PP - 2416 SOUTHCENTER MALL - UNKNOWN TENANT - PERMITS AND PLANS
2416 SOUTHCENTER MALL ASSOCIATED PERMITS 11-F-095 08-F-276 11-S-088 11-S-081 08-S-303 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Vanilla Box 2416 Southcenter Mall Permit No.: 08-S-303 Date: June 11, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 '/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • These conditions apply to any sprinkler piping exposed as necessary to accomplish the permitted scope of work. All references are NFPA 13, 2007 Edition. FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Etiquette 2416 Southcenter Mall Permit No.: 11-S-088 Date: April 26, 2011 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ` of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. A! • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 20 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2010 Edition. III, Hydraulic Summary Job Number: KS0407 Report Description: Ordinary Group II Job:' Job Number Design Engineer KS0407 Adam Kanter Job Name State Certification/License Number Vanilla Shells 2416 WESTESF136QF Address 1 1 AHJ Southcenter Mall City of Tukwila Address 2 Job Site Southcenter Mall City State Zip Code Drawing Name Tukwila Wa 98188 FP-1-2416.cad System _ - . - 1 Remote Atea(s) Most Demanding Sprinkler Data Occupancy 5.6 K -Factor 20.00 at 12.755 Ordinary Group II Hose Allowance At Source Density Area of Application 250.00 . 0.20gpm/ft2 777.99ft2 (Actual 777.99ft2) Additional Hose Supplies PP Number Of Sprinklers Calculated Coverage Per Sprinkler Node Flow(gpmZ 12 100.00ft2 Total Hose Streams_. G' 250.00 n ii System Flow Demand Total Water Required (Including Hose Allowance) 258.17 ' 508.17t_, I/1 s •"�_ Maximum Pressure Unbalance In Loops I r L. 1111 0.000 r,, �' `��' 1._ y Maximum Velocity Above Ground 13.71 between nodes 26 and 12311747/r* IF Maximum Velocity Under Ground V. 0.98 between nodes 1 and 366 4161111186 Volume capacity of Wet Pipes i Volume capacity of Dry Pipes 3415.34gal 0.84ft3 Supplies . . Hose Flow Static Residual Flow Available @ Total Demand Required Safety Margin Node i (gpm) (psi) (psi) (gpm) l (psi) (gpm) (psi) (psi) 1 250.00 140.000 1 20.000 10900.00 139.587 508.17 59.971 79.616 GQrjtractor _ _ Contractor Number Contact Name Contact Title KS0407 Adam Kantner Project Manager Contractor Name Phone Extension Western States Fire Protection 425.881.0100 Address 1 FAX 7102 180th Ave Ne, Suite A-105 485.736.9032 Address 2 E-mail City State Zip Code Web -Site Redmond WA 98052 (bl ©M.E.P.CAD, Inc. 4.0 AutoSPRINK® VR5 v5.2.6 06/03/2008 11:30:50AM Page 1 11. -Summary Of Outflowing Devices Job Number: KS0407 Report Description: Ordinary Group II Device Actual Flow (gpm) Minimum Flow (gpm) K -Factor (K) Pressure (psi) Sprinkler 112 22.61 20.00 5.6 16.304 Sprinkler 111 22.57 20.00 5.6 16.240 Sprinkler 110 22.51 20.00 5.6 16.154 Sprinkler 109 21.89 20.00 5.6 15.279 Sprinkler 108 21.85 20.00 5.6 15.224 Sprinkler 102 20.36 20.00 5.6 13.224 Sprinkler 107 21.48 20.00 5.6 14.711 Sprinkler 106 21.44 20.00 5.6 14.659 c Sprinkler 101 20.00 20.00 5.6 12.755 Sprinkler 105 21.31 20.00 5.6 14.477 Sprinkler 104 21.11 20.00 5.6 14.216 Sprinkler 103 21.04 20.00 5.6 14.115 c Most Demanding Sprinkler Data ©M.E.P.CAD, Inc. M AutoSPRINK® VR5 v5.2.6 06/03/2008 11:30: 53AM Page 2 2 Node Analysis Job Number: KS0407 Report Description: Ordinary Group 11 Node Elevation(Foot) Fittings Pressure(psi) 1 Discharge(gpm) 16 16-6 fEE(4-6) 33.327 17 17-3 fEE(4-6) 33.163 18 17-3 P0(26-4) 33.446 20 18-6 fE(8-111/2) 33.491 26 17-11 P0(8-0) 29.626 27 17-11 2P0(8-0) 29.642 28 17-11 2P0(8-0) 29.743 123 16-6 P0(5-0) 20.893 124 16-6 P0(5-0) 21.026 131 16-6 PO(5-0) 21.105 138 16-6 P0(5-0) 19.487: 139 16-6 P0(5-0) 19.620 147 16-6 • PO(5-0) 20.068 157 14-11 P0(5-0) 19.158 158 , 14-11 1 P0(5-0) 19.289 166 14-11 P0(5-0) 19.791 171 14-11 E(2-0) 19.702 174 14-11 E(2-0) 19.187 191 14-11 E(2-0) 19.041 188 17-10 36.304 318 -16-1 2P0(43-1) 51.918 ' 324 -16-1 52.345 366 -12-4 BFP(-5.000) 55.732 112 12-0 Spr(-16.304) 16.304 22.61 111 12-0 Spr(-16.240) 16.240 22.57 110 12-0 Spr(-16.154) 16.154 ' 22.51 109 12-0 Spr(-15.279) 15.279 15.224 21.89 108 12-0 Spr(-15.224) 21.85 102 1 12-0 ' Spr(-13.224) 13.224 14.711 1 20.36 107 12-0 Spr(-14.711) 21.48 106 12-0 Spr(-14.659) 14.659 • 21.44 • 101 • 12-0 , Spr(-12.755) 12.755 14.477 ' 20.00 21.31 105 15-0 Spr(-14.477) 104 15-0 Spr(-14.216) 14.216 21.11 103 15-0 Spr(-14.115) 14.115 21.04 1 -22-0 S 59.971 , 258.17 M.E.P.CAD, Inc. 41 AutoSPRINK® VR5 v5.2.6 06/03/2008 11:30:57AM Page 3 1 r Hydraulic Analysis Job Number: KS0407 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Length Summary Length Downstream Upstream Elevation Discharge K -Factor Pt Pn Fittings. Eq. Total Qi Route 1 DR 1.049 Q=20.00 7.42 C=120 0.130131 50-10 Pf 8.304 101 12-0 q=20.00 K=5.6 12.755 Spr(-12.755) 13-0 Pe -1.268 166 14-11 19.791 4E(2-0), P0(5-0) 63-10 Pv BL 1.610 0=41.31 6.51 C=120 0.061811 11-7 Pf 0.963 166 14-11 19.791 4-0 Pe -0.686 147 16-6 20.068 2LtE(2-0) 15-7 Pv BL 1.610 Q=61.67 9.72 C=120 0.129738 8-0 Pf 1.038 147 16-6 20.068 Pe 131 16-6 21.105 8-0 Pv BL 1.610 0=84.18 13.27 C=120 0.230695 28-1 Pf 9.251 131 16-6 21.105 12-0 Pe -0.614 28 17-11 29.743 2LtE(2-0), PO(8-0) 40-1 Pv CM 4.260 0=258.17 5.81 C=120 0.016049 140-7 Pf 2.966 28 17-11 29.743 44-3 Pe 0.618 16 16-6 33.327 2E(13-2), 2fE(8-11 Y2) 184-9% Pv RN 4.260 Q=258.17 5.81 C=120 0.016049 1-0Y Pf 0.161 16 16-6 33.327 fEE(4-6) 9-0 Pe -0.325 17 17-3 33.163 fEE(4-6) 10-0% Pv CM 4.260 0=258.17 5.81 C=120 0.016049 17-7% Pf 0.283 17 17-3 33.163 ' Pe 18 17-3 33.446 17-7% Pv RN 4.260 0=258.17 5.81 C=120 0.016049 1-3 Pf 0.586 18 17-3 33.446 P0(26-4) 35-3%cPe -0.542 20 18-6 33.491 fE(8-11 Y2) 36-6'/2 Pv CM 4.260 0=258.17 5.81 C=120 0.016049 139-5 Pf 2.525 20 18-6 33.491 17-11, Pe 0.289 188 17-10 36.304 2fE(8-11%) 157-4Pv CM 6.357 0=258.17 2.61 C=120 0.002285 180-10 Pf 0.910 188 17-10 36.304 217-5Yz Pe 14.704 318 -16-1 51.918 12fE(12-7), BV(12-7), fE(10-0), 398-3% Pv CV(40-3), GV(3-9%) BL 8.329 0=258.17 1.52 C=120 0.000613 17-10 Pf 0.427 318 -16-1 51.918 P0(43-1) 678-3$ Pe -0.000 324 -16-1 52.345 2fE(16-0), 14P0(43-1) 696-1% Pv MS 10.020 0=258.17 1.05 C=120 0.000249 20-2 Pf 5.022 324 -16-1 52.345 67-0 Pe -1.635 366 -12-4 55.732 3LtE(16-0), BV(19-0), BFP(-5.000) 87-2 Pv UG 10.400 0=258.17 0.98 C=140 0.000156 112-10% Pf 0.039 366 -12-4 55.732 137-1 Y2 Pe 4.200 1 -22-0 59.971 4LtE(25-6), 2EE(17-6Y2), S 250-0 Pv Route 2 DR 1.049 0=20.36 7.56 C=120 0.134546 52-5 Pf 8.799 102 12-0 q=20.36 K=5.6 13.224 Spr(-13.224) 13-0 Pe -1.955 147 16-6 20.068 4E(2-0), PO(5-0) 65-5 Pv Route 3 DR 1.049 Q=21.04 7.81 C=120 0.142918 26-2 Pf 4.885 103 15-0 q=21.04 K=5.6 14.115 Spr(-14.115) 8-0 Pe 0.041 191 14-11 19.041 4E(2-0) 34-2 Pv BL 1.610 0=21.04 3.32 C=120 0.017743 6-7 Pf 0.116 191 14-11 19.041 Pe 157 14-11 19.158 6-7 Pv BL 1.610 Q=42.52 6.70 C=120 0.065203 11-7 Pf 1.016' 157 14-11 19.158 4-0 Pe -0.686 138 16-6 19.487 2LtE(2-0) 15-7 Pv BL 1.610 0=64.41 10.15 C=120 0.140587 10-0 Pf 1.406 138 16-6 19.487 Pe 123 16-6 20.893 10-0 Pv BL 1.610 0=87.02 13.71 C=120 0.245304 26-1, Pf 9.347 123 16-6 20.893 12-0 Pe -0.614 26 17-11 29.626 2LtE(2-0), PO(8-0) 38-1 Pv CM 4.260 0=87.02 1.96 C=120 0.002146 7-7 Pf 0.016 26 17-11 29.626 Pe 27 17-11 29.642 7-7 Pv CM 4.260 0=173.99 3.92 C=120 0.007734 13-0 Pf 0.101 27 17-11 29.642 Pe 28 17-11 29.743 13-0 Pv Q. Route 4 DR 1.049 0=21.11 7.84 C=120 0.143858 26-4 Pf 4.939 104 15-0 q=21.11 K=5.6 14.216 Spr(-14.216) 8-0 Pe 0.032 174 14-11 19.187 4E(2-0) 34-4 Pv ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 06/03/2008 11:31:01 AM Page 4 Hydraulic Analysis Job Number: KS0407 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K -Factor Upstream Pt Pn Fittings Eq. Length Summary Total Length BL 1.610 0=21.11 3.33 C=120 0.017859 5-81,4 Pf 0.102 174 14-11 158 14-11 19.187 19.289 Pe 5-81,4Pv BL 1.610 0=42.55 6.71 C=120 0.065308 11-7 Pf 1.018 158 14-11 139 16-6 19.289 19.620 2LtE(2-0) 4-0 Pe -0.686 15-7 Pv BL 1.610 0=64.41 10.15 C=120 0.140577 10-0 Pf 1.406 139 16-6 124 16-6 19.620 21.026 Pe 10-0 Pv BL 1.610 0=86.97 13.71 C=120 0.245058 25-8 Pf 9.230 124 16-6 27 17-11 21.026 29.642 2LtE(2-0), Z, P0(8-0) 12-0 Pe -0.614 37-8 Pv Route 5 DR 1.049 0=21.31 7.91 C=120 0.146306 27-6 Pf 5.193 105 15-0 q=21.31 K=5.6 171 14-11 14.477 19.702 Spr(-14.477) 4E(2-0) 8-0 Pe 0.032 35-6 Pv BL 1.610 0=21.31 3.36 C=120 0.018163 4-10% Pf 0.088 171 14-11 166 14-11 19.702 19.791 Pe 4-101,4Pv 4, Route 6 DR 1.049 0=21.44 7.96 C=120 0.148004 28-9% Pf 5.889 106 12-0 q=21.44 K=5.6 158 14-11 14.659 19.289 Spr(-14.659) 3E(2-0), P0(5-0) 11-0 Pe -1.259 39-9'/z Pv Route 7 DR 1.049 0=21.48 7.97 C=120 0.148486 27-5 Pf 5.707 107 12-0 q=21.48 K=5.6 157 14-11 14.711 19.158 Spr(-14.711) 3E(2-0), P0(5-0) 