HomeMy WebLinkAboutPP - 1378 SOUTHCENTER MALL - BOSS WEAR - PERMITS AND PLANS1378 SOUTHCENTER MALL ASSOCIATED PERMITS 15-F-131 11-F-184 15-S-149 11-S-169 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Daiso Japan 1378 Southcenter Mall Permit No.: 15-S-149 Date: September 24, 2015 Reviewer: Al Metzler Fire Protection Project Coordinator (206) 575-4407 option # 2 (Inspection Requests) (206) 971-8718 (Plan Review Questions) • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes iri pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Flexible sprinkler hose bends shall not exceed the maximum radius permitted by the listing. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • All valves controlling the water supply for automatic sprinkler systems and waterflow switches on all sprinkler systems shall be electrically supervised. • All interior control valves shall be readily accessible, labeled and located not more than 6 ft. above the floor. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 20 or more sprinkler heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems in addition to the standard hydrostatic test, an air pressure leakage test at 40 psii shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2013 Edition. 07/26/2011 13:34 4254818695 FAX TRANSMITTAL CROWN FIRE Fax No. CROWN FIRE PROTECTION, INC. EMI Company 7.26.11 Fire Prevention Bureau Tukwila Fire Department / Don Tomaso Demo Permit Number of Pages (Including Cover 17 Urgent ® For Review 1 ❑ Please Comment ❑ Please Reply PAGE 01/01 206575.4439 Jessica Robinson PH:425.481.7669 FX:425.481.8695 Please provide a demo permit to remove (2) sarin, heads that are in the way of a wall that is being removed at the Daiso Japan project . Southcenter Ma . This work is being done in accordance with Cristie' s phone conversation with—A Metzler today. The building permit is D11-191. Please let us know if you have any questions. yt lJS �Cr?°>s Thanks P.O. BOX 12113 MILL CREEK, WA 98082 PH: 425.481.7669 TUKWILA FIRE DEPARTMENT Please call 206-575-4407 and give this Fire Permit No. and exact address for shut- nown or restoration approval. FX: 425. 481.8695 k 7 lz / NOTICE 4 completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and 1)!,: (.1:ion Syst rns. Failur,L! t:..st will result in a Re-insp ction Fee and termination of the testing DA F RE ALA T K IS JAP S TE ILA, `.', ASHII\T N DITIO ON SHEET \UM3E� SH IET TITLE FA -01 SYSTEM FO MATIO\ FA -02 TYPICAL WHI\G A\D MOU\TI G DETAILS FA -03 SYSTEM CALC U LATI O S A\D SI\GLE LI\E DIAGRAM FA -04 FRE ALARM SYSTEM PLA\ SHEET INDEX Without Comments p As Noted in Regi o Per The Attaches Letter The6e plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawing: after this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: S! ?j By: 1 -RA/VILA FIRE DEP SRT 'ri" ' fr`'► se call 206-575- x.07 an give this Fhc Permit mit O. 1, =F- 1 3 I .ind exact a dclg.ss for shut- down or res r oin approval. 3ULE A\D CO\DUIT FILL CHAT WIRE DESIGNATI❑N SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKED D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKED P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V' SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1 2'. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 8. 9. 10 11 12 DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR S'ZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vaC POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 131 ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14 ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15 PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN—UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN—UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE V/ITH NFPA 72 CHAPTER 7. 16 WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17 ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21 ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI—CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY EX 1 1 1 5 1 EX EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT BPS REMOTE BOOSTER POWER SUPPLY EX (EXISTING) PAD -3 SIEMENS PAD-3—ENCL 66" A.F.F. TO TOP ®p DUCT SMOKE DETECTOR AD2—P W/ SIEMENS HFP-11 DET. DUCT HOUSING VERIFY IN FIELD TSM DUCT DETECTOR TEST SWITCH TSM -1 SIEMENS 1—GANG BOX VERIFY IN FIELD HTR -R INTERFACE MODULE WITH RELAY HTRI—R SIEMENS 4S DEEP BOX VERIFY IN FIELD jj FIRE ALARM HORN STROBE ZH—MC—CW SIEMENS 4S DEEP BOX CEILING l FIRE ALARM STROBE ZR—MC—CW SIEMENS 4S DEEP BOX CEILING HTR -R EX INTERFACE MODULE WITH RELAY (EXISTING) HTRI—R SIEMENS 4S DEEP BOX VERIFY IN FIELD ® Ex SMOKE DETECTOR (ADDRESSABLE—PHOTO) (EXISTING) HFP-1 1 SIEMENS EXISTING CEILING A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT N/A REMOVE N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A SYMBOLS LEGEND NORDSTROM 3 LEVELS 171,2.75sf t' IICSSJ r. 5' macys 4 LEVELS 250,407sf DAISO JAPAN 1378 E uu-No e�aenn TNCER 8O 1 ❑ ` ZPsys stop n .RARE ROS cyci:i.nR L1 I_ C1 REGALIA NV LAS n clot g 0 '.0'.'4 5 I-1 I I s AInR SS CAht\t7.V WSTAND 6 SOLE S CES SOLE SIOES IKE CO(X. LIDS •772,,q01_711,_ WIRE DESIGNATION GENERAL NOTES SITE PLAN EXOIINC JCPenney 3 LEWES 276,46Ssf PAID AUG 17 2015 TUKWILAJIRE cc -20 aj -AL z z e• Q 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: DMG DESCRIPTION SHOP DRAWINGS DATE 0 M cO 0 2aaaaa SCALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE DATE: 08/ 13/ 15 BACKROUND PLAN PROVIDED BY: Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved \OB NUMBER:13153-1 J - SHEET Q FA -01 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TUBE OUTLET SAMPLING TUBE INLET SAMPLING DUCK OVER 3' WIDE: SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL 120VAC-60HZ DEDICATED E AERGENCY NOTE FOR ADDITIONAL SPECIRCATIONS SEE PRODUCT DOCIIAMENTA11ON. *CONTACT RATINGS 4.0A 0 125VAC 4.0A 0 30VDC ISOLATE FROM GRl1NDING TO NEXT ADDRESSABLE (+ DEVICE STOP IF LAST DEVICE µ- FROM XLS CONTROL PANEL l OR PREVIOUS ADDRESSABLE DEVICE GROUND - 1] O O 0 HTRI-R 0 ©, 0' O o O NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. C -CABLE C -CABLE 0 EIFJEJ 0000 L PAD -3 oo° NPUT INPUT TROUBLE NACI NAC2 NAC3 NAC4 AUX + 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - S 0 0 0 0 0 -I 3.6k EOL (-) (+) SPARE SPARE SPARE (-) FROM PREVIOUS ADDRESSABLE DEVICE HFP-11 \\\\,\2:2,_ TB1 O 0 10 NO COM NC 2 TO FAN SHUTDOWN EOLR 470 m & 0 SWITCH + - INPUT LED TSM -1 0 00 TO NEXT ADDRESSABLE DEVICE 0 6 /1/1/ 1 2 3 4 5 00 NO 6) COM e HTRI-R KG 0 0 TYPICAL DUCT DETECTOR/HTRI-R MODULE/TSM-1 SWITCH WIRING DETAIL POWER SUPPLY & RELAY MODULE WIRING DETAIL (+) HORN/STROBE OR STROBE ONLY HORN/STROBE OR STROBE ONLY HORN/STROBE OR STROBE ONLY HONR STROBES & STROBES ONLY WIRING DETAIL TYPICAL TO NEXT DEVICE OR END OF LINE WIRING AND MOUNTING DETAILS CEILIN TILE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER T1N TEMPERA RE: +32' F 0' C TO 100' F (3& C) HUMIDITY: -9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR -)' FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE [DATA IN ( ) >— DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPUCATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW (-) > TO NEXT 1 1 ADDRESSABLE (+) SMOKE DETECTOR WIRING DETAIL 1®D 0 0 SUPPORT BRIDGE 4" SQUARE DEEP BOX CEILING /- HORN STROBE / STROBE ONLY DROP CEILING MOUNTING HARD LID CEILING DEVICE SUPPORT BRIDGE 4" SQUARE DEEP BOX CEILING HORN STROBE STROBE ONLY HARD LID MOUNTING HORN STROBE & STROBE CEILING MOUNTING DETAIL JUNCTI❑N BOX MOUNTED ON CEILING FLEX 0WON e':.so'S. e':?:%.mss':::%`S.se':?s%'%so%su%'S::%Smu`'%m':se'S:s%. n JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT TO NEXT DEVICE CADDY BAR SMOKE/HEAT DETECTOR SUSPENDED ILLUMINATED CEILING SMOKE/HEAT DETECTOR MOUNTING DETAIL 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: DMG DESCRIPTION SHOP DRAWINGS DATE I- , 0 co Z r CZ rn 2z a. <WF- < LU _ O (1) Q Cf) CC2 Q O- < co— Wcv; �yr CC r = LL cf (774 w 0 z fCALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE DATE: 08/ 13/ 15 BACKROUND PLAN PROVIDED BY: ,JOB NUMBER:13153-1i ( SHEET FA -02 1 Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved \ SITE LOCATION CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East Tukwila, WA 98188 206-575-4407 Date application accepted: FIRE PROTECTION SYSTEMS PERMIT APPLICATION Applications and plans must be complete in order to be accepted for plan review. **PLEASE PRINT** King Co. Assessor's Tax No.: Site Address: 1378 South Center Mall, Tukwila, WA 98188 suite Number: 920247-0010 Floor: Tenant Name: Daiso Southcenter Mall New Tenant? - Yes 111- No Property Owner's Name: Westfield Property Tax Dept. Mailing Address: same as site address CONTACT PERSON -if there are questions about the submittal. Name: Karina Veliz Day Telephone: 206.349.5889 Company Name: Guardian Security Systems City State Zip Mailing Address: 1743 First Ave South, Seattle, WA 98134 kvelizng y uardiansecurit .com City State Zip E-mail Address: kveliz@guardiansecurity.com Number: 206.374 2852 Total number of new/relocated devices or sprinkler heads: — 1 Valuation of Project (contractor's bid price): $ 5,400. Scope of Work (please provide detailed information): Add 9 devices to existing FACP. PERMIT APPLICATION NOTES Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules. Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILDING,0 NF,tt OR iUTHOIZED AGENT: Signature: Print Name: Karina Veliz Date: `� t Day Telephone: 206.349.5889 Plan Permit App.doc 1/2/13 TFD FP Form 8 Loa us ngs D2 Series ENGINEER AND ARCHITECT SPECIFICATIONS • For Series 11 Detectors • Relay Models Available • Design for AirVelocity Range of 100 to 4000 fpm • Alarm LED Visible From Front Fire Safety • Clear Housing Cover for Quick Identification of Detector Type Removable With Only Four Captive Screws • 0 UL Listed, CSFM Approved, ULC Listed Introduction The Siemens BuildingTechnologies, Fire Safety Division air duct detector housings are designed to be used with the 11 -Series detectors. Designed for installation directly to heating, ventilating and air conditioning duct systems, they comply with National Fire Protection Association Standard No. 90A. When equipped with photoelectric detectors, these units will signal the presence of hazard- ous quantities of products of combustion or smoke being carried through the duct system. Air duct detectors are not intended to be substituted for open area detection. Air duct housings can be equipped with optional relays. These relays are utilized to operate any supplementary equipment when smoke or particles of combustion are detected. Note: Most conventional time control equipment guaran- tee only one detector per zone when the detector oper- ated relay function is critical.The connection of a remote lamp and a remote relay per detector is allowed with PXL or System 3TM only, other conventional systems may use either a remote lamp or a relay. With the MXL series of control panels, up to 60 detectors per circuit having relays may be used.The connection of a remote lamp or a remote relay is allowed for each detector but not both. With the FireFinder XLS series of control panels, up to 252 detectors per circuit having relays may be used. The Connection of an intelligent remote lamp and a remote Relay (ILED), is also allowed. Air duct housings (see Ordering Information) are Under- writers Laboratories, Inc. listed. Description The Fire Safety air duct housing is uniquely designed to use the photoelectric detector. Sensitivity of PE -11 detectors can be checked by viewing the LED or an RSAW-11 or RSAC-11 multicolor remote lamp. A green flash indicates the detector has passed its self test. Amber indicates a trouble condition, and red indicates an alarm state. HFP-11,HFPO-11 and FP -11 sensitivity may be viewed from the multi -color LED on the detector or preferably may be printed by command on an optional printer from the MXL control panel. The detector unit employs a cross-sectional sampling principle of operation. Inlet sampling tubes are available in four lengths (see table on reverse side). Outlet sampling tubes are one common length. A continuous cross- sectional sample of air moving through the duct stratifica- tion or skin effect phenomena occurring in the duct that could prevent combustion product or smoke (especially in large ducts) from reaching a spot type detector. In addition, the unique design of the sampling chamber insures uniform sensitivity in air velocities, ranging from a low of 100 feet per minute to as high as 4000 feet per minute. The housing comes with two' " conduit CATALOG NUMBER 6185 knockouts and one 1/2" conduit opening fora number of 3 wiring entry ports. The inlet sampling tube length is determined by the width of the air duct being protected.The inlet tube nearest to but greater than the duct width should be used (see table).The inlet tube can then be trimmed at the job site to the exact width of the duct.The outlet sampling tube for all ducts, irrespective of width, has a fixed length of approximately 5.5 inches and is supplied with the duct housing. When the use of a remote relay is required, order model AD2-PR for conventional systems; AD2-XHR for address- able systems. When required the WP -2000 weatherproof enclosure for Duct Housing is available. For full details, refer to installation instructions part number315-049708. Sampling Tube Selection Table Duct Width Sampling Tube Model No. For duct widths 6' to 1' ST -10 For duct widths over 1' to 3' ST -25 For duct widths over 3' to 5' (requires support) ST -50 For duct widths over 5' to 10' (requires support) ST -100 Maintenance of the detector is easily accomplished by the removal of the Series 11 duct housing sampling chamber cover.The detector, which plugs into the hous- ing, is easily removed for cleaning by a trained technician. All that is necessary for installation of the air duct detector is the cutting of three small holes for the sampling tube installation (template included) and the drilling of four holes for mounting the air duct housing.The unit is then easily mounted in place and connection made to the existing wires or terminals if optional accessories are utilized. ST -50 and ST -100 require support. ST -100 is shipped in two five foot pieces with a coupling for field assembly. Technical Data Temperature Range Altitude Range Relative Humidity Air DuctVelocity Range SamplingTube Pressure Range of Differences 32°F (0°C) -100°F (38°C) No Altitude Limitations 10-85% (non-condens ing/non-freezing) 100-4000 Ft/Min. Greater than 0.01 amps less than 1.2 inches of water column Note to Architect: When building codes regulate the location of detectors within ventilating systems, make sure that the number and locations of detectors is in accordance with the code regulations. Order Information Model Description Part Number AD2-P Air Duct Housing for use with FP -11, HFP-11, HFPO-11, PE -11 500-649706 AD2-PR Air Duct Housing for use with PE -11 with relay 500-649707 AD2-XHR Air Duct Housing for use with FP -11, HFP-11, HFP0-11, with relay 500-649708 ST -10 Sampling Tube for Ducts 6" to 1' 500-649710 ST -25 Sampling Tube for Ducts over 1' to 3' 500-649711 ST -50 Sampling Tube for Ducts over 3' to 5' 500-649712 ST -100 Sampling Tube for Ducts over 5' to 10' 500-649713 Product Includes One Short Return (outlet)Tube One Stopper Two #12 + 3/4" Sheet Metal Screws MountingTemplate Note: Detector and sampling tube to be purchased separately Note: Minimum hardware required is one Air Duct Housing Assembly, one Sampling Tube and one Detector NOTICE: The use of other than Fire Safety detectors and bases with Fire Safety equipment will be considered a misapplication of Fire Safety equipment and as such voids all warranties either expressed or implied in regard to loss, damage, liabilities and/or service problems Siemens Building Technologies Fire Safety Fire Safety 8 Fernwood Road Florham Park, NJ 07932 Tel: (973) 593-2600 FAX: (973) 593-6670 Website: www.sbt.siemens.com/fis 9/06 5M SFS -IG Printed in U.S.A. Fire Safety 2 Kenview Boulevard Brampton, Ontario Canada L6T 5E4 Tel: (905) 799-9937 FAX: (905) 799-9858 September 2006 Supersedes sheet dated 4/06 F11 FreFrn.1eiTM [I:etect r Fire Safety intelligent Fire Detector for FireFinder XLS and FS -250 Control Panels ENGINEER AND ARCHITECT SPECIFICATIONS Model HFP-11 • Most Sophisticated "Detector Intelligence" available today • Multi -Criteria fire detection for the price of a photoelectric detector • FirePrintT"Technology to discriminate between deceptive phenomena and an actual fire • Easily programmed to match specific hazard profiles from the control panel • Polarity Insensitive with SureWireT'Technology • Pre -Alarm reporting based on fire profile selected • Remote sensitivity measurement capability • System logic activation based on any of three inputs from detector (smoke, heat or neural network) • Detectors are self -testing, completing diagnostics every 4 seconds • Field cleanable chamber with replaceable chambeE parts available • Multi -color detector status LED • Two -wire operation • Compatible Model DPU field device programmer/tester unit • Supports software based automatic environments compensation • Optional fully programmable relay base, audible base, and duct housing • U� ULC Listed, CSFM, FM, NYMEA Approved Introduction The Siemens Building Technologies, Fire Safety Divi- sion HFP-11 Intelligent Fire Detector provides the life safety industry with the most highly evolved detection system available today. The HFP-11 utilizes advanced detection technology that allows the detector to distinguish non -threatening deceptive phenomena, such as cigarette smoke, from actual fire hazards, while optimizing detection for the area in which it is installed. No other detection system available today offers a higher level of protection or nuisance alarm immunity. The HFP-11 uses state-of-the-art micropro- cessor circuitry with error check, detector self -diagnos- tics and supervision programs. The HFP-11 intelligent fire detector is compatible with the Fire Safety Model DPU field device programmer/ tester unit, which is a compact, portable, menu -driven accessory for electronically programming and testing detectors, easily and reliably. The DPU eliminates the need for cumbersome, unreliable mechanical program- ming methods, such as dials or switches and reduces installation and service costs by electronically pro- gramming and testing the detector prior to installation. The HFP-11 fire detector is compatible with the Fire Finder XLS series of control panels. CATALOG NUMBER 1 Description The HFP-11 is a plug-in, two -wire, multi -sensor detector with both photoelectric and thermal inputs and is compat- ible with Fire Finder XLS and FS -250 series of control panel systems. Each detector consists of a dust resis- tant, field -cleanable photoelectric chamber, a solid state non-mechanical thermal sensor, and microprocessor based electronics