HomeMy WebLinkAboutPP - 2836 SOUTHCENTER MALL - CLAIRES - PERMITS AND PLANS2836 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-253 08-S-292 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Claires 2836 Southcenter Mall Permit No.: 08-S-292 Date: June 10, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 % inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • These conditions apply to any sprinkler piping exposed as necessary to accomplish the permitted scope of work. All references are NFPA 13, 2007 Edition. THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT DUCT DETECTOR L❑CATION COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING ]?O:,NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR I - PREVIOUS ADDRESSABLE DEVIC OUTLET SAMPLING TUBE INLET SAMPLING TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED d REMOTE + 0. DEVICE LOOP -4-- 0 NOT USED 0 REMOTE DEVICE LOOP FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> SCALE:NONE GROUND -12) HTRI-R NOTE: :. FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL v LABEL SCALE ' (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE DEVICE NOTE 1: VOLTAGE MAX.— CURRENT MAX,— CONT. RES, MAX,— MAX. CABLE LENGTH— C (LINE TO LINE) C (LINE TO SHIELD— MAX. LINE SIZE MIN. LINE SIZE— MUSIC COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING• TO NEXT ADDRESSABLE DEVICE: f(+) STOP IF LAST DEVICE i (-) FROM XLS CONTROL PANEL ❑R:,f(+) PREVIOUS ADDRESSABLE DEVICE H RELAY CONTACTS (4.0A @ 125VAC) (4.OA @ 30VDC) 27 VDC 3.5 PIA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0,02uF 0,04uF 14 AWG 18 AWG NOTE 2: ALL SUPERVISED.SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC, TO GUARANTEE DETECTION, s00am 123456 SUPERVISED 1' SWITCH' i GROUND: HTRI-D NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL 0 GND N AC INPUT INPUT .TROUBLE',NAC1 NAC2 :NAC3 NAC4 AUX 1+1- 1 2+2- 2'NC- C NO:+ -'+ - +' + + - ' TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE 470 OHMS �YV EOL TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL FROM REMOTE POWER SUPPLY ('S' CABLE) END i 0 LINE, EVICE FROM FACP 3.6K }1 14W) (VOICE CIRCUIT), ('V' CABLE) SUPE ISED SWITCH f - SCALE NONE (+) (-) STROBE (+) (-) STROBE SPEAKER (+) (-) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE 80 A.F.Fi 4S DEEP BOX W/ 1-1 /2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL. MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE=NONE EXT DEVICE OR P IF LAST DEVICE 1,NEXT VICE OR A OF LINE :NEXT ✓ICE OR OF LINE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION._ OPERtIIN TEMPERAIU E: +32' F 0— C) TO 100' F 38' C) HUMIDITY: 9 % RELATIVE HUMIDITY, NON—CONDENSING HFP-11 SMOKE DETECTOR —* FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (-) DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL DB -11 STANDARD SMOKE DETECTOR BASE TO NEXT DEVICE* > ( ) DATA OUT} > (+) DATA OUT LABEL SCALE CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID HARD LID CEILING ----SPEAKER SUPPORT T ---- BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE=NONE JUNCTION BOX —, MOUNTED ON CEILINGI FLEX {I - JUNCTION BOX =MOUNTED AGAINST ':`CEILING SUPPORT 4 N 000 O O I TO NEXT DEVIC 0 0 SMOKE DETECTOR SMOKE DETECTOR MOUNTING SUSPENDED ILLUMINATED:LEIL DO \IOT D \STALL ADDESSAB_.