HomeMy WebLinkAboutPP - 2600 SOUTHCENTER MALL FC-9 - CHARLEY'S GRILLED SUBS - PERMITS AND PLANS2600 SOUTHCENTER MALL FC -9 FOOD COURT ASSOCIATED PERMITS 08-F-350 08-S-397 08-H-383 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: CHARLEY'S GRILLED SUBS 2600 Southcenter Mall FC -9 Permit No.: 08-S397 Date: July 29, 2008 Reviewer: Steve Kohler Fire Inspector/Plan Review (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. CITY OF TUKWILA Community Development Department Public Works Department Permit Center 6300 Southcenter Blvd., Suite 100 Tukwila, WA 98188 hup://www.citultwila.wa.us Building Permit No. Mechanical Permit No. Plumbing/Gas Permit No. Public Works Permit No. Project No. (For office use only) Applications and plans must be complete in order to be accepted for plan review. Applications will not be accepted through the mail or by fax. **Please Print* * SITE LOCATION King Co Assessor's Tax No.: Site Address: QLP OO 80vcr 4Geylt'1Y r/10.,1 1 Suite Number: Floor: Tenant Name: (41A. i. C L l I✓l S 8 LOOS New Tenant: I Yes ❑ ..No Property Owners Name: Mailing Address: City State Zip CONTACT PERSON - who do we contact when your permit is ready to be issued Name: Jai nt€)4 YYl i call exte - Day Telephone: (&O ID) x-0710 - Cd-1-0 Mailing Address: j o L OO 1 a . S . 5L2i'X t -u, u3Pt q61 Og City E -Mail Address: V- is e—y . fl 11 Ghe.Y►GY e r+hnod.(.omFax Number: (c4019) Il01 " a(D 0+ State Zip GENERAL CONTRACTOR INFORMATION - Five 5 u p press i on stew - (Contractor Information for Mechanical (pg 4) for Plumbing and Gas Piping (pg 5)) Company Name: Q -- HOc j (lrlof Duet ServlGras Mailing Address: 1Q100 1 a N' Qlu-e . S • Beatru to A 9 8 1 Q Ai City State Zip Contact Person: V.Y. iSteXI mC.h Day Telephone: (0)019 'j 19 — Orid-to E -Mail Address: Fax Number: (a0 CD ) 1-(99-- - Sa) 0 la/ 1/aoo1 Contractor Registration Number: t O 0 j *- d $ 86iL. Expiration Date: ARCHITECT OF RECORD - All plans must be wet stamped by Architect of Record Company Name: Mailing Address: city �StatP Contact Person: Day Telephone: E -Mail Address: Fax Number: ENGINEER OF RECORD - All plans must be wet stamped by Engineer of Record PAI D Company Name: Mailing Address: JUL 17 2008 ,(9/' City Contact Person: Day TelephoneTukwila3/ E -Mail Address: Fax Number: Q Apphcanons\Fofms-Applications On Lm&3-2006 - Permit Applicanon.doc Revised 9-2006 bh Zip ts(fr) Page 1 of 6 y BUILDING PERMIT INFORMATION — 206-431-3670 Valuation of Project (contractor's bid price): $ a �{' ��451 . C O Existing Building Valuation: $ Scope of Work (please provide detailed information): "3/1St- a 0.x'10 n. O - 0.k //VA StA k 3.6 C(0L110n ire SUppresSion ov -t12x,n 36 c �necS• Will there be new rack storage? ❑ Yes ❑.. No If yes, a separate permit and plan submittal will be required. Provide All Building Areas in Square Footage Below PLANNING DIVISION: Single family building footprint (area of the foundation of all structures, plus any decks over 18 inches and overhangs greater than 18 inches) *For an Accessory dwelling, provide the following: Lot Area (sq ft): Floor area of principal dwelling: Floor area of accessory dwelling: *Provide documentation that shows that the principal owner lives in one of the dwellings as his or her primary residence. Number of Parking Stalls Provided: Standard: Compact: Handicap: Will there be a change in use? ❑ Yes 0 No If "yes", explain: FIRE PROTECTION/HAZARDOUS MATERIALS: ❑ Sprinklers 0 Automatic Fire Alarm 0 None 114 Other (specify) 1Vt c, up p reSSt o h Will there be storage or use of flammable, combustible or hazardous materials in the building? ❑ Yes 0 No If `yes', attach List of materials and storage locations on a separate 8-1/2"x 11 "paper including quantities and Material Safety Data Sheets. SEPTIC SYSTEM ❑ On-site Septic System - For on-site septic system, provide 2 copies of a current septic design approved by King County Health Department. Q:Wpplicat ons\Fonns-Applications On LineO-2006 - Pemut Application.doc Revised. 9-2006 bh Page 2 of 6 Existing Interior Remodel Addition to Existing Structure New Type of Construction per IBC Type of Occupancy per IBC 15t Floor pia Floor 3rd Floor Floors thru Basement Accessory Structure* Attached Garage Detached Garage Attached Carport Detached Carport Covered Deck Uncovered Deck PLANNING DIVISION: Single family building footprint (area of the foundation of all structures, plus any decks over 18 inches and overhangs greater than 18 inches) *For an Accessory dwelling, provide the following: Lot Area (sq ft): Floor area of principal dwelling: Floor area of accessory dwelling: *Provide documentation that shows that the principal owner lives in one of the dwellings as his or her primary residence. Number of Parking Stalls Provided: Standard: Compact: Handicap: Will there be a change in use? ❑ Yes 0 No If "yes", explain: FIRE PROTECTION/HAZARDOUS MATERIALS: ❑ Sprinklers 0 Automatic Fire Alarm 0 None 114 Other (specify) 1Vt c, up p reSSt o h Will there be storage or use of flammable, combustible or hazardous materials in the building? ❑ Yes 0 No If `yes', attach List of materials and storage locations on a separate 8-1/2"x 11 "paper including quantities and Material Safety Data Sheets. SEPTIC SYSTEM ❑ On-site Septic System - For on-site septic system, provide 2 copies of a current septic design approved by King County Health Department. Q:Wpplicat ons\Fonns-Applications On LineO-2006 - Pemut Application.doc Revised. 9-2006 bh Page 2 of 6 Vico / Fire & Security R-102 RESTAURANT SYSTEM NOZZLE COVERAGE SUMMARY SHEET ANSULI Appliance Nozzle Type Flow Points Width (In) Max. Side • Max. Length (In) Side Multiple Nozzle wo/Drip Board Area Sq. In. Multiple Nozzle w/Drip Board Area Sq. In. Min. Nozzle Ht. (In) Max. Nozzle Ht. (in) Fryers without drip boards Split or No Split Vat 230 2 14 15 — — 27 47 245 2 14 15 — — 20 27 Fryers without drip boards Non -Split Vat RNLI) 290 2 19.5 19 — —13 4 • ' 16 , 3N 3 19.5 19 — — , 21 34 3N 3 18 18 — — 25 35 • Fryers with drip boards Split or No Split Vat' 230 2 14 21 210 294 27 47 245 2 14 21 210 294 20 27 Fryers with drip boards' Non -Split Vat (ONLY) 290 2 19.5 25 3/8 370.5 495 13 , 16 3N 3 19.5 25 3/8 370.5 495 21 34 3N 3 18 • 27 3/4 324. 497 25 35 Tilt Skillet/Braising Pan' Coverage Exception. limitation are based on fryer sizes Including the drip boards. Tilt Skillets and Braising may exceed the maximum of 6 sq. ft. Range Without back shelf With back shelf Without back shelf With back shelf . 1N 1 12 32 — — 30 40 1F 1 12 28 — — 30 50 1F . 1 12 28 — — 40 48 245 2 24 28 — — 40 50 260 2 24 32 — — 30 40 260 . 2 12 32 — — 30 40 2 x 290 4 36 28 — — 15 20 Griddle .' . • • 1 Wi NSS 1 36 30 — — 35 40 290 2 30 24 — — 30 50 260 2 48 30 — — 30 50 290 2 48 30 — — 20 .30 2120 2 48 30 — — 10 20 Chaln Broiler' (Overhead Protection). 2 x 1W 2 34 30 —— 10 26 Chain Broiler (Horizontal Protection) 2 x 1N • 2 31 43 — • — Front edge; above the chain 1 in. - 3 in. • Char Broiler Gas -Radiant Electric Lava -Rock Natural Charcoal' Lava -Rock or Natural Charcoal' 1 N/1 NSS 1 • 24 36 — — 15 %. 40 1 N/1 NSS 1 20 34 — — 20 50 1 N/1 NSS 1 13 24 — — 18 35 1 N/1 NSS 1 12 24 — — 18 40 3N 3 24 30 — — 14 40 Wood Fueled' 3N 3 24 30 — — 14 40 Upright Broiler 2 x 1/2N 1 30 32.5 Front edge; above the grate Salamander Broiler 2 x 1/2N 1 30 32.5 — 1N 1 16 29 — — — 1 N nozzle location to be on the vertical edge 6 to 12 in. in front and 0 to 121n. above the top of broiler Internal Chamber 1N 1 16 29 — — 6-12 in. above either end Wok 3.75 to 8 Inches deep 260 2 14 in. to 30 In. diameter — — 35 I 45 3 to 6 Inches deep • 1 N/1 NSS 1 11 in. to 24 In. diameter — — 30 40 • ' For multiple nozzle protection of single fryers, see detailed Information on pages 4-10 to 4-11 of manual. ' See Figure 1 for nozzle location. ' Minimum chain broiler exhaust opening –12 Ih. x 12 In. (31 cm x 31 cm); and not Tess than 60% of Internal broiler size. ' 4 in. (102 mm) maximum fuel depth. ' 6 In. (15 cm) maximum fuel depth. ` -qco/Fire & Security' R -102 -RESTAURANT SYSTEM NOZZLE COVERAGE. SUMMARY SHEET ANSUL. Plenum Nozzle Type Flow Points Width (In) Max. Side Length (In) Max. Side Nozzle Placement (See Manual for More Detail) Min. Height (In) Max. Height (In) NIS`roU° ' `Gi fe ., 1N.......v- 1 ..