PP - 2600 SOUTHCENTER MALL FOOD COURT 8 - UNKNOWN TENANT - PERMITS AND PLANS
2600 SOUTHCENTER MALL FC -8 FOOD COURT ASSOCIATED PERMITS 09-F-183 09-S-163 09-H-167 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Cafe Pho 2600 Southcenter Mall FC -8 Permit No.: 09-S-163 Date: October 21, 2009 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'/ inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 30 or more heads require hydrostatic test and system isolation if necessary. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2007 Edition. FIRE DEPARTMENT HOOD SUPPRESSION PLAN REVIEW COMMENTS Project Name: Cafe Pho 2600 Southcenter Mall FC -8 Permit No.: 09-H-167 Date: October 26, 2009 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 FILL uUPY • Nozzle heights above appliances to be per manufacturers installation guidelines. • Install splash guards between fryers and ranges/charbroilers. • Upon activation of the suppression system, the make-up air supply will shut off and the exhaust will keep running. • Type 1 hood systems shall be designed and installed to automatically activate the exhaust fan whenever cooking operations occur. The activation of the exhaust fan shall occur through an interlock with the cooking appliances, by means of heat sensors or by means of other approved methods. • Activation of the suppression system shall shunt all electrical power under the hood as well as the gas supply. • Install a "K" rated portable fire extinguisher within 30 ft. of the cooking equipment. • The hood suppression system shall be monitored by a U.L. Central Monitoring Station. • The suppression system manual pull station shall be located no closer that 10 ft. and no farther than 20 ft. from the cooking equipment and be placed at a height of 42 to 48 inches above the floor. CO co 0 0 41- a3- C • .2 " Ste, V t 0 0 w 'SrCO pp ON N N 0% rte+ N 0t CO 00m co r4 -.. i; r 1 0 co re 1 ed g cm 0 a !2 N W gi P\ 00 u 'n74 tioo cT; z� ;Ft. " v N X 5 2 u.t �• .- ••v....srw+ac-+�xvr,ss•.x�•gra•s:.•nrwet•�'s'armsu;,s�Ev7lKQP3�iW.7�7;'fi-�s"r�:-l:ridlllQl'cQi.���l�L�l4i.�. i�LJllli�iJ���LPt,(j�,'t�t�w��.-�±`r��� . GENERAL. INFORMATION The Amerex KP Series Automatic.Wet Chemical Extinguishing System is designed and has-been tested to provide fire protection for commercial cooking operations covering the hood, ducts, plenum and appliances. Amerex KP Systems are a pre-engineered type as defined in NFPA 17A.— Standard for Wet Chemical Extinguishing. Systems. It is manufactured by the Amerex Corporation, Trussville, Alabama. It is essential that all installations of the Amerex KP Series Systems be performed in compliance with this manual. Those individuals responsible for the design, installation, operation and maintenance of the Amerex KP Restaurant Fire Suppression System must be trained by Amerex and hold a current Amerex Certificate. All piping limitations, • nozzle coverages, detector placements, etc. have been proven and established through exhaustive testing by Underwriters Laboratories, Inc. Use of components other than those referenced in this manual, or installations exceeding limitations stated in this manual will void all of the Amerex KP Series System listings. . LISTINGS:. , . •. The Amerex KP Series. Is a listed, pre-engineered fire extinguishing system. .The KP system is• listed with Underwriters Laboratories, Inc. — USA per UL 300 fire. test specification; Underwriters' Laboratories of Canada, Inc.. per ULC/ORD 1254.6=1995*and Loss Prevention Certification Board - UK per•LPS 1223 rev. . B: Testing.required for listings•underthese standards involve live fire tests under specific conditions involving commercial kitchen hoods, ducts and •appliances. Each test fire Is allowed to reach its maximum intensity befpie agent is discharged. Each test was repeated using both maximum and minimum piping, variations in agent storage cylinder pressure to simulate maximum and minimum temperature ratings. Duct fire tests were extinguished with fans .off and fans on; dampers open and closed. Splash.tests for various appliances were conducted to assure that discharge of the agent would not cause excessive splashing of hot grease to.provide greater employee safety during commercial cooking operations. • . UL Standard 300 introduces a series of tests by specifically addressing the use of high efficiency fryers, ranges, woks and the unique fire extinguishing chaltenges that these appliances present. . DESIGN: . The Amerex KP Series Pre -Engineered System consists of mechanical and electrical oomponents to be installed by an. Authorized Factory Trained and Certified • Amerex KP Systems distributor, • The system . Is 'composed of an. agent cylinder/discharge valve ..charged with. Amerex KP Liquid Agent and a Mechanical Release Module (MRM) or Pneumatic Release Module .(PRM). •The quantity of detectors, fusible links, nozzles, comer pulleys, pulley tees and manual pull .stations will vary depending on kitchen design. • The- system operates either automatically if actuated by a detector or manually If actuated by a manual pull station. Upon system operation, energy sources for the cooking 'appliances are required to be shut off • immediately. Electrical shutdown devices or suitable gas yalves are referenced in. this manual. Other equipment such as audible/visual signaling devices can be added where required.• The Amerex. KP System suppresses fire in commercial cooking .equipment by spraying KP liquid agent in. a predetermined manner onto cooking appliances 'and into exhaust ducts, filters and plenum areas. The primary Means of fire suppression is either by saponification of surface grease or by cooling .the surface of oils and hot metal surfaces With fine droplets of agent, reducing • the temperature of the oil and appliance below the auto -ignition point. • • . Upon system discharge, the exhaust fans should lie left on to aid In dispersal of the liquid suppressant that results in cooling the plenum and duct. Any integral make-up or supply air should be automatically shut off along with all cooking appliances. Some local Authorities Having Jurisdiction October require exhaust fans to be shut down by the fire suppression system. Check local fire codes and requirements in the specific area that the system is being installed. • • The Amerex KP System agent storage cylinders and cartridge shall not be installed in environments. below 32° F or above 120° F (0° C to 49° C). DUCT PROTECTION LIMITATIONS — TWO NOZZLES (2 x P/N 16416) Two Amerex duct nozzles (P/N 16416) will protect ducts with a perimeter of 51 inches to 82 inches (129.5 — 208.3 cm) or a maximum diameter of 26 inches (66 cm). To correctly position the nozzles a rectangular duct should be divided along its longest side into four equal distances. A circular duct should be divided along a centerline into four equal distances. 'A Nozzle should be placed at one quarter of the duct's width (or diameter) with both nozzles on .the centerline,. paced 2-8 inches (5.08 - 20.3 cm) into the duct opening and aimed at the center of the cross section of the. duct. Each nozzle has one flow point. NOTE: In no case can the diagonal dimension of each module exceed 18.8 inches (46 cm). DUCT PROTECTION LIMITATIONS 100 IN. PERIMETER TWO —1'/: FLOW POINT NOZZLES (PIN 11983) The Amerex solid fuel appliance/duct nozzle .(PM 11983) is listed to protect a restaurant cooking exhaustduct of unlimited length and up to 100 perimeter inches (254 cm) or 32 inch diameter (812 cm) using two nozzles. The nozzles total three flow points and to properly position the nozzles, a rectangular duct should be divided along its longest side into four equal distances. A circular duct should be divided along its center line into four equal distances: The 1/4 nozzles are to be placed at one quarter and three quarters position of the duct width (or diameter) with both nozzles on the center line, placed 2 - 8 inches (5.08 — 20.3 cm) into the duct opening and aimed straight up in a vertically run duct. NOTE: In no case can the diagonal dimension of the duct exceed 37.2 inches (94.4 cm) without adding additional duct nozzles. NOTE: The use of one duct nozzle PM 11983 is permitted for duct 50 perimeter inches or Tess fn the same manner as duct nozzle 16416. 