HomeMy WebLinkAboutPP - 2446 SOUTHCENTER MALL - WET SEAL - PERMITS AND PLANS2446 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-289 08-S-262 .7 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Wet Seal 2446 Southcenter Mall Permit No.: 08-S-262 Date: June 3, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). f 1 • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. COSCO FIRE PROTECTION, INC. 10910 - 117TH PLACE, N.E. KIRKLAND,WA 98033-5027 HYDRAULIC CALCULATIONS FOR 'WET SEAL - SPACE 2446 2446 SOUTHCENTER PARKWAY' TUKWILA, WASHINGTON 98188 FILE NUMBER: 25 KS 7953 DATE: MAY 30, 2008 DESIGN DATA: REMOTE AREA - A OCCUPANCY CLASSIFICATION: ORDINARY HAZARD GROUP 2 DENSITY: 0.20 gpm/sq. ft. AREA OF APPLICATION: 1,500 sq. ft. COVERAGE PER SPRINKLER: 130 sq. ft. NUMBER OF SPRINKLERS CALCULATED: 15 sprinklers TOTAL SPRINKLER WATER FLOW REQUIRED: 467.6 gpm TOTAL WATER REQUIRED (including hose): 900.0 gpm FLOW AND PRESSURE (@ BOR): 650 gpm @ 110.5 psi SPRINKLER ORIFICE SIZE: 1/2 inch NOTE: NODES 1,3,4,8,9 ARE ON "FLEX HEAD" FLEXABLE CONNECTIONS. MODEL #2024, 2'-0" LONG, 17'-0" EQUIVILENT FEET OF 1" PIPE. DESIGN/LAYOUT BY: D. CLARK AUTHORITY HAVING JURISDICTION: TUKWILA FIRE DEPT. CONTRACTOR CERTIFICATION NUMBER: COSCOFP110NM CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 4903012830) HRS SYSTEMS, INC. TUCKER, GA 30084 TUCKER, GA 30084 SPRINKLER SYSTEM INPUT DATA Page 1 DATE: 5/30/2008L:\DAYWORKS KS 7700 +\KS 7953 -WET SEAL\CALCULATIONS\HYDRAULIC CALC'S JOB TITLE: WET SEAL-SOUTHCENTER MALL AREA -1 Source Nodes Node Tag Elevation Static Residual Residual Hose Stream Pressure Pressure Flow Allowance (ft) (psi) (psi) (gpm) (gpm) SOURCE -3.00 140.0 20.0 10900 250 Node Data Node Tag Elevation K Node Tag Elevation K (ft) (ft) 1 30.25 5.62 8A 36.08 0.00 2 31.25 5.62 9A 36.08 0.00 3 30.25 5.62 10A 36.08 0.00 4 28.25 5.62 11A 36.08 0.00 5 31.25 5.62 12A 36.08 0.00 6 31.25 5.62 13A 36.08 0.00 7 31.25 5.62 14A 36.08 0.00 8 30.25 5.62 15A 36.08 0.00 9 28.25 5.62 30 36.80 -182.40 10 31.25 5.62 31 36.08 0.00 11 31.25 5.62 32 36.08 0.00 12 31.25 5.62 33 36.08 0.00 13 31.25 5.62 34 36.08 0.00 14 31.25 5.62 35 36.08 0.00 15 31.25 5.62 36 15.00 0.00 2A 36.08 0.00 TOR 15.00 0.00 1A 36.08 0.00 BOR 2.00 0.00 4A 36.08 0.00 55 2.00 0.00 5A 36.08 0.00 56 1.00 0.00 6A 36.08 0.00 BF -IN 2.00 0.00 7A 36.08 0.00 BF -OUT 2.00 0.00 SOURCE -3.00 SOURCE SPRINKLER SYSTEM INPUT DATA Page 2 DATE: 5/30/2008L:\DAYWORKS KS 7700 +\KS 7953 -WET SEAL\CALCULATIONS\HYDRAULIC CALC'S JOB TITLE: WET SEAL-SOUTHCENTER MALL AREA -1 Pipe Data Pipe Tag End Node Tags Length Fittings Diameter HWC (ft) (ft) (in) 1 1A 1 23.92 2ET 1.049 (A1.000) 120 2 2A 2 8.00 2ET 1.049 (A1.000) 120 3 8A 3 24.17 2ET 1.049 (A1.000) 120 4 4A 4 26.33 2ET 1.049 (A1.000) 120 5 5A 5 5.83 2ET 1.049 (A1.000) 120 6 6A 6 5.83 2ET 1.049 (A1.000) 120 7 7A 7 5.83 2ET 1.049 (A1.000) 120 8 8A 8 25.50 3E 1.049 (A1.000) 120 9 9A 9 22.25 2ET 1.049 (A1.000) 120 10 10A 10 5.50 2ET 1.049 (A1.000) 120 11 11A 11 5.50 2ET 1.049 (A1.000) 120 12 12A 12 5.50 2ET 1.049 (A1.000) 120 13 13A 13 5.25 2ET 1.049 (A1.000) 120 14 14A 14 5.25 2ET 1.049 (A1.000) 120 15 15A 15 5.25 2ET 1.049 (A1.000) 120 18 4A 1A 11.75 0.0 1.610 (A1.500) 120 18A 2A 4A 1.00 0.0 1.610 (A1.500) 120 19 5A 2A 8.00 0.0 1.610 (A1.500) 120 20 6A 5A 12.00 0.0 1.610 (A1.500) 120 21 7A 6A 12.00 0.0 1.610 (A1.500) 120 22 30 7A 8.25 2ET 1.610 (A1.500) 120 23 9A 8A 11.75 0.0 1.610 (A1.500) 120 24 10A 9A 9.00 0.0 1.610 (A1..500) 120 25 11A 10A 12.00 0.0 1.610 (A1.500) 120 26 12A 11A 12.00 0.0 1.610 (A1.500) 120 27 32 12A 4.50 2ET 1.610 (A1.500) 120 28 14A 13A 12.00 0.0 1.610 (A1.500) 120 29 15A 14A 12.00 0.0 1.610 (A1.500) 120 30 33 15A 4.50 2ET 1.610 (A1.500) 120 31 31 30 5.00 0.0 4.260 (B4.000) 120 32 32 31 7.75 0.0 4.260 (84.000) 120 33 33 32 11.00 0.0 4.260 (B4.000) 120 34 34 33 213.00 6ET 4.260 (B4.000) 120 35 35 34 55.00 2E 6.357 (86.000) 120 36 36 35 21.42 E 6.357 (B6.000) 120 37 TOR 36 86.00 8E 6.357 (B6.000) 120 38 BOR TOR 13.00 TCG 6.357 (B6.000) 120 39 55 BOR 19.00 2E 8.249 (B8.000) 120 40 BF -OUT 55 11.00 3E 10.374 (B10.00) 120 41 BF -IN BF -OUT Fixed Loss Device -5.0 psi 42 56 BF -IN 2.00 E 10.374 (B10.00) 120 43 SOURCE 56 80.00 2ETG 10.275 (D10.00) 140 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 5/30/20083 -WET SEAL\CALCULATIONS\HYDRAULIC CALC'S \REMOTE AREA 1.SDF JOB TITLE: WET SEAL-SOUTHCENTER MALL AREA -1 WATER SUPPLY DATA SOURCE NODE TAG SOURCE STATIC RESID. FLOW AVAIL. TOTAL PRESS. PRESS. @ PRESS. @ DEMAND (PSI) (PSI) (GPM) (PSI) (GPM) REQ'D PRESS. (PSI) 140.0 20.0 10900.0 138.8 900.0 118.2 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE TOTAL HOSE STREAM ALLOWANCE AT SOURCE OTHER HOSE STREAM ALLOWANCES TOTAL DISCHARGE FROM ACTIVE SPRINKLERS NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE (FT) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 2A 1A 4A 5A 6A 7A 8A 9A 10A 11A 12A 13A 14A 15A 30 31 32 33 34 30.2 31.2 30.2 28.2 31.2 31.2 31.2 30.2 28.2 31.2 31.2 31.2 31.2 31.2 31.2 36.1 36.1 36.1 36.1 36.1 36.1 36.1 36.1 36.1 36.1 36.1 36.1 36.1 36.1 36.8 36.1 36.1 36.1 36.1 K= K= K= K= K= K= K= K= K= K= K= K= K= K= K= 5.62 5.62 5.62 5.62 5.62 5.62 5.62 5.62 5.62 5.62 5.62 5.62 5.62 5.62 5.62 HOSE STREAM 900.0 GPM 250.0 GPM 182.4 GPM 467.6 GPM PRESSURE (PSI) 21.4 24.3 22.4 21.9 26.2 30.2 36.4 22.7 24.3 28.4 32.4 39.0 46.2 46.8 48.9 26.2 25.8 26.1 27.9 32.4 39.4 27.1 28.3 30.2 34.9 42.2 50.3 50.9 53.3 60.4 60.9 61.1 61.8 90.0 DISCHARGE (GPM) 26.0 27.7 26.6 26.3 28.8 30.9 33.9 26.7 27.7 29.9 32.0 35.1 38.2 38.5 39.3 182.4 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 5/30/20083 -WET SEAL\CALCULATIONS\HYDRAULIC CALC'S\REMOTE AREA 1.SDF JOB TITLE: WET SEAL-SOUTHCENTER MALL AREA -1 NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) 35 36.1 91.1 36 15.0 100.8 TOR 15.0 103.6 BOR 2.0 110.5 55 2.0 110.7 56 1.0 116.2 BF -IN 2.0 115.8 BF -OUT 2.0 - - - - 110.8 - - - SOURCE -3.0 SOURCE 118.2 650.0 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 5/30/20083 -WET SEAL\CALCULATIONS\HYDRAULIC CALC'S\REMOTE AREA 1.SDF JOB TITLE: WET SEAL-SOUTHCENTER MALL AREA -1 PIPE DATA PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 1 26.0 1.049 PL 23.92 PF 7.0 1A 36.1 0.0 25.8 0.0 9.7 120 FTG 2ET PE 2.5 1 30.2 5.6 21.4 26.0 0.211 TL 32.92 PV Pipe: 2 27.7 1.049 PL 8.00 PF 4.0 2A 36.1 0.0 26.2 0.0 10.3 120 FTG 2ET PE 2.1 2 31.2 5.6 24.3 27.7 0.238 TL 17.00 PV Pipe: 3 26.6 1.049 PL 24.17 PF 7.3 8A 36.1 0.0 27.1 0.0 9.9 120 FTG 2ET PE 2.5 3 30.2 5.6 22.4 26.6 0.220 TL 33.17 PV Pipe: 4 26.3 1.049 PL 26.33 PF 7.6 4A 36.1 0.0 26.1 0.0 9.8 120 FTG 2ET PE 3.4 4 28.2 5.6 21.9 26.3 0.216 TL 35.33 PV Pipe: 5 28.8 1.049 PL 5.83 PF 3.8 5A 36.1 0.0 27.9 0.0 10.7 120 FTG 2ET PE 2.1 5 31.2 5.6 26.2 28.8 0.255 TL 14.83 PV Pipe: 6 30.9 1.049 PL 5.83 PF 4.3 6A 36.1 0.0 32.4 0.0 11.5 120 FTG 2ET PE 2.1 6 31.2 5.6 30.2 30.9 0.290 TL 14.83 PV Pipe: 7 33.9 1.049 PL 5.83 PF 5.1 7A 36.1 0.0 39.4 0.0 12.6 120 FTG 2ET PE 2.1 7 31.2 5.6 36.4 33.9 0.345 TL 14.83 PV Pipe: 8 26.7 1.049 PL 25.50 PF 7.0 8A 36.1 0.0 27.1 0.0 9.9 120 FTG 3E PE 2.5 8 30.2 5.6 22.7 26.7 0.223 TL 31.50 PV Pipe: 9 27.7 1.049 PL 22.25 PF 7.4 9A 36.1 0.0 28.3 0.0 10.3 120 FTG 2ET PE 3.4 9 28.2 5.6 24.3 27.7 0.238 TL 31.25 PV Pipe: 10 29.9 1.049 PL 5.50 PF 4.0 10A 36.1 0.0 30.2 0.0 11.1 120 FTG 2ET PE 2.1 10 31.2 5.6 28.4 29.9 0.274 TL 14.50 PV Pipe: 11 32.0 1.049 PL 5.50 PF 4.5 11A 36.1 0.0 34.9 0.0 11.9 120 FTG 2ET PE 2.1 11 31.2 5.6 32.4 32.0 0.311 TL 14.50 PV Pipe: 12 35.1 1.049 PL 5.50 PF 5.3 12A 36.1 0.0 42.2 0.0 13.0 120 FTG 2ET PE 2.1 12 31.2 5.6 39.0 35.1 0.368 TL 14.50 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: 5/30/20083 -WET SEAL\CALCULATIONS\HYDRAULIC CALC'S\REMOTE AREA 1.SDF JOB TITLE: WET SEAL-SOUTHCENTER MALL AREA -1 PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 13 38.2 1.049 PL 5.25 PF 6.1 13A 36.1 0.0 50.3 0.0 14.2 120 FTG 2ET PE 2.1 13 31.2 5.6 46.2 38.2 0.431 TL 14.25 PV Pipe: 14 38.5 1.049 PL 5.25 PF 6.2 14A 36.1 0.0 50.9 0.0 14.3 120 FTG 2ET PE 2.1 14 31.2 5.6 46.8 38.5 0.436 TL 14.25 PV Pipe: 15 39.3 1.049 PL 5.25 PF 6.5 15A 36.1 0.0 53.3 0.0 14.6 120 FTG 2ET PE 2.1 15 31.2 5.6 48.9 39.3 0.454 TL 14.25 PV Pipe: 18 26.0 1.610 PL 11.75 PF 0.3 4A 36.1 0.0 26.1 0.0 4.1 120 FTG ---- PE 0.0 1A 36.1 0.0 25.8 0.0 0.026 TL 11.75 PV Pipe: 18A 52.3 1.610 PL 1.00 PF 0.1 2A 36.1 0.0 26.2 0.0 8.2 120 FTG ---- PE 0.0 4A 36.1 0.0 26.1 0.0 0.096 TL 1.00 PV Pipe: 19 80.0 1.610 PL 8.00 PF 1.7 5A 36.1 0.0 27.9 0.0 12.6 120 FTG ---- PE 0.0 2A 36.1 0.0 26.2 0.0 0.210 TL 8.00 PV Pipe: 20 108.8 1.610 PL 12.00 PF 4.4 6A 36.1 0.0 32.4 0.0 17.1 120 FTG ---- PE 0.0 5A 36.1 0.0 27.9 0.0 0.371 TL 12.00 PV Pipe: 21 139.6 1.610 PL 12.00 PF 7.1 7A 36.1 0.0 39.4 0.0 22.0 120 FTG ---- PE 0.0 6A 36.1 0.0 32.4 0.0 0.588 TL 12.00 PV Pipe: 22 173.6 1.610 PL 8.25 PF 21.3 30 36.8 H.S. 60.4 182.4 27.4 120 FTG 2ET PE 0.3 7A 36.1 0.0 39.4 0.0 0.880 TL 24.25 PV Pipe: 23 53.3 1.610 PL 11.75 PF 