11-0 Pe -1.259 38-5 Pv Q. Route 8 DR 1.049 0=21.85 8.11 C=120 0.153276 304' Pf 6.342 108 12-0 q=21.85 K=5.6 139 16-6 15.224 19.620 Spr(-15.224) 3E(2-0), PO(5-0) 11-0 Pe -1.946 41-4'% Pv iwo Route 9 DR 1.049 0=21.89 8.13 C=120 0.153789 29-0 Pf 6.154 11-0 Pe -1.946 40-0 Pv 109 12-0 q=21.89 K=5.6 138 16-6 15.279 19.487 Spr(-15.279) 3E(2-0), PO(5-0) Route 10 DR 1.049 0=22.51 8.36 C=120 0.161913 31-7 Pf 6.897 11-0 Pe -1.946 42-7 Pv 110 12-0 q=22.51 K=5.6 131 16-6 16.154 21.105 Spr(-16.154) 3E(2-0), P0(5-0) v Route 11 DR 1.049 0=22.57 8.38 C=120 0.162710 30-4% Pf 6.732 11-0, Pe -1.946 41-4% Pv 111 12-0 q=22.57 K=5.6 124 16-6 16.240 21.026 Spr(-16.240) 3E(2-0), PO(5-0) .i Route 12 DR 1.049 0=22.61 8.39 C=120 0.163308 29-0 Pf 6.535 11-0 Pe -1.946 40-0 Pv 112 12-0 q=22.61 K=5.6 123 16-6 16.304 20.893 Spr(-16.304) 3E(2-0), P0(5-0) Equivalent Pipe.Lengths of Valves and Fittings (C=120 only) ; I C Value:Multiplier 0 Actual Inside Diameter 4.87 ) Value Of C 100 Multiplying Factor 0.713 130 1.16 140 150 1.33 1.51 = Factor ( Schedule 40 Steel Pipe Inside Diameter �A ©M.E.P.CAD, Inc. irjAutoSPRINK® VR5 v5.2.6 06/03/2008 11:31:01 AM Page 5 1111 Hydraulic Analysis Pipe Type Diameter Job Number: KS0407 Report Description: Ordinary Group II Flow Velocity HWC Friction Loss Downstream Elevation Upstream 'Pipe Type Legend Discharge K -Factor Pt Pn Fittings Length Pressure Eq. Length Summary Total Length Units Legend Fittings Legend AO Arm -Over Diameter BL Branch Line Elevation CM Cross Main Flow DN Drain Discharge DR Drop Velocity DY Dynamic Pressure FM Feed Main Length FR Feed Riser Friction Loss MS Miscellaneous HWC OR Outrigger Pt RN Riser Nipple Pn SP Sprig Pf ST Stand Pipe Pe UG Underground Pv Inch Foot gpm gpm fps psi Foot psi/Foot Hazen -Williams Constant Total pressure at a point in a pipe Normal pressure at a point in a pipe Pressure loss due to friction between points Pressure due to elevation difference between indicated points Velocity pressure at a point in a pipe ALV AngV b BaIV BFP BV C cplg Cr CV De1V DPV E EE Eel Ee2 FDC fE fEE flg FN fT g GIoV GV Hose HV Hyd LtE mecT Noz P1 P2 PIV PO PrV PRV red S sCV Spr St T Tr U WirF WMV z Alarm Valve Angle Valve Bushing Ball Valve Backflow Preventer Butterfly Valve Cross Flow Tum 90° Coupling Cross Run Check Valve Deluge Valve Dry Pipe Valve 90° Elbow 45° Elbow 11W Elbow 22W Elbow Flow Device Fire Department Connection 90° FireLock(TM) Elbow 45° FireLock(TM) Elbow Flange Floating Node FireLock(TM) Tee Gauge Globe Valve Gate Valve Hose Hose Valve Hydrant Long Turn Elbow Mechanical Tee Nozzle Pump In Pump Out Post Indicating Valve Pipe Outlet Pressure Relief Valve Pressure Reducing Valve Reducer/Adapter Supply Swing Check Valve Sprinkler Strainer Tee Flow Turn 90° Tee Run Union Wirsbo Water Meter Valve Cap © M.E.P.CAD, Inc. �•,���AutoSPRINK® VR5 v5.2.6 06/03/2008 11:31:01 AM Page 6 dna Hydraulic Graph Job Number: KS0407 Report Description: Ordinary Group II Supply at Node 1 150 Static Pressure 140.000 135 120 105 90 .N a LIE 75 rn to m a 1,508.17 with hose streams 60 -258.17 @ 59.971 45 System demand curve 30 1 10900.00 @ 20.0001 15 111 11 11 1 1 1 1 1 I) 1 1 1 1 (I 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 ( 1 1 1 1 1 1 1 1 I I I 1 1 I I I I 1 1 1 1 1 1 I 1 1 1 ( 1 1 1 1 1 0 /7111111111111 T1002200 3300 4.40011000 5500 6600 7700 8800 9900 Water flow, gpm Hydraulic Graph Supply at Node 1 Static Pressure 140.000 Residual Pressure 10900.00 @ 20.000 Available PressureTime of Test 139.587 @ 508.17 System Demand 258.17 @ 59.971 System Demand (Including Hose Allowance) 508.17 @ 59.971 ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 06/03/2008 11:31:10AM Page 7 111 Flow Diagram _(Top View) Job Number: KS0407 Report Description: Ordinary Group II (�c, ©M.E.P.CAD, Inc. 411 AutoSPRINK®VR5 v5.2.6 06/03/2008 11:31:14AM Page 8 04/18/2011 /2011 12:33 4254818695 CROWN FIRE L CROWN FIRE PROTECTION, INC. 221 Company Subjec 4.18.11 Fire Prevention Bureau Tukwila Fire Department/ Don Tomaso Dema Permit Number of Pages (Including Cover 0 Urgent From 1 For Review d Please Comment Jessica Robinson Fax No. PAGE 01/01 206.575.4439 TL'tc-''vILA FIRE. DEPAR', Please call 20,5-575-4'!1;./ give this FireOil: an,.! exact address for s �i down or restoration approval. ❑ Please Reply PH:425.481.7669 FX:425-481.8695 Please provide a demo permit to shorten (2) sprinkler drops that are in the way of the new construction at the Etiquette project at 2416 Southcenter Mall. The building permit is 010246. Please let us know if you have any questions. Thanks P.O. BOX 12113 MILL CREEK, WA 980$2 P11: 425.481,7669 -- — — _ — FX: 425. 481.8695 • DDIT N Without Comments O As Noted in Red D Per The Attached Letter iese plans have ben reviewed by The Tukwila Fire •:vention Bureau for (7)nfo rriance with current City ndards. Accepr ,,; ;::: } pit r..i, to eiTors and Llissions which ,:,i,,, ;u`:: iIC t?{'ize'violations of adopted ndards and ordin,anc:<. The r . ponsibility for the equacy of design :'::£:t:_ totally with d;e designer, ,iidltions, deletions i;'?i::ion i':) ghee drawings after •'nis date will void rhl:; 'Mll require a «•esubmittai or revised dravlinus for sub5equent approval. Final acceptance is subject to field test and Inspection by The Tukwila Fire Prevention Bureau. Date: 5- Lf -1 ( By: 4 F ,,R i"+ 77-V• RTMENT ...LLL.. Iv.'L.. tl�a. Plot: 4s.:a E ° . ,!.375-407 and give tris No. it -� oar and c .W. .lu : 7 :l $i shut- down or ;" � ; wi cry i pprovaL NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and SHEET \UV3E SHE -T TITLE SYSTEV I\FOMATION FRE ALAN SYSTE SHEET INDEX WISE SCHEDULE A\ CO\DUIT FILL C FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. QUANTITY EX EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX • • MOUNTING HEIGHT S FIRE ALARM SPEAKER STROBE EX (EXISTING) SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1 /2 EXTN �EX FIRE ALARM STROBE (EXISTING) ZR -MC -CW SIEMENS 4S DEEP BOX CEILING A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A co 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 m 0 C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V' SPEAKER CIRCUIT- RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. DESCRIPTION ,SHOP DRAWINGS DATE f 04/26/11 WIRE DESIGNATION SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V' SPEAKER CIRCUIT- RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. SYMBOLS LEGEND 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 126061 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 'Mr°' i JOHNNY �FC16J ISHA 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. SARKU 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. RETAIL SUSHI rro SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END 23. RETAIL NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED WIRE DESIGNATION GENERAL NOTES ROOF ROOF ROOF' ETIQUETTE (2416) TERRACE PAID I.1HY - 2 2011 TUKWILA FIRE Yko- SCALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE:04/26/1 1 \OB NUMBER: SITE PLAN SHEET FA -01 Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved I\J BACKROUND PLAN PROVIDED BY: ck 17•••• • ••••.: r•••••••• EX ... Z.; ............. . ...... ... S1-1 95cd V-1 S )Z,N EX S1-2 15cd TO FACP EX "'• t • 7. •.• „ ...... ' S1-5 75cd V-4 S,S' V,V S1-3 95cd V-2 EX 61-4 95cd V-3 EX ....................................................................................................................................................... EX A — • ................................................... •.• • , , f . . . FIRE ALARM SYSTEM PLAN •-•:••• HARD LID CEILING FLAG NOTES: RELOCATE EXISTING SPEAKER STROBE TO NEW LOCATION INDICATED (BELOW DROP CEILING). SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX 7----- WITH 1-1/2' EXTENSION \\\\\\ CEILING MOUNTED SPEAKER/STROBE SPEAKER STROBE MOUNTING DETAIL P0 CO 0 \ 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS IREV. BY: I 0 m 0 DESCRIPTION SHOP DRAWINGS DATE 04/26/11 2 <<<<< u_ 'ALE: 3/16:=1'0" *N\ DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE:04/26/11 BACKROUND PLAN PROVIDED BY: .J013 NUMBER: —) r SHEET FA -02 Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved i EST LI! VAN 1 LLA SUITE 241 RE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET \UM3ESHEET TITLE FA -01 SYSTEM I\FOvATIO\ FA -02 TYPICAL DETAILS - WRI\G A\� MOU\TING FA -03 FRE ALARM SYSTEM FLOG DLA\ FA -04 SYSTEM CALC U LATI O \S r GE\EAL), �ISE� SITE PLA\ WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C, AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEVIBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 1 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM SDD-C REMOTE ANNUNCIATOR SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD B Q LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING D DUCT SMOKE DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD 0 HEAT DETECTOR (ADDRESSABLE) HFPT-11 w/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM Ric FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM STROBE (CEILING MOUNT) SET -HMC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING L FIRE ALARM STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. PC FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. B �W P FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) SET -W SIEMENS. 