1/4 1/2 k2,1 V PLENUM. PROTECTION PLENUM PROTECTION LIMITATIONS — SINGLE FLOW POINT NOZZLE (P/N 11982) The Amerex appliance, plenum nozzle (P/N 11982) is capable of protecting plenums up to 10 feet (3.048m) long with either a single inclined filter bank or a "V" bank filter arrangement. The filter height cannot exceed 24 inches (60.96 cm). Each plenum- nozzle uses one flow point The nozzle must be .positioned 4 inches (10.16) maximum from the wall; aimed horizontally and positioned down 113 the filter height from the top of the filter. • PLENUM PROTECTION — MULTIPLE NOZZLES Plenums exceeding :10 feet (3.048 ni). in length may be protected by using multiple plenum nozzles. Each nozzle must be protecting an area of no more than 10 feet in length. Nozzles may be positioned facing each other or facing the 'same direction as long. as the entire plenum area is being covered. Nozzles may not face in opposite directions from a common tee. SINGLE BURNER RANGE PROTECTION ONE — 1/2 FLOW POINT NOZZLE (P/N 11984) The Amerex half (1/2) flow point nozzle (P/N 11984) will protect a single burner with a surface area of 18" x 18" (46 x 46 cm). The nozzles must be located on the perimeter. The nozzle is aimed at to point 7" above cm)e aboveve -the bumers surface. center of the. bumer. SINGLE BURNER RANGE PROTECTION — OVERHEAD ONE - 1/2 FLOW POINT NOZZLE (P/N 11984) The Amerex half (Y:) flow point nozzle (P/N 11984) will protect a single bumer witha surface area of 18" x 18" (46 x 46 cm). The nozzles must be located directly above the center of the bumer and 24 to 42" (61 - 107 cm) above the bumers surface. The nozzle is aimed at the center of the bumer. TWO BURNER RANGE PROTECTION — SINGLE FLOW POINT NOZZLE (P/N 11982) The Amerex appliance, plenum nozzle (P/N 11982) has one flowpoint and will protect a range surface area of. 14" x 28" (36 x 71 cm). The center to center distance between burners must not exceed .14" (36 cm). The nozzle must be located 44 - 48" (112 - 122 cm) above the range surface and centered between the two bumers. The range surface area is measured from the outside of the burner to the outside of the bumer. NOTE: Maximum and minimum heights must be measured from the tip of nozzle to the surface of the appliance. r Hi 48 in. II CO d �7 in u) Tt to LO d 4 • d si' 4 n .l 05 I • • • Protection is not !knifed to the Items listed on this chart Modulizing larger appliances is an acceptable practice. See your Amerex KP Manuel for additional Cnfornrat/on. r 'C n y = C CO CO C CO CO G ...4z 't- e- C O N C v Nt c CO 'CO C CO e- C O ep C O CO C O CO c I N- c O e- c O c- C CO !"''t C CO -.J C O " C v C D v C •> .Unlimited 'C3. C > . —ems Length •C CA t- im M ko ap. CO N C COCO `- C N G d' N C t1' .N 4-7 depth I C CO C). C N 48 In. \ CO C •C N 24 in. N CO H CO • H \ CO Length O L m E 4 C CO T' ' • C N co .. 'al O) N: p) • C) C. O e- C T' e- • C N e- • C 'I'ccy N 1 C O CO C O CO C O CO C. • O C d' N G d' N C d' N C , . NN C d- = et 1 1 m ?C ) 2 *CC'al E C O tp C 00 e- • •• QO LL Q. N . N C 4 \ r' 1- N e- e- N Cy- e- c- e• ' - e- O O Ll. 0.. e- . d C LL D. e- e- cri co Q d 11 0 13729 .0) N f� M e- CO •e- *a CV 11984 N co co i r • N CO O e- • r 14178 N co co r i Griddle • . I • • 11982 Griddle .. • 13729 Griddle• 14178 Upright Broiler • 2-11984 Charbroiler (Lava Rock) • 11983 Charbroiler (Gas Radiant & Electric Radiant) I 11982 • .! Natural & Mesquite Charcoal Charbroiler 11983 II Mesquite Chips & Chunks Charbroiler • -- 11983 Mesquite Log Charbroiler • 11983 Plenum- • Nozzle P/N N CO CA r. c' • 4 i C w c. N CCI C u) z , 0.. d' Ti 0 • 44 o 0 • CO e�-• .CO e- ' CO = Cr) Q) tt: i Circular _ 16416 I Rectangular 2-11983 .� 0) c- �. CV • 1 tU 03 0 Cti 1 Q a Q • ' j Deep'Fai< Fryer–without Drip Pan Deep Fat Fryer – with Drip Pan RI Deep Fat Fryer – with Drip Pan Low Proximity Raroe – Single Burner Range ;Two Sumer II Range – Two Burner Range – Four Burner • -se .0 4 a KP DISTRIBUTION PIPING DESIGN LIMITS FOR ALL CYLINDER SIZES When designing a KP system to protect a kitchen containing a Fryer, Wok or Range, the following MINIMUM TOTAL SYSTEM PIPING must be used in accordance with the chart below: MINIMUM PIPING REQUIREMENTS MINIMUM MINIMUM TOTAL MINIMUM FLOW APPLIANCE LINEAR FEET EQUIVALENT FEET POINTS PER SYSTEM Wok 6.5 9 7 10 22.1 16.4 6 4 SUPPLY LINE LIMITATIONS: All pipe and fittings running from the distributor block or fill discharge fitting to thefirs CYLINDER MAXIMUM LINEAR MAX. QTY. MAX. QTY. �vy MAX. QTY. FLOW POINTS PIPE SIZE FEET OF PIPE TEES ELBOWS BUSHINGS KP275 - 8 3/8 20 1 MAX. QTY. ELBOWS ` 5 . ' - 0 KP375 -11 3/8 OR 1/2 25 . .1 „ - 5 3/8 OR 1/2 1 KP475 -14 1/2 ,25 1 KP475 -14 5 , ' - 2 KP600 -18 . 1/2 25 1 . AS NOTED 5 50' 3/8" PIPE ONLY ., 2 2-KP375 - 22 - 1/2 30 2 40 7 18 2 : 1. Use 3/8" supply line only when all piping is to be 3/8" pipe. 2. The supply line has a maximum vertical rise above the distributor of 10 feet. SUPPLY BRANCH LINE (including last nozzle branch) LIMITATIONS: All pipe and fittings leaving the first splitting tee in the system and ending with the last nozzle in the last branch line. While the last nozzle branch is included in the piping limitations for the supply branch line, the limitation (pipe size and maximum length) for nozzle branch lines apply to this portion of the supply branch line. CYLINDER FLOW POINTS PIPE SIZE MAX. FEET OF PIPE Si RAIGHT MAX. FEET OF PIPE SPLIT MAX. QTY. TEES MAX. QTY. ELBOWS MAX. QTY. REDUCING BUSHINGS KP275 - 8 3/8 20 25 7 8 0 KP375 -11 3/8 OR 1/2 27 30 10 8 2 KP475 -14 3/8 27 30 12 8 2 KP600 - 18 AS NOTED 33' OF 3/8" OR 1/2" 50' 3/8" PIPE ONLY 14 8 2 2-KP375-22 1/2* 40 45 18 8 0 . 1. In a single 3.75 Gallon Straight Pipe System, 5of pipe may be transferred from the supply line to the supply branch line. *2. The use of 3/8" pipe with two manifold KP375s is only permitted when the SUPPLY UNE length is equal to or less than 20'. NOZZLE BRANCH LINE LIMITATIONS: All pipe and fittings leading from the supply branch tee to a system nozzle. • `p - TOTAL LINEAR MAX. QTY. MAX. QTY. FLOW POINTS PIPE SIZE FEET OF PIPE TEES ELBOWS MAX. QTY. BUSHINGS KP275-8 3/8 32 - 5 10 0 KP375 -11 3/8 OR 1/2 32 8 12 11 KP475 - 14 3/8 32 10 15 0 KP600 - 18 3/8 32 11 18 15 2-KP375 - 22 3/8 32 18 18 20 MAX. PER NOZZLE BRANCH 7 3 6 4 GENERAL SYSTEM LIMITATIONS: 1. No %2" pipe nozzle branches shorter than 12" long. 2. Nozzle types may not be mixed on any nozzle branch line and a maximum of 4 flow points. 3. The discharge fitting, distributor and distribution hose are not to be included in any calculations. 4. No mixing of pipe sizes is allowed within pipe categories. Example: if one nozzle branch is to be W' pipe then all must be'/" pipe. Y2" pipe for nozzle branch lines is allowed only in an 11 flow point system. 