Loading...
HomeMy WebLinkAboutPP - 2600 SOUTHCENTER MALL FC-7 - DAPHNES GREEK CAFÉ - PERMITS AND PLANS2600 SOUTHCENTER MALL FC -7 FOOD COURT ASSOCIATED PERMITS 08-F-318 08-S-285 10-H-144 08-H-324 FILE COPY FIRE DEPARTMENT HOOD SUPPRESSION PLAN REVIEW COMMENTS Project Name: Daphne's Greek Cafe 2600 Southcenter Mall FC -7 Permit No.: 08-H-324 Date: June 12, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Nozzle heights above appliances to be per manufacturers installation guidelines. • Install splash guards between fryers and ranges/charbroilers. • Upon activation of the suppression system, the make-up air supply will shut off and the exhaust will keep running. • Type 1 hood systems shall be designed and installed to automatically activate the exhaust fan whenever cooking operations occur. The activation of the exhaust fan shall occur through an interlock with the cooking appliances, by means of heat sensors or by means of other approved methods. • Activation of the suppression system shall shunt all electrical power under the hood as well as the gas supply. • Install a "K" rated portable fire extinguisher within 30 ft. of the cooking equipment. • The hood suppression system shall be monitored by a U.L. Central Monitoring Station. FIRE DEPARTMENT HOOD SUPPRESSION PLAN REVIEW COMMENTS Project Name: Indibite 2600 Southcenter Mall, FC -0 7 Permit No.: 10-H-144 Date: July 19, 2010 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Nozzle heights above appliances to be per manufacturers installation guidelines. • Fryers shall be installed with at least a 16 inch space between the fryer and surface flames from adjacent cooking equipment or a minimum 8 inch high steel or tempered glass baffle plate shall be installed between the appliances. • Upon activation of the suppression system, the make-up air supply will shut off and the exhaust will keep running. • Type 1 hood systems shall be designed and installed to automatically activate the exhaust fan whenever cooking operations occur. The activation of the exhaust fan shall occur through an interlock with the cooking appliances, by means of heat sensors or by means of other approved methods. • Activation of the suppression system shall shunt all electrical power under the hood as well as the gas supply. • Install a "K" rated portable fire extinguisher within 30 ft. of the cooking equipment. • The hood suppression system shall be monitored by a U.L. Central Monitoring Station. • The suppression system manual pull station shall be located no closer that 10 ft. and no farther than 20 ft. from the cooking equipment and be placed at a height of 42 to 48 inches above the floor. • The inside lower edge of the hood shall overhang or extend a horizontal distance of not less than 6 inches beyond the edge of the top horizontal surface of the appliance on all open sides. The vertical distance between the front lower lip of the hood and such surface shall not exceed 4 feet. FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Daphne's 2600 Southcenter Mall FC -7 Permit No.: 08-S-285 Date: June 5, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 % inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • These conditions apply to any sprinkler piping exposed as necessary to accomplish the permitted scope of work. All references are NFPA 13, 2007 Edition. ilHyd ra Iic Summary - Job Number: KS0427 Report Description: Ordinary Group II Job Job Number Design Engineer KS0427 Adam Kanter Job Name State Certification/License Number Daphe's WESTESF136QF Address 1 Al-IJ 2600 Southcenter Mall City of Tukwila Address 2 Job Site Southcenter Mall City State Zip Code Drawing Name Tukwila Wa 98188 FP-1.cad System Remote Area(s) Most Demanding Sprinkler Data Occupancy 5.6 K-Factor 20.00 at 12.755 Ordinary Group II Hose Allowance At Source Density Area of Application 250.00 0.20gpm/ft2 678.29ft2 (Actual 678.29ft2) Additional Hose Supplies Number Of Sprinklers Calculated Coverage Per Sprinkler Node Flow(opm) 13 100.00ft2 Total Hose Streams 250.00 System Flow Demand Total Water Required (Including Hose Allowance) � 41 303.17 : 553.17 . !.11407, Maximum Pressure Unbalance In Loops\/ 0.000 11 �3':, likki._ .ii Maximum Velocity Above Ground 23.77 between nodes 87 and 105 , Vhf 3 lo p Maximum Velocity Under Ground 4*. 1.15 between nodes 1 and 279 Volume capacity of Wet Pipes I Volume capacity of Dry Pipes I 2023.06gal 1.22ft3 Supplies Hose Flow Static Residual pe Flow Available Total Demand Required Safety Margin Node (gpm) (psi) (psi) (gpm) (psi) (gpm) (psi) (psi) 1 250.00 140.000 20.000 10900.00 139.517 553.17 65.256 74.261 Contractor Contractor Number Contact Name Contact Title KS0427 Adam Kantner Project Manager Contractor Name Phone Extension Western States Fire Protection 425.881.0100 Address 1 FAX 7102 180th Ave Ne, Suite A-105 485.736.9032 Address 2 E-mail City State Zip Code Web-Site Redmond WA 98052 ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 06/02/2008 11:55:45AM Page 1 11.1.- Summary Of Outflowing Devices mber: 427 1Report Description:b Oudinary Gro pp H Actual Flow Minimum Flow K -Factor Pressure Device (gpm) (gpm) (K) (psi) Sprinkler 116 26.66 20.00 5.6 22.658 Sprinkler 117 27.30 20.00 5.6 23.769 Sprinkler 115 25.35 20.00 5.6 20.486 Sprinkler 108 23.52 20.00 5.6 17.644 Sprinkler 109 23.88 20.00 5.6 18.178 Sprinkler 107 22.55 20.00 5.6 16.218 Sprinkler 114 24.34 20.00 5.6 18.898 Sprinkler 106 20.63 20.00 5.6 13.573 Sprinkler 110 24.33 20.00 5.6 18.883 Sprinkler 103 20.18 20.00 5.6 12.992 14> Sprinkler 101 20.00 20.00 5.6 12.755 Sprinkler 111 24.34 20.00 5.6 18.896 Sprinkler 102 20.08 20.00 5.6 12.856 c> Most Demanding Sprinkler Data ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 06/02/2008 11:55:49AM Page 2 Node Analysis Job Number: KS0427 Report Description: Ordinary Group II Node Elevation(Foot) Fittings Pressure(psi) Discharge(gpm) 86 13-6 PO(5-0) 32.015 87 13-6 PO(8-0) 31.046 90 13-6 PO(5-0) 30.800 91 13-6 PO(8-0) 30.734 44.492 97 1-6 104 14-1 P0(5-0) 27.226 105 14-1 P0(5-0) 23.508 112 14-1 P0(5-0) 21.891 113 14-1 P0(5-0) 20.498 120 14-1 P0(5-0) 25.098 17.693 127 14-1 LtE(2-5%) 130 14-1 LtE(2-5%) 24.373 135 14-1 P0(5-0) 16.547 139 14-1 P0(5-0) 23.755 15.811 15.438 142 14-1 P0(5-0) 169 14-1 P0(5-0) 240 14-1 E(2-0) -14-1 PO(5-0), PO(26-4) 23.452 58.096 61.802 15.343 271 279 -12-1% BF (4.500) _ 303 14-1 E(2-0) -14-1 LtE(16-0) 319 58.114 116 11-6% Spr(-22.658) 22.658 26.66 117 11-6'/2 Spr(-23.769) 23.769 27.30 115 11-6'/2 Spr(-20.486) 20.486 25.35 108 8-0V2 Spr(-17.644) 17.644 18.178 16.218 _ 23.52 109 7-0 Spr(-18.178) 23.88 107 8-0 Spr(-16.218) 22.55 114 11-6% Spry -18.898) 18.898 13.573 24.34: 20.63 106 9-0 Spr(-13.573) 9-0 Spr(-18.883) 110 18.883 24.33 103 9-0 Spr(-12.992) 12.992 20.18 ' 101 9-0 Spr(-12.755) 12.755 18.896 , 20.00 111 9-0 ; SK 18.896) 24.34 102 9-0 ' Spr(-12.856) 12.856 65.256 20.008 1 -20-0 1 S 303.17 D(/� ©M.E.P.CAD, Inc. 411 AutoSPRINK® VR5 v5.2.6 06/02/2008 11:55:53AM Page 3 899 Hydraulic Analysis 1 Job Number: KS0427 Report Description: Ordinary Group 11 Pipe Type Diameter Elevation Flow Discharge Velocity K -Factor HWC Pt Friction Loss Length Pressure Pn Fittings Eq. Length Summary Total Length Downstream Upstream v Route 1 DR 1.049 Q=20.00 7.42 C=120 0.130131 28-61/2 Pf 4.885 101 9-0 q=20.00 K=5.6 12.755 Spr(-12.755) 9-0 Pe -2.202 169 14-1 15.438 2E(2-0), PO(5-0) 37-61/2 Pv BL 1.682 Q=40.08 5.79 C=120 0.047236 7-101/2 Pf 0.373 169 14-1 15.438 Pe 142 14-1 15.811 7-10% Pv BL 1.682 Q=60.26 8.70 C=120 0.100457 7-4 Pf 0.735 142 14-1 15.811 Pe 135 14-1 16.547 7-4 Pv BL 1.682 Q=80.89 11.68 C=120 0.173195 4-1% Pf 1.146 135 14-1 16.547 2-5% Pe 127 14-1 17.693 LtE(2-5%) 6-7'/z Pv BL 1.610 Q=80.89 12.75 C=120 0.214321 7-1 Pf 2.805 127 14-1 17.693 6-0 Pe -0.000 113 14-1 20.498 3LtE(2-0) 13-1 Pv BL 1.610 Q=103.45 16.30 C=120 0.337786 4-1% Pf 1.394 113 14-1 20.498 Pe 112 14-1 21.891 4-11/2 Pv BL 1.610 Q=126.97 20.01 C=120 0.493465 3-31/2 Pf 1.616 112 14-1 21.891 Pe -0.000 105 14-1 23.508 3-3'% Pv BL 1.610 Q=150.85 23.77 C=120 0.678729 0-8% Pf 7.278 105 14-1 23.508 10-0, Pe 0.260 87 13-6 31.046 LtE(2-0), PO(8-0) 10-8V2 Pv CM 2.635 Q=275.87 16.23 C=120 0.188259 5-2 Pf 0.969 87 13-6 31.046 Pe 86 13-6 32.015 5-2. Pv CM 2.635 Q=303.17 17.84 C=120 0.224169 14-1'/z Pf 7.271 86 13-6 32.015 18-31/2 Pe 5.206 97 1-6 44.492 fE(4-3%), 2fEE(2-2%), BV(9-7%) 32-5 Pv CM 4.260 Q=303.17 6.82 C=120 0.021605 179-4 Pf 6.852 97 1-6 44.492 137-9% Pe 6.752 271 -14-1 58.096 4fE(6-9%), 3P0(26-4), 317-2 Pv CV(28-11'/2), GV(2-7%) FM 8.329 Q=303.1.7 1.79 C=120 0.000825 5-7 Pf 0.018 271 -14-1 58.096 16-0 Pe -0.000 319 -14-1 58.114 LtE(16-0) 21-7. Pv FM 10.420 Q=303.17 1.14 C=120 0.000277 26-51/2 Pf 4.530 319 -14-1 58.114 83-0 Pe -0.842 279 -12-1% 61.802 4LtE(16-0), BV(19-0), BFP(-4.500) 109-5'/2 Pv UG 10.400 Q=303.17 1.15 C=140 0.000210 109-2 Pf 0.046 279 L12-1% 61.802 111-7i Pe 3.407 1 -20-0 65.256 E(35-1), 3LtE(25-6), S 220-9% Pv ai Route 2 DR 1.049 Q=20.08 7.45 C=120 0.131082 29-9 Pf 4.689 102 9-0 q=20.08 K=5.6 12.856 Spr(-12.856) 6-0, Pe -2.202 303 14-1 15.343 3E(2-0) 35-9' Pv BL 1.682 Q=20.08 2.90 C=120 0.013151 7-3' Pf 0.095 303 14-1 15.343 Pe 169 14-1 15.438 7-3 Pv • Route 3 DR 1.049 Q=20.18 7.49 C=120 0.132361 28-11' Pf 5.021 103 9-0 q=20.18 K=5.6 12.992 Spr(-12.992) 9-0 Pe -2.202 142 14-1 15.811 2E(2-0), PO(5-0) 37-11 Pv v Route 4 DR 1.049 Q=20.63 7.66 C=120 0.137835 28-61/2 Pf 5.175 106 9-0 q=20.63 K=5.6 13.573 Spr(-13.573) 9-0 Pe -2.202 135 14-1 16.547 2E(2-0), PO(5-0) 37-61/2 Pv v Route 5 DR 1.049 Q=22.55 8.37 C=120 0.162511 31-6'/z Pf 6.914 107 8-0 q=22.55 K=5.6 16.218 Spr(-16.218) 11-0. Pe -2.635 113 14-1 20.498 3E(2-0), PO(5-0) 42-6'/z Pv Route 6 DR 1.049 Q=23.52 8.73 C=120 0.175678 30-2 Pf 6.883 108 8-0% q=23.52 K=5.6 17.644 Spr(-17.644) 9-0 Pe -2.635 112 14-1 21.891 2E(2-0), PO(5-0) 39-2 Pv v Route 7 DR 1.049 Q=23.88 8.86 C=120 0.180593 35-6 Pf 8.398 109 7-0 q=23.88 K=5.6 18.178 Spr(-18.178) 11-0 Pe -3.069 105 14-1 23.508 3E(2-0), PO(5-0) 46-6 Pv Route 8 ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 06/02/2008 11:55:57AM Page 4 111 Hydraulic Analysis Pipe Type Diameter Flow Job Number: KS0427 Report. Description: Ordinary Group II Velocity HWC Friction Loss Downstream Upstream DR Elevation Discharge K -Factor Pt Fittings Length Pressure Eq. Length Summary Total Length 1.049 Q=24.33 9.03 C=120 0.187064 110 9-0 q=24.33 K=5.6 139 14-1 18.883 23.755 Spr(-18.883) 2E(2-0), PO(5-0) 28-10 Pf 7.073 9-0 Pe -2.202 37-10 Pv BL 1.682 Q=48.68 7.03 C=120 0.067677 139 14-1 130 14-1 23.755 24.373 LtE(2-51/2) 6-8 Pf 0.618 2-5% Pe 9-1% Pv BL 1.610 Q=48.68 7.67 130 14-1 120 14-1 C=120 0.083747 24.373 25.098 3LtE(2-0) 2-8 Pf 0.725 6-0 Pe 8-8 Pv BL 1.610 Q=73.02 11.51 C=120 0.177336 120 14-1 104 14-1 25.098 27.226 12-0 Pf 2.128 Pe -0.000 12-0, Pv BL 104 91 1.610 14-1 13-6 Q=98.37 15.50 C=120 0.307746 27.226 30.734 LtE(2-0), PO(8-0) 0-61/2 Pf 3.249 10-0 Pe 0.260 10-6% Pv CM 2.635 Q=98.37 5.79 91 13-6 90 13-6 C=120 30.734 30.800 0.027940 2-4% Pf 0.066 Pe 2-4% Pv CM 2.635 Q=125.02 7.36 C=120 0.043540 90 13-6 87 13-6 30.800 31.046 5-7'/z Pf 0.245 Pe 5-7% Pv .i Route 9 DR 1.049 Q=24.34 9.04 111 9-0 q=24.34 K=5.6 240 14-1 C=120 18.896 23.452 0.187185 Spr(-18.896) 3E(2-0) 30-1, Pf 6.758 6-0 Pe -2.202 36-1 Pv BL 240 139 1.682 14-1 14-1 Q=24.34 3.51 C=120 0.018779 23.452 23.755 16-11/2 Pf 0.303 Pe 16-1'/z Pv GO Route 10 DR 1.049 Q=24.34 9.04 114 11-6% q=24.34 K=5.6 120 14-1 C=120 18.898 25.098 0.187198 Spr(-18.898) 3E(2-0), PO(5-0) 28-1Pf 7.318 11-0 Pe -1.118 39-1 Pv • Route 11 DR 115 104 1.049 11-6% 14-1 Q=25.35 9.41 C=120 0.201710 q=25.35 K=5.6 20.486 27.226 Spr(-20.486) 3E(2-0), PO(5-0) 27-11% Pf 7.858 11-0 Pe -1.118 38-11 % Pv ✓ Route 12 DR 1.049 Q=26.66 9.90 116 11-6% q=26.66 K=5.6 90 13-6 C=120 22.658 30.800 0.221415 Spr(-22.658) 3E(2-0), PO(5-0) 29-8, Pf 9.000 11-0 Pe -0.858 40-8 Pv .O Route 13 DR 1.049 Q=27.30 10.14 C=120 0.231437 117 11-6% q=27.30 K=5.6 86 13-6 23.769 32.015 Spr(-23.769) 3E(2-0), PO(5-0) 28-4 Pf 9.104 11-0 Pe -0.858 39-4 Pv Equivalent Pipe Lengths of Valves and Fittings (C=120 only) Actual Inside Diameter Schedule 40 Steel Pipe Inside Diameter 4.87 = Factor C Value Multiplier 1 Value Of C 100 Multiplying Factor 0.713 130 140 150 1.16 1.33 1.51 © M.E.P.CAD, Inc. 41AutoSPRINK® VR5 v5.2.6 06/02/2008 11:55:57AM Page 5 Hydraulic Analysis Pipe Type Downstream Upstream Diameter Elevation Flow Discharge Job Number: KS0427 Report Description: Ordinary Group II Velocity HWC Friction Loss K -Factor Pt Pn Fittings Length Pressure Eq. Length Summary Total Length Pipe Type Legend Units Legend Fittings Legend AO Arm -Over Diameter BL Branch Line Elevation CM Cross Main Flow DN Drain Discharge DR Drop Velocity DY Dynamic Pressure FM Feed Main Length FR Feed Riser Friction Loss MS Miscellaneous HWC OR Outrigger Pt RN Riser Nipple Pn SP Sprig Pt ST Stand Pipe Pe UG Underground Pv Inch Foot gpm gpm fps psi Foot psi/Foot Hazen -Williams Constant Total pressure at a point in a pipe Normal pressure at a point in a pipe Pressure loss due to friction between points Pressure due to elevation difference between indicated points Velocity pressure at a point in a pipe ALV Alarm Valve AngV Angle Valve b Bushing BaIV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Turn 90° cplg Coupling Cr Cross Run CV Check Valve DeIV Deluge Valve DPV Dry Pipe Valve E 90° Elbow EE 45° Elbow Eel 11% Elbow Ee2 221/0 Elbow f Flow Device FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow flg Flange FN Floating Node fT FireLock(TM) Tee g Gauge GIoV Globe Valve GV Gate Valve Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PrV Pressure Relief Valve PRV Pressure Reducing Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap (A� ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 06/02/2008 11: 55: 57AM Page 6 • Hydraulic Graph Job Number: KS0427 Report Description: Ordinary Group II Supply at Node 1 150 Static Pressure 140.000 135 120 105 • 90 .N o. s 75 N co N o_ „553.17 2303.17 with hose @ 65.256 streams 60 45 =System J demand curve 30 10900.00 @ 20.000_ 15 I1111IIII III1111II 1 1 1 1111 11 11 I 1 f 1 I (I 111111111 111111111 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 I 1 1 0 110022 3300 4400 5500 6600 7700 8800 9900 11000 Water flow, gpm Hydraulic Graph Supply at Node 1 Static Pressure 140.000 Residual Pressure 10900.00 © 20.000 Available PressureTIme of Test 139.517 © 553.17 System Demand 303.17 @ 65.256 System Demand (Including Hose Allowance) 553.17 © 65.256 ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 06/02/2008 11:56:06AM Page 7 lid Flow Diagram (Top View) 1 Job Number: KS0427 Report Description: Ordinary Group II %©M.E.P.CA D, Inc. JAutoSPRINK® VR5 v5.2.6 06/02/2008 11:56:10AM Page 8 i •,-1 %.1 [.vvv 11:11 /Art .IWIXOJd 481H Q JeH0003 soJAD I WX ifa Q JaHoo3X saKDBi o`i4 Q otax 004,pjvo*wit S -aa .k4 A}1611xoJd 48IH i p, off diiea ,* S� a1Cj� ]NIdId Q13Id DNIdId A21010dd JC 4 N L r.) I w I 0 L 0 1'1 COgo- Received Time May.30, 8:07AM Page: 4 0 • r ° L. L_ to a i13 3 x ru 2 co lawoN qor 10L I Z c. r S. c r- 14)0 / QV/ L.VVO 11:11 Ari Page: 3 Nola - Fire Systems - Parts List Report 5/28/08 12:00 PM' Fire System Parts List Job # 776631 - Daphne's - Seattle, WA Location: Seattle, WA Fire System # 1 Ansul R102 Hoods Covered: Hood # 1 Gas Valve(s): ANSUL-3.0/3.0- MANIFOLD Tag: Supplied by Ship Qty Item CAS # Vendor # Description MA CAS Inst Loose 2 1 AT - 3.0 AT - 3.0 TANK(#1 B) - 3.0 Gallon SS Tank (for use with 2 0 Automan Release, Actuator, or SS Enclosure (UL)) 1 2 AP - AR AP - AR AUTOMAN RELEASE - Ansul Automan 1 0 Mechanical Release (UL) Tank sold separately 1 3 AP - AE AP - AE ENCLOSURE - Stainless Steel Enclosure 1 0 Assembly (UL) 2 5 LIQ -3.0 79372 AGENT - Ansulex Low PH Wet Chemical Agent, 3 2 0 Gallon (UL) 1 9 DT -CART 73022 Double Tank Nitrogen Cartridge 1 0 1 10 TLINK TLINK LINK - Test Link Package 1 0 1 11 MICRO -SD MICRO -SD MICROSWITCH - Single Dual Electric Switch 1 0 1 12 HOSEGROMMET 418511 HOSE - Hose/Grommet Package 1 0 1 13 419337 419337 NOZZLE -2W Nozzle, Duct 0 1 4 16 419335 419335 NOZZLE - 1N Nozzle, Plenum/Appliance 0 4 2 20 419340 419340 NOZZLE - 245 Nozzle, Appliance 0 2 2 21 419339 419339 NOZZLE - 230 Nozzle, Appliance 0 2 2 25 418569 418569 NOZZLE ADAPTOR - Swivel Nozzle Adaptor 0 2 9 26 QSA-3/8 QSA-3/8 QUIK SEAL - 318" (UL) 0 9 1 27 QPSA-1/2 QPSA-1/2 PULLEY SEAL- 1/2" Hood Seal (UL) 0 1 5 28 S -DET S -DET DETECTOR -Series (Scissor Linkage) 0 5 2 29 ANS-360FL ANS-360FL FUSIBLE LINK - 360deg F, R-102 and PIRANHA 0 2 3 30 ANS-500FL ANS-500FL FUSIBLE LINK - 500deg F, R-102 and PIRANHA 0 3 1 34 RPS -A RPS -A REMOTE PULL STATION -Aluminum (without 1 0 wire rope) 10 35 PE -LT PE -LT PULLEY ELBOW - Low Temp. Pulley Elbow, Set 10 0 Screw Type 1 36 PE -HT PE -HT PULLEY ELBOW - High Temp Pulley Elbow, 0 1 Compression Type 2 41 SN -CHAR SN -CHAR SINGLE NOZZLE EXTENDED DROP ASSY 0 2 Oa http://appl.captiveaire.com/Order/FireSystems/PartsListReport.aspx?JobFireSystemid=169916 Page 1 of 1 Received Time May, 30, 8:07AM SECTION IV — SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-28 REV.5 4-1-06 Nozzle Application Chart The following chart has been developed to assist in calculating the quantity and type of nozzle required to protect each duct, plenum, or appliance. . NOTICE This chart is for general reference only. See complete details for each type of hazard. Hazard ► Duct or Transition (Single Nozzle) Duct or Transition (Single Nozzle) Duct or Transition (Dual Nozzle) Electrostatic Precipitator (At Base of Duct) Plenum (Horizontal Protection) ► Plenum (Horizontal Protection) Plenum (Vertical Protection) ► Fryer (Split or Non -Split Vat) Fryer (Split or Non -Split Vat) Fryer (Split or Non -Split Vat)* Fryer (Non -Split Vat Only) Maximum Hazard Dimensions Length — Unlimited Perimeter — 50 in. (127 cm) Diameter —16 in. (40.6 cm) Length — Unlimited Perimeter —100 in. (254 cm) Diameter — 31 7/8 in. (81 cm) Length — Unlimited Perimeter -150 in. (381 cm) Diameter — 48 in. (122 cm) Individual Cell Length —10 ft. (3.1 m) Length — 6 ft. (1.8 m) Width — 4 ft. (1.2 m) Length — 4 ft. (1.2 m) Width — 4 ft. (1.2 m) Maximum Size (without drip board) 14 in. (36 cm) x 15 in. (38 cm) Low Proximity Maximum Size (without drip board) 141/2 in. (37 cm) x 14 in. (36 cm) Medium Proximity Maximum Size (without drip board) 15 in. (38 cm) x 14 in. (36 cm) High Proximity Medium Proximity Maximum Size (without drip board) 19 1/2 in. (49.5 cm) x 19 in. (48.2 cm) High Proximity Low Proximity Maximum Size (without drip board) 18 in. (45:7. cm) x 18 in. (45.7 cm) High Proximity Minimum Nozzle Nozzle Quantity Heights 1 1 1 1 1 1 1 1 1 For multiple nozzle protection of single fryers, see detailed information on Pages 4-12 through 4-14. 13 — 16 in. (33 — 41 cm) 16 — 27 in. (41 - 69 cm) 27 — 47 in. 20 — 27 in. 21 — 34 in. 13-16 in. 25 — 35 in. (64-89 cm) Nozzle Part No. 430912 419337 419337 419334 419335 430192 419336 419336 419342 419342 419339 419340 419338 419342 419338 Nozzle Tip Stamping — Flow No. 1W 2W 2W 1 /2N 1N 1W 1W 1W 290 290 230 245 3N 290 3N Nozzle Application Chart (Continued) Hazard Fryer (Non -Split Vat Only)` Fryer (Split or Non -Split Vat) Fryer (Split or Non -Split Vat) Range Maximum Hazard Dimensions Maximum Size (with drip board) 21 in: (53 cm) x 14 in. (36 cm). (Fry Pot must not exceed 15 in. x 14 in: (38 cm x 36 cm)) High Proximity Medium Proximity Maximum Size (with drip board) 25 3/8 in. (64.4 cm) x 19 1/2 in: (49.5 cm) (Fry pot side must not exceed 19 1/2 in. (49.5 cm) x 19 in. (48.2 cm) High Proximity . Low Proximity Maximum Size (with drip board) 18 in. (45.7 cm) x 27 3/4 in. (70.5 cm) High Proximity Minimum Nozzle Nozzle Quantity Heights 1 Maximum Size (with drip board) 14 in. (36 cm) x 21 in. (53 cm) Low Proximity Maximum Size (with drip board) 141/2in. (37cm) x 261/2 in. (67 cm) Medium Proximity Longest Side 1 32 in. (81 cm) Area — 384 sq. in. _ (2477 sq. cm) Longest Side 28 in. (71 cm) Area — 336 sq. in. (2168 sq. cm) Longest Side (High Proximity) 1 28 in. (71 cm) Area — 672 sq. in. (4335 sq. cm) Longest Side (Medium Proximity) 1 32 in. (81 cm) Area -768 sq. in. (4955 sq. cm) Longest Side (Low Proximity) 2 36 in. (91 cm) Area —1008 .sq. in. (6503 sq. cm) For multiple nozzle protection of single fryers, see detailed. information on Pages 4-7 through 4-11. SECTION IV - SYSTEM DESIGN UL EX; 3470 ULC CEx747 Page 4-29 4-1-06 REV 27 — 47 in. 20 — 27 in. 21 —34 in. 13-16 in. 25 — 35 in. (64-89 cm) 13 —16 in: (33 —41 cm) 16 — 27 in. (41 — 69 cm) 30 — 40 in. (76 -102 cm) 40 — 48 in. (102 —122 cm) (With Backshelf) 40— 50 in. (102 — 127 cm) 30 — 40 in. (76 —102 cm) 15 — 20 in. (38 — 51 cm) Nozzle Part No. 419339 419340 419338 419342 419338 419342 419342 419335 419333 419340 419341 419342 Nozzle Tip Stamping — Flow No. 230 245 3N 290 3N 290 290 1N 1F 245 260 290 SECTION IV - SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-30 REV. 3 10-1-02 Nozzle Application Chart (Continued) Hazard Griddle Chain Broiler* (Overhead Protection) Chain Broiler (Horizontal Protection) Gas -Radiant Char -Broiler Electric Char -Broiler Lava -Rock Broiler Natural Charcoal Broiler Lava -Rock or Natural Charcoal Char -Broiler Maximum Hazard Dimensions Longest Side (High Proximity) 48 in. (122 cm) Area – 1440 sq. in. (9290 sq. cm) Longest Side (High Proximity) 1 30 in. (76 cm) Area – 720 sq. in. (4645 sq. cm) Longest Side (High Proximity) 1 36 in. (91 cm) Area –1080 sq. in. (6968 sq. cm) Longest Side (Medium Proximity) 48 in. (122 cm) Area –1440 sq. in. (9290 sq. cm) Longest Side (Low Proximity) 1 48 in. (122 cm) Area – 1440 sq. in. (9290 sq. cm) Longest Side – 34 in. (86 cm) 2 Area –1088 sq. in. (7019 sq. cm) Length – 43 in. (109 cm) Width – 31 in. (79 cm) Longest Side – 36 in. (91 cm) Area – 864 sq. in. (5574 sq. cm) Longest Side – 34 in. (86 cm) Area – 680 sq. in. (4383 sq. cm) Longest Side 24 in. (61 cm) Area – 312 sq. in. (2013 sq. cm) Longest Side – 24 in. (61 cm) Area – 288 sq. in. (1858 sq. cm) Longest Side – 30 in. (76 cm) Area – 720 sq. in. (4645 sq. cm) Minimum Nozzle Quantity 1 1 2 1 Nozzle Heights 30 – 50 in. (76 – 127 cm) (perimeter located) 30 – 50 in. (76 –127 cm) (center located) 35 — 40 in. (89 –102 cm) (perimeter located) 20 – 30 in. (51 – 76 cm) (perimeter located) 10 – 20 in. (25 – 51 cm) (perimeter located) 10 – 26 in. (25 – 66 cm) 1 – 3 in. (3 – 8 cm) 15 – 40 in. (38 –102 cm) 20 – 50 in. (51 – 127 cm) 18 – 35 in. (46 – 89 cm) 18 – 40 in. (46 –102 cm) 14-40 in. (36 –102 cm) • Minimum chain broiler exhaust opening — 12 in. x 12 in. (31 cm x 31 cm), and not less than 60% of internal broiler size. Nozzle Part No. 419341 Nozzle Tip Stamping – Flow No. 260 419342 290 419335/417332 1N/1NSS 419342 290 419343 419336/417333 419335/417332 419335/417332 419335/417332 419335/417332 419335/417332 419338 2120 1 W/1 WSS 1N/1NSS 1N/1NSS 1N/1NSS 1N/1NSS 1N/1NSS 3N .J vir11v necauizieo mecii JIiL .I ,- eiease Assembly (3.0 gallon — Part No. 79290 cr 1.5 gallon — Par, No. 79291) contains the regulated release mechanism, agent tank. expellant gas hose for agent tank hookup. and enclosure knockouts to facilitate installing actuation, piping; expellaru piping; detection system: and additional equipment. This regu- lated release assembly is used in single, double, and multiple - tank systems and must be mounted to a rigid -surface. The release mechanism can be used to interconnect both the actu- ation and expellant gas lines as required per system design. The regulator is designed to allow a constant flow of gas into the tank at 100 psi (690 kPa) when the system is actuated. • In single, double, and multiple -tank systems, the provided expel- lant gas hose connects the aoent tank to the bottom outlet of the regulator. In double and multiple -tank system configurations, the back outlet of the regulator is used as an expellant gas feed for one additional tank -enclosure or tank -bracket hookup. The enclosure contains the required knockouts to