with a low -profile plastic housing.The HFP-11 utilizes state-of-the-art ASIC circuitry and surface mount technology for maximum reliability. Every HFP-11 fire detector is shipped with a protective dust cover.The HFP-11 fire detector utilizes an infrared light emitting diode (IRLED), and light sensing photodiode. Under normal conditions, light transmitted by the LED is directed away from the photodiode and scattered through the smoke chamber in a controlled pattern.The smoke chamber is designed to manage light dissipation and extraneous reflections from dust particles or other non - smoke airborne contaminants in such a way as to main- tain stable, consistent detector operation. When smoke enters the detector chamber, light emitted from the IRLED is scattered by the smoke particles and is received by the photodiode. The HFP-11 also utilizes a modern, accurate, shock - resistant thermistor to sense temperature changes. The "on -board" FirePrint technology allows the detec- tor to gather smoke and thermal data, and to analyze this information in the detector's "neural network" By comparing data received with the common characteris- tics of fires, or fire fingerprints, the HFP-11 can com- pare these "Fire Prints" to those of deceptive phe- nomena that cause other detectors to false alarm.The advanced FirePrint technology allows the HFP-11 to accurately determine a true fire hazard from a non- threatening deceptive phenomena WITHOUT needing to use alarm delaying verification and confirmation techniques, which can increase the probability of losses due to fire. The HFP-11 provides the highest level of detector intelligence available today with a detector/control panel link that allows the user to program the detector for the specific hazard profile using a simple software menu selection. Detectors are optimized by selecting one of the following eleven applications: • Office/Retail • Lobby • Computer Room • Dormitory • Healthcare • Parking Garage • Utility/Transformer Room • Hostile Environment • Precious Storage • Air Duct • Warehouse/Light Manufacturing The software does the rest; no guessing on detector sensitivities or alarm verification; the control panel programs the HFP-11 detector for the protected area without hassle and without confirmation delays. Once optimized for the hazards in the protected area, the HFP-11 provides the best detection you can buy. Should the operator or installer forget to program the detector, the HFP-11 will revert to a default setting that allows it to operate as an office environment detector. The HFP-11's FirePrint technology monitors input from both the photo chamber and the thermal sensor, evaluating this information with sophisticated math- ematical formulas, or algorithms, comparing this input to characteristics of both threatening fires and decep- tive phenomena that would "fool" any ordinary detec- tor. This technology was developed over years of research and reviewing the results of over 20 years of fire test data in one of the world's most advanced fire research centers. The results of this research are the mathematical models that form the algorithms used in FirePrint. No other fire detector has this level of intelligence or this amount of research and development supporting it's design. The microprocessor's software can identify and disregard false input caused by radio frequency (RFI) and electromagnetic (EMI) interference, and validates all trouble conditions before annunciating or reporting to the control panel.The HFP-11 detector's microprocessor uses an integral EEPROM to store the detector's address and other critical operating param- eters which include the assigned program values for alarm and trouble thresholds. Communications within the detector itself and be- tween the HFP-11 and the control panel, or with the DPU field device programmer/tester unit, are super- vised and safe -guarded against disruption by reliable, microprocessor based error checking routines. Addi- tionally, the micro -processor supervises all EEPROM memory locations and provides a high degree of EEPROM failure fault tolerance. The HFP-11 determines its operating status to be normal, in alarm, or in trouble depending on the difference between the alarm threshold values stored in the detector's memory and the detector's latest analog measurement. The detector then communicates changes in its status to the control panel. In addition, the FireFinder XLS control pariel will sample the value of the HFP-11's analog signal over a period of time in order to determine if those values indicate excessive buildup in the photo chamber; if so, the FireFinder XLS control panel will indicate that the particular detector requires maintenance. The HFP-11 is listed as a self -testing device.The HFP-11's visible light emitting diode (LED) flashes green every 4 seconds to indicate it is communicating with the control panel and that it has passed its internal self -test. Should the detector sense a fault or failure within its systems, the LED will flash amber and the detector will transmit that information to the control panel. A quick visual inspection is sufficient to indicate the condition of the detector at any time. If more detailed information is required, a printed report can be provided from the Fire Finder XLS panel indicating the status and settings assigned to each individual detector. When the HFP-11 moves to the alarm mode, it will flash red and to continue flashing until the system is reset at the control panel. At that same time, any user defined system alarm functions programmed into the system are activated. Detector sensitivity, calibration, and identification are dynamically supervised by the control panel. Detector sensitivity and pre -alarm levels are a function of the application chosen at the control panel and are controlled by the panel. If an alternate, non-FirePrint mode is selected, then the sensitivity can be changed from the control panel. The DPU Device Program/Test Unit accessory is used to program and verify the detector's address. The technician selects the accessory's program mode to enter the desired address. The DPU automatically sets and verifies the address and tests the detector. The DPU operates on AC power or rechargeable batteries, providing flexibility and convenience in programming and testing equipment almost anywhere. When in the test mode, the DPU will perform a series of diagnostic tests without altering the address or other stored data, allowing technicians to determine if the detector is operating properly. The HFP-11 fire detector may be installed on the same initiating circuit with HMS series manual stations, HTRI series interfaces, HCP output control devices, or HZM series of addressable, conventional zone modules. All HFP-11 detectors can be cleaned in the field, when required, by simply removing the detector cover and unsnapping the photo chamber. There is also the option of cleaning the interior of the detector with a clean, soft cloth or brush, or replacing the labyrinth and bug screen included in the detector maintenance kit, model DMK-11. The HFP-11 uses the low -profile surface mounting base, model DB -11. This base mounts on a 4 -inch octagon, square, or a single gang electrical box. The base utilizes screw clamp contacts for electrical connections and self -wiping contacts for increased reliability. The base can be used with the optional LK -11 detector locking kit which contains 50 detector locks and an installation tool, to prevent unauthorized - removal of the detector head.The DB -11 base has integral decorative plugs to cover the outer mounting screw holes. All HFP-11 detectors are approved for operation within the UL specified temperature range of 32 to 100 degrees F (0 to 38 degrees C). Application Data Installation of the HFP-11 series of fire detectors requires a two -wire circuit. In many retrofit cases, existing wiring may be used. "T -tapping" is permitted only for Style 4 (Class B) wiring. The HFP-11 is polarity insensitive. This feature can greatly reduce installation an debugging time. HFP-11 fire detectors can be applied within the maximum 30 foot center spacing (900 sq. ft. areas) as referenced in NFPA 72. This applications guideline is based on ideal conditions, specifically, smooth ceiling surfaces, minimal air movement, and no physical obstructions between potential fire sources and the detector. Do not mount detectors in close proximity to ventilation or heating and air conditioning outlets. Exposed joints or beamed ceilings may also affect safe spacing limitations for detectors. Should questions arise regarding detector placement, observe NFPA 72 guidelines. Good fire protection system engineering and common sense dictate how and when fire detectors are installed and used. Contact your local Fire Safety distributor or sales office whenever you need assistance applying FirePrint in unusual applications. Be sure to follow NFPA guidelines and ULJULC approved installation instructions, which are included with every Fire Safety detector, and local codes as for all fire protection equipment. Dimensions T 23. Overall Height 1 6" Diameter Base , 1._.x`7 11111411W law Technical Specifications Operating Temperature: +32°F (0°C) to 100°F (38°C) per UL 268/268A Humidity: Maximum spacing: 0-93% Relative Humidity Non -Condensing 30 foot centers (900 sq. ft.) per NFPA 72 Chapter 5 and CAN/ULC-S524 Model Detetiptian Part Number HFP-11 dyddres satiw FirePrirn Fre De:ecmr 511C0 -113:M. DB -11 DiInnIrr Memtesing Bit lfit S@;ttNi j1 RIC -1194.151 DB -11E DtctcIlur El lstr illi Y 51D UB+1151E AD -11P Air DtAzit Housing ler Surras 11 SDrr11BRU AD-Hz1 fin Du. --1 Housing w Relay' ler H=Series IniediDent ['howl 5'16-U i14U D6•HA Rcld BaSu fur 11,- Scrum It=tclllittut. Dutucin s 50CU3322D ADl3H=11 Audible bass, 5D61133Z11U RLI`#C Remota 'reit alarm indrAto 4' n .. on b >< mourn 5DU-413323 RUTIN Remote 'red" aarm indt • sir41n Rang bux mourn 511D-U3a3UU LK -11 Base. Lucking rt. MT Series 11 detectors mile- 5 DLIK-11 Series 11 Mair. Kb 'replacement labyrinth aryl hug lxig scree} SDC -B 15a^'t.2 In Canada Onion. EHFP-11C itiAtiressa&ie FirePrin1Fire Detectnr1L(LC) SDCD95112C DB -11C Detests; Mourning. SDC41951.7 AD-11PC lir. DtntHousina(L1tC} 50C4159414 DB -HRC Relay Base tnr Series 11 Imelligent Detectors ft1LCI 51C11'f1' PC ADBi1-11 C kidihle Base for Series 11 (it_enr Detector (11LCI 511D-11n2In{: NOTICE: The use of other than Fire Safety detectors and bases with Fire Safety equipment will be considered a misapplication of Fire Safety equipment and as such void all warranties either expressed or implied with regard to loss, damage, liabilities and/or service problems. Siemens Building Technologies Fire Safety Fire Safety Fire Safety 8 Fernwood Road 2 Kenview Boulevard Florham Park, NJ 07932 10/05 Brampton, Ontario Tel. (973) 593-2600 5M Canada L6T 5E4 FAX: (973) 593-6670 SFS -IG Tel: (905) 799-9937 Website: www.sbt.siemens.com/fis Printed to U.S.A. FAX. (905) 799-9858 October2005 Supersedes sheet dated 7/03 Duct Detector Test Switch ENGINEER AND ARCHITECT SPECIFICATIONS • T45 Key Operated • LED Indicates Detector in Alarm • Mounts in Single Gang Box • Compatible with All Siemens Building Technologies, Fire Safety Division Intelligent Duct Detectors • ®UL Listed Fire Safety Description The TSM -1, Test Switch Module is a key activated device that will functionally test a detector. The module is compatible with Siemens Fire Safety intelligent fire, smoke and duct detectors used on MXL, MXLV and MXL-IQ systems. The TSM -1 includes a red LED that illuminates when the corresponding duct detector is in alarm. The switch operates in conjunction with a TRI -R Interface Module with relay. Either that relay or the relay in the duct detector can be used for control of building equipment such as HVAC fans and elevators. The TSM -1 mounts in a single gang electrical box and includes a red cover plate. When the switch is operated a signal is transmitted to the appropriate detector forcing it to alarm. That alarm will activate all functions programmed to follow that detector. The TSM -1 therefore provides a true functional test of the actions associated with duct detectors on MXL systems as require by many jurisdictions. Underwriters' Laboratories, Inc has listed the TSM -1 as compatible with MXL intelligent detectors. Ordering information Model Description Part Number TSM -i Detector Test Switch 5OG-696353 Refer to Installation Instructions, P/N 315-098285 CATALOG NUMBER 6196 TSM -1 Interface to MXL System TSM -1 LED operated by the TRI -R relay contacts. From MXL + ALD Loop End of Line Device for TRI -R 3.6K, 1/4W, P/N 140-820185 0 1 0 2 P"I 0 000 Switch + – Input LED TSM -1 03 0 4 Earth Ground5 TRI -R 81-0 710 J} 1 To Air Duct Detector or next device on loop } 24 VDC From MMB -2, TB5 Terminals 9-12 or PSR -1, TB3 Terminals 3-6 or UL Listed Power Supply Notes: 1. For use only with Air Ducts with an incorporated relay. 2. Refer to the TRI Installation Instructions, P/N 315-096242, for specific interface module wiring requirements. 3. Refer to the AD -11P AD-11XPR Installation Instructions, P/N 315-095659, or the AD-31/-3ILP Installation Instructions, P/N 315-093234, for specific duct detector wiring requirements, as applicable. TSM -1 Interface to MXL System TSM -1 LED operated by the Air Duct Detector. From MXL + ALD Loop End of Line Device for TRI -R 3.6K, 1/4W, P/N 140-820185 1To Air Duct Detector or next device on loop 000 Switch + – lnput LED TSM -1 01 02 03 04 Earth Ground 5 TRI -R To Fan Shutdown Control To Air Duct Detector (See Detector installation Instruction for Remote Alarm Indicator Connection) Notes: 1. For use only with Air Ducts without an incorporated relay. 2. Refer to the TRI Installation Instructions, P/N 315-096242, for specific interface module wiring requirements. 3 Refer to the AD -11P Installation Instructions, P/N 315-095659, or the AD-31/-3ILP Installation Instructions, P/N 315-093234, for specific duct detector wiring requirements, as applicable. Mounting Diagram Caution: The TSM -1 switch module does not perform al of the required smoke detector test as specified in NFPA Standard 72. Please refer to the instructions that accompany the detector for the complete test requirements. Single Gang Mounting Box (User Supplied) Keyswitch Mating Plug TSM -1 Assembly LED Connector + — 11 00 JP1 (Piot Used) Siemens Building Technologies Fire Safety Fire Safety Fire Safety 8 Femwood Road 2 Kenview Boulevard Florham Park, NJ 07932 7/03 Brampton, Ontario Tel: (973) 593-2600 5M Canada L6T 5E4 FAX: (973) 593-6670 SFS -IG Tel: (905) 799-9937 Website: www.sbt.siemens.com/fis Printed in U.S.A. FAX: (905) 799-9858 July 2003 Supersedes sheet dated 2/02 SE Sa E T' I Seri's Fire Safety FireFinder XLS and FS -250 Intelligent Initiating Devices Interface Modules ENGINEER AND ARCHITECT SPECIFICATIONS Intelligent Interface Modules for FireFinder XLS and FS -250 Fire Alarm Control Panels HTRI-S, HTRI-D, HTRI-R • Interfaces and Supervises Normally Open or Normally Closed Contacts • Integral SPDT Relay (up to 4 amps) on HTRI-R Model • Dual Input on HTRI-D Model using a single address • Polarity Insensitive with SureWire'"' Technology • Multi -color L.E.D. indicates status (green, amber, red) • Easy front access to programming port and wiring terminals • Mounts 4 inch square 2 1/4 deep box, or double gang box • Dynamic Supervision • Comes with 5x5 inch faceplate • Two wire operation • DPU Device Program/Test Unit programs and Verifies Device's Address and Tests Devices functionality • Electronic Address Programming is Easy and Dependable • U� 0 ULC Listed CFSM, FM, NYMEAApproved Series Introduction The HTRI Series Intelligent interface modules are de- signed to provide the means of interfacing direct shorting devices to the FireFinder XLS and FS -250 Fire Alarm Control Panel loop circuit. The HTRI Series Intelligent interface modules provide the market's most advanced method of address programming and supervision, combined with sophisticated control panel communication. Each HTRI Series interface module incorporates a microcomputer chip. The HTRI Series microcomputer chip technology and its sophisticated bi-directional communication capabilities with the control panel, achieve the state of an "Intelligence Device" Description The HTRI Series intelligent interface modules are available in three models. The HTRI-S and HTRI-R are designed to monitor a normally open or closed dry contact. The interface module reports the contact's status to the control panel. The HTRI-S model can only monitor and report the status of the contact, while the HTRI-R incorporates an addressable Form C relay. The HTRI-R relay and contact device input are controlled at the same address. For the control panel system, the relay and input contact can be controlled as a separate function. The relay is typically used where control or shunting of external equipment is required. The HTRI-D is a dual input module and is designed to supervise and monitor two sets of dry contacts. The Dual Input Module only requires one address but re- sponds independently to each input. The HTRI-D is ideal for monitoring a water flow switch and its respective valve tamper switch. The HTRI has a multi -color Light Emitting Diode that flashes green when operating normally, amber if unit is in trouble condition, and red to indicate a change of state. The HTRI-D flashes twice, once for each ad- dress, the HTRI-R red L.E.D. indicates a change of state in the relay. CATALOG NUMBER 6304 The device's microcomputer chip has the capacity of storing, in memory, identification information as well as important operating status information. Siemens Building Technologies, Inc., Fire Safety Division innovative technology allows all HTRI Series intelligent interface modules to be programmed by using the DPU Device Programming/Test Unit. The DPU is a compact, portable, menu driven accessory that makes program- ming and testing an interface device faster, easier and more dependable than previous methods. The DPU eliminates the need for mechanical addressing mecha- nisms, such as program jumpers, DIP switches or rotary dials, because the DPU electronically sets the HTRI interface's address into the interface's microcomputer chip nonvolatile memory. Vibration, corrosion and other conditions that deteriorate mechanical addressing mecha- nisms are no longera cause for concern. The HTRI Series is fitted with screw terminals for connection to an addressable circuit. The HTRI Series is fully compatible on the same FireFinderXLS and FS -250 circuits with all intelligent H Series detectors, HMS Series addressable manual stations or any other addressable intelligent modules, such as the HZM or HCP. All HTRI Series intelligent interface modules are UL listed. Environmental operating conditions for all HTRI Series modules are 32°F (°C) to 120°F (49°C) with a