Loading...
HomeMy WebLinkAboutPP - 2600 SOUTHCENTER MALL FOOD COURT 5 - UNKNOWN TENANT - PERMITS AND PLANS2600 SOUTHCENTER MALL FC -5 FOOD COURT ASSOCIATED PERMITS 10-F-261 10-S-250 10-H-265 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Bayou Grill 2600 Southcenter Mall FC -5 Permit No.: 10-S-250 Date: November 16, 2010 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 30 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2010 Edition. FIRE DEPARTMENT HOOD SUPPRESSION PLAN REVIEW COMMENTS Project Name: Bayou Grill 2600 Southcenter Mall FC -5 Permit No.: 10-H-265 Date: December 8, 2010 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 P/4. • Nozzle heights above appliances to be per manufacturers installation guidelines. • Fryers shall be installed with at least a 16 inch space between the fryer and surface flames from adjacent cooking equipment or a minimum 8 inch high steel or tempered glass baffle plate shall be installed between the appliances. • Upon activation of the suppression system, the make-up air supply will shut off and the exhaust will keep running. • Type 1 hood systems shall be designed and installed to automatically activate the exhaust fan whenever cooking operations occur. The activation of the exhaust fan shall occur through an interlock with the cooking appliances, by means of heat sensors or by means of other approved methods. • Activation of the suppression system shall shunt all electrical power under the hood as well as the gas supply. • Install a "K" rated portable fire extinguisher within 30 ft. of the cooking equipment. • The hood suppression system shall be monitored by a U.L. Central Monitoring Station. • The suppression system manual pull station shall be located no closer that 10 ft. and no farther than 20 ft. from the cooking equipment and be planed at a height of 42 to 48 inches above the floor. • The inside lower edge of the hood shall overhang or extend a horizontal distance of not less than 6 inches beyond the edge of the top horizontal surface of the appliance on all open sides. The vertical distance between the front lower Hp of the hood and such surface shall not exceed 4 feet. NOZZLE HEIGHT 42IN PIP SIZE in 1/2 total flow point 15 Amerex kp 2 x3.75 fire suppression system ul bayou grill 2600 south center mall Amerex kp 600 hood 16' DUCT 18x18 DUG 18x18 FUSIBLE LINKS 450 maximun flow point 6 .mipimum 18 1982 24x24 El broiler MECHANICAL GAS VALVES t t 16416 16416 11982 18x36 rice cook c 1 t 416416 16416 11982 40" N co Q1 N co wok alkooking equipmint undder the hood shall stay 6" inside from edge of hood 3" 44 ") N N n m 1`"- .- 6 "minimum EXIT ■ MANUAL PULL 48" HEIGHT dep fryer dep fryer 16X16 16X16 All cooking equipment undder the hood shll shut off when system is actuated & make up air unit and gas shut valve to.fire suppression system shall be connected to the fire alarm system Installed by Frank fire portection inc 206 229 5245 K CLASS FIRE EXTI PAID DEC - 3 2010 TUKWILA FIRE Jte(ii Oise AMEREX KP RESTAURANT SYSTEM NOZZLE APPLICATION CHART July 2006 Section 3 Design Page 3-17 Amcrcx KP Wet Chemical System (EX 4658) 4- 5co ,aaococoN E '4*. c '0" c C) 50 in. 1 c �rM c CDOOOcoOO C V�OCD c C c Ur) C c 10ct10 c c c 10 c 't fid' c O cc ODOfl C) CO 42 in. 1 c w X p a es sr C co 'xi , c ti CO ' Unlimited 55.9 in. 11 Unlimited -11 Protection Is not limited to the hems listed on this chart. ModulizIng larger appliances is an acceptable practice. See your Amerex KP Manual for additional information. M e t g mOOOo�OctODO =MMC—N�Mct<-Nr c C 'n C C C C r4-7 depth 40 in. 36 in. 30 in. C Coto Mr C NiCpp ctst C C C 1010 rr C C NNODOUt7) rrrry- C C C Length Unlimited Unlimited Unlimited 0 E C Length e O rN0.—NNN�MN C C Co co M CO OD C 03 C C ct ct C N C OO) C vr C\ C C V'rr NNNMM C '- C C= M 31 in. 31 in. 24 in. 281/2 in. __ J \ CO J o r m C E (p 6 32 In. . C 00 = �+ ? C CO\\aD�NNctNN rp)O•--rrr C C CCCCCC 24 in. 14-24 dia. 30 in. C C C C NN`-NNNII! C C C 3 T- Max. Perimeter 50 in. 100 in. C r 0 O�NNN\ it a NrrNNy- �r r 11982 1 13729 2 4 —11982 4 11983 1 1/2 r r Flow Points i- O O1-rMM a Tr 14 - _. I Nuzzle P/N ' Appliance 1 Deep Fat Fryer — without Drip Pan ; 13729 13729 2-11982 11984 11982 11982 r r N 14178 11982 --1-11982 13729 14178 2-11984 11983 11982 11983 11983 o coco t N G Z 01 r r Nozzle P/N 16416 16416 �r 2-11983 2-11983 3-11983 O') 07 r M Deep Fat Fryer — with Drip Pan Deep Fat Fryer — with Drip Pan Low Proximity Range — Single Burner II Range — Two Burner Range — Two Burner II Range- Two Burners w/Back Shelf ILow Back-Shelf/Salamander — BS Manifold Range — Three Burners Wok Griddle Griddle Griddle Upright Broiler Charbroiler (Lava Rock) Charbroiler (Gas Radiant & Electric Radiant) ! — Chain Broiler — Closed Top Chain Broiler — Nieco Model 9025 /Catalyst (2L__ Natural & Mesquite Charcoal Charbroiler Mesquite Chips & Chunks Charbroiler Plenum Sin le Bank/V-Bank Duct Rectangular Circular Rectangular Circular V. N CNI t� m W [Ifni! z !1,3-.10 z CO 00 0) T.z a Section 3 Design Page 3 — 22 Amerex KP Wet Chemical System (EX 4658) KP DISTRIBUTION PIPING DESIGN LIMITS FOR ALL CYLINDER SIZES When designing a KP system to protect a kitchen containing a Fryer, Wok or Range, the following MINIMUM TOTAL SYSTEM PIPING must be used in accordance with the chart below: PIPING REQUIREMENTS MINIMUM \IINI\It 1I TOTAL APPLIANCE LINEAR FEET tt,11UiVALEf t'FE' t "'P 1NTS'`FoMs STEM, WENN MINIMUM FLOW %Alnl. 6.5 a 10 79 1 2 Range 7 SUPPLY LINE LIMITATIONS: 16.4 4 ina from the distributor block or the discharge fitting to the first tee. CYLINDER FLOW POINTS PIPE SIZE -. MAXIMUM LINEAR.. . A. MAX. QTY .: . JV1AX•:,.QTY.,...<: r MAX,.. QTY.. FEET OF PIPE TEES ELBOWS BUSHINGS :'KP275-8 �E 20 1 5 0 KP375 - 11 3/8 OR 1/2 25 1 5 1 KP475 - 14 1/2 25 1 5 2 KP600 -18 1/2 25 1 5 2 2-KP375 - 22 1/2 30 2 7 2 NOTE: 1. Use 3/8" supply line only when all piping is to be 3/8" pipe. 2. The supply line has a maximum vertical rise above the distributor of 10 feet. SUPPLY BRANCH LINE (including last nozzle branch) LIMITATIONS: All pipe and fittings leaving the first splitting tee in the system and ending with the last nozzle in the last branch line. While the last nozzle branch is included in the piping limitations for the supply branch line, the limitation (pipe size and maximum length) for nozzle branch lines apply to this portion of the supply branch line. CYLINDER FLOW POINTS MAX. FEET OF .,_ PIPE STRAIGHT PIPE SIZE - ,::>::. ., ..,_ MAX. FEET OF PIPE SPLIT .:..;.,,:,MAX:, QTY. TEES , ...- MAX... QTY. ELBOWS ' MAX. QTY. >-, REDUCING BUSHINGS KP275 - 8 3/8 20 25 7 8 0 KP375 -11 3/8 OR 1/2 27 30 10 8 2 KP475 -14 3/8 27 30 12 8 2 KP600 - 18 AS NOTED 35' OF 3/8" OR 1/2" 50' 3/8" PIPE ONLY 14 8 2 2-KP375-22 AS NOTED 40' OF W 45 OF 1/2" 18 8 0 "30' OF 3/8" *30' OF 3/8" NOTE: 1. In a single 3.75 Gallon Straight Pipe System, 5' of pipe may be transferred from the supply line to the supply branch line. *2. The use of 3/8" pipe with two manifold KP375s is only permitted when the supply Line length is equal to or Tess than 20 feet. NOZZLE BRANCH LINE LIMITATIONS: All pipe and fittings leading from the supply branch tee to a system nozzle. CYLINDER TOTAL LINEAR MAX. QTY. MAX. QTY. MAX. QTY. FLOW POINTS PIPE SIZE FEET OF PIPE TEES ELBOWS BUSHINGS KP275 - 8 3/8 32 5 10 0 KP375 -11 3/8 OR 1/2 32 8 12 11 KP475 -14 3/8 32 10 15 0 KP600 - 18 3/8 32 11 18 15 2-KP375 - 22 3/8 32 18 18 20 MAX. PER NO77J F BRANCH 7 3 6 4 GENERAL SYSTEM LIMITATIONS: 1. No W pipe nozzle branches shorter than 12" long. 2. Nozzle types may not be mixed on any nozzle branch line and a maximum of 4 flow points. \3. The discharge fitting, distrib and distribution hose are not to be included in any calculations. 4. No mixing of pipe sizes allowed within pipe categories. Example: if one nozzle branch is to be '/2" pipe then all must be Y2 pipe. %a' ' • = for nozzle lines is allowed only in an 11 flow point system. 