Loading...
HomeMy WebLinkAboutPP - 2600 SOUTHCENTER MALL FC-4 - SBARRO - PERMITS AND PLANS2600 SOUTHCENTER MALL FC -4 FOOD COURT ASSOCIATED PERMITS 08-F-182 08-F-154 08-S-162 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Sbarro 2600 Southcenter Mall FC -04 Permit No.: 08-S-162 Date: May 5, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'/z inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. • Job Number: KS0344 Report Description: Ordinary Group II Jb Job Number KS0344 Design Engineer Adam Kanter Job Name Sbarro State Certification/License Number WESTESF136QF Address1 2600 Southcentner Mall AHJ City of Tukwila Address 2 Job Site Southcenter Mall City Tukwila std. Wa Zip Code 98188 Drawing Name FP-1.cad :f3:0MOtkNO '''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''' Most Demanding Spnrilder Data 5.6 K -Factor 20.00 at 12.755 Occupancy Ordinary Group II Hose Allowance Al Source 250.00 0.20gpm/ft2 Area of Application 895.00ft2 (Actual 895.26ft2) Additional Hose Supplies Node Flow(gpm) Total Hose Streams 250.00 System Flow Demand 295.72 Total Water Required (Including Hose Allowance) 545.72 Maximum Pressure Unbalance In Loops 0.000 Msaimum Velocity Above Ground 20.18 between nodes 71 and 74 Maximum Velocity Under Ground 1.12 between nodes 1 and 238 Volume capacity of Wet Pipes 1851.81gal Volum. capacity of Dry Pipes 1.35ft3 Number Of SprinIders Calculated 13 Coverage Por Sprinlder 100.00ft2 suppl Node Hose Flow (gpm) Static (psi) Residual Flow (psi) (gpm) 1 250.00 140.000 20.000 1 10900.00 Available Total Demand (psi) (gpm) 139.529 1 545.72 Required (psi) Safety Margin (psi) 52.358 87.171 Contractor Number KS0344 Contact Nemo Adam Kantner Contact Title Project Manager Contractor Name Western States Fire Protection Phone 425.881.0100 Extension Address 1 7102 180th Ave Ne, Suite A-105 FAX 485.736.9032 Address 2 Smaa City Redmond State WA Zip Code 98052 Web -Site M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 04/30/2008 10:09:50AM Page 1 Job Number: KS0344 Report Description. Ordinary Group II Device Actual Flow (gpm) Minimum Flow (gpm) K -Factor (K) Pressure (psi) Sprinkler 113 24.65 20.00 5.6 19.375 Sprinkler 112 24.11 20.00 5.6 18.535 Sprinkler 114 24.94 20.00 5.6 19.837 Sprinkler 106 23.28 20.00 5.6 17.289 Sprinkler 107 23.47 20.00 5.6 17.562 Sprinkler 111 23.73 20.00 5.6 17.960 Sprinkler 109 23.47 20.00 5.6 17.570 Sprinkler 102 20.06 20.00 5.6 12.829 i Sprinkler 101 20.00 20.00 5.6 12.755 Sprinkler 105 21.63 20.00 5.6 14.922 Sprinkler 103 21.27 20.00 5.6 14.421 Sprinkler 110 23.62 20.00 5.6 17.789 Sprinkler 104 21.49 20.00 5.6 14.724 _ :% Most Demanding Sprinkler Data • © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 04/30/2008 10:09:57A M Page 2 Job Number: KS0344 Report Description: Ordinary Group II Node Elevation(Foot) Fittings Pressure(psi) Discharge(gpm) 19 18-3 PO(8-0) 28.148 22 18-3 PO(5-0) 25.192 28 18-3 PO(5-0) 23.531 30 18-3 PO(5-0) 23.380 46 18-3 PO(8-0) 28.169 51 18-3 PO(5-0) 23.096 52 18-3 PO(5-0) 21.712 54 18-3 PO(5-0) 21.429 56 18-3 E(2-0) 21.273 66 18-3 2T(5-0) 16.146 71 18-3 PO(8-0) 28.232 74 18-3 PO(5-0) 22.290 76 18-3 PO(5-0) 18.977 77 18-3 PO(5-0) 18.207 79 18-3 PO(5-0) 17.763 83 18-3 E(2-0) 17.698 108 18-3 2T(26-4) 29.445 161 -16-1 P0(37 -8Y2) 45.181 238 -14-1% BFP(-4.500) 48.906 272 -16-1 LtE(16-0) 45.219 113 10-5% Spr(-19.375) 19.375 24.65 112 9-0 Spr(-18.535) 18.535 24.11 114 12-10% Spr(-19.837) 19.837 24.94 106 12-10 Spr(-17.289) 17.289 23.28 107 10-5% Spr(-17.562) 17.562 23.47 111 12-10 Spr(-17.960) 17.960 23.73 109 10-5%2 Spr(-17.570) 17.570 23.47 102 12-10 Spr(-12.829) 12.829 20.06 101 12-10% Spr(-12.755) 12.755 20.00 105 10-5% Spr(-14.922) 14.922 21.63 103 10-5 Spr(-14.421) 14.421 21.27 110 12-10 Spr(-17.789) 17.789 23.62 104 12-10 Spr(-14.724) 14.724 21.49 1 -22-0 S 52.358 295.72 M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 04/30/2008 10:09:58A M Page 3 Job Number: KS0344 Report Description: Ordinary Group 11 Pipe Type Diameter Flow Velocity HWC Friction Loss Length Eq. Length Total Length Pressure Summary Downstream Upstream Elevation Discharge K -Factor Pt Pn Fittings 4is Route 1 DR 1.049 Q=20.00 7.42 C=120 0.130131 35-0 Pf 5.727 101 12-10Y2 q=20.00 K=5.6 12.755 Spr(-12.755) 9-0 Pe -2.336 66 18-3 16.146 2E(2-0), T(5-0) 44-0 Pv AO 1.049 Q=40.06 14.87 C=120 0.470386 1-0 Pf 2.831 66 18-3 16.146 5-0 Pe 76 18-3 18.977 PO(5-0) 6-0 Pv BL 1.610 Q=104.44 16.46 C=120 0.343833 9-7Y2 Pf 3.313 76 18-3 18.977 Pe 0.000 74 18-3 22.290 9-7'A Pv BL 1.610 Q=128.06 20.18 C=120 0.501356 3-10 Pf 5.943 74 18-3 22.290 8-0 Pe -0.000 71 18-3 28.232 P0(8-0) 11-10 Pv CM 4.260 Q=295.72 6.66 C=120 0.020633 32-5Y2 Pf 1.213 71 18-3 28.232 26-4 Pe 0.000 108 18-3 29.445 T(26-4) 58-9% Pv CM 6.357 Q=295.72 2.99 C=120 0.002937 133-10 Pf 0.855 108 18-3 29.445 157-2 Pe 14.881 161 -16-1 45.181 5fE(12-7), BV(12-7), CV(40-3), 291-0 Pv GV(3-9Y2), PO(37-8'/2) FM 8.329 Q=295.72 1.74 C=120 0.000788 16-5Y2 Pf 0.038 161 -16-1 45.181 32-0 Pe 0.000 272 -16-1 45.219 fE(16-0), LtE(16-0) 48-5Y2 Pv FM 10.420 Q=295.72 1.11 C=120 0.000265 28-2% Pf 4.529 272 -16-1 45.219 83-0 Pe -0.842 238 -14-1% 48.906 4LtE(16-0), BV(19-0), BFP(-4.500) 111-2% Pv UG 10.400 Q=295.72 1.12 C=140 0.000201 110-2 Pf 0.045 238 -141'/2 48.906 111-7 Pe 3.407 1 -22-0 52.358 E(35-1), 3LtE(25-6), S 221-9Y2 Pv iso Route 2 DR 1.049 Q=20.06 7.45 C=120 0.130832 34-2% Pf 5.653 102 12-10 q=20.06 K=5.6 12.829 Spr(-12.829) 9-0 Pe -2.336 66 18-3 16.146 2E(2-0), T(5-0) 43-2Y2 Pv Jilt Route 3 DR 1.049 Q=21.27 7.89 C=120 0.145776 35-2 Pf 6.731 103 10-5 q=21.27 K=5.6 14.421 Spr(-14.421) 11-0 Pe -3.389 79 18-3 17.763 3E(2-0), PO(5-0) 46-2 Pv BL 1.610 Q=42.90 6.76 C=120 0.066286 6-81/2 Pf 0.445 79 18-3 17.763 Pe -0.000 77 18-3 18.207 6-8Y2 Pv BL 1.610 Q=64.39 10.15 C=120 0.140500 5-6 Pf 0.770 77 18-3 18.207 Pe -0.000 76 18-3 18.977 5-6 Pv 6+ Route 4 DR 1.049 Q=21.49 7.98 C=120 0.148607 32-2 Pf 5.819 104 12-10 q=21.49 K=5.6 14.724 Spr(-14.724) 7-0 Pe -2.336 77 18-3 18.207 E(2-0), PO(5-0) 39-2 Pv Route 5 DR 1.049 Q=21.63 8.03 C=120 0.150459 34-11 Pf 6.159 105 10-5% q=21.63 K=5.6 14.922 Spr(-14.922) 6-0 Pe -3.383 83 18-3 17.698 3E(2-0) 40-11 Pv BL 1.610 Q=21.63 3.41 C=120 0.018679 3-5Y2 Pf 0.065 83 18-3 17.698 Pe 79 18-3 17.763 3-5Y2 Pv Route 6 DR 1.049 Q=23.28 8.64 C=120 0.172411 32-2Y2 Pf 6.759 106 12-10 q=23.28 K=5.6 17.289 Spr(-17.289) 7-0 Pe -2.336 52 18-3 21.712 E(2-0), PO(5-0) 39-2Y2 Pv BL 1.610 Q=70.23 11.07 C=120 0.164981 8-4Y2 Pf 1.383 52 18-3 21.712 Pe -0.000 51 18-3 23.096 8-4Y2 Pv BL 1.610 Q=93.96 14.81 C=120 0.282710 9-11Y2 Pf 5.073 51 18-3 23.096 8-0 Pe 46 18-3 28.169 P0(8-0) 17-11 V2 Pv CM 4.260 Q=167.66 3.77 C=120 0.007221 8-10 Pf 0.064 46 18-3 28.169 Pe 0.000 71 18-3 28.232 8-10 Pv ss. Route 7 DR 1.049 Q=23.47 8.71 C=120 0.174927 34-6Y2 Pf 7.094 107 10-5% q=23.47 K=5.6 17.562 Spr(-17.562) 6-0 Pe -3.383 56 18-3 21.273 3E(2-0) 40-6Y2 Pv © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 04/30/2008 10:09:59A M Page 4 Job Number: KS0344 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Friction Loss Length Eq. Length Total Length Pressure Summary Downstream Elevation Discharge K -Factor Upstream Pt Pn Fittings BL 1.610 Q=23.47 3.70 C=120 0.021717 7-2%2 7-2'V2 Pf Pe Pv 0.156 0.000 56 18-3 54 18-3 21.273 21.429 BL 1.610 Q=46.94 7.40 C=120 0.078304 3-7% 3-7'% Pf Pe Pv 0.283 0.000 54 18-3 52 18-3 21.429 21.712 so Route 8 DR 1.049 Q=23.47 8.71 C=120 0.174997 32-4%2 9-0 41-4%Pv Pf Pe 7.239 -3.380 109 10-5Y2 q=23.47 K=5.6 54 18-3 17.570 21.429 Spr(-17.570) 2E(2-0), PO(5-0) Route 9 DR 1.049 Q=23.62 8.77 C=120 0.177013 31-71,4 7-0 38-7Y2 Pf Pe Pv 6.837 -2.336 110 12-10 q=23.62 K=5.6 74 18-3 17.789 22.290 Spr(-17.789) E(2-0), PO(5-0) Si Route 10 DR 1.049 Q=23.73 8.81 C=120 0.178588 32-10 9-0 41-10 Pf Pe Pv 7.471 -2.336 111 12-10 q=23.73 K=5.6 51 18-3 17.960 23.096 Spr(-17.960) 2E(2-0), PO(5-0) .fii+ Route 11 DR 1.049 Q=24.11 8.95 C=120 0.183871 37-11 11-0 48-11 Pf Pe Pv 8.994 -3.997 112 9-0 q=24.11 K=5.6 28 18-3 18.535 23.531 Spr(-18.535) 3E(2-0), PO(5-0) BL 1.610 Q=48.76 7.68 C=120 0.084005 15-9 4-0 19-9 Pf Pe Pv 1.661 -0.000 28 18-3 22 18-3 23.531 25.192 2LtE(2-0) BL 1.610 Q=73.70 11.61 C=120 0.180396 8-4'/2 8-0 16-4'/2 Pf Pe Pv 2.957 -0.000 22 18-3 19 18-3 25.192 28.148 PO(8-0) CM 4.260 Q=73.70 1.66 C=120 0.001578 12-9% 12-9%2 Pf Pe Pv 0.020 0.000 19 18-3 46 18-3 28.148 28.169 6810 Route 12 DR 1.049 Q=24.65 9.15 C=120 0.191566 31-7 7-0 38-7 Pf Pe Pv 7.389 -3.383 113 10-5%2 q=24.65 K=5.6 30 18-3 19.375 23.380 Spr(-19.375) E(2-0), P0(5-0) BL 1.610 Q=24.65 3.88 C=120 0.023782 6-4 6-4 Pf Pe Pv 0.151 -0.000 30 18-3 28 18-3 23.380 23.531 Route 13 DR 1.049 Q=24.94 9.26 C=120 0.195787 32-3Y2 7-0 39-3%2 Pf Pe Pv 7.691 -2.336 114 12-10'V2 q=24.94 K=5.6 22 18-3 19.837 25.192 Spr(-19.837) E(2-0), PO(5-0) t*gWIHi1(::1p6:::6Ef115fdiY85::Trf::ti154 0:0ii1y:::>::::>::>:<>:<::i:<1 Actual Inside Diameter 4.87 Value Of C 100 Multiplying Factor 0.713 130 140 1.16 1.33 150 1.51 Schedule 40 Steel Pipe Inside Diameter / = Factor M.E.P.CAD, Inc. AutoSPRINKO VR5 v5.2.6 04/30/2008 10:09:59AM Page 5 Job Number: KS0344 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Friction Loss Downstream Upstream Elevation Discharge K -Factor Pt Pn Fittings Length Eq. Length Total Length Pressure Summary AO Arm -Over BL Branch Line CM Cross Main DN Drain DR Drop DY Dynamic FM Feed Main FR Feed Riser MS Miscellaneous OR Outrigger RN Riser Nipple SP Sprig ST Stand Pipe UG Underground Diameter Elevation Flow Discharge Velocity Pressure Length Friction Loss HWC Pt Pn Pf Pe Pv Inch Foot gpm gpm fps psi Foot psi/Foot Hazen -Williams Constant Total pressure at a point in a pipe Normal pressure at a point in a pipe Pressure loss due to friction between points Pressure due to elevation difference between indicated points Velocity pressure at a point in a pipe ALV AngV b BaIV BFP BV C cplg Cr CV DeIV DPV E EE Eel Ee2 FDC fE fEE flg FN fT g GIoV GV Hose HV Hyd LtE mecT Noz P1 P2 PIV PO PrV PRV red S sCV Spr St T Tr U WirF WMV z Alarm Valve Angle Valve Bushing Ball Valve Backflow Preventer Butterfly Valve Cross Flow Turn 90° Coupling Cross Run Check Valve Deluge Valve Dry Pipe Valve 90° Elbow 45° Elbow 11W Elbow 22W Elbow Flow Device Fire Department Connection 90° FireLock(TM) Elbow 45° FireLock(TM) Elbow Flange Floating Node FireLock(TM) Tee Gauge Globe Valve Gate Valve Hose Hose Valve Hydrant Long Turn Elbow Mechanical Tee Nozzle Pump In Pump Out Post Indicating Valve Pipe Outlet Pressure Relief Valve Pressure Reducing Valve Reducer/Adapter Supply Swing Check Valve Sprinkler Strainer Tee Flow Turn 90° Tee Run Union Wirsbo Water Meter Valve Cap (1 © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 04/30/2008 10:09:59AM Page 6 Job Number: KS0344 Report Description: Ordinary Group II ACA Supply at Node 1 Pressure, psi 111111111111111111111111111111111111111111111111111111111111111111_1_11111111111111111111111111111i 11 Static Pressure 140.000 ,545.72 295.72 with hose @ 52.358 streams System demand curve 10900.00 @ 20.000, lllllltl l 1111111 11 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 I I 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 t.1 010022 3300 4400 5500 6600 7700 Water flow, gpm 8800 9900 11000 Hydraulic Graph Supply at Node 1 Static Pressure 140.000 Residual Pressure 10900.00 @ 20.000 Available P,.ssureTinw of Test 139.529 @ 545.72 System Demand 295.72 @ 52.358 System Demand (Including Hos. Allowance) 545.72 @ 52.358 ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 04/30/2008 10:10:OOA M Page 7 Job Number: KS0344 Report Description: Ordinary Group 11 (�y ©M.E.P.CAD, Inc. 411 AutoSPRINK® VR5 v5.2.6 04/30/2008 10:10:01 AM Page 8 nm. I VIv GIVhK le fueS (SyUU 04/23 '08 13:34 N0.599 03/03 TITLE? ANSUL R-102 FIRE SYSTEM LAYOUT PROJECT? SBARRO SOUTHCENTER MALL DATE? 04/22/08® c6mci-r - S � Fcl DWG' 15119—A I-Flikv?A. 9eies ' 3 1kf4.. STMYflo) tt PMc DST" lex 1(9" N w� O rda ��.....