PP - 2477 SOUTHCENTER MALL - JOURNEYS - PERMITS AND PLANS
2477 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-272 08-S-279 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Journeys 2477 Southcenter Mall Permit No.: 08-S-279 Date: June 5, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • These conditions apply to any sprinkler piping exposed as necessary to accomplish the permitted scope of work. All references are NFPA 13, 2007 Edition. Hydraulic Overview Job Number: N/A Report Description: Ordinary Group II Job Job Number Desgn Engineer N/A CHRIS ISAAC • Job Name Phone FAX JOURNEY'S 425.881.0100 425.881.3030 Address 1 State CetSficalion&Ucense Number 2477 Southcenter Pkwy WESTESF136QF Address 2 AHJ City of Tukwila City State Zip Code Job Site Tukwila WA 98188 Expansion System Dente Area of Application 0.200gpm/ft2 1047.69ft2 (Actual 1047.69ft2) Most Demanding Sprinkler Data Hose Streams 5.6 K -Factor 24.00 at 18.367 250.00 Coverage Per Sprinkler Number Of Sprinklers Calculated 120.00ft2 11 System Pressure Demand System Flow Demand 77.526 315.38 Total Demand Pressure Result 565.38 @ 77.526 +61.970 (44.4%) Supplies Check Point Gauges Node Flow(aDm) Hose Flow(opm) Static(psil Residual(psi) Identifier Pressure(psi) K-Factor(K) Fiow(acm) 40 I i /II P1�: WINIA'takw fl. IIII • 1 10900.00 250.00 140.000 20.000 JOURNEY'S FP-1.cad Supply at Node 1 (10900.00, 250.00, 140.000, 20.000) !'----- 150 11 Static Pressure i 140.000 135 120 105 _ 90 Q d 65.38 with hose streams in 75 in W c15.38@77.5 6 1^ I n`. 60 45 System demand curve 30 10900.00 @ 20.000; 15 11uNllll lllllllll 11111111111111111111111111111 1111111111111111 111 111111 0 193000 5500 6600 7700 8800 9900 11000 Water flow, gpm y(y ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 05/29/2008 2:07:11 PM Page 1 Hydraulic Summary 1 Job Number: N/A Report Description: Ordinary Group II Job Job Number N/A Job Name JOURNEY'S Address 1 2477 Southcenter Pkwy Address 2 City Stale Zip Code Tukwila WA 98188 Design Engineer CHRIS ISAAC State Certification/License Number WESTESF136QF AHJ City of Tukwila Job Site Expansion Drawing Name JOURNEYS FP-1.cad System 1 Remote Area(s) Most Demanding Spnnkler Data 5.6 K -Factor 24.00 at 18.367 Hose Allowance At Source 250.00 Additional Hose Supplies Node Flow(gpm) Occupancy Ordinary Group II Density 0.200gpm/ft2 Number Of Spnnklers Calculated 11 Area of Application 1047.69ft2 (Actual 1047.69ft2) Coverage Per Sprinkler 120.00ft2 Tote! Hose Streams 250.00 System flow Demand Total Water Required (Including Hose Allowance) 315.38 565.38 Maximum Pressure Unbalance In Loops 0.000 Maximum Velocity Above Ground 38.32 between nodes 49 and 48 Maximum Velocity Under Ground 1.19 between nodes 1 and 348 Volume capacity of Wet Pipes Volume capacity of Dry Pipes 3202.22ga1 6.30ga1 Supplies Hose Flow Static Residual @ Flow Node (gpm) (psi) (psi) (gpm) Available @ Total Demand (psi) (gpm) Required Safety Margin (psi) (psi) 1 250.00 140.000 20.000 10900.00 139.497 565.38 77.526 61.970 Contractor Contractor Number N/A Contractor Name Western States Fire Protection (Redmond) Address 1 7102 180th Ave NE, Suite A-105 Address 2 City State Zip Code Redmond WA 98052 Contact Name Chris J Isaac Phone (425)881-0100 FAX (425)881-3030 E-mail chris.isaac@wsfp.us Web -See Contact Tab Designer Extension l� © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 05/29/2008 2:07:12PM Page 2 Summary Of Outflowing Devices Job Number: N/A Report Description: Ordinary Group 11 Device Actual Flow (gpm) Minimum Flow K -Factor Pressure (gpm) (K) (psi) Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler c> Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler 104 103 109 102 105 101 107 106 110 111 108 c> Most Demanding Sprinkler Data 25.66 25.02 32.07 24.89 26.30 24.00 26.82 26.76 36.09 36.14 31.62 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 20.999 19.954 32.803 19.758 22.050 18.367 22.945 22.833 41.534 41.660 31.884 CM, © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 05/29/2008 2:07:12PM Page 3 Node Analysis 1 Job Number: N/A Report Description: Ordinary Group II Node Elevation(Foot) 26 12.-0 20 13'-0 21 12'-0 31 12'-0 38 13'-0 43 13'-0 46 13'-0 52 13'-0 44 13'-0 59 13'-0 48 13'-0 49 13'-0 50 16-0 68 16'-0 66 16-0 67 16'-0 151 16'-0 153 16'-0 184 16'-0 256 -16'-1 306 -16'-1 348 104 11'-614 103 11'-6%4 109 11'-6% 102 11'-61/4 105 12'-0Y4 101 11'-0Y4 107 12'-014 106 11'-0%4 110 12'-01. 111 12'-0%4 108 1 -22'-0 Fittings E(2'-0) E(2'-0) E(2'-0) PO(5'-0) PO(5'-0) PO(5'-0) PO(5'-0) PO(5'-0) PO(8'-0) PO(8'-0) PO(8'-0) LtE(2-0) LtE(3'-0) E(2'-0) E(2'-0) P0(6-0) 3P0(26-4), 3C(26'-4) pog-o) PO(6-0) 2P0(43'-1) BFP(5.000) Spr(-20.999) Spr(-19.954) Spr(-32.803) Spr(-19.758) Spr(-22.050) Spr(-18.367) Spr(-22.945) Spr(-22.833) Spr(-41.534) Spr(-41.660) Spr(-31.884) S Pressure(psi) Discharge(gpm) 26.012 27.897 41.235 26.047 28.050 26.809 29.186 28.502 32.995 41.117 42.257 49.793 51.409 50.472 50.243 39.276 54.362 52.777 52.554 69.350 69.873 73.270 20.999 19.954 32.803 19.758 22.050 18.367 22.945 22.833 41.534 41.660 31.884 77.526 25.66 25.02 32.07 24.89 26.30 24.00 26.82 26.76 36.09 36.14 31.62 315.38 (N, ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 05/29/2008 2:07:13PM Page 4 Hydraulic Analysis Pipe Type Downstream Upstream Job Number: N/A Report Description: Ordinary Group II Diameter Flow Velocity HWC Friction Loss Length Pressure Elevation Discharge K -Factor Pt Pn Fittings Eq. Length Summary Total Length Route 1 DR 1.0490 0=24.00 8.91 C=120 0.182334 101 11'-0Y. q=24.00 K=5.6 18.367 Spr(-18.367) 43 13'-0 26.809 E(2'-0), PO(5'-0) 44'-0 Pf 9.299 7'-0 Pe -0.857 51'-0 Pv BL 1.6100 0=73.91 11.65 C=120 43 13'-0 26.809 52 13'-0 28.502 0.181336 9' 4 Pf 1.693 Pe -0.000 9'-4 Pv BL 1.6100 0=100.67 15.86 C=120 52 13'-0 28.502 44 13'-0 32.995 0.321180 P0(8'-0) 5'-11% Pf 4.492 8'-0 Pe -0.000 13'-11 % Pv BL 1.6100 0=179.45 28.28 C=120 44 13'-0 32.995 59 13'-0 41.117 0.935840 8'-81h Pf 8.122 Pe -0.000 8'-8% Pv BL 1.6100 Q=211.07 33.26 C=120 59 13'-0 41.117 48 13'-0 42.257 1.263571 0'-10% Pf 1.141 Pe -0.000 0'-10'/. Pv BL 1.6100 Q=243.14 38.32 C=120 48 13'-0 42.257 49 13'-0 49.793 1.641554 LtE(2'-0) 2'-7 Pf 7.536 2'-0 Pe -0.000 4'-7 Pv BL 2.0670 0=243.14 23.25 C=120 49 13'-0 49.793 50 16'-0 51.409 0.486171 LtE(3'-0) 3'-0 Pf 2.917 3'-0 Pe -1.301 6'-0 Pv CM 4.2600 Q=243.14 5.47 C=120 50 16-0 51.409 184 16'-0 52.554 0.014364 PO(26'-4) 53'-5 Pf 1.146 26'-4 Pe -0.001 79'-9 Pv CM 4.2600 0=279.29 6.29 C=120 184 16'-0 52.554 153 16'-0 52.777 0.018562 12'-0 Pf 0.223 Pe 12'-0 Pv CM 4.2600 0=315.38 7.10 C=120 0.023242 15-6Y2 Pf 1.585 153 16'-0 52.777 52'-8 Pe 151 16'-0 54.362 P0(26-4), C(26'-4) 68'-2'/ Pv CM 6.3570 0=315.38 3.19 C=120 151 16'-0 54.362 256 -16-1 69.350 0.003309 10fE(12'-7), BV(12'-7), fE(10'-0), CV(40'-2%), GV(3'-9'h) 133'-91/2 Pf 1.079 192'-3% Pe 13.909 326.-1% Pv BL 8.3290 Q=315.38 1.86 C=120 0.000888 13'-4 Pf 0.523 256 -16'-1 69.350 P0(43'-1) 576-1Y2 Pe -0.000 306 -16'-1 69.873 12P0(43'-1), fE(16'-0) 589'-5Y2 Pv MS 10.0200 Q=315.38 1.28 C=120 306 -16-1 69.873 348 -12'-3% 73.270 0.000361 3LtE(16'-0), BV(19'-0), BFP(-5.000) 20'-2 Pf 5.031 67'-0 Pe -1.635 87'-2 Pv UG 10.4000 Q=315.38 1.19 C=140 0.000226 112'-10% Pf 0.057 348 -12'-3% 73.270 137'-1% Pe 4.200 1 -22'-0 77.526 4LtE(25'-6), 2EE(17'-6Y2), S 250'-0 Pv Qi Route 2 DR 1.0490 0=24.89 9.24 C=120 0.195069 26'-3V2 Pf 6.496 102 11'-6Y. q=24.89 K=5.6 19.758 Spr(-19.758) 7'-0 Pe -0.207 31 12'-0 26.047 E(2'-0), PO(5'-0) 33'-3Y2 Pv BL 1.6100 0=49.91 7.87 C=120 31 12'-0 26.047 43 13'-0 26.809 0.087703 2LtE(2'-0) 9'-7'/2 Pf 1.196 4'-0 Pe -0.434 13'-7Y2 Pv Route 3 DR 1.0490 0=25.02 9.29 C=120 0.196860 27-93h Pf 6.265 103 11'-6Y. q=25.02 K=5.6 19.954 Spr(-19.954) 4'-0 Pe -0.207 26 12'-0 26.012 2E(2'-0) 31'-9'/1 Pv BL 1.6100 Q=25.02 3.94 C=120 26 12'-0 26.012 31 12'-0 26.047 0.024439 1'-5'/. Pf 0.035 Pe 1'-5Y. Pv ao Route 4 DR 1.0490 0=25.66 9.53 C=120 0.206375 28'-6% Pf 7.539 104 11'-6% q=25.66 K=5.6 20.999 Spr(-20.999) 8'-0 Pe -0.640 20 13'-0 27.897 4E(2'-0) 36'-61h Pv BL 1.6100 Q=25.66 4.04 C=120 20 13'-0 27.897 38 13'-0 28.050 0.025621 5'-11% Pf 0.152 Pe 5.-11% Pv BL 1.6100 0=51.96 8.19 C=120 38 13'-0 28.050 46 13'-0 29.186 0.094486 12'-0Y. Pf 1.136 Pe 12'-0'h Pv BL 1.6100 0=78.78 12.42 C=120 46 13'-0 29.186 44 13'-0 32.995 0.204082 LtE(2'-0) 16'-8 Pf 3.809 2'-0 Pe -0.000 18'-8 Pv a Route 5 (M ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 05/29/2008 2:07:13PM Page 5 Hydraulic Analysis 1 Job Number: N/A Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity Downstream Elevation Discharge K -Factor Upstream HWC Pt Friction Loss Pn Fittings Length Pressure Eq. Length Summary Total Length DR 1.0490 Q=26.30 9.76 C=120 0.215911 22'-9 Pf 6.423 105 12'-0Y+ q=26.30 K=5.6 22.050 Spr(-22.050) 7'-0 Pe -0.423 38 13'-0 28.050 E(2'-0), PO(5'-0) 29'-9 Pv .