5. Duct nozzle has a maximum vertical rise above the supply branch line of 4'0". ACC ?TED 0 O As sa' Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards. Acceptance Is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings after this date will void this acceptance and will require,a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: 10 F - c 9 By: Y1 ( 1 UKWILA FIRE DEPARTIIAFi11 Please call: 575.4407 and give this job No. 4C1— if -/ir7 and exact address for shute -town or restoration appro m FILE COPY CAFE HO FIRE LARM SYSTEM Tt KWILA, ' ASHINGT SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET NUMBER SHEET TITLE FA -01 SYSTEM INFORMATION FA -02 TYPICAL DETAILS - WIRING AND MOUNTING FA -03 FIRE ALARM SYSTEM FLOOR PLAN FA -04 SYSTEM CALCULATIONS (GENERAL), RISER, SITE PLAN 4.11 6P 15/ Without Comments As Noted in Red Q Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted aandards and ordinances. The responsitiiity for the adequacy of design rests totally with the designer. Additions:, deletions or revisions to these drawings after this date will void this acceptance and will requirea resubmittal of revised drawings for sui equent approval Final acceptance is subject to i.l,ld i:r;st and inspection by The Tukwila Fire Prevention Bureau. Date:/I,(2.-O9 By:, /414,1,5-1 TUKWILA FIRE DEPARTMEM Please call: 875.4407 • and give this job NO, Oq-F-183 and exact address for shun av an or restoration . approval, NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems./ Failure of test willresult in a Re -inspection Fee and termination of the testing, WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDIO TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE TWO 600V #12 AWG THHN/THWN TWO 600V #14 AWG THHN/THWN TWISTED TWO CONDUCTOR 300V #18 AWG FPL TW CABLE CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF CONDUIT SIZE MAXIMUM F 1/2" .12 SQUARE 3/4" .21 SQUARE 1" .34 SQUARE 1-1/4" .60 SQUARE 1-1/2" .82 SQUARE 2 1.34 SQUARE FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM DIMENSIONS AREA .244 O.D. .0467 .210 0.0. .0346 .156 O.D. .0191 FROM THE TABLE FILL DIMENSION FROM THE WIRE. LL NCH NCH NCH NCH NCH INCH N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (LE., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 3 3 2 2 1 1 2 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP a INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S DEEP VERIFY IN FIELD 0 DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD C)/CONVENTIONAL CARBON MONOXIDE DETECTOR CODET 12-24 SIEMENS 4S DEEP BOX ® SMOKE DETECTOR (ADDRESSABLE -PHOTO) HFP-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING 12" A.F.F. INSTALLED BY OTHERS CEILING ® DUCT SMOKE p DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING 8cc Ec FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING ▪ c FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING FIRE ALARM © STROBE (WALL MOUNT) FIRE ALARM SPEAKER (CEILING MOUNT) Q C ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. SET -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING B WP FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) MR MULTI -VOLTAGE CONTROL RELAY SET -W SIEMENS SET -S17 -WP SIEMENS MR -201 /C AIR PRODUCTS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD 4S BOX VERIFY IN FIELD El MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD O JUNCTI❑N BOX F.B.D. F.B.O. N/A VERIFY IN FIELD A,F,F. ABOVE FINISHED FLOOR N/A N/A N/A N/A F.B.D. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A U.D.N. UNLESS OTHERWISE NOTED N/A N/A N/A N/A WP WEATHERPROOF DEVICE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A '!- A ° ts0 M� co V 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z DESCRIPTION SHOP DRAWINGS DATE 0 rn 2 C<<<< co LLL 00 w <cl-CO" O W (/)0 J15 W cc [flu) Q Q <t z wg wv I OU i a 200t' Tukwila Fire SCALE: 1/8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 9/1 1 /08 BACKROUND PLAN PROVIDED BY: .0B NUMBER: SHEET FA -01 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved } 139 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE O DUCT DETECTOR LOCATION FROM XLS CONTROL PANEL OR g ----- PREVIOUS ADDRESSABLE DEVIL y END DF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH - 1 GROUND 0 0 d- HTRI-R STATUS LED 0 N.O. t�- 0 COM 0 N.0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-R CONTROL RELAY MODULE -VI (RING AND MOUNTING DETAIL O 0 LABEL SCALE (BACKGOUND IVUSIC SHUTDOVN) NOTE 11 VOLTAGE MAX. - CURRENT MAX. - CONT. RES. MAX. - MAX. CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN. LINE SIZE - 27 VDC 3.5 mA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0.02uF 0.04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTI❑N. PREVIOUS ADDRESSABLE DEVICE + TO NEXT ADDRESSABLE r+ DEVICE _ L 0 TB1 0 0 0 0 123456 HCP TB2 65 Ak411- 4321 0 OUTLET SAMPLING TUBE INLET SAMPLING • TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL IUOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE MUSIC��}-AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING O TO NEXT ADDRESSABLE DEVICE 0.) STOP IF LAST DEVICE 1(-) FROM XLS CONTROL PANEL DR 1(+) PREVIOUS ADDRESSABLE DEVICE tH Y END OF LINE 1 DEVICE (3.6K 1/4W) SUPERVISED...........% SWITCH RELAY CONTACTS (4.OA @ 125VAC) GROUND (4.OA @ 30VDC) 0 GND N AC m 0 PAD -3 0 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - Ll LJ II 111 24K TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE 0 —0 Ln 0 0 HTRI-D STATUS LED 0 NOT USED 0 END OF -'- LINE DEVICE 3.6K 1/4V) 0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 'TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) NAC -4 NAC -3 2 NAC -2 NAC -1 DATA OUT TO PANEL L++ L DATA IN UPERVISED WITCH OVEN FAN CONTACTS NO C NC O O\AA/Q 121 END OF LINE DEVICE SUPERVISED SWITCH 0 0 GROUND NOT SHIELD FAN SHUTDOWN SCALE:NONE @ HTRI—R ©STATUS LED N.C. Cal 0 c0 0 - t FRONT VIEW 1 l NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE DEVICE LOOP 0 0 FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY C'S' CABLE) 470 OHMS 4W EOL WIIC �INPU O TEM -1 Q V) o=Z D-0 O O 0 0 O TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE NONE FROM FACP (VOICE CIRCUIT) ('V' CABLE) c) STROBE SPEAKER (+) (-) EARTH GROUND -�(+)TO NEXT DEVICE OR } >(-) STOP IF LAST DEVICE (STROBE) (STROBE) SPEAKER (+) (-) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE. OR STROBE ONLY 80" A.F.F. 4S DEEP BOX IN/ 1-1/2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE TO NEXT DEVICE ❑R END DF LINE TO NEXT DEVICE OR END DF LINE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERATING TEMPERATURE:+3) HUMIDITY: O-93% RELATIVE (HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR -> FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE rDATA IN ( )>— S1. DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT IN WHEN USED IN CONJUNCTION TH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT DEVICE > (-) DATA OUT > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID CEILING HARD LID --\ SPEAKER SUPPORT TILL.... BRIDGE - 4" SQUARE DEEP BOX - ..-.......-� WITH 1-1/2" EXTENSION CEILING MOUNTED - , xv SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTI❑N BOX MOUNTED ON CEILING, FLEX JUNCTIIIN BOX --- MOUNTED AGAINST CEILING SUPPORT / / / / / / 0 0 l TO NEXT DEVICE 0 0 CADDY BAR SMOKE DETECTOR •- SMOKE DETECTOR MOUNTING SCALE:NONE SCALE:NONE SUSPENDED ILLUMINATED CEILING DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS IREV. BY: z a2 DESCRIPTION SHOP DRAWINGS DATE 9/11/08 1<«« c0 0 LL c0 woo T <0) o Woo J � EL 2Z W EC w can d Qz� U o os LL1— oF- M (0 z Z 0 0 Z c� z CC 1 �CALE: 1 /8"=1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 9/11 /08 BACKROUND PLAN PROVIDED BY: .JOB NUMBER: SHEET Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved FA -02 J (.;)sc�OW 4 A.F.F. ��E•-. ir.31-1 031 LANDLORD) MAI L CAFE PHO WESTFJELD SOUTHCENTER ALL SCALE 118":1' FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE, FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATI❑N SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICAL CONTRACT❑R, SIEMENS HTRI-D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL, FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT, ALARM SIGNAL TO ALARM SYSTEM WILL BE SUPERVIZ❑RY, SUPERVIZED CARBON M❑N❑XIDE SENSOR AND SHUTDOWN THE OVEN TO OVEN FAN CONTROL TERMINALS DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. Copyright 2006 by Guardian Security S stems, Inc. All Ri • hts Reserved r) co 0' W o. FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS IREV. BY: z DESCRIPTION SHOP DRAWINGS Lu a— o co z CCCCC J cp LL CO W 00 T Q0) O W U)0 cn .44z W cc W co QaC ¢z� o 0� QF._ OE— M M ‘CALE: 1 /8"=1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 9/11 /08 BACKROUND PLAN PROVIDED BY: .,JOB NUMBER: 1 SHEET FA -03} RELEASE/REVISIONS ..... .. ....................... PROJECT: Panel: Date: September 11, 2009 CIRCUIT: 1 S1 Notification ApplianceCircuit Detail WESTFIELD SOUTHCENTER MALL CAFE PHO Wire Resistance 2.58 CURRENT TOTAL= 640 QTYI Device Type Alarm Current! Alarm Total 0 1SET-MC @15CD 1 641 1SET-MC @30CD !SET -MC @75CD I SET -NIC @110CD ISET-HMC-C@115CD 0 1 SET-HMC-C@177CD 0 (SET -HMC @135CD 0 (SET -HMC @185CD 3 1Z-MC@15CD 0 ,Z-MC@30CD 981 ...........