 411015 11Jr h13721.E 11 FLC.Y1 414018 111t/No22LE11 F101,10 411137 I2W NDi21E [1 ELMS) 4199713 I361 NDZZL.E 13 ILFW5S1 41!3]0 1250 KD721E 12 FUR%) 411340 1155 KaTI E 12 FLOPS) 419141 1291 10723E 12 FLOWS) 414042 2W 6DOLb.E R Ftp/+) 4111343 12121 NOZZLE f2ELCRI9I 470012 I11UD 110271E 11 FtOM 41150E ISM4EL/LPPTIA CFROVIE45DEGREEEIEKY$rS Hood Masi: Hood 1 -SECTION 1 E.halsl Ccllar. 12114"( 14' Htad {andel C -HEV -11-S TUTTAL IJ0 D FLOW POINTS 2 10 LPL SYS LI MED FI01,4 P01645 20 MINT/774E SYs16J7 FLOW POINT -5 20 DISTRIBUTOR RESPONSJBIIITIES - cook011A11i10N OF JCB PiIrALLAT1DNYJIIh1.b[i D019TRACTOR. -G49 VALVE W LL<LP TO RELEASE VEORAMSN 1111AN lJT .SELE 6 TAT E4E VALVE AS KEI:IESWIYj -6E401E PULL STATION HOO1lUP EL EASE NEr.RA Sld -a10R131W, TEST INct. M1 CER TT1rJ.1TtI1 DF sfSTEM FIPINGAND NU22LES FROM FACTORY mecum 4'iM IFY APPLIANCE DWFS IF SHELVES CR &AJ.Jlt4AYDETi5 GtJ "THE APPIIA ICE LYTERFEREWRH H022LE D[3[RAflJ E. - SUPPLY PPM BETWEEN 6LILTIPLE HCOCS, WORAMY.TEWITH HDOD EN9TALLER FCR PROPER GTIEMAUI H DF MJU1PLE Hma% UL 300 FIRE PROTECTION SYSTEM S5904799 ('1-nc (FN NMI& gFATT1 F WA 8 771 8 2 7 5 6 A H 42 O QOid ALIS SECTION IV — SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-28 REV.5' 4-1-06 Nozzle Application Chart The following chart has been developed to assist in calculating the quantity and type of nozzle required to protect each duct, plenum, or appliance. NOTICE This chart is for general reference only. See complete details for each type of hazard. Hazard ► Duct or Transition (Single Nozzle) Duct or Transition (Single Nozzle) Duct or Transition (Dual Nozzle) Electrostatic Precipitator (At Base of Duct) Plenum (Horizontal Protection) ► Plenum (Horizontal Protection) Plenum (Vertical Protection) P. Fryer (Split or Non -Split Vat) Fryer (Split or Non -Split Vat) Fryer (Split or Non -Split Vat)' Fryer (Non -Split Vat Only) Minimum Maximum Hazard Nozzle Nozzle Dimensions Quantity Heights Length — Unlimited 1 — Perimeter -50 in. (127 cm) Diameter —16 in. (40.6 cm) Length — Unlimited 1 Perimeter —100 in. (254 cm) Diameter — 31 7/8 in. (81 cm) Length — Unlimited Perimeter -150 in. (381 cm) Diameter — 48 in. (122 cm) Individual Cell Length —10 ft. (3.1 m) Length — 6 ft. (1.8 m) Width — 4 ft. (1.2 m) Length — 4 ft. (1.2 m) Width — 4 ft. (1.2 m) Maximum Size (without drip board) 14 in. (36 cm) x 15 in. (38 cm) Low Proximity Maximum Size (without drip board) 14 1/2 in. (37 cm) x 14 in. (36 cm) Medium Proximity Maximum Size (without drip board) 15 in. (38 cm) x 14 in. (36 cm) High Proximity Medium Proximity Maximum Size (without drip board) 19 1/2 in. (49.5 cm) x 19 in. (48.2 cm) - High Proximity Low Proximity Maximum Size (without drip board) 18 in. (45.7 cm) x 18 in. (45.7 cm) High Proximity 1 1 1 1 1 1 1 1 1 1 ' For multiple nozzle protection of single fryers, see detailed information on Pages 4-12 through 4-14. 13-16 in. (33 — 41 cm) 16 — 27 in. (41 — 69 cm) 27 — 47 in. 20 — 27 in. 21 —34 in. 13-16 in. 25 — 35 in. (64-89 cm) Nozzle Part No. 430912 419337 419337 419334 419335 430192 419336 419336 419342 419342 419339 419340 419338 419342 419338 Nozzle Tip Stamping — Flow No. 1W 2W 2W 1 /2N 1N 1W 1W 1W 290 290 230 245 3N 290 3N Nozzle Application Chart (Continued) Hazard Fryer (Non -Split Vat Only)` Fryer (Split or Non -Split Vat) Fryer (Split or Non -Split Vat) Range Maximum Hazard. Dimensions Maximum Size (with drip board) 21 in. (53 cm) x 14 in. (36 cm) (Fry Pot must not exceed 15 in. x14in. (38 cm x 36 cm)) High Proximity Medium Proximity Maximum Size (with drip board) 25 3/8 in. (64.4 cm) x 19 1/2 in: (49.5 cm) (Fry pot side must not exceed 191/2 in. (49.5 cm) x 19 in. (48.2 cm) - High Proximity Low Proximity Maximum Size (with drip board) 18 in. (45.7 cm) x 27 3/4 in. (70.5 cm) High Proximity Minimum Nozzle Nozzle Quantity Heights 1 1 1 Maximum Size (with drip board) 14 in. (36 cm) x 21 in. (53 cm) 1 Low Proximity Maximum Size (with drip board) 141/2 in. (37 cm) x 261/2 in. (67 cm) 1 Medium Proximity Longest Side 1 32 in. (81 cm) Area — 384 sq. in. (2477 sq. cm) Longest Side 28 in. (71 cm) Area — 336 sq. in. (2168 sq. cm) Longest Side (High Proximity)• 1 28 in. (71 cm) Area — 672 sq. in. (4335 sq. cm) Longest Side (Medium Proximity) 1 32 in. (81 cm) Area — 768 sq. in. (4955 sq. cm) Longest Side (Low Proximity) 2 36 in. (91 cm) Area —1008 sq. in. (6503 sq. cm) For multiple nozzle protection of single fryers, see detailed information on Pages 4-7 through 4-11. SECTION IV — SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-29 4-1-06 REV 5 27 — 47 in. 20 — 27 in. 21 34 in. 13-16 in. 25 — 35 in. (64-89 cm) 13-16 in. (33 — 41 cm) 16-27 in. (41 — 69 cm) 30 — 40 in. (76 - 102 cm) 40 — 48 in. (102 -122 cm) (With Backshelf) 40 — 50 in. (102.-127 cm) 30 — 40 in. (76 — 102 cm) 15 — 20 in. (38 — 51 cm) Nozzle Part No. 419339 419340 419338 419342 419338 419342 419342 419335 419333 419340 419341 419342 Nozzle Tip Stamping — Flow No. 230 245 3N 290 3N 290 290 1N 1F 245 260 290 SECTION IV – SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-30 REV.3 10-1-02 Nozzle Application Chart (Continued) Hazard Griddle Chain Broiler* (Overhead Protection) Chain Broiler (Horizontal Protection) Gas -Radiant Char -Broiler Electric Char -Broiler Lava -Rock Broiler Natural Charcoal Broiler Lava -Rock or Natural Charcoal Char -Broiler Minimum Maximum Hazard Nozzle Dimensions Quantity Longest Side (High Proximity) 1 48 in. (122 cm) Area – 1440 sq. in. (9290 sq. cm) Longest Side (High Proximity) 1 30 in. (76 cm) Area – 720 sq. in. (4645 sq. cm) Longest Side (High Proximity) .1 36 in. (91 cm) Area –1080 sq. in. (6968 sq. cm) Longest Side 1 (Medium Proximity) 48 in. (122 cm) Area –1440 sq. in. (9290 sq. cm) Longest Side (Low Proximity) 1 48 in. (122 cm) Area –1440 sq. in. (9290 sq. cm) Longest Side – 34 in. (86 cm) 2 Area –1088 sq. in. (7019 sq. cm) Length – 43 in. (109 cm) 2 Width – 31 in. (79 cm) Longest Side – 36 in. (91 cm) 1 Area – 864 sq. in. (5574 sq. cm) Longest Side – 34 in. (86 cm) 1 Area – 680 sq. in. (4383 sq. cm) Longest Side – 24 in. (61 cm) 1 Area – 312 sq. in. (2013 sq. cm) Longest Side – 24 in. (61 cm) 1 Area – 288 sq. in. (1858 sq. cm) Longest Side – 30 in. (76 cm) 1 Area – 720 sq. in. (4645 sq. cm) Nozzle Heights 30 – 50 in. (76 –127 cm) (perimeter located) 30 – 50 in. (76 –127 cm) (center located) 35 — 40 in. (89 – 102 cm) (perimeter located) 20 – 30 in. (51 – 76 cm) (perimeter located) 10 – 20 in. (25 – 51 cm) (perimeter located) 10 – 26 in. (25 – 66 cm) 1-3in. (3 – 8 cm) 15 – 40 in. (38 – 102 cm) 20 – 50 in. (51 – 127 cm) 18 – 35 in. (46 – 89 cm) 18 – 40 in. (46 – 102 cm) 14 – 40 in. (36 –102 cm) - Minimum chain broiler exhaust opening — 12 M. x 12 in. (31 cm x 31 cm), and not less than 60% of internal broiler size. Nozzle Part No. 419341 Nozzle Tip Stamping – Flow No. 260 419342 290 419335/417332 1N/1NSS 419342 290 419343 2120 419336/417333 1 W/1 WSS 419335/417332 419335/417332 419335/417332 419335/417332 419335/417332 419338 1N/1NSS 1N/1NSS 1N/1NSS 1N/1NSS 1N/1NSS 3N ytr+l' rteuuiafeq mecnanicai Ketease Assembly (3.0 gallon — Part No. 79290 or 1.5 gallon — Part No. 79291) contains the regulated release mechanism, ageni tank, expellant gas hose for agent tank hookup. and enclosure knockouts to facilitate installing actuation, piping; expellant piping; detection system: and additional equipment. This regu- lated releaseassembly is used in single, double, and multiple - tank systems and must' be mounted to a rigid -surface. The release mechanism can be used to interconnect both the actu- ation and expellant gas lines as required per system design. The regulator is designed to allow a constant flow of gas into the tank at 100 psi (690 kPa) when the system is actuated. In single, double, and multiple -tank systems. the provided expel- lant Gas hose connects the agent tank to the bottom outlet of the regulator. In double and multiple -tank system configurations. the back outlet of the regulator is used as an expellant gas feed for one additional tank -enclosure or tank -bracket hookup. The enclosure contains the required knockouts to facilitate this con - rection. If a pressure switch is to be attached to the regulator, additional fittings are required. The tank is mounted within the enclosure. The tank contains an adaptor/tube assembly with a burst disc union. The burst disc helps prevent siphoning of the agent up the pipe due to signifi- cant temperature fluctuations in the area where the tank is located. The tank is mild steel and. under normal conditions, requires hydrostatic testing. every twelve years. - The agent tank is shipped uncharged and must be filled with 1.53 Gallons (5.8 L) or 3.06 gallons (11.6 L) of only ANSULEX Low pH Liquid Fire Suppressant during installation. - The detection and additional equipment required per system design are connected to'ithe release mechanism. The enclosure contains knockouts to facilitate detection and additional hookups. The system can b : actuated automatically or manually. Auto- matic actuation occurs when a fusible link within the detection system separates in a fire condition. Manual actuation of the system occurs when personnel pull on the remote manual pull station pull ring. EXTINGUISHING AGENT ANSULEX Low pH Liquid Fire Suppressant (1.5 gallon — Part No. 79694 or 3.0 aalion — Part No. 79372) is .a potassium -based solution designed for fast knock -down and suppression of grease -related fires. The agent is shipped in plastic containers which provide one complete tank charge. Agent storage life expectancy is twelve years. The distributor must record the batch numbers and date of shipment receipt to be filed with each instal- lation record. ANSUL, Total Tank Type of Flow No.* Quantity System Type of Hardware 1-5 1 Single 1.5 Gal. Reg. Release 6-11 1 Single 3.0 Gal. Reg. Release ELECTRICAL SWITCHES — LOCATED _ltd E& AUTD-i The electrical switches are intended for use with electric gas valves, alarms, contactors, lights, contractor supplied electric power shut-off devices :and other electrical devicet t are designed to shut off or tum on when the system is actuated. Switches are available in kits: One Switch Kit, Part No. 423878, Two Switch Kit, Part No. 423879, Three Switch Kit, Part No. 423880, and Four Switch Kit, Part No. 423881. Each switch has a set of single -pole, double -throw contacts rated of 21 amp, 1 HP, 125, 250, 277 VAC or 2 HP, 250. 277 VAC. Mounting hardware is provided with each kit. R-102 RESTAURANT. FIRE SUPPRESSION SYSTEM (Standard UL 300 Listed) Nozzle Identification Chart Nozzle Nbzz{e T voa Part No. 1W Nozzle 419336 1WSS Nozzle 417333 1N Nozzle 419335 1 NSS Nozzle 417332 1/2N Nozzle 419334 3N Nozzle 419338 2W Nole 419337 2WH Nozzle 78078 Nozz;a Noz Stinoina Flov •W 1 '.W 1 1N 1 1N 1 1/2N 1/2 3N 3 2W 2 2WH 2 230 Nozzle 419339 230 245 Nozzle 419340 245 260 Nozzle 419341 260 290 Nozzle 419342 290 2120 Nozzle 419343 2120 1F Noz<le 419333 1F IIDo 1407.7..1..E -*OM. I1D0 Nitrogen Crtridae Required LT -20-R (7032) LT -30-R (5373) Carbon Dioxide Cartridge Reouired 101-10 (15850) 101-20 (17492) WE;I i 1 a E(stPrJS i s 5 S LAcck Sgkii5 O ?o 1.4631) 51' C 2 2 2 2 2 1 SECTION IX - APPENDIX UL EX. 3470 ULC CEx747 Page 9-1 7-1-98 REV. 3 SYSTEM SELECTION GUIDE NOTE: System options do not cover all conceivable variations. They are listed here as a general guideline to show the most common type arrangement for multiple systems, Based on certain system designs utilizing manifolding, non-manifolding, 3 -tank systems, etc., other tank/cartridge combinations can be designed. The combinations below are based on 11 flow, 3.0 gallon tanks and 5 flow, 1.5 gallon tanks. More competitive designs may be available by utilizing 12 flow and 6 flow systems when appropriate. Total Tank Type of y Nitrogen Carbon Dioxide Flow No.