- 'lir ,.. " 120 _0 fn. - 8 in. from end of p)enum 2 4• Perpendicular Protection Single Bank 1W/1100 1 48 48 See Manual for more detail 1 20 Horizontal Protection V -Bank 2 x 1N 2 48 120 0 in. - 6 In. from end of plenum 2 4 , Horizontal Protection V Bank 1W/1100 1 48 72 0 In. - 6 in. from end of plenum 1/3 the height of filter Perpendicular Protection V -Bank 1W/1100 1 48 48 See Manual for more detail 1 20 ' Duct Nozzle Type Flow Points Perimeter (In) Diameter (In) Nozzle Placement (See Manual for More Detail) Duct Length (In) Single Nozzle 1 flow nozzle 1100 1 50 16 See Manual for more detail Unlimited $Ing e.Nozzle 2.11 tW noz le. 2W 2 100 31 7/8 See-Menyal-fo_r more detail Unlimited Multiple*Nozzle 2W +1100 3 135 48 See Manual for more detail Unlimited Multiple 2W Nozzle 2W - • >135 >135 See Manual for more detail Unlimited R-102 OVERLAPPING PROTECTION The 245 nozzle, Part No. 419340, Is the only approved nozzle for overlapping (zone) protection. Appliance Type Maximum. Cooking Hazard Fryer 34 in. (864 mm) Deep x 5.8 sq. ft. (.54 sq. m) Griddle 30 in. (762 mm) Deep x Unlimited Length Range 28 In. (711 mm) Deep x Unlimited Length Wok, Maximum 30 In. (762 mm) Diameter x 8 In. (203 mm) Deep Wok, Minlgtum 11 in. (279 mm) Diameter x 3 in. (78 mm) Deep Braising Pan/Tilt Skillet' 34 in. (864 mm) Deep x Unlimited Length Lava Rock Char-Broller 32 in. (813 mm) Deep x Unlimited Length Charcoal Broiler 32 in. (813 mm) Deep x Unlimited L9ngth (4 in. (102 mm) Maximum Fuel Depth) Mesquite Wood Broiler 32 In. (813 rnm) Deep x Unlimited Length (12 in. (305 mm) Maximum Fuel Depth) Gas Radiant Char -Broiler 36 in. (914 mm) Deep x Unlimited Length Electric Char -Broiler 34 in. (864 mm) Deep x Unlimited Length ' See FJgure 1 tor nozzle location. COVER MUST NOT INTERFERE WITH EDGE OF DISCHARGE PATTERN 1.41-44, 0-0.8 IN. (0-15 cm) I 1 f 40.451N. 1 (1-1.1 m) '1 I 1 r1 1 ZONE f f ZONE CENTER UNE 000927 Ost REE f.. TYCO SAFETY PRODUCTS. ONE STANTON STREET. MARINETTE. WI 54143-2542 715-735-7411 Form No. F-2005010 02005 AnsuI Incorporated Utho SECTION IV — SYSTEM DESIGN ► UL EX. 3470 ULC CEx747 Page 4-34 7-1-98 REV.4 MNK AND CARTRIDGE REQUIREMENTS Qnoe the hazard analysis Is completed and the total nozzle flow numbers are established, the quantity and 'size of agent tanks and cartridges needed to supply the nozzles with the proper volumes of agent at the proper flow rates can be determined. For cartridges used in the regulated release mechanism, flow capacities, tank quantities and sizes, and regulated release cartridge options are given hi the table below. Total Quantity and Regulated Release Flow Size of Cartridge Options Numbers* Tanks) Nitrogen Carbon Dioxide 1 — 6 (1) 1.5 Gallon LT 20-R (7032) 101-10 (15850) 8 — 11 (1) 3.0 Gallon LT -30-R (5373) 101-20 (17492) 11 — 18 (1) 1.5 Galion Double (73022) 101-30 (15851) (1) 3.0 Galion yy((i 18 — 22 (2) 3.0 Gallon Double (73022) 101-30 (15851) t When one or more regulated actuators are used, the following tank and cartridge combinations apply for eabh regulated actuator: Regulated Actuator Regulated Actuator Tank(s) Cartridge (1) 1.5 Gallon (1) 3.0 Gallon (1) 1.5 Gallon and I (1) 3.0 Gallon (2) 3.0 Galion LT 20-R or 101-10 LT 30-R or 101-20 LT -A-101-30 or 101-30" LT -A-101-30 or 101-30" "a "noonday 10 maximum lbw number". us OYU*Won Piping RoadManMnts lou 1.6 ON - and t and 0.0 pion optima In MAY Bastion. For higher total flow numbers (23 to 110), multiple cartridges and regulated actuators are required as shown In the System Selection Guide In Section IX—Appendix. ACTUATION GAS LINE WITH AN Lr 20.3, LT -30.8.101.10 OR 101-20 CARTRIDGE MAXIMUM LENGTH OF 20 FT (0 m). MAXIMUM NO. OF FITTINGS e 'ANSULAUTOMAM REGULATED RELEASE ASSEMBLY ACTUATION AND EXPELLANT GAS UNE REQUIREMENTS , This section contains the guidelines for Installing the actuation end expellant gas lines between the regulated release mechanism reg- ulator, each regulated actuator regulator, and each agent tank. Thee* limitations should be considered when selecting the com- ponent mounting looafione. ► Actuation Gas Line — 6 to 8* Tanks Maximum 1..8 Tank maximum reflects the utilization Of 3 tank regulated aotualors. 1. Use only 1/4 in. Schedule 40 black Iron, hot -dipped galva- nized, chrome -plated, or stainless steel pipe and fittings. 2. The actuation gas line piping Is Installed from the regulated release mechanism to each regulated actuator connected within the system. The total length of the 'actuation gas line from the regulated release assembly to the regulated actuator as?; (les) must riot exceed 20 ft. (8 m) when using an LT 20-8 Part No. 7032), an LT -30 -fl nitrogen cartridge (Part No. 6373), or a 101-10 (Part.No. 15850) ora 101-20 (Part No. ► 17492) carbon dioxide cartridge. See Figure 73. REGULATED ACTUATOR ASSEMBLY EXPELLANT OAS LNES NOT INCLUDED IN ACTUATION GAS UNE LENGTH TOTALS FIGURE 73 000776 • r sr 0 11 ■ 111114111•11.111110.1•• VW/maOr -1•11•1141•11MilimMemili, ACCEPTED Without Cornments I / As Noted In Red Per The Attached Letter these plans have been reviewed by The Tulc.ivila Fire , I aPrevention Bureau for conformance with current city standards. Acceptance is :!ubjerrors and omissions which do not authorize violations of dopted tanaaras and ordinances. The responsibility for the -..lequacy or design rests totally with the designer. - ::klitions, deletions or revisions to these drawings atter :is date will void this acceptance and will require a . ---submittal of revised drawings for subsequent approval. :Thal acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date:7// 7/4 f 2) By: 1 24 (..- a 1UKWILA -IRI. OhrlArt Please call: 575.4407 and give this job and exact address for shut. lows) or restoration approval. CHARLEY'S GRILED SUBS FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET \UV3E SHEET TITLE FA -01 SYSTEM I NFO MATI O \ FA -02 TYPICAL DETAILS - WRI\G A\3 MOU\TI\G FA -03 FRE ALARM SYSTEIv FLOO PLA\ FA -04 SYSTEM CALCULATIO\S GE\EAL), �ISE� SITE PLA\ WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATION SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD 416 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR 414 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH _ 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. - 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL -BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION' BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM • SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHER.E THE CABLE IS INSTALLED QUANTITY 2 1 1 1 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD I v Q LINEAR BEAM 'v SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD A SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING DUCT SMOKE D DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN HELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX CEILING IN/ 1-1/2" EXT. SET -MC -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX CEILING IN/ 1-1/2" EXT. C FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING FIRE ALARM © STROBE (WALL MOUNT) FIRE ALARM SPEAKER (CEILING MOUNT) Tc ZR -MC -W, SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. SET -CW SIEMENS 4S DEEP BOX CEILING IN/ 1-1/2" EXT. B AWP FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) SET -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR MULTI -VOLTAGE CONTROL RELAY MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JB❑X FIRE ALARM TERMINAL CABINETIN FIELD F.B.O. F.B.O. F.B.O. VERIFY feramarasestreemessew JUNCTI❑N BOX F.B.❑, FSB.❑. . N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A `ACCEPTE N/A F.B.❑. FURNISHED BY OTHERS N/A N/A NOT APPLICABLE N/A U.O.N. UNLESS OTHERWISE NOTED N/A I4/A .,. ‘NAr--1 on d d G 9 y Withodt1 mments As Noted In Red Per Tl Cached Letter N/A N/A :nese plans have been reviewed by The Tukwila Fire N even Bureau for /Iormance with curren,i1 stars ar s. Acceptance is suhle t to errors and emissions whietl do not authoriize violations of adopted WP WEATHERPROOF DEVICE N/A e N Aanaaras nd oratnanps The responsibility fg14 ade uac of design rests totally with the designer. Additions, deizt;ciis err ricins b-tha"s " , ter N is date will void this acp ptance and will requi�,3 resubmittal of revised drawings for subsequent approval. N Anal acceptance is sutslj. t to field test and inspctipti by The Tukwila Fire Prevention Bureau. RED AS BUILT ADD OR CHANGE N/A GREEN BLUE AS BUILT REMOVE AS BUILT NOTES TO CAD N/A N/A N bate: /thy:-5c7?.o!