� e O 54' 69' 2V (2) 245 245 (2) <2) 11 YI �o -s� 10111011 PAM . • • .'ter •� 1) ANSUL R-102 FIRE SYSTEM 2) ONE TANK SYSEM (3 GALLDN> 3) 3/8' BLACK IRON PIPING W/3/8' S,S. APPLIANCE DROPS 4) MECHANICAL GAS VALVE = (ADVISE) A004 REMOTE MOUNTED 1 REGULATED RELEASE Basin ras 2 0-30,1 3c iLbA iii/moi 0 0 ()lei ael 3/3 5w* ivs+ct l ( "'rem e,gf',hcti;ts�►C►• Ail Arel COKE 4/411 +V✓r vevh Ik,-:or 5.ys4 -. — U L ce vviive, t 4 MEW/010u MS iiALVE R- Fuca S IOW- I r: ; ` 2008 Tukwila Fire Received Time Apr. 23. 12:38PM SECTION IV — SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-28 REV.5 4-1-06 Nozzle Application Chart The following chart has been developed to assist in calculating the quantity and type of nozzle required to protect each duct, plenum, or appliance. NOTICE This chart is for general reference only. See complete details for each type of hazard. Hazard ► Duct or Transition (Single Nozzle) Duct or Transition (Single Nozzle) Duct or Transition (Dual Nozzle) Electrostatic Precipitator (At Base of Duct) Plenum (Horizontal Protection) ► Plenum (Horizontal Protection) Plenum (Vertical Protection) ► Fryer (Split or Non -Split Vat) Fryer (Split or Non -Split Vat) ► Fryer (Split or Non -Split Vat)* Fryer (Non -Split Vat Only) Maximum Hazard Dimensions • Length — Unlimited Perimeter — 50 in. (127 cm) Diameter —16 in. (40.6 crn) Length — Unlimited Perimeter —100 in. (254 cm) Diameter — 31 7/8 in. (81 cm) Length — Unlimited 2 Perimeter -150 in. (381 cm) Diameter — 48 in. (122 cm) Individual Cell 1 Length —10 ft (3.1 m) Length — 6 ft. (1.8 m) Width — 4 ft. (1.2 m). Length — 4 ft. (1.2 m) Width-4ft(1.2m) Maximum Size (without drip board) 14 in. (36 cm) x 15 in. (38 cm) Low Proximity Maximum Size (without drip board) 141 /2 in. (37 cm) x 14in. (36cm) Medium Proximity Maximum Size (without drip board) 15 in. (38 cm) x 14 in. (36 cm) High Proximity Medium Proximity Maximum Size (without drip board) 19 1/2 in. (49.5 cm) x 19 in. (48.2 cm) High Proximity Low Proximity Maximum Size - (without drip board) 18 in. (45.7 cm) x 18 in. (45.7 cm) . High Proximity Minimum Nozzle Nozzle Quantity Heights 1 1 1 1 1 1 1 1 For multiple nozzle protection of single fryers, see detailed information on Pages 4-12 through 4-14. 13-16 in. (33 — 41 cm) 16 — 27 in. (41 — 69 cm) 27 — 47 in. 20 — 27 in. 21 —34 in. 13-16 in. 25 — 35 in. (64-89 cm) Nozzle Part No. 430912 419337 419337 419334 419335 430192 419336 419336 419342 419342 419339 419340 419338 419342 419338 Nozzle Tip Stamping — Flow No. 1W 2W 2W 1 /2N 1N 1W 1W 1W 290 290 230 245 3N 290 3N Nozzle Application Chart (Continued) Hazard Fryer (Non -Split Vat Only)` Fryer (Split or Non -Split Vat) Fryer (Split or Non -Split Vat) Range Maximum Hazard Dimensions Maximum Size (with drip board) 21 in. (53 cm) x 14 in. (36 cm) (Fry Pot must not exceed 15irtx14in. (38 cm x 36 cin)) High Proximity Medium Proximity Maximum Size (with drip board) 25 3/8 in. (64.4 cm) x 19 1/2 in: (49.5 cm) (Fry pot side must not exceed 191 /2 (49.5cm) x19in. (48.2 cm) High Proximity. Low Proximity Maximum Size (with drip board) 18 in. (45.7 cm) x 27 3/4 in. (70.5 cm) High Proximity Minimum Nozzle Nozzle Quantity Heights 1 Maximum Size (with drip board) 14in. (36cm) x 21 in: (53 cm) 1 Low Proximity Maximum Size (with drip board) 141/2 in. (37 cm) x 261/2 in. (67 cm) Medium Proximity Longest Side 32 in. (81 cm) Area — 384 sq. in. _ (2477 sq. cm) Longest Side 28 in. (71 cm) Area — 336 sq. in. (2168 sq. cm) Longest Side (High Proximity) 1 28 in. (71 cm) Area — 672 sq. in. (4335 sq. cm) Longest Side (Medium Proximity) 32 in. (81 cm) Area — 768 sq. in. (4955 sq. cm) Longest Side (Low Proximity) 36 in. (91 cm) Area—1008.sq. in. (6503 sq. cm) For multiple nozzle protection of single fryers, see detailed information on Pages 4-7 through 4-11. SECTION IV — SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-29 4-1-06 REV 5 27 — 47 in. 20-27 in. 21-34 in. 1 —16 in. 25-35 in. (64-89 cm) 13-16in. {33 —41 cm) 16— 27 in. (41 — 69 cm) 30 —40 in. (76 = 102 cm) Nozzle Part No. 419339 419340 419338 419342 419338 419342 419342 419335 40 48 in. 419333 (102 -122 cm) (With Backshelf) 40.— 50 in. (102 -127 cm) 30-40 in. (76 — 102 cm) 15 — 20 in. (38 — 51 cm) 419340 419341 419342 Nozzle Tip Stamping — Flow No. 230 245 3N 290 3N 290 290 1N 1F 245 260 290 ., v wruv Yieoulatea Mecnanicai Helease Assembly (3.'0 gallon — Part No. 79290 or 1.5 gallon. — Pan No. 79291) contains the regulated release mechanism, agent tank. expellant gas hose for agent tank hookup. and.enclosure knockouts. to facilitate installing actuation, piping; expellant piping; detection system; and additional equipment. This regu- lated release assembly is used in single, double. and multiple. tank systems and must be mounted to a rigid -surface.. The release mechanism can be used to interconnect both the actu- ation and expellant gas lines as required per system design. The regulator is designed to allow a constant flow of gas into the tank at 100 psi (690 kPa) when the system is actuated. In single, double. and multiple -tank systems, the provided expel- lant cas hose connects the agent tank to the bottom outlet of the regulator. In double and multiple -tank system configurations, the back outlet of the regulator is used es an expellant gas feed for one additional tank -enclosure or tank -bracket hookup: The enclosure contains the required knockouts to facilitate this cor- rection. If a pressure switch is to be attached to the regulator, additional fittings are required. • The tank is mounted within the enclosure. The tank contains an adaptor/tube assembly with a burst disc union: The burst disc helps prevent siphoning of the agent up the pipe due to signifi- cant temperature fluctuations in the area where the •tank is located. The tank is mild steel and. under normal conditions, requires hydrostatic testing .every twelve years. • The agent tank is shipped uncharged and must be filled with 1.53 gallons (5.8 L) or 3.06 gallons (11.6 L) of only ANSULEX Low pH Liquid Fire Suppressant during installation. The detection and additional equipment required per system design are connected to'the release mechanism. The enclosure contains knockouts to facilitate detection and additional hookups. The system can b= actuated automatically, or manually. Auto- matic actuation occurs when a fusible link within the detection -system separates in a fire'condition. Manual actuation of the system occurs when personnel pull on the remote manual pull station pull ring. EXTINGUISHING AGENT ANSULEX Low pH Liquid Fire Suppressant (1.5 gallon — Part No. 79694 or 3.0 gallon — Part No. 79372) is a potassium -based - solution .designed for fast knock -down and suppression of grease -related fires. The agent is shipped in plastic containers which provide one complete tank charge. Agent storage life expectancy is twelve years. The distributor must record the batch numbers and date of shipment receipt to be filed with each instal- lation record. Total Flow No' 1-5 Tank Quantity 1 6-11 1 Type of System Single Single ANSUL Type of Hardware • 1.5 Gal. Reg. Release 3.0 Gal. Reg. Release ELECTRICAL SWITCHES - L0CfarrCP :IP W.f.( '..P11/TD. The electrical switches are intended for .use with electric gas valves, alarms, contactors, lights, contractor supplied electric power shut-off devices :and other electrical devices that are designed to shut off or tun: on when the systemis actuated. Switches are available in kits: One Switch Kit, Part•No.423878; Two Switch Kit, Part No. 423879, Three Switch Kit; Part No. 423880, arid Four Swifch Kit, Part No. 423681. Each switch has a set of single -pole, double -throw contacts rated of 21 amp, 1 HP 125, 250, 277 VAC or 2 HP, 250, 277 VAC. Mounting hardware is provided with each kit. R-102 RESTAURANT FIRE SUPPRESSION SYSTEM (Standard UL 300 Listed) No=fe identification Chart Nozzle Nole Nozz{--? Tome Part No Sta moino 1W Nozzle 419336 1W 1WSS Nozzle 417333 1W 1N Nozzle 419335 1N 1 NSS Nozzle 417332 1N 1/2N Nozzle 419334 1/2N 3N Nozzle 419338 3N 2W Nozzle 419337 2W 2WH Nozzle 78078 2WH Noz Fiov 1 1 1 1 1/2 3 2 2 230 Nozzle 419339 230 2 245 -Nozzle 419340 245 2 260 Nozzle 419341 260 2 290 Nozzle 419342 290 2 2120 Nozzle 419343 2120 2 1F Nozzle 419333 1F 1 1100 titnaE -43Og12 1 1 c 0 1 Nitrogen Cartridge Required LT -20-R (7032) LT -30-R (5373) Carbon Dioxide Cartridoe Required 101-10 (15850) 101-20 (17492) ( f`osT 1741 SIPsNis 0i\\ ,S\J'L(ttRSrr3 ?o (o0, -c_ ) Uma-rP NW) 511 �. FLA:) 5 LGIN ! . iS -55 T 1 ACCEPTED Without Comments As Noted In Red Per The Attached Letter i nese plans have been revioweo by The Tukwila Fire Prevention Bureau for corkrmance with current city standards. Accawance ...:L.;biact to errors and omissions which -6-,)n uthorize -violations of adopted standaros and The refiponsibil4y for the adequacy of With tne designer. Additions, docs oi IOflS hl) these drawings atter this date will void tni.:.; acceptance lnd will require a resubmittal of revised drawings for subsequent approval. sinal acceptance is subject to field test and inspection by ; he Tukwila Fire Prevention Bureau. late: — By: toKWILA FIRE DEPARThibill Please call: 575-440 and give thisiob No. -) ind exact address for shut' 441wn or restoration approval SHEET INDEX SHEET NUMBER SHEET TITLE FA -01 SYSTEM INFORMATION FA -02 TYPICAL DETAILS - WIRING AND MOUNTING FA -03 FIRE ALARM SYSTEM FLOOR PLAN FA -04 SYSTEM CALCULATIONS (GENERAL), RISE, SITE PLAN 1 E 58 pvwvwnt3A.10.1.0" Without Comments As Noted In Red Per The Attached Letter 'nese plans have been reviw .d by The Tukwila Fire-' Prevention Burn.au fof c4:' ,. t:..