* Quantity System Type of Hardware Cartridge Required 1-5 Cartridge Required 1 Single 1.5 Gal. Reg. Release LT -20-R (7032) 101-10 (15850) 6-11 1 Single 3.0 Gal. Reg. Release LT -30-R(5373) ) 101-20 (17492) 12-16 2 Double 1.5 Gal. Reg. Release Double73022 3.0 Gal: Additional Tank Double(73022) 101 30 (15851) 17-22 2 Double 3.0 Gal. Reg. Release Double73022 3.0 Gal. Additional Tank Double(73022) 101 30 (15851)" 23-27 3 Multiple 1.5 Gal. Reg.Release LT -20-.R (7032) 101-10 (15850) 3.0 Gal. Reg. Actuator LT -A-101-30 (29187) 101-30 (15851y- 3.0 Gal. Additional Tank 28-33 28-33 (Optional) 34-38 3 Multiple 3.0 Gal. Reg. Release LT -30-R(5373) ) 101-20 (17492) 3.0 Gal. Reg. Actuator LT -A-101-30 (29187) 101-30 (15851y- 3.0 Gal. Additional Tank 3 Multiple 3.0 Gal. Reg. Release Double (73022) N/A (2) 3.0 Gal. Additional Tanks ? Multiple 1.5 Gal. Reg. Release Double73022 3.0 Gal. Additional Tank Double(73022) 101-30 (15851) 3.0 Gal. Reg. Actuator LT -A-101-30 (29187) 101-30 (15851)"' 3.0 Gal. Additional Tank 39-44 4 Multiple 3.0 Gal. Reg. Release Double73022 • 3.0 Gal. Additional Tank Double(73022) 101-30 (15851) 3.0 Gal. Reg. Actuator LT -A-101-30 (29187) 101-30 (1585' y-- 3.0 Gal. Additional Tank. 45-49 5 Multiple 1.5 Gal. Reg.Release LT -20-R (7032) 101-10 (15850) 3.0 Gal. Reg. Actuator LT -A-101-30 (29187) 101-30 (15851)•*" 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator LT -A-101-30 (29187) 101-30 (15851)- 3.0 Gal. Additional Tank 50-55 5 Multiple 3.0 Gal. Reg. Release LT -30-R(5373) ) 101-20 (17492) 3.0 Gal. Reg. Actuator LT -A-101-30 (29187) 101-30 (15851)- 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator LT -A-101-30 (29187) 101-30 (15851y- 3.0 Gal. Additional Tank 56-60 6 Multiple 1.5 Gal. Reg. Release Double73022 ( ) 101-30 (15851) 3.0 Gal. Additional Tank 3.0_Gal. Reg. Actuator LT -A-101-30 (29187) 101-30 (15851)- 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator-' LT -A-101-30 (29187) 101-30 (15851)' 3.0 Gal. Additional Tank 61-66 6 Multiple 3.0 Gal. Reg.Release Double (73022) 101-30 (15851)- 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator LT -A-101-30 (29187) 101-30 (15851)*" 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator LT -A-101-30 (29187) 101-30 (15851)"" 3.0 Gal. Additional Tank Based on 5 flow numbers for a 1.5 gal. system and 11 flow numbers for a 3.0 gal. system. See Pages 4-39 - 4-42 for exceptions. If tanks are manifolded, only a "double tank' nitrogen cartridge (Part No. 73022) can be used. - If tanks are manifolded, either an LT -A-101-30 nitrogen cartridge (Part No. 29187) or a double tank cartridge (Part No. 73022) can be used. 0 r Without Comments As Noted In Red Per The Attached Letter i nese plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is suhiect to errors and omissions which do not authorize violations o; adopted stanaaras and orornances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings atter this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureaus, By: (?c WUKWILA FIRE DENArc t n+�.►�t Please call: 575-4407 and give this lo�c0 No. and exact address for shut, 'own or restoration aoorovd. EraN 1 GA Odle Fool Typo: Cs' 2a'L X 24"WX3CH Rona .2 burners FIMi Typal Gu 12 L X 24-Wx3tr-n Fryer - Run NI W inty( Rip Fuel Typo: Go tar'L X 14TWX39'H Fryer -AP vat wotout DIP Fuel Type: fjei 15-1. x 1PwXlirH Fyn - Full rr t viehcid DI Fool lypr Ges 766 x IPwx3P11 — f ..p•q Fryer - Full Mot without Dlpdmd �./ Fuel e• Goa I--• 1A -L X 1WWx311' 00 .... n ,.o Yn rn vuTir okoc.•1 oo2 cza-ci_ N y g N a. 10 7 t] ? FT - Fo � rigl ,8 N G )4114 tv T r4 0. a• r a SECTION N SYSTEM DESIGN - ULE "170 LIC CEz747 :Page 4-28 REV.5 4-1-06 Nozzle Application Chart Ttie following Chart has; been developed to 2ssistiri calculating the quantity and type of nozzle required to protect eath duct, plenum; or appliance: - : . Hazard This chart for general :reference `only=See: complete d+ilsfor each type of hazard ' Maxiinuin' Hazard Dimensiorie' Duct orTranettion (Single Nozzle) . Duct or transition (Single Noe) : Duct orTransilon (Dual Nozzle) Electrostalic. Precipitator (At Base of :Duct) .. Plenum (Horizontal. Protection) Length = U nif° Perimeter - 50in. (127 crn) : -Diameter:- :l6 in. (40:6 cm)` Length iJntiinifed' Perimeter 'H 100. in: 054- Diameter 254Diameter 31;7/8 tri:?(81:gni) Length. ini'¢nited Perimeter:F150 ip::(381 cm) • Indrvidual Cell: Plenum (Horizontal Protection) Plenum (Vertical Protection) Fryer (Sprit or I Non -Split Vat) Fryer (Sprd or •. Non -Sprit \fat) Fryer (Split for Non -Sprit Vat)* Length -10 ft (31 m) Length 6 tt_.(1:8 rri) Width — 4-fit.112 m): -Length -44 it.:(? 2`m • Wi4ih-4 ft. (12 m Maximum See., :::. • (without drip ESoart>)';1 y 4 in: (36 15 r . (38 cm) Low,Pitndmity: • maximum:Size • (vvrthout:drip board) 14 -1r210 -437, -Cm) x?: 121 -fin. (36: cm): Medium. Prpdrruty'_ Mai imuiFa S•ize•' (whhout drnploard l :115 in:'(38:cm): x. ::14:ur. (36 cm): .. High Prcodmiiy Medium.P#dmity. Fryer (Non -;Split Vat Only) Maximurri.S•ize' .... (without chipboard) 191 /21ri:;(49:5 cir) 19 in ilgh Proxirriity:.` tow Proximity Ma�murn Size..; (without drip board) .° 18 in. -(45Jixn) x 18 in: '(45.7cm) High 430192 1W 419336 1W 4119336. 1W NozleTip Stamping• Flow No.. 1W 2W 2W 1/2N 1N .419339 419340 290 290 230 245 419338 3N - 419342 •. 290 For multiple i..Ie Prem of soak fryers, see detailed Paaes 4-i2Ihrouyh 914. 25-35 in. (64-89 cm) 419338 3N Nozzle Application Chart (Continued) 1-12zard Fryer (Non -Split Vat Only)* Fryer (Spkt or Non -Sprit \/) •Fryer (Split or Non -Split Vat) Range - Maximum Haiard Nole :Nozzle (puerility 'Heights Maximurn SiZe (Witir,dritYboard.) - . .• -21. in; (53 00.1) .*-• • - • • • • • • • .• •• : • . (Fj.Oot-riiLittpiit exceed.• ..*: . • 15 it xl4in. . • • I- : tat -cm* • • - • .1\itediurn PrCotkiiity- ....• MaxiMurn;.Siie(will-' drip board) : :.• • • 25 3/a-itl„:Asl-A.-aer_rj:;,.. '- • . _ . • •• (Frir:Pot side MISt riotexceed 19 l/2.in. -.• 1482 cr'6).-.1.f- 1."'•• High ProximityLow Proximxiy s • Mparnurn Size . " • . . -.-.. • • .. -. • • •••••••• . • (with drip board) • ••• .18 in..(45.7. CM) : s x 27 3!.4.irt, (705cm) - •'• z•-• MaXirrium Stie • (with drip board) • .14 (36 Cm) .• 21 'in: (53 Crp):- . Low Maxirn • (With-driii board) •••• - • : : 14112 (3Tarn) -26 11.2)6._ _:(67*1). •ietfium lvdnft . • &ECM% V5Tzti 3470 ULC CE):747 Page 4-Z5' 4-1-0S RS -it S Nozzle Part No_ 419339 419340 • 34. _ 419338 • 13 18 : 419342 • • 5 —35 in. • - 41-9338 64-49 CM) 1 {33-7;-41 cm) Longest Side ;•;:-.: : : 32 in7 Area:— 384 (2477-:Sct. cM) - :Longest Side • - gi*,arr0- Area —.336 schin. • . -'(2168 sq. crn) ; ":„ • Longest Sideltfigh Froximrty). • - 28 in. (71 cm) • Area :7672 sq: in. •-• : - Medium la'ioximity). 32 in.. (81 arri) : Area =768 .sq, in. (4955 sq. cm) Longest Side tow Proximity) 2 36 in. (p1 prro Area — 1008 sq. in. _ (6503 sq. cm) 3r r.jj n=le Amle=tonaf =Pie frYers,e detailectinforrnalion on Pag-4-7 through 4-11. . . . 419342 Noe Tip Srtiping — Pk* No. 230 245 3N 290 3N 290 16 —271n. 419342 290 •,-(41 — 69 cm) • .40 Oni) (VVith gaclollelf) - - • - .40. 50 in. • (1027127 'cni) 4-19335 419333 419340 -•30 7 40 in. 419341 (7-5_ 102 cm) 15 —20 in. 41934 2 (38 — 51-crt) 1N 245 20 290 SECTION IV — SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-30 REV. 3 10-1-02 Nozzle Application Chart (Continued) Hazard Griddle Chain Broiler' (Overhead Protection) Chain Broiler (Horizontal Protection) Gas -Radiant Char -Broiler Electric Char -Broiler Lava -Rock Broiler Natural Charcoal Broiler Lava -Rock or Natural Charcoal Char -Broiler Maximum Hazard Dimensions Longest Side (High Proximity) 48 in. (122 cm) Area —1440 sq. in. (9290 sq. cm) Longest Side (High Proximity) 1 30 in. (76 cm) Area - 720 sq. in. (4645 sq. cm) Longest Side (High Proximity) .1 36 in. (91 cm) Area —1080 sq. in. (6968 sq. cm) Longest Side 1 (Medium Proximity) 48 in. (122 crn) Area —1440 sq: in. (9290 sq. cm) Longest Side (Low Proximity) 1 48 in. (122 cm) Area =1440 sq. in. (9290 sq. cm) Longest Side — 34 in. (86 cm) 2 Area —1088 sq.. in. (7019 sq: cm) Length — 43 in. (109 cm) 2 Width — 31 in. (79 cm) Longest Side — 36 in. (91 cm) 1 Area — 864 sq. in. (5574 sq. cm) Longest Side — 34 in. (86 cm) 1 Area — 680 sq. in. (4388 sq. cm) Longest Side— 24 in. (61 cm) 1 Area — 312 sq. in. (2013 sq. cm) Longest Side — 24 in. . (61 cm) 1 Area - 288.sq. in. (1858 sq. cm) Longest Side — 30 in. (76 cm) 1 Area — 720 sq. in. (4645 sq. cm) Minimum Nozzle Quantity 1 Nozzle Heights 30 — 50 in. (76 —127 cm) (perimeter located) 30 — 50 in. (76 —127 cm) (center. located) 35-40 in. (89 102 cm) (perimeter locate (51 — 76 cm) (perimeter located) 10 — 20 in. (25 — 51 cm) (perimeter located) 10 — 26 in. (25-66 cm) 1-3 in. (3 — 8 cm) 15 —40 in. (38 -102 cm) 20 — 50 in. (51 — 127 cm) 18-35 in. (46 - 89 cm) 18-40 in. (46 =102 cm) 14 — 40 in. (36 -102 cm) ' Minimum chain broiler exhaust opening —12 in. x 12 in. (31 cm x 31 cm), and not less than 60% of internal broiler size. Nozzle Part No. 419341 Nozzle Tip Stamping — Row No 260 419342 .290 419335/417332 1N/1NSS - 419342 419343 290 • 2120 419336/417333 1 W/1 WSS 419335/417332 419335/417332 419335/417332 419335/417332 419335/417332 419338 1N/1NSS 1N/1NSS 1 N/1 NSS 1N/1NSS 1N/1NSS 3N ssenbfy (3.0 Gallon _ .Part NO. 79250 cr 1.5 canon !0. 75291) cor.t=_ins the reslated rle�e mechanism, , Pan asmanent an" e.^;' gas hose for'aoent tank hookup. and-encosure nockautS. to fediiitate installing aatcaiion piping," ez e!fani icing: Os -traction system. and additional equipment. This recu- 9• tion additional :ted release assembly is used in sioole, dcuble..and multiple- ank .systems and must be .mounted to a tinid surface. The elease mechanism can be sed to interconnect both the actu- tion and expellant gas tines as required per sFstem desiign.The eautator is designed to' allow a constant dcw of Cas irrto'the ank at 100 psi. (590 kPaj whet) the system is 'actuated:. 1 single. double, and multiple-tenk.systerP5 the pravid i! expel rit cas hose .connects the anent tank.10 the bottorn `outlet:of to reeuiator- In double.and. multlple-taik sjsem contTguratla ts,. le back outlet of the regulator is used ;:s an- ekpellar cas:feed.. r one addiiiional tank-emidosure or lank -bracket :tiobkuo: The :nclosure contains the required knockouts to facilitatethis".cOn71 Lection: 1f a pressure switch is to be attached to the regulator; :dditioral faunas are required. the tank; is mounted Within the"encibsufe. The tank contains _t adaptoritube asternbry with a burst disc union .iiie.burst disc . letps prevent siphonina.of the agent:uothe pipe" due to signuT- ..arit temperature fluctuations'in...the area=where- the-tank::is ocated. The tank is mild steel and, under normal ronditi0ns, raquires.hydrostatic testing'. every ;we'veThe agent tank is shipped uncharaed :and :must .belittled with_ 1.53 ealf:ons•-(5.6 L) or 3.06 gallons (11.6"!_). of.oiiiy. ANSULEX Low pH Liquid Fire Suppressant "during instal'atioit:::-.::. . The date .ti' r. ;enc' �r rjrtin! =t e ;�r reg)_; c4 o. desi rr are � a' tpac::-4#4.n!>: Qconnected tot*. release mecha�isrti..The endosure. containsimockouts to fa6Titate detection and additiionai.hoola%ps.:.. The system can bs actuated automatically or rnanuaity_:•f tits- :' Matic actuation ocarrs when a fusible fink within: the )detection .7 system Separates in a fire condr5on_1jfanuaj actuatiort:of-.the system occurs when personnel obit on the remote: manuar pull . station pull ruin. •• R-102 REST URANrr FIRE _SUPPRESS O N SYSTEM (Standard tit 300'i . _ Nome --�dentttii jNtonCe hart: No_- , Noz No9TVDPart NO. Stampj nG Ploy 1W Norte 419336 ; 1W .WSS.Nb�zle 417333 ; 1W n 1 1 N NOrie 1 a1 °335 } 1N 1 NSS Nozzle 417332 1 IN 1/2N Noale •419334 11/21 3N Nozzle 419339 1 3N 2W No1e 419337 ; 2W 2Wri Noz�1e 78078 12Vin.i EXTINGUIS'HING AGENT ANSULEX Liv pH Liquid Fire .5uppr ssant-(1...5 gallon 2 P No. 79694 or: 3.0 Callon Part No: 78372) is apoiassiurti=based solution .designed for knock-dowri; .and' suppression':of Grease -related. fires. The agent is shipped in plastic containers which provide one. complete tank :charge °.Agent:storage- ife e ectancy is twehre years: The distributor-:riustr rthe-batch numbers and date of shiprtient ..receipt Lobe filed .with eacli.instai- tation record. To;ali Tank Flow No' Quay 1-5 1 230 Norio `245 Noale 260 Norte 290 -Norte . 