PP - 2846 SOUTHCENTER MALL - SUNGLASS HUT - PERMITS AND PLANS
2846 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-334 08-S-265 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Sunglass Hut 2846 Southcenter Mall Permit No.: 08-S-265 Date: June 4, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1 DATE: 5/30/2008K5 7946 SGH 5665\CALCULATIONS\HYDRAULIC CALC'S\SGH5665.SDF JOB TITLE: Sunglass Hut #5665 WATER SUPPLY DATA SOURCE NODE TAG SRC STATIC PRESS. (PSI) 140.0 RESID. PRESS. (PSI) 20.0 AGGREGATE FLOW ANALYSIS: FLOW (GPM) 10900.0 TOTAL FLOW AT SOURCE TOTAL HOSE STREAM ALLOWANCE AT SOURCE OTHER HOSE STREAM ALLOWANCES TOTAL DISCHARGE FROM ACTIVE SPRINKLERS NODE ANALYSIS DATA NODE TAG ELEVATION (FT) S1 S2 S3 S4 S5 S6 S7 S8 S9 S10 Sll S12 1 2 3 4 5 6 7 8 9 10 11 12 M1 M2 M3 M4 M5 10.0 11.0 11.0 12.0 12.0 12.0 12.0 12.0 12.0 8.0 11.0 11.0 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 NODE TYPE K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 HOSE STREAM AVAIL. PRESS. (PSI) 138.8 TOTAL @ DEMAND (GPM) 903.7 GPM 250.0 GPM 329.0 GPM 324.7 GPM PRESSURE (PSI) 22.2 21.6 23.1 23.1 23.0 23.5 23.4 24.0 24.0 24.3 23.5 24.5 21.6 21.7 22.2 22.4 22.4 22.9 22.8 23.4 23.4 22.9 23.3 23.8 22.7 22.8 23.2 23.8 24.3 REQ'D PRESS. (PSI) 903.7 73.9 DISCHARGE (GPM) 26.4 26.0 26.9 26.9 26.9 27.1 27.1 27.5 27.4 27.6 27.1 27.7 329.0 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 5/30/2008KS 7946 SGH 5665\CALCULATIONS\HYDRAULIC CALC'S\SGH5665.SDF JOB TITLE: Sunglass Hut #5665 NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) CAP 17.5 24.4 TIE 17.5 27.6 5423 15.3 51.4 7265 -16.1 70.8 5096 -16.1 71.0 7561 -14.1 - - - - 70.3 - - - SRC -22.0 SOURCE 73.9 653.7 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 5/30/2008KS 7946 SGH 5665\CALCULATIONS\HYDRAULIC CALC'S\SGH5665.SDF JOB TITLE: Sunglass Hut #5665 PIPE DATA PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 1 -26.4 1.049 PL 8.23 PF 2.7 S1 10.0 5.6 22.2 26.4 9.8 120 FTG 2E PE -3.2 1 17.5 0.0 21.6 0.0 0.217 TL 12.23 PV Pipe: 2 -26.0 1.049 PL 7.23 PF 3.0 S2 11.0 5.6 21.6 26.0 9.7 120 FTG ET PE -2.8 2 17.5 0.0 21.7 0.0 0.211 TL 14.23 PV Pipe: 3 -26.9 1.049 PL 6.60 PF 1.9 S3 11.0 5.6 23.1 26.9 10.0 120 FTG E PE -2.8 3 17.5 0.0 22.2 0.0 0.225 TL 8.60 PV Pipe: 4 -26.9 1.049 PL 5.60 PF 1.7 S4 12.0 5.6 23.1 26.9 10.0 120 FTG E PE -2.4 4 17.5 0.0 22.4 0.0 0.225 TL 7.60 PV Pipe: 5 -26.9 1.049 PL 5.60 PF 1.7 S5 12.0 5.6 23.0 26.9 10.0 120 FTG E PE -2.4 5 17.5 0.0 22.4 0.0 0.225 TL 7.60 PV Pipe: 6 -27.1 1.049 PL 5.60 PF 1.7 S6 12.0 5.6 23.5 27.1 10.1 120 FTG E PE -2.4 6 17.5 0.0 22.9 0.0 0.229 TL 7.60 PV Pipe: 7 -27.1 1.049 PL 5.60 PF 1.7 S7 12.0 5.6 23.4 27.1 10.1 120 FTG E PE -2.4 7 17.5 0.0 22.8 0.0 0.228 TL 7.60 PV Pipe: 8 -27.5 1.049 PL 5.60 PF 1.8 S8 12.0 5.6 24.0 27.5 10.2 120 FTG E PE -2.4 8 17.5 0.0 23.4 0.0 0.234 TL 7.60 PV Pipe: 9 -27.4 1.049 PL 5.60 PF 1.8 S9 12.0 5.6 24.0 27.4 10.2 120 FTG E PE -2.4 9 17.5 0.0 23.4 0.0 0.233 TL 7.60 PV Pipe: 10 -27.6 1.049 PL 9.60 PF 2.7 S10 8.0 5.6 24.3 27.6 10.2 120 FTG E PE -4.1 10 17.5 0.0 22.9 0.0 0.236 TL 11.60 PV Sil 11 Pipe: 11 -27.1 1.049 PL 6.60 PF 2.7 11.0 5.6 23.5 27.1 10.1 120 FTG T PE -2.8 17.5 0.0 23.3 0.0 0.229 TL 11.60 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 5/30/2008KS 7946 SGH 5665\CALCULATIONS\HYDRAULIC CALC'S\SGH5665.SDF JOB TITLE: Sunglass Hut #5665 PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 12 -27.7 1.049 PL 6.60 PF 2.1 S12 11.0 5.6 24.5 27.7 10.3 120 FTG E PE -2.8 12 17.5 0.0 23.8 0.0 0.238 TL 8.60 PV Pipe: 13 -26.4 1.610 PL 4.50 PF 0.1 1 17.5 0.0 21.6 0.0 4.2 120 FTG ---- PE 0.0 2 17.5 0.0 21.7 0.0 0.027 TL 4.50 PV Pipe: 14 -52.4 1.610 PL 1.50 PF 0.9 2 17.5 0.0 21.7 0.0 8.3 120 FTG T PE 0.0 M1 17.5 H.S. 22.7 329.0 0.096 TL 9.50 PV Pipe: 15 -26.9 1.610 PL 7.46 PF 0.4 3 17.5 0.0 22.2 0.0 4.2 120 FTG T PE 0.0 M1 17.5 H.S. 22.7 329.0 0.028 TL 15.46 PV Pipe: 16 -26.9 1.610 PL 5.00 PF 0.4 4 17.5 0.0 22.4 0.0 4.2 120 FTG T PE 0.0 M2 17.5 0.0 22.8 0.0 0.028 TL 13.00 PV Pipe: 17 -26.9 1.610 PL 7.00 PF 0.4 5 17.5 0.0 22.4 0.0 4.2 120 FTG T PE 0.0 M2 17.5 0.0 22.8 0.0 0.028 TL 15.00 PV Pipe: 18 -27.1 1.610 PL 5.00 PF 0.4 6 17.5 0.0 22.9 0.0 4.3 120 FTG T PE 0.0 M3 17.5 0.0 23.2 0.0 0.028 TL 13.00 PV Pipe: 19 -27.1 1.610 PL 7.00 PF 0.4 7 17.5 0.0 22.8 0.0 4.3 120 FTG T PE 0.0 M3 17.5 0.0 23.2 0.0 0.028 TL 15.00 PV Pipe: 20 -27.5 1.610 PL 5.00 PF 0.4 8 17.5 0.0 23.4 0.0 4.3 120 FTG T PE 0.0 M4 17.5 0.0 23.8 0.0 0.029 TL 13.00 PV Pipe: 21 -27.4 1.610 PL 7.00 PF 0.4 9 17.5 0.0 23.4 0.0 4.3 120 FTG T PE 0.0 M4 17.5 0.0 23.8 0.0 0.029 TL 15.00 PV 10 11 Pipe: 22 -27.6 1.610 PL 5.12 PF 0.4 17.5 0.0 22.9 0.0 4.4 120 FTG T PE 0.0 17.5 0.0 23.3 0.0 0.029 TL 13.12 PV Pipe: 23 -54.7 1.610 PL 1.21 PF 1.0 11 17.5 0.0 23.3 0.0 8.6 120 FTG T PE 0.0 M5 17.5 0.0 24.3 0.0 0.104 TL 9.21 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: 5/30/2008KS 7946 SGH 5665\CALCULATIONS\HYDRAULIC CALC'S\SGH5665.SDF JOB TITLE: Sunglass Hut #5665 PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 24 -27.7 1.610 PL 8.79 PF 0.5 12 17.5 0.0 23.8 0.0 4.4 120 FTG T PE 0.0 M5 17.5 0.0 24.3 0.0 0.030 TL 16.79 PV Pipe: 25 -408.3 4.260 PL 3.00 PF 0.1 M1 17.5 H.S. 22.7 329.0 9.2 120 FTG ---- PE 0.0 M2 17.5 0.0 22.8 0.0 0.037 TL 3.00 PV Pipe: 26 -462.1 4.260 PL 9.50 PF 0.4 M2 17.5 0.0 22.8 0.0 10.4 120 FTG ---- PE 0.0 M3 17.5 0.0 23.2 0.0 0.047 TL 9.50 PV Pipe: 27 -516.3 4.260 PL 10.00 PF 0.6 M3 17.5 0.0 23.2 0.0 11.6 120 FTG ---- PE 0.0 M4 17.5 0.0 23.8 0.0 0.058 TL 10.00 PV Pipe: 28 -571.2 4.260 PL 6.88 PF 0.5 M4 17.5 0.0 23.8 0.0 12.9 120 FTG ---- PE 0.0 M5 17.5 0.0 24.3 0.0 0.070 TL 6.88 PV Pipe: 29 -653.7 4.260 PL 1.83 PF 0.2 M5 17.5 0.0 24.3 0.0 14.7 120 FTG ---- PE 0.0 CAP 17.5 0.0 24.4 0.0 0.089 TL 1.83 PV Pipe: 30 -653.7 4.260 PL 8.50 PF 3.1 CAP 17.5 0.0 24.4 0.0 14.7 120 FTG T PE 0.0 TIE 17.5 0.0 27.6 0.0 0.089 TL 34.80 PV Pipe: 38 -653.7 4.260 PL 243.00 PF 22.9 TIE 17.5 0.0 27.6 0.0 14.7 120 FTG E PE 0.9 5423 15.3 0.0 51.4 0.0 0.089 TL 256.20 PV Pipe: 39 -653.7 6.357 PL 234.80 PF 5.8 5423 15.3 0.0 51.4 0.0 6.6 120 FTG 219.9 PE 13.6 7265 -16.1 0.0 70.8 0.0 0.013 TL 454.70 PV Pipe: 40 -653.7 8.329 PL 12.60 PF 0.2 7265 -16.1 0.0 70.8 0.0 3.8 120 FTG 32.0 PE 0.0 5096 -16.1 0.0 71.0 0.0 0.003 TL 44.60 PV Pipe: 41 -653.7 10.420 PL 27.60 PF 0.1 5096 -16.1 0.0 71.0 0.0 2.5 120 FTG 83.0 PE -0.8 7561 -14.1 0.0 70.3 0.0 0.001 TL 110.60 PV Pipe: 42 -653.7 10.400 PL 108.50 PF 0.3 7561 -14.1 0.0 70.3 0.0 2.5 120 FTG 111.6 PE 3.4 SRC -22.0 SRCE 73.9 (N/A) 0.001 TL 220.10 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 DATE: 5/30/2008KS 7946 SGH 5665\CALCULATIONS\HYDRAULIC CALC'S\SGH5665.SDF JOB TITLE: Sunglass Hut #5665 PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) NOTES (HASS): (1) Calculations were performed by the HASS 7.9 computer program under license no. 4903012830 granted by HRS Systems, Inc. 4792 LaVista Road Tucker, GA 30084 (2) The system has been calculated to provide an average imbalance at each node of 0.002 gpm and a maximum imbalance at any node of 0.064 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 