PP - 2600 SOUTHCENTER MALL FC-1 - JOHNNY ROCKETS - PERMITS AND PLANS
2600 SOUTHCENTER MALL FC -1 FOOD COURT ASSOCIATED PERMITS 08-F-180 08-S-160 14-H-021 08-H-267 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Johnny Rockets 2600 Southcenter Mall FC -01 Permit No.: 08-S-160 Date: May 5, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). FIRE DEPARTMENT HOOD SUPPRESSION PLAN REVIEW COMMENTS Project Name: Johny Rockets 2600 Southcenter Mall space FC -1 Permit No.: 08-H-267 Date: June 4, 2008 Reviewer: Steve Kohler Fire Protection Inspector/Plan Review (206)575-4407 • Nozzle heights above appliances to be per manufacturers installation guidelines. • Install splash guards between fryers and ranges/charbroilers. • Upon activation of the suppression system, the make-up air supply will shut off and the exhaust will keep running. • Type 1 hood systems shall be designed and installed to automatically activate the exhaust fan whenever cooking operations occur. The activation of the exhaust fan shall occur through an interlock with the cooking appliances, by means of heat sensors or by means of other approved methods. • Activation of the suppression system shall shunt all electrical power under the hood as well as the gas supply. • Install a "K" rated portable fire extinguisher within 30 ft. of the cooking equipment. • The hood suppression system shall be monitored by a U.L. Central Monitoring Station. Job Number: KS0334 Report Description: Ordinary Group II • • • • • F.. Job Number KS0334 Design Engineer Adam Kanter Job Name Johnny Rockets State Certification/License Number WESTESF136QF Address 1 2600 Southcentner Mall A11.1 City of Tukwila Address 2 Job Site Southcenter Mall City Tukwila State Wa Zip Code 98188 Drawing Name FP-1.cad Systen Most Demanding Sprialder Data 5.6 K -Factor 20.00 at 12.755 Occupancy Ordinary Group II Hose Allowance At Source 250.00 Density 0.20gpm/ft2 Area of Application 793.00ft2 (Actual 889.16ft2) Additional Hose Supplies Node Flow(gom) Total Hose Streams 250.00 System Flow Demand 288.73 Total Water Required (Including Hose Allowance) 538.73 Maximum Pressure Unbalance In Loops 0.000 Maximum Velocity Above Ground 16.33 between nodes 53 and 52 Maximum Velocity Under Ground 1.09 between nodes 1 and 268 Volume capacity of Wet Pipes 1930.11gal Volume capacity of Dry Pipes 1.36ft3 Number Of SprinIdars Calculated 13 Coverage Par Spnnider 1 00.00ft2 Node Hose Flow (gpm) Static (psi) Residual Flow (psi) (gpm) 250.00 140.000 20.000 1 10900.00 Available Total Demand (psi) (gpm) 139.540 _I 538.73 Required (psi) Safety Margin (psi) 52.021 87.518 Confractor Contractor Number KS0334 Contact Name Adam Kantner Contact Title Project Manager Contractor Name Western States Fire Protection Phone 425.881.0100 Extension Address 1 7102 180th Ave Ne, Suite A-105 FAX 485.736.9032 Address 2 City Redmond State WA Zip Code 98052 Web -Site © M. E P .CA D , Inc. 41 A utoS PRIN K® VR5 v5.2.6 04/24/2008 11:35:06AM • Page 1 Job Number: KS0334 Report Description. Ordinary Group II Device Actual Flow (gpm) Minimum Flow (gpm) K -Factor (K) Pressure (psi) Sprinkler 111 23.48 20.00 5.6 17.583 Sprinkler 112 23.50 20.00 5.6 17.610 Sprinkler 113 24.02 20.00 5.6 18.393 Sprinkler 103 20.57 20.00 5.6 13.498 Sprinkler 108 22.08 20.00 5.6 15.552 Sprinkler 104 20.63 20.00 5.6 13.572 Sprinkler 102 20.34 20.00 5.6 13.191 ==v Sprinkler 101 20.00 20.00 5.6 12.755 Sprinkler 110 23.37 20.00 5.6 17.411 Sprinkler 105 21.77 20.00 5.6 15.114 Sprinkler 109 22.53 20.00 5.6 16.193 Sprinkler 107 21.83 20.00 5.6 15.202 Sprinkler 114 24.60 20.00 5.6 19.290 '> Most Demanding Sprinkler Data © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 04/24/2008 11:35:12A M Page 2 Job Number: KS0334 Report Description: Ordinary Group II Node Elevation(Foot) Fittings Pressure(psi) Discharge(gpm) 17 15-11 15-11 P0(8-0) P0(5-0) 25.908 22.152 21 25 15-11 P0(5-0) 21.202 28 15-11 E(2-0) 20.946 42 18-11 P0(5-0) 16.612 46 18-11 P0(5-0) 15.076 49 18-11 P0(5-0) 14.719 51 18-11 2E(2-0) 14.622 52 15-11 P0(5-0) 19.821 53 15-11 P0(8-0) 25.915 72 15-11 P0(8-0) 25.982 74 15-11 P0(5-0) 21.714 79 18-11 P0(5-0) 18.909 80 18-11 P0(5-0) 18.800 84 18-11 P0(5-0) 18.433 100 15-11 P0(8-0) 26.127 106 18-11 P0(5-0) 24.052 138 18-5 2P0(26-4) 29.150 191 -15-11 P0(37-8%) 44.849 268 -13-11% BFP(-4.500) 48.572 302 -15-11 LtE(16-0) 44.886 111 10-01A Spr(-17.583) 17.583 23.48 112 7-0 Spr(-17.610) 17.610 23.50 113 12-0 Spr(-18.393) 18.393 24.02 103 7-0 Spr(-13.498) 13.498 20.57 108 12-0 Spr(-15.552) 15.552 22.08 104 12-0 Spr(-13.572) 13.572 20.63 102 10-0 Spr(-13.191) 13.191 20.34 101 10-0 Spr(-12.755) 12.755 20.00 110 12-0 Spr(-17.411) 17.411 23.37 105 12-0 Spr(-15.114) 15.114 21.77 109 10-0Y2 Spr(-16.193) 16.193 22.53 107 12-0 Spr(-15.202) 15.202 21.83 114 12-0 Spr(-19.290) 19.290 24.60 1 -21-10 S 52.021 288.73 dt, ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 04/24/2008 11:35:12A M Page 3 Job Number: KS0334 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Friction Loss Length Eq. Length Total Length Pressure Summary Downstream Upstream Elevation Discharge K -Factor Pt Pn Fittings Route 1 DR 1.049 Q=20.00 7.42 C=120 0.130131 36-04 Pf 5.733 101 10-0 q=20.00 K=5.6 12.755 Spr(-12.755) 8-0 Pe -3.866 51 18-11 14.622 4E(2-0) 44012 Pv BL 1.610 Q=20.00 3.15 C=120 0.016155 5-111: Pf 0.096 51 18-11 14.622 Pe 49 18-11 14.719 5-11'/2 Pv BL 1.610 Q=40.34 6.36 C=120 0.059156 6-012 Pf 0.357 49 18-11 14.719 Pe 46 18-11 15.076 6-0% Pv BL 1.610 Q=60.91 9.60 C=120 0.126802 12-112 Pf 1.536 46 18-11 15.076 Pe 42 18-11 16.612 12-112 Pv BL 1.610 Q=81.54 12.85 C=120 0.217510 4912 Pf 1.909 42 18-11 16.612 40 Pe 1.301 52 15-11 19.821 2LtE(2-0) 8-912 Pv BL 1.610 Q=103.63 16.33 C=120 0.338875 10-0 Pf 6.094 52 15-11 19.821 8-0 Pe 53 15-11 25.915 P0(8-0) 18-0 Pv CM 4.260 Q=174.63 3.93 C=120 0.007786 8-71/2 Pf 0.067 53 15-11 25.915 Pe 72 15-11 25.982 8-71/2 Pv CM 4.260 Q=264.13 5.95 C=120 0.016742 8-712 Pf 0.145 72 15-11 25.982 Pe 100 15-11 26.127 8-712 Pv CM 4.260 Q=288.73 6.50 C=120 0.019739 127-8 Pf 4.100 100 15-11 26.127 80-0% Pe -1.077 138 18-5 29.150 6fE(8-1112), P0(26-4) 207-8% Pv CM 6.357 Q=288.73 2.92 C=120 0.002810 133-10 Pf 0.818 138 18-5 29.150 157-2 Pe 14.881 191 -15-11 44.849 5fE(12-7), BV(12-7), CV(40-3), 291-0 Pv GV(3-912), PO(37-81/2) FM 8.329 Q=288.73 1.70 C=120 0.000754 16-512 Pf 0.037 191 -15-11 44.849 32-0 Pe 0.000 302 -15-11 44.886 fE(16-0), LtE(16-0) 48-51/2 Pv FM 10.420 Q=288.73 1.09 C=120 0.000253 28-21/2 Pf 4.528 302 -15-11 44.886 83-0 Pe -0.842 268 -13-111/2 48.572 4LtE(16-0), BV(19-0), BFP(-4.500) 111-212 Pv UG 10.400 Q=288.73 1.09 C=140 0.000192 110-2 Pf 0.043 268 -13-1112 48.572 111-7 Pe 3.407 1 -21-10 52.021 E(35-1), 3LtE(25-6), S 221-912 Pv so Route 2 DR 1.049 Q=20.34 7.55 C=120 0.134241 31-21/2 Pf 5.397 102 10-0 q=20.34 K=5.6 13.191 Spr(-13.191) 9-0 Pe -3.869 49 18-11 14.719 2E(2-0), P0(5-0) 40-212 Pv sr Route 3 DR 1.049 Q=20.57 7.64 C=120 0.137126 38-11/2 Pf 6.739 103 7-0 q=20.57 K=5.6 13.498 Spr(-13.498) 11-0 Pe -5.161 46 18-11 15.076 3E(2-0), PO(5-0) 49-11/2 Pv = Route 4 DR 1.049 Q=20.63 7.66 C=120 0.137820 32-91/2 Pf 6.033 104 12-0 q=20.63 K=5.6 13.572 Spr(-13.572) 11-0 Pe -2.993 42 18-11 16.612 3E(2-0), P0(5-0) 43-912 Pv eaw Route 5 DR 1.049 Q=21.77 8.08 C=120 0.152245 32-10% Pf 6.679 105 12-0 q=21.77 K=5.6 15.114 Spr(-15.114) 11-0 Pe -2.993 80 18-11 18.800 3E(2-0), PO(5-0) 43-10'/2 Pv BL 1.610 Q=44.31 6.98 C=120 0.070366 1-61/2 Pf 0.110 80 18-11 18.800 Pe 79 18-11 18.909 1-612 Pv BL 1.610 Q=66.14 10.42 C=120 0.147661 6-2 Pf 1.504 79 18-11 18.909 4-0 Pe 1.301 74 15-11 21.714 2LtE(2-0) 10-2 Pv BL 1.610 Q=89.51 14.11 C=120 0.258428 8-6 Pf 4.269 74 15-11 21.714 8-0 Pe 72 15-11 25.982 P0(8-0) 16-6 Pv sik Route 6 DR 1.049 Q=21.83 8.11 C=120 0.153063 34912 Pf 6.701 107 12-0 q=21.83 K=5.6 15.202 Spr(-15.202) 9-0 Pe -2.993 79 18-11 18.909 2E(2-0), P0(5-0) 43-912 Pv Route 7 fit, ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 04/24/2008 11:35:13A M Page 4 41 Job Number: KS0334 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Friction Loss Length Eq. Length Total Length Pressure Summary Downstream Elevation Discharge Upstream K -Factor Pt Pn Fittings DR 1.049 Q=22.08 8.20 C=120 0.156323 29-2 9-0 38-2 Pf 5.967 Pe -1.698 Pv 108 12-0 q=22.08 52 15-11 K=5.6 15.552 19.821 Spr(-15.552) 2E(2-0), PO(5-0) Route 8 DR 1.049 Q=22.53 8.37 C=120 0.162278 30-6Y2 7-0 37-6Y2 Pf 6.091 Pe -3.851 Pv 109 10-0Y: q=22.53 84 18-11 K=5.6 16.193 18.433 Spr(-16.193) E(2-0), PO(5-0) BL 1.610 Q=22.53 3.55 C=120 0.020146 18-21A 18-21A Pf 0.367 Pe Pv 84 18-11 80 18-11 18.433 18.800 = Route 9 DR 1.049 Q=23.37 8.67 C=120 0.173530 27-6'/z 7-0 34-6% Pf 5.996 Pe -1.693 Pv 110 12-0 q=23.37 74 15-11 K=5.6 17.411 21.714 Spr(-17.411) E(2-0), PO(5-0) Route 10 DR 1.049 Q=23.48 8.72 C=120 0.175119 29-10 4-0 33-10 Pf 5.923 Pe -2.560 Pv 111 10-0% q=23.48 28 15-11 K=5.6 17.583 20.946 Spr(-17.583) 2E(2-0) BL 1.610 Q=23.48 3.70 C=120 0.021740 11-91/� 11-9V2 Pf 0.256 Pe -0.000 Pv 28 15-11 25 15-11 20.946 21.202 BL 1.610 Q=46.98 7.40 C=120 0.078431 12-1% 12-1 Yz Pf 0.950 Pe -0.000 Pv 25 15-11 21 15-11 21.202 22.152 BL 1.610 Q=71.00 11.19 C=120 0.168356 14-4 8-0 22-4 Pf 3.757 Pe Pv 21 15-11 17 15-11 22.152 25.908 P0(8-0) CM 4.260 Q=71.00 1.60 C=120 0.001473 4-9% 4-9Y: Pf 0.007 Pe Pv 17 15-11 53 15-11 25.908 25.915 (as. Route 11 DR 1.049 Q=23.50 8.72 C=120 0.175373 33-6 9-0 42-6 Pf 7.452 Pe -3.860 Pv 112 7-0 q=23.50 25 15-11 K=5.6 17.610 21.202 Spr(-17.610) 2E(2-0), PO(5-0) .sr Route 12 DR 1.049 Q=24.02 8.92 C=120 0.182572 24-11 5-0 29-11 Pf 5.460 Pe -1.702 Pv 113 12-0 q=24.02 21 15-11 K=5.6 18.393 22.152 Spr(-18.393) P0(5-0) Route 13 DR 1.049 Q=24.60 9.13 C=120 0.190790 31-8 9-0 40-8 Pf 7.755 Pe -2.993 Pv 114 12-0 q=24.60 106 18-11 K=5.6 19.290 24.052 Spr(-19.290) 2E(2-0), PO(5-0) BL 1.610 Q=24.60 3.88 C=120 0.023686 20-8Yz 12-0 32-8Yz Pf 0.774 Pe 1.301 Pv 106 18-11 100 15-11 24.052 26.127 2LtE(2-0), PO(8-0) .0400.teflx . e L45iA 'Ai)..„: €t ` s' :W3`2{Y l:':' >1 a1us( :IFllult'`tier >< > > Actual Inside Diameter 4.87 = Factor Value Of C 100 Multiplying Factor 0.713 130 140 150 1.16 1.33 1.51 Schedule 40 Steel Pipe Inside Diameter / (dam © M.E.P.CAD, Inc. AutoSPRINKO VR5 v5.2.6 04/24/2008 11:35:13A M Page 5 Job Number: KS0334 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Friction Loss Downstream Upstream Elevation Discharge K -Factor Pt Pn Fittings Length Eq. Length Total Length Pressure Summary AO BL CM DN DR DY FM FR MS OR RN SP ST UG .........Y[?ete�er ................. �e ......................... Arm -Over Branch Line Cross Main Drain Drop Dynamic Feed Main Feed Riser Miscellaneous Outrigger Riser Nipple Sprig Stand Pipe Underground Diameter Elevation Flow Discharge Velocity Pressure Length Friction Loss HWC Pt Pn Pf Pe Pv Inch Foot gpm gpm fps psi Foot psi/Foot Hazen -Williams Constant Total pressure at a point in a pipe Normal pressure at a point in a pipe Pressure loss due to friction between points Pressure due to elevation difference between indicated points Velocity pressure at a point in a pipe ALV Alarm Valve AngV Angle Valve b Bushing BalV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Turn 90° cplg Coupling Cr Cross Run CV Check Valve DeIV Deluge Valve DPV Dry Pipe Valve E 90° Elbow EE 45° Elbow Eel 11%* Elbow Ee2 22W Elbow f Flow Device FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow flg Flange FN Floating Node ft' FireLock(TM) Tee g Gauge GIoV Globe Valve GV Gate Valve Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PrV Pressure Relief Valve PRV Pressure Reducing Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap (DA © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 04/24/2008 11:35:13A M Page 6 il :.... P..:: Job Number KS033, Report Description: Ordinary Group 1 Supply at Node 1 1 C Pressure, psi w3 0, W A O N p p Ncr.IIIIIII1t11111111111111,111111111111111111111111111111111I11111111111„11131111111111111„(C,I Static Pressure 140.000 „538.73 288.73 with hose @ 52.021 streams S /stem demand curve 10900.00 @ 20,000 Iriniiiltlll 111111111 111111 I l l 1 1 1 1 1 1 t H 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 111111111 v 910022W 3300 4400 5500 6600 7700 8800 9900 11000 Water flow, gpm Hydraulic Graph Supply at Node 1 Static Pressure 140.000 Residual Pressure 10900.00 @ 20.000 Available PressureTene of Test 139.540 @ 538.73 System Demand 288.73 @ 52.021 System Demand (Including Hose Allowance) 538.73 @ 52.021 DI, ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 04/24/2008 11:35:14AM Page 7 Job Number: KS0334 Report Description: Ordinary Group 11 M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 04/24/2008 11: 35:15A M Page 8 I G 1 -J O©® -I1 1 ��— 1 w �J' 0 I 1 113 v: pmpA CIO Z N I kr, cgm ig Received Time May, 28. 9:54AM I;J #111 11 11 m 9NIdId O13I4 DNIJId A21O13V4 - THIS FIRE SYSTEM COMPLIES WITH U.L. 300 REQUIREMENTS 1 Nm 1 1 1 1 1 I Z -'1*-.XXO IO'1 -1 a'I.-.aarrlrr�►� m rir x >omr y a o$a xn<a Z .ZI x aa.r DZ < ZZ-1Z2 to maNwrl m dmr rS,.rom mx ZrzNp0 mc1n5rloa myXPIo2coPati y Oia x 0 ZQ� tri -IO 312M d_Q e_IMO r= 0o arZnZZ Z=-1< 711:$ xmo r -a1 Z oo1 zr rtA m -Im3 viy ciz3.�D r -D td X Or Oy X.-.-. 1 In rl mA� Cb rriMZO n DMZ ry dN -riOr 0 -iOrl x In minx 0 0 ly 7:1201WW _o.<,0070 rp0L 066a **3 o -Z 63 C1 --VTG O Z N mOm- -9 a N''`ca MZ ay rr 71-4 re axt zr, �i 70 ym y Nrl 3311d21f1S ONI)1003 3H1 00 0 _ 1 Noun Duct PPln"r' o 1 1 1 1 1 I Z -'1*-.XXO IO'1 -1 a'I.-.aarrlrr�►� m rir x >omr y a o$a xn<a Z .ZI x aa.r DZ < ZZ-1Z2 to maNwrl m dmr rS,.rom mx ZrzNp0 mc1n5rloa myXPIo2coPati y Oia x 0 ZQ� tri -IO 312M d_Q e_IMO r= 0o arZnZZ Z=-1< 711:$ xmo r -a1 Z oo1 zr rtA m -Im3 viy ciz3.�D r -D td X Or Oy X.-.-. 1 In rl mA� Cb rriMZO n DMZ ry dN -riOr 0 -iOrl x In minx 0 0 ly 7:1201WW _o.