+ Route 6 DR 1.0490 Q=26.76 9.93 C=120 0.222998 22'-3Y. Pf 6.526 106 11'-0Y, q=26.76 K=5.6 22.833 Spr(-22.833) 7'-0 Pe -0.857 52 13'-0 28.502 E(2'-0), PO(5'-0) 29'-3% Pv a Route 7 DR 1.0490 Q=26.82 9.96 C=120 0.224006 22'-9 Pf 6.664 107 12'-0%, q=26.82 K=5.6 22.945 Spr(-22.945) 7'-0 Pe -0.423 46 13'-0 29.186 E(2'-0), PO(5'-0) 29'-9 Pv a Route 8 DR 1.0490 Q=31.62 11.74 C=120 0.303689 22'-11% Pf 9.107 108 12'-0% q=31.62 K=5.6 31.884 Spr(-31.884) 7'-0 Pe -1.715 67 16-0 39.276 E(2'-0), PO(5'-0) 29.-11% Pv BL 1.6100 Q=31.62 4.98 C=120 0.037702 4'-3' Pf 0.540 67 16'-0 39.276 10'-0 Pe 1.301 59 13'-0 41.117 LtE(2'-0), PO(8'-0) 14'-3% Pv a Route 9 DR 1.0490 Q=32.07 11.91 C=120 0.311773 23'-8Y2 Pf 8.639 109 11'-6% q=32.07 K=5.6 32.803 Spr(-32.803) 4'-0 Pe -0.207 21 12'-0 41.235 2E(2'-0) 27-812 Pv BL 1.6100 Q=32.07 5.05 C=120 0.038706 25'-7Y2 Pf 1.456 21 12'-0 41.235 12'-0 Pe -0.434 48 13'-0 42.257 2LtE(2'-0), PO(8'-0) 37'-7% Pv r+ Route 10 DR 1.0490 Q=36.09 13.40 C=120 0.387837 23'-6 Pf 10.663 110 12'-0% q=36.09 K=5.6 41.534 Spr(-41.534) 4'-0 Pe -1.725 68 16-0 50.472 2E(2'-0) 27'-6 Pv BL 1.6100 Q=36.09 5.69 C=120 0.048149 39'-10Y4 Pf 2.304 68 16'-0 50.472 8'-0 Pe -0.000 153 16'-0 52.777 PO(8'-0) 47'-10% Pv a Route 11 DR 1.0490 Q=36.14 13.42 C=120 0.388922 22'-6 Pf 10.309 111 12'-0% q=36.14 K=5.6 41.660 Spr(-41.660) 4'-0 Pe -1.725 66 16-0 50.243 2E(2'-0) 26'-6 Pv BL 1.6100 Q=36.14 5.70 C=120 0.048283 39'-10Y4 Pf 2.311 66 16'-0 50.243 8'-0 Pe -0.000 184 16'-0 52.554 PO(8'-0) 47'-10Y4 Pv Equivalent Pipe Lengths of Valves and Fittings (C=120 only) ` C Value Multiplier II Actual Inside Diameter 4.87 ) = Factor Value Of C 100 130 140 150 ( Schedule 40 Steel Pipe Inside Diameter Multiplying Factor 0.713 1.16 1.33 1.51 ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 05/29/2008 2:07:13PM Page 6 I Hydraulic Analysis Pipe Type Downstream Upstream Diameter Elevation Flow Discharge Job Number: N/A Report Description: Ordinary Group II Velocity HWC K -Factor Pt Friction Loss Pn Fittings Length Pressure Eq. Length Summary Total Length Pipe Type Legend Units Legend Fittings Legend AO BL CM DN DR DY FM FR MS OR RN SP ST UG Arm -Over Diameter Branch Line Elevation Cross Main Flow Drain Discharge Drop Velocity Dynamic Pressure Feed Main Length Feed Riser Friction Loss Miscellaneous HWC Outrigger Pt Riser Nipple Pn Sprig pf Stand Pipe Pe Underground Pv Inch Foot gpm gpm fps psi Foot psi/Foot Hazen -Williams Constant Total pressure at a point in a pipe Normal pressure at a point in a pipe Pressure loss due to friction between points Pressure due to elevation difference between indicated points Velocity pressure at a point in a pipe ALV Alarm Valve AngV Angle Valve b Bushing BaIV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Turn 90° cplg Coupling Cr Cross Run CV Check Valve DeIV Deluge Valve DPV Dry Pipe Valve E 90° Elbow EE 45° Elbow Eel 11%° Elbow Ee2 22%° Elbow f Flow Device FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow flg Flange FN Floating Node fT FireLock(TM) Tee g Gauge GIoV Globe Valve GV Gate Valve Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PrV Pressure Relief Valve PRV Pressure Reducing Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 900 Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap (M © M.E.P.CAD, Inc. AutoSPRINK®VR5 v5.1.32 05/29/2008 2:07:13PM Page 7 ii Hydraulic Graph Job Number: N/A Re ort Description: Ordinary Group II • Supply at Node 1 150 -Static Pressure 140.000 135 120 105 90 a E 75 315.38 w fn - rp _ d - .565.38 with hose @ 77.526 streams 60 45 :System demand curve 30 - 10900.00 @ 20.000, 15 W 111111111111111111 111111111 111111111 11111 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 i10022°° 3300 4400 5500 6600 7700 Water flow, gpm 8800 9900 11000 Hydraulic Graph Supply at Node 1 Static Pressure 140.000 Residual Pressure 10900.00 @ 20.000 Available PressureTime of Test 139.497 @ 565.38 System Demand 315.38 @ 77.526 System Demand (Including Hose Allowance) 565.38 @ 77.526 (M ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 05/29/2008 2:07: age Flow Diagram (Top View) 1 Job Number: N/A Report Description: Ordinary Group 11 ©M.E.P.CAD, Inc. AutoSPRINK®VR5 v5.1.32 05/29/2008 2:07:15PM Page 9 S EET \U V REQ SHEET TITLE SHEET INDEX JOU RE ALARM YTEM TUKWILA, WASHINGTON EY FA -01 SYSTE V INFOMATIO\ FA -02 TYPICAL DETAILS - WI�I \G A\3 VOU\TI\G FA -03 FI �E ALARM SYSTEM FLOO PLA\ FA -04 SYSTEM CALCULATIO \S (cE\EAL), RISER, SITE PLA\ WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END GENERAL NOTES FOR. SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED: NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF ,NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TQ FIRST DEVICE 'ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 2 1 EX SYMBOL DESCRIPTION SYMBOLS LEGEND MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD B a LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING DUCT SMOKE AD DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP IN/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 4S DEEP BOX W/ 1-1/2" EXT. CEILING 80" A.F.F. TO BOTTOM FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -:-CW SIEMENS 4S BOX W/ 1G RING CEILING L YC FIRE ALARM STROBE (WALL MOUNT) ZR -MC W SIEMENS 19 90X W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX W/ 1-1 /2" EXT. CEILING B WP MR FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) MULTI -VOLTAGE CONTROL RELAY SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -S17 -WP SIEMENS MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD 0 MAGNETIC DOOR HOLDER F.B.O. M. FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. CCg qTE VERT IN F LD JUNCTI❑N BOX F.B.O. F.B.❑. N/A VERT IN F LD A,F,F, WIRE DESIGNATION SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D H P S A V I X UD UI M B DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 •FPL/FPLR RED (JACKET) DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) ANNUNCIATOR TWISTED PAIR W/ SHIELD 4416 FPL/FPLR RED (JACKET) SPEAKER CIRCUIT - FEED TWISTED PAIR 4414 FPL/FPLR RED (JACKET) REMOTE INDICATION LIGHT TWD #18 FPL/FPLR RED (JACKET) LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UNDERGROUND INITIATI❑N TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) DOOR HOLDER POWER TWO *16 FPL/FPLR RED (JACKET) BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) F.B.O. CONDUIT FILL CHART N/A NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL • 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END GENERAL NOTES FOR. SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED: NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF ,NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TQ FIRST DEVICE 'ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 2 1 EX SYMBOL DESCRIPTION SYMBOLS LEGEND MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD B a LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING DUCT SMOKE AD DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP IN/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 4S DEEP BOX W/ 1-1/2" EXT. CEILING 80" A.F.F. TO BOTTOM FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -:-CW SIEMENS 4S BOX W/ 1G RING CEILING L YC FIRE ALARM STROBE (WALL MOUNT) ZR -MC W SIEMENS 19 90X W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX W/ 1-1 /2" EXT. CEILING B WP MR FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) MULTI -VOLTAGE CONTROL RELAY SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -S17 -WP SIEMENS MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD 0 MAGNETIC DOOR HOLDER F.B.O. M. FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. CCg qTE VERT IN F LD JUNCTI❑N BOX F.B.O. F.B.❑. N/A VERT IN F LD A,F,F, ABOVE FINISHED FLOOR N/A �..v �AsNoted IrO N/A Ad N/A ❑ Per The Attached Letter F.B.O. FURNISHED BY OTHERS N/A i riUtii plans have been revli d by The Tukwila Fir@/A Prevention Bureau for conformance with current city N/A NOT APPLICABLE N/A standards. Acceptance Is suhlect to errors and orh6 ons which do not aut 1 rile violations of adopt6Id'A stanaaras and orainances. The responsibility for the U,❑.N. UNLESS OTHERWISE NOTED N/A adequacy of aesign rests totally with the designer. A�lititms, deletions or revislk46 to these drawings aftWrA this date will void this acceptance and will require a WP WEATHERPROOF DEVICE N/A resubmittal of revised drawings for subsequent appy v N/A N/A R1�A Final acceptance is subject to field test and inspection by RED AS BUILT ADD OR CHANGE N/A The Tukwila Fire Prevention Bureau. N/A N/?