HomeMy WebLinkAboutPP - 1395 SOUTHCENTER MALL - SWEET FACTORY - PERMITS AND PLANS1395 SOUTHCENTER MALL ASSOCIATED PERMITS 14-F-118 14-S-111 C ., FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: 100 % Pure 1395 Southcenter Mall Permit No.: 14-S-111 Date: May 14, 2014 Reviewer: Al Metzler Fire Protection Project Coordinator (206) 575-4407 option # 2 (Inspection Requests) (206) 971-8718 (Plan Review Questions) • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 20 or more sprinkler heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a Toss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. All code references are NFPA 13, 2010 Edition. JrZEUr SITE LOCATION CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East Tukwila, WA 98188 206-575-4407 Date application accepted: FIRE PROTECTION SYSTEMS PERMIT APPLICATION Applications and plans must be complete in order to be accepted for plan review. **PLEASE PRINT** King Co. Assessor's Tax No.: 9202470010 Site Address: 1395 Southcenter Mall Suite Number: 356 Floor: Tenant Name: 100% Pure New Tenant? E - Yes ❑ - No Property Owner's Name: Westfield Property Tax Dept. Mailing Address: POB 130940, Carlsbad, CA 92013 CONTACT PERSON -if there are questions about the submittal. Name: Karina Veliz Day Telephone: 206.349.5889 City State Zip Company Name: Guardian Security Systems Mailing Address: 1743 First Ave South, Seattle, WA 98134 kveliz@guardiansecurity.com .com City State Zip �g Y E-mail Address: Fax Number: 206.628.4990 Total number of new/relocated devices or sprinkler heads: 32 Valuation of Project (contractor's bid price): $ 1400 Scope of Work (please provide detailed information): Adding 7 devices to existing FACP. PERMIT APPLICATION NOTES Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules. Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILDING 0 ER OR AUTHORI E 1 AGENT: Signature: Date7.5 11_009 Print Name: Karina Veliz Day Telephone: 206.349.5889 Plan Permit App.doc 1/2/13 TFD FP Form 8 \\\\\\\\\\\\\ S\\\\\w��ww�w�ww}w�ww�wwww�w�ww�w�ww�wwwwww�ww-\\\\\\\\\\` O Q -0 O a 0 O O o c] O O 0 M Q 0 51 v -5- m REFLECTED .CEILING PLAN A Scale: 1/4" = 1'-0" , II I -lo FlexHead Sprinkler Drop Corrugated stainless steel hose with stainless steel braid available in 2', 3',4',5' & 6' Iegnths . Mulli-Port Bracket • • Adjustable Hub 7 . mo FIEXII ���� INousIFIEsf Flexhead'tomniercial Ceiling Unit T -Bar Ceiling Installation Model #2024,2036,2048,2060,2072 Design per NFPA 13, Ordinary Hazard, Group 2 All materials to be new, U.L. listed, and F.M. approved All fire sprinkler heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart ® 11 — Add Reliable Model G5-56 QR 165° White Concealed Pendents 1/2 x 1/2 CCE ID Without Comments 0 As Note() in Red lir Per The Attached Letter These pians have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current. City standards. Acceptance is'subject to errors and omissions which do not authorize violations of adopted standards and ordinances, The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings after :this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance Is subject to•fleld test and Inspection by The Tukwila Fire Prevention Bureau, Date: S fLf-1 Y By: 1 1 TUKWILA FIRE DEPARTMENT Please call 206-575-4407 and give this Fire Permit No. /1-/,S-/// and exact address fix shut- down or restoration approval. RETAINER STRAP WHERE REQUIRED IN SEISHIC AREAS TOP BEAM/ C—CLAMP WITH SET SCREW 3/9' ALL THREAD ROD PIPE SWIVEL RING CRO.WN. FIRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 STEEL JOIST/TRUSS HANGER DETAIL NTS bk. WASHINGTON STATE CERTIFICATE OF COMPETENCY ' FIRE PROTECTION SPRINKLER SYSTEM John J. Abel 9760.0591•CG Level 3 C wn Fire Protection, Inc.. 0-* NFPO, i 10 , Expires Signature 12/31/14 Pileamiu1U.waw...a.wl•ntwauttnm+awraewM-itis,-twi • of Ion in.1• ah 11 ° w li! LF Iii 1liJ,I u14;7:.Fggv dt i4 rPI fir r;;s "ALWA ►a7 '1 MMI "1.ail., w ■ villi X11 111_ PARTIAL SITE MAP N.T.S 100% Pure /39s Southcenter Mall Tukwila, WA DATE: 3--..