<,0070 rp0L 066a **3 o -Z 63 C1 --VTG O Z N mOm- -9 a N''`ca MZ ay rr 71-4 re axt zr, �i 70 ym y Nrl 3311d21f1S ONI)1003 3H1 iv • vV �lJ Nola - Fire Systems - Parts List Report Fire System Parts List Job # 702814 - Johnny Rockets - Tukwila WA Location: Tukwila, WA Fire System # 1 Ansul R102 Hoods Covered: Hood # 1 Gas Valve(s) : ANSUL-3.0/1.5 Tag: 50 Page: 4 5/19/08 1:51 PM Supplied by Ship =Item CAS # Vendor # Description Dist CAS Inst Loose 1 1 AT - 1.5 AT - 1.5 TANK(#1A) - 1.5 Gallon SS Tank (for use with Automan 0 1 Release, Actuator, or SS Enclosure (UL)) 1 1 AT - 3.0 AT - 3.0 TANK(#1 B) - 3.0 Gallon SS Tank (for use with Automan Release, Actuator, or SS Enclosure (UL)) 0 1 1 3 ANS -OEM ANS -OEM REGULATED RELEASE - Ansul Regulated Mechanical Release/Bracket Assembly, OEM, R-102 0 1 1 5 LIQ -3.0 79372 AGENT -Ansulex Low PH Wet Chemical Agent, 3 1 0 Gallon (UL) 1 6 LIQ -1.5 79694 AGENT -Ansulex Low PH Wet Chemical Agent, 1.5 Gallon (UL) 1 0 1 9 101-30 101-30 CARTRIDGE - Carbon Dioxide, 101-30, Double Tank Cartridge (R-102) 1 0 1 10 TLINK TLINK LINK - Test Link Package 1 0 1 11 MICRO -SD MICRO -SD MICROSWITCH -Single Dual Electric Switch 0 1 1 12 HOSE 79007 HOSE - Rubber Hose 0 1 1 13 419337 419337 NOZZLE - 2W Nozzle, Duct 0 1 5 16 419335 419335 NOZZLE - 1N Nozzle, Plenum/Appliance 0 5 2 19 419338 419338 NOZZLE - 3N Nozzle, Appliance 0 2 3 25 418569 418569 NOZZLE ADAPTOR - Swivel Nozzle Adaptor 0 3 8 26 QSA-3/8 QSA-3/8 QUIK SEAL - 3/8" (UL) 0 8 1 27 QPSA-1/2 QPSA-1/2 PULLEY SEAL -1/2" Hood Seal (UL) 0 1 4 28 S -DET S -DET DETECTOR - Series (Scissor Linkage) 0 4 2 29 ANS-360FL ANS-360FL FUSIBLE LINK - 360deg F, R-102 and PIRANHA 0 2 2 30 ANS-500FL ANS-500FL FUSIBLE LINK - 500deg F, R-102 and PIRANHA 0 2 1 34 RPS -A RPS -A REMOTE PULL STATION -Aluminum (without wire 0 1 rope) 2 35 PE -LT PE -LT PULLEY ELBOW - Low Temp. Pulley Elbow, Set 0 2 Screw Type 1 36 PE -HT PE -HT PULLEY ELBOW - High Temp Pulley Elbow, 0 1 Compression Type 5 41 SN -CHAR SN -CHAR SINGLE NOZZLE EXTENDED DROP ASSY 0 5 http://appl.captiveaire.com/Order/FireSystems/PartsListReport.aspx?JobFireSystemld=145287 Page 1 of 2 Received Time May. 28. 9:54AM 1 r..._1 . L. %I -L t.. a CJ 1 1 S Page: 7 Received Time May, 28. 9:54AM SECTION IV — SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-28 REV. 5 4-1-06 Nozzle Application Chart The following chart has been developed to assist in calculating the quantity and type of nozzle required to protect each duct, plenum, or appliance. NOTICE This chart is for general reference only. See complete details for each type of hazard. Hazard ► Duct or Transition (Single Nozzle) Duct or Transition (Single Nozzle) Duct or Transition (Dual Nozzle) Electrostatic Precipitator (At Base of Duct) Plenum (Horizontal Protection) ► Plenum (Horizontal Protection) Plenum (Vertical Protection) ► Fryer (Split or Non -Split Vat) Fryer (Split or Non -Split Vat) Fryer (Split or Non -Split Vat)* Fryer (Non -Split Vat Only) Maximum Hazard Dimensions Minimum Nozzle_ Nozzle Quantity Heights Length — Unlimited 1 Perimeter — 50 in. (127 cm) Diameter —16 in. (40.6 cm) Length — Unlimited Perimeter —100 in. (254 cm) Diameter —31 7/8 in. (81 cm) Length — Unlimited Perimeter —150 in. (381 cm) Diameter — 48 in. (122 cm) Individual Cell Length —10 ft. (3.1 m) Length — 6 ft. (1.8 m) Width — 4 ft. (1.2 m) Length — 4 ft. (1.2 m) Width — 4 ft. (1.2 m) Maximum Size (without drip board) 14 in. (36 cm) x 15 in. (38 cm) Low Proximity Maximum Size (without drip board) 141/2 in. (37 cm) x 14 in. (36 cm) Medium Proximity Maximum Size (without drip board) 15 in. (38 cm) x 14 in. (36 cm) High Proximity Medium Proximity Maximum Size (without drip board) 19 1/2 in. (49.5 cm) x 19 in. (48.2 cm) High Proximity Low Proximity Maximum Size (without drip board) 18 in. (45.7 cm) x 18 in. (45.7 cm) High Proximity 1 2 1 1 1 1 1 1 1 1 1 1 For multiple nozzle protection of single fryers, see detailed information on Pages 4-12 through 4-14. 13-16 in. (33 — 41 cm) 16 — 27 in. (41 - 69 cm) 27 — 47 in. 20 — 27 in. 21 — 34 in. 13-16 in. 25 — 35 in. (64-89 cm) Nozzle Part No. 430912 419337 419337 419334 419335 430192 419336 419336 419342 419342 419339 419340 419338 419342 419338 Nozzle Tip Stamping — Flow No. 1W 2W 2W 1 /2N 1N 1W 1W 1W 290 290 230 245 3N 290 3N Nozzle Application Chart (Continued) Hazard Fryer (Non -Split Vat Only)' Fryer (Split or Non -Split Vat) Fryer (Split or Non -Split Vat) Range Maximum Hazard Dimensions Maximum Size (with drip board) 21 in. (53 cm) x 14 in. (36 cm) (Fry Pot must not exceed 15in. x14in. (38 cm x 36 crn)) High Proximity Medium Proximity Maximum Size (with.drip board) 25 3/8 in. (64.4 cm) x 19 1/2 in: (49.5 cm) (Fry pot side must not exceed 19 1/2 in. (49.5 cm) x 19 in. (48.2 cm) High Proximity. Low Proximity Maximum Size (with drip board) 18 in. (45.7 cm) x 27 3/4 in. (70.5 cm) High Proximity Minimum Nozzle Quantity 1 1 Maximum Size (with drip board) 14in.(36cm)x 21 in. (53 cm) 1 Low Proximity Maximum Size (with drip board) 141 /2 in. (37 cm) x 261/2 in. (67 cm) 1 Medium Proximity Longest Side 32 in. (81 crn) Area — 384 sq. in. (2477 sq. cm) Longest Side 28 in. (71 cm) Area — 336 sq. in. (2168 sq. cm) Longest Side (High Proximity) 1 28 in. (71 cm) Area — 672 sq. in. (4335 sq. cm) Longest Side (Medium Proximity) 32 in. (81 cm) Area — 768 sq. in. (4955 sq. cm) Longest Side (Low Proximity) 2 36 in. (91 cm) Area —1008 sq. in. (6503 sq. cm) For multiple nozzle protection of single fryers, see detailed information on Pages 4-7 through 4-11. SECTION IV — SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-29 4-1-06 REV_ s Nozzle -Heights. 27 — 47 in. 20 - 27 in. 21 —34 in. 13-16 in. 25 — 35 in. (64-89 cm) 13-16 in. (33 — 41 cm) 16-27 in. (41 — 69 cm) 30 —40 in. (76 -102 cm) 40 — 48 in. (102 -122 cm) (With Bookshelf) 40 — 50 in. (102-127 cm 30 — 40 in. (76 — 102 cm) 15 — 20 in. (38 — 51 cm) Nozzle Part No. 419339 419340 419338 419342 419338 419342 419342 419335 419333 419340 419341 419342 Nozzle Tip Stamping — Flow No. 230 245 3N 290 3N 290 290 1N 1F 245 260 290 SECTION IV – SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-30 REV. 3 10-1-02 Nozzle Application Chart (Continued) Hazard Griddle Chain Broiler* (Overhead Protection) Chain Broiler (Horizontal Protection) Gas -Radiant Char -Broiler Electric Char -Broiler Lava -Rock Broiler Natural Charcoal Broiler Lava -Rock or Natural Charcoal Char -Broiler Minimum Maximum Hazard Nozzle Dimensions Quantity Longest Side (High Proximity) 1 48 in. (122 cm) Area –1440 sq. in. (9290 sq. cm) Longest Side (High Proximity) 1 30 in. (76 cm) Area – 720 sq. in. (4645 sq. cm) Longest Side (High Proximity) 1 36 in. (91 cm) Area –1080 sq. in. (6968 sq. cm) Longest Side 1 (Medium Proximity) 48 in. (122 cm) Area –1440 sq. in. (9290 sq. cm) Longest Side (Low Proximity) 1 48 in. (122 cm) Area – 1440 sq. in. (9290 sq. cm) Longest Side – 34 in. (86 cm) 2 Area – 1088 sq. in. (7019 sq. cm) Length – 43 in. (109 cm) 2 Width – 31 in. (79 cm) Longest Side – 36 in. (91 cm) 1 Area – 864 sq. in. (5574 sq. cm) Longest Side – 34 in. (86 cm) 1 Area – 680 sq. in. (4383 sq. cm) Longest Side – 24 in. (61 cm) 1 Area – 312 sq. in. (2013 sq. cm) Longest Side – 24 in. (61 cm) 1 Area – 288 sq. in. (1858 sq. cm) Longest Side – 30 in. (76 cm) 1 Area – 720 sq. in. (4645 sq. cm) Nozzle Heights 30 – 50 in. (76 – 127 cm) (perimeter located) 30 – 50 in. (76 – 127 cm) (center located) 35 — 40 in. (89 – 102 cm) (perimeter located) 20 – 30 in. (51 – 76 cm) (perimeter located) 10 – 20 in. (25 – 51 cm) (perimeter located) 10 – 26 in. (25 – 66 cm) 1 – 3 in. (3 – 8 cm) 15 –40 in. (38 –102 cm) 20 – 50 in. (51 – 127 cm) 18 – 35 in. (46 – 89 cm) 18 – 40 in. (46 – 102 cm) 14 – 40 in. (36 –102 cm) Minimum chain broiler exhaust opening —12 in. x 12 in. (31 cm x 31 cm), and not less than 60% of internal broiler size. Nozzle Part No. 419341 Nozzle Tip Stamping – Flow No. 260 419342 290 419335/417332 1N/1NSS 419342 290 419343 419336/417333 419335/417332 419335/417332 419335/417332 419335/417332 419335/417332 419338 2120 1 W/1 WSS 1N/1NSS 1N/1NSS 1N/1NSS 1N/1NSS 1N/1NSS 3N v,vIMIV I-Segutaiea M9Crlanicai rseiease Assembly (3.0 gallon — Part No. 79290 or 1.5 gallon — Pan No. 79291) contains the regulated release mechanism, agent tank, expellant gas hose for agent tank hookup. and enclosure knockouts to facilitate installing actuation, piping; expellant piping; detection system; and additional equipment. This regu- lated release assembly is used in single, double. and multiple - tank systems and must- be mounted to a rigid -surface. The release mechanism can be used to interconnect both the actu- ation and expellant gas lines as required per system design. The regulator is designed to allow a constant flow of gas into the tank at 100 psi (690 kPa) when the system is actuated. In single. double, and multiple -tank systems, the provided expel- lant gas hose connects the agent tank to the bottom outlet of the regulator. In double and multiple -tank system configurations, the back outlet of the regulator is used as an expellant gas feed for one additional tank -enclosure or tank -bracket hookup. The enclosure contains the required knockouts to facilitate this con- nection. If a pressure switch is to be attached to the regulator, additional fittings are required. • - The tank is mounted within the enclosure. The tank contains an adaptor/tube assembly with a burst disc union. The burst disc helps prevent siphoning of the agent up the pipe due to signifi- cant temperature fluctuations in the area where the tank .is located. The tank is mild steel and, under normal conditions, requires hydrostatic testing .every twelve years. - The agent tank is shipped uncharged and must be filled with 1.53 gallons (5.8 L) or 3.06 gallons (11.6 L) of only ANSULEX Low pH Liquid Fire Suppressant during installation. The detection and additional equipment required per system design are connected tothe release mechanism. The enclosure contains knockouts to facilitate detection and additional hookups. The system can b actuated automatically or manually. Auto- - matic actuation occurs when a fusible link within the detection system separates in a fire condition. Manual actuation of the system occurs when personnel pull on the remote manual pull station pull rine. EXTINGUISHING AGENT ANSULEX Low pH Liquid Fire Suppressant (1:5 gallon — Part No. 79694 or 3.0 gallon — Par No. 79372) is a potassium -based solution designed for fast knock -down and suppression of grease -related fires. The agent is shipped in plastic containers which provide one complete tank charge. Agent storage life expectancy is twelve years. The distributor must record the batch numbers and date of shipment receipt to be filed with each instal- lation record. NIL Total Tank Type of Flow No.* Quantity System r Type of Hardware 1-5 1 Single 1.5 Gal. Reg. Release 6-11 1 Single - 3.0 Gal. Reg. Release ELECTRICAL SWITCHES - LOG°tra It3 Eprcl{ F Uto_ The electrical switches are intended for use with. electric gas valves, alarms, contactors, lights, contractor supplied electric power shut-off devices :and other electrical devices that are designed to shut off or tum on when the system is actuated. Switches are available in kits: One Switch Kit, Part No. 423878, Two Switch Kit, Part No. 423879; Three Switch . Kit, Part No. 423880, and Four Switch Kit, Part No. 423881. Each switch has a set of single -pole, double=throw contacts rated of 21 amp, 1 HP, 125, 250, 277 VAC or 2 HP, 250, 277 VAC. Mounting hardware is provided with each kit. R-102 RESTAURANT • FIRE SUPPRESSION SYSTEM (Standard UL 300 Listed) Nozzle Identification Chart Nozzle Nozzle. Nozzle Tvoe Part No. Sta monoino 1W Nozzle 419336 1W 1WSS Nozzle 417333 1W 1N Nozzle 419335 1N 1NSS Nozzle 417332 1N 1/2N Nozzle 419334 1/2N 3N Nozzle 419338 3N 2W Nozzle 419337 2W 2WH Nozzle 78078 2WH Noz Flov 1 1 1 1 1/2 3 2 2 230 Nozzle 419339 230 2 245 -Nozzle 419340 245 2 260 Nozzle 419341 260 2 290 Nozzle 419342 290 2 2120 Nozzle 419343 2120 2 1F Nozzle 419333 1F 1 I(oo Mflzzl.t: 4S07IZ (MD Nitrogen Cartridge Reauired LT -20-R (7032) LT -30-R (5373) Kf(6—, + 5ri)1S oi\\ S' fL1 kik Sr T5 D uW:rO PT K-rr5-01 SicINAL Carbon Dioxide Cartridoe Reauired 101-10 (15850) 101-20 (17492) X31)5'W1-- tS S SECTION IX - APPENDIX UL EX. 3470 ULC CEx747 Page 9-1 7-1-98 REV. 3 SYSTEM SELECTION GUIDE ' NOTE: System options do not cover all conceivable variations. They are listed here as a general guideline to show the most common type arrangement for multiple systems, Based on certain system designs utilizing manifolding, non-manifolding, 3 -tank systems, etc., other tank/cartridge combinations can be designed. The combinations below are based on 11 flow, 3.0 gallon tanks and 5 flow, 1.5 gallon tanks. More competitive designs may be available by utilizing 12 flow and 6 flow systems when appropriate. • Total Tank Type of Nitrogen Flow No. Quantity System Type of Hardware Carbon Dioxide Cartridge Required Cartridge Re o uirPd 1-5 1 Single 1.5 Gal. Reg. Release LT -20-R(7032) ) 101-10 (15850) 6-11 1 Single 3.0 Gal. Reg- Release LT -30-R(5373) ) 101-20 (17492) 12-16 2 Double 1.5 Gal. Reg. Release Double(73022) 101 30(15851) 3.0 Gal: Additional Tank ( 17-22 23-27 28-33 28-33 (Optional) 34-38 39-44 45-49 50-55 56-60 61-66 2 3 3 4 4 5 5 6 Double Multiple Multiple Multiple Multiple 3.0 Gal. Reg. Release 3.0 Gal. Additional Tank 1.5 Gal. Reg. Release 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 3.0 Gal. Reg. Release 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 3.0 Gal. Reg. Release (2) 3.0 Gal. Additional Tanks 1.5 Gal. Reg. Release • 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank Multiple 3.0 Gal. Reg. Release • 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank Multiple 1.5 Gal. Reg. Release 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank Multiple 3.0 Gal. Reg. Release 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank Multiple 1.5 Gal. Reg. Release 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tarek 3.0 Gal. Reg. Actuator' 3.0 Gal. Additional Tank 6 Multiple 3.0 Gal. Reg. Release 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank Based on 5 flow numbers for a 1.5 gal. system and 11 flow numbers for a 3.0 gal. system. See Pages 4-39 - 4-42 for exceptions. If tanks are mandolded, only a -double tank" nitrogen cartridge (Part No. 73022) can be used. "- If tanks are manifolded, either an LT -A-101-30 nitrogen cartridge (Part No. 29187) or a double tank cartridge (Part No. 73022) can be used. Double (73022) 101-30 (15851)" LT -20-.R (7032) 101-10 (15850) LT -A-101.30 (29187) 101-30 (15851)"' LT -30-R (5373) 101-20 (17492) LT -A-101-30 (29187) 101-30 (15851)' Double (73022) N/A Double (73022) 101-30 (15851) LT -A-101-30 (29187) 101-30 (15851r - Double (73022) 101-30 (15851)" LT -A-101-30 (29187) 101-30 (15851)"` LT -20-R (7032) LT -A-101-30 (29187) LT -A-101-30 (29187) LT -30-R (5373) LT -A-101-30 (29187) LT -A-101-30 (29187) Double (73022) LT -A-101-30 (29187) LT -A-101-30 (29187) Double (73022) LT -A-101-30 (29187) LT -A-101-30 (29187) 101-10(15850) 101-30 (15851r- 101-30 (15851r 15851r- 101-30(15851) 101-20 (17492) 101-30 (15851)- 101-30 (15851)*_ 101-30 (15851) 101-30 (15851)"* 101-30 (15851)*** 101-30 (15851)** 101-30 (15851)"* 101-30 (15851)"' ACCEPTED Without Comments ❑, As Noted In Red Per The Attached Letter i nese plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is subie t to errors and omissions which do not authorize violations of adopted standards and oroinances. The responsibility for the . adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings atter this date will void this.acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to fietd test and inspection by The Tukwila Fire. Prevention Bureau. Date: By: SKe700 I UKWILA FIRE. UENArc I ►vrr.