FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS
Project Name: Stride Right
1077 Southcenter Mall
Permit No.: 08-S-325
Date: June 13, 2008
Reviewer: Al Metzler
Fire Protection Project Coordinator
(206)575-4407
• Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross
mains, and branch lines 2.5" and larger. Bracing is provided for the last length of
pipe but within 6' of the end of a feed or cross main. Bracing is required unless
all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for
any size pipe, 9.3.5.3.
• Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4
exceptions, 9.3.4.
• Longitudinal sway bracing Is a maximum of 80' for mains and cross mains and
within 40 ' of the end of the line, 9.3.5.4.
• Provide lateral and longitudinal bracing for changes in pipe direction per section
9.3.5.11.2 for pipe size 2'/2 inches and larger.
• Restrain branch lines at the end sprinkler of each line, restrain against vertical
and lateral movement, 9.3.6.3.
• Restraints for branch lines shall be at intervals per table 9.3.6.4 and section
9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6.
• Comply with ASCE 7-02, section 9.6.2.6.2 (e).
• Provide sprinkler protection beneath all obstructions greater than 4 ft. in width.
• Extend sprinkler protection to all combustible concealed spaces.
• Comply with NFPA 13 obstruction tables.
• Sprinkler heads spaced closer than 6 ft. apart must be baffled.
• These conditions apply to all sprinkler piping exposed as necessary to
accomplish the permitted scope of work.
All references are NFPA 13, 2007 Edition.
/077 Sc mtf(
LL
VNL CI
1/44s. W7 3 toANal
0
Ato
S ..in ')f
ti.7 ...
A
a
N Z.
1..
MOB. O B.. g g
0.) gaEE31:1 vg
c 73 MEPIA
W734) -t82ggliSilib
G
EE cp �cu ��a �o.sC
V -a Q,o = Z a
ZL
III1!1U
111111111
0
A
(
STRIDE RIGHT
FIRE ALARM SYSTEM
TUKWILA, WASHINGTON
SHEET INDEX
GENERAL NOTES
SYMBOLS LEGEND
SHEET
UVV3ER SHEET TITLE
FA -01
SYSTEM I \ FORMATIO \
FA -02
TYPICAL DETAILS - WIRING A\
D MOU
\TI \ G
FA -03
FRE ALARM SYSTEM FLOOR PLA
FA -04
SYSTEM CALCULATIONS
r
GE\EAL),
RISER, SITE PLA\
WIRE DESIGNATION SCHEDULE
WIRE SCHEDULE AND CONDUIT FILL CHART
SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END
FOR SIEMENS SYSTEM:
DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH
DEVICES ADDRESS.
1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS
DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1.
2. • DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED.
3, AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED, NO PARALLEL
BRANCHING IS PERMISSIBLE
4. .INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL
ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY. HAVING JURISDICTION.
5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS,
STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT)
ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION.
6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT
AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1-
7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY,
TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY,
AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION.
8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED
DRAWINGS FOR "AS BUILT" PURPOSES.
g. • FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT
SHEETS AND/OR INSTALLATION INSTRUCTIONS.
10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS
MUST COMPLY WITH ARTICLE 725 AND 760 OF -NFPA 70, N.E.C. AND NFPA 72,
SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER
SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT
DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN.
11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT
OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, ,WHICHEVER IS LESS.
12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE
ACTIVATION DEVICE.
13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET.
14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY
GENERATOR.
15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER
THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL.
EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION
FOR PROTECTION DURING CONSTRUCTION.
DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL
TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72
CHAPTER 7.
16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT
AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR
OTHER BACK BOXES OF DIFFERENT CIRCUITS.
17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND
AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO
FINAL EQUIPMENT TRIM.
18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A
PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP.
19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE
OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES
AFTER COMPLETION OF THEIR INSTALLATION.
20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH
IT IS LOCATED.
21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT.
22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING
PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE
INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING
FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE
ROUTED SEPARATELY. THE OUTGOING AND RETURN. (REDUNDANT) CIRCUIT
CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E.,
MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY.
23.
NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE
ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES.
THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE
CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM
SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE
THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE
CABLE IS INSTALLED
QUANTITY
2
2
EX
SYMBOL DESCRIPTION
MODEL
MANUFACTURER
BACKBOX
MOUNTING HEIGHT
FACP
FIRE ALARM
EX CONTROL PANEL
XLS-V
SIEMENS
PROVIDED
66" A.F.F.
TO TOP
FARA
FIRE ALARM
REMOTE ANNUNCIATOR
SDD-C
SIEMENS
PROVIDED
66" A.F.F.
TO TOP
BPS
REMOTE BOOSTER
EX POWER SUPPLY
PAD -3
SIEMENS
PROVIDED
66" A.F.F.
TO TOP
INTERFACE MODULE HTRI-R
WITH RELAY
SIEMENS
4S DEEP
VERIFY
IN FIELD
DUAL INPUT
INTERFACE MODULE
HTRI-D
SIEMENS
4S DEEP
VERIFY
IN FIELD
HCP
CONTROL POINT
MODULE
HCP
SIEMENS
4S DEEP
VERIFY
IN FIELD
HZM
REMOTE CONVENTIONAL HZM
ZONE MODULE
SIEMENS
4S DEEP
VERIFY
IN FIELD
IB
LINEAR BEAM
SMOKE DETECTOR
PBA -1191 SIEMENS
PROVIDED
VERIFY
IN FIELD
SMOKE DETECTOR HFP-11 W/ SIEMENS
(ADDRESSABLE -PHOTO) DB -11 BASE
4S DEEP
W/ 1G RING
CEILING
AD
DUCT SMOKE
DETECTOR
AD2-P W/ SIEMENS
TSM MODULE
DUCT HOUSING VERIFY
IN FIELD
HEAT DETECTOR
(ADDRESSABLE)
HFPT-11 W/ SIEMENS
DB -11 BASE
4S DEEP
W/ 1G RING
CEILING
Ec
FIRE ALARM
SPEAKER STROBE
(CEILING MOUNT)
SET -MC -CW SIEMENS
4S DEEP BOX CEILING
W/ 1-1/2" EXT.