facilitate this con- nection. If a pressure switch is to be attached to the regulator, additional fittings are required. . The tank is mounted within the enclosure. The tank contains an adaptor/tube assembly with a burst disc union. The burst disc helps prevent siphoning of the agent up the pipe due to signifi• - cant temperature fluctuations in the area where the • tank is located. The tank is mild steel and, under normal conditions, requires hydrostatic testing every twelve years. - The agent tank is shipped 'uncharged and must be -filled with 1.53 cations (5.6 L) or 3.06 gallons (11.6 L) of only ANSULEX Low pH Liquid Fire Suppressant during installation.. The detection and additional equipment required:per -system design are connected to'the release mechanism. The enclosure contains knockouts to facilitate detection and additional hookups. The system can b•?, actuated automatically, or manually. Auto-" uratic actuation occurs when a fusible link within the detection system separates in a fire condition. Manual actuation of the system occurs when personnel pull on the remote manual pull station pull ring. EXT;NGUISHING AGENT ANSULEX Low pH Liquid Fire Suppressant (1.5 gallon Part No. 79694 or 3.0 gallon — Part No. 79372) is apotassium-based - solution designed for fast knock -down and suppression of grease -related fires. The agent is shipped in plasticcbntaihers which provide one complete tank charge. Agent storage life expectancy is twelve years. The distributor mtist.record the batch numbers and date of shipment receipt to be filed with each instal- lation record. ANSUL, • • ! Total Tank Type of Flow No. Quantity System - - Type of Hardware 1-5 1 Single 1.5 Gal. Reg. Release 6-11 - 1 Single 3.0 Gal. Reg. Release ELECTRICAL SWITCHES — 1_0 fE3 E F The electrical switches are intended for .use with electric gas valves, alarms, contactors, lights, contractor- supplied electric power shut-off devices :and other elect cal devices that are designed to shut off or tum on when the system is actuated. Switches are available in kits: One Switch Kit, Part No: 423878, Two Switch Kit, Part No. 423879, Three Switch Kit,' Part No. 423880, anti Four Switch Kt, Part No. 423881. Each switch has a set of single -pole, double=throw contacts rated at 21 amp, 1 HP, 125, 250, 277 VAC or 2 HP, 250, 277 VAC. Mounting hardware is provided with each kit. R-102 RESTAURANT FIRE SUPPRESSION SYSTEM (Standard UL 300 Listed) Nozzle Identification Chart Nozzle Nozzle Nozzle .Type Part No. - Stamoino 1W Nozzle 419336 1W 1 1WSS Nozzle 417333 1W 1 1N Nozzle 419335 1N 1 NSS Nozzle 417332 1N 1/2N Nozzle 419334 1/2N 3N Nozzle 419338 3N 2W Nozzle 419337 2W 2WH Nozzle 78078 2WH Noz Flov 230 Nole 245 Nozzle 260 Nozzle 290 Nozzle 2120 Nozzle 1F Nozzle 1D0 i407.7.tr Nitrogen Cartridoe Reouired LT -20-R (7032) LT -30-R (5373) 419339 419340 419341 419342 419343 419333 430712 230 245 260 290 2120 1F i1pc, Carbon Dioxide Cartridoe Required 101-10 (15850) 101-20 (17492) Wit%�` 1 f;'J5t 5►S 0i\\ S\J -P 1 kik SAkiT5 O ? (purL. -S) 14,561) 514 c IF Pi -LAP -m.5-0, SicIPIL . Is 5s 1 1 1/2 3 2 2 2 2 2 2 2 1 SECTION IX - APPENDIX • UL EX. 3470 ULC CEx747 Page 9-1 7-1-98 REV. 3 SYSTEM SELECTION GUIDE NOTE: System options do not cover all conceivable variations. They are listed here as a general guideline to show the most common type arrangement for multiple systems, Based on certain system designs utilizing manifolding, non-manifolding, 3 -tank systems, etc., other tank/cartridge combinations can be designed. The combinations below are based on 11 flow, 3.0 gallon tanks and 5 • flow, 1.5 gallon tanks. More competitive designs may be available by utilizing 12 flow and 6 flow systems when appropriate. • Nitrogen Cartridge Required Total Flow No.* Tank Quantity Type of System Single Type of Hardware 1-5 6-11 12-16 17-22 23-27 28-33 28-33 3.0 Gal. Reg. Release (Optional) (2) 3.0 Gal. Additional Tanks 1 1 2 3 1.5 Gal. Reg. Release Single 3.0 Gal. Reg. Release Double 1.5 Gal. Reg. Release 3.0 Gal: Additional Tank Double Multiple Multiple Multiple Multiple 3.0 Gal. Reg. Release 3.0 Gal. Additional Tank 1.5 Gal. Reg. Release 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 3.0 Gal. Reg. Release 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 34-38 1.5 Gal. Reg. Release • 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 39-44 4 Multiple 3.0 Gal. Reg. Release 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 45-49 5 Multiple 1.5 Gal. Reg. Release 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 50-55 5 Multiple 3.0 Gal. Reg. Release 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 56-60 6 Multiple 1.5 Gal. Reg. Release 3.0 Gal. Additional Tank 61-66 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 6 Multiple 3.0 Gal. Reg. Release 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank Based on 5 flow numbers for a t5 gal. system and 11 flow numbers for a 3 0 gal. system. See Pages 4-39 - 4-42 for exceptions. If tanks are manifolded, only a "double tank" nitrogen cartridge (Part No. 73022) can be used. If tanks are manifolded, either an LT -A-101-30 nitrogen cartridge (Part No. 29187) or a double tank cartridge (Part No. 73022) can be used. LT -20-R (7032) LT -30-R (5373) Double (73022) Carbon Dioxide Cartridge Reouired 101-10 (15850) 101-20 (17492) 101-30 (15851) Double (73022) 101-30 (15851) - LT -20-.R (7032) 101-10 (15850) LT -A-101:30 (29187) 101-30 (15851)'"* LT -30-R (5373) 101-20 (17492) LT -A-101-30 (29187) 101-30 (15851r - Double (73022) N/A Double (73022) LT -A-101-30 (29187) Double (73022) LT -A-101-30 (29187) LT -20-R (7032) LT -A-101-30 (29187) LT -A-101-30 (29187) LT -30-R (5373) LT -A-101-30 (29187) LT -A-101-30 (29187) Double (73022) LT -A-101-30 (29187) LT -A-101-30 (29187) Double (73022) LT -A-101-30 (29187) LT -A-101-30 (29187) 101-30 (15851) 101-30 (15851)`- 101-30(15851)" 101-30 (15851y- 101-10 (15850) 101-30 (15851)*** 101-30 (15851)**` 101-20 (17492) 101-30 (15851)* 101-30 (15851)*** 101-30 (15851) 101-30 (15851)*'* 101-30 (15851)" 101-30 (15851)- 101-30 (15851r- 101-30 (15851)"* = =-i "tea r , { 9 I UKWILA FIRE DEPARTMELM , , Please call: 575.4402 and give this job ii No. o8 -H - 3a , and exact address for shute 0 l VithOut CON-Az-ratc )own or restoration approve; - / ❑ AF ;d:::;d In Red 12( Par Tile Au_ chad Leber i nese plans ho -L.,tj hr TIP' -ita Fire Prevent, or, E',. _ , r _.c , .- , . - t c'` ', standards A '• • omissionth vv' starta giros 1, adequacy , L•, Additions, c. , : „ f • t' i this Cat? +v;li voo, !to :t ',.. i',i . >, r� t,,, ,L .7, resubmittal of revrse� ..:.,..o.!• ;s !Jr R ;y:.` yl,`_'t, e.i2rcval. Final acceptance is s ab!ect to f cid test ar,d inspection by The Tukwila Fere Preve,itron Bureau. F Date: 6 -/d1-o8 By: r 1 J ea • ANSLJL. >fycto Fin Suppression & Building Products R-102 RESTAURANT SYSTEM NOZZLE COVERAGE/OVERLAPPING SUMMARY SHEET ► App8ance Nozzle Type Pow Points width In. (cm) Max. Side Multiple Length in. (cm) Max. Stile Multiple Nozzle w/o Drip Board Area int (crrr2) Nozzle w/ Drip Board Area brz (ctnm) Minimum Nozzle Ht. In. (cm) Maximum Nozzle HL in. (cm) Fryers withot{t drip boards Pr0Split 230/290* 2 14 (36) 15 (38) -'Low - 27/13 (69/33) 47/16 (119/41). dr No Split Vat 245/290' 2 14/14.5 (36/37) 15/14 (38/36) - - 20/16 (51/41) 27/27 (69/69) Fryers without drip boards 290 2 19.5 (50) 19 (48.2) - - 13 (33) 16 (41) Non -Split Vat (ONLY) 3N 3 19.5 (50) 19 (48.2) - - 21 (53) 34 (86) 3N 3 18 (45.7) 18 (45.7) - - 25 (64) 35 (89) *Low Prude* Fryers with drip boards 230/290* 2 14 (36) 21 (53) 210 (1355) 294 (1897) 27/13 (69/33) 47/16 (119/41) Split qr No Split Vat' 245/290* 2 14/14.5 (36/37) 21/26.5 (53/67) 210/203 (1355/1310) 2941384.2 (1897/2479) 20/16 (51/41) 27/27 (69/69) fors ! wit1( drip boards' 290 2 19.5 (50) 25 3/8 (65) 370.5 (2390) 495 (3194) 13 (33) 16 (41) Non -Split Vat (ONLY) 3N ' 3 19.5 (50) 25 3/8 (65) 370.5 (2390) 495 (3194) 21 (53) 34 (86) E 3N 3 1$ _ (45.7) 27 3/4 (70.5) 324 (2090) 497 (3206) 25 (64) 35 (89) Tilt SidtietBraisifig Pan' Coverage limitation are based on fryer sizes including the drip boards. Exception: Tilt Skillets and Braising may exceed the maximum of 6 ft2 (0.56 m2) Longest Side Max. Area In' (cm') f'llange 1} L1N - -. -T2 (30.0 �_ X30.5) - 30 (76) 40 (102) Without back shelf 1i 1 ,_ ._ 12 (30.5) .4 28 (71) 336 (2168) - 30 (76) 50 (127) With back shelf' 1F 1 12 (30.5) 28 (71) 336 (2168) - 40 (102) 48 (122) 245 2 24 (61) 28 (71) - - 40 (102) 50 (127) Witho'utback shelf 260 2 24 (61) 32 (81) 768 (4955) - 30 (76) 40 (102) Wi(h back shelf 260 2 12 (30.5) 32 (81) 384 (2477) - 30 (76) 40 (102) 2 x 290 4 36 (91)_ . 28 _ (71) 1008 (6503) - 15 (38) 20 (51) 'Griddle 1 11N/1 NO 1 36.._ (91) _ 34 (76) - - 35 (89)- 40 (102) - 290 2 30 (76) 24 (61) - - 30 (76) 7 50 (127) 260 2 48 (122) 30 (76) - - 30 (76) 50 (127) 290 2 48 (122) 30 (76) - - 20 (51) 30 (76) 2120 2 48 (122) 30 (76) - - 10 (25) 20 (51) Chain Broiler' (Overhead Protecctjon) 2 x 1W 2 34 (86) 30 (76) - 10 (25) 26 (66) Chain Broiler (Horizontal Protec ion) 2 x 1N 2 31 (79) 43 (109) - - Front edge; 1 to (3 to 8 cm) above 3 in. the chain Char Broiler 'Gas -Radiant 1W1NSS 1 24 (61) 36 (91) - - 15 (38) 40 (102) Electric 1W1NSS 1 20 (51) 34 (86) - - 20 (51) 50 (127) Lava -Rock 1W1NSS 1 13 (33) 24 (61) - - 18 (46) 35 (89) Nab ai Charcoal' 1W1NSS 1 12 (30.5) 24 (61) - - 18 (46) 40 (102) Lava -Rock or NattUal Charcoal' 3N 3 24 (61) 30 (76) - - 14 (36) 40 (102) Wood Fueled' 3N 3 24 (61) 30 (76) - - 14 (36) 40 (102) Upright Broiler 2 x 1/2N 1 30 (76) 32.5 (82.5) Front edge; Salamander Brollpr 2 x 1211 1 30 (76) 32.5 (82.5) - - above the grate 1N 1 16 (41) 29 (74) - - - I- !the 1 N nozzle location to be on the vertical edge 6 to 12 in. (15.2 to 30.5 cm) in front and 0 to 12 in. (0 to 30.5 cm) above top of broiler Interjtal Chamber 119 1 16 (41) 29 (74) - - 6-12 in. above either end (15.2 to 30.5 cm) Wok 3.75 to 8 in. deep (9. to 20.3 cm) 260 2 14 to 30 in. (36 to 76 cm) diameter -35 - (89) 45 (114) 3 to 6 In. (7.6 to 15.2 cm) deep ' For multiple nozzle orotwilInn of 1W1NSS ct,,,,e fn,e... 1 .. ., 11 to 24 In. (28 to 61 cm) diameter .,..,.”-. ,-.-__..-_ - 30 (76) 40 (102) pages 4-8 to 4111 of manual. ' See Figure 1 for nozzle location. ' Minimum chair *Deer exhaust opening -12 In. x 12 In. (30.5 cm x 30.5 cm), and not less than160% of internal broiler size. ► ' 4 In. (10 cm) maximum fuel depth. `6 In. (15 cm) maximum fuel depth. • nen can ovemang bumer(s) by maximum of 11 In. (28 cm) and height limitation of 20 In. (51 cm) from bottom of lowest part of shelf to the top of bumer grate. ' Shelf can overhang bumer(s) by maximum of 11 In. (28 cm) and height ► limitation of 18 in. (45.7 cm) from bottom of lowest part of shelf to the top of bumer grate. • Low Proximity ► *NW!. 101 CO Rre Suppression & Building products R-102 RESTAURANT SYSTEM NOZZLE COVERAGE/OVERLAPPING SUMMARY SHEET Duct I Plenum .Horizontal Nozzle Type Flow Points Width in. (cm) Max Side Length In. (cm) Max. Side Nozzle Placement (See Manual for More Detail) Min. Height t In. (cm) Max. Height In. (cm) Protection Single Bank i ` 1N 1 - 48 (122} 120 (305).. 0 in. to.6 In. (0 to 15.2 cm) from end of plenum 2 (5) 4 (10)7 Perpendicular Protection Single Bank 1W 1 48 (122) 48 (122) See Manual for more detail 1 (2.5) 20 (51) Horizontal Protection V -Bank 2 x 1N 2 48 (122) 120 (305) 0 in. to 6 in. (0 to 15.2 cm) from end of plenum 2 (5) 4 (10) Horizontal Protection V Bank 1W 1 48 (122) 72 (183) 0 In. to 6 In. (0 to 15.2 cm) from end of plenum 1/3 the height 01 filter Perpendicular Protection V Bank 1W 1 48 (122) 48 (122) See Manual for more detail 1 (2.5) 20 (51) Duct I Nozzle Type Flow Points Perimeter In. (cm) Diameter In. (cm) Nozzle Placement (See Manual for More Detail) Duct Length in. (cm) Single Nozzle 1 Flow Nozzle 1W 1 50 (127) 16 (41) See Manual for more detail Unlimited reingie Nozzle 2jFlow Nozzle 2W 2 100 (254) 31 7/8 (81) See Manual for more detail Unlimited/ Multiple Nozzle 2W + 1W 3 135 (343) 48 (122) See Manual for more detail Unlimited Multiple 2W No zie 2W — >135 (343) >135 (343) See Manual for more detail Unlimited R-102 OVERLAPPING PROTECTION The 245 nozzle, Part No. 419340, must be used for 'end of zone protection, and the 260 noXzle, Part No. 419341, must be used for zone protection. Appliance lypie Fryer Griddle Range Wok, Maximum Wok, Minimum: Braising Panhlilt Skillet' Lava Rock Char -Broiler Charcoal Broiler Mesquite Wood Broiler Gas Radiant Cftar-Broiler Electric Char -Broiler ' See Figure 1 tor nozzle location. Note: Group protection option is required for appliances on either side of an appliance(s) using dedicated protection — see manual for details. Maximum Cooking Hazard 34 in. (864 mm) Deep x 5.8 ft2 (5388 cm2) 30 in. (762 mm) Deep x Unlimited Length 30 M. (762 mm) Deep x Unlimited Length 30 in. (762 mm) Diameter x 8 in. (203 mm) Deep 11 in. (279 mm) Diameter x 3 in. (76 mm) Deep 34 in. (864 mm) Deep x Unlimited Length 26 in. (660 mm) Deep x Unlimited Length 30 in. (762 mm) Deep x Unlimited Length (4 in. (102 mm) Maximum Fuel Depth) 30 in. (762 mm) Deep x Unlimited Length (6 in. (152 mm) Maximum Fuel Depth) 36 In (914 mm) Deep x Unlimited Length 34 in. (864 mm) Deep x Unlimited Length COVER MUST NOT INTERFERE wiTH EDGE OF DISCHARGE PATTERN ZONE CENTER UNE Overlapping System Piping Limitations System Size 3Gal (11 L) 6 Total Flow Numbers 6 Gal (23 L) 12 Man folded Max. 3/8 in. Max. Pipe No. of Length Elbows 75 ft 25 (22.9 m) 75 ft 25 (22.9 m) 50 ft (15.2 m) maximum pipe from first to last nozzle. 50 ft (15.2 m) maximum pipe after the split on a split system. Maximum Elevation Rise 10ft (3.1 m) 10ft (3.1 m) Cartridge Size LT -30-R Double Tank FIGURE 1 ANSUL INCORPDRA72`D. ONE STANTON STREET. MARINETTE. WI 54143-2542 715-735-7411 Form No. F-2005010-2 CopydgM CMS Maul Incorporated • k § z ± m 6X26 DUCT 0 0 { 360* FUSE LINKS { z — -- -- \ $ Z —111 \ CO 0 _I �0 /\$ 0 @< m \ \ 40-46" 40-46" { -- Z / \/§ 0 w < <0 • 36" X 24" GAS GRIDDLE • • e e • • • • • • * • 36" X 24" GAS RANGE SAN WTCH STATION $ 2 0 j CE =25I tQ.00 E z 2. 0) N C Cr f° E -a 0 �k3 1 / .0. - 2 ` 2 c 0 -Ca C \��} 03 I -C m m e o Coli s=m 2 = o C 0• )2 ■ ck schedule 40 E 03 0 \ 2 £ o ± o = 7 0) • / ■ 0 z / / E 03 0 E f 0) T 03 E 2 0 0 2 2 £ / / \ § j E k \ 0 ■ CEPTED p Without Comments p As Noted in Red Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City is subject to errors and oniasions whim c -a nut authorize violations of adopted ndards ano oraff inces. The responsibility for the ;,t.Prquacy of des'cp ests totally with the designer. ,4rOttions, deletyoris or revisions to these drawingsYafter t is nate wiil void this acceptance and will require a resut rrnittai of revised drawings for subsequent approval. Final acceptance is subject to field test a1d Inspection by 1 rie Tukwila Fire Prevention Bureau. Date: 7 '1 K —I By: 51 I FIRE DEPARDWitni Please call: 575.4407 and give this job No. A2 I and exact address for shuts Town or restoration anorovol Because of increased demand our inspectors' schedules are booked 3-7 days ahead. Therefore, you will need to call 206-575-44,7 or email fireinspreauest@ ci.tukwila.wa.us to schedule your inspections a minimum of 48 hours in advance of the date you want an inspection. 1 11 • ANSUL. f qco Fin Suppression & Building Products R-102 RESTAURANT SYSTEM NO Z LE COVERAGE/OVERLAPPING SUMMARY SHEET . Appliance Nozzle Type Fiow Points Width in. ( Max. Si ) Multiple Length In. (cm) Max. Side Multiple Nozzle w/o Drip Board Area hrz (cm2) Nozzle w/ Drip Board Area tnz (aril Minimum Nozzle Ht. In. (cm) Maximum Nozzle HL In. (cm) Fryers withotjt drip boards 230/290* 2 14 (36) 15 (38) - - 27/13 (69/33) 47/16 (119/41)taw Prokilry. Split dr No Split Vat 245/290' 2 14/14.5 (36/3 15/14 (38/36) - - 20/16 (51/41) 27/27 (69/69) Fryers withotit drip boards 290 2 19.5 (50) 19 (48.2) - - -ti 13 (33) 16 (41) Non -Split Vat (ONLY) 3N 3 19.5 (50) I 19 (48.2) - - 4- " 21^ (53) 34 (86) 3N 3 18 (45.7 18 (45.7) - - ,25 _(64) 35 (89) Fryers with drip boards 'Low Proxlmly 230/290' 2 14 (36) 1 21 (53) 210 (1355) 294 (1897) 27113 •(69/33) 47/16 (119/41) Split qr No Split Vat' 245t290*2 2 14/14.5 (36/30 21/26.5 (53/67) 210/203 (1355/1310) 291/381 (1897/2479) 20/16 (51/41) 27/27 (69/69) Fryers w t1tdrip boards' 290 2 19.5 (50) ; 25 3/8 (65) 370.5 (2390) 495 (3194) 13 (33) 16 ` (41) Non -Split Vat (ONLY) 3N 3 19.5 (50) 25 3/8 (65) 370.5 (2390) 495 (3194) 21 (53) 34 (86) 3N 3 18 (45. 27 3/4 (70.5) 324 (2090) _497 (3206) 25 (64) 35 (89) Tilt SldlietBraisllip Pan' Coverage limitation are based o fryer sizes including the drip boards. Exception: Tilt Skillets and Brai 'ng may exceed the maximum of 6 ft2 (0.56 m2) Longest Side Max. Area in, (cm2) Range 1N 1 12 (30. 32 (81) 384 (2477) - 30 (76) 40 (102) Without back shelf 1F 1 12 (30. 28 (71) 336 (2168) - 30 (76) 50 (127) With back shelf' 1F 1 12 (30.5) 28 (71) 336 (2168) - 40 (102) 48 (122) 245 2 24 (61) 28 (71) - - 40 (102) 50 (127) Without back shelf 260 2 24 (61) 32 (81) 768 (4955) - 30 (76) 40 (102) Wier back shelf' 260 2 12 (30.5) 32 (81) 384 (2477) - 30 (76) 40 (102) 2 x 290 4 36 (91) 28 (71) 1008 (6503) - 15 (38) 20 (51) Griddle 1W1NSS 1 36 (91) 30 (76) - - 35 (89) 40 (102) 290 2 30 (76) 24 (61) - - 30 (76) 50 (127) 260 2 48 (122 30 (76) - - 30 (76) 50 (127) 290 2 48 (122 30 (76) - - 20 (51) 30 (76) 2120 2 48 (122 30 (76) - - 10 (25) 20 (51) Chain Broiler' (Overhead Protection) 2 x 1W 2 34 (86) 30 (76) - - 10 (25) 26 (66) Chain Broiler (Horizontal Protec ion) 2 x 1N 2 31 (79) 43 (109) - - Front edge; 1 to 3 in. (3 to 8 cm) above the chain Char Broiler 1Gas-Radiant 1N/1NSS 1 24 (61) 36 (91) - - 15 (38) 40 (102) Electric 1N/1NSS 1 20 (51) ' 34 (86) - - 20 (51) 50 (127) Lava -Rock 1N/1NSS 1 13 (33) I 24 (61) - - 18 (46) 35 (89) Natt*aICharcoal' 1N/1NSS 1 12 41 (30.) 24 (61) - - 18 (46) 40 (102) Lava -Rock or Natural Charcoal' 3N 3 24 (61) 30 (7 - 14 (36) 40 (102) VI/ood Fueled' 3N 3 24 (61) 30 ) - 14 (36) 40 (102) Upright Broiler 2 x 1/2N 1 30 (76) 32.5 (82.5) :v t Front edge; Salamander Broiler 2 x 1/2N 1 30 (76) 32.5 (82.5) - i' above the grate 1N 1 16 (41) 29 (74) - !- IN nozzle location to be on the vortical edge 6 to 12 In. (15.2 to 30.5 cm) In front and 0 to to 30. ) above the top of broiler Internal Chamber 1N 1 16 (41) 29 (74) - - In. above either end (1 .2 to 30.5 cm) Wok 3.75 to 8 in. deep (9.51 to 20.3 cm) 260 2 14 to 30 In. (36 to 76 cm) diameter - - 35 (89) 45 (114) 3 to 6 In. (7.6 to 15.2 cm) deep ' For multiniw nrv7b nmfn..tb.....G 1 N/1 NSS ei....i. I........ 1 _ 11 to 24 in. (28 to 61 cm) diameter .J__-..-- - - - 30 (76) 40 (102) pages 4-8 to 4-111 of manual. ' See Figure 1 for nozzle location. ►' Minimum chain baohter exhaust opening - 12 In. x 12 In. (30.5 m x 30.5 cm), and not less than 16o% of Internal broiler size. ► ' 4 In. (10 cm) maximum fuel depth. 6 In. (15 an) maximum fuel depth. ' Snen can overhang bumer(s) by maximum of 11 In. (28 cm) and height limitation of 20 In. (51 cm) from bottom of lowest part of shelf to the top of bumer grate. Shelf can ht ►' limitation of 18 in. overhang45.7 cm) from bottom of maximum olowest part of shel) f to the top of bumer grate. • Low Proximity •L • ANSLJL. Vico Rre Suppression & Building Products NOZZL R-102 RESTAURANT SYSTEM COVERAGE/OVERLAPPING SUMMARY SHEET Plenum Nozzle Type Flow Points in. Max. Width (cm) Side Length In. (cm) Max. Side Nozzle Placement (See Manual for More Detail) Min. Height in. (cm) Max. Height In. (cm) Horizontal Protection Single Bank 1N 1 48 (122) 120 (305) 0 in. to 6 in. (0 to 15.2 cm) from end of plenum 2 (5) 4 (10) Perpendicular Protection Single Bank 1W 1 48 (122) 48 (122) See Manual for more detail 1 (2.5) 20 (51) Horizontal Protection V -Bank 2 x 1N 2 48 (122) 120 (305) 0 in. to 6 In. (0 to 15.2 cm) from end of plenum 2 (5) 4 (10) Horizontal Protetition V -Bank 1W 1 48 (122) 72 (183) 0 in. to 6 In. (0 to 15.2 cm) from end of plenum 1/3 the he ght of filter Perpendicular Pirotection V -Bank 1 W 1 48 (122) 48 (122) See Manual for more detail 1 (2.5) 20 (51) Duct Nozzle Type Flow Points Perimeter n. (cm) Diameter In. (cm) Nozzle Placement (See Manual for More Detail) Duct Length in. (cm) Single Nozzle 1 IFlow Nozzle 1W 1 50 (127) 16 (41) See Manual for more detail Unlimited Single Nozzle 2tFlow Nozzle 2W 2 100 (254) 31 7/8 (81) See Manual for more detail Unlimited Multiple Nozzle 2W + 1W 3 135 (343) 48 (122) See Manual for more detail Unlimited Multiple 2W No3zle 2W — >135 (343) >135 (343) See Manual for more detail Unlimited R-102 OVERLAPPING PROTECTION The 245 nozzle, Part No. 419340, must be used for -end of zone protection, and the 260 nozzle, Part No. 419341, must be used for zone" protection. Appliance lyp(e Fryer Griddle Range Wok, Maximum Wok, Minimum Braising Pan/Tilt Skillet' Lava Rock Cher -Broiler Charcoal Broiler Mesquite Wood Broiler Gas Radiant Cftar-Broiler Electric Char-Bjoiler ' See Figure 1 10 nozzle location. Note: Group protection option Is required for appliances on either Side of an appliance(s) using dedicated protection — see manual for details. Maximum Cooking Hazard 34 in. (864 mm) Deep x 5.8 12 (5388 cm2) 30 jn. (762 mm) Deep x Unlimited Length 30 in. (762 mm) Deep x Unlimited Length 30 In. (762 mm) Diameter x In. (203 mm) Deep 11 In. (279 mm) Diameter x in. (76 mm) Deep 34 In. (864 mm) Deep x Unl ited Length 26 In. (660 mm) Deep x Unl ited Length 30 In. (762 mm) Deep x Unl fled Length (4 in. (102 mm) Maximum F el Depth) 30 in. (762 mm) Deep x Unl ited Length (6 in. (152 mm) Maximum F el Depth) 36 In (914 mm) Deep x Unli ited Length 34 in. (864 mm) Deep x Uni fled Length COVER MUST NOT INTERFERE WITH EDGE OF DISCHARGE PATTERN 0-12 IN 11 (0.305 mm) I • 1 1 ZONE i ZONE CENTER UNE Overlapping System Piping Limitations System Size 3Gal (11 L) 6 Total Flow Numbers 6 Gal (23 L) 12 Manifolded 50 ft (15.2 m) maximum 50 ft (15.2 m) maximum Max. 3/8 in. Max. Pipe No. of Length Elbows 75 ft 25 (22.9 m) 75 ft 25 (22.9 m) pipe from first to last nozzle. pipe after the split on a split system. Maximum Elevation Rise 10ft (3.1 m) 10 ft (3.1 m) Cartridge Size LT -30-R Double Tank FIGURE 1 ANSUL INCORPORAT ONE E STANTON STREET. MARINErTE. WI 541 542 715-735-7411 Forth No. F-2005010-2 CoPrhWtt moo Mau incorporated a A11NSU.IL. R-102TM' RESTAURANT SYSTEM DISTRIBUTION PIPING REQUIREMENTS SHEET Distribution Piping Requirements - 6.0 Gallon (22.7 Liter Manifolded System Requirements Supply Une Duct Branch Une Plenum Branch Line Appliance Branch Une Pipe Size Maximum Lepgth Maximum Rise Maximum 90r Elbow Maximum Tees Maximum Flaw Numbers 3/8 In. 32 ft (9.7 m) 6 ft (1.8 m) 8 2 22 3/8 in. 8 ft (2.4 m) 4 ft (1.2 m) 4 2 4 3/8 in. 4ft(1.2m) 2 ft (0.6 m) 4 2 2 3/8 in. 12 ft (3.7 m) 2 ft (0.6 m) 6 4 4 Distribution Piping Requirements - 6.0 (22.7 Liter) Gallon System 1. The maXimum length between the start of the first branch Ilne and the start of the last branch line must not exceed 24 ft (7.3 m). When thsupply line is split, the combined total of both legs of the supply line (from the start of the first branch line to the start of the,last branch line) must not exceed 24 ft (7.3 m). 2. -',..The total length of all branch lines must not exceed 36 ft (10.9 m). -34 Use a 3/6 in., union to connect the tank adaptor to the 3/8 in. supply line. ► _.: Disiributlon Piping Requirements - 9.0 (34 Liter) Gallon System Requirements Duct Supply Une Branch Une Plenum Branch Une Appliance Branch Une Pipe Size 3/8 in. Maximum Length 40 ft (12.2 m) Maximum Rise 6 ft (1.8 m) Maximum 90° Elbow 9 Maximum Tees 1 Maximum Flow Numbers 11' 'Exceptions; 1. Twelve (14) flow numbers are allowed in any one t 2. Twelve (1) flow numbers are allowed with any one 3. Twelve (14) flow numbers are allowed with any one Special Insthjuctions: 1. Twelve (12) flow numbers are allowed when four (4) 2. For certain McDonald's applications, 11.5 flow num • 1/2N electrostatic precipitator nozzle, one (1) 1N ple Applications Engineering Department for additional i 3/8 in. 8 ft (2.4 m) 4 ft (1.2 m) 4 2 4 3/8 in. 4 ft (1.2 m) 2 ft (0.6 m) 4 2 2 k for hood and duct protection. nk using only two -flow appliance nozzles. k using only three -flow appliance nozzles. 