►5r �. Please call: 575-4407 and give this job No. ef3 7 and exact address for shut. -inwn or restoration approval. NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. rattrrIT stc:',." • •1"itaitommi SHEET NUMBER SHEET TITLE SHEET INDEX FA -01 SYSTEM INFORMATION FA -02 TYPICAL DETAILS - WRING AND MOUNTING FA -03 FRE ALARM SYSTEM FLOOR PLAN FA -04 SYSTEM CALCULATIONS (GENEAL), RISER, SITE PLAN oar-aaa.a.aaaaa.a=aasaaamaaaraaa.aaaaa.a.aaaaa=aaaaaaaaaaaaaaaaa-aanaaaaaaaaaan eirif-r,.;r5T717,11[) 'q••41P' k4tSty Without Comments As Acted In Red Per The Attached Letter i nee plsnE. have been r' ;'d by Thr..; Tukwila Fire Previ.•••ntioni3u1ti .lr f....C.ei*:.,; .f...:•;1' 1'.:•;"! current city 1-:•••-...%:,.•-•J•,..,r-.:: 1. '..;...;3,..r..;:;.•:;, 1,0 *,:ft FOCti and i',;1"ni••••;:'..ie..:iciF.., sml-i•••••••;:i oc 1.'...;;I': ji,",i.ii:.tti...";.:: -:t:tIS of adopted I, • • •! t.,...,r;•:-.i:•ii.:1....!......-ui ,..•• !;0....ic,...:•••:•.-.„ i • ••.,. i • . .'.'i„.311,Sib,!.ty for the 1•••;.: '1•••;1';'...t.":-:•' '-:.;',..si-,•.• •',; i i;:' • ,.. ii •;,-;;Iy. ", .11. rlf,:•: (it.---,••....lgner. .!,;,;:;•:-.!...-.::;::.•:-:.,-.), d• ‘;'....; •:;:., •••,1:.......•:: ..:, .,-0...•(.:;::;(.z;+..Yings atter I.: !,i)1.. d..i•r::::- ,,,I,',': ,:....0 ii!...:.•;,... ..-..c.., ...,,;(:.: !-;.,';::i v!iii r.equire a •,;!,,.....y.:,!_11.;i.i.11.'.l.-.; Qr i..,-.:,;•::: ..-...', t.'..1...:.'!.'Y.1.,, f‘.:;1 ''...Elellt approval. nL-..1r:c.c•-:,....!...;-,-.:.:;, i:•• .i.....':-..;:•.1 i.i...) ficid test and inspection by U.,,k,ic... l'A L.'. CI •-•11,:..t1111C.:11 LAI; •..:CIU. Date: 5 6\--0 By: LmwILA FIRE DEPARTIVIE11 Hease call: 575-440Z and give this job and exact address for shut dk,wn or restoration approvair NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATION SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE • COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 ' FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO , #16 FPL/FPLR RED (JACKET), S STROBE CIRCUIT - FEED TWISTED PAIR. W/ SHIELD #12 FPL/FPLR RED (JACKET) 2S STROBE CIRCUIT - RETURN TWISTED PAIR \d/ SHIELD , #12 • FPL/FPLR ' RED (JACKET) '1 A ANNUNCIATOR TWISTED PAIR W/ SHIELD 1416 FPL/FPLR RED (JACKET) • V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) 2V SPEAKER CIRCUIT - RETURN TWISTED PAIR s 1414 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO 1418 FPL/FPLR RED (JACKET) X LOW LEVEL AUDIO TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED MB FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART - . • . - . NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600v 1112 AWG THHN/THWN .244 0.D. .0467 , TWO 600V 1114 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM , THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 'SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C. CHP. 9. TABLE 4. SHIELDED WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END GENERAL NOTES FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLEjNITIATING DEVICES UNTIL PREPGRAMMED WITH 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS. DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 'I 2. DETECTOR AND AUDIBLE CIRCUIT I-',OLARITY SHALL BE OBSERVED. I 3. AUDIBLE/VISUAL CIRCUIT WIRING IOUPERVISEO, NO PARALLEL BRANCHING IS PERMISSIBLE J,'11: 4. INSTALLATION SHALL BE IN STRICTHONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL' CODE(S) AND/OR AUTHORITY! HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONbUlfl WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBEIROS DIVISION. SYMBOLS LEGEND DEVICES ADDRESS. !i• • ., 6. DETECTORS SHALL NOT BE MOUNTLb IbIRECT AIR STREAM OF AIR SUPPLY OUTLOS. PER NFPA 72 2-3.5.1 •,. 7. WIRING SHALL BE PER PLAN WITHHRESPEbT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE,1L CONDUCTORS SHALL BE PERMANENTLY, • AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. , • : • • 8. INSTALLING CONTRACTOR SHALL RETURN .ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES I • „ 9. FOR ADDITIONAL INSTALLATION INS:1)R, OCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTROCTIONS. 10. THE 120vac POWER ELECTRICAL WR 'SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 ANIQ1. 760 OF, NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120voc POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE AL/6W 'TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPpEl). CEILING; WHICHEVER IS LESS. - 4 . 12. ALL MANUAL PULL STATIONS SHAW BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. I 13. ALL PANEL NUMBERS AND CIRCUITS ,WILL BE ON THE RECORD DRAWINGS SET. !!i!! 14. ALL 120VAC CIRCUITS ARE FROM IVICATED CIRCUITS !FROM THE EMERGENCY GENERATOR: 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF, ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE! AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. • DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAR-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS EOM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE'', WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT:CIRCUITS. • • .2 • 17. ALL WIRING SHALL BE METERED; VERIFIED TO BE CONTINUOUS, FREE, OF GROUND AND FREE OF SHORTS BETWEEN ONDUC.TORS 'AND OTHER CIRCUITS. PRIOR TO • FINAL EQUIPMb\IT :TRIM.: • . , ALL CABLES SHALL BE MARKED A,'INDICATEO, ON FIRE ALARM. RISER WITH A PERMANENT LABEL" AT ALL DEVICES, JUNCTION BOXES AND FACP. • 19 THE ELECTRICAL CONTRACTOR SHALL CLEAN :'•ALL DIRT AND DEBRIS FROM THE . , • OUTSIDE AND INSIDE OF THE FIRE.- ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. • • 20. DETECTORS MUST 'BE RATED -FOR.JEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. . .•. „ •• •. •• • 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTIROL, UNIT, !RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOINA ANO RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN 4 :T4 SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE,, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF ' 6.4.2.2.2 IS TO PROVIDE ADEQUATE. SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. ,THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) 'WHERE THE CABLE IS INSTALLED • QUANTITY 1 1 1 1 - 7 - SYMBOL ; DESCRIPTION MODEL MANUFACTURER BACKBOX. MOUNTING HEIGHT • • •, ; FIRE ALARM x! CONTROL PANEL FACP XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP ! FIRE ALARM FARA , REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS' . , REMOTE BOOSTER E) POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP •;•;,; • ).11 INTERFACE MODULE HTRI-R : SIEMENS WITH RELAY ,• " • 4S DEEP VERIFY IN FIELD , 1111;111.11; ' DUAL• INPUT • INTERFACE MODULE HTRI-D SIEMENS 4S DEEP ; VERIFY IN FIELD Hcp.1CONTROL POINT ,MODULE HCP SIEMENS 4S DEEP • VERIFY IN FIELD HZM1 REMOTE CONVENTIONAL HZM ;; • ZONE MODULE ..l!.! SIEMENS 4S DEEP VERIFY IN FIELD 1,1•• • LINEAR BEAM 0.•• .1 SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD A 1:H SMOKE DETECTOR HFP-11 W/ SIEMENS i=11:••• (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING DUCT SMOKE DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 BASEVV/ SIEMENS DB -1,1 4S DEEP VV/ 1G RING CEILING F;,. FIRE ALARM SPEAKER STROBE L C1i41 (CEILING MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. ,!!in: • FIRE ALARM „ SPEAKER STROBE (WALL MOUNT) s• • FIRE ALARM '"' SPEAKER STROBE C•E`: (CEILING MOUNT) SET -MC -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. 1;1 FIRE ALARM , • STROBE C I (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING L 1, FIRE ALARM 1!;!.• • • STROBE • (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. FIRE ALARM 9, SPEAKER k',11 • (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. FIRE ALARM SPEAKER '; • (WALL MOUNT) SET -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM !! FIRE ALARM le Or STROBE WP (WEATHERPROOF) SET -S17 -WP SIEMENS MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD MR • MULTI -VOLTAGE CONTROL RELAY MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD iv t' MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JBEIX FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD ® JUNCTION BOX F.B.O. F.B.O. N/A VERIFY IN FIELD . ABOVE FINISHED FLOOR N/A N/A N/A N/A .;; FURNISHED BY ; N/A ; OTHERS N/A N/A N/A NOT N/A N/A 7; APPLICABLE '• .:.! llL• N/A N/A • N/A UNLESS OTHERWISE NOTED N/A N/A N/A : N/A • WEATHERPROOF • DEVICE N/A N/A N/A N/A . i••• • AS BUILT ADD OR CHANGE N/A N/A N/A N/A AS BUILT GREEN! REMOVE N/A N/A N/A N/A BLUE , AS BUILT NOTES TO CAD N/A N/A N/A N/A ri ht 2006 b Guardian Securit 1.: 11 • 1 • • .• • 111, 1,1 , • ill! • • • •• .21 Lti efta *;• 1743 IST AVE: SO:, SEATTLE,INASHINGTON- 981314 U) z 0 UJ w UJ _J LU REV. BY: Z, DESCRIPTION SHOP DRAWINGS , DATE 5/5/08 • !•.'i .1 .••••• • . .e.;11. • i• ' GJ • 2008 Tukwila Fire S stems, Inc. All Ri hts Resered ‘CALE: 1 /8"= 1 ›i• DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE: 5/05/08 BACKROUND PLAN PROVIDED BY: ..JOB NUMBER:54520 SHEET FA -01 • t1 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS DUCT DETECTOR LOCATION p TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVIC JL END OF LINE DEVICE(3.6K 1/4W) - 0 SUPERVISED SWITCH GROUND -0 d 0 HTRI-R 0110 STATUS LED CO N to 0 0 0 N.O. COM N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVIOUS ADDRESSABLE DEVICE TO NEXT ADDRESSABLE E DEVICE L NOTE 1: VOLTAGE MAX, - CURRENT MAX. - CONT, RES. MAX. - MAX. CABLE LENGTH- C CLINE TO LINE)— C CLINE TO SHIELD) - MAX. LINE SIZE - MIN. LINE SIZE- OUTLET SAMPLING TUBE INLET SAMPLING—\ TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE MUSIC 1} -AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE{ (+) STOP IF LAST DEVICE (-)- FROM XLS CONTROL PANEL ❑R�¢)- PREVIOUS ADDRESSABLE DEVICE (-) RELAY CONTACTS (4.OA @ 125VAC) C4.0A @ 30VDC) 27 VDC 3,5 riA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0.02uF 0.04uF ' 14 AWG':. 18 AVG NOTE 2: ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTI❑N. loal ama .�TB1 • 1 2 3.4 5.6 ° HCP TB2 6 5 4(t 4 3 2 _27„ END, OF LINE DEVICE 0 C3.6K 1/4W) / / SUPERVISED / SWITCH GROUND 0 0 0 HTRI-D STATUS LED CO 0' t` 0 ,.I NOT USED, cno 0 0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) - 0 CND N AC C 0 0 PAD -3 0 00 0 INPUT •'' INPUT TROUBLE NAC1 NAC2 NAC3 .NAC4 AUX 1+ 1-.' 1 2+ 2-;2 . NC C NO + = '+ - + - +._ - • +- EA V MIWMILg 1011 24K TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE NAC -4 NAC -3 NAC -2 NAC -.1 i 'i FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP W, NOT USED REMOTE DEVICE LOOP 0- 0 0 FROM .XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY C'S' CABLE) END OF LINE.DEVIC, Er, FROM, FACP • 3.6K 1:/4,W)'' i!: CVCIIOE CIRCUIT) ' CABLE) UPER\%ISED, C'V' WITCH 470 OHMS EOL TSM -1 0 TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE NOW STROBE SPEAKER ( (-) STROBE EARTH GROUND ,(+)TO NEXT DEVICE OR >(-) STOP IF LAST DEVICE 0 STROBE SPEAKER (1,., ^) SPEAKERISRROBE AND STROBE WIRING LABEL SCALE ;iA SPEAKER STROBE OR STROBE ONLY 80- A.F.F. 4S DEEP BOX • w/. 1-1/2" EXTENSION RING (SPEAKER STROBE) • 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE ;�. TO NEXT, ;,DEVICE OR END OF LINE TO NEXT DEVICE OR END. OF LINE is NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERTIN TEMPERATU +32' F 0' C TO 100* F (NtC) HUMIDITY: RELATIVE HUMIDITY. NON -CONDENSING HFP-11 SMOKE DETECTOR ,\ FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (-) DATA IN (+) > DEVICE IS USED FOR AIR VOLOCITY APPUCATIONS OF 300-4000 FT IN WHEN USED IN CONJUNCTION WH DUCT HOUSINGS AD -11P OR AD-11XPR D8-11 4I { % STANDARD SM06NE DETECTOR BASE ,! REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT DEVICE i ( ) DATA OUT > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID --- CEILING SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION /--- CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTION BOX MOUNTED ON CEILINGI FLEX \. JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT / / / / / / / / 0 0 0 0 1L" TO NEXT DEVICE - CADDY BAR SMOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE:NONE SUSPENDED ILLUMINATED CEILING Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved J RELEASE/REVISIONS IREV. BY: I z Q DESCRIPTION SHOP DRAWINGS DATE 0o 0 i U") 2 CCCCC (/) :51 w Cn E5 z O (I)H rx:. cc (I) 8,4tt ZU co-- L 75 11: EL- - o CD OD SCALE: 1 /8"=1 J "eZC DRAWN. BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/05/08 BACKROUND PLAN PROVIDED BY: �OB NUMBER:54520 • ./ CSHEET FA -02 j UP TO ROOF TOP ADDRESSABLE RELAY ,E0L—S1 j202_ 11;21 21 7'-O" AFF I Q / r-0" \ 30 .