•..• _ ti current city stand31.d:6. Ac.:_ ; 1r+t;� �: I rk.:< and ornissionti a(: 001 aa. U .. 'ii ,7 ..'-.:•;(.;(1S of adopted :ifann .1•ra` e. I(j i} �;i l.:�1•• .. I I . C (i'-al?.1Ay for the =tihcaU s `, f ; .:?..•.:Ir r=:.... ; t• tri:: signer. iCi!;IitiUr'Iza, 4:'.!t_.,;iii1. `.;I ;'•_ 'I':;I„ui, ,. ii... rt:ar.winysafter ,lis duty c.); + ;il , .::C.: ;;!_.:l !:. r, i Viiit require a esubmittal of revie::lt tot s:b:.i ;quent approval. final acc+r'ptbncEi is subject to fi.=•Id test and inspection by The Tukwila Fire, Prevention Bureau. Date: /(1("1 S` \ rUKWILA FIRE DEPARTIVIEM Please call: 575.4402 and give this job No. 0% -L-19)-)- a, ' exact address for shut or restoration approval: 1 NOTICE A completed, signed, Tukwila Gore Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE. COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) 2S STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #12 FPL/FPLR ..RED (JACKET), A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) 2V SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATI❑N LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL%FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED; #18 FPL/FPLR RED (JACKET). UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TW❑ #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO 1414 , FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END GENERAL NOTES FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPGRAMMED WITH DEVICES ADDRESS. NG 1. NUMBERS ADJACENT TO DEVICE SYMBOLDENOTE DEVICE CIRCUIT/ADDRESS: DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS, SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. ,,CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE' IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES.: g_ FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK'; SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 .AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED :AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL. BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED -CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. , DETECTORS .THAT HAVE BEEN. INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN FULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. • 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING :BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4,2.2.2 ALL STYLES OF CLASS A CIRCUITS. USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (LE., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM •(1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 1 1 2 SYMBOL DESCRIPTION SYMBOLS LEGEND MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD MCP, CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD B LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS ® (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING DUCT SMOKE ®p" DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. 4S DEEP BOX 80" A.F.F. W/ 1-1 /2" EXT. TO BOTTOM E. C FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING L FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING FIRE ALARM STROBE (WALL MOUNT) FIRE ALARM SPEAKER (CEILING MOUNT) ZR -MC -W SIEMENS SET -CW SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. 4S DEEP BOX CEILING W/ 1-1/2" EXT. FIRE ALARM SPEAKER (WALL MOUNT) SET -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM FIRE ALARM STROBE (WEATHERPROOF) SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR MULTI -VOLTAGE CONTROL RELAY MR -201 /C AIR PRODUCTS 4S BOX VERIFY IN FIELD 0 MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD O JUNCTI❑N BOX F.B.❑. F.B.❑. N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A F.B.❑. FURNISHED BY OTHERS N/A N/A N/A N/A N/A. NOT APPLICABLE N/A N/A N/A N/A U.❑.N, UNLESS OTHERWISE NOTED N/A N/A N/A N/A WP WEATHERPROOF DEVICE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A Fig eft 2008 Tukwila Fire --W-2.515)13 ,'75 -- Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved RELEASE/REVISIONS Hcs LU DESCRIPTION SHOP DRAWINGS AHJ LU F --- C21 co 0 0 0 z W cc (i) CC 2 O� Q W cc 1 -I co O) w z wa oz 1_ D Q 0 LL 0 N ~ 0 1... 0 z ILI (i) >m rr � (SCALE: 1 /8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE:5/05/08 BACKROUND PLAN PROVIDED BY: .OB NUMBER:54541 ( SHEET FA -01 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT bMDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS DUCT DETECTOR LOCATION p TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT 0 LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE A_ c STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVIC y END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH O 0 0 GROUND HTRI-R STATUS LED 00 CO 0 0 0 N.0 COM N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL `ABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE' DEVICE TO NEXT ADDRESSABLEf DEVICE L - NOTE 1: VOLTAGE MAX. - CURRENT MAX. - CONT. RES, MAX. - MAX. CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN. LINE SIZE- N❑TE 2: ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTI❑N. MUSIC OUTLET SAMPLING TUBE INLET SAMPLING, TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE=NONE LLI-AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE f STOP IF LAST DEVICE l(-) FROM XLS CONTROL PANEL OR ¢) PREVIOUS ADDRESSABLE DEVICE t-) RELAY CONTACTS (4.0A @ 125VAC) (4.0A @ 30VDC) 27 VDC 3.5 r1A DURING POLLING 10 OHMS 200 FT. (18 AWG)' 0.02uF 0.04uF 14 AWG 18 AWG A TB1 123456 HCP A 65 4321 END OF LINE, � 1 DEVICE (3.6K 1/4W) SUPERVISED SWITCH GROUND '� 0 re) d- 0 HTRI-D OSTATUS LED CO 0` 0 FRONT MEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE 1 DEVICE LOOP ! 0 FROM XLS CONTROL PANEL OR (O> PREVIOUS ADDRESSABLE DEVICE (-)> NOT USED 0 NOTE: FOR ADDITIONAL . SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE, SUPPRESSION SYSTEM INTERFACE) 0 CND N AC le I 0 PAD -3 0 INPUT INPUT TROUBLE. NAC1 NAC2 NAC3 NAC4 AUX 1+ 1-..1, .2+ 2— 2 .NC .0 NO + =• + + + — + — Ll MIRIAM 24K TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE END OF LINE DEVICE 3.6K 1/4W) UPERVISED 1 �WITCHH Ij j FROM REMOTE POWER SUPPLY ('S' CABLE) FROM`FACP. (VOICE CIRCUIT) ('V' CABLE) 470 OHMS �IN EOL TSM -1 • .L= : 0 TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE: NONE (+) (_) STROBE SPEAKER (+) (-) (STROBE) EARTH GROUND.: —.(+)TO NEXT; DEVICE OR l >(-) STOP IE LAST DEVICE J (-10 STROBE-) SPEAKER (+) (-) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE 2 NAC -4 2 NAC -3 NAC -2 2 NAC -1 SPEAKER STROBE OR STROBE ONLY BO" A.F.F: • L T r: u 4S DEEP BOX W/ 1-1/2_ ; EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) ,TO NEXT DEVICE OR END OF LINE J)TO NEXT DEVICE OR t, END OF LINE SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERA11IN TEMPERAVE +32' F 0- C TO 1017 F 3Ei C) JIUMIDITY: O- 9 X RELATIVE HUMIDITY. NON -CONDENSING HIP -11 SMOKE DETECTOR —� DEVICE IS LISTED FOR AIR VOLOOTY APPLICATIONS OF 300-4000 FT/MIN Y4IEN USED IN CONJUNCTION VON DUCT HOUSINGS AD -11P OR AD-11XPR D8-11 STANDARD SMOKE BASE DETECTOR 00 0' 0 ittg z_ 0' 0' . I . 00, N 0 0 N d .' FROM PREVIOUS ADDRESSABLE DEVICE OR POVER SOURCE DATA IN (-) >- DATA IN (+) > REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE > ( ) DATA OUT > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID CEILING SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION •\.., CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE _ JUNCTI❑N BOX—, MOUNTED ON \\` CEILING. FLEX JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT / / / / / 0 0 f TO NEXT DEVICE 0 0 ----CADDY BAR SMOKE DETECTOR SMOKE DETECTOR MOUNTING SUSPENDED ILLUMINATED CEILING SCALE=NONE Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved J UJ F-. U) z 0 LU Ot LU LU J LU Et { z Ia DESCRIPTION SHOP DRAWINGS AHJ w co 0 u7 LO 0 z 0Y (0 CM ‘CALE : 1/811=11 DRAWN BY: (.ANDERSON DESIGNED BY:. R.VEZZANI DATE:5/05/08 BACKROUND PLAN PROVIDED BY: 1.9B NUMBER:54541 /- SHEET FA -02 ,• s • ••• !!.; NORTH r • !s'!' • • • !!!, •I 1' I... :1 • SBARRO WESTFIELD SOUTHCENTER MALL tt If 3 • FLAG .!!! • ; . • • • Ittf NOTES: FIELD 'LOCATE RELAY MODULE FOR' :BACK! GROUND MUSIC. INTERFACE. FIELDH LOCATE SIEMENS DUCT DETEOOR ON RETURN SIDE OF ALLLyAv UNITS.(SEE SIEMENS ;INSTALLATION SUBMITTAL FOR LEIcATiciN GUIDELINES AND, FA=02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY .ELECTRICAL CONTRACTOR. • , ! 111;10',,;•;,!!' ,,•!!11 fo!,:1.!!!,;!; ! 1! 1, t: t • fl • .•.!,!1! ; I • • ! 3.1,, • ,Z4 Iftm CD • 1'0 ON 0` CO (\-1 0 F-- 0 \CD c) c\J r LL < < LIT LIJ ft 1,0 TEL. (206) 622-654.5 I, I t RELEASE/REVISIONS-----_•• z , uJ DESCRIPTION - SHOP DRAWINGS AHJ c0 0 z Copyright ! 2006 b Guardian Securit S stems, Inc. All 12. hts Reserved (SCALE: 1/8'1=1' DRAWN. BY: [ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/05/08 BACKROUND PLAN PROVIDED BY: \LOB NUMBER:54541 2 SHEET, FA -03 N N.. N. o 0 • .3 0 I; 1\'' 0, .1004:2°' ......... \ 0 ,' \ 0\,. L., , \ \ 0 .----0,3 \\\ 0, k r,,k \ .. .. _ •-•c-A, A -.I "Tr'°J.° (s'r .., )..' ;!, \,, \ \ ,. .• - \ 0 r 'N .0,00- 1 1 rt \ t \ S 3•000., . .. __ _ • r; - --°- °- _...,....,100000---r° , \‘0, ,...-- 0 ..:_:._•_-_-_-_-_::::----- --T: .., • r -• - 1,..'_..,....;,..,„....--• .1-:,,,,,,\._. % ,‘,, ,.--.,,I.\ \ \ \ V.1 \ J-- .. I.