HomeMy WebLinkAboutPP - 1374 SOUTHCENTER MALL - WHISTLE WORKWEAR - PERMITS AND PLANS1374 SOUTHCENTER MALL ASSOCIATED PERMITS 10-S-117 10-H-150 e IL. FIRE DEPARTMENT HOOD SUPPRESSION PLAN REVIEW COMMENTS Project Name: Red Ribbon 1374 Southcenter Mall Permit No.: 10-H-150 Date: July 22, 2010 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Nozzle heights above appliances to be per manufacturers installation guidelines. • Fryers shall be installed with at least a 16 inch space between the fryer and surface flames from adjacent cooking equipment or a minimum 8 inch high steel or tempered glass baffle plate shall be installed between the appliances. • Upon activation of the suppression system, the make-up air supply will shut off and the exhaust will keep running. • Type 1 hood systems shall be designed and installed to automatically activate the exhaust fan whenever cooking operations occur. The activation of the exhaust fan shall occur through an interlock with the cooking appliances, by means of heat sensors or by means of other approved methods. • Activation of the suppression system shall shunt all electrical power under the hood as well as the gas supply. • Install a "K" rated portable fire extinguisher within 30 ft. of the cooking equipment. • The hood suppression system shall be monitored by a U.L. Central Monitoring Station. • The suppression system manual pull station shall be located no closer that 10 ft. and no farther than 20 ft. from the cooking equipment and be placed at a height of 42 to 48 inches above the floor. • The inside lower edge of the hood shall overhang or extend a horizontal distance of not less than 6 inches beyond the edge of the top horizontal surface of the appliance on all open sides. The vertical distance between the front lower lip of the hood and such surface shall not exceed 4 feet. 08/17/2010 11:12 2067672607 RT HOOD & DUCT RTS � Heed di Ned Scr.lret, 1.c, Isrito.dmilihasimmu. d100 17+ Av. S. s.orit wA 41130 r.... aoil +sdt.o noipormum ATTENTION:. cc__ COMPANY t414_____ FROM: NUMBER OF PAGES: (Including Cover) COMMENTS: iS V DATE: FAX #: PHONE #: 1 t� l3 e� 4+ C) -AJ c tS PAGE 01 FAX COVER SHEET o 92.5.5 5 . i1 H 2-Lt 5 -"e‘taAiste- afk (4 144 ov•c cev s. 08/17/2010 11:12 2067672607 RT HOOD & DUCT PAGE 02 z 0 H m 1 1 a to cu 3 3 L v m 0 m ■ ns s�m 0 41 Pk - oma x fl I co o a_ y 0 n ■ 1 m -c 0* _- 0 j m 4 y wtM Jre oga 3 0 0— I:1IdV1IM}Inl 0 % ■■ =e» C// %am k¥° E 2 Ai/ 7! } §FIT a c 0 \ G ntij 2: A. 5 \ Q. 0 CO5 § E - E\ E koM 2�k CD0 �/} } ■ /E§%ƒ JRa53 q ; ƒ e ] =n%oo me CD ! { k \ 0 ° .1 o a J;2K 0 la D £�-- 0 0 S A 0 a co z rn > b9 00 E § _ S£ SZ .,917-0t7 § NOT1VO £ lf1SN'd / 4 0001-1 NI 6 lJ tr S11NI1 3SIld x09£ 0 m§X, \}Fe ¥ xc c2 „=— ƒ 2\ \ \§a{ k\k§ n qpm >¥® 0 \2K m - o, \� 2E ;-0-1 j 0, CI Without Comments o As Noted in Red g Per The Attached Letter ese plans have .,,2(:n reviewed by The Tukwila Fire ;ventlon Burtd J f ; Lnnl ormance with current City -.=ndards: Accertzirc� is subject to errors and :.. nissions which do not authorize violations of adopted .;:andards and orvir?races. The responsibility for the Adequacy of design r : is totally with the designer. .dditions, deletion ; evisions to these drawings;after this date will volu rt- • .L ..t.•nce and will require a resubmittal of re, -r,,' draw'ot�s for subsequent approval. Final acceptance is yupject to „old test and Inspection by The Tukwila Fire Prevention Bureau. - �.� — c7 By: .s�71 Date: - •t46,w4LA riRE oEPAt2T ?tease call: 575.4407 and give this job No. /0 -i4- -C1) a rid Flxact address for shut. . •wn or restoration aoorovai •. • R -102T" RESTAURANT SYSTEM DISTRIBUTION PIPING REQUIREMENTS SHEET Distribution 'iping Requirements -1.5 Gallon (5.6 Liter) System tt Requlremen s Supply Une Duct Branch Line Plenum Branch Une Appliance Branch Une Pipe Size Maximum Length Maximum Rise Maximum 90° Elbow Maximum Tees Maximum Fibw Numbers 3/8 in. 40 ft (12.2 m) 6 ft (1.8 m) 9 1 5' 3/8 in. 6 ft (1.8 m) 4 ft (1.2 m) 4 1 2 3/8 In. 4 ft (1.2 m) 2 ft (0.6 m) 4 2 2 3/8 In. 10 ft(3 m) 2 ft (0.6 m) 6 3 3 ° Exceptionls: 1. Six (6) flaw numbers are allowed when a duct branch line Is the last branch line on the piping network and no 1N nozzles, Part No. 56930, are used to protect woks or griddles. 2. Six (6) f cw numbers are allowed when six (6) 1N nozzles, Part No. 56930, are used and none of the nozzles are used to protect woks and griddles. Note: Only five (5) flow numbers are allowed If a 1N nozzle is used for wok or griddle protection. 3. Six (6) flaw numbers are allowed when only two (2) 3N nozzles, Part No. 76782, are used. Distributio)f Piping Requirements -1.5 Gallon (5.6 Uter) System 1. This option allows for duct protection, plenum protection, appliance protection, or any combination. 2. When using a combination of plenum and duct protection only, only one duct nozzle, either a 1W, 1100, or a 2W, may be used. 3. The ma$imum length between the start of the first branch line and the start of the last branch line must not exceed 8 ft (2.4 m). When the supply line is split, the combined total of both legs of the supply line (from the start of the first branch line to the start of the last branch line) must not exceed 8 ft (2.4 m). 4. The total length of all branch lines must not exceed 22 ft (6.7 m). 5. Use a th8 in. union to connect the tank adaptor to the 3/8 In. supply line. Distribution illping Requirements - 3.0 Gallon (11.3 Liter) System Requirements Supply Lina Duct Branch Une Plenum Branch Une Appliance Branch Une Pipe Size Maximum Length Maximum Rife Maximum 90° Elbow Maximum Tees Maximum Flew Numbers 3/8 In. 40 ft (12.2 m) 6 ft (1.8 m) 9 1 11 • 3/8 In. 8 ft (2.4 m) 4 ft (1.2 m) 4 2 4 3/8 in. 4 ft (1.2 m) 2 ft (0.6 m) 4 2 2 3/8 In. 12 ft (3.7 m) 2 ft (0.6 m) 6 4 4 *Exception*: 1. Twelve (1 ) flow numbers are allowed in any one tank for hood and duct protection. 2. Twelve (1 ) flow numbers are allowed with any one tank using only two -flow appliance nozzles. 3. Twelve (10 flow numbers are allowed with any one tank using only three -flow appliance nozzles. Special Instfuctions: 1. Twelve (1) flow numbers are allowed when four (4) Dean Industries GTI Gas Fryers are protected at low proximity. 2. For certain McDonald's applications, 11.5 flow numbers are allowed when using a combination of one (1) 2W duct nozzle, one (1) 1/2N el tic precipitator nozzle, one (1) 1N plenum nozzle, and four (4) two -flow appliance nozzles. ContactANSUL Applica s Engineering Department for additional information. Distribution Piping Requirements - 3.0 Galion (11.3 Uter) System 1. The maiimum length between the start of the first branch line and the start of the last branch line must not exceed 24 ft (7.3 m). When the supply line is split, the combined total of both legs of the supply line (from the start of the first branch line to the start of the last branch line) must not exceed 24 ft (7.3 m). 