3/8 in. 12 ft (3.7 m) 2 ft (0.6 m) 6 4 4 jean Industries GTI Gas Fryers are protected at low proximity. rs are allowed when using a combination of one (1) 2W duct nozzle, one (1) um nozzle, and four (4) two -flow appliance nozzles. Contact ANSUL formation. Distribution Piping Requirements - 9.0 (34 Liter) G 1. The max)mum length between the start of the first b When the supply line Is split, the combined total of the last branch line) must not exceed 24 ft (7.3 m). 2. The total length of all branch lines must not exceed ft (10.9 m). 3. Use a 3/1 In. union to connect the tank adaptor to th = 3/8 in. supply line. Ion System line and the start of the last branch line must not exceed 24 ft (7.3 m). th legs of the supply line (from the start of the first branch line to the start of General Poling Requirements 1. All R-104 system piping is straight line. Therefore, _ need for critical lengths and balancing is minimized. 2. Two 45° ;elbows count as one 90° elbow. 3. Each branch line includes the tee or elbow leading to it, and all fittings within the branch line itself. 4. The minimum piping length of Schedule 40, 3/8 in. pipe from the tank outlet to any nozzle protecting a range, fryer, or wok must be 6 ft (1.8 Vin). 5. Pipe lengths are measured from center of fitting to center of fitting. 6. All distribution piping must be Schedule 40 black iron, chromeplated, or stainless steel. Do not use hot dipped galvanized pipe on the distribution piping. 7. All three connections located in and above the protected area must be sealed with pipe tape. Tape should be applied to male threads ly. Make certain tape does not extend over the end of the thread, as this could cause possible blockage of the agent distrib A 6UL INCORPORATED, ONE STANTON STREET, MARI ETTE. WI 541432542 715-735-7411 Fonn No. F-2005074-1 Copyright ceOO8 Ansel Incorporated 1 C • c• ca o a CDD O • g co z. sa t0 m C 9D "' CG a C c CG uncle pa}aauuoa uaap,SS ■ 0tr alnpauas Noglq sl adld iw In :310N 0 �(DD 5 • CD lQ C7 W0-g.umi o m to to m rn m < 0 (D2. th m0 0 x rn CD o 0 Cco CD o CD CD to :L 1 ■ nv,m1v = • x0-70 rn 3 0 r. 02 o O CD 4 7 -w N 1.12 CD N 3 ro 5 CD CD 0 CD a3 o m j O 3 CD 0 D- ▪ 7 (D a c5 0 O 0 O 3 2. a 0 CD o — 0. co o - Co 0. NOIIVIS HD1Vv JNVS C48' }C 24" GAS GRIDDLE 1II • • 1 0 • • 6 • • C K C -rrl 4 3> °D O C O r r ,,8tr-017 „gtr-017 — O Cb C4 z -- 4�-- n W % y aa) ,,moo O 0 z c') • C rrn O4 rn rn OC°rn • 2 0ZD Z O O z z S>INll 3Sn3 r090 2 0 0 0 ..KX9 o - - i • 9 z m -- -i rn 0, 0 m [T �� i3—Po Ees o -4 o�QD &--rnoF n --1 0 rn� m > V cc. n rno, - CI CO ru - -O rn 91' MO13 ltin1D it ANSUL. tyco An Sappns:fon &BuildingProducts R-102 RESTAURANT SYSTEM NOZZLE COVERAGE/OVERLAPPING SUMMARY SHEET . Appliance pages 4-8 to 4.11 of manual. See Figure 1 for nozzle location. ► ' Minimum chain beer exhaust opening -12 in. x 12 In. (30.5 cm x 30.5 cm), and not less t anl60% of Internal broiler size. ► ' 4 In. (10 cm) max+mum fuel depth. 6 In. (15 cm) max)mum fuel depth. Nozzle type Flow Point+ t46d9r in. ( ) Max. Si Multiple Length in. (cm) Max. Side Multiple Nozzle w/o Drip Board Area Rri (cmz) Nozzle w/ Drip Board Area int (cm2) Minimum Nozzle lit In. (cm) Maximum Nozzle Ht. In. (cm) Fryers wtthot(t drip boards Proximity Split dr No Split Vat Fryers withotit drip boards Non -Split Vat (ONLY) 230/290' 2 14 (36) 15 (38) - - 27/13 (69/33) 47/16 (119/41)tew . 245/290' 2 14/14.5 (36/3 15/14 (38/36) - - 20/16 (51/41) 27/27 (69/69) 290 2 19.5 (50) 19 (48.2) - - 13 (33) 16 (41) 3N 3 19.5 (50) 19 (48.2) - - 21 (53) 34 (86) 3N 3 18 (45.7) 18 (45.7) - - 25 (64) 35 (89) Fryers with drip boards Split cir No Split Vat' 230/290* 2 14 (36) 21 (53) 210 (1355) 294 (1897) 27/13 (69/33) 47/16 (119/41) 245290` 2 14/14.5 (36/37) 21/26.5 (53/67) 210/203 (1355/1310) 294/384.2 (18972479) 20/16 (51/41) 27/27 (69/69) Fryers wit}( drip boards' Non -Split Vat (ONLY) 290 2 19.5 (50) 25 3/8 (65) 370.5 (2390) 495 (3194) 13 (33) 16 (41) 3N 3 19.5 (50) 25 3/8 (65) 370.5 (2390) 495 (3194) 21 (53) 34 (86) 3N 3 18 (45.7) 27 3/4 (70.5) 324 (2090) 497 (3206) 25 (64) 35 (89) Tilt Skillet/Bnisif4g Pan° Coverage limitation are based Exception: Tilt Skillets and Braising o1 fryer sizes including the drip boards. may exceed the maximum of 6 ft2 (0.56 m2) Range Without back shelf Wiih back shelf Withdutback shelf Wt tbackshelf Longest Side Max. Area in, (cm') 1N 1 12 (30.5) 32 (81) 384 (2477) - 30 (76) 40 (102) 1F 1 12 (30.5) 28 (71) 336 (2168) - 30 (76) 50 (127) 1F 1 12 (30.5) 28 (71) 336 (2168) - 40 (102) 48 (122) 245 2 24 (61) 28 (71) - - 40 (102) 50 (127) 260 2 24 (61) 32 (81) 768 (4955) - 30 (76) 40 (102) 260 2 12 (30.5) 32 (81) 384 (2477) - 30 (76) 40 (102) 2 x 290 4 36 (91) 28 (71) 1008 (6503) - 15 (38) 20 (51) Griddle 1W1NSS 1 36 (91) 30 (76) - - 35 (89) 40 (102) 290 2 30 (76) 24 (61) - - 30 (76) 50 (127) 260 2 48 (1221 30 (76) - - 30 (76) 50 (127) 290 2 48 (122 30 (76) - - 20 (51) 30 (76) 2120 2 48 (122 30 (76) - - 10 (25) 20 (51) Chain Broiler' (Overhead Protection) 2 x 1W 2 34 (86) 30 (76) - - 10 (25) 26 (66) Chin Broiler (Horizontal Protection) Ch Char Broiler jGas-Radiant Electric Lava -Rock Natural Charcoal' Lava -Rock or Naturae Charcoal' V/lood Fueled` 2 x 1N 2 31 (79) 43 (109) - - Front edge; 1 to 3 in. (3 to 8 cm) above the chain 1W1NSS 1 24 (61) 36 (91) -- 15 (38) 40 (102) 1W1NSS 1 20 (51) 34 (86) - - 20 (51) 50 (127) 1W1NSS 1 13 (33) 24 (61) - - 18 (46) 35 (89) 1W1NSS 1 12 (30.) 24 (61) - - 18 (46) 40 (102) 3N 3 24 (61) 30 (76) -- 14 (36) 40 (102) 3N 3 24 (61) 30 (76) - - 14 (36) 40 (102) Upright Broiler Salamander Broiler 'Mahal Chamber 2 x 1/2N 1 30 (76) 32.5 (82.5) Front edge; 2 x 1/2N 1 30 (76) 32.5 (82.5) - - above the grate 1N 1 16 (41) 29 (74) - - - - 1 N nozzle location to be on the vertical edge 6 to 12 In. (15.2 to 30.5 cm) In front and 0 to 12 In. (0 to 30.5 cm) above the top of broiler 1N 1 16 (41) 29 (74) - - 6-12 in. above either end (15.2 to 30.5 cm) Wok 3.75 8 In. deep (9. to 20.3 cm) 3 to 6 in. (7.6 to 15.2 cm) deep 260 2 14 to 30 in. (36 to 76 cm) diameter ( - - 35 (89) 45 (114) 1W1NSS 1 11 to 24 in. (ptj-8 to 61 cm) diameter - - 30 (76) 40 (102) 1 For multinia nn77in nrnte..fi.... of . t....I,. f....... - _.J___ . Shelf can overhang bume (s) by maximum of 11 in. (28 cm) and height limitation of 20 In. (51 cm) from bottom of lowest part of shelf to the top of bumer grate. ' Shelf can overhang bumer(s) by maximum of 11 in. (28 cm) and height ► limitation of 18 in. (45.7 cm) from bottom of lowest part of shelf to the top of bumer grate. • Low Proximity 10. v. 3. •l • ANSLJL. !Vico Are Suppression & Building Products NOZZL R-102 RESTAURANT SYSTEM COVERAGE/OVERLAPPING SUMMARY SHEET Plenum i Nozzle Type Flow Points Width in. (cm) Max. Side Length In. (cm) Max. Side Nozzle Placement (See Manual for More Detail) Min. Height In. (cm) Max. Height In. (cm) Horizontal Protebtlon Single Bank 1N 1 48 (122) 120 (305) 0 in. to 6 in. (0 to 15.2 cm) from end of plenum 2 (5) 4 (10) Perpendicular Ptotection Single Bank 1W 1 48 (122) 48 (122) See Manual for more detail 1 (2.5) 20 (51) Horizontal Prote4tion V -Bank 2 x 1N 2 48 (122) 120 (305) 0 in. to 6 in. (0 to 15.2 cm) from end of plenum 2 (5) 4 (10) Horizontal Protection V -Bank 1W 1 48 (122) 72 (183) 0 in. to 6 In. (0 to 15.2 cm) from end of plenum 1/3 the height of filter Perpendicular Pfotectlon V -Bank 1 W 1 48 (122) 48 (122) See Manual for more detail 1 (2.5) 20 (51) R-102 OVERLAPPING PROTECTION The 245 nozzle, Part No. 419340, must be used for "end of and the 260 noXzle, Part No. 419341, must be used for 'z Appliance 'type Fryer Griddle Range Wok, Maximum Wok, Minimum; Braising Panrfllt Skillet' Lava Rock Cher -Broiler Charcoal Broiler Mesquite Wool) Broiler Gas Radiant Ctiar-Broiler Electric Char -Boiler ' See Figure 1 foj nozzle location. Note: Group protection option is required for appliances on either Maximum Cookln, Hazard 34 in. (864 mm) Deep x 5.8 30 in. (762 mm) Deep x Un 30 in. (762 mm) Deep x Unli 30 in. (762 mm) Diameter x 11 in. (279 mm) Diameter x 34 In. (864 mm) Deep x Unl 26 In. (660 mm) Deep x Unl 30 In. (762 mm) Deep x Unl (4 In. (102 mm) Maximum F 30 in. (762 mm) Deep x Unl (6 in. (152 mm) Maximum F 36 in (914 mm) Deep x Unli 34 In. (864 mm) Deep x Unl Overlapping System Piping Umitations Total Max. 3/8 In. Max. System Flow Pipe No. of Size Numbers Length Elbows 3Gal (11 L) 6 75ft 25 (22.9 m) 6 Gal (23 L) 12 75 ft Manifolded (22.9 m) 50 ft (15.2 m) Maximum pipe from first to last nozzle. 50 ft (15.2 m) maximum pipe after the split on a split systerk 25 e' protection, e protection. 2 (5386 cm2) ited Length ited Length in. (203 mm) Deep in. (76 mm) Deep ited Length ited Length lied Length el Depth) fled Length el Depth) ited Length ked Length COVER MUST NOT INTERFERE WiTH EDGE OF DISCHARGE PATTERN 1 t 1.0--46 0-12 IN I I (0-305 mm) 1 1 '1 I1 1 1 ZONE ZONE CENTER UNE ide of an appliance(s) using dedicated protection — see manual for details. Maximum Elevation Rise 10ft (3.1 m) 10 ft (3.1 m) Cartridge Size LT -30-R Double Tank FIGURE 1 ANSUL INCORPORATiu, ONE STANTON SWEET, MARItETTE. WI 541 542 715-735-7411 Form No. F-2005010-2 Copyright 02008 Ansul Incorporated Nozzle Placement Duct Nozzle Flow erimeter Diameter (See Manual Length Duct 1 Type Points n. (cm) In. (cm) for More Detail) In. (cm) Single Nozzle 1 Flow Nozzle 1W 1 (127) 16 (41) See Manual for more detail Unlimited Single Nozzle 21Fiow Nozzle 2W 2 100 (254) 31 7/8 (81) See Manual for more detail Unlimited Multiple Nozzle 2W + 1W 3 135 (343) 48 (122) See Manual for more detail Unlimited Multiple 2W Noizle 2W — >135 (343) >135 (343) See Manual for more detail Unlimited R-102 OVERLAPPING PROTECTION The 245 nozzle, Part No. 419340, must be used for "end of and the 260 noXzle, Part No. 419341, must be used for 'z Appliance 'type Fryer Griddle Range Wok, Maximum Wok, Minimum; Braising Panrfllt Skillet' Lava Rock Cher -Broiler Charcoal Broiler Mesquite Wool) Broiler Gas Radiant Ctiar-Broiler Electric Char -Boiler ' See Figure 1 foj nozzle location. Note: Group protection option is required for appliances on either Maximum Cookln, Hazard 34 in. (864 mm) Deep x 5.8 30 in. (762 mm) Deep x Un 30 in. (762 mm) Deep x Unli 30 in. (762 mm) Diameter x 11 in. (279 mm) Diameter x 34 In. (864 mm) Deep x Unl 26 In. (660 mm) Deep x Unl 30 In. (762 mm) Deep x Unl (4 In. (102 mm) Maximum F 30 in. (762 mm) Deep x Unl (6 in. (152 mm) Maximum F 36 in (914 mm) Deep x Unli 34 In. (864 mm) Deep x Unl Overlapping System Piping Umitations Total Max. 3/8 In. Max. System Flow Pipe No. of Size Numbers Length Elbows 3Gal (11 L) 6 75ft 25 (22.9 m) 6 Gal (23 L) 12 75 ft Manifolded (22.9 m) 50 ft (15.2 m) Maximum pipe from first to last nozzle. 50 ft (15.2 m) maximum pipe after the split on a split systerk 25 e' protection, e protection. 2 (5386 cm2) ited Length ited Length in. (203 mm) Deep in. (76 mm) Deep ited Length ited Length lied Length el Depth) fled Length el Depth) ited Length ked Length COVER MUST NOT INTERFERE WiTH EDGE OF DISCHARGE PATTERN 1 t 1.0--46 0-12 IN I I (0-305 mm) 1 1 '1 I1 1 1 ZONE ZONE CENTER UNE ide of an appliance(s) using dedicated protection — see manual for details. Maximum Elevation Rise 10ft (3.1 m) 10 ft (3.1 m) Cartridge Size LT -30-R Double Tank FIGURE 1 ANSUL INCORPORATiu, ONE STANTON SWEET, MARItETTE. WI 541 542 715-735-7411 Form No. F-2005010-2 Copyright 02008 Ansul Incorporated ANAL. R-102TM' ESTAURANT SYSTEM DISTRIBUTION PIPING REQUIREMENTS SHEET Distribution Piping Requirements - 6.0 Gallon (22.7 UterManifolded System Requirement's Supply Une Duct Branch Une Plenum Branch Une Appliance Branch Une Pipe Size Maximum Length Maximum RiSe Maximum 90r Elbow Maximum Tees Maximum Flow Numbers 3/8 In. 32 ft (9.7 m) 6 ft (1.8 m) 8 2 22 3/8 in. 8 ft (2.4 m) 4 ft (1.2 m) 4 2 4 3/8 in. 4 ft (1.2 m) 2 ft (0.6 m) 4 2 2 3/8 in. 12 ft (3.7 m) 2 ft (0.6 m) 6 4 d Distribution Piping Requirements - 6.0 (22.7 Liter) Gallon System 1. The maximum length between the start of the first branch Ilne and the start of the last branch line must not exceed 24 ft (7.3 m). When the supply line is split, the combined total of both legs of the supply line (from the start of the first branch line to the start of the last branch line) must not exceed 24 ft (7.3 m). 2. The•total length of all branch lines must not exceed 303 ft (10.9 m). 3' Use a 3/6 in. union to connect the tank adaptor to the 3/8 in. supply line. Distribution Piping Requirements - 9.0 (34 Uter) Gallon Requirement's Supply Une System Duct Branch Une Plenum Branch Une Appliance Branch Une Pipe Size 1 3/8 in. 3/8 in. 3/8 in. 3/8 in. Maximum Length 40 ft (12.2 m) 8 ft (2.4 m) 4 ft (1.2 m) 12 ft (3.7 m) Maximum Rife 6 ft (1.8 m) 4 ft (1.2 m) 2 ft (0.6 m) 2 ft (0.6 m) Maximum 90? Elbow 9 4 4 6 Maximum Teas 1 2 2 4 Maximum Flow Numbers 11' 4 2 4 'Exceptions; 1. Twelve (12) flow numbers are allowed In any one tank for hood and duct protection. 2. Twelve (12) flow numbers are allowed with any one nk using only two -flow appliance nozzles. 3. Twelve (1?) flow numbers are allowed with any one k using only three -flow appliance nozzles. Special Inst#uctions: 1. Twelve (12) flow numbers are allowed when four (4) can Industries GTI Gas Fryers are protected at low proximity. 2. For certal' McDonald's applications, 11.5 flow numb rs are allowed when using a combination of one (1) 2W duct nozzle, one (1) 1/2N elegy rostatic precipitator nozzle, one (1) 1N ple um nozzle, and four (4) two -flow appliance nozzles. Contact ANSUL Applicatio Engineering Department for additional i formation. Distribution Piping Requirements - 9.0 (34 Uter) G Ion System 1. The maximum length between the start of the first b line and the start of the last branch line must not exceed 24 ft (7.3 m). When the supply line is split, the combined total of th legs of the supply line (from the start of the first branch line to the start of the last branch line) must not exceed 24 ft (7.3 m). 2. The tota length of all branch lines must not exceed ft (10.9 m). 3. Use a 3,13 In. union to connect the tank adaptor to the 3/8 in. supply line. General Pining Requirements 1. All R-104 system piping is straight line. Therefore, the need for critical lengths and balancing is minimized. 2. Two 45' leibows count as one 90' elbow. 3. Each brr> h line Includes the tee or elbow leading t it, and all fittings within the branch line itself. 4. The minimum piping length of Schedule 40, 3/8 In. pe from the tank outlet to any nozzle protecting a range, fryer, or wok must be 6ft(1.8m). 5. Pipe lengths are measured from center of fitting to center of fitting. 6. All distribution piping must be Schedule 40 black iron, chromeplated, or stainless steel. Do not use hot dipped galvanized pipe on the distrilaution piping. 7. All threaded connections located in and above the protected area must be sealed with pipe tape. Tape should be applied to male threads only. Make certain tape does not extend over the end of the thread, as this could cause possible blockage of the agent distributlOn. AMAX INCORPORATED. ONE STANTON STREET, MARIr ETTE, W1541432542 715-735-7411 Form No. F2005071-1 Copyright 02004 Ana Incorporated 1 \`c K \ $ }k 0o a. to cr< J � / \ so 0c CD Wagla aal; o} pa}oauuoo w s,S ■ Ob alnpagos losiq sl did ilb' ■ :DION ■ e RK7 7 2. 5'n 5mGE u 0-E m g E m m rnCO I.C2 CD ƒ\I0 (ti — o ? o — \ ® 5' CD - NOIIVIS HD1W►ANV'S 111 48' X 24" GAS GRIDDLE 111 \ k — & -- — 9 A co / is j ------ �0) \ x7 / g k S>INI1 DSnA :09£ I 0 0 0 m \ k — & -- — 9 A co / is j ------ �0) \ x7 / g k S>INI1 DSnA :09£ I 0 0 0 m •t • ANSUL. tyco Fir. Suppression & Building Products R-102 RESTAURANT SYSTEM NOZ7LE COVERAGE/OVERLAPPING SUMMARY SHEET ApplIance Nozzle Type Flow Paints Width in. (an) Max. Side Multiple Length in. (cm) Max. Side Multiple Nozzle w/o Drip Board Area irtz (cm2) Nozzle w/ Drip Board Area Int (cm2) Minimum Nozzle RL in. (cm) Maximum Nozzle Rt in. (cm) Fryers without drip boards 23W290' 2 14 (36) 15 (38) - - 27/13 (69/33) 47/16 (119/41)*Low �Spiit dr No Split Vat 245/290' 2 14/14.5 (36/37) 15/14 (38/36) - - 20/16 (51/41) 27/27 (69/69) Fryers without drip boards 290 2 19.5 (50) 19 (48.2) - - 13 (33) 16 (41) Non -Split Vat (ONLY) 3N 3 19.5 (50) 19 (48.2) - - 21 (53) 34 (86) 3N 3 18 (45.7) 18 (45.7) - - 25 (64) 35 (89) Fryers with drip boards 230/290` 2 14 (36) 21 (53) 210 (1355) 294 (1897) 27/13 (69/33) 47/16 (119/41) 'Lot Pnoinity Spilt qr No Split Vat' 245/290' 2 14/14.5 (36/3 21/26.5 (53/67) 210/203 (1355/1310) 29413812 (1802479) 20/16 (51/41) 2727 (69/69) Fryers with drip boards' 290 2 19.5 (50) 25 3/8 (65) 370.5 (2390) 495 (3194) 13 (33) 16 (41) Non -Split Vat (ONLY) 3N 3 19.5 (50) 25 3/8 (65) 370.5 (2390) 495 (3194) 21 (53) 34 (86) 3N 3 18 (45. 27 3/4 (70.5) 324 (2090) 497 (3206) _ 25 (64) 35 (89) Tilt Skiliet/Bratshig Pan' Coverage limitation are based o fryer sizes including the drip boards. Exception: Tilt Skillets and Brai 'ng may exceed the maximum of 6 ft2 (0.56 m2) Longest Side Max Area ire (cm') Range 1N 1 12 (30.1 32 (81) 384 (2477) - 30 (76) 40 (102) Without back shelf 1F 1 12 (30.1 28 (71) 336 (2168) - 30 (76) 50 (127) With back shelf' 1F 1 12 (30. 28 (71) 336 (2168) - 40 (102) 48 (122) 245 2 24 (61) 28 (71) - - 40 (102) 50 (127) Withdutbackshelf 260 2 24 (61) 32 (81) 768 (4955) - 30 (76) 40 (102) Writ' back shelf' 260 2 12 (30: 32 (81) 384 (2477) - 30 (76) 40 (102) 2 x 290 4 36 (91) 28 (71) 1008 (6503) - 15 (38) 20 (51) Griddle 1W1NSS 1 36 (91) 30 (76) - - 35 (89) 40 (102) 290 2 30 (76) 24 (61) - - 30 (76) 50 (127) 260 2 48 (122 30 (76) - - 30 (76) 50 (127) 290 2 48 (122 30 (76) - - 20 (51) 30 (76) _ 2120 2 48 (122 30 (76) - - 10 (25) 20 (51) Chain Broiler' (Overhead Protection) 2 x 1W 2 34 (86) 30 (76) - - t0 (25) 26 (66) Chain Broiler (Horizontal Protection) 2 x 1N 2 31 (79) 43 (109) - - Front edge; 1 to 3 in. (3 to 8 cm) above the chain Char Broiler IGas-Radiant 1W1NSS 1 24 (61) 36 (91) - - 15 (38) 40 (102) Electric 1 W1 NSS 1 20 (51) 34 (86) - - 20 (51) 50 (127) Lava -Rock 1W1 NSS 1 13 (33) I 24 (61) - - 18 (46) 35 (89) NatujaICharcoal' 1WINSS 1 12 (30.5) 24 (61) - - 18 (46) 40 (102) Lava -Rock or Natural Charcoal' 3N 3 24 (61) 30 (76) - - 14 (36) 40 (102) yllood Fueled` 3N 3 24 (61) 30 (76) - - 14 (36) 40 (102) Upright Broiler 2 x 1/2N 1 30 (76) 32.5 (82.5) Front edge; Salamander Broiler 2 x 1/2N 1 30 (76) 32.5 (82.5) - - above the grate 1N 1 16 (41) 29 (74) - - - - 1N nozzle location to be on the vertical edge 6 to 12 In. (15.2 to 30.5 cm) In front and 0 to 12 in. (0 to 30.5 cm) above the top of broiler Interhal Chamber 1N 1 16 (41) 29 (74) - - 6-12 in. above either end (15.2 to 30.5 cm) Wok 3.75 8 In. deep (9. to 20.3 cm) 260 2 14 to 30 in. (56 to 76 cm) diameter I - - 35 (89) 45 (114) 3 to 6 in. (7.6 to 15.2 cm) deep 1 W1 NSS 1 11 to 24 in. (8 to 61 cm) diameter f - - 30 (76) 40 (102) rryars, sea oe[anea wn4rma[an on pages 4-8 to 411, of manual. See Figure 1 for nozzle location. P. • Minimum chain biolier exhaust opening -12 In. x 12 In. (30.5 cm x 30.5 cm), arid not Tess than160% of internal broiler size. ► ' 4 In. (10 cm) maxfrnum fuel depth. `6 In. (15 cm) maximum fuel depth. •Shen can overhang bumer(s) by maximum of 11 In. (28 cm) and height limitation of 20 In. (51 cm) from bottom of lowest part of shelf to the top of burner grate. Shelf bums ► r limitation nof 18 .(45.7 cm) from bottom maximum of lowest part of shelf to the top of bumer grate. • Low Proximity '1 ANSti. tgco Sr. Suppmsslon & Building Products NOZZL R-102 RESTAURANT SYSTEM COVERAGE/OVERLAPPING SUMMARY SHEET Plenum Nozzle Type Flow Points Width in. I (cm) Malt. Side Length In. (cm) Max. Side Nozzle Placement (See Manual for More Detail) Min. Height In. (cm) Max. Height In. (cm) Horizontal Proteon Single Bank i 1N 1 48 (122) 120 (305) 0 in. to 6 in. (0 to 15.2 cm) from end of plenum 2 (5) 4 (10) Perpendicular Piotecdon Single Bank 1W 1 48 (122) 48 (122) See Manual for more detail 1 (2.5) 20 (51) Horizontal Protebtion V -Bank 2 x 1N 2 48 (122) 120 (305) 0 in. to 6 In. (0 to 15.2 cm) from end of plenum 2 (5) 4 (10) Horizontal Prote.tion V -Bank 1 W 1 48 (122) 72 (183) 0 in. to 6 in. (0 to 15.2 cm) from end of plenum 1/3 the height of filter Perpendicular Protection V -Bank 1 W 1 48 (122) 48 (122) See Manual for more detail 1 (2.5)1 20 (51) R-102 OVERLAPPING PROTECTION The 245 nozzle, Part No. 419340, must be used for "end of and the 260 nozzle, Part No. 419341, must be used for 'z Appliance Type Fryer Griddle Range Wok, Maximum Wok, Minimum Braising Pan/Tilt Skillet' Lava Rock Cndr-Broiler Charcoal Broiler Mesquite Wood Broiler Gas Radiant C-rar-Brroiler Electric Char -Boiler ' See Figure 1 toj nozzle location. Note: Group protection option Is required for appliances on either ide of an appliance(s) using dedicated protection — see manual for details. Maximum Cooking Hazard 34 in. (864 mm) Deep x 5.8 30 jn. (762 mm) Deep x Unli 30 in. (762 mm) Deep x Unli e' protection, e" protection. 2 (5368 cm2) tied Length ited Length 30 in. (762 mm) Diameter x in. (203 mm) Deep 11 in. (279 mm) Diameter x $ in. (76 mm) Deep 34 in. (864 mm) Deep x Uni. 26 in. (660 mm) Deep x Uni' 30 in. (762 mm) Deep x Unli (4 in. (102 mm) Maximum F nited Length nited Length nfted Length el Depth) 30 in. (762 mm) Deep x Unl ited Length (6 in. (152 mm) Maximum Fiel Depth) 36 In (914 mm) Deep x Unlimited Length 34 in. (864 mm) Deep x Unlimited Length COVER MUST NOT INTERFERE WITH EDGE OF DISCHARGE PATTERN 0-12 IN 1 (0305 mm) '1 I / 11 ! ZONE f ZONE CENTER UNE Overlapping System Piping Limitations System Size 3 Gal (11 L) 6 Gal (23 L) Manifolded Total Flow Numbers 6 12 Max. 3/8 in. Pipe Length 75 ft (22.9 m) 75 ft 25 (22.9 m) Max. No. of Elbows 25 50 ft (15.2 m) maximum pipe from first to last nozzle. 50 ft (15.2 m) maximum pipe after the split on a split system Maximum Elevation Rise 10ft (3.1 m) 10ft (3.1 m) Cartridge Size LT -30-R Double Tank FIGURE 1 ANSUL WcoRForiAio. arE STANT 4 sTREEr.. MARWErrE. WI 541 542 715-735-7411 Form No. F-2005010-2 Copyright 02608 Aneul Incorporated Nozzle Placement Duct Nozzle Flow !meter Diameter (See Manual Length Duct j Type Points n. (cm) In. (cm) for More Detail) in. (cm) Single Nozzle 1 IFlow Nozzle 1W 1 (127) 16 (41) See Manual for more detail Unlimited Single Nozzle 21Flow Nozzle 2W 2 00 (254) 31 7/8 (81) See Manual for more detail Unlimited Multiple Nozzle 2W + 1W 3 35 (343) 48 (122) See Manual for more detail Unlimited Multiple 2W Noizle 2W — > 35 (343) >135 (343) See Manual for more detail Unlimited R-102 OVERLAPPING PROTECTION The 245 nozzle, Part No. 419340, must be used for "end of and the 260 nozzle, Part No. 419341, must be used for 'z Appliance Type Fryer Griddle Range Wok, Maximum Wok, Minimum Braising Pan/Tilt Skillet' Lava Rock Cndr-Broiler Charcoal Broiler Mesquite Wood Broiler Gas Radiant C-rar-Brroiler Electric Char -Boiler ' See Figure 1 toj nozzle location. Note: Group protection option Is required for appliances on either ide of an appliance(s) using dedicated protection — see manual for details. Maximum Cooking Hazard 34 in. (864 mm) Deep x 5.8 30 jn. (762 mm) Deep x Unli 30 in. (762 mm) Deep x Unli e' protection, e" protection. 2 (5368 cm2) tied Length ited Length 30 in. (762 mm) Diameter x in. (203 mm) Deep 11 in. (279 mm) Diameter x $ in. (76 mm) Deep 34 in. (864 mm) Deep x Uni. 26 in. (660 mm) Deep x Uni' 30 in. (762 mm) Deep x Unli (4 in. (102 mm) Maximum F nited Length nited Length nfted Length el Depth) 30 in. (762 mm) Deep x Unl ited Length (6 in. (152 mm) Maximum Fiel Depth) 36 In (914 mm) Deep x Unlimited Length 34 in. (864 mm) Deep x Unlimited Length COVER MUST NOT INTERFERE WITH EDGE OF DISCHARGE PATTERN 0-12 IN 1 (0305 mm) '1 I / 11 ! ZONE f ZONE CENTER UNE Overlapping System Piping Limitations System Size 3 Gal (11 L) 6 Gal (23 L) Manifolded Total Flow Numbers 6 12 Max. 3/8 in. Pipe Length 75 ft (22.9 m) 75 ft 25 (22.9 m) Max. No. of Elbows 25 50 ft (15.2 m) maximum pipe from first to last nozzle. 