`�.'V DRAWN: ( SCALE:. \ j y 0 FIRE A ARM S ST K ILA, P DDITION ASMI GTON CC. P E Without Comments ❑ As Note;1 ,r1 Red ❑ Per The (attached Letter The6e plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City st, ndards. Acceptance Is subject errors and omissions which do not authorize violations of adopted r andards and ordinances. The responsibility for the Udequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings after this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to fleld test and Inspection by The Tukwila Fire Prevention Bureau. Date: - - / `'j . By: J 1 SHEET \UV3ESHEET TITLE FA -01 SYSTEM I \ FO V ATI O \ FA -02 TYPICAL WRING A\D MOU\TI\G DETAILS FA -03 SYSTEM CALCULATIO\S A\D SI\GLE LI\E DIAGA V FA -04 FRE ALAN SYSTEM PLAN SHEET INDEX WISE SCH -DULE A\D CO \ D U IT FILL C HATT WIRE DESIGNATI❑N SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V' SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED -UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE 'NITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTDRS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PRCVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY EX EX 1 1 2 2 1 SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX TUKWILA FIRE DEPARTMENT Please call 206-575-4407 and give this Fire Permit No. ILL. F -1I' and exact address for shut- down or restoration approval. NOTICE 4 completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing MOUNTING HEIGHT BPS REMOTE BOOSTER POWER SUPPLY PAD -3 SIEMENS PAD-3-ENCL 66" A.F.F. TO TOP SMOKE DETECTOR HFP-11 W/ SIEMENS (PHOTO -ADDRESSABLE) DB -11 BASE ® D DUCT DETECTOR 4S DEEP W/ 1 G RING AD2-P W/ SIEMENS DUCT HOUSING HFP-11 DET. CEILING VERIFY IN FIELD TSM DUCT DETECTOR TEST SWITCH TSM -1 SIEMENS 1 -GANG BOX VERIFY IN FIELD FAT -171 INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP BOX VERIFY IN FIELD FIRE ALARM Dl HORN STROBE (CEILING MOUNT) ZH-MC-CW SIEMENS.. 4S DEEP BOX CEILING FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -CW SIEMENS 4S DEEP BOX CEILING A. F. F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A SYMBOLS LEGEND BE4 8100E JEW '1S HI.RF FIE1/IE TENANT SOACE / %].R WAICEN800KS 0 COOIVA 100-1 51 8100.0 AVON YERILO4 W.RELLSS WADE IN WASHI`IOION IIAR.ONAL UNIVERSITY OEAUTY 1WRK5 SEAIRS 10.00 1h% Flx1 LTrc.,Hlm M -LAV fra "'a"' HI41&ASj OESCN macys 4 LEVELS 250,407sf USN COSNERCS ARM EL K015 J C0E'W 6' Rik THE RARE ROSE L1141EL DISNEY STORE CNCUAR I ICING 91E1K SNOE5 f; FF�A�4 91.010 & 001/0 g 7,p;; 5 IN'ti0t 5 I I htO 18 GAGE AF'h aTANO 100% PURE #1395 / SPACE #356 T0K10 10850 01100<1/16 U OrrlY HCO 01880/1 JOLLIBCE 0/150 KING COUNTY LIORARY PAID MAY 29 2014 TUKWILA FIRE 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 z 0 w w w w Ch REV. BY: 0 m 0 z 0 w E U w w o SHOP DRAWINGS DATE 05/27/14 1� 1 Z 0 W co Z WCO O Ur W8coz cc < ItF2 w �z p C'WC/) CC O 2 z� O v� W L /C/) I- CO V% �CALE: NOT 1-1 0 Z 11.1 0) 0) TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE DATE:05/27/14 BACKROUND PLAN PROVIDED BY: WIRE DESIGNATION GENERAL NOTES SITE PLAN Gly Proprietary and Confidential, Copyright 2012 by Guardian Security Systems, Inc. All Rights Reserved .OB NUMBER: 8985-9 U� SHEET n FA -01} THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DUCK OVER 3' WIDE: SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. TUBE OUTLET SAMPLING TUBE INLET SAMPLING AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL 120VAC-6011Z — DEDICATED EMERGENCY NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PR60UCT DOCUMENTATION. *CONTACT RATINGS: 4.0A 0 125VAC 4.0A 0 30VDC TO NEXT ADDRESSABLE 14 TO DEVICE SP IF LAST DEVICE - TRIM TLCs CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVICE O O O 1] HTRI-R � O 0 0311 ®* o O N01E FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. C -CABLE C -CABLE 0 FROM PREVIOUS > (+) ADDRESSABLE > DEVICE (-) IXI Z 0 PAD -3 00 INPUT INPUT TROUBLE MCI W.C2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 0 0 0 3.6k EOL w a 0 (-) (+) 2 SPARE SPARE j SPARE (-) NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. (+) 0 WIRE DESIGNATION, NUMBEROFCONDUCTORS SIZE TYPE COLORCODE TWISTED PAIRWITH SHIELD #I8 FPLIFPLR RED (JACKET) *CONTACT RATINGS: 4.0A 0 125VAC 4.0A 0 30VDC FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. O 0 4 LJ I I HTRI-R I -I GROUND A 0 0 0 0 (+)> TO NEXT DEVICE OR (-) > STOP IF LAST DEVICE DRY CONTACTS TO VAV .