‘-..; ------------ \''' '::'' I.:`! i,.. -.11.---7:----" -''...::' vi ' \ \ ‘ i ',1 \ ti 1 1 7; . i A 1 .--1 011 -; 1: .....:I. n 1 -, 1 -1,..., i i .0 \ ..: 0. 2S,2V j — \ ,i; 1 \ 1 AFF 9'-6" AFF (7) ...!_,„_;,,,_...., I .r.).,- t- It --1 „ \‘‘,.1--":::: ‘k, cl. 1 't.,3 fl.,... 1 ,.......›.. r.,.....y ‘ \ , \\N.. \\ ,,,,,t ,...„.\::,...,.;; . 7 ,:i.,"• ..; \ ,17 21-,,;\\\\.=\=,\trci,111.:1 .- ' n44\‘ 1 ' '. tr..-.'" ‘,. N.\, \-:.::.,'• '\-‘'`''\','o\.:. ' \ \.r" ' \,,,,, .:.n':, .,;, \ .......\ -. \ \•::‘\ ' :';,',...."+-, -i ,,;n'•,I,tn %!,.,.h,.....;..,.:..!---:n:n•i: .. 1i \ \1;,-'\ \. ---:— \1‘ 1‘' . 1 \,,...c: \ 1\ ;,I ,• >-- —. ,,\ 1 ,,,_,----\ \ \ c.; NORTH 12'-O" AFF D,I JOHNNY ROCKET'S WESTFIELD SOUTHCENTER MALL Ar SCALE 1/8":11 HvAc ROOF. DOWN TO REMOTE LED/TEST SWITCH '1 It • . FLAG NOTES: . I . FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE: FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS.(SEE SIEMENS INSTALLATION SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED. BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR. SIEMANS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLATOR FIRE SUPPRESION SYSTEM. FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS 5: uJ DESCRIPTION SHOP DRAWINGS uJ F— CO 0 11) < <<< ( 1 'ALE: 1 /8" =1 DRAWN BY: 'ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/05/08 BACKROUND PLAN PROVIDED BY: ,JOB NUMBER: 54520 SHEET FA -03 ,} •,-L*.- • t•T 6 ! I - Rh/ 11 film I Hum Hi mill IuJflunIu ‘c -54-••A 0 FT;7__,:s;.;-:-;\\\ - ---i , ---------'-'„ __ ___... \\ \\ ' - - - j. ,, -__...,, • ,, ___V .••-•=/•=\ -_--,--!, -- -k--- .:- -- \ , _- .,r , ' :?, 1 , \\1 \\\ \ \ --- - ----2f-.1. - o ..•,,,,,,, ,, \ --,--.--------15A.-. ‘qf---- ' NORTH PA 0 1 _ _ JOHNNY ROC 11 0 • P 0 t./ ----- , /---.., -1 •-•.. it- '".-.-------- -,,, .„:„..„, ",.. 0 /6 4 ' ' ".. ) ....,.!--1, 4' "'--[-- ----- I- \ t:..--'•;'" ------ ---- -//' . • . ----- -. -..- ----------------------- : \ ------L----------------- -- JOHNNY ROCKET'S WESTFIELD SOUTHCENTER MALL • R • . / • !!:!•:'• „- lJTh [N. 77 c SCALE 11374 P1 A `; , . • 2I DI D 30 STORE LEVEL 30 c 110 2S,2V FA-BLIX FACP EX . .• • .• SYSTEM CALCULATIONS BATTERY SIZING CALCULATION , JOHNNY ROCKETS Notification Appliance Circuit Detail JOHNNY ROCKETS • FACP ADD ONS WESTFIELD SOUTHCENTER MALL • SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations LLI PROJECT: JOHNNY ROCKET'S •Wire Resistance 1.62 _ ..._:. _...._ . . Panel: Date: May 8, 2008 CURRENT TOTAL= 429 CIRCUIT: S1 9 Current Load: Standby: Alarm: Current Load: Device Type Alarm Current Alarm Total Standby: Alarm: Voltage at EOL Circuit Total 0 SET -MC @15CD 64 0 Total Wire Resistance ( R ) 0.45 1 SET -MC @30CD 98 98 Device Type , Qty Amps • Total Amps Total SET -MC @75CD , Device Type Qty Amps Total Amps Total 1 SET -MC @110CD HFP-11 , 0.0022 0.0022 0.0023 (Total Cct Load) 0 - SET-HMC-C@115CD 318 0 ' Voltage Drop ( E ) AD2-P 1, 0 1 0.0635 0.0635. 0.064 0.064 , Main.System Board (E= I * R) 1 0.03 SET -HMC @135CD 0.03 0.030 0.030 s HTR -R 1 0.009600 0.0096 0.021 0.021 - 0 SET -MC @15CD (20.4 - E) 0.064 Z-MC@15CD : 64 0 HTRI-D 1 0.001600 0.0016 0.0035 0.004 1 Z-MC@30CD SET -MC @30CD SET -MC @75CD 98 1 0.098 0.098 0 ICP -B6 ; ;‘ 233 0 0.005 ' DEVICES= 3 TOTAL m A= 0.175 12 140 20.2054056 429 SET -MC ©110CD 1 0.233 0.318 0.233 Notification Appliance Circuit Detail , : 1 PROJECT , 1i,SET-HMC-C@115CD JOHNNY ROCKET'S Wire Resistance 2.58. . Panel: May 8,1,2008 CURRENT TOTAL= SET-HMC-C©135CD ,SET-HMC-C@185CD Date: CIRCUIT: 0.318 0.445 . • 1, 0.0747 Amps 0.0885 Amps Alarm Current Alarm iTotal Wire Size Wire Length Voltage at EOL Circuit Total 2 ,ZR -MC @15CD ZR -MC @30CD HCP : 1:8 3.6 i 0.064 0.098 0.0015 0.098 Total Wire Resistance ( R ) ., Standby Current Load: 0.0747 Amps For 24 Hours = 1.793 Amp -hours i ( WL * 2 )* (R/ft) 0 i 0 i Alarm Current Load: 0.0885 Amps For 5 Minutes= 0.007 Amp -hours 0 (Total Cct Load) 0.03 Amps 0.459 Amps l' , 4 Voltage Drop ( E ) 0.00 •0 ; 0 25% Derating=, 2.250 Amp -hours (E= I * R) Standby Current Load: ,, : ' 0.03 Amps For 24 Hours = 0.720 Amp -hours ' T - 20.40 , 0 0 0 (20.4 - E) 0 0 0 0 0 0 Alarm Current Load: 0.459 Amps 2 For 5 Minutes= 0.039 Amp -hours 25d, : . 20.390-51 3.61 Total System Current Load. 2.250 Amp -hours . , 25% Derating= 0.948 Amp -hours , Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.948 Amp -hours , ! , Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULATION , Z < Notification Appliance Circuit Detail DESCRIPTION WESTFIELD SOUTHCENTER MALL LLI PROJECT: JOHNNY ROCKET'S •Wire Resistance 1.62 _ ..._:. _...._ . . Panel: Date: May 8, 2008 CURRENT TOTAL= 429 CIRCUIT: S1 9 <1<<<< QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 0 SET -MC @15CD 64 0 Total Wire Resistance ( R ) 0.45 1 SET -MC @30CD 98 98 ( WL * 2 ) * (R/ft) 0 SET -MC @75CD 175 0 Total Device Load, Amps (I) 0.43 1 SET -MC @110CD 233 233 (Total Cct Load) 0 - SET-HMC-C@115CD 318 0 ' Voltage Drop ( E ) 0.19 0 SET-HMC-C@177CD 445 0 1 (E= I * R) 0 SET -HMC @135CD - 318 ; 0. s EOL Voltage 20.21 0 SET -HMC @185CD r 445 - 0 1 (20.4 - E) 0 , Z-MC@15CD : 64 0 1 Z-MC@30CD " 98 98 0 SET-MC-CW@110CD 233 0 DEVICES= 3 TOTAL m A= - 429 12 140 20.2054056 429 Notification Appliance Circuit Detail PROJECT WESTFIELD SOUTHCENTER MALL .• , , JOHNNY ROCKET'S Wire Resistance 2.58. Panel: May 8,1,2008 CURRENT TOTAL= 3.6 Date: CIRCUIT: SPEAKER CIRCUIT . . • QTY Device Type Alarm Current Alarm iTotal Wire Size Wire Length Voltage at EOL Circuit Total 2 70.7V 1/8 , : 1:8 3.6 i Total Wire Resistance ( R ) 1.29 0 0 ; 0 ( WL * 2 )* (R/ft) 0 i 0 • Total Device Load, Amps (I) 0.00 0 0 0 (Total Cct Load) 0 0 0 Voltage Drop ( E ) 0.00 •0 ; 0 (E= I * R) 0 ,, : ' 0 0 EOL Voltage .:: -,. - - 20.40 , 0 0 0 (20.4 - E) 0 0 0 0 0 0 DEVICES= 2 TOTAL m A= . 3.6 14 25d, : . 20.390-51 3.61 FAX (206) 628-4990 RELEASE/REVISIONS REV. BY: Z < DESCRIPTION SHOP DRAWINGS LLI 5/5/08 I-- < c) 9 <1<<<< z. 5 cwd- LLI cc - L7] w6w CC Oz z 8,< z < w-- z Li2 z LT o 80 -3 co w >- (/) 8"='i' 8"=1' 6ALE:- 1 DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE:5/05/08 BACKROUND PLAN PROVIDED BY: RISER DIAGRAM •VOLTAGE DR P CALCULATION NUMBER:54520 SHEET FA -04- Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved • [] Without Cornment8 ] A fdot8dInRed Per The Attached Letter nese plans ;,4,,/., 1 , . /l .., I:,. I./. The Tulp V,Iila Fire Prevention % ::.; _i .;; ..r. cl_irr:':nt city standard_.. ! and omission:. vic(.;tlon:; of ;adopted standcro,. SI',c.. r' - r :: .I iz;il:;<c r for the ,J ..� _},, ,.. -•.fgner. ail Cnqu[I{�' l!� - ,I' .. .. .. 'll: t_!1[� (.I �:�."�' Addition c . l ;::.,,_.. , kc: i lr:, : di wirlgs atter this cft' \•v.....:nd will require a resubmittal of ;.:,;!; : ;Jr.:ving:. for oubsequent approval. Final acc:*'pt<:ncr: i::.f.'Ijc:.ci to field test and inspection by Thtt Tukwila Fire Prevention Bureau. Date: ` o By: ? Weil stamps rni sL be inspected before pipe, is hung. Do not paint piping prior to hydrostatic tic t st • —Johnny Rockets General Notes -------------- VICINITY MAP (Suite#2600) SCALE: NTS 1. Western States Fire Protection to add new pendent heads new upright heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of aII sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. rLIKWILA FIRE DEPARTMEN1 Please call: 575.4407 and give this job No. OB -S-/c6 and exact address for shut. z:.1wnln or rF,,,toration aprrov$:lJ: EAST RISER DETAI I , HYDRAULIC REFERENCE ONLY NOT TO SCALE SYMBOL LEGEND 2 -WAY EARTHQUAKE BRACE 4 -WAY EARTHQUAKE BRACE NO. REVISIONS DESCRIPTION DATE HYDRAULIC REFERENCE POINT HANGER SYMBOL BRANCHLINE RESTRAINT 4" Existing Main Zone M-5 SYM. O (I SIN R5415 R5714 R5415 1'/i' Existing Branchline—t 1'h" x 1" Mech Tee CLG 0'-0" 4 lust 0 — ^+ Ti. .OW PLUG— Ct$ 1 / N - CLO 12'-0.2;HT1 , :,("4,;4:4- 3.0% ' CLG 12'-0" 1'A" x Mech Tee 1.13%' CLG-8'-Q" CLO 14'-0" .: Pocket + Gl CLG 9'-6" rPLUG1 Cooking Hood 1'N' Existing Branchline Ordinary Group II.0.20gpm/ft2 for 793.00ft2 Mech Tee 1'/i' x 1" FIRE SPRINKLER SYSTEM QTY. 10 2 4 Total = 16 K 5.6 5.6 5.6 SPRAY Pendent Pendent Pendent 1/8" =1'-0" Sprinkler Legend ORIF. Y2' W. FIN. White White White TEMP. 155°F 155°F 200°F MFR./MODEL Realible G4A Concealed F3QR Dry Pendent Realible G4A Concealed COOLER APPROVAL: Johnny Rockets Remote Area: Retail # 2600 CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY ciAss ORD HAZARD II MAX. COVERAGE per HEAD 130 DENSITY .20 GPM / Ft' for 793 SPRINKLER Reliable Model G4A ORIFICE 1/2" K= 5.6 Ft' FI' WATER FLOW INFORMATION: STATIC 140 PSI RESIDUAL 20 PSI FLOW 10900 GPM AT BASE OF RISER, SYSTEM REQUIRES: 288.73 GPM cas 48.57 PSI City of Tukwila At time of Design CONT. NO.: KS0334 DRAWN BY: Adam Kantner SPRK ON SHEET: SEE LEGEND SPRK. ON JOB: DATE 05/01/08 :TYPICAL FLEXABLE SPRINKLER CONNECTION: FLEXHEAD MOUNTING BRACKET PIPE NIPPLE SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS REDUCING FITTING SUSPENDED T -BAR GRID SPRINKLER HEAD CEILING TILE FLEXHEAD DETAIL NOT TO SCALE FIG. 909 SWIVEL SWAY BRACE FITTING 31B" MIK BOLT (2114' EMBED LENGTH) . F10.1000 "TALI- SWAY BRACE ATTACHMENT LINE PIPE LATERAL LINE RESTRAINTS NON -THREADED BRACE PIPE FIG.4A PIPE CLAMP FOR SWAY BRACE 3/8'KWIK BOLT ' (21/4" EMBED LENGTH) FIG. 909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT LATERAL BRANCHLINE RESTRAINT BRACE PIPE 9 I NON -THREADED BRACE PIPE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE Hanger No. 07C HILTI Kwik Bolt III HILTI Kwlc Batt II Drilled Anchor i Cut Rod Lgth Rounded to Nearest Inch Rod Coupling All Thread Rod • Swivel Ring Concrete Construction q. • Bottom of Concrete to Center Line of Pipe Pipe Note on Plan Note on Plan: Hanger Number and 'A' Dimension HANGER DETAIL NOT TO SCALE VICINITY MAP DETAIL NOT TO SCALE Western States Fire Protection Company 7102 180th AVE NE, STE A-105 - REDMOND, WA- 98052 Lic. //: WESTESF136QF -- L. LUUO Tukwila Fire -? 5d 77//-9 w• •z O Adam Kantner Westwood Contractors fY 0 U Q' .CC 1— z 0 U WESTERN STATES FIRE PROTECTION COMPANY -OFFICES LOCATED ALBUQUERQUE/AUSTIN/DALLAS/DECATUR/DENVER fDULUIHIHOUSTON /KANSAS CITY LAS VEGAS /MINNEAPOLIS /PHOENIX/PORTLAND/ RAPID CITY/ ST. PAUL/SALT LAKECITYISEATTLE Phone: 425-881-0100 Fax 425-881-3030 Johnny Rockets 2600 Southcentner Mall ��-�/ Tukwila ,Wa 98188 FIRE SPRINKLER SYSTEM SHEET FP -1 OF. •1 Johnny Rockets _______________ General Notes VICINITY MAP (Suite#2600) SCALE: NTS 1. Western States Fire Protection to add new pendent heads new upright heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. EAST RISER DETAIL HYDRAULIC REFERENCE ONLY NOT TO SCALE 4" Existing Main Zone M-5 1'A" Existing Branchline 1 1'A" x 1" Mech Tee ry11+wa" CLG lYz"x1".DN 1x11 - Me;h-Tee\To FLEX ,/ �O PICU 0 L PLUG CLG 12'-0" j CLG 7'-0" Lx r14— °I 9 )IN I 1'A" Existing Branchline x 1" Mech Tee CLG 14'-0/0 Pocket 45. o'R‘o``y t CLG 9'-6" 'PLUG; Cooking Hood Ordinary Group II.0.20gpm/ft2 for 793.00ft2 Mech Tee 1'A" x 1" FIRE SPRINKLER SYSTEM 1/8" = 1'-0" COOLER Johnny Rockets Remote Area: Retail # 2600 CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY cLAss ORD HAZARD II MAX. COVERAGE per HEAD 130 DENSITY .20 GPM / Ft' for 793 SPRINKLER Reliable Model G4A ORIFICE 1/2" K= 5.6 Ft' Ft' WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 PSI FLOW 10900 GPM AT BASE OF RISER, SYSTEM REQUIRES: 288.73 GPM © 48.57 PSI ' At time of Design TYPICAL FLEXA13LE SPRINKLER CONNECTION FLEXHEAD MOUNTING BRACKET PIPE NIPPLE SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS ^� ^ REDUCING FITTING SUSPENDED T -BAR Gt2ID SPRINKLER HEAD CEILING TILE axs:**F1,S*a.% FLEXHEAD DETAIL NOT TO SCALE 3/9' KWIK BOLT .�.- (2 1k' EMBED LENGTH) FIG.909 SWIVEL SWAY BRACE FITTING Teta FIG. 1000 "FAST CLAMP" SWAY BRACE ATTACHMENT LATERAL LINE RESTRAINTS NON -THREADED BRACE PIPE FIG. 4A PIPE CLAMP FOR SWAY BRACE 3/9' KWIK BOLT (21k' EMBED LENGTH) FIG.909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT LATERAL BRANCHLINE RESTRAINT LP BRACE PIPE lo NON -THREADED BRACE PIPE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE Hanger No. 07C HILTI Kwik Bolt III Cut Rod Lgth Rounded to Nearest Inch N N 1 HILTI Kwik Bok 11 / Drilled An hor �`..-ri.