��...__............ ................... _.._.. __ 0 0 1 SET-MC-CW@11 OCD 233 DEVICES=16 TOTAL mA=I 640 14 Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: CAFE PHO Date: !September 11, 2009 CIRCUIT: {SPEAKER CIRCUIT Device Type ;Alarm Current; Alarm Total Wire Size Wire Length 170.7V 1/8 1.8, 5.4 k 1 CAFE PHO WESTFIELD SOUTHCENTER ALL SCALE 1116"=1' 98 175' 350 233 3181 445E 318' 4451 0 64; 192 0 Wire Length Voltage at EOL 1 Circuit Total 0 Total Wire Resistance (R ) 98 0� (WL*2)*(R/ft) Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E ) (E= I * R) EOL Voltage (20.4 - E) 0.644 0.55 19.851 19.8451968 QTY ;Wire Resistance 2.58 CURRENT TOTAL=; 5.4 0' Voltage at EOL Circuit Total Total Wire Resistance (R ) 0 ( WL * 2 )* (R/ft) Total Device Load, Amps (I) 0.01, 2.92; 0 (Total Cct Load) VoltageDrop ( E ) (E_i. * R) __....... EOL Voltage (20.4 - E) 0.021 20.381 TOTAL mA= 5.4 20.38425684 5.4 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved REV. BY: CAFE PHO CAFE PHO FACP ADD ONS DESCRIPTION SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations w E-- Q c, o O rn Current Load: Standby: Alarm: Current Load: Standby: Alarm: 1 Device Type Qty Amps Total Amps Total Device Type Qty Amps Total Amps Total HFP-11 0.0022 0.0022 0.0023 AD2-P 2 0.0635 0.0635 0.064 0.128 Main System Board 1 0.03 0.03 0.030 0.030 HTR -R HTR -D 3 0.009600 0.0096 0.021 0.063 SET -MC @15CD SET -MC @30CD SET -MC @75CD SET -MC @110CD SET HMC-C@115CD SET HMC-C@135CD SET HMC-C@185CD 1 0.064 0.064 3 0.009600 0.0096 0.021 0.063 0.098 3 0.175 0.525 0.233 0.318 0.318 0.0849 Amps 0.254 Amps 0.445 ZR -MC @15CD ZR -MC @30CD HCP 1 0.064 0.064 Standby Current Load: 0.0849 Amps For 24 Hours = 2.038 Amp -hours 0.098 1 0.0015 Alarm Current Load: 0.254 Amps For 5 Minutes= 2.000 Amp -hours 0.03 Amps 0.683 Amps 25% Derating= 5.047 Amp -hours Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours Alarm Current Load: 0.683 Amps For 5 Minutes= 0.057 Amp -hours Total System Current Load: 5.047 Amp -hours 25% Derating= 0.972 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 8AH Total System Current Load: 0.972 Amp -hours 1 Battery Pair to be Used: 12VDC Amp -hours 7AH RELEASE/REVISIONS ..... .. ....................... PROJECT: Panel: Date: September 11, 2009 CIRCUIT: 1 S1 Notification ApplianceCircuit Detail WESTFIELD SOUTHCENTER MALL CAFE PHO Wire Resistance 2.58 CURRENT TOTAL= 640 QTYI Device Type Alarm Current! Alarm Total 0 1SET-MC @15CD 1 641 1SET-MC @30CD !SET -MC @75CD I SET -NIC @110CD ISET-HMC-C@115CD 0 1 SET-HMC-C@177CD 0 (SET -HMC @135CD 0 (SET -HMC @185CD 3 1Z-MC@15CD 0 ,Z-MC@30CD 981 ...........��...__............ ................... _.._.. __ 0 0 1 SET-MC-CW@11 OCD 233 DEVICES=16 TOTAL mA=I 640 14 Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: CAFE PHO Date: !September 11, 2009 CIRCUIT: {SPEAKER CIRCUIT Device Type ;Alarm Current; Alarm Total Wire Size Wire Length 170.7V 1/8 1.8, 5.4 k 1 CAFE PHO WESTFIELD SOUTHCENTER ALL SCALE 1116"=1' 98 175' 350 233 3181 445E 318' 4451 0 64; 192 0 Wire Length Voltage at EOL 1 Circuit Total 0 Total Wire Resistance (R ) 98 0� (WL*2)*(R/ft) Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E ) (E= I * R) EOL Voltage (20.4 - E) 0.644 0.55 19.851 19.8451968 QTY ;Wire Resistance 2.58 CURRENT TOTAL=; 5.4 0' Voltage at EOL Circuit Total Total Wire Resistance (R ) 0 ( WL * 2 )* (R/ft) Total Device Load, Amps (I) 0.01, 2.92; 0 (Total Cct Load) VoltageDrop ( E ) (E_i. * R) __....... EOL Voltage (20.4 - E) 0.021 20.381 TOTAL mA= 5.4 20.38425684 5.4 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved REV. BY: z a DESCRIPTION SHOP DRAWINGS w E-- Q c, o O rn 0 W O W cp (f) LL co CC wco .. 1«.) Q� 0- z O w p OC 0' M 2 z W W °Cw 0 Q Q azo 0 CO VEI p= F - co 0 J cr) dni W CALE: 1/8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 9/ 1 1 /08 BACKROUND PLAN PROVIDED BY: \OB NUMBER: SHEET FA -04} +,' fi ❑ '} f'1F r SLE 3 : /?•" .J 1_L 1'. ' L.E63{ r6wER 1 '1?-1T!P 1 _ 1 RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD ROD PIPE SWIVEL RING STEEL JOIST/TRUSS HANGER DETAIL NTS Model MT -3 & MT -9 Mechanical tee serves the same function as MT -1 & MT -8 but Uses a steel aleciro plated u -bolt to save space and for easier irrstallatlon In tight places. It is ideal for direct connections with sprinkler heads•and drop nipples. HOUSING: Ductile iron ASTM A536 grade 65-45-12. COATING: Zinc electroplated U - BOLT: Carbon steel SAE grade 2, zinc plated. NUT: Carbon steel ASTM A194, zinc plated. GASKET: EPDM (-300F b + 230°F) THREADS: MT -3 NPT per ANSI/ASME B1.20.1 MT -9 British standard parallel (BSP) par BS21 {� Lr iV IY7 G k�x � '� T.-4;MCGHE�P4I AL T' fES • APPRO%. WSIONT EACH 3,01.• 0,67 HOMINAt 9108 IN, MAX, 11029I910 f ,$,I.1 300 „•t[ 9121 IN. 1.19 21N iM3,ollS.I .(n. A 1 2,14 1.64 C 2 5.51) 1.21 9 3,20 . 1 9/4,11/2 1114R314 3M 1.14 2.14 1,64 356 121 125 9.87 1 11491 200 1,10 2.27 I.61 769 3.50 1,11 2.25. 1.06 11!21112 300 1.19 Z24 f 1.76 1,3.1 2,26 0.63 1 I/21204 900 1.19 2.26 1.76 3•U0 1.33 2.25 0.97 1 1/2 1 1 300 1,19 2.33 1 1,733.50 f , 1.21 7.25 1.02 2t1/2 100 1.10 2.51 1 2.01 3.91 1a4 2,76 0.N1 21214 200 1.10 •� 2.51 1 Or 3.70 1.28 ^ Trr..- - 2.25 1 0.04 --2-15.x..••0.09.. .,,i 2.29 "1""."73735-- -1 211 2 1/2 1 1/1. 300 -'- 300 • 1.19 1.19 1""'--2.9.4--4---17.1m. •'1 :1."15 3.78 2,20 • .15 1 Si 2 1Y.1 y 0/4 SCd •"'1-'"'•2.26 1.19 y�'76 2:2. 6: 1.29 1.111 i 2.9 (2.94 � '1 21121 t 300 0.19 3.66 l' 2.22 f. 2 62 I 3, l2 ' • '1.29 �T.1.5 11, 6I t nn r ,.711' h--- r8a_._.---1,33"--r---1.7:1'- ,a2:2520 I 20 1.14- 't.92 ----OW- - -1 3 0.0.1112 3 W 1.19 '' 313.n.y:1+a .�..y� ..,...30.v:><f 7V0 .IOq�-..1i9' l.lv 262 ,.:ss Al_ ----1 2.75 _t_._ { 4.26 2.25 0.23 7 -Ti t95 1 i.29 a 3,,X LEVITON ODS10-ID PIR _ O CUPANC-Y-SENSOR, OR EQUAL. (TYP.) LIGHTING PLAN :F,. SCALE: 1/4" = 1'-0" Design per NFPA 13 - Ordinary Hazard Occupancy - 130 sq ft per sprinkler All materials to be new, U.L. listed, and F.M. approved All heads to be a minimum of 6' apart and to be unobstructed by any means 4 - Add Tyco TY -FRB 3231 155° Chrome Pendents 1/2 x 1/2 6 - Add Reliable G4 -A 165° Concealed Pendents 1/2 x 1/2 te 2 - Add Tyco DS -1 QR 200° Dry Pendent 1/2 x 1/2 �. c c D Without Comments As Noted in Red • Per The Attached Letter These pians have been reviewed by The Tukwila Fire prevention Bureau for conformance with current City •I:andards. Acceptance is subject to errors and :.missions which do not authorize violations of adopted andards and ordinances. The responsibility for the iequacy of design rests totally with the designer. -dditions, deletions or revisions to these drawings after this date will void this acceptance and will require;'a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: /0- a (-0 By: 41^4..