- sk .,. % , y t„, ----------1-Y • \ 0 is\ NORTH rr 3r- A I, SBARRO VIESTFIELD SOUTHCENTER MALL •-s • / -00 • • -00- \ • SCALE 11324 30 30 EOL -S1 20.31V RISER DIAGRAM t! •,'• . ''•;' ' '• I SYSTEM CALCULATIONS SBARRO FACP ADD ONS SBARRO Current Load: SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations •.1' ; ! ' h 11 Standby: Alarm: Current Load: Device Type HFP-11 AD2-P1 Qty HTR.: -R! HTRI-D ICP -B61' Standby Current, Load: 1 1 Amps Standby: Alarm: 0.0022 Total 0.0022 Amps Total Device Type Qty Amps Total 0.0023 Amps Total 0.0635 0.009600 0.001600 0.005 0.0635 0.0096 0.064 0.064 Main System Board •1 0.03 0.03 0.030 • 3 ;01:j 0.030 1. 0.021 0.0035 0.021 0.0731 Amps 0.085 Amps 0.0731 Amps For 24 Hours = 1.754 Amp -hours SET -MC @15CD SET -MC @30CD SET -MC @75CD SET -MC @110CD SET-HMC-C@115CD SET-HMC-C@135CD SET-HMC-C@185CD ZR -MC @15CD 0.064 ZR -MC @30CD HCP Alarm Current Load: 0.085 Amps For 5 Minutes= 2 0.098 0.196 I.; I ' '.1! • 0.175 1:1 111.. 0.233 0.318 0.318 1 1 0.445 0.064 0.098 0.0015 '!, 11 II! •• ; t• i '•' 0.007 ; . • ;11.111. 1.-e • •" I 1, ; I BattyPair to be Used: • s't 10, Total System Current Load: 12VDC 25% Derating= Amp -hours ; • 0 • 0.03 Amps 0.226 Amps • • ii' 1! 2.202 Amp -hours Standby Current Load: Alarm Current Load: 0.03 • 0.226 Amps Amps For 24 Hours = For 5 Minutes= 0.720 0.019 2.202 Amp -hours Amp -hours 7AH 010' • ; 3 ; Total System Current Load: Battery Pair to be Used: 12VDC BATTERY SIZING CALCULATION • • 00010 ,.• ; Notification Appliance Circuit Detail •;- • 25% Derating= Amp -hours 0.924 0.924 7AH PROJECT: iWESTFIELD SOUTHCENTER MALL •1 • I,; • • . • • . • „ Panel: : SBARRO 1VVire Resistance 1.62 Date: I May 7, 2008 CURRENT TOTAL= 196 CIRCUIT:1S1 i11 .13, . +,' , 11t - . ' aTY DeviceType Alarm Current AlarmTotal WreSize WireLength VoltageatEOL CircuitTotal 0 SET -MC @15CD 64 0 , Total Wire Resistance ( R ) 0.451 4 -4 ;, t-- )2 SET -MC @30CD 98 196 , (WL *2 ) * (Rif) I,,II , i 1 0 SET -MC @75CD 175 Oi , , I , . i , Total Device Load, Amps (1) 1 0.20i 1 0 SET -MC @IIOCD 233 3 01. 3 I (Total Cct Load) • 0 1SET-HMC-C@115CD • 318 iVoltage Drop ( E ) 0.091 ' 0000 SET TCC-I-IMC 50-C@ 177CD ..., ,.. , • 0.0 , (E = I * R) 135CD 318 ; i , EOLVolage ..: . • 1i,11,111,I1, 20: 3 0 SET-HMC@185CD 445 01 i 1 (204-E) . 01 i , , I; , @, 1 i0 SET-MC-CW@110CD 233, 1',I1i,1i1;: DEVCES=2 TOTAL m A=1 1961 12 i 140 -i, - 2031109441 196! ; 1. t • ; ; 1 4 - 1 . Notification Applance Circuit D' etail , PROJECTWESTFIELDSOUTHCENTERMALL Panel:I- SBARRO -- • Date: May 7, 2008 •CIRCUIT:SPEAKER CIRCUIT iWira Resistance 2.58 ; CURRENT TOTAL=36 3 / , I QTY 1 Device Type Alarm Current Alarm Total I Wire Size I Wire Length ,:',Voltage at EOL i Circuit Total i ' 1 1 ; 1 f -3i•• • ,s--- • --1-- 3- ,- . -`, - - ,.•, 1.81 3.6 3 3 f '3 0 . i 1 2 70.7V 1/8 , L! !Total Wire Resistance ( R ) 0 00 , 0 .i. ii 0 oi 1 --i ( WL * a) * (Rf) 1 0 0 1 , 1 Total Device Load, Amps (1) 0.00 1 0 0 0 ,tII (Total , Cct Load) 10 0 0 I I 1VoItageDroptE) 1 0.00, 61 1 ':;:i .1':',:: . 0 1• 1 i 0 • - . • 0; ... 0 ; 0 :01 .... . ; 1'.' ... i.:,.• 1 • ,•. ,...?. , ; ,..tL! 0 1 . 01 01* • .- . : z • . ;:; .3.. .. . - ,.1.• - - ;. ,.. 0 t . ; 0 .01 . . It .;;! 1-1::, ' -- ! : - I i i- .1._ .i.„ • . DEVICES=12 'i TOTAL m A= 36i :140 1 , . r - 3 - . • ; 0,, - i:,,: , ..1. • - 20.4 3.6 I ....: 3 ; •. . • . ,, . 3 •3 • 1 (E= 1*. EOL Voltage • 20.401 VOLTAGE DROP CALCULATION • .1: Copyright 2006 by Guardian Security Amp -hours Amp -hours -1111 Amp -hours Amp -hours 1'1 t .1: • '0, .!, • ,• ' • ;11,1".",.• . °I 10 ." • , 1 11 (206) 622-6545 _J LLJ RELEASE/REVISIONS-- CD uJ DESCRIPTION cr 0 .;!•:;;.1 t, • 0 , DRAWN BY: LAN DERSON DESIGNED BY: R.VEZZANI DATE: 5/05/08 BACKROUND PLAN PROVIDED BY: Systems, Inc. All Rights Reserv .11 t • -... 001 FA -04 General Notes VICINITY MAP (Suite#2600) SCALE: NTS 1. Western States Fire Protection to add new pendent heads new upright heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft' maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. EAST RISER DETAIL, HYDRAULIC REFERENCE ONLY NOT TO SCALE Existing Main o 24 O 5 cgdef * -0 9 Ordinary Group II.0.20gpm/ft2 for 895.00ft2 LG 12'-0' CLG 12'40' 0 A — III 11 _s CLG I9 11.011. u Existing Branch Lines v 3-a'%. e 0 ranch Lines CLG 10'-5' I I- 111 1'/a :5-9 11 I 100 11211-" !' Existing = 41 Mech Tee ptug_ I 0 1 Existing Main A es LG FIRE SPRINKLER SYSTEM 1/8" = 1'-0 >aC2_ 0 0 Without Comments T -I 0 / Noted Red As In T /ad Per The Attached Letter I hese plants hav2 i' ..:r; 1( ry F..., .',::d by The- ilmfil e revention t umr.iI.1 ':.r -:,...:,,.;s":: i... >. with cu ent city standards.: (:(a,:h: IL :i: t/.; errors a omissions wh:c' i :r. , ,.i.,..,,,, _I(,!.h -i:a : violations o — ~ of Standards and :i' , ?' Ii/t=: ri''."'pcnsie)ilityfor the adequacy of ,....1',.:,,,ii , .;li',' %•. ,1, tfie designer. Additions, d._)i' , 1:,'.. . .,';-. .:f . !': l.i:c e drawings atter `i his d ',:e viii i:,.,,- :.i,', ..: ;i•. _:a• , r,d will require a -esuhn itt of f .:`ir,'-' ? ; ..-'/.jnc—r ` t se . .,,.. for .1.1.:, quent approval. e t i Sbarro Remote Area: Retail # 2600 CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY a/ass ORD HAZARD II MAX. COVERAGE per HEAD 130 FN • DENSITY .20 GPM ! Ft' for 895 Ft' SPRINKLER Reliable Model G4A ORIFICE 1/2" K=55.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 P.SI FLOW 10900 GPM AT BASE OF RISER, SYSTEM REQUIRES: 295.72 GPM @ 48.91 PSI ' At time of Design Weld stam inspected approval. ICE TYPICAL FLEXABLE SPRINKLER CONNECTION PIPE NIPPLE SPRINKLER BRANCHLIKE FLEXABLE CONNECTING` HOSE IN STANDARD LENGTHS MOUNTING BRACKET REDUCING FITTING SUSPENDED T -BAR GRID CEILING TILE FLEX HEAD DETAIL NOT TO SCALE FWV0L SWIVEL SWAY BRACE FITTING 'BRACE PIPE 5/9' KWIK BOLT —(2114' EMBED LENGTH) FIG.1000 " —"FAST CLAMP' ' SWAY BRACEATTACHMENT \ LINE PIPE • LATERAL LINE RESTRAINTS NON -THREADED BRACE PIPE must be before Ow. is int piping -incl aoctp....incr. i5 : , i s *_Yi, l.:) fir., -1d tett and inspection by file. Tukwila i'i;:i i-re`io—,ii.ion Bureau. [Date: -57---5---°g By: fel , .1 1 3 5 7 9 TUKWILA FIRE DEPARTMENT, Please call: 575.4407, and give this job No.05 '-1 a- ._ • and exact address for shut• Town or rt st:.ration approval, SYMBOL LEGEND REVISIONS 2 -WAY EARTHQUAKE BRACE NO. DESCRIPTION DATE 4 -WAY EARTHQUAKE BRACE Sprinkler Legend SYM. SIN QTY. K SPRAY ORIF. FIN. TEMP. MFR./MODEL R5415 9 5.6 HYDRAULIC REFERENCE POINT R5415 4 5.6 Pendent Pendent %Z' White 155°F G4A Concealed APPROVAL: City of Tukwila 1,E White 200°F G4A Concealed HANGER SYMBOL Total = 13 CONT. NO.: KS0344 DRAWN BY: Adam Kantner BRANCHLINE RESTRAINT SPRK ON SHEET: SEE LEGEND SPRK. ON JOB: DATE 04/30/08 FPS. 4A PIPECLAMP FOR SWAY BRACE n LATERAL BRANCHLINE RESTRAINT FIG. 909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT a/9' KWIK BOLT (2 1/4' EMBED LENGTH) BRACE PIPE gl°g:1 NON -THREADED BRACE PIPE LATERAL BRANCHLINE RESTRAINT NO TO SCALE Hanger No. 07C HILT! Kwik Bolt III Cut Rod Lgth Rounded to Nearest Inch N // HILT! Kwik Bok 11 Dnl(edAnchor 1 i C( 1 \-1" / Concrete Construction / Rod Coupling All Thread Rod Swivel Ring Bottom of Concrete to Center Line of Pipe Note on Plan Note on Plan: Hanger Number and '/IV Dimension HANGER DETAIL NOT TO SCALE VICINITY MAP DETAIL NOT TO SCALE Western States Fire Protection Company 7102 180th AVE NE, STE 4105 - REDMOND, WA - 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY -OFFICES LOCATED ALBUQUERQUE/AUSTIN/DALLAS!DECATUR/ DENVER /DULUTH /HOUSTON /KANSAS CITY LAS VEDAS/MINJEAPOLIS/PHOENIX/PORTLAND /RAPID CITY/ST. PARR/SALT LAKE car/SEATTLE Phone: 425-881-0100 Fax 425-881-3030 2008 • Tukwila Fire on ce,A4- -x'/77 (10' caroti )/ itfra $ David A. Chute 305.09-2697 ;t Vik Nt —wailD Q (0 U)• w Adam Kantner 0 co .m 5, 0 L U CONTRACTO Sbarro 2600 Southcentner Mall —A e--4 tl Tukwila ,Wa 98188 FIRE SPRINKLER SYSTEM SHEET FP -1 OF 1 SYMBOL LEGEND General Notes VICINITY MAP (Suite#2600) SCALE: NTS 1. Western States Fire Protection to add new pendent heads new upright heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. 'Lh 'yflt.dt?N tM1 EAST RISER DETAIL HYDRAULIC REFERENCE ONLY NOT TO SCALE REVISIONS Existing Main Existing Main 0 Ordinary Group II.0.20gpm/ft2 for 895.00ft2 CLG 12'-0' r—CLG 12'-10' CLG 9'-0' Existing Branch Lines • ranch Lines CLG 10'-5" LO 12'-0" FIRE SPRINKLER SYSTEM 1/8" = 1'-0 Sprinkler Legend Existing =ranch tiee Sbarro Remote Area: Retail # 2600 CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY cLAss ORD HAZARD II MAX. COVERAGE per HEAD 130 DENSITY .20 GPM / Ft' for 895 SPRINKLER Reliable Model G4A Ft' F1' ORIFICE 1/2" K. 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 PSI FLOW 10900 GPM AT BASE OF RISER, SYSTEM REQUIRES: 295.72 GPM @ 48.91 PSI ' At time of Design 2 -WAY EARTHQUAKE BRACE N0. DESCRIPTION DATE SYM. SIN QTY. K SPRAY ORIF. FIN. TEMP. MFR./MODEL 4 -WAY EARTHQUAKE BRACE R5415 9 5.6 Pendent Z White 155°F G4A Concealed APPROVAL: City of Tukwila HYDRAULIC REFERENCE POINT R5415 4 5.6 Pendent %2 ' White 200°F G4A Concealed CONT. NO.: KS0344 Total = 13 DRAWN BY: Adam Kantner HANGER SYMBOL BRANCHLINE RESTRAINT SPRK. ON SHEET: SEE LEGEND SPRK. ON JOB: DATE: 06/19/08 r -LD TYPICAL FLEXABLE SPRINKLER CONNECTION FLEXHEAD MOUNTING BRACKET PIPE NIPPLE • SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS REDUCING FITTING SIJSPENDED T -BAR GRID SPRINKLER HEAD CEILING TILE FLEXHEAD DETAIL NOT TO SCALE FIG.909 SWIVEL SWAY BRACE FITTING KWIK BOLT .