� MIT DEVICES. UNT FREDRO:GRAMMED WI DEVICES ADDRESS. Copyright 2006 by GDardian.. Security Systems, Inc. All Rights Re„Ser, -p1)- __ 00 00 0, O CDZ 0 `) IAA g Ca W J F= F— LLLJ q 00 O Ea 60 W Q Cn .5h 0 0' -11 oo 0' (V 0 N x LL_ RELEASE/REVISIONS m w CY z DESCRIPTION SHOP DRAWINGS w Q co 0 rn 0 z OD co J y - J CO cc O I- 0 zz W Uw = Q C) M, op CV D I (CALE: 1/8"=1 DRAWN BY: LANDERSON DESIGNED BY:. R.VEZZANI DATE: 5/19/08:. BACKROUND PLAN :PROVIDED BY: %OB NUMBER:54524 I SHEET- 340 4}-D Co-�1 01- 0 01-0 \• IZ-I AFE il` I 11 CEi L !D-0 AFF 1 0 . SEISMIC SEP /� C. Et L 12/-1//AFF. f ft - 20-Gt 1301D REFLECTED CEI LIN& PLAM SPRINKLER HEAD LEGEND:. SYMBOL S/N ORIFICE NPT K•FACT. ASH FINISH TEMP. QUAN. RELIABLE MOD G4A CONCEALED SSP W 1/2' 1/2'. 5.6 BRASS WHT 165 I I RELIABLE MOD G4A CONCEALED SSP ® 1/2' 1/2' 5.6 BRASS BLACK 165 4 RELIABLE MOD FIFR REC SSP . . 00 1/2' 1/2' 5.6 WHT . WHT 155 a APPROVALS BY: . TOTAL SPRINKLERS = THIS SHEET ( 7 0 TYPICAL ARMOVER TO NEW SPRINKLER HEAD FILE COPY THICIQEB6 CF CCICRETE PARED &iv X2414' KiMC On . ". MY cut WAIR ME PLM PDR Int91W RNaFIATAi /ARQ$JE Cr1111 #13 HANGER ASSEMBLY (TYTPICAL HANGER U.O.N.) [X'—X•] —DENOTES HANGER LENGTH Without Comments As Noted In Red Par The Attached Letter !nese plans have.been reviewed by The Tukwila Fire Prevention Bureau.for conformance with current city standards. Acceptance is subject to errors and g omissions which do not authorize violations of adopted stalwarcis and ordinances. The responsibility for the adequacy df design rests totally with the designer. Additions, deletions or' evisions.'o these; drawings atter this date will void thk3 acceptance rAnd will require e resubmittal of revised drawings for sub3equent approval, Final acceptance is subject to fiold•test and inspecti The Tukwila Fire Prevention Bureaau: • Date: ('10 — o 3y: . %II FIG. 65 BEAM CLAMP TUKWILA FIRE DEPARTMEN'L Please call: 575-4407 and give this job and exact address for shut. 'town or restoration approval: FIG. 69 RETAINING STRAP JA �.\ LOCK �•�EW A -A • NUT REQ D PIG. 100 • ALL THREAD ROD FIG. 200 ADJUSTABLE RING HANGER 13OTTOM !BEAM CLAMP, ROD, AND RING #02 HANGER DETAIL N.T.S.. LINE RESTRAINT DETAIL NOTE: 1) SPACE WITI.1 IN 6" OP A HANGER EVERY 42'-0" 2) BRACING PER NEPA-13(2001 ed.) SECTIONS 93588, TABLE ' 3. S.S(a) AND 93. -RE 'TAINT OP BRANCH LINES GENER NOTES' 1. RETAIL AREAS ARE DESIGNED IN ACCORDANCE WITH THE REQUIREMENTS OF N.F. P.A. 13-2007 ORDINARY HAZARD GROUP 2 MAX SPACING 130 SQ. FT. 2: COSCO POINT OF CONNECTION I5 AT EXIST BUILDING SHELL SYSTEM OUTLETS 1 1/2" GOL ON 4" FLOOR MAIN AS SHOWN ON THESE PLANS. 