14.7 ft/sec at pipe 29. (4) PIPE FITTINGS TABLE Pipe Table Name: MOST.PIP PAGE: * MATERIAL: S40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkV1v BfyVly GatV1v AlmChk DPV1v NPTee 6.357 17.60 37.72 11.32 40.23 12.57 3.77 35.21 35.21 37.72 8.329 22.16 43.09 16.00 55.40 14.77 4.92 38.16 38.16 43.09 10.400 26.37 59.94 19.18 65.93 22.78 5.99 44.35 44.35 59.94 10.420 26.62 60.50 19.36 66.55 22.99 6.05 44.77 44.77 60.50 PAGE: A MATERIAL: SCH.40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D F Ell Tee LngEll ChkV1v BfyVly GatVly AlmChk DPV1v 45E11 H Q 1 S U V W 22/Ell 11gEll Couplg FM90E1 FM45E1 FMTee FMRunT 1.049 2.00 5.00 2.00 5.00 6.00 1.00 17.00 23.00 1.00 0.50 0.30 1.00 6.00 5.00 9.00 0.00 1.610 4.00 8.00 2.00 9.00 6.00 1.00 17.00 23.00 2.00 1.00 0.50 1.00 8.00 6.00 12.00 0.00 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7 DATE: 5/30/2008KS 7946 SGH 5665\CALCULATIONS\HYDRAULIC CALC'S\SGH5665.SDF JOB TITLE: Sunglass Hut #5665 PAGE: B MATERIAL: SCH.10 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D F Ell Tee LngEll ChkVly BfyVly GatV1v AlmChk DPV1v 45E11 H 4 1 S U V W 22/Ell 11gE11 Couplg FM90E1 FM45E1 FMTee FMRunT 4.260 13.20 26.30 7.90 29.00 15.80 2.60 36.90 39.50 6.60 3.30 1.60 1.30 18.40 11.90 31.60 0.00 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 8 DATE: 5/30/2008KS 7946 SGH 5665\CALCULATIONS\HYDRAULIC CALC'S\SGH5665.SDF JOB TITLE: Sunglass Hut #5665 WATER SUPPLY ANALYSIS 0 0 J (i)0 H e � a� I tri rn 0. O � N U 0 o o ri 1-1C o Ul m W O ¢, b U v a v o r, a, u �n Q I 0 qq 0 3W .0 a w p,) Q) rn CW %CCo -H ri 0 >, G. "7 RI CO b' • . > r1 N r1 -,--I RC a r FC CO a I O I O O O,1 C,1 00 W '0 N x W Oi O4 I o a N 0 0 o 0 wH I U 4J (IS 4J 0) O O O 0 1/40 r -I 0 0 d' N H g w a'a w cn x w -- aw O O O O O CO 'D a, O O N 0 0 1/401/40 O O in O O N SUNGLASS HUT 2115 FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET \UV 3ER SHEET TITLE FA -01 SYSTEM INFORMATION FA -02 TYPICAL DETAILS - WIRI\G A\D MOU \TI\G FA -03 FRE ALARM SYSTEM FLOOR PLA\ FA -04 SYSTEM CALCULATIO\S (GENEAL), ISE.R, SITE PLA WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N • SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE TWO 600V #12 AWG THHN/THWN TWO 600V #14 AWG THHN/THWN TWISTED TWO CONDUCTOR 300V #18 AWG FPL TW CABLE CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF CONDUIT SIZE MAXIMUM F 1/2" .12 SQUARE 3/4" .21 SQUARE 1" .34 SQUARE 1-1/4" .60 SQUARE 1-1/2" .82 SQUARE 2" 1.34 SQUARE FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM DIMENSIONS AREA .244 0.D. .0467 .210 0.D. .0346 .156 0.D. .0191 FROM THE TABLE FILL DIMENSION FROM THE WIRE. LL NCH NCH NCH NCH NCH INCH N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT. AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO 'CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. To THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 1 1 1 1 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT HTRI-D SIEMENS INTERFACE MODULE 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD r LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING DUCT SMOKE AD DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING Ec FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING L FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -OW SIEMENS 4S BOX W/ 1G RING CEILING L FIRE ALARM STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. Yc FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING WP MR FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) MULTI -VOLTAGE CONTROL RELAY SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -S17 -WP SIEMENS MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD MR -201 /C AIR PRODUCTS 4S BOX VERIFY IN FIELD 0 MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. 'r.b.U. F.B.. IN FIELD O JUNCTI❑N BOX F.B.O. A.F.F. ABOVE FINISHED FLOOR N/A B.❑. N/A PF VERIFY IN FIE L� NOTICE . A completed, signed, Tukwi N/A Without Comments N/A a Fire Department Pre-test Certificate must be presented spector prior to lent of Acceptance F.B,❑, FURNISHED BY OTHERS N/A /.--A /f ❑- As Note0 Red N/A Lw Ulu it ❑ Per The Attached Letter commencer Testing c N/A NOT APPLICABLE N/A ase plans have been r i4wed by The Tukwila jm Prevention Bureau for conformance with current city Aecet� if., cut pct to eFrorc and and Det Failure c U.O.N. UNLESS OTHERWISE NOTED N/A ctondards. ice issicns which do not IAorize violations of adR9tgd stanaaras and oro=nances. The responsibility for the igi totally with thee-decigncr. in a Re -in terminatil WP WEATHERPROOF DEVICE N/A «<« adequacy of rests editions, deletions or r ,igons to these drawinglsiarfer this date will void thi-s acceptance and will require a RED AS BUILT ADD OR CHANGE N/A resuLiiiitlatuf ieviaed diciwiligs fur subsequent approval. /A N/A N/A Final acceptance is subject to field test and inspection by GREEN AS BUILT REMOVE N/A Tne Tukwira r -ire Prevention Burea . /A N/A N/A (Date: O By: _� 'y7�� ,., . - AS BUILT N/A "� t', - =- ....p.w.ori NOTES TO CAD TUKWILA FIRE DEPARTM�� Please call: 575.4402 and give this job No.©� fg3t- and exact address for shut down or restoration approval, any Fire Alarm ection Systems. If test will result spection Fee and n of the testing. Ai JUN 12 200 Tukwila Fir /6O Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved '144 c#) ® 2 CC co 0' O C.9 C/) LLJ. uJ (n 0 LLJ t) O 0' 0' c0 (V \O 0 N >G La LC) LC) CV CV .O O CV J uJ RELEASE/REVISIONS REV. BY: 1 NVI DESCRIPTION SHOP DRAWINGS DATE 5/15/08 1(2 «<« SCALE: 1/8"=1' DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE:5/12/08 BACKROUND PLAN PROVIDED BY: .OB NUMBER: 1 SHEET FA -01 J THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE+ STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR S+ PREVIOUS ADDRESSABLE DEVIC END OF LINE DEVICE(3,6K 1/4W) o DUCT DETECTOR L❑CATION 1 0 0 SUPERVISED SWITCH ------ GROUND—CD r7 L) HTRI—R OSTATUS LED oo N.O. r- 0 COM 0 N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. O TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVIOUS ADDRESSABLE[ DEVICE TO NEXT ADDRESSABLE DEVICE L + NOTE 11 VOLTAGE MAX. - CURRENT MAX, - CONT. RES, MAX, - MAX. CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX, LINE SIZE - MIN. LINE SIZE- OUTLET SAMPLING----•\ TUBE `\ INLET SAMPLING TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE=NONE M U SIC }AC POWER SOURCE COMBINE ALL •SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE {I STOP IF LAST DEVICE (-) FROM XLS CONTROL PANEL OR {(+) PREVIOUS ADDRESSABLE DEVICE( RELAY CONTACTS (4.0A @ 125VAC) (4.0A @ 30VDC) 27 VDC 3,5 riA DURING POLLING 10 OHMS 200 FT, (18 AWG) 0,02uF 0,04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTI❑N. 0 O I' ml TB1 6 0 6 6 0 123456 TB2 c o cmc 654321 0 O END OF LINE DEVICE (3.6K 1/4W) / / SUPERVISED_ / / / SWITCH / GROUND ' N © HTRI—D OSTATUS LED CO 0 0 co O 1' NOT USED END OF LINE DEVICE 3.6K 1/4W) O \- UPERVISED l SWITCH NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC TOO T T 0 PAD -3 0 00 O INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 0 • • - 24K TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE ,NAC -4 NAC -3 NAC -2 NAC -1 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE + DEVICE LOOP NOT USED REMOTE DEVICE LOOP ! 