--> FAN SHUTDOWN PROVIDED BY MECH/ELEC. DUCT DETECTOR, TEST SWITCH & RELAY MODULE WIRING DETAIL POWER SUPPLY & RELAY MODULE WIRING DETAIL (+) HORN STROBE OR STROBE ONLY 80" A.F.F. (OR UNLESS OTHERWISE SPEC FIED) 4S DEEP BOX HORN STROBE & STROBE WALL MOUNTING DETAIL + `J HORN/STROBE OR STROBE ONLY C) HORN/STROBE OR STROBE ONLY HORN/STROBE OR STROBE ONLY HONR STROBES & STROBES ONLY WIRING DETAIL TO NEXT DEVICE OR END ❑F LINE TYPICAL WIRING AND MOUNTING DETAILS CEILIN TILE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER TIN TEMPEJA RE: +32' F 0' C) TO 100 F (36 C) HUMIDITY: -9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN ( ) >-- DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR r DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW (-) (+) SMOKE DETECTOR WIRING DETAIL 00�0. QO♦00 0 0 SUPPORT BRIDGE 4" SQUARE DEEP BOX CEILING /- HORN STROBE / STROBE ONLY DROP CEILING MOUNTING HARD LID CEILING > TO NEXT ADDRESSABLE DEVICE SUPPORT BRIDGE 4" SQUARE DEEP BOX CEILING HORN STROBE STROBE ONLY HARD LID MOUNTING HORN STROBE & STROBE CEILING MOUNTING DETAIL "Svt , o4I4I," JUNCTI❑N BOX MOUNTED ON CEILING FLEX 4+,4'4'40,4" i JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT 0 OH O O I TO NEXT DEVICE CADDY BAR SMOKE/HEAT DETECTOR SUSPENDED ILLUMINATED CEILING SMOKE/HEAT DETECTOR MOUNTING DETAIL 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY:] 0 m D DESCRIPTION SHOP DRAWINGS DATE 05/27/14 2«a<a< coLLI co1 O U - I_ tra3 o fn0 O W 2z ccl cc w Q=- W ~ cc On Z LcoU)E 0) 4-CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE DATE:05/27/14 BACKROUND PLAN PROVIDED BY: \OB NUMBER: 8985-1i SHEET FA -02 Proprietary and Confidential, Copyright 2012 by Guardian Security Systems, Inc. All Rights Reserved :R P zk. r �<,� : d J,y�. ;`{ ,.,€. %# xi,'"•k�y �P .gi,j±,r33y, . N.3'"'L�', ls<"•� 1�1M1:3.',1p.?ziiY{4i'.;:'�^€ '��^>�':. yy{{::ee2i '�3 f,.Y � :YL>�, EY„s; <,<#k,2," ++�� ssd,. �ik'd, ..<"�i < � ,..� x! k3a'ss"�°7: i:v i1 `i.''.�,^'`}:"'✓' §ii?`�'y_.<i f��,�as.t. �,. ,..� k5 €��', .; F,/.; a.s<l;,.y;4: fi. '<}'�LhS ''85'Y `�"�` s .'mt� r, . PS`'S`wE' A..,4 c':ii u� Sd�,*w`�i{ kn„<t�y�., rf; �L.��1 a:utkC S<x`, } i?;+"'+'w€ v. ,:;€�.*5`d ��, �-,g,6��',E i`�%d9 �7','N'{3r4�ia `wn• e #,�F.ati� 3 r:s<�i?�L ,E, ��y .�.<ds'). � y x+t,�2;,�b5'A .hX>,v �< p S` :`,yb ''�S''n" (�^�.' «{'n�1 ', .%C „'dv, y< d .l$,:"•y3°' 'pe 4:"`. a'' rV�:g3),�?<m x§'' e$¢;� pi� w3 � i,vN `siv "4'' ' � .?�2.: r:*^a.�, ti.�, 'S j, �}, U ej, Y: ''/X r.; x> : kw : � s�tj ,.i( 5..'Y, vt"'f erz:,�-:,1.. , g A't. °Kr, 3S - � "#�; <x,.e �, is '#:i'; i.�51 ti,?k :d'ii"£., '?n �F `f !> xr�, x' ,#..s.ifi";; �'a'£i�"�.n� £s; x £'0.t i#3 � "dk'„'� ?r k^.ki'`yb.,"p�#'•'�`z 9'� j�f^,4.f 'r, aL3 ��i � "57 ra `” ".,^ ..,,,¢ .� '. 7.:'Y3 .? ;i^, �" dF;#',w0.',Yi eY' y+ y{jiy��"^Ya'' oi. .. ok'4 '2a ,j ��n r :'z � #', '#; ;� a l k C'. vk ,nt 3 4e rti5 ,`i ><,£ :;'45� ''� ,��,4il5<x,�, �,�Sb �^f"k`za`ur ,;� r�i `�`� ? S ` M,t F t z: t 1 WMNi4w ro 3 f DATE Current Load: Standby: Alarm: .:35ca`9s` ,,:�`. ;,+ y Yg,u<'j€;, , ::t ,, .x• ' My ,$}. {p is•�'#v'` .� t., ra r' Ya. {j.��y ,4.' NSA"'„ik !.:,Yx” q9� :>.^k'H:f?i; uy■{r�: 't�! VMM>Y 4:s'h,<. .nj .�' 3�k4x}�; r'J'.,�<,,{ ..; .r .�wa, .:(z,.y,Y,. >✓i<,v{i<..?�N�.�.,.��,. :4a, �<#g�, ,. r,.,,,, ,,.q...,k$+' , ., `a�P' `'k''r,.i ,}$ r'ke :5 x ..,r�!'�s >y.,V i•" 16 xrt � ;�, � '2 < ^Y rY' '>'S,'r^ *r S ^' 3 ,L; �, y&" ,.;b �: # :a' ?R,';` qua, > ;<., A% #S3 �" , Sseh'«f' "}tl'%:`,'yE: ,1 ,�1�I,. e. Na> e�� {�.s�`�.��' $4 :k' .Y,9.,Ak..z :. y,,, .s Y:..Y �i«u";U .:. �h,ny ,,<f ., ,r. .. ... � R>: ' k +>y' y#:�`!.<s,, ,, '�, w it'a r, < ph, :>'g'r X 3< yyy� ,;Y 3 ,. ":. Lix € Y AMM' M b,t ) , i .^'„ ,':Y+f, � >,.. ,r, s „ M' :#� s Device Type Qty Amps Total Amps Total HFP-11': ' 0.0022 - 0.0022 , 0.0023 0.000',. Qty AD2-P 1 0.0635 0.0635 0.064 0.064 HTR -R : :. > 2 0.009600 0.0096 0.021 0.042 Main System Board 1 0.03 0.03 0.030 0.030 ZH-1111C=CW @15CD 13 , ` : 0.0875 0.0731 Amps 0.106 Amps �5 5. FiI 'fi 'fi ✓wt, t rF' Y i � 1 � ,.� � , . �' �. k. � �,,. Y F 4 t } J 5t 31 '',<' Y' as t I q k 'N ✓ d2 g a�#. �' �'sia.k qW' '�✓ , .r :- �^,. ,, . . �' . , t ,n $"F` .. 3 { 59 0 � 5 d J { M 'Yn ..e�Y� .,.g �} S"� '¢'ke fk ';s i .�,a '3s y 1,�. •, s 4: S ` M,t F t z: t 1 WMNi4w ro 3 f DATE 05/27/14 .:35ca`9s` ,,:�`. ;,+ y Yg,u<'j€;, , ::t ,, .x• ' My ,$}. {p is•�'#v'` .� t., ra r' Ya. {j.��y ,4.' NSA"'„ik !.:,Yx” q9� :>.^k'H:f?i; uy■{r�: 't�! VMM>Y 4:s'h,<. .nj .�' 3�k4x}�; r'J'.,�<,,{ ..; .r .�wa, .:(z,.y,Y,. >✓i<,v{i<..?�N�.�.,.��,. :4a, �<#g�, ,. r,.,,,, ,,.q...,k$+' , ., `a�P' `'k''r,.i ,}$ r'ke :5 x ..,r�!'�s >y.,V i•" 16 xrt � ;�, � '2 < ^Y rY' '>'S,'r^ *r S ^' 3 ,L; �, y&" ,.;b �: # :a' ?R,';` qua, > ;<., A% #S3 �" , Sseh'«f' "}tl'%:`,'yE: ,1 ,�1�I,. e. Na> e�� {�.s�`�.