2. The total length of all branch lines must not exceed 38 ft (10.9 m). 3. Use a 3/8 In. union to connect the tank adaptor to the 3/8 In. supply line. it ANSLJL. Vico R-102 RESTAURANT SYSTEM ARrnSBupuppnsslon olnp Products NOZZLE COVERAGE/OVERLAPPING SUMMARY SHEET Plenum 1 Nozzle Type Flow Points Width In. (cm) Max. Side Length In. (cm) Max. Side Nozzle Placement (See Manual for More Detail) Min. Height In. (cm) Max. Height in. (cm) Horizontal Protection Single Bank 1N 1 48 (122) 120 (305) 0 in. to 6 in. (0 to 15.2 cm) from end of plenum 2 (5) 4 (10) Perpendicular Protection Single Bank 1W 1 48 (122) 48 (122) See Manual for more detail 1 (2.5) 20 (51) Horizontal Prote):tion V -Bank 2 x 1N 2 48 (122) 120 (305) 0 in. to 6 In. (0 to 15.2 cm) from end of plenum 2 (5) 4 (10) Horizontal ProteOtion V -Bank 1 W 1 48 (122) 72 (183) 0 in. to 6 in. (0 to 15.2 cm) from end of plenum 1/3 the height of filter Perpendicular Pjotection V -Bank 1 W 1 48 (122) 48 (122) See Manual for more detail 1 (2.5) 1 20 (51) Duct Nozzle Type Flow Points Perimeter In. (cm) Diameter In. (cm) Nozzle Placement (See Manual for More Detail) Duct Length in. (cm) Single Nozzle 1 Flow Nozzle 1W 1 50 (127) 16 (41) See Manual for more detail Unlimited Single Nozzle 2 Flow Nozzle 2W 2 100 (254) 31 7/8 (81) See Manual for more detail Unlimited Multiple Nozzle ; 2W + 1W 3 135 (343) 48 (122) See Manual for more detail Unlimited Multiple 2W Nozzle 2W — >135 (343) _ >135 (343) See Manual for more detail Unlimited R-102 OVERLAPPING PROTECTION The 245 nozzle, Part No. 419340, must be used for "end of zone protection, and the 260 node, Part No. 419341, must be used for 'zone protection. Appliance Type Maximum Cooking Hazard Fryer 34 in. (864 mm) Deep x 5.8 ft2 (5388 cm2) Griddle 30 in. (762 mm) Deep x Unlimited Length Range 30 in. (762 mm) Deep x Unlimited Length Wok, Maximum 30 In. (762 mm) Diameter x 8 in. (203 mm) Deep Wok, Minimum: 11 in. (279 mm) Diameter x 3 in. (76 mm) Deep Braising PanITi)t Skillet' 34 in. (864 mm) Deep x Unlimited Length Lava Rock Char -Broiler 26 in. (660 mm) Deep x Unlimited Length Charcoal Broiler 30 In. (762 mm) Deep x Unlimited Length (4 In. (102 mm) Maximum Fuel Depth) Mesquite Wood Broiler 30 in. (762 mm) Deep x Unlimited Length (6 in. (152 mm) Maximum Fuel Depth) Gas Radiant Char -Broiler 36 In (914 mm) Deep x Unlimited Length Electric Char -Boiler 34 in. (864 mm) Deep x Unlimited Length ' See Figure 1 for nozzle location. Note: Group protection option Is required for appliances on either side of an apptance(s) using dedicated protection — see manual tor details. Ifi COVER MUST NOT INTERFERE WRH EDGE OF DISCHARGE PATTERN 0.121N 1i(0.305mm) 1 • 1 1 it 1 ZONE ZONE CENTER UNE Overlapping System Piping Limitations Total Max. 3/8 in. Max. Maximum System Flow Pipe No. of Elevation Cartridge Size Numbers Length Elbows Rise Size 3 Gal (11 L) 6 75 ft 25 10 ft LT -30-R (22.9 m) (3.1 m) 6 Gal (23 L) 12 75 ft 25 10 ft Double Manifolded (22.9 m) (3.1 m) Tank 50 ft (15.2 m) maximum pipe from first to last nozzle. 50 ft (152 m) maximum pipe after the split on a split system. FIGURE 1 ANSUL NCORpORATED. OPE STANTON STREET. MARIPETTE. WI 54143-2542 715-735-7411 Form No. F-2005010-2 Copyight 0200e AnsU Incorporated a ANSL JL. 'two Fire Suppression & Building Products R-102 RESTAURANT SYSTEM NOZZLE COVERAGE/OVERLAPPING SUMMARY SHEET Appfance Nozzle 'type Flow Points Width in. (cm) Max. Side Multiple Length let. (cm) Max. Side Multiple Nozzle w/o Ddp Board Area int (cm2) Nozzle w/ Drip Board Area h2 (cm2) Minimum Nozzle Ht In. (cm) Maximum Nozzle HL In. (cm) Fryers without drip boards *Low Pra Split dr No Split Vat Fryers withot¢ drip boards Non -Spilt Vat (ONLY) 230/290' 2 14 (36) 15 (38) - - 27/13 (69/33) 47/16 (119/41) 245/290* 2 14/14.5 (36/37) 15/14 (38/36) - - 20/16 (51/41) 27/27 (69/69) 290 2 19.5 (50) 19 (48.2) - - 13 (33) 16 (41) 3N 3 19.5 (50) 19 (48.2) - - 21 (53) 34 (86) 3N 3 18 (45.7) 18 (45.7) - - 25 (64) 35 (89) Fryers with drip boards 'Low PredmAy Split dr No Split Vat' 230290' 2 14 (36) 21 (53) 210 (1355) 294 (1897) 27/13 (69/33) 47/16 (119/41) 245/290* 2 14/14.5 (36/37) 21/26.5 (53/67) 210/203 (1355/1310) 294/384.2.(189712479) 20/16 (51/41) 27/27 (69/69) ,Fryers J witt drip boards' Non -Spin Vat (ONLY) j 290 2 19.5 (50) 25 3/8 (65) 370.5 (2390) 495 (3194) 13 (33) 16 (41) 3N 3 19.5 (50) 25 3/8 (65) 370.5 (2390) 495 (3194) 21 (53) 34 (86) 3N 3 18 (45.7) 27 3/4 (70.5) 324 (2090) _497 (3206) 25 (64) 35 (89) Til SId11et/Braisirig Pan' Coverage limitation are based on fryer sizes including the drip boards. Exception: Tilt Skillets and Braising may exceed the maximum of 6 ft2 (0.56 m2) Range ^' Without back shell With back shell' Wdhdut back shelf Oh back shelf' • Longest Side Max Area in' (cm') 1N 1 12 (30.5) 32 (81) 384 (2477) - 30 (76) 40 (102) 1F 1 12 (30.5) 28 (71) 336 (2168) - 30 (76) 50 (127) 1F 1 12 (30.5) 28 (71) 336 (2168) - 40 (102) 48 (122) 245 2 24 (61) 28 (71) - - 40 (102) 50 (127) 260 2 24 (61) 32 (81) 768 (4955) - 30 (76) 40 (102) 260 2 12 (30.5) 32 (81) 384 (2477) - 30 (76) 40 (102) 2 x 290 4 36 (91) 28 (71) 1008 (6503) - 15 (38) 20 (51) Griddle 1N/1NSS 1 36 (91) 30 (76) - - 35 (89) 40 (102) 290 2 30 (76) 24 (61) - - 30 (76) 50 (127) 260 2 48 (122) 30 (76) - - 30 (76) 50 (127) 290 2 48 (122) 30 (76) - - 20 (51) 30 (76) 2120 2 48 (122) 30 (76) - - 10 (25) 20 (51) Chain Broiler' (Overhead Protection) 2 x 1W 2 34 (86) 30 (76) - - 10 (25) 26 (66) Chain Broiler . (Horizontal Protection) Char Broiler IGas-Radiant ' Electric Lava -Rock Natt*al Charcoal' Lava -Rock or Nattlral Charcoal' V/ood Fueled' 2 x 1N 2 31 (79) 43 (109) - - Front edge; 1 to 31n. (3 to 8 cm) above the chain 1N/1NSS 1 24 (61) 36 (91) - - 15 (38) 40 (102) 1W1NSS 1 20 (51) 34 (86) - - 20 (51) 50 (127) 1W1NSS 1 13 (33) 24 (61) - - 18 (46) 35 (89) 1 N/1 NSS 1 12 (30.5) 24 (61) - - 18 (46) 40 (102) 3N 3 24 (61) 30 (76) - - 14 (36) 40 (102) 3N 3 24 (61) 30 (76) - - 14 (36) 40 (102) Upright Broiler Salamander Broiler Interhal Chamber 2 x 1/2N 1 30 (76) 32.5 (82.5) Front edge; above the grate 2 x 1/2N 1 30 (76) 32.5 (82.5) - - 1N 1 16 (41) 29 (74) - - - - 1N nozzle location to be on the vertical edge 6 to 121n. (15.2 to 30.5 cm) in front and 0 to 12 in. (0 to 30.5 cm) above the top of broiler 1N 1 16 (41) 29 (74) - - 6-12 in. above either end (15.2to30.5cm) Wok 3.75 too 8 In. deep (9.0 to 20.3 cm) 3 to 6 In. (7.6 to 15.2 cm) deep 260 2 14 to 301n. (36 to 76 cm) diameter - - 35 (89) 45 (114) 1 W1 NSS 1 11 to 24 In. (28 to 61 cm) diameter - - 30 (76) 40 (102) 'For muttipb nozze protecnon of single fryers. see