1.2 9A 36.1 0.0 28.3 0.0 8.4 120 FTG ---- PE 0.0 8A 36.1 0.0 27.1 0.0 0.099 TL 11.75 PV Pipe: 24 81.0 1.610 PL 9.00 PF 1.9 10A 36.1 0.0 30.2 0.0 12.8 120 FTG ---- PE 0.0 9A 36.1 0.0 28.3 0.0 0.215 TL 9.00 PV Pipe: 25 110.9 1.610 PL 12.00 PF 4.6 11A 36.1 0.0 34.9 0.0 17.5 120 FTG ---- PE 0.0 10A 36.1 0.0 30.2 0.0 0.384 TL 12.00 PV Pipe: 26 143.0 1.610 PL 12.00 PF 7.4 12A 36.1 0.0 42.2 0.0 22.5 120 FTG ---- PE 0.0 11A 36.1 0.0 34.9 0.0 0.614 TL 12.00 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 DATE: 5/30/20083 -WET SEAL\CALCULATIONS\HYDRAULIC CALC'S\REMOTE AREA 1.SDF JOB TITLE: WET SEAL-SOUTHCENTER MALL AREA -1 PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 27 178.0 1.610 PL 4.50 PF 18.9 32 36.1 0.0 61.1 0.0 28.1 120 FTG 2ET PE 0.0 12A 36.1 0.0 42.2 0.0 0.922 TL 20.50 PV Pipe: 28 38.2 1.610 PL 12.00 PF 0.6 14A 36.1 0.0 50.9 0.0 6.0 120 FTG ---- PE 0.0 13A 36.1 0.0 50.3 0.0 0.054 TL 12.00 PV Pipe: 29 76.7 1.610 PL 12.00 PF 2.3 15A 36.1 0.0 53.3 0.0 12.1 120 FTG ---- PE 0.0 14A 36.1 0.0 50.9 0.0 0.194 TL 12.00 PV Pipe: 30 116.0 1.610 PL 4.50 PF 8.6 33 36.1 0.0 61.8 0.0 18.3 120 FTG 2ET PE 0.0 15A 36.1 0.0 53.3 0.0 0.417 TL 20.50 PV Pipe: 31 356.0 4.260 PL 5.00 PF 0.1 31 36.1 0.0 60.9 0.0 8.0 120 FTG ---- PE -0.3 30 36.8 H.S. 60.4 182.4 0.029 TL 5.00 PV Pipe: 32 356.0 4.260 PL 7.75 PF 0.2 32 36.1 0.0 61.1 0.0 8.0 120 FTG ---- PE 0.0 31 36.1 0.0 60.9 0.0 0.029 TL 7.75 PV Pipe: 33 534.0 4.260 PL 11.00 PF 0.7 33 36.1 0.0 61.8 0.0 12.0 120 FTG ---- PE 0.0 32 36.1 0.0 61.1 0.0 0.062 TL 11.00 PV Pipe: 34 650.0 4.260 PL 213.00 PF 28.2 34 36.1 0.0 90.0 0.0 14.6 120 FTG 6ET PE 0.0 33 36.1 0.0 61.8 0.0 0.089 TL 318.50 PV Pipe: 35 650.0 6.357 PL 55.00 PF 1.1 35 36.1 0.0 91.1 0.0 6.6 120 FTG 2E PE 0.0 34 36.1 0.0 90.0 0.0 0.013 TL 90.20 PV Pipe: 36 650.0 6.357 PL 21.42 PF 0.5 36 15.0 0.0 100.8 0.0 6.6 120 FTG E PE -9.1 35 36.1 0.0 91.1 0.0 0.013 TL 39.02 PV Pipe: 37 650.0 6.357 PL 86.00 PF 2.9 TOR 15.0 0.0 103.6 0.0 6.6 120 FTG 8E PE 0.0 36 15.0 0.0 100.8 0.0 0.013 TL 226.80 PV BOR TOR Pipe: 38 650.0 6.357 PL 13.00 PF 1.2 2.0 0.0 110.5 , 0.0 6.6 120 FTG TCG PE -5.6 15.0 0.0 103.6 0.0 0.013 TL 94.70 PV Pipe: 39 650.0 8.249 PL 19.00 PF 0.2 55 2.0 0.0 110.7 0.0 3.9 120 FTG 2E PE 0.0 BOR 2.0 0.0 110.5 0.0 0.004 TL 59.00 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7 DATE: 5/30/20083 -WET SEAL\CALCULATIONS\HYDRAULIC CALC'S\REMOTE AREA 1.SDF JOB TITLE: WET SEAL-SOUTHCENTER MALL AREA -1 PIPE TAG Q(GPM) DIA(IN) LENGTH END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) NODES (FT) (K) (PSI) (GPM) FL/FT PRESS. SUM. (PSI) Pipe: 40 650.0 10.374 PL 11.00 PF 0.1 BF -OUT 2.0 0.0 110.8 0.0 2.5 120 FTG 3E PE 0.0 55 2.0 0.0 110.7 0.0 0.001 TL 84.80 PV Pipe: 41 FIXED PRESSURE LOSS DEVICE BF -IN 2.0 0.0 115.8 0.0 5.0 psi, 650.0 gpm BF -OUT 2.0 0.0 110.8 0.0 Pipe: 42 650.0 10.374 PL 2.00 PF 0.0 56 1.0 0.0 116.2 0.0 2.5 120 FTG E PE -0.4 BF -IN 2.0 0.0 115.8 0.0 0.001 TL 26.60 PV Pipe: 43 650.0 10.275 PL 80.00 PF 0.2 SOURCE -3.0 SRCE 118.2 (N/A) 2.5 140 FTG 2ETG PE -1.7 56 1.0 0.0 116.2 0.0 0.001 TL 220.80 PV NOTES (HASS): (1) Calculations were performed by the HASS 7.9 computer program under license no. 4903012830 granted by HRS Systems, Inc. 4792 LaVista Road Tucker, GA 30084 (2) The system has been calculated to provide an average imbalance at each node of 0.002 gpm and a maximum imbalance at any node of 0.084 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 28.1 ft/sec at pipe 27. (4) PIPE FITTINGS TABLE Pipe Table Name: MOST.PIP PAGE: A MATERIAL: SCH.40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D F Ell Tee LngEll ChkVly BfyVly GatVly AlmChk DPV1v 45E11 H Q I S U V W 22/Ell 11gE11 Couplg FM90E1 FM45E1 FMTee FMRunT 1.049 2.00 5.00 2.00 5.00 6.00 1.00 17.00 23.00 1.00 0.50 0.30 1.00 6.00 5.00 9.00 0.00 1.610 4.00 8.00 2.00 9.00 6.00 1.00 17.00 23.00 2.00 1.00 0.50 1.00 8.00 6.00 12.00 0.00 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 8 DATE: 5/30/20083 -WET SEAL\CALCULATIONS\HYDRAULIC CALC' S\REMOTE AREA 1.SDF JOB TITLE: WET SEAL-SOUTHCENTER MALL AREA -1 PAGE: B MATERIAL: SCH.10 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D F Ell Tee LngEll ChkVly BfyVly GatV1v AlmChk DPV1v 45E11 ----------------------- H Q I S U V W 22/Ell 11gE11 Couplg FM90E1 FM45E1 FMTee FMRunT 4.260 13.20 26.30 7.90 29.00 15.80 2.60 36.90 39.50 6.60 3.30 1.60 1.30 18.40 11.90 31.60 0.00 6.357 17.60 37.70 11.30 40.20 12.60 3.80 37.70 41.50 8.80 4.40 2.20 1.30 22.60 13.80 42.70 0.00 8.249 20.00 38.90 14.50 50.00 13.30 4.40 45.60 41.50 10.00 5.00 2.50 1.10 24.50 14.50 43.40 0.00 10.374 24.60 56.00 17.90 61.60 21.30 5.60 45.60 41.50 12.30 6.20 3.10 1.10 29.10 16.80 56.00 0.00 PAGE: D MATERIAL: DI -52 HWC: 140 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D F Ell Tee LngEll ChkVly BfyVly GatV1v AlmChk DPV1v 45E11 10.275 H Q 22/Ell 11gE11 31.30 71.10 22.70 78.20 27.00 7.10 61.20 47.20 15.60 7.80 3.90 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 9 DATE: 5/30/20083 -WET SEAL\CALCULATIONS\HYDRAULIC CALC'S\REMOTE AREA 1.SDF JOB TITLE: WET SEAL-SOUTHCENTER MALL AREA -1 O 0 0 0.00 psi Flow: • rl UI H O M O • U w,� cr E pE v v tn a) o o U U Sa • a) 0 sa 0 > b N 0 o ri C W al co an a, al fa, s -i C A 2 ( a•CO �aroac°'i W ro o 1 r 0 I-1 ft CO tr'a > m (1) -4• 4 •-•4 ri N B. System O O O O O O O O O 10 d' N O O ri ri ri r -I C7 g W a a W m u, ,7 a W `- ¢,m -H N 0 0 O 0 rI N ' 0 0 0 ri 0 0 rn rn O O X S a 0 w 0 0 0 o O 0 0 0 M M SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 10 DATE: 5/30/20083 -WET SEAL\CALCULATIONS\HYDRAULIC CALC'S\REMOTE AREA 1.SDF JOB TITLE: WET SEAL-SOUTHCENTER MALL AREA -1 WATER SUPPLY CURVE 144+ 0 1\ 132+ \ 1 \ 1 \ 1 \ 120+ \ X 1 1 108+ 1 1 1 P 96+ R 1 E 1 s 1 S 84+ U 1 R 1 E 1 72+ ( 1 P 1 S 1 I 60+ 1 1 1 48+ 1 1 1 36+ 1 1 1 24+ 1 1X 1 12+ 10 1 \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ LEGEND \ 11 * <-20.0 psi @ 10900 gpm = Required Water Supply Flow Test Point 118.16 psi @ 900.0 gpm Available Water Supply 138.81 psi @ 900.0 gpm 11 11 0++-+---+ 32004800 6400 8000 9600 11200 12800 14400 16000 FLOW (GPM) WET SEAL FIRE ALARM `:~SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET \UM3E. SHEET TITLE FA -01 SYST EV I\FO ATI O \ FA -02 TYPICAL DETAILS - WRI\G A \D MOU\TI\G FA -03 FRE ALARM SYSTEM FLOO PLAN FA -04 SYSTE V CALCULATIO\S (GENEAL), �ISE�, SITE PLA\ WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATI❑N LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATI❑N TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD ,DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROVI DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT., 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT). WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 3 2 4 2 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN HELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD 17-3-a LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING D DUCT SMOKE DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 w/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING • CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) gL C FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 4S DEEP BOX W/ 1-1/2" EXT. CEILING 80" A.F.F. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING L C FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -OW SIEMENS L FIRE ALARM STROBE (WALL MOUNT) 4S BOX W/ 1G RING CEILING ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. Q C Q FIRE ALARM SPEAKER (CEILING MOUNT) FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM B b STROBE WP (WEATHERPROOF) MR MULTI -VOLTAGE CONTROL RELAY SET -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -Si 7 -WP SIEMENS MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD MR -201 /C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JBOX FIRE ALARM TERMINAL CABINET F.B.O. r V =K ICY IN FIELD A.F.F. JUNCTI❑N BOX ABOVE FINISHED FLOOR F.B.❑, N/A P N/A • CCe0 N/A Without Comments VERI IN F ELD N/A F.B.D. FURNISHED BY OTHERS N/A N (] As Noted IWggd Per The Attached Letter N/A NOT APPLICABLE N/A U.❑.N, UNLESS OTHERWISE NOTED N/A WP WEATHERPROOF DEVICE N/A RED AS BUILT ADD OR CHANGE N/A i NSA plans have been re\Pib<ded by The Tukwila Fid/A Prevention Bureau for conformance with current city standards. Acceptance is su�. E �..