�7 N/A Date: ®gi By: _ __, AS BUILT N/A REMOVE BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A tUKWIIA FIRE DEPARTM1tA Please call: 575-440Z and give this job No. J exact address for shut• ' n or restoration approval, RECEIVED JIJN - 3 2008A0 co&201q RELEASE/REVISIONS REV. BY: I NVI DESCRIPTION SHOP DRAWINGS DATE 6/03/08 k ««< T <0) 1 w CEO W(DZZ z 2 w1 D 1--ic Q crop FL ~� N F - Z 0 F cc 0 z SCALE: 1 /8"=1 DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/03/08 BACKROUND PLAN PROVIDED BY: 101i3 NUMBER:54521 SHEET Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved FA -41 1 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE DUCT DETECTOR L❑CATI❑N FROM XLS CONTROL PANEL OR PREVI❑US ADDRESSABLE DEVIC END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH GROUND 0 0 �t- 10 0 0 HTRI—R OSTATUS LED 00 N.O. a COM to m N NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE PREVI❑US ADDRESSABLE DEVICE (BACKGOUND MUSIC SHUTDOWN) TO NEXT ADDRESSABLE DEVICE L NOTE 1: VOLTAGE MAX, - CURRENT MAX. - CONT. RES, MAX. - MAX, CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX, LINE SIZE - MIN, LINE SIZE- OUTLET SAMPLING TUBE INLET SAMPLING TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE MUSIC —1.) -AC POWER SOURCE COMBINE ALL SHIELDS AND IS❑LATE FROM GROUNDING 0 TO NEXT ADDRESSABLE DEVICE f(+) STOP IF LAST DEVICE (-) FROM XLS CONTROL PANEL OR .[(+) PREVI❑US ADDRESSABLE DEVICE ()- RELAY CONTACTS (4.OA @ 125VAC) (4.OA @ 3OVDC) 27 VDC 3.5 nA DURING POLLING 10 OHMS 200 FT, (18 AWG) 0,02uF 0,04uF 14 AWG 18 AWG NOTE 2; ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST 25 SEC. TO GUARANTEE DETECTION, 0 1001 TB1 S. 0 0 0 0 123456 HC TB2 D 00 65 43 +- 21 0 END OF LINE 1 0 DEVICE0 (3.6K 1/4W) .'� i 0 SUPERVISED___/ SWITCH GROUND NOTE: ; 1 ; ; Pr) 0 0 HTRI—D OSTATUS LED m NOT USED END OF LINE DEVICE 3.6K 1/4W) 0 FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE C (FIRE SUPPRESSION SYSTEM INTERFACE) 0 0 GND N AC O 0 0 T rT Y PAD -3 0 00 0 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 0 uuuu 0 0 0 0 0 0 0 24K TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE NAC -4 NAC -3 2 NAC -2 NAC -1 \ UPERVISED SWITCH 2 FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 1 '4,-::1--'\ NOT USED REMOTE + ill DEVICE LOOP NOT USED REMOTE ..I. ( \ DEVICE LOOP %1-' 0 0 0 {FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY C'S' CABLE) FROM FACP (V❑ICE CIRCUIT) ('V' CABLE) 470 OHMS �IV EOL N T M-1 O 0 TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE NONE rTh () S (-) STROBE SPEAKER + v (STR❑BE) ) EARTH GROUND 0 -->(+)TO NEXT DEVICE OR } >(-) STOP IF LAST DEVICE (+) (-) STROBE SPEAKER ("-N (-) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY 4S DEEP BOX W/ 1-1 /2" EXTENSION RING (SPEAKER SIHOBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE TO NEXT DEVICE ❑R END OF LINE TO NEXT DEVICE OR END OF LINE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER T1N TEMPERATURE: +32' F 0- C) TO 100' F 38' C) HUMIDITY: O- 9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (-) >- DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOGTY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW TO NEXT DEVICE - > ( ) DATA OUT 1 > (+) DATA OUT o HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID CEILING HARD LID -- SPEAKER SUPPORT TTLE BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSI❑N CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTI❑N BOX ----, MOUNTED ON \\ CEILING( FLEX JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT /i O O O O 1L" TO NEXT DEVICE CADDY BAR SMOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE:NONE SUSPENDED ILLUMINATED CEILING DO \OT INSTAL ADDRESSABLE \IT DEVICES ,dINTI L PREPROGRAMMED W DEVICES ADDRESS. ATI ti TH G Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved RELEASE/REVISIONS REV. BY: z a DESCRIPTION ISHOP DRAWINGS DATE 00 0 M 0 10 2 <aaaa 00 co co0) !) w cc 0 WW0 z = cn z ryw I1 _ezt� O wok D 1- z 0 0 z z E r1 V , 0 SCALE: 1/8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/03/08 BACKROUND PLAN PROVIDED BY: .,JOB NUMBER:54521 SHEET FA -02 NORTH EOL—S1 20.10V JOURNEY WESTFIELD SOUTHCENTER MALL SCALE 118°=1' TAG NOTES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE, FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS.(SEE SIEMENS INSTALLATION SUBMITTAL FOR L❑CATI❑N GUIDELINES AND FA -O2) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR. SIEMENS HTRI-D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NO D AIS A L L ADDRESSABLE IN T ATIN DFVICES J\TIL P PROGRAMMED WO -H DEVICES ADDRESS. G RELEASE/REVISIONS REV. BY: Z Q DESCRIPTION SHOP DRAWINGS DATE CO 0 M 0 CD aaaaa co co co J T Q rt frp Iz W ~� zz_ Z v= CC cc (PO O �o5 ND 1— W CC LL -CALE: 1/8" =1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/03/08 BACKROUND PLAN PROVIDED BY: 1,OB NUMBER:54521 J SHEET FA Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved O3� NORTH JOURNEYS WESTFIELD SOUTHCENTER MALL SCALE 11321=11 EX SYSTEM CALCULATIONS 144 sizi 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS BATTERY SIZING CALCULATION JOURNEYS JOURNEYS FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL DATE 6/03/08 Panel: JOURNEYS Wire Resistance 1.62 z«aaa Date: June 3, 2008 CURRENT TOTAL= Current Load: Standby: Alarm: S1 Current Load: Standby: Alarm: QTY Device Type Alarm Current Alarm Total ~ Wire Size � Wire Length Voltage a_ t EOL Circuit Total�� 1 SET -MC @15CD 64 64 Device Type Qty Amps Total Amps TotalDevice - . -------- Type Qty Amps Total Amps Total HFP-11 0.0022 0.0022 0.0023 233 0 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 AD2-P 1 0.0635 0.0635 0.064 0.064 0 Main System Board ! 1 0.03 0.03 0.030 0.030 HTR -R 2 0.009600 0.0096 0.021 0.042 SET -MC @15CD i 1 1 Z-MC@15CD 64 0.064 0.064 HTRI-D 0.001600 98 0.0035 ....._.. SET -MC @30CD 0 SET-MC-CW@110CD 233 0 0.098 478 ICP -B6 - 0.005 478 12 191 SET -MC @75CD 2 - Notification Appliance Circuit Detail 0.175 0.350 PROJECT: WESTFIELD SOUTHCENTER MALL Panel: JOURNEYS SET -MC @110CD Date: June 3, 2008 CURRENT TOTAL= 5.4 0.233 CIRCUIT: SPEAKER CIRCUIT SET HMC-C@115CD QTY Device Type Alarm Current Alarm Total Wire Size Wire Length 0.318 Circuit Total 3 70.7V1/8 1.8 5.4 SET HMC-C@135CD 0.99 0 0 0 0 0 0.318 L (WL*2)*(R/ft) Total Device Load, Amps (1) 0.01 0 0 0.0731 Amps 0.106 Amps SET HMC-C@185CD ZR -MC @15CD (Total Cct Load) 0 0 0 0.445 Voltage Drop ( E) 0.01 0 0 0 1 (E= I* R) 0.064 0.064 0 Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours 0 ZR -MC @3OCD 0 0.098 0 ci HCP 0 0 20.394677981 5.4 0.0015 DEVICES= 3 Alarm Current Load: 5.4 0.106 Amps For 5 Minutes= 0.009 Amp -hours 0.03 Amps 0.508 Amps 25% Derating= 2.204 Amp -hours Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours Alarm Current Load: 0.508 Amps For 5 Minutes= 0.043 Amp -hours Total System Current Load: 2.204 Amp -hours 25% Derating= 0.953 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.953 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH 144 sizi 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS BATTERY SIZING CALCULATION REV. BY: z Notification Appliance Circuit Detail DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL DATE 6/03/08 Panel: JOURNEYS Wire Resistance 1.62 z«aaa Date: June 3, 2008 CURRENT TOTAL= 478 CIRCUIT: S1 QTY Device Type Alarm Current Alarm Total ~ Wire Size � Wire Length Voltage a_ t EOL Circuit Total�� 1 SET -MC @15CD 64 64 Total Wire Resistance (R) 0.62 0 j SET -MC @30CD 98 0 - . -------- (WL 2) (R/ft) 2 SET -MC @75CD 175 350 Total Device Load, Amps (I) 0.48 0 SET -MC @110CD 233 0 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 Voltage Drop (E) 0.30 0 SET-HMC-C@177CD 445 0 _ (E= I * R) 0 SET -HMC @135CD 318 0 EOL Voltage 20.10 0 SET -HMC @185CD 445 0 (20.4 - E) 1 Z-MC@15CD 64 64 0 Z -MC @30C D 98 0 .._._...... ....._.. 