2120 Norte 1 F Norte'.•: 1166 1407.7-2.E 1 -a^C i r iCA.L Swrrcts.3 t ---OcAi:P_.:tt3:'cfsCi{-_AU-3j.: tie ele�gi - --:- - -. ....: switche..§ are intended. • for :i:se " ... ' alamts contactdrs, r ? e1e^trilet mover shirt -off do 9 , contractor._ suppped _ vices :and' other ei " , - t. uric:. • esigned to shut off or torr, on when the sem' ds c oaf. az e . •s.....i fs.acivatecl: w S .siatiable :m 011e Swat G`, P .No.. _ • .. _ . 1238$0 � Part No. 423879. Triuee Swilph.' ' ' ,af of 0 a-xcl Four Switftli }3t; Part -ho- c23B81.` £' �t No. _ singlelpole, double4ijrgy�,corfaCtsBch same 1rHPg` 25,250, 277 VAC or 2 .Hp 25C 2 Ci ounfing lie p arHP ,rovided with each kit. - 1S COMMON 419339 419340 419341 419342 419343 419333 -4t2 1 1/2 3 2 2 230 2 245 2 260 2 290 2 2120 2 1i= 1 lleo 1 Carbon Dioxide Cartridge Reoui; ed 101-10 (15950) 101-20 (17452) rL7Li� L" 0\7t7_1:71 -s) { t _ .HiS w1-tb-l n-_ r . SECTION IX - APPENDIX UL EX. 3470 ULC CEx747 Page 9-1 10-1-02 REV.5 SYSTEM SELECTION GUIDE Note: System options do not cover all conceivable variations. They are listed here as a general guideline to show the most common type arrangement for multiple systems, Based on Certain System designs utilizing manifolding, non-manifolding, 3 -tank systems, etc., other tank/cartridge combinations can be designed. The combinations below are based on 11 flow, 3.0 gallon tanks and 5 flow, 1.5 gallon tanks. More competitive designs may be available by utilizing 12 flow and 6 flow systems when appropriate. 'Total Tank Type of Row No.* Quantity System Type of Hardware Carbon Dioxide Nitrogen Cartridgee Required Cartridoe Required 1-5 1 Single 1.5 Gal. Reg. Release 101-10423439 ( ) LT -20-R (423429) 6-11 1 Single 3.0 Gal. Reg. Release 101-20423441 ( ) LT 3010 (423435) 12-16 2 Double 1.5 Gal. Reg.Release 101-30(423443) Double (423493) 3.0 Gal. Addition[ Tank 17-22 2 Double 3.0 Gal. Reg. Release 101-30 (423443)- Double (423493) 3.0 Gal. Additional Tank 23-33 3 Multiple 3.0 Gal. R Release keg. 101-20 (423441) LT -30-R (423435) 3.0 Gal. Reg. Actuator 101-30 (423443)"` LTA -101-30 (423491) 3.0 Gat. Additional Tank 23-27 3 Multiple 1.5 Gal. Reg. Release 101-10 423439 (Optional) ( ) ' LT 2010 (423429) 3.0 Gal. Reg. Actuator 101-30 (423443)- LT -A-101-30 (423491) 3.0 Gal. Additional Tank 28-33 3 Multiple 3.0 Gal. Reg. Release N/A (Optional) (2) 3.0 Gal. Additional Tanks Double (423493) 34-38 4 Multiple 1.5 Gal. Reg. Release 101-10423439 3.0 Gal. Reg. Actuator N/A ( ) LT -10 ( Double 3.0 Gal. Tank Box LT -A-101-30 ( (423423 491) 34-38 4 Multiple 1.5 Gal. Reg. Release 101-30 423443 (Optional) 3.0 Gal. Additional Tank ( ) Double (423493) 3.0 Gal. Reg. Actuator 101-30 (423443)"' LT -A-101-30 (423491) 3.0 Gal. Additional Tank 39-44 4 Multiple 3.0 Gal. Reg. Release 101-20423441 ( ) LT -30-0 (423435) 3.0 gal. Reg. Actuator N/A LT -A-101-30 (423491) Double 3.0 Gal. Tank Box • 39-44 (Optional) 4 Multiple 3.0 Gal. Reg. Release 101-30 (423443)" Double (423493) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)-' LTA -101-30 (423491) 3.0 Gal. Additional Tank 45-49 5 Multiple 1.5 Gal. Reg. Release 101-30 (423443) Double (423493) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator N/A LT -A-101-30 (423491) Double 3.0 Gal. Tank Box 45-49 5 Multiple 1.5 Gal. Reg. Release 101-10 (423439) LT 20-R (423429) (Optional) 3.0 Gal. Reg. Actuator 101-30 (423443) LTA -101-30 (423491) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443) LT -A-101-30 (423491) 3.0 Gal. Additional Tank Based on 5 flow numbers tor a 1.5 gaL system and 11 flow numbers for a 3.0 gal. system. •• If tanks are maniiolded, only `double tank' nitrogen cartridge (Part No. 423493) can be used. "' If tanks are manitolded. either an LT -A-101-30 nitrogen cartridge (Part No. 423491) or a double tank cartridge (Part Na 423493) can be used. O Without Comments O As Noted in Red Per The Attached Letter These plans have been reviewed by The Tukwila Fire prevention Bureau for conformance w th current City standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or ravisons to mese drawings after this date will void r '_ icceptaice ar require a resubmittal of re i s:. c-awings for suoseu..2nt approval. Final acceota^ce it subject to field test and Inspection by The Tukwila Fire 1'1 eventon Bureau. Date: %-)-"1-1 a- RY.1141 I I'UKWIL' FIRE DEPARTMENT ?!eat 206-575-44107 and rl:Nia this Fire Permit No. exact r'" /ress for shut - or r: gyration approval. REVISIONS DESCRIPTION DATE 10'-0" A.F.F. BOTT. OF SOFFIT BOTT. OF SIGN BAND BOTT. OF SOFFIT SPACE #FC11 0 TYPICAL ARMOVER TO NEW SPRINKLER. HEAD N.T.L ARGCO #3B OFFSET 45deg MIN WHERE LENGTH OF ALL THREAD ROD EXCEEDS 1,-1O" ADD SECOND RESTRAINT LINE RESTRAINT DETAIL 3/8 X 3-1/2 LAG SCREW FOR WOOD 3/8" KWIK BOLT FOR CONCRETE 1/4 X 1 TEK FOR BAR3OIST OR STEEL BEAM 3/8"x1-10 ALL THREAD ROD. MAX PER SINGLE RESTRAINT HANGER RING (UP TO 2" PIPE) NOTE: 1) SPACE WITH IN 6" OF A HANGER EVERY 42'-0". 2) BRACING PER NFPA-13(2007 ed.) SECTIONS 9.3.5.8.8, TABLE 9.3.5.8.8(c) AND 9.3.6-RESTAINT OF BRANCH LINES THICKNESS OF CONCRETE VARIES A - 3/8' X2-3/4' KWIK B0L'6 • t • DA • 1. A 3/8' ROD CPLG. CUT 3/8' A.T.R. (PER PLAN) RING HANGER FOR 1' TO 4' PIPE ALL LOCATIONS (O.N.O.) (1) (1) (1) (1) 3/8' x2-3/4' HILT) QIYIK BOLT 3/8' A.T.R. x (SEE PLAN) 3/8' ROD CPLG. PIPE HANGER RING LAS RECCOMENDED BY MFG. #13 HANGER DETAIL N.T.S. FIG. 65 BEAM CLAMP FIG. 69 RETAINING STRAP J4 LOCK NUT REQ'D VIEW A -A FIG. 100 ALL THREAD ROD �-- FIG. 200 ADJUSTABLE RING HANGER BOTTOM BEAM CLAMP, ROD, AND RING r CCE Without Comments As Noted In Red 0 Per The Attached Letter 1 nese plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is subject to errors and omissions which da not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings atter this date will void this.acceptance and wll require a resubmittal of revised drawings for subsequent approval. 02 HANGER DETAIL N.T.S. Final acceptance is subject to field test and inspection by The Tukwila Fire, Prevention Bure 1'UKWILA FIRE DEPARTMENT Please call: 575-4407, and give this job No.4.3— 53 and exact address for shut. down or restoration approval; ? O CE Weld stamps must be - inspected before pipe is 01 By .: _moi hung. Do not paint piping prior to hydrostatic test approval. GENER NOTES* �p14. Alt9iAi SPK. 1-15'�/e Nr -M/3 CP /mix/ a2 & FFL . I .RETAIL AREAS ARE DESIGNED IN ACCO WITH DANCE REQUIREMENTS OF N.F.P.A. 13 ODINARY HAZARD G OUP 2 MAX SPACING 130 SQ. FT. R IT THE 2. COSCO POINT OF CONNECTION 15 AT EXIST BUILDING SHELL SYSTEM 4" MAIN AS SHOWN ON THESE PLANS. 3. ALL PAINTING OF FIRE SPRINKLER PIPING (IF REQ) TO BE DONE BY OTHERS - 4. ALL WIRING BY OTHER. 5. ALL MATERIAL IS NEW U.L. LISTED AND MEETS THE REQUIREMENTS OF THE TUKWILA FIRE FIRE DEPT. 6. OWNER IS RESPONSIBLE TO ASSURE THAT STRUCTURE AS IT IS SHOWN ON CONTRACT DRAWINGS CAN ADEQUATELY SUPPORT ALL FIRE SPRINKLER PIPING LOADS. NO AUXILLIARY DEVICES OR ATTACHMENTS SHALL BE PROVIDED BY COSCO TO SUPPLIMENT THE STRUCTURE TO ACCOMODATE FIRE SPRINKLER - PIPING LOADS. 7. OWNER IS RESPONSIBLE TO PROVIDE ADEQUATE HEAT TO MAINTAIN 40 DEG. F. MINIMUM AT ALL TIMES YEAR ROUND. 8. SPRINKLER HEAD LOCATIONS INDICATED ON THESE DRAWINGS ARE NOT INTENDED TO BE "CENTER OF TILE" HEAD PLACEMENT: 9. COSCO ASSUMES NO RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, FOR THE CONDITION, PERFORMANCE OR CURRENT CODE COMPLIANCE OF THE EXISTING SYSTEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY. COSCO. 10. OWNER IS RESPONSIBLE TO ARRANGE FOR THE PERIODIC INSPECTION, TESTING AND MAINTENANCE OF THESE FIRE SPRINKLER SYSTEMS IN ACCORDANCE WITH THE MINIMUM REQUIREMENTS OF N.F.P.A. 25-2002 BY QUALIFIED PERSONNEL COMMENCING AFTER WARRANTY PERIOD HAS EXPIRED. THE FIRM THAT DESIGNED AND INSTALLED THIS SYSTEM 15 BEST QUALIFIED TO PROVIDE THE'ONGOING LONG TERM TESTING, MAINTENANCE AND SERVICING OF THIS SYSTEM(S). ****** FIELD NOTES ****** I) THREADED PIPE FROM I " THRU :2" SIZE TO BE SCH. 40 STD. WALL PIPE (IMPORT). 2) GROOVED END PIPE FROM 2 1/2" THRU 8" TO BE SC1-1.10 (IMPORT). 3) ALL GROOVED COUPLING ARE TO BE "RIGID" TYPE U.N.O. (IMPORT). 4) ALL THREADED FITTINGS ARE 300# CLASS D.I. (IMPORT). FIELD/NOTES r EXISTING PIPE NEW PIPE EXISTING HEAD NEW HEAD PERMIT # D08-086 r3 1.1 SCALE:1/4=1'--0 SPRINKLER HEAD LEGEND : SYMBOL S/N ORIFICE NPT K -FACT. HEAD FINISH PLATE FINISH TEMP. QUAN. RELIABLE MOD G4A CONCEALED SSP 1/2' 1/2' 5.6 BRASS WHT 165 Co REUABLE MOD G4A CONCEALED SSP RELIABLE MOD F1 FR REC SSP 1/2' 1/2' 1/2' 1/2' 5.6 5.6 BRASS CHR BLACK CHR 165 155 APPROVALS BY: I TOTAL SPRINKLERS THIS SHEET ••0 o.• •.® 00 00• • ®° I Fire Protection FIRE PROTECTION AND LIFE SAFETY SPECIALISTS WASHINGTON OFFICE 15000 Woodinville -Redmond Rd NE License No: Woodinville, Washington 98072. COSCOFP11ONM call (425) 686-8300 • fax (425) 827-4784 SAN DIEGO •'LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEA1TLE • ANCHORAGE COSCO www.coscofire.com PROJECT: CHICKEN NOW 2 ,o0na SOUTHCENTER taAs.PACE FC11 TUKWILA, WA 98188 111UN 18 2008. CONTRACT WITH: MT DESIGN INC. 151 SABAL PLAM DRIVE LONGWOOD, FL 32779 FRANK 704-929-1593 TuKWIIa Fire 4.2_4o(o(e $ i56° E>✓ DRArnNc TIRE FIRE SPRINKLER TENANT IMPROVEMENT DATE : 06/16/08 SCALE : 1/4= 1'-0" DRAWN BY : BRIAN SCHULZE 15SS7962 SHEET � � OF 1 KW i ' A, s N SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET \UIVSHEET TITLE FA -01 SYSTEM I \ FO N ATI O \ FA -02 TYPICAL DETAILS - WRI\G A\D MOUNT( \G FA -03 FRE ALAS V SYSTEM FLOG PLA\ FA -04 SYSTEM CALC U LATI O \ S r GE\EAL), �ISE�, SITE PLA\ WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) 2S STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) 2V SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) W ERE THE CABLE IS INSTALLED QUANTITY 2 1 1 1 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD n DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD B< LINEAR BEAM SMOKE DETECTOR. PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 IN/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING 1,4 D DUCT SMOKE DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP IN/ 1G RING CEILING gL C FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX CEILING IN/ 1-1/2" EXT. FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -W SIEMENS 4S DEEP BOX 80" A.F.F. IN/ 1-1/2" EXT. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX CEILING IN/ 1-1/2" EXT. L c Qc FIRE ALARM STROBE (CEILING MOUNT) FIRE ALARM STROBE (WALL MOUNT) FIRE ALARM SPEAKER (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING ZR -MC -W SIEMENS 4S BOX IN/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. SET -CW SIEMENS 4S DEEP BOX CEILING w/ 1-1/2" EXT. FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM B p STROBE WP (WEATHERPROOF) SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO B OTTO M SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR MULTI -VOLTAGE CONTROL RELAY MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JBOX FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD JUNCTI❑N BOX F.B.D. F.B.