-`1......1to errors and ckiiiAions which do not au(ttorize violations of adoptfflA standards and ordinances. The responsibility for the cuacy of design rests totally with the designer. A," ditions, deletions or revl-F6 S o these drawings; t xt4 this date will void this_acceptance and will require aovat rNessAbmittal of revised draw(ings for sOtbsequtnt ap r . N/A Final acceptance is subject to field test and inspection by TIATukwila Fire. N/A N/A GREEN BLUE AS BUILT REMOVE AS BUILT NOTES TO CAD N/A N/A z Li CD FAX (206) 628-4990 (206) 622-6545 RELEASE/REVISIONS REV. BY: I NVI DESCRIPTION SHOP DRAWINGS DATE 06/04/08 2 a<aaa CO CO J T CO < 0) _! W 1 O W ZZ (l) cW3 = cr 1- Q W Q OJ N � NOTICE A completed, signed, TukvIila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance- Testing of any Fire Alar n and Detection Systems. Failure of test will resu t in a Re -inspection Fee and termination of the testing. PAVVILA FIFE DEPART iita4, please call: 575-4407 and give this job and exact address for shut4 riown or restoration apprcvaI RECEIVED J!1 - 5 2008 37 u, ila Eir/5-?e Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved Z 0 Q EC 0 z N } N SCALE: NOT TO SCALE DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE:06/04/08 BACKROUND PLAN PROVIDED BY: \OB NUMBER: f SHEET FA -01 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE o FROM XLS CONTROL PANEL OR i+ PREVIOUS ADDRESSABLE DEVIC END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH GROUND m DUCT DETECTOR LOCATI❑N HTRI-R STATUS LED oo t\ to 0 0 0 N.O. COM N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE PREVI❑US ADDRESSABLE DEVICE TO NEXT ADDRESSABLE DEVICE (BACKGOUND MUSIC SHUTDOWN) + 0 I0 01 TB1 NOTE 11 VOLTAGE MAX, - CURRENT MAX, - CONT, RES, MAX, - MAX, CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN. LINE SIZE - MUSIC OUTLET SAMPLING - TUBE INLET SAMPLING— TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE �}-AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE 1(+) STOP IF LAST DEVICE {(+) FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVICE (-) RELAY CONTACTS (4.OA @ 125VAC) (4.OA @ 30VDC) 27 VDC 3,5 riA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0,02uF 0,04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTI❑N, 0 S630000 1 2 3 4 5 6 TB2 CP OOH -+ 654321 0 0 /Z END OF LINE DEVICE (3.6K 1/4W) SUPERVISED SWITCH GROUND ' 0 0 0\\Th J HTRI-D STATUS LED Co 0 NOT USED END OF LINE DEVICE 3.6K 1/4W) 0 NOTE: 1 FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC 0 0 0 -1-J- 1- TT TT 0 PAD -3 0 00 0 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+1- 1 2+2- 2 NC C NO + - + - + - + - + - 24K n TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE ,NAC -4 NAC -3 NAC -2 NAC -1 \SUPERVISED SWITCH ( FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE DEVICE LOOP 0 0 0 0 FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY C'S' CABLE) FROM FACP (VOICE CIRCUIT) <'V' CABLE) 470 OHMS �YV EOL TEM -1 0 IDIC O 0 Y 4.6_ CCgc1 --- --- - -- -- -- TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE NO E M STR❑BE) SPEAKER (+) (-) STROBE GROUND ->(+)TO NEXT DEVICE OR 1 >(-) STOP IF LAST DEVICE v u (STROBE( -) SPEAKER SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY 80" A.F.F. 4S DEEP BOX W/ 1-1 /2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE TO NEXT DEVICE OR END OF LINE TO NEXT DEVICE OR END OF LINE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER T1IN TEMPERATU E: +32"F (0' C) TO 100"F 36 C) HUMIDITY: 9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE [DATA IN ( )> DATA IN (+) > DEVICE IS USTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR j-- DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT DEVICE < > ( ) DATA OUT > (+) DATA OUT J7 CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID ^\ CEILING HARD LID —..\ ---SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSI❑N CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTI❑N BOX ---, MOUNTED ON CEILING, FLEX JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT f// / / / 00 /40 0 TO NEXT DEVICE ------CADDY BAR SMOKE DETECTOR— SMOKE ETECTOR— SMOKE DETECTOR MOUNTING SCALE:NONE SUSPENDED ILLUMINATED CEILING DO \OT INSTAL ADDRESSABLE 0\ DEVICES u INTI FREF OC AMIMED W DEVICES ADDRESS. TAT 0\IC T Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved Col I €61 el izt Co CT 0 z_ LL J uJ (1) O LU () rn FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z DESCRIPTION SHOP DRAWINGS DATE 06/04/08 2 a<aa< co co I coT 0) _1 w 0 OC I--- W co~� (!) mow= cc w 5,=< W Q�� cc OJ ND H rTh z z J 0 0 z z E �1 V J f -- W CJ SCALE: NOT TO SCALE DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 06/04/08 BACKROUND PLAN PROVIDED BY: S0B NUMBER: SHEET FA -02 .} EOL -S1 19.96V NORTH WET SEAL WESTFIELD SOUTHCENTER MALL SCALE 118"=1' AG 1\® ES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE, FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS.(SEE SIEMENS INSTALLATI❑N SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR. SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL, FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NO NS AL ADDRESSABLE I\ T A 1 DFVICLS UNTIL DRFRROGRAMMED WI-I-- DEVICES D IDEVICES ADDRESS. NG Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 00 O' ft3 y CA FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z DESCRIPTION SHOP DRAWINGS DATE 06/04/08 <aaaa _! W W W¢ W rzLL co ao co T <7 z cc WO zz U= 2 Q O - cn N 1--- Q W SCALE: 1/8" = 1'0" DRAWN BY: [.ANDERSON DESIGNED BY: R.VEZZANI DATE: 06/04/08 BACKROUND PLAN PROVIDED BY: \:,..19B NUMBER: FA -03} TRASH 0 i1 -J t C7 LJ _r 0 L �_- R TZ TO CO TINDER 90x CT) u_1 l_) Hi • itF H W A Gi;,IE`d�E;_ER c M RS. IELDS JOURNE`(S ----- ----------------------- Ei ASK I N ROBRIN IS t�J 1_:J 11 40 LJ r NORTH ['4401 11 601 0. N.I . C. H Sl F\IGLASS H. ---,, iv LA.R PI ER 01 NC JI ._.r LIDS : SPECS I N TRASH T -; E CITY KID _, f,3 400] v) () LLJ 7: 0 CL_ tom, Z. >-- Co -C'o t () EXIST:NG FOOT OCYER TENANCY '0 -11..OCI, _:r- 1200 :.4 WET SEAL WESTFIELD SOUTHCENTER MALL SCALE 1132"=1' 2S,2V 0 w 0 f== LTJ c_) i L_J v (n 1215] 142°1 D EOL -S1 EX SYSTEM CALCULATIONS BATTERY SIZING CALCULATION WET SEAL WET SEAL FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL DATE 06/04/08 Panel: WET SEAL Wire Resistance 1.62 Date: June 4, 2008 CURRENT TOTAL Current Load: Standby: Alarm: S1 Current Load: Standby: Alarm: _ QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 SET -MC @15CD 64 128 Device Type Qty Amps Total Amps Total 98 Device Type Qty Amps Total Amps Total SET -MC @75CD HFP-11 350 0.0022 0.0022 0.0023 Total Device Load, Amps (I) 0.70 0 SET -MC @110CD 233 0 (Total Cct Load) AD2-P 0 2 0.0635 0.0635 0.064 0.128 Main System Board Voltage Drop ( E) 1 0.03 SET-HMC-C@177CD 0.03 0.030 0.030 HTR -R 3 0.009600 0.0096 0.021 0.063 0 SET -MC @15CD 2 EOL Voltage 19.96 0.064 0.128 445 HTRI-D 0.001600 0.0035 2 SET -MC @30CD 64 1 0.098 0.098 ICP -B6 Z-MC@30CD 98 0.005 SET -MC @75CD 0 2 233 0 0.175 0.350 DEVICES= 7 TOTAL mA= 704 12 191 19.96433664 704 SET -MC @110CD 0.233 Notification Appliance Circuit Detail SET HMC-C@115CD PROJECT: WESTFIELD SOUTHCENTER MALL 0.318 Panel: WET SEAL Wire Resistance 2.58 Date: June 4, 2008 CURRENT TOTAL= SET HMC-C@135CD CIRCUIT: SPEAKER CIRCUIT 0.318 0.0731 Amps 0.191 Amps SET HMC-C@185CD Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 0.445 5 70.7V 1/8 1.8 9 ZR -MC @15CD Total Wire Resistance (R j 2 0 0 0.064 0.128 Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours 0 ZR -MC @30CD 0.098 0.01 0 0 0 HCP 0 0 0 0.0015 Alarm Current Load: 0.191 Amps For 5 Minutes= 0.016 Amp -hours 0.03 Amps 0.734 Amps 0 0 EOL Voltage 20.39 0 0 0 (20.4 - E) 0 25% Derating= 2.213 Amp -hours Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours 0 0 DEVICES= 5 TOTAL mA= 9 14 191 20.39112996) Alarm Current Load: 0.734 Amps For 5 Minutes= 0.062 Amp -hours Total System Current Load: _ 2.213 Amp -hours 25% Derating= 0.977 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.977 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULATION z :5 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-651+5 RELEASE/REVISIONS REV. BY: z Notification Appliance Circuit Detail DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL DATE 06/04/08 Panel: WET SEAL Wire Resistance 1.62 Date: June 4, 2008 CURRENT TOTAL 704 CIRCUIT: S1 _ QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 SET -MC @15CD 64 128 Total Wire Resistance ( R) 0.62 1 SET -MC @30CD 98 98 (WL *2 ) * (R/ft) 2 SET -MC @75CD 175 350 Total Device Load, Amps (I) 0.70 0 SET -MC @110CD 233 0 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 Voltage Drop ( E) 0.44 0 SET-HMC-C@177CD 445 0 (E= I * R) 0 SET -HMC @135CD 318 0 EOL Voltage 19.96 0 SET -HMC @185CD 445 0 (20.4 - E) 2 Z-MC@15CD 64 128 0 Z-MC@30CD 98 0 0 SET-MC-CW@110CD 233 0 DEVICES= 7 TOTAL mA= 704 12 191 19.96433664 704 Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: WET SEAL Wire Resistance 2.58 Date: June 4, 2008 CURRENT TOTAL= 9 CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 5 70.7V 1/8 1.8 9 Total Wire Resistance (R j 0.99 0 0 0 0 0 0 Total Device Load, Amps (1) 0.01 0 0 0 (Total Cct Load) 0 0 0 Voltage Drop (E) 0.01 0 0 0 EOL Voltage 20.39 0 0 0 (20.4 - E) 0 0 0 0 0 0 DEVICES= 5 TOTAL mA= 9 14 191 20.39112996) z :5 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-651+5 RELEASE/REVISIONS REV. BY: z DESCRIPTION SHOP DRAWINGS DATE 06/04/08 co 0) J w (tp g< wl- W~0 U)2 W= Fg - =Q W Q 0> cc 0 N D i - CC w cc< W z W 0 C/)Z a ‘CALE: AS NOTED DRAWN BY: !.ANDERSON DESIGNED BY: R.VEZZANI DATE: 06/04/08 BACKROUND PLAN PROVIDED BY: \0B NUMBER: RISER DIAGRAM VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved SHEET FA -04 NE CE RO 2'X4'A.C.T. LING IN STOCK M ® 12'-0" 1— N W G . BD. CEILING 8'-0 A.F.F. PAINT NEW 2' CEILING CORRID NEW G FLUOR CORRID SURFA 0 X 4' A.C.T. IN EXIT R 0 12'-0" BD. CEILING A:F:FT PAINT - CENT LIGHTS 11R TO BE E MOUNTE S1 Sl UORESCENT LIGHTS OCKROOM TO BE RFACE MOUNTED 13'-8211 2T -G11' Mew .011 ved NEW FIT11NG ROOM 'X4'TEGULAR EILING ® 10'-0" TGC IS TO CUT THE GRIDS OUT AT LIGHTS TO I PROVIDE ACCESS TO CHANGE LAMPS —TRACK LIGHTING ON UNISTRUT SEE DETAIL 2/E102 BOTTOM OF NEW LIGHT COVE 0 12'-l" 11'-421" 2'-0" X 4'-0" WHITE GRID SUSPEND 3" BELOW SOFFIT 5/8" G' '. BD. SOFFIT ® 12'-7 - PAINT 2-11/2 B-012 TRACK LIGHTS IN SALES AREA SURFACE MOUNTED (TYP.) GENERAL NOTE=S I. 2. 