HomeMy WebLinkAboutPP - 1077 SOUTHCENTER MALL - STRIDE RITE - PERMITS AND PLANS1077 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-340 10-S-013 08-S-325 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Stride Right 1077 Southcenter Mall Permit No.: 08-S-325 Date: June 13, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing Is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All references are NFPA 13, 2007 Edition. /077 Sc mtf( LL VNL CI 1/44s. W7 3 toANal 0 Ato S ..in ')f ti.7 ... A a N Z. 1.. MOB. O B.. g g 0.) gaEE31:1 vg c 73 MEPIA W734) -t82ggliSilib G EE cp �cu ��a �o.sC V -a Q,o = Z a ZL III1!1U 111111111 0 A ( STRIDE RIGHT FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET UVV3ER SHEET TITLE FA -01 SYSTEM I \ FORMATIO \ FA -02 TYPICAL DETAILS - WIRING A\ D MOU \TI \ G FA -03 FRE ALARM SYSTEM FLOOR PLA FA -04 SYSTEM CALCULATIONS r GE\EAL), RISER, SITE PLA\ WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. • DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3, AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED, NO PARALLEL BRANCHING IS PERMISSIBLE 4. .INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY. HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1- 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g. • FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF -NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, ,WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN. (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 2 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD IB LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING AD DUCT SMOKE DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING Ec FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -HMC --CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING L FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING FIRE ALARM STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. YC FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. FIRE ALARM SPEAKER (WALL MOUNT) SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM C3WP MR FIRE ALARM STROBE (WEATHERPROOF) MULTI -VOLTAGE CONTROL RELAY SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. FA JBOX FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. VERIFY IN FIELD VERITY IN FIELD JUNCTI❑N BOX F.B.D. EPTE V( i INERFIj=LD A.F.F. ABOVE FINISHED N/A .N0 Without Ccik.Aents N/A 11 `-"U M WIRE DESIGNATION -- '/0' As Noted In Red SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D H P S A V I X UD UI M B DATA LINE -ADDRESSABLE LOOP DOOR HOLDER POWER - 24VDC DEVICE POWER - 24VDC STROBE CIRCUIT - FEED ANNUNCIATOR SPEAKER CIRCUIT - FEED REMOTE INDICATION LIGHT LOW LEVEL AUDI❑ UNDERGROUND DATA UNDERGROUND INITIATI❑N DOOR HOLDER POWER BEAM DETECTOR POWER TWISTED PAIR WITH SHIELD #16 TWO #14 TWO #16 TWISTED PAIR W/ SHIELD #12 TWISTED PAIR W/ SHIELD #16 TWISTED PAIR #14 TWO #18 TWISTED PAIR W/ SHIELD #16 TWISTED PAIR RATED #18 TWISTED PAIR RATED #18 TWO #16 TWO #14 FPL/FPLR RED (JACKET) FPL/FPLR RED (JACKET) FPL/FPLR RED (JACKET) FPL/FPLR RED (JACKET) FPL/FPLR RED (JACKET) FPL/FPLR RED (JACKET) FPL/FPLR RED (JACKET) FPL/FPLR RED (JACKET) FPL/FPLR RED (JACKET) FPL/FPLR RED (JACKET) FPL/FPLR RED (JACKET) FPL/FPLR RED (JACKET) N/A CONDUIT FILL CHART N/A } i nese plans PiVrention Bureau for conildrri nce with current cit',N/A !. standards. Acceptance is subject to errors and of adopted NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE TWO . 