❑, N/A VERIFY IN FIFL,p A.F.F. F.B.D. ABOVE FINISHED FLOOR FURNISHED BY OTHERS N/A N/A N/A /A N/A N/A N/A NOT APPLICABLE N/A /A z 0 Withoutic ments N/A As Noted In Red U.O.N. UNLESS OTHERWISE NOTED N/A Per IheAttacheaLetter /A N/A N/A i nese plans have been reviewed by The Tukwila Fire EATHERPR❑❑F DEVICE N/A 7vention Bureau forcrmancewith current tD dards. Acceptance li 4blect to errors and N A omissions which do not authorize violations of adopted A comp RED AS BUILT ADD ❑R CHANGE N/A stanaaras and oramances. The responsibility for theA arc equacy of design restY(cl�at ily with the designees Additions, deletions or revisions to these drawings atter Fire C Certifici GREEN AS BUILT REMOVE N/A t/his date will void thi�s.acgepLance and will requir 1 resubmittal of revised drevised &di/16gsforsubsequenta Orblval. to th commer Test -in and 1 Failur BLUE AS BUILT NOTES T❑ CAD N/A Fi al acceptance is sub' o field test and ins t' by /� p The Tukwila FiretiPrevention Bureau. �, Date: 0 0 By: tO in a RE termin, TUKWILA FIRE DEPARfNrrrs� Please call: 575.4407 and give this job No. end exact address for shut' town or restoration approve): Copyright 2006 by Guardian Security Systems, FAX (206) 628-4990 LO CV CV '0 CV J• uJ RELEASE/REVISIONS m LU z a DESCRIPTION SHOP DRAWINGS LU 0 co 0 C C -J -J CO C10 CTS CC OW1O Z W C3 W CC �Q O� Q UWT 7=4 0L� Op (DI - C\1 NOTICE Ieted, signed, Tukwila )epartment Pre-test ate must be preser ted e Inspector prior to cement of AcceptE rice g of any Fire Alarm Detection Systems. e of test will result inspection Fee an I ation of the testing. XAD -' Zoon ukwita Fire Inc. All Rights Reserved CCALE: 1/8" =1 ' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/04/08 BACKROUND PLAN PROVIDED BY: \OB NUMBER:54497 SHEET k FA -011 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR i+ PREVI❑US ADDRESSABLE DEVIL O DUCT DETECTOR L❑CATION END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH 0 GROUND_0 HTRI-R OSTATUS LED 0 N.O. N. 0 COM 0 N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SSE (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE DEVICE TO NEXT ADDRESSABLE DEVICE + NOTE 11 VOLTAGE MAX, - CURRENT MAX. - CONT, RES, MAX, - MAX, CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN. LINE SIZE - MUSIC OUTLET SAMPLING TUBE INLET SAMPLING,—\ TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE LrAC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE f(+) STOP IF LAST DEVICE (-) FROM XLS CONTROL PANEL OR PREVI❑US ADDRESSABLE DEVICE (-) END OF LINE DEVICE RELAY CONTACTS (4.0A @ 125VAC) (4.OA @ 30VDC) 27 VDC 3,5 r1A DURING POLLING 10 OHMS 200 FT. (18 AWG) 0.02uF 0.04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTI❑N. TB1 S 0 0 0 0 123456 HC TB2 D 654321 0 0 O m tV (3.6K 1/4W) SUPERVISED / SWITCH 7' ; GROUND NOTE: O © HTRI-D OSTATUS LED CO 0 m NOT USED CO m O FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL `ABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC � 0 0 0 1 J.- J. T T T 0 PAD -3 0 0 00 O INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 0 0 0 0 0 24K TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE NAC -4 NAC -3 NAC -2 NAC -1 END OF LINE DEVICE 3.6K 1/4W) UPERVISED -WITCH ( FRONT VIEW � l NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. � NOT USED REMOTE + DEVICE LOOP NOT USED REMOTE DEVICE LOOP 0 0 0 FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> 470 OHMS �N! EOL 0 WI 1 INPU + 9 9 TCM -1 Q 8 0 it' MOO O • 41 C O_CI CO e TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE N01 FROM REMOTE POWER SUPPLY ('S' CABLE) FROM FACP <V❑ICE CIRCUIT) C'V' CABLE) + `J (STROBE) SPEAKER (4) (-) EARTH GROUND 0 --).(+)TO NEXT DEVICE OR >{-) STOP IF LAST DEVICE ( STROBE-) (S ) STROBE SPEAKER (4) (-) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY 80" A.F.F. 4S DEEP BOX W/ 1-1/2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE TO NEXT DEVICE ❑R END OF LINE TO NEXT DEVICE ❑R END OF LINE NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER 11N TEMPERA RE: +32'F (0' C) TO 100' F 38 C) HUMIDITY: 0bb00O-9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN ( ) ,— DATA IN (+) > DEVICE IS USTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WWIITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT DEVICE F > (-) DATA OUT > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID —\ CEILING HARD LID .... SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION `N, CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTION BOX—. MOUNTED ON \ CEILING FLEX \ JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT FI i O O O O IL TO NEXT DEVICE CADDY BAR �—J SMOKE DETECTOR ------ SMOKE DETECTOR MOUNTING SCALE:NONE "---- SUSPENDED ILLUMINATED CEILING DO \OT I\ S 0 LL ADDRESSABLE IItJT ATPNG DEVICES �,NTIL PREP OGRMMED WITH DEVICES ADDRESS. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved Mfti •4 I743. IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS Lu 5/15/08 Q a 9 CCCCa z z 0 0 z t� z CC -§"" J W J SCALE: 1 /8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/04/08 BACKROUND PLAN PROVIDED BY: %OB NUMBER:54497 FA -02 I.� i1 !I 11-rr A.F.F. BAND BUM OF SIGN SAND'" OL—S1 F.F. OP G(.1FFYf 11. lin i D 4i-••=,,,/, NORTH :' Hort. OF ENr1STINCa LANDLORD FLOATING CFIL NG ELEMENT ---- 0I/ OsOFuLemt°ln IJCdff F1Y: LIFT SEE ELECT. CHICKEN NOW WESTFIELD SOUTHCENTER MALL SCALE 118"=1' FLAG NO ES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,CSEE SIEMENS INSTALLATION SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICAL CONTRACTOR, SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. PLANS \OT APPROVED DO NOT INSTAL ADD-RESSABLE INATIATING DEVICES U\ U IL DREPOGRAMN97D WASH DEVICES DDRESS. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved IMma e FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS DATE 5/15/08 )� a«CCC -J CO J co CC X00 Z VW E'- O 2 __ W fsQ U W .— -] o Co D co I— CV LIJ ct Q uJ SCALE: 1/8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/04/08 BACKROUND PLAN PROVIDED BY: \0B NUMBER:54497 J SHEET FA -03 SYSTEM CALCULATIONS 0 CHICKEN NOW NORTH CHICKEN NOW WESTFIELD SOUTHCENTER MALL iy�i 1 .L; 0 5:.;1rr---*---': z--- - 1 ' 3 L m -- ---- 1 ID SCALE 1132".1 EX RISER DIAGRAM CHICKEN NOW CHICKEN NOW FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL 1 w 5/15/08 Panel: CHICKEN NOW Wire Resistance 1.62 Q in Date: June 4, 2008 CURRENT TOTAL= Current Load: Standby: Alarm: S1 _ Current Load: Standby: Alarm: QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 SET -MC @15CD 64 128 Device Type Qty Amps Total Amps Total 0.62 Device Type SET -MC @30CD Qty Amps Total Amps Total 1 HFP-11 o SET -MC @75CD 0.0022 0.0022 0.0023 Total Device Load, Amps (I) 0.13 0 SET -MC @110CD 233 0 AD2-P 1 0.0635 0.0635 0.064 0.064 SET-HMC-C@115CD Main System Board 0 1 0.03 0.03 0.030 0.030 0.08 HTR -R SET-HMC-C@177CD 2 0.009600 0.0096 0.021 0.042 SET -MC @15CD (E= 1* R) 2 0 SET -HMC @135CD 318 0.064 0.128 HTRI-D ■ 0.001600 0 0.0035 445 0 SET -MC @30CD ■ (20.4 - E) 0.098 0 Z-MC@15CD ICP -B6 0 0.005 SET -MC @75CD 0 Z-MC@30CD 98 0 0.175 0 SET-MC-CW@110CD 233 0 SET -MC @110CD 0.233 2 TOTAL mA= 128 12 191 20.32078848 128 SET HMC-C@115CD 0.318 Notification Appliance Circuit Detail SET HMC-C@135CD PROJECT: WESTFIELD SOUTHCENTER MALL 0.318 Panel: CHICKEN NOW Wire Resistance 2.58 0.0731 Amps 0.106 Amps SET HMC-C@185CD CIRCUIT: SPEAKER CIRCUIT 0.445 _ QTY Device Type ZR -MC @15CD Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 0.064 Standby Current Load: 70.7V1/8 0.0731 Amps For 24 Hours = 1.754 Amp -hours ZR -MC @30CD Total Wire Resistance (R) 0.99 0 �.�.�..._a. ... - _ 0 0.098 - (WL*2)*(R/ft) _ �� 0 HCP I Total Device Load, Amps (I) 0.00 0 0.0015 0 0 0 Alarm Current Load: 0.106 Amps For 5 Minutes= 0.009 Amp -hours 0 0 0.03 Amps 0.158 Amps 0 0 0 (E= I* R) 0 0 0 EOL Voltage 25% Derating= 2.204 Amp -hours 0 Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours 0 0 0 0 DEVICES= 2 TOTAL mA= 3.6 14 191 2039645198 3.6 Alarm Current Load: 0.158 Amps For 5 Minutes= 0.013 Amp -hours Total System Current Load: 2.204 Amp -hours 25% Derating= 0.917 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.917 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH 0 CHICKEN NOW NORTH CHICKEN NOW WESTFIELD SOUTHCENTER MALL iy�i 1 .L; 0 5:.;1rr---*---': z--- - 1 ' 3 L m -- ---- 1 ID SCALE 1132".1 EX RISER DIAGRAM VOLTAGE DROP CALCULATION Cot yriaht 2006 by Guardian Security Systems, Inc. All Rights Reserved FAX (206) 628-4990 RELEASE/REVISIONS REV. BY: z Q Notification Appliance Circuit Detail 1 DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL 1 w 5/15/08 Panel: CHICKEN NOW Wire Resistance 1.62 Q in Date: June 4, 2008 CURRENT TOTAL= 128 CIRCUIT: S1 _ QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 SET -MC @15CD 64 128 ■ Total Wire Resistance (R) 0.62 0 SET -MC @30CD 98 0 -_ 1 (WL * 2) *Rift) o SET -MC @75CD 175 0 Total Device Load, Amps (I) 0.13 0 SET -MC @110CD 233 0 . (Total Cct Load) 0 SET-HMC-C@115CD 318 0 ■ Voltage Drop ( E) 0.08 0 SET-HMC-C@177CD 445 0 ■ (E= 1* R) 20.32 0 SET -HMC @135CD 318 0 ■ EOL Voltage 0 SET -HMC @185CD 445 0 ■ (20.4 - E) 0 Z-MC@15CD 64 0 0 Z-MC@30CD 98 0 0 SET-MC-CW@110CD 233 0 DEVICES= 2 TOTAL mA= 128 12 191 20.32078848 128 Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: CHICKEN NOW Wire Resistance 2.58 Date: June 4, 2008 CURRENT TOTAL= 3.6 CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 70.7V1/8 1.8 3.6 Total Wire Resistance (R) 0.99 0 �.�.�..._a. ... - _ 0 0 0 - (WL*2)*(R/ft) _ �� 0 I Total Device Load, Amps (I) 0.00 0 0 0 0 (Total Cct Load) 0.00 0 0 Voltage Drop ( E) 0 0 0 (E= I* R) 0 0 0 EOL Voltage 20.40 00 0 0 (204-E) 0 0 0 0 DEVICES= 2 TOTAL mA= 3.6 14 191 2039645198 3.6 VOLTAGE DROP CALCULATION Cot yriaht 2006 by Guardian Security Systems, Inc. All Rights Reserved FAX (206) 628-4990 RELEASE/REVISIONS REV. BY: z Q DESCRIPTION SHOP DRAWINGS w 5/15/08 Q in 00 CO -J eco t7� 0 W IW- Q Z w(~5 Z 2 __ W cc 15w W r CC i U oD N~ is w cf) z w z 0 DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/04/08 BACKROUND PLAN PROVIDED BY: \0B NUMBER:54497 FA -04 2600 SOUTHCENTER MALL FC -11 FOOD COURT ASSOCIATED PERMITS 08-F-293 08-S-344 12-H-164 08-H-358 FIRE DEPARTMENT HOOD SUPPRESSION PLAN REVIEW COMMENTS Project Name: Chicken Now 2600 Southcenter Mall FC -11 Permit No.: 08-H-358 Date: June 25, 2008 Reviewer: Steve Kohlerr Fire Prevention Inspector/plan review (206)575-4407 • Nozzle heights above appliances to be per manufacturers installation guidelines. • Install splash guards between fryers and ranges/charbroilers. • Upon activation of the suppression system, the make-up air supply will shut off and the exhaust will keep running. • Type 1 hood systems shall be designed and installed to automatically activate the exhaust fan whenever cooking operations occur. The activation of the exhaust fan shall occur through an interlock with the cooking appliances, by means of heat sensors or by means of other approved methods. • Activation of the suppression system shall shunt all electrical power under the hood as well as the gas supply. • Install a "K" rated portable fire extinguisher within 30 ft. of the cooking equipment. • The hood suppression system shall be monitored by a U.L. Central Monitoring Station. FIRE DEPARTMENT HOOD SUPPRESSION PLAN REVIEW COMMENTS Project Name: Chicken Now A*** 2600 Southcenter Mall FC -11 Permit No.: 12-H-164 Date: July 24, 2012 Reviewer: Al Metzler Fire Protection Project Coordinator (206) 575-4407 option # 2 (Inspection Requests) (206) 971-8718 (Plan Review Questions) F • Nozzle heights above appliances to be per manufacturers installation guidelines. • Fryers shall be installed with at least a 16 inch space between the fryer and surface flames from adjacent cooking equipment or a minimum 8 inch high steel or tempered glass baffle plate shall be installed between the appliances. • Upon activation of the suppression system, the make-up air supply will shut off and the exhaust will keep running. • Type 1 hood systems shall be designed and installed to automatically activate the exhaust system whenever cooking operations occur. The activation of the exhaust system shall occur through an interlock with the cooking appliances, by means of heat sensors or by means of other approved methods. • Activation of the suppression system shall shunt all electrical power under the hood as well as the gas supply. • Install a "K" rated portable fire extinguisher within 30 ft. of the cooking equipment. • The hood suppression system shall be monitored by a U.L. Central Monitoring Station. • A minimum 110 candela horn/strobe shall be installed above the kitchen hood suppression system manual pull station at a height of 80 inches above the floor. • A separate fire alarm permit from the Tukwila Fire Department is required for all fire alarm work. • The suppression system manual pull station shall be located no closer than 10 ft. and no farther than 20 ft. from the cooking equipment and be placed at a height of 42 to 48 inches above the floor. • The inside lower edge of the hood shall overhang or extend a horizontal distance of not less than 6 inches beyond the edge of the top horizontal surface of the appliance on all open sides. The vertical distance between the front lower lip of the hood and such surface shall not exceed 4 feet. • If cooking appliances are wheeled, the appliance wheels shall be set in tracks permanently mounted to the floor to ensure appliance is returned to original location if moved for cleaning or maintenance. } b9SLae ZZ si kck GAadIa Feld Tpaa! Ce 2a'1. X 24'WX26"N Boge .2 burners F� Type G.. Irl K2rWX3erri �ryr-I i V.1Wmo r Fuld Typal Go Irl x wwxarH Fryer Rol Type: Gas MOM 1WL x 1PWx411-14 Fry■.