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR MULTI -VOLTAGE CONTROL RELAY MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. r... INFILD FA JBOX FIRE ALARM TERMINAL CABINET JUNCTI❑N BOX F.B.O. F.B.O. N/A TE VERT IN FI LD VERT IN FI LD WIRE DESIGNATI❑N SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D H P S A V I X UD UI M B DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) ANNUNCIAT❑R TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) RED (JACKET) REMOTE INDICATI❑N LIGHT TWO #18 FPL/FPLR RED (JACKET) LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) A.F.F. CONDUIT FILL CHART N/A NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C, AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEVIBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 1 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM SDD-C REMOTE ANNUNCIATOR SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD B Q LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING D DUCT SMOKE DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD 0 HEAT DETECTOR (ADDRESSABLE) HFPT-11 w/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM Ric FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM STROBE (CEILING MOUNT) SET -HMC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING L FIRE ALARM STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. PC FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. B �W P FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) SET -W SIEMENS. 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR MULTI -VOLTAGE CONTROL RELAY MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. r... INFILD FA JBOX FIRE ALARM TERMINAL CABINET JUNCTI❑N BOX F.B.O. F.B.O. N/A TE VERT IN FI LD VERT IN FI LD REMOVE BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A OTICE 413 • '44 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 d, signed, TukwilE RELEASE/REVISIONS REV. BY: EGH i VVRI KR9lLVitUilCtil* A.F.F. ABOVE FINISHED FLOOR N/A N/A As Noted Irci,Rd N/A ❑ Per The Attached Letter F.B.❑. FURNISHED BY OTHERS N/A 'Iciest plans have been re>l fed by The Tukwila FWA Prevention Bureau for conformance with current city N/A NOT APPLICABLE N/A standdrds. Acceptdnce is eabi�,;l lu ettuts and ohlIrsiions which do not auttli6tize violations of adop iA standards and ordinances. The responsibility for the U.D.N. UNLESS OTHERWISE NOTED N/A adequacy of design rests totally with the designer. At}difons, deletions or revii�k s to these drawings t� this date will void thi.s.acceptance and will require a r A complete WP WEATHERPROOF DEVICE N/A resubmittal of revised drawings tor subsequent approval. N/A N/A N/A Final acceptance is subject to field test and inspection by Fire Dei Certificate RED AS BUILT ADD OR CHANGE N/A The Tukwila Fire Prevention Bureau. N/A N/A • N/A Date: 0 By: v to the ] commencE Testing ---- AS BUILT N/A ._._ . . ' and DE REMOVE BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A OTICE 413 • '44 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 d, signed, TukwilE RELEASE/REVISIONS REV. BY: EGH DESCRIPTION SHOP DRAWINGS DATE 05/20/2008 2 CCCCC artment Pre-test must be presentedF Inspector prior to C!) ment of Acceptances of any Fire Alarm tection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. fUKWILA FIRE DEPART E. 'i , Please call: 575-4407 and give this job No. and exact address for shut, Lown or restoration approval. Copyright 2006 by Guardian Security Systems, exam amm,41 2008 Tukwila Fire zoo/� /75- Inc. x'75Inc. All Rights Reserved SCALE: 1 /8"=1' DRAWN BY: E.HAMERSKI DESIGNED BY: R.VEZZANI DATE:05/20/2008 BACKROUND PLAN PROVIDED BY: .10B NUMBER: C SHEET FA -0 1 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT WE SCALE COMBINE ALL SHIELDS AND IS❑LATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE �+ STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR -�-i- PREVIOUS ADDRESSABLE DEVICE' END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH DUCT DETECTOR LOCATI❑N GROUND-- _r> CV r') L() 0 NN HTRI-R • STATUS LED 00 ( N.0 COM N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE DEVICE TO NEXT ADDRESSABLE DEVICE NOTE 1: VOLTAGE MAX, - CURRENT MAX. - CONT. RES, MAX. - MAX. CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX, LINE SIZE - MIN, LINE SIZE- OUTLET SAMPLING ---- TUBE INLET SAMPLING— . TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE=NONE MUSIC L -AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE f(+) STOP IF LAST DEVICE `(-) FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVICE (-) RELAY CONTACTS (4,OA @ 125VAC) (4.OA @ 30VDC) 27 VDC 3.5 riA DURING POLLING 10 OHMS 200 FT, (18 AWG) 0,02uF 0.04uF 14 AWG 18 AWG NOTE 2: ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTI❑N. 0 I00I TB1 SSOGOG 123456 HCP TB2 - +- G G G 654321 J 0 \N) 1_ END OF LINE DEVICE r (3.6K 1/4W) 1- 1-7% 1-% SUPERVISED__-__/ SWITCH GROUND CV Co1.0 _ HTRI-D *STATUS '--'STATUS LED CO NOT USED ------ END OF LINE DEVICE `(3.6K 1/4W) 0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 CND N AC n 0 0 0 0 PAD -3 0 0 OC 0 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 102 24K n + TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE NAC -4 2 NAC -3 NAC -2 NAC -1 UPERVISED SWITCH ( FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE + DEVICE LOOP NOT USED REMOTE DEVICE LOOP 0 0 0 FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY C'S' CABLE) FROM FACP (VOICE CIRCUIT) ('V' CABLE) 470 OHMS III EOL 1.1 9 9 9 TEM -1 0 r ~ 0 0 bo �z giti 00 0 TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE N06E (+) ( ) STROBE SPEAKER (+) (,) (STROBE(-) EARTH GROUND 0 ..(+)TO NEXT DEVICE OR } >(-) STOP IF LAST DEVICE (+) (_) STROBE SPEAKER (+) (-) 0 SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY RI 0 807 A.F.F. 4S DEEP BOX W/ 1-1/2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE=NONE TO NEXT DEVICE ❑R END OF LINE TO NEXT DEVICE ❑R END OF LINE NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER,11N TEMPERATU +32' F (0' C) E TO 100' F 38' C) HUMIDITY: O-9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR —> FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE r DATA IN( )>- it DATA IN (+) > DEVICE IS USED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT DEVICEF > ( ) DATA OUT > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID —\ CEILING HARD LID SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSI❑N \._ CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE=NONE JUNCTI❑N BOX MOUNTED ON CEILING FLEX \ JUNCTI❑ MOUNTED A( CEILING SU N BOX iAINST PP❑RT 0 0 0 0 TO NEXT DEVICE CADDY BAR SMOKE DETECTOR ---- SMOKE DETECTOR MOUNTING SCALE=NONE SUSPENDED ILLUMINATED CEILING DO NOT ADDRESS DEVICES PREPROG DEVICES I\ST BLE Nl�I L NDMI, TM R A iV E D W DDIESS. T Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved rn 0o O DE Z_ (/) W J UJ C) O W r--- LU ` FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: EGH DESCRIPTION SHOP DRAWINGS w 105/20/20081 I- 0 z z 52 0 tV � W CO Cly w cO //�/� 1:1-1-1C9z VJ ZZ> < z ow < IT -1 �w cc (1) ■ (/) W w U SCALE: 1/8"=1' DRAWN BY: E.HAMERSKI DESIGNED BY: R.VEZZANI DATE:05/20/2008 BACKROUND PLAN PROVIDED BY: %OB NUMBER: SHEET C FA -02 EOL—S1 20.19V 2S,2V 2I 2S,2V n, X75 C 121 V i'. NORTH VANILLA SUITE 2416 WESTFIELD SOUTHCENTER MALL SCALE 118°=1' 'JAG IO ES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS.(SEE SIEMENS INSTALLATI❑N SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR, SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLATOR FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT, DO NO INSTAL ADD-ESSABLE INHT ATIN DEVICES U\TIL PREPROGRAMMED WI—H EVICES ADDRESS. G Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS J REV. BY: 0 w DESCRIPTION SHOP DRAWINGS DATE 105/20/2008 9 aaCCa W LL (SCALE: 1/8" =1 ' DRAWN BY: E.HAMERSKI DESIGNED BY: R.VEZZANI DATE: 05/20/2008 BACKROUND PLAN PROVIDED BY: �OB NUMBER: SHEET FA -33, j A J • NORTH • VANILLA SUITE 2416 WESTFIELD SOUTHCENTER MAL SCALE 11321=1' EX SYSTEM CALCULATIONS BATTERY SIZING CALCULATION WESTFIELD VANILLA SUITE 2416 Notification Appliance Circuit Detail WESTFIELD VANILLA SUITE 2416 FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations WESTFIELD SOUTHCENTER MALL NO DATE I A 105/20/20081 Panel: WESTFIELD VANILLA SUITE 2416 Wire Resistance 1.62 Date: June 2, 2008 CURRENT TOTAL= 239 Current Load: CIRCUIT: Standby: Alarm: I Current Load: Standby: Alarm: QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 0 SET -MC @15CD 64 0 Device Type Qty Amps Total 0.0022 Amps 0.0023 Total 98 Device Type Qty Amps Total Amps Total 1 HFP-11 175 175 0.0022 AD2-P 1 0.0635 0.0635 0.0096 0.064 0.021 0.064 0.042 SET -MC @110CD Main System Board SET -MC @15C D 0 1 0.03 0.03 0.030 0.064 0.030 HTR -R SET-HMC-C@115CD 2 0.009600 HTRI-D 0.001600 0.0035 0.21 0 SET -MC @30CD 445 0 0.098 (E= I * R) ICP -B6 0 SET -HMC @135CD 0.005 0 SET -MC @75CD 1 20.19 0 SET -HMC @185CD 0.175 0.175 (20.4 - E) 1 Z-MC@15CD SET -MC @110CD 64 0.233 SET HMC-C@115CD SET HMC-C@135CD ! 98 0 0.318 0.318 Standby Current Load: 0.0731 Amps 0.0731 For 24 Hours = Amps 1.754 0.106 Amp -hours Amps SET-HMC-C@185CD , DEVICES= 0.445 TOTAL mA= 239 ZR -MC @15CD 265 1 0.064 0.064 ZR -MC @30CD HCP ; 0.03 0.098 0.0015 Amps 0.269 Amps Notification Appliance Circuit MALL Detail PROJECT: Alarm Current Load: WESTFIELD VANILLA SUITE 2416 0.106 Amps For 5 Minutes= 0.009 Amp -hours Date: June 2, 2008 CURRENT TOTAL= 1.8 25% Derating= 9 2.204 Amp -hours p CIRCUIT: Standby Current Load: 0.03 Amps = For 24 Hours0.720 Amp -hours QTY Device Type Alarm Current Alarm Total VVire Size Wire Length Voltage at EOL Circuit Total 1 70.7V1/8 1.8 1.8 Alarm Current Load: 0.269 Amps Total Wire Resistance (R) For 5 Minutes= 0.023 Amp -hours 0 Total System Current Load: 2.204 Amp -hours (WL*2)*(R/ft) 0 0 0 Total Device Load, Amps (I) 0.00 0 0 0 25% Derating= 0.928 Amp -hours 0 Battery Pair to be Used: 0 12VDC Amp -hours 7AH Voltage Drop (E) 0.01 0 0 0 (E=I*R) 0 0 0 Total System Current Load: 20.39 0.928 Amp -hours 0 0 (20.4-E) 0 Battery Pair to be Used: 0 12VDC Amp -hours __ 7AH BATTERY SIZING CALCULATION z 445, qg z 1,0 CO 0' 0 z_ w LLJ (1)0 ui E -- FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: EGH Notification Appliance Circuit Detail DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL NO DATE I A 105/20/20081 Panel: WESTFIELD VANILLA SUITE 2416 Wire Resistance 1.62 Date: June 2, 2008 CURRENT TOTAL= 239 CIRCUIT: S1 I QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 0 SET -MC @15CD 64 0 Total Wire Resistance (R) 0.86 0 SET -MC @30CD 98 0 (WL * 2 ) * (R/ft) 1 SET -MC @75CD 175 175 Total Device Load, Amps (I) 0.24 0 SET -MC @110CD 233 0 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 Voltage Drop (E) 0.21 0 SET-HMC-C@177CD 445 0 (E= I * R) 0 SET -HMC @135CD 318 0 EOL Voltage 20.19 0 SET -HMC @185CD 445 0 (20.4 - E) 1 Z-MC@15CD 64 64 0 Z-MC@30CD 98 0 0 SET-MC-CW@110CD 233 0 DEVICES= 2 TOTAL mA= 239 12 265 20.19479461 239 WESTFIELD SOUTHCENTER Notification Appliance Circuit MALL Detail PROJECT: Panel: WESTFIELD VANILLA SUITE 2416 Wire Resistance 2.58; Date: June 2, 2008 CURRENT TOTAL= 1.8 CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total VVire Size Wire Length Voltage at EOL Circuit Total 1 70.7V1/8 1.8 1.8 Total Wire Resistance (R) 2.92 0 0 0 (WL*2)*(R/ft) 0 0 0 Total Device Load, Amps (I) 0.00 0 0 0 (Total Cct Load) 0 0 0 Voltage Drop (E) 0.01 0 0 0 (E=I*R) 0 0 0 EOL Voltage 20.39 0 0 0 (20.4-E) 0 0 0 0 1 0 TOTAL m A= 0 1.8 14 565 20.394752281 1.81 DEVICES= z 445, qg z 1,0 CO 0' 0 z_ w LLJ (1)0 ui E -- FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: EGH DESCRIPTION SHOP DRAWINGS NO DATE I A 105/20/20081 T C co J c LU 2 �z I -- U cr Q Z_Z CA =Q wig LI_iEc_ vJ Np LU r` Qz 0 W V) LU CC ‘CALE: 1/8"=1' DRAWN BY: E.HAMERSKI DESIGNED BY: R.VEZZANI DATE:05/20/2008 BACKROUND PLAN PROVIDED BY: �OB NUMBER: RISER DIAGRAM VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved SHEET FA -04 (E) VACANT SPACE NO WOW TI -HS AREA o Without Comments El As Noted in Red qr Per. The At:tached Letter ;-hese plans have been reviewed by The Tukwila Fire 'rcvention Bureau for conformance with current City •mndards. Acceptance is subject to errors and ,•nissions which do not authorize violations of adopted candards and ordinances. The respOnsibility for the dequacy of design rests totally with the designer. \clditions, deletions or revisions to these drawings after hIs date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. A Date: 11-°‘ -/ I By: len r , r 1 • TLIKV,VILA FIRE DEPARTMENT Please call 206-575-4407 and give this Fire Permit No. and exact address for shut- down or restoration approval. (E) TENANT DEMISING WALL TO REMAIN RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8ALL THREAD RDD PIPE SNIVEL RING (E) OLUMP TO REMAIN STEEL JOIST/TRUSS HANGER DETAIL NTS LEASE LINE Design per NFPA 13, Ordinary Hazard All materials to be new, U.L. listed, and F.M. approved All fire sprinkler heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart • 8 — Add Reliable Model F 1 Standard Response 155 ° Pendents 1/2 x 1/2 • E — Existing 8 — Total (E) VACANT SPACE NO WORK -n-iie AREA (E) GWEs SOPPIT Site Plan (E) E3ARRICADE AND DOOR TO REMAIN wies WINITSIACE 1.111113OUTMENTER NORTH ENLARGED REFLECTED CEILING PLAN 1/4" = 1'-0" FIRE PROTECTION INCORPORATED P.O. BOX 12113. MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7689 • • • IL,,./,F,'tl,,r'I�i/.., .�li`7!.'r.,rry'.,,`t�,: ,ii'•:�i'%'JE�i. �r Final acc-r .-.. c, ‘:> The Tu cilli ; A Date: G -1/-0 8 w; ; _. IUKWILA FIRE DEPARTMEN Please call: 575-440Z and give this job No. and exact address for shut. �.wvn or restoration aonrolml [NOTICE Weld starnps must be inspected before pipe is hung. Do not paint piping prior to hydrostatic test pprovaL" bi1:�;CCi! it IJV —2416 SHELL SPACE VICINITY MAP (Suite#2416) SCALE: NTS General Notes 1. Western States Fire Protection to add new pendent heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. EAST RISER DETAIL HYDRAULIC REFERENCE ON Y NOT TO SCALE Remote Area Is MG .,,EIBM r� so Has® MX RBI xYq w1M1*:W4. 1 � =I tea 1 LOB =X MI DM Dffill- � »n A P �� f "� i r •'• 00 , . '•' r. ;2' ;• :• .. .' , . .a dv/ •' - ':*"3w0' O I IT , k • .•• . ' r 4 .. • CA.. o ,g A . 4 . J.\O�� - ..• JO Ordinary Group II.0.20gpm/ft2 for 777.99ft2 FIRE SPRINKLER SYSTEM Lag 1--0—Existin Main ZONE T7 SYMBOL LEGEND REVISIONS Sprinkler Legend 3 5 7 9 11 �� Itttti��ta•��� Iltfi Its • .;TYPICAL FLEXABLE SPRINKLER CONNECTION; FLEXHEAD PIPE NIPPLE • MOUNTING BRACKET SPRINKLER BRANCHLINE FLEXASLE 'CONNECTING HOSE IN STANDARD LENGTHS REDUCING FITTING SUSPENDED T -BAR GRID SPRINKLER HEAD CEILING TILE FLEXHEAD DETAIL NOT TO SCALE FIG. ON • SWIVEL SWAY BRACE FITTING 3/8' KWIK BOLT _...•-(21/4' EMBED LENGTH) BRACE PIPE FIG.1000 "FAST CLAMP" SWAY BRACE ATTACHMENT LINE PIPE LATERAL LINE RESTRAINTS NON -THREADED BRACE PIPE Remote Area 2416 SHELL SPACE CALCULATION DESIGN CRITERIA STANDARD NFPA #13-2007 occuPANcvcLAss ORD HAZARD 1I MAX. COVERAGE per HEAD 130 . Ft' DENSITY .20 GPM ! Ft' for 777.99 Ft' SPRINKLER Reliable F1FR Semi-Rec ORIFICE 1/2" K. 5.6 WATER FLOW INFORMATION'; STATIC 140 PSI RESIDUAL 20 PSI FLOW 10900 GPM AT BASE OF RISER, SYSTEM REQUIRES: 258.17 GPM © 55.73 PSI i!+Sh•✓"+=9ri'.v,YK'y»...We:.+�:�,^+M'+vA K,r'kx..e`t•.re,•„�nK-�•.w.P C+�4 * At time of Design ' 12%0" CLG. m 37.00% AREA REDUCTION FIG. 4A PIPE CLAMP FOR SWAY BRACE OLATERAL BRANCHUNE RESTRAINT U I NON -THREADED BRACE PIPE FIG.909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT B/9' KWIK BOLT (21/4' EMBED LENGTH) BRACE PIPE LATERAL BRANCHLIN RE S TRAINT NOT TO SCALE Hanger No: 07C HILTI Kwik Bolt 111 Cut Rod Lgth Rounded to Nearest Inch Rod Coupling All Thread �I Rod Swivel Ring Concrete - Construction Bottom of Concrete to Center Line of Pipe Note on Plan Nota on Plan: Hanger Number and 'A' Dimension HANGER DETAIL NOT TO SCALE FILE COPY pedlon Com ate CertfBo,Qr 1 Awa J� itu;Iut y *B. .-,-39-2697 VICINITY MAP DETAIL NOT TO SCALE (Q N as w z 0 Adam Kantner Swinerton B IY 0 I— Q I— z 0 0 2 -WAY EARTHQUAKE BRACE NO. DESCRIPTION DATE SYM. SIN QTY. SPRAY ORIF. FIN. TEMP. MFR./MODEL 4 -WAY EARTHQUAKE BRACE R3615 9 HYDRAULIC REFERENCE POINT R5415 3 5.6 5.6 Pendent Z Chrome 155°F F1 FR Semi-Rec APPROVAL: City of Tukwila Pendent White 155°F G4A Concealed CONT. NO.: KS0407 Total =12 DRAWN BY: Adam Kantner HANGER SYMBOL BRANCHLINE RESTRAINT SPRK ON SHEET: SEE LEGEND SPRK ON JOB: DATE: 06/03/08 Western States Fire Protection Company 7102 180th AVE NE, STE A-105 - REDMOND, WA - 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE/AUSTIN/DALLAS/DECATUR/DENVER/DULUTH/ HOUSTON I KANSAS CITY LAS VEGAS IMINVEAPOLIS /PHOENIX/PORTLAND/RAPID CITY/ ST. PAUL/SALT LAKE CITY ISEATTLE Phone: 425-881-0100 Fax 425-881-3030 Vanilla Shells 2416 Southcenter Mall Tukwila ,Wa 98188 FIRE SPRINKLER SYSTEM ,.• � .. 