( 1 Concrete Construction Rod Coupling Swivel Ring Pipe cL Bottom of Concrete to Center Line of Pipe Note on Plan Note on Plan: Hanger Number and 'A' Dimension HANGER DETAIL NOT TO SCALE VICINITY MAP DETAIL NOT TO SCALE Johnny Rockets w z 0 Adam Kantner 0 Westwood Contractors CONTRACTOR: SYMBOL LEGEND REVISIONS Sprinkler Legend 2 -WAY EARTHQUAKE BRACE NO. DESCRIPTION DATE SYM. SIN QTY. K SPRAY ORIF. FIN. TEMP. MFR./MODEL 4 -WAY EARTHQUAKE BRACE R5415 10 5.6 Pendent z White 155°F Realible G4A Concealed APPROVAL: City of Tukwila HYDRAULIC REFERENCE POINT .4 R5714 2 5.6 Pendent %Z' White 155°F F3QR Dry Pendent CONT. NO.: KS0334 R5415 HANGER SYMBOL 4 Total = 16 5.6 Pendent %' White 200°F Realible G4A Concealed DRAWN BY: Adam Kantner BRANCHLINE RESTRAINT SPRK. ON SHEET: SEE LEGEND SPRK. ON JOB: DATE: 06/19/08 Western States Fire Protection Company 7102 180th AVE NE, STE A-105 - REDMOND, WA - 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY • OFFICES LOCATED ALBUQUERQUE /AUSTIN/DALLASI DECATUR/DENVER/DULUTH/HOUSTON/KANSAS CITY LITS VEGAS /MINNEAPOLIS / PHOENIX /PORTLAND /RAPID CITY /ST, PAUL /SALT LAKE CITYI SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 Johnny Rockets 2600 Southcentner Mall Tukwila ,Wa 98188 FIRE SPRINKLER SYSTEM SHEET FP -1 OF 1 2600 SOUTHCENTER MALL FC -1 FOOD COURT ASSOCIATED PERMITS 08-F-180 08-S-160 14-H-021 08-H-267 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Johnny Rockets 2600 Southcenter Mall FC -01 Permit No.: 08-S-160 Date: May 5, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). FIRE DEPARTMENT HOOD SUPPRESSION PLAN REVIEW COMMENTS Project Name: Johny Rockets 2600 Southcenter Mall space FC -1 Permit No.: 08-H-267 Date: June 4, 2008 Reviewer: Steve Kohler Fire Protection Inspector/Plan Review (206)575-4407 • Nozzle heights above appliances to be per manufacturers installation guidelines. • Install splash guards between fryers and ranges/charbroilers. • Upon activation of the suppression system, the make-up air supply will shut off and the exhaust will keep running. • Type 1 hood systems shall be designed and installed to automatically activate the exhaust fan whenever cooking operations occur. The activation of the exhaust fan shall occur through an interlock with the cooking appliances, by means of heat sensors or by means of other approved methods. • Activation of the suppression system shall shunt all electrical power under the hood as well as the gas supply. • Install a "K" rated portable fire extinguisher within 30 ft. of the cooking equipment. • The hood suppression system shall be monitored by a U.L. Central Monitoring Station. Job Number: KS0334 Report Description: Ordinary Group II • • • • • F.. Job Number KS0334 Design Engineer Adam Kanter Job Name Johnny Rockets State Certification/License Number WESTESF136QF Address 1 2600 Southcentner Mall A11.1 City of Tukwila Address 2 Job Site Southcenter Mall City Tukwila State Wa Zip Code 98188 Drawing Name FP-1.cad Systen Most Demanding Sprialder Data 5.6 K -Factor 20.00 at 12.755 Occupancy Ordinary Group II Hose Allowance At Source 250.00 Density 0.20gpm/ft2 Area of Application 793.00ft2 (Actual 889.16ft2) Additional Hose Supplies Node Flow(gom) Total Hose Streams 250.00 System Flow Demand 288.73 Total Water Required (Including Hose Allowance) 538.73 Maximum Pressure Unbalance In Loops 0.000 Maximum Velocity Above Ground 16.33 between nodes 53 and 52 Maximum Velocity Under Ground 1.09 between nodes 1 and 268 Volume capacity of Wet Pipes 1930.11gal Volume capacity of Dry Pipes 1.36ft3 Number Of SprinIdars Calculated 13 Coverage Par Spnnider 1 00.00ft2 Node Hose Flow (gpm) Static (psi) Residual Flow (psi) (gpm) 250.00 140.000 20.000 1 10900.00 Available Total Demand (psi) (gpm) 139.540 _I 538.73 Required (psi) Safety Margin (psi) 52.021 87.518 Confractor Contractor Number KS0334 Contact Name Adam Kantner Contact Title Project Manager Contractor Name Western States Fire Protection Phone 425.881.0100 Extension Address 1 7102 180th Ave Ne, Suite A-105 FAX 485.736.9032 Address 2 City Redmond State WA Zip Code 98052 Web -Site © M. E P .CA D , Inc. 41 A utoS PRIN K® VR5 v5.2.6 04/24/2008 11:35:06AM • Page 1 Job Number: KS0334 Report Description. Ordinary Group II Device Actual Flow (gpm) Minimum Flow (gpm) K -Factor (K) Pressure (psi) Sprinkler 111 23.48 20.00 5.6 17.583 Sprinkler 112 23.50 20.00 5.6 17.610 Sprinkler 113 24.02 20.00 5.6 18.393 Sprinkler 103 20.57 20.00 5.6 13.498 Sprinkler 108 22.08 20.00 5.6 15.552 Sprinkler 104 20.63 20.00 5.6 13.572 Sprinkler 102 20.34 20.00 5.6 13.191 ==v Sprinkler 101 20.00 20.00 5.6 12.755 Sprinkler 110 23.37 20.00 5.6 17.411 Sprinkler 105 21.77 20.00 5.6 15.114 Sprinkler 109 22.53 20.00 5.6 16.193 Sprinkler 107 21.83 20.00 5.6 15.202 Sprinkler 114 24.60 20.00 5.6 19.290 '> Most Demanding Sprinkler Data © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 04/24/2008 11:35:12A M Page 2 Job Number: KS0334 Report Description: Ordinary Group II Node Elevation(Foot) Fittings Pressure(psi) Discharge(gpm) 17 15-11 15-11 P0(8-0) P0(5-0) 25.908 22.152 21 25 15-11 P0(5-0) 21.202 28 15-11 E(2-0) 20.946 42 18-11 P0(5-0) 16.612 46 18-11 P0(5-0) 15.076 49 18-11 P0(5-0) 14.719 51 18-11 2E(2-0) 14.622 52 15-11 P0(5-0) 19.821 53 15-11 P0(8-0) 25.915 72 15-11 P0(8-0) 25.982 74 15-11 P0(5-0) 21.714 79 18-11 P0(5-0) 18.909 80 18-11 P0(5-0) 18.800 84 18-11 P0(5-0) 18.433 100 15-11 P0(8-0) 26.127 106 18-11 P0(5-0) 24.052 138 18-5 2P0(26-4) 29.150 191 -15-11 P0(37-8%) 44.849 268 -13-11% BFP(-4.500) 48.572 302 -15-11 LtE(16-0) 44.886 111 10-01A Spr(-17.583) 17.583 23.48 112 7-0 Spr(-17.610) 17.610 23.50 113 12-0 Spr(-18.393) 18.393 24.02 103 7-0 Spr(-13.498) 13.498 20.57 108 12-0 Spr(-15.552) 15.552 22.08 104 12-0 Spr(-13.572) 13.572 20.63 102 10-0 Spr(-13.191) 13.191 20.34 101 10-0 Spr(-12.755) 12.755 20.00 110 12-0 Spr(-17.411) 17.411 23.37 105 12-0 Spr(-15.114) 15.114 21.77 109 10-0Y2 Spr(-16.193) 16.193 22.53 107 12-0 Spr(-15.202) 15.202 21.83 114 12-0 Spr(-19.290) 19.290 24.60 1 -21-10 S 52.021 288.73 dt, ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 04/24/2008 11:35:12A M Page 3 Job Number: KS0334 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Friction Loss Length Eq. Length Total Length Pressure Summary Downstream Upstream Elevation Discharge K -Factor Pt Pn Fittings Route 1 DR 1.049 Q=20.00 7.42 C=120 0.130131 36-04 Pf 5.733 101 10-0 q=20.00 K=5.6 12.755 Spr(-12.755) 8-0 Pe -3.866 51 18-11 14.622 4E(2-0) 44012 Pv BL 1.610 Q=20.00 3.15 C=120 0.016155 5-111: Pf 0.096 51 18-11 14.622 Pe 49 18-11 14.719 5-11'/2 Pv BL 1.610 Q=40.34 6.36 C=120 0.059156 6-012 Pf 0.357 49 18-11 14.719 Pe 46 18-11 15.076 6-0% Pv BL 1.610 Q=60.91 9.60 C=120 0.126802 12-112 Pf 1.536 46 18-11 15.076 Pe 42 18-11 16.612 12-112 Pv BL 1.610 Q=81.54 12.85 C=120 0.217510 4912 Pf 1.909 42 18-11 16.612 40 Pe 1.301 52 15-11 19.821 2LtE(2-0) 8-912 Pv BL 1.610 Q=103.63 16.33 C=120 0.338875 10-0 Pf 6.094 52 15-11 19.821 8-0 Pe 53 15-11 25.915 P0(8-0) 18-0 Pv CM 4.260 Q=174.63 3.93 C=120 0.007786 8-71/2 Pf 0.067 53 15-11 25.915 Pe 72 15-11 25.982 8-71/2 Pv CM 4.260 Q=264.13 5.95 C=120 0.016742 8-712 Pf 0.145 72 15-11 25.982 Pe 100 15-11 26.127 8-712 Pv CM 4.260 Q=288.73 6.50 C=120 0.019739 127-8 Pf 4.100 100 15-11 26.127 80-0% Pe -1.077 138 18-5 29.150 6fE(8-1112), P0(26-4) 207-8% Pv CM 6.357 Q=288.73 2.92 C=120 0.002810 133-10 Pf 0.818 138 18-5 29.150 157-2 Pe 14.881 191 -15-11 44.849 5fE(12-7), BV(12-7), CV(40-3), 291-0 Pv GV(3-912), PO(37-81/2) FM 8.329 Q=288.73 1.70 C=120 0.000754 16-512 Pf 0.037 191 -15-11 44.849 32-0 Pe 0.000 302 -15-11 44.886 fE(16-0), LtE(16-0) 48-51/2 Pv FM 10.420 Q=288.73 1.09 C=120 0.000253 28-21/2 Pf 4.528 302 -15-11 44.886 83-0 Pe -0.842 268 -13-111/2 48.572 4LtE(16-0), BV(19-0), BFP(-4.500) 111-212 Pv UG 10.400 Q=288.73 1.09 C=140 0.000192 110-2 Pf 0.043 268 -13-1112 48.572 111-7 Pe 3.407 1 -21-10 52.021 E(35-1), 3LtE(25-6), S 221-912 Pv so Route 2 DR 1.049 Q=20.34 7.55 C=120 0.134241 31-21/2 Pf 5.397 102 10-0 q=20.34 K=5.6 13.191 Spr(-13.191) 9-0 Pe -3.869 49 18-11 14.719 2E(2-0), P0(5-0) 40-212 Pv sr Route 3 DR 1.049 Q=20.57 7.64 C=120 0.137126 38-11/2 Pf 6.739 103 7-0 q=20.57 K=5.6 13.498 Spr(-13.498) 11-0 Pe -5.161 46 18-11 15.076 3E(2-0), PO(5-0) 49-11/2 Pv = Route 4 DR 1.049 Q=20.63 7.66 C=120 0.137820 32-91/2 Pf 6.033 104 12-0 q=20.63 K=5.6 13.572 Spr(-13.572) 11-0 Pe -2.993 42 18-11 16.612 3E(2-0), P0(5-0) 43-912 Pv eaw Route 5 DR 1.049 Q=21.77 8.08 C=120 0.152245 32-10% Pf 6.679 105 12-0 q=21.77 K=5.6 15.114 Spr(-15.114) 11-0 Pe -2.993 80 18-11 18.800 3E(2-0), PO(5-0) 43-10'/2 Pv BL 1.610 Q=44.31 6.98 C=120 0.070366 1-61/2 Pf 0.110 80 18-11 18.800 Pe 79 18-11 18.909 1-612 Pv BL 1.610 Q=66.14 10.42 C=120 0.147661 6-2 Pf 1.504 79 18-11 18.909 4-0 Pe 1.301 74 15-11 21.714 2LtE(2-0) 10-2 Pv BL 1.610 Q=89.51 14.11 C=120 0.258428 8-6 Pf 4.269 74 15-11 21.714 8-0 Pe 72 15-11 25.982 P0(8-0) 16-6 Pv sik Route 6 DR 1.049 Q=21.83 8.11 C=120 0.153063 34912 Pf 6.701 107 12-0 q=21.83 K=5.6 15.202 Spr(-15.202) 9-0 Pe -2.993 79 18-11 18.909 2E(2-0), P0(5-0) 43-912 Pv Route 7 fit, ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 04/24/2008 11:35:13A M Page 4 41 Job Number: KS0334 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Friction Loss Length Eq. Length Total Length Pressure Summary Downstream Elevation Discharge Upstream K -Factor Pt Pn Fittings DR 1.049 Q=22.08 8.20 C=120 0.156323 29-2 9-0 38-2 Pf 5.967 Pe -1.698 Pv 108 12-0 q=22.08 52 15-11 K=5.6 15.552 19.821 Spr(-15.552) 2E(2-0), PO(5-0) Route 8 DR 1.049 Q=22.53 8.37 C=120 0.162278 30-6Y2 7-0 37-6Y2 Pf 6.091 Pe -3.851 Pv 109 10-0Y: q=22.53 84 18-11 K=5.6 16.193 18.433 Spr(-16.193) E(2-0), PO(5-0) BL 1.610 Q=22.53 3.55 C=120 0.020146 18-21A 18-21A Pf 0.367 Pe Pv 84 18-11 80 18-11 18.433 18.800 = Route 9 DR 1.049 Q=23.37 8.67 C=120 0.173530 27-6'/z 7-0 34-6% Pf 5.996 Pe -1.693 Pv 110 12-0 q=23.37 74 15-11 K=5.6 17.411 21.714 Spr(-17.411) E(2-0), PO(5-0) Route 10 DR 1.049 Q=23.48 8.72 C=120 0.175119 29-10 4-0 33-10 Pf 5.923 Pe -2.560 Pv 111 10-0% q=23.48 28 15-11 K=5.6 17.583 20.946 Spr(-17.583) 2E(2-0) BL 1.610 Q=23.48 3.70 C=120 0.021740 11-91/� 11-9V2 Pf 0.256 Pe -0.000 Pv 28 15-11 25 15-11 20.946 21.202 BL 1.610 Q=46.98 7.40 C=120 0.078431 12-1% 12-1 Yz Pf 0.950 Pe -0.000 Pv 25 15-11 21 15-11 21.202 22.152 BL 1.610 Q=71.00 11.19 C=120 0.168356 14-4 8-0 22-4 Pf 3.757 Pe Pv 21 15-11 17 15-11 22.152 25.908 P0(8-0) CM 4.260 Q=71.00 1.60 C=120 0.001473 4-9% 4-9Y: Pf 0.007 Pe Pv 17 15-11 53 15-11 25.908 25.915 (as. Route 11 DR 1.049 Q=23.50 8.72 C=120 0.175373 33-6 9-0 42-6 Pf 7.452 Pe -3.860 Pv 112 7-0 q=23.50 25 15-11 K=5.6 17.610 21.202 Spr(-17.610) 2E(2-0), PO(5-0) .sr Route 12 DR 1.049 Q=24.02 8.92 C=120 0.182572 24-11 5-0 29-11 Pf 5.460 Pe -1.702 Pv 113 12-0 q=24.02 21 15-11 K=5.6 18.393 22.152 Spr(-18.393) P0(5-0) Route 13 DR 1.049 Q=24.60 9.13 C=120 0.190790 31-8 9-0 40-8 Pf 7.755 Pe -2.993 Pv 114 12-0 q=24.60 106 18-11 K=5.6 19.290 24.052 Spr(-19.290) 2E(2-0), PO(5-0) BL 1.610 Q=24.60 3.88 C=120 0.023686 20-8Yz 12-0 32-8Yz Pf 0.774 Pe 1.301 Pv 106 18-11 100 15-11 24.052 26.127 2LtE(2-0), PO(8-0) .0400.teflx . e L45iA 'Ai)..„: €t ` s' :W3`2{Y l:':' >1 a1us( :IFllult'`tier >< > > Actual Inside Diameter 4.87 = Factor Value Of C 100 Multiplying Factor 0.713 130 140 150 1.16 1.33 1.51 Schedule 40 Steel Pipe Inside Diameter / (dam © M.E.P.CAD, Inc. AutoSPRINKO VR5 v5.2.6 04/24/2008 11:35:13A M Page 5 Job Number: KS0334 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Friction Loss Downstream Upstream Elevation Discharge K -Factor Pt Pn Fittings Length Eq. Length Total Length Pressure Summary AO BL CM DN DR DY FM FR MS OR RN SP ST UG .........Y[?ete�er ................. �e ......................... Arm -Over Branch Line Cross Main Drain Drop Dynamic Feed Main Feed Riser Miscellaneous Outrigger Riser Nipple Sprig Stand Pipe Underground Diameter Elevation Flow Discharge Velocity Pressure Length Friction Loss HWC Pt Pn Pf Pe Pv Inch Foot gpm gpm fps psi Foot psi/Foot Hazen -Williams Constant Total pressure at a point in a pipe Normal pressure at a point in a pipe Pressure loss due to friction between points Pressure due to elevation difference between indicated points Velocity pressure at a point in a pipe ALV Alarm Valve AngV Angle Valve b Bushing BalV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Turn 90° cplg Coupling Cr Cross Run CV Check Valve DeIV Deluge Valve DPV Dry Pipe Valve E 90° Elbow EE 45° Elbow Eel 11%* Elbow Ee2 22W Elbow f Flow Device FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow flg Flange FN Floating Node ft' FireLock(TM) Tee g Gauge GIoV Globe Valve GV Gate Valve Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PrV Pressure Relief Valve PRV Pressure Reducing Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap (DA © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 04/24/2008 11:35:13A M Page 6 il :.... P..:: Job Number KS033, Report Description: Ordinary Group 1 Supply at Node 1 1 C Pressure, psi w3 0, W A O N p p Ncr.IIIIIII1t11111111111111,111111111111111111111111111111111I11111111111„11131111111111111„(C,I Static Pressure 140.000 „538.73 288.73 with hose @ 52.021 streams S /stem demand curve 10900.00 @ 20,000 Iriniiiltlll 111111111 111111 I l l 1 1 1 1 1 1 t H 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 111111111 v 910022W 3300 4400 5500 6600 7700 8800 9900 11000 Water flow, gpm Hydraulic Graph Supply at Node 1 Static Pressure 140.000 Residual Pressure 10900.00 @ 20.000 Available PressureTene of Test 139.540 @ 538.73 System Demand 288.73 @ 52.021 System Demand (Including Hose Allowance) 538.73 @ 52.021 DI, ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 04/24/2008 11:35:14AM Page 7 Job Number: KS0334 Report Description: Ordinary Group 11 M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 04/24/2008 11: 35:15A M Page 8 I G 1 -J O©® -I1 1 ��— 1 w �J' 0 I 1 113 v: pmpA CIO Z N I kr, cgm ig Received Time May, 28. 9:54AM I;J #111 11 11 m 9NIdId O13I4 DNIJId A21O13V4 - THIS FIRE SYSTEM COMPLIES WITH U.L. 300 REQUIREMENTS 1 Nm 1 1 1 1 1 I Z -'1*-.XXO IO'1 -1 a'I.-.aarrlrr�►� m rir x >omr y a o$a xn<a Z .ZI x aa.r DZ < ZZ-1Z2 to maNwrl m dmr rS,.rom mx ZrzNp0 mc1n5rloa myXPIo2coPati y Oia x 0 ZQ� tri -IO 312M d_Q e_IMO r= 0o arZnZZ Z=-1< 711:$ xmo r -a1 Z oo1 zr rtA m -Im3 viy ciz3.�D r -D td X Or Oy X.-.-. 1 In rl mA� Cb rriMZO n DMZ ry dN -riOr 0 -iOrl x In minx 0 0 ly 7:1201WW _o.<,0070 rp0L 066a **3 o -Z 63 C1 --VTG O Z N mOm- -9 a N''`ca MZ ay rr 71-4 re axt zr, �i 70 ym y Nrl 3311d21f1S ONI)1003 3H1 00 0 _ 1 Noun Duct PPln"r' o 1 1 1 1 1 I Z -'1*-.XXO IO'1 -1 a'I.-.aarrlrr�►� m rir x >omr y a o$a xn<a Z .ZI x aa.r DZ < ZZ-1Z2 to maNwrl m dmr rS,.rom mx ZrzNp0 mc1n5rloa myXPIo2coPati y Oia x 0 ZQ� tri -IO 312M d_Q e_IMO r= 0o arZnZZ Z=-1< 711:$ xmo r -a1 Z oo1 zr rtA m -Im3 viy ciz3.�D r -D td X Or Oy X.-.-. 1 In rl mA� Cb rriMZO n DMZ ry dN -riOr 0 -iOrl x In minx 0 0 ly 7:1201WW _o.