- Full Val lel Mad N r rwx3erw o Ryer - Fuel 7yFFi.I aiaag Dla�■d�, pe* Gac trl x IrwxSrw PL212,75 U J L 14.37 N. N. W N. N. 5 • t 4 ce " N. N. - • ...i z J IV 0 11- 0 0 uI 0 1• OZ Fo G C (^T_` r LA z cp IONE 5 Et Hoof Mil. Hood 1 -SEC' E thatw1 Ccllar. 121 W)C 1 g ° a N V- r N a+if 4,71G ITiligi Part No. ZZ 182756A Drawing No. ZZL ST182756A ANSUL R-102_ FIRE SYSTEM PARTS JOITmrs+ TAINS CDtFIDENT(I4L IIF THE C113KPANY [iF THE CAHP/WNY fIN REDIJE4T. 1J4TION tT WNTAINS CLJIISED TD PERSENS TV CEIsSISTENT WITH 'HE DDCIR'ENT 1, I'V PARR TF i DESCRP1WPl MEDI I1S41ALLONANS0E* T037 13 4 anLLLINIAtrllex 417J'%I ISFAIES DETECTOR FUSEiLE LDJitS ITBIYj 1 1 218:4 IT T LPZ 1GAS V Jt IF13d]DETERIMED 15!50 LD1 -10 CARBON (ROME CART_ 5373 LT 111F1 NTAOGEM CPRTHIUf 13E61 114140 CAFBQ4 U100»JDE CART - G 12 YES 421E53 IREGLIIATfD REIBISE ASSY 430850 IREG:I A -1E IACTWTORASSY 110501 I GE3.1 REGULATED ACTUATOR 42!J1E.2 3p CIAllf111 TANKPSSFIJBLY 42Pa70 13.G GALLON TANK {aTC BIKE dIVR 4 115 CALLON OM AVZLI3LY 4L1S (REMOTE PULL STATION 4271 GB IFULIEY TEF 15621 IWRE ROPE (4D FF_ETl 1 1 42.5578 DP DE ELECTRICAL SWITCH t 1 IAJAR LEN' SUM_ I1JRfl6IRO€E 10 1 415571 THIGH TEI P PLLLEY ELBC. 77164 313 RRQUICK.SF& 77216 131 IM. COMPREBSK)N SEA 701=0 lin Pt OCYJC47WrSEAL ?Ma IFIDOD SEA. 419373 11Ft 72LET1FLOM 418314 I1/2 N IJO2 LE I E0- 411015 11Jr h13721.E 11 FLC.Y1 414018 111t/No22LE11 F101,10 411137 I2W NDi21E [1 ELMS) 4199713 I361 NDZZL.E 13 ILFW5S1 41!3]0 1250 KD721E 12 FUR%) 411340 1155 KaTI E 12 FLOPS) 419141 1291 10723E 12 FLOWS) 414042 2W 6DOLb.E R Ftp/+) 4111343 12121 NOZZLE f2ELCRI9I 470012 I11UD 110271E 11 FtOM 41150E ISM4EL/LPPTIA CFROVIE45DEGREEEIEKY$rS Hood Masi: Hood 1 -SECTION 1 E.halsl Ccllar. 12114"( 14' Htad {andel C -HEV -11-S TUTTAL IJ0 D FLOW POINTS 2 10 LPL SYS LI MED FI01,4 P01645 20 MINT/774E SYs16J7 FLOW POINT -5 20 DISTRIBUTOR RESPONSJBIIITIES - cook011A11i10N OF JCB PiIrALLAT1DNYJIIh1.b[i D019TRACTOR. -G49 VALVE W LL<LP TO RELEASE VEORAMSN 1111AN lJT .SELE 6 TAT E4E VALVE AS KEI:IESWIYj -6E401E PULL STATION HOO1lUP EL EASE NEr.RA Sld -a10R131W, TEST INct. M1 CER TT1rJ.1TtI1 DF sfSTEM FIPINGAND NU22LES FROM FACTORY mecum 4'iM IFY APPLIANCE DWFS IF SHELVES CR &AJ.Jlt4AYDETi5 GtJ "THE APPIIA ICE LYTERFEREWRH H022LE D[3[RAflJ E. - SUPPLY PPM BETWEEN 6LILTIPLE HCOCS, WORAMY.TEWITH HDOD EN9TALLER FCR PROPER GTIEMAUI H DF MJU1PLE Hma% UL 300 FIRE PROTECTION SYSTEM S5904799 ('1-nc (FN NMI& gFATT1 F WA 8 771 8 2 7 5 6 A H 42 O QOid ALIS SECTION IV — SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-28 REV.5' 4-1-06 Nozzle Application Chart The following chart has been developed to assist in calculating the quantity and type of nozzle required to protect each duct, plenum, or appliance. NOTICE This chart is for general reference only. See complete details for each type of hazard. Hazard ► Duct or Transition (Single Nozzle) Duct or Transition (Single Nozzle) Duct or Transition (Dual Nozzle) Electrostatic Precipitator (At Base of Duct) Plenum (Horizontal Protection) ► Plenum (Horizontal Protection) Plenum (Vertical Protection) P. Fryer (Split or Non -Split Vat) Fryer (Split or Non -Split Vat) Fryer (Split or Non -Split Vat)' Fryer (Non -Split Vat Only) Minimum Maximum Hazard Nozzle Nozzle Dimensions Quantity Heights Length — Unlimited 1 — Perimeter -50 in. (127 cm) Diameter —16 in. (40.6 cm) Length — Unlimited 1 Perimeter —100 in. (254 cm) Diameter — 31 7/8 in. (81 cm) Length — Unlimited Perimeter -150 in. (381 cm) Diameter — 48 in. (122 cm) Individual Cell Length —10 ft. (3.1 m) Length — 6 ft. (1.8 m) Width — 4 ft. (1.2 m) Length — 4 ft. (1.2 m) Width — 4 ft. (1.2 m) Maximum Size (without drip board) 14 in. (36 cm) x 15 in. (38 cm) Low Proximity Maximum Size (without drip board) 14 1/2 in. (37 cm) x 14 in. (36 cm) Medium Proximity Maximum Size (without drip board) 15 in. (38 cm) x 14 in. (36 cm) High Proximity Medium Proximity Maximum Size (without drip board) 19 1/2 in. (49.5 cm) x 19 in. (48.2 cm) - High Proximity Low Proximity Maximum Size (without drip board) 18 in. (45.7 cm) x 18 in. (45.7 cm) High Proximity 1 1 1 1 1 1 1 1 1 1 ' For multiple nozzle protection of single fryers, see detailed information on Pages 4-12 through 4-14. 13-16 in. (33 — 41 cm) 16 — 27 in. (41 — 69 cm) 27 — 47 in. 20 — 27 in. 21 —34 in. 13-16 in. 25 — 35 in. (64-89 cm) Nozzle Part No. 430912 419337 419337 419334 419335 430192 419336 419336 419342 419342 419339 419340 419338 419342 419338 Nozzle Tip Stamping — Flow No. 1W 2W 2W 1 /2N 1N 1W 1W 1W 290 290 230 245 3N 290 3N Nozzle Application Chart (Continued) Hazard Fryer (Non -Split Vat Only)` Fryer (Split or Non -Split Vat) Fryer (Split or Non -Split Vat) Range Maximum Hazard. Dimensions Maximum Size (with drip board) 21 in. (53 cm) x 14 in. (36 cm) (Fry Pot must not exceed 15 in. x14in. (38 cm x 36 cm)) High Proximity Medium Proximity Maximum Size (with drip board) 25 3/8 in. (64.4 cm) x 19 1/2 in: (49.5 cm) (Fry pot side must not exceed 191/2 in. (49.5 cm) x 19 in. (48.2 cm) - High Proximity Low Proximity Maximum Size (with drip board) 18 in. (45.7 cm) x 27 3/4 in. (70.5 cm) High Proximity Minimum Nozzle Nozzle Quantity Heights 1 1 1 Maximum Size (with drip board) 14 in. (36 cm) x 21 in. (53 cm) 1 Low Proximity Maximum Size (with drip board) 141/2 in. (37 cm) x 261/2 in. (67 cm) 1 Medium Proximity Longest Side 1 32 in. (81 cm) Area — 384 sq. in. (2477 sq. cm) Longest Side 28 in. (71 cm) Area — 336 sq. in. (2168 sq. cm) Longest Side (High Proximity)• 1 28 in. (71 cm) Area — 672 sq. in. (4335 sq. cm) Longest Side (Medium Proximity) 1 32 in. (81 cm) Area — 768 sq. in. (4955 sq. cm) Longest Side (Low Proximity) 2 36 in. (91 cm) Area —1008 sq. in. (6503 sq. cm) For multiple nozzle protection of single fryers, see detailed information on Pages 4-7 through 4-11. SECTION IV — SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-29 4-1-06 REV 5 27 — 47 in. 20 — 27 in. 21 34 in. 13-16 in. 25 — 35 in. (64-89 cm) 13-16 in. (33 — 41 cm) 16-27 in. (41 — 69 cm) 30 — 40 in. (76 - 102 cm) 40 — 48 in. (102 -122 cm) (With Backshelf) 40 — 50 in. (102.-127 cm) 30 — 40 in. (76 — 102 cm) 15 — 20 in. (38 — 51 cm) Nozzle Part No. 419339 419340 419338 419342 419338 419342 419342 419335 419333 419340 419341 419342 Nozzle Tip Stamping — Flow No. 230 245 3N 290 3N 290 290 1N 1F 245 260 290 SECTION IV – SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-30 REV.3 10-1-02 Nozzle Application Chart (Continued) Hazard Griddle Chain Broiler* (Overhead Protection) Chain Broiler (Horizontal Protection) Gas -Radiant Char -Broiler Electric Char -Broiler Lava -Rock Broiler Natural Charcoal Broiler Lava -Rock or Natural Charcoal Char -Broiler Minimum Maximum Hazard Nozzle Dimensions Quantity Longest Side (High Proximity) 1 48 in. (122 cm) Area – 1440 sq. in. (9290 sq. cm) Longest Side (High Proximity) 1 30 in. (76 cm) Area – 720 sq. in. (4645 sq. cm) Longest Side (High Proximity) .1 36 in. (91 cm) Area –1080 sq. in. (6968 sq. cm) Longest Side 1 (Medium Proximity) 48 in. (122 cm) Area –1440 sq. in. (9290 sq. cm) Longest Side (Low Proximity) 1 48 in. (122 cm) Area –1440 sq. in. (9290 sq. cm) Longest Side – 34 in. (86 cm) 2 Area –1088 sq. in. (7019 sq. cm) Length – 43 in. (109 cm) 2 Width – 31 in. (79 cm) Longest Side – 36 in. (91 cm) 1 Area – 864 sq. in. (5574 sq. cm) Longest Side – 34 in. (86 cm) 1 Area – 680 sq. in. (4383 sq. cm) Longest Side – 24 in. (61 cm) 1 Area – 312 sq. in. (2013 sq. cm) Longest Side – 24 in. (61 cm) 1 Area – 288 sq. in. (1858 sq. cm) Longest Side – 30 in. (76 cm) 1 Area – 720 sq. in. (4645 sq. cm) Nozzle Heights 30 – 50 in. (76 –127 cm) (perimeter located) 30 – 50 in. (76 –127 cm) (center located) 35 — 40 in. (89 – 102 cm) (perimeter located) 20 – 30 in. (51 – 76 cm) (perimeter located) 10 – 20 in. (25 – 51 cm) (perimeter located) 10 – 26 in. (25 – 66 cm) 1-3in. (3 – 8 cm) 15 – 40 in. (38 – 102 cm) 20 – 50 in. (51 – 127 cm) 18 – 35 in. (46 – 89 cm) 18 – 40 in. (46 – 102 cm) 14 – 40 in. (36 –102 cm) - Minimum chain broiler exhaust opening — 12 M. x 12 in. (31 cm x 31 cm), and not less than 60% of internal broiler size. Nozzle Part No. 419341 Nozzle Tip Stamping – Flow No. 260 419342 290 419335/417332 1N/1NSS 419342 290 419343 2120 419336/417333 1 W/1 WSS 419335/417332 419335/417332 419335/417332 419335/417332 419335/417332 419338 1N/1NSS 1N/1NSS 1N/1NSS 1N/1NSS 1N/1NSS 3N ytr+l' rteuuiafeq mecnanicai Ketease Assembly (3.0 gallon — Part No. 79290 or 1.5 gallon — Part No. 79291) contains the regulated release mechanism, ageni tank, expellant gas hose for agent tank hookup. and enclosure knockouts to facilitate installing actuation, piping; expellant piping; detection system: and additional equipment. This regu- lated releaseassembly is used in single, double, and multiple - tank systems and must' be mounted to a rigid -surface. The release mechanism can be used to interconnect both the actu- ation and expellant gas lines as required per system design. The regulator is designed to allow a constant flow of gas into the tank at 100 psi (690 kPa) when the system is actuated. In single, double, and multiple -tank systems. the provided expel- lant Gas hose connects the agent tank to the bottom outlet of the regulator. In double and multiple -tank system configurations. the back outlet of the regulator is used as an expellant gas feed for one additional tank -enclosure or tank -bracket hookup. The enclosure contains the required knockouts to facilitate this con - rection. If a pressure switch is to be attached to the regulator, additional fittings are required. The tank is mounted within the enclosure. The tank contains an adaptor/tube assembly with a burst disc union. The burst disc helps prevent siphoning of the agent up the pipe due to signifi- cant temperature fluctuations in the area where the tank is located. The tank is mild steel and. under normal conditions, requires hydrostatic testing. every twelve years. - The agent tank is shipped uncharged and must be filled with 1.53 Gallons (5.8 L) or 3.06 gallons (11.6 L) of only ANSULEX Low pH Liquid Fire Suppressant during installation. - The detection and additional equipment required per system design are connected to'ithe release mechanism. The enclosure contains knockouts to facilitate detection and additional hookups. The system can b : actuated automatically or manually. Auto- matic actuation occurs when a fusible link within the detection system separates in a fire condition. Manual actuation of the system occurs when personnel pull on the remote manual pull station pull ring. EXTINGUISHING AGENT ANSULEX Low pH Liquid Fire Suppressant (1.5 gallon — Part No. 79694 or 3.0 aalion — Part No. 79372) is .a potassium -based solution designed for fast knock -down and suppression of grease -related fires. The agent is shipped in plastic containers which provide one complete tank charge. Agent storage life expectancy is twelve years. The distributor must record the batch numbers and date of shipment receipt to be filed with each instal- lation record. ANSUL, Total Tank Type of Flow No.