PP - 1076 SOUTHCENTER MALL - BEACH WORKS - PERMITS AND PLANS
1076 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-342 08-F-252 08-S-339 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Vanilla Shell 1076 Southcenter Mall Permit No.: 08-S339 Date: June 18, 2008 Reviewer: Steve Kohler Fire Inspector/Plan Review (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. 11. SUt1 ma ` '"`' " ' e`' ""` ""'` Job Number:IHydraulic Report Description: Ordinary Group II Job" -n Job Number KS0407 Design Engineer Adam Kanter Job Name Vanilla Shells State Certification/License Number WESTESF136QF Address 1 Southcenter Mall AHJ City of Tukwila Address 2 Job Site Southcenter Mall Cdy State Zip Code Tukwila Wa 98188 Drawmg Name FP-1-1076.cad System... { Remote Area(s) Most Demanding Spnnkler Data 5.6 K -Factor 26.00 at 21.556 Occupancy Ordinary Group II Hose Allowance At Source 250.00 Densly Area of Application 0.20gpm/ft2 990.00ft2 (Actual 1036.90ft2) Additional Hose Supplies Node Flow(apm) --- —_ -_ Number Of Sprinklers Calculated Coverage Per Sprinkler 15 130.00ft2 AutoPeak Results Pressure For Remote Area(s) Adjacent To Most Remote Area ii /A417.62 Total Hose Streams — — — — — 250.00 System Flow Demand Total Water Required (Including Hose Allowance) 667.62 Maximum Pressure Unbalance In Loops 0.000 sirs-/• l � \� C' ' ..a. Nir � 1� R ,�0 "re Maximum Velocity Above Ground 26.18 between nodes 106 and 155 Maximum Velocity Under Ground 1.58 between nodes 1 and 325 Volume capacity of Wet Pipes Volume capacity of Dry Pipes 2052.87ga1 1.22ft3 .j, ;a,. 5 ..PP. -.,.. � �..... _..- :t—y:.i.. ,:-s:x— _.. .��� �,w�<_.. tier��='>=i� : .... _�.., Hose Flow Static Residual Flow Node (gpm) (psi) (psi) (gpm) Available @ Total Demand Required Safety Margin (psi) (gpm) (psi) (psi) 1 250.00 140.000 20.000 10900.00 1 139.316 667.62 91.773 47.543 Contractor,* h a ,. Contractor Number KS0407 Contact Name Contact Tito Adam Kantner Project Manager Contractor Name Western States Fire Protection Phone Extension 425.881.0100 Address 1 7102 180th Ave Ne, Suite A-105 FAX 485.736.9032 Address 2 E-mail Cdy State Zip Code Redmond WA 98052 Web -Ste (, ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 06/17/2008 8:22:11 AM Page 1 i f Summary Of.Outflow ng De c4" Job Number: KSO407 Report Description: Ordinary Group II Actual Flow Minimum Flow K -Factor Pressure Device (gpm) (gpm) (K) (psi) Sprinkler 115 29.18 26.00 5.6 27.151 Sprinkler 118 30.04 26.00 5.6 28.776 Sprinkler 113 28.46 26.00 5.6 25.824 Sprinkler 111 27.78 26.00 5.6 24.606 Sprinkler 110 27.37 26.00 5.6 23.885 Sprinkler 116 29.24 26.00 5.6 27.263 Sprinkler 109 27.25 26.00 5.6 23.680 Sprinkler 108 27.04 26.00 5.6 23.313 Sprinkler 107 26.94 26.00 5.6 23.147 Sprinkler 103 26.23 26.00 5.6 21.938 Sprinkler 112 27.83 26.00 5.6 24.702 Sprinkler 114 28.86 26.00 _ 5.6 26.551 b Sprinkler 101 26.00 _ 26.00 5.6 21.556 Sprinkler 102 26.13 26.00 5.6 21.765 Sprinkler 117 29.28 26.00 5.6 27.345 c Most Demanding Sprinkler Data M.E.P.CAD, Inc. 4AutoSPRINK® VR5 v5.2.6 06/17/2008 8:22:14AM Page 2 111 Job Number: KS0407 Report Description: Ordinary Group II Node Elevation(Foot) Fittings Pressure(psi) Discharge(gpm) 104 15-0 2P0(8-0) 48.807 105 15-0 2P0(8-0) 48.531 106 15-0 2P0(8-0) 2P0(5-0) 48.439 38.134 155 15-0 165 15-0 P0(5-0) 37.876 168 15-0 P0(5-0) 34.017 156 15-0 2P0(5-0) 33.593 179 15-0 P0(5-0) 35.899 182 15-0 P0(5-0) 31.209 171 15-0 P0(5-0) 31.842 172 15-0 P0(5-0) 31.686 190 15-0 P0(5-0) E(2-0) 29.865 183 15-0 31.514 199 15-0 P0(5-0) 34.968 29.492 200 15-0 P0(5-0) 211 15-0 P0(5-0) E(2-0) 29.487 34.829 216 15-0 201 15-0 fEE(3-5) 67.349 202 16-1 fEE(3-5) 67.206 203 14-0 fE(6-91/2) 70.115 204 16-1 fE(6-9%) BFP(-4.500) 68.599 88.281 325 3-10% 350 1-11 P0(37-8%) 84.539 354 14-0 fE(10-0) 78.788 365 1-11 LtE(16-0) 84.569 27.151 115 14-0 Spr(-27.151) 29.18 118 14-0 Spr(-28.776) 28.776 30.04 113 14-0 Spr(-25.824) 25.824 28.46 111 14-0 Spr4.606) 24.606 23.885 27.78 110 14-0 Spr(-23.885) 27.37 116 14-0 Spr(-27.263) 27.263 29.24 109 14-0 Spr(-23.680) Spr(-23.313) Spr(-23.147) 23.680 23.313 27.25 27.04 108 14-0 107 13-6 23.147 26.94 103 1 13-6 Spr(-21.938) 21.938 26.23 112 13-6 Spr(-24.702) Spr(-26.551) 24.702 26.551 27.83 114 14-0 , 28.86 , 101 13-6 ' Spr(-21.556) 21.556 21.765 26.00 , 102 13-6 S_prj21.7651 26.13 117 13-6 Spr(-27.345L27.345 , 29.28 1 -4-0 S 91.773 417.62T ge M .E. P .CAD, Inc. AutoSPRINK® VR5 v5.2.6 06/17/2008 8:22:16AM Page 3 li Hy d1744PC Ani" al ` "i» :;_ ;.; Job Number: KS0407 Report Description: Ordinary Group I1 Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq. Length Summary Upstream Total Length Gil Route 1 DR 1.049 0=26.00 9.65 C=120 0.211435 29-6Y2 Pf 8.573 101 13-6 q=26.00 K=5.6 21.556 Spr(-21.556) 11-0 Pe -0.638 200 15-0 29.492 3E(2-0), PO(5-0) 40-6% Pv BL 1.610 0=52.13 8.21 C=120 0.095051 3-11 Pf 0.373 200 15-0 29.492 Pe -0.000 190 15-0 29.865 3-11 Pv BL 1.610 0=78.35 _ 12.35 C=120 0.2.02038 6-8 Pf 1.345 190 15-0 29.865 Pe 0.000 182 15-0 31.209 6-8 Pv BL 1.610 0=105.61 16.64 C=120 0.350940 8-0 Pf 2.808 182 15-0 31.209 Pe 168 15-0 34.017 8-0 Pv BL 1.610 0=134.06 21.13 C=120 0.545676 14-7 Pf 14.514 168 15-0 34.017 12-0 Pe 105 15-0 48.531 2LtE(2-0), PO(8-0) 26-7 Pv CM 4.260 Q=300.20 6.76 C=120 0.021215 13-0 Pf 0.276 105 15-0 48.531 ' Pe 104 15-0 48.807 13-0 Pv CM 4.260 Q=41.7.62 9.40 C=120 0.039073 350-4'/z Pf 18.542 104 15-0 48.807 47-5 Pe 201 15-0 67.349 2cplg(-1.500), 4Ee2(5-3), PO(26-4) 397-9 Pv RN 4.260 0=417.62 9.40 C=120 0.039073 1-6Y2 Pf 0.327 201 15-0 67.349 fEE(3-5) 6-10 Pe -0.470 202 16-1 67.206 fEE(3-5) 8-4Yz Pv CM 4.260 0=417.62 9.40 C=120 0.039073 35-8 Pf 1.393 202 16-1 67.206 Pe -0.000 204 16-1 68.599 35-8 Pv RN 4.260 Q=417.62 9.40 C=120 0.039073 2-1 Pf 0.613 204 16-1 68.599 fE(6-9%) 13-7 Pe 0.903 203 14-0 70.115 fE(6-9%) 15-8 Pv CM 4.260 0=417.62 9.40 C=120 0.039073 205-2 Pf 8.673 203 14-0 70.115 16-9Yz Pe 0.000 354 14-0 78.788 fE(6-9Y2), fE(10-0) 221-11% Pv FM 6.357 Q=417.62 4.22 C=120 0.005562 11-1Yz Pf 0.516 354 14-0 78.788 81-8% Pe 5.235 350 1-11 84.539 CV(40-3), GV(3-9Yz), P0(37-8%) 92-10 Pv FM 8.329 Q=417.62 2.46 C=120 0.001492 3-7 Pf 0.029 350 1-11 84.539 16-0 Pe -0.000 365 1-11 84.569 LtE(16-0) 19-7, Pv FM 10.420 0=417.62 1.57 C=120 0.000501 26-5Y: Pf 4.555 365 1-11 84.569 83-0 Pe -0.842 325 3-10% 88.281 4LtE(16-0), BV(19-0), BFP(-4.500) 109-5% Pv UG 10.400 Q=417.62 1.58 C=140 