600V #12 AWG THHN/THWN TWO 600V #14 AWG THHN/THWN TWISTED TWO CONDUCTOR 300V #18 AWG FPL TW CABLE CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF CONDUIT SIZE MAXIMUM F 1/2" .12 SQUARE 3/4" .21 SQUARE 1" .34 SQUARE 1-1/4" .60 SQUARE 1-1/2" .82 SQUARE 2" 1.34 SQUARE FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM DIMENSIONS ' AREA .244 0.D. .0467 .210 0.D. .0346 .156 0.D. .0191 FROM THE TABLE FILL DIMENSION FROM THE WIRE. LL NCH NCH NCH NCH NCH INCH N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. • DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3, AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED, NO PARALLEL BRANCHING IS PERMISSIBLE 4. .INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY. HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1- 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g. • FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF -NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, ,WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN. (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 2 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD IB LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING AD DUCT SMOKE DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING Ec FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -HMC --CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING L FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING FIRE ALARM STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. YC FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. FIRE ALARM SPEAKER (WALL MOUNT) SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM C3WP MR FIRE ALARM STROBE (WEATHERPROOF) MULTI -VOLTAGE CONTROL RELAY SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. FA JBOX FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. VERIFY IN FIELD VERITY IN FIELD JUNCTI❑N BOX F.B.D. EPTE V( i INERFIj=LD A.F.F. ABOVE FINISHED N/A .N0 Without Ccik.Aents N/A 11 `-"U M -- '/0' As Noted In Red F B ❑ FURNISHED BY OTHERS N/A N/A 0 Per The Altp, ed Letter N/A have bccn reviewed by The Tukwiie Fire N/A NOT APPLICABLE N/A } i nese plans PiVrention Bureau for conildrri nce with current cit',N/A !. standards. Acceptance is subject to errors and of adopted U.D.N. UNLESS OTHERWISE NOTED N/A ornissions Wliich do not authorize violations sW,ERM,aras and orainances.NTh responsibility for thR/A adequacy of design rests totally with the designer. these drawings atter { A complct Fire Del Certificate WP WEATHERPROOF DEVICE N/A Additions, deIeiioiis or revisions to Ukisqlete will void this.acceltsltdAce and will require aN/A resubmittal of revised drawings for subsequent approval. RED AS BUILTt0 ADD OR CHANGE N/A FIh acceptance is subjecitJtoEfield