* Quantity System Type of Hardware 1-5 1 Single 1.5 Gal. Reg. Release 6-11 1 Single 3.0 Gal. Reg. Release ELECTRICAL SWITCHES — LOCATED _ltd E& AUTD-i The electrical switches are intended for use with electric gas valves, alarms, contactors, lights, contractor supplied electric power shut-off devices :and other electrical devicet t are designed to shut off or tum on when the system is actuated. Switches are available in kits: One Switch Kit, Part No. 423878, Two Switch Kit, Part No. 423879, Three Switch Kit, Part No. 423880, and Four Switch Kit, Part No. 423881. Each switch has a set of single -pole, double -throw contacts rated of 21 amp, 1 HP, 125, 250, 277 VAC or 2 HP, 250. 277 VAC. Mounting hardware is provided with each kit. R-102 RESTAURANT. FIRE SUPPRESSION SYSTEM (Standard UL 300 Listed) Nozzle Identification Chart Nozzle Nbzz{e T voa Part No. 1W Nozzle 419336 1WSS Nozzle 417333 1N Nozzle 419335 1 NSS Nozzle 417332 1/2N Nozzle 419334 3N Nozzle 419338 2W Nole 419337 2WH Nozzle 78078 Nozz;a Noz Stinoina Flov •W 1 '.W 1 1N 1 1N 1 1/2N 1/2 3N 3 2W 2 2WH 2 230 Nozzle 419339 230 245 Nozzle 419340 245 260 Nozzle 419341 260 290 Nozzle 419342 290 2120 Nozzle 419343 2120 1F Noz<le 419333 1F IIDo 1407.7..1..E -*OM. I1D0 Nitrogen Crtridae Required LT -20-R (7032) LT -30-R (5373) Carbon Dioxide Cartridge Reouired 101-10 (15850) 101-20 (17492) WE;I i 1 a E(stPrJS i s 5 S LAcck Sgkii5 O ?o 1.4631) 51' C 2 2 2 2 2 1 SECTION IX - APPENDIX UL EX. 3470 ULC CEx747 Page 9-1 7-1-98 REV. 3 SYSTEM SELECTION GUIDE NOTE: System options do not cover all conceivable variations. They are listed here as a general guideline to show the most common type arrangement for multiple systems, Based on certain system designs utilizing manifolding, non-manifolding, 3 -tank systems, etc., other tank/cartridge combinations can be designed. The combinations below are based on 11 flow, 3.0 gallon tanks and 5 flow, 1.5 gallon tanks. More competitive designs may be available by utilizing 12 flow and 6 flow systems when appropriate. Total Tank Type of y Nitrogen Carbon Dioxide Flow No.* Quantity System Type of Hardware Cartridge Required 1-5 Cartridge Required 1 Single 1.5 Gal. Reg. Release LT -20-R (7032) 101-10 (15850) 6-11 1 Single 3.0 Gal. Reg. Release LT -30-R(5373) ) 101-20 (17492) 12-16 2 Double 1.5 Gal. Reg. Release Double73022 3.0 Gal: Additional Tank Double(73022) 101 30 (15851) 17-22 2 Double 3.0 Gal. Reg. Release Double73022 3.0 Gal. Additional Tank Double(73022) 101 30 (15851)" 23-27 3 Multiple 1.5 Gal. Reg.Release LT -20-.R (7032) 101-10 (15850) 3.0 Gal. Reg. Actuator LT -A-101-30 (29187) 101-30 (15851y- 3.0 Gal. Additional Tank 28-33 28-33 (Optional) 34-38 3 Multiple 3.0 Gal. Reg. Release LT -30-R(5373) ) 101-20 (17492) 3.0 Gal. Reg. Actuator LT -A-101-30 (29187) 101-30 (15851y- 3.0 Gal. Additional Tank 3 Multiple 3.0 Gal. Reg. Release Double (73022) N/A (2) 3.0 Gal. Additional Tanks ? Multiple 1.5 Gal. Reg. Release Double73022 3.0 Gal. Additional Tank Double(73022) 101-30 (15851) 3.0 Gal. Reg. Actuator LT -A-101-30 (29187) 101-30 (15851)"' 3.0 Gal. Additional Tank 39-44 4 Multiple 3.0 Gal. Reg. Release Double73022 • 3.0 Gal. Additional Tank Double(73022) 101-30 (15851) 3.0 Gal. Reg. Actuator LT -A-101-30 (29187) 101-30 (1585' y-- 3.0 Gal. Additional Tank. 45-49 5 Multiple 1.5 Gal. Reg.Release LT -20-R (7032) 101-10 (15850) 3.0 Gal. Reg. Actuator LT -A-101-30 (29187) 101-30 (15851)•*" 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator LT -A-101-30 (29187) 101-30 (15851)- 3.0 Gal. Additional Tank 50-55 5 Multiple 3.0 Gal. Reg. Release LT -30-R(5373) ) 101-20 (17492) 3.0 Gal. Reg. Actuator LT -A-101-30 (29187) 101-30 (15851)- 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator LT -A-101-30 (29187) 101-30 (15851y- 3.0 Gal. Additional Tank 56-60 6 Multiple 1.5 Gal. Reg. Release Double73022 ( ) 101-30 (15851) 3.0 Gal. Additional Tank 3.0_Gal. Reg. Actuator LT -A-101-30 (29187) 101-30 (15851)- 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator-' LT -A-101-30 (29187) 101-30 (15851)' 3.0 Gal. Additional Tank 61-66 6 Multiple 3.0 Gal. Reg.Release Double (73022) 101-30 (15851)- 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator LT -A-101-30 (29187) 101-30 (15851)*" 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator LT -A-101-30 (29187) 101-30 (15851)"" 3.0 Gal. Additional Tank Based on 5 flow numbers for a 1.5 gal. system and 11 flow numbers for a 3.0 gal. system. See Pages 4-39 - 4-42 for exceptions. If tanks are manifolded, only a "double tank' nitrogen cartridge (Part No. 73022) can be used. - If tanks are manifolded, either an LT -A-101-30 nitrogen cartridge (Part No. 29187) or a double tank cartridge (Part No. 73022) can be used. 0 r Without Comments As Noted In Red Per The Attached Letter i nese plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is suhiect to errors and omissions which do not authorize violations o; adopted stanaaras and orornances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings atter this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureaus, By: (?c WUKWILA FIRE DENArc t n+�.►�t Please call: 575-4407 and give this lo�c0 No. and exact address for shut, 'own or restoration aoorovd. EraN 1 GA Odle Fool Typo: Cs' 2a'L X 24"WX3CH Rona .2 burners FIMi Typal Gu 12 L X 24-Wx3tr-n Fryer - Run NI W inty( Rip Fuel Typo: Go tar'L X 14TWX39'H Fryer -AP vat wotout DIP Fuel Type: fjei 15-1. x 1PwXlirH Fyn - Full rr t viehcid DI Fool lypr Ges 766 x IPwx3P11 — f ..p•q Fryer - Full Mot without Dlpdmd �./ Fuel e• Goa I--• 1A -L X 1WWx311' 00 .... n ,.o Yn rn vuTir okoc.•1 oo2 cza-ci_ N y g N a. 10 7 t] ? FT - Fo � rigl ,8 N G )4114 tv T r4 0. a• r a SECTION N SYSTEM DESIGN - ULE "170 LIC CEz747 :Page 4-28 REV.5 4-1-06 Nozzle Application Chart Ttie following Chart has; been developed to 2ssistiri calculating the quantity and type of nozzle required to protect eath duct, plenum; or appliance: - : . Hazard This chart for general :reference `only=See: complete d+ilsfor each type of hazard ' Maxiinuin' Hazard Dimensions' Duct orTranettion (Single Nozzle) . Duct or transition (Single Noe) : Duct orTransilon (Dual Nozzle) Electrostalic. Precipitator (At Base of :Duct) .. Plenum (Horizontal. Protection) Length = U nif° Perimeter - 50in. (127 crn) : -Diameter:- :l6 in. (40:6 cm)` Length iJntiinifed' Perimeter 'H 100. in: 054- Diameter 254Diameter 31;7/8 tri:?(81:gni) Length. ini'¢nited Perimeter:F150 ip::(381 cm) • Indrvidual Cell: Plenurn (Horizontal Protection) Plenum (Vertical Protection) Fryer (Sprit or I Non -Split Vat) Fryer (Sprd or •. Non -Sprit \fat) Fryer (Split for Non -Sprit Vat)* Length -10 ft (31 m) Length 6 tt_.(1:8 rri) Width — 4-fit.112 m): -Length -44 it.:(? 2`m • Wi4ih-4 ft. (12 m Maximum See., :::. • (without drip ESoart>)';1 y 4 in: (36 15 r . (38 cm) Low,Pitndmity: • maximum:Size • (vvrthout:drip board) 14 -1r210 -437, -Cm) x?: 121 -fin. (36: cm): Medium. Prpdrruty'_ Mai imuiFa S•ize•' (whhout drnploard l :115 in:'(38:cm): x. ::14:ur. (36 cm): .. High Prcodmiiy Medium.P#dmity. Fryer (Non -;Split Vat Only) Maximurri.S•ize' .... (without chipboard) 191/21ri:;(49:5 Citi) 19 in ilgh Proxirriity:.` tow Proximity Ma�murn Size..; (without drip board) .° 18 in. -(45Ji rn) x 18 in: '(45.7cm) High 430192 1W 419336 1W 4119336. 1W NozleTip Stamping• Flow No.. 1W 2W 2W 1/2N 1N .419339 419340 290 290 230 245 419338 3N - 419342 •. 290 For multiple i..Ie Prem of soak fryers, see detailed Paaes 4-i2Ihrouyh 914. 25-35 in. (64-89 cm) 419338 3N Nozzle Application Chart (Continued) 1-12zard Fryer (Non -Split Vat Only)* Fryer (Spkt or Non -Sprit \/) •Fryer (Split or Non -Split Vat) Range - Maximum Haiard Nole :Nozzle (puerility 'Heights Maximurn SiZe (Witir,dritYboard.) - . .• -21. in; (53 00.1) .*-• • - • • • • • • • .• •• : • . (Fj.Oot-riiLittpiit exceed.• ..*: . • 15 it xl4in. . • • I- : tat -cm* • • - • .1\itediurn PrCotkiiity- ....• MaxiMurn;.Siie(will-' drip board) : :.• • • 25 3/a-itl„:Asl-A.-aer_rj:;,.. '- • . _ . • •• (Frir:Pot side MISt riotexceed 19 l/2.in. -.• 1482 cr'6).-.1.f- 1."'•• High ProximityLow Proximxiy s • Mparnurn Size . " • . . -.-.. • • .. -. • • •••••••• . • (with drip board) • ••• .18 in..(45.7. CM) : s x 27 3!.4.irt, (705cm) - •'• z•-• MaXirrium Stie • (with drip board) • .14 (36 Cm) .• 21 'in: (53 Crp):- . Low Maxirn • (With-driii board) •••• - • : : 14112 (3Tarn) -26 11.2)6._ _:(67*1). •ietfium lvdnft . • &ECM% V5Tzti 3470 ULC CE):747 Page 4-Z5' 4-1-0S RS -it S Nozzle Part No_ 419339 419340 • 34. _ 419338 • 13 18 : 419342 • • 5 —35 in. • - 41-9338 64-49 CM) 1 {33-7;-41 cm) Longest Side ;•;:-.: : : 32 in7 Area:— 384 (2477-:Sct. cM) - :Longest Side • - gi*,arr0- Area —.336 schin. • . -'(2168 sq. crn) ; ":„ • Longest Sideltfigh Froximrty). • - 28 in. (71 cm) • Area :7672 sq: in. •-• : - Medium la'ioximity). 32 in.. (81 arri) : Area =768 .sq, in. (4955 sq. cm) Longest Side tow Proximity) 2 36 in. (p1 prro Area — 1008 sq. in. _ (6503 sq. cm) 3r r.jj n=le Amle=tonaf =Pie frYers,e detailectinforrnalion on Pag-4-7 through 4-11. . . . 419342 Noe Tip Srtiping — Pk* No. 230 245 3N 290 3N 290 16 —271n. 419342 290 •,-(41 — 69 cm) • .40 Oni) (VVith gaclollelf) - - • - .40. 50 in. • (1027127 'cni) 4-19335 419333 419340 -•30 7 40 in. 419341 (7-5_ 102 cm) 15 —20 in. 41934 2 (38 — 51-crt) 1N 245 20 290 SECTION IV — SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-30 REV. 3 10-1-02 Nozzle Application Chart (Continued) Hazard Griddle Chain Broiler' (Overhead Protection) Chain Broiler (Horizontal Protection) Gas -Radiant Char -Broiler Electric Char -Broiler Lava -Rock Broiler Natural Charcoal Broiler Lava -Rock or Natural Charcoal Char -Broiler Maximum Hazard Dimensions Longest Side (High Proximity) 48 in. (122 cm) Area —1440 sq. in. (9290 sq. cm) Longest Side (High Proximity) 1 30 in. (76 cm) Area - 720 sq. in. (4645 sq. cm) Longest Side (High Proximity) .1 36 in. (91 cm) Area —1080 sq. in. (6968 sq. cm) Longest Side 1 (Medium Proximity) 48 in. (122 crn) Area —1440 sq: in. (9290 sq. cm) Longest Side (Low Proximity) 1 48 in. (122 cm) Area =1440 sq. in. (9290 sq. cm) Longest Side — 34 in. (86 cm) 2 Area —1088 sq.. in. (7019 sq: cm) Length — 43 in. (109 cm) 2 Width — 31 in. (79 cm) Longest Side — 36 in. (91 cm) 1 Area — 864 sq. in. (5574 sq. cm) Longest Side — 34 in. (86 cm) 1 Area — 680 sq. in. (4388 sq. cm) Longest Side— 24 in. (61 cm) 1 Area — 312 sq. in. (2013 sq. cm) Longest Side — 24 in. . (61 cm) 1 Area - 288.sq. in. (1858 sq. cm) Longest Side — 30 in. (76 cm) 1 Area — 720 sq. in. (4645 sq. cm) Minimum Nozzle Quantity 1 Nozzle Heights 30 — 50 in. (76 —127 cm) (perimeter located) 30 — 50 in. (76 —127 cm) (center. located) 35-40 in. (89 102 cm) (perimeter locate (51 — 76 cm) (perimeter located) 10 — 20 in. (25 — 51 cm) (perimeter located) 10 — 26 in. (25-66 cm) 1-3 in. (3 — 8 cm) 15 —40 in. (38 -102 cm) 20 — 50 in. (51 — 127 cm) 18-35 in. (46 - 89 cm) 18-40 in. (46 =102 cm) 14 — 40 in. (36 -102 cm) ' Minimum chain broiler exhaust opening —12 in. x 12 in. (31 cm x 31 cm), and not less than 60% of internal broiler size. Nozzle Part No. 419341 Nozzle Tip Stamping — Row No 260 419342 .290 419335/417332 1N/1NSS - 419342 419343 290 • 2120 419336/417333 1 W/1 WSS 419335/417332 419335/417332 419335/417332 419335/417332 419335/417332 419338 1N/1NSS 1N/1NSS 1 N/1 NSS 1N/1NSS 1N/1NSS 3N ssenbfy (3.0 Gallon _ .Part NO. 79250 cr 1.5 canon !0. 75291) cor.t=_ins the reslated rle�e mechanism, , Pan asmanent an" e.