5. rlDuct nozzle h9s a ' ximum vertical se above the supply branch line of 4'0". iI Section 3 Design Page 3 —15 Amerex KP Wet Chemical System (EX 4658) , October 21;03 GAS RADIANT CHARBROILER PROTECTION SINGLE FLOW POINT NOZZLE (P/N 11982) One Amerex plenum nozzle (P/N 11982) will protect a gas radiant charbroiler with a cooking surface measuring 24 inches X 24 inches (61 x 61 cm) maximum_ The nozzle uses one flow point_ It must be located 18 to 48 inches (46 — 122 cm) above the cooking surface and anywhere along or within the perimeter aimed towards the center. ELECTRIC RADIANT CHARBROILER PROTECTION SINGLE FLOW POINT NOZZLE (P/N 11982) Note: Electric charbroiiers with a non -grated surface or a solid ribbed surface may be protected using the same limitations as a griddle_ Electric charbroiiers with an open grate may be protected with one Amerex appliance, plenum nozzle (P/N 11982) provided that the area is no larger than 24 inches X 24 inches (61 x 61 cm). The nozzle uses one flow point and must be located within 18 — 48 inches (46 — 122 cm) above the grate surface, anywhere along or within the perimeter of the protected area, aimed towards the center_ LAVA ROCK (CERAMIC/SYNTHETIC) CHARBROILER SINGLE FLOW POINT NOZZLE (PIN 11983) A single Amerex solid fuel appliance plenum nozzle (P/N 11983) will protect a lava rock charbroiler with a maximum cooking surface of 24 inches wide (61 cm) by 24 inches deep - (61 cm). The appliance nozzle uses 1 'A flow point and for this application must be located between 18 to 44 inches (46 to 122 cm) above the cooking surface anywhere along or within the perimeter of the appliance aimed toward the center_ cr 1 trade flux- a Wu. borstals meat bs aneattsattamths exp attoai. toflestop altao cooking salaam 1 • 'October 2003 Section 3 Design Page 3-10 Amerex KP Wet Chemical System (EX 4658) FOUR (4) BURNER RANGE PROTECTION _ TWO (2) FLOW POINT NOZZLE (P/N 14178) The Amerex 4 burner range nozzle (P/N 14178) has two (2) flow points and will protect a range surface area of 24' x 24" (61 x 61 cm). The center to center distance between bumers must not exceed 12 inches. The nozzle must be located 18 - 50" (46 - 127 cm) above the range surface and centered between the bumers. The nozzle is aimed straight down at the center of the appliance NOTE: Maximum and minimum heights must be measured from the tip of nozzle to the surface of the appliance. RANGE PROTECTION -MULTIPLE NOZZLES (P/N 14178) For ranges that have a surface area exceeding the capabilities of a single nozzle, multiple nozzles must be used provided that the surface area of the range is divided into equally sized modules. Each module must be equal to or less than 24" x 24" (61 x 61 cm). NOTE: When using this nozzle to protect a two (2) burner range the aiming point is where an 8.50" radius from the center of each burner crosses one another WOK PROTECTION SINGLE FLOW POINT NOZZLE (P/N 11982) The Amerex appliance plenum nozzle (P/N 11982) has one flow point and will protect a wok with '::dimensions between a minimum diameter of 14" (36 cm) and a maximum diameter of 24" (61 cm) inclusive. The wok must have a height dimension between a minimum of 4" (10 cm) and a maximum of 7" (18 cm) inclusive. The nozzle must be centered over- the center of the wok and located at a height between 40 " (102 cm) and 50" (127 cm) from the bottom of the inside of the wok and aimed at the center of the wok. Mn. Size Max. Size Alm Poen DUCT PROTECTION LIMITATIONS — TWO NOZZLES (2 x PIN 16416) Two Amerex duct nozzles (PIN 16416) will protect ducts with a perimeter of 51 inches to 82 inches (129.5 — 208.3 cm) or a maximum diameter of 26 inches (66 cm). To correctly position the nozzles a rectangular duct should be divided along its longest side into four equal distances. A drcular A nozzle should be placed along a centerlinefthe duct'srequal distances. width (or diameter) with both nozzle be the c at one quart 2-8 inches (5.08 - 20.3 cm) into the duct nodes on the centerline, paced opening and aimed at the center of the cross section of the duct. Each nozzle has one flow point. NOTE: In no case can the diagonal dimension of each module exceed 18.8 inches (46 cm). xs- MAX. DUCT PROTECTION LIMITATIONS 100 IN. PERIMETER TWO —11A FLOW POINT NOZZLES (P/N 11903) The Amerex solid fuel appliance/duct nozzle (P/N 11983) is listed to protect a restaurant cooking exhaust duct of unI mated length and up to 100 perimeter inches (254 cm) or 32 inch diameter (81.2 cm) using two nozzles. The nozzles total three flow points and to properly position the nozzles. a rectangular duct should be divided along its longest side into four equal distances. A circular duct should be divided along its center line into four equal distances. The nozzles are to be placed at one quarter and three quarters position of the duct width (or diameter) with both nozzles on the center Erne, placed 2 - 8 inches (5.08 — 20.3 cm) into the duct opening and aimed straight up in a vertically run duct. NOTE: In no case can the diagonal dimension of the duct exceed 372 inches (94.4 cm) without adding additional duct nozzles. NOTE: The use of one duct nozzle P/1inches 1983 is permitted for duct 50 perimeter less in the same manner as duct nozzle 16416. DUCT PROTECTION LIMITATIONS - TWO NOZZLES (2 it PIN 164101 Two Amerex duct nozzles (P/N 16416) will protect duds with a perimeter of 51 inches to 82 Inches {129.5 — 208.3 cm) or a maidmum diameter of 26 inches (66 cm). To correctly position the nozzles a rectangi.dar duct should be divided along its longest side into four equal distances. A cimular dud should be divided along a centerline into four equal distances. A nozzle should be placed at one quarter of the dud's width (or diameter) with both nozzles on the centerline. paced 2-8 inches (5.08 - 202 cm) into the duct opening and aimed at the center of the cross section of the dud. Each nazzie has one flow point. NOTE: In no case can the diagonal dimension of each module exceed 18.8 inches (46 an). PROTECTION LIMITATIONS 100 DUCT o�t[VEM13) The Amerex solid fuel appliance/duct nozzle (P/N 11983) is listed to protect a restaurant (=king exhaust dud of unlimited length and t to 100 perimeter inches (254 an) or 32 inch diameter (812 m) l three now points andto using two nozzles. should be properly position the nozzles. a g� A d be d duct along its longest side into fax equal should be divided along its center line into four equal distances. The of th es are io th t one � des on the center line, and three quarters position of the duct width (or diameter) placed 2 - 8 inches (5.08 — 20.3 cm) into the dud opening and aimed streight up in a verbosity run duct. NOTE: In no case can the diagonal dimension of the duct exceed 37.2 inches (94.4 cm) without adding addiuonai axe i"'u as. NOTE: The use of one duct nozzle P/N 11983 is permitted for duct 50 perimeter inches or less in the same manner as duct nozzle 16416. zx MAX. ACCEP1ID O Without Comments Er As Noted in Red ®' Per The Attached Letter These plans have been reviewed by The Tukwila Fire 'reventlon Bureau for conformance with current City standards. Acceptance: is subject r_., errors and omissions which do not authorize violations of adopted andards and ordinances. The responsibility for the adequacy of design rests totally with the designer, Additions, deletions or revisions to these drawings after Jthis date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: I -8-10 By: s 11 curaiii.A FIRE DEPARTIWIX Please cafl: 575•44O and give this job No. 10 -Pi ).