> N/A TUKWILA FIRE DEPARTtvitA Please call: 575-4407 and give this job No.6 --fl -6-0 and exact address for shut. -)own or restoration approval, NOTICE *Ai ro 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS DATE 5/15/08 2aaa<a A completed, signed, TukwilO Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptar Testing of any Fire Alarm and Detection Systems. of test will result in a Re -inspection Fee anc termination of the testing. Ai JUN 23 2008 Tukwila Are Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved Ce �CALE: 1 /8"=1 DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: .10B NUMBER: SHEET FA -01 J THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND IS❑LATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE -(+ FROM XLS CONTROL PANEL OR- PREVI❑US ADDRESSABLE DEVICE -1 STOP IF LAST DEVICE 0 DUCT DETECTOR L❑CATI❑N 92) END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH 0 GROUND' -ID C4 N) HTRI-R STATUS LED N.O. 0 COM co 0 N NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL `` SALE (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE DEVICE TO NEXT ADDRESSABLE DEVICE L - NOTE 1; VOLTAGE MAX. - CURRENT MAX. - CONT. RES. MAX. - MAX. CABLE LENGTH - C CLINE TO LINE) - C CLINE TO SHIELD) - MAX, LINE SIZE - MIN, LINE SIZE- OUTLET SAMPLING---\ TUBE INLET SAMPLING TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE=NONE MUSIC�}-AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING 0 TO NEXT ADDRESSABLE DEVICE f(+) STOP IF LAST DEVICE (-) FROM XLS CONTROL PANEL OR {(+) PREVIOUS ADDRESSABLE DEVICE (-) RELAY CONTACTS (4.0A @ 125VAC> C4.OA @ 30VDC) 27 VDC 3.5 rnA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0,02uF 0,04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST 25 SEC. TO GUARANTEE DETECTI❑N. 0 0 V Th 1001 TB1 5 0 0 0 0 123456 TB2 C 3 0 J _f_yL CV END OF LINE } 1 DEVICE (3.6K 1/4W) SUPERVISED _/ SWITCH GROUND NOTE: 0 HTRI-D STATUS LED Co 0 0 c0 0 NOT USED 0 FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL s (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC 0 0 0 1 J_ J_ J_ T T T T U 0 PAD -3 0 00 0 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 24K n TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE END OF LINE DEVICE 3.6K 1/4W) SUPERVISED 1 SWITCH NAC -4 NAC -3 NAC -2 NAC -1 f FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE DEVICE LOOP 0 0 0 eT FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY C'S' CABLE) FROM FACP <VOICE CIRCUIT) C'V' CABLE) 470 OHMS IW EOL T M-1 0 0 IMi 0 TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE: NO E EARTH GROUND .. .(+)TO NEXT DEVICE OR 1 >(-) STOP IF LAST DEVICE 1 (+) (-) STROBE SPEAKER (0 0 .1 STROBE(-) (+) O STROBE SPEAKER (+) (-) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY R 80" A.F.F. 4S DEEP BOX W/ 1-1 /2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE=NONE TO NEXT DEVICE OR END OF LINE TO NEXT DEVICE OR END OF LINE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERA11N TEMPERATURE: +32' F 0- C) TO 100' F 36 C) HUMIDITY: 0- 9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE fDATA IN (-) > DATA IN (+) > DEVICE IS LISTED FOR MR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID CEILING SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX.- ig� WITH 1-1/2' EXTENSION• \, \, CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKER/STROBE MOUNTING (DROP CEILING) SCALE=NONE JUNCTI❑N B❑X-----'.\ MOUNTED ON \ CEILING FLEX \ JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT / / 4 0 0 I TO NEXT DEVICE 0 0 CADDY BAR SMOKE DETECTOR ---- SMOKE- SMOKE DETECTOR MOUNTING SCALE=NONE \ SUSPENDED ILLUMINATED CEILING DO NOT I \ ST ' LL ADDRESSABLE N T DEVICES INIJ PREPROGRAMMED W DEVICES ADDRESS. AT 106 T NG Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved z z 65. 44 z 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z Q DESCRIPTION SHOP DRAWINGS DATE 1 2 aa<a< 0 uJ J —J++ LL 0 >W J CC 0 CC 1 0 SCALE: 1 /8"=1 DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: \OB NUMBER: SHEET FA -02 V J D,S,2V O DOWN 1 A(` -1V ------------------ 11 R1-21 UP TO MAC 6 VA -1 —5 2S 2A-1-6 15cd V2A-1— 5 `-i \11 1 1 !-i _ ---_ 1, 1 , � 1 1 ( , I '.I_\... -t- i 1 1 i \ 1 i 1 \T i' 1 '1 1 1 \I III 1 \\ l __ (-� <1 ------ ------- ------- z i 15 off`'\ 1 • ( 15cd V2A-1-4 `11 I\ I\ 1 11'I I II( 1\ — — — --1 • --- �_-� — r— -==T ____---------- 11 MAC -1 R ii 111 1 D 0W\11 I 111 s� \ / - - 1 -. •`"'111 1 Dy1moR(,\ 11 1 la ES,EV IhGO✓L& , ‘• i, \, • 1, F,L-1144. 1, \Va 11 s., ,- -- 1\_I 1 \101 ,-_ ' �-' ! -r- 11j1 II----- •- �\\\\ \ \ \\ n \\ \� Il \\ \\ \\ \ \\\,`` i1 `\ 5.'H_F.� `\ `;\\\ , \\ — \ �--- �\\ \\ ti - ,1\\ - \ . • EZEE 2A -1-g' ,1 110cd NORTH •-fl \ ----- \ I1 1\ 111 '•1 —`� A i `_� 111 t y CHARLEY'S GRILLED SUBS WESTFIELD SOUTHCENTER MALL SCALE 118"=1' 1 1 '' 11 III1 I 1• 1_ i • ( { FLAG NO ES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE, FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITSI(SEE SIEMENS INSTALLATI❑N SUBMITTAL FOR L❑CATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR. SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL, FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. PLA S NOT APPROV DO NOT INS -AL_ ADDRESSABLE !NOT A I ISG DEVICES U\TIL PREPROGRAMvED WI -H DEVICES ADDR-SS. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved CO 0' 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: NVI DESCRIPTION SHOP DRAWINGS DATE 5/15/08 2 <<a« (1) cn (/) 0 W —J J E 0 (r) W J CC 0 J CO < 2frzO) w wp cn w° _Z cc cf) gp< <Co 0 coo F_ CV F_ / W SCALE: 1 /8"=1 DRAWN BY: ,.ANDERSON DESIGNED BY: R.VEZZANI DATE:5/1 2/08 BACKROUND PLAN PROVIDED BY: 1.08 NUMBER:XXXXXXX(XX SHEET FA -03, t'- -1- --J. 1•1-flI1' 0,, 0 :,t •�d ,t 1I 11 1' J�= lJ* !NII I NI VIII IIID -- SYSTEM CALCULATIONS a 0 !; '/ -- �1r -� _ - \\t--r"`_a\ \1_� \ ,\ -� " ~- 1\, t,.._y\\..,:_,,_,,:c-i.E.-:5k----5.\\:;,::\‘\\,.\‘‘,\\,\\\" t. ms'r 1 ,� iJ NORTH r - i (Tr-- 1in-- ,41 ---- BATTERY SZING CALCULATION 0 0 /0 \c - \ tit it C __ -1 , B L . ti d 1 - / -1 CHARLEY'S GRILLED SUBS WESTFIELD SOUTHCENTER MALL :: SCALE 1132'=1' EX t I. CHARLEY'S GRILLED SUBS CHARLEY'S GRILLED SUBS FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL DATE co 0 Panel: CHARLEY'S GRILLED SUBS Wire Resistance 1.62 Date: June 10, 2008 CURRENT TOTAL=1 162 Current Load: Standby: Alarm: Current Load: Standby: Alarm: QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 1 SET -MC @15CD 64 64 • Total Wire Resistance (R) 0.62 Device Type SET -MC @30CD Qty Amps Total Amps Total (WL * 2 ) * (R/ft) Device Type 0 Qty Amps 0 Total Amps Total Total Device Load, Amps (1) HFP-11 0 SET -MC @11OCD 0.0022 0.0022 0.0023 a (Total Cct Load) 0 SET-HMC-C@115CD 318 0 ■ AD2-P 0.10 1 0.0635 0.0635 0.064 0.064 Main System Board (E= 1 * R) EOL Voltage 1 - 0.03 - 0.03 0.030 0.030 0 HTR -R 2 0.009600 0.0096 0.021 0.042 64 SET -MC @15CD 1 0.064 0.064 98 HTRI-D - 0.001600 0.0035 0 SET-MC-CW@110CD SET -MC @30CD 0 1 0.098 0.098 2 ICP -B6 162 191 20.29974792 0.005 ■ SET -MC @75CD 0.175 • Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL SET -MC @110CD Panel: 0.233 Wire Resistance 2ss Date: June 10, 2008 CURRENT TOTAL= 3.6 SET HMC-C@115CD CIRCUIT: SPEAKER CIRCUIT 0.318 QTY Device Type Alarm Current Alarm Total Wire Size SET HMC-C@135CD Voltage at EOL Circuit Total 0.318 70.7V1/8 1.8 3.6 0.0731 Amps 0.106 Amps SET HMC-C@185CD ZR -MC @15CD 0 0 0.445 0.064 ( WL*2 )*(R/ft) 0 Standby Current Load: 0 0.0731 Amps For 24 Hours = 1.754 Amp -hours Total Device Load, Amps (I) (Total Cct Load) ZR -MC @30CD HCP 0 0.098 0.0015 0 0 Alarm Current Load: ( E) 0.106 Amps For 5 Minutes= 0.009 Amp -hours . (E= I* R) EOL Voltage 0.03 Amps 0.192 Amps 0 0 0 0 (20.4 - E) 0 0 0 25% Derating= 2.204 Amp -hours Standby Current Load: 0 0.03 Amps For 24 Hours = 0.720 Amp -hours DEVICES= 2 TOTAL mA, 3.6 14 191 20.39645198 3.6 1 _. � 9 Alarm Current Load: 0.192 Amps For 5 Minutes= 0.016 Amp -hours Total System Current Load: 2.204 Amp -hours 25% Derating= 0.920 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.920 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SZING CALCULATION 0 0 /0 \c - \ tit it C __ -1 , B L . ti d 1 - / -1 CHARLEY'S GRILLED SUBS WESTFIELD SOUTHCENTER MALL :: SCALE 1132'=1' EX t I. RISER DIAGRAM VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved lam eel Itt 