relative humidity of not greater than 93% non-condensating. Ordering Information Model Description Shipping Wt. Lh. Kg. Part Number HTRI-S Single Input 7 oz. 2 500-033370 HTRI-R Single Input w/Relay 7 oz. 2 500-033300 HTRI-D Dual input 7 oz. 2 500-033360 NOTICE. The use of other than Fire Safety detectors and bases with Fire Safety equipment will be considered a misapplication of Fire Safety equipment and as such void all warranties either expressed or implied with regard to loss, damage, liabilities and/or service problems. Siemens Building Technologies Fire Safety Mounting Data Addressable Interface Model HTRI-S, HTRI-D, HTRI-R mounts directly into a 4 inch square 21/4 deep box or a double gang box (user supplied). A 5 inch square off-white faceplate is included with each HTRI. MOUNTING SLOTS FOR 4 INCH SWITCHBOX MOUNTING SLOTS FOR DOUBLEGANG SWITCHBOX Figure A Mounting the HTRI-S/-D/-R Electrical Ratings Current Draw (Active or Standby): 1 mA HTRI-R Relay Ratings Resistive: 4A, 125 VAC 4A, 30 VDC Inductive: 3.5A, 120 VAC (0.6P.F.) 3.0A, 30 VDC (0.6P.F.) 2.0A, 120 VAC (0.4P.F.) 2.0A, 120 VAC (0.35P.F.) 2.0A, 30 VDC (0.35P.F.) Fire Safety 8 Fernwood Road Florham Park, NJ 07932 Tel: (973) 593-2600 FAX: (973) 593-6670 Website: www.sbt.siemens.com/fis 12/04 5M SFS -IG Printed in U.S.A. Fire Safety 2 Kenview Boulevard Brampton, Ontario Canada L6T 5E4 Tel: (905) 799-9937 FAX: (905) 799-9858 HTRI-S/-D/41 MODULE MOUNTING HOLES FOR SWITCHPLATE December 2004 Supersedes sheet dated 1/03 SIE ENS Catalog Sheet Fire Safety & Security Products 8 Series Notffic.ton ZH & ZR - Strobes, Horns, Horn / Strobes Series ZH r Series ZR p 1 ces Application: Indoor ZR AND ZH Mounting Product Overview Strobes can be synchronized using the Siemens DSC sync modules, FS -250 panel, XLS panel, or PAD -3 power supply with built-in sync protocol Selectable Continuous Horn or Temporal (Code -3) Tones with 90 or 95 dBA selectable setting (ZH) Ceiling -mount models feature field -selectable Candela settings of 15130175195cd and 115/177cd Wall -mount models feature field -selectable Candela settings of 15130175/110cd and 135/185cd Base plate is protected by a disposable cover, one the appliances can quickly snap onto the base after the walls are painted Strobes produce 1 flash per second "Special Applications" listed with Siemens panels EZ Mount Universal Mounting Plate (ZBB) — uses single plate for ceiling and wall mount installations EZ Mount design — with separate base plate — provides ability to pre -wire the base and test the circuit wiring before the walls are covered 0 UL Listed & ULC Listed; FM, CSFM & NYMEA Approved ADA/NFPA compliant Specifications • General - AudibleNisual notification appliances shall be listed for indoor use only - Appliances shall be listed under O UL Standard 1971 (Standard for Safety Signaling Devices for Hearing Impaired) and ® UL Standard 464 (Fire Protective Signaling) Appliances shall use a universal back plate, which shall allow mounting to a single -gang, double -gang, 4 -inch -square, 4" -octal, or a 3 -112" -octal backbox Two -wire appliance wiring shall be capable of directly connecting to the mounting back plate — Continuity check shall occur for entire NAC circuit prior to attaching any audible / visual -notification appliances Dust cover shall fit and protect the mounting plate — Dust cover shall be easily removed when the appliance is installed over the back plate Removal of an appliance shall result in a trouble condition by the Fire Alarm Control Panel (FACP) '08 Series Notification Appliances 2584 Building Technologies Fire Safety & Security Products Specifications — (continued) • Strobes — Strobe appliances shall produce a minimum flash rate of 60 flashes per minute (1 flash per second) over the Regulated Input Voltage Range, and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens — Strobes shall be available with two or four field -selectable settings in one unit, and shall be rated — per 0UL1971 —for up to: • 15130175111 0cd for wall mounted • 135/185cd for wall mounted • 15/30175/95cd for ceiling mounted • 115/177cd for ceiling mounted — Strobes shall operate over an extended temperature range of 32°F to 120°F (0°C to 49°C), and be listed for maximum humidity of 95% RH — Strobe inputs shall be polarized for compatibility with standard reverse -polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP) • Audibles and Audible / Strobe Combinations — Horns and horn I strobes shall be listed for Indoor use under ® UL Standard 464 — Horns shall be able to produce continuous synchronized output or a temporal code -3 synchronized output — Horns shall have at least 2 sound -level settings of 90 and 95 dBA • Synchronization Modules — The strobe portion, when synchronization is required, shall be compatible with DSC sync modules, FS -250 panel, XLS panel, or PAD -3 power supply with built-in sync protocol — The strobes shall not drift out of synchronization at any time during operation — Audibles and strobes shall be able to synchronize on a 2 -wire circuit with the capability to silence the audible, if required — Strobes shall revert to a non -synchronized flash -rate, if the sync module or Power Supply should fail to operate (i.e. — contacts remain closed) — All notification appliances shall be listed for Special Applications: ■ Strobes are designed to flash at 1 -flash -per -second minimum over their "Regulated Input Voltage Range" Note: NFPA-72 specifies a flash rate of 1 -to -2 flashes per second, and ADA Guidelines specify a flash rate of 1 -to -3 flashes per second ■ All candela ratings represent minimum -effective Strobe intensity, based on ® UL Standard 1971 ■ Series ZH Strobe products are listed under ® UL Standards 1971 and 464 for indoor use with a temperature range of 32°F to 120°F (0°C to 49°C) and maximum humidity of 93% (± 2%) ■ Series ZH horns are listed under O UL Standard 464 for audible signal appliances (Indoor use only) Building Technologies Fire Safety & Security Products Mounting Diagram Mounting Options ::r atanrm,....*1 ANDa-A .S;E:1.11C110N ‘C...4t4DE-LA P0114 pAtIDE.L.4. EECTQr AN.. -LA ONTEP fatc-c CANDELAPk id MC CANDELAPONT-2. 1111.1111Mill MC CANDELA POINTER Technical Data Model • Voltage Range (Special Application) Per UL 1971 (VDC/VRMS) i. JUIS 3.• 254 Horn Current Draw See Table Mounting ZR -MC 16-33 15/30[75/110 - 3 Wall ZR -I -IMC 16-33 1351165 - 3 Wall ZR -MC -C 16-33 15/30175/95 - 3 Ceiling ZR -HMC -C 16-33 1151177 - 3 Ceiling ZH-MC 16-33 15130175/110 X 4 Wall . 16-33 . X 4 Wall ZH-MC-C 16-33 15/3075195 X 4 . ZH-HMC-C 16-33 115/177 X 4 ,... ZH 16-33 - ir- 5 Wall or Ceiling in iii r + tl-' ti. ,, ... , Mounting Options ::r atanrm,....*1 ANDa-A .S;E:1.11C110N ‘C...4t4DE-LA P0114 pAtIDE.L.4. EECTQr AN.. -LA ONTEP fatc-c CANDELAPk id MC CANDELAPONT-2. 1111.1111Mill MC CANDELA POINTER Technical Data Model • Voltage Range (Special Application) Per UL 1971 (VDC/VRMS) Strobe (cd) Horn Current Draw See Table Mounting ZR -MC 16-33 15/30[75/110 - 3 Wall ZR -I -IMC 16-33 1351165 - 3 Wall ZR -MC -C 16-33 15/30175/95 - 3 Ceiling ZR -HMC -C 16-33 1151177 - 3 Ceiling ZH-MC 16-33 15130175/110 X 4 Wall ZH-HMC 16-33 135/185 X 4 Wall ZH-MC-C 16-33 15/3075195 X 4 Ceiling ZH-HMC-C 16-33 115/177 X 4 Ceiling ZH 16-33 - X 5 Wall or Ceiling • Available in red and white Building Technologies Fire Safety & Security Products Technical Data - (continued) Table 2: 11 and Zti-MC Flom Reverberant Strobe Setting (cd) ZH-MC and ZH at 24V dBA per UL464 16.0V 24V 33.0V Continuous Hom High 83 87 90 Low 77 81 83 Code 3 Hom or *March Time High 79 82 86 Low 72 76 79 *Available in sync mode only Table 3: ZR Strobe Current Draw (Amps) 116-33 Volts Table 5: ZH Horn Current Draw (Amps) Horn Senting 16-33 Volts DC High* 0.044 Low* 0.016 FWR High* 0.075 Low' 0.045 0dLTalt D;ae the scone forthe Continuous Ham, Coe 3 I koea and Mardi -funs Sec ings Table 4: ZH HomrStrote Current Draw (Amps) at 16-33 Volts Strobe Setting (cd) MC HMC MC -C HMC -C 15 30 75 110 135 185 15 30 75 95 115 177 DC 0.064 0.098 0.175 0.233 0_318 0.445 0.069 0.111 0.290 0.264 0.318 0.445 FAR 0.108 0.164 0.266 0.368 0.482 0.664 0.117 0.180 0.297 0.398 0.482 0.684 Table 4: ZH HomrStrote Current Draw (Amps) at 16-33 Volts * Current Draw is the sarne for the Continuous Hom, Cade 3 Hom and March lime Settings Details for Ordering / Mounting Requirements / Approvals Model Number Order Code Strobe Setting (cd. Horn Setting MC HMC MC -C HMC -C 15 30 75 11D 135 165 15 30 75 95 115 177 DC High* 0.078 0-113 0.195 0.259 0.371 0.506 0.037 0.131 0 0.292 0.371 0.506 Low* 0.074 0.107 0.166 0.246 0.324 0.455 0.075 0.121 0213 0277 0.324 0.455 ,R High' 0.141 0.200 0.302 0.406 0.521 0.722 0.149 0.216 0.331 0.436 0.521 0.722 Low' 0.123 0179 0290 0.391 0.497 0.699 0.131 0.195 0.319 0.421 0.497 0.699 * Current Draw is the sarne for the Continuous Hom, Cade 3 Hom and March lime Settings Details for Ordering / Mounting Requirements / Approvals Model Number Order Code Rtounting Options Agency Approvals UL ULC CSFH FM ZH-MC-R 560-638.,6181 3, 0, E, F XX X X ZH 4AC-W 500-355162 6, 0, E. F XX X X ZH-HMC- 500-538163 6, 0, E. F X X X X ZH-HMC-W 500-636164 3, 0, E, F XX X X ZH-n^, 500-3158 5, 0, E, F XX X X ZH-W 500-160 5, 0, E, F X X X X ZH-MC-CR 500.3135185 6, 0, E, F XX X X ZH-MC-CW 500-105 5, 0, E, F XX X X ZH-HMC-CR 500-W55187 6, t}, E. F XX X X ZH-HMC-CW 500-635183 5,0,5, F X X X X ZR -MC -R 500-W3159 6, 0, E, F XX X X ZR -MC -W 500-0.8170 6, 0.5, F XX X X ZR -HMC -R 00-65171 6, 0, E, F XX X X ZR -HMC -W 500-172 £, 0, E, F XX X X ZR -MC -CW 500-W8174 8174 3, D. E. F X X X X ZR- 1C -C3 500-W5173 6, 9, E. F XX X X ZR -HMC -CR 5005175 6, 0, E. F XX X X ZRS-HMC-CW 500-W88176 5, 0, E. F XX X X ZBB-R 500-836183 A)essory- Includes btee, d1St 001/F-‘7,. mounting screws and "€ 3Ita o sheet 265-W 500-835184 Axeosory - Includes base, dust cover, mounting sc,-ews and 1 atbri sheet = Refer -to Data Sheet #2585 For axavnvng options X = iistedlapprov Notice: This marketing catalog sheet is not intended to be used for system design or installation purposes. For the most up-to-date information, refer to each product's installation instructions. Building Technologies Fire Safety & Security Products Fire Safety 8 Femwood Road Florham Park, NJ 07932 Tel: (973) 593-2600 SFS FAX: (973) 593-6670 Printed in U.S.A. URL: www.SBT.Sremens.com/FIS Fire Safety 2185 Derry Road West Mississauga, Ontario L5N 7A6 Canada Tel: (905) 799-9937 FAX: (905) 799-9858 December 2008 Supersedes sheet dated 7/07 • ' 1 i,--- 0, 0 = , , ., A,t= tte,f== igi:t,':fi? ,1, 'A ',ii -4; = = ,tt= 4,, ,- t.= . --ti 1'M:44V 40' 0' t '.d' t4 NW gr ' love A k SHOP DRAWINGS DATE Current Load: Standby: tA My,kAtr' A „Ir, Alarm: '.- 14) Device Type Qty Amps Total Amps Total Total HFP-11 1 0.0022 0.0022 0.0023 0.002 Main System Board AD2-P 1 0.0635 0.0635 0.064 0.064 ZI4MCCWCD , 11 ' HTR -R. 1 0.009600 1 0.0096 0.021 0.021 4 1 0.131 ..mc 75CD ' 8 - 0,222 ZH-MC-CW ©95CD 1 . 1 0.292 0.292 -H C -C 15CD. '' , 0.0731 Amps 0.085 Amps • ' 0 M 0 '.d' t4 NW gr ' love A k SHOP DRAWINGS DATE LO tA My,kAtr' A „Ir, '.- 14) z-• Device Type Qty Amps Total Amps Total 0 Main System Board 1 0.03 0.03 0.030 0.030 ZI4MCCWCD , 11 ' 0.0875 ZJ1-[Mc-CW ©30CD 4 1 0.131 ..mc 75CD ' 8 - 0,222 ZH-MC-CW ©95CD 1 1 0.292 0.292 -H C -C 15CD. '' , 0.371 ZR -MC -CW ©15CD 8 0.069 0.552 ZR -MC -W ©15CD 0.064 0O3 Amps . 0.874 Amps Standby Current Load: 0.03 Amps , - F�r 24. Hours = '0.720 Amp -hours Alarm Current Load: 0874 Amps For 5Minutes 0.073 Amp -hours 25% Derating= 0.992 Amp -hours Total System Current Load: 0.992 Amp -hours ' ' ' ' '' -,, ' ' :,,,,,,,,,,,,,,03',,e,'.M;;. ,1:, < , , i . ',' ,,i,,,;,.,,<,:,.,,:.!1,.:,t`4,:,,3 ' '"'-' '''' ' -, '" 4: ,,;.; ,,,,'.;;t,P,11,bla 4 '0,„4'';',0: A -,:,,,':i:`,5 ,,,,,T, -,- L.,,, --,-. ,, ":'AfiV;•::- ' ; '-,1';,,.' , , Notification A PROJECT: DAISO - JAPAN Panel: EXISTING PAD -3 POWER SUPPLY Date: August 13, 2015 «e, pliance Circuit Detail vv,Z17V r Wire Resistance 2.58 CURRENT TOTAL= 1044.00 ,...;,, ,..... i .. — ZH-MC-CW ©156-13i 87 87 ZR -Mo -CW ©30CD 131 0 4 ZH-MC-CW ©75CD 222 888 21-1-MC,CW ©95CD 292 0 -cw @i6co , 6 9 ZR -MC — J ' 3711 ZH-MC-CW ©115CD 0 ZR -MC -W ©15CD ' 64 01 DEVICES= 6 175 0 TOTAL mA= 1044 14 'Total Wire Resistance ( R ) Total Device Load, Amps (I) yoltage Drop ( E ) EOL Voltage 3 143 I 2323 1044 L*2 )*(Rift) 0 7 (Total Cct Load) 1",04 0.77 043 SYSTEM CALCULATIONS 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS TO EXISTING SIGNALING ( CIRCUIT/DEVICE 0 120VAC, DEDICATED ( BY OTHERS ) 2C—cp. cD—S • Ps EX ) EXISTING NAC CKT S1 ) EXISTING NAC CKT S2 S3-1 15cd (LOCATED AT TORAGE AREA 102) S3-2 S3-3 S3-4 S3-5 75cd 15cd 75cd 15cd TO OTHER DEVICES SINGLE LINE DIAGRAM S3-6 15cd EOL S1 FLAG NOTES: EXISTING RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. EXISTING SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110VAC BRANCH CIRCUIT. DUCT DETECTOR, RELAY MODULE FOR FAN SHUTDOWN & TEST SWITCH LOCATIONS TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. IREV. BY: 0 M 0 DESCRIPTION SHOP DRAWINGS DATE LO '.- 14) z-• C) 0 2 <<<<< Zco c 0 Jj 07) < a cco eL <LLJI- • 2 I—05 z z Liu O CD M(.:C) < C5)) 0 < co > w cc cf) D LL cc 0 0 w z —J w — J 0 z (75 0 z (/) z0 0 1.1.1 CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE DATE:08/13/15 BACKROUND PLAN PROVIDED BY: \1_013 NUMBER:13153- 1} SHEET Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved FA -03 • VX/ :......... l ...EOL S3 S3-6 75cd 'D cio'-a" V.I.F. // // / // / / : ,/ / REF. E1 . T AIL SAL..I.W SLOOK S3 5 75 d IT W�. _ _._ _ _. a _. is tj7 / i/// / /// f/ S3-4 75cd ®D HTR -R (.......103.._..�XISTIF\ WAR C 0 0 M 15cd D TSM l�� S3-2 75cd S 10RACE.. i 102 S3-3 15cd EX 4 D R EX EX CO MOR ......._104.......1 / ///// , / .-/ /fff/ FIRE ALARM SYSTEM PLAN 1 D TO OTHER DEVICES FLAG NOTES: EXISTING RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. EXISTING SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 11 OVAC BRANCH CIRCUIT. DUCT DETECTOR, RELAY MODULE FOR FAN SHUTDOWN & TEST SWITCH LOCATIONS TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 m D fl DESCRIPTION SHOP DRAWINGS 11 is tj7 / i/// / /// f/ S3-4 75cd ®D HTR -R (.......103.._..�XISTIF\ WAR C 0 0 M 15cd D TSM l�� S3-2 75cd S 10RACE.. i 102 S3-3 15cd EX 4 D R EX EX CO MOR ......._104.......1 / ///// , / .-/ /fff/ FIRE ALARM SYSTEM PLAN 1 D TO OTHER DEVICES FLAG NOTES: EXISTING RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. EXISTING SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 11 OVAC BRANCH CIRCUIT. DUCT DETECTOR, RELAY MODULE FOR FAN SHUTDOWN & TEST SWITCH LOCATIONS TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 m D DESCRIPTION SHOP DRAWINGS DATE Z M co 0 W �CALE: 1/4"=1'0" DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE DATE: 08/13/15 BACKROUND PLAN PROVIDED BY: .OB NUMBER: 13153-1} SHEET FA -04 Ec) TUKWILA FIRE DEPARTMENT 116 w. call 206-575-4407 and g ve tls Fire Permit No. rtnd erect ^d , ss ?or shut- c: ,uvn or° R.T.IforAion approval. RETAINER STRAP WHERE REQUIRED IN SEISHIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD ROD PIPE SWIVEL RItdG • STEEL JOIST/TRUSS HANGER DETAIL NTS 8'- •" 67' -II". 13'70" 4'-0" 4'-0" . 7'-O" /may` ��//' /{'' C/LLLG'LLL_LLL,4 ,' :' �' .' //' / /LL, .FL/L/LLLLGL LCLf`L/�LGC=' //LL/_✓ZLZ:_ '''''',2//22,./.,,Z/W42/71//p// / ,//////„/% ;X/ //4/<2Z4 .Z.L /./ZL ,/ / ;% / / r /' LZL' ` / /., /;; ° // //' //' ALL L �� L�LL � /��LL / % /' ' � , / /.// / ��L=fL'1ZL_ //: !• ,ice' ,/ Li�L�L• LLGf`LLL j/LLG• L�jLLL'�LLLL LL��L ,-' LLL/LLL/� LG��LL-/ c � .; • �• GN -0; •3 4 . xy .. _ All. o •I • • 4 • //11 �r. 0 0 '• !i" 3r �, �l ::.' ;x »» 4 +21'-0". ' •. 0 RGN-O r `o� ; OPEN TO ... 1 I r �' "' ( y STRUCTURE °"f ABOVE _ GN -O -GN-O• F& 4 10 b'-3" 31-1" TYP. a®r` 0 .. .... . . r- Mi.v r. tii."tt L.. + _ \'ti. 111111� pit . . _— - �. • 77 '77% '//7., i / /,, /7///�/��// / 1/' ''//•%.j .,- / / 7. // y/ / /.� ,'7&/7/ / / 0.\/C ///,..- /r '/ / ', b'-6" %// ,. /// L. I 7/4'-2" 6'-6"i \/ AC. : • ‘' L.. X f REFLECTED CEILING PLAN. SGALE. 11 3 /l Design per NFPA 13, Ordinary Hazard Group 2 All materials to be new, U.L. listed, and F.M. approved All fire sprinkler heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart o 40 — Relocate Globe Model GL5651 Standard Response 155° Chrome Pendents 1/2 x I/2 (w/ 401 Trim) O 1 —Add Globe Model GL5651 Standard Response 155° Chrome Pendents 1/2 x 1/2 (w/ 401 Trim) 11 t•sa g i r£a Iii O Without Comments • • As MAO. in fie:4 • The Attached Letter pians have beeen reviewed by The Tukwila Fire , ''-1wndori Bureau for •c.:Yl ornance With current City . :1CI3;%15. Acceptance s Strb'lect: r'r, :mors and whiter, do f oi..1l..rrlori,:r: '.f olatic,rrs of adopted -T41dards and ordinaric. s i Y r:esoor,sibiii'ty for the ...;;quacy of design rt?sr. vole'+r the designer. !)llll"(('151 deletions a','si ri::vi'riorr7 ;'(.' tneSE: drawings after r.r,isdate IMIi' ` o d i ht,:. acceptance and vjlii require a resubrnitca r,)t. revised dr'awingt� for ..suk,e q'uent .:ipprov 1. Final acceprznce is subject to field test and inspection by • The Tukwila Fire Prevention Bureau. Late: -�`1-1J By: S6r FlexHead Sprinkler Drop 111 .