test and inspectjgh1 y The Tukwila Fire Prevention Bureau. the commence TenGREEN D� t=aiInre AS BUILT REMOVand N/A1/ig/o3_•_\jYAj7c1) N/ W BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A y oC4► FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS z Q DESCRIPTION SHOP DRAWINGS L1J cO 0 C aC aC co T Q nz w fro Lut5 cc zz W vcn =Q Q �� CC dog v, O= 4OTICE ed, signed, Tukwila �artment Pre-test must be presente Inspector prior to ment of Acceptance of any Fire Alarm �tection Systems. of test will result in a Re -inspection Fee and termination of the testing. TUKWILA FIRE DEPARTM:.4J Please call: 5754402 and give this job a .d exact address for shut* in or restoration approval . Copyright 2006 by Guardian Security Systems, Inc. All Rig hts Reserved Z 0 CC 0 Z H >rn DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/1 6/08 BACKROUND PLAN PROVIDED BY: \z_JOB NUMBER: SHEET C FA -01 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND IS❑LATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR PREVI❑US ADDRESSABLE DEVIL END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH O DUCT DETECTOR LOCATION 0 GROUND_.(?) Lo 0 HTRI-R STATUS LED 00 n CO 0 0 0 N.O. COM N.G. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. O TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE_ DEVICE TO NEXT ADDRESSABLE DEVICE NOTE 1: VOLTAGE MAX. - CURRENT MAX, - CONT, RES. MAX, - MAX, CABLE LENGTH - C (LINE TO LINE) - C (LINE T ❑ SHIELD) - MAX, LINE SIZE - MIN, LINE SIZE - MUSIC OUTLET SAMPLING----•\ TUBE INLET SAMPLING \ \ TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE=NONE }AC POWER SOURCE COMBINE ALL SHIELDS AND IS❑LATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE f(+) ) STOP IF LAST DEVICE {(+) FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVICE (-)—/ RELAY CONTACTS (4.OA @ 125VAC) (4.OA @ 30VDC) 27 VDC 3.5 mA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0,02uF 0.04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST 25 SEC. TO GUARANTEE DETECTI❑N. lo TB1 sm� 123456 TB2 CP me ie _m + 654321 END OF LINE DEVICE (3.6K 1/4W) SUPERVISED____' / O N SWITCH GROUND ' NOTE: HTRI-D OSTATUS LED 00 0 c0 0 C NOT USED FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC DIDID ED I I J- -r -r L 0 PAD -3 0 00 O INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 0 24K HH 0 n + TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE ,NAC -4 NAC -3 2 NAC -2 NAC -1 END OF LINE DEVICE 3.6K 1/4W) SUPERVISED SWITCH FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE DEVICE LOOP!. 0.- 0 (FROM XLS CONTROL PANEL OR (+)) PREVIOUS ADDRESSABLE DEVICE (-)> 470 OHMS EOL 0 FC INPU (+r(-) 9 9 TEM -1 0 P o �N o106 0 0 -17 2 3--4-=5, [CC C TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL EARTH GROUND ->(+) TO NEXT DEVICE OR >(-) STOP IF LAST DEVICE FROM REMOTE POWER SUPPLY C'S' CABLE) FROM FACP (V❑ICE CIRCUIT) C'V' CABLE) SCALE NONE (-) STROBE (SPEAKER ) � u (STROBE) 6/-) (STR❑BE) SPEAKER SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY 80" A.F.F.' -------------------- 4S DEEP BOX W/ -1 /2" EXTENSION RING (SPEAKER SI KOBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE=NONE