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: NVI Notification Appliance Circuit Detail DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL DATE co 0 Panel: CHARLEY'S GRILLED SUBS Wire Resistance 1.62 Date: June 10, 2008 CURRENT TOTAL=1 162 CIRCUIT: S1 QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 1 SET -MC @15CD 64 64 • Total Wire Resistance (R) 0.62 1 SET -MC @30CD 98 98 r (WL * 2 ) * (R/ft) 0 SET -MC @75CD 175 0 Total Device Load, Amps (1) 0.16 0 SET -MC @11OCD 233 0 a (Total Cct Load) 0 SET-HMC-C@115CD 318 0 ■ Voltage Drop ( E) 0.10 0 SET-HMC-C@177CD 445 318 0 0 ■ (E= 1 * R) EOL Voltage 20.30 0 SET -HMC @135CD 0 SET -HMC @185CD 445 0 (20.4 - E) 0 Z-MC@15CD 64 0 0 Z-MC@30CD 98 0 ■ 0 SET-MC-CW@110CD 233 0 DEVICES= 2 TOTAL mA= 162 191 20.29974792 162 ■ • Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: CHARLEY'S GRILLED SUBS Wire Resistance 2ss Date: June 10, 2008 CURRENT TOTAL= 3.6 CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 70.7V1/8 1.8 3.6 Total Wire Resistance (R) 0.99 0 0 0 ( WL*2 )*(R/ft) 0 0 0 • Total Device Load, Amps (I) (Total Cct Load) 0.00 0 0 0 Voltage Drop ( E) 0.00 0 0 0 . (E= I* R) EOL Voltage 20.40 0 0 0 0 0 0 (20.4 - E) 0 0 0 0 0 0 DEVICES= 2 TOTAL mA, 3.6 14 191 20.39645198 3.6 1 _. � 9 RISER DIAGRAM VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved lam eel Itt 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: NVI DESCRIPTION SHOP DRAWINGS DATE co 0 J c0 Q T- T- O �o) z cc 2__ C'# < JCC D � u' U SCALE: 1/8"=1' CC tr= w z w z 0 U U w DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: \JOB NUMBER:54511 SHEET FA -04 a}1 GENERAL NOTES 1. Western States Fire Protection to add and/or relocate existing sprinklers due to new walls and ceilings being added for the tenant improvement from existing fire sprinkler piping. 2. Sprinklers shall be spaced in accordance with NFPA #13 with a 15'- 0" maximum distance between sprinklers. Maximum coverage area of 130 sq. ft. at Ordinary Hazard Occupancy. 3. All hangers' assemblies shall be spaced and installed in accordance with NEPA-13 & manufacture's specifications. 4. All new sprinklerr inkier drops and arm -over pipee isblack schedulehedule 4 0 pipe.e. ductile iron class 5. All new threaded fittings are cast iron class 125 or due t 150. 6. The owner is responsible for all apprriate maintenance ee of sprinkler er & local codes. system in accordance with NFPA, as wellstate as 7. FlexHead fire sprinlder assemblies to be used to attach fire sprinklers at ceilings. 8. Existing fire sprinlder system to remain. Western States Fire Protection will modify the existing system only in the areas of work shown. All other areas are not in contract and WSFP is not responsible for existing conditions. FtexHead Suspended Ceiling Detail Each FM -approved unit is ready -to -install, pressure- and leak -tested, and comes complete with a flexible stainless-steel hose and mounting bracket with adjustable hub. Multi -port ceiling grid mounting bracket FtexHead sprinkler drop ti Adjustable hub Sprinkler branchline Suspended t -bar grid Sprinkler head FlexHead Metal Stud Sprinkler branchline FtexHead sprinkler drop Adjustable hub .FF7. Ceiling file Multi -port metal stud mounting bracket Metal stud RETAINER TRAP C -CLAMP WITH f LOCKNUT `�- ALL THREAD ROD PIPE RING C—CLAMP HANGER W,/RETAINER ,STRAP Sheetrock ceiling Sprinkler head ea: • B.O. SOFFIT T-0' AFF. E G-2 B.O. CEILING I2'-10" AFF. CDNC DECK FLAT DR CDRR HILTI SWI HILTI KWIK-BOAT \d/ROD COUPLING FIG. 100 ALL THREAD RDD �-- FIG. 200 ADJUSTABLE RING HANGER <-3 LT HANGER OE N ®N B.O. CEILING II' -O" AFF. G -I B.O. CEILING -i'-O" AFF. Fire Sprinkler Plan Scale: 1/4" = 1'-0" SYMBOL LEGEND Existing piping New piping Mech. Tee cut into existing pipe Hanger notation see detail Existing Upright sprinkler New Concealed pendant sprinkler New Dry pendant sprinkler G-2 G-2 11118.0. SOFFIT B.O.SOFFIT 11-47 AFF. C-2 12'-O" AFF. 5-1 V.7,..7.NITY MAP /Y" L .. •6�44rr,, • L •#. • R,? �.(�,r '.a X77' • ` 4,444;04-_ M' ,yy.+MMR! ,. pY lt41±a5 :{j�{'f` , i'6rS rr': ib.w.' k'a Yrtb•;.,uV• ,b '.; -.a •k�.."�, l $ a ., .•'$.. l - ,, r ..,„ 'j'' -1 ax nwry•Pp_ r11 7.. r �r M t4� ? V � . � • .7�}....�M >.` I{. j „'RWF•i' I'3J • i� • �1 '. 1 '(+"h ��• 7�t� ,',�' {,.., ��%A •#a v;, 1J, '•a .,.j ,'"wyy ,r:.`f • P,tvT.s.:...,rr k.,.. tl•{N4.o;.?•••V4 ""'(;� "55Al '- ,•�,-.' i S • `fid • o� i ,` inr,r .' 9 6'JJM1/7.4\.+H'A�k '..,,..rI . •`fl'.1::—....7..?i'...:;;)..-„ ,�,�' ,'}.i,•,.;4.i. ;?'�.r,Jw: 'i.• eszC.;,. .y' rk.a~ hsy,f !�W�'WL •LSu e:.:51vd•7 r,f:..Y'N •R L - ,j{�aL' . ` jb " �syuv ;7' . .': `i J',•Y.'.Lti!•,,. '}"r,•, 'i M:aLL •��+�1':.aMr,}w •:tar..{�cyjf.. i. .diY;4'M."J ". .,9 ' .h .7rr :p' �u'`Y - 4*"i,!'�M c 1.. r �,� • �4 •- 'na"v,•n•'. r'.Ei;`;f ' ` e..a.w•;r •,,,....• ' .?3 . • 'et'y `�,`�}&,`{ n.��, ��lWy.ti�." . • A ? : P 3, -I �a 'Mr �' : ...H FF l ,• , ys',]i•y �li Or1 _aYu • .,/jJ ;i'Yn' Gfv. f14, ' s-�7,•"''>m'�L�rYe+r•rY s ':K.+i".siixfkr i�Jw,N.!.atc.Y yrq.r�s.i � ' . •rVS'.c • } t W rN .uvl!<i/(n"nY 1tiif-t L( i { 2 }msµ �•2. t. .•,..rA. +saw` <'n,r _ . • N:Yqi .rYCi•v•.; om, F Mtt¢E1.QvfrJyii41pr4�.:aea. •.,,:Jun. , • + . dV:'.:.L,`,-r'r,;$q'.a$ ...C��f� . 1� li, " : Y �;J , ,.,.„- : ,Kw,.e,Hut`rl.f"a,. ,.wR• ::.•;.1 r ,J'4 � .! or �1Y.,.w.�BAa ter}} r4( 1.'k ' 6 Of' . .:. �r f FrP�, , .y,. M'wNv :. i4t :r•evr.#.. . \ 7. i,' -FDy.�:' ti • Vi Ir i f;`•fw:.- . k. s L ,f. '. .Y �,f' K74..., 3? ' • Jy •' Y:,L;��.:rr'�t �t. t , ^M�nl' �6 R• 0 1. •N �J ,i.r r t � ttfJ' .` .,. . '#)s.:fir ,rmtrAr,;r,:i�i• •n ,l,a.{••}?:a'%"r �rtk,'firi.M�'� �YctidNa� X,)�7':� . 3''''' , .• X' ' 4 4 > 3, .} �. . •,:„, ,w.�,, • t a_ .,m. .r. '�i, 'TVI ftaa ai• ;'.. N•.',:497#Y6ttb4{.` w. . ce I., 4Y i ,..1.� •w . �9F•� , •�:t 4 r :,.. _ ' 1s;: :.•iVE„... J" wri ; • •; ..,, ,l .t• .,.,...,,t. ..aa . _ � . ,, .,.�.: , .:>s x,- .. :,. N,i.4 • y.jk,.D,.. ,. 5',,. ' y 1AtiM eNa{:,r PROJECT LOCATION merayRro . • w�ae I NORDSTROM mac ftl"ba•-01 III• II Mtt,IM] lai I7 . , ,. ���,,qq LII 1. d • . 1k, , ij IN .. til • - `�I, �.. ;�T . r , I. 1. - • r' 1.. mane • i• �rk` �II: �� ��ti� o. J 1 :. `.',�., at,rte— , — is err0 .U'�‘i r I *Woo \— FOOD COURT......-... � ■- is ' ....,_.._.. r• _.... — , SOUTHCENTER MALL LEVEL 2 OF 3 C NOW 1l w 4 . r„: fctt”, iP j Vit,Thout Corn As Noted In - .. R . ,j ., _ nese evention • - Per The Attact. -. iave been reviewed Bureau for conformar}C's`WL11 ed Itter by The �'----_. _ stta.w>r. L .;• `nc- s•.cttoer\- - ® omi K di I thi ` ionE • aro: ►- ions, - c. whr enc of cosign deletion o '- • tori o ,. {Y - �b. re or rgisio id th'Saccept The - I n 4- iolati respgno with the to these a an EN _ bD COUR re 'ltbmitt- ---„jsi,- of vise, . Q - ccepiankeiss bject ''T- ila Fi '� Pre - - in O •n s t• l for subs eidtest reau. = E 'STING ® , ® o . E PLOYEE �� •il -„� 0 `; To LETS c z + Date: =YY y ilO I 'I i�li iJ'i i. I�E tea' 1 i _,,,_. I'LL., ,T,�. HD o rtl li {��f � / PLROJECT ® ® , _r�.r . ION L�L��'_��__ 11.1. (91: Jm 70. . 71-.4111117 rY i0 I AugJ TSI I. •- .. rUKwlw rlf3t ut: Weld stamps must be Please call; 575.4407 PUBLIC • inspected before pipe is and give this job RESTROOMS hung. Do not paint pipinTo. _, •7 NORTFJ riot• to hydrostatic test and exact address fors SOUTHCENTER down or at apuroval, + FOOD COURT - LE' JVc1 I ' pi 4,1 Tukwila Fire current city rs and ms of adopted ibility for the designer. drawings atter ill require a equent approval. d inspection by 7e0 GENERAL NOTES r.; r1 uesiyn and installation in accor- dance with NFPA Standards. ,;R materials to be Underwriters Labora- ;.ries Listed and / or FM approved. . Overhead piping to be black steel :Lontorming to specifications of . 1M A795, ANSI / ASTM A53, ANSI :3 i.1OM, ASTM A135. AREA OF •o. RATIN HYDRAULIC DESIGN INFORMATION SYSTEM DESIGN FLOW TEST REVISIONS DESCRIPTION SPRINKLER LEGEND DESCRIPTION ORIF. TEMP. FINISH NO. REQ, DEVICE MFG. DESCRIPTION OFIF. TEMP. FINISH MAX. AREAIHEAD RESIDUAL GPM FLOWING DATE & TIME Western States Fire protection Company 7102 - 180th AVE. NE, SUITE A-105 • REDMOND, WA • 98052 WESTERN STATES ARE PROTECTION COMPANY -- OFFICES LOCATED DENVER / RAPID CITY / MINNEAPOLIS / DULUTH / DALLAS / HOUSTON ALBUQUERQUE / AUSTIN / SEATTLE / PORTLAND / PHOENIX / KANSAS CITY / ST. LOUIS Phone; 206-881-0100 WA. Reg. # WESTESF136QF CHARLEY'S G " LLED SUBS 2600 Southcenter Mall, Space FC -9 Tukwila, WA 95188 JUL 8 2008 {k Tukrila Fire .2.16.