50 ft (15.2 m) maximum pipe after the split on a split system Maximum Elevation Rise 10ft (3.1 m) 10ft (3.1 m) Cartridge Size LT -30-R Double Tank FIGURE 1 ANSUL WcoRForiAio. arE STANT 4 sTREEr.. MARWErrE. WI 541 542 715-735-7411 Form No. F-2005010-2 Copyright 02608 Aneul Incorporated a ANS,UL. R-102TM ESTAURANT SYSTEM DISTRIBUTION P PING REQUIREMENTS SHEET Distribution Piping Requirements - 6.0 Gallon (22.7 UterManlfolded System Duct Supply Une Branch Une Requirements Plenum Branch Une Appliance Branch Une Pipe Size Maximum Lehgth Maximum Riyte Maximum 90'r Elbow Maximum Teis Maximum Flgw Numbers 3/8 in. 32 ft (9.7 m) 6ft(1.8m) 8 2 22 3/8 in. 8 ft (2.4 m) 4 ft (1.2 m) 4 2 4 3/8 in. 4ft(1.2m) 2 ft (0.6 m) 4 2 2 3/8 in. 12 ft (3.7 m) 2 ft (0.6 m) 6 4 4 DlstribuUo6 Piping Requirements - 8.0 (22.7 Uter) Gallon System 1. The maximum length between the start of the first branch line and the start of the last branch line must not exceed 24 ft (7.3 m). When this supply line Is split, the combined total of both legs of the supply line (from the start of the first branch line to the start of the,last branch line) must not exceed 24 ft (7.3 m). 2. The total length of all branch lines must not exceed 36 ft (10.9 m). 3;.Use. a 3/8 in., union to connect the tank adaptor to the 3/8 in. supply line. ► .: Dtstributlon Piping Requirements - 9.0 (34 Uter) Gallon System Requirement's Supply Une Duct Branch Une Plenum Branch Une Appliance Branch Une Pipe Size I 3/8 In. 3/8 in. 3/8 in. 3/8 in. Maximum Lehgth 40 ft (12.2 m) 8 ft (2.4 m) 4 ft (1.2 m) 12 ft (3.7 m) Maximum RiSe 6 ft (1.8 m) 4 ft (1.2 m) 2 ft (0.6 m) 2 ft (0.6 m) Maximum 90° Elbow 9 4 4 6 Maximum Tees 1 2 2 4 Maximum Flow Numbers 11' 4 2 4 'Exceptions; 1. Twelve (12) flow numbers are allowed in any one t k for hood and duct protection. 2. Twelve (12) flow numbers are allowed with any one nk using only two -flow appliance nozzles. 3. Twelve (12) flow numbers are allowed with any one k using only three -now appliance nozzles. Special Instjuctlons: 1. Twelve (12) flow numbers are allowed when four (4) bean Industries GTI Gas Fryers are protected at low proximity. 2. For certai McDonald's applications, 11.5 flow numbers are allowed when using a combination of one (1) 2W duct nozzle, one (1) 1/2N el tic precipitator nozzle, one (1) 1N plenum nozzle, and four (4) two -flow appliance nozzles. Contact ANSUL Applicatio Engineering Department for additional information. Distribution Piping Requirements - 9.0 (34 Uter) GaIon System etch line and the start of the last branch line must not exceed 24 ft (7.3 m). th legs of the supply line (from the start of the first branch line to the start of 1. The maximum length between the start of the first b When the supply line is split, the combined total of t the last branch line) must not exceed 24 ft (7.3 m). 2. The tote,length of all branch lines must not exceed ft (10.9 m). 3. Use a 3/8 in. union to connect the tank adaptor to the 3/8 in. supply line. General Piping Requirements 1. All R-104 system piping is straight line. Therefore, the need for critical lengths and balancing is minimized. 2. Two 45° lelbows count as one 90° elbow. 3. Each brunch line includes the tee or elbow leading t it, and all fittings within the branch line itself. 4. The minimum piping length of Schedule 40, 3/8 in. pe from the tank outlet to any nozzle protecting a range, fryer, or wok must be 6ft(1.8in). 5. Pipe lenoths are measured from center of fitting to nter of fitting. 6. All distribution piping must be Schedule 40 black fro , chromeplated, or stainless steel. Do not use hot dipped galvanized pipe on the distribution piping. 7. All three d connections located in and above the protected area must be sealed with pipe tape. Tape should be applied to male threads ly. Make certain tape does not extend over the end of the thread, as this could cause possible blockage of the agent distrib Ar'6Ut. Pl00RPORATED, OPE STANTON STREET. MARINE TE. WI 54143-2542 715-735.7411 Form No. F-2005074-1 Copyright 02ooe Mst4 incorporated waala GA o} papauuoo wa},s,S ■ Otr alnpauos loaiq sl 9c10 11,00 ■ :310N ■ /\2 = K s n 5ncE u a E m CI CD 0 -/7= CD ,s2 ai - -.c \/ ai }c0- $ CD< 0 C ■ 1 § CO k C am: CD a/ƒ7c $ < 0 j _ ; 0 0 CO f ' «' ] E 9 ƒ E 0 - \ -0 \ 0r, CD /\q 0 0 o (1-,- f > / a a o \ e \ \ 0 CD D - 1- NOIIVIS HD1LM INVS 111 48' X 24" GAS GRIDDLE III •■ $ $ •_ • a e { 2 O m z Q. k\\ 0�/ 2 „9tr-017 „9tr-Otr — co > \ / R0 a2 SllNf-1 3Sf13 r09£ 1Dna „8ZX9 I 0 0 0 2 0 6 \ £ I MO1J 1Vfl l k A DAPHNES FIRE ALARM SYSTEM TUKWILA, WASHINGTON Lt. ow a Iv es SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET \UVIRER SHEET TITLE FA -01 SYSTEM INFORMATIO\ FA -02 TYPICAL DETAILS - WIRI\G A D VI O U \TI \ G FA -03 FRE ALARM SYSTEM FLOOR PLA\ FA -04 SYSTEM CALC U LATI O \ S GE\EAL)-, RISE, SITE PLA\ WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATI❑N LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATI❑N TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE 7WO 600V #12 AWG THHN/THWN TWO 600V #14 AWG THHN/THWN TWISTED TWO CONDUCTOR 300V #18 AWG FPL TW CABLE CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BONG RUN IN THE CONDUIT ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF CONDUIT SIZE MAXIMUM F 1/2" .12 SQUARE 3/4" .21 SQUARE 1" .34 SQUARE 1-1/4" .60 SQUARE 1-1/2" .82 SQUARE 2" 1.34 SQUARE FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM DIMENSIONS AREA .244 0.0. .0467 .210 0.D. .0346 .156 0.D. .0191 FROM THE TABLE FILL DIMENSION FROM THE WIRE. LL NCH NCH NCH NCH NCH INCH N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD ® SMOKE DETECTOR HFP-11 IN/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING 1;4 D DUCT SMOKE DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING Ec FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX IN/ 1-1/2" EXT. CEILING L C FIRE ALARM STROBE (CEILING MOUNT) ZR-MC-C.W SIEMENS 4S BOX IN/ 1G RING CEILING ILI FIRE ALARM STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX IN/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. YC FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING Q FB -0 WP MR FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) MULTI -VOLTAGE CONTROL RELAY SET -W SIEMENS SET -S17 -WP SIEMENS MR -201 /C AIR PRODUCTS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD O JUNCTI❑N BOX F,B.❑, N/ Vtttlr r IN FIELD F.B.D. FURNISHED BY OTHERS N/A N/A Without Comments N/A N/A NOT APPLICABLE N/A -e ` As Not Red /A Per The Attached Letter N/A UNLESS OTHERWISE NOTED N/A ' vseenptiloannsBuhraevaeu befoer nc»rmweadncbey wTihthe CTuurkrewnilaarRU.D,N. WP WEATHERPROOF DEVICE N/A missions which do notNytorize violations of adjplt4d standards and ordinances. The responsibility for the A =OE RED AS BUILT ADD OR CHANGE N/A i, 0ditions, deletions or r ons to these drawin `�er this date will void thie.acceptance and will require a ire DE Certifical GREEN AS BUILT REMOVE N/A /A N/A N/A Final acceptance is subject to field test and Inspection by .. commenc Testinc BLUE AS BUILT NOTES TO CAD N/A . _.:., /AcN/A N/A Date: _ °g By: 7'6 and D Failure TUKWILA FIRE DEPART iv...N;.r Please call:575.4407. and give this job andexortred or ationfor apPr tv rlD FAX (206) 628-4990 RELEASE/REVISIONS CO w DESCRIPTION SHOP DRAWINGS w c0 0 0 z C C Jop co T 2a) Cd) w w 0 W Z~ W t� Z CC cp a_ 5 < Q Q o� 0 r� LT_ O oD c'1 NOTICE ted, signed, Tukw apartment Pre-test .e must be presented Inspector prior to :ement of Acceptarce I of any Fire Alarm etection Systems. of test will result inspection Fee and ermination of the testing. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved .CALF: 1 /8"=1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: \OB NUMBER: SHEET n FA -01 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO 11 -IRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND IS❑LATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR S+ PREVIOUS ADDRESSABLE DEVIC Y O DUCT DETECTOR LOCATION END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH 0 rr) 0 GROUND HTRI-R STATUS LED 0 N.O. n O c.0 0 COM N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. O TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE DEVICE TO NEXT ADDRESSABLE DEVICE L NOTE 1: VOLTAGE MAX. - CURRENT MAX. - CONT. RES. MAX. - MAX. CABLE LENGTH - C CLINE TO LINE) - C CLINE TO SHIELD) - MAX. LINE SIZE - MIN. LINE SIZE- OUTLET SAMPLING TUBE INLET SAMPLING -- TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE=NONE MUSICL}-AC POWER SOURCE COMBINE ALL SHIELDS AND IS❑LATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE f STOP IF LAST DEVICE l(-) FROM XLS CONTROL PANEL OR {(+) PREVIOUS ADDRESSABLE DEVICE (-) RELAY CONTACTS C4.OA @ 125VAC) (4.OA @ 30VDC) 27 VDC 3.5 nA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0.O2uF 0.O4uF 14 AWG 18 AWG NOTE 2: ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST 25 SEC. TO GUARANTEE DETECTI❑N. (7/ 0 0 10 01 TB1 5 5 9 0 0 0 1 2 3 4 5 6 TB2 CP 0 0 mct +- 65432 1 END OF LINE DEVICE (3.6K 1/4W) O SUPERVISED. -_-__/ SWITCH GROUND i -4- O HTRI-D OSTATUS LED 00 r 0 C NOT USED O NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 CND N AC 0 0 0 J_ J_ J_ T Y T =r- 0 PAD -3 0 0 00 O INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 1132 24K n + TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE 2 NAC -4 NAC -3 NAC -2 2 NAC -1 END OF LINE DEVICE 3,6K 1/4W) SUPERVISED &WITCH FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. -•I \ NOT USED REMOTE + DEVICE LOOP NOT USED REMOTE DEVICE LOOP 0 0 0 FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY C'S' CABLE) FROM FACP (VOIC,E CIRCUIT) C'V' CABLE) 470 OHMS �YV EOL 0 fC M INPU (+ ` N 9 9 TEM -1 Q INC 1- 0 co TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE NUE (STROBE) SPEAKER (+) ( �) (STROBE) -4-- r EARTH GROUND -)(+)TO NEXT DEVICE OR >(-) STOP IF LAST DEVICE � u () STR❑BE) SPEAKER (+) (—) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY 80" A.F.F. R 4S DEEP BOX W/ 1-1/2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE=NONE TO NEXT DEVICE ❑R END OF LINE TO NEXT DEVICE OR END OF LINE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPE 811N TEMPERA1U E: +32'F 0- C TO 100' F 38' C) HUMIDITY: O- 9 333333% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR —� FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE fDATA IN (-) > DATA IN (+) > DEVICE IS USTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJJNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL TO NEXT DEVICEE- > (-) DATA OUT > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID —� CEILING HARD LID ---SPEAKER SUPPORT TI _- BRIDGE - 4' SQUARE DEEP BOX .-- WITH 1-1/2' EXTENSI❑N N CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE=NONE JUNCTI❑N BOX—, MOUNTED ON \ CEILING FLEX \ //I JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT 0 0 ; 1 TO NEXT DEVICE 0 0 CADDY BAR SMOKE DETECTOR ----- SMOKE' SMOKE DETECTOR MOUNTING SCALE=NONE D f ---- SUSPENDED ILLUMINATED CEILING DO \OT I \STA_L ADDRESSABLE IN T DEVICES .,N I IL DREPROGAMMED W DEVICES ADDHSS. AT O N G TH Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved z co)z z 00 0' 0 z_ (1) LLT J I~ - W U) O' W rte) F-- r--- m ` FAX (206) 628-1+990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS DATE oo 0 tn in 19 CCCCC J o .2E6' 20 2 z CO W o z W � _ F_ ) Q QOM W I\� E-1): 0 op N� I z z 0 0 z z E V )J 0 SCALE: 1 /8"=1 ' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: \OB NUMBER: SHEET FA -02 l • • 2C-3-5 110cd 2A-1-9 110cd EOL 2A-1 ' 111 1 •"�%`-x;11 11 1 }yr• i \\ \.,`\ "I.\\\\\ \ „) �. ' V'� ^\' \\\'\'\..)<;- \\-..''',',,,:.'N '\ �, ,"F; \\\ \ \\ `\`\` \ \ \, \ / S 0+\`2` \\\ \, \ •fit \\\•‘,:\\ \ '_\\\:-_-._\,‘ \_-.-\s._k,1 ,\-_- ,. ,-,,,\:e--,-:-.,-‘7\.._,..\,6s__ \\ \ ,\\.:)"\,\\ \,,\\\(—\ \'"h\\w( \ ` \ \ -''' S :.,._:\ \ • ..\. :.- ,:._ .:.• \ ` V ``Y=�\ 110cd % __ \.. I/ iL;,--\:' ------�\ v S i - \ Eo / 20. NORTH , ,\ It, / % J EX / 1 --,.- 1 1 77-7 2C-- 1 E S DAPHNES SOUTHCENTER MALL WESTFIELD SOUTHCENTER MALL SCALE 118"=1' FLAG \ OTES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE, FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATI❑N SUBMITTAL FOR L❑CATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICAL CONTRACTOR, SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO \CT NS AL ADDRESSABLE IN TIATIr DEVICES UNTIL °REPROGRAMMED WI H DEVICES ADD ESS. G Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 11 rfiC Ci3 141 ®2 CC CO 0' 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z DESCRIPTION SHOP DRAWINGS DATE 5/15/08 2 ‹<aaa JCO CO 'CC a) crZ (/)W~0 W CI -1)z a F=- 5 D< 1 Qo L 0 0� CO SCALE: 1. /8"=1 DRAWN BY: ,.ANDERSON DESIGNED BY: R.VEZZAN I DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: \ 0B NUMBER: FA� 03 j \ 0 • ,1 _'__� 111 / l \; `, 1.11111 / t -'1,111 / ,6` _- 11111 --_f "' .il. 1• 1 , •__-__ -=-= 1 11 \ l Il. \ 1 is I. %1. 11 /"' / : = - NORTH N. 'N. 11s =i_711 RIO;: II it �,ii�il� II � , SII D fier Ir,festa eit, FINES1t ric.„ r(tiotz 0 DAPHNES WESTFIELD SOUTHCENTER MALL 0 0 /6 `` ----- ,‘An!• 4 it SCALE 1132"=1' EX SYSTEM CALCULATIONS BATTERY SIZING CALCULATION DAPHNES DAPHNES FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL DATE 5/15/08 Panel: DAPHNES Wire Resistance 1.62. 9 <«« Date: June 10, 2008 CURRENT TOTAL= Current Load: Standby: Alarm: S1 Current Load: Standby: Alarm: QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 0 SET -MC @15CD 64 0 Device Type Qty Amps Total Amps Total SET -MC @30CD Device Type 196 Qty Amps Total Amps Total 0 HFP-11 175 0 0.0022 0.0022 0.0023 Total Device Load, Amps (1) 0.20 0 SET -MC @11 OCD 233 0 AD2-P 0 0.0635 0.0635 0.064 Main System Board 1 0.03 0 0.03 0.030 0.030 HTR -R 0.009600 0.0096 0.021 SET -HMC @135CD 318 SET -MC @15CD EOL Voltage 0.064 0 SET -HMC @185CD HTRI-D 0 0.001600 0.0035 (20.4 - E) SET -MC @30CD Z-MC@15CD 2 0 0.098 0.196 ICP -B6 0 Z-MC@30CD 0.005 0 SET -MC @75CD 0 SET-MC-CW@110CD 233 0.175 DEVICES= 2 TOTAL mA= 196 12 191 SET -MC @11 OCD 0.233 Notification Appliance Circuit Detail - PROJECT: WESTFIELD SOUTHCENTER MALL SET HMC-C@115CD Panel: DAPHNES Wire Resistance 2.58 0.318 Date: June 10, 2008 CURRENT TOTAL 3.6 CIRCUIT: SPEAKER CIRCUIT SET HMC-C@135CD 0.318 QTY Device Type Alarm Current Alarm Total 0.0731 Amps Voltage at EOL Amps SET HMC-C@185CD 2 70.7V 1/8 1.8 0.445 Total Wire Resistance (R) 0.99 0 0 ZR -MC @15CD 0.064 0 Standby Current Load: 0 0.0731 Amps For 24 Hours = 1.754 Amp -hours ZR -MC @30CD 0.00 0 0 0 0.098 (Total Cct Load) 0 0- 0 HCP - Voltage Drop 0.0015 0.00 0 Alarm Current Load: 0 0 Amps For 5 Minutes= Amp -hours (E=I*R) 0 0 0.03 Amps 0.226 Amps EOL Voltage 20.40 0 0 0 (20.4 - E) 0 25% Derating= 2.193 Amp -hours Standby Current Load: 0 0.03 Amps 3.6 For 24 Hours = 0.720 Amp -hours 3.61 DEVICES= 2 Alarm Current Load: 0.226 Amps For 5 Minutes= 0.019 Amp -hours Total System Current Load: 2.193 Amp -hours 25% Derating= 0.924 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.924 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULATION 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a Notification Appliance Circuit Detail DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL DATE 5/15/08 Panel: DAPHNES Wire Resistance 1.62. 9 <«« Date: June 10, 2008 CURRENT TOTAL= 196 CIRCUIT: S1 QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 0 SET -MC @15CD 64 0 Total Wire Resistance (R) 0.62 2 SET -MC @30CD 98 196 (WL * 2) * (R/ft) 0 SET -MC @75CD 175 0 Total Device Load, Amps (1) 0.20 0 SET -MC @11 OCD 233 0 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 Voltage Drop ( E) 0.12 0 SET-HMC-C@177CD 445 0 (E= I * R) 0 SET -HMC @135CD 318 0 EOL Voltage 20.28 0 SET -HMC @185CD 445 0 (20.4 - E) 0 Z-MC@15CD 64 0 0 Z-MC@30CD 98 0 0 SET-MC-CW@110CD 233 0 DEVICES= 2 TOTAL mA= 196 12 191 20.27870736) 1961 Notification Appliance Circuit Detail - PROJECT: WESTFIELD SOUTHCENTER MALL Panel: DAPHNES Wire Resistance 2.58 Date: June 10, 2008 CURRENT TOTAL 3.6 CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 70.7V 1/8 1.8 3.6 Total Wire Resistance (R) 0.99 0 0 0 (WL*2)*(R/ft) 0 0 0 Total Device Load, Amps (I) 0.00 0 0 0 (Total Cct Load) 0 0- 0 - Voltage Drop ( E) 0.00 0 0 0 (E=I*R) 0 0 0 EOL Voltage 20.40 0 0 0 (20.4 - E) 0 0 0 TOTAL mA= 3.6 14 191 20.396451981 3.61 DEVICES= 2 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS DATE 5/15/08 9 <«« 1 J03 00 CQ T C0) CC (� W O W W� Z 1 cc II Q Qco 0 tis 0 0D CDN w O w z w Cl) z 0 U 'GALE: 1 /8" = 1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: RISER DIAGRAM VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved .1013 NUMBER: SHEET k FA -04, ZONE T4 VICFNITY MAP-(Suite#2600) --- SCALE: NTS 2600 DAPHE'S General Notes 1. Western States Fire Protection to add new pendent heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only jn the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. `Without Comments As Noted In Red Per The Attached Letter in 3se plans have ti,,F..•.:ri revi,2.vad by Tie TtikVITlia Fire Pri-vention So; ..,a;.i.'or crohloi'ffiance v.ii;-.n CU rront city staidards. Aco.Ttncice i. !.._.i..iot to c:frors and orr ss.lons ‘,J:hich CO IRA iiiiI.XV-Iii.Z.E: violations of adapted sta -maids and Of ;P:'::::f.k:!•S.. -II 4'.. r.:1-':0(1•.;ibiA.!" for the adoquacy of d,-,.....-,1,.pit.&tot:ly with none designer. Additions; def,ons or 1-.,,yi:.ioilf'. I'u these dri.-.1wings atter this date will void tii•,:,.o..:ccpt:-,,noe nnd will iequire a res Jbmittal of rcuic,ed dra,,vings for subsequent approval. Final acceptance is subject to field test and inspectio TI -1 Tukwila Fire Prevention Bureau. IData: • By: issestrtne...zzottummettrateeneteesontirculetortY•masosimatetlfaxatr.• I wiLA FIRE DEPARTMENI Please call: 575-4407 and give this job znd exact address for shut' )t)k.vri or restoration approval; EAST RISER DETAIL DRAULIC REFERENCE ONLY NO TO SCALE title!d stamps must be inspaled before pipe is hung. Elp_oce paint piping prior to hydrostatic test ppproval. K L •-• • SYMBOL LEGEND REVISIONS 1 4 , ,., . . . . . . ...... Ordinary Group11.0.20gprnift2for 678.29ft2 —0 ---Existing Main ZONE T4 OPEN TO ROOF 115: Remote Area.... -1,•••• FIRE SPRINKLER_SYSTEM_ 1 6 Remote Area 2600 DAPHNE'S CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY CLASS ORD HAZARD 11 MAX. COVERAGE per HEAD 130 DENSITY .20 GPM 1 Ftfor 678.29 Ft' Ft' SPRINKLER Reliable FI FR Semi-Rec ORIFICE 1/2" K. 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 PSI GPM FLOW 10900 AT BASE OF RISER, SYSTEM REQUIRES: 303.17 GPM © 61.8 PSI ,t ,nt1C • At time of Design 17. 1 3 5_7 914 K L M N TYPICAL FLEXABLE SPRINKLER CONNECTION, FLEXHEAD MOUNTING BRACKET PIPE NIPPLE , • •:-•wor,•,* 4o:e4:4,1e,g," • ., SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS REDUCING FITTING • SUSPENDED T -BAR GRID • .*ON• ........ .... • italr4Voxili,,,t.ox...tirfah=tir.." • .. SPRINKLER -HEAD - CEILING Tlf.:E REM -MAD DETAIL NOT TO SCALE ////////////// //.,-(2,AMBLW.T.-D F00.900 SWIVEL SWAY BRACE FITTING BRACE PIPE 1000 FIG. • • • " s" INF 'FA BCRAIAMCEPATTACHMENT 0 lad) LINE PIPE LATERAL LINE RESTRAINTS NON -THREADED BRACE PIPE FIG. 4A PIPE CLAMP FOR SWAY BRACE 0, LATERAL BRANCHLINE RESTRAINT 3/B'' KWIK BOLT (21/4' EMBED LENGTH) FIG. 909 NO -THREAD SWIVEL SWAY DRAGS ATTAcHmENT NON -THREADED BRACE P(PE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE Hanger No. 07C HILTI Kwik Bolt 111 < / N / 1 \ HILTI Kwik Bolt Drilled Anchori / / Cut Rod Lgth Rounded to Nearest Inch Rod Coupling ----N., All Thread Rod Swivel Ring Pipe Concrete Construction Bottom of Concrete to Center Line of Pipe Note on Flan Note on Plan: Hanger Number and 7V Dimension HANGER DETAIL NOT TO SCALE FILE COPY VICINITY_MAP_DETAIL /11 "kw Sprinkler Legend 2 -WAY EARTHQUAKE BRACE NO. DESCRIPTION DATE SYM. SIN QTY. K SPRAY ORIF. FIN. TEMP. MFR./MODEL 4-WAYEARTHQUAKE BRACE R3615 13 5.6 Pendent 1/2, Chrome 155°F F1FR Semi- Rec APPROVAL: City of Tukwila HYDRAULIC REFERENCE POINT R5415 1 5.6 Pendent Brass 286°F F3QR Dry Pendent CONT. NO.: KS0427 Total = 14 DRAWN BY: Adam Kantner HANGER SYMBOL , . BRANCHLINE RESTRAINT SPRK ON SHEET: SEE LEGEND SPRK. ON JOB: DATE: 06/02/08 Western States Fire Protection Company 7102.180th AVE NE, STE A-105 - REDMOND, WA- 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPR'. OFFICES LOCATED ALBUQUERQUE/AUSTIN/DALLAS /DECATUR DENVER/ MUM/ HOUSTON 1 KANSAS CITY LAS VEGAS iNIIMEAPOUS /PHOENIX/PORTLAND/ RAPID CITY/ST. PAUL/SALT LAKE CITY/ SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 Daphe's 2600 Southcenter Mall fc---7 Tukwila ,Wa 98188 FIRE SPRINKLER SYSTEM (/) CL CO 0 w z • 8 Adam Kantner Western Construction Services 0 0 z S HE El FP -1 OF 1 2003 Tukwila Fire yjz ••••••"'" ------------- VICINITY MAP (Suite#2600) SCALE: NTS 2600 DAPHE'S General Notes 1. Western States Fire Protection to add new pendent heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existingfire sprinkler system to remain. Western States Fire Protection will modify the existing system only jnacwoes of work. All other areas are not in contract and WSFP is not responsible for EAST RISER DETAIL HYDRAULIC REFERENCE ON Y NOT TO SCALE 14 14 1 Ordinary Group II.0.20gpm,ft2 for 678.29ft2 A.F.F 11'-6" O4 N A.F.F 7'-0" 16 Existing Main ZONE T4 A.F.F 12'-4" HOOD ^i� F 15 A.F.F 8'-0" OPEN TO ROOF A.F.F 9'-0" COOLER Remote Area FIRE SPRINKLER SYSTEM 16 1/8"=11-0" Remote Area 2600 DAPHNE'S CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY CLASS ORD HAZARD II MAX. COVERAGE per HEAD 130 Ft' DENSITY .20 GPM ! Ft' for 678.29 Ft' SPRINKLER Reliable F1 FR Semi-Rec ORIFICE 1/2" K. 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 PSI FLOW 10900 GPM AT BASE OF . SYSTEM REQUIRES: 303.17 RISER. 