-:,;;;,;,;,i. Corrugated stainless steel hose with stainless steel brat 0 available in 2', 3',4',5' & 6' legnths •l;ikkiak `sus:• Adjustable Mob II MuIU-Port Bracket • • • • FLEXIVAii IN°USI0.IES/ • Flexhead omrriercial Ceilirig Unit •' T -Bar Gelling Installation Model #2024,2036,2048,060,2672 P CERTTE 15r{Oq•Ts OF COMNOTON PETENCY FIRE PROTECTION SPRINKLER eYaTE John J. Abel 9760.0591 -CQ Level3 vm Fire Protection, Inc. C ` w'►_FP044LL ILL \ 0 I aignaturr Expires 1211HS dl VICINITY MAP CROWN FIRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 Daiso Japan \%~79 Southcenter Mall Space # 1378 Tukwila, WA PAD SEP 10 2015 TUKWILP FIRE -�df�lP.z6 DATE:. el" z" (.S DRAWN: lr SCALE: ' 3'((0 )1w ? -Re/ 11,271120 SITE LOCATION CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East Tukwila, WA 98188 206-575-4407 Date application accepted: FIRE PROTECTION SYSTEMS PERMIT APPLICATION Applications and plans must be complete in order to be accepted for plan review. **PLEASE PRINT** King Co. Assessor's Tax No.: Site Address: IS7cFs 5oviiicerlks Ma. 11 Suite Num be )378 Floor: Tenant Name: "exxs) "Sit New Tenant? ❑ - Yes ❑ - No Property Owner's Name: V,..P \--c" \ eY151-13 Mailing Address: City State Zip CONTACT PERSON -if there are questions about the submittal. Name: k2& 1 RC12U7S O/) Day Telephone: 1425 '�s-1 ' 1 o l Company Name: Crown )) -t1 on, 1Y1 C Mailing•Address: P© '2>< \2 \ 1� WA 1\` '�-�,� �T\ P�'BCity Sat- Zi E-mail Address: \ 1 cEc.,ybv3n4 p, Cr,in Fax Number: Total number of new/relocated devices or sprinkler heads: �l Valuation of Project (contractor's bid price): $ (J• Scope of Work (please provide detailed information): _\ y0 , pke3,a PERMIT APPLICATION NOTES Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules. Expiration of Plan Review -Every permit issued shall became invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in • writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILDING 0 ER OR AUTHORIZED AGENT: Signature: t^' Print Name: (IC��jj SS1(_//'I 9?Oh'J)7&7? Plan Permit App.doc 1/2/13 Date: Ci, /l ilc Day Telephone: /42-5 • (' 1 TFD FP Form 8 FIRE SPRINKLER CORPORATION DESCRIPTION AND OPERATION AUTOMATIC SPRINKLERS GL SERIES UPRIGHT •PENDENT VERTICAL SIDEWALL HORIZONTAL SIDEWALL CONVENTIONAL (OLD STYLE) The Globe GL Series Sprinkler is a low profile yet durable design which utilizes a frangible glass ampule as the thermo- sensitive element. While the sprinkler provides an aestheti- cally pleasing appearance, it can be installed wherever stan- dard spray sprinklers are specified. This sprinkler series is available in various styles, orifices, temperature ratings and finishes to meet varying design requirements. The heart of Globe's GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern depending upon the deflector style used. TECHNICAL DATA O See reverse side for Approvals and Specifications. O Temperature Ratings - 135°F (57°C), 155°F (68°C), 175°F (79°C), 200°F (93°C), 286°F (141°C), 360°F (182°C) O 500°F (260°C) Available Upon Request Without Approvals o Water Working Pressure Rating - 175 psi (12 Bars) o Factory tested hydrostatically to 500 psi (34 Bars) O Maximum low temperature glass bulb rating is -67°F (-55°C) O Frame - bronze 0 Deflector - brass 0 Screw - brass O Bulb seat - copper 0 Spring - nickel alloy 0 Seal - teflon O Bulb - glass with glycerin solution, 5mm size UPRIGHT CONVENTIONAL PENDENT VERTICAL SIDEWALL HORIZONTAL SIDEWALL O SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING CLASSIFICATION AVAILABLE SPRINKLER TEMPERATURES BULB COLOR N.F.P.A. MAXIMUM CEILING TEMPERATURE ORDINARY ' =135°F/155°F 57°Ci68°C ORANGE/RED 100°F 38°C INTERMEDIATE 175'F1200°F 79°C/93°C YELLOW/GREEN 150°F X66°C HIGH 286°F 141°C BLUE 225°F 107°C EXTRA HIGH : 360°F. ;. ;182°C MAUVE 300°F 149°C ULTRA HIGH 500°F ^ ' 260°C BLACK 475°F 246°6, 4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658 MARCH 2011 A-65 989-846-4583. FAX 989-846-9231 BULLETIN GL5661, REV. #4 AUTOMATIC SPRINKLERS GL SERIES SPECIFICATIONS NOMINAL "K" FACTOR THREAD SIZE LENGTH 1 FINISHES 2.8 (39 metric) 1/2" NPT 2 1/4" (5.7 cm) Factory Bronze * 500°F * 260°C cULus FM LPC Bright Chrome 4.2 (59 metric) 1/2" NPT 2 1/4" (5.7 cm) Satin Chrome 2 X X X X White Polyest3 5.6 (80 metric) 1/2" NPT 2 1/4" (5.7 cm) Black Poly sterr2.3 7.8 (111 metric) 1/2" NPT 2 1/4" (5.7 cm) Wax Coated 2,3,4 X X X X Lead Coated 2.3 8.1 (116 metric) 3/4" NPT 2 7/16" (6.2 cm) Wax over Lead 2,3,4 NOTE: METRIC CONVERSIONS ARE APPROXIMATE. APPROVALS 1 HORIZONTAL SIDEWALL IS 2 9/16". 2 FINISHES AVA LABLE ON SPECIAL ORDER. a AVAILABLE AS cULus LISTED CORROSION RESISTANT -WHEN SPECIFIED ON ORDER. 4 WAX COATING UL LISTED UP TO 200°F ONLY. STYLE SIN MODEL ORIFICE SIZE 135°F 57°C 155°F 68°C 175°F 79°C 200°F 93°C 286°F 141°C 360°F 182°C * 500°F * 260°C cULus FM LPC CE NYC - DOB MEA 101-92-E GL2861 2.8 X X X X X X X X — — — X GL4261 4.2 X X X X X X X X — — — X UPRIGHT GL5661 5.6 X X X X X X X X X X X X GL8161 7.8t X X X X X X X X — — — X GL8164 8.1 X X X X X X X X X X X X GL2851 2.8 X X X X X X X X — — — X GL4251 4.2 X X X X X X X X — — — X PENDENT GL5651 5.6 X X X X X X X X X X X X GL8151 7.8t X X X X X X X X X — — X GL8156 8.1 X X X X X X X X X X X X VERTICAL GL5675 5.6 X X X X X X X X X — — X SIDEWALL $ GL8176 8.1 X X X X X X X X — — — X GL2870 2.8 X X X X X X X X — — — X HORIZONTAL GL4270 4.2 X X X X X X X X — — — X SIDEWALL § GL5670 5.6 X X X X X X X X X — — X GL8171 8.1 X X X X X X X X — — — — CONVENTIONAL GL5668 5.6 X X X X X X X — — X X — (OLD STYLE) GL8169 8.1 X X X X X X X — — X X — ORDERING INFORMATION SPECIFY • Quantity • Model Number • Style • Orifice • Thread Sizes • Temperature • Finishes desired • Quantity - Wrenches - P/N 325390 (1/2"); P/N 312366 (L.O.) FIRE SPRINKLER CORPORATION MARCH 2011 *500°F 260°C AVAILABLE UPON REQUEST WITH NO APPROVALS. t 1/2" NPT. $ VERTICAL SIDEWALL UL LISTED FOR LIGHT HAZARD ONLY. PENDENT VERTICAL SIDEWALL UL LISTED FOR 6' MIN. SPACING. UPRIGHT VERTICAL SIDEWALL UL LISTED FOR 9' MIN. SPACING. § HORIZONTAL SIDEWALL UL LISTED FOR DEFLECTOR 4" TO 12" BELOW THE CEILING, FM APPROVED 4" TO 6". GLOBE® PRODUCT WARRANTY Globe agrees to repair or replace any of its own manufactured products found to be defective in material or workmanship for a period of one year from date of shipment. For specific details of our warranty, please refer to Price List Terms and Conditions of Sale (Our Price List). 4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658 989-846-4583 FAX 989-846-9231 1-800-248-0278 www.globesprinkler.com PRINTED U.S.A. BULLETIN GL5661, REV. #4 FIRE SPRINKLER CORPORATION DESCRIPTION AND OPERATION AUTOMATIC SPRINKLERS GL SERIES UPRIGHT 0 PENDENT VERTICAL SIDEWALL HORIZONTAL SIDEWALL CONVENTIONAL (OLD STYLE) The Globe GL Series Sprinkler is a low profile yet durable design which utilizes a frangible glass ampule as the thermo- sensitive element. While the sprinkler provides an aestheti- cally pleasing appearance, it can be installed wherever stan- dard spray sprinklers are specified. This sprinkler series is available in various styles, orifices, temperature ratings and finishes to meet varying design requirements. The heart of Globe's GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern depending upon the deflector style used. TECHNICAL DATA o See reverse side for Approvals and Specifications. o Temperature Ratings - 135°F (57°C), 155°F (68°C), 175°F (79°C), 200°F (93°C), 286°F (141°C), 360°F (182°C) o 500°F (260°C) Available Upon Request Without Approvals o Water Working Pressure Rating - 175 psi (12 Bars) o Factory tested hydrostatically to 500 psi (34 Bars) o Maximum low temperature glass bulb rating is -67°F (-55°C) o Frame - bronze o Deflector - brass o Screw - brass o Bulb seat - copper o Spring - nickel alloy o Seal - teflon o Bulb - glass with glycerin solution, 5mm size UPRIGHT CONVENTIONAL VERTICAL SIDEWALL HORIZONTAL SIDEWALL o SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING CLASSIFICATION AVAILABLE SPRINKLER TEMPERATURES BULB COLOR N.F.P.A. MAXIMUM CEILING TEMPERATURE ORDINARY 135°F/155°F :. ` ` 57C/68°C ORANGE/RED 100°F 38°C INTERMEDIATE 175*F/200°F 79C/93°C YELLOW/GREEN 150°F 66°C HIGH 286°F. 141°C BLUE 225°F 107°C EXTRA HIGH 360°Ft , 182°C MAUVE 300°F 149°C ULTRA HIGH 500°F 260°C BLACK 475°F 246°C 4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658 MARCH 2011 A-65 989-846-4583. FAX 989-846-9231 BULLETIN GL5661, REV. #4 AUTOMATIC SPRINKLERS GL SERIES SPECIFICATIONS NOMINAL "K" FACTOR THREAD SIZE LENGTH 1 FINISHES 2.8 (39 metric) 1/2" NPT 2 1/4" (5.7 cm) Factory Bronze * 500°F * 260°C cULus FM LPC Bright Chrome 4.2 (59 metric) 1/2" NPT 2 1/4" (5.7 cm) Satin Chrome 2 5.6 (80 metric) 1/2" NPT 2 1/4" (5.7 cm) White Polyesterz3 Black Polyester 7.8 (111 metric) 1/2" NPT 2 1/4" (5.7 cm) Wax Coated 2.3,4 X GL4261 4.2 Lead Coated 2,3 8.1 (116 metric) 3/4" NPT 2 7/16" (6.2 cm) Wax over Lead 2.3,4 NOTE: METRIC CONVERSIONS ARE APPROXIMATE. APPROVALS 1 HORIZONTAL SIDEWALL IS 2 9/16". 2 FINISHES AVA LABLE ON SPECIAL ORDER. 3 AVAILABLE AS cULus LISTED CORROSION RESISTANT -WHEN SPECIFIED ON ORDER. 4 WAX COATING UL LISTED UP TO 200°F ONLY. STYLE SIN MODEL ORIFICE SIZE 135°F 57°C 155°F 68°C 175°F 79°C 200°F 93°C 286°F 141°C 360°F 182°C * 500°F * 260°C cULus FM LPC CE NYC - DOB MEA101-92-E GL2861 2.8 X X X X X X X X — — — X GL4261 4.2 X X X X X X X X — — — X UPRIGHT GL5661 5.6 X X X X X X X X X X X X GL8161 7.8f X X X X X X X X — — — X GL8164 8.1 X X X X X X X X X X X X GL2851 2.8 X X X X X X X X — — — X GL4251 4.2 X X X X X X X X — — — X PENDENT GL5651 5.6 X X X X X X X X X X X X GL8151 7.8t X X X X X X X X X — — X GL8156 8.1 X X X X X X X X X X X X VERTICAL GL5675 5.6 X X X X X X X X X — — X SIDEWALL $ GL8176 8.1 X X X X X X X X — — — X GL2870 2.8 X X X X X X X X — — — X HORIZONTAL GL4270 42 X X X X X X X X — — — X SIDEWALL § GL5670 5.6 X X X X X X X X X — — X GL8171 8.1 X X X X X X X X — — — — CONVENTIONAL GL5668 5.6 X X X X X X X — — X X — (OLD STYLE) GL8169 8.1 X X X X X X X — — X X — ORDERING INFORMATION SPECIFY • Quantity • Model Number • Style • Orifice • Thread Sizes • Temperature • Finishes desired • Quantity - Wrenches - P/N 325390 (1/2"); P/N 312366 (L.O.) MARCH 2011 *500°F 260°C AVAILABLE UPON REQUEST WITH NO APPROVALS. t 1/2" NPT. $ VERTICAL SIDEWALL UL LISTED FOR LIGHT HAZARD ONLY. PENDENT VERTICAL SIDEWALL UL LISTED FOR 6' MIN. SPACING. UPRIGHT VERTICAL SIDEWALL UL LISTED FOR 9' MIN. SPACING. § HORIZONTAL SIDEWALL UL LISTED FOR DEFLECTOR 4" TO 12" BELOW THE CEILING, FM APPROVED 4" TO 6". GLOBE® PRODUCT WARRANTY Globe agrees to repair or replace any of its own manufactured products found to be defective in material or workmanship for a period of one year from date of shipment. For specific details of our warranty, please refer to Price List Terms and Conditions of Sale (Our Price List). 4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658 989-846-4583 FAX 989-846-9231 1-800-248-0278 www.globesprinkler.com PRINTED U.S.A. BULLETIN GL5661, REV. #4 pi( e lFIRE A UK TE ILA, ASHI N DDITION ON SHEET \ UN/ 3E� SHEET TITLE FA -01 SYSTEV \FOfv ATI O FA -02 TYPICAL WHI\ G A \D VOU\TI \G DETAILS FA -03 SYSTE V CALCULATIO\S A \D SI\GLE LI\ E DIAGA V FA -04 FRE ALAS IV SYSTE V PLA\ SHEET INDEX t VV thout Comments As Noted in Red ® Per The Attached Letter These mans have been reviewed by The Tukwila Fire Preve:;tion Bureau for conformance with current City stancards. Acceptance is subject to errors and o: ni.zIons which do not authorize violation; of adopted -:flclards and. >.<rdinances. 'rhe responsibility for the -Luny of design rests totally with the designer. ^r;s, deletions or revisions to these drawings after ger 1mill void this :-acceptance and will require a . •.Ibmttt:ai of revised drawings for subsequent approval. acceptance is subject to field test and Inspection by TulCw is Fre Prevention Bureau. e: 6' ()- - l l ay: .< 1 WISE SCHE TUKWILA FIRE DEPARTMENT Please call 206-575-4407 and give this Fire Permit No,, End exact acldtess for shut- ;; s :`C, a;:i0i1i approval: I: NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and t-PrrninrOtlon of the testino. D U L- A\ D CO \ D U IT FILL CHAT WIRE DESIGNATION SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKED D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V' SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION • FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4, INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vaC POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NEPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 1 1 1 2 3 3 EX EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT BPS REMOTE BOOSTER POWER SUPPLY PAD -3 SIEMENS PAD-3-ENCL 66" A.F.F. TO TOP DUCT DETECTOR AD2-P W/ SIEMENS HFP-1 1 DET. DUCT HOUSING VERIFY IN FIELD TSM DUCT DETECTOR TEST SWITCH TSM -1 SIEMENS 1 -GANG BOX VERIFY IN FIELD HTR -R INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP BOX VERIFY IN FIELD Di FIRE ALARM HORN STROBE ZH-MC-CW SIEMENS 4S DEEP BOX CEILING FIRE ALARM STROBE ZR -MC -CW SIEMENS 4S DEEP BOX CEILING TSM EX DUCT DETECTOR TEST SWITCH (EXISTING) TSM -1 SIEMENS EXISTING VERIFY IN FIELD ® EX SMOKE DETECTOR (ADDRESSABLE -PHOTO) (EXISTING) HFP-1 1 SIEMENS EXISTING CEILING A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A SYMBOLS LEGEND NORDSTROM 3 LEVELS 171,2.75sf GEO. IGCOI 10 10001 10 FNO 81.NK J�G AG� DEMEV 4000 1!! WASTONG10N NAIL ,LE MARS IPi�Et.6J:i.TLS macys 4 LEVELS NT u 7 44 K Vi AO0RCR04PIe. 250,407st 1. DAISO JAPAN 1378 }�r .�Cr`��� T110 RARE ROA' GN .VIM. GEST 000 ICOILE (,,r�{GV/ AVER te COLD INI..s I � GAZE+ hUL'�5AEL�SS AY WGTAND 1R CNOW Ni80 1001'0 10000 now ft Nl'11 ROM 00<1(011 1.4 COUNTY GNAW( Nal) NEYTX1 :y, ELENS EXISTING JCPenney 3 L 1:VELS 276,168sf PAID AUG -9 2011 TUKWILA FIRE 41:?'7373 7aoi% Lu C13 ca Q 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 z 0 (75 w w Q w J w REV. BY: og 0 DESCRIPTION SHOP DRAWINGS DATE 08/05/11 2aaaaa /GALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 08/05/1 1 BACKROUND PLAN PROVIDED BY: WIRE DESIGNATION GENERAL NOTES SITE PLAN Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved ,JOB NUMBER: 55307 FA -01 } SHEET %1 /�6& / THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCA11ON OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TUBE OUTLET SAMPLING TUBE INLET SAMPLING DUCK OVER 3' WIDE: SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL 120VAC-60NZ DEDICATED E1lERGENCY N01E: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. *CONTACT RATINGS 4.0A 0 125VAC 4.0A 0 30VDC EVAPLR64sgifoLtADV TO NEXT ADDRESSABLE (+ DEVICE STIP IF LAST DEVICE µ- FROM XLS CONTROL PANEL( DR PREVIOUS ADDRESSABLE DEVICE I s}) ' GROUND'S * J O O 0 HTRI-R �-0 0 0' 0' ©• 0 O NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. C -CABLE C -CABLE 0 FROM PREVIOUS > (+) ADDRESSABLE > DEVICE (-) 00 0 PAD -3 00 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 0 s 0 0 0 0 0 3.6k EOL (-) (+) SPARE ; SPARE SPARE (-) NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTA11ON. (+) 0 WIRE DESIGNATION: NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE TWISTED PAIR WITH SHIELD #1B FPLIFPLR RED (JACKET) *CONTACT RATINGS 4.0A 0 125VAC 4.0A 0 30VOC FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTA11ON. O 0 GROUND 0 0 0 0 I ®, I I °• // HTRI-R (-) 0 � (+)> TO NEXT DEVICE OR STOP IF LAST DEVICE (-) DRY CONTACTS TO VAV FAN SHUTDOWN PROVIDED BY MECH/ELEC. DUCT DETECTOR, TEST SWITCH & RELAY MODULE WIRING DETAIL (+) HORN STROBE OR STROBE ONLY 80" A.F.F. (OR UNLESS OTHERWISE SPEC FIED) 4S DEEP BOX HORN STROBE & STROBE WALL MOUNTING DETAIL HORN/STROBE OR STROBE ONLY HORN/STROBE OR STROBE ONLY HORN/STROBE OR STROBE ONLY POWER SUPPLY & RELAY MODULE WIRING DETAIL HONR STROBES & STROBES ONLY WIRING DETAIL TO NEXT DEVICE OR END OF LINE TYPICAL WIRING AND MOUNTING.DETAILS CEILIN TILE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER TIN TEMPERA RE: +32' F (0' C) TO 100' F (38' C) HUMIDITY: 0-9 % RELATIVE HUMIDITY, NON—CONDENSING HFP-11 SMOKE DETECTOR —� FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN ( )> DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION HATH DUCT HOUSINGS AD -11P OR AD-11XPR --- DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW (+) SMOKE DETECTOR WIRING DETAIL 1•0kT> 00 SUPPORT BRIDGE 4" SQUARE DEEP BOX CEILING /— HORN STROBE STROBE ONLY DROP CEILING MOUNTING HARD LID CEILING > TO NEXT ADDRESSABLE DEVICE SUPPORT BRIDGE 4" SQUARE DEEP BOX CEILING HORN STROBE STROBE ONLY HARD LID MOUNTING HORN STROBE & STROBE CEILING MOUNTING DETAIL JUNCTI❑N BOX MOUNTED ON CEILING FLEX JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT / / / 0 0 Io 0 TO NEXT DEVICE CADDY BAR SMOKE/HEAT DETECTOR SUSPENDED ILLUMINATED CEILING SMOKE/HEAT DETECTOR MOUNTING DETAIL Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved w) -t n z '4 1743 IST FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY:_l 0 m 0 DESCRIPTION SHOP DRAWINGS DATE Lo0 to 0 1 �CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 08/05/11 BACKROUND PLAN PROVIDED BY: �OB NUMBER: 55307 SHEET FA -02 DAISO FACP ADD-ONS' ., , !ii`:4))4",.`g4"4''''''' ' ': - - , '''' "gV''gr,g''''':''',g'"`}-'-'-l";A„''''i''''' , •„ ", Calculations DESCRIPTION SHOP DRAWINGS Current Load: C rren 1-6 '' '--', ,:=0 :-',f,:-. ,:::,;,-- Standby: Alarm: ', °' , . , 0 0 . Device Type Qty Amps Total Amps Total Total HFP-11- <<<<< ' 0.0022 0.0022 0.0023 0.000 AD2-P 1 0.0635 0.0635 0.064 0.064 0.030 HTR -R 2 0.009600 ' : ' 070096 0.021 0.042 ZH-MC-CW @30CD 1 0.131 Zi-1-MC-CVV ©75CD 0.222 iZH-MC-CW @95CD 2 0.0731 Amps 0.106 Amps , t , Signal'4111,71 C: Paneli' BatteryLoad Calculations DESCRIPTION SHOP DRAWINGS C rren 1-6 '' '--', ,:=0 :-',f,:-. ,:::,;,-- ' " ,.,= ,' ° ,:',1c,' ' =,,.,Standby: '',45','.,=',4` ', °' , 0 0 Device Type Qty Amps Total Amps Total 2 <<<<< Main System Board 1 0.03 0.03 0.030 0.030 ZH-MC-CW 5CD , 0.0875 ZH-MC-CW @30CD 1 0.131 Zi-1-MC-CVV ©75CD 0.222 iZH-MC-CW @95CD 2 0.292 0.584 Zi -I -HMC -CW ©115CD 0.371 ZR -MC -CW @15CD 3 0.069 0.207 ZR C -W ©15CD 0.064 0.03 Amps 0.821 Amps Standby Current Load: 0.03 Amps. For 24. Hours z-- 0.720 Amp -hours Alarm Current Load: 0.821 Amps For 5 Minutes 0.069 Amp -hours 25% Derating= 0.986 Amp -hours Total System Current Load: 0.986 Amp -hours Battery Pair16 beiised I2VDC',-: '':::- 3 1 '-,"*I';'!' = Amp -hours ' ' NotificationApplianceCircuit Detail PROJECT: DAISO Panel: 1, PAD -3 POWER SUPPLY ,Wire Resistance 2.58 Date: August 8, 2011 CURRENT TOTAL= 922.00 @15CD 871 1. ZH-MC-CW ©30CD 131 ZH-MC-CW @75CD 222 . , 2 ZH-MC-CW @95CD 292 @115CD 1 371 0 ZR -MC -CW ©15CD 69 207 'ZR -MC -W @15CD 64 01 DEVICES= 6 175 0 TOTAL mA=1 922 Total Wire Resistance ( R ) Total Device Load, Amps (I) Voltage Drop ( E) EOL Voltage 14 208 23.011 9221 1.071 (TOtal=,CotirLoad) 0.92 1(E= I * R).1 0.991 24. -;Ey 23.01 1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 z 0 U) LLJ Ct LU (/) LU _J LU TO EXISTING SIGNALING CIRCUIT/DEVICE 120VAC, DEDICATED ( BY OTHERS ) SYSTEM CALCULATIONS 2C —c> BPS EX S1-1 S1-2 30cd 15cd (LOCATED AT STORAGE AREA) S1-3 S1-4 15cd 15cd EX TSM AHU TSM S1-5 95cd S1-6 95cd EXISTING DATA LOOP EOL S1 FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110VAC BRANCH CIRCUIT. SMOKE DETECTOR MUST BE LOCATED IN THE SAME ROOM/AREA AS THE PAD -3. DUCT DETECTOR, RELAY MODULE FOR FAN SHUTDOWN & TEST SWITCH LOCATIONS TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. REV. BY: 0 m 0 DESCRIPTION SHOP DRAWINGS DATE ... 0 0 co 0 2 <<<<< ALE: NOT cc 0 0 w z w 0 z z C/) z0 C.) F. - CI) TO SCALE" SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE:08/05/11 BACKROUND PLAN PROVIDED BY: SINGLE LINE DIAGRAM Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved \JOB NUMBER: 55307 SHEET FA -03 ;.* 4011 (r.. (.0 6 AHU EX (HTR -R TSM) EOL S1 S1-6 95cd L A 100 L 0-02) F-02 ) I I i S1-5 95cd r F 1 FIRE ALARM SYSTEM PLAN S1-4 15cd F06 _l-0 Db T77....7 .--771-- -- LST 15c4 [411 EX SIC s,s 1 AG 101 S1-2 " 15cd / c 18 J 103 CN FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110VAC BRANCH CIRCUIT. SMOKE DETECTOR MUST BE LOCATED IN THE SAME ROOM/AREA AS THE PAD -3. DUCT DETECTOR, RELAY MODULE FOR FAN SHUTDOWN & TEST SWITCH LOCATIONS TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. FLOOR PLAN NOTES SYM OL `J O T DISPLAY FIXE,JRES 3ROVIDED BY TENA\ T, TYDICAL CASH WAD 9:0V DEQ BY T-\A\T, TO 31 ADA CONDI_ ANT WITH CC/A\SI A117.1-2003 CI --IATER 9 ATAGRA. 