(if tUKWILA FIRE. DEPARrMtNI Please call: 575.4407 and give this job 40. and exact address for shut. down or restoration 'approvat CROW\ FIRE PROTECTION 1N CORPORATE D P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 FILE CAFE PHO 633 Southcenter Mall Space FC -8 '1 ukwila, WA 98188 PAID OCT L. ' 200: Tukwila. Fir€ DATE• /•6 -/5o J DRAWN: J jG- I SCALE:. // 1 2600 SOUTHCENTER MALL FC -8 FOOD COURT ASSOCIATED PERMITS 09-F-183 09-S-163 09-H-167 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Cafe Pho 2600 Southcenter Mall FC -8 Permit No.: 09-S-163 Date: October 21, 2009 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'/ inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 30 or more heads require hydrostatic test and system isolation if necessary. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2007 Edition. FIRE DEPARTMENT HOOD SUPPRESSION PLAN REVIEW COMMENTS Project Name: Cafe Pho 2600 Southcenter Mall FC -8 Permit No.: 09-H-167 Date: October 26, 2009 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 FILL uUPY • Nozzle heights above appliances to be per manufacturers installation guidelines. • Install splash guards between fryers and ranges/charbroilers. • Upon activation of the suppression system, the make-up air supply will shut off and the exhaust will keep running. • Type 1 hood systems shall be designed and installed to automatically activate the exhaust fan whenever cooking operations occur. The activation of the exhaust fan shall occur through an interlock with the cooking appliances, by means of heat sensors or by means of other approved methods. • Activation of the suppression system shall shunt all electrical power under the hood as well as the gas supply. • Install a "K" rated portable fire extinguisher within 30 ft. of the cooking equipment. • The hood suppression system shall be monitored by a U.L. Central Monitoring Station. • The suppression system manual pull station shall be located no closer that 10 ft. and no farther than 20 ft. from the cooking equipment and be placed at a height of 42 to 48 inches above the floor. CO co 0 0 41- a3- C • .2 " Ste, V t 0 0 w 'SrCO pp ON N N 0% rte+ N 0t CO 00m co r4 -.. i; r 1 0 co re 1 ed g cm 0 a !2 N W gi P\ 00 u 'n74 tioo cT; z� ;Ft. " v N X 5 2 u.t �• .- ••v....srw+ac-+�xvr,ss•.x�•gra•s:.•nrwet•�'s'armsu;,s�Ev7lKQP3�iW.7�7;'fi-�s"r�:-l:ridlllQl'cQi.���l�L�l4i.�. i�LJllli�iJ���LPt,(j�,'t�t�w��.-�±`r��� . GENERAL. INFORMATION The Amerex KP Series Automatic.Wet Chemical Extinguishing System is designed and has-been tested to provide fire protection for commercial cooking operations covering the hood, ducts, plenum and appliances. Amerex KP Systems are a pre-engineered type as defined in NFPA 17A.— Standard for Wet Chemical Extinguishing. Systems. It is manufactured by the Amerex Corporation, Trussville, Alabama. It is essential that all installations of the Amerex KP Series Systems be performed in compliance with this manual. Those individuals responsible for the design, installation, operation and maintenance of the Amerex KP Restaurant Fire Suppression System must be trained by Amerex and hold a current Amerex Certificate. All piping limitations, • nozzle coverages, detector placements, etc. have been proven and established through exhaustive testing by Underwriters Laboratories, Inc. Use of components other than those referenced in this manual, or installations exceeding limitations stated in this manual will void all of the Amerex KP Series System listings. . LISTINGS:. , . •. The Amerex KP Series. Is a listed, pre-engineered fire extinguishing system. .The KP system is• listed with Underwriters Laboratories, Inc. — USA per UL 300 fire. test specification; Underwriters' Laboratories of Canada, Inc.. per ULC/ORD 1254.6=1995*and Loss Prevention Certification Board - UK per•LPS 1223 rev. . B: Testing.required for listings•underthese standards involve live fire tests under specific conditions involving commercial kitchen hoods, ducts and •appliances. Each test fire Is allowed to reach its maximum intensity befpie agent is discharged. Each test was repeated using both maximum and minimum piping, variations in agent storage cylinder pressure to simulate maximum and minimum temperature ratings. Duct fire tests were extinguished with fans .off and fans on; dampers open and closed. Splash.tests for various appliances were conducted to assure that discharge of the agent would not cause excessive splashing of hot grease to.provide greater employee safety during commercial cooking operations. • . UL Standard 300 introduces a series of tests by specifically addressing the use of high efficiency fryers, ranges, woks and the unique fire extinguishing chaltenges that these appliances present. . DESIGN: . The Amerex KP Series Pre -Engineered System consists of mechanical and electrical oomponents to be installed by an. Authorized Factory Trained and Certified • Amerex KP Systems distributor, • The system . Is 'composed of an. agent cylinder/discharge valve ..charged with. Amerex KP Liquid Agent and a Mechanical Release Module (MRM) or Pneumatic Release Module .(PRM). •The quantity of detectors, fusible links, nozzles, comer pulleys, pulley tees and manual pull .stations will vary depending on kitchen design. • The- system operates either automatically if actuated by a detector or manually If actuated by a manual pull station. Upon system operation, energy sources for the cooking 'appliances are required to be shut off • immediately. Electrical shutdown devices or suitable gas yalves are referenced in. this manual. Other equipment such as audible/visual signaling devices can be added where required.• The Amerex. KP System suppresses fire in commercial cooking .equipment by spraying KP liquid agent in. a predetermined manner onto cooking appliances 'and into exhaust ducts, filters and plenum areas. The primary Means of fire suppression is either by saponification of surface grease or by cooling .the surface of oils and hot metal surfaces With fine droplets of agent, reducing • the temperature of the oil and appliance below the auto -ignition point. • • . Upon system discharge, the exhaust fans should lie left on to aid In dispersal of the liquid suppressant that results in cooling the plenum and duct. Any integral make-up or supply air should be automatically shut off along with all cooking appliances. Some local Authorities Having Jurisdiction October require exhaust fans to be shut down by the fire suppression system. Check local fire codes and requirements in the specific area that the system is being installed. • • The Amerex KP System agent storage cylinders and cartridge shall not be installed in environments. below 32° F or above 120° F (0° C to 49° C). DUCT PROTECTION LIMITATIONS — TWO NOZZLES (2 x P/N 16416) Two Amerex duct nozzles (P/N 16416) will protect ducts with a perimeter of 51 inches to 82 inches (129.5 — 208.3 cm) or a maximum diameter of 26 inches (66 cm). To correctly position the nozzles a rectangular duct should be divided along its longest side into four equal distances. A circular duct should be divided along a centerline into four equal distances. 'A Nozzle should be placed at one quarter of the duct's width (or diameter) with both nozzles on .the centerline,. paced 2-8 inches (5.08 - 20.3 cm) into the duct opening and aimed at the center of the cross section of the. duct. Each nozzle has one flow point. NOTE: In no case can the diagonal dimension of each module exceed 18.8 inches (46 cm). DUCT PROTECTION LIMITATIONS 100 IN. PERIMETER TWO —1'/: FLOW POINT NOZZLES (PIN 11983) The Amerex solid fuel appliance/duct nozzle .(PM 11983) is listed to protect a restaurant cooking exhaustduct of unlimited length and up to 100 perimeter inches (254 cm) or 32 inch diameter (812 cm) using two nozzles. The nozzles total three flow points and to properly position the nozzles, a rectangular duct should be divided along its longest side into four equal distances. A circular duct should be divided along its center line into four equal distances: The 1/4 nozzles are to be placed at one quarter and three quarters position of the duct width (or diameter) with both nozzles on the center line, placed 2 - 8 inches (5.08 — 20.3 cm) into the duct opening and aimed straight up in a vertically run duct. NOTE: In no case can the diagonal dimension of the duct exceed 37.2 inches (94.4 cm) without adding additional duct nozzles. NOTE: The use of one duct nozzle PM 11983 is permitted for duct 50 perimeter inches or Tess fn the same manner as duct nozzle 16416. 