Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
PP - 2636 SOUTHCENTER MALL - FYE - PERMITS AND PLANS
2636 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-227 08-S-287 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: FYE -2-146 Southcenter Mall Permit No.: 08-S287 Date: June 10, 2008, 2008 Reviewer: Steve Kohler Fire Inspector/Plan Review (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. t 414 Hydraulic Overview 1 Job Number: KSO415 Report Description: WET SYSTEM Job Job Number Design Engineer KS0415 CHRIS ISAAC Job Name Phone FAX FYE 425.881.0100 425.881.3030 Address 1 State CertficaboMicense Number 2110 Southcenter Pkwy WESTESF136QF Address 2 AR) City of Tukwila City State Zip Code Job Site Tukwila WA 98188 Expansion System Density Area of Application 0.20gpm/ft2 959.23ft2 (Actual 959.23ft2) Most Demanding Sprinkler Data Nose Streams 5.6 K-Factor 24.00 at 18.367 250.00 Coverage Per Sprinkle. Number Of Sprinklers Calculated 120.00ft2 11 System Pressure Demand System Flow Demand 72.752 303.29 Total Demand Pressure Result 553.29 @ 72.752 +66.765 (47.9%) Supplies Check Point Gauges Node Flow(gpm) Hose Flow(gpm) Static(psi) Residual(psi) Identifier Pressure(psi) K-Factor(K) Flow(gpm) 1 10900.00 250.00 140.000 20.000 ops 9 t f rCo 1 k. /11 y«.11 A . FYE-FP-1.cad Supply at Node 1 (10900.00, 250.00, 140.000, 20.000) ACA --ErA Pressure, psi cn o 0n 8' 01 `8 con o EA E �uuuw�uuuui�uuuw�inuuu�uuuw�uuuui�unuw�uuuui�nuun�uuuw Static Pressure 140.000 rJ 0 iI6 lel wi h hose streams N553.29 ..03.29 @ 72.752 System demand curve 10900.00 @ 20.000{ I'I' a N•11111111111111111111111111111 111111111 111111111 111111 h 1 111111111 1111 11 11 1 v �p�a�� �t 111AT330q" 5500 6600 7700 8800 9900 11000 Water flow, gpm A[S ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 06/09/2008 10:28:35AM Page 1 (:15A Hydraulic Summary 1 Job Number: KS0415 Report Description: WET SYSTEM Job Job Number KS0415 Job Name FYE Address 1 2110 Southcenter Pkwy Address 2 City State Zip Code Tukwila WA 98188 Design Engineer CHRIS ISAAC State Cenrfication/License Number WESTESF136QF AHJ City of Tukwila Job Site Expansion Drawing Name FYE-FP-1.cad System ' Remote Area(s) Most Demanding Sprinkler Data 5.6 K -Factor 24.00 at 18.367 Hose Allowance At Source 250.00 Additional Hose Supplies Node Flow(gpm) Occupancy Ordinary Group II Density 0.20gpm/ft2 Number Of Sprinklers Calculated 11 Area of Application 959.23ft2 (Actual 959.23ft2) Coverage Per Sprinkler 120.00ft2 Total Hose Streams 250.00 System Flow Demand Total Water Required (Including Hose Allowance) 303.29 553.29 Maximum Pressure Unbalance In Loops 0.000 Maximum Velocity Above Ground 20.36 between nodes 254 and 137 Maximum Velodty Under Ground 1.15 between nodes 1 and 472 Volume capacity of Wet Pipes Volume capacity of Dry Pipes 3523.02gal Supplies Hose Flow Static Residual @ Flow Node (gpm) (psi) (psi) (gpm) Available @ Total Demand (psi) (gpm) Required Safety Margin (psi) (psi) 1 250.00 140.000 20.000 10900.00 139.516 553.29 72.752 66.765 Contractor Contractor Number KS0414 Contractor Name Western States Fire Protection (Redmond) Address 1 7102 180th Ave NE, Suite A-105 Address 2 City State Zip Code Redmond WA 98052 Contact Name Chris J Isaac Phone (425)881-0100 FAX (425)881-3030 E-mail chris.isaac@wsfp.us Web -Site Contact Title Designer Extension (A ©M.E.P.CAD, Inc. AutoSPRINK®VR5 v5.1.32 06/09/2008 10:28:36AM Page 2 ia Summary Of Outflowing Devices Device Actual Flow (gpm) Job Number: KS0415 Report Description: WET SYSTEM Minimum Flow K -Factor Pressure (gpm) (K) (psi) Sprinkler Sprinkler Sprinkler * Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler 104 102 105 101 103 109 107 106 111 110 108 Most Demanding Sprinkler Data 26.32 24.14 26.47 24.00 25.58 30.49 26.99 26.78 33.30 30.53 28.68 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 22.098 18.578 22.343 18.367 20.862 29.650 23.234 22.864 35.368 29.726 26.225 (M © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 06/09/2008 10:28:36AM Page 3 Node Analysis 1 Job Number: KS0415 Report Description: WET SYSTEM Node Elevation(Foot) Fittings 55 15-8 PO(5-0) 69 15-8 E(2-0) 67 15-8 PO(5-0) 83 15-8 PO(5-0) 87 15-8 PO(5-0) 96 15-8 PO(5-0) 85 15-8 PO(5-0) 100 15-8 PO(5-0) 130 15-8 PO(5-0) 136 15-8 PO(5-0) 137 15-8 PO(5-0) 138 17-3 PO(26-4) 140 18-6 fE(8-11%) 141 15-8 fE(8-11'A) 142 17-3 fE(8-11'/) 246 15-8 2P0(8-0) 215 15-8 P0(8-0) 254 15-8 PO(8-0) 297 17-10 425 -16-1 2P0(43-1) 431 -16-1 472 -12-4 BFP(-5.000) 104 12-0Y2 Spr(-22.098) 102 12-0Y: Spr(-18.578) 105 12-0% Spr(-22.343) 101 12-0'% Spr(-18.367) 103 12-0Y2 Spr(-20.862) 109 12-0% Spr(-29.650) 107 12-0% Spr(-23.234) 106 12-0% Spr(-22.864) 111 12-0% Spr(-35.368) 110 12-0'/ Spr(-29.726) 108 12-0% Spr(-26.225) 1 -22-0 S Pressure(psi) Discharge(gpm) 2.86 22.869 28.309 23.144 23.554 37.871 29.476 24.817 38.294 31.984 28.659 44.662 44.910 44.644 44.379 41.827 41.715 41.689 48.600 64.530 65.105 68.499 22.098 18.578 22.343 18.367 20.862 29.650 23.234 22.864 35.368 29.726 26.225 72.752 26.32 24.14 26.47 24.00 25.58 30.49 26.99 26.78 33.30 30.53 28.68 303.29 [by ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 06/09/2008 10:28:37AM Page 4 Hydraulic Analysis Pipe Type Downstream Upstream M Job Number: KS0415 Report Description: WET SYSTEM Diameter Flow Velocity HWC Elevation Discharge K -Factor Pt Friction Loss Pn Fittings Length Pressure Eq. Length Summary Total Length Route 1 DR 101 83 1.049 12-0% 15-8 Q=24.00 8.91 q=24.00 K=5.6 C=120 18.367 23.144 0.182334 Spr(-18.367) 2E(2-0), PO(5-0) 25-10 Pf 6.351 9-0 Pe -1.575 34-10 Pv BL 83 87 1.610 15-8 15-8 Q=48.14 7.59 C=120 23.144 23.554 0.082036 5-0 Pf 0.410 Pe 5-0 Pv BL 87 100 1.610 15-8 15-8 Q=73.72 11.62 C=120 23.554 24.817 0.180466 7-0 Pf 1.263 Pe 7-0 Pv BL 100 137 1.610 15-8 15-8 Q=100.49 15.84 C=120 24.817 28.659 0.320155 12-0 Pf 3.842 Pe 12-0 Pv BL 137 254 1.610 15-8 15-8 Q=129.17 20.36 C=120 28.659 41.689 0.509407 PO(8-0) 17-7 Pf 13.030 8-0 Pe 25-7 Pv CM 254 215 4.260 15-8 15-8 Q=129.17 2.91 C=120 41.689 41.715 0.004457 6-0 Pf 0.027 Pe 6-0 Pv CM 215 246 4.260 15-8 15-8 Q=239.49 5.39 C=120 41.715 41.827 0.013967 8-0 Pf 0.112 Pe 8-0 Pv CM 246 141 4.260 15-8 15-8 Q=303.29 6.83 C=120 41.827 44.644 0.021620 fE(8-11%) 121-4 Pf 2.817 8-11% Pe 130-3% Pv RN 141 142 4.260 15-8 17-3 Q=303.29 6.83 C=120 44.644 44.379 0.021620 fE(8-11 V2) fE(8-11Y) 1-7 Pf 0.421 17-11 Pe -0.686 19-6 Pv CM 142 138 4.260 17-3 17-3 Q=303.29 6.83 C=120 44.379 44.662 0.021620 13-1 Pf 0.283 Pe 13-1 Pv RN 138 140 4.260 17-3 18-6 Q=303.29 6.83 C=120 44.662 44.910 0.021620 PO(26-4) fE(8-11 Y2) 1-3 Pf 0.790 35-3Y2 Pe -0.542 36-6'A Pv CM 140 297 4.260 18-6 17-10 Q=303.29 6.83 C=120 44.910 48.600 0.021620 2fE(8-111/2) 139-5 Pf 3.401 17-11 Pe 0.289 157-4 Pv CM 297 425 6.357 17-10 -16-1 Q=303.29 3.07 C=120 48.600 64.530 0.003078 12fE(12-7), BV(12-7), fE(10-0), CV(40-3), GV(3-9Y2) 180-10 Pf 1.226 217-5% Pe 14.704 398-3Y2 Pv BL 425 431 8.329 -16-1 -16-1 Q=303.29 1.79 C=120 64.530 65.105 0.000826 PO(43-1) 2fE(16-0), 14P0(43-1) 17-10 Pf 0.575 678-3Y2 Pe -0.000 696-1% Pv MS 431 472 10.020 -16-1 -12-4 Q=303.29 1.23 C=120 65.105 68.499 0.000336 3LtE(16-0), BV(19-0), BFP(-5.000) 20-2 Pf 5.029 67-0 Pe -1.635 87-2 Pv UG 472 1 10.400 -12-4 -22-0 Q=303.29 1.15 C=140 0.000211 112-10114Pf 0.053 68.499 137-1% Pe 4.200 72.752 4LtE(25-6), 2EE(17-6Y2), S 250-0 Pv tia Route 2 DR 102 69 1.049 12-0'/2 15-8 Q=24.14 8.96 q=24.14 K=5.6 C=120 0.184269 25-10 Pf 5.866 18.578 Spr(-18.578) 6-0 Pe -1.575 22.869 3E(2-0) 31-10 Pv BL 69 83 1.610 15-8 15-8 Q=24.14 3.80 C=120 22.869 23.144 0.022876 12-0 Pf 0.275 Pe 12-0 Pv Route 3 DR 103 87 1.049 12-0Y2 15-8 Q=25.58 9.50 q=25.58 K=5.6 C=120 20.862 23.554 0.205131 Spr(-20.862) 3E(2-0), PO(5-0) 9-91/2 Pf 4.267 11-0 Pe -1.575 20-9'2 Pv Route 4 DR 104 55 1.049 12-0Y2 15-8 Q=26.32 9.77 q=26.32 K=5.6 C=120 22.098 27.986 0.216346 Spr(-22.098) 2E(2-0), PO(5-0) 25-6 Pf 7.463 9-0 Pe -1.575 34-6 Pv BL 55 67 1.610 15-8 15-8 Q=26.32 4.15 C=120 27.986 28.309 0.026859 12-0 Pf 0.322 Pe 12-0 Pv BL 67 85 1.610 15-8 15-8 Q=52.80 8.32 C=120 28.309 29.476 0.097322 12-0 Pf 1.168 Pe 12-0 Pv ©M.E.P.CAD, Inc. ,?* AutoSPRINK®VR5 v5.1.32 06/09/2008 10:28: 37AM Page 5 Hydraulic Analysis 1 Job Number: KS0415 Report Description: WET SYSTEM Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K -Factor Pt Pn Fittings Eq. Length Summary Upstream Total Length BL 1.610 Q=79.79 12.57 C=120 0.208928 12-0 Pf 2.507 85 15-8 29.476 Pe 136 15-8 31.984 12-0 Pv BL L 1.610 Q=110.32 17.39 C=120 0.380473 17-7 Pf 9.732 136 15-8 31.984 8-0 Pe 215 15-8 41.715 P0(8-0) 25-7 Pv .* Route 5 DR 1.049 Q=26.47 9.83 C=120 0.218569 25-6 Pf 7.540 105 12-0% q=26.47 K=5.6 22.343 Spr(-22.343) 9-0 Pe -1.575 67 15-8 28.309 2E(2-0), PO(5-0) 34-6 Pv t'+ Route 6 DR 1.049 Q=26.78 9.94 C=120 0.223279 6-9Y: Pf 3.528 106 12-0% q=26.78 K=5.6 22.864 Spr(-22.864) 9-0 Pe -1.575 100 15-8 24.817 2E(2-0), PO(5-0) 15-9Y: Pv Aa Route 7 DR R 1.049 Q=26.99 10.02 C=120 0.226613 25-6 Pf 7.818 107 12-0Y: q=26.99 K=5.6 23.234 Spr(-23.234) 9-0 Pe -1.575 85 15-8 29.476 2E(2-0), PO(5-0) 34-6 Pv Route 8 DR 1.049 Q=28.68 10.65 C=120 0.253479 6-9% Pf 4.000 108 12-0Y: q=28.68 K=5.6 26.225 Spr(-26.225) 9-0 Pe -1.566 137 15-8 28.659 2E(2-0), PO(5-0) 15-9% Pv Route 9 DR 1.049 Q=30.49 11.32 C=120 0.283954 25-6 Pf 9.796 109 12-0% q=30.49 K=5.6 29.650 Spr(-29.650) 9-0 Pe -1.575 96 15-8 37.871 2E(2-0), PO(5-0) 34-6 Pv BL 1.610 Q=30.49 4.81 C=120 0.035252 12-0 Pf 0.423 96 15-8 37.871 Pe 130 15-8 38.294 12-0 Pv BL 1.610 Q=63.80 10.05 C=120 0.138131 17-7 Pf 3.533 130 15-8 38.294 8-0 Pe 246 15-8 41.827 P0(8-0) 25-7 Pv .- Route 10 DR 1.049 Q=30.53 11.33 C=120 0.284630 4-5% Pf 3.832 110 12-0%z q=30.53 K=5.6 29.726 Spr(-29.726) 9-0 Pe -1.575 136 15-8 31.984 2E(2-0), PO(5-0) 13-5'A Pv Route 11 DR 1.049 Q=33.30 12.36 C=120 0.334267 4-5% Pf 4.501 111 12-0Y: q=33.30 K=5.6 35.368 Spr(-35.368) 9-0 Pe -1.575 130 15-8 38.294 2E(2-0), PO(5-0) 13-5% Pv Equivalent Pipe Lengths of Valves and Fittings (C=120 only) 1 C Value Multiplier II Value Of C 100 130 140 150 Multiplying Factor 0.713 1.16 1.33 1.51 / Actual Inside Diameter \ 4.87 = Factor Schedule 40 Steel Pipe Inside Diameter J L,© M.E.P.CAD, Inc. AutoSPRINKO VR5 v5.1.32 06/09/2008 10:28:37AM Page 6 4 5 Hydraulic Analysis Pipe Type Downstream Upstream Diameter Elevation Flow Discharge Job Number: KS0415 Report Description: WET SYSTEM Velocity HWC K -Factor Pt Friction Loss Pn Fittings Length Pressure Eq. Length Summary Total Length Pipe Type Legend Units Legend Fittings Legend AO Arm -Over Diameter BL Branch Line Elevation CM Cross Main Flow DN Drain Discharge DR Drop Velocity DY Dynamic Pressure FM Feed Main Length FR Feed Riser Friction Loss MS Miscellaneous HWC OR Outrigger Pt RN Riser Nipple pn SP Sprig pf ST Stand Pipe Pe UG Underground Pv Inch Foot gpm gpm fps psi Foot psi/Foot Hazen -Williams Constant Total pressure at a point in a pipe Normal pressure at a point in a pipe Pressure loss due to friction between points Pressure due to elevation difference between indicated points Velocity pressure at a point in a pipe ALV AngV b BaIV BFP BV C cplg Cr CV De1V DPV E EE Eel Ee2 FDC fE fEE flg FN fr g GIoV GV Hose HV Hyd LtE mecT Noz P1 P2 PIV PO PrV PRV red S sCV Spr St T Tr U WirF WMV z Alarm Valve Angle Valve Bushing Ball Valve Backflow Preventer Butterfly Valve Cross Flow Turn 90° Coupling Cross Run Check Valve Deluge Valve Dry Pipe Valve 90° Elbow 450 Elbow 11%° Elbow 22%0 Elbow Flow Device Fire Department Connection 90° FireLock(TM) Elbow 45° FireLock(TM) Elbow Flange Floating Node FireLock(TM) Tee Gauge Globe Valve Gate Valve Hose Hose Valve Hydrant Long Turn Elbow Mechanical Tee Nozzle Pump In Pump Out Post Indicating Valve Pipe Outlet Pressure Relief Valve Pressure Reducing Valve Reducer/Adapter Supply Swing Check Valve Sprinkler Strainer Tee Flow Tum 90° Tee Run Union Wirsbo Water Meter Valve Cap ,, ©M.E.P.CAD, Inc. AutoSPRINK®VR5 v5.1.32 06/09/2008 10:28:37AM Page 7 Hydraulic Graph Job Number: KS0415 Report Description: WET SYSTEM M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 06/09/2008 10:28:38AM Page 8 Supply at Node 1 150 Static Pressure 140.000 135 120 105 A p� Pressure, psi 1 N N O N C 1111111111 1111111111111111111111111111111111111111111111111 553.29 c . 