TO NEXT DEVICE ❑R END OF LINE TO NEXT DEVICE OR END OF LINE NOTE FOR ADDITIONAL SPEcF1CATIONS SEE PRODUCT DOCUMENTATION. OPER )11N E TEMPERATU +32` F O- C) TO 101 F C) HUMIDITY: O-9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR —> FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (-) > DATA IN (+) > DEVICE IS USTED FOR NR VOLOCITY APPUCATIONS OF 300-4000 FT/ AIN WHEN USED IN CONIINCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW TO NEXT DEVICEF > (-) DATA OUT HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID —\ CEILING HARD LID '\ SPEAKER SUPPORT TiLE 11/4 BRIDGE ------ 4" SQUARE DEEP BOX ------- WITH 1-1/2' EXTENSION \ --------- CEILING MOUNTED SPEAKER/STROBE N. CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE=NONE JUNCTI❑N BOX MOUNTED ON \\ CEILINGI FLEX \ JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT / / /ft 0 0 I TO NEXT DEVICE 0 0 CADDY BAR SMOKE DETECTOR-- SMOKE ETECT❑R— SMOKE DETECTOR MOUNTING SCALE=NONE SUSPENDED ILLUMINATED CEILING DO NOT INSTALL ADDR-SSABLE DEVICES ., \TI PREPWGRAM DEVICES ADD NIT AT VIED W CESS. l� Copyright 2006 by Guardian Security Systems, Inc. All. Rights Reserved RELEASE/REVISIONS REV. BY: I NVI DESCRIPTION SHOP DRAWINGS DATE co 0 in Lo 2 aCaCa OD OD 7.J T Q _22Z Crn W C ° Cr ZZ W � _w oC fac cf)g U) CD T" E— 0 SCALE: 1 /8"=1 DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/1 6/08 BACKROUND PLAN PROVIDED BY: ,JOB NUMBER: SHEET FA -02 J EOL—S1 20.28V • lj s . srcl nix^^xn �xs^xc <v s•r. cc[ NORTH STRIDE RIGHT WESTFIELD SOUTHCENTER MALL SCALE 118%1 FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATI❑N SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR, SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLATOR FIRE SUPPRESION SYSTEM, FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NOT INS -ALL ADD ESSABLE I\ T DEVICES UNTIL PREPROGRAV MED WI DEVICES ADDRESS. A D I NG. -H Copyright 2006 by Guardian Security Systems, Inc.. All Rights Reserved z 0 z_ w w cn0 Li] FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS z DESCRIPTION SHOP DRAWINGS w co 0 In 0 Z C C co co co J T < 0) _ 2 Z 0 w° (i)zz w= W 4=<Q cc w o CO II D W CC SCALE: 1 /8"=1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/1 6/08 BACKROUND PLAN PROVIDED BY: JOB NUMBER: SHEET FA -03} IL -7 r �l CO r R r\ CN AMILY m E3171 C.)17 �(i;AII ..�0iRLON L \;\/ - L=-1=<`_, FIELDS CLA. jou RNE`.'S BA.'SKIP R,BRN'3 w w N,•1 EN I ; `J GI__ A ._) HUT - C =_i AN r-, >-CO- KITS C AM ER, 'vl0 THERHOOD M ATER [\ f:) A l_ . _. [) ,A, LIDS Y ------------- NORTH k ,_.CC -[-L C,KE 1 00 tis 0 l_% 12101 L,_ 12::C1 1420 `t STRIDE RIGHT WESTFIELD SOUTHCENTER MALL a_ EL COm -1-'21S6 (r 0 Cl_. u c11 0 J LL_I T J vrl 0 EXISTING • FOi)?LOCKER TE ANC 111 1111111 1111 1 HEIII{ STRIDE RIGHT FACP ADD ONS Current Load: Device Type HFP-11 AD2-P HTR -R Qty 1 2 Amps 0.0022 0.0635 Standby: 0.009600 0.001600 0.005 Standby Current Load: Alarm Current Load: 0.0731 Amps 0.106 Amps Total System Current Load: Battery Pair to be Used: 12VDC • �, STRIDE RIGHT IQ SCALE 1132'=11 EX SYSTEM CALCULATIONS Total 0.0022 0.0635 0.0096 0.0731 For 