FIRE ALARM
SPEAKER STROBE
(WALL MOUNT)
SET -MC -W SIEMENS
4S DEEP BOX 80" A.F.F.
W/ 1-1/2" EXT. TO BOTTOM
FIRE ALARM
SPEAKER STROBE
(WALL MOUNT)
SET -HMC --CW SIEMENS
4S DEEP BOX
W/ 1-1/2" EXT.
CEILING
L
FIRE ALARM
STROBE
(CEILING MOUNT)
ZR -MC -CW SIEMENS
4S BOX
W/ 1G RING
CEILING
FIRE ALARM
STROBE
(WALL MOUNT)
ZR -MC -W SIEMENS
4S BOX
W/ 1G RING
80" A.F.F.
TO BOTTOM U.O.N.
YC
FIRE ALARM
SPEAKER
(CEILING MOUNT)
SET -CW
SIEMENS
4S DEEP BOX CEILING
W/ 1-1/2" EXT.
FIRE ALARM
SPEAKER
(WALL MOUNT)
SET -W
SIEMENS
4S DEEP BOX
W/ 1-1/2" EXT.
80" A.F.F.
TO BOTTOM
C3WP
MR
FIRE ALARM
STROBE
(WEATHERPROOF)
MULTI -VOLTAGE
CONTROL RELAY
SET -S17 -WP SIEMENS
MT -SUR -BOX VERIFY
1/2" PIPE
IN FIELD
MR -201/C AIR PRODUCTS
4S BOX
VERIFY
IN FIELD
MAGNETIC
DOOR HOLDER
F.B.O.
F.B.O.
F.B.O.
FA JBOX
FIRE ALARM
TERMINAL CABINET
F.B.O.
F.B.O.
VERIFY
IN FIELD
VERITY
IN FIELD
JUNCTI❑N BOX
F.B.D.
EPTE
V( i
INERFIj=LD
A.F.F.
ABOVE FINISHED
N/A
.N0
Without Ccik.Aents
N/A 11
`-"U M
WIRE DESIGNATION
-- '/0' As Noted In Red
SYMBOL DESCRIPTION
NUMBER OF CONDUCTORS SIZE
TYPE COLOR CODE
D
H
P
S
A
V
I
X
UD
UI
M
B
DATA LINE -ADDRESSABLE LOOP
DOOR HOLDER POWER - 24VDC
DEVICE POWER - 24VDC
STROBE CIRCUIT - FEED
ANNUNCIATOR
SPEAKER CIRCUIT - FEED
REMOTE INDICATION LIGHT
LOW LEVEL AUDI❑
UNDERGROUND DATA
UNDERGROUND INITIATI❑N
DOOR HOLDER POWER
BEAM DETECTOR POWER
TWISTED PAIR WITH SHIELD #16
TWO #14
TWO #16
TWISTED PAIR W/ SHIELD #12
TWISTED PAIR W/ SHIELD #16
TWISTED PAIR #14
TWO #18
TWISTED PAIR W/ SHIELD #16
TWISTED PAIR RATED #18
TWISTED PAIR RATED #18
TWO #16
TWO #14
FPL/FPLR RED (JACKET)
FPL/FPLR RED (JACKET)
FPL/FPLR RED (JACKET)
FPL/FPLR RED (JACKET)
FPL/FPLR RED (JACKET)
FPL/FPLR RED (JACKET)
FPL/FPLR RED (JACKET)
FPL/FPLR RED (JACKET)
FPL/FPLR RED (JACKET)
FPL/FPLR RED (JACKET)
FPL/FPLR RED (JACKET)
FPL/FPLR RED (JACKET)
N/A
CONDUIT FILL CHART
N/A
} i nese plans
PiVrention Bureau for conildrri nce with current cit',N/A !.
standards. Acceptance is subject to errors and
of adopted
NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE
TWO . 600V #12 AWG THHN/THWN
TWO 600V #14 AWG THHN/THWN TWISTED
TWO CONDUCTOR 300V #18 AWG FPL TW CABLE
CONDUIT FILL
CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT
ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM
THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF
CONDUIT SIZE MAXIMUM F
1/2" .12 SQUARE
3/4" .21 SQUARE
1" .34 SQUARE
1-1/4" .60 SQUARE
1-1/2" .82 SQUARE
2" 1.34 SQUARE
FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM
DIMENSIONS ' AREA
.244 0.D. .0467
.210 0.D. .0346
.156 0.D. .0191
FROM THE TABLE
FILL DIMENSION FROM
THE WIRE.
LL
NCH
NCH
NCH
NCH
NCH
INCH
N.E.C., CHP. 9, TABLE 4.
SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END
FOR SIEMENS SYSTEM:
DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH
DEVICES ADDRESS.
1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS
DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1.
2. • DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED.
3, AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED, NO PARALLEL
BRANCHING IS PERMISSIBLE
4. .INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL
ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY. HAVING JURISDICTION.
5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS,
STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT)
ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION.
6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT
AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1-
7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY,
TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY,
AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION.
8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED
DRAWINGS FOR "AS BUILT" PURPOSES.
g. • FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT
SHEETS AND/OR INSTALLATION INSTRUCTIONS.
10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS
MUST COMPLY WITH ARTICLE 725 AND 760 OF -NFPA 70, N.E.C. AND NFPA 72,
SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER
SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT
DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN.