3. FILE COPY 4. TGC IS TO CUT THE GRIDS OUT AT LIGHTS TO PROVIDE ACCESS TO CHANGE LAMPS 2'-0" X 4'-0" WHITE GRID SUSPEND 3" BELOW SOFFIT 5/8" GYP. BD. SOFFIT 012'-7" - PAINT BOTTOM OF NEW LIGHT COVE ® 12'-1" 5. 6. 1. 10. 11. 10. 11. 12. 13. 5/8" C J'. BD. SOFFIT 12'-1 - PAINT SIGNAGE. SEE DETAILS ON SHEET A401 .�1 L) FI TTI G ROO S II A DESIGN AND INSTALLATION SHALL CONFORM TO NFPA PAMPHLET 13 AND CITY OF TUKUJILA FIRE DEPT. REQUIREMENTS. ALL MATERIALS SHALL BE NEUJ AND U.L. APPROVED. PIPE: ALL PIPE 2" AND LARGER TO BE SCHEDULE 40 BLACK STEEL. ALL PIPE 2i" AND LARGER TO BE SCHEDULE 10 BLACK STEEL. FITTINGS: ALL FITTING5 (SCREWED AND GROOVED) AND GROOVED COUPLINGS TO BE STAR BRAND DUCTILE IRON. PAINTING OF PIPE AND PROTECTION OF SPRINKLER HEADS FROM PAINT IS BY OTHERS. ALL ELECTRICAL WIRING AND CONDIUT IS BY OTHERS. ALL WELDING TO CONFORM WITH AWS D109 AND WILL BE PERFORMED IN COSCO'S SHOP. It IS THE BUILDING OWNERS RESPONSIBILITY TO KEEP ALL AREAS WITH WET SPRINKLER SYSTEMS HEATED TO A MINIMUM 40 DEGREES FAHRENHEIT TO PREVENT FREEZING OP PIPES. OWNER IS RESPONSIBLE TO ASSURE THAT STRUCTURE AS IT IS SHOWN ON THE CONTRACT DRAWINGS CAN ADEQUATELY SUPPORT ALL FIRE SPRINKLER PIPING LOADS. NO AUXILLIARY DEVICES OR ATTACHMENTS SHALL BE PROVIDED BY COSCO TO SUPPLIMENT THE STRUCTURE TO ACCOMODATE FIRE SPRINKLER PIPING LOADS. COSCO ASSUMES NO RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, FOR THE CONDITION, PERFORMANCE OR CURRENT CODE COMPLIANCE OF THE EXISTING SYSTEM TO BE MODIPIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY COSCO FIRE PROTECTION. UNDERGROUND CONTRACTOR SHALL FLUSH THE UNDERGROUND AND PROVIDE COSCO WITH THE PROPER CERTIFICATE OF DOING SO BEFORE COSCO WILL CONNECT TO THE UNDERGROUND PIPE. SPRINKLER HEADS ARE DESIGNED TO BE IN CENTERLINE OF CEILING TILE (+1- 1"). ALL DIMENSIONS ARE TO CENTERLINE OF PIPE. DOTTED LINES DENOTE EXISTING PIPE. ( -DENOTES EXISTING SPRINKLER HEAD. SYMBOLS/ABREVIATIONS: FUKWILA FIRE DEPARTMENT Please call: 575-4407 and give this job [X' -X"] - DENOTES CENTER LINE OF SPRINKLER PIPE AP °• (-)23 and exact address for shut" >own or restoration approval. X' -X" - DENOTES CEILING HEIGHT. AFF - CENTERLINE OF PIPE. ABOVE FINISHED FLOOR. BDK - CENTERLINE OF PIPE BELOW BOTTOM. •� DECK F - FLEXIBLE GROOVED COUPLING. MT - MECHANICAL TEE AT - HYDRAULIC REFERENCE NODE. ;-) iltzb,r- TGC IS TO CUT THE GRIDS OUT AT LIGHTS TO PROVIDE ACCESS TO CHANGE LAMPS 5/8" GYP. BD. SOFFIT - ®-12'-7 ---PAINS - — { i TRACK LIGHTS IN SALES AREA SURFACE MOUN D (TYP.) /2 1311- .. 1 "A1 TOLCO FIG. 65 C -CLAMP PIPE ROD SIZE DIA 1" 3/8" 11/4" 3/8" 1 I/2" 3/8" 2" 3/8" 2 1/2" 3/8" 3" 3/8" 4" 3/8" 6" 1/2" 8" 1/2" RETAINER STRAP, NUT THREADED ROD HILTI FIG LH OR TOLCO FIG 200 HANGER RING UL 04/2007 COSCO STANDARD HANGER 2 C 1 1131202811 1 FLUORESCENT LIGHT TO BE SURFACE MOUNTED SALcS AREA CEILING 5/8 GYP. BD. ® 13'-0" A.F.F. - PAINT FIRE PROTECTIONPIPING PLAN TOLCO FIG. 78 THREADED STEEL DECK PLATE (2)-I/4" x I" TEK SHEET METAL SCREW PIPE ROD SIZE DIA I" 3/8" 1 I/4" 3/8" 1 1/2" 3/8" 2" 3/8" THREADED ROD HILTI FIG LH OR TOLCO FIG 200 HANGER RING UL 04/2007 COSCO STANDARD HANGER 8 METAL TOLCO FIG. 25 SURGE RESTRAINER TYPE 1 — FOR 1" AND 1-1/4" PIPE AND HANGER TYPE 2 — FOR 1-1/2" AND 2" PIPE AND HANGER SYSTEM PRESSURE EXCEEDS 100 PSI. USE FIG. 25 WITH TOLCO BAND HANGERS FIG. 200 AND 2NFPA TO RESTRAIN THE UPWARD MOVEMENT OF PIPE AS IT OCCURS DURING SPRINKLER HEAD ACTIVATION OR SEISMIC ACTIVITY FIGURE 25 SURGE RESTRAINER. IA FOR STEEL OR CPVC PLASTIC PIPE BRANCHLINE '1- HYDRAULIC REMOTE AREA — A (ORDINARY HAZARD GROUP 2) THIS SYSTEM DESIGNED TO DISCHARGE 0.20 G.P.M. OVER THE HYDRAULIC MOST REMOTE 1500 SQ. FT. WHEN SUPPLIED WITH WATER AT THE CITY CONN. AT A RATE OF 650 G.P.M. AT 110.5 P.S.I. INSIDE HOSE ALLOWANCE: NONE OUTSIDE HOSE ALLOWANCE: 250 G.P.M. 1" X DROP (SEE PLAN) 1" X ARMOVER / (SEE PLAN) SUSPENDED CEILING 1" X 1/2" RC IN TILE CEILINGS -"1" ADJUSTABLE DROP IN GYP BOARD CEILINGS TYPICAL DROP TO SPRINKLER HEAD DESCRIPTION atl •`i'titlmlR4�?'MP4t1W�.Y+�iiaVMwM1'�FuwWM1dMM SPRINKLER HEAD LEGEND : S/N ORIFICE NPT K -FACT. TEMP. 1 1/2" BRANCHLINE Li—IL "FLEXHEAD" FLEXABLE DROP CORRUGATED STAINLESS STEEL BRAIDED HOSE ADJUSTABLE HUB MOUNTING BRACKET \ NE ■ �■ • J w 2' 0" X 4'-O" WHITE GRID SUSPEND 3" BELOW SOFFIT BOTTOM OF NEW LIGHT COVE 12'-l" WHERE LENGTH OF ALL THREAD ROD ARGCO 03B OFFSET EXCEEDS 1'-10" ADD SECOND RESTRAINT F , �r. linage plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. . Acceptance is wubiect to errors and omiseions which do not authorize violations of adopted standards and °romances. The responsibility for the adequacy of design rests tot=ally with the designer. Additions,dal,::tion or ro,visions t) theta { ralr.'ings atter P this date will void t 1 ; t carx;c:pfanc,r.. :;!rid will rc gl.l,re ;1 resubmittal o' .: vised c1 '.&-irigs for sub; equerlt approval. Final accr..pt.;nr..E_ is 3ub;oct to field test and inspection by The Tukwila FTs i, r.:n.,;.ition Bureau. G - -3-U Date: _ l,y: 0 0 Without Comment, t As Noted in Red Per The Attached Utter Lqe 3/8 X 3-1/2 LAG BOLI FOR WOOD - _3/8" KWIK BOLT POR CONCRETE 1/4 X I TEK FOR BARJOIST OR STEEL E3EAM 3/8"x1-10 ALL THREAD ROD MAX PER SINGLE RESTRAINT 1.N ROP PN TO PIPE OR USE TOLCO FIG 25 HANGER RING (UP TO 2" PIPE) LINE RESTRAINT DETAIL SYMBOL =i CEILING NOTE: 1) SPACE UJITN IN 6" OF A HANGER EVERY 42'-0". 2) BRACING PER NFPA-13(200"1 ed.) SECTIONS 93.5.63.8, TABLE 9.3.5.82(c) AND 93.6 -RESTA INT OF BRAN( -1 LINES TYPICAL DROP TO SPRINKLER HEAD IN AC TILE CEILINGS QUAN. RELIABLE MODEL G4A CONCEALED PENDENT RELIABLE MODEL G4A CONCEALED PENDENT RELIABLE Fl FR RECESSED PENDENT R5415 1/2' 1/2' 5.6 BRASS WHITE 165 31 0 R5415 1/2' 1/2' 5.6 BRASS BLACK 165 6 R3615 1/2' 1/2' 5.62 WHITE WHITE 155 10 1 i APPROVALS BY: CITY OF TUKWILLA TOTAL SPRINKLERS THIS SHEET 47 . ®0 0®. • 00 ^ 00• • 00 00®• . 00 0®•• C SC Fire Protection FIRE PROTECTION AND LIFE SAFETY SPECIALISTS www.coscofire.com WASHINGTON OFFICE 15000 Woodinville -Redmond Rd NE Woodinville, Washington 98072 call (425) 686-8300 • fax (425) 827-4784 SAN DIEGO • LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE License No: COSCOFP 11 ONM SPACE 2446 LEVEL -2 ttOTICII[ M kik 1In ‘Dante! McLuen 391-07.6676 11.W111.11.., KEY PLAN PROJECT:WET SEAL 2446 SOUTHCENTER MALL TUKWILLA, WASHINGTON CONTRACT W1rH: JEM CONSTRUCTION 29506 - 8th AVE. S. ROY, WASHINGTON 98580 SPACE #2446 DRAWING TIRE FIRE PROTECTION PLAN 2008 Tukwila Fire; DATE : 5/2008 SCALE : 1 /4"=1'-0" DRAWN BY : D. CLARK 4B,tI(05 KS 7953 SHEET NO. FP -1 of 2 y411:n•001YyNV4 • ;;;y40 Vsk;4'+ yiyal.o"•7fPxiw.44Nt4 Y+ ..�+1N4PUXprpantlWr t :r .-041) �w MEM TAR 10 IE I17Mf® HYDFIAILIO AIM= AMA - A ((pIDNAfff NAZAFID 0110UP Y) THIS SYSTEM DESIGNED TD DISaHRCE 0.20 OVER THE NrDRU$JC MOST REMOTE 1500 S0. FT. WHEN SUPPLIED WON WATER AT THE CITY CONN. ATARATE OF6500.P.U.AT110.5PS.L ONSIDE HOSE ALLOWANCE NONE OUTSIDE HOSE ALLOWANCE 250 C.P.M. gun T vAL1k: 0. C1.EiK WLV1= 6' F6Em MA W TOLri r -r Er =CI= PIT 4TCYR Vaal: Mir= Cid: NY Y Iv =nut rai I}b" GROOVED VA' GIWANR, STAIR #2 STAIR #2 LEVEL -1 !3/32'•1'-0') YY mg • REVISIONS NO. DESCRIPTION DATE SPRINKLER HEAD LEGEND : RELIABLE MODEL G4A CONCEALED PENDENT SYMBOL S/N ORIFICE NPT K -FACT. R5415 5.6 BRASS WHITE TEMP. QUAN. 165 RELIABLE MODEL G4A CONCEALED PENDENT R5415 1/2' 1/2' 5.6 BRASS BLACK 165 6 " RELIABLE F1 FR RECESSED PENDENT R3615 1/2' 1/2' 5.62 WHITE WHITE 155 10 APPROVALS BY: CITY OF TUKWILLA TOTAL SPRINKLERS THIS SHEET 47 .o0 00 . • o® 0 0 o• • ®o Fire Protection FIRE PROTECTION AND LIFE SAFETY SPECIALISTS WASHINGTON OFFICE 15000 Woodinville -Redmond Rd NE Woodinville, Washington 98072 call (425) 686-8300 • fax (425) 827-4784 SAN DIEGO • LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE sc www.coscofire.com License No: COSCOFP 11 ONM PROJECT: WET SEAL 2446 SOUTHCENTER MALL TUKWILLA, WASHINGTON SPACE #2446 CONTRACT WITH: JEM CONSTRUCTION 29506 - 8th AVE. S. ROY, WASHINGTON 98580 DRAWING TITLE SITE PLAN DATE : 5/2008 SCALE : 1/t=11-0" DRAWN BY : D. CLARK 