1-1 90 -.3 LI\E OF EXISTING GWS SOF-F- 8'-6" ABOVE FINIS -ED 7L00 Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 02 0 DESCRIPTION SHOP DRAWINGS DATE 08/05/11 co z co r z a. Q wa dCwWz 0. (/) = ,.'c cn cc <go ty. CO Z a w 1-1 >- (0 ccW SCALE: 1/4"=1'0" DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 08/05/ 1 1 BACKROUND PLAN PROVIDED BY: .OB NUMBER: 55307 FA -04 C SHEET 1378 SOUTHCENTER MALL ASSOCIATED PERMITS 15-F-131 11-F-184 15-S-149 11-S-169 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Daiso Japan 1378 Southcenter Mall Permit No.: 15-S-149 Date: September 24, 2015 Reviewer: Al Metzler Fire Protection Project Coordinator (206) 575-4407 option # 2 (Inspection Requests) (206) 971-8718 (Plan Review Questions) • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes iri pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Flexible sprinkler hose bends shall not exceed the maximum radius permitted by the listing. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • All valves controlling the water supply for automatic sprinkler systems and waterflow switches on all sprinkler systems shall be electrically supervised. • All interior control valves shall be readily accessible, labeled and located not more than 6 ft. above the floor. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 20 or more sprinkler heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems in addition to the standard hydrostatic test, an air pressure leakage test at 40 psii shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2013 Edition. 07/26/2011 13:34 4254818695 FAX TRANSMITTAL CROWN FIRE Fax No. CROWN FIRE PROTECTION, INC. EMI Company 7.26.11 Fire Prevention Bureau Tukwila Fire Department / Don Tomaso Demo Permit Number of Pages (Including Cover 17 Urgent ® For Review 1 ❑ Please Comment ❑ Please Reply PAGE 01/01 206575.4439 Jessica Robinson PH:425.481.7669 FX:425.481.8695 Please provide a demo permit to remove (2) sarin, heads that are in the way of a wall that is being removed at the Daiso Japan project . Southcenter Ma . This work is being done in accordance with Cristie' s phone conversation with—A Metzler today. The building permit is D11-191. Please let us know if you have any questions. yt lJS �Cr?°>s Thanks P.O. BOX 12113 MILL CREEK, WA 98082 PH: 425.481.7669 TUKWILA FIRE DEPARTMENT Please call 206-575-4407 and give this Fire Permit No. and exact address for shut- nown or restoration approval. FX: 425. 481.8695 k 7 lz / NOTICE 4 completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and 1)!,: (.1:ion Syst rns. Failur,L! t:..st will result in a Re-insp ction Fee and termination of the testing DA F RE ALA T K IS JAP S TE ILA, `.', ASHII\T N DITIO ON SHEET \UM3E� SH IET TITLE FA -01 SYSTEM FO MATIO\ FA -02 TYPICAL WHI\G A\D MOU\TI G DETAILS FA -03 SYSTEM CALC U LATI O S A\D SI\GLE LI\E DIAGRAM FA -04 FRE ALARM SYSTEM PLA\ SHEET INDEX Without Comments p As Noted in Regi o Per The Attaches Letter The6e plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawing: after this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: S! ?j By: 1 -RA/VILA FIRE DEP SRT 'ri" ' fr`'► se call 206-575- x.07 an give this Fhc Permit mit O. 1, =F- 1 3 I .ind exact a dclg.ss for shut- down or res r oin approval. 3ULE A\D CO\DUIT FILL CHAT WIRE DESIGNATI❑N SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKED D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKED P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V' SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1 2'. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 8. 9. 10 11 12 DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR S'ZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vaC POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 131 ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14 ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15 PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN—UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN—UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE V/ITH NFPA 72 CHAPTER 7. 16 WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17 ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21 ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI—CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY EX 1 1 1 5 1 EX EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT BPS REMOTE BOOSTER POWER SUPPLY EX (EXISTING) PAD -3 SIEMENS PAD-3—ENCL 66" A.F.F. TO TOP ®p DUCT SMOKE DETECTOR AD2—P W/ SIEMENS HFP-11 DET. DUCT HOUSING VERIFY IN FIELD TSM DUCT DETECTOR TEST SWITCH TSM -1 SIEMENS 1—GANG BOX VERIFY IN FIELD HTR -R INTERFACE MODULE WITH RELAY HTRI—R SIEMENS 4S DEEP BOX VERIFY IN FIELD jj FIRE ALARM HORN STROBE ZH—MC—CW SIEMENS 4S DEEP BOX CEILING l FIRE ALARM STROBE ZR—MC—CW SIEMENS 4S DEEP BOX CEILING HTR -R EX INTERFACE MODULE WITH RELAY (EXISTING) HTRI—R SIEMENS 4S DEEP BOX VERIFY IN FIELD ® Ex SMOKE DETECTOR (ADDRESSABLE—PHOTO) (EXISTING) HFP-1 1 SIEMENS EXISTING CEILING A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT N/A REMOVE N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A SYMBOLS LEGEND NORDSTROM 3 LEVELS 171,2.75sf t' IICSSJ r. 5' macys 4 LEVELS 250,407sf DAISO JAPAN 1378 E uu-No e�aenn TNCER 8O 1 ❑ ` ZPsys stop n .RARE ROS cyci:i.nR L1 I_ C1 REGALIA NV LAS n clot g 0 '.0'.'4 5 I-1 I I s AInR SS CAht\t7.V WSTAND 6 SOLE S CES SOLE SIOES IKE CO(X. LIDS •772,,q01_711,_ WIRE DESIGNATION GENERAL NOTES SITE PLAN EXOIINC JCPenney 3 LEWES 276,46Ssf PAID AUG 17 2015 TUKWILAJIRE cc -20 aj -AL z z e• Q 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: DMG DESCRIPTION SHOP DRAWINGS DATE 0 M cO 0 2aaaaa SCALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE DATE: 08/ 13/ 15 BACKROUND PLAN PROVIDED BY: Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved \OB NUMBER:13153-1 J - SHEET Q FA -01 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TUBE OUTLET SAMPLING TUBE INLET SAMPLING DUCK OVER 3' WIDE: SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL 120VAC-60HZ DEDICATED E AERGENCY NOTE FOR ADDITIONAL SPECIRCATIONS SEE PRODUCT DOCIIAMENTA11ON. *CONTACT RATINGS 4.0A 0 125VAC 4.0A 0 30VDC ISOLATE FROM GRl1NDING TO NEXT ADDRESSABLE (+ DEVICE STOP IF LAST DEVICE µ- FROM XLS CONTROL PANEL l OR PREVIOUS ADDRESSABLE DEVICE GROUND - 1] O O 0 HTRI-R 0 ©, 0' O o O NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. C -CABLE C -CABLE 0 EIFJEJ 0000 L PAD -3 oo° NPUT INPUT TROUBLE NACI NAC2 NAC3 NAC4 AUX + 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - S 0 0 0 0 0 -I 3.6k EOL (-) (+) SPARE SPARE SPARE (-) FROM PREVIOUS ADDRESSABLE DEVICE HFP-11 \\\\,\2:2,_ TB1 O 0 10 NO COM NC 2 TO FAN SHUTDOWN EOLR 470 m & 0 SWITCH + - INPUT LED TSM -1 0 00 TO NEXT ADDRESSABLE DEVICE 0 6 /1/1/ 1 2 3 4 5 00 NO 6) COM e HTRI-R KG 0 0 TYPICAL DUCT DETECTOR/HTRI-R MODULE/TSM-1 SWITCH WIRING DETAIL POWER SUPPLY & RELAY MODULE WIRING DETAIL (+) HORN/STROBE OR STROBE ONLY HORN/STROBE OR STROBE ONLY HORN/STROBE OR STROBE ONLY HONR STROBES & STROBES ONLY WIRING DETAIL TYPICAL TO NEXT DEVICE OR END OF LINE WIRING AND MOUNTING DETAILS CEILIN TILE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER T1N TEMPERA RE: +32' F 0' C TO 100' F (3& C) HUMIDITY: -9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR -)' FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE [DATA IN ( ) >— DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPUCATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW (-) > TO NEXT 1 1 ADDRESSABLE (+) SMOKE DETECTOR WIRING DETAIL 1®D 0 0 SUPPORT BRIDGE 4" SQUARE DEEP BOX CEILING /- HORN STROBE / STROBE ONLY DROP CEILING MOUNTING HARD LID CEILING DEVICE SUPPORT BRIDGE 4" SQUARE DEEP BOX CEILING HORN STROBE STROBE ONLY HARD LID MOUNTING HORN STROBE & STROBE CEILING MOUNTING DETAIL JUNCTI❑N BOX MOUNTED ON CEILING FLEX 0WON e':.so'S. e':?:%.mss':::%`S.se':?s%'%so%su%'S::%Smu`'%m':se'S:s%. n JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT TO NEXT DEVICE CADDY BAR SMOKE/HEAT DETECTOR SUSPENDED ILLUMINATED CEILING SMOKE/HEAT DETECTOR MOUNTING DETAIL 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: DMG DESCRIPTION SHOP DRAWINGS DATE I- , 0 co Z r CZ rn 2z a. <WF- < LU _ O (1) Q Cf) CC2 Q O- < co— Wcv; �yr CC r = LL cf (774 w 0 z fCALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE DATE: 08/ 13/ 15 BACKROUND PLAN PROVIDED BY: ,JOB NUMBER:13153-1i ( SHEET FA -02 1 Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved \ SITE LOCATION CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East Tukwila, WA 98188 206-575-4407 Date application accepted: FIRE PROTECTION SYSTEMS PERMIT APPLICATION Applications and plans must be complete in order to be accepted for plan review. **PLEASE PRINT** King Co. Assessor's Tax No.: Site Address: 1378 South Center Mall, Tukwila, WA 98188 suite Number: 920247-0010 Floor: Tenant Name: Daiso Southcenter Mall New Tenant? - Yes 111- No Property Owner's Name: Westfield Property Tax Dept. Mailing Address: same as site address CONTACT PERSON -if there are questions about the submittal. Name: Karina Veliz Day Telephone: 206.349.5889 Company Name: Guardian Security Systems City State Zip Mailing Address: 1743 First Ave South, Seattle, WA 98134 kvelizng y uardiansecurit .com City State Zip E-mail Address: kveliz@guardiansecurity.com Number: 206.374 2852 Total number of new/relocated devices or sprinkler heads: — 1 Valuation of Project (contractor's bid price): $ 5,400. Scope of Work (please provide detailed information): Add 9 devices to existing FACP. PERMIT APPLICATION NOTES Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules. Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILDING,0 NF,tt OR iUTHOIZED AGENT: Signature: Print Name: Karina Veliz Date: `� t Day Telephone: 206.349.5889 Plan Permit App.doc 1/2/13 TFD FP Form 8 Loa us ngs D2 Series ENGINEER AND ARCHITECT SPECIFICATIONS • For Series 11 Detectors • Relay Models Available • Design for AirVelocity Range of 100 to 4000 fpm • Alarm LED Visible From Front Fire Safety • Clear Housing Cover for Quick Identification of Detector Type Removable With Only Four Captive Screws • 0 UL Listed, CSFM Approved, ULC Listed Introduction The Siemens BuildingTechnologies, Fire Safety Division air duct detector housings are designed to be used with the 11 -Series detectors. Designed for installation directly to heating, ventilating and air conditioning duct systems, they comply with National Fire Protection Association Standard No. 90A. When equipped with photoelectric detectors, these units will signal the presence of hazard- ous quantities of products of combustion or smoke being carried through the duct system. Air duct detectors are not intended to be substituted for open area detection. Air duct housings can be equipped with optional relays. These relays are utilized to operate any supplementary equipment when smoke or particles of combustion are detected. Note: Most conventional time control equipment guaran- tee only one detector per zone when the detector oper- ated relay function is critical.The connection of a remote lamp and a remote relay per detector is allowed with PXL or System 3TM only, other conventional systems may use either a remote lamp or a relay. With the MXL series of control panels, up to 60 detectors per circuit having relays may be used.The connection of a remote lamp or a remote relay is allowed for each detector but not both. With the FireFinder XLS series of control panels, up to 252 detectors per circuit having relays may be used. The Connection of an intelligent remote lamp and a remote Relay (ILED), is also allowed. Air duct housings (see Ordering Information) are Under- writers Laboratories, Inc. listed. Description The Fire Safety air duct housing is uniquely designed to use the photoelectric detector. Sensitivity of PE -11 detectors can be checked by viewing the LED or an RSAW-11 or RSAC-11 multicolor remote lamp. A green flash indicates the detector has passed its self test. Amber indicates a trouble condition, and red indicates an alarm state. HFP-11,HFPO-11 and FP -11 sensitivity may be viewed from the multi -color LED on the detector or preferably may be printed by command on an optional printer from the MXL control panel. The detector unit employs a cross-sectional sampling principle of operation. Inlet sampling tubes are available in four lengths (see table on reverse side). Outlet sampling tubes are one common length. A continuous cross- sectional sample of air moving through the duct stratifica- tion or skin effect phenomena occurring in the duct that could prevent combustion product or smoke (especially in large ducts) from reaching a spot type detector. In addition, the unique design of the sampling chamber insures uniform sensitivity in air velocities, ranging from a low of 100 feet per minute to as high as 4000 feet per minute. The housing comes with two' " conduit CATALOG NUMBER 6185 knockouts and one 1/2" conduit opening fora number of 3 wiring entry ports. The inlet sampling tube length is determined by the width of the air duct being protected.The inlet tube nearest to but greater than the duct width should be used (see table).The inlet tube can then be trimmed at the job site to the exact width of the duct.The outlet sampling tube for all ducts, irrespective of width, has a fixed length of approximately 5.5 inches and is supplied with the duct housing. When the use of a remote relay is required, order model AD2-PR for conventional systems; AD2-XHR for address- able systems. When required the WP -2000 weatherproof enclosure for Duct Housing is available. For full details, refer to installation instructions part number315-049708. Sampling Tube Selection Table Duct Width Sampling Tube Model No. For duct widths 6' to 1' ST -10 For duct widths over 1' to 3' ST -25 For duct widths over 3' to 5' (requires support) ST -50 For duct widths over 5' to 10' (requires support) ST -100 Maintenance of the detector is easily accomplished by the removal of the Series 11 duct housing sampling chamber cover.The detector, which plugs into the hous- ing, is easily removed for cleaning by a trained technician. All that is necessary for installation of the air duct detector is the cutting of three small holes for the sampling tube installation (template included) and the drilling of four holes for mounting the air duct housing.The unit is then easily mounted in place and connection made to the existing wires or terminals if optional accessories are utilized. ST -50 and ST -100 require support. ST -100 is shipped in two five foot pieces with a coupling for field assembly. Technical Data Temperature Range Altitude Range Relative Humidity Air DuctVelocity Range SamplingTube Pressure Range of Differences 32°F (0°C) -100°F (38°C) No Altitude Limitations 10-85% (non-condens ing/non-freezing) 100-4000 Ft/Min. Greater than 0.01 amps less than 1.2 inches of water column Note to Architect: When building codes regulate the location of detectors within ventilating systems, make sure that the number and locations of detectors is in accordance with the code regulations. Order Information Model Description Part Number AD2-P Air Duct Housing for use with FP -11, HFP-11, HFPO-11, PE -11 500-649706 AD2-PR Air Duct Housing for use with PE -11 with relay 500-649707 AD2-XHR Air Duct Housing for use with FP -11, HFP-11, HFP0-11, with relay 500-649708 ST -10 Sampling Tube for Ducts 6" to 1' 500-649710 ST -25 Sampling Tube for Ducts over 1' to 3' 500-649711 ST -50 Sampling Tube for Ducts over 3' to 5' 500-649712 ST -100 Sampling Tube for Ducts over 5' to 10' 500-649713 Product Includes One Short Return (outlet)Tube One Stopper Two #12 + 3/4" Sheet Metal Screws MountingTemplate Note: Detector and sampling tube to be purchased separately Note: Minimum hardware required is one Air Duct Housing Assembly, one Sampling Tube and one Detector NOTICE: The use of other than Fire Safety detectors and bases with Fire Safety equipment will be considered a misapplication of Fire Safety equipment and as such voids all warranties either expressed or implied in regard to loss, damage, liabilities and/or service problems Siemens Building Technologies Fire Safety Fire Safety 8 Fernwood Road Florham Park, NJ 07932 Tel: (973) 593-2600 FAX: (973) 593-6670 Website: www.sbt.siemens.com/fis 9/06 5M SFS -IG Printed in U.S.A. Fire Safety 2 Kenview Boulevard Brampton, Ontario Canada L6T 5E4 Tel: (905) 799-9937 FAX: (905) 799-9858 September 2006 Supersedes sheet dated 4/06 F11 FreFrn.1eiTM [I:etect r Fire Safety intelligent Fire Detector for FireFinder XLS and FS -250 Control Panels ENGINEER AND ARCHITECT SPECIFICATIONS Model HFP-11 • Most Sophisticated "Detector Intelligence" available today • Multi -Criteria fire detection for the price of a photoelectric detector • FirePrintT"Technology to discriminate between deceptive phenomena and an actual fire • Easily programmed to match specific hazard profiles from the control panel • Polarity Insensitive with SureWireT'Technology • Pre -Alarm reporting based on fire profile selected • Remote sensitivity measurement capability • System logic activation based on any of three inputs from detector (smoke, heat or neural network) • Detectors are self -testing, completing diagnostics every 4 seconds • Field cleanable chamber with replaceable chambeE parts available • Multi -color detector status LED • Two -wire operation • Compatible Model DPU field device programmer/tester unit • Supports software based automatic environments compensation • Optional fully programmable relay base, audible base, and duct housing • U� ULC Listed, CSFM, FM, NYMEA Approved Introduction The Siemens Building Technologies, Fire Safety Divi- sion HFP-11 Intelligent Fire Detector provides the life safety industry with the most highly evolved detection system available today. The HFP-11 utilizes advanced detection technology that allows the detector to distinguish non -threatening deceptive phenomena, such as cigarette smoke, from actual fire hazards, while optimizing detection for the area in which it is installed. No other detection system available today offers a higher level of protection or nuisance alarm immunity. The HFP-11 uses state-of-the-art micropro- cessor circuitry with error check, detector self -diagnos- tics and supervision programs. The HFP-11 intelligent fire detector is compatible with the Fire Safety Model DPU field device programmer/ tester unit, which is a compact, portable, menu -driven accessory for electronically programming and testing detectors, easily and reliably. The DPU eliminates the need for cumbersome, unreliable mechanical program- ming methods, such as dials or switches and reduces installation and service costs by electronically pro- gramming and testing the detector prior to installation. The HFP-11 fire detector is compatible with the Fire Finder XLS series of control panels. CATALOG NUMBER 1 Description The HFP-11 is a plug-in, two -wire, multi -sensor detector with both photoelectric and thermal inputs and is compat- ible with Fire Finder XLS and FS -250 series of control panel systems. Each detector consists of a dust resis- tant, field -cleanable photoelectric chamber, a solid state non-mechanical thermal sensor, and microprocessor based electronics with a low -profile plastic