11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT
OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, ,WHICHEVER IS LESS.
12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE
ACTIVATION DEVICE.
13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET.
14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY
GENERATOR.
15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER
THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL.
EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION
FOR PROTECTION DURING CONSTRUCTION.
DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL
TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72
CHAPTER 7.
16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT
AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR
OTHER BACK BOXES OF DIFFERENT CIRCUITS.
17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND
AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO
FINAL EQUIPMENT TRIM.
18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A
PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP.
19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE
OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES
AFTER COMPLETION OF THEIR INSTALLATION.
20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH
IT IS LOCATED.
21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT.
22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING
PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE
INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING
FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE
ROUTED SEPARATELY. THE OUTGOING AND RETURN. (REDUNDANT) CIRCUIT
CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E.,
MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY.
23.
NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE
ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES.
THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE
CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM
SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE
THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE
CABLE IS INSTALLED
QUANTITY
2
2
EX
SYMBOL DESCRIPTION
MODEL
MANUFACTURER
BACKBOX
MOUNTING HEIGHT
FACP
FIRE ALARM
EX CONTROL PANEL
XLS-V
SIEMENS
PROVIDED
66" A.F.F.
TO TOP
FARA
FIRE ALARM
REMOTE ANNUNCIATOR
SDD-C
SIEMENS
PROVIDED
66" A.F.F.
TO TOP
BPS
REMOTE BOOSTER
EX POWER SUPPLY
PAD -3
SIEMENS
PROVIDED
66" A.F.F.
TO TOP
INTERFACE MODULE HTRI-R
WITH RELAY
SIEMENS
4S DEEP
VERIFY
IN FIELD
DUAL INPUT
INTERFACE MODULE
HTRI-D
SIEMENS
4S DEEP
VERIFY
IN FIELD
HCP
CONTROL POINT
MODULE
HCP
SIEMENS
4S DEEP
VERIFY
IN FIELD
HZM
REMOTE CONVENTIONAL HZM
ZONE MODULE
SIEMENS
4S DEEP
VERIFY
IN FIELD
IB
LINEAR BEAM
SMOKE DETECTOR
PBA -1191 SIEMENS
PROVIDED
VERIFY
IN FIELD
SMOKE DETECTOR HFP-11 W/ SIEMENS
(ADDRESSABLE -PHOTO) DB -11 BASE
4S DEEP
W/ 1G RING
CEILING
AD
DUCT SMOKE
DETECTOR
AD2-P W/ SIEMENS
TSM MODULE
DUCT HOUSING VERIFY
IN FIELD
HEAT DETECTOR
(ADDRESSABLE)
HFPT-11 W/ SIEMENS
DB -11 BASE
4S DEEP
W/ 1G RING
CEILING
Ec
FIRE ALARM
SPEAKER STROBE
(CEILING MOUNT)
SET -MC -CW SIEMENS
4S DEEP BOX CEILING
W/ 1-1/2" EXT.
FIRE ALARM
SPEAKER STROBE
(WALL MOUNT)
SET -MC -W SIEMENS
4S DEEP BOX 80" A.F.F.
W/ 1-1/2" EXT. TO BOTTOM
FIRE ALARM
SPEAKER STROBE
(WALL MOUNT)
SET -HMC --CW SIEMENS
4S DEEP BOX
W/ 1-1/2" EXT.
CEILING
L
FIRE ALARM
STROBE
(CEILING MOUNT)
ZR -MC -CW SIEMENS
4S BOX
W/ 1G RING
CEILING
FIRE ALARM
STROBE
(WALL MOUNT)
ZR -MC -W SIEMENS
4S BOX
W/ 1G RING
80" A.F.F.
TO BOTTOM U.O.N.
YC
FIRE ALARM
SPEAKER
(CEILING MOUNT)
SET -CW
SIEMENS
4S DEEP BOX CEILING
W/ 1-1/2" EXT.
FIRE ALARM
SPEAKER
(WALL MOUNT)
SET -W
SIEMENS
4S DEEP BOX
W/ 1-1/2" EXT.
80" A.F.F.
TO BOTTOM
C3WP
MR
FIRE ALARM
STROBE
(WEATHERPROOF)
MULTI -VOLTAGE
CONTROL RELAY
SET -S17 -WP SIEMENS
MT -SUR -BOX VERIFY
1/2" PIPE
IN FIELD
MR -201/C AIR PRODUCTS
4S BOX
VERIFY
IN FIELD
MAGNETIC
DOOR HOLDER
F.B.O.
F.B.O.
F.B.O.
FA JBOX
FIRE ALARM
TERMINAL CABINET
F.B.O.
F.B.O.
VERIFY
IN FIELD
VERITY
IN FIELD
JUNCTI❑N BOX
F.B.D.
EPTE
V( i
INERFIj=LD
A.F.F.
ABOVE FINISHED
N/A
.N0
Without Ccik.Aents
N/A 11
`-"U M
-- '/0' As Noted In Red
F B ❑
FURNISHED BY
OTHERS
N/A
N/A 0 Per The Altp, ed Letter N/A
have bccn reviewed by The Tukwiie Fire
N/A
NOT
APPLICABLE
N/A
} i nese plans
PiVrention Bureau for conildrri nce with current cit',N/A !.
standards. Acceptance is subject to errors and
of adopted
U.D.N.
UNLESS OTHERWISE
NOTED
N/A
ornissions Wliich do not authorize violations
sW,ERM,aras and orainances.NTh responsibility for thR/A
adequacy of design rests totally with the designer.
these drawings atter
{
A complct
Fire Del
Certificate
WP
WEATHERPROOF
DEVICE
N/A
Additions, deIeiioiis or revisions to
Ukisqlete will void this.acceltsltdAce and will require aN/A
resubmittal of revised drawings for subsequent approval.