0 0 0 0 FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY ('S' CABLE) FROM FACP <VOICE CIRCUIT) ('V' CABLE) 470 OHMS EOL TEM -1 0 oaf IP 8oREz 1 V) o CC000 0 0 CCC'CQ --- --- --- --- -- - TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE NOE (STROBE) SPEAKER 0) () (S ) STROBE v EARTH GROUND --.(+)TO NEXT DEVICE OR } _(-) STOP IF LAST DEVICE (+) ( ) STROBE SPEAKER (-) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY 80" A.F.F. O O O 4S DEEP BOX W/ 1-1/2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE TO NEXT DEVICE OR END OF LINE TO NEXT DEVICE OR END OF LINE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER�TIN TEMPERATU E: +32'F 0- C) TO 100 F 3S C) HUMIDITY: 9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR -� FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (-) DATA IN (+) > DEVICE IS USED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT DEVICE -t-- > (-) DATA OUT (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID —\ CEILING HARD LID SPEAKER SUPPORT TILE------ ------- BRIDGE LE --------------- BRIDGE 4' SQUARE DEEP BOX. WITH 1-1/2' EXTENSION N. CEILING MOUNTED N SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE=NONE JUNCTI❑N BOX • MOUNTED ON \\ CEILING FLEX \ ENF- / / / JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT 0 0 ; 1 TO NEXT DEVICE 0 0 CADDY BAR SMOKE DETECTOR ------ SMOKE DETECTOR MOUNTING SCALE=NONE SUSPENDED ILLUMINATED CEILING DO NOT INSTA L ADDRESSABLE 0 \MOAT NG DEVICES vNTIL DRE D OGVVIMED WITH DEVICES ADDRESS. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved r z c LU z 0.1 z rn co 0' FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z 4 DESCRIPTION SHOP DRAWINGS DATE co 0 in Lo °aaa« co co T T N ¢� I— 0 O D LU ZcpZ Z JJ CSC U= rrO or JJ Z co J CV () ~ V z Z a 0 Z 0 E (1 V J J F -- W J a SCALE: 1 /8"=1 DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: JOB NUMBER: SHEET FA -02 � ap 00 NORTH 42Fc.I.T2z2ES x 1!I 1 II_ 411' 4 X s' —. — , -- i— �— =+ : — 15 i r 1 l— y --- [ ]- L'a .t ^�E •P 4 I Iil —�-- y 1121 E SUNGLASS HUT 2115 WESTFIELD SOUTHCENTER MALL SCALE 10=1' FLAG NOTES FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,CSEE SIEMENS INSTALLATI❑N SUBMITTAL FOR L❑CATI❑N GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICAL CONTRACTOR. SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT, DO N0 NSTALL ADDRESSABLE IN T ATI NG DEVICES U\TIL DREP OGRAM M D WOTH EVICES ADDRESS. • Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved z co) a Z.4icxz F) c0 0' z 0 I -- c.9 z LLQ LLI 0 LLJ TEL. (206) 622-6545 RELEASE/REVISIONS T EN- C/) (/) 0 z �CALE: 1 /8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE:5/1 2/08 BACKROUND PLAN PROVIDED BY: \OB NUMBER: SHEET ( NORDSTROM 3 LEVEI_.S ! /! 71.275:f nn:^el rx.S m0� 4-6 Jr -0.000 CLRF mCS 4 LEVELS 250. 4U%57 ML :J\ SCUP gA00r2 Ce G0 merwyrirs 2 LEVELS 65,7)7,r PAnE.5 .Ir�[SCLwCC $009;3 R xYs llw•ex ,o:na /.iR'n ACOR 0,0:;: C00JA: UNP 0;01.r II100.4'f o r c NAL.\S Nt'1 2 Cti;aC• 005 ^wN.742 '•RR'"L::4 '*1n".2SS CAN.:: 'N WASH.:70N ,9040:0. ^1'S •' Va.1 [II(e ,HF P•;;nF[� YE•T':C NOT•.ER0000 057R S,00y:ICCS 3001E 00000 0.0 0000 PAC', :JJr. 545011• 1,590.9 01!,:,150 04.4004. yl'`CV4 F'`,iJ 0.:5 49.515>55 YE 1400 5•\; C'I. ::DC] a w 1 p_).• ICL' J c L iJ DIA r :U; Z 1 -1150'; 341 .I}G9 :0 i Y 5:41 00: 114 n1'Mii I'l # 11..00 F 0 -d''l 4.21 r=M»1 ' 551100105,5 R2A K:TChC:I G.AC 555,0 0J'O'lA IONS 00.1 a, "10 IAAG 0.015 (N lf'M 1111 01'!.!11 ,1-C141,1i NORTH SUNGLASS HUT 2115 WESTFIELD SOUTHCENTER MALL E%I.S1011.0 00:0 3 LEVELS 276.46`sr SCALE 1/32°=1' S,2V 2S42V - 2Si2V 30 C 15 15 EX RISER DIAGRAM SYSTEM CALCULATIONS SUNGLASS HUT 2115 SUNGLASS HUT 2115 FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations PROJECT: WESTFIELD SOUTHCENTER MALL Panel: SUNGLASS HUT 2115 Wire Resistance 1.62 Current Load: Standby: Alarm: CURRENT TOTAL= Current Load: Standby: Alarm: CIRCUIT: S1 QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Device Type Qty Amps Total Amps Total 64 Device Type Qty Amps Total Amps Total 0.62 HFP-11 SET -MC @30CD 0.0022 0.0022 0.0023 (WL * 2 ) * (R/ft) 0 SET -MC @75CD 175 0 AD2-P 1 0.0635 0.0635 0.064 0.064 0 Main System Board 1 0.03 0.03 0.030 0.030 HTR -R 2 0.009600 0.0096 0.021 0.042 SET -MC @15CD 1 Voltage Drop ( E) 0.064 0.064 SET-HMC-C@177CD HTRI-D 0 0.001600 0.0035 (E= 1* R) SET -MC @30CD 1 SET -HMC @135CD 318 0.098 0.098 ICP -B6 0.005 20.26 0 SET -HMC @185CD 445 SET -MC @75CD 0.175 (20.4 - E) 1 Z-MC@15CD 64 - 64 SET -MC @110CD 0 0.233 98 0 0 SET HMC-C@115CD 233 0 0.318 DEVICES= 3 TOTAL mA= 226 12 SET HMC-C@135CD 20.260142161 2261 0.318 W 0.0731 Amps 0.106 Amps SET HMC-C@185CD 0.445 PROJECT: Panel: SUNGLASS HUT 2115 Wire Resistance 2.58 Date: June 10,2008 ZR -MC @15CD 1 3.6 0.064 0.064 CIRCUIT: Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours ZR -MC @30CD QTY 0.098 Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total HCP 70.7V1/8 1.8 3.6 0.0015 Alarm Current Load: 0.106 Amps For 5 Minutes= 0.009 Amp -hours 0 0 0.03 Amps 0.256 Amps 0 25% Derating= 2.204 Amp -hours Total Device Load, Amps (I) 0.00 0 Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours (Total Cct Load) 0 0 0 Voltage Drop ( E) 0.00 0 0 0 (E= I * R) 0 Alarm Current Load: 0.256 Amps For 5 Minutes= 0.022 Amp -hours . EOL Voltage Total System Current Load: 0 2.204 Amp -hours 0 (20.4 - E) 0 0 0 25% Derating= 0.927 Amp -hours 0 Battery Pair to be Used: 12VDC Amp -hours 7AH DEVICES= 2 TOTAL mA= 3.6 14 191 20.396451981 3.6 Total System Current Load: 0.927 Amp -hours Battery Pair to be Used: 12VDC 1 Amp -hours 7AH BATTERY SIZING CALCULATION VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved FA -04. z ca 64.4 cz z FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS m Lu z a DESCRIPTION SHOP DRAWINGS cO 0 1� Y / 1.0 as 0 w C!)• O LLI 1.0 co CC co., I-Wcc ccp rr D I co Z Z Z C1)cCU� W cf)-JEQ C Q�� �w � z L�- 0 Z co - D ND Cf) V U LLI C!) y- C/) �CALE: 1 /8"=1 DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: \0B NUMBER: SHEET ----- Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: SUNGLASS HUT 2115 Wire Resistance 1.62 Date: June 10, 2008 CURRENT TOTAL= J 226 ---1 CIRCUIT: S1 QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 1 SET -MC @15CD 64 64 Total Wire Resistance (R) 0.62 1 SET -MC @30CD 98 98 (WL * 2 ) * (R/ft) 0 SET -MC @75CD 175 0 Total Device Load, Amps (I) 0.23 0 SET -MC @11OCD 233 0 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 Voltage Drop ( E) 0.14 0 SET-HMC-C@177CD 445 0 (E= 1* R) 0 SET -HMC @135CD 318 0 EOL Voltage 20.26 0 SET -HMC @185CD 445 0 (20.4 - E) 1 Z-MC@15CD 64 - 64 0 Z-mc@30CD 98 0 0 SET-MC-CW@110CD 233 0 DEVICES= 3 TOTAL mA= 226 12 191 20.260142161 2261 W WESTFIELD SOUTHCENTER Notification Appliance Circuit MALL Detail PROJECT: Panel: SUNGLASS HUT 2115 Wire Resistance 2.58 Date: June 10,2008 CURRENT TOTAL= 3.6 CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 70.7V1/8 1.8 3.6 Total Wire Resistance (R) 0.99 0 0 0 (WL*2)*(R/ft) 0 0 0 Total Device Load, Amps (I) 0.00 0 0 0 J (Total Cct Load) 0 0 0 Voltage Drop ( E) 0.00 0 0 0 (E= I * R) 0 0 0 . EOL Voltage 20.40 0 0 0 (20.4 - E) 0 0 0 0 0 0 DEVICES= 2 TOTAL mA= 3.6 14 191 20.396451981 3.6 VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved FA -04. z ca 64.4 cz z FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS m Lu z a DESCRIPTION SHOP DRAWINGS cO 0 1� Y / 1.0 as 0 w C!)