61.8 PSI At time of Design 3 5 7 9 11 17 17 TYPICAL FLEXABLE SPRINKLER CONNECTION FLEXHEAD MOUNTING BRACKET PIPE NIPPLE • SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS REDUCING FITTING SUSPENDED T -BAR GRID SPRINKLER HEAD CEILING TILE FLEXHEAD DETAIL NOT TO SCALE ///////////��%���-(2,3/11' KWIK 4 EMBED LENG TH) FIG.909 SWIVEL SWAY BRACE FITTING \\\ BRACE PIPE FIG. 1000 "FAST CLAMP" SWAY BRACE ATTACHMENT LINE PIPE LATERAL LINE RESTRAINTS NON -THREADED BRACE PIPE 318' KWIK BOLT (2114- EMBED LENGTH) FIG. 909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT FIG. 4A PIPE CLAMP FOR SWAY BRACE �Frl1 LATERAL BRANCHLINE RESTRAINT 441 BRACE PIPE SZ... ..fl NON -THREADED BRACE PIPE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE Hanger No. 07C HILTI Kwik Bolt III N� -/ HILTI Kwlk Bolt II — D/lied Anc\ or 7 — i G 1. / ry Cut Rod Lgth Rounded to Nearest Inch Concrete Construction Bottom of Concrete to Center Line of Pipe Note on Plan Note on Plan: Hanger Number and 'A' Dimension HANGER DETAIL NOT TO SCALE VICE\ TY MAP DETAIL NOT TO SCALE J f fP 6 Q) 0 w. z 0 Adam Kantner D 0) a� m ru0 Western Construction Services CONTRACTOR: SYMBOL LEGEND REVISIONS Sprinkler Legend 2 -WAY EARTHQUAKE BRACE NO. DESCRIPTION DATE SYM. SIN QTY. K SPRAY ORIF. FIN. TEMP. MFR./MODEL 4 -WAY EARTHQUAKE BRACE R3615 13 5.6 Pendent „ 2� Chrome 155°F F1 FR Semi- Rec APPROVAL: City of Tukwila HYDRAULIC REFERENCE POINT R5415 1 5.6 Pendent Brass 286°F F3QR Dry Pendent CONT. NO.: KS0427 Total = 14 DRAWN BY: Adam Kantner HANGER SYMBOL BRANCHLINE RESTRAINT SPRK. ON SHEET: SEE LEGEND SPRK. ON JOB: DATE: 06/19/08 Western States Fire Protection Company 7102 180th AVE NE, STE A-105 - REDMOND, WA - 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY -OFFICES LOCATED ALBUOUEROUE /AUSTIN ! DALLAS /DECATUR /DENVER /DULUTH I HOUSTON /KANSAS CITY LAS VEGAS /MINNEAPOLIS /PHOENIX/ PORTLAND / RAPID CIN/ ST. PAUL I SALT LAKE CITY /SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 Daphe's 2600 Southcenter Mall Tukwila ,Wa 98188 FIRE SPRINKLER SYSTEM SHEET FP -1 OF 1 2600 SOUTHCENTER MALL FC -7 FOOD COURT ASSOCIATED PERMITS 08-F-318 08-S-285 10-H-144 08-H-324 FILE COPY FIRE DEPARTMENT HOOD SUPPRESSION PLAN REVIEW COMMENTS Project Name: Daphne's Greek Cafe 2600 Southcenter Mall FC -7 Permit No.: 08-H-324 Date: June 12, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Nozzle heights above appliances to be per manufacturers installation guidelines. • Install splash guards between fryers and ranges/charbroilers. • Upon activation of the suppression system, the make-up air supply will shut off and the exhaust will keep running. • Type 1 hood systems shall be designed and installed to automatically activate the exhaust fan whenever cooking operations occur. The activation of the exhaust fan shall occur through an interlock with the cooking appliances, by means of heat sensors or by means of other approved methods. • Activation of the suppression system shall shunt all electrical power under the hood as well as the gas supply. • Install a "K" rated portable fire extinguisher within 30 ft. of the cooking equipment. • The hood suppression system shall be monitored by a U.L. Central Monitoring Station. FIRE DEPARTMENT HOOD SUPPRESSION PLAN REVIEW COMMENTS Project Name: Indibite 2600 Southcenter Mall, FC -0 7 Permit No.: 10-H-144 Date: July 19, 2010 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Nozzle heights above appliances to be per manufacturers installation guidelines. • Fryers shall be installed with at least a 16 inch space between the fryer and surface flames from adjacent cooking equipment or a minimum 8 inch high steel or tempered glass baffle plate shall be installed between the appliances. • Upon activation of the suppression system, the make-up air supply will shut off and the exhaust will keep running. • Type 1 hood systems shall be designed and installed to automatically activate the exhaust fan whenever cooking operations occur. The activation of the exhaust fan shall occur through an interlock with the cooking appliances, by means of heat sensors or by means of other approved methods. • Activation of the suppression system shall shunt all electrical power under the hood as well as the gas supply. • Install a "K" rated portable fire extinguisher within 30 ft. of the cooking equipment. • The hood suppression system shall be monitored by a U.L. Central Monitoring Station. • The suppression system manual pull station shall be located no closer that 10 ft. and no farther than 20 ft. from the cooking equipment and be placed at a height of 42 to 48 inches above the floor. • The inside lower edge of the hood shall overhang or extend a horizontal distance of not less than 6 inches beyond the edge of the top horizontal surface of the appliance on all open sides. The vertical distance between the front lower lip of the hood and such surface shall not exceed 4 feet. FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Daphne's 2600 Southcenter Mall FC -7 Permit No.: 08-S-285 Date: June 5, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 % inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • These conditions apply to any sprinkler piping exposed as necessary to accomplish the permitted scope of work. All references are NFPA 13, 2007 Edition. ilHyd ra Iic Summary - Job Number: KS0427 Report Description: Ordinary Group II Job Job Number Design Engineer KS0427 Adam Kanter Job Name State Certification/License Number Daphe's WESTESF136QF Address 1 Al-IJ 2600 Southcenter Mall City of Tukwila Address 2 Job Site Southcenter Mall City State Zip Code Drawing Name Tukwila Wa 98188 FP-1.cad System Remote Area(s) Most Demanding Sprinkler Data Occupancy 5.6 K-Factor 20.00 at 12.755 Ordinary Group II Hose Allowance At Source Density Area of Application 250.00 0.20gpm/ft2 678.29ft2 (Actual 678.29ft2) Additional Hose Supplies Number Of Sprinklers Calculated Coverage Per Sprinkler Node Flow(opm) 13 100.00ft2 Total Hose Streams 250.00 System Flow Demand Total Water Required (Including Hose Allowance) � 41 303.17 : 553.17 . !.11407, Maximum Pressure Unbalance In Loops\/ 0.000 11 �3':, likki._ .ii Maximum Velocity Above Ground 23.77 between nodes 87 and 105 , Vhf 3 lo p Maximum Velocity Under Ground 4*. 1.15 between nodes 1 and 279 Volume capacity of Wet Pipes I Volume capacity of Dry Pipes I 2023.06gal 1.22ft3 Supplies Hose Flow Static Residual pe Flow Available Total Demand Required Safety Margin Node (gpm) (psi) (psi) (gpm) (psi) (gpm) (psi) (psi) 1 250.00 140.000 20.000 10900.00 139.517 553.17 65.256 74.261 Contractor Contractor Number Contact Name Contact Title KS0427 Adam Kantner Project Manager Contractor Name Phone Extension Western States Fire Protection 425.881.0100 Address 1 FAX 7102 180th Ave Ne, Suite A-105 485.736.9032 Address 2 E-mail City State Zip Code Web-Site Redmond WA 98052 ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 06/02/2008 11:55:45AM Page 1 11.1.- Summary Of Outflowing Devices mber: 427 1Report Description:b Oudinary Gro pp H Actual Flow Minimum Flow K -Factor Pressure Device (gpm) (gpm) (K) (psi) Sprinkler 116 26.66 20.00 5.6 22.658 Sprinkler 117 27.30 20.00 5.6 23.769 Sprinkler 115 25.35 20.00 5.6 20.486 Sprinkler 108 23.52 20.00 5.6 17.644 Sprinkler 109 23.88 20.00 5.6 18.178 Sprinkler 107 22.55 20.00 5.6 16.218 Sprinkler 114 24.34 20.00 5.6 18.898 Sprinkler 106 20.63 20.00 5.6 13.573 Sprinkler 110 24.33 20.00 5.6 18.883 Sprinkler 103 20.18 20.00 5.6 12.992 14> Sprinkler 101 20.00 20.00 5.6 12.755 Sprinkler 111 24.34 20.00 5.6 18.896 Sprinkler 102 20.08 20.00 5.6 12.856 c> Most Demanding Sprinkler Data ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 06/02/2008 11:55:49AM Page 2 Node Analysis Job Number: KS0427 Report Description: Ordinary Group II Node Elevation(Foot) Fittings Pressure(psi) Discharge(gpm) 86 13-6 PO(5-0) 32.015 87 13-6 PO(8-0) 31.046 90 13-6 PO(5-0) 30.800 91 13-6 PO(8-0) 30.734 44.492 97 1-6 104 14-1 P0(5-0) 27.226 105 14-1 P0(5-0) 23.508 112 14-1 P0(5-0) 21.891 113 14-1 P0(5-0) 20.498 120 14-1 P0(5-0) 25.098 17.693 127 14-1 LtE(2-5%) 130 14-1 LtE(2-5%) 24.373 135 14-1 P0(5-0) 16.547 139 14-1 P0(5-0) 23.755 15.811 15.438 142 14-1 P0(5-0) 169 14-1 P0(5-0) 240 14-1 E(2-0) -14-1 PO(5-0), PO(26-4) 23.452 58.096 61.802 15.343 271 279 -12-1% BF (4.500) _ 303 14-1 E(2-0) -14-1 LtE(16-0) 319 58.114 116 11-6% Spr(-22.658) 22.658 26.66 117 11-6'/2 Spr(-23.769) 23.769 27.30 115 11-6'/2 Spr(-20.486) 20.486 25.35 108 8-0V2 Spr(-17.644) 17.644 18.178 16.218 _ 23.52 109 7-0 Spr(-18.178) 23.88 107 8-0 Spr(-16.218) 22.55 114 11-6% Spry -18.898) 18.898 13.573 24.34: 20.63 106 9-0 Spr(-13.573) 9-0 Spr(-18.883) 110 18.883 24.33 103 9-0 Spr(-12.992) 12.992 20.18 ' 101 9-0 Spr(-12.755) 12.755 18.896 , 20.00 111 9-0 ; SK 18.896) 24.34 102 9-0 ' Spr(-12.856) 12.856 65.256 20.008 1 -20-0 1 S 303.17 D(/� ©M.E.P.CAD, Inc. 411 AutoSPRINK® VR5 v5.2.6 06/02/2008 11:55:53AM Page 3 899 Hydraulic Analysis 1 Job Number: KS0427 Report Description: Ordinary Group 11 Pipe Type Diameter Elevation Flow Discharge Velocity K -Factor HWC Pt Friction Loss Length Pressure Pn Fittings Eq. Length Summary Total Length Downstream Upstream v Route 1 DR 1.049 Q=20.00 7.42 C=120 0.130131 28-61/2 Pf 4.885 101 9-0 q=20.00 K=5.6 12.755 Spr(-12.755) 9-0 Pe -2.202 169 14-1 15.438 2E(2-0), PO(5-0) 37-61/2 Pv BL 1.682 Q=40.08 5.79 C=120 0.047236 7-101/2 Pf 0.373 169 14-1 15.438 Pe 142 14-1 15.811 7-10% Pv BL 1.682 Q=60.26 8.70 C=120 0.100457 7-4 Pf 0.735 142 14-1 15.811 Pe 135 14-1 16.547 7-4 Pv BL 1.682 Q=80.89 11.68 C=120 0.173195 4-1% Pf 1.146 135 14-1 16.547 2-5% Pe 127 14-1 17.693 LtE(2-5%) 6-7'/z Pv BL 1.610 Q=80.89 12.75 C=120 0.214321 7-1 Pf 2.805 127 14-1 17.693 6-0 Pe -0.000 113 14-1 20.498 3LtE(2-0) 13-1 Pv BL 1.610 Q=103.45 16.30 C=120 0.337786 4-1% Pf 1.394 113 14-1 20.498 Pe 112 14-1 21.891 4-11/2 Pv BL 1.610 Q=126.97 20.01 C=120 0.493465 3-31/2 Pf 1.616 112 14-1 21.891 Pe -0.000 105 14-1 23.508 3-3'% Pv BL 1.610 Q=150.85 23.77 C=120 0.678729 0-8% Pf 7.278 105 14-1 23.508 10-0, Pe 0.260 87 13-6 31.046 LtE(2-0), PO(8-0) 10-8V2 Pv CM 2.635 Q=275.87 16.23 C=120 0.188259 5-2 Pf 0.969 87 13-6 31.046 Pe 86 13-6 32.015 5-2. Pv CM 2.635 Q=303.17 17.84 C=120 0.224169 14-1'/z Pf 7.271 86 13-6 32.015 18-31/2 Pe 5.206 97 1-6 44.492 fE(4-3%), 2fEE(2-2%), BV(9-7%) 32-5 Pv CM 4.260 Q=303.17 6.82 C=120 0.021605 179-4 Pf 6.852 97 1-6 44.492 137-9% Pe 6.752 271 -14-1 58.096 4fE(6-9%), 3P0(26-4), 317-2 Pv CV(28-11'/2), GV(2-7%) FM 8.329 Q=303.1.7 1.79 C=120 0.000825 5-7 Pf 0.018 271 -14-1 58.096 16-0 Pe -0.000 319 -14-1 58.114 LtE(16-0) 21-7. Pv FM 10.420 Q=303.17 1.14 C=120 0.000277 26-51/2 Pf 4.530 319 -14-1 58.114 83-0 Pe -0.842 279 -12-1% 61.802 4LtE(16-0), BV(19-0), BFP(-4.500) 109-5'/2 Pv UG 10.400 Q=303.17 1.15 C=140 0.000210 109-2 Pf 0.046 279 L12-1% 61.802 111-7i Pe 3.407 1 -20-0 65.256 E(35-1), 3LtE(25-6), S 220-9% Pv ai Route 2 DR 1.049 Q=20.08 7.45 C=120 0.131082 29-9 Pf 4.689 102 9-0 q=20.08 K=5.6 12.856 Spr(-12.856) 6-0, Pe -2.202 303 14-1 15.343 3E(2-0) 35-9' Pv BL 1.682 Q=20.08 2.90 C=120 0.013151 7-3' Pf 0.095 303 14-1 15.343 Pe 169 14-1 15.438 7-3 Pv • Route 3 DR 1.049 Q=20.18 7.49 C=120 0.132361 28-11' Pf 5.021 103 9-0 q=20.18 K=5.6 12.992 Spr(-12.992) 9-0 Pe -2.202 142 14-1 15.811 2E(2-0), PO(5-0) 37-11 Pv v Route 4 DR 1.049 Q=20.63 7.66 C=120 0.137835 28-61/2 Pf 5.175 106 9-0 q=20.63 K=5.6 13.573 Spr(-13.573) 9-0 Pe -2.202 135 14-1 16.547 2E(2-0), PO(5-0) 37-61/2 Pv v Route 5 DR 1.049 Q=22.55 8.37 C=120 0.162511 31-6'/z Pf 6.914 107 8-0 q=22.55 K=5.6 16.218 Spr(-16.218) 11-0. Pe -2.635 113 14-1 20.498 3E(2-0), PO(5-0) 42-6'/z Pv Route 6 DR 1.049 Q=23.52 8.73 C=120 0.175678 30-2 Pf 6.883 108 8-0% q=23.52 K=5.6 17.644 Spr(-17.644) 9-0 Pe -2.635 112 14-1 21.891 2E(2-0), PO(5-0) 39-2 Pv v Route 7 DR 1.049 Q=23.88 8.86 C=120 0.180593 35-6 Pf 8.398 109 7-0 q=23.88 K=5.6 18.178 Spr(-18.178) 11-0 Pe -3.069 105 14-1 23.508 3E(2-0), PO(5-0) 46-6 Pv Route 8 ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 06/02/2008 11:55:57AM Page 4 111 Hydraulic Analysis Pipe Type Diameter Flow Job Number: KS0427 Report. Description: Ordinary Group II Velocity HWC Friction Loss Downstream Upstream DR Elevation Discharge K -Factor Pt Fittings Length Pressure Eq. Length Summary Total Length 1.049 Q=24.33 9.03 C=120 0.187064 110 9-0 q=24.33 K=5.6 139 14-1 18.883 23.755 Spr(-18.883) 2E(2-0), PO(5-0) 28-10 Pf 7.073 9-0 Pe -2.202 37-10 Pv BL 1.682 Q=48.68 7.03 C=120 0.067677 139 14-1 130 14-1 23.755 24.373 LtE(2-51/2) 6-8 Pf 0.618 2-5% Pe 9-1% Pv BL 1.610 Q=48.68 7.67 130 14-1 120 14-1 C=120 0.083747 24.373 25.098 3LtE(2-0) 2-8 Pf 0.725 6-0 Pe 8-8 Pv BL 1.610 Q=73.02 11.51 C=120 0.177336 120 14-1 104 14-1 25.098 27.226 12-0 Pf 2.128 Pe -0.000 12-0, Pv BL 104 91 1.610 14-1 13-6 Q=98.37 15.50 C=120 0.307746 27.226 30.734 LtE(2-0), PO(8-0) 0-61/2 Pf 3.249 10-0 Pe 0.260 10-6% Pv CM 2.635 Q=98.37 5.79 91 13-6 90 13-6 C=120 30.734 30.800 0.027940 2-4% Pf 0.066 Pe 2-4% Pv CM 2.635 Q=125.02 7.36 C=120 0.043540 90 13-6 87 13-6 30.800 31.046 5-7'/z Pf 0.245 Pe 5-7% Pv .i Route 9 DR 1.049 Q=24.34 9.04 111 9-0 q=24.34 K=5.6 240 14-1 C=120 18.896 23.452 0.187185 Spr(-18.896) 3E(2-0) 30-1, Pf 6.758 6-0 Pe -2.202 36-1 Pv BL 240 139 1.682 14-1 14-1 Q=24.34 3.51 C=120 0.018779 23.452 23.755 16-11/2 Pf 0.303 Pe 16-1'/z Pv GO Route 10 DR 1.049 Q=24.34 9.04 114 11-6% q=24.34 K=5.6 120 14-1 C=120 18.898 25.098 0.187198 Spr(-18.898) 3E(2-0), PO(5-0) 28-1Pf 7.318 11-0 Pe -1.118 39-1 Pv • Route 11 DR 115 104 1.049 11-6% 14-1 Q=25.35 9.41 C=120 0.201710 q=25.35 K=5.6 20.486 27.226 Spr(-20.486) 3E(2-0), PO(5-0) 27-11% Pf 7.858 11-0 Pe -1.118 38-11 % Pv ✓ Route 12 DR 1.049 Q=26.66 9.90 116 11-6% q=26.66 K=5.6 90 13-6 C=120 22.658 30.800 0.221415 Spr(-22.658) 3E(2-0), PO(5-0) 29-8, Pf 9.000 11-0 Pe -0.858 40-8 Pv .O Route 13 DR 1.049 Q=27.30 10.14 C=120 0.231437 117 11-6% q=27.30 K=5.6 86 13-6 23.769 32.015 Spr(-23.769) 3E(2-0), PO(5-0) 28-4 Pf 9.104 11-0 Pe -0.858 39-4 Pv Equivalent Pipe Lengths of Valves and Fittings (C=120 only) Actual Inside Diameter Schedule 40 Steel Pipe Inside Diameter 4.87 = Factor C Value Multiplier 1 Value Of C 100 Multiplying Factor 0.713 130 140 150 1.16 1.33 1.51 © M.E.P.CAD, Inc. 41AutoSPRINK® VR5 v5.2.6 06/02/2008 11:55:57AM Page 5 Hydraulic Analysis Pipe Type Downstream Upstream Diameter Elevation Flow Discharge Job Number: KS0427 Report Description: Ordinary Group II Velocity HWC Friction Loss K -Factor Pt Pn Fittings Length Pressure Eq. Length Summary Total Length Pipe Type Legend Units Legend Fittings Legend AO Arm -Over Diameter BL Branch Line Elevation CM Cross Main Flow DN Drain Discharge DR Drop Velocity DY Dynamic Pressure FM Feed Main Length FR Feed Riser Friction Loss MS Miscellaneous HWC OR Outrigger Pt RN Riser Nipple Pn SP Sprig Pt ST Stand Pipe Pe UG Underground Pv Inch Foot gpm gpm fps psi Foot psi/Foot Hazen -Williams Constant Total pressure at a point in a pipe Normal pressure at a point in a pipe Pressure loss due to friction between points Pressure due to elevation difference between indicated points Velocity pressure at a point in a pipe ALV Alarm Valve AngV Angle Valve b Bushing BaIV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Turn 90° cplg Coupling Cr Cross Run CV Check Valve DeIV Deluge Valve DPV Dry Pipe Valve E 90° Elbow EE 45° Elbow Eel 11% Elbow Ee2 221/0 Elbow f Flow Device FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow flg Flange FN Floating Node fT FireLock(TM) Tee g Gauge GIoV Globe Valve GV Gate Valve Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PrV Pressure Relief Valve PRV Pressure Reducing Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap (A� ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 06/02/2008 11: 55: 57AM Page 6 • Hydraulic Graph Job Number: KS0427 Report Description: Ordinary Group II Supply at Node 1 150 Static Pressure 140.000 135 120 105 • 90 .N o. s 75 N co N o_ „553.17 2303.17 with hose @ 65.256 streams 60 45 =System J demand curve 30 10900.00 @ 20.000_ 15 I1111IIII III1111II 1 1 1 1111 11 11 I 1 f 1 I (I 111111111 111111111 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 I 1 1 0 110022 3300 4400 5500 6600 7700 8800 9900 11000 Water flow, gpm Hydraulic Graph Supply at Node 1 Static Pressure 140.000 Residual Pressure 10900.00 © 20.000 Available PressureTIme of Test 139.517 © 553.17 System Demand 303.17 @ 65.256 System Demand (Including Hose Allowance) 553.17 © 65.256 ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 06/02/2008 11:56:06AM Page 7 lid Flow Diagram (Top View) 1 Job Number: KS0427 Report Description: Ordinary Group II %©M.E.P.CA D, Inc. JAutoSPRINK® VR5 v5.2.6 06/02/2008 11:56:10AM Page 8 i •,-1 %.1 [.vvv 11:11 /Art .IWIXOJd 481H Q JeH0003 soJAD I WX ifa Q JaHoo3X saKDBi o`i4 Q otax 004,pjvo*wit S -aa .k4 A}1611xoJd 48IH i p, off diiea ,* S� a1Cj� ]NIdId Q13Id DNIdId A21010dd JC 4 N L r.) I w I 0 L 0 1'1 COgo- Received Time May.30, 8:07AM Page: 4 0 • r ° L. L_ to a i13 3 x ru 2 co lawoN qor 10L I Z c. r S. c r- 14)0 / QV/ L.VVO 11:11 Ari Page: 3 Nola - Fire Systems - Parts List Report 5/28/08 12:00 PM' Fire System Parts List Job # 776631 - Daphne's - Seattle, WA Location: Seattle, WA Fire System # 1 Ansul R102 Hoods Covered: Hood # 1 Gas Valve(s): ANSUL-3.0/3.0- MANIFOLD Tag: Supplied by Ship Qty Item CAS # Vendor # Description MA CAS Inst Loose 2 1 AT - 3.0 AT - 3.0 TANK(#1 B) - 3.0 Gallon SS Tank (for use with 2 0 Automan Release, Actuator, or SS Enclosure (UL)) 1 2 AP - AR AP - AR AUTOMAN RELEASE - Ansul Automan 1 0 Mechanical Release (UL) Tank sold separately 1 3 AP - AE AP - AE ENCLOSURE - Stainless Steel Enclosure 1 0 Assembly (UL) 2 5 LIQ -3.0 79372 AGENT - Ansulex Low PH Wet Chemical Agent, 3 2 0 Gallon (UL) 1 9 DT -CART 73022 Double Tank Nitrogen Cartridge 1 0 1 10 TLINK TLINK LINK - Test Link Package 1 0 1 11 MICRO -SD MICRO -SD MICROSWITCH - Single Dual Electric Switch 1 0 1 12 HOSEGROMMET 418511 HOSE - Hose/Grommet Package 1 0 1 13 419337 419337 NOZZLE -2W Nozzle, Duct 0 1 4 16 419335 419335 NOZZLE - 1N Nozzle, Plenum/Appliance 0 4 2 20 419340 419340 NOZZLE - 245 Nozzle, Appliance 0 2 2 21 419339 419339 NOZZLE - 230 Nozzle, Appliance 0 2 2 25 418569 418569 NOZZLE ADAPTOR - Swivel Nozzle Adaptor 0 2 9 26 QSA-3/8 QSA-3/8 QUIK SEAL - 318" (UL) 0 9 1 27 QPSA-1/2 QPSA-1/2 PULLEY SEAL- 1/2" Hood Seal (UL) 0 1 5 28 S -DET S -DET DETECTOR -Series (Scissor Linkage) 0 5 2 29 ANS-360FL ANS-360FL FUSIBLE LINK - 360deg F, R-102 and PIRANHA 0 2 3 30 ANS-500FL ANS-500FL FUSIBLE LINK - 500deg F, R-102 and PIRANHA 0 3 1 34 RPS -A RPS -A REMOTE PULL STATION -Aluminum (without 1 0 wire rope) 10 35 PE -LT PE -LT PULLEY ELBOW - Low Temp. Pulley Elbow, Set 10 0 Screw Type 1 36 PE -HT PE -HT PULLEY ELBOW - High Temp Pulley Elbow, 0 1 Compression Type 2 41 SN -CHAR SN -CHAR SINGLE NOZZLE EXTENDED DROP ASSY 0 2 Oa http://appl.captiveaire.com/Order/FireSystems/PartsListReport.aspx?JobFireSystemid=169916 Page 1 of 1 Received Time May, 30, 8:07AM SECTION IV — SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-28 REV.5 4-1-06 Nozzle Application Chart The following chart has been developed to assist in calculating the quantity and type of nozzle required to protect each duct, plenum, or appliance. . NOTICE This chart is for general reference only. See complete details for each type of hazard. Hazard ► Duct or Transition (Single Nozzle) Duct or Transition (Single Nozzle) Duct or Transition (Dual Nozzle) Electrostatic Precipitator (At Base of Duct) Plenum (Horizontal Protection) ► Plenum (Horizontal Protection) Plenum (Vertical Protection) ► Fryer (Split or Non -Split Vat) Fryer (Split or Non -Split Vat) Fryer (Split or Non -Split Vat)* Fryer (Non -Split Vat Only) Maximum Hazard Dimensions Length — Unlimited Perimeter — 50 in. (127 cm) Diameter —16 in. (40.6 cm) Length — Unlimited Perimeter —100 in. (254 cm) Diameter — 31 7/8 in. (81 cm) Length — Unlimited Perimeter -150 in. (381 cm) Diameter — 48 in. (122 cm) Individual Cell Length —10 ft. (3.1 m) Length — 6 ft. (1.8 m) Width — 4 ft. (1.2 m) Length — 4 ft. (1.2 m) Width — 4 ft. (1.2 m) Maximum Size (without drip board) 14 in. (36 cm) x 15 in. (38 cm) Low Proximity Maximum Size (without drip board) 141/2 in. (37 cm) x 14 in. (36 cm) Medium Proximity Maximum Size (without drip board) 15 in. (38 cm) x 14 in. (36 cm) High Proximity Medium Proximity Maximum Size (without drip board) 19 1/2 in. (49.5 cm) x 19 in. (48.2 cm) High Proximity Low Proximity Maximum Size (without drip board) 18 in. (45:7. cm) x 18 in. (45.7 cm) High Proximity Minimum Nozzle Nozzle Quantity Heights 1 1 1 1 1 1 1 1 1 For multiple nozzle protection of single fryers, see detailed information on Pages 4-12 through 4-14. 13 — 16 in. (33 — 41 cm) 16 — 27 in. (41 - 69 cm) 27 — 47 in. 20 — 27 in. 21 — 34 in. 13-16 in. 25 — 35 in. (64-89 cm) Nozzle Part No. 430912 419337 419337 419334 419335 430192 419336 419336 419342 419342 419339 419340 419338 419342 419338 Nozzle Tip Stamping — Flow No. 1W 2W 2W 1 /2N 1N 1W 1W 1W 290 290 230 245 3N 290 3N Nozzle Application Chart (Continued) Hazard Fryer (Non -Split Vat Only)` Fryer (Split or Non -Split Vat) Fryer (Split or Non -Split Vat) Range Maximum Hazard Dimensions Maximum Size (with drip board) 21 in: (53 cm) x 14 in. (36 cm). (Fry Pot must not exceed 15 in. x 14 in: (38 cm x 36 cm)) High Proximity Medium Proximity Maximum Size (with drip board) 25 3/8 in. (64.4 cm) x 19 1/2 in: (49.5 cm) (Fry pot side must not exceed 19 1/2 in. (49.5 cm) x 19 in. (48.2 cm) High Proximity . Low Proximity Maximum Size (with drip board) 18 in. (45.7 cm) x 27 3/4 in. (70.5 cm) High Proximity Minimum Nozzle Nozzle Quantity Heights 1 Maximum Size (with drip board) 14 in. (36 cm) x 21 in. (53 cm) Low Proximity Maximum Size (with drip board) 141/2in. (37cm) x 261/2 in. (67 cm) Medium Proximity Longest Side 1 32 in. (81 cm) Area — 384 sq. in. _ (2477 sq. cm) Longest Side 28 in. (71 cm) Area — 336 sq. in. (2168 sq. cm) Longest Side (High Proximity) 1 28 in. (71 cm) Area — 672 sq. in. (4335 sq. cm) Longest Side (Medium Proximity) 1 32 in. (81 cm) Area -768 sq. in. (4955 sq. cm) Longest Side (Low Proximity) 2 36 in. (91 cm) Area —1008 .sq. in. (6503 sq. cm) For multiple nozzle protection of single fryers, see detailed. information on Pages 4-7 through 4-11. SECTION IV - SYSTEM DESIGN UL EX; 3470 ULC CEx747 Page 4-29 4-1-06 REV 27 — 47 in. 20 — 27 in. 21 —34 in. 13-16 in. 25 — 35 in. (64-89 cm) 13 —16 in: (33 —41 cm) 16 — 27 in. (41 — 69 cm) 30 — 40 in. (76 -102 cm) 40 — 48 in. (102 —122 cm) (With Backshelf) 40— 50 in. (102 — 127 cm) 30 — 40 in. (76 —102 cm) 15 — 20 in. (38 — 51 cm) Nozzle Part No. 419339 419340 419338 419342 419338 419342 419342 419335 419333 419340 419341 419342 Nozzle Tip Stamping — Flow No. 230 245 3N 290 3N 290 290 1N 1F 245 260 290 SECTION IV - SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-30 REV. 3 10-1-02 Nozzle Application Chart (Continued) Hazard Griddle Chain Broiler* (Overhead Protection) Chain Broiler (Horizontal Protection) Gas -Radiant Char -Broiler Electric Char -Broiler Lava -Rock Broiler Natural Charcoal Broiler Lava -Rock or Natural Charcoal Char -Broiler Maximum Hazard Dimensions Longest Side (High Proximity) 48 in. (122 cm) Area – 1440 sq. in. (9290 sq. cm) Longest Side (High Proximity) 1 30 in. (76 cm) Area – 720 sq. in. (4645 sq. cm) Longest Side (High Proximity) 1 36 in. (91 cm) Area –1080 sq. in. (6968 sq. cm) Longest Side (Medium Proximity) 48 in. (122 cm) Area –1440 sq. in. (9290 sq. cm) Longest Side (Low Proximity) 1 48 in. (122 cm) Area – 1440 sq. in. (9290 sq. cm) Longest Side – 34 in. (86 cm) 2 Area –1088 sq. in. (7019 sq. cm) Length – 43 in. (109 cm) Width – 31 in. (79 cm) Longest Side – 36 in. (91 cm) Area – 864 sq. in. (5574 sq. cm) Longest Side – 34 in. (86 cm) Area – 680 sq. in. (4383 sq. cm) Longest Side 24 in. (61 cm) Area – 312 sq. in. (2013 sq. cm) Longest Side – 24 in. (61 cm) Area – 288 sq. in. (1858 sq. cm) Longest Side – 30 in. (76 cm) Area – 720 sq. in. (4645 sq. cm) Minimum Nozzle Quantity 1 1 2 1 Nozzle Heights 30 – 50 in. (76 – 127 cm) (perimeter located) 30 – 50 in. (76 –127 cm) (center located) 35 — 40 in. (89 –102 cm) (perimeter located) 20 – 30 in. (51 – 76 cm) (perimeter located) 10 – 20 in. (25 – 51 cm) (perimeter located) 10 – 26 in. (25 – 66 cm) 1 – 3 in. (3 – 8 cm) 15 – 40 in. (38 –102 cm) 20 – 50 in. (51 – 127 cm) 18 – 35 in. (46 – 89 cm) 18 – 40 in. (46 –102 cm) 14-40 in. (36 –102 cm) • Minimum chain broiler exhaust opening — 12 in. x 12 in. (31 cm x 31 cm), and not less than 60% of internal broiler size. Nozzle Part No. 419341 Nozzle Tip Stamping – Flow No. 260 419342 290 419335/417332 1N/1NSS 419342 290 419343 419336/417333 419335/417332 419335/417332 419335/417332 419335/417332 419335/417332 419338 2120 1 W/1 WSS 1N/1NSS 1N/1NSS 1N/1NSS 1N/1NSS 1N/1NSS 3N .J vir11v necauizieo mecii JIiL .I ,- eiease Assembly (3.0 gallon — Part No. 79290 cr 1.5 gallon — Par, No. 79291) contains the regulated release mechanism, agent tank. expellant gas hose for agent tank hookup. and enclosure knockouts to facilitate installing actuation, piping; expellaru piping; detection system: and additional equipment. This regu- lated release assembly is used in single, double, and multiple - tank systems and must be mounted to a rigid -surface. The release mechanism can be used to interconnect both the actu- ation and expellant gas lines as required per system design. The regulator is designed to allow a constant flow of gas into the tank at 100 psi (690 kPa) when the system is actuated. • In single, double, and multiple -tank systems, the provided expel- lant gas hose connects the aoent tank to the bottom outlet of the regulator. In double and multiple -tank system configurations, the back outlet of the regulator is used as an expellant gas feed for one additional tank -enclosure or tank -bracket hookup. The enclosure contains the required knockouts to facilitate this con- nection. If a pressure switch