^;' gas hose for'aoent tank hookup. and-encosure nockautS. to fediiitate installing aatcaiion piping," ez e!fani icing: Os -traction system. and additional equipment. This recu- 9• tion additional :ted release assembly is used in sioole, dcuble..and multiple- ank .systems and must be .mounted to a tinid surface. The elease mechanism can be sed to interconnect both the actu- tion and expellant gas tines as required per sFstem desiign.The eautator is designed to' allow a constant dcw of Cas irrto'the ank at 100 psi. (590 kPaj whet) the system is 'actuated:. 1 single. double, and multiple-tenk.systerP5 the pravid i! expel rit cas hose .connects the anent tank.10 the bottorn `outlet:of to reeuiator- In double.and. multlple-taik sjsem contTguratla ts,. le back outlet of the regulator is used ;:s an- ekpellar cas:feed.. r one addiiiional tank-emidosure or lank -bracket :tiobkuo: The :nclosure contains the required knockouts to facilitatethis".cOn71 Lection: 1f a pressure switch is to be attached to the regulator; :dditioral faunas are required. the tank; is mounted Within the"encibsufe. The tank contains _t adaptoritube asternbry with a burst disc union .iiie.burst disc . letps prevent siphonina.of the agent:uothe pipe" due to signuT- ..arit temperature fluctuations'in...the area=where- the-tank::is ocated. The tank is mild steel and, under normal ronditi0ns, raquires.hydrostatic testing'. every ;we'veThe agent tank is shipped uncharaed :and :must .belittled with_ 1.53 ealf:ons•-(5.6 L) or 3.06 gallons (11.6"!_). of.oiiiy. ANSULEX Low pH Liquid Fire Suppressant "during instal'atioit:::-.::. . The date .ti' r. ;enc' �r rjrtin! =t e ;�r reg)_; c4 o. desi rr are � a' tpac::-4#4.n!>: Qconnected tot*. release mecha�isrti..The endosure. containsimockouts to fa6Titate detection and additiionai.hoola%ps.:.. The system can bs actuated automatically or rnanuaity_:•f tits- :' Matic actuation ocarrs when a fusible fink within: the )detection .7 system Separates in a fire condr5on_1jfanuaj actuatiort:of-.the system occurs when personnel obit on the remote: manuar pull . station pull ruin. •• R-102 REST URANrr FIRE _SUPPRESS O N SYSTEM (Standard tit 300'i . _ Nome --�dentttii jNtonCe hart: No_- , Noz No9TVDPart NO. Stampj nG Ploy 1W Norte 419336 ; 1W .WSS.Nb�zle 417333 ; 1W n 1 1 N NOrie 1 a1 °335 } 1N 1 NSS Nozzle 417332 1 IN 1/2N Noale •419334 11/21 3N Nozzle 419339 1 3N 2W No1e 419337 ; 2W 2Wri Noz�1e 78078 12Vin.i EXTINGUIS'HING AGENT ANSULEX Liv pH Liquid Fire .5uppr ssant-(1...5 gallon 2 P No. 79694 or: 3.0 Callon Part No: 78372) is apoiassiurti=based solution .designed for knock-dowri; .and' suppression':of Grease -related. fires. The agent is shipped in plastic containers which provide one. complete tank :charge °.Agent:storage- ife e ectancy is twehre years: The distributor-:riustr rthe-batch numbers and date of shiprtient ..receipt Lobe filed .with eacli.instai- tation record. To;ali Tank Flow No' Quay 1-5 1 230 Norio `245 Noale 260 Norte 290 -Norte . 2120 Norte 1 F Norte'.•: 1166 1407.7-2.E 1 -a^C i r iCA.L Swrrcts.3 t ---OcAi:P_.:tt3:'cfsCi{-_AU-3j.: tie ele�gi - --:- - -. ....: switche..§ are intended. • for :i:se " ... ' alamts contactdrs, r ? e1e^trilet mover shirt -off do 9 , contractor._ suppped _ vices :and' other ei " , - t. uric:. • esigned to shut off or torr, on when the sem' ds c oaf. az e . •s.....i fs.acivatecl: w S .siatiable :m 011e Swat G`, P .No.. _ • .. _ . 1238$0 � Part No. 423879. Triuee Swilph.' ' ' ,af of 0 a-xcl Four Switftli }3t; Part -ho- c23B81.` £' �t No. _ singlelpole, double4ijrgy�,corfaCtsBch same 1rHPg` 25,250, 277 VAC or 2 .Hp 25C 2 Ci ounfing lie p arHP ,rovided with each kit. - 1S COMMON 419339 419340 419341 419342 419343 419333 -4t2 1 1/2 3 2 2 230 2 245 2 260 2 290 2 2120 2 1i= 1 lleo 1 Carbon Dioxide Cartridge Reoui; ed 101-10 (15950) 101-20 (17452) rL7Li� L" 0\7t7_1:71 -s) { t _ .HiS w1-tb-l n-_ r . SECTION IX - APPENDIX UL EX. 3470 ULC CEx747 Page 9-1 10-1-02 REV.5 SYSTEM SELECTION GUIDE Note: System options do not cover all conceivable variations. They are listed here as a general guideline to show the most common type arrangement for multiple systems, Based on Certain System designs utilizing manifolding, non-manifolding, 3 -tank systems, etc., other tank/cartridge combinations can be designed. The combinations below are based on 11 flow, 3.0 gallon tanks and 5 flow, 1.5 gallon tanks. More competitive designs may be available by utilizing 12 flow and 6 flow systems when appropriate. 'Total Tank Type of Row No.* Quantity System Type of Hardware Carbon Dioxide Nitrogen Cartridgee Required Cartridoe Required 1-5 1 Single 1.5 Gal. Reg. Release 101-10423439 ( ) LT -20-R (423429) 6-11 1 Single 3.0 Gal. Reg. Release 101-20423441 ( ) LT 3010 (423435) 12-16 2 Double 1.5 Gal. Reg.Release 101-30(423443) Double (423493) 3.0 Gal. Addition[ Tank 17-22 2 Double 3.0 Gal. Reg. Release 101-30 (423443)- Double (423493) 3.0 Gal. Additional Tank 23-33 3 Multiple 3.0 Gal. R Release keg. 101-20 (423441) LT -30-R (423435) 3.0 Gal. Reg. Actuator 101-30 (423443)"` LTA -101-30 (423491) 3.0 Gat. Additional Tank 23-27 3 Multiple 1.5 Gal. Reg. Release 101-10 423439 (Optional) ( ) ' LT 2010 (423429) 3.0 Gal. Reg. Actuator 101-30 (423443)- LT -A-101-30 (423491) 3.0 Gal. Additional Tank 28-33 3 Multiple 3.0 Gal. Reg. Release N/A (Optional) (2) 3.0 Gal. Additional Tanks Double (423493) 34-38 4 Multiple 1.5 Gal. Reg. Release 101-10423439 3.0 Gal. Reg. Actuator N/A ( ) LT -10 ( Double 3.0 Gal. Tank Box LT -A-101-30 ( (423423 491) 34-38 4 Multiple 1.5 Gal. Reg. Release 101-30 423443 (Optional) 3.0 Gal. Additional Tank ( ) Double (423493) 3.0 Gal. Reg. Actuator 101-30 (423443)"' LT -A-101-30 (423491) 3.0 Gal. Additional Tank 39-44 4 Multiple 3.0 Gal. Reg. Release 101-20423441 ( ) LT -30-0 (423435) 3.0 gal. Reg. Actuator N/A LT -A-101-30 (423491) Double 3.0 Gal. Tank Box • 39-44 (Optional) 4 Multiple 3.0 Gal. Reg. Release 101-30 (423443)" Double (423493) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)-' LTA -101-30 (423491) 3.0 Gal. Additional Tank 45-49 5 Multiple 1.5 Gal. Reg. Release 101-30 (423443) Double (423493) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator N/A LT -A-101-30 (423491) Double 3.0 Gal. Tank Box 45-49 5 Multiple 1.5 Gal. Reg. Release 101-10 (423439) LT 20-R (423429) (Optional) 3.0 Gal. Reg. Actuator 101-30 (423443) LTA -101-30 (423491) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443) LT -A-101-30 (423491) 3.0 Gal. Additional Tank Based on 5 flow numbers tor a 1.5 gaL system and 11 flow numbers for a 3.0 gal. system. •• If tanks are maniiolded, only `double tank' nitrogen cartridge (Part No. 423493) can be used. "' If tanks are manitolded. either an LT -A-101-30 nitrogen cartridge (Part No. 423491) or a double tank cartridge (Part Na 423493) can be used. O Without Comments O As Noted in Red Per The Attached Letter These plans have been reviewed by The Tukwila Fire prevention Bureau for conformance w th current City standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or ravisons to mese drawings after this date will void r '_ icceptaice ar require a resubmittal of re i s:. c-awings for suoseu..2nt approval. Final acceota^ce it subject to field test and Inspection by The Tukwila Fire 1'1 eventon Bureau. Date: %-)-"1-1 a- RY.1141 I I'UKWIL' FIRE DEPARTMENT ?!eat 206-575-44107 and rl:Nia this Fire Permit No. exact r'" /ress for shut - or r: gyration approval. REVISIONS DESCRIPTION DATE 10'-0" A.F.F. BOTT. OF SOFFIT BOTT. OF SIGN BAND BOTT. OF SOFFIT SPACE #FC11 0 TYPICAL ARMOVER TO NEW SPRINKLER. HEAD N.T.L ARGCO #3B OFFSET 45deg MIN WHERE LENGTH OF ALL THREAD ROD EXCEEDS 1,-1O" ADD SECOND RESTRAINT LINE RESTRAINT DETAIL 3/8 X 3-1/2 LAG SCREW FOR WOOD 3/8" KWIK BOLT FOR CONCRETE 1/4 X 1 TEK FOR BAR3OIST OR STEEL BEAM 3/8"x1-10 ALL THREAD ROD. MAX PER SINGLE RESTRAINT HANGER RING (UP TO 2" PIPE) NOTE: 1) SPACE WITH IN 6" OF A HANGER EVERY 42'-0". 2) BRACING PER NFPA-13(2007 ed.) SECTIONS 9.3.5.8.8, TABLE 9.3.5.8.8(c) AND 9.3.6-RESTAINT OF BRANCH LINES THICKNESS OF CONCRETE VARIES A - 3/8' X2-3/4' KWIK B0L'6 • t • DA • 1. A 3/8' ROD CPLG. CUT 3/8' A.T.R. (PER PLAN) RING HANGER FOR 1' TO 4' PIPE ALL LOCATIONS (O.N.O.) (1) (1) (1) (1) 3/8' x2-3/4' HILT) QIYIK BOLT 3/8' A.T.R. x (SEE PLAN) 3/8' ROD CPLG. PIPE HANGER RING LAS RECCOMENDED BY MFG. #13 HANGER DETAIL N.T.S. FIG. 65 BEAM CLAMP FIG. 69 RETAINING STRAP J4 LOCK NUT REQ'D VIEW A -A FIG. 100 ALL THREAD ROD �-- FIG. 200 ADJUSTABLE RING HANGER BOTTOM BEAM CLAMP, ROD, AND RING r CCE Without Comments As Noted In Red 0 Per The Attached Letter 1 nese plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is subject to errors and omissions which da not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings atter this date will void this.acceptance and wll require a resubmittal of revised drawings for subsequent approval. 02 HANGER DETAIL N.T.S. Final acceptance is subject to field test and inspection by The Tukwila Fire, Prevention Bure 1'UKWILA FIRE DEPARTMENT Please call: 575-4407, and give this job No.4.3— 53 and exact address for shut. down or restoration approval; ? O CE Weld stamps must be - inspected before pipe is 01 By .: _moi hung. Do not paint piping prior to hydrostatic test approval. GENER NOTES* �p14. Alt9iAi SPK. 1-15'�/e Nr -M/3 CP /mix/ a2 & FFL . I .RETAIL AREAS ARE DESIGNED IN ACCO WITH DANCE REQUIREMENTS OF N.F.P.A. 13 ODINARY HAZARD G OUP 2 MAX SPACING 130 SQ. FT. R IT THE 2. COSCO POINT OF CONNECTION 15 AT EXIST BUILDING SHELL SYSTEM 4" MAIN AS SHOWN ON THESE PLANS. 3. ALL PAINTING OF FIRE SPRINKLER PIPING (IF REQ) TO BE DONE BY OTHERS - 4. ALL WIRING BY OTHER. 5. ALL MATERIAL IS NEW U.L. LISTED AND MEETS THE REQUIREMENTS OF THE TUKWILA FIRE FIRE DEPT. 6. OWNER IS RESPONSIBLE TO ASSURE THAT STRUCTURE AS IT IS SHOWN ON CONTRACT DRAWINGS CAN ADEQUATELY SUPPORT ALL FIRE SPRINKLER PIPING LOADS. NO AUXILLIARY DEVICES OR ATTACHMENTS SHALL BE PROVIDED BY COSCO TO SUPPLIMENT THE STRUCTURE TO ACCOMODATE FIRE SPRINKLER - PIPING LOADS. 7. OWNER IS RESPONSIBLE TO PROVIDE ADEQUATE HEAT TO MAINTAIN 40 DEG. F. MINIMUM AT ALL TIMES YEAR ROUND. 8. SPRINKLER HEAD LOCATIONS INDICATED ON THESE DRAWINGS ARE NOT INTENDED TO BE "CENTER OF TILE" HEAD PLACEMENT: 9. COSCO ASSUMES NO RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, FOR THE CONDITION, PERFORMANCE OR CURRENT CODE COMPLIANCE OF THE EXISTING SYSTEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY. COSCO. 10. OWNER IS RESPONSIBLE TO ARRANGE FOR THE PERIODIC INSPECTION, TESTING AND MAINTENANCE OF THESE FIRE SPRINKLER SYSTEMS IN ACCORDANCE WITH THE MINIMUM REQUIREMENTS OF N.F.P.A. 25-2002 BY QUALIFIED PERSONNEL COMMENCING AFTER WARRANTY PERIOD HAS EXPIRED. THE FIRM THAT DESIGNED AND INSTALLED THIS SYSTEM 15 BEST QUALIFIED TO PROVIDE THE'ONGOING LONG TERM TESTING, MAINTENANCE AND SERVICING OF THIS SYSTEM(S). ****** FIELD NOTES ****** I) THREADED PIPE FROM I " THRU :2" SIZE TO BE SCH. 40 STD. WALL PIPE (IMPORT). 2) GROOVED END PIPE FROM 2 1/2" THRU 8" TO BE SC1-1.10 (IMPORT). 3) ALL GROOVED COUPLING ARE TO BE "RIGID" TYPE U.N.O. (IMPORT). 4) ALL THREADED FITTINGS ARE 300# CLASS D.I. (IMPORT). FIELD/NOTES r EXISTING PIPE NEW PIPE EXISTING HEAD NEW HEAD PERMIT # D08-086 r3 1.1 SCALE:1/4=1'--0 SPRINKLER HEAD LEGEND : SYMBOL S/N ORIFICE NPT K -FACT. HEAD FINISH PLATE FINISH TEMP. QUAN. RELIABLE MOD G4A CONCEALED SSP 1/2' 1/2' 5.6 BRASS WHT 165 Co REUABLE MOD G4A CONCEALED SSP RELIABLE MOD F1 FR REC SSP 1/2' 1/2' 1/2' 1/2' 5.6 5.6 BRASS CHR BLACK CHR 165 155 APPROVALS BY: I TOTAL SPRINKLERS THIS SHEET ••0 o.• •.