3.29 with hose @ 72.752 streams S tem demand curve 10900.00 @ 20.000 1111 11111111111 1 1 11 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 11 1 1 11 1 1 1 1 1 1 1 1 1 111111111 11111111 I 1 1 1 1 1 1 1 1 1 V 91 002 3300 4400 5500 6600 7700 8800 Water flow, gpm 9900 11000 Hydraulic Graph Supply at Node 1 Static Pressure 140.000 Residual Pressure 10900.00 @ 20.000 Available PressureTime of Test 139.516 @ 553.29 System Demand 303.29 @ 72.752 System Demand (Including Hose Allowance) 553.29 @ 72.752 M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 06/09/2008 10:28:38AM Page 8 Flow Diagram (Top View) Job Number: KS0415 Report Description: WET SYSTEM (M © M.E.P.CAD, Inc. ?* AutoSPRINK® VR5 v5.1.32 06/09/2008 10:28:39AM Page 9 FYE #2110 STOCKROOM coFINISHED CEILING EGRESS CORRIDOR co FINISHED 0E14143HEIG ■Id�l_.. rr�1��Ty r�,_ �r„err%rriii�tiiiiittlirii�+i►i'►�'���� illiii,i,�l �[ < ...rte ae, • 0,../643t: s �� SYMBOL LEGEND General Notes EXIT FIXTURE TO BE WAIL MOLNTEO CENTERED ABOVE WORM' T•S• A.P.F. TO CEMERLIFE OF FIXTURE EGRESS ALCOVE FINISHED CEILING HEIOVQ.� BLD'AFF. PV�•� STOCKROOM MISLED DEILINO 11EI011IIrL��7 1T-0•AF F. NOTE?PSTOCKROON LAY•IHCEILINo TO CONTINUE ABOVE TDILE7 ROOM GYP. ID IOP MIN. OFT-0`AF P. AT AREA OF STRUCTURAL BRACING, T G C. 70 ADJUST CEILING AS REQUIRED TOILET ROOM GYP. SD, DEELMN0 ° S 7L0"Arf. mama 111Vel Y AOA/X NOTE.NSTOCKROCN IAY.010EILINO TD CONTINUE ABOVE TOILET ROOM. 4 Mt UN NM P411111r 1 11 ickArAii&101111.4 in VICINITY MAP (Suite #2110) SCALE: 1. Western States Fire Protection to add new pendent/upright heads� new and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary Class II Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for alt appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system onlyjn the areas of work. All other areas are not in contract and WSFP is not responsible for exiting conditions. EMEIGIMEIDelain EXISTING PIPE NEW PIPE X11 NOTE.IPLNDERSIDE Of CORRUGATED METAL DECK 18 . 154•AF F.& 2DLI I•AF.P STEEL SEWS SPAN FRONT TO BACK MO SIDE 70 SIDE LOWEST CLEAR HEIGHT TO THF `a'Y 141 TS•• STET[IS VC V 0. FIREPROOFING OTHER TNI ON COLUMNS ATTACHED TOX.BRACNO. FYE Remote Area: Retail # 2110 CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 occuPANcrcLAss ORD HAZARD II MAX. COVERAGE per HEAD 130 FN DENSITY .20 GPM/Fe for 959.23 Fe SPRINKLER Reliable Model G4A/ F1FR ORIFICE 1/20 K. . 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 PSI FLOW 10900 GPM AT BASE OF RISER, SYSTEM REQUIRES: 303.29 GPM © 64.53 PSI ' At time of Design REMOTE AREA REDUCTION - 37% 945 SQ/FT Ordinary Group II.0.20gpm/ft2 for 959.23ft2 5'-0 FLEX HEADS TO BE USED SALES AREA MASHED CEILNGHEIIDI�T IY•0'AF.F Vv 5'-0 FLEX HEADS TO BE USED TYPICAL FLEXABLE SPRINKLER CONNECTION FLEXHEAD MOUNTING BRACKET PIPE NIPPLE SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS REDUCING FITTING SUSPENDED T BAR GRID SPRINKLER HEAD FLEXHEAD DETAIL NOT TO SCALE FIG.909 SWIVEL SWAY BRACE FITTINGS BRACE PIPE 2/8' KWIK BOLT (2 1/4" EMBED LENGTH) FIG 1000 "FAST CLAMP' SWAY BRACE ATTACHMENT LINE PIPE LATERAL LINE RESTRAINTS laga NON -THREADED BRACE PIPE FIG. 4A PIPE CLAMP FOR SWAY BRACE . © LATERAL BRANCHLINE RESTRAINT MC) NCN•THREADED BRACE PIPE FIG.909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT i 9/9" KWIK BOLT (21/4" EMBED LENGTH) BRACE PIPE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE Hanger No. 07C HILTI Kwik Bolt III 17 MAIN LOCATION''• FNISHEDCelt* FOCHT 11,10.AF,F, 1-9 REVISIONS RISER ROOM A DETAIL HYDRAULIC REFERENCE ONLY NOT TO SCALE SOFFIT ®FNI°0ED CEILING HEK.H1 18,10144'AF F. N ENTRY SOFFIT FNIEFEDOEILINOHEbM 10'.0'AFF. e d CENTERLINE OF MANUAL ROLL.UP GRIM PNNT RET WIS SOFFIT in FINISHED CEIUNGHEI g 5 13''-10 NX"AFF. NOTEIP a:HTPIXYURE•PTD BE CENTERED BETWEEN CLAZNGCHN<IE. ANDALLYANUM PANEL Sprinkler Legend 2 -WAY EARTHQUAKE BRACE DESCRIPTION K SPRAY R3625 Pendent Pendent Upright FINIDFED CEILBLO HEIGHT 11'-10`AFF. D n 1 3 5 7 9 11 APPROVAL: City of Tukwila MFR./MODEL Brass Brass Brass — HANGER SYMBOL 1 BRANCHLINE RESTRAINT Total = 44 155°F 155°F 155°F REL F1FR SSU CONT. NO.: KSO415 DRAWN BY: CHRIS ISAAC SPRK. ON SHEET: SEE LEGEND SPRK. ON JOB: DATE: 06/09/08 Cut Rod Lgth Rounded to Nearest Inch NOTICE Weld starnps'rilustbe Rod Coupling —� All Thread —� Rod Swivel Ring Pi Concrete Construction E E Without Comments As Noted In Red Per The Attached Letter ct i nese plans have been reviewed by The Tukwila Fire Bottom ofconcvaevention Bureau for conformance with current city Hole CenerLionPlneanoffxottandards. Acceptance is suhiect to errors and omissions which do not authorize violations of adopted stanaaras and orainances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings atter this date will void this -acceptance and will require a resubmittal of revised drawings for subsequent approval. Note on Plan: Hanger Number and' A' Dimension inspected before pipers. hung. Do not paint piping Final acceptance is subject to field test and inspection by prior to hydrostatic test The Tukwila Fire, Prevention Bureau. ate NOT TO SCALE HANGER DETA O 0 d IUKWILA FIRE UErHr(i ltiti:.t111� Please call: 575-440Z and give this job No. dam— S�-----'� and exact address for shut. lawn or restoration approval/ VICINITY MAP DETAIL. Western States Fire NOT TO Protection Company 7102180th AVE NE, STE A-105 - REDMOND, WA - 98052 Lic. #: WESTESF1380F WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE/AUSTIN/DALLAS /DECATUR !DENVER /DULUTH/HOUSTON /KANSAS CITY LAS VEGAS/MINNEAPOLIS/ PHOENIX ! PORTLAND /RAPID CITY/ ST. PAUL/SALT LAKE CITY$ SEATTLE Phone: 425.881-0100 Fax: 425.881.3030 SCALE FYE Southcenter Pkwy Tukwila,WA 98188 FYE TI (1 „.. V 0 D c h— z 0 U z 2 2008 b' U' WI��re r. - JUN 10 2008 JUN 01 2008 SHEET FP -1 OF 1 CONTRACTOR: FYE #2110 STOCKROOM (±)c._ ��FINISHED CEILING HEIGHT LJLIyy�� ID-OAFF. T& EGRESS CORRIDOR ((��yy�� FINISHED CEILINGHEI°HTr^�.1 1J7=/ 1OLV AFF. �y limmommiumineviiiitijen 10.0_1111111 I\ FAIR 111111� STOCKROOM //��y��� FINISHED CEILINGHEI3KTT�rIF? L/L/ 17.0.AF.F. \P EXIT FIXTURE TO BE WALL MOUNTED, CENTERED ABOVE DOOR AT T-0' A.F.F. TO CENTERLINE OF FUTURE EGRESS ALCOVE FINISHED CEILING HEIGH& C.0 .kFF. �I GYP. BD SOFFIT MN. OF?LT AFF. ATAREA OF STRUCTURAL BRACING. T.0 C. TO ADJLLBT C EIUEG AS REQUIRED TOILET ROOM GYP. 90. CEILING • B T-s•AFF. NOTEIPSTOCKROON LAY.IN CEILING TO CONTINUE ABOVE TOILET ROOM. WITH OI.T[rou."ns N0TEIPSTOCKR0O9 LAY -IN CEILING TO CONTINUE ABOVE TOILET ROOM.. 3-7 3.7 VICINITY MAP (Suite #2110) SCALE: N I General Notes 1. Western States Fire Protection to add new pendent/upright heads new and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary Class II Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and aualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA. as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not desinned for free7inn conditions 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. VL_ - - -;l EXISTING PIPE -»� NEW PIPE T7 MAIN LOCATION FINISHED CEILING HEIGHT 1 -1a AFF. '1 Y.• 0 RISER ROOM A DETAIL HYDRAULIC REFERENCE ONLY NOT TO SCALE SOFFIT ®FINISHED CEILING HEIGHT 13101H'AFF. Y E ENTRY SOFFIT I,yrJ FINISHED CEILING HEIGHT V 10'-0'0.30. 0 E CENTERLINE OF MANUAL ROLL4IP GRILLE, PAM RETURNS SOFFIT fWISMEU CEILWOHEIGHT�B 1Y-f01N'AFF. NOTE WIGHT FUTURE'D' TO BE CENTERED BETWEEN GLAZING CHANNEL AND AJ.U010 1 PANEL NOTE:WNDERSIDE OF CORRUGATED KETAL DECK IS 13.1' AF.F. B 20'-13AF.F. STEEL SEAMS SPAN FRONT TO BACK AND SIDE TO SIDE LOWEST CLEAR HEIGHT TO STRUCTURE IS ITW A.F.F. THERE IS NO SPRAY ON FIREPROOFING OTHER THAN ON COLLINS ATTACHED TO X-BRACIN0. FYE Remote Area: Retail # 2110 CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY cLJnss_ORD HAZARD II MAX. COVERAGE per HEAD 130 FN DENSITY .20 GPM / Ft'tor 959.23 Ft' SPRINKLER Reliable Model G4A/ F1 FR ORIFICE 1/2M. K. 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 PSI FLOW 10900 GPM AT BASF (W RISER, SYSTEM RE3I IIRF0' 303.29_ GPM ® _64.53 PSI At time of Design REMOTE AREA REDUCTION - 37% 945 SQ/FT Ordinary Group II.0.20gpm/ft2 for 959.23ft2 5'-0 FLEX HEADS TO BE USED SALES AREA FINISHED CEILING HEIGHT 17-PAFF. • 5'-0 FLEX HEADS TO BE USED e/ I FINISHED CEIL WUIISI0HT 1r-1PAF0. B 2 TYPICAL FLEXABLE SPRINKLER CONNECTION:. FLEXHEAD MOUNTING BRACKET PIPE NIPPLE FkV) SPRINKLER BRANCHLIKE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS REDUCING FITTING SUSPENDED T -BAR GRID SPRINKLER HEAD CEILING TILE FLEXHEAD DETAIL NOT TO SCALE FIG. 909 SWIVEL SWAY BRACE FITTING 319' KWIK BOLT (21/4' EMBED LENGTH) FIG. 1000 "FAST CLAMP" SWAY BRACE ATTACHMENT O LATERAL LINE RESTRAINTS NON -THREADED BRACE PIPE *NV SYMBOL LEGEND 2 -WAY EARTHQUAKE BRACE 4 -WAY EARTHQUAKE BRACE REVISIONS DESCRIPTION SYM. SIN QTY. FYE - TI 1/8" =1-0 Sprinkler Legend 3 5 7 9 11 APPROVAL: City of Tukwila SPRAY ORIF. FIN. TEMP. 5.6 Pendent Pendent HYDRAULIC REFERENCE POINT HANGER SYMBOL R3625 5.6 Upright Brass Brass 155°F 155°F MFR./MODEL FIG. 4A PIPE CLAMP FOR SWAY BRACE 319' KWIK BOLT (2 ye EMBED LENGTH) FIG.909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT LATERAL BRANCHLINE RESTRAINT 40 ugO NON -THREADED BRACE PIPE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE Hanger No. 07C HILTI Kwik Bolt III / HILTI Kwik Sok II Rod Coupling Cut Rod Lath Rounded to Nearest Inch Q All Thread Rod CL Swivel Ring Concrete Construction Bottom of Concrete to Center Line of Pipe Note on Plan Note on Plan: Hanger Number and'A Dimension HANGER DETAIL NOT TO SCALE VICINITY MAP DETAIL O E3-5;-) ?-7 Western States Fire NOT TO Brass 155°F REL F1 FR SSU Total = 44 CONT. NO.: K$0415 DRAWN BY: CHRIS ISAAC SPRK. ON SHEET: SEE LEGEND SPRK. ON JOB: BRANCHLINE RESTRAINT DATE: 07/21/08 Protection Company 7102 180th AVE NE, STE A-105 - REDMOND, WA - 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE/AUSTIN/DALLAS/ DECATUR I DENVER/ DULUTH I HOUSTON/KANSAS CITY LAS VEGAS /MINNEAPOLIS / PHOENIX/ PORTLAND /RAPID CITY/ ST. PAUL / SALT LAKE CITY/ SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 FYE 2110 Southcenter Pkwy Tukwila,WA 98188 FYE - TI W >- 0 O CHRIS ISAAC 2 0 v c OT L 31) 0 CUMMINGS CONSTRUCTION CONTRACTOR. SHEET FP -1 OF 1 V , rst u C), v5 • cD x a L.) 0 a) it) ; Cr) (NI CO j • ! C:) (N.1 Cr) rN1 cp LL uJ -C! I LL I 6) < LL • - CO < 1. LLJ 1— UJ • 0 CL : LLI c a) u A: •+, O 1 tr) 4-, • to cm • 3 -1 ci 7 X ,1I FILE COPY FIRE TUK ; I it 11 SHEET INDEX i I ERAL NOTES SYMBOLS LEGEND EET SHEET TITLE FA -01 SYSTEv VATIO FA -02 TYPAL DETAILS -- WRI\G A\3 IVOU\TI\G FA -03 • Fl ALAV SYSTEM FLOC) PLA\ FA -04 11:11' I 11, CALCULATIO \S GE\ EAL), ISE, SITE PLA\ I LI! ......4...astotommt,f,Ha I!! ! I I 0 I; • vo, ji vo , omrneno ,i . ,1„, O Az NOT ' in Red1.1,, O Per T6 AttachedLeter , ;- ;';;;I nese plans have be reviewed. by The Ttii<wila Fire Prevention Bureau tolf.!.4informanc with current city: .