0.000380 109-2 Pf 0.084 325 3-10,4 88.281 111-7 Pe 3.407 1 -4-0 91.773 E(35-1), 3LtE(25-6), S 220-9Yz Pv ao Route 2 DR 1.049 Q=26.13 9.70 C=120 0.213328 28-3 Pf 8.369 102 13-6 q=26.13 K=5.6 21.765 Spr(-21.765) 11-0 Pe -0.647 211 15-0 29.487 3E(2-0), PO(5-0) 39-3 Pv BL 1.610 0=26.13 4.12 C=120 0.026484 0-2 Pf 0.005 211 15-0 29.487 Pe -0.000 200 15-0 29.492 0-2 Pv w Route 3 DR 1.049 0=26.23 9.74 C=120 0.214899 28-10 Pf 8.564 103 13-6 q=26.23 K=5.6 21.938 Spr(-21.938) 11-0 Pe -0.638 190 15-0 29.865 3E(2-0), PO(5-0) 39-10 Pv v Route 4 DR 1.049 Q=26.94 10.00 C=120 0.225831 29-714 Pf 9.176 107 13-6 q=26.94 K=5.6 23.147 Spr(-23.147) 11-0 Pe -0.638 172 15-0 31.686 3E(2-0), PO(5-0) 40-7Y: Pv BL 1.610 0=54.77 8.63 C=120 0.104180 1-6 Pf 0.156 172 15-0 31.686 Pe 171 15-0 31.842 1-6 Pv BL 1.610 0=81.81 12.89 C=120 0.218845 8-0 Pf 1.751 171 15-0 31.842 Pe 156 15-0 33.593 8-0 Pv BL 1.610 0=136.96 21.58 C=120 0.567688 8-0 Pf 4.542 156 15-0 33.593 Pe 155 15-0 38.134 8-0 Pv BL 1.610 0=166.14 26.18 C=120 0.811498 4-8Y Pf 10.304 155 15-0 38.134 8-0 Pe 106 15-0 48.439 P0(8-0) 12-8% Pv © M.E.P.CAD, Inc. +AutoSPRINK® VR5 v5.2.6 06/17/2008 8:22:18AM Page 4 IV ly,*-4u-lio::A6411i4i*.li: ,e_--,;::;-- 1 Job Number: KS0407 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq. Length Summary Upstream Total Length CM 4.260 Q=166.14 3.74 C=120 0.007101 13-0 Pf 0.092 106 15-0 48.439 Pe 105 15-0 48.531 13-0 Pv Gi Route 5 DR 1.049 0=27.04 10.04 C=120 0.227327 28-41/2 Pf 8.950 108 14-0 q=27.04 K=5.6 23.313 Spr(-23.313) 11-0 Pe -0.421 171 15-0 31.842 3E(2-0), P0(5-0) 39-4% Pv Gi Route 6 DR 1.049 0=27.25 10.12 C=120 0.230637 25-5% Pf 7.950 109 14-0 q=27.25 K=5.6 23.680 Spr(-23.680) 9-0 Pe -0.421 182 15-0 31.209 2E(2-0), P0(5-0) 34-5% Pv ei. Route 7 DR 1.049 Q=27.37 10.16 C=120 0.232480 32-7 Pf 10.129 110 14-0 q=27.37 K=5.6 23.885 Spr(-23.885) 11-0 Pe -0.421 156 15-0 33.593 3E(2-0), P0(5-0) 43-7 Pv Gi Route 8 DR 1.049 Q=27.78 10.31 C=120 0.238962 28-4% Pf 9.408 111 14-0 q=27.78 K=5.6 24.606 Spr(-24.606) 11-0 Pe -0.421 156 15-0 33.593 3E(2-0), P0(5-0) 39-4% Pv Route 9 DR 1.049 0=27.83 10.33 C=120 0.239826 25-1 Pf 7.450 112 13-6 q=27.83 K=5.6 24.702 Spr(-24.702) 6-0 Pe -0.638 183 15-0 31.514 3E(2-0) 31-1 Pv BL 1.610 Q=27.83 4.39 C=120 0.029774 5-9% Pf 0.172 183 15-0 31.514 Pe 172 15-0 31.686 5-9% Pv ii Route 10 DR 1.049 0=28.46 10.56 C=120 0.249888 25-5Y2 Pf 8.614 113 14-0 q=28.46 K=5.6 25.824 Spr(-25.824) 9-0 Pe -0.421 168 15-0 34.017 2E(2-0), P0(5-0) 34-51,4Pv ai Route 11 DR 1.049 Q=28.86 10.71 C=120 0.256390 25-5% Pf 8.838 114 14-0 q=28.86 K=5.6 26.551 Spr(-26.551) 9-0 Pe -0.421 199 15-0 34.968 2E(2-0), P0(5-0) 34-5% Pv BL 1.610 Q=58.14 9.16 C=120 0.116328 8-0 Pf 0.931 199 15-0 34.968 : Pe 179 15-0 35.899 84 Pv BL 1.610 Q=87.38 13.77 C=120 0.247182 8-0 Pf 1.977 179 15-0 35.899 Pe 165 15-0 37.876 8-0 Pv BL 1.610 Q=117.42 18.50 C=120 0.427003 13-7 Pf 10.931 165 15-0 37.876 12-0 Pe 104 15-0 48.807 2LtE(2-0), P0(8-0) 25-7 Pv eio Route 12 DR 1.049 0=29.18 10.83 C=120 0.261745 32-7 Pf 11.404 115 14-0 q=29.18 K=5.6 27.151 Spr(-27.151) 11-0 Pe -0.421 155 15-0 38.134 3E(2-0), P0(5-0) 43-7 Pv a, Route 13 DR 1.049 0=29.24 10.85 C=120 0.262741 25-5% Pf 9.057 116 14-0 q=29.24 K=5.6 27.263 Spr(-27.263) 9-0 Pe -0.421 179 15-0 35.899 2E(2-0), P0(5-0) 34-5Y2 Pv a. Route 14 DR 1.049 0=29.28 10.87 C=120 0.263477 24-10 Pf 8.122 117 13-6 q=29.28 K=5.6 27.345 Spr(-27.345) 6-0 Pe -0.638 216 15-0 34.829 3E(2-0) 30-10 Pv BL 1.610 Q=29.28 4.61 C=120 0.032710 4-3 Pf 0.139 216 15-0 34.829 Pe 199 15-0 34.968 4-3 Pv a. Route 15 DR 1.049 0=30.04 11.15 C=120 0.276204 25-5% Pf 9.521 118 14-0 q=30.04 K=5.6 28.776 Spr(-28.776) 9-0 Pe -0.421 165 15-0 37.876 2E(2-0), P0(5-0) 34-5% Pv aeldiValeil(PiPe Lefigthebt:VON4rincirtttifigs (OF-7)2ffiinlY)MM& OValtie„MatiplieA Value Of C 100 130 140 150 Multiplying Factor 0.713 1.16 1.33 1.51 Actual Inside Diameter ) Factor 487 Schedule 40 Steel Pipe Inside Diameter = M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 06/17/2008 8:22:18AM Page 5 Hydraulic ;Analysis Job Number: KS0407 Report Description: Ordinary Group II Pipe Type Downstream Upstream Diameter Elevation Flow Discharge Velocity HWC K -Factor Pt Friction Loss Pn Fittings Length Pressure Eq. Length Summary Total Length `.Pipe Type Legend, Units Legend Fittings Legend AO Arm -Over Diameter BL Branch Line Elevation CM Cross Main Flow DN Drain Discharge DR Drop Velocity DY Dynamic Pressure FM Feed Main Length FR Feed Riser Friction Loss MS Miscellaneous HWC OR Outrigger pt RN Riser Nipple Pn SP Sprig Pf ST Stand Pipe Pe UG Underground Pv Inch Foot gpm gpm fps psi Foot psVFoot Hazen -Williams Constant Total pressure at a point in a pipe Normal pressure at a point in a pipe Pressure loss due to friction between points Pressure due to elevation difference between indicated points Velocity pressure at a point in a pipe ALV Alarm Vaive AngV Angle Valve b Bushing BalV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Turn 90° cplg Coupling Cr Cross Run CV Check Valve DeIV Deluge Valve DPV Dry Pipe Valve E 90° Elbow EE 45° Elbow Eel 11%° Elbow Ee2 22W Elbow f Flow Device FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow flg Flange FN Floating Node fT FireLock(TM) Tee g Gauge GIoV Globe Valve GV Gate Valve Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PrV Pressure Relief Valve PRV Pressure Reducing Vaive red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 06/17/2008 8:22:18AM Page 6 li f , : f t.: > ' _'; : Hydraulic Graph; �;�;;3���>u����;�,a��:-��m:�; Job Number: KSO407 Report Description: Ordinary Group II Supply at Node 1 150 :Static 135 Pressure 140.000 120 105 Ja667.62 90 with hose @ 91.773 streams -j417.62 .y a Ec 75 N N N a 60 :System demand curve 45 30 10900.00 @ 20.000 15 0 W1J11I11111 11111 1 1 11 1 1 1 1 1 1 1 1 I 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 I 1 1 1 1 1 1 1 1 1 11 1 1 1 1 1 I 1 1 1 1 1 1 1 1 1 1 111111111 910022W 3300 4400 5500 6600 7700 8800 9900 11000 Water flow, gpm Hydraulic Graph Supply at Node 1 Static Pressure 140.000 Residual Pressure 10900.00 @ 20.000 Available PressureTime of Test 139.316 @ 667.62 System Demand 417.62 @ 91.773 System Demand (Including Hose Allowance) 667.62 @ 91.773 dA, © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 06/17/2008 8:22:23AM Page 7 NS Job Number: KS0407 Report Description: Ordinary Group II k,© M.E.P.CAD, Inc. alAutoSPRINK® VR5 v5.2.6 06/17/2008 8:22:26AM Page 8 BEACH WO FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SH =ET \U V.3E. SHEET TITLE FA -01 SYSTEM I\FOMATIO\ FA -02 TYPICAL DETAILS - WRI\G A\3 v O U \TI \IC FA -03 FRE ALAV SYSTEV FLOG PLAN FA -04 SYSTEM CALCULATIONS r G SIT - SLA WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATION SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH .SHIELD #16 FPL/FPLR -RED (JACKET) H DOOR -HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIAT❑R TWISTED PAIR W/ SHIELD .