• O LLI 1.0 co CC co., I-Wcc ccp rr D I co Z Z Z C1)cCU� W cf)-JEQ C Q�� �w � z L�- 0 Z co - D ND Cf) V U LLI C!) y- C/) �CALE: 1 /8"=1 DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: \0B NUMBER: SHEET TOLCO PIC#+. WO UNIvORSAL SWAY ORACS PITTIN3 may,. v.+: •.• ••,".'r" 1' SCM 40 TOLCO PII tNIVRRSAL SWAY DRAGS PITTN3 TOLCO PIPS CLAMP P13. 4A (24}" PIPS AND LARal PIG. 4 (211 PIP AND SMALLRR) LONG ITUDIN1bTL BRACE NTS " KWIIC DOLT D. MIN. NA Oft tge 4831 SO Mt ' 6' I e, LATERAL 1+3RACE 0 0 6 0 9 I d I (2" PIPS 4 SMALLER) NTS 1 . T'OICOPIC LNIVRRSAL SWAY DRAGS PI'rTIN3 *. „•r:, f.T ...t0.. tOLCO P13.1001 PAST CLAMP 44" ICWNC DOLT LATERAL i3R14CE (21/2" PIPE 4 LARGER) NTS ,4 SCO Mae 3* x 3.1/2 1.44 SCRRW POTS WOOD 1/4" Wit BOLT POR CONCRSTU 1/4 X 1 IIIK POR eARJOIS1 OR STOOL SRAM 3/0"x1 -t0 ALL THROAT, ROD MAX MIR 611.131.3 RDISTRANNT WHERE LENBtH CP ALL THREAD R 1'-10" ADD SECOND RESTRAIN' INE RESTRA INT IDET>AI IL SYMBOL =X NOTE: 1) SPACE WITH N 6" OF 14 HANGER EVERY 42'-0". 2) BRACING PER NFPA-13(200i ed.) SECTIONS 9.3.5.13.S, TABLE 9.3.5.S.S(c) AND 93.6-RESTAINT OF BRANCH LINES /�I-/111 fIGG� ff�O 23'-10" 3I -CI CORA OR 0/17#77 illar.71,1,1/711270/ 1 MALI CONCOURSE N 1 5I -6 ADJACENT TENANT SIRE SPRINKLER PIPINCa PLAN REVISIONS DESCRIPTION DATE SPRINKLER HEAD LEGEND: UL TDLCO FIG. 65 C -CLAMP PIPE SIZE I I/4' 1 I/2' 2 1/2' 3' 4' 6' 8' ROD DIA 3/8' 3/8' 3/8' 3/8' 3/8' 3/8' 3/8' I/2' 112' RETAINER STRAP, NUT THREADED ROD HILTI FIG LH OR TOLCO FIG 200 HANGER RING e . 04/2007 1 COSCO STANDARD HANGER I 2 TYPICAL HAIJTSR LI81I4. 1' AND t1+' P '1'-1' at W-0' ARP BLEVATICN) 11,0 PIPl1•1'44' SS PLAN POR ALL ODOR 1.11N31146 UL . HILTI KWIK BOLT TZ ANCHOR ICC REPORT #ESR -1917 MIN OF 3,000 PSI CONCRETE MIN .3 1/4' CONCRETE OVER MAX 3' METAL DECK 3/8' ANCHOR W/20# TORQUE: TENSION=395#,SHEAR=750# I/2' ANCHOR W/40# TORQUE: TENSION=440#,SHEAR=750# 1/2' MIN N 111 ROD COUPLING THREADED ROD PIPE ROD SIZE DIA I' 3/8' 1.25' 3/8' 1.5' 3/8' 2' 3/8' 2.5' '3/8' 3' . 3/8' 4' 3/8' 6' 1/2' 8' 1/2' BOLT IMBED LGTH DEPTH 7' 2 1/4' 7' 2 1/4' 7' 2 1/4' 7' 2 1/4' 7' 21/6' 7' 2 1/4' 7' 21/4'. 7' 2 1/4' 7 2 1/4' HILTI FIG LH OR • TOLCO FIG 200 HANGER RING 0 •04/2007 I COSCO STANDARD HANGER 1 13 MDLH HYDRAULIC DESIGN -REMOTE AREA SUNGLASS HUT #5665 - ENTIRE TENANT SPACE ORDINARY. HAZARD GROUP 2 .20 GPM/1500 S.F. K=5.6. 130 S.F. MAX: PER HEAD 12 SPRINKLERS DISCHARGING IN REMOTE AREA SYSTEM DEMAND: 903.7 GPM ® 73.9 PSI TOLCO FIG. 25 SURGE RESTRAINER TYPE 1 - FOR 1" AND 1-1/4" PIPE AND HANGER TYPE 2 - FOR 1-1/2" AND 2" PIPE AND HANGER TOLCO FIG. 25 IS DESIGNED TO BE USED ONLY WITH TOLCO BAND HANGERS FIG. 200 AND 2NFPA TO RESTRAIN THE UPWARD MOVEMENT OF PIPE AS IT OCCURS DURING SPRINKLER HEAD ACTIVATION OR SEISMIC ACTIVITY OPIGURE 25 SURGL RESTRAINER FOR STEEL OR CPVC PLASTIC PIPE FIRE SPRINKLER SYMBOL EENID c 111-0'I • LONGITUDINAL SWAY BRACE LATERAL SIUAY BRACE BRANCHLINE RESTRAINT PIPE HANGER PIPE ELEVATION AFTER FLOOR CEILING ELEVATION AFTER FLOOR HYDRAULIC NODE PENDENT/CONCEALED SPRINKLER SYMBOL S/N ORIFICE NPT K•FACT. HEAD FINISH PLATE FINISH TYPICAL DROP TO SPRINKLER HEAD GENVZ41.., NOTES 1 1/2" BRANCHLINE L__11.011 "FLEXHEAD" FLEXABLE DROP CORRUGATED STAINLESS STEEL BRAIDED HOSE ADJUSTABLE HUB MOUNTING BRACKET CEIUNG TYPICAL DROP TO SPRINKLER HEAD IN AC TILE CEILINGS 2. 3. 4. 5. 6. 1. S. 9. 10. 11. 11. 12. DESIGN AND INSTALLATION SHALL CONFORM TO NPA PAMPHLET 13 AND CITY OF TUKWILA FIRE DWPt. REQUIREMENTS. ALL MATERIALS. SHALL BE NEW AND U.I.. APPROVED. PIPE: ALL PIPE 2" AND LARGER TO BE SCHEDULE 40 BLACK STEEL. ALL PIPE 21" AND LARGER TO BE SCHEDULE I0. BLACK STEEL. FITTINGS: ALL FITTINGS (SCREWED AND GROOVED) AND GROOVED COUPLINGS TO BE STAR BRAND DUCTILE IRON. PAINTING OF PIPE AND PROTECTION OF SPRINKLER HEADS FROM PAINT IS BY OTHERS. ALL ELECTRICAL WIRING AND CONDIUT IS BY OTHERS. • ALL WELDING TO CONFORM WITH (AWS 010.9 AND WILL BE PERFORMED IN COSCO'S SHOP. IT 15 THE BUILDING OUJNERS RESPONSIBILITY TO KEEP ALL AREAS WITH WET SPRINKLER SYSTEMS HEATED TO. A MINIMUM 40 DEGREES FAHRENHEIT TO PREVENT FREEZING OF PIPES. OWNER IS RESPONSIBLE TO ASSURE THAT STRUCTURE AS IT 15 SHOWN ON THS CONTRACT DRAWINGS CAN t4DEQUA'tELY SUPPORT ALL FIRE SPRINKLER PIPING LOADS. NO.AUXILLIARY DEVICES OR ATTACHMENTS SHALL BE PROVIDED BY COSCO TO. SUPPLIMENT THE STRUCTURE TO ACCOMODATE FIRE SPRINKLER PIPING LOADS COSCO ASSUMES NO RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, POR THE CONDITION, PERFORMANCE OR CURRENT CODE COMPLIANCE OP THE EXISTING SYSTEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY COSCO FIRE PROTECTION. UNDERGROUND CONTRACTOR SHALL FLUSH THE UNDERGROUND AND PROVIDE COSCO WITH THE PROPER CERTIFICATE OP 'DOING SO BEFORE COSCO WILL CONNECT TO THE UNDERGROUND PIPE. SPRINKLER HEADS ARE DESIGNED TO BE IN CENTERLINE OP CEILING TILE (+1- I"). ALL DIMENSIONS ARE TO CENTERLINE OP PIPE. DOTTED LINES DENOTE EXISTING PIPE. • s /ut:Ut Comments PGI Leti:er it •• 1 nese P;'1'.•:,'".•'-2 i �,,,1 .F_s Fire tl :Y3,.1:; II 1-•� ?,y, :'I ; e:1• TEMP. QUAN. RELIABLE MODEL G4A QR CONCEALED PENDENT R5415 1/2' 1/2' 5.6 BR WH 165° • 12 APPROVALS BY: CITY OF TUKWILA TOTAL SPRINKLERS THIS SHEET 12 EAST RISER ROOM -PLAN VIEW St3t1dc:1,..:. "Fadeq-: r• ,, r AdditionT, 3' .,I i, this dEA,3 L,,,{11 „'y 4` .ca of ,/11'•30 i.i' .:,,r` K3!' C.It}`AtLi ,L;i'1t r;i: plovai. ,, CSUaC"illt i•` ti � l - •t.s:;t: ct to bold test and inspection by I Final acc�p�T�ce i;�Y�., The. Tukwila Fife Frcveniion Bureau. . TUKWILA FIRE DEPARTMIrN', Please call: 575.4402 and give this job No.2- - �•.(P� and exact address for shut= a:,v4r1 or restjration approval EV OGl dSLCE Weld stamps mu 'I:be inspected before pipe is hung. P� not paint piping prior to hydrostatic test approval. 1Date:!_LiL___ =•S• 00®• . ••® 00 0•.