<,0070 rp0L 066a **3 o -Z 63 C1 --VTG O Z N mOm- -9 a N''`ca MZ ay rr 71-4 re axt zr, �i 70 ym y Nrl 3311d21f1S ONI)1003 3H1 iv • vV �lJ Nola - Fire Systems - Parts List Report Fire System Parts List Job # 702814 - Johnny Rockets - Tukwila WA Location: Tukwila, WA Fire System # 1 Ansul R102 Hoods Covered: Hood # 1 Gas Valve(s) : ANSUL-3.0/1.5 Tag: 50 Page: 4 5/19/08 1:51 PM Supplied by Ship =Item CAS # Vendor # Description Dist CAS Inst Loose 1 1 AT - 1.5 AT - 1.5 TANK(#1A) - 1.5 Gallon SS Tank (for use with Automan 0 1 Release, Actuator, or SS Enclosure (UL)) 1 1 AT - 3.0 AT - 3.0 TANK(#1 B) - 3.0 Gallon SS Tank (for use with Automan Release, Actuator, or SS Enclosure (UL)) 0 1 1 3 ANS -OEM ANS -OEM REGULATED RELEASE - Ansul Regulated Mechanical Release/Bracket Assembly, OEM, R-102 0 1 1 5 LIQ -3.0 79372 AGENT -Ansulex Low PH Wet Chemical Agent, 3 1 0 Gallon (UL) 1 6 LIQ -1.5 79694 AGENT -Ansulex Low PH Wet Chemical Agent, 1.5 Gallon (UL) 1 0 1 9 101-30 101-30 CARTRIDGE - Carbon Dioxide, 101-30, Double Tank Cartridge (R-102) 1 0 1 10 TLINK TLINK LINK - Test Link Package 1 0 1 11 MICRO -SD MICRO -SD MICROSWITCH -Single Dual Electric Switch 0 1 1 12 HOSE 79007 HOSE - Rubber Hose 0 1 1 13 419337 419337 NOZZLE - 2W Nozzle, Duct 0 1 5 16 419335 419335 NOZZLE - 1N Nozzle, Plenum/Appliance 0 5 2 19 419338 419338 NOZZLE - 3N Nozzle, Appliance 0 2 3 25 418569 418569 NOZZLE ADAPTOR - Swivel Nozzle Adaptor 0 3 8 26 QSA-3/8 QSA-3/8 QUIK SEAL - 3/8" (UL) 0 8 1 27 QPSA-1/2 QPSA-1/2 PULLEY SEAL -1/2" Hood Seal (UL) 0 1 4 28 S -DET S -DET DETECTOR - Series (Scissor Linkage) 0 4 2 29 ANS-360FL ANS-360FL FUSIBLE LINK - 360deg F, R-102 and PIRANHA 0 2 2 30 ANS-500FL ANS-500FL FUSIBLE LINK - 500deg F, R-102 and PIRANHA 0 2 1 34 RPS -A RPS -A REMOTE PULL STATION -Aluminum (without wire 0 1 rope) 2 35 PE -LT PE -LT PULLEY ELBOW - Low Temp. Pulley Elbow, Set 0 2 Screw Type 1 36 PE -HT PE -HT PULLEY ELBOW - High Temp Pulley Elbow, 0 1 Compression Type 5 41 SN -CHAR SN -CHAR SINGLE NOZZLE EXTENDED DROP ASSY 0 5 http://appl.captiveaire.com/Order/FireSystems/PartsListReport.aspx?JobFireSystemld=145287 Page 1 of 2 Received Time May. 28. 9:54AM 1 r..._1 . L. %I -L t.. a CJ 1 1 S Page: 7 Received Time May, 28. 9:54AM SECTION IV — SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-28 REV. 5 4-1-06 Nozzle Application Chart The following chart has been developed to assist in calculating the quantity and type of nozzle required to protect each duct, plenum, or appliance. NOTICE This chart is for general reference only. See complete details for each type of hazard. Hazard ► Duct or Transition (Single Nozzle) Duct or Transition (Single Nozzle) Duct or Transition (Dual Nozzle) Electrostatic Precipitator (At Base of Duct) Plenum (Horizontal Protection) ► Plenum (Horizontal Protection) Plenum (Vertical Protection) ► Fryer (Split or Non -Split Vat) Fryer (Split or Non -Split Vat) Fryer (Split or Non -Split Vat)* Fryer (Non -Split Vat Only) Maximum Hazard Dimensions Minimum Nozzle_ Nozzle Quantity Heights Length — Unlimited 1 Perimeter — 50 in. (127 cm) Diameter —16 in. (40.6 cm) Length — Unlimited Perimeter —100 in. (254 cm) Diameter —31 7/8 in. (81 cm) Length — Unlimited Perimeter —150 in. (381 cm) Diameter — 48 in. (122 cm) Individual Cell Length —10 ft. (3.1 m) Length — 6 ft. (1.8 m) Width — 4 ft. (1.2 m) Length — 4 ft. (1.2 m) Width — 4 ft. (1.2 m) Maximum Size (without drip board) 14 in. (36 cm) x 15 in. (38 cm) Low Proximity Maximum Size (without drip board) 141/2 in. (37 cm) x 14 in. (36 cm) Medium Proximity Maximum Size (without drip board) 15 in. (38 cm) x 14 in. (36 cm) High Proximity Medium Proximity Maximum Size (without drip board) 19 1/2 in. (49.5 cm) x 19 in. (48.2 cm) High Proximity Low Proximity Maximum Size (without drip board) 18 in. (45.7 cm) x 18 in. (45.7 cm) High Proximity 1 2 1 1 1 1 1 1 1 1 1 1 For multiple nozzle protection of single fryers, see detailed information on Pages 4-12 through 4-14. 13-16 in. (33 — 41 cm) 16 — 27 in. (41 - 69 cm) 27 — 47 in. 20 — 27 in. 21 — 34 in. 13-16 in. 25 — 35 in. (64-89 cm) Nozzle Part No. 430912 419337 419337 419334 419335 430192 419336 419336 419342 419342 419339 419340 419338 419342 419338 Nozzle Tip Stamping — Flow No. 1W 2W 2W 1 /2N 1N 1W 1W 1W 290 290 230 245 3N 290 3N Nozzle Application Chart (Continued) Hazard Fryer (Non -Split Vat Only)' Fryer (Split or Non -Split Vat) Fryer (Split or Non -Split Vat) Range Maximum Hazard Dimensions Maximum Size (with drip board) 21 in. (53 cm) x 14 in. (36 cm) (Fry Pot must not exceed 15in. x14in. (38 cm x 36 crn)) High Proximity Medium Proximity Maximum Size (with.drip board) 25 3/8 in. (64.4 cm) x 19 1/2 in: (49.5 cm) (Fry pot side must not exceed 19 1/2 in. (49.5 cm) x 19 in. (48.2 cm) High Proximity. Low Proximity Maximum Size (with drip board) 18 in. (45.7 cm) x 27 3/4 in. (70.5 cm) High Proximity Minimum Nozzle Quantity 1 1 Maximum Size (with drip board) 14in.(36cm)x 21 in. (53 cm) 1 Low Proximity Maximum Size (with drip board) 141 /2 in. (37 cm) x 261/2 in. (67 cm) 1 Medium Proximity Longest Side 32 in. (81 crn) Area — 384 sq. in. (2477 sq. cm) Longest Side 28 in. (71 cm) Area — 336 sq. in. (2168 sq. cm) Longest Side (High Proximity) 1 28 in. (71 cm) Area — 672 sq. in. (4335 sq. cm) Longest Side (Medium Proximity) 32 in. (81 cm) Area — 768 sq. in. (4955 sq. cm) Longest Side (Low Proximity) 2 36 in. (91 cm) Area —1008 sq. in. (6503 sq. cm) For multiple nozzle protection of single fryers, see detailed information on Pages 4-7 through 4-11. SECTION IV — SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-29 4-1-06 REV_ s Nozzle -Heights. 27 — 47 in. 20 - 27 in. 21 —34 in. 13-16 in. 25 — 35 in. (64-89 cm) 13-16 in. (33 — 41 cm) 16-27 in. (41 — 69 cm) 30 —40 in. (76 -102 cm) 40 — 48 in. (102 -122 cm) (With Bookshelf) 40 — 50 in. (102-127 cm 30 — 40 in. (76 — 102 cm) 15 — 20 in. (38 — 51 cm) Nozzle Part No. 419339 419340 419338 419342 419338 419342 419342 419335 419333 419340 419341 419342 Nozzle Tip Stamping — Flow No. 230 245 3N 290 3N 290 290 1N 1F 245 260 290 SECTION IV – SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-30 REV. 3 10-1-02 Nozzle Application Chart (Continued) Hazard Griddle Chain Broiler* (Overhead Protection) Chain Broiler (Horizontal Protection) Gas -Radiant Char -Broiler Electric Char -Broiler Lava -Rock Broiler Natural Charcoal Broiler Lava -Rock or Natural Charcoal Char -Broiler Minimum Maximum Hazard Nozzle Dimensions Quantity Longest Side (High Proximity) 1 48 in. (122 cm) Area –1440 sq. in. (9290 sq. cm) Longest Side (High Proximity) 1 30 in. (76 cm) Area – 720 sq. in. (4645 sq. cm) Longest Side (High Proximity) 1 36 in. (91 cm) Area –1080 sq. in. (6968 sq. cm) Longest Side 1 (Medium Proximity) 48 in. (122 cm) Area –1440 sq. in. (9290 sq. cm) Longest Side (Low Proximity) 1 48 in. (122 cm) Area – 1440 sq. in. (9290 sq. cm) Longest Side – 34 in. (86 cm) 2 Area – 1088 sq. in. (7019 sq. cm) Length – 43 in. (109 cm) 2 Width – 31 in. (79 cm) Longest Side – 36 in. (91 cm) 1 Area – 864 sq. in. (5574 sq. cm) Longest Side – 34 in. (86 cm) 1 Area – 680 sq. in. (4383 sq. cm) Longest Side – 24 in. (61 cm) 1 Area – 312 sq. in. (2013 sq. cm) Longest Side – 24 in. (61 cm) 1 Area – 288 sq. in. (1858 sq. cm) Longest Side – 30 in. (76 cm) 1 Area – 720 sq. in. (4645 sq. cm) Nozzle Heights 30 – 50 in. (76 – 127 cm) (perimeter located) 30 – 50 in. (76 – 127 cm) (center located) 35 — 40 in. (89 – 102 cm) (perimeter located) 20 – 30 in. (51 – 76 cm) (perimeter located) 10 – 20 in. (25 – 51 cm) (perimeter located) 10 – 26 in. (25 – 66 cm) 1 – 3 in. (3 – 8 cm) 15 –40 in. (38 –102 cm) 20 – 50 in. (51 – 127 cm) 18 – 35 in. (46 – 89 cm) 18 – 40 in. (46 – 102 cm) 14 – 40 in. (36 –102 cm) Minimum chain broiler exhaust opening —12 in. x 12 in. (31 cm x 31 cm), and not less than 60% of internal broiler size. Nozzle Part No. 419341 Nozzle Tip Stamping – Flow No. 260 419342 290 419335/417332 1N/1NSS 419342 290 419343 419336/417333 419335/417332 419335/417332 419335/417332 419335/417332 419335/417332 419338 2120 1 W/1 WSS 1N/1NSS 1N/1NSS 1N/1NSS 1N/1NSS 1N/1NSS 3N v,vIMIV I-Segutaiea M9Crlanicai rseiease Assembly (3.0 gallon — Part No. 79290 or 1.5 gallon — Pan No. 79291) contains the regulated release mechanism, agent tank, expellant gas hose for agent tank hookup. and enclosure knockouts to facilitate installing actuation, piping; expellant piping; detection system; and additional equipment. This regu- lated release assembly is used in single, double. and multiple - tank systems and must- be mounted to a rigid -surface. The release mechanism can be used to interconnect both the actu- ation and expellant gas lines as required per system design. The regulator is designed to allow a constant flow of gas into the tank at 100 psi (690 kPa) when the system is actuated. In single. double, and multiple -tank systems, the provided expel- lant gas hose connects the agent tank to the bottom outlet of the regulator. In double and multiple -tank system configurations, the back outlet of the regulator is used as an expellant gas feed for one additional tank -enclosure or tank -bracket hookup. The enclosure contains the required knockouts to facilitate this con- nection. If a pressure switch is to be attached to the regulator, additional fittings are required. • - The tank is mounted within the enclosure. The tank contains an adaptor/tube assembly with a burst disc union. The burst disc helps prevent siphoning of the agent up the pipe due to signifi- cant temperature fluctuations in the area where the tank .is located. The tank is mild steel and, under normal conditions, requires hydrostatic testing .every twelve years. - The agent tank is shipped uncharged and must be filled with 1.53 gallons (5.8 L) or 3.06 gallons (11.6 L) of only ANSULEX Low pH Liquid Fire Suppressant during installation. The detection and additional equipment required per system design are connected tothe release mechanism. The enclosure contains knockouts to facilitate detection and additional hookups. The system can b actuated automatically or manually. Auto- - matic actuation occurs when a fusible link within the detection system separates in a fire condition. Manual actuation of the system occurs when personnel pull on the remote manual pull station pull rine. EXTINGUISHING AGENT ANSULEX Low pH Liquid Fire Suppressant (1:5 gallon — Part No. 79694 or 3.0 gallon — Par No. 79372) is a potassium -based solution designed for fast knock -down and suppression of grease -related fires. The agent is shipped in plastic containers which provide one complete tank charge. Agent storage life expectancy is twelve years. The distributor must record the batch numbers and date of shipment receipt to be filed with each instal- lation record. NIL Total Tank Type of Flow No.* Quantity System r Type of Hardware 1-5 1 Single 1.5 Gal. Reg. Release 6-11 1 Single - 3.0 Gal. Reg. Release ELECTRICAL SWITCHES - LOG°tra It3 Eprcl{ F Uto_ The electrical switches are intended for use with. electric gas valves, alarms, contactors, lights, contractor supplied electric power shut-off devices :and other electrical devices that are designed to shut off or tum on when the system is actuated. Switches are available in kits: One Switch Kit, Part No. 423878, Two Switch Kit, Part No. 423879; Three Switch . Kit, Part No. 423880, and Four Switch Kit, Part No. 423881. Each switch has a set of single -pole, double=throw contacts rated of 21 amp, 1 HP, 125, 250, 277 VAC or 2 HP, 250, 277 VAC. Mounting hardware is provided with each kit. R-102 RESTAURANT • FIRE SUPPRESSION SYSTEM (Standard UL 300 Listed) Nozzle Identification Chart Nozzle Nozzle. Nozzle Tvoe Part No. Sta monoino 1W Nozzle 419336 1W 1WSS Nozzle 417333 1W 1N Nozzle 419335 1N 1NSS Nozzle 417332 1N 1/2N Nozzle 419334 1/2N 3N Nozzle 419338 3N 2W Nozzle 419337 2W 2WH Nozzle 78078 2WH Noz Flov 1 1 1 1 1/2 3 2 2 230 Nozzle 419339 230 2 245 -Nozzle 419340 245 2 260 Nozzle 419341 260 2 290 Nozzle 419342 290 2 2120 Nozzle 419343 2120 2 1F Nozzle 419333 1F 1 I(oo Mflzzl.t: 4S07IZ (MD Nitrogen Cartridge Reauired LT -20-R (7032) LT -30-R (5373) Kf(6—, + 5ri)1S oi\\ S' fL1 kik Sr T5 D uW:rO PT K-rr5-01 SicINAL Carbon Dioxide Cartridoe Reauired 101-10 (15850) 101-20 (17492) X31)5'W1-- tS S SECTION IX - APPENDIX UL EX. 3470 ULC CEx747 Page 9-1 7-1-98 REV. 3 SYSTEM SELECTION GUIDE ' NOTE: System options do not cover all conceivable variations. They are listed here as a general guideline to show the most common type arrangement for multiple systems, Based on certain system designs utilizing manifolding, non-manifolding, 3 -tank systems, etc., other tank/cartridge combinations can be designed. The combinations below are based on 11 flow, 3.0 gallon tanks and 5 flow, 1.5 gallon tanks. More competitive designs may be available by utilizing 12 flow and 6 flow systems when appropriate. • Total Tank Type of Nitrogen Flow No. Quantity System Type of Hardware Carbon Dioxide Cartridge Required Cartridge Re o uirPd 1-5 1 Single 1.5 Gal. Reg. Release LT -20-R(7032) ) 101-10 (15850) 6-11 1 Single 3.0 Gal. Reg- Release LT -30-R(5373) ) 101-20 (17492) 12-16 2 Double 1.5 Gal. Reg. Release Double(73022) 101 30(15851) 3.0 Gal: Additional Tank ( 17-22 23-27 28-33 28-33 (Optional) 34-38 39-44 45-49 50-55 56-60 61-66 2 3 3 4 4 5 5 6 Double Multiple Multiple Multiple Multiple 3.0 Gal. Reg. Release 3.0 Gal. Additional Tank 1.5 Gal. Reg. Release 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 3.0 Gal. Reg. Release 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 3.0 Gal. Reg. Release (2) 3.0 Gal. Additional Tanks 1.5 Gal. Reg. Release • 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank Multiple 3.0 Gal. Reg. Release • 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank Multiple 1.5 Gal. Reg. Release 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank Multiple 3.0 Gal. Reg. Release 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank Multiple 1.5 Gal. Reg. Release 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tarek 3.0 Gal. Reg. Actuator' 3.0 Gal. Additional Tank 6 Multiple 3.0 Gal. Reg. Release 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank Based on 5 flow numbers for a 1.5 gal. system and 11 flow numbers for a 3.0 gal. system. See Pages 4-39 - 4-42 for exceptions. If tanks are mandolded, only a -double tank" nitrogen cartridge (Part No. 73022) can be used. "- If tanks are manifolded, either an LT -A-101-30 nitrogen cartridge (Part No. 29187) or a double tank cartridge (Part No. 73022) can be used. Double (73022) 101-30 (15851)" LT -20-.R (7032) 101-10 (15850) LT -A-101.30 (29187) 101-30 (15851)"' LT -30-R (5373) 101-20 (17492) LT -A-101-30 (29187) 101-30 (15851)' Double (73022) N/A Double (73022) 101-30 (15851) LT -A-101-30 (29187) 101-30 (15851r - Double (73022) 101-30 (15851)" LT -A-101-30 (29187) 101-30 (15851)"` LT -20-R (7032) LT -A-101-30 (29187) LT -A-101-30 (29187) LT -30-R (5373) LT -A-101-30 (29187) LT -A-101-30 (29187) Double (73022) LT -A-101-30 (29187) LT -A-101-30 (29187) Double (73022) LT -A-101-30 (29187) LT -A-101-30 (29187) 101-10(15850) 101-30 (15851r- 101-30 (15851r 15851r- 101-30(15851) 101-20 (17492) 101-30 (15851)- 101-30 (15851)*_ 101-30 (15851) 101-30 (15851)"* 101-30 (15851)*** 101-30 (15851)** 101-30 (15851)"* 101-30 (15851)"' ACCEPTED Without Comments ❑, As Noted In Red Per The Attached Letter i nese plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is subie t to errors and omissions which do not authorize violations of adopted standards and oroinances. The responsibility for the . adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings atter this date will void this.acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to fietd test and inspection by The Tukwila Fire. Prevention Bureau. Date: By: SKe700 I UKWILA FIRE. UENArc I ►vrr.