FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS
Project Name: Claires
2836 Southcenter Mall
Permit No.: 08-S-292
Date: June 10, 2008
Reviewer: Al Metzler
Fire Protection Project Coordinator
(206)575-4407
• Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross
mains, and branch lines 2.5" and larger. Bracing is provided for the last length of
pipe but within 6' of the end of a feed or cross main. Bracing is required unless
all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for
any size pipe, 9.3.5.3.
• Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4
exceptions, 9.3.4.
• Longitudinal sway bracing is a maximum of 80' for mains and cross mains and
within 40 ' of the end of the line, 9.3.5.4.
• Provide lateral and longitudinal bracing for changes in pipe direction per section
9.3.5.11.2 for pipe size 2 % inches and larger.
• Restrain branch lines at the end sprinkler of each line, restrain against vertical
and lateral movement, 9.3.6.3.
• Restraints for branch lines shall be at intervals per table 9.3.6.4 and section
9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6.
• Comply with ASCE 7-02, section 9.6.2.6.2 (e).
• Ceilings used for flex drop attachments shall comply with ASTM C 635 and
ASTM C 636 per section 9.2.1.3.3.2.
• Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a
suspended ceiling, a hanger(s) attached to the structure shall be required to
ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3).
• Provide sprinkler protection beneath all obstructions greater than 4 ft. in width.
• Extend sprinkler protection to all combustible concealed spaces.
• Comply with NFPA 13 obstruction tables.
• Sprinkler heads spaced closer than 6 ft. apart must be baffled.
• These conditions apply to any sprinkler piping exposed as necessary to
accomplish the permitted scope of work.
All references are NFPA 13, 2007 Edition.
THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72.
THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX
DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED.
BEND OR OTHER
ANY DUCK OVER 3' WIDE, SAMPLE TUBE
MUST GO THRU THE DUCT AND BE CAPPED.
TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT
DUCT DETECTOR
L❑CATION
COMBINE ALL SHIELDS AND
ISOLATE FROM GROUNDING
]?O:,NEXT ADDRESSABLE DEVICE
STOP IF LAST DEVICE
FROM XLS CONTROL PANEL OR I -
PREVIOUS ADDRESSABLE DEVIC
OUTLET SAMPLING
TUBE
INLET SAMPLING
TUBE
AT LEAST
SIX DUCT
WIDTHS
FROM BEND
TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR
FRONT VIEW
NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION.
NOT USED d
REMOTE + 0.
DEVICE LOOP -4-- 0
NOT USED 0
REMOTE
DEVICE LOOP
FROM XLS CONTROL PANEL OR (+)>
PREVIOUS ADDRESSABLE DEVICE (-)>
SCALE:NONE
GROUND -12)
HTRI-R
NOTE: :.
FOR ADDITIONAL SPECIFICATIONS
SEE PRODUCT DOCUMENTATION.
TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL
v LABEL SCALE ' (BACKGOUND MUSIC SHUTDOWN)
PREVI❑US ADDRESSABLE
DEVICE
NOTE 1:
VOLTAGE MAX.—
CURRENT MAX,—
CONT. RES, MAX,—
MAX. CABLE LENGTH—
C (LINE TO LINE)
C (LINE TO SHIELD—
MAX. LINE SIZE
MIN. LINE SIZE—
MUSIC
COMBINE ALL SHIELDS AND
ISOLATE FROM GROUNDING•
TO NEXT ADDRESSABLE DEVICE: f(+)
STOP IF LAST DEVICE i (-)
FROM XLS CONTROL PANEL ❑R:,f(+)
PREVIOUS ADDRESSABLE DEVICE H
RELAY CONTACTS
(4.0A @ 125VAC)
(4.OA @ 30VDC)
27 VDC
3.5 PIA DURING POLLING
10 OHMS
200 FT. (18 AWG)
0,02uF
0,04uF
14 AWG
18 AWG
NOTE 2:
ALL SUPERVISED.SWITCHES MUST BE HELD CLOSED
AND/OR OPEN FOR AT LEAST .25 SEC, TO GUARANTEE
DETECTION,
s00am
123456
SUPERVISED 1'
SWITCH' i
GROUND:
HTRI-D
NOTE:
FOR ADDITIONAL SPECIFICATIONS
SEE PRODUCT DOCUMENTATION.
TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL
0
GND N AC
INPUT INPUT .TROUBLE',NAC1 NAC2 :NAC3 NAC4 AUX
1+1- 1 2+2- 2'NC- C NO:+ -'+ - +' + + - '
TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP)
LABEL SCALE
470
OHMS
�YV
EOL
TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL
FROM REMOTE
POWER SUPPLY
('S' CABLE)
END i 0
LINE, EVICE FROM FACP
3.6K }1 14W) (VOICE CIRCUIT),
('V' CABLE)
SUPE ISED
SWITCH
f -
SCALE NONE
(+) (-)
STROBE
(+) (-)
STROBE
SPEAKER
(+) (-)
SPEAKERISTROBE AND STROBE WIRING
LABEL SCALE
80 A.F.Fi
4S DEEP BOX
W/ 1-1 /2"
EXTENSION RING
(SPEAKER STROBE)
4S BOX
(STROBE ONLY)
SPEAKER/STROBE
WALL. MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS
SCALE=NONE
EXT DEVICE OR
P IF LAST DEVICE
1,NEXT
VICE OR
A OF LINE
:NEXT
✓ICE OR
OF LINE
NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION._
OPERtIIN TEMPERAIU E:
+32' F 0— C) TO 100' F 38' C)
HUMIDITY: 9 % RELATIVE HUMIDITY,
NON—CONDENSING
HFP-11 SMOKE
DETECTOR
—* FROM PREVIOUS
ADDRESSABLE DEVICE
OR POWER SOURCE
DATA IN (-)
DATA IN (+) >
DEVICE IS LISTED FOR AIR VOLOCITY
APPLICATIONS OF 300-4000 FT/MIN
WHEN USED IN CONJUNCTION WITH
DUCT HOUSINGS AD -11P OR AD-11XPR
REAR VIEW
HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL
DB -11
STANDARD
SMOKE
DETECTOR
BASE
TO NEXT DEVICE*
> ( ) DATA OUT}
> (+) DATA OUT
LABEL SCALE
CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID)
HARD LID
HARD LID
CEILING ----SPEAKER SUPPORT T ----
BRIDGE
4' SQUARE DEEP BOX
WITH 1-1/2' EXTENSION
CEILING MOUNTED
SPEAKER/STROBE
CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING)
SCALE=NONE
JUNCTION BOX —,
MOUNTED ON
CEILINGI FLEX
{I -
JUNCTION BOX
=MOUNTED AGAINST
':`CEILING SUPPORT
4
N
000
O O I TO NEXT DEVIC
0 0
SMOKE DETECTOR
SMOKE DETECTOR MOUNTING
SUSPENDED
ILLUMINATED:LEIL
DO \IOT D \STALL
ADDESSAB_.� MIT
DEVICES. UNT
FREDRO:GRAMMED WI
DEVICES ADDRESS.
Copyright 2006 by GDardian.. Security Systems, Inc. All Rights Re„Ser,
-p1)-
__
00 00
0,
O
CDZ
0 `)
IAA g
Ca W
J
F=
F—
LLLJ
q 00
O
Ea 60
W
Q
Cn
.5h
0
0'
-11
oo
0'
(V
0
N
x
LL_
RELEASE/REVISIONS
m
w
CY
z
DESCRIPTION
SHOP DRAWINGS
w
Q
co
0
rn
0
z
OD
co
J y -
J CO
cc O
I- 0
zz
W
Uw
= Q
C)
M,
op
CV D
I
(CALE: 1/8"=1
DRAWN BY:
LANDERSON
DESIGNED BY:.
R.VEZZANI
DATE: 5/19/08:.
BACKROUND PLAN :PROVIDED BY:
%OB NUMBER:54524
I SHEET-
340
4}-D Co-�1
01- 0
01-0
\•
IZ-I AFE
il` I 11
CEi L !D-0 AFF
1
0 .