(r if/W% 2600 SOUTHCENTER MALL FC -9 FOOD COURT ASSOCIATED PERMITS 08-F-350 08-S-397 08-H-383 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: CHARLEY'S GRILLED SUBS 2600 Southcenter Mall FC -9 Permit No.: 08-S397 Date: July 29, 2008 Reviewer: Steve Kohler Fire Inspector/Plan Review (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. CITY OF TUKWILA Community Development Department Public Works Department Permit Center 6300 Southcenter Blvd., Suite 100 Tukwila, WA 98188 hup://www.citultwila.wa.us Building Permit No. Mechanical Permit No. Plumbing/Gas Permit No. Public Works Permit No. Project No. (For office use only) Applications and plans must be complete in order to be accepted for plan review. Applications will not be accepted through the mail or by fax. **Please Print* * SITE LOCATION King Co Assessor's Tax No.: Site Address: QLP OO 80vcr 4Geylt'1Y r/10.,1 1 Suite Number: Floor: Tenant Name: (41A. i. C L l I✓l S 8 LOOS New Tenant: I Yes ❑ ..No Property Owners Name: Mailing Address: City State Zip CONTACT PERSON - who do we contact when your permit is ready to be issued Name: Jai nt€)4 YYl i call exte - Day Telephone: (&O ID) x-0710 - Cd-1-0 Mailing Address: j o L OO 1 a . S . 5L2i'X t -u, u3Pt q61 Og City E -Mail Address: V- is e—y . fl 11 Ghe.Y►GY e r+hnod.(.omFax Number: (c4019) Il01 " a(D 0+ State Zip GENERAL CONTRACTOR INFORMATION - Five 5 u p press i on stew - (Contractor Information for Mechanical (pg 4) for Plumbing and Gas Piping (pg 5)) Company Name: Q -- HOc j (lrlof Duet ServlGras Mailing Address: 1Q100 1 a N' Qlu-e . S • Beatru to A 9 8 1 Q Ai City State Zip Contact Person: V.Y. iSteXI mC.h Day Telephone: (0)019 'j 19 — Orid-to E -Mail Address: Fax Number: (a0 CD ) 1-(99-- - Sa) 0 la/ 1/aoo1 Contractor Registration Number: t O 0 j *- d $ 86iL. Expiration Date: ARCHITECT OF RECORD - All plans must be wet stamped by Architect of Record Company Name: Mailing Address: city �StatP Contact Person: Day Telephone: E -Mail Address: Fax Number: ENGINEER OF RECORD - All plans must be wet stamped by Engineer of Record PAI D Company Name: Mailing Address: JUL 17 2008 ,(9/' City Contact Person: Day TelephoneTukwila3/ E -Mail Address: Fax Number: Q Apphcanons\Fofms-Applications On Lm&3-2006 - Permit Applicanon.doc Revised 9-2006 bh Zip ts(fr) Page 1 of 6 y BUILDING PERMIT INFORMATION — 206-431-3670 Valuation of Project (contractor's bid price): $ a �{' ��451 . C O Existing Building Valuation: $ Scope of Work (please provide detailed information): "3/1St- a 0.x'10 n. O - 0.k //VA StA k 3.6 C(0L110n ire SUppresSion ov -t12x,n 36 c �necS• Will there be new rack storage? ❑ Yes ❑.. No If yes, a separate permit and plan submittal will be required. Provide All Building Areas in Square Footage Below PLANNING DIVISION: Single family building footprint (area of the foundation of all structures, plus any decks over 18 inches and overhangs greater than 18 inches) *For an Accessory dwelling, provide the following: Lot Area (sq ft): Floor area of principal dwelling: Floor area of accessory dwelling: *Provide documentation that shows that the principal owner lives in one of the dwellings as his or her primary residence. Number of Parking Stalls Provided: Standard: Compact: Handicap: Will there be a change in use? ❑ Yes 0 No If "yes", explain: FIRE PROTECTION/HAZARDOUS MATERIALS: ❑ Sprinklers 0 Automatic Fire Alarm 0 None 114 Other (specify) 1Vt c, up p reSSt o h Will there be storage or use of flammable, combustible or hazardous materials in the building? ❑ Yes 0 No If `yes', attach List of materials and storage locations on a separate 8-1/2"x 11 "paper including quantities and Material Safety Data Sheets. SEPTIC SYSTEM ❑ On-site Septic System - For on-site septic system, provide 2 copies of a current septic design approved by King County Health Department. Q:Wpplicat ons\Fonns-Applications On LineO-2006 - Pemut Application.doc Revised. 9-2006 bh Page 2 of 6 Existing Interior Remodel Addition to Existing Structure New Type of Construction per IBC Type of Occupancy per IBC 15t Floor pia Floor 3rd Floor Floors thru Basement Accessory Structure* Attached Garage Detached Garage Attached Carport Detached Carport Covered Deck Uncovered Deck PLANNING DIVISION: Single family building footprint (area of the foundation of all structures, plus any decks over 18 inches and overhangs greater than 18 inches) *For an Accessory dwelling, provide the following: Lot Area (sq ft): Floor area of principal dwelling: Floor area of accessory dwelling: *Provide documentation that shows that the principal owner lives in one of the dwellings as his or her primary residence. Number of Parking Stalls Provided: Standard: Compact: Handicap: Will there be a change in use? ❑ Yes 0 No If "yes", explain: FIRE PROTECTION/HAZARDOUS MATERIALS: ❑ Sprinklers 0 Automatic Fire Alarm 0 None 114 Other (specify) 1Vt c, up p reSSt o h Will there be storage or use of flammable, combustible or hazardous materials in the building? ❑ Yes 0 No If `yes', attach List of materials and storage locations on a separate 8-1/2"x 11 "paper including quantities and Material Safety Data Sheets. SEPTIC SYSTEM ❑ On-site Septic System - For on-site septic system, provide 2 copies of a current septic design approved by King County Health Department. Q:Wpplicat ons\Fonns-Applications On LineO-2006 - Pemut Application.doc Revised. 9-2006 bh Page 2 of 6 Vico / Fire & Security R-102 RESTAURANT SYSTEM NOZZLE COVERAGE SUMMARY SHEET ANSULI Appliance Nozzle Type Flow Points Width (In) Max. Side • Max. Length (In) Side Multiple Nozzle wo/Drip Board Area Sq. In. Multiple Nozzle w/Drip Board Area Sq. In. Min. Nozzle Ht. (In) Max. Nozzle Ht. (in) Fryers without drip boards Split or No Split Vat 230 2 14 15 — — 27 47 245 2 14 15 — — 20 27 Fryers without drip boards Non -Split Vat RNLI) 290 2 19.5 19 — —13 4 • ' 16 , 3N 3 19.5 19 — — , 21 34 3N 3 18 18 — — 25 35 • Fryers with drip boards Split or No Split Vat' 230 2 14 21 210 294 27 47 245 2 14 21 210 294 20 27 Fryers with drip boards' Non -Split Vat (ONLY) 290 2 19.5 25 3/8 370.5 495 13 , 16 3N 3 19.5 25 3/8 370.5 495 21 34 3N 3 18 • 27 3/4 324. 497 25 35 Tilt Skillet/Braising Pan' Coverage Exception. limitation are based on fryer sizes Including the drip boards. Tilt Skillets and Braising may exceed the maximum of 6 sq. ft. Range Without back shelf With back shelf Without back shelf With back shelf . 1N 1 12 32 — — 30 40 1F 1 12 28 — — 30 50 1F . 1 12 28 — — 40 48 245 2 24 28 — — 40 50 260 2 24 32 — — 30 40 260 . 2 12 32 — — 30 40 2 x 290 4 36 28 — — 15 20 Griddle .' . • • 1 Wi NSS 1 36 30 — — 35 40 290 2 30 24 — — 30 50 260 2 48 30 — — 30 50 290 2 48 30 — — 20 .30 2120 2 48 30 — — 10 20 Chaln Broiler' (Overhead Protection). 2 x 1W 2 34 30 —— 10 26 Chain Broiler (Horizontal Protection) 2 x 1N • 2 31 43 — • — Front edge; above the chain 1 in. - 3 in. • Char Broiler Gas -Radiant Electric Lava -Rock Natural Charcoal' Lava -Rock or Natural Charcoal' 1 N/1 NSS 1 • 24 36 — — 15 %. 40 1 N/1 NSS 1 20 34 — — 20 50 1 N/1 NSS 1 13 24 — — 18 35 1 N/1 NSS 1 12 24 — — 18 40 3N 3 24 30 — — 14 40 Wood Fueled' 3N 3 24 30 — — 14 40 Upright Broiler 2 x 1/2N 1 30 32.5 Front edge; above the grate Salamander Broiler 2 x 1/2N 1 30 32.5 — 1N 1 16 29 — — — 1 N nozzle location to be on the vertical edge 6 to 12 in. in front and 0 to 121n. above the top of broiler Internal Chamber 1N 1 16 29 — — 6-12 in. above either end Wok 3.75 to 8 Inches deep 260 2 14 in. to 30 In. diameter — — 35 I 45 3 to 6 Inches deep • 1 N/1 NSS 1 11 in. to 24 In. diameter — — 30 40 • ' For multiple nozzle protection of single fryers, see detailed Information on pages 4-10 to 4-11 of manual. ' See Figure 1 for nozzle location. ' Minimum chain broiler exhaust opening –12 Ih. x 12 In. (31 cm x 31 cm); and not Tess than 60% of Internal broiler size. ' 4 in. (102 mm) maximum fuel depth. ' 6 In. (15 cm) maximum fuel depth. ` -qco/Fire & Security' R -102 -RESTAURANT SYSTEM NOZZLE COVERAGE. SUMMARY SHEET ANSUL. Plenum Nozzle Type Flow Points Width (In) Max. Side Length (In) Max. Side Nozzle Placement (See Manual for More Detail) Min. Height (In) Max. Height (In) NIS`roU° ' `Gi fe ., 1N.......v- 1 ..