►5r �. Please call: 575-4407 and give this job No. ef3 7 and exact address for shut. -inwn or restoration approval. NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. rattrrIT stc:',." • •1"itaitommi SHEET NUMBER SHEET TITLE SHEET INDEX FA -01 SYSTEM INFORMATION FA -02 TYPICAL DETAILS - WRING AND MOUNTING FA -03 FRE ALARM SYSTEM FLOOR PLAN FA -04 SYSTEM CALCULATIONS (GENEAL), RISER, SITE PLAN oar-aaa.a.aaaaa.a=aasaaamaaaraaa.aaaaa.a.aaaaa=aaaaaaaaaaaaaaaaa-aanaaaaaaaaaan eirif-r,.;r5T717,11[) 'q••41P' k4tSty Without Comments As Acted In Red Per The Attached Letter i nee plsnE. have been r' ;'d by Thr..; Tukwila Fire Previ.•••ntioni3u1ti .lr f....C.ei*:.,; .f...:•;1' 1'.:•;"! current city 1-:•••-...%:,.•-•J•,..,r-.:: 1. '..;...;3,..r..;:;.•:;, 1,0 *,:ft FOCti and i',;1"ni••••;:'..ie..:iciF.., sml-i•••••••;:i oc 1.'...;;I': ji,",i.ii:.tti...";.:: -:t:tIS of adopted I, • • •! t.,...,r;•:-.i:•ii.:1....!......-ui ,..•• !;0....ic,...:•••:•.-.„ i • ••.,. i • . .'.'i„.311,Sib,!.ty for the 1•••;.: '1•••;1';'...t.":-:•' '-:.;',..si-,•.• •',; i i;:' • ,.. ii •;,-;;Iy. ", .11. rlf,:•: (it.---,••....lgner. .!,;,;:;•:-.!...-.::;::.•:-:.,-.), d• ‘;'....; •:;:., •••,1:.......•:: ..:, .,-0...•(.:;::;(.z;+..Yings atter I.: !,i)1.. d..i•r::::- ,,,I,',': ,:....0 ii!...:.•;,... ..-..c.., ...,,;(:.: !-;.,';::i v!iii r.equire a •,;!,,.....y.:,!_11.;i.i.11.'.l.-.; Qr i..,-.:,;•::: ..-...', t.'..1...:.'!.'Y.1.,, f‘.:;1 ''...Elellt approval. nL-..1r:c.c•-:,....!...;-,-.:.:;, i:•• .i.....':-..;:•.1 i.i...) ficid test and inspection by U.,,k,ic... l'A L.'. CI •-•11,:..t1111C.:11 LAI; •..:CIU. Date: 5 6\--0 By: LmwILA FIRE DEPARTIVIE11 Hease call: 575-440Z and give this job and exact address for shut dk,wn or restoration approvair NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATION SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE • COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 ' FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO , #16 FPL/FPLR RED (JACKET), S STROBE CIRCUIT - FEED TWISTED PAIR. W/ SHIELD #12 FPL/FPLR RED (JACKET) 2S STROBE CIRCUIT - RETURN TWISTED PAIR \d/ SHIELD , #12 • FPL/FPLR ' RED (JACKET) '1 A ANNUNCIATOR TWISTED PAIR W/ SHIELD 1416 FPL/FPLR RED (JACKET) • V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) 2V SPEAKER CIRCUIT - RETURN TWISTED PAIR s 1414 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO 1418 FPL/FPLR RED (JACKET) X LOW LEVEL AUDIO TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED MB FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART - . • . - . NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600v 1112 AWG THHN/THWN .244 0.D. .0467 , TWO 600V 1114 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM , THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 'SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C. CHP. 9. TABLE 4. SHIELDED WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END GENERAL NOTES FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLEjNITIATING DEVICES UNTIL PREPGRAMMED WITH 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS. DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 'I 2. DETECTOR AND AUDIBLE CIRCUIT I-',OLARITY SHALL BE OBSERVED. I 3. AUDIBLE/VISUAL CIRCUIT WIRING IOUPERVISEO, NO PARALLEL BRANCHING IS PERMISSIBLE J,'11: 4. INSTALLATION SHALL BE IN STRICTHONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL' CODE(S) AND/OR AUTHORITY! HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONbUlfl WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBEIROS DIVISION. SYMBOLS LEGEND DEVICES ADDRESS. !i• • ., 6. DETECTORS SHALL NOT BE MOUNTLb IbIRECT AIR STREAM OF AIR SUPPLY OUTLOS. PER NFPA 72 2-3.5.1 •,. 7. WIRING SHALL BE PER PLAN WITHHRESPEbT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE,1L CONDUCTORS SHALL BE PERMANENTLY, • AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. , • : • • 8. INSTALLING CONTRACTOR SHALL RETURN .ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES I • „ 9. FOR ADDITIONAL INSTALLATION INS:1)R, OCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTROCTIONS. 10. THE 120vac POWER ELECTRICAL WR 'SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 ANIQ1. 760 OF, NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120voc POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE AL/6W 'TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPpEl). CEILING; WHICHEVER IS LESS. - 4 . 12. ALL MANUAL PULL STATIONS SHAW BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. I 13. ALL PANEL NUMBERS AND CIRCUITS ,WILL BE ON THE RECORD DRAWINGS SET. !!i!! 14. ALL 120VAC CIRCUITS ARE FROM IVICATED CIRCUITS !FROM THE EMERGENCY GENERATOR: 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF, ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE! AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. • DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAR-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS EOM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE'', WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT:CIRCUITS. • • .2 • 17. ALL WIRING SHALL BE METERED; VERIFIED TO BE CONTINUOUS, FREE, OF GROUND AND FREE OF SHORTS BETWEEN ONDUC.TORS 'AND OTHER CIRCUITS. PRIOR TO • FINAL EQUIPMb\IT :TRIM.: • . , ALL CABLES SHALL BE MARKED A,'INDICATEO, ON FIRE ALARM. RISER WITH A PERMANENT LABEL" AT ALL DEVICES, JUNCTION BOXES AND FACP. • 19 THE ELECTRICAL CONTRACTOR SHALL CLEAN :'•ALL DIRT AND DEBRIS FROM THE . , • OUTSIDE AND INSIDE OF THE FIRE.- ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. • • 20. DETECTORS MUST 'BE RATED -FOR.JEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. . .•. „ •• •. •• • 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTIROL, UNIT, !RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOINA ANO RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN 4 :T4 SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE,, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF ' 6.4.2.2.2 IS TO PROVIDE ADEQUATE. SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. ,THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) 'WHERE THE CABLE IS INSTALLED • QUANTITY 1 1 1 1 - 7 - SYMBOL ; DESCRIPTION MODEL MANUFACTURER BACKBOX. MOUNTING HEIGHT • • •, ; FIRE ALARM x! CONTROL PANEL FACP XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP ! FIRE ALARM FARA , REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS' . , REMOTE BOOSTER E) POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP •;•;,; • ).11 INTERFACE MODULE HTRI-R : SIEMENS WITH RELAY ,• " • 4S DEEP VERIFY IN FIELD , 1111;111.11; ' DUAL• INPUT • INTERFACE MODULE HTRI-D SIEMENS 4S DEEP ; VERIFY IN FIELD Hcp.1CONTROL POINT ,MODULE HCP SIEMENS 4S DEEP • VERIFY IN FIELD HZM1 REMOTE CONVENTIONAL HZM ;; • ZONE MODULE ..l!.! SIEMENS 4S DEEP VERIFY IN FIELD 1,1•• • LINEAR BEAM 0.•• .1 SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD A 1:H SMOKE DETECTOR HFP-11 W/ SIEMENS i=11:••• (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING DUCT SMOKE DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 BASEVV/ SIEMENS DB -1,1 4S DEEP VV/ 1G RING CEILING F;,. FIRE ALARM SPEAKER STROBE L C1i41 (CEILING MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. ,!!in: • FIRE ALARM „ SPEAKER STROBE (WALL MOUNT) s• • FIRE ALARM '"' SPEAKER STROBE C•E`: (CEILING MOUNT) SET -MC -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. 1;1 FIRE ALARM , • STROBE C I (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING L 1, FIRE ALARM 1!;!.• • • STROBE • (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. FIRE ALARM 9, SPEAKER k',11 • (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. FIRE ALARM SPEAKER '; • (WALL MOUNT) SET -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM !! FIRE ALARM le Or STROBE WP (WEATHERPROOF) SET -S17 -WP SIEMENS MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD MR • MULTI -VOLTAGE CONTROL RELAY MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD iv t' MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JBEIX FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD ® JUNCTION BOX F.B.O. F.B.O. N/A VERIFY IN FIELD . ABOVE FINISHED FLOOR N/A N/A N/A N/A .;; FURNISHED BY ; N/A ; OTHERS N/A N/A N/A NOT N/A N/A 7; APPLICABLE '• .:.! llL• N/A N/A • N/A UNLESS OTHERWISE NOTED N/A N/A N/A : N/A • WEATHERPROOF • DEVICE N/A N/A N/A N/A . i••• • AS BUILT ADD OR CHANGE N/A N/A N/A N/A AS BUILT GREEN! REMOVE N/A N/A N/A N/A BLUE , AS BUILT NOTES TO CAD N/A N/A N/A N/A ri ht 2006 b Guardian Securit 1.: 11 • 1 • • .• • 111, 1,1 , • ill! • • • •• .21 Lti efta *;• 1743 IST AVE: SO:, SEATTLE,INASHINGTON- 981314 U) z 0 UJ w UJ _J LU REV. BY: Z, DESCRIPTION SHOP DRAWINGS , DATE 5/5/08 • !•.'i .1 .••••• • . .e.;11. • i• ' GJ • 2008 Tukwila Fire S stems, Inc. All Ri hts Resered ‘CALE: 1 /8"= 1 ›i• DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE: 5/05/08 BACKROUND PLAN PROVIDED BY: ..JOB NUMBER:54520 SHEET FA -01 • t1 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS DUCT DETECTOR LOCATION p TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVIC JL END OF LINE DEVICE(3.6K 1/4W) - 0 SUPERVISED SWITCH GROUND -0 d 0 HTRI-R 0110 STATUS LED CO N to 0 0 0 N.O. COM N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVIOUS ADDRESSABLE DEVICE TO NEXT ADDRESSABLE E DEVICE L NOTE 1: VOLTAGE MAX, - CURRENT MAX. - CONT, RES. MAX. - MAX. CABLE LENGTH- C CLINE TO LINE)— C CLINE TO SHIELD) - MAX. LINE SIZE - MIN. LINE SIZE- OUTLET SAMPLING TUBE INLET SAMPLING—\ TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE MUSIC 1} -AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE{ (+) STOP IF LAST DEVICE (-)- FROM XLS CONTROL PANEL ❑R�¢)- PREVIOUS ADDRESSABLE DEVICE (-) RELAY CONTACTS (4.OA @ 125VAC) C4.0A @ 30VDC) 27 VDC 3,5 riA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0.02uF 0.04uF ' 14 AWG':. 18 AVG NOTE 2: ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTI❑N. loal ama .�TB1 • 1 2 3.4 5.6 ° HCP TB2 6 5 4(t 4 3 2 _27„ END, OF LINE DEVICE 0 C3.6K 1/4W) / / SUPERVISED / SWITCH GROUND 0 0 0 HTRI-D STATUS LED CO 0' t` 0 ,.I NOT USED, cno 0 0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) - 0 CND N AC C 0 0 PAD -3 0 00 0 INPUT •'' INPUT TROUBLE NAC1 NAC2 NAC3 .NAC4 AUX 1+ 1-.' 1 2+ 2-;2 . NC C NO + = '+ - + - +._ - • +- EA V MIWMILg 1011 24K TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE NAC -4 NAC -3 NAC -2 NAC -.1 i 'i FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP W, NOT USED REMOTE DEVICE LOOP 0- 0 0 FROM .XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY C'S' CABLE) END OF LINE.DEVIC, Er, FROM, FACP • 3.6K 1:/4,W)'' i!: CVCIIOE CIRCUIT) ' CABLE) UPER\%ISED, C'V' WITCH 470 OHMS EOL TSM -1 0 TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE NOW STROBE SPEAKER ( (-) STROBE EARTH GROUND ,(+)TO NEXT DEVICE OR >(-) STOP IF LAST DEVICE 0 STROBE SPEAKER (1,., ^) SPEAKERISRROBE AND STROBE WIRING LABEL SCALE ;iA SPEAKER STROBE OR STROBE ONLY 80- A.F.F. 4S DEEP BOX • w/. 1-1/2" EXTENSION RING (SPEAKER STROBE) • 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE ;�. TO NEXT, ;,DEVICE OR END OF LINE TO NEXT DEVICE OR END. OF LINE is NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERTIN TEMPERATU +32' F 0' C TO 100* F (NtC) HUMIDITY: RELATIVE HUMIDITY. NON -CONDENSING HFP-11 SMOKE DETECTOR ,\ FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (-) DATA IN (+) > DEVICE IS USED FOR AIR VOLOCITY APPUCATIONS OF 300-4000 FT IN WHEN USED IN CONJUNCTION WH DUCT HOUSINGS AD -11P OR AD-11XPR D8-11 4I { % STANDARD SM06NE DETECTOR BASE ,! REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT DEVICE i ( ) DATA OUT > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID --- CEILING SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION /--- CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTION BOX MOUNTED ON CEILINGI FLEX \. JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT / / / / / / / / 0 0 0 0 1L" TO NEXT DEVICE - CADDY BAR SMOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE:NONE SUSPENDED ILLUMINATED CEILING Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved J RELEASE/REVISIONS IREV. BY: I z Q DESCRIPTION SHOP DRAWINGS DATE 0o 0 i U") 2 CCCCC (/) :51 w Cn E5 z O (I)H rx:. cc (I) 8,4tt ZU co-- L 75 11: EL- - o CD OD SCALE: 1 /8"=1 J "eZC DRAWN. BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/05/08 BACKROUND PLAN PROVIDED BY: �OB NUMBER:54520 • ./ CSHEET FA -02 j UP TO ROOF TOP ADDRESSABLE RELAY ,E0L—S1 j202_ 11;21 21 7'-O" AFF I Q / r-0" \ 30 .