(#S + id exact address for shut. gun or restoration aporoval FIRE ALA:'' M S UK ILA, I TE DDITION ASHING N SHEET \U V 3E SHEET TITLE FA -01 SYSTEM \FOIVATIO\ FA -02 TYPICAL WHI\G A \D NOUNTI \G DETAILS FA -03 SYSTEv CALCULATIO\ S A N D SI\GLE LI\E DIAG A VI FA -04 FRE ALA vl SYSTE V PLA\ SHEET INDEX C1i Without. Comments ,] As Noted in Red l� Ped The . attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau fc,!. cc,nforrnance with current City standards. Acceprar11 iF: subject to errors and omissions which do i -icy .;iithorize violations of adopted landards andesponsibiiity for the adequacy of :otally with the designer. Additions; deletio 1s= •cj visions to these drawings after chis date will void ths a cceptance -and will require a ;•esubmittai of revised drawings for subsequent approval r'inal acceptance 3ubiec t to field test and Inspection by, The Tukwila Fire Prevention Bureau. Date:! Z3././9 Bv: _,Al) 1 NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee ant termination of the testin% 1 "M+KWtLA FIRE DEPARTrVfsalL Please call: 575.4407, and give this job No. /0- F.) 4 )nd exact address for shut. uswn or restoration approval) WITEIIEDULE A\D CO\SUIT FILL CHAT WIRE DESIGNATION SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V' SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL •1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END WIRE DESIGNATION FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2, DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED GENERAL NOTES QUANTITY 1 1 3 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT BPS REMOTE BOOSTER POWER SUPPLY PAD -3 SIEMENS PAD-3-ENCL 66" A.F.F. TO TOP HTR -R INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP BOX VERIFY IN FIELD S FIRE ALARM SPEAKER STROBE SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2 EXTN CO JUNCTION BOX N/A N/A N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N -/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A SYMBOLS LEGEND 1:2000] MJN1 ANCHOR U 1- 0 120051 W 01 01 c 0 J 30 6 12113] 121201 0 O 0 0 0 IT 0 W 4 0 0 0 O w 121701 L175] 1 121801 __ rn A 12.1301 ❑ a 0 12.2061 13 ❑ CllAi01 m U 123101 1 R&�AIL 0 n ❑ ❑ 0 ❑ ❑ I FC1 1 JOHNNY 1 FC121i IFC1oI Tyvqj 11 of Cc>_51 THAI GO o 15HAI�K\i''S [2205. w vi 0 N 0 AUNIANCi10R a It F- 0) v _0 122001 0 K IFC31 SARKU RETAIL 0 \SUSHI TT)) 4%7- FAX (206) 628-4990 RELEASE/REVISIONS REV. BY: DMG DESCRIPTION SHOP DRAWINGS DATE 11/30/10 2 aaaaa 0 O v� J o 8z C'3w--I° z 0 E < D;T) U. O 2W m Q V_ Lu cc i- 0 0 11.1 >v 0) 0) RETAIL ---,yap-- - ROOF ROOF / \ROO ' T RAGE TERRACE BAYOU GRILL (2600, FOOD COURT #5) 2ND LEVEL PAID DEC -32010 TUKWILA FI13.E -6/b969' x7s' SITE PLAN Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved �CALE: NOT TO SCALE" DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 1 1 /30/1 0 BACKROUND PLAN PROVIDED BY: \0B NUMBER: 1 SHEET FA -01 120VAC-60H2 — DEDICATED EMERGENCY THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DUCK OVER 3' WIDE; SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. TUBE OUTLET SAMPLING TUBE INLET SAMPLING AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. *CONTACT RATINGS 4.0A 0 125VAC 4.0A 0 30VDC RIfIi1SOROIINIDINOD TO NEXT ADDRESSABLE (+ DEVICE STOP IF LAST DEVICE - rim XLS CDNTRW. PANEL (f DR PREVIOUS ADDRESSABLE DEVICE O 0 © O co.HTRI-R I g 1 O 0 NOTE EEADDITIONAL CATOS SEE ODUTDOCUMENATIN C -CABLE C -CABLE PAD -3 00n INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ - 1 2+ 2- 2 NC C NO + - + - + - + - + - 0 0 I h.. s2 3.6k EOL (-) (+) SPARE FROM PREVIOUS > (+) ADDRESSABLE > DEVICE (-) I1❑ NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. s C7 m 0 0 (=)(-) (+)(+) g (+) WIRE DESIGNATION; NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE TWISTED PAIR WITH SHELD #18 FPLIFPLR RED (JACKET) *CONTACT RATINGS 4.0A 0 125VAC 4.0A 0 30VDC FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. O 0 4 r 0 0 0 0 —LT!: J- I HTRI-R I g( J GROUND ❑II I 1 e' Z (:&: II 1 1 � , o, Q� I o o 0 ®` o C,°" 0=1 10= 7 6 = ILII � .1'1;7 �- " - '� toconox - Iro •- �ecocrox " ' 11 •- tecoc►ox 11 - tteocrox " 11 B - b rri l rrl- 1 lkiiiiiiiitis _,I_ : ® / .. 9 . g v ` Imo■ .: r .. • 00 a❑ SPARE SPARE (-) POWER SUPPLY & RELAY MODULE WIRING DETAIL FROM PRECEDING SPEAKER < OR FIRE ALARM CONTROL PANEL < (+) (+) (-) 0 (+)> TO NEXT DEVICE OR STOP IF LAST DEVICE (-) DRY CONTACTS TO VAV FAN SHUTDOWN PROVIDED BY MECH/ELEC. DUCT DETECTOR, TEST SWITCH & RELAY MODULE WIRING DETAIL STROBE SPEAKER L ❑ ❑ I1 - 1 _ e' Z (:&: El - O 1 i � , o, Q� I o o 0 ®` /.n.m ' 0=1 10= 7 6 = ILII � �- " - '� toconox - Iro •- �ecocrox " ' 11 •- tecoc►ox 11 11 a' 1:1:1:1:1 11:1:1- B - b rri l rrl- 1 lkiiiiiiiitis _,I_ : -Tj 1 o o l_ IL® X , 1I-: 0 a 40 ,,,,2 .. • 00 (-) ❑OD STROBE CIRCUIT STROBE =❑ I — O 1 — e' Z (:&: 1 . � 1 1 � , o, 0 o * "1:0t. ( .. e, /.n.m ' 0=1 10= 1111 � �- " - '� toconox - Iro •- tecoc►ox 11 a 1 rrrl n:ri- - b rri l rrl- lkiiiiiiiitis _,I_ _ 1 I (-) (-) SPEAKER CIRCUIT (+) (+) ❑a STROBE SPEAKER/STROBE ❑IJ a❑ (-) STROBE ❑Ol CIRCUIT (-) SPEAKER CIRCUIT SPEAKER STROBES & STROBES ONLY WIRING DETAIL TYPICAL WIRING AND MOUNTING DETAILS (+) S TO NEXT APPLIANCE S OR 24K (EOLR) (+) (+) S TO NEXT SPEAKER OR END OR LINE RESISTOR S 24K (EOLR) (-) SPEAKER CIRCUIT NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER TIN TEMPERA RE: +32' F 0' C TO 100' F (38 C) HUMIDITY: —9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR --> FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE r DATA IN ( ) Sl DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION HATH DUCT HOUSINGS AD -11P OR AD-11XPR STANDDB-11ARD SMOKE DETECTORBASE rr REAR VIEW (-) (+) SMOKE DETECTOR WIRING DETAIL HARD LID —\ �.: ::,;:; ; SPEAKER SUPPORT TILE BRIDGE ProDrietar > TO NEXT ADDRESSABLE DEVICE 4" SQUARE DEEP BOX WITH 1-1/2" EXTENSI❑N — CEILING MOUNTED SPEAKER/STROBE SPEAKER STROBE MOUNTING DETAIL JUNCTION BOX 1 JUNCTION BOX MOUNTED ON CEILING FLEX MOUNTED AGAINST CEILING SUPPORT 0 0 TO NEXT DEVICE CADDY BAR SMOKE/HEAT DETECTOR SUSPENDED ILLUMINATED CEILING SMOKE/HEAT DETECTOR MOUNTING DETAIL 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS 4 LL. Z OW 0U7- F rn """"1 8z F- `C 0w Q z 2Fo O 2 w� cc ca cc (i) O co �CALE: NOT J ttttett� W 0 0 z 0 0 z z OC tttttJ .) U L.B. TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 1 1 /30/1 0 BACKROUND PLAN PROVIDED BY: 10B NUMBER: 1 C SHEET FA -02 and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved J o quo 1 1 � , O O(A /.n.m ' 0=1 10= t I� i \ •- tecoc►ox 11 \ - b rri l rrl- lkiiiiiiiitis _,I_ _ 1 a❑ (-) STROBE ❑Ol CIRCUIT (-) SPEAKER CIRCUIT SPEAKER STROBES & STROBES ONLY WIRING DETAIL TYPICAL WIRING AND MOUNTING DETAILS (+) S TO NEXT APPLIANCE S OR 24K (EOLR) (+) (+) S TO NEXT SPEAKER OR END OR LINE RESISTOR S 24K (EOLR) (-) SPEAKER CIRCUIT NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER TIN TEMPERA RE: +32' F 0' C TO 100' F (38 C) HUMIDITY: —9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR --> FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE r DATA IN ( ) Sl DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION HATH DUCT HOUSINGS AD -11P OR AD-11XPR STANDDB-11ARD SMOKE DETECTORBASE rr REAR VIEW (-) (+) SMOKE DETECTOR WIRING DETAIL HARD LID —\ �.: ::,;:; ; SPEAKER SUPPORT TILE BRIDGE ProDrietar > TO NEXT ADDRESSABLE DEVICE 4" SQUARE DEEP BOX WITH 1-1/2" EXTENSI❑N — CEILING MOUNTED SPEAKER/STROBE SPEAKER STROBE MOUNTING DETAIL JUNCTION BOX 1 JUNCTION BOX MOUNTED ON CEILING FLEX MOUNTED AGAINST CEILING SUPPORT 0 0 TO NEXT DEVICE CADDY BAR SMOKE/HEAT DETECTOR SUSPENDED ILLUMINATED CEILING SMOKE/HEAT DETECTOR MOUNTING DETAIL 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS 4 LL. Z OW 0U7- F rn """"1 8z F- `C 0w Q z 2Fo O 2 w� cc ca cc (i) O co �CALE: NOT J ttttett� W 0 0 z 0 0 z z OC tttttJ .) U L.B. TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 1 1 /30/1 0 BACKROUND PLAN PROVIDED BY: 10B NUMBER: 1 C SHEET FA -02 and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved J ',.(-1- 01 •=,,,'' 'i,,`; < .-4',,, f 0. ,`,,; ,,I.,, 4 , , ''..,;,,,,;,“;,i1 .:, : • .:, .21,, r ,'. , '',„ ,'''''' FAG Db�SCurrent "..i..' "1'4,-'' ':' ii`; .1- > -, ' ., •- ,,,,, ./4 4 1. ! F I) ii.: '' _ '' q` ' ' } *; ' '' W.:.i.: , ',' ''°.,'''' 1.3 V., ' " , P.,, P ','',,t'' ''' ''i• ,; .•'::1; ,tak,j'',,,,,.,,. " '''?:1'4''''''1:41''' ' '''''''''' ''' ' ".1.4a,',4', , , •' ',.,' '="'" ''','''''''' i,..,i,',::„; ,:' ,...;:AI ''''' '''" ''''''''' ' ' ' ''''',,' ,:,''C,r+ ' Load: Standby: Alarm: . Device Type Qty Amps Total Device Type Qty Amps Total Amps Total • HFP-11 0.0022 0.0022 0.0023 0.000 0.03 AD2-P 0.030 0.0635 0.0635 0.064 0.000 . HTR -R 1 0.009600 0.0096 0.021 0.021 0.131 0.131 SETMC.C-©75CD ' . : , . :1 0.222 ' : 0.222 SET -MC -C @95CD 0.292 0.0731 Amps 0.021 Amps ',.