detailed Information on pages 4-8 to 4-11: of manual. ' See Figure 1 for dozzle location. ► ' Minimum chain boiler exhaust opening -12 In. x 12 In. (30.5 cm x 30.5 cm), and not less thanI60% of Internal broiler size. ► ' 4 in. (10 an) maximum fuel depth. • 6 In. (15 cm) maximum fuel depth. • Shelf can overhang bumer(s) by maximum of 11 in. (28 cm) and height (imitation of 20 In. (51 cm) from bottom 01 lowest part of shelf to the top of bumer grate. ' Shelf can overhang bumer(s) by maximum of 11 In. (28 cm) and height ► limitation of 18 in. (45.7 cm) from bottom of lowest part of shelf to the top of bumer grate. • Low Proximity ► :l. ANSUL. tgco Fin Suppression & Building Products R-102RetTAURANT SYSTEM NOZZLE COVERAGE/OVERLAPPING SUMMARY SHEET Appliance i Nozzle Type Flow Points Width in. (cm) Max. Side Multiple Length in. (cm) Max. Side Multiple Nozzle w/o Drip Board Area int (cm2) Noah w/ Drip Board Area 1,12 (cm2) Minimum Nozzle lit In. (cm) Maximum Nozzle Ht in. (cm) Fryers without drip boards Pr 230/290* 2 14 (36) 15 (38) - - 27/13 (69/33) 47/16 (119/41) Split dr No Split Vat 245/290` 2 14/14.5 (36/37) 15/14 (38/36) - - 20/16 (51/41) 27/27 (69/69) Fryers without drip boards 290 2 19.5 (50) 19 (48.2) - - 13 (33) 16 (41) Non -Split Vat (ONLY) 3N 3 19.5 (50) 19 (48.2) - - 21 (53) 34 (86) 3N 3 18 (45.7) 18 (45.7) - - 25 (64) 35 (89) Fryers witi1 drip boards • 1"PmximivSplit 230/290* 2 14 (36) 21 (53) 210 (1355) 294 (1897) 27/13 (69/33) 47/16 (119/41) Or No Split Vat' 245/290' 2 14/14.5 (36/37) 21/26.5 (53/67) 210/203 (1355/1310) 294/384.2 (1897/2479 20/16 (51/41) 27/27 (69/69) Fryers with; drip boards' 290 2 19.5 (50) 25 3/8 (65) 370.5 (2390) 495 (3194) 13 (33) 16 (41) Non -Split Vat•(ONLY) 3N 3 19.5 (50) 25 3/8 (65) 370.5 (2390) 495 (3194) 21 (53) 34 (86) 3N 3 18 (45.7) 273/4 (70.5) 324 (2090) 497 (3206) 25 (64) 35 (89) Tilt SIdllet/Bnising Pan' Coverage limitation are based on fryer sizes including the drip boards. Exception: Tilt Skillets and Braising may exceed the maximum of 6 ft2 (0.56 m2) Longest Side Max. Area Int (cm') Range 1N 1 12 (30.5) 32 (81) 384 (2477) - 30 (76) 40 (102) Without back shelf 1F 1 12 (30.5) 28 (71) 336 (2168) - 30 (76) 50 (127) With back shelf' 1F 1 12 (30.5) 28 (71) 336 (2168) - 40 (102) 48 (122) 245 2 24 (61) 28 (71) - - 40 (102) 50 (127) Withdutback shelf 260 2 24 (61) 32 (81) 768 (4955) - 30 (76) 40 (102) Will back shelf' 260 2 12 (30.5) 32 (81) 384 (2477) - 30 (76) 40 (102) 2x290 4 36 (91) 28 (71) 1008 (6503) - 15 (38) 20 (51) Griddle 1W1NSS 1 36 (91) 30 (76) - - 35 (89) 40 (102) 290 2 30 (76) 24 (61) - - 30 (76) 50 (127) 260 2 48 (122) 30 (76) - - 30 (76) 50 (127) 290 2 48 (122) 30 (76) -_ - 20 (51) 30 (76) 2120 2 48 (122) 30 (76) - - 10 (25) 20 (51) Chain Broiler' (Overhead Protection) 2 x 1W 2 34 (86) 30 (76) - - 10 (25) 26 (66) Chain Broiler (Horizontal Protection) 2 x 1N 2 31 (79) 43 (109) - . - Front edge; 1 to 3 in. (3 to 8 cm) above the chain Char Broiler ;Gas -Radiant 1N/1NSS 1 24 (61) 36 (91) - - 15 (38) 40 (102) Electric ' 1W1NSS 1 20 (51) 34 (86) - Jss - 20 (51) 50 (127) Lava -Rock 1W1NSS 1 13 (33) 24 ,(61) - 18 (46) 35 (89) Nadia] Charcoal' 1 W1 NSS 1 12 (30.5) 24 (61) - o.18 (46) 40 (102) Lava -Rock or Natural Charcoal' 3N 3 24 (61) 30 (76) - a 14 (36) 40 (102) Wood Fueled' 3N 3 24 (61) 30 (76) - - 14 (36) 40 (102) Upright Broiler 2 x 1/2N 1 30 (76) 32.5 (82.5) ' '' ont edge; Salamander Broiler 2 x 1/2N 1 30 (76) 32.5 (82.5) - -:F the grate , y 1N 1 16 (41) 29 (74) - - - 1 N nozzle location to be on the vertical edge 6 to 12 In. (15.2 to 30.5 cm) in front and 0 10 12 In. (0 ) a the top of broiler Internal Chamber 1N 1 16 (41) 29 (74) - - n. r end (1 . cm) Wok 3.75 to 8 in. deep (9.0 to 20.3 cm) 260 2 14 to 30 in. (36 to 76 cm) diameter - - 35 (89) 45 (114) 3 to 6 In. (7.6 to 15.2 cm) deep ' For multi len tech 1 N/1 NSS f 1 11 to 24 in. (28 to 61 cm) diameter - - 30 (76) 40 (102) p ozz(e pro ono s ngle fryers, see detailed information on pages 4-8 to 4-11 of manual. 'See Figure 1 for nozzle location. ► 'Minimum chain broiler exhaust opening - 12 In. x 12 in. (30.5 cm x 30.5 cm), and not less than160% of internal broiler size. ► ' 4 In. (10 cm) maximum fuel depth. 6 In. (15 cm) maximum fuel depth. 'Shelf can overhang bume (s) by maximum of 11 in. (28 cm) and height limitation of 20 In. (51 cm) from bottom of lowest part of shed to the top of bumer grate. ' Shelf can overhang bumer(s) by maximum of 11 in. (28 cm) and height ► limitation of 18 in. (45.7 cm) from bottom of lowest part of shelf to the top of bumer grate. Low Proximity laltuum11.1 Vico Fire Suppression & Building Products R-102 RESTAURANT SYSTEM NOZZLE COVERAGE/OVERLAPPING SUMMARY SHEET Plenum Horizontal Protection Single Bank Nozzle type Flow Points Width In. (cm) Max. Side Length In. (cm) Max. Side Perpendicular P4otection Single Bank Horizontal Protebtion V -Bank Horizontal Protea tion V Bank 1N 1 48 (122) 120 (305) 1W 1 48 (122) 48 (122) 2x 1N 2 48 (122) 120 (305) Perpendicular PFotection V Bank 1W 1 48 (122) 72 (183) 1W 1 48 (122) 48 (122) Nozzle Placement (See Manual for More Detail) O in. to bin. (0 to 15.2 cm) from end of plenum See Manual for more detail Oin. to6in. (Oto15.2cm) from end of plenum OIn. to6in. (Oto 15.2 cm) from end of plenum See Manual for more detail Min. Height in. (cm) Max. Height in. (cm) Nozzle Type Flow Points Perimeter in. (cm) Diameter In. (cm) 2 (5) 4 (10) 1 (2.5) 20 (51) 2 (5) 4 (10) 1/3 the height of filter 1 (2.5) 1 20 (51) Multiple Nozzle ; 2W + 1W R-102 OVERLAPPING PROTECTION The 245 nozzle, Part No. 419340, must be used for "end of zone" protection, and the 260 nozzle, Part No. 419341, must be used for "zone" protection. Appliance 1y�e Fryer Griddle Range Wok, Maximum Wok, Minimum Braising Panfli)t Skillet' Lava Rock Char -Broiler Charcoal Broiler Mesquite Wood Broiler Gas Radiant Char -Broiler Electric Char -Broiler See Figure 1 for nozzle location. Note: Group protection option is required for appliances on either side of an appliance(s) using dedicated protection - see manual for details. Maximum Cooking Hazard 34 in. (864 mm) Deep x 5.8 ft2 (5388 cm2) 30 jn. (762 mm) Deep x Unlimited Length 30 in. (762 mm) Deep x Unlimited Length 30 in. (762 mm) Diameter x 8 In. (203 mm) Deep 11 in. (279 mm) Diameter x 3 in. (76 mm) Deep 34 M. (864 mm) Deep x Unlimited Length 26 In. (660 mm) Deep x Unlimited Length 30 In. (762 mm) Deep x Unlimited Length (4 In. (102 mm) Maximum Fuel Depth) 30 in. (762 mm) Deep x Unlimited Length (6 in. (152 mm) Maximum Fuel Depth) 36 in (914 mm) Deep x Unlimited Length 34 in. (864 mm) Deep x Unlimited Length COVER MUST NOT INTERFERE WITH EDGE OF DISCHARGE PATTERN '-.