#16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED. (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWD #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWD #14 FPL/FPLR RED (JACKET). CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CF -IP. 9,. TABLE 4, SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING -DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP: 1. DETECTOR .,AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED, NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY --HAVING JURISDICTION. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE; FITTINGS, HANGERS, STANDARD BOXES,. FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT; AIR STREAM OF AIR . SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO ,CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF -NEPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED. BRANCH POWER SOURCES.. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT. DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE vIOUNTED AT 48" A F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED :UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS CO1IPLETE AND FINAL: EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JJRISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR: TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7: 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. . 17. ALL WIRING SHALL - BE - METERED; VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS. BETWEEN CONDUCTORS :AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM.. 18_. ALL CABLES SHALL BE MARKED AS INDICATED-. ON FIRE ALARM' RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP.' 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS, FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT)' WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 3 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP n INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD B LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD l/4 SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING ® DUCT SMOKE D DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11. W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING F FIRE ALARM SPEAKER STROBE L C (CEILING MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET-MC=W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING L FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING L FIRE ALARM STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. Q C FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX W/ 1-1 /2" EXT. CEILING FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM B IQ STROBE WP (WEATHERPROOF) SET -W SIEMENS - 4S DEEP BOX - W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -S17 -WP SIEMENS MT -SUR -BOX 1/2" PIPE VERIFY IN. FIELD MR MULTI -VOLTAGE CONTROL RELAY MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD a MAGNETIC DOOR HOLDER. F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JBEIX FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD A.F.F. JUNCTI❑N BOX F.B.O. N/A VERIFY IN - FIELD ABOVE FINISHED FLOOR N/A N/A N/A F.B.❑. FURNISHED BY N/A N✓A Without Corliirh@nts N/Ad TUKWILA FIRE DEPARTI Alt, Please call: 575.4402 and give this job No. and exact address for shute iown or restoration approvallw 4:7 cL TEL. (206) 622-651+5 rn z 0 uJ OJ, Q uJ J r CO LIJ z DESCRIPTION SHOP DRAWINGS LU cm 0 co U3 0 z OTICE , signed, Tukwi'lti rtment Pre-test rust be presented spector prior to gent of Acceptance any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved CO co Q0) Z CCW 0 Q u,H0 F...< O 1- ct Z (CALE: 1 /8"=1 ' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/1 6/08 BACKROUND PLAN PROVIDED BY: .10B NUMBER: FA-ET 01 "'nL"'' --1"El As Noted In Red N/A NOT APPLICABLE N/A N/A 0 Per The Att1 Rd Letter N/A i nese plans have been reviewed by The Tukwila Fire U,❑,N, UNLESS OTHERWISE NOTED N/A Pregtion Bureau for confo ce with current city N/A standards. Acceptance is iect to errors and omissionh do not authorize violationsof adopted WP WEATHERPROOF DEVICE N/A st*t {as and ordinances. -Al responsibility for the N/A adequacy of design rests totally with the designer. Additions, deletiorls or revisions to these drawings RED AS BUILT ADD OR CHANGE N/A attcr thiN e will void this accepi�rpr and will require a N/A resubmittal of revised drawings for subsequent approval. N A complete, GREEN AS BUILT REMOVE N/A Fir jracceptance is subject 402Aid test and inspectiofilkip The Tukwila Fire Prevention Bureau. Fire Depz Certificate! to the In BLUE AS BUILT NOTES TO CAD N/A Dates' By:N/A 0200 NSA commencen Testing o' TUKWILA FIRE DEPARTI Alt, Please call: 575.4402 and give this job No. and exact address for shute iown or restoration approvallw 4:7 cL TEL. (206) 622-651+5 rn z 0 uJ OJ, Q uJ J r CO LIJ z DESCRIPTION SHOP DRAWINGS LU cm 0 co U3 0 z OTICE , signed, Tukwi'lti rtment Pre-test rust be presented spector prior to gent of Acceptance any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved CO co Q0) Z CCW 0 Q u,H0 F...