(-1- 01 •=,,,'' 'i,,`; < .-4',,, f 0. ,`,,; ,,I.,, 4 , , ''..,;,,,,;,“;,i1 .:, : • .:, .21,, r ,'. , '',„ ,'''''' DESCRIPTION SHOP DRAWINGS ] "..i..' "1'4,-'' ':' ii`; .1- > -, ' ., •- ,,,,, ./4 4 1. ! F I) ii.: '' _ '' q` ' ' } *; ' '' W.:.i.: , ',' ''°.,'''' 1.3 V., ' " , P.,, P ','',,t'' ''' ''i• ,; .•'::1; ,tak,j'',,,,,.,,. " '''?:1'4''''''1:41''' ' '''''''''' ''' ' ".1.4a,',4', , , •' ',.,' '="'" ''','''''''' i,..,i,',::„; ,:' ,...;:AI ''''' '''" ''''''''' ' ' ' ''''',,' ,:,''C,r+ ' 2 „ . Device Type Qty Amps Total Amps Total • Main System Board 1 0.03 0.03 0.030 0.030 SET -MC -C @1 CD . ' ' 1 ' , . 0.0875 's 0.088 1SET-MC-C @30CD 1 0.131 0.131 SETMC.C-©75CD ' . : , . :1 0.222 ' : 0.222 SET -MC -C @95CD 0.292 SET -MC -C 1 OCD : 0.259 ZR -MC ©15CD 0.064 ZR -MC ©30CD . „ -- 0.098 ZR -MC @75CD 0.2 • 0.03 Amps 0.4705 Amps Standby Current Load: ' „ : 0.03 Amps .. For 24 Hours = '' 0.720 Amp -hours Alarm Current Load: - . 0.4705 Amps... For5 Minutes.= ' . .". 0.040 Amp -hours • " ' , . 25% Derating = . ' 0.949 Amp -hours Total System Current Load: 0.949 Amp -hours . , . Satte, ,cki ai TJA -,..; - ,,:.,.Used'-'.-.„4,:iv,,'TJAA:,12VC,-4, 7- t,ii, ''" v2A '-$.' .:7-,,,e-?-:,•). " ';'7.'..'"'... ::',.-r.:;,;V:':;,-,;',',,i1 Notification Appliance Circuit Detail PROJECT: BAYOU GRILL Panel PAD -3 POWER SUPPLY 1Wire Resistance 2.58 Date: December 1, 2010 CURRENT TOTAI:=12485.50 1SET-MC-C @15CD 87.51 87.5 SET-MC-C@30CP 131 131 1 1SET-MC-C @75CD 222 222 'SET4C-C 695CD 292 - 0 0 1ZR-MC @110CD 1 259 0 0 M411 C I 5C D 0 aC @ 50. DD 0 @ y .. DEVICES=13 64 0 98 01 175 0 TOTALrnA=1 440.51 14 Total Wire Resistance ( R ) Total Device Load, Amps (I) 1Voltage Drop ( E ) EOL Voltage J • 183 23.581 440.51 ( WL * 2 )* (R/ft) 0.941 (Total COt Load) 0.44 1(E= I * R) 0.421 24 - E) 23.58 Notification Appliance Circuit Detail i I PROJECT: BAYOU GRILL Panel: XLS-V !Wire Resistance 2.58 Date: December 1, 2010 CURRENT toTAH#REF! 18 70.7V 1/4 0 70.7V1/2 70.7V 1 DEV10ES=165 3.54 63.72 0 0 0 0 TOTAL mA= 148.321 14 Total Wire Resistance ( R ) Total Device Load, Amps (1) Voltage Drop ( E) EOL Voltage 1,327 19.3844055, 148.32 I( WL* 2) * (R/ft) 6.85 (TOtal-cpt- Load). •0,15 (E= I *.F1) 1 1.02 SYSTEM CALCULATIONS EX EX8 V V (HALLWAY) 13 EX BPS 2C 120VAC, DEDICATED (BY OTHERS) BPS (ELECTRICAL ROOM) HTR -R S1-1 15cd V-1 1/4-W S1-2 75cd V-2 1/4-W S1-3 30cd V-3 1/4-W EOL S1 FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. NEW SIEMENS PAD -3 BOOSTER POWER SUPPLY SHALL BE LOCATED IN THE ELECTRICAL ROOM. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 11OVAC BRANCH CIRCUIT. C/3 co 0' 1743 1ST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 m 0 DESCRIPTION SHOP DRAWINGS ] DATE 11/30/10 2 <KKK< CC 0 uJ z -J w Z 0 28 rz coS Z - o ooz EE mut w --lz z g_ < 2(T) < 0 (I) <iuji OZ w cc nn F- 0 0 c‘, w (1) ‘CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 1 1 /30/1 0 BACKROUND PLAN PROVIDED BY: SINGLE LINE DIAGRAM \0B NUMBER: Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved \ SHEET FA -03 —UJASI-TABLE �nr............ CEILING TILE TI -IIS AREA N \N, S1-1 V1`1N (CEILING: +12) / N 0 i/// r. / // ////// '//// /c) \`� C (GW) CEILING) (+12'-0") / 7 2x4 SUSPENDED / ACOUSTIC CEILING. - .....J - J / J 7/7 7 /77 / / zzJ �5 DEDICATE (I) LIGHT FIXTURE PER TENANT SPACE TO BE ILLUMINATED AT ALL TIMES, TY"P. / / • / //7 S S1-3 -� 30cd ��)) V1-3 —, 'N" /5 ' \ CO REFLECTED CEILING PLAN EXISTING ADJACENT TENANT_ r ---"SUBWAY" (GWB SOFFIT) (+12'-O") TO ELECTRICAL ROOM (S -WIRES TO NEW POWER SUPPLY & D -WIRES TO EXISTING SMOKE DETECTOR) D,S dR'RJ 0_14"1 0 i ELECT PANEL DRY FOOD SHELVING S1-1 1 5cd V1-1 --- EMPLOYEE LOCKERS / 7 / 'i' Cly) FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. NEW SIEMENS PAD -3 BOOSTER POWER SUPPLY SHALL BE LOCATED IN THE ELECTRICAL ROOM. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 11OVAC BRANCH CIRCUIT. BACK KITCHEN D,S KITCHEN V,V1 0 0 EX WALK-IN COOLER i WALK-IN j FREEZER / /r / //ZZ2%27 I222ZZ/%1Z1.11r1'-Z 277ZZZ. COFFEE BREWER SINK EOL S1 22222 S,V,V \ ,_,, , S S1-2\ moo 75cd V1-2 \ V' \\ S1-3 30cd V1-3 COLN F c�8/ oa 7-y_ 7:5 ryQC! SERVICE COUNTER AREA COLUMN JUICE DISPLAY FIRE ALARM SYSTEM PLAN R4 z yy 144 z 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 DESCRIPTION SHOP DRAWINGS DATE 11/30/10 2a<aa< i - /5 ' \ CO REFLECTED CEILING PLAN EXISTING ADJACENT TENANT_ r ---"SUBWAY" (GWB SOFFIT) (+12'-O") TO ELECTRICAL ROOM (S -WIRES TO NEW POWER SUPPLY & D -WIRES TO EXISTING SMOKE DETECTOR) D,S dR'RJ 0_14"1 0 i ELECT PANEL DRY FOOD SHELVING S1-1 1 5cd V1-1 --- EMPLOYEE LOCKERS / 7 / 'i' Cly) FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. NEW SIEMENS PAD -3 BOOSTER POWER SUPPLY SHALL BE LOCATED IN THE ELECTRICAL ROOM. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 11OVAC BRANCH CIRCUIT. BACK KITCHEN D,S KITCHEN V,V1 0 0 EX WALK-IN COOLER i WALK-IN j FREEZER / /r / //ZZ2%27 I222ZZ/%1Z1.11r1'-Z 277ZZZ. COFFEE BREWER SINK EOL S1 22222 S,V,V \ ,_,, , S S1-2\ moo 75cd V1-2 \ V' \\ S1-3 30cd V1-3 COLN F c�8/ oa 7-y_ 7:5 ryQC! SERVICE COUNTER AREA COLUMN JUICE DISPLAY FIRE ALARM SYSTEM PLAN R4 z yy 144 z 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 DESCRIPTION SHOP DRAWINGS DATE 11/30/10 2a<aa< 0 cc c .0c-6 - D o� ooz (f) CC Q LL" o >1. wtz D= U) D(T) O °i CC I— < 11.6 � w =� cc 1- u_ 01- 0 O N W 4-CALE: 3/8"=1 '0" DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE:1 1 /30/ 10 BACKROUND PLAN PROVIDED BY: .1OB NUMBER: SHEET FA -04 Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved % EMERGENCY EXIT SIGN W/ BACK-UP BATTERY, TYP CEILING TILE THIS AREA RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD ROD PIPE SWIVEL RING DICATE (I) LIGHT Fl TURE PER TE T SPACE TO BE I �UMINATED AT ALL T f; IES, TYP. STEEL JOIST/TRUSS HANGER DETAIL NTS REFLEGTED CEILING FLAN Design per NFPA 13, Ordinary Hazard 130 sq ft All materials to be new, U.L. listed, and F.M. approved All fire sprinkler heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart 7— Add Reliable Model F1 Standard Response 155° Pendants 1/2 x 1/2 3- Add Reliable Model G4A Standard Response 155 Consealed155 1/2x1/2 2- Add Reliable Model F3 Dry Pendants Standard Response 200 1/2 xl/2 12 — Total (d) = Ductile iron Model MT -3 & MT -9 Mechanical tea serves the same function as MTI z MT -8 but uses a steel electro plated u -bolt to save space and for easier insrnliaUan In tight places. It is ideal for direct connections with sprinkler heads and drop nipples. HOUSING: Ductile iron ASTMA536 grade 85-45-12. COATING: Zine electroplated U - BOLT: Carbon steel SAE grade 2, zinc plated. NUT: Carbon steel ASTM A194, zinc plated. GASKET: EPDM (-30°F to + 230°F) THREADS: MT -3 NPT per ANSI/ASME 81.20.1 MT -9 British standard parall0l (BOP) per BS21 Illi Tri,&`MT 9vMEC1-1AIW LTi=1 ma 1 4L M•1=. M •L! DIMIN510Nf.lnorm I -�- - E — APPROX. WLIGNT Q WItheut Comments Er As Noted in Red 12r Per The Attached Letter -ese plans have been reviewed by The Tukwila Fire .evention Fureal..+ r:,, : Infornraocc. with current CIty �ndards. ?cc r:.t , r:: errors and nissions whirl= : ; ., i, a= rl.horizp violations of adopted 3ndards ana c : c:.. :enc s rh i esponslhfllty for the ,equacy ,r cies1T rests totally with the designer. dltiofis. deleliof:s r:= R visions to these drawingsS,after ,s date mil void the acceptance and will require'a ,submittar r!I !