is to be attached to the regulator, additional fittings are required. . The tank is mounted within the enclosure. The tank contains an adaptor/tube assembly with a burst disc union. The burst disc helps prevent siphoning of the agent up the pipe due to signifi• - cant temperature fluctuations in the area where the • tank is located. The tank is mild steel and, under normal conditions, requires hydrostatic testing every twelve years. - The agent tank is shipped 'uncharged and must be -filled with 1.53 cations (5.6 L) or 3.06 gallons (11.6 L) of only ANSULEX Low pH Liquid Fire Suppressant during installation.. The detection and additional equipment required:per -system design are connected to'the release mechanism. The enclosure contains knockouts to facilitate detection and additional hookups. The system can b•?, actuated automatically, or manually. Auto-" uratic actuation occurs when a fusible link within the detection system separates in a fire condition. Manual actuation of the system occurs when personnel pull on the remote manual pull station pull ring. EXT;NGUISHING AGENT ANSULEX Low pH Liquid Fire Suppressant (1.5 gallon Part No. 79694 or 3.0 gallon — Part No. 79372) is apotassium-based - solution designed for fast knock -down and suppression of grease -related fires. The agent is shipped in plasticcbntaihers which provide one complete tank charge. Agent storage life expectancy is twelve years. The distributor mtist.record the batch numbers and date of shipment receipt to be filed with each instal- lation record. ANSUL, • • ! Total Tank Type of Flow No. Quantity System - - Type of Hardware 1-5 1 Single 1.5 Gal. Reg. Release 6-11 - 1 Single 3.0 Gal. Reg. Release ELECTRICAL SWITCHES — 1_0 fE3 E F The electrical switches are intended for .use with electric gas valves, alarms, contactors, lights, contractor- supplied electric power shut-off devices :and other elect cal devices that are designed to shut off or tum on when the system is actuated. Switches are available in kits: One Switch Kit, Part No: 423878, Two Switch Kit, Part No. 423879, Three Switch Kit,' Part No. 423880, anti Four Switch Kt, Part No. 423881. Each switch has a set of single -pole, double=throw contacts rated at 21 amp, 1 HP, 125, 250, 277 VAC or 2 HP, 250, 277 VAC. Mounting hardware is provided with each kit. R-102 RESTAURANT FIRE SUPPRESSION SYSTEM (Standard UL 300 Listed) Nozzle Identification Chart Nozzle Nozzle Nozzle .Type Part No. - Stamoino 1W Nozzle 419336 1W 1 1WSS Nozzle 417333 1W 1 1N Nozzle 419335 1N 1 NSS Nozzle 417332 1N 1/2N Nozzle 419334 1/2N 3N Nozzle 419338 3N 2W Nozzle 419337 2W 2WH Nozzle 78078 2WH Noz Flov 230 Nole 245 Nozzle 260 Nozzle 290 Nozzle 2120 Nozzle 1F Nozzle 1D0 i407.7.tr Nitrogen Cartridoe Reouired LT -20-R (7032) LT -30-R (5373) 419339 419340 419341 419342 419343 419333 430712 230 245 260 290 2120 1F i1pc, Carbon Dioxide Cartridoe Required 101-10 (15850) 101-20 (17492) Wit%�` 1 f;'J5t 5►S 0i\\ S\J -P 1 kik SAkiT5 O ? (purL. -S) 14,561) 514 c IF Pi -LAP -m.5-0, SicIPIL . Is 5s 1 1 1/2 3 2 2 2 2 2 2 2 1 SECTION IX - APPENDIX • UL EX. 3470 ULC CEx747 Page 9-1 7-1-98 REV. 3 SYSTEM SELECTION GUIDE NOTE: System options do not cover all conceivable variations. They are listed here as a general guideline to show the most common type arrangement for multiple systems, Based on certain system designs utilizing manifolding, non-manifolding, 3 -tank systems, etc., other tank/cartridge combinations can be designed. The combinations below are based on 11 flow, 3.0 gallon tanks and 5 • flow, 1.5 gallon tanks. More competitive designs may be available by utilizing 12 flow and 6 flow systems when appropriate. • Nitrogen Cartridge Required Total Flow No.* Tank Quantity Type of System Single Type of Hardware 1-5 6-11 12-16 17-22 23-27 28-33 28-33 3.0 Gal. Reg. Release (Optional) (2) 3.0 Gal. Additional Tanks 1 1 2 3 1.5 Gal. Reg. Release Single 3.0 Gal. Reg. Release Double 1.5 Gal. Reg. Release 3.0 Gal: Additional Tank Double Multiple Multiple Multiple Multiple 3.0 Gal. Reg. Release 3.0 Gal. Additional Tank 1.5 Gal. Reg. Release 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 3.0 Gal. Reg. Release 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 34-38 1.5 Gal. Reg. Release • 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 39-44 4 Multiple 3.0 Gal. Reg. Release 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 45-49 5 Multiple 1.5 Gal. Reg. Release 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 50-55 5 Multiple 3.0 Gal. Reg. Release 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 56-60 6 Multiple 1.5 Gal. Reg. Release 3.0 Gal. Additional Tank 61-66 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 6 Multiple 3.0 Gal. Reg. Release 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank Based on 5 flow numbers for a t5 gal. system and 11 flow numbers for a 3 0 gal. system. See Pages 4-39 - 4-42 for exceptions. If tanks are manifolded, only a "double tank" nitrogen cartridge (Part No. 73022) can be used. If tanks are manifolded, either an LT -A-101-30 nitrogen cartridge (Part No. 29187) or a double tank cartridge (Part No. 73022) can be used. LT -20-R (7032) LT -30-R (5373) Double (73022) Carbon Dioxide Cartridge Reouired 101-10 (15850) 101-20 (17492) 101-30 (15851) Double (73022) 101-30 (15851) - LT -20-.R (7032) 101-10 (15850) LT -A-101:30 (29187) 101-30 (15851)'"* LT -30-R (5373) 101-20 (17492) LT -A-101-30 (29187) 101-30 (15851r - Double (73022) N/A Double (73022) LT -A-101-30 (29187) Double (73022) LT -A-101-30 (29187) LT -20-R (7032) LT -A-101-30 (29187) LT -A-101-30 (29187) LT -30-R (5373) LT -A-101-30 (29187) LT -A-101-30 (29187) Double (73022) LT -A-101-30 (29187) LT -A-101-30 (29187) Double (73022) LT -A-101-30 (29187) LT -A-101-30 (29187) 101-30 (15851) 101-30 (15851)`- 101-30(15851)" 101-30 (15851y- 101-10 (15850) 101-30 (15851)*** 101-30 (15851)**` 101-20 (17492) 101-30 (15851)* 101-30 (15851)*** 101-30 (15851) 101-30 (15851)*'* 101-30 (15851)" 101-30 (15851)- 101-30 (15851r- 101-30 (15851)"* = =-i "tea r , { 9 I UKWILA FIRE DEPARTMELM , , Please call: 575.4402 and give this job ii No. o8 -H - 3a , and exact address for shute 0 l VithOut CON-Az-ratc )own or restoration approve; - / ❑ AF ;d:::;d In Red 12( Par Tile Au_ chad Leber i nese plans ho -L.,tj hr TIP' -ita Fire Prevent, or, E',. _ , r _.c , .- , . - t c'` ', standards A '• • omissionth vv' starta giros 1, adequacy , L•, Additions, c. , : „ f • t' i this Cat? +v;li voo, !to :t ',.. i',i . >, r� t,,, ,L .7, resubmittal of revrse� ..:.,..o.!• ;s !Jr R ;y:.` yl,`_'t, e.i2rcval. Final acceptance is s ab!ect to f cid test ar,d inspection by The Tukwila Fere Preve,itron Bureau. F Date: 6 -/d1-o8 By: r 1 J ea • ANSLJL. >fycto Fin Suppression & Building Products R-102 RESTAURANT SYSTEM NOZZLE COVERAGE/OVERLAPPING SUMMARY SHEET ► App8ance Nozzle Type Pow Points width In. (cm) Max. Side Multiple Length in. (cm) Max. Stile Multiple Nozzle w/o Drip Board Area int (crrr2) Nozzle w/ Drip Board Area brz (ctnm) Minimum Nozzle Ht. In. (cm) Maximum Nozzle HL in. (cm) Fryers withot{t drip boards Pr0Split 230/290* 2 14 (36) 15 (38) -'Low - 27/13 (69/33) 47/16 (119/41). dr No Split Vat 245/290' 2 14/14.5 (36/37) 15/14 (38/36) - - 20/16 (51/41) 27/27 (69/69) Fryers without drip boards 290 2 19.5 (50) 19 (48.2) - - 13 (33) 16 (41) Non -Split Vat (ONLY) 3N 3 19.5 (50) 19 (48.2) - - 21 (53) 34 (86) 3N 3 18 (45.7) 18 (45.7) - - 25 (64) 35 (89) *Low Prude* Fryers with drip boards 230/290* 2 14 (36) 21 (53) 210 (1355) 294 (1897) 27/13 (69/33) 47/16 (119/41) Split qr No Split Vat' 245/290* 2 14/14.5 (36/37) 21/26.5 (53/67) 210/203 (1355/1310) 2941384.2 (1897/2479) 20/16 (51/41) 27/27 (69/69) fors ! wit1( drip boards' 290 2 19.5 (50) 25 3/8 (65) 370.5 (2390) 495 (3194) 13 (33) 16 (41) Non -Split Vat (ONLY) 3N ' 3 19.5 (50) 25 3/8 (65) 370.5 (2390) 495 (3194) 21 (53) 34 (86) E 3N 3 1$ _ (45.7) 27 3/4 (70.5) 324 (2090) 497 (3206) 25 (64) 35 (89) Tilt SidtietBraisifig Pan' Coverage limitation are based on fryer sizes including the drip boards. Exception: Tilt Skillets and Braising may exceed the maximum of 6 ft2 (0.56 m2) Longest Side Max. Area In' (cm') f'llange 1} L1N - -. -T2 (30.0 �_ X30.5) - 30 (76) 40 (102) Without back shelf 1i 1 ,_ ._ 12 (30.5) .4 28 (71) 336 (2168) - 30 (76) 50 (127) With back shelf' 1F 1 12 (30.5) 28 (71) 336 (2168) - 40 (102) 48 (122) 245 2 24 (61) 28 (71) - - 40 (102) 50 (127) Witho'utback shelf 260 2 24 (61) 32 (81) 768 (4955) - 30 (76) 40 (102) Wi(h back shelf 260 2 12 (30.5) 32 (81) 384 (2477) - 30 (76) 40 (102) 2 x 290 4 36 (91)_ . 28 _ (71) 1008 (6503) - 15 (38) 20 (51) 'Griddle 1 11N/1 NO 1 36.._ (91) _ 34 (76) - - 35 (89)- 40 (102) - 290 2 30 (76) 24 (61) - - 30 (76) 7 50 (127) 260 2 48 (122) 30 (76) - - 30 (76) 50 (127) 290 2 48 (122) 30 (76) - - 20 (51) 30 (76) 2120 2 48 (122) 30 (76) - - 10 (25) 20 (51) Chain Broiler' (Overhead Protecctjon) 2 x 1W 2 34 (86) 30 (76) - 10 (25) 26 (66) Chain Broiler (Horizontal Protec ion) 2 x 1N 2 31 (79) 43 (109) - - Front edge; 1 to (3 to 8 cm) above 3 in. the chain Char Broiler 'Gas -Radiant 1W1NSS 1 24 (61) 36 (91) - - 15 (38) 40 (102) Electric 1W1NSS 1 20 (51) 34 (86) - - 20 (51) 50 (127) Lava -Rock 1W1NSS 1 13 (33) 24 (61) - - 18 (46) 35 (89) Nab ai Charcoal' 1W1NSS 1 12 (30.5) 24 (61) - - 18 (46) 40 (102) Lava -Rock or NattUal Charcoal' 3N 3 24 (61) 30 (76) - - 14 (36) 40 (102) Wood Fueled' 3N 3 24 (61) 30 (76) - - 14 (36) 40 (102) Upright Broiler 2 x 1/2N 1 30 (76) 32.5 (82.5) Front edge; Salamander Brollpr 2 x 1211 1 30 (76) 32.5 (82.5) - - above the grate 1N 1 16 (41) 29 (74) - - - I- !the 1 N nozzle location to be on the vertical edge 6 to 12 in. (15.2 to 30.5 cm) in front and 0 to 12 in. (0 to 30.5 cm) above top of broiler Interjtal Chamber 119 1 16 (41) 29 (74) - - 6-12 in. above either end (15.2 to 30.5 cm) Wok 3.75 to 8 in. deep (9. to 20.3 cm) 260 2 14 to 30 in. (36 to 76 cm) diameter -35 - (89) 45 (114) 3 to 6 In. (7.6 to 15.2 cm) deep ' For multiple nozzle orotwilInn of 1W1NSS ct,,,,e fn,e... 1 .. ., 11 to 24 In. (28 to 61 cm) diameter .,..,.”-. ,-.-__..-_ - 30 (76) 40 (102) pages 4-8 to 4111 of manual. ' See Figure 1 for nozzle location. ' Minimum chair *Deer exhaust opening -12 In. x 12 In. (30.5 cm x 30.5 cm), and not less than160% of internal broiler size. ► ' 4 In. (10 cm) maximum fuel depth. `6 In. (15 cm) maximum fuel depth. • nen can ovemang bumer(s) by maximum of 11 In. (28 cm) and height limitation of 20 In. (51 cm) from bottom of lowest part of shelf to the top of bumer grate. ' Shelf can overhang bumer(s) by maximum of 11 In. (28 cm) and height ► limitation of 18 in. (45.7 cm) from bottom of lowest part of shelf to the top of bumer grate. • Low Proximity ► *NW!. 101 CO Rre Suppression & Building products R-102 RESTAURANT SYSTEM NOZZLE COVERAGE/OVERLAPPING SUMMARY SHEET Duct I Plenum .Horizontal Nozzle Type Flow Points Width in. (cm) Max Side Length In. (cm) Max. Side Nozzle Placement (See Manual for More Detail) Min. Height t In. (cm) Max. Height In. (cm) Protection Single Bank i ` 1N 1 - 48 (122} 120 (305).. 0 in. to.6 In. (0 to 15.2 cm) from end of plenum 2 (5) 4 (10)7 Perpendicular Protection Single Bank 1W 1 48 (122) 48 (122) See Manual for more detail 1 (2.5) 20 (51) Horizontal Protection V -Bank 2 x 1N 2 48 (122) 120 (305) 0 in. to 6 in. (0 to 15.2 cm) from end of plenum 2 (5) 4 (10) Horizontal Protection V Bank 1W 1 48 (122) 72 (183) 0 In. to 6 In. (0 to 15.2 cm) from end of plenum 1/3 the height 01 filter Perpendicular Protection V Bank 1W 1 48 (122) 48 (122) See Manual for more detail 1 (2.5) 20 (51) Duct I Nozzle Type Flow Points Perimeter In. (cm) Diameter In. (cm) Nozzle Placement (See Manual for More Detail) Duct Length in. (cm) Single Nozzle 1 Flow Nozzle 1W 1 50 (127) 16 (41) See Manual for more detail Unlimited reingie Nozzle 2jFlow Nozzle 2W 2 100 (254) 31 7/8 (81) See Manual for more detail Unlimited/ Multiple Nozzle 2W + 1W 3 135 (343) 48 (122) See Manual for more detail Unlimited Multiple 2W No zie 2W — >135 (343) >135 (343) See Manual for more detail Unlimited R-102 OVERLAPPING PROTECTION The 245 nozzle, Part No. 419340, must be used for 'end of zone protection, and the 260 noXzle, Part No. 419341, must be used for zone protection. Appliance lypie Fryer Griddle Range Wok, Maximum Wok, Minimum: Braising Panhlilt Skillet' Lava Rock Char -Broiler Charcoal Broiler Mesquite Wood Broiler Gas Radiant Cftar-Broiler Electric Char -Broiler ' See Figure 1 tor nozzle location. Note: Group protection option is required for appliances on either side of an appliance(s) using dedicated protection — see manual for details. Maximum Cooking Hazard 34 in. (864 mm) Deep x 5.8 ft2 (5388 cm2) 30 in. (762 mm) Deep x Unlimited Length 30 M. (762 mm) Deep x Unlimited Length 30 in. (762 mm) Diameter x 8 in. (203 mm) Deep 11 in. (279 mm) Diameter x 3 in. (76 mm) Deep 34 in. (864 mm) Deep x Unlimited Length 26 in. (660 mm) Deep x Unlimited Length 30 in. (762 mm) Deep x Unlimited Length (4 in. (102 mm) Maximum Fuel Depth) 30 in. (762 mm) Deep x Unlimited Length (6 in. (152 mm) Maximum Fuel Depth) 36 In (914 mm) Deep x Unlimited Length 34 in. (864 mm) Deep x Unlimited Length COVER MUST NOT INTERFERE wiTH EDGE OF DISCHARGE PATTERN ZONE CENTER UNE Overlapping System Piping Limitations System Size 3Gal (11 L) 6 Total Flow Numbers 6 Gal (23 L) 12 Man folded Max. 3/8 in. Max. Pipe No. of Length Elbows 75 ft 25 (22.9 m) 75 ft 25 (22.9 m) 50 ft (15.2 m) maximum pipe from first to last nozzle. 50 ft (15.2 m) maximum pipe after the split on a split system. Maximum Elevation Rise 10ft (3.1 m) 10ft (3.1 m) Cartridge Size LT -30-R Double Tank FIGURE 1 ANSUL INCORPDRA72`D. ONE STANTON STREET. MARINETTE. WI 54143-2542 715-735-7411 Form No. F-2005010-2 CopydgM CMS Maul Incorporated • k § z ± m 6X26 DUCT 0 0 { 360* FUSE LINKS { z — -- -- \ $ Z —111 \ CO 0 _I �0 /\$ 0 @< m \ \ 40-46" 40-46" { -- Z / \/§ 0 w < <0 • 36" X 24" GAS GRIDDLE • • e e • • • • • • * • 36" X 24" GAS RANGE SAN WTCH STATION $ 2 0 j CE =25I tQ.00 E z 2. 0) N C Cr f° E -a 0 �k3 1 / .0. - 2 ` 2 c 0 -Ca C \��} 03 I -C m m e o Coli s=m 2 = o C 0• )2 ■ ck schedule 40 E 03 0 \ 2 £ o ± o = 7 0) • / ■ 0 z / / E 03 0 E f 0) T 03 E 2 0 0 2 2 £ / / \ § j E k \ 0 ■ CEPTED p Without Comments p As Noted in Red Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City is subject to errors and oniasions whim c -a nut authorize violations of adopted ndards ano oraff inces. The responsibility for the ;,t.Prquacy of des'cp ests totally with the designer. ,4rOttions, deletyoris or revisions to these drawingsYafter t is nate wiil void this acceptance and will require a resut rrnittai of revised drawings for subsequent approval. Final acceptance is subject to field test a1d Inspection by 1 rie Tukwila Fire Prevention Bureau. Date: 7 '1 K —I By: 51 I FIRE DEPARDWitni Please call: 575.4407 and give this job No. A2 I and exact address for shuts Town or restoration anorovol Because of increased demand our inspectors' schedules are booked 3-7 days ahead. Therefore, you will need to call 206-575-44,7 or email fireinspreauest@ ci.tukwila.wa.us to schedule your inspections a minimum of 48 hours in advance of the date you want an inspection. 1 11 • ANSUL. f qco Fin Suppression & Building Products R-102 RESTAURANT SYSTEM NO Z LE COVERAGE/OVERLAPPING SUMMARY SHEET . Appliance Nozzle Type Fiow Points Width in. ( Max. Si ) Multiple Length In. (cm) Max. Side Multiple Nozzle w/o Drip Board Area hrz (cm2) Nozzle w/ Drip Board Area tnz (aril Minimum Nozzle Ht. In. (cm) Maximum Nozzle HL In. (cm) Fryers withotjt drip boards 230/290* 2 14 (36) 15 (38) - - 27/13 (69/33) 47/16 (119/41)taw Prokilry. Split dr No Split Vat 245/290' 2 14/14.5 (36/3 15/14 (38/36) - - 20/16 (51/41) 27/27 (69/69) Fryers withotit drip boards 290 2 19.5 (50) 19 (48.2) - - -ti 13 (33) 16 (41) Non -Split Vat (ONLY) 3N 3 19.5 (50) I 19 (48.2) - - 4- " 21^ (53) 34 (86) 3N 3 18 (45.7 18 (45.7) - - ,25 _(64) 35 (89) Fryers with drip boards 'Low Proxlmly 230/290' 2 14 (36) 1 21 (53) 210 (1355) 294 (1897) 27113 •(69/33) 47/16 (119/41) Split qr No Split Vat' 245t290*2 2 14/14.5 (36/30 21/26.5 (53/67) 210/203 (1355/1310) 291/381 (1897/2479) 20/16 (51/41) 27/27 (69/69) Fryers w t1tdrip boards' 290 2 19.5 (50) ; 25 3/8 (65) 370.5 (2390) 495 (3194) 13 (33) 16 ` (41) Non -Split Vat (ONLY) 3N 3 19.5 (50) 25 3/8 (65) 370.5 (2390) 495 (3194) 21 (53) 34 (86) 3N 3 18 (45. 27 3/4 (70.5) 324 (2090) _497 (3206) 25 (64) 35 (89) Tilt SldlietBraisllip Pan' Coverage limitation are based o fryer sizes including the drip boards. Exception: Tilt Skillets and Brai 'ng may exceed the maximum of 6 ft2 (0.56 m2) Longest Side Max. Area in, (cm2) Range 1N 1 12 (30. 32 (81) 384 (2477) - 30 (76) 40 (102) Without back shelf 1F 1 12 (30. 28 (71) 336 (2168) - 30 (76) 50 (127) With back shelf' 1F 1 12 (30.5) 28 (71) 336 (2168) - 40 (102) 48 (122) 245 2 24 (61) 28 (71) - - 40 (102) 50 (127) Without back shelf 260 2 24 (61) 32 (81) 768 (4955) - 30 (76) 40 (102) Wier back shelf' 260 2 12 (30.5) 32 (81) 384 (2477) - 30 (76) 40 (102) 2 x 290 4 36 (91) 28 (71) 1008 (6503) - 15 (38) 20 (51) Griddle 1W1NSS 1 36 (91) 30 (76) - - 35 (89) 40 (102) 290 2 30 (76) 24 (61) - - 30 (76) 50 (127) 260 2 48 (122 30 (76) - - 30 (76) 50 (127) 290 2 48 (122 30 (76) - - 20 (51) 30 (76) 2120 2 48 (122 30 (76) - - 10 (25) 20 (51) Chain Broiler' (Overhead Protection) 2 x 1W 2 34 (86) 30 (76) - - 10 (25) 26 (66) Chain Broiler (Horizontal Protec ion) 2 x 1N 2 31 (79) 43 (109) - - Front edge; 1 to 3 in. (3 to 8 cm) above the chain Char Broiler 1Gas-Radiant 1N/1NSS 1 24 (61) 36 (91) - - 15 (38) 40 (102) Electric 1N/1NSS 1 20 (51) ' 34 (86) - - 20 (51) 50 (127) Lava -Rock 1N/1NSS 1 13 (33) I 24 (61) - - 18 (46) 35 (89) Natt*aICharcoal' 1N/1NSS 1 12 41 (30.) 24 (61) - - 18 (46) 40 (102) Lava -Rock or Natural Charcoal' 3N 3 24 (61) 30 (7 - 14 (36) 40 (102) VI/ood Fueled' 3N 3 24 (61) 30 ) - 14 (36) 40 (102) Upright Broiler 2 x 1/2N 1 30 (76) 32.5 (82.5) :v t Front edge; Salamander Broiler 2 x 1/2N 1 30 (76) 32.5 (82.5) - i' above the grate 1N 1 16 (41) 29 (74) - !- IN nozzle location to be on the vortical edge 6 to 12 In. (15.2 to 30.5 cm) In front and 0 to to 30. ) above the top of broiler Internal Chamber 1N 1 16 (41) 29 (74) - - In. above either end (1 .2 to 30.5 cm) Wok 3.75 to 8 in. deep (9.51 to 20.3 cm) 260 2 14 to 30 In. (36 to 76 cm) diameter - - 35 (89) 45 (114) 3 to 6 In. (7.6 to 15.2 cm) deep ' For multiniw nrv7b nmfn..tb.....G 1 N/1 NSS ei....i. I........ 1 _ 11 to 24 in. (28 to 61 cm) diameter .J__-..-- - - - 30 (76) 40 (102) pages 4-8 to 4-111 of manual. ' See Figure 1 for nozzle location. ►' Minimum chain baohter exhaust opening - 12 In. x 12 In. (30.5 m x 30.5 cm), and not less than 16o% of Internal broiler size. ► ' 4 In. (10 cm) maximum fuel depth. 6 In. (15 an) maximum fuel depth. ' Snen can overhang bumer(s) by maximum of 11 In. (28 cm) and height limitation of 20 In. (51 cm) from bottom of lowest part of shelf to the top of bumer grate. Shelf can ht ►' limitation of 18 in. overhang45.7 cm) from bottom of maximum olowest part of shel) f to the top of bumer grate. • Low Proximity •L • ANSLJL. Vico Rre Suppression & Building Products NOZZL R-102 RESTAURANT SYSTEM COVERAGE/OVERLAPPING SUMMARY SHEET Plenum Nozzle Type Flow Points in. Max. Width (cm) Side Length In. (cm) Max. Side Nozzle Placement (See Manual for More Detail) Min. Height in. (cm) Max. Height In. (cm) Horizontal Protection Single Bank 1N 1 48 (122) 120 (305) 0 in. to 6 in. (0 to 15.2 cm) from end of plenum 2 (5) 4 (10) Perpendicular Protection Single Bank 1W 1 48 (122) 48 (122) See Manual for more detail 1 (2.5) 20 (51) Horizontal Protection V -Bank 2 x 1N 2 48 (122) 120 (305) 0 in. to 6 In. (0 to 15.2 cm) from end of plenum 2 (5) 4 (10) Horizontal Protetition V -Bank 1W 1 48 (122) 72 (183) 0 in. to 6 In. (0 to 15.2 cm) from end of plenum 1/3 the he ght of filter Perpendicular Pirotection V -Bank 1 W 1 48 (122) 48 (122) See Manual for more detail 1 (2.5) 20 (51) Duct Nozzle Type Flow Points Perimeter n. (cm) Diameter In. (cm) Nozzle Placement (See Manual for More Detail) Duct Length in. (cm) Single Nozzle 1 IFlow Nozzle 1W 1 50 (127) 16 (41) See Manual for more detail Unlimited Single Nozzle 2tFlow Nozzle 2W 2 100 (254) 31 7/8 (81) See Manual for more detail Unlimited Multiple Nozzle 2W + 1W 3 135 (343) 48 (122) See Manual for more detail Unlimited Multiple 2W No3zle 2W — >135 (343) >135 (343) See Manual for more detail Unlimited R-102 OVERLAPPING PROTECTION The 245 nozzle, Part No. 419340, must be used for -end of zone protection, and the 260 nozzle, Part No. 419341, must be used for zone" protection. Appliance lyp(e Fryer Griddle Range Wok, Maximum Wok, Minimum Braising Pan/Tilt Skillet' Lava Rock Cher -Broiler Charcoal Broiler Mesquite Wood Broiler Gas Radiant Cftar-Broiler Electric Char-Bjoiler ' See Figure 1 10 nozzle location. Note: Group protection option Is required for appliances on either Side of an appliance(s) using dedicated protection — see manual for details. Maximum Cooking Hazard 34 in. (864 mm) Deep x 5.8 12 (5388 cm2) 30 jn. (762 mm) Deep x Unlimited Length 30 in. (762 mm) Deep x Unlimited Length 30 In. (762 mm) Diameter x In. (203 mm) Deep 11 In. (279 mm) Diameter x in. (76 mm) Deep 34 In. (864 mm) Deep x Unl ited Length 26 In. (660 mm) Deep x Unl ited Length 30 In. (762 mm) Deep x Unl fled Length (4 in. (102 mm) Maximum F el Depth) 30 in. (762 mm) Deep x Unl ited Length (6 in. (152 mm) Maximum F el Depth) 36 In (914 mm) Deep x Unli ited Length 34 in. (864 mm) Deep x Uni fled Length COVER MUST NOT INTERFERE WITH EDGE OF DISCHARGE PATTERN 0-12 IN 11 (0.305 mm) I • 1 1 ZONE i ZONE CENTER UNE Overlapping System Piping Limitations System Size 3Gal (11 L) 6 Total Flow Numbers 6 Gal (23 L) 12 Manifolded 50 ft (15.2 m) maximum 50 ft (15.2 m) maximum Max. 3/8 in. Max. Pipe No. of Length Elbows 75 ft 25 (22.9 m) 75 ft 25 (22.9 m) pipe from first to last nozzle. pipe after the split on a split system. Maximum Elevation Rise 10ft (3.1 m) 10 ft (3.1 m) Cartridge Size LT -30-R Double Tank FIGURE 1 ANSUL INCORPORAT ONE E STANTON STREET. MARINErTE. WI 541 542 715-735-7411 Forth No. F-2005010-2 CoPrhWtt moo Mau incorporated a A11NSU.IL. R-102TM' RESTAURANT SYSTEM DISTRIBUTION PIPING REQUIREMENTS SHEET Distribution Piping Requirements - 6.0 Gallon (22.7 Liter Manifolded System Requirements Supply Une Duct Branch Une Plenum Branch Line Appliance Branch Une Pipe Size Maximum Lepgth Maximum Rise Maximum 90r Elbow Maximum Tees Maximum Flaw Numbers 3/8 In. 32 ft (9.7 m) 6 ft (1.8 m) 8 2 22 3/8 in. 8 ft (2.4 m) 4 ft (1.2 m) 4 2 4 3/8 in. 4ft(1.2m) 2 ft (0.6 m) 4 2 2 3/8 in. 12 ft (3.7 m) 2 ft (0.6 m) 6 4 4 Distribution Piping Requirements - 6.0 (22.7 Liter) Gallon System 1. The maXimum length between the start of the first branch Ilne and the start of the last branch line must not exceed 24 ft (7.3 m). When thsupply line is split, the combined total of both legs of the supply line (from the start of the first branch line to the start of the,last branch line) must not exceed 24 ft (7.3 m). 2. -',..The total length of all branch lines must not exceed 36 ft (10.9 m). -34 Use a 3/6 in., union to connect the tank adaptor to the 3/8 in. supply line. ► _.: Disiributlon Piping Requirements - 9.0 (34 Liter) Gallon System Requirements Duct Supply Une Branch Une Plenum Branch Une Appliance Branch Une Pipe Size 3/8 in. Maximum Length 40 ft (12.2 m) Maximum Rise 6 ft (1.8 m) Maximum 90° Elbow 9 Maximum Tees 1 Maximum Flow Numbers 11' 'Exceptions; 1. Twelve (14) flow numbers are allowed in any one t 2. Twelve (1) flow numbers are allowed with any one 3. Twelve (14) flow numbers are allowed with any one Special Insthjuctions: 1. Twelve (12) flow numbers are allowed when four (4) 2. For certain McDonald's applications, 11.5 flow num • 1/2N electrostatic precipitator nozzle, one (1) 1N ple Applications Engineering Department for additional i 3/8 in. 8 ft (2.4 m) 4 ft (1.2 m) 4 2 4 3/8 in. 4 ft (1.2 m) 2 ft (0.6 m) 4 2 2 k for hood and duct protection. nk using only two -flow appliance nozzles. k using only three -flow appliance nozzles. 