RED
AS BUILTt0
ADD OR CHANGE
N/A
FIh acceptance is subjecitJtoEfield test and inspectjgh1 y
The Tukwila Fire Prevention Bureau.
the
commence
TenGREEN
D�
t=aiInre
AS BUILT
REMOVand
N/A1/ig/o3_•_\jYAj7c1)
N/
W
BLUE
AS BUILT
NOTES TO CAD
N/A
N/A
N/A
N/A
y
oC4►
FAX (206) 628-4990
TEL. (206) 622-6545
RELEASE/REVISIONS
z
Q
DESCRIPTION
SHOP DRAWINGS
L1J
cO
0
C
aC
aC
co
T
Q
nz
w fro
Lut5
cc zz
W vcn
=Q
Q ��
CC dog
v,
O=
4OTICE
ed, signed, Tukwila
�artment Pre-test
must be presente
Inspector prior to
ment of Acceptance
of any Fire Alarm
�tection Systems.
of test will result
in a Re -inspection Fee and
termination of the testing.
TUKWILA FIRE DEPARTM:.4J
Please call: 5754402
and give this job
a .d exact address for shut*
in or restoration approval .
Copyright 2006 by Guardian Security Systems, Inc. All Rig hts Reserved
Z
0
CC
0
Z
H
>rn
DRAWN BY:
(.ANDERSON
DESIGNED BY:
R.VEZZANI
DATE: 6/1 6/08
BACKROUND PLAN PROVIDED BY:
\z_JOB NUMBER:
SHEET
C FA -01
THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72.
THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX
DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED.
BEND OR OTHER
OBSTRUCTION
ANY DUCK OVER 3' WIDE, SAMPLE TUBE
MUST GO THRU THE DUCT AND BE CAPPED.
6-10 DUCT
EQUIVALENT
DIAMETERS
TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT
LABEL SCALE
COMBINE ALL SHIELDS AND
IS❑LATE FROM GROUNDING
TO NEXT ADDRESSABLE DEVICE
STOP IF LAST DEVICE
FROM XLS CONTROL PANEL OR
PREVI❑US ADDRESSABLE DEVIL
END OF LINE DEVICE(3.6K 1/4W)
SUPERVISED SWITCH
O
DUCT DETECTOR
LOCATION
0
GROUND_.(?)
Lo
0
HTRI-R
STATUS LED
00
n
CO
0
0
0
N.O.
COM
N.G.
NOTE:
FOR ADDITIONAL SPECIFICATIONS
SEE PRODUCT DOCUMENTATION.
O
TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL
LABEL
SCALE (BACKGOUND MUSIC SHUTDOWN)
PREVI❑US ADDRESSABLE_
DEVICE
TO NEXT ADDRESSABLE
DEVICE
NOTE 1:
VOLTAGE MAX. -
CURRENT MAX, -
CONT, RES. MAX, -
MAX, CABLE LENGTH -
C (LINE TO LINE) -
C (LINE T ❑ SHIELD) -
MAX, LINE SIZE -
MIN, LINE SIZE -
MUSIC
OUTLET SAMPLING----•\
TUBE
INLET SAMPLING \ \
TUBE
AT LEAST
SIX DUCT
WIDTHS
FROM BEND
TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR
SCALE=NONE
}AC POWER SOURCE
COMBINE ALL SHIELDS AND
IS❑LATE FROM GROUNDING
TO NEXT ADDRESSABLE DEVICE f(+) )
STOP IF LAST DEVICE {(+)
FROM XLS CONTROL PANEL OR
PREVIOUS ADDRESSABLE DEVICE (-)—/
RELAY CONTACTS
(4.OA @ 125VAC)
(4.OA @ 30VDC)
27 VDC
3.5 mA DURING POLLING
10 OHMS
200 FT. (18 AWG)
0,02uF
0.04uF
14 AWG
18 AWG
NOTE 21
ALL SUPERVISED SWITCHES MUST BE HELD CLOSED
AND/OR OPEN FOR AT LEAST 25 SEC. TO GUARANTEE
DETECTI❑N.
lo
TB1
sm�
123456
TB2
CP
me ie _m +
654321
END OF LINE
DEVICE
(3.6K 1/4W)
SUPERVISED____' /
O
N
SWITCH
GROUND '
NOTE:
HTRI-D
OSTATUS LED
00
0
c0
0
C
NOT USED
FOR ADDITIONAL SPECIFICATIONS
SEE PRODUCT DOCUMENTATION.
TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL
LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE)
0
GND N AC
DIDID
ED
I I
J-
-r -r
L
0
PAD -3
0
00
O
INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX
1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + -
0
24K
HH
0
n
+
TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP)
LABEL SCALE
,NAC -4
NAC -3
2 NAC -2
NAC -1
END OF
LINE DEVICE
3.6K 1/4W)
SUPERVISED
SWITCH
FRONT VIEW
NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION.
NOT USED
REMOTE
DEVICE LOOP
NOT USED
REMOTE
DEVICE LOOP!.
0.-
0
(FROM XLS CONTROL PANEL OR (+))
PREVIOUS ADDRESSABLE DEVICE (-)>
470
OHMS
EOL
0
FC
INPU
(+r(-)
9 9
TEM -1
0
P
o �N
o106
0
0
-17
2 3--4-=5,
[CC C
TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL
EARTH
GROUND
->(+) TO NEXT DEVICE OR
>(-) STOP IF LAST DEVICE
FROM REMOTE
POWER SUPPLY
C'S' CABLE)
FROM FACP
(V❑ICE CIRCUIT)
C'V' CABLE)
SCALE NONE
(-)
STROBE
(SPEAKER )
� u
(STROBE)
6/-)
(STR❑BE)
SPEAKER
SPEAKERISTROBE AND STROBE WIRING
LABEL SCALE
SPEAKER STROBE
OR STROBE ONLY
80" A.F.F.'