-; � sec: drawings for subsequent approval. nal acceptance is subject to field test and Inspection by ne Tukwila Fire Prevention Bureau. Date: / I - I CO /6 By: ,4, ' i y / ( titiKWILA FIRE DEPARTMai1 Please calf: 575.4407 and give this job No. / (7 -S- e): S� and exact address for shut. o4min or rest;;ration approval. NOTICE Weld stamps must be inspected before pipe is hung. Do not paint piping prior to hydrostatic test approval. CROV\/N FIRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 BAYOU GRILL 2600 SOUTHGENTER MALL • FOOD COURT #5 TUKWILA, NA 98188-2816 DATE: DRAWN: I SCALE: PAID NOV 10 2010 TUKWILA FIRE 1.c3 2600 SOUTHCENTER MALL FC -5 FOOD COURT ASSOCIATED PERMITS 10-F-261 10-S-250 10-H-265 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Bayou Grill 2600 Southcenter Mall FC -5 Permit No.: 10-S-250 Date: November 16, 2010 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 30 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2010 Edition. FIRE DEPARTMENT HOOD SUPPRESSION PLAN REVIEW COMMENTS Project Name: Bayou Grill 2600 Southcenter Mall FC -5 Permit No.: 10-H-265 Date: December 8, 2010 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 P/4. • Nozzle heights above appliances to be per manufacturers installation guidelines. • Fryers shall be installed with at least a 16 inch space between the fryer and surface flames from adjacent cooking equipment or a minimum 8 inch high steel or tempered glass baffle plate shall be installed between the appliances. • Upon activation of the suppression system, the make-up air supply will shut off and the exhaust will keep running. • Type 1 hood systems shall be designed and installed to automatically activate the exhaust fan whenever cooking operations occur. The activation of the exhaust fan shall occur through an interlock with the cooking appliances, by means of heat sensors or by means of other approved methods. • Activation of the suppression system shall shunt all electrical power under the hood as well as the gas supply. • Install a "K" rated portable fire extinguisher within 30 ft. of the cooking equipment. • The hood suppression system shall be monitored by a U.L. Central Monitoring Station. • The suppression system manual pull station shall be located no closer that 10 ft. and no farther than 20 ft. from the cooking equipment and be planed at a height of 42 to 48 inches above the floor. • The inside lower edge of the hood shall overhang or extend a horizontal distance of not less than 6 inches beyond the edge of the top horizontal surface of the appliance on all open sides. The vertical distance between the front lower Hp of the hood and such surface shall not exceed 4 feet. NOZZLE HEIGHT 42IN PIP SIZE in 1/2 total flow point 15 Amerex kp 2 x3.75 fire suppression system ul bayou grill 2600 south center mall Amerex kp 600 hood 16' DUCT 18x18 DUG 18x18 FUSIBLE LINKS 450 maximun flow point 6 .mipimum 18 1982 24x24 El broiler MECHANICAL GAS VALVES t t 16416 16416 11982 18x36 rice cook c 1 t 416416 16416 11982 40" N co Q1 N co wok alkooking equipmint undder the hood shall stay 6" inside from edge of hood 3" 44 ") N N n m 1`"- .- 6 "minimum EXIT ■ MANUAL PULL 48" HEIGHT dep fryer dep fryer 16X16 16X16 All cooking equipment undder the hood shll shut off when system is actuated & make up air unit and gas shut valve to.fire suppression system shall be connected to the fire alarm system Installed by Frank fire portection inc 206 229 5245 K CLASS FIRE EXTI PAID DEC - 3 2010 TUKWILA FIRE Jte(ii Oise AMEREX KP RESTAURANT SYSTEM NOZZLE APPLICATION CHART July 2006 Section 3 Design Page 3-17 Amcrcx KP Wet Chemical System (EX 4658) 4- 5co ,aaococoN E '4*. c '0" c C) 50 in. 1 c �rM c CDOOOcoOO C V�OCD c C c Ur) C c 10ct10 c c c 10 c 't fid' c O cc ODOfl C) CO 42 in. 1 c w X p a es sr C co 'xi , c ti CO ' Unlimited 55.9 in. 11 Unlimited -11 Protection Is not limited to the hems listed on this chart. ModulizIng larger appliances is an acceptable practice. See your Amerex KP Manual for additional information. M e t g mOOOo�OctODO =MMC—N�Mct<-Nr c C 'n C C C C r4-7 depth 40 in. 36 in. 30 in. C Coto Mr C NiCpp ctst C C C 1010 rr C C NNODOUt7) rrrry- C C C Length Unlimited Unlimited Unlimited 0 E C Length e O rN0.—NNN�MN C C Co co M CO OD C 03 C C ct ct C N C OO) C vr C\ C C V'rr NNNMM C '- C C= M 31 in. 31 in. 24 in. 281/2 in. __ J \ CO J o r m C E (p 6 32 In. . C 00 = �+ ? C CO\\aD�NNctNN rp)O•--rrr C C CCCCCC 24 in. 14-24 dia. 30 in. C C C C NN`-NNNII! C C C 3 T- Max. Perimeter 50 in. 100 in. C r 0 O�NNN\ it a NrrNNy- �r r 11982 1 13729 2 4 —11982 4 11983 1 1/2 r r Flow Points i- O O1-rMM a Tr 14 - _. I Nuzzle P/N ' Appliance 1 Deep Fat Fryer — without Drip Pan ; 13729 13729 2-11982 11984 11982 11982 r r N 14178 11982 --1-11982 13729 14178 2-11984 11983 11982 11983 11983 o coco t N G Z 01 r r Nozzle P/N 16416 16416 �r 2-11983 2-11983 3-11983 O') 07 r M Deep Fat Fryer — with Drip Pan Deep Fat Fryer — with Drip Pan Low Proximity Range — Single Burner II Range — Two Burner Range — Two Burner II Range- Two Burners w/Back Shelf ILow Back-Shelf/Salamander — BS Manifold Range — Three Burners Wok Griddle Griddle Griddle Upright Broiler Charbroiler (Lava Rock) Charbroiler (Gas Radiant & Electric Radiant) ! — Chain Broiler — Closed Top Chain Broiler — Nieco Model 9025 /Catalyst (2L__ Natural & Mesquite Charcoal Charbroiler Mesquite Chips & Chunks Charbroiler Plenum Sin le Bank/V-Bank Duct Rectangular Circular Rectangular Circular V. N CNI t� m W [Ifni! z !1,3-.10 z CO 00 0) T.z a Section 3 Design Page 3 — 22 Amerex KP Wet Chemical System (EX 4658) KP DISTRIBUTION PIPING DESIGN LIMITS FOR ALL CYLINDER SIZES When designing a KP system to protect a kitchen containing a Fryer, Wok or Range, the following MINIMUM TOTAL SYSTEM PIPING must be used in accordance with the chart below: PIPING REQUIREMENTS MINIMUM \IINI\It 1I TOTAL APPLIANCE LINEAR FEET tt,11UiVALEf t'FE' t "'P 1NTS'`FoMs STEM, WENN MINIMUM FLOW %Alnl. 6.5 a 10 79 1 2 Range 7 SUPPLY LINE LIMITATIONS: 16.4 4 ina from the distributor block or the discharge fitting to the first tee. CYLINDER FLOW POINTS PIPE SIZE -. MAXIMUM LINEAR.. . A. MAX. QTY .: . JV1AX•:,.QTY.,...<: r MAX,.. QTY.. FEET OF PIPE TEES ELBOWS BUSHINGS :'KP275-8 �E 20 1 5 0 KP375 - 11 3/8 OR 1/2 25 1 5 1 KP475 - 14 1/2 25 1 5 2 KP600 -18 1/2 25 1 5 2 2-KP375 - 22 1/2 30 2 7 2 NOTE: 1. Use 3/8" supply line only when all piping is to be 3/8" pipe. 2. The supply line has a maximum vertical rise above the distributor of 10 feet. SUPPLY BRANCH LINE (including last nozzle branch) LIMITATIONS: All pipe and fittings leaving the first splitting tee in the system and ending with the last nozzle in the last branch line. While the last nozzle branch is included in the piping limitations for the supply branch line, the limitation (pipe size and maximum length) for nozzle branch lines apply to this portion of the supply branch line. CYLINDER FLOW POINTS MAX. FEET OF .,_ PIPE STRAIGHT PIPE SIZE - ,::>::. ., ..,_ MAX. FEET OF PIPE SPLIT .:..;.,,:,MAX:, QTY. TEES , ...- MAX... QTY. ELBOWS ' MAX. QTY. >-, REDUCING BUSHINGS KP275 - 8 3/8 20 25 7 8 0 KP375 -11 3/8 OR 1/2 27 30 10 8 2 KP475 -14 3/8 27 30 12 8 2 KP600 - 18 AS NOTED 35' OF 3/8" OR 1/2" 50' 3/8" PIPE ONLY 14 8 2 2-KP375-22 AS NOTED 40' OF W 45 OF 1/2" 18 8 0 "30' OF 3/8" *30' OF 3/8" NOTE: 1. In a single 3.75 Gallon Straight Pipe System, 5' of pipe may be transferred from the supply line to the supply branch line. *2. The use of 3/8" pipe with two manifold KP375s is only permitted when the supply Line length is equal to or Tess than 20 feet. NOZZLE BRANCH LINE LIMITATIONS: All pipe and fittings leading from the supply branch tee to a system nozzle. CYLINDER TOTAL LINEAR MAX. QTY. MAX. QTY. MAX. QTY. FLOW POINTS PIPE SIZE FEET OF PIPE TEES ELBOWS BUSHINGS KP275 - 8 3/8 32 5 10 0 KP375 -11 3/8 OR 1/2 32 8 12 11 KP475 -14 3/8 32 10 15 0 KP600 - 18 3/8 32 11 18 15 2-KP375 - 22 3/8 32 18 18 20 MAX. PER NO77J F BRANCH 7 3 6 4 GENERAL SYSTEM LIMITATIONS: 1. No W pipe nozzle branches shorter than 12" long. 2. Nozzle types may not be mixed on any nozzle branch line and a maximum of 4 flow points. \3. The discharge fitting, distrib and distribution hose are not to be included in any calculations. 4. No mixing of pipe sizes allowed within pipe categories. Example: if one nozzle branch is to be '/2" pipe then all must be Y2 pipe. %a' ' • = for nozzle lines is allowed only in an 11 flow point system. 