• • 0 00 0 a ••0 .O•. COSCO .Fire Protection FIRE PROTECTION AND LIFE SAFETY SPECIALISTS WASHINGTON OFFICE 15000 Woodinville -Redmond Rd NE License No: Woodinville, Washington 98072 COSCOFP11ONM call (425) 686-8300. • fax (425) 827-4784 SAN DIEGO • LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE Www.coscoftre.com O S By: FILE COPY r , ••ria R:ci.uer. l 399-‘77- "K, • NORDSTROM •9y. TENANT SF'ACE- f FUM -'U,' 51AIL SUNGLASS HUT #5665 633 SOUTHCENTER MALL SUITE 2846 TUKWILA, WA • . . CONTRACT WITH: TURNER BUSCH CONSTRUCTION 214 STATE STREET HACKENSACK, NJ 07601 I woattteta, LLC ADDRRSS PTA" NOB • Tukwila Fire z&' od s SWING TITLE FIRE SPRINKLER TENENT IMPROVEMENT 14/ s�l� MVO 'AS OF: Apr 10, LKS itYril 0 Southcont°r 2., DATE : 05-29-08 SCALE : 1/2"=1'-0" DRAWN BY : T.N.RHODES JOB 5 KS 7946 SHIT NO. l ofl 2846 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-334 08-S-265 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Sunglass Hut 2846 Southcenter Mall Permit No.: 08-S-265 Date: June 4, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1 DATE: 5/30/2008K5 7946 SGH 5665\CALCULATIONS\HYDRAULIC CALC'S\SGH5665.SDF JOB TITLE: Sunglass Hut #5665 WATER SUPPLY DATA SOURCE NODE TAG SRC STATIC PRESS. (PSI) 140.0 RESID. PRESS. (PSI) 20.0 AGGREGATE FLOW ANALYSIS: FLOW (GPM) 10900.0 TOTAL FLOW AT SOURCE TOTAL HOSE STREAM ALLOWANCE AT SOURCE OTHER HOSE STREAM ALLOWANCES TOTAL DISCHARGE FROM ACTIVE SPRINKLERS NODE ANALYSIS DATA NODE TAG ELEVATION (FT) S1 S2 S3 S4 S5 S6 S7 S8 S9 S10 Sll S12 1 2 3 4 5 6 7 8 9 10 11 12 M1 M2 M3 M4 M5 10.0 11.0 11.0 12.0 12.0 12.0 12.0 12.0 12.0 8.0 11.0 11.0 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 NODE TYPE K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 HOSE STREAM AVAIL. PRESS. (PSI) 138.8 TOTAL @ DEMAND (GPM) 903.7 GPM 250.0 GPM 329.0 GPM 324.7 GPM PRESSURE (PSI) 22.2 21.6 23.1 23.1 23.0 23.5 23.4 24.0 24.0 24.3 23.5 24.5 21.6 21.7 22.2 22.4 22.4 22.9 22.8 23.4 23.4 22.9 23.3 23.8 22.7 22.8 23.2 23.8 24.3 REQ'D PRESS. (PSI) 903.7 73.9 DISCHARGE (GPM) 26.4 26.0 26.9 26.9 26.9 27.1 27.1 27.5 27.4 27.6 27.1 27.7 329.0 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 5/30/2008KS 7946 SGH 5665\CALCULATIONS\HYDRAULIC CALC'S\SGH5665.SDF JOB TITLE: Sunglass Hut #5665 NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) CAP 17.5 24.4 TIE 17.5 27.6 5423 15.3 51.4 7265 -16.1 70.8 5096 -16.1 71.0 7561 -14.1 - - - - 70.3 - - - SRC -22.0 SOURCE 73.9 653.7 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 5/30/2008KS 7946 SGH 5665\CALCULATIONS\HYDRAULIC CALC'S\SGH5665.SDF JOB TITLE: Sunglass Hut #5665 PIPE DATA PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 1 -26.4 1.049 PL 8.23 PF 2.7 S1 10.0 5.6 22.2 26.4 9.8 120 FTG 2E PE -3.2 1 17.5 0.0 21.6 0.0 0.217 TL 12.23 PV Pipe: 2 -26.0 1.049 PL 7.23 PF 3.0 S2 11.0 5.6 21.6 26.0 9.7 120 FTG ET PE -2.8 2 17.5 0.0 21.7 0.0 0.211 TL 14.23 PV Pipe: 3 -26.9 1.049 PL 6.60 PF 1.9 S3 11.0 5.6 23.1 26.9 10.0 120 FTG E PE -2.8 3 17.5 0.0 22.2 0.0 0.225 TL 8.60 PV Pipe: 4 -26.9 1.049 PL 5.60 PF 1.7 S4 12.0 5.6 23.1 26.9 10.0 120 FTG E PE -2.4 4 17.5 0.0 22.4 0.0 0.225 TL 7.60 PV Pipe: 5 -26.9 1.049 PL 5.60 PF 1.7 S5 12.0 5.6 23.0 26.9 10.0 120 FTG E PE -2.4 5 17.5 0.0 22.4 0.0 0.225 TL 7.60 PV Pipe: 6 -27.1 1.049 PL 5.60 PF 1.7 S6 12.0 5.6 23.5 27.1 10.1 120 FTG E PE -2.4 6 17.5 0.0 22.9 0.0 0.229 TL 7.60 PV Pipe: 7 -27.1 1.049 PL 5.60 PF 1.7 S7 12.0 5.6 23.4 27.1 10.1 120 FTG E PE -2.4 7 17.5 0.0 22.8 0.0 0.228 TL 7.60 PV Pipe: 8 -27.5 1.049 PL 5.60 PF 1.8 S8 12.0 5.6 24.0 27.5 10.2 120 FTG E PE -2.4 8 17.5 0.0 23.4 0.0 0.234 TL 7.60 PV Pipe: 9 -27.4 1.049 PL 5.60 PF 1.8 S9 12.0 5.6 24.0 27.4 10.2 120 FTG E PE -2.4 9 17.5 0.0 23.4 0.0 0.233 TL 7.60 PV Pipe: 10 -27.6 1.049 PL 9.60 PF 2.7 S10 8.0 5.6 24.3 27.6 10.2 120 FTG E PE -4.1 10 17.5 0.0 22.9 0.0 0.236 TL 11.60 PV Sil 11 Pipe: 11 -27.1 1.049 PL 6.60 PF 2.7 11.0 5.6 23.5 27.1 10.1 120 FTG T PE -2.8 17.5 0.0 23.3 0.0 0.229 TL 11.60 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 5/30/2008KS 7946 SGH 5665\CALCULATIONS\HYDRAULIC CALC'S\SGH5665.SDF JOB TITLE: Sunglass Hut #5665 PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 12 -27.7 1.049 PL 6.60 PF 2.1 S12 11.0 5.6 24.5 27.7 10.3 120 FTG E PE -2.8 12 17.5 0.0 23.8 0.0 0.238 TL 8.60 PV Pipe: 13 -26.4 1.610 PL 4.50 PF 0.1 1 17.5 0.0 21.6 0.0 4.2 120 FTG ---- PE 0.0 2 17.5 0.0 21.7 0.0 0.027 TL 4.50 PV Pipe: 14 -52.4 1.610 PL 1.50 PF 0.9 2 17.5 0.0 21.7 0.0 8.3 120 FTG T PE 0.0 M1 17.5 H.S. 22.7 329.0 0.096 TL 9.50 PV Pipe: 15 -26.9 1.610 PL 7.46 PF 0.4 3 17.5 0.0 22.2 0.0 4.2 120 FTG T PE 0.0 M1 17.5 H.S. 22.7 329.0 0.028 TL 15.46 PV Pipe: 16 -26.9 1.610 PL 5.00 PF 0.4 4 17.5 0.0 22.4 0.0 4.2 120 FTG T PE 0.0 M2 17.5 0.0 22.8 0.0 0.028 TL 13.00 PV Pipe: 17 -26.9 1.610 PL 7.00 PF 0.4 5 17.5 0.0 22.4 0.0 4.2 120 FTG T PE 0.0 M2 17.5 0.0 22.8 0.0 0.028 TL 15.00 PV Pipe: 18 -27.1 1.610 PL 5.00 PF 0.4 6 17.5 0.0 22.9 0.0 4.3 120 FTG T PE 0.0 M3 17.5 0.0 23.2 0.0 0.028 TL 13.00 PV Pipe: 19 -27.1 1.610 PL 7.00 PF 0.4 7 17.5 0.0 22.8 0.0 4.3 120 FTG T PE 0.0 M3 17.5 0.0 23.2 0.0 0.028 TL 15.00 PV Pipe: 20 -27.5 1.610 PL 5.00 PF 0.4 8 17.5 0.0 23.4 0.0 4.3 120 FTG T PE 0.0 M4 17.5 0.0 23.8 0.0 0.029 TL 13.00 PV Pipe: 21 -27.4 1.610 PL 7.00 PF 0.4 9 17.5 0.0 23.4 0.0 4.3 120 FTG T PE 0.0 M4 17.5 0.0 23.8 0.0 0.029 TL 15.00 PV 10 11 Pipe: 22 -27.6 1.610 PL 5.12 PF 0.4 17.5 0.0 22.9 0.0 4.4 120 FTG T PE 0.0 17.5 0.0 23.3 0.0 0.029 TL 13.12 PV Pipe: 23 -54.7 1.610 PL 1.21 PF 1.0 11 17.5 0.0 23.3 0.0 8.6 120 FTG T PE 0.0 M5 17.5 0.0 24.3 0.0 0.104 TL 9.21 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: 5/30/2008KS 7946 SGH 5665\CALCULATIONS\HYDRAULIC CALC'S\SGH5665.SDF JOB TITLE: Sunglass Hut #5665 PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 24 -27.7 1.610 PL 8.79 PF 0.5 12 17.5 0.0 23.8 0.0 4.4 120 FTG T PE 0.0 M5 17.5 0.0 24.3 0.0 0.030 TL 16.79 PV Pipe: 25 -408.3 4.260 PL 3.00 PF 0.1 M1 17.5 H.S. 22.7 329.0 9.2 120 FTG ---- PE 0.0 M2 17.5 0.0 22.8 0.0 0.037 TL 3.00 PV Pipe: 26 -462.1 4.260 PL 9.50 PF 0.4 M2 17.5 0.0 22.8 0.0 10.4 120 FTG ---- PE 0.0 M3 17.5 0.0 23.2 0.0 0.047 TL 9.50 PV Pipe: 27 -516.3 4.260 PL 10.00 PF 0.6 M3 17.5 0.0 23.2 0.0 11.6 120 FTG ---- PE 0.0 M4 17.5 0.0 23.8 0.0 0.058 TL 10.00 PV Pipe: 28 -571.2 4.260 PL 6.88 PF 0.5 M4 17.5 0.0 23.8 0.0 12.9 120 FTG ---- PE 0.0 M5 17.5 0.0 24.3 0.0 0.070 TL 6.88 PV Pipe: 29 -653.7 4.260 PL 1.83 PF 0.2 M5 17.5 0.0 24.3 0.0 14.7 120 FTG ---- PE 0.0 CAP 17.5 0.0 24.4 0.0 0.089 TL 1.83 PV Pipe: 30 -653.7 4.260 PL 8.50 PF 3.1 CAP 17.5 0.0 24.4 0.0 14.7 120 FTG T PE 0.0 TIE 17.5 0.0 27.6 0.0 0.089 TL 34.80 PV Pipe: 38 -653.7 4.260 PL 243.00 PF 22.9 TIE 17.5 0.0 27.6 0.0 14.7 120 FTG E PE 0.9 5423 15.3 0.0 51.4 0.0 0.089 TL 256.20 PV Pipe: 39 -653.7 6.357 PL 234.80 PF 5.8 5423 15.3 0.0 51.4 0.0 6.6 120 FTG 219.9 PE 13.6 7265 -16.1 0.0 70.8 0.0 0.013 TL 454.70 PV Pipe: 40 -653.7 8.329 PL 12.60 PF 0.2 7265 -16.1 0.0 70.8 0.0 3.8 120 FTG 32.0 PE 0.0 5096 -16.1 0.0 71.0 0.0 0.003 TL 44.60 PV Pipe: 41 -653.7 10.420 PL 27.60 PF 0.1 5096 -16.1 0.0 71.0 0.0 2.5 120 FTG 83.0 PE -0.8 7561 -14.1 0.0 70.3 0.0 0.001 TL 110.60 PV Pipe: 42 -653.7 10.400 PL 108.50 PF 0.3 7561 -14.1 0.0 70.3 0.0 2.5 120 FTG 111.6 PE 3.4 SRC -22.0 SRCE 73.9 (N/A) 0.001 TL 220.10 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 DATE: 5/30/2008KS 7946 SGH 5665\CALCULATIONS\HYDRAULIC CALC'S\SGH5665.SDF JOB TITLE: Sunglass Hut #5665 PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) NOTES (HASS): (1) Calculations were performed by the HASS 7.9 computer program under license no. 4903012830 granted by HRS Systems, Inc. 4792 LaVista Road Tucker, GA 30084 (2) The system has been calculated to provide an average imbalance at each node of 0.002 gpm and a maximum imbalance at any node of 0.064 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 14.7 ft/sec at pipe 