-• standards. l-kocar:1.-.Ar4 s eLhiect to errors and I ', II omissions whr,t, c,..i i,li, ,luthorizeiolationS ofadopted standaws and (c.) -J iv.:1 s. T'il responsibititY for the:I dequEl\cy 01; d.: -.,;;.;:i ;•-.4 6tally With the de' signer. !; i Addition5, .:=Giciioos olrivisions ts'Isthese drawings atter ::. this date wOi void t hie Lill' Ptancend will require a is q resubmittal of re vised•'„,kit- iings fdrSubseqUent approval ..; . , Final acceptance it st4 t to field test and inspection bV _ i he Tukwila Fire Prev-4)n Bureap. .n 'i'• I sl Date: 51e) -.S) OD . • iRACUritiP U045'.10,484,,o-.) (smnrs [ • ringS ; - s q01 S114 0/q2pu ritovv-gzg :EA° iese9k; INVd30 381:11hAm1n 4 NO ACF -- A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. rukwtLA FIRE DEPARTMEN1, Please call: 575-4407 and give this job No. o -F )4- and exact address for shut. lown or restoration approval: WIRE DESIGNATION SCHEDULE WIRE SCHEDULE .AND CONDUIT FILL CHART SHIELDE WIRE TO BE:GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH. EACH DEVICE WRAPPED WITH .TAPE AND TAPED AT END ".:•„!.. • .1 ;.'••• • . „ FOR SIEMENS SYST DO NOT INSTALL ADDRESS DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DE DEVICE 01-1-02 WOULD BE 2. DETECTOR AND AUDIBLE CI 3. AUDIBLE/VISUAL CIRCUIT WI BRANCHING IS PERMISSIB 4. INSTALLATION SHALL BE IN ELECTRIC CODE, NFPA 72, 5. INSTALLATION MATERIALS (I STANDARD BOXES, FIBER 0' ARE NOT SUPPLIED BY SIE 6. DETECTORS SHALL NOT BE; AIR STREAM OF AIR SUPPL: 7. WIRING SHALL BE PER PLA TYPE, QUANTITY AND COLO AND UNIQUELY MARKED FO 8. 9. 10. INSTALLING CONTRACTOR S DRAWINGS FOR "AS BUILT" FOR ADDITIONAL INSTALLAT SHEETS AND/OR INSTALLAT THE 120vac POWER ELECTR1 MUST COMPLY WITH ARTICL SPECIFICALLY SECTION 1-51 SOURCES. 120vac POWER 5 DIRECT SUPERVISION OF FIf 11. ALL HORN/STROBE AND S OF 80" A.F.F. OR 6" BELO 12. ALL MANUAL PULL STATIO ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND !O.! I II: • ' I • BLE INITIATING : DEVICES UNTIL PREPROGRAMMED WITH I ICE Sy, BOL DENOTE DEVICE CIRCUIT/ADDRESS THEf10ND DEVICE ON . ADDRESSABLE LOOP 1. UIT 1NG CAL: • LARITY SHALL BE OBSERVED. UPERVISED. NO PARALLEL CONFORMANCE WITH THE NATIONAL DE(S), AND/OR AUTHORITY HAVING JURISDICTION. :6& 1UIT, WIRE, FITTINGS, HANGERS, ICS I04[BLE, FITTINGS, AND ASSOCIATED EQUIPIVENT) SC, 1BERUS DIVISION. ON -t, ,; IN DIRECT • UTLEHS. PER NFPA 72 2-3.5.1 ! yviiik i ,ESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, CODE CONDUCTORS SHALL BE PERMANENTLY, iUTUF IDENTIFICATION. 'ALL R URPO N INlS .;1 N AL 725I ALL AL R OP S HA Ecyi 14. ALL 120VAC CIRCUITS ARE1LRQMDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. iitji 15. PER NFPA 72 SECTION 5— .1.3DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEANUP OrMLL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED: BYiJaHE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING C9NSTRUCTION. DETECTORS THAT HAVE BEA INSTALLED PRIOR TO FINAL CLEAN—UP BY ALL TRADES SHALL BE CLEANE OR REPLACED IN ACCORDANCE WITH NFPA 72 ,URN ONE SET OF ACCURATELY MARKED 4jUCTIONS, REFER TO CATALOG CUT IUCTIONS. 3K SUPPLYING FIRE ALARM SYSTEM PANELS D 760 OF NFPA 70, N.E.C. AND NFPA 72, REFERENCE TO DEDICATED BRANCH POWER T BE APPLIED TO FIRE ALARM PANEL WITHOUT TECHNICIAN. • . VICES SHALL BE MOUNTED AT A HEIGHT 'ED CEILING, WHICHEVER IS LESS. BE MOUNTED AT 48" A.F.F. TO THE WILL BE ON THE RECORD DRAWINGS SET. CHAPTER 7. is 16. WIRING SHALL RUN CONTIN 0USOM FACP TO FIRST DEVICE ON A CIRCUIT • AND THEN FROM DEVICE ij DEV WITHOUT S,PLICING IN PULL BOXES OR OTHER BACK BOXES OF 0FEREil CIRCUITS. • 17. HALL sWIRING SHALL BE MET ED, s'.,;RIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BE EEN1INDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. ALLCABLES SHALL BE MA ED 1 INDICATED, ON, EIRE: ALAR IV .RISER WITH A PERMANENT LABEL AT AL' DEVI(0., , JUNCTION BOXES AND :FACP.1 19. THE :ELECTRICAL CONTRAC R SHA L CLEAN: ALL DIRT AND DEBRIS FROM THE OUTSIDE 'AND INSIDE OF T FIRE )8,LARM I316‘cl BOXES AND JUNCTION BOXES • AFTER COMPLETION OF TH R 'IN;'STALLATION. 20 DETECTORS MUST BE RAT FORorMPERATUFE IN THE ENVIRONMENT IN s WHICH .1T IS LOCATED. . 21 ALL WIRING BETWEEN FLOG S HAL B• E LOCATED IN CONDUIT. • 22 NEPA 72 2007 6.4.2.2.2 AL sTyh'i O• F CLASS ik CIRCUITS 'USING, PHYSICAL CONDUCTORS (E. IV E-14LIC, OP, TICAL FIBER) SHALL BE INSTALLED SUCH THAT THE UTG0,1" G AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO Et,ROL UNIT,:RESPECTIVELY, ARE ROUTED SEPARATELY. :THE OTG6,1'I'' AND RETURN; (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT B THE SAME CABLE I iMULTI—CONDUCTOR CABLE) L.NC40i VRE, OR RACEWAY: 23. NFPA 72 2007 A:6.4.2.2.2 A G OF 6.42:.2 IS TO PROVIDE ADEQUATE SEPARATION BE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUI JELP ENSURE 'PROTECTION OF THE :CABLES FROM PHYSICAL DA AGE E RECOMMENDED iV,INIMOM :SEPARATION TO PREVENT P sY:S141DAlv AGE IS 305 MIVI, (1: ET) WHERE •THE CABLE IS INSTALLED V I1gAfr AND 1.22 M (4 FT) WHERE THE :CABLE :IS INSTALLED • H l!s! • • f • • QUANTITY 3 2 1 2 2 EX • • Ai; •1 SYMBOL DESCRIPTION ' 11: MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT ;EIRE ALARM x CONTROL PANEL XLS—V SIEMENS PROVIDED 66" A.F.F. TO TOP PROVIDED • 66" A.F.F. i 1cEILING MOUNT) : , , WIRE DESIGNATION FIRE ALARM D: S D—C SIEMENS ,:pEMOTE ANNUNCIATOR TO TOP SYMBOL DESCRIPTION : NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE 1111,1 ! D DATA LINE -ADDRESSABLE LOOP ! TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) SET—MC—W SIEMENS H DOOR : HOLDER POWER - 24VDC TWO : #14 FPL/FPLR RED (JACKET) poIlLvI P . DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) ;POWER EX '! •1111 I ii; S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) . 2S STROBE CIRCUIT - RETURN TWISTED PAIR : W/ SHIELD #12 FPL/FPLR RED (JACKET) .I.UUAL INPUT HTRI—D SIEMENS 4S DEEP VERIFY :INTERFACE MODULE •IN FIELD A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) 1 V•SPEAKER CIRCUIT 7 FEED , TWISTED PAIR #14 FPL/FPLR RED (JACKET) •;;STROBE 2V SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) 4S BOX W/ 1G RING I REMOTE INDICATION LIGHT TWO #18 FPL/PLR RED (JACKET) SIEMENS 4S DEEP VERIFY X Low LEVEL AUDIO TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) m UD : UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) ., UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) ' ' M . DDDR : HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) DETECTOR HFP-11 W/ SIEMENS 4S DEEP CEILING •il'ADDRESSABLE—PHOTO) DB -11 BASE W/ 1G RING B BEAM •: DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) • • ; ! 1. •::: . CONDUIT FILL CHART No. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA 1 ! TWO 600V #12 AWG THHN/THWN .244 O.D. : .0467 ! TWO 600V #14 AWG THHN/THWN TWISTED .210 • 0.D. .0346 i 3 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE 1:156 O.D. .0191 , . CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM : THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AR EA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE 1NCH • 3/4" .21 SQUARE INCH „ 1" : 34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 1.34 SQUARE INCH !;! FIGURES ARE BASED ON 407 CONDUIT FILL AND ARE TAKEN FROM. N.E.C., CHP. 9, TABLE 4. ' SHIELDE WIRE TO BE:GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH. EACH DEVICE WRAPPED WITH .TAPE AND TAPED AT END ".:•„!.. • .1 ;.'••• • . „ FOR SIEMENS SYST DO NOT INSTALL ADDRESS DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DE DEVICE 01-1-02 WOULD BE 2. DETECTOR AND AUDIBLE CI 3. AUDIBLE/VISUAL CIRCUIT WI BRANCHING IS PERMISSIB 4. INSTALLATION SHALL BE IN ELECTRIC CODE, NFPA 72, 5. INSTALLATION MATERIALS (I STANDARD BOXES, FIBER 0' ARE NOT SUPPLIED BY SIE 6. DETECTORS SHALL NOT BE; AIR STREAM OF AIR SUPPL: 7. WIRING SHALL BE PER PLA TYPE, QUANTITY AND COLO AND UNIQUELY MARKED FO 8. 9. 10. INSTALLING CONTRACTOR S DRAWINGS FOR "AS BUILT" FOR ADDITIONAL INSTALLAT SHEETS AND/OR INSTALLAT THE 120vac POWER ELECTR1 MUST COMPLY WITH ARTICL SPECIFICALLY SECTION 1-51 SOURCES. 120vac POWER 5 DIRECT SUPERVISION OF FIf 11. ALL HORN/STROBE AND S OF 80" A.F.F. OR 6" BELO 12. ALL MANUAL PULL STATIO ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND !O.! I II: • ' I • BLE INITIATING : DEVICES UNTIL PREPROGRAMMED WITH I ICE Sy, BOL DENOTE DEVICE CIRCUIT/ADDRESS THEf10ND DEVICE ON . ADDRESSABLE LOOP 1. UIT 1NG CAL: • LARITY SHALL BE OBSERVED. UPERVISED. NO PARALLEL CONFORMANCE WITH THE NATIONAL DE(S), AND/OR AUTHORITY HAVING JURISDICTION. :6& 1UIT, WIRE, FITTINGS, HANGERS, ICS I04[BLE, FITTINGS, AND ASSOCIATED EQUIPIVENT) SC, 1BERUS DIVISION. ON -t, ,; IN DIRECT • UTLEHS. PER NFPA 72 2-3.5.1 ! yviiik i ,ESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, CODE CONDUCTORS SHALL BE PERMANENTLY, iUTUF IDENTIFICATION. 'ALL R URPO N INlS .;1 N AL 725I ALL AL R OP S HA Ecyi 14. ALL 120VAC CIRCUITS ARE1LRQMDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. iitji 15. PER NFPA 72 SECTION 5— .1.3DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEANUP OrMLL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED: BYiJaHE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING C9NSTRUCTION. DETECTORS THAT HAVE BEA INSTALLED PRIOR TO FINAL CLEAN—UP BY ALL TRADES SHALL BE CLEANE OR REPLACED IN ACCORDANCE WITH NFPA 72 ,URN ONE SET OF ACCURATELY MARKED 4jUCTIONS, REFER TO CATALOG CUT IUCTIONS. 3K SUPPLYING FIRE ALARM SYSTEM PANELS D 760 OF NFPA 70, N.E.C. AND NFPA 72, REFERENCE TO DEDICATED BRANCH POWER T BE APPLIED TO FIRE ALARM PANEL WITHOUT TECHNICIAN. • . VICES SHALL BE MOUNTED AT A HEIGHT 'ED CEILING, WHICHEVER IS LESS. BE MOUNTED AT 48" A.F.F. TO THE WILL BE ON THE RECORD DRAWINGS SET. CHAPTER 7. is 16. WIRING SHALL RUN CONTIN 0USOM FACP TO FIRST DEVICE ON A CIRCUIT • AND THEN FROM DEVICE ij DEV WITHOUT S,PLICING IN PULL BOXES OR OTHER BACK BOXES OF 0FEREil CIRCUITS. • 17. HALL sWIRING SHALL BE MET ED, s'.,;RIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BE EEN1INDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. ALLCABLES SHALL BE MA ED 1 INDICATED, ON, EIRE: ALAR IV .RISER WITH A PERMANENT LABEL AT AL' DEVI(0., , JUNCTION BOXES AND :FACP.1 19. THE :ELECTRICAL CONTRAC R SHA L CLEAN: ALL DIRT AND DEBRIS FROM THE OUTSIDE 'AND INSIDE OF T FIRE )8,LARM I316‘cl BOXES AND JUNCTION BOXES • AFTER COMPLETION OF TH R 'IN;'STALLATION. 20 DETECTORS MUST BE RAT FORorMPERATUFE IN THE ENVIRONMENT IN s WHICH .1T IS LOCATED. . 