--� 0-12 IN ) I (0.305 mm) iI 1 ) I 1 I/ 1 ZONE I ZONE CENTER UNE Overlapping System Piping Limitations Total System Flow Size Numbers 3 Gal (11 L) 6 Max. 3/8 in. Maximum Pipe Elevation Length Rise 75ft 25 10 ft (22.9 m) (3.1 m) Max. No. of Elbows 6 Gal (23 L) 12 75ft 25 10 ft Manifolded (22.9 m) (3.1 m) 50 ft (15.2 m) maximum pipe from first to last nozzle. 50 ft (15.2 m) maximum pipe after the split on a split system. Cartridge Size LT -30-R Double Tank FIGURE 1 NUL INCORPORATED, ONE STANTON STREET, MARINErTE, W 54143-2542 715-735-7411 Form No. F-2005010-2 Copyright 02005 Anel Incorporated Nozzle Type Flow Points Perimeter in. (cm) Diameter In. (cm) Nozzle (See Manual ment for More Detail) LengDucth h in. (cm) Single Nozzle 1 Flow Nozzle 1W 1 50 (127) 16 (41) See Manual for more detail Unlimited Single Nozzle 2Flow Nozzle 2W 2 100 (254) 31 7/8 (81) See Manual for more detail Unlimited Multiple Nozzle ; 2W + 1W 3 135 (343) 48 (122) See Manual for more detail Unlimited Multiple 2W No zle 2W - >135 (343) >135 (343) See Manual for more detail Unlimited R-102 OVERLAPPING PROTECTION The 245 nozzle, Part No. 419340, must be used for "end of zone" protection, and the 260 nozzle, Part No. 419341, must be used for "zone" protection. Appliance 1y�e Fryer Griddle Range Wok, Maximum Wok, Minimum Braising Panfli)t Skillet' Lava Rock Char -Broiler Charcoal Broiler Mesquite Wood Broiler Gas Radiant Char -Broiler Electric Char -Broiler See Figure 1 for nozzle location. Note: Group protection option is required for appliances on either side of an appliance(s) using dedicated protection - see manual for details. Maximum Cooking Hazard 34 in. (864 mm) Deep x 5.8 ft2 (5388 cm2) 30 jn. (762 mm) Deep x Unlimited Length 30 in. (762 mm) Deep x Unlimited Length 30 in. (762 mm) Diameter x 8 In. (203 mm) Deep 11 in. (279 mm) Diameter x 3 in. (76 mm) Deep 34 M. (864 mm) Deep x Unlimited Length 26 In. (660 mm) Deep x Unlimited Length 30 In. (762 mm) Deep x Unlimited Length (4 In. (102 mm) Maximum Fuel Depth) 30 in. (762 mm) Deep x Unlimited Length (6 in. (152 mm) Maximum Fuel Depth) 36 in (914 mm) Deep x Unlimited Length 34 in. (864 mm) Deep x Unlimited Length COVER MUST NOT INTERFERE WITH EDGE OF DISCHARGE PATTERN '-.--� 0-12 IN ) I (0.305 mm) iI 1 ) I 1 I/ 1 ZONE I ZONE CENTER UNE Overlapping System Piping Limitations Total System Flow Size Numbers 3 Gal (11 L) 6 Max. 3/8 in. Maximum Pipe Elevation Length Rise 75ft 25 10 ft (22.9 m) (3.1 m) Max. No. of Elbows 6 Gal (23 L) 12 75ft 25 10 ft Manifolded (22.9 m) (3.1 m) 50 ft (15.2 m) maximum pipe from first to last nozzle. 50 ft (15.2 m) maximum pipe after the split on a split system. Cartridge Size LT -30-R Double Tank FIGURE 1 NUL INCORPORATED, ONE STANTON STREET, MARINErTE, W 54143-2542 715-735-7411 Form No. F-2005010-2 Copyright 02005 Anel Incorporated R-102"" RESTAURANT SYSTEM DISTRIBUTION PIPING REQUIREMENTS SHEET Distribution Piping Requirements - 6.0 Gallon (22.7 Liter) Manlfoided System Requirements Supply Line Duct Branch Line Plenum Branch Line Appliance Branch Line Pipe Size Maximum 3/8 In. 3/8 in. 3/8 in. 3/8 in. Length Maximum 32 ft (9.7 m) 8 ft (2.4 m) 4 ft (1.2 m) 12 ft (3.7 m) Rise 6 ft (1.8 m) 4 ft (1.2 m) 2 ft (0.6 m) 2 ft (0.6 m) Maximum 90� Elbow 8 4 4 6 Maximum Tes 2 2 2 4 Maximum Flt?w Numbers 22 4 2 A DIstrlbutlo t Piping Requirements - 6.0 (22.7 Liter) Gallon System 1. The maximum length between the start of the first branch fine and the start of the last branch Zine must not exceed 24 ft (7.3 m). When the supply line is split, the combined total of both legs of the supply line (from the start of the first branch line to the start of the,last branch line) must not exceed 24 ft (7.3 m). 2. ;The total length of all branch lines must not exceed 36 ft (10.9 m). 3.; Use a 3/8 inunion to connect the tank adaptor to the 3/8 in. supply line. Distribution Piping Requirements - 9.0 (34 Liter) Gallon System Requirement's Supply Line Duct Branch Line Plenum Branch Line Appliance Branch Line Pipe Size i Maximum Lehgth Maximum Rise Maximum 90" Elbow Maximum Tees Maximum Flow Numbers 3/8 in. 40 ft (12.2 m) 6ft(1.8m) 9 1 11' 3/8 in. 8 ft (2.4 m) 4ft(1.2m) 4 2 4 3/8 in. 4 ft (1.2 m) 2ft(0.6m) 4 2 2 3/8 in. 12 ft (3.7 m) 2ft(0.6m) 6 4 4 *Exceptions: 1. Twelve (12) flow numbers are allowed in any one tank for hood and duct protection. 2. Twelve (1?) flow numbers are allowed with any one tank using only two -flow appliance nozzles. 3. Twelve (12) flow numbers are allowed with any one tank using only three -flow appliance nozzles. Special Inst4uctions: 1. Twelve (1?) flow numbers are allowed when four (4) Dean Industries GTI Gas Fryers are protected at low proximity. 2. For certai McDonald's applications, 11.5 flow numbers are allowed when using a combination of one (1) 2W duct nozzle, one (1) 1/2N elecfrostatic precipitator nozzle, one (1) 1N plenum nozzle, and four (4) two -flow appliance nozzles. Contact ANSUL Applications Engineering Department for additional information. Distribution Piping Requirements - 9.0 (34 Liter) Gallon System 1. The maximum length between the start of the first branch line and the start of the last branch line must not exceed 24 ft (7.3 m). When the supply line is split, the combined total of both legs of the supply line (from the start of the first branch line to the start of the last branch line) must not exceed 24 ft (7.3 m). 2. The tote( length of all branch lines must not exceed 36 ft (10.9 m). 3. Use a 3/O In. union to connect the tank adaptor to the 3/8 in. supply line. General Piping Requirements 1. All R-10? system piping is straight line. Therefore, the need for critical lengths and balancing is minimized. 2. Two 45° elbows count as one 90° elbow. 3. Each branch line includes the tee or elbow leading to it, and all fittings within the branch line itself. 4. The minimum piping length of Schedule 40, 3/8 in. pipe from the tank outlet to any nozzle protecting a range, fryer, or wok must be 6ft(1.8m). 5. Pipe lengths are measured from center of fitting to center of fitting. 6. All distribution piping must be Schedule 40 black iron, chromeplated, or stainless steel. Do not use hot dipped galvanized pipe on the distribution piping. 