1/4 1/2 k2,1 V PLENUM. PROTECTION PLENUM PROTECTION LIMITATIONS — SINGLE FLOW POINT NOZZLE (P/N 11982) The Amerex appliance, plenum nozzle (P/N 11982) is capable of protecting plenums up to 10 feet (3.048m) long with either a single inclined filter bank or a "V" bank filter arrangement. The filter height cannot exceed 24 inches (60.96 cm). Each plenum- nozzle uses one flow point The nozzle must be .positioned 4 inches (10.16) maximum from the wall; aimed horizontally and positioned down 113 the filter height from the top of the filter. • PLENUM PROTECTION — MULTIPLE NOZZLES Plenums exceeding :10 feet (3.048 ni). in length may be protected by using multiple plenum nozzles. Each nozzle must be protecting an area of no more than 10 feet in length. Nozzles may be positioned facing each other or facing the 'same direction as long. as the entire plenum area is being covered. Nozzles may not face in opposite directions from a common tee. SINGLE BURNER RANGE PROTECTION ONE — 1/2 FLOW POINT NOZZLE (P/N 11984) The Amerex half (1/2) flow point nozzle (P/N 11984) will protect a single burner with a surface area of 18" x 18" (46 x 46 cm). The nozzles must be located on the perimeter. The nozzle is aimed at to point 7" above cm)e aboveve -the bumers surface. center of the. bumer. SINGLE BURNER RANGE PROTECTION — OVERHEAD ONE - 1/2 FLOW POINT NOZZLE (P/N 11984) The Amerex half (Y:) flow point nozzle (P/N 11984) will protect a single bumer witha surface area of 18" x 18" (46 x 46 cm). The nozzles must be located directly above the center of the bumer and 24 to 42" (61 - 107 cm) above the bumers surface. The nozzle is aimed at the center of the bumer. TWO BURNER RANGE PROTECTION — SINGLE FLOW POINT NOZZLE (P/N 11982) The Amerex appliance, plenum nozzle (P/N 11982) has one flowpoint and will protect a range surface area of. 14" x 28" (36 x 71 cm). The center to center distance between burners must not exceed .14" (36 cm). The nozzle must be located 44 - 48" (112 - 122 cm) above the range surface and centered between the two bumers. The range surface area is measured from the outside of the burner to the outside of the bumer. NOTE: Maximum and minimum heights must be measured from the tip of nozzle to the surface of the appliance. r Hi 48 in. II CO d �7 in u) Tt to LO d 4 • d si' 4 n .l 05 I • • • Protection is not !knifed to the Items listed on this chart Modulizing larger appliances is an acceptable practice. See your Amerex KP Manuel for additional Cnfornrat/on. r 'C n y = C CO CO C CO CO G ...4z 't- e- C O N C v Nt c CO 'CO C CO e- C O ep C O CO C O CO c I N- c O e- c O c- C CO !"''t C CO -.J C O " C v C D v C •> .Unlimited 'C3. C > . —ems Length •C CA t- im M ko ap. CO N C COCO `- C N G d' N C t1' .N 4-7 depth I C CO C). C N 48 In. \ CO C •C N 24 in. N CO H CO • H \ CO Length O L m E 4 C CO T' ' • C N co .. 'al O) N: p) • C) C. O e- C T' e- • C N e- • C 'I'ccy N 1 C O CO C O CO C O CO C. • O C d' N G d' N C d' N C , . NN C d- = et 1 1 m ?C ) 2 *CC'al E C O tp C 00 e- • •• QO LL Q. N . N C 4 \ r' 1- N e- e- N Cy- e- c- e• ' - e- O O Ll. 0.. e- . d C LL D. e- e- cri co Q d 11 0 13729 .0) N f� M e- CO •e- *a CV 11984 N co co i r • N CO O e- • r 14178 N co co r i Griddle • . I • • 11982 Griddle .. • 13729 Griddle• 14178 Upright Broiler • 2-11984 Charbroiler (Lava Rock) • 11983 Charbroiler (Gas Radiant & Electric Radiant) I 11982 • .! Natural & Mesquite Charcoal Charbroiler 11983 II Mesquite Chips & Chunks Charbroiler • -- 11983 Mesquite Log Charbroiler • 11983 Plenum- • Nozzle P/N N CO CA r. c' • 4 i C w c. N CCI C u) z , 0.. d' Ti 0 • 44 o 0 • CO e�-• .CO e- ' CO = Cr) Q) tt: i Circular _ 16416 I Rectangular 2-11983 .� 0) c- �. CV • 1 tU 03 0 Cti 1 Q a Q • ' j Deep'Fai< Fryer–without Drip Pan Deep Fat Fryer – with Drip Pan RI Deep Fat Fryer – with Drip Pan Low Proximity Raroe – Single Burner Range ;Two Sumer II Range – Two Burner Range – Four Burner • -se .0 4 a KP DISTRIBUTION PIPING DESIGN LIMITS FOR ALL CYLINDER SIZES When designing a KP system to protect a kitchen containing a Fryer, Wok or Range, the following MINIMUM TOTAL SYSTEM PIPING must be used in accordance with the chart below: MINIMUM PIPING REQUIREMENTS MINIMUM MINIMUM TOTAL MINIMUM FLOW APPLIANCE LINEAR FEET EQUIVALENT FEET POINTS PER SYSTEM Wok 6.5 9 7 10 22.1 16.4 6 4 SUPPLY LINE LIMITATIONS: All pipe and fittings running from the distributor block or fill discharge fitting to thefirs CYLINDER MAXIMUM LINEAR MAX. QTY. MAX. QTY. �vy MAX. QTY. FLOW POINTS PIPE SIZE FEET OF PIPE TEES ELBOWS BUSHINGS KP275 - 8 3/8 20 1 MAX. QTY. ELBOWS ` 5 . ' - 0 KP375 -11 3/8 OR 1/2 25 . .1 „ - 5 3/8 OR 1/2 1 KP475 -14 1/2 ,25 1 KP475 -14 5 , ' - 2 KP600 -18 . 1/2 25 1 . AS NOTED 5 50' 3/8" PIPE ONLY ., 2 2-KP375 - 22 - 1/2 30 2 40 7 18 2 : 1. Use 3/8" supply line only when all piping is to be 3/8" pipe. 2. The supply line has a maximum vertical rise above the distributor of 10 feet. SUPPLY BRANCH LINE (including last nozzle branch) LIMITATIONS: All pipe and fittings leaving the first splitting tee in the system and ending with the last nozzle in the last branch line. While the last nozzle branch is included in the piping limitations for the supply branch line, the limitation (pipe size and maximum length) for nozzle branch lines apply to this portion of the supply branch line. CYLINDER FLOW POINTS PIPE SIZE MAX. FEET OF PIPE Si RAIGHT MAX. FEET OF PIPE SPLIT MAX. QTY. TEES MAX. QTY. ELBOWS MAX. QTY. REDUCING BUSHINGS KP275 - 8 3/8 20 25 7 8 0 KP375 -11 3/8 OR 1/2 27 30 10 8 2 KP475 -14 3/8 27 30 12 8 2 KP600 - 18 AS NOTED 33' OF 3/8" OR 1/2" 50' 3/8" PIPE ONLY 14 8 2 2-KP375-22 1/2* 40 45 18 8 0 . 1. In a single 3.75 Gallon Straight Pipe System, 5of pipe may be transferred from the supply line to the supply branch line. *2. The use of 3/8" pipe with two manifold KP375s is only permitted when the SUPPLY UNE length is equal to or less than 20'. NOZZLE BRANCH LINE LIMITATIONS: All pipe and fittings leading from the supply branch tee to a system nozzle. • `p - TOTAL LINEAR MAX. QTY. MAX. QTY. FLOW POINTS PIPE SIZE FEET OF PIPE TEES ELBOWS MAX. QTY. BUSHINGS KP275-8 3/8 32 - 5 10 0 KP375 -11 3/8 OR 1/2 32 8 12 11 KP475 - 14 3/8 32 10 15 0 KP600 - 18 3/8 32 11 18 15 2-KP375 - 22 3/8 32 18 18 20 MAX. PER NOZZLE BRANCH 7 3 6 4 GENERAL SYSTEM LIMITATIONS: 1. No %2" pipe nozzle branches shorter than 12" long. 2. Nozzle types may not be mixed on any nozzle branch line and a maximum of 4 flow points. 3. The discharge fitting, distributor and distribution hose are not to be included in any calculations. 4. No mixing of pipe sizes is allowed within pipe categories. Example: if one nozzle branch is to be W' pipe then all must be'/" pipe. Y2" pipe for nozzle branch lines is allowed only in an 11 flow point system. 5. Duct nozzle has a maximum vertical rise above the supply branch line of 4'0". ACC ?TED 0 O As sa' Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards. Acceptance Is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings after this date will void this acceptance and will require,a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: 10 F - c 9 By: Y1 ( 1 UKWILA FIRE DEPARTIIAFi11 Please call: 575.4407 and give this job No. 4C1— if -/ir7 and exact address for shute -town or restoration appro m FILE COPY CAFE HO FIRE LARM SYSTEM Tt KWILA, ' ASHINGT SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET NUMBER SHEET TITLE FA -01 SYSTEM INFORMATION FA -02 TYPICAL DETAILS - WIRING AND MOUNTING FA -03 FIRE ALARM SYSTEM FLOOR PLAN FA -04 SYSTEM CALCULATIONS (GENERAL), RISER, SITE PLAN 4.11 6P 15/ Without Comments As Noted in Red Q Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted aandards and ordinances. The responsitiiity for the adequacy of design rests totally with the designer. Additions:, deletions or revisions to these drawings after this date will void this acceptance and will requirea resubmittal of revised drawings for sui equent approval Final acceptance is subject to i.l,ld i:r;st and inspection by The Tukwila Fire Prevention Bureau. Date:/I,(2.