29. (4) PIPE FITTINGS TABLE Pipe Table Name: MOST.PIP PAGE: * MATERIAL: S40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkV1v BfyVly GatV1v AlmChk DPV1v NPTee 6.357 17.60 37.72 11.32 40.23 12.57 3.77 35.21 35.21 37.72 8.329 22.16 43.09 16.00 55.40 14.77 4.92 38.16 38.16 43.09 10.400 26.37 59.94 19.18 65.93 22.78 5.99 44.35 44.35 59.94 10.420 26.62 60.50 19.36 66.55 22.99 6.05 44.77 44.77 60.50 PAGE: A MATERIAL: SCH.40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D F Ell Tee LngEll ChkV1v BfyVly GatVly AlmChk DPV1v 45E11 H Q 1 S U V W 22/Ell 11gEll Couplg FM90E1 FM45E1 FMTee FMRunT 1.049 2.00 5.00 2.00 5.00 6.00 1.00 17.00 23.00 1.00 0.50 0.30 1.00 6.00 5.00 9.00 0.00 1.610 4.00 8.00 2.00 9.00 6.00 1.00 17.00 23.00 2.00 1.00 0.50 1.00 8.00 6.00 12.00 0.00 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7 DATE: 5/30/2008KS 7946 SGH 5665\CALCULATIONS\HYDRAULIC CALC'S\SGH5665.SDF JOB TITLE: Sunglass Hut #5665 PAGE: B MATERIAL: SCH.10 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D F Ell Tee LngEll ChkVly BfyVly GatV1v AlmChk DPV1v 45E11 H 4 1 S U V W 22/Ell 11gE11 Couplg FM90E1 FM45E1 FMTee FMRunT 4.260 13.20 26.30 7.90 29.00 15.80 2.60 36.90 39.50 6.60 3.30 1.60 1.30 18.40 11.90 31.60 0.00 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 8 DATE: 5/30/2008KS 7946 SGH 5665\CALCULATIONS\HYDRAULIC CALC'S\SGH5665.SDF JOB TITLE: Sunglass Hut #5665 WATER SUPPLY ANALYSIS 0 0 J (i)0 H e � a� I tri rn 0. O � N U 0 o o ri 1-1C o Ul m W O ¢, b U v a v o r, a, u �n Q I 0 qq 0 3W .0 a w p,) Q) rn CW %CCo -H ri 0 >, G. "7 RI CO b' • . > r1 N r1 -,--I RC a r FC CO a I O I O O O,1 C,1 00 W '0 N x W Oi O4 I o a N 0 0 o 0 wH I U 4J (IS 4J 0) O O O 0 1/40 r -I 0 0 d' N H g w a'a w cn x w -- aw O O O O O CO 'D a, O O N 0 0 1/401/40 O O in O O N SUNGLASS HUT 2115 FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET \UV 3ER SHEET TITLE FA -01 SYSTEM INFORMATION FA -02 TYPICAL DETAILS - WIRI\G A\D MOU \TI\G FA -03 FRE ALARM SYSTEM FLOOR PLA\ FA -04 SYSTEM CALCULATIO\S (GENEAL), ISE.R, SITE PLA WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N • SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE TWO 600V #12 AWG THHN/THWN TWO 600V #14 AWG THHN/THWN TWISTED TWO CONDUCTOR 300V #18 AWG FPL TW CABLE CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF CONDUIT SIZE MAXIMUM F 1/2" .12 SQUARE 3/4" .21 SQUARE 1" .34 SQUARE 1-1/4" .60 SQUARE 1-1/2" .82 SQUARE 2" 1.34 SQUARE FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM DIMENSIONS AREA .244 0.D. .0467 .210 0.D. .0346 .156 0.D. .0191 FROM THE TABLE FILL DIMENSION FROM THE WIRE. LL NCH NCH NCH NCH NCH INCH N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT. AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO 'CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. To THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 1 1 1 1 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT HTRI-D SIEMENS INTERFACE MODULE 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD r LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING DUCT SMOKE AD DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING Ec FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING L FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -OW SIEMENS 4S BOX W/ 1G RING CEILING L FIRE ALARM STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. Yc FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING WP MR FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) MULTI -VOLTAGE CONTROL RELAY SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -S17 -WP SIEMENS MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD MR -201 /C AIR PRODUCTS 4S BOX VERIFY IN FIELD 0 MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. 'r.b.U. F.B.. IN FIELD O JUNCTI❑N BOX F.B.O. A.F.F. ABOVE FINISHED FLOOR N/A B.❑. N/A PF VERIFY IN FIE L� NOTICE . A completed, signed, Tukwi N/A Without Comments N/A a Fire Department Pre-test Certificate must be presented spector prior to lent of Acceptance F.B,❑, FURNISHED BY OTHERS N/A /.--A /f ❑- As Note0 Red N/A Lw Ulu it ❑ Per The Attached Letter commencer Testing c N/A NOT APPLICABLE N/A ase plans have been r i4wed by The Tukwila jm Prevention Bureau for conformance with current city Aecet� if., cut pct to eFrorc and and Det Failure c U.O.N. UNLESS OTHERWISE NOTED N/A ctondards. ice issicns which do not IAorize violations of adR9tgd stanaaras and oro=nances. The responsibility for the igi totally with thee-decigncr. in a Re -in terminatil WP WEATHERPROOF DEVICE N/A «<« adequacy of rests editions, deletions or r ,igons to these drawinglsiarfer this date will void thi-s acceptance and will require a RED AS BUILT ADD OR CHANGE N/A resuLiiiitlatuf ieviaed diciwiligs fur subsequent approval. /A N/A N/A Final acceptance is subject to field test and inspection by GREEN AS BUILT REMOVE N/A Tne Tukwira r -ire Prevention Burea . /A N/A N/A (Date: O By: _� 'y7�� ,., . - AS BUILT N/A "� t', - =- ....p.w.ori NOTES TO CAD TUKWILA FIRE DEPARTM�� Please call: 575.4402 and give this job No.©� fg3t- and exact address for shut down or restoration approval, any Fire Alarm ection Systems. If test will result spection Fee and n of the testing. Ai JUN 12 200 Tukwila Fir /6O Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved '144 c#) ® 2 CC co 0' O C.9 C/) LLJ. uJ (n 0 LLJ t) O 0' 0' c0 (V \O 0 N >G La LC) LC) CV CV .O O CV J uJ RELEASE/REVISIONS REV. BY: 1 NVI DESCRIPTION SHOP DRAWINGS DATE 5/15/08 1(2 «<« SCALE: 1/8"=1' DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE:5/12/08 BACKROUND PLAN PROVIDED BY: .OB NUMBER: 1 SHEET FA -01 J THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE+ STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR S+ PREVIOUS ADDRESSABLE DEVIC END OF LINE DEVICE(3,6K 1/4W) o DUCT DETECTOR L❑CATION 1 0 0 SUPERVISED SWITCH ------ GROUND—CD r7 L) HTRI—R OSTATUS LED oo N.O. r- 0 COM 0 N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. O TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVIOUS ADDRESSABLE[ DEVICE TO NEXT ADDRESSABLE DEVICE L + NOTE 11 VOLTAGE MAX. - CURRENT MAX, - CONT. RES, MAX, - MAX. CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX, LINE SIZE - MIN. LINE SIZE- OUTLET SAMPLING----•\ TUBE `\ INLET SAMPLING TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE=NONE M U SIC }AC POWER SOURCE COMBINE ALL •SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE {I STOP IF LAST DEVICE (-) FROM XLS CONTROL PANEL OR {(+) PREVIOUS ADDRESSABLE DEVICE( RELAY CONTACTS (4.0A @ 125VAC) (4.0A @ 30VDC) 27 VDC 3,5 riA DURING POLLING 10 OHMS 200 FT, (18 AWG) 0,02uF 0,04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTI❑N. 0 O I' ml TB1 6 0 6 6 0 123456 TB2 c o cmc 654321 0 O END OF LINE DEVICE (3.6K 1/4W) / / SUPERVISED_ / / / SWITCH / GROUND ' N © HTRI—D OSTATUS LED CO 0 0 co O 1' NOT USED END OF LINE DEVICE 3.6K 1/4W) O \- UPERVISED l SWITCH NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC TOO T T 0 PAD -3 0 00 O INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 0 • • - 24K TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE ,NAC -4 NAC -3 NAC -2 NAC -1 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE + DEVICE LOOP NOT USED REMOTE DEVICE LOOP ! 