7. All threaded connections located in and above the protected area must be sealed with pipe tape. Tape should be applied to male threads gnly. Make certain tape does not extend over the end of the thread, as this could cause possible blockage of the agent distribution. ANSUL INCORPORATED. OPE STANTON STREET. MARINETTE. WI 54143-2542 715.735-7411 Form No. F-2005074.1 Copyright 02008 Maul Incorporated • S0 O O • SNNI 3Snd .09£ 12" X 24 GAS RANGE 0 x O C n ti 4-, n. m r3 0 •0 Dw w Z a N w V i D 6Z M013lVn1J z w cn 0 • • - y mix 7 y a r cn 11 a w N h Z 4 N ( • -4 c/ • D 0 - r c c w 0 -,r 04 N r c o 0 rn > (-) m a o m 0 m 0 > r V1 ✓ C O r z U7 + { w -i m 1374 SOUTHCENTER MALL ASSOCIATED PERMITS 10-S-117 10-H-150 e IL. FIRE DEPARTMENT HOOD SUPPRESSION PLAN REVIEW COMMENTS Project Name: Red Ribbon 1374 Southcenter Mall Permit No.: 10-H-150 Date: July 22, 2010 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Nozzle heights above appliances to be per manufacturers installation guidelines. • Fryers shall be installed with at least a 16 inch space between the fryer and surface flames from adjacent cooking equipment or a minimum 8 inch high steel or tempered glass baffle plate shall be installed between the appliances. • Upon activation of the suppression system, the make-up air supply will shut off and the exhaust will keep running. • Type 1 hood systems shall be designed and installed to automatically activate the exhaust fan whenever cooking operations occur. The activation of the exhaust fan shall occur through an interlock with the cooking appliances, by means of heat sensors or by means of other approved methods. • Activation of the suppression system shall shunt all electrical power under the hood as well as the gas supply. • Install a "K" rated portable fire extinguisher within 30 ft. of the cooking equipment. • The hood suppression system shall be monitored by a U.L. Central Monitoring Station. • The suppression system manual pull station shall be located no closer that 10 ft. and no farther than 20 ft. from the cooking equipment and be placed at a height of 42 to 48 inches above the floor. • The inside lower edge of the hood shall overhang or extend a horizontal distance of not less than 6 inches beyond the edge of the top horizontal surface of the appliance on all open sides. The vertical distance between the front lower lip of the hood and such surface shall not exceed 4 feet. 08/17/2010 11:12 2067672607 RT HOOD & DUCT RTS � Heed di Ned Scr.lret, 1.c, Isrito.dmilihasimmu. d100 17+ Av. S. s.orit wA 41130 r.... aoil +sdt.o noipormum ATTENTION:. cc__ COMPANY t414_____ FROM: NUMBER OF PAGES: (Including Cover) COMMENTS: iS V DATE: FAX #: PHONE #: 1 t� l3 e� 4+ C) -AJ c tS PAGE 01 FAX COVER SHEET o 92.5.5 5 . i1 H 2-Lt 5 -"e‘taAiste- afk (4 144 ov•c cev s. 08/17/2010 11:12 2067672607 RT HOOD & DUCT PAGE 02 z 0 H m 1 1 a to cu 3 3 L v m 0 m ■ ns s�m 0 41 Pk - oma x fl I co o a_ y 0 n ■ 1 m -c 0* _- 0 j m 4 y wtM Jre oga 3 0 0— I:1IdV1IM}Inl 0 % ■■ =e» C// %am k¥° E 2 Ai/ 7! } §FIT a c 0 \ G ntij 2: A. 5 \ Q. 0 CO5 § E - E\ E koM 2�k CD0 �/} } ■ /E§%ƒ JRa53 q ; ƒ e ] =n%oo me CD ! { k \ 0 ° .1 o a J;2K 0 la D £�-- 0 0 S A 0 a co z rn > b9 00 E § _ S£ SZ .,917-0t7 § NOT1VO £ lf1SN'd / 4 0001-1 NI 6 lJ tr S11NI1 3SIld x09£ 0 m§X, \}Fe ¥ xc c2 „=— ƒ 2\ \ \§a{ k\k§ n qpm >¥® 0 \2K m - o, \� 2E ;-0-1 j 0, CI Without Comments o As Noted in Red g Per The Attached Letter ese plans have .,,2(:n reviewed by The Tukwila Fire ;ventlon Burtd J f ; Lnnl ormance with current City -.=ndards: Accertzirc� is subject to errors and :.. nissions which do not authorize violations of adopted .;:andards and orvir?races. The responsibility for the Adequacy of design r : is totally with the designer. .dditions, deletion ; evisions to these drawings;after this date will volu rt- • .L ..t.•nce and will require a resubmittal of re, -r,,' draw'ot�s for subsequent approval. Final acceptance is yupject to „old test and Inspection by The Tukwila Fire Prevention Bureau. - �.� — c7 By: .s�71 Date: - •t46,w4LA riRE oEPAt2T ?tease call: 575.4407 and give this job No. /0 -i4- -C1) a rid Flxact address for shut. . •wn or restoration aoorovai •. • R -102T" RESTAURANT SYSTEM DISTRIBUTION PIPING REQUIREMENTS SHEET Distribution 'iping Requirements -1.5 Gallon (5.6 Liter) System tt Requlremen s Supply Une Duct Branch Line Plenum Branch Une Appliance Branch Une Pipe Size Maximum Length Maximum Rise Maximum 90° Elbow Maximum Tees Maximum Fibw Numbers 3/8 in. 40 ft (12.2 m) 6 ft (1.8 m) 9 1 5' 3/8 in. 6 ft (1.8 m) 4 ft (1.2 m) 4 1 2 3/8 In. 4 ft (1.2 m) 2 ft (0.6 m) 4 2 2 3/8 In. 10 ft(3 m) 2 ft (0.6 m) 6 3 3 ° Exceptionls: 1. Six (6) flaw numbers are allowed when a duct branch line Is the last branch line on the piping network and no 1N nozzles, Part No. 56930, are used to protect woks or griddles. 2. Six (6) f cw numbers are allowed when six (6) 1N nozzles, Part No. 56930, are used and none of the nozzles are used to protect woks and griddles. Note: Only five (5) flow numbers are allowed If a 1N nozzle is used for wok or griddle protection. 3. Six (6) flaw numbers are allowed when only two (2) 3N nozzles, Part No. 76782, are used. Distributio)f Piping Requirements -1.5 Gallon (5.6 Uter) System 1. This option allows for duct protection, plenum protection, appliance protection, or any combination. 2. When using a combination of plenum and duct protection only, only one duct nozzle, either a 1W, 1100, or a 2W, may be used. 3. The ma$imum length between the start of the first branch line and the start of the last branch line must not exceed 8 ft (2.4 m). When the supply line is split, the combined total of both legs of the supply line (from the start of the first branch line to the start of the last branch line) must not exceed 8 ft (2.4 m). 4. The total length of all branch lines must not exceed 22 ft (6.7 m). 5. Use a th8 in. union to connect the tank adaptor to the 3/8 In. supply line. Distribution illping Requirements - 3.0 Gallon (11.3 Liter) System Requirements Supply Lina Duct Branch Une Plenum Branch Une Appliance Branch Une Pipe Size Maximum Length Maximum Rife Maximum 90° Elbow Maximum Tees Maximum Flew Numbers 3/8 In. 40 ft (12.2 m) 6 ft (1.8 m) 9 1 11 • 3/8 In. 8 ft (2.4 m) 4 ft (1.2 m) 4 2 4 3/8 in. 4 ft (1.2 m) 2 ft (0.6 m) 4 2 2 3/8 In. 12 ft (3.7 m) 2 ft (0.6 m) 6 4 4 *Exception*: 1. Twelve (1 ) flow numbers are allowed in any one tank for hood and duct protection. 2. Twelve (1 ) flow numbers are allowed with any one tank using only two -flow appliance nozzles. 3. Twelve (10 flow numbers are allowed with any one tank using only three -flow appliance nozzles. Special Instfuctions: 1. Twelve (1) flow numbers are allowed when four (4) Dean Industries GTI Gas Fryers are protected at low proximity. 2. For certain McDonald's applications, 11.5 flow numbers are allowed when using a combination of one (1) 2W duct nozzle, one (1) 1/2N el tic precipitator nozzle, one (1) 1N plenum nozzle, and four (4) two -flow appliance nozzles. ContactANSUL Applica s Engineering Department for additional information. Distribution Piping Requirements - 3.0 Galion (11.3 Uter) System 1. The maiimum length between the start of the first branch line and the start of the last branch line must not exceed 24 ft (7.3 m). When the supply line is split, the combined total of both legs of the supply line (from the start of the first branch line to the start of the last branch line) must not exceed 24 ft (7.3 m). 