< O 1- ct Z (CALE: 1 /8"=1 ' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/1 6/08 BACKROUND PLAN PROVIDED BY: .10B NUMBER: FA-ET 01 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND IS❑LATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR S+ PREVIOUS ADDRESSABLE DEVIL 0 DUCT DETECTOR L❑CATI❑N 0 END OF LINE DEVICE(3.6K 1/4W) m SUPERVISED SWITCH GROUND 0 0 HTRI-R OSTATUS LED 0o 0 N.O. 0 m COM N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. O TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVIOUS ADDRESSABLE DEVICE TO NEXT ADDRESSABLE E DEVICE L + NOTE 11 VOLTAGE MAX - CURRENT MAX, - CONT. RES. MAX, - MAX, CABLE LENGTH - C (LINE TO LINE) - C CLINE TO SHIELD) - MAX. LINE SIZE - MIN. LINE SIZE - MUSIC OUTLET SAMPLIN TUBE INLET SAMPLIN TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE 1 -AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE j STOP IF LAST DEVICE 1(-� FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVICE 1( i RELAY CONTACTS (4.OA @ 125VAC) (4.0A @ 30VDC) 27 VDC 3,5 mA DURING POLLING 10 OHMS 200 FT, (18 AWG) 0.02uF 0,04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTI❑N. 0 Inial TB1 123456 TB2 C 6) 6) +- 654321 END OF LINE DEVICE (3.6K 1/4W) 0 Pr SUPERVISEII_____" / SWITCH GROUND NOTE: 0 0 HTRI-D bTATUS LED 00 m NOT USED 0 � O o FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCA<E (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC LL JJ 7—r T T 1-] 0 PAD -3 0 00 0 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 0 m B 24K n + TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE END OF LINE DEVICE 3.6K 1/4W) SUPERVISED SWITCH 2 NAC -4 NAC -3 NAC -2 NAC -1 ins NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE ++ DEVICE LOOP NOT USED REMOTE DEVICE LOOP .� 0 0 (a 0—r FROM XLS CONTROL PANEL OR (+)y PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY C'S' CABLE) FROM 'FACP (V❑ICE CIRCUIT) ('V' CABLE) 470 OHMS �1N EOL 0 O TC INPU (+ 1?--) 9 9 9 TEM -1 Q • • • • 1 OQCO TYPICAL AD2-P DUCT SMOKE DETECTOR -WIRING DETAIL SCALE: NOPE (+) () STROBE SPEAKER (±) (-) (S (-) STROBE EARTH GROUND 0 —).(+)TO NEXT DEVICE OR > (-) STOP IF LAST DEVICE (+) SPEAKER (-) SPEAKER/STROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE - OR STROBE ONLY 80" A.F.F. 45 DEEP BOX W/ 1-1 /2" EXTENSION RING (SPEAKER STROBE) 45 BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM'DEVICE MOUNTING ELEVATIONS SCALE:NONE TO NEXT DEVICE OR END OF LINE TO NEXT DEVICE OR END OF LINE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER TIN TEMPERATURE: +32' F 0' C) TO 100' F (338' C) HUMIDITY: 9 X RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR DEVICE IS USED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR IDB -11 STANDARD r SMOKE DETECTOR BASE FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (-) > �DATA IN(+)> REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT DEVICE 41 > ( ) DATA OUT (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID —\ CEILING SPEAKER SUPPORT BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSI❑N '\ CEILING MOUNTED. SPEAKER/STROBE \ CEILING MOUNTED SPEAKER/STROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTI❑N BOX MOUNTED ON \\ CEILING FLEX \ JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT / / / / 0 0 ; TO NEXT DEVICE 0 0 CADDY BAR SMOKE DETECTOR --- SMOKE DETECTOR MOUNTING SCALE=NONE SUSPENDED ILLUMINATED CEILING DO NOT INST LL ADDRESS ,BLE 0 \ ITOATI NG DEVICES PRE iOG A:VED WITH DEVICES ADDRESS. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved Z 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS z w DESCRIPTION SHOP DRAWINGS w 0 co 0 0 z C C 00 00 Q 0) :EZ w rro O i -O 2w= („) a W LT co — CO D H V z F— z J 0 0 z 0 Z J \ ./t. 2 (SCALE: 1/8"= ' DRAWN BY: I -ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/16/08 BACKROUND PLAN PROVIDED BY: 9B NUMBER: SHEET FA -02 NORTH EOL—S1 20.02V 2S,2V c>-2S,2V 2S,2V 4 0;* 30 2S,2V Ar,t4WANYCOVAI acaiSoNgig,IM 75 2S,2V 75 BEACH WORKS WESTFIELD SOUTHCENTER MALL SCALE 118'1=1' FLAG \ OTES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE, FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATION SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR, SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLATOR FIRE SUPPRESION SYSTEM, FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NO NS AL_ ADDR_SSABLI INMATIN DEVICES UNTIL PREPROGRAMMED W TH DEVICES ADDR SS. G Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 j 0 5 uJ ci uJ LU uJ cr z 0 uJ SHOP DRAWINGS LU LU F -- op 0 to 0 z CO CO —J !L- W .0 2 Z cc 0 oLij CD ZZ > 2 WI CC C.) co 5 F.< < c°5 Wco- uI 1.8 ALE: 1 /8"= 1 DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE: 6/1 6/08 BACKROUND PLAN PROVIDED BY: \J..013 NUMBER: c 1 SHEET FA -039 iJ B --7 1MIIIJ I 1 SYSTEM CALCULATIONS BATTERY SIZING CALCULATION L. PROJECT: Panel: Date: Notification Appliance Circuit Detail HELD SOUTHCENTER MALL BEACH'WORKS June 1'04.-2008 z O LU CC w U) w J W Wire Resistance 1. CURRENT TOTAL= 610 CIRCUIT: QTY Alarm Current 64 i i NORTH 0 SET -MC ©75CD SET -MC @1 10CD SETHMCC@115CD SET-HMC-C@177CD 98 175 233 318 445 318 Alarm Total Were Size Wire Length Voltage at EOL 196 350 0 N `{ \\ �� \\\`\ k- \ L_� 1 \\'\ \\\ \\\ Total Wire Resistance (R (WL*2)*(Rift) Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E) (E= I* R) EOL Voltage (20.4-E) BEACH WORKS WESTFIELD SOUTHCENTER MALL SCALE 1132"=1' 75 C 75 C 30 30 C 15 EX RISER DIAGRAM S L.; -1- DEVICES= PROJECT: Panel: Date: CIRCUIT: QTY Z-MC@30C D SET -MC -C W@110C D 5 TOTAL m A= 20.0225076 Notification Appliance Circ uit Detail WESTFIELD SOUTHCENTER MALL BEACH: WORKS June 16, 2008 SPEAKER CIRCUIT Device Type 70.7V1/8 Alarm Current 1.8 0 0 0 0 0 0 Wire Resistance x.58 CURRENT TOTAL= 7.2 Alarm Total Wire Size Wire Length Voltage at EOL Total Wire Resistance (R ) (WL*2)*(Rift) Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E ) (E=I*R) EOL Voltage (20.4 - E) DEVICES= TOTAL mA= 20.39290397 VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved >- m w z DESCRIPTION N z a 0 0 c0 W O C C C J 03 co T Q 0) cc Wopo o P -2C3 zz 5, cc o I2 Q o W j co - m p r� 1 - CC W I-- C) SCALE: 1 /8"=1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/1 6/08 BACKROUND PLAN PROVIDED BY: \:0B NUMBER: SHEET FA -04 , BEACH WORKS BEACH WORKS FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations Current Load: Standby: Alarm: Current Load: Standby: Alarm: Device Type Qty Amps Total Amps Total Device Type Qty Amps Total Amps Total HFP-11 0,0022 0.0022 0.0023 AD2-P 1 0.0635 0.0635 0.064 0.064 Main System Board 1 0.03 0.03 0.030 0.030 HTR -R 2 0:009600 0.0096 0.021 0.042 SET -MC @15CD 0.064 HTRI-D ° 0.001600 0.0035 SET -MC @30CD 2 0.098 0.196 ICP -B6.