SEISMIC SEP
/�
C. Et L 12/-1//AFF.
f ft -
20-Gt 1301D
REFLECTED
CEI LIN& PLAM
SPRINKLER HEAD LEGEND:.
SYMBOL
S/N
ORIFICE
NPT
K•FACT.
ASH
FINISH
TEMP.
QUAN.
RELIABLE MOD G4A CONCEALED SSP
W
1/2'
1/2'.
5.6
BRASS
WHT
165
I I
RELIABLE MOD G4A CONCEALED SSP
®
1/2'
1/2'
5.6
BRASS
BLACK
165
4
RELIABLE MOD FIFR REC SSP . .
00
1/2'
1/2'
5.6
WHT .
WHT
155
a
APPROVALS BY: .
TOTAL SPRINKLERS =
THIS SHEET
( 7
0 TYPICAL ARMOVER TO NEW SPRINKLER HEAD
FILE COPY
THICIQEB6 CF CCICRETE PARED
&iv X2414' KiMC On . ".
MY
cut WAIR
ME PLM PDR Int91W
RNaFIATAi
/ARQ$JE
Cr1111
#13 HANGER ASSEMBLY
(TYTPICAL HANGER U.O.N.)
[X'—X•] —DENOTES HANGER LENGTH
Without Comments
As Noted In Red
Par The Attached Letter
!nese plans have.been reviewed by The Tukwila Fire
Prevention Bureau.for conformance with current city
standards. Acceptance is subject to errors and
g omissions which do not authorize violations of adopted
stalwarcis and ordinances. The responsibility for the
adequacy df design rests totally with the designer.
Additions, deletions or' evisions.'o these; drawings atter
this date will void thk3 acceptance rAnd will require e
resubmittal of revised drawings for sub3equent approval,
Final acceptance is subject to fiold•test and inspecti
The Tukwila Fire Prevention Bureaau:
•
Date: ('10 — o 3y: . %II
FIG. 65
BEAM CLAMP
TUKWILA FIRE DEPARTMEN'L
Please call: 575-4407
and give this job
and exact address for shut.
'town or restoration approval:
FIG. 69
RETAINING
STRAP
JA
�.\
LOCK
�•�EW A -A
•
NUT REQ D
PIG. 100 •
ALL THREAD ROD
FIG. 200
ADJUSTABLE RING
HANGER
13OTTOM !BEAM CLAMP, ROD, AND RING
#02 HANGER DETAIL
N.T.S..
LINE RESTRAINT DETAIL
NOTE: 1) SPACE WITI.1 IN 6" OP A HANGER EVERY 42'-0"
2) BRACING PER NEPA-13(2001 ed.) SECTIONS 93588,
TABLE ' 3. S.S(a) AND 93. -RE 'TAINT OP BRANCH LINES
GENER NOTES'
1. RETAIL AREAS ARE DESIGNED IN ACCORDANCE WITH THE REQUIREMENTS OF N.F. P.A. 13-2007 ORDINARY HAZARD GROUP 2 MAX SPACING 130 SQ. FT.
2: COSCO POINT OF CONNECTION I5 AT EXIST BUILDING SHELL SYSTEM OUTLETS 1 1/2" GOL ON 4" FLOOR MAIN AS SHOWN ON THESE PLANS.
3. ALL PAINTING OF FIRE SPRINKLER PIPING (IF REQ) TO BE DONE BY OTHERS
4. ALL WIRING BY OTHER.
5. ALL MATERIAL I5 NEW U.L. LISTED AND MEETS THE REQUIREMENTS OF THE TUKWILA FIRE DEPT.
G. OWNER i5 RESPONSIBLE TO ASSURE THAT STRUCTURE AS ITIS SHOWN ON CONTRACT DRAWINGS CAN
ADEQUATELY SUPPORT ALL FIRE SPRINKLER PIPING LOADS.. NO AUXILLIARY DEVICES OR ATTACHMENTS
SHALL BE PROVIDED BY COSCO TO SUPPLIMENT THE STRUCTURE TO ACCOMODATE FIRE SPRINKLER
PIPING LOADS.