housing.The HFP-11 utilizes state-of-the-art ASIC circuitry and surface mount technology for maximum reliability. Every HFP-11 fire detector is shipped with a protective dust cover.The HFP-11 fire detector utilizes an infrared light emitting diode (IRLED), and light sensing photodiode. Under normal conditions, light transmitted by the LED is directed away from the photodiode and scattered through the smoke chamber in a controlled pattern.The smoke chamber is designed to manage light dissipation and extraneous reflections from dust particles or other non - smoke airborne contaminants in such a way as to main- tain stable, consistent detector operation. When smoke enters the detector chamber, light emitted from the IRLED is scattered by the smoke particles and is received by the photodiode. The HFP-11 also utilizes a modern, accurate, shock - resistant thermistor to sense temperature changes. The "on -board" FirePrint technology allows the detec- tor to gather smoke and thermal data, and to analyze this information in the detector's "neural network" By comparing data received with the common characteris- tics of fires, or fire fingerprints, the HFP-11 can com- pare these "Fire Prints" to those of deceptive phe- nomena that cause other detectors to false alarm.The advanced FirePrint technology allows the HFP-11 to accurately determine a true fire hazard from a non- threatening deceptive phenomena WITHOUT needing to use alarm delaying verification and confirmation techniques, which can increase the probability of losses due to fire. The HFP-11 provides the highest level of detector intelligence available today with a detector/control panel link that allows the user to program the detector for the specific hazard profile using a simple software menu selection. Detectors are optimized by selecting one of the following eleven applications: • Office/Retail • Lobby • Computer Room • Dormitory • Healthcare • Parking Garage • Utility/Transformer Room • Hostile Environment • Precious Storage • Air Duct • Warehouse/Light Manufacturing The software does the rest; no guessing on detector sensitivities or alarm verification; the control panel programs the HFP-11 detector for the protected area without hassle and without confirmation delays. Once optimized for the hazards in the protected area, the HFP-11 provides the best detection you can buy. Should the operator or installer forget to program the detector, the HFP-11 will revert to a default setting that allows it to operate as an office environment detector. The HFP-11's FirePrint technology monitors input from both the photo chamber and the thermal sensor, evaluating this information with sophisticated math- ematical formulas, or algorithms, comparing this input to characteristics of both threatening fires and decep- tive phenomena that would "fool" any ordinary detec- tor. This technology was developed over years of research and reviewing the results of over 20 years of fire test data in one of the world's most advanced fire research centers. The results of this research are the mathematical models that form the algorithms used in FirePrint. No other fire detector has this level of intelligence or this amount of research and development supporting it's design. The microprocessor's software can identify and disregard false input caused by radio frequency (RFI) and electromagnetic (EMI) interference, and validates all trouble conditions before annunciating or reporting to the control panel.The HFP-11 detector's microprocessor uses an integral EEPROM to store the detector's address and other critical operating param- eters which include the assigned program values for alarm and trouble thresholds. Communications within the detector itself and be- tween the HFP-11 and the control panel, or with the DPU field device programmer/tester unit, are super- vised and safe -guarded against disruption by reliable, microprocessor based error checking routines. Addi- tionally, the micro -processor supervises all EEPROM memory locations and provides a high degree of EEPROM failure fault tolerance. The HFP-11 determines its operating status to be normal, in alarm, or in trouble depending on the difference between the alarm threshold values stored in the detector's memory and the detector's latest analog measurement. The detector then communicates changes in its status to the control panel. In addition, the FireFinder XLS control pariel will sample the value of the HFP-11's analog signal over a period of time in order to determine if those values indicate excessive buildup in the photo chamber; if so, the FireFinder XLS control panel will indicate that the particular detector requires maintenance. The HFP-11 is listed as a self -testing device.The HFP-11's visible light emitting diode (LED) flashes green every 4 seconds to indicate it is communicating with the control panel and that it has passed its internal self -test. Should the detector sense a fault or failure within its systems, the LED will flash amber and the detector will transmit that information to the control panel. A quick visual inspection is sufficient to indicate the condition of the detector at any time. If more detailed information is required, a printed report can be provided from the Fire Finder XLS panel indicating the status and settings assigned to each individual detector. When the HFP-11 moves to the alarm mode, it will flash red and to continue flashing until the system is reset at the control panel. At that same time, any user defined system alarm functions programmed into the system are activated. Detector sensitivity, calibration, and identification are dynamically supervised by the control panel. Detector sensitivity and pre -alarm levels are a function of the application chosen at the control panel and are controlled by the panel. If an alternate, non-FirePrint mode is selected, then the sensitivity can be changed from the control panel. The DPU Device Program/Test Unit accessory is used to program and verify the detector's address. The technician selects the accessory's program mode to enter the desired address. The DPU automatically sets and verifies the address and tests the detector. The DPU operates on AC power or rechargeable batteries, providing flexibility and convenience in programming and testing equipment almost anywhere. When in the test mode, the DPU will perform a series of diagnostic tests without altering the address or other stored data, allowing technicians to determine if the detector is operating properly. The HFP-11 fire detector may be installed on the same initiating circuit with HMS series manual stations, HTRI series interfaces, HCP output control devices, or HZM series of addressable, conventional zone modules. All HFP-11 detectors can be cleaned in the field, when required, by simply removing the detector cover and unsnapping the photo chamber. There is also the option of cleaning the interior of the detector with a clean, soft cloth or brush, or replacing the labyrinth and bug screen included in the detector maintenance kit, model DMK-11. The HFP-11 uses the low -profile surface mounting base, model DB -11. This base mounts on a 4 -inch octagon, square, or a single gang electrical box. The base utilizes screw clamp contacts for electrical connections and self -wiping contacts for increased reliability. The base can be used with the optional LK -11 detector locking kit which contains 50 detector locks and an installation tool, to prevent unauthorized - removal of the detector head.The DB -11 base has integral decorative plugs to cover the outer mounting screw holes. All HFP-11 detectors are approved for operation within the UL specified temperature range of 32 to 100 degrees F (0 to 38 degrees C). Application Data Installation of the HFP-11 series of fire detectors requires a two -wire circuit. In many retrofit cases, existing wiring may be used. "T -tapping" is permitted only for Style 4 (Class B) wiring. The HFP-11 is polarity insensitive. This feature can greatly reduce installation an debugging time. HFP-11 fire detectors can be applied within the maximum 30 foot center spacing (900 sq. ft. areas) as referenced in NFPA 72. This applications guideline is based on ideal conditions, specifically, smooth ceiling surfaces, minimal air movement, and no physical obstructions between potential fire sources and the detector. Do not mount detectors in close proximity to ventilation or heating and air conditioning outlets. Exposed joints or beamed ceilings may also affect safe spacing limitations for detectors. Should questions arise regarding detector placement, observe NFPA 72 guidelines. Good fire protection system engineering and common sense dictate how and when fire detectors are installed and used. Contact your local Fire Safety distributor or sales office whenever you need assistance applying FirePrint in unusual applications. Be sure to follow NFPA guidelines and ULJULC approved installation instructions, which are included with every Fire Safety detector, and local codes as for all fire protection equipment. Dimensions T 23. Overall Height 1 6" Diameter Base , 1._.x`7 11111411W law Technical Specifications Operating Temperature: +32°F (0°C) to 100°F (38°C) per UL 268/268A Humidity: Maximum spacing: 0-93% Relative Humidity Non -Condensing 30 foot centers (900 sq. ft.) per NFPA 72 Chapter 5 and CAN/ULC-S524 Model Detetiptian Part Number HFP-11 dyddres satiw FirePrirn Fre De:ecmr 511C0 -113:M. DB -11 DiInnIrr Memtesing Bit lfit S@;ttNi j1 RIC -1194.151 DB -11E DtctcIlur El lstr illi Y 51D UB+1151E AD -11P Air DtAzit Housing ler Surras 11 SDrr11BRU AD-Hz1 fin Du. --1 Housing w Relay' ler H=Series IniediDent ['howl 5'16-U i14U D6•HA Rcld BaSu fur 11,- Scrum It=tclllittut. Dutucin s 50CU3322D ADl3H=11 Audible bass, 5D61133Z11U RLI`#C Remota 'reit alarm indrAto 4' n .. on b >< mourn 5DU-413323 RUTIN Remote 'red" aarm indt • sir41n Rang bux mourn 511D-U3a3UU LK -11 Base. Lucking rt. MT Series 11 detectors mile- 5 DLIK-11 Series 11 Mair. Kb 'replacement labyrinth aryl hug lxig scree} SDC -B 15a^'t.2 In Canada Onion. EHFP-11C itiAtiressa&ie FirePrin1Fire Detectnr1L(LC) SDCD95112C DB -11C Detests; Mourning. SDC41951.7 AD-11PC lir. DtntHousina(L1tC} 50C4159414 DB -HRC Relay Base tnr Series 11 Imelligent Detectors ft1LCI 51C11'f1' PC ADBi1-11 C kidihle Base for Series 11 (it_enr Detector (11LCI 511D-11n2In{: NOTICE: The use of other than Fire Safety detectors and bases with Fire Safety equipment will be considered a misapplication of Fire Safety equipment and as such void all warranties either expressed or implied with regard to loss, damage, liabilities and/or service problems. Siemens Building Technologies Fire Safety Fire Safety Fire Safety 8 Fernwood Road 2 Kenview Boulevard Florham Park, NJ 07932 10/05 Brampton, Ontario Tel. (973) 593-2600 5M Canada L6T 5E4 FAX: (973) 593-6670 SFS -IG Tel: (905) 799-9937 Website: www.sbt.siemens.com/fis Printed to U.S.A. FAX. (905) 799-9858 October2005 Supersedes sheet dated 7/03 Duct Detector Test Switch ENGINEER AND ARCHITECT SPECIFICATIONS • T45 Key Operated • LED Indicates Detector in Alarm • Mounts in Single Gang Box • Compatible with All Siemens Building Technologies, Fire Safety Division Intelligent Duct Detectors • ®UL Listed Fire Safety Description The TSM -1, Test Switch Module is a key activated device that will functionally test a detector. The module is compatible with Siemens Fire Safety intelligent fire, smoke and duct detectors used on MXL, MXLV and MXL-IQ systems. The TSM -1 includes a red LED that illuminates when the corresponding duct detector is in alarm. The switch operates in conjunction with a TRI -R Interface Module with relay. Either that relay or the relay in the duct detector can be used for control of building equipment such as HVAC fans and elevators. The TSM -1 mounts in a single gang electrical box and includes a red cover plate. When the switch is operated a signal is transmitted to the appropriate detector forcing it to alarm. That alarm will activate all functions programmed to follow that detector. The TSM -1 therefore provides a true functional test of the actions associated with duct detectors on MXL systems as require by many jurisdictions. Underwriters' Laboratories, Inc has listed the TSM -1 as compatible with MXL intelligent detectors. Ordering information Model Description Part Number TSM -i Detector Test Switch 5OG-696353 Refer to Installation Instructions, P/N 315-098285 CATALOG NUMBER 6196 TSM -1 Interface to MXL System TSM -1 LED operated by the TRI -R relay contacts. From MXL + ALD Loop End of Line Device for TRI -R 3.6K, 1/4W, P/N 140-820185 0 1 0 2 P"I 0 000 Switch + – Input LED TSM -1 03 0 4 Earth Ground5 TRI -R 81-0 710 J} 1 To Air Duct Detector or next device on loop } 24 VDC From MMB -2, TB5 Terminals 9-12 or PSR -1, TB3 Terminals 3-6 or UL Listed Power Supply Notes: 1. For use only with Air Ducts with an incorporated relay. 2. Refer to the TRI Installation Instructions, P/N 315-096242, for specific interface module wiring requirements. 3. Refer to the AD -11P AD-11XPR Installation Instructions, P/N 315-095659, or the AD-31/-3ILP Installation Instructions, P/N 315-093234, for specific duct detector wiring requirements, as applicable. TSM -1 Interface to MXL System TSM -1 LED operated by the Air Duct Detector. From MXL + ALD Loop End of Line Device for TRI -R 3.6K, 1/4W, P/N 140-820185 1To Air Duct Detector or next device on loop 000 Switch + – lnput LED TSM -1 01 02 03 04 Earth Ground 5 TRI -R To Fan Shutdown Control To Air Duct Detector (See Detector installation Instruction for Remote Alarm Indicator Connection) Notes: 1. For use only with Air Ducts without an incorporated relay. 2. Refer to the TRI Installation Instructions, P/N 315-096242, for specific interface module wiring requirements. 3 Refer to the AD -11P Installation Instructions, P/N 315-095659, or the AD-31/-3ILP Installation Instructions, P/N 315-093234, for specific duct detector wiring requirements, as applicable. Mounting Diagram Caution: The TSM -1 switch module does not perform al of the required smoke detector test as specified in NFPA Standard 72. Please refer to the instructions that accompany the detector for the complete test requirements. Single Gang Mounting Box (User Supplied) Keyswitch Mating Plug TSM -1 Assembly LED Connector + — 11 00 JP1 (Piot Used) Siemens Building Technologies Fire Safety Fire Safety Fire Safety 8 Femwood Road 2 Kenview Boulevard Florham Park, NJ 07932 7/03 Brampton, Ontario Tel: (973) 593-2600 5M Canada L6T 5E4 FAX: (973) 593-6670 SFS -IG Tel: (905) 799-9937 Website: www.sbt.siemens.com/fis Printed in U.S.A. FAX: (905) 799-9858 July 2003 Supersedes sheet dated 2/02 SE Sa E T' I Seri's Fire Safety FireFinder XLS and FS -250 Intelligent Initiating Devices Interface Modules ENGINEER AND ARCHITECT SPECIFICATIONS Intelligent Interface Modules for FireFinder XLS and FS -250 Fire Alarm Control Panels HTRI-S, HTRI-D, HTRI-R • Interfaces and Supervises Normally Open or Normally Closed Contacts • Integral SPDT Relay (up to 4 amps) on HTRI-R Model • Dual Input on HTRI-D Model using a single address • Polarity Insensitive with SureWire'"' Technology • Multi -color L.E.D. indicates status (green, amber, red) • Easy front access to programming port and wiring terminals • Mounts 4 inch square 2 1/4 deep box, or double gang box • Dynamic Supervision • Comes with 5x5 inch faceplate • Two wire operation • DPU Device Program/Test Unit programs and Verifies Device's Address and Tests Devices functionality • Electronic Address Programming is Easy and Dependable • U� 0 ULC Listed CFSM, FM, NYMEAApproved Series Introduction The HTRI Series Intelligent interface modules are de- signed to provide the means of interfacing direct shorting devices to the FireFinder XLS and FS -250 Fire Alarm Control Panel loop circuit. The HTRI Series Intelligent interface modules provide the market's most advanced method of address programming and supervision, combined with sophisticated control panel communication. Each HTRI Series interface module incorporates a microcomputer chip. The HTRI Series microcomputer chip technology and its sophisticated bi-directional communication capabilities with the control panel, achieve the state of an "Intelligence Device" Description The HTRI Series intelligent interface modules are available in three models. The HTRI-S and HTRI-R are designed to monitor a normally open or closed dry contact. The interface module reports the contact's status to the control panel. The HTRI-S model can only monitor and report the status of the contact, while the HTRI-R incorporates an addressable Form C relay. The HTRI-R relay and contact device input are controlled at the same address. For the control panel system, the relay and input contact can be controlled as a separate function. The relay is typically used where control or shunting of external equipment is required. The HTRI-D is a dual input module and is designed to supervise and monitor two sets of dry contacts. The Dual Input Module only requires one address but re- sponds independently to each input. The HTRI-D is ideal for monitoring a water flow switch and its respective valve tamper switch. The HTRI has a multi -color Light Emitting Diode that flashes green when operating normally, amber if unit is in trouble condition, and red to indicate a change of state. The HTRI-D flashes twice, once for each ad- dress, the HTRI-R red L.E.D. indicates a change of state in the relay. CATALOG NUMBER 6304 The device's microcomputer chip has the capacity of storing, in memory, identification information as well as important operating status information. Siemens Building Technologies, Inc., Fire Safety Division innovative technology allows all HTRI Series intelligent interface modules to be programmed by using the DPU Device Programming/Test Unit. The DPU is a compact, portable, menu driven accessory that makes program- ming and testing an interface device faster, easier and more dependable than previous methods. The DPU eliminates the need for mechanical addressing mecha- nisms, such as program jumpers, DIP switches or rotary dials, because the DPU electronically sets the HTRI interface's address into the interface's microcomputer chip nonvolatile memory. Vibration, corrosion and other conditions that deteriorate mechanical addressing mecha- nisms are no longera cause for concern. The HTRI Series is fitted with screw terminals for connection to an addressable circuit. The HTRI Series is fully compatible on the same FireFinderXLS and FS -250 circuits with all intelligent H Series detectors, HMS Series addressable manual stations or any other addressable intelligent modules, such as the HZM or HCP. All HTRI Series intelligent interface modules are UL listed. Environmental operating conditions for all HTRI Series modules are 32°F (°C) to 120°F (49°C) with a relative humidity of not greater than 