0 0 0 0 FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY ('S' CABLE) FROM FACP <VOICE CIRCUIT) ('V' CABLE) 470 OHMS EOL TEM -1 0 oaf IP 8oREz 1 V) o CC000 0 0 CCC'CQ --- --- --- --- -- - TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE NOE (STROBE) SPEAKER 0) () (S ) STROBE v EARTH GROUND --.(+)TO NEXT DEVICE OR } _(-) STOP IF LAST DEVICE (+) ( ) STROBE SPEAKER (-) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY 80" A.F.F. O O O 4S DEEP BOX W/ 1-1/2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE TO NEXT DEVICE OR END OF LINE TO NEXT DEVICE OR END OF LINE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER�TIN TEMPERATU E: +32'F 0- C) TO 100 F 3S C) HUMIDITY: 9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR -� FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (-) DATA IN (+) > DEVICE IS USED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT DEVICE -t-- > (-) DATA OUT (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID —\ CEILING HARD LID SPEAKER SUPPORT TILE------ ------- BRIDGE LE --------------- BRIDGE 4' SQUARE DEEP BOX. WITH 1-1/2' EXTENSION N. CEILING MOUNTED N SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE=NONE JUNCTI❑N BOX • MOUNTED ON \\ CEILING FLEX \ ENF- / / / JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT 0 0 ; 1 TO NEXT DEVICE 0 0 CADDY BAR SMOKE DETECTOR ------ SMOKE DETECTOR MOUNTING SCALE=NONE SUSPENDED ILLUMINATED CEILING DO NOT INSTA L ADDRESSABLE 0 \MOAT NG DEVICES vNTIL DRE D OGVVIMED WITH DEVICES ADDRESS. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved r z c LU z 0.1 z rn co 0' FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z 4 DESCRIPTION SHOP DRAWINGS DATE co 0 in Lo °aaa« co co T T N ¢� I— 0 O D LU ZcpZ Z JJ CSC U= rrO or JJ Z co J CV () ~ V z Z a 0 Z 0 E (1 V J J F -- W J a SCALE: 1 /8"=1 DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: JOB NUMBER: SHEET FA -02 � ap 00 NORTH 42Fc.I.T2z2ES x 1!I 1 II_ 411' 4 X s' —. — , -- i— �— =+ : — 15 i r 1 l— y --- [ ]- L'a .t ^�E •P 4 I Iil —�-- y 1121 E SUNGLASS HUT 2115 WESTFIELD SOUTHCENTER MALL SCALE 10=1' FLAG NOTES FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,CSEE SIEMENS INSTALLATI❑N SUBMITTAL FOR L❑CATI❑N GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICAL CONTRACTOR. SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT, DO N0 NSTALL ADDRESSABLE IN T ATI NG DEVICES U\TIL DREP OGRAM M D WOTH EVICES ADDRESS. • Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved z co) a Z.4icxz F) c0 0' z 0 I -- c.9 z LLQ LLI 0 LLJ TEL. (206) 622-6545 RELEASE/REVISIONS T EN- C/) (/) 0 z �CALE: 1 /8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE:5/1 2/08 BACKROUND PLAN PROVIDED BY: \OB NUMBER: SHEET ( NORDSTROM 3 LEVEI_.S ! /! 71.275:f nn:^el rx.S m0� 4-6 Jr -0.000 CLRF mCS 4 LEVELS 250. 4U%57 ML :J\ SCUP gA00r2 Ce G0 merwyrirs 2 LEVELS 65,7)7,r PAnE.5 .Ir�[SCLwCC $009;3 R xYs llw•ex ,o:na /.iR'n ACOR 0,0:;: C00JA: UNP 0;01.r II100.4'f o r c NAL.\S Nt'1 2 Cti;aC• 005 ^wN.742 '•RR'"L::4 '*1n".2SS CAN.:: 'N WASH.:70N ,9040:0. ^1'S •' Va.1 [II(e ,HF P•;;nF[� YE•T':C NOT•.ER0000 057R S,00y:ICCS 3001E 00000 0.0 0000 PAC', :JJr. 545011• 1,590.9 01!,:,150 04.4004. yl'`CV4 F'`,iJ 0.:5 49.515>55 YE 1400 5•\; C'I. ::DC] a w 1 p_).• ICL' J c L iJ DIA r :U; Z 1 -1150'; 341 .I}G9 :0 i Y 5:41 00: 114 n1'Mii I'l # 11..00 F 0 -d''l 4.21 r=M»1 ' 551100105,5 R2A K:TChC:I G.AC 555,0 0J'O'lA IONS 00.1 a, "10 IAAG 0.015 (N lf'M 1111 01'!.!11 ,1-C141,1i NORTH SUNGLASS HUT 2115 WESTFIELD SOUTHCENTER MALL E%I.S1011.0 00:0 3 LEVELS 276.46`sr SCALE 1/32°=1' S,2V 2S42V - 2Si2V 30 C 15 15 EX RISER DIAGRAM SYSTEM CALCULATIONS SUNGLASS HUT 2115 SUNGLASS HUT 2115 FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations PROJECT: WESTFIELD SOUTHCENTER MALL Panel: SUNGLASS HUT 2115 Wire Resistance 1.62 Current Load: Standby: Alarm: CURRENT TOTAL= Current Load: Standby: Alarm: CIRCUIT: S1 QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Device Type Qty Amps Total Amps Total 64 Device Type Qty Amps Total Amps Total 0.62 HFP-11 SET -MC @30CD 0.0022 0.0022 0.0023 (WL * 2 ) * (R/ft) 0 SET -MC @75CD 175 0 AD2-P 1 0.0635 0.0635 0.064 0.064 0 Main System Board 1 0.03 0.03 0.030 0.030 HTR -R 2 0.009600 0.0096 0.021 0.042 SET -MC @15CD 1 Voltage Drop ( E) 0.064 0.064 SET-HMC-C@177CD HTRI-D 0 0.001600 0.0035 (E= 1* R) SET -MC @30CD 1 SET -HMC @135CD 318 0.098 0.098 ICP -B6 0.005 20.26 0 SET -HMC @185CD 445 SET -MC @75CD 0.175 (20.4 - E) 1 Z-MC@15CD 64 - 64 SET -MC @110CD 0 0.233 98 0 0 SET HMC-C@115CD 233 0 0.318 DEVICES= 3 TOTAL mA= 226 12 SET HMC-C@135CD 20.260142161 2261 0.318 W 0.0731 Amps 0.106 Amps SET HMC-C@185CD 0.445 PROJECT: Panel: SUNGLASS HUT 2115 Wire Resistance 2.58 Date: June 10,2008 ZR -MC @15CD 1 3.6 0.064 0.064 CIRCUIT: Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours ZR -MC @30CD QTY 0.098 Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total HCP 70.7V1/8 1.8 3.6 0.0015 Alarm Current Load: 0.106 Amps For 5 Minutes= 0.009 Amp -hours 0 0 0.03 Amps 0.256 Amps 0 25% Derating= 2.204 Amp -hours Total Device Load, Amps (I) 0.00 0 Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours (Total Cct Load) 0 0 0 Voltage Drop ( E) 0.00 0 0 0 (E= I * R) 0 Alarm Current Load: 0.256 Amps For 5 Minutes= 0.022 Amp -hours . EOL Voltage Total System Current Load: 0 2.204 Amp -hours 0 (20.4 - E) 0 0 0 25% Derating= 0.927 Amp -hours 0 Battery Pair to be Used: 12VDC Amp -hours 7AH DEVICES= 2 TOTAL mA= 3.6 14 191 20.396451981 3.6 Total System Current Load: 0.927 Amp -hours Battery Pair to be Used: 12VDC 1 Amp -hours 7AH BATTERY SIZING CALCULATION VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved FA -04. z ca 64.4 cz z FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS m Lu z a DESCRIPTION SHOP DRAWINGS cO 0 1� Y / 1.0 as 0 w C!)• O LLI 1.0 co CC co., I-Wcc ccp rr D I co Z Z Z C1)cCU� W cf)-JEQ C Q�� �w � z L�- 0 Z co - D ND Cf) V U LLI C!) y- C/) �CALE: 1 /8"=1 DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: \0B NUMBER: SHEET ----- Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: SUNGLASS HUT 2115 Wire Resistance 1.62 Date: June 10, 2008 CURRENT TOTAL= J 226 ---1 CIRCUIT: S1 QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 1 SET -MC @15CD 64 64 Total Wire Resistance (R) 0.62 1 SET -MC @30CD 98 98 (WL * 2 ) * (R/ft) 0 SET -MC @75CD 175 0 Total Device Load, Amps (I) 0.23 0 SET -MC @11OCD 233 0 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 Voltage Drop ( E) 0.14 0 SET-HMC-C@177CD 445 0 (E= 1* R) 0 SET -HMC @135CD 318 0 EOL Voltage 20.26 0 SET -HMC @185CD 445 0 (20.4 - E) 1 Z-MC@15CD 64 - 64 0 Z-mc@30CD 98 0 0 SET-MC-CW@110CD 233 0 DEVICES= 3 TOTAL mA= 226 12 191 20.260142161 2261 W WESTFIELD SOUTHCENTER Notification Appliance Circuit MALL Detail PROJECT: Panel: SUNGLASS HUT 2115 Wire Resistance 2.58 Date: June 10,2008 CURRENT TOTAL= 3.6 CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 70.7V1/8 1.8 3.6 Total Wire Resistance (R) 0.99 0 0 0 (WL*2)*(R/ft) 0 0 0 Total Device Load, Amps (I) 0.00 0 0 0 J (Total Cct Load) 0 0 0 Voltage Drop ( E) 0.00 0 0 0 (E= I * R) 0 0 0 . EOL Voltage 20.40 0 0 0 (20.4 - E) 0 0 0 0 0 0 DEVICES= 2 TOTAL mA= 3.6 14 191 20.396451981 3.6 VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved FA -04. z ca 64.4 cz z FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS m Lu z a DESCRIPTION SHOP DRAWINGS cO 0 1� Y / 1.0 as 0 w C!)