7. OWNER. 15 RESPONSIBLE TO PROVIDE ADEQUATE HEAT TO MAINTAIN 40 DEG. F. MINIMUM AT ALL TIMES YEAR ROUND.
8. SPRINKLER HEAD LOCATIONS INDICATED ON THESE DRAWINGS ARE NOT INTENDED TO BE "CENTER OF TILE" HEAD PLACEMENT.
9. COSCO ASSUMES NO RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, FOR THE CONDITION, PERFORMANCE OR
CURRENT CODE COMPLIANCE OF THE EXISTING SYSTEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM ON SITE
EXCEPT FOR WORK PERFORMED DIRECTLY BY COSCO.
10. OWNER I5 RESPONSIBLE TO ARRANGE FOR THE PERIODIC INSPECTION, TESTING AND MAINTENANCE OF THESE FIRE SPRINKLER
SYSTEMS IN ACCORDANCE WITH THE MINIMUM REQUIREMENTS OF N.F.P.A. 25-2002 BY QUALIFIED PERSONNEL COMMENCING
AFTER WARRANTY. PERIOD HAS EXPIRED. THE FIRM THAT DESIGNED AND INSTALLED THIS SYSTEM IS BEST QUALIFIED TO PROVIDE
THE ONGOING LONG TERM TESTING, MAINTENANCE AND SERVICING OF THIS SYSTEM(S).
FIELD NOTES
I) THREADED PIPE FROM I " THRU 2" SIZE TO BE SCH. 40 STD. WALL PIPE (IMPORT).
2) GROOVED END PIPE FROM 2 1/2" THRU 8" TO. BE SCH. I 0 (IMPORT).
3) ALL GROOVED COUPLING ARE TO BE "RIGID" TYPE U.N.O. (IMPORT).
4) ALL THREADED FITTINGS ARE 300# CLASS D.I. (IMPORT).
FIELD/NOTES
EXISTING PIPE
NEW. PIPE
EXISTING HEAD
NEW HEAD GO! -IL.
NE1AJ HEAD RFT
•
•
••••••.
•••••••
•••••••
•••®••.
COSCO
Fire Protection
FIRE PROTECTION AND LIFE SAFETY SPECIALISTS
WASHINGTON OFFICE
15000 Woodinville -Redmond Rd NE License No:
Woodinville, Washington 98072 COSCOFP11ONfv1
call (425) 686-8300 • fax (425) 827-4784
SAN DIEGO • LOS ANGELES • FRESNO • SAN FRANCISCO SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE
www.coscofire.com
PERMIT ##D08-0112
N'= 9 200�8%
ukwila Fire
PROJECT:
CLAIRES
2836 SOUTHCENTER MALL SPACE #2150
TUKWILA, WA 98188 JIM 405-288-2311
CONTRACT MATH:
HARDCASTLE CONSTRUCTION INC.
P.O.BOX 617
WASHINGTON, OK 73093
DRAWING 11TLE
FIRE SPRINKLER TENANT IMPROVEMENT
DATE : 06/06/08
SCALE : 1 /4" = 1' - 0'
DRAWN B't : BRIAN SCHULZE
�l5KS7956
SHEET NO.
'1 OF 1
2836 SOUTHCENTER MALL
ASSOCIATED PERMITS
08-F-253
08-S-292
FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS
Project Name: Claires
2836 Southcenter Mall
Permit No.: 08-S-292
Date: June 10, 2008
Reviewer: Al Metzler
Fire Protection Project Coordinator
(206)575-4407
• Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross
mains, and branch lines 2.5" and larger. Bracing is provided for the last length of
pipe but within 6' of the end of a feed or cross main. Bracing is required unless
all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for
any size pipe, 9.3.5.3.
• Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4
exceptions, 9.3.4.
• Longitudinal sway bracing is a maximum of 80' for mains and cross mains and
within 40 ' of the end of the line, 9.3.5.4.
• Provide lateral and longitudinal bracing for changes in pipe direction per section
9.3.5.11.2 for pipe size 2 % inches and larger.
• Restrain branch lines at the end sprinkler of each line, restrain against vertical
and lateral movement, 9.3.6.3.