- 'lir ,.. " 120 _0 fn. - 8 in. from end of p)enum 2 4• Perpendicular Protection Single Bank 1W/1100 1 48 48 See Manual for more detail 1 20 Horizontal Protection V -Bank 2 x 1N 2 48 120 0 in. - 6 In. from end of plenum 2 4 , Horizontal Protection V Bank 1W/1100 1 48 72 0 In. - 6 in. from end of plenum 1/3 the height of filter Perpendicular Protection V -Bank 1W/1100 1 48 48 See Manual for more detail 1 20 ' Duct Nozzle Type Flow Points Perimeter (In) Diameter (In) Nozzle Placement (See Manual for More Detail) Duct Length (In) Single Nozzle 1 flow nozzle 1100 1 50 16 See Manual for more detail Unlimited $Ing e.Nozzle 2.11 tW noz le. 2W 2 100 31 7/8 See-Menyal-fo_r more detail Unlimited Multiple*Nozzle 2W +1100 3 135 48 See Manual for more detail Unlimited Multiple 2W Nozzle 2W - • >135 >135 See Manual for more detail Unlimited R-102 OVERLAPPING PROTECTION The 245 nozzle, Part No. 419340, Is the only approved nozzle for overlapping (zone) protection. Appliance Type Maximum. Cooking Hazard Fryer 34 in. (864 mm) Deep x 5.8 sq. ft. (.54 sq. m) Griddle 30 in. (762 mm) Deep x Unlimited Length Range 28 In. (711 mm) Deep x Unlimited Length Wok, Maximum 30 In. (762 mm) Diameter x 8 In. (203 mm) Deep Wok, Minlgtum 11 in. (279 mm) Diameter x 3 in. (78 mm) Deep Braising Pan/Tilt Skillet' 34 in. (864 mm) Deep x Unlimited Length Lava Rock Char-Broller 32 in. (813 mm) Deep x Unlimited Length Charcoal Broiler 32 in. (813 mm) Deep x Unlimited L9ngth (4 in. (102 mm) Maximum Fuel Depth) Mesquite Wood Broiler 32 In. (813 rnm) Deep x Unlimited Length (12 in. (305 mm) Maximum Fuel Depth) Gas Radiant Char -Broiler 36 in. (914 mm) Deep x Unlimited Length Electric Char -Broiler 34 in. (864 mm) Deep x Unlimited Length ' See FJgure 1 tor nozzle location. COVER MUST NOT INTERFERE WITH EDGE OF DISCHARGE PATTERN 1.41-44, 0-0.8 IN. (0-15 cm) I 1 f 40.451N. 1 (1-1.1 m) '1 I 1 r1 1 ZONE f f ZONE CENTER UNE 000927 Ost REE f.. TYCO SAFETY PRODUCTS. ONE STANTON STREET. MARINETTE. WI 54143-2542 715-735-7411 Form No. F-2005010 02005 AnsuI Incorporated Utho SECTION IV — SYSTEM DESIGN ► UL EX. 3470 ULC CEx747 Page 4-34 7-1-98 REV.4 MNK AND CARTRIDGE REQUIREMENTS Qnoe the hazard analysis Is completed and the total nozzle flow numbers are established, the quantity and 'size of agent tanks and cartridges needed to supply the nozzles with the proper volumes of agent at the proper flow rates can be determined. For cartridges used in the regulated release mechanism, flow capacities, tank quantities and sizes, and regulated release cartridge options are given hi the table below. Total Quantity and Regulated Release Flow Size of Cartridge Options Numbers* Tanks) Nitrogen Carbon Dioxide 1 — 6 (1) 1.5 Gallon LT 20-R (7032) 101-10 (15850) 8 — 11 (1) 3.0 Gallon LT -30-R (5373) 101-20 (17492) 11 — 18 (1) 1.5 Galion Double (73022) 101-30 (15851) (1) 3.0 Galion yy((i 18 — 22 (2) 3.0 Gallon Double (73022) 101-30 (15851) t When one or more regulated actuators are used, the following tank and cartridge combinations apply for eabh regulated actuator: Regulated Actuator Regulated Actuator Tank(s) Cartridge (1) 1.5 Gallon (1) 3.0 Gallon (1) 1.5 Gallon and I (1) 3.0 Gallon (2) 3.0 Galion LT 20-R or 101-10 LT 30-R or 101-20 LT -A-101-30 or 101-30" LT -A-101-30 or 101-30" "a "noonday 10 maximum lbw number". us OYU*Won Piping RoadManMnts lou 1.6 ON - and t and 0.0 pion optima In MAY Bastion. For higher total flow numbers (23 to 110), multiple cartridges and regulated actuators are required as shown In the System Selection Guide In Section IX—Appendix. ACTUATION GAS LINE WITH AN Lr 20.3, LT -30.8.101.10 OR 101-20 CARTRIDGE MAXIMUM LENGTH OF 20 FT (0 m). MAXIMUM NO. OF FITTINGS e 'ANSULAUTOMAM REGULATED RELEASE ASSEMBLY ACTUATION AND EXPELLANT GAS UNE REQUIREMENTS , This section contains the guidelines for Installing the actuation end expellant gas lines between the regulated release mechanism reg- ulator, each regulated actuator regulator, and each agent tank. Thee* limitations should be considered when selecting the com- ponent mounting looafione. ► Actuation Gas Line — 6 to 8* Tanks Maximum 1..8 Tank maximum reflects the utilization Of 3 tank regulated aotualors. 1. Use only 1/4 in. Schedule 40 black Iron, hot -dipped galva- nized, chrome -plated, or stainless steel pipe and fittings. 2. The actuation gas line piping Is Installed from the regulated release mechanism to each regulated actuator connected within the system. The total length of the 'actuation gas line from the regulated release assembly to the regulated actuator as?; (les) must riot exceed 20 ft. (8 m) when using an LT 20-8 Part No. 7032), an LT -30 -fl nitrogen cartridge (Part No. 6373), or a 101-10 (Part.No. 15850) ora 101-20 (Part No. ► 17492) carbon dioxide cartridge. See Figure 73. REGULATED ACTUATOR ASSEMBLY EXPELLANT OAS LNES NOT INCLUDED IN ACTUATION GAS UNE LENGTH TOTALS FIGURE 73 000776 • r sr 0 11 ■ 111114111•11.111110.1•• VW/maOr -1•11•1141•11MilimMemili, ACCEPTED Without Cornments I / As Noted In Red Per The Attached Letter these plans have been reviewed by The Tulc.ivila Fire , I aPrevention Bureau for conformance with current city standards. Acceptance is :!ubjerrors and omissions which do not authorize violations of dopted tanaaras and ordinances. The responsibility for the -..lequacy or design rests totally with the designer. - ::klitions, deletions or revisions to these drawings atter :is date will void this acceptance and will require a . ---submittal of revised drawings for subsequent approval. :Thal acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date:7// 7/4 f 2) By: 1 24 (..- a 1UKWILA -IRI. OhrlArt Please call: 575.4407 and give this job and exact address for shut. lows) or restoration approval. CHARLEY'S GRILED SUBS FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET \UV3E SHEET TITLE FA -01 SYSTEM I NFO MATI O \ FA -02 TYPICAL DETAILS - WRI\G A\3 MOU\TI\G FA -03 FRE ALARM SYSTEIv FLOO PLA\ FA -04 SYSTEM CALCULATIO\S GE\EAL), �ISE� SITE PLA\ WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATION SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD 416 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR 414 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH _ 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. - 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL -BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION' BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM • SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHER.E THE CABLE IS INSTALLED QUANTITY 2 1 1 1 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD I v Q LINEAR BEAM 'v SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD A SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING DUCT SMOKE D DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN HELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX CEILING IN/ 1-1/2" EXT. SET -MC -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX CEILING IN/ 1-1/2" EXT. C FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING FIRE ALARM © STROBE (WALL MOUNT) FIRE ALARM SPEAKER (CEILING MOUNT) Tc ZR -MC -W, SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. SET -CW SIEMENS 4S DEEP BOX CEILING IN/ 1-1/2" EXT. B AWP FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) SET -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR MULTI -VOLTAGE CONTROL RELAY MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JB❑X FIRE ALARM TERMINAL CABINETIN FIELD F.B.O. F.B.O. F.B.O. VERIFY feramarasestreemessew JUNCTI❑N BOX F.B.❑, FSB.❑. . N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A `ACCEPTE N/A F.B.❑. FURNISHED BY OTHERS N/A N/A NOT APPLICABLE N/A U.O.N. UNLESS OTHERWISE NOTED N/A I4/A .,. ‘NAr--1 on d d G 9 y Withodt1 mments As Noted In Red Per Tl Cached Letter N/A N/A :nese plans have been reviewed by The Tukwila Fire N even Bureau for /Iormance with curren,i1 stars ar s. Acceptance is suhle t to errors and emissions whietl do not authoriize violations of adopted WP WEATHERPROOF DEVICE N/A e N Aanaaras nd oratnanps The responsibility fg14 ade uac of design rests totally with the designer. Additions, deizt;ciis err ricins b-tha"s " , ter N is date will void this acp ptance and will requi�,3 resubmittal of revised drawings for subsequent approval. N Anal acceptance is sutslj. t to field test and inspctipti by The Tukwila Fire Prevention Bureau. RED AS BUILT ADD OR CHANGE N/A GREEN BLUE AS BUILT REMOVE AS BUILT NOTES TO CAD N/A N/A N bate: /thy:-5c7?.o!