21 ALL WIRING BETWEEN FLOG S HAL B• E LOCATED IN CONDUIT. • 22 NEPA 72 2007 6.4.2.2.2 AL sTyh'i O• F CLASS ik CIRCUITS 'USING, PHYSICAL CONDUCTORS (E. IV E-14LIC, OP, TICAL FIBER) SHALL BE INSTALLED SUCH THAT THE UTG0,1" G AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO Et,ROL UNIT,:RESPECTIVELY, ARE ROUTED SEPARATELY. :THE OTG6,1'I'' AND RETURN; (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT B THE SAME CABLE I iMULTI—CONDUCTOR CABLE) L.NC40i VRE, OR RACEWAY: 23. NFPA 72 2007 A:6.4.2.2.2 A G OF 6.42:.2 IS TO PROVIDE ADEQUATE SEPARATION BE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUI JELP ENSURE 'PROTECTION OF THE :CABLES FROM PHYSICAL DA AGE E RECOMMENDED iV,INIMOM :SEPARATION TO PREVENT P sY:S141DAlv AGE IS 305 MIVI, (1: ET) WHERE •THE CABLE IS INSTALLED V I1gAfr AND 1.22 M (4 FT) WHERE THE :CABLE :IS INSTALLED • H l!s! • • f • • QUANTITY 3 2 1 2 2 EX • • Ai; •1 SYMBOL DESCRIPTION ' 11: MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT ;EIRE ALARM x CONTROL PANEL XLS—V SIEMENS PROVIDED 66" A.F.F. TO TOP PROVIDED • 66" A.F.F. i 1cEILING MOUNT) FRA FIRE ALARM D: S D—C SIEMENS ,:pEMOTE ANNUNCIATOR TO TOP 1111,1 ! ' ! i • IfIRE ALARM .ii.SPEAKER STROBE' H (WALL MOUNT) SET—MC—W SIEMENS SIEMENS PROVIDED 66" A.F.F 80 A.F.F. TO BOTTOM poIlLvI REMOTE BOOSTER PAD -3. . SUPPLY TO TOP FIRE ALARM iliSPEAKER STROBE ' j,I;(CEILING MOUNT) ;POWER EX '! •1111 I ii; 4S DEEP BOX VV/ 1-1/2" EXT. • INTERFACE MODULE HTRI—R SIEMENS 4S DEEP VERIFY I, I WITH RELAY IN FIELD . ' mai' .I.UUAL INPUT HTRI—D SIEMENS 4S DEEP VERIFY :INTERFACE MODULE •IN FIELD 4S BOX W/ 1G RING VII' 4S DEEP VERIFY •;;STROBE Lino ONTROL POINT • HCP SIEMENS IN FIELD 4S BOX W/ 1G RING • •;MODULE sL H.: GO SIEMENS 4S DEEP VERIFY •EIREALARM 1 SPEAKER RCEILI NG MOUNT) SET—CW SIEMENS m !;REMOTE CONVENTIONAL HZM -IZONE FIELD MODULE •IN •i: FIRE ALARM SFT—W SIEMENS I . LINEAR BEAM : PBA -1191 SIEMENS PROVIDED VERIFY ' s:SMOKE DETECTOR • IN FIELD i 80" A.F.F. DETECTOR HFP-11 W/ SIEMENS 4S DEEP CEILING •il'ADDRESSABLE—PHOTO) DB -11 BASE W/ 1G RING i tAl :IDUCT SMOKE AD2—P W/ SIEMENS DUCT HOUSING VERIFY DETECTOR TSM MODULE IN FIELD ..1 • ,. •I EAT DETECTOR oil • ili(ADDRESSABLE) ,11 -IRE ALARM 11SPEAKER STROBE HFPT-11 VV/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING SET—MC—CW SIEMENS 4S DEEP BOX CEILING LLC i 1cEILING MOUNT) VV/ 1— 1 / Z LAI. ' ' ! i • IfIRE ALARM .ii.SPEAKER STROBE' H (WALL MOUNT) SET—MC—W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80 A.F.F. TO BOTTOM .7'1 1311 FIRE ALARM iliSPEAKER STROBE ' j,I;(CEILING MOUNT) SET—HMC—CW SIEMENS • 4S DEEP BOX VV/ 1-1/2" EXT. CEILING . •I . .'-FIRE ALARM iSTROBE I II(CEILING MOUNT) ZR—MC—CW SIEMENS • 4S BOX W/ 1G RING CEILING ;1 •;;STROBE :TIRE ALARM : I!WALL MOUNT) • ZR—MC—W SIEMENS • • 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. H.: GO •EIREALARM 1 SPEAKER RCEILI NG MOUNT) SET—CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING ; •i: FIRE ALARM SFT—W SIEMENS 4S DEEP BOX 80" A.F.F. 1 (WALL MOUNT) W/ 1-1/2" EXT. TO BOTTOM • 'I:FIRE ALARM • , STROBE IWP •r(WEATHERPROOF) I • MI MULTI—VOLTAGE CONTROL RELAY SET—S17—WP SIEMENS MT—SUR—BOX VERIFY 1/2" PIPE IN FIELD MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD I: . MAGNETIC w • :DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD 1 FIRE ALARM FA IJBOXTERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD 1,2 FUNCTION BOX •;4, • IABOVE FINISHED • FLOOR 111- F.B.O. F.B.O. N/A VERIFY IN FIELD N/A • N/A N/A N/A : PURNISHED BY • -'0THERS N/A N/A • N/A N/A NOTAPPLICABLE ' • N/A N/A N/A N/A U. .N. ;UNLESS OTHERWISE - N/A . ' !NOTED • N/A • N/A N/A WEATHERPROOF I)EVICE • N/A N/A N/A N/A i?ssiS BUILT ADD OR CHANGE N/A N/A N/A N/A iI61S BUILT EN 'REMOVE N/A N/A N/A , N/A B UE s• •lAs BUILT •!NOTES TO CAD N/A N/A N/A N/A g it Co.yright 2006 Guardidn! SecUtit S .1. • , • • nd. All IR' hts sery 11 6 1 743 IST AVE. SO., SEATTLE, WASHINGTON RELEASE/REVISIONS GO LL1 DESCRIPTION 1 < 0 OE 1,Ln UJ • . , ‘ALE: 1 /'=1 1==i1 DRAWN. BY:. LANDERSON DESIGNED BY: R.VEZZANI DATE:5/12/08 BACKROUND PLAN PROVIDED BY: NUMBER:XXXXX SHEET", 1 I!I :.! ;;IE: I L r,�(,, NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. I THE DUCT SMOKE DETECTOR] ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. ;;.THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. OPER TIN TEMPERATU E: +32'F (O' C) TO 100' F (38' C) HUMIDITY: 0-9333% RELATIVE HUMIDITY, NON -CONDENSING DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OUTLET SAMPLING -\. TUBE FRONT VIEW HFP-11 SMOKE DETECTOR DB -11 STANDARD SMOKE DETECTOR BASE 'END OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. INLET SAMPLING TUBE NOT USED REMOTE + DEVICE LOOP NOT USED REMOTE DEVICE LOOP 470 OHMS INPU (+ AT LEAST,• SIX DUCT,. WIDTHS FROM BEND 6-10 DUCT EQUIVALENT DIAMETERS DUCT DETECTOR LOCATION - FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (-) > TO NEXT DEVICE -r- REAR VIEW DATA IN (+) > > (-) DATA OUT 1 > (+) DATA OUT J7 TYPICAL SMOKE DETE LEL VIII TOR ISTALATION REQUIREMENT FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> CE OR DEVICE w TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE MUSIC CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) COMBINE ALL SFI1 HARD LID --\. RELEASE/REVISIONS DESCRIPTION FROM XLS CONTROL ; FYANEL ❑R,I, PREVI❑US ADDRESSA13UE DEVICE END OF LINE DEVICE!( ,6K 1/4;W SUPERVISED8 WITCH TO NEXT ADDRESSABLE DEVICE f(+) STOP IF LAST DEVICE (-) FROM XLS CONTROL PANEL OR i(+) PREVI❑US ADDRESSABLE DEVICE (-) HTRI—D FROM REMOTE POWER SUPPLY ('S' CABLE) T❑4NEXT DEVICE OR ENP OF LINE HARD LID CEILING SPEAKER SUPPORT TTL=E BRIDGE SHOP DRAWINGS GROUND a) ,✓ V 0 0 x N ro 0 _' 0 to rstN 0 ' w 0 o N N o u 3 < E co i W H z W W O z t cn -o Cj a, tri END OF LINE DEVICE (3.6K 1/4W) SUPERVISED !� RELAY CONTACTS SWITCH (4.04 @ 125VAC) GROUND (4.OA @ 30VDC) LU D 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSI❑N CO •0 END d LINE i 3,6K 1/ UPE TWIT FROM FACP (V❑ICE CIRCUIT) ("V' CABLE) NEXT D:!'DICE OR E1t'D. OF LINE CEILING MOUNTED SPEAKER/STROBE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE • (BACKGOUND MUSIC SHUTDOWN) NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE NOTE 11 VOLTAGE MAX, - CURRENT MAX, - CONT, RES, MAX, - MAX, CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN, LINE SIZE - PREVI❑US ADDRaSSABL DEVICE la i JUNCTION BOX ----\ MOUNTED ON \\ CEILING, FLEX 27 VDC 3.5 r1A DURING POLLING 10 OHMS' 200 FT. (18 , AWG) 0,02uF 0,04uF 14 AWG 18 AWG 0 CND N AC • //40 O TO NEXT NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD. CLOSED.' AND/OR OPEN FOR AT LEAST .25. SEC, TO GUARANTEE DETECTION. SPEAKER STROBE OR STROBE ONLY TO NEXT ADDRE SABLE DEVICE 4S; DEEP BOX W/.1-1/2" EXTENSION RING (SPEAKER 'STROBE) 4S BOX (STROBE ONLY) / JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT CADDY BAR z Z 0 00 __I co e� Q W 0 C� CD:12 z II U- <D CC o LL CO --* 0.R 1- 0 0 S a 0 0 a 123456 INPUT INPUT 'TROUBLE NAC1' NAC2 NAC3 NAC4 AUX _ 1+1- 1'2+2- 2 NC C NO '+ - + - + - + - + - .a m IS -[1(1)11-b1 -9-0 0 0 Q Q 24K. • n 80" A.F.F. SMOKE DETECTOR— SMOKE ETECT❑R— SUSPENDED ILLUMINATED SMOKE DETECTOR MOUNTING SCALE:NONE TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE DO \QT INSTALL ADDRESSABLE \IT AT DEVICES-JI\TIL DREP OGRAMVED W T DEVICES ADDRESS. SCALE:' 1 /8"=1 ' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/12/08 BACKROU,ND PLAN PROVIDED BY: \OB NUMBER:54511 l SHEET'. �. Copyright: .2006 by Guardian Security: Systems, Inc. All Rights !!: , t,'•• .!I 11 I, • ; 12'-O" AFF 10' -0" AFF 10 - 0" AFF E <:[ 0 N 7Q11.ET rTh_f , L 15 - ••••"-F!TC.; A . . D ; CD CD- - :1'4;32- Zi TW:_'• 2- fr'i - iv/ 7.2 115_ 31_. [ A.!•71 D ,th CD- A!;CA 2S,2V _c DI 21 14.4 i", ....... 3he:‘4,49 ----- ----- - 4.1 L 2'› ,•>4("Iz5 2:>: NORTH FYE WESTFI SCALE 104 11 C\2 L. L. IL 11 ' : t. : : • I- ' • , . - '72 1 4 _ - .. 1 _______ 1 __I___ , I CASH WP: AP 7 .._ f„ _ _ ___, , ( Li .47. •1 \ . I t , • SALE'S AR:- __,..• A t .1 2S,2V DT ,4, z. z 0 3 ! I I •i_ I _________ -•-• 1 II • ! '''‘. --- -.. : ....• 15 C ;_71 ! • '."'Ir «.: -I .1. ! I . ! 2 2: ; 1 ' ::" 71 z,v6:2&5E4..--!.• • , : .„. D Tr:, 6 R • : }.3 11 _ FEAT 72 I H- z ' L , . --I OP "";:: r.""•.../•..-44 c.,.-4.;..1._ T., 4,,v, 7 : - ' . , ••k:;"" ;• , • :1 ! ! . 1111 1 HCENTER MALL • •i1' I. • :4 • r CI; • , • • 'LAG NO ES: LI> FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE, FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS.(SEE SIEMENS INSTALLATION SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR. SIEMENS HTRI-D ADDRESSABLE INPUT WITH HOOD VENILLATOR FIRE SUPPRESION SYSTEM, FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL, FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NO NS ALL ADP -ESSAF3LE INOT DEVICESUNTIL PREPROGRAMMED WO DEVICES ADDRESS. AT Copyright 2006 by Guardian Security; Systems, Inc. All Rights Lo .0 (.4 .0 c." j LLJ • RELEASE/REVISIONS cO LIJ z • DESCRIPTION • uJ1• ; • 0 . • • z <1< 4-74-3,r,r7;.4, Lij I (c.CALE: 1/8"=1' DRAWN.. BY: LANDERSON DESIGNED BY:. R.VEZZANI DATE:5/12/08 BACKROUND PLAN PROVIDED BY: .‘JOB NUMBER:54511 .1 SHEET. FA -0 . 11i.! .!, i !' _!' • 7 ..! : A 114 •• 4 SYSTEM CA ULATIONS FYE FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations Current Ld Standby: Alarm: Current Load: Standby: Device Ty ie HFP-11 Amps 0.0022 0.0635 0.009600 Total 0.0022 . 0.0635 0.0096 Amps 0.0023 Total Device Type Total Total 0.001600 0.0035 0.0731 rrent Load: 0.0731 For 24 Hours = Amp -hours Main System Board SET -MC @15CD SET -MC @30CD SET -MC ©75CD SET -MC @110CD SETHMC-C@115CD.' SET-HMC-C@135CD SET HMC-C@185CD ZR -MC @15CD ZR -MC @30CD HCP For 5 Minutes= Amp -hours 25% Derating= Amp -hours Standby Current Load: Alarm Current Load: For 24 Hours = 0.956 Amps For 5 Minutes= Amp -hours 25% Derating= 0.03011E1=1l 0.064 : NI� 0.098 11 1111111111M111111111 x;11®lf 0.128 MI MI 1®I1 Amp -hours t Imo{NMI at 11111 IRII 0.636 Amp -hours Amp -hours Bettery P -!r to be Used: 12VDC Amp -hours Amp -hours ( . PROJECT Battery Pair to be Used: 12VDC Amp -hours BATTERY SIZE' .G CALCULATON Notification Appliance WESTFIELD SOUTHCENTER MALL ircuit Detail 1 � Panel: Date: May 22, 2008 CIRCUIT: QTY 1 1 FYE WESTFIELD SOUTHCENTER MALL SCALE 1132".1' Device Type SET -MC @15CD SET -MC @30CD 0 SET -MC @75CD Alarm Current Alarm Total Wire Size ;Length Voltage at EOL Circuit Total 0 SET -MC @110CD 2 SET-HMC-C@115CD 0 SET-HMC-C@177CD 0 SET -HMC @135CD 0 SET -HMC @185CD 2 Z-MC@15CD Z-MC@30CD Total Wire Resistance (R ) (WL*2)*(R/ft) Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E ) (E= I * R) 0.86 0.93 0.80 19.60 0 SET-MC-CW@110CD DEVICES= PROJECT: Panel: Date: CIRCUIT: QTY 4 0 TOTAL m A= 19.6049364 Notification Appliance Circuit Detail WESTFIELD SOUTHCENTER MALL FYE May 20, 2008 Wire Resistance 2;58: CURRENT TOTAL= 7.2 CO0 JCO <0) 2 2z WO W ZZ >- CC Uczn Q CC W CO SPEAKER CIRCUIT Device Type 70.7V1/8 Alarm Current Alarm Total Wire Size ength Voltage at EOL Circuit Total Total Wire Resistance (R ) 2S,2V S,2V 2S,2V 2S,2V 2S,2V ( WL * 2 )* (R/ft) Total Device Load, Amps (I) 0.01 (Total Cct Load) Voltage Drop (E ) EOL Voltage (20.4 - E) 115 C 115 C 15 15 30 C 15 DEVICES= 0'. TOTAL m A= 20.37900912 SCALE:: 1 DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08. BACKROUND PLAN PROVIDED,':BY: ,J.OB NUMBER:5451 1 RISER DIAGRAM VOLTAGE DRO ALCULATION