0 SET-MC-CW@110CD 233 0 20.104194481 478 DEVICES= 4 TOTAL m A= 478 12 191 - Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: JOURNEYS Wire Resistance 2:58 Date: June 3, 2008 CURRENT TOTAL= 5.4 CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 3 70.7V1/8 1.8 5.4 Total Wire Resistance (R) 0.99 0 0 0 0 0 L (WL*2)*(R/ft) Total Device Load, Amps (1) 0.01 0 0 0 (Total Cct Load) 0 0 0 Voltage Drop ( E) 0.01 0 0 0 (E= I* R) 0 0 0 EOL Voltage 20.39 0 0 (20.4 - E) 0 ci 0 0 0 20.394677981 5.4 DEVICES= 3 TOTAL mA= 5.4 14 191 REV. BY: z DESCRIPTION I SHOP DRAWINGS DATE 6/03/08 z«aaa CL w CO CC ao.. J CO � NC/) LL1 OC w I-0 w zz z z2w w fr °s z o N 1-- SCALE: 1/8" =1 ' DRAWN BY: LAN DERSON DESIGNED BY: R.VEZZANI DATE: 6/03/08 BACKROUND PLAN PROVIDED BY: �0B NUMBER:54521 1 RISER DIAGRAM VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved SHEET FA -04 1 cam=: JOURNEY'S #2477 VICINITY MAP (Suite #2477) SCALE: NTS General Notes 1. Western States Fire Protection to add new pendent heads new and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary Class II Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads wilt be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only .in The areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. LIU MI LTA EXISTING PIPE .. r -m NEW PIPE LINE OF PLYWOOD BULKHEAD 10'-0 AFF NEW 5/8" TYPE X GYPBOARD CEILING 6 11'-6" SUSPENDED TRACK FROM CEILING AT 10'-0" AFF - TYP ALL TRACK NEW 1/2" GYPBOARD CEILING i 12'-0 AFF - FLAT BLACK PAINTED FINISH JOURNEY'S Remote Area: Retail # 2477 CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY CLASS ORD HAZARD II MAX. COVERAGE per HEAD 130 FN DENSITY .20 GPM /R'for 1047 FN SPRINKLER Reliable Model G4A/ FIFR ORIFICE 1/2' K. 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 PSI FLOW 10900 GPM AT BASE OF RISER, SYSTEM REQUIRES: 315.38 GPM @ 69.87 PSI • At time of Design Ordinary Group il-0.200gpm/ft2 for 1047.69ft2 11'-0 TO 11'-6 AFF INSTALL "N" FIXTURE WITH BOTTOM OF FIXTURE AT 8'-0 AFF GYPBOARD HEADER 6 P-0 2x4 ACT 15'-0 no dm ism tit:®ttaamaIISma ICI Etta t�®t1TWitstItomet�®®!�11tm®Msmit 0 Without Comments.. AsNoted inF? d Per The ,Attached ;vett r !nese plans have ben revi.0 red:by Thir.Turt,a 1# Prevention Bureau `orCu I.i'fitiiti7 .+rdii1.Citrivrltcli standards. Ac aDt-nC:. omissions 4`/h!:il too riot a thLrtzt standaits and ri.}� :air�Cir7iL:S. I f1:: fC?,'.rJC3'ii?iiE.7 1f � Clf•.ti1t°: adequIy-;,y of d- si 11 trit;.:lly viith:trli cf: ; frier'. Additions, G{ fls;G(;d;S a i�ilC?ii`:: 'ftil.tilt?�;F .G"!`uV/1ri s a ter this date will void thy:_ -,E?( Gt;PiI:;r7C(;';-no Wail i'£:C(Ulre resubr .it;a'l of rt,.; i;ed i'i r. f+tii :;:tar:;si}b.s ,giie'i}t'�;p(aroval: Final acc®ptt.nc i., ;-1.it:jc:.t tr; (icid trst:and inspection.bv' The Tukwila Fir: Fr vention:. . Date: Co —J -01 By: I UKWILA FIRE DEPARTMEMY Please call: 575-4407 and give this job Ivo. and exact address for shut. •-own or restoration aonrov!{:I MOTKCE Wek3 stamps must bow hs;'a< c ed before pipe 15 hung. Do not paint pipin6 prior to hydrostatic tes - approva1. RISER ROOM A DETAIL HYDRAULIC REFERENCE ONLY NOT TO SCALE SYMBOL LEGEND REVISIONS SURFACE MOUNTED FLUORESCENT STRIP i� :TYPICAL FLEXABLE SPRINKLER CONNECTION FLEXHEAD SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE.::. IN STANDARD LENGTHS MOUNTING BRACKET' REDUCING FITTING • SPRINKLER HEAD FLEXHEAD DETAIL NOT TO SCALE ////////// / FIG, BOB SWIVEL SWAY BRACE FITTING BRACE PIPE 318' MIK BOLT (2114' EMBED LENGTI- F10.1000 'FAST CLAMP" SWAY BRACE ATTACHMENT LINE PIPE LATERAL LINE RESTRAINTS ®I NON•THREADED BRACE PIPE G4A CONCEALED SPRINKLER HEAD F1FR SEMI REC SPRINKLER HEAD Ida" A SUSPENDED CEILING DETAIL \77...Y NOT TO SCALE Sprinkler Legend 2 -WAY EARTHQUAKE BRACE NO. DESCRIPTION DATE SYM. SIN QTY. SPRAY ORIF. FIN. TEMP. MFR./MODEL APPROVAL: City of Tukwila 4 -WAY EARTHQUAKE BRACE R5415 14 5.6 HYDRAULIC REFERENCE POINT R3615 16 5.6 Pendent Pendent Brass 1ir5°F REL G4A CONCEALOR Chrome 155°F REL FIFR SSP CONT. NO.: N/A HANGER SYMBOL Total = 30 DRAWN BY: CHRIS ISAAC BRANCHLINE RESTRAINT SPRK. ON SHEET: SEE LEGEND SPRK. ON JOB: DATE: 05/29/08 BILE COPY ' KW 0KD BOLT (2131�14 EMBLENGTH FIG. B09 ND•THREAD SWIVEL SWAY BRACE ATTACHMENT i FIG.4A PIPE CLAMP FOR SWAY BRACE ( LATERAL BRANCHLINE RESTRAINT BRACE PIPE 7; NON•THREADED BRACE PIPE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE SUSPENDED CEILING Hanger No. 07C HILTI Kwik Bolt III HILTI Kwik Bolt II i QrllledAnctir / ( / ` 7 Cut Rod Lgth Rounded to Nearest Inch Swivel Ring ti Concrete . Construction Bottom of Concrete to Center Line of Pipe Note an Plan Note on Plan: Hanger Number and 'N Dimension HANGER DETAIL NOT TO SCALE VICINITY MAP DETAIL NOT TO SCALE Western States Fire Protection Company 7102180th AVE NE, STE A 105 - REDMOND, WA - 98052 Ltc. #: WESTESF136QF t'.':. n 2008 Tukwila Fire Zthereekv WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE/AUSTIN/DALLAS/DECATUR/DENVER/DULUTH /HOUSTON) KANSAS CITY LAS VEGAS / MINNEAPOLIS / PHOENIX ! PORTLAND /RAPID CITY/ST. PAUL/SALT LAKE CITY/SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 JOURNEY'S w z 0 GENESCO 0 I- 0 U JOURNEY'S 2477. Southcenter Pkwy TuKwila,WA 98188 JOURNEY'S - TI SHEET FP -1 OF 1 JOURNEY'S #2477 ontionatunimussuillit rielltrial -11-12111- 11-1161 General Notes VICINITY MAP (Suite #2477) bel LI : N 16 1. Western States Fire Protection to add new pendent heads new and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary Class II Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand fiexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The buildina is constructed with non-combustible materials and aualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The nwner is resnnnsihle fnr all annrnpriate maintenance of sprinkler system in accordance with NFPA. as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not riesinned for free7inn C:nnciitinns 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. - ---11 EXISTING PIPE i. NEW PIPE RISER ROOM A DETAIL HYDRAULIC REFERENCE ONLY NOT TO SCALE LINE OF PLYWOOD BULKHEAD @ 10'-0 AFF NEW 5/8" TYPE X GYPBOARD CEILING © 11'-6" SUSPENDED TRACK FROM CEILING AT 1f1'_n" APP _ TVP Al 1 TPAiNe NEW 1/2" GYPBOARD CEILING @ 12'-0 AFF - FLAT BLACK PAINTED FINISH JOURNEY'S Remote Area: Retail # 2477 CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY CLASS _ORD HAZARD II MAX. COVERAGE per HEAD 130 Ft' DENSITY .20 _GPM 1 FN for 1047 F1' SPRINKLER Reliable Model G4A/ F1 FR ORIFICE 1/2" K. 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 PSI FLOW 10900 GPM AT BASE OF RISER, SYSTEM REQUIRES: 315.38 GPM©69.87 PSI * At time of Design GYPBOARD HEADER © 7'-0 2x4 ACT © 15'-0 4 ..... 1162:41.111f..---9 y4- .4-1-1-iiiiii,„ O ®p ---0----_,D___ �•1111111111111111111. �• �N d¢ M =:\ O"_� �_O ' 79 X3-6 O• e 051-7 ort c1 ®-3%E403J1 f I Ir /�o v.'sIz 2o,,,II to r MQ •'(z1 ci -�-� ,,,, ,e'' NM r /0 ...05 r I 5'-• 91-33A I ■ / /.� r Q C it) ■m I N e IIIR ..■ A II mom A I .9 BEN ll 1 CY ., 'en MEM ::I 111111 I r 9 N 4 Q r 4 r mum mom � ��' 1'/ 0'-10✓ 4' i •1 a 9,-� 0 r1 ci 8�-81� :4 2 -4 cii U 1,_® 0;.21'-0 r! w J YN (x .,�,., r - II 4'-B% f _ 10'-0 10'-0 r 0 j SALES AREA " o CO 114'_9 _. 1 T I _, �o M� 1,o III 2'-3%2® I® r Eo N BATHROOM STOCK AREA 0'9% 0 co 9 r C A Ordinary Group II.0.200gpm/ft2 for 1047.69ft2 11'-0 TO 11'-6 AFF II INSTALL "N" FIXTURE WITH BOTTOM OF FIXTURE AT 8'-0 AFF ALCOVE 0'-9% sQ 3 -8'/. 12'-0 r i` Oy:®_ SURFACE MOUNTED FLUORESCENT STRIP b 41 TYPICAL FLEXABLE SPRINKLER CONNECTION FLEXHEAD MOUNTING BRACKET PIPE NIPPLE SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS REDUCING FITTING SUSPENDED T -BAR GRID SPRINKLER HEAD CEILING TILE FLEXHEAD DETAIL NOT TO SCALE FIG. 9D9 SWIVEL SWAY BRACE FITTING 4a1 3/8' KWIK BOLT (2114' EMBED LENGTH) FIG. 1000 "FAST CLAMP" :WAY BRACE ATTACHMENT LATERAL LINE RESTRAINTS NON•THREADED BRACE PIPE G4A CONCEALED SPRINKLER HEAD F1 FR SEMI REC SPRINKLER HEAD SUSPENDED CEILING DETAIL R1 NOT TO SCALE JOURNEY'S - TI 1/8" = 1'-0 FIG. 909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT FIG. 4A PIPE CLAMP FOR SWAY BRACE LATERAL BRANCHLINE RESTRAINT 819' KWIK BOLT (21/4' EMBED LENGTH) BRACE PIPE lad NON -THREADED BRACE PIPE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE SUSPENDED CEILING Hanger No. 07C HILTI Kwik Bolt III / HILTI KwO, Bolt 11 Drilled Anchor Cut Rod Lgth Rounded to Nearest Inch Rod Coupling AU Thread Rod Swivel Ring 1 111 CL Pipe Concrete Construction Bottom of Concrete to Center Line of Pipe Note on Plan Note on Plan: Hanger Number and 'A' Dimension HANGER DETAIL NOT TO SCALE VICINITY MAP DETAIL NOT TO SCALE SYMBOL LEGEND REVISIONS Sprinkler Legend 2 -WAY EARTHQUAKE BRACE NO. DESCRIPTION DATE SYM. SIN QTY. K SPRAY ORIF. FIN. TEMP. MFR./MODEL 4 -WAY EARTHQUAKE BRACE HYDRAULIC REFERENCE POINT 1 R5415 14 5.6 Pendent Brass 155°F REL G4A CONCEALOR APPROVAL: City of Tukwila R3615 16 5.6 Pendent Chrome 155°F REL F1 FR SSP CONT. NO.: N/A Total = 30 DRAWN BY: CHRIS ISAAC HANGER SYMBOL BRANCHLINE RESTRAINT SPRK ON SHEET: SEE LEGEND SPRK. ON JOB: DATE: 07/21/08 Western States Fire Protection Company 7102 180th AVE NE, STE A-105- REDMOND, WA- 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY -OFFICES LOCATED ALBUQUERQUE /AUSTIN /DALLAS/ DECATUR ! DENVER f DULUTH I HOUSTON I KANSAS CITY LAS VEGAS / MINNEAPOLIS / PHOENIXI PORTLAND/RAPID CITY/ ST. PAULI SALT LAKE CITY/ SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 —S.277 JOURNEY'S 2477 Southcenter Pkwy Tukwila,WA 98188 JOURNEY'S - TI (1) z Ct 0 w z 0 CHRIS ISAAC