-(21/4' EMBED LENGTH) BRACE PIPE FIG.1090 �"--- "FAST CLAMP" SWAY BRACE ATTACHMENT LINE PIPE LATERAL LINE RESTRAINTS NON -THREADED BRACE PIPE FIG. 4A PIPE CLAMP FOR SWAY BRACE 3/9' KWIK BOLT (2 1/4' EMBED LENGTH) FIG. 909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT LATERAL BRANCHLINE RESTRAINT BRACE PIPE td NON -THREADED BRACE PIPE LATERAL BRANCHLIN RESTRAINT NOT TO SCALE Hanger No. 07C HILTI Kwik Bolt III / HILTI Kwik Boll 11 Drilled Anchor• 5 /L \'\L / Rod Coupling All Thread Rod Cut Rod Lgth Rounded to Nearest Inch Swivel Ring Pipe Concrete Construction Bottom of Concrete to Center Line of Pipe Note on Plan Note on Plan: Hanger Number and 'A' Dimension HANGER DETAIL NOT TO SCALE VICINITY MAP DETAIL NOT TO SCALE Western States Fire Protection Company 7102 180th AVE NE, STE A-105 - REDMOND, WA - 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE/AUSTIN/DALLAS/DECATUR/DEM/ER/DULUTH/HOUSTON/KANSAS CITY LAS VEGAS /MINNEAPOLIS /PHOENIX/PORTLAND 1 RAPID CITY/ ST. PAUL /SALT LAKE CITY/SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 Sbarro 2600 Southcentner Mall Tukwila ,Wa 98188 FIRE SPRINKLER SYSTEM 0 2 i (t3 (1) IY w 0 Adam Kantner 2 0) c7) N 0) a SHEET FP -1 OF 1 2600 SOUTHCENTER MALL FC -4 FOOD COURT ASSOCIATED PERMITS 08-F-182 08-F-154 08-S-162 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Sbarro 2600 Southcenter Mall FC -04 Permit No.: 08-S-162 Date: May 5, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'/z inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. • Job Number: KS0344 Report Description: Ordinary Group II Jb Job Number KS0344 Design Engineer Adam Kanter Job Name Sbarro State Certification/License Number WESTESF136QF Address1 2600 Southcentner Mall AHJ City of Tukwila Address 2 Job Site Southcenter Mall City Tukwila std. Wa Zip Code 98188 Drawing Name FP-1.cad :f3:0MOtkNO '''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''' Most Demanding Spnrilder Data 5.6 K -Factor 20.00 at 12.755 Occupancy Ordinary Group II Hose Allowance Al Source 250.00 0.20gpm/ft2 Area of Application 895.00ft2 (Actual 895.26ft2) Additional Hose Supplies Node Flow(gpm) Total Hose Streams 250.00 System Flow Demand 295.72 Total Water Required (Including Hose Allowance) 545.72 Maximum Pressure Unbalance In Loops 0.000 Msaimum Velocity Above Ground 20.18 between nodes 71 and 74 Maximum Velocity Under Ground 1.12 between nodes 1 and 238 Volume capacity of Wet Pipes 1851.81gal Volum. capacity of Dry Pipes 1.35ft3 Number Of SprinIders Calculated 13 Coverage Por Sprinlder 100.00ft2 suppl Node Hose Flow (gpm) Static (psi) Residual Flow (psi) (gpm) 1 250.00 140.000 20.000 1 10900.00 Available Total Demand (psi) (gpm) 139.529 1 545.72 Required (psi) Safety Margin (psi) 52.358 87.171 Contractor Number KS0344 Contact Nemo Adam Kantner Contact Title Project Manager Contractor Name Western States Fire Protection Phone 425.881.0100 Extension Address 1 7102 180th Ave Ne, Suite A-105 FAX 485.736.9032 Address 2 Smaa City Redmond State WA Zip Code 98052 Web -Site M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 04/30/2008 10:09:50AM Page 1 Job Number: KS0344 Report Description. Ordinary Group II Device Actual Flow (gpm) Minimum Flow (gpm) K -Factor (K) Pressure (psi) Sprinkler 113 24.65 20.00 5.6 19.375 Sprinkler 112 24.11 20.00 5.6 18.535 Sprinkler 114 24.94 20.00 5.6 19.837 Sprinkler 106 23.28 20.00 5.6 17.289 Sprinkler 107 23.47 20.00 5.6 17.562 Sprinkler 111 23.73 20.00 5.6 17.960 Sprinkler 109 23.47 20.00 5.6 17.570 Sprinkler 102 20.06 20.00 5.6 12.829 i Sprinkler 101 20.00 20.00 5.6 12.755 Sprinkler 105 21.63 20.00 5.6 14.922 Sprinkler 103 21.27 20.00 5.6 14.421 Sprinkler 110 23.62 20.00 5.6 17.789 Sprinkler 104 21.49 20.00 5.6 14.724 _ :% Most Demanding Sprinkler Data • © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 04/30/2008 10:09:57A M Page 2 Job Number: KS0344 Report Description: Ordinary Group II Node Elevation(Foot) Fittings Pressure(psi) Discharge(gpm) 19 18-3 PO(8-0) 28.148 22 18-3 PO(5-0) 25.192 28 18-3 PO(5-0) 23.531 30 18-3 PO(5-0) 23.380 46 18-3 PO(8-0) 28.169 51 18-3 PO(5-0) 23.096 52 18-3 PO(5-0) 21.712 54 18-3 PO(5-0) 21.429 56 18-3 E(2-0) 21.273 66 18-3 2T(5-0) 16.146 71 18-3 PO(8-0) 28.232 74 18-3 PO(5-0) 22.290 76 18-3 PO(5-0) 18.977 77 18-3 PO(5-0) 18.207 79 18-3 PO(5-0) 17.763 83 18-3 E(2-0) 17.698 108 18-3 2T(26-4) 29.445 161 -16-1 P0(37 -8Y2) 45.181 238 -14-1% BFP(-4.500) 48.906 272 -16-1 LtE(16-0) 45.219 113 10-5% Spr(-19.375) 19.375 24.65 112 9-0 Spr(-18.535) 18.535 24.11 114 12-10% Spr(-19.837) 19.837 24.94 106 12-10 Spr(-17.289) 17.289 23.28 107 10-5% Spr(-17.562) 17.562 23.47 111 12-10 Spr(-17.960) 17.960 23.73 109 10-5%2 Spr(-17.570) 17.570 23.47 102 12-10 Spr(-12.829) 12.829 20.06 101 12-10% Spr(-12.755) 12.755 20.00 105 10-5% Spr(-14.922) 14.922 21.63 103 10-5 Spr(-14.421) 14.421 21.27 110 12-10 Spr(-17.789) 17.789 23.62 104 12-10 Spr(-14.724) 14.724 21.49 1 -22-0 S 52.358 295.72 M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 04/30/2008 10:09:58A M Page 3 Job Number: KS0344 Report Description: Ordinary Group 11 Pipe Type Diameter Flow Velocity HWC Friction Loss Length Eq. Length Total Length Pressure Summary Downstream Upstream Elevation Discharge K -Factor Pt Pn Fittings 4is Route 1 DR 1.049 Q=20.00 7.42 C=120 0.130131 35-0 Pf 5.727 101 12-10Y2 q=20.00 K=5.6 12.755 Spr(-12.755) 9-0 Pe -2.336 66 18-3 16.146 2E(2-0), T(5-0) 44-0 Pv AO 1.049 Q=40.06 14.87 C=120 0.470386 1-0 Pf 2.831 66 18-3 16.146 5-0 Pe 76 18-3 18.977 PO(5-0) 6-0 Pv BL 1.610 Q=104.44 16.46 C=120 0.343833 9-7Y2 Pf 3.313 76 18-3 18.977 Pe 0.000 74 18-3 22.290 9-7'A Pv BL 1.610 Q=128.06 20.18 C=120 0.501356 3-10 Pf 5.943 74 18-3 22.290 8-0 Pe -0.000 71 18-3 28.232 P0(8-0) 11-10 Pv CM 4.260 Q=295.72 6.66 C=120 0.020633 32-5Y2 Pf 1.213 71 18-3 28.232 26-4 Pe 0.000 108 18-3 29.445 T(26-4) 58-9% Pv CM 6.357 Q=295.72 2.99 C=120 0.002937 133-10 Pf 0.855 108 18-3 29.445 157-2 Pe 14.881 161 -16-1 45.181 5fE(12-7), BV(12-7), CV(40-3), 291-0 Pv GV(3-9Y2), PO(37-8'/2) FM 8.329 Q=295.72 1.74 C=120 0.000788 16-5Y2 Pf 0.038 161 -16-1 45.181 32-0 Pe 0.000 272 -16-1 45.219 fE(16-0), LtE(16-0) 48-5Y2 Pv FM 10.420 Q=295.72 1.11 C=120 0.000265 28-2% Pf 4.529 272 -16-1 45.219 83-0 Pe -0.842 238 -14-1% 48.906 4LtE(16-0), BV(19-0), BFP(-4.500) 111-2% Pv UG 10.400 Q=295.72 1.12 C=140 0.000201 110-2 Pf 0.045 238 -141'/2 48.906 111-7 Pe 3.407 1 -22-0 52.358 E(35-1), 3LtE(25-6), S 221-9Y2 Pv iso Route 2 DR 1.049 Q=20.06 7.45 C=120 0.130832 34-2% Pf 5.653 102 12-10 q=20.06 K=5.6 12.829 Spr(-12.829) 9-0 Pe -2.336 66 18-3 16.146 2E(2-0), T(5-0) 43-2Y2 Pv Jilt Route 3 DR 1.049 Q=21.27 7.89 C=120 0.145776 35-2 Pf 6.731 103 10-5 q=21.27 K=5.6 14.421 Spr(-14.421) 11-0 Pe -3.389 79 18-3 17.763 3E(2-0), PO(5-0) 46-2 Pv BL 1.610 Q=42.90 6.76 C=120 0.066286 6-81/2 Pf 0.445 79 18-3 17.763 Pe -0.000 77 18-3 18.207 6-8Y2 Pv BL 1.610 Q=64.39 10.15 C=120 0.140500 5-6 Pf 0.770 77 18-3 18.207 Pe -0.000 76 18-3 18.977 5-6 Pv 6+ Route 4 DR 1.049 Q=21.49 7.98 C=120 0.148607 32-2 Pf 5.819 104 12-10 q=21.49 K=5.6 14.724 Spr(-14.724) 7-0 Pe -2.336 77 18-3 18.207 E(2-0), PO(5-0) 39-2 Pv Route 5 DR 1.049 Q=21.63 8.03 C=120 0.150459 34-11 Pf 6.159 105 10-5% q=21.63 K=5.6 14.922 Spr(-14.922) 6-0 Pe -3.383 83 18-3 17.698 3E(2-0) 40-11 Pv BL 1.610 Q=21.63 3.41 C=120 0.018679 3-5Y2 Pf 0.065 83 18-3 17.698 Pe 79 18-3 17.763 3-5Y2 Pv Route 6 DR 1.049 Q=23.28 8.64 C=120 0.172411 32-2Y2 Pf 6.759 106 12-10 q=23.28 K=5.6 17.289 Spr(-17.289) 7-0 Pe -2.336 52 18-3 21.712 E(2-0), PO(5-0) 39-2Y2 Pv BL 1.610 Q=70.23 11.07 C=120 0.164981 8-4Y2 Pf 1.383 52 18-3 21.712 Pe -0.000 51 18-3 23.096 8-4Y2 Pv BL 1.610 Q=93.96 14.81 C=120 0.282710 9-11Y2 Pf 5.073 51 18-3 23.096 8-0 Pe 46 18-3 28.169 P0(8-0) 17-11 V2 Pv CM 4.260 Q=167.66 3.77 C=120 0.007221 8-10 Pf 0.064 46 18-3 28.169 Pe 0.000 71 18-3 28.232 8-10 Pv ss. Route 7 DR 1.049 Q=23.47 8.71 C=120 0.174927 34-6Y2 Pf 7.094 107 10-5% q=23.47 K=5.6 17.562 Spr(-17.562) 6-0 Pe -3.383 56 18-3 21.273 3E(2-0) 40-6Y2 Pv © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 04/30/2008 10:09:59A M Page 4 Job Number: KS0344 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Friction Loss Length Eq. Length Total Length Pressure Summary Downstream Elevation Discharge K -Factor Upstream Pt Pn Fittings BL 1.610 Q=23.47 3.70 C=120 0.021717 7-2%2 7-2'V2 Pf Pe Pv 0.156 0.000 56 18-3 54 18-3 21.273 21.429 BL 1.610 Q=46.94 7.40 C=120 0.078304 3-7% 3-7'% Pf Pe Pv 0.283 0.000 54 18-3 52 18-3 21.429 21.712 so Route 8 DR 1.049 Q=23.47 8.71 C=120 0.174997 32-4%2 9-0 41-4%Pv Pf Pe 7.239 -3.380 109 10-5Y2 q=23.47 K=5.6 54 18-3 17.570 21.429 Spr(-17.570) 2E(2-0), PO(5-0) Route 9 DR 1.049 Q=23.62 8.77 C=120 0.177013 31-71,4 7-0 38-7Y2 Pf Pe Pv 6.837 -2.336 110 12-10 q=23.62 K=5.6 74 18-3 17.789 22.290 Spr(-17.789) E(2-0), PO(5-0) Si Route 10 DR 1.049 Q=23.73 8.81 C=120 0.178588 32-10 9-0 41-10 Pf Pe Pv 7.471 -2.336 111 12-10 q=23.73 K=5.6 51 18-3 17.960 23.096 Spr(-17.960) 2E(2-0), PO(5-0) .fii+ Route 11 DR 1.049 Q=24.11 8.95 C=120 0.183871 37-11 11-0 48-11 Pf Pe Pv 8.994 -3.997 112 9-0 q=24.11 K=5.6 28 18-3 18.535 23.531 Spr(-18.535) 3E(2-0), PO(5-0) BL 1.610 Q=48.76 7.68 C=120 0.084005 15-9 4-0 19-9 Pf Pe Pv 1.661 -0.000 28 18-3 22 18-3 23.531 25.192 2LtE(2-0) BL 1.610 Q=73.70 11.61 C=120 0.180396 8-4'/2 8-0 16-4'/2 Pf Pe Pv 2.957 -0.000 22 18-3 19 18-3 25.192 28.148 PO(8-0) CM 4.260 Q=73.70 1.66 C=120 0.001578 12-9% 12-9%2 Pf Pe Pv 0.020 0.000 19 18-3 46 18-3 28.148 28.169 6810 Route 12 DR 1.049 Q=24.65 9.15 C=120 0.191566 31-7 7-0 38-7 Pf Pe Pv 7.389 -3.383 113 10-5%2 q=24.65 K=5.6 30 18-3 19.375 23.380 Spr(-19.375) E(2-0), P0(5-0) BL 1.610 Q=24.65 3.88 C=120 0.023782 6-4 6-4 Pf Pe Pv 0.151 -0.000 30 18-3 28 18-3 23.380 23.531 Route 13 DR 1.049 Q=24.94 9.26 C=120 0.195787 32-3Y2 7-0 39-3%2 Pf Pe Pv 7.691 -2.336 114 12-10'V2 q=24.94 K=5.6 22 18-3 19.837 25.192 Spr(-19.837) E(2-0), PO(5-0) t*gWIHi1(::1p6:::6Ef115fdiY85::Trf::ti154 0:0ii1y:::>::::>::>:<>:<::i:<1 Actual Inside Diameter 4.87 Value Of C 100 Multiplying Factor 0.713 130 140 1.16 1.33 150 1.51 Schedule 40 Steel Pipe Inside Diameter / = Factor M.E.P.CAD, Inc. AutoSPRINKO VR5 v5.2.6 04/30/2008 10:09:59AM Page 5 Job Number: KS0344 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Friction Loss Downstream Upstream Elevation Discharge K -Factor Pt Pn Fittings Length Eq. Length Total Length Pressure Summary AO Arm -Over BL Branch Line CM Cross Main DN Drain DR Drop DY Dynamic FM Feed Main FR Feed Riser MS Miscellaneous OR Outrigger RN Riser Nipple SP Sprig ST Stand Pipe UG Underground Diameter Elevation Flow Discharge Velocity Pressure Length Friction Loss HWC Pt Pn Pf Pe Pv Inch Foot gpm gpm fps psi Foot psi/Foot Hazen -Williams Constant Total pressure at a point in a pipe Normal pressure at a point in a pipe Pressure loss due to friction between points Pressure due to elevation difference between indicated points Velocity pressure at a point in a pipe ALV AngV b BaIV BFP BV C cplg Cr CV DeIV DPV E EE Eel Ee2 FDC fE fEE flg FN fT g GIoV GV Hose HV Hyd LtE mecT Noz P1 P2 PIV PO PrV PRV red S sCV Spr St T Tr U WirF WMV z Alarm Valve Angle Valve Bushing Ball Valve Backflow Preventer Butterfly Valve Cross Flow Turn 90° Coupling Cross Run Check Valve Deluge Valve Dry Pipe Valve 90° Elbow 45° Elbow 11W Elbow 22W Elbow Flow Device Fire Department Connection 90° FireLock(TM) Elbow 45° FireLock(TM) Elbow Flange Floating Node FireLock(TM) Tee Gauge Globe Valve Gate Valve Hose Hose Valve Hydrant Long Turn Elbow Mechanical Tee Nozzle Pump In Pump Out Post Indicating Valve Pipe Outlet Pressure Relief Valve Pressure Reducing Valve Reducer/Adapter Supply Swing Check Valve Sprinkler Strainer Tee Flow Turn 90° Tee Run Union Wirsbo Water Meter Valve Cap (1 © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 04/30/2008 10:09:59AM Page 6 Job Number: KS0344 Report Description: Ordinary Group II ACA Supply at Node 1 Pressure, psi 111111111111111111111111111111111111111111111111111111111111111111_1_11111111111111111111111111111i 11 Static Pressure 140.000 ,545.72 295.72 with hose @ 52.358 streams System demand curve 10900.00 @ 20.000, lllllltl l 1111111 11 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 I I 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 t.1 010022 3300 4400 5500 6600 7700 Water flow, gpm 8800 9900 11000 Hydraulic Graph Supply at Node 1 Static Pressure 140.000 Residual Pressure 10900.00 @ 20.000 Available P,.ssureTinw of Test 139.529 @ 545.72 System Demand 295.72 @ 52.358 System Demand (Including Hos. Allowance) 545.72 @ 52.358 ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 04/30/2008 10:10:OOA M Page 7 Job Number: KS0344 Report Description: Ordinary Group 11 (�y ©M.E.P.CAD, Inc. 411 AutoSPRINK® VR5 v5.2.6 04/30/2008 10:10:01 AM Page 8 nm. I VIv GIVhK le fueS (SyUU 04/23 '08 13:34 N0.599 03/03 TITLE? ANSUL R-102 FIRE SYSTEM LAYOUT PROJECT? SBARRO SOUTHCENTER MALL DATE? 04/22/08® c6mci-r - S � Fcl DWG' 15119—A I-Flikv?A. 9eies ' 3 1kf4.. STMYflo) tt PMc DST" lex 1(9" N w� O rda ��.....