Copyri•ht 2006 b Guardian Securit S stems, Inc. All R. hts 2636 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-227 08-S-287 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: FYE -2-146 Southcenter Mall Permit No.: 08-S287 Date: June 10, 2008, 2008 Reviewer: Steve Kohler Fire Inspector/Plan Review (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. t 414 Hydraulic Overview 1 Job Number: KSO415 Report Description: WET SYSTEM Job Job Number Design Engineer KS0415 CHRIS ISAAC Job Name Phone FAX FYE 425.881.0100 425.881.3030 Address 1 State CertficaboMicense Number 2110 Southcenter Pkwy WESTESF136QF Address 2 AR) City of Tukwila City State Zip Code Job Site Tukwila WA 98188 Expansion System Density Area of Application 0.20gpm/ft2 959.23ft2 (Actual 959.23ft2) Most Demanding Sprinkler Data Nose Streams 5.6 K-Factor 24.00 at 18.367 250.00 Coverage Per Sprinkle. Number Of Sprinklers Calculated 120.00ft2 11 System Pressure Demand System Flow Demand 72.752 303.29 Total Demand Pressure Result 553.29 @ 72.752 +66.765 (47.9%) Supplies Check Point Gauges Node Flow(gpm) Hose Flow(gpm) Static(psi) Residual(psi) Identifier Pressure(psi) K-Factor(K) Flow(gpm) 1 10900.00 250.00 140.000 20.000 ops 9 t f rCo 1 k. /11 y«.11 A . FYE-FP-1.cad Supply at Node 1 (10900.00, 250.00, 140.000, 20.000) ACA --ErA Pressure, psi cn o 0n 8' 01 `8 con o EA E �uuuw�uuuui�uuuw�inuuu�uuuw�uuuui�unuw�uuuui�nuun�uuuw Static Pressure 140.000 rJ 0 iI6 lel wi h hose streams N553.29 ..03.29 @ 72.752 System demand curve 10900.00 @ 20.000{ I'I' a N•11111111111111111111111111111 111111111 111111111 111111 h 1 111111111 1111 11 11 1 v �p�a�� �t 111AT330q" 5500 6600 7700 8800 9900 11000 Water flow, gpm A[S ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 06/09/2008 10:28:35AM Page 1 (:15A Hydraulic Summary 1 Job Number: KS0415 Report Description: WET SYSTEM Job Job Number KS0415 Job Name FYE Address 1 2110 Southcenter Pkwy Address 2 City State Zip Code Tukwila WA 98188 Design Engineer CHRIS ISAAC State Cenrfication/License Number WESTESF136QF AHJ City of Tukwila Job Site Expansion Drawing Name FYE-FP-1.cad System ' Remote Area(s) Most Demanding Sprinkler Data 5.6 K -Factor 24.00 at 18.367 Hose Allowance At Source 250.00 Additional Hose Supplies Node Flow(gpm) Occupancy Ordinary Group II Density 0.20gpm/ft2 Number Of Sprinklers Calculated 11 Area of Application 959.23ft2 (Actual 959.23ft2) Coverage Per Sprinkler 120.00ft2 Total Hose Streams 250.00 System Flow Demand Total Water Required (Including Hose Allowance) 303.29 553.29 Maximum Pressure Unbalance In Loops 0.000 Maximum Velocity Above Ground 20.36 between nodes 254 and 137 Maximum Velodty Under Ground 1.15 between nodes 1 and 472 Volume capacity of Wet Pipes Volume capacity of Dry Pipes 3523.02gal Supplies Hose Flow Static Residual @ Flow Node (gpm) (psi) (psi) (gpm) Available @ Total Demand (psi) (gpm) Required Safety Margin (psi) (psi) 1 250.00 140.000 20.000 10900.00 139.516 553.29 72.752 66.765 Contractor Contractor Number KS0414 Contractor Name Western States Fire Protection (Redmond) Address 1 7102 180th Ave NE, Suite A-105 Address 2 City State Zip Code Redmond WA 98052 Contact Name Chris J Isaac Phone (425)881-0100 FAX (425)881-3030 E-mail chris.isaac@wsfp.us Web -Site Contact Title Designer Extension (A ©M.E.P.CAD, Inc. AutoSPRINK®VR5 v5.1.32 06/09/2008 10:28:36AM Page 2 ia Summary Of Outflowing Devices Device Actual Flow (gpm) Job Number: KS0415 Report Description: WET SYSTEM Minimum Flow K -Factor Pressure (gpm) (K) (psi) Sprinkler Sprinkler Sprinkler * Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler 104 102 105 101 103 109 107 106 111 110 108 Most Demanding Sprinkler Data 26.32 24.14 26.47 24.00 25.58 30.49 26.99 26.78 33.30 30.53 28.68 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 22.098 18.578 22.343 18.367 20.862 29.650 23.234 22.864 35.368 29.726 26.225 (M © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 06/09/2008 10:28:36AM Page 3 Node Analysis 1 Job Number: KS0415 Report Description: WET SYSTEM Node Elevation(Foot) Fittings 55 15-8 PO(5-0) 69 15-8 E(2-0) 67 15-8 PO(5-0) 83 15-8 PO(5-0) 87 15-8 PO(5-0) 96 15-8 PO(5-0) 85 15-8 PO(5-0) 100 15-8 PO(5-0) 130 15-8 PO(5-0) 136 15-8 PO(5-0) 137 15-8 PO(5-0) 138 17-3 PO(26-4) 140 18-6 fE(8-11%) 141 15-8 fE(8-11'A) 142 17-3 fE(8-11'/) 246 15-8 2P0(8-0) 215 15-8 P0(8-0) 254 15-8 PO(8-0) 297 17-10 425 -16-1 2P0(43-1) 431 -16-1 472 -12-4 BFP(-5.000) 104 12-0Y2 Spr(-22.098) 102 12-0Y: Spr(-18.578) 105 12-0% Spr(-22.343) 101 12-0'% Spr(-18.367) 103 12-0Y2 Spr(-20.862) 109 12-0% Spr(-29.650) 107 12-0% Spr(-23.234) 106 12-0% Spr(-22.864) 111 12-0% Spr(-35.368) 110 12-0'/ Spr(-29.726) 108 12-0% Spr(-26.225) 1 -22-0 S Pressure(psi) Discharge(gpm) 2.86 22.869 28.309 23.144 23.554 37.871 29.476 24.817 38.294 31.984 28.659 44.662 44.910 44.644 44.379 41.827 41.715 41.689 48.600 64.530 65.105 68.499 22.098 18.578 22.343 18.367 20.862 29.650 23.234 22.864 35.368 29.726 26.225 72.752 26.32 24.14 26.47 24.00 25.58 30.49 26.99 26.78 33.30 30.53 28.68 303.29 [by ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 06/09/2008 10:28:37AM Page 4 Hydraulic Analysis Pipe Type Downstream Upstream M Job Number: KS0415 Report Description: WET SYSTEM Diameter Flow Velocity HWC Elevation Discharge K -Factor Pt Friction Loss Pn Fittings Length Pressure Eq. Length Summary Total Length Route 1 DR 101 83 1.049 12-0% 15-8 Q=24.00 8.91 q=24.00 K=5.6 C=120 18.367 23.144 0.182334 Spr(-18.367) 2E(2-0), PO(5-0) 25-10 Pf 6.351 9-0 Pe -1.575 34-10 Pv BL 83 87 1.610 15-8 15-8 Q=48.14 7.59 C=120 23.144 23.554 0.082036 5-0 Pf 0.410 Pe 5-0 Pv BL 87 100 1.610 15-8 15-8 Q=73.72 11.62 C=120 23.554 24.817 0.180466 7-0 Pf 1.263 Pe 7-0 Pv BL 100 137 1.610 15-8 15-8 Q=100.49 15.84 C=120 24.817 28.659 0.320155 12-0 Pf 3.842 Pe 12-0 Pv BL 137 254 1.610 15-8 15-8 Q=129.17 20.36 C=120 28.659 41.689 0.509407 PO(8-0) 17-7 Pf 13.030 8-0 Pe 25-7 Pv CM 254 215 4.260 15-8 15-8 Q=129.17 2.91 C=120 41.689 41.715 0.004457 6-0 Pf 0.027 Pe 6-0 Pv CM 215 246 4.260 15-8 15-8 Q=239.49 5.39 C=120 41.715 41.827 0.013967 8-0 Pf 0.112 Pe 8-0 Pv CM 246 141 4.260 15-8 15-8 Q=303.29 6.83 C=120 41.827 44.644 0.021620 fE(8-11%) 121-4 Pf 2.817 8-11% Pe 130-3% Pv RN 141 142 4.260 15-8 17-3 Q=303.29 6.83 C=120 44.644 44.379 0.021620 fE(8-11 V2) fE(8-11Y) 1-7 Pf 0.421 17-11 Pe -0.686 19-6 Pv CM 142 138 4.260 17-3 17-3 Q=303.29 6.83 C=120 44.379 44.662 0.021620 13-1 Pf 0.283 Pe 13-1 Pv RN 138 140 4.260 17-3 18-6 Q=303.29 6.83 C=120 44.662 44.910 0.021620 PO(26-4) fE(8-11 Y2) 1-3 Pf 0.790 35-3Y2 Pe -0.542 36-6'A Pv CM 140 297 4.260 18-6 17-10 Q=303.29 6.83 C=120 44.910 48.600 0.021620 2fE(8-111/2) 139-5 Pf 3.401 17-11 Pe 0.289 157-4 Pv CM 297 425 6.357 17-10 -16-1 Q=303.29 3.07 C=120 48.600 64.530 0.003078 12fE(12-7), BV(12-7), fE(10-0), CV(40-3), GV(3-9Y2) 180-10 Pf 1.226 217-5% Pe 14.704 398-3Y2 Pv BL 425 431 8.329 -16-1 -16-1 Q=303.29 1.79 C=120 64.530 65.105 0.000826 PO(43-1) 2fE(16-0), 14P0(43-1) 17-10 Pf 0.575 678-3Y2 Pe -0.000 696-1% Pv MS 431 472 10.020 -16-1 -12-4 Q=303.29 1.23 C=120 65.105 68.499 0.000336 3LtE(16-0), BV(19-0), BFP(-5.000) 20-2 Pf 5.029 67-0 Pe -1.635 87-2 Pv UG 472 1 10.400 -12-4 -22-0 Q=303.29 1.15 C=140 0.000211 112-10114Pf 0.053 68.499 137-1% Pe 4.200 72.752 4LtE(25-6), 2EE(17-6Y2), S 250-0 Pv tia Route 2 DR 102 69 1.049 12-0'/2 15-8 Q=24.14 8.96 q=24.14 K=5.6 C=120 0.184269 25-10 Pf 5.866 18.578 Spr(-18.578) 6-0 Pe -1.575 22.869 3E(2-0) 31-10 Pv BL 69 83 1.610 15-8 15-8 Q=24.14 3.80 C=120 22.869 23.144 0.022876 12-0 Pf 0.275 Pe 12-0 Pv Route 3 DR 103 87 1.049 12-0Y2 15-8 Q=25.58 9.50 q=25.58 K=5.6 C=120 20.862 23.554 0.205131 Spr(-20.862) 3E(2-0), PO(5-0) 9-91/2 Pf 4.267 11-0 Pe -1.575 20-9'2 Pv Route 4 DR 104 55 1.049 12-0Y2 15-8 Q=26.32 9.77 q=26.32 K=5.6 C=120 22.098 27.986 0.216346 Spr(-22.098) 2E(2-0), PO(5-0) 25-6 Pf 7.463 9-0 Pe -1.575 34-6 Pv BL 55 67 1.610 15-8 15-8 Q=26.32 4.15 C=120 27.986 28.309 0.026859 12-0 Pf 0.322 Pe 12-0 Pv BL 67 85 1.610 15-8 15-8 Q=52.80 8.32 C=120 28.309 29.476 0.097322 12-0 Pf 1.168 Pe 12-0 Pv ©M.E.P.CAD, Inc. ,?* AutoSPRINK®VR5 v5.1.32 06/09/2008 10:28: 37AM Page 5 Hydraulic Analysis 1 Job Number: KS0415 Report Description: WET SYSTEM Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K -Factor Pt Pn Fittings Eq. Length Summary Upstream Total Length BL 1.610 Q=79.79 12.57 C=120 0.208928 12-0 Pf 2.507 85 15-8 29.476 Pe 136 15-8 31.984 12-0 Pv BL L 1.610 Q=110.32 17.39 C=120 0.380473 17-7 Pf 9.732 136 15-8 31.984 8-0 Pe 215 15-8 41.715 P0(8-0) 25-7 Pv .* Route 5 DR 1.049 Q=26.47 9.83 C=120 0.218569 25-6 Pf 7.540 105 12-0% q=26.47 K=5.6 22.343 Spr(-22.343) 9-0 Pe -1.575 67 15-8 28.309 2E(2-0), PO(5-0) 34-6 Pv t'+ Route 6 DR 1.049 Q=26.78 9.94 C=120 0.223279 6-9Y: Pf 3.528 106 12-0% q=26.78 K=5.6 22.864 Spr(-22.864) 9-0 Pe -1.575 100 15-8 24.817 2E(2-0), PO(5-0) 15-9Y: Pv Aa Route 7 DR R 1.049 Q=26.99 10.02 C=120 0.226613 25-6 Pf 7.818 107 12-0Y: q=26.99 K=5.6 23.234 Spr(-23.234) 9-0 Pe -1.575 85 15-8 29.476 2E(2-0), PO(5-0) 34-6 Pv Route 8 DR 1.049 Q=28.68 10.65 C=120 0.253479 6-9% Pf 4.000 108 12-0Y: q=28.68 K=5.6 26.225 Spr(-26.225) 9-0 Pe -1.566 137 15-8 28.659 2E(2-0), PO(5-0) 15-9% Pv Route 9 DR 1.049 Q=30.49 11.32 C=120 0.283954 25-6 Pf 9.796 109 12-0% q=30.49 K=5.6 29.650 Spr(-29.650) 9-0 Pe -1.575 96 15-8 37.871 2E(2-0), PO(5-0) 34-6 Pv BL 1.610 Q=30.49 4.81 C=120 0.035252 12-0 Pf 0.423 96 15-8 37.871 Pe 130 15-8 38.294 12-0 Pv BL 1.610 Q=63.80 10.05 C=120 0.138131 17-7 Pf 3.533 130 15-8 38.294 8-0 Pe 246 15-8 41.827 P0(8-0) 25-7 Pv .- Route 10 DR 1.049 Q=30.53 11.33 C=120 0.284630 4-5% Pf 3.832 110 12-0%z q=30.53 K=5.6 29.726 Spr(-29.726) 9-0 Pe -1.575 136 15-8 31.984 2E(2-0), PO(5-0) 13-5'A Pv Route 11 DR 1.049 Q=33.30 12.36 C=120 0.334267 4-5% Pf 4.501 111 12-0Y: q=33.30 K=5.6 35.368 Spr(-35.368) 9-0 Pe -1.575 130 15-8 38.294 2E(2-0), PO(5-0) 13-5% Pv Equivalent Pipe Lengths of Valves and Fittings (C=120 only) 1 C Value Multiplier II Value Of C 100 130 140 150 Multiplying Factor 0.713 1.16 1.33 1.51 / Actual Inside Diameter \ 4.87 = Factor Schedule 40 Steel Pipe Inside Diameter J L,© M.E.P.CAD, Inc. AutoSPRINKO VR5 v5.1.32 06/09/2008 10:28:37AM Page 6 4 5 Hydraulic Analysis Pipe Type Downstream Upstream Diameter Elevation Flow Discharge Job Number: KS0415 Report Description: WET SYSTEM Velocity HWC K -Factor Pt Friction Loss Pn Fittings Length Pressure Eq. Length Summary Total Length Pipe Type Legend Units Legend Fittings Legend AO Arm -Over Diameter BL Branch Line Elevation CM Cross Main Flow DN Drain Discharge DR Drop Velocity DY Dynamic Pressure FM Feed Main Length FR Feed Riser Friction Loss MS Miscellaneous HWC OR Outrigger Pt RN Riser Nipple pn SP Sprig pf ST Stand Pipe Pe UG Underground Pv Inch Foot gpm gpm fps psi Foot psi/Foot Hazen -Williams Constant Total pressure at a point in a pipe Normal pressure at a point in a pipe Pressure loss due to friction between points Pressure due to elevation difference between indicated points Velocity pressure at a point in a pipe ALV AngV b BaIV BFP BV C cplg Cr CV De1V DPV E EE Eel Ee2 FDC fE fEE flg FN fr g GIoV GV Hose HV Hyd LtE mecT Noz P1 P2 PIV PO PrV PRV red S sCV Spr St T Tr U WirF WMV z Alarm Valve Angle Valve Bushing Ball Valve Backflow Preventer Butterfly Valve Cross Flow Turn 90° Coupling Cross Run Check Valve Deluge Valve Dry Pipe Valve 90° Elbow 450 Elbow 11%° Elbow 22%0 Elbow Flow Device Fire Department Connection 90° FireLock(TM) Elbow 45° FireLock(TM) Elbow Flange Floating Node FireLock(TM) Tee Gauge Globe Valve Gate Valve Hose Hose Valve Hydrant Long Turn Elbow Mechanical Tee Nozzle Pump In Pump Out Post Indicating Valve Pipe Outlet Pressure Relief Valve Pressure Reducing Valve Reducer/Adapter Supply Swing Check Valve Sprinkler Strainer Tee Flow Tum 90° Tee Run Union Wirsbo Water Meter Valve Cap ,, ©M.E.P.CAD, Inc. AutoSPRINK®VR5 v5.1.32 06/09/2008 10:28:37AM Page 7 Hydraulic Graph Job Number: KS0415 Report Description: WET SYSTEM M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 06/09/2008 10:28:38AM Page 8 Supply at Node 1 150 Static Pressure 140.000 135 120 105 A p� Pressure, psi 1 N N O N C 1111111111 1111111111111111111111111111111111111111111111111 553.29 c . 