3/8 in. 12 ft (3.7 m) 2 ft (0.6 m) 6 4 4 jean Industries GTI Gas Fryers are protected at low proximity. rs are allowed when using a combination of one (1) 2W duct nozzle, one (1) um nozzle, and four (4) two -flow appliance nozzles. Contact ANSUL formation. Distribution Piping Requirements - 9.0 (34 Liter) G 1. The max)mum length between the start of the first b When the supply line Is split, the combined total of the last branch line) must not exceed 24 ft (7.3 m). 2. The total length of all branch lines must not exceed ft (10.9 m). 3. Use a 3/1 In. union to connect the tank adaptor to th = 3/8 in. supply line. Ion System line and the start of the last branch line must not exceed 24 ft (7.3 m). th legs of the supply line (from the start of the first branch line to the start of General Poling Requirements 1. All R-104 system piping is straight line. Therefore, _ need for critical lengths and balancing is minimized. 2. Two 45° ;elbows count as one 90° elbow. 3. Each branch line includes the tee or elbow leading to it, and all fittings within the branch line itself. 4. The minimum piping length of Schedule 40, 3/8 in. pipe from the tank outlet to any nozzle protecting a range, fryer, or wok must be 6 ft (1.8 Vin). 5. Pipe lengths are measured from center of fitting to center of fitting. 6. All distribution piping must be Schedule 40 black iron, chromeplated, or stainless steel. Do not use hot dipped galvanized pipe on the distribution piping. 7. All three connections located in and above the protected area must be sealed with pipe tape. Tape should be applied to male threads ly. Make certain tape does not extend over the end of the thread, as this could cause possible blockage of the agent distrib A 6UL INCORPORATED, ONE STANTON STREET, MARI ETTE. WI 541432542 715-735-7411 Fonn No. F-2005074-1 Copyright ceOO8 Ansel Incorporated 1 C • c• ca o a CDD O • g co z. sa t0 m C 9D "' CG a C c CG uncle pa}aauuoa uaap,SS ■ 0tr alnpauas Noglq sl adld iw In :310N 0 �(DD 5 • CD lQ C7 W0-g.umi o m to to m rn m < 0 (D2. th m0 0 x rn CD o 0 Cco CD o CD CD to :L 1 ■ nv,m1v = • x0-70 rn 3 0 r. 02 o O CD 4 7 -w N 1.12 CD N 3 ro 5 CD CD 0 CD a3 o m j O 3 CD 0 D- ▪ 7 (D a c5 0 O 0 O 3 2. a 0 CD o — 0. co o - Co 0. NOIIVIS HD1Vv JNVS C48' }C 24" GAS GRIDDLE 1II • • 1 0 • • 6 • • C K C -rrl 4 3> °D O C O r r ,,8tr-017 „gtr-017 — O Cb C4 z -- 4�-- n W % y aa) ,,moo O 0 z c') • C rrn O4 rn rn OC°rn • 2 0ZD Z O O z z S>INll 3Sn3 r090 2 0 0 0 ..KX9 o - - i • 9 z m -- -i rn 0, 0 m [T �� i3—Po Ees o -4 o�QD &--rnoF n --1 0 rn� m > V cc. n rno, - CI CO ru - -O rn 91' MO13 ltin1D it ANSUL. tyco An Sappns:fon &BuildingProducts R-102 RESTAURANT SYSTEM NOZZLE COVERAGE/OVERLAPPING SUMMARY SHEET . Appliance pages 4-8 to 4.11 of manual. See Figure 1 for nozzle location. ► ' Minimum chain beer exhaust opening -12 in. x 12 In. (30.5 cm x 30.5 cm), and not less t anl60% of Internal broiler size. ► ' 4 In. (10 cm) max+mum fuel depth. 6 In. (15 cm) max)mum fuel depth. Nozzle type Flow Point+ t46d9r in. ( ) Max. Si Multiple Length in. (cm) Max. Side Multiple Nozzle w/o Drip Board Area Rri (cmz) Nozzle w/ Drip Board Area int (cm2) Minimum Nozzle lit In. (cm) Maximum Nozzle Ht. In. (cm) Fryers wtthot(t drip boards Proximity Split dr No Split Vat Fryers withotit drip boards Non -Split Vat (ONLY) 230/290' 2 14 (36) 15 (38) - - 27/13 (69/33) 47/16 (119/41)tew . 245/290' 2 14/14.5 (36/3 15/14 (38/36) - - 20/16 (51/41) 27/27 (69/69) 290 2 19.5 (50) 19 (48.2) - - 13 (33) 16 (41) 3N 3 19.5 (50) 19 (48.2) - - 21 (53) 34 (86) 3N 3 18 (45.7) 18 (45.7) - - 25 (64) 35 (89) Fryers with drip boards Split cir No Split Vat' 230/290* 2 14 (36) 21 (53) 210 (1355) 294 (1897) 27/13 (69/33) 47/16 (119/41) 245290` 2 14/14.5 (36/37) 21/26.5 (53/67) 210/203 (1355/1310) 294/384.2 (18972479) 20/16 (51/41) 27/27 (69/69) Fryers wit}( drip boards' Non -Split Vat (ONLY) 290 2 19.5 (50) 25 3/8 (65) 370.5 (2390) 495 (3194) 13 (33) 16 (41) 3N 3 19.5 (50) 25 3/8 (65) 370.5 (2390) 495 (3194) 21 (53) 34 (86) 3N 3 18 (45.7) 27 3/4 (70.5) 324 (2090) 497 (3206) 25 (64) 35 (89) Tilt Skillet/Bnisif4g Pan° Coverage limitation are based Exception: Tilt Skillets and Braising o1 fryer sizes including the drip boards. may exceed the maximum of 6 ft2 (0.56 m2) Range Without back shelf Wiih back shelf Withdutback shelf Wt tbackshelf Longest Side Max. Area in, (cm') 1N 1 12 (30.5) 32 (81) 384 (2477) - 30 (76) 40 (102) 1F 1 12 (30.5) 28 (71) 336 (2168) - 30 (76) 50 (127) 1F 1 12 (30.5) 28 (71) 336 (2168) - 40 (102) 48 (122) 245 2 24 (61) 28 (71) - - 40 (102) 50 (127) 260 2 24 (61) 32 (81) 768 (4955) - 30 (76) 40 (102) 260 2 12 (30.5) 32 (81) 384 (2477) - 30 (76) 40 (102) 2 x 290 4 36 (91) 28 (71) 1008 (6503) - 15 (38) 20 (51) Griddle 1W1NSS 1 36 (91) 30 (76) - - 35 (89) 40 (102) 290 2 30 (76) 24 (61) - - 30 (76) 50 (127) 260 2 48 (1221 30 (76) - - 30 (76) 50 (127) 290 2 48 (122 30 (76) - - 20 (51) 30 (76) 2120 2 48 (122 30 (76) - - 10 (25) 20 (51) Chain Broiler' (Overhead Protection) 2 x 1W 2 34 (86) 30 (76) - - 10 (25) 26 (66) Chin Broiler (Horizontal Protection) Ch Char Broiler jGas-Radiant Electric Lava -Rock Natural Charcoal' Lava -Rock or Naturae Charcoal' V/lood Fueled` 2 x 1N 2 31 (79) 43 (109) - - Front edge; 1 to 3 in. (3 to 8 cm) above the chain 1W1NSS 1 24 (61) 36 (91) -- 15 (38) 40 (102) 1W1NSS 1 20 (51) 34 (86) - - 20 (51) 50 (127) 1W1NSS 1 13 (33) 24 (61) - - 18 (46) 35 (89) 1W1NSS 1 12 (30.) 24 (61) - - 18 (46) 40 (102) 3N 3 24 (61) 30 (76) -- 14 (36) 40 (102) 3N 3 24 (61) 30 (76) - - 14 (36) 40 (102) Upright Broiler Salamander Broiler 'Mahal Chamber 2 x 1/2N 1 30 (76) 32.5 (82.5) Front edge; 2 x 1/2N 1 30 (76) 32.5 (82.5) - - above the grate 1N 1 16 (41) 29 (74) - - - - 1 N nozzle location to be on the vertical edge 6 to 12 In. (15.2 to 30.5 cm) In front and 0 to 12 In. (0 to 30.5 cm) above the top of broiler 1N 1 16 (41) 29 (74) - - 6-12 in. above either end (15.2 to 30.5 cm) Wok 3.75 8 In. deep (9. to 20.3 cm) 3 to 6 in. (7.6 to 15.2 cm) deep 260 2 14 to 30 in. (36 to 76 cm) diameter ( - - 35 (89) 45 (114) 1W1NSS 1 11 to 24 in. (ptj-8 to 61 cm) diameter - - 30 (76) 40 (102) 1 For multinia nn77in nrnte..fi.... of . t....I,. f....... - _.J___ . Shelf can overhang bume (s) by maximum of 11 in. (28 cm) and height limitation of 20 In. (51 cm) from bottom of lowest part of shelf to the top of bumer grate. ' Shelf can overhang bumer(s) by maximum of 11 in. (28 cm) and height ► limitation of 18 in. (45.7 cm) from bottom of lowest part of shelf to the top of bumer grate. • Low Proximity 10. v. 3. •l • ANSLJL. !Vico Are Suppression & Building Products NOZZL R-102 RESTAURANT SYSTEM COVERAGE/OVERLAPPING SUMMARY SHEET Plenum i Nozzle Type Flow Points Width in. (cm) Max. Side Length In. (cm) Max. Side Nozzle Placement (See Manual for More Detail) Min. Height In. (cm) Max. Height In. (cm) Horizontal Protebtlon Single Bank 1N 1 48 (122) 120 (305) 0 in. to 6 in. (0 to 15.2 cm) from end of plenum 2 (5) 4 (10) Perpendicular Ptotection Single Bank 1W 1 48 (122) 48 (122) See Manual for more detail 1 (2.5) 20 (51) Horizontal Prote4tion V -Bank 2 x 1N 2 48 (122) 120 (305) 0 in. to 6 in. (0 to 15.2 cm) from end of plenum 2 (5) 4 (10) Horizontal Protection V -Bank 1W 1 48 (122) 72 (183) 0 in. to 6 In. (0 to 15.2 cm) from end of plenum 1/3 the height of filter Perpendicular Pfotectlon V -Bank 1 W 1 48 (122) 48 (122) See Manual for more detail 1 (2.5) 20 (51) R-102 OVERLAPPING PROTECTION The 245 nozzle, Part No. 419340, must be used for "end of and the 260 noXzle, Part No. 419341, must be used for 'z Appliance 'type Fryer Griddle Range Wok, Maximum Wok, Minimum; Braising Panrfllt Skillet' Lava Rock Cher -Broiler Charcoal Broiler Mesquite Wool) Broiler Gas Radiant Ctiar-Broiler Electric Char -Boiler ' See Figure 1 foj nozzle location. Note: Group protection option is required for appliances on either Maximum Cookln, Hazard 34 in. (864 mm) Deep x 5.8 30 in. (762 mm) Deep x Un 30 in. (762 mm) Deep x Unli 30 in. (762 mm) Diameter x 11 in. (279 mm) Diameter x 34 In. (864 mm) Deep x Unl 26 In. (660 mm) Deep x Unl 30 In. (762 mm) Deep x Unl (4 In. (102 mm) Maximum F 30 in. (762 mm) Deep x Unl (6 in. (152 mm) Maximum F 36 in (914 mm) Deep x Unli 34 In. (864 mm) Deep x Unl Overlapping System Piping Umitations Total Max. 3/8 In. Max. System Flow Pipe No. of Size Numbers Length Elbows 3Gal (11 L) 6 75ft 25 (22.9 m) 6 Gal (23 L) 12 75 ft Manifolded (22.9 m) 50 ft (15.2 m) Maximum pipe from first to last nozzle. 50 ft (15.2 m) maximum pipe after the split on a split systerk 25 e' protection, e protection. 2 (5386 cm2) ited Length ited Length in. (203 mm) Deep in. (76 mm) Deep ited Length ited Length lied Length el Depth) fled Length el Depth) ited Length ked Length COVER MUST NOT INTERFERE WiTH EDGE OF DISCHARGE PATTERN 1 t 1.0--46 0-12 IN I I (0-305 mm) 1 1 '1 I1 1 1 ZONE ZONE CENTER UNE ide of an appliance(s) using dedicated protection — see manual for details. Maximum Elevation Rise 10ft (3.1 m) 10 ft (3.1 m) Cartridge Size LT -30-R Double Tank FIGURE 1 ANSUL INCORPORATiu, ONE STANTON SWEET, MARItETTE. WI 541 542 715-735-7411 Form No. F-2005010-2 Copyright 02008 Ansul Incorporated Nozzle Placement Duct Nozzle Flow erimeter Diameter (See Manual Length Duct 1 Type Points n. (cm) In. (cm) for More Detail) In. (cm) Single Nozzle 1 Flow Nozzle 1W 1 (127) 16 (41) See Manual for more detail Unlimited Single Nozzle 21Fiow Nozzle 2W 2 100 (254) 31 7/8 (81) See Manual for more detail Unlimited Multiple Nozzle 2W + 1W 3 135 (343) 48 (122) See Manual for more detail Unlimited Multiple 2W Noizle 2W — >135 (343) >135 (343) See Manual for more detail Unlimited R-102 OVERLAPPING PROTECTION The 245 nozzle, Part No. 419340, must be used for "end of and the 260 noXzle, Part No. 419341, must be used for 'z Appliance 'type Fryer Griddle Range Wok, Maximum Wok, Minimum; Braising Panrfllt Skillet' Lava Rock Cher -Broiler Charcoal Broiler Mesquite Wool) Broiler Gas Radiant Ctiar-Broiler Electric Char -Boiler ' See Figure 1 foj nozzle location. Note: Group protection option is required for appliances on either Maximum Cookln, Hazard 34 in. (864 mm) Deep x 5.8 30 in. (762 mm) Deep x Un 30 in. (762 mm) Deep x Unli 30 in. (762 mm) Diameter x 11 in. (279 mm) Diameter x 34 In. (864 mm) Deep x Unl 26 In. (660 mm) Deep x Unl 30 In. (762 mm) Deep x Unl (4 In. (102 mm) Maximum F 30 in. (762 mm) Deep x Unl (6 in. (152 mm) Maximum F 36 in (914 mm) Deep x Unli 34 In. (864 mm) Deep x Unl Overlapping System Piping Umitations Total Max. 3/8 In. Max. System Flow Pipe No. of Size Numbers Length Elbows 3Gal (11 L) 6 75ft 25 (22.9 m) 6 Gal (23 L) 12 75 ft Manifolded (22.9 m) 50 ft (15.2 m) Maximum pipe from first to last nozzle. 50 ft (15.2 m) maximum pipe after the split on a split systerk 25 e' protection, e protection. 2 (5386 cm2) ited Length ited Length in. (203 mm) Deep in. (76 mm) Deep ited Length ited Length lied Length el Depth) fled Length el Depth) ited Length ked Length COVER MUST NOT INTERFERE WiTH EDGE OF DISCHARGE PATTERN 1 t 1.0--46 0-12 IN I I (0-305 mm) 1 1 '1 I1 1 1 ZONE ZONE CENTER UNE ide of an appliance(s) using dedicated protection — see manual for details. Maximum Elevation Rise 10ft (3.1 m) 10 ft (3.1 m) Cartridge Size LT -30-R Double Tank FIGURE 1 ANSUL INCORPORATiu, ONE STANTON SWEET, MARItETTE. WI 541 542 715-735-7411 Form No. F-2005010-2 Copyright 02008 Ansul Incorporated ANAL. R-102TM' ESTAURANT SYSTEM DISTRIBUTION PIPING REQUIREMENTS SHEET Distribution Piping Requirements - 6.0 Gallon (22.7 UterManifolded System Requirement's Supply Une Duct Branch Une Plenum Branch Une Appliance Branch Une Pipe Size Maximum Length Maximum RiSe Maximum 90r Elbow Maximum Tees Maximum Flow Numbers 3/8 In. 32 ft (9.7 m) 6 ft (1.8 m) 8 2 22 3/8 in. 8 ft (2.4 m) 4 ft (1.2 m) 4 2 4 3/8 in. 4 ft (1.2 m) 2 ft (0.6 m) 4 2 2 3/8 in. 12 ft (3.7 m) 2 ft (0.6 m) 6 4 d Distribution Piping Requirements - 6.0 (22.7 Liter) Gallon System 1. The maximum length between the start of the first branch Ilne and the start of the last branch line must not exceed 24 ft (7.3 m). When the supply line is split, the combined total of both legs of the supply line (from the start of the first branch line to the start of the last branch line) must not exceed 24 ft (7.3 m). 2. The•total length of all branch lines must not exceed 303 ft (10.9 m). 3' Use a 3/6 in. union to connect the tank adaptor to the 3/8 in. supply line. Distribution Piping Requirements - 9.0 (34 Uter) Gallon Requirement's Supply Une System Duct Branch Une Plenum Branch Une Appliance Branch Une Pipe Size 1 3/8 in. 3/8 in. 3/8 in. 3/8 in. Maximum Length 40 ft (12.2 m) 8 ft (2.4 m) 4 ft (1.2 m) 12 ft (3.7 m) Maximum Rife 6 ft (1.8 m) 4 ft (1.2 m) 2 ft (0.6 m) 2 ft (0.6 m) Maximum 90? Elbow 9 4 4 6 Maximum Teas 1 2 2 4 Maximum Flow Numbers 11' 4 2 4 'Exceptions; 1. Twelve (12) flow numbers are allowed In any one tank for hood and duct protection. 2. Twelve (12) flow numbers are allowed with any one nk using only two -flow appliance nozzles. 3. Twelve (1?) flow numbers are allowed with any one k using only three -flow appliance nozzles. Special Inst#uctions: 1. Twelve (12) flow numbers are allowed when four (4) can Industries GTI Gas Fryers are protected at low proximity. 2. For certal' McDonald's applications, 11.5 flow numb rs are allowed when using a combination of one (1) 2W duct nozzle, one (1) 1/2N elegy rostatic precipitator nozzle, one (1) 1N ple um nozzle, and four (4) two -flow appliance nozzles. Contact ANSUL Applicatio Engineering Department for additional i formation. Distribution Piping Requirements - 9.0 (34 Uter) G Ion System 1. The maximum length between the start of the first b line and the start of the last branch line must not exceed 24 ft (7.3 m). When the supply line is split, the combined total of th legs of the supply line (from the start of the first branch line to the start of the last branch line) must not exceed 24 ft (7.3 m). 2. The tota length of all branch lines must not exceed ft (10.9 m). 3. Use a 3,13 In. union to connect the tank adaptor to the 3/8 in. supply line. General Pining Requirements 1. All R-104 system piping is straight line. Therefore, the need for critical lengths and balancing is minimized. 2. Two 45' leibows count as one 90' elbow. 3. Each brr> h line Includes the tee or elbow leading t it, and all fittings within the branch line itself. 4. The minimum piping length of Schedule 40, 3/8 In. pe from the tank outlet to any nozzle protecting a range, fryer, or wok must be 6ft(1.8m). 5. Pipe lengths are measured from center of fitting to center of fitting. 6. All distribution piping must be Schedule 40 black iron, chromeplated, or stainless steel. Do not use hot dipped galvanized pipe on the distrilaution piping. 7. All threaded connections located in and above the protected area must be sealed with pipe tape. Tape should be applied to male threads only. Make certain tape does not extend over the end of the thread, as this could cause possible blockage of the agent distributlOn. AMAX INCORPORATED. ONE STANTON STREET, MARIr ETTE, W1541432542 715-735-7411 Form No. F2005071-1 Copyright 02004 Ana Incorporated 1 \`c K \ $ }k 0o a. to cr< J � / \ so 0c CD Wagla aal; o} pa}oauuoo w s,S ■ Ob alnpagos losiq sl did ilb' ■ :DION ■ e RK7 7 2. 5'n 5mGE u 0-E m g E m m rnCO I.C2 CD ƒ\I0 (ti — o ? o — \ ® 5' CD - NOIIVIS HD1W►ANV'S 111 48' X 24" GAS GRIDDLE 111 \ k — & -- — 9 A co / is j ------ �0) \ x7 / g k S>INI1 DSnA :09£ I 0 0 0 m \ k — & -- — 9 A co / is j ------ �0) \ x7 / g k S>INI1 DSnA :09£ I 0 0 0 m •t • ANSUL. tyco Fir. Suppression & Building Products R-102 RESTAURANT SYSTEM NOZ7LE COVERAGE/OVERLAPPING SUMMARY SHEET ApplIance Nozzle Type Flow Paints Width in. (an) Max. Side Multiple Length in. (cm) Max. Side Multiple Nozzle w/o Drip Board Area irtz (cm2) Nozzle w/ Drip Board Area Int (cm2) Minimum Nozzle RL in. (cm) Maximum Nozzle Rt in. (cm) Fryers without drip boards 23W290' 2 14 (36) 15 (38) - - 27/13 (69/33) 47/16 (119/41)*Low �Spiit dr No Split Vat 245/290' 2 14/14.5 (36/37) 15/14 (38/36) - - 20/16 (51/41) 27/27 (69/69) Fryers without drip boards 290 2 19.5 (50) 19 (48.2) - - 13 (33) 16 (41) Non -Split Vat (ONLY) 3N 3 19.5 (50) 19 (48.2) - - 21 (53) 34 (86) 3N 3 18 (45.7) 18 (45.7) - - 25 (64) 35 (89) Fryers with drip boards 230/290` 2 14 (36) 21 (53) 210 (1355) 294 (1897) 27/13 (69/33) 47/16 (119/41) 'Lot Pnoinity Spilt qr No Split Vat' 245/290' 2 14/14.5 (36/3 21/26.5 (53/67) 210/203 (1355/1310) 29413812 (1802479) 20/16 (51/41) 2727 (69/69) Fryers with drip boards' 290 2 19.5 (50) 25 3/8 (65) 370.5 (2390) 495 (3194) 13 (33) 16 (41) Non -Split Vat (ONLY) 3N 3 19.5 (50) 25 3/8 (65) 370.5 (2390) 495 (3194) 21 (53) 34 (86) 3N 3 18 (45. 27 3/4 (70.5) 324 (2090) 497 (3206) _ 25 (64) 35 (89) Tilt Skiliet/Bratshig Pan' Coverage limitation are based o fryer sizes including the drip boards. Exception: Tilt Skillets and Brai 'ng may exceed the maximum of 6 ft2 (0.56 m2) Longest Side Max Area ire (cm') Range 1N 1 12 (30.1 32 (81) 384 (2477) - 30 (76) 40 (102) Without back shelf 1F 1 12 (30.1 28 (71) 336 (2168) - 30 (76) 50 (127) With back shelf' 1F 1 12 (30. 28 (71) 336 (2168) - 40 (102) 48 (122) 245 2 24 (61) 28 (71) - - 40 (102) 50 (127) Withdutbackshelf 260 2 24 (61) 32 (81) 768 (4955) - 30 (76) 40 (102) Writ' back shelf' 260 2 12 (30: 32 (81) 384 (2477) - 30 (76) 40 (102) 2 x 290 4 36 (91) 28 (71) 1008 (6503) - 15 (38) 20 (51) Griddle 1W1NSS 1 36 (91) 30 (76) - - 35 (89) 40 (102) 290 2 30 (76) 24 (61) - - 30 (76) 50 (127) 260 2 48 (122 30 (76) - - 30 (76) 50 (127) 290 2 48 (122 30 (76) - - 20 (51) 30 (76) _ 2120 2 48 (122 30 (76) - - 10 (25) 20 (51) Chain Broiler' (Overhead Protection) 2 x 1W 2 34 (86) 30 (76) - - t0 (25) 26 (66) Chain Broiler (Horizontal Protection) 2 x 1N 2 31 (79) 43 (109) - - Front edge; 1 to 3 in. (3 to 8 cm) above the chain Char Broiler IGas-Radiant 1W1NSS 1 24 (61) 36 (91) - - 15 (38) 40 (102) Electric 1 W1 NSS 1 20 (51) 34 (86) - - 20 (51) 50 (127) Lava -Rock 1W1 NSS 1 13 (33) I 24 (61) - - 18 (46) 35 (89) NatujaICharcoal' 1WINSS 1 12 (30.5) 24 (61) - - 18 (46) 40 (102) Lava -Rock or Natural Charcoal' 3N 3 24 (61) 30 (76) - - 14 (36) 40 (102) yllood Fueled` 3N 3 24 (61) 30 (76) - - 14 (36) 40 (102) Upright Broiler 2 x 1/2N 1 30 (76) 32.5 (82.5) Front edge; Salamander Broiler 2 x 1/2N 1 30 (76) 32.5 (82.5) - - above the grate 1N 1 16 (41) 29 (74) - - - - 1N nozzle location to be on the vertical edge 6 to 12 In. (15.2 to 30.5 cm) In front and 0 to 12 in. (0 to 30.5 cm) above the top of broiler Interhal Chamber 1N 1 16 (41) 29 (74) - - 6-12 in. above either end (15.2 to 30.5 cm) Wok 3.75 8 In. deep (9. to 20.3 cm) 260 2 14 to 30 in. (56 to 76 cm) diameter I - - 35 (89) 45 (114) 3 to 6 in. (7.6 to 15.2 cm) deep 1 W1 NSS 1 11 to 24 in. (8 to 61 cm) diameter f - - 30 (76) 40 (102) rryars, sea oe[anea wn4rma[an on pages 4-8 to 411, of manual. See Figure 1 for nozzle location. P. • Minimum chain biolier exhaust opening -12 In. x 12 In. (30.5 cm x 30.5 cm), arid not Tess than160% of internal broiler size. ► ' 4 In. (10 cm) maxfrnum fuel depth. `6 In. (15 cm) maximum fuel depth. •Shen can overhang bumer(s) by maximum of 11 In. (28 cm) and height limitation of 20 In. (51 cm) from bottom of lowest part of shelf to the top of burner grate. Shelf bums ► r limitation nof 18 .(45.7 cm) from bottom maximum of lowest part of shelf to the top of bumer grate. • Low Proximity '1 ANSti. tgco Sr. Suppmsslon & Building Products NOZZL R-102 RESTAURANT SYSTEM COVERAGE/OVERLAPPING SUMMARY SHEET Plenum Nozzle Type Flow Points Width in. I (cm) Malt. Side Length In. (cm) Max. Side Nozzle Placement (See Manual for More Detail) Min. Height In. (cm) Max. Height In. (cm) Horizontal Proteon Single Bank i 1N 1 48 (122) 120 (305) 0 in. to 6 in. (0 to 15.2 cm) from end of plenum 2 (5) 4 (10) Perpendicular Piotecdon Single Bank 1W 1 48 (122) 48 (122) See Manual for more detail 1 (2.5) 20 (51) Horizontal Protebtion V -Bank 2 x 1N 2 48 (122) 120 (305) 0 in. to 6 In. (0 to 15.2 cm) from end of plenum 2 (5) 4 (10) Horizontal Prote.tion V -Bank 1 W 1 48 (122) 72 (183) 0 in. to 6 in. (0 to 15.2 cm) from end of plenum 1/3 the height of filter Perpendicular Protection V -Bank 1 W 1 48 (122) 48 (122) See Manual for more detail 1 (2.5)1 20 (51) R-102 OVERLAPPING PROTECTION The 245 nozzle, Part No. 419340, must be used for "end of and the 260 nozzle, Part No. 419341, must be used for 'z Appliance Type Fryer Griddle Range Wok, Maximum Wok, Minimum Braising Pan/Tilt Skillet' Lava Rock Cndr-Broiler Charcoal Broiler Mesquite Wood Broiler Gas Radiant C-rar-Brroiler Electric Char -Boiler ' See Figure 1 toj nozzle location. Note: Group protection option Is required for appliances on either ide of an appliance(s) using dedicated protection — see manual for details. Maximum Cooking Hazard 34 in. (864 mm) Deep x 5.8 30 jn. (762 mm) Deep x Unli 30 in. (762 mm) Deep x Unli e' protection, e" protection. 2 (5368 cm2) tied Length ited Length 30 in. (762 mm) Diameter x in. (203 mm) Deep 11 in. (279 mm) Diameter x $ in. (76 mm) Deep 34 in. (864 mm) Deep x Uni. 26 in. (660 mm) Deep x Uni' 30 in. (762 mm) Deep x Unli (4 in. (102 mm) Maximum F nited Length nited Length nfted Length el Depth) 30 in. (762 mm) Deep x Unl ited Length (6 in. (152 mm) Maximum Fiel Depth) 36 In (914 mm) Deep x Unlimited Length 34 in. (864 mm) Deep x Unlimited Length COVER MUST NOT INTERFERE WITH EDGE OF DISCHARGE PATTERN 0-12 IN 1 (0305 mm) '1 I / 11 ! ZONE f ZONE CENTER UNE Overlapping System Piping Limitations System Size 3 Gal (11 L) 6 Gal (23 L) Manifolded Total Flow Numbers 6 12 Max. 3/8 in. Pipe Length 75 ft (22.9 m) 75 ft 25 (22.9 m) Max. No. of Elbows 25 50 ft (15.2 m) maximum pipe from first to last nozzle. 50 ft (15.2 m) maximum pipe after the split on a split system Maximum Elevation Rise 10ft (3.1 m) 10ft (3.1 m) Cartridge Size LT -30-R Double Tank FIGURE 1 ANSUL WcoRForiAio. arE STANT 4 sTREEr.. MARWErrE. WI 541 542 715-735-7411 Form No. F-2005010-2 Copyright 02608 Aneul Incorporated Nozzle Placement Duct Nozzle Flow !meter Diameter (See Manual Length Duct j Type Points n. (cm) In. (cm) for More Detail) in. (cm) Single Nozzle 1 IFlow Nozzle 1W 1 (127) 16 (41) See Manual for more detail Unlimited Single Nozzle 21Flow Nozzle 2W 2 00 (254) 31 7/8 (81) See Manual for more detail Unlimited Multiple Nozzle 2W + 1W 3 35 (343) 48 (122) See Manual for more detail Unlimited Multiple 2W Noizle 2W — > 35 (343) >135 (343) See Manual for more detail Unlimited R-102 OVERLAPPING PROTECTION The 245 nozzle, Part No. 419340, must be used for "end of and the 260 nozzle, Part No. 419341, must be used for 'z Appliance Type Fryer Griddle Range Wok, Maximum Wok, Minimum Braising Pan/Tilt Skillet' Lava Rock Cndr-Broiler Charcoal Broiler Mesquite Wood Broiler Gas Radiant C-rar-Brroiler Electric Char -Boiler ' See Figure 1 toj nozzle location. Note: Group protection option Is required for appliances on either ide of an appliance(s) using dedicated protection — see manual for details. Maximum Cooking Hazard 34 in. (864 mm) Deep x 5.8 30 jn. (762 mm) Deep x Unli 30 in. (762 mm) Deep x Unli e' protection, e" protection. 2 (5368 cm2) tied Length ited Length 30 in. (762 mm) Diameter x in. (203 mm) Deep 11 in. (279 mm) Diameter x $ in. (76 mm) Deep 34 in. (864 mm) Deep x Uni. 26 in. (660 mm) Deep x Uni' 30 in. (762 mm) Deep x Unli (4 in. (102 mm) Maximum F nited Length nited Length nfted Length el Depth) 30 in. (762 mm) Deep x Unl ited Length (6 in. (152 mm) Maximum Fiel Depth) 36 In (914 mm) Deep x Unlimited Length 34 in. (864 mm) Deep x Unlimited Length COVER MUST NOT INTERFERE WITH EDGE OF DISCHARGE PATTERN 0-12 IN 1 (0305 mm) '1 I / 11 ! ZONE f ZONE CENTER UNE Overlapping System Piping Limitations System Size 3 Gal (11 L) 6 Gal (23 L) Manifolded Total Flow Numbers 6 12 Max. 3/8 in. Pipe Length 75 ft (22.9 m) 75 ft 25 (22.9 m) Max. No. of Elbows 25 50 ft (15.2 m) maximum pipe from first to last nozzle. 