� e O 54' 69' 2V (2) 245 245 (2) <2) 11 YI �o -s� 10111011 PAM . • • .'ter •� 1) ANSUL R-102 FIRE SYSTEM 2) ONE TANK SYSEM (3 GALLDN> 3) 3/8' BLACK IRON PIPING W/3/8' S,S. APPLIANCE DROPS 4) MECHANICAL GAS VALVE = (ADVISE) A004 REMOTE MOUNTED 1 REGULATED RELEASE Basin ras 2 0-30,1 3c iLbA iii/moi 0 0 ()lei ael 3/3 5w* ivs+ct l ( "'rem e,gf',hcti;ts�►C►• Ail Arel COKE 4/411 +V✓r vevh Ik,-:or 5.ys4 -. — U L ce vviive, t 4 MEW/010u MS iiALVE R- Fuca S IOW- I r: ; ` 2008 Tukwila Fire Received Time Apr. 23. 12:38PM SECTION IV — SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-28 REV.5 4-1-06 Nozzle Application Chart The following chart has been developed to assist in calculating the quantity and type of nozzle required to protect each duct, plenum, or appliance. NOTICE This chart is for general reference only. See complete details for each type of hazard. Hazard ► Duct or Transition (Single Nozzle) Duct or Transition (Single Nozzle) Duct or Transition (Dual Nozzle) Electrostatic Precipitator (At Base of Duct) Plenum (Horizontal Protection) ► Plenum (Horizontal Protection) Plenum (Vertical Protection) ► Fryer (Split or Non -Split Vat) Fryer (Split or Non -Split Vat) ► Fryer (Split or Non -Split Vat)* Fryer (Non -Split Vat Only) Maximum Hazard Dimensions • Length — Unlimited Perimeter — 50 in. (127 cm) Diameter —16 in. (40.6 crn) Length — Unlimited Perimeter —100 in. (254 cm) Diameter — 31 7/8 in. (81 cm) Length — Unlimited 2 Perimeter -150 in. (381 cm) Diameter — 48 in. (122 cm) Individual Cell 1 Length —10 ft (3.1 m) Length — 6 ft. (1.8 m) Width — 4 ft. (1.2 m). Length — 4 ft. (1.2 m) Width-4ft(1.2m) Maximum Size (without drip board) 14 in. (36 cm) x 15 in. (38 cm) Low Proximity Maximum Size (without drip board) 141 /2 in. (37 cm) x 14in. (36cm) Medium Proximity Maximum Size (without drip board) 15 in. (38 cm) x 14 in. (36 cm) High Proximity Medium Proximity Maximum Size (without drip board) 19 1/2 in. (49.5 cm) x 19 in. (48.2 cm) High Proximity Low Proximity Maximum Size - (without drip board) 18 in. (45.7 cm) x 18 in. (45.7 cm) . High Proximity Minimum Nozzle Nozzle Quantity Heights 1 1 1 1 1 1 1 1 For multiple nozzle protection of single fryers, see detailed information on Pages 4-12 through 4-14. 13-16 in. (33 — 41 cm) 16 — 27 in. (41 — 69 cm) 27 — 47 in. 20 — 27 in. 21 —34 in. 13-16 in. 25 — 35 in. (64-89 cm) Nozzle Part No. 430912 419337 419337 419334 419335 430192 419336 419336 419342 419342 419339 419340 419338 419342 419338 Nozzle Tip Stamping — Flow No. 1W 2W 2W 1 /2N 1N 1W 1W 1W 290 290 230 245 3N 290 3N Nozzle Application Chart (Continued) Hazard Fryer (Non -Split Vat Only)` Fryer (Split or Non -Split Vat) Fryer (Split or Non -Split Vat) Range Maximum Hazard Dimensions Maximum Size (with drip board) 21 in. (53 cm) x 14 in. (36 cm) (Fry Pot must not exceed 15irtx14in. (38 cm x 36 cin)) High Proximity Medium Proximity Maximum Size (with drip board) 25 3/8 in. (64.4 cm) x 19 1/2 in: (49.5 cm) (Fry pot side must not exceed 191 /2 (49.5cm) x19in. (48.2 cm) High Proximity. Low Proximity Maximum Size (with drip board) 18 in. (45.7 cm) x 27 3/4 in. (70.5 cm) High Proximity Minimum Nozzle Nozzle Quantity Heights 1 Maximum Size (with drip board) 14in. (36cm) x 21 in: (53 cm) 1 Low Proximity Maximum Size (with drip board) 141/2 in. (37 cm) x 261/2 in. (67 cm) Medium Proximity Longest Side 32 in. (81 cm) Area — 384 sq. in. _ (2477 sq. cm) Longest Side 28 in. (71 cm) Area — 336 sq. in. (2168 sq. cm) Longest Side (High Proximity) 1 28 in. (71 cm) Area — 672 sq. in. (4335 sq. cm) Longest Side (Medium Proximity) 32 in. (81 cm) Area — 768 sq. in. (4955 sq. cm) Longest Side (Low Proximity) 36 in. (91 cm) Area—1008.sq. in. (6503 sq. cm) For multiple nozzle protection of single fryers, see detailed information on Pages 4-7 through 4-11. SECTION IV — SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-29 4-1-06 REV 5 27 — 47 in. 20-27 in. 21-34 in. 1 —16 in. 25-35 in. (64-89 cm) 13-16in. {33 —41 cm) 16— 27 in. (41 — 69 cm) 30 —40 in. (76 = 102 cm) Nozzle Part No. 419339 419340 419338 419342 419338 419342 419342 419335 40 48 in. 419333 (102 -122 cm) (With Backshelf) 40.— 50 in. (102 -127 cm) 30-40 in. (76 — 102 cm) 15 — 20 in. (38 — 51 cm) 419340 419341 419342 Nozzle Tip Stamping — Flow No. 230 245 3N 290 3N 290 290 1N 1F 245 260 290 ., v wruv Yieoulatea Mecnanicai Helease Assembly (3.'0 gallon — Part No. 79290 or 1.5 gallon. — Pan No. 79291) contains the regulated release mechanism, agent tank. expellant gas hose for agent tank hookup. and.enclosure knockouts. to facilitate installing actuation, piping; expellant piping; detection system; and additional equipment. This regu- lated release assembly is used in single, double. and multiple. tank systems and must be mounted to a rigid -surface.. The release mechanism can be used to interconnect both the actu- ation and expellant gas lines as required per system design. The regulator is designed to allow a constant flow of gas into the tank at 100 psi (690 kPa) when the system is actuated. In single, double. and multiple -tank systems, the provided expel- lant cas hose connects the agent tank to the bottom outlet of the regulator. In double and multiple -tank system configurations, the back outlet of the regulator is used es an expellant gas feed for one additional tank -enclosure or tank -bracket hookup: The enclosure contains the required knockouts to facilitate this cor- rection. If a pressure switch is to be attached to the regulator, additional fittings are required. • The tank is mounted within the enclosure. The tank contains an adaptor/tube assembly with a burst disc union: The burst disc helps prevent siphoning of the agent up the pipe due to signifi- cant temperature fluctuations in the area where the •tank is located. The tank is mild steel and. under normal conditions, requires hydrostatic testing .every twelve years. • The agent tank is shipped uncharged and must be filled with 1.53 gallons (5.8 L) or 3.06 gallons (11.6 L) of only ANSULEX Low pH Liquid Fire Suppressant during installation. The detection and additional equipment required per system design are connected to'the release mechanism. The enclosure contains knockouts to facilitate detection and additional hookups. The system can b= actuated automatically, or manually. Auto- matic actuation occurs when a fusible link within the detection -system separates in a fire'condition. Manual actuation of the system occurs when personnel pull on the remote manual pull station pull ring. EXTINGUISHING AGENT ANSULEX Low pH Liquid Fire Suppressant (1.5 gallon — Part No. 79694 or 3.0 gallon — Part No. 79372) is a potassium -based - solution .designed for fast knock -down and suppression of grease -related fires. The agent is shipped in plastic containers which provide one complete tank charge. Agent storage life expectancy is twelve years. The distributor must record the batch numbers and date of shipment receipt to be filed with each instal- lation record. Total Flow No' 1-5 Tank Quantity 1 6-11 1 Type of System Single Single ANSUL Type of Hardware • 1.5 Gal. Reg. Release 3.0 Gal. Reg. Release ELECTRICAL SWITCHES - L0CfarrCP :IP W.f.( '..P11/TD. The electrical switches are intended for .use with electric gas valves, alarms, contactors, lights, contractor supplied electric power shut-off devices :and other electrical devices that are designed to shut off or tun: on when the systemis actuated. Switches are available in kits: One Switch Kit, Part•No.423878; Two Switch Kit, Part No. 423879, Three Switch Kit; Part No. 423880, arid Four Swifch Kit, Part No. 423681. Each switch has a set of single -pole, double -throw contacts rated of 21 amp, 1 HP 125, 250, 277 VAC or 2 HP, 250, 277 VAC. Mounting hardware is provided with each kit. R-102 RESTAURANT FIRE SUPPRESSION SYSTEM (Standard UL 300 Listed) No=fe identification Chart Nozzle Nole Nozz{--? Tome Part No Sta moino 1W Nozzle 419336 1W 1WSS Nozzle 417333 1W 1N Nozzle 419335 1N 1 NSS Nozzle 417332 1N 1/2N Nozzle 419334 1/2N 3N Nozzle 419338 3N 2W Nozzle 419337 2W 2WH Nozzle 78078 2WH Noz Fiov 1 1 1 1 1/2 3 2 2 230 Nozzle 419339 230 2 245 -Nozzle 419340 245 2 260 Nozzle 419341 260 2 290 Nozzle 419342 290 2 2120 Nozzle 419343 2120 2 1F Nozzle 419333 1F 1 1100 titnaE -43Og12 1 1 c 0 1 Nitrogen Cartridge Required LT -20-R (7032) LT -30-R (5373) Carbon Dioxide Cartridoe Required 101-10 (15850) 101-20 (17492) ( f`osT 1741 SIPsNis 0i\\ ,S\J'L(ttRSrr3 ?o (o0, -c_ ) Uma-rP NW) 511 �. FLA:) 5 LGIN ! . iS -55 T 1 ACCEPTED Without Comments As Noted In Red Per The Attached Letter i nese plans have been revioweo by The Tukwila Fire Prevention Bureau for corkrmance with current city standards. Accawance ...:L.;biact to errors and omissions which -6-,)n uthorize -violations of adopted standaros and The refiponsibil4y for the adequacy of With tne designer. Additions, docs oi IOflS hl) these drawings atter this date will void tni.:.; acceptance lnd will require a resubmittal of revised drawings for subsequent approval. sinal acceptance is subject to field test and inspection by ; he Tukwila Fire Prevention Bureau. late: — By: toKWILA FIRE DEPARThibill Please call: 575-440 and give thisiob No. -) ind exact address for shut' 441wn or restoration approval SHEET INDEX SHEET NUMBER SHEET TITLE FA -01 SYSTEM INFORMATION FA -02 TYPICAL DETAILS - WIRING AND MOUNTING FA -03 FIRE ALARM SYSTEM FLOOR PLAN FA -04 SYSTEM CALCULATIONS (GENERAL), RISE, SITE PLAN 1 E 58 pvwvwnt3A.10.1.0" Without Comments As Noted In Red Per The Attached Letter 'nese plans have been reviw .d by The Tukwila Fire-' Prevention Burn.au fof c4:' ,. t:..