‘-..; ------------ \''' '::'' I.:`! i,.. -.11.---7:----" -''...::' vi ' \ \ ‘ i ',1 \ ti 1 1 7; . i A 1 .--1 011 -; 1: .....:I. n 1 -, 1 -1,..., i i .0 \ ..: 0. 2S,2V j — \ ,i; 1 \ 1 AFF 9'-6" AFF (7) ...!_,„_;,,,_...., I .r.).,- t- It --1 „ \‘‘,.1--":::: ‘k, cl. 1 't.,3 fl.,... 1 ,.......›.. r.,.....y ‘ \ , \\N.. \\ ,,,,,t ,...„.\::,...,.;; . 7 ,:i.,"• ..; \ ,17 21-,,;\\\\.=\=,\trci,111.:1 .- ' n44\‘ 1 ' '. tr..-.'" ‘,. N.\, \-:.::.,'• '\-‘'`''\','o\.:. ' \ \.r" ' \,,,,, .:.n':, .,;, \ .......\ -. \ \•::‘\ ' :';,',...."+-, -i ,,;n'•,I,tn %!,.,.h,.....;..,.:..!---:n:n•i: .. 1i \ \1;,-'\ \. ---:— \1‘ 1‘' . 1 \,,...c: \ 1\ ;,I ,• >-- —. ,,\ 1 ,,,_,----\ \ \ c.; NORTH 12'-O" AFF D,I JOHNNY ROCKET'S WESTFIELD SOUTHCENTER MALL Ar SCALE 1/8":11 HvAc ROOF. DOWN TO REMOTE LED/TEST SWITCH '1 It • . FLAG NOTES: . I . FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE: FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS.(SEE SIEMENS INSTALLATION SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED. BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR. SIEMANS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLATOR FIRE SUPPRESION SYSTEM. FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS 5: uJ DESCRIPTION SHOP DRAWINGS uJ F— CO 0 11) < <<< ( 1 'ALE: 1 /8" =1 DRAWN BY: 'ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/05/08 BACKROUND PLAN PROVIDED BY: ,JOB NUMBER: 54520 SHEET FA -03 ,} •,-L*.- • t•T 6 ! I - Rh/ 11 film I Hum Hi mill IuJflunIu ‘c -54-••A 0 FT;7__,:s;.;-:-;\\\ - ---i , ---------'-'„ __ ___... \\ \\ ' - - - j. ,, -__...,, • ,, ___V .••-•=/•=\ -_--,--!, -- -k--- .:- -- \ , _- .,r , ' :?, 1 , \\1 \\\ \ \ --- - ----2f-.1. - o ..•,,,,,,, ,, \ --,--.--------15A.-. ‘qf---- ' NORTH PA 0 1 _ _ JOHNNY ROC 11 0 • P 0 t./ ----- , /---.., -1 •-•.. it- '".-.-------- -,,, .„:„..„, ",.. 0 /6 4 ' ' ".. ) ....,.!--1, 4' "'--[-- ----- I- \ t:..--'•;'" ------ ---- -//' . • . ----- -. -..- ----------------------- : \ ------L----------------- -- JOHNNY ROCKET'S WESTFIELD SOUTHCENTER MALL • R • . / • !!:!•:'• „- lJTh [N. 77 c SCALE 11374 P1 A `; , . • 2I DI D 30 STORE LEVEL 30 c 110 2S,2V FA-BLIX FACP EX . .• • .• SYSTEM CALCULATIONS BATTERY SIZING CALCULATION , JOHNNY ROCKETS Notification Appliance Circuit Detail JOHNNY ROCKETS • FACP ADD ONS WESTFIELD SOUTHCENTER MALL • SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations LLI PROJECT: JOHNNY ROCKET'S •Wire Resistance 1.62 _ ..._:. _...._ . . Panel: Date: May 8, 2008 CURRENT TOTAL= 429 CIRCUIT: S1 9 Current Load: Standby: Alarm: Current Load: Device Type Alarm Current Alarm Total Standby: Alarm: Voltage at EOL Circuit Total 0 SET -MC @15CD 64 0 Total Wire Resistance ( R ) 0.45 1 SET -MC @30CD 98 98 Device Type , Qty Amps • Total Amps Total SET -MC @75CD , Device Type Qty Amps Total Amps Total 1 SET -MC @110CD HFP-11 , 0.0022 0.0022 0.0023 (Total Cct Load) 0 - SET-HMC-C@115CD 318 0 ' Voltage Drop ( E ) AD2-P 1, 0 1 0.0635 0.0635. 0.064 0.064 , Main.System Board (E= I * R) 1 0.03 SET -HMC @135CD 0.03 0.030 0.030 s HTR -R 1 0.009600 0.0096 0.021 0.021 - 0 SET -MC @15CD (20.4 - E) 0.064 Z-MC@15CD : 64 0 HTRI-D 1 0.001600 0.0016 0.0035 0.004 1 Z-MC@30CD SET -MC @30CD SET -MC @75CD 98 1 0.098 0.098 0 ICP -B6 ; ;‘ 233 0 0.005 ' DEVICES= 3 TOTAL m A= 0.175 12 140 20.2054056 429 SET -MC ©110CD 1 0.233 0.318 0.233 Notification Appliance Circuit Detail , : 1 PROJECT , 1i,SET-HMC-C@115CD JOHNNY ROCKET'S Wire Resistance 2.58. . Panel: May 8,1,2008 CURRENT TOTAL= SET-HMC-C©135CD ,SET-HMC-C@185CD Date: CIRCUIT: 0.318 0.445 . • 1, 0.0747 Amps 0.0885 Amps Alarm Current Alarm iTotal Wire Size Wire Length Voltage at EOL Circuit Total 2 ,ZR -MC @15CD ZR -MC @30CD HCP : 1:8 3.6 i 0.064 0.098 0.0015 0.098 Total Wire Resistance ( R ) ., Standby Current Load: 0.0747 Amps For 24 Hours = 1.793 Amp -hours i ( WL * 2 )* (R/ft) 0 i 0 i Alarm Current Load: 0.0885 Amps For 5 Minutes= 0.007 Amp -hours 0 (Total Cct Load) 0.03 Amps 0.459 Amps l' , 4 Voltage Drop ( E ) 0.00 •0 ; 0 25% Derating=, 2.250 Amp -hours (E= I * R) Standby Current Load: ,, : ' 0.03 Amps For 24 Hours = 0.720 Amp -hours ' T - 20.40 , 0 0 0 (20.4 - E) 0 0 0 0 0 0 Alarm Current Load: 0.459 Amps 2 For 5 Minutes= 0.039 Amp -hours 25d, : . 20.390-51 3.61 Total System Current Load. 2.250 Amp -hours . , 25% Derating= 0.948 Amp -hours , Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.948 Amp -hours , ! , Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULATION , Z < Notification Appliance Circuit Detail DESCRIPTION WESTFIELD SOUTHCENTER MALL LLI PROJECT: JOHNNY ROCKET'S •Wire Resistance 1.62 _ ..._:. _...._ . . Panel: Date: May 8, 2008 CURRENT TOTAL= 429 CIRCUIT: S1 9 <1<<<< QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 0 SET -MC @15CD 64 0 Total Wire Resistance ( R ) 0.45 1 SET -MC @30CD 98 98 ( WL * 2 ) * (R/ft) 0 SET -MC @75CD 175 0 Total Device Load, Amps (I) 0.43 1 SET -MC @110CD 233 233 (Total Cct Load) 0 - SET-HMC-C@115CD 318 0 ' Voltage Drop ( E ) 0.19 0 SET-HMC-C@177CD 445 0 1 (E= I * R) 0 SET -HMC @135CD - 318 ; 0. s EOL Voltage 20.21 0 SET -HMC @185CD r 445 - 0 1 (20.4 - E) 0 , Z-MC@15CD : 64 0 1 Z-MC@30CD " 98 98 0 SET-MC-CW@110CD 233 0 DEVICES= 3 TOTAL m A= - 429 12 140 20.2054056 429 Notification Appliance Circuit Detail PROJECT WESTFIELD SOUTHCENTER MALL .• , , JOHNNY ROCKET'S Wire Resistance 2.58. Panel: May 8,1,2008 CURRENT TOTAL= 3.6 Date: CIRCUIT: SPEAKER CIRCUIT . . • QTY Device Type Alarm Current Alarm iTotal Wire Size Wire Length Voltage at EOL Circuit Total 2 70.7V 1/8 , : 1:8 3.6 i Total Wire Resistance ( R ) 1.29 0 0 ; 0 ( WL * 2 )* (R/ft) 0 i 0 • Total Device Load, Amps (I) 0.00 0 0 0 (Total Cct Load) 0 0 0 Voltage Drop ( E ) 0.00 •0 ; 0 (E= I * R) 0 ,, : ' 0 0 EOL Voltage .:: -,. - - 20.40 , 0 0 0 (20.4 - E) 0 0 0 0 0 0 DEVICES= 2 TOTAL m A= . 3.6 14 25d, : . 20.390-51 3.61 FAX (206) 628-4990 RELEASE/REVISIONS REV. BY: Z < DESCRIPTION SHOP DRAWINGS LLI 5/5/08 I-- < c) 9 <1<<<< z. 5 cwd- LLI cc - L7] w6w CC Oz z 8,< z < w-- z Li2 z LT o 80 -3 co w >- (/) 8"='i' 8"=1' 6ALE:- 1 DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE:5/05/08 BACKROUND PLAN PROVIDED BY: RISER DIAGRAM •VOLTAGE DR P CALCULATION NUMBER:54520 SHEET FA -04- Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved • [] Without Cornment8 ] A fdot8dInRed Per The Attached Letter nese plans ;,4,,/., 1 , . /l .., I:,. I./. The Tulp V,Iila Fire Prevention % ::.; _i .;; ..r. cl_irr:':nt city standard_.. ! and omission:. vic(.;tlon:; of ;adopted standcro,. SI',c.. r' - r :: .I iz;il:;<c r for the ,J ..� _},, ,.. -•.fgner. ail Cnqu[I{�' l!� - ,I' .. .. .. 'll: t_!1[� (.I �:�."�' Addition c . l ;::.,,_.. , kc: i lr:, : di wirlgs atter this cft' \•v.....:nd will require a resubmittal of ;.:,;!; : ;Jr.:ving:. for oubsequent approval. Final acc:*'pt<:ncr: i::.f.'Ijc:.ci to field test and inspection by Thtt Tukwila Fire Prevention Bureau. Date: ` o By: ? Weil stamps rni sL be inspected before pipe, is hung. Do not paint piping prior to hydrostatic tic t st • —Johnny Rockets General Notes -------------- VICINITY MAP (Suite#2600) SCALE: NTS 1. Western States Fire Protection to add new pendent heads new upright heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of aII sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. rLIKWILA FIRE DEPARTMEN1 Please call: 575.4407 and give this job No. OB -S-/c6 and exact address for shut. z:.1wnln or rF,,,toration aprrov$:lJ: EAST RISER DETAI I , HYDRAULIC REFERENCE ONLY NOT TO SCALE SYMBOL LEGEND 2 -WAY EARTHQUAKE BRACE 4 -WAY EARTHQUAKE BRACE NO. REVISIONS DESCRIPTION DATE HYDRAULIC REFERENCE POINT HANGER SYMBOL BRANCHLINE RESTRAINT 4" Existing Main Zone M-5 SYM. O (I SIN R5415 R5714 R5415 1'/i' Existing Branchline—t 1'h" x 1" Mech Tee CLG 0'-0" 4 lust 0 — ^+ Ti. .OW PLUG— Ct$ 1 / N - CLO 12'-0.2;HT1 , :,("4,;4:4- 3.0% ' CLG 12'-0" 1'A" x Mech Tee 1.13%' CLG-8'-Q" CLO 14'-0" .: Pocket + Gl CLG 9'-6" rPLUG1 Cooking Hood 1'N' Existing Branchline Ordinary Group II.0.20gpm/ft2 for 793.00ft2 Mech Tee 1'/i' x 1" FIRE SPRINKLER SYSTEM QTY. 10 2 4 Total = 16 K 5.6 5.6 5.6 SPRAY Pendent Pendent Pendent 1/8" =1'-0" Sprinkler Legend ORIF. Y2' W. FIN. White White White TEMP. 155°F 155°F 200°F MFR./MODEL Realible G4A Concealed F3QR Dry Pendent Realible G4A Concealed COOLER APPROVAL: Johnny Rockets Remote Area: Retail # 2600 CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY ciAss ORD HAZARD II MAX. COVERAGE per HEAD 130 DENSITY .20 GPM / Ft' for 793 SPRINKLER Reliable Model G4A ORIFICE 1/2" K= 5.6 Ft' FI' WATER FLOW INFORMATION: STATIC 140 PSI RESIDUAL 20 PSI FLOW 10900 GPM AT BASE OF RISER, SYSTEM REQUIRES: 288.73 GPM cas 48.57 PSI City of Tukwila At time of Design CONT. NO.: KS0334 DRAWN BY: Adam Kantner SPRK ON SHEET: SEE LEGEND SPRK. ON JOB: DATE 05/01/08 :TYPICAL FLEXABLE SPRINKLER CONNECTION: FLEXHEAD MOUNTING BRACKET PIPE NIPPLE SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS REDUCING FITTING SUSPENDED T -BAR GRID SPRINKLER HEAD CEILING TILE FLEXHEAD DETAIL NOT TO SCALE FIG. 909 SWIVEL SWAY BRACE FITTING 31B" MIK BOLT (2114' EMBED LENGTH) . F10.1000 "TALI- SWAY BRACE ATTACHMENT LINE PIPE LATERAL LINE RESTRAINTS NON -THREADED BRACE PIPE FIG.4A PIPE CLAMP FOR SWAY BRACE 3/8'KWIK BOLT ' (21/4" EMBED LENGTH) FIG. 909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT LATERAL BRANCHLINE RESTRAINT BRACE PIPE 9 I NON -THREADED BRACE PIPE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE Hanger No. 07C HILTI Kwik Bolt III HILTI Kwlc Batt II Drilled Anchor i Cut Rod Lgth Rounded to Nearest Inch Rod Coupling All Thread Rod • Swivel Ring Concrete Construction q. • Bottom of Concrete to Center Line of Pipe Pipe Note on Plan Note on Plan: Hanger Number and 'A' Dimension HANGER DETAIL NOT TO SCALE VICINITY MAP DETAIL NOT TO SCALE Western States Fire Protection Company 7102 180th AVE NE, STE A-105 - REDMOND, WA- 98052 Lic. //: WESTESF136QF -- L. LUUO Tukwila Fire -? 5d 77//-9 w• •z O Adam Kantner Westwood Contractors fY 0 U Q' .CC 1— z 0 U WESTERN STATES FIRE PROTECTION COMPANY -OFFICES LOCATED ALBUQUERQUE/AUSTIN/DALLAS/DECATUR/DENVER fDULUIHIHOUSTON /KANSAS CITY LAS VEGAS /MINNEAPOLIS /PHOENIX/PORTLAND/ RAPID CITY/ ST. PAUL/SALT LAKECITYISEATTLE Phone: 425-881-0100 Fax 425-881-3030 Johnny Rockets 2600 Southcentner Mall ��-�/ Tukwila ,Wa 98188 FIRE SPRINKLER SYSTEM SHEET FP -1 OF. •1 Johnny Rockets _______________ General Notes VICINITY MAP (Suite#2600) SCALE: NTS 1. Western States Fire Protection to add new pendent heads new upright heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. EAST RISER DETAIL HYDRAULIC REFERENCE ONLY NOT TO SCALE 4" Existing Main Zone M-5 1'A" Existing Branchline 1 1'A" x 1" Mech Tee ry11+wa" CLG lYz"x1".DN 1x11 - Me;h-Tee\To FLEX ,/ �O PICU 0 L PLUG CLG 12'-0" j CLG 7'-0" Lx r14— °I 9 )IN I 1'A" Existing Branchline x 1" Mech Tee CLG 14'-0/0 Pocket 45. o'R‘o``y t CLG 9'-6" 'PLUG; Cooking Hood Ordinary Group II.0.20gpm/ft2 for 793.00ft2 Mech Tee 1'A" x 1" FIRE SPRINKLER SYSTEM 1/8" = 1'-0" COOLER Johnny Rockets Remote Area: Retail # 2600 CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY cLAss ORD HAZARD II MAX. COVERAGE per HEAD 130 DENSITY .20 GPM / Ft' for 793 SPRINKLER Reliable Model G4A ORIFICE 1/2" K= 5.6 Ft' Ft' WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 PSI FLOW 10900 GPM AT BASE OF RISER, SYSTEM REQUIRES: 288.73 GPM © 48.57 PSI ' At time of Design TYPICAL FLEXA13LE SPRINKLER CONNECTION FLEXHEAD MOUNTING BRACKET PIPE NIPPLE SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS ^� ^ REDUCING FITTING SUSPENDED T -BAR Gt2ID SPRINKLER HEAD CEILING TILE axs:**F1,S*a.% FLEXHEAD DETAIL NOT TO SCALE 3/9' KWIK BOLT .�.- (2 1k' EMBED LENGTH) FIG.909 SWIVEL SWAY BRACE FITTING Teta FIG. 1000 "FAST CLAMP" SWAY BRACE ATTACHMENT LATERAL LINE RESTRAINTS NON -THREADED BRACE PIPE FIG. 4A PIPE CLAMP FOR SWAY BRACE 3/9' KWIK BOLT (21k' EMBED LENGTH) FIG.909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT LATERAL BRANCHLINE RESTRAINT LP BRACE PIPE lo NON -THREADED BRACE PIPE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE Hanger No. 07C HILTI Kwik Bolt III Cut Rod Lgth Rounded to Nearest Inch N N 1 HILTI Kwik Bok 11 / Drilled An hor �`..-ri.( 1 Concrete Construction Rod Coupling Swivel Ring Pipe cL Bottom of Concrete to Center Line of Pipe Note on Plan Note on Plan: Hanger Number and 'A' Dimension HANGER DETAIL NOT TO SCALE VICINITY MAP DETAIL NOT TO SCALE Johnny Rockets w z 0 Adam Kantner 0 Westwood Contractors CONTRACTOR: SYMBOL LEGEND REVISIONS Sprinkler Legend 2 -WAY EARTHQUAKE BRACE NO. DESCRIPTION DATE SYM. SIN QTY. K SPRAY ORIF. FIN. TEMP. MFR./MODEL 4 -WAY EARTHQUAKE BRACE R5415 10 5.6 Pendent z White 155°F Realible G4A Concealed APPROVAL: City of Tukwila HYDRAULIC REFERENCE POINT .4 R5714 2 5.6 Pendent %Z' White 155°F F3QR Dry Pendent CONT. NO.: KS0334 R5415 HANGER SYMBOL 4 Total = 16 5.6 Pendent %' White 200°F Realible G4A Concealed DRAWN BY: Adam Kantner BRANCHLINE RESTRAINT SPRK. ON SHEET: SEE LEGEND SPRK. ON JOB: DATE: 06/19/08 Western States Fire Protection Company 7102 180th AVE NE, STE A-105 - REDMOND, WA - 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY • OFFICES LOCATED ALBUQUERQUE /AUSTIN/DALLASI DECATUR/DENVER/DULUTH/HOUSTON/KANSAS CITY LITS VEGAS /MINNEAPOLIS / PHOENIX /PORTLAND /RAPID CITY /ST, PAUL /SALT LAKE CITYI SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 Johnny Rockets 2600 Southcentner Mall Tukwila ,Wa 98188 FIRE SPRINKLER SYSTEM SHEET FP -1 OF 1