--------------------
4S DEEP BOX
W/ -1 /2"
EXTENSION RING
(SPEAKER SI KOBE)
4S BOX
(STROBE ONLY)
SPEAKER/STROBE
WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS
SCALE=NONE
TO NEXT
DEVICE ❑R
END OF LINE
TO NEXT
DEVICE OR
END OF LINE
NOTE FOR ADDITIONAL SPEcF1CATIONS SEE PRODUCT DOCUMENTATION.
OPER )11N E
TEMPERATU
+32` F O- C) TO 101 F C)
HUMIDITY: O-9 % RELATIVE HUMIDITY,
NON -CONDENSING
HFP-11 SMOKE
DETECTOR
—> FROM PREVIOUS
ADDRESSABLE DEVICE
OR POWER SOURCE
DATA IN (-) >
DATA IN (+) >
DEVICE IS USTED FOR NR VOLOCITY
APPUCATIONS OF 300-4000 FT/ AIN
WHEN USED IN CONIINCTION WITH
DUCT HOUSINGS AD -11P OR AD-11XPR
DB -11
STANDARD
SMOKE
DETECTOR
BASE
REAR VIEW
TO NEXT DEVICEF
> (-) DATA OUT
HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL
LABEL SCALE
> (+) DATA OUT
CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID)
HARD LID —\
CEILING
HARD LID '\
SPEAKER SUPPORT TiLE 11/4
BRIDGE
------ 4" SQUARE DEEP BOX -------
WITH 1-1/2' EXTENSION \
--------- CEILING MOUNTED
SPEAKER/STROBE N.
CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING)
SCALE=NONE
JUNCTI❑N BOX
MOUNTED ON \\
CEILINGI FLEX \
JUNCTI❑N BOX
MOUNTED AGAINST
CEILING SUPPORT
/ / /ft 0 0 I TO NEXT DEVICE
0 0
CADDY BAR
SMOKE DETECTOR--
SMOKE
ETECT❑R—
SMOKE DETECTOR MOUNTING
SCALE=NONE
SUSPENDED
ILLUMINATED CEILING
DO NOT INSTALL
ADDR-SSABLE
DEVICES ., \TI
PREPWGRAM
DEVICES ADD
NIT AT
VIED W
CESS.
l�
Copyright 2006 by Guardian Security Systems, Inc. All. Rights Reserved
RELEASE/REVISIONS
REV. BY:
I NVI
DESCRIPTION
SHOP DRAWINGS
DATE
co
0
in
Lo
2
aCaCa
OD
OD
7.J T
Q
_22Z
Crn W
C °
Cr ZZ
W � _w
oC fac cf)g
U)
CD
T"
E—
0
SCALE: 1 /8"=1
DRAWN BY:
I.ANDERSON
DESIGNED BY:
R.VEZZANI
DATE: 6/1 6/08
BACKROUND PLAN PROVIDED BY:
,JOB NUMBER:
SHEET
FA -02 J
EOL—S1
20.28V
• lj
s .
srcl nix^^xn �xs^xc <v s•r. cc[
NORTH
STRIDE RIGHT WESTFIELD SOUTHCENTER MALL
SCALE 118%1
FLAG NOTES:
FIELD LOCATE RELAY MODULE FOR
BACK GROUND MUSIC INTERFACE.
FIELD LOCATE SIEMENS DUCT
DETECTOR ON RETURN SIDE OF
ALL VAV UNITS,(SEE SIEMENS
INSTALLATI❑N SUBMITTAL FOR
LOCATION GUIDELINES AND FA -02)
DEVICES SUPPLIED BY GSS,
INSTALLED BY MECHANICAL
CONTRACTOR.
WIRED BY ELECTRICAL
CONTRACTOR,
SIEMENS HTRI—D ADDRESSABLE
INPUT WITH HOOD VENILLATOR
FIRE SUPPRESION SYSTEM, FIELD
LOCATE WITHIN 3 FEET OF
CONTRL PANEL.
FIELD LOCATE SIEMENS PAD -3
BOOSTER POWER SUPPLY FOR
STROBE POWER, AC POWER BY EC
FROM DEDICATED, LOCKED OUT
20A, 110 VAC BRANCH CIRCUIT.
DO NOT INS -ALL
ADD ESSABLE I\ T
DEVICES UNTIL
PREPROGRAV MED WI
DEVICES ADDRESS.
A D I NG.
-H
Copyright 2006 by Guardian Security Systems, Inc.. All Rights Reserved
z
0
z_
w
w
cn0
Li]
FAX (206) 628-4990
TEL. (206) 622-6545
RELEASE/REVISIONS
z
DESCRIPTION
SHOP DRAWINGS
w
co
0
In
0
Z
C
C
co
co
co
J T
< 0)
_ 2 Z
0 w°
(i)zz
w=
W 4=<Q
cc w o
CO II
D
W
CC
SCALE: 1 /8"=1
DRAWN BY:
(.ANDERSON
DESIGNED BY:
R.VEZZANI
DATE: 6/1 6/08
BACKROUND PLAN PROVIDED BY:
JOB NUMBER:
SHEET
FA -03}
IL
-7
r
�l
CO
r
R r\
CN
AMILY
m
E3171 C.)17
�(i;AII
..�0iRLON
L \;\/ - L=-1=<`_,
FIELDS
CLA.