• Restraints for branch lines shall be at intervals per table 9.3.6.4 and section
9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6.
• Comply with ASCE 7-02, section 9.6.2.6.2 (e).
• Ceilings used for flex drop attachments shall comply with ASTM C 635 and
ASTM C 636 per section 9.2.1.3.3.2.
• Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a
suspended ceiling, a hanger(s) attached to the structure shall be required to
ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3).
• Provide sprinkler protection beneath all obstructions greater than 4 ft. in width.
• Extend sprinkler protection to all combustible concealed spaces.
• Comply with NFPA 13 obstruction tables.
• Sprinkler heads spaced closer than 6 ft. apart must be baffled.
• These conditions apply to any sprinkler piping exposed as necessary to
accomplish the permitted scope of work.
All references are NFPA 13, 2007 Edition.
THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72.
THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX
DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED.
BEND OR OTHER
ANY DUCK OVER 3' WIDE, SAMPLE TUBE
MUST GO THRU THE DUCT AND BE CAPPED.
TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT
DUCT DETECTOR
L❑CATION
COMBINE ALL SHIELDS AND
ISOLATE FROM GROUNDING
]?O:,NEXT ADDRESSABLE DEVICE
STOP IF LAST DEVICE
FROM XLS CONTROL PANEL OR I -
PREVIOUS ADDRESSABLE DEVIC
OUTLET SAMPLING
TUBE
INLET SAMPLING
TUBE
AT LEAST
SIX DUCT
WIDTHS
FROM BEND
TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR
FRONT VIEW
NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION.
NOT USED d
REMOTE + 0.
DEVICE LOOP -4-- 0
NOT USED 0
REMOTE
DEVICE LOOP
FROM XLS CONTROL PANEL OR (+)>
PREVIOUS ADDRESSABLE DEVICE (-)>
SCALE:NONE
GROUND -12)
HTRI-R
NOTE: :.
FOR ADDITIONAL SPECIFICATIONS
SEE PRODUCT DOCUMENTATION.
TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL
v LABEL SCALE ' (BACKGOUND MUSIC SHUTDOWN)
PREVI❑US ADDRESSABLE
DEVICE
NOTE 1:
VOLTAGE MAX.—
CURRENT MAX,—
CONT. RES, MAX,—
MAX. CABLE LENGTH—
C (LINE TO LINE)
C (LINE TO SHIELD—
MAX. LINE SIZE
MIN. LINE SIZE—
MUSIC
COMBINE ALL SHIELDS AND
ISOLATE FROM GROUNDING•
TO NEXT ADDRESSABLE DEVICE: f(+)
STOP IF LAST DEVICE i (-)
FROM XLS CONTROL PANEL ❑R:,f(+)
PREVIOUS ADDRESSABLE DEVICE H
RELAY CONTACTS
(4.0A @ 125VAC)
(4.OA @ 30VDC)
27 VDC
3.5 PIA DURING POLLING
10 OHMS
200 FT. (18 AWG)
0,02uF
0,04uF
14 AWG
18 AWG
NOTE 2:
ALL SUPERVISED.SWITCHES MUST BE HELD CLOSED
AND/OR OPEN FOR AT LEAST .25 SEC, TO GUARANTEE
DETECTION,
s00am
123456
SUPERVISED 1'
SWITCH' i
GROUND:
HTRI-D
NOTE:
FOR ADDITIONAL SPECIFICATIONS
SEE PRODUCT DOCUMENTATION.
TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL
0
GND N AC
INPUT INPUT .TROUBLE',NAC1 NAC2 :NAC3 NAC4 AUX
1+1- 1 2+2- 2'NC- C NO:+ -'+ - +' + + - '
TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP)
LABEL SCALE
470
OHMS
�YV
EOL
TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL
FROM REMOTE
POWER SUPPLY
('S' CABLE)
END i 0
LINE, EVICE FROM FACP
3.6K }1 14W) (VOICE CIRCUIT),
('V' CABLE)
SUPE ISED
SWITCH
f -
SCALE NONE
(+) (-)
STROBE
(+) (-)
STROBE
SPEAKER
(+) (-)
SPEAKERISTROBE AND STROBE WIRING
LABEL SCALE
80 A.F.Fi
4S DEEP BOX
W/ 1-1 /2"
EXTENSION RING
(SPEAKER STROBE)
4S BOX
(STROBE ONLY)
SPEAKER/STROBE
WALL. MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS
SCALE=NONE
EXT DEVICE OR
P IF LAST DEVICE
1,NEXT
VICE OR
A OF LINE
:NEXT
✓ICE OR
OF LINE
NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION._
OPERtIIN TEMPERAIU E:
+32' F 0— C) TO 100' F 38' C)
HUMIDITY: 9 % RELATIVE HUMIDITY,
NON—CONDENSING
HFP-11 SMOKE
DETECTOR
—* FROM PREVIOUS
ADDRESSABLE DEVICE
OR POWER SOURCE
DATA IN (-)
DATA IN (+) >
DEVICE IS LISTED FOR AIR VOLOCITY
APPLICATIONS OF 300-4000 FT/MIN
WHEN USED IN CONJUNCTION WITH
DUCT HOUSINGS AD -11P OR AD-11XPR
REAR VIEW
HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL
DB -11
STANDARD
SMOKE
DETECTOR
BASE
TO NEXT DEVICE*
> ( ) DATA OUT}
> (+) DATA OUT
LABEL SCALE
CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID)
HARD LID
HARD LID
CEILING ----SPEAKER SUPPORT T ----
BRIDGE
4' SQUARE DEEP BOX
WITH 1-1/2' EXTENSION
CEILING MOUNTED
SPEAKER/STROBE
CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING)
SCALE=NONE
JUNCTION BOX —,
MOUNTED ON
CEILINGI FLEX
{I -
JUNCTION BOX
=MOUNTED AGAINST
':`CEILING SUPPORT
4
N
000
O O I TO NEXT DEVIC
0 0
SMOKE DETECTOR
SMOKE DETECTOR MOUNTING
SUSPENDED
ILLUMINATED:LEIL
DO \IOT D \STALL
ADDESSAB_.� MIT
DEVICES. UNT
FREDRO:GRAMMED WI
DEVICES ADDRESS.
Copyright 2006 by GDardian.. Security Systems, Inc. All Rights Re„Ser,
-p1)-
__
00 00
0,
O
CDZ
0 `)
IAA g
Ca W
J
F=
F—
LLLJ
q 00
O
Ea 60
W
Q
Cn
.5h
0
0'
-11
oo
0'
(V
0
N
x
LL_
RELEASE/REVISIONS
m
w
CY
z
DESCRIPTION
SHOP DRAWINGS
w
Q
co
0
rn
0
z
OD
co
J y -
J CO
cc O
I- 0
zz
W
Uw
= Q
C)
M,
op
CV D
I
(CALE: 1/8"=1
DRAWN BY:
LANDERSON
DESIGNED BY:.
R.VEZZANI
DATE: 5/19/08:.
BACKROUND PLAN :PROVIDED BY:
%OB NUMBER:54524
I SHEET-
lft
H. •
z
LAG NOTES:
FIELD LOCATE RELAY MODULE FOR
BACK GROUND MUSIC INTERFACE.
FIELD LOCATE SIEMENS DUCT
DETECTOR ON RETURN SIDE OF
ALL VAV UNITS,(SEE SIEMENS
INSTALLATION SUBMITTAL FOR
LOCATION GUIDELINES AND FA -02)
DEVICES SUPPLIED BY GSS,
INSTALLED BY MECHANICAL
CONTRACTOR,
WIRED BY ELECTRICAL
CONTRACTOR,
SIEMENS HTRI—D ADDRESSABLE
INPUT WITH HOOD VENILLATOR
FIRE SUPPRESION SYSTEM. FIELD
LOCATE WITHIN 3 FEET OF
CONTRL PANEL,
RELEASE/REVISIONS
DESCRIPTION
•
SHOP DRAWINGS
LLJ
D
co
0
0,
0
z
FIELD LOCATE SIEMENS PAD -3
BOOSTER POWER SUPPLY FOR
STROBE POWER, AC POWER BY EC
FROM DEDICATED, LOCKED OUT
20A, 110 VAC BRANCH CIRCUIT.