2000 uM4tvan. I' ir° .ek 24,o Zai SHEET FP -1 OF 1 2416 SOUTHCENTER MALL ASSOCIATED PERMITS 11-F-095 08-F-276 11-S-088 11-S-081 08-S-303 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Vanilla Box 2416 Southcenter Mall Permit No.: 08-S-303 Date: June 11, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 '/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • These conditions apply to any sprinkler piping exposed as necessary to accomplish the permitted scope of work. All references are NFPA 13, 2007 Edition. FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Etiquette 2416 Southcenter Mall Permit No.: 11-S-088 Date: April 26, 2011 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ` of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. A! • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 20 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2010 Edition. III, Hydraulic Summary Job Number: KS0407 Report Description: Ordinary Group II Job:' Job Number Design Engineer KS0407 Adam Kanter Job Name State Certification/License Number Vanilla Shells 2416 WESTESF136QF Address 1 1 AHJ Southcenter Mall City of Tukwila Address 2 Job Site Southcenter Mall City State Zip Code Drawing Name Tukwila Wa 98188 FP-1-2416.cad System _ - . - 1 Remote Atea(s) Most Demanding Sprinkler Data Occupancy 5.6 K -Factor 20.00 at 12.755 Ordinary Group II Hose Allowance At Source Density Area of Application 250.00 . 0.20gpm/ft2 777.99ft2 (Actual 777.99ft2) Additional Hose Supplies PP Number Of Sprinklers Calculated Coverage Per Sprinkler Node Flow(gpmZ 12 100.00ft2 Total Hose Streams_. G' 250.00 n ii System Flow Demand Total Water Required (Including Hose Allowance) 258.17 ' 508.17t_, I/1 s •"�_ Maximum Pressure Unbalance In Loops I r L. 1111 0.000 r,, �' `��' 1._ y Maximum Velocity Above Ground 13.71 between nodes 26 and 12311747/r* IF Maximum Velocity Under Ground V. 0.98 between nodes 1 and 366 4161111186 Volume capacity of Wet Pipes i Volume capacity of Dry Pipes 3415.34gal 0.84ft3 Supplies . . Hose Flow Static Residual Flow Available @ Total Demand Required Safety Margin Node i (gpm) (psi) (psi) (gpm) l (psi) (gpm) (psi) (psi) 1 250.00 140.000 1 20.000 10900.00 139.587 508.17 59.971 79.616 GQrjtractor _ _ Contractor Number Contact Name Contact Title KS0407 Adam Kantner Project Manager Contractor Name Phone Extension Western States Fire Protection 425.881.0100 Address 1 FAX 7102 180th Ave Ne, Suite A-105 485.736.9032 Address 2 E-mail City State Zip Code Web -Site Redmond WA 98052 (bl ©M.E.P.CAD, Inc. 4.0 AutoSPRINK® VR5 v5.2.6 06/03/2008 11:30:50AM Page 1 11. -Summary Of Outflowing Devices Job Number: KS0407 Report Description: Ordinary Group II Device Actual Flow (gpm) Minimum Flow (gpm) K -Factor (K) Pressure (psi) Sprinkler 112 22.61 20.00 5.6 16.304 Sprinkler 111 22.57 20.00 5.6 16.240 Sprinkler 110 22.51 20.00 5.6 16.154 Sprinkler 109 21.89 20.00 5.6 15.279 Sprinkler 108 21.85 20.00 5.6 15.224 Sprinkler 102 20.36 20.00 5.6 13.224 Sprinkler 107 21.48 20.00 5.6 14.711 Sprinkler 106 21.44 20.00 5.6 14.659 c Sprinkler 101 20.00 20.00 5.6 12.755 Sprinkler 105 21.31 20.00 5.6 14.477 Sprinkler 104 21.11 20.00 5.6 14.216 Sprinkler 103 21.04 20.00 5.6 14.115 c Most Demanding Sprinkler Data ©M.E.P.CAD, Inc. M AutoSPRINK® VR5 v5.2.6 06/03/2008 11:30: 53AM Page 2 2 Node Analysis Job Number: KS0407 Report Description: Ordinary Group 11 Node Elevation(Foot) Fittings Pressure(psi) 1 Discharge(gpm) 16 16-6 fEE(4-6) 33.327 17 17-3 fEE(4-6) 33.163 18 17-3 P0(26-4) 33.446 20 18-6 fE(8-111/2) 33.491 26 17-11 P0(8-0) 29.626 27 17-11 2P0(8-0) 29.642 28 17-11 2P0(8-0) 29.743 123 16-6 P0(5-0) 20.893 124 16-6 P0(5-0) 21.026 131 16-6 PO(5-0) 21.105 138 16-6 P0(5-0) 19.487: 139 16-6 P0(5-0) 19.620 147 16-6 • PO(5-0) 20.068 157 14-11 P0(5-0) 19.158 158 , 14-11 1 P0(5-0) 19.289 166 14-11 P0(5-0) 19.791 171 14-11 E(2-0) 19.702 174 14-11 E(2-0) 19.187 191 14-11 E(2-0) 19.041 188 17-10 36.304 318 -16-1 2P0(43-1) 51.918 ' 324 -16-1 52.345 366 -12-4 BFP(-5.000) 55.732 112 12-0 Spr(-16.304) 16.304 22.61 111 12-0 Spr(-16.240) 16.240 22.57 110 12-0 Spr(-16.154) 16.154 ' 22.51 109 12-0 Spr(-15.279) 15.279 15.224 21.89 108 12-0 Spr(-15.224) 21.85 102 1 12-0 ' Spr(-13.224) 13.224 14.711 1 20.36 107 12-0 Spr(-14.711) 21.48 106 12-0 Spr(-14.659) 14.659 • 21.44 • 101 • 12-0 , Spr(-12.755) 12.755 14.477 ' 20.00 21.31 105 15-0 Spr(-14.477) 104 15-0 Spr(-14.216) 14.216 21.11 103 15-0 Spr(-14.115) 14.115 21.04 1 -22-0 S 59.971 , 258.17 M.E.P.CAD, Inc. 41 AutoSPRINK® VR5 v5.2.6 06/03/2008 11:30:57AM Page 3 1 r Hydraulic Analysis Job Number: KS0407 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Length Summary Length Downstream Upstream Elevation Discharge K -Factor Pt Pn Fittings. Eq. Total Qi Route 1 DR 1.049 Q=20.00 7.42 C=120 0.130131 50-10 Pf 8.304 101 12-0 q=20.00 K=5.6 12.755 Spr(-12.755) 13-0 Pe -1.268 166 14-11 19.791 4E(2-0), P0(5-0) 63-10 Pv BL 1.610 0=41.31 6.51 C=120 0.061811 11-7 Pf 0.963 166 14-11 19.791 4-0 Pe -0.686 147 16-6 20.068 2LtE(2-0) 15-7 Pv BL 1.610 Q=61.67 9.72 C=120 0.129738 8-0 Pf 1.038 147 16-6 20.068 Pe 131 16-6 21.105 8-0 Pv BL 1.610 0=84.18 13.27 C=120 0.230695 28-1 Pf 9.251 131 16-6 21.105 12-0 Pe -0.614 28 17-11 29.743 2LtE(2-0), PO(8-0) 40-1 Pv CM 4.260 0=258.17 5.81 C=120 0.016049 140-7 Pf 2.966 28 17-11 29.743 44-3 Pe 0.618 16 16-6 33.327 2E(13-2), 2fE(8-11 Y2) 184-9% Pv RN 4.260 Q=258.17 5.81 C=120 0.016049 1-0Y Pf 0.161 16 16-6 33.327 fEE(4-6) 9-0 Pe -0.325 17 17-3 33.163 fEE(4-6) 10-0% Pv CM 4.260 0=258.17 5.81 C=120 0.016049 17-7% Pf 0.283 17 17-3 33.163 ' Pe 18 17-3 33.446 17-7% Pv RN 4.260 0=258.17 5.81 C=120 0.016049 1-3 Pf 0.586 18 17-3 33.446 P0(26-4) 35-3%cPe -0.542 20 18-6 33.491 fE(8-11 Y2) 36-6'/2 Pv CM 4.260 0=258.17 5.81 C=120 0.016049 139-5 Pf 2.525 20 18-6 33.491 17-11, Pe 0.289 188 17-10 36.304 2fE(8-11%) 157-4Pv CM 6.357 0=258.17 2.61 C=120 0.002285 180-10 Pf 0.910 188 17-10 36.304 217-5Yz Pe 14.704 318 -16-1 51.918 12fE(12-7), BV(12-7), fE(10-0), 398-3% Pv CV(40-3), GV(3-9%) BL 8.329 0=258.17 1.52 C=120 0.000613 17-10 Pf 0.427 318 -16-1 51.918 P0(43-1) 678-3$ Pe -0.000 324 -16-1 52.345 2fE(16-0), 14P0(43-1) 696-1% Pv MS 10.020 0=258.17 1.05 C=120 0.000249 20-2 Pf 5.022 324 -16-1 52.345 67-0 Pe -1.635 366 -12-4 55.732 3LtE(16-0), BV(19-0), BFP(-5.000) 87-2 Pv UG 10.400 0=258.17 0.98 C=140 0.000156 112-10% Pf 0.039 366 -12-4 55.732 137-1 Y2 Pe 4.200 1 -22-0 59.971 4LtE(25-6), 2EE(17-6Y2), S 250-0 Pv Route 2 DR 1.049 0=20.36 7.56 C=120 0.134546 52-5 Pf 8.799 102 12-0 q=20.36 K=5.6 13.224 Spr(-13.224) 13-0 Pe -1.955 147 16-6 20.068 4E(2-0), PO(5-0) 65-5 Pv Route 3 DR 1.049 Q=21.04 7.81 C=120 0.142918 26-2 Pf 4.885 103 15-0 q=21.04 K=5.6 14.115 Spr(-14.115) 8-0 Pe 0.041 191 14-11 19.041 4E(2-0) 34-2 Pv BL 1.610 0=21.04 3.32 C=120 0.017743 6-7 Pf 0.116 191 14-11 19.041 Pe 157 14-11 19.158 6-7 Pv BL 1.610 Q=42.52 6.70 C=120 0.065203 11-7 Pf 1.016' 157 14-11 19.158 4-0 Pe -0.686 138 16-6 19.487 2LtE(2-0) 15-7 Pv BL 1.610 0=64.41 10.15 C=120 0.140587 10-0 Pf 1.406 138 16-6 19.487 Pe 123 16-6 20.893 10-0 Pv BL 1.610 0=87.02 13.71 C=120 0.245304 26-1, Pf 9.347 123 16-6 20.893 12-0 Pe -0.614 26 17-11 29.626 2LtE(2-0), PO(8-0) 38-1 Pv CM 4.260 0=87.02 1.96 C=120 0.002146 7-7 Pf 0.016 26 17-11 29.626 Pe 27 17-11 29.642 7-7 Pv CM 4.260 0=173.99 3.92 C=120 0.007734 13-0 Pf 0.101 27 17-11 29.642 Pe 28 17-11 29.743 13-0 Pv Q. Route 4 DR 1.049 0=21.11 7.84 C=120 0.143858 26-4 Pf 4.939 104 15-0 q=21.11 K=5.6 14.216 Spr(-14.216) 8-0 Pe 0.032 174 14-11 19.187 4E(2-0) 34-4 Pv ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 06/03/2008 11:31:01 AM Page 4 Hydraulic Analysis Job Number: KS0407 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K -Factor Upstream Pt Pn Fittings Eq. Length Summary Total Length BL 1.610 0=21.11 3.33 C=120 0.017859 5-81,4 Pf 0.102 174 14-11 158 14-11 19.187 19.289 Pe 5-81,4Pv BL 1.610 0=42.55 6.71 C=120 0.065308 11-7 Pf 1.018 158 14-11 139 16-6 19.289 19.620 2LtE(2-0) 4-0 Pe -0.686 15-7 Pv BL 1.610 0=64.41 10.15 C=120 0.140577 10-0 Pf 1.406 139 16-6 124 16-6 19.620 21.026 Pe 10-0 Pv BL 1.610 0=86.97 13.71 C=120 0.245058 25-8 Pf 9.230 124 16-6 27 17-11 21.026 29.642 2LtE(2-0), Z, P0(8-0) 12-0 Pe -0.614 37-8 Pv Route 5 DR 1.049 0=21.31 7.91 C=120 0.146306 27-6 Pf 5.193 105 15-0 q=21.31 K=5.6 171 14-11 14.477 19.702 Spr(-14.477) 4E(2-0) 8-0 Pe 0.032 35-6 Pv BL 1.610 0=21.31 3.36 C=120 0.018163 4-10% Pf 0.088 171 14-11 166 14-11 19.702 19.791 Pe 4-101,4Pv 4, Route 6 DR 1.049 0=21.44 7.96 C=120 0.148004 28-9% Pf 5.889 106 12-0 q=21.44 K=5.6 158 14-11 14.659 19.289 Spr(-14.659) 3E(2-0), P0(5-0) 11-0 Pe -1.259 39-9'/z Pv Route 7 DR 1.049 0=21.48 7.97 C=120 0.148486 27-5 Pf 5.707 107 12-0 q=21.48 K=5.6 157 14-11 14.711 19.158 Spr(-14.711) 3E(2-0), P0(5-0) 11-0 Pe -1.259 38-5 Pv Q. Route 