• O LLI 1.0 co CC co., I-Wcc ccp rr D I co Z Z Z C1)cCU� W cf)-JEQ C Q�� �w � z L�- 0 Z co - D ND Cf) V U LLI C!) y- C/) �CALE: 1 /8"=1 DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: \0B NUMBER: SHEET TOLCO PIC#+. WO UNIvORSAL SWAY ORACS PITTIN3 may,. v.+: •.• ••,".'r" 1' SCM 40 TOLCO PII tNIVRRSAL SWAY DRAGS PITTN3 TOLCO PIPS CLAMP P13. 4A (24}" PIPS AND LARal PIG. 4 (211 PIP AND SMALLRR) LONG ITUDIN1bTL BRACE NTS " KWIIC DOLT D. MIN. NA Oft tge 4831 SO Mt ' 6' I e, LATERAL 1+3RACE 0 0 6 0 9 I d I (2" PIPS 4 SMALLER) NTS 1 . T'OICOPIC LNIVRRSAL SWAY DRAGS PI'rTIN3 *. „•r:, f.T ...t0.. tOLCO P13.1001 PAST CLAMP 44" ICWNC DOLT LATERAL i3R14CE (21/2" PIPE 4 LARGER) NTS ,4 SCO Mae 3* x 3.1/2 1.44 SCRRW POTS WOOD 1/4" Wit BOLT POR CONCRSTU 1/4 X 1 IIIK POR eARJOIS1 OR STOOL SRAM 3/0"x1 -t0 ALL THROAT, ROD MAX MIR 611.131.3 RDISTRANNT WHERE LENBtH CP ALL THREAD R 1'-10" ADD SECOND RESTRAIN' INE RESTRA INT IDET>AI IL SYMBOL =X NOTE: 1) SPACE WITH N 6" OF 14 HANGER EVERY 42'-0". 2) BRACING PER NFPA-13(200i ed.) SECTIONS 9.3.5.13.S, TABLE 9.3.5.S.S(c) AND 93.6-RESTAINT OF BRANCH LINES /�I-/111 fIGG� ff�O 23'-10" 3I -CI CORA OR 0/17#77 illar.71,1,1/711270/ 1 MALI CONCOURSE N 1 5I -6 ADJACENT TENANT SIRE SPRINKLER PIPINCa PLAN REVISIONS DESCRIPTION DATE SPRINKLER HEAD LEGEND: UL TDLCO FIG. 65 C -CLAMP PIPE SIZE I I/4' 1 I/2' 2 1/2' 3' 4' 6' 8' ROD DIA 3/8' 3/8' 3/8' 3/8' 3/8' 3/8' 3/8' I/2' 112' RETAINER STRAP, NUT THREADED ROD HILTI FIG LH OR TOLCO FIG 200 HANGER RING e . 04/2007 1 COSCO STANDARD HANGER I 2 TYPICAL HAIJTSR LI81I4. 1' AND t1+' P '1'-1' at W-0' ARP BLEVATICN) 11,0 PIPl1•1'44' SS PLAN POR ALL ODOR 1.11N31146 UL . HILTI KWIK BOLT TZ ANCHOR ICC REPORT #ESR -1917 MIN OF 3,000 PSI CONCRETE MIN .3 1/4' CONCRETE OVER MAX 3' METAL DECK 3/8' ANCHOR W/20# TORQUE: TENSION=395#,SHEAR=750# I/2' ANCHOR W/40# TORQUE: TENSION=440#,SHEAR=750# 1/2' MIN N 111 ROD COUPLING THREADED ROD PIPE ROD SIZE DIA I' 3/8' 1.25' 3/8' 1.5' 3/8' 2' 3/8' 2.5' '3/8' 3' . 3/8' 4' 3/8' 6' 1/2' 8' 1/2' BOLT IMBED LGTH DEPTH 7' 2 1/4' 7' 2 1/4' 7' 2 1/4' 7' 2 1/4' 7' 21/6' 7' 2 1/4' 7' 21/4'. 7' 2 1/4' 7 2 1/4' HILTI FIG LH OR • TOLCO FIG 200 HANGER RING 0 •04/2007 I COSCO STANDARD HANGER 1 13 MDLH HYDRAULIC DESIGN -REMOTE AREA SUNGLASS HUT #5665 - ENTIRE TENANT SPACE ORDINARY. HAZARD GROUP 2 .20 GPM/1500 S.F. K=5.6. 130 S.F. MAX: PER HEAD 12 SPRINKLERS DISCHARGING IN REMOTE AREA SYSTEM DEMAND: 903.7 GPM ® 73.9 PSI TOLCO FIG. 25 SURGE RESTRAINER TYPE 1 - FOR 1" AND 1-1/4" PIPE AND HANGER TYPE 2 - FOR 1-1/2" AND 2" PIPE AND HANGER TOLCO FIG. 25 IS DESIGNED TO BE USED ONLY WITH TOLCO BAND HANGERS FIG. 200 AND 2NFPA TO RESTRAIN THE UPWARD MOVEMENT OF PIPE AS IT OCCURS DURING SPRINKLER HEAD ACTIVATION OR SEISMIC ACTIVITY OPIGURE 25 SURGL RESTRAINER FOR STEEL OR CPVC PLASTIC PIPE FIRE SPRINKLER SYMBOL EENID c 111-0'I • LONGITUDINAL SWAY BRACE LATERAL SIUAY BRACE BRANCHLINE RESTRAINT PIPE HANGER PIPE ELEVATION AFTER FLOOR CEILING ELEVATION AFTER FLOOR HYDRAULIC NODE PENDENT/CONCEALED SPRINKLER SYMBOL S/N ORIFICE NPT K•FACT. HEAD FINISH PLATE FINISH TYPICAL DROP TO SPRINKLER HEAD GENVZ41.., NOTES 1 1/2" BRANCHLINE L__11.011 "FLEXHEAD" FLEXABLE DROP CORRUGATED STAINLESS STEEL BRAIDED HOSE ADJUSTABLE HUB MOUNTING BRACKET CEIUNG TYPICAL DROP TO SPRINKLER HEAD IN AC TILE CEILINGS 2. 3. 4. 5. 6. 1. S. 9. 10. 11. 11. 12. DESIGN AND INSTALLATION SHALL CONFORM TO NPA PAMPHLET 13 AND CITY OF TUKWILA FIRE DWPt. REQUIREMENTS. ALL MATERIALS. SHALL BE NEW AND U.I.. APPROVED. PIPE: ALL PIPE 2" AND LARGER TO BE SCHEDULE 40 BLACK STEEL. ALL PIPE 21" AND LARGER TO BE SCHEDULE I0. BLACK STEEL. FITTINGS: ALL FITTINGS (SCREWED AND GROOVED) AND GROOVED COUPLINGS TO BE STAR BRAND DUCTILE IRON. PAINTING OF PIPE AND PROTECTION OF SPRINKLER HEADS FROM PAINT IS BY OTHERS. ALL ELECTRICAL WIRING AND CONDIUT IS BY OTHERS. • ALL WELDING TO CONFORM WITH (AWS 010.9 AND WILL BE PERFORMED IN COSCO'S SHOP. IT 15 THE BUILDING OUJNERS RESPONSIBILITY TO KEEP ALL AREAS WITH WET SPRINKLER SYSTEMS HEATED TO. A MINIMUM 40 DEGREES FAHRENHEIT TO PREVENT FREEZING OF PIPES. OWNER IS RESPONSIBLE TO ASSURE THAT STRUCTURE AS IT 15 SHOWN ON THS CONTRACT DRAWINGS CAN t4DEQUA'tELY SUPPORT ALL FIRE SPRINKLER PIPING LOADS. NO.AUXILLIARY DEVICES OR ATTACHMENTS SHALL BE PROVIDED BY COSCO TO. SUPPLIMENT THE STRUCTURE TO ACCOMODATE FIRE SPRINKLER PIPING LOADS COSCO ASSUMES NO RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, POR THE CONDITION, PERFORMANCE OR CURRENT CODE COMPLIANCE OP THE EXISTING SYSTEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY COSCO FIRE PROTECTION. UNDERGROUND CONTRACTOR SHALL FLUSH THE UNDERGROUND AND PROVIDE COSCO WITH THE PROPER CERTIFICATE OP 'DOING SO BEFORE COSCO WILL CONNECT TO THE UNDERGROUND PIPE. SPRINKLER HEADS ARE DESIGNED TO BE IN CENTERLINE OP CEILING TILE (+1- I"). ALL DIMENSIONS ARE TO CENTERLINE OP PIPE. DOTTED LINES DENOTE EXISTING PIPE. • s /ut:Ut Comments PGI Leti:er it •• 1 nese P;'1'.•:,'".•'-2 i �,,,1 .F_s Fire tl :Y3,.1:; II 1-•� ?,y, :'I ; e:1• TEMP. QUAN. RELIABLE MODEL G4A QR CONCEALED PENDENT R5415 1/2' 1/2' 5.6 BR WH 165° • 12 APPROVALS BY: CITY OF TUKWILA TOTAL SPRINKLERS THIS SHEET 12 EAST RISER ROOM -PLAN VIEW St3t1dc:1,..:. "Fadeq-: r• ,, r AdditionT, 3' .,I i, this dEA,3 L,,,{11 „'y 4` .ca of ,/11'•30 i.i' .:,,r` K3!' C.It}`AtLi ,L;i'1t r;i: plovai. ,, CSUaC"illt i•` ti � l - •t.s:;t: ct to bold test and inspection by I Final acc�p�T�ce i;�Y�., The. Tukwila Fife Frcveniion Bureau. . TUKWILA FIRE DEPARTMIrN', Please call: 575.4402 and give this job No.2- - �•.(P� and exact address for shut= a:,v4r1 or restjration approval EV OGl dSLCE Weld stamps mu 'I:be inspected before pipe is hung. P� not paint piping prior to hydrostatic test approval. 1Date:!_LiL___ =•S• 00®• . ••® 00 0•.• • 0 00 0 a ••0 .O•. COSCO .Fire Protection FIRE PROTECTION AND LIFE SAFETY SPECIALISTS WASHINGTON OFFICE 15000 Woodinville -Redmond Rd NE License No: Woodinville, Washington 98072 COSCOFP11ONM call (425) 686-8300. • fax (425) 827-4784 SAN DIEGO • LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE Www.coscoftre.com O S By: FILE COPY r , ••ria R:ci.uer. l 399-‘77- "K, • NORDSTROM •9y. TENANT SF'ACE- f FUM -'U,' 51AIL SUNGLASS HUT #5665 633 SOUTHCENTER MALL SUITE 2846 TUKWILA, WA • . . CONTRACT WITH: TURNER BUSCH CONSTRUCTION 214 STATE STREET HACKENSACK, NJ 07601 I woattteta, LLC ADDRRSS PTA" NOB • Tukwila Fire z&' od s SWING TITLE FIRE SPRINKLER TENENT IMPROVEMENT 14/ s�l� MVO 'AS OF: Apr 10, LKS itYril 0 Southcont°r 2., DATE : 05-29-08 SCALE : 1/2"=1'-0" DRAWN BY : T.N.RHODES JOB 5 KS 7946 SHIT NO. l ofl