��' $4 :k' .Y,9.,Ak..z :. y,,, .s Y:..Y �i«u";U .:. �h,ny ,,<f ., ,r. .. ... � R>: ' k +>y' y#:�`!.<s,, ,, '�, w it'a r, < ph, :>'g'r X 3< yyy� ,;Y 3 ,. ":. Lix € Y AMM' M b,t ) , i .^'„ ,':Y+f, � >,.. ,r, s „ M' :#� s . 1� «'Y• ,} .'oC jiY,t'..Czr::':�. t'.`•°'??Y': y �t iL �nh,,,v, ..,, .i.v; *;�5 ;:'...� ,ry;; j�; Device Type Qty Amps Total Amps Total Main System Board 1 0.03 0.03 0.030 0.030 ZH-1111C=CW @15CD 13 , ` : 0.0875 ZH-MC-CW @30CD 5 0.131 al -MC -CW @75CD 4 0.222 ZH-MC-CW ©95CD 0.292 71 -1 -HMC -CW ©11 CD 0.371 ZR -MC -CW @15CD 15 0.069 1.035 ZR -MC -W @15CD ` 0.064 0.03 Amps 1.065 Amps Standb CuCurrent,Load:`. y.03 Amps ' ' ' ' For 24 Hours = 0.720 Amp -hours Alarm Current Load: '1.065 Amps For 5 Minutes= 0.089 Amp -hours 25% Derating= 1.012 Amp -hours Total System Current Load: 1.012 Amp -hours dOs t;.£,y■£', F , q, * k' .', 9'iY3i yZyx �..a[�' k ,f fl d#'j.,,<yyq' s ft%,�: A: .fi i`4 4 {.i <,A5 A.'r' €'t`,6 �y'sY b# y ,',§'9li>M$fA y} Notification Appliance Circuit Detail PROJECT: 100% PURE Panel: EXISTING PAD -3 POWER SUPPLY Date: May 27, 2014 Wire Resistance 2.58 CURRENT TOTAL= 378.00 ZH-MC-CW @15cd 8 -MC-CW @30cc1 ZH-MC-CW @75cd YN= VIC' 95cct al -MC -CW @115cd ZR -MC -+CW @l5cd 222 2221 292 DEVICES , 3 TOTAL mA= 286 23.441 378 Total Wire Resistance R ota1 Device Load, Amps(I) Voltage Drop ( E ) EOL Voltage WL 2) R/ft 1.48 48 otai cet Load 0. 8: E_I.<._.,, 0.56 SYSTEM CALCULATIONS TO NEAREST EXISTING POWER SUPPLY TO NEAREST EXISTING DATA LOOP S S1-1 S1-2 Eivvv_EOL S1 S1-3 15cd 15cd 75cd FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. DUCT DETECTOR, RELAY MODULE FOR FAN SHUTDOWN & TEST SWITCH LOCATIONS TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. c igi 462 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4.990 TEL. (206) 622-6545 U) z 0 U) w w Q LU J LU CC IREV. BY: 0 m 0 DESCRIPTION SHOP DRAWINGS DATE 05/27/14 z <<<<< oc 0 0 w z CO LU Z W coc —J 0 CD rim, Z w o ccQJO 0 w �Z z )z d U) CDocw.' Z ICOR u- Cn I— LO M T 0 w F-- (/) >— (1) CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE SINGLE LINE DIAGRAM DATE: 05/27/14 BACKROUND PLAN PROVIDED BY: SOB NUMBER: 89857_1} SHEET FA -03 Proprietary and Confidential, Copyright 2012 by Guardian Security Systems, Inc. All Rights Reserved 11 TO NEAREST EXISTING POWER SUPPLY TO NEAREST EXISTING DATA LOOP S c 41 fir- -- ;�;'� STORAGE AREA 002 IMMO _J - • _J - _J MOO J EMERGENCY GRILLE RELEASE BUTTON WITH SIGNAGE WITH BRAILLE ALSO KEY LOCATION TO OPERATE GRILLE S1-1 12"D \4 S1-2 1 HDCP5cd RESTROOM Li�� SALES AREA 0011 EOL -�A"__� S1 S1-3 S1-3 75cd \ 7-7 NEW CLEAR 1/2"_ ANODIZED ALUM REVEAL 13)0 C17 KEY LOCATION TO OPERATE GRILL ----NEW CLEAR 1/2" ANODIZED ALUM REVEAL 3 g 71-Z 'I J SYMBOL LEGEND (E) PARTITION TO REMAIN r rr 3 5/8" 20GA MTL STUD FURRING W 5/8" TYPE 'X' GWB AT EXPOSED SIDES 'TL�l.T1A (N) FULL HIEGHT PARTITION 35/8' 20 GA METAL ENDS @16" O.C. W/ %TYPE 'X' GYP BOARD BOTH SIDES; FIRE CAULK AND TAPED METAL SIGN BOX/ROLL DOWN GRILLE POST CLADDING CONSTRUCTION KEY NOTES () (N) ROLL DOWN GRILL C?) 3) (N) ILLUMINATED SIGN BOX BY SIGN VENDOR. LEASE LINE (N) TELEPHONE BACKBOARD (N) ELECTRICAL PANEL (N) POST FOR ROLL -DOWN GRILLE RAIL SUPPORT SINK - KOHLER KATHRYN #K -2297-G FAUCET - GROHE ALLURE #20191-000 G.C. TO PROVIDE BACKING FOR WALL STANDARDS RECESSED WALL STANDARDS BY VISPLAY SYSTEM, SEE SHEET A-6.2 (N) TEMPERED BUTT -JOINED GLASS -1/2" STAR FIRE T.G. 01) NON- ILLUMINATED GRAPHIC. (•th'') RECESSED LIGHT BOX FOR ILLUMINATED GRAPHIC . 13) 7" ANTIQUE WHITE OAK CLADDING EXTENSION. C1� FIRE ALARM SYSTEM PLAN MELANINE SHELVING 12" DEEP WITH SURFACE MOUNTED STANDARDS 6' LONG, G.C. TO PROVIDE BACKING FOR STANDARDS EMPLOYEE LOCKERS 1 TIER 4 LOCKERS EXTEND (E) NEUTRAL PIER AS REQUIRED FOR (N) STOREFRONT PROJECTION. EXISTING EXPANSION JOINT TO REMAIN BARRICADE FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. DUCT DETECTOR, RELAY MODULE FOR FAN SHUTDOWN & TEST SWITCH LOCATIONS TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS IREV. BY: 1 0 m 0 DESCRIPTION SHOP DRAWINGS DATE 05/27/14 2 co z w o0oo o 01- P SS upcnz Er Q w z J1 nD Q_ cc I w. ) 0 Z� <1— w� cc o� LLC - 0) M W CC �CALE: 1/4"=1'0" DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE DATE: 05/27/14 BACKROUND PLAN PROVIDED BY: ,JOB NUMBER: 8985-I) r SHEET FA -04 Proprietary and Confidential, Copyright 2012 by Guardian