jou RNE`.'S
BA.'SKIP
R,BRN'3
w
w
N,•1 EN
I ; `J GI__ A ._)
HUT -
C =_i AN
r-,
>-CO-
KITS
C AM ER,
'vl0 THERHOOD M ATER [\
f:) A l_ . _. [) ,A,
LIDS
Y
-------------
NORTH
k ,_.CC -[-L C,KE
1 00
tis
0
l_%
12101
L,_
12::C1
1420
`t
STRIDE RIGHT WESTFIELD SOUTHCENTER MALL
a_
EL
COm
-1-'21S6
(r
0
Cl_.
u
c11
0
J
LL_I
T
J
vrl
0
EXISTING
• FOi)?LOCKER
TE ANC
111 1111111
1111 1
HEIII{
STRIDE RIGHT
FACP ADD ONS
Current Load:
Device Type
HFP-11
AD2-P
HTR -R
Qty
1
2
Amps
0.0022
0.0635
Standby:
0.009600
0.001600
0.005
Standby Current Load:
Alarm Current Load:
0.0731
Amps
0.106
Amps
Total System Current Load:
Battery Pair to be Used:
12VDC
•
�,
STRIDE RIGHT
IQ
SCALE 1132'=11
EX
SYSTEM CALCULATIONS
Total
0.0022
0.0635
0.0096
0.0731
For 24 Hours =
For 5 Minutes=
25% Derating=
Amp -hours
Alarm:
Amps
0.0023
0.064
0.021
0.0035
Amps
1.754
0.009
2.204
2.204
7AH
Total
0.064
0.042
0.106
Amp -hours
Amp -hours
Amp -hours
Amp -hours
Amps
Current Load:
Device Type
STRIDE RIGHT
SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations
Qty
Amps
Standby:
Total
Amps
Alarm:
Total
Main System Board
1
0.03
0.03
0.030
0.030
SET -MC @15CD
0.064
SET -MC @30CD
2
0.098
0.196
SET -MC @75CD
0.175
SET -MC @110CD
0.233
SET-HMC-C@115CD
0.318
SET-HMC-C@135CD
0.318
SET-HMC-C@185CD
0.445
ZR -MC @15CD
ZR -MC @30CD
0.064
0.098
HCP
0.0015
0.03
Amps
0.226
Amps
Standby Current Load:
0.03 Amps
For 24 Hours =
0.720
Amp -hours
Alarm Current Load:
0.226 Amps
For 5 Minutes=
0.019
Amp -hours
25% Derating=
0.924
Amp -hours
Total System Current Load:
0.924
Amp -hours
Battery Pair to be Used:
12VDC
Amp -hours
7AH
BATTERY SIZING CALCULATION
tt
lau
FAX (206) 628-4990
TEL. (206) 622-6545
RELEASE/REVISIONS
REV. BY: I
z
a
Notification Appliance Circuit Detail
DESCRIPTION
PROJECT:
WESTFIELD SOUTHCENTER MALL
Panel:
STRIDE RIGHT
Wire Resistance 1.62'
Date:
June 16, 2008
CURRENT TOTAL=
196
Q
CIRCUIT:
S1
D
QTY
Device Type
Alarm Current
Alarm Total
Wire Size
Wire Length
Voltage at EOL
Circuit Total
0
SET -MC @15CD
64
0
Total Wire Resistance (R)
0.62
2
SET-MC@30CD
98
196
(WL*2)*(R/ft)
0
SET -MC @75CD
175
0
Total Device Load, Amps (1)
0.20
0
SET -MC @11OCD
233
0
(Total Cct Load)
0
SET-HMC-C@115CD
318
0
Voltage Drop ( E)
0.12
0
SET-HMC-C@177CD
445
0
(E= 1 * R)
0
SET -HMC @135CD
318
0
EOL Voltage
20.28
0
SET -HMC @185CD
445
0
(20.4 - E)
0
Z-MC@15CD .
64
0
0
Z-MC@30CD
98
0
0
SET-MC-CW@110CD
233
0
DEVICES=
2
TOTAL mA=
196
12
191
20.27870736
196
Notification Appliance Circuit Detail
PROJECT:
WESTFIELD SOUTHCENTER MALL
Panel:
STRIDE RIGHT
Wire Resistance 2.58.:
Date:
June 16, 2008
CURRENT TOTAL=
3.6
CIRCUIT:
SPEAKER CIRCUIT
.
QTY
Device Type
Alarm Current
Alarm Total
Wire Size
Wire Length
Voltage at EOL
Circuit Total
2
70.7V1/8
1.8
3.6
Total Wire Resistance (R)
0.99
0
0
0
(WL*2)*(R/ft)
0
0
0
Total Device Load, Amps (I)
0.00
0
0
0
(Total Cct Load)
0
0
0
Voltage Drop
( E)
0.00
0
0
0
,
(E=I*R)
0
0
0
.
EOL Voltage
20.40
0
0
0
III
(20.4 - E)
0
0
0
0
0
0
3.6
14
191
20.396451981
3.6
DEVICES=
2
TOTAL mA=
tt
lau
FAX (206) 628-4990
TEL. (206) 622-6545
RELEASE/REVISIONS
REV. BY: I
z
a
DESCRIPTION
SHOP DRAWINGS
c0
LU
O
Q
Ln
D
In
W
F-
C/)
C)
J\ %
SCALE: 1 /8"=1
DRAWN BY:
!.ANDERSON
DESIGNED BY:
R.VEZZANI
DATE: 6/1 6/08
BACKROUND PLAN PROVIDED BY:
RISER DIAGRAM
VOLTAGE DROP CALCULATION
Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved
�OB NUMBER:
SHEET
k FA -04
FIG. 69R
RETAINING
STRAP
FIG. 100
ALL THREAD ROD
NO LOCK
,..—"NUT REQ'D
ti
JA
FIG, 65
BEAM CLAMP
VIEW A—A
LOCKING THREAD
CONNECTION
FIG. 200
ADJUSTABLE RING
HANGER
TOP BEAM CLAMP HANGER
SCALE:NONE
(E) 4"
EL=14'-6"
*—
I1�WF
X CEiL!;NG
ACCESS PANEL I
WITH H !N IEGRAI_ cyv.