3.29 with hose @ 72.752 streams S tem demand curve 10900.00 @ 20.000 1111 11111111111 1 1 11 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 11 1 1 11 1 1 1 1 1 1 1 1 1 111111111 11111111 I 1 1 1 1 1 1 1 1 1 V 91 002 3300 4400 5500 6600 7700 8800 Water flow, gpm 9900 11000 Hydraulic Graph Supply at Node 1 Static Pressure 140.000 Residual Pressure 10900.00 @ 20.000 Available PressureTime of Test 139.516 @ 553.29 System Demand 303.29 @ 72.752 System Demand (Including Hose Allowance) 553.29 @ 72.752 M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 06/09/2008 10:28:38AM Page 8 Flow Diagram (Top View) Job Number: KS0415 Report Description: WET SYSTEM (M © M.E.P.CAD, Inc. ?* AutoSPRINK® VR5 v5.1.32 06/09/2008 10:28:39AM Page 9 FYE #2110 STOCKROOM coFINISHED CEILING EGRESS CORRIDOR co FINISHED 0E14143HEIG ■Id�l_.. rr�1��Ty r�,_ �r„err%rriii�tiiiiittlirii�+i►i'►�'���� illiii,i,�l �[ < ...rte ae, • 0,../643t: s �� SYMBOL LEGEND General Notes EXIT FIXTURE TO BE WAIL MOLNTEO CENTERED ABOVE WORM' T•S• A.P.F. TO CEMERLIFE OF FIXTURE EGRESS ALCOVE FINISHED CEILING HEIOVQ.� BLD'AFF. PV�•� STOCKROOM MISLED DEILINO 11EI011IIrL��7 1T-0•AF F. NOTE?PSTOCKROON LAY•IHCEILINo TO CONTINUE ABOVE TDILE7 ROOM GYP. ID IOP MIN. OFT-0`AF P. AT AREA OF STRUCTURAL BRACING, T G C. 70 ADJUST CEILING AS REQUIRED TOILET ROOM GYP. SD, DEELMN0 ° S 7L0"Arf. mama 111Vel Y AOA/X NOTE.NSTOCKROCN IAY.010EILINO TD CONTINUE ABOVE TOILET ROOM. 4 Mt UN NM P411111r 1 11 ickArAii&101111.4 in VICINITY MAP (Suite #2110) SCALE: 1. Western States Fire Protection to add new pendent/upright heads� new and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary Class II Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for alt appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system onlyjn the areas of work. All other areas are not in contract and WSFP is not responsible for exiting conditions. EMEIGIMEIDelain EXISTING PIPE NEW PIPE X11 NOTE.IPLNDERSIDE Of CORRUGATED METAL DECK 18 . 154•AF F.& 2DLI I•AF.P STEEL SEWS SPAN FRONT TO BACK MO SIDE 70 SIDE LOWEST CLEAR HEIGHT TO THF `a'Y 141 TS•• STET[IS VC V 0. FIREPROOFING OTHER TNI ON COLUMNS ATTACHED TOX.BRACNO. FYE Remote Area: Retail # 2110 CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 occuPANcrcLAss ORD HAZARD II MAX. COVERAGE per HEAD 130 FN DENSITY .20 GPM/Fe for 959.23 Fe SPRINKLER Reliable Model G4A/ F1FR ORIFICE 1/20 K. . 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 PSI FLOW 10900 GPM AT BASE OF RISER, SYSTEM REQUIRES: 303.29 GPM © 64.53 PSI ' At time of Design REMOTE AREA REDUCTION - 37% 945 SQ/FT Ordinary Group II.0.20gpm/ft2 for 959.23ft2 5'-0 FLEX HEADS TO BE USED SALES AREA MASHED CEILNGHEIIDI�T IY•0'AF.F Vv 5'-0 FLEX HEADS TO BE USED TYPICAL FLEXABLE SPRINKLER CONNECTION FLEXHEAD MOUNTING BRACKET PIPE NIPPLE SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS REDUCING FITTING SUSPENDED T BAR GRID SPRINKLER HEAD FLEXHEAD DETAIL NOT TO SCALE FIG.909 SWIVEL SWAY BRACE FITTINGS BRACE PIPE 2/8' KWIK BOLT (2 1/4" EMBED LENGTH) FIG 1000 "FAST CLAMP' SWAY BRACE ATTACHMENT LINE PIPE LATERAL LINE RESTRAINTS laga NON -THREADED BRACE PIPE FIG. 4A PIPE CLAMP FOR SWAY BRACE . © LATERAL BRANCHLINE RESTRAINT MC) NCN•THREADED BRACE PIPE FIG.909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT i 9/9" KWIK BOLT (21/4" EMBED LENGTH) BRACE PIPE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE Hanger No. 07C HILTI Kwik Bolt III 17 MAIN LOCATION''• FNISHEDCelt* FOCHT 11,10.AF,F, 1-9 REVISIONS RISER ROOM A DETAIL HYDRAULIC REFERENCE ONLY NOT TO SCALE SOFFIT ®FNI°0ED CEILING HEK.H1 18,10144'AF F. N ENTRY SOFFIT FNIEFEDOEILINOHEbM 10'.0'AFF. e d CENTERLINE OF MANUAL ROLL.UP GRIM PNNT RET WIS SOFFIT in FINISHED CEIUNGHEI g 5 13''-10 NX"AFF. NOTEIP a:HTPIXYURE•PTD BE CENTERED BETWEEN CLAZNGCHN<IE. ANDALLYANUM PANEL Sprinkler Legend 2 -WAY EARTHQUAKE BRACE DESCRIPTION K SPRAY R3625 Pendent Pendent Upright FINIDFED CEILBLO HEIGHT 11'-10`AFF. D n 1 3 5 7 9 11 APPROVAL: City of Tukwila MFR./MODEL Brass Brass Brass — HANGER SYMBOL 1 BRANCHLINE RESTRAINT Total = 44 155°F 155°F 155°F REL F1FR SSU CONT. NO.: KSO415 DRAWN BY: CHRIS ISAAC SPRK. ON SHEET: SEE LEGEND SPRK. ON JOB: DATE: 06/09/08 Cut Rod Lgth Rounded to Nearest Inch NOTICE Weld starnps'rilustbe Rod Coupling —� All Thread —� Rod Swivel Ring Pi Concrete Construction E E Without Comments As Noted In Red Per The Attached Letter ct i nese plans have been reviewed by The Tukwila Fire Bottom ofconcvaevention Bureau for conformance with current city Hole CenerLionPlneanoffxottandards. Acceptance is suhiect to errors and omissions which do not authorize violations of adopted stanaaras and orainances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings atter this date will void this -acceptance and will require a resubmittal of revised drawings for subsequent approval. Note on Plan: Hanger Number and' A' Dimension inspected before pipers. hung. Do not paint piping Final acceptance is subject to field test and inspection by prior to hydrostatic test The Tukwila Fire, Prevention Bureau. ate NOT TO SCALE HANGER DETA O 0 d IUKWILA FIRE UErHr(i ltiti:.t111� Please call: 575-440Z and give this job No. dam— S�-----'� and exact address for shut. lawn or restoration approval/ VICINITY MAP DETAIL. Western States Fire NOT TO Protection Company 7102180th AVE NE, STE A-105 - REDMOND, WA - 98052 Lic. #: WESTESF1380F WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE/AUSTIN/DALLAS /DECATUR !DENVER /DULUTH/HOUSTON /KANSAS CITY LAS VEGAS/MINNEAPOLIS/ PHOENIX ! PORTLAND /RAPID CITY/ ST. PAUL/SALT LAKE CITY$ SEATTLE Phone: 425.881-0100 Fax: 425.881.3030 SCALE FYE Southcenter Pkwy Tukwila,WA 98188 FYE TI (1 „.. V 0 D c h— z 0 U z 2 2008 b' U' WI��re r. - JUN 10 2008 JUN 01 2008 SHEET FP -1 OF 1 CONTRACTOR: FYE #2110 STOCKROOM (±)c._ ��FINISHED CEILING HEIGHT LJLIyy�� ID-OAFF. T& EGRESS CORRIDOR ((��yy�� FINISHED CEILINGHEI°HTr^�.1 1J7=/ 1OLV AFF. �y limmommiumineviiiitijen 10.0_1111111 I\ FAIR 111111� STOCKROOM //��y��� FINISHED CEILINGHEI3KTT�rIF? L/L/ 17.0.AF.F. \P EXIT FIXTURE TO BE WALL MOUNTED, CENTERED ABOVE DOOR AT T-0' A.F.F. TO CENTERLINE OF FUTURE EGRESS ALCOVE FINISHED CEILING HEIGH& C.0 .kFF. �I GYP. BD SOFFIT MN. OF?LT AFF. ATAREA OF STRUCTURAL BRACING. T.0 C. TO ADJLLBT C EIUEG AS REQUIRED TOILET ROOM GYP. 90. CEILING • B T-s•AFF. NOTEIPSTOCKROON LAY.IN CEILING TO CONTINUE ABOVE TOILET ROOM. WITH OI.T[rou."ns N0TEIPSTOCKR0O9 LAY -IN CEILING TO CONTINUE ABOVE TOILET ROOM.. 3-7 3.7 VICINITY MAP (Suite #2110) SCALE: N I General Notes 1. Western States Fire Protection to add new pendent/upright heads new and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary Class II Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and aualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA. as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not desinned for free7inn conditions 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. VL_ - - -;l EXISTING PIPE -»� NEW PIPE T7 MAIN LOCATION FINISHED CEILING HEIGHT 1 -1a AFF. '1 Y.• 0 RISER ROOM A DETAIL HYDRAULIC REFERENCE ONLY NOT TO SCALE SOFFIT ®FINISHED CEILING HEIGHT 13101H'AFF. Y E ENTRY SOFFIT I,yrJ FINISHED CEILING HEIGHT V 10'-0'0.30. 0 E CENTERLINE OF MANUAL ROLL4IP GRILLE, PAM RETURNS SOFFIT fWISMEU CEILWOHEIGHT�B 1Y-f01N'AFF. NOTE WIGHT FUTURE'D' TO BE CENTERED BETWEEN GLAZING CHANNEL AND AJ.U010 1 PANEL NOTE:WNDERSIDE OF CORRUGATED KETAL DECK IS 13.1' AF.F. B 20'-13AF.F. STEEL SEAMS SPAN FRONT TO BACK AND SIDE TO SIDE LOWEST CLEAR HEIGHT TO STRUCTURE IS ITW A.F.F. THERE IS NO SPRAY ON FIREPROOFING OTHER THAN ON COLLINS ATTACHED TO X-BRACIN0. FYE Remote Area: Retail # 2110 CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY cLJnss_ORD HAZARD II MAX. COVERAGE per HEAD 130 FN DENSITY .20 GPM / Ft'tor 959.23 Ft' SPRINKLER Reliable Model G4A/ F1 FR ORIFICE 1/2M. K. 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 PSI FLOW 10900 GPM AT BASF (W RISER, SYSTEM RE3I IIRF0' 303.29_ GPM ® _64.53 PSI At time of Design REMOTE AREA REDUCTION - 37% 945 SQ/FT Ordinary Group II.0.20gpm/ft2 for 959.23ft2 5'-0 FLEX HEADS TO BE USED SALES AREA FINISHED CEILING HEIGHT 17-PAFF. • 5'-0 FLEX HEADS TO BE USED e/ I FINISHED CEIL WUIISI0HT 1r-1PAF0. B 2 TYPICAL FLEXABLE SPRINKLER CONNECTION:. FLEXHEAD MOUNTING BRACKET PIPE NIPPLE FkV) SPRINKLER BRANCHLIKE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS REDUCING FITTING SUSPENDED T -BAR GRID SPRINKLER HEAD CEILING TILE FLEXHEAD DETAIL NOT TO SCALE FIG. 909 SWIVEL SWAY BRACE FITTING 319' KWIK BOLT (21/4' EMBED LENGTH) FIG. 1000 "FAST CLAMP" SWAY BRACE ATTACHMENT O LATERAL LINE RESTRAINTS NON -THREADED BRACE PIPE *NV SYMBOL LEGEND 2 -WAY EARTHQUAKE BRACE 4 -WAY EARTHQUAKE BRACE REVISIONS DESCRIPTION SYM. SIN QTY. FYE - TI 1/8" =1-0 Sprinkler Legend 3 5 7 9 11 APPROVAL: City of Tukwila SPRAY ORIF. FIN. TEMP. 5.6 Pendent Pendent HYDRAULIC REFERENCE POINT HANGER SYMBOL R3625 5.6 Upright Brass Brass 155°F 155°F MFR./MODEL FIG. 4A PIPE CLAMP FOR SWAY BRACE 319' KWIK BOLT (2 ye EMBED LENGTH) FIG.909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT LATERAL BRANCHLINE RESTRAINT 40 ugO NON -THREADED BRACE PIPE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE Hanger No. 07C HILTI Kwik Bolt III / HILTI Kwik Sok II Rod Coupling Cut Rod Lath Rounded to Nearest Inch Q All Thread Rod CL Swivel Ring Concrete Construction Bottom of Concrete to Center Line of Pipe Note on Plan Note on Plan: Hanger Number and'A Dimension HANGER DETAIL NOT TO SCALE VICINITY MAP DETAIL O E3-5;-) ?-7 Western States Fire NOT TO Brass 155°F REL F1 FR SSU Total = 44 CONT. NO.: K$0415 DRAWN BY: CHRIS ISAAC SPRK. ON SHEET: SEE LEGEND SPRK. ON JOB: BRANCHLINE RESTRAINT DATE: 07/21/08 Protection Company 7102 180th AVE NE, STE A-105 - REDMOND, WA - 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE/AUSTIN/DALLAS/ DECATUR I DENVER/ DULUTH I HOUSTON/KANSAS CITY LAS VEGAS /MINNEAPOLIS / PHOENIX/ PORTLAND /RAPID CITY/ ST. PAUL / SALT LAKE CITY/ SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 FYE 2110 Southcenter Pkwy Tukwila,WA 98188 FYE - TI W >- 0 O CHRIS ISAAC 2 0 v c OT L 31) 0 CUMMINGS CONSTRUCTION CONTRACTOR. SHEET FP -1 OF 1 V , rst u C), v5 • cD x a L.) 0 a) it) ; Cr) (NI CO j • ! C:) (N.1 Cr) rN1 cp LL uJ -C! I LL I 6) < LL • - CO < 1. LLJ 1— UJ • 0 CL : LLI c a) u A: •+, O 1 tr) 4-, • to cm • 3 -1 ci 7 X ,1I FILE COPY FIRE TUK ; I it 11 SHEET INDEX i I ERAL NOTES SYMBOLS LEGEND EET SHEET TITLE FA -01 SYSTEv VATIO FA -02 TYPAL DETAILS -- WRI\G A\3 IVOU\TI\G FA -03 • Fl ALAV SYSTEM FLOC) PLA\ FA -04 11:11' I 11, CALCULATIO \S GE\ EAL), ISE, SITE PLA\ I LI! ......4...astotommt,f,Ha I!! ! I I 0 I; • vo, ji vo , omrneno ,i . ,1„, O Az NOT ' in Red1.1,, O Per T6 AttachedLeter , ;- ;';;;I nese plans have be reviewed. by The Ttii<wila Fire Prevention Bureau tolf.!.4informanc with current city: .