24 Hours = For 5 Minutes= 25% Derating= Amp -hours Alarm: Amps 0.0023 0.064 0.021 0.0035 Amps 1.754 0.009 2.204 2.204 7AH Total 0.064 0.042 0.106 Amp -hours Amp -hours Amp -hours Amp -hours Amps Current Load: Device Type STRIDE RIGHT SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations Qty Amps Standby: Total Amps Alarm: Total Main System Board 1 0.03 0.03 0.030 0.030 SET -MC @15CD 0.064 SET -MC @30CD 2 0.098 0.196 SET -MC @75CD 0.175 SET -MC @110CD 0.233 SET-HMC-C@115CD 0.318 SET-HMC-C@135CD 0.318 SET-HMC-C@185CD 0.445 ZR -MC @15CD ZR -MC @30CD 0.064 0.098 HCP 0.0015 0.03 Amps 0.226 Amps Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours Alarm Current Load: 0.226 Amps For 5 Minutes= 0.019 Amp -hours 25% Derating= 0.924 Amp -hours Total System Current Load: 0.924 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULATION tt lau FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: I z a Notification Appliance Circuit Detail DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL Panel: STRIDE RIGHT Wire Resistance 1.62' Date: June 16, 2008 CURRENT TOTAL= 196 Q CIRCUIT: S1 D QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 0 SET -MC @15CD 64 0 Total Wire Resistance (R) 0.62 2 SET-MC@30CD 98 196 (WL*2)*(R/ft) 0 SET -MC @75CD 175 0 Total Device Load, Amps (1) 0.20 0 SET -MC @11OCD 233 0 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 Voltage Drop ( E) 0.12 0 SET-HMC-C@177CD 445 0 (E= 1 * R) 0 SET -HMC @135CD 318 0 EOL Voltage 20.28 0 SET -HMC @185CD 445 0 (20.4 - E) 0 Z-MC@15CD . 64 0 0 Z-MC@30CD 98 0 0 SET-MC-CW@110CD 233 0 DEVICES= 2 TOTAL mA= 196 12 191 20.27870736 196 Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: STRIDE RIGHT Wire Resistance 2.58.: Date: June 16, 2008 CURRENT TOTAL= 3.6 CIRCUIT: SPEAKER CIRCUIT . QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 70.7V1/8 1.8 3.6 Total Wire Resistance (R) 0.99 0 0 0 (WL*2)*(R/ft) 0 0 0 Total Device Load, Amps (I) 0.00 0 0 0 (Total Cct Load) 0 0 0 Voltage Drop ( E) 0.00 0 0 0 , (E=I*R) 0 0 0 . EOL Voltage 20.40 0 0 0 III (20.4 - E) 0 0 0 0 0 0 3.6 14 191 20.396451981 3.6 DEVICES= 2 TOTAL mA= tt lau FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: I z a DESCRIPTION SHOP DRAWINGS c0 LU O Q Ln D In W F- C/) C) J\ % SCALE: 1 /8"=1 DRAWN BY: !.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/1 6/08 BACKROUND PLAN PROVIDED BY: RISER DIAGRAM VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved �OB NUMBER: SHEET k FA -04 FIG. 69R RETAINING STRAP FIG. 100 ALL THREAD ROD NO LOCK ,..—"NUT REQ'D ti JA FIG, 65 BEAM CLAMP VIEW A—A LOCKING THREAD CONNECTION FIG. 200 ADJUSTABLE RING HANGER TOP BEAM CLAMP HANGER SCALE:NONE (E) 4" EL=14'-6" *— I1�WF X CEiL!;NG ACCESS PANEL I WITH H !N IEGRAI_ cyv. 100.1 SALFS AREA GYP. [BD. CEILING 1O' -O" A.r_±-. 12"WF 02 /1; I 0 (E)4 i!i i1 I 11-1-11-q, -0 ' I -- ill j Z.. I— 1 I tt 1-4 fx1 12"WI , -TOC-K- -R-00tittr 11 II , II II! � I I 12"WF -1 • • ii II 1-11'7..--7-71 i ', t t —_� , PIPING PLAN Scale:1/4"=1'-0" 0 rj SCOPE: 1. FSI TO ADD NEW HEADS IN NEW TENENT SPACE GENERAL NOTES: 1. ALL MATERIAL AND EQUIPMENT TO BE NEW AND UL LISTED OR FM APPROVED. 