93% non-condensating. Ordering Information Model Description Shipping Wt. Lh. Kg. Part Number HTRI-S Single Input 7 oz. 2 500-033370 HTRI-R Single Input w/Relay 7 oz. 2 500-033300 HTRI-D Dual input 7 oz. 2 500-033360 NOTICE. The use of other than Fire Safety detectors and bases with Fire Safety equipment will be considered a misapplication of Fire Safety equipment and as such void all warranties either expressed or implied with regard to loss, damage, liabilities and/or service problems. Siemens Building Technologies Fire Safety Mounting Data Addressable Interface Model HTRI-S, HTRI-D, HTRI-R mounts directly into a 4 inch square 21/4 deep box or a double gang box (user supplied). A 5 inch square off-white faceplate is included with each HTRI. MOUNTING SLOTS FOR 4 INCH SWITCHBOX MOUNTING SLOTS FOR DOUBLEGANG SWITCHBOX Figure A Mounting the HTRI-S/-D/-R Electrical Ratings Current Draw (Active or Standby): 1 mA HTRI-R Relay Ratings Resistive: 4A, 125 VAC 4A, 30 VDC Inductive: 3.5A, 120 VAC (0.6P.F.) 3.0A, 30 VDC (0.6P.F.) 2.0A, 120 VAC (0.4P.F.) 2.0A, 120 VAC (0.35P.F.) 2.0A, 30 VDC (0.35P.F.) Fire Safety 8 Fernwood Road Florham Park, NJ 07932 Tel: (973) 593-2600 FAX: (973) 593-6670 Website: www.sbt.siemens.com/fis 12/04 5M SFS -IG Printed in U.S.A. Fire Safety 2 Kenview Boulevard Brampton, Ontario Canada L6T 5E4 Tel: (905) 799-9937 FAX: (905) 799-9858 HTRI-S/-D/41 MODULE MOUNTING HOLES FOR SWITCHPLATE December 2004 Supersedes sheet dated 1/03 SIE ENS Catalog Sheet Fire Safety & Security Products 8 Series Notffic.ton ZH & ZR - Strobes, Horns, Horn / Strobes Series ZH r Series ZR p 1 ces Application: Indoor ZR AND ZH Mounting Product Overview Strobes can be synchronized using the Siemens DSC sync modules, FS -250 panel, XLS panel, or PAD -3 power supply with built-in sync protocol Selectable Continuous Horn or Temporal (Code -3) Tones with 90 or 95 dBA selectable setting (ZH) Ceiling -mount models feature field -selectable Candela settings of 15130175195cd and 115/177cd Wall -mount models feature field -selectable Candela settings of 15130175/110cd and 135/185cd Base plate is protected by a disposable cover, one the appliances can quickly snap onto the base after the walls are painted Strobes produce 1 flash per second "Special Applications" listed with Siemens panels EZ Mount Universal Mounting Plate (ZBB) — uses single plate for ceiling and wall mount installations EZ Mount design — with separate base plate — provides ability to pre -wire the base and test the circuit wiring before the walls are covered 0 UL Listed & ULC Listed; FM, CSFM & NYMEA Approved ADA/NFPA compliant Specifications • General - AudibleNisual notification appliances shall be listed for indoor use only - Appliances shall be listed under O UL Standard 1971 (Standard for Safety Signaling Devices for Hearing Impaired) and ® UL Standard 464 (Fire Protective Signaling) Appliances shall use a universal back plate, which shall allow mounting to a single -gang, double -gang, 4 -inch -square, 4" -octal, or a 3 -112" -octal backbox Two -wire appliance wiring shall be capable of directly connecting to the mounting back plate — Continuity check shall occur for entire NAC circuit prior to attaching any audible / visual -notification appliances Dust cover shall fit and protect the mounting plate — Dust cover shall be easily removed when the appliance is installed over the back plate Removal of an appliance shall result in a trouble condition by the Fire Alarm Control Panel (FACP) '08 Series Notification Appliances 2584 Building Technologies Fire Safety & Security Products Specifications — (continued) • Strobes — Strobe appliances shall produce a minimum flash rate of 60 flashes per minute (1 flash per second) over the Regulated Input Voltage Range, and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens — Strobes shall be available with two or four field -selectable settings in one unit, and shall be rated — per 0UL1971 —for up to: • 15130175111 0cd for wall mounted • 135/185cd for wall mounted • 15/30175/95cd for ceiling mounted • 115/177cd for ceiling mounted — Strobes shall operate over an extended temperature range of 32°F to 120°F (0°C to 49°C), and be listed for maximum humidity of 95% RH — Strobe inputs shall be polarized for compatibility with standard reverse -polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP) • Audibles and Audible / Strobe Combinations — Horns and horn I strobes shall be listed for Indoor use under ® UL Standard 464 — Horns shall be able to produce continuous synchronized output or a temporal code -3 synchronized output — Horns shall have at least 2 sound -level settings of 90 and 95 dBA • Synchronization Modules — The strobe portion, when synchronization is required, shall be compatible with DSC sync modules, FS -250 panel, XLS panel, or PAD -3 power supply with built-in sync protocol — The strobes shall not drift out of synchronization at any time during operation — Audibles and strobes shall be able to synchronize on a 2 -wire circuit with the capability to silence the audible, if required — Strobes shall revert to a non -synchronized flash -rate, if the sync module or Power Supply should fail to operate (i.e. — contacts remain closed) — All notification appliances shall be listed for Special Applications: ■ Strobes are designed to flash at 1 -flash -per -second minimum over their "Regulated Input Voltage Range" Note: NFPA-72 specifies a flash rate of 1 -to -2 flashes per second, and ADA Guidelines specify a flash rate of 1 -to -3 flashes per second ■ All candela ratings represent minimum -effective Strobe intensity, based on ® UL Standard 1971 ■ Series ZH Strobe products are listed under ® UL Standards 1971 and 464 for indoor use with a temperature range of 32°F to 120°F (0°C to 49°C) and maximum humidity of 93% (± 2%) ■ Series ZH horns are listed under O UL Standard 464 for audible signal appliances (Indoor use only) Building Technologies Fire Safety & Security Products Mounting Diagram Mounting Options ::r atanrm,....*1 ANDa-A .S;E:1.11C110N ‘C...4t4DE-LA P0114 pAtIDE.L.4. EECTQr AN.. -LA ONTEP fatc-c CANDELAPk id MC CANDELAPONT-2. 1111.1111Mill MC CANDELA POINTER Technical Data Model • Voltage Range (Special Application) Per UL 1971 (VDC/VRMS) i. JUIS 3.• 254 Horn Current Draw See Table Mounting ZR -MC 16-33 15/30[75/110 - 3 Wall ZR -I -IMC 16-33 1351165 - 3 Wall ZR -MC -C 16-33 15/30175/95 - 3 Ceiling ZR -HMC -C 16-33 1151177 - 3 Ceiling ZH-MC 16-33 15130175/110 X 4 Wall . 16-33 . X 4 Wall ZH-MC-C 16-33 15/3075195 X 4 . ZH-HMC-C 16-33 115/177 X 4 ,... ZH 16-33 - ir- 5 Wall or Ceiling in iii r + tl-' ti. ,, ... , Mounting Options ::r atanrm,....*1 ANDa-A .S;E:1.11C110N ‘C...4t4DE-LA P0114 pAtIDE.L.4. EECTQr AN.. -LA ONTEP fatc-c CANDELAPk id MC CANDELAPONT-2. 1111.1111Mill MC CANDELA POINTER Technical Data Model • Voltage Range (Special Application) Per UL 1971 (VDC/VRMS) Strobe (cd) Horn Current Draw See Table Mounting ZR -MC 16-33 15/30[75/110 - 3 Wall ZR -I -IMC 16-33 1351165 - 3 Wall ZR -MC -C 16-33 15/30175/95 - 3 Ceiling ZR -HMC -C 16-33 1151177 - 3 Ceiling ZH-MC 16-33 15130175/110 X 4 Wall ZH-HMC 16-33 135/185 X 4 Wall ZH-MC-C 16-33 15/3075195 X 4 Ceiling ZH-HMC-C 16-33 115/177 X 4 Ceiling ZH 16-33 - X 5 Wall or Ceiling • Available in red and white Building Technologies Fire Safety & Security Products Technical Data - (continued) Table 2: 11 and Zti-MC Flom Reverberant Strobe Setting (cd) ZH-MC and ZH at 24V dBA per UL464 16.0V 24V 33.0V Continuous Hom High 83 87 90 Low 77 81 83 Code 3 Hom or *March Time High 79 82 86 Low 72 76 79 *Available in sync mode only Table 3: ZR Strobe Current Draw (Amps) 116-33 Volts Table 5: ZH Horn Current Draw (Amps) Horn Senting 16-33 Volts DC High* 0.044 Low* 0.016 FWR High* 0.075 Low' 0.045 0dLTalt D;ae the scone forthe Continuous Ham, Coe 3 I koea and Mardi -funs Sec ings Table 4: ZH HomrStrote Current Draw (Amps) at 16-33 Volts Strobe Setting (cd) MC HMC MC -C HMC -C 15 30 75 110 135 185 15 30 75 95 115 177 DC 0.064 0.098 0.175 0.233 0_318 0.445 0.069 0.111 0.290 0.264 0.318 0.445 FAR 0.108 0.164 0.266 0.368 0.482 0.664 0.117 0.180 0.297 0.398 0.482 0.684 Table 4: ZH HomrStrote Current Draw (Amps) at 16-33 Volts * Current Draw is the sarne for the Continuous Hom, Cade 3 Hom and March lime Settings Details for Ordering / Mounting Requirements / Approvals Model Number Order Code Strobe Setting (cd. Horn Setting MC HMC MC -C HMC -C 15 30 75 11D 135 165 15 30 75 95 115 177 DC High* 0.078 0-113 0.195 0.259 0.371 0.506 0.037 0.131 0 0.292 0.371 0.506 Low* 0.074 0.107 0.166 0.246 0.324 0.455 0.075 0.121 0213 0277 0.324 0.455 ,R High' 0.141 0.200 0.302 0.406 0.521 0.722 0.149 0.216 0.331 0.436 0.521 0.722 Low' 0.123 0179 0290 0.391 0.497 0.699 0.131 0.195 0.319 0.421 0.497 0.699 * Current Draw is the sarne for the Continuous Hom, Cade 3 Hom and March lime Settings Details for Ordering / Mounting Requirements / Approvals Model Number Order Code Rtounting Options Agency Approvals UL ULC CSFH FM ZH-MC-R 560-638.,6181 3, 0, E, F XX X X ZH 4AC-W 500-355162 6, 0, E. F XX X X ZH-HMC- 500-538163 6, 0, E. F X X X X ZH-HMC-W 500-636164 3, 0, E, F XX X X ZH-n^, 500-3158 5, 0, E, F XX X X ZH-W 500-160 5, 0, E, F X X X X ZH-MC-CR 500.3135185 6, 0, E, F XX X X ZH-MC-CW 500-105 5, 0, E, F XX X X ZH-HMC-CR 500-W55187 6, t}, E. F XX X X ZH-HMC-CW 500-635183 5,0,5, F X X X X ZR -MC -R 500-W3159 6, 0, E, F XX X X ZR -MC -W 500-0.8170 6, 0.5, F XX X X ZR -HMC -R 00-65171 6, 0, E, F XX X X ZR -HMC -W 500-172 £, 0, E, F XX X X ZR -MC -CW 500-W8174 8174 3, D. E. F X X X X ZR- 1C -C3 500-W5173 6, 9, E. F XX X X ZR -HMC -CR 5005175 6, 0, E. F XX X X ZRS-HMC-CW 500-W88176 5, 0, E. F XX X X ZBB-R 500-836183 A)essory- Includes btee, d1St 001/F-‘7,. mounting screws and "€ 3Ita o sheet 265-W 500-835184 Axeosory - Includes base, dust cover, mounting sc,-ews and 1 atbri sheet = Refer -to Data Sheet #2585 For axavnvng options X = iistedlapprov Notice: This marketing catalog sheet is not intended to be used for system design or installation purposes. For the most up-to-date information, refer to each product's installation instructions. Building Technologies Fire Safety & Security Products Fire Safety 8 Femwood Road Florham Park, NJ 07932 Tel: (973) 593-2600 SFS FAX: (973) 593-6670 Printed in U.S.A. URL: www.SBT.Sremens.com/FIS Fire Safety 2185 Derry Road West Mississauga, Ontario L5N 7A6 Canada Tel: (905) 799-9937 FAX: (905) 799-9858 December 2008 Supersedes sheet dated 7/07 • ' 1 i,--- 0, 0 = , , ., A,t= tte,f== igi:t,':fi? ,1, 'A ',ii -4; = = ,tt= 4,, ,- t.= . --ti 1'M:44V 40' 0' t '.d' t4 NW gr ' love A k SHOP DRAWINGS DATE Current Load: Standby: tA My,kAtr' A „Ir, Alarm: '.- 14) Device Type Qty Amps Total Amps Total Total HFP-11 1 0.0022 0.0022 0.0023 0.002 Main System Board AD2-P 1 0.0635 0.0635 0.064 0.064 ZI4MCCWCD , 11 ' HTR -R. 1 0.009600 1 0.0096 0.021 0.021 4 1 0.131 ..mc 75CD ' 8 - 0,222 ZH-MC-CW ©95CD 1 . 1 0.292 0.292 -H C -C 15CD. '' , 0.0731 Amps 0.085 Amps • ' 0 M 0 '.d' t4 NW gr ' love A k SHOP DRAWINGS DATE LO tA My,kAtr' A „Ir, '.- 14) z-• Device Type Qty Amps Total Amps Total 0 Main System Board 1 0.03 0.03 0.030 0.030 ZI4MCCWCD , 11 ' 0.0875 ZJ1-[Mc-CW ©30CD 4 1 0.131 ..mc 75CD ' 8 - 0,222 ZH-MC-CW ©95CD 1 1 0.292 0.292 -H C -C 15CD. '' , 0.371 ZR -MC -CW ©15CD 8 0.069 0.552 ZR -MC -W ©15CD 0.064 0O3 Amps . 0.874 Amps Standby Current Load: 0.03 Amps , - F�r 24. Hours = '0.720 Amp -hours Alarm Current Load: 0874 Amps For 5Minutes 0.073 Amp -hours 25% Derating= 0.992 Amp -hours Total System Current Load: 0.992 Amp -hours ' ' ' ' '' -,, ' ' :,,,,,,,,,,,,,,03',,e,'.M;;. ,1:, < , , i . ',' ,,i,,,;,.,,<,:,.,,:.!1,.:,t`4,:,,3 ' '"'-' '''' ' -, '" 4: ,,;.; ,,,,'.;;t,P,11,bla 4 '0,„4'';',0: A -,:,,,':i:`,5 ,,,,,T, -,- L.,,, --,-. ,, ":'AfiV;•::- ' ; '-,1';,,.' , , Notification A PROJECT: DAISO - JAPAN Panel: EXISTING PAD -3 POWER SUPPLY Date: August 13, 2015 «e, pliance Circuit Detail vv,Z17V r Wire Resistance 2.58 CURRENT TOTAL= 1044.00 ,...;,, ,..... i .. — ZH-MC-CW ©156-13i 87 87 ZR -Mo -CW ©30CD 131 0 4 ZH-MC-CW ©75CD 222 888 21-1-MC,CW ©95CD 292 0 -cw @i6co , 6 9 ZR -MC — J ' 3711 ZH-MC-CW ©115CD 0 ZR -MC -W ©15CD ' 64 01 DEVICES= 6 175 0 TOTAL mA= 1044 14 'Total Wire Resistance ( R ) Total Device Load, Amps (I) yoltage Drop ( E ) EOL Voltage 3 143 I 2323 1044 L*2 )*(Rift) 0 7 (Total Cct Load) 1",04 0.77 043 SYSTEM CALCULATIONS 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS TO EXISTING SIGNALING ( CIRCUIT/DEVICE 0 120VAC, DEDICATED ( BY OTHERS ) 2C—cp. cD—S • Ps EX ) EXISTING NAC CKT S1 ) EXISTING NAC CKT S2 S3-1 15cd (LOCATED AT TORAGE AREA 102) S3-2 S3-3 S3-4 S3-5 75cd 15cd 75cd 15cd TO OTHER DEVICES SINGLE LINE DIAGRAM S3-6 15cd EOL S1 FLAG NOTES: EXISTING RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. EXISTING SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110VAC BRANCH CIRCUIT. DUCT DETECTOR, RELAY MODULE FOR FAN SHUTDOWN & TEST SWITCH LOCATIONS TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. IREV. BY: 0 M 0 DESCRIPTION SHOP DRAWINGS DATE LO '.- 14) z-• C) 0 2 <<<<< Zco c 0 Jj 07) < a cco eL <LLJI- • 2 I—05 z z Liu O CD M(.:C) < C5)) 0 < co > w cc cf) D LL cc 0 0 w z —J w — J 0 z (75 0 z (/) z0 0 1.1.1 CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE DATE:08/13/15 BACKROUND PLAN PROVIDED BY: \1_013 NUMBER:13153- 1} SHEET Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved FA -03 • VX/ :......... l ...EOL S3 S3-6 75cd 'D cio'-a" V.I.F. // // / // / / : ,/ / REF. E1 . T AIL SAL..I.W SLOOK S3 5 75 d IT W�. _ _._ _ _. a _. is tj7 / i/// / /// f/ S3-4 75cd ®D HTR -R (.......103.._..�XISTIF\ WAR C 0 0 M 15cd D TSM l�� S3-2 75cd S 10RACE.. i 102 S3-3 15cd EX 4 D R EX EX CO MOR ......._104.......1 / ///// , / .-/ /fff/ FIRE ALARM SYSTEM PLAN 1 D TO OTHER DEVICES FLAG NOTES: EXISTING RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. EXISTING SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 11 OVAC BRANCH CIRCUIT. DUCT DETECTOR, RELAY MODULE FOR FAN SHUTDOWN & TEST SWITCH LOCATIONS TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 m D fl DESCRIPTION SHOP DRAWINGS 11 is tj7 / i/// / /// f/ S3-4 75cd ®D HTR -R (.......103.._..�XISTIF\ WAR C 0 0 M 15cd D TSM l�� S3-2 75cd S 10RACE.. i 102 S3-3 15cd EX 4 D R EX EX CO MOR ......._104.......1 / ///// , / .-/ /fff/ FIRE ALARM SYSTEM PLAN 1 D TO OTHER DEVICES FLAG NOTES: EXISTING RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. EXISTING SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 11 OVAC BRANCH CIRCUIT. DUCT DETECTOR, RELAY MODULE FOR FAN SHUTDOWN & TEST SWITCH LOCATIONS TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 m D DESCRIPTION SHOP DRAWINGS DATE Z M co 0 W �CALE: 1/4"=1'0" DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE DATE: 08/13/15 BACKROUND PLAN PROVIDED BY: .OB NUMBER: 13153-1} SHEET FA -04 Ec) TUKWILA FIRE DEPARTMENT 116 w. call 206-575-4407 and g ve tls Fire Permit No. rtnd erect ^d , ss ?or shut- c: ,uvn or° R.T.IforAion approval. RETAINER STRAP WHERE REQUIRED IN SEISHIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD ROD PIPE SWIVEL RItdG • STEEL JOIST/TRUSS HANGER DETAIL NTS 8'- •" 67' -II". 13'70" 4'-0" 4'-0" . 7'-O" /may` ��//' /{'' C/LLLG'LLL_LLL,4 ,' :' �' .' //' / /LL, .FL/L/LLLLGL LCLf`L/�LGC=' //LL/_✓ZLZ:_ '''''',2//22,./.,,Z/W42/71//p// / ,//////„/% ;X/ //4/<2Z4 .Z.L /./ZL ,/ / ;% / / r /' LZL' ` / /., /;; ° // //' //' ALL L �� L�LL � /��LL / % /' ' � , / /.// / ��L=fL'1ZL_ //: !• ,ice' ,/ Li�L�L• LLGf`LLL j/LLG• L�jLLL'�LLLL LL��L ,-' LLL/LLL/� LG��LL-/ c � .; • �• GN -0; •3 4 . xy .. _ All. o •I • • 4 • //11 �r. 0 0 '• !i" 3r �, �l ::.' ;x »» 4 +21'-0". ' •. 0 RGN-O r `o� ; OPEN TO ... 1 I r �' "' ( y STRUCTURE °"f ABOVE _ GN -O -GN-O• F& 4 10 b'-3" 31-1" TYP. a®r` 0 .. .... . . r- Mi.v r. tii."tt L.. + _ \'ti. 111111� pit . . _— - �. • 77 '77% '//7., i / /,, /7///�/��// / 1/' ''//•%.j .,- / / 7. // y/ / /.� ,'7&/7/ / / 0.\/C ///,..- /r '/ / ', b'-6" %// ,. /// L. I 7/4'-2" 6'-6"i \/ AC. : • ‘' L.. X f REFLECTED CEILING PLAN. SGALE. 11 3 /l Design per NFPA 13, Ordinary Hazard Group 2 All materials to be new, U.L. listed, and F.M. approved All fire sprinkler heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart o 40 — Relocate Globe Model GL5651 Standard Response 155° Chrome Pendents 1/2 x I/2 (w/ 401 Trim) O 1 —Add Globe Model GL5651 Standard Response 155° Chrome Pendents 1/2 x 1/2 (w/ 401 Trim) 11 t•sa g i r£a Iii O Without Comments • • As MAO. in fie:4 • The Attached Letter pians have beeen reviewed by The Tukwila Fire , ''-1wndori Bureau for •c.:Yl ornance With current City . :1CI3;%15. Acceptance s Strb'lect: r'r, :mors and whiter, do f oi..1l..rrlori,:r: '.f olatic,rrs of adopted -T41dards and ordinaric. s i Y r:esoor,sibiii'ty for the ...;;quacy of design rt?sr. vole'+r the designer. !)llll"(('151 deletions a','si ri::vi'riorr7 ;'(.' tneSE: drawings after r.r,isdate IMIi' ` o d i ht,:. acceptance and vjlii require a resubrnitca r,)t. revised dr'awingt� for ..suk,e q'uent .:ipprov 1. Final acceprznce is subject to field test and inspection by • The Tukwila Fire Prevention Bureau. Late: -�`1-1J By: S6r FlexHead Sprinkler Drop 111 .