DO • \0 INS -ALL
AppRES$APLE N HAT
PREF)RQQRAMMEIQ WIT
• DIFVHCES: ,DDRESS.
• • •
‘CALE:
:
Co pYri01,f 200„by , uardian,. Security Systems, Inc. All Rights Reserved
DRAWN BY:
I.ANDERSON
DESIGNED BY:
R.VEZZANI :„:
DATE:5/19/08
BACKROUND PLAN PROVIDED BY:
NUMBER:54524
f
SHEET
340
4}-D Co-�1
01- 0
01-0
\•
IZ-I AFE
il` I 11
CEi L !D-0 AFF
1
0 .
SEISMIC SEP
/�
C. Et L 12/-1//AFF.
f ft -
20-Gt 1301D
REFLECTED
CEI LIN& PLAM
SPRINKLER HEAD LEGEND:.
SYMBOL
S/N
ORIFICE
NPT
K•FACT.
ASH
FINISH
TEMP.
QUAN.
RELIABLE MOD G4A CONCEALED SSP
W
1/2'
1/2'.
5.6
BRASS
WHT
165
I I
RELIABLE MOD G4A CONCEALED SSP
®
1/2'
1/2'
5.6
BRASS
BLACK
165
4
RELIABLE MOD FIFR REC SSP . .
00
1/2'
1/2'
5.6
WHT .
WHT
155
a
APPROVALS BY: .
TOTAL SPRINKLERS =
THIS SHEET
( 7
0 TYPICAL ARMOVER TO NEW SPRINKLER HEAD
FILE COPY
THICIQEB6 CF CCICRETE PARED
&iv X2414' KiMC On . ".
MY
cut WAIR
ME PLM PDR Int91W
RNaFIATAi
/ARQ$JE
Cr1111
#13 HANGER ASSEMBLY
(TYTPICAL HANGER U.O.N.)
[X'—X•] —DENOTES HANGER LENGTH
Without Comments
As Noted In Red
Par The Attached Letter
!nese plans have.been reviewed by The Tukwila Fire
Prevention Bureau.for conformance with current city
standards. Acceptance is subject to errors and
g omissions which do not authorize violations of adopted
stalwarcis and ordinances. The responsibility for the
adequacy df design rests totally with the designer.
Additions, deletions or' evisions.'o these; drawings atter
this date will void thk3 acceptance rAnd will require e
resubmittal of revised drawings for sub3equent approval,
Final acceptance is subject to fiold•test and inspecti
The Tukwila Fire Prevention Bureaau:
•
Date: ('10 — o 3y: . %II
FIG. 65
BEAM CLAMP
TUKWILA FIRE DEPARTMEN'L
Please call: 575-4407
and give this job
and exact address for shut.
'town or restoration approval:
FIG. 69
RETAINING
STRAP
JA
�.\
LOCK
�•�EW A -A
•
NUT REQ D
PIG. 100 •
ALL THREAD ROD
FIG. 200
ADJUSTABLE RING
HANGER
13OTTOM !BEAM CLAMP, ROD, AND RING
#02 HANGER DETAIL
N.T.S..
LINE RESTRAINT DETAIL
NOTE: 1) SPACE WITI.1 IN 6" OP A HANGER EVERY 42'-0"
2) BRACING PER NEPA-13(2001 ed.) SECTIONS 93588,
TABLE ' 3. S.S(a) AND 93. -RE 'TAINT OP BRANCH LINES
GENER NOTES'
1. RETAIL AREAS ARE DESIGNED IN ACCORDANCE WITH THE REQUIREMENTS OF N.F. P.A. 13-2007 ORDINARY HAZARD GROUP 2 MAX SPACING 130 SQ. FT.
2: COSCO POINT OF CONNECTION I5 AT EXIST BUILDING SHELL SYSTEM OUTLETS 1 1/2" GOL ON 4" FLOOR MAIN AS SHOWN ON THESE PLANS.