5. rlDuct nozzle h9s a ' ximum vertical se above the supply branch line of 4'0". iI Section 3 Design Page 3 —15 Amerex KP Wet Chemical System (EX 4658) , October 21;03 GAS RADIANT CHARBROILER PROTECTION SINGLE FLOW POINT NOZZLE (P/N 11982) One Amerex plenum nozzle (P/N 11982) will protect a gas radiant charbroiler with a cooking surface measuring 24 inches X 24 inches (61 x 61 cm) maximum_ The nozzle uses one flow point_ It must be located 18 to 48 inches (46 — 122 cm) above the cooking surface and anywhere along or within the perimeter aimed towards the center. ELECTRIC RADIANT CHARBROILER PROTECTION SINGLE FLOW POINT NOZZLE (P/N 11982) Note: Electric charbroiiers with a non -grated surface or a solid ribbed surface may be protected using the same limitations as a griddle_ Electric charbroiiers with an open grate may be protected with one Amerex appliance, plenum nozzle (P/N 11982) provided that the area is no larger than 24 inches X 24 inches (61 x 61 cm). The nozzle uses one flow point and must be located within 18 — 48 inches (46 — 122 cm) above the grate surface, anywhere along or within the perimeter of the protected area, aimed towards the center_ LAVA ROCK (CERAMIC/SYNTHETIC) CHARBROILER SINGLE FLOW POINT NOZZLE (PIN 11983) A single Amerex solid fuel appliance plenum nozzle (P/N 11983) will protect a lava rock charbroiler with a maximum cooking surface of 24 inches wide (61 cm) by 24 inches deep - (61 cm). The appliance nozzle uses 1 'A flow point and for this application must be located between 18 to 44 inches (46 to 122 cm) above the cooking surface anywhere along or within the perimeter of the appliance aimed toward the center_ cr 1 trade flux- a Wu. borstals meat bs aneattsattamths exp attoai. toflestop altao cooking salaam 1 • 'October 2003 Section 3 Design Page 3-10 Amerex KP Wet Chemical System (EX 4658) FOUR (4) BURNER RANGE PROTECTION _ TWO (2) FLOW POINT NOZZLE (P/N 14178) The Amerex 4 burner range nozzle (P/N 14178) has two (2) flow points and will protect a range surface area of 24' x 24" (61 x 61 cm). The center to center distance between bumers must not exceed 12 inches. The nozzle must be located 18 - 50" (46 - 127 cm) above the range surface and centered between the bumers. The nozzle is aimed straight down at the center of the appliance NOTE: Maximum and minimum heights must be measured from the tip of nozzle to the surface of the appliance. RANGE PROTECTION -MULTIPLE NOZZLES (P/N 14178) For ranges that have a surface area exceeding the capabilities of a single nozzle, multiple nozzles must be used provided that the surface area of the range is divided into equally sized modules. Each module must be equal to or less than 24" x 24" (61 x 61 cm). NOTE: When using this nozzle to protect a two (2) burner range the aiming point is where an 8.50" radius from the center of each burner crosses one another WOK PROTECTION SINGLE FLOW POINT NOZZLE (P/N 11982) The Amerex appliance plenum nozzle (P/N 11982) has one flow point and will protect a wok with '::dimensions between a minimum diameter of 14" (36 cm) and a maximum diameter of 24" (61 cm) inclusive. The wok must have a height dimension between a minimum of 4" (10 cm) and a maximum of 7" (18 cm) inclusive. The nozzle must be centered over- the center of the wok and located at a height between 40 " (102 cm) and 50" (127 cm) from the bottom of the inside of the wok and aimed at the center of the wok. Mn. Size Max. Size Alm Poen DUCT PROTECTION LIMITATIONS — TWO NOZZLES (2 x PIN 16416) Two Amerex duct nozzles (PIN 16416) will protect ducts with a perimeter of 51 inches to 82 inches (129.5 — 208.3 cm) or a maximum diameter of 26 inches (66 cm). To correctly position the nozzles a rectangular duct should be divided along its longest side into four equal distances. A drcular A nozzle should be placed along a centerlinefthe duct'srequal distances. width (or diameter) with both nozzle be the c at one quart 2-8 inches (5.08 - 20.3 cm) into the duct nodes on the centerline, paced opening and aimed at the center of the cross section of the duct. Each nozzle has one flow point. NOTE: In no case can the diagonal dimension of each module exceed 18.8 inches (46 cm). xs- MAX. DUCT PROTECTION LIMITATIONS 100 IN. PERIMETER TWO —11A FLOW POINT NOZZLES (P/N 11903) The Amerex solid fuel appliance/duct nozzle (P/N 11983) is listed to protect a restaurant cooking exhaust duct of unI mated length and up to 100 perimeter inches (254 cm) or 32 inch diameter (81.2 cm) using two nozzles. The nozzles total three flow points and to properly position the nozzles. a rectangular duct should be divided along its longest side into four equal distances. A circular duct should be divided along its center line into four equal distances. The nozzles are to be placed at one quarter and three quarters position of the duct width (or diameter) with both nozzles on the center Erne, placed 2 - 8 inches (5.08 — 20.3 cm) into the duct opening and aimed straight up in a vertically run duct. NOTE: In no case can the diagonal dimension of the duct exceed 372 inches (94.4 cm) without adding additional duct nozzles. NOTE: The use of one duct nozzle P/1inches 1983 is permitted for duct 50 perimeter less in the same manner as duct nozzle 16416. DUCT PROTECTION LIMITATIONS - TWO NOZZLES (2 it PIN 164101 Two Amerex duct nozzles (P/N 16416) will protect duds with a perimeter of 51 inches to 82 Inches {129.5 — 208.3 cm) or a maidmum diameter of 26 inches (66 cm). To correctly position the nozzles a rectangi.dar duct should be divided along its longest side into four equal distances. A cimular dud should be divided along a centerline into four equal distances. A nozzle should be placed at one quarter of the dud's width (or diameter) with both nozzles on the centerline. paced 2-8 inches (5.08 - 202 cm) into the duct opening and aimed at the center of the cross section of the dud. Each nazzie has one flow point. NOTE: In no case can the diagonal dimension of each module exceed 18.8 inches (46 an). PROTECTION LIMITATIONS 100 DUCT o�t[VEM13) The Amerex solid fuel appliance/duct nozzle (P/N 11983) is listed to protect a restaurant (=king exhaust dud of unlimited length and t to 100 perimeter inches (254 an) or 32 inch diameter (812 m) l three now points andto using two nozzles. should be properly position the nozzles. a g� A d be d duct along its longest side into fax equal should be divided along its center line into four equal distances. The of th es are io th t one � des on the center line, and three quarters position of the duct width (or diameter) placed 2 - 8 inches (5.08 — 20.3 cm) into the dud opening and aimed streight up in a verbosity run duct. NOTE: In no case can the diagonal dimension of the duct exceed 37.2 inches (94.4 cm) without adding addiuonai axe i"'u as. NOTE: The use of one duct nozzle P/N 11983 is permitted for duct 50 perimeter inches or less in the same manner as duct nozzle 16416. zx MAX. ACCEP1ID O Without Comments Er As Noted in Red ®' Per The Attached Letter These plans have been reviewed by The Tukwila Fire 'reventlon Bureau for conformance with current City standards. Acceptance: is subject r_., errors and omissions which do not authorize violations of adopted andards and ordinances. The responsibility for the adequacy of design rests totally with the designer, Additions, deletions or revisions to these drawings after Jthis date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: I -8-10 By: s 11 curaiii.A FIRE DEPARTIWIX Please cafl: 575•44O and give this job No. 10 -Pi ).