•..• _ ti current city stand31.d:6. Ac.:_ ; 1r+t;� �: I rk.:< and ornissionti a(: 001 aa. U .. 'ii ,7 ..'-.:•;(.;(1S of adopted :ifann .1•ra` e. I(j i} �;i l.:�1•• .. I I . C (i'-al?.1Ay for the =tihcaU s `, f ; .:?..•.:Ir r=:.... ; t• tri:: signer. iCi!;IitiUr'Iza, 4:'.!t_.,;iii1. `.;I ;'•_ 'I':;I„ui, ,. ii... rt:ar.winysafter ,lis duty c.); + ;il , .::C.: ;;!_.:l !:. r, i Viiit require a esubmittal of revie::lt tot s:b:.i ;quent approval. final acc+r'ptbncEi is subject to fi.=•Id test and inspection by The Tukwila Fire, Prevention Bureau. Date: /(1("1 S` \ rUKWILA FIRE DEPARTIVIEM Please call: 575.4402 and give this job No. 0% -L-19)-)- a, ' exact address for shut or restoration approval: 1 NOTICE A completed, signed, Tukwila Gore Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE. COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) 2S STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #12 FPL/FPLR ..RED (JACKET), A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) 2V SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATI❑N LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL%FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED; #18 FPL/FPLR RED (JACKET). UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TW❑ #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO 1414 , FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END GENERAL NOTES FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPGRAMMED WITH DEVICES ADDRESS. NG 1. NUMBERS ADJACENT TO DEVICE SYMBOLDENOTE DEVICE CIRCUIT/ADDRESS: DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS, SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. ,,CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE' IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES.: g_ FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK'; SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 .AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED :AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL. BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED -CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. , DETECTORS .THAT HAVE BEEN. INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN FULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. • 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING :BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4,2.2.2 ALL STYLES OF CLASS A CIRCUITS. USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (LE., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM •(1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 1 1 2 SYMBOL DESCRIPTION SYMBOLS LEGEND MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD MCP, CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD B LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS ® (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING DUCT SMOKE ®p" DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. 4S DEEP BOX 80" A.F.F. W/ 1-1 /2" EXT. TO BOTTOM E. C FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING L FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING FIRE ALARM STROBE (WALL MOUNT) FIRE ALARM SPEAKER (CEILING MOUNT) ZR -MC -W SIEMENS SET -CW SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. 4S DEEP BOX CEILING W/ 1-1/2" EXT. FIRE ALARM SPEAKER (WALL MOUNT) SET -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM FIRE ALARM STROBE (WEATHERPROOF) SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR MULTI -VOLTAGE CONTROL RELAY MR -201 /C AIR PRODUCTS 4S BOX VERIFY IN FIELD 0 MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD O JUNCTI❑N BOX F.B.❑. F.B.❑. N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A F.B.❑. FURNISHED BY OTHERS N/A N/A N/A N/A N/A. NOT APPLICABLE N/A N/A N/A N/A U.❑.N, UNLESS OTHERWISE NOTED N/A N/A N/A N/A WP WEATHERPROOF DEVICE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A Fig eft 2008 Tukwila Fire --W-2.515)13 ,'75 -- Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved RELEASE/REVISIONS Hcs LU DESCRIPTION SHOP DRAWINGS AHJ LU F --- C21 co 0 0 0 z W cc (i) CC 2 O� Q W cc 1 -I co O) w z wa oz 1_ D Q 0 LL 0 N ~ 0 1... 0 z ILI (i) >m rr � (SCALE: 1 /8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE:5/05/08 BACKROUND PLAN PROVIDED BY: .OB NUMBER:54541 ( SHEET FA -01 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT bMDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS DUCT DETECTOR LOCATION p TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT 0 LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE A_ c STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVIC y END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH O 0 0 GROUND HTRI-R STATUS LED 00 CO 0 0 0 N.0 COM N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL `ABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE' DEVICE TO NEXT ADDRESSABLEf DEVICE L - NOTE 1: VOLTAGE MAX. - CURRENT MAX. - CONT. RES, MAX. - MAX. CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN. LINE SIZE- N❑TE 2: ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTI❑N. MUSIC OUTLET SAMPLING TUBE INLET SAMPLING, TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE=NONE LLI-AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE f STOP IF LAST DEVICE l(-) FROM XLS CONTROL PANEL OR ¢) PREVIOUS ADDRESSABLE DEVICE t-) RELAY CONTACTS (4.0A @ 125VAC) (4.0A @ 30VDC) 27 VDC 3.5 r1A DURING POLLING 10 OHMS 200 FT. (18 AWG)' 0.02uF 0.04uF 14 AWG 18 AWG A TB1 123456 HCP A 65 4321 END OF LINE, � 1 DEVICE (3.6K 1/4W) SUPERVISED SWITCH GROUND '� 0 re) d- 0 HTRI-D OSTATUS LED CO 0` 0 FRONT MEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE 1 DEVICE LOOP ! 0 FROM XLS CONTROL PANEL OR (O> PREVIOUS ADDRESSABLE DEVICE (-)> NOT USED 0 NOTE: FOR ADDITIONAL . SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE, SUPPRESSION SYSTEM INTERFACE) 0 CND N AC le I 0 PAD -3 0 INPUT INPUT TROUBLE. NAC1 NAC2 NAC3 NAC4 AUX 1+ 1-..1, .2+ 2— 2 .NC .0 NO + =• + + + — + — Ll MIRIAM 24K TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE END OF LINE DEVICE 3.6K 1/4W) UPERVISED 1 �WITCHH Ij j FROM REMOTE POWER SUPPLY ('S' CABLE) FROM`FACP. (VOICE CIRCUIT) ('V' CABLE) 470 OHMS �IN EOL TSM -1 • .L= : 0 TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE: NONE (+) (_) STROBE SPEAKER (+) (-) (STROBE) EARTH GROUND.: —.(+)TO NEXT; DEVICE OR l >(-) STOP IE LAST DEVICE J (-10 STROBE-) SPEAKER (+) (-) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE 2 NAC -4 2 NAC -3 NAC -2 2 NAC -1 SPEAKER STROBE OR STROBE ONLY BO" A.F.F: • L T r: u 4S DEEP BOX W/ 1-1/2_ ; EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) ,TO NEXT DEVICE OR END OF LINE J)TO NEXT DEVICE OR t, END OF LINE SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERA11IN TEMPERAVE +32' F 0- C TO 1017 F 3Ei C) JIUMIDITY: O- 9 X RELATIVE HUMIDITY. NON -CONDENSING HIP -11 SMOKE DETECTOR —� DEVICE IS LISTED FOR AIR VOLOOTY APPLICATIONS OF 300-4000 FT/MIN Y4IEN USED IN CONJUNCTION VON DUCT HOUSINGS AD -11P OR AD-11XPR D8-11 STANDARD SMOKE BASE DETECTOR 00 0' 0 ittg z_ 0' 0' . I . 00, N 0 0 N d .' FROM PREVIOUS ADDRESSABLE DEVICE OR POVER SOURCE DATA IN (-) >- DATA IN (+) > REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE > ( ) DATA OUT > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID CEILING SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION •\.., CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE _ JUNCTI❑N BOX—, MOUNTED ON \\` CEILING. FLEX JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT / / / / / 0 0 f TO NEXT DEVICE 0 0 ----CADDY BAR SMOKE DETECTOR SMOKE DETECTOR MOUNTING SUSPENDED ILLUMINATED CEILING SCALE=NONE Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved J UJ F-. U) z 0 LU Ot LU LU J LU Et { z Ia DESCRIPTION SHOP DRAWINGS AHJ w co 0 u7 LO 0 z 0Y (0 CM ‘CALE : 1/811=11 DRAWN BY: (.ANDERSON DESIGNED BY:. R.VEZZANI DATE:5/05/08 BACKROUND PLAN PROVIDED BY: 1.9B NUMBER:54541 /- SHEET FA -02 ,• s • ••• !!.; NORTH r • !s'!' • • • !!!, •I 1' I... :1 • SBARRO WESTFIELD SOUTHCENTER MALL tt If 3 • FLAG .!!! • ; . • • • Ittf NOTES: FIELD 'LOCATE RELAY MODULE FOR' :BACK! GROUND MUSIC. INTERFACE. FIELDH LOCATE SIEMENS DUCT DETEOOR ON RETURN SIDE OF ALLLyAv UNITS.(SEE SIEMENS ;INSTALLATION SUBMITTAL FOR LEIcATiciN GUIDELINES AND, FA=02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY .ELECTRICAL CONTRACTOR. • , ! 111;10',,;•;,!!' ,,•!!11 fo!,:1.!!!,;!; ! 1! 1, t: t • fl • .•.!,!1! ; I • • ! 3.1,, • ,Z4 Iftm CD • 1'0 ON 0` CO (\-1 0 F-- 0 \CD c) c\J r LL < < LIT LIJ ft 1,0 TEL. (206) 622-654.5 I, I t RELEASE/REVISIONS-----_•• z , uJ DESCRIPTION - SHOP DRAWINGS AHJ c0 0 z Copyright ! 2006 b Guardian Securit S stems, Inc. All 12. hts Reserved (SCALE: 1/8'1=1' DRAWN. BY: [ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/05/08 BACKROUND PLAN PROVIDED BY: \LOB NUMBER:54541 2 SHEET, FA -03 N N.. N. o 0 • .3 0 I; 1\'' 0, .1004:2°' ......... \ 0 ,' \ 0\,. L., , \ \ 0 .----0,3 \\\ 0, k r,,k \ .. .. _ •-•c-A, A -.I "Tr'°J.° (s'r .., )..' ;!, \,, \ \ ,. .• - \ 0 r 'N .0,00- 1 1 rt \ t \ S 3•000., . .. __ _ • r; - --°- °- _...,....,100000---r° , \‘0, ,...-- 0 ..:_:._•_-_-_-_-_::::----- --T: .., • r -• - 1,..'_..,....;,..,„....--• .1-:,,,,,,\._. % ,‘,, ,.--.,,I.\ \ \ \ V.1 \ J-- .. I.- sk .,. % , y t„, ----------1-Y • \ 0 is\ NORTH rr 3r- A I, SBARRO VIESTFIELD SOUTHCENTER MALL •-s • / -00 • • -00- \ • SCALE 11324 30 30 EOL -S1 20.31V RISER DIAGRAM t! •,'• . ''•;' ' '• I SYSTEM CALCULATIONS SBARRO FACP ADD ONS SBARRO Current Load: SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations •.1' ; ! ' h 11 Standby: Alarm: Current Load: Device Type HFP-11 AD2-P1 Qty HTR.: -R! HTRI-D ICP -B61' Standby Current, Load: 1 1 Amps Standby: Alarm: 0.0022 Total 0.0022 Amps Total Device Type Qty Amps Total 0.0023 Amps Total 0.0635 0.009600 0.001600 0.005 0.0635 0.0096 0.064 0.064 Main System Board •1 0.03 0.03 0.030 • 3 ;01:j 0.030 1. 