-:,;;;,;,;,i. Corrugated stainless steel hose with stainless steel brat 0 available in 2', 3',4',5' & 6' legnths •l;ikkiak `sus:• Adjustable Mob II MuIU-Port Bracket • • • • FLEXIVAii IN°USI0.IES/ • Flexhead omrriercial Ceilirig Unit •' T -Bar Gelling Installation Model #2024,2036,2048,060,2672 P CERTTE 15r{Oq•Ts OF COMNOTON PETENCY FIRE PROTECTION SPRINKLER eYaTE John J. Abel 9760.0591 -CQ Level3 vm Fire Protection, Inc. C ` w'►_FP044LL ILL \ 0 I aignaturr Expires 1211HS dl VICINITY MAP CROWN FIRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 Daiso Japan \%~79 Southcenter Mall Space # 1378 Tukwila, WA PAD SEP 10 2015 TUKWILP FIRE -�df�lP.z6 DATE:. el" z" (.S DRAWN: lr SCALE: ' 3'((0 )1w ? -Re/ 11,271120 SITE LOCATION CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East Tukwila, WA 98188 206-575-4407 Date application accepted: FIRE PROTECTION SYSTEMS PERMIT APPLICATION Applications and plans must be complete in order to be accepted for plan review. **PLEASE PRINT** King Co. Assessor's Tax No.: Site Address: IS7cFs 5oviiicerlks Ma. 11 Suite Num be )378 Floor: Tenant Name: "exxs) "Sit New Tenant? ❑ - Yes ❑ - No Property Owner's Name: V,..P \--c" \ eY151-13 Mailing Address: City State Zip CONTACT PERSON -if there are questions about the submittal. Name: k2& 1 RC12U7S O/) Day Telephone: 1425 '�s-1 ' 1 o l Company Name: Crown )) -t1 on, 1Y1 C Mailing•Address: P© '2>< \2 \ 1� WA 1\` '�-�,� �T\ P�'BCity Sat- Zi E-mail Address: \ 1 cEc.,ybv3n4 p, Cr,in Fax Number: Total number of new/relocated devices or sprinkler heads: �l Valuation of Project (contractor's bid price): $ (J• Scope of Work (please provide detailed information): _\ y0 , pke3,a PERMIT APPLICATION NOTES Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules. Expiration of Plan Review -Every permit issued shall became invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in • writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILDING 0 ER OR AUTHORIZED AGENT: Signature: t^' Print Name: (IC��jj SS1(_//'I 9?Oh'J)7&7? Plan Permit App.doc 1/2/13 Date: Ci, /l ilc Day Telephone: /42-5 • (' 1 TFD FP Form 8 FIRE SPRINKLER CORPORATION DESCRIPTION AND OPERATION AUTOMATIC SPRINKLERS GL SERIES UPRIGHT •PENDENT VERTICAL SIDEWALL HORIZONTAL SIDEWALL CONVENTIONAL (OLD STYLE) The Globe GL Series Sprinkler is a low profile yet durable design which utilizes a frangible glass ampule as the thermo- sensitive element. While the sprinkler provides an aestheti- cally pleasing appearance, it can be installed wherever stan- dard spray sprinklers are specified. This sprinkler series is available in various styles, orifices, temperature ratings and finishes to meet varying design requirements. The heart of Globe's GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern depending upon the deflector style used. TECHNICAL DATA O See reverse side for Approvals and Specifications. O Temperature Ratings - 135°F (57°C), 155°F (68°C), 175°F (79°C), 200°F (93°C), 286°F (141°C), 360°F (182°C) O 500°F (260°C) Available Upon Request Without Approvals o Water Working Pressure Rating - 175 psi (12 Bars) o Factory tested hydrostatically to 500 psi (34 Bars) O Maximum low temperature glass bulb rating is -67°F (-55°C) O Frame - bronze 0 Deflector - brass 0 Screw - brass O Bulb seat - copper 0 Spring - nickel alloy 0 Seal - teflon O Bulb - glass with glycerin solution, 5mm size UPRIGHT CONVENTIONAL PENDENT VERTICAL SIDEWALL HORIZONTAL SIDEWALL O SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING CLASSIFICATION AVAILABLE SPRINKLER TEMPERATURES BULB COLOR N.F.P.A. MAXIMUM CEILING TEMPERATURE ORDINARY ' =135°F/155°F 57°Ci68°C ORANGE/RED 100°F 38°C INTERMEDIATE 175'F1200°F 79°C/93°C YELLOW/GREEN 150°F X66°C HIGH 286°F 141°C BLUE 225°F 107°C EXTRA HIGH : 360°F. ;. ;182°C MAUVE 300°F 149°C ULTRA HIGH 500°F ^ ' 260°C BLACK 475°F 246°6, 4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658 MARCH 2011 A-65 989-846-4583. FAX 989-846-9231 BULLETIN GL5661, REV. #4 AUTOMATIC SPRINKLERS GL SERIES SPECIFICATIONS NOMINAL "K" FACTOR THREAD SIZE LENGTH 1 FINISHES 2.8 (39 metric) 1/2" NPT 2 1/4" (5.7 cm) Factory Bronze * 500°F * 260°C cULus FM LPC Bright Chrome 4.2 (59 metric) 1/2" NPT 2 1/4" (5.7 cm) Satin Chrome 2 X X X X White Polyest3 5.6 (80 metric) 1/2" NPT 2 1/4" (5.7 cm) Black Poly sterr2.3 7.8 (111 metric) 1/2" NPT 2 1/4" (5.7 cm) Wax Coated 2,3,4 X X X X Lead Coated 2.3 8.1 (116 metric) 3/4" NPT 2 7/16" (6.2 cm) Wax over Lead 2,3,4 NOTE: METRIC CONVERSIONS ARE APPROXIMATE. APPROVALS 1 HORIZONTAL SIDEWALL IS 2 9/16". 2 FINISHES AVA LABLE ON SPECIAL ORDER. a AVAILABLE AS cULus LISTED CORROSION RESISTANT -WHEN SPECIFIED ON ORDER. 4 WAX COATING UL LISTED UP TO 200°F ONLY. STYLE SIN MODEL ORIFICE SIZE 135°F 57°C 155°F 68°C 175°F 79°C 200°F 93°C 286°F 141°C 360°F 182°C * 500°F * 260°C cULus FM LPC CE NYC - DOB MEA 101-92-E GL2861 2.8 X X X X X X X X — — — X GL4261 4.2 X X X X X X X X — — — X UPRIGHT GL5661 5.6 X X X X X X X X X X X X GL8161 7.8t X X X X X X X X — — — X GL8164 8.1 X X X X X X X X X X X X GL2851 2.8 X X X X X X X X — — — X GL4251 4.2 X X X X X X X X — — — X PENDENT GL5651 5.6 X X X X X X X X X X X X GL8151 7.8t X X X X X X X X X — — X GL8156 8.1 X X X X X X X X X X X X VERTICAL GL5675 5.6 X X X X X X X X X — — X SIDEWALL $ GL8176 8.1 X X X X X X X X — — — X GL2870 2.8 X X X X X X X X — — — X HORIZONTAL GL4270 4.2 X X X X X X X X — — — X SIDEWALL § GL5670 5.6 X X X X X X X X X — — X GL8171 8.1 X X X X X X X X — — — — CONVENTIONAL GL5668 5.6 X X X X X X X — — X X — (OLD STYLE) GL8169 8.1 X X X X X X X — — X X — ORDERING INFORMATION SPECIFY • Quantity • Model Number • Style • Orifice • Thread Sizes • Temperature • Finishes desired • Quantity - Wrenches - P/N 325390 (1/2"); P/N 312366 (L.O.) FIRE SPRINKLER CORPORATION MARCH 2011 *500°F 260°C AVAILABLE UPON REQUEST WITH NO APPROVALS. t 1/2" NPT. $ VERTICAL SIDEWALL UL LISTED FOR LIGHT HAZARD ONLY. PENDENT VERTICAL SIDEWALL UL LISTED FOR 6' MIN. SPACING. UPRIGHT VERTICAL SIDEWALL UL LISTED FOR 9' MIN. SPACING. § HORIZONTAL SIDEWALL UL LISTED FOR DEFLECTOR 4" TO 12" BELOW THE CEILING, FM APPROVED 4" TO 6". GLOBE® PRODUCT WARRANTY Globe agrees to repair or replace any of its own manufactured products found to be defective in material or workmanship for a period of one year from date of shipment. For specific details of our warranty, please refer to Price List Terms and Conditions of Sale (Our Price List). 4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658 989-846-4583 FAX 989-846-9231 1-800-248-0278 www.globesprinkler.com PRINTED U.S.A. BULLETIN GL5661, REV. #4 FIRE SPRINKLER CORPORATION DESCRIPTION AND OPERATION AUTOMATIC SPRINKLERS GL SERIES UPRIGHT 0 PENDENT VERTICAL SIDEWALL HORIZONTAL SIDEWALL CONVENTIONAL (OLD STYLE) The Globe GL Series Sprinkler is a low profile yet durable design which utilizes a frangible glass ampule as the thermo- sensitive element. While the sprinkler provides an aestheti- cally pleasing appearance, it can be installed wherever stan- dard spray sprinklers are specified. This sprinkler series is available in various styles, orifices, temperature ratings and finishes to meet varying design requirements. The heart of Globe's GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern depending upon the deflector style used. TECHNICAL DATA o See reverse side for Approvals and Specifications. o Temperature Ratings - 135°F (57°C), 155°F (68°C), 175°F (79°C), 200°F (93°C), 286°F (141°C), 360°F (182°C) o 500°F (260°C) Available Upon Request Without Approvals o Water Working Pressure Rating - 175 psi (12 Bars) o Factory tested hydrostatically to 500 psi (34 Bars) o Maximum low temperature glass bulb rating is -67°F (-55°C) o Frame - bronze o Deflector - brass o Screw - brass o Bulb seat - copper o Spring - nickel alloy o Seal - teflon o Bulb - glass with glycerin solution, 5mm size UPRIGHT CONVENTIONAL VERTICAL SIDEWALL HORIZONTAL SIDEWALL o SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING CLASSIFICATION AVAILABLE SPRINKLER TEMPERATURES BULB COLOR N.F.P.A. MAXIMUM CEILING TEMPERATURE ORDINARY 135°F/155°F :. ` ` 57C/68°C ORANGE/RED 100°F 38°C INTERMEDIATE 175*F/200°F 79C/93°C YELLOW/GREEN 150°F 66°C HIGH 286°F. 141°C BLUE 225°F 107°C EXTRA HIGH 360°Ft , 182°C MAUVE 300°F 149°C ULTRA HIGH 500°F 260°C BLACK 475°F 246°C 4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658 MARCH 2011 A-65 989-846-4583. FAX 989-846-9231 BULLETIN GL5661, REV. #4 AUTOMATIC SPRINKLERS GL SERIES SPECIFICATIONS NOMINAL "K" FACTOR THREAD SIZE LENGTH 1 FINISHES 2.8 (39 metric) 1/2" NPT 2 1/4" (5.7 cm) Factory Bronze * 500°F * 260°C cULus FM LPC Bright Chrome 4.2 (59 metric) 1/2" NPT 2 1/4" (5.7 cm) Satin Chrome 2 5.6 (80 metric) 1/2" NPT 2 1/4" (5.7 cm) White Polyesterz3 Black Polyester 7.8 (111 metric) 1/2" NPT 2 1/4" (5.7 cm) Wax Coated 2.3,4 X GL4261 4.2 Lead Coated 2,3 8.1 (116 metric) 3/4" NPT 2 7/16" (6.2 cm) Wax over Lead 2.3,4 NOTE: METRIC CONVERSIONS ARE APPROXIMATE. APPROVALS 1 HORIZONTAL SIDEWALL IS 2 9/16". 2 FINISHES AVA LABLE ON SPECIAL ORDER. 3 AVAILABLE AS cULus LISTED CORROSION RESISTANT -WHEN SPECIFIED ON ORDER. 4 WAX COATING UL LISTED UP TO 200°F ONLY. STYLE SIN MODEL ORIFICE SIZE 135°F 57°C 155°F 68°C 175°F 79°C 200°F 93°C 286°F 141°C 360°F 182°C * 500°F * 260°C cULus FM LPC CE NYC - DOB MEA101-92-E GL2861 2.8 X X X X X X X X — — — X GL4261 4.2 X X X X X X X X — — — X UPRIGHT GL5661 5.6 X X X X X X X X X X X X GL8161 7.8f X X X X X X X X — — — X GL8164 8.1 X X X X X X X X X X X X GL2851 2.8 X X X X X X X X — — — X GL4251 4.2 X X X X X X X X — — — X PENDENT GL5651 5.6 X X X X X X X X X X X X GL8151 7.8t X X X X X X X X X — — X GL8156 8.1 X X X X X X X X X X X X VERTICAL GL5675 5.6 X X X X X X X X X — — X SIDEWALL $ GL8176 8.1 X X X X X X X X — — — X GL2870 2.8 X X X X X X X X — — — X HORIZONTAL GL4270 42 X X X X X X X X — — — X SIDEWALL § GL5670 5.6 X X X X X X X X X — — X GL8171 8.1 X X X X X X X X — — — — CONVENTIONAL GL5668 5.6 X X X X X X X — — X X — (OLD STYLE) GL8169 8.1 X X X X X X X — — X X — ORDERING INFORMATION SPECIFY • Quantity • Model Number • Style • Orifice • Thread Sizes • Temperature • Finishes desired • Quantity - Wrenches - P/N 325390 (1/2"); P/N 312366 (L.O.) MARCH 2011 *500°F 260°C AVAILABLE UPON REQUEST WITH NO APPROVALS. t 1/2" NPT. $ VERTICAL SIDEWALL UL LISTED FOR LIGHT HAZARD ONLY. PENDENT VERTICAL SIDEWALL UL LISTED FOR 6' MIN. SPACING. UPRIGHT VERTICAL SIDEWALL UL LISTED FOR 9' MIN. SPACING. § HORIZONTAL SIDEWALL UL LISTED FOR DEFLECTOR 4" TO 12" BELOW THE CEILING, FM APPROVED 4" TO 6". GLOBE® PRODUCT WARRANTY Globe agrees to repair or replace any of its own manufactured products found to be defective in material or workmanship for a period of one year from date of shipment. For specific details of our warranty, please refer to Price List Terms and Conditions of Sale (Our Price List). 4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658 989-846-4583 FAX 989-846-9231 1-800-248-0278 www.globesprinkler.com PRINTED U.S.A. BULLETIN GL5661, REV. #4 pi( e lFIRE A UK TE ILA, ASHI N DDITION ON SHEET \ UN/ 3E� SHEET TITLE FA -01 SYSTEV \FOfv ATI O FA -02 TYPICAL WHI\ G A \D VOU\TI \G DETAILS FA -03 SYSTE V CALCULATIO\S A \D SI\GLE LI\ E DIAGA V FA -04 FRE ALAS IV SYSTE V PLA\ SHEET INDEX t VV thout Comments As Noted in Red ® Per The Attached Letter These mans have been reviewed by The Tukwila Fire Preve:;tion Bureau for conformance with current City stancards. Acceptance is subject to errors and o: ni.zIons which do not authorize violation; of adopted -:flclards and. >.<rdinances. 'rhe responsibility for the -Luny of design rests totally with the designer. ^r;s, deletions or revisions to these drawings after ger 1mill void this :-acceptance and will require a . •.Ibmttt:ai of revised drawings for subsequent approval. acceptance is subject to field test and Inspection by TulCw is Fre Prevention Bureau. e: 6' ()- - l l ay: .< 1 WISE SCHE TUKWILA FIRE DEPARTMENT Please call 206-575-4407 and give this Fire Permit No,, End exact acldtess for shut- ;; s :`C, a;:i0i1i approval: I: NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and t-PrrninrOtlon of the testino. D U L- A\ D CO \ D U IT FILL CHAT WIRE DESIGNATION SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKED D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V' SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION • FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4, INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vaC POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NEPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 1 1 1 2 3 3 EX EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT BPS REMOTE BOOSTER POWER SUPPLY PAD -3 SIEMENS PAD-3-ENCL 66" A.F.F. TO TOP DUCT DETECTOR AD2-P W/ SIEMENS HFP-1 1 DET. DUCT HOUSING VERIFY IN FIELD TSM DUCT DETECTOR TEST SWITCH TSM -1 SIEMENS 1 -GANG BOX VERIFY IN FIELD HTR -R INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP BOX VERIFY IN FIELD Di FIRE ALARM HORN STROBE ZH-MC-CW SIEMENS 4S DEEP BOX CEILING FIRE ALARM STROBE ZR -MC -CW SIEMENS 4S DEEP BOX CEILING TSM EX DUCT DETECTOR TEST SWITCH (EXISTING) TSM -1 SIEMENS EXISTING VERIFY IN FIELD ® EX SMOKE DETECTOR (ADDRESSABLE -PHOTO) (EXISTING) HFP-1 1 SIEMENS EXISTING CEILING A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A SYMBOLS LEGEND NORDSTROM 3 LEVELS 171,2.75sf GEO. IGCOI 10 10001 10 FNO 81.NK J�G AG� DEMEV 4000 1!! WASTONG10N NAIL ,LE MARS IPi�Et.6J:i.TLS macys 4 LEVELS NT u 7 44 K Vi AO0RCR04PIe. 250,407st 1. DAISO JAPAN 1378 }�r .�Cr`��� T110 RARE ROA' GN .VIM. GEST 000 ICOILE (,,r�{GV/ AVER te COLD INI..s I � GAZE+ hUL'�5AEL�SS AY WGTAND 1R CNOW Ni80 1001'0 10000 now ft Nl'11 ROM 00<1(011 1.4 COUNTY GNAW( Nal) NEYTX1 :y, ELENS EXISTING JCPenney 3 L 1:VELS 276,168sf PAID AUG -9 2011 TUKWILA FIRE 41:?'7373 7aoi% Lu C13 ca Q 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 z 0 (75 w w Q w J w REV. BY: og 0 DESCRIPTION SHOP DRAWINGS DATE 08/05/11 2aaaaa /GALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 08/05/1 1 BACKROUND PLAN PROVIDED BY: WIRE DESIGNATION GENERAL NOTES SITE PLAN Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved ,JOB NUMBER: 55307 FA -01 } SHEET %1 /�6& / THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCA11ON OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TUBE OUTLET SAMPLING TUBE INLET SAMPLING DUCK OVER 3' WIDE: SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL 120VAC-60NZ DEDICATED E1lERGENCY N01E: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. *CONTACT RATINGS 4.0A 0 125VAC 4.0A 0 30VDC EVAPLR64sgifoLtADV TO NEXT ADDRESSABLE (+ DEVICE STIP IF LAST DEVICE µ- FROM XLS CONTROL PANEL( DR PREVIOUS ADDRESSABLE DEVICE I s}) ' GROUND'S * J O O 0 HTRI-R �-0 0 0' 0' ©• 0 O NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. C -CABLE C -CABLE 0 FROM PREVIOUS > (+) ADDRESSABLE > DEVICE (-) 00 0 PAD -3 00 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 0 s 0 0 0 0 0 3.6k EOL (-) (+) SPARE ; SPARE SPARE (-) NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTA11ON. (+) 0 WIRE DESIGNATION: NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE TWISTED PAIR WITH SHIELD #1B FPLIFPLR RED (JACKET) *CONTACT RATINGS 4.0A 0 125VAC 4.0A 0 30VOC FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTA11ON. O 0 GROUND 0 0 0 0 I ®, I I °• // HTRI-R (-) 0 � (+)> TO NEXT DEVICE OR STOP IF LAST DEVICE (-) DRY CONTACTS TO VAV FAN SHUTDOWN PROVIDED BY MECH/ELEC. DUCT DETECTOR, TEST SWITCH & RELAY MODULE WIRING DETAIL (+) HORN STROBE OR STROBE ONLY 80" A.F.F. (OR UNLESS OTHERWISE SPEC FIED) 4S DEEP BOX HORN STROBE & STROBE WALL MOUNTING DETAIL HORN/STROBE OR STROBE ONLY HORN/STROBE OR STROBE ONLY HORN/STROBE OR STROBE ONLY POWER SUPPLY & RELAY MODULE WIRING DETAIL HONR STROBES & STROBES ONLY WIRING DETAIL TO NEXT DEVICE OR END OF LINE TYPICAL WIRING AND MOUNTING.DETAILS CEILIN TILE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER TIN TEMPERA RE: +32' F (0' C) TO 100' F (38' C) HUMIDITY: 0-9 % RELATIVE HUMIDITY, NON—CONDENSING HFP-11 SMOKE DETECTOR —� FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN ( )> DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION HATH DUCT HOUSINGS AD -11P OR AD-11XPR --- DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW (+) SMOKE DETECTOR WIRING DETAIL 1•0kT> 00 SUPPORT BRIDGE 4" SQUARE DEEP BOX CEILING /— HORN STROBE STROBE ONLY DROP CEILING MOUNTING HARD LID CEILING > TO NEXT ADDRESSABLE DEVICE SUPPORT BRIDGE 4" SQUARE DEEP BOX CEILING HORN STROBE STROBE ONLY HARD LID MOUNTING HORN STROBE & STROBE CEILING MOUNTING DETAIL JUNCTI❑N BOX MOUNTED ON CEILING FLEX JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT / / / 0 0 Io 0 TO NEXT DEVICE CADDY BAR SMOKE/HEAT DETECTOR SUSPENDED ILLUMINATED CEILING SMOKE/HEAT DETECTOR MOUNTING DETAIL Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved w) -t n z '4 1743 IST FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY:_l 0 m 0 DESCRIPTION SHOP DRAWINGS DATE Lo0 to 0 1 �CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 08/05/11 BACKROUND PLAN PROVIDED BY: �OB NUMBER: 55307 SHEET FA -02 DAISO FACP ADD-ONS' ., , !ii`:4))4",.`g4"4''''''' ' ': - - , '''' "gV''gr,g''''':''',g'"`}-'-'-l";A„''''i''''' , •„ ", Calculations DESCRIPTION SHOP DRAWINGS Current Load: C rren 1-6 '' '--', ,:=0 :-',f,:-. ,:::,;,-- Standby: Alarm: ', °' , . , 0 0 . Device Type Qty Amps Total Amps Total Total HFP-11- <<<<< ' 0.0022 0.0022 0.0023 0.000 AD2-P 1 0.0635 0.0635 0.064 0.064 0.030 HTR -R 2 0.009600 ' : ' 070096 0.021 0.042 ZH-MC-CW @30CD 1 0.131 Zi-1-MC-CVV ©75CD 0.222 iZH-MC-CW @95CD 2 0.0731 Amps 0.106 Amps , t , Signal'4111,71 C: Paneli' BatteryLoad Calculations DESCRIPTION SHOP DRAWINGS C rren 1-6 '' '--', ,:=0 :-',f,:-. ,:::,;,-- ' " ,.,= ,' ° ,:',1c,' ' =,,.,Standby: '',45','.,=',4` ', °' , 0 0 Device Type Qty Amps Total Amps Total 2 <<<<< Main System Board 1 0.03 0.03 0.030 0.030 ZH-MC-CW 5CD , 0.0875 ZH-MC-CW @30CD 1 0.131 Zi-1-MC-CVV ©75CD 0.222 iZH-MC-CW @95CD 2 0.292 0.584 Zi -I -HMC -CW ©115CD 0.371 ZR -MC -CW @15CD 3 0.069 0.207 ZR C -W ©15CD 0.064 0.03 Amps 0.821 Amps Standby Current Load: 0.03 Amps. For 24. Hours z-- 0.720 Amp -hours Alarm Current Load: 0.821 Amps For 5 Minutes 0.069 Amp -hours 25% Derating= 0.986 Amp -hours Total System Current Load: 0.986 Amp -hours Battery Pair16 beiised I2VDC',-: '':::- 3 1 '-,"*I';'!' = Amp -hours ' ' NotificationApplianceCircuit Detail PROJECT: DAISO Panel: 1, PAD -3 POWER SUPPLY ,Wire Resistance 2.58 Date: August 8, 2011 CURRENT TOTAL= 922.00 @15CD 871 1. ZH-MC-CW ©30CD 131 ZH-MC-CW @75CD 222 . , 2 ZH-MC-CW @95CD 292 @115CD 1 371 0 ZR -MC -CW ©15CD 69 207 'ZR -MC -W @15CD 64 01 DEVICES= 6 175 0 TOTAL mA=1 922 Total Wire Resistance ( R ) Total Device Load, Amps (I) Voltage Drop ( E) EOL Voltage 14 208 23.011 9221 1.071 (TOtal=,CotirLoad) 0.92 1(E= I * R).1 0.991 24. -;Ey 23.01 1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 z 0 U) LLJ Ct LU (/) LU _J LU TO EXISTING SIGNALING CIRCUIT/DEVICE 120VAC, DEDICATED ( BY OTHERS ) SYSTEM CALCULATIONS 2C —c> BPS EX S1-1 S1-2 30cd 15cd (LOCATED AT STORAGE AREA) S1-3 S1-4 15cd 15cd EX TSM AHU TSM S1-5 95cd S1-6 95cd EXISTING DATA LOOP EOL S1 FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110VAC BRANCH CIRCUIT. SMOKE DETECTOR MUST BE LOCATED IN THE SAME ROOM/AREA AS THE PAD -3. DUCT DETECTOR, RELAY MODULE FOR FAN SHUTDOWN & TEST SWITCH LOCATIONS TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. REV. BY: 0 m 0 DESCRIPTION SHOP DRAWINGS DATE ... 0 0 co 0 2 <<<<< ALE: NOT cc 0 0 w z w 0 z z C/) z0 C.) F. - CI) TO SCALE" SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE:08/05/11 BACKROUND PLAN PROVIDED BY: SINGLE LINE DIAGRAM Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved \JOB NUMBER: 55307 SHEET FA -03 ;.* 4011 (r.. (.0 6 AHU EX (HTR -R TSM) EOL S1 S1-6 95cd L A 100 L 0-02) F-02 ) I I i S1-5 95cd r F 1 FIRE ALARM SYSTEM PLAN S1-4 15cd F06 _l-0 Db T77....7 .--771-- -- LST 15c4 [411 EX SIC s,s 1 AG 101 S1-2 " 15cd / c 18 J 103 CN FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110VAC BRANCH CIRCUIT. SMOKE DETECTOR MUST BE LOCATED IN THE SAME ROOM/AREA AS THE PAD -3. DUCT DETECTOR, RELAY MODULE FOR FAN SHUTDOWN & TEST SWITCH LOCATIONS TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. FLOOR PLAN NOTES SYM OL `J O T DISPLAY FIXE,JRES 3ROVIDED BY TENA\ T, TYDICAL CASH WAD 9:0V DEQ BY T-\A\T, TO 31 ADA CONDI_ ANT WITH CC/A\SI A117.1-2003 CI --IATER 9 ATAGRA. 1-1 90 -.3 LI\E OF EXISTING GWS SOF-F- 8'-6" ABOVE FINIS -ED 7L00 Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 02 0 DESCRIPTION SHOP DRAWINGS DATE 08/05/11 co z co r z a. Q wa dCwWz 0. (/) = ,.'c cn cc <go ty. CO Z a w 1-1 >- (0 ccW SCALE: 1/4"=1'0" DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 08/05/ 1 1 BACKROUND PLAN PROVIDED BY: .OB NUMBER: 55307 FA -04 C SHEET