GENESCO 0 0 IY 0 SHEET FP -1 OF 1 2477 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-272 08-S-279 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Journeys 2477 Southcenter Mall Permit No.: 08-S-279 Date: June 5, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • These conditions apply to any sprinkler piping exposed as necessary to accomplish the permitted scope of work. All references are NFPA 13, 2007 Edition. Hydraulic Overview Job Number: N/A Report Description: Ordinary Group II Job Job Number Desgn Engineer N/A CHRIS ISAAC • Job Name Phone FAX JOURNEY'S 425.881.0100 425.881.3030 Address 1 State CetSficalion&Ucense Number 2477 Southcenter Pkwy WESTESF136QF Address 2 AHJ City of Tukwila City State Zip Code Job Site Tukwila WA 98188 Expansion System Dente Area of Application 0.200gpm/ft2 1047.69ft2 (Actual 1047.69ft2) Most Demanding Sprinkler Data Hose Streams 5.6 K -Factor 24.00 at 18.367 250.00 Coverage Per Sprinkler Number Of Sprinklers Calculated 120.00ft2 11 System Pressure Demand System Flow Demand 77.526 315.38 Total Demand Pressure Result 565.38 @ 77.526 +61.970 (44.4%) Supplies Check Point Gauges Node Flow(aDm) Hose Flow(opm) Static(psil Residual(psi) Identifier Pressure(psi) K-Factor(K) Fiow(acm) 40 I i /II P1�: WINIA'takw fl. IIII • 1 10900.00 250.00 140.000 20.000 JOURNEY'S FP-1.cad Supply at Node 1 (10900.00, 250.00, 140.000, 20.000) !'----- 150 11 Static Pressure i 140.000 135 120 105 _ 90 Q d 65.38 with hose streams in 75 in W c15.38@77.5 6 1^ I n`. 60 45 System demand curve 30 10900.00 @ 20.000; 15 11uNllll lllllllll 11111111111111111111111111111 1111111111111111 111 111111 0 193000 5500 6600 7700 8800 9900 11000 Water flow, gpm y(y ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 05/29/2008 2:07:11 PM Page 1 Hydraulic Summary 1 Job Number: N/A Report Description: Ordinary Group II Job Job Number N/A Job Name JOURNEY'S Address 1 2477 Southcenter Pkwy Address 2 City Stale Zip Code Tukwila WA 98188 Design Engineer CHRIS ISAAC State Certification/License Number WESTESF136QF AHJ City of Tukwila Job Site Expansion Drawing Name JOURNEYS FP-1.cad System 1 Remote Area(s) Most Demanding Spnnkler Data 5.6 K -Factor 24.00 at 18.367 Hose Allowance At Source 250.00 Additional Hose Supplies Node Flow(gpm) Occupancy Ordinary Group II Density 0.200gpm/ft2 Number Of Spnnklers Calculated 11 Area of Application 1047.69ft2 (Actual 1047.69ft2) Coverage Per Sprinkler 120.00ft2 Tote! Hose Streams 250.00 System flow Demand Total Water Required (Including Hose Allowance) 315.38 565.38 Maximum Pressure Unbalance In Loops 0.000 Maximum Velocity Above Ground 38.32 between nodes 49 and 48 Maximum Velocity Under Ground 1.19 between nodes 1 and 348 Volume capacity of Wet Pipes Volume capacity of Dry Pipes 3202.22ga1 6.30ga1 Supplies Hose Flow Static Residual @ Flow Node (gpm) (psi) (psi) (gpm) Available @ Total Demand (psi) (gpm) Required Safety Margin (psi) (psi) 1 250.00 140.000 20.000 10900.00 139.497 565.38 77.526 61.970 Contractor Contractor Number N/A Contractor Name Western States Fire Protection (Redmond) Address 1 7102 180th Ave NE, Suite A-105 Address 2 City State Zip Code Redmond WA 98052 Contact Name Chris J Isaac Phone (425)881-0100 FAX (425)881-3030 E-mail chris.isaac@wsfp.us Web -See Contact Tab Designer Extension l� © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 05/29/2008 2:07:12PM Page 2 Summary Of Outflowing Devices Job Number: N/A Report Description: Ordinary Group 11 Device Actual Flow (gpm) Minimum Flow K -Factor Pressure (gpm) (K) (psi) Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler c> Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler 104 103 109 102 105 101 107 106 110 111 108 c> Most Demanding Sprinkler Data 25.66 25.02 32.07 24.89 26.30 24.00 26.82 26.76 36.09 36.14 31.62 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 20.999 19.954 32.803 19.758 22.050 18.367 22.945 22.833 41.534 41.660 31.884 CM, © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 05/29/2008 2:07:12PM Page 3 Node Analysis 1 Job Number: N/A Report Description: Ordinary Group II Node Elevation(Foot) 26 12.-0 20 13'-0 21 12'-0 31 12'-0 38 13'-0 43 13'-0 46 13'-0 52 13'-0 44 13'-0 59 13'-0 48 13'-0 49 13'-0 50 16-0 68 16'-0 66 16-0 67 16'-0 151 16'-0 153 16'-0 184 16'-0 256 -16'-1 306 -16'-1 348 104 11'-614 103 11'-6%4 109 11'-6% 102 11'-61/4 105 12'-0Y4 101 11'-0Y4 107 12'-014 106 11'-0%4 110 12'-01. 111 12'-0%4 108 1 -22'-0 Fittings E(2'-0) E(2'-0) E(2'-0) PO(5'-0) PO(5'-0) PO(5'-0) PO(5'-0) PO(5'-0) PO(8'-0) PO(8'-0) PO(8'-0) LtE(2-0) LtE(3'-0) E(2'-0) E(2'-0) P0(6-0) 3P0(26-4), 3C(26'-4) pog-o) PO(6-0) 2P0(43'-1) BFP(5.000) Spr(-20.999) Spr(-19.954) Spr(-32.803) Spr(-19.758) Spr(-22.050) Spr(-18.367) Spr(-22.945) Spr(-22.833) Spr(-41.534) Spr(-41.660) Spr(-31.884) S Pressure(psi) Discharge(gpm) 26.012 27.897 41.235 26.047 28.050 26.809 29.186 28.502 32.995 41.117 42.257 49.793 51.409 50.472 50.243 39.276 54.362 52.777 52.554 69.350 69.873 73.270 20.999 19.954 32.803 19.758 22.050 18.367 22.945 22.833 41.534 41.660 31.884 77.526 25.66 25.02 32.07 24.89 26.30 24.00 26.82 26.76 36.09 36.14 31.62 315.38 (N, ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 05/29/2008 2:07:13PM Page 4 Hydraulic Analysis Pipe Type Downstream Upstream Job Number: N/A Report Description: Ordinary Group II Diameter Flow Velocity HWC Friction Loss Length Pressure Elevation Discharge K -Factor Pt Pn Fittings Eq. Length Summary Total Length Route 1 DR 1.0490 0=24.00 8.91 C=120 0.182334 101 11'-0Y. q=24.00 K=5.6 18.367 Spr(-18.367) 43 13'-0 26.809 E(2'-0), PO(5'-0) 44'-0 Pf 9.299 7'-0 Pe -0.857 51'-0 Pv BL 1.6100 0=73.91 11.65 C=120 43 13'-0 26.809 52 13'-0 28.502 0.181336 9' 4 Pf 1.693 Pe -0.000 9'-4 Pv BL 1.6100 0=100.67 15.86 C=120 52 13'-0 28.502 44 13'-0 32.995 0.321180 P0(8'-0) 5'-11% Pf 4.492 8'-0 Pe -0.000 13'-11 % Pv BL 1.6100 0=179.45 28.28 C=120 44 13'-0 32.995 59 13'-0 41.117 0.935840 8'-81h Pf 8.122 Pe -0.000 8'-8% Pv BL 1.6100 Q=211.07 33.26 C=120 59 13'-0 41.117 48 13'-0 42.257 1.263571 0'-10% Pf 1.141 Pe -0.000 0'-10'/. Pv BL 1.6100 Q=243.14 38.32 C=120 48 13'-0 42.257 49 13'-0 49.793 1.641554 LtE(2'-0) 2'-7 Pf 7.536 2'-0 Pe -0.000 4'-7 Pv BL 2.0670 0=243.14 23.25 C=120 49 13'-0 49.793 50 16'-0 51.409 0.486171 LtE(3'-0) 3'-0 Pf 2.917 3'-0 Pe -1.301 6'-0 Pv CM 4.2600 Q=243.14 5.47 C=120 50 16-0 51.409 184 16'-0 52.554 0.014364 PO(26'-4) 53'-5 Pf 1.146 26'-4 Pe -0.001 79'-9 Pv CM 4.2600 0=279.29 6.29 C=120 184 16'-0 52.554 153 16'-0 52.777 0.018562 12'-0 Pf 0.223 Pe 12'-0 Pv CM 4.2600 0=315.38 7.10 C=120 0.023242 15-6Y2 Pf 1.585 153 16'-0 52.777 52'-8 Pe 151 16'-0 54.362 P0(26-4), C(26'-4) 68'-2'/ Pv CM 6.3570 0=315.38 3.19 C=120 151 16'-0 54.362 256 -16-1 69.350 0.003309 10fE(12'-7), BV(12'-7), fE(10'-0), CV(40'-2%), GV(3'-9'h) 133'-91/2 Pf 1.079 192'-3% Pe 13.909 326.-1% Pv BL 8.3290 Q=315.38 1.86 C=120 0.000888 13'-4 Pf 0.523 256 -16'-1 69.350 P0(43'-1) 576-1Y2 Pe -0.000 306 -16'-1 69.873 12P0(43'-1), fE(16'-0) 589'-5Y2 Pv MS 10.0200 Q=315.38 1.28 C=120 306 -16-1 69.873 348 -12'-3% 73.270 0.000361 3LtE(16'-0), BV(19'-0), BFP(-5.000) 20'-2 Pf 5.031 67'-0 Pe -1.635 87'-2 Pv UG 10.4000 Q=315.38 1.19 C=140 0.000226 112'-10% Pf 0.057 348 -12'-3% 73.270 137'-1% Pe 4.200 1 -22'-0 77.526 4LtE(25'-6), 2EE(17'-6Y2), S 250'-0 Pv Qi Route 2 DR 1.0490 0=24.89 9.24 C=120 0.195069 26'-3V2 Pf 6.496 102 11'-6Y. q=24.89 K=5.6 19.758 Spr(-19.758) 7'-0 Pe -0.207 31 12'-0 26.047 E(2'-0), PO(5'-0) 33'-3Y2 Pv BL 1.6100 0=49.91 7.87 C=120 31 12'-0 26.047 43 13'-0 26.809 0.087703 2LtE(2'-0) 9'-7'/2 Pf 1.196 4'-0 Pe -0.434 13'-7Y2 Pv Route 3 DR 1.0490 0=25.02 9.29 C=120 0.196860 27-93h Pf 6.265 103 11'-6Y. q=25.02 K=5.6 19.954 Spr(-19.954) 4'-0 Pe -0.207 26 12'-0 26.012 2E(2'-0) 31'-9'/1 Pv BL 1.6100 Q=25.02 3.94 C=120 26 12'-0 26.012 31 12'-0 26.047 0.024439 1'-5'/. Pf 0.035 Pe 1'-5Y. Pv ao Route 4 DR 1.0490 0=25.66 9.53 C=120 0.206375 28'-6% Pf 7.539 104 11'-6% q=25.66 K=5.6 20.999 Spr(-20.999) 8'-0 Pe -0.640 20 13'-0 27.897 4E(2'-0) 36'-61h Pv BL 1.6100 Q=25.66 4.04 C=120 20 13'-0 27.897 38 13'-0 28.050 0.025621 5'-11% Pf 0.152 Pe 5.-11% Pv BL 1.6100 0=51.96 8.19 C=120 38 13'-0 28.050 46 13'-0 29.186 0.094486 12'-0Y. Pf 1.136 Pe 12'-0'h Pv BL 1.6100 0=78.78 12.42 C=120 46 13'-0 29.186 44 13'-0 32.995 0.204082 LtE(2'-0) 16'-8 Pf 3.809 2'-0 Pe -0.000 18'-8 Pv a Route 5 (M ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 05/29/2008 2:07:13PM Page 5 Hydraulic Analysis 1 Job Number: N/A Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity Downstream Elevation Discharge K -Factor Upstream HWC Pt Friction Loss Pn Fittings Length Pressure Eq. Length Summary Total Length DR 1.0490 Q=26.30 9.76 C=120 0.215911 22'-9 Pf 6.423 105 12'-0Y+ q=26.30 K=5.6 22.050 Spr(-22.050) 7'-0 Pe -0.423 38 13'-0 28.050 E(2'-0), PO(5'-0) 29'-9 Pv .