8 DR 1.049 0=21.85 8.11 C=120 0.153276 304' Pf 6.342 108 12-0 q=21.85 K=5.6 139 16-6 15.224 19.620 Spr(-15.224) 3E(2-0), PO(5-0) 11-0 Pe -1.946 41-4'% Pv iwo Route 9 DR 1.049 0=21.89 8.13 C=120 0.153789 29-0 Pf 6.154 11-0 Pe -1.946 40-0 Pv 109 12-0 q=21.89 K=5.6 138 16-6 15.279 19.487 Spr(-15.279) 3E(2-0), PO(5-0) Route 10 DR 1.049 0=22.51 8.36 C=120 0.161913 31-7 Pf 6.897 11-0 Pe -1.946 42-7 Pv 110 12-0 q=22.51 K=5.6 131 16-6 16.154 21.105 Spr(-16.154) 3E(2-0), P0(5-0) v Route 11 DR 1.049 0=22.57 8.38 C=120 0.162710 30-4% Pf 6.732 11-0, Pe -1.946 41-4% Pv 111 12-0 q=22.57 K=5.6 124 16-6 16.240 21.026 Spr(-16.240) 3E(2-0), PO(5-0) .i Route 12 DR 1.049 0=22.61 8.39 C=120 0.163308 29-0 Pf 6.535 11-0 Pe -1.946 40-0 Pv 112 12-0 q=22.61 K=5.6 123 16-6 16.304 20.893 Spr(-16.304) 3E(2-0), P0(5-0) Equivalent Pipe.Lengths of Valves and Fittings (C=120 only) ; I C Value:Multiplier 0 Actual Inside Diameter 4.87 ) Value Of C 100 Multiplying Factor 0.713 130 1.16 140 150 1.33 1.51 = Factor ( Schedule 40 Steel Pipe Inside Diameter �A ©M.E.P.CAD, Inc. irjAutoSPRINK® VR5 v5.2.6 06/03/2008 11:31:01 AM Page 5 1111 Hydraulic Analysis Pipe Type Diameter Job Number: KS0407 Report Description: Ordinary Group II Flow Velocity HWC Friction Loss Downstream Elevation Upstream 'Pipe Type Legend Discharge K -Factor Pt Pn Fittings Length Pressure Eq. Length Summary Total Length Units Legend Fittings Legend AO Arm -Over Diameter BL Branch Line Elevation CM Cross Main Flow DN Drain Discharge DR Drop Velocity DY Dynamic Pressure FM Feed Main Length FR Feed Riser Friction Loss MS Miscellaneous HWC OR Outrigger Pt RN Riser Nipple Pn SP Sprig Pf ST Stand Pipe Pe UG Underground Pv Inch Foot gpm gpm fps psi Foot psi/Foot Hazen -Williams Constant Total pressure at a point in a pipe Normal pressure at a point in a pipe Pressure loss due to friction between points Pressure due to elevation difference between indicated points Velocity pressure at a point in a pipe ALV AngV b BaIV BFP BV C cplg Cr CV De1V DPV E EE Eel Ee2 FDC fE fEE flg FN fT g GIoV GV Hose HV Hyd LtE mecT Noz P1 P2 PIV PO PrV PRV red S sCV Spr St T Tr U WirF WMV z Alarm Valve Angle Valve Bushing Ball Valve Backflow Preventer Butterfly Valve Cross Flow Tum 90° Coupling Cross Run Check Valve Deluge Valve Dry Pipe Valve 90° Elbow 45° Elbow 11W Elbow 22W Elbow Flow Device Fire Department Connection 90° FireLock(TM) Elbow 45° FireLock(TM) Elbow Flange Floating Node FireLock(TM) Tee Gauge Globe Valve Gate Valve Hose Hose Valve Hydrant Long Turn Elbow Mechanical Tee Nozzle Pump In Pump Out Post Indicating Valve Pipe Outlet Pressure Relief Valve Pressure Reducing Valve Reducer/Adapter Supply Swing Check Valve Sprinkler Strainer Tee Flow Turn 90° Tee Run Union Wirsbo Water Meter Valve Cap © M.E.P.CAD, Inc. �•,���AutoSPRINK® VR5 v5.2.6 06/03/2008 11:31:01 AM Page 6 dna Hydraulic Graph Job Number: KS0407 Report Description: Ordinary Group II Supply at Node 1 150 Static Pressure 140.000 135 120 105 90 .N a LIE 75 rn to m a 1,508.17 with hose streams 60 -258.17 @ 59.971 45 System demand curve 30 1 10900.00 @ 20.0001 15 111 11 11 1 1 1 1 1 I) 1 1 1 1 (I 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 ( 1 1 1 1 1 1 1 1 I I I 1 1 I I I I 1 1 1 1 1 1 I 1 1 1 ( 1 1 1 1 1 0 /7111111111111 T1002200 3300 4.40011000 5500 6600 7700 8800 9900 Water flow, gpm Hydraulic Graph Supply at Node 1 Static Pressure 140.000 Residual Pressure 10900.00 @ 20.000 Available PressureTime of Test 139.587 @ 508.17 System Demand 258.17 @ 59.971 System Demand (Including Hose Allowance) 508.17 @ 59.971 ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 06/03/2008 11:31:10AM Page 7 111 Flow Diagram _(Top View) Job Number: KS0407 Report Description: Ordinary Group II (�c, ©M.E.P.CAD, Inc. 411 AutoSPRINK®VR5 v5.2.6 06/03/2008 11:31:14AM Page 8 04/18/2011 /2011 12:33 4254818695 CROWN FIRE L CROWN FIRE PROTECTION, INC. 221 Company Subjec 4.18.11 Fire Prevention Bureau Tukwila Fire Department/ Don Tomaso Dema Permit Number of Pages (Including Cover 0 Urgent From 1 For Review d Please Comment Jessica Robinson Fax No. PAGE 01/01 206.575.4439 TL'tc-''vILA FIRE. DEPAR', Please call 20,5-575-4'!1;./ give this FireOil: an,.! exact address for s �i down or restoration approval. ❑ Please Reply PH:425.481.7669 FX:425-481.8695 Please provide a demo permit to shorten (2) sprinkler drops that are in the way of the new construction at the Etiquette project at 2416 Southcenter Mall. The building permit is 010246. Please let us know if you have any questions. Thanks P.O. BOX 12113 MILL CREEK, WA 980$2 P11: 425.481,7669 -- — — _ — FX: 425. 481.8695 • DDIT N Without Comments O As Noted in Red D Per The Attached Letter iese plans have ben reviewed by The Tukwila Fire •:vention Bureau for (7)nfo rriance with current City ndards. Accepr ,,; ;::: } pit r..i, to eiTors and Llissions which ,:,i,,, ;u`:: iIC t?{'ize'violations of adopted ndards and ordin,anc:<. The r . ponsibility for the equacy of design :'::£:t:_ totally with d;e designer, ,iidltions, deletions i;'?i::ion i':) ghee drawings after •'nis date will void rhl:; 'Mll require a «•esubmittai or revised dravlinus for sub5equent approval. Final acceptance is subject to field test and Inspection by The Tukwila Fire Prevention Bureau. Date: 5- Lf -1 ( By: 4 F ,,R i"+ 77-V• RTMENT ...LLL.. Iv.'L.. tl�a. Plot: 4s.:a E ° . ,!.375-407 and give tris No. it -� oar and c .W. .lu : 7 :l $i shut- down or ;" � ; wi cry i pprovaL NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and SHEET \UV3E SHE -T TITLE SYSTEV I\FOMATION FRE ALAN SYSTE SHEET INDEX WISE SCHEDULE A\ CO\DUIT FILL C FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. QUANTITY EX EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX • • MOUNTING HEIGHT S FIRE ALARM SPEAKER STROBE EX (EXISTING) SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1 /2 EXTN �EX FIRE ALARM STROBE (EXISTING) ZR -MC -CW SIEMENS 4S DEEP BOX CEILING A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A co 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 m 0 C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V' SPEAKER CIRCUIT- RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. DESCRIPTION ,SHOP DRAWINGS DATE f 04/26/11 WIRE DESIGNATION SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V' SPEAKER CIRCUIT- RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. SYMBOLS LEGEND 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 126061 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 'Mr°' i JOHNNY �FC16J ISHA 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. SARKU 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. RETAIL SUSHI rro SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END 23. RETAIL NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED WIRE DESIGNATION GENERAL NOTES ROOF ROOF ROOF' ETIQUETTE (2416) TERRACE PAID I.1HY - 2 2011 TUKWILA FIRE Yko- SCALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE:04/26/1 1 \OB NUMBER: SITE PLAN SHEET FA -01 Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved I\J BACKROUND PLAN PROVIDED BY: ck 17•••• • ••••.: r•••••••• EX ... Z.; ............. . ...... ... S1-1 95cd V-1 S )Z,N EX S1-2 15cd TO FACP EX "'• t • 7. •.• „ ...... ' S1-5 75cd V-4 S,S' V,V S1-3 95cd V-2 EX 61-4 95cd V-3 EX ....................................................................................................................................................... EX A — • ................................................... •.• • , , f . . . FIRE ALARM SYSTEM PLAN •-•:••• HARD LID CEILING FLAG NOTES: RELOCATE EXISTING SPEAKER STROBE TO NEW LOCATION INDICATED (BELOW DROP CEILING). SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX 7----- WITH 1-1/2' EXTENSION \\\\\\ CEILING MOUNTED SPEAKER/STROBE SPEAKER STROBE MOUNTING DETAIL P0 CO 0 \ 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS IREV. BY: I 0 m 0 DESCRIPTION SHOP DRAWINGS DATE 04/26/11 2 <<<<< u_ 'ALE: 3/16:=1'0" *N\ DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE:04/26/11 BACKROUND PLAN PROVIDED BY: .J013 NUMBER: —) r SHEET FA -02 Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved i EST LI! VAN 1 LLA SUITE 241 RE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET \UM3ESHEET TITLE FA -01 SYSTEM I\FOvATIO\ FA -02 TYPICAL DETAILS - WRI\G A\� MOU\TING FA -03 FRE ALARM SYSTEM FLOG DLA\ FA -04 SYSTEM CALC U LATI O \S r GE\EAL), �ISE� SITE PLA\ WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C, AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEVIBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 1 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM SDD-C REMOTE ANNUNCIATOR SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD B Q LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING D DUCT SMOKE DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD 0 HEAT DETECTOR (ADDRESSABLE) HFPT-11 w/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM Ric FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM STROBE (CEILING MOUNT) SET -HMC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING L FIRE ALARM STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. PC FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. B �W P FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) SET -W SIEMENS. 