-O9 By:, /414,1,5-1 TUKWILA FIRE DEPARTMEM Please call: 875.4407 • and give this job NO, Oq-F-183 and exact address for shun av an or restoration . approval, NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems./ Failure of test willresult in a Re -inspection Fee and termination of the testing, WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDIO TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE TWO 600V #12 AWG THHN/THWN TWO 600V #14 AWG THHN/THWN TWISTED TWO CONDUCTOR 300V #18 AWG FPL TW CABLE CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF CONDUIT SIZE MAXIMUM F 1/2" .12 SQUARE 3/4" .21 SQUARE 1" .34 SQUARE 1-1/4" .60 SQUARE 1-1/2" .82 SQUARE 2 1.34 SQUARE FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM DIMENSIONS AREA .244 O.D. .0467 .210 0.0. .0346 .156 O.D. .0191 FROM THE TABLE FILL DIMENSION FROM THE WIRE. LL NCH NCH NCH NCH NCH INCH N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (LE., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 3 3 2 2 1 1 2 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP a INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S DEEP VERIFY IN FIELD 0 DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD C)/CONVENTIONAL CARBON MONOXIDE DETECTOR CODET 12-24 SIEMENS 4S DEEP BOX ® SMOKE DETECTOR (ADDRESSABLE -PHOTO) HFP-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING 12" A.F.F. INSTALLED BY OTHERS CEILING ® DUCT SMOKE p DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING 8cc Ec FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING ▪ c FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING FIRE ALARM © STROBE (WALL MOUNT) FIRE ALARM SPEAKER (CEILING MOUNT) Q C ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. SET -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING B WP FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) MR MULTI -VOLTAGE CONTROL RELAY SET -W SIEMENS SET -S17 -WP SIEMENS MR -201 /C AIR PRODUCTS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD 4S BOX VERIFY IN FIELD El MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD O JUNCTI❑N BOX F.B.D. F.B.O. N/A VERIFY IN FIELD A,F,F. ABOVE FINISHED FLOOR N/A N/A N/A N/A F.B.D. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A U.D.N. UNLESS OTHERWISE NOTED N/A N/A N/A N/A WP WEATHERPROOF DEVICE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A '!- A ° ts0 M� co V 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z DESCRIPTION SHOP DRAWINGS DATE 0 rn 2 C<<<< co LLL 00 w <cl-CO" O W (/)0 J15 W cc [flu) Q Q <t z wg wv I OU i a 200t' Tukwila Fire SCALE: 1/8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 9/1 1 /08 BACKROUND PLAN PROVIDED BY: .0B NUMBER: SHEET FA -01 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved } 139 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE O DUCT DETECTOR LOCATION FROM XLS CONTROL PANEL OR g ----- PREVIOUS ADDRESSABLE DEVIL y END DF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH - 1 GROUND 0 0 d- HTRI-R STATUS LED 0 N.O. t�- 0 COM 0 N.0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-R CONTROL RELAY MODULE -VI (RING AND MOUNTING DETAIL O 0 LABEL SCALE (BACKGOUND IVUSIC SHUTDOVN) NOTE 11 VOLTAGE MAX. - CURRENT MAX. - CONT. RES. MAX. - MAX. CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN. LINE SIZE - 27 VDC 3.5 mA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0.02uF 0.04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTI❑N. PREVIOUS ADDRESSABLE DEVICE + TO NEXT ADDRESSABLE r+ DEVICE _ L 0 TB1 0 0 0 0 123456 HCP TB2 65 Ak411- 4321 0 OUTLET SAMPLING TUBE INLET SAMPLING • TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL IUOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE MUSIC��}-AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING O TO NEXT ADDRESSABLE DEVICE 0.) STOP IF LAST DEVICE 1(-) FROM XLS CONTROL PANEL DR 1(+) PREVIOUS ADDRESSABLE DEVICE tH Y END OF LINE 1 DEVICE (3.6K 1/4W) SUPERVISED...........% SWITCH RELAY CONTACTS (4.OA @ 125VAC) GROUND (4.OA @ 30VDC) 0 GND N AC m 0 PAD -3 0 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - Ll LJ II 111 24K TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE 0 —0 Ln 0 0 HTRI-D STATUS LED 0 NOT USED 0 END OF -'- LINE DEVICE 3.6K 1/4V) 0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 'TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) NAC -4 NAC -3 2 NAC -2 NAC -1 DATA OUT TO PANEL L++ L DATA IN UPERVISED WITCH OVEN FAN CONTACTS NO C NC O O\AA/Q 121 END OF LINE DEVICE SUPERVISED SWITCH 0 0 GROUND NOT SHIELD FAN SHUTDOWN SCALE:NONE @ HTRI—R ©STATUS LED N.C. Cal 0 c0 0 - t FRONT VIEW 1 l NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE DEVICE LOOP 0 0 FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY C'S' CABLE) 470 OHMS 4W EOL WIIC �INPU O TEM -1 Q V) o=Z D-0 O O 0 0 O TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE NONE FROM FACP (VOICE CIRCUIT) ('V' CABLE) c) STROBE SPEAKER (+) (-) EARTH GROUND -�(+)TO NEXT DEVICE OR } >(-) STOP IF LAST DEVICE (STROBE) (STROBE) SPEAKER (+) (-) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE. OR STROBE ONLY 80" A.F.F. 4S DEEP BOX IN/ 1-1/2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE TO NEXT DEVICE ❑R END DF LINE TO NEXT DEVICE OR END DF LINE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERATING TEMPERATURE:+3) HUMIDITY: O-93% RELATIVE (HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR -> FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE rDATA IN ( )>— S1. DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT IN WHEN USED IN CONJUNCTION TH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT DEVICE > (-) DATA OUT > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID CEILING HARD LID --\ SPEAKER SUPPORT TILL.... BRIDGE - 4" SQUARE DEEP BOX - ..-.......-� WITH 1-1/2" EXTENSION CEILING MOUNTED - , xv SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTI❑N BOX MOUNTED ON CEILING, FLEX JUNCTIIIN BOX --- MOUNTED AGAINST CEILING SUPPORT / / / / / / 0 0 l TO NEXT DEVICE 0 0 CADDY BAR SMOKE DETECTOR •- SMOKE DETECTOR MOUNTING SCALE:NONE SCALE:NONE SUSPENDED ILLUMINATED CEILING DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS IREV. BY: z a2 DESCRIPTION SHOP DRAWINGS DATE 9/11/08 1<«« c0 0 LL c0 woo T <0) o Woo J � EL 2Z W EC w can d Qz� U o os LL1— oF- M (0 z Z 0 0 Z c� z CC 1 �CALE: 1 /8"=1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 9/11 /08 BACKROUND PLAN PROVIDED BY: .JOB NUMBER: SHEET Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved FA -02 J (.;)sc�OW 4 A.F.F. ��E•-. ir.31-1 031 LANDLORD) MAI L CAFE PHO WESTFJELD SOUTHCENTER ALL SCALE 118":1' FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE, FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATI❑N SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICAL CONTRACT❑R, SIEMENS HTRI-D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL, FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT, ALARM SIGNAL TO ALARM SYSTEM WILL BE SUPERVIZ❑RY, SUPERVIZED CARBON M❑N❑XIDE SENSOR AND SHUTDOWN THE OVEN TO OVEN FAN CONTROL TERMINALS DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. Copyright 2006 by Guardian Security S stems, Inc. All Ri • hts Reserved r) co 0' W o. FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS IREV. BY: z DESCRIPTION SHOP DRAWINGS Lu a— o co z CCCCC J cp LL CO W 00 T Q0) O W U)0 cn .44z W cc W co QaC ¢z� o 0� QF._ OE— M M ‘CALE: 1 /8"=1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 9/11 /08 BACKROUND PLAN PROVIDED BY: .,JOB NUMBER: 1 SHEET FA -03} RELEASE/REVISIONS ..... .. ....................... PROJECT: Panel: Date: September 11, 2009 CIRCUIT: 1 S1 Notification ApplianceCircuit Detail WESTFIELD SOUTHCENTER MALL CAFE PHO Wire Resistance 2.58 CURRENT TOTAL= 640 QTYI Device Type Alarm Current! Alarm Total 0 1SET-MC @15CD 1 641 1SET-MC @30CD !SET -MC @75CD I SET -NIC @110CD ISET-HMC-C@115CD 0 1 SET-HMC-C@177CD 0 (SET -HMC @135CD 0 (SET -HMC @185CD 3 1Z-MC@15CD 0 ,Z-MC@30CD 981 ...........