50 ft (15.2 m) maximum pipe after the split on a split system Maximum Elevation Rise 10ft (3.1 m) 10ft (3.1 m) Cartridge Size LT -30-R Double Tank FIGURE 1 ANSUL WcoRForiAio. arE STANT 4 sTREEr.. MARWErrE. WI 541 542 715-735-7411 Form No. F-2005010-2 Copyright 02608 Aneul Incorporated a ANS,UL. R-102TM ESTAURANT SYSTEM DISTRIBUTION P PING REQUIREMENTS SHEET Distribution Piping Requirements - 6.0 Gallon (22.7 UterManlfolded System Duct Supply Une Branch Une Requirements Plenum Branch Une Appliance Branch Une Pipe Size Maximum Lehgth Maximum Riyte Maximum 90'r Elbow Maximum Teis Maximum Flgw Numbers 3/8 in. 32 ft (9.7 m) 6ft(1.8m) 8 2 22 3/8 in. 8 ft (2.4 m) 4 ft (1.2 m) 4 2 4 3/8 in. 4ft(1.2m) 2 ft (0.6 m) 4 2 2 3/8 in. 12 ft (3.7 m) 2 ft (0.6 m) 6 4 4 DlstribuUo6 Piping Requirements - 8.0 (22.7 Uter) Gallon System 1. The maximum length between the start of the first branch line and the start of the last branch line must not exceed 24 ft (7.3 m). When this supply line Is split, the combined total of both legs of the supply line (from the start of the first branch line to the start of the,last branch line) must not exceed 24 ft (7.3 m). 2. The total length of all branch lines must not exceed 36 ft (10.9 m). 3;.Use. a 3/8 in., union to connect the tank adaptor to the 3/8 in. supply line. ► .: Dtstributlon Piping Requirements - 9.0 (34 Uter) Gallon System Requirement's Supply Une Duct Branch Une Plenum Branch Une Appliance Branch Une Pipe Size I 3/8 In. 3/8 in. 3/8 in. 3/8 in. Maximum Lehgth 40 ft (12.2 m) 8 ft (2.4 m) 4 ft (1.2 m) 12 ft (3.7 m) Maximum RiSe 6 ft (1.8 m) 4 ft (1.2 m) 2 ft (0.6 m) 2 ft (0.6 m) Maximum 90° Elbow 9 4 4 6 Maximum Tees 1 2 2 4 Maximum Flow Numbers 11' 4 2 4 'Exceptions; 1. Twelve (12) flow numbers are allowed in any one t k for hood and duct protection. 2. Twelve (12) flow numbers are allowed with any one nk using only two -flow appliance nozzles. 3. Twelve (12) flow numbers are allowed with any one k using only three -now appliance nozzles. Special Instjuctlons: 1. Twelve (12) flow numbers are allowed when four (4) bean Industries GTI Gas Fryers are protected at low proximity. 2. For certai McDonald's applications, 11.5 flow numbers are allowed when using a combination of one (1) 2W duct nozzle, one (1) 1/2N el tic precipitator nozzle, one (1) 1N plenum nozzle, and four (4) two -flow appliance nozzles. Contact ANSUL Applicatio Engineering Department for additional information. Distribution Piping Requirements - 9.0 (34 Uter) GaIon System etch line and the start of the last branch line must not exceed 24 ft (7.3 m). th legs of the supply line (from the start of the first branch line to the start of 1. The maximum length between the start of the first b When the supply line is split, the combined total of t the last branch line) must not exceed 24 ft (7.3 m). 2. The tote,length of all branch lines must not exceed ft (10.9 m). 3. Use a 3/8 in. union to connect the tank adaptor to the 3/8 in. supply line. General Piping Requirements 1. All R-104 system piping is straight line. Therefore, the need for critical lengths and balancing is minimized. 2. Two 45° lelbows count as one 90° elbow. 3. Each brunch line includes the tee or elbow leading t it, and all fittings within the branch line itself. 4. The minimum piping length of Schedule 40, 3/8 in. pe from the tank outlet to any nozzle protecting a range, fryer, or wok must be 6ft(1.8in). 5. Pipe lenoths are measured from center of fitting to nter of fitting. 6. All distribution piping must be Schedule 40 black fro , chromeplated, or stainless steel. Do not use hot dipped galvanized pipe on the distribution piping. 7. All three d connections located in and above the protected area must be sealed with pipe tape. Tape should be applied to male threads ly. Make certain tape does not extend over the end of the thread, as this could cause possible blockage of the agent distrib Ar'6Ut. Pl00RPORATED, OPE STANTON STREET. MARINE TE. WI 54143-2542 715-735.7411 Form No. F-2005074-1 Copyright 02ooe Mst4 incorporated waala GA o} papauuoo wa},s,S ■ Otr alnpauos loaiq sl 9c10 11,00 ■ :310N ■ /\2 = K s n 5ncE u a E m CI CD 0 -/7= CD ,s2 ai - -.c \/ ai }c0- $ CD< 0 C ■ 1 § CO k C am: CD a/ƒ7c $ < 0 j _ ; 0 0 CO f ' «' ] E 9 ƒ E 0 - \ -0 \ 0r, CD /\q 0 0 o (1-,- f > / a a o \ e \ \ 0 CD D - 1- NOIIVIS HD1LM INVS 111 48' X 24" GAS GRIDDLE III •■ $ $ •_ • a e { 2 O m z Q. k\\ 0�/ 2 „9tr-017 „9tr-Otr — co > \ / R0 a2 SllNf-1 3Sf13 r09£ 1Dna „8ZX9 I 0 0 0 2 0 6 \ £ I MO1J 1Vfl l k A DAPHNES FIRE ALARM SYSTEM TUKWILA, WASHINGTON Lt. ow a Iv es SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET \UVIRER SHEET TITLE FA -01 SYSTEM INFORMATIO\ FA -02 TYPICAL DETAILS - WIRI\G A D VI O U \TI \ G FA -03 FRE ALARM SYSTEM FLOOR PLA\ FA -04 SYSTEM CALC U LATI O \ S GE\EAL)-, RISE, SITE PLA\ WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATI❑N LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATI❑N TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE 7WO 600V #12 AWG THHN/THWN TWO 600V #14 AWG THHN/THWN TWISTED TWO CONDUCTOR 300V #18 AWG FPL TW CABLE CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BONG RUN IN THE CONDUIT ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF CONDUIT SIZE MAXIMUM F 1/2" .12 SQUARE 3/4" .21 SQUARE 1" .34 SQUARE 1-1/4" .60 SQUARE 1-1/2" .82 SQUARE 2" 1.34 SQUARE FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM DIMENSIONS AREA .244 0.0. .0467 .210 0.D. .0346 .156 0.D. .0191 FROM THE TABLE FILL DIMENSION FROM THE WIRE. LL NCH NCH NCH NCH NCH INCH N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD ® SMOKE DETECTOR HFP-11 IN/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING 1;4 D DUCT SMOKE DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING Ec FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX IN/ 1-1/2" EXT. CEILING L C FIRE ALARM STROBE (CEILING MOUNT) ZR-MC-C.W SIEMENS 4S BOX IN/ 1G RING CEILING ILI FIRE ALARM STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX IN/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. YC FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING Q FB -0 WP MR FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) MULTI -VOLTAGE CONTROL RELAY SET -W SIEMENS SET -S17 -WP SIEMENS MR -201 /C AIR PRODUCTS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD O JUNCTI❑N BOX F,B.❑, N/ Vtttlr r IN FIELD F.B.D. FURNISHED BY OTHERS N/A N/A Without Comments N/A N/A NOT APPLICABLE N/A -e ` As Not Red /A Per The Attached Letter N/A UNLESS OTHERWISE NOTED N/A ' vseenptiloannsBuhraevaeu befoer nc»rmweadncbey wTihthe CTuurkrewnilaarRU.D,N. WP WEATHERPROOF DEVICE N/A missions which do notNytorize violations of adjplt4d standards and ordinances. The responsibility for the A =OE RED AS BUILT ADD OR CHANGE N/A i, 0ditions, deletions or r ons to these drawin `�er this date will void thie.acceptance and will require a ire DE Certifical GREEN AS BUILT REMOVE N/A /A N/A N/A Final acceptance is subject to field test and Inspection by .. commenc Testinc BLUE AS BUILT NOTES TO CAD N/A . _.:., /AcN/A N/A Date: _ °g By: 7'6 and D Failure TUKWILA FIRE DEPART iv...N;.r Please call:575.4407. and give this job andexortred or ationfor apPr tv rlD FAX (206) 628-4990 RELEASE/REVISIONS CO w DESCRIPTION SHOP DRAWINGS w c0 0 0 z C C Jop co T 2a) Cd) w w 0 W Z~ W t� Z CC cp a_ 5 < Q Q o� 0 r� LT_ O oD c'1 NOTICE ted, signed, Tukw apartment Pre-test .e must be presented Inspector prior to :ement of Acceptarce I of any Fire Alarm etection Systems. of test will result inspection Fee and ermination of the testing. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved .CALF: 1 /8"=1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: \OB NUMBER: SHEET n FA -01 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO 11 -IRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND IS❑LATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR S+ PREVIOUS ADDRESSABLE DEVIC Y O DUCT DETECTOR LOCATION END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH 0 rr) 0 GROUND HTRI-R STATUS LED 0 N.O. n O c.0 0 COM N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. O TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE DEVICE TO NEXT ADDRESSABLE DEVICE L NOTE 1: VOLTAGE MAX. - CURRENT MAX. - CONT. RES. MAX. - MAX. CABLE LENGTH - C CLINE TO LINE) - C CLINE TO SHIELD) - MAX. LINE SIZE - MIN. LINE SIZE- OUTLET SAMPLING TUBE INLET SAMPLING -- TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE=NONE MUSICL}-AC POWER SOURCE COMBINE ALL SHIELDS AND IS❑LATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE f STOP IF LAST DEVICE l(-) FROM XLS CONTROL PANEL OR {(+) PREVIOUS ADDRESSABLE DEVICE (-) RELAY CONTACTS C4.OA @ 125VAC) (4.OA @ 30VDC) 27 VDC 3.5 nA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0.O2uF 0.O4uF 14 AWG 18 AWG NOTE 2: ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST 25 SEC. TO GUARANTEE DETECTI❑N. (7/ 0 0 10 01 TB1 5 5 9 0 0 0 1 2 3 4 5 6 TB2 CP 0 0 mct +- 65432 1 END OF LINE DEVICE (3.6K 1/4W) O SUPERVISED. -_-__/ SWITCH GROUND i -4- O HTRI-D OSTATUS LED 00 r 0 C NOT USED O NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 CND N AC 0 0 0 J_ J_ J_ T Y T =r- 0 PAD -3 0 0 00 O INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 1132 24K n + TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE 2 NAC -4 NAC -3 NAC -2 2 NAC -1 END OF LINE DEVICE 3,6K 1/4W) SUPERVISED &WITCH FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. -•I \ NOT USED REMOTE + DEVICE LOOP NOT USED REMOTE DEVICE LOOP 0 0 0 FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY C'S' CABLE) FROM FACP (VOIC,E CIRCUIT) C'V' CABLE) 470 OHMS �YV EOL 0 fC M INPU (+ ` N 9 9 TEM -1 Q INC 1- 0 co TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE NUE (STROBE) SPEAKER (+) ( �) (STROBE) -4-- r EARTH GROUND -)(+)TO NEXT DEVICE OR >(-) STOP IF LAST DEVICE � u () STR❑BE) SPEAKER (+) (—) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY 80" A.F.F. R 4S DEEP BOX W/ 1-1/2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE=NONE TO NEXT DEVICE ❑R END OF LINE TO NEXT DEVICE OR END OF LINE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPE 811N TEMPERA1U E: +32'F 0- C TO 100' F 38' C) HUMIDITY: O- 9 333333% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR —� FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE fDATA IN (-) > DATA IN (+) > DEVICE IS USTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJJNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL TO NEXT DEVICEE- > (-) DATA OUT > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID —� CEILING HARD LID ---SPEAKER SUPPORT TI _- BRIDGE - 4' SQUARE DEEP BOX .-- WITH 1-1/2' EXTENSI❑N N CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE=NONE JUNCTI❑N BOX—, MOUNTED ON \ CEILING FLEX \ //I JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT 0 0 ; 1 TO NEXT DEVICE 0 0 CADDY BAR SMOKE DETECTOR ----- SMOKE' SMOKE DETECTOR MOUNTING SCALE=NONE D f ---- SUSPENDED ILLUMINATED CEILING DO \OT I \STA_L ADDRESSABLE IN T DEVICES .,N I IL DREPROGAMMED W DEVICES ADDHSS. AT O N G TH Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved z co)z z 00 0' 0 z_ (1) LLT J I~ - W U) O' W rte) F-- r--- m ` FAX (206) 628-1+990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS DATE oo 0 tn in 19 CCCCC J o .2E6' 20 2 z CO W o z W � _ F_ ) Q QOM W I\� E-1): 0 op N� I z z 0 0 z z E V )J 0 SCALE: 1 /8"=1 ' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: \OB NUMBER: SHEET FA -02 l • • 2C-3-5 110cd 2A-1-9 110cd EOL 2A-1 ' 111 1 •"�%`-x;11 11 1 }yr• i \\ \.,`\ "I.\\\\\ \ „) �. ' V'� ^\' \\\'\'\..)<;- \\-..''',',,,:.'N '\ �, ,"F; \\\ \ \\ `\`\` \ \ \, \ / S 0+\`2` \\\ \, \ •fit \\\•‘,:\\ \ '_\\\:-_-._\,‘ \_-.-\s._k,1 ,\-_- ,. ,-,,,\:e--,-:-.,-‘7\.._,..\,6s__ \\ \ ,\\.:)"\,\\ \,,\\\(—\ \'"h\\w( \ ` \ \ -''' S :.,._:\ \ • ..\. :.- ,:._ .:.• \ ` V ``Y=�\ 110cd % __ \.. I/ iL;,--\:' ------�\ v S i - \ Eo / 20. NORTH , ,\ It, / % J EX / 1 --,.- 1 1 77-7 2C-- 1 E S DAPHNES SOUTHCENTER MALL WESTFIELD SOUTHCENTER MALL SCALE 118"=1' FLAG \ OTES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE, FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATI❑N SUBMITTAL FOR L❑CATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICAL CONTRACTOR, SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO \CT NS AL ADDRESSABLE IN TIATIr DEVICES UNTIL °REPROGRAMMED WI H DEVICES ADD ESS. G Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 11 rfiC Ci3 141 ®2 CC CO 0' 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z DESCRIPTION SHOP DRAWINGS DATE 5/15/08 2 ‹<aaa JCO CO 'CC a) crZ (/)W~0 W CI -1)z a F=- 5 D< 1 Qo L 0 0� CO SCALE: 1. /8"=1 DRAWN BY: ,.ANDERSON DESIGNED BY: R.VEZZAN I DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: \ 0B NUMBER: FA� 03 j \ 0 • ,1 _'__� 111 / l \; `, 1.11111 / t -'1,111 / ,6` _- 11111 --_f "' .il. 1• 1 , •__-__ -=-= 1 11 \ l Il. \ 1 is I. %1. 11 /"' / : = - NORTH N. 'N. 11s =i_711 RIO;: II it �,ii�il� II � , SII D fier Ir,festa eit, FINES1t ric.„ r(tiotz 0 DAPHNES WESTFIELD SOUTHCENTER MALL 0 0 /6 `` ----- ,‘An!• 4 it SCALE 1132"=1' EX SYSTEM CALCULATIONS BATTERY SIZING CALCULATION DAPHNES DAPHNES FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL DATE 5/15/08 Panel: DAPHNES Wire Resistance 1.62. 9 <«« Date: June 10, 2008 CURRENT TOTAL= Current Load: Standby: Alarm: S1 Current Load: Standby: Alarm: QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 0 SET -MC @15CD 64 0 Device Type Qty Amps Total Amps Total SET -MC @30CD Device Type 196 Qty Amps Total Amps Total 0 HFP-11 175 0 0.0022 0.0022 0.0023 Total Device Load, Amps (1) 0.20 0 SET -MC @11 OCD 233 0 AD2-P 0 0.0635 0.0635 0.064 Main System Board 1 0.03 0 0.03 0.030 0.030 HTR -R 0.009600 0.0096 0.021 SET -HMC @135CD 318 SET -MC @15CD EOL Voltage 0.064 0 SET -HMC @185CD HTRI-D 0 0.001600 0.0035 (20.4 - E) SET -MC @30CD Z-MC@15CD 2 0 0.098 0.196 ICP -B6 0 Z-MC@30CD 0.005 0 SET -MC @75CD 0 SET-MC-CW@110CD 233 0.175 DEVICES= 2 TOTAL mA= 196 12 191 SET -MC @11 OCD 0.233 Notification Appliance Circuit Detail - PROJECT: WESTFIELD SOUTHCENTER MALL SET HMC-C@115CD Panel: DAPHNES Wire Resistance 2.58 0.318 Date: June 10, 2008 CURRENT TOTAL 3.6 CIRCUIT: SPEAKER CIRCUIT SET HMC-C@135CD 0.318 QTY Device Type Alarm Current Alarm Total 0.0731 Amps Voltage at EOL Amps SET HMC-C@185CD 2 70.7V 1/8 1.8 0.445 Total Wire Resistance (R) 0.99 0 0 ZR -MC @15CD 0.064 0 Standby Current Load: 0 0.0731 Amps For 24 Hours = 1.754 Amp -hours ZR -MC @30CD 0.00 0 0 0 0.098 (Total Cct Load) 0 0- 0 HCP - Voltage Drop 0.0015 0.00 0 Alarm Current Load: 0 0 Amps For 5 Minutes= Amp -hours (E=I*R) 0 0 0.03 Amps 0.226 Amps EOL Voltage 20.40 0 0 0 (20.4 - E) 0 25% Derating= 2.193 Amp -hours Standby Current Load: 0 0.03 Amps 3.6 For 24 Hours = 0.720 Amp -hours 3.61 DEVICES= 2 Alarm Current Load: 0.226 Amps For 5 Minutes= 0.019 Amp -hours Total System Current Load: 2.193 Amp -hours 25% Derating= 0.924 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.924 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULATION 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a Notification Appliance Circuit Detail DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL DATE 5/15/08 Panel: DAPHNES Wire Resistance 1.62. 9 <«« Date: June 10, 2008 CURRENT TOTAL= 196 CIRCUIT: S1 QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 0 SET -MC @15CD 64 0 Total Wire Resistance (R) 0.62 2 SET -MC @30CD 98 196 (WL * 2) * (R/ft) 0 SET -MC @75CD 175 0 Total Device Load, Amps (1) 0.20 0 SET -MC @11 OCD 233 0 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 Voltage Drop ( E) 0.12 0 SET-HMC-C@177CD 445 0 (E= I * R) 0 SET -HMC @135CD 318 0 EOL Voltage 20.28 0 SET -HMC @185CD 445 0 (20.4 - E) 0 Z-MC@15CD 64 0 0 Z-MC@30CD 98 0 0 SET-MC-CW@110CD 233 0 DEVICES= 2 TOTAL mA= 196 12 191 20.27870736) 1961 Notification Appliance Circuit Detail - PROJECT: WESTFIELD SOUTHCENTER MALL Panel: DAPHNES Wire Resistance 2.58 Date: June 10, 2008 CURRENT TOTAL 3.6 CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 70.7V 1/8 1.8 3.6 Total Wire Resistance (R) 0.99 0 0 0 (WL*2)*(R/ft) 0 0 0 Total Device Load, Amps (I) 0.00 0 0 0 (Total Cct Load) 0 0- 0 - Voltage Drop ( E) 0.00 0 0 0 (E=I*R) 0 0 0 EOL Voltage 20.40 0 0 0 (20.4 - E) 0 0 0 TOTAL mA= 3.6 14 191 20.396451981 3.61 DEVICES= 2 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS DATE 5/15/08 9 <«« 1 J03 00 CQ T C0) CC (� W O W W� Z 1 cc II Q Qco 0 tis 0 0D CDN w O w z w Cl) z 0 U 'GALE: 1 /8" = 1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: RISER DIAGRAM VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved .1013 NUMBER: SHEET k FA -04, ZONE T4 VICFNITY MAP-(Suite#2600) --- SCALE: NTS 2600 DAPHE'S General Notes 1. Western States Fire Protection to add new pendent heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only jn the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. • h: `Without Comments As Noted In Red Per The Attached Letter in 3se plans have ti,,F..•.:ri revi,2.vad by Tie TtikVITlia Fire Pri-vention So; ..,a;.1;'or crohloi'ffiance v.ii;-.n CU rr,..:nit city staidards. Aco.Ttncice i. !.L.i..iot to c:frors and orr ss.lons ‘,J:hich OO IRA iiill-Itii.Z.E: violations of adapted sta -maids and Of :,P11.11:f).1.. -II . a•-•:0(1•.;ibiA.!" for the adoquacy of d,-,.....-,1,.pit.&tot:ly with none designer. Additions; def,ons, or 1-.,,yi:,ioilf'. I'u these dri.-.1wings atter this date will void tii•,:,.o,.:ccpt:-,,noe nnd will iequire a res Jbmittal of rcuic,ed dra,,vings for subsequent approval. Final acceptance is subject to field test and inspectio TI -1 Tukwila Fire Prevention Bureau. IData: • By: issestrtne....u.tummerratetatt.netcesarzwrolnors.srnalmatetlislott.• lui\wiLA FIRE DEPARTMENI Please call: 575-4407 and give this job znd exact address for shut, )t)k...m or restoration approval; EAST RISER DETAIL DRAULIC REFERENCE ONLY NO TO SCALE tfile!d stamps must be inspaled before pipe is hung. 11,29.. rye paint piping prior to hydrostatic test ppproval. K L • •-• • SYMBOL LEGEND REVISIONS 1 4 , ,., . . . . . . ...... Ordinary Group11.0.20gprnift2for 678.29ft2 •—•—•—Existing Main ZONE T4 OPENTO ROOF 115: Remote Area.---0..- FIRE SPRINKLER_SYSTEM_ II_ 1 6 Remote Area 2600 DAPHNE'S CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY CLASS ORD HAZARD II MAX. COVERAGE per HEAD 130 DENSITY .20 GPM 1 Ftfor 678.29 Ft' Ft' SPRINKLER Reliable FI FR Semi-Rec ORIFICE 1/2" K. 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 PSI GPM FLOW 10900 AT BASE OF RISER, SYSTEM REQUIRES: 303.17 GPM © 61.8 PSI ,t !AVM • At time of Design 1 3 5_7 914 K L M N TYPICAL FLEXABLE SPRINKLER CONNECTION, FLEXHEAD MOUNTING BRACKET PIPE NIPPLE , • •:-•ch40$4, 4o:e4:4,1e,g," • ., SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS REDUCING FITTING • SUSPENDED T -BAR GRID • ........ .... • italtr4V0Z•14•A!!•!tt.ox...titt==r.." • .. SPRINKLER -HEAD - CEILING Tlf.:E REM -MAD DETAIL NOT TO SCALE ////////////// //.,-(2,AMBLW.T.-D F00.900 SWIVEL SWAY BRACE FITTING BRACE PIPE 1000 FIG. • s" INF 'FA BCRAIAMCEPATTACHMENT 0 'WO LINE PIPE LATERAL LINE RESTRAINTS NON -THREADED BRACE PIPE FIG. 4A PIPE CLAMP FOR SWAY BRACE 0, LATERAL BRANCHLINE RESTRAINT 3/B` KW] K BOLT (2 1/4' EMBED LENGTH} FIG. 909 NO -THREAD SWIVEL SWAY DRAGS ATTACHMENT NON -THREADED BRACE P(PE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE Hanger No. 07C HILTI Kwik Boit III < / N / HILTI Kwik Bolt II Drilled Anchori / / Cut Rod Lgth Rounded to Nearest Inch Rod Coupling ----N., All Thread Rod Swivel Ring Pipe Concrete Construction Bottom of Concrete to Center Line of Pipe Note on Flan Note on Plan: Hanger Number and 7V Dimension HANGER DETAIL NOT TO SCALE FILE COPY VICINITY_MAP_DETAIL /11 "kw Sprinkler Legend 2 -WAY EARTHQUAKE BRACE NO. DESCRIPTION DATE SYM. SIN QTY. K SPRAY ORIF. FIN. TEMP. MFR./MODEL 4-WAYEARTHQUAKE BRACE R3615 13 5.6 Pendent 1/2,, Chrome 155°F F1FR Semi- Rec APPROVAL: City of Tukwila HYDRAULIC REFERENCE POINT R5415 1 5.6 Pendent Brass 286°F F3QR Dry Pendent CONT. NO.: KS0427 Total = 14 DRAWN BY: Adam Kantner HANGER SYMBOL , t BRANCHLINE RESTRAINT SPRK ON SHEET: SEE LEGEND SPRK. ON JOB: DATE: 06/02/08 Western States Fire Protection Company 7102.180th AVE NE, STE A-105 - REDMOND, WA- 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPR'. OFFICES LOCATED ALBUQUERQUE/AUSTIN/DALLAS /DECATUR / DENVER/ °ULM/ HGATON /KANSAS CITY IAS VEDAS /MINVEAPOUS /PHOENIX/PORTLAND/ RAPID CITY/ ST. PAUL/SALT LAKE CITY/ SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 Daphe's 2600 Southcenter Mall fc---7 Tukwila ,Wa 98188 FIRE SPRINKLER SYSTEM (/) CL CO 0 w z • 8 Adam Kantner Western Construction Services 0 0 z 0 SHEE1 FP -1 OF 1 2003 Tukwila Fire yjz •••••-"'" ------------- VICINITY MAP (Suite#2600) SCALE: NTS 2600 DAPHE'S General Notes 1. Western States Fire Protection to add new pendent heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existingfire sprinkler system to remain. Western States Fire Protection will modify the existing system only jnacwoes of work. All other areas are not in contract and WSFP is not responsible for EAST RISER DETAIL HYDRAULIC REFERENCE ON Y NOT TO SCALE 14 14 1 Ordinary Group II.0.20gpm,ft2 for 678.29ft2 A.F.F 11'-6" O4 N A.F.F 7'-0" 16 Existing Main ZONE T4 A.F.F 12'-4" HOOD ^i� F 15 A.F.F 8'-0" OPEN TO ROOF A.F.F 9'-0" COOLER Remote Area FIRE SPRINKLER SYSTEM 16 1/8"=11-0" Remote Area 2600 DAPHNE'S CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY CLASS ORD HAZARD II MAX. COVERAGE per HEAD 130 Ft' DENSITY .20 GPM ! Ft' for 678.29 Ft' SPRINKLER Reliable F1 FR Semi-Rec ORIFICE 1/2" K. 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 PSI FLOW 10900 GPM AT BASE OF . SYSTEM REQUIRES: 303.17 RISER. 61.8 PSI At time of Design 3 5 7 9 11 17 17 TYPICAL FLEXABLE SPRINKLER CONNECTION FLEXHEAD MOUNTING BRACKET PIPE NIPPLE • SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS REDUCING FITTING SUSPENDED T -BAR GRID SPRINKLER HEAD CEILING TILE FLEXHEAD DETAIL NOT TO SCALE ///////////��%���-(2,3/11' KWIK 4 EMBED LENG TH) FIG.909 SWIVEL SWAY BRACE FITTING \\\ BRACE PIPE FIG. 1000 "FAST CLAMP" SWAY BRACE ATTACHMENT LINE PIPE LATERAL LINE RESTRAINTS NON -THREADED BRACE PIPE 318' KWIK BOLT (2114- EMBED LENGTH) FIG. 909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT FIG. 4A PIPE CLAMP FOR SWAY BRACE �Frl1 LATERAL BRANCHLINE RESTRAINT 441 BRACE PIPE SZ... ..fl NON -THREADED BRACE PIPE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE Hanger No. 07C HILTI Kwik Bolt III N� -/ HILTI Kwlk Bolt II — D/lied Anc\ or 7 — i G 1. / ry Cut Rod Lgth Rounded to Nearest Inch Concrete Construction Bottom of Concrete to Center Line of Pipe Note on Plan Note on Plan: Hanger Number and 'A' Dimension HANGER DETAIL NOT TO SCALE VICE\ TY MAP DETAIL NOT TO SCALE J f fP 6 Q) 0 w. z 0 Adam Kantner D 0) a� m ru0 Western Construction Services CONTRACTOR: SYMBOL LEGEND REVISIONS Sprinkler Legend 2 -WAY EARTHQUAKE BRACE NO. DESCRIPTION DATE SYM. SIN QTY. K SPRAY ORIF. FIN. TEMP. MFR./MODEL 4 -WAY EARTHQUAKE BRACE R3615 13 5.6 Pendent „ 2� Chrome 155°F F1 FR Semi- Rec APPROVAL: City of Tukwila HYDRAULIC REFERENCE POINT R5415 1 5.6 Pendent Brass 286°F F3QR Dry Pendent CONT. NO.: KS0427 Total = 14 DRAWN BY: Adam Kantner HANGER SYMBOL BRANCHLINE RESTRAINT SPRK. ON SHEET: SEE LEGEND SPRK. ON JOB: DATE: 06/19/08 Western States Fire Protection Company 7102 180th AVE NE, STE A-105 - REDMOND, WA - 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY -OFFICES LOCATED ALBUOUEROUE /AUSTIN ! DALLAS /DECATUR /DENVER /DULUTH I HOUSTON /KANSAS CITY LAS VEGAS /MINNEAPOLIS /PHOENIX/ PORTLAND / RAPID CIN/ ST. PAUL I SALT LAKE CITY /SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 Daphe's 2600 Southcenter Mall Tukwila ,Wa 98188 FIRE SPRINKLER SYSTEM SHEET FP -1 OF 1