® 00 00• • ®° I Fire Protection FIRE PROTECTION AND LIFE SAFETY SPECIALISTS WASHINGTON OFFICE 15000 Woodinville -Redmond Rd NE License No: Woodinville, Washington 98072. COSCOFP11ONM call (425) 686-8300 • fax (425) 827-4784 SAN DIEGO •'LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEA1TLE • ANCHORAGE COSCO www.coscofire.com PROJECT: CHICKEN NOW 2 ,o0na SOUTHCENTER taAs.PACE FC11 TUKWILA, WA 98188 111UN 18 2008. CONTRACT WITH: MT DESIGN INC. 151 SABAL PLAM DRIVE LONGWOOD, FL 32779 FRANK 704-929-1593 TuKWIIa Fire 4.2_4o(o(e $ i56° E>✓ DRArnNc TIRE FIRE SPRINKLER TENANT IMPROVEMENT DATE : 06/16/08 SCALE : 1/4= 1'-0" DRAWN BY : BRIAN SCHULZE 15SS7962 SHEET � � OF 1 KW i ' A, s N SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET \UIVSHEET TITLE FA -01 SYSTEM I \ FO N ATI O \ FA -02 TYPICAL DETAILS - WRI\G A\D MOUNT( \G FA -03 FRE ALAS V SYSTEM FLOG PLA\ FA -04 SYSTEM CALC U LATI O \ S r GE\EAL), �ISE�, SITE PLA\ WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) 2S STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) 2V SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) W ERE THE CABLE IS INSTALLED QUANTITY 2 1 1 1 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD n DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD B< LINEAR BEAM SMOKE DETECTOR. PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 IN/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING 1,4 D DUCT SMOKE DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP IN/ 1G RING CEILING gL C FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX CEILING IN/ 1-1/2" EXT. FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -W SIEMENS 4S DEEP BOX 80" A.F.F. IN/ 1-1/2" EXT. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX CEILING IN/ 1-1/2" EXT. L c Qc FIRE ALARM STROBE (CEILING MOUNT) FIRE ALARM STROBE (WALL MOUNT) FIRE ALARM SPEAKER (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING ZR -MC -W SIEMENS 4S BOX IN/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. SET -CW SIEMENS 4S DEEP BOX CEILING w/ 1-1/2" EXT. FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM B p STROBE WP (WEATHERPROOF) SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO B OTTO M SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR MULTI -VOLTAGE CONTROL RELAY MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JBOX FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD JUNCTI❑N BOX F.B.D. F.B.❑, N/A VERIFY IN FIFL,p A.F.F. F.B.D. ABOVE FINISHED FLOOR FURNISHED BY OTHERS N/A N/A N/A /A N/A N/A N/A NOT APPLICABLE N/A /A z 0 Withoutic ments N/A As Noted In Red U.O.N. UNLESS OTHERWISE NOTED N/A Per IheAttacheaLetter /A N/A N/A i nese plans have been reviewed by The Tukwila Fire EATHERPR❑❑F DEVICE N/A 7vention Bureau forcrmancewith current tD dards. Acceptance li 4blect to errors and N A omissions which do not authorize violations of adopted A comp RED AS BUILT ADD ❑R CHANGE N/A stanaaras and oramances. The responsibility for theA arc equacy of design restY(cl�at ily with the designees Additions, deletions or revisions to these drawings atter Fire C Certifici GREEN AS BUILT REMOVE N/A t/his date will void thi�s.acgepLance and will requir 1 resubmittal of revised drevised &di/16gsforsubsequenta Orblval. to th commer Test -in and 1 Failur BLUE AS BUILT NOTES T❑ CAD N/A Fi al acceptance is sub' o field test and ins t' by /� p The Tukwila FiretiPrevention Bureau. �, Date: 0 0 By: tO in a RE termin, TUKWILA FIRE DEPARfNrrrs� Please call: 575.4407 and give this job No. end exact address for shut' town or restoration approve): Copyright 2006 by Guardian Security Systems, FAX (206) 628-4990 LO CV CV '0 CV J• uJ RELEASE/REVISIONS m LU z a DESCRIPTION SHOP DRAWINGS LU 0 co 0 C C -J -J CO C10 CTS CC OW1O Z W C3 W CC �Q O� Q UWT 7=4 0L� Op (DI - C\1 NOTICE Ieted, signed, Tukwila )epartment Pre-test ate must be preser ted e Inspector prior to cement of AcceptE rice g of any Fire Alarm Detection Systems. e of test will result inspection Fee an I ation of the testing. XAD -' Zoon ukwita Fire Inc. All Rights Reserved CCALE: 1/8" =1 ' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/04/08 BACKROUND PLAN PROVIDED BY: \OB NUMBER:54497 SHEET k FA -011 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR i+ PREVI❑US ADDRESSABLE DEVIL O DUCT DETECTOR L❑CATION END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH 0 GROUND_0 HTRI-R OSTATUS LED 0 N.O. N. 0 COM 0 N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SSE (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE DEVICE TO NEXT ADDRESSABLE DEVICE + NOTE 11 VOLTAGE MAX, - CURRENT MAX. - CONT, RES, MAX, - MAX, CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN. LINE SIZE - MUSIC OUTLET SAMPLING TUBE INLET SAMPLING,—\ TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE LrAC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE f(+) STOP IF LAST DEVICE (-) FROM XLS CONTROL PANEL OR PREVI❑US ADDRESSABLE DEVICE (-) END OF LINE DEVICE RELAY CONTACTS (4.0A @ 125VAC) (4.OA @ 30VDC) 27 VDC 3,5 r1A DURING POLLING 10 OHMS 200 FT. (18 AWG) 0.02uF 0.04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTI❑N. TB1 S 0 0 0 0 123456 HC TB2 D 654321 0 0 O m tV (3.6K 1/4W) SUPERVISED / SWITCH 7' ; GROUND NOTE: O © HTRI-D OSTATUS LED CO 0 m NOT USED CO m O FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL `ABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC � 0 0 0 1 J.- J. T T T 0 PAD -3 0 0 00 O INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 0 0 0 0 0 24K TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE NAC -4 NAC -3 NAC -2 NAC -1 END OF LINE DEVICE 3.6K 1/4W) UPERVISED -WITCH ( FRONT VIEW � l NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. � NOT USED REMOTE + DEVICE LOOP NOT USED REMOTE DEVICE LOOP 0 0 0 FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> 470 OHMS �N! EOL 0 WI 1 INPU + 9 9 TCM -1 Q 8 0 it' MOO O • 41 C O_CI CO e TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE N01 FROM REMOTE POWER SUPPLY ('S' CABLE) FROM FACP <V❑ICE CIRCUIT) C'V' CABLE) + `J (STROBE) SPEAKER (4) (-) EARTH GROUND 0 --).(+)TO NEXT DEVICE OR >{-) STOP IF LAST DEVICE ( STROBE-) (S ) STROBE SPEAKER (4) (-) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY 80" A.F.F. 4S DEEP BOX W/ 1-1/2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE TO NEXT DEVICE ❑R END OF LINE TO NEXT DEVICE ❑R END OF LINE NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER 11N TEMPERA RE: +32'F (0' C) TO 100' F 38 C) HUMIDITY: 0bb00O-9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN ( ) ,— DATA IN (+) > DEVICE IS USTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WWIITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT DEVICE F > (-) DATA OUT > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID —\ CEILING HARD LID .... SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION `N, CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTION BOX—. MOUNTED ON \ CEILING FLEX \ JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT FI i O O O O IL TO NEXT DEVICE CADDY BAR �—J SMOKE DETECTOR ------ SMOKE DETECTOR MOUNTING SCALE:NONE "---- SUSPENDED ILLUMINATED CEILING DO \OT I\ S 0 LL ADDRESSABLE IItJT ATPNG DEVICES �,NTIL PREP OGRMMED WITH DEVICES ADDRESS. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved Mfti •4 I743. IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS Lu 5/15/08 Q a 9 CCCCa z z 0 0 z t� z CC -§"" J W J SCALE: 1 /8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/04/08 BACKROUND PLAN PROVIDED BY: %OB NUMBER:54497 FA -02 I.� i1 !I 11-rr A.F.F. BAND BUM OF SIGN SAND'" OL—S1 F.F. OP G(.1FFYf 11. lin i D 4i-••=,,,/, NORTH :' Hort. OF ENr1STINCa LANDLORD FLOATING CFIL NG ELEMENT ---- 0I/ OsOFuLemt°ln IJCdff F1Y: LIFT SEE ELECT. CHICKEN NOW WESTFIELD SOUTHCENTER MALL SCALE 118"=1' FLAG NO ES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,CSEE SIEMENS INSTALLATION SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICAL CONTRACTOR, SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. PLANS \OT APPROVED DO NOT INSTAL ADD-RESSABLE INATIATING DEVICES U\ U IL DREPOGRAMN97D WASH DEVICES DDRESS. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved IMma e FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS DATE 5/15/08 )� a«CCC -J CO J co CC X00 Z VW E'- O 2 __ W fsQ U W .— -] o Co D co I— CV LIJ ct Q uJ SCALE: 1/8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/04/08 BACKROUND PLAN PROVIDED BY: \0B NUMBER:54497 J SHEET FA -03 SYSTEM CALCULATIONS 0 CHICKEN NOW NORTH CHICKEN NOW WESTFIELD SOUTHCENTER MALL iy�i 1 .L; 0 5:.;1rr---*---': z--- - 1 ' 3 L m -- ---- 1 ID SCALE 1132".1 EX RISER DIAGRAM CHICKEN NOW CHICKEN NOW FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL 1 w 5/15/08 Panel: CHICKEN NOW Wire Resistance 1.62 Q in Date: June 4, 2008 CURRENT TOTAL= Current Load: Standby: Alarm: S1 _ Current Load: Standby: Alarm: QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 SET -MC @15CD 64 128 Device Type Qty Amps Total Amps Total 0.62 Device Type SET -MC @30CD Qty Amps Total Amps Total 1 HFP-11 o SET -MC @75CD 0.0022 0.0022 0.0023 Total Device Load, Amps (I) 0.13 0 SET -MC @110CD 233 0 AD2-P 1 0.0635 0.0635 0.064 0.064 SET-HMC-C@115CD Main System Board 0 1 0.03 0.03 0.030 0.030 0.08 HTR -R SET-HMC-C@177CD 2 0.009600 0.0096 0.021 0.042 SET -MC @15CD (E= 1* R) 2 0 SET -HMC @135CD 318 0.064 0.128 HTRI-D ■ 0.001600 0 0.0035 445 0 SET -MC @30CD ■ (20.4 - E) 0.098 0 Z-MC@15CD ICP -B6 0 0.005 SET -MC @75CD 0 Z-MC@30CD 98 0 0.175 0 SET-MC-CW@110CD 233 0 SET -MC @110CD 0.233 2 TOTAL mA= 128 12 191 20.32078848 128 SET HMC-C@115CD 0.318 Notification Appliance Circuit Detail SET HMC-C@135CD PROJECT: WESTFIELD SOUTHCENTER MALL 0.318 Panel: CHICKEN NOW Wire Resistance 2.58 0.0731 Amps 0.106 Amps SET HMC-C@185CD CIRCUIT: SPEAKER CIRCUIT 0.445 _ QTY Device Type ZR -MC @15CD Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 0.064 Standby Current Load: 70.7V1/8 0.0731 Amps For 24 Hours = 1.754 Amp -hours ZR -MC @30CD Total Wire Resistance (R) 0.99 0 �.�.�..._a. ... - _ 0 0.098 - (WL*2)*(R/ft) _ �� 0 HCP I Total Device Load, Amps (I) 0.00 0 0.0015 0 0 0 Alarm Current Load: 0.106 Amps For 5 Minutes= 0.009 Amp -hours 0 0 0.03 Amps 0.158 Amps 0 0 0 (E= I* R) 0 0 0 EOL Voltage 25% Derating= 2.204 Amp -hours 0 Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours 0 0 0 0 DEVICES= 2 TOTAL mA= 3.6 14 191 2039645198 3.6 Alarm Current Load: 0.158 Amps For 5 Minutes= 0.013 Amp -hours Total System Current Load: 2.204 Amp -hours 25% Derating= 0.917 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.917 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH 0 CHICKEN NOW NORTH CHICKEN NOW WESTFIELD SOUTHCENTER MALL iy�i 1 .L; 0 5:.;1rr---*---': z--- - 1 ' 3 L m -- ---- 1 ID SCALE 1132".1 EX RISER DIAGRAM VOLTAGE DROP CALCULATION Cot yriaht 2006 by Guardian Security Systems, Inc. All Rights Reserved FAX (206) 628-4990 RELEASE/REVISIONS REV. BY: z Q Notification Appliance Circuit Detail 1 DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL 1 w 5/15/08 Panel: CHICKEN NOW Wire Resistance 1.62 Q in Date: June 4, 2008 CURRENT TOTAL= 128 CIRCUIT: S1 _ QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 SET -MC @15CD 64 128 ■ Total Wire Resistance (R) 0.62 0 SET -MC @30CD 98 0 -_ 1 (WL * 2) *Rift) o SET -MC @75CD 175 0 Total Device Load, Amps (I) 0.13 0 SET -MC @110CD 233 0 . (Total Cct Load) 0 SET-HMC-C@115CD 318 0 ■ Voltage Drop ( E) 0.08 0 SET-HMC-C@177CD 445 0 ■ (E= 1* R) 20.32 0 SET -HMC @135CD 318 0 ■ EOL Voltage 0 SET -HMC @185CD 445 0 ■ (20.4 - E) 0 Z-MC@15CD 64 0 0 Z-MC@30CD 98 0 0 SET-MC-CW@110CD 233 0 DEVICES= 2 TOTAL mA= 128 12 191 20.32078848 128 Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: CHICKEN NOW Wire Resistance 2.58 Date: June 4, 2008 CURRENT TOTAL= 3.6 CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 70.7V1/8 1.8 3.6 Total Wire Resistance (R) 0.99 0 �.�.�..._a. ... - _ 0 0 0 - (WL*2)*(R/ft) _ �� 0 I Total Device Load, Amps (I) 0.00 0 0 0 0 (Total Cct Load) 0.00 0 0 Voltage Drop ( E) 0 0 0 (E= I* R) 0 0 0 EOL Voltage 20.40 00 0 0 (204-E) 0 0 0 0 DEVICES= 2 TOTAL mA= 3.6 14 191 2039645198 3.6 VOLTAGE DROP CALCULATION Cot yriaht 2006 by Guardian Security Systems, Inc. All Rights Reserved FAX (206) 628-4990 RELEASE/REVISIONS REV. BY: z Q DESCRIPTION SHOP DRAWINGS w 5/15/08 Q in 00 CO -J eco t7� 0 W IW- Q Z w(~5 Z 2 __ W cc 15w W r CC i U oD N~ is w cf) z w z 0 DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/04/08 BACKROUND PLAN PROVIDED BY: \0B NUMBER:54497 FA -04