��...__............ ................... _.._.. __ 0 0 1 SET-MC-CW@11 OCD 233 DEVICES=16 TOTAL mA=I 640 14 Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: CAFE PHO Date: !September 11, 2009 CIRCUIT: {SPEAKER CIRCUIT Device Type ;Alarm Current; Alarm Total Wire Size Wire Length 170.7V 1/8 1.8, 5.4 k 1 CAFE PHO WESTFIELD SOUTHCENTER ALL SCALE 1116"=1' 98 175' 350 233 3181 445E 318' 4451 0 64; 192 0 Wire Length Voltage at EOL 1 Circuit Total 0 Total Wire Resistance (R ) 98 0� (WL*2)*(R/ft) Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E ) (E= I * R) EOL Voltage (20.4 - E) 0.644 0.55 19.851 19.8451968 QTY ;Wire Resistance 2.58 CURRENT TOTAL=; 5.4 0' Voltage at EOL Circuit Total Total Wire Resistance (R ) 0 ( WL * 2 )* (R/ft) Total Device Load, Amps (I) 0.01, 2.92; 0 (Total Cct Load) VoltageDrop ( E ) (E_i. * R) __....... EOL Voltage (20.4 - E) 0.021 20.381 TOTAL mA= 5.4 20.38425684 5.4 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved REV. BY: CAFE PHO CAFE PHO FACP ADD ONS DESCRIPTION SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations w E-- Q c, o O rn Current Load: Standby: Alarm: Current Load: Standby: Alarm: 1 Device Type Qty Amps Total Amps Total Device Type Qty Amps Total Amps Total HFP-11 0.0022 0.0022 0.0023 AD2-P 2 0.0635 0.0635 0.064 0.128 Main System Board 1 0.03 0.03 0.030 0.030 HTR -R HTR -D 3 0.009600 0.0096 0.021 0.063 SET -MC @15CD SET -MC @30CD SET -MC @75CD SET -MC @110CD SET HMC-C@115CD SET HMC-C@135CD SET HMC-C@185CD 1 0.064 0.064 3 0.009600 0.0096 0.021 0.063 0.098 3 0.175 0.525 0.233 0.318 0.318 0.0849 Amps 0.254 Amps 0.445 ZR -MC @15CD ZR -MC @30CD HCP 1 0.064 0.064 Standby Current Load: 0.0849 Amps For 24 Hours = 2.038 Amp -hours 0.098 1 0.0015 Alarm Current Load: 0.254 Amps For 5 Minutes= 2.000 Amp -hours 0.03 Amps 0.683 Amps 25% Derating= 5.047 Amp -hours Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours Alarm Current Load: 0.683 Amps For 5 Minutes= 0.057 Amp -hours Total System Current Load: 5.047 Amp -hours 25% Derating= 0.972 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 8AH Total System Current Load: 0.972 Amp -hours 1 Battery Pair to be Used: 12VDC Amp -hours 7AH RELEASE/REVISIONS ..... .. ....................... PROJECT: Panel: Date: September 11, 2009 CIRCUIT: 1 S1 Notification ApplianceCircuit Detail WESTFIELD SOUTHCENTER MALL CAFE PHO Wire Resistance 2.58 CURRENT TOTAL= 640 QTYI Device Type Alarm Current! Alarm Total 0 1SET-MC @15CD 1 641 1SET-MC @30CD !SET -MC @75CD I SET -NIC @110CD ISET-HMC-C@115CD 0 1 SET-HMC-C@177CD 0 (SET -HMC @135CD 0 (SET -HMC @185CD 3 1Z-MC@15CD 0 ,Z-MC@30CD 981 ...........��...__............ ................... _.._.. __ 0 0 1 SET-MC-CW@11 OCD 233 DEVICES=16 TOTAL mA=I 640 14 Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: CAFE PHO Date: !September 11, 2009 CIRCUIT: {SPEAKER CIRCUIT Device Type ;Alarm Current; Alarm Total Wire Size Wire Length 170.7V 1/8 1.8, 5.4 k 1 CAFE PHO WESTFIELD SOUTHCENTER ALL SCALE 1116"=1' 98 175' 350 233 3181 445E 318' 4451 0 64; 192 0 Wire Length Voltage at EOL 1 Circuit Total 0 Total Wire Resistance (R ) 98 0� (WL*2)*(R/ft) Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E ) (E= I * R) EOL Voltage (20.4 - E) 0.644 0.55 19.851 19.8451968 QTY ;Wire Resistance 2.58 CURRENT TOTAL=; 5.4 0' Voltage at EOL Circuit Total Total Wire Resistance (R ) 0 ( WL * 2 )* (R/ft) Total Device Load, Amps (I) 0.01, 2.92; 0 (Total Cct Load) VoltageDrop ( E ) (E_i. * R) __....... EOL Voltage (20.4 - E) 0.021 20.381 TOTAL mA= 5.4 20.38425684 5.4 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved REV. BY: z a DESCRIPTION SHOP DRAWINGS w E-- Q c, o O rn 0 W O W cp (f) LL co CC wco .. 1«.) Q� 0- z O w p OC 0' M 2 z W W °Cw 0 Q Q azo 0 CO VEI p= F - co 0 J cr) dni W CALE: 1/8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 9/ 1 1 /08 BACKROUND PLAN PROVIDED BY: \OB NUMBER: SHEET FA -04} +,' fi ❑ '} f'1F r SLE 3 : /?•" .J 1_L 1'. ' L.E63{ r6wER 1 '1?-1T!P 1 _ 1 RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD ROD PIPE SWIVEL RING STEEL JOIST/TRUSS HANGER DETAIL NTS Model MT -3 & MT -9 Mechanical tee serves the same function as MT -1 & MT -8 but Uses a steel aleciro plated u -bolt to save space and for easier irrstallatlon In tight places. It is ideal for direct connections with sprinkler heads•and drop nipples. HOUSING: Ductile iron ASTM A536 grade 65-45-12. COATING: Zinc electroplated U - BOLT: Carbon steel SAE grade 2, zinc plated. NUT: Carbon steel ASTM A194, zinc plated. GASKET: EPDM (-300F b + 230°F) THREADS: MT -3 NPT per ANSI/ASME B1.20.1 MT -9 British standard parallel (BSP) par BS21 {� Lr iV IY7 G k�x � '� T.-4;MCGHE�P4I AL T' fES • APPRO%. WSIONT EACH 3,01.• 0,67 HOMINAt 9108 IN, MAX, 11029I910 f ,$,I.1 300 „•t[ 9121 IN. 1.19 21N iM3,ollS.I .(n. A 1 2,14 1.64 C 2 5.51) 1.21 9 3,20 . 1 9/4,11/2 1114R314 3M 1.14 2.14 1,64 356 121 125 9.87 1 11491 200 1,10 2.27 I.61 769 3.50 1,11 2.25. 1.06 11!21112 300 1.19 Z24 f 1.76 1,3.1 2,26 0.63 1 I/21204 900 1.19 2.26 1.76 3•U0 1.33 2.25 0.97 1 1/2 1 1 300 1,19 2.33 1 1,733.50 f , 1.21 7.25 1.02 2t1/2 100 1.10 2.51 1 2.01 3.91 1a4 2,76 0.N1 21214 200 1.10 •� 2.51 1 Or 3.70 1.28 ^ Trr..- - 2.25 1 0.04 --2-15.x..••0.09.. .,,i 2.29 "1""."73735-- -1 211 2 1/2 1 1/1. 300 -'- 300 • 1.19 1.19 1""'--2.9.4--4---17.1m. •'1 :1."15 3.78 2,20 • .15 1 Si 2 1Y.1 y 0/4 SCd •"'1-'"'•2.26 1.19 y�'76 2:2. 6: 1.29 1.111 i 2.9 (2.94 � '1 21121 t 300 0.19 3.66 l' 2.22 f. 2 62 I 3, l2 ' • '1.29 �T.1.5 11, 6I t nn r ,.711' h--- r8a_._.---1,33"--r---1.7:1'- ,a2:2520 I 20 1.14- 't.92 ----OW- - -1 3 0.0.1112 3 W 1.19 '' 313.n.y:1+a .�..y� ..,...30.v:><f 7V0 .IOq�-..1i9' l.lv 262 ,.:ss Al_ ----1 2.75 _t_._ { 4.26 2.25 0.23 7 -Ti t95 1 i.29 a 3,,X LEVITON ODS10-ID PIR _ O CUPANC-Y-SENSOR, OR EQUAL. (TYP.) LIGHTING PLAN :F,. SCALE: 1/4" = 1'-0" Design per NFPA 13 - Ordinary Hazard Occupancy - 130 sq ft per sprinkler All materials to be new, U.L. listed, and F.M. approved All heads to be a minimum of 6' apart and to be unobstructed by any means 4 - Add Tyco TY -FRB 3231 155° Chrome Pendents 1/2 x 1/2 6 - Add Reliable G4 -A 165° Concealed Pendents 1/2 x 1/2 te 2 - Add Tyco DS -1 QR 200° Dry Pendent 1/2 x 1/2 �. c c D Without Comments As Noted in Red • Per The Attached Letter These pians have been reviewed by The Tukwila Fire prevention Bureau for conformance with current City •I:andards. Acceptance is subject to errors and :.missions which do not authorize violations of adopted andards and ordinances. The responsibility for the iequacy of design rests totally with the designer. -dditions, deletions or revisions to these drawings after this date will void this acceptance and will require;'a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: /0- a (-0 By: 41^4..(if tUKWILA FIRE. DEPARrMtNI Please call: 575.4407 and give this job 40. and exact address for shut. down or restoration 'approvat CROW\ FIRE PROTECTION 1N CORPORATE D P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 FILE CAFE PHO 633 Southcenter Mall Space FC -8 '1 ukwila, WA 98188 PAID OCT L. ' 200: Tukwila. Fir€ DATE• /•6 -/5o J DRAWN: J jG- I SCALE:. // 1