3. ALL PAINTING OF FIRE SPRINKLER PIPING (IF REQ) TO BE DONE BY OTHERS 4. ALL WIRING BY OTHER. 5. ALL MATERIAL I5 NEW U.L. LISTED AND MEETS THE REQUIREMENTS OF THE TUKWILA FIRE DEPT. G. OWNER i5 RESPONSIBLE TO ASSURE THAT STRUCTURE AS ITIS SHOWN ON CONTRACT DRAWINGS CAN ADEQUATELY SUPPORT ALL FIRE SPRINKLER PIPING LOADS.. NO AUXILLIARY DEVICES OR ATTACHMENTS SHALL BE PROVIDED BY COSCO TO SUPPLIMENT THE STRUCTURE TO ACCOMODATE FIRE SPRINKLER PIPING LOADS. 7. OWNER. 15 RESPONSIBLE TO PROVIDE ADEQUATE HEAT TO MAINTAIN 40 DEG. F. MINIMUM AT ALL TIMES YEAR ROUND. 8. SPRINKLER HEAD LOCATIONS INDICATED ON THESE DRAWINGS ARE NOT INTENDED TO BE "CENTER OF TILE" HEAD PLACEMENT. 9. COSCO ASSUMES NO RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, FOR THE CONDITION, PERFORMANCE OR CURRENT CODE COMPLIANCE OF THE EXISTING SYSTEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY COSCO. 10. OWNER I5 RESPONSIBLE TO ARRANGE FOR THE PERIODIC INSPECTION, TESTING AND MAINTENANCE OF THESE FIRE SPRINKLER SYSTEMS IN ACCORDANCE WITH THE MINIMUM REQUIREMENTS OF N.F.P.A. 25-2002 BY QUALIFIED PERSONNEL COMMENCING AFTER WARRANTY. PERIOD HAS EXPIRED. THE FIRM THAT DESIGNED AND INSTALLED THIS SYSTEM IS BEST QUALIFIED TO PROVIDE THE ONGOING LONG TERM TESTING, MAINTENANCE AND SERVICING OF THIS SYSTEM(S). FIELD NOTES I) THREADED PIPE FROM I " THRU 2" SIZE TO BE SCH. 40 STD. WALL PIPE (IMPORT). 2) GROOVED END PIPE FROM 2 1/2" THRU 8" TO. BE SCH. I 0 (IMPORT). 3) ALL GROOVED COUPLING ARE TO BE "RIGID" TYPE U.N.O. (IMPORT). 4) ALL THREADED FITTINGS ARE 300# CLASS D.I. (IMPORT). FIELD/NOTES EXISTING PIPE NEW. PIPE EXISTING HEAD NEW HEAD GO! -IL. NE1AJ HEAD RFT • • ••••••. ••••••• ••••••• •••®••. COSCO Fire Protection FIRE PROTECTION AND LIFE SAFETY SPECIALISTS WASHINGTON OFFICE 15000 Woodinville -Redmond Rd NE License No: Woodinville, Washington 98072 COSCOFP11ONfv1 call (425) 686-8300 • fax (425) 827-4784 SAN DIEGO • LOS ANGELES • FRESNO • SAN FRANCISCO SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE www.coscofire.com PERMIT ##D08-0112 N'= 9 200�8% ukwila Fire PROJECT: CLAIRES 2836 SOUTHCENTER MALL SPACE #2150 TUKWILA, WA 98188 JIM 405-288-2311 CONTRACT MATH: HARDCASTLE CONSTRUCTION INC. P.O.BOX 617 WASHINGTON, OK 73093 DRAWING 11TLE FIRE SPRINKLER TENANT IMPROVEMENT DATE : 06/06/08 SCALE : 1 /4" = 1' - 0' DRAWN B't : BRIAN SCHULZE �l5KS7956 SHEET NO. '1 OF 1 2836 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-253 08-S-292 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Claires 2836 Southcenter Mall Permit No.: 08-S-292 Date: June 10, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 % inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • These conditions apply to any sprinkler piping exposed as necessary to accomplish the permitted scope of work. All references are NFPA 13, 2007 Edition. THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT DUCT DETECTOR L❑CATION COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING ]?O:,NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR I - PREVIOUS ADDRESSABLE DEVIC OUTLET SAMPLING TUBE INLET SAMPLING TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED d REMOTE + 0. DEVICE LOOP -4-- 0 NOT USED 0 REMOTE DEVICE LOOP FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> SCALE:NONE GROUND -12) HTRI-R NOTE: :. FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL v LABEL SCALE ' (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE DEVICE NOTE 1: VOLTAGE MAX.— CURRENT MAX,— CONT. RES, MAX,— MAX. CABLE LENGTH— C (LINE TO LINE) C (LINE TO SHIELD— MAX. LINE SIZE MIN. LINE SIZE— MUSIC COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING• TO NEXT ADDRESSABLE DEVICE: f(+) STOP IF LAST DEVICE i (-) FROM XLS CONTROL PANEL ❑R:,f(+) PREVIOUS ADDRESSABLE DEVICE H RELAY CONTACTS (4.0A @ 125VAC) (4.OA @ 30VDC) 27 VDC 3.5 PIA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0,02uF 0,04uF 14 AWG 18 AWG NOTE 2: ALL SUPERVISED.SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC, TO GUARANTEE DETECTION, s00am 123456 SUPERVISED 1' SWITCH' i GROUND: HTRI-D NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL 0 GND N AC INPUT INPUT .TROUBLE',NAC1 NAC2 :NAC3 NAC4 AUX 1+1- 1 2+2- 2'NC- C NO:+ -'+ - +' + + - ' TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE 470 OHMS �YV EOL TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL FROM REMOTE POWER SUPPLY ('S' CABLE) END i 0 LINE, EVICE FROM FACP 3.6K }1 14W) (VOICE CIRCUIT), ('V' CABLE) SUPE ISED SWITCH f - SCALE NONE (+) (-) STROBE (+) (-) STROBE SPEAKER (+) (-) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE 80 A.F.Fi 4S DEEP BOX W/ 1-1 /2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL. MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE=NONE EXT DEVICE OR P IF LAST DEVICE 1,NEXT VICE OR A OF LINE :NEXT ✓ICE OR OF LINE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION._ OPERtIIN TEMPERAIU E: +32' F 0— C) TO 100' F 38' C) HUMIDITY: 9 % RELATIVE HUMIDITY, NON—CONDENSING HFP-11 SMOKE DETECTOR —* FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (-) DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL DB -11 STANDARD SMOKE DETECTOR BASE TO NEXT DEVICE* > ( ) DATA OUT} > (+) DATA OUT LABEL SCALE CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID HARD LID CEILING ----SPEAKER SUPPORT T ---- BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE=NONE JUNCTION BOX —, MOUNTED ON CEILINGI FLEX {I - JUNCTION BOX =MOUNTED AGAINST ':`CEILING SUPPORT 4 N 000 O O I TO NEXT DEVIC 0 0 SMOKE DETECTOR SMOKE DETECTOR MOUNTING SUSPENDED ILLUMINATED:LEIL DO \IOT D \STALL ADDESSAB_.