> N/A TUKWILA FIRE DEPARTtvitA Please call: 575-4407 and give this job No.6 --fl -6-0 and exact address for shut. -)own or restoration approval, NOTICE *Ai ro 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS DATE 5/15/08 2aaa<a A completed, signed, TukwilO Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptar Testing of any Fire Alarm and Detection Systems. of test will result in a Re -inspection Fee anc termination of the testing. Ai JUN 23 2008 Tukwila Are Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved Ce �CALE: 1 /8"=1 DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: .10B NUMBER: SHEET FA -01 J THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND IS❑LATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE -(+ FROM XLS CONTROL PANEL OR- PREVI❑US ADDRESSABLE DEVICE -1 STOP IF LAST DEVICE 0 DUCT DETECTOR L❑CATI❑N 92) END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH 0 GROUND' -ID C4 N) HTRI-R STATUS LED N.O. 0 COM co 0 N NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL `` SALE (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE DEVICE TO NEXT ADDRESSABLE DEVICE L - NOTE 1; VOLTAGE MAX. - CURRENT MAX. - CONT. RES. MAX. - MAX. CABLE LENGTH - C CLINE TO LINE) - C CLINE TO SHIELD) - MAX, LINE SIZE - MIN, LINE SIZE- OUTLET SAMPLING---\ TUBE INLET SAMPLING TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE=NONE MUSIC�}-AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING 0 TO NEXT ADDRESSABLE DEVICE f(+) STOP IF LAST DEVICE (-) FROM XLS CONTROL PANEL OR {(+) PREVIOUS ADDRESSABLE DEVICE (-) RELAY CONTACTS (4.0A @ 125VAC> C4.OA @ 30VDC) 27 VDC 3.5 rnA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0,02uF 0,04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST 25 SEC. TO GUARANTEE DETECTI❑N. 0 0 V Th 1001 TB1 5 0 0 0 0 123456 TB2 C 3 0 J _f_yL CV END OF LINE } 1 DEVICE (3.6K 1/4W) SUPERVISED _/ SWITCH GROUND NOTE: 0 HTRI-D STATUS LED Co 0 0 c0 0 NOT USED 0 FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL s (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC 0 0 0 1 J_ J_ J_ T T T T U 0 PAD -3 0 00 0 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 24K n TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE END OF LINE DEVICE 3.6K 1/4W) SUPERVISED 1 SWITCH NAC -4 NAC -3 NAC -2 NAC -1 f FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE DEVICE LOOP 0 0 0 eT FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY C'S' CABLE) FROM FACP <VOICE CIRCUIT) C'V' CABLE) 470 OHMS IW EOL T M-1 0 0 IMi 0 TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE: NO E EARTH GROUND .. .(+)TO NEXT DEVICE OR 1 >(-) STOP IF LAST DEVICE 1 (+) (-) STROBE SPEAKER (0 0 .1 STROBE(-) (+) O STROBE SPEAKER (+) (-) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY R 80" A.F.F. 4S DEEP BOX W/ 1-1 /2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE=NONE TO NEXT DEVICE OR END OF LINE TO NEXT DEVICE OR END OF LINE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERA11N TEMPERATURE: +32' F 0- C) TO 100' F 36 C) HUMIDITY: 0- 9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE fDATA IN (-) > DATA IN (+) > DEVICE IS LISTED FOR MR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID CEILING SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX.- ig� WITH 1-1/2' EXTENSION• \, \, CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKER/STROBE MOUNTING (DROP CEILING) SCALE=NONE JUNCTI❑N B❑X-----'.\ MOUNTED ON \ CEILING FLEX \ JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT / / 4 0 0 I TO NEXT DEVICE 0 0 CADDY BAR SMOKE DETECTOR ---- SMOKE- SMOKE DETECTOR MOUNTING SCALE=NONE \ SUSPENDED ILLUMINATED CEILING DO NOT I \ ST ' LL ADDRESSABLE N T DEVICES INIJ PREPROGRAMMED W DEVICES ADDRESS. AT 106 T NG Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved z z 65. 44 z 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z Q DESCRIPTION SHOP DRAWINGS DATE 1 2 aa<a< 0 uJ J —J++ LL 0 >W J CC 0 CC 1 0 SCALE: 1 /8"=1 DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: \OB NUMBER: SHEET FA -02 V J D,S,2V O DOWN 1 A(` -1V ------------------ 11 R1-21 UP TO MAC 6 VA -1 —5 2S 2A-1-6 15cd V2A-1— 5 `-i \11 1 1 !-i _ ---_ 1, 1 , � 1 1 ( , I '.I_\... -t- i 1 1 i \ 1 i 1 \T i' 1 '1 1 1 \I III 1 \\ l __ (-� <1 ------ ------- ------- z i 15 off`'\ 1 • ( 15cd V2A-1-4 `11 I\ I\ 1 11'I I II( 1\ — — — --1 • --- �_-� — r— -==T ____---------- 11 MAC -1 R ii 111 1 D 0W\11 I 111 s� \ / - - 1 -. •`"'111 1 Dy1moR(,\ 11 1 la ES,EV IhGO✓L& , ‘• i, \, • 1, F,L-1144. 1, \Va 11 s., ,- -- 1\_I 1 \101 ,-_ ' �-' ! -r- 11j1 II----- •- �\\\\ \ \ \\ n \\ \� Il \\ \\ \\ \ \\\,`` i1 `\ 5.'H_F.� `\ `;\\\ , \\ — \ �--- �\\ \\ ti - ,1\\ - \ . • EZEE 2A -1-g' ,1 110cd NORTH •-fl \ ----- \ I1 1\ 111 '•1 —`� A i `_� 111 t y CHARLEY'S GRILLED SUBS WESTFIELD SOUTHCENTER MALL SCALE 118"=1' 1 1 '' 11 III1 I 1• 1_ i • ( { FLAG NO ES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE, FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITSI(SEE SIEMENS INSTALLATI❑N SUBMITTAL FOR L❑CATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR. SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL, FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. PLA S NOT APPROV DO NOT INS -AL_ ADDRESSABLE !NOT A I ISG DEVICES U\TIL PREPROGRAMvED WI -H DEVICES ADDR-SS. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved CO 0' 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: NVI DESCRIPTION SHOP DRAWINGS DATE 5/15/08 2 <<a« (1) cn (/) 0 W —J J E 0 (r) W J CC 0 J CO < 2frzO) w wp cn w° _Z cc cf) gp< <Co 0 coo F_ CV F_ / W SCALE: 1 /8"=1 DRAWN BY: ,.ANDERSON DESIGNED BY: R.VEZZANI DATE:5/1 2/08 BACKROUND PLAN PROVIDED BY: 1.08 NUMBER:XXXXXXX(XX SHEET FA -03, t'- -1- --J. 1•1-flI1' 0,, 0 :,t •�d ,t 1I 11 1' J�= lJ* !NII I NI VIII IIID -- SYSTEM CALCULATIONS a 0 !; '/ -- �1r -� _ - \\t--r"`_a\ \1_� \ ,\ -� " ~- 1\, t,.._y\\..,:_,,_,,:c-i.E.-:5k----5.\\:;,::\‘\\,.\‘‘,\\,\\\" t. ms'r 1 ,� iJ NORTH r - i (Tr-- 1in-- ,41 ---- BATTERY SZING CALCULATION 0 0 /0 \c - \ tit it C __ -1 , B L . ti d 1 - / -1 CHARLEY'S GRILLED SUBS WESTFIELD SOUTHCENTER MALL :: SCALE 1132'=1' EX t I. CHARLEY'S GRILLED SUBS CHARLEY'S GRILLED SUBS FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL DATE co 0 Panel: CHARLEY'S GRILLED SUBS Wire Resistance 1.62 Date: June 10, 2008 CURRENT TOTAL=1 162 Current Load: Standby: Alarm: Current Load: Standby: Alarm: QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 1 SET -MC @15CD 64 64 • Total Wire Resistance (R) 0.62 Device Type SET -MC @30CD Qty Amps Total Amps Total (WL * 2 ) * (R/ft) Device Type 0 Qty Amps 0 Total Amps Total Total Device Load, Amps (1) HFP-11 0 SET -MC @11OCD 0.0022 0.0022 0.0023 a (Total Cct Load) 0 SET-HMC-C@115CD 318 0 ■ AD2-P 0.10 1 0.0635 0.0635 0.064 0.064 Main System Board (E= 1 * R) EOL Voltage 1 - 0.03 - 0.03 0.030 0.030 0 HTR -R 2 0.009600 0.0096 0.021 0.042 64 SET -MC @15CD 1 0.064 0.064 98 HTRI-D - 0.001600 0.0035 0 SET-MC-CW@110CD SET -MC @30CD 0 1 0.098 0.098 2 ICP -B6 162 191 20.29974792 0.005 ■ SET -MC @75CD 0.175 • Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL SET -MC @110CD Panel: 0.233 Wire Resistance 2ss Date: June 10, 2008 CURRENT TOTAL= 3.6 SET HMC-C@115CD CIRCUIT: SPEAKER CIRCUIT 0.318 QTY Device Type Alarm Current Alarm Total Wire Size SET HMC-C@135CD Voltage at EOL Circuit Total 0.318 70.7V1/8 1.8 3.6 0.0731 Amps 0.106 Amps SET HMC-C@185CD ZR -MC @15CD 0 0 0.445 0.064 ( WL*2 )*(R/ft) 0 Standby Current Load: 0 0.0731 Amps For 24 Hours = 1.754 Amp -hours Total Device Load, Amps (I) (Total Cct Load) ZR -MC @30CD HCP 0 0.098 0.0015 0 0 Alarm Current Load: ( E) 0.106 Amps For 5 Minutes= 0.009 Amp -hours . (E= I* R) EOL Voltage 0.03 Amps 0.192 Amps 0 0 0 0 (20.4 - E) 0 0 0 25% Derating= 2.204 Amp -hours Standby Current Load: 0 0.03 Amps For 24 Hours = 0.720 Amp -hours DEVICES= 2 TOTAL mA, 3.6 14 191 20.39645198 3.6 1 _. � 9 Alarm Current Load: 0.192 Amps For 5 Minutes= 0.016 Amp -hours Total System Current Load: 2.204 Amp -hours 25% Derating= 0.920 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.920 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SZING CALCULATION 0 0 /0 \c - \ tit it C __ -1 , B L . ti d 1 - / -1 CHARLEY'S GRILLED SUBS WESTFIELD SOUTHCENTER MALL :: SCALE 1132'=1' EX t I. RISER DIAGRAM VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved lam eel Itt 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: NVI Notification Appliance Circuit Detail DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL DATE co 0 Panel: CHARLEY'S GRILLED SUBS Wire Resistance 1.62 Date: June 10, 2008 CURRENT TOTAL=1 162 CIRCUIT: S1 QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 1 SET -MC @15CD 64 64 • Total Wire Resistance (R) 0.62 1 SET -MC @30CD 98 98 r (WL * 2 ) * (R/ft) 0 SET -MC @75CD 175 0 Total Device Load, Amps (1) 0.16 0 SET -MC @11OCD 233 0 a (Total Cct Load) 0 SET-HMC-C@115CD 318 0 ■ Voltage Drop ( E) 0.10 0 SET-HMC-C@177CD 445 318 0 0 ■ (E= 1 * R) EOL Voltage 20.30 0 SET -HMC @135CD 0 SET -HMC @185CD 445 0 (20.4 - E) 0 Z-MC@15CD 64 0 0 Z-MC@30CD 98 0 ■ 0 SET-MC-CW@110CD 233 0 DEVICES= 2 TOTAL mA= 162 191 20.29974792 162 ■ • Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: CHARLEY'S GRILLED SUBS Wire Resistance 2ss Date: June 10, 2008 CURRENT TOTAL= 3.6 CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 70.7V1/8 1.8 3.6 Total Wire Resistance (R) 0.99 0 0 0 ( WL*2 )*(R/ft) 0 0 0 • Total Device Load, Amps (I) (Total Cct Load) 0.00 0 0 0 Voltage Drop ( E) 0.00 0 0 0 . (E= I* R) EOL Voltage 20.40 0 0 0 0 0 0 (20.4 - E) 0 0 0 0 0 0 DEVICES= 2 TOTAL mA, 3.6 14 191 20.39645198 3.6 1 _. � 9 RISER DIAGRAM VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved lam eel Itt 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: NVI DESCRIPTION SHOP DRAWINGS DATE co 0 J c0 Q T- T- O �o) z cc 2__ C'# < JCC D � u' U SCALE: 1/8"=1' CC tr= w z w z 0 U U w DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: \JOB NUMBER:54511 SHEET FA -04 a}1 GENERAL NOTES 1. Western States Fire Protection to add and/or relocate existing sprinklers due to new walls and ceilings being added for the tenant improvement from existing fire sprinkler piping. 2. Sprinklers shall be spaced in accordance with NFPA #13 with a 15'- 0" maximum distance between sprinklers. Maximum coverage area of 130 sq. ft. at Ordinary Hazard Occupancy. 3. All hangers' assemblies shall be spaced and installed in accordance with NEPA-13 & manufacture's specifications. 4. All new sprinklerr inkier drops and arm -over pipee isblack schedulehedule 4 0 pipe.e. ductile iron class 5. All new threaded fittings are cast iron class 125 or due t 150. 6. The owner is responsible for all apprriate maintenance ee of sprinkler er & local codes. system in accordance with NFPA, as wellstate as 7. FlexHead fire sprinlder assemblies to be used to attach fire sprinklers at ceilings. 8. Existing fire sprinlder system to remain. Western States Fire Protection will modify the existing system only in the areas of work shown. All other areas are not in contract and WSFP is not responsible for existing conditions. FtexHead Suspended Ceiling Detail Each FM -approved unit is ready -to -install, pressure- and leak -tested, and comes complete with a flexible stainless-steel hose and mounting bracket with adjustable hub. Multi -port ceiling grid mounting bracket FtexHead sprinkler drop ti Adjustable hub Sprinkler branchline Suspended t -bar grid Sprinkler head FlexHead Metal Stud Sprinkler branchline FtexHead sprinkler drop Adjustable hub .FF7. Ceiling file Multi -port metal stud mounting bracket Metal stud RETAINER TRAP C -CLAMP WITH f LOCKNUT `�- ALL THREAD ROD PIPE RING C—CLAMP HANGER W,/RETAINER ,STRAP Sheetrock ceiling Sprinkler head ea: • B.O. SOFFIT T-0' AFF. E G-2 B.O. CEILING I2'-10" AFF. CDNC DECK FLAT DR CDRR HILTI SWI HILTI KWIK-BOAT \d/ROD COUPLING FIG. 100 ALL THREAD RDD �-- FIG. 200 ADJUSTABLE RING HANGER <-3 LT HANGER OE N ®N B.O. CEILING II' -O" AFF. G -I B.O. CEILING -i'-O" AFF. Fire Sprinkler Plan Scale: 1/4" = 1'-0" SYMBOL LEGEND Existing piping New piping Mech. Tee cut into existing pipe Hanger notation see detail Existing Upright sprinkler New Concealed pendant sprinkler New Dry pendant sprinkler G-2 G-2 11118.0. SOFFIT B.O.SOFFIT 11-47 AFF. C-2 12'-O" AFF. 5-1 V.7,..7.NITY MAP /Y" L .. •6�44rr,, • L •#. • R,? �.(�,r '.a X77' • ` 4,444;04-_ M' ,yy.+MMR! ,. pY lt41±a5 :{j�{'f` , i'6rS rr': ib.w.' k'a Yrtb•;.,uV• ,b '.; -.a •k�.."�, l $ a ., .•'$.. l - ,, r ..,„ 'j'' -1 ax nwry•Pp_ r11 7.. r �r M t4� ? V � . � • .7�}....�M >.` I{. j „'RWF•i' I'3J • i� • �1 '. 1 '(+"h ��• 7�t� ,',�' {,.., ��%A •#a v;, 1J, '•a .,.j ,'"wyy ,r:.`f • P,tvT.s.:...,rr k.,.. tl•{N4.o;.?•••V4 ""'(;� "55Al '- ,•�,-.' i S • `fid • o� i ,` inr,r .' 9 6'JJM1/7.4\.+H'A�k '..,,..rI . •`fl'.1::—....7..?i'...:;;)..-„ ,�,�' ,'}.i,•,.;4.i. ;?'�.r,Jw: 'i.• eszC.;,. .y' rk.a~ hsy,f !�W�'WL •LSu e:.:51vd•7 r,f:..Y'N •R L - ,j{�aL' . ` jb " �syuv ;7' . .': `i J',•Y.'.Lti!•,,. '}"r,•, 'i M:aLL •��+�1':.aMr,}w •:tar..{�cyjf.. i. .diY;4'M."J ". .,9 ' .h .7rr :p' �u'`Y - 4*"i,!'�M c 1.. r �,� • �4 •- 'na"v,•n•'. r'.Ei;`;f ' ` e..a.w•;r •,,,....• ' .?3 . • 'et'y `�,`�}&,`{ n.��, ��lWy.ti�." . • A ? : P 3, -I �a 'Mr �' : ...H FF l ,• , ys',]i•y �li Or1 _aYu • .,/jJ ;i'Yn' Gfv. f14, ' s-�7,•"''>m'�L�rYe+r•rY s ':K.+i".siixfkr i�Jw,N.!.atc.Y yrq.r�s.i � ' . •rVS'.c • } t W rN .uvl!<i/(n"nY 1tiif-t L( i { 2 }msµ �•2. t. .•,..rA. +saw` <'n,r _ . • N:Yqi .rYCi•v•.; om, F Mtt¢E1.QvfrJyii41pr4�.:aea. •.,,:Jun. , • + . dV:'.:.L,`,-r'r,;$q'.a$ ...C��f� . 1� li, " : Y �;J , ,.,.„- : ,Kw,.e,Hut`rl.f"a,. ,.wR• ::.•;.1 r ,J'4 � .! or �1Y.,.w.�BAa ter}} r4( 1.'k ' 6 Of' . .:. �r f FrP�, , .y,. M'wNv :. i4t :r•evr.#.. . \ 7. i,' -FDy.�:' ti • Vi Ir i f;`•fw:.- . k. s L ,f. '. .Y �,f' K74..., 3? ' • Jy •' Y:,L;��.:rr'�t �t. t , ^M�nl' �6 R• 0 1. •N �J ,i.r r t � ttfJ' .` .,. . '#)s.:fir ,rmtrAr,;r,:i�i• •n ,l,a.{••}?:a'%"r �rtk,'firi.M�'� �YctidNa� X,)�7':� . 3''''' , .• X' ' 4 4 > 3, .} �. . •,:„, ,w.�,, • t a_ .,m. .r. '�i, 'TVI ftaa ai• ;'.. N•.',:497#Y6ttb4{.` w. . ce I., 4Y i ,..1.� •w . �9F•� , •�:t 4 r :,.. _ ' 1s;: :.•iVE„... J" wri ; • •; ..,, ,l .t• .,.,...,,t. ..aa . _ � . ,, .,.�.: , .:>s x,- .. :,. N,i.4 • y.jk,.D,.. ,. 5',,. ' y 1AtiM eNa{:,r PROJECT LOCATION merayRro . • w�ae I NORDSTROM mac ftl"ba•-01 III• II Mtt,IM] lai I7 . , ,. ���,,qq LII 1. d • . 1k, , ij IN .. til • - `�I, �.. ;�T . r , I. 1. - • r' 1.. mane • i• �rk` �II: �� ��ti� o. J 1 :. `.',�., at,rte— , — is err0 .U'�‘i r I *Woo \— FOOD COURT......-... � ■- is ' ....,_.._.. r• _.... — , SOUTHCENTER MALL LEVEL 2 OF 3 C NOW 1l w 4 . r„: fctt”, iP j Vit,Thout Corn As Noted In - .. R . ,j ., _ nese evention • - Per The Attact. -. iave been reviewed Bureau for conformar}C's`WL11 ed Itter by The �'----_. _ stta.w>r. L .;• `nc- s•.cttoer\- - ® omi K di I thi ` ionE • aro: ►- ions, - c. whr enc of cosign deletion o '- • tori o ,. {Y - �b. re or rgisio id th'Saccept The - I n 4- iolati respgno with the to these a an EN _ bD COUR re 'ltbmitt- ---„jsi,- of vise, . Q - ccepiankeiss bject ''T- ila Fi '� Pre - - in O •n s t• l for subs eidtest reau. = E 'STING ® , ® o . E PLOYEE �� •il -„� 0 `; To LETS c z + Date: =YY y ilO I 'I i�li iJ'i i. I�E tea' 1 i _,,,_. I'LL., ,T,�. HD o rtl li {��f � / PLROJECT ® ® , _r�.r . ION L�L��'_��__ 11.1. (91: Jm 70. . 71-.4111117 rY i0 I AugJ TSI I. •- .. rUKwlw rlf3t ut: Weld stamps must be Please call; 575.4407 PUBLIC • inspected before pipe is and give this job RESTROOMS hung. Do not paint pipinTo. _, •7 NORTFJ riot• to hydrostatic test and exact address fors SOUTHCENTER down or at apuroval, + FOOD COURT - LE' JVc1 I ' pi 4,1 Tukwila Fire current city rs and ms of adopted ibility for the designer. drawings atter ill require a equent approval. d inspection by 7e0 GENERAL NOTES r.; r1 uesiyn and installation in accor- dance with NFPA Standards. ,;R materials to be Underwriters Labora- ;.ries Listed and / or FM approved. . Overhead piping to be black steel :Lontorming to specifications of . 1M A795, ANSI / ASTM A53, ANSI :3 i.1OM, ASTM A135. AREA OF •o. RATIN HYDRAULIC DESIGN INFORMATION SYSTEM DESIGN FLOW TEST REVISIONS DESCRIPTION SPRINKLER LEGEND DESCRIPTION ORIF. TEMP. FINISH NO. REQ, DEVICE MFG. DESCRIPTION OFIF. TEMP. FINISH MAX. AREAIHEAD RESIDUAL GPM FLOWING DATE & TIME Western States Fire protection Company 7102 - 180th AVE. NE, SUITE A-105 • REDMOND, WA • 98052 WESTERN STATES ARE PROTECTION COMPANY -- OFFICES LOCATED DENVER / RAPID CITY / MINNEAPOLIS / DULUTH / DALLAS / HOUSTON ALBUQUERQUE / AUSTIN / SEATTLE / PORTLAND / PHOENIX / KANSAS CITY / ST. LOUIS Phone; 206-881-0100 WA. Reg. # WESTESF136QF CHARLEY'S G " LLED SUBS 2600 Southcenter Mall, Space FC -9 Tukwila, WA 95188 JUL 8 2008 {k Tukrila Fire .2.16.(r if/W%