- ._ 0.005 SET -MC @75CD 2 0.175 0.350 SET -MC @110CD 0.233 SET HMC-C@115CD 0.318 SET HMC-C@135CD 0.318 0.0731 Amps 0:106 Amps SET HMC-C@185CD ZR -MC @15CD 1 0.445 0.064 0.064 Standby Current Load:' 0.0731 Amps For 24 Hours = 1.754 Amp -hours ZR -MC @3OCD 0.098 HCP 0.0015 Alarm Current Load: 0.106 Amps For 5 Minutes= 0.009 Amp -hours 0.03 Amps 0.64 Amps 25% Derating= 2.204 Amp -hours Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours Total System Current Load: Alarm Current Load: 0.64 Amps For 5 Minutes= 0.054 Amp -hours 2.204 Amp -hours 25% Derating= 0.967 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.967 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULATION L. PROJECT: Panel: Date: Notification Appliance Circuit Detail HELD SOUTHCENTER MALL BEACH'WORKS June 1'04.-2008 z O LU CC w U) w J W Wire Resistance 1. CURRENT TOTAL= 610 CIRCUIT: QTY Alarm Current 64 i i NORTH 0 SET -MC ©75CD SET -MC @1 10CD SETHMCC@115CD SET-HMC-C@177CD 98 175 233 318 445 318 Alarm Total Were Size Wire Length Voltage at EOL 196 350 0 N `{ \\ �� \\\`\ k- \ L_� 1 \\'\ \\\ \\\ Total Wire Resistance (R (WL*2)*(Rift) Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E) (E= I* R) EOL Voltage (20.4-E) BEACH WORKS WESTFIELD SOUTHCENTER MALL SCALE 1132"=1' 75 C 75 C 30 30 C 15 EX RISER DIAGRAM S L.; -1- DEVICES= PROJECT: Panel: Date: CIRCUIT: QTY Z-MC@30C D SET -MC -C W@110C D 5 TOTAL m A= 20.0225076 Notification Appliance Circ uit Detail WESTFIELD SOUTHCENTER MALL BEACH: WORKS June 16, 2008 SPEAKER CIRCUIT Device Type 70.7V1/8 Alarm Current 1.8 0 0 0 0 0 0 Wire Resistance x.58 CURRENT TOTAL= 7.2 Alarm Total Wire Size Wire Length Voltage at EOL Total Wire Resistance (R ) (WL*2)*(Rift) Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E ) (E=I*R) EOL Voltage (20.4 - E) DEVICES= TOTAL mA= 20.39290397 VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved >- m w z DESCRIPTION N z a 0 0 c0 W O C C C J 03 co T Q 0) cc Wopo o P -2C3 zz 5, cc o I2 Q o W j co - m p r� 1 - CC W I-- C) SCALE: 1 /8"=1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/1 6/08 BACKROUND PLAN PROVIDED BY: \:0B NUMBER: SHEET FA -04 , .W,ESTFIEL FIRE ALA TUKWILA, ; s' l• SHEET INDEX . I IVA *• , AL NOTES UITE 1076 SYSTEM INGTON SYMBOLS LEGEND SHEET \U v3E. HEO TITLE FA -01 . I •5 YSTEIV I \ FO IVATIO \ FA -02 ; TYPICAL DETAILS - WI I \ G A\ D VOU\TI\G FA -03 SYSTE \A FLOO PLA\ FA -04 YS -10 CALCULATIO\S (GE\E AL), SITE PLA\ WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL •CHART • .•. WIRE DESIGNATION :!i. SYMBOL DESCRIPTION .. , .. NUMBER OF CONDUCTORS SIZE TYPE COLORCODE D '. H .I P .::i S il 2S1 A ;I . V ..: 2Vi I X UD UI : II M ,i B -1 DATA LINE -ADDRESSABLE LOOP DOOR HOLDER POWER - 24VDC DEVICE POWER - 24VDC -11ROBE CIRCUIT - FEED STROBE CIRCUIT - RETURN . ANNUNCIATOR I . PEAKER CIRCUIT - FEED SPEAKER' CIRCUIT - RETURN : REMOTE INDICATION LIGHT ! LOW LEVEL AUDIO : UNDERGROUND DATA UNDERGROUND INITIATION ' DOOR HOLDER POWER ! BEAM DETECTOR POWER TWISTED PAIR WITH SHIELD #16 : .,:FPL/FPLR RED (JACKET) TWD #14 ...FPL/FPLR . RED (JACKET) TWO #16 • FPL/FPLR RED (JACKET) TWISTED PAIR W/ SHIELD #12 ::•FPL/FPLR RED (JACKET) TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) TWISTED PAIR W/ SHIELD #16 FPL/FPLR 'RED (JACKET) TWISTED PAIR *14. FPL/FPLR :, RED (JACKET) TWISTED PAIR #14 FPL/FPLR RED (JACKET) TWO #18 . ' FPL/FPLR . RED (JACKET) TWISTED PAIR W/ SHIELD #16 ' ...: FPL/FPLR :RED (JACKET) TWISTED. PAIR RATED : 418 '' FPL/FPLR , RED (JACKET) TWISTED PAIR RATED #1.8.; FPL/FPLR ':: RED (JACKET) TWD : . #16:,*:h3L/FPLR RED (JACKET) TWO • • *14. : FPL/FPLR RED (JACKET) CONDUIT FILL CHART : 1 . .. ! ! .i: , :• ! •, • . • , . NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA : . 600V #12 AWG THHN/THWN - .244 0.D. .0467 1 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.6. .0346 , TWO CONDUCTOR 300V #18 AWG FPL TW CABLE . .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE' ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL ' 1/2" .12 SQUARE INCH - 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH " 1-1/2 .82 SQUARE INCH ' . • - , , 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4: SHIELDED WIRE TO BE: GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND:: TAPED AT END FOR SIEMENS SYSTEIVV ,!1 DO NOT INSTALL ADDRESSA9LE IN DEVICES ADDRESS. '‘lATING DEVICES UNTIL PREPROGRAMMED WITH 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE T4E SEC. D DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRC,POL 3. AUDIBLE/VISUAL CIRCUIT WIRIN, , IS S BRANCHING IS PERMISSIBLELI 4. INSTALLATION SHALL BE IN SICT CI ELECTRIC CODE, NEPA 72, LO' L co ,11.11 5. INSTALLATION MATERIALS (LE,onoNDu STANDARD BOXES, FIBER OPTIr' :CAB ARE NOT SUPPLIED BY SIEME,, CERB 6. DETECTORS SHALL NOT BE MO ATED AIR STREAM OF AIR SUPPLY WLETS 7. WIRING SHALL BE PER PLAN RE TYPE, QUANTITY AND COLOR iIDE. C AND UNIQUELY MARKED FOR 11TURE 8. INSTALLING CONTRACTOR SHALL RETL DRAWINGS FOR "AS BUILT" PU, POSE 9. FOR ADDITIONAL INSTALLATI0fl1 INSTRI SHEETS AND/OR INSTALLATIO IN STR 10. THE 120vac POWER ELECTRICq LWOR MUST COMPLY WITH ARTICLE 125: AN SPECIFICALLY SECTION 1-5.2.H12: IN SOURCES. 120vac POWER SH*LI NOT DIRECT SUPERVISION OF FIRL1'r IIARM 11. ALL HORN/STROBE AND STR OF 80" A.F.F. OR 6" BELOW . ITY SHALL BE OBSERVED. ERVISED. NO PARALLEL FORMANCE WITH THE NATIONAL (5), AND/OR AUTHORITY HAVING JURISDICTION. WIRE, FITTINGS, HANGERS, FITTINGS, AND ASSOCIATED EQUIPMENT) RUS DIVISION. DIRECT PER NFPA 72 2-3.5.1 i'ECT TO CONDUCTOR SIZE, & OR CABLE TRAY, NDUCTORS SHALL BE PERMANENTLY, ENTIFICATION. N ONE SET OF ACCURATELY MARKED TIONS, REFER TO CATALOG CUT TIONS. SUPPLYING FIRE ALARM SYSTEM PANELS I760 OF NFPA 70, N.E.C. AND NFPA 72, EFERENCE TO DEDICATED BRANCH POWER E APPLIED TO FIRE ALARM PANEL WITHOUT ECHNICIAN. I 3E DEVLES SHALL BE MOUNTED ,'AT A HEIGHT OPPE CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONSI ALL E MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CO UITS ILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FO V1 DE CATED CIRCUITS FROM THE EMERGENCY - GENERATOR. - ...; I 15. PER NFPA 72 SECTION 5-3.61 3 DE L. CTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF AUL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIREDI;BY TH1 AUTHORI.TY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUC10. • DETECTORS THAT HAVE BEEKINSTAL D PRIOR TO .FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED R REPLI CED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FRO AND THEN FROM DEVICE TOgVICE OTHER, BACK BOXES OF' DIFFIgRENT • 17. ALL • WIRING SHALL BE METERA' AND FREE OF SHORTS BETWg FINAL EQUIPMENT TRIM. 1 • 18. ALL CABLES SHALL BE MARqDrAS I PERMANENT LABEL AT ALL TIVICES 1,1 ; 19. THE ELECTRICAL' CONTRACTO1SHALL OUTSIDE AND INSIDE OF THEITIRE.. A AFTER COMPLETION OF THElf,O.NSTAL VER. CO 20.. DETECTORS MUST BE RATED R TE IT IS LOCATED. . FACP TO FIRST DEVICE (ON A CIRCUIT ITHOUT SPLICING .IN PULL BOXES OR CUITS. IED TO BE CONTINUOUS,I 'FREE .OF GROUND UCTORS AND :OTHER CIRCUITS PRIOR •TO •DICATED 1(c)N FIRE ALARM RISER WITH A UNCTION BOXES. AND FACP. •• . , CLEAN ALL DIRT AND DEBRIS FROM. THE RM BACK BOXES, AND JUNCTION BOXES ATION. • r „ ERATURE IN THE ENVIRONMENT IN :WHICH. 