� MIT DEVICES. UNT FREDRO:GRAMMED WI DEVICES ADDRESS. Copyright 2006 by GDardian.. Security Systems, Inc. All Rights Re„Ser, -p1)- __ 00 00 0, O CDZ 0 `) IAA g Ca W J F= F— LLLJ q 00 O Ea 60 W Q Cn .5h 0 0' -11 oo 0' (V 0 N x LL_ RELEASE/REVISIONS m w CY z DESCRIPTION SHOP DRAWINGS w Q co 0 rn 0 z OD co J y - J CO cc O I- 0 zz W Uw = Q C) M, op CV D I (CALE: 1/8"=1 DRAWN BY: LANDERSON DESIGNED BY:. R.VEZZANI DATE: 5/19/08:. BACKROUND PLAN :PROVIDED BY: %OB NUMBER:54524 I SHEET- lft H. • z LAG NOTES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATION SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICAL CONTRACTOR, SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLATOR FIRE SUPPRESION SYSTEM. FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL, RELEASE/REVISIONS DESCRIPTION • SHOP DRAWINGS LLJ D co 0 0, 0 z FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO • \0 INS -ALL AppRES$APLE N HAT PREF)RQQRAMMEIQ WIT • DIFVHCES: ,DDRESS. • • • ‘CALE: : Co pYri01,f 200„by , uardian,. Security Systems, Inc. All Rights Reserved DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI :„: DATE:5/19/08 BACKROUND PLAN PROVIDED BY: NUMBER:54524 f SHEET 340 4}-D Co-�1 01- 0 01-0 \• IZ-I AFE il` I 11 CEi L !D-0 AFF 1 0 . SEISMIC SEP /� C. Et L 12/-1//AFF. f ft - 20-Gt 1301D REFLECTED CEI LIN& PLAM SPRINKLER HEAD LEGEND:. SYMBOL S/N ORIFICE NPT K•FACT. ASH FINISH TEMP. QUAN. RELIABLE MOD G4A CONCEALED SSP W 1/2' 1/2'. 5.6 BRASS WHT 165 I I RELIABLE MOD G4A CONCEALED SSP ® 1/2' 1/2' 5.6 BRASS BLACK 165 4 RELIABLE MOD FIFR REC SSP . . 00 1/2' 1/2' 5.6 WHT . WHT 155 a APPROVALS BY: . TOTAL SPRINKLERS = THIS SHEET ( 7 0 TYPICAL ARMOVER TO NEW SPRINKLER HEAD FILE COPY THICIQEB6 CF CCICRETE PARED &iv X2414' KiMC On . ". MY cut WAIR ME PLM PDR Int91W RNaFIATAi /ARQ$JE Cr1111 #13 HANGER ASSEMBLY (TYTPICAL HANGER U.O.N.) [X'—X•] —DENOTES HANGER LENGTH Without Comments As Noted In Red Par The Attached Letter !nese plans have.been reviewed by The Tukwila Fire Prevention Bureau.for conformance with current city standards. Acceptance is subject to errors and g omissions which do not authorize violations of adopted stalwarcis and ordinances. The responsibility for the adequacy df design rests totally with the designer. Additions, deletions or' evisions.'o these; drawings atter this date will void thk3 acceptance rAnd will require e resubmittal of revised drawings for sub3equent approval, Final acceptance is subject to fiold•test and inspecti The Tukwila Fire Prevention Bureaau: • Date: ('10 — o 3y: . %II FIG. 65 BEAM CLAMP TUKWILA FIRE DEPARTMEN'L Please call: 575-4407 and give this job and exact address for shut. 'town or restoration approval: FIG. 69 RETAINING STRAP JA �.