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR MULTI -VOLTAGE CONTROL RELAY MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. r... INFILD FA JBOX FIRE ALARM TERMINAL CABINET JUNCTI❑N BOX F.B.O. F.B.O. N/A TE VERT IN FI LD VERT IN FI LD WIRE DESIGNATI❑N SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D H P S A V I X UD UI M B DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) ANNUNCIAT❑R TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) RED (JACKET) REMOTE INDICATI❑N LIGHT TWO #18 FPL/FPLR RED (JACKET) LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) A.F.F. CONDUIT FILL CHART N/A NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C, AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEVIBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 1 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM SDD-C REMOTE ANNUNCIATOR SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD B Q LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING D DUCT SMOKE DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD 0 HEAT DETECTOR (ADDRESSABLE) HFPT-11 w/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM Ric FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM STROBE (CEILING MOUNT) SET -HMC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING L FIRE ALARM STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. PC FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. B �W P FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) SET -W SIEMENS. 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR MULTI -VOLTAGE CONTROL RELAY MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. r... INFILD FA JBOX FIRE ALARM TERMINAL CABINET JUNCTI❑N BOX F.B.O. F.B.O. N/A TE VERT IN FI LD VERT IN FI LD REMOVE BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A OTICE 413 • '44 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 d, signed, TukwilE RELEASE/REVISIONS REV. BY: EGH i VVRI KR9lLVitUilCtil* A.F.F. ABOVE FINISHED FLOOR N/A N/A As Noted Irci,Rd N/A ❑ Per The Attached Letter F.B.❑. FURNISHED BY OTHERS N/A 'Iciest plans have been re>l fed by The Tukwila FWA Prevention Bureau for conformance with current city N/A NOT APPLICABLE N/A standdrds. Acceptdnce is eabi�,;l lu ettuts and ohlIrsiions which do not auttli6tize violations of adop iA standards and ordinances. The responsibility for the U.D.N. UNLESS OTHERWISE NOTED N/A adequacy of design rests totally with the designer. At}difons, deletions or revii�k s to these drawings t� this date will void thi.s.acceptance and will require a r A complete WP WEATHERPROOF DEVICE N/A resubmittal of revised drawings tor subsequent approval. N/A N/A N/A Final acceptance is subject to field test and inspection by Fire Dei Certificate RED AS BUILT ADD OR CHANGE N/A The Tukwila Fire Prevention Bureau. N/A N/A • N/A Date: 0 By: v to the ] commencE Testing ---- AS BUILT N/A ._._ . . ' and DE REMOVE BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A OTICE 413 • '44 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 d, signed, TukwilE RELEASE/REVISIONS REV. BY: EGH DESCRIPTION SHOP DRAWINGS DATE 05/20/2008 2 CCCCC artment Pre-test must be presentedF Inspector prior to C!) ment of Acceptances of any Fire Alarm tection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. fUKWILA FIRE DEPART E. 'i , Please call: 575-4407 and give this job No. and exact address for shut, Lown or restoration approval. Copyright 2006 by Guardian Security Systems, exam amm,41 2008 Tukwila Fire zoo/� /75- Inc. x'75Inc. All Rights Reserved SCALE: 1 /8"=1' DRAWN BY: E.HAMERSKI DESIGNED BY: R.VEZZANI DATE:05/20/2008 BACKROUND PLAN PROVIDED BY: .10B NUMBER: C SHEET FA -0 1 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT WE SCALE COMBINE ALL SHIELDS AND IS❑LATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE �+ STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR -�-i- PREVIOUS ADDRESSABLE DEVICE' END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH DUCT DETECTOR LOCATI❑N GROUND-- _r> CV r') L() 0 NN HTRI-R • STATUS LED 00 ( N.0 COM N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE DEVICE TO NEXT ADDRESSABLE DEVICE NOTE 1: VOLTAGE MAX, - CURRENT MAX. - CONT. RES, MAX. - MAX. CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX, LINE SIZE - MIN, LINE SIZE- OUTLET SAMPLING ---- TUBE INLET SAMPLING— . TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE=NONE MUSIC L -AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE f(+) STOP IF LAST DEVICE `(-) FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVICE (-) RELAY CONTACTS (4,OA @ 125VAC) (4.OA @ 30VDC) 27 VDC 3.5 riA DURING POLLING 10 OHMS 200 FT, (18 AWG) 0,02uF 0.04uF 14 AWG 18 AWG NOTE 2: ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTI❑N. 0 I00I TB1 SSOGOG 123456 HCP TB2 - +- G G G 654321 J 0 \N) 1_ END OF LINE DEVICE r (3.6K 1/4W) 1- 1-7% 1-% SUPERVISED__-__/ SWITCH GROUND CV Co1.0 _ HTRI-D *STATUS '--'STATUS LED CO NOT USED ------ END OF LINE DEVICE `(3.6K 1/4W) 0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 CND N AC n 0 0 0 0 PAD -3 0 0 OC 0 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 102 24K n + TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE NAC -4 2 NAC -3 NAC -2 NAC -1 UPERVISED SWITCH ( FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE + DEVICE LOOP NOT USED REMOTE DEVICE LOOP 0 0 0 FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY C'S' CABLE) FROM FACP (VOICE CIRCUIT) ('V' CABLE) 470 OHMS III EOL 1.1 9 9 9 TEM -1 0 r ~ 0 0 bo �z giti 00 0 TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE N06E (+) ( ) STROBE SPEAKER (+) (,) (STROBE(-) EARTH GROUND 0 ..(+)TO NEXT DEVICE OR } >(-) STOP IF LAST DEVICE (+) (_) STROBE SPEAKER (+) (-) 0 SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY RI 0 807 A.F.F. 4S DEEP BOX W/ 1-1/2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE=NONE TO NEXT DEVICE ❑R END OF LINE TO NEXT DEVICE ❑R END OF LINE NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER,11N TEMPERATU +32' F (0' C) E TO 100' F 38' C) HUMIDITY: O-9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR —> FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE r DATA IN( )>- it DATA IN (+) > DEVICE IS USED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT DEVICEF > ( ) DATA OUT > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID —\ CEILING HARD LID SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSI❑N \._ CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE=NONE JUNCTI❑N BOX MOUNTED ON CEILING FLEX \ JUNCTI❑ MOUNTED A( CEILING SU N BOX iAINST PP❑RT 0 0 0 0 TO NEXT DEVICE CADDY BAR SMOKE DETECTOR ---- SMOKE DETECTOR MOUNTING SCALE=NONE SUSPENDED ILLUMINATED CEILING DO NOT ADDRESS DEVICES PREPROG DEVICES I\ST BLE Nl�I L NDMI, TM R A iV E D W DDIESS. T Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved rn 0o O DE Z_ (/) W J UJ C) O W r--- LU ` FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: EGH DESCRIPTION SHOP DRAWINGS w 105/20/20081 I- 0 z z 52 0 tV � W CO Cly w cO //�/� 1:1-1-1C9z VJ ZZ> < z ow < IT -1 �w cc (1) ■ (/) W w U SCALE: 1/8"=1' DRAWN BY: E.HAMERSKI DESIGNED BY: R.VEZZANI DATE:05/20/2008 BACKROUND PLAN PROVIDED BY: %OB NUMBER: SHEET C FA -02 EOL—S1 20.19V 2S,2V 2I 2S,2V n, X75 C 121 V i'. NORTH VANILLA SUITE 2416 WESTFIELD SOUTHCENTER MALL SCALE 118°=1' 'JAG IO ES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS.(SEE SIEMENS INSTALLATI❑N SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR, SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLATOR FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT, DO NO INSTAL ADD-ESSABLE INHT ATIN DEVICES U\TIL PREPROGRAMMED WI—H EVICES ADDRESS. G Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS J REV. BY: 0 w DESCRIPTION SHOP DRAWINGS DATE 105/20/2008 9 aaCCa W LL (SCALE: 1/8" =1 ' DRAWN BY: E.HAMERSKI DESIGNED BY: R.VEZZANI DATE: 05/20/2008 BACKROUND PLAN PROVIDED BY: �OB NUMBER: SHEET FA -33, j A J • NORTH • VANILLA SUITE 2416 WESTFIELD SOUTHCENTER MAL SCALE 11321=1' EX SYSTEM CALCULATIONS BATTERY SIZING CALCULATION WESTFIELD VANILLA SUITE 2416 Notification Appliance Circuit Detail WESTFIELD VANILLA SUITE 2416 FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations WESTFIELD SOUTHCENTER MALL NO DATE I A 105/20/20081 Panel: WESTFIELD VANILLA SUITE 2416 Wire Resistance 1.62 Date: June 2, 2008 CURRENT TOTAL= 239 Current Load: CIRCUIT: Standby: Alarm: I Current Load: Standby: Alarm: QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 0 SET -MC @15CD 64 0 Device Type Qty Amps Total 0.0022 Amps 0.0023 Total 98 Device Type Qty Amps Total Amps Total 1 HFP-11 175 175 0.0022 AD2-P 1 0.0635 0.0635 0.0096 0.064 0.021 0.064 0.042 SET -MC @110CD Main System Board SET -MC @15C D 0 1 0.03 0.03 0.030 0.064 0.030 HTR -R SET-HMC-C@115CD 2 0.009600 HTRI-D 0.001600 0.0035 0.21 0 SET -MC @30CD 445 0 0.098 (E= I * R) ICP -B6 0 SET -HMC @135CD 0.005 0 SET -MC @75CD 1 20.19 0 SET -HMC @185CD 0.175 0.175 (20.4 - E) 1 Z-MC@15CD SET -MC @110CD 64 0.233 SET HMC-C@115CD SET HMC-C@135CD ! 98 0 0.318 0.318 Standby Current Load: 0.0731 Amps 0.0731 For 24 Hours = Amps 1.754 0.106 Amp -hours Amps SET-HMC-C@185CD , DEVICES= 0.445 TOTAL mA= 239 ZR -MC @15CD 265 1 0.064 0.064 ZR -MC @30CD HCP ; 0.03 0.098 0.0015 Amps 0.269 Amps Notification Appliance Circuit MALL Detail PROJECT: Alarm Current Load: WESTFIELD VANILLA SUITE 2416 0.106 Amps For 5 Minutes= 0.009 Amp -hours Date: June 2, 2008 CURRENT TOTAL= 1.8 25% Derating= 9 2.204 Amp -hours p CIRCUIT: Standby Current Load: 0.03 Amps = For 24 Hours0.720 Amp -hours QTY Device Type Alarm Current Alarm Total VVire Size Wire Length Voltage at EOL Circuit Total 1 70.7V1/8 1.8 1.8 Alarm Current Load: 0.269 Amps Total Wire Resistance (R) For 5 Minutes= 0.023 Amp -hours 0 Total System Current Load: 2.204 Amp -hours (WL*2)*(R/ft) 0 0 0 Total Device Load, Amps (I) 0.00 0 0 0 25% Derating= 0.928 Amp -hours 0 Battery Pair to be Used: 0 12VDC Amp -hours 7AH Voltage Drop (E) 0.01 0 0 0 (E=I*R) 0 0 0 Total System Current Load: 20.39 0.928 Amp -hours 0 0 (20.4-E) 0 Battery Pair to be Used: 0 12VDC Amp -hours __ 7AH BATTERY SIZING CALCULATION z 445, qg z 1,0 CO 0' 0 z_ w LLJ (1)0 ui E -- FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: EGH Notification Appliance Circuit Detail DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL NO DATE I A 105/20/20081 Panel: WESTFIELD VANILLA SUITE 2416 Wire Resistance 1.62 Date: June 2, 2008 CURRENT TOTAL= 239 CIRCUIT: S1 I QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 0 SET -MC @15CD 64 0 Total Wire Resistance (R) 0.86 0 SET -MC @30CD 98 0 (WL * 2 ) * (R/ft) 1 SET -MC @75CD 175 175 Total Device Load, Amps (I) 0.24 0 SET -MC @110CD 233 0 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 Voltage Drop (E) 0.21 0 SET-HMC-C@177CD 445 0 (E= I * R) 0 SET -HMC @135CD 318 0 EOL Voltage 20.19 0 SET -HMC @185CD 445 0 (20.4 - E) 1 Z-MC@15CD 64 64 0 Z-MC@30CD 98 0 0 SET-MC-CW@110CD 233 0 DEVICES= 2 TOTAL mA= 239 12 265 20.19479461 239 WESTFIELD SOUTHCENTER Notification Appliance Circuit MALL Detail PROJECT: Panel: WESTFIELD VANILLA SUITE 2416 Wire Resistance 2.58; Date: June 2, 2008 CURRENT TOTAL= 1.8 CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total VVire Size Wire Length Voltage at EOL Circuit Total 1 70.7V1/8 1.8 1.8 Total Wire Resistance (R) 2.92 0 0 0 (WL*2)*(R/ft) 0 0 0 Total Device Load, Amps (I) 0.00 0 0 0 (Total Cct Load) 0 0 0 Voltage Drop (E) 0.01 0 0 0 (E=I*R) 0 0 0 EOL Voltage 20.39 0 0 0 (20.4-E) 0 0 0 0 1 0 TOTAL m A= 0 1.8 14 565 20.394752281 1.81 DEVICES= z 445, qg z 1,0 CO 0' 0 z_ w LLJ (1)0 ui E -- FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: EGH DESCRIPTION SHOP DRAWINGS NO DATE I A 105/20/20081 T C co J c LU 2 �z I -- U cr Q Z_Z CA =Q wig LI_iEc_ vJ Np LU r` Qz 0 W V) LU CC ‘CALE: 1/8"=1' DRAWN BY: E.HAMERSKI DESIGNED BY: R.VEZZANI DATE:05/20/2008 BACKROUND PLAN PROVIDED BY: �OB NUMBER: RISER DIAGRAM VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved SHEET FA -04 (E) VACANT SPACE NO WOW TI -HS AREA o Without Comments El As Noted in Red qr Per. The At:tached Letter ;-hese plans have been reviewed by The Tukwila Fire 'rcvention Bureau for conformance with current City •mndards. Acceptance is subject to errors and ,•nissions which do not authorize violations of adopted candards and ordinances. The respOnsibility for the dequacy of design rests totally with the designer. \clditions, deletions or revisions to these drawings after hIs date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. A Date: 11-°‘ -/ I By: len r , r 1 • TLIKV,VILA FIRE DEPARTMENT Please call 206-575-4407 and give this Fire Permit No. and exact address for shut- down or restoration approval. (E) TENANT DEMISING WALL TO REMAIN RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8ALL THREAD RDD PIPE SNIVEL RING (E) OLUMP TO REMAIN STEEL JOIST/TRUSS HANGER DETAIL NTS LEASE LINE Design per NFPA 13, Ordinary Hazard All materials to be new, U.L. listed, and F.M. approved All fire sprinkler heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart • 8 — Add Reliable Model F 1 Standard Response 155 ° Pendents 1/2 x 1/2 • E — Existing 8 — Total (E) VACANT SPACE NO WORK -n-iie AREA (E) GWEs SOPPIT Site Plan (E) E3ARRICADE AND DOOR TO REMAIN wies WINITSIACE 1.111113OUTMENTER NORTH ENLARGED REFLECTED CEILING PLAN 1/4" = 1'-0" FIRE PROTECTION INCORPORATED P.O. BOX 12113. MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7689 • • • IL,,./,F,'tl,,r'I�i/.., .�li`7!.'r.,rry'.,,`t�,: ,ii'•:�i'%'JE�i. �r Final acc-r .-.. c, ‘:> The Tu cilli ; A Date: G -1/-0 8 w; ; _. IUKWILA FIRE DEPARTMEN Please call: 575-440Z and give this job No. and exact address for shut. �.wvn or restoration aonrolml [NOTICE Weld starnps must be inspected before pipe is hung. Do not paint piping prior to hydrostatic test pprovaL" bi1:�;CCi! it IJV —2416 SHELL SPACE VICINITY MAP (Suite#2416) SCALE: NTS General Notes 1. Western States Fire Protection to add new pendent heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. EAST RISER DETAIL HYDRAULIC REFERENCE ON Y NOT TO SCALE Remote Area Is MG .,,EIBM r� so Has® MX RBI xYq w1M1*:W4. 1 � =I tea 1 LOB =X MI DM Dffill- � »n A P �� f "� i r •'• 00 , . '•' r. ;2' ;• :• .. .' , . .a dv/ •' - ':*"3w0' O I IT , k • .•• . ' r 4 .. • CA.. o ,g A . 4 . J.\O�� - ..• JO Ordinary Group II.0.20gpm/ft2 for 777.99ft2 FIRE SPRINKLER SYSTEM Lag 1--0—Existin Main ZONE T7 SYMBOL LEGEND REVISIONS Sprinkler Legend 3 5 7 9 11 �� Itttti��ta•��� Iltfi Its • .;TYPICAL FLEXABLE SPRINKLER CONNECTION; FLEXHEAD PIPE NIPPLE • MOUNTING BRACKET SPRINKLER BRANCHLINE FLEXASLE 'CONNECTING HOSE IN STANDARD LENGTHS REDUCING FITTING SUSPENDED T -BAR GRID SPRINKLER HEAD CEILING TILE FLEXHEAD DETAIL NOT TO SCALE FIG. ON • SWIVEL SWAY BRACE FITTING 3/8' KWIK BOLT _...•-(21/4' EMBED LENGTH) BRACE PIPE FIG.1000 "FAST CLAMP" SWAY BRACE ATTACHMENT LINE PIPE LATERAL LINE RESTRAINTS NON -THREADED BRACE PIPE Remote Area 2416 SHELL SPACE CALCULATION DESIGN CRITERIA STANDARD NFPA #13-2007 occuPANcvcLAss ORD HAZARD 1I MAX. COVERAGE per HEAD 130 . Ft' DENSITY .20 GPM ! Ft' for 777.99 Ft' SPRINKLER Reliable F1FR Semi-Rec ORIFICE 1/2" K. 5.6 WATER FLOW INFORMATION'; STATIC 140 PSI RESIDUAL 20 PSI FLOW 10900 GPM AT BASE OF RISER, SYSTEM REQUIRES: 258.17 GPM © 55.73 PSI i!+Sh•✓"+=9ri'.v,YK'y»...We:.+�:�,^+M'+vA K,r'kx..e`t•.re,•„�nK-�•.w.P C+�4 * At time of Design ' 12%0" CLG. m 37.00% AREA REDUCTION FIG. 4A PIPE CLAMP FOR SWAY BRACE OLATERAL BRANCHUNE RESTRAINT U I NON -THREADED BRACE PIPE FIG.909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT B/9' KWIK BOLT (21/4' EMBED LENGTH) BRACE PIPE LATERAL BRANCHLIN RE S TRAINT NOT TO SCALE Hanger No: 07C HILTI Kwik Bolt 111 Cut Rod Lgth Rounded to Nearest Inch Rod Coupling All Thread �I Rod Swivel Ring Concrete - Construction Bottom of Concrete to Center Line of Pipe Note on Plan Nota on Plan: Hanger Number and 'A' Dimension HANGER DETAIL NOT TO SCALE FILE COPY pedlon Com ate CertfBo,Qr 1 Awa J� itu;Iut y *B. .-,-39-2697 VICINITY MAP DETAIL NOT TO SCALE (Q N as w z 0 Adam Kantner Swinerton B IY 0 I— Q I— z 0 0 2 -WAY EARTHQUAKE BRACE NO. DESCRIPTION DATE SYM. SIN QTY. SPRAY ORIF. FIN. TEMP. MFR./MODEL 4 -WAY EARTHQUAKE BRACE R3615 9 HYDRAULIC REFERENCE POINT R5415 3 5.6 5.6 Pendent Z Chrome 155°F F1 FR Semi-Rec APPROVAL: City of Tukwila Pendent White 155°F G4A Concealed CONT. NO.: KS0407 Total =12 DRAWN BY: Adam Kantner HANGER SYMBOL BRANCHLINE RESTRAINT SPRK ON SHEET: SEE LEGEND SPRK ON JOB: DATE: 06/03/08 Western States Fire Protection Company 7102 180th AVE NE, STE A-105 - REDMOND, WA - 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE/AUSTIN/DALLAS/DECATUR/DENVER/DULUTH/ HOUSTON I KANSAS CITY LAS VEGAS IMINVEAPOLIS /PHOENIX/PORTLAND/RAPID CITY/ ST. PAUL/SALT LAKE CITY ISEATTLE Phone: 425-881-0100 Fax 425-881-3030 Vanilla Shells 2416 Southcenter Mall Tukwila ,Wa 98188 FIRE SPRINKLER SYSTEM ,.• � .. 2000 uM4tvan. I' ir° .ek 24,o Zai SHEET FP -1 OF 1