2. PIPING DIMENSIONS ARE CENTER TO CENTER EXCEPT RISER & DIMENSIONS SHOWN THUSLY (1-6), WHICH IS END TO END. 3. PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13, 2002 EDITION. 4. PIPING SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13, 2002 EDITION. 5. JOINING OF PIPE AND FITTINGS, THREADED AND WELDED SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13, 2002 EDITION. 6. OWNER TO PROVIDE ADEQUATE HEAT TO PREVENT WATER IN PIPES FROM FREEZING IN AREAS PROTECTED BY A WET PIPE SPRINKLER SYSTEM. 7. STRUCTURAL ADEQUACY OF THE BUILING TO SUPPORT THE SPRINKLER PIPING IS THE RESPONSIBILITY OF THE OWNER AND/OR HIS STRUCTURAL ENG. 8. ALL FIRE ALARMS, WIRING AND MONITORING ARE TO BE INSTALLED BY OTHERS. CONSTRUCTION NOTES: 1. ALL NEW PIPING TO BE IMPORT SCHEDULE 40 & DYNAFLOW. 2. ALL NEW FITTINGS TO BE IMPORT DUCTILE IRON AND GROOVED FITTINGS. 3. ARMOVERS LONGER THAN 2'-0" SHALL HAVE A HANGER. irga `Without Cornme its As Rated In Red Per The Attached Letter nese plans have ius'F3tl reviewed by The Tukwila Fire Pre‘.'entionni glib eat.i `or r_ o'i';1orm; nce with current t City standards. > ,i;% ep cinoe I$ !!:i!L: ,ct to errors and O?T1issio`.'i£ iAiK7-...;ti inti i'40i authorize vi 43iicn . of adopted standards and o` }tr1:'lnce:'.s. i s the The l�e,.,r1()ii.'.islji;�fl.H for adequacy of (1,.--.sion totally with r✓C"s1Qnr. r''_dditions, deletions or I'< [t51%(l P.o these drowitigs atter :lis date will void this al.ceptancs rici =• m re: ti :e a resubmittal of revised drawings for sub ieouent approval -- Final acceptance. is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: W"13 Og By:Alivi 1_ FILE cC y IUKWILA FIRE DEPARTIyiEI'3T Please call: 575-4407 and give this job No., OR- S- 3a s - ani exact address for shut' dow'i or restoration approval, CO —J w CC c.) 0 - DRAWING DRAWING SYMBOLS HYDRAULIC DESIGN INFO. HANGER LEGEND HEAD LEGEND - ALARM VALVE RISER - FLOW SWTICH RISER 1751 - DELUGE/P.A. RISER DRY PIPE RISER FIRE DEPARTMENT CONNECTION .8. - WATER MOTOR GONG D - ELECTRIC BELL F FLEXIBLE GROOVED COUPLING $ - RIGID GROOVED COUPLING - THREADED PIPE COUPLING - — - CONTROL VALVE -� - CHECK VALVE --f"PIPE HANGER (SEE CHART) -+ - PIPE HANGER (SEE CHART) ( A-1 ) - WELDED PIPE TAG 0 - BRANCHLINE NUMBER 1 9-0 1 (8-10) PIPE SIZE & LENGTH PIPE SIZE & LENGTH(CUT) - HYDRAULIC NODE 10'-0"AFF ELEVATION DATUM 0'-10" BOD - CENTERLINE OF PIPE TO DECK ❑ THIS SYSTEM IS FA THIS SYSTEM IS NOT HYDRAULICALLY DESIGNED �! HYDRAULICALLY DESIGNED A U -HOOK L "L" ROD SPRINKLER, TYPE MFG MODEL SYMBOL ORIFICE FINISH CANOPY TEMP K -FAC QTY FLOW TEST STATIC xx RESIDUAL xx GPM FLOWING xx DATE & TIME xx B COACH SCREW ROD N TOGGLE NUT RECESSED PENDENT TYCO TY -FRB • 112" CHROME CHROME 155° 5.6 12 C "C" CLAMP P HDI -P D TOP BEAM CLAMP W/ STRAP R WEDGE ANCHOR E EYE ROD S SAMMY SIDEWINDER (SWG2D) SYSTEM DESIGN F FLUSH SHELL S20 SAMMY SUPER SCREW (GST20) REMOTE AREA xx DENSITY xx MAX. AREA/HEAD xx K -FACTOR xx xx G CEILING FLANGE SX SAMMY X -PRESS H SIDE BEAM BRACKET T TRAPEZE J "J" BOLT U UNISTRUT POST K SHORT CLIP TOTAL THIS SHEET 12 / Fire Sprinklers • WA CL# FIRESI*988RJ 1014 North Street Sumner, WA 98390 (253) 826-0099 email:mike@firesprinklersinc.com PROJECT: Stride Rite • ■ Tukwila, WA. 1 • ) ()11 S,C, oa11 CONTRACT WITH: Flinthills Construction R.1 TECE WekI L rasps must be inspected before • •e is hung. Do not paint piping prior to hydrostatic test DESIGNER: Mike DATE: 619108 SCALE: As Noted HAZARD: OHG II AHJ: City of Tukwila JOB # 1979 SHEET # FP1 �lw 0 41 NORDSTROM Ma CO Oiir.