2. The total length of all branch lines must not exceed 38 ft (10.9 m). 3. Use a 3/8 In. union to connect the tank adaptor to the 3/8 In. supply line. it ANSLJL. Vico R-102 RESTAURANT SYSTEM ARrnSBupuppnsslon olnp Products NOZZLE COVERAGE/OVERLAPPING SUMMARY SHEET Plenum 1 Nozzle Type Flow Points Width In. (cm) Max. Side Length In. (cm) Max. Side Nozzle Placement (See Manual for More Detail) Min. Height In. (cm) Max. Height in. (cm) Horizontal Protection Single Bank 1N 1 48 (122) 120 (305) 0 in. to 6 in. (0 to 15.2 cm) from end of plenum 2 (5) 4 (10) Perpendicular Protection Single Bank 1W 1 48 (122) 48 (122) See Manual for more detail 1 (2.5) 20 (51) Horizontal Prote):tion V -Bank 2 x 1N 2 48 (122) 120 (305) 0 in. to 6 In. (0 to 15.2 cm) from end of plenum 2 (5) 4 (10) Horizontal ProteOtion V -Bank 1 W 1 48 (122) 72 (183) 0 in. to 6 in. (0 to 15.2 cm) from end of plenum 1/3 the height of filter Perpendicular Pjotection V -Bank 1 W 1 48 (122) 48 (122) See Manual for more detail 1 (2.5) 1 20 (51) Duct Nozzle Type Flow Points Perimeter In. (cm) Diameter In. (cm) Nozzle Placement (See Manual for More Detail) Duct Length in. (cm) Single Nozzle 1 Flow Nozzle 1W 1 50 (127) 16 (41) See Manual for more detail Unlimited Single Nozzle 2 Flow Nozzle 2W 2 100 (254) 31 7/8 (81) See Manual for more detail Unlimited Multiple Nozzle ; 2W + 1W 3 135 (343) 48 (122) See Manual for more detail Unlimited Multiple 2W Nozzle 2W — >135 (343) _ >135 (343) See Manual for more detail Unlimited R-102 OVERLAPPING PROTECTION The 245 nozzle, Part No. 419340, must be used for "end of zone protection, and the 260 node, Part No. 419341, must be used for 'zone protection. Appliance Type Maximum Cooking Hazard Fryer 34 in. (864 mm) Deep x 5.8 ft2 (5388 cm2) Griddle 30 in. (762 mm) Deep x Unlimited Length Range 30 in. (762 mm) Deep x Unlimited Length Wok, Maximum 30 In. (762 mm) Diameter x 8 in. (203 mm) Deep Wok, Minimum: 11 in. (279 mm) Diameter x 3 in. (76 mm) Deep Braising PanITi)t Skillet' 34 in. (864 mm) Deep x Unlimited Length Lava Rock Char -Broiler 26 in. (660 mm) Deep x Unlimited Length Charcoal Broiler 30 In. (762 mm) Deep x Unlimited Length (4 In. (102 mm) Maximum Fuel Depth) Mesquite Wood Broiler 30 in. (762 mm) Deep x Unlimited Length (6 in. (152 mm) Maximum Fuel Depth) Gas Radiant Char -Broiler 36 In (914 mm) Deep x Unlimited Length Electric Char -Boiler 34 in. (864 mm) Deep x Unlimited Length ' See Figure 1 for nozzle location. Note: Group protection option Is required for appliances on either side of an apptance(s) using dedicated protection — see manual tor details. Ifi COVER MUST NOT INTERFERE WRH EDGE OF DISCHARGE PATTERN 0.121N 1i(0.305mm) 1 • 1 1 it 1 ZONE ZONE CENTER UNE Overlapping System Piping Limitations Total Max. 3/8 in. Max. Maximum System Flow Pipe No. of Elevation Cartridge Size Numbers Length Elbows Rise Size 3 Gal (11 L) 6 75 ft 25 10 ft LT -30-R (22.9 m) (3.1 m) 6 Gal (23 L) 12 75 ft 25 10 ft Double Manifolded (22.9 m) (3.1 m) Tank 50 ft (15.2 m) maximum pipe from first to last nozzle. 50 ft (152 m) maximum pipe after the split on a split system. FIGURE 1 ANSUL NCORpORATED. OPE STANTON STREET. MARIPETTE. WI 54143-2542 715-735-7411 Form No. F-2005010-2 Copyight 0200e AnsU Incorporated a ANSL JL. 'two Fire Suppression & Building Products R-102 RESTAURANT SYSTEM NOZZLE COVERAGE/OVERLAPPING SUMMARY SHEET Appfance Nozzle 'type Flow Points Width in. (cm) Max. Side Multiple Length let. (cm) Max. Side Multiple Nozzle w/o Ddp Board Area int (cm2) Nozzle w/ Drip Board Area h2 (cm2) Minimum Nozzle Ht In. (cm) Maximum Nozzle HL In. (cm) Fryers without drip boards *Low Pra Split dr No Split Vat Fryers withot¢ drip boards Non -Spilt Vat (ONLY) 230/290' 2 14 (36) 15 (38) - - 27/13 (69/33) 47/16 (119/41) 245/290* 2 14/14.5 (36/37) 15/14 (38/36) - - 20/16 (51/41) 27/27 (69/69) 290 2 19.5 (50) 19 (48.2) - - 13 (33) 16 (41) 3N 3 19.5 (50) 19 (48.2) - - 21 (53) 34 (86) 3N 3 18 (45.7) 18 (45.7) - - 25 (64) 35 (89) Fryers with drip boards 'Low PredmAy Split dr No Split Vat' 230290' 2 14 (36) 21 (53) 210 (1355) 294 (1897) 27/13 (69/33) 47/16 (119/41) 245/290* 2 14/14.5 (36/37) 21/26.5 (53/67) 210/203 (1355/1310) 294/384.2.(189712479) 20/16 (51/41) 27/27 (69/69) ,Fryers J witt drip boards' Non -Spin Vat (ONLY) j 290 2 19.5 (50) 25 3/8 (65) 370.5 (2390) 495 (3194) 13 (33) 16 (41) 3N 3 19.5 (50) 25 3/8 (65) 370.5 (2390) 495 (3194) 21 (53) 34 (86) 3N 3 18 (45.7) 27 3/4 (70.5) 324 (2090) _497 (3206) 25 (64) 35 (89) Til SId11et/Braisirig Pan' Coverage limitation are based on fryer sizes including the drip boards. Exception: Tilt Skillets and Braising may exceed the maximum of 6 ft2 (0.56 m2) Range ^' Without back shell With back shell' Wdhdut back shelf Oh back shelf' • Longest Side Max Area in' (cm') 1N 1 12 (30.5) 32 (81) 384 (2477) - 30 (76) 40 (102) 1F 1 12 (30.5) 28 (71) 336 (2168) - 30 (76) 50 (127) 1F 1 12 (30.5) 28 (71) 336 (2168) - 40 (102) 48 (122) 245 2 24 (61) 28 (71) - - 40 (102) 50 (127) 260 2 24 (61) 32 (81) 768 (4955) - 30 (76) 40 (102) 260 2 12 (30.5) 32 (81) 384 (2477) - 30 (76) 40 (102) 2 x 290 4 36 (91) 28 (71) 1008 (6503) - 15 (38) 20 (51) Griddle 1N/1NSS 1 36 (91) 30 (76) - - 35 (89) 40 (102) 290 2 30 (76) 24 (61) - - 30 (76) 50 (127) 260 2 48 (122) 30 (76) - - 30 (76) 50 (127) 290 2 48 (122) 30 (76) - - 20 (51) 30 (76) 2120 2 48 (122) 30 (76) - - 10 (25) 20 (51) Chain Broiler' (Overhead Protection) 2 x 1W 2 34 (86) 30 (76) - - 10 (25) 26 (66) Chain Broiler . (Horizontal Protection) Char Broiler IGas-Radiant ' Electric Lava -Rock Natt*al Charcoal' Lava -Rock or Nattlral Charcoal' V/ood Fueled' 2 x 1N 2 31 (79) 43 (109) - - Front edge; 1 to 31n. (3 to 8 cm) above the chain 1N/1NSS 1 24 (61) 36 (91) - - 15 (38) 40 (102) 1W1NSS 1 20 (51) 34 (86) - - 20 (51) 50 (127) 1W1NSS 1 13 (33) 24 (61) - - 18 (46) 35 (89) 1 N/1 NSS 1 12 (30.5) 24 (61) - - 18 (46) 40 (102) 3N 3 24 (61) 30 (76) - - 14 (36) 40 (102) 3N 3 24 (61) 30 (76) - - 14 (36) 40 (102) Upright Broiler Salamander Broiler Interhal Chamber 2 x 1/2N 1 30 (76) 32.5 (82.5) Front edge; above the grate 2 x 1/2N 1 30 (76) 32.5 (82.5) - - 1N 1 16 (41) 29 (74) - - - - 1N nozzle location to be on the vertical edge 6 to 121n. (15.2 to 30.5 cm) in front and 0 to 12 in. (0 to 30.5 cm) above the top of broiler 1N 1 16 (41) 29 (74) - - 6-12 in. above either end (15.2to30.5cm) Wok 3.75 too 8 In. deep (9.0 to 20.3 cm) 3 to 6 In. (7.6 to 15.2 cm) deep 260 2 14 to 301n. (36 to 76 cm) diameter - - 35 (89) 45 (114) 1 W1 NSS 1 11 to 24 In. (28 to 61 cm) diameter - - 30 (76) 40 (102) 'For muttipb nozze protecnon of single fryers. see detailed Information on pages 4-8 to 4-11: of manual. ' See Figure 1 for dozzle location. ► ' Minimum chain boiler exhaust opening -12 In. x 12 In. (30.5 cm x 30.5 cm), and not less thanI60% of Internal broiler size. ► ' 4 in. (10 an) maximum fuel depth. • 6 In. (15 cm) maximum fuel depth. • Shelf can overhang bumer(s) by maximum of 11 in. (28 cm) and height (imitation of 20 In. (51 cm) from bottom 01 lowest part of shelf to the top of bumer grate. ' Shelf can overhang bumer(s) by maximum of 11 In. (28 cm) and height ► limitation of 18 in. (45.7 cm) from bottom of lowest part of shelf to the top of bumer grate. • Low Proximity ► :l. ANSUL. tgco Fin Suppression & Building Products R-102RetTAURANT SYSTEM NOZZLE COVERAGE/OVERLAPPING SUMMARY SHEET Appliance i Nozzle Type Flow Points Width in. (cm) Max. Side Multiple Length in. (cm) Max. Side Multiple Nozzle w/o Drip Board Area int (cm2) Noah w/ Drip Board Area 1,12 (cm2) Minimum Nozzle lit In. (cm) Maximum Nozzle Ht in. (cm) Fryers without drip boards Pr 230/290* 2 14 (36) 15 (38) - - 27/13 (69/33) 47/16 (119/41) Split dr No Split Vat 245/290` 2 14/14.5 (36/37) 15/14 (38/36) - - 20/16 (51/41) 27/27 (69/69) Fryers without drip boards 290 2 19.5 (50) 19 (48.2) - - 13 (33) 16 (41) Non -Split Vat (ONLY) 3N 3 19.5 (50) 19 (48.2) - - 21 (53) 34 (86) 3N 3 18 (45.7) 18 (45.7) - - 25 (64) 35 (89) Fryers witi1 drip boards • 1"PmximivSplit 230/290* 2 14 (36) 21 (53) 210 (1355) 294 (1897) 27/13 (69/33) 47/16 (119/41) Or No Split Vat' 245/290' 2 14/14.5 (36/37) 21/26.5 (53/67) 210/203 (1355/1310) 294/384.2 (1897/2479 20/16 (51/41) 27/27 (69/69) Fryers with; drip boards' 290 2 19.5 (50) 25 3/8 (65) 370.5 (2390) 495 (3194) 13 (33) 16 (41) Non -Split Vat•(ONLY) 3N 3 19.5 (50) 25 3/8 (65) 370.5 (2390) 495 (3194) 21 (53) 34 (86) 3N 3 18 (45.7) 273/4 (70.5) 324 (2090) 497 (3206) 25 (64) 35 (89) Tilt SIdllet/Bnising Pan' Coverage limitation are based on fryer sizes including the drip boards. Exception: Tilt Skillets and Braising may exceed the maximum of 6 ft2 (0.56 m2) Longest Side Max. Area Int (cm') Range 1N 1 12 (30.5) 32 (81) 384 (2477) - 30 (76) 40 (102) Without back shelf 1F 1 12 (30.5) 28 (71) 336 (2168) - 30 (76) 50 (127) With back shelf' 1F 1 12 (30.5) 28 (71) 336 (2168) - 40 (102) 48 (122) 245 2 24 (61) 28 (71) - - 40 (102) 50 (127) Withdutback shelf 260 2 24 (61) 32 (81) 768 (4955) - 30 (76) 40 (102) Will back shelf' 260 2 12 (30.5) 32 (81) 384 (2477) - 30 (76) 40 (102) 2x290 4 36 (91) 28 (71) 1008 (6503) - 15 (38) 20 (51) Griddle 1W1NSS 1 36 (91) 30 (76) - - 35 (89) 40 (102) 290 2 30 (76) 24 (61) - - 30 (76) 50 (127) 260 2 48 (122) 30 (76) - - 30 (76) 50 (127) 290 2 48 (122) 30 (76) -_ - 20 (51) 30 (76) 2120 2 48 (122) 30 (76) - - 10 (25) 20 (51) Chain Broiler' (Overhead Protection) 2 x 1W 2 34 (86) 30 (76) - - 10 (25) 26 (66) Chain Broiler (Horizontal Protection) 2 x 1N 2 31 (79) 43 (109) - . - Front edge; 1 to 3 in. (3 to 8 cm) above the chain Char Broiler ;Gas -Radiant 1N/1NSS 1 24 (61) 36 (91) - - 15 (38) 40 (102) Electric ' 1W1NSS 1 20 (51) 34 (86) - Jss - 20 (51) 50 (127) Lava -Rock 1W1NSS 1 13 (33) 24 ,(61) - 18 (46) 35 (89) Nadia] Charcoal' 1 W1 NSS 1 12 (30.5) 24 (61) - o.18 (46) 40 (102) Lava -Rock or Natural Charcoal' 3N 3 24 (61) 30 (76) - a 14 (36) 40 (102) Wood Fueled' 3N 3 24 (61) 30 (76) - - 14 (36) 40 (102) Upright Broiler 2 x 1/2N 1 30 (76) 32.5 (82.5) ' '' ont edge; Salamander Broiler 2 x 1/2N 1 30 (76) 32.5 (82.5) - -:F the grate , y 1N 1 16 (41) 29 (74) - - - 1 N nozzle location to be on the vertical edge 6 to 12 In. (15.2 to 30.5 cm) in front and 0 10 12 In. (0 ) a the top of broiler Internal Chamber 1N 1 16 (41) 29 (74) - - n. r end (1 . cm) Wok 3.75 to 8 in. deep (9.0 to 20.3 cm) 260 2 14 to 30 in. (36 to 76 cm) diameter - - 35 (89) 45 (114) 3 to 6 In. (7.6 to 15.2 cm) deep ' For multi len tech 1 N/1 NSS f 1 11 to 24 in. (28 to 61 cm) diameter - - 30 (76) 40 (102) p ozz(e pro ono s ngle fryers, see detailed information on pages 4-8 to 4-11 of manual. 'See Figure 1 for nozzle location. ► 'Minimum chain broiler exhaust opening - 12 In. x 12 in. (30.5 cm x 30.5 cm), and not less than160% of internal broiler size. ► ' 4 In. (10 cm) maximum fuel depth. 6 In. (15 cm) maximum fuel depth. 'Shelf can overhang bume (s) by maximum of 11 in. (28 cm) and height limitation of 20 In. (51 cm) from bottom of lowest part of shed to the top of bumer grate. ' Shelf can overhang bumer(s) by maximum of 11 in. (28 cm) and height ► limitation of 18 in. (45.7 cm) from bottom of lowest part of shelf to the top of bumer grate. Low Proximity laltuum11.1 Vico Fire Suppression & Building Products R-102 RESTAURANT SYSTEM NOZZLE COVERAGE/OVERLAPPING SUMMARY SHEET Plenum Horizontal Protection Single Bank Nozzle type Flow Points Width In. (cm) Max. Side Length In. (cm) Max. Side Perpendicular P4otection Single Bank Horizontal Protebtion V -Bank Horizontal Protea tion V Bank 1N 1 48 (122) 120 (305) 1W 1 48 (122) 48 (122) 2x 1N 2 48 (122) 120 (305) Perpendicular PFotection V Bank 1W 1 48 (122) 72 (183) 1W 1 48 (122) 48 (122) Nozzle Placement (See Manual for More Detail) O in. to bin. (0 to 15.2 cm) from end of plenum See Manual for more detail Oin. to6in. (Oto15.2cm) from end of plenum OIn. to6in. (Oto 15.2 cm) from end of plenum See Manual for more detail Min. Height in. (cm) Max. Height in. (cm) Nozzle Type Flow Points Perimeter in. (cm) Diameter In. (cm) 2 (5) 4 (10) 1 (2.5) 20 (51) 2 (5) 4 (10) 1/3 the height of filter 1 (2.5) 1 20 (51) Multiple Nozzle ; 2W + 1W R-102 OVERLAPPING PROTECTION The 245 nozzle, Part No. 419340, must be used for "end of zone" protection, and the 260 nozzle, Part No. 419341, must be used for "zone" protection. Appliance 1y�e Fryer Griddle Range Wok, Maximum Wok, Minimum Braising Panfli)t Skillet' Lava Rock Char -Broiler Charcoal Broiler Mesquite Wood Broiler Gas Radiant Char -Broiler Electric Char -Broiler See Figure 1 for nozzle location. Note: Group protection option is required for appliances on either side of an appliance(s) using dedicated protection - see manual for details. Maximum Cooking Hazard 34 in. (864 mm) Deep x 5.8 ft2 (5388 cm2) 30 jn. (762 mm) Deep x Unlimited Length 30 in. (762 mm) Deep x Unlimited Length 30 in. (762 mm) Diameter x 8 In. (203 mm) Deep 11 in. (279 mm) Diameter x 3 in. (76 mm) Deep 34 M. (864 mm) Deep x Unlimited Length 26 In. (660 mm) Deep x Unlimited Length 30 In. (762 mm) Deep x Unlimited Length (4 In. (102 mm) Maximum Fuel Depth) 30 in. (762 mm) Deep x Unlimited Length (6 in. (152 mm) Maximum Fuel Depth) 36 in (914 mm) Deep x Unlimited Length 34 in. (864 mm) Deep x Unlimited Length COVER MUST NOT INTERFERE WITH EDGE OF DISCHARGE PATTERN '-.