(#S + id exact address for shut. gun or restoration aporoval FIRE ALA:'' M S UK ILA, I TE DDITION ASHING N SHEET \U V 3E SHEET TITLE FA -01 SYSTEM \FOIVATIO\ FA -02 TYPICAL WHI\G A \D NOUNTI \G DETAILS FA -03 SYSTEv CALCULATIO\ S A N D SI\GLE LI\E DIAG A VI FA -04 FRE ALA vl SYSTE V PLA\ SHEET INDEX C1i Without. Comments ,] As Noted in Red l� Ped The . attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau fc,!. cc,nforrnance with current City standards. Acceprar11 iF: subject to errors and omissions which do i -icy .;iithorize violations of adopted landards andesponsibiiity for the adequacy of :otally with the designer. Additions; deletio 1s= •cj visions to these drawings after chis date will void ths a cceptance -and will require a ;•esubmittai of revised drawings for subsequent approval r'inal acceptance 3ubiec t to field test and Inspection by, The Tukwila Fire Prevention Bureau. Date:! Z3././9 Bv: _,Al) 1 NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee ant termination of the testin% 1 "M+KWtLA FIRE DEPARTrVfsalL Please call: 575.4407, and give this job No. /0- F.) 4 )nd exact address for shut. uswn or restoration approval) WITEIIEDULE A\D CO\SUIT FILL CHAT WIRE DESIGNATION SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V' SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL •1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END WIRE DESIGNATION FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2, DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED GENERAL NOTES QUANTITY 1 1 3 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT BPS REMOTE BOOSTER POWER SUPPLY PAD -3 SIEMENS PAD-3-ENCL 66" A.F.F. TO TOP HTR -R INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP BOX VERIFY IN FIELD S FIRE ALARM SPEAKER STROBE SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2 EXTN CO JUNCTION BOX N/A N/A N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N -/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A SYMBOLS LEGEND 1:2000] MJN1 ANCHOR U 1- 0 120051 W 01 01 c 0 J 30 6 12113] 121201 0 O 0 0 0 IT 0 W 4 0 0 0 O w 121701 L175] 1 121801 __ rn A 12.1301 ❑ a 0 12.2061 13 ❑ CllAi01 m U 123101 1 R&�AIL 0 n ❑ ❑ 0 ❑ ❑ I FC1 1 JOHNNY 1 FC121i IFC1oI Tyvqj 11 of Cc>_51 THAI GO o 15HAI�K\i''S [2205. w vi 0 N 0 AUNIANCi10R a It F- 0) v _0 122001 0 K IFC31 SARKU RETAIL 0 \SUSHI TT)) 4%7- FAX (206) 628-4990 RELEASE/REVISIONS REV. BY: DMG DESCRIPTION SHOP DRAWINGS DATE 11/30/10 2 aaaaa 0 O v� J o 8z C'3w--I° z 0 E < D;T) U. O 2W m Q V_ Lu cc i- 0 0 11.1 >v 0) 0) RETAIL ---,yap-- - ROOF ROOF / \ROO ' T RAGE TERRACE BAYOU GRILL (2600, FOOD COURT #5) 2ND LEVEL PAID DEC -32010 TUKWILA FI13.E -6/b969' x7s' SITE PLAN Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved �CALE: NOT TO SCALE" DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 1 1 /30/1 0 BACKROUND PLAN PROVIDED BY: \0B NUMBER: 1 SHEET FA -01 120VAC-60H2 — DEDICATED EMERGENCY THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DUCK OVER 3' WIDE; SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. TUBE OUTLET SAMPLING TUBE INLET SAMPLING AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. *CONTACT RATINGS 4.0A 0 125VAC 4.0A 0 30VDC RIfIi1SOROIINIDINOD TO NEXT ADDRESSABLE (+ DEVICE STOP IF LAST DEVICE - rim XLS CDNTRW. PANEL (f DR PREVIOUS ADDRESSABLE DEVICE O 0 © O co.HTRI-R I g 1 O 0 NOTE EEADDITIONAL CATOS SEE ODUTDOCUMENATIN C -CABLE C -CABLE PAD -3 00n INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ - 1 2+ 2- 2 NC C NO + - + - + - + - + - 0 0 I h.. s2 3.6k EOL (-) (+) SPARE FROM PREVIOUS > (+) ADDRESSABLE > DEVICE (-) I1❑ NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. s C7 m 0 0 (=)(-) (+)(+) g (+) WIRE DESIGNATION; NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE TWISTED PAIR WITH SHELD #18 FPLIFPLR RED (JACKET) *CONTACT RATINGS 4.0A 0 125VAC 4.0A 0 30VDC FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. O 0 4 r 0 0 0 0 —LT!: J- I HTRI-R I g( J GROUND ❑II I 1 e' Z (:&: II 1 1 � , o, Q� I o o 0 ®` o C,°" 0=1 10= 7 6 = ILII � .1'1;7 �- " - '� toconox - Iro •- �ecocrox " ' 11 •- tecoc►ox 11 - tteocrox " 11 B - b rri l rrl- 1 lkiiiiiiiitis _,I_ : ® / .. 9 . g v ` Imo■ .: r .. • 00 a❑ SPARE SPARE (-) POWER SUPPLY & RELAY MODULE WIRING DETAIL FROM PRECEDING SPEAKER < OR FIRE ALARM CONTROL PANEL < (+) (+) (-) 0 (+)> TO NEXT DEVICE OR STOP IF LAST DEVICE (-) DRY CONTACTS TO VAV FAN SHUTDOWN PROVIDED BY MECH/ELEC. DUCT DETECTOR, TEST SWITCH & RELAY MODULE WIRING DETAIL STROBE SPEAKER L ❑ ❑ I1 - 1 _ e' Z (:&: El - O 1 i � , o, Q� I o o 0 ®` /.n.m ' 0=1 10= 7 6 = ILII � �- " - '� toconox - Iro •- �ecocrox " ' 11 •- tecoc►ox 11 11 a' 1:1:1:1:1 11:1:1- B - b rri l rrl- 1 lkiiiiiiiitis _,I_ : -Tj 1 o o l_ IL® X , 1I-: 0 a 40 ,,,,2 .. • 00 (-) ❑OD STROBE CIRCUIT STROBE =❑ I — O 1 — e' Z (:&: 1 . � 1 1 � , o, 0 o * "1:0t. ( .. e, /.n.m ' 0=1 10= 1111 � �- " - '� toconox - Iro •- tecoc►ox 11 a 1 rrrl n:ri- - b rri l rrl- lkiiiiiiiitis _,I_ _ 1 I (-) (-) SPEAKER CIRCUIT (+) (+) ❑a STROBE SPEAKER/STROBE ❑IJ a❑ (-) STROBE ❑Ol CIRCUIT (-) SPEAKER CIRCUIT SPEAKER STROBES & STROBES ONLY WIRING DETAIL TYPICAL WIRING AND MOUNTING DETAILS (+) S TO NEXT APPLIANCE S OR 24K (EOLR) (+) (+) S TO NEXT SPEAKER OR END OR LINE RESISTOR S 24K (EOLR) (-) SPEAKER CIRCUIT NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER TIN TEMPERA RE: +32' F 0' C TO 100' F (38 C) HUMIDITY: —9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR --> FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE r DATA IN ( ) Sl DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION HATH DUCT HOUSINGS AD -11P OR AD-11XPR STANDDB-11ARD SMOKE DETECTORBASE rr REAR VIEW (-) (+) SMOKE DETECTOR WIRING DETAIL HARD LID —\ �.: ::,;:; ; SPEAKER SUPPORT TILE BRIDGE ProDrietar > TO NEXT ADDRESSABLE DEVICE 4" SQUARE DEEP BOX WITH 1-1/2" EXTENSI❑N — CEILING MOUNTED SPEAKER/STROBE SPEAKER STROBE MOUNTING DETAIL JUNCTION BOX 1 JUNCTION BOX MOUNTED ON CEILING FLEX MOUNTED AGAINST CEILING SUPPORT 0 0 TO NEXT DEVICE CADDY BAR SMOKE/HEAT DETECTOR SUSPENDED ILLUMINATED CEILING SMOKE/HEAT DETECTOR MOUNTING DETAIL 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS 4 LL. Z OW 0U7- F rn """"1 8z F- `C 0w Q z 2Fo O 2 w� cc ca cc (i) O co �CALE: NOT J ttttett� W 0 0 z 0 0 z z OC tttttJ .) U L.B. TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 1 1 /30/1 0 BACKROUND PLAN PROVIDED BY: 10B NUMBER: 1 C SHEET FA -02 and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved J o quo 1 1 � , O O(A /.n.m ' 0=1 10= t I� i \ •- tecoc►ox 11 \ - b rri l rrl- lkiiiiiiiitis _,I_ _ 1 a❑ (-) STROBE ❑Ol CIRCUIT (-) SPEAKER CIRCUIT SPEAKER STROBES & STROBES ONLY WIRING DETAIL TYPICAL WIRING AND MOUNTING DETAILS (+) S TO NEXT APPLIANCE S OR 24K (EOLR) (+) (+) S TO NEXT SPEAKER OR END OR LINE RESISTOR S 24K (EOLR) (-) SPEAKER CIRCUIT NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER TIN TEMPERA RE: +32' F 0' C TO 100' F (38 C) HUMIDITY: —9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR --> FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE r DATA IN ( ) Sl DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION HATH DUCT HOUSINGS AD -11P OR AD-11XPR STANDDB-11ARD SMOKE DETECTORBASE rr REAR VIEW (-) (+) SMOKE DETECTOR WIRING DETAIL HARD LID —\ �.: ::,;:; ; SPEAKER SUPPORT TILE BRIDGE ProDrietar > TO NEXT ADDRESSABLE DEVICE 4" SQUARE DEEP BOX WITH 1-1/2" EXTENSI❑N — CEILING MOUNTED SPEAKER/STROBE SPEAKER STROBE MOUNTING DETAIL JUNCTION BOX 1 JUNCTION BOX MOUNTED ON CEILING FLEX MOUNTED AGAINST CEILING SUPPORT 0 0 TO NEXT DEVICE CADDY BAR SMOKE/HEAT DETECTOR SUSPENDED ILLUMINATED CEILING SMOKE/HEAT DETECTOR MOUNTING DETAIL 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS 4 LL. Z OW 0U7- F rn """"1 8z F- `C 0w Q z 2Fo O 2 w� cc ca cc (i) O co �CALE: NOT J ttttett� W 0 0 z 0 0 z z OC tttttJ .) U L.B. TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 1 1 /30/1 0 BACKROUND PLAN PROVIDED BY: 10B NUMBER: 1 C SHEET FA -02 and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved J ',.(-1- 01 •=,,,'' 'i,,`; < .-4',,, f 0. ,`,,; ,,I.,, 4 , , ''..,;,,,,;,“;,i1 .:, : • .:, .21,, r ,'. , '',„ ,'''''' FAG Db�SCurrent "..i..' "1'4,-'' ':' ii`; .1- > -, ' ., •- ,,,,, ./4 4 1. ! F I) ii.: '' _ '' q` ' ' } *; ' '' W.:.i.: , ',' ''°.,'''' 1.3 V., ' " , P.,, P ','',,t'' ''' ''i• ,; .•'::1; ,tak,j'',,,,,.,,. " '''?:1'4''''''1:41''' ' '''''''''' ''' ' ".1.4a,',4', , , •' ',.,' '="'" ''','''''''' i,..,i,',::„; ,:' ,...;:AI ''''' '''" ''''''''' ' ' ' ''''',,' ,:,''C,r+ ' Load: Standby: Alarm: . Device Type Qty Amps Total Device Type Qty Amps Total Amps Total • HFP-11 0.0022 0.0022 0.0023 0.000 0.03 AD2-P 0.030 0.0635 0.0635 0.064 0.000 . HTR -R 1 0.009600 0.0096 0.021 0.021 0.131 0.131 SETMC.C-©75CD ' . : , . :1 0.222 ' : 0.222 SET -MC -C @95CD 0.292 0.0731 Amps 0.021 Amps ',.