21. ALL WIRING BETWEEN FLOORS, HALL E LOCATED IN CONDUIT. . 22. NFPA 72 2007 6.4.2.2.2 ALLIH YLES' F CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., IL 'ETALL , OPTICAL' FIBER) SHALL BE. '• INSTALLED SUCH THAT THE OVTGOING AND RETURN 'CONDUCTORS, EXITING FROM AND RETURNING TO T4IIICONTR L UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUOING ND RETURN (REDUNDANT) .CIRCUIT CONDUCTORS SHALL NOT BE N IN HE SAME CABLE ASSEMBLY (1:E.,. 4r'LOSU MULTI -CONDUCTOR CABLE), E. 23. NFPA 72 2007 A.6:4.2.2.2 AP OAL,, ADEQUATE SEPARATION BETW, N1 THE „ THIS SEPARATION IS REQUIREOIITO HE CABLES FROM PHYSICAL DAM'T- SEPARATION TO PREVENT PHY,„ CAL ' D THE CABLE IS INSTALLED VERT ALLY CABLE IS . INSTALLED . • t • gi! • :H; OR RACEWAY. 6.4.2.2.2.15 TO PROVIDE OUTGOING AND RETURN.CABLES. P ENSURE PROTECTION OF THE RECOtv MENDED MINIMUM MAGE IS, 305. MM (.1 FT) :WHERE ND 1.22 M .(4 FT) WHERE •THE . t 4 QUANTITY 2 2 2 EX SYMB DE RIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FAC FIR1i ALARM CO TROL PANEL EX XLS-V SIEMENS • PROVIDED 66" A.F.F. TO TOP FAR FIR ' ALARM RE OTE ANNUNCIATOR SDD-C SIEMENS PROVIDED . 66" A.F.F. TO TOP BP RE OTE BOOSTER EX PO ER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP . IT( INT WIT kFACE MODULE RELAY HTRI-R SIEMENS 4S DEEP VERIFY IN FIELD OU:' INT INPUT 1RFACE MODULE. HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HC CO NO h-ROL POINT l<U LE HCP SIEMENS 4S DEEP VERIFY , IN FIELD RE, ZO OTE CONVENTIONAL HZM IE MODULE LIN' AR BEAM SN1( KE DETECTOR SIEMENS 4S DEEP PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD VERIFY IN FIELD SM (AD ID CTOR KE DETECTOR HFP-11 1/‘// SIEMENS RESSABLE- PHOTO) DB -11 BASE A DU 4S DEEP W/ 1G RING CEILING SMOKE AD2-P W/ SIEMENS DUCT HOUSING VERIFY TSM MODULE IN FIELD DETECTOR RESSABLE) HFPT- 1 1 \AY SIEMENS DB -11 BASE IN/ 1G RING. 4S DEEP CEILING FIR SP (C ALARM KER STROBE LING MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING FIR SP (W ALARM KER STROBE L MOUNT) SET -MC -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM L L FIR: ALARM SP r KER STROBE (WAL MOUNT) FIR! ALARM ST"OBE (C L1 LING MOUNT) FlR1 ALARM STBE (W L MOUNT) SET -HMC -OW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. FIR SP (C ALARM KER LING MOUNT) SET -CW SIEMENS 4S DEEP BOX \V 1-1/2" EXT. CEILING FIR SP (1,W ALARM KER L MOUNT) B FIR STF (WE ALARM OBE THERPROOF) MR MU TI -VOLTAGE C0Ij1TR0L RELAY MA r N ET I C DOQR HOLDER FA JB8X FIR ALARM TE 1 INAL CABINET F,B, N/ GRE • , • ti U TWIN BOX ABIIIVE FINISHED rLIIR FU DT NO AP UNINO, It455 WE DE AS RE ISHED BY RS ICABLE SS OTHERWISE THERPROOF' ICE BUILT OR CHANGE UILT VE ASABUILT NO S TO CAD A completd, signed; TglicwOR_Box siEmENsNoricE W/ 1_1/2" EXT. F.B.O. SET -W tee Li /nation ofthe tepn9..IEP BOX inp ..g -inspection Fee isliti SET -S17 -WP OnaighVartment Pre-T9ss' PIPE Testing of any Fire Ala rp,. Certificate must be presented to theeTBRelor prio4toBox corifnePrkdment of Acceptanc pecbDetection Syste Failure of test will result MR -201/C F.B.O. F B .0. N/A N/A N/A N/A N/A N/A N/A N/A • .N/A NI /A N/A CCEPTE N/A Without Comments N10 . As Noted In Rd& A 0 Per The Attached Letter 80" A.F.F. TO BOTTOM VERIFY IN FIELD VERIFY IN FIELD VERIFY IN FIELD VERIFY IN FIELD RIFY FIELD . N A NIA NA nese4p1dns have been reviel,veli/Sy The Tukwila Fire N Prevention Bureau for conformance with current city standards. Acceptance is subio^t to errors and omissrlia which' do not autho • &lotions of ad,opted " standards and ordinances. The responsibir for the a eduacy of design rests totally with the designer. Additieiris deletions or revisionaahese drawings atter N this date will void this acceptance and will require a resubrRI of revised drawingspiRubsequent approyaIN jFinal acceptance is subject to field test and inspection by The Tflin!la Fire, Prevention B !Date: ea pg By! fUKWILA FIRE DEPARTivitAt Please call: 575-440Z end give this job No. and exact address for shut. tik,wn or restoration approval. Copyright 2006 by Guardian Security. •Systems, A A A 5 r) 0' co RELEASE/REVISIONS .14 44 144 114 OT/CE !Because of increaSedidemane out !inspectors' schedUlesrare boo <ed A 3-7 days aheafdi-e, you l will need to call 2()6575-4407 to schedule yoursa minimum of4 idur${h adva of the date yoU wantpn Inspection. • -J,2008 Tukwila 1. Inc. All Rights Rery co co co 2 2Z W 0 Ci) zz Er < w0 C1) CC C/).3 fe:*- 02 SCALE: 1/8"=l' DRAWN BY: E.HAMERSKI DESIGNED BY: R.VEZZANI DATE: 05/20/2008 BACKROUND PLAN PROVIDED BY: NUMBER: SHEET 0 • , THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTFIS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT •1 DIAMETERS i.:• TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE _(+ STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVIC END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH o DUCT DETECTOR LOCATION NOTE: FOR ADDITIONAL SPECIFICATONS SEE PRODUCT DOCUMENTATION. LC) HTRI-R STATUS LED oo 0 0 N.O. COM CC! 0 N C TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVIOUS ADDRESSABLE_ DEVICE TO NEXT ADDRESSABLE DEVICE ; NOTE 1.1 VOLTAGE MAX.— CURRENT MAX,— CONT, RES, MAX,— MAX, CABLE LENGTH— C (LINE TO LINE)— C (LINE TO SHIELD)— MAX, LINE SIZE— MIN. LINE SIZE— • 1 OUTLET TUBE SAMPLING •! !: •' • INLET SAMPLING •, , TUBE ; •! I • • ! •1 • ; AT LEAST HSIX DUCT '•• WIDTHS 'FROM BEND ; . : ;;••2• I ; • • H••• i! :11! ,1; • .• •!: ; • 11, ,!:1•!;.! TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE !1411'i MUSIC —4 -AC POWER SOURQ1 COMBINE ALL SHIELDS AND. ISOLATE FROM GROUNDING .!•1:1 11 •,.,• TO NEXT ADDRESSABLE DEvIcg, 54, STOP IF LAST DEVICE ;11 FROM XLS CONTROL. PANEL ORI: [`+' PREVIOUS ADDRESSABLE DEVIPEl1c •;0 ) k.• j • END OFIiE DEVICE:11 I (3,6K 11/14W)i ! • / , • , • ' !!? ;.„ !!.! • RELAY CONTACTS (4.OA @ 125VAC) (4.OA @ 30VDC) 27 VDC 3,5 mA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0.02uF 0.04uF 14 AWG 18 AWG NOTE 2: ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC, TO GUARANTEE DETECTION. .) 