100.1
SALFS AREA
GYP. [BD. CEILING
1O' -O" A.r_±-.
12"WF
02
/1;
I
0
(E)4
i!i i1 I
11-1-11-q, -0 ' I --
ill
j
Z..
I— 1
I
tt
1-4
fx1
12"WI
,
-TOC-K- -R-00tittr
11
II
,
II
II!
� I I
12"WF
-1
•
•
ii
II
1-11'7..--7-71
i
',
t
t
—_� ,
PIPING PLAN
Scale:1/4"=1'-0"
0
rj
SCOPE:
1. FSI TO ADD NEW HEADS IN NEW TENENT SPACE
GENERAL NOTES:
1. ALL MATERIAL AND EQUIPMENT TO BE NEW AND UL LISTED OR FM APPROVED.
2. PIPING DIMENSIONS ARE CENTER TO CENTER EXCEPT RISER & DIMENSIONS
SHOWN THUSLY (1-6), WHICH IS END TO END.
3. PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH
NFPA PAMPHLET NO. 13, 2002 EDITION.
4. PIPING SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13, 2002 EDITION.
5. JOINING OF PIPE AND FITTINGS, THREADED AND WELDED SHALL BE IN
ACCORDANCE WITH NFPA PAMPHLET NO. 13, 2002 EDITION.
6. OWNER TO PROVIDE ADEQUATE HEAT TO PREVENT WATER IN PIPES FROM
FREEZING IN AREAS PROTECTED BY A WET PIPE SPRINKLER SYSTEM.
7. STRUCTURAL ADEQUACY OF THE BUILING TO SUPPORT THE SPRINKLER
PIPING IS THE RESPONSIBILITY OF THE OWNER AND/OR HIS STRUCTURAL ENG.
8. ALL FIRE ALARMS, WIRING AND MONITORING ARE TO BE INSTALLED BY OTHERS.
CONSTRUCTION NOTES:
1. ALL NEW PIPING TO BE IMPORT SCHEDULE 40 & DYNAFLOW.
2. ALL NEW FITTINGS TO BE IMPORT DUCTILE IRON AND GROOVED FITTINGS.
3. ARMOVERS LONGER THAN 2'-0" SHALL HAVE A HANGER.
irga
`Without Cornme its
As Rated In Red
Per The Attached Letter
nese plans have ius'F3tl reviewed by The Tukwila Fire
Pre‘.'entionni glib eat.i `or r_ o'i';1orm; nce with current t City
standards. > ,i;% ep cinoe I$ !!:i!L: ,ct to errors and
O?T1issio`.'i£ iAiK7-...;ti inti i'40i authorize vi 43iicn . of adopted
standards and o` }tr1:'lnce:'.s. i s the
The l�e,.,r1()ii.'.islji;�fl.H for
adequacy of (1,.--.sion totally with r✓C"s1Qnr.
r''_dditions, deletions or I'< [t51%(l P.o these drowitigs atter
:lis date will void this al.ceptancs rici =• m re: ti :e a
resubmittal of revised drawings for sub ieouent approval --
Final acceptance. is subject to field test and inspection by
The Tukwila Fire Prevention Bureau.
Date: W"13 Og By:Alivi 1_
FILE cC y
IUKWILA FIRE DEPARTIyiEI'3T
Please call: 575-4407
and give this job
No., OR- S- 3a s -
ani exact address for shut'
dow'i or restoration approval,
CO
—J
w
CC
c.)
0 -
DRAWING
DRAWING SYMBOLS
HYDRAULIC DESIGN INFO.
HANGER LEGEND
HEAD LEGEND
- ALARM VALVE RISER
- FLOW SWTICH RISER
1751 - DELUGE/P.A. RISER
DRY PIPE RISER
FIRE DEPARTMENT CONNECTION
.8. - WATER MOTOR GONG
D - ELECTRIC BELL
F FLEXIBLE GROOVED COUPLING
$ - RIGID GROOVED COUPLING
- THREADED PIPE COUPLING
- — - CONTROL VALVE
-� - CHECK VALVE
--f"PIPE HANGER (SEE CHART)
-+ - PIPE HANGER (SEE CHART)
( A-1 ) - WELDED PIPE TAG
0 - BRANCHLINE NUMBER
1
9-0
1
(8-10)
PIPE SIZE & LENGTH
PIPE SIZE & LENGTH(CUT)
- HYDRAULIC NODE
10'-0"AFF ELEVATION DATUM
0'-10" BOD
- CENTERLINE OF PIPE TO DECK
❑
THIS SYSTEM IS FA THIS SYSTEM IS NOT
HYDRAULICALLY DESIGNED �! HYDRAULICALLY DESIGNED
A
U -HOOK
L
"L" ROD
SPRINKLER, TYPE
MFG
MODEL
SYMBOL
ORIFICE
FINISH
CANOPY
TEMP
K -FAC
QTY
FLOW TEST
STATIC
xx
RESIDUAL
xx
GPM FLOWING
xx
DATE & TIME
xx
B
COACH SCREW ROD
N
TOGGLE NUT
RECESSED PENDENT
TYCO
TY -FRB
•
112"
CHROME
CHROME
155°
5.6
12
C
"C" CLAMP
P
HDI -P
D
TOP BEAM CLAMP W/ STRAP
R
WEDGE ANCHOR
E
EYE ROD
S
SAMMY SIDEWINDER (SWG2D)
SYSTEM DESIGN
F
FLUSH SHELL
S20
SAMMY SUPER SCREW (GST20)
REMOTE AREA
xx
DENSITY
xx
MAX. AREA/HEAD
xx
K -FACTOR
xx
xx
G
CEILING FLANGE
SX
SAMMY X -PRESS
H
SIDE BEAM BRACKET
T
TRAPEZE
J
"J" BOLT
U
UNISTRUT POST
K SHORT CLIP
TOTAL THIS SHEET
12
/
Fire Sprinklers
•
WA CL# FIRESI*988RJ
1014 North Street
Sumner, WA 98390
(253) 826-0099
email:mike@firesprinklersinc.com
PROJECT:
Stride Rite
• ■
Tukwila, WA.