+ Route 6 DR 1.0490 Q=26.76 9.93 C=120 0.222998 22'-3Y. Pf 6.526 106 11'-0Y, q=26.76 K=5.6 22.833 Spr(-22.833) 7'-0 Pe -0.857 52 13'-0 28.502 E(2'-0), PO(5'-0) 29'-3% Pv a Route 7 DR 1.0490 Q=26.82 9.96 C=120 0.224006 22'-9 Pf 6.664 107 12'-0%, q=26.82 K=5.6 22.945 Spr(-22.945) 7'-0 Pe -0.423 46 13'-0 29.186 E(2'-0), PO(5'-0) 29'-9 Pv a Route 8 DR 1.0490 Q=31.62 11.74 C=120 0.303689 22'-11% Pf 9.107 108 12'-0% q=31.62 K=5.6 31.884 Spr(-31.884) 7'-0 Pe -1.715 67 16-0 39.276 E(2'-0), PO(5'-0) 29.-11% Pv BL 1.6100 Q=31.62 4.98 C=120 0.037702 4'-3' Pf 0.540 67 16'-0 39.276 10'-0 Pe 1.301 59 13'-0 41.117 LtE(2'-0), PO(8'-0) 14'-3% Pv a Route 9 DR 1.0490 Q=32.07 11.91 C=120 0.311773 23'-8Y2 Pf 8.639 109 11'-6% q=32.07 K=5.6 32.803 Spr(-32.803) 4'-0 Pe -0.207 21 12'-0 41.235 2E(2'-0) 27-812 Pv BL 1.6100 Q=32.07 5.05 C=120 0.038706 25'-7Y2 Pf 1.456 21 12'-0 41.235 12'-0 Pe -0.434 48 13'-0 42.257 2LtE(2'-0), PO(8'-0) 37'-7% Pv r+ Route 10 DR 1.0490 Q=36.09 13.40 C=120 0.387837 23'-6 Pf 10.663 110 12'-0% q=36.09 K=5.6 41.534 Spr(-41.534) 4'-0 Pe -1.725 68 16-0 50.472 2E(2'-0) 27'-6 Pv BL 1.6100 Q=36.09 5.69 C=120 0.048149 39'-10Y4 Pf 2.304 68 16'-0 50.472 8'-0 Pe -0.000 153 16'-0 52.777 PO(8'-0) 47'-10% Pv a Route 11 DR 1.0490 Q=36.14 13.42 C=120 0.388922 22'-6 Pf 10.309 111 12'-0% q=36.14 K=5.6 41.660 Spr(-41.660) 4'-0 Pe -1.725 66 16-0 50.243 2E(2'-0) 26'-6 Pv BL 1.6100 Q=36.14 5.70 C=120 0.048283 39'-10Y4 Pf 2.311 66 16'-0 50.243 8'-0 Pe -0.000 184 16'-0 52.554 PO(8'-0) 47'-10Y4 Pv Equivalent Pipe Lengths of Valves and Fittings (C=120 only) ` C Value Multiplier II Actual Inside Diameter 4.87 ) = Factor Value Of C 100 130 140 150 ( Schedule 40 Steel Pipe Inside Diameter Multiplying Factor 0.713 1.16 1.33 1.51 ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 05/29/2008 2:07:13PM Page 6 I Hydraulic Analysis Pipe Type Downstream Upstream Diameter Elevation Flow Discharge Job Number: N/A Report Description: Ordinary Group II Velocity HWC K -Factor Pt Friction Loss Pn Fittings Length Pressure Eq. Length Summary Total Length Pipe Type Legend Units Legend Fittings Legend AO BL CM DN DR DY FM FR MS OR RN SP ST UG Arm -Over Diameter Branch Line Elevation Cross Main Flow Drain Discharge Drop Velocity Dynamic Pressure Feed Main Length Feed Riser Friction Loss Miscellaneous HWC Outrigger Pt Riser Nipple Pn Sprig pf Stand Pipe Pe Underground Pv Inch Foot gpm gpm fps psi Foot psi/Foot Hazen -Williams Constant Total pressure at a point in a pipe Normal pressure at a point in a pipe Pressure loss due to friction between points Pressure due to elevation difference between indicated points Velocity pressure at a point in a pipe ALV Alarm Valve AngV Angle Valve b Bushing BaIV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Turn 90° cplg Coupling Cr Cross Run CV Check Valve DeIV Deluge Valve DPV Dry Pipe Valve E 90° Elbow EE 45° Elbow Eel 11%° Elbow Ee2 22%° Elbow f Flow Device FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow flg Flange FN Floating Node fT FireLock(TM) Tee g Gauge GIoV Globe Valve GV Gate Valve Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PrV Pressure Relief Valve PRV Pressure Reducing Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 900 Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap (M © M.E.P.CAD, Inc. AutoSPRINK®VR5 v5.1.32 05/29/2008 2:07:13PM Page 7 ii Hydraulic Graph Job Number: N/A Re ort Description: Ordinary Group II • Supply at Node 1 150 -Static Pressure 140.000 135 120 105 90 a E 75 315.38 w fn - rp _ d - .565.38 with hose @ 77.526 streams 60 45 :System demand curve 30 - 10900.00 @ 20.000, 15 W 111111111111111111 111111111 111111111 11111 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 i10022°° 3300 4400 5500 6600 7700 Water flow, gpm 8800 9900 11000 Hydraulic Graph Supply at Node 1 Static Pressure 140.000 Residual Pressure 10900.00 @ 20.000 Available PressureTime of Test 139.497 @ 565.38 System Demand 315.38 @ 77.526 System Demand (Including Hose Allowance) 565.38 @ 77.526 (M ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 05/29/2008 2:07: age Flow Diagram (Top View) 1 Job Number: N/A Report Description: Ordinary Group 11 ©M.E.P.CAD, Inc. AutoSPRINK®VR5 v5.1.32 05/29/2008 2:07:15PM Page 9 S EET \U V REQ SHEET TITLE SHEET INDEX JOU RE ALARM YTEM TUKWILA, WASHINGTON EY FA -01 SYSTE V INFOMATIO\ FA -02 TYPICAL DETAILS - WI�I \G A\3 VOU\TI\G FA -03 FI �E ALARM SYSTEM FLOO PLA\ FA -04 SYSTEM CALCULATIO \S (cE\EAL), RISER, SITE PLA\ WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END GENERAL NOTES FOR. SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED: NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF ,NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TQ FIRST DEVICE 'ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 2 1 EX SYMBOL DESCRIPTION SYMBOLS LEGEND MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD B a LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING DUCT SMOKE AD DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP IN/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 4S DEEP BOX W/ 1-1/2" EXT. CEILING 80" A.F.F. TO BOTTOM FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -:-CW SIEMENS 4S BOX W/ 1G RING CEILING L YC FIRE ALARM STROBE (WALL MOUNT) ZR -MC W SIEMENS 19 90X W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX W/ 1-1 /2" EXT. CEILING B WP MR FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) MULTI -VOLTAGE CONTROL RELAY SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -S17 -WP SIEMENS MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD 0 MAGNETIC DOOR HOLDER F.B.O. M. FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. CCg qTE VERT IN F LD JUNCTI❑N BOX F.B.O. F.B.❑. N/A VERT IN F LD A,F,F, WIRE DESIGNATION SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D H P S A V I X UD UI M B DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 •FPL/FPLR RED (JACKET) DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) ANNUNCIATOR TWISTED PAIR W/ SHIELD 4416 FPL/FPLR RED (JACKET) SPEAKER CIRCUIT - FEED TWISTED PAIR 4414 FPL/FPLR RED (JACKET) REMOTE INDICATION LIGHT TWD #18 FPL/FPLR RED (JACKET) LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UNDERGROUND INITIATI❑N TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) DOOR HOLDER POWER TWO *16 FPL/FPLR RED (JACKET) BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) F.B.O. CONDUIT FILL CHART N/A NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL • 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END GENERAL NOTES FOR. SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED: NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF ,NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TQ FIRST DEVICE 'ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 2 1 EX SYMBOL DESCRIPTION SYMBOLS LEGEND MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD B a LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING DUCT SMOKE AD DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP IN/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 4S DEEP BOX W/ 1-1/2" EXT. CEILING 80" A.F.F. TO BOTTOM FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -:-CW SIEMENS 4S BOX W/ 1G RING CEILING L YC FIRE ALARM STROBE (WALL MOUNT) ZR -MC W SIEMENS 19 90X W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX W/ 1-1 /2" EXT. CEILING B WP MR FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) MULTI -VOLTAGE CONTROL RELAY SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -S17 -WP SIEMENS MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD 0 MAGNETIC DOOR HOLDER F.B.O. M. FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. CCg qTE VERT IN F LD JUNCTI❑N BOX F.B.O. F.B.❑. N/A VERT IN F LD A,F,F, ABOVE FINISHED FLOOR N/A �..v �AsNoted IrO N/A Ad N/A ❑ Per The Attached Letter F.B.O. FURNISHED BY OTHERS N/A i riUtii plans have been revli d by The Tukwila Fir@/A Prevention Bureau for conformance with current city N/A NOT APPLICABLE N/A standards. Acceptance Is suhlect to errors and orh6 ons which do not aut 1 rile violations of adopt6Id'A stanaaras and orainances. The responsibility for the U,❑.N. UNLESS OTHERWISE NOTED N/A adequacy of aesign rests totally with the designer. A�lititms, deletions or revislk46 to these drawings aftWrA this date will void this acceptance and will require a WP WEATHERPROOF DEVICE N/A resubmittal of revised drawings for subsequent appy v N/A N/A R1�A Final acceptance is subject to field test and inspection by RED AS BUILT ADD OR CHANGE N/A The Tukwila Fire Prevention Bureau. N/A N/?