10 01 cs•sl•ools).s2 1 2 3 4 5 6 TB2 r • 3 eso —\+ — 6 5 4 3 2 1 0 0 TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE :!• 2j ;!! Vi 1. / ••1:: ; i / SUPERVISEID___./ SWITCH • GROUND / @ HTRI-D STA1US LED 00 0 0 NOT NOTE: • .! FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL m (FIRE SUPPRESSION SYSTEM INTERFACE) 0 !! CND N ACI ' • _Ln; 0 0 0 • '0' U 0 P A D 3 • • INPUT INPUT 1— 1 2+ 2— 2 g. 0 L!, ' 0 I=1 TROUBLE 'NAC1 NAC2NAC3 • NA C4 AUX NC C NO + — + — + + — 24K 'n •!, :12 ?NAC -4 ?NAC -3 NAC -2 (?NAC -1 .! !. ! • SED .t ! OFLNE K 1/4 LIPERVI 3c/ITCH 1, • •,4 fl , ( FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED 0 REMOTE + DEVICE LOOP NOT USED 0 REMOTE 10 DEVICE LOOP..L. 0 FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> 470 OHMS EOL INPI s)1 T M-1 m TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE NCTE FROM REMOTE POWER SUPPLY ('S' CABLE) CE FROM FACP (VOICE CIRCUIT) ('V' CABLE) D F M (-) STROBE SPEAKER (+) (—) (Th -) STROBE C (+) (—) STROBE SPEAKER —) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY 80" A.F.F. 4S DEEP BOX W/ 1 -1 /2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE 'TO N DEVI END o T OR LINE T OR LINE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERtIll TEMPERANRE: +32'F O'C TO 100*F (36 c) HUMIDITY: —9 % RELATIVE HUMIDITY, NON—CONDENSING HFP-11 SMOKE DETECTOR —, , . DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION MTH DUCT HOUSINGS AD -11P OR AD -11)9312 DB -11 STANDARD SMOKE DETECTOR BASE !I • . .1q!, -->• FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE { DATA IN (—) > DATA IN (+) > REAR VIEW I 1 (-) DATA OUT }! (+) DATA OUT HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID HARD LID —;\ CEILING SPEAKER SUPPORT TILT BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION N CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE=NONE JUNCTION BOX MOUNTED ON CEILING FLEX JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT 00 TO NEXT DE ----CADDY BAR SMOKE DETECTOR— SMOKE DETECTOR MOUNTING SCALE=NONE \--- SUSPENDED ILLUMINATED C DO NO1 ADDRESS DEVICES DREPROG DEVICES \S LAIL BLE ON \-11 AT MMED W DDESS. 1,\ TH, Copyright 2006 by Guardian Security Systems, Inc. All Rights Re4rved • • ; • , ••!., CO ON tsr) RELEASE/REVISIONS LLJ -DESCRIPTION SHOP DRAWINGS uJ t -H CO! co c•1 Ln LL (/) 1.1.1 ALE: 1 /8” 1 DRAWN BY: E.HAMERSKI DESIGNED BY: R.VEZZANI DATE:05/20/2008 BACKROUND PLAN PROVIDED BY: \z...10B NUMBER: SHEET A-0 t I : I t LL ;,; • X ISir Pq •it 2S,2V li- --------------- - ----- ---- ----- ------------- V- EX EOL—S 19.99V FACP LC) C 75 2S,2V 1,1! tt: • CA_ 2S,2V -------------- NORTH SUITE 1076 VVES SCALE 118'4 ' TI L C 75 fl OUTHCENTER MALL 11 •41 'LAG \ S:. 1:1 I '1 fr; FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS(SEE SIEMENS INSTALLATION SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRCTOR. WIRED BY ELECTRICAL CONTRACTOR, SIEMENS HTRI-D ADDRESSABLE INPUT WITH HOOD VENILLATOR FIRE SUPPRESION SYSTEM. FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL. FIELDLOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY-. FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, no VAC BRANCH CIRCUIT. RELEASE/REVISIONS REV. BY: cp L..1 'DESCRIPTION• • SHOP DRAWINGS - • w 1 -- 05/20/20081 cm ( it DO NO ONSTAL_ ADDRESSABLE MOT ATI DLVICES U\TIL PEPOGRAMMED WI DEVICES ADRESS. Copyright 2006 by •Guardian Security Systems, Inc. All , Rights Res & DRAWN BY: E.HAMERSKI DESIGNED BY: R.VEZZANI DATE: 05/20/2008 BACKROUND PLAN PROVIDED BY: JO•Ei NUMBER: SHEET FA -03 •1• ." .4"1 ' dd. 1076 FACP ADD ONS I--10(:1'.0— C ) i---- . -., 1 TS C M ER EXI s-ri NG • JCPenney LE \IF S Standby: SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations HTR HTRI-D 1.0TH ERFI 00D M A TEIRNI PIERciNc PAc,onA D S C.' -_ +- 0 (--.) "...3 SPECS 1 NI TRASH THE CITY sp A ...... it7 X:ST:rsiG ROOTL(ICKER KIDS F00 -FLOCK ER [1200 Stadby Cutent Load: ti AlaCurrelt Load: ! i1:111 1 141 11111 1 1 1 ii11 111 ' Main :§ystem Board SET- ic @15CD SET- :jC @30CD SET- C @75CD SET- @110CD SET- MC-C@115CD SET-WC-C@135CD SET-HMC-C@185CD 1ZR-M 5CD ZR -M @30CD HCP • i" 12.35 1240 2. BATTERY SIZI -.7,ty,.; L L 0C) • , • ; 430 EEC RiCs!q CALIFORNI1A PIZZA\ K ICH EN • NORTH #fv.'N SUITE 1076 WESTFIELD SOUTHCENTER MALL 11,5 SCALE 113264 Notification Appliance C WESTFIELD SOUTHCENTER MALL 1076 Lilt De tail Voltage at EOL 2 S,2 2S2V 2S2V 2S2V C 75 C 75 15 15 D,I Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E) (E= I *R) EOL Voltage (20.4 - E) 0.00 21 'ALE: SEE SHEET ') EOL — S1 EX DRAWN BY: E.HAMERSKI DESIGNED BY: R.VEZZANI DATE: 05/20/2008 BACKROUND PLAN PROVIDED BY: JOB NUMBER: Cop right 2006 b Guardian Securit S stems, Inc. All Ri hts Rei-ved dd t Notification Appliance cuiDetaiI PROJECT: WESTFIELD SOUTHCENTER MALL J Panel: 1076 ', * ire Resistance 1.62 Date: May 29,2008 UR -ENT TOTAL= 478 CIRCUIT: S1 QTY Device Type Alarm Current Alarm Total Wire Size Wire ngth , Voltage at EOL Circuit Tata! 0 SET -MC @15CD 64 0 Total Wire Resistance ( R ) 0.86 0 __ SET -MC @30CD 98 0 ( WL * 2 )* (R/ft) 2 SET -MC @75CD 175 350 i Total Device Load, Amps (I) 0.48 0 SET -MC @110CD 233 0 -4-- — (Total Cct Load) 0 SET-HMC-C@115CD 318 0 _, 1 la Voltage Drop ( E ) 0.41 0 SET-HMC-C@177CD 445 0 ' , (E= I* R) 0 SET -HMC @135CD 318 0 EOL Voltage 1999. 0 SET -HMC @185CD 445 0 (20.4 - E) 2 Z-MC@15CD 64 128 0 Z-MC@30CD 98 0 , 0 SET-MC-CW@110CD 233 0 . DEVICES= 4 TOTAL m A= 478 12 19.9895892 474 1 Notification Appliance C WESTFIELD SOUTHCENTER MALL 1076 Lilt De tail Voltage at EOL 2 S,2 2S2V 2S2V 2S2V C 75 C 75 15 15 D,I Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E) (E= I *R) EOL Voltage (20.4 - E) 0.00 21 'ALE: SEE SHEET ') EOL — S1 EX DRAWN BY: E.HAMERSKI DESIGNED BY: R.VEZZANI DATE: 05/20/2008 BACKROUND PLAN PROVIDED BY: JOB NUMBER: Cop right 2006 b Guardian Securit S stems, Inc. All Ri hts Rei-ved dd t VICINITY MAP (Suite# 1076) SCALE: NTS • 28 General Notes 1. Western States Fire Protection to add new pendent heads new upright heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. AH other areas are not in contract and WSFP is not responsible for existing conditions. WEST RISER DETAIL HYDRAULIC REFERENCE ONLY NOT TO SCALE + 81-0" AFF : �29� 30/. + 14'-0" AFF I ----L—'-- ---'- I OO1 . A I 1+ 8'-0" AFF Existing Main —+-T� ezi'esti - + 11'-0" AFF 2 1OW. +til- of 7 is 211B'N + 12'-0" AFF 1 r+ 14'-0" AFF 4 .v . :l I -:pit 1-1.