Security Systems, Inc. All Rights Reserved 1395 SOUTHCENTER MALL ASSOCIATED PERMITS 14-F-118 14-S-111 C ., FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: 100 % Pure 1395 Southcenter Mall Permit No.: 14-S-111 Date: May 14, 2014 Reviewer: Al Metzler Fire Protection Project Coordinator (206) 575-4407 option # 2 (Inspection Requests) (206) 971-8718 (Plan Review Questions) • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 20 or more sprinkler heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a Toss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. All code references are NFPA 13, 2010 Edition. JrZEUr SITE LOCATION CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East Tukwila, WA 98188 206-575-4407 Date application accepted: FIRE PROTECTION SYSTEMS PERMIT APPLICATION Applications and plans must be complete in order to be accepted for plan review. **PLEASE PRINT** King Co. Assessor's Tax No.: 9202470010 Site Address: 1395 Southcenter Mall Suite Number: 356 Floor: Tenant Name: 100% Pure New Tenant? E - Yes ❑ - No Property Owner's Name: Westfield Property Tax Dept. Mailing Address: POB 130940, Carlsbad, CA 92013 CONTACT PERSON -if there are questions about the submittal. Name: Karina Veliz Day Telephone: 206.349.5889 City State Zip Company Name: Guardian Security Systems Mailing Address: 1743 First Ave South, Seattle, WA 98134 kveliz@guardiansecurity.com .com City State Zip �g Y E-mail Address: Fax Number: 206.628.4990 Total number of new/relocated devices or sprinkler heads: 32 Valuation of Project (contractor's bid price): $ 1400 Scope of Work (please provide detailed information): Adding 7 devices to existing FACP. PERMIT APPLICATION NOTES Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules. Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILDING 0 ER OR AUTHORI E 1 AGENT: Signature: Date7.5 11_009 Print Name: Karina Veliz Day Telephone: 206.349.5889 Plan Permit App.doc 1/2/13 TFD FP Form 8 \\\\\\\\\\\\\ S\\\\\w��ww�w�ww}w�ww�wwww�w�ww�w�ww�wwwwww�ww-\\\\\\\\\\` O Q -0 O a 0 O O o c] O O 0 M Q 0 51 v -5- m REFLECTED .CEILING PLAN A Scale: 1/4" = 1'-0" , II I -lo FlexHead Sprinkler Drop Corrugated stainless steel hose with stainless steel braid available in 2', 3',4',5' & 6' Iegnths . Mulli-Port Bracket • • Adjustable Hub 7 . mo FIEXII ���� INousIFIEsf Flexhead'tomniercial Ceiling Unit T -Bar Ceiling Installation Model #2024,2036,2048,2060,2072 Design per NFPA 13, Ordinary Hazard, Group 2 All materials to be new, U.L. listed, and F.M. approved All fire sprinkler heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart ® 11 — Add Reliable Model G5-56 QR 165° White Concealed Pendents 1/2 x 1/2 CCE ID Without Comments 0 As Note() in Red lir Per The Attached Letter These pians have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current. City standards. Acceptance is'subject to errors and omissions which do not authorize violations of adopted standards and ordinances, The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings after :this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance Is subject to•fleld test and Inspection by The Tukwila Fire Prevention Bureau, Date: S fLf-1 Y By: 1 1 TUKWILA FIRE DEPARTMENT Please call 206-575-4407 and give this Fire Permit No. /1-/,S-/// and exact address fix shut- down or restoration approval. RETAINER STRAP WHERE REQUIRED IN SEISHIC AREAS TOP BEAM/ C—CLAMP WITH SET SCREW 3/9' ALL THREAD ROD PIPE SWIVEL RING CRO.WN. FIRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 STEEL JOIST/TRUSS HANGER DETAIL NTS bk. WASHINGTON STATE CERTIFICATE OF COMPETENCY ' FIRE PROTECTION SPRINKLER SYSTEM John J. Abel 9760.0591•CG Level 3 C wn Fire Protection, Inc.. 0-* NFPO, i 10 , Expires Signature 12/31/14 Pileamiu1U.waw...a.wl•ntwauttnm+awraewM-itis,-twi • of Ion in.1• ah 11 ° w li! LF Iii 1liJ,I u14;7:.Fggv dt i4 rPI fir r;;s "ALWA ►a7 '1 MMI "1.ail., w ■ villi X11 111_ PARTIAL SITE MAP N.T.S 100% Pure /39s Southcenter Mall Tukwila, WA DATE: 3--..