(-1- 01 •=,,,'' 'i,,`; < .-4',,, f 0. ,`,,; ,,I.,, 4 , , ''..,;,,,,;,“;,i1 .:, : • .:, .21,, r ,'. , '',„ ,'''''' DESCRIPTION SHOP DRAWINGS ] "..i..' "1'4,-'' ':' ii`; .1- > -, ' ., •- ,,,,, ./4 4 1. ! F I) ii.: '' _ '' q` ' ' } *; ' '' W.:.i.: , ',' ''°.,'''' 1.3 V., ' " , P.,, P ','',,t'' ''' ''i• ,; .•'::1; ,tak,j'',,,,,.,,. " '''?:1'4''''''1:41''' ' '''''''''' ''' ' ".1.4a,',4', , , •' ',.,' '="'" ''','''''''' i,..,i,',::„; ,:' ,...;:AI ''''' '''" ''''''''' ' ' ' ''''',,' ,:,''C,r+ ' 2 „ . Device Type Qty Amps Total Amps Total • Main System Board 1 0.03 0.03 0.030 0.030 SET -MC -C @1 CD . ' ' 1 ' , . 0.0875 's 0.088 1SET-MC-C @30CD 1 0.131 0.131 SETMC.C-©75CD ' . : , . :1 0.222 ' : 0.222 SET -MC -C @95CD 0.292 SET -MC -C 1 OCD : 0.259 ZR -MC ©15CD 0.064 ZR -MC ©30CD . „ -- 0.098 ZR -MC @75CD 0.2 • 0.03 Amps 0.4705 Amps Standby Current Load: ' „ : 0.03 Amps .. For 24 Hours = '' 0.720 Amp -hours Alarm Current Load: - . 0.4705 Amps... For5 Minutes.= ' . .". 0.040 Amp -hours • " ' , . 25% Derating = . ' 0.949 Amp -hours Total System Current Load: 0.949 Amp -hours . , . Satte, ,cki ai TJA -,..; - ,,:.,.Used'-'.-.„4,:iv,,'TJAA:,12VC,-4, 7- t,ii, ''" v2A '-$.' .:7-,,,e-?-:,•). " ';'7.'..'"'... ::',.-r.:;,;V:':;,-,;',',,i1 Notification Appliance Circuit Detail PROJECT: BAYOU GRILL Panel PAD -3 POWER SUPPLY 1Wire Resistance 2.58 Date: December 1, 2010 CURRENT TOTAI:=12485.50 1SET-MC-C @15CD 87.51 87.5 SET-MC-C@30CP 131 131 1 1SET-MC-C @75CD 222 222 'SET4C-C 695CD 292 - 0 0 1ZR-MC @110CD 1 259 0 0 M411 C I 5C D 0 aC @ 50. DD 0 @ y .. DEVICES=13 64 0 98 01 175 0 TOTALrnA=1 440.51 14 Total Wire Resistance ( R ) Total Device Load, Amps (I) 1Voltage Drop ( E ) EOL Voltage J • 183 23.581 440.51 ( WL * 2 )* (R/ft) 0.941 (Total COt Load) 0.44 1(E= I * R) 0.421 24 - E) 23.58 Notification Appliance Circuit Detail i I PROJECT: BAYOU GRILL Panel: XLS-V !Wire Resistance 2.58 Date: December 1, 2010 CURRENT toTAH#REF! 18 70.7V 1/4 0 70.7V1/2 70.7V 1 DEV10ES=165 3.54 63.72 0 0 0 0 TOTAL mA= 148.321 14 Total Wire Resistance ( R ) Total Device Load, Amps (1) Voltage Drop ( E) EOL Voltage 1,327 19.3844055, 148.32 I( WL* 2) * (R/ft) 6.85 (TOtal-cpt- Load). •0,15 (E= I *.F1) 1 1.02 SYSTEM CALCULATIONS EX EX8 V V (HALLWAY) 13 EX BPS 2C 120VAC, DEDICATED (BY OTHERS) BPS (ELECTRICAL ROOM) HTR -R S1-1 15cd V-1 1/4-W S1-2 75cd V-2 1/4-W S1-3 30cd V-3 1/4-W EOL S1 FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. NEW SIEMENS PAD -3 BOOSTER POWER SUPPLY SHALL BE LOCATED IN THE ELECTRICAL ROOM. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 11OVAC BRANCH CIRCUIT. C/3 co 0' 1743 1ST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 m 0 DESCRIPTION SHOP DRAWINGS ] DATE 11/30/10 2 <KKK< CC 0 uJ z -J w Z 0 28 rz coS Z - o ooz EE mut w --lz z g_ < 2(T) < 0 (I) <iuji OZ w cc nn F- 0 0 c‘, w (1) ‘CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 1 1 /30/1 0 BACKROUND PLAN PROVIDED BY: SINGLE LINE DIAGRAM \0B NUMBER: Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved \ SHEET FA -03 —UJASI-TABLE �nr............ CEILING TILE TI -IIS AREA N \N, S1-1 V1`1N (CEILING: +12) / N 0 i/// r. / // ////// '//// /c) \`� C (GW) CEILING) (+12'-0") / 7 2x4 SUSPENDED / ACOUSTIC CEILING. - .....J - J / J 7/7 7 /77 / / zzJ �5 DEDICATE (I) LIGHT FIXTURE PER TENANT SPACE TO BE ILLUMINATED AT ALL TIMES, TY"P. / / • / //7 S S1-3 -� 30cd ��)) V1-3 —, 'N" /5 ' \ CO REFLECTED CEILING PLAN EXISTING ADJACENT TENANT_ r ---"SUBWAY" (GWB SOFFIT) (+12'-O") TO ELECTRICAL ROOM (S -WIRES TO NEW POWER SUPPLY & D -WIRES TO EXISTING SMOKE DETECTOR) D,S dR'RJ 0_14"1 0 i ELECT PANEL DRY FOOD SHELVING S1-1 1 5cd V1-1 --- EMPLOYEE LOCKERS / 7 / 'i' Cly) FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. NEW SIEMENS PAD -3 BOOSTER POWER SUPPLY SHALL BE LOCATED IN THE ELECTRICAL ROOM. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 11OVAC BRANCH CIRCUIT. BACK KITCHEN D,S KITCHEN V,V1 0 0 EX WALK-IN COOLER i WALK-IN j FREEZER / /r / //ZZ2%27 I222ZZ/%1Z1.11r1'-Z 277ZZZ. COFFEE BREWER SINK EOL S1 22222 S,V,V \ ,_,, , S S1-2\ moo 75cd V1-2 \ V' \\ S1-3 30cd V1-3 COLN F c�8/ oa 7-y_ 7:5 ryQC! SERVICE COUNTER AREA COLUMN JUICE DISPLAY FIRE ALARM SYSTEM PLAN R4 z yy 144 z 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 DESCRIPTION SHOP DRAWINGS DATE 11/30/10 2a<aa< i - /5 ' \ CO REFLECTED CEILING PLAN EXISTING ADJACENT TENANT_ r ---"SUBWAY" (GWB SOFFIT) (+12'-O") TO ELECTRICAL ROOM (S -WIRES TO NEW POWER SUPPLY & D -WIRES TO EXISTING SMOKE DETECTOR) D,S dR'RJ 0_14"1 0 i ELECT PANEL DRY FOOD SHELVING S1-1 1 5cd V1-1 --- EMPLOYEE LOCKERS / 7 / 'i' Cly) FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. NEW SIEMENS PAD -3 BOOSTER POWER SUPPLY SHALL BE LOCATED IN THE ELECTRICAL ROOM. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 11OVAC BRANCH CIRCUIT. BACK KITCHEN D,S KITCHEN V,V1 0 0 EX WALK-IN COOLER i WALK-IN j FREEZER / /r / //ZZ2%27 I222ZZ/%1Z1.11r1'-Z 277ZZZ. COFFEE BREWER SINK EOL S1 22222 S,V,V \ ,_,, , S S1-2\ moo 75cd V1-2 \ V' \\ S1-3 30cd V1-3 COLN F c�8/ oa 7-y_ 7:5 ryQC! SERVICE COUNTER AREA COLUMN JUICE DISPLAY FIRE ALARM SYSTEM PLAN R4 z yy 144 z 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 DESCRIPTION SHOP DRAWINGS DATE 11/30/10 2a<aa< 0 cc c .0c-6 - D o� ooz (f) CC Q LL" o >1. wtz D= U) D(T) O °i CC I— < 11.6 � w =� cc 1- u_ 01- 0 O N W 4-CALE: 3/8"=1 '0" DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE:1 1 /30/ 10 BACKROUND PLAN PROVIDED BY: .1OB NUMBER: SHEET FA -04 Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved % EMERGENCY EXIT SIGN W/ BACK-UP BATTERY, TYP CEILING TILE THIS AREA RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD ROD PIPE SWIVEL RING DICATE (I) LIGHT Fl TURE PER TE T SPACE TO BE I �UMINATED AT ALL T f; IES, TYP. STEEL JOIST/TRUSS HANGER DETAIL NTS REFLEGTED CEILING FLAN Design per NFPA 13, Ordinary Hazard 130 sq ft All materials to be new, U.L. listed, and F.M. approved All fire sprinkler heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart 7— Add Reliable Model F1 Standard Response 155° Pendants 1/2 x 1/2 3- Add Reliable Model G4A Standard Response 155 Consealed155 1/2x1/2 2- Add Reliable Model F3 Dry Pendants Standard Response 200 1/2 xl/2 12 — Total (d) = Ductile iron Model MT -3 & MT -9 Mechanical tea serves the same function as MTI z MT -8 but uses a steel electro plated u -bolt to save space and for easier insrnliaUan In tight places. It is ideal for direct connections with sprinkler heads and drop nipples. HOUSING: Ductile iron ASTMA536 grade 85-45-12. COATING: Zine electroplated U - BOLT: Carbon steel SAE grade 2, zinc plated. NUT: Carbon steel ASTM A194, zinc plated. GASKET: EPDM (-30°F to + 230°F) THREADS: MT -3 NPT per ANSI/ASME 81.20.1 MT -9 British standard parall0l (BOP) per BS21 Illi Tri,&`MT 9vMEC1-1AIW LTi=1 ma 1 4L M•1=. M •L! DIMIN510Nf.lnorm I -�- - E — APPROX. WLIGNT Q WItheut Comments Er As Noted in Red 12r Per The Attached Letter -ese plans have been reviewed by The Tukwila Fire .evention Fureal..+ r:,, : Infornraocc. with current CIty �ndards. ?cc r:.t , r:: errors and nissions whirl= : ; ., i, a= rl.horizp violations of adopted 3ndards ana c : c:.. :enc s rh i esponslhfllty for the ,equacy ,r cies1T rests totally with the designer. dltiofis. deleliof:s r:= R visions to these drawingsS,after ,s date mil void the acceptance and will require'a ,submittar r!I !-; � sec: drawings for subsequent approval. nal acceptance is subject to field test and Inspection by ne Tukwila Fire Prevention Bureau. Date: / I - I CO /6 By: ,4, ' i y / ( titiKWILA FIRE DEPARTMai1 Please calf: 575.4407 and give this job No. / (7 -S- e): S� and exact address for shut. o4min or rest;;ration approval. NOTICE Weld stamps must be inspected before pipe is hung. Do not paint piping prior to hydrostatic test approval. CROV\/N FIRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 BAYOU GRILL 2600 SOUTHGENTER MALL • FOOD COURT #5 TUKWILA, NA 98188-2816 DATE: DRAWN: I SCALE: PAID NOV 10 2010 TUKWILA FIRE 1.c3