'DB 05 KS 7953 SHEET NO. FP -2 of 2 O 2446 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-289 08-S-262 .7 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Wet Seal 2446 Southcenter Mall Permit No.: 08-S-262 Date: June 3, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). f 1 • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. COSCO FIRE PROTECTION, INC. 10910 - 117TH PLACE, N.E. KIRKLAND,WA 98033-5027 HYDRAULIC CALCULATIONS FOR 'WET SEAL - SPACE 2446 2446 SOUTHCENTER PARKWAY' TUKWILA, WASHINGTON 98188 FILE NUMBER: 25 KS 7953 DATE: MAY 30, 2008 DESIGN DATA: REMOTE AREA - A OCCUPANCY CLASSIFICATION: ORDINARY HAZARD GROUP 2 DENSITY: 0.20 gpm/sq. ft. AREA OF APPLICATION: 1,500 sq. ft. COVERAGE PER SPRINKLER: 130 sq. ft. NUMBER OF SPRINKLERS CALCULATED: 15 sprinklers TOTAL SPRINKLER WATER FLOW REQUIRED: 467.6 gpm TOTAL WATER REQUIRED (including hose): 900.0 gpm FLOW AND PRESSURE (@ BOR): 650 gpm @ 110.5 psi SPRINKLER ORIFICE SIZE: 1/2 inch NOTE: NODES 1,3,4,8,9 ARE ON "FLEX HEAD" FLEXABLE CONNECTIONS. MODEL #2024, 2'-0" LONG, 17'-0" EQUIVILENT FEET OF 1" PIPE. DESIGN/LAYOUT BY: D. CLARK AUTHORITY HAVING JURISDICTION: TUKWILA FIRE DEPT. CONTRACTOR CERTIFICATION NUMBER: COSCOFP110NM CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 4903012830) HRS SYSTEMS, INC. TUCKER, GA 30084 TUCKER, GA 30084 SPRINKLER SYSTEM INPUT DATA Page 1 DATE: 5/30/2008L:\DAYWORKS KS 7700 +\KS 7953 -WET SEAL\CALCULATIONS\HYDRAULIC CALC'S JOB TITLE: WET SEAL-SOUTHCENTER MALL AREA -1 Source Nodes Node Tag Elevation Static Residual Residual Hose Stream Pressure Pressure Flow Allowance (ft) (psi) (psi) (gpm) (gpm) SOURCE -3.00 140.0 20.0 10900 250 Node Data Node Tag Elevation K Node Tag Elevation K (ft) (ft) 1 30.25 5.62 8A 36.08 0.00 2 31.25 5.62 9A 36.08 0.00 3 30.25 5.62 10A 36.08 0.00 4 28.25 5.62 11A 36.08 0.00 5 31.25 5.62 12A 36.08 0.00 6 31.25 5.62 13A 36.08 0.00 7 31.25 5.62 14A 36.08 0.00 8 30.25 5.62 15A 36.08 0.00 9 28.25 5.62 30 36.80 -182.40 10 31.25 5.62 31 36.08 0.00 11 31.25 5.62 32 36.08 0.00 12 31.25 5.62 33 36.08 0.00 13 31.25 5.62 34 36.08 0.00 14 31.25 5.62 35 36.08 0.00 15 31.25 5.62 36 15.00 0.00 2A 36.08 0.00 TOR 15.00 0.00 1A 36.08 0.00 BOR 2.00 0.00 4A 36.08 0.00 55 2.00 0.00 5A 36.08 0.00 56 1.00 0.00 6A 36.08 0.00 BF -IN 2.00 0.00 7A 36.08 0.00 BF -OUT 2.00 0.00 SOURCE -3.00 SOURCE SPRINKLER SYSTEM INPUT DATA Page 2 DATE: 5/30/2008L:\DAYWORKS KS 7700 +\KS 7953 -WET SEAL\CALCULATIONS\HYDRAULIC CALC'S JOB TITLE: WET SEAL-SOUTHCENTER MALL AREA -1 Pipe Data Pipe Tag End Node Tags Length Fittings Diameter HWC (ft) (ft) (in) 1 1A 1 23.92 2ET 1.049 (A1.000) 120 2 2A 2 8.00 2ET 1.049 (A1.000) 120 3 8A 3 24.17 2ET 1.049 (A1.000) 120 4 4A 4 26.33 2ET 1.049 (A1.000) 120 5 5A 5 5.83 2ET 1.049 (A1.000) 120 6 6A 6 5.83 2ET 1.049 (A1.000) 120 7 7A 7 5.83 2ET 1.049 (A1.000) 120 8 8A 8 25.50 3E 1.049 (A1.000) 120 9 9A 9 22.25 2ET 1.049 (A1.000) 120 10 10A 10 5.50 2ET 1.049 (A1.000) 120 11 11A 11 5.50 2ET 1.049 (A1.000) 120 12 12A 12 5.50 2ET 1.049 (A1.000) 120 13 13A 13 5.25 2ET 1.049 (A1.000) 120 14 14A 14 5.25 2ET 1.049 (A1.000) 120 15 15A 15 5.25 2ET 1.049 (A1.000) 120 18 4A 1A 11.75 0.0 1.610 (A1.500) 120 18A 2A 4A 1.00 0.0 1.610 (A1.500) 120 19 5A 2A 8.00 0.0 1.610 (A1.500) 120 20 6A 5A 12.00 0.0 1.610 (A1.500) 120 21 7A 6A 12.00 0.0 1.610 (A1.500) 120 22 30 7A 8.25 2ET 1.610 (A1.500) 120 23 9A 8A 11.75 0.0 1.610 (A1.500) 120 24 10A 9A 9.00 0.0 1.610 (A1..500) 120 25 11A 10A 12.00 0.0 1.610 (A1.500) 120 26 12A 11A 12.00 0.0 1.610 (A1.500) 120 27 32 12A 4.50 2ET 1.610 (A1.500) 120 28 14A 13A 12.00 0.0 1.610 (A1.500) 120 29 15A 14A 12.00 0.0 1.610 (A1.500) 120 30 33 15A 4.50 2ET 1.610 (A1.500) 120 31 31 30 5.00 0.0 4.260 (B4.000) 120 32 32 31 7.75 0.0 4.260 (84.000) 120 33 33 32 11.00 0.0 4.260 (B4.000) 120 34 34 33 213.00 6ET 4.260 (B4.000) 120 35 35 34 55.00 2E 6.357 (86.000) 120 36 36 35 21.42 E 6.357 (B6.000) 120 37 TOR 36 86.00 8E 6.357 (B6.000) 120 38 BOR TOR 13.00 TCG 6.357 (B6.000) 120 39 55 BOR 19.00 2E 8.249 (B8.000) 120 40 BF -OUT 55 11.00 3E 10.374 (B10.00) 120 41 BF -IN BF -OUT Fixed Loss Device -5.0 psi 42 56 BF -IN 2.00 E 10.374 (B10.00) 120 43 SOURCE 56 80.00 2ETG 10.275 (D10.00) 140 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 5/30/20083 -WET SEAL\CALCULATIONS\HYDRAULIC CALC'S \REMOTE AREA 1.SDF JOB TITLE: WET SEAL-SOUTHCENTER MALL AREA -1 WATER SUPPLY DATA SOURCE NODE TAG SOURCE STATIC RESID. FLOW AVAIL. TOTAL PRESS. PRESS. @ PRESS. @ DEMAND (PSI) (PSI) (GPM) (PSI) (GPM) REQ'D PRESS. (PSI) 140.0 20.0 10900.0 138.8 900.0 118.2 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE TOTAL HOSE STREAM ALLOWANCE AT SOURCE OTHER HOSE STREAM ALLOWANCES TOTAL DISCHARGE FROM ACTIVE SPRINKLERS NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE (FT) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 2A 1A 4A 5A 6A 7A 8A 9A 10A 11A 12A 13A 14A 15A 30 31 32 33 34 30.2 31.2 30.2 28.2 31.2 31.2 31.2 30.2 28.2 31.2 31.2 31.2 31.2 31.2 31.2 36.1 36.1 36.1 36.1 36.1 36.1 36.1 36.1 36.1 36.1 36.1 36.1 36.1 36.1 36.8 36.1 36.1 36.1 36.1 K= K= K= K= K= K= K= K= K= K= K= K= K= K= K= 5.62 5.62 5.62 5.62 5.62 5.62 5.62 5.62 5.62 5.62 5.62 5.62 5.62 5.62 5.62 HOSE STREAM 900.0 GPM 250.0 GPM 182.4 GPM 467.6 GPM PRESSURE (PSI) 21.4 24.3 22.4 21.9 26.2 30.2 36.4 22.7 24.3 28.4 32.4 39.0 46.2 46.8 48.9 26.2 25.8 26.1 27.9 32.4 39.4 27.1 28.3 30.2 34.9 42.2 50.3 50.9 53.3 60.4 60.9 61.1 61.8 90.0 DISCHARGE (GPM) 26.0 27.7 26.6 26.3 28.8 30.9 33.9 26.7 27.7 29.9 32.0 35.1 38.2 38.5 39.3 182.4 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 5/30/20083 -WET SEAL\CALCULATIONS\HYDRAULIC CALC'S\REMOTE AREA 1.SDF JOB TITLE: WET SEAL-SOUTHCENTER MALL AREA -1 NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) 35 36.1 91.1 36 15.0 100.8 TOR 15.0 103.6 BOR 2.0 110.5 55 2.0 110.7 56 1.0 116.2 BF -IN 2.0 115.8 BF -OUT 2.0 - - - - 110.8 - - - SOURCE -3.0 SOURCE 118.2 650.0 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 5/30/20083 -WET SEAL\CALCULATIONS\HYDRAULIC CALC'S\REMOTE AREA 1.SDF JOB TITLE: WET SEAL-SOUTHCENTER MALL AREA -1 PIPE DATA PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 1 26.0 1.049 PL 23.92 PF 7.0 1A 36.1 0.0 25.8 0.0 9.7 120 FTG 2ET PE 2.5 1 30.2 5.6 21.4 26.0 0.211 TL 32.92 PV Pipe: 2 27.7 1.049 PL 8.00 PF 4.0 2A 36.1 0.0 26.2 0.0 10.3 120 FTG 2ET PE 2.1 2 31.2 5.6 24.3 27.7 0.238 TL 17.00 PV Pipe: 3 26.6 1.049 PL 24.17 PF 7.3 8A 36.1 0.0 27.1 0.0 9.9 120 FTG 2ET PE 2.5 3 30.2 5.6 22.4 26.6 0.220 TL 33.17 PV Pipe: 4 26.3 1.049 PL 26.33 PF 7.6 4A 36.1 0.0 26.1 0.0 9.8 120 FTG 2ET PE 3.4 4 28.2 5.6 21.9 26.3 0.216 TL 35.33 PV Pipe: 5 28.8 1.049 PL 5.83 PF 3.8 5A 36.1 0.0 27.9 0.0 10.7 120 FTG 2ET PE 2.1 5 31.2 5.6 26.2 28.8 0.255 TL 14.83 PV Pipe: 6 30.9 1.049 PL 5.83 PF 4.3 6A 36.1 0.0 32.4 0.0 11.5 120 FTG 2ET PE 2.1 6 31.2 5.6 30.2 30.9 0.290 TL 14.83 PV Pipe: 7 33.9 1.049 PL 5.83 PF 5.1 7A 36.1 0.0 39.4 0.0 12.6 120 FTG 2ET PE 2.1 7 31.2 5.6 36.4 33.9 0.345 TL 14.83 PV Pipe: 8 26.7 1.049 PL 25.50 PF 7.0 8A 36.1 0.0 27.1 0.0 9.9 120 FTG 3E PE 2.5 8 30.2 5.6 22.7 26.7 0.223 TL 31.50 PV Pipe: 9 27.7 1.049 PL 22.25 PF 7.4 9A 36.1 0.0 28.3 0.0 10.3 120 FTG 2ET PE 3.4 9 28.2 5.6 24.3 27.7 0.238 TL 31.25 PV Pipe: 10 29.9 1.049 PL 5.50 PF 4.0 10A 36.1 0.0 30.2 0.0 11.1 120 FTG 2ET PE 2.1 10 31.2 5.6 28.4 29.9 0.274 TL 14.50 PV Pipe: 11 32.0 1.049 PL 5.50 PF 4.5 11A 36.1 0.0 34.9 0.0 11.9 120 FTG 2ET PE 2.1 11 31.2 5.6 32.4 32.0 0.311 TL 14.50 PV Pipe: 12 35.1 1.049 PL 5.50 PF 5.3 12A 36.1 0.0 42.2 0.0 13.0 120 FTG 2ET PE 2.1 12 31.2 5.6 39.0 35.1 0.368 TL 14.50 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: 5/30/20083 -WET SEAL\CALCULATIONS\HYDRAULIC CALC'S\REMOTE AREA 1.SDF JOB TITLE: WET SEAL-SOUTHCENTER MALL AREA -1 PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 13 38.2 1.049 PL 5.25 PF 6.1 13A 36.1 0.0 50.3 0.0 14.2 120 FTG 2ET PE 2.1 13 31.2 5.6 46.2 38.2 0.431 TL 14.25 PV Pipe: 14 38.5 1.049 PL 5.25 PF 6.2 14A 36.1 0.0 50.9 0.0 14.3 120 FTG 2ET PE 2.1 14 31.2 5.6 46.8 38.5 0.436 TL 14.25 PV Pipe: 15 39.3 1.049 PL 5.25 PF 6.5 15A 36.1 0.0 53.3 0.0 14.6 120 FTG 2ET PE 2.1 15 31.2 5.6 48.9 39.3 0.454 TL 14.25 PV Pipe: 18 26.0 1.610 PL 11.75 PF 0.3 4A 36.1 0.0 26.1 0.0 4.1 120 FTG ---- PE 0.0 1A 36.1 0.0 25.8 0.0 0.026 TL 11.75 PV Pipe: 18A 52.3 1.610 PL 1.00 PF 0.1 2A 36.1 0.0 26.2 0.0 8.2 120 FTG ---- PE 0.0 4A 36.1 0.0 26.1 0.0 0.096 TL 1.00 PV Pipe: 19 80.0 1.610 PL 8.00 PF 1.7 5A 36.1 0.0 27.9 0.0 12.6 120 FTG ---- PE 0.0 2A 36.1 0.0 26.2 0.0 0.210 TL 8.00 PV Pipe: 20 108.8 1.610 PL 12.00 PF 4.4 6A 36.1 0.0 32.4 0.0 17.1 120 FTG ---- PE 0.0 5A 36.1 0.0 27.9 0.0 0.371 TL 12.00 PV Pipe: 21 139.6 1.610 PL 12.00 PF 7.1 7A 36.1 0.0 39.4 0.0 22.0 120 FTG ---- PE 0.0 6A 36.1 0.0 32.4 0.0 0.588 TL 12.00 PV Pipe: 22 173.6 1.610 PL 8.25 PF 21.3 30 36.8 H.S. 60.4 182.4 27.4 120 FTG 2ET PE 0.3 7A 36.1 0.0 39.4 0.0 0.880 TL 24.25 PV Pipe: 23 53.3 1.610 PL 11.75 PF 1.2 9A 36.1 0.0 28.3 0.0 8.4 120 FTG ---- PE 0.0 8A 36.1 0.0 27.1 0.0 0.099 TL 11.75 PV Pipe: 24 81.0 1.610 PL 9.00 PF 1.9 10A 36.1 0.0 30.2 0.0 12.8 120 FTG ---- PE 0.0 9A 36.1 0.0 28.3 0.0 0.215 TL 9.00 PV Pipe: 25 110.9 1.610 PL 12.00 PF 4.6 11A 36.1 0.0 34.9 0.0 17.5 120 FTG ---- PE 0.0 10A 36.1 0.0 30.2 0.0 0.384 TL 12.00 PV Pipe: 26 143.0 1.610 PL 12.00 PF 7.4 12A 36.1 0.0 42.2 0.0 22.5 120 FTG ---- PE 0.0 11A 36.1 0.0 34.9 0.0 0.614 TL 12.00 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 DATE: 5/30/20083 -WET SEAL\CALCULATIONS\HYDRAULIC CALC'S\REMOTE AREA 1.SDF JOB TITLE: WET SEAL-SOUTHCENTER MALL AREA -1 PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 27 178.0 1.610 PL 4.50 PF 18.9 32 36.1 0.0 61.1 0.0 28.1 120 FTG 2ET PE 0.0 12A 36.1 0.0 42.2 0.0 0.922 TL 20.50 PV Pipe: 28 38.2 1.610 PL 12.00 PF 0.6 14A 36.1 0.0 50.9 0.0 6.0 120 FTG ---- PE 0.0 13A 36.1 0.0 50.3 0.0 0.054 TL 12.00 PV Pipe: 29 76.7 1.610 PL 12.00 PF 2.3 15A 36.1 0.0 53.3 0.0 12.1 120 FTG ---- PE 0.0 14A 36.1 0.0 50.9 0.0 0.194 TL 12.00 PV Pipe: 30 116.0 1.610 PL 4.50 PF 8.6 33 36.1 0.0 61.8 0.0 18.3 120 FTG 2ET PE 0.0 15A 36.1 0.0 53.3 0.0 0.417 TL 20.50 PV Pipe: 31 356.0 4.260 PL 5.00 PF 0.1 31 36.1 0.0 60.9 0.0 8.0 120 FTG ---- PE -0.3 30 36.8 H.S. 60.4 182.4 0.029 TL 5.00 PV Pipe: 32 356.0 4.260 PL 7.75 PF 0.2 32 36.1 0.0 61.1 0.0 8.0 120 FTG ---- PE 0.0 31 36.1 0.0 60.9 0.0 0.029 TL 7.75 PV Pipe: 33 534.0 4.260 PL 11.00 PF 0.7 33 36.1 0.0 61.8 0.0 12.0 120 FTG ---- PE 0.0 32 36.1 0.0 61.1 0.0 0.062 TL 11.00 PV Pipe: 34 650.0 4.260 PL 213.00 PF 28.2 34 36.1 0.0 90.0 0.0 14.6 120 FTG 6ET PE 0.0 33 36.1 0.0 61.8 0.0 0.089 TL 318.50 PV Pipe: 35 650.0 6.357 PL 55.00 PF 1.1 35 36.1 0.0 91.1 0.0 6.6 120 FTG 2E PE 0.0 34 36.1 0.0 90.0 0.0 0.013 TL 90.20 PV Pipe: 36 650.0 6.357 PL 21.42 PF 0.5 36 15.0 0.0 100.8 0.0 6.6 120 FTG E PE -9.1 35 36.1 0.0 91.1 0.0 0.013 TL 39.02 PV Pipe: 37 650.0 6.357 PL 86.00 PF 2.9 TOR 15.0 0.0 103.6 0.0 6.6 120 FTG 8E PE 0.0 36 15.0 0.0 100.8 0.0 0.013 TL 226.80 PV BOR TOR Pipe: 38 650.0 6.357 PL 13.00 PF 1.2 2.0 0.0 110.5 , 0.0 6.6 120 FTG TCG PE -5.6 15.0 0.0 103.6 0.0 0.013 TL 94.70 PV Pipe: 39 650.0 8.249 PL 19.00 PF 0.2 55 2.0 0.0 110.7 0.0 3.9 120 FTG 2E PE 0.0 BOR 2.0 0.0 110.5 0.0 0.004 TL 59.00 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7 DATE: 5/30/20083 -WET SEAL\CALCULATIONS\HYDRAULIC CALC'S\REMOTE AREA 1.SDF JOB TITLE: WET SEAL-SOUTHCENTER MALL AREA -1 PIPE TAG Q(GPM) DIA(IN) LENGTH END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) NODES (FT) (K) (PSI) (GPM) FL/FT PRESS. SUM. (PSI) Pipe: 40 650.0 10.374 PL 11.00 PF 0.1 BF -OUT 2.0 0.0 110.8 0.0 2.5 120 FTG 3E PE 0.0 55 2.0 0.0 110.7 0.0 0.001 TL 84.80 PV Pipe: 41 FIXED PRESSURE LOSS DEVICE BF -IN 2.0 0.0 115.8 0.0 5.0 psi, 650.0 gpm BF -OUT 2.0 0.0 110.8 0.0 Pipe: 42 650.0 10.374 PL 2.00 PF 0.0 56 1.0 0.0 116.2 0.0 2.5 120 FTG E PE -0.4 BF -IN 2.0 0.0 115.8 0.0 0.001 TL 26.60 PV Pipe: 43 650.0 10.275 PL 80.00 PF 0.2 SOURCE -3.0 SRCE 118.2 (N/A) 2.5 140 FTG 2ETG PE -1.7 56 1.0 0.0 116.2 0.0 0.001 TL 220.80 PV NOTES (HASS): (1) Calculations were performed by the HASS 7.9 computer program under license no. 4903012830 granted by HRS Systems, Inc. 4792 LaVista Road Tucker, GA 30084 (2) The system has been calculated to provide an average imbalance at each node of 0.002 gpm and a maximum imbalance at any node of 0.084 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 28.1 ft/sec at pipe 27. (4) PIPE FITTINGS TABLE Pipe Table Name: MOST.PIP PAGE: A MATERIAL: SCH.40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D F Ell Tee LngEll ChkVly BfyVly GatVly AlmChk DPV1v 45E11 H Q I S U V W 22/Ell 11gE11 Couplg FM90E1 FM45E1 FMTee FMRunT 1.049 2.00 5.00 2.00 5.00 6.00 1.00 17.00 23.00 1.00 0.50 0.30 1.00 6.00 5.00 9.00 0.00 1.610 4.00 8.00 2.00 9.00 6.00 1.00 17.00 23.00 2.00 1.00 0.50 1.00 8.00 6.00 12.00 0.00 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 8 DATE: 5/30/20083 -WET SEAL\CALCULATIONS\HYDRAULIC CALC' S\REMOTE AREA 1.SDF JOB TITLE: WET SEAL-SOUTHCENTER MALL AREA -1 PAGE: B MATERIAL: SCH.10 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D F Ell Tee LngEll ChkVly BfyVly GatV1v AlmChk DPV1v 45E11 ----------------------- H Q I S U V W 22/Ell 11gE11 Couplg FM90E1 FM45E1 FMTee FMRunT 4.260 13.20 26.30 7.90 29.00 15.80 2.60 36.90 39.50 6.60 3.30 1.60 1.30 18.40 11.90 31.60 0.00 6.357 17.60 37.70 11.30 40.20 12.60 3.80 37.70 41.50 8.80 4.40 2.20 1.30 22.60 13.80 42.70 0.00 8.249 20.00 38.90 14.50 50.00 13.30 4.40 45.60 41.50 10.00 5.00 2.50 1.10 24.50 14.50 43.40 0.00 10.374 24.60 56.00 17.90 61.60 21.30 5.60 45.60 41.50 12.30 6.20 3.10 1.10 29.10 16.80 56.00 0.00 PAGE: D MATERIAL: DI -52 HWC: 140 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D F Ell Tee LngEll ChkVly BfyVly GatV1v AlmChk DPV1v 45E11 10.275 H Q 22/Ell 11gE11 31.30 71.10 22.70 78.20 27.00 7.10 61.20 47.20 15.60 7.80 3.90 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 9 DATE: 5/30/20083 -WET SEAL\CALCULATIONS\HYDRAULIC CALC'S\REMOTE AREA 1.SDF JOB TITLE: WET SEAL-SOUTHCENTER MALL AREA -1 O 0 0 0.00 psi Flow: • rl UI H O M O • U w,� cr E pE v v tn a) o o U U Sa • a) 0 sa 0 > b N 0 o ri C W al co an a, al fa, s -i C A 2 ( a•CO �aroac°'i W ro o 1 r 0 I-1 ft CO tr'a > m (1) -4• 4 •-•4 ri N B. System O O O O O O O O O 10 d' N O O ri ri ri r -I C7 g W a a W m u, ,7 a W `- ¢,m -H N 0 0 O 0 rI N ' 0 0 0 ri 0 0 rn rn O O X S a 0 w 0 0 0 o O 0 0 0 M M SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 10 DATE: 5/30/20083 -WET SEAL\CALCULATIONS\HYDRAULIC CALC'S\REMOTE AREA 1.SDF JOB TITLE: WET SEAL-SOUTHCENTER MALL AREA -1 WATER SUPPLY CURVE 144+ 0 1\ 132+ \ 1 \ 1 \ 1 \ 120+ \ X 1 1 108+ 1 1 1 P 96+ R 1 E 1 s 1 S 84+ U 1 R 1 E 1 72+ ( 1 P 1 S 1 I 60+ 1 1 1 48+ 1 1 1 36+ 1 1 1 24+ 1 1X 1 12+ 10 1 \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ LEGEND \ 11 * <-20.0 psi @ 10900 gpm = Required Water Supply Flow Test Point 118.16 psi @ 900.0 gpm Available Water Supply 138.81 psi @ 900.0 gpm 11 11 0++-+---+ 32004800 6400 8000 9600 11200 12800 14400 16000 FLOW (GPM) WET SEAL FIRE ALARM `:~SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET \UM3E. SHEET TITLE FA -01 SYST EV I\FO ATI O \ FA -02 TYPICAL DETAILS - WRI\G A \D MOU\TI\G FA -03 FRE ALARM SYSTEM FLOO PLAN FA -04 SYSTE V CALCULATIO\S (GENEAL), �ISE�, SITE PLA\ WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATI❑N LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATI❑N TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD ,DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROVI DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT., 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT). WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 3 2 4 2 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN HELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD 17-3-a LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING D DUCT SMOKE DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 w/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING • CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) gL C FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 4S DEEP BOX W/ 1-1/2" EXT. CEILING 80" A.F.F. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING L C FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -OW SIEMENS L FIRE ALARM STROBE (WALL MOUNT) 4S BOX W/ 1G RING CEILING ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. Q C Q FIRE ALARM SPEAKER (CEILING MOUNT) FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM B b STROBE WP (WEATHERPROOF) MR MULTI -VOLTAGE CONTROL RELAY SET -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -Si 7 -WP SIEMENS MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD MR -201 /C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JBOX FIRE ALARM TERMINAL CABINET F.B.O. r V =K ICY IN FIELD A.F.F. JUNCTI❑N BOX ABOVE FINISHED FLOOR F.B.❑, N/A P N/A • CCe0 N/A Without Comments VERI IN F ELD N/A F.B.D. FURNISHED BY OTHERS N/A N (] As Noted IWggd Per The Attached Letter N/A NOT APPLICABLE N/A U.❑.N, UNLESS OTHERWISE NOTED N/A WP WEATHERPROOF DEVICE N/A RED AS BUILT ADD OR CHANGE N/A i NSA plans have been re\Pib<ded by The Tukwila Fid/A Prevention Bureau for conformance with current city standards. Acceptance is su�. E �..