3. ALL PAINTING OF FIRE SPRINKLER PIPING (IF REQ) TO BE DONE BY OTHERS
4. ALL WIRING BY OTHER.
5. ALL MATERIAL I5 NEW U.L. LISTED AND MEETS THE REQUIREMENTS OF THE TUKWILA FIRE DEPT.
G. OWNER i5 RESPONSIBLE TO ASSURE THAT STRUCTURE AS ITIS SHOWN ON CONTRACT DRAWINGS CAN
ADEQUATELY SUPPORT ALL FIRE SPRINKLER PIPING LOADS.. NO AUXILLIARY DEVICES OR ATTACHMENTS
SHALL BE PROVIDED BY COSCO TO SUPPLIMENT THE STRUCTURE TO ACCOMODATE FIRE SPRINKLER
PIPING LOADS.
7. OWNER. 15 RESPONSIBLE TO PROVIDE ADEQUATE HEAT TO MAINTAIN 40 DEG. F. MINIMUM AT ALL TIMES YEAR ROUND.
8. SPRINKLER HEAD LOCATIONS INDICATED ON THESE DRAWINGS ARE NOT INTENDED TO BE "CENTER OF TILE" HEAD PLACEMENT.
9. COSCO ASSUMES NO RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, FOR THE CONDITION, PERFORMANCE OR
CURRENT CODE COMPLIANCE OF THE EXISTING SYSTEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM ON SITE
EXCEPT FOR WORK PERFORMED DIRECTLY BY COSCO.
10. OWNER I5 RESPONSIBLE TO ARRANGE FOR THE PERIODIC INSPECTION, TESTING AND MAINTENANCE OF THESE FIRE SPRINKLER
SYSTEMS IN ACCORDANCE WITH THE MINIMUM REQUIREMENTS OF N.F.P.A. 25-2002 BY QUALIFIED PERSONNEL COMMENCING
AFTER WARRANTY. PERIOD HAS EXPIRED. THE FIRM THAT DESIGNED AND INSTALLED THIS SYSTEM IS BEST QUALIFIED TO PROVIDE
THE ONGOING LONG TERM TESTING, MAINTENANCE AND SERVICING OF THIS SYSTEM(S).
FIELD NOTES
I) THREADED PIPE FROM I " THRU 2" SIZE TO BE SCH. 40 STD. WALL PIPE (IMPORT).
2) GROOVED END PIPE FROM 2 1/2" THRU 8" TO. BE SCH. I 0 (IMPORT).
3) ALL GROOVED COUPLING ARE TO BE "RIGID" TYPE U.N.O. (IMPORT).
4) ALL THREADED FITTINGS ARE 300# CLASS D.I. (IMPORT).
FIELD/NOTES
EXISTING PIPE
NEW. PIPE
EXISTING HEAD
NEW HEAD GO! -IL.
NE1AJ HEAD RFT
•
•
••••••.
•••••••
•••••••
•••®••.
COSCO
Fire Protection
FIRE PROTECTION AND LIFE SAFETY SPECIALISTS
WASHINGTON OFFICE
15000 Woodinville -Redmond Rd NE License No:
Woodinville, Washington 98072 COSCOFP11ONfv1
call (425) 686-8300 • fax (425) 827-4784
SAN DIEGO • LOS ANGELES • FRESNO • SAN FRANCISCO SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE
www.coscofire.com
PERMIT ##D08-0112
N'= 9 200�8%
ukwila Fire
PROJECT:
CLAIRES
2836 SOUTHCENTER MALL SPACE #2150
TUKWILA, WA 98188 JIM 405-288-2311
CONTRACT MATH:
HARDCASTLE CONSTRUCTION INC.
P.O.BOX 617
WASHINGTON, OK 73093
DRAWING 11TLE
FIRE SPRINKLER TENANT IMPROVEMENT
DATE : 06/06/08
SCALE : 1 /4" = 1' - 0'
DRAWN B't : BRIAN SCHULZE
�l5KS7956
SHEET NO.
'1 OF 1