`�.'V DRAWN: ( SCALE:. \ j y 0 FIRE A ARM S ST K ILA, P DDITION ASMI GTON CC. P E Without Comments ❑ As Note;1 ,r1 Red ❑ Per The (attached Letter The6e plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City st, ndards. Acceptance Is subject errors and omissions which do not authorize violations of adopted r andards and ordinances. The responsibility for the Udequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings after this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to fleld test and Inspection by The Tukwila Fire Prevention Bureau. Date: - - / `'j . By: J 1 SHEET \UV3ESHEET TITLE FA -01 SYSTEM I \ FO V ATI O \ FA -02 TYPICAL WRING A\D MOU\TI\G DETAILS FA -03 SYSTEM CALCULATIO\S A\D SI\GLE LI\E DIAGA V FA -04 FRE ALAN SYSTEM PLAN SHEET INDEX WISE SCH -DULE A\D CO \ D U IT FILL C HATT WIRE DESIGNATI❑N SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V' SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED -UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE 'NITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTDRS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PRCVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY EX EX 1 1 2 2 1 SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX TUKWILA FIRE DEPARTMENT Please call 206-575-4407 and give this Fire Permit No. ILL. F -1I' and exact address for shut- down or restoration approval. NOTICE 4 completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing MOUNTING HEIGHT BPS REMOTE BOOSTER POWER SUPPLY PAD -3 SIEMENS PAD-3-ENCL 66" A.F.F. TO TOP SMOKE DETECTOR HFP-11 W/ SIEMENS (PHOTO -ADDRESSABLE) DB -11 BASE ® D DUCT DETECTOR 4S DEEP W/ 1 G RING AD2-P W/ SIEMENS DUCT HOUSING HFP-11 DET. CEILING VERIFY IN FIELD TSM DUCT DETECTOR TEST SWITCH TSM -1 SIEMENS 1 -GANG BOX VERIFY IN FIELD FAT -171 INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP BOX VERIFY IN FIELD FIRE ALARM Dl HORN STROBE (CEILING MOUNT) ZH-MC-CW SIEMENS.. 4S DEEP BOX CEILING FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -CW SIEMENS 4S DEEP BOX CEILING A. F. F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A SYMBOLS LEGEND BE4 8100E JEW '1S HI.RF FIE1/IE TENANT SOACE / %].R WAICEN800KS 0 COOIVA 100-1 51 8100.0 AVON YERILO4 W.RELLSS WADE IN WASHI`IOION IIAR.ONAL UNIVERSITY OEAUTY 1WRK5 SEAIRS 10.00 1h% Flx1 LTrc.,Hlm M -LAV fra "'a"' HI41&ASj OESCN macys 4 LEVELS 250,407sf USN COSNERCS ARM EL K015 J C0E'W 6' Rik THE RARE ROSE L1141EL DISNEY STORE CNCUAR I ICING 91E1K SNOE5 f; FF�A�4 91.010 & 001/0 g 7,p;; 5 IN'ti0t 5 I I htO 18 GAGE AF'h aTANO 100% PURE #1395 / SPACE #356 T0K10 10850 01100<1/16 U OrrlY HCO 01880/1 JOLLIBCE 0/150 KING COUNTY LIORARY PAID MAY 29 2014 TUKWILA FIRE 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 z 0 w w w w Ch REV. BY: 0 m 0 z 0 w E U w w o SHOP DRAWINGS DATE 05/27/14 1� 1 Z 0 W co Z WCO O Ur W8coz cc < ItF2 w �z p C'WC/) CC O 2 z� O v� W L /C/) I- CO V% �CALE: NOT 1-1 0 Z 11.1 0) 0) TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE DATE:05/27/14 BACKROUND PLAN PROVIDED BY: WIRE DESIGNATION GENERAL NOTES SITE PLAN Gly Proprietary and Confidential, Copyright 2012 by Guardian Security Systems, Inc. All Rights Reserved .OB NUMBER: 8985-9 U� SHEET n FA -01} THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DUCK OVER 3' WIDE: SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. TUBE OUTLET SAMPLING TUBE INLET SAMPLING AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL 120VAC-6011Z — DEDICATED EMERGENCY NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PR60UCT DOCUMENTATION. *CONTACT RATINGS: 4.0A 0 125VAC 4.0A 0 30VDC TO NEXT ADDRESSABLE 14 TO DEVICE SP IF LAST DEVICE - TRIM TLCs CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVICE O O O 1] HTRI-R � O 0 0311 ®* o O N01E FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. C -CABLE C -CABLE 0 FROM PREVIOUS > (+) ADDRESSABLE > DEVICE (-) IXI Z 0 PAD -3 00 INPUT INPUT TROUBLE MCI W.C2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 0 0 0 3.6k EOL w a 0 (-) (+) 2 SPARE SPARE j SPARE (-) NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. (+) 0 WIRE DESIGNATION, NUMBEROFCONDUCTORS SIZE TYPE COLORCODE TWISTED PAIRWITH SHIELD #I8 FPLIFPLR RED (JACKET) *CONTACT RATINGS: 4.0A 0 125VAC 4.0A 0 30VDC FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. O 0 4 LJ I I HTRI-R I -I GROUND A 0 0 0 0 (+)> TO NEXT DEVICE OR (-) > STOP IF LAST DEVICE DRY CONTACTS TO VAV .