�7 N/A Date: ®gi By: _ __, AS BUILT N/A REMOVE BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A tUKWIIA FIRE DEPARTM1tA Please call: 575-440Z and give this job No. J exact address for shut• ' n or restoration approval, RECEIVED JIJN - 3 2008A0 co&201q RELEASE/REVISIONS REV. BY: I NVI DESCRIPTION SHOP DRAWINGS DATE 6/03/08 k ««< T <0) 1 w CEO W(DZZ z 2 w1 D 1--ic Q crop FL ~� N F - Z 0 F cc 0 z SCALE: 1 /8"=1 DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/03/08 BACKROUND PLAN PROVIDED BY: 101i3 NUMBER:54521 SHEET Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved FA -41 1 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE DUCT DETECTOR L❑CATI❑N FROM XLS CONTROL PANEL OR PREVI❑US ADDRESSABLE DEVIC END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH GROUND 0 0 �t- 10 0 0 HTRI—R OSTATUS LED 00 N.O. a COM to m N NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE PREVI❑US ADDRESSABLE DEVICE (BACKGOUND MUSIC SHUTDOWN) TO NEXT ADDRESSABLE DEVICE L NOTE 1: VOLTAGE MAX, - CURRENT MAX. - CONT. RES, MAX. - MAX, CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX, LINE SIZE - MIN, LINE SIZE- OUTLET SAMPLING TUBE INLET SAMPLING TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE MUSIC —1.) -AC POWER SOURCE COMBINE ALL SHIELDS AND IS❑LATE FROM GROUNDING 0 TO NEXT ADDRESSABLE DEVICE f(+) STOP IF LAST DEVICE (-) FROM XLS CONTROL PANEL OR .[(+) PREVI❑US ADDRESSABLE DEVICE ()- RELAY CONTACTS (4.OA @ 125VAC) (4.OA @ 3OVDC) 27 VDC 3.5 nA DURING POLLING 10 OHMS 200 FT, (18 AWG) 0,02uF 0,04uF 14 AWG 18 AWG NOTE 2; ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST 25 SEC. TO GUARANTEE DETECTION, 0 1001 TB1 S. 0 0 0 0 123456 HC TB2 D 00 65 43 +- 21 0 END OF LINE 1 0 DEVICE0 (3.6K 1/4W) .'� i 0 SUPERVISED___/ SWITCH GROUND NOTE: ; 1 ; ; Pr) 0 0 HTRI—D OSTATUS LED m NOT USED END OF LINE DEVICE 3.6K 1/4W) 0 FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE C (FIRE SUPPRESSION SYSTEM INTERFACE) 0 0 GND N AC O 0 0 T rT Y PAD -3 0 00 0 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 0 uuuu 0 0 0 0 0 0 0 24K TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE NAC -4 NAC -3 2 NAC -2 NAC -1 \ UPERVISED SWITCH 2 FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 1 '4,-::1--'\ NOT USED REMOTE + ill DEVICE LOOP NOT USED REMOTE ..I. ( \ DEVICE LOOP %1-' 0 0 0 {FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY C'S' CABLE) FROM FACP (V❑ICE CIRCUIT) ('V' CABLE) 470 OHMS �IV EOL N T M-1 O 0 TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE NONE rTh () S (-) STROBE SPEAKER + v (STR❑BE) ) EARTH GROUND 0 -->(+)TO NEXT DEVICE OR } >(-) STOP IF LAST DEVICE (+) (-) STROBE SPEAKER ("-N (-) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY 4S DEEP BOX W/ 1-1 /2" EXTENSION RING (SPEAKER SIHOBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE TO NEXT DEVICE ❑R END OF LINE TO NEXT DEVICE OR END OF LINE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER T1N TEMPERATURE: +32' F 0- C) TO 100' F 38' C) HUMIDITY: O- 9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (-) >- DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOGTY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW TO NEXT DEVICE - > ( ) DATA OUT 1 > (+) DATA OUT o HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID CEILING HARD LID -- SPEAKER SUPPORT TTLE BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSI❑N CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTI❑N BOX ----, MOUNTED ON \\ CEILING( FLEX JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT /i O O O O 1L" TO NEXT DEVICE CADDY BAR SMOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE:NONE SUSPENDED ILLUMINATED CEILING DO \OT INSTAL ADDRESSABLE \IT DEVICES ,dINTI L PREPROGRAMMED W DEVICES ADDRESS. ATI ti TH G Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved RELEASE/REVISIONS REV. BY: z a DESCRIPTION ISHOP DRAWINGS DATE 00 0 M 0 10 2 <aaaa 00 co co0) !) w cc 0 WW0 z = cn z ryw I1 _ezt� O wok D 1- z 0 0 z z E r1 V , 0 SCALE: 1/8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/03/08 BACKROUND PLAN PROVIDED BY: .,JOB NUMBER:54521 SHEET FA -02 NORTH EOL—S1 20.10V JOURNEY WESTFIELD SOUTHCENTER MALL SCALE 118°=1' TAG NOTES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE, FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS.(SEE SIEMENS INSTALLATION SUBMITTAL FOR L❑CATI❑N GUIDELINES AND FA -O2) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR. SIEMENS HTRI-D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NO D AIS A L L ADDRESSABLE IN T ATIN DFVICES J\TIL P PROGRAMMED WO -H DEVICES ADDRESS. G RELEASE/REVISIONS REV. BY: Z Q DESCRIPTION SHOP DRAWINGS DATE CO 0 M 0 CD aaaaa co co co J T Q rt frp Iz W ~� zz_ Z v= CC cc (PO O �o5 ND 1— W CC LL -CALE: 1/8" =1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/03/08 BACKROUND PLAN PROVIDED BY: 1,OB NUMBER:54521 J SHEET FA Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved O3� NORTH JOURNEYS WESTFIELD SOUTHCENTER MALL SCALE 11321=11 EX SYSTEM CALCULATIONS 144 sizi 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS BATTERY SIZING CALCULATION JOURNEYS JOURNEYS FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL DATE 6/03/08 Panel: JOURNEYS Wire Resistance 1.62 z«aaa Date: June 3, 2008 CURRENT TOTAL= Current Load: Standby: Alarm: S1 Current Load: Standby: Alarm: QTY Device Type Alarm Current Alarm Total ~ Wire Size � Wire Length Voltage a_ t EOL Circuit Total�� 1 SET -MC @15CD 64 64 Device Type Qty Amps Total Amps TotalDevice - . -------- Type Qty Amps Total Amps Total HFP-11 0.0022 0.0022 0.0023 233 0 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 AD2-P 1 0.0635 0.0635 0.064 0.064 0 Main System Board ! 1 0.03 0.03 0.030 0.030 HTR -R 2 0.009600 0.0096 0.021 0.042 SET -MC @15CD i 1 1 Z-MC@15CD 64 0.064 0.064 HTRI-D 0.001600 98 0.0035 ....._.. SET -MC @30CD 0 SET-MC-CW@110CD 233 0 0.098 478 ICP -B6 - 0.005 478 12 191 SET -MC @75CD 2 - Notification Appliance Circuit Detail 0.175 0.350 PROJECT: WESTFIELD SOUTHCENTER MALL Panel: JOURNEYS SET -MC @110CD Date: June 3, 2008 CURRENT TOTAL= 5.4 0.233 CIRCUIT: SPEAKER CIRCUIT SET HMC-C@115CD QTY Device Type Alarm Current Alarm Total Wire Size Wire Length 0.318 Circuit Total 3 70.7V1/8 1.8 5.4 SET HMC-C@135CD 0.99 0 0 0 0 0 0.318 L (WL*2)*(R/ft) Total Device Load, Amps (1) 0.01 0 0 0.0731 Amps 0.106 Amps SET HMC-C@185CD ZR -MC @15CD (Total Cct Load) 0 0 0 0.445 Voltage Drop ( E) 0.01 0 0 0 1 (E= I* R) 0.064 0.064 0 Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours 0 ZR -MC @3OCD 0 0.098 0 ci HCP 0 0 20.394677981 5.4 0.0015 DEVICES= 3 Alarm Current Load: 5.4 0.106 Amps For 5 Minutes= 0.009 Amp -hours 0.03 Amps 0.508 Amps 25% Derating= 2.204 Amp -hours Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours Alarm Current Load: 0.508 Amps For 5 Minutes= 0.043 Amp -hours Total System Current Load: 2.204 Amp -hours 25% Derating= 0.953 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.953 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH 144 sizi 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS BATTERY SIZING CALCULATION REV. BY: z Notification Appliance Circuit Detail DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL DATE 6/03/08 Panel: JOURNEYS Wire Resistance 1.62 z«aaa Date: June 3, 2008 CURRENT TOTAL= 478 CIRCUIT: S1 QTY Device Type Alarm Current Alarm Total ~ Wire Size � Wire Length Voltage a_ t EOL Circuit Total�� 1 SET -MC @15CD 64 64 Total Wire Resistance (R) 0.62 0 j SET -MC @30CD 98 0 - . -------- (WL 2) (R/ft) 2 SET -MC @75CD 175 350 Total Device Load, Amps (I) 0.48 0 SET -MC @110CD 233 0 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 Voltage Drop (E) 0.30 0 SET-HMC-C@177CD 445 0 _ (E= I * R) 0 SET -HMC @135CD 318 0 EOL Voltage 20.10 0 SET -HMC @185CD 445 0 (20.4 - E) 1 Z-MC@15CD 64 64 0 Z -MC @30C D 98 0 .._._...... ....._.. 0 SET-MC-CW@110CD 233 0 20.104194481 478 DEVICES= 4 TOTAL m A= 478 12 191 - Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: JOURNEYS Wire Resistance 2:58 Date: June 3, 2008 CURRENT TOTAL= 5.4 CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 3 70.7V1/8 1.8 5.4 Total Wire Resistance (R) 0.99 0 0 0 0 0 L (WL*2)*(R/ft) Total Device Load, Amps (1) 0.01 0 0 0 (Total Cct Load) 0 0 0 Voltage Drop ( E) 0.01 0 0 0 (E= I* R) 0 0 0 EOL Voltage 20.39 0 0 (20.4 - E) 0 ci 0 0 0 20.394677981 5.4 DEVICES= 3 TOTAL mA= 5.4 14 191 REV. BY: z DESCRIPTION I SHOP DRAWINGS DATE 6/03/08 z«aaa CL w CO CC ao.. J CO � NC/) LL1 OC w I-0 w zz z z2w w fr °s z o N 1-- SCALE: 1/8" =1 ' DRAWN BY: LAN DERSON DESIGNED BY: R.VEZZANI DATE: 6/03/08 BACKROUND PLAN PROVIDED BY: �0B NUMBER:54521 1 RISER DIAGRAM VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved SHEET FA -04 1 cam=: JOURNEY'S #2477 VICINITY MAP (Suite #2477) SCALE: NTS General Notes 1. Western States Fire Protection to add new pendent heads new and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary Class II Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads wilt be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only .in The areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. LIU MI LTA EXISTING PIPE .. r -m NEW PIPE LINE OF PLYWOOD BULKHEAD 10'-0 AFF NEW 5/8" TYPE X GYPBOARD CEILING 6 11'-6" SUSPENDED TRACK FROM CEILING AT 10'-0" AFF - TYP ALL TRACK NEW 1/2" GYPBOARD CEILING i 12'-0 AFF - FLAT BLACK PAINTED FINISH JOURNEY'S Remote Area: Retail # 2477 CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY CLASS ORD HAZARD II MAX. COVERAGE per HEAD 130 FN DENSITY .20 GPM /R'for 1047 FN SPRINKLER Reliable Model G4A/ FIFR ORIFICE 1/2' K. 