0.021 0.0035 0.021 0.0731 Amps 0.085 Amps 0.0731 Amps For 24 Hours = 1.754 Amp -hours SET -MC @15CD SET -MC @30CD SET -MC @75CD SET -MC @110CD SET-HMC-C@115CD SET-HMC-C@135CD SET-HMC-C@185CD ZR -MC @15CD 0.064 ZR -MC @30CD HCP Alarm Current Load: 0.085 Amps For 5 Minutes= 2 0.098 0.196 I.; I ' '.1! • 0.175 1:1 111.. 0.233 0.318 0.318 1 1 0.445 0.064 0.098 0.0015 '!, 11 II! •• ; t• i '•' 0.007 ; . • ;11.111. 1.-e • •" I 1, ; I BattyPair to be Used: • s't 10, Total System Current Load: 12VDC 25% Derating= Amp -hours ; • 0 • 0.03 Amps 0.226 Amps • • ii' 1! 2.202 Amp -hours Standby Current Load: Alarm Current Load: 0.03 • 0.226 Amps Amps For 24 Hours = For 5 Minutes= 0.720 0.019 2.202 Amp -hours Amp -hours 7AH 010' • ; 3 ; Total System Current Load: Battery Pair to be Used: 12VDC BATTERY SIZING CALCULATION • • 00010 ,.• ; Notification Appliance Circuit Detail •;- • 25% Derating= Amp -hours 0.924 0.924 7AH PROJECT: iWESTFIELD SOUTHCENTER MALL •1 • I,; • • . • • . • „ Panel: : SBARRO 1VVire Resistance 1.62 Date: I May 7, 2008 CURRENT TOTAL= 196 CIRCUIT:1S1 i11 .13, . +,' , 11t - . ' aTY DeviceType Alarm Current AlarmTotal WreSize WireLength VoltageatEOL CircuitTotal 0 SET -MC @15CD 64 0 , Total Wire Resistance ( R ) 0.451 4 -4 ;, t-- )2 SET -MC @30CD 98 196 , (WL *2 ) * (Rif) I,,II , i 1 0 SET -MC @75CD 175 Oi , , I , . i , Total Device Load, Amps (1) 1 0.20i 1 0 SET -MC @IIOCD 233 3 01. 3 I (Total Cct Load) • 0 1SET-HMC-C@115CD • 318 iVoltage Drop ( E ) 0.091 ' 0000 SET TCC-I-IMC 50-C@ 177CD ..., ,.. , • 0.0 , (E = I * R) 135CD 318 ; i , EOLVolage ..: . • 1i,11,111,I1, 20: 3 0 SET-HMC@185CD 445 01 i 1 (204-E) . 01 i , , I; , @, 1 i0 SET-MC-CW@110CD 233, 1',I1i,1i1;: DEVCES=2 TOTAL m A=1 1961 12 i 140 -i, - 2031109441 196! ; 1. t • ; ; 1 4 - 1 . Notification Applance Circuit D' etail , PROJECTWESTFIELDSOUTHCENTERMALL Panel:I- SBARRO -- • Date: May 7, 2008 •CIRCUIT:SPEAKER CIRCUIT iWira Resistance 2.58 ; CURRENT TOTAL=36 3 / , I QTY 1 Device Type Alarm Current Alarm Total I Wire Size I Wire Length ,:',Voltage at EOL i Circuit Total i ' 1 1 ; 1 f -3i•• • ,s--- • --1-- 3- ,- . -`, - - ,.•, 1.81 3.6 3 3 f '3 0 . i 1 2 70.7V 1/8 , L! !Total Wire Resistance ( R ) 0 00 , 0 .i. ii 0 oi 1 --i ( WL * a) * (Rf) 1 0 0 1 , 1 Total Device Load, Amps (1) 0.00 1 0 0 0 ,tII (Total , Cct Load) 10 0 0 I I 1VoItageDroptE) 1 0.00, 61 1 ':;:i .1':',:: . 0 1• 1 i 0 • - . • 0; ... 0 ; 0 :01 .... . ; 1'.' ... i.:,.• 1 • ,•. ,...?. , ; ,..tL! 0 1 . 01 01* • .- . : z • . ;:; .3.. .. . - ,.1.• - - ;. ,.. 0 t . ; 0 .01 . . It .;;! 1-1::, ' -- ! : - I i i- .1._ .i.„ • . DEVICES=12 'i TOTAL m A= 36i :140 1 , . r - 3 - . • ; 0,, - i:,,: , ..1. • - 20.4 3.6 I ....: 3 ; •. . • . ,, . 3 •3 • 1 (E= 1*. EOL Voltage • 20.401 VOLTAGE DROP CALCULATION • .1: Copyright 2006 by Guardian Security Amp -hours Amp -hours -1111 Amp -hours Amp -hours 1'1 t .1: • '0, .!, • ,• ' • ;11,1".",.• . °I 10 ." • , 1 11 (206) 622-6545 _J LLJ RELEASE/REVISIONS-- CD uJ DESCRIPTION cr 0 .;!•:;;.1 t, • 0 , DRAWN BY: LAN DERSON DESIGNED BY: R.VEZZANI DATE: 5/05/08 BACKROUND PLAN PROVIDED BY: Systems, Inc. All Rights Reserv .11 t • -... 001 FA -04 General Notes VICINITY MAP (Suite#2600) SCALE: NTS 1. Western States Fire Protection to add new pendent heads new upright heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft' maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. EAST RISER DETAIL, HYDRAULIC REFERENCE ONLY NOT TO SCALE Existing Main o 24 O 5 cgdef * -0 9 Ordinary Group II.0.20gpm/ft2 for 895.00ft2 LG 12'-0' CLG 12'40' 0 A — III 11�_s CLG I9 11.011. u Existing Branch Lines v 3-a'%. e 0 ranch Lines CLG 10'-5' I I- 111 1'/a :5-9 11 �I 100 11211-" !' Existing = 41 Mech Tee ptug_ I 0 1 Existing Main A es LG FIRE SPRINKLER SYSTEM 1/8" = 1'-0 >aC2_ 0 0 Without Comments T -I 0 / Noted Red As In T�/ad Per The Attached Letter I hese plants hav2� i' ..:r; 1( ry F..., .',::d by The- ilmfil e revention t umr.iI.1 ':.r -:,...:,,.;s":: i... >. with cu ent city standards.:�(:(a,:h: IL :i: t/.; errors a omissions wh:c' i :r. , ,.i.,..,,,, _I(,!.h -i:a : violations o — ~ of Standards and :i' , ?' Ii/t=: ri''."'pcnsie)ilityfor the adequacy of ,....1',.:,,,ii , .;li',' %•. ,1, tfie designer. Additions, d._)i' , 1:,'.. . .,';-. .:f . !': l.i:c e drawings atter `i his d ',:e viii i:,.,,- :.i,', ..: ;i•. _:a• , r,d will require a -esuhn itt of f .:`ir,'-' ? ; ..-'/.jnc—r� ` t se . .,,.. for .1.1.:,�quent approval. e t i Sbarro Remote Area: Retail # 2600 CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY a/ass ORD HAZARD II MAX. COVERAGE per HEAD 130 FN • DENSITY .20 GPM ! Ft' for 895 Ft' SPRINKLER Reliable Model G4A ORIFICE 1/2" K=55.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 P.SI FLOW 10900 GPM AT BASE OF RISER, SYSTEM REQUIRES: 295.72 GPM @ 48.91 PSI ' At time of Design aessnay........... as sneaxsw.>a usmrcacnn. Weld stam inspected hung° prior to hyd approval. ICE TYPICAL FLEXABLE SPRINKLER CONNECTION PIPE NIPPLE SPRINKLER BRANCHLIKE FLEXABLE CONNECTING` HOSE IN STANDARD LENGTHS MOUNTING BRACKET REDUCING FITTING SUSPENDED T -BAR GRID CEILING TILE FLEX HEAD DETAIL NOT TO SCALE FWV0L SWIVEL SWAY BRACE FITTING 'BRACE PIPE 5/9' KWIK BOLT —(2114' EMBED LENGTH) FIG.1000 "�—"FAST CLAMP' ' SWAY BRACEATTACHMENT \ LINE PIPE • LATERAL LINE RESTRAINTS NON -THREADED BRACE PIPE must be before Ow. is int piping -incl aoctp....incr. i5 : , i s *_Yi, l.:) fir., -1d tett and inspection by file. Tukwila i'i;:i i-re`io—,ii.ion Bureau. [Date: -57---5---°g By: fel , .1 1 3 5 7 9 TUKWILA FIRE DEPARTMENT, Please call: 575.4407, and give this job No.05 '-1 a- ._ • and exact address for shut• Town or rt st:.ration approval, SYMBOL LEGEND REVISIONS 2 -WAY EARTHQUAKE BRACE NO. DESCRIPTION DATE 4 -WAY EARTHQUAKE BRACE Sprinkler Legend SYM. SIN QTY. K SPRAY ORIF. FIN. TEMP. MFR./MODEL R5415 9 5.6 HYDRAULIC REFERENCE POINT R5415 4 5.6 Pendent Pendent %Z' White 155°F G4A Concealed APPROVAL: City of Tukwila 1,E White 200°F G4A Concealed HANGER SYMBOL Total = 13 CONT. NO.: KS0344 DRAWN BY: Adam Kantner BRANCHLINE RESTRAINT SPRK ON SHEET: SEE LEGEND SPRK. ON JOB: DATE 04/30/08 FPS. 4A PIPECLAMP FOR SWAY BRACE n LATERAL BRANCHLINE RESTRAINT FIG. 909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT a/9' KWIK BOLT (2 1/4' EMBED LENGTH) BRACE PIPE gl°g:1 NON -THREADED BRACE PIPE LATERAL BRANCHLINE RESTRAINT NO TO SCALE Hanger No. 07C HILT! Kwik Bolt III Cut Rod Lgth Rounded to Nearest Inch N // HILT! Kwik Bok 11 Dnl(edAnchor 1 i C( 1 \-1" / Concrete Construction / Rod Coupling All Thread Rod Swivel Ring Bottom of Concrete to Center Line of Pipe Note on Plan Note on Plan: Hanger Number and '/IV Dimension HANGER DETAIL NOT TO SCALE VICINITY MAP DETAIL NOT TO SCALE Western States Fire Protection Company 7102 180th AVE NE, STE 4105 - REDMOND, WA - 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY -OFFICES LOCATED ALBUQUERQUE/AUSTIN/DALLAS!DECATUR/ DENVER /DULUTH /HOUSTON /KANSAS CITY LAS VEDAS/MINJEAPOLIS/PHOENIX/PORTLAND /RAPID CITY/ST. PARR/SALT LAKE car/SEATTLE Phone: 425-881-0100 Fax 425-881-3030 2008 • Tukwila Fire on ce,A4- -x'/77 (10' caroti )/� itfra $ David A. Chute 305.09-2697 ;t Vik Nt —wailD Q (0 U)• w Adam Kantner 0 co .m 5, 0 L U CONTRACTO Sbarro 2600 Southcentner Mall —A e--4 tl Tukwila ,Wa 98188 FIRE SPRINKLER SYSTEM SHEET FP -1 OF 1 SYMBOL LEGEND General Notes VICINITY MAP (Suite#2600) SCALE: NTS 1. Western States Fire Protection to add new pendent heads new upright heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. 'Lh 'yflt.dt?N tM1 EAST RISER DETAIL HYDRAULIC REFERENCE ONLY NOT TO SCALE REVISIONS Existing Main Existing Main 0 Ordinary Group II.0.20gpm/ft2 for 895.00ft2 CLG 12'-0' r—CLG 12'-10' CLG 9'-0' Existing Branch Lines • ranch Lines CLG 10'-5" LO 12'-0" FIRE SPRINKLER SYSTEM 1/8" = 1'-0 Sprinkler Legend Existing =ranch tiee Sbarro Remote Area: Retail # 2600 CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY cLAss ORD HAZARD II MAX. COVERAGE per HEAD 130 DENSITY .20 GPM / Ft' for 895 SPRINKLER Reliable Model G4A Ft' F1' ORIFICE 1/2" K. 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 PSI FLOW 10900 GPM AT BASE OF RISER, SYSTEM REQUIRES: 295.72 GPM @ 48.91 PSI ' At time of Design 2 -WAY EARTHQUAKE BRACE N0. DESCRIPTION DATE SYM. SIN QTY. K SPRAY ORIF. FIN. TEMP. MFR./MODEL 4 -WAY EARTHQUAKE BRACE R5415 9 5.6 Pendent Z White 155°F G4A Concealed APPROVAL: City of Tukwila HYDRAULIC REFERENCE POINT R5415 4 5.6 Pendent %2 ' White 200°F G4A Concealed CONT. NO.: KS0344 Total = 13 DRAWN BY: Adam Kantner HANGER SYMBOL BRANCHLINE RESTRAINT SPRK. ON SHEET: SEE LEGEND SPRK. ON JOB: DATE: 06/19/08 r -LD TYPICAL FLEXABLE SPRINKLER CONNECTION FLEXHEAD MOUNTING BRACKET PIPE NIPPLE • SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS REDUCING FITTING SIJSPENDED T -BAR GRID SPRINKLER HEAD CEILING TILE FLEXHEAD DETAIL NOT TO SCALE FIG.909 SWIVEL SWAY BRACE FITTING KWIK BOLT .-(21/4' EMBED LENGTH) BRACE PIPE FIG.1090 �"--- "FAST CLAMP" SWAY BRACE ATTACHMENT LINE PIPE LATERAL LINE RESTRAINTS NON -THREADED BRACE PIPE FIG. 4A PIPE CLAMP FOR SWAY BRACE 3/9' KWIK BOLT (2 1/4' EMBED LENGTH) FIG. 909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT LATERAL BRANCHLINE RESTRAINT BRACE PIPE td NON -THREADED BRACE PIPE LATERAL BRANCHLIN RESTRAINT NOT TO SCALE Hanger No. 07C HILTI Kwik Bolt III / HILTI Kwik Boll 11 Drilled Anchor• 5 /L \'\L / Rod Coupling All Thread Rod Cut Rod Lgth Rounded to Nearest Inch Swivel Ring Pipe Concrete Construction Bottom of Concrete to Center Line of Pipe Note on Plan Note on Plan: Hanger Number and 'A' Dimension HANGER DETAIL NOT TO SCALE VICINITY MAP DETAIL NOT TO SCALE Western States Fire Protection Company 7102 180th AVE NE, STE A-105 - REDMOND, WA - 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE/AUSTIN/DALLAS/DECATUR/DEM/ER/DULUTH/HOUSTON/KANSAS CITY LAS VEGAS /MINNEAPOLIS /PHOENIX/PORTLAND 1 RAPID CITY/ ST. PAUL /SALT LAKE CITY/SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 Sbarro 2600 Southcentner Mall Tukwila ,Wa 98188 FIRE SPRINKLER SYSTEM 0 2 i (t3 (1) IY w 0 Adam Kantner 2 0) c7) N 0) a SHEET FP -1 OF 1