--> FAN SHUTDOWN PROVIDED BY MECH/ELEC. DUCT DETECTOR, TEST SWITCH & RELAY MODULE WIRING DETAIL POWER SUPPLY & RELAY MODULE WIRING DETAIL (+) HORN STROBE OR STROBE ONLY 80" A.F.F. (OR UNLESS OTHERWISE SPEC FIED) 4S DEEP BOX HORN STROBE & STROBE WALL MOUNTING DETAIL + `J HORN/STROBE OR STROBE ONLY C) HORN/STROBE OR STROBE ONLY HORN/STROBE OR STROBE ONLY HONR STROBES & STROBES ONLY WIRING DETAIL TO NEXT DEVICE OR END ❑F LINE TYPICAL WIRING AND MOUNTING DETAILS CEILIN TILE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER TIN TEMPEJA RE: +32' F 0' C) TO 100 F (36 C) HUMIDITY: -9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN ( ) >-- DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR r DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW (-) (+) SMOKE DETECTOR WIRING DETAIL 00�0. QO♦00 0 0 SUPPORT BRIDGE 4" SQUARE DEEP BOX CEILING /- HORN STROBE / STROBE ONLY DROP CEILING MOUNTING HARD LID CEILING > TO NEXT ADDRESSABLE DEVICE SUPPORT BRIDGE 4" SQUARE DEEP BOX CEILING HORN STROBE STROBE ONLY HARD LID MOUNTING HORN STROBE & STROBE CEILING MOUNTING DETAIL "Svt , o4I4I," JUNCTI❑N BOX MOUNTED ON CEILING FLEX 4+,4'4'40,4" i JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT 0 OH O O I TO NEXT DEVICE CADDY BAR SMOKE/HEAT DETECTOR SUSPENDED ILLUMINATED CEILING SMOKE/HEAT DETECTOR MOUNTING DETAIL 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY:] 0 m D DESCRIPTION SHOP DRAWINGS DATE 05/27/14 2«a<a< coLLI co1 O U - I_ tra3 o fn0 O W 2z ccl cc w Q=- W ~ cc On Z LcoU)E 0) 4-CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE DATE:05/27/14 BACKROUND PLAN PROVIDED BY: \OB NUMBER: 8985-1i SHEET FA -02 Proprietary and Confidential, Copyright 2012 by Guardian Security Systems, Inc. All Rights Reserved :R P zk. r �<,� : d J,y�. ;`{ ,.,€. %# xi,'"•k�y �P .gi,j±,r33y, . N.3'"'L�', ls<"•� 1�1M1:3.',1p.?ziiY{4i'.;:'�^€ '��^>�':. yy{{::ee2i '�3 f,.Y � :YL>�, EY„s; <,<#k,2," ++�� ssd,. �ik'd, ..<"�i < � ,..� x! k3a'ss"�°7: i:v i1 `i.''.�,^'`}:"'✓' §ii?`�'y_.<i f��,�as.t. �,. ,..� k5 €��', .; F,/.; a.s<l;,.y;4: fi. '<}'�LhS ''85'Y `�"�` s .'mt� r, . PS`'S`wE' A..,4 c':ii u� Sd�,*w`�i{ kn„<t�y�., rf; �L.��1 a:utkC S<x`, } i?;+"'+'w€ v. ,:;€�.*5`d ��, �-,g,6��',E i`�%d9 �7','N'{3r4�ia `wn• e #,�F.ati� 3 r:s<�i?�L ,E, ��y .�.<ds'). � y x+t,�2;,�b5'A .hX>,v �< p S` :`,yb ''�S''n" (�^�.' «{'n�1 ', .%C „'dv, y< d .l$,:"•y3°' 'pe 4:"`. a'' rV�:g3),�?<m x§'' e$¢;� pi� w3 � i,vN `siv "4'' ' � .?�2.: r:*^a.�, ti.�, 'S j, �}, U ej, Y: ''/X r.; x> : kw : � s�tj ,.i( 5..'Y, vt"'f erz:,�-:,1.. , g A't. °Kr, 3S - � "#�; <x,.e �, is '#:i'; i.�51 ti,?k :d'ii"£., '?n �F `f !> xr�, x' ,#..s.ifi";; �'a'£i�"�.n� £s; x £'0.t i#3 � "dk'„'� ?r k^.ki'`yb.,"p�#'•'�`z 9'� j�f^,4.f 'r, aL3 ��i � "57 ra `” ".,^ ..,,,¢ .� '. 7.:'Y3 .? ;i^, �" dF;#',w0.',Yi eY' y+ y{jiy��"^Ya'' oi. .. ok'4 '2a ,j ��n r :'z � #', '#; ;� a l k C'. vk ,nt 3 4e rti5 ,`i ><,£ :;'45� ''� ,��,4il5<x,�, �,�Sb �^f"k`za`ur ,;� r�i `�`� ? S ` M,t F t z: t 1 WMNi4w ro 3 f DATE Current Load: Standby: Alarm: .:35ca`9s` ,,:�`. ;,+ y Yg,u<'j€;, , ::t ,, .x• ' My ,$}. {p is•�'#v'` .� t., ra r' Ya. {j.��y ,4.' NSA"'„ik !.:,Yx” q9� :>.^k'H:f?i; uy■{r�: 't�! VMM>Y 4:s'h,<. .nj .�' 3�k4x}�; r'J'.,�<,,{ ..; .r .�wa, .:(z,.y,Y,. >✓i<,v{i<..?�N�.�.,.��,. :4a, �<#g�, ,. r,.,,,, ,,.q...,k$+' , ., `a�P' `'k''r,.i ,}$ r'ke :5 x ..,r�!'�s >y.,V i•" 16 xrt � ;�, � '2 < ^Y rY' '>'S,'r^ *r S ^' 3 ,L; �, y&" ,.;b �: # :a' ?R,';` qua, > ;<., A% #S3 �" , Sseh'«f' "}tl'%:`,'yE: ,1 ,�1�I,. e. Na> e�� {�.s�`�.��' $4 :k' .Y,9.,Ak..z :. y,,, .s Y:..Y �i«u";U .:. �h,ny ,,<f ., ,r. .. ... � R>: ' k +>y' y#:�`!.<s,, ,, '�, w it'a r, < ph, :>'g'r X 3< yyy� ,;Y 3 ,. ":. Lix € Y AMM' M b,t ) , i .^'„ ,':Y+f, � >,.. ,r, s „ M' :#� s Device Type Qty Amps Total Amps Total HFP-11': ' 0.0022 - 0.0022 , 0.0023 0.000',. Qty AD2-P 1 0.0635 0.0635 0.064 0.064 HTR -R : :. > 2 0.009600 0.0096 0.021 0.042 Main System Board 1 0.03 0.03 0.030 0.030 ZH-1111C=CW @15CD 13 , ` : 0.0875 0.0731 Amps 0.106 Amps �5 5. FiI 'fi 'fi ✓wt, t rF' Y i � 1 � ,.� � , . �' �. k. � �,,. Y F 4 t } J 5t 31 '',<' Y' as t I q k 'N ✓ d2 g a�#. �' �'sia.k qW' '�✓ , .r :- �^,. ,, . . �' . , t ,n $"F` .. 3 { 59 0 � 5 d J { M 'Yn ..e�Y� .,.g �} S"� '¢'ke fk ';s i .�,a '3s y 1,�. •, s 4: S ` M,t F t z: t 1 WMNi4w ro 3 f DATE 05/27/14 .:35ca`9s` ,,:�`. ;,+ y Yg,u<'j€;, , ::t ,, .x• ' My ,$}. {p is•�'#v'` .� t., ra r' Ya. {j.��y ,4.' NSA"'„ik !.:,Yx” q9� :>.^k'H:f?i; uy■{r�: 't�! VMM>Y 4:s'h,<. .nj .�' 3�k4x}�; r'J'.,�<,,{ ..; .r .�wa, .:(z,.y,Y,. >✓i<,v{i<..?�N�.�.,.��,. :4a, �<#g�, ,. r,.,,,, ,,.q...,k$+' , ., `a�P' `'k''r,.i ,}$ r'ke :5 x ..,r�!'�s >y.,V i•" 16 xrt � ;�, � '2 < ^Y rY' '>'S,'r^ *r S ^' 3 ,L; �, y&" ,.;b �: # :a' ?R,';` qua, > ;<., A% #S3 �" , Sseh'«f' "}tl'%:`,'yE: ,1 ,�1�I,. e. Na> e�� {�.s�`�.