-• standards. l-kocar:1.-.Ar4 s eLhiect to errors and I ', II omissions whr,t, c,..i i,li, ,luthorizeiolationS ofadopted standaws and (c.) -J iv.:1 s. T'il responsibititY for the:I dequEl\cy 01; d.: -.,;;.;:i ;•-.4 6tally With the de' signer. !; i Addition5, .:=Giciioos olrivisions ts'Isthese drawings atter ::. this date wOi void t hie Lill' Ptancend will require a is q resubmittal of re vised•'„,kit- iings fdrSubseqUent approval ..; . , Final acceptance it st4 t to field test and inspection bV _ i he Tukwila Fire Prev-4)n Bureap. .n 'i'• I sl Date: 51e) -.S) OD . • iRACUritiP U045'.10,484,,o-.) (smnrs [ • ringS ; - s q01 S114 0/q2pu ritovv-gzg :EA° iese9k; INVd30 381:11hAm1n 4 NO ACF -- A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. rukwtLA FIRE DEPARTMEN1, Please call: 575-4407 and give this job No. o -F )4- and exact address for shut. lown or restoration approval: WIRE DESIGNATION SCHEDULE WIRE SCHEDULE .AND CONDUIT FILL CHART SHIELDE WIRE TO BE:GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH. EACH DEVICE WRAPPED WITH .TAPE AND TAPED AT END ".:•„!.. • .1 ;.'••• • . „ FOR SIEMENS SYST DO NOT INSTALL ADDRESS DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DE DEVICE 01-1-02 WOULD BE 2. DETECTOR AND AUDIBLE CI 3. AUDIBLE/VISUAL CIRCUIT WI BRANCHING IS PERMISSIB 4. INSTALLATION SHALL BE IN ELECTRIC CODE, NFPA 72, 5. INSTALLATION MATERIALS (I STANDARD BOXES, FIBER 0' ARE NOT SUPPLIED BY SIE 6. DETECTORS SHALL NOT BE; AIR STREAM OF AIR SUPPL: 7. WIRING SHALL BE PER PLA TYPE, QUANTITY AND COLO AND UNIQUELY MARKED FO 8. 9. 10. INSTALLING CONTRACTOR S DRAWINGS FOR "AS BUILT" FOR ADDITIONAL INSTALLAT SHEETS AND/OR INSTALLAT THE 120vac POWER ELECTR1 MUST COMPLY WITH ARTICL SPECIFICALLY SECTION 1-51 SOURCES. 120vac POWER 5 DIRECT SUPERVISION OF FIf 11. ALL HORN/STROBE AND S OF 80" A.F.F. OR 6" BELO 12. ALL MANUAL PULL STATIO ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND !O.! I II: • ' I • BLE INITIATING : DEVICES UNTIL PREPROGRAMMED WITH I ICE Sy, BOL DENOTE DEVICE CIRCUIT/ADDRESS THEf10ND DEVICE ON . ADDRESSABLE LOOP 1. UIT 1NG CAL: • LARITY SHALL BE OBSERVED. UPERVISED. NO PARALLEL CONFORMANCE WITH THE NATIONAL DE(S), AND/OR AUTHORITY HAVING JURISDICTION. :6& 1UIT, WIRE, FITTINGS, HANGERS, ICS I04[BLE, FITTINGS, AND ASSOCIATED EQUIPIVENT) SC, 1BERUS DIVISION. ON -t, ,; IN DIRECT • UTLEHS. PER NFPA 72 2-3.5.1 ! yviiik i ,ESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, CODE CONDUCTORS SHALL BE PERMANENTLY, iUTUF IDENTIFICATION. 'ALL R URPO N INlS .;1 N AL 725I ALL AL R OP S HA Ecyi 14. ALL 120VAC CIRCUITS ARE1LRQMDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. iitji 15. PER NFPA 72 SECTION 5— .1.3DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEANUP OrMLL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED: BYiJaHE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING C9NSTRUCTION. DETECTORS THAT HAVE BEA INSTALLED PRIOR TO FINAL CLEAN—UP BY ALL TRADES SHALL BE CLEANE OR REPLACED IN ACCORDANCE WITH NFPA 72 ,URN ONE SET OF ACCURATELY MARKED 4jUCTIONS, REFER TO CATALOG CUT IUCTIONS. 3K SUPPLYING FIRE ALARM SYSTEM PANELS D 760 OF NFPA 70, N.E.C. AND NFPA 72, REFERENCE TO DEDICATED BRANCH POWER T BE APPLIED TO FIRE ALARM PANEL WITHOUT TECHNICIAN. • . VICES SHALL BE MOUNTED AT A HEIGHT 'ED CEILING, WHICHEVER IS LESS. BE MOUNTED AT 48" A.F.F. TO THE WILL BE ON THE RECORD DRAWINGS SET. CHAPTER 7. is 16. WIRING SHALL RUN CONTIN 0USOM FACP TO FIRST DEVICE ON A CIRCUIT • AND THEN FROM DEVICE ij DEV WITHOUT S,PLICING IN PULL BOXES OR OTHER BACK BOXES OF 0FEREil CIRCUITS. • 17. HALL sWIRING SHALL BE MET ED, s'.,;RIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BE EEN1INDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. ALLCABLES SHALL BE MA ED 1 INDICATED, ON, EIRE: ALAR IV .RISER WITH A PERMANENT LABEL AT AL' DEVI(0., , JUNCTION BOXES AND :FACP.1 19. THE :ELECTRICAL CONTRAC R SHA L CLEAN: ALL DIRT AND DEBRIS FROM THE OUTSIDE 'AND INSIDE OF T FIRE )8,LARM I316‘cl BOXES AND JUNCTION BOXES • AFTER COMPLETION OF TH R 'IN;'STALLATION. 20 DETECTORS MUST BE RAT FORorMPERATUFE IN THE ENVIRONMENT IN s WHICH .1T IS LOCATED. . 21 ALL WIRING BETWEEN FLOG S HAL B• E LOCATED IN CONDUIT. • 22 NEPA 72 2007 6.4.2.2.2 AL sTyh'i O• F CLASS ik CIRCUITS 'USING, PHYSICAL CONDUCTORS (E. IV E-14LIC, OP, TICAL FIBER) SHALL BE INSTALLED SUCH THAT THE UTG0,1" G AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO Et,ROL UNIT,:RESPECTIVELY, ARE ROUTED SEPARATELY. :THE OTG6,1'I'' AND RETURN; (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT B THE SAME CABLE I iMULTI—CONDUCTOR CABLE) L.NC40i VRE, OR RACEWAY: 23. NFPA 72 2007 A:6.4.2.2.2 A G OF 6.42:.2 IS TO PROVIDE ADEQUATE SEPARATION BE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUI JELP ENSURE 'PROTECTION OF THE :CABLES FROM PHYSICAL DA AGE E RECOMMENDED iV,INIMOM :SEPARATION TO PREVENT P sY:S141DAlv AGE IS 305 MIVI, (1: ET) WHERE •THE CABLE IS INSTALLED V I1gAfr AND 1.22 M (4 FT) WHERE THE :CABLE :IS INSTALLED • H l!s! • • f • • QUANTITY 3 2 1 2 2 EX • • Ai; •1 SYMBOL DESCRIPTION ' 11: MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT ;EIRE ALARM x CONTROL PANEL XLS—V SIEMENS PROVIDED 66" A.F.F. TO TOP PROVIDED • 66" A.F.F. i 1cEILING MOUNT) : , , WIRE DESIGNATION FIRE ALARM D: S D—C SIEMENS ,:pEMOTE ANNUNCIATOR TO TOP SYMBOL DESCRIPTION : NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE 1111,1 ! D DATA LINE -ADDRESSABLE LOOP ! TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) SET—MC—W SIEMENS H DOOR : HOLDER POWER - 24VDC TWO : #14 FPL/FPLR RED (JACKET) poIlLvI P . DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) ;POWER EX '! •1111 I ii; S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) . 2S STROBE CIRCUIT - RETURN TWISTED PAIR : W/ SHIELD #12 FPL/FPLR RED (JACKET) .I.UUAL INPUT HTRI—D SIEMENS 4S DEEP VERIFY :INTERFACE MODULE •IN FIELD A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) 1 V•SPEAKER CIRCUIT 7 FEED , TWISTED PAIR #14 FPL/FPLR RED (JACKET) •;;STROBE 2V SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) 4S BOX W/ 1G RING I REMOTE INDICATION LIGHT TWO #18 FPL/PLR RED (JACKET) SIEMENS 4S DEEP VERIFY X Low LEVEL AUDIO TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) m UD : UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) ., UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) ' ' M . DDDR : HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) DETECTOR HFP-11 W/ SIEMENS 4S DEEP CEILING •il'ADDRESSABLE—PHOTO) DB -11 BASE W/ 1G RING B BEAM •: DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) • • ; ! 1. •::: . CONDUIT FILL CHART No. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA 1 ! TWO 600V #12 AWG THHN/THWN .244 O.D. : .0467 ! TWO 600V #14 AWG THHN/THWN TWISTED .210 • 0.D. .0346 i 3 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE 1:156 O.D. .0191 , . CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM : THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AR EA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE 1NCH • 3/4" .21 SQUARE INCH „ 1" : 34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 1.34 SQUARE INCH !;! FIGURES ARE BASED ON 407 CONDUIT FILL AND ARE TAKEN FROM. N.E.C., CHP. 9, TABLE 4. ' SHIELDE WIRE TO BE:GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH. EACH DEVICE WRAPPED WITH .TAPE AND TAPED AT END ".:•„!.. • .1 ;.'••• • . „ FOR SIEMENS SYST DO NOT INSTALL ADDRESS DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DE DEVICE 01-1-02 WOULD BE 2. DETECTOR AND AUDIBLE CI 3. AUDIBLE/VISUAL CIRCUIT WI BRANCHING IS PERMISSIB 4. INSTALLATION SHALL BE IN ELECTRIC CODE, NFPA 72, 5. INSTALLATION MATERIALS (I STANDARD BOXES, FIBER 0' ARE NOT SUPPLIED BY SIE 6. DETECTORS SHALL NOT BE; AIR STREAM OF AIR SUPPL: 7. WIRING SHALL BE PER PLA TYPE, QUANTITY AND COLO AND UNIQUELY MARKED FO 8. 9. 10. INSTALLING CONTRACTOR S DRAWINGS FOR "AS BUILT" FOR ADDITIONAL INSTALLAT SHEETS AND/OR INSTALLAT THE 120vac POWER ELECTR1 MUST COMPLY WITH ARTICL SPECIFICALLY SECTION 1-51 SOURCES. 120vac POWER 5 DIRECT SUPERVISION OF FIf 11. ALL HORN/STROBE AND S OF 80" A.F.F. OR 6" BELO 12. ALL MANUAL PULL STATIO ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND !O.! I II: • ' I • BLE INITIATING : DEVICES UNTIL PREPROGRAMMED WITH I ICE Sy, BOL DENOTE DEVICE CIRCUIT/ADDRESS THEf10ND DEVICE ON . ADDRESSABLE LOOP 1. UIT 1NG CAL: • LARITY SHALL BE OBSERVED. UPERVISED. NO PARALLEL CONFORMANCE WITH THE NATIONAL DE(S), AND/OR AUTHORITY HAVING JURISDICTION. :6& 1UIT, WIRE, FITTINGS, HANGERS, ICS I04[BLE, FITTINGS, AND ASSOCIATED EQUIPIVENT) SC, 1BERUS DIVISION. ON -t, ,; IN DIRECT • UTLEHS. PER NFPA 72 2-3.5.1 ! yviiik i ,ESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, CODE CONDUCTORS SHALL BE PERMANENTLY, iUTUF IDENTIFICATION. 'ALL R URPO N INlS .;1 N AL 725I ALL AL R OP S HA Ecyi 14. ALL 120VAC CIRCUITS ARE1LRQMDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. iitji 15. PER NFPA 72 SECTION 5— .1.3DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEANUP OrMLL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED: BYiJaHE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING C9NSTRUCTION. DETECTORS THAT HAVE BEA INSTALLED PRIOR TO FINAL CLEAN—UP BY ALL TRADES SHALL BE CLEANE OR REPLACED IN ACCORDANCE WITH NFPA 72 ,URN ONE SET OF ACCURATELY MARKED 4jUCTIONS, REFER TO CATALOG CUT IUCTIONS. 3K SUPPLYING FIRE ALARM SYSTEM PANELS D 760 OF NFPA 70, N.E.C. AND NFPA 72, REFERENCE TO DEDICATED BRANCH POWER T BE APPLIED TO FIRE ALARM PANEL WITHOUT TECHNICIAN. • . VICES SHALL BE MOUNTED AT A HEIGHT 'ED CEILING, WHICHEVER IS LESS. BE MOUNTED AT 48" A.F.F. TO THE WILL BE ON THE RECORD DRAWINGS SET. CHAPTER 7. is 16. WIRING SHALL RUN CONTIN 0USOM FACP TO FIRST DEVICE ON A CIRCUIT • AND THEN FROM DEVICE ij DEV WITHOUT S,PLICING IN PULL BOXES OR OTHER BACK BOXES OF 0FEREil CIRCUITS. • 17. HALL sWIRING SHALL BE MET ED, s'.,;RIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BE EEN1INDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. ALLCABLES SHALL BE MA ED 1 INDICATED, ON, EIRE: ALAR IV .RISER WITH A PERMANENT LABEL AT AL' DEVI(0., , JUNCTION BOXES AND :FACP.1 19. THE :ELECTRICAL CONTRAC R SHA L CLEAN: ALL DIRT AND DEBRIS FROM THE OUTSIDE 'AND INSIDE OF T FIRE )8,LARM I316‘cl BOXES AND JUNCTION BOXES • AFTER COMPLETION OF TH R 'IN;'STALLATION. 20 DETECTORS MUST BE RAT FORorMPERATUFE IN THE ENVIRONMENT IN s WHICH .1T IS LOCATED. . 