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 PSI FLOW 10900 GPM AT BASE OF RISER, SYSTEM REQUIRES: 315.38 GPM @ 69.87 PSI • At time of Design Ordinary Group il-0.200gpm/ft2 for 1047.69ft2 11'-0 TO 11'-6 AFF INSTALL "N" FIXTURE WITH BOTTOM OF FIXTURE AT 8'-0 AFF GYPBOARD HEADER 6 P-0 2x4 ACT 15'-0 no dm ism tit:®ttaamaIISma ICI Etta t�®t1TWitstItomet�®®!�11tm®Msmit 0 Without Comments.. AsNoted inF? d Per The ,Attached ;vett r !nese plans have ben revi.0 red:by Thir.Turt,a 1# Prevention Bureau `orCu I.i'fitiiti7 .+rdii1.Citrivrltcli standards. Ac aDt-nC:. omissions 4`/h!:il too riot a thLrtzt standaits and ri.}� :air�Cir7iL:S. I f1:: fC?,'.rJC3'ii?iiE.7 1f � Clf•.ti e adequIy-;,y of d- si 11 trit;.:lly viith:trli cf: ; frier'. Additions, G{ fls;G(;d;S a i�ilC?ii`:: 'ftil.tilt?�;F .G"!`uV/1ri s a ter this date will void thy:_ -,E?( Gt;PiI:;r7C(;';-no Wail i'£:C(Ulre resubr .it;a'l of rt,.; i;ed i'i r. f+tii :;:tar:;si}b.s ,giie'i}t'�;p(aroval: Final acc®ptt.nc i., ;-1.it:jc:.t tr; (icid trst:and inspection.bv' The Tukwila Fir: Fr vention:. . Date: Co —J -01 By: I UKWILA FIRE DEPARTMEMY Please call: 575-4407 and give this job Ivo. and exact address for shut. •-own or restoration aonrov!{:I MOTKCE Wek3 stamps must bow hs;'a< c ed before pipe 15 hung. Do not paint pipin6 prior to hydrostatic tes - approva1. RISER ROOM A DETAIL HYDRAULIC REFERENCE ONLY NOT TO SCALE SYMBOL LEGEND REVISIONS SURFACE MOUNTED FLUORESCENT STRIP i� :TYPICAL FLEXABLE SPRINKLER CONNECTION FLEXHEAD SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE.::. IN STANDARD LENGTHS MOUNTING BRACKET' REDUCING FITTING • SPRINKLER HEAD FLEXHEAD DETAIL NOT TO SCALE ////////// / FIG, BOB SWIVEL SWAY BRACE FITTING BRACE PIPE 318' MIK BOLT (2114' EMBED LENGTI- F10.1000 'FAST CLAMP" SWAY BRACE ATTACHMENT LINE PIPE LATERAL LINE RESTRAINTS ®I NON•THREADED BRACE PIPE G4A CONCEALED SPRINKLER HEAD F1FR SEMI REC SPRINKLER HEAD Ida" A SUSPENDED CEILING DETAIL \77...Y NOT TO SCALE Sprinkler Legend 2 -WAY EARTHQUAKE BRACE NO. DESCRIPTION DATE SYM. SIN QTY. SPRAY ORIF. FIN. TEMP. MFR./MODEL APPROVAL: City of Tukwila 4 -WAY EARTHQUAKE BRACE R5415 14 5.6 HYDRAULIC REFERENCE POINT R3615 16 5.6 Pendent Pendent Brass 1ir5°F REL G4A CONCEALOR Chrome 155°F REL FIFR SSP CONT. NO.: N/A HANGER SYMBOL Total = 30 DRAWN BY: CHRIS ISAAC BRANCHLINE RESTRAINT SPRK. ON SHEET: SEE LEGEND SPRK. ON JOB: DATE: 05/29/08 BILE COPY ' KW 0KD BOLT (2131�14 EMBLENGTH FIG. B09 ND•THREAD SWIVEL SWAY BRACE ATTACHMENT i FIG.4A PIPE CLAMP FOR SWAY BRACE ( LATERAL BRANCHLINE RESTRAINT BRACE PIPE 7; NON•THREADED BRACE PIPE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE SUSPENDED CEILING Hanger No. 07C HILTI Kwik Bolt III HILTI Kwik Bolt II i QrllledAnctir / ( / ` 7 Cut Rod Lgth Rounded to Nearest Inch Swivel Ring ti Concrete . Construction Bottom of Concrete to Center Line of Pipe Note an Plan Note on Plan: Hanger Number and 'N Dimension HANGER DETAIL NOT TO SCALE VICINITY MAP DETAIL NOT TO SCALE Western States Fire Protection Company 7102180th AVE NE, STE A 105 - REDMOND, WA - 98052 Ltc. #: WESTESF136QF t'.':. n 2008 Tukwila Fire Zthereekv WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE/AUSTIN/DALLAS/DECATUR/DENVER/DULUTH /HOUSTON) KANSAS CITY LAS VEGAS / MINNEAPOLIS / PHOENIX ! PORTLAND /RAPID CITY/ST. PAUL/SALT LAKE CITY/SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 JOURNEY'S w z 0 GENESCO 0 I- 0 U JOURNEY'S 2477. Southcenter Pkwy TuKwila,WA 98188 JOURNEY'S - TI SHEET FP -1 OF 1 JOURNEY'S #2477 ontionatunimussuillit rielltrial -11-12111- 11-1161 General Notes VICINITY MAP (Suite #2477) bel LI : N 16 1. Western States Fire Protection to add new pendent heads new and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary Class II Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand fiexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The buildina is constructed with non-combustible materials and aualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The nwner is resnnnsihle fnr all annrnpriate maintenance of sprinkler system in accordance with NFPA. as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not riesinned for free7inn C:nnciitinns 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. - ---11 EXISTING PIPE i. NEW PIPE RISER ROOM A DETAIL HYDRAULIC REFERENCE ONLY NOT TO SCALE LINE OF PLYWOOD BULKHEAD @ 10'-0 AFF NEW 5/8" TYPE X GYPBOARD CEILING © 11'-6" SUSPENDED TRACK FROM CEILING AT 1f1'_n" APP _ TVP Al 1 TPAiNe NEW 1/2" GYPBOARD CEILING @ 12'-0 AFF - FLAT BLACK PAINTED FINISH JOURNEY'S Remote Area: Retail # 2477 CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY CLASS _ORD HAZARD II MAX. COVERAGE per HEAD 130 Ft' DENSITY .20 _GPM 1 FN for 1047 F1' SPRINKLER Reliable Model G4A/ F1 FR ORIFICE 1/2" K. 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 PSI FLOW 10900 GPM AT BASE OF RISER, SYSTEM REQUIRES: 315.38 GPM©69.87 PSI * At time of Design GYPBOARD HEADER © 7'-0 2x4 ACT © 15'-0 4 ..... 1162:41.111f..---9 y4- .4-1-1-iiiiii,„ O ®p ---0----_,D___ �•1111111111111111111. �• �N d¢ M =:\ O"_� �_O ' 79 X3-6 O• e 051-7 ort c1 ®-3%E403J1 f I Ir /�o v.'sIz 2o,,,II to r MQ •'(z1 ci -�-� ,,,, ,e'' NM r /0 ...05 r I 5'-• 91-33A I ■ / /.� r Q C it) ■m I N e IIIR ..■ A II mom A I .9 BEN ll 1 CY ., 'en MEM ::I 111111 I r 9 N 4 Q r 4 r mum mom � ��' 1'/ 0'-10✓ 4' i •1 a 9,-� 0 r1 ci 8�-81� :4 2 -4 cii U 1,_® 0;.21'-0 r! w J YN (x .,�,., r - II 4'-B% f _ 10'-0 10'-0 r 0 j SALES AREA " o CO 114'_9 _. 1 T I _, �o M� 1,o III 2'-3%2® I® r Eo N BATHROOM STOCK AREA 0'9% 0 co 9 r C A Ordinary Group II.0.200gpm/ft2 for 1047.69ft2 11'-0 TO 11'-6 AFF II INSTALL "N" FIXTURE WITH BOTTOM OF FIXTURE AT 8'-0 AFF ALCOVE 0'-9% sQ 3 -8'/. 12'-0 r i` Oy:®_ SURFACE MOUNTED FLUORESCENT STRIP b 41 TYPICAL FLEXABLE SPRINKLER CONNECTION FLEXHEAD MOUNTING BRACKET PIPE NIPPLE SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS REDUCING FITTING SUSPENDED T -BAR GRID SPRINKLER HEAD CEILING TILE FLEXHEAD DETAIL NOT TO SCALE FIG. 9D9 SWIVEL SWAY BRACE FITTING 4a1 3/8' KWIK BOLT (2114' EMBED LENGTH) FIG. 1000 "FAST CLAMP" :WAY BRACE ATTACHMENT LATERAL LINE RESTRAINTS NON•THREADED BRACE PIPE G4A CONCEALED SPRINKLER HEAD F1 FR SEMI REC SPRINKLER HEAD SUSPENDED CEILING DETAIL R1 NOT TO SCALE JOURNEY'S - TI 1/8" = 1'-0 FIG. 909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT FIG. 4A PIPE CLAMP FOR SWAY BRACE LATERAL BRANCHLINE RESTRAINT 819' KWIK BOLT (21/4' EMBED LENGTH) BRACE PIPE lad NON -THREADED BRACE PIPE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE SUSPENDED CEILING Hanger No. 07C HILTI Kwik Bolt III / HILTI KwO, Bolt 11 Drilled Anchor Cut Rod Lgth Rounded to Nearest Inch Rod Coupling AU Thread Rod Swivel Ring 1 111 CL Pipe Concrete Construction Bottom of Concrete to Center Line of Pipe Note on Plan Note on Plan: Hanger Number and 'A' Dimension HANGER DETAIL NOT TO SCALE VICINITY MAP DETAIL NOT TO SCALE SYMBOL LEGEND REVISIONS Sprinkler Legend 2 -WAY EARTHQUAKE BRACE NO. DESCRIPTION DATE SYM. SIN QTY. K SPRAY ORIF. FIN. TEMP. MFR./MODEL 4 -WAY EARTHQUAKE BRACE HYDRAULIC REFERENCE POINT 1 R5415 14 5.6 Pendent Brass 155°F REL G4A CONCEALOR APPROVAL: City of Tukwila R3615 16 5.6 Pendent Chrome 155°F REL F1 FR SSP CONT. NO.: N/A Total = 30 DRAWN BY: CHRIS ISAAC HANGER SYMBOL BRANCHLINE RESTRAINT SPRK ON SHEET: SEE LEGEND SPRK. ON JOB: DATE: 07/21/08 Western States Fire Protection Company 7102 180th AVE NE, STE A-105- REDMOND, WA- 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY -OFFICES LOCATED ALBUQUERQUE /AUSTIN /DALLAS/ DECATUR ! DENVER f DULUTH I HOUSTON I KANSAS CITY LAS VEGAS / MINNEAPOLIS / PHOENIXI PORTLAND/RAPID CITY/ ST. PAULI SALT LAKE CITY/ SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 —S.277 JOURNEY'S 2477 Southcenter Pkwy Tukwila,WA 98188 JOURNEY'S - TI (1) z Ct 0 w z 0 CHRIS ISAAC GENESCO 0 0 IY 0 SHEET FP -1 OF 1