\ LOCK �•�EW A -A • NUT REQ D PIG. 100 • ALL THREAD ROD FIG. 200 ADJUSTABLE RING HANGER 13OTTOM !BEAM CLAMP, ROD, AND RING #02 HANGER DETAIL N.T.S.. LINE RESTRAINT DETAIL NOTE: 1) SPACE WITI.1 IN 6" OP A HANGER EVERY 42'-0" 2) BRACING PER NEPA-13(2001 ed.) SECTIONS 93588, TABLE ' 3. S.S(a) AND 93. -RE 'TAINT OP BRANCH LINES GENER NOTES' 1. RETAIL AREAS ARE DESIGNED IN ACCORDANCE WITH THE REQUIREMENTS OF N.F. P.A. 13-2007 ORDINARY HAZARD GROUP 2 MAX SPACING 130 SQ. FT. 2: COSCO POINT OF CONNECTION I5 AT EXIST BUILDING SHELL SYSTEM OUTLETS 1 1/2" GOL ON 4" FLOOR MAIN AS SHOWN ON THESE PLANS. 3. ALL PAINTING OF FIRE SPRINKLER PIPING (IF REQ) TO BE DONE BY OTHERS 4. ALL WIRING BY OTHER. 5. ALL MATERIAL I5 NEW U.L. LISTED AND MEETS THE REQUIREMENTS OF THE TUKWILA FIRE DEPT. G. OWNER i5 RESPONSIBLE TO ASSURE THAT STRUCTURE AS ITIS SHOWN ON CONTRACT DRAWINGS CAN ADEQUATELY SUPPORT ALL FIRE SPRINKLER PIPING LOADS.. NO AUXILLIARY DEVICES OR ATTACHMENTS SHALL BE PROVIDED BY COSCO TO SUPPLIMENT THE STRUCTURE TO ACCOMODATE FIRE SPRINKLER PIPING LOADS. 7. OWNER. 15 RESPONSIBLE TO PROVIDE ADEQUATE HEAT TO MAINTAIN 40 DEG. F. MINIMUM AT ALL TIMES YEAR ROUND. 8. SPRINKLER HEAD LOCATIONS INDICATED ON THESE DRAWINGS ARE NOT INTENDED TO BE "CENTER OF TILE" HEAD PLACEMENT. 9. COSCO ASSUMES NO RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, FOR THE CONDITION, PERFORMANCE OR CURRENT CODE COMPLIANCE OF THE EXISTING SYSTEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY COSCO. 10. OWNER I5 RESPONSIBLE TO ARRANGE FOR THE PERIODIC INSPECTION, TESTING AND MAINTENANCE OF THESE FIRE SPRINKLER SYSTEMS IN ACCORDANCE WITH THE MINIMUM REQUIREMENTS OF N.F.P.A. 25-2002 BY QUALIFIED PERSONNEL COMMENCING AFTER WARRANTY. PERIOD HAS EXPIRED. THE FIRM THAT DESIGNED AND INSTALLED THIS SYSTEM IS BEST QUALIFIED TO PROVIDE THE ONGOING LONG TERM TESTING, MAINTENANCE AND SERVICING OF THIS SYSTEM(S). FIELD NOTES I) THREADED PIPE FROM I " THRU 2" SIZE TO BE SCH. 40 STD. WALL PIPE (IMPORT). 2) GROOVED END PIPE FROM 2 1/2" THRU 8" TO. BE SCH. I 0 (IMPORT). 3) ALL GROOVED COUPLING ARE TO BE "RIGID" TYPE U.N.O. (IMPORT). 4) ALL THREADED FITTINGS ARE 300# CLASS D.I. (IMPORT). FIELD/NOTES EXISTING PIPE NEW. PIPE EXISTING HEAD NEW HEAD GO! -IL. NE1AJ HEAD RFT • • ••••••. ••••••• ••••••• •••®••. COSCO Fire Protection FIRE PROTECTION AND LIFE SAFETY SPECIALISTS WASHINGTON OFFICE 15000 Woodinville -Redmond Rd NE License No: Woodinville, Washington 98072 COSCOFP11ONfv1 call (425) 686-8300 • fax (425) 827-4784 SAN DIEGO • LOS ANGELES • FRESNO • SAN FRANCISCO SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE www.coscofire.com PERMIT ##D08-0112 N'= 9 200�8% ukwila Fire PROJECT: CLAIRES 2836 SOUTHCENTER MALL SPACE #2150 TUKWILA, WA 98188 JIM 405-288-2311 CONTRACT MATH: HARDCASTLE CONSTRUCTION INC. P.O.BOX 617 WASHINGTON, OK 73093 DRAWING 11TLE FIRE SPRINKLER TENANT IMPROVEMENT DATE : 06/06/08 SCALE : 1 /4" = 1' - 0' DRAWN B't : BRIAN SCHULZE �l5KS7956 SHEET NO. '1 OF 1