-`1......1to errors and ckiiiAions which do not au(ttorize violations of adoptfflA standards and ordinances. The responsibility for the cuacy of design rests totally with the designer. A," ditions, deletions or revl-F6 S o these drawings; t xt4 this date will void this_acceptance and will require aovat rNessAbmittal of revised draw(ings for sOtbsequtnt ap r . N/A Final acceptance is subject to field test and inspection by TIATukwila Fire. N/A N/A GREEN BLUE AS BUILT REMOVE AS BUILT NOTES TO CAD N/A N/A z Li CD FAX (206) 628-4990 (206) 622-6545 RELEASE/REVISIONS REV. BY: I NVI DESCRIPTION SHOP DRAWINGS DATE 06/04/08 2 a<aaa CO CO J T CO < 0) _! W 1 O W ZZ (l) cW3 = cr 1- Q W Q OJ N � NOTICE A completed, signed, TukvIila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance- Testing of any Fire Alar n and Detection Systems. Failure of test will resu t in a Re -inspection Fee and termination of the testing. PAVVILA FIFE DEPART iita4, please call: 575-4407 and give this job and exact address for shut4 riown or restoration apprcvaI RECEIVED J!1 - 5 2008 37 u, ila Eir/5-?e Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved Z 0 Q EC 0 z N } N SCALE: NOT TO SCALE DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE:06/04/08 BACKROUND PLAN PROVIDED BY: \OB NUMBER: f SHEET FA -01 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE o FROM XLS CONTROL PANEL OR i+ PREVIOUS ADDRESSABLE DEVIC END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH GROUND m DUCT DETECTOR LOCATI❑N HTRI-R STATUS LED oo t\ to 0 0 0 N.O. COM N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE PREVI❑US ADDRESSABLE DEVICE TO NEXT ADDRESSABLE DEVICE (BACKGOUND MUSIC SHUTDOWN) + 0 I0 01 TB1 NOTE 11 VOLTAGE MAX, - CURRENT MAX, - CONT, RES, MAX, - MAX, CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN. LINE SIZE - MUSIC OUTLET SAMPLING - TUBE INLET SAMPLING— TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE �}-AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE 1(+) STOP IF LAST DEVICE {(+) FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVICE (-) RELAY CONTACTS (4.OA @ 125VAC) (4.OA @ 30VDC) 27 VDC 3,5 riA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0,02uF 0,04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTI❑N, 0 S630000 1 2 3 4 5 6 TB2 CP OOH -+ 654321 0 0 /Z END OF LINE DEVICE (3.6K 1/4W) SUPERVISED SWITCH GROUND ' 0 0 0\\Th J HTRI-D STATUS LED Co 0 NOT USED END OF LINE DEVICE 3.6K 1/4W) 0 NOTE: 1 FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC 0 0 0 -1-J- 1- TT TT 0 PAD -3 0 00 0 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+1- 1 2+2- 2 NC C NO + - + - + - + - + - 24K n TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE ,NAC -4 NAC -3 NAC -2 NAC -1 \SUPERVISED SWITCH ( FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE DEVICE LOOP 0 0 0 0 FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY C'S' CABLE) FROM FACP (VOICE CIRCUIT) <'V' CABLE) 470 OHMS �YV EOL TEM -1 0 IDIC O 0 Y 4.6_ CCgc1 --- --- - -- -- -- TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE NO E M STR❑BE) SPEAKER (+) (-) STROBE GROUND ->(+)TO NEXT DEVICE OR 1 >(-) STOP IF LAST DEVICE v u (STROBE( -) SPEAKER SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY 80" A.F.F. 4S DEEP BOX W/ 1-1 /2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE TO NEXT DEVICE OR END OF LINE TO NEXT DEVICE OR END OF LINE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER T1IN TEMPERATU E: +32"F (0' C) TO 100"F 36 C) HUMIDITY: 9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE [DATA IN ( )> DATA IN (+) > DEVICE IS USTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR j-- DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT DEVICE < > ( ) DATA OUT > (+) DATA OUT J7 CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID ^\ CEILING HARD LID —..\ ---SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSI❑N CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTI❑N BOX ---, MOUNTED ON CEILING, FLEX JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT f// / / / 00 /40 0 TO NEXT DEVICE ------CADDY BAR SMOKE DETECTOR— SMOKE ETECTOR— SMOKE DETECTOR MOUNTING SCALE:NONE SUSPENDED ILLUMINATED CEILING DO \OT INSTAL ADDRESSABLE 0\ DEVICES u INTI FREF OC AMIMED W DEVICES ADDRESS. TAT 0\IC T Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved Col I €61 el izt Co CT 0 z_ LL J uJ (1) O LU () rn FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z DESCRIPTION SHOP DRAWINGS DATE 06/04/08 2 a<aa< co co I coT 0) _1 w 0 OC I--- W co~� (!) mow= cc w 5,=< W Q�� cc OJ ND H rTh z z J 0 0 z z E �1 V J f -- W CJ SCALE: NOT TO SCALE DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 06/04/08 BACKROUND PLAN PROVIDED BY: S0B NUMBER: SHEET FA -02 .} EOL -S1 19.96V NORTH WET SEAL WESTFIELD SOUTHCENTER MALL SCALE 118"=1' AG 1\® ES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE, FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS.(SEE SIEMENS INSTALLATI❑N SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR. SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL, FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NO NS AL ADDRESSABLE I\ T A 1 DFVICLS UNTIL DRFRROGRAMMED WI-I-- DEVICES D IDEVICES ADDRESS. NG Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 00 O' ft3 y CA FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z DESCRIPTION SHOP DRAWINGS DATE 06/04/08 <aaaa _! W W W¢ W rzLL co ao co T <7 z cc WO zz U= 2 Q O - cn N 1--- Q W SCALE: 1/8" = 1'0" DRAWN BY: [.ANDERSON DESIGNED BY: R.VEZZANI DATE: 06/04/08 BACKROUND PLAN PROVIDED BY: \:,..19B NUMBER: FA -03} TRASH 0 i1 -J t C7 LJ _r 0 L �_- R TZ TO CO TINDER 90x CT) u_1 l_) Hi • itF H W A Gi;,IE`d�E;_ER c M RS. IELDS JOURNE`(S ----- ----------------------- Ei ASK I N ROBRIN IS t�J 1_:J 11 40 LJ r NORTH ['4401 11 601 0. N.I . C. H Sl F\IGLASS H. ---,, iv LA.R PI ER 01 NC JI ._.r LIDS : SPECS I N TRASH T -; E CITY KID _, f,3 400] v) () LLJ 7: 0 CL_ tom, Z. >-- Co -C'o t () EXIST:NG FOOT OCYER TENANCY '0 -11..OCI, _:r- 1200 :.4 WET SEAL WESTFIELD SOUTHCENTER MALL SCALE 1132"=1' 2S,2V 0 w 0 f== LTJ c_) i L_J v (n 1215] 142°1 D EOL -S1 EX SYSTEM CALCULATIONS BATTERY SIZING CALCULATION WET SEAL WET SEAL FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL DATE 06/04/08 Panel: WET SEAL Wire Resistance 1.62 Date: June 4, 2008 CURRENT TOTAL Current Load: Standby: Alarm: S1 Current Load: Standby: Alarm: _ QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 SET -MC @15CD 64 128 Device Type Qty Amps Total Amps Total 98 Device Type Qty Amps Total Amps Total SET -MC @75CD HFP-11 350 0.0022 0.0022 0.0023 Total Device Load, Amps (I) 0.70 0 SET -MC @110CD 233 0 (Total Cct Load) AD2-P 0 2 0.0635 0.0635 0.064 0.128 Main System Board Voltage Drop ( E) 1 0.03 SET-HMC-C@177CD 0.03 0.030 0.030 HTR -R 3 0.009600 0.0096 0.021 0.063 0 SET -MC @15CD 2 EOL Voltage 19.96 0.064 0.128 445 HTRI-D 0.001600 0.0035 2 SET -MC @30CD 64 1 0.098 0.098 ICP -B6 Z-MC@30CD 98 0.005 SET -MC @75CD 0 2 233 0 0.175 0.350 DEVICES= 7 TOTAL mA= 704 12 191 19.96433664 704 SET -MC @110CD 0.233 Notification Appliance Circuit Detail SET HMC-C@115CD PROJECT: WESTFIELD SOUTHCENTER MALL 0.318 Panel: WET SEAL Wire Resistance 2.58 Date: June 4, 2008 CURRENT TOTAL= SET HMC-C@135CD CIRCUIT: SPEAKER CIRCUIT 0.318 0.0731 Amps 0.191 Amps SET HMC-C@185CD Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 0.445 5 70.7V 1/8 1.8 9 ZR -MC @15CD Total Wire Resistance (R j 2 0 0 0.064 0.128 Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours 0 ZR -MC @30CD 0.098 0.01 0 0 0 HCP 0 0 0 0.0015 Alarm Current Load: 0.191 Amps For 5 Minutes= 0.016 Amp -hours 0.03 Amps 0.734 Amps 0 0 EOL Voltage 20.39 0 0 0 (20.4 - E) 0 25% Derating= 2.213 Amp -hours Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours 0 0 DEVICES= 5 TOTAL mA= 9 14 191 20.39112996) Alarm Current Load: 0.734 Amps For 5 Minutes= 0.062 Amp -hours Total System Current Load: _ 2.213 Amp -hours 25% Derating= 0.977 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.977 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULATION z :5 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-651+5 RELEASE/REVISIONS REV. BY: z Notification Appliance Circuit Detail DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL DATE 06/04/08 Panel: WET SEAL Wire Resistance 1.62 Date: June 4, 2008 CURRENT TOTAL 704 CIRCUIT: S1 _ QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 SET -MC @15CD 64 128 Total Wire Resistance ( R) 0.62 1 SET -MC @30CD 98 98 (WL *2 ) * (R/ft) 2 SET -MC @75CD 175 350 Total Device Load, Amps (I) 0.70 0 SET -MC @110CD 233 0 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 Voltage Drop ( E) 0.44 0 SET-HMC-C@177CD 445 0 (E= I * R) 0 SET -HMC @135CD 318 0 EOL Voltage 19.96 0 SET -HMC @185CD 445 0 (20.4 - E) 2 Z-MC@15CD 64 128 0 Z-MC@30CD 98 0 0 SET-MC-CW@110CD 233 0 DEVICES= 7 TOTAL mA= 704 12 191 19.96433664 704 Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: WET SEAL Wire Resistance 2.58 Date: June 4, 2008 CURRENT TOTAL= 9 CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 5 70.7V 1/8 1.8 9 Total Wire Resistance (R j 0.99 0 0 0 0 0 0 Total Device Load, Amps (1) 0.01 0 0 0 (Total Cct Load) 0 0 0 Voltage Drop (E) 0.01 0 0 0 EOL Voltage 20.39 0 0 0 (20.4 - E) 0 0 0 0 0 0 DEVICES= 5 TOTAL mA= 9 14 191 20.39112996) z :5 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-651+5 RELEASE/REVISIONS REV. BY: z DESCRIPTION SHOP DRAWINGS DATE 06/04/08 co 0) J w (tp g< wl- W~0 U)2 W= Fg - =Q W Q 0> cc 0 N D i - CC w cc< W z W 0 C/)Z a ‘CALE: AS NOTED DRAWN BY: !.ANDERSON DESIGNED BY: R.VEZZANI DATE: 06/04/08 BACKROUND PLAN PROVIDED BY: \0B NUMBER: RISER DIAGRAM VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved SHEET FA -04 NE CE RO 2'X4'A.C.T. LING IN STOCK M ® 12'-0" 1— N W G . BD. CEILING 8'-0 A.F.F. PAINT NEW 2' CEILING CORRID NEW G FLUOR CORRID SURFA 0 X 4' A.C.T. IN EXIT R 0 12'-0" BD. CEILING A:F:FT PAINT - CENT LIGHTS 11R TO BE E MOUNTE S1 Sl UORESCENT LIGHTS OCKROOM TO BE RFACE MOUNTED 13'-8211 2T -G11' Mew .011 ved NEW FIT11NG ROOM 'X4'TEGULAR EILING ® 10'-0" TGC IS TO CUT THE GRIDS OUT AT LIGHTS TO I PROVIDE ACCESS TO CHANGE LAMPS —TRACK LIGHTING ON UNISTRUT SEE DETAIL 2/E102 BOTTOM OF NEW LIGHT COVE 0 12'-l" 11'-421" 2'-0" X 4'-0" WHITE GRID SUSPEND 3" BELOW SOFFIT 5/8" G' '. BD. SOFFIT ® 12'-7 - PAINT 2-11/2 B-012 TRACK LIGHTS IN SALES AREA SURFACE MOUNTED (TYP.) GENERAL NOTE=S I. 2. 