��' $4 :k' .Y,9.,Ak..z :. y,,, .s Y:..Y �i«u";U .:. �h,ny ,,<f ., ,r. .. ... � R>: ' k +>y' y#:�`!.<s,, ,, '�, w it'a r, < ph, :>'g'r X 3< yyy� ,;Y 3 ,. ":. Lix € Y AMM' M b,t ) , i .^'„ ,':Y+f, � >,.. ,r, s „ M' :#� s . 1� «'Y• ,} .'oC jiY,t'..Czr::':�. t'.`•°'??Y': y �t iL �nh,,,v, ..,, .i.v; *;�5 ;:'...� ,ry;; j�; Device Type Qty Amps Total Amps Total Main System Board 1 0.03 0.03 0.030 0.030 ZH-1111C=CW @15CD 13 , ` : 0.0875 ZH-MC-CW @30CD 5 0.131 al -MC -CW @75CD 4 0.222 ZH-MC-CW ©95CD 0.292 71 -1 -HMC -CW ©11 CD 0.371 ZR -MC -CW @15CD 15 0.069 1.035 ZR -MC -W @15CD ` 0.064 0.03 Amps 1.065 Amps Standb CuCurrent,Load:`. y.03 Amps ' ' ' ' For 24 Hours = 0.720 Amp -hours Alarm Current Load: '1.065 Amps For 5 Minutes= 0.089 Amp -hours 25% Derating= 1.012 Amp -hours Total System Current Load: 1.012 Amp -hours dOs t;.£,y■£', F , q, * k' .', 9'iY3i yZyx �..a[�' k ,f fl d#'j.,,<yyq' s ft%,�: A: .fi i`4 4 {.i <,A5 A.'r' €'t`,6 �y'sY b# y ,',§'9li>M$fA y} Notification Appliance Circuit Detail PROJECT: 100% PURE Panel: EXISTING PAD -3 POWER SUPPLY Date: May 27, 2014 Wire Resistance 2.58 CURRENT TOTAL= 378.00 ZH-MC-CW @15cd 8 -MC-CW @30cc1 ZH-MC-CW @75cd YN= VIC' 95cct al -MC -CW @115cd ZR -MC -+CW @l5cd 222 2221 292 DEVICES , 3 TOTAL mA= 286 23.441 378 Total Wire Resistance R ota1 Device Load, Amps(I) Voltage Drop ( E ) EOL Voltage WL 2) R/ft 1.48 48 otai cet Load 0. 8: E_I.<._.,, 0.56 SYSTEM CALCULATIONS TO NEAREST EXISTING POWER SUPPLY TO NEAREST EXISTING DATA LOOP S S1-1 S1-2 Eivvv_EOL S1 S1-3 15cd 15cd 75cd FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. DUCT DETECTOR, RELAY MODULE FOR FAN SHUTDOWN & TEST SWITCH LOCATIONS TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. c igi 462 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4.990 TEL. (206) 622-6545 U) z 0 U) w w Q LU J LU CC IREV. BY: 0 m 0 DESCRIPTION SHOP DRAWINGS DATE 05/27/14 z <<<<< oc 0 0 w z CO LU Z W coc —J 0 CD rim, Z w o ccQJO 0 w �Z z )z d U) CDocw.' Z ICOR u- Cn I— LO M T 0 w F-- (/) >— (1) CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE SINGLE LINE DIAGRAM DATE: 05/27/14 BACKROUND PLAN PROVIDED BY: SOB NUMBER: 89857_1} SHEET FA -03 Proprietary and Confidential, Copyright 2012 by Guardian Security Systems, Inc. All Rights Reserved 11 TO NEAREST EXISTING POWER SUPPLY TO NEAREST EXISTING DATA LOOP S c 41 fir- -- ;�;'� STORAGE AREA 002 IMMO _J - • _J - _J MOO J EMERGENCY GRILLE RELEASE BUTTON WITH SIGNAGE WITH BRAILLE ALSO KEY LOCATION TO OPERATE GRILLE S1-1 12"D \4 S1-2 1 HDCP5cd RESTROOM Li�� SALES AREA 0011 EOL -�A"__� S1 S1-3 S1-3 75cd \ 7-7 NEW CLEAR 1/2"_ ANODIZED ALUM REVEAL 13)0 C17 KEY LOCATION TO OPERATE GRILL ----NEW CLEAR 1/2" ANODIZED ALUM REVEAL 3 g 71-Z 'I J SYMBOL LEGEND (E) PARTITION TO REMAIN r rr 3 5/8" 20GA MTL STUD FURRING W 5/8" TYPE 'X' GWB AT EXPOSED SIDES 'TL�l.T1A (N) FULL HIEGHT PARTITION 35/8' 20 GA METAL ENDS @16" O.C. W/ %TYPE 'X' GYP BOARD BOTH SIDES; FIRE CAULK AND TAPED METAL SIGN BOX/ROLL DOWN GRILLE POST CLADDING CONSTRUCTION KEY NOTES () (N) ROLL DOWN GRILL C?) 3) (N) ILLUMINATED SIGN BOX BY SIGN VENDOR. LEASE LINE (N) TELEPHONE BACKBOARD (N) ELECTRICAL PANEL (N) POST FOR ROLL -DOWN GRILLE RAIL SUPPORT SINK - KOHLER KATHRYN #K -2297-G FAUCET - GROHE ALLURE #20191-000 G.C. TO PROVIDE BACKING FOR WALL STANDARDS RECESSED WALL STANDARDS BY VISPLAY SYSTEM, SEE SHEET A-6.2 (N) TEMPERED BUTT -JOINED GLASS -1/2" STAR FIRE T.G. 01) NON- ILLUMINATED GRAPHIC. (•th'') RECESSED LIGHT BOX FOR ILLUMINATED GRAPHIC . 13) 7" ANTIQUE WHITE OAK CLADDING EXTENSION. C1� FIRE ALARM SYSTEM PLAN MELANINE SHELVING 12" DEEP WITH SURFACE MOUNTED STANDARDS 6' LONG, G.C. TO PROVIDE BACKING FOR STANDARDS EMPLOYEE LOCKERS 1 TIER 4 LOCKERS EXTEND (E) NEUTRAL PIER AS REQUIRED FOR (N) STOREFRONT PROJECTION. EXISTING EXPANSION JOINT TO REMAIN BARRICADE FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. DUCT DETECTOR, RELAY MODULE FOR FAN SHUTDOWN & TEST SWITCH LOCATIONS TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS IREV. BY: 1 0 m 0 DESCRIPTION SHOP DRAWINGS DATE 05/27/14 2 co z w o0oo o 01- P SS upcnz Er Q w z J1 nD Q_ cc I w. ) 0 Z� <1— w� cc o� LLC - 0) M W CC �CALE: 1/4"=1'0" DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE DATE: 05/27/14 BACKROUND PLAN PROVIDED BY: ,JOB NUMBER: 8985-I) r SHEET FA -04 Proprietary and Confidential, Copyright 2012 by Guardian Security Systems, Inc. All Rights Reserved