21 ALL WIRING BETWEEN FLOG S HAL B• E LOCATED IN CONDUIT. • 22 NEPA 72 2007 6.4.2.2.2 AL sTyh'i O• F CLASS ik CIRCUITS 'USING, PHYSICAL CONDUCTORS (E. IV E-14LIC, OP, TICAL FIBER) SHALL BE INSTALLED SUCH THAT THE UTG0,1" G AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO Et,ROL UNIT,:RESPECTIVELY, ARE ROUTED SEPARATELY. :THE OTG6,1'I'' AND RETURN; (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT B THE SAME CABLE I iMULTI—CONDUCTOR CABLE) L.NC40i VRE, OR RACEWAY: 23. NFPA 72 2007 A:6.4.2.2.2 A G OF 6.42:.2 IS TO PROVIDE ADEQUATE SEPARATION BE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUI JELP ENSURE 'PROTECTION OF THE :CABLES FROM PHYSICAL DA AGE E RECOMMENDED iV,INIMOM :SEPARATION TO PREVENT P sY:S141DAlv AGE IS 305 MIVI, (1: ET) WHERE •THE CABLE IS INSTALLED V I1gAfr AND 1.22 M (4 FT) WHERE THE :CABLE :IS INSTALLED • H l!s! • • f • • QUANTITY 3 2 1 2 2 EX • • Ai; •1 SYMBOL DESCRIPTION ' 11: MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT ;EIRE ALARM x CONTROL PANEL XLS—V SIEMENS PROVIDED 66" A.F.F. TO TOP PROVIDED • 66" A.F.F. i 1cEILING MOUNT) FRA FIRE ALARM D: S D—C SIEMENS ,:pEMOTE ANNUNCIATOR TO TOP 1111,1 ! ' ! i • IfIRE ALARM .ii.SPEAKER STROBE' H (WALL MOUNT) SET—MC—W SIEMENS SIEMENS PROVIDED 66" A.F.F 80 A.F.F. TO BOTTOM poIlLvI REMOTE BOOSTER PAD -3. . SUPPLY TO TOP FIRE ALARM iliSPEAKER STROBE ' j,I;(CEILING MOUNT) ;POWER EX '! •1111 I ii; 4S DEEP BOX VV/ 1-1/2" EXT. • INTERFACE MODULE HTRI—R SIEMENS 4S DEEP VERIFY I, I WITH RELAY IN FIELD . ' mai' .I.UUAL INPUT HTRI—D SIEMENS 4S DEEP VERIFY :INTERFACE MODULE •IN FIELD 4S BOX W/ 1G RING VII' 4S DEEP VERIFY •;;STROBE Lino ONTROL POINT • HCP SIEMENS IN FIELD 4S BOX W/ 1G RING • •;MODULE sL H.: GO SIEMENS 4S DEEP VERIFY •EIREALARM 1 SPEAKER RCEILI NG MOUNT) SET—CW SIEMENS m !;REMOTE CONVENTIONAL HZM -IZONE FIELD MODULE •IN •i: FIRE ALARM SFT—W SIEMENS I . LINEAR BEAM : PBA -1191 SIEMENS PROVIDED VERIFY ' s:SMOKE DETECTOR • IN FIELD i 80" A.F.F. DETECTOR HFP-11 W/ SIEMENS 4S DEEP CEILING •il'ADDRESSABLE—PHOTO) DB -11 BASE W/ 1G RING i tAl :IDUCT SMOKE AD2—P W/ SIEMENS DUCT HOUSING VERIFY DETECTOR TSM MODULE IN FIELD ..1 • ,. •I EAT DETECTOR oil • ili(ADDRESSABLE) ,11 -IRE ALARM 11SPEAKER STROBE HFPT-11 VV/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING SET—MC—CW SIEMENS 4S DEEP BOX CEILING LLC i 1cEILING MOUNT) VV/ 1— 1 / Z LAI. ' ' ! i • IfIRE ALARM .ii.SPEAKER STROBE' H (WALL MOUNT) SET—MC—W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80 A.F.F. TO BOTTOM .7'1 1311 FIRE ALARM iliSPEAKER STROBE ' j,I;(CEILING MOUNT) SET—HMC—CW SIEMENS • 4S DEEP BOX VV/ 1-1/2" EXT. CEILING . •I . .'-FIRE ALARM iSTROBE I II(CEILING MOUNT) ZR—MC—CW SIEMENS • 4S BOX W/ 1G RING CEILING ;1 •;;STROBE :TIRE ALARM : I!WALL MOUNT) • ZR—MC—W SIEMENS • • 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. H.: GO •EIREALARM 1 SPEAKER RCEILI NG MOUNT) SET—CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING ; •i: FIRE ALARM SFT—W SIEMENS 4S DEEP BOX 80" A.F.F. 1 (WALL MOUNT) W/ 1-1/2" EXT. TO BOTTOM • 'I:FIRE ALARM • , STROBE IWP •r(WEATHERPROOF) I • MI MULTI—VOLTAGE CONTROL RELAY SET—S17—WP SIEMENS MT—SUR—BOX VERIFY 1/2" PIPE IN FIELD MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD I: . MAGNETIC w • :DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD 1 FIRE ALARM FA IJBOXTERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD 1,2 FUNCTION BOX •;4, • IABOVE FINISHED • FLOOR 111- F.B.O. F.B.O. N/A VERIFY IN FIELD N/A • N/A N/A N/A : PURNISHED BY • -'0THERS N/A N/A • N/A N/A NOTAPPLICABLE ' • N/A N/A N/A N/A U. .N. ;UNLESS OTHERWISE - N/A . ' !NOTED • N/A • N/A N/A WEATHERPROOF I)EVICE • N/A N/A N/A N/A i?ssiS BUILT ADD OR CHANGE N/A N/A N/A N/A iI61S BUILT EN 'REMOVE N/A N/A N/A , N/A B UE s• •lAs BUILT •!NOTES TO CAD N/A N/A N/A N/A g it Co.yright 2006 Guardidn! SecUtit S .1. • , • • nd. All IR' hts sery 11 6 1 743 IST AVE. SO., SEATTLE, WASHINGTON RELEASE/REVISIONS GO LL1 DESCRIPTION 1 < 0 OE 1,Ln UJ • . , ‘ALE: 1 /'=1 1==i1 DRAWN. BY:. LANDERSON DESIGNED BY: R.VEZZANI DATE:5/12/08 BACKROUND PLAN PROVIDED BY: NUMBER:XXXXX SHEET", 1 I!I :.! ;;IE: I L r,�(,, NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. I THE DUCT SMOKE DETECTOR] ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. ;;.THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. OPER TIN TEMPERATU E: +32'F (O' C) TO 100' F (38' C) HUMIDITY: 0-9333% RELATIVE HUMIDITY, NON -CONDENSING DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OUTLET SAMPLING -\. TUBE FRONT VIEW HFP-11 SMOKE DETECTOR DB -11 STANDARD SMOKE DETECTOR BASE 'END OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. INLET SAMPLING TUBE NOT USED REMOTE + DEVICE LOOP NOT USED REMOTE DEVICE LOOP 470 OHMS INPU (+ AT LEAST,• SIX DUCT,. WIDTHS FROM BEND 6-10 DUCT EQUIVALENT DIAMETERS DUCT DETECTOR LOCATION - FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (-) > TO NEXT DEVICE -r- REAR VIEW DATA IN (+) > > (-) DATA OUT 1 > (+) DATA OUT J7 TYPICAL SMOKE DETE LEL VIII TOR ISTALATION REQUIREMENT FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> CE OR DEVICE w TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE MUSIC CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) COMBINE ALL SFI1 HARD LID --\. RELEASE/REVISIONS DESCRIPTION FROM XLS CONTROL ; FYANEL ❑R,I, PREVI❑US ADDRESSA13UE DEVICE END OF LINE DEVICE!( ,6K 1/4;W SUPERVISED8 WITCH TO NEXT ADDRESSABLE DEVICE f(+) STOP IF LAST DEVICE (-) FROM XLS CONTROL PANEL OR i(+) PREVI❑US ADDRESSABLE DEVICE (-) HTRI—D FROM REMOTE POWER SUPPLY ('S' CABLE) T❑4NEXT DEVICE OR ENP OF LINE HARD LID CEILING SPEAKER SUPPORT TTL=E BRIDGE SHOP DRAWINGS GROUND a) ,✓ V 0 0 x N ro 0 _' 0 to rstN 0 ' w 0 o N N o u 3 < E co i W H z W W O z t cn -o Cj a, tri END OF LINE DEVICE (3.6K 1/4W) SUPERVISED !� RELAY CONTACTS SWITCH (4.04 @ 125VAC) GROUND (4.OA @ 30VDC) LU D 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSI❑N CO •0 END d LINE i 3,6K 1/ UPE TWIT FROM FACP (V❑ICE CIRCUIT) ("V' CABLE) NEXT D:!'DICE OR E1t'D. OF LINE CEILING MOUNTED SPEAKER/STROBE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE • (BACKGOUND MUSIC SHUTDOWN) NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE NOTE 11 VOLTAGE MAX, - CURRENT MAX, - CONT, RES, MAX, - MAX, CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN, LINE SIZE - PREVI❑US ADDRaSSABL DEVICE la i JUNCTION BOX ----\ MOUNTED ON \\ CEILING, FLEX 27 VDC 3.5 r1A DURING POLLING 10 OHMS' 200 FT. (18 , AWG) 0,02uF 0,04uF 14 AWG 18 AWG 0 CND N AC • //40 O TO NEXT NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD. CLOSED.' AND/OR OPEN FOR AT LEAST .25. SEC, TO GUARANTEE DETECTION. SPEAKER STROBE OR STROBE ONLY TO NEXT ADDRE SABLE DEVICE 4S; DEEP BOX W/.1-1/2" EXTENSION RING (SPEAKER 'STROBE) 4S BOX (STROBE ONLY) / JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT CADDY BAR z Z 0 00 __I co e� Q W 0 C� CD:12 z II U- <D CC o LL CO --* 0.R 1- 0 0 S a 0 0 a 123456 INPUT INPUT 'TROUBLE NAC1' NAC2 NAC3 NAC4 AUX _ 1+1- 1'2+2- 2 NC C NO '+ - + - + - + - + - .a m IS -[1(1)11-b1 -9-0 0 0 Q Q 24K. • n 80" A.F.F. SMOKE DETECTOR— SMOKE ETECT❑R— SUSPENDED ILLUMINATED SMOKE DETECTOR MOUNTING SCALE:NONE TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE DO \QT INSTALL ADDRESSABLE \IT AT DEVICES-JI\TIL DREP OGRAMVED W T DEVICES ADDRESS. SCALE:' 1 /8"=1 ' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/12/08 BACKROU,ND PLAN PROVIDED BY: \OB NUMBER:54511 l SHEET'. �. Copyright: .2006 by Guardian Security: Systems, Inc. All Rights !!: , t,'•• .!I 11 I, • ; 12'-O" AFF 10' -0" AFF 10 - 0" AFF E <:[ 0 N 7Q11.ET rTh_f , L 15 - ••••"-F!TC.; A . . D ; CD CD- - :1'4;32- Zi TW:_'• 2- fr'i - iv/ 7.2 115_ 31_. [ A.!•71 D ,th CD- A!;CA 2S,2V _c DI 21 14.4 i", ....... 3he:‘4,49 ----- ----- - 4.1 L 2'› ,•>4("Iz5 2:>: NORTH FYE WESTFI SCALE 104 11 C\2 L. L. IL 11 ' : t. : : • I- ' • , . - '72 1 4 _ - .. 1 _______ 1 __I___ , I CASH WP: AP 7 .._ f„ _ _ ___, , ( Li .47. •1 \ . I t , • SALE'S AR:- __,..• A t .1 2S,2V DT ,4, z. z 0 3 ! I I •i_ I _________ -•-• 1 II • ! '''‘. --- -.. : ....• 15 C ;_71 ! • '."'Ir «.: -I .1. ! I . ! 2 2: ; 1 ' ::" 71 z,v6:2&5E4..--!.• • , : .„. D Tr:, 6 R • : }.3 11 _ FEAT 72 I H- z ' L , . --I OP "";:: r.""•.../•..-44 c.,.-4.;..1._ T., 4,,v, 7 : - ' . , ••k:;"" ;• , • :1 ! ! . 1111 1 HCENTER MALL • •i1' I. • :4 • r CI; • , • • 'LAG NO ES: LI> FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE, FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS.(SEE SIEMENS INSTALLATION SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR. SIEMENS HTRI-D ADDRESSABLE INPUT WITH HOOD VENILLATOR FIRE SUPPRESION SYSTEM, FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL, FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NO NS ALL ADP -ESSAF3LE INOT DEVICESUNTIL PREPROGRAMMED WO DEVICES ADDRESS. AT Copyright 2006 by Guardian Security; Systems, Inc. All Rights Lo .0 (.4 .0 c." j LLJ • RELEASE/REVISIONS cO LIJ z • DESCRIPTION • uJ1• ; • 0 . • • z <1< 4-74-3,r,r7;.4, Lij I (c.CALE: 1/8"=1' DRAWN.. BY: LANDERSON DESIGNED BY:. R.VEZZANI DATE:5/12/08 BACKROUND PLAN PROVIDED BY: .‘JOB NUMBER:54511 .1 SHEET. FA -0 . 11i.! .!, i !' _!' • 7 ..! : A 114 •• 4 SYSTEM CA ULATIONS FYE FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations Current Ld Standby: Alarm: Current Load: Standby: Device Ty ie HFP-11 Amps 0.0022 0.0635 0.009600 Total 0.0022 . 0.0635 0.0096 Amps 0.0023 Total Device Type Total Total 0.001600 0.0035 0.0731 rrent Load: 0.0731 For 24 Hours = Amp -hours Main System Board SET -MC @15CD SET -MC @30CD SET -MC ©75CD SET -MC @110CD SETHMC-C@115CD.' SET-HMC-C@135CD SET HMC-C@185CD ZR -MC @15CD ZR -MC @30CD HCP For 5 Minutes= Amp -hours 25% Derating= Amp -hours Standby Current Load: Alarm Current Load: For 24 Hours = 0.956 Amps For 5 Minutes= Amp -hours 25% Derating= 0.03011E1=1l 0.064 : NI� 0.098 11 1111111111M111111111 x;11®lf 0.128 MI MI 1®I1 Amp -hours t Imo{NMI at 11111 IRII 0.636 Amp -hours Amp -hours Bettery P -!r to be Used: 12VDC Amp -hours Amp -hours ( . PROJECT Battery Pair to be Used: 12VDC Amp -hours BATTERY SIZE' .G CALCULATON Notification Appliance WESTFIELD SOUTHCENTER MALL ircuit Detail 1 � Panel: Date: May 22, 2008 CIRCUIT: QTY 1 1 FYE WESTFIELD SOUTHCENTER MALL SCALE 1132".1' Device Type SET -MC @15CD SET -MC @30CD 0 SET -MC @75CD Alarm Current Alarm Total Wire Size ;Length Voltage at EOL Circuit Total 0 SET -MC @110CD 2 SET-HMC-C@115CD 0 SET-HMC-C@177CD 0 SET -HMC @135CD 0 SET -HMC @185CD 2 Z-MC@15CD Z-MC@30CD Total Wire Resistance (R ) (WL*2)*(R/ft) Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E ) (E= I * R) 0.86 0.93 0.80 19.60 0 SET-MC-CW@110CD DEVICES= PROJECT: Panel: Date: CIRCUIT: QTY 4 0 TOTAL m A= 19.6049364 Notification Appliance Circuit Detail WESTFIELD SOUTHCENTER MALL FYE May 20, 2008 Wire Resistance 2;58: CURRENT TOTAL= 7.2 CO0 JCO <0) 2 2z WO W ZZ >- CC Uczn Q CC W CO SPEAKER CIRCUIT Device Type 70.7V1/8 Alarm Current Alarm Total Wire Size ength Voltage at EOL Circuit Total Total Wire Resistance (R ) 2S,2V S,2V 2S,2V 2S,2V 2S,2V ( WL * 2 )* (R/ft) Total Device Load, Amps (I) 0.01 (Total Cct Load) Voltage Drop (E ) EOL Voltage (20.4 - E) 115 C 115 C 15 15 30 C 15 DEVICES= 0'. TOTAL m A= 20.37900912 SCALE:: 1 DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08. BACKROUND PLAN PROVIDED,':BY: ,J.OB NUMBER:5451 1 RISER DIAGRAM VOLTAGE DRO ALCULATION Copyri•ht 2006 b Guardian Securit S stems, Inc. All R. hts