+ 13•-6" AFF Ordinary Group II•120gpmlft2 for 990.00ft2 • 29�i /30� FIRE SPRINKLER SYSTEM 3 5 7 9 11 TYPICAL FLEXABLE SPRINKLER CONNECTION:: FLEXHEAD MOUNTING BRACKET PIPE NIPPLE SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS REDUCING FITTING SUSPENDED T -BAR GRID SPRINKLER HEAD CEILING TILE FLEXEIEAD DETAIL NOT TO SCALE FIG. UI9 SWIVEL SWAY BRACE FITTING BRACE PIPE (21MEMBEDLENGTH) - FIG.1000 •'FAST CLAMP" SWAY BRACE ATTACHMENT LINE PIPE LATERAL LINE RESTRAINTS NON -THREADED BRACE PIPE FIG.4A PIPE CLAMP FOR SWAY BRACE LATERAL BRANCHLINE RESTRAINT FIG.909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT 3/B` KWIK BOLT (2 1/4' EMBED LENGTH) BRACE PIPE oagi NON -THREADED BRACE PIPE LATERAL BRANCHLIN NOT TO SCALE VANILLA SHELL 1076 Remote Area: Retail # 1076 CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY CLASS ORD HAZARD II MAX. COVERAGE per HEAD 130 Ft' Ft' DENSITY .20 GPM / Ft' for 990 SPRINKLER Reliable Model G4A ORIFICE 112" K= 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 PSI FLOW 10904 GPM AT BASE OF RISER, SYSTEM REQUIRES: 417.62 GPM 88.28 PSI At time of Design 14'-0" CLG.=34.0%. AREA REDUCTION RESTRAIW\ T Hanger No. 07C HILTI Kwik Bolt III / HILT) Krill Bolt II Drilled Ancor Rod Coupling —.„1/4 All Thread Rod Swivel Ring Pipe Weld stamps must be inspected before pipe is hung. Do. not infllar iIrNberand'A'Dlmenslon prior to hydrostatic test II'' approval. Concrete Construction Bottom of Concrete to Center Line of Pipe Note on Plan 0 A EP Without Cornments As Noted In Red Per The Attached Letter W 0 5.- a) Ines plans have been reviewed by The Tukwila F e Prev: ntion Bureau for conformance with current cit stan.ards. Acceptance is tuhie•ot to errors and omis-.ions which do riot authorize violations ofado •ecE stan.aras and ordinances. The responsibility forth ti3 adeq acy of design rests totally with the designer. Addit ons, deletions or revisions to these drawings tt this sate will void thr.acceptance and will require a resu•mittal of revised drawings for subsequent app ovd. nf� HANGER .NV 11 . DETAIL Final acceptance is subject to field test and Inspect The Tukwila Fire Prevention Bureau. e o >y: 6/(/ 8 NOT TO SCALE Date: I.UKWILA FIRE UEFAit 1: ...ilk Please call: 575.4407, and give this job No. — 33 and exact address for sh t• Town or restoration app •vet to Sr 0 t 0 c VICINITY MAP DETAIL NOT TO SCALE SYMBOL LEGEND REVISIONS Sprinkler Legend 2 -WAY EARTHQUAKE BRACE N0. DESCRIPTION DATE SYM. SIN QTY. K SPRAY ORIF. FIN. TEMP. 1 MFR./MODEL 4 -WAY EARTHQUAKE BRACE R5415 8 5.6 Pendent White 155°F G4A Concealed APPROVAL: CIty of Tukwila HYDRAULIC REFERENCE POINT R3615 23 5.6 Pendent %Z' Chrome 155°F F1 FR Semi-Rec CONT. NO.: KS0407 Total = 31 DRAWN BY: Adam Kantner HANGER SYMBOL BRANCHLINE RESTRAINT SPRK ON SHEET: SEE LEGEND SPRIG ON JOB: DATE 06/17/08 Western States Fire Protection Company 7102 180th AVE NE, STE A-105 - REDMOND, WA - 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE/AUSTIN/DALLAS/DECATUR/DENVER/DULUTH/HOUSTON/KANSAS CITY LAS VEDAS/MRIIEAPOLIS /PHOENIX/ PORTLAND /RAPID CITY/ST. PAUL/SALT LAKE CITY/ SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 1.7 ID JUN,1;2101,0,84„,e, 'ire �{cw Vanilla Shells 107b Southcenter Mall Tukwila ,Wa 98188 FIRE SPRINKLER SYSTEM SHEET FP -1 OF 1 TYPICAL FLEXABLE SPRINKLER, CONNECTION PIPE NIPPLE FLEXHEAD F'= SPRINKLER • BRANCHLINE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS MOUNTING BRACKET REDUCING FITTING 1+ 8'-0" AFF FLEXHEAD DETAIL NOT TO SCALE General Notes 1. Western States Fire Protection to add new pendent heads new upright heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile.iron class 150. ' 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for . existing conditions. I +�¢ m i I I A•�y 1 1 I it 4 I cs0 I E' �aCQrC� 11 1"'I 122 CM ism 0021 Os mai ina" I• 8 2\10,4; ©I A -1,1 i I i, v ; ! II 1Y Rt 4 I 1 V r 1 I l O Il li 3/8- KWIK BOLT (2 1/4' EMBED LENGTH) 3/9' KWIK BOLT. (21/4' EMBED LENGTH) FIG. 009 • SPIIVEL SWAY &TACE FITTING ' FIG. 009 •�- -•-� NO•THREAD SWIVEL SWAY BRACE ATTACHMENT -`'-••�I sto met 02* trai ism sit fig I I 1��} CoQ I I Q 1 217- •11 • I 4-- •• - I I BRACE PIPE FIG.1000 FAST CLAMP" SWAY BRACE ATTACHMENT LINE PIPE BRACE PIPE LATERAL LINE RESTRAINTS NON -THREADED BRACE PIPE FIG. 4A PIPE CLAMP FOR SWAY BRACE . LATERAL BRANCHLINE RESTRAINT Thad NON -THREADED BRACE PIPE 6+10% +1V-6"AFF LATERAL BRANCHLINE RESTRAINT NOT TO SCALE 1+ 11'-0" AFF Ordinary Group II.0.20gpm/ft2 for 990.00ft2 i VANILLA SHELL 1076 Remote Area: Retail # 1076 CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY CLASS ORD HAZARD II Hanger No. 07C HILTI Kwik Bolt III MAX. COVERAGE per HEAD 130 Ft' DENSITY .20 GPM / Ft' for 990 Ft' SPRINKLER Reliable Model G4A ORIFICE 1/2" K= 5.6 , WATER FLOW INFORMATION': STATIC 140 i . PSI RESIDUAL 20 PSI FLOW 10900 GPM AT BASE OF RISER, SYSTEM REQUIRES: 417.62 GPM © 88.28 PSI ' At time of Design • CLG.=34.0% AREA REDUCTION HILT! Kwik Bolt II Rod Coupling —� Cut Rod Lgth Rounded to Nearest Inch All Thread Rod Concrete Construction Bottom of Concrete to' Center Line of Pipe Note on Plan Swivel Ring ' Note ort Plan: Hanger Number and'A' Dimension Adam Kantner HANGER DETAIL NOT TO SCALE n_ 0) 0 WEST RISER DETAIL HYDRAULIC REFERENCE ONLY NOT TO SCALE VICINITY MAP DETAIL NOT TO SCALE SYMBOL LEGEND REVISIONS Sprinkler Legend APPROVAL: 2 -WAY EARTHQUAKE BRACE 4 -WAY EARTHQUAKE BRACE NO. DESCRIPTION DATE SYM. SIN QTY. R5415 R3615 HYDRAULIC REFERENCE POINT 8 23 K SPRAY 5.6 5.6 Pendent Pendent ORIF. Y2' FIN. White TEMP. Chrome 155°F 155°F MFR./MODEL G4A Concealed F1 FR Semi-Rec City of Tukwila Western States Fire Total = 31 HANGER SYMBOL BRANCHLINE RESTRAINT CONT. NO.: KS0407 DRAWN BY: Adam Kantner SPRK. ON SHEET: SEE LEGEND SPRK. ON JOB: Ott DATE: 06/19/08 Protection Company 7102 180th AVE NE, STE A-105 - REDMOND, WA - 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE/AUSTIN/DALLAS/ DECATUR I DENVER/DULUTH/HOUSTON/KANSAS CITY LAS VEGAS/ MINNEAPOLIS I PHOENIX / PORTLAND 1 RAPID CIN/ ST. PAUL/SALT LAKE CITY/SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 Vanilla Shells Southcenter Mall Tukwila Oa 98188 FIRE SPRINKLER SYSTEM SHEET FP -1 OF 1 1077