� I .i 1. DDD O O O 0 0 O O - IIII a _ ..... iiFILI r91 -.1■ II 117 ■ 111 IIIIIip--� lar .• u STRIDE RITE • 1300 LEVEL 1__...,_�=..._ -.r . EIVIER ML ti irga `Without Cornme its As Rated In Red Per The Attached Letter nese plans have ius'F3tl reviewed by The Tukwila Fire Pre‘.'entionni glib eat.i `or r_ o'i';1orm; nce with current t City standards. > ,i;% ep cinoe I$ !!:i!L: ,ct to errors and O?T1issio`.'i£ iAiK7-...;ti inti i'40i authorize vi 43iicn . of adopted standards and o` }tr1:'lnce:'.s. i s the The l�e,.,r1()ii.'.islji;�fl.H for adequacy of (1,.--.sion totally with r✓C"s1Qnr. r''_dditions, deletions or I'< [t51%(l P.o these drowitigs atter :lis date will void this al.ceptancs rici =• m re: ti :e a resubmittal of revised drawings for sub ieouent approval -- Final acceptance. is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: W"13 Og By:Alivi 1_ FILE cC y IUKWILA FIRE DEPARTIyiEI'3T Please call: 575-4407 and give this job No., OR- S- 3a s - ani exact address for shut' dow'i or restoration approval, CO —J w CC c.) 0 - DRAWING DRAWING SYMBOLS HYDRAULIC DESIGN INFO. HANGER LEGEND HEAD LEGEND - ALARM VALVE RISER - FLOW SWTICH RISER 1751 - DELUGE/P.A. RISER DRY PIPE RISER FIRE DEPARTMENT CONNECTION .8. - WATER MOTOR GONG D - ELECTRIC BELL F FLEXIBLE GROOVED COUPLING $ - RIGID GROOVED COUPLING - THREADED PIPE COUPLING - — - CONTROL VALVE -� - CHECK VALVE --f"PIPE HANGER (SEE CHART) -+ - PIPE HANGER (SEE CHART) ( A-1 ) - WELDED PIPE TAG 0 - BRANCHLINE NUMBER 1 9-0 1 (8-10) PIPE SIZE & LENGTH PIPE SIZE & LENGTH(CUT) - HYDRAULIC NODE 10'-0"AFF ELEVATION DATUM 0'-10" BOD - CENTERLINE OF PIPE TO DECK ❑ THIS SYSTEM IS FA THIS SYSTEM IS NOT HYDRAULICALLY DESIGNED �! HYDRAULICALLY DESIGNED A U -HOOK L "L" ROD SPRINKLER, TYPE MFG MODEL SYMBOL ORIFICE FINISH CANOPY TEMP K -FAC QTY FLOW TEST STATIC xx RESIDUAL xx GPM FLOWING xx DATE & TIME xx B COACH SCREW ROD N TOGGLE NUT RECESSED PENDENT TYCO TY -FRB • 112" CHROME CHROME 155° 5.6 12 C "C" CLAMP P HDI -P D TOP BEAM CLAMP W/ STRAP R WEDGE ANCHOR E EYE ROD S SAMMY SIDEWINDER (SWG2D) SYSTEM DESIGN F FLUSH SHELL S20 SAMMY SUPER SCREW (GST20) REMOTE AREA xx DENSITY xx MAX. AREA/HEAD xx K -FACTOR xx xx G CEILING FLANGE SX SAMMY X -PRESS H SIDE BEAM BRACKET T TRAPEZE J "J" BOLT U UNISTRUT POST K SHORT CLIP TOTAL THIS SHEET 12 / Fire Sprinklers • WA CL# FIRESI*988RJ 1014 North Street Sumner, WA 98390 (253) 826-0099 email:mike@firesprinklersinc.com PROJECT: Stride Rite • ■ Tukwila, WA. 1 • ) ()11 S,C, oa11 CONTRACT WITH: Flinthills Construction R.1 TECE WekI L rasps must be inspected before • •e is hung. Do not paint piping prior to hydrostatic test DESIGNER: Mike DATE: 619108 SCALE: As Noted HAZARD: OHG II AHJ: City of Tukwila JOB # 1979 SHEET # FP1