3. FILE COPY 4. TGC IS TO CUT THE GRIDS OUT AT LIGHTS TO PROVIDE ACCESS TO CHANGE LAMPS 2'-0" X 4'-0" WHITE GRID SUSPEND 3" BELOW SOFFIT 5/8" GYP. BD. SOFFIT 012'-7" - PAINT BOTTOM OF NEW LIGHT COVE ® 12'-1" 5. 6. 1. 10. 11. 10. 11. 12. 13. 5/8" C J'. BD. SOFFIT 12'-1 - PAINT SIGNAGE. SEE DETAILS ON SHEET A401 .�1 L) FI TTI G ROO S II A DESIGN AND INSTALLATION SHALL CONFORM TO NFPA PAMPHLET 13 AND CITY OF TUKUJILA FIRE DEPT. REQUIREMENTS. ALL MATERIALS SHALL BE NEUJ AND U.L. APPROVED. PIPE: ALL PIPE 2" AND LARGER TO BE SCHEDULE 40 BLACK STEEL. ALL PIPE 2i" AND LARGER TO BE SCHEDULE 10 BLACK STEEL. FITTINGS: ALL FITTING5 (SCREWED AND GROOVED) AND GROOVED COUPLINGS TO BE STAR BRAND DUCTILE IRON. PAINTING OF PIPE AND PROTECTION OF SPRINKLER HEADS FROM PAINT IS BY OTHERS. ALL ELECTRICAL WIRING AND CONDIUT IS BY OTHERS. ALL WELDING TO CONFORM WITH AWS D109 AND WILL BE PERFORMED IN COSCO'S SHOP. It IS THE BUILDING OWNERS RESPONSIBILITY TO KEEP ALL AREAS WITH WET SPRINKLER SYSTEMS HEATED TO A MINIMUM 40 DEGREES FAHRENHEIT TO PREVENT FREEZING OP PIPES. OWNER IS RESPONSIBLE TO ASSURE THAT STRUCTURE AS IT IS SHOWN ON THE CONTRACT DRAWINGS CAN ADEQUATELY SUPPORT ALL FIRE SPRINKLER PIPING LOADS. NO AUXILLIARY DEVICES OR ATTACHMENTS SHALL BE PROVIDED BY COSCO TO SUPPLIMENT THE STRUCTURE TO ACCOMODATE FIRE SPRINKLER PIPING LOADS. COSCO ASSUMES NO RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, FOR THE CONDITION, PERFORMANCE OR CURRENT CODE COMPLIANCE OF THE EXISTING SYSTEM TO BE MODIPIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY COSCO FIRE PROTECTION. UNDERGROUND CONTRACTOR SHALL FLUSH THE UNDERGROUND AND PROVIDE COSCO WITH THE PROPER CERTIFICATE OF DOING SO BEFORE COSCO WILL CONNECT TO THE UNDERGROUND PIPE. SPRINKLER HEADS ARE DESIGNED TO BE IN CENTERLINE OF CEILING TILE (+1- 1"). ALL DIMENSIONS ARE TO CENTERLINE OF PIPE. DOTTED LINES DENOTE EXISTING PIPE. ( -DENOTES EXISTING SPRINKLER HEAD. SYMBOLS/ABREVIATIONS: FUKWILA FIRE DEPARTMENT Please call: 575-4407 and give this job [X' -X"] - DENOTES CENTER LINE OF SPRINKLER PIPE AP °• (-)23 and exact address for shut" >own or restoration approval. X' -X" - DENOTES CEILING HEIGHT. AFF - CENTERLINE OF PIPE. ABOVE FINISHED FLOOR. BDK - CENTERLINE OF PIPE BELOW BOTTOM. •� DECK F - FLEXIBLE GROOVED COUPLING. MT - MECHANICAL TEE AT - HYDRAULIC REFERENCE NODE. ;-) iltzb,r- TGC IS TO CUT THE GRIDS OUT AT LIGHTS TO PROVIDE ACCESS TO CHANGE LAMPS 5/8" GYP. BD. SOFFIT - ®-12'-7 ---PAINS - — { i TRACK LIGHTS IN SALES AREA SURFACE MOUN D (TYP.) /2 1311- .. 1 "A1 TOLCO FIG. 65 C -CLAMP PIPE ROD SIZE DIA 1" 3/8" 11/4" 3/8" 1 I/2" 3/8" 2" 3/8" 2 1/2" 3/8" 3" 3/8" 4" 3/8" 6" 1/2" 8" 1/2" RETAINER STRAP, NUT THREADED ROD HILTI FIG LH OR TOLCO FIG 200 HANGER RING UL 04/2007 COSCO STANDARD HANGER 2 C 1 1131202811 1 FLUORESCENT LIGHT TO BE SURFACE MOUNTED SALcS AREA CEILING 5/8 GYP. BD. ® 13'-0" A.F.F. - PAINT FIRE PROTECTIONPIPING PLAN TOLCO FIG. 78 THREADED STEEL DECK PLATE (2)-I/4" x I" TEK SHEET METAL SCREW PIPE ROD SIZE DIA I" 3/8" 1 I/4" 3/8" 1 1/2" 3/8" 2" 3/8" THREADED ROD HILTI FIG LH OR TOLCO FIG 200 HANGER RING UL 04/2007 COSCO STANDARD HANGER 8 METAL TOLCO FIG. 25 SURGE RESTRAINER TYPE 1 — FOR 1" AND 1-1/4" PIPE AND HANGER TYPE 2 — FOR 1-1/2" AND 2" PIPE AND HANGER SYSTEM PRESSURE EXCEEDS 100 PSI. USE FIG. 25 WITH TOLCO BAND HANGERS FIG. 200 AND 2NFPA TO RESTRAIN THE UPWARD MOVEMENT OF PIPE AS IT OCCURS DURING SPRINKLER HEAD ACTIVATION OR SEISMIC ACTIVITY FIGURE 25 SURGE RESTRAINER. IA FOR STEEL OR CPVC PLASTIC PIPE BRANCHLINE '1- HYDRAULIC REMOTE AREA — A (ORDINARY HAZARD GROUP 2) THIS SYSTEM DESIGNED TO DISCHARGE 0.20 G.P.M. OVER THE HYDRAULIC MOST REMOTE 1500 SQ. FT. WHEN SUPPLIED WITH WATER AT THE CITY CONN. AT A RATE OF 650 G.P.M. AT 110.5 P.S.I. INSIDE HOSE ALLOWANCE: NONE OUTSIDE HOSE ALLOWANCE: 250 G.P.M. 1" X DROP (SEE PLAN) 1" X ARMOVER / (SEE PLAN) SUSPENDED CEILING 1" X 1/2" RC IN TILE CEILINGS -"1" ADJUSTABLE DROP IN GYP BOARD CEILINGS TYPICAL DROP TO SPRINKLER HEAD DESCRIPTION atl •`i'titlmlR4�?'MP4t1W�.Y+�iiaVMwM1'�FuwWM1dMM SPRINKLER HEAD LEGEND : S/N ORIFICE NPT K -FACT. TEMP. 1 1/2" BRANCHLINE Li—IL "FLEXHEAD" FLEXABLE DROP CORRUGATED STAINLESS STEEL BRAIDED HOSE ADJUSTABLE HUB MOUNTING BRACKET \ NE ■ �■ • J w 2' 0" X 4'-O" WHITE GRID SUSPEND 3" BELOW SOFFIT BOTTOM OF NEW LIGHT COVE 12'-l" WHERE LENGTH OF ALL THREAD ROD ARGCO 03B OFFSET EXCEEDS 1'-10" ADD SECOND RESTRAINT F , �r. linage plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. . Acceptance is wubiect to errors and omiseions which do not authorize violations of adopted standards and °romances. The responsibility for the adequacy of design rests tot=ally with the designer. Additions,dal,::tion or ro,visions t) theta { ralr.'ings atter P this date will void t 1 ; t carx;c:pfanc,r.. :;!rid will rc gl.l,re ;1 resubmittal o' .: vised c1 '.&-irigs for sub; equerlt approval. Final accr..pt.;nr..E_ is 3ub;oct to field test and inspection by The Tukwila FTs i, r.:n.,;.ition Bureau. G - -3-U Date: _ l,y: 0 0 Without Comment, t As Noted in Red Per The Attached Utter Lqe 3/8 X 3-1/2 LAG BOLI FOR WOOD - _3/8" KWIK BOLT POR CONCRETE 1/4 X I TEK FOR BARJOIST OR STEEL E3EAM 3/8"x1-10 ALL THREAD ROD MAX PER SINGLE RESTRAINT 1.N ROP PN TO PIPE OR USE TOLCO FIG 25 HANGER RING (UP TO 2" PIPE) LINE RESTRAINT DETAIL SYMBOL =i CEILING NOTE: 1) SPACE UJITN IN 6" OF A HANGER EVERY 42'-0". 2) BRACING PER NFPA-13(200"1 ed.) SECTIONS 93.5.63.8, TABLE 9.3.5.82(c) AND 93.6 -RESTA INT OF BRAN( -1 LINES TYPICAL DROP TO SPRINKLER HEAD IN AC TILE CEILINGS QUAN. RELIABLE MODEL G4A CONCEALED PENDENT RELIABLE MODEL G4A CONCEALED PENDENT RELIABLE Fl FR RECESSED PENDENT R5415 1/2' 1/2' 5.6 BRASS WHITE 165 31 0 R5415 1/2' 1/2' 5.6 BRASS BLACK 165 6 R3615 1/2' 1/2' 5.62 WHITE WHITE 155 10 1 i APPROVALS BY: CITY OF TUKWILLA TOTAL SPRINKLERS THIS SHEET 47 . ®0 0®. • 00 ^ 00• • 00 00®• . 00 0®•• C SC Fire Protection FIRE PROTECTION AND LIFE SAFETY SPECIALISTS www.coscofire.com WASHINGTON OFFICE 15000 Woodinville -Redmond Rd NE Woodinville, Washington 98072 call (425) 686-8300 • fax (425) 827-4784 SAN DIEGO • LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE License No: COSCOFP 11 ONM SPACE 2446 LEVEL -2 ttOTICII[ M kik 1In ‘Dante! McLuen 391-07.6676 11.W111.11.., KEY PLAN PROJECT:WET SEAL 2446 SOUTHCENTER MALL TUKWILLA, WASHINGTON CONTRACT W1rH: JEM CONSTRUCTION 29506 - 8th AVE. S. ROY, WASHINGTON 98580 SPACE #2446 DRAWING TIRE FIRE PROTECTION PLAN 2008 Tukwila Fire; DATE : 5/2008 SCALE : 1 /4"=1'-0" DRAWN BY : D. CLARK 4B,tI(05 KS 7953 SHEET NO. FP -1 of 2 y411:n•001YyNV4 • ;;;y40 Vsk;4'+ yiyal.o"•7fPxiw.44Nt4 Y+ ..�+1N4PUXprpantlWr t :r .-041) �w MEM TAR 10 IE I17Mf® HYDFIAILIO AIM= AMA - A ((pIDNAfff NAZAFID 0110UP Y) THIS SYSTEM DESIGNED TD DISaHRCE 0.20 OVER THE NrDRU$JC MOST REMOTE 1500 S0. FT. WHEN SUPPLIED WON WATER AT THE CITY CONN. ATARATE OF6500.P.U.AT110.5PS.L ONSIDE HOSE ALLOWANCE NONE OUTSIDE HOSE ALLOWANCE 250 C.P.M. gun T vAL1k: 0. C1.EiK WLV1= 6' F6Em MA W TOLri r -r Er =CI= PIT 4TCYR Vaal: Mir= Cid: NY Y Iv =nut rai I}b" GROOVED VA' GIWANR, STAIR #2 STAIR #2 LEVEL -1 !3/32'•1'-0') YY mg • REVISIONS NO. DESCRIPTION DATE SPRINKLER HEAD LEGEND : RELIABLE MODEL G4A CONCEALED PENDENT SYMBOL S/N ORIFICE NPT K -FACT. R5415 5.6 BRASS WHITE TEMP. QUAN. 165 RELIABLE MODEL G4A CONCEALED PENDENT R5415 1/2' 1/2' 5.6 BRASS BLACK 165 6 " RELIABLE F1 FR RECESSED PENDENT R3615 1/2' 1/2' 5.62 WHITE WHITE 155 10 APPROVALS BY: CITY OF TUKWILLA TOTAL SPRINKLERS THIS SHEET 47 .o0 00 . • o® 0 0 o• • ®o Fire Protection FIRE PROTECTION AND LIFE SAFETY SPECIALISTS WASHINGTON OFFICE 15000 Woodinville -Redmond Rd NE Woodinville, Washington 98072 call (425) 686-8300 • fax (425) 827-4784 SAN DIEGO • LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE sc www.coscofire.com License No: COSCOFP 11 ONM PROJECT: WET SEAL 2446 SOUTHCENTER MALL TUKWILLA, WASHINGTON SPACE #2446 CONTRACT WITH: JEM CONSTRUCTION 29506 - 8th AVE. S. ROY, WASHINGTON 98580 DRAWING TITLE SITE PLAN DATE : 5/2008 SCALE : 1/t=11-0" DRAWN BY : D. CLARK 'DB 05 KS 7953 SHEET NO. FP -2 of 2 O