1
•
) ()11 S,C, oa11
CONTRACT WITH:
Flinthills Construction
R.1 TECE
WekI L rasps must be
inspected before • •e is
hung. Do not paint piping
prior to hydrostatic test
DESIGNER:
Mike
DATE:
619108
SCALE:
As Noted
HAZARD:
OHG II
AHJ:
City of Tukwila
JOB #
1979
SHEET # FP1
�lw
0
41
NORDSTROM
Ma CO
Oiir.�
I
.i
1.
DDD O O O 0 0
O O
-
IIII
a
_
.....
iiFILI
r91
-.1■
II
117
■
111
IIIIIip--�
lar
.• u
STRIDE RITE
• 1300
LEVEL 1__...,_�=..._ -.r . EIVIER ML
ti
irga
`Without Cornme its
As Rated In Red
Per The Attached Letter
nese plans have ius'F3tl reviewed by The Tukwila Fire
Pre‘.'entionni glib eat.i `or r_ o'i';1orm; nce with current t City
standards. > ,i;% ep cinoe I$ !!:i!L: ,ct to errors and
O?T1issio`.'i£ iAiK7-...;ti inti i'40i authorize vi 43iicn . of adopted
standards and o` }tr1:'lnce:'.s. i s the
The l�e,.,r1()ii.'.islji;�fl.H for
adequacy of (1,.--.sion totally with r✓C"s1Qnr.
r''_dditions, deletions or I'< [t51%(l P.o these drowitigs atter
:lis date will void this al.ceptancs rici =• m re: ti :e a
resubmittal of revised drawings for sub ieouent approval --
Final acceptance. is subject to field test and inspection by
The Tukwila Fire Prevention Bureau.
Date: W"13 Og By:Alivi 1_
FILE cC y
IUKWILA FIRE DEPARTIyiEI'3T
Please call: 575-4407
and give this job
No., OR- S- 3a s -
ani exact address for shut'
dow'i or restoration approval,
CO
—J
w
CC
c.)
0 -
DRAWING
DRAWING SYMBOLS
HYDRAULIC DESIGN INFO.
HANGER LEGEND
HEAD LEGEND
- ALARM VALVE RISER
- FLOW SWTICH RISER
1751 - DELUGE/P.A. RISER
DRY PIPE RISER
FIRE DEPARTMENT CONNECTION
.8. - WATER MOTOR GONG
D - ELECTRIC BELL
F FLEXIBLE GROOVED COUPLING
$ - RIGID GROOVED COUPLING
- THREADED PIPE COUPLING
- — - CONTROL VALVE
-� - CHECK VALVE
--f"PIPE HANGER (SEE CHART)
-+ - PIPE HANGER (SEE CHART)
( A-1 ) - WELDED PIPE TAG
0 - BRANCHLINE NUMBER
1
9-0
1
(8-10)
PIPE SIZE & LENGTH
PIPE SIZE & LENGTH(CUT)
- HYDRAULIC NODE
10'-0"AFF ELEVATION DATUM
0'-10" BOD
- CENTERLINE OF PIPE TO DECK
❑
THIS SYSTEM IS FA THIS SYSTEM IS NOT
HYDRAULICALLY DESIGNED �! HYDRAULICALLY DESIGNED
A
U -HOOK
L
"L" ROD
SPRINKLER, TYPE
MFG
MODEL
SYMBOL
ORIFICE
FINISH
CANOPY
TEMP
K -FAC
QTY
FLOW TEST
STATIC
xx
RESIDUAL
xx
GPM FLOWING
xx
DATE & TIME
xx
B
COACH SCREW ROD
N
TOGGLE NUT
RECESSED PENDENT
TYCO
TY -FRB
•
112"
CHROME
CHROME
155°
5.6
12
C
"C" CLAMP
P
HDI -P
D
TOP BEAM CLAMP W/ STRAP
R
WEDGE ANCHOR
E
EYE ROD
S
SAMMY SIDEWINDER (SWG2D)
SYSTEM DESIGN
F
FLUSH SHELL
S20
SAMMY SUPER SCREW (GST20)
REMOTE AREA
xx
DENSITY
xx
MAX. AREA/HEAD
xx
K -FACTOR
xx
xx
G
CEILING FLANGE
SX
SAMMY X -PRESS
H
SIDE BEAM BRACKET
T
TRAPEZE
J
"J" BOLT
U
UNISTRUT POST
K SHORT CLIP
TOTAL THIS SHEET
12
/
Fire Sprinklers
•
WA CL# FIRESI*988RJ
1014 North Street
Sumner, WA 98390
(253) 826-0099
email:mike@firesprinklersinc.com
PROJECT:
Stride Rite
• ■
Tukwila, WA.
1
•
) ()11 S,C, oa11
CONTRACT WITH:
Flinthills Construction
R.1 TECE
WekI L rasps must be
inspected before • •e is
hung. Do not paint piping
prior to hydrostatic test
DESIGNER:
Mike
DATE:
619108
SCALE:
As Noted
HAZARD:
OHG II
AHJ:
City of Tukwila
JOB #
1979
SHEET # FP1