--� 0-12 IN ) I (0.305 mm) iI 1 ) I 1 I/ 1 ZONE I ZONE CENTER UNE Overlapping System Piping Limitations Total System Flow Size Numbers 3 Gal (11 L) 6 Max. 3/8 in. Maximum Pipe Elevation Length Rise 75ft 25 10 ft (22.9 m) (3.1 m) Max. No. of Elbows 6 Gal (23 L) 12 75ft 25 10 ft Manifolded (22.9 m) (3.1 m) 50 ft (15.2 m) maximum pipe from first to last nozzle. 50 ft (15.2 m) maximum pipe after the split on a split system. Cartridge Size LT -30-R Double Tank FIGURE 1 NUL INCORPORATED, ONE STANTON STREET, MARINErTE, W 54143-2542 715-735-7411 Form No. F-2005010-2 Copyright 02005 Anel Incorporated Nozzle Type Flow Points Perimeter in. (cm) Diameter In. (cm) Nozzle (See Manual ment for More Detail) LengDucth h in. (cm) Single Nozzle 1 Flow Nozzle 1W 1 50 (127) 16 (41) See Manual for more detail Unlimited Single Nozzle 2Flow Nozzle 2W 2 100 (254) 31 7/8 (81) See Manual for more detail Unlimited Multiple Nozzle ; 2W + 1W 3 135 (343) 48 (122) See Manual for more detail Unlimited Multiple 2W No zle 2W - >135 (343) >135 (343) See Manual for more detail Unlimited R-102 OVERLAPPING PROTECTION The 245 nozzle, Part No. 419340, must be used for "end of zone" protection, and the 260 nozzle, Part No. 419341, must be used for "zone" protection. Appliance 1y�e Fryer Griddle Range Wok, Maximum Wok, Minimum Braising Panfli)t Skillet' Lava Rock Char -Broiler Charcoal Broiler Mesquite Wood Broiler Gas Radiant Char -Broiler Electric Char -Broiler See Figure 1 for nozzle location. Note: Group protection option is required for appliances on either side of an appliance(s) using dedicated protection - see manual for details. Maximum Cooking Hazard 34 in. (864 mm) Deep x 5.8 ft2 (5388 cm2) 30 jn. (762 mm) Deep x Unlimited Length 30 in. (762 mm) Deep x Unlimited Length 30 in. (762 mm) Diameter x 8 In. (203 mm) Deep 11 in. (279 mm) Diameter x 3 in. (76 mm) Deep 34 M. (864 mm) Deep x Unlimited Length 26 In. (660 mm) Deep x Unlimited Length 30 In. (762 mm) Deep x Unlimited Length (4 In. (102 mm) Maximum Fuel Depth) 30 in. (762 mm) Deep x Unlimited Length (6 in. (152 mm) Maximum Fuel Depth) 36 in (914 mm) Deep x Unlimited Length 34 in. (864 mm) Deep x Unlimited Length COVER MUST NOT INTERFERE WITH EDGE OF DISCHARGE PATTERN '-.--� 0-12 IN ) I (0.305 mm) iI 1 ) I 1 I/ 1 ZONE I ZONE CENTER UNE Overlapping System Piping Limitations Total System Flow Size Numbers 3 Gal (11 L) 6 Max. 3/8 in. Maximum Pipe Elevation Length Rise 75ft 25 10 ft (22.9 m) (3.1 m) Max. No. of Elbows 6 Gal (23 L) 12 75ft 25 10 ft Manifolded (22.9 m) (3.1 m) 50 ft (15.2 m) maximum pipe from first to last nozzle. 50 ft (15.2 m) maximum pipe after the split on a split system. Cartridge Size LT -30-R Double Tank FIGURE 1 NUL INCORPORATED, ONE STANTON STREET, MARINErTE, W 54143-2542 715-735-7411 Form No. F-2005010-2 Copyright 02005 Anel Incorporated R-102"" RESTAURANT SYSTEM DISTRIBUTION PIPING REQUIREMENTS SHEET Distribution Piping Requirements - 6.0 Gallon (22.7 Liter) Manlfoided System Requirements Supply Line Duct Branch Line Plenum Branch Line Appliance Branch Line Pipe Size Maximum 3/8 In. 3/8 in. 3/8 in. 3/8 in. Length Maximum 32 ft (9.7 m) 8 ft (2.4 m) 4 ft (1.2 m) 12 ft (3.7 m) Rise 6 ft (1.8 m) 4 ft (1.2 m) 2 ft (0.6 m) 2 ft (0.6 m) Maximum 90� Elbow 8 4 4 6 Maximum Tes 2 2 2 4 Maximum Flt?w Numbers 22 4 2 A DIstrlbutlo t Piping Requirements - 6.0 (22.7 Liter) Gallon System 1. The maximum length between the start of the first branch fine and the start of the last branch Zine must not exceed 24 ft (7.3 m). When the supply line is split, the combined total of both legs of the supply line (from the start of the first branch line to the start of the,last branch line) must not exceed 24 ft (7.3 m). 2. ;The total length of all branch lines must not exceed 36 ft (10.9 m). 3.; Use a 3/8 inunion to connect the tank adaptor to the 3/8 in. supply line. Distribution Piping Requirements - 9.0 (34 Liter) Gallon System Requirement's Supply Line Duct Branch Line Plenum Branch Line Appliance Branch Line Pipe Size i Maximum Lehgth Maximum Rise Maximum 90" Elbow Maximum Tees Maximum Flow Numbers 3/8 in. 40 ft (12.2 m) 6ft(1.8m) 9 1 11' 3/8 in. 8 ft (2.4 m) 4ft(1.2m) 4 2 4 3/8 in. 4 ft (1.2 m) 2ft(0.6m) 4 2 2 3/8 in. 12 ft (3.7 m) 2ft(0.6m) 6 4 4 *Exceptions: 1. Twelve (12) flow numbers are allowed in any one tank for hood and duct protection. 2. Twelve (1?) flow numbers are allowed with any one tank using only two -flow appliance nozzles. 3. Twelve (12) flow numbers are allowed with any one tank using only three -flow appliance nozzles. Special Inst4uctions: 1. Twelve (1?) flow numbers are allowed when four (4) Dean Industries GTI Gas Fryers are protected at low proximity. 2. For certai McDonald's applications, 11.5 flow numbers are allowed when using a combination of one (1) 2W duct nozzle, one (1) 1/2N elecfrostatic precipitator nozzle, one (1) 1N plenum nozzle, and four (4) two -flow appliance nozzles. Contact ANSUL Applications Engineering Department for additional information. Distribution Piping Requirements - 9.0 (34 Liter) Gallon System 1. The maximum length between the start of the first branch line and the start of the last branch line must not exceed 24 ft (7.3 m). When the supply line is split, the combined total of both legs of the supply line (from the start of the first branch line to the start of the last branch line) must not exceed 24 ft (7.3 m). 2. The tote( length of all branch lines must not exceed 36 ft (10.9 m). 3. Use a 3/O In. union to connect the tank adaptor to the 3/8 in. supply line. General Piping Requirements 1. All R-10? system piping is straight line. Therefore, the need for critical lengths and balancing is minimized. 2. Two 45° elbows count as one 90° elbow. 3. Each branch line includes the tee or elbow leading to it, and all fittings within the branch line itself. 4. The minimum piping length of Schedule 40, 3/8 in. pipe from the tank outlet to any nozzle protecting a range, fryer, or wok must be 6ft(1.8m). 5. Pipe lengths are measured from center of fitting to center of fitting. 6. All distribution piping must be Schedule 40 black iron, chromeplated, or stainless steel. Do not use hot dipped galvanized pipe on the distribution piping. 7. All threaded connections located in and above the protected area must be sealed with pipe tape. Tape should be applied to male threads gnly. Make certain tape does not extend over the end of the thread, as this could cause possible blockage of the agent distribution. ANSUL INCORPORATED. OPE STANTON STREET. MARINETTE. WI 54143-2542 715.735-7411 Form No. F-2005074.1 Copyright 02008 Maul Incorporated • S0 O O • SNNI 3Snd .09£ 12" X 24 GAS RANGE 0 x O C n ti 4-, n. m r3 0 •0 Dw w Z a N w V i D 6